Know Your Options: 69 kV XLPE Power Cable 3 Section 2 Conductor material and size •Copper conductor common for larger loads •When both copper and aluminum conductors can meet your requirements, the more economical solution will be a function of the metal and the cable component costs Insulation thickness •For cables with a radial moisture barrier, “Southwire Standard Wall” reduced insulation thicknesses within the stress limits in AEIC specification CS9 are recommended •Cables referred to by “Traditional Wall” insulation (650 mils) follow the traditional insulation wall practice referenced in ICEA standard S-108-720 appendix F as still specified by a number of customers and utilities •For applications requiring smaller cable diameters, specific designs are available upon request Sheath material •Copper and aluminum corrugated sheaths offer the best mechanical and moisture protection for your HV cable, and copper will provide better short circuit performance and improved connectability •Full wall cables with concentric neutrals are an economical option for mostly dry environments •Composite laminate sheaths in both copper and aluminum that offer excellent protection against moisture ingress Jacket •Standard outer jacket: extruded LLDPE with a co-extruded outer semi-conductive polyethylene layer for jacket integrity testing •Halogen Free Fire Retardant (HFFR) compounds are available upon request for installations in cable trays and ventilated troughs 4 69 kV Power Cables Conductor material is a matter of both customer preference and required current carrying capacity 69 kV Power Cables 69 kV XLPE – Copper Conductor Traditional Wall 650 mil XLPE Copper Corrugated Sheath Cable Construction •Reverse Concentric Stranded Copper, Compressed Conductor or Milliken •Super Smooth Conductor Shield •Super Clean XLPE Insulation •Traditional Wall - 650 mil XLPE •True Triple Extrusion and Dry Cured •Firmly Bonded Insulation Shield •Welded Copper Corrugated Sheath •Polyethylene Jacket with Extruded Semi-Conductive Outer Layer Cable Data Voltage Characteristics (kV) Max Voltage Rating 72.5 BIL Rating 350 Temperatures ( C) o Nominal Conductor 90 Max. Emergency Conductor 105 Short Circuit Conductor 250 Minimum Installation -10 Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 120 kV / 15 min. 0.0005 2.3 5 Section 2 Conductor Size in kcmil1 500 750 1000 1250 1500 1750 2000 2500 3000 3500 4000 Nominal Conductor Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21 mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1 in 2.21 2.39 2.53 2.67 2.79 2.90 3.00 3.26 3.42 3.58 3.71 mm 56.1 60.7 64.3 67.8 70.9 73.7 76.2 82.8 86.9 90.8 94.2 in 2.68 2.88 3.04 3.19 3.32 3.44 3.56 3.85 4.03 4.20 4.34 mm 68.1 73.2 77.2 81.0 84.3 87.4 90.4 97.8 102.3 106.6 110.3 in 2.96 3.16 3.33 3.47 3.60 3.72 3.84 4.13 4.31 4.48 4.62 mm 75.2 80.3 84.6 88.1 91.4 94.5 97.5 104.9 109.4 113.7 117.4 Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight lbs/ft 4.8 5.9 6.9 7.9 8.8 9.8 10.7 12.9 14.8 16.7 18.5 Min. Bending Radius (install/perm.) in in 59/44 63/47 67/50 69/52 72/54 74/56 77/58 83/62 86/65 90/67 92/69 Maximum Pulling Tension lbs 4,000 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000 69 kV Power Cables Dimensional Typical Shipping Reel Size Flange x Width in 126x95 126x95 126x95 126x95 126x95 126x95 150x95 158x95 150x95 150x95 150x95 Shipping Reel Capacity* ft 3,000 3,000 3,000 3,000 3,000 2,950 3,000 2,800 2,500 2,200 1,975 Conductor Shield kV/mm 3.9 3.7 3.5 3.4 3.4 3.3 3.3 3.2 3.1 3.1 3.1 Insulation Shield kV/mm 1.6 1.7 1.7 1.8 1.8 1.8 1.8 1.9 1.9 1.9 1.9 Electrical Short Circuit for 0.5s 3 Conductor kA 51.3 76.9 102.5 128.1 153.8 179.4 205 256.3 307.5 358.8 410 Sheath kA 33.6 36.1 38.2 40 41.6 43.2 44.6 48.3 50.5 52.6 54.4 DC @ 20o C Ω/kft 0.021 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.004 0.003 0.003 DC @ 90 C Ω/kft 0.027 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003 Capacitance pF/ft 43.8 49.5 54.2 58.4 62.1 65.5 68.7 76.5 81.5 86.2 90.3 Charging Current Amps/ kft 0.66 0.74 0.81 0.88 0.93 0.98 1.03 1.15 1.22 1.29 1.36 Ampacity @ 90o C per circuit Typical Single Ductbank4 Amps 600 740 820 960 1040 1110 1180 1390 1506 1595 1673 Power Rating MVA 72 89 98 115 125 133 142 167 180 191 200 Typical Double Ductbank4 Amps 510 630 710 810 880 940 990 1181 1276 1432 1517 Power Rating MVA 61 76 85 97 106 113 119 142 153 172 182 Conductor Resistance o 2500-4000 kcmil conductors are 5 segment Milliken conductors. Increased shipping reel capacity can be accommodated on request. Declared values for 30 mils copper sheath. Thicker sheath can accommodate more current. 4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded 1 2 3 6 Traditional Wall 650 mil XLPE Copper Corrugated Sheath Electrical Stress @ Uo 69 kV Power Cables 69 kV XLPE – Copper Conductor SW Standard Wall XLPE Copper Corrugated Sheath Cable Construction •Reverse Concentric Stranded Copper, Compressed Conductor or Milliken •Super Smooth Conductor Shield •Super Clean XLPE Insulation •430 mil XLPE minimum •True Triple Extrusion and Dry Cured •Firmly Bonded Insulation Shield •Welded Copper Corrugated Sheath •Polyethylene Jacket with Extruded SemiConductive Outer Layer Cable Data Voltage Characteristics (kV) Max Voltage Rating 72.5 BIL Rating 350 Temperatures ( C) o Nominal Conductor 90 Max. Emergency Conductor 105 Short Circuit Conductor 250 Minimum Installation -10 Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 120 kV / 15 min. 0.0005 2.3 7 Section 2 Conductor Size in kcmil1 500 750 1000 1250 1500 1750 2000 2500 3000 3500 4000 Nominal Conductor Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21 mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1 mils 520 490 470 450 450 440 430 430 440 450 450 mm 13.2 12.4 11.9 11.4 11.4 11.2 10.9 10.9 11.2 11.4 11.4 in 1.95 2.07 2.18 2.27 2.39 2.48 2.56 2.82 2.92 3.1 3.23 mm 49.5 52.5 55.4 57.7 60.7 63.0 65.0 71.6 74.2 78.7 82.0 in 2.39 2.51 2.63 2.73 2.87 2.96 3.05 3.35 3.44 3.64 3.78 mm 60.7 63.8 66.8 69.3 72.9 75.2 77.5 85.0 87.4 92.5 96.0 Overall Jacket Diameter in 2.67 2.80 2.91 3.01 3.15 3.24 3.33 3.63 3.72 3.92 4.06 mm 67.8 71.0 73.9 76.5 80.0 82.3 84.6 92.1 94.5 99.6 103.1 Total Weight lbs/ft 4.2 5.2 6.1 6.9 7.9 8.8 9.6 11.7 13.3 15.3 17 Min. Bending Radius (install/ perm.) in 53/40 56/42 58/44 60/45 63/47 65/49 67/50 73/54 74/56 78/59 81/61 Maximum Pulling Tension lbs 4,000 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000 Insulation Thickness Diameter over Insulation Diameter over Sheath 69 kV Power Cables Dimensional Typical Shipping Reel Size in 126x95 126x95 126x95 126x95 126x95 126x95 126x95 126x95 150x95 150x95 158x95 Shipping Reel Capacity2 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000 3,000 2,750 2,400 2,100 Conductor Shield kV/mm 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.3 4.2 4.1 Insulation Shield kV/mm 2.1 2.4 2.6 2.7 2.8 2.9 3.0 3.0 3.0 3.0 3.0 Electrical Electrical Stress @ Uo Short Circuit for 0.5s3 Conductor kA 51.3 76.9 102.5 128.1 153.8 179.4 205 256.3 307.5 358.8 410 Sheath kA 29.9 31.5 33 34.2 35.9 37.1 38.2 41.9 43.1 45.5 47.4 DC @ 20o C Ω/kft 0.021 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.004 0.003 0.003 Conductor Resistance DC @ 90 C Ω/kft 0.027 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003 Capacitance pF/ft 51.1 60.6 68.9 77.1 82.4 88.9 95.3 107.1 108.6 113.3 119.2 Charging Current Amps/ kft 0.74 0.91 1.04 1.16 1.24 1.34 1.43 1.31 1.63 1.7 1.79 Ampacity @ 90o C per circuit Typical Single Ductbank4 Amps 600 750 870 970 1060 1130 1200 1422 1544 1632 1714 Power Rating MVA 72 90 104 116 127 136 144 170 185 196 205 Typical Double Ductbank4 Amps 520 640 740 820 890 950 1000 1202 1303 1377 1445 Power Rating MVA 63 77 89 98 107 114 120 144 156 165 173 o 1 2 2500-4000 kcmil conductors are 5 segment Milliken conductors. Increased shipping reel capacity can be accommodated on request. Declared values for 30 mils copper sheath. Thicker sheath can accommodate more current. 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded 3 4 8 SW Standard Wall XLPE Copper Corrugated Sheath Flange x Traverse 69 kV Power Cables 69 kV XLPE Aluminum Conductor Traditional Wall 650 mil XLPE Aluminum Corrugated Sheath Cable Construction •Reverse Concentric Stranded Aluminum, Compressed Conductor •Super Smooth Conductor Shield •Super Clean XLPE Insulation •Traditional Wall - 650 mil XLPE •True Triple Extrusion and Dry Cured •Firmly Bonded Insulation Shield •Welded Aluminum Corrugated Sheath •Polyethylene Jacket with Extruded SemiConductive Outer Layer Cable Data Voltage Characteristics (kV) Max Voltage Rating 72.5 BIL Rating 350 Temperatures ( C) o Nominal Conductor 90 Max. Emergency Conductor 105 Short Circuit Conductor 250 Minimum Installation -10 Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 120 kV / 15 min. 0.0005 2.3 9 Section 2 Conductor Size in kcmil 500 750 1000 1250 1500 1750 2000 1.25 1.37 1.48 1.61 Nominal Conductor Diameter in 0.79 0.97 1.12 mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 in 2.21 2.39 2.53 2.67 2.79 2.90 3.00 mm 56.1 60.7 64.3 67.8 70.9 73.7 76.2 Diameter over Insulation Diameter over Sheath Overall Jacket Diameter in 2.78 2.98 3.15 3.30 3.43 3.55 3.67 mm 70.6 75.7 80.0 83.7 87.1 90.2 93.2 in 3.06 3.26 3.43 3.58 3.71 3.83 3.95 mm 77.7 82.8 87.1 90.8 94.2 97.3 100.3 Total Weight lbs/ft 3.2 3.6 4.1 4.5 4.9 5.3 5.7 Min. Bending Radius (install/perm.) in 61/46 65/49 69/51 72/54 74/56 77/57 79/59 Maximum Pulling Tension lbs 3,000 4,500 6,000 7,500 9,000 10,500 12,000 in 126x95 126x95 126x95 126x95 126x95 150x95 150x95 ft 3,000 3,000 3,000 3,000 2,950 3,000 3,000 Conductor Shield kV/mm 3.9 3.7 3.5 3.4 3.4 3.3 3.3 Insulation Shield kV/mm 1.6 1.7 1.7 1.8 1.8 1.8 1.8 Conductor kA 33.8 50.8 67.7 84.6 101.5 118.5 135.4 Sheath kA 38 40.7 43 45 46.9 48.6 50.1 DC @ 20o C Ω/kft 0.035 0.023 0.017 0.014 0.012 0.010 0.009 69 kV Power Cables Dimensional Typical Shipping Reel Size Flange x Traverse Shipping Reel Capacity 1 Electrical Electrical Stress @ Uo Conductor Resistance DC @ 90 C Ω/kft 0.044 0.030 0.022 0.018 0.015 0.013 0.011 Capacitance pF/ft 43.8 49.5 54.2 58.4 62.1 65.5 68.7 Charging Current Amps/ kft 0.66 0.74 0.81 0.88 0.93 0.98 1.03 Amps 470 580 680 770 840 910 970 Power Rating MVA 57 70 82 93 101 109 116 Typical Double Ductbank3 Amps 400 500 580 650 710 770 820 Power Rating MVA 48 60 70 78 85 93 98 o Ampacity @ 90o C Typical Single Ductbank 1 2 3 per circuit 3 Increased shipping reel capacity can be accommodated on request. Declared values for 50 mils aluminum sheath. Thicker sheath can accommodate more current. 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded 10 Traditional Wall 650 mil XLPE Aluminum Corrugated Sheath Short Circuit for 0.5s2 69 kV Power Cables 69 kV XLPE Aluminum Conductor SW Standard Wall XLPE Aluminum Corrugated Sheath Cable Construction •Reverse Concentric Stranded Aluminum, Compressed Conductor •Super Smooth Conductor Shield •Super Clean XLPE Insulation •430 mil XLPE minimum •True Triple Extrusion and Dry Cured •Firmly Bonded Insulation Shield •Welded Aluminum Corrugated Sheath •Polyethylene Jacket with Extruded SemiConductive Outer Layer Cable Data Voltage Characteristics (kV) Max Voltage Rating 72.5 BIL Rating 350 Temperatures ( C) o Nominal Conductor 90 Max. Emergency Conductor 105 Short Circuit Conductor 250 Minimum Installation -10 Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 120 kV / 15 min. 0.0005 2.3 11 Section 2 Conductor Size in kcmil 500 750 1000 1250 1500 1750 2000 Nominal Conductor Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 Insulation Thickness mils 520 490 470 450 450 440 430 mm 13.2 12.4 11.9 11.4 11.4 11.2 10.9 Diameter over Insulation Diameter over Sheath Overall Jacket Diameter in 1.95 2.07 2.18 2.27 2.39 2.48 2.56 mm 49.5 52.6 55.4 57.7 60.7 63.0 65.0 in 2.47 2.61 2.73 2.83 2.96 3.06 3.15 mm 62.7 66.3 69.3 71.9 75.2 77.7 80.0 in 2.75 2.89 3.01 3.11 3.24 3.34 3.43 mm 69.9 73.4 76.5 79.0 82.3 84.8 87.1 Total Weight lbs/ft 2.7 3.0 3.4 3.7 4.1 4.4 4.7 Min. Bending Radius (install/perm.) in 55/41 58/43 60/45 62/47 65/49 67/50 69/51 Maximum Pulling Tension lbs 3,000 4,500 6,000 7,500 9,000 10,500 12,000 Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 126x95 126x95 Shipping Reel Capacity1 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000 kV/mm 4.5 4.5 4.5 3.4 4.5 4.5 4.5 kV/mm 2.1 2.4 2.6 1.8 2.8 2.9 3.0 Conductor kA 33.8 50.8 67.7 84.6 101.5 118.5 135.4 Sheath kA 33.8 35.6 37.3 38.7 40.5 41.8 43.1 DC @ 20o C Ω/kft 0.035 0.023 0.017 0.014 0.012 0.010 0.009 DC @ 90o C Ω/kft 0.044 0.030 0.022 0.018 0.015 0.013 0.011 Capacitance pF/ft 51.1 60.6 68.9 77.1 82.4 88.9 95.3 Charging Current Amps/ kft 0.77 0.91 1.04 1.16 1.24 1.34 1.43 470 590 690 780 860 920 990 69 kV Power Cables Dimensional Typical Shipping Reel Size Electrical Electrical Stress @ Uo Conductor Shield Insulation Shield Conductor Resistance Ampacity @ 90o C Typical Single Ductbank per circuit 3 Amps Power Rating MVA 57 71 83 94 103 110 119 Typical Double Ductbank3 Amps 410 510 590 660 720 780 820 Power Rating MVA 49 61 71 79 87 94 98 Increased shipping reel capacity can be accommodated on request. Declared values for 50 mils aluminum sheath. Thicker sheath can accommodate more current. 3 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded 1 2 12 SW Standard Wall XLPE Aluminum Corrugated Sheath Short Circuit for 0.5s 2 69 kV Power Cables 69 kV XLPE Copper Conductor Traditional Wall 650 mil XLPE Copper Concentric Neutrals Cable Construction •Reverse Concentric Stranded Copper, Compressed Conductor or Milliken •Super Smooth Conductor Shield •Super Clean XLPE Insulation •Traditional Wall - 650 mil XLPE •True Triple Extrusion and Dry Cured •Firmly Bonded Insulation Shield •Copper Concentric Neutrals •Polyethylene Jacket with Extruded Semi-Conductive Outer Layer Cable Data Voltage Characteristics (kV) Max Voltage Rating 72.5 BIL Rating 350 Temperatures ( C) o Nominal Conductor 90 Max. Emergency Conductor 105 Short Circuit Conductor 250 Minimum Installation -10 Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 120 kV / 15 min. 0.0005 2.3 13 Section 2 Conductor Size in kcmil1 500 750 1000 1250 1500 1750 2000 2500 3000 3500 4000 Nominal Conductor Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21 mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1 in 2.21 2.39 2.53 2.67 2.79 2.90 3.00 3.18 3.34 3.5 3.63 mm 56.1 60.7 64.3 67.8 70.9 73.7 76.2 80.8 84.9 88.9 92.2 in 2.56 2.74 2.88 3.02 3.14 3.25 3.35 3.53 3.69 3.84 3.98 mm 65.0 69.6 73.2 76.7 79.8 82.6 85.1 89.6 93.7 97.6 101.1 in 2.86 3.04 3.18 3.32 3.44 3.55 3.66 3.83 3.99 4.15 4.28 (mm) 72.6 77.2 80.8 84.3 87.4 90.2 93.0 97.4 101.4 105.4 108.7 Diameter over Insulation Diameter over Neutrals Overall Jacket Diameter Total Weight lbs/ft 4.2 5.2 6.1 7.1 8.0 8.9 9.8 11.6 13.4 15.2 17 Min. Bending Radius (install/ perm.) in 57/43 61/46 64/48 66/50 69/52 71/53 73/55 77/57 80/60 83/62 86/64 Maximum Pulling Tension lbs 4,000 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000 69 kV Power Cables Dimensional Typical Shipping Reel Size in 126x95 126x95 126x95 126x95 126x95 126x95 126x95 150x95 150x95 150x95 150x95 Shipping Reel Capacity2 ft 3,000 3,000 3,000 3,000 3,000 3,000 2,950 3,000 2,700 2,400 2,150 Conductor Shield kV/mm 3.9 3.7 3.5 3.4 3.4 3.3 3.3 3.2 3.1 3.1 3.0 Insulation Shield kV/mm 1.6 1.7 1.7 1.8 1.8 1.8 1.8 1.9 1.9 1.9 1.9 Electrical Electrical Stress @ Uo Short Circuit for 0.5s3 Conductor kA 51.3 76.9 102.5 128.1 153.8 179.4 205 256.3 307.5 358.8 410 Nuetrals kA 35.6 35.6 35.6 35.6 35.6 35.6 35.6 35.6 35.6 35.6 35.6 DC @ 20o C Ω/kft 0.021 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.004 0.003 0.003 DC @ 90 C Ω/kft 0.027 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003 Capacitance pF/ft 43.8 49.5 54.2 58.4 62.1 65.5 68.7 74.4 81.4 83.7 90.3 Charging Current Amps/ kft 0.66 0.74 0.81 0.88 0.93 0.98 1.03 1.12 1.22 1.26 1.36 Ampacity @ 90o C per circuit Typical Single Ductbank4 Amps 610 760 880 980 1070 1150 1210 1456 1600 1709 1814 Power Rating MVA 73 91 106 118 128 138 145 175 192 205 217 Typical Double Ductbank4 Amps 520 640 740 830 900 960 1020 1226 1341 1432 1517 Power Rating MVA 63 77 89 100 108 115 122 147 161 172 182 Conductor Resistance o 2500-4000 kcmil conductors are 5 segment Milliken conductors. Increased shipping reel capacity can be accommodated on request. 3 Declared Values are for 80 x 14 AWG copper wire. Larger wires can accommodate more current. 4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded 1 2 14 Traditional Wall 650 mil XLPE Copper Concentric Neutrals Flange x Traverse 69 kV Power Cables 69 kV XLPE Aluminum Conductor Traditional Wall 650 mil XLPE Copper Concentric Neutrals Cable Construction •Reverse Concentric Stranded Aluminum, Compressed Conductor •Super Smooth Conductor Shield •Super Clean XLPE Insulation •Traditional Wall - 650 mil XLPE •True Triple Extrusion and Dry Cured •Firmly Bonded Insulation Shield •Copper Concentric Neutrals •Polyethylene Jacket with Extruded Semi-Conductive Outer Layer Cable Data Voltage Characteristics (kV) Max Voltage Rating 72.5 BIL Rating 350 Temperatures ( C) o Nominal Conductor 90 Max. Emergency Conductor 105 Short Circuit Conductor 250 Minimum Installation -10 Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 120 kV / 15 min. 0.0005 2.3 15 Section 2 Conductor Size in kcmil 500 750 1000 1250 1500 1750 2000 1.25 1.37 1.48 1.61 Nominal Conductor Diameter in 0.79 0.97 1.12 mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 in 2.21 2.39 2.53 2.67 2.79 2.90 3.00 mm 56.1 60.7 64.3 67.8 70.9 73.7 76.2 Diameter over Insulation Diameter over Neutral Overall Jacket Diameter in 2.56 2.74 2.88 3.02 3.14 3.25 3.35 mm 65.0 69.6 73.2 76.7 79.8 82.6 85.1 in 2.86 3.04 3.18 3.32 3.44 3.55 3.66 mm 72.6 77.2 80.8 84.3 87.4 90.2 93.0 Total Weight lbs/ft 3.1 4.1 4.5 4.9 5.2 5.6 6.0 Min. Bending Radius (install/perm.) in in 57/43 61/46 64/48 66/50 69/52 71/53 73/55 Maximum Pulling Tension lbs 3,000 4,500 6,000 7,500 9,000 10,500 12,000 Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 126x95 126x95 Shipping Reel Capacity1 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000 Conductor Shield kV/mm 3.9 3.7 3.5 3.4 3.4 3.3 3.3 Insulation Shield kV/mm 1.6 1.7 1.7 1.8 1.8 1.8 1.8 69 kV Power Cables Dimensional Typical Shipping Reel Size Electrical Electrical Stress @ Uo Conductor kA 33.8 50.8 67.7 84.6 101.5 118.5 135.4 Nuetrals kA 35.6 35.6 35.6 35.6 35.6 35.6 35.6 DC @ 20o C Ω/kft 0.035 0.023 0.017 0.014 0.012 0.010 0.009 DC @ 90o C Ω/kft 0.044 0.030 0.022 0.018 0.015 0.013 0.011 Capacitance pF/ft 43.9 49.5 54.2 58.4 62.1 65.5 68.7 Charging Current Amps/ kft 0.66 0.74 0.81 0.88 0.93 0.98 1.03 Amps 480 600 700 780 860 930 1000 MVA 58 72 84 94 103 112 120 Amps 410 510 590 660 730 780 830 MVA 49 61 71 79 88 94 100 Conductor Resistance Ampacity @ 90o C Typical Single Ductbank per circuit 3 Power Rating Typical Double Ductbank Power Rating 1 2 3 3 Increased shipping reel capacity can be accommodated on request. Declared Values are for 80 x 14 AWG copper wire. Larger wires can accommodate more current. 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded 16 Traditional Wall 650 mil XLPE Copper Concentric Neutrals Short Circuit for 0.5s 2 69 kV Power Cables 69 kV XLPE Copper Conductor TRADITIONAL WALL 650 MIL XLPE Copper neutrals with copper composite Laminate sheath Cable Construction •Reverse Concentric Stranded Copper, Compressed Conductor or Milliken •Super Smooth Conductor Shield •Super Clean XLPE Insulation •Traditional Wall - 650 mil XLPE •True Triple Extrusion and Dry Cured •Firmly Bonded Insulation Shield •Copper Concentric Neutrals with Copper Composite Laminate Sheath •Polyethylene Jacket with Extruded Semi-Conductive Outer Layer Cable Data Voltage Characteristics (kV) Max Voltage Rating 72.5 BIL Rating 350 Temperatures ( C) o Nominal Conductor 90 Max. Emergency Conductor 105 Short Circuit Conductor 250 Minimum Installation -10 Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 120 kV / 15 min. 0.0005 2.3 17 Section 2 Conductor Size in kcmil1 500 750 1000 1250 1500 1750 2000 2500 3000 3500 4000 Nominal Conductor Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 1.78 1.98 2.08 2.21 mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 45.2 50.2 52.8 56.1 in 2.21 2.39 2.54 2.67 2.79 2.90 3.00 3.18 3.34 3.5 3.63 mm 56.1 60.7 64.5 67.8 70.9 73.7 76.2 80.8 84.8 88.9 92.2 in 2.59 2.77 2.92 3.06 3.18 3.29 3.39 3.59 3.75 3.91 4.04 mm 65.8 70.4 74.2 77.7 80.8 83.6 86.1 91.2 95.3 99.3 102.6 in 2.91 3.09 3.24 3.38 3.50 3.61 3.71 3.91 4.07 4.23 4.36 mm 73.9 78.5 82.3 85.9 88.9 91.7 94.2 99.3 103.4 107.4 110.7 Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight lbs/ft 4.5 5.5 6.5 7.4 8.4 9.3 10.2 12.1 13.8 15.7 17.5 Min. Bending Radius (install/ perm.) in 58/44 62/46 65/49 68/51 70/53 72/54 74/56 78/59 81/61 85/63 87/65 Maximum Pulling Tension lbs 4,000 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000 69 kV Power Cables Dimensional Typical Shipping Reel Size Flange x Width in 126x95 126x95 126x95 138x95 138x95 138x95 150x95 150x95 150x95 150x95 150x95 Shipping Reel Capacity2 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000 3,000 2,650 2350 2100 Conductor Shield kV/mm 3.9 3.7 3.5 3.4 3.4 3.3 3.3 3.2 3.1 3.1 3.0 Insulation Shield kV/mm 1.6 1.7 1.7 1.8 1.8 1.8 1.8 1.9 1.9 1.9 1.9 Electrical Electrical Stress @ Uo Conductor kA 51.3 76.9 102.5 128.1 153.8 179.4 205 256.3 307.5 358.8 410 Sheath kA 42.3 42.8 43.2 43.5 43.9 44.1 44.4 44.9 45.4 45.8 46.1 DC @ 20o C Ω/kft 0.021 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.004 0.003 0.003 DC @ 90 C Ω/kft 0.027 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003 Capacitance pF/ft 43.8 49.5 54.2 58.4 62.1 65.5 68.7 74.4 81.4 83.7 90.3 Charging Current Amps/ kft 0.66 0.74 0.81 0.88 0.93 0.98 1.03 1.12 1.22 1.26 1.36 Ampacity @ 90o C per circuit Typical Single Ductbank4 Amps 610 760 880 980 1070 1150 1210 1456 1600 1709 1814 Power Rating MVA 73 91 106 118 128 138 145 175 192 205 217 Typical Double Ductbank4 Amps 520 640 740 830 900 960 1020 1226 1341 1432 1517 Power Rating MVA 63 77 89 100 108 115 122 147 161 172 182 Conductor Resistance o 2500-4000 kcmil conductors are 5 segment Milliken conductors. Increased shipping reel capacity can be accommodated on request. 3 Declared values for 80 x 14 AWG copper wire screen with 6 mil copper tape shield. Larger wires can accommodate more current. 4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded 1 2 18 Traditional Wall 650 Mil XLPE Copper Neutrals with Copper Composite Laminate Sheath Short Circuit for 0.5s3 69 kV Power Cables 69 kV XLPE Copper Conductor SW Standard Wall XLPE Copper neutrals with copper composite laminate sheath Cable Construction •Reverse Concentric Stranded Copper, Compressed Conductor or Milliken •Super Smooth Conductor Shield •Super Clean XLPE Insulation •430 mil XLPE minimum •True Triple Extrusion and Dry Cured •Firmly Bonded Insulation Shield •Copper Neutrals with Copper Composite Laminate Sheath •Polyethylene Jacket with Extruded Semi-Conductive Outer Layer Cable Data Voltage Characteristics (kV) Max Voltage Rating 72.5 BIL Rating 350 Temperatures ( C) o Nominal Conductor 90 Max. Emergency Conductor 105 Short Circuit Conductor 250 Minimum Installation -10 Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 120 kV / 15 min. 0.0005 2.3 19 Section 2 Conductor Size in kcmil1 500 750 1000 1250 1500 1750 2000 2500 3000 3500 4000 Nominal Conductor Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 1.78 1.98 2.08 2.21 mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 45.2 50.2 52.8 56.1 mils 520 490 470 450 450 440 430 430 440 450 450 mm 13.2 12.4 11.9 11.4 11.4 11.2 10.9 10.9 11.2 11.4 11.4 in 1.95 2.07 2.18 2.27 2.39 2.48 2.56 2.74 2.92 3.1 3.23 mm 49.5 52.5 55.4 57.7 60.7 63.0 65.0 69.6 74.2 78.7 82.0 in 2.33 2.45 2.56 2.66 2.78 2.87 2.95 3.16 3.41 3.51 3.64 mm 59.3 62.2 65.0 67.4 70.5 72.8 74.9 80.3 86.6 89.1 92.5 Overall Jacket Diameter in 2.65 2.77 2.88 2.98 3.10 3.19 3.27 3.48 3.73 3.83 3.96 mm 67.3 70.4 73.2 75.7 78.6 80.9 83.0 88.4 94.7 97.2 100.6 Total Weight lbs/ft 4.9 6.0 6.3 7.1 8.0 8.9 9.7 11.7 13.5 15.4 17.1 Min. Bending Radius (install/ perm.) in 53/40 55/42 58/43 60/45 62/46 64/48 65/49 70/52 75/56 77/57 79/59 Maximum Pulling Tension lbs 4,000 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000 Insulation Thickness Diameter over Insulation Diameter over Sheath 69 kV Power Cables Dimensional Typical Shipping Reel Size Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 126x95 126x95 138x95 150x95 150x95 150x95 Shipping Reel Capacity2 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000 3,000 2,800 2,500 2,200 Conductor Shield kV/mm 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.3 4.2 4.1 Insulation Shield kV/mm 2.1 2.4 2.6 2.7 2.8 2.9 3.0 3.0 3.0 3.0 3.0 Electrical Electrical Stress @ Uo Conductor kA 51.3 76.9 102.5 128.1 153.8 179.4 205 256.3 307.5 358.8 410.0 Sheath kA 41.7 42 42.3 42.5 42.8 43.1 43.3 43.8 44.5 44.7 45.1 DC @ 20o C Ω/kft 0.021 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.004 0.003 0.003 Conductor Resistance DC @ 90 C Ω/kft 0.027 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003 Capacitance pF/ft 51.1 60.6 68.9 77.1 82.4 88.9 95.3 103.8 112.1 113.3 119.24 Charging Current Amps/ kft 0.77 0.91 1.04 1.16 1.24 1.34 1.43 1.56 1.68 1.702 1.791 Ampacity @ 90o C per circuit Typical Single Ductbank4 Amps 620 770 900 1010 1100 1180 1250 1471 1609 1730 1836 Power Rating MVA 75 93 108 121 132 142 150 176 193 207 220 Typical Double Ductbank4 Amps 520 640 740 830 900 960 1010 1235 1346 1444 1530 Power Rating MVA 63 77 89 100 108 115 121 148 161 173 183 o 1 2 2500-4000 kcmil conductors are 5 segment Milliken conductors. Increased shipping reel capacity can be accommodated on request. Declared values for 80 x 14 AWG copper wire screen with 6 mil copper tape shield. Larger wires can accommodate more current. 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded 3 4 20 standard wall xlpe Copper Neutrals with Copper Composite Laminate Sheath Short Circuit for 0.5s3 69 kV Power Cables 69 kV XLPE Aluminum Conductor Traditional Wall 650 mil XLPE Copper neutrals with aluminum composite laminate sheath Cable Construction •Reverse Concentric Stranded Aluminum, Compressed Conductor •Super Smooth Conductor Shield •Super Clean XLPE Insulation •Traditional Wall - 650 mil XLPE •True Triple Extrusion and Dry Cured •Firmly Bonded Insulation Shield •Copper Neutrals with Aluminum Composite Laminate Sheath •Polyethylene Jacket with Extruded Semi-Conductive Outer Layer Cable Data Voltage Characteristics (kV) Max Voltage Rating 72.5 BIL Rating 350 Temperatures ( C) o Nominal Conductor 90 Max. Emergency Conductor 105 Short Circuit Conductor 250 Minimum Installation -10 Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 120 kV / 15 min. 0.0005 2.3 21 Section 2 Conductor Size in kcmil 500 750 1000 1250 1500 1750 2000 1.25 1.37 1.48 1.61 Nominal Conductor Diameter in 0.79 0.97 1.12 mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 in 2.21 2.39 2.54 2.67 2.79 2.90 3.00 mm 56.1 60.7 64.4 67.8 70.9 73.7 76.2 Diameter over Insulation Diameter over Sheath Overall Jacket Diameter in 2.60 2.78 2.93 3.06 3.18 3.29 3.39 mm 66.0 70.5 74.3 77.7 80.7 83.5 86.1 in 2.92 3.10 3.25 3.38 3.50 3.61 3.71 mm 74.1 78.7 82.4 85.8 88.9 91.7 94.2 Total Weight lbs/ft 3.7 4.2 4.7 5.1 5.5 5.8 6.2 Min. Bending Radius (install/perm.) in 58/44 62/46 65/49 68/51 70/52 72/54 74/56 Maximum Pulling Tension lbs 3,000 4,500 6,000 7,500 9,000 10,500 12,000 Flange x Width in 126x95 126x95 126x95 138x95 138x95 138x95 150x95 Shipping Reel Capacity1 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000 Conductor Shield kV/mm 3.9 3.7 3.5 3.4 3.4 3.3 3.3 Insulation Shield kV/mm 1.6 1.7 1.7 1.8 1.8 1.8 1.8 Conductor kA 33.8 50.8 67.7 84.6 101.5 118.5 135.4 Sheath kA 41.6 42 42.3 42.6 42.9 43.1 43.4 DC @ 20o C Ω/kft 0.035 0.023 0.017 0.014 0.012 0.010 0.009 DC @ 90o C Ω/kft 0.043 0.028 0.021 0.017 0.014 0.012 0.011 Capacitance pF/ft 43.9 49.5 54.2 58.4 62.1 65.5 68.7 Charging Current Amps/ kft 0.66 0.74 0.81 0.88 0.93 0.98 1.03 Amps 480 600 700 780 860 930 1000 MVA 58 72 84 94 103 112 120 Amps 410 510 590 660 730 780 830 MVA 49 61 71 79 88 94 100 69 kV Power Cables Dimensional Typical Shipping Reel Size Electrical Electrical Stress @ Uo Short Circuit for 0.5s 2 Ampacity @ 90o C Typical Single Ductbank per circuit 3 Power Rating Typical Double Ductbank Power Rating 3 Increased shipping reel capacity can be accommodated on request. Declared values for 80 x 14 AWG copper wire screen with 8 mil aluminum tape shield. Larger wires can accommodate more current. 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded 1 2 3 22 traditional wall 650 mil xlpe Copper Neutrals with aluminum Composite Laminate Sheath Conductor Resistance 69 kV Power Cables 69 kV XLPE Aluminum Conductor SW Standard Wall XLPE copper neutrals with aluminum laminate sheath Cable Construction •Reverse Concentric Stranded Aluminum, Compressed Conductor •Super Smooth Conductor Shield •Super Clean XLPE Insulation •430 mil XLPE minimum •True Triple Extrusion and Dry Cured •Firmly Bonded Insulation Shield •Copper Neutrals with Aluminum Composite Laminate Sheath •Polyethylene Jacket with Extruded Semi-Conductive Outer Layer Cable Data Voltage Characteristics (kV) Max Voltage Rating 72.5 BIL Rating 350 Temperatures ( C) o Nominal Conductor 90 Max. Emergency Conductor 105 Short Circuit Conductor 250 Minimum Installation -10 Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 120 kV / 15 min. 0.0005 2.3 23 Section 2 Conductor Size in kcmil 500 750 1000 1250 1500 1750 2000 Nominal Conductor Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 Insulation Thickness mils 520 490 470 450 450 440 430 mm 13.2 12.4 11.9 11.4 11.4 11.2 10.9 Diameter over Insulation Diameter over Sheath Overall Jacket Diameter in 1.95 2.07 2.18 2.27 2.39 2.48 2.56 mm 49.5 52.5 55.3 57.7 60.7 63.0 65.1 in 2.34 2.46 2.57 2.66 2.78 2.87 2.95 mm 59.4 62.4 65.2 67.5 70.6 72.9 75.0 in 2.66 2.78 2.89 2.98 3.10 3.19 3.27 mm 67.5 70.5 73.3 75.7 78.7 81.0 83.1 Total Weight lbs/ft 3.3 3.7 4.0 4.3 4.7 5.0 5.3 Min. Bending Radius (install/perm.) in 53/40 56/42 58/43 60/45 62/46 64/48 65/49 Maximum Pulling Tension lbs 3,000 4,500 6,000 7,500 9,000 10,500 12,000 in 126x95 126x95 126x95 126x95 126x95 138x95 138x95 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000 Conductor Shield kV/mm 4.5 4.5 4.5 4.5 4.5 4.5 4.5 Insulation Shield kV/mm 2.1 2.4 2.6 2.7 2.8 2.9 3.0 Conductor kA 33.8 50.8 67.7 84.6 101.5 118.5 135.4 Sheath kA 41 41.2 41.5 41.7 42 42.2 42.4 DC @ 20o C Ω/kft 0.035 0.023 0.017 0.014 0.012 0.010 0.009 DC @ 90o C Ω/kft 0.043 0.028 0.021 0.017 0.014 0.012 0.011 Capacitance pF/ft 51.1 60.6 68.9 77.1 82.4 88.9 95.3 Charging Current Amps/ kft 0.77 0.91 1.04 1.16 1.24 1.34 1.43 Amps 485 608 712 803 884 957 1023 MVA 58 73 86 96 106 115 123 Amps 408 507 590 661 724 780 829 MVA 49 61 71 79 87 94 100 69 kV Power Cables Dimensional Typical Shipping Reel Size Flange x Traverse Shipping Reel Capacity 1 Electrical Electrical Stress @ Uo Short Circuit for 0.5s2 Conductor Resistance Typical Single Ductbank per circuit 3 Power Rating Typical Double Ductbank Power Rating 3 Increased shipping reel capacity can be accommodated on request. Declared values for 80 x 14 AWG copper wire screen with 8 mil aluminum tape shield. Larger wires can accommodate more current. 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded 1 2 3 24 standard wall xlpe Copper Neutrals with Aluminum Composite Laminate Sheath Ampacity @ 90o C