Presentation, description Safety automation solutions 0 Preventa safety PLCs Modular, type XPS MF60 “In rack” relay output module Presentation The relay output module XPS MFDO801 is designed to meet SIL 3 requirements of standard IEC 61508 and category 4 requirements conforming to EN 954-1/ ISO 13849-1. b It incorporates 8 relay safety outputs (3.15 A fuse) that are configurable using programming software XPSMFWIN. b The module can be installed in rack XPS MFGEH01 as many times as required in the six slots available. Functional synoptic Relay outputs 1 to 8 3.15 A 3.15 A 8 1 RUN ERR & Test & T T I/O bus (back plane bus of rack XPS MFGEH01) 1 2 3 T L+ Self-monitoring or “Watchdog” Description On the front face of the module: 1 Two process status LEDs (RUN, ERR). 2 Eight output status LEDs. 3 Eight removable screw terminal blocks (2 terminals per block) for connection of outputs (1). 4 Grip to assist installation/removal. On the rear: 5 Terminals for automatic electrical connection to the back plane bus of rack XPS MFGEH01. 5 LED details LED RUN 4 2 Colour Green Status On Off On Description Voltage present. No voltage. ERR Red Module defect or external error, diagnostics response. Off No error regarding the module or on the channels. (1) The connection of cables to captive screw terminal blocks that are both removable and guide marked avoids all connection errors when, for example, carrying out maintenance. Terminal blocks included with module. 38811-EN_Ver2.0.indd Characteristics, references, connections Safety automation solutions 0 Preventa safety PLCs Modular, type XPS MF60 “In rack” relay output module Characteristics Output module type Supply XPS MFDO801 Voltage V XPS MFPS01 - 15…+ 20% Voltage limits Ambient air temperature conforming to EN 61131-2 Number and type of outputs Relay Operating Storage Type Degree of protection Contact material Switching time Reset time Bounce time Mechanical life Electrical durability Switching voltage Switching capacity Operational data LED display Connections °C °C ms ms ms V Switching current c 24, supplied by rack XPS MFGEH01 incorporating power supply module 0…+ 50 (1) - 40…+ 85 8 relay outputs, volt-free, with N/O contact 2 safety relays with positively guided contacts IP 40 Silver alloy, gold flashed 30 approx. 20 approx. 30 approx. u 10 million operating cycles u 250 000 operating cycles on full load (resistive) and y 0.1 operating cycles/s a 6 V…230 V / c 110 V 3.15 A with internal fuse Breaking capacity 100 A VA max., cos φ= 1 y700 30 V: 95 W max. (3.15 A) yc 70 V: 40 W max. (0.5 A) yc c 110 V: 33 W max. (0.315 A) With suitable external fuse c 3.3 V / 0.2 A, c 24 V ± 10% (1) / 0.7 A Yes Shielded dual twisted pair cable recommended to provide protection against electromagnetic interference, or Ø 12 mm max. cable with connection to earth of rack XPS MFGEH01 (1) Limited system data. A a.c. d.c. (non inductive) References Description Output module Characteristics Reference 8 relay outputs XPS MFDO801 a 6 V…230 V / c 110 V Weight kg 0.600 Connections A B C Item A Connection Relay output Screw Function 1 Contact 1, terminal A Contact 1, terminal B Contact 2, terminal A Contact 2, terminal B Contact 3, terminal A Contact 3, terminal B Contact 4, terminal A Contact 4, terminal B Contact 5, terminal A Contact 5, terminal B Contact 6, terminal A Contact 6, terminal B Contact 7, terminal A Contact 7, terminal B Contact 8, terminal A Contact 8, terminal B 02 B Relay output D 03 2 04 E C F D Relay output 05 3 06 Relay output 07 4 08 G H Screw N° 01 E Relay output 09 5 10 F Relay output 11 6 12 G XPS MFDO801 Relay output 13 H Relay output 15 16 38811-EN_Ver2.0.indd 7 14 8 3