GE Energy Digital Energy Zenith Energy Commander Paralleling Switchgear Application Guide GE Energy – Digital Energy Zenith Energy Commander Paralleling Switchgear • Flexibility Introduction Increased Reliability • Increased Reliability Paralleling is an operation in which multiple power sources, usually two or more generator sets, are connected and synchronized to a common bus (same parameters in regards to frequency, phase angle, etc.). • Uninterruptible Maintenance Why Zenith Energy Commander? Systems in which part of the load is very critical may be best served by paralleling one or more generator sets. Under parallel operation all the generator sets are started at once. The first set to reach the proper parameters will assume the most critical portion of the load, with the remaining sets picking up lower priority loads. In addition, by using a load shedding application, the failure of one generator set will not interrupt power to the critical loads, as less critical loads can be shed. • Cost Savings • Scalability • Proven Experience • World-Class Global Service Zenith Energy Commanderprovides customer facilities with reliable power switching systems. Since the inception of paralleling switchgear (PSG), many successful Energy Commander installations have been supplied with a focus on providing reliability. Zenith Energy Commander has evolved and adapted to the changing technologies in engine generator design, switchgear controls and monitoring systems. It reflects GE’s continuing commitment to reliable solutions for critical power applications. Why Parallel? Information contained in this application guide is based on established industry standards and practices. It is published in the interest of assisting in the preparation of plans and specifications for medium and low voltage paralleling switchgear. Neither the General Electric Company nor any person acting on its behalf assumes any liability with respect to the use of, or for damages or injury resulting from the use of any information contained in this application guide. This guide should be considered a supplement and should be used in conjunction with the GE Switchgear medium and low voltage application guides. There are several advantages to employing PSG in an electrical design, such as flexibility, increased reliability, ease of uninterruptible maintenance and application/operation cost savings. It is because of these advantages that PSG has become one of the best choices for meeting today’s power requirements. Flexibility Paralleling power sources allows for a wide variety of choices in the generation, distribution and utilization of the system’s power. Uninterruptible Maintenance When one engine - generator set is out of service for maintenance or repair, having others synchronized on the same bus can provide the needed back-up power, should an outage occur. Cost Savings and Scalability Savings can be realized on the application when a number of smaller sets would be less expensive than one large set or when the load makes it impractical to divide into several sections, each with it’s own generator. Also, when it is anticipated that the load will grow significantly in the future, the capital investment can be reduced by starting with small sets and paralleling additional units as load increases dictate. Zenith Energy Commander Paralleling Switchgear System Applications Emergency or Standby Power > Features > Configuration Example The emergency system is used to supply power to building loads during a power failure. Paralleling switchgear controls the system transfer to generators and return back to normal sequences of operations. Generator Generator Paralleling switchgear controls the addition of load on/off generators (load add/shed). Transfers between utilities and generators occur in open transition or passive momentary closed transition (no active synchronization of sources). > Components System typically consists of paralleling switchgear product and automatic transfer switch or auto throw-over products ATS Emergency ATS Emergency > Sequence of Operation 1. Utility fails. Figure 1 Multiple Gen Sets, No Utility Transfer Control with ATS’s 2. ATS’s (or ATO’s) send start signal to PSG 3. Generators start and parallel to bus. 4. PSG Controls the ATS’s transfer to paralleled generators. (load add) 5. PSG controls optimization of generators. (shutting off and starting generators as needed) 6. PSG controls load shed operation. (shutting off loads and/or ATS/ATO devices non-critical if generators become overloaded) 7. Utility returns. 8. ATS transfers back to utility (open transition... lights blink, or momentary closed transition... lights stay on, depending how ATS is configured) 9. Generators shut down. 10. Peak shave often used to send non-emergency start to system to transfer ATS or ATO devices onto generators to “shave” load off the utility. Page 1 • TB-2103 Zenith Energy Commander Paralleling Switchgear System Applications Prime Power Parallel with Utility > Features > Features On-site prime power systems are most often used where there is no utility source available. The required electricity is generated entirely on-site, typically at facilities such as island resorts, mines, mills or other remote locations. Since utility is not available in prime power systems, ATS’s/ATO’s and utility/tie breakers are not required. > Components Generators are the only source of power. The system typically consists of PSG product with no ATS/ATO products. > Sequence of Operation 1. System enable signal causes generators to start and parallel to bus. 2. PSG controls optimization of generators. (shutting off and starting generators as needed) 3. PSG controls load shed operation. (shutting off loads non-critical if generators become overloaded) 4. PSG controls frequency of generators for clock/time correction. 5. Removing system enable signal will shutdown the generators. > Configuration Example Parallel with utility systems are utilized whenever generators are to be actively synchronized and paralleled with utility sources for short or long durations. These systems are often also used for standby use. PSG controls the generators transfer operations with the utility source(s) as well as the power management (loading controls) to direct power the appropriate direction. Transfers may occur in short duration (momentary closed transition), a somewhat longer duration (softload/unload closed transition), or a sustained duration (maintained parallel with utility). Power management in maintained parallel situations includes controlling import levels from utility, export levels to utility, or base load levels where generators are loaded to set amount disregarding the import and export contribution from utility. “Co-generation” is often used for maximizing generator efficiency with heat recovery systems. > Components System combines generators with utility sources. It typically consists of PSG product which controls the ATS/ATO operations. > Peak Shave Example Generator kW Generator Non-Purchased Power Generator OFF ON kW Demand Threshold Utility Purchased Power 8 Load Load Figure 2 Multiple Gen Sets, No Utility Transfer Control TB-2103 • Page 2 9 10 11 12 Noon 1 2 3 4 5 6 7 Time 8 Zenith Energy Commander Paralleling Switchgear System Applications Sequence of Operation 1. Utility When used for standby, the PSG operates in the same manner as the emergency standby sequence. If not used for standby, the generators remain offline when utility is not present. 2. Non-emergency start signal is sent to PSG for peak shave or exporting power to utility applications. 3. Generators start and parallel to bus and with utility. 4. PSG controls the transfer of loads off the utility onto the generators in momentary closed transition (if emergency standby is also utilized) or softload closed transition. 5. > Configuration Examples In maintained parallel with utility applications, the PSG controls the amount of import power from utility, export power to utility, or base loads the generators to a fixed amount non-dependent upon the utilitysupplied power. With emergency standby applications not maintaining paralleling with utility, the PSG in this case controls the synchronizing of generators with utility and momentary closed transition transfer onto the generator bus. 6. PSG controls optimization of generators (shutting off and starting generators as needed). 7. PSG controls load shed operation if emergency standby is also utilized. 8. Non-emergency start signal is removed. 9. PSG controls the soft unload of generators off the utility or momentary closed transition from utility if emergency standby is utilized. Generator Generator Generator Generator Utility Load Load Figure 4 Multiple Gen Sets, Utility Main Transfer Control (M) Load Load Figure 3 Multiple Gen Sets, Utility and Generator Main-Tie Transfer Control Generator Generator Utility Load Figure 5 Multiple Gen Sets, Utility and Generator Main-Tie’s Transfer Control (M-T) and Utility M-T-T-M Operations Utility Load Load Load 10. Generators shut down. Utility Generator Generator Figure 6 Multiple Gen Sets, Utility and Generator Main-Tie’s Transfer Control (M-T) and Utility M-T-M Operations Generator Utility Load Utility Load Figure 7 Single Gen Set, Utility with Gen/Utility Breaker Transfer Control Load Load Load Load Page 3 • TB-2103 Zenith Energy Commander Paralleling Switchgear Protection Schemes Standby Gen > Example – Low Voltage Gen EE Figure 8 This is a back-up power scheme for a low voltage application. Includes current, potential and control power transformers, and circuit breakers with built-in overcurrent protection. This scheme includes: EE 50/51 N/G 40 25 32 CT Typical 27/59 81 • Load Shed PT • Under/Over Voltage CPT CPT • Reverse Power PT 81 U/O • Loss of Excitation • Ground Over Current LS 25 TVSS • Under/Over Frequency • Surge Suppression (TVSS) Typical ATS • Synchronism Check ATS Emergency Emergency > Example – Medium Voltage Figure 9 Gen This is a back-up power scheme for a medium voltage application. Includes current and potential transformers and vacuum circuit breakers without overcurrent protection. This scheme includes: Gen EE EE CT CT 50/51 N/G NGR 51V 40 25 32 • Load Shed • Under/Over Voltage • Reverse Power 87 50/51 CT Typical 87 27/59 81 PT SA SA • Loss of Excitation PT 81 U/O • Ground Over Current • Instantaneous and Timed Over Current LS 25 50/51 50/51 N/G • Under/Over Frequency Typical • Differential Protection • Surge Suppression (TVSS) ATS • Synchronism Check ATS SA Emergency Emergency Example Relay Definitions 25 Synchronization – Prevents the closing of paralleling AC currents and, if required, signals governor controls to meet the desired match of voltage, frequency and phase angle. 27 Undervoltage – Operates when the AC voltage drops below a preset value. 32 Directional or Reverse Power – Operates when generator draws power from the bus vs. supplying power to the bus. This fault condition is also known as “motoring”. 40 Field – Operates upon excessive current within excitation field TB-2103 • Page 4 46 Reverse Phase or Phase Balance Current – Operates upon the reversal of the phase sequence in the polyphase currents or when the polyphase currents are imbalanced or contain negative phase sequence properties above a given value. 47 Phase Sequence Voltage – Operates upon a preset value of polyphase voltage in the desired phase sequence. 50 Instantaneous Over Current – Operates immediately upon excessive current or excessive rate of rise in current. 51 AC Time Over Current – Operates upon excessive current. 59 AC Overvoltage – Operates upon excessive AC voltage past a set value. 67 AC Directional Overcurrent – Operates on a set value of AC overcurrent in a predetermined direction. 81 Frequency – Operates when frequency frequency drops below or rises above a set value. 87 Differential – A fault detecting device which operates upon a difference in current of a given percentage or amount. Zenith Energy Commander Paralleling Switchgear Protection Schemes Parallel with Utility > Example – Low Voltage Figure 10 Exhaust This is a parallel power scheme for a low voltage co-generation application. Includes current, potential and control power transformers and circuit breakers with built-in over-current protection. This scheme includes: Utility Gen • Load Shed Gen EE 50/51 N/G 32 25 Heat Load EE 50/51 N/G 46 67 CT • Under/Over Voltage • Reverse Power 40 25 32 27/59 81 U/O 47 PT CPT Heat Recovery System CT Typical 27/59 81 PT • Negative Sequence Current CPT CPT • Negative Sequence Voltage CPT PT 81 U/O • Loss of Excitation • Ground Over Current TVSS LS 25 • Directional Over Current TVSS CPT • Under/Over Frequency Typical 25 PT • Surge Suppression (TVSS) Feeders Typical • Synchronism Check ATS • Interlock Schemes & Backup Trip Protection Emergency > Example – Medium Voltage Figure 11 This is a back-up power scheme for a medium voltage application. Includes current and potential transformers and vacuum circuit breakers without overcurrent protection. This scheme includes: Exhaust Utility Gen • Load Shed CT • Reverse Power PT 46 67 CT 50/51 N/G NGR SA 87 87 27/59 81 PT SA SA PT • Loss of Excitation 81 U/O • Ground Over Current 50/51 50/51 N/G LS 25 • Instantaneous & Timed Over Current 50/51 50/51 N/G 50/51 50/51 N/G • Directional Over Current • Differential Protection 50/51 CT Typical • Negative Sequence Voltage • Under/Over Frequency Heat Recovery System 51V 40 25 32 27/59 81 U/O 47 • Negative Sequence Current Heat Load EE CT 32 25 • Under/Over Voltage Gen EE 50/51 N/G Typical PT 25 SA Feeders Typical SA ATS • Surge Suppression (TVSS) Emergency • Synchronism Check • Interlock Schemes & Backup Trip Protection Example Legend ATS CT CPT EE Automatic Transfer Switch Current Transformer Control Power Transformers for Breakers Electrical Energy LS NGR PT SA TVSS Load Shed Neutral Grounding Resistor Potential Transformer Surge Arrestor Transient Voltage Surge Suppression Page 5 • TB-2103 Zenith Energy Commander Paralleling Switchgear Stack Configuration Guide Configuration Instructions 1. After designing a system one-line, you are now ready to layout your electrical room using the enclosed switchgear and control stacks configurator. 2. Based on system electrical requirements, choose the appropriate low voltage or medium voltage available configurations from the stack configuration guide. 3. In an effort to minimize footprint, select the nearest available Stack Number that meets breaker capacities. Use remaining space for fitting the appropriate controls as desired. The control and breakers definitions are included on the following pages. 4. Once the paralleling switchgear system has been configured, please refer to the enclosed dimension table for overall lengths, widths, depths and weights. TB-2103 • Page 6 Zenith Energy Commander Paralleling Switchgear Stack Configuration Guide 1 Legend 7 Option Notes 2 A 2 Stack Number 800-1600 Amp A B 3 B C A 800-2000 Amp 1 2 2 3 2 4 2 A 5 2 A 6 2 8 A A A B 800-2000 Amp 5000 Amp B B 32004000 Amp C 800-2000 Amp C 6 6 6 6 A A C C 800-2000 Amp D 800-2000 Amp 6 B B B 800-2000 Amp C 8 10 3 2 2 2 A C A 11 12 2 A 800-2000 Amp 13 5 4 2 7 A D 32004000 Amp 8002000 Amp 9 1 800-2000 Amp C 5000 Amp 32004000 Amp 6 2 A 8001600 Amp 2000 Amp 7 2 7 A B B B 6 B B 800-2000 Amp 8002000 Amp 800-2000 Amp A 8004000 Amp B Integrated Control/ Low Voltage UL 1558 Breaker Stacks C D A A A 800-2000 Amp 3200 Amp B 800-2000 Amp 2 A 800-1600 Amp B B B 7 2 8 A 800-2000 Amp C Low or Medium Voltage Separate Control Stacks A Compartment 8 2 3 A 800-1600 Amp A 800-2000 Amp Integrated Control/ Low Voltage UL 891 Breaker Stacks 2 4 800-1600 Amp B 8002000 Amp B C B 800-1600 Amp C 800-2000 Amp 1 C C B 800-2000 Amp B 8004000 Amp 25003000 Amp 8001600 Amp D 800-2000 Amp D 2 3 C D 8002000 Amp 800-1600 Amp D 800-2000 Amp 4 A 800-2000 Amp 6 7 8 7 A 12003000 Amp C 800-1600 Amp 5 A 12003000 Amp C E 800-2000 Amp A A 1200 Amp A 600 Amp A B B B C C B A Medium Voltage Breaker Stacks B B 12003000 Amp C C 12003000 Amp B 12003000 Amp C 1200 Amp 600 Amp Page 7 • TB-2103 Zenith Energy Commander Paralleling Switchgear Stack Configuration Guide Low or Medium Voltage Separate Control Stack Options Full Stack Description Generator Control Compartment System/Master Control Compartment Utility Transfer Control Compartment Automatic Throw-over Transfer Control Compt. Annunciator/Mimic Panel Control Compartment Remote Annunciator Control Section Comp A A A A A A Half Stack Stack 1 1 1 1 1 3 Comp A, B Stack 2 A, B A, B A, B A 2 2 2 3 NOTE: System Master control compartment should be located in an “A” compartment See suggested control compartment options for component details. Integrated Control/ Low Voltage Stack Options Description Blank Auxiliary Compartments for Controls Utility, Generator & Feeder Breaker Compartments Tie Breaker Compartments UL 1558 Up to 5000 Amps UL 1558 6000 Amps UL 891 Up to 6000 Amps Comp A B Stack 1, 2, 4 7 Comp A3 A4 Stack 8, 9 11 Comp A3 B Stack 1, 2 7, 8 B B, C B, C B, D A, C B5 B B, C B, C B, D A, C 1, 2, 3 4 5 6 7 1, 2, 3 1, 2, 3 4 5 6 7 B B, C B, C B, D 8, 9, 10 11 12 13 B3 B B, C B, C B, D 8, 9, 10 8, 9, 10 11 12 13 B B, C B, C, D B, C, D, E A, C B3 B B, C B, C, D B, C, D, E A, C 1 2, 3 4, 5 6 7, 8 1 1 2, 3 4, 5 6 7, 8 NOTES: 1. All stacks with bussing must be the same depth 2. Use 74" depths in lieu of 67" when cable sizes exceed 9100A for 3-wire systems, 6000A for 4-wire systems. All breakers are thru the door. 3. If bus-bus tie breaker is required in a stack, no other breakers are allowed 4. All breakers are thru the door type at depths of 60", use 70" depths in lieu of 60" when cable sizes exceed 9100A for 3-wire systems, 6000A for 4-wire systems 5. 22" width not available if controls are inserted 6. Stack will be limited to 2 multifunction protective relays 7. PT's are included in rear for source/transfer breakers and main buses: (2) in open delta or (3) in wye connection depending on 3 wire or 4 wire systems respectively as default (3) available if specified 8. Insulated/Isolated and compartmentalized bus options available 4000A and below Medium Voltage Stack Options Control/Auxiliary Comp Stack A 4, 5 B 6, 7, 8 B, C 2 A, B 3 A, C 8 Utility, Generator, Feeder Breaker Comp Stack A, B 1 A 2 C 3 B 5 A, C 7, 8 Tie Breaker Comp Stack B2,3 1 A, B 1 A 2 C 3 B 5 A, C 7, 8 NOTES: 1. All stacks with bussing must be the same depth 2. If figure 2 is being used for tie, then either figure 3 or 4 must be placed on one of the sides of the tie stack 3. If figure 3 is being used for tie, then either figure 2 or 4 must be placed on one of the sides of the tie stack 4. Front-draw-out PT's are included for source/transfer breakers and main buses: (2) in open delta or (3) in wye connection depending on 3 wire or 4 wire systems respectively as default (3) available if specified 5. Stack for 5KV class 100MVA only. (1) top drawout PT and (1) rear fixed PT available for source/transfer breakers Breaker & Control Compartment Definitions – Page 15 TB-2103 • Page 8 Zenith Energy Commander Paralleling Switchgear Stack Configuration Guide Stack Application Notes: 1. Dimensions and weights shown are in inches and pounds respectively. 2. Application information is based on GE’s design specification 3. All dimensions and weights are approximate and subject to change without notice. Information should be used for reference only and not used for construction until issuance of approval drawings. 4. For additional application data, please reference “switchgear” on GE’s website or contact your local sales representative. 5. Low voltage 8000A main bus or higher applications are available but will require factory assistance. Contact your local sales representative for these special applications. 6. All breaker stacks are based on utilizing electrically operated draw-out style circuit breakers. 7. Breaker stacks contain the utility breakers, generator breakers, tie breakers, and feeder breakers according to the appropriate system 1-line. 8. The UL 1558 breaker stacks are based on using GE WavePro circuit breakers. 9. The UL 891 breaker stacks are based on using GE Power Break II circuit breakers. 10. The Medium voltage breaker stacks are based on using GE Power Vac vacuum circuit breakers. 11. Generator control compartments will be required for every generator to be controlled by GE in the PSG system. 12. Master/System control compartments will be required for every PSG job paralleling multiple generators. 13. Master/System control is based on all generators paralleling onto a single main bus. Systems with tie breakers between generators are assumed to always be closed with system in manual whenever generator tie(s) are open. 16. ANN annunciator/mimic panel may be utilized for dedicated compartment display of system 1-line graphical LED display. 17. RAN remote annunciator may be utilized for duplication of PSG status and alarming indications remote from PSG. 18. When control compartments are to be inserted into breaker stacks (breaker and control cubicles), blank auxiliary compartments will be required in the breaker cubicles for housing these control compartments. 19. Dimensional information is based on NEMA 1, front and rear access, seismic zone 2, top or bottom cable entry. Contact factory for bus duct applications. 20. Operating temperatures based on 0° C up to 40° C (indoor) and -20° up to 40° C (outdoor) and elevations up to 2000m for LV and 1000m for MV. 21. Additional references: ANSI/IEEE, NEMA, NFPA, NEC, UL , IEC, CSA. 22. All cubicle sizes are based on using wiring terminal blocks for bare wire. If wire lugs are required, consider as high option layouts. 23. Door meters, CT circuits, and main DC power circuits are equipped with ring type terminal blocks and lugs. 24. Control power on Medium voltage multiple Gen. systems are (-) ground 24VDC for controls, 125VDC (48VDC optional) for breaker tripping, closing and charging and relays. 25. Control power on multiple Gen. low voltage systems are (-) ground 24VDC for controls, relays, and breaker tripping, and 120VAC for breaker closing and charging. 26. Control power on Medium voltage single Gen/utility ATO systems are (-) ground 24VDC for controls/ relays, 120VAC for breaker tripping, closing and charging (capacitive trip). (120VAC UPS when no 24VDC is available) 14. Utility transfer control compartment will be required for every utility source/breaker(s) to be controlled in PSG system. 27. Control power on low voltage single Gen/utility ATO systems are (-) ground 24VDC for controls, relays, and breaker tripping, and 120VAC for breaker closing and charging. 15. ATO control compartment is utilized for systems requiring transfer control for only 1 generator and utility source. 28. Contact factory if swing generators are required (when one (1) generator feeds more than one (1) generator breaker). Page 9 • TB-2103 Zenith Energy Commander Paralleling Switchgear Control Configuration Guide Suggested Control Component Options Option Type Analog Metering Digital Metering Logic Controller Communications Eng/Util control Protection Note 3 HMI Panel Note 10 Annunciation Notes 6,14 Lamps/Indicators Note 4 Alarm Horn Switches/Buttons/Pots Generator Control Standard AM / WM Note 1 GE 90-30 — SPMA, Note 15 Ind. Grade MFR Series — Incandescent Breaker Open/Closed — 3P/ECS/LTS/Reset/90S/65S/52S Optional VM / FM / PFM Note 1 Note 2 — AGLC/VAR-PFC, Note 15 Util.Grade Multilin Series — LED Locked Out / Drawn Out — ESTOP/86/TP/BLP Master Control Standard Optional VM/FM inc / run sync AM / WM None PQM GE 90-30 Redundant GE 90-30*** Note 13 Modbus and/or Ethernet* None SPMA/APTL Note 17 Load Shed — 5" Monochrome OIP 12" Color ACS** Incandescent LED Note 7 Note 7 Yes — AUMS/LTS/Reset/HS Note 8 52S/86/TP Relays Note 5 Trm. blocks/fuses/wire As Required As Required As Required As Required As Required As Required Annunciation Notes 6,14 Lamps/Indicators Note 4 Alarm Horn Switches/Buttons/Pots Relays Note 5 Trm. blocks/fuses/wire Utility Control Standard AM / WM Note 1 Note 9 — Note 15 Industrial Grade HMI Panel Note 10 Incandescent Bkr Open/Closed UBK,GMBK — LTS/Reset/52S As Required As Required Optional VM / FM / PFM Note 1 Note 9 — Notes 15, 16 Utility Grade — LED Locked Out/Drawn Out — I-E/TMS/RTN/PSS/YN/86/TP As Required As Required Auto Throw Over Control Standard Optional AM/WM (U&G) VM/FM/PFM Note 1 Note 1 GE 90-30 Note 2 Modbus Modbus & Ethernet AGLC/VARPFC/APTL N/A GBK-Ind.grade, UBK-Ut.grade Full Utility Grade 5" Monochrome LCD 15" color ACS Incandescent LED Bkr Open/Closed (GBK/UBK) Locked Out/Drawn Out Yes — ECS/AUMS/LTS/RESET/90S/65S/52S ESTOP/86/TP/BLP/TMS/RTN/PSS/YN As Required As Required As Required As Required Option Type Logic Controller Communications Note 13 HMI Panel Note 10 Annunciation Note 14 Lamps/Indicators Alarm Horn Switches/Buttons/Pots Relays Note 5 Trm. blocks/fuses/wire Mimic Panel Control, Note 11 Standard Optional None GE 90-30 — — — — — — Note 11 Note 11 — — LTS — As Required As Required As Required As Required As Required As Required *** Note 13 *** Note 10 *** Note 20 Option Type Analog Metering Digital Metering Logic Controller Communications Note 13 Eng/Util control Protection Note 3 Control Component Definitions – Page 15 TB-2103 • Page 10 Remote Annunciator Control, Note 12 Standard Optional None GE 90-30 — — — — Incandescent LED — — Yes — LTS/HS/Reset — As Required As Required As Required As Required Zenith Energy Commander Paralleling Switchgear Control Configuration Guide Control Application Notes 1. Based on a multifunction protective relay/digital metering, industrial grade low voltage, utility grade medium voltage (and utility parallel). 13. BMS Communications (with isolation) based on ethernet using OPC or over RS-485/422 using modbus RTU. 2. Consult factory for custom logic controller specifications. 14. Annunciator panels use green, red, amber indicators. 3. Based on protective relaying mounted in appropriate breaker compartment. For utility interconnection, the utility protective relay shall be IEEE 1547 compliant. 4. Based on breaker status indication-open/closed. GC-gen breakers, UTC-utility breakers and gen main transfer breakers. 5. Based on control relays only. Aux relays include engine running, summary alarm/shutdown, and breaker status. Additional auxiliary relays for customer use if specified may alter size. Contact factory when additional status contacts are required. 6. Up to 36 indications for annunciation per control section. 15. Consult factory for non-Woodward compatible engine generator set interface and/or digital controller requirements. 16. Parallel with utility systems will require watt transducer inclusions at breakers requiring synchronizing and load controls. 17. Consult factory for additional redundancy options for user interface panel. 18. Paralleling with utility applications will require generator controls with full stack compartments. 19. Customer supplied components can affect footprint size and need to be considered. 20. Redundant Master PLC’s will require full stack compartments. 7. System/Master breaker indications only for ties between generators or load bank breakers. 8. System includes hard-wired breaker control switches and backup switches for disabling automatic operation and starting engines. Backup hard-wired load control switches are included and footprint will increase with more than 16 load add/shed devices. 9. Utility transfer logic will be part of System/Master controller logic unless specified as remote/ATO operations. 10. Standard defaults are smallest HMI’s if not specified. 15", 19" or 42" available. 11. Based on supplying full compartment displaying of graphical system 1-line representations with (2) LED indications per device (contact factory for stack sizing). 12. Based on supplying duplicate annunciation to generator and system/master annunciation points (up to 54 points for the 28/18/12 stack) (up to 108 annunciator points for the 35/26/12 stack) (up to 144 annunciator points for the 42/26/12 stack). Dimensions Figures H" Control Stacks 1-3 90 4 28, 35, 42 Low Voltage UL 1558 Stacks 1, 4, 6, 7 90 2, 3 90 5 90 8 90 9, 12 90 10 90 11 90 12 90 13 90 Low Voltage UL 891 Stacks 1-8 90 Medium Voltage Stacks 1-6, 8 95 7 90 W" D" Weight (lbs.) 32 18, 26 35 12 1000 200 22, 30 38 30 30 40 44 30, 40 40 30, 40 60, 67, 74 67, 74 60, 67, 74 60, 70 60, 70 60, 70 60, 70 60, 70 70 3-4000 3-4000 3-4000 3-4000 3-4000 3-4000 3-4000 3-4000 3-4000 22, 30 60, 67, 74 3-4000 36 40 94 60 35-4500 2500 Page 11 • TB-2103 Zenith Energy Commander Paralleling Switchgear System HMI Ease of Use & Operations A Master HMI panel can be useful to PSG systems for user access and monitoring. The key control and monitoring functions in these systems include metering, annunciation, controlling breakers and engine generators in automatic operations as well as manual. This monitoring and control should be carefully considered when selecting which type of HMI is best suited for the operator and the facility. The greatest reliability in monitoring and control functions is realized with hardwired analog meters, switches and annunciation indicators, with very limited HMI access needs by the operator. In some cases, critical facilities may be suitable for additional system monitoring, troubleshooting and remote access ability. Operators in this case will require a more advanced Master HMI in addition to the system hard-wired meters, switches and annunciation. The Energy Commander ACS “Advanced Control System” is recommended for these cases. The Energy Commander Operator Interface Panel (OIP) is ideal for simpler systems. Since status of the system can be viewed in front of the switchgear, including all source metering, alarm, shutdown and status annunciation, the operator is not required to utilize the OIP to cycle through any screens for system control and monitoring. The user is only required to use the OIP touch panel for system testing purposes, noncritical settings and timing adjustments and limited manual control redundant to the hard-wired switches. Standard Operator Interface Panel (OIP) > Intuitive interface makes operation simple. Little or no learning curve required to operate system. > A main screen with navigation buttons and non-system critical button/switches. > System testing screen allowing the operator to manually initiate automatic system testing operations. > Generator interface settings latched into the PLC control system upon entry. > System load add/shed manual control redundant to hard-wired manual control switches in master control. > Generator optimization settings latched into PLC control system. TB-2103 • Page 12 Optional Advanced Control System (ACS) for Special Applications > Full functions of standard OIP with the addition of SCADA capabilities. > Internet capable – allows remote access via web. > Online controllable / programmable (behind customer’s own firewall). > Advanced Event Logging & Source Trending allows statistical root cause analysis. > Duplicates System & Generator Annunciation. > Remote system diagnostics. > Alarm and maintenance messaging, including predictive maintenance. > Graphical user interface. Intuitive and user-friendly. Requires NO computer experience to operate. > Password protection – capable of hundreds of levels of authority. Zenith Energy Commander Paralleling Switchgear System HMI HMI Features Feature OIP ACS Type 5" monochrome LCD 12", 15", 19" or 42" color LCD Metering — Full analog displays VM, WM, AM, KM, PFM Breaker Control — Optional Engine Settings Engine cranking, cool down Engine cranking, cool down Monitoring Engine run-time Engine run time, status, capacity, engine/breaker/ATS status and metering, 1-line source/bkr status, bkr operations, event logging, trending, communication status, navigation help, system control help, and optional engine parameters Annunciation — Full generator, Master and Utility annunciation matching, door-mounted, hard-wired annunciation Security Yes Enhanced levels Testing Manual initiated system testing Manual initiated system testing plus 7-day or 365-day built-in programmable exerciser as specified Load Add/Shed Manual load add/shed priority block push-buttons; logic with priority pass-along Manual load add/shed per load buttons, “On-the-fly” priority settings ability, load add/shed delay timers Gen Optimization Manual priority settings or run-time based Manual priority settings or run-time based with drag-drop starting/stopping points, bar graph monitoring for sequencing, on and off delay timer settings PSG Network Comm Status — Full device green/red status Internet — Optional web page serving/IP address Remote Notification — Optional e-mail ability thru internet for operator Page 13 • TB-2103 Zenith Energy Commander Paralleling Switchgear Network Architecture Sample Control Network • Modbus Communications with any Engine • Configurable for BMS via RS-485, Modbus, RTU or Ethernet EGD • 256 Kb PLC Bus Advanced Control System (ACS) (Optional) • ACS Optional Remote Stations • Generator Load Share Network • Start Signals and Load Add/Shed Hard-wired with Backup Switches Hub Intranet/ Internet Operator Interface Panel (OIP) To BMS Annunciator Lights Master Programming Logic Controller Master Control Annunciator Lights Generator Programmable Logic Controller Breaker Protective Relay Breaker Metering Engine Control Other Generators Breaker Generator Breaker & Control Emergency Start Signal Automatic Transfer Switch (ATS) Uninterruptible Power Supply (UPS) Breaker & Control Compartment Definitions – Page 15 TB-2103 • Page 14 10 Mbps Ethernet Modbus Control Wiring Genius SNP Load Share Network Generator Zenith Energy Commander Paralleling Switchgear Definitions Breaker Compartment Definitions Control Component Definitions Utility Compartment Breaker directly fed from utility source. 86 Lockout Relay 52S Breaker Control 65S Speed Adjustment 90S Voltage Adjustment AGLC Generator Loading Control Utility Tie Breaker that ties utility sources together. AM Ammeter APTL Power Transfer Control Generator Tie Breaker that ties generator sources together. AUMS Automatic/Manual Selector BLP Base-Load Adjustment ECS Engine Control ESTOP Emergency Stop FM Frequency Meter HS Horn Silence IEP Import/Export Control LTS Light Test PFM Power Factor Meter PQM Power Quality Meter PSS Peak Shave Selector RESET Alarm/Shutdown Reset Button RTN Return to Normal Selector SPMA Automatic Synchronizer TMS Transition Mode Selector TP Test Plug Generator Compartment Breaker directly fed from generator source. Tie Compartment Breaker in-between source breakers. Generator Main Breaker that ties generator and utility sources together and used for transfer control between sources. Feeder/Distribution Compartment Breaker directly feeding load or feeding a device that has mechanical interlock / separation of sources. Control Compartment Definitions Master/System Used for controlling the paralleling of generators, generator optimization, load add/shed, system status annunciation, user HMI, and when local transfer control is required since remote ATS’s or similar control devices are not available. Generator Used when needed to start/stop generator sources, control the voltage and speed and provide annunciation of engine and generator status. Utility Transfer Used for loading control when softload/unload transfers between utility sources and generator sources are required in an emergency standby system and provides transfer devices status annunciation. Also used in maintained parallel with utility systems for controlling power management. Mimic Panel Used when needed to display system one line status of generator sources, utility sources and all distribution and transfer devices. VAR/PFC Reactive Power / Power Factor Control VM Volt Meter WM Watt Meter WT Watt Transducer YN Bypass to Normal Selector Annunciator Panel Used typically remote for annunciation of system status conditions. Page 15 • TB-2103 Zenith Energy Commander Paralleling Switchgear System Example One Line System Design • Parallel with Utility System Exhaust • Co-Generation Application with Daily Peak Shave Operation for Limiting Utility Power Import Heat Load Utility Generator Generator Heat Recovery System Description • 2 Generators Paralleling with Heat Recovery System • 1 Utility Source Feeders • 8 Feeders to Facility Load • Low Voltage Parallel with Utility Protection Scheme Switchgear Stack Layout • 1 Gen Control & Breaker Stack for Each Generator Set • Master Control & Gen-Main Breaker in One Stack • 8 Feeder Breakers in Two Stacks • Utility Control and Breaker in Stack To BMS Generator 1 Control Generator 2 Control Master Control Generator 2 Generator Breaker Generator Breaker Generator Main Breaker Feeder Breaker Feeder Breaker Feeder Breaker Feeder Breaker Feeder Breaker Feeder Breaker Feeder Breaker Feeder Breaker Load Load Utility Utility Control Utility Breaker Generator 1 Control Interconnections Power Interconnections Breaker & Control Compartment Definitions – Page 15 TB-2103 • Page 16 Zenith Energy Commander Paralleling Switchgear System Example Implementation 1 3 2 2 4 7 1 5 6 9 8 Outside GE Power Breakers 1 2 3 4 5 6 7 8 9 GE Multilin Protective Relays Annunciator Panels Metering GE Fanuc Advanced Control System (ACS) Control Switches & Breaker Status Indicators Utility Feeder Tie Generator 2 Inside 1 Engine Generator Controller 2 GE Fanuc Programmable Logic Controller (PLC) 3 Wire Hiding Raceways, Relays, Terminal Blocks and Power Supply 3 Breaker & Control Compartment Definitions – Page 15 1 Page 17 • TB-2103 Contact Us We protect and connect the world’s ensure critical equipment to safe, reliable power Assembled in the USA GE Energy – Digital Energy 830 W 40th Street, Chicago, IL 60609 USA 800 637 1738 www.gepowerquality.com Information subject to change without notice. Please verify all details with GE. © 2010 General Electric Company All Rights Reserved TB-2103 (10/10)