GENERAL REQUIREMENTS SU ASTM A36 ANGLES & CHANNELS ASTM A36 RECTANGULAR HSS (TUBES) ASTM A500, GRADE B BOLTS ASTM A325 N, UON ANCHOR RODS ASTM F1554, Fy=36ksi, UON THREADED RODS ASTM A36 WELDING ELECTRODES E70, SEE SPECIFICATIONS FOR CVN REQUIREMENTS PA H. SI-2) THE SPECIAL INSPECTOR SHALL BE A QUALIFIED (LICENSED) PERSON WHO SHALL PROVIDE WRITTEN DOCUMENTATION TO THE BUILDING OFFICIAL DEMONSTRATING HIS OR HER COMPETENCE AND RELEVANT TRAINING OR EXPERIENCE TO THE SATISFACTION OF THE BUILDING OFFICIAL. EXPERIENCE SHALL BE FOR SPECIAL INSPECTION OF THE PARTICULAR TYPE OF CONSTRUCTION OR OPERATION REQUIRING SPECIAL INSPECTION. SI-3) THE FOLLOWING WORK REQUIRES STRUCTURAL TESTS AND/OR INSPECTIONS. FOR SPECIFIC REQUIREMENTS OF STRUCTURAL TESTS, SEE THE GENERAL NOTES, UON. SIMPSON STRONG-BOLT 2 IN NORMAL-WEIGHT CONCRETE ANCHOR MINIMUM TORQUE TEST Hnom DIAMETER HOLE DEPTH VALUE (FT-LBS) 1 7/8" 2" 30 3/8" 2 3/4" 3" 60 1/2" 5 1/8" 5 3/8" 90 5/8" 5 3/4" 6" 150 3/4" C. D. D O FES S ION PR A TI N D. FA L EY G. CD-9) STRUCTURAL COMPONENTS ARE NOT DESIGNED FOR VIBRATING EQUIPMENT. MOUNT VIBRATING EQUIPMENT ON VIBRATION ISOLATORS. HILTI KWIK BOLT TZ IN NORMAL-WEIGHT CONCRETE ANCHOR MINIMUM TORQUE TEST Hnom DIAMETER HOLE DEPTH VALUE (FT-LBS) 2 5/16" 2 5/8" 25 3/8" 2 3/8" 2 5/8" 40 1/2" 4 7/16" 4 3/4" 60 5/8" 5 9/16" 5 3/4" 110 3/4" NO. 4833 T A ER GINE EN CD-5) WIND LOAD DESIGN DATA: N/A TEST 10% OF ANCHORS, UON. IF ANY ANCHOR FAILS TESTING, TEST ALL ANCHORS OF THE SAME TYPE NOT PREVIOUSLY TESTED UNTIL 20 CONSECUTIVE ANCHORS PASS. FIELD TESTS SHALL BE EITHER TENSION TESTS OR TORQUE TESTS, AS REQUIRED FOR THE SPECIFIC ANCHOR TYPE. TENSION TESTS: APPLY TEST LOADS TO ANCHORS WITHOUT REMOVING THE NUT IF POSSIBLE. IF NOT, REMOVE NUT AND INSTALL A THREADED COUPLER TO THE SAME TIGHTNESS AS THE ORIGINAL NUT USING A TORQUE WRENCH. REACTION LOADS FROM TEST FIXTURES MAY BE APPLIED CLOSE TO THE ANCHOR BEING TESTED, PROVIDED THE ANCHOR IS NOT RESTRAINED FROM WITHDRAWING BY THE FIXTURES. TO BE ACCEPTABLE, ANCHORS SHALL HAVE NO OBSERVABLE MOVEMENT AT THE APPLICABLE TEST LOAD (OBSERVABLE MOVEMENT IS DEFINED AS THE WASHER UNDER THE NUT BECOMING LOOSE). TORQUE TESTS: TO BE ACCEPTABLE, THE APPLICABLE TEST TORQUE MUST BE REACHED WITHIN ONE-HALF TURN OF THE NUT. TEST EQUIPMENT IS TO BE CALIBRATED BY AN APPROVED TESTING LABORATORY IN ACCORDANCE WITH STANDARD RECOGNIZED PROCEDURES. FIELD TESTING SHALL BE DONE IN THE PRESENCE OF THE PROJECT INSPECTOR. TESTING SHOULD OCCUR A MINIMUM OF 24 HOURS AFTER INSTALLATION OF THE SUBJECT ANCHOR. SI-1) SPECIAL INSPECTIONS SHALL BE PERFORMED BY A SPECIAL INSPECTOR PER CBC SECTIONS 1704 AND 1705. THE SPECIAL INSPECTOR SHALL BE EMPLOYED BY THE OWNER AND NOT BY THE CONTRACTOR OR ANY OTHER PERSON RESPONSIBLE FOR THE WORK. H E. F. CD-8) DISTRIBUTE THE MAXIMUM LOAD HUNG FROM ANY STRUCTURAL MEMBER FOR MEP DUCTWORK, PIPING ETC OVER THE MEMBER’S TRIBUTARY AREA IN A WAY THAT THE DESIGN SUPERIMPOSED DEAD LOADS LISTED IN CONTRACT DOCUMENTS ARE NOT EXCEEDED. THE CONTRACTOR SHALL COORDINATE THE LOADS OF ALL TRADES AND PROVIDE ADDITIONAL SUPPORT OR DISTRIBUTION FRAMING AS REQUIRED TO ACHIEVE THE ALLOWABLE LOAD DISTRIBUTION. SI SPECIAL INSPECTIONS AND STRUCTURAL TESTING ST A. B. CD-2) RISK CATEGORY: III SCHOOL CD-7) IN CASES WHERE THE CONTRACTOR DETERMINES THAT SUSPENDED OR FLOOR MOUNTED MEP EQUIPMENT LOADS EXIST WHICH EXCEED DESIGN LOADS INDICATED ON CONTRACT DOCUMENTS, CONTRACTOR SHALL SUBMIT LOAD DATA TO DESIGN PROFESSIONALS FOR REVIEW PRIOR TO PROCEEDING WITH WORK. CONCRETE SLAB PA-5) FIELD TESTING OF POST-INSTALLED ANCHORS IS REQUIRED, UON. TEST INSTALLED ANCHORS IN ACCORDANCE WITH THE FOLLOWING: 2013 CALIFORNIA BUILDING CODE (CBC) 1.0 2.15 g 0.79 g 1.72 g 1.03 g D E 1.0 2.5 STRUCTURAL STEEL POST-INSTALLED ANCHORS PA-4) SPECIAL INSPECTION IS REQUIRED FOR ALL POST-INSTALLED ANCHOR INSTALLATIONS, UON. D. CD-6) SEISMIC LOAD DESIGN DATA: COMPONENT IMPORTANCE FACTOR (Ip) Ss S1 SDS SD1 SITE CLASS SEISMIC DESIGN CATEGORY SEISMIC RESPONSE COEFFICIENT (ap) RESPONSE MODIFICATION FACTOR (Rp) SU-2) FOR COMPONENTS THAT REQUIRE ENGINEERING BY THE CONTRACTOR, PROVIDE A NOTE ON EACH SHOP DRAWING, WRITTEN AND SIGNED BY THE SUPPLIER' S ENGINEER, INDICATING THAT THE SHOP DRAWING IS IN CONFORMANCE WITH THE CALCULATIONS OF THE CONTRACTOR' S ENGINEER. SU-3) THE FOLLOWING ITEMS REQUIRE SUBMITTALS FOR STRUCTURAL REVIEW PA-3) DRILLED HOLES FOR POST-INSTALLED ANCHORS SHALL BE LOCATED TO AVOID CUTTING OR DAMAGING EXISTING REINFORCING BARS, UNLESS OTHERWISE NOTED OR APPROVED BY THE ENGINEER. DETERMINE EXISTING REINFORCING LOCATIONS BY NON-DESTRUCTIVE MEANS. WHERE SPECIFICALLY NOTED ON DRAWINGS, SCAN (X-RAY OR SIMILAR) EXISITNG CONCRETE TO LOCATE EXISTING REBAR PRIOR TO DRILLING. OTHERWISE, NON-DESTRUCTIVE MEANS MAY INCLUDE DRILLING WITH ROTARY DRILL, AND STOPPING DRILLING IF REBAR IS ENCOUNTERED. CD-1) PERFORM ALL CONSTRUCTION IN CONFORMANCE WITH THE BUILDING AND DESIGN CODES REFERENCED WITHIN THESE DOCUMENTS. THE PROJECT DOCUMENTS REFER TO THE FOLLOWING CODES AND STANDARDS, UON: CD-4) SNOW LOADS: N/A EXPANSION ANCHOR FASTENED PART CONCRETE SUBSTRATE SC-6) ALL WELDING SHALL CONFORM TO THE REQUIREMENTS OF THE STRUCTURAL WELDING CODE, ANSI/AWS D1.1, LATEST EDITION. ALL WELD SIZES SHALL BE THE LARGER OF THE SIZE REQUIRED BY CONNECTION FORCES, THE MINIMUM SIZE PER ANSI/AWS D1.1, OR 3/16 INCH MINIMUM FILLET WELD UON. ANY WELD SIZES SHOWN ON THE DESIGN DRAWINGS ARE CONSIDERED EFFECTIVE WELD SIZES AND SHALL BE INCREASED IN ACCORDANCE WITH AWS AS REQUIRED BY GAPS OR SKEWS BETWEEN COMPONENTS. C. 100 PSF THE STRUCTURAL ENGINEER SHALL RETURN, WITHOUT COMMENT, SUBMITTALS WHICH THE CONTRACTOR HAS NOT STAMPED OR WHICH DO NOT MEET THE ABOVE REQUIREMENTS. THE STRUCTURAL ENGINEER' S REVIEW OF SUBMITTALS SHALL BE FOR GENERAL CONFORMANCE WITH THE DESIGN INTENT. NO WORK SHALL BE STARTED WITHOUT SUCH REVIEW. SS-5) FIELD MODIFICATION OF STRUCTURAL STEEL IS PROHIBITED WITHOUT PRIOR APPROVAL OF THE ARCHITECT AND STRUCTURAL ENGINEER. CD CODES AND DESIGN CRITERIA CD-3) LIVE LOADS: FLOOR ANCHOR EMBEDMENTS BELOW ARE TO BE USED WHEN EXPLICITLY SPECIFIED IN THE STRUCTURAL DRAWINGS. FOR LOCATIONS WHERE TENSION TEST VALUES ARE NOT SPECIFIED IN THE DRAWINGS, CONSULT WITH THE SER. 6. 7. 8. THE SHOP DRAWING IS REQUESTED. THE SHOP DRAWING IS BASED ON THE LATEST DESIGN. THE ARCHITECT' S AND STRUCTURAL ENGINEER' S COMMENTS FROM ANY PREVIOUS SUBMITTALS ARE ADDRESSED. THE WORK IS COORDINATED AMONG ALL CONSTRUCTION TRADES. REVISIONS FROM PREVIOUS SUBMITTALS ARE CLEARLY MARKED BY CIRCLING OR CLOUDS. SUBMITTAL IS COMPLETE. SUBMITTAL DOES NOT INCLUDE SUBSTITUTION REQUEST SUBMITTAL SHALL INCLUDE A STAMP INDICATING PROJECT NAME AND LOCATION, SUBMITTAL NUMBER, SPECIFICATION SECTION NUMBER. S GR-13) THE CONTRACTOR SHALL VERIFY ALL OPENING SIZES AND LOCATIONS WITH OTHER DISCIPLINES. THE DRAWINGS DO NOT SHOW ALL OPENINGS REQUIRED. ADDITIONAL OPENINGS, BLOCKOUTS AND SLEEVES MAY BE REQUIRED BY OTHER DISCIPLINES AND SHALL BE CONSTRUCTED USING THE TYPICAL DETAILS AND/OR THE CRITERIA INDICATED ON THE DRAWINGS. OPENINGS REQUIRED BUT NOT SHOWN ON THE STRUCTURAL DRAWINGS MUST BE APPROVED BY THE STRUCTURAL ENGINEER. B. SS-4) SHOW ALL COPES, HOLES, OPENINGS AND MODIFICATIONS REQUIRED IN STRUCTURAL STEEL MEMBERS FOR ERECTION OR THE WORK OF OTHER TRADES ON THE SHOP DRAWINGS FOR APPROVAL BY THE ARCHITECT AND STRUCTURAL ENGINEER. PA-2) INSTALL POST-INSTALLED ANCHORS IN ACCORDANCE WITH THE APPLICABLE ICC-ES REPORT AND THE MANUFACTURER'S RECOMMENDATIONS. GR-12) THE CONTRACTOR SHALL VERIFY THAT CONSTRUCTION LOADS DO NOT EXCEED THE CAPACITY OF THE STRUCTURE AT THE TIME THE LOAD IS APPLIED. 4. 5. USE OF CARBON STEEL EXPANSION ANCHORS IS LIMITED TO DRY, INTERIOR LOCATIONS. USE STAINLESS STEEL EXPANSION ANCHORS AT EXTERIOR, WEATHER-EXPOSED, OR DAMP LOCATIONS. SS-3) SPLICES SHALL BE ALLOWED ONLY AT LOCATIONS SPECIFICALLY INDICATED ON THE STRUCTURAL DRAWINGS UNLESS APPROVED OTHERWISE BY THE SER IN WRITING. GR-8) ONLY USE DIMENSIONS INDICATED ON THE DRAWINGS. DO NOT SCALE DRAWINGS. GR-11) THE CONTRACTOR SHALL PROTECT EXISTING FACILITIES, STRUCTURES AND UTILITIES FROM DAMAGE. SIMPSON STRONG-BOLT 2 (ICC-ES REPORT ESR-3037) SS-2) WHERE NO CAMBER IS INDICATED, FABRICATE BEAMS SO THAT ANY NATURAL CAMBER IS UPWARD AFTER ERECTION. GR-7) APPLY DETAILS, SECTIONS, AND NOTES ON THE DRAWINGS WHERE CONDITIONS ARE SIMILAR TO THOSE INDICATED BY DETAIL, DETAIL TITLE OR NOTE. GR-10) CENTERLINES OF FRAMING MEMBERS COINCIDE WITH COLUMN CENTERLINES, UON. 1. 2. 3. HILTI KWIK BOLT TZ (ICC-ES REPORT ESR-1917) L MISCELLANEOUS PLATES PA-1) POST-INSTALLED ANCHORS INCLUDE EXPANSION ANCHORS, SCREW ANCHORS, EPOXY ANCHORS/DOWELS, AND POWDER-ACTUATED FASTENERS. GR-9) ASSUME EQUAL SPACING BETWEEN ESTABLISHED DIMENSIONS, IF NOT INDICATED ON DRAWINGS. PLOTTED ON: 7/20/2016 11:15:37 AM © THORNTON TOMASETTI, INC. 2013 C:\Scratch\U16102_Central_R15_gtriplitt.rvt MATERIAL A UC T UR N TE R O F C A L I FO R IA GR-6) IN CASES OF CONFLICT BETWEEN DRAWINGS AND OTHER DISCIPLINES OR EXISTING CONDITIONS, CONTRACTOR SHALL NOTIFY THE DESIGN PROFESSIONALS AND OBTAIN CLARIFICATION PRIOR TO BIDDING AND PROCEEDING WITH WORK. SHAPE EXPANSION ANCHORS SHALL BE EITHER ONE OF THE FOLLOWING, UON: S GR-5) THE CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND CONDITIONS AND COORDINATE WITH THE STRUCTURAL DRAWINGS, ARCHITECTURAL DRAWINGS, DRAWINGS FROM OTHER CONSULTANTS, PROJECT SHOP DRAWINGS AND FIELD CONDITIONS. A. ER E GR-4) THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE DESIGN, INSTALLATION, AND REMOVAL OF TEMPORARY BRACING AND CONSTRUCTION SUPPORTS, FOR NEW AND EXISTING STRUCTURES, AS NECESSARY TO COMPLETE THE PROJECT. NO PORTION OF THE PROJECT WHILE UNDER CONSTRUCTION IS INTENDED TO BE STABLE IN THE ABSENCE OF THE CONTRACTOR’S TEMPORARY SUPPORTS AND BRACES. CONTRACTOR SHALL RETAIN A STRUCTURAL ENGINEER LICENSED IN THE STATE IN WHICH THE PROJECT IS LOCATED TO DESIGN TEMPORARY BRACING AND CONSTRUCTION SUPPORTS. SS-1) STEEL MATERIALS: SU-1) THE CONTRACTOR IS TO REVIEW EACH SUBMITTAL PRIOR TO FORWARDING TO ARCHITECT AND STRUCTURAL ENGINEER. THE CONTRACTOR IS TO STAMP EACH SUBMITTAL VERIFYING THAT THE FOLLOWING IS ADDRESSED: JU GR-3) THE CONTRACTOR IS RESPONSIBLE FOR THE STABILITY OF THE STRUCTURE UNTIL THE CONSTRUCTION OF THE STRUCTURE REACHES ITS FINAL CONDITION. PA-6) EXPANSION ANCHORS SUBMITTALS REG IST GR-2) THE CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF THE STRUCTURAL WORK WITH THE ARCHITECTURAL, CIVIL, MEP CONTRACT DOCUMENTS, AS WELL AS ANY OTHER APPLICABLE TRADES. SS STRUCTURAL STEEL HOLE DEPTH GR-1) AS USED IN THESE GENERAL NOTES: "DRAWINGS" MEANS THE LATEST STRUCTURAL DESIGN DRAWINGS, UON. "SPECIFICATIONS" MEANS THE LATEST PROJECT SPECIFICATIONS, UON. “CONTRACT DOCUMENTS” IS DEFINED AS THE DESIGN DRAWINGS AND THE SPECIFICATIONS “SER” IS DEFINED AS THE STRUCTURAL ENGINEER OF RECORD FOR THE STRUCTURE IN ITS FINAL CONDITION. “DESIGN PROFESSIONALS” IS DEFINED AS THE OWNER’S ARCHITECT AND SER. “MEP” INCLUDES, BUT IS NOT LIMITED TO MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION. “CONTRACTOR” IS DEFINED TO INCLUDE ANY OF THE FOLLOWING: GENERAL CONTRACTOR AND THEIR SUBCONTRACTORS, CONSTRUCTION MANAGER AND THEIR SUBCONTRACTORS, STRUCTURAL STEEL FABRICATOR OR STRUCTURAL STEEL ERECTOR. “BASE BUILDING STRUCTURE” IS DEFINED AS THE STRUCTURAL FRAME DESIGNED BY THORNTON TOMASETTI. “STRUCTURE IN ITS FINAL CONDITION” MEANS ALL STRUCTURAL ELEMENTS SHOWN ON THE STRUCTURAL CONTRACT DOCUMENTS ARE INSTALLED AND COMPLETELY CONNECTED AND INSPECTED WITH NO OUTSTANDING NON-COMPLIANCE ISSUES. Hnom GR POST-INSTALLED ANCHORS STRUCTURAL STEEL MATERIALS AND FABRICATION, PER AISC 360, CHAPTER N (SEE NOTE SI-4) WELDING: STRUCTURAL STEEL , PER AISC 360, CHAPTER N (SEE NOTE SI-4) SI-4) IF APPROVED BY THE BUILDING OFFICIAL, STRUCTURAL STEEL AND WELDING INSPECTIONS MAY BE PERFORMED BY FABRICATOR/ERECTOR QUALITY CONTROL PERSONNEL. REV. ISSUE DATE Hnom IS MEASURED FROM FACE OF CONCRETE SUBSTRATE TO THE END OF THE BOLT. CONTRACTOR SHALL PROVIDE ANCHORS WITH SUFFICIENT TOTAL LENGTH FOR THE SPECIFIED EMBEDMENT LENGTH, THICKNESS OF FASTENED PART, WASHER AND NUT. PA-7) EPOXY ANCHORS AND DOWELS A. EPOXY SHALL BE EITHER ONE OF THE FOLLOWING, UON: HILTI HIT-HY 200 (ICC-ES REPORT ESR-3187) HILTI HIT-RE 500-SD (ICC-ES REPORT ESR-2322) SIMPSON SET-XP (ICC-ES REPORT ESR-2508) B. RODS EMBEDDED IN EPOXY SHALL BE CARBON STEEL THREADED RODS PER THE EPOXY MANUFACTURER'S ICC-ES REPORT. FOR HILTI HIT-HY 200 EPOXY, HILTI HIT-Z ANCHOR RODS MAY BE SUBSTITUTED FOR THREADED RODS AT CONTRACTOR'S OPTION. C. ANCHOR EMBEDMENT AND TENSION TEST VALUES BELOW ARE TO BE USED WHEN EXPLICITLY SPECIFIED IN THE STRUCTURAL DRAWINGS. FOR LOCATIONS WHERE TENSION TEST VALUES ARE NOT SPECIFIED IN THE DRAWINGS, CONSULT WITH THE SER. LIBRARY BOOKSTACK RELOCATION SUMMER 2016 EPOXY ANCHORS IN NORMAL-WEIGHT CONCRETE (3000 PSI MIN) D. E. F. G. H. I. THREADED ROD DIAMETER (IN) EMBEDMENT (IN) 3/8 1/2 5/8 3/4 7/8 3 4 5 6 7 TENSION TEST VALUE (LBS) HILTI HIT-HY 200 2500 4480 7030 10180 11710 HILTI HIT-RE 500-SD 1230 2110 3170 4450 4720 SIMPSON SET-XP HUMBOLT STATE UNIVERSITY (BLDG 90) 1700 2600 3450 4440 5540 TITLE GENERAL NOTES TESTING OF EPOXY DOWELS AT JOINTS BETWEEN NEW AND EXISTING SLABS-ON-GRADE IS NOT REQUIRED. TESTING SHALL OCCUR AFTER EPOXY HAS CURED, AS PER MANUFACTURER'S RECOMMENDATIONS. OVERHEAD AND/OR CONSTANT TENSION EPOXY ANCHOR INSTALLATIONS NOT SHOWN ON THE DRAWINGS SHALL NOT BE PERMITTED UNLESS EACH CONDITION IS REVIEWED AND APPROVED IN WRITTING BY SER. EPOXY ANCHORS SHALL BE INSTALLED IN CONCRETE HAVING A MINIMUM AGE OF 21 DAYS AT TIME OF ANCHOR INSTALLATION. INSTALLATION AND INSPECTION OF EPOXY ANCHORS SHALL COMPLY WITH ACI 318-11 APPENDIX D SECTIONS D.9.2.2 AND D.9.2.4. FOR USES OF EPOXY DOWELS NOT EXPLICITLY SPECIFIED IN THE STRUCTURAL DRAWINGS, CONTACT THE SER. PROJECT NO: SHEET NUMBER U16102.00 SCALE: As indicated DRAWN BY: NK CHECKED BY: S1 JDF DATE: IFB #PW16-1, Addendum #2, Exhibit S, Page 1 of 2 7/20/16 © Copyright Thornton Tomasetti, Inc. 2013 3" MIN 12" MAX UNISTRUT P1000 AS REQUIRED 1" (E) POST 1/2" DIA A307 BOLT W/ STD WASHER 2" UNISTRUT P1068 FITTING PL 1", ASTM A36 5" 5" (E) POST 6" MAX 7" PL 1", ASTM A36 (E) POST TURNBUCKLE SHIM AS REQUIRED AT BOLT LOCATIONS HSS2X2X1/4 7" HSS2X2X1/4 BENT PL 1/4"X1 3/4" WIDE 1/4" DIA. BOLT, TYP TOP, BOTT & CENTER OF (N) POST 3/8" DIA THREADED ROD 3/16 2" 3/16 1" (E) SHELF 3/8" DIA SIMPSON TORQCUT ANCHOR (4" MIN EMBED), TYP 1/2" DIA A307 BOLT W/ STD WASHER BASEMENT BENT PL 1/4"X1 3/4" WIDE 3" = 1'-0" 3" = 1'-0" 3 THREADED ROD BRACE CONNECTION 3" = 1'-0" S JU REG IST TYPICAL POST TO POST CONN N D. FA L EY 2 TI NO. 4833 T ST A ER GINE EN TYPICAL BASE PLATE DETAIL O FES S ION PR A S 1 D H ER E NOTE: IN LIEU OF ANCHOR TESTING FREQUENCY NOTED ON SHEET S1, THE FIRST 10 ANCHORS FOR EACH INSTALLER SHALL BE TESTED, FOLLOWED BY TESTING OF 5% OF REMAINING ANCHORS. L 3" MIN 12" MAX 2ND AND 3RD FLOORS #2 CLEVIS A UC T UR N TE R O F C A L I FO R IA 2 1/4" 6" MAX 2 1/4" 3/4" DIA SIMPSON STRONG-BOLT 2 ANCHOR (5 3/4" MIN EMBED), TYP (E) STACK POST, TYP (E) STACK SHELF, TYP (E) "STRUT" MEMBER AS OCCURS, OR PROVIDE NEW UNISTRUT P1000 REV. 3 S5 ISSUE DATE TYP 7' - 6" MAX THREADED ROD BRACING EVERY THIRD BAY EXISTING AS OCCURS, OR PROVIDE NEW 3'-6" MIN 2 S5 1 2 S5 3 S5 LIBRARY BOOKSTACK RELOCATION SUMMER 2016 TYP S5 HUMBOLT STATE UNIVERSITY (BLDG 90) HSS AT EA (E) POST, LOCATED EITHER SIDE OF POST (TYPICALLY BEST TO ALTERNATE SIDES AS SHOWN TO FACILITATE ACCESS IN EXISTING FILLED STACKS) PLOTTED ON: 7/20/2016 11:15:40 AM © THORNTON TOMASETTI, INC. 2013 C:\Scratch\U16102_Central_R15_gtriplitt.rvt 9 TITLE STACK RETROFIT DETAILS TYPICAL STACK ELEVATION 3/4" = 1'-0" PROJECT NO: SHEET NUMBER U16102.00 SCALE: As indicated DRAWN BY: NK CHECKED BY: S5 JDF DATE: IFB #PW16-1, Addendum #2, Exhibit S, Page 2 of 2 7/20/2016 © Copyright Thornton Tomasetti, Inc. 2013