December 12, 2013 Bid & Permit Gensler 01.9462.002 Transbay Marketing Center 50 Fremont Street, 21st floor San Francisco, CA SECTION 26 06 51 – LIGHTING FIXTURE SCHEDULE PART 1 – GENERAL 1.1 A. 1.2 A. 1.3 A. 1.4 DESCRIPTION Provide and install lighting fixtures as shown on drawings and as specified in this and all related Sections. RELATED SECTIONS 26 51 00 Architectural Lighting Fixtures, Lamps & Ballasts DEFINITIONS The term Architect refers to the Architect, Interior Designer, Lighting Designer or Owner’s Representative individually or collectively. GENERAL REQUIREMENTS A. Provide all lighting fixtures as shown complete with all lamps, completely wired, controlled and securely attached to supports. B. Where a catalog number and a narrative or pictorial descriptions are provided, the written description shall take precedence and prevail. C. General Contractor shall provide electrical subcontractor with entire lighting specification (including fixture illustrations and sketches); electrical subcontractor shall provide each specified manufacturer with complete information about the fixtures they will supply. D. Type of fixtures shall be as indicated alphanumerically and as specified. E. Fixture details shown may be modified by the manufacturer provided all of the following conditions have been met: 1. 2. 3. 4. 1.5 Fixture performance is equal or improved; Structural, mechanical, electrical, safety, and maintenance characteristics are equal or improved; Cost to the Owner is reduced or equal. Modifications have been reviewed by the Architect and have been approved by the Architect in writing. LIGHTING FIXTURE DESCRIPTIONS Lighting Fixture Schedule Copyright 2011 Gensler 26 06 51 - 1 Gensler 01.9462.002 December 12, 2013 Bid & Permit Transbay Marketing Center 50 Fremont Street, 21st floor San Francisco, CA Lighting Fixture Schedule Copyright 2011 Gensler 26 06 51 - 2 Gensler 01.9462.002 December 12, 2013 Bid & Permit Transbay Marketing Center 50 Fremont Street, 21st floor San Francisco, CA Lighting Fixture Schedule Copyright 2011 Gensler 26 06 51 - 3 Gensler 01.9462.002 December 12, 2013 Bid & Permit Transbay Marketing Center 50 Fremont Street, 21st floor San Francisco, CA Lighting Fixture Schedule Copyright 2011 Gensler 26 06 51 - 4 Gensler 01.9462.002 December 12, 2013 Bid & Permit Transbay Marketing Center 50 Fremont Street, 21st floor San Francisco, CA Lighting Fixture Schedule Copyright 2011 Gensler 26 06 51 - 5 Gensler 01.9462.002 December 12, 2013 Bid & Permit Transbay Marketing Center 50 Fremont Street, 21st floor San Francisco, CA END OF SECTION 26 06 51 Lighting Fixture Schedule Copyright 2011 Gensler 26 06 51 - 6 Lighting Fixture Cut Sheets For Permit & Bid Set Transbay Marketing Center 10 December 2013 HORNET® HP DOWNLIGHT HDL-HP-RD LED 3.5” ROUND DOWNLIGHT LED APPLICATIONS: Retail and commercial ambient lighting CONSTRUCTION: 20 ga. galvanized steel frame 18 ga. galvanized steel splice housing and hanger brackets Die-cast optical housing and trim Extruded aluminum and die-cast heat sink MOUNTING: For use in T-grid or sheet rock ceilings, (max ceiling thickness 1”) PROJECT: LABELING: R C US TYPE: 4 3/4” For indoor use only IC/AT rated (17w only, not Energy Star rated) Damp location 11 3/4” 7 3 /4 ” ELECTRICAL: Electronic constant current LED driver 120v or 277v input Dimming options available for Triac, ELV, 0-10v and Lutron systems. See following pages for more information. This product complies with IEEE C62.41 for surge endurance up to 2.5KV. Amerlux® recommends using additional surge protection with this unit (supplied by others), surge damage is not covered by warranty. OPTICS: LED: Color Temp Options: 2700K, 3000K, 3500K, 4000K CRI: 85 typ. (2700K, 3000K, 3500K, 4000K) 90 typ. (3000K) Binning: 3 MacAdam (SDMC) Lumen Maintenance: >70% of intial lumens @ 50,000 hrs Lumen Output per head at 3000K: 17w: Spot 818 typ. 20w: Spot 986 typ. Flood 748 typ. Flood 901 typ. Wide Flood 693 typ. Wide Flood 835 typ. 3 1/2” 5 4 3/8” 11 /2” 14 1/2” min - 26” max 1 Electrostatic sensitive device, observe precautions for handling /8” Ceiling Cut Out Dimension: 4” dia. ELECTRICAL 17w 20w System System Driver Watts Amps Watts Amps Electronic 120v 17 0.14 20 0.17 277v 17 0.06 20 0.07 6 3/4” 13” 16 1/2” IC Housing 5 15” 14 1/2” min 26” max (see website for details) ORDERING INFORMATION: Housing: Model Wattage Lamp Driver Voltage Options Type HDL-HP-R 17 LED E - electronic 120 DIM-ELV- ELV dimming (120v only) 20 277 DIM-TRIAC - Triac dimming (120v only) HILUME - Lutron Hi-lume® dimming 0-10V - 0-10v dimming MF - multi-function driver CP - Chicago Plenum EM - emergency battery pack w/remote test switch IC/AT* - insulated ceiling/air tight (17w only) Trim: Model Color Temp HDL-HP-RD Reflector with White NSP - narrow spot, 12º 2700* 3000 Painted Flange SP - spot, 15º MBW - matte black NF - narrow flood, 20º 3500 MWW - matte white MFL - medium flood, 4000 SLVW - matte silver 24º 3000-90* FL - flood, 28º (90CRI) WF - wide flood, 45º VWF - very wide flood, 60º LS - linear spread, 60º x 10º Complete Example: HDL-HP-R-20-LED-E-120/HDL-HP-RD-MBW-FL-3000 Housing Example: HDL-HP-R-20-LED-E-120 Reflector Example: HDL-HP-RD-MBW-FL-3000 Aperture Finish Beam Spread * NOTE: 2700, 3000-90CRI & IC/AT options are not Energy Star rated Cat #: Amerlux® reserves the right to change details that do not affect overall function and performance. Amerlux®, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com Project: Transbay Marketing Center Project # 13168.00 Date: 10 December 2013 Type: F1 LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com HORNET® HP DOWNLIGHT HDL-HP-RD LED 3.5” ROUND DOWNLIGHT LED TYPE: FIXTURE DATA: For 17w data, multiply by 0.85 Complete photometric data (ies format) available upon request. 20W LED SPOT DISTRIBUTION LTL # 36952 FLOOD DISTRIBUTION LTL # 36953 90 WIDE FLOOD DISTRIBUTION LTL # 36954 90 90 600 1200 2500 60 60 60 5000 2400 1200 7500 3600 1800 0 30 Candelas at Nadir Deg Candela 0 8680 5 7080 15 1074 25 132 35 26 45 2 APPLICATION DATA: 0 30 Candelas at Nadir Deg Candela 0 3713 5 3354 15 1502 25 324 35 48 45 5 0 30 Candelas at Nadir Deg Candela 0 1821 5 1743 15 1215 25 544 35 123 45 9 Notes and Definitions: Beam spread is to 50% center beam candlepower (CBCP). D=Distance to floor or wall. FC=Footcandles on floor or wall at center beam aiming location. L=Effective Visual Beam length in feet (50% of maximum footcandle level). W=Effective Visual Beam width in feet (50% of maximum footcandle level). CB=Distance across or down to center beam location. D W FC L SPOT D 5.0’ 7.5’ 10.0’ 12.5’ FC 233 126 76 51 L 1.8 2.6 3.3 4.0 W 1.8 2.6 3.3 4.0 FLOOD D 5.0’ 7.5’ 10.0’ 12.5’ FC 120 59 35 23 L 2.6 3.5 4.7 5.7 W 2.6 3.5 4.7 5.7 WIDE FLOOD 0o Aiming Angle Horizontal Footcandles D 5.0’ 7.5’ 10.0’ 12.5’ FC 73 33 19 12 L 3.2 4.7 6.3 7.8 W 3.2 4.7 6.3 7.8 Amerlux®, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com Project: Transbay Marketing Center Project # 13168.00 LIT-1242 rev 10/13 Date: 10 December 2013 Type: F1 LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com HORNET® HP DOWNLIGHT HDL-HP-RD LED 3.5” ROUND DOWNLIGHT LED TYPE: DIMMING COMPATIBILITY: Amerlux® “Hornet®” fixtures are compatible with all major dimming protocols prevalent in the United States. Please see below for general compatibilities and wiring diagrams. Amerlux® recommends testing your unique dimming configuration as the exact full configuration (Dimmer, Fixture Quantity, Voltage, etc) may affect dimming performance. TRIAC (Forward Phase) DIMMING (-DIM-TRIAC Option) ---not compatible with 12w module--Utilizes “Standard” incandescent dimmers that are in wide use in installations across the US. Best for retrofit applications where Triac dimmers are installed. Wiring Diagram Notes: • 120v ONLY Driver Triac • Dims down to less than 5% light output (most cases) Black Black Dimmer LED • Consult Dimming manufacturer for installastion RED White (by others) instructions - DO NOT SHARE NEUTRALS! Green • Must meet dimmer Minimum Load Requirements per dimming manufacturer 120v Compatible Dimmers Wall Box (Incandescent Style, Wattage as required) Central System Lutron “Diva” Lutron “Vareo” ETC “SR” Rack w/D20 ETC “DRD” Rack w/D20 Lutron “Nova-T” Lutron “Skylark” Module Module Lutron “Maestro” Lutron “GP” Panel Lutron Grafix Eye QS ELV - Electronic Low Voltage (Reverse Phase) DIMMING (-DIM-ELV Option) Utilizes specialized “ELV” dimmers. Best for New Construction appilications Notes: • 120v ONLY • Dims down to less than 5% light output (most cases) • Consult Dimming manufacturer for installastion instructions - DO NOT SHARE NEUTRALS! • Must meet dimmer Minimum Load Requirements Wiring Diagram Driver Black Black RED White Green ELV Dimmer (by others) LED 120v Compatible Dimmers Wall Box (ELV Style) Lutron “Diva” Lutron “Nova-T” Lutron “Maestro” Leviton “Surslide” Lutron “Vareo” Lutron “Skylark” Leviton “Vizio” Central System ETC “SR” Rack w/ELV10 Module Lutron “GP” Panel with PHPM-PA Interface ETC “DRD” Rack w/ELV10 Module Lutron Grafix Eye QS with PHPM-PA Interface 0-10V - DIMMING (-0-10V Option) Integrates into a variety of building management and day-lighting controls Wiring Diagram Notes: • 120v - 277v • Dims down to less than 10% light output • Requires interface to turn off power to driver • Consult Dimming manufacturer for installastion instructions - DO NOT SHARE NEUTRALS! Compatible Dimmers Wall Box Lutron “Diva” - DVTV with PP-120H Interface Leviton Renoir II 0-10v Driver Violet Black RED Grey 0-10v Dimmer LED Black White Green Bldg Power or Interface Central System Lutron Grafix Eye with GRX-TVI Interface Amerlux®, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com Project: Transbay Marketing Center Project # 13168.00 LIT-1242 rev 10/13 Date: 10 December 2013 Type: F1 LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com HORNET® HP DOWNLIGHT HDL-HP-RD LED 3.5” ROUND DOWNLIGHT LED TYPE: LUTRON HI-LUME / ECO-SYSTEM (-DIM-HILUME Option) Integrates into a variety of building management and day-lighting controls 3-Wire Wiring Diagram Notes: • 120v or 277v Driver • Dims down to less than 5% light output 3-Wire FL Black Switched Hot • May use 3-Wire or Ecosystem Control Control Orange Dimmed Hot • Consult Dimming manufacturer for installastion (by others) White Neu instructions - DO NOT SHARE NEUTRALS! Green Gnd Purple/Grey E2 Purple E1 Compatible Dimmers Wall Box (3-Wire Fluorescent) ECO-Sys Bus DIVA Cap Wires Maestro Nova T ECO System Digital Control Wiring Vareo Cap Lead Central System Lutron ECO-System compatible controls ETC “SR” Rack w/D20F Module ETC “DRD” Rack w/D20F Module ECO System Control (by others) Black Orange White Green Purple/Grey Purple Driver Switched Hot Dimmed Hot Black RED LED Black RED LED VV+ VV+ Neu Gnd E2 E1 ECO-Sys Bus MULTI-FUNCTION Emergency Configuration 120v/277v Normal Power 120v/277v Normal Power Primary Driver Emergency system (by others) to ensure only one feed is active at a time. 120v/277v Emergency Feed (by others) Night Light Configuration LED Primary Driver On/Off control LED (by others) Secondary Driver 120v/277v Constant Power Secondary Driver In Night Light configuration Multi-Function driver provides 10 mA of drive current when primary driver is switched off. 17w = 2% output 20w = 1.5% output In Emergency configuration Multi-Function driver provides 100 mA of drive current. 17w = 20% output 20w = 16% output Patent-Pending Amerlux®, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com Project: Transbay Marketing Center Project # 13168.00 LIT-1242 rev 10/13 Date: 10 December 2013 Type: F1 LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com Calculite® Compact Fluorescent Open Downlight 8011 Page 1 of 2 4 1/2” Aperture Triple Tube Vertical Lamp 5 11 1/2" (292 mm) 2 4 1 6 8 1/16" (210 mm) 3 3/8" (86 mm) 10 1/2" (267 mm) 18W 8 1/8" (207 mm) Top View 3" (76 mm) 4 1/2" (115 mm) Dia. 1" (25 mm) min. 2 1/8" (54 mm) max. Flush 5" (127 mm) 3 Overlap 5 3/4" (147 mm) 1 1/8" (29 mm) max. Ceiling Thickness Ceiling Cutout: 5 1/16" (129 mm) Dia. Reflector Trim 8011CCLW 8011CCLP 8011CCL 8011 Frame-In Kit Comfort Clear™, White Flange 4118VU Electronic 120V - 277V Comfort Clear™, Polished Flange Comfort Clear™, Molded Trim Ring Add suffix. See options for other finishes. Features 1.Reflector: 16 ga. Alzak® aluminum, 50° visual cutoff to lamp and lamp image, medium distribution. Comfort Clear™ low iridescence finish. Selfflanged or flangeless with molded white trim ring (field paintable). 2. Socket Cup: Die-cast aluminum cup effectively dissipates heat and positions lamp holder. Snaps onto reflector neck to assure consistently correct optical alignment without tools. 3. Mounting Frame: Die-cast aluminum for dry or plaster ceilings. 4. Retaining Springs: Precision-tooled steel friction springs secure reflector to mounting frame for quick, tool-less installation. 5. Mounting Brackets: 16 ga. steel. Adjust from inside of fixture. Use 3/4" or 1 1/2" lathing channel, 1/2" EMT, or optional mounting bars. 6.Ballast/J-Box: Outboard mounted to reduce heat transfer and maintain lamp efficacy and life. Service from below without tools. Lamp 18W Triple Tube 4-Pin (Amalgam) Options and Accessories (continued) Emergency Add suffix EM Chicago Plenum Add suffix LC Emergency Ltg. Kit FA EM3E* FA EM4E* Fuse (Slow Blow) Add suffix F *See Spec. Sheet: FAEM Mounting Bars & Accessories; see Specification Sheet MBA. Sloped Ceiling Adapters; see Specification Sheet SCA. IC Frame available; see C4CFL18 Specification Sheet. Labels UL listed for damp locations, I.B.E.W. Electrical Note: For ballast electrical data and latest lamp/ballast compatibility refer to “Ballast” specification sheet for complete electrical data. UL listed for through branch circuit wiring with max of (8) No. 12 AWG, 90°C supply conductors. Options and Accessories Comfort Clear Finishes Diffuse CCD Champagne Bronze CCZ Other Finish White WH Specular Clear CL ™ 1 Alzak® is a registered trademark of ALCOA. Job Information Type: Job Name: Cat. No.: Lamp(s): Notes: 1 Specify desired flange W White, P Polished Blank - Molded Ring Lightolier a Genlyte company www.lightolier.com 631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2011 Genlyte Group LLC • C0711 Project: Transbay Marketing Center Project # 13168.00 Date: 10 December 2013 Type: F1A LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com Calculite® Compact Fluorescent Open Downlight 8011 Page 21 of 2 4 1/2” Aperture Triple Tube Vertical Lamp Quick Calculator ROOM SURFACE REFLECTANCES: 40 80% Ceiling; 50% Wall; 20% Floor 1200 Lumens Per Lamp 35 30 INITIAL FOOTCANDLES 25 RCR = 1 (Rm. width = 10 x Mtg. Ht. above work plane) RCR = 5 (Rm. width = 2 x Mtg. Ht. above work plane) RCR = 10 (Rm. width = Mtg. Ht. above work plane) 20 15 10 5 10 20 30 40 50 60 70 80 90 100 110 AREA PER FIXTURE IN SQUARE FEET 3 4 5 6 7 8 9 10 CENTER TO CENTER DISTANCE OF FIXTURE IN FEET This quick calculator chart determines the number and spacing of 1 lt.-18W PL-T units with clear reflector, for any level of illumination. Spacing Ratio = 1.2 CERTIFIED TEST REPORT NO. 0662FR COMPUTED BY LSI PROGRAM **TEST-LITE** CALCULITE RECESSED COMPACT FLUORESCENT OPEN DOWNLIGHT, 4 1/2” DIA. APERTURE CLEAR REFLECTOR 1-18W PLT LAMP. LUMEN RATING = 1200 LMS. CANDLEPOWER SUMMARY 85ϒ 75ϒ 65ϒ 200 55ϒ 45ϒ 400 0ϒ 5ϒ 15ϒ 25ϒ 35ϒ ** Efficiency = 42.38% ** ANGLE MEAN CP LUMENS 0 350 5 368 35 10 394 15 394 110 20 374 25 343 158 30 305 35 254 155 40 171 45 36 48 50 5 55 1 2 60 0 65 0 0 70 0 75 0 0 80 0 85 0 0 90 0 ZONAL LUMENS AND PERCENTAGES ZONE LUMENS Coefficients of Utilization CC WALL RCR 0-30 0-40 0-60 0-90 40-90 60-90 90-180 0-180 303 458 507 507 49 0 0 507 % LAMP %LUMINAIRE 25.30 38.18 42.30 42.30 4.13 .00 .00 42.30 59.81 90.25 100.00 100.00 9.75 .00 .00 100.00 ZONAL CAVITY METHOD EFFECTIVE FLOOR CAVITY REFLECTANCE = .20 80 70 50 3010 50 30 10 50 30 10 50 30 10 50 30 10 50 30 10 0 1 2 3 4 5 6 7 8 9 10 .47.46.46.47.46.45.45.44.43.43.43.42.42.41.41.40 .44.43.42 .44.42.41.42.41.40.41.40.39.40.39.39.38 .42.40.38.41.39.38.40.39.37.39.38.37.38.37.36.36 .39.37.36.39.37.35.38.36.35.37.36.35.36.35.34.33 .37.34.33.36.34.33.36.34.32.35.33.32.34.33.32.31 .35.32.31.34.32.30.34.32.30.33.31.30.33.31.30.29 .32.30.28.32.30.28.32.29.28.31.29.28.31.29.28.27 .30.28.26.30.28.26.30.27.26.29.27.26.29.27.26.25 .28.26.24.28.26.24.28.25.24.27.25.24.27.25.24.23 .26.24.22.26.24.22.26.24.22.25.23.22.25.23.22.21 Job Information Type: Lightolier a Genlyte company www.lightolier.com 631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2011 Genlyte Group LLC • C0711 Project: Transbay Marketing Center Project # 13168.00 Date: 10 December 2013 Type: F1A LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com Specification Decorative *>}iÊ£ÊvÊÓÊ {¸Ê«iÀÌÕÀiÊ/À«iÊ/ÕLiÊÀ>iÊÌ 5 11 1/2" (292 mm) D4132VU 2 4 1 6 8 1/16" (210 mm) 3 3/8" (86 mm) 10 1/2" (267 mm) 18W 8 1/8" (207 mm) Top View 3" (76 mm) 4 1/2" (115 mm) Dia. 1" (25 mm) min. 2 1/8" (54 mm) max. Flush 5" (127 mm) 3 Overlap 5 3/4" (147 mm) 1 1/8" (29 mm) max. Ceiling Thickness Ceiling Cutout: 5 1/16" (129 mm) Dia. Frame-In Kit D4132VU iVÌÀVÊ£Óä6ÓÇÇ6 ÓÈÊÀÊÎÓ7Ê/À«iÊ/ÕLi {*Ê­>}>® Compatible Reflector Trims Vetro Accessory Downlights I"ÞÊvÀÊÕÃiÊÜÌ Ê6iÌÀÊVViÃÃÀÞ 8011CL "«i]Ê6iÀÌV>Ê>«} {ä£]Ê{äÓ]Ê{äÎ]Ê{ä{]Ê{£Î]Ê{£{ Features Options & Accessories 1. Socket Cup:Ê->«ÃÊÌÊÀiviVÌÀÊiVÊÌÊ>ÃÃÕÀiÊVÃÃÌiÌÞÊVÀÀiVÌÊ«ÌV>Ê >}iÌÊÜÌ ÕÌÊÌð 2. Mounting Frame:Ê>Û>âi`ÊÃÌ>«i`ÊÃÌiiÊvÀÊ`ÀÞÊÀÊ«>ÃÌiÀÊVi}ð 3. Retaining Springs:Ê*ÀiVÃÌi`ÊÃÌiiÊvÀVÌÊëÀ}ÃÊÃiVÕÀiÊÀiviVÌÀÊÌÊ ÕÌ}ÊvÀ>iÊvÀʵÕV]ÊÌiÃÃÊÃÌ>>Ì° 4. Mounting Brackets:Ê>Û>âi`ÊÃÌii°Ê`ÕÃÌÊvÀÊÃ`iÊvÊvÝÌÕÀi°Ê 1ÃiÊÎÉ{¸ÊÀʣʣÉÓ¸Ê>Ì }ÊV >i]Ê£ÉÓ¸Ê/]ÊÀÊ«Ì>ÊÕÌ}ÊL>Àð 5. Ballast/J-Box:ÊiVÌÀVÊ£Óä6ÊÊÓÇÇ6°Ê1ÊÃÌi`ÊvÀÊÌ ÀÕ} ÊLÀ>V ÊVÀVÕÌÊ ÜÀ}ÊÜÌ Ê>ÝÊvÊ­n®Ê °Ê£ÓÊ7]Êäc ÊÃÕ««ÞÊV`ÕVÌÀðÊ"ÕÌL>À`Ê ÕÌi`ÊÌÊÀi`ÕViÊ i>ÌÊÌÀ>ÃviÀÊ>`Ê>Ì>Ê>«ÊivvV>VÞÊ>`Êvi°Ê-iÀÛViÊ vÀÊLiÜÊÜÌ ÕÌÊÌð Note:ÊÀÊL>>ÃÌÊiiVÌÀV>Ê`>Ì>Ê>`Ê>ÌiÃÌÊ>«ÉL>>ÃÌÊV«>ÌLÌÞÊÀiviÀÊÌÊ “Ballast” specification sheet for complete electrical data. Chicago Plenum Option: D4132VULC Note:Ê"ÞÊvÀÊÕÃiÊÜÌ ÊiVÀ>ÌÛiÊ`Ü} ÌÊ>VViÃÃÀÞÊ{ä£]Ê{äÓ]Ê{äÎ]Ê {£Î]Ê{ä£{]Ê{£{ Mounting Bars: T-Bar Anchor Clips: 1950 Ê£n¸Ê-iÌÊvÊ­Ó® 1951 ÊÓǸÊ-iÌÊvÊ­Ó® 1956 Ê-iÌÊvÊ­{®]ÊvÀÊÕÃiÊÜÌ Ê>LÛi Labels 1ÊÃÌi`ÊvÀÊ`>«ÊV>Ìð Job Information Type: Job Name: Cat. No.: Lamp(s): Notes: ÈΣÊÀ«ÀÌÊ,>`]Ê>Ê,ÛiÀ]ÊÊäÓÇÓäÊUÊ­xän®ÊÈÇn£Î£ÊUÊ>ÝÊ­xän®ÊÈÇ{{Ç£ä We reserve the right to change details of design, materials and finish. ÜÜÜ°} ÌiÀ°VÊ^ÊÓääÊ* «ÃÊÀÕ«ÊUÊ äÎä Lightolier is a Philips group brand Project: Transbay Marketing Center Project # 13168.00 Date: 10 December 2013 Type: F1A LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com HORNET® HIGH POWER TRACK HEAD HORNET-HP LED LED APPLICATION Accent and display lighting for retail, commercial & hospitality environments CONSTRUCTION: Complete die-cast construction No exposed wiring Powder coat paint ELECTRICAL: Electronic constant current LED driver 120v - 277v input Dimming options available for Triac and ELV systems. See following pages for more information. This product complies with IEEE C62.41 for surge endurance up to 2.5KV. Amerlux® recommends using additional surge protection with this unit (supplied by others), surge damage is not covered by warranty. MOUNTING: Track, canopy and busway - Not for use on vertically mounted track OPTICS: 0-180º tilt, 360º rotation Available in a variety of beam spreads LED: Color Temp Options: 2700K, 3000K, 3500K, 4000K CRI: 85 typ. (2700K, 3000K, 3500K, 4000K) 90 typ. (3000K) Binning: 3 macAdam Lumen Maintenance: >70% of intial lumens @ 50,000 hrs Lumen output (21w): Spot,15º - 1115 lm typ (3000K) Flood, 28º - 1058 lm typ (3000K) Wide Flood, 45º - 1051 lm typ (3000K) ACCESSORIES: Snoot: Die-cast aluminum, 1” length, painted finish Cross Blade: Stamped steel painted optical matte black cross blade sits in snoot which must be ordered when using cross blade LABELING: PROJECT: TYPE: For indoor use only 4 1/4” Electrostatic sensitive device, observe precautions for handling 3 3/8” 4 11/16” Accessory Options: 90º 4 5/8” 90º Ø2 13/16” Accessory Holder ELECTRICAL 18w 21w System System Driver Watts Amps Watts Amps Electronic 120v 18 0.15 21 0.18 277v 18 0.06 21 0.08 Snoot Accessory Holder ORDERING INFORMATION: Model Wattage HORNET-HP 18 21 Lamp Type Driver Finish LED E - electronic WT - white texture BT - black texture ST - silver texture __ - _______ (other RAL) Example: HORNET-HP-21-LED-E-WT-TN1-120-FL-3000 Mounting Voltage TN1 - Global 1cir, 120v 120 TEK - Global 2cir/2neut, 120v 277 TN3 - Global 3cir, 120v TN2 - Global 2cir/2neut, 277v B - busway C - canopy CCL - C-clamp __ - __________ (other) (see website for details) Beam Spread Color Temp NSP - narrow spot, 12º SP - spot, 15º NF - narrow flood, 20º MFL - medium flood, 24º FL - flood, 28º WF - wide flood, 45º VWF - very wide flood, 60º LS - linear spread, 60º x 10º 2700 3000 3500 4000 Options/Accessories* SNAH - snoot accessory holder, 1” length, matte black interior, specify exterior color (WT, BT, ST) accepts cross blade plus 2 additional forms of media 3000-90* AH - accessory holder, specify finish (90CRI) (WT, BT, ST), accepts 2 forms of media CB - cross blade, matte black finish, requires snoot HEX - hexcell louver (1/8” x 1/8”) DIM-ELV - ELV dimming (120v only) * NOTE: 3000-90CRI & accessories are not Energy Star rated. DIM-TRIAC - Triac dimming (120v only) Cat #: Amerlux® reserves the right to change details that do not affect overall function and performance. Amerlux®, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com Project: Transbay Marketing Center Project # 13168.00 Date: 10 December 2013 Type: F3 LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com HORNET® HIGH POWER TRACK HEAD HORNET-HP LED LED TYPE: FIXTURE DATA: For 18w data, multiply by .86 Complete photometric data (ies format) available upon request. 21W LED SPOT (SP) DISTRIBUTION LTL #33661 180 FLOOD (FL) DISTRIBUTION LTL # 33664 120 150 ACROSS 45 ALONG 180 WIDE FLOOD (WF) DISTRIBUTION LTL # 33665 180 120 150 ACROSS 45 ALONG 90 90 90 2500 400 1100 60 60 60 5000 2200 800 7500 3300 1200 0 30 0 Candelas at Nadir Deg Candela 0 8755 5 7093 15 1113 25 220 35 91 45 36 APPLICATION DATA: 120 150 ACROSS 45 ALONG 0 30 30 Candelas at Nadir Deg Candela 0 1407 5 1364 15 1064 25 637 35 288 45 109 Candelas at Nadir Deg Candela 0 3808 5 3430 15 1532 25 386 35 115 45 51 D Notes and Definitions: Beam spread is to 50% center beam candlepower (CBCP). D=Distance to floor or wall. FC=Footcandles on floor or wall at center beam aiming location. L=Effective Visual Beam length in feet (50% of maximum footcandle level). W=Effective Visual Beam width in feet (50% of maximum footcandle level). CB=Distance across or down to center beam location. CB 30° 30° D FC W FC CB L 30o Aiming Angle Horizontal Footcandles 30o Aiming Angle Vertical Footcandles 60o Aiming Angle Vertical Footcandles 60° 60º SPOT 30º30° L D 5.0’ 7.5’ 10.0’ 12.5’ FC 230 127 77 51 L 1.8 2.6 3.2 3.9 W 1.8 2.6 3.2 3.9 D 5.0’ 7.5’ 10.0’ 12.5’ FC 172 88 52 34 L 2.3 3.2 4.9 5.1 W 2.1 2.9 4.3 4.6 CB 3.0 4.0 5.0 7.0 D 3.0’ 4.0’ 5.0’ 6.0’ FC 141 83 54 35 L 2.9 3.7 4.7 5.8 W 1.5 2.2 2.8 3.4 CB 4.0 6.0 7.0 9.0 D 3.0’ 4.0’ 5.0’ 6.0’ FC 529 348 223 155 L 1.3 1.7 2.1 2.4 W 1.1 1.3 1.6 2.0 CB 2.0 2.0 3.0 3.0 FLOOD 30° 30º W FC D 5.0’ 7.5’ 10.0’ 12.5’ FC 122 61 36 23 L 2.6 3.5 4.6 5.7 W 2.6 3.5 4.6 5.7 D 5.0’ 7.5’ 10.0’ 12.5’ FC 84 42 25 16 L 3.2 4.4 5.7 7.1 W 2.9 3.9 5.1 6.4 CB 3.0 4.0 5.0 6.0 D 3.0’ 4.0’ 5.0’ 6.0’ FC 65 39 25 18 L 3.8 4.8 6.0 7.3 W 2.6 3.2 4.0 4.7 CB 4.0 5.0 7.0 8.0 D 3.0’ 4.0’ 5.0’ 6.0’ FC 243 164 98 73 L 2.1 2.2 3.0 3.4 W 1.5 1.9 2.7 3.0 CB 2.0 2.0 3.0 3.0 WIDE FLOOD 0o Aiming Angle Horizontal Footcandles D 5.0’ 7.5’ 10.0’ 12.5’ FC 52 24 14 9 L 3.8 5.7 7.6 9.5 W 3.8 5.7 7.6 9.5 D 5.0’ 7.5’ 10.0’ 12.5’ FC 39 18 10 7 L 4.4 6.4 8.6 10.9 W 4.2 6.1 8.1 10.4 CB 2.0 3.0 4.0 5.0 D 3.0’ 4.0’ 5.0’ 6.0’ FC 38 23 15 11 L 4.0 5.2 6.5 7.9 W 3.4 4.4 5.4 6.5 CB 3.0 4.0 5.0 5.0 D 3.0’ 4.0’ 5.0’ 6.0’ FC 116 64 43 29 L 2.6 3.5 4.3 5.2 W 2.4 3.3 4.0 4.9 CB 1.0 2.0 2.0 2.0 Amerlux®, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com Project: Transbay Marketing Center Project # 13168.00 L W LIT-1206 rev 10/13 Date: 10 December 2013 Type: F3 LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com HORNET® HIGH POWER TRACK HEAD HORNET-HP LED LED TYPE: DIMMING COMPATIBILITY: Amerlux® “Hornet®” track head is compatible with TRIAC and ELV dimming protocols prevalent in the United States. Please see below for general compatibilities and wiring diagrams. Amerlux® recommends testing your unique dimming configuration as the exact full configuration (Dimmer, Fixture Quantity, Voltage, etc) may affect dimming performance. TRIAC (Forward Phase) DIMMING (-DIM-TRIAC Option) ---not compatible with 12w module--Utilizes “Standard” incandescent dimmers that are in wide use in installations across the US. Best for retrofit applications where Triac dimmers are installed. Wiring Diagram Notes: • 120v ONLY Driver Triac • Dims down to less than 5% light output (most cases) Black Black Dimmer LED • Consult Dimming manufacturer for installastion RED White (by others) instructions - DO NOT SHARE NEUTRALS! Green • Must meet dimmer Minimum Load Requirements per dimming manufacturer 120v Compatible Dimmers Wall Box (Incandescent Style, Wattage as required) Central System Lutron “Diva” Lutron “Vareo” ETC “SR” Rack w/D20 ETC “DRD” Rack w/D20 Lutron “Nova-T” Lutron “Skylark” Module Module Lutron “Maestro” Lutron “GP” Panel Lutron Grafix Eye QS ELV - Electronic Low Voltage (Reverse Phase) DIMMING (-DIM-ELV Option) Utilizes specialized “ELV” dimmers. Best for New Construction appilications Notes: • 120v ONLY • Dims down to less than 5% light output (most cases) • Consult Dimming manufacturer for installastion instructions - DO NOT SHARE NEUTRALS! • Must meet dimmer Minimum Load Requirements Wiring Diagram Driver Black Black RED White Green ELV Dimmer (by others) LED 120v Compatible Dimmers Wall Box (ELV Style) Lutron “Diva” Lutron “Nova-T” Lutron “Maestro” Leviton “Surslide” Lutron “Vareo” Lutron “Skylark” Leviton “Vizio” Central System ETC “SR” Rack w/ELV10 Module Lutron “GP” Panel with PHPM-PA Interface ETC “DRD” Rack w/ELV10 Module Lutron Grafix Eye QS with PHPM-PA Interface Amerlux®, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com Project: Transbay Marketing Center Project # 13168.00 LIT-1206 rev 10/13 Date: 10 December 2013 Type: F3 LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com Project: Transbay Marketing Center Project # 13168.00 Date: 10 December 2013 Type: F3 LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com ° ROTATION 360 9/16 n5 1 3/4 2 1/4 STEM LENGTH 5 1/4 2 5/16 2 7/8 1/4 4 REV WorkInProgress DESIGN STATE 90° TILT 1 13/16 FINISH MATERIAL DATE APPROVED SHEET SCALE 1 DRAWN BY DATE G L O B A L OF 1 3/8 GGP 8/20/2012 DESCRIPTION A DATE DWG.# CHKD. BY SIZE S O L U TIO N S ED-0626 DATE APPRD. BY HORNET STEM CANOPY L IG H TIN G REV. 23 Daniel Road East Fairfield, N.J. 07004 Phone: 973-882-5010 Fax: 973-882-2604 Web: www.amerlux.com AMERLUX RESERVES THE RIGHT TO CHANGE DETAILS THAT DO NOT AFFECT OVERALL FUNCTION AND PERFORMANCE. ENGINEERING APPROVAL TO START DESIGN: _______________ DATE: __________ CUSTOMER APPROVAL: _______________ DATE: __________ FIXTURE TYPE: JOB NAME: HORNET-15-LED-E-FINISH-MTG-VOLTAGE-BEAM-COLOR TEMP-OPTIONS 90° TILT 4" OCTAGONAL J-BOX (BY OTHERS) REVISION HISTORY DESCRIPTION DIMENSIONS ARE IN INCHES TOLERANCES ARE: FRACTIONAL: ± 1/64 DECIMAL: .XX ± .01, .XXX ± .005 ANGLE: ± .5~ UNLESS OTHERWISE SPECIFIED 1 5/8 PROPRIETARY AND CONFIDENTIAL THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF AMERLUX LIGHTING SOLUTIONS. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF AMERLUX LIGHTING SOLUTIONS IS STRICTLY PROHIBITED. 2 3/4 4" OCTAGONAL J-BOX (BY OTHERS) 4 1/4 1 11/16 3 7/8 GRÜV MINI EXTRUDED GRUVM-EX-GB LED 2.5” RECESSED LINEAR LED, GYP BOARD APPLICATIONS: Retail and commercial ambient lighting in wall to ceiling applications ELECTRICAL: Electronic, multi-volt (120v-277v) constant current driver Dimmable, 0-10v This product complies with IEEE C62.41 for surge endurance up to 3KV. Amerlux recommends using additional surge protection with this unit (supplied by others), surge damage is not covered by warranty. Emergency circuit via remote inverter or auxillary emergency power supply (by others) CONSTRUCTION: Extruded aluminum housing Ceiling trim is high reflectance white finish MOUNTING: For use in sheet rock ceilings or walls only Fixtures must be installed before finished ceiling or walls are installed LABELING: OPTICS: 5w/ft, 3500K LED’s standard, other color temps available Extruded white acrylic lens, snap-in, 8’ maximum section Amerlux exclusive white acrylic lens provides excellent transmission while effectively concealing lamp image TYPE: Mounting rods & hardware by others 3” PROJECT: For indoor use only 1’ to 2’ from end of fixture (2 per fixture) Suspension brackets supplied by Amerlux 3” 5 3 5 /8 ” Fixture height Support method by others /8” Driver Electronic Wattage per foot 5 Lamping 120v 277v 4’ Input watts Amps 22 .18 20 .07 Input watts 44 40 Electrostatic sensitive device, observe precautions for handling Feed location (optional) 1 5/16” NOTE: Minimum ceiling opening must be held by installer for the full length of the run 2 1/2” 5 1/4” ELECTRICAL 5 7/16” Fixture & mounting bracket height Feed location (default) 1 /16” Overall length of run 8’ Amps .37 .14 Ceiling contractor to spackle, feather & sand at ceiling interface. (see website for details) ORDERING INFORMATION: Model Wattage Lamp Type Per Foot GRUVM-EX-GB 5 LED Driver E - electronic Voltage 120/277 Length Mounting For Straight Runs 4 - 4’ IND - individual 8 - 8’ BOR - beginning of run _______ MOR - middle of run (other consult EOR - end of run factory) For Ceiling/Wall Corner BORWC - beginning of run, wall corner EORWC - end of run, wall corner BORCC - beginning of run, ceiling corner EORCC - end of run, ceiling corner Color Temp Options 2700 3000 3500 4000 HILUME - Lutron HiLume driver CP - Chicago plenum Example: GRUVM-EX-GB-5-LED-E-120/277-8-IND-3500 Cat #: Amerlux reserves the right to change details that do not affect overall function and performance. Amerlux, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com Project: Transbay Marketing Center Project # 13168.00 Date: 10 December 2013 Type: F4,F4A,F4B,F4C LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com GRÜV MINI EXTRUDED GRUVM-EX-GB LED 2.5” RECESSED LINEAR LED, GYP BOARD TYPE: FIXTURE DATA: Complete photometric data (.ies format) available upon request. GRÜV MINI 5W LED SOURCE: 120 WHITE LEDS LUMENS: 1458 RECESSED ZONAL LUMEN SUMMARY Zone Lumens %Lamp 0-30 487 NA 0-40 763 NA 0-60 1220 NA 0-90 1458 NA 90-180 0 NA 0-180 1458 NA LTL# 31019 %Fixt 33.4 52.3 83.7 100.0 0.0 100.0 90 75 175 60 350 45 Total Luminaire Efficacy = 69.9 lumens/watt COEFFICIENTS OF UTILIZATION Effective Floor Cavity Reflectance 20% RC 80 RW 70 50 30 10 RCR 0 1736 1736 1736 1736 1 1598 1534 1476 1424 2 1465 1353 1261 1183 3 1345 1201 1090 1001 4 1239 1074 954 862 5 1145 968 844 752 6 1062 878 754 665 7 989 801 679 593 8 923 734 616 534 9 865 677 562 484 10 813 627 516 442 525 700 0 15 30 LIT-1144 rev 12/12 Amerlux, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com Project: Transbay Marketing Center Project # 13168.00 Date: 10 December 2013 Type: F4,F4A,F4B,F4C LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com HORNET HP DOWNLIGHT HDL-HPX-RLW-TL LED 3.5” ROUND LENSED WALL WASH TRIMLESS LED ELECTRICAL: Electronic constant current LED driver 120v or 277v input Dimming options available for Triac, ELV, 0-10v and Lutron systems. See following pages for more information. Also optional is Emergency Battery Pack with a remote test switch. This product complies with IEEE C62.41 for surge endurance up to 2.5KV. Amerlux recommends using additional surge protection with this unit (supplied by others), surge damage is not covered by warranty. APPLICATIONS: Retail and commercial wall wash lighting CONSTRUCTION: 20 ga. galvanized steel frame 18 ga. galvanized steel splice housing and hanger brackets Cast aluminum plaster frame w/perforated face Die-cast trim, extruded aluminum heat sink Thermally protected Optic can be rotated to any position MOUNTING: For use in T-grid or sheet rock ceilings, max ceiling thickness 3/4”, consult factory for thicker ceilings LABELING: For indoor use only IC/AT rated (optional) Damp location 5 4 3/16” TYPE: 3 9/16” Ceiling Cut Out Dimension: 4 1/2” dia. ELECTRICAL Electronic driver 12w 17w 20w 23w System System System System Watts Amps Watts Amps Watts Amps Watts Amps 120v 12 0.1 17 0.14 20 0.17 23 0.19 277v 12 0.04 17 0.06 20 0.07 23 0.08 3 4 6 5 1. Reflector Trim 2. Fixture Housing Aperture Plate 2 3. Ceiling 5/8” (1” max) 4. Cast Aluminum Plaster Frame 1 5. Plaster Skim Coat (by others) 6. 6-32 Type F Thread Cutting Screw Wattage Lamp Type Driver 12 17 20 LED E - electronic 120 277 HDL-HPX-R-TL 23 5 (see website for details) ORDERING INFORMATION: HDL-HP-R-TL Electrostatic sensitive device, observe precautions for handling 3 1 /2 ” /8” 11 1/2” 14 1/2” min - 26” max Housing: Model PROJECT: Approved to UL standards as tested by CSA. R US C 4 13/16” 4 11/16” 7 3/4” 11 11/16” OPTICS: High reflectance, high diffusivity mixing chamber Engineered nano technology lens provides transmission while concealing LED image LED: Color Temp Options: 2700K, 3000K, 3500K, 4000K CRI: 85 typ. (2700K, 3000K, 3500K, 4000K) 90 typ. (3000K) Binning: 3 MacAdam (SDMC) Life: 50,000 hrs Lumen Maintenance: >70% of intial lumens @ 50,000 hrs Lumen Output at 3000K: 17w: 632 lm 20w: 743 lm 23w: 854 lm Trim: Model Voltage Options DIM-ELV- ELV dimming (120v only) DIM-TRIAC - Triac dimming (120v only) HILUME - Lutron Hi-lume® EcoSystem 3 wire, 1% dim 0-10V - 0-10v dimming MF-EM - multi-function emergency driver MF-NL - multi-function night light driver CP - Chicago Plenum EM - emergency battery pack w/remote test switch IC/AT* - insulated ceiling/air tight (17w only) Aperture Finish Reflector with White HDL-HPX-RLW-TL Painted Flange MBW - matte black MWW - matte white SLVW - matte silver Color Temp 2700 3000 3500 4000 3000-90 (90CRI) Complete Example: HDL-HP-R-TL-20-LED-E-120/HDL-HPX-RLW-TL-MWW-3000 Housing Example: HDL-HP-R-TL-20-LED-E-120 Reflector Example: HDL-HPX-RLW-TL-MWW-3000 Cat #: Amerlux reserves the right to change details that do not affect overall function and performance. Amerlux, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com Project: Transbay Marketing Center Project # 13168.00 Date: 10 December 2013 Type: F5 LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com HORNET® HP DOWNLIGHT HDL-HPX-RLD-TL LED 3.5” ROUND LENSED DOWNLIGHT TRIMLESS LED TYPE: FIXTURE DATA: For 17w data, multiply by 0.74; For 20w data, multiply by 0.87 Complete photometric data (.ies format) available upon request. Hornet HP Round Lens Wall Washer 23w LED Source: LED with frosted plastic optic Lumens: 854 Recessed LTL# 369000 150 180 120 ACROSS 45 ALONG ZONAL LUMEN SUMMARY Zone Lumens %Fixt 0-30 410 48.00 0-40 587 68.73 0-60 782 91.54 0-90 854 100.0 90-180 0 0.0 0-180 854 100.0 120 90 60 150 90 200 60 400 30 Luminaire Efficacy: 37.6 lumens/watt 30 600 0 APPLICATION DATA: Footcandles are average and rounded off. Data for multiple units are based on a minimum of five units. Footcandles on Wall 1.5’ 23 45 46 35 24 17 13 10 24 46 47 36 25 18 13 10 0.5’ 1.5’ 2.5’ 3.5’ 4.5’ 5.5’ 6.5’ 7.5’ 17 33 34 26 18 13 10 8 19 36 36 27 19 14 11 9 18 34 36 28 20 15 11 9 0.5’ 1.5’ 2.5’ 3.5’ 4.5’ 5.5’ 6.5’ 7.5’ 10 22 26 24 19 15 11 9 11 24 27 25 21 16 12 10 11 24 28 26 21 17 13 11 Distance from ceiling 23 43 43 32 22 16 12 9 Distance from ceiling 1.5’ 0.5’ 1.5’ 2.5’ 3.5’ 4.5’ 5.5’ 6.5’ 7.5’ Distance from ceiling 1.5 Feet From Wall 1.5 Feet From Wall 24 45 46 35 25 17 13 10 22 43 44 33 22 16 12 9 19 36 37 28 20 15 12 9 17 34 36 28 20 15 11 9 11 24 28 26 22 17 13 11 11 24 28 26 21 17 13 10 2’ 2 Feet From Wall 2’ 2’ 19 36 36 27 20 14 11 9 17 33 34 26 18 13 10 8 11 24 27 26 21 16 12 10 10 22 26 24 19 15 11 9 2’ Amerlux, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com Project: Transbay Marketing Center Project # 13168.00 rev 11/13 Date: 10 December 2013 Type: F5 LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com HORNET® HP DOWNLIGHT HDL-HPX-RLD-TL LED 3.5” ROUND LENSED DOWNLIGHT TRIMLESS LED TYPE: DIMMING COMPATIBILITY: Amerlux “Hornet” fixtures are compatible with all major dimming protocols prevalent in the United States. Please see below for general compatibilities and wiring diagrams. Amerlux recommends testing your unique dimming configuration as the exact full configuration (Dimmer, Fixture Quantity, Voltage, etc) may affect dimming performance. TRIAC (Forward Phase) DIMMING (-DIM-TRIAC Option) ---not compatible with 12w module--Utilizes “Standard” incandescent dimmers that are in wide use in installations across the US. Best for retrofit applications where Triac dimmers are installed. Wiring Diagram Notes: • 120v ONLY Driver Triac • Dims down to less than 5% light output (most cases) Black Black Dimmer LED • Consult Dimming manufacturer for installastion RED White (by others) instructions - DO NOT SHARE NEUTRALS! Green • Must meet dimmer Minimum Load Requirements per dimming manufacturer 120v Compatible Dimmers Wall Box (Incandescent Style, Wattage as required) Central System Lutron “Diva” Lutron “Vareo” ETC “SR” Rack w/D20 ETC “DRD” Rack w/D20 Lutron “Nova-T” Lutron “Skylark” Module Module Lutron “Maestro” Lutron “GP” Panel Lutron Grafix Eye QS ELV - Electronic Low Voltage (Reverse Phase) DIMMING (-DIM-ELV Option) Utilizes specialized “ELV” dimmers. Best for New Construction appilications Notes: • 120v ONLY • Dims down to less than 5% light output (most cases) • Consult Dimming manufacturer for installastion instructions - DO NOT SHARE NEUTRALS! • Must meet dimmer Minimum Load Requirements Wiring Diagram Driver Black Black RED White Green ELV Dimmer (by others) LED 120v Compatible Dimmers Wall Box (ELV Style) Lutron “Diva” Lutron “Nova-T” Lutron “Maestro” Leviton “Surslide” Lutron “Vareo” Lutron “Skylark” Leviton “Vizio” Central System ETC “SR” Rack w/ELV10 Module Lutron “GP” Panel with PHPM-PA Interface ETC “DRD” Rack w/ELV10 Module Lutron Grafix Eye QS with PHPM-PA Interface 0-10V - DIMMING (-0-10V Option) Integrates into a variety of building management and day-lighting controls Wiring Diagram Notes: • 120v - 277v • Dims down to less than 10% light output • Requires interface to turn off power to driver • Consult Dimming manufacturer for installastion instructions - DO NOT SHARE NEUTRALS! Compatible Dimmers Wall Box Lutron “Diva” - DVTV with PP-120H Interface Leviton Renoir II 0-10v Driver Violet Black RED Grey 0-10v Dimmer LED Black White Green Bldg Power or Interface Central System Lutron Grafix Eye with GRX-TVI Interface Amerlux, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com Project: Transbay Marketing Center Project # 13168.00 rev 11/13 Date: 10 December 2013 Type: F5 LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com HORNET® HP DOWNLIGHT HDL-HPX-RLD-TL LED 3.5” ROUND LENSED DOWNLIGHT TRIMLESS LED TYPE: LUTRON HI-LUME / ECO-SYSTEM (-DIM-HILUME Option) Integrates into a variety of building management and day-lighting controls 3-Wire Wiring Diagram Notes: • 120v or 277v Driver • Dims down to less than 5% light output 3-Wire FL Black Switched Hot • May use 3-Wire or Ecosystem Control Control Orange Dimmed Hot • Consult Dimming manufacturer for installastion (by others) White Neu instructions - DO NOT SHARE NEUTRALS! Green Gnd Purple/Grey E2 Purple E1 Compatible Dimmers Wall Box (3-Wire Fluorescent) ECO-Sys Bus DIVA Cap Wires Maestro Nova T ECO System Digital Control Wiring Vareo Cap Lead Central System Lutron ECO-System compatible controls ETC “SR” Rack w/D20F Module ETC “DRD” Rack w/D20F Module ECO System Control (by others) Black Orange White Green Purple/Grey Purple Driver Switched Hot Dimmed Hot Black RED LED Black RED LED VV+ VV+ Neu Gnd E2 E1 ECO-Sys Bus MULTI-FUNCTION Emergency Configuration 120v/277v Normal Power 120v/277v Normal Power Primary Driver Emergency system (by others) to ensure only one feed is active at a time. 120v/277v Emergency Feed (by others) Night Light Configuration LED Primary Driver On/Off control LED (by others) Secondary Driver 120v/277v Constant Power Secondary Driver In Night Light configuration Multi-Function driver provides 10 mA of drive current when primary driver is switched off. 17w = 2% output 20w = 1.5% output In Emergency configuration Multi-Function driver provides 100 mA of drive current. 17w = 20% output 20w = 16% output Patent-Pending Amerlux, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com Project: Transbay Marketing Center Project # 13168.00 rev 11/13 Date: 10 December 2013 Type: F5 LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com PROJECT SPECIFIER TYPE ZONE __ __ SKU 1. SERIES LIGHT ENGINE 24V DC DIMMING CLASS 2 IP20 DRY LOCATION NOTE SUITABLE FOR INSTALLATION WITHIN THE CLOSET STORAGE SPACE (WITH CLOTHING) 2. COLOR CODE ETL (INTERTEK) APPROVED NFPA ATRICLE 410.16 (ALL SECTIONS) UL LISTED 2108 FILE NUMBER E364348 LUMINAIRE MUST BE INSTALLED IN ACCORDANCE WITH NFPA 70, ARTICLE 410.16 1. SERIES 2. COLOR 94+ CRI WHITE 8000 SERIES HIGH OUTPUT SINGLE BIN 8024 83+CRI 6.0W /ft ≤546 Lm/ft 8924 94+CRI 5.6W /ft ≤463 Lm/ft 8024/8924 SERIES CCT 2150K 94CRI 2650K 97CRI 2950K 97CRI COLOR CODE 22 26 29 83+ CRI WHITE SINGLE BIN 0.55 1.0 0.10 MIN INCREMENT = 1 INCH / MAX PER CIRCUIT = 15 FEET 27 30 35 40 60 2700K 3000K 3500K 4000K 6000K COLORS 4000 SERIES MID OUTPUT 4924 94+CRI 2.8W /ft ≤236 Lm/ft 0.40 4024/4924 SERIES UL E364348 R G B A PK PR RED GREEN BLUE AMBER PINK PURPLE 4024 83+CRI 3.0W /ft ≤279 Lm/ft 3W/FT 24VDC 2.0 CRI = Color Rendering Index CCT = CorRelated Color Temperature 0.10 MIN INCREMENT = 2 INCHES / MAX PER CIRCUIT = 30 FEET 3000 SERIES LOW OUTPUT (INDIRECT APPLICATIONS ONLY) 3024 83+CRI 1.5W /ft ≤137 Lm/ft 3924 94+CRI 1.4W /ft ≤116 Lm/ft 0.40 3024/3924 SERIES UL E364348 1.5W/FT 24VDC 4.0 0.10 MIN INCREMENT = 4 INCHES / MAX PER CIRCUIT = 32 FEET COMPONENT OF A COMPLETE SYSTEM INCLUDING: AION LED A-TRACK LIGHT ENGINE, AION LED A-TRACK HOUSING WITH DIFFUSER LENS, & AION LED DRIVER (POWER SUPPLY). DIMMER NOT INCLUDED. APPROVED DIMMERS, CONTROLS, POWER SUPPLIES, CABLE, & OTHER COMPONENTS ONLY. CONTACT AION LED FOR QUESTIONS REGARDING COMPATIBILTY. ELECTRICIAN INSTALLED. STRICTLY ADHERE TO NEC & LOCAL BUILDING CODE. LIMITED 5-YEAR WARRANTY AGAINST MANUFACTURING DEFECTS ONLY, DOES NOT COVER LABOR; VOIDED BY: INADEQUATE VENTILLATION, FIELD MODIFICATIONS, INSTALLATION BY UNQUALIFIED PERSONNEL, UNAPPROVED CONTROLS, DRIVERS, CABLING, OTHER DEVICES, NOT FOLLOWING INSTALLATION GUIDELINES & PROTOCOL, GENERAL NEGLIGENCE. INSTALLER ASSUMES ALL LIABILITY WITH REGARD TO PROPERTY & SAFETY. THIS PRODUCT IS UL LISTED. SEE SEPARATE: “AION LED WARRANTY TERMS” & ADDITIONAL INSTRUCTIONAL MATERIALS FOR MORE INFORMATION. AUTHORIZED INSTALLERS ONLY. SYSTEMS TESTED PRIOR TO SHIPPING. © Copyright 2013 Aion LED, Inc. All Rights Reserved Project: Transbay Marketing Center Project # 13168.00 (415) 255-AION (2466) Date: www.AionLED.com 10 December 2013 Type: F6 LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com A-TRACK SEAMLESS FIXTURE UP TO 30 FEET PER CIRCUIT (24V) CUSTOM CRAFTED TO GIVEN DIMENSIONS BEST IN CLASS DIFFUSION OPTIONS HIGH QUALITY, HIGH OUTPUT CABLE ARMOR OPTION COMPATIBLE WITH PS TYPE: 4000, 4024, 8024, 7000-RGB, & 7024-RGB LINEAR FIXTURE -NOT INCLUDED, SOLD SEPARATELY (multiple pages) Warning: Installation should only be attempted by qualified and authorized personnel. Licensed electricians and trained technicians must wire all components in strict compliance with local building codes. Installer assumes all liability for safety and hazard mitigation. Aion LED is not liable for damages incurred by negligence, faulty wiring, poor design, overloading, or other. Authorized Aion LED Installers are trained in installation methods, materials, and code-related protocol. AION LED, LLC 2325 3RD ST #330 SAN FRANCISCO, CA 94107 © Copyright 2012 Aion LED All Rights Reserved TOLL FREE: (877) 345-AION [2466] INTERNATIONAL PATENTS PENDING Project: Transbay Marketing Center Project # 13168.00 Date: FAX: (415) 285-1335 CustomerCare@AionLED.com www.AionLED.com 10 December 2013 Type: F6 LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com Project: Transbay Marketing Center Project # 13168.00 Date: 10 December 2013 Type: F6 LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com Class 2 Dimming LED Driver 24 Volt ELECTRICIAN INSTALLED MODEL D20-D-24 DIMENSIONS (L-W-H) INCHES WATTAGE RATING CLASS 2 (UL STANDARD) NEMA 3R CASE INPUT VOLTAGE OUTPUT VOLTAGE LOADED VOLTAGE OPEN MAX INPUT CURRENT PRIMARY BREAKER SECONDARY BREAKER DIMMING DIMMER TYPE* LEADS PRIMARY AWG, TEMP LEADS SECONDARY AWG, TEMP THERMAL CLASS BOOST TAP 10% MAX FEET #3024/3924 SERIES MAX FEET #4024/4924 SERIES MAX FEET #8024/8924 SERIES (5 x 2.1 x 2) 20 ETL (UL 8750) Yes Indoor 120V 60Hz 23.5 VDC 25.5 VDC 206mA Thermal 2A Triac/ Primary Magnetic/ Low-voltage #20 105 C #16 105 C (B) 130 C No 12 6 3 D40-D-24 (5 x 2.1 x 2) 40 ETL (UL 8750) Yes Indoor 120V 60Hz 23.5 VDC 25.5 VDC 360mA Thermal 4A Triac/ Primary Magnetic/ Low-voltage #20 105 C #16 105 C (B) 130 C No 24 12 6 D60-D-24 (8.5 x 3 x 2.9) 60 ETL (UL 1310) Yes Indoor/ Outdoor 120V 60Hz 23.5 VDC 25.5 VDC 0.6A 1A THERMAL 5A THERMAL Triac/ Primary Magnetic/ Low-voltage #18 105 C #12 105 C (B) 130 C Yes 36 18 9 D100-D-24 (9 x 4.2 x 3.25) 96 ETL (UL 1310) Yes Indoor/ Outdoor 120V 60Hz 23.5 VDC 25.5 VDC 1A 2A THERMAL 4A MAGNETIC Triac/ Primary Magnetic/ Low-voltage #18 105 C #12 105 C (B) 130 C Yes 60 30 15 D300-D3-24 (7 x 7 x 3.2) 288 (3 x 96) ETL (UL 1310) Yes Indoor 120V 60Hz 23.5 VDC 25.5 VDC 3A 5A THERMAL (3X) 4A MAGNETIC Triac/ Primary Magnetic/ Low-voltage #18 105 C #12 105 C (B) 130 C Yes 180 90 45 *CONTROLS COMPATIBILITY 1. 2 WIRE, FORWARD-PHASE, MAGNETIC TRANSFORMER. LOAD DRIVER BETWEEN 50 to 90% OF MAXIMUM RATED WATTAGE. 2. MAGNETIC LOW VOLTAGE DIMMERS SUCH AS: LUTRON HOMEWORKS, GRAFIK EYE, RADIO RA, & NOVA -SELECT MODELS ONLY. 3. LOW END DIMMING PERCENTAGE VARIES PER MODEL. CONTACT AION LED FOR MORE INFORMATION REGARDING APPROVED CONTROLS. MAX LED RUN PER CIRCUIT 1. [4A (96W) per circuit] (NEC Article 725) 2. 10% headroom included 3. Use electrical junction boxes to transition between building wire and Aion LED power feeds per local code. SUB BOXES Use larger guage cord for sub feeds and longer runs. Junction building wire to fixture whips within electrical boxes per local code. HEAT & EMI MAGNETIC DC TRANSFORMERS EMIT HEAT AND ELECTROMAGNETIC ENERGY. ADEQUATE VENTILATION REQUIRED (NEC ARTICLE 450) PLEASE LEAVE 15 INCHES OF SPACE BETWEEN EACH TRANSFORMER. MAGNETIC LOW-VOLTAGE 120VAC FIRM D-24-SERIES 24VDC TYPE DESC + _ L N JOB SKU MEMO [FOR NEUTRAL DIMMING SWITCHES: REFER TO MANUFACTURER’S INSTRUCTIONS Warning: Installation should only be attempted by qualified and authorized personnel. Licensed electricians and trained technicians must wire all components in strict compliance with local building codes and NEC. Installer assumes all liability for safety and hazard mitigation. Aion LED is not liable for damages incurred by negligence, faulty wiring, poor design, overloading, inadequate ventilation, inadequate spacing, or other. Authorized Aion LED Installers are trained in installation methods, materials, and code-related protocol. AION LED, INC. 2325 3RD ST #330 SAN FRANCISCO, CA 94107 TOLL FREE: (877) 345-AION [2466] © Copyright 2012 Aion LED All Rights Reserved Project: Transbay Marketing Center Project # 13168.00 FAX: (415) 285-1335 CustomerCare@AionLED.com www.AionLED.com Date: 10 December 2013 Type: F6 LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com 1.800.263.AXIS [ T ] 514.948.6272 [ F ] 514.948.6271 PENDANT ASYMMETRIC MOUNT www.axislighting.com PROJECT INFORMATION Project: Notes: Type: DIMENSIONS SECTION VIEWS Asymmetric Indirect Asymmetric Direct 4" 102mm 4" 102mm SHOWN WITH LENS OPTION 3 13/32” 87mm 3 13/32” 87mm ORDERING CODE 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 PRODUCT SPECIFICATIONS 1 PRODUCT ID BMD pendant direct BMI pendant indirect 2 OPTICS 3 LENGTH/FT A asymmetric AF asymmetric frosted(1) 2 3 4 5 6 8 12 S# 4 SPECIFY LENGTH NL NL4 EX EX4 2’ 3’ 4’ 5’ 6’ 8’ 12’ System Run 5 LAMP nominal (3’ & 4’ lamps) nominal (4’ lamps only) exact (3’ & 4’ lamps) exact (4’ lamps only) 6 LAMP CONFIGURATION T5 T5 T5HO T5HO 1 1 lamp (1) For direct light distribution only 7 MR M16# MR 16 halogen M16LED# MR 16 LED 8 FINISH AP aluminum paint W white C custom Add 9” per lamp 13 BATTERY B# battery pack 4’ sections 9 VOLTAGE 120 277 347 UNV 120V 277V 347V(2) universal (2) Please consult factory 14 OTHER F fuse 10 BALLAST D E ERS T 1 2A/B +E# +NL# +GTD# +M 1 regular 2 alternating emergency section night light section generator transfer device MR 12 MOUNTING/SUSPENSION SA# drywall+stem length >48” (18" std.) Use ballast guide for ballast specification (3) In T5HO, only available for 2x4’ lamp configuration 15 IC CONTROLS DS# OS# DS+OS# DOS# 11 CIRCUITS dimming instant start rapid start step dimming(3) daylight sensor occupancy sensor daylight+occupancy sensor daylight&occupancy sensor See integrated controls guide for further details 16 CUSTOM C custom Please specify Ballast, Battery Pack and Integrated Control Details and Custom Description: FILE NAME:BM.ASYM.SPEC July 8, 2013 Product design and development is an ongoing process at Axis Lighting. We reserve the right to change specifications. Contact Axis for the latest product information. Project: Transbay Marketing Center Project # 13168.00 Date: © 2011 Axis Lighting Inc. Page: 1 / 5 10 December 2013 Type: F7,F7A,F7B LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com 1.800.263.AXIS [ T ] 514.948.6272 [ F ] 514.948.6271 PENDANT ASYMMETRIC MOUNT www.axislighting.com CONSTRUCTION JOINERS Housing Extruded Aluminum (0.075'' nominal) up to 70% Recycled Content End Cap Sheet Steel (18 ga) Interior Brackets Die Formed Sheet Steel (18 gauge) Reflectors White Powder Coated Sheet Steel (22 ga) Blank Extruded Aluminum (0.075'' nominal) Lenses Extruded Acrylic (0.070'' nominal) Frosted: 85% trans. Suspension Ø 1/2" Stem In order to allow very long runs of BEAM 3 luminaires, Axis has developed an effective joining system. Special care has been taken to maximize the performance of the joiner for each BEAM option. WEIGHT 4 ft 8 ft 12 ft 12.3 lbs / 5.0 kg 24.6 lbs / 10.1 Kg 36.9 lbs / 15.1 Kg NOTE: Hang each system segment individually. Do not assemble system prior to hanging. SYSTEM (S#) MR16 BEAM 3 linear systems, with the use of a strong profile, allow for a nearly hair thin connection system of continuous runs. Lengths of 4', 8', 12' as well as custom lengths are available. Runs of BEAM 3 that are greater than 12' in length are designated as systems (S#). This means that the run is comprised of a combination of 4', 8' and/or 12' sections to be assembled on site using our joining system. For more information on systems and joining, please refer to the BEAM installation sheets available for download at www.axislighting.com. Blank MR16 Halogens MR16 LED Quantity Spacing Extruded Aluminum (0.075'' nominal) 2.0'' diameter (35W / 50W) 2.0'' diameter For every 4' fluorescent lamp section, there may be up to a maximum of 4 x MR16 lamps. Each MR16 is placed centered on a blank section 9'' in length. 4" 3 13/32" For a series of MR16's within a given section length, they will be spaced evenly on a longer blank section. The directed light of MR16 Halogen lamps are fixed downward. Custom spacing may be available on special request. *Please consult factory ELECTRIC AL Ballast Emergency Voltage Electronic IS, Electronic Rapid Start, Dimming (0- 10V, Line, Step, EcoSystem, DALI) with preinstalled ballast disconnect as per NEC & CEC Emergency battery pack or emergency circuit 120V, 277V, 347V, UNV Incorporating these components may have limitations or effect the length of the luminaire, please contact factory for more details. Between fluorescent lamps sections APPROVALS 9" Certified to UL and CUL standards Meets NYC requirements At luminaire ends FINISH Aluminium paint, Powder Coated and custom finishes are also available. 9" Several in a long blank section variable FILE NAME:BM.ASYM.SPEC July 8, 2013 Product design and development is an ongoing process at Axis Lighting. We reserve the right to change specifications. Contact Axis for the latest product information. Project: Transbay Marketing Center Project # 13168.00 Date: © 2011 Axis Lighting Inc. Page: 2 / 5 10 December 2013 Type: F7,F7A,F7B LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com 1.800.263.AXIS [ T ] 514.948.6272 [ F ] 514.948.6271 PENDANT ASYMMETRIC MOUNT www.axislighting.com SA STEM MOUNT IN DRYWALL CEILING OPTICS ASYMMETRIC FROSTED LENS (acrylic snap-in lens) frosted: 85% trans. AF asymmetric frosted ASYMMETRIC NO LENS (asymmetric reflector) Power feed Non power feed A asymmetric ASYMMETRIC MOUNTING SPACING Inner Asymmetric Reflector Outer Asymmetric Reflector Die Formed Specular Aluminum (22 gauge) Extruded Aluminum (0.075'' nominal) Outer Asymm reflector sits flush 3 7/16" (46 5/16" C.C.) 8' (92 5/8" C.C.) 12'(138 15/16" C.C.) T8 LAMP 4" Inner Asymm reflector T5/T5HO LAMP 4' 1 7/8" 4' 8' 12' (48" C.C.) (96" C.C.) (144" C.C.) OTHER MOUNTING OPTIONS BEAM 3 is also available with recessed, surface, wall, recessed wall, asymmetric and wall wash mounted options. Specification sheets and Installation sheets for all mounting for BEAM luminaires are available for download at www.axislighting.com FILE NAME:BM.ASYM.SPEC July 8, 2013 Product design and development is an ongoing process at Axis Lighting. We reserve the right to change specifications. Contact Axis for the latest product information. Project: Transbay Marketing Center Project # 13168.00 Date: © 2011 Axis Lighting Inc. Page: 3 / 5 10 December 2013 Type: F7,F7A,F7B LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com 1.800.263.AXIS [ T ] 514.948.6272 [ F ] 514.948.6271 PENDANT ASYMMETRIC MOUNT www.axislighting.com INTEGRATED CONTROL OPTIONS BEAM 3 luminaires allow the use of integrated controls such as daylight sensors (DS), occupancy sensors (OS), individual daylight sensors and occupancy sensors (DS+OS), and combination daylight/occupancy sensors (DOS). These options can be seamlessly integrated into our luminaires. The control system could be used to optimize the lighting of the space by reducing energy consumption through daylight harvesting and occupancy, thereby improving the overall interior environment and allowing for LEED credits. CONTROL SENSORS ● Consult factory for other options. ● Refer to IC brochure for more information. SENSORS BRAND Model TYPE CODE COMPATIBLE DIMMING BALLAST Lutron EC-DIR-WH Daylight LD EcoSystem Wattstopper FD-301 Daylight WD 0-10V Philips Luxsense Daylight PL 0-10V FS-205 PIR Occupancy WP1 Programmed Rapid Start Occupancy Sensor (OS) Wattstopper FS-355 PIR Occupancy WP2 Programmed Rapid Start FM-105 High Frequency Occupancy WH Programmed Rapid Start Actilume Daylight & PIR Occupancy PA DALI or 0-10V Daylight Sensor (DS) Daylight & Occupancy Sensors (DOS) Philips PHOTOMETRIC DATA CANDELA DISTRIBUTION 1 T5 COEFFICIENTS OF UTILIZATION (%) Zonal Lumens Horizontal Angles Vertical Angle PHOTOMETRIC CURVE 90° 90° 104 209 60° 45° 417 60° 626 30° 45° 834 0° 90° 30° 15° 0° 15° Test Lamp: 1xF28T5 IES FILE: BMD-A-4-T5-1 Efficiency: 70.3% 0 5 15 25 35 45 55 65 75 85 90 95 105 115 125 135 145 155 165 175 180 0 23 45 68 90 135 157 180 569 510 395 304 233 178 126 80 46 15 1 0 0 0 0 0 0 0 0 0 0 569 498 397 314 243 187 133 88 47 16 1 0 0 0 0 0 0 0 0 0 0 569 506 432 352 281 213 155 99 52 16 1 0 0 0 0 0 0 0 0 0 0 569 535 482 416 348 275 201 129 63 16 2 0 0 0 0 0 0 0 0 0 0 569 564 558 519 485 418 345 247 143 36 2 0 0 0 0 0 0 0 0 0 0 569 621 705 783 827 812 720 490 242 54 5 0 0 0 0 1 1 0 0 0 0 569 650 755 866 916 878 703 462 216 52 4 0 0 0 0 0 1 1 0 0 0 569 652 780 892 939 878 678 450 205 49 4 0 0 0 0 0 1 1 0 0 0 Wall 31 135 238 324 376 375 304 188 65 2 0 0 0 0 0 0 0 0 80 Ceiling 70 50 70 50 30 10 70 50 30 10 50 30 10 0 84 84 84 84 82 82 1 76 73 69 67 74 71 2 69 63 58 54 67 61 3 62 55 49 44 61 54 4 57 48 42 37 55 47 5 52 43 36 31 51 42 6 48 38 32 27 47 38 7 44 34 28 24 43 34 8 41 31 25 21 40 31 9 38 29 23 19 37 28 10 36 26 21 17 35 26 Based on floor reflectance of 20 82 68 57 48 41 36 31 28 25 22 20 82 66 53 44 36 31 27 24 21 19 17 78 68 59 51 45 40 36 33 30 27 25 78 66 55 47 40 35 31 27 24 22 20 78 63 52 43 36 31 27 23 21 18 17 LUMINANCE DATA (CD/M 2) Horizontal Angles Vertical Angle 45 55 65 75 85 0 984 708 477 296 112 23 1060 770 539 317 120 90 4189 4126 3792 3210 1594 135 5069 4687 3441 1908 498 180 4866 3829 2673 1326 358 All IES files for other lamping are available for download at: www.axislighting.com FILE NAME:BM.ASYM.SPEC July 8, 2013 Product design and development is an ongoing process at Axis Lighting. We reserve the right to change specifications. Contact Axis for the latest product information. Project: Transbay Marketing Center Project # 13168.00 Date: © 2011 Axis Lighting Inc. Page: 4 / 5 10 December 2013 Type: F7,F7A,F7B LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com 1.800.263.AXIS [ T ] 514.948.6272 [ F ] 514.948.6271 PENDANT ASYMMETRIC MOUNT www.axislighting.com PHOTOMETRIC DATA CANDELA DISTRIBUTION 1 T5HO COEFFICIENTS OF UTILIZATION (%) Zonal Lumens Horizontal Angles Vertical Angle PHOTOMETRIC CURVE 90° 90° 180 361 60° 45° 722 60° 1083 30° 45° 1444 0° 90° 30° 15° 0° 15° Test Lamp: 1xF54T5HO IES FILE: BMD-A-4-T5HO-1 Efficiency: 70.3% 0 5 15 25 35 45 55 65 75 85 90 95 105 115 125 135 145 155 165 175 180 0 23 45 68 90 135 157 987 833 678 530 403 303 211 143 80 27 1 0 0 0 0 0 0 0 0 0 0 987 884 697 546 420 322 231 148 81 27 1 0 0 0 0 0 0 0 0 0 0 987 895 742 611 490 369 268 172 88 27 2 0 0 0 0 0 0 0 0 0 0 987 915 807 729 604 470 345 217 109 28 3 0 0 0 0 0 0 0 0 0 0 987 989 965 912 838 728 585 423 244 63 4 0 0 0 0 0 0 0 0 0 0 987 1094 1229 1357 1434 1398 1231 849 426 96 9 0 0 0 0 1 1 1 0 0 0 987 1093 1305 1490 1575 1517 1212 790 374 88 7 0 0 0 0 0 1 1 0 0 0 Wall 31 135 238 324 376 375 304 188 65 2 0 0 0 0 0 0 0 0 80 Ceiling 70 50 70 50 30 10 70 50 30 10 50 30 10 0 84 84 84 84 82 82 1 76 73 70 67 74 71 2 69 63 58 54 67 62 3 63 55 49 44 61 54 4 57 48 42 37 55 47 5 52 43 36 31 51 42 6 48 38 32 27 47 38 7 44 35 28 24 43 34 8 41 31 25 21 40 31 9 38 29 23 19 37 28 10 36 26 21 17 35 26 Based on floor reflectance of 20 82 68 57 48 41 36 31 28 25 23 20 82 66 53 44 37 31 27 24 21 19 17 78 68 59 52 45 40 36 33 30 27 25 78 66 55 47 40 35 31 27 25 22 20 78 64 52 43 36 31 27 23 21 19 17 LUMINANCE DATA (CD/M 2) Horizontal Angles Vertical Angle 45 55 65 75 85 0 1678 1192 850 519 201 23 1822 1336 901 540 210 90 7302 6991 6495 5483 2810 135 8729 8013 5958 3351 895 180 8498 6623 4577 2267 613 All IES files for other lamping are available for download at: www.axislighting.com FILE NAME:BM.ASYM.SPEC July 8, 2013 Product design and development is an ongoing process at Axis Lighting. We reserve the right to change specifications. Contact Axis for the latest product information. Project: Transbay Marketing Center Project # 13168.00 Date: © 2011 Axis Lighting Inc. Page: 5 / 5 10 December 2013 Type: F7,F7A,F7B LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com PROJECT SPECIFIER TYPE ZONE __ __ SKU 1. SERIES LIGHT ENGINE 24V DC DIMMING CLASS 2 IP20 DRY LOCATION NOTE SUITABLE FOR INSTALLATION WITHIN THE CLOSET STORAGE SPACE (WITH CLOTHING) 2. COLOR CODE ETL (INTERTEK) APPROVED NFPA ATRICLE 410.16 (ALL SECTIONS) UL LISTED 2108 FILE NUMBER E364348 LUMINAIRE MUST BE INSTALLED IN ACCORDANCE WITH NFPA 70, ARTICLE 410.16 1. SERIES 2. COLOR 94+ CRI WHITE 8000 SERIES HIGH OUTPUT SINGLE BIN 8024 83+CRI 6.0W /ft ≤546 Lm/ft 8924 94+CRI 5.6W /ft ≤463 Lm/ft 8024/8924 SERIES CCT 2150K 94CRI 2650K 97CRI 2950K 97CRI COLOR CODE 22 26 29 83+ CRI WHITE SINGLE BIN 0.55 1.0 0.10 MIN INCREMENT = 1 INCH / MAX PER CIRCUIT = 15 FEET 27 30 35 40 60 2700K 3000K 3500K 4000K 6000K COLORS 4000 SERIES MID OUTPUT 4924 94+CRI 2.8W /ft ≤236 Lm/ft 0.40 4024/4924 SERIES UL E364348 R G B A PK PR RED GREEN BLUE AMBER PINK PURPLE 4024 83+CRI 3.0W /ft ≤279 Lm/ft 3W/FT 24VDC 2.0 CRI = Color Rendering Index CCT = CorRelated Color Temperature 0.10 MIN INCREMENT = 2 INCHES / MAX PER CIRCUIT = 30 FEET 3000 SERIES LOW OUTPUT (INDIRECT APPLICATIONS ONLY) 3024 83+CRI 1.5W /ft ≤137 Lm/ft 3924 94+CRI 1.4W /ft ≤116 Lm/ft 0.40 3024/3924 SERIES UL E364348 1.5W/FT 24VDC 4.0 0.10 MIN INCREMENT = 4 INCHES / MAX PER CIRCUIT = 32 FEET COMPONENT OF A COMPLETE SYSTEM INCLUDING: AION LED A-TRACK LIGHT ENGINE, AION LED A-TRACK HOUSING WITH DIFFUSER LENS, & AION LED DRIVER (POWER SUPPLY). DIMMER NOT INCLUDED. APPROVED DIMMERS, CONTROLS, POWER SUPPLIES, CABLE, & OTHER COMPONENTS ONLY. CONTACT AION LED FOR QUESTIONS REGARDING COMPATIBILTY. ELECTRICIAN INSTALLED. STRICTLY ADHERE TO NEC & LOCAL BUILDING CODE. LIMITED 5-YEAR WARRANTY AGAINST MANUFACTURING DEFECTS ONLY, DOES NOT COVER LABOR; VOIDED BY: INADEQUATE VENTILLATION, FIELD MODIFICATIONS, INSTALLATION BY UNQUALIFIED PERSONNEL, UNAPPROVED CONTROLS, DRIVERS, CABLING, OTHER DEVICES, NOT FOLLOWING INSTALLATION GUIDELINES & PROTOCOL, GENERAL NEGLIGENCE. INSTALLER ASSUMES ALL LIABILITY WITH REGARD TO PROPERTY & SAFETY. THIS PRODUCT IS UL LISTED. SEE SEPARATE: “AION LED WARRANTY TERMS” & ADDITIONAL INSTRUCTIONAL MATERIALS FOR MORE INFORMATION. AUTHORIZED INSTALLERS ONLY. SYSTEMS TESTED PRIOR TO SHIPPING. © Copyright 2013 Aion LED, Inc. All Rights Reserved Project: Transbay Marketing Center Project # 13168.00 (415) 255-AION (2466) Date: www.AionLED.com 10 December 2013 Type: F8 LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com A-TRACK SEAMLESS FIXTURE UP TO 30 FEET PER CIRCUIT (24V) CUSTOM CRAFTED TO GIVEN DIMENSIONS BEST IN CLASS DIFFUSION OPTIONS HIGH QUALITY, HIGH OUTPUT CABLE ARMOR OPTION COMPATIBLE WITH PS TYPE: 4000, 4024, 8024, 7000-RGB, & 7024-RGB LINEAR FIXTURE -NOT INCLUDED, SOLD SEPARATELY (multiple pages) Warning: Installation should only be attempted by qualified and authorized personnel. Licensed electricians and trained technicians must wire all components in strict compliance with local building codes. Installer assumes all liability for safety and hazard mitigation. Aion LED is not liable for damages incurred by negligence, faulty wiring, poor design, overloading, or other. Authorized Aion LED Installers are trained in installation methods, materials, and code-related protocol. AION LED, LLC 2325 3RD ST #330 SAN FRANCISCO, CA 94107 © Copyright 2012 Aion LED All Rights Reserved TOLL FREE: (877) 345-AION [2466] INTERNATIONAL PATENTS PENDING Project: Transbay Marketing Center Project # 13168.00 Date: FAX: (415) 285-1335 CustomerCare@AionLED.com www.AionLED.com 10 December 2013 Type: F8 LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com Project: Transbay Marketing Center Project # 13168.00 Date: 10 December 2013 Type: F8 LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com Class 2 Dimming LED Driver 24 Volt ELECTRICIAN INSTALLED MODEL D20-D-24 DIMENSIONS (L-W-H) INCHES WATTAGE RATING CLASS 2 (UL STANDARD) NEMA 3R CASE INPUT VOLTAGE OUTPUT VOLTAGE LOADED VOLTAGE OPEN MAX INPUT CURRENT PRIMARY BREAKER SECONDARY BREAKER DIMMING DIMMER TYPE* LEADS PRIMARY AWG, TEMP LEADS SECONDARY AWG, TEMP THERMAL CLASS BOOST TAP 10% MAX FEET #3024/3924 SERIES MAX FEET #4024/4924 SERIES MAX FEET #8024/8924 SERIES (5 x 2.1 x 2) 20 ETL (UL 8750) Yes Indoor 120V 60Hz 23.5 VDC 25.5 VDC 206mA Thermal 2A Triac/ Primary Magnetic/ Low-voltage #20 105 C #16 105 C (B) 130 C No 12 6 3 D40-D-24 (5 x 2.1 x 2) 40 ETL (UL 8750) Yes Indoor 120V 60Hz 23.5 VDC 25.5 VDC 360mA Thermal 4A Triac/ Primary Magnetic/ Low-voltage #20 105 C #16 105 C (B) 130 C No 24 12 6 D60-D-24 (8.5 x 3 x 2.9) 60 ETL (UL 1310) Yes Indoor/ Outdoor 120V 60Hz 23.5 VDC 25.5 VDC 0.6A 1A THERMAL 5A THERMAL Triac/ Primary Magnetic/ Low-voltage #18 105 C #12 105 C (B) 130 C Yes 36 18 9 D100-D-24 (9 x 4.2 x 3.25) 96 ETL (UL 1310) Yes Indoor/ Outdoor 120V 60Hz 23.5 VDC 25.5 VDC 1A 2A THERMAL 4A MAGNETIC Triac/ Primary Magnetic/ Low-voltage #18 105 C #12 105 C (B) 130 C Yes 60 30 15 D300-D3-24 (7 x 7 x 3.2) 288 (3 x 96) ETL (UL 1310) Yes Indoor 120V 60Hz 23.5 VDC 25.5 VDC 3A 5A THERMAL (3X) 4A MAGNETIC Triac/ Primary Magnetic/ Low-voltage #18 105 C #12 105 C (B) 130 C Yes 180 90 45 *CONTROLS COMPATIBILITY 1. 2 WIRE, FORWARD-PHASE, MAGNETIC TRANSFORMER. LOAD DRIVER BETWEEN 50 to 90% OF MAXIMUM RATED WATTAGE. 2. MAGNETIC LOW VOLTAGE DIMMERS SUCH AS: LUTRON HOMEWORKS, GRAFIK EYE, RADIO RA, & NOVA -SELECT MODELS ONLY. 3. LOW END DIMMING PERCENTAGE VARIES PER MODEL. CONTACT AION LED FOR MORE INFORMATION REGARDING APPROVED CONTROLS. MAX LED RUN PER CIRCUIT 1. [4A (96W) per circuit] (NEC Article 725) 2. 10% headroom included 3. Use electrical junction boxes to transition between building wire and Aion LED power feeds per local code. SUB BOXES Use larger guage cord for sub feeds and longer runs. Junction building wire to fixture whips within electrical boxes per local code. HEAT & EMI MAGNETIC DC TRANSFORMERS EMIT HEAT AND ELECTROMAGNETIC ENERGY. ADEQUATE VENTILATION REQUIRED (NEC ARTICLE 450) PLEASE LEAVE 15 INCHES OF SPACE BETWEEN EACH TRANSFORMER. MAGNETIC LOW-VOLTAGE 120VAC FIRM D-24-SERIES 24VDC TYPE DESC + _ L N JOB SKU MEMO [FOR NEUTRAL DIMMING SWITCHES: REFER TO MANUFACTURER’S INSTRUCTIONS Warning: Installation should only be attempted by qualified and authorized personnel. Licensed electricians and trained technicians must wire all components in strict compliance with local building codes and NEC. Installer assumes all liability for safety and hazard mitigation. Aion LED is not liable for damages incurred by negligence, faulty wiring, poor design, overloading, inadequate ventilation, inadequate spacing, or other. Authorized Aion LED Installers are trained in installation methods, materials, and code-related protocol. AION LED, INC. 2325 3RD ST #330 SAN FRANCISCO, CA 94107 TOLL FREE: (877) 345-AION [2466] © Copyright 2012 Aion LED All Rights Reserved Project: Transbay Marketing Center Project # 13168.00 FAX: (415) 285-1335 CustomerCare@AionLED.com www.AionLED.com Date: 10 December 2013 Type: F8 LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com HORNET® HP DOWNLIGHT HDL-HP-RA-TL LED 3.5” ROUND ADJUSTABLE TRIMLESS LED APPLICATIONS: Retail and commercial accent & display lighting OPTICS: LED: Color Temp Options: 2700K, 3000K, 3500K, 4000K CRI: 85 typ. (2700K, 3000K, 3500K, 4000K) 90 typ. (3000K) Binning: 3 MacAdam (SDMC) Lumen Maintenance: >70% of intial lumens @ 50,000 hrs Lumen Output per head at 3000K, 0º tilt: 17w: Spot 818 typ. 20w: Spot 986 typ. Flood 748 typ. Flood 901 typ. Wide Flood 693 typ. Wide Flood 835 typ. 0-30º lockable tilt, 358º rotation CONSTRUCTION: 20 ga. galvanized steel frame 18 ga. galvanized steel splice housing and hanger brackets Cast aluminum plaster frame w/perforated face Die-cast optical housing Extruded aluminum and die-cast heat sink ELECTRICAL: Electronic constant current LED driver 120v or 277v input Dimming options available for Triac, ELV, 0-10v and Lutron systems. See following pages for more information. This product complies with IEEE C62.41 for surge endurance up to 2.5KV. Amerlux® recommends using additional surge protection with this unit (supplied by others), surge damage is not covered by warranty. MOUNTING: For use in sheet rock ceilings (max ceiling thickness 1”) PROJECT: LABELING: R C US TYPE: 11 3/4” 7 3 /4 ” 4 11/16 ” For indoor use only IC/AT rated (17w only, not Energy Star rated) Damp location 30º 5 3 1 /2 ” 3 9/16” 11 1/2 ” Electrostatic sensitive device, observe precautions for handling /8” Ceiling Cut Out Dimension: 4 1/2” dia. 14 /2” min - 26” max 1 1. Reflector Trim 2. Fixture Housing Aperture Plate 3. Ceiling 5/8” (1” max) 2 4. Cast Aluminum Plaster Frame 5. Plaster Skim Coat (by others) 1 6. 6-32 Type F Thread Cutting Screw ELECTRICAL 17w 20w System System Driver Watts Amps Watts Amps Electronic 120v 17 0.14 20 0.17 277v 17 0.06 20 0.07 3 4 6 5 5 (see website for details) ORDERING INFORMATION: Housing: Model Wattage HDL-HP-R-TL 17 20 Lamp Type Driver Voltage LED E - electronic 120 277 Options/Accessories DIM-ELV- ELV dimming (120v only) DIM-TRIAC - Triac dimming (120v only) HILUME - Lutron Hi-lume® dimming 0-10V - 0-10v dimming MF multi-function driver CP - Chicago Plenum EM - emergency battery pack w/remote test switch Trim: Model Aperture Finish HDL-HP-RA-TL MB - matte black NSP - narrow spot, 12º MW - matte white SP - spot, 15º SLV - matte silver NF - narrow flood, 20º MFL - medium flood, 24º FL - flood, 28º WF - wide flood, 45º LS - linear spread, 60º x 10º IC/AT* - insulated ceiling/air tight (17w only) Complete Example: HDL-HP-R-TL-20-LED-E-120/HDL-HP-RA-TL-MBW-FL-3000 Housing Example: HDL-HP-R-TL-20-LED-E-120 Reflector Example: HDL-HP-RA-TL-MBW-FL-3000 Beam Spread Color Temp 2700* 3000 3500 4000 3000-90* (90CRI) * NOTE: 2700, 3000-90CRI & IC/AT are not Energy Star rated Cat #: Amerlux® reserves the right to change details that do not affect overall function and performance. Amerlux®, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com Project: Transbay Marketing Center Project # 13168.00 Date: 10 December 2013 Type: F9, F9A LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com HORNET® HP DOWNLIGHT HDL-HP-RA-TL 3.5” ROUND ADJUSTABLE TRIMLESS LED LED TYPE: FIXTURE DATA: For 17w data, multiply by 0.85 Complete photometric data (ies format) available upon request. 20W LED SPOT DISTRIBUTION LTL # 36952 FLOOD DISTRIBUTION LTL # 36953 90 WIDE FLOOD DISTRIBUTION LTL # 36954 90 90 600 1200 2500 60 60 60 5000 2400 1200 7500 3600 1800 0 30 Candelas at Nadir Deg Candela 0 8680 5 7080 15 1074 25 132 35 26 45 2 APPLICATION DATA: 0 30 Candelas at Nadir Deg Candela 0 3713 5 3354 15 1502 25 324 35 48 45 5 0 30 Candelas at Nadir Deg Candela 0 1821 5 1743 15 1215 25 544 35 123 45 9 Notes and Definitions: Beam spread is to 50% center beam candlepower (CBCP). D=Distance to floor or wall. FC=Footcandles on floor or wall at center beam aiming location. L=Effective Visual Beam length in feet (50% of maximum footcandle level). W=Effective Visual Beam width in feet (50% of maximum footcandle level). CB=Distance across or down to center beam location. D CB 30° 30° D FC L W W FC L CB W FC L SPOT D 5.0’ 7.5’ 10.0’ 12.5’ FC 233 126 76 51 L 1.8 2.6 3.3 4.0 W 1.8 2.6 3.3 4.0 FLOOD D 5.0’ 7.5’ 10.0’ 12.5’ FC 120 59 35 23 L 2.6 3.5 4.7 5.7 W 2.6 3.5 4.7 5.7 WIDE FLOOD 0o Aiming Angle Horizontal Footcandles D 5.0’ 7.5’ 10.0’ 12.5’ FC 73 33 19 12 L 3.2 4.7 6.3 7.8 W 3.2 4.7 6.3 7.8 Amerlux®, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com Project: Transbay Marketing Center Project # 13168.00 LIT-1262 rev 10/13 Date: 10 December 2013 Type: F9, F9A LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com HORNET® HP DOWNLIGHT HDL-HP-RA-TL 3.5” ROUND ADJUSTABLE TRIMLESS LED LED TYPE: DIMMING COMPATIBILITY: Amerlux® “Hornet®” fixtures are compatible with all major dimming protocols prevalent in the United States. Please see below for general compatibilities and wiring diagrams. Amerlux® recommends testing your unique dimming configuration as the exact full configuration (Dimmer, Fixture Quantity, Voltage, etc) may affect dimming performance. TRIAC (Forward Phase) DIMMING (-DIM-TRIAC Option) ---not compatible with 12w module--Utilizes “Standard” incandescent dimmers that are in wide use in installations across the US. Best for retrofit applications where Triac dimmers are installed. Wiring Diagram Notes: • 120v ONLY Driver Triac • Dims down to less than 5% light output (most cases) Black Black Dimmer LED • Consult Dimming manufacturer for installastion RED White (by others) instructions - DO NOT SHARE NEUTRALS! Green • Must meet dimmer Minimum Load Requirements per dimming manufacturer 120v Compatible Dimmers Wall Box (Incandescent Style, Wattage as required) Central System Lutron “Diva” Lutron “Vareo” ETC “SR” Rack w/D20 ETC “DRD” Rack w/D20 Lutron “Nova-T” Lutron “Skylark” Module Module Lutron “Maestro” Lutron “GP” Panel Lutron Grafix Eye QS ELV - Electronic Low Voltage (Reverse Phase) DIMMING (-DIM-ELV Option) Utilizes specialized “ELV” dimmers. Best for New Construction appilications Notes: • 120v ONLY • Dims down to less than 5% light output (most cases) • Consult Dimming manufacturer for installastion instructions - DO NOT SHARE NEUTRALS! • Must meet dimmer Minimum Load Requirements Wiring Diagram Driver Black Black RED White Green ELV Dimmer (by others) LED 120v Compatible Dimmers Wall Box (ELV Style) Lutron “Diva” Lutron “Nova-T” Lutron “Maestro” Leviton “Surslide” Lutron “Vareo” Lutron “Skylark” Leviton “Vizio” Central System ETC “SR” Rack w/ELV10 Module Lutron “GP” Panel with PHPM-PA Interface ETC “DRD” Rack w/ELV10 Module Lutron Grafix Eye QS with PHPM-PA Interface 0-10V - DIMMING (-0-10V Option) Integrates into a variety of building management and day-lighting controls Wiring Diagram Notes: • 120v - 277v • Dims down to less than 10% light output • Requires interface to turn off power to driver • Consult Dimming manufacturer for installastion instructions - DO NOT SHARE NEUTRALS! Compatible Dimmers Wall Box Lutron “Diva” - DVTV with PP-120H Interface Leviton Renoir II 0-10v Driver Violet Black RED Grey 0-10v Dimmer Black White Green Bldg Power or Interface Central System Lutron Grafix Eye with GRX-TVI Interface Amerlux®, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com Project: Transbay Marketing Center Project # 13168.00 LED LIT-1262 rev 10/13 Date: 10 December 2013 Type: F9, F9A LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com HORNET® HP DOWNLIGHT HDL-HP-RA-TL 3.5” ROUND ADJUSTABLE TRIMLESS LED LED TYPE: LUTRON HI-LUME / ECO-SYSTEM (-DIM-HILUME Option) Integrates into a variety of building management and day-lighting controls 3-Wire Wiring Diagram Notes: • 120v or 277v Driver • Dims down to less than 5% light output 3-Wire FL Black Switched Hot • May use 3-Wire or Ecosystem Control Control Orange Dimmed Hot • Consult Dimming manufacturer for installastion (by others) White Neu instructions - DO NOT SHARE NEUTRALS! Green Gnd Purple/Grey E2 Purple E1 Compatible Dimmers Wall Box (3-Wire Fluorescent) ECO-Sys Bus DIVA Cap Wires Maestro Nova T ECO System Digital Control Wiring Vareo Cap Lead Central System Lutron ECO-System compatible controls ETC “SR” Rack w/D20F Module ETC “DRD” Rack w/D20F Module ECO System Control (by others) Black Orange White Green Purple/Grey Purple Driver Switched Hot Dimmed Hot Black RED LED Black RED LED VV+ VV+ Neu Gnd E2 E1 ECO-Sys Bus MULTI-FUNCTION Emergency Configuration 120v/277v Normal Power 120v/277v Normal Power Primary Driver Emergency system (by others) to ensure only one feed is active at a time. 120v/277v Emergency Feed (by others) Night Light Configuration LED Primary Driver On/Off control LED (by others) Secondary Driver 120v/277v Constant Power Secondary Driver In Night Light configuration Multi-Function driver provides 10 mA of drive current when primary driver is switched off. 17w = 2% output 20w = 1.5% output In Emergency configuration Multi-Function driver provides 100 mA of drive current. 17w = 20% output 20w = 16% output Patent-Pending Amerlux®, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com Project: Transbay Marketing Center Project # 13168.00 LIT-1262 rev 10/13 Date: 10 December 2013 Type: F9, F9A LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc. Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com December 12, 2013 Bid & Permit Gensler 01.9462.002 Transbay Marketing Center 50 Fremont Street, 21st floor San Francisco, CA SECTION 26 51 00 – ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS PART 1 – GENERAL 1.1 A. 1.2 A. 1.3 A. 1.4 DESCRIPTION Provide and install lighting fixtures as shown on drawings and as specified in this and all related Sections. RELATED SECTIONS 26 06 51 Lighting Fixture Schedule DEFINITIONS The term Architect refers to the Architect, Interior Designer, Lighting Designer or Owner’s Representative individually or collectively. GENERAL REQUIREMENTS A. Provide all lighting fixtures as shown complete with all lamps, completely wired, controlled and securely attached to supports. B. Where a catalog number and a narrative or pictorial descriptions are provided, the written description shall take precedence and prevail. C. General Contractor shall provide electrical subcontractor with entire lighting specification (including fixture illustrations and sketches); electrical subcontractor shall provide each specified manufacturer with complete information about the fixtures they will supply. D. Type of fixtures shall be as indicated alphanumerically and as specified. E. Fixture details shown may be modified by the manufacturer provided all of the following conditions have been met: 1. Fixture performance is equal or improved; 2. Structural, mechanical, electrical, safety, and maintenance characteristics are equal or improved; 3. Cost to the Owner is reduced or equal. 4. Modifications have been reviewed by the Architect and have been approved by the Architect in writing. 1.5 A. STANDARDS The standards and regulating committees referred to in this specification and to which compliance with is required are: 1. 2. 3. 4. UL NRTL NEC ANSI Underwriters Laboratories Nationally Recognized Testing Laboratory National Electric Code American National Standards Institute ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS Copyright 2011 Gensler 26 51 00 - 1 December 12, 2013 Bid & Permit Gensler 01.9462.002 5. 6. 7. Transbay Marketing Center 50 Fremont Street, 21st floor San Francisco, CA ASTM American Society of Testing and Materials NEMA National Electrical Manufacturers Association IEC International Electrotechnical Commission B. All fixtures and assembled components shall be new, of good quality, and be approved by and bear the label of UL for the applicable location and conditions (wet, damp, dry, etc.) or other approved testing agencies, i.e. CSA, ETL, unless otherwise specified in writing. C. All fixtures shall meet all required local, state and/or national building, electrical and energy codes and regulations. 1.6 BIDDING A. Follow bidding procedures as described in Division 01 of this specification. B. Provide unit and alternate prices as required in Section 26 06 51 Lighting Fixture Schedule. 1.7 A. SUBSTITUTIONS Bidders' attention is called to the following procedure to be followed in submitting alternate fixture manufacturers than those specified: 1. 2. 3. 4. Bidders wishing to obtain approval on brands other than those specified by name and/or catalog number in Section 26 06 51, Lighting Fixture Schedule, shall submit their requests not later than ten (10) business days before the bid opening. Approval will be in the form of an addendum to the specifications issued to all prospective bidders indicating that the additional brand or brands are approved as equal to those specified as far as the requirements of the project are concerned. If the bidders do not elect to obtain prior approval during the time so specified, the Owner has no obligation to review or consider any such article after the contract award. If the bidder wishes to substitute fixtures from alternate manufacturers, his attention is called to Section 2.1, GENERAL MATERIAL REQUIREMENTS of PART 2 PRODUCTS. In addition, he shall note that the dimensions of visible parts of many fixtures (for example, the aperture diameters of incandescent fixtures) are binding to the bidder and cannot be changed without prior approval by the Architect. Contractor shall pay professional fees (at current standard hourly rates) and reimburse expenses directly to all designers (Architect, Engineer, Lighting Designer, et. al.) for time spent reviewing substitutions proposed by the Contractor. If payment by the Contractor is not made within 60 days of invoice date, the Owner shall deduct the amount due from subsequent payments to the Contractor in order to reimburse designers. Request for approval shall be accompanied by working fixture samples (with an appropriate lamp, complete photometric, mechanical and electrical data, list of materials and finishes and unit cost to the Owner) of both the specified brand and the proposed substitutes as required to make complete comparison and evaluation. These samples shall be in addition to those required by Lighting Fixture Specification. The above data shall be delivered separately to the Architect and the Lighting Designer. The fixture samples shall be furnished and installed, at the bidder's expense, at the location selected by the Architect. In addition, the bidder shall furnish the Architect and the Lighting Designer with the name and location of at least one completed project where each proposed substitute has been in operation for a period of at least six (6) months, as well as the names and addresses of the Owner, the Lighting Designer and the Architect of record. ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS Copyright 2011 Gensler 26 51 00 - 2 December 12, 2013 Bid & Permit Gensler 01.9462.002 1.8 Transbay Marketing Center 50 Fremont Street, 21st floor San Francisco, CA SUBMITTALS A. For standard catalog items with no modifications, submit catalog cut sheets prepared by the manufacturer which clearly show all elements to be supplied and all corresponding product data (including lamping; ballast manufacturer and model number; voltage; accessories or options and any miscellaneous items detailed in the written description of the specification.) If cut sheet shows more than one (1) fixture type, all non-applicable information shall be crossed out. B. For standard cataloged fixtures: 1. 2. Submit one sample cone for each fixture type for review. Submit a certificate of compliance with Alzak finish requirements with all requests for approval. When more than one louver panel occurs in a fixture, submit as a part of shop drawings the dimensioned layout of individual louver panels and supporting "tee" members. C. For custom fixtures, modified fixtures or linear fluorescent fixtures mounted in continuous rows, submit an engineered line drawing prepared by the manufacturer showing all details of construction, lengths of runs, lamping layout, pendant locations, power locations, finishes and list of materials. Drawings must be to scale. Contractor shall provide manufacturer with field dimensions where required. If scallop shields, wallwash reflectors or baffles are required, drawings shall indicate relative position to wall or adjacent vertical surface. D. For all submittals under paragraphs A through C above, manufacturer shall provide submittals with fixture installation instruction sheets. E. For all submittals under paragraphs A through C above, manufacturer shall provide submittals within two weeks of receipt of order. All submittals shall have project name and fixture type clearly shown. F. Fixture cuts and shop drawings shall be submitted in quantities and format as described in the general conditions section the specification. G. The Architect shall make the final determination as to whether or not the submittal contains sufficient information and reserves the right to request a shop drawing if the fixture cut is insufficient. H. MOCK-UPS 1. 2. 3. It shall be the responsibility of the Contractor to provide a mock-up of the lighting fixture or lighting systems as indicated in the fixture description. The mock-up shall be erected within a time period and in a location that is acceptable to the Architect. The mock-up installation shall closely conform to the conditions of the actual installation as to: height, distance from ceiling, number and type of lamps, material, color and etc. The Contractor shall submit a written description of each proposed mock-up with drawings in order to obtain the Architect's approval prior to commencement of each mock-up. The purpose of the mock-up will be to study the general appearance and performance of the intended lighting systems. At that time, certain minimal test variations may be requested as to lamp location, lamp type, reflector shape, color and etc. Final modifications, if any, shall be considered a part of these Specifications and shall be accomplished with no additional cost to the Owner. ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS Copyright 2011 Gensler 26 51 00 - 3 December 12, 2013 Bid & Permit Gensler 01.9462.002 I. SAMPLES 1. 2. 3. 4. 1.9 Transbay Marketing Center 50 Fremont Street, 21st floor San Francisco, CA It shall be the responsibility of the Contractor to provide a sample(s) fixture as indicated in Section 26 06 51, Lighting Fixture Schedule. When samples are called for the manufacturer shall provide two working samples complete with lamp, ballast (rated for 120 Volt operation) and 6’ pig-tail with 3-prong Edison plug. The sample(s) shall be shipped to a location that is determined by the Architect. Shipping and return shipping costs shall be provided as part of the contract. The purpose of the sample is to review manufacturing techniques, detailing, lamping and scale. Sample fixtures must be approved prior to fabrication of fixtures for the project. Minor modifications, if any, shall be considered part of these Specifications and shall be accomplished with no additional cost to the Owner. Sample fixtures may not be used on the project. EXTRA STOCK A. Furnish to the Owner and store at the site where directed, extra stock of each type of lighting fixture type and lamp type installed in the Project in quantities as required by Owner, packaged in manufacturer’s unopened cartoons and identified as to contents by fixture type. B. Furnish items above with appropriate quantity of each exposed trim, fastener, bracket and other items as required for a complete installation. 1.10 WARRANTIES A. All fixtures and workmanship shall be guaranteed free of defects and fully operational for a minimum of one year after the acceptance of the project by the Owner. Any fixtures or workmanship found to be defective during the warranty period will be either fixed or replaced by the Contractor at no cost to the Owner. B. Ballasts for fluorescent fixtures shall be covered by a five year warranty against defects in workmanship or material. Warranty shall include in-warranty service program providing for payment of authorized labor charges incurred in replacement of inoperative, in- warranty ballasts. PART 2 - PRODUCTS 2.1 GENERAL MATERIAL REQUIREMENTS A. Ferrous mounting hardware and accessories shall be finished using either a galvanic or phosphate primer/baked paint process to prevent corrosion and discoloration of adjacent materials. B. For weatherproof and vaportight installation, painted finishes of fixtures and accessories shall be weatherproof enamel using proper primers or hot dipped galvanized and bonderized epoxy, in accordance with manufacturer’s requirements. Unless otherwise specified all painted surfaces shall have a life expectancy of not less than twenty years. 1. 2. Hangers shall be conduit with chemically resistant, weatherproof, baked enamel finish. Where dissimilar metal parts come in contact with each other, apply to both surfaces a coating material to prevent corrosion. ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS Copyright 2011 Gensler 26 51 00 - 4 Gensler 01.9462.002 3. December 12, 2013 Bid & Permit Transbay Marketing Center 50 Fremont Street, 21st floor San Francisco, CA Colors shall be as specified in the Section 26 06 51, Lighting Fixture Schedule section of this specification. C. Fasteners shall be manufactured of non-magnetic stainless steel or anodized aluminum, except in indoor applications where galvanized steel shall be acceptable. D. Fixtures shall be free of light leaks and shall be designed to provide sufficient ventilation of lamps and ballasts including vent holes where required. E. All sheet metal work shall be free from tool marks and dents and shall have accurate angles bent as sharp as compatible with the gauges of the required metal. All intersections and joints shall be formed true and of adequate strength and structural rigidity to prevent any distortion after assembly. All sheet metal shall be free of light leaks. All edges shall be finished so there are no sharp edges exposed. All miters shall be in accurate alignment with abutting intersecting members. Piecing of plates in individual runs in single planes and the use of spliced pieces or filler material to cover defective workmanship shall not be acceptable. Sheet metal work shall be properly fabricated so that planes will not deform (i.e. become concave or convex, due to normal expected ambient and operating conditions). F. Lampholders shall hold lamps securely against normal vibrations and maintenance handling. G. Wiring channels and lampholder mountings shall be rigid and accurately made. H. Reflector Cones: 1. 2. 3. 4. Provide 45° lamp and lamp image cut-off unless otherwise specified. In fixtures where upper reflector is separate from cone, cut-off shall be 45° unless otherwise specified. Plastic materials shall not be used for reflector cones or aperture plates. Fixtures in which reflector cones are riveted or welded to housing or where removal of cone requires pressure to be applied to finished surface of reflector shall not be acceptable. Cone flange shall be formed as an integral part of the cone and shall have identical color and finish as the cone, except as shown. The flange major surface shall be perpendicular to the cone axis. The width of the flange shall adequately cover the ceiling opening without light leaks. No fixture parts (housing, mounting frame, etc.) shall be visible between the ceiling surface and the edge of the cone flange. The same requirement shall be applicable to fixtures where main reflector extends down to the bottom edge of the fixture without a separate cone. In such case, the flange shall be formed as an integral part of the main reflector. 5. Reflector cones shall be manufactured of uniform gauge, not less than 0.032" thick, high purity aluminum Alcoa 3002 alloy free of spin marks or other defects or blemishes caused during manufacturing. 6. The finish of the inner surface of the reflector shall be highly specular as produced under the Alzak process. The reflector shall have an anodic coating of not less than four mils thick. The reflector inner surface shall be free of water spotting and shall maintain a reflectivity ratio of not less than 85% on clear specular finish. The reflector shall have a low iridescence finish free from multiple colors seen from normal viewing angles. Colors shall be derived from dyes supplied by Sandoz Chemical Company or approved equal. The reflecting surface of the cone shall be tested for proper sealing. Test per ASTM B136-63T. 7. ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS Copyright 2011 Gensler 26 51 00 - 5 December 12, 2013 Bid & Permit Gensler 01.9462.002 I. 8. Fixtures with Alzak reflector cones, unless otherwise specified, must be furnished by the same manufacturer. 9. Reflector cone retention devices shall not deform cone in any manner whatsoever. 10. Submit a certificate of compliance with Alzak finish requirements with all requests for approval. Lenses: 1. Fresnel: a. b. c. d. 2. 3. Lens shall have uniform brightness throughout the entire visible area at angles from 45° to 90° from vertical, without bright spots or striations. Lens shall have opaque risers; color shall be as specified in Section 26 06 51, Lighting Fixture Schedule. Finish of visible regress surface of door shall be matte baked enamel paint, special color as selected by Architect. All fixtures with fresnel lenses, unless otherwise specified, must be furnished by the same manufacturer. Glass: a. b. Flat glass lenses shall be heat tempered borosilicate glass unless otherwise noted. Glass finishes, i.e. sandblasting, etching, polishing shall be performed as described in the fixture description. Acrylic: a. b. c. J. Transbay Marketing Center 50 Fremont Street, 21st floor San Francisco, CA Lenses shall be of injection molded crystal clear material 100% virgin acrylic (except as shown). For lenses with male pattern of pyramids or cones, specified minimum thickness refers to distance from flat surface to base of pyramids (cones), or thickness of undisturbed material. For lenses with female pattern, specified minimum thickness refers to overall thickness of material. Lenses shall fully eliminate lamp images when viewed from all directions within the 45° to 90° angle from vertical when the ratio of lamp spacing to the distance from lamp underside to top of lens does not exceed 1.50. Within the viewing angle from 0° to 45° the ratio of maximum brightness (under a lamp) to minimum brightness (between lamps) shall not exceed 3 to 1. Finishes, i.e. sandblasting, etching, polishing shall be performed as described in the fixture description. Louvers: 1. Parabolic: a. b. c. Louvers shall be continuously bound in channel formed frame, finish and color as specified or as selected. Louver shall provide a minimum visual cut-off to the lamp of 45°. The finish of the inner surface of the reflector shall be highly specular as produced under the Alzak process. The reflector shall have an anodic coating of not less ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS Copyright 2011 Gensler 26 51 00 - 6 December 12, 2013 Bid & Permit Gensler 01.9462.002 2. Transbay Marketing Center 50 Fremont Street, 21st floor San Francisco, CA than four mils thick. The reflector inner surface shall be free of water spotting and shall maintain a reflectivity ratio of not less than 85% on clear specular finish. The reflector shall have a low iridescence finish free from multiple colors seen from normal viewing angles. Flat Blade: a. b. c. Provide flat blade louvers within formed frame, finish and color as specified. Louvers to provide minimum of 45° degree cut-off from lamp image. Blade thickness to minimum .125” flat steel. K. In adjustable fixtures, aiming and positive locking devices shall be provided. L. Fixtures with an adjustable lamp and using a lamp with an asymmetrical light pattern shall have an aiming stop which can be permanently set so that the lamp shall remain correctly positioned after service or relamping. M. Fluorescent Fixtures: 1. Hot Cathode: a. Housing: 1) 2) 3) No. 22 minimum gauge steel, bonderized or equal rust protected, or No. 16 gauge aluminum rigid construction, suitable for continuous row mounting where indicated. Finish: Baked enamel paint finish unless otherwise specified, color as specified or as selected. Exterior Fixture Finishes: a) b) b. c. Reflector: Minimum 85% reflectance. Lightshields: 1) 2) d. Frames: Provide extruded aluminum frames with mitered corners filled and ground smooth. Provided with concealed hinges and invisible latching. No cross bars shall be permitted over lightshields. Lampholders: 1) e. Unless otherwise specified, all painted surfaces shall have an outdoor life expectancy of not less than 20 years. Surfaces shall be prepared, primed, and material applied in accordance with the manufacturer's requirements. Color: Colors shall be as specified under Section 26 06 51, Lighting Fixture Schedule. Lampholders shall be UL listed, and meet IEC-60400, “International Standard: Lampholders for tubular fluorescent lamps and startholders”. For rapid start lamps on single ballasts, provide one (1) grounding lampholder per lamp. Lampholders operating with open circuit voltage in excess of 300 volts shall ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS Copyright 2011 Gensler 26 51 00 - 7 December 12, 2013 Bid & Permit Gensler 01.9462.002 Transbay Marketing Center 50 Fremont Street, 21st floor San Francisco, CA be safety type and shall open supply circuit when lamp is removed from lampholder. 1) 2) f. g. Mount lamps used in rapid start circuits 430mA and below: within 1/2" of grounded metal as long as the lamp. 800mA and 1500mA lamps: mount within 1" of grounded metal as long as the lamp. Fluorescent fixtures shall conform to NEMA Standards, including references to fixture dimensions and temperature ratings. Ballasts shall be electronic high power factor (greater than 90%), ballast factor (greater than 87%) and approved by UL (UL 935 listed). Ballasts shall be certified for voltage and number of lamps specified and equipped with internal thermal protectors unless otherwise specified. 1) 2) 3) 4) 5) Ballasts shall have a Crest Factor of less than one and seven tenths. Ballasts for indoor applications shall be "Class P". Provide multi-lamp ballasts where possible including continuous rows of one-lamp fixtures, and one-lamp ballasts only where the fixture layout does not permit the use of multi-lamp ballasts. Ballast shall be a dedicated ballast to operate a specific lamp, i.e., T8 ballasts specifically for a T8 lamp. All ballasts shall operate at the voltage as described in Section 26 06 51, Lighting Fixture Schedule and confirmed on electrical drawings. Ballasts shall operate lamps properly through the following supply voltage ranges: a) b) 6) 7) 8) 9) 10) 11) 12) Ballast shall tolerate sustained open circuit and short circuit output conditions without damage. Frequency shall be 20 Khz or greater except as noted without any discernible flicker (<3% flicker index). Ballast shall have input current total harmonic distortion not to exceed 10% of the fundamental harmonic (60 Hz). Ballast shall not contain PCB materials. Ballast shall provide transient immunity as recommended by ANSI C62.411991 location Category A2. Ballast shall be encapsulated to ensure maximum thermal and structural integrity. Ballast minimum sound ratings: a) b) c) d) 13) 14) Rated voltage +/- 10% Universal voltage of 108 to 305V on 50 or 60Hz supply 265 mA: Class 'A' 430 mA: Class 'A' 800 mA: Class 'B' 1500 mA: Class 'C' Ballasts for T5, T5HO, and CFL lamps shall incorporate auto resetting lamp shutdown circuitry for end of lamp life protection thereby allowing for relamping without the need to cycle power. Program Rapid start ballasts shall be used when the lamps are to be frequently turned on/off (with cycles of less than 3 hours). Otherwise ballast ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS Copyright 2011 Gensler 26 51 00 - 8 December 12, 2013 Bid & Permit Gensler 01.9462.002 15) 16) 17) Transbay Marketing Center 50 Fremont Street, 21st floor San Francisco, CA shall provide instant starting sequence consistent with ANSI standard C82.11-1993. Ballast shall be manufactured in an ISO 9002 certified facility. Manufacturer shall have minimum 15 years of manufacturing experience. Ballast, unless specified otherwise, shall be same manufacturer and model in each fixture of the same type. Acceptable ballast manufacturers unless otherwise noted are: a) b) c) d) h. 2. Advance Universal Lighting Technologies Osram/Sylvania Lutron Lighting fixtures recessed in a hung ceiling where the space above the hung ceiling is used as a plenum chamber for either supply or return air for the air conditioning system shall be designed, manufactured and wired to conform to NEC Article 300-22. When specified, fluorescent luminaires shall have radio frequency interference (RFI) or electromagnetic interference filters. Filters shall either be integral or external to the ballast, but must be integral to the luminaire assembly with one filter per ballast and shall suppress electromagnetic interference in the AM radio band from 500 to 1700 kHz. Filters shall also be in the circuit serving the lighting fixture. O. Solid State Lighting / Light Emitting Diode (LED) Lamps and Luminaires: 1. General: a. b. c. d. e. f. Luminaire manufacturer shall have a minimum of five (5) years experience in the manufacture and design of LED products and systems and no less than one hundred (100) North American installations. Unless otherwise specified, all LED luminaires and power/data supplies shall be provided by a single manufacturer to ensure compatibility. All components, peripheral devices and control software are to be provided by and shall be the responsibility of a single entity. All components shall perform successfully as a complete system and shall operate as described in Lighting Designer’s Control Narrative documents or Section 26 06 51, Lighting Fixture Schedule. Provide submittals as described in Part 1 above. Include all components necessary for a complete installation. Provide all power supplies, synchronizers, data cables, and data terminators for a complete working system. All LED sources used in the LED luminaire shall be of proven quality from established and reputable LED manufacturers and shall have been fabricated after 2007. Acceptable LED lamp manufacturers unless otherwise noted are: 1) 2) 3) 4) 5) Cree, Inc. Philips Lighting Nichia Corporation Norlux Opto Technology, Inc. ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS Copyright 2011 Gensler 26 51 00 - 9 December 12, 2013 Bid & Permit Gensler 01.9462.002 6) 2. Osram Optronic Semiconductors Replacement and Spares: a. Manufacturer shall provide written guarantee of the following: 1) 2) 3) b. 2) c. Manufacturer will keep record of original bin for each LED module and have replacement modules from the same bin available for three (3) years after date of installation. Manufacturer will keep an inventory of replacement parts (source assembly, power and control components). Manufacturer’s LED system will not become obsolete for ten (10) years: Manufacturer will provide exact replacement parts, or provide upgraded parts that are designed to fit into the original luminaire and provide equivalent distribution and lumen output to the original, without any negative consequences. All parts of system shall replaceable in field. Manufacturer shall provide written guarantee of the following: 1) 3. Transbay Marketing Center 50 Fremont Street, 21st floor San Francisco, CA Manufacturer has in place a written recycling and re-use program, and will accept returned product and/or components for recycling or re-use. Manufacturer will properly dispose of non-recyclable components that are deemed harmful to the environment. System shall carry a full warranty for five (5) years. Manufacturer shall be responsible for cost of labor not to exceed $50 per individual part, and cost of shipping, to replace any component of the system that fails within 2 years of installation. Products and Components – Performance a. b. c. d. e. f. g. h. LED luminaires and components shall be UL listed or UL classified. LED luminaires and components shall be CE certified. All LED luminaires shall be subjected to the following JEDEC Reliability Tests for Lead-free Semiconductors: HTOL, RTOL, LTOL, PTMCL, TMSK, Mechanical Shock, Variable Vibration Frequency, SHR, Autoclave. To ensure luminaire quality, luminaire shall have been tested under accelerated life test conditions including an operating temperature span of 360 degrees F, and cyclic loading up to 60G. All products included in system shall use Mil-Std 810F, Random Vibration 7.698g as a minimum standard. In installations subject to vibration, luminaire shall be installed with vibration isolation hardware to sufficiently dampen vibrations. All LED components shall be mercury and lead-free. All manufacturing processes and materials shall conform to the requirements of the European Union's Restriction on the Use of Hazardous Substances in Electrical and Electronics Equipment (RoHS) Directive, 2002/95/EC. LEDs shall comply with ANSI/NEMA/ANSLG C78.377-2008 – Specifications for the Chromaticity of Solid State Lighting Products. Color shall remain stable throughout the life of the lamp. Color shall match approved sample. ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS Copyright 2011 Gensler 26 51 00 - 10 December 12, 2013 Bid & Permit Gensler 01.9462.002 i. j. k. l. m. n. o. p. q. r. s. t. u. v. Transbay Marketing Center 50 Fremont Street, 21st floor San Francisco, CA LEDs shall comply with IESNA LM-80 – Standards for Lumen Maintenance of LED Lighting Products White LEDs shall have a rated source life of 50,000 hours under normal operating conditions. RGB LEDs shall have a rated source life of 100,000 hours. LED “rated source life” is defined as the time when a minimum of 70% of initial lumen output remains. Luminaire assembly shall include a method of dissipating heat so as to not degrade life of source, electronic equipment, or lenses. LED luminaire housing shall be designed to transfer heat from the LED board to the outside environment. Luminaire housing shall have no negative impact on life of components. Manufacturer shall supply in writing a range of permissible operating temperatures in which system will perform optimally. High power LED luminaires shall be thermally protected using one or more of the following thermal management techniques: metal core board, gap pad, and/or internal monitoring firmware LEDs shall be adequately protected from moisture or dust in interior applications. For wet and damp use, LED-based luminaires itself shall be sealed, rated, and tested for appropriate environmental conditions, not accomplished by using an additional housing or enclosure. Such protection shall have no negative impact on rated life of source or components, or if so, such reductions shall be explicitly brought to the attention of the designer. All hardwired connections to LED luminaires shall be reverse polarity protected and provide high voltage protection in the event connections are reversed or shorted during the installation process. The LED luminaire shall be operated at constant and carefully regulated current levels. LEDs shall not be overdriven beyond their specified nominal voltage and current. Manufacturer shall be able to provide supporting documentation of the product meeting third party regulatory compliance. Manufacturer shall ensure that products undergo and successfully meet appropriate design and manufacturability testing including Design FMEA, Process FMEA, Environmental Engineering Considerations and Laboratory Tests, IEC standards and UL/CE testing. All LED luminaires (100% of each lot) shall undergo a minimum twenty-four (24) hour burn-in during manufacturing, prior to shipping. Manufacturer shall provide Luminaire Efficacy (lm/W), total luminous flux (lumens), luminous intensity (candelas) chromaticity coordinates, CCT and CRI. optical performance, polar diagrams, and relevant luminance and illuminance photometric data. Provide data in IES file format in accordance with IES LM-792008, based on test results from an independent Nationally Recognized Testing Laboratory. Power / data supply shall have the following: 1) 2) 3) 4) Supply outputs shall have current limiting protection. Supply shall provide miswiring protection. Supply shall have power factor correction. Supply shall provide connections that are conduit-ready or clamp-style connections in the case of low-voltage wiring. ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS Copyright 2011 Gensler 26 51 00 - 11 December 12, 2013 Bid & Permit Gensler 01.9462.002 5) 6) 4. LED Control and Communication – Performance a. b. c. d. e. f. P. Transbay Marketing Center 50 Fremont Street, 21st floor San Francisco, CA Supply shall come with a housing that meets a minimum IP20 rating for dry location installation unless located in a damp or wet location. Supply shall be UL listed for Class 1 or Class 2 wiring LED luminaires shall be network controllable via digital control. The LED system shall use integral and differential non-linear control. Constant data transmission rates shall be employed, resulting in the output being independent of distance of cable between power supply and light source within the specified length. LED system shall have a selectable means of external control via a data network. Each LED luminaire and/or node shall have the capability to be set to a unique and individual address. Address shall be selectable through on board switches or by an external hardware or software method. The LED system shall be scalable, with every LED luminaire/address in the system capable of being controlled by a single, centralized controller. Wiring: 1. Voltage Rating a. b. 2. For voltages up to 120 volts fixture wiring shall be rated for 300 volts minimum. For voltages above 120 volts fixture wiring shall be rated for 600 volts minimum. Temperature Rating - Internal to Fixture a. b. All wiring shall be code-approved for fixture wiring, and shall comply with the following temperature ratings unless fixture design or local codes require higher temperature wire. Fluorescent 1) minimum rating between lampholder(s) and internal ballast. 2) minimum between ballast and separate junction box, or connection within integral wireway. 3. Temperature Rating - External to Fixture a. b. 4. All flexible cord wiring between fixture components or to electrical receptacle and not in wireways shall have a minimum temperature rating of 105°C. Cord type shall be suitable for application and shall be fitted with proper strain relief and watertight entries where required by application. Splices a. b. Splices internal to fixture shall be made within separate splice compartments and shall utilize nylon insulated crimped connections or insulated quick disconnects. Splices to branch circuit wiring in separate junction boxes shall utilize flame retardant thermoplastic caps with fully seated helical metal spring and threaded entry. ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS Copyright 2011 Gensler 26 51 00 - 12 Gensler 01.9462.002 5. 6. 7. Q. December 12, 2013 Bid & Permit Transbay Marketing Center 50 Fremont Street, 21st floor San Francisco, CA No internal wiring shall be visible at normal viewing angles, i.e., above 45° from vertical. Use additional wire clamps if necessary. Anticipate increased visibility if fixtures are mounted on or recessed within a sloping surface. Any fixture fed from more than one panel, i.e., for normal and night or emergency operation, shall have separate neutrals to each panel. Furnish code-approved wiring in ceiling cavities forming air plenums. Lamps: 1. Hot cathode fluorescent lamps: a. b. Shall be 3000° Kelvin, with 85 CRI or greater except as shown. Refer to Section 26 06 51, Lighting Fixture Schedule for details. All lamps, except as specified, shall be of the same manufacturer: 1) 2) 3) General Electric North American Philips Osram/Sylvania PART 3 – EXECUTION 3.1 SHIPPING AND STORAGE A. All fixtures received at the site shall be stored in clean and dry space until fixtures are installed. B. Manufacturer shall clearly mark each box with fixture designation prior to shipping. C. Reflector cones, baffles, louvers, aperture plates, and decorative elements of fixtures shall be packed by the manufacturer separate from the housing (body, stem, etc.) of the fixture. 3.2 LOCATION A. Locations of fixtures are shown diagrammatically. Verify exact location and spacing with Reflected Ceiling Plans and other reference data before ordering of fixtures and during installation. B. Notify Architect about field conditions at variance with Contract Documents before commencing installation. C. Coordinate space conditions with other trades before ordering of fixtures. D. Pendant mount, as approved, surface type fixtures where required to meet space conditions. E. Coordinate length of continuous-run fluorescent fixtures with adjacent walls, partitions, coffers and other architectural elements as required. 1. Continuous runs shall be defined as the optimal combination of 3’ and 4’ lamp length as necessary to complete runs with no more than 6” of free space at either end of the run as provided by the contractor. ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS Copyright 2011 Gensler 26 51 00 - 13 December 12, 2013 Bid & Permit Gensler 01.9462.002 3.3 Transbay Marketing Center 50 Fremont Street, 21st floor San Francisco, CA INSTALLATION A. Provide accessories as required for ceiling construction type indicated on Finish Schedule. Fixture catalog numbers do not necessarily denote specific mounting accessories for type of ceiling in which a fixture may be installed. B. Provide adequate and sturdy support for each lighting fixture. Contractor shall be responsible for verifying weight and mounting method of all fixtures and furnish and install suitable supports. Fixture mounting assemblies shall comply with all local seismic codes and regulations. C. Install rows of fixtures accurately on straight lines unless otherwise indicated on drawings. Coordinate with mechanical work. D. Install fixtures with vent holes free of air blocking obstacles. E. Where plaster ceilings occur, furnish plaster frames for setting under other applicable sections. Direct the setting and be responsible for correct location; make sure the bottom of frame is flush with finished ceiling, forming screed edge for finished plaster. 1. Fixtures shall be supported by plaster frames utilizing yokes or leveling lugs. a. b. 2. 3. Fixtures and support elements shall not be mounted to or in contact with ducts or pipes. Yoke shall have channel cross section of sufficient gauge, and shall support a fixture by means of not fewer than two (2) bolts each. If air diffusers are located in common continuous rows with lighting fixtures in plaster ceilings, furnish plaster frames of proper length to accommodate diffusers. Lighting fixtures recessed in ceilings which have a fire resistive rating of one hour or more shall be enclosed in a box which has a fire resistive rating equal to that of the ceiling. F. Contractor shall be responsible for adjusting aperture rings on all ceiling recessed fixtures to accommodate various ceiling material thickness. Contractor shall responsible for coordinating the cut-out size in ceiling to ensure aperture covers cut-out entirely. The bottom of aperture rings shall be flush with finished ceiling or not more that 1/16" above. Under no circumstances will the aperture ring extend below the finished ceiling surface. G. For fixtures with variable position lampholder assemblies Contractor shall confirm prior to installation proper lampholder (socket) position in field, and shall adjust, if necessary, after coordination with manufacturer. H. Surface Mounted Fixtures: Support surface mounted fixtures from structural members other than ceiling tees. I. Pendant Mounted Fixtures: 1. 2. Pendant mounted fixtures shall be supported from structural framework of ceiling or from inserts cast into slab. All pendants shall have swivel aligners located at the top ends; pendants shall be 1/2" rigid steel conduit unless specifically indicated otherwise on drawings or in specifications. ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS Copyright 2011 Gensler 26 51 00 - 14 Gensler 01.9462.002 3. December 12, 2013 Bid & Permit Transbay Marketing Center 50 Fremont Street, 21st floor San Francisco, CA All fluorescent pendant and surface mounted fixtures shall be supported with two (2) supports per four foot section or three (3) per eight foot section unless otherwise recommended by manufacturer. J. Bracket Mounted Fixtures: For each bracket fixture, provide flanged metal stem attached to outlet box, with threaded end suitable for supporting the fixture rigidly in design position. Flanged part of fixture stud shall be of broad base type, secured to outlet box at not fewer than three (3) points. K. Top Relamping Fixtures: Top relamping fixtures shall have the necessary top-relamping screws loosened and moderately tightened, prior to installation, to assure ease of operation when relamping is required. L. Fluorescent Fixtures: Replace noisy ballasts as directed, at no cost to the Owner. M. Mask the trims and bottoms of all lighting fixtures if necessary to protect the fixture during construction. N. At the completion of construction clean the bottoms, the trim, the reflecting surfaces, lenses, baffles, louvers and reflector cones of all lighting fixtures so as to render them free of any material, substance or film foreign to the fixture. If the luminaires are deemed dirty by the Architect at the completion of the project, the Contractor shall clean them at no additional cost to the Owner. Luminaire components whose finishes are damaged shall be replaced at no cost to the Owner. O. Ascertain and ensure that all lamps installed are exactly as specified for each fixture type. P. Replace all burned-out or inoperative lamps, and inoperative ballasts in all fluorescent fixtures before the building is accepted by the Owner so that all lighting fixtures will be in first-class operating condition. Q. Provide labor and materials for final aiming of all adjustable fixtures under the Architect's supervision. Aiming shall take place immediately before building is turned over to Owner, after regular working hours where required. END OF SECTION 26 51 00 ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS Copyright 2011 Gensler 26 51 00 - 15