Panelboards and Lighting Control Pow-R-Command 10.6 Contents Pow-R-Command Family Description Page Product Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Command 4000 (PRC4000) . . . . . . . . . . . . . . . . . . . Pow-R-Command 2000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 1000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 750 Panelboard . . . . . . . . . . . . . . . . . . . . PRC100 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC100EC Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC50 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC25 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 451 453 454 457 460 463 467 470 473 10 10 10 10 10 10 10 An Eaton Green Solution 10 10 10 10 Product Overview Eaton’s Pow-R-Command™ family of lighting control panelboards is designed to meet the lighting control needs for buildings of all sizes and complexity. The system incorporates microprocessorbased distributed intelligence within a traditional panelboard, simplifying wiring in the field. The system can be networked over customers’ LAN or directly interfaced to the Internet, allowing for password protected web access. The panelboard design allows the Pow-R-Command lighting control system to meet shortcircuit ratings, as required by the National Electrical Code (NEC). The Pow-R-Command panelboard mounting, power wiring and branch wiring are the same as in traditional panelboards. Depending on the controller model, PRC controllers can be applied to distribution systems rated single-phase three-wire and three-phase four-wire 120, 120/240, 208Y/120 and 480Y/277 Vac. The PRC family consists of the PRC2000, PRC1000, PRC750, PRCEP, PRC100, PRC50 and the PRC25 for panelboard installations and the PRC4000 building control devices, which have wireless communications. Lighting Control Overview Traditional lighting control employs lighting contactors or relay panels to turn groups of lighting on or off. Input devices are typically time clocks, photo cells, wall switches, or, in more sophisticated applications, contact inputs from a building automation system (BAS). Pow-R-Command is a lighting control panelboard with remote controllable circuit breakers. These controllable circuit breakers perform a dual function: 1. They provide the overcurrent and overload protection for the circuit. 2. They perform the same function as relays and contactors in traditional lighting control systems, opening and closing the circuit in response to a remote signal. Design Considerations Short-Circuit Protection: In the past, contactors or relay panels were mounted close to the lighting load and shortcircuit ratings were not a major concern. Today, most of the lighting control devices are located in electrical rooms, often adjacent to the panelboards that feed them. These devices are subjected to short-circuit conditions almost as high as those of the electrical distribution equipment. The current version of the National Electrical Code requires that these lighting control devices carry a short-circuit rating (Article 110-10). Although some traditional lighting control components are available with short-circuit ratings, these ratings are limited and may require upstream fusing. A lighting control panelboard makes meeting the requirements of NEC 110-10 as simple as specifying the short-circuit rating of the panelboard. Retrofit Applications: Retrofitting traditional lighting control methods into an existing electrical distribution system often requires extensive rewiring and unwanted downtime. In most cases, a Pow-R-Command panel interior can be installed into an existing panelboard back box, and the cables can be re-terminated on the new circuit breakers, with minimal downtime. 10 10 10 10 10 10 10 10 Flexibility: Lighting control panelboards allow simple and inexpensive changes during startup. Contactor and relay panels often require rewiring to make changes in the field. 10 10 10 Choices: Eaton’s lighting control panelboards offer varying levels of flexibility, from six zones per panel with the Pow-R-Command 25 up to 250 zones per panel with the Pow-R-Command 2000. 10 10 10 Space: Lighting control panelboards eliminate contactor panels and/or relay panels, freeing up valuable wall space. Pow-R-Command panels are the same width as standard panelboards. Volume 2—Commercial Distribution CA08100003E—December 2010 10 10 10 10 10 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 447 10.6 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 Panelboards and Lighting Control Pow-R-Command Installation Considerations Simplicity: Lighting control panelboards are as easy to install as standard panelboards. There are no additional components to install. Labor: Because contactors and relays are eliminated, the labor associated with installing them and the additional cables and conduit associated with them is eliminated. Startup: Startup for the PowR-Command panelboards is straightforward. The PRC25 requires no startup. It is prewired at the factory. The PRC100 is provided with factory startup assistance for trouble-free installation. The PRC750 is provided with an LCD display and keypad for on-site programming. The PRC1000 and PRC2000 are programmed over the network. They have an optional display available for local interface. Operational Considerations Failure Modes: If a lighting contactor or relay fails to operate due to a mechanical or control system failure, it is very difficult to control the lights manually. Often, it is necessary to hard-wire around the device on a temporary basis. With a lighting control panelboard system, the circuit breaker can be manually switched on or off as necessary until the system is back in operation. Flexibility: In many cases, the lighting control scheme may change over the life of the facility. With traditional lighting control methods, changes require major rewiring and facility downtime. Breaker control schemes can be changed within the lighting control panelboard, often with a simple modification through software. 10 10 10 448 Pow-R-Command 4000 (PRC4000) The Power-R-Command 4000 wireless lighting control system is a robust wireless communication system that can be utilized in new and retrofit applications. The wireless system components consist of the Pow-RCommand 4000 (PRC4000) controller, the Pow-RCommand Wireless I/O Module (PRCWIOM) and the Pow-R-Command Wireless Switch (PRCWS). It has a multitude of advanced features that perform the seamless control of every zone in your entire facility, as well as complex energymanagement tasks. Basic programming of the PRC4000 is done through a standard Web page interface including the scheduling, status and override. Pow-R-Command 2000 (PRC2000) Eaton’s PRC2000 is a microprocessor-based programmable lighting control system that can be used to control all of the lighting in your industrial facilities, high-rise office buildings and airports. Being on the cutting edge of technology, the Pow-RCommand 2000 is an IPbased device with an embedded Web server. Capable of being utilized in both standalone and networkable applications, the PRC2000 can incorporate both standard branch mounted breakers and controllable thermal-magnetic breakers for tailored control. The System Controller also includes load override, holiday scheduling, one-shot or event schedules, off warning to tenants, memory loss protection, hardware diagnostics and real-time clock for optimal energy management functions. The PRC2000 also incorporates the ability to communicate with networked devices over the Building Automation and Control Network (BACnet®) protocol. BACnet is an industry standard protocol and provides increased flexibility in component and device selection for the control system. Pow-R-Command 1000 (PRC1000) Eaton’s PRC1000 is a microprocessor-based programmable lighting control system. With ratings from 100–225A, the PRC1000 can be used as a standalone panelboard or networked as a system. The panelboard utilizes both branch mounted standard breakers through 100A, and controllable thermal-magnetic breakers controlled by the Pow-R-Command 1000 System Controller. The System Controller also includes load override, holiday scheduling, one-shot or event schedules, off warning to tenants, memory loss protection, hardware diagnostics and real-time clock for optimal energy management functions. The PRC1000 system contains networkable intelligence and provides automated switching of branch circuit breakers. Advanced Control Devices The PRC2000 and PRC1000 controller has an onboard Digital Switch Network (DSN) that provides interaction with the Pow-R-Command Digital Switches. The Pow-RCommand Digital Switch (PRCDS) is a state-of-the-art microprocessor-based low voltage device. Each PRCDS is completely customizable and can be programmed to meet the needs of the customer’s lighting control strategy. This programming is stored directly in the switch’s integrated memory, which adds to the reliability of the digital switch network. Each switch has the ability to communicate directly to a PRC1000 or PRC2000 lighting controller through a dedicated switch network. In addition to its network communication capabilities, the PRCDS has built-in inputs and outputs that allow the connection of photo sensors, occupancy sensors and dimmable Volume 2—Commercial Distribution CA08100003E—December 2010 ballasts to achieve a fully integrated zone lighting control from one device. Each PRC controller can have up to 99 digital switches connected to its DSN using CAT6 cable. This gives distributed control throughout the entire facility at a much lower cost of installation. In addition, there is local feedback through a status LED illuminated in each button on the switch. The Pow-R-Command Low Voltage Switch (PRCLS) is a momentary dry contact switch that is used for inputs into the Pow-R-Command controllers. This simple switch does not need a power supply; it is connected directly between the digital or universal inputs and its common of the PRC controller. This provides the ability to have up to six individual switches in one standard switch location. Both the PRCDS and PRCLS are offered in three configurations, a 2-button, 4button or 6-button. In addition, each configuration is offered in three colors, Black, White or Almond. Pow-R-Command 750 (PRC750) Designed for standalone applications, Eaton’s PRC750 is a premier microprocessorbased lighting control system that can be used to control all of the lighting in your industrial facilities, high-rise office buildings and airports. A single PRC750 panelboard can be connected to a maximum of three expansion panelboards for the ability to control up to a total of 168 Smart Breakers™. The PRC750 also boasts load override, holiday scheduling, memory loss protection, astronomical time clocks and scheduling, 16 switch inputs, and alarm and message log features. www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Panelboards and Lighting Control Pow-R-Command Pow-R-Command Expansion Panelboard (PRCEP) The PRCEP is a slave panelboard designed to work in conjunction with the PRC750, PRC1000 and PRC2000 controller. The PRCEP is configured the same as a standard panelboard, but has PRC Breaker Control Bus (BCB) units installed that communicate to the PRC controller. To aid in cost reduction in some applications, there can be controllable and standard breakers installed in the panelboard, and the panelboard can be configured with a BCB on the left, the right or on both sides of the panelboard for a more custom solution. The PRC controller has the ability to control up to eight BCBs in any of the various PRCEP configurations. The PRCEP breaker compatibility is the same as the PRC controller panelboards and the layout and sizing rules are the same as a standard 1A/2A panelboard. Pow-R-Command 100 (PRC100) Eaton’s PRC100 panelboard system offers the broadest range of energy control in the industry using standalone PRC100 panelboards or a network of PRC100 panelboards. The PRC100 system is ideal for large, medium and small facilities with lighting control systems that require frequent changes, networkable panelboards, remote access, or all of the above. There are applicationspecific controllers available such as the native Johnson Controls® Metasys® (JCI) and the native Modbus® controllers. Examples may include stadiums, auditoriums and theatres, office buildings, large retailers and schools. Pow-R-Command 50 (PRC50) The PRC50 panelboard is a PRC100 panelboard with additional programming capability added that provides the ability to group up to 42 remotely operated circuit breakers into 8 individual zones. Each zone is designed to be switched by a dry contact from an external time clock, switch or Interposing relay. The PRC50 programming board included with the controller allows the breakers to be grouped locally without the need of special equipment or software. The groupings can be easily changed without the need of any field rewiring. The grouping configurations are made using simple pushbutton inputs. The panelboards are available with a full line of ratings and accessories. Pow-R-Command 25 (PRC25) Eaton’s PRC25 Panelboard replaces contactors and relay panels in lighting control and other load switching systems. It is the most basic and cost-effective way to remotely control loads. The PRC25 is ideal for any building that requires a fixed lighting control scheme with a low installed cost. Examples may include small commercial buildings, tenant spaces, and other light commercial facilities. Pow-R-Command 100 Universal System Controller (PRC100 USC) The heart of the PRC100 panelboard is the Universal System Controller. Integral to the panelboard, this controller provides the PRC100 panelboard with distributed intelligence to control solenoid operated circuit breakers. The controller has the ability to communicate with other panelboard mounted controllers using a shielded twisted pair network cable. To further support system integrations, the PRC100 is also available in two additional native protocol versions that are installed in the PRC100 panelboard. The PRC100MOD is a native Modbus protocol controller that can be integrated easily into an existing or new Modbus system. Also available is the PRCJCI, a native JCI Metasys protocol controller, which is used in new or existing JCI system integrations. Pow-R-Command PRC100 Panelboard Standard Features ● Time-of-Day scheduling— Each breaker may be individually time scheduled ● Holiday scheduling ● Astronomical scheduling ● Memory loss protection ● Real-time clock ● Hardware diagnostics ● Power failure recovery ● Brownout recovery ● Alarms and alarm log ● Local programming port ● Network communications port ● Breaker bypass On/Off and restore buttons ● Lights-off warning ● Load priority management ● Plug-and-play installation ● Data logging ● 12 dry contact switch inputs Pow-R-Command PRC100 Panelboard Network Should more than one panelboard be required for a facility, Pow-R-Command panelboards can be networked to form a system. This allows each panelboard to communicate with each other and to a central computer over a shielded twisted pair network cable. Pow-R-Command PRC100 Panelboard Optional Features: The Pow-R-Command PRC100 panelboard may be ordered with an optional factory-installed Expansion Chassis in addition to the factory-installed Universal System Controller. The optional Expansion Chassis houses up to two PRC100 Application Specific Controllers (ASC), which may be field installed. The addition of the optional Expansion Chassis and Application Specific Controllers to the standard PRC100 panelboard will extend the functionality of the PRC100 panelboard beyond time-of-day power Volume 2—Commercial Distribution CA08100003E—December 2010 10.6 switching. 10 PRC100 Application Specific Controllers Eaton’s Pow-R-Command Application Specific Controllers (ASCs) are designed to expand the PRC100 panelboard system beyond time-of-day power switching requirements. The controllers may be plugged into the PRC100EC panelboard and the PRC100SCC Control Cabinet. 10 10 10 10 10 10 10 10 10 10 10 10 10 PRC100SCC Control Cabinet with Application Specific Controllers Switch Override Controller (PRC100SOC) The Switch Override Controller provides the ability to connect and monitor up to 48 dry contact closures from wall switches, occupancy sensors, photocells, building automation system relay contacts or any remotely mounted device with a dry contact relay. Input connections to the controller are self powered with 28 Vac and may be individually custom programmed to operate differently. It is possible to program any connected input to control any breaker or group of breakers in the panelboard or system. Inputs have adjustable priorities and are capable of being individually time schedule enabled for different days of the week. 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 449 10.6 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 Panelboards and Lighting Control Pow-R-Command Telephone Override Controller (PRC100TOC) The Telephone Override Controller provides a voice prompted method for On/Off override control of lighting. The telephone override controller is connected the same as an extension telephone. Simply plug it into a local analog telephone extension wall jack. The telephone override controller allows voice prompted control of lighting circuits for up to 1000 individual users. It is possible to program any of the 1000 users to override any breaker, or group of breakers in the panelboard, or system on or off during scheduled or non-scheduled hours, using any touch-tone telephone. Remote Access Controller (PRC100RAC) Allows programming and monitoring of the Pow-RCommand system from a remote location using a personal computer with a modem. The RAC is ideal for multi-location systems, such as campus and chain stores. Only one RAC is required per system to accomplish this task. The system can be designed to allow various levels of access. All programming and monitoring functions are available from the central location. PRC100 Network Interface Box (PRC100NIB) The Network Interface Box allows the central computer to be located more than 25 feet (7.6m) from the closest Pow-R-Command panelboard. The Network Interface Box comes complete with serial interface cable and power cord. PRC100 Control Cabinet The PRC100 Control Cabinet incorporates a power supply and the Universal System Controller from the PRC100 panelboard into a cabinet that may house up to three ASCs. The PRC100 Control Cabinet is ideal for retrofit applications when the existing panelboards may be reused or new construction applications where two or more panelboards requiring switched loads are located within the same electrical closet. The PRC100 Control Cabinet will control up to 48 remotely mounted circuit breakers using preterminated pigtail cables. PRC100 Setup Software (PRC100LOS) Windows®-based setup software is required for programming the PRC100 panelboard and Application Specific Controllers. PRC100 System Support Application Engineering support is available from the Pow-R-Command Applications Engineering Group located in the Sumter, SC, plant. PRC100 Field Technical Support Programming, Startup, Training and Field Service are available from a professional team of factory trained engineers. Startup services are recommended to ensure peak system performance. Online Support Available to those customers who choose Remote Access Controllers. Factory technicians can help diagnose systems, set up or change programs and troubleshoot online. 10 10 10 10 10 10 10 10 10 10 10 450 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Panelboards and Lighting Control Pow-R-Command 10.6 Product Selection Guide 10 Pow-R-Command Selection Guide 10 10 10 10 10 Controller PRC25 PRC50 PRC100 PRC750 PRC1000 PRC2000 PRC2000B Mandatory Eaton startup and integration required No No Yes No Yes Yes No Switch 6 8 4 8 8 8 8 Universal (switch or analog) 0 0 8 8 8 8 8 10 10 Inputs Optional switch input expander 0 0 48 0 48 48 48 Total inputs 6 8 64 16 64 64 64 Outputs digital (maximum controllable zones) 6 0 4 16 75 75 75 Analog 0 0 4 0 4 4 4 Universal I/O module No No Yes No Yes Yes Yes Telephone override No No Yes No Yes Yes Yes 10 10 10 Outputs Data logging No No Yes No Yes Yes Yes Remote access No No Yes No Yes Yes Yes Power supply for external devices N/A No Yes Yes Yes Yes Yes Maximum number of loads (breaker/relay) 42 42 42 168 168 168 168 Number of expansion panels 0 0 0 7 7 7 7 Manual override Yes Yes Yes Yes Yes Yes Yes 10 10 10 10 10 10 Notes Startup and Integration by Eaton is not mandatory when utilizing the PRC2000B with BACnet protocol. Each rail drives 21 breakers. Rails can be distributed individually over a total of eight panels (max. SLAN wire-length of 150 ft). 10 10 10 10 10 10 10 10 10 10 10 10 10 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 451 10.6 10 Panelboards and Lighting Control Pow-R-Command Pow-R-Command Selection Guide, continued PRC25 PRC50 PRC100 PRC750 PRC1000 PRC2000 PRC2000B Dimming No No Yes No Yes Yes Yes Maximum number of dimming ballasts 0 0 160 0 160 160 160 Daylight harvesting (using dimming ballasts) No No Yes No Yes Yes Yes Daylight switching (on/off circuit switching) Yes Yes Yes Yes Yes Yes Yes 10 Time clock No No Yes Yes Yes Yes Yes Time schedules No No Yes Yes Yes Yes Yes 10 Scheduling zones N/A N/A 75 75 75/250 75/250 75/250 10 10 10 Controller Outputs (continued) On/off periods per schedule N/A N/A 50 50 50 50 50 Holidays N/A N/A 30 30 30/16 30/16 30/16 Blink notice No No Yes Yes Yes Yes Yes Maximum override time (hrs) N/A N/A 24 24 24 24 24 RS-232 port No No No No No No No RS-485 port No No Yes No Yes Yes Yes 10 Ethernet port No No No No No Yes Yes Ethernet via external gateway No No Yes No Yes Yes Yes 10 Input/output matrix across controllers No No Yes No Yes Yes Yes Input/output matrix within controller No Yes Yes Yes Yes Yes Yes 10 Local LCD/LED display No No No Yes Option Option Option Local LED status indicators Yes Yes Yes Yes Yes Yes Yes Non-volatile program memory No Yes Yes Yes Yes Yes Yes Battery backup for program memory N/A 10 yrs 10 yrs 10 yrs 10 yrs 10 yrs 10 yrs Clock memory backup N/A 10 yrs 10 yrs 10 yrs 10 yrs 10 yrs 10 yrs 10 Flash firmware memory N/A No No Yes Yes Yes Yes 10 Modbus® ASCII/RTU N/A N/A Yes No No No N/A Modbus TCP N/A N/A No No No No N/A 10 Johnson Controls® N2 N/A N/A Yes No No No N/A BACnet N/A N/A Yes No Yes Yes Yes 10 10 10 10 10 10 10 Protocols LonWorks® N/A N/A No No No No N/A SOAP/XML N/A N/A Yes No Yes Yes N/A OPC N/A N/A Yes No Yes Yes Yes N/A No Yes No Yes Yes Yes 10 Browser Access 10 Built-in Web Server TCP/IP N/A No No N/A N/A Yes Yes 10 BACnet IP server N/A No No N/A N/A N/A Yes TCP/IP external device Standards 10 UL 916 energy management equipment Yes Yes Yes Yes Yes Yes Yes California Title 24 N/A N/A Yes Yes Yes Yes Yes NEC 110-10 — Yes Yes Yes Yes Yes Yes 10 UL 67 panelboards Yes Yes Yes Yes Yes Yes Yes CSA C22.2 #29 panelboards Yes Yes Yes Yes Yes Yes Yes 10 Baud rate N/A 9.6k 9.6k 9.6k 9.6k 9.6k 9.6k Maximum controllers/network N/A 1 120 1 1800 1800 1800 10 Password protected No No Yes Yes Yes Yes Yes Three-pole breaker housing No No No No No No No External bracket mount available Yes Yes Yes Yes Yes Yes Yes 10 Mounting 10 10 10 Notes 250 additional schedules with optional Network Interface Box NIB. 16 additional holidays with optional Network Interface Box NIB. 452 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Panelboards and Lighting Control Pow-R-Command 10.6 Contents Pow-R-Command 4000 Wireless Controller Description Page Product Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Command 4000 (PRC4000) Pow-R-Command 2000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 1000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 750 Panelboard . . . . . . . . . . . . . . . . . . . . PRC100 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC100EC Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC50 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC25 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 447 451 454 457 460 463 467 470 473 An Eaton Green Solution 10 10 10 10 10 10 10 10 10 10 10 Pow-R-Command 4000 (PRC4000) 10 Product Description The PRC4000 wireless controller is designed to act as the coordinator of the wireless lighting network; All configuration and control can be done through a standard Web browser instead of learning a new software platform. In addition, the PRC4000 is networkable with existing Pow-R-Command lighting control products over the RS-485 network to expand system capabilities. The PRC4000 also comes equipped with analog and digital inputs/outputs to accommodate an extended array of input devices, switching and dimming needs. The PRC4000 wirelessly communicates to the PRCWIOM and the PRC Wireless Switch using the IEEE®802.15.4 standard. Components ● Embedded Web server ● Integrated I/O ● PRC Wireless I/O Module ● PRC Wireless Switch PRC Wireless I/O Module The PRC4000 wireless controller offers industryleading wireless technology. Not only does it have a builtin radio to communicate wirelessly directly with each I/O module and wireless switch, but it also offers many advanced features to help coordinate your lighting network. The PRC4000 has a built-in battery-backed time clock. In addition to its advanced time-scheduling feature set, the PRC4000 also offers astronomical time scheduling that dynamically adjusts to your geographic location and time of year. With any automated system, data logging and alarm notifications are essential. To meet this need, the PRC4000 offers an integrated internal data and alarm notification system. This gives you access to valuable information that you would need to quickly see the status of your lighting system. PRC Wireless Devices PRC Wireless I/O Module (PRCWIOM) The PRCWIOM is used to segment the system and connect external inputs and loads to the system remotely. It allows local connectivity of low voltage switches, photo sensors, occupancy sensors, 0–10 Vdc dimming ballasts, and other auxiliary devices. The I/O module also adds discrete on/off load control through an onboard relay for loads up to 120/277V, 20A. Running control wires from each device in the facility back to the electrical room is no longer required. The configuration and programming is stored in the internal memory of the PRC Wireless I/O module and the PRC Wireless Switch. This allows for distributed intelligence that adds reliability to an already robust lighting control network. PRC Wireless Switch Interface Pow-R-Command line of lighting controllers through a Pow-R-Command Wireless Switch Interface (PRCWSI) unit. Each PRCWS switch is completely customizable and can be programmed to meet the needs of the customer’s lighting control strategy. The PRCWS configuration is stored directly in the integrated memory of the switch, which adds to the reliability of the device. In addition to the wireless network communication capabilities, the PRCWS has built-in input and output that are capable of connecting a photo sensor, occupancy sensor, and dimmable ballasts to achieve a fully integrated zone lighting control from one device. The wireless switch network can have up to 99 switches per controller. PRC Wireless Switch (PRCWS) PRC Wireless Switch Interface (PRCWSI) The PRC Wireless Switch is a state-of-the-art, microprocessor-based, low voltage wireless communication device that is based on the 802.15.4 wireless standard. The switch is used for local control and has the ability to communicate directly to the PRC4000 and to the standard The PRCWSI is a wireless gateway device that passes the wireless data of the PRC Wireless Switch to the PRC Digital Switch network of the PRC1000 or PRC2000 Controller. This two-way communication transfers commands from the switch as well as feedback from the controller. Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 10 10 10 10 10 10 10 10 10 10 10 10 10 453 10 10 10 10 10 10.6 10 Panelboards and Lighting Control Pow-R-Command Contents Pow-R-Command 2000 Panelboard Description 10 Page Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Command 4000 (PRC4000) . . . . . . . . . . . . . . . . . . . Pow-R-Command 2000 Panelboard Technical Data and Specifications . . . . . . . . . . . . . . . . . . Panel Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Command 1000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 750 Panelboard . . . . . . . . . . . . . . . . . . . . PRC100 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC100EC Panelboard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC50 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC25 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 10 10 10 10 10 10 447 451 453 455 456 478 457 460 463 467 470 473 An Eaton Green Solution 10 10 10 10 10 10 10 10 Pow-R-Command 2000 Panelboard Product Description Features Eaton’s Pow-R-Command 2000 is a microprocessor-based programmable lighting control system with an embedded Web server for robust control. The PRC2000 can be used as a standalone panelboard or networked as a system. An upgrade can be purchased to integrate the unit within BACnet native control networks. ● 10 ● ● ● ● ● ● ● ● ● 10 ● 10 ● 10 LCD display and keypad Memory loss protection Power failure/brownout recovery Astronomical real-time clock Control software Time scheduling Holiday scheduling Input to output switch matrix Messages/alarms Daylight optimization Switch Override Controller (SOC) Telephone Override Controller (TOC) Components Embedded Web server ● Intelligent power switching equipment ● LCD programming display and keypad ● Application Specific Controllers (ASCs) ● Software and support ● Integration components 10 ● 10 10 10 10 Intelligent Power Switching Equipment PRC2000 Panelboards 10 10 208Y/120V and 480Y/277V, single-phase and threephase. The panelboard utilizes both branch mounted standard breakers through 100A, and controllable thermal-magnetic breakers that are controlled by the PRC2000 System Controller. The PRC2000 controllers provide the ability to directly operate up to eight breaker control buses that are installed in the PRC2000 panelboard and the various PRCEP panelboards with one or two breaker control bus installed in each. Such a capability allows a single controller to directly operate up to 168 GHQRSP and BABRSP controllable circuit breakers, with individual control and status feedback of each controllable breaker. The System Controller also includes load override, holiday scheduling, one-shot or event schedules, off warning to tenants by blinking lights, memory loss protection, power failure/brownout protection, hardware diagnostics, a real-time clock and 16 dry contact switch inputs. Equipment within the PRC2000 system may be networked. Up to 120 panelboards may be networked over a shielded twisted pair network cable without the need for a personal computer in the system. To better support retrofit applications, the PRC2000 is offered in an external cabinet and the Breaker Control Bus is offered in retrofit kits. BACnet Protocol The PRC2000 unit can also be used for integration within BACnet native control networks. BACnet is a communications protocol widely used in building automation and controls and adds even more flexibility to the control system. Standards and Certifications The Pow-R-Command 2000 Panelboard is listed UL 67 for panelboards and UL 916 for energy management equipment. PRC2000 panelboards are offered from 100–225A in main lug and main configurations. Available voltages are 120/240V, 10 10 454 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Panelboards and Lighting Control Pow-R-Command 10.6 Technical Data and Specifications System Configurations PRC2000 Network Architecture 10 Breaker Control Buses (BCB) Containing an embedded webserver, each PRC2000 system is programmed with a unique IP address for communication via any standard Internet browser. Web access is standard with the PRC2000. Eight 21-circuit control buses configured as needed throughout PRL1A and PRL2A panels. The PRC2000B directly interfaces to a BACnet Client Workstation. 10 Every Pow-R-Command Expansion Panelboard can be configured with the left and/ or right breaker control buses installed. When using PRC EP Panel with one BCB, the remote-controlled breakers are placed on the side with the control bus. Standard and controlled breakers can be distributed anywhere in the panel as needed. 10 10 10 10 10 10 10 PRC2000 Breaker Control Busses 10 10 PRC EP 2 BCBs PRC EP 1 BCB 10 10 5th Floor Sub LAN 4 Conductor Cable 10 PRC EP 2 BCBs PRC EP 1 BCB 10 4th Floor 10 Sub LAN 4 Conductor Cable 10 PRC EP 2 BCBs PRC EP 2 BCBs 10 3rd Floor 10 Sub LAN 4 Conductor Cable PRC 2000 2 BCBs PRC EP 2 BCBs 10 10 2nd Floor Sub LAN 4 Conductor Cable PRC 2000 2 BCBs Customer Ethernet LAN 10 PC with Internet Browser 10 10 Ground Each Pow-R-Command 2000 Typical for 8 Breaker Control Busses Each with 21 Breakers 10 Remote Access Thru VPN 10 10 10 10 10 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 455 10.6 10 Panelboards and Lighting Control Pow-R-Command Panel Layout PRC2000 Layout 10 Controller 10 ckt 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 10 10 10 10 10 10 10 10 10 10 14 in.–18 Ckt. Chassis Includes PRC2000 Controller ckt 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 20 in.–30 Ckt. Chassis Includes PRC2000 Controller 26 in.–42 Ckt. Chassis Includes PRC2000 Controller Main Lug Section 2 in.—100 Amp MLO 4 in.—225 Amp MLO 6 in.— 400 Amp MLO Vertically Mounted 8 in.—100 Ampere Frame EHD, EDB, EDS, ED, EDH, FD, HFD 10 PRC2000 Panel Layout Instructions 1. Select PRC2000 Panelboard Chassis from layout on left. Layout Example 1. Panel Description: a. PRC2000, threephase four-wire, 208Y/120 Vac, interrupting rating of 10 kAIC symmetrical: 225A main lugs only at bottom, surface mounted and the following branch breakers b. 36–20A, single-pole BABRSP c. 6–20A, single-pole BABRSP spaces 2. Layout information from layout on left. a. Determine required mains (lugs or breaker) b. Select appropriate main lug c. Select appropriate main device d. Select appropriate branch breakers 2. Layout panel as shown on left. Total “in.” determine box height shown in on left. (When total “in.” units exceeds the number shown, use next size box size. a. PRC2000 with 42circuit Interior 26 inches b. 225A main lugs Section 4 inches c. Total panelboard height 30 inches 3. From table below: 9 in. — 225 Ampere Frame EDB, EDS, ED, EDH, FD, HFD, FDC 10 ● 22 in.—400 Ampere Frame DK, KD, HKD, KDC ● 10 ● 10 ● 10 10 Approximate Dimensions in Inches (mm) 10 Box Selection 10 Maximum Panel Height Box Height, Catalog Number YS Box LT Trim Panel height: 30 inches 20 inches wide x 5.75 inches deep Box height: 48 inches Box catalog number: YS2048 or EZB2048R Trim catalog number: LT2048S or EZT2048S EZ Box EZ Trim 20-Inch Wide x 5.75-Inch Deep Boxes 10 0–22.00 36.00 (914.4) YS2036 LT2036S or F EZB2036R EZT2036S or F 10 23.00–28.00 42.00 (1066.8) YS2042 LT2042S or F EZB2042R EZT2042S or F 29.00–34.00 48.00 (1219.2) YS2048 LT2048S or F EZB2048R EZT2048S or F 10 35.00–46.00 60.00 (1524.0) YS2060 LT2060S or F EZB2060R EZT2060S or F 47.00–58.00 72.00 (1828.8) YS2072 LT2072S or F EZB2072R EZT2072S or F 10 10 Cabinets Trims are code gauge steel, ANSI 61 light gray painted finish. Boxes are code gauge galvanized steel without knockout. Standard size is 20.00 inches (508.0 mm) wide x 5.75 inches (146.1 mm) deep. 10 Note: Width of enclosure will be 28.00 inches (711.2 mm) minimum. 10 10 10 456 Volume 2—Commercial Distribution CA08100003E—December 2010 Top and Bottom Gutters 6.38 inches (162.1 mm). Minimum Side Gutters 4.00-inch (101.6 mm) minimum on 20.00-inch (508.0 mm) wide box size. www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Panelboards and Lighting Control Pow-R-Command 10.6 Contents Pow-R-Command 1000 Panelboard Description Page Product Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Command 4000 (PRC4000) . . . . . . . . . . . . . . . . . . . Pow-R-Command 2000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 1000 Panelboard Technical Data and Specifications . . . . . . . . . . . . . . . . . . Panel Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Command 750 Panelboard . . . . . . . . . . . . . . . . . . . . PRC100 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC100EC Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC50 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC25 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 447 451 453 454 458 459 478 460 463 467 470 473 10 10 10 10 10 10 10 10 10 An Eaton Green Solution 10 10 Pow-R-Command 1000 Panelboard Product Description Features Eaton’s Pow-R-Command 1000 is a microprocessor-based programmable lighting control system. The PRC1000 can be used as a standalone panelboard or networked as a system. ● ● ● ● ● ● ● ● ● ● ● ● LCD display and keypad Memory loss protection Power failure/brownout recovery Astronomical real-time clock Control software Time scheduling Holiday scheduling Input to output switch matrix Messages/alarms Daylight optimization Switch Override Controller (SOC) Telephone Override Controller (TOC) Components ● Intelligent power switching equipment ● LCD programming display and keypad ● Application Specific Controllers (ASCs) ● Software and support ● Integration components 10 Intelligent Power Switching Equipment PRC1000 Panelboards PRC1000 panelboards are offered from 100–225A in main lug and main breaker configurations. Available voltages are 120/240V, 208Y/ 120V and 480Y/277V, singlephase and three-phase. The panelboard utilizes both branch mounted standard breakers through 100A, and controllable thermal-magnetic breakers that are controlled by the PRC1000 System Controller. The PRC1000 controllers provide the ability to directly operate up to eight breaker control buses. To better support retrofit applications, the PRC1000 is offered in an external cabinet and the Breaker Control Bus is offered in retrofit kits. Such a capability allows a single controller to directly operate up to 168 GHQRSP and BABRSP controllable circuit breakers, with individual control and status feedback of each controllable breaker. The System Controller also includes load override, holiday scheduling, one-shot or event schedules, off warning to tenants by blinking lights, memory loss protection, power failure/brownout protection, hardware diagnostics, a real-time clock and 16 dry contact switch inputs. Equipment within the PRC1000 system may be networked. Up to 120 panelboards may be networked over a shielded twisted pair network cable without the need for a personal computer in the system that are installed in the PRC1000 panelboard and the various PRCEP panelboards with one or two breaker control bus installed in each. Standards and Certifications The PRC1000 panelboard is listed UL 67 for panelboards and UL 916 for energy management equipment. 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 457 10.6 10 10 Panelboards and Lighting Control Pow-R-Command Technical Data and Specifications System Configurations PRC1000 Application 10 Customizable extension panels allow for combinations of both regular and remote controllable breakers for individualized solutions as shown in this riser diagram. Eaton’s PRC1000 Controller can support up to eight 10 PRC1000 Breaker Control Buses 10 10 10 Breaker Control Buses contained within four standard panelboards or split between a maximum of eight. When connected to the building’s Internet, all master and expansion panels can be controlled. 10 10 PRC EP 2 BCBs PRC EP 1 BCB 10 5th Floor 10 Sub LAN 4 Conductor Cable 10 10 4th Floor Sub LAN 4 Conductor Cable 10 PRC EP 2 BCBs PRC EP 2 BCBs 10 10 PRC EP 2 BCBs PRC EP 1 BCB 3rd Floor Sub LAN 4 Conductor Cable 10 PRC 1000 2 BCBs PRC EP 2 BCBs 10 2nd Floor 10 Sub LAN 4 Conductor Cable PRC 1000 2 BCBs 10 10 RS-485 Network Interface PC with Software Ground 10 Remote Access Thru Modem 10 10 10 10 10 10 10 10 458 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 10.6 Panelboards and Lighting Control Pow-R-Command Panel Layout PRC1000 Layout 14 in. - 18 Ckt. Chassis Includes PRC1000 Controller Controller ckt 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 ckt 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 20 in. - 30 Ckt. Chassis Includes PRC1000 Controller 26 in. - 42 Ckt. Chassis Includes PRC1000 Controller Main Lug Section 2 in.—100 Amp MLO 4 in.—225 Amp MLO 6 in.— 400 Amp MLO Vertically Mounted 8 in.—100 Ampere Frame EHD, EDB, EDS, ED, EDH, FD, HFD PRC1000 Panel Layout Instructions 1. Select PRC1000 Panelboard Chassis from layout on left. a. Determine required mains (lugs or breaker) b. Select appropriate main lug c. Select appropriate main device d. Select appropriate branch breakers 2. Layout panel as shown on left. Total “in.” determine box height shown on left. (When total “in.” units exceeds the number shown, use next size box size. Layout Example 1. Panel Description: 10 a. PRC1000, threephase four-wire, 208Y/120 Vac, interrupting rating of 10 kAIC symmetrical: 225A main lugs only at bottom, surface mounted and the following branch breakers b. 36–20A, single-pole BABRSP c. 6–20A, single-pole BABRSP spaces 2. Layout information from layout on left. 10 ● 22 in.—400 Ampere Frame DK, KD, HKD, KDC ● ● ● 10 10 10 10 10 10 10 a. PRC1000 with 42-circuit Interior 26 inches b. 225A main lugs section 4 inches c. Total panelboard height 30 inches 3. From table below: 9 in. — 225 Ampere Frame EDB, EDS, ED, EDH, FD, HFD, FDC 10 10 10 10 Panel height: 30 inches 20 inches wide x 5.75 inches deep Box height: 48 inches Box catalog number: YS2048 or EZB2048R Trim catalog number: LT2048S or EZT2048S 10 10 10 10 10 Approximate Dimensions in Inches (mm) 10 Box Selection 10 Maximum Panel Height Box Height, Catalog Number YS Box LT Trim EZ Box EZ Trim 10 10 20-Inch Wide x 5.75-Inch Deep Boxes 0–22.00 36.00 (914.4) YS2036 LT2036S or F EZB2036R EZT2036S or F 23.00–28.00 42.00 (1066.8) YS2042 LT2042S or F EZB2042R EZT2042S or F 29.00–34.00 48.00 (1219.2) YS2048 LT2048S or F EZB2048R EZT2048S or F 35.00–46.00 60.00 (1524.0) YS2060 LT2060S or F EZB2060R EZT2060S or F 47.00–58.00 72.00 (1828.8) YS2072 LT2072S or F EZB2072R EZT2072S or F Cabinets Trims are code gauge steel, ANSI 61 light gray painted finish. Boxes are code gauge galvanized steel without knockout. Standard size is 20.00 inches (508.0 mm) wide x 5.75 inches (146.1 mm) deep. Top and Bottom Gutters 6.38 inches (162.1 mm). 10 10 10 Minimum Side Gutters 10 4.00-inch (101.6 mm) minimum on 20.00-inch (508.0 mm) wide box size. 10 10 Note: Width of enclosure will be 28.00 inches (711.2 mm) minimum. Volume 2—Commercial Distribution CA08100003E—December 2010 10 10 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 459 10.6 10 Panelboards and Lighting Control Pow-R-Command Contents Pow-R-Command 750 Panelboard Description 10 Page Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Command 4000 (PRC4000) . . . . . . . . . . . . . . . . . . . Pow-R-Command 2000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 1000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 750 Panelboard Technical Data and Specifications . . . . . . . . . . . . . . . . . . Panel Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC100 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC100EC Panelboard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC50 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC25 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 10 10 10 10 10 10 447 451 453 454 457 461 462 478 463 467 470 473 An Eaton Green Solution 10 10 10 10 10 10 10 Pow-R-Command 750 Panelboard Product Description Features Eaton’s Pow-R-Command 750 is a microprocessorbased programmable lighting control system. The PRC750 can be used as a standalone panel, or the user has the option to connect up to three expansion panels, creating its own standalone subnetwork. ● ● ● ● ● ● ● 10 ● 10 ● ● 10 ● 10 ● 10 LCD display and keypad Memory loss protection Power failure/brownout recovery Astronomical real-time clock Control software Time scheduling Holiday scheduling Input to output switch matrix Messages/alarms Daylight optimization Switch Override Controller (SOC) Telephone Override Controller (TOC) Components Intelligent power switching equipment ● LCD programming display and keypad ● Integration components 10 ● 10 10 10 10 Intelligent Power Switching Equipment PRC750 Panelboards PRC750 panelboards are offered from 100–225A in main lug and main breaker configurations. Available voltages are 120/240V, 208Y/ 120V and 480Y/277V, singlephase and three-phase. The panelboard utilizes both branch mounted standard breakers through 100A, and controllable thermal-magnetic breakers that are controlled by the PRC750 system controller. The PRC750 controllers provide the ability to directly operate up to eight breaker control buses. To better support retrofit applications, the PRC750 is offered in an external cabinet and the Breaker Control Bus is offered in retrofit kits. Such a capability allows a single controller to directly operate up to 168 GHQRSP and BABRSP controllable circuit breakers, with individual control and status feedback of each controllable breaker. The System Controller also includes load override, holiday scheduling, one-shot or event schedules, off warning to tenants by blinking lights, memory loss protection, power failure/brownout protection, hardware diagnostics, a real-time clock and 16 dry contact switch inputs that are installed in the PRC750 panelboard and the various PRCEP panelboards with one or two breaker control bus installed in each. Standards and Certifications The PRC750 panelboard is listed UL 67 for panelboards and UL 916 for energy management equipment. 10 10 10 10 460 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Panelboards and Lighting Control Pow-R-Command 10.6 Technical Data and Specifications Designed for standalone applications, Eaton’s PRC750 is a premier microprocessorbased lighting control system that can be used to control all of the lighting in your industrial facilities, high-rise office buildings and airports. A single PRC750 panel can be connected to a maximum of eight Breaker Control Buses 10 (BCB) in any combination within panelboards for the ability to control up to a total of 168 Smart Breakers. The PRC750 also boasts load override, holiday scheduling, memory loss protection, astronomical time clocks and scheduling, 16 switch inputs, and alarm and message log features. 10 10 10 10 10 10 PRC750 Standalone System Architecture 10 PRC EP 1 BCB 10 10 5th Floor Sub LAN 4 Conductor Cable 10 PRC EP 1 BCB 10 4th Floor 10 Sub LAN 4 Conductor Cable 10 PRC EP 2 BCBs 10 3rd Floor 10 Sub LAN 4 Conductor Cable PRC EP 2 BCBs 10 10 2nd Floor Sub LAN 4 Conductor Cable PRC 750 2 BCBs 10 Programming via Local LCD Display 10 No Start-Up Required by Factory 10 Ground 10 10 10 10 10 10 10 10 10 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 461 10.6 10 Panelboards and Lighting Control Pow-R-Command Panel Layout PRC750 Layout 10 Controller 10 ckt 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 10 10 10 10 10 10 10 10 10 10 14 in. - 18 Ckt. Chassis Includes PRC750 Controller ckt 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 20 in. - 30 Ckt. Chassis Includes PRC750 Controller 26 in. - 42 Ckt. Chassis Includes PRC750 Controller Main Lug Section 2 in.—100 Amp MLO 4 in.—225 Amp MLO 6 in.—400 Amp MLO Vertically Mounted 8 in.—100 Ampere Frame EHD, EDB, EDS, ED, EDH, FD, HFD 10 PRC750 Panel Layout Instructions 1. Select PRC750 Panelboard Chassis from layout on left. Layout Example 1. Panel description: a. PRC750, three-phase four-wire, 208Y/120 Vac, interrupting rating of 10 kAIC symmetrical: 225A main lugs only at bottom, surface mounted and the following branch breakers b. 36–20A, single-pole BABRSP c. 6–20A, single-pole BABRSP spaces 2. Layout information from layout on left. a. Determine required mains (lugs or breaker) b. Select appropriate main lug c. Select appropriate main device d. Select appropriate branch breakers 2. Layout panel as shown on left. Total “in.” determine box height shown on left. (When total “in.” units exceeds the number shown, use next size box size. a. PRC750 with 42-circuit Interior 26 inches b. 225A main lugs section 4 inches c. Total panelboard height 30 inches 3. From table below: ● 9 in.—225 Ampere Frame EDB, EDS, ED, EDH, FD, HFD, FDC 10 22 in.—400 Ampere Frame DK, KD, HKD, KDC ● 10 ● 10 ● Panel height: 30 inches 20 inches wide x 5.75 inches deep Box height: 48 inches Box catalog number: YS2048 or EZB2048R Trim catalog number: LT2048S or EZT2048S 10 Approximate Dimensions in Inches (mm) 10 Box Selection 10 Maximum Panel Height 10 Box Height, Catalog Number YS Box LT Trim EZ Box EZ Trim 20-Inch Wide x 5.75-Inch Deep Boxes 10 0–22.00 36.00 (914.4) YS2036 LT2036S or F EZB2036R EZT2036S or F 23.00–28.00 42.00 (1066.8) YS2042 LT2042S or F EZB2042R EZT2042S or F 10 29.00–34.00 48.00 (1219.2) YS2048 LT2048S or F EZB2048R EZT2048S or F 35.00–46.00 60.00 (1524.0) YS2060 LT2060S or F EZB2060R EZT2060S or F 47.00–58.00 72.00 (1828.8) YS2072 LT2072S or F EZB2072R EZT2072S or F 10 10 Cabinets Trims are code gauge steel, ANSI 61 light gray painted finish. Boxes are code gauge galvanized steel without knockout. Standard size is 20.00 inches (508.0 mm) wide x 5.75 inches (146.1 mm) deep. 10 10 10 10 Top and Bottom Gutters 6.38 inches (162.1 mm). Minimum Side Gutters 4.00-inch (101.6 mm) minimum on 20.00-inch (508.0 mm) wide box size. Note: Width of enclosure will be 28.00 inches (711.2 mm) minimum. 10 462 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Panelboards and Lighting Control Pow-R-Command 10.6 Contents PRC100 Panelboard Description Page Product Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Command 4000 (PRC4000) . . . . . . . . . . . . . . . . . . . Pow-R-Command 2000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 1000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 750 Panelboard . . . . . . . . . . . . . . . . . . . . PRC100 Panelboard Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Panel Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC100EC Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC50 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC25 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 447 451 453 454 457 460 10 464 466 478 467 470 473 10 10 10 10 10 10 10 An Eaton Green Solution 10 10 PRC100 Panelboard Product Description Standards and Certifications Eaton’s Pow-R-Command is designed to meet the needs for microprocessor-based programmable lighting control. Used as a standalone panelboard or networked as a system, the Pow-R-Command PRC100 offers the broadest range of energy control in the industry. The PRC100 panelboard system is ideal for large, medium and small building applications. The Pow-R-Command panelboard mounts the same as traditional panelboards. Power and branch wiring is also the same. It can be applied to distribution systems rated single-phase three-wire and three-phase four-wire 120V, 120/240V, 208Y/120V and 480Y/277 Vac. ● ● ● ● ● ● ● 10 UL 67 Panelboards UL 50 Enclosures UL 916 Energy Management Equipment National Electrical Code Federal Specification W-P-115C FCC Emissions Standards: Part 15, Subject J for Class A Application IBC and UBC Seismic Qualified Equipment is available 10 10 10 10 10 10 10 10 10 10 10 See Page 447 for additional information. 10 Branch Breakers ● Refer to Page 465. 10 10 10 10 10 10 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 463 10.6 10 10 Panelboards and Lighting Control Pow-R-Command Product Selection Type PRC100 10 PRC100 Panelboard Ampere Rating 10 Main Integral Fuse Disconnect—Series Rated Combinations Interrupting Rating (kA Symmetrical) Device 240V 480Y/277V Type Main Lug Only 10 100 — — MLO 250 — — MLO 10 400 — — MLO Main Breaker 10 100 18 14 EHD 10 100 18 14 FDB 100 65 35 FD 10 100 100 65 HFD 100 200 100 FDC 100 200 150 FCL 100 200 200 FB-P 225 22 — EDB 10 225 42 — EDS 225 65 — ED 10 225 100 — EDH 225 200 — EDC 225 65 35 FD 10 225 100 65 HFD 225 200 100 FDC 10 250 65 35 JD 250 100 65 HJD 10 250 200 100 JDC 400 65 — DK 400 65 35 KD 10 400 100 65 HKD 400 200 100 KDC 10 400 200 100 LCL 10 10 10 10 Ampere Rating Interrupting Rating (kA Symmetrical) 240V 480Y/277V 100 100 200 65 Device Type Approved Branch Devices 100 T Fuse Disconnect GHB, GHBS, EHD, FDB, FD 65 T Fuse Disconnect GHB, GHBS, EHD, FDB, FD Notes The short-circuit rating of the MLO assembled panelboard may be fully rated based upon the lowest rated branch breaker or series rated with an approved upstream device. The short-circuit rating shown is that of the main breaker only. The rating of the assembled panelboard is the same as the short-circuit rating of the lowest rated main or branch device. Top feed only. Requires 6.50-inch (165.1 mm) deep box. The short-circuit rating shown is the rating of the panelboard assembly with the main and approved branch devices as listed. Fuses not included. Includes Smart Chassis (system controller integral to the panelboard chassis). Lighting optimization software and startup support must be included with each system—see Page 475. 10 10 10 10 10 10 10 10 10 10 464 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Panelboards and Lighting Control Pow-R-Command 10.6 10 BABRP Remote Control Circuit Breaker 10 Branch Circuit Breakers—480Y/277V Maximum Ampere Rating Interrupting Rating (kA Symmetrical) 240V 480V 10 Breaker Type 10 Remote Controllable Branch Circuit Breakers 15–30 10 — BABRP 15–30 10 — BABRSP 15–20 65 14 GHQRSP 15–30 65 14 GHBS 10 10 Conventional Branch Circuit Breakers—Not Controllable GHBS Remote Control Circuit Breaker 15–60 10 — 10 BAB 15–60 10 — BAB-H 70 10 — BAB 70 10 — BAB-H 80–100 10 — BAB 10 10 10 80–100 10 — BAB-H 15–50 10 — QBGF 15–50 10 — QBGFEP 15–20 10 — QBCAF 15–20 65 14 GHQ 15–20 65 14 GHB 25–60 65 14 GHB 70–100 65 14 GHB 15–60 18 14 EHD 70–100 18 14 EHD 15–60 18 14 FDB 70–100 18 14 FDB 110–150 18 14 FDB 15–60 65 35 FD 70–100 65 35 FD 110–225 65 35 FD 15–60 100 65 HFD 70–100 100 65 HFD 110–225 100 65 HFD 15–60 200 100 FDC 70–100 200 100 FDC 110–225 200 100 FDC 100–225 22 — EDB 100–225 42 — EDS 100–225 65 — ED 100–225 100 — EDH 100–225 200 — EDC 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 Notes Single-pole breaker rated 120 Vac. two-pole breaker rated 120/240 Vac. Single-pole breakers are rated 277 Vac maximum. Two- and three-pole breakers are rated 480Y/277 Vac maximum. For use on 480Y/277 Vac maximum.50A devices are available as two-pole only. GFCI for 5 mA personnel protection. GFP for 30 mA equipment protection. Arc fault circuit breaker. Maximum lug size, 4/0 AWG Al/Cu in 20-inch (508.0 mm) wide box. 300 kcmil lug available in 28-inch (711.2 mm) wide box. 10 10 10 10 10 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 465 10.6 10 Panel Layout 10 PRC100 Layout Panelboards and Lighting Control Pow-R-Command 1-Pole 1-Pole 1X EHD 10 2-Pole 2-Pole 2X FDB FD 10 1-Pole 3-Pole 3X HFD FDC 2-Pole 10 10 2-Pole 3-Pole 2X EDB, EDS, ED, EDH EDC 3X EDB, EDS, ED, EDH EDC 10 10 5X 12 Poles 10X 24 Poles 10 10 10 ckt 2 4 6 8 10 12 14 16 18 ckt 1 3 5 7 9 11 13 15 17 10 10 10 10 BABRP BABRSP BAB GHBS GHQRSP GHB 13X Smart Chassis includes spaces for 18 Poles GHBS, GHQRSP, GHB, BABRP, BABRSP, BAB Layout Instructions 1. Select: a. Smart Chassis from layout on left. Note: Smart chassis is always located at the bottom of the panelboard chassis immediately below the bottom breaker. b. Required mains (lugs, breaker or fuse pullout). c. Appropriate neutral. d. Branch breakers and additional chassis space, as needed. 2. Layout panel as shown on left, using appropriate “X” units. Total “X” units determine box height shown in table below. (When total “X” units exceeds the number shown, use next size box size. Smart Chassis is always located at the bottom of the panelboard chassis immediately below all GHBS/GHB or BABR/ BABRS/BAB breakers. 10 10 10 10 10 10 Neutral Section 5X 8X 100–250 A 400 A Main Lug Section 2X 5X 8X 100 A 250 A 400 A Main Device Horizontally Mounted Main Device Vertically Mounted 10 10 10 10 10 10 7X—EHD, FDB, FD, HFD, FDC, EDB, EDS, ED, EDH, EDC Box Tabulation “X” Units Box Height YS Box Catalog Number LT Trim Catalog Number EZ Box Catalog Number EZ Trim Catalog Number 100–400A 23X 48.00 (1219.2) YS2048 LT2048S or F EZB2048R EZT2048S or F 31X 60.00 (1524.0) YS2060 LT2060S or F EZB2060R EZT2060S or F 9X—200 A Class T fusible pullout 40X 72.00 (1828.8) YS2072 LT2072S or F EZB2072R EZT2072S or F 9X—FB-P 53X 90.00 (2286.0) YS2090 LT2090S or F EZB2090R EZT2090S or F 15X—DK, KD, HKD, KDC Notes All F-Frame branch breakers must be mounted above (top) of all controllable breakers on the chassis. EDB, EDS, ED, EDH and EDC branch mounted breakers may be mounted with load lugs on either left or right. Specify on order. All add-on branch spaces must be adjacent to smart chassis poles. GHBS, GHQRSP and GHB breakers cannot be mixed on same chassis with BABRP, BABRSP and BAB breakers. Top-mounted main—only. 466 Approximate Dimensions in Inches (mm) 7X—100 A Class T fusible pullout 14X—JD, HJD, JDC 10 10 See branch mounted — EHD, FD, FDB, HFD, FDC, EDB, EDS, ED, EDH, EDC above 2. Layout information from layout on left: a. Smart Chassis . = 13X b. 24-circuit add-on chassis . . . . . . = 10X c. 250A neutral . . = 5X d. 250A main lugs only . . . . . = 5X e. Total panelboard height . . . . . . . = 33X 3. From table below: 33X height (use 40X box). Box catalog number. . . . . . . YS2072 Trim catalog number. . . . . . LT2072S OR Box catalog number. . . . . EZB2072R Trim catalog number. . . . . EZT2072S Pow-R-Command Smart Chassis and 18 Pole Spaces 10 Layout Example 1. Panel description: a. Pow-R-Command, three-phase, four-wire 480Y/277 Vac, interrupting rating of 14 kAIC symmetrical, 250A main lugs only at bottom, surface mounted and the following branch breakers: b. 36–20A, single-pole GHBS. c. 6–20A, single-pole GHBS spaces. Cabinets Fronts are code-gauge steel, ANSI-61 light gray painted finish. Boxes are code-gauge galvanized steel without knockouts. Standard depth is 5.75 inches (146.1 mm). Standard width is 20.00-inch (508.0 mm) 100–400A. Volume 2—Commercial Distribution CA08100003E—December 2010 Top and Bottom Gutters 5.50 inches (139.7 mm) minimum. Side Gutters 4.00 inches (101.6 mm) minimum. www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Panelboards and Lighting Control Pow-R-Command PRC100EC Panelboard 10.6 Contents Description Page Product Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Command 4000 (PRC4000) . . . . . . . . . . . . . . . . . . . Pow-R-Command 2000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 1000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 750 Panelboard . . . . . . . . . . . . . . . . . . . . PRC100 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC100EC Panelboard Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Panel Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC50 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC25 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 447 451 453 454 457 460 463 468 469 478 470 473 An Eaton Green Solution 10 10 10 10 10 10 10 10 10 10 PRC100EC Panelboard 10 Product Description 10 Eaton’s Pow-R-Command PRC100 panelboard may be ordered with an optional factory-installed Expansion Chassis in addition to the factory-installed Universal System Controller. The optional Expansion Chassis houses up to two PRC100 Application Specific Controllers (ASC) that may be field installed. The addition of the optional Expansion Chassis and Application Specific Controllers to the standard PRC100 panelboard will extend the functionality of the PRC100 panelboard beyond time-of-day power switching. 10 10 10 10 10 10 10 10 10 Branch Breakers ● Refer to Page 465 10 10 Application Specific Controllers (ASC) ● 10 Select up to two ASCs per panel from Page 475 10 10 10 10 10 10 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 467 10.6 10 10 Panelboards and Lighting Control Pow-R-Command Product Selection Type PRC100EC 10 Ampere Rating 10 Main Integral Fuse Disconnect—Series Rated Combinations PRC100EC Panelboard Interrupting Rating (kA Symmetrical) Device 240V 480Y/277V Type Main Lug Only 10 100 — — MLO 250 — — MLO 10 400 — — MLO 100 18 14 EHD 10 100 18 14 FDB 100 65 35 FD 10 100 100 65 HFD 100 200 100 FDC 100 200 150 FCL 10 200 200 FB-P 225 22 — EDB 10 225 42 — EDS 225 65 — ED 10 225 100 — EDH 225 200 — EDC 225 65 35 FD 10 225 100 65 HFD 225 200 100 FDC 10 250 65 35 JD 250 100 65 HJD 10 250 200 100 JDC 400 65 — DK 400 65 35 KD 400 100 65 HKD 400 200 100 KDC 10 10 10 100 100 200 65 Device Type Approved Branch Devices 100 T Fuse Disconnect GHB, GHBS, EHD, FDB, FD 65 T Fuse Disconnect GHB, GHBS, EHD, FDB, FD Includes Smart Chassis (system controller integral to the panelboard chassis). 100 10 Interrupting Rating (kA Symmetrical) 240V 480Y/277V Notes The short-circuit rating of the MLO assembled panelboard may be fully rated based upon the lowest rated branch breaker or series rated with an approved upstream device. The short-circuit rating shown is that of the main breaker only. The rating of the assembled panelboard is the same as the short-circuit rating of the lowest rated main or branch device. Top feed only. The short-circuit rating shown is the rating of the panelboard assembly with the main and approved branch devices as listed. Fuses not included. Main Breaker 10 Ampere Rating Lighting optimization software and startup support must be included with each system—see Page 475. 10 10 10 10 10 10 10 10 10 10 10 468 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 10.6 Panelboards and Lighting Control Pow-R-Command Panel Layout Pow-R-Command PRC100EC Layout 1-Pole 1-Pole 1X EHD 2-Pole 2-Pole 2X FDB FD 3X HFD FDC 2X EDB, EDS, ED, EDH EDC 3X EDB, EDS, ED, EDH, EDC 1-Pole 3-Pole 2-Pole 2-Pole 3-Pole BABRP BABRSP BAB GHQRSP GHBS GHB 5X 12 Poles 10X 24 Poles ckt 2 4 6 8 10 12 14 16 18 ckt 1 3 5 7 9 11 13 15 17 Pow-R-Command Smart Chassis and 18 Pole Spaces Expansion Chassis Accepts 1 Application Specific Controller 20X Smart Chassis includes spaces for 18 Poles GHBS, GHQRSP, GHB, BABRP, BABRSP, BAB Instructions 1. Select: (from layout on left) a. Smart Chassis with Expansion Chassis. Layout Example 1. Panel description: a. Pow-R-Command, three-phase, four-wire 480Y/277 Vac, interrupting rating of 14 kAIC symmetrical, 250A main lugs only at bottom, surface mounted and the following branch breakers: b. 36–20A, single-pole GHBS. c. 6–20A, single-pole GHBS spaces. Note: Smart chassis is always located at the bottom of the panelboard chassis immediately below the bottom breaker. b. Required mains (lugs, breaker or fuse pullout). c. Appropriate neutral. d. Branch breakers and additional chassis space, as needed. 2. Layout information from layout on left: a. Smart Chassis with EC . . . . . . = 20X b. 24-circuit add-on chassis . . . . . . = 10X c. 250A neutral . . = 5X d. 250A main lugs only . . . . . = 5X e. Total panelboard height . . . . . . . = 40X 2. Layout panel as shown on left, using appropriate “X” units. Total “X” units determine box height shown on left. (When total “X” units exceeds the number shown, use next size box size.) Smart Chassis is always located at the bottom of the panelboard chassis immediately below all GHBS/GHB or BABR/ BABRS/BAB breakers. Neutral Section 5X 8X 100–250 A 400 A Main Lug Section 2X 5X 8X 100 A 250 A 400 A 3. From table below: (40X box) Box catalog number . . . . . . . YS2072 Trim catalog number . . . . . . LT2072S OR Box catalog number . . . . . EZB2072R Trim catalog number . . . . . EZT2072S See branch mounted — EHD, FD, FDB, HFD, FDC, EDB, EDS, ED, EDH, EDC above Main Devices Vertically Mounted 7X—EHD, FDB, FD, HFD, FDC, EDB, EDS, ED, EDH, EDC 7X—100 A Class T fusible pullout 9X—200 A Class T fusible pullout 9X—FB-P 14X—JD, HJD, JDC 15X—DK, KD, HKD, KDC Notes All F-Frame branch breakers must be mounted above (top) of all controllable breakers on the chassis. EDB, EDS, ED, EDH and EDC branch mounted breakers may be mounted with load lugs on either left or right. Specify on order. All add-on branch spaces must be adjacent to smart chassis poles. GHBS, GHQRSP and GHB breakers cannot be mixed on same chassis with BABRP, BABRSP and BAB breakers. Top mounted main—only. Box Height 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 Box Tabulation “X” Units 10 10 Approximate Dimensions in Inches (mm) Main Device Horizontally Mounted 10 YS Box Catalog Number LT Trim Catalog Number EZ Box Catalog Number EZ Trim Catalog Number 10 10 100–400A 23X 48.00 (1219.2) YS2048 LT2048S or F EZB2048R EZT2048S or F 31X 60.00 (1524.0) YS2060 LT2060S or F EZB2060R EZT2060S or F 40X 72.00 (1828.8) YS2072 LT2072S or F EZB2072R EZT2072S or F 53X 90.00 (2286.0) YS2090 LT2090S or F EZB2090R EZT2090S or F Cabinets Fronts are code-gauge steel, ANSI-61 light gray painted finish. Boxes are code-gauge galvanized steel without knockouts. Standard depth is 5.75 inches (146.1 mm). Standard width is 20.00-inch (508.0 mm) 100–400 amperes. Volume 2—Commercial Distribution CA08100003E—December 2010 Top and Bottom Gutters 5.50 inches (139.7 mm) minimum. 10 10 10 10 10 Side Gutters 4.00 inches (101.6 mm) minimum. 10 10 10 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 469 10.6 10 Panelboards and Lighting Control Pow-R-Command Contents PRC50 Panelboard Description 10 Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Command 4000 (PRC4000) . . . . . . . . . . . . . . . . . . . Pow-R-Command 2000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 1000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 750 Panelboard . . . . . . . . . . . . . . . . . . . . PRC100 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC100EC Panelboard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC50 Panelboard Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC25 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 10 10 10 10 10 Page 447 451 453 454 457 460 463 467 471 478 473 An Eaton Green Solution 10 10 10 PRC50 Panelboard 10 Product Description 10 10 10 10 10 10 10 10 10 10 Eaton’s PRC50 panelboard is similar to a PRC100 panelboard with additional programming capability added that provides the ability to group up to 42 remotely operated circuit breakers into eight individual zones. Each zone is designed to be switched by a dry contact from an external time clock, switch or interposing relay. The PRC50 programming board included with the controller allows the breakers to be grouped locally without the need of special equipment or software. The groupings can be easily changed without the need of any field rewiring. The grouping configurations are made using simple pushbutton inputs. Service 120/240 Vac single-phase three-wire, 208Y/120 Vac three-phase four-wire ● 240/120 Vac three-phase four-wire, 480Y/277 Vac three-phase four-wire ● Zone Configuration Eight Zones of Event Driven Control ● Simple two key field programming ● Matrix wiring allows breakers to be assigned to multiple zones ● Eight integrated digital override inputs ● No analog inputs ● Branch Breakers Refer to Page 472 ● 10 10 10 10 10 10 10 10 470 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Panelboards and Lighting Control Pow-R-Command 10.6 Product Selection Type PRC100 10 PRC50 Panelboard Ampere Rating Main Integral Fuse Disconnect—Series Rated Combinations Interrupting Rating (kA Symmetrical) Device 240V 480Y/277V Type Main Lug Only 100 — — MLO 250 — — MLO 400 — — MLO Main Breaker 100 18 14 EHD 100 18 14 FDB 100 65 35 FD 100 100 65 HFD 100 200 100 FDC 100 200 150 FCL 100 200 200 FB-P 225 22 — EDB 225 42 — EDS 225 65 — ED 225 100 — EDH 225 200 — EDC 225 65 35 FD 225 100 65 HFD 225 200 100 FDC 250 65 35 JD 250 100 65 HJD 250 200 100 JDC 400 65 — DK 400 65 35 KD 400 100 65 HKD 400 200 100 KDC 400 200 100 LCL Ampere Rating Interrupting Rating (kA Symmetrical) 240V 480Y/277V 100 100 200 65 Device Type Approved Branch Devices 100 T Fuse Disconnect GHB, GHBS, EHD, FDB, FD 65 T Fuse Disconnect GHB, GHBS, EHD, FDB, FD 10 10 10 10 Notes The short-circuit rating of the MLO assembled panelboard may be fully rated based upon the lowest rated branch breaker or series rated with an approved upstream device. The short-circuit rating shown is that of the main breaker only. The rating of the assembled panelboard is the same as the short-circuit rating of the lowest rated main or branch device. Top feed only. Requires 6.50-inch (165.1 mm) deep box. The short-circuit rating shown is the rating of the panelboard assembly with the main and approved branch devices as listed. Fuses not included. Includes Pow-R-Command Universal System Controller integral to the panelboard chassis (Smart Chassis) and the PRC50 Programming Board. Lighting optimization software and start-up support are not required. 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 471 10.6 10 BABRP Remote Control Circuit Breaker Pow-R-Command Branch Circuit Breakers—480Y/277 Volt Maximum Ampere Rating 10 Interrupting Rating (kA Symmetrical) 240 Volt 480 Volt Breaker Type Remote Controllable Branch Circuit Breakers 10 10 10 10 Panelboards and Lighting Control 15–30 10 — BABRP 15–30 10 — BABRSP 15–20 65 14 GHQRSP 15–30 65 14 GHBS Conventional Branch Circuit Breakers—Not Controllable GHBS Remote Control Circuit Breaker 10 10 15–60 10 — BAB 15–60 10 — BAB-H 70 10 — BAB 70 10 — BAB-H 80–100 10 — BAB 80–100 10 — BAB-H 15–50 10 — QBGF 15–50 10 — QBGFEP 15–20 10 — QBCAF 10 15–20 65 14 GHQ 15–20 65 14 GHB 10 25–60 65 14 GHB 70–100 65 14 GHB 15–60 18 14 EHD 10 10 10 70–100 18 14 EHD 15–60 18 14 FDB 70–100 18 14 FDB 110–150 18 14 FDB 10 15–60 65 35 FD 70–100 65 35 FD 10 110–225 65 35 FD 15–60 100 65 HFD 10 70–100 100 65 HFD 110–225 100 65 HFD 15–60 200 100 FDC 70–100 200 100 FDC 110–225 200 100 FDC 10 100–225 22 — EDB 100–225 42 — EDS 10 100–225 65 — ED 100–225 100 — EDH 10 100–225 200 — EDC 10 10 10 10 Notes Single-pole breaker rated 120 Vac. Two-pole breaker rated 120/240 Vac. Single-pole breakers are rated 277 Vac maximum. Two- and three-pole breakers are rated 480Y/277 Vac maximum. 50A devices are available as two-pole only. GFCI for 5 mA personnel protection. GFP for 30 mA equipment protection. Arc fault circuit breaker. For use on 480Y/277 Vac maximum. Maximum lug size, 4/0 AWG Al/Cu in 20-inch (508.0 mm) wide box. 300 kcmil lug available in 28-inch (711.2 mm) wide box. 10 10 10 10 10 10 10 472 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 10.6 Panelboards and Lighting Control Pow-R-Command Contents PRC25 Panelboard Description Page Product Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pow-R-Command 4000 (PRC4000) . . . . . . . . . . . . . . . . . . . Pow-R-Command 2000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 1000 Panelboard . . . . . . . . . . . . . . . . . . . Pow-R-Command 750 Panelboard . . . . . . . . . . . . . . . . . . . . PRC100 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC100EC Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC50 Panelboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PRC25 Panelboard Panel Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 447 451 453 454 457 460 463 467 470 474 478 10 10 10 10 10 10 10 10 10 10 10 PRC25 Panelboard 10 Product Description The PRC25 panelboard is designed to meet the needs for control of lighting and small branch circuits. Used as a standalone panelboard controlled by a time clock or wall switch, the PRC25 offers a solution for replacement of contactor and relay-based lighting control schemes. It can be applied to distribution systems rated: ● ● Single-phase three-wire and three-phase four-wire 120/240, 208Y/120 and 480Y/277 Vac to group individual breakers into zones that may be switched on/off by a dry contact from a time clock, photocell, wall switch or building automation system. Branch Breakers—PRC25 10 Ampere Rating Interrupting Rating (kA Symmetrical) 480Y/277 Vac Breaker Type 15–20 14 GHQ 15–20 14 GHB Branch Breakers Refer to Page 478. 25–60 14 GHB 70–100 14 GHB Standards and Certifications 15–30 25 HGHB 15–20 14 GHQRSP 15–60 14 GHBGFEP 15–20 14 GHBHID Provision — — ● ● ● UL 67, UL 50 Federal Specification W-P-115c Refer to Page 463 for additional information 10 10 10 10 10 10 10 Notes Single-pole breakers are rated 120 Vac maximum. 50 ampere devices are available as two-pole only. GFCI for 5 mA personnel protection. GFP for 30 mA equipment protection. Arc fault circuit breaker. HID (High Intensity Discharge) rated breaker. Switching neutral breaker. Single-pole device requires two-pole space; two-pole device requires three-pole space. Solenoid operated breaker. The heart of the PRC25 panel is the Zoning Board integral to the panelboard. This controller provides the ability Product Selection Branch Circuit Breakers—PRC25 Ampere Rating Interrupting Rating (kA Symmetrical) 240 Vac Breaker Type 15–60 70 80–100 15–50 15–50 15–20 15–60 15–30 15–30 15–30 10 10 10 10 10 10 10 10 10 10 BAB BAB BAB QBGF QBGFEP QBCAF BAB-D BAB-C BABRP BABRSP Provision — — Volume 2—Commercial Distribution CA08100003E—December 2010 10 10 10 10 10 10 10 10 10 10 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 473 10.6 10 Panel Layout 10 PRC25 Layout 10 ckt 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 ckt 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 10 10 10 10 10 10 10 31 in. - Includes Class II Chassis and spaces for 42 poles Note: PRC25 Chassis may be located at the Top or Bottom of the panelboard immediately above or below the breakers. Instructions 1. Select PRC25 Panelboard Chassis from layout on left. Layout Example 1. Panel Description: a. PRC25, three-phase four-wire, 208Y/120 Vac, interrupting rating of 10 kAIC symmetrical: 225A main lugs only at bottom, surface mounted and the following branch breakers b. 36–20A, single-pole BABRP c. 6–20A, single-pole BABRP spaces 2. Layout information from layout on left. a. Determine required mains (lugs or breaker) b. Select appropriate main lug c. Select appropriate main device d. Select appropriate branch breakers 2. Layout panel as shown on left. Total inches determine box height shown on left. (When total inch units exceed the number shown, use next size box size.) a. PRC25 with 42-circuit Interior 31 inches b. 225A main lugs Section 4 inches c. Total panelboard height 35 inches 3. From table below: PRC25 Class II Chassis 10 10 Pow-R-Command Note: Controlled circuits must be grouped in maximum of 6 Zones. All circuits within a zone must be together on the same side of the panelboard. 10 10 Panelboards and Lighting Control Deadfront Cover 2 in. for Deadfront Cover Supports Main Lug Section 2 in.—100 Amp MLO 4 in.—225 Amp MLO 21 in.—400 Amp MLO 10 Vertically Mounted 10 ● ● 8 in.—100 Ampere Frame EHD, EDB, EDS, ED, EDH, FD, HFD ● 9 in.—225 Ampere Frame EDB, EDS, ED, EDH, FD, HFD, FDC 10 ● 24 in.—JD, HJD, JDC 10 24 in.—DK, KD, HKD, KDC 10 Panel height: 20 inches wide x 5.75 inches deep Box height: 35 inches 60 inches Box catalog number: YS2060 or EZB2060R Trim catalog number: LT2060S or EZT2060S Approximate Dimensions in Inches (mm) Box Tabulation 10 “X” Units 10 Box Height YS Box Catalog Number LT Trim Catalog Number EZ Box Catalog Number EZ Trim Catalog Number 20-Inch Wide x 5.75-Inch Deep Boxes 10 33.00 (838.2) 48.00 (1219.2) YS2048 LT2048S or F EZB2048R EZT2048S or F 35.00 (889.0) 60.00 (1524.0) YS2060 LT2060S or F EZB2060R EZT2060S or F 10 38.00 (965.2) 60.00 (1524.0) YS2060 LT2060S or F EZB2060R EZT2060S or F 40.00 (1016.0) 60.00 (1524.0) YS2060 LT2060S or F EZB2060R EZT2060S or F 44.00 (1117.6) 60.00 (1524.0) YS2060 LT2060S or F EZB2060R EZT2060S or F 55.00 (1397.0) 72.00 (1828.8) YS2072 LT2072S or F EZB2072R EZT2072S or F 10 10 Cabinets Trims are code gauge steel, ANSI 61 light gray painted finish. Boxes are code gauge galvanized steel without knockout. Standard size is 20.00 inches (508.0 mm) wide x 5.75 inches (146.1 mm) deep. 10 10 10 10 Top and Bottom Gutters 6.38 inches (162.1 mm). Minimum Side Gutters 4.00-inch (101.6 mm) minimum on 20.00-inch (508.0 mm) wide box size. 10 474 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Panelboards and Lighting Control Pow-R-Command 10.6 PRC Catalog Numbers Description 10 Catalog Number 10 Control Cabinet—With Power Supply, System Controller and Space for Up to Three ASCs Control cabinet—surface mount PRC100CCS Control cabinet—flush mount PRC100CCF GHBS pigtail cable—8 feet (2.4m) PRL100ECP GHBS pigtail cable—16 feet (4.9m) PRC100ECP-16 GHBS pigtail cable—24 feet (7.3m) PRC100ECP-24 GHBS pigtail cable—32 feet (9.8m) PRC100ECP-32 10 10 10 10 Controllers 208V PRC2000 Controller—LCD display PRC2000D-208 480V PRC2000 Controller—LCD display PRC2000D-480 240V PRC2000 Controller—LCD display PRC2000D-240 208V PRC2000 Controller PRC2000-208 480V PRC2000 Controller PRC2000-480 240V PRC2000 Controller PRC2000-240 208V PRC1000 Controller—LCD display PRC1000D-208 480V PRC1000 Controller—LCD display PRC1000D-480 240V PRC1000 Controller—LCD display PRC1000D-240 208V PRC1000 Controller PRC1000-208 480V PRC1000 Controller PRC1000-480 240V PRC1000 Controller PRC1000-240 208V PRC750 Controller—LCD display PRC750D-208 480V PRC750 Controller—LCD display PRC750D-480 240V PRC2000 Controller—LCD display PRC750D-240 10 120V PRC2000 External Controller—LCD display PRC2000ECD-120 10 120V PRC2000 External Controller PRC2000EC-120 277V PRC2000 External Controller—LCD display PRC2000ECD-277 277V PRC2000 External Controller PRC2000EC-277 120V PRC1000 External Controller—LCD display PRC1000ECD-120 120V PRC1000 External Controller PRC1000EC-120 277V PRC1000 External Controller—LCD display PRC1000ECD-277 277V PRC1000 External Controller PRC1000EC-277 120V PRC750 External Controller—LCD display PRC750ECD-120 277V PRC750 External Controller—LCD display PRC750ECD-277 10 10 10 10 10 10 10 10 External Controller 10 10 10 10 10 10 Note All catalog numbers are non-standard items. 10 10 10 10 10 10 10 10 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 475 10.6 10 10 Panelboards and Lighting Control Pow-R-Command PRC Catalog Numbers, continued Catalog Number Description Advanced Control Devices PRC Digital Network Switch 2-button (Black) PRCDS2B PRC Digital Network Switch 2-button (White) PRCDS2W 10 PRC Digital Network Switch 2-button (Almond) PRCDS2A PRC Digital Network Switch 4-button (Black) PRCDS4B 10 PRC Digital Network Switch 4-button (White) PRCDS4W PRC Digital Network Switch 4-button (Almond) PRCDS4A PRC Digital Network Switch 6-button (Black) PRCDS6B 10 PRC Digital Network Switch 6-button (White) PRCDS6W PRC Digital Network Switch 6-button (Almond) PRCDS6A 10 PRC Digital Switch Network Power Injector PRCDSNPI PRC Digital Switch Network Splitter PRCDSNSP PRC 2-button Momentary Low Voltage Switch (Black) PRCLS2B 10 PRC 2-button Momentary Low Voltage Switch (White) PRCLS2W PRC 2-button Momentary Low Voltage Switch (Almond) PRCLS2A 10 PRC 4-button Momentary Low Voltage Switch (Black) PRCLS4B PRC 4-button Momentary Low Voltage Switch (White) PRCLS4W PRC 4-button Momentary Low Voltage Switch (Almond) PRCLS4A 10 PRC 6-button Momentary Low Voltage Switch (Black) PRCLS6B PRC 6-button Momentary Low Voltage Switch (White) PRCLS6W 10 PRC 6-button Momentary Low Voltage Switch (Almond) PRCLS6A 10 10 10 10 10 Wireless Control Devices PRC4000 Wireless Small Building Controller PRC4000-W 10 PRC4000 Wireless Extended Range Small Building Controller PRC4000-WX PRC Wireless I/O Module Assembly PRCWIOM 10 PRC Wireless Switch Interface PRCWSI PRC Wireless Network Switch 2-button (Black) PRCWS2B PRC Wireless Network Switch 2-button (White) PRCWS2W 10 PRC Wireless Network Switch 2-button (Almond) PRCWS2A PRC Wireless Network Switch 4-button (Black) PRCWS4B 10 PRC Wireless Network Switch 4-button (White) PRCWS4W PRC Wireless Network Switch 4-button (Almond) PRCWS4A PRC Wireless Network Switch 6-button (Black) PRCWS6B 10 PRC Wireless Network Switch 6-button (White) PRCWS6W PRC Wireless Network Switch 6-button (Almond) PRCWS6A 10 PRC25 10 10 10 10 6-zone PRC25 Maintained to Momentary Controller PRC25-6 4-zone PRC25 Maintained to Momentary Controller PRC25-4 Note All catalog numbers are non-standard items. 10 10 10 10 10 476 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Panelboards and Lighting Control Pow-R-Command 10.6 PRC Catalog Numbers, continued 10 Catalog Number Description 10 Optional Equipment LCD Display unit for PRC1000/2000 PRCLCD Breaker Control Bus—21-circuit—Retrofit Kit PRCBCB-21R Breaker Control Bus—15-circuit—Retrofit Kit PRCBCB-15R Breaker Control Bus— 9-circuit—Retrofit Kit PRCBCB-9R Breaker Control Bus—21-circuit PRCBCB-21 Breaker Control Bus—15-circuit PRCBCB-15 Breaker Control Bus—9-circuit PRCBCB-9 24 Volt AC Power supply PRCPS24 10 Switch override controller PRC100SOC Telephone override controller PRC100TOC 10 PRC100 universal system controller PRC100USC PRC50 programming board PRC50SPB Native Modbus controller PRC100MOD JCI Metasys controller PCR100JCI 10 10 10 10 Application Specific Controllers (ASC) 10 10 10 Computers and Peripherals Network interface box PRC100NIB Ethernet terminal server PRC100ENS Smart programming cable (serial) PRCSMARTCABLE Modbus programming cable (serial) MPC-S Laptop computer PRC100LTC Central operator’s station PRC100COS Data logging printer PRC100DLP Data fax modem—56K PRC100DFM 10 10 10 10 Software 10 Lighting optimization software PRC100SLO Web server software with hardware server key PRC100SWS Building graphics software with PC hardware key PRC100SBG Custom graphics screens programming PRC100SCG 10 Startup, training and/or programming first day of trip (includes expenses) PRC100SUT1 10 Additional consecutive days of same trip PRC100SUT2 Additional user’s guide PRC100UG 10 Technical Support 10 10 Notes All catalog numbers are non-standard items. One software package required per system. One day required per system (up to six panels). Required to start up six panels per day after the first day. One user’s guide included with each system at no charge. 10 10 10 10 10 10 10 10 10 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 477 10.6 10 Panelboards and Lighting Control Pow-R-Command Modifications 1. Special Cabinet (Box) Construction 8. Trim and Door Modifications —Special Fronts and Doors Modification 1 Modification 8 Modification Description Type 1 Enclosure Door-in-door, one door over interior and one which exposes gutter (LT Trim) 28-inch (711.2 mm) wide in place of standard 20-inch (508.0 mm) wide Common LT trim for two section panels with boxes bolted together 10 Type 2 Enclosure Standard flush lock with quarter turn fasteners at top and bottom of trim door (standard on doors 48-inch (1219.2 mm) high and over) (LT Trim) 10 Type 3R Enclosure 10 10 10 10 10 10 10 10 10 10 10 10 (Drip-proof with gasketed trim) (20-inch (508 mm) wide) (28-inch (711.2 mm) wide) 9. Special Hinges—LT Trim Piano hinges in lieu of standard hinges. Type 12 Enclosure Modification 9 (20-inch (508 mm) wide) (28-inch (711.2 mm) wide) Description Add for each panel door 2. Complete Assembly Complete assembly of panelboard box, interior and trim prior to shipment when required. 10. Special Locks Modification 2 Description Description LT Type Trim Add per panel Yale 511S with rosette Yale 4651S (LL803 Key) Master keying—above locks or standard lock—per panelboard 3. Concealed Trim Clamps—LT Trim 10 Tee handle and 3-point catch Modification 3 National metal lock with standard keying Description National metal lock with GE75 keyway Add per panel EZ Trim 10 10 Modification 10 Standard lock, keyed GE75 4. Nameplate, Engraved Standard lock, keyed to Corbin TEU-1 Modification 4 Standard lock, keyed to Corbin Cat 60 Type Standard lock, keyed to Corbin WEM1 Mastic back and installed by purchaser, per nameplate 10 Fixed to panel trim with two screws or rivets, per nameplate 10 5. Directory Frame—Metal 10 Modification 5 Modification 11 Cover Type Frame Type 10 11. Conduit Covers Fabricated sheet metal to cover open conduits above and/or below standard NEMA Type 1 box. Metal frame, plastic cover Conduit enclosing shield (open back) Conduit enclosure (solid back) 10 6. Permanent Circuit Numbers 10 Modification 6 12. Increased Dimensions Modification 12 Description 10 To provide permanently attached Micarta circuit numbers 10 7. Tamperproof Screws—LT Trim 10 Modification 7 Description Increased End Gutters 7-inch (177.8 mm) top or bottom 12-inch (304.8 mm) top or bottom Description 10 4-inch (101.6 mm) top or bottom Increased Side Gutters Tamperproof screws for trims, in lieu of standard screws 10 4-inch (101.6 mm) left or right 7-inch (177.8 mm) left or right 12-inch (304.8 mm) left or right 10 478 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 10.6 Panelboards and Lighting Control Pow-R-Command 13. Painting and Special Coatings Standard boxes are code-gauge galvanized sheet steel. Standard trims are code-gauge sheet steel with a rust inhibiting phosphatized coating and finished with ANSI-61. 16. Bus Density Main bus ampere rating is determined by UL listed temperature test. For 750 ampere per square inch aluminum or 1000 ampere per square inch copper, make price addition as follows: Modification 13 Modification 16 Description Amperes Per Square Inch Painted boxes (ANSI-61) Aluminum—750A Painted trims or boxes (other than ANSI-61) 250A Maximum 10 10 10 10 10 400A Maximum 14. Copper Main Bus Copper—1000A Modification 14 250A Maximum Main Bus Ratings Amperes 400A Maximum 100 Note: Modification 14—Applies to 310 and 310+ Trip Units. 10 17. Neutral Rated 200% 10 10 10 225–250 400 Modification 17 14a. Silver-Plated Copper Main Bus For silver-plated copper panelboard main bus and/or connectors, add as follows: Main Bus Rating Amperes Neutral Rating Amperes Box Height Addition 100 225 0 225 450 0 Modification 14a 250 500 3X Main Bus Ratings Amperes 400 800 3X 100–250 10 10 10 Note: Prices and dimensions based on mechanical lugs. For compression or copper lugs, refer to Eaton. 400 14b. Tin-Plated Copper Main Bus For tin-plated copper panelboard main bus and/or connectors, add as follows: 18. Increased Panel Main Bus Rating 10 100–250 Main Bus Ratings Amperes 10 250–400 100–250 400–600 10 19. Compression Main Lugs—Type Burndy Range Taking Al/Cu Compression Terminations For other terminal types, refer to Eaton. 10 400 15. Ground Bar Modification 15 Aluminum Terminal Bar for Aluminum or Copper Cable Standard Insulated/ Isolated Copper Terminal Bar for Copper Cable Only Standard Insulated/ Isolated 10 10 Modification 18 Ampere Rating Change Modification 14b 10 10 Modification 19 10 Wire Range by Panel Type Main Ampere PRL1a and PRL2a PRL3E PRL3a PRL4 100 (1) #1–1/0 or (1) 2/0–300 kcmil — — — 125 — (1) #4–2/0 or (1) 2/0 –300 kcmil (1) #4–2/0 or (1) 2/0–300 kcmil — 225 (1) 2/0–300 kcmil or — (1) 4/0–500 kcmil — — 250 — 400 (2) 4/0–300 kcmil or (2) 4/0–300 kcmil or (2) 4/0–300 kcmil or (2) 500–750 kcmil (2) 500–750 kcmil (2) 500–750 kcmil (2) 500–750 kcmil 600 — (2) 2/0–500 kcmil or (2) 2/0–500 kcmil or (2) 500–750 kcmil (2) 500–750 kcmil (2) 500–750 kcmil 10 800 — — — (3) 500–750 kcmil 1200 — — — (4) #2–600 kcmil or (4) 500–750 kcmil 10 10 10 10 (1) 2/0 –350 kcmil or (1) 2/0–350 kcmil or (2) 500–750 kcmil (1) 4/0–500 kcmil (1)–4/0–500 kcmil Note Insulated/isolated ground bar includes a standard ground bar. Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 10 10 10 10 479 10.6 10 10 10 Panelboards and Lighting Control Pow-R-Command 20. Copper Lugs Optional copper mechanical main lugs only. (Includes main incoming neutral lug.) 25. Circuit Breaker Handle Lockoff Devices Modification 25 Breaker Type Modification 20 Non-Padlockable Main Amperes Wire Range and Number of Lugs Per Phase GHB, EHD, FDB, FD, ED, EDH, EDC, BAB 10 100 (1) #14–1/0 Padlockable 225–250 (1) #6–250 kcmil EHD, FDB, FD, HFD, FDC, ED, EDH, EDC, GHB, BAB 10 400 (2) #1/0–600 kcmil 10 10 21. Sub-Feed Lugs—PRC100 and PRC50 Only Mechanical Al/Cu lugs. Compression or copper lugs requires additional price adder from Modification 19 or Modification 20 as appropriate. 10 Available on main lug panels only. 10 Modification 21 10 10 10 10 10 10 10 10 10 10 10 10 Main Amperes Box Height Addition 100–250 1X Terminal Material Wire Range F 225 Copper #4–4/0 J 250 Stainless Steel #4–350 K 225 Copper (1)#3–350 350 Copper (1)250–500 400 Copper (2)3/0–250 Description Main Amperes Box Height Addition 100 2X 250 5X 400 8X 23. Service Entrance To provide a Service Entrance label as detailed under the “Service Entrance Equipment” in application considerations. Only panelboards meeting these requirements can be labeled as such. The requirement for a Service Entrance Label must be noted on order entry. Includes neutral disconnect link and Service Entrance Equipment Label. (Ground bar not included— see Modification 15.) Modification 27 12 oz. Spray Can. ANSI-61 Light Gray Indoor Case lot of 12—12 oz. spray cans. ANSI-61 light gray indoor Single style Note BAB breakers with shunt trips require one additional pole space, i.e., three-pole breaker with shunt trip requires four-pole space. Modification 23 Device 24. Shunt Trip for Main or Branch Circuit Breaker For tripping circuit breaker from a remote point. Voltage and frequency must be specified. Wiring to terminal blocks is not included. Standard leads extend 18 inches (457.2 mm) out of breaker. Circuit breakers with factory-installed 120, 240 or 480 Vac shunt trips are available with UL listing as shown in table below. 10 Modification 24 10 GHB (three-pole only) 10 Max. Breaker Ampere Rating Modification 22 10 10 Frame 27. Touchup Paint Add per panel 10 Modification 26 22. Through-Feed Lugs Mechanical Al/Cu lugs. Compression or copper lugs requires additional price adder from Modification 19 or Modification 20 as appropriate. 10 10 26. Copper Wire Only Terminals for Molded Case Circuit Breakers (To replace standard Al/Cu terminals) Device All other circuit breakers 10 480 Volume 2—Commercial Distribution CA08100003E—December 2010 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Index A ability, 2-3, 7-8, 11, 14-15, 24, 27 above, 3, 20, 23, 28, 32 AC, 31 ac, 27 Accepts, 23 Access, 4, 9, 12 access, 1, 3-5, 7, 9 accessories, 3 AccessTCP, 6 accommodate, 7 accomplish, 4 achieve, 2, 7 across, 6 act, 7 Add, 32, 34 add, 20, 23, 33 added, 3, 24 adder, 34 Addition, 33-34 addition, 2-3, 7, 21, 33 Additional, 31 additional, 2-3, 6, 17, 20, 23-24, 27, 34 address, 9 adds, 2, 7-8 adjacent, 1, 20, 23 adjustable, 3 adjusts, 7 Advanced, 2, 30 advanced, 2, 7 after, 31 aid, 3 airports, 2, 15 Al, 19, 26, 33-34 alarm, 2-3, 7, 15 Alarms, 3 alarms, 8, 11, 14 All, 4, 7, 20, 23, 28-31, 34 all, 1-3, 12, 15, 20, 23 allow, 1-2, 4, 12 allowing, 1 Allows, 4 allows, 1, 3-4, 7-8, 11, 14, 24 Almond, 2, 30 almost, 1 already, 7 Also, 3 also, 2-3, 7-8, 11, 14-15, 17 Although, 1 Aluminum, 33 aluminum, 33 always, 20, 23 Amp, 10, 13, 16, 28 Ampere, 10, 13, 16, 18-19, 22, 25-28, 33-34 ampere, 27, 33 Amperes, 33-34 amperes, 23 An, 1, 7-8, 11, 14, 17, 21, 24 an, 1-4, 7-9, 11, 14, 18, 21-22, 24-25 Analog, 5 analog, 4-5, 7, 24 and, 1-34 ANSI, 10, 13, 16, 20, 23, 28, 33-34 any, 3-4, 7, 9, 15, 24 anywhere, 9 Index Application, 3-4, 8, 11-12, 17, 21, 23, 31 application, 3, 34 Applications, 1, 4 applications, 1-4, 8, 11, 14-15, 17 applied, 1, 17, 27 Applies, 33 Appropriate, 20, 23 appropriate, 10, 13, 16, 20, 23, 28, 34 Approved, 18, 22, 25 approved, 18, 22, 25 Approximate, 10, 13, 16, 20, 23, 28 APRC, 30 Arc, 19, 26-27 Architecture, 9, 15 are, 1-4, 7-11, 13-14, 16, 19-20, 23-31, 33-34 around, 2 array, 7 art, 2, 7 Article, 1 as, 1-4, 7-14, 16-20, 22-23, 25-28, 33-34 ASC, 3, 21, 31 ASCII, 6 ASCs, 3-4, 8, 11, 21, 29 assembled, 18, 22, 25 Assembly, 30, 32 assembly, 18, 22, 25, 32 assigned, 24 assistance, 2 associated, 2 Astronomical, 3, 8, 11, 14 astronomical, 2, 7, 15 at, 1-34 attached, 32 auditoriums, 3 automated, 2, 7 Automation, 2 automation, 1, 3, 8, 27 auxiliary, 7 Available, 4, 8, 11, 14, 34 available, 1-4, 6, 17, 19, 26-27, 34 AWG, 19, 26 B BAB, 19-20, 23, 26-27, 34 BABR, 20, 23 BABRP, 19-20, 23, 26-28 BABRS, 20, 23 BABRSP, 8, 10-11, 13-14, 16, 19-20, 23, 26-27 back, 1-2, 7, 32 backed, 7 backup, 6 BACnet, 2, 5-6, 8-9 ballasts, 2, 6-7 Bar, 33 bar, 33-34 BAS, 1 based, 1-2, 4, 7-8, 11, 14-15, 17-18, 22, 25, 27, 33 Basic, 2 basic, 3 basis, 2 Battery, 6 battery, 7 Baud, 6 BCB, 3, 9, 12, 15 BCBs, 3, 9, 12, 15 be, 1-5, 7-18, 20-25, 27-28, 34 Because, 2 Being, 2 being, 2-3 below, 10, 13, 16, 20, 23, 28, 32, 34 better, 8, 11, 14 between, 2, 12 beyond, 3, 21 Black, 2, 30 Blink, 6 blinking, 8, 11, 14 blocks, 34 Board, 25, 27 board, 3, 24, 31 boasts, 2, 15 bolted, 32 Both, 2 both, 2-3, 8, 11-12, 14 Bottom, 10, 13, 16, 20, 23, 28 bottom, 10, 13, 16, 20, 23, 28, 32 bottomcation, 32 Box, 4, 6, 10, 13, 16, 20, 23, 28, 32-34 box, 1, 10, 13, 16, 18-20, 23, 25-26, 28, 31-32 Boxes, 10, 13, 16, 20, 23, 28 boxes, 32-33 bracket, 6 Branch, 17-27, 34 branch, 1-2, 8, 10-11, 13-14, 16-18, 20, 22-23, 25, 27-28 Breaker, 2-3, 8-9, 11-12, 14-15, 18-19, 22, 25-27, 31, 34 breaker, 2-6, 8-11, 13-14, 16, 18-20, 22-23, 25-28, 34 Breakers, 2, 9, 15, 17, 19, 21, 24, 26-27, 34 breakers, 1-5, 8-14, 16, 19-20, 23-24, 26-28, 34 broadest, 3, 17 Brownout, 3 brownout, 8, 11, 14 Index Browser, 6, 9 browser, 7, 9 Building, 2, 30-31 building, 1, 3, 8, 12, 17, 27 buildings, 1-3, 15 Built, 6 built, 2, 7 Burndy, 33 Bus, 3, 8, 11, 14, 31, 33 bus, 8-9, 11, 14, 33 Buses, 9, 12, 15 buses, 8-9, 11, 14 Busses, 9 but, 3, 7 button, 2, 30 buttons, 3 by, 1-3, 5, 8, 11, 14-15, 24, 27, 32-33 bypass, 3 C CA, 1-34 Cabinet, 3-4, 29, 32 cabinet, 4, 8, 11, 14, 29 Cabinets, 10, 13, 16, 20, 23, 28 Cable, 9, 12, 15, 33 cable, 2-4, 8, 11, 29, 31 cables, 1-2, 4 California, 6 call, 1-34 campus, 4 Can, 34 can, 1-5, 7-9, 11-12, 14-15, 17, 24, 27, 34 cannot, 20, 23 cans, 34 capabilities, 2, 7 capability, 3, 8, 11, 14, 24 Capable, 2 capable, 3, 7 carry, 1 Case, 34 cases, 1-2 CAT, 2 Cat, 32 Catalog, 10, 13, 16, 20, 23, 28-31 catalog, 10, 13, 16, 20, 23, 28-31 CatalogMain, 20 catchModification, 32 cation, 32-33 CCF, 29 CCS, 29 cells, 1 Central, 31 central, 3-4 Certifications, 11, 14, 17, 27 Certificationsholiday, 8 chain, 4 Change, 33 change, 2, 4 changed, 2-3, 24 changes, 1-3 charge, 31 Chassis, 3, 10, 13, 16, 18, 20-23, 25, 28 chassis, 18, 20, 22-23, 25 Choices, 1 choose, 4 Circuit, 1, 19, 26-27, 32, 34 circuit, 1-4, 6, 8-11, 13-14, 16, 18-20, 22-28, 31-32, 34 circuits, 4, 27-28 Ckt, 10, 13, 16 ckt, 10, 13, 16, 20, 23, 28 Clamps, 32 Class, 17, 20, 23, 28 Client, 9 Clock, 6 clock, 2-3, 6-8, 11, 14, 24, 27 clocks, 1-2, 15 close, 1 closest, 4 closet, 4 closing, 1 closures, 3 coating, 33 Coatings, 33 Code, 1, 17 code, 10, 13, 16, 20, 23, 28, 33 colors, 2 com, 1-34 combination, 15 Combinations, 18, 22, 25 combinations, 12 comes, 4, 7 Command, 1-34 commands, 7 Commercial, 1-34 commercial, 3 Common, 32 common, 2 communicate, 2-3, 7 communicates, 7 communication, 2, 7, 9 Index communications, 1, 3, 8 compatibility, 3 Complete, 32 complete, 4 completely, 2, 7 complex, 2 complexity, 1 component, 2 Components, 7-8, 11, 14 components, 1-2, 8, 11, 14 Compression, 33-34 compression, 33 computer, 3-4, 8, 11, 31 Computers, 31 Concealed, 32 concern, 1 conditions, 1 Conductor, 9, 12, 15 Conduit, 32 conduit, 2 conduits, 32 Configuration, 24 configuration, 2, 7 Configurations, 9, 12 configurations, 2-3, 8, 11, 14, 24 configured, 3, 9 conjunction, 3 connect, 3, 7, 14 connected, 2-4, 12, 15 connecting, 7 connection, 2 connections, 3 connectivity, 7 connectors, 33 consecutive, 31 Considerations, 1-2 considerations, 34 consist, 2 consists, 1 Construction, 32 construction, 4 contact, 1-3, 8, 11, 14, 24, 27 Contactor, 1 contactor, 1-2, 27 contactors, 1-3 contacts, 3 contained, 12 Containing, 9 contains, 2 Contents, 1, 7-8, 11, 14, 17, 21, 24, 27 continued, 6, 30-31 Control, 1-34 control, 1-4, 7-9, 11, 14-15, 17, 27 Controllable, 19, 26 controllable, 1-3, 5, 8, 11-12, 14, 20, 23 Controlled, 28 controlled, 2, 8-9, 11-12, 14, 27 Controller, 2-8, 10-14, 16, 21, 23, 25, 29-30 controller, 1-4, 6-8, 11, 14, 18, 22, 24, 27, 31 Controllers, 3-4, 8, 11, 21, 29, 31 controllers, 1-3, 6-8, 11, 14 Controls, 3, 6 controls, 8 Conventional, 19, 26 coordinate, 7 coordinator, 7 Copper, 33-34 copper, 33-34 Corbin, 32 cord, 4 COS, 31 cost, 2-3 Cover, 28, 32 cover, 32 Covers, 32 creating, 14 Cu, 19, 26, 33-34 current, 1 Custom, 31 custom, 3 Customer, 9 customer, 2, 7 customers, 1, 4 Customizable, 12 customizable, 2, 7 cutting, 2 D Data, 3, 5, 8-9, 11-12, 14-15, 31 data, 7 Day, 3 day, 3, 21, 31 Daylight, 6, 8, 11, 14 days, 3, 31 Deadfront, 28 December, 1-34 dedicated, 2 Deep, 10, 13, 16, 28 deep, 10, 13, 16, 18, 25, 28 Delivery, 1-34 Index Density, 33 Depending, 1 depth, 20, 23 Description, 1, 7-8, 10-11, 13-14, 17, 21, 24, 27-34 description, 16, 20, 23 Design, 1 design, 1 Designed, 2, 15 designed, 1, 3-4, 7, 17, 24, 27 detailed, 34 Determine, 10, 13, 16, 28 determine, 10, 13, 16, 20, 23, 28 determined, 33 Device, 18, 20, 22-23, 25, 34 device, 2-3, 6-7, 10, 13, 16, 18, 22, 25, 27-28 Devices, 2, 7, 23, 25, 30 devices, 1-2, 5, 7, 18-19, 22, 25-27 DevicesMain, 18, 22 DevicesOptional, 34 DFM, 31 diagnose, 4 diagnostics, 2, 8, 11, 14 diagnosticsany, 3 diagram, 12 different, 3 differently, 3 difficult, 2 Digital, 2, 7, 30 digital, 2, 5, 7, 24 Dimensions, 10, 13, 16, 20, 23, 28, 32 dimensions, 33 dimmable, 2, 7 Dimming, 6 dimming, 6-7 directly, 1-2, 7-9, 11, 14 Directory, 32 Discharge, 27 Disconnect, 18, 22, 25 disconnect, 34 discrete, 7 Display, 15, 31 display, 2, 6, 8, 11, 14, 29 distributed, 1-3, 5, 7, 9 Distribution, 1-34 distribution, 1, 17, 27 DK, 10, 13, 16, 18, 20, 22-23, 25, 28 DLP, 31 does, 2, 7 done, 2, 7 Door, 32 door, 32 Doors, 32 doors, 32 downtime, 1-2 Drip, 32 Driven, 24 drives, 5 dry, 2-3, 8, 11, 14, 24, 27 DSN, 2 dual, 1 due, 2 during, 1, 4 dynamically, 7 E Each, 2-3, 5, 7, 9, 24 each, 2-3, 7-9, 11, 14, 18, 22, 31-32 easily, 3, 24 easy, 2 Eaton, 1-3, 5, 7-8, 11-12, 14-15, 17, 21, 24, 33 eaton, 1-34 EC, 1, 3, 7-8, 11, 14, 17, 21-24, 27, 29 ECD, 29 ECP, 29 ED, 10, 13, 16, 18-20, 22-23, 25-26, 28, 34 EDB, 10, 13, 16, 18-20, 22-23, 25-26, 28 EDC, 18-20, 22-23, 25-26, 34 edge, 2 EDH, 10, 13, 16, 18-20, 22-23, 25-26, 28, 34 EDS, 10, 13, 16, 18-20, 22-23, 25-26, 28 effective, 3 EHD, 10, 13, 16, 18-20, 22-23, 25-26, 28, 34 Eight, 9, 24 eight, 3, 5, 8, 11-12, 14-15, 24 either, 20, 23 Electrical, 1, 17 electrical, 1, 4, 7 elephone, 5 eliminate, 1 eliminated, 2 Embedded, 7-8 embedded, 2, 8-9 Emissions, 17 employs, 1 enabled, 3 enclosing, 32 Enclosure, 32 enclosure, 10, 13, 16, 32 Enclosures, 17 End, 32 Index Energy, 17 energy, 2-3, 6, 8, 11, 14, 17 Engineering, 4 engineers, 4 Engraved, 32 ENS, 31 ensure, 4 entire, 2 Entrance, 34 EntranceTo, 34 entry, 34 EP, 9, 12, 15 Equipment, 8, 11, 14, 17, 31, 34 equipment, 1, 3, 6, 8, 11, 14, 19, 24, 26-27 equipped, 7 ertically, 16 essential, 7 Ethernet, 6, 9, 31 even, 8 Event, 24 event, 2, 8, 11, 14 Every, 9 every, 2 Example, 13, 20, 23, 28 ExampleInstructions, 10, 16 Examples, 3 exceed, 28 exceeds, 10, 13, 16, 20, 23 existing, 1, 3-4, 7 expand, 3, 7 expander, 5 Expansion, 3, 9, 21, 23 expansion, 2, 5, 12, 14 expenses, 31 exposes, 32 extend, 3, 21, 34 Extended, 30 extended, 7 extension, 4, 12 extensive, 1 External, 6, 29 external, 3, 5-8, 11, 14, 24 EZ, 10, 13, 16, 20, 23, 28, 32 EZB, 10, 13, 16, 20, 23, 28 EZT, 10, 13, 16, 20, 23, 28 F Fabricated, 32 facilities, 2-3, 15 facility, 2-3, 7 Factory, 4, 15 factory, 2-4, 21, 34 fails, 2 Failure, 2 failure, 2-3, 8, 11, 14 Family, 1 family, 1 fasteners, 32 fault, 19, 26-27 fax, 31 FB, 18, 20, 22-23, 25 FCC, 17 FCL, 18, 22, 25 FD, 10, 13, 16, 18-20, 22-23, 25-26, 28, 34 FDB, 18-20, 22-23, 25-26, 34 FDC, 10, 13, 16, 18-20, 22-23, 25-26, 28, 34 feature, 7 Features, 3, 8, 11, 14 features, 2, 7, 15 Federal, 17, 27 Feed, 34 feed, 1, 18, 22, 25 feedback, 2, 7-8, 11, 14 feet, 4, 29 Field, 4 field, 1, 3, 21, 24 finish, 10, 13, 16, 20, 23, 28 finished, 33 firmware, 6 first, 31 Fixed, 32 fixed, 3 Flash, 6 Flexibility, 1-2 flexibility, 1-2, 8 Floor, 9, 12, 15 flush, 29, 32 following, 10, 13, 16, 20, 23, 28 follows, 33 For, 1-34 for, 1-9, 11-12, 14-15, 17, 19-20, 23, 26-29, 31-34 form, 3 four, 1, 10, 12-13, 16-17, 20, 23-24, 27-28, 34 Frame, 10, 13, 16, 20, 23, 28, 32, 34 frame, 32 Index free, 2 freeing, 1 frequency, 34 frequent, 3 From, 10, 13, 16, 20, 23, 28 from, 1-4, 7-8, 10-11, 13-14, 16, 20-21, 23-24, 27-28, 34 Fronts, 20, 23, 32 ft, 5 full, 3 fully, 2, 7, 18, 22, 25 function, 1 functionality, 3, 21 functions, 2, 4 further, 3 Fuse, 18, 22, 25 fuse, 20, 23 Fuses, 18, 22, 25 fusible, 20, 23 fusing, 1 G galvanized, 10, 13, 16, 20, 23, 28, 33 gasketed, 32 gateway, 6-7 gauge, 10, 13, 16, 20, 23, 28, 33 GE, 32 geographic, 7 GFCI, 19, 26-27 GFP, 19, 26-27 GHB, 18-20, 22-23, 25-27, 34 GHBGFEP, 27 GHBHID, 27 GHBS, 18-20, 22-23, 25-26, 29 GHQ, 19, 26-27 GHQRSP, 8, 11, 14, 19-20, 23, 26-27 gives, 2, 7 graphics, 31 Gray, 34 gray, 10, 13, 16, 20, 23, 28, 34 Green, 1, 7-8, 11, 14, 17, 21, 24 Ground, 9, 12, 15, 33-34 ground, 33 Group, 4 group, 3-4, 24, 27 grouped, 3, 24, 28 grouping, 3, 24 groupings, 3, 24 groups, 1 Guide, 1, 5-8, 11, 14, 17, 21, 24, 27 guide, 31 gutter, 32 Gutters, 10, 13, 16, 20, 23, 28, 32 GuttersTamperproof, 32 GuttersTrims, 28 H Handle, 34 handle, 32 hard, 2 Hardware, 3 hardware, 2, 8, 11, 14, 31 harvesting, 6 has, 2-3, 7, 14 have, 1-3, 7 heart, 3, 27 Height, 10, 13, 16, 20, 23, 28, 33-34 height, 10, 13, 16, 20, 23, 28 help, 4, 7 HFD, 10, 13, 16, 18-20, 22-23, 25-26, 28, 34 HGHB, 27 HID, 27 High, 27 high, 1-2, 15, 32 Hinges, 32 hinges, 32 HJD, 18, 20, 22-23, 25, 28 HKD, 10, 13, 16, 18, 20, 22-23, 25, 28 Holiday, 3, 8, 11, 14 holiday, 2, 11, 14-15 Holidays, 6 holidays, 6 Horizontally, 23 hours, 4 house, 4 houses, 3, 21 housing, 6 hrs, 6 Index I IBC, 17 ideal, 3-4, 17 IEEE, 7 If, 2 II, 28 illuminated, 2 Immediate, 1-34 immediately, 20, 23, 28 In, 1-2, 7 in, 1-4, 6-17, 19-21, 23, 26, 28, 32, 34 Inch, 10, 13, 16, 28, 33 inch, 10, 13, 16, 18-20, 23, 25-26, 28, 32-33 Inches, 10, 13, 16, 20, 23, 28 inches, 10, 13, 16, 20, 23, 28, 34 inchesertically, 28 include, 3 included, 3, 18, 22, 24-25, 31, 34 Includes, 10, 13, 16, 18, 22, 25, 28, 34 includes, 2, 8, 11, 14, 20, 23, 31, 33 including, 2 incoming, 34 incorporate, 2 incorporates, 1-2, 4 Increased, 32-33 increased, 2 indicators, 6 individual, 2-4, 8, 11, 14, 24, 27 individualized, 12 individually, 3, 5 Indoor, 34 indoor, 34 industrial, 2, 15 industry, 2-3, 7, 17 inexpensive, 1 information, 7, 10, 13, 16-17, 20, 23, 27-28 inhibiting, 33 Injector, 30 Input, 1, 3, 6, 8, 11, 14 input, 3, 5, 7 Inputs, 3, 5 inputs, 1-3, 5, 7-8, 11, 14-15, 24 install, 2 Installation, 2 installation, 2-3 installations, 1 installed, 1, 3, 8-9, 11, 14, 21, 32, 34 installing, 2 instead, 7 Instructions, 13, 20, 23, 28 Insulated, 33 Integral, 3, 18, 22, 25 integral, 18, 22, 25, 27 integrate, 8 Integrated, 7 integrated, 2-3, 7, 24 Integration, 5, 8, 11, 14 integration, 5, 8 integrations, 3 intelligence, 1-3, 7 Intelligent, 8, 11, 14 Intensity, 27 interaction, 2 Interface, 4, 6-7, 12, 30 interface, 2, 4, 31 interfaced, 1 interfaces, 9 Interior, 10, 13, 16, 28 interior, 1, 32 internal, 7 Internet, 1, 9, 12 Interposing, 3 interposing, 24 Interrupting, 18-19, 22, 25-27 interrupting, 10, 13, 16, 20, 23, 28 into, 1-4, 24, 27 IP, 2, 6, 9 is, 1-5, 7-11, 13-18, 20, 22-25, 27-28, 33-34 Isolated, 33 isolated, 33 It, 2-4, 7, 17, 27 it, 2, 4, 7 items, 29-31 its, 2, 7, 14 J jack, 4 JCI, 3, 31 JD, 18, 20, 22-23, 25, 28 JDC, 18, 20, 22-23, 25, 28 Johnson, 3, 6 Index K kA, 18-19, 22, 25-27 kAIC, 10, 13, 16, 20, 23, 28 kcmil, 19, 26, 33-34 KD, 10, 13, 16, 18, 20, 22-23, 25, 28 KDC, 10, 13, 16, 18, 20, 22-23, 25, 28 Key, 32 key, 24, 31 keyed, 32 keying, 32 keypad, 2, 8, 11, 14 keyway, 32 Kit, 31 kits, 8, 11, 14 KMParts, 1-34 knockout, 10, 13, 16, 28 knockouts, 20, 23 L Label, 34 label, 34 labeled, 34 Labor, 2 labor, 2 LAN, 1, 9, 12, 15 Laptop, 31 large, 3, 17 Layout, 8, 10-11, 13-14, 16-17, 20-21, 23, 27-28 layout, 3, 10, 13, 16, 20, 23, 28 LCD, 2, 6, 8, 11, 14-15, 29, 31 LCL, 18, 25 leading, 7 leads, 34 learning, 7 LED, 2, 6 left, 3, 9-10, 13, 16, 20, 23, 28, 32 length, 5 levels, 1, 4 lieu, 32 life, 2 Light, 34 light, 3, 10, 13, 16, 20, 23, 28, 34 Lighting, 1-34 lighting, 1-4, 7-8, 11, 14-15, 17, 27 Lights, 3 lights, 2, 8, 11, 14 limited, 1 line, 3, 7 link, 34 listed, 8, 11, 14, 18, 22, 25, 33 listing, 34 LL, 32 Load, 3 load, 1-3, 7-8, 11, 14-15, 20, 23 loads, 3-5, 7 Local, 3, 6, 15 local, 2, 4, 7 locally, 3, 24 located, 1, 4, 20, 23, 28 location, 2, 4, 7 lock, 32 Lockoff, 34 Locks, 32 locks, 32 log, 2-3, 15 logging, 3, 5, 7, 31 longer, 7 LonWorks, 6 LOS, 4 loss, 2-3, 8, 11, 14-15 lot, 34 Low, 2, 30 low, 2-3, 7 lower, 2 lowest, 18, 22, 25 LT, 10, 13, 16, 20, 23, 28, 32 LTC, 31 Lug, 10, 13, 16, 18, 20, 22-23, 25, 28 lug, 8, 10-11, 13-14, 16, 19, 26, 28, 34 Lugs, 33-34 lugs, 10, 13, 16, 20, 23, 28, 33-34 M mA, 19, 26-27 made, 3, 24 magnetic, 2, 8, 11, 14 Main, 10, 13, 16, 18, 20, 22-23, 25, 28, 33-34 main, 8, 10-11, 13-14, 16, 18, 20, 22-23, 25, 28, 33-34 mains, 10, 13, 16, 20, 23, 28 Maintained, 30 major, 1-2 Index make, 1, 33 makes, 1 Management, 17 management, 2-3, 6, 8, 11, 14 Mandatory, 5 mandatory, 5 Manual, 5 manually, 2 many, 2, 7 Master, 32 master, 12 Mastic, 32 Material, 34 Matrix, 24 matrix, 6, 8, 11, 14 Max, 34 max, 5 Maximum, 5-6, 10, 13, 16, 19, 26, 33 maximum, 2, 5, 12, 15, 19, 26-28 MaximumCircuit, 26 may, 1-4, 8, 11, 18, 20-23, 25, 27-28 Mechanical, 34 mechanical, 2, 33-34 medium, 3, 17 meet, 1-2, 7, 17, 27 meeting, 1, 34 Memory, 3, 8, 11, 14 memory, 2, 6-8, 11, 14-15 message, 2, 15 Messages, 8, 11, 14 Metal, 32 metal, 32 Metasys, 3, 31 method, 4 methods, 1-2 Micarta, 32 microprocessor, 1-2, 7-8, 11, 14-15, 17 microprocessortemporary, 2 minimal, 1 Minimum, 10, 13, 16, 28 minimum, 10, 13, 16, 20, 23, 28 mixed, 20, 23 MLO, 10, 13, 16, 18, 22, 25, 28 mm, 10, 13, 16, 18-20, 23, 25-26, 28, 32, 34 MOD, 3, 31 Modbus, 3, 6, 31 model, 1 Modem, 12 modem, 4, 31 Modes, 2 Modifi, 32-33 Modification, 32-34 modification, 2 Modifications, 8, 11, 14, 17, 21, 24, 27, 32 Module, 2, 7, 30 module, 5, 7 Molded, 34 Momentary, 30 momentary, 2 monitor, 3 monitoring, 4 more, 1, 3-4, 8 most, 1, 3 mount, 6, 29 Mounted, 10, 13, 16, 20, 23, 28 mounted, 1-4, 8, 10-11, 13-14, 16, 20, 23, 28 Mounting, 6 mounting, 1 mounts, 17 MPC, 31 much, 2 multi, 4 multiple, 24 multitude, 2 must, 18, 20, 22-23, 28, 34 N Nameplate, 32 nameplate, 32 National, 1, 17, 32 Native, 31 native, 3, 8 nd, 9, 12, 15 NEC, 1, 6 necessary, 2 need, 2-3, 7-8, 11, 24 needed, 9, 20, 23 needs, 1-2, 7, 17, 27 NEMA, 32 Network, 2-4, 6, 9, 12, 30-31 network, 2-3, 6-8, 11 networkable, 2-3, 7 networked, 1-3, 8, 11, 17 networks, 8 Neutral, 20, 23, 33 neutral, 20, 23, 27, 34 new, 1-4, 7 next, 10, 13, 16, 20, 23, 28 NIB, 4, 6, 31 No, 5-6, 15, 24 Index no, 2, 7, 31 Non, 6, 34 non, 4, 29-31 Not, 7, 19, 26 not, 1-2, 5, 18, 22, 25, 34 Note, 10, 13, 16, 20, 23, 28-30, 33-34 noted, 34 Notes, 5-6, 18-20, 22-23, 25-27, 31 notice, 6 notification, 7 notifications, 7 Number, 5, 10, 13, 16, 20, 23, 28-31, 34 number, 5-6, 10, 13, 16, 20, 23, 28 Numbers, 29-32 numbers, 29-32 O occupancy, 2-3, 7 of, 1-8, 10-18, 20-25, 27-28, 31-32, 34 Off, 3-4 off, 1-4, 6-8, 11, 14, 27 offer, 1 offered, 2, 8, 11, 14 offers, 3, 7, 17, 27 office, 2-3, 15 Often, 2 often, 1-2 On, 3-4, 6 on, 1-4, 6-7, 9-10, 13, 16, 19-20, 23, 26-28, 32-34 onboard, 2, 7 One, 31 one, 2-4, 7-9, 11, 14, 32, 34 Online, 4 online, 4 Only, 4, 18, 22, 25, 33-34 only, 7, 10, 13, 16, 18-20, 22-23, 25-28, 34 OPC, 6 open, 32 opening, 1 operate, 2-3, 8, 11, 14 operated, 3, 24, 27 operation, 2 Operational, 2 operator, 31 optimal, 2 optimization, 8, 11, 14, 18, 22, 25, 31 Option, 6 option, 14 Optional, 3, 5, 31 optional, 2-3, 6, 21 OR, 23 or, 1-34 order, 20, 23, 34 ordered, 3, 21 other, 3, 7, 33-34 out, 34 output, 6-8, 11, 14 Outputs, 5-6 outputs, 2, 7 over, 1-3, 5, 7-8, 11, 32 overcurrent, 1 overload, 1 Override, 3-4, 8, 11, 14 override, 2, 4-6, 8, 11, 14-15, 24, 31 Overview, 1, 7-8, 11, 14, 17, 21, 24, 27 own, 14 oz, 34 P package, 31 Padlockable, 34 PadlockableMain, 34 Page, 1, 7-8, 11, 14, 17-18, 21-22, 24, 27 page, 2 Paintadditional, 34 Painted, 33 painted, 10, 13, 16, 20, 23, 28 Painting, 33 pair, 3, 8, 11 Panel, 8-11, 13-14, 16-17, 20-21, 23, 27-28, 33 panel, 1, 9-10, 13-16, 20-21, 23, 27-28, 32, 34 Panelboard, 1, 3, 7-11, 13-14, 16-18, 21-22, 24-25, 27-28 panelboard, 1-4, 8, 10-11, 13-14, 16-18, 20-25, 27-28, 32-33 Panelboards, 1-34 panelboards, 1-4, 6, 8, 11-12, 14-15, 17, 34 PanelboardTechnical, 14 panels, 1, 3, 5, 9, 12, 14, 31-32, 34 Part, 17 passes, 7 Password, 6 password, 1 past, 1 PC, 9, 12, 31 Index PCR, 31 peak, 4 Per, 33-34 per, 1, 4, 6-7, 21, 31-34 perform, 1-2 performance, 4 periods, 6 Peripherals, 31 Permanent, 32 permanently, 32 personal, 4, 8, 11 personnel, 19, 26-27 Phase, 34 phase, 1, 8, 10-11, 13-14, 16-17, 20, 23-24, 27-28 phosphatized, 33 photo, 1-2, 7 photocell, 27 photocells, 3 Piano, 32 pigtail, 4, 29 place, 32 placed, 9 plant, 4 plastic, 32 Plated, 33 plated, 33 platform, 7 play, 3 Plug, 3 plug, 4 plugged, 3 point, 32, 34 Pole, 20, 23 pole, 6, 10, 13, 16, 19-20, 23, 26-28, 34 Poles, 20, 23 poles, 20, 23, 28 port, 3, 6 possible, 3-4 Pow, 1-34 Power, 2-3, 5, 8, 11, 14, 17, 29-31 power, 1-4, 8, 11, 14, 21 powered, 3 PRC, 1-18, 20-25, 27-31, 34 PRCBCB, 31 PRCDS, 2, 30 PRCDSNPI, 30 PRCDSNSP, 30 PRCEP, 1, 3, 8, 11-12, 14 PRCJCI, 3 PRCLCD, 31 PRCLS, 2, 30 PRCPS, 31 PRCSMARTCABLE, 31 PRCWIOM, 2, 7, 30 PRCWS, 2, 7, 30 PRCWSI, 7, 30 pre, 4 premier, 2, 15 prewired, 2 price, 33-34 Prices, 33 printer, 31 prior, 32 priorities, 3 priority, 3 PRL, 9, 29, 33 Product, 1, 5, 7-8, 11, 14, 17-18, 21-22, 24-25, 27 products, 7 professional, 4 program, 3-4, 6 programmable, 2, 8, 11, 14, 17 programmed, 2-3, 7, 9 Programming, 4, 15, 25 programming, 2-4, 7-8, 11, 14, 24, 31 programs, 4 prompted, 4 proof, 32 protected, 1, 6 Protection, 1 protection, 1-3, 8, 11, 14-15, 19, 26-27 Protocol, 8 protocol, 2-3, 5, 8 provide, 1, 8, 11, 14, 32, 34 provided, 2 provides, 2-4, 24, 27 Provision, 27 pullout, 20, 23 purchased, 8 purchaser, 32 pushbutton, 3, 24 Q QBCAF, 19, 26-27 QBGF, 19, 26-27 QBGFEP, 19, 26-27 Qualified, 17 quarter, 32 quickly, 7 Index R RAC, 4 radio, 7 rail, 5 Rails, 5 Range, 30, 33-34 range, 3, 17 rate, 6 Rated, 18, 22, 25, 33 rated, 1, 17-19, 22, 25-27 Rating, 18-19, 22, 25-27, 33-34 rating, 1, 10, 13, 16, 18, 20, 22-23, 25, 28, 33 RatingAmpere, 18, 22 Ratings, 33 ratings, 1-3 rd, 9, 12, 15 re, 1 Real, 3 real, 2, 8, 11, 14 recommended, 4 recovery, 3, 8, 11, 14 reduction, 3 Refer, 17, 21, 24, 27 refer, 33 regular, 12 relay, 1-3, 5, 7, 24, 27 relays, 1-2 reliability, 2, 7 Remote, 4-5, 9, 12, 19, 26 remote, 1, 3-4, 9, 12, 34 remotely, 3-4, 7, 24 replace, 34 replacement, 27 replaces, 3 require, 1-3, 34 Required, 15, 20, 23, 31 required, 1, 3-5, 7, 10, 13, 16, 25, 28, 31-32 requirement, 34 requirements, 1, 3, 34 Requires, 18, 25 requires, 1-3, 27, 34 requiring, 4 response, 1 restore, 3 retailers, 3 Retrofit, 1, 31 retrofit, 2, 4, 8, 11, 14 Retrofitting, 1 reused, 4 rewiring, 1-3, 24 right, 3, 9, 20, 23, 32 rise, 2, 15 riser, 12 rivets, 32 robust, 2, 7-8 room, 7 rooms, 1 rosette, 32 RS, 6-7, 12 RTU, 6 rules, 3 Running, 7 rust, 33 S same, 1, 3-4, 17-18, 20, 22-23, 25, 28, 31 SBG, 31 SC, 4 SCC, 3 SCG, 31 schedule, 3, 6 scheduled, 3-4 schedules, 2, 6, 8, 11, 14 Scheduling, 6 scheduling, 2-3, 7-8, 11, 14-15 schedulingBACnet, 8 scheme, 2-3 schemes, 2, 27 schools, 3 screens, 31 Screws, 32 screws, 32 seamless, 2 Section, 10, 13, 16, 20, 23, 28 section, 13, 16, 32 See, 17, 20, 23 see, 7, 18, 22, 34 segment, 7 Seismic, 17 Select, 10, 13, 16, 20-21, 23, 28 Selection, 1, 5-8, 10-11, 13-14, 16-18, 21-22, 24-25, 27 selection, 2 self, 3 sensor, 7 sensors, 2-3, 7 serial, 4, 31 Index Series, 18, 22, 25 series, 18, 22, 25 Server, 6 server, 2, 6-8, 31 Service, 4, 24, 34 services, 4 set, 4, 7 Setup, 4 setup, 4 sheet, 32-33 shield, 32 shielded, 3, 8, 11 shipment, 32 Shor, 1 short, 1, 18, 22, 25 shot, 2, 8, 11, 14 Should, 3 shown, 10, 12-13, 16, 18, 20, 22-23, 25, 28, 34 Shunt, 34 shunt, 34 Side, 10, 13, 16, 20, 23, 28, 32 side, 9, 28 sides, 3 signal, 1 Silver, 33 silver, 33 similar, 24 Simple, 24 simple, 1-3, 24 Simplicity, 2 simplifying, 1 Simply, 4 Single, 19, 26-27, 34 single, 1-2, 8, 10-11, 13-17, 20, 23-24, 28 site, 2 six, 1-2, 31 size, 10, 13, 16, 19-20, 23, 26, 28 sizes, 1 sizing, 3 SLAN, 5 slave, 3 SLO, 31 Small, 30 small, 3, 17, 27 Smart, 2, 15, 18, 20, 22-23, 25, 31 smart, 20, 23 SOAP, 6 SOC, 3, 8, 11, 14, 31 Software, 4, 8, 11-12, 31 software, 2-4, 7-8, 11, 14, 18, 22, 24-25, 31 Solenoid, 27 solenoid, 3 solid, 32 Solution, 1, 7-8, 11, 14, 17, 21, 24 solution, 3, 27 solutions, 12 some, 1, 3 sophisticated, 1 SOR, 20 Space, 1, 29 space, 1, 20, 23, 27, 34 Spaces, 20, 23 spaces, 3, 10, 13, 20, 23, 28 spaceson, 16 SPB, 31 Special, 32-33 special, 3, 24 Specific, 3-4, 8, 11, 21, 23, 31 specific, 3 Specification, 17, 27 Specifications, 8-9, 11-12, 14-15 specified, 34 Specify, 20, 23 specifying, 1 split, 12 Splitter, 30 Spray, 34 spray, 34 Square, 33 square, 33 stadiums, 3 Stainless, 34 Standalone, 15 standalone, 2-3, 8, 11, 14-15, 17, 27 Standard, 3, 9-10, 13, 16, 20, 23, 28, 32-34 standard, 1-3, 7-9, 11-12, 14, 21, 29-34 Standards, 6, 8, 11, 14, 17, 27 Start, 15 start, 25, 31 Startup, 2, 4-5, 31 startup, 1-2, 5, 18, 22 state, 2, 7 station, 31 status, 2, 6-8, 11, 14 Steel, 34 steel, 10, 13, 16, 20, 23, 28, 33 stored, 2, 7 stores, 4 straightforward, 2 strategy, 2, 7 style, 34 Sub, 9, 12, 15, 34 Subject, 17 subjected, 1 subnetwork, 14 Such, 8, 11, 14 Index such, 3-4, 34 Sumter, 4 Supply, 29 supply, 2, 4-5, 31 Support, 1-34 support, 3-4, 8, 11-12, 14, 18, 22, 25 Supports, 28 Supportswitched, 4 Supportthe, 4 surface, 10, 13, 16, 20, 23, 28-29 SUT, 31 Switch, 2-3, 5, 7-8, 11, 14, 30-31 switch, 2-3, 5, 7-8, 11, 14-15, 24, 27 switched, 2-3, 24, 27 Switches, 2 switches, 1-3, 7 Switching, 8, 11, 14, 27 switching, 2-3, 6-8, 11, 14, 21 SWS, 31 Symmetrical, 18-19, 22, 25-27 symmetrical, 10, 13, 16, 20, 23, 28 System, 2-4, 8-9, 11-12, 14-15, 21, 25, 29 system, 1-4, 7-9, 11, 14-15, 17-18, 22, 27, 31 systems, 1, 3-4, 17, 27 T table, 10, 13, 16, 20, 23, 28, 34 Tabulation, 23, 28 TabulationHorizontally, 20 tailored, 2 Taking, 33 Tamperproof, 32 task, 4 tasks, 2 TCP, 6 team, 4 Tech, 1-34 Technical, 4, 8-9, 11-12, 15, 31 technicians, 4 technology, 2, 7 Tee, 32 Telephone, 4, 8, 11, 14, 31 telephone, 4 temperature, 33 tenant, 3 tenants, 2, 8, 11, 14 Terminal, 33-34 terminal, 31, 33-34 Terminals, 34 terminals, 34 terminated, 1, 4 Terminations, 33 test, 33 TEU, 32 th, 9, 12, 15 than, 3-4, 33 that, 1-4, 7-8, 11, 14-15, 18, 21-22, 24-25, 27 The, 1-4, 7-9, 11, 14-15, 17-18, 21-22, 24-25, 27, 34 the, 1-5, 7-18, 20-25, 27-28, 31, 34 theatres, 3 them, 1-2 There, 2-3 there, 2-3 thermal, 2, 8, 11, 14 These, 1 these, 1, 34 They, 1-2 This, 2-3, 7, 27 this, 3-4, 7, 12 those, 1, 4 Three, 6, 29 three, 1-2, 4, 8, 10-11, 13-14, 16-17, 19-20, 23-24, 26-28, 34 Through, 34 through, 2, 7-8, 11, 14 throughout, 2, 9 Thru, 9, 12 Time, 3, 6, 8, 11, 14 time, 1-3, 6-8, 11, 14-15, 21, 24, 27 Tin, 33 tin, 33 Title, 6 To, 3, 7-8, 11, 14, 32, 34 to, 1-4, 7-9, 11-12, 14-15, 17-18, 20-25, 27, 29-34 TOC, 4, 8, 11, 14, 31 Today, 1 together, 28, 32 tone, 4 Top, 10, 13, 16, 18, 20, 22-23, 25, 28 top, 20, 23, 32 Total, 5, 10, 13, 16, 20, 23, 28 total, 2, 5, 10, 13, 15-16, 20, 23, 28 touch, 4 Touchup, 34 Traditional, 1 traditional, 1-2, 17 trained, 4 Training, 4 training, 31 transfers, 7 Index Trim, 10, 13, 16, 20, 23, 28, 32 trim, 32 Trims, 10, 13, 16 trims, 32-33 Trip, 33-34 trip, 31, 34 tripping, 34 trips, 34 trouble, 2 troubleshoot, 4 turn, 1, 32 twisted, 3, 8, 11 Two, 19, 26 two, 3-4, 7-8, 11, 14, 19, 21, 24, 26-27, 32 Type, 18-19, 22, 25-27, 32-34 types, 33 Typeype, 32 Typical, 9 typically, 1 U UBC, 17 UG, 31 UL, 6, 8, 11, 14, 17, 27, 33-34 under, 34 unique, 9 unit, 7-8, 31 Units, 20, 23, 28, 33 units, 3, 10, 13, 16, 20, 23, 28 Universal, 3-5, 21, 25 universal, 2, 31 until, 2 unwanted, 1 Up, 8, 11, 15, 29 up, 1-4, 7-8, 11-12, 14-15, 21, 24-25, 31 upgrade, 8 upon, 18, 22, 25 upstream, 1, 18, 22, 25 USC, 3, 31 use, 10, 13, 16, 19-20, 23, 26, 28 Used, 17, 27 used, 2-3, 7-8, 11, 14-15 user, 14, 31 users, 4 using, 2-4, 6-7, 9, 20, 23-24 utilized, 2 utilizes, 2, 8, 11, 14 utilizing, 5 V Vac, 1, 3, 10, 13, 16-17, 19-20, 23-24, 26-28, 34 valuable, 1, 7 various, 3-4, 8, 11, 14 varying, 1 Vdc, 7 version, 1 versions, 3 Vertically, 10, 13, 20, 23 very, 2 via, 6, 9, 15 voice, 4 volatile, 6 Volt, 26, 31 Voltage, 2, 30, 34 voltage, 2, 7 voltages, 8, 11, 14 Volume, 1-34 VPN, 9 W wall, 1, 3-4, 27 warning, 2-3, 8, 11, 14 way, 3, 7 Web, 2, 6-9, 31 web, 1 webserver, 9 week, 3 well, 2, 7 WEM, 32 were, 1 When, 9-10, 12-13, 16, 20, 23, 28 when, 4-5, 32 where, 4 which, 1-3, 7, 32 White, 2, 30 who, 4 Wide, 10, 13, 16, 28 wide, 10, 13, 16, 19, 26, 28, 32 widely, 8 Index Width, 10, 13, 16 width, 1, 20, 23 will, 3-4, 10, 13, 16, 21 Windows, 4 Wire, 33-34 wire, 1-2, 5, 10, 13, 16-17, 20, 23-24, 27-28 Wireless, 2, 7, 30 wireless, 1-2, 7 wirelessly, 7 wires, 7 Wiring, 34 wiring, 1, 17, 24 With, 2, 7, 29 with, 1-14, 16, 18, 20-25, 28, 31-34 within, 1-2, 4, 6, 8, 11-12, 15, 28 without, 3, 8, 10-11, 13, 16, 20, 23-24, 28 work, 3 Workstation, 9 would, 7 WPRC, 30 www, 1-34 WX, 30 X Xckt, 20 XML, 6 Y Yale, 32 year, 7 Yes, 5-6 YesCSA, 6 YesEthernet, 6 YesProtocols, 6 YesTime, 6 you, 7 your, 2, 7, 15 yrs, 6 YS, 10, 13, 16, 20, 23, 28 Z Zone, 24 zone, 2-3, 7, 24, 28, 30 Zones, 24, 28 zones, 1, 3, 5-6, 24, 27 Zoning, 27