20131212 Trans Bay BID PERMIT SET 6 Lighting Combined Specs

December 12, 2013
Bid & Permit
Gensler
01.9462.002
Transbay Marketing Center
50 Fremont Street, 21st floor
San Francisco, CA
SECTION 26 06 51 – LIGHTING FIXTURE SCHEDULE
PART 1 – GENERAL
1.1
A.
1.2
A.
1.3
A.
1.4
DESCRIPTION
Provide and install lighting fixtures as shown on drawings and as specified in this and all
related Sections.
RELATED SECTIONS
26 51 00
Architectural Lighting Fixtures, Lamps & Ballasts
DEFINITIONS
The term Architect refers to the Architect, Interior Designer, Lighting Designer or Owner’s
Representative individually or collectively.
GENERAL REQUIREMENTS
A.
Provide all lighting fixtures as shown complete with all lamps, completely wired, controlled
and securely attached to supports.
B.
Where a catalog number and a narrative or pictorial descriptions are provided, the written
description shall take precedence and prevail.
C.
General Contractor shall provide electrical subcontractor with entire lighting specification
(including fixture illustrations and sketches); electrical subcontractor shall provide each
specified manufacturer with complete information about the fixtures they will supply.
D.
Type of fixtures shall be as indicated alphanumerically and as specified.
E.
Fixture details shown may be modified by the manufacturer provided all of the following
conditions have been met:
1.
2.
3.
4.
1.5
Fixture performance is equal or improved;
Structural, mechanical, electrical, safety, and maintenance characteristics are equal or
improved;
Cost to the Owner is reduced or equal.
Modifications have been reviewed by the Architect and have been approved by the
Architect in writing.
LIGHTING FIXTURE DESCRIPTIONS
Lighting Fixture Schedule
Copyright 2011 Gensler
26 06 51 - 1
Gensler
01.9462.002
December 12, 2013
Bid & Permit
Transbay Marketing Center
50 Fremont Street, 21st floor
San Francisco, CA
Lighting Fixture Schedule
Copyright 2011 Gensler
26 06 51 - 2
Gensler
01.9462.002
December 12, 2013
Bid & Permit
Transbay Marketing Center
50 Fremont Street, 21st floor
San Francisco, CA
Lighting Fixture Schedule
Copyright 2011 Gensler
26 06 51 - 3
Gensler
01.9462.002
December 12, 2013
Bid & Permit
Transbay Marketing Center
50 Fremont Street, 21st floor
San Francisco, CA
Lighting Fixture Schedule
Copyright 2011 Gensler
26 06 51 - 4
Gensler
01.9462.002
December 12, 2013
Bid & Permit
Transbay Marketing Center
50 Fremont Street, 21st floor
San Francisco, CA
Lighting Fixture Schedule
Copyright 2011 Gensler
26 06 51 - 5
Gensler
01.9462.002
December 12, 2013
Bid & Permit
Transbay Marketing Center
50 Fremont Street, 21st floor
San Francisco, CA
END OF SECTION 26 06 51
Lighting Fixture Schedule
Copyright 2011 Gensler
26 06 51 - 6
Lighting Fixture Cut Sheets
For Permit & Bid Set
Transbay Marketing Center
10 December 2013
HORNET® HP DOWNLIGHT
HDL-HP-RD
LED
3.5” ROUND DOWNLIGHT LED
APPLICATIONS:
Retail and commercial ambient lighting
CONSTRUCTION:
20 ga. galvanized steel frame
18 ga. galvanized steel splice housing and hanger
brackets
Die-cast optical housing and trim
Extruded aluminum and die-cast heat sink
MOUNTING:
For use in T-grid or sheet rock ceilings,
(max ceiling thickness 1”)
PROJECT:
LABELING:
R
C
US
TYPE:
4 3/4”
For indoor use only
IC/AT rated (17w only, not Energy Star rated)
Damp location
11 3/4”
7 3 /4 ”
ELECTRICAL:
Electronic constant current LED driver
120v or 277v input
Dimming options available for Triac, ELV, 0-10v and
Lutron systems. See following pages for more information.
This product complies with IEEE C62.41 for surge endurance up to 2.5KV. Amerlux® recommends using additional surge protection with this unit (supplied by others),
surge damage is not covered by warranty.
OPTICS:
LED:
Color Temp Options: 2700K, 3000K, 3500K, 4000K
CRI: 85 typ. (2700K, 3000K, 3500K, 4000K)
90 typ. (3000K)
Binning: 3 MacAdam (SDMC)
Lumen Maintenance: >70% of intial lumens @ 50,000 hrs
Lumen Output per head at 3000K:
17w: Spot 818 typ.
20w: Spot 986 typ.
Flood 748 typ.
Flood 901 typ.
Wide Flood 693 typ.
Wide Flood 835 typ.
3 1/2”
5
4 3/8”
11 /2”
14 1/2” min - 26” max
1
Electrostatic sensitive device,
observe precautions for
handling
/8”
Ceiling Cut Out Dimension: 4” dia.
ELECTRICAL
17w
20w
System
System
Driver
Watts Amps Watts Amps
Electronic 120v 17
0.14
20
0.17
277v 17
0.06
20
0.07
6 3/4”
13”
16 1/2”
IC Housing
5
15”
14 1/2” min 26” max
(see website for details)
ORDERING INFORMATION:
Housing:
Model
Wattage Lamp Driver
Voltage Options
Type
HDL-HP-R 17
LED
E - electronic 120
DIM-ELV- ELV dimming (120v only)
20
277
DIM-TRIAC - Triac dimming (120v only)
HILUME - Lutron Hi-lume® dimming
0-10V - 0-10v dimming
MF - multi-function driver
CP - Chicago Plenum
EM - emergency battery pack
w/remote test switch
IC/AT* - insulated ceiling/air tight
(17w only)
Trim:
Model
Color
Temp
HDL-HP-RD Reflector with White NSP - narrow spot, 12º 2700*
3000
Painted Flange
SP - spot, 15º
MBW - matte black NF - narrow flood, 20º 3500
MWW - matte white MFL - medium flood, 4000
SLVW - matte silver
24º
3000-90*
FL - flood, 28º
(90CRI)
WF - wide flood, 45º
VWF - very wide
flood, 60º
LS - linear spread,
60º x 10º
Complete Example: HDL-HP-R-20-LED-E-120/HDL-HP-RD-MBW-FL-3000
Housing Example: HDL-HP-R-20-LED-E-120
Reflector Example: HDL-HP-RD-MBW-FL-3000
Aperture Finish
Beam Spread
* NOTE: 2700, 3000-90CRI & IC/AT options are not Energy Star rated
Cat #:
Amerlux® reserves the right to change details that do not affect overall function and performance.
Amerlux®, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com
Project:
Transbay Marketing Center
Project #
13168.00
Date:
10 December 2013
Type:
F1
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
HORNET® HP DOWNLIGHT
HDL-HP-RD
LED
3.5” ROUND DOWNLIGHT LED
TYPE:
FIXTURE DATA: For 17w data, multiply by 0.85
Complete photometric data (ies format) available upon request.
20W LED
SPOT
DISTRIBUTION
LTL # 36952
FLOOD
DISTRIBUTION
LTL # 36953
90
WIDE FLOOD
DISTRIBUTION
LTL # 36954
90
90
600
1200
2500
60
60
60
5000
2400
1200
7500
3600
1800
0
30
Candelas at Nadir
Deg
Candela
0
8680
5
7080
15
1074
25
132
35
26
45
2
APPLICATION DATA:
0
30
Candelas at Nadir
Deg
Candela
0
3713
5
3354
15
1502
25
324
35
48
45
5
0
30
Candelas at Nadir
Deg
Candela
0
1821
5
1743
15
1215
25
544
35
123
45
9
Notes and Definitions:
Beam spread is to 50% center beam candlepower (CBCP).
D=Distance to floor or wall.
FC=Footcandles on floor or wall at center beam aiming location.
L=Effective Visual Beam length in feet (50% of maximum footcandle level).
W=Effective Visual Beam width in feet (50% of maximum footcandle level).
CB=Distance across or down to center beam location.
D
W
FC
L
SPOT
D
5.0’
7.5’
10.0’
12.5’
FC
233
126
76
51
L
1.8
2.6
3.3
4.0
W
1.8
2.6
3.3
4.0
FLOOD
D
5.0’
7.5’
10.0’
12.5’
FC
120
59
35
23
L
2.6
3.5
4.7
5.7
W
2.6
3.5
4.7
5.7
WIDE
FLOOD
0o Aiming Angle
Horizontal
Footcandles
D
5.0’
7.5’
10.0’
12.5’
FC
73
33
19
12
L
3.2
4.7
6.3
7.8
W
3.2
4.7
6.3
7.8
Amerlux®, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com
Project:
Transbay Marketing Center
Project #
13168.00
LIT-1242 rev 10/13
Date:
10 December 2013
Type:
F1
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
HORNET® HP DOWNLIGHT
HDL-HP-RD
LED
3.5” ROUND DOWNLIGHT LED
TYPE:
DIMMING COMPATIBILITY:
Amerlux® “Hornet®” fixtures are compatible with all major dimming protocols prevalent in the United States. Please see
below for general compatibilities and wiring diagrams. Amerlux® recommends testing your unique dimming configuration as
the exact full configuration (Dimmer, Fixture Quantity, Voltage, etc) may affect dimming performance.
TRIAC (Forward Phase) DIMMING (-DIM-TRIAC Option) ---not compatible with 12w module--Utilizes “Standard” incandescent dimmers that are in wide use in installations across the US. Best for retrofit applications
where Triac dimmers are installed.
Wiring Diagram
Notes:
• 120v ONLY
Driver
Triac
• Dims down to less than 5% light output (most cases)
Black Black
Dimmer
LED
• Consult Dimming manufacturer for installastion
RED
White
(by others)
instructions - DO NOT SHARE NEUTRALS!
Green
• Must meet dimmer Minimum Load Requirements
per dimming manufacturer
120v
Compatible Dimmers
Wall Box (Incandescent Style, Wattage as required)
Central System
Lutron “Diva”
Lutron “Vareo”
ETC “SR” Rack w/D20
ETC “DRD” Rack w/D20
Lutron “Nova-T”
Lutron “Skylark”
Module
Module
Lutron “Maestro”
Lutron “GP” Panel
Lutron Grafix Eye QS
ELV - Electronic Low Voltage (Reverse Phase) DIMMING (-DIM-ELV Option)
Utilizes specialized “ELV” dimmers. Best for New Construction appilications
Notes:
• 120v ONLY
• Dims down to less than 5% light output (most cases)
• Consult Dimming manufacturer for installastion
instructions - DO NOT SHARE NEUTRALS!
• Must meet dimmer Minimum Load Requirements
Wiring Diagram
Driver
Black Black
RED
White
Green
ELV
Dimmer
(by others)
LED
120v
Compatible Dimmers
Wall Box (ELV Style)
Lutron “Diva”
Lutron “Nova-T”
Lutron “Maestro”
Leviton “Surslide”
Lutron “Vareo”
Lutron “Skylark”
Leviton “Vizio”
Central System
ETC “SR” Rack w/ELV10
Module
Lutron “GP” Panel with
PHPM-PA Interface
ETC “DRD” Rack w/ELV10
Module
Lutron Grafix Eye QS with
PHPM-PA Interface
0-10V - DIMMING (-0-10V Option)
Integrates into a variety of building management and day-lighting controls
Wiring Diagram
Notes:
• 120v - 277v
• Dims down to less than 10% light output
• Requires interface to turn off power to driver
• Consult Dimming manufacturer for installastion
instructions - DO NOT SHARE NEUTRALS!
Compatible Dimmers
Wall Box
Lutron “Diva” - DVTV with
PP-120H Interface
Leviton Renoir II 0-10v
Driver
Violet Black
RED
Grey
0-10v
Dimmer
LED
Black
White
Green
Bldg
Power or
Interface
Central System
Lutron Grafix Eye with
GRX-TVI Interface
Amerlux®, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com
Project:
Transbay Marketing Center
Project #
13168.00
LIT-1242 rev 10/13
Date:
10 December 2013
Type:
F1
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
HORNET® HP DOWNLIGHT
HDL-HP-RD
LED
3.5” ROUND DOWNLIGHT LED
TYPE:
LUTRON HI-LUME / ECO-SYSTEM (-DIM-HILUME Option)
Integrates into a variety of building management and day-lighting controls
3-Wire Wiring Diagram
Notes:
• 120v or 277v
Driver
• Dims down to less than 5% light output
3-Wire FL
Black
Switched Hot
• May use 3-Wire or Ecosystem Control
Control
Orange
Dimmed Hot
• Consult Dimming manufacturer for installastion
(by others)
White
Neu
instructions - DO NOT SHARE NEUTRALS!
Green
Gnd
Purple/Grey E2
Purple
E1
Compatible Dimmers
Wall Box (3-Wire Fluorescent)
ECO-Sys Bus
DIVA
Cap Wires
Maestro
Nova T
ECO System Digital Control Wiring
Vareo
Cap Lead
Central System
Lutron ECO-System compatible controls
ETC “SR” Rack w/D20F Module
ETC “DRD” Rack w/D20F Module
ECO
System
Control
(by others)
Black
Orange
White
Green
Purple/Grey
Purple
Driver
Switched Hot
Dimmed Hot
Black
RED
LED
Black
RED
LED
VV+
VV+
Neu
Gnd
E2
E1
ECO-Sys Bus
MULTI-FUNCTION
Emergency Configuration
120v/277v
Normal
Power
120v/277v
Normal
Power
Primary
Driver
Emergency system (by
others) to ensure only one
feed is active at a time.
120v/277v
Emergency
Feed
(by others)
Night Light Configuration
LED
Primary
Driver
On/Off
control
LED
(by others)
Secondary
Driver
120v/277v
Constant
Power
Secondary
Driver
In Night Light configuration
Multi-Function driver provides
10 mA of drive current when
primary driver is switched off.
17w = 2% output
20w = 1.5% output
In Emergency configuration
Multi-Function driver provides
100 mA of drive current.
17w = 20% output
20w = 16% output
Patent-Pending
Amerlux®, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com
Project:
Transbay Marketing Center
Project #
13168.00
LIT-1242 rev 10/13
Date:
10 December 2013
Type:
F1
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
Calculite® Compact Fluorescent Open Downlight 8011
Page 1 of 2
4 1/2” Aperture Triple Tube Vertical Lamp
5
11 1/2"
(292 mm)
2
4
1
6
8 1/16"
(210 mm)
3 3/8"
(86 mm)
10 1/2"
(267 mm)
18W
8 1/8"
(207 mm)
Top View
3"
(76 mm)
4 1/2" (115 mm) Dia.
1" (25 mm) min.
2 1/8" (54 mm) max.
Flush
5" (127 mm)
3
Overlap
5 3/4" (147 mm)
1 1/8" (29 mm) max.
Ceiling Thickness
Ceiling Cutout: 5 1/16" (129 mm) Dia.
Reflector Trim
8011CCLW 8011CCLP 8011CCL
8011
Frame-In Kit
Comfort Clear™, White Flange
4118VU
Electronic 120V - 277V Comfort Clear™, Polished Flange
Comfort Clear™, Molded Trim Ring
Add suffix. See options for other finishes.
Features
1.Reflector: 16 ga. Alzak® aluminum, 50° visual cutoff to lamp and lamp
image, medium distribution. Comfort Clear™ low iridescence finish. Selfflanged or flangeless with molded white trim ring (field paintable).
2. Socket Cup: Die-cast aluminum cup effectively dissipates heat and
positions lamp holder. Snaps onto reflector neck to assure consistently
correct optical alignment without tools.
3. Mounting Frame: Die-cast aluminum for dry or plaster ceilings.
4. Retaining Springs: Precision-tooled steel friction springs secure reflector
to mounting frame for quick, tool-less installation.
5. Mounting Brackets: 16 ga. steel. Adjust from inside of fixture. Use 3/4" or
1 1/2" lathing channel, 1/2" EMT, or optional mounting bars.
6.Ballast/J-Box: Outboard mounted to reduce heat transfer and maintain
lamp efficacy and life. Service from below without tools.
Lamp
18W Triple Tube
4-Pin (Amalgam)
Options and Accessories (continued)
Emergency
Add suffix EM
Chicago Plenum
Add suffix LC
Emergency Ltg. Kit
FA EM3E*
FA EM4E*
Fuse (Slow Blow)
Add suffix F
*See Spec. Sheet: FAEM
Mounting Bars & Accessories; see Specification Sheet MBA. Sloped Ceiling
Adapters; see Specification Sheet SCA.
IC Frame available; see C4CFL18 Specification Sheet.
Labels
UL listed for damp locations, I.B.E.W.
Electrical
Note: For ballast electrical data and latest lamp/ballast compatibility refer to
“Ballast” specification sheet for complete electrical data.
UL listed for through branch circuit wiring with max of (8) No. 12 AWG, 90°C
supply conductors.
Options and Accessories
Comfort Clear Finishes
Diffuse
CCD
Champagne Bronze
CCZ
Other Finish
White
WH
Specular Clear
CL
™
1
Alzak® is a registered trademark of ALCOA.
Job Information
Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
1
Specify desired flange
W White, P Polished
Blank - Molded Ring
Lightolier a Genlyte company
www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
© 2011 Genlyte Group LLC • C0711
Project:
Transbay Marketing Center
Project #
13168.00
Date:
10 December 2013
Type:
F1A
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
Calculite® Compact Fluorescent Open Downlight 8011
Page 21 of 2
4 1/2” Aperture Triple Tube Vertical Lamp
Quick Calculator
ROOM SURFACE REFLECTANCES:
40
80% Ceiling; 50% Wall; 20% Floor
1200 Lumens Per Lamp
35
30
INITIAL FOOTCANDLES
25
RCR = 1
(Rm. width = 10 x Mtg. Ht. above work plane)
RCR = 5
(Rm. width = 2 x Mtg. Ht. above work plane)
RCR = 10
(Rm. width =
Mtg. Ht. above work plane)
20
15
10
5
10
20
30
40
50
60
70
80
90
100
110
AREA PER FIXTURE IN SQUARE FEET
3
4
5
6
7
8
9
10
CENTER TO CENTER DISTANCE OF FIXTURE IN FEET
This quick calculator chart determines the number and spacing of 1 lt.-18W PL-T units
with clear reflector, for any level of illumination.
Spacing Ratio = 1.2
CERTIFIED TEST REPORT NO. 0662FR
COMPUTED BY LSI PROGRAM **TEST-LITE**
CALCULITE RECESSED COMPACT FLUORESCENT OPEN DOWNLIGHT,
4 1/2” DIA. APERTURE CLEAR REFLECTOR
1-18W PLT LAMP. LUMEN RATING = 1200 LMS.
CANDLEPOWER SUMMARY
85ϒ
75ϒ
65ϒ
200
55ϒ
45ϒ
400
0ϒ
5ϒ
15ϒ
25ϒ
35ϒ
** Efficiency = 42.38% **
ANGLE
MEAN CP LUMENS
0
350
5
368
35
10
394
15
394
110
20
374
25
343
158
30
305
35
254
155
40
171
45
36
48
50
5
55
1
2
60
0
65
0
0
70
0
75
0
0
80
0
85
0
0
90
0
ZONAL LUMENS AND PERCENTAGES
ZONE LUMENS
Coefficients of Utilization
CC
WALL
RCR
0-30
0-40
0-60
0-90
40-90
60-90
90-180
0-180
303
458
507
507
49
0
0
507
% LAMP %LUMINAIRE
25.30
38.18
42.30
42.30
4.13
.00
.00
42.30
59.81
90.25
100.00
100.00
9.75
.00
.00
100.00
ZONAL CAVITY METHOD
EFFECTIVE FLOOR CAVITY REFLECTANCE = .20
80 70 50 3010
50 30 10 50 30 10 50 30 10 50 30 10 50 30 10 0
1
2
3
4
5
6
7
8
9
10
.47.46.46.47.46.45.45.44.43.43.43.42.42.41.41.40
.44.43.42 .44.42.41.42.41.40.41.40.39.40.39.39.38
.42.40.38.41.39.38.40.39.37.39.38.37.38.37.36.36
.39.37.36.39.37.35.38.36.35.37.36.35.36.35.34.33
.37.34.33.36.34.33.36.34.32.35.33.32.34.33.32.31
.35.32.31.34.32.30.34.32.30.33.31.30.33.31.30.29
.32.30.28.32.30.28.32.29.28.31.29.28.31.29.28.27
.30.28.26.30.28.26.30.27.26.29.27.26.29.27.26.25
.28.26.24.28.26.24.28.25.24.27.25.24.27.25.24.23
.26.24.22.26.24.22.26.24.22.25.23.22.25.23.22.21
Job Information
Type:
Lightolier a Genlyte company
www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
© 2011 Genlyte Group LLC • C0711
Project:
Transbay Marketing Center
Project #
13168.00
Date:
10 December 2013
Type:
F1A
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
Specification Decorative
*>}iʣʜvÊÓÊ
{¸Ê«iÀÌÕÀiÊ/Àˆ«iÊ/ÕLiÊÀ>“i‡˜ÊˆÌ
5
11 1/2"
(292 mm)
D4132VU
2
4
1
6
8 1/16"
(210 mm)
3 3/8"
(86 mm)
10 1/2"
(267 mm)
18W
8 1/8"
(207 mm)
Top View
3"
(76 mm)
4 1/2" (115 mm) Dia.
1" (25 mm) min.
2 1/8" (54 mm) max.
Flush
5" (127 mm)
3
Overlap
5 3/4" (147 mm)
1 1/8" (29 mm) max.
Ceiling Thickness
Ceiling Cutout: 5 1/16" (129 mm) Dia.
Frame-In Kit
D4132VU
iVÌÀœ˜ˆVÊ£Óä6‡ÓÇÇ6
ÓÈʜÀÊÎÓ7Ê/Àˆ«iÊ/ÕLi
{‡*ˆ˜Ê­“>}>“®
Compatible Reflector Trims
Vetro Accessory
Downlights
I"˜ÞÊvœÀÊÕÃiÊ܈̅Ê6iÌÀœÊVViÃÜÀÞ
8011CL
"«i˜]Ê6iÀ̈V>Ê>“«ˆ˜}
{ä£]Ê{äÓ]Ê{äÎ]Ê{ä{]Ê{£Î]Ê{£{
Features
Options & Accessories
1. Socket Cup:Ê-˜>«Ãʜ˜ÌœÊÀiviV̜ÀʘiVŽÊ̜Ê>ÃÃÕÀiÊVœ˜ÃˆÃÌi˜ÌÞÊVœÀÀiVÌʜ«ÌˆV>Ê
>ˆ}˜“i˜ÌÊ܈̅œÕÌÊ̜œÃ°
2. Mounting Frame:Ê>Û>˜ˆâi`ÊÃÌ>“«i`ÊÃÌiiÊvœÀÊ`ÀÞʜÀÊ«>ÃÌiÀÊViˆˆ˜}ð
3. Retaining Springs:Ê*ÀiVˆÃˆœ˜‡Ìœœi`ÊÃÌiiÊvÀˆV̈œ˜ÊëÀˆ˜}ÃÊÃiVÕÀiÊÀiviV̜ÀÊ̜Ê
“œÕ˜Ìˆ˜}ÊvÀ>“iÊvœÀʵՈVŽ]Ê̜œ‡iÃÃʈ˜ÃÌ>>̈œ˜°
4. Mounting Brackets:Ê>Û>˜ˆâi`ÊÃÌii°Ê`ÕÃÌÊvÀœ“ʈ˜Ãˆ`iʜvÊvˆÝÌÕÀi°Ê
1ÃiÊÎÉ{¸ÊœÀʣʣÉӸʏ>̅ˆ˜}ÊV…>˜˜i]Ê£ÉÓ¸Ê/]ʜÀʜ«Ìˆœ˜>Ê“œÕ˜Ìˆ˜}ÊL>Àð
5. Ballast/J-Box:ʏiVÌÀœ˜ˆVÊ£Óä6ʇÊÓÇÇ6°Ê1ʏˆÃÌi`ÊvœÀÊ̅ÀœÕ}…ÊLÀ>˜V…ÊVˆÀVՈÌÊ
܈Àˆ˜}Ê܈̅ʓ>ÝʜvÊ­n®Ê œ°Ê£ÓÊ7]ʙäc
ÊÃÕ««ÞÊVœ˜`ÕV̜ÀðÊ"ÕÌLœ>À`Ê
“œÕ˜Ìi`Ê̜ÊÀi`ÕViʅi>ÌÊÌÀ>˜ÃviÀÊ>˜`ʓ>ˆ˜Ì>ˆ˜Ê>“«ÊivvˆV>VÞÊ>˜`ʏˆvi°Ê-iÀۈViÊ
vÀœ“ÊLiœÜÊ܈̅œÕÌÊ̜œÃ°
Note:ʜÀÊL>>ÃÌÊiiVÌÀˆV>Ê`>Ì>Ê>˜`ʏ>ÌiÃÌʏ>“«ÉL>>ÃÌÊVœ“«>̈LˆˆÌÞÊÀiviÀÊ̜Ê
“Ballast” specification sheet for complete electrical data.
Chicago Plenum Option:
D4132VULC
Note:Ê"˜ÞÊvœÀÊÕÃiÊ܈̅ÊiVœÀ>̈ÛiÊ`œÜ˜ˆ}…ÌÊ>VViÃÜÀÞÊ{ä£]Ê{äÓ]Ê{äÎ]Ê
{£Î]Ê{ä£{]Ê{£{
Mounting Bars:
T-Bar Anchor Clips:
1950 ‡Ê£n¸Ê-iÌʜvÊ­Ó®
1951 ‡ÊÓǸÊ-iÌʜvÊ­Ó®
1956 ‡Ê-iÌʜvÊ­{®]ÊvœÀÊÕÃiÊ܈̅Ê>LœÛi
Labels
1ʏˆÃÌi`ÊvœÀÊ`>“«ÊœV>̈œ˜Ã°
Job Information
Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
ÈΣʈÀ«œÀÌÊ,œ>`]Ê>Ê,ˆÛiÀ]ÊÊäÓÇÓäÊUÊ­xän®ÊÈǙ‡n£Î£ÊUÊ>ÝÊ­xän®ÊÈÇ{‡{Ç£ä
We reserve the right to change details of design, materials and finish.
ÜÜÜ°ˆ}…ÌœˆiÀ°Vœ“Ê^ÊÓää™Ê*…ˆˆ«ÃÊÀœÕ«ÊUÊ
äÎä™
Lightolier is a Philips group brand
Project:
Transbay Marketing Center
Project #
13168.00
Date:
10 December 2013
Type:
F1A
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
HORNET® HIGH POWER
TRACK HEAD
HORNET-HP
LED
LED
APPLICATION
Accent and display lighting for retail, commercial &
hospitality environments
CONSTRUCTION:
Complete die-cast construction
No exposed wiring
Powder coat paint
ELECTRICAL:
Electronic constant current LED driver
120v - 277v input
Dimming options available for Triac and ELV systems. See
following pages for more information.
This product complies with IEEE C62.41 for surge endurance up to 2.5KV. Amerlux® recommends using additional surge protection with this unit (supplied by others),
surge damage is not covered by warranty.
MOUNTING:
Track, canopy and busway
- Not for use on vertically mounted track
OPTICS:
0-180º tilt, 360º rotation
Available in a variety of beam spreads
LED:
Color Temp Options: 2700K, 3000K, 3500K, 4000K
CRI: 85 typ. (2700K, 3000K, 3500K, 4000K)
90 typ. (3000K)
Binning: 3 macAdam
Lumen Maintenance: >70% of intial lumens @ 50,000 hrs
Lumen output (21w):
Spot,15º - 1115 lm typ (3000K)
Flood, 28º - 1058 lm typ (3000K)
Wide Flood, 45º - 1051 lm typ (3000K)
ACCESSORIES:
Snoot: Die-cast aluminum, 1” length, painted finish
Cross Blade: Stamped steel painted optical matte black
cross blade sits in snoot which must be ordered when
using cross blade
LABELING:
PROJECT:
TYPE:
For indoor use only
4 1/4”
Electrostatic sensitive device,
observe precautions for
handling
3 3/8”
4 11/16”
Accessory Options:
90º
4 5/8”
90º
Ø2 13/16”
Accessory
Holder
ELECTRICAL
18w
21w
System
System
Driver
Watts Amps Watts Amps
Electronic 120v
18
0.15
21
0.18
277v
18
0.06
21
0.08
Snoot Accessory
Holder
ORDERING INFORMATION:
Model
Wattage
HORNET-HP 18
21
Lamp
Type
Driver
Finish
LED
E - electronic WT - white
texture
BT - black
texture
ST - silver
texture
__ - _______
(other RAL)
Example: HORNET-HP-21-LED-E-WT-TN1-120-FL-3000
Mounting
Voltage
TN1 - Global 1cir, 120v
120
TEK - Global 2cir/2neut, 120v 277
TN3 - Global 3cir, 120v
TN2 - Global 2cir/2neut, 277v
B - busway
C - canopy
CCL - C-clamp
__ - __________
(other)
(see website for details)
Beam Spread
Color
Temp
NSP - narrow spot, 12º
SP - spot, 15º
NF - narrow flood, 20º
MFL - medium flood,
24º
FL - flood, 28º
WF - wide flood, 45º
VWF - very wide
flood, 60º
LS - linear spread,
60º x 10º
2700
3000
3500
4000
Options/Accessories*
SNAH - snoot accessory holder, 1”
length, matte black interior, specify
exterior color (WT, BT, ST) accepts
cross blade plus 2 additional forms
of media
3000-90* AH - accessory holder, specify finish
(90CRI) (WT, BT, ST), accepts 2 forms of
media
CB - cross blade, matte black finish,
requires snoot
HEX - hexcell louver (1/8” x 1/8”)
DIM-ELV - ELV dimming (120v only)
* NOTE: 3000-90CRI & accessories are not Energy Star rated.
DIM-TRIAC - Triac dimming
(120v only)
Cat #:
Amerlux® reserves the right to change details that do not affect overall function and performance.
Amerlux®, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com
Project:
Transbay Marketing Center
Project #
13168.00
Date:
10 December 2013
Type:
F3
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
HORNET® HIGH POWER
TRACK HEAD
HORNET-HP
LED
LED
TYPE:
FIXTURE DATA:
For 18w data, multiply by .86
Complete photometric data (ies format) available upon request.
21W LED
SPOT (SP)
DISTRIBUTION
LTL #33661
180
FLOOD (FL)
DISTRIBUTION
LTL # 33664
120
150
ACROSS
45
ALONG
180
WIDE FLOOD (WF)
DISTRIBUTION
LTL # 33665
180
120
150
ACROSS
45
ALONG
90
90
90
2500
400
1100
60
60
60
5000
2200
800
7500
3300
1200
0
30
0
Candelas at Nadir
Deg
Candela
0
8755
5
7093
15
1113
25
220
35
91
45
36
APPLICATION DATA:
120
150
ACROSS
45
ALONG
0
30
30
Candelas at Nadir
Deg
Candela
0
1407
5
1364
15
1064
25
637
35
288
45
109
Candelas at Nadir
Deg
Candela
0
3808
5
3430
15
1532
25
386
35
115
45
51
D
Notes and Definitions:
Beam spread is to 50% center beam candlepower (CBCP).
D=Distance to floor or wall.
FC=Footcandles on floor or wall at center beam aiming location.
L=Effective Visual Beam length in feet (50% of maximum footcandle level).
W=Effective Visual Beam width in feet (50% of maximum footcandle level).
CB=Distance across or down to center beam location.
CB
30°
30°
D
FC
W
FC
CB
L
30o Aiming Angle
Horizontal
Footcandles
30o Aiming Angle
Vertical
Footcandles
60o Aiming Angle
Vertical
Footcandles
60°
60º
SPOT
30º30°
L
D
5.0’
7.5’
10.0’
12.5’
FC
230
127
77
51
L
1.8
2.6
3.2
3.9
W
1.8
2.6
3.2
3.9
D
5.0’
7.5’
10.0’
12.5’
FC
172
88
52
34
L
2.3
3.2
4.9
5.1
W
2.1
2.9
4.3
4.6
CB
3.0
4.0
5.0
7.0
D
3.0’
4.0’
5.0’
6.0’
FC
141
83
54
35
L
2.9
3.7
4.7
5.8
W
1.5
2.2
2.8
3.4
CB
4.0
6.0
7.0
9.0
D
3.0’
4.0’
5.0’
6.0’
FC
529
348
223
155
L
1.3
1.7
2.1
2.4
W
1.1
1.3
1.6
2.0
CB
2.0
2.0
3.0
3.0
FLOOD
30°
30º
W
FC
D
5.0’
7.5’
10.0’
12.5’
FC
122
61
36
23
L
2.6
3.5
4.6
5.7
W
2.6
3.5
4.6
5.7
D
5.0’
7.5’
10.0’
12.5’
FC
84
42
25
16
L
3.2
4.4
5.7
7.1
W
2.9
3.9
5.1
6.4
CB
3.0
4.0
5.0
6.0
D
3.0’
4.0’
5.0’
6.0’
FC
65
39
25
18
L
3.8
4.8
6.0
7.3
W
2.6
3.2
4.0
4.7
CB
4.0
5.0
7.0
8.0
D
3.0’
4.0’
5.0’
6.0’
FC
243
164
98
73
L
2.1
2.2
3.0
3.4
W
1.5
1.9
2.7
3.0
CB
2.0
2.0
3.0
3.0
WIDE
FLOOD
0o Aiming Angle
Horizontal
Footcandles
D
5.0’
7.5’
10.0’
12.5’
FC
52
24
14
9
L
3.8
5.7
7.6
9.5
W
3.8
5.7
7.6
9.5
D
5.0’
7.5’
10.0’
12.5’
FC
39
18
10
7
L
4.4
6.4
8.6
10.9
W
4.2
6.1
8.1
10.4
CB
2.0
3.0
4.0
5.0
D
3.0’
4.0’
5.0’
6.0’
FC
38
23
15
11
L
4.0
5.2
6.5
7.9
W
3.4
4.4
5.4
6.5
CB
3.0
4.0
5.0
5.0
D
3.0’
4.0’
5.0’
6.0’
FC
116
64
43
29
L
2.6
3.5
4.3
5.2
W
2.4
3.3
4.0
4.9
CB
1.0
2.0
2.0
2.0
Amerlux®, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com
Project:
Transbay Marketing Center
Project #
13168.00
L
W
LIT-1206 rev 10/13
Date:
10 December 2013
Type:
F3
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
HORNET® HIGH POWER
TRACK HEAD
HORNET-HP
LED
LED
TYPE:
DIMMING COMPATIBILITY:
Amerlux® “Hornet®” track head is compatible with TRIAC and ELV dimming protocols prevalent in the United States. Please
see below for general compatibilities and wiring diagrams. Amerlux® recommends testing your unique dimming configuration as the exact full configuration (Dimmer, Fixture Quantity, Voltage, etc) may affect dimming performance.
TRIAC (Forward Phase) DIMMING (-DIM-TRIAC Option) ---not compatible with 12w module--Utilizes “Standard” incandescent dimmers that are in wide use in installations across the US. Best for retrofit applications
where Triac dimmers are installed.
Wiring Diagram
Notes:
• 120v ONLY
Driver
Triac
• Dims down to less than 5% light output (most cases)
Black Black
Dimmer
LED
• Consult Dimming manufacturer for installastion
RED
White
(by others)
instructions - DO NOT SHARE NEUTRALS!
Green
• Must meet dimmer Minimum Load Requirements
per dimming manufacturer
120v
Compatible Dimmers
Wall Box (Incandescent Style, Wattage as required)
Central System
Lutron “Diva”
Lutron “Vareo”
ETC “SR” Rack w/D20
ETC “DRD” Rack w/D20
Lutron “Nova-T”
Lutron “Skylark”
Module
Module
Lutron “Maestro”
Lutron “GP” Panel
Lutron Grafix Eye QS
ELV - Electronic Low Voltage (Reverse Phase) DIMMING (-DIM-ELV Option)
Utilizes specialized “ELV” dimmers. Best for New Construction appilications
Notes:
• 120v ONLY
• Dims down to less than 5% light output (most cases)
• Consult Dimming manufacturer for installastion
instructions - DO NOT SHARE NEUTRALS!
• Must meet dimmer Minimum Load Requirements
Wiring Diagram
Driver
Black Black
RED
White
Green
ELV
Dimmer
(by others)
LED
120v
Compatible Dimmers
Wall Box (ELV Style)
Lutron “Diva”
Lutron “Nova-T”
Lutron “Maestro”
Leviton “Surslide”
Lutron “Vareo”
Lutron “Skylark”
Leviton “Vizio”
Central System
ETC “SR” Rack w/ELV10
Module
Lutron “GP” Panel with
PHPM-PA Interface
ETC “DRD” Rack w/ELV10
Module
Lutron Grafix Eye QS with
PHPM-PA Interface
Amerlux®, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com
Project:
Transbay Marketing Center
Project #
13168.00
LIT-1206 rev 10/13
Date:
10 December 2013
Type:
F3
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
Project:
Transbay Marketing Center
Project #
13168.00
Date:
10 December 2013
Type:
F3
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
° ROTATION
360
9/16
n5
1
3/4
2 1/4
STEM LENGTH
5 1/4
2 5/16
2 7/8
1/4
4
REV
WorkInProgress
DESIGN STATE
90°
TILT
1 13/16
FINISH
MATERIAL
DATE
APPROVED
SHEET
SCALE
1
DRAWN BY
DATE
G L O B A L
OF
1
3/8
GGP
8/20/2012
DESCRIPTION
A
DATE
DWG.#
CHKD. BY
SIZE
S O L U TIO N S
ED-0626
DATE
APPRD. BY
HORNET STEM CANOPY
L IG H TIN G
REV.
23 Daniel Road East
Fairfield, N.J. 07004
Phone: 973-882-5010
Fax: 973-882-2604
Web: www.amerlux.com
AMERLUX RESERVES THE RIGHT TO CHANGE DETAILS THAT DO NOT
AFFECT OVERALL FUNCTION AND PERFORMANCE.
ENGINEERING APPROVAL TO START DESIGN: _______________ DATE: __________
CUSTOMER APPROVAL: _______________ DATE: __________
FIXTURE TYPE:
JOB NAME:
HORNET-15-LED-E-FINISH-MTG-VOLTAGE-BEAM-COLOR TEMP-OPTIONS
90°
TILT
4" OCTAGONAL
J-BOX (BY OTHERS)
REVISION HISTORY
DESCRIPTION
DIMENSIONS ARE IN INCHES
TOLERANCES ARE:
FRACTIONAL: ± 1/64
DECIMAL: .XX ± .01, .XXX ± .005
ANGLE: ± .5~
UNLESS OTHERWISE SPECIFIED
1 5/8
PROPRIETARY AND CONFIDENTIAL
THE INFORMATION CONTAINED IN THIS
DRAWING IS THE SOLE PROPERTY OF
AMERLUX LIGHTING SOLUTIONS.
ANY REPRODUCTION IN PART OR
AS A WHOLE WITHOUT THE WRITTEN
PERMISSION OF AMERLUX LIGHTING
SOLUTIONS IS STRICTLY PROHIBITED.
2 3/4
4" OCTAGONAL J-BOX
(BY OTHERS)
4 1/4
1 11/16
3 7/8
GRÜV MINI EXTRUDED
GRUVM-EX-GB
LED
2.5” RECESSED LINEAR LED, GYP BOARD
APPLICATIONS:
Retail and commercial ambient lighting in wall to ceiling
applications
ELECTRICAL:
Electronic, multi-volt (120v-277v) constant current driver
Dimmable, 0-10v
This product complies with IEEE C62.41 for surge endurance up to 3KV. Amerlux recommends using additional
surge protection with this unit (supplied by others), surge
damage is not covered by warranty.
Emergency circuit via remote inverter or auxillary emergency power supply (by others)
CONSTRUCTION:
Extruded aluminum housing
Ceiling trim is high reflectance white finish
MOUNTING:
For use in sheet rock ceilings or walls only
Fixtures must be installed before finished ceiling or walls
are installed
LABELING:
OPTICS:
5w/ft, 3500K LED’s standard, other color temps available
Extruded white acrylic lens, snap-in, 8’ maximum section
Amerlux exclusive white acrylic lens provides excellent
transmission while effectively concealing lamp image
TYPE:
Mounting rods &
hardware by others
3”
PROJECT:
For indoor use only
1’ to 2’
from end of fixture
(2 per fixture)
Suspension brackets
supplied by Amerlux
3”
5
3 5 /8 ”
Fixture height
Support method
by others
/8”
Driver
Electronic
Wattage
per foot
5
Lamping
120v
277v
4’
Input
watts Amps
22
.18
20
.07
Input
watts
44
40
Electrostatic sensitive device,
observe precautions for
handling
Feed location
(optional)
1 5/16”
NOTE: Minimum ceiling
opening must be held
by installer for the full
length of the run
2 1/2”
5 1/4”
ELECTRICAL
5 7/16”
Fixture & mounting
bracket height
Feed location
(default)
1
/16”
Overall length
of run
8’
Amps
.37
.14
Ceiling contractor to spackle,
feather & sand at ceiling interface.
(see website for details)
ORDERING INFORMATION:
Model
Wattage Lamp Type
Per Foot
GRUVM-EX-GB 5
LED
Driver
E - electronic
Voltage
120/277
Length
Mounting
For Straight Runs
4 - 4’
IND - individual
8 - 8’
BOR - beginning of run
_______
MOR - middle of run
(other consult
EOR - end of run
factory)
For Ceiling/Wall Corner
BORWC - beginning of run, wall corner
EORWC - end of run, wall corner
BORCC - beginning of run, ceiling
corner
EORCC - end of run, ceiling corner
Color Temp
Options
2700
3000
3500
4000
HILUME - Lutron
HiLume driver
CP - Chicago
plenum
Example: GRUVM-EX-GB-5-LED-E-120/277-8-IND-3500
Cat #:
Amerlux reserves the right to change details that do not affect overall function and performance.
Amerlux, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com
Project:
Transbay Marketing Center
Project #
13168.00
Date: 10 December 2013
Type:
F4,F4A,F4B,F4C
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
GRÜV MINI EXTRUDED
GRUVM-EX-GB
LED
2.5” RECESSED LINEAR LED, GYP BOARD
TYPE:
FIXTURE DATA:
Complete photometric data (.ies format) available upon request.
GRÜV MINI 5W LED
SOURCE: 120 WHITE LEDS LUMENS: 1458
RECESSED
ZONAL LUMEN SUMMARY
Zone Lumens %Lamp
0-30
487
NA
0-40
763
NA
0-60
1220
NA
0-90
1458
NA
90-180
0
NA
0-180
1458
NA
LTL# 31019
%Fixt
33.4
52.3
83.7
100.0
0.0
100.0
90
75
175
60
350
45
Total Luminaire Efficacy = 69.9 lumens/watt
COEFFICIENTS OF UTILIZATION
Effective Floor Cavity Reflectance 20%
RC
80
RW
70
50
30
10
RCR
0
1736
1736
1736
1736
1
1598
1534
1476
1424
2
1465
1353
1261
1183
3
1345
1201
1090
1001
4
1239
1074
954
862
5
1145
968
844
752
6
1062
878
754
665
7
989
801
679
593
8
923
734
616
534
9
865
677
562
484
10
813
627
516
442
525
700
0
15
30
LIT-1144 rev 12/12
Amerlux, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com
Project:
Transbay Marketing Center
Project #
13168.00
Date: 10 December 2013
Type:
F4,F4A,F4B,F4C
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
HORNET HP DOWNLIGHT
HDL-HPX-RLW-TL
LED
3.5” ROUND LENSED WALL WASH TRIMLESS LED
ELECTRICAL:
Electronic constant current LED driver
120v or 277v input
Dimming options available for Triac, ELV, 0-10v and Lutron systems. See following pages for more information.
Also optional is Emergency Battery Pack with a remote
test switch.
This product complies with IEEE C62.41 for surge endurance up to 2.5KV. Amerlux recommends using additional
surge protection with this unit (supplied by others), surge
damage is not covered by warranty.
APPLICATIONS:
Retail and commercial wall wash lighting
CONSTRUCTION:
20 ga. galvanized steel frame
18 ga. galvanized steel splice housing and hanger
brackets
Cast aluminum plaster frame w/perforated face
Die-cast trim, extruded aluminum heat sink
Thermally protected
Optic can be rotated to any position
MOUNTING:
For use in T-grid or sheet rock ceilings, max ceiling thickness 3/4”, consult factory for thicker ceilings
LABELING:
For indoor use only
IC/AT rated (optional)
Damp location
5
4 3/16”
TYPE:
3 9/16”
Ceiling Cut Out Dimension: 4 1/2” dia.
ELECTRICAL
Electronic driver
12w
17w
20w
23w
System
System
System
System
Watts Amps Watts Amps Watts Amps Watts Amps
120v
12
0.1
17
0.14
20
0.17
23
0.19
277v
12
0.04
17
0.06
20
0.07
23
0.08
3
4
6
5
1. Reflector Trim
2. Fixture Housing Aperture Plate
2 3. Ceiling 5/8” (1” max)
4. Cast Aluminum Plaster Frame
1 5. Plaster Skim Coat (by others)
6. 6-32 Type F Thread Cutting Screw
Wattage
Lamp
Type
Driver
12
17
20
LED
E - electronic 120
277
HDL-HPX-R-TL 23
5
(see website for details)
ORDERING INFORMATION:
HDL-HP-R-TL
Electrostatic sensitive device,
observe precautions for
handling
3 1 /2 ”
/8”
11 1/2”
14 1/2” min - 26” max
Housing:
Model
PROJECT:
Approved to UL standards as tested by CSA.
R
US
C
4 13/16”
4 11/16”
7 3/4”
11 11/16”
OPTICS:
High reflectance, high diffusivity mixing chamber
Engineered nano technology lens provides transmission
while concealing LED image
LED:
Color Temp Options: 2700K, 3000K, 3500K, 4000K
CRI: 85 typ. (2700K, 3000K, 3500K, 4000K)
90 typ. (3000K)
Binning: 3 MacAdam (SDMC)
Life: 50,000 hrs
Lumen Maintenance: >70% of intial lumens @ 50,000 hrs
Lumen Output at 3000K:
17w: 632 lm 20w: 743 lm 23w: 854 lm
Trim:
Model
Voltage Options
DIM-ELV- ELV dimming (120v only)
DIM-TRIAC - Triac dimming (120v only)
HILUME - Lutron Hi-lume® EcoSystem 3 wire, 1% dim
0-10V - 0-10v dimming
MF-EM - multi-function emergency driver
MF-NL - multi-function night light driver
CP - Chicago Plenum
EM - emergency battery pack w/remote test switch
IC/AT* - insulated ceiling/air tight (17w only)
Aperture Finish
Reflector with White
HDL-HPX-RLW-TL Painted Flange
MBW - matte black
MWW - matte white
SLVW - matte silver
Color
Temp
2700
3000
3500
4000
3000-90
(90CRI)
Complete Example: HDL-HP-R-TL-20-LED-E-120/HDL-HPX-RLW-TL-MWW-3000
Housing Example: HDL-HP-R-TL-20-LED-E-120
Reflector Example: HDL-HPX-RLW-TL-MWW-3000
Cat #:
Amerlux reserves the right to change details that do not affect overall function and performance.
Amerlux, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com
Project:
Transbay Marketing Center
Project #
13168.00
Date:
10 December 2013
Type:
F5
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
HORNET® HP DOWNLIGHT
HDL-HPX-RLD-TL
LED
3.5” ROUND LENSED DOWNLIGHT TRIMLESS LED
TYPE:
FIXTURE DATA: For 17w data, multiply by 0.74; For 20w data, multiply by 0.87
Complete photometric data (.ies format) available upon request.
Hornet HP Round Lens Wall Washer 23w LED
Source: LED with frosted plastic optic Lumens: 854
Recessed
LTL# 369000
150
180
120
ACROSS
45
ALONG
ZONAL LUMEN SUMMARY
Zone Lumens
%Fixt
0-30
410
48.00
0-40
587
68.73
0-60
782
91.54
0-90
854
100.0
90-180
0
0.0
0-180
854
100.0
120
90
60
150
90
200
60
400
30
Luminaire Efficacy: 37.6 lumens/watt
30
600
0
APPLICATION DATA:
Footcandles are average and rounded off.
Data for multiple units are based
on a minimum of five units.
Footcandles on Wall
1.5’
23
45
46
35
24
17
13
10
24
46
47
36
25
18
13
10
0.5’
1.5’
2.5’
3.5’
4.5’
5.5’
6.5’
7.5’
17
33
34
26
18
13
10
8
19
36
36
27
19
14
11
9
18
34
36
28
20
15
11
9
0.5’
1.5’
2.5’
3.5’
4.5’
5.5’
6.5’
7.5’
10
22
26
24
19
15
11
9
11
24
27
25
21
16
12
10
11
24
28
26
21
17
13
11
Distance from ceiling
23
43
43
32
22
16
12
9
Distance from ceiling
1.5’
0.5’
1.5’
2.5’
3.5’
4.5’
5.5’
6.5’
7.5’
Distance from ceiling
1.5 Feet From Wall
1.5 Feet From Wall
24
45
46
35
25
17
13
10
22
43
44
33
22
16
12
9
19
36
37
28
20
15
12
9
17
34
36
28
20
15
11
9
11
24
28
26
22
17
13
11
11
24
28
26
21
17
13
10
2’
2 Feet From Wall
2’
2’
19
36
36
27
20
14
11
9
17
33
34
26
18
13
10
8
11
24
27
26
21
16
12
10
10
22
26
24
19
15
11
9
2’
Amerlux, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com
Project:
Transbay Marketing Center
Project #
13168.00
rev 11/13
Date:
10 December 2013
Type:
F5
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
HORNET® HP DOWNLIGHT
HDL-HPX-RLD-TL
LED
3.5” ROUND LENSED DOWNLIGHT TRIMLESS LED
TYPE:
DIMMING COMPATIBILITY:
Amerlux “Hornet” fixtures are compatible with all major dimming protocols prevalent in the United States. Please see below
for general compatibilities and wiring diagrams. Amerlux recommends testing your unique dimming configuration as the
exact full configuration (Dimmer, Fixture Quantity, Voltage, etc) may affect dimming performance.
TRIAC (Forward Phase) DIMMING (-DIM-TRIAC Option) ---not compatible with 12w module--Utilizes “Standard” incandescent dimmers that are in wide use in installations across the US. Best for retrofit applications
where Triac dimmers are installed.
Wiring Diagram
Notes:
• 120v ONLY
Driver
Triac
• Dims down to less than 5% light output (most cases)
Black Black
Dimmer
LED
• Consult Dimming manufacturer for installastion
RED
White
(by others)
instructions - DO NOT SHARE NEUTRALS!
Green
• Must meet dimmer Minimum Load Requirements
per dimming manufacturer
120v
Compatible Dimmers
Wall Box (Incandescent Style, Wattage as required)
Central System
Lutron “Diva”
Lutron “Vareo”
ETC “SR” Rack w/D20
ETC “DRD” Rack w/D20
Lutron “Nova-T”
Lutron “Skylark”
Module
Module
Lutron “Maestro”
Lutron “GP” Panel
Lutron Grafix Eye QS
ELV - Electronic Low Voltage (Reverse Phase) DIMMING (-DIM-ELV Option)
Utilizes specialized “ELV” dimmers. Best for New Construction appilications
Notes:
• 120v ONLY
• Dims down to less than 5% light output (most cases)
• Consult Dimming manufacturer for installastion
instructions - DO NOT SHARE NEUTRALS!
• Must meet dimmer Minimum Load Requirements
Wiring Diagram
Driver
Black Black
RED
White
Green
ELV
Dimmer
(by others)
LED
120v
Compatible Dimmers
Wall Box (ELV Style)
Lutron “Diva”
Lutron “Nova-T”
Lutron “Maestro”
Leviton “Surslide”
Lutron “Vareo”
Lutron “Skylark”
Leviton “Vizio”
Central System
ETC “SR” Rack w/ELV10
Module
Lutron “GP” Panel with
PHPM-PA Interface
ETC “DRD” Rack w/ELV10
Module
Lutron Grafix Eye QS with
PHPM-PA Interface
0-10V - DIMMING (-0-10V Option)
Integrates into a variety of building management and day-lighting controls
Wiring Diagram
Notes:
• 120v - 277v
• Dims down to less than 10% light output
• Requires interface to turn off power to driver
• Consult Dimming manufacturer for installastion
instructions - DO NOT SHARE NEUTRALS!
Compatible Dimmers
Wall Box
Lutron “Diva” - DVTV with
PP-120H Interface
Leviton Renoir II 0-10v
Driver
Violet Black
RED
Grey
0-10v
Dimmer
LED
Black
White
Green
Bldg
Power or
Interface
Central System
Lutron Grafix Eye with
GRX-TVI Interface
Amerlux, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com
Project:
Transbay Marketing Center
Project #
13168.00
rev 11/13
Date:
10 December 2013
Type:
F5
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
HORNET® HP DOWNLIGHT
HDL-HPX-RLD-TL
LED
3.5” ROUND LENSED DOWNLIGHT TRIMLESS LED
TYPE:
LUTRON HI-LUME / ECO-SYSTEM (-DIM-HILUME Option)
Integrates into a variety of building management and day-lighting controls
3-Wire Wiring Diagram
Notes:
• 120v or 277v
Driver
• Dims down to less than 5% light output
3-Wire FL
Black
Switched Hot
• May use 3-Wire or Ecosystem Control
Control
Orange
Dimmed Hot
• Consult Dimming manufacturer for installastion
(by others)
White
Neu
instructions - DO NOT SHARE NEUTRALS!
Green
Gnd
Purple/Grey E2
Purple
E1
Compatible Dimmers
Wall Box (3-Wire Fluorescent)
ECO-Sys Bus
DIVA
Cap Wires
Maestro
Nova T
ECO System Digital Control Wiring
Vareo
Cap Lead
Central System
Lutron ECO-System compatible controls
ETC “SR” Rack w/D20F Module
ETC “DRD” Rack w/D20F Module
ECO
System
Control
(by others)
Black
Orange
White
Green
Purple/Grey
Purple
Driver
Switched Hot
Dimmed Hot
Black
RED
LED
Black
RED
LED
VV+
VV+
Neu
Gnd
E2
E1
ECO-Sys Bus
MULTI-FUNCTION
Emergency Configuration
120v/277v
Normal
Power
120v/277v
Normal
Power
Primary
Driver
Emergency system (by
others) to ensure only one
feed is active at a time.
120v/277v
Emergency
Feed
(by others)
Night Light Configuration
LED
Primary
Driver
On/Off
control
LED
(by others)
Secondary
Driver
120v/277v
Constant
Power
Secondary
Driver
In Night Light configuration
Multi-Function driver provides
10 mA of drive current when
primary driver is switched off.
17w = 2% output
20w = 1.5% output
In Emergency configuration
Multi-Function driver provides
100 mA of drive current.
17w = 20% output
20w = 16% output
Patent-Pending
Amerlux, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com
Project:
Transbay Marketing Center
Project #
13168.00
rev 11/13
Date:
10 December 2013
Type:
F5
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
PROJECT
SPECIFIER
TYPE
ZONE
__
__
SKU
1. SERIES
LIGHT ENGINE
24V DC
DIMMING
CLASS 2
IP20 DRY LOCATION
NOTE
SUITABLE FOR INSTALLATION WITHIN THE CLOSET STORAGE SPACE (WITH CLOTHING)
2. COLOR
CODE
ETL (INTERTEK) APPROVED NFPA ATRICLE 410.16 (ALL SECTIONS)
UL LISTED 2108 FILE NUMBER E364348
LUMINAIRE MUST BE INSTALLED IN ACCORDANCE WITH NFPA 70, ARTICLE 410.16
1. SERIES
2. COLOR
94+ CRI WHITE
8000 SERIES HIGH OUTPUT
SINGLE BIN
8024 83+CRI 6.0W /ft ≤546 Lm/ft
8924 94+CRI 5.6W /ft ≤463 Lm/ft
8024/8924 SERIES
CCT
2150K 94CRI
2650K 97CRI
2950K 97CRI
COLOR
CODE
22
26
29
83+ CRI WHITE
SINGLE BIN
0.55
1.0
0.10
MIN INCREMENT = 1 INCH / MAX PER CIRCUIT = 15 FEET
27
30
35
40
60
2700K
3000K
3500K
4000K
6000K
COLORS
4000 SERIES MID OUTPUT
4924 94+CRI 2.8W /ft ≤236 Lm/ft
0.40
4024/4924 SERIES
UL E364348
R
G
B
A
PK
PR
RED
GREEN
BLUE
AMBER
PINK
PURPLE
4024 83+CRI 3.0W /ft ≤279 Lm/ft
3W/FT 24VDC
2.0
CRI = Color Rendering Index
CCT = CorRelated Color Temperature
0.10
MIN INCREMENT = 2 INCHES / MAX PER CIRCUIT = 30 FEET
3000 SERIES LOW OUTPUT
(INDIRECT APPLICATIONS ONLY)
3024 83+CRI 1.5W /ft ≤137 Lm/ft
3924 94+CRI 1.4W /ft ≤116 Lm/ft
0.40
3024/3924 SERIES
UL E364348
1.5W/FT 24VDC
4.0
0.10
MIN INCREMENT = 4 INCHES / MAX PER CIRCUIT = 32 FEET
COMPONENT OF A COMPLETE SYSTEM INCLUDING: AION LED A-TRACK LIGHT ENGINE, AION LED A-TRACK HOUSING WITH DIFFUSER LENS, & AION LED DRIVER (POWER SUPPLY). DIMMER NOT
INCLUDED. APPROVED DIMMERS, CONTROLS, POWER SUPPLIES, CABLE, & OTHER COMPONENTS ONLY. CONTACT AION LED FOR QUESTIONS REGARDING COMPATIBILTY. ELECTRICIAN INSTALLED.
STRICTLY ADHERE TO NEC & LOCAL BUILDING CODE. LIMITED 5-YEAR WARRANTY AGAINST MANUFACTURING DEFECTS ONLY, DOES NOT COVER LABOR; VOIDED BY: INADEQUATE VENTILLATION,
FIELD MODIFICATIONS, INSTALLATION BY UNQUALIFIED PERSONNEL, UNAPPROVED CONTROLS, DRIVERS, CABLING, OTHER DEVICES, NOT FOLLOWING INSTALLATION GUIDELINES & PROTOCOL,
GENERAL NEGLIGENCE. INSTALLER ASSUMES ALL LIABILITY WITH REGARD TO PROPERTY & SAFETY. THIS PRODUCT IS UL LISTED. SEE SEPARATE: “AION LED WARRANTY TERMS” & ADDITIONAL
INSTRUCTIONAL MATERIALS FOR MORE INFORMATION. AUTHORIZED INSTALLERS ONLY. SYSTEMS TESTED PRIOR TO SHIPPING.
© Copyright 2013 Aion LED, Inc. All Rights Reserved
Project:
Transbay Marketing Center
Project #
13168.00
(415) 255-AION (2466)
Date:
www.AionLED.com
10 December 2013
Type:
F6
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
A-TRACK
SEAMLESS FIXTURE UP TO 30 FEET PER CIRCUIT (24V)
CUSTOM CRAFTED TO GIVEN DIMENSIONS
BEST IN CLASS DIFFUSION OPTIONS
HIGH QUALITY, HIGH OUTPUT
CABLE ARMOR OPTION
COMPATIBLE WITH PS TYPE: 4000, 4024, 8024, 7000-RGB, & 7024-RGB
LINEAR FIXTURE -NOT INCLUDED, SOLD SEPARATELY
(multiple pages)
Warning: Installation should only be attempted by qualified and authorized personnel. Licensed electricians and trained technicians must wire all components in strict
compliance with local building codes. Installer assumes all liability for safety and hazard mitigation. Aion LED is not liable for damages incurred by negligence, faulty
wiring, poor design, overloading, or other. Authorized Aion LED Installers are trained in installation methods, materials, and code-related protocol.
AION LED, LLC
2325 3RD ST #330 SAN FRANCISCO, CA 94107
© Copyright 2012 Aion LED All Rights Reserved
TOLL FREE: (877) 345-AION [2466]
INTERNATIONAL PATENTS PENDING
Project:
Transbay Marketing Center
Project #
13168.00
Date:
FAX: (415) 285-1335
CustomerCare@AionLED.com
www.AionLED.com
10 December 2013
Type:
F6
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
Project:
Transbay Marketing Center
Project #
13168.00
Date:
10 December 2013
Type:
F6
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
Class 2 Dimming LED Driver
24 Volt
ELECTRICIAN INSTALLED
MODEL
D20-D-24
DIMENSIONS (L-W-H) INCHES
WATTAGE
RATING
CLASS 2 (UL STANDARD)
NEMA 3R CASE
INPUT VOLTAGE
OUTPUT VOLTAGE LOADED
VOLTAGE OPEN
MAX INPUT CURRENT
PRIMARY BREAKER
SECONDARY BREAKER
DIMMING
DIMMER TYPE*
LEADS PRIMARY AWG, TEMP
LEADS SECONDARY AWG, TEMP
THERMAL CLASS
BOOST TAP 10%
MAX FEET #3024/3924 SERIES
MAX FEET #4024/4924 SERIES
MAX FEET #8024/8924 SERIES
(5 x 2.1 x 2)
20
ETL (UL 8750)
Yes
Indoor
120V 60Hz
23.5 VDC
25.5 VDC
206mA
Thermal
2A
Triac/ Primary
Magnetic/ Low-voltage
#20 105 C
#16 105 C
(B) 130 C
No
12
6
3
D40-D-24
(5 x 2.1 x 2)
40
ETL (UL 8750)
Yes
Indoor
120V 60Hz
23.5 VDC
25.5 VDC
360mA
Thermal
4A
Triac/ Primary
Magnetic/ Low-voltage
#20 105 C
#16 105 C
(B) 130 C
No
24
12
6
D60-D-24
(8.5 x 3 x 2.9)
60
ETL (UL 1310)
Yes
Indoor/ Outdoor
120V 60Hz
23.5 VDC
25.5 VDC
0.6A
1A THERMAL
5A THERMAL
Triac/ Primary
Magnetic/ Low-voltage
#18 105 C
#12 105 C
(B) 130 C
Yes
36
18
9
D100-D-24
(9 x 4.2 x 3.25)
96
ETL (UL 1310)
Yes
Indoor/ Outdoor
120V 60Hz
23.5 VDC
25.5 VDC
1A
2A THERMAL
4A MAGNETIC
Triac/ Primary
Magnetic/ Low-voltage
#18 105 C
#12 105 C
(B) 130 C
Yes
60
30
15
D300-D3-24
(7 x 7 x 3.2)
288 (3 x 96)
ETL (UL 1310)
Yes
Indoor
120V 60Hz
23.5 VDC
25.5 VDC
3A
5A THERMAL
(3X) 4A MAGNETIC
Triac/ Primary
Magnetic/ Low-voltage
#18 105 C
#12 105 C
(B) 130 C
Yes
180
90
45
*CONTROLS COMPATIBILITY
1. 2 WIRE, FORWARD-PHASE, MAGNETIC TRANSFORMER. LOAD DRIVER BETWEEN 50 to 90% OF MAXIMUM RATED WATTAGE.
2. MAGNETIC LOW VOLTAGE DIMMERS SUCH AS: LUTRON HOMEWORKS, GRAFIK EYE, RADIO RA, & NOVA -SELECT MODELS ONLY.
3. LOW END DIMMING PERCENTAGE VARIES PER MODEL. CONTACT AION LED FOR MORE INFORMATION REGARDING APPROVED CONTROLS.
MAX LED RUN PER CIRCUIT
1. [4A (96W) per circuit] (NEC Article 725)
2. 10% headroom included
3. Use electrical junction boxes to transition between building wire and Aion LED power feeds per local code.
SUB BOXES
Use larger guage cord for sub feeds and longer runs. Junction building wire to fixture whips within electrical boxes per local code.
HEAT & EMI
MAGNETIC DC TRANSFORMERS EMIT HEAT AND ELECTROMAGNETIC ENERGY. ADEQUATE VENTILATION REQUIRED (NEC ARTICLE 450)
PLEASE LEAVE 15 INCHES OF SPACE BETWEEN EACH TRANSFORMER.
MAGNETIC LOW-VOLTAGE
120VAC
FIRM
D-24-SERIES
24VDC
TYPE
DESC
+
_
L
N
JOB
SKU
MEMO
[FOR NEUTRAL DIMMING SWITCHES: REFER TO MANUFACTURER’S INSTRUCTIONS
Warning: Installation should only be attempted by qualified and authorized personnel. Licensed electricians and trained technicians must wire all components in strict
compliance with local building codes and NEC. Installer assumes all liability for safety and hazard mitigation. Aion LED is not liable for damages incurred by
negligence, faulty wiring, poor design, overloading, inadequate ventilation, inadequate spacing, or other. Authorized Aion LED Installers are trained in installation
methods, materials, and code-related protocol.
AION LED, INC.
2325 3RD ST #330 SAN FRANCISCO, CA 94107
TOLL FREE: (877) 345-AION [2466]
© Copyright 2012 Aion LED All Rights Reserved
Project:
Transbay Marketing Center
Project #
13168.00
FAX: (415) 285-1335
CustomerCare@AionLED.com
www.AionLED.com
Date:
10 December 2013
Type:
F6
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
1.800.263.AXIS
[ T ] 514.948.6272
[ F ] 514.948.6271
PENDANT ASYMMETRIC MOUNT
www.axislighting.com
PROJECT INFORMATION
Project:
Notes:
Type:
DIMENSIONS
SECTION VIEWS
Asymmetric
Indirect
Asymmetric
Direct
4"
102mm
4"
102mm
SHOWN WITH LENS OPTION
3 13/32”
87mm
3 13/32”
87mm
ORDERING CODE
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
PRODUCT SPECIFICATIONS
1 PRODUCT ID
BMD pendant direct
BMI pendant indirect
2 OPTICS
3 LENGTH/FT
A asymmetric
AF asymmetric frosted(1)
2
3
4
5
6
8
12
S#
4 SPECIFY LENGTH
NL
NL4
EX
EX4
2’
3’
4’
5’
6’
8’
12’
System Run
5 LAMP
nominal (3’ & 4’ lamps)
nominal (4’ lamps only)
exact (3’ & 4’ lamps)
exact (4’ lamps only)
6 LAMP CONFIGURATION
T5 T5
T5HO T5HO
1 1 lamp
(1) For direct light distribution only
7 MR
M16# MR 16 halogen
M16LED# MR 16 LED
8 FINISH
AP aluminum paint
W white
C custom
Add 9” per lamp
13 BATTERY
B# battery pack 4’ sections
9 VOLTAGE
120
277
347
UNV
120V
277V
347V(2)
universal
(2) Please consult factory
14 OTHER
F fuse
10 BALLAST
D
E
ERS
T
1
2A/B
+E#
+NL#
+GTD#
+M
1 regular
2 alternating
emergency section
night light section
generator transfer device
MR
12 MOUNTING/SUSPENSION
SA# drywall+stem length >48” (18" std.)
Use ballast guide for ballast specification
(3) In T5HO, only available for 2x4’ lamp
configuration
15 IC CONTROLS
DS#
OS#
DS+OS#
DOS#
11 CIRCUITS
dimming
instant start
rapid start
step dimming(3)
daylight sensor
occupancy sensor
daylight+occupancy sensor
daylight&occupancy sensor
See integrated controls guide for further details
16 CUSTOM
C custom
Please specify
Ballast, Battery Pack and Integrated Control Details and Custom Description:
FILE NAME:BM.ASYM.SPEC
July 8, 2013
Product design and development is an ongoing process at Axis Lighting. We reserve the right to change specifications. Contact Axis for the latest product information.
Project:
Transbay Marketing Center
Project #
13168.00
Date:
© 2011 Axis Lighting Inc. Page: 1 / 5
10 December 2013
Type:
F7,F7A,F7B
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
1.800.263.AXIS
[ T ] 514.948.6272
[ F ] 514.948.6271
PENDANT ASYMMETRIC MOUNT
www.axislighting.com
CONSTRUCTION
JOINERS
Housing
Extruded Aluminum (0.075'' nominal)
up to 70% Recycled Content
End Cap Sheet Steel (18 ga)
Interior Brackets Die Formed Sheet Steel (18 gauge)
Reflectors
White Powder Coated Sheet Steel (22 ga)
Blank
Extruded Aluminum (0.075'' nominal)
Lenses
Extruded Acrylic (0.070'' nominal)
Frosted: 85% trans.
Suspension
Ø 1/2" Stem
In order to allow very long runs of BEAM 3 luminaires, Axis has
developed an effective joining system.
Special care has been taken to maximize the performance of the
joiner for each BEAM option.
WEIGHT
4 ft 8 ft 12 ft 12.3 lbs / 5.0 kg
24.6 lbs / 10.1 Kg
36.9 lbs / 15.1 Kg
NOTE: Hang each system segment individually.
Do not assemble system prior to hanging.
SYSTEM (S#)
MR16
BEAM 3 linear systems, with the use of a strong profile, allow for a
nearly hair thin connection system of continuous runs.
Lengths of 4', 8', 12' as well as custom lengths are available.
Runs of BEAM 3 that are greater than 12' in length are designated as
systems (S#). This means that the run is comprised of a combination
of 4', 8' and/or 12' sections to be assembled on site using our joining
system. For more information on systems and joining, please refer to
the BEAM installation sheets available for download at
www.axislighting.com.
Blank MR16 Halogens
MR16 LED
Quantity
Spacing
Extruded Aluminum (0.075'' nominal)
2.0'' diameter (35W / 50W)
2.0'' diameter
For every 4' fluorescent lamp section,
there may be up to a maximum of
4 x MR16 lamps.
Each MR16 is placed centered on a blank section 9'' in length.
4"
3 13/32"
For a series of MR16's within a given section length, they will be spaced evenly on a longer blank section.
The directed light of MR16 Halogen lamps are fixed downward.
Custom spacing may be available on special request. *Please consult factory
ELECTRIC AL
Ballast
Emergency
Voltage
Electronic IS, Electronic Rapid Start, Dimming (0-
10V, Line, Step, EcoSystem, DALI) with preinstalled
ballast disconnect as per NEC & CEC
Emergency battery pack or emergency circuit
120V, 277V, 347V, UNV
Incorporating these components may have limitations or effect the
length of the luminaire, please contact factory for more details.
Between
fluorescent
lamps sections
APPROVALS
9"
Certified to UL and CUL standards
Meets NYC requirements
At luminaire
ends
FINISH
Aluminium paint, Powder Coated and custom finishes are also
available.
9"
Several in a
long blank
section
variable
FILE NAME:BM.ASYM.SPEC
July 8, 2013
Product design and development is an ongoing process at Axis Lighting. We reserve the right to change specifications. Contact Axis for the latest product information.
Project:
Transbay Marketing Center
Project #
13168.00
Date:
© 2011 Axis Lighting Inc. Page: 2 / 5
10 December 2013
Type:
F7,F7A,F7B
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
1.800.263.AXIS
[ T ] 514.948.6272
[ F ] 514.948.6271
PENDANT ASYMMETRIC MOUNT
www.axislighting.com
SA STEM MOUNT IN DRYWALL CEILING
OPTICS
ASYMMETRIC FROSTED LENS
(acrylic snap-in lens)
frosted: 85% trans.
AF asymmetric frosted
ASYMMETRIC NO LENS
(asymmetric reflector)
Power feed
Non power feed
A asymmetric
ASYMMETRIC
MOUNTING SPACING
Inner Asymmetric Reflector
Outer Asymmetric Reflector
Die Formed Specular Aluminum (22 gauge)
Extruded Aluminum (0.075'' nominal)
Outer Asymm
reflector sits flush
3 7/16"
(46 5/16" C.C.)
8'
(92 5/8" C.C.)
12'(138 15/16" C.C.)
T8 LAMP
4"
Inner Asymm
reflector
T5/T5HO LAMP 4'
1 7/8"
4'
8'
12'
(48" C.C.)
(96" C.C.)
(144" C.C.)
OTHER MOUNTING OPTIONS
BEAM 3 is also available with recessed, surface, wall, recessed wall, asymmetric and wall wash mounted options.
Specification sheets and Installation sheets for all mounting for BEAM luminaires are available for download at www.axislighting.com
FILE NAME:BM.ASYM.SPEC
July 8, 2013
Product design and development is an ongoing process at Axis Lighting. We reserve the right to change specifications. Contact Axis for the latest product information.
Project:
Transbay Marketing Center
Project #
13168.00
Date:
© 2011 Axis Lighting Inc. Page: 3 / 5
10 December 2013
Type:
F7,F7A,F7B
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
1.800.263.AXIS
[ T ] 514.948.6272
[ F ] 514.948.6271
PENDANT ASYMMETRIC MOUNT
www.axislighting.com
INTEGRATED CONTROL OPTIONS
BEAM 3 luminaires allow the use of integrated controls such as daylight sensors (DS),
occupancy sensors (OS), individual daylight sensors and occupancy sensors (DS+OS),
and combination daylight/occupancy sensors (DOS). These options can be seamlessly
integrated into our luminaires. The control system could be used to optimize the lighting
of the space by reducing energy consumption through daylight harvesting and occupancy,
thereby improving the overall interior environment and allowing for LEED credits.
CONTROL
SENSORS
● Consult factory for other options.
● Refer to IC brochure for more information.
SENSORS
BRAND
Model
TYPE
CODE
COMPATIBLE DIMMING BALLAST
Lutron
EC-DIR-WH
Daylight
LD
EcoSystem
Wattstopper
FD-301
Daylight
WD
0-10V
Philips
Luxsense
Daylight
PL
0-10V
FS-205
PIR Occupancy
WP1
Programmed Rapid Start
Occupancy Sensor (OS) Wattstopper FS-355
PIR Occupancy
WP2
Programmed Rapid Start
FM-105
High Frequency Occupancy
WH
Programmed Rapid Start
Actilume
Daylight & PIR Occupancy
PA
DALI or 0-10V
Daylight Sensor (DS)
Daylight & Occupancy
Sensors (DOS)
Philips
PHOTOMETRIC DATA
CANDELA DISTRIBUTION
1 T5
COEFFICIENTS OF UTILIZATION (%)
Zonal
Lumens
Horizontal Angles
Vertical
Angle
PHOTOMETRIC CURVE
90°
90°
104
209
60°
45°
417
60°
626
30°
45°
834
0°
90°
30°
15°
0°
15°
Test Lamp: 1xF28T5
IES FILE: BMD-A-4-T5-1
Efficiency: 70.3%
0
5
15
25
35
45
55
65
75
85
90
95
105
115
125
135
145
155
165
175
180
0
23
45
68
90
135
157
180
569
510
395
304
233
178
126
80
46
15
1
0
0
0
0
0
0
0
0
0
0
569
498
397
314
243
187
133
88
47
16
1
0
0
0
0
0
0
0
0
0
0
569
506
432
352
281
213
155
99
52
16
1
0
0
0
0
0
0
0
0
0
0
569
535
482
416
348
275
201
129
63
16
2
0
0
0
0
0
0
0
0
0
0
569
564
558
519
485
418
345
247
143
36
2
0
0
0
0
0
0
0
0
0
0
569
621
705
783
827
812
720
490
242
54
5
0
0
0
0
1
1
0
0
0
0
569
650
755
866
916
878
703
462
216
52
4
0
0
0
0
0
1
1
0
0
0
569
652
780
892
939
878
678
450
205
49
4
0
0
0
0
0
1
1
0
0
0
Wall
31
135
238
324
376
375
304
188
65
2
0
0
0
0
0
0
0
0
80
Ceiling
70
50
70 50 30 10 70 50 30 10 50 30 10
0
84 84 84 84 82 82
1
76 73 69 67 74 71
2
69 63 58 54 67 61
3
62 55 49 44 61 54
4
57 48 42 37 55 47
5
52 43 36 31 51 42
6
48 38 32 27 47 38
7
44 34 28 24 43 34
8
41 31 25 21 40 31
9
38 29 23 19 37 28
10
36 26 21 17 35 26
Based on floor reflectance of 20
82
68
57
48
41
36
31
28
25
22
20
82
66
53
44
36
31
27
24
21
19
17
78
68
59
51
45
40
36
33
30
27
25
78
66
55
47
40
35
31
27
24
22
20
78
63
52
43
36
31
27
23
21
18
17
LUMINANCE DATA (CD/M 2)
Horizontal Angles
Vertical Angle
45
55
65
75
85
0
984
708
477
296
112
23
1060
770
539
317
120
90
4189
4126
3792
3210
1594
135
5069
4687
3441
1908
498
180
4866
3829
2673
1326
358
All IES files for other lamping are available for download at: www.axislighting.com
FILE NAME:BM.ASYM.SPEC
July 8, 2013
Product design and development is an ongoing process at Axis Lighting. We reserve the right to change specifications. Contact Axis for the latest product information.
Project:
Transbay Marketing Center
Project #
13168.00
Date:
© 2011 Axis Lighting Inc. Page: 4 / 5
10 December 2013
Type:
F7,F7A,F7B
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
1.800.263.AXIS
[ T ] 514.948.6272
[ F ] 514.948.6271
PENDANT ASYMMETRIC MOUNT
www.axislighting.com
PHOTOMETRIC DATA
CANDELA DISTRIBUTION
1 T5HO
COEFFICIENTS OF UTILIZATION (%)
Zonal
Lumens
Horizontal Angles
Vertical
Angle
PHOTOMETRIC CURVE
90°
90°
180
361
60°
45°
722
60°
1083
30°
45°
1444
0°
90°
30°
15°
0°
15°
Test Lamp: 1xF54T5HO
IES FILE: BMD-A-4-T5HO-1
Efficiency: 70.3%
0
5
15
25
35
45
55
65
75
85
90
95
105
115
125
135
145
155
165
175
180
0
23
45
68
90
135
157
987
833
678
530
403
303
211
143
80
27
1
0
0
0
0
0
0
0
0
0
0
987
884
697
546
420
322
231
148
81
27
1
0
0
0
0
0
0
0
0
0
0
987
895
742
611
490
369
268
172
88
27
2
0
0
0
0
0
0
0
0
0
0
987
915
807
729
604
470
345
217
109
28
3
0
0
0
0
0
0
0
0
0
0
987
989
965
912
838
728
585
423
244
63
4
0
0
0
0
0
0
0
0
0
0
987
1094
1229
1357
1434
1398
1231
849
426
96
9
0
0
0
0
1
1
1
0
0
0
987
1093
1305
1490
1575
1517
1212
790
374
88
7
0
0
0
0
0
1
1
0
0
0
Wall
31
135
238
324
376
375
304
188
65
2
0
0
0
0
0
0
0
0
80
Ceiling
70
50
70 50 30 10 70 50 30 10 50 30 10
0
84 84 84 84 82 82
1
76 73 70 67 74 71
2
69 63 58 54 67 62
3
63 55 49 44 61 54
4
57 48 42 37 55 47
5
52 43 36 31 51 42
6
48 38 32 27 47 38
7
44 35 28 24 43 34
8
41 31 25 21 40 31
9
38 29 23 19 37 28
10
36 26 21 17 35 26
Based on floor reflectance of 20
82
68
57
48
41
36
31
28
25
23
20
82
66
53
44
37
31
27
24
21
19
17
78
68
59
52
45
40
36
33
30
27
25
78
66
55
47
40
35
31
27
25
22
20
78
64
52
43
36
31
27
23
21
19
17
LUMINANCE DATA (CD/M 2)
Horizontal Angles
Vertical Angle
45
55
65
75
85
0
1678
1192
850
519
201
23
1822
1336
901
540
210
90
7302
6991
6495
5483
2810
135
8729
8013
5958
3351
895
180
8498
6623
4577
2267
613
All IES files for other lamping are available for download at: www.axislighting.com
FILE NAME:BM.ASYM.SPEC
July 8, 2013
Product design and development is an ongoing process at Axis Lighting. We reserve the right to change specifications. Contact Axis for the latest product information.
Project:
Transbay Marketing Center
Project #
13168.00
Date:
© 2011 Axis Lighting Inc. Page: 5 / 5
10 December 2013
Type:
F7,F7A,F7B
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
PROJECT
SPECIFIER
TYPE
ZONE
__
__
SKU
1. SERIES
LIGHT ENGINE
24V DC
DIMMING
CLASS 2
IP20 DRY LOCATION
NOTE
SUITABLE FOR INSTALLATION WITHIN THE CLOSET STORAGE SPACE (WITH CLOTHING)
2. COLOR
CODE
ETL (INTERTEK) APPROVED NFPA ATRICLE 410.16 (ALL SECTIONS)
UL LISTED 2108 FILE NUMBER E364348
LUMINAIRE MUST BE INSTALLED IN ACCORDANCE WITH NFPA 70, ARTICLE 410.16
1. SERIES
2. COLOR
94+ CRI WHITE
8000 SERIES HIGH OUTPUT
SINGLE BIN
8024 83+CRI 6.0W /ft ≤546 Lm/ft
8924 94+CRI 5.6W /ft ≤463 Lm/ft
8024/8924 SERIES
CCT
2150K 94CRI
2650K 97CRI
2950K 97CRI
COLOR
CODE
22
26
29
83+ CRI WHITE
SINGLE BIN
0.55
1.0
0.10
MIN INCREMENT = 1 INCH / MAX PER CIRCUIT = 15 FEET
27
30
35
40
60
2700K
3000K
3500K
4000K
6000K
COLORS
4000 SERIES MID OUTPUT
4924 94+CRI 2.8W /ft ≤236 Lm/ft
0.40
4024/4924 SERIES
UL E364348
R
G
B
A
PK
PR
RED
GREEN
BLUE
AMBER
PINK
PURPLE
4024 83+CRI 3.0W /ft ≤279 Lm/ft
3W/FT 24VDC
2.0
CRI = Color Rendering Index
CCT = CorRelated Color Temperature
0.10
MIN INCREMENT = 2 INCHES / MAX PER CIRCUIT = 30 FEET
3000 SERIES LOW OUTPUT
(INDIRECT APPLICATIONS ONLY)
3024 83+CRI 1.5W /ft ≤137 Lm/ft
3924 94+CRI 1.4W /ft ≤116 Lm/ft
0.40
3024/3924 SERIES
UL E364348
1.5W/FT 24VDC
4.0
0.10
MIN INCREMENT = 4 INCHES / MAX PER CIRCUIT = 32 FEET
COMPONENT OF A COMPLETE SYSTEM INCLUDING: AION LED A-TRACK LIGHT ENGINE, AION LED A-TRACK HOUSING WITH DIFFUSER LENS, & AION LED DRIVER (POWER SUPPLY). DIMMER NOT
INCLUDED. APPROVED DIMMERS, CONTROLS, POWER SUPPLIES, CABLE, & OTHER COMPONENTS ONLY. CONTACT AION LED FOR QUESTIONS REGARDING COMPATIBILTY. ELECTRICIAN INSTALLED.
STRICTLY ADHERE TO NEC & LOCAL BUILDING CODE. LIMITED 5-YEAR WARRANTY AGAINST MANUFACTURING DEFECTS ONLY, DOES NOT COVER LABOR; VOIDED BY: INADEQUATE VENTILLATION,
FIELD MODIFICATIONS, INSTALLATION BY UNQUALIFIED PERSONNEL, UNAPPROVED CONTROLS, DRIVERS, CABLING, OTHER DEVICES, NOT FOLLOWING INSTALLATION GUIDELINES & PROTOCOL,
GENERAL NEGLIGENCE. INSTALLER ASSUMES ALL LIABILITY WITH REGARD TO PROPERTY & SAFETY. THIS PRODUCT IS UL LISTED. SEE SEPARATE: “AION LED WARRANTY TERMS” & ADDITIONAL
INSTRUCTIONAL MATERIALS FOR MORE INFORMATION. AUTHORIZED INSTALLERS ONLY. SYSTEMS TESTED PRIOR TO SHIPPING.
© Copyright 2013 Aion LED, Inc. All Rights Reserved
Project:
Transbay Marketing Center
Project #
13168.00
(415) 255-AION (2466)
Date:
www.AionLED.com
10 December 2013
Type:
F8
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
A-TRACK
SEAMLESS FIXTURE UP TO 30 FEET PER CIRCUIT (24V)
CUSTOM CRAFTED TO GIVEN DIMENSIONS
BEST IN CLASS DIFFUSION OPTIONS
HIGH QUALITY, HIGH OUTPUT
CABLE ARMOR OPTION
COMPATIBLE WITH PS TYPE: 4000, 4024, 8024, 7000-RGB, & 7024-RGB
LINEAR FIXTURE -NOT INCLUDED, SOLD SEPARATELY
(multiple pages)
Warning: Installation should only be attempted by qualified and authorized personnel. Licensed electricians and trained technicians must wire all components in strict
compliance with local building codes. Installer assumes all liability for safety and hazard mitigation. Aion LED is not liable for damages incurred by negligence, faulty
wiring, poor design, overloading, or other. Authorized Aion LED Installers are trained in installation methods, materials, and code-related protocol.
AION LED, LLC
2325 3RD ST #330 SAN FRANCISCO, CA 94107
© Copyright 2012 Aion LED All Rights Reserved
TOLL FREE: (877) 345-AION [2466]
INTERNATIONAL PATENTS PENDING
Project:
Transbay Marketing Center
Project #
13168.00
Date:
FAX: (415) 285-1335
CustomerCare@AionLED.com
www.AionLED.com
10 December 2013
Type:
F8
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
Project:
Transbay Marketing Center
Project #
13168.00
Date:
10 December 2013
Type:
F8
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
Class 2 Dimming LED Driver
24 Volt
ELECTRICIAN INSTALLED
MODEL
D20-D-24
DIMENSIONS (L-W-H) INCHES
WATTAGE
RATING
CLASS 2 (UL STANDARD)
NEMA 3R CASE
INPUT VOLTAGE
OUTPUT VOLTAGE LOADED
VOLTAGE OPEN
MAX INPUT CURRENT
PRIMARY BREAKER
SECONDARY BREAKER
DIMMING
DIMMER TYPE*
LEADS PRIMARY AWG, TEMP
LEADS SECONDARY AWG, TEMP
THERMAL CLASS
BOOST TAP 10%
MAX FEET #3024/3924 SERIES
MAX FEET #4024/4924 SERIES
MAX FEET #8024/8924 SERIES
(5 x 2.1 x 2)
20
ETL (UL 8750)
Yes
Indoor
120V 60Hz
23.5 VDC
25.5 VDC
206mA
Thermal
2A
Triac/ Primary
Magnetic/ Low-voltage
#20 105 C
#16 105 C
(B) 130 C
No
12
6
3
D40-D-24
(5 x 2.1 x 2)
40
ETL (UL 8750)
Yes
Indoor
120V 60Hz
23.5 VDC
25.5 VDC
360mA
Thermal
4A
Triac/ Primary
Magnetic/ Low-voltage
#20 105 C
#16 105 C
(B) 130 C
No
24
12
6
D60-D-24
(8.5 x 3 x 2.9)
60
ETL (UL 1310)
Yes
Indoor/ Outdoor
120V 60Hz
23.5 VDC
25.5 VDC
0.6A
1A THERMAL
5A THERMAL
Triac/ Primary
Magnetic/ Low-voltage
#18 105 C
#12 105 C
(B) 130 C
Yes
36
18
9
D100-D-24
(9 x 4.2 x 3.25)
96
ETL (UL 1310)
Yes
Indoor/ Outdoor
120V 60Hz
23.5 VDC
25.5 VDC
1A
2A THERMAL
4A MAGNETIC
Triac/ Primary
Magnetic/ Low-voltage
#18 105 C
#12 105 C
(B) 130 C
Yes
60
30
15
D300-D3-24
(7 x 7 x 3.2)
288 (3 x 96)
ETL (UL 1310)
Yes
Indoor
120V 60Hz
23.5 VDC
25.5 VDC
3A
5A THERMAL
(3X) 4A MAGNETIC
Triac/ Primary
Magnetic/ Low-voltage
#18 105 C
#12 105 C
(B) 130 C
Yes
180
90
45
*CONTROLS COMPATIBILITY
1. 2 WIRE, FORWARD-PHASE, MAGNETIC TRANSFORMER. LOAD DRIVER BETWEEN 50 to 90% OF MAXIMUM RATED WATTAGE.
2. MAGNETIC LOW VOLTAGE DIMMERS SUCH AS: LUTRON HOMEWORKS, GRAFIK EYE, RADIO RA, & NOVA -SELECT MODELS ONLY.
3. LOW END DIMMING PERCENTAGE VARIES PER MODEL. CONTACT AION LED FOR MORE INFORMATION REGARDING APPROVED CONTROLS.
MAX LED RUN PER CIRCUIT
1. [4A (96W) per circuit] (NEC Article 725)
2. 10% headroom included
3. Use electrical junction boxes to transition between building wire and Aion LED power feeds per local code.
SUB BOXES
Use larger guage cord for sub feeds and longer runs. Junction building wire to fixture whips within electrical boxes per local code.
HEAT & EMI
MAGNETIC DC TRANSFORMERS EMIT HEAT AND ELECTROMAGNETIC ENERGY. ADEQUATE VENTILATION REQUIRED (NEC ARTICLE 450)
PLEASE LEAVE 15 INCHES OF SPACE BETWEEN EACH TRANSFORMER.
MAGNETIC LOW-VOLTAGE
120VAC
FIRM
D-24-SERIES
24VDC
TYPE
DESC
+
_
L
N
JOB
SKU
MEMO
[FOR NEUTRAL DIMMING SWITCHES: REFER TO MANUFACTURER’S INSTRUCTIONS
Warning: Installation should only be attempted by qualified and authorized personnel. Licensed electricians and trained technicians must wire all components in strict
compliance with local building codes and NEC. Installer assumes all liability for safety and hazard mitigation. Aion LED is not liable for damages incurred by
negligence, faulty wiring, poor design, overloading, inadequate ventilation, inadequate spacing, or other. Authorized Aion LED Installers are trained in installation
methods, materials, and code-related protocol.
AION LED, INC.
2325 3RD ST #330 SAN FRANCISCO, CA 94107
TOLL FREE: (877) 345-AION [2466]
© Copyright 2012 Aion LED All Rights Reserved
Project:
Transbay Marketing Center
Project #
13168.00
FAX: (415) 285-1335
CustomerCare@AionLED.com
www.AionLED.com
Date:
10 December 2013
Type:
F8
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
HORNET® HP DOWNLIGHT
HDL-HP-RA-TL
LED
3.5” ROUND ADJUSTABLE TRIMLESS LED
APPLICATIONS:
Retail and commercial accent & display lighting
OPTICS:
LED:
Color Temp Options: 2700K, 3000K, 3500K, 4000K
CRI: 85 typ. (2700K, 3000K, 3500K, 4000K)
90 typ. (3000K)
Binning: 3 MacAdam (SDMC)
Lumen Maintenance: >70% of intial lumens @ 50,000 hrs
Lumen Output per head at 3000K, 0º tilt:
17w: Spot 818 typ.
20w: Spot 986 typ.
Flood 748 typ.
Flood 901 typ.
Wide Flood 693 typ.
Wide Flood 835 typ.
0-30º lockable tilt, 358º rotation
CONSTRUCTION:
20 ga. galvanized steel frame
18 ga. galvanized steel splice housing and hanger
brackets
Cast aluminum plaster frame w/perforated face
Die-cast optical housing
Extruded aluminum and die-cast heat sink
ELECTRICAL:
Electronic constant current LED driver
120v or 277v input
Dimming options available for Triac, ELV, 0-10v and
Lutron systems. See following pages for more information.
This product complies with IEEE C62.41 for surge endurance up to 2.5KV. Amerlux® recommends using additional surge protection with this unit (supplied by others),
surge damage is not covered by warranty.
MOUNTING:
For use in sheet rock ceilings
(max ceiling thickness 1”)
PROJECT:
LABELING:
R
C
US
TYPE:
11 3/4”
7 3 /4 ”
4 11/16 ”
For indoor use only
IC/AT rated (17w only, not Energy Star rated)
Damp location
30º
5
3 1 /2 ”
3 9/16”
11 1/2 ”
Electrostatic sensitive device,
observe precautions for
handling
/8”
Ceiling Cut Out Dimension: 4 1/2” dia.
14 /2” min - 26” max
1
1. Reflector Trim
2. Fixture Housing Aperture Plate
3. Ceiling 5/8” (1” max)
2 4. Cast Aluminum Plaster Frame
5. Plaster Skim Coat (by others)
1 6. 6-32 Type F Thread Cutting Screw
ELECTRICAL
17w
20w
System
System
Driver
Watts Amps Watts Amps
Electronic 120v 17
0.14
20
0.17
277v 17
0.06
20
0.07
3
4
6
5
5
(see website for details)
ORDERING INFORMATION:
Housing:
Model
Wattage
HDL-HP-R-TL 17
20
Lamp
Type
Driver
Voltage
LED
E - electronic 120
277
Options/Accessories
DIM-ELV- ELV dimming (120v only)
DIM-TRIAC - Triac dimming (120v only)
HILUME - Lutron Hi-lume® dimming
0-10V - 0-10v dimming
MF multi-function driver
CP - Chicago Plenum
EM - emergency battery pack
w/remote test switch
Trim:
Model
Aperture Finish
HDL-HP-RA-TL
MB - matte black NSP - narrow spot, 12º
MW - matte white SP - spot, 15º
SLV - matte silver NF - narrow flood, 20º
MFL - medium flood,
24º
FL - flood, 28º
WF - wide flood, 45º
LS - linear spread,
60º x 10º
IC/AT* - insulated ceiling/air tight
(17w only)
Complete Example: HDL-HP-R-TL-20-LED-E-120/HDL-HP-RA-TL-MBW-FL-3000
Housing Example: HDL-HP-R-TL-20-LED-E-120
Reflector Example: HDL-HP-RA-TL-MBW-FL-3000
Beam Spread
Color
Temp
2700*
3000
3500
4000
3000-90*
(90CRI)
* NOTE: 2700, 3000-90CRI & IC/AT are not Energy Star rated
Cat #:
Amerlux® reserves the right to change details that do not affect overall function and performance.
Amerlux®, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com
Project:
Transbay Marketing Center
Project #
13168.00
Date:
10 December 2013
Type:
F9, F9A
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
HORNET® HP DOWNLIGHT
HDL-HP-RA-TL
3.5” ROUND ADJUSTABLE TRIMLESS LED
LED
TYPE:
FIXTURE DATA: For 17w data, multiply by 0.85
Complete photometric data (ies format) available upon request.
20W LED
SPOT
DISTRIBUTION
LTL # 36952
FLOOD
DISTRIBUTION
LTL # 36953
90
WIDE FLOOD
DISTRIBUTION
LTL # 36954
90
90
600
1200
2500
60
60
60
5000
2400
1200
7500
3600
1800
0
30
Candelas at Nadir
Deg
Candela
0
8680
5
7080
15
1074
25
132
35
26
45
2
APPLICATION DATA:
0
30
Candelas at Nadir
Deg
Candela
0
3713
5
3354
15
1502
25
324
35
48
45
5
0
30
Candelas at Nadir
Deg
Candela
0
1821
5
1743
15
1215
25
544
35
123
45
9
Notes and Definitions:
Beam spread is to 50% center beam candlepower (CBCP).
D=Distance to floor or wall.
FC=Footcandles on floor or wall at center beam aiming location.
L=Effective Visual Beam length in feet (50% of maximum footcandle level).
W=Effective Visual Beam width in feet (50% of maximum footcandle level).
CB=Distance across or down to center beam location.
D
CB
30°
30°
D
FC
L
W
W
FC
L
CB
W
FC
L
SPOT
D
5.0’
7.5’
10.0’
12.5’
FC
233
126
76
51
L
1.8
2.6
3.3
4.0
W
1.8
2.6
3.3
4.0
FLOOD
D
5.0’
7.5’
10.0’
12.5’
FC
120
59
35
23
L
2.6
3.5
4.7
5.7
W
2.6
3.5
4.7
5.7
WIDE
FLOOD
0o Aiming Angle
Horizontal
Footcandles
D
5.0’
7.5’
10.0’
12.5’
FC
73
33
19
12
L
3.2
4.7
6.3
7.8
W
3.2
4.7
6.3
7.8
Amerlux®, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com
Project:
Transbay Marketing Center
Project #
13168.00
LIT-1262 rev 10/13
Date:
10 December 2013
Type:
F9, F9A
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
HORNET® HP DOWNLIGHT
HDL-HP-RA-TL
3.5” ROUND ADJUSTABLE TRIMLESS LED
LED
TYPE:
DIMMING COMPATIBILITY:
Amerlux® “Hornet®” fixtures are compatible with all major dimming protocols prevalent in the United States. Please see
below for general compatibilities and wiring diagrams. Amerlux® recommends testing your unique dimming configuration as
the exact full configuration (Dimmer, Fixture Quantity, Voltage, etc) may affect dimming performance.
TRIAC (Forward Phase) DIMMING (-DIM-TRIAC Option) ---not compatible with 12w module--Utilizes “Standard” incandescent dimmers that are in wide use in installations across the US. Best for retrofit applications
where Triac dimmers are installed.
Wiring Diagram
Notes:
• 120v ONLY
Driver
Triac
• Dims down to less than 5% light output (most cases)
Black Black
Dimmer
LED
• Consult Dimming manufacturer for installastion
RED
White
(by others)
instructions - DO NOT SHARE NEUTRALS!
Green
• Must meet dimmer Minimum Load Requirements
per dimming manufacturer
120v
Compatible Dimmers
Wall Box (Incandescent Style, Wattage as required)
Central System
Lutron “Diva”
Lutron “Vareo”
ETC “SR” Rack w/D20
ETC “DRD” Rack w/D20
Lutron “Nova-T”
Lutron “Skylark”
Module
Module
Lutron “Maestro”
Lutron “GP” Panel
Lutron Grafix Eye QS
ELV - Electronic Low Voltage (Reverse Phase) DIMMING (-DIM-ELV Option)
Utilizes specialized “ELV” dimmers. Best for New Construction appilications
Notes:
• 120v ONLY
• Dims down to less than 5% light output (most cases)
• Consult Dimming manufacturer for installastion
instructions - DO NOT SHARE NEUTRALS!
• Must meet dimmer Minimum Load Requirements
Wiring Diagram
Driver
Black Black
RED
White
Green
ELV
Dimmer
(by others)
LED
120v
Compatible Dimmers
Wall Box (ELV Style)
Lutron “Diva”
Lutron “Nova-T”
Lutron “Maestro”
Leviton “Surslide”
Lutron “Vareo”
Lutron “Skylark”
Leviton “Vizio”
Central System
ETC “SR” Rack w/ELV10
Module
Lutron “GP” Panel with
PHPM-PA Interface
ETC “DRD” Rack w/ELV10
Module
Lutron Grafix Eye QS with
PHPM-PA Interface
0-10V - DIMMING (-0-10V Option)
Integrates into a variety of building management and day-lighting controls
Wiring Diagram
Notes:
• 120v - 277v
• Dims down to less than 10% light output
• Requires interface to turn off power to driver
• Consult Dimming manufacturer for installastion
instructions - DO NOT SHARE NEUTRALS!
Compatible Dimmers
Wall Box
Lutron “Diva” - DVTV with
PP-120H Interface
Leviton Renoir II 0-10v
Driver
Violet Black
RED
Grey
0-10v
Dimmer
Black
White
Green
Bldg
Power or
Interface
Central System
Lutron Grafix Eye with
GRX-TVI Interface
Amerlux®, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com
Project:
Transbay Marketing Center
Project #
13168.00
LED
LIT-1262 rev 10/13
Date:
10 December 2013
Type:
F9, F9A
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
HORNET® HP DOWNLIGHT
HDL-HP-RA-TL
3.5” ROUND ADJUSTABLE TRIMLESS LED
LED
TYPE:
LUTRON HI-LUME / ECO-SYSTEM (-DIM-HILUME Option)
Integrates into a variety of building management and day-lighting controls
3-Wire Wiring Diagram
Notes:
• 120v or 277v
Driver
• Dims down to less than 5% light output
3-Wire FL
Black
Switched Hot
• May use 3-Wire or Ecosystem Control
Control
Orange
Dimmed Hot
• Consult Dimming manufacturer for installastion
(by others)
White
Neu
instructions - DO NOT SHARE NEUTRALS!
Green
Gnd
Purple/Grey E2
Purple
E1
Compatible Dimmers
Wall Box (3-Wire Fluorescent)
ECO-Sys Bus
DIVA
Cap Wires
Maestro
Nova T
ECO System Digital Control Wiring
Vareo
Cap Lead
Central System
Lutron ECO-System compatible controls
ETC “SR” Rack w/D20F Module
ETC “DRD” Rack w/D20F Module
ECO
System
Control
(by others)
Black
Orange
White
Green
Purple/Grey
Purple
Driver
Switched Hot
Dimmed Hot
Black
RED
LED
Black
RED
LED
VV+
VV+
Neu
Gnd
E2
E1
ECO-Sys Bus
MULTI-FUNCTION
Emergency Configuration
120v/277v
Normal
Power
120v/277v
Normal
Power
Primary
Driver
Emergency system (by
others) to ensure only one
feed is active at a time.
120v/277v
Emergency
Feed
(by others)
Night Light Configuration
LED
Primary
Driver
On/Off
control
LED
(by others)
Secondary
Driver
120v/277v
Constant
Power
Secondary
Driver
In Night Light configuration
Multi-Function driver provides
10 mA of drive current when
primary driver is switched off.
17w = 2% output
20w = 1.5% output
In Emergency configuration
Multi-Function driver provides
100 mA of drive current.
17w = 20% output
20w = 16% output
Patent-Pending
Amerlux®, LLC • 23 daniel road, fairfield NJ 07004 • p: 973.882.5010 f: 973-882.2605 • www.amerlux.com
Project:
Transbay Marketing Center
Project #
13168.00
LIT-1262 rev 10/13
Date:
10 December 2013
Type:
F9, F9A
LIGHT FIXTURE CUT SHEET Note: This document is for information only. Refer to specifications for all catalog numbers, lamps, finishes, etc.
Horton Lees Brogden Lighting Design 300 Brannan Street Suite 212 San Francisco, California 94107 tel 415.348.8273 www.hlblighting.com
December 12, 2013
Bid & Permit
Gensler
01.9462.002
Transbay Marketing Center
50 Fremont Street, 21st floor
San Francisco, CA
SECTION 26 51 00 – ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS
PART 1 – GENERAL
1.1
A.
1.2
A.
1.3
A.
1.4
DESCRIPTION
Provide and install lighting fixtures as shown on drawings and as specified in this and all
related Sections.
RELATED SECTIONS
26 06 51
Lighting Fixture Schedule
DEFINITIONS
The term Architect refers to the Architect, Interior Designer, Lighting Designer or Owner’s
Representative individually or collectively.
GENERAL REQUIREMENTS
A.
Provide all lighting fixtures as shown complete with all lamps, completely wired, controlled
and securely attached to supports.
B.
Where a catalog number and a narrative or pictorial descriptions are provided, the written
description shall take precedence and prevail.
C.
General Contractor shall provide electrical subcontractor with entire lighting specification
(including fixture illustrations and sketches); electrical subcontractor shall provide each
specified manufacturer with complete information about the fixtures they will supply.
D.
Type of fixtures shall be as indicated alphanumerically and as specified.
E.
Fixture details shown may be modified by the manufacturer provided all of the following
conditions have been met:
1.
Fixture performance is equal or improved;
2.
Structural, mechanical, electrical, safety, and maintenance characteristics are equal or
improved;
3.
Cost to the Owner is reduced or equal.
4.
Modifications have been reviewed by the Architect and have been approved by the
Architect in writing.
1.5
A.
STANDARDS
The standards and regulating committees referred to in this specification and to which
compliance with is required are:
1.
2.
3.
4.
UL
NRTL
NEC
ANSI
Underwriters Laboratories
Nationally Recognized Testing Laboratory
National Electric Code
American National Standards Institute
ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS
Copyright 2011 Gensler
26 51 00 - 1
December 12, 2013
Bid & Permit
Gensler
01.9462.002
5.
6.
7.
Transbay Marketing Center
50 Fremont Street, 21st floor
San Francisco, CA
ASTM American Society of Testing and Materials
NEMA National Electrical Manufacturers Association
IEC
International Electrotechnical Commission
B.
All fixtures and assembled components shall be new, of good quality, and be approved by and
bear the label of UL for the applicable location and conditions (wet, damp, dry, etc.) or other
approved testing agencies, i.e. CSA, ETL, unless otherwise specified in writing.
C.
All fixtures shall meet all required local, state and/or national building, electrical and energy
codes and regulations.
1.6
BIDDING
A.
Follow bidding procedures as described in Division 01 of this specification.
B.
Provide unit and alternate prices as required in Section 26 06 51 Lighting Fixture Schedule.
1.7
A.
SUBSTITUTIONS
Bidders' attention is called to the following procedure to be followed in submitting alternate
fixture manufacturers than those specified:
1.
2.
3.
4.
Bidders wishing to obtain approval on brands other than those specified by name and/or
catalog number in Section 26 06 51, Lighting Fixture Schedule, shall submit their
requests not later than ten (10) business days before the bid opening. Approval will be in
the form of an addendum to the specifications issued to all prospective bidders indicating
that the additional brand or brands are approved as equal to those specified as far as the
requirements of the project are concerned. If the bidders do not elect to obtain prior
approval during the time so specified, the Owner has no obligation to review or consider
any such article after the contract award.
If the bidder wishes to substitute fixtures from alternate manufacturers, his attention is
called to Section 2.1, GENERAL MATERIAL REQUIREMENTS of PART 2 PRODUCTS. In addition, he shall note that the dimensions of visible parts of many
fixtures (for example, the aperture diameters of incandescent fixtures) are binding to the
bidder and cannot be changed without prior approval by the Architect.
Contractor shall pay professional fees (at current standard hourly rates) and reimburse
expenses directly to all designers (Architect, Engineer, Lighting Designer, et. al.) for
time spent reviewing substitutions proposed by the Contractor. If payment by the
Contractor is not made within 60 days of invoice date, the Owner shall deduct the
amount due from subsequent payments to the Contractor in order to reimburse designers.
Request for approval shall be accompanied by working fixture samples (with an
appropriate lamp, complete photometric, mechanical and electrical data, list of materials
and finishes and unit cost to the Owner) of both the specified brand and the proposed
substitutes as required to make complete comparison and evaluation. These samples shall
be in addition to those required by Lighting Fixture Specification. The above data shall
be delivered separately to the Architect and the Lighting Designer. The fixture samples
shall be furnished and installed, at the bidder's expense, at the location selected by the
Architect. In addition, the bidder shall furnish the Architect and the Lighting Designer
with the name and location of at least one completed project where each proposed
substitute has been in operation for a period of at least six (6) months, as well as the
names and addresses of the Owner, the Lighting Designer and the Architect of record.
ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS
Copyright 2011 Gensler
26 51 00 - 2
December 12, 2013
Bid & Permit
Gensler
01.9462.002
1.8
Transbay Marketing Center
50 Fremont Street, 21st floor
San Francisco, CA
SUBMITTALS
A.
For standard catalog items with no modifications, submit catalog cut sheets prepared by the
manufacturer which clearly show all elements to be supplied and all corresponding product
data (including lamping; ballast manufacturer and model number; voltage; accessories or
options and any miscellaneous items detailed in the written description of the specification.) If
cut sheet shows more than one (1) fixture type, all non-applicable information shall be crossed
out.
B.
For standard cataloged fixtures:
1.
2.
Submit one sample cone for each fixture type for review. Submit a certificate of
compliance with Alzak finish requirements with all requests for approval.
When more than one louver panel occurs in a fixture, submit as a part of shop drawings
the dimensioned layout of individual louver panels and supporting "tee" members.
C.
For custom fixtures, modified fixtures or linear fluorescent fixtures mounted in continuous
rows, submit an engineered line drawing prepared by the manufacturer showing all details of
construction, lengths of runs, lamping layout, pendant locations, power locations, finishes and
list of materials. Drawings must be to scale. Contractor shall provide manufacturer with field
dimensions where required. If scallop shields, wallwash reflectors or baffles are required,
drawings shall indicate relative position to wall or adjacent vertical surface.
D.
For all submittals under paragraphs A through C above, manufacturer shall provide submittals
with fixture installation instruction sheets.
E.
For all submittals under paragraphs A through C above, manufacturer shall provide submittals
within two weeks of receipt of order. All submittals shall have project name and fixture type
clearly shown.
F.
Fixture cuts and shop drawings shall be submitted in quantities and format as described in the
general conditions section the specification.
G.
The Architect shall make the final determination as to whether or not the submittal contains
sufficient information and reserves the right to request a shop drawing if the fixture cut is
insufficient.
H.
MOCK-UPS
1.
2.
3.
It shall be the responsibility of the Contractor to provide a mock-up of the lighting
fixture or lighting systems as indicated in the fixture description. The mock-up shall be
erected within a time period and in a location that is acceptable to the Architect.
The mock-up installation shall closely conform to the conditions of the actual installation
as to: height, distance from ceiling, number and type of lamps, material, color and etc.
The Contractor shall submit a written description of each proposed mock-up with
drawings in order to obtain the Architect's approval prior to commencement of each
mock-up.
The purpose of the mock-up will be to study the general appearance and performance of
the intended lighting systems. At that time, certain minimal test variations may be
requested as to lamp location, lamp type, reflector shape, color and etc. Final
modifications, if any, shall be considered a part of these Specifications and shall be
accomplished with no additional cost to the Owner.
ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS
Copyright 2011 Gensler
26 51 00 - 3
December 12, 2013
Bid & Permit
Gensler
01.9462.002
I.
SAMPLES
1.
2.
3.
4.
1.9
Transbay Marketing Center
50 Fremont Street, 21st floor
San Francisco, CA
It shall be the responsibility of the Contractor to provide a sample(s) fixture as indicated
in Section 26 06 51, Lighting Fixture Schedule. When samples are called for the
manufacturer shall provide two working samples complete with lamp, ballast (rated for
120 Volt operation) and 6’ pig-tail with 3-prong Edison plug.
The sample(s) shall be shipped to a location that is determined by the Architect.
Shipping and return shipping costs shall be provided as part of the contract.
The purpose of the sample is to review manufacturing techniques, detailing, lamping and
scale. Sample fixtures must be approved prior to fabrication of fixtures for the project.
Minor modifications, if any, shall be considered part of these Specifications and shall be
accomplished with no additional cost to the Owner.
Sample fixtures may not be used on the project.
EXTRA STOCK
A.
Furnish to the Owner and store at the site where directed, extra stock of each type of lighting
fixture type and lamp type installed in the Project in quantities as required by Owner, packaged
in manufacturer’s unopened cartoons and identified as to contents by fixture type.
B.
Furnish items above with appropriate quantity of each exposed trim, fastener, bracket and other
items as required for a complete installation.
1.10
WARRANTIES
A.
All fixtures and workmanship shall be guaranteed free of defects and fully operational for a
minimum of one year after the acceptance of the project by the Owner. Any fixtures or
workmanship found to be defective during the warranty period will be either fixed or replaced
by the Contractor at no cost to the Owner.
B.
Ballasts for fluorescent fixtures shall be covered by a five year warranty against defects in
workmanship or material. Warranty shall include in-warranty service program providing for
payment of authorized labor charges incurred in replacement of inoperative, in- warranty
ballasts.
PART 2 - PRODUCTS
2.1
GENERAL MATERIAL REQUIREMENTS
A.
Ferrous mounting hardware and accessories shall be finished using either a galvanic or
phosphate primer/baked paint process to prevent corrosion and discoloration of adjacent
materials.
B.
For weatherproof and vaportight installation, painted finishes of fixtures and accessories shall
be weatherproof enamel using proper primers or hot dipped galvanized and bonderized epoxy,
in accordance with manufacturer’s requirements. Unless otherwise specified all painted
surfaces shall have a life expectancy of not less than twenty years.
1.
2.
Hangers shall be conduit with chemically resistant, weatherproof, baked enamel finish.
Where dissimilar metal parts come in contact with each other, apply to both surfaces a
coating material to prevent corrosion.
ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS
Copyright 2011 Gensler
26 51 00 - 4
Gensler
01.9462.002
3.
December 12, 2013
Bid & Permit
Transbay Marketing Center
50 Fremont Street, 21st floor
San Francisco, CA
Colors shall be as specified in the Section 26 06 51, Lighting Fixture Schedule section of
this specification.
C.
Fasteners shall be manufactured of non-magnetic stainless steel or anodized aluminum, except
in indoor applications where galvanized steel shall be acceptable.
D.
Fixtures shall be free of light leaks and shall be designed to provide sufficient ventilation of
lamps and ballasts including vent holes where required.
E.
All sheet metal work shall be free from tool marks and dents and shall have accurate angles
bent as sharp as compatible with the gauges of the required metal. All intersections and joints
shall be formed true and of adequate strength and structural rigidity to prevent any distortion
after assembly. All sheet metal shall be free of light leaks. All edges shall be finished so there
are no sharp edges exposed. All miters shall be in accurate alignment with abutting
intersecting members. Piecing of plates in individual runs in single planes and the use of
spliced pieces or filler material to cover defective workmanship shall not be acceptable. Sheet
metal work shall be properly fabricated so that planes will not deform (i.e. become concave or
convex, due to normal expected ambient and operating conditions).
F.
Lampholders shall hold lamps securely against normal vibrations and maintenance handling.
G.
Wiring channels and lampholder mountings shall be rigid and accurately made.
H.
Reflector Cones:
1.
2.
3.
4.
Provide 45° lamp and lamp image cut-off unless otherwise specified. In fixtures where
upper reflector is separate from cone, cut-off shall be 45° unless otherwise specified.
Plastic materials shall not be used for reflector cones or aperture plates.
Fixtures in which reflector cones are riveted or welded to housing or where removal of
cone requires pressure to be applied to finished surface of reflector shall not be
acceptable.
Cone flange shall be formed as an integral part of the cone and shall have identical color
and finish as the cone, except as shown. The flange major surface shall be perpendicular
to the cone axis. The width of the flange shall adequately cover the ceiling opening
without light leaks. No fixture parts (housing, mounting frame, etc.) shall be visible
between the ceiling surface and the edge of the cone flange. The same requirement shall
be applicable to fixtures where main reflector extends down to the bottom edge of the
fixture without a separate cone. In such case, the flange shall be formed as an integral
part of the main reflector.
5.
Reflector cones shall be manufactured of uniform gauge, not less than 0.032" thick, high
purity aluminum Alcoa 3002 alloy free of spin marks or other defects or blemishes
caused during manufacturing.
6.
The finish of the inner surface of the reflector shall be highly specular as produced under
the Alzak process. The reflector shall have an anodic coating of not less than four mils
thick. The reflector inner surface shall be free of water spotting and shall maintain a
reflectivity ratio of not less than 85% on clear specular finish. The reflector shall have a
low iridescence finish free from multiple colors seen from normal viewing angles.
Colors shall be derived from dyes supplied by Sandoz Chemical Company or approved
equal.
The reflecting surface of the cone shall be tested for proper sealing. Test per ASTM
B136-63T.
7.
ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS
Copyright 2011 Gensler
26 51 00 - 5
December 12, 2013
Bid & Permit
Gensler
01.9462.002
I.
8.
Fixtures with Alzak reflector cones, unless otherwise specified, must be furnished by the
same manufacturer.
9.
Reflector cone retention devices shall not deform cone in any manner whatsoever.
10.
Submit a certificate of compliance with Alzak finish requirements with all requests for
approval.
Lenses:
1.
Fresnel:
a.
b.
c.
d.
2.
3.
Lens shall have uniform brightness throughout the entire visible area at angles
from 45° to 90° from vertical, without bright spots or striations.
Lens shall have opaque risers; color shall be as specified in Section 26 06 51,
Lighting Fixture Schedule.
Finish of visible regress surface of door shall be matte baked enamel paint, special
color as selected by Architect.
All fixtures with fresnel lenses, unless otherwise specified, must be furnished by
the same manufacturer.
Glass:
a.
b.
Flat glass lenses shall be heat tempered borosilicate glass unless otherwise noted.
Glass finishes, i.e. sandblasting, etching, polishing shall be performed as described
in the fixture description.
Acrylic:
a.
b.
c.
J.
Transbay Marketing Center
50 Fremont Street, 21st floor
San Francisco, CA
Lenses shall be of injection molded crystal clear material 100% virgin acrylic
(except as shown). For lenses with male pattern of pyramids or cones, specified
minimum thickness refers to distance from flat surface to base of pyramids
(cones), or thickness of undisturbed material. For lenses with female pattern,
specified minimum thickness refers to overall thickness of material.
Lenses shall fully eliminate lamp images when viewed from all directions within
the 45° to 90° angle from vertical when the ratio of lamp spacing to the distance
from lamp underside to top of lens does not exceed 1.50. Within the viewing angle
from 0° to 45° the ratio of maximum brightness (under a lamp) to minimum
brightness (between lamps) shall not exceed 3 to 1.
Finishes, i.e. sandblasting, etching, polishing shall be performed as described in
the fixture description.
Louvers:
1.
Parabolic:
a.
b.
c.
Louvers shall be continuously bound in channel formed frame, finish and color as
specified or as selected.
Louver shall provide a minimum visual cut-off to the lamp of 45°.
The finish of the inner surface of the reflector shall be highly specular as produced
under the Alzak process. The reflector shall have an anodic coating of not less
ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS
Copyright 2011 Gensler
26 51 00 - 6
December 12, 2013
Bid & Permit
Gensler
01.9462.002
2.
Transbay Marketing Center
50 Fremont Street, 21st floor
San Francisco, CA
than four mils thick. The reflector inner surface shall be free of water spotting and
shall maintain a reflectivity ratio of not less than 85% on clear specular finish. The
reflector shall have a low iridescence finish free from multiple colors seen from
normal viewing angles.
Flat Blade:
a.
b.
c.
Provide flat blade louvers within formed frame, finish and color as specified.
Louvers to provide minimum of 45° degree cut-off from lamp image.
Blade thickness to minimum .125” flat steel.
K.
In adjustable fixtures, aiming and positive locking devices shall be provided.
L.
Fixtures with an adjustable lamp and using a lamp with an asymmetrical light pattern shall
have an aiming stop which can be permanently set so that the lamp shall remain correctly
positioned after service or relamping.
M.
Fluorescent Fixtures:
1. Hot Cathode:
a.
Housing:
1)
2)
3)
No. 22 minimum gauge steel, bonderized or equal rust protected, or No. 16
gauge aluminum rigid construction, suitable for continuous row mounting
where indicated.
Finish: Baked enamel paint finish unless otherwise specified, color as
specified or as selected.
Exterior Fixture Finishes:
a)
b)
b.
c.
Reflector: Minimum 85% reflectance.
Lightshields:
1)
2)
d.
Frames: Provide extruded aluminum frames with mitered corners filled and
ground smooth. Provided with concealed hinges and invisible latching.
No cross bars shall be permitted over lightshields.
Lampholders:
1)
e.
Unless otherwise specified, all painted surfaces shall have an outdoor
life expectancy of not less than 20 years. Surfaces shall be prepared,
primed, and material applied in accordance with the manufacturer's
requirements.
Color: Colors shall be as specified under Section 26 06 51, Lighting
Fixture Schedule.
Lampholders shall be UL listed, and meet IEC-60400, “International
Standard: Lampholders for tubular fluorescent lamps and startholders”.
For rapid start lamps on single ballasts, provide one (1) grounding lampholder per
lamp. Lampholders operating with open circuit voltage in excess of 300 volts shall
ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS
Copyright 2011 Gensler
26 51 00 - 7
December 12, 2013
Bid & Permit
Gensler
01.9462.002
Transbay Marketing Center
50 Fremont Street, 21st floor
San Francisco, CA
be safety type and shall open supply circuit when lamp is removed from
lampholder.
1)
2)
f.
g.
Mount lamps used in rapid start circuits 430mA and below: within 1/2" of
grounded metal as long as the lamp.
800mA and 1500mA lamps: mount within 1" of grounded metal as long as
the lamp.
Fluorescent fixtures shall conform to NEMA Standards, including references to
fixture dimensions and temperature ratings.
Ballasts shall be electronic high power factor (greater than 90%), ballast factor
(greater than 87%) and approved by UL (UL 935 listed). Ballasts shall be certified
for voltage and number of lamps specified and equipped with internal thermal
protectors unless otherwise specified.
1)
2)
3)
4)
5)
Ballasts shall have a Crest Factor of less than one and seven tenths.
Ballasts for indoor applications shall be "Class P".
Provide multi-lamp ballasts where possible including continuous rows of
one-lamp fixtures, and one-lamp ballasts only where the fixture layout does
not permit the use of multi-lamp ballasts.
Ballast shall be a dedicated ballast to operate a specific lamp, i.e., T8
ballasts specifically for a T8 lamp.
All ballasts shall operate at the voltage as described in Section 26 06 51,
Lighting Fixture Schedule and confirmed on electrical drawings. Ballasts
shall operate lamps properly through the following supply voltage ranges:
a)
b)
6)
7)
8)
9)
10)
11)
12)
Ballast shall tolerate sustained open circuit and short circuit output
conditions without damage.
Frequency shall be 20 Khz or greater except as noted without any discernible
flicker (<3% flicker index).
Ballast shall have input current total harmonic distortion not to exceed 10%
of the fundamental harmonic (60 Hz).
Ballast shall not contain PCB materials.
Ballast shall provide transient immunity as recommended by ANSI C62.411991 location Category A2.
Ballast shall be encapsulated to ensure maximum thermal and structural
integrity.
Ballast minimum sound ratings:
a)
b)
c)
d)
13)
14)
Rated voltage +/- 10%
Universal voltage of 108 to 305V on 50 or 60Hz supply
265 mA: Class 'A'
430 mA: Class 'A'
800 mA: Class 'B'
1500 mA: Class 'C'
Ballasts for T5, T5HO, and CFL lamps shall incorporate auto resetting lamp
shutdown circuitry for end of lamp life protection thereby allowing for relamping without the need to cycle power.
Program Rapid start ballasts shall be used when the lamps are to be
frequently turned on/off (with cycles of less than 3 hours). Otherwise ballast
ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS
Copyright 2011 Gensler
26 51 00 - 8
December 12, 2013
Bid & Permit
Gensler
01.9462.002
15)
16)
17)
Transbay Marketing Center
50 Fremont Street, 21st floor
San Francisco, CA
shall provide instant starting sequence consistent with ANSI standard
C82.11-1993.
Ballast shall be manufactured in an ISO 9002 certified facility.
Manufacturer shall have minimum 15 years of manufacturing experience.
Ballast, unless specified otherwise, shall be same manufacturer and model in
each fixture of the same type. Acceptable ballast manufacturers unless
otherwise noted are:
a)
b)
c)
d)
h.
2.
Advance
Universal Lighting Technologies
Osram/Sylvania
Lutron
Lighting fixtures recessed in a hung ceiling where the space above the hung ceiling
is used as a plenum chamber for either supply or return air for the air conditioning
system shall be designed, manufactured and wired to conform to NEC Article
300-22.
When specified, fluorescent luminaires shall have radio frequency interference (RFI) or
electromagnetic interference filters. Filters shall either be integral or external to the
ballast, but must be integral to the luminaire assembly with one filter per ballast and shall
suppress electromagnetic interference in the AM radio band from 500 to 1700 kHz.
Filters shall also be in the circuit serving the lighting fixture.
O. Solid State Lighting / Light Emitting Diode (LED) Lamps and Luminaires:
1.
General:
a.
b.
c.
d.
e.
f.
Luminaire manufacturer shall have a minimum of five (5) years experience in the
manufacture and design of LED products and systems and no less than one
hundred (100) North American installations.
Unless otherwise specified, all LED luminaires and power/data supplies shall be
provided by a single manufacturer to ensure compatibility.
All components, peripheral devices and control software are to be provided by and
shall be the responsibility of a single entity. All components shall perform
successfully as a complete system and shall operate as described in Lighting
Designer’s Control Narrative documents or Section 26 06 51, Lighting Fixture
Schedule.
Provide submittals as described in Part 1 above.
Include all components necessary for a complete installation. Provide all power
supplies, synchronizers, data cables, and data terminators for a complete working
system.
All LED sources used in the LED luminaire shall be of proven quality from
established and reputable LED manufacturers and shall have been fabricated after
2007. Acceptable LED lamp manufacturers unless otherwise noted are:
1)
2)
3)
4)
5)
Cree, Inc.
Philips Lighting
Nichia Corporation
Norlux
Opto Technology, Inc.
ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS
Copyright 2011 Gensler
26 51 00 - 9
December 12, 2013
Bid & Permit
Gensler
01.9462.002
6)
2.
Osram Optronic Semiconductors
Replacement and Spares:
a.
Manufacturer shall provide written guarantee of the following:
1)
2)
3)
b.
2)
c.
Manufacturer will keep record of original bin for each LED module and have
replacement modules from the same bin available for three (3) years after
date of installation.
Manufacturer will keep an inventory of replacement parts (source assembly,
power and control components).
Manufacturer’s LED system will not become obsolete for ten (10) years:
Manufacturer will provide exact replacement parts, or provide upgraded
parts that are designed to fit into the original luminaire and provide
equivalent distribution and lumen output to the original, without any
negative consequences.
All parts of system shall replaceable in field. Manufacturer shall provide written
guarantee of the following:
1)
3.
Transbay Marketing Center
50 Fremont Street, 21st floor
San Francisco, CA
Manufacturer has in place a written recycling and re-use program, and will
accept returned product and/or components for recycling or re-use.
Manufacturer will properly dispose of non-recyclable components that are
deemed harmful to the environment.
System shall carry a full warranty for five (5) years. Manufacturer shall be
responsible for cost of labor not to exceed $50 per individual part, and cost of
shipping, to replace any component of the system that fails within 2 years of
installation.
Products and Components – Performance
a.
b.
c.
d.
e.
f.
g.
h.
LED luminaires and components shall be UL listed or UL classified.
LED luminaires and components shall be CE certified.
All LED luminaires shall be subjected to the following JEDEC Reliability Tests
for Lead-free Semiconductors: HTOL, RTOL, LTOL, PTMCL, TMSK,
Mechanical Shock, Variable Vibration Frequency, SHR, Autoclave.
To ensure luminaire quality, luminaire shall have been tested under accelerated life
test conditions including an operating temperature span of 360 degrees F, and
cyclic loading up to 60G.
All products included in system shall use Mil-Std 810F, Random Vibration 7.698g
as a minimum standard. In installations subject to vibration, luminaire shall be
installed with vibration isolation hardware to sufficiently dampen vibrations.
All LED components shall be mercury and lead-free.
All manufacturing processes and materials shall conform to the requirements of the
European Union's Restriction on the Use of Hazardous Substances in Electrical
and Electronics Equipment (RoHS) Directive, 2002/95/EC.
LEDs shall comply with ANSI/NEMA/ANSLG C78.377-2008 – Specifications for
the Chromaticity of Solid State Lighting Products. Color shall remain stable
throughout the life of the lamp. Color shall match approved sample.
ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS
Copyright 2011 Gensler
26 51 00 - 10
December 12, 2013
Bid & Permit
Gensler
01.9462.002
i.
j.
k.
l.
m.
n.
o.
p.
q.
r.
s.
t.
u.
v.
Transbay Marketing Center
50 Fremont Street, 21st floor
San Francisco, CA
LEDs shall comply with IESNA LM-80 – Standards for Lumen Maintenance of
LED Lighting Products
White LEDs shall have a rated source life of 50,000 hours under normal operating
conditions. RGB LEDs shall have a rated source life of 100,000 hours. LED
“rated source life” is defined as the time when a minimum of 70% of initial lumen
output remains.
Luminaire assembly shall include a method of dissipating heat so as to not degrade
life of source, electronic equipment, or lenses. LED luminaire housing shall be
designed to transfer heat from the LED board to the outside environment.
Luminaire housing shall have no negative impact on life of components.
Manufacturer shall supply in writing a range of permissible operating temperatures
in which system will perform optimally.
High power LED luminaires shall be thermally protected using one or more of the
following thermal management techniques: metal core board, gap pad, and/or
internal monitoring firmware
LEDs shall be adequately protected from moisture or dust in interior applications.
For wet and damp use, LED-based luminaires itself shall be sealed, rated, and
tested for appropriate environmental conditions, not accomplished by using an
additional housing or enclosure. Such protection shall have no negative impact on
rated life of source or components, or if so, such reductions shall be explicitly
brought to the attention of the designer.
All hardwired connections to LED luminaires shall be reverse polarity protected
and provide high voltage protection in the event connections are reversed or
shorted during the installation process.
The LED luminaire shall be operated at constant and carefully regulated current
levels. LEDs shall not be overdriven beyond their specified nominal voltage and
current.
Manufacturer shall be able to provide supporting documentation of the product
meeting third party regulatory compliance.
Manufacturer shall ensure that products undergo and successfully meet appropriate
design and manufacturability testing including Design FMEA, Process FMEA,
Environmental Engineering Considerations and Laboratory Tests, IEC standards
and UL/CE testing.
All LED luminaires (100% of each lot) shall undergo a minimum twenty-four (24)
hour burn-in during manufacturing, prior to shipping.
Manufacturer shall provide Luminaire Efficacy (lm/W), total luminous flux
(lumens), luminous intensity (candelas) chromaticity coordinates, CCT and CRI.
optical performance, polar diagrams, and relevant luminance and illuminance
photometric data. Provide data in IES file format in accordance with IES LM-792008, based on test results from an independent Nationally Recognized Testing
Laboratory.
Power / data supply shall have the following:
1)
2)
3)
4)
Supply outputs shall have current limiting protection.
Supply shall provide miswiring protection.
Supply shall have power factor correction.
Supply shall provide connections that are conduit-ready or clamp-style
connections in the case of low-voltage wiring.
ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS
Copyright 2011 Gensler
26 51 00 - 11
December 12, 2013
Bid & Permit
Gensler
01.9462.002
5)
6)
4.
LED Control and Communication – Performance
a.
b.
c.
d.
e.
f.
P.
Transbay Marketing Center
50 Fremont Street, 21st floor
San Francisco, CA
Supply shall come with a housing that meets a minimum IP20 rating for dry
location installation unless located in a damp or wet location.
Supply shall be UL listed for Class 1 or Class 2 wiring
LED luminaires shall be network controllable via digital control.
The LED system shall use integral and differential non-linear control.
Constant data transmission rates shall be employed, resulting in the output being
independent of distance of cable between power supply and light source within the
specified length.
LED system shall have a selectable means of external control via a data network.
Each LED luminaire and/or node shall have the capability to be set to a unique and
individual address. Address shall be selectable through on board switches or by an
external hardware or software method.
The LED system shall be scalable, with every LED luminaire/address in the system
capable of being controlled by a single, centralized controller.
Wiring:
1.
Voltage Rating
a.
b.
2.
For voltages up to 120 volts fixture wiring shall be rated for 300 volts minimum.
For voltages above 120 volts fixture wiring shall be rated for 600 volts minimum.
Temperature Rating - Internal to Fixture
a.
b.
All wiring shall be code-approved for fixture wiring, and shall comply with the
following temperature ratings unless fixture design or local codes require higher
temperature wire.
Fluorescent
1) minimum rating between lampholder(s) and internal ballast.
2) minimum between ballast and separate junction box, or connection within
integral wireway.
3.
Temperature Rating - External to Fixture
a.
b.
4.
All flexible cord wiring between fixture components or to electrical receptacle and
not in wireways shall have a minimum temperature rating of 105°C.
Cord type shall be suitable for application and shall be fitted with proper strain
relief and watertight entries where required by application.
Splices
a.
b.
Splices internal to fixture shall be made within separate splice compartments and
shall utilize nylon insulated crimped connections or insulated quick disconnects.
Splices to branch circuit wiring in separate junction boxes shall utilize flame
retardant thermoplastic caps with fully seated helical metal spring and threaded
entry.
ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS
Copyright 2011 Gensler
26 51 00 - 12
Gensler
01.9462.002
5.
6.
7.
Q.
December 12, 2013
Bid & Permit
Transbay Marketing Center
50 Fremont Street, 21st floor
San Francisco, CA
No internal wiring shall be visible at normal viewing angles, i.e., above 45° from
vertical. Use additional wire clamps if necessary. Anticipate increased visibility if
fixtures are mounted on or recessed within a sloping surface.
Any fixture fed from more than one panel, i.e., for normal and night or emergency
operation, shall have separate neutrals to each panel.
Furnish code-approved wiring in ceiling cavities forming air plenums.
Lamps:
1.
Hot cathode fluorescent lamps:
a.
b.
Shall be 3000° Kelvin, with 85 CRI or greater except as shown. Refer to Section
26 06 51, Lighting Fixture Schedule for details.
All lamps, except as specified, shall be of the same manufacturer:
1)
2)
3)
General Electric
North American Philips
Osram/Sylvania
PART 3 – EXECUTION
3.1
SHIPPING AND STORAGE
A.
All fixtures received at the site shall be stored in clean and dry space until fixtures are
installed.
B.
Manufacturer shall clearly mark each box with fixture designation prior to shipping.
C.
Reflector cones, baffles, louvers, aperture plates, and decorative elements of fixtures shall be
packed by the manufacturer separate from the housing (body, stem, etc.) of the fixture.
3.2
LOCATION
A.
Locations of fixtures are shown diagrammatically. Verify exact location and spacing with
Reflected Ceiling Plans and other reference data before ordering of fixtures and during
installation.
B.
Notify Architect about field conditions at variance with Contract Documents before
commencing installation.
C.
Coordinate space conditions with other trades before ordering of fixtures.
D.
Pendant mount, as approved, surface type fixtures where required to meet space conditions.
E.
Coordinate length of continuous-run fluorescent fixtures with adjacent walls, partitions, coffers
and other architectural elements as required.
1.
Continuous runs shall be defined as the optimal combination of 3’ and 4’ lamp length as
necessary to complete runs with no more than 6” of free space at either end of the run as
provided by the contractor.
ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS
Copyright 2011 Gensler
26 51 00 - 13
December 12, 2013
Bid & Permit
Gensler
01.9462.002
3.3
Transbay Marketing Center
50 Fremont Street, 21st floor
San Francisco, CA
INSTALLATION
A.
Provide accessories as required for ceiling construction type indicated on Finish Schedule.
Fixture catalog numbers do not necessarily denote specific mounting accessories for type of
ceiling in which a fixture may be installed.
B.
Provide adequate and sturdy support for each lighting fixture. Contractor shall be responsible
for verifying weight and mounting method of all fixtures and furnish and install suitable
supports. Fixture mounting assemblies shall comply with all local seismic codes and
regulations.
C.
Install rows of fixtures accurately on straight lines unless otherwise indicated on drawings.
Coordinate with mechanical work.
D.
Install fixtures with vent holes free of air blocking obstacles.
E.
Where plaster ceilings occur, furnish plaster frames for setting under other applicable sections.
Direct the setting and be responsible for correct location; make sure the bottom of frame is
flush with finished ceiling, forming screed edge for finished plaster.
1.
Fixtures shall be supported by plaster frames utilizing yokes or leveling lugs.
a.
b.
2.
3.
Fixtures and support elements shall not be mounted to or in contact with ducts or
pipes.
Yoke shall have channel cross section of sufficient gauge, and shall support a
fixture by means of not fewer than two (2) bolts each.
If air diffusers are located in common continuous rows with lighting fixtures in plaster
ceilings, furnish plaster frames of proper length to accommodate diffusers.
Lighting fixtures recessed in ceilings which have a fire resistive rating of one hour or
more shall be enclosed in a box which has a fire resistive rating equal to that of the
ceiling.
F.
Contractor shall be responsible for adjusting aperture rings on all ceiling recessed fixtures to
accommodate various ceiling material thickness. Contractor shall responsible for coordinating
the cut-out size in ceiling to ensure aperture covers cut-out entirely. The bottom of aperture
rings shall be flush with finished ceiling or not more that 1/16" above. Under no circumstances
will the aperture ring extend below the finished ceiling surface.
G.
For fixtures with variable position lampholder assemblies Contractor shall confirm prior to
installation proper lampholder (socket) position in field, and shall adjust, if necessary, after
coordination with manufacturer.
H.
Surface Mounted Fixtures: Support surface mounted fixtures from structural members other
than ceiling tees.
I.
Pendant Mounted Fixtures:
1.
2.
Pendant mounted fixtures shall be supported from structural framework of ceiling or
from inserts cast into slab.
All pendants shall have swivel aligners located at the top ends; pendants shall be 1/2"
rigid steel conduit unless specifically indicated otherwise on drawings or in
specifications.
ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS
Copyright 2011 Gensler
26 51 00 - 14
Gensler
01.9462.002
3.
December 12, 2013
Bid & Permit
Transbay Marketing Center
50 Fremont Street, 21st floor
San Francisco, CA
All fluorescent pendant and surface mounted fixtures shall be supported with two (2)
supports per four foot section or three (3) per eight foot section unless otherwise
recommended by manufacturer.
J.
Bracket Mounted Fixtures: For each bracket fixture, provide flanged metal stem attached to
outlet box, with threaded end suitable for supporting the fixture rigidly in design position.
Flanged part of fixture stud shall be of broad base type, secured to outlet box at not fewer than
three (3) points.
K.
Top Relamping Fixtures: Top relamping fixtures shall have the necessary top-relamping
screws loosened and moderately tightened, prior to installation, to assure ease of operation
when relamping is required.
L.
Fluorescent Fixtures: Replace noisy ballasts as directed, at no cost to the Owner.
M.
Mask the trims and bottoms of all lighting fixtures if necessary to protect the fixture during
construction.
N.
At the completion of construction clean the bottoms, the trim, the reflecting surfaces, lenses,
baffles, louvers and reflector cones of all lighting fixtures so as to render them free of any
material, substance or film foreign to the fixture. If the luminaires are deemed dirty by the
Architect at the completion of the project, the Contractor shall clean them at no additional cost
to the Owner. Luminaire components whose finishes are damaged shall be replaced at no cost
to the Owner.
O.
Ascertain and ensure that all lamps installed are exactly as specified for each fixture type.
P.
Replace all burned-out or inoperative lamps, and inoperative ballasts in all fluorescent fixtures
before the building is accepted by the Owner so that all lighting fixtures will be in first-class
operating condition.
Q.
Provide labor and materials for final aiming of all adjustable fixtures under the Architect's
supervision. Aiming shall take place immediately before building is turned over to Owner,
after regular working hours where required.
END OF SECTION 26 51 00
ARCHITECTURAL LIGHTING FIXTURES, LAMPS & BALLASTS
Copyright 2011 Gensler
26 51 00 - 15