ANSI/IEEE Std 995-1987 IEEE Recommended Practice for Efficiency Determination of Alternating-Current Adjustable-Speed Drives Part I-Load Commutated Inverter Synchronous Motor Drives Published by The Institute of Electrical and Electronics Engineers, Inc 345 East 47th Street, New York, N Y 10017, USA March 21. 1988 SHIIBIO ANSI / IEEE Std 995-1987 An American National Standard IEEE Recommended Practice for Efficiency Determination of Alternating-Current Adjustable-Speed Drives Part I Load Commutated Inverter Synchronous Motor Drives Sponsor Industrial Drives Committee of the IEEE Industry Applications Society Approved March 12, 1987 IEEE Standards Board Approved September 11, 1987 American National Standards Institute @ Copyright 1988 by The Institute of Electrical and Electronics Engineers, Inc 345 East 47th Street, New York, NY 10017, USA No part of this publication m a y be reproduced in any form, in a n electronic retrieval system or otherwise, without the prior written permission of the publisher. IEEE Standards documents are developed within the Technical Committees of the IEEE Societies and the Standards Coordinating Committees of the IEEE Standards Board. Members of the committees serve voluntarily and without compensation. They are not necessarily members of the Institute. The standards developed within IEEE represent a consensus of the broad expertise on the subject within the Institute as well as those activities outside of IEEE which have expressed an interest in participating in the development of the standard. Use of an IEEE Standard is wholly voluntary. The existence of an IEEE Standard does not imply that there are no other ways to produce, test, measure, purchase, market, or provide other goods and services related to the scope of the IEEE Standard. Furthermore, the viewpoint expressed at the time a standard is approved and issued is subject to change brought about through developments in the state of the art and comments received from users of the standard. Every IEEE Standard is subjected to review at least once every five years for revision or reaffirmation. When a document is more than five years old, and has not been reaffirmed, it is reasonable to conclude that its contents, although still of some value, do not wholly reflect the present state of the art. Users are cautioned to check to determine that they have the latest edition of any IEEE Standard. Comments for revision of IEEE Standards are welcome from any interested party, regardless of membership affiliation with IEEE. Suggestions for changes in documents should be in the form of a proposed change of text, together with appropriate supporting comments. Interpretations: Occasionally questions may arise regarding the meaning of portions of standards as they relate to specific applications. When the need for interpretations is brought to the attention of IEEE, the Institute will initiate action to prepare appropriate responses. Since IEEE Standards represent a consensus of all concerned interests, it is important to ensure that any interpretation has also received the concurrence of a balance of interests. For this reason IEEE and the members of its technical committees are not able to provide an instant response to interpretation requests except in those cases where the matter has previously received formal consideration. Comments on standards and requests for interpretations should be addressed to: Secretary, IEEE Standards Board 345 East 47th Street New York, NY 10017 USA IEEE Standards documents are adopted by the Institute of Electrical and Electronics Engineers without regard to whether their adoption may involve patents on articles, materials, or processes. Such adoption does not assume any liability to any patent owner, nor does it assume any obligation whatever to parties adopting the standards documents. Foreword (This Foreword is not a part of ANSI/IEEE Std 995-1987, IEEE Recommended Practice for Efficiency Determination of Alternating-Current Adjustable-Speed Drives) This recommended practice was prepared by the Industrial Drives Committee of the IEEE Industry Applications Society. Working Group P995 was established in 1983 to define a consistent method for determining and specifying the efficiency of large adjustable-speed alternating-current motordrive systems. The working group was divided into two groups designated P995.1 and P995.2 with assigned responsibilities for load commutated inverter synchronous motor drives and self-commutated inverter induction motor drives, respectively. The membership of the working group that prepared this recommended practice was as follows: Herbert W. Weiss, Chairman Nirmal K. Ghai Leonard P. Gripp Gunter Hausen Thomas A. Higgins, J r James L. Kirtley, J r Charles P. Lemone Edward F. Munk Donald W. Novotny James Oliver Claude L. Philibert Dana Ralston Mohammad Safiuddin John Yost The following persons were on the balloting committee that approved this recommended practice for submission to the IEEE Standards Board: Albert0 Abbondanti John P. C. Allen Thomas H. Barton Jesse A. Batten Bimal K. Bose William D. Brand Dennis H. Braun Frederick C. Brockhurst Jimmie J . Cathey Edward P. Cornel1 C. J . Cowie A. Malcom Curry Shashi B. Dewan Paul C. Donatelli Richard F. Dugan Ben Esar Donald Galler David C. Hamilton Gunter Hausen Richard G. Hoft S. S. Hubli Peter Huetter Linos J . Jacovides Thomas M. Jahns Atsuo Kawamura Yuri Khersonsky Daniel Kirschen Frank N. Klein Alexander Kusko Thomas S. Latos James F. Lindsay Thomas A. Lip0 Robert D. Lorenz James Lousier Robert B. Maag Walter A. Maslowski George MacMunn Ian M. MacDonald Paul McNally H. Paul Meisel Richard W. Miller T. J. E. Miller Balarama V. Murty Syed A. Nasar Thomas W. Nehl N. E. Nilsson Donald W. Novotny Guy Oliver Steven Peak Erland K. Persson Allan B. Plunkett Thomas H. Putman M.A. Rahman M. H. Rashid Thomas Rehm Harold Romanowitz Mohammed Safiuddin Lee A. Schlabach Paresh C. Sen Frank E. Simo Jon W. Simons Gordon R. Slemon Victor R. Stefanovic Loren F. Stringer George H. Studtmann K. Reed Thompson Peter J. Tsivitse Henry W. Wearsch Herbert W. Weiss Francis M. Wells George Younkin When the IEEE Standards Board approved this standard on March 12, 1987, it had the following membership: Donald C. Fleckenstein, Chairman Marco W. Migliaro, Vice Chairman Sava I. Sherr, Secretary James H. Beall Dennis Bodson Marshall L. Cain James M. Daly Stephen R. Dillon Eugene P. Fogarty Jay Forster Kenneth D. Hendrix Irvin N. Howell Member emeritus Leslie R. Kerr Jack Kinn Irving Kolodny Joseph L. Koepfinger' Edward Lohse John May Lawrence V. McCall L. Bruce McClung Donald T. Michael* L. John Rankine John P. Riganati Gary S. Robinson Frank L. Rose Robert E. Rountree William R. Tackaberry William B. Wilkens Helen M. Wood Contents SECTION PAGE 1. Scope .................................................................................................. 5 2. Reference ............................................................................................. 5 3. Definitions ............................................................................................ 3.1 Basic Terms ................................................................................... 3.2 Performance Characteristics ................................................................ 3.3 Letter Symbols................................................................................ 6 6 8 9 4. System Description .................................................................................. 4.1 Line-Side Interface ........................................................................... 4.2 Power Converter .............................................................................. 4.3 DC Link Inductor ............................................................................ 4.4 Synchronous Machine ....................................................................... 4.5 Service Conditions ............................................................................ 9 9 10 10 10 11 5. Efficiency Determination ........................................................................... 5.1 Methods for Determination of Losses ...................................................... 5.2 System Operating Parameters .............................................................. Determination of Losses ..................................................................... 5.3 5.4 Recording of Losses .......................................................................... Determination of Efficiency ................................................................. 5.5 12 13 13 13 20 20 FIGURES Drive System Configuration .................................................................. Converter Circuit Elements .................................................................. Waveform Definitions ......................................................................... Transformer Circuits .......................................................................... Typical Power Converter ...................................................................... Efficiency Determination ..................................................................... Dual Winding Machine Test .................................................................. Converter DC Circuit .......................................................................... 5 7 8 10 11 12 14 18 Table 1 Reference Temperature for Load Losses .................................................... Table 2 Tabulation of Losses ............................................................................ 12 19 Fig 1 Fig 2 Fig 3 Fig 4 Fig 5 Fig 6 Fig 7 Fig 8 TABLES APPENDIXES Appendix A Appendix B Explanation of Practices and Procedures ............................................ Example Efficiency Determination ................................................... 21 29 APPENDIX TABLES Table B1 Table B2 Tabulation of Losses ....................................................................... Tabulation of Losses ....................................................................... 29 30 An American National Standard IEEE Recommended Practice for Efficiency Determination of Alternating-Current Adjustable-Speed Drives Part I Load Commutated Inverter Synchronous Motor Drives 1. Scope included herein to account for operating characteristics of the adjustable-speed drive systems. This recommended practice proposes a method for determining the efficiency of large, adjustable-speed ac motor-drive systems consisting of a load commutated inverter and a synchronous machine, in which a dc-linked converter is connected between the line and the load. This recommended practice is directed primarily to high-capacity systems (exceeding 1000 hp) and drive systems, which normally include equipments such as transformers, reactors, thyristor power converters, and synchronous machines. The drive system configurations, which are covered specifically in this recommended practice, are shown in Fig 1. The method recommends that the existing test standards for the system equipments be used as reference, supplemented by test and calculations 2. References The standards listed below cover the definition of losses and efficiency, and the test methods for the equipments that are part of the adjustable-speed drive system. When approved revisions of the reference standards are issued, the revision should be used. This recommended practice should be used in conjunction with the following publications: [l]ANSI C50.10-1977, American National Standard General Requirements for Synchronous Machines.' ANSI publications are available from the Sales Department, American National Standards Institute, 1430 Broadway, New York, NY 10018. Fig 1 System Configurations (a) Single Channel System (b)Dual Channel Parallel System ( c ) Dual Channel Series System la) (bl 1 I I I POWER SOURCE LINE SIDE INTERFACE LINE SIDE CONVERTER DC LINK INDUCTOR LOAD SIDE CONVERTER SYNCHRONOUS MACHINE FORM C CONVERl 5 ANSI / IEEE Std 995-1987 AC ADJUSTABLE-SPEED DRIVES sion, comprising one or more electronic switching devices and any associated components, such as transformers, filters, commutation aids, controls, and auxiliaries. [2] ANSI (37.16-1958 (R1971), American National Standard Requirements, Terminology, and Test Code for Current-Limiting Reactors. [3] ANSI / IEEE C57.12.00-1987, IEEE Standard General Requirements for Liquid-Immersed Distribution, Power and Regulating Transformew2 direct-current linked alternating-current converter. A converter comprising a rectifier and an inverter, with a n intermediate dc link. [4] ANSI / IEEE C57.12.01-1979, IEEE Standard General Requirements for Dry-Type Distribution and Power Transformers. NOTES: (1)This definition is intended to include only those circuits in which the dc link is readily identified or explicit, and not those circuits having an implicit dc link but no single pair of conductors that can be identified as the dc link. (2) For the purpose of this recommended practice the rectifier and inverter are form C converter. [5] ANSI / IEEE C57.12.90-1987, IEEE Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers and Guide for Short-circuit Testing of Distribution and Power Transformers. externally commutated converter.A converter in which the commutating voltages are supplied by the ac supply lines, the ac load, or some other ac source outside the converter. [6] ANSI / IEEE (37.12.91-1979, IEEE Standard Test Code for Dry-Type Distribution and Power Transformers. [7] ANSI / IEEE C57.110-1986, IEEE Recommended Practice for Establishing Transformer Capability when Supplying Nonsinusoidal Load Currents. NOTE: For the purpose of this recommended practice, the term converter should be used. form C converter. A single converter unit in which the direct current can flow in one direction only and which is capable of inverting energy from the load to the ac supPly. [8] ANSI / IEEE Std 100-1984, IEEE Standard Dictionary of Electrical and Electronic Terms. [9] ANSIIIEEE Std 115-1983, IEEE Guide: Test Procedures for Synchronous Machines. inverter. A converter for conversion from [lo] ANSI / IEEE Std 444-1973, IEEE Standard Practices and Requirements for Thyristor Converters for Motor Drives Part I-Converters for DC Motor Armature Supplies. dc to ac. NOTE: For the purpose of this recommended practice the loud side converter normally operates as an inverter. [ l l ] ANSI / NEMA MG1-1978, Standards Publication for Motors and Generators. load commutatedinverter. A converter in which the commutation voltages are supplied by the ac load. [12] FISCHER, J.D., So You Don’t Think You Have a Harmonic Problem. Conference Record, 1979, IEEE Industry and Applications Society Annual Meeting (Power Systems Protection Committee), Table IV, 41D. NOTE: For the purpose of this recommended practice the ac load is a synchronous machine operating as a motor. rectifier. A converter for conversion from ac to dc. NOTE: For the purpose of this recommended practice the line-side converter normally operates as a rectifier. 3. Definitions 3.1 Basic Terms 3.1.1 converter or converter equipment. 3.1.2 convertor circuit elements (see Fig 2) An operative unit for electronic power conver- ac filter. Resistor-capacitor circuits connected in three-phase wye or delta on the ac terminals of a converter. ANSI / IEEE publications are available from IEEE service Center, 445 Hoes Lane, PO Box 1331,Piscataway, NJ 08855-1331,or from the Sales Department, American National Standards Institute, 1430 Broadway, New York, NY 10018. converter switching element. A part of 6 ANSI / IEEE Std 995-1987 LOAD COMMUTATED INVERTER DC LINK IN DUCT0 R LINESIDE LOADSIDE LINE SIDE TERMINALS Fig 2 Converter Circuit Elements the converter circuit, bounded by two principal terminals, containing one or more semiconductor devices having the property of controllable or noncontrollable conduction in a t least one direction. principal terminal. A terminal (of a device or circuit element) through which passes the current transmitting the power that is controlled by the device or circuit element. The term is used for distinction from control terminals, monitoring signal terminals, etc. dc filter. A resistor-capacitor circuit connected between the positive and negative terminals of the dc link. NOTE: Examples of principal terminals are the anode and cathode of thyristor or diode devices, the collector and emitter of bipolar transistor devices, and the source and drain of fieldeffect transistor devices. equalizing resistor. The resistor connected across the circuit element to equalize the off state voltage across elements that are connected in series. snubber. An auxiliary circuit element or combination of elements employed to modify the transient voltage or current of a semiconductor device during switching. principal branch (main branch). A branch involved in the major transfer of energy from one side of the converter to the other. (1) shunt snubber. Circuit elements, usually including a capacitor and a resistor connected in shunt with a switching device to limit the rate of rise of voltage 7 ANSI / IEEE Std 995-1987 AC ADJUSTABLE-SPEED DRIVES 3.1.3 Circuit Properties or the peak voltage across the device (or both) when switching from a conducting to a blocking state or when subjected to a n external voltage transient. (2) series snubber. Circuit elements, usually including an inductor, connected in series with a switching device to limit the rate of rise or fall of current through the device when switching on or off, respectively. commutation.The transfer of current from one converter switching branch to another. commutating voltage. The voltage that causes the current to commutate from one switching branch to another. NOTE: In an externally commutated converter, the commutating voltage is supplied by an ac source outside the converter. switching branch. A part of the circuit, including at least one switching element, Performance Characteristics bounded by two principal terminals. direct current. The time average value of NOTE: A switching branch may include one or more simultaneously conducting converter switching elements connected together, commutating reactor windings, and other devices intended to protect the semiconductor devices or to ensure their proper function, such as voltage and current dividers, and snubbers. In the simplest case, a switching branch may consist of only the switching element, which may be a single semiconductor device. The adjective switching may be omitted when the context of converter circuits is clear. the current in the dc link. line-side converter alternating current. The magnitude of the current expressed in amperes of the rms value of current at the output terminals of the line-side interface and the input terminals of line-side converter. Fig 3 Waveform Definitions f- PHASE VOLTAGE +-%% PHASE CURRENT 4 0 L P H A S O R ANGLE LOAD-SIDE CONVERTER PHASE VOLTAGE (COMMUTATING VOLTAGE) FUNDAMENTAL A T SYNCHRONOUS MACHINE / / FUNDAMENTAL PHASE CURRENT MACHINE CURRENT 8 ANSI / IEEE Std 995-1987 LOAD COMMUTATED INVERTER line-side converter ac voltage. The rms power-frequency voltage from line to line at the ac terminals of the line-side converter. NOTE: This voltage is the same as the rated system voltage times the turns ratio of the input interface equipment. load-side converter ac voltage. The rms value of the power-frequency sinusoidal envelope of voltage at the ac terminals of the load-side converter (Fig 3). This is the commutating voltage of the load-side converter. NOTE. This is the voltage that appears at the terminals of the synchronous machine and is not the rms fundamental sine-wave voltage of the machine. machine current. The rms magnitude of the fundamental sinusoidal current at the terminals of the machine. machine voltage. The rms value of the fundamental sinusoidal voltage at the terminals of the machine. phasor power factor. The power factor of the synchronous machine defined by the cosine of the phasor angle between the fundamental sinusoidal phase voltage and the fundamental sinusoidal phase current. NOTE: This is not the angle between the load converter commutating voltage and the machine current (See Fig 3). rated system frequency. The frequency expressed in hertz, of the power system alternating voltage. rated system voltage. The rms power-frequency voltage from line to line that has been designated as the basis for the system rating. The line-side interface equipments may or may not have the same rated voltage. 3.3 Letter Symbols Ed = direct voltage, average E = rms ac fundamental line-line voltage at the synchronous machine E , = rms ac fundamental phase voltage a t the synchronous machine E L = rms ac system line-line voltage I d = direct current, average I, rms fundamental line current a t the synchronous machine armature I L = rms ac line current at line-side converter P = active (real) power, average FPP= phasor power factor 4 = phasor power-factor angle p = commutation overlap angle expressed in degrees a = delay angle, expressed in degrees p = pulse number of a commutating group = I ~ = RI ~ R = open circuit core loss SL = stray loss PRS = armature (stator) I ~ loss R 12RR = field (rotor) 12R loss P h = harmonic losses due to nonsinusoidal voltage and current KWRL = test and drive motor running light losses I'RDMC = drive motor 12Rloss correction KWDM = drive motor input power KWEX = exciter input power OCCL 4. System Description The drive system consists of the equipments that are utilized to convert electric energy from the plant bus to mechanical energy in the form of shaft speed and torque. The typical system configurations are shown in Fig 1. For the purpose of this recommended practice the drive system efficiency is determined by the losses associated with the equipments listed below and do not include the losses associated with interconnecting cables or power switchgear equipment. NOTE: The interconnecting cable and power switchgear equipment losses may be included in the efficiency determination if so specified. 4.1 Line-Side Interface. The line-side interface is the equipment that is connected between the power source and the power converter. This equipment serves to insert impedance between the converter and the power source, or to establish electrical isolation between the converter system and the power source, or to transform the voltage from the power source level to converter system level, or a combination of these ANSI / IEEE Std 995-1987 AC ADJUSTABLE-SPEED DRIVES wye) for use with thyristor converter circuit number 31 as shown in Fig 4 (see ANSI / IEEE Std 444-1973 [lo], Fig 6) (3) Line reactors iron or air core The losses for the line-side interface equipment should include no-load and load losses. In addition, the losses for auxiliary devices that are required for the equipment to perform its function should be included in the equipment loss. These auxiliary devices might be fans or pumps for the equipment cooling system. CIRCUIT NUMBER 23 DELTA-WYE, THREE-PHASE BRIDGE (DOUBLE-WAY). SIX-PULSE 4.2 Power Converter. The power converter CIRCUIT NUMBER 25 equipment includes the power and control electronics that convert and condition the power from the line-side interface to the power that is applied to the synchronous machine to achieve adjustable speed at the machine shaft. The power converter is a dc-linked ac converter consisting of a line-side converter to convert fixed frequency ac power to dc power and a load-side converter to invert dc power to adjustable frequency ac power for an adjustable speed synchronous machine. The control electronics include the gating circuits for the power converters, the protective functions and the drive system logic and regulating functions. The excitation control for the synchronous machine is also included in the control electronics, whether ac or dc. Any auxiliary devices that may be required by the power converter to perform its function should be included within its scope. These might be cooling fans, pumps, power supplies and UPS systems, etc. The typical power converter configuration is shown in Fig 5. DELTA-DELTA, THREE-PHASE BRIDGE (DOUBLE-WAY),SIX-PULSE CIRCUIT NUMBER 31 DE LTA-DELTANvY E, THREE-PHASE MULTIPLE-BRIDGE (DOUBLE-WAY), TWELVE-PULSE NOTE:Circuit numbers 23,25, and 31 aretakenfromANSI/ IEEE Std 444-1973 [lo]. Fig 4 Transformer Circuits 4.3 Direct-CurrentLink Inductor.This equip- ment is connected between the line-side converter and the load-side converter and forms a part of the dc link of the power converter. The losses for this equipment are those that are incident to the carrying of current. In addition, losses of auxiliary devices required by the equipment to perform its function should be included. These auxiliary devices might be fans or pumps for the cooling system. functions. The line-side interface equipment may be one or more of the following (l), (2), (3): (1) Isolation transformer with one primary winding and one secondary winding for use with thyristor converter circuit numbers 23 and 25 as shown in Fig 4 (see ANSI / IEEE Std 444-1973 [lOI3,Fig 6) (2) Isolation transformer with one primary winding and two secondary windings (delta and 4.4 Synchronous Machine. The synchronous machine converts the electric power from the power converter to mechanical power to the driven load. The power to the machine includes that delivered to the armature winding (or windings in the case of dual-winding machines) and the field winding or rotating exciter. The numbers in brackets correspond to those of the references in Section 2. 10 ANSI / IEEE Std 995-1987 LOAD COMMUTATED INVERTER DC LINK INDUCTOR LINESIDE LOADSIDE LINE SIDE INTERFACE SYNCHRONOUS MACHINE I I I I I I I I r- I I I I I I I I I I I COOLING SYSTEM LOGIC I T ( - AND CONTROL AUXILIARY CONTROL POWER I I b EXCITATION CONTROL I I Fig 5 Typical Power Converter 4.5.2 Reference Altitude and Ambient Temperature. Altitude at factory site: The losses of auxiliary devices that are required for the equipment to perform its function should be included. These might be auxiliary blowers for ventilation or lube pump when the machine has a dedicated system. Ambient Temperature (1) 20 "C for transformers, reactors and inductors (2) 25 "C for synchronous machines (3) 40 "C for power conversion /control 4.5.3 Temperature Reference for Load 4.5 Service Conditions. For the purpose of this recommended practice the determination of equipment losses should be based on the service conditions listed below. 4.5.1 Input Voltage. The rms power-frequency voltage applied to the primary terminals of the line-side interface equipment should be taken as the rated system voltage and frequency that has been designated for the system. Loss (1) When the equipment is tested for winding temperature rise at a specific load, the reference temperature should be taken as the measured average temperature rise (by resistance) plus the reference ambient temperature listed in 4.5.2. (2) When the equipment is not tested for winding temperature rise at a specific load, the ref11 ANSI / IEEE Std 995-1987 AC ADJUSTABLE-SPEED DRIVES Table I Reference Temperature for Load Loss Class of Insulation Svstem A B 5. Efficiency Determination The efficiency of the adjustable-speed drive system should be determined from the summation of the segregated losses of the drive system equipments that are measured or calculated, or both, as described in these recommendations at a specific drive operating point or points. The efficiency of the drive system is given by the following equation: Reference Temperature "C 75 95 115 130 F H erence temperature should be taken from Table 1. The reference temperature should be used for determining load losses a t all loads. If the rated temperature rise for the equipment is specified as that of a lower class of insulation system, the temperature for resistance correction should be that of the lower temperature rise. 4.5.4 Temperature Reference for Bus and Cable. The reference temperature of the current carrying conductors should be taken as 90 "Cfor bare bus and 75 "C for insulated bus or cable. Efficiency (%) = output * 100 losses output + A drive operating point is defined in terms of (1) Shaft speed (2) Shaft torque (or horsepower) The procedure for the determination of the losses is illustrated in Fig 6. Fig 6 Efficiency Determination OPERATING POINTS 1 I METHODS (5.2) SYSTEM OPERATING PARAMETERS I I (5.1) METHODS FOR DETERMINATION OF LOSSES I I FUNDAMENTAL SINE-WAVE LOSSES 5.2.1 I 1 I I (2)ADJUSTMENT LOSSES 5.2.2 5.3.1.3 SYNCHRONOUS MACHINE 5.3.2.2 ISOLATION TRANSFORMER 5.3.3.2 LINE REACTOR 5.3.4(3) DC LINK INDUCTOR 5.3.4(4) DC LINK INDUCTOR 5.3.5.3 POWER CONVERTER 5.3.5.4 POWER CONVERTER LOSSES I 5.3.1 SYNCHRONOUS MACHINE 5.3.2 ISOLATION TRANSFORMER 5.3.3 LINE REACTOR 5.3.4 ( 1 ) (2)DC LINK INDUCTOR 5.3.5.2 (1) POWER CONVERTER AUXILIARY LOSSES 12 5.3.1.4 SYNCHRONOUS MACHINE 5.3.3.3 LINE REACTOR 5.3.4(4) DC LINK INDUCTOR 5.3.5.5 POWER CONVERTER 5.3.5.6 POWER CONVERTER ANSI / IEEE Std 995-1987 LOAD COMMUTATED INVERTER (2) DC link inductor 5.1 Methods for Determination of Losses. The equipment losses should be determined by one of the following methods, which are recommended by this recommended practice. (1) Fundamental sine-wave losses that can be determined by test (2) Harmonic losses that are determined by a standard adjustment factor applied to sine-wave losses (3) Losses that are determined by a standard calculation procedure (4) Auxiliary system losses that can be determined by test are to be included in the total equipment loss. The recommended practices herein include practices and procedures that are simplified to minimize the complexity when the accuracy of the results is not significant. When a simplified practice or procedure is used to reduce complexity it is identified by the symbol P followed by a numeral in the right-hand margin of the column. The explanation of the simplified practice or procedure is presented in Appendix A. IT Id = Ia 3 P2 (3) Power converter IT Id = Ia 3 P2 Line-side converter a = c0s-l C92j p3 Load-side converter a = -cos-' (0.95F,,) P4 ~ and Load-side converter E L = E p = 0 for both converters 5.3 Determination of Losses 5.3.1 Synchronous Machine. The segregated losses of a synchronous machine should be determined using the test procedure outline in ANSI/IEEE Std 115-1983 [9] as amended by the additional test procedures, harmonic losses, and auxiliary losses presented in this section. 5.3.1.1 Additions to ANSI/IEEE Std 1151983 [9] (1) Methods of Loss Measurements. For the purpose of this recommended practice one of the following test methods should be used: ANSI / IEEE 115-1983 [9], 4.2, Separate-drive method ANSI / IEEE 115-1983 [9], 4.3, Electric-input method (2) Operating Parameters for Testing. For the purpose of this recommended practice the machine may be tested at operating points other than at rated speed, rated voltage, and rated current. Therefore, rated speed, voltage, and current should be that assigned only for the test, as defined in 5.2.1 of this recommended practice. (3) Test Speed and Torque. The machine should be tested at the speed at which the losses are to be determined. For each test speed, the following operating parameters should be defined. (a) Speed (and frequency) (b) Shaft torque (c) Fundamental sine-wave voltage, E (d) Fundamental sine-wave current, I , (e) Fundamental phasor power factor, F,, 5.3.1.2 Additional Test Procedures (1) Testing for dual winding machine 5.2 System Operating Parameters. The drive system efficiency is a function of the equipment losses at a given operating point. The operating point as previously defined is in terms of shaft speed and torque (or horsepower). For each of the specified operating points the system operating parameters should be defined as the base for determining the equipment losses. 5.2.1 SynchronousMachine Operating Parameters. The operating parameters for each equipment should be derived from the operating parameters of the synchronous machine a t a given bperating point. The following machine operating parameters should be specified by the system supplier for each operating point that is selected for efficiency determination: (1) Shaft speed (2) Shaft torque (or horsepower) (3) Fundamental sine-wave voltage, E (4) Fundamental sine-wave current, I , (5) Fundamental phasor power factor, F,, 5.2.2 System Equipment Operating Parameters. The operating parameters for the other system equipments should be determined by the following procedure. (1) Line-side interface P1 (Fig 7) 13 ANSI / IEEE AC ADJUSTABLE-SPEED DRIVES Std 995-1987 i NORMAL CONNECTION TEST CONNECTION METHOD 2 TEST CONNECTION METHOD 1 Fig 7 Dual Winding Machine Test (a) Separate Drive Method. Each of the two stator windings should be tested independently and simultaneously. For the open-circuit core loss test and saturation curve, measure and record the open-circuit voltage in all three phases of each winding a t each data point during the test. The opencircuit core loss may be obtained by subtracting the following losses from the drive motor plus the exciter input power at each data point. KWRL I f V f (see 5.3.1.2(2)(a)) KW exc loss (see 5.3.1.2(2)(a))exciter electrical loss I~RDMC 12RS, stator 12R loss at the average winding temperature at each test point. Thus the short-circuit core loss at each point is: SCCL = KWDM KWEXC - KWRL - 12RR - KW exc loss - 12RS - 12RDMC. + (i) KWRL, the test and drive motor running light losses (ii) I f V f ,the test motor rotor 12RR (see 5.3.1.2(2)(a)) (iii) KW exc loss, (see 5.3.1.2(2)(a)).Exciter electrical loss. (iv) I’RDMC, the drive motor 12R loss correction from running light losses, if any Thus the open-circuit core loss at each point is: OCCL = KWDM KWEXC - KWRL - 12RR - KW exc loss - 12RDMC For the short-circuit core loss test, and saturation curve, short circuit the three phases of each winding together independently and measure and record the short-circuit current in all three phases of each winding at each data point during the test. The short-circuit core loss may be obtained by subtracting the following losses from the drive motor plus exciter input power. @) Electric-Input Method. These motors present a special problem. To test them, two three-phase power supplies with 30 electrical phase difference are needed, which may not be available to the manufacturer’s facility. These motors can, however, be tested by interconnecting the windings. Method 1-Delta Connection. The two threephase windings with 30°C phase belt have phases A, B, C and A’, B’, C’, the test can be made by connecting Phase A in series with Phase A’; Phase B in series with Phase B’; and Phase C in series with Phase C’;. The 3 phases thus obtained are then connected in delta. The motor should now be tested with a single three-phase power supply at equivalent voltage and line currents given below: + I* = 14 0.746 - h p 77m . cos . J3 . E ~ lop3 . + ANSI / IEEE Std 995-1987 LOAD COMMUTATED INVERTER Ert = 2Efm cos 15" (approximately) Armature 12R loss = (armature 12R loss a t IrJ (cos 15 1' ' a where Ert = rated line fundamental rms voltage for test, V Ef, = rated motor line fundamental rms voltage, V Irt= rated line rms current for test, A I p h t = phase current measured for I r t line current, A hp = rated horsepower of the motor qm = calculated motor efficiency at rated load in per unit cos 4 = motor rated phasor power factor The open-circuit core loss, friction and windage loss, stray loss and field 12R loss and armature 12R loss are determined for Ert and Irt at rated power factor. The armature 12Rloss and stray load loss are then corrected for efficiency determination as follows: Armature 12R loss = (armature loss at Irt) . (cos 15°)2.K Stray load loss = (stray load loss a t Irt) . (cos 15 . K P5 NOTE: The results should be corrected for 3rd harmonic circulation current as follows: Method 2-Wye Connection. The two threephase windings with 30 "Cphase belt and having phases A, B, C and A', B', C' are first connected as follows: Phase A is connected in series with Phase A'; Phase B in series with Phase B' and Phase C in series with Phase C'. Now we have winding with 60 phase belts. This winding is connected as wye. The motor can now be tested with single three-phase power supply at equivalent line voltage and line current given below: E* = Irt = 2 Efm COS 15" 0.746 * hp qm . cos 4 .a. E ~ 10-3 . The armature 12Rloss and stray load loss are then corrected for efficiency determination as follows: Stray load loss = (stray load loss a t I*) . (cos 15")2 (2) Brushless Exciter Losses. The brushless exciter consists of the stator, rotor, rotor bearings (when supplied as part of the exciter), power rectifier elements (semiconductors, surge suppressors, heat sinks) and interconnecting cables. The following test methods are recommended to determine exciter losses: (a) Separate-Drive Method. This test can be executed during the regular segregated loss tests at the designated test speed. (i) Use a calibrated drive motor of reasonable size relative to the losses of the test motor (see ANSI/IEEE Std 115-1983, [9], 4.2.1). (ii) Mount a dc shunt on the exciter rotor and attach a n instrument collector to read the test motor field current and voltage Ifand Vf. (iii) Measure the power (watts) input to the exciter stator. The sinusoidal stator voltage is adjusted to achieve the desired rotor field current. Data can be taken during the OCCL test since that loss also must be measured. The data should be taken in steps from 20% to approximately 110% of rated full-load field current. The exciter loss curve can be established by using the following example. From the classic "M" induction motor equations: Exciter KWtotal= KWEXC stator input . slip Shaft power = (slip - 1.0) . KW stator input where +KW = power in the exciter shaft -KW = power out the exciter shaft I ~ motor R rotor = I ~ R R Exciter electrical losses = KWtotal - IfVf = kw exc loss + Slip = rated speed operating speed rated speed for contra-rotation Slip = rated speed - operating speed rated speed for standard (forward rotation) rated speed = freq . 60 poled2 ANSI / IEEE Std 995-1987 AC ADJUSTABLE-SPEED DRIVES in the rotor winding caused by the rectifier connection, and the harmonic currents in the stator that are induced from the rotor. These harmonic losses are included in the test methods that are recommended in sections 5.3.1.2(2)(a) and 5.3.1.2(2)@).When these recommended methods are not used and the exciter stator and rotor are tested on sinusoidal power without the rectifier, the additional loss is given by The exciter friction and windage loss is included with the motor friction and windage. The diode drop losses are measured as a part of the electrical losses by this method. (b) Electrical-Input Method. Same as Separate-Drive Method. (c) ANSUIEEE Std 115-1983 [9], 4.1.3 should be deleted when the machine is equipped with a brushless exciter. 5.3.1.3 Harmonic Losses. The test procedures outlined in ANSI/IEEE Std 115-1983 [9] are based on sinusoidal voltage and current and do not include a measurement of the losses that are produced in the machine when it operates with nonsinusoidal voltage and current. For the purpose of this recommended practice, the harmonic losses are calculated as a fixed percentage of the fundamental sine-wave losses at the specified operating point defined in 5.3.1.1(3). The fixed percentage harmonic loss factor should be used for the efficiency determination unless a specific calculation procedure is established and agreed upon between the system supplier and the user. Ph 0.2 5.3.1.4 Auxiliary Losses. The auxiliary losses are classified as Ventilating and Cooling Loss (see ANSI C50.10-1977 [l], 7.3.10). When externally driven ventilation equipments are required, this power should be measured by conventional wattmeter methods and included in the losses assigned to the machine. 5.3.2 Isolation Transformer. The losses of the transformer should be determined using the test procedures outlined in ANSI/IEEE C57.12.90-1987 [5] and ANSI/IEEE C57.12.911979 [6] as amended by the harmonic loss, auxiliary loss, and additions presented in this section. 5.3.2.1 Additions to ANSI/IEEE C57.12.90-1987 [5] and ANSI/IEEE C57.12.911979 [6]. For the purpose of this recommended practice the rated current for the load-loss test should be taken from the operating parameter given in 5.2.2. The rated current for the load loss is given by IT IL = P6 + = k2 . (sine-wave load losses) I, 3 P1 5.3.2.2 Harmonic Losses. The harmonic currents increase the stray losses as described in ANSI/IEEE C57.110-1986 [7]. The increased losses due to harmonic current should be taken as a fixed multiplier of the stray load loss at the specified operating point. where 12RS sine-wave load losses = SL k1 = 0.3 (2)Dual Winding Machine Operating with SixPulse Converter Connected to each Three-phase Winding. The two windings are phase displaced 30 electrical degrees. The additional loss due to nonsinusoidal voltage and current is given by Ph P8 k3 = (1) Three-phase Machine Operating with SixPulse Converter. The additional loss due to nonsinusoidal voltage and current is given by . (sine-wave load losses) . (exciter electrical sine-wave loss) where NOTE: The adjustment for harmonic losses is intended for efficiency determination only and in no way should be used as a design criteria for temperature rise of the machine. The temperature rise of the machine is the responsibility of the machine manufacturer. The adjustment for harmonic losses listed below, K1 and K z , assumes that the machine has a laminated salient pole construction with amortisseur windings and closed end rings. For other types of machine construction the adjustment for harmonic losses should be specified. p h = k1 = k3 p h = k4 - (stray load loss) P9 where k4 P7 3 where sine-wave load losses = SL kz = 0.15 NOTE: The harmonic losses calculated by this method are for the purpose of this recommended practice and should not be used as a measure of winding temperature rise. (3)Brushless Exciter. The additional losses in the exciter are generated by harmonic currents 5.3.2.3 Auxiliary Losses. The power for auxiliary devices, such as pumps or fans, which + 12RS 16 ~ ANSI / IEEE Std 995-1987 LOAD COMMUTATED INVERTER be measured by conventional wattmeter methods and taken as a loss. (5) When iron-core inductors are applied, core losses should be taken as a fixed multiplier of the 12R loss at the operating point. Pc = k6 * 12R lOSS P11 are required to operate for the transformer to perform its function, should be measured by conventional wattmeter methods and stated as a loss. 5.3.3 Line Reactor. The losses of the line reactors should be determined using the test procedures outlined in ANSI (357.16-1958 (R 1971) [2] as amended by the harmonic loss, auxiliary loss, and additions presented in this section. 5.3.3.1 Additions to ANSI C57.16-1958 (R 1971) [2]. For the purpose of this recommended practice the rated current for the load loss test should be taken from the operating parameters given in 5.2.2. The rated current for the load loss test is given by IL = I, 7T - 3 where k6 = P1 5.3.3.2 Harmonic Losses. The harmonic currents increase the stray loss. The increased loss due to harmonic current should be taken as a fixed multiplier of the stray loss at the specified operating point. P h = k5 . (stray loss) P9 where k5 = 3 NOTE: The harmonic losses calculated by this method are for the purpose of this recommended practice and should not be used as a measure of winding temperature. 5.3.3.3 Auxiliary Losses. The power for auxiliary devices, such as pumps or fans, which are required to operate for the reactor to perform its function, should be measured by conventional wattmeter methods and stated as a loss. 5.3.4 Direct-Current Link Inductor (1)The losses in an air-core inductor should be the 12R losses. The current to be used to determine the loss should be taken from the operating parameters specified in 5.2.2. I -I 7T 0.05 5.3.5 Power Converter. The losses of the power converter should be determined using the procedures outlined in this section. The losses should be determined for the operating parameters specified in 5.2.2. 5.3.5.1 Classification of Losses. The following losses should be included: (1)Losses in thyristors (2) Power circuit connection losses should include power circuit fuses, bus and cable, branch or line reactors, current balancing devices (3) Losses in filters, thyristor snubbers, and voltage equalizers (4) Power for fans or pumps for moving the cooling media through the cooling system of the converter, whether or not these devices are integrally mounted in the converter (5) Losses in control and signal electronics. 5.3.5.2 Thyristor Losses (1) The forward power loss should be determined by passing direct current through the thyristor and heat sink assembly and measuring the voltage across the assembly. The assembly should consist of the thyristor or thyristors and the associated heat sinks and connections. The magnitude of direct current as defined in 5.2.2 is: P2 A minimum of 10% of the thyristor and heat sink assemblies for each converter should be tested and the average value of power loss used to determine the forward power loss. P2 P (assembly) d - = V . Id The thyristor forward power loss for each sixpulse converter should be calculated. (2) The resistance should be determined using the procedure in ANSI C57.16-1958 (R 1971) [2], 16-91. (3) Harmonic loss should not be assigned to air-core inductors. P10 (4) The power for auxiliary devices, such as fans OT pumps, which are required to operate for the inductor to perform its function, should P6 = P (assembly) . (assembly per converter branch) . 2 (branches in conduction at any given time) The total thyristor forward power loss for the line side and load side converter = Pfc= 2 Ps - 17 ~ ANSI / IEEE Std 995-1987 AC ADJUSTABLE-SPEED DRIVES Fig 8 Converter Direct-Current Circuit culated using the procedure given in this section. The operating parameters are given in 5.2.2 for the specified operating point. Filter losses are identified in two general categories; low frequency P l f and high frequency P h f . Both categories are only slightly affected by load but are significantly affected by voltage, frequency, and gating angle. The total filter loss is the summation of P l f and P h f . It is recognized that filter losses for dual winding systems should be higher than a single winding system that is covered by the equations. These additional filter losses are due to electromagnetic coupling between the two windings on the synchronous machines. For the purpose of this recommended practice the same calculation procedure should be used for single and dual winding systems. P14 The equations presented in the following sections cover ac line filters that are connected in ungrounded wye. When filters are connected in delta, these same equations can be used by transposing the delta component values to wye equivalent values. When the line filters are connected in grounded wye, the filter loss calculations assume that there is no other ground in the system. Calculation of filter losses when neutral currents are present is beyond the scope of this recommended practice. (2) An alternate method to determine the forward power loss should use the published data for the forward voltage drop of the semiconductor device at 125 "C. (3) Thristor reverse power and turn-on/turnoff losses are acknowledged to be small and are not included unless specifically requested. When specified a mutually agreeable test or calculaP12 tion procedure should be established. 5.3.5.3 Power Circuit Conductor Losses. The conduction losses should be calculated from published or measured values for conductor resistance. The dc resistance should be corrected to 90 "C for bare bus and 75 "C for insulated bus or cable. The conduction losses should be based on a dc circuit path from the source ac terminals of the converter to the load ac terminals of the converter. This circuit involves two branches of the line side converter and two branches of the load side converter. The conductor length, fuses, and reactors in this loop should be included in the loss. The circuit is shown in Fig 8. The conduction loss should be 12R where the magnitude of the direct current is given by 5.2.2 P2 NOTE: It is recognized that additional losses should result from harmonic current and skin effects, but these should not be included. P13 (1)AC line-Neutral RC Filter Loss 5.3.5.4 Filter, Snubber, and VoltageEqualizer Losses. These losses should be cal18 ANSI / IEEE Std 995-1987 LOAD COMMUTATED INVERTER Cy = capacitor expressed in farads in one phase of wye Ry = resistor expressed in ohms in one phase of wye ELL= rms line-line voltage at ac terminals of converter a = thyristor gating retard angle C, = capacitor expressed in farads for each thyristor shunt snubber n = number of thyristors in series string R, = resistor expressed in ohms for each thyristor shunt snubber Re = resistor expressed in ohms for each thyristor voltage equalizer cd = capacitor expressed in farads in dc filter R d = resistor expressed in ohms in dc filter p = commutation overlap angle = 0 (for this recommended practice) P3 (2) Thyristor Shunt Snubber Loss P1f = l 2 0 f 2 (CSl2 ELL^ R, n (1 (n) + 0.5 Sin2 a ) (3) Thyristor Voltage Equalizer Loss (4) DC Filter Loss + + f 2 cd2 ELL^ Rd [1 11.5 Sin2 a] 1.5 f Cd ELL^ [Sin2 a Sin2 (a p)] (5) Letter Symbols for Quantities Used for Filter-Loss Calculations Pif = 5.2 Phf = + P l f = low-frequency filter loss Phf = high-frequency filter loss f = frequency Operating Parameters (Section 5.2) Shaft Speed Shaft Torque Synchronous machine 5.3.2 Isolation transformer (b) Open Circuit Core (c) Stray Load (d) Arm 12R (e) Field 12R (0 Exciter (g) Harmonic (h) Auxiliary (a) No Load (b) Fundamental Sine-Wave Volts (E) Fundamental Sine-Wave Ampers ( I a ) Fundamental Phasor Power Factor (F’,,) I 5.3.1 5.3.1 5.3.1 5.3.1 5.3.1.2(2) I 5.3.1.3 5.3.1.4 5.3.2 5.3.2 5.3.2 I ~ R (c) Stray (d) Harmonic (e) Auxiliary 5.3.3 Line reactor 5.3.4 DC link inductor 5.3.5 Power converter 5.3.2.2 5.3.2.3 (a) 12R (b) Stray (c) Harmonic (d) Auxiliary 5.3.3 5.3.3 (a) 12R (b) Core Losses (c) Harmonic (d) Auxiliary (a) Thyristor 03) Poker Circuit Connectors (c) RC Filters and Snubbers (d) Cooling System (e) Control Total Losses 5.3.4 5.3.3.2 5.3.3.3 I 5.3.4(5) 5.3.4(3) 5.3.4(4) 5.3.5.2 5.3.5.3 5.3.5.4 5.3.5.5 5.3.5.6 0 19 +( ) +( ) ANSI / IEEE Std 995-1987 AC ADJUSTABLE-SPEED DRIVES electric power under specified conditions. On larger equipment where the system staging is not readily available and mechanical power cannot be measured accurately, a conventional efficiency is used, based on segregated losses. (2) The conventional efficiency is related to the sum of the segregated losses as follows: 5.3.5.5 Power for Cooling System. The power input to pump or fan motors should be measured directly by conventional wattmeter methods. 5.3.5.6 Control Losses. The power input to the logic and gating circuits should be measured directly by conventional wattmeter methods with the control system fully activated and the gating circuits producing pulses to the thyristors on the line-side and load-side converters. Efficiency (%) = output * 100 output losses + In the above equation, power output and losses are expressed in watts (or kilowatts). When the drive output is expressed in horsepower the conversion to kilowatts is: 5.4 Recording of Losses. The segregated losses that have been determined for each operating point should be tabulated according to the classifications listed in 5.1. Table 2 includes a listing of the segregated losses and the classification of the losses. Kilowatts = horsepower . 0.746 (3) The calculated value for efficiency should be rounded off to two decimal places (hundredths). For example, the efficiency value that is calculated at 93.4524% should be expressed as 93.45%. 5.5 Determination of Efficiency (1)The true efficiency of the drive system is the ratio of output mechanical power to input 20 ANSI / IEEE Std 995-1987 LOAD COMMUTATED INVERTER Appendixes (These Appendixes are not a part of ANSI / IEEE Std 995 1987, IEEE Recommended Practice for Efficiency Determination of Alternating-Current Adjustable-Speed Drives, but are included for information only.) Appendix A Explanation of Practices and Procedures A2. P3-Derivation of a for Line-Side Converter Filter Loss Calculations The practices and procedures that are presented in this recommended practice are based on a goal to determine the losses within 5% of actual on a total drive system basis. This level of accuracy should result in the determination of the drive system efficiency within one percentage point down to 80% efficiency. This is well within the accuracy that can be achieved by measurement of input and output power. The practices and procedures that are identified by a P number on the right-hand side of a column have been selected to eliminate rigorous calculations and procedures when the accuracy of the recommended approaches was deemed to be adequate to meet the accuracy goal. The goal of the accuracy of loss calculation on equipment is f.10% or better. It is expected that the deviations from the exact loss will be both plus and minus, and in most cases will be less than lo%, therefore the 5% accuracy goal on a drive system basis is realistic. The recommended practices and procedures are presented in A1 through A14. Neglecting losses, the power at the synchronous machine must equal the power at the dc link of the load-side converter. - I, F,, E * 8 = Ed - Id IT Id = I, then 3 Ed (load side) = E - I, - F,, - 8 IT and Ed (load side) = E 3Jz Fp, IT If we assume that p = 0 then the dc voltage from the line-side converter becomes Ed (line side) Al. P1 and P2-Conversion Factors for Current = 3Jz E L -cos a IT Ed (line) must be higher than Ed (load) by the IR drops in the loop. Typical values for loop IR drop will range from 0.5% at light load to 3% at rated load. For simplicity a one percent adjustment is recommended. The recommended method for the conversion of dc to rms ac (Pl) and the conversion of fundamental ac to dc (P2) are presented in [A5].4 P1 is covered in [A5], Appendix A-Effective Value of Alternating Current of a Six-pulse Converter. P2 is covered in [A5], Ch 3-Analysis of a Bridge Converter, Eq 39 The conversion errors are less than 5% in the normal operating range for the simplified procedure of setting p = 0. Then Ed ( h e side) = 1.01 Ed (load side) Ed (line side) = 1.01 E 3Jz . Fpp- 1.01 E - l7 EL and The numbers in brackets preceded by A correspond to the references in Appendix A. 21 3 4 ~ IT COS a = 3'8 FppIT ANSI / IEEE Std 995-1987 AC ADJUSTABLE-SPEED DRIVES Ratio of filter loss calculation for p # 0 versus p 1 1 = 0 + cos 6 = cos a 0 (for the case with p = 0) 2 1 I 1 1 I 1 1 1 1 1 1 1 I 1 + 0.2 cos' 2a + 0.2 cos2 2a 1.01 1.01 1.02 1.01 1.01 = - 1.01 1.02 1.02 1.01 1.01 1.02 1.01 related to the phasor power factor Fppof the machine at the specified operating point. As stated in P3 3Jz c o s a + ~ EL 77 1.01 1.02 With commutation overlap ( p # 0) Ed ( h e side) cos a 2 E where * 1, * Fpp 8 = Ed I d From Fig 3 of this recommended practice it is evident that the commutating voltage is not the same magnitude or phase angle as the synchronous machine phase voltage E,. Since it is the commutating voltage and the gating angle of the load-side converter that determine the filter loss, a n expression will be derived to account for the differences in voltage and angle. The envelope of the commutating voltage is greater than the envelope of the fundamental by a function that includes the volt-seconds of the commutation notches. At zero current the two are the same. To avoid the complexity of including commutation voltages and commutation reactances (thus p = 0) and to maintain reasonable accuracy, the following expressions are recommended for the derivation of the gating angle for the load-side converter. 6 = a + p Since a and p are used to determine filter losses only, the above tabulation shows the magnitude of the difference in filter loss calculation for the recommended method with p = 0. The difference between the two cases is not significant for three of the four functions and in all cases becomes small at the greater values of phase retard where the filter losses become significant. The function (1 11.5 sin2a) for the low-frequency dc filt.er loss shows the greatest departure from 1.0 but this is used in only one calculation and normally represents a small part of the total. + Let the commutation voltage loads. A3. P4-Derivation of a for Load-Side Converter Filter Loss Calculations = 1.05 E for all Then E 3 4 - 1.05 E Fpp* 7r The calculation of filter losses on the load-side converter require a value for a and p at each operating point. As in the line side filter loss calculation the accuracy of the results is not significant if p = 0. The gating angle of the load-side converter is COS * 3 3 ll and a = cos-' (0.95 Fpp) and ELLin the filter calculation = E 22 ANSI / IEEE Std 995-1987 LOAD COMMUTATED INVERTER The fixed multiplier kl = 0.3 establishes a reasonable value for the additional losses in the machine with a six-pulse power converter. There is minimal information available on the subject but a 10% to 15% machine derating for operation with a six-pulse static inverter is a reasonable and accepted practice. The 0.3 multiplier on machine SL and 12RS losses represents approximately 15% additional electric losses over the sinusoidal losses at rated power. P15 P h = K1 (sine-wave load losses) A4. P5-Definition of E,t The motor has two three-phase windings phase-shifted by 30". For testing, they are connected in series as indicated in Fig 7 of this recommended practice. For the wye connection Ert = 2 EfmCOS 15" Efm* 0.966 = 2 - where K1 = 0.3 is recommended to determine the machine harmonic losses with a six-pulse converter. NOTE: This assumes that machines with laminated field poles will have amortisseur windings and closed end-ring connection. trt There is a 3.4% difference in voltage and magnetic saturation. The test voltage is cos 15" times actual and the test current is l / c o s 15" times actual. The tested stator 1 2 R and stray load loss is approximately ( l / c o s 15")' . actual. The correction, then, is a (cos 15"12 multiplier. A6. P7-Synchronous Machine Harmonic Loss With reference to P5, the fixed multiplier for harmonic loss is reduced from 0.3 to 0.15. A reduction is necessary to account for the cancellation of rotor harmonic currents by the 30 degree phase displacement in the stator windings of a dual winding machine. The 5thand 7th, 17th and lgth, etc are cancelled by the stator phase displacement and the 6th, 18th,etc harmonics do not appear in the rotor. Thus, the harmonic losses in the rotor, which represented the major part of the harmonic losses in the machine, are significantly reduced. The stator windings are still exposed to the sixpulse current wave forms, but the losses are reduced slightly due to some cancellation of harmonic fluxes. P h = K 2 (sine-wave load losses) P15 A5. P6-Synchronous Machine Harmonic Loss The additional loss due to nonsinusoidal voltage and current is taken as a fixed multiplier of the machine losses due to stator current ( S L 12RS).The harmonic losses in the stator and rotor are a function of the current in the stator winding, not the rotor field winding and the excitation losses. The load commutated inverter is a current source, which means that the harmonic currents are a function of the current applied to the stator winding. The ijth and 7th stator harmonics both produce a 6th harmonic rotor current. The llth and 13th stator harmonics both produce a 12th harmonic rotor current, etc. The harmonic currents in the rotor produce losses in the amortisseur winding and the pole face. Thus, the harmonic currents in the rotor are a direct function of the stator winding harmonic currents and the additional losses due to harmonics should be based on the machine load losses, SL and 12RS. + where Kz = 0.15 is recommended to determine the machine harmonic losses with dual six-pulse converters. NOTE: This assumes that machines with laminated field poles will have amortisseur windings and closed end-ring connection. 23 ANSI / IEEE Std 995-1987 AC ADJUSTABLE-SPEED DRIVES A7. P8-Brushless Exciter Harmonic Loss square of the load current and the square of frequency. The other stray losses (POSL) will also increase as a result of nonsinusoidal load current and are generally considered to be proportional to the square of the load current and to frequency to the first power. To accurately determine the harmonic losses the subdivision of the stray losses into PEC and POSL must be known. This subdivision of stray loss is not part of the transformer test procedure and can only be determined from the design data (if available). Therefore, it is recommended that the harmonic loss be taken as a fixed multiplier to the measured stray load loss. The additional losses due to nonsinusoidal voltage and current is taken as fixed multiplier of the exciter electrical sine-wave loss. The voltage applied to the exciter stator is considered to be sinusoidal. The brushless exciter rotor is connected to a static converter, which is normally a three-phase, six-pulse rectifier. The exciter rotor current contains harmonics of the order 6 n '. 1 where n is any integer of the rotor frequency. The rotor fundamental frequency is a function of the exciter slip and may become quite high for contra-rotation exciters. The rotor winding harmonic currents are coupled into the stator winding at frequencies that are also a function of rotor slip, therefore are not a constant harmonic order on the supply frequency. The fixed multiplier k 3 = 0.2 establishes a reasonable level for the additional losses due to the high frequencies and beat frequencies, which might be present at various operating conditions. P h = k 3 . (exciter electrical sine-wave loss) P h = K4 P15 where k4 = 3 The accuracy of this recommendation is discussed below. A8.1 Alternate 1 For the worst-case harmonic current distribution P15 where k3 = . (stray load loss) 0.2 Ih = is recommended to determine the exciter harmonic loss. 1 For this case the winding eddy-current losses due to harmonic currents are A8. P9-Transformer Harmonic Loss (See ANSIIIEEE C57.110-1987[All The nonwinding stray losses due to harmonic currents are 25 The transformer load losses are divided into 12RS loss and stray loss. Stray loss can be defined as those losses due to stray electromagnetic flux in the windings, core, core clamps, magnetic shields, enclosure or tank walls, etc. Thus the stray losses are subdivided into the winding stray losses and stray losses in components other than windings. The winding stray load loss includes winding conductor strand eddy-current losses and losses due to circulating currents between strands or parallel winding circuits. All of this loss may be considered to be winding eddy-current (PEC) losses. Winding eddy-current losses in the power frequency spectrum are proportional to the Ph = POSL & (A)h =5 2 h = 0.7 POSL It is reasonable to assume that the winding eddy-current losses PEC are not more than half of the total stray load loss. In the maximum case the total harmonic loss is Ph = 0.5 * Ph = 4.35 8 * PEC 4- 0.5 - 0.7 POSL . (stray load loss) This represents a worst-case example and the actual harmonic loss is less than this value. Therefore, the recommended procedure, which uses the fixed multiplier of k4 = 3, should provide reasonably accurate results. 24 ANSI / IEEE Std 995-1987 LOAD COMMUTATED INVERTER that the ac currents are rectangular in shape; therefore, the current in the dc link inductor is purely dc with no harmonic content and the eddy current loss, circulating current loss and stray loss will be zero. A8.2 Alternate 2 (1) The transformer stray losses are assumed to be winding eddy-current losses PEC. (2) The winding eddy-current losses due to any defined nonsinusoidal load current can be expressed as h = A10. P11-Core Losses in Iron-Core DC Link Inductors 25 The additional losses in the dc link inductor due to a n iron core are taken as a constant multiplier on the 12Rloss. The multiplier k6 = 0.05 is based on limited test data but does recognize the additional core loss as compared to air-core inductors. P15 where PEC = fundamental eddy-current loss (3) A reasonable harmonic distribution for the nonsinusoidal load current in pu of the fundamental is h Ih Ih2 h2 5 7 11 13 17 19 23 25 0.19 0.13 0.07 0.90 0.83 0.59 0.42 0.26 0.14 0.05 0.03 0.02 0.01 0.005 A l l . P12-Thyristor Reverse Power and Turn-ON / Turn-OFF Losses These losses are a small part of the total converter loss and are difficult to determine accurately. The thyristor reverse power loss is heavily dependent on device operating temperature and applied voltage. The turn-off loss is dependent on circuit d i l d t and snubber design. The turnon loss can be determined from device test data (if supplied) but is heavily dependent on snubber design and commutation overlap angle p, which has been set to zero for this recommended practice. The losses covered by this recommendation should be less than 5% of the thyristor forward power loss in a power converter designed for large ac motor drives. The recommendation to not include these losses is supported by the recommended practice documents listed below. (1) ANSI/IEEE Std 444-1973 [A2], 6.3.4. When the total reverse current loss in the semiconductors, voltage divider resistors, and surge suppressor circuits is reasonably estimated to be less than 5% of the converter forward power loss, these losses need not be measured and may be disregarded in determination of efficiency. (2) IEC Publication 146-1973 [A3], Semiconductor Converters Section 472.1, Power loss determination for diode assemblies and rectifier equipment. (a) The losses in the cells in service, due to reverse current and voltage, are normally negligible. 0.05 0.02 3.21 Therefore, the fixed multiplier of k4 = 3 for harmonic losses represents a reasonable accuracy for the recommended procedure. For the case of line reactors the harmonic losses should be similar to those of a transformer. Therefore, the fixed multiplier k5 = 3 is recommended for reasonable accuracy. P15 A9. P10-Harmonic Losses in Air-Core DC Link Inductors The IEC Publication 146-1973 [A31 has established the precedent for this recommendation for the determination of harmonic losses in a series-smoothing reactor-by stating (1) Iron losses are, by convention, to be ignored (2) The losses in the winding are calculated as the product of the dc resistance and the square of the direct current in the winding. This is consistent with other recommendations presented in Appendix A which assume 25 ANSI / IEEE Std 995-1987 AC ADJUSTABLE-SPEED DRIVES A12. P13-Power Circuit Conduction Harmonic Losses chines due to the electromagnetic coupling between the two windings. The line-line commutating voltage waveforms are shown below for single- and dual-winding machines with a 30 degree electrical phase displacement between windings. The waveforms show the commutation notches from the A-B winding being coupled into the A'-B' voltage and vice-versa. The magnitude of the coupling is dependent on the self and mutual leakage inductance of the two windings. Mutual coupling of 50% is reasonable and this results in the coupled voltage notch being 50% of the depth of the notch in the commutating winding. The increased filter loss occurs mainly in the high-frequency loss component of the ac lineneutral filters and the thyristor shunt snubbers. The high-frequency loss is a function of the voltage step squared, that is, The Wave Shape Working Group of the IEEE Power Systems Protection Committee recognized the additional losses in current carrying conductors due to skin effects at higher frequencies. The ac to dc resistance ratio for copper bus is presented in [A4], Table IV. Table IV ac to dc Resistance Ratio for 0.25 x 4 in Cu Bus f Rac / Rdc 1 60 1.158 5 300 1.64 7 420 1.79 11 660 2.05 13 780 2.15 H [sin2 a ELL' The 50% coupling will increase the high-frequency losses of the ac line-neutral and shunt snubber loss by approximately 25%, but this will generally not result in a total increase in filter loss (line and load side) by more than 5%. Using the resistance data presented in Table IV (Taken from Reference [A411 for harmonics to the thirteenth and assuming the harmonic current magnitude of 1 / H, the conduction losses calculate to be 1.037 times the method recommended in this recommended practice. This difference represents a very minimal effect on the total power converter equipment losses and therefore the harmonic losses are not included. A13. P14-Filter + sin2 (a + p)] A14. P15-Constant Multiplier for Harmonic Losses The application of a constant multiplier to determine harmonic losses is a n estimate that is based on engineering judgment of the information available to date. When more exact data becomes available from test data or published papers, or both, the recommendations herein should be changed to include more accurate methods. Prior to any improved method the recommended constant multipliers do provide a n Losses for Dual- Winding Machines The filter losses on the load-side converters of systems with dual winding machines will be slightly higher than those for single-winding ma- I A-B A-B B' SINGLE WINDING MACHINE VOLTAGE D U A L WINDING MACHINE VOLTAGE 26 ANSI / IEEE Std 995-1987 LOAD COMMUTATED INVERTER [A31 IEC Publication 146-1973, Semiconductors ~onverters.~ acceptable means to account for harmonic losses within the accuracy goals for this recommended practice. [A41 IEEE Conference Record. So You Don’t Think You Have a Harmonic Problem. Industry Applications Society, Annual Meeting, 1979. IAS79: 41D. A15. References [A51 KIMBARK, EDWARD WILSON. Direct Current Transmission vol I. New York: WileyInterscience, 1971. [All ANSI / IEEE C57.110-1987, IEEE Recommended Practice for Establishing Transformer Capability when Supplying Nonsinusoidal Load Currents. IEC publications are available in the United States from the Sales Department, American National Standards Institute, 1430 Broadway, New York, NY 10018, USA, and also from International Electrotechnical Commission, 3, rue de Varembe, Case postale 131,1211-Geneve 20, Switzerland / Suisse. [A21 ANSI/ IEEE Std 444-1973, IEEE Standard Practices and Requirements for Thyristor Converters for Motor Drives, Part I-Converters for DC Motor Armature Supplies. 27 ANSI / IEEE Std 995-1987 LOAD COMMUTATED INVERTER Appendix B Example Efficiency Determination An example is presented to illustrate the recommended practice for the efficiency determination of a ac adjustable speed drive. The drive system is a dual channel parallel system (see Fig 16) rated to produce 4200 hp a t 720 r l m i n . The system efficiency was determined for two specified operating points. Point Shaft Speed Shaft Torque Shaft Horsepower 1 2 720 r / m i n 562 r / m i n 30 637 lbf . ft 18 625 lbf ft 4200 1933 . eters a t these operating points were specified by the system supplier. Point E (Volt) I, (Ampere) 1 2 1885/1885 2000/ 2000 516/516 233 / 233 Fpp(%I 95/ 95 95/ 95 The system equipment operating parameters were determined using the procedures of 5.2.2 and the equipment losses were then determined by the recommended procedures. The losses are tabulated in Tables B1 and B2. The synchronous machine operating param- Table B1 Tabulation of Losses Operating parameters (Section 5.2) Shaft Speed 720 r / m i n Shaft Torque 30 637 lbf. ft 5.3.2 Isolation transformer 5.3.3 Line reactor 5.3.4 Direct-Current link inductor 5.3.5 Power converter Loss Determination Class (Section Reference) Fundamental Losses by Sine-Wave Losses Losses by Input Power by Test Calculation Measurement Segregated Loss Component Equipment 5.3.1 Synchronous machine Fundamental Sine-Wave Volts ( E ) 1885/ 1885 Fundamental Sine-Wave Amperes (I, 5161516 Fundamental Phasor-Power Factor (FDp) 0.95/ 0.95 (a) Windage and friction Open-circuit core (c) Stray Load (d) Arm 12R (e) Field 12R (f) Exciter (g) Harmonic (h) Auxiliary (a) No Load 15.0 11.7 6.6 23.5 9.8 3.6 (b) 4.5 I ~ R (c) Stray (d) Harmonic (e) Auxiliary (a) I ~ R (b) Stray (c) Harmonic (d) Auxiliary (a) PR (b) Core Losses (c) Harmonic (d) Auxiliary (a) Thyristor (b) Power-Circuit connectors (c) RC filters and snubbers (d) Cooling system (e) Signal electric (b) Total Losses 4.4 28.2 3.2 9.6 20.0 22.2 1.1 9.2 5.0 5.0 126.0 NOTE: All losses, kW 29 +46.6 + 10.0 ANSI / IEEE Std 995-1987 Table B2 Tabulation of Losses Operating Parameters (Section 5.2) Shaft Speed 562 r / m i n Shaft Torque 18625 lbf ft Fundamental Sine-Wave Volts ( E ) 2000/2000 Fundamental SineWave Ampers (I,) 233 /233 Fundamental Phasor Power Factor ( F A0.95/ 0.95 Loss Determination Class (Section Reference) Fundamental Losses by Sine Wave Losses Losses by Input Power by Test Calculation Measurement 8.7 19.1 1.3 4.8 10.1 3.6 0.9 Segregated Loss Component (a) Windage and friction (b) Open-circuit core (c) Stray Load (d) Arm Z2R (e) Field 12R (f) Exciter (g) Harmonic (h) Auxiliary (a) No Load (b) I ~ R (c) Stray (d) Harmonic (e) Auxiliary (a) I'R (b) Stray (c) Harmonic (d) Auxiliary (a) Z2R (b) Core Losses (c) Harmonic (d) Auxiliary (a) Thyristor (b) Power-circuit connectors (c) RC filters and snubbers (d) Cooling system (e) Signal electric Total Losses Equipment 5.3.1 Synchronous machine 5.3.2 Isolation transformer 5.3.3 Line reactor 5.3.4 DC link inductor 5.3.5 Power converter 4.4 5.7 0.6 1.8 4.1 8.4 0.2 7.1 5.0 5.0 + 18.4 62.4 + 10.0 NOTE: All losses, kW The drive system efficiency at the specified operating points is then calculated. Point 1 Output kW Point 2 Output kW = 1993 * 0.746 = 1486.8 1486.8 Efficiency (%) = 100 1486.8(62.4 18.4 10) + - 4200 0.746 = 3133.2 3133.2 Efficiency (%) = 100 3133.2 (126 46.6 10) -~ - 3133-2 100 = 94.493 3315.8 = 94.49% = + + + + --.1486*8 100 = 94.244 - 1577.6 = 94.24% 30