PDF, 2,3 MB

advertisement
Main
Switches
catalogue
15
Main switches & isolators
MCCBs, load break switches
& isolating switches
This section includes moulded case circuit breakers and load break switches which are utilised for the
switching, protection and distribution of low voltage installations.
MCCBs
characteristics
C.4
MCCBs
& accessories selection guide
C.6
MCCBs x160
C.10
MCCBs x250
C.12
MCCBs h250
C.14
MCCBs h630
C.16
MCCBs h1000
C.19
MCCBs h1600
C.21
Load break switches
C.23
Load break switches characteristics
C.25
Earth leakage relays and toroids
C.26
Ph 1300 850 253 | customerservice@hagerelectro.com.au | Fx 1300 424 372
Main Switches
& Isolators
C.2
Expert tips -
MCCBs
16A to 1600A
Easy mounting and safety
The new
range of MCCBs provide safe and easy solutions for low voltage electrical circuits
protection. The state of the art circuit breakers offer both designers and installers a wide range of
range perfectly meets
features and benefits. With special attention being given to ergonomics, the
reliability requirements for main incoming devices in commercial premises: strength, reliability, efficient
protection and standards compliant selection.
The advantages for you:
Technical data:
• Easy to install
• Comply with IEC 60947-2
• Quick, easy and safe mounting of accessories
• 6 frame sizes: x160, x250, h250, h630, h1000, h1600
• Wide range of rated current ratings and breaking capacities
• Breaking capacity: 25, 40, 50, 70kA
• Range of termination accessories
• Thermal magnetic and electronic trip units
• DIN rail profile up to 250A
• 1 pole to 4 poles
• Current limiting type
• Complete range of accessories
• International certification and approvals
C.2
Expert
tips
1
2
3
4
Design by Hager
In harmony with Hager enclosures
and modular products.
Electronic trip unit (LSI)
Provides total selectivity along
with generator protection.
Breaking capacity
25 to 70kA, Icu 415V AC, covers
all applications.
Easy auxiliary mounting
Easy opening of secondary cover,
clip-in type auxiliaries.
5
6
7
8
Visibility of auxiliaries
A clear window indicates the
type of auxiliary mounted in the
breaker.
Integrated padlocking
Provides a convenient
solution for maintenance.
Full accessory range
Rotary handles, padlocks, motor
operators, terminal covers...
Flexible connection
Collar terminals, front and rear
connections, straight connections,
spreaders...
C.3
MCCBs
- characteristics
Product
Reference
Number of poles [No.]
Electrical characteristics
Rated current In [A]
Current rated range
[A]
Rated service voltage, (AC)
Ue
[V]
Frequencyf [Hz]
Rated insulation voltage
Ui
[V]
Rated impulse withstand voltage
Uimp [kV]
Rated ultimate short-circuit breaking capacity, (Icu)
(AC) 50-60 Hz 220/230 V
Icu
[kA]
x160 TM MCCB
HHA
3-4
35
85
85
Rated
HNA
160
16-160
220-440
50/60
690
8
x250 TM MCCB
HNB
3-4
250
100-250
220-440
50/60
800
8
(AC) 50-60 Hz 380/415 V
Icu
(AC) 50-60 Hz 480/500/525 V
Icu
(AC) 50-60 Hz 660/690 V
Icu
(DC) 250 V - 2 poles in series
Icu
service short-circuit breaking capacity, (Ics)
(AC) 50-60 Hz 220/230 V
Ics
[kA]
[kA]
[kA]
[kA]
25
10
40
10
40
9
[kA]
25
40
40
(AC) 50-60 Hz 380/415 V
Ics
(AC) 50-60 Hz 480/500/525 V
Ics
(AC) 50-60 Hz 660/690 V
Ics
(DC) 250 V - 2 poles in series
Ics
Rated short-circuit making capacity
Icm
Rated short-time withstand current for 1s
Icw
Category of use (EN 60947-2)
Calibration temperature
Derating40°C
50°C
55°C
60°C
65°C
Suitability for isolation
Electric endurance in number of cycles
Mechanical endurance in number of operations
Operating temperature
Storage temperature
Power loss (at In for 3P)
Reference standard
Releases: switch
Releases: TM (thermomagnetic)
T fixed, M fixed
T adjustable, M fixed
T adjustable, M adjustable
Thermal adjustment value
Magnetic adjustment value
[kA]
[kA]
[kA]
[kA]
[kA]
[kA]
20
20
20
Releases: LSI (electronic)
Long delay
Short delay
-
5
A
50°C
100%
100%
94%
91%
88%
ok
10000
20000
-25 to +70°C
-35 to +70°C
60
IEC 60947-2
ok
ok
ok
0,63 to 0.8 to 1 x In
6-8-10-13 x In (200A)
5-7-9-11 In (250A)
-
Time delay
Terminations
Standard terminal type
Maximum terminal capacity
Terminal width
Terminal shields
Cage terminal
Extended connections
Rear connections
Dimensions
Height
mm
Width
3P mm
4Pmm
Depth
mm
Weight
3P
kg
4Pkg
-
-
cage
95 mm2
ok
integrated
ok
no
lugs
185 mm2 (cage)
25
ok
ok
ok
ok
130
75
100
68
0,715
0,95
165
105
140
68
1,3
1,6
C.4
[W]
mm
5
5
A
50°C
100%
100%
95%
93%
90%
ok
10000
20000
-25 to +70°C
-35 to +70°C
39
IEC 60947-2
ok
ok
ok
0,63 to 0.8 to 1 x In
-
h400 TM MCCB
HND
3-4
h630 LSI MCCB
HND
HED
3-4
h1000 LSI MCCB
HNE
HEE
3-4
h1600 LSI MCCB
HNF
HEF
3-4
250
40-125-250
220-690
50/60
800
8
400
250-400
220-690
50/60
800
8
630
250-630
220-690
50/60
800
8
1000
800-1000
220-690
50/60
800
8
1600
1250-1600
220-690
50/60
800
8
85
100
85
85
100
50
25
7,5
-
70
45
20
-
50
30
20
40
50
30
20
70
30
20
85
100
85
85
85
25
10
7,5
B
40°C
100%
95%
90%
80%
80%
ok
10000
30000
-25 to +70°C
-35 to +70°C
75
IEC 60947-2
-
70
45
15
-
50
30
15
40
A
50°C
100%
100%
95%
92%
89%
ok
4500
15000
-25 to +70°C
-35 to +70°C
75
IEC 60947-2
ok
ok
0,63 to 0.8 to 1 x In
6-8-10-12 x In
50
30
15
50
30
15
0,4 to 1 x Ir
2,5 to 10 x Ir
-
100
100
100
70
30
20
-
50
45
25
-
70
65
45
-
75
75
B (400A) - A (630A)
40°C
100%
100%
95%
90%
80%
ok
4500
15000
-25 to +70°C
-35 to +70°C
150
IEC 60947-2
-
85 (800A)
100 (800A)
75 (1000A)
75 (1000A)
50
50
30
30
20
20
B (800A) - A (1000A)
40°C
100%
100%
95%
90%
80%
ok
4500
15000
-25 to +70°C
-35 to +70°C
150
IEC 60947-2
-
50
45
25
B
40°C
100%
100%
95%
90%
80%
ok
4500
15000
-25 to +70°C
-35 to +70°C
170
IEC 60947-2
-
50
50
34
-
ok
0,4
2,5
2,5
0,1
ok
0,4 to 1 x In
2,5 to 10 x Ir
-
ok
0,4
2,5
2,5
0,1
0,1 - 0,2s
lugs
120 mm2 (cage)
25
ok
ok
ok
ok
lugs
240 mm2 (cage)
30
ok
ok
ok
ok
lugs
30
ok
integrated
ok
lugs
45
ok
integrated
ok
lugs
45
ok
integrated
ok
165
105
140
97
2,5
3,3
260
140
185
97
4,2
5,6
260
140
185
97
4,3
5,7
273/433
210
280
99,5
11
14,8
370/570
210
280
140
27
31
to 1 x Ir
to 10 x Ir (400A)
to 8 x Ir (630A)
- 0,2s
85 (800A)
75 (1000A)
50
30
20
-
to 1 x Ir
to 10 x Ir (800A)
to 8 x Ir (1000A)
- 0,2s
Main Switches
& Isolators
h250 LSI MCCB
HNC
HEC
3-4
0,1 - 0,2s
C.5
MCCBs
& accessory selection guide
MCCB’s
Terminal connectors
HHA125U
Frame
Trip Unit
Pole
3
X160
TM
4
3
x250
4
Frame
x160
x250
C.6
HNB160U
In (A)
25 kA
40 kA
25
40
63
80
100
125
160
25
40
63
80
100
125
160
160
200
250
160
200
250
HHA025U
HHA040U
HHA063U
HHA080U
HHA100U
HHA125U
HHA160U
HHA026U
HHA041U
HHA064U
HHA081U
HHA101U
HHA126U
HHA161U
-
HNA025U
HNA040U
HNA063U
HNA080U
HNA100U
HNA125U
HNA160U
HNA026U
HNA041U
HNA064U
HNA081U
HNA101U
HNA126U
HNA161U
HNB160U
HNB200U
HNB250U
HNB161U
HNB201U
HNB251U
HYB031H
HYA015H
Terminal connectors
Collar
Straight
Spreader
Rear
HYA005H
HYA013H
HYA014H
-
HYA006H
HYA013H
HYA015H
-
HYB001H
HYB010H
HYB011H
HYB031H
HYB002H
HYB010H
HYB012H
HYB032H
Shunt Trips
- SH
Under Voltage
- UV
Motor
Operator
Auxilliary Contact
(1C/O)
HXA004H
HXA014H
HXB040H
HXA021H
Operating
Voltage
Shunt Trips
- SH
Under Voltage
- UV
Motor
Operator
Auxilliary Contact (1C/O)
AUX, AX
Alarm, AL
(1NO + 1NC)
(1NO +1NC)
24V DC
48V DC
HXA001H
HXA002H
HXA011H
-
-
100 - 120V AC
200 - 240V AC
380 - 450V AC
24V DC
48V DC
100 - 120V AC
230 - 240V AC
200 - 240V AC
380 - 450V AC
HXA003H
HXA004H
HXA005H
HXA001H
HXA002H
HXA003H
HXA004H
HXA005H
HXA013H
HXA014H
HXA015H
HXA011H
HXA013H
HXA014H
HXA015H
HXB040H
HXB042H
-
HXA024H
HXA021H
HXA024H
HXA021H
HXA024H
Interlock
Phase
Barrier
DIN rail
adaptor
Rotary Handle
Padlock
HXB065H
HYA019H
HYA033H
HXA031H
HXA039H
Interlock
Phase
Barrier
DIN rail
adaptor
Rotary Handle
Direct
Extended
Padlock
HYA027H
HYB022H
Terminal covers
Collar
Straight
Spreader
Rear
HYA027H
HYA021H
HYA023H
-
-
HYA019H
HYA033H
HXA030H
HXA031H
HXA039H
HYA028H
HYA022H
HYA024H
-
-
HYA019H
HYA033H
HXA030H
HXA031H
HXA039H
HYB027H
HYB021H
HYB023H
HYB025H
HXB065H
HYB019H
-
HXB030H
HXB031H
HXA039H
HYB028H
HYB022H
HYB024H
HYB026H
HXB065H
HYB019H
-
HXB030H
HXB031H
HXA039H
C.7
Main Switches
& Isolators
Terminal covers
MCCBs
& accessory selection guide
MCCB’s
Terminal connectors
HEC250H
Frame
Trip Unit
Pole
3
h250
4
3
h630
LSI
4
3
h1000
4
3
h1600
4
Frame
h250
h630
C.8
HNE970H
In (A)
50 kA
70 kA
40
125
250
40
125
250
400
630
400
630
800
1000
800
1000
1250
1600
1250
1600
HNC040H
HNC125H
HNC250H
HNC041H
HNC126H
HNC251H
HND400H
HND630H
HND401H
HND631H
HNE800H
HNE970H
HNE801H
HNE971H
HNF980H
HNF990H
HNF981H
HNF991H
HEC040H
HEC125H
HEC250H
HEC041H
HEC126H
HEC251H
HED400H
HED630H
HED401H
HED631H
HEE800H
HEE970H
HEE801H
HEE971H
HEF980H
HEF990H
HEF981H
HEF991H
HYD015H
HYD033H
Terminal connectors
Collar
Straight
Spreader
Rear
HYC003H
HYC010H
HYC011H
HYC031H
HYC004H
HYC010H
HYC012H
HYC032H
HYD003H
HYD007H
HYD004H
HYD008H
HYD010H
HYD013H
HYD010H
HYD013H
HYD011H
HYD014H
HYD012H
HYD015H
-
-
-
-
-
-
HYD031H
HYD033H
HYD032H
HYD034H
HYE031H
HYE033H
HYE032H
HYE034H
-
-
-
-
-
-
-
-
Shunt Trips
- SH
Under Voltage
- UV
Motor
Operator
Auxilliary Contact
(1C/O)
HXC004H
HXC014H
HXD042H
HXC021H
Operating
Voltage
Shunt Trips SH
Under Voltage
- UV
Motor
Operator
Auxilliary Contact (1C/O)
AUX, AX
Alarm, AL
(1NO + 1NC)
(1NO +1NC)
24V DC
48V DC
100 - 120V AC
200 - 240V AC
380 - 450V AC
24V DC
48V DC
100 - 120V AC
200 - 240V AC
380 - 450V AC
HXC001H
HXC002H
HXC003H
HXC004H
HXC005H
HXC001H
HXC002H
HXC003H
HXC004H
HXC005H
HXC011H
HXC013H
HXC014H
HXC015H
HXC011H
HXC013H
HXC014H
HXC015H
HXC040H
HXC042H
HXD040H
HXD040H
HXD042H
HXD042H
-
HXC024H
HXC021H
HXC024H
HXC021H
HXA024H
Interlock
Interphase
Barrier
Rotary handles
Padlock
HXC065H
HYC019H
HXD030H
HXC039H
Interlock
Interphase
Barrier
Rotary handles
Direct
Extended
Padlock
HYD022H
HYD023H
Terminal covers
Collar
Straight
Spreader
Rear
HYC027H
HYC021H
-
HYC025H
HXC065H
HYC019H
HXC030H
HXC031H
HXC039H
HYC028H
HYC022H
-
HYC026H
HXC065H
HYC019H
HXC030H
HXC031H
HXC039H
HYD027H
HYD021H
HYD023H
HYD025H
HXD065H
HYD019H
HXD030H
HXD031H
HXD039H
HYD028H
HYD022H
HYD024H
HYD026H
HXD065H
HYD019H
HXD030H
HXD031H
HXD039H
-
HYE021H
-
HYE025H
HXE065H
-
HXE030H
HXE031H
HXD039H
-
HYE022H
-
HYE026H
HXE065H
-
HXE030H
HXE031H
HXD039H
-
-
-
-
-
HXF030H
HXF031H
HXF039H
-
-
-
-
-
HXF030H
HXF031H
HXF039H
Frame
h1000
h1600
Shunt Trips
- SH
Under Voltage
- UV
Motor
Operator
Auxilliary Contact
(1C/O)
HXC004H
HXE014H
HXF040H
HXC012H
Operating
Voltage
Shunt Trips SH
Under Voltage
- UV
Motor
Operator
Auxilliary Contact (1C/O)
AUX, AX
Alarm, AL
(1NO + 1NC)
(1NO +1NC)
24V DC
48V DC
100 - 120V AC
200 - 240V AC
380 - 450V AC
24V DC
48V DC
100 - 120V AC
200 - 240V AC
380 - 450V AC
HXC001H
HXC002H
HXC003H
HXC004H
HXC005H
HXC001H
HXC002H
HXC003H
HXC004H
HXC005H
HXE011H
HXE013H
HXE014H
HXE015H
HXE011H
HXE013H
HXE014H
HXE015H
HXE040H
HXE040H
HXE042H
HXE042H
HXF040H
HXF042H
-
HXC024H
HXC021H
HXC024H
HXC021H
HXC024H
C.9
Main Switches
& Isolators
Terminal covers
MCCBs
x160
Moulded case circuit
breakers x160
- Thermal magnetic trip
unit, 2 versions:
- Z version: fixed thermal
and fixed magnetic
- U version: adjustable thermal
and fixed magnetic
- 1P, 2P, 3P & 4P
- Mechanical test button,
sealable settings, integrated
padlocking handle Ø4mm.
Connection capacity:
-95mm2 rigid cables
-70mm2 flexible cables
- Comply with IEC60947-2.
Technical information:
- Visit our website at
www.hagerelectro.com.au
*Please check availability with your local Hager sales office at time of order
MCCBs x160 25kA
Description
- Breaking capacity
Ics: 20kA (400/415V AC)
- Fixed thermal 1 x In
- Fixed magnetic > 10 x In
HHA125U
- Adjustable thermal
0.63 - 0.8 - 1 x In
- Fixed magnetic > 10 x In
HHA161U
In
16A
20A
25A
32A
40A
50A
63A
80A
100A
125A
25A
40A
63A
80A
100A
125A
160A
Cat ref.
Cat ref.
Cat ref.
1P
3P
4P*
HHA014Z
HHA018Z
HHA023Z
HHA030Z
HHA038Z
HHA048Z
HHA061Z
HHA078Z
HHA098Z
HHA123Z
-
HHA025U
HHA040U
HHA063U
HHA080U
HHA100U
HHA125U
HHA160U
HHA026U
HHA041U
HHA064U
HHA081U
HHA101U
HHA126U
HHA161U
Cat ref.
Cat ref.
MCCBs x160 40kA
Description
- Breaking capacity
Ics: 20kA (400/415V AC)
- Adjustable thermal
0.63 - 0.8 - 1 x In
- Fixed magnetic > 10 x In
HNA125U
C.10
In
25A
40A
63A
80A
100A
125A
160A
3P
4P*
HNA025U
HNA040U
HNA063U
HNA080U
HNA100U
HNA125U
HNA160U
HNA026U
HNA041U
HNA064U
HNA081U
HNA101U
HNA126U
HNA161U
MCCBs
x160 - accessories
Coil connection
- Connection capacity: 0.75mm
flexible or rigid cables.
- Optional connection cables.
The cable capacity of the
terminals is 0.5 to 1.25mm2.
Shunt trip
- Remote tripping of MCCBs
or trip-free switches.
- Operating voltage:
0.7 to 1.1 x Un
Under voltage release
- Allows the tripping of MCCBs
when voltage level drops
between 35 and 70% of Un.
- Pick up voltage 0.85 x Un
Direct rotary handle
-Padlockable
- Equipped with front
cover and handle
- Fixing without any
additional screw.
Extended rotary handle
- IP 55
- Supplied complete with
shaft and handle.
Technical information:
- Visit our website at
www.hagerelectro.com.au
Accessories
HXA021H
Description
Characteristics
Cat ref.
Auxiliary contacts
AX
AL
1 changeover contact (ON/OFF)
250V AC / 3A
125V DC / 0.4A
1NO + 1NC
1 changeover alarm contact
250V AC / 3A
125V DC / 0.4A
1NO + 1NC
24V DC
48V DC
100 - 120V AC
200 - 240V AC
380 - 450V AC
24V DC
100 - 120V AC
200 - 240V AC
380 - 450V AC
HXA021H
HXA024H
Shunt trips
SH
Undervoltage releases
UV
HXA004H
HXA014H
HXA024H
HXA001H
HXA002H
HXA003H
HXA004H
HXA005H
HXA011H
HXA013H
HXA014H
HXA015H
Accessories
Description
HXA031H
HYA015H
Direct rotary handle
Padlockable
Extended rotary handle
Padlockable
Padlocking device
To mount on MCCB for handle
locking 3 padlocks
Collar terminals
Terminals for aluminium conductor
Extended connections
Straight connections
Spreader connections
Interphase barriers
Terminal covers
Din rail adaptor
Characteristics
Cat ref.
Cat ref.
3P
4P
Max Ø 6mm
HXA030H
HXA030H
Max Ø 8mm
200mm
Max Ø 8mm
HXA031H
HXA031H
HXA039H
HXA039H
Set of 3 or 4
HYA005H
HYA006H
Set of 4
Set of 3 or 4
Set of x 2
Height: 50mm
For extended straight connections
For extended spreader
connections
For collar terminal
HYA013H
HYA014H
HYA019H
HYA013H
HYA015H
HYA019H
HYA021H
HYA023H
HYA022H
HYA024H
HYA027H
HYA033H
HYA028H
HYA033H
HYA021H
C.11
Main Switches
& Isolators
Indication contacts
- 1 changeover switch (ON/OFF):
indicates the position of the
MCCB is “open” or “closed”.
- 1 changeover alarm contact:
indicates MCCB tripping.
MCCBs
x250
Moulded case circuit breakers
x250
- Adjustable thermal and
magnetic trip unit
- 3P and 4P
- Mechanical test button
- Lockable settings
- Integrated padlocking handle
Ø 4mm
- Complies with IEC60947-2.
Connection:
- Terminal area width 25mm
Connection capacity:
-185mm2 rigid cables
- Collar terminals optional
Technical information:
- Visit our website at
www.hagerelectro.com.au
*Please check availability with your local Hager sales office at time of order
MCCBs x250 40kA
Description
HNB160U
C.12
Breaking capacity
Icu: 40 kA (400/415V AC)
Ics: 20 kA
Adjustable thermal
0.63 - 0.8 - 1x In
Adjustable magnetic
6 - 8 - 10 - 13 x In (160/200A)
5 - 7 - 9 - 11 x In (250A)
4P neutral setting: 0 or 100%
In
160A
200A
250A
Cat ref.
Cat ref.
3P
4P*
HNB160U
HNB200U
HNB250U
HNB161U
HNB201U
HNB251U
MCCBs
x250 - accessories
Coil connection
- Connection capacity: 0.75mm2
flexible or rigid cables
- Optional connection cables.
The cable capacity of the
terminals is 0.5 to 1.25mm2.
Shunt trip
- Remote tripping of MCCBs or
trip-free switches. Operating
voltage: 0.7 to 1.1 x Un.
Under voltage release
- Allows the tripping of MCCBs
when voltage level drops
between 35 and 70% of Un.
- Pick up voltage 0.85 x Un.
Direct rotary handle
-Padlockable
- Equipped with front
cover and handle
- Fixing without any
additional screw.
Extended rotary handle
-IP55
- Supplied complete with
shaft and handle.
Technical information:
- Visit our website at
www.hagerelectro.com.au
Accessories
HXA021H
Description
Characteristics
Cat ref.
Auxiliary contacts
AX
AL
1 changeover contact
250V AC / 3A
125V DC / 0.4A
1NO + 1NC
1 changeover alarm contact
250V AC / 3A
125V DC / 0.4A
1NO + 1NC
24V DC
48V DC
100 - 120V AC
200 - 240V AC
380 - 450V AC
24V DC
100 - 120V AC
200 - 240V AC
380 - 450V AC
Max Ø 6mm
HXA021H
HXA024H
Shunt trips
SH
Undervoltage releases
UV
HXA004H
HXA014H
Direct rotary handles
Padlockable
Extended rotary handles
Padlockable
Padlocking device
To mount on MCCBs for handle
locking 3 padlocks
Motor operators
HXB040H
HXA024H
HXA001H
HXA002H
HXA003H
HXA004H
HXA005H
HXA011H
HXA013H
HXA014H
HXA015H
HXB030H
HXB031H
Max Ø 8mm
200mm
Max Ø 8mm
HXA039H
24V DC
230 - 240V AC
HXB040H
HXB042H
Accessories
Cat ref.
HYB022H
HYB024H
Characteristics
3P
4P
Interlocking
Collar terminals
Aluminium / copper conductors
150mm2 rigid cables
185mm2 flexible cables
Extended connections
For straight connections
Wire type
Set of 4 pieces
HXB065H
HYB001H
HXB065H
HYB002H
Set of 4 pieces
Set of 4 pieces
Set of 3 pieces
Set of 3
Height: 97mm
For extended straight connections
For extended spreader
connections
For rear connections
For collar terminals
HYB010H
HYB011H
HYB031H
HYB019H
HYB010H
HYB012H
HYB032H
HYB019H
HYB021H
HYB023H
HYB022H
HYB024H
HYB025H
HYB027H
HYB026H
HYB028H
For spreader connections
Rear connections
Interphase barriers
Terminal covers
HYB031H
Cat ref.
Description
C.13
Main Switches
& Isolators
Indication contacts
- 1 changeover switch
(ON/OFF): indicates the
position of the MCCB is
“open” or “closed”.
- 1 changeover alarm contact:
indicates MCCB tripping.
MCCBs
h250
Moulded case circuit
breakers h250
- 3P & 4P
- Mechanical test button,
sealable settings.
- Comply with IEC 60947-2.
Connection:
Terminal area width 25 mm
Electronic trip unit LSI:
- Long delay
(thermal equivalent)
adjustable: Ir = 0.4 to 1 x In
- Short delay
(magnetic equivalent)
adjustable: 2.5 to 10 x Ir
- Time delay: 0.1 - 0.2s
Technical information:
- Visit our website at
www.hagerelectro.com.au
*Please check availability with your local Hager sales office at time of order
MCCBs h250 50kA LSI
Description
- Breaking capacity
Icu: 50 kA (400/415V AC)
Ics: 25 kA
HNC250H
- Adjustable thermal
Ir = 0.4 to 1 x In
Characteristics
Cat ref.
Cat ref.
3P
4P*
40A
125A
250A
HNC040H
HNC125H
HNC250H
HNC041H
HNC126H
HNC251H
Characteristics
Cat ref.
Cat ref.
- Adjustable magnetic
2.5 to 10 x Ir
MCCBs h250 70kA LSI
Description
HEC250H
C.14
- Breaking capacity
Icu: 70 kA (400/415V AC)
Ics: 70 kA
- Adjustable thermal
Ir = 0.4 to 1 x In
- Adjustable magnetic
2.5 to 10 x Ir
40A
125A
250A
3P
4P*
HEC040H
HEC125H
HEC250H
HEC041H
HEC126H
HEC251H
MCCBs
h250 - accessories
Coil connection
- Connection capacity: 0.75mm2
flexible or rigid cables
- Optional connection cables.
The cable capacity of the
terminals is 0.5 to 1.25mm2.
Shunt trip
- Remote tripping of MCCBs or
trip-free switches. Operating
voltage: 0.7 to 1.1 x Un.
Under voltage release
- Allows the tripping of MCCBs
when voltage level drops
between 35 and 70% of Un.
- Pick up voltage 0.85 x Un.
Direct rotary handle
-Padlockable
- Equipped with front
cover and handle
- Fixing without any
additional screw.
Extended rotary handle
-IP55
- Supplied complete with
shaft and handle.
Technical information:
- Visit our website at
www.hagerelectro.com.au
Accessories
HXC021H
Description
Characteristics
Cat ref.
Auxiliary contacts
AX
AL
1 changeover contact
250V AC / 3A
125V DC / 0,4A
1NO + 1NC
1 changeover alarm contact
250V AC / 3A
125V DC / 0,4A
1NO + 1NC
24V DC
HXC021H
48V DC
100 - 120V AC
200 - 240V AC
380 - 450V AC
24V DC
100 - 120V AC
200 - 240V AC
380 - 450V AC
Ø 5 - 8mm2 max
HXC002H
HXC003H
HXC004H
HXC005H
HXC011H
HXC013H
HXC014H
HXC015H
HXC030H
Ø 5 - 8mm2 max
320mm
Max Ø 5mm
HXC031H
24V DC
230-240V AC
HXC040H
HXC042H
HXC065H
HXC024H
Shunt trips
SH
Undervoltage releases
UV
HXC004H
HXC014H
Direct rotary handles
Padlockable
Extended rotary handles
Padlockable
Padlocking device
To mount on MCCBs for handle
locking 3 padlocks
Motor operators
HXC039H
HXC024H
HXC001H
HXC039H
Interlocking
Wire type
Accessories
Description
HYC011H
Collar terminals
Extended connections
Rear connections
Interphase barriers
Terminal covers
HYC031H
Characteristics
Copper
Straight connections
Spreader connections
Cat ref.
3P
4P
HYC003H
HYC010H
HYC011H
HYC031H
HYC019H
HYC004H
HYC010H
HYC012H
HYC032H
HYC019H
Set of 3
Height: 97mm
For extended straight connections HYC021H
(LSI only)
HYC025H
For rear connections
HYC027H
For collar terminals
HYC022H
HYC026H
HYC028H
C.15
Main Switches
& Isolators
Indication contacts
- 1 changeover switch
(ON/OFF): indicates the
position of the MCCB is
“open” or “closed”.
- 1 changeover alarm contact:
indicates MCCB tripping.
MCCBs
h630
Moulded case circuit
breakers h630
- 3P & 4P
- Adjustable neutral
0 - 50% - 100%
- Mechanical test button,
lockable settings
- Comply with IEC 60947-2.
Connection:
- Directly on copper cable
terminal, with end lug
max. width: 30mm
Electronic trip unit LSI:
- Long delay (thermal
equivalent) adjustable:
Ir = 0.4 to 1 x In
- Short delay (magnetic
equivalent) adjustable:
2.5 to 10 x Ir (400A)
2.5 to 8 x Ir (630A)
- Time delay: 0.1 - 0.2 s
Technical information:
- Visit our website at
www.hagerelectro.com.au
*Please check availability with your local Hager sales office at time of order
MCCBs h630 50kA LSI
Description
HND630H
- Breaking capacity
Icu: 50 kA (400/415V AC)
Ics: 50 kA
- Adjustable thermal
Ir = 0.4 to 1 x In
- Adjustable magnetic
2.5 to 10 x Ir (400A)
2.5 to 8 x Ir (630A)
- Time delay: 0.1 - 0.2s
In
Cat ref.
Cat ref.
3P
4P*
400A
630A
HND400H
HND630H
HND401H
HND631H
In
Cat ref.
Cat ref.
MCCBs h630 70kA LSI
Description
HED630H
C.16
- Breaking capacity
Icu: 70 kA (400/415V AC)
Ics: 50 kA
- Adjustable thermal
Ir = 0.4 to 1 x In
- Adjustable magnetic
2.5 to 10 x Ir (400A)
2.5 to 8 x Ir (630A)
- Time delay: 0.1 - 0.2s
400A
630A
3P
4P*
HED400H
HED630H
HED401H
HED631H
MCCBs
h630 - accessories
Coil connection
- Connection capacity: 0.75mm2
flexible or rigid cables
- Optional connection cables.
The cable capacity of the
terminals is 0.5 to 1.25mm2.
Shunt trip
- Remote tripping of
MCCBs. Operating
voltage: 0.7 to 1.1 x Un.
Under voltage release
- Allows the tripping of MCCBs
when voltage level drops
between 35 and 70% of Un.
- Pick up voltage 0.85 x Un.
Direct rotary handle
-Padlockable
- Equipped with front
cover and handle
- Fixing without any
additional screw.
Technical information:
- Visit our website at
www.hagerelectro.com.au
Extended rotary handle
-IP55
- Supplied complete with
shaft and handle.
Main Switches
& Isolators
Indication contacts
- 1 changeover switch
(ON/OFF): indicates the
position of the MCCB is
“open” or “closed”.
- 1 changeover alarm contact:
indicates MCCB tripping.
Accessories
HXC021H
Description
Characteristics
Cat ref.
Auxiliary contacts
AX
AL
1 changeover contact
250V AC / 3A
125V DC / 0,4A
1NO + 1NC
1 changeover alarm contact
250V AC / 3A
125V DC / 0,4A
1NO + 1NC
24V DC
48V DC
100 - 120V AC
200 - 240V AC
380 - 450V AC
24V DC
100 - 120V AC
200 - 240V AC
380 - 450V AC
Max Ø 6 mm
HXC021H
HXC024H
Shunt trips
SH
Undervoltage releases UV
HXC004H
HXC014H
Direct rotary handles
Padlockable
Extended rotary handles
Padlockable
Padlocking device
To mount on MCCBs for handle
locking 3 padlocks
Max Ø 8mm
320mm
Max Ø 8mm
HXC024H
HXC001H
HXC002H
HXC003H
HXC004H
HXC005H
HXC011H
HXC013H
HXC014H
HXC015H
HXD030H
HXD031H
HXD039H
HXD030H
HXD039H
C.17
MCCBs
h630 - accessories
Accessories
Cat ref.
HXD042H
HYD003H
Description
Characteristics
Motor operators
24-48V DC
100-240V AC
Interlocking
Wire type
Collar terminals
Terminals for copper
conductors 1 x 35 - 240mm2
Terminals for multiple
aluminium/copper conductors
2 x 35 - 240mm2
Extended connections
For straight connections
For spreader connections
HYD015H
HYD022H
HYD033H
C.18
Terminal covers
For extended straight connections
For extended spreader
connections
For rear connections
For collar terminals
Cat ref.
3P
4P
HXD040H
HXD042H
HXD065H
HXD040H
HXD042H
HXD065H
Set of 3 or 4
160 - 400A
HYD003H
HYD004H
Set of 3 or 4
400 - 630A
HYD007H
HYD008H
Set of 4 pieces
400A
630A
400A
630A
400A
630A
HYD010H
HYD013H
HYD011H
HYD014H
HYD031H
HYD033H
HYD019H
HYD010H
HYD013H
HYD012H
HYD015H
HYD032H
HYD034H
HYD019H
HYD021H
HYD023H
HYD022H
HYD024H
HYD025H
HYD027H
HYD026H
HYD028H
Set of 4 pieces
Rear connections
Interphase barriers
In
Set of 3
Height: 97mm
MCCBs
h1000
Moulded case circuit
breakers h1000
- 3P & 4P
- Adjustable neutral
0 - 50% - 100%
- Mechanical test button,
lockable settings.
Connection:
- Direct on copper terminal, with
end lug max. width: 50mm
- Comply with IEC60947-2.
Electronic trip unit LSI:
- Long delay (thermal
equivalent) adjustable:
Ir= 0,4 to 1 x In
- Short delay (magnetic
equivalent) adjustable:
2,5 to 10 x Ir (630-800A)
2.5 to 8 x Ir (1000A)
- Time delay: 0.1-0.2s
Technical information:
- Visit our website at
www.hagerelectro.com.au
Main Switches
& Isolators
*Please check availability with your local Hager sales office at time of order
MCCBs h1000 50kA LSI
Description
HNE970H
- Breaking capacity
Icu: 50 kA (400/415V AC)
Ics: 50 kA
- Adjustable thermal
Ir = 0,4 to 1 x In
- Adjustable magnetic
2,5 to 10 x Ir (800A)
2,5 to 8 x Ir (1000A)
- Time delay: 0.1-0.2s
- Neutral setting from
0-50 to 100%
In
800A
1000A
Cat ref.
Cat ref.
3P
4P*
HNE800H
HNE970H
HNE801H
HNE971H
MCCBs h1000 70kA LSI
Description
HEE801H
- Breaking capacity
Icu: 70 kA (400/415V AC)
Ics: 50 kA
- Adjustable thermal
Ir = 0,4 to 1 x In
- Adjustable magnetic
2,5 to 10 x Ir (800A)
2,5 to 8 x Ir (1000A)
- Time delay: 0,1-0,2s
- Neutral setting from
0-50 to 100%
In
800A
1000A
Cat ref.
Cat ref.
3P
4P*
HEE800H
HEE970H
HEE801H
HEE971H
C.19
MCCBs
h1000 - accessories
Indication contacts
- 1 changeover switch
(ON/OFF): indicates the
position of the MCCB is
“open” or “closed”.
- 1 changeover alarm contact:
indicates MCCB tripping.
Coil connection
- Connection capacity: 0.75mm2
flexible or rigid cables
- Optional connection cables.
The cable capacity of the
terminals is 0.5 to 1.25mm2.
Shunt trip
- Remote tripping of
MCCBs. Operating
voltage: 0.7 to 1.1 x Un.
Under voltage release
- Allows the tripping of MCCBs
when voltage level drops
between 35 and 70% of Un.
- Pick up voltage 0.85 x Un.
Direct rotary handle
-Padlockable
- Equipped with front
cover and handle
- Fixing without any
additional screw.
Technical information:
- Visit our website at
www.hagerelectro.com.au
Extended rotary handle
-IP55
- Supplied complete with
shaft and handle.
Accessories
HXC021H
Description
Characteristics
Cat ref.
Auxiliary contacts
AX
AL
1 changeover contact
250V AC / 3A
125V DC / 0,4A
1NO + 1NC
1 changeover alarm contact
250V AC / 3A
125V DC / 0,4A
1NO + 1NC
24V DC
HXC021H
HXC024H
Shunt trips
SH
Undervoltage releases
UV
HXC004H
HXE014H
Direct rotary handle
Padlockable
Extended rotary handles
Padlockable
Padlocking device
To mount on MCCB for handle
locking 3 padlocks
Motor operators
HXD039H
48V DC
100 - 120V
200 - 240V
380 - 450V
24V DC
100 - 120V
200 - 240V
380 - 450V
HXC024H
HXC001H
HXC002H
HXC003H
HXC004H
HXC005H
HXE011H
HXE013H
HXE014H
HXE015H
HXE030H
AC
AC
AC
AC
AC
AC
HXE031H
Max Ø 8mm
320mm
Max Ø 8 mm
HXD039H
HXE040H
HXE042H
HXE065H
24 - 48V DC
100 - 240V AC
Interlocking
Wire type
Accessories
Description
HYE031H
C.20
Terminal covers
For extended connections
For rear connections
Rear connections
In
800A
1000A
Cat ref.
Cat ref.
3P
4P*
HYE021H
HYE025H
HYE031H
HYE033H
HYE022H
HYE026H
HYE032H
HYE034H
MCCBs
h1600
Moulded case circuit
breakers h1600
- 3 pole - 3 trip units
4 pole - 4 trip units
- Adjustable neutral
0 - 50% - 100%
- Mechanical test button,
lockable settings.
- Comply with IEC60947-2.
- Short delay (magnetic
equivalent) adjustable:
2.5 to 10 x Ir
- Time delay: 0.1-0.2
Technical information:
- Visit our website at
www.hagerelectro.com.au
Connection:
- Directly on copper cable
terminal, with end lug
max. width: 60mm
*Please check availability with your local Hager sales office at time of order
MCCBs h1600 50kA LSI
Description
HNF990H
- Breaking capacity
Icu: 50 kA (400/415V AC)
Ics: 50 kA
- Adjustable thermal
Ir = 0.4 to 1 x In
- Adjustable magnetic
2.5 to 10 x Ir
- Time delay: 0.1-0.2s
- Neutral setting 0, 50, 100%
In
1250A
1600A
Cat ref.
Cat ref.
3P
4P*
HNF980H
HNF990H
HNF981H
HNF991H
MCCBs h1600 70kA LSI
Description
HEF980H
In
1250A
- Breaking capacity
Icu: 70 kA (400/415V AC)
1600A
Ics: 50 kA
- Adjustable thermal
Ir = 0.4 to 1 x In
- Adjustable magnetic
2.5 to 10 x Ir
- Time delay: 0.1-0.2s
- Neutral setting from 0, 50, 100%
Cat ref.
Cat ref.
3P
4P*
HEF980H
HEF990H
HEF981H
HEF991H
C.21
Main Switches
& Isolators
Electronic trip unit LSI:
- Long delay (thermal
equivalent) adjustable:
Ir = 0.4 to 1 x In
MCCBs
h1600 - accessories
Indication contacts
- 1 changeover switch
(ON/OFF): indicates the
position of the MCCB is
“open” or “closed”.
- 1 changeover alarm contact:
indicates MCCB tripping.
Coil connection
- Connection capacity: 0.75mm2
flexible or rigid cables
- Optional connection cables.
The cable capacity of the
terminals is 0.5 to 1.25mm2.
Shunt trip
- Remote tripping of
MCCBs. Operating
voltage: 0.7 to 1.1 x Un.
Under voltage release
- Allows the tripping of MCCBs
when voltage level drops
between 35 and 70% of Un.
- Pick up voltage 0.85 x Un.
Direct rotary handle
-Padlockable
- Equipped with front
cover and handle
- Fixing without any
additional screw.
Technical information:
- Visit our website at
www.hagerelectro.com.au
Extended rotary handle
-IP55
- Supplied complete with
shaft and handle.
Rear connection included
Accessories
HXC021H
Description
Characteristics
Cat ref.
Auxiliary contacts
AX
AL
1 changeover contact
250V AC / 3A
125V DC / 0,4A
1NO + 1NC
1 changeover alarm contact
250V AC / 3A
125V DC / 0,4A
1NO + 1NC
24V DC
HXC021H
HXF001H
48V DC
100 - 120V AC
200 - 240V AC
380 - 450V AC
24V DC
100 - 120V AC
200 - 240V AC
380 - 450V AC
Max Ø 8mm
HXF002H
HXF003H
HXF004H
HXF005H
HXE011H
HXE013H
HXE014H
HXE015H
HXF030H
Max Ø 8mm
320mm
Max Ø 8mm
HXF031H
HXF039H
24V DC
200 - 230V AC
HXF040H
HXF042H
HXC024H
Shunt trips
SH
Undervoltage releases
UV
HXF004H
HXE014H
Direct rotary handles
Padlockable
Extended rotary handles
Padlockable
Padlocking device
To mount on MCCBs for handle
locking 3 padlocks
Motor operators
HXF040H
C.22
HXC024H
Load break switches
Technical data
- Visualised breaking
- Double breaking per
phase
- 3 or 4 pole
- Padlockable handle
- Auxiliary contacts
- Rotary handles
complete with
extension shaft
- Complying with
IEC60947-3
Main Switches
& Isolators
Description
The HA series is a range of
multi-pole load disconnector
switches with manual operation.
They enable making and
breaking on load and safety
isolation of any low voltage
installation.
DIN & screw mount isolators
Description
Width
Characteristics
Module mm
Cat ref.
3 pole 400V~
6 mod
6 mod
6 mod
8.5 mod
8.5 mod
8.5 mod
6 mod
8.5 mod
In
In
In
In
In
In
In
In
108
108
108
142
142
142
108
142
HA304
HA305
HA306
HA307
HA308
HA309M
HA406
HA408
Description
Width
Characteristics
Module mm
Cat ref.
3 pole 400V~
-
In
In
In
In
In
In
In
In
-
HA354
HA356
HA358
HA360
HA362
HA364
HA457
HA458
HA305
4 pole 400V~
80A
100A
125A
160A
200A
250A
125A
200A
Screw mount isolators
HA354
4 pole 400V~
250A
400A
630A
800A
1250A
1600A
400A - AC23
630A - AC23
C.23
Load break switches
Accessories
Description
The HA series is a range of
multi-pole load disconnector
switches with manual operation.
They enable making and
breaking on load and safety
isolation of any low voltage
installation.
Technical data
-Visualised breaking
-Double breaking per
phase
-DIN rail mounting
-3 or 4 pole
-Padlockable handle
-Auxiliary contacts
-Complying with
IEC60947-3
Rotary handles
Description
Characteristics
Cat ref.
To suit HA360/HA362/HA364
To suit HA354/HA356/HA358
To suit HA304/HA305/
HA306/HA307/HA308
Black IP65
Black IP55
Black IP55
HZC003
HZC002
HZC001
HZC003
Extension shafts
HZC106
Description
Characteristics
Cat ref.
To suit HA360/HA362/HA364
To suit HA354/HA356/HA358
To suit HA304/HA305/
HA306/HA307/HA308
320mm
320mm
200mm
HZC106
HZC102
HZC103
Auxiliary contacts
HZ022
Description
Characteristics
Cat ref.
Suitable for HA304/HA305/
HA306/HA307/HA308
Suitable for HA354/HA356/
HA358/HA360/HA362/HA364
In 5A -250V~
HZ022
In 16A - 250V~
HZ023
Terminal shrouds
HZC203
C.24
Description
Width
Cat ref.
To suit HA354
Switch-line or load side
To suit HA356/HA358/
Switch-line or load side
To suit HA307/HA308
Switch-line or load side
(Cable lug connection)
To suit HA307/HA308/
Switch c/- cable clamp
line or load side
1 mod
HZC203
1 mod
HZC205
1 mod
HZ062
1 mod
HZ072
Cat ref.
thermal current Ith
insulation voltage Ui (V)
impulse withstand voltage Uimp (kV)
rated operation current (A)
AC-21A / AC-21B
400V AC(1)
AC-22A / AC-22B
AC-23A / AC-23B
AC-20A / AC-20B
690V AC(2)
AC-22A / AC-22B
AC-23A / AC-23B
220V DC
DC-20A / DC-20B
operational power (kW)
400V AC
690V AC
short time withstand current 1 sec (kA rms)
short circuit making capacity (kA peak)
connection
max. cable section (mm)
max. busbar width (mm)
(1)
(2)
HA305
100
800
8
A/B
100/100
100/100
100/100
100/100
40/40
25/25
100/100
HA306
125
800
8
A/B
125/125
125/125
125/125
125/125
40/40
25/25
125/125
HA307
160
800
8
A/B
160/160
160/160
160/160
160/160
160/160
63/80
160/160
HA308
200
800
8
A/B
200/200
200/200
200/200
200/200
160/160
63/80
200/200
HA309M
250
800
8
A/B
200/250
200/200
200/200
200/250
160/160
63/80
200/250
40
51
63
80
100
100
33
33
33
150
150
150
2.5
12
2.5
12
2.5
12
4
16
4
16
4
16
50
-
50
-
50
-
95
20
95
20
95
20
A/B = category with index - A = frequent operation / B = infrequent operation
with terminal shrouds or phase barriers
Cat ref.
thermal current Ith
insulation voltage Ui (V)
impulse withstand voltage Uimp (kV)
rated operation current (A)
AC-21A / AC-21B
400V AC(1)
AC-22A / AC-22B
AC-23A / AC-23B
AC-20A / AC-20B
690V AC(2)
AC-22A / AC-22B
AC-23A / AC-23B
220V DC
DC-20A / DC-20B
operational power (kW)
400V AC
690V AC
short time withstand current 1 sec (kA rms)
short circuit making capacity (kA peak)
connection
max. cable section (mm)
max. busbar width (mm)
(1)
(2)
HA304
80
800
8
A/B
80/80
80/80
80/80
80/80
40/40
25/25
80/80
HA354
250
800
8
A/B
250/250
250/250
250/250
250/250
200/250
125/160
250/250
HA356
400
1000
12
A/B
400/400
400/400
400/400
400/400
400/400
250/315
400/400
HA358
630
1000
12
A/B
630/630
630/630
500/630
630/630
500/500
315/315
630/630
HA360
800
1000
12
A/B
800/800
800/800
800/800
800/800
800/800
800/800
800/800
HA362
1250
1000
12
A/B
1250/1250
1250/1250
1250/1250
1250/1250
1000/1000
1000/1000
1250/1250
HA364
1600
1000
12
A/B
1600/1600
1600/1600
1250/1250
1600/1600
1000/1000
1000/1000
1600/1600
132/132
90/110
220/220
150/185
280/280
150/185
450/450
185/220
710/710
475/475
710/710
475/475
9
30
13
45
13
45
26
55
50
110
50
110
150
32
240
40
2 x 300
50
2 x 300
63
4 x 185
100
6X185
100
A/B = category with index - A = frequent operation / B = infrequent operation
with terminal shrouds or phase barriers
Application condition & utilisation category, according to IEC 60947-3
Utilisation category
AC
DC
AC20
DC20
AC21
DC21
AC22
DC22
AC23
DC23
Use
Application
Off-load making & breaking
Resistive loads including moderate overloads
Disconnector
Switches at installation head or for resistive circuits
(lighting)
Switches in secondary circuits or reactive circuits
(capacitor banks)
Switches feeding one or serveral motor or inductive
circuits (series motors, magnetic brakes)
Inductive & resistive mixed loads including moderate
overloads
Loads made of motors or other hightly inductive loads
Subject to technical change.
C.25
Main Switches
& Isolators
Load break switches - characteristics
(according to IEC 60947-3)
Earth leakage relays & toroids
Description
This range of earth leakage
relays were designed on
an electronic basis, which
ensure the monitoring of
earth fault currents. When the
fault current rises above the
selected level, the outputs of
the relay operate & depending
on the relay selected, it
can have both adjustable
sensitivity and time delay
that can provide selectivity/
discrimination. The relays are
linked with detection toroids.
Common characteristics
- Standard DIN EN60947-2,
IEC60755, IEC61008-8
- Fixed & adjustable devices
- Positive safety: the relay
trips in the event of a
break in the connection
between relay & toroid.
- Positive / local reset required
after a fault is detected.
- Protected against
nuisance tripping
- Class A
- Output: 1c/o contact
250V~ 6A AC1
- Visual display of fault
- Supply voltage 230V
+/- 20% 50/60Hz
Premium features
- Adjustable sensitivity &
time delay (sealable)
- Display of fault current prior
to triggering relay (5%-75%)
- Extra output contact
(250V-AC1/6A) to enable
remote indication of fault
currents above 50% of Irn
- Remote test and reset
by three wire link
Connection capacity
- Flexible - 1 to 2.5mm
- Stranded/rigid - 1.5 to 4mm
supply
contactor
trip
earth
leakage
relay
detection
toroid
conforms to IEC 1008
Earth leakage relays
HR510
HR520
Description
Width
Cat ref.
Without delay
c/o contact 250V 6A ~ AC1
Fixed sensitivity = 300mA
Trips immediately
Standard
c/o contact 250V 6A ~ AC1
Adjustable sensitivity Irn= 0.03/0.1/0.3/0.5/1/3/10A
Adjustable time delay rt= 0/0.1/0.3/0.4/0.5/1/3sec
Premium
c/o contact 250V 6A ~ AC1
Fail safe contact 250V 6A ~ AC1
Pre-alarm contact 250V 6A ~ AC1
Adjustable sensitivity Irn= 0.03/0.1/0.3/0.5/1/3/10A
Adjustable time delay rt= 0/0.1/0.3/0.4/0.5/1/3sec
Bargraph = 5% - 75% Irn
Integral toroid
c/o contact 250V 6A ~ AC1
Adjustable sensitivity Irn= 0.03/0.1/0.3/0.5/1/3A
Adjustable time delay rt= 0/0.1/0.3/0.5/0.75/1sec
Ø of toroid: 35mm
1 mod
HR502
3 mod
HR510
3 mod
HR520
6 mod
HR441
Circular section toroids
Characteristics
HR700
C.26
Inside
Inside
Inside
Inside
Inside
Ø
Ø
Ø
Ø
Ø
of
of
of
of
of
Cat ref.
toroid:
toroid:
toroid:
toroid:
toroid:
30mm
35mm
70mm
105mm
140mm
HR700
HR701
HR702
HR703
HR704
Technical specifications for
Residual current (earth leakage) relays
Earth leakage relays
Permissible overload of the toroid
Test & reset push button voltage
Type A
Increased immunity (HI)
Voltage & fault indication
Signalling current default
Bar graph indication
Standard output (1OF)
Fail safe output (1OF)
50% Irn output
Analog output
W/o adjustment Adjustable
HR502
HR510
HR520
1
3
3
230V +/- 20%
50 à 700V
3 VA
5 VA
Potential free changeover contacts
5A / 250V AC1 6A / 250V AC1
0.3A
0.03 / 0.1/0.3 / 0.5/ 1/ 3/10
Instant
0/0,1s/0,3s/0,4s 0/0,1s/0,3s/0,4s
/0,5s/1s/3s
/0,5s/1s/3s/5S
30 kA / 100 ms
100 - 250V
yes
yes
yes
yes
yes
yes
no
yes
yes
-
Maximum cable length to test & reset
Maximum cable length between toroid & relay
Connection. Relay: cage terminals
rigid/stranded
flexible
Connection. Toroid:
rigid/stranded
flexible
Operating temperature
Storage temperature
Standard compliance
200m
50m maximum width 1,5mm² twisted pair cable - 25m for non twisted cable
1,5 to 4 mm²
1,5 to 4 mm²
1 to 2,5 mm²
1 to 2,5 mm²
1,5 to 4 mm²
1,5 to 4 mm²
1 to 6 mm²
1 to 6 mm²
-10 to +55°C
-25 to +70°C
IEC 60947-2 annexe B, IEC 61543, IEC 61008-1, IEC 60755
6 VA
0.03 / 0.1/0.3 / 0.5/ 1/ 3
0s /0,1s /0,3s
/0,5s/0,75s/1s
Main Switches
& Isolators
Number of modules
Supply voltage
~50/60Hz
Network voltage
~50/60Hz
Power consumption
Output command
Contact rating (standard output, fail safe, 50% pre-alarm)
Residual current settings Irn
Delay on opening (+/- 20%)
With integrated toroid
HR441
6
no
0,03A Irn = 2,25 mV/mA
0,1A Irn = 2,25 mV/mA
0,3A Irn = 2,25 mV/mA
0,5A Irn = 2,25 mV/mA
1A Irn = 2,25 mV/mA
3A Irn = 2,25 mV/mA
Toroids
Internal diameter of toroid
Maximum screw torque
Maximum connection distance between toroid & ELR
Rated frequency
Connection: rigid/stranded cable
Connection section in flexible cable for the
measurement
Operating temperature
Storage temperature
Rated voltage for alternating use
Rated insulation voltage
Rated impulse withstand voltage
IP for torroids
HR700
HR701
HR702
30mm
35mm
70mm
1Nm
50m max with twisted pair cable
50-60 Hz
1 to 1.5 mm²
1,5 à 4 mm²
1 to 1,5mm²
HR703
105mm
HR704
140mm
1,5 à 2,5mm²
-10 to +55°C
-25 to +70°C
50 to 700V
250V
4kV
IP41
Application notes
Discrimination between Residual Current Devices
Hager residual current relays (HR210, HR212) have adjustable
time delay and residual current settings. They can be used as
an upstream device to achieve residual current protection of the
entire installation. It is advisable to set the residual current relay
at a residual higher tripping current than a downstream devices
(> 30mA) since the upstream device will see the accumulation
of leakage currents from the entire installation. The residual
current setting will depend on the quantity and type of equipment
connected to the installation (Immersion water heaters, switch
mode power supplies are particularly prone to leakage currents
to earth). The time delay should be set above zero to 300ms.
In theory it is possible to achieve current discrimination between
residual current devices, but the limit of discrimination is far too
low for practical purposes. Time delay is the only reliable & by far
the best method used to obtain discrimination. It can be achieved
by delaying the tripping of the upstream residual current devices.
The downstream device would typically be a 30mA or
occasionally a 10mA residual current device. Typically they
will operate within 40ms and occasionally much faster.
If further levels of protection are required upstream from the
Hager residual current relay, then another residual current
relay can be installed upstream and the settings of the
device (time and residual current) adjusted higher again.
Subject to technical change.
C.27
Hager Electro Pty Ltd
1/170 Power Street
Glendenning NSW 2761
www.hagerelectro.com.au
Nationwide sales
Ph 1300 850 253
Fx 1300 424 372
Email: customerservice@hagerelectro.com.au
State offices in:
New South Wales
North Queensland
South East Queensland
South Australia
Victoria
Western Australia
Distributors in:
Northern Territory
Tasmania
Download