B Bleed Sensor Under-floor to Wall Installation

advertisement
EBTRON
Bleed Airflow Sensor
a measurable difference!
Installation Guide for Underfloor/Wall Mount Kit
Bleed Airflow Sensor Thermal Dispersion Airflow Measurement Technology
Bleed Airflow Sensor
Installation Guide with
Underfloor/Wall Mount Kit
Models GB1, HB1
Bleed Airflow Sensor
Underfloor/Wall Mount Kit (Part number 800-1260)
Document Name: IG_GB_UF_WALL_P1A
Bleed Airflow Sensor with Underfloor/Wall Mount Kit Document Number 930‐0095UW EBTRON • 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com EBTRON
®
BLEED AIRFLOW SENSOR INSTALLATION
with Underfloor/Wall Mount Kit
a measurable difference!
Table of Contents 1 OVERVIEW .................................................................................................................................................................. 3 2 PREPARATION FOR INSTALLATION ............................................................................................................................. 4 3 BLEED SENSOR UNDERFLOOR/WALL MOUNT KIT INSTALLATION ............................................................................. 4 List of Figures Figure 1. Bleed Airflow Sensor and Underfloor/Wall Mount Installation Kit Components .................................................. 3 Figure 2. Typical Application, Bleed Airflow Sensor and Underfloor/Wall Mount Installation Kit ....................................... 3 IG_GB_UF_WALL_P1A 2
EBTRON • 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com
EBTRON
®
BLEED AIRFLOW SENSOR INSTALLATION
with Underfloor/Wall Mount Kit
a measurable difference!
1
OVERVIEW This document provides the instructions necessary to install the Bleed Airflow Sensor when supplied with the Underfloor/Wall mounting kit shown in Figures 1 and 2. Figure 2 shows installation details for the underfloor/wall mounting kit for underfloor systems. The bleed sensor requires a 3 to 3.5 inch (76.2 to 88.9 mm) opening. The opening is covered by the stainless steel face plate and the protective screen provided. The plate should be secured and sealed to the wall. A
B
C
Label Qty. Description
4 in. x 4 in., 304 stainless steel face plate with
A
1
protective mesh screen. Accepts 0.75 in. (19.05 mm) NPT
male pipe or fitting.
BS
B
1
0.75 in. (19.05 mm) NPT male x 0.5 in. (12.7
mm) NPT reducer fitting.
C
1
0.5 in. (12.7 mm) NPT male x 0.5 in. (12.7 mm)
NPT female right angle fitting.
BS
1
Bleed sensor assembly.
D
1
0.5 in. (12.7 mm) NPT male x 0.5 in. (12.7 mm)
NPT x 8 in. (203.2 mm) pipe.
D
Figure 1. Bleed Airflow Sensor and Underfloor/Wall Mount Installation Kit Components Plenum rated cable
to transmitter.
2.25 in
(57.2 mm)
Block or stud for sensor
housing mounting
(size for wall thickness).
IG_GB_UF_WALL_P1A Drill1.0 in. (25.4 mm)
hole through floor.
Seal hole after
installing tube.
Figure 2. Typical Application, Bleed Airflow Sensor and Underfloor/Wall Mount Installation Kit
EBTRON • 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com
3 EBTRON
®
BLEED AIRFLOW SENSOR INSTALLATION
with Underfloor/Wall Mount Kit
a measurable difference!
2
PREPARATION FOR INSTALLATION a.
Determine the specified location for the Bleed Airflow Sensor as indicated on the engineer's plans. Ensure that the cable supplied with the sensor is of sufficient length to reach the planned transmitter installation site. It is recommended that the sensor be installed first to ensure that the included cable will reach the transmitter after routing and securing the cable. WARNING !
b.
Do not place the protective screen in an expected high traffic area since it protrudes approximately 1‐3/8 inches above the mounting surface. Carefully open the Bleed Airflow Sensor and Underfloor/Wall Mount Installation Kit packages and inspect for damage. If damage is noted, immediately file a claim with carrier. 3
BLEED SENSOR UNDERFLOOR/WALL MOUNT KIT INSTALLATION The following paragraphs detail installation of the bleed airflow sensor with the underfloor/wall mount installation kit. Figure 2 shows typical Bleed Airflow Sensor installation detail for the Underfloor/Wall Mounting kit. The bleed sensor requires a 3 to 3.5 inch (76.2 to 88.9 mm) opening in the wall in a suitable (not high traffic) location. The opening is covered by the stainless steel face plate and the protective screen provided. The plate should be secured and sealed to the wall mounting surface. a.
Orient the bleed sensor so that the airflow directional arrow label points up away from the floor (flow is typically from the normally higher pressure underfloor plenum side to the lower pressure wall side of the installation). b.
Drill a 1.0 inch (25.4 mm) hole through the base wall sole plate and floor where the bleed sensor will be mounted so that when mounted, the end of the tube protrudes slightly into the floor plenum. c.
Install tubing as shown. d.
Secure the bleed sensor housing (BS) to a support beam or other suitable bracket so that the base of the sensor is approximately 2.25 inches (57.2 mm) from the interior wall surface (room side).Install tubing as shown. e.
The supplied shield (or equivalent) must be used to protect the Bleed Sensor opening. Do not place in expected high traffic areas since the protective screen protrudes approximately 1‐3/8 inches from the wall surface. In addition, prevent water carry over into the sensor in all applications. f.
Route the plenum rated cable supplied to the Ebtron transmitter. g.
For improved accuracy, engage the Field Adjust Wizard feature on the transmitter as outlined in the Transmitter technical manual (under separate cover). IG_GB_UF_WALL_P1A For any application specific installation questions, concerns or assistance, please contact the Ebtron Applications team at 800.2EBTRON (800. 232‐8766). 4
EBTRON • 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com
Download