Tomco2 Fire Systems 8/16/10 Rev. 0 High Pressure CO2 Engineering, Installation and Operation Manual 7619 Hamilton Avenue Cincinnati, OH 45231 USA (513) 729-3473 phone (513) 729-3444 fax Tomco2 Fire Systems 8/16/10 Rev. 0 TABLE OF CONTENTS SECTION 1 2 3 4 5 DESCRIPTION INTRODUCTION SYSTEM COMPONENTS SYSTEM DESIGN INSTALLATION OPERATION AND SERVICE Tomco2 Fire Systems Introduction 8/16/10 Rev. 0 SECTION 1 INTRODUCTION Table of Contents Paragraph 1-1 1-2 1-3 1-4 1-5 Subject Purpose Description Properties of Carbon Dioxide Quality of Carbon Dioxide Safety Tomco2 Fire Systems Introduction 8/16/10 Rev. 0 SECTION 1 INTRODUCTION 1-1 PURPOSE The intent of this manual is to provide the user with the information necessary to adequately select, operate and maintain our high pressure CO2 fire suppression equipment required to protect a specific hazard. 1-2 DESCRIPTION A. A high pressure CO2 system is a specialized fire suppression system designed to maintain the carbon dioxide supply at 70º F and 850 psig in strength alloy steel cylinders. The cylinders contain the CO2 required to protect the largest single hazard and any number of back-up discharges required by the authority having jurisdiction. B. On large hazards where several cylinders are required, a manifold is used to connect each cylinder by means of flexible hoses and check valves. C. Cylinder valves control the CO2 flow to the hazard through properly sized pipe, terminating in nozzles that apply the CO2. Flow rate is controlled by nozzle orifices as well as pipe sizes. The cylinder master valves are electronically operated and the slave valves are back pressure actuated. The master valves can be automatically and/or manually operated. D. Lock-Out Valves A lock out shall be installed on all systems where carbon dioxide could migrate, creating a hazard to personnel. The valves shall be supervised for both automatic and manual systems unless specifically waived by the authority having jurisdiction. Systems shall be locked out when persons not familiar with the systems and their operation or when persons are present in locations where discharge of the system will endanger them before they can proceed to a safe location within the time delay period. E. The equipment is UL listed for an ambient temperature range of 0°F to 130°F (-18°C to 54°C) of the protected area. Any approved releasing control panel can provide automatic actuation. Electric release stations provide manual release. The control panel operates the alarm devices, provides shut-down of auxiliary equipment, and supervises all circuits. The control panel also provides delays so alarms (audible and visual) in the protected area can evacuate personnel before the CO2 discharges. F. Pneumatic Time Delays A pneumatic pre-discharge alarm and pneumatic time delay shall be provided for all total flooding systems protecting normally occupied and occupiable enclosures where the discharge will expose personnel to hazardous concentrations of carbon dioxide. (NFPA 12, Paragraph 4.5.6, 2005 Edition) The pneumatic pre-discharge alarms and pneumatic time delays are required on all new installations and it is mandated that all existing systems be upgraded no later than December 31, 2008. 1-1 Tomco2 Fire Systems 1-3 Introduction 8/16/10 Rev. 0 PROPERTIES OF CARBON DIOXIDE A. Under normal atmospheric temperature and pressures, carbon dioxide exists as a colorless, odorless gas which is about 1.5 times heavier than air. Carbon dioxide will not burn or support combustion and will not sustain life. B. When confined within a suitable pressure vessel and depending on temperature and pressure conditions, carbon dioxide can exist in any of three stages of matter; solid, liquid and gas. The point at which all three states may exist is -69.9º F and 60.4 psig. This is called the triple point. At temperatures and pressures lower than -69.9º F and 60.4 psig, carbon dioxide may be either a solid or gas, again depending on conditions. Solid carbon dioxide (dry ice) at a temperature of -119.4º F and atmospheric pressure, sublimes (transforms directly from a solid to a gas without the formation of liquid). C. The critical point of carbon dioxide is 87.8º F and 1057.4 psig. At temperatures and pressures greater than 87.8º F and 1057.4 psig, carbon dioxide liquid cannot exist. D. At temperatures and pressures above -69.9º F and 60.4 psig, and below 87.8º F and 1057.4 psig, carbon dioxide liquid with overlying vapor may exist in equilibrium within a closed vessel. Within this range, there is a definite relationship between temperature, pressure and density. E. The term “high pressure” is used to describe storage of carbon dioxide at ambient temperature which is usually 850 psig @ 70° F. 1-2 Tomco2 Fire Systems Introduction 8/16/10 Rev. 0 F. 2000 CRITICAL TEMPERATURE 1000 900 800 700 600 500 LIQUID REGION ABSOLUTE PRESSURE LBS./SQ. IN. 400 300 200 SOLID REGION VAPOR 100 90 80 70 TRIPLE POINT 60 50 40 30 20 ATMOSPHERIC PRESSURE 10 -120 -100 -80 -60 -40 -20 0 20 40 60 80 100 TEMPERATURE DEG F For SI Units: 1 psi = 0.0689 bars: ºC = 5/9(ºF -32). Figure 1-1 Variation of Pressure of Carbon Dioxide with Change in Temperature (Constant Volume). Below the critical temperature (87.8º F) (31º C), carbon dioxide in a closed container is part liquid and part gas. Above the critical temperature it is entirely gas. Figure 1-1 Vapor Pressure Curve 1-3 120 140 Tomco2 Fire Systems 1-4 Introduction 8/16/10 Rev. 0 QUALITY OF CARBON DIOXIDE Carbon dioxide used for initial supply and replenishment shall be of good commercial grade, free of water and other contaminants that might cause container corrosion or interfere with free discharge through nozzle orifices. Carbon dioxide obtained by converting dry ice to liquid will not be satisfactory unless it is properly processed to remove excess water and oil. The vapor phase shall be not less than 99.5 percent carbon dioxide with no detectable off-taste or odor. The water content of the liquid phase shall be not more than 0.01% by weight (-30º F [-34º C] dew point). Oil content shall be not more than 10 PPM by weight. Caution: Carbon Dioxide should not be used to protect the following hazards: 1. Chemical compounds such as gunpowder or cellulose nitrate which supply their own oxygen. 2. Reactive materials such as sodium, potassium, magnesium, titanium, zirconium, uranium and plutonium. 3. Metal hydrides. 4. Chemicals capable of undergoing auto thermal decomposition (hydrazine and certain organic peroxides). 1-5 SAFETY A. Pressure Hazard - The storage cylinders covered in this manual may contain pressures over 850 psig (59 bar/5,861 kPa). Sudden release of this pressure may cause personal injury by issuing cold gas or liquid, or by expelling parts during servicing. Do not attempt any repairs on these cylinders until all pressure is released and the contents have been allowed to vaporize to ensure no pressure buildup can occur. B. Extreme Cold - Cover Eyes and Exposed Skin - Accidental contact of the skin or eyes with carbon dioxide may cause a freezing injury similar to frostbite. Protect your eyes and cover your skin when handling the tank or transferring liquid, or in any instance where the possibility of contact with liquid, cold pipes and cold gas may exist. Safety goggles or a face shield should be worn when withdrawing liquid or gas. Long-sleeved clothing and gloves that can be easily removed are recommended for skin protection. C. Keep Equipment Well Ventilated - Although carbon dioxide is non-toxic and nonflammable, it can cause asphyxiation in a confined area without adequate ventilation. An atmosphere of carbon dioxide does not contain enough oxygen for breathing and will cause dizziness, unconsciousness, or even death. Carbon dioxide cannot be detected by the human senses and will be inhaled normally as if it was air. Ensure there is adequate ventilation where carbon dioxide is used and store tanks in a well ventilated area. D. Install Relief Valves in Liquid Lines - When installing piping make certain a suitable safety relief valve is installed in each section of piping between valves. Trapped liquefied gas will expand as it warms and may burst hoses or piping causing property damage or injury. 1-4 Tomco2 Fire Systems Operation And Service 8/16/10 Rev. 0 SECTION 2 SYSTEM COMPONENTS Table of Contents Paragraph 2-1 2-2 2-3 2-4 2-5 2-6 2-7 2-8 2-9 2-10 2-11 2-12 2-13 2-14 2-15 Subject Cylinder Assemblies Discharge Bends and Adapters Cylinder Brackets Check Valves Bleeder Valves Discharge Nozzles Manual Actuator Electric Actuation Discharge Pressure Switch Pressure Release Trip Header Safety Pressure Operated Siren Cylinder Assemblies Lock-Out Valves Pneumatic Time Delay Tomco2 Fire Systems System Components 8/16/10 Rev. 0 SECTION 2 SYSTEM COMPONENTS 2-1 CYLINDER ASSEMBLIES A basic cylinder assembly consists of a pressure vessel, a valve and siphon tube assembly, and a charge of carbon dioxide. A variety of cylinder sizes are available. They are all designed to hold pressurized carbon dioxide in liquid form at atmospheric temperatures, corresponding to a normal pressure of 850 psi at 70°F (58.6 bar at 21°C). All cylinders are seamless. They are manufactured and tested in accordance with the requirements of Department of Transportation and/or Transport Canada, Specification 3AA-1800 or higher. Larger cylinders having capacities of 35, 50, 75 and 100 pounds (15.9, 22.7, 34 and 45 kg) are made of steel. Small cylinders, used for special applications, have capacities of 10 and 15 pounds (4.5 and 6.8 kg) and may be made of aluminum or steel, depending on availability. Except for special temperature conditions, all cylinders are filled to their specified weight with liquid carbon dioxide. Cylinders are not partially filled. The pressure inside the cylinder will vary as the temperature changes. In general, the ambient storage temperature for standard cylinders used in local application systems should be between 32°F and 120°F (0°C and 49°C). For standard cylinders used in total flooding systems, the ambient storage temperature should be between 0°F and 130°F (18°C and 54°C). Two cylinder valves are available: the SW-50M (master) and the SW-50S (slave). Both are manufactured of brass with an optional nickel plated finish. The valves are of the force differential type using a piston seal. The pressure above the piston is maintained at cylinder pressure, but the area at the top of the piston is greater than the seal area. This results in a higher force above the piston, which acts to keep the valve closed. To open the valve, the pressure above the piston is vented and cylinder pressure raises the piston to open the valve. A transport plug is attached to the valve by a chain attached to the discharge port when the cylinder is disconnected from the discharge piping. A pressure safety disc, incorporated into the cylinder valve, is designed to release pressure should the cylinder be subjected to exceptionally high temperatures or other abnormal conditions. The disc rupture point is in the range of 2,600 to 3,000 psi (182.7 to 206.8 bar). The safety disc nut is of a type that will relieve pressure without cylinder recoil. The SW-50M master valve can be operated manually, by pressure actuator, with a solenoid valve kit, or by direct back pressure from the discharge manifold. The SW-50S slave valve can b operated only by direct back pressure from the discharge manifold. Single cylinder systems simply require a single SW-50M with a manual actuator and/or a solenoid valve. This is generally referred to as a master cylinder. For systems with two cylinders interconnected, only one master valve is required. The other cylinder is operated by a SW-50S slave valve. For systems with three or more cylinders interconnected, two cylinders must act as masters and have solenoid and/or manual actuators arranged for simultaneous operation. A rigid siphon tube is used in all cylinders to ensure liquid discharge. All cylinders must therefore be installed in a normal upright position. 2-1 Tomco2 Fire Systems 2-2 System Components 8/16/10 Rev. 0 DISCHARGE BENDS AND ADAPTERS A discharge bend is used to connect the cylinder valve outlet to the system manifold and discharge piping. This flexible hose allows for the temporary misalignment of the cylinders on installation, and for ease of cylinder removal for maintenance. The cylinder end of the hose has a swivel connection for ease of installation. A discharge bend with a built-in check valve must be used when cylinders are manifolded together. The check valve is locked onto the hose assembly and must not separated from it. If a cylinder assembly is disconnected from the discharge bend, and if the system operates while the cylinder is disconnected, the check valve will ensure that an appreciable quantity of carbon dioxide will not discharge from the disconnected discharge bend. Flexible discharge bend adapter combinations are available for single cylinder systems where a check valve is not required. When the discharge adapter is used without the flexible bend, a union connection must be installed close to the cylinder for ease of installation and maintenance. It is important that neither the discharge bends nor the discharge adapter be mounted onto the cylinder valve during transportation and storage. The transit plug must remain in place on cylinder valve until the cylinder is installed and secure in its brackets. 2-3 CYLINDER BRACKETS The cylinder can be arranged to be bracketed to a wall or to be free standing when no wall is available. Straps for single cylinder wall mounting installations are available from Tomco Fire Systems. Brackets for multiple wall mounted installations and frames for multiple cylinder free standing installations are normally supplied by the installer, and assembled on site to suit space available. For installation of three or more cylinders, a variety of arrangements can be fabricated by installer. The single row, wall mounting arrangement is recommended for installations of up to five cylinders. Double row, free standing arrangements have the advantage (particularly for systems using main and reserve cylinders, and for joint systems), that any cylinder can be removed for recharging without disturbing the others. However, this arrangement requires two aisles and considerably more space. The double row, wall mounting arrangement is generally used when sufficient space is not available for free standing arrangement or for single row wall mounting arrangement. For marine applications, additional cylinder supports are required. Two straps or sets of retainers must be used. 2-4 CHECK VALVES A range of check valves are available. These are used to isolate the main cylinder manifold from the interconnected reserve cylinder manifold. In the manifolds of joint systems they are also used to prevent the discharge from activated cylinders causing activation of the other cylinders in the bank. 2-5 BLEEDER VALVES Bleeder valves are used in the manifolds of main and reserve banks of cylinders, as well as in the manifolds of systems that have selector valves (joint systems). The bleeder valve 2-2 Tomco2 Fire Systems System Components 8/16/10 Rev. 0 vents accidental check valve leakage (that could discharge the other bank or banks of cylinders) from one bank to the other. The valve is normally open and closes when manifold pressure reaches approximately 20 psi (1.4 bar) to prevent loss of CO2 under normal discharge conditions. The pipe connection is 1/2" NPT. 2-6 DISCHARE NOZZLES Two types of discharge nozzle are available: total flooding type and local application type. Total flooding nozzles are used where an even distribution of gas is required throughout and enclosure. Local application or directional nozzles are used where a concentration of carbon dioxide is required on a particular surface or piece of equipment. Nozzles are designed to discharge large volumes of carbon dioxide without freezing. For local application use (when installed in accordance with their approvals), the velocity of discharge from the nozzle is reduced to prevent agitation and splattering of hazardous material which could spread the fire. All nozzles have a drilled orifice. The nozzle orifice size will vary depending on the flow and the location of the nozzle in the system. It is important that nozzles are installed exactly as specified on the project drawings, otherwise system performance will be jeopardized. The wall type and vent type nozzles are used exclusively for total flooding installations. The S-Type nozzle may also be used for total flooding installations, however, its cost normally restricts its use to local application installations. The S-Type nozzle may be fitted to flanges to enable it to be mounted onto sheet metal equipment closures and ductwork. It may also be supplied with a frangible disc to prevent clogging of the orifice. Special finishes for nozzles are available and can be provided by special order to suit project requirements. 2-7 MANUAL ACTUATOR A manual actuator is used to operate the carbon dioxide system manually and locally at the cylinders. The actuator is screwed into a port on the top of the SW-50M cylinders valve. When two master cylinders are required, the levers of the two actuators are joined together with a connecting link for simultaneous operation. The actuator has a hole in the side of the main body fitted with a blank plug. The hole allows to actuator to be operated from an external pressure source. It is also used to connect to the discharge from the solenoid valve (when used). The blank plug is removed from the actuator only for these two purposes. Otherwise the plug must remain tightly connected at all times. The hand lever on the manual actuator can be operated from a remote location. This is achieved be connecting 1/16” diameter stainless steel cable to the end of the lever, and running the cable through 1/2" conduit or 3/8” pipe to a pull box using corner pulleys at each change in cable direction. Using a mechanical dual junction box, two remote pull boxes can be joined to operate one master cylinder arrangement. Or, one remote pull box can be used to operate two separate manual actuators. 2-8 ELECTRIC ACTUATOR Electric actuation is achieved by using a solenoid valve kit. The solenoid valve is normally closed device, closed when de-energized and open when energized. The standard solenoid voltage is 24 VDC, but other voltages and special enclosures (including explosion-proof) are available by special order. The standard electric connection is by a DIN connector, and a cable assembly is available for ease of connection to field wiring. 2-3 Tomco2 Fire Systems System Components 8/16/10 Rev. 0 The solenoid coil is designed and rated for continuous duty service. However, it is recommended that the actuating circuit incorporate a shut-down device (e.g. a pressure switch or time delay relay) to open the circuit when the cylinder is empty. When the coil is energized for a long period of time, the solenoid enclosure becomes hot. This is a safe operating temperature and will not damage the solenoid. Any excessive heating will be indicated by smoke of burning coil insulation. The solenoid valve connects directly to a special adapter on the SW-50M cylinder valve. The discharge side of the solenoid valve is connected to the pressure port on the manual actuator with supplied 3/16” braided hose. When de-energized, the solenoid valve opens allowing pressure from above the main piston of the cylinder valve to operate the actuator and open the valve. The solenoid should be connected to a Listed control panel that is powered through a separately fused circuit, and that also incorporates battery backup power. 2-9 DISCHARGE PRESSURE SWITCH The pressure switch connects to the carbon dioxide discharge piping and operates when the system discharges. The switch may be wired with contacts in the open or closed position. Operation causes the electrical switch contacts to reverse position. Switches can be used to confirm system discharge, to operate alarms, to shutdown motors, pumps, fans and conveyors, to release magnetic door holders, etc., automatically when the system discharges. The switch may be mounted in any position, but preferred installation in with the pressure connection (CO2 supply line) entering from the bottom. The switch enclosure is rated for standard and weatherproof conditions. When the line load of the equipment to be operated is greater than the switch rating, the switch should be used to break a relay holding-coil circuit. 2-10 PRESSURE RELEASE TRIP The pressure release trip can be used to release dampers, close fire doors, windows, louvers, fuel supply valves, to open dump valves, etc., automatically when the system discharges. The equipment to be operated must be weight or spring loaded, or be pivoted off centre. The release trip is connected to a carbon dioxide discharge piping for operation when the system discharges. Cable from the equipment to be controlled is looped over the pressure release operating stem. When the trip is operated, the stem retracts and the cable is released. 2-11 HEADER SAFTEY This pressure relief device is installed in sections of closed piping such as between selector valves and the cylinder manifold. It is a frangible disc assembly designed to rupture if trapped CO2 expands and the line pressure exceeds 2,650 to 3,000 psi (182.7 to 206.8 bar). The body is made of brass and the pipe connection is 1/2" NPT. 2-12 PRESSURE OPERATED SIREN This unit sounds an alarm by means of carbon dioxide pressure. It is connected t the discharge piping of the system, or to a spate independent carbon dioxide cylinder. Sirens should be located throughout the hazard area in order to ensure an audible alarm will be heard on the activation and discharge of the carbon dioxide system. Due consideration should be given to the normal background noise in the area. 2-4 Tomco2 Fire Systems System Components 8/16/10 Rev. 0 The carbon dioxide system incorporates a delayed action device, the siren must be arranged to operate at the same time that the delayed action device is initiated. When connected to the carbon dioxide system piping, the alarm will cease when the gas discharge had been completed. If it is desirable or necessary for the sirens to operate for a longer period of time than will be allowed by the system discharge time, a separate independent carbon dioxide cylinder must be used. 2-13 CYLINDER ASSEMBLIES Carbon dioxide cylinders may be located inside or outside the protected space, although it is preferable to locate them outside the space. When they are installed within the space they protect, a remote manual control should be installed to ensure the system can be actuated from a safe location outside the fire area. The cylinders should be located to provide convenient access so that they can be readily inspected and easily removed after use for recharging. They should not be installed where that will be exposed to the weather elements or the direct rays of the sun. Cylinders should not be installed where they will be subjected to temperatures of less than 0°F (18°C) or higher than 130°F (54°C), unless otherwise specified. If cylinders are located in hazardous (explosion-proof) area, the cylinder solenoid should be approved for such use, and the installation of all materials needs to be done in an approved manner. Cylinders should be installed in the normal upright position. All cylinders are provided with a siphon tube. . 2-14 LOCK-OUT VALVE ASSEMBLY A lock-out valve should be provided with all systems where CO2 could migrate creating a hazard to personnel. The valve should be located in the discharge piping between the nozzles and supply in the fire suppression system. The valve is used to prevent accidental or deliberate discharge when persons not familiar with the system are present in the protected space. The valve shall be maintained in the open position. Closing this valve takes the system out of service. The valve position should be continuously monitored at the control panel and is equipped with a pad-locking device to lock the valve in the open or closed position. Manually operated valves in the 1/2", 3/4", 1”, 1 1/4", 1 1/2" and 2” sizes are the full port ball valve type. Each valve is equipped with a pad locking type handle and supervisory switch is normally maintained in the fully open position. 2-15 PNUEMATIC TIME DELAY A pneumatic time delay shall be provided for all total flooding systems protecting normally occupied and occupiable enclosures and local application systems where the CO2 discharge will expose personnel to hazardous concentrations. The pneumatic time delay delays the discharge of CO2 for predetermined amount of time. This extra time allows additional time for ventilation and equipment shutdown. The time delay is installed between the master CO2 cylinders and the discharge nozzles. The time delay has inlet port and outlet port, both with a 3/4" NPT connection. The actual time delay period is per-set at the factory. Tomco Fire Systems offers both 30 and 60 second time delays. The time delay will operate at temperatures from 0 to 130°F. Note: Delay times will vary slightly with the ambient temperature. The time delay is equipped with manual override lever. This lever allows the time delay to be bypassed and allows the CO2 to discharge immediately. 2-5 High Pressure CO2 Fire Protection SW-50 Cylinder Valve 2 in (50 mm) 96060233 SW-50M Master Valve, Brass 96060286 SW-50M Master Valve, Nickel Plated 96060232 SW-50S Slave Valve, Brass 96060285 SW-50S Slave Valve, Nickel Plated Top View Solenoid Actuator Protection Cap Manual Actuator Port Slave Piston Cavity Main Valve Cavity Vent Discharge Port Vent 5 in (127 mm) Remove safety plugs from valve only after securing cylinder in cylinder bracket. Safety Relief Side View 1inch NPT Thread 1inch NPT Thread SW-50M Master Valve Minimum Burst Pressure 6,000 PSI (414 Bar) Safety Relief Operating Pressure 2,650 to 3,000 PSI (182 to 207 Bar) Equivalent Length 5 feet (1.5 m) of ½" Schedule 40 Black Pipe Dimensions 5" (127 mm) high x 2" (50 mm) wide Operating Temperature 0° F to 130° F (-18° C to 54° C) Weight 3.5 lb. (1.6 kg) 7619 Hamilton Ave, Cincinnati, Oh 45231 Page 1 of 1 SW-50S Slave Valve Telephone +1 513 729-2473 Fax +1 513 729-3444 Website tomcofiresystems.com 51-0141-0997 Two Cylinder Installation H 2/3 H 1/4 H Marine Installation 7619 Hamilton Ave, Cincinnati, Oh 45231 Industrial Installation Mounting bolts must be anchored into solid structural members. Bolts must not be anchored into plaster or other facing materials. Only the strap is supplied by inControl Systems. All other components and mounting hardware is to be supplied by the installer to suit site conditions. Cylinder straps are intended to support floor mounted cylinders against a solid wall. Cylinder Mounting Strap High Pressure CO2 Fire Protection 3/4 H Telephone +1 513 729-2473 6.73 7.00 (38 lb) 9.06 (50 lb) 9.25 (75 lb) 10.50 (100 lb) 96040332 96040146 96040147 96040309 96040148 Fax +1 513 729-3444 Cylinder dia. Part number 36" clear space in front of cylinders for maintenance 10.05 10.33 12.33 12.57 13.83 A D C Back Channel (unistrut or equal) by installer, as required C Website tomcofiresystems.com 6.57 6.87 8.85 9.09 10.35 Dimensions 8.80 9.10 11.08 11.32 12.58 B B A D 1.50 1.50 1.50 1.50 1.50 Page 1 of 1 51-0104-0400 High Pressure CO2 Fire Protection Typical Single-Cylinder Installation To Nozzles Discharge Hose with Check V alve or Discharge Adapter P/N 96060242 Junction Box by Installer Manual Actuator P/N 96060235 Solenoid V alve Kit P/N 96060322 To Electrical Control Electrical Connector P/N 96110012 Cylinder Strap Master Cylinder Assembly 7619 Hamilton Ave, Cincinnati, Oh 45231 Page 1 of 1 Telephone +1 513 729-2473 Fax +1 513 729-3444 Website tomcofiresystems.com 51-1050-0398 Cylinder Bracketry Fabricated by Installer Solenoid Valve Kit P/N 96060322 Electrical Connector P/N 96110012 Assembly 7619 Hamilton Ave, Cincinnati, Oh 45231 Master Cylinder Assembly To Nozzles Fax +1 513 729-3444 Assembly Slave Cylinder SW-50S Manifold by Installer Slave Cylinder Slave Cylinder Assembly Assembl Telephone +1 513 729-2473 Assembly Slave Cylinder SW-50S Manual Actuator P/N 96060235 Master Cylinder SW-50M Junction Box by Installer To Electrical Control Typical Assembly, 100 lb. Cylinders High Pressure CO2 Fire Protection 39" Website tomcofiresystems.com 58" Discharge Bend with Check Valve P/N 96060237 Optional Pressure Switch Page 1 of 1 51-51-1052-0997 High Pressure CO2 Fire Protection Typical Two-Cylinder Installation To Electrical Control Electrical Connector P/N 96110012 To Nozzles Discharge Bend with Check Valve P/N 96060237 Junction Box by Installer Manual Actuator P/N 96060235 Solenoid Valve kit P/N 96060322 Slave Cylinder Bracketry Fabricated by Installer Height of Cylinder Master Cylinder Assembly 2/3 Height of Cylinder Slave Cylinder Assembly 7619 Hamilton Ave, Cincinnati, Oh 45231 Page 1 of 1 Telephone +1 513 729-2473 Fax +1 513 729-3444 Website tomcofiresystems.com 51-1051-0501 Cylinder Bracketry Fabricated by Installer Solenoid Valve Kit P/N 96060322 Slave Cylinder Assembly Fax +1 513 729-3444 Slave Cylinder Assembly Reserve Master Cylinder Assembly To Nozzles Telephone +1 513 729-2473 Manifold by Installer 7619 Hamilton Ave, Cincinnati, Oh 45231 Main Master Cylinder Assembly Manual Actuator P/N 96060235 Electrical Connector P/N 96110012 Junction Box by Installer Changeover Switch To Electrical Control 39" Typical Main and Reserve Cylinder Installation High Pressure CO2 Fire Protection 58" Website tomcofiresystems.com Check Va lve ½" P/N 96060140 3/4" P/N 96060328 1" P/N 96060327 Page 1 of 1 51-51-1053-1097 Discharge Bend with Check Valve P/N 96060237 Optional Pressure Switch P/N 06-0247 High Pressure CO2 Fire Protection Manual/Pressure Actuator Part Number: 96060235 (Brass) 96060235 (Nickel Plated) 90º to operate 3 1/8 in (79 mm) 5 1/4 in (133 mm) 1/8" NPT hole with plug. This plug is to be removed only to install a pressure source. 2 9/16 in (65 mm) Locking Nut. Unscrew 1/4 turn to orientate body. SW-50 Discharge Valve 0.14 in (3.6 mm) Connecting Link Assembly 96060344 (Brass) Ensure piston is retracted before assembling to valve. Manual/Pressure Actuator 1. Install actuator only after cylinders have been secured in their brackets. 2. Before connecting actuator to cylinder valve, ensure: a) (a) The pull pin is installed and secured with a seal. b) (b) The piston is retracted as indicated. SW50M 3. Install the actuator to the cylinder valve, hand tighten. 4. Minimum pressure required for pressure operation: For 850 psi cylinder pressure (70º): 260 psi For 2,280 psi cylinder pressure (130º): 665 psi Connecting link used for simultaneous operation of two cylinder valves. Also used for remote manual cable operation, non-tension type. 7619 Hamilton Ave, Cincinnati, Oh 45231 Page 1 of 1 5. When a solenoid actuator is used, discharge from solenoid valve must be connected to the pressure port of the manual actuator. Telephone +1 513 729-2473 Fax +1 513 729-3444 Website tomcofiresystems.com 51-0142-0997 High Pressure CO2 Fire Protection Solenoid Actuator DIN Connector Tighten coupling nut securely 3/16" flexible hose. Connect to manual actuator. Tighten after connecting actuator to valve SW-50M Cylinder Valve Electrical Rating: 24 vdc, 10 watts. Part Number: 96060322 Important 1. The carbon dioxide cylinder assembly must be restrained in its bracket and discharge piping connected before solenoid actuator is connected to or disconnected from the cylinder valve. 2. The discharge from the solenoid valve must be connected to the manual actuator with the 3/16 inch flexible hose provided. Notes 1. The solenoid valve is normally closed. It opens when energized. 2. Solenoid enclosure is a general purpose type. Drip proof, raintight and explosion-proof enclosures are available by special order. 3. Standard voltage is 24 vdc. Other voltages are available by special order. 4. The solenoid valve is designed and rated for continuous duty service. 5. Operating temperature: 0 to 130 °F (-18 to 54 °C). 7619 Hamilton Ave, Cincinnati, Oh 45231 Page 1 of 1 Telephone +1 513 729-2473 Fax +1 513 729-3444 Website tomcofiresystems.com 51-0143-0997 High Pressure CO2 Fire Protection Flexible Discharge Bends ½" NPT Male solid to Manifold ½" NPT Male solid to Manifold Bend Assembly 22" overall Length Bend Assembly 22" overall Length Swivel Swivel 1-1/16" - 12 UN Valve Discharge Port Check Valve Discharge Adapter P/N 96040148 Discharge Bend with Adaptor PĚ€/N 96060242 Discharge Bend & Check Valve P/N 96060237 Use • The discharge bend and check valve are supplied locked together as a single unit. • • The discharge bend and check valve assembly must be used whenever cylinders are manifolded together. The discharge bend and adaptor assembly may be used for single cylinder systems. Hose Specification Hose Type SAE 100R1 Type AT Minimum Burst Pressure 5,000 PSI Minimum Bend Radius 9.5 Inches Equivalent Length, Discharge Bend and Check Valve 7.3 Feet (2.22 m) Of 1/2" Std Black Pipe. Installation • Cylinders and manifold must be installed securely before the discharge bends are installed. • Apply Teflon tape (pipe sealant) to the solid male 1/2" NPT pipe thread on then end of the hose. • Screw the solid male 1/2" NPT end of the discharge bend into the manifold, wrench tight. • Remove the safety shipping plug from the discharge port of the SW-50 cylinder valve and install the swivel end of the discharge bend assembly into the discharge port of the valve, wrench tight. 7619 Hamilton Ave, Cincinnati, Oh 45231 Page 1 of 1 Telephone +1 513 729-2473 Fax +1 513 729-3444 Website tomcofiresystems.com 51-0144-0997 CATALOG NUMBER C.1.32.01 PNEUMATIC TIME DELAY Architect and Engineer Specification Marine Suppression System P/N C70-235 (30 sec. delay) P/N C70-237 (60 sec. delay) UL - Ex 4447 ULC - CEx 1312 FM - 3002238 USCG - 162.161/2/0 (HFC-227ea) USCG - 162.038/12/0 (CO 2) 3 1/2" MAX (89 mm) 2" (51 mm) 22 1/4" (565 mm) 17" 6" (152 mm) (432 mm) 9/32" DIA (7 mm) TYP. 4 PLCS. 5 1/2" (140 mm) 4 1/4" (108 mm) INSTALLATION DESCRIPTION The pneumatic time delay delays the discharge of CO for 2 a predetermined amount of time. This extra time allows personnel to get out of the discharge area. It also allows additional time for ventilation and equipment shutdown. The pneumatic time delay is installed onto the discharge piping of the manifold. The valve body has a 3/4" NPT (20mm) threaded inlet and outlet for the piping connection. It is recommended that a union be placed on either side of the time delay for ease of removal. The time delay is installed between the master CO cylin2 ders and the discharge nozzles. The time delay has an inlet port and an outlet port, both with a ¾" NPT connection. The actual time delay period is pre-set at the factory. Tomco Fire Systems offers both 30 and 60 second time delays. In a CO 2 system the pneumatic time delay must be placed after the Master cylinder(s) and before the slave cylinder(s) connection(s) in the manifold. Refer to the typical arrangement drawings for installation configuration. The time delay will operate at temperatures from 0 to 130° F. Note: Delay times will vary slightly with the ambient temperature. Dimensions: 5 1/2" x 5 7/8" x 23 3/8" (139.7 x 149.2 x 593.7 mm) Materials: Time Delay - Brass Override lever - Stainless Steel Paint - Red gloss enamel The time delay is equipped with a manual override lever. This lever allows the time delay to be bypassed and allows the CO 2 to discharge immediately. SPECIFICATIONS July, 2002 Revised Issue 704 S. 10th Street • P.O. Box 610 • Blue Springs, Missouri 64013-0610 U.S.A. • (816) 229-3405 • Fax (816) 229-0314 • www.fike.com High Pressure CO2 Fire Protection Half-inch Header Safety 7/8" Hex Safety Nut Safety Disc 1/2" N Safety Washer Body Bursting Pressure 2650 to 3000 PSI Part Number: 96060276 7619 Hamilton Ave, Cincinnati, Oh 45231 Page 1 of 1 Telephone +1 513 729-2473 Fax +1 513 729-3444 Website tomcofiresystems.com 51-0156-0200 High Pressure CO2 Fire Protection Selector Valves ¼" — 18 NPT Pilot pressure outlet Seal Retainer Rings Piston Seals Nut Piston: Brass, ASTM B16 Alloy UNS C36000 O-ring Top Cap: Forged Brass, ASTM A124 ¼" — 18 NPT Pilot pressure outlet Pushrod 416 SST Disc Nut Pipe Flow Seat Disc Body: Leaded red brass, ASTM 4A (85-5-5) Bottom Cap: Cast brass Disc Holder: Brass, ASTM B16 Alloy UNS C36000 Spring Description Ordering Information Selector or directional valves allow the use of a single group of cylinders to protect multiple areas or hazards. These valves act as blocking devices directing the flow of CO2 to the protected space. Valve sizes range from ½" (13 mm) to 4" (102 mm) outlet sizes. Valves are provided with a screwed inlet and outlet connection. 3" and 4" valves have a flanged connection on both. 7619 Hamilton Ave, Cincinnati, Oh 45231 Page 1 of 1 O-ring 9630610047 9630610048 9610610371 9610610369 9610610370 9610610733 9610610734 9620480482 96060347 Telephone +1 513 729-2473 Selector Valve, ½ inch (13 mm), screwed Selector Valve, ¾ inch (19 mm), screwed Selector Valve, 1 inch (25 mm), screwed Selector Valve, 1½ inch (38 mm), screwed Selector Valve, 2 inch (51 mm), screwed Selector Valve, 3 inch (76 mm), flanged Selector Valve, 4 inch (102 mm), flanged Actuation Kit for Selector Valves with manual actuation. Selector/Stop Valve, ½-¾" brass, R1 type Fax +1 513 729-3444 Website tomcofiresystems.com 51-0111-0109 A 'L' 2 2 7619 Hamilton Ave, Cincinnati, Oh 45231 1½ 1½ 1¼ 1 1¼ 1 1¼ 1 ¾ ¾ 5.82 4.55 4.13 3.75 3.40 3.38 Length L (inches) PORT 'B' Telephone +1 513 729-2473 2½ 2 1½ ¾ ½ ½ Port B (OUT) NPT Port A (IN) NPT A 'W' Nominal Size (inches) In-line Check Valves High Pressure CO2 Fire Protection Part No. 96060323 96060325 96060326 96060327 96060328 96060140 Fax +1 513 729-3444 3.63 3.0 2.5 2.0 1.63 1.50 Dimension W (inches) A/F SECTION A-A Website tomcofiresystems.com Page 1 of 1 51-0134-0899 PORT 'A' High Pressure CO2 Fire Protection Pressure Operated Switch Rating: Operated Position Moisture-proof joint Pressure Switch, Part No. 96060247 Double pole, double throw Switch box Reset Plunger (raised position indicates the switch has operated. 15 Amps, 120 Vac per pole 8 amps, 240 Vac per pole 1 HP, 120 Vac, 5 phase Name Plate Finish: Cadmium plated weatherproof enclosure The pressure connection of the switch can be connected to the discharge piping of any cylinder in the system, or to the nitrogen actuation tubing, if used. Togle switch in normal "standby" position. 2 1/4 in Pressure switches can be used to shut down motors, pumps, fans, or operate alarms, release doors, or provide confirmation of extinguishment system operation, etc. automatically when the extinguishing system discharges. Piston Cover Plate 1/4" NPT (Pressure connection) 1 1/4 in For ½" Electric conduit 1 3/4 in Mounting and application The switch may be mounted in any position, but the preferred installation is with the pressure connection (gas supply line) entering from the bottom. Pipe to nozzles Installation can be made using 1/4" steel pipe and fittings. Alternately, 1/4" or 3/16" x .032" wall soft copper tubing with swagelock or equal fittings can be used. Typical installation using copper tubing Note: When the line load is greater than the switch rating, the switch should be used to break a relay holding coil circuit (relay supplied by others). Testing Tube x N.I.P. Fitting To test the circuits and to ensure auxiliary functions operate correctly: Either.. 1. If additional switches or release trips are required, install Tee and branch to other units. Disconnect the union at the pressure connection, insert a small rod into the pressure connection of the cover plate, and push against the piston to trip the switch. Push the plunger down to reset the switch. Or... 2. Remove the four cover screws and swing the cover away from the switch box. Manually operate the interior toggle switch. After testing, ensure the toggle is mounted in the normal standby position, then reinstall the cover plate. 3/16" or 1/4" o.d. x 0.32" wall tube Tube x N.I.P. Fitting Pipe from cylinders 7619 Hamilton Ave, Cincinnati, Oh 45231 Page 1 of 1 Telephone +1 513 729-2473 Fax +1 513 729-3444 Website tomcofiresystems.com 51-0102-0304 High Pressure CO2 Fire Protection Bleeder Valve 7/8" Hex Vent 2-1/2" 1/2" NPT Part no. 96040343 This bleeder valve is installed in main and reserve cylinder manifolds to vent accidental check valve leakage during discharge of one cylinder bank. If unvented, accumulated leakage pressure could cause actuation of the other cylinder bank. The valve closes when manifold pressure reaches approximately 20 PSIG to prevent agent loss under normal discharge conditions. 7619 Hamilton Ave, Cincinnati, Oh 45231 Page 1 of 1 Telephone +1 513 729-2473 Fax +1 513 729-3444 Website tomcofiresystems.com 51-0168-0403 1/2” - 2” Lock-out Valve The lock-out valve is a manually operated valve used to inhibit the discharge of CO2 into an entire system or specific area of a system. The valves are rated to a working pressure of 2,200psi WOG. The valve is equipped with a supervisory switch for remote monitoring and a locking device to pad lock the valve in the open or closed position. Material: Body: Ball/Stem: Seats: Carbon Steel Stainless Steel RTFE Switch Rating: Housing: Contacts: Approval: NEMA 4 10a 24vDc/120vac/250vac FM Approvals FM Approvals has not verified the NEMA rating of the housing. A B POSITION INDICATOR 3/4" [19] NPT CONDUIT OPENING D E F LOCKING DEVICE C Refer to next page for dimensional information Tomco Fire Systems 7619 Hamilton Avenue Cincinnati, OH 45231 Equipment Data Sheet 990920 Rev. 0 5/06 1/2” - 2” Lock-out Valve Size Part Number A B C D E F Weight 1/2” 990920 7 5/8” (194) 6 3/8” (162) 3” (76) 10 1/2” (267) 11 5/8” (296) 6 1/2” (165) 5.5 lbs 2.5 kg 3/4” 990921 7 5/8” (194) 6 3/8” (162) 3 3/8” (86) 10 3/4” (273) 11 15/16” (303) 6 1/2” (165) 7 lbs 3.2 kg 1” 990922 7 5/8” (194) 6 3/8” (162) 4” (102) 11 1/4” (286) 12 11/16” (322) 9 7/8” (251) 8.5 lbs 3.9 kg 1 1/4” 990923 7 5/8” (194) 6 3/8” (162) 4 3/8” (111) 11 7/16” (291) 13 3/16” (335) 9 7/8” (251) 11 lbs 5 kg 1 1/2” 990924 7 5/8” (194) 6 3/8” (162) 5” (127) 11 3/4” (299) 13 5/8” (346) 10 7/16” (265) 14 lbs 6.4 kg 7 5/8” (194) 6 3/8” (162) 5 3/4” (146) 12 1/8” (308) 14 9/16” (370) 10 7/16” (265) 21 lbs 9.5 kg 2” 990925 RED BLUE YELLOW RED BLUE YELLOW N.O. N.C. LOWER/CLOSE COM. N.O. N.C. UPPER/OPEN COM. CAMS Switch Configuration Tomco Fire Systems 7619 Hamilton Avenue Cincinnati, OH 45231 Equipment Data Sheet 990900 Rev. 0 5/06 High Pressure CO2 Fire Protection Half inch Wall Nozzle for Total Flooding Applications Nozzle orfice sized to suits design requirement 1.75 7/8 AF 1/2" NPT Part Number: 96060237 Part Number: 96060237 7619 Hamilton Ave, Cincinnati, Oh 45231 Page 1 of 1 Telephone +1 513 729-2473 Fax +1 513 729-3444 Website tomcofiresystems.com 51-0145-0899 High Pressure CO2 Fire Protection Pneumatic Siren Decibel Rating: CO2 Consumption: Materials: Housing: Wheel: Part Number: Approval: 90 dBa @ 10' [3.05m] 12lbs/min [5.5 kg/min] Brass Stainless Steel 990979 FM Approvals 7619 Hamilton Ave, Cincinnati, Oh 45231 Page 1 of 1 Telephone +1 513 729-2473 Fax +1 513 729-3444 Website tomcofiresystems.com 51-0152-0997 High Pressure CO2 Fire Protection Pressure Release Trip Re lease Tr ip, P art No. 96060246 Body material: Cast brass 1 1/2" 25/32" 3 1/2" Piston Spring 3 1/8" Stem Vent with rubber bung 1/4" NPT pressure connection 2 mounting holes (3/8" dia.) Notes These units are used to release dampers, doors, windows, louvres, to open dump valves, and to close fuel supply valves, etc. automatically when agent discharges. Ty pical Connectio n Re lease T rip to Discharge Piping The equipment to be operated must be weight or spring loaded, or be pivoted off-centre. The pressure connection of the trip can be connected to the discharge piping of any cylinder in the system, to the rid valve pilot tubing, or to the nitrogen actuation tubing. Tube X M.I.P . Fitting The maximum load that can be hung on the piston stem is 76 lb. (34 kg). Connection can be made in 1/4" steel pipe, 1/4" or 3/16" x .032" wall soft copper tube. Swagelok, Gyrolok, or similar fittings are recommended for tube connections. Optional Anti-vibration Bracket If additional release trips or pressure switches are required, install branch tees to suit. Extinguishing agent suppl y To device operated or released 7619 Hamilton Ave, Cincinnati, Oh 45231 Page 1 of 1 Telephone +1 513 729-2473 Fax +1 513 729-3444 Website tomcofiresystems.com 51-0100-0304 High Pressure CO2 Fire Protection Remote Manual Control Application ax. 30° m 9" min. clear (typical) Connecting Link Cable Clamp Conduit Bracket & Fitting 90° Corner Pulley 1/16" dia.Stainless Steel Cable To Pull Box Lever-operated Actuator Conduit Bracket & Fitting To Cylinder Valve Actuator ½" Conduit or 3/8" Pipe Single Actuation from two Pull Boxes Installation N Notes 1. Run cable in 1/2" EMT conduit or 3/8" diameter pipe. 2. Install a corner pulley at each change in direction of cable. for installa3. Covers of corner pulleys must be accessible after installation to allow removal re tion of cable. FOR FIRE FOR FIRE OPEN DOOR PULL HANDLE HARD OPEN DOOR PULL HANDLE HARD 4. Remote manual pull box should be installed three to fieve feet above flooor level in a readily accessible location, and in the main egress from the protected space. Pull Boxes 5. Ensure space in front of pull box will allow a straight pull of approximately nine inches. Alternatively, actuation of two separate devices (i.e.: cylinder valve and selector valve) from a single pull box. 6. Before starting to install the cable, ensure the safety pin is installed in the th actuator(s). Remove the safety pin after completion of cable installation. 7. Maximum length of 1/16" stainless steel cable that can be installed is 500 50 feet. 8. Maximum number of pulleys that can be used: a) on a single run is 15. b) on a double run arrangement is 18, with a maximum of nine on any one leg. 7619 Hamilton Ave, Cincinnati, Oh 45231 Page 1 of 1 Telephone +1 513 729-2473 Fax +1 513 729-3444 Website tomcofiresystems.com 51-0108-0304 High Pressure CO2 Fire Protection Remote Manual Control Components 90 º Corner Pulley Pa rt No. 96060245 Conduit Brackets 4" 1" 2 11/16" 1 3/4" 2" 7/8" 3/8" diameter mounting holes Both holes threaded for 3/8" pipe "A" (See table) 1 1/8" Cable Clamp Pa rt No. 96060012 3/8" 3/4" 1/2" Dual Junction Pa rt No. 96060256 Conduit Bracket Dimension "A" Used on... 96060257 1 3/4" Small cylinders up to 20 lbs. 96060248 2 1/2" Large cylinders more than 50 lbs. Two socket set- screws 2 1/4 3/8" diameter mounting holes 3 3/8" Direction of pull (see note) 9" (min.) Cover fastening screws 1" (max.) 16 1/2" Note: to pull in the opposite direction, reverse the two boxed dimensions. Latch T ype Pull Box Pa rt No. 96060259 Two 3/16" diameter countersunk mounting holes 3/8" pipe thread Base of pull box wall mounted Lead and wire seal broken when catch is opened 15/16" diam . 2 Pull handl e FOR FO OR FIRE FIIRE OPEN OP PEN EN DOOR DOOR PU ULL HANDLE HANDL DLE HARD HARD D PULL 4 1/8" 1-7/16" 7 /8 " Providete adequna ce cleara r to for doofully open Catch 4 3/16" 1/2" 7619 Hamilton Ave, Cincinnati, Oh 45231 Page 1 of 1 Telephone +1 513 729-2473 Fax +1 513 729-3444 Website tomcofiresystems.com 51-0109-0304 High Pressure CO2 Fire Protection S-Type Discharge Nozzle 1/2" NPT Nozzle assy P/N 96060291 Performance Data Flange set P/N 96060353 Orifice code stamped here Height ft. Flow Rate (lb per min.) Area of Coverage (sq. ft.) 1 16 5.0 2 24 7.0 3 32 8.7 4 41 10.7 5 49 12.6 6 57 14.5 7 66 15.0 8 74 15.0 Enclosure Nozzles up to and including #5 orifice are equipped with strainers. Materials: Installation without seal Installation with seal in place horn - steel ni pltd insert & body - brass flanges - steel ni pltd Flange set consists of two flanges, seal, 3 nuts, bolts 7 washers. Ordered as a set. 5/16 cap screw 5/16 nut Installation 5/16 lockwasher Seal P/N 96040504 flanges Installation with seal without enclosure (To be replaced after each discharge) 7619 Hamilton Ave, Cincinnati, Oh 45231 Page 1 of 1 Telephone +1 513 729-2473 1. Cut a 3-5/8" dia. Hote in side of enclosure where shown on system drawing. Drill three 3/8" holes for cap screws using a clamping flange as a template. 2. If hazard is totally enclosed (i.e. In an air duct), cut a hand hole adjacent to nozzle for access for nut and bolt fixing. (Cover hand hole after nozzle installation.) Fax +1 513 729-3444 Website tomcofiresystems.com 51-0146-0202 High Pressure CO2 Fire Protection Vent Nozzle 1-1/8 AF 1/2" NPT 1.69in 1/2" NPT Nozzle orfice sized to suit design requirements MATERIAL: BRASS Part Number: 96060360 7619 Hamilton Ave, Cincinnati, Oh 45231 Page 1 of 1 Telephone +1 513 729-2473 Fax +1 513 729-3444 Website tomcofiresystems.com 51-0169-0203 High Pressure CO2 Fire Protection Test Unit, 24 VDC Solenoid Valve Light Adapter LED Attach connector cable here. LED will light when solenoid circuit is activated. This unit is insensitive to polarity and is equipped with VDR protection against overvoltages when switching off. Dummy Solenoid Coil 7619 Hamilton Ave, Cincinnati, Oh 45231 Page 1 of 1 Telephone +1 513 729-2473 Fax +1 513 729-3444 Website tomcofiresystems.com 51-0135-1099 1-5/8” Ref Double Bracket Marine Installations 36" (91cm ) Back beam (2) 96050016-XX 7619 Hamilton Ave, Cincinnati, Oh 45231 Section A- A Telephone +1 513 729-2473 Anchor bolts to be anchored into solid structure (by others) 10.0 Ref 12 Ctrs Ref Showing the arrangement for an odd number of cylinders A A Washer , 96020048 Lockwasher , 96020084 Nut, 96020047 Note: Install captive nuts in back beam before beam is fastened to wall Captive nut 96020085 15” (38 cm ) Single Bracket Standard Industrial Installations 36" (91cm ) 2. 7 Ref 3/8" anchor bolts by others Position 12” to 24” apart avoiding contact with cylinders 3/8" threaded rod 14-1/2” long 96040469,, as a req’d 100 lb. CO2 Cylinder Fax +1 513 729-3444 Typical wall fastening Page 1 of 1 51-51-1054-1097 12 0 5 4 9 15 19 19 4 Part no. for the complete module is 51-1055-XX, where XX represents the total no. of cylinders. 5. Hardware required for two bank set-up 5 6 7 8 9 10 11 1 0 1 0 1 0 1 1 2 2 3 3 4 4 4 4 4 4 4 4 4 6 6 7 7 8 8 9 5 6 8 9 11 12 14 9 10 12 13 15 16 18 9 10 12 13 15 16 18 4 4 4 4 4 4 4 Design is based upon the use of 1-5/8” technistrut beams and components, or similar. XX of the part no. for the front beam indicates the number of cylinders contained by the beam. XX of the part no. for the two back beams indicates the number of cylinders between them. See 51-1054 for single bank. 4. 3. 2. 1. Notes Website tomcofiresystems.com 4 0 1 4 5 3 7 7 4 Steel angle, 96050019 Cap screw, 96020065 Washer, 96020048 Lockwasher, 96020084 Captive nut, 96060085 Total no. of cylinders Rod, 14-1/2", 96040469 Rod, 26-1/2", 96040470 Angle, 96050019 Captive nut, 96020085 Plain nut, 96020047 Plain washer, 96020048 Lockwasher, 96020084 Cap screw, 96020065 Front beam , 96050018-XX to suit the no. of cyl in front row 3/8" threaded rod 26-1/2” long, 96040470 11.0 Ref Typical Bracketing, Double Bank 100 lb. Cylinders High Pressure CO2 Fire Protection 10 lb CO2 Cylinder (or size to suit) Discharge Adapter P/N 9604299 Standard Pipe Union Actuator P/N 96060235 Sirens in protected area Master Actuator 7619 Hamilton Ave, Cincinnati, Oh 45231 Solenoid 1/8" pipe or 3/16" copper tube Pressure Switch if required Telephone +1 513 729-2473 Master Time Delay if required P/N 96060345 Slave 3/4" NPT Fax +1 513 729-3444 Slave Page 1 of 1 51-51-1064-0402 To Nozzles © Copyright 2008 inControl Systems and Automation. All rights reserved Website tomcofiresystems.com 3/4" NPT Actuator if R equired P/N 96060348 Stop V alve if required P/N 96060347 Adapter if R equired P/N 96040499 Typical Installation with Gas Operated Sirens High Pressure CO2 Fire Protection 7619 Hamilton Ave, Cincinnati, Oh 45231 Master Cylinder Assembly Slave Cylinder Assembly Slave Cylinder Assembly Slave Cylinder Assembly Slave Cylinder Assembly Master Cylinder Assembly Master Cylinder Assembly Main CO2 Supply Master Slave Slave Slave Slave Master Zone 2 Master Change - Over Switch P/N 96060235 Zone select Zone 1 Slave Cylinder Assembly Slave Slave Cylinder Assembly Slave Zone 3 Telephone +1 513 729-2473 Pressure Switch P/N 990119 (optional ) Slave Slave Cylinder Assembly Fax +1 513 729-3444 Slave Cylinder Assembly Slave Check Valve Detail 'A' Selector Solenoid Valve Actuation Kit P/N 96060335 Website tomcofiresystems.com Page 1 of 1 51-51-1059-1001 Manifold Bleed Valve P/N 96060343 See also Data Sheet No. 51-1052 Manifold Header Safety P/N 96060276 Selector Va lve see detail ‘A’ below Reserve CO2 Supply Master Cylinder Assembly Master Typical Joint System with Main and Reserve Cylinders High Pressure CO2 Fire Protection High Pressure CO2 Fire Protection CO2 Pressure/Temperature Curve g ng lin ing ng Filli ng Fil Fill Filli % 5 Filli 6 % % % % 5 8 0 4 8 6 6 5 6 5 180 170 160 150 140 Temperature: Degrees Fahrenheit 130 120 110 100 90 80 70 60 50 40 30 20 10 0 -10 -20 -30 -40 0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 3400 3600 3800 Pressure: Lbs. per Square Inch This curve shows the pressure in carbon dioxide cylinders at various temperatures when filled to a percentage of their water capacity. In general, cylinders should not be filled to more than 68% or less than 60% of their water capacity. Cylinders currently supplied by inControl fire are filled to 68% of their water capacity. Percent filling = Lb. CO2 in cylinder Lb. water capacity of cylinder 7619 Hamilton Ave, Cincinnati, Oh 45231 Page 1 of 1 Telephone +1 513 729-2473 x 100 Fax +1 513 729-3444 Website tomcofiresystems.com 51-0140-0997 High Pressure CO2 Fire Protection Warning Signs 10" [254.00] WARNING Carbon dixide gas can cause injury or death. When alarm operates, do not enter until ventilated. CAUTION Carbon dixide gas can cause injury or death. Ventilate the area before entering. A high carbon dioxide gas concentration can occur in this area and can cause suffocation. 7" [177.80] Ø1/8" [Ø3.18] Part Number: 990491 Part Number: 990493 WARNING CAUTION Carbon dixide gas can cause injury or death. When alarm operates, vacate immediately. Carbon dixide gas can cause injury or death. Carbon dioxide gas discharge into nearby space can collect here. When alarm operates vacate immediately. Part Number: 990492 7619 Hamilton Ave, Cincinnati, Oh 45231 Page 1 of 1 Part Number: 990495 Telephone +1 513 729-2473 Fax +1 513 729-3444 Website tomcofiresystems.com 51-0149-0997 1-5/8 Ref Double Bracket Marine Installations 36” (91 cm ) Washer , 96020048 Lockwasher , 96020084 Nut, 96020047 Plan View A A Section A- A 7619 Hamilton Ave, Cincinnati, Oh 45231 NOTE: Install captive nuts in back beam before beam is fastened to wall Captive nut 96020085 15” (38 cm ) Single Bracket Standard Industrial Installations 36" (91cm ) 2. 7 Ref 12 Ctrs Ref Telephone +1 513 729-2473 13.3 Ref No. of cylinders Rod, 14-1/2", 96040469 Angle, 96050019 Captive nut, 96020085 Plain nut, 96020047 Plain washer, 96020048 Lockwasher, 96020084 Cap screw, 96020065 10.7 Ref Fax +1 513 729-3444 Typical Wall Fastening 3/8" Threaded rod 14-1/2" long 96040469 Back Beam 96050016-XX Anchor bolts to be anchored into solid structure 3/8" anchor bolts by othere Position 12” to 24” apart avoiding contact with cylinders Typical Bracketing, Single Bank 100 lb. Cylinders High Pressure CO2 Fire Protection No. of pieces required for single bank set-up 3 4 5 6 7 8 9 2 3 4 5 6 7 8 2 2 2 2 2 2 2 4 5 6 7 8 9 10 3 6 8 10 12 14 16 6 8 10 12 14 16 18 6 8 10 12 14 16 18 2 2 2 2 2 2 2 10 9 2 11 18 20 20 2 Website tomcofiresystems.com Page 1 of 1 51-51-1054-1097 2. Design is based upon the use of 1-5/8” technistrut beams and components, or similar. 1. XX of beam part no. indicates the number of cylinders. Notes 2 1 2 3 2 4 4 2 Front beam 96050018-XX 100 lb. CO2 Cylinder Steel angle 96050019 Cap screw , 96020065 Washer , 96020048 Lockwasher , 96020084 Tomco2 Fire Systems System Design 8/16/10 Rev. 0 SECTION 3 SYSTEM DESIGN Table of Contents Paragraph 3-1 3-2 3-3 Subject General Total Flood System Design Local Application System Design Tomco2 Fire Systems System Design 8/16/10 Rev. 0 SECTION 3 SYSTEM DESIGN 3-1 GENERAL This section is provided as a guide in designing a high pressure CO2 fire extinguishing system. The two major types of systems covered in this section are total flooding and local application. 3-2 TOTAL FLOOD SYSTEM DESIGN A. A total flooding system consists of a fixed supply of carbon dioxide connected to a piping network with fixed nozzles that discharge into an enclosed space. This type of system may be used whenever an enclosure exists about the hazard. The enclosure must be adequate to contain the discharge of agent to achieve the required carbon dioxide concentration. Figure 3-1 illustrates a total flood design process. B. Fires which can be extinguished by total flooding methods may be divided into two categories: 1. Surface fires involving flammable liquids, gases and solids. 2. Deep seated fires involving solids subject to smoldering. C. Surface fires are the most common hazard and are usually subject to prompt extinguishment when carbon dioxide is quickly introduced into the enclosure in sufficient quantity. D. For deep-seated fires, the required extinguishing concentration shall be maintained for a sufficient period of time to allow the smoldering to be extinguished and the material to cool to a point to prevent re-ignition. 3-1 Tomco2 Fire Systems System Design 8/16/10 Rev. 0 SYSTEM DESIGN PROCESS TOTAL FLOODING Caution: This design criteria is for enclosure temperature only. Figure 3-1 Total Flood Design Process 3-2 Tomco2 Fire Systems System Design 8/16/10 Rev. 0 3-2.1 Quantity Calculations for Surface Fires A. Section 5-3 of NFPA Standard 12 2005 gives the guidelines for determining the quantity of carbon dioxide quantities for surface fires. B. The minimum design concentration of carbon dioxide required in no case shall be less than 34%. C. Table 3-1 lists the minimum design concentrations required for extinguishment of some common liquids and gases. 3-3 Tomco2 Fire Systems System Design 8/16/10 Rev. 0 Material Minimum Design CO2 Concentration (%) 66 34 36 37 41 34 37 72 64 37 37 40 40 46 40 43 46 49 34 53 34 35 34 75 36 36 34 34 36 34 34 35 40 36 40 39 35 36 36 34 Acetylene Acetone Aviation Gas Grades 115/145 Benzol, Benzene Butadiene Butane Butane 1 Carbon Disulfide Carbon Monoxide Coal or Natural Gas Cyclopropane Diethyl Ether Dimethyl Ether Dowtherm Ethane Ethyl Alcohol Ethyl Ether Ethylene Ethylene Dichloride Ethylene Oxide Gasoline Hexane Higher Paraffin Hydrocarbons Hydrogen Hydrogen Sulfide Isobutane Isobutylene Isobutyl Formate JP - 4 Kerosene Methane Methyl Acetate Methyl Alcohol Methyl Butane 1 Methyl Ethyl Ketone Methyl Formate Pentane Propane Propylene Quench, Lube Oils Note: The theoretical minimum extinguishing concentrations in air for the above materials were obtained from a compilation of Bureau of Mines Limits of Flammability of Gases and Vapors (Bulletins 503 and 627). Table 3-1 Minimum Carbon Dioxide Concentrations for Extinguishment (TABLE 5.3.2.2 from NFPA 12 2005) 3-4 Tomco2 Fire Systems System Design 8/16/10 Rev. 0 D. In figuring the net cubic volume to be protected, the volume of permanent, nonremovable, impermeable structures may be subtracted from the gross volume to be protected, however, this allowance is not recommended. E. In two or more interconnected volumes where "free flow" of carbon dioxide can take place, the carbon dioxide quantity shall be the sum of the quantities for each volume, using its respective volume factor from table 3-2. If one volume requires greater than 34% concentration, the higher concentration shall be used in all interconnected volumes. Volume of Space (ft3 Incl.) Up to 140 141 500 501 1,600 1,601 4,500 4,501 50,000 Over 50,000 Volume Factor 3 (ft /lb. CO2) (lb. CO2/ft3) 14 .072 15 .067 16 .063 18 .056 20 .050 22 .046 Calculated Quantity Not Less Than ---10 35 100 250 2,500 Table 3-2 Flooding Factors For 34% Concentration (Table 5.3.3(a) NFPA 12 2005) 3-2.2 Material Conversion Factor Conversion Factor For materials requiring a design concentration over 34%, the basic quantity of carbon dioxide calculated from the volume factor given in table 3-2 shall be increased by multiplying this quantity by the appropriate conversion factor given in table 3-3. 4 3 2 1 30 34 40 50 60 70 80 Minimum Design CO2 Concentration - % Table 3-3 Material Conversion Factors (Table 5.3.4 NFPA 12 2005) 3-5 90 Tomco2 Fire Systems System Design 8/16/10 Rev. 0 3-2.3 Special Conditions A. Additional quantities of carbon dioxide shall be provided to compensate for any special condition that may adversely affect the extinguishing efficiency. B. Any openings that cannot be closed at the time of extinguishment shall be compensated for by the addition of a quantity of carbon dioxide equal to the anticipated loss at the design concentration during a one (1) minute period. This amount of carbon dioxide shall be applied through the regular distribution system. See 5.4.4.1 of NFPA Standard 12 2005. C. For ventilating systems which cannot be shut-down, additional carbon dioxide shall be added to the space through the regular distribution system in an amount computed by dividing the volume moved during the liquid discharge period by the flooding factor. This shall be multiplied by the material conversion factor determined in table 3-3 when the design concentration is greater than 34%. D. For applications where the normal temperature of the enclosure is above 200º F (93º C), a 1% increase in the calculated total quantity of carbon dioxide shall be provided for each additional 5º F (-15º C) above 200º F (93º C). E. For applications where the normal temperature of the enclosure is below 0º F (-18º C), a 1% increase in the calculated total quantity of carbon dioxide shall be provided for each degree below 0º F (-18º C). F. Under normal conditions, surface fires are usually extinguished during the discharge period. Except for unusual conditions, it will not be necessary to provide extra carbon dioxide to maintain the concentration. G. A flooding factor 8 ft3/lb. shall be used in ducts and covered trenches. If the combustibles represent a deep-seated fire, it shall be treated as described in section 3.2.4. 3-2.4 Quantity Calculations for Deep Seated Fires The quantity of carbon dioxide for a deep-seated type fire is based on a fairly tight enclosure. After the design concentration is reached, the concentration shall be maintained for a substantial period of time, but not less than 20 minutes. Any possible leakage shall be given special consideration since no allowance is included in the basic flooding factors. 3-2.5 Combustible Materials A. For combustible materials capable of producing deep-seated fires, the required carbon dioxide concentrations cannot be determined with the same accuracy possible with surface burning materials. The extinguishing concentration will vary with the mass of material present because of the thermal insulating effects. Flooding factors have therefore been determined on the basis of practical test conditions. B. The design concentrations listed in table 3-4 shall be achieved for the hazards listed. Generally, the flooding factors have been found to provide proper design concentrations for the rooms and enclosures listed. 3-6 Tomco2 Fire Systems System Design 8/16/10 Rev. 0 C. Flooding factors for other deep seated fires shall be justified to the satisfaction of the authority having jurisdiction before use. Proper consideration shall be given to the mass of material to be protected because the rate of cooling is reduced by the thermal insulating effects. ft3/lb. CO2 10 m3/kg CO2 0.62 lbs. CO2/ft3 0.100 kg CO2/m3 1.60 50 12 0.75 0.083 (200 lb. minimum) 1.33 (91 kg minimum) 65 8 0.50 0.125 2.00 75 6 0.38 0.166 2.66 Design Concentration % 50 Specific Hazard Dry electrical hazards in general. (Spaces 0-2000 ft3) Dry electrical hazards in general. (Spaces greater than 2000 ft3) Record (bulk paper) storage, ducts and covered trenches. Fur storage vaults, dust collectors. Table 3-4 Flooding Factors for Specific Hazards (Table 5.4.2.1 NFPA 12 2005) D. For deep seated fires the design concentration shall be achieved within 7 minutes as specified in Paragraph 5.5.2.3 of the NFPA Standard 12 2005. In addition to the basic quantity, any leakage or temperature factors must be added. The discharge rate shall develop a concentration of 30% that must be achieved within 2 minutes. To develop the 30% concentration within 2 minutes a flooding factor of 0.043 lbs/fr3 should be used. 3-2.6 Estimated Flow Rate Calculations A. The problem encountered in flow rate calculations is complicated by the physical characteristics of carbon dioxide. The agent leaves the storage tank as a liquid at saturation pressure (850 psig @ 70º F). B. As the temperature of the liquid increases as it flows through the discharge piping, the liquid CO2 begins to vaporize producing a mixture of liquid and vapor. As the pressure increases, the density of the vapor over the liquid increases. On the other hand, the liquid expands as the temperature goes up and its density decreases. This phenomenon reduces the density of the agent and results in an increase in the flow velocity. C. Since the flow rate for the vapor phase is considerably less than the flow rate for the liquid phase, compensation must be made during the calculation of the actual flow rate. 3-2.7 Nozzle Placement Guide A. Tomco2 Fire Systems uses both wall, vent or s-type discharge nozzles for total flood hazards. All of these types of nozzles have proven to be effective in providing a uniform concentration throughout the hazard enclosure. 3-7 Tomco2 Fire Systems System Design 8/16/10 Rev. 0 B. The wall nozzle usually creates a high velocity discharge that provides a thorough mix of CO2 throughout the entire enclosure. S-type nozzles are usually used when a slower more "cushioned" discharge is required in areas such as computer rooms, sub-floor areas or records vaults where a high velocity discharge could seriously damage the contents. Vent nozzles are typically used in small spaces, such as duct work. C. It is not necessary to place the nozzles directly at the ceiling level. In applications where obstructions are encountered at the ceiling level, the nozzles should be installed lower than these obstructions. In no case should the nozzles be installed less than 3' above the highest object within the protected enclosure. D. A full discharge test shall be conducted on all systems. The coverage of nozzles in the actual installation will be verified by this test except when waived by the authority having jurisdiction. More often the area of coverage per nozzle will be reduced from the above recommended maximums due to: 1. Inability of single nozzle to deliver the required flow rate to flood the maximum area. 2. Consideration of obstructions within the hazard that require additional nozzles to cover the space on both sides of the obstruction. 3. The hazard contains delicate or fragile materials that might be damaged by a highly turbulent discharge. Table 3-5 Nozzle Spacing E. The particular shape or the contents of a hazard may also necessitate a greater number of nozzles than what is shown on the above chart. F. The wall nozzle can be used in most total flood applications. Maximum spacing shall not exceed 16ft. G. Wall nozzles should not be used for protecting ducts, pits or covered trenches. H. In special applications requiring a low velocity discharge, s-type nozzles usually associated with local application may be used in total flooding systems and should not exceed a maximum side dimension of 16 feet. I. Protection of any unusual shaped volumes or excessive ceiling heights should be directed to Tomco2 Fire Systems. 3-8 Tomco2 Fire Systems 3-3 System Design 8/16/10 Rev. 0 LOCAL APPLICATION SYSTEM DESIGN 3-3.1 General A. A local application system consists of a fixed supply of carbon dioxide permanently connected to a system of fixed piping with nozzles arranged so as to discharge the agent directly onto the hazard. B. Local application systems are used for the suppression of surface fires in flammable liquids, gases and shallow solids where the hazard is not enclosed or where the enclosure does not conform to the requirements for total flooding. Examples of hazards that may be protected by local application systems include dip tanks, quench tanks, spray booths, machining operations and printing presses. Figure 3-2 illustrates a local application design process. C. A discharge test must be conducted to verify complete coverage of the hazard based on nozzle placement. D. To determine the nominal cylinder storage capacity for all local application systems, the computed quantity of carbon dioxide shall be increased by 40% to compensate for the vapor phase of discharge. Only the liquid portion of the discharge is effective. 3-9 Tomco2 Fire Systems System Design 8/16/10 Rev. 0 HAZARD ANALYSIS LOCAL APPLICATION LIQUID SURFACE WETTED SURFACE NOZZLE PLACEMENT NOZZLE FLOW RATE AGENT QUANTITY HYDRAULIC CALCULATIONS (NOZZLE ORIFICE CODES AND PIPE SIZES) DETECTION AND ACTUATION EQUIPMENT Figure 3-2 Local Application Design Process 3-10 Tomco2 Fire Systems System Design 8/16/10 Rev. 0 3-3.2 Types of Surface Fires A. Within the scope of this manual, two types of surfaces must be considered: liquid surfaces and wetted or coated surfaces. The liquid surface is that surface of deep layer of flammable liquid usually more than 1/4" in depth that is exposed to the atmosphere. Wetted or coated surfaces are defined as those designed for drainage which are constructed and maintained so that no pools of liquid usually less than 1/4" in depth and will accumulate over a total area exceeding 10% of the protected surface. This does not apply where there is a heavy buildup of residue. B. National Fire Protection Association NFPA 12 Standard For Carbon Dioxide Systems and FM Global Property Loss Control Data Sheets should be referenced when determining the suitability of a hazard for the local application method of protection. 3-3.3 Duration of Discharge The minimum effective discharge time for computing quantity of agent shall be 30 seconds of liquid discharge at the nozzles. Where there is a possibility that metal or another material may become heated above the ignition temperature of the fuel, the effective (liquid) discharge time shall be increased to permit adequate cooling of the material. Special fuels such as paraffin wax or cooking oil require a minimum discharge time of 3 minutes because the auto-ignition point is below its boiling point. 3-3.4 Methods of Application There are two accepted methods of calculating the quantity of CO2 required for local application systems. The RATE-BY-AREA METHOD is used where the fire hazard consists primarily of a flat surface or low level objects associated with horizontal surfaces. The RATE-BY VOLUME METHOD of system design is used where the fire hazard consists of three dimensional irregular objects that cannot easily be reduced to equivalent surface areas. 3-3.5 Rate-By-Area Method A. For rate-by-area local application systems, the quantity of CO2 required to protect a hazard is based on the summation of the listed discharge rates from all individual nozzles. The discharge rate for each nozzle is determined by the distance from the surface to be protected to the nozzle. The discharge rate and distance from the protected surface to nozzle determines the maximum area which a nozzle can protect. The flow rates, area of coverage and height limitations are found in tables 3-8, 3-9, 3-10. B. Overhead type nozzles shall be installed perpendicular to the hazard and centered over the area protected by the nozzle. They may also be installed at angles between 45 degrees and 90 degrees from the plane of the hazard surface as described in table 3-7. The height used in determining the necessary flow rate and area coverage shall be the distance from the aiming point on the protected surface to the nozzle measured along the axis of the nozzle. C. When installed at an angle, nozzles shall be aimed at a point measured from the near side of the area protected by the nozzle, the location of which is calculated 3-11 Tomco2 Fire Systems System Design 8/16/10 Rev. 0 by multiplying the fractional aiming factor in table 3-7 by the width of the area protected by the nozzle. D. If there is a physical limitation on the height of the nozzle above the protected surface, this height limitation may determine the number and type of nozzles that must be used. If there are no restrictions on nozzle height, the minimum number of nozzles may be used based on the maximum allowable distance. E. When coated stock or parts extend above a protected surface more than two feet additional nozzles may be required to protect this stock. When determining the location of nozzles, considerations should be given for the possible affects of air currents, winds and forced drafts, as additional nozzles may be required. 3-3.6 Rate-By-Volume Method A. If a hazard is three dimensional in nature and cannot be easily reduced to equivalent surface areas, rate-by-area protection is not recommended. For such three dimensional solid type hazards a rate-by-volume approach should be used when designing a local application system using the rate-by-volume method. B. The total discharge rate of the system shall be based on the volume of an assumed enclosure entirely surrounding the hazard. C. The assumed enclosure shall be based on an actual closed floor unless special provisions are made to take care of bottom conditions. D. The assumed walls and ceiling of this enclosure shall be at least 2 ft (0.6 m) from the main hazard unless actual walls are involved and shall enclose all areas of possible leakage, splashing or spillage. E. No deductions shall be made for solid objects within this volume. F. A minimum dimension of 4 ft (1.2 m) shall be used in calculating the volume of the assumed enclosure. G. If the hazard may be subjected to forced drafts, the assumed volume shall be increased to compensate for losses on the windward sides. H. Calculation of the system discharge rate and quantity of CO2 required is based on the volume of an assumed enclosure surrounding the hazard. The assumed enclosure is based on the presence of a closed floor under the hazard. The assumed enclosure is at least two feet in all directions from the actual hazard. The basic system discharge rate is then calculated using one lb. per min. per cubic foot of assumed volume. I. Location and Number of Nozzles. A sufficient number of nozzles shall be used to adequately cover the entire hazard volume on the basis of the system discharge rate as determined by the assumed volume. J. Nozzles shall be located and directed so as to retain the discharged carbon dioxide in the hazard volume by suitable cooperation between nozzles and objects in the hazard volume. 3-12 Tomco2 Fire Systems System Design 8/16/10 Rev. 0 K. Nozzles shall be located so as to compensate for any possible effects of air currents, or forced drafts. 3-3.7 Rate-By-Volume Partial Enclosure A. If the assumed enclosure has a closed floor and is partly defined by permanent continuous walls extending at least 2 ft. above the hazard (where the walls are not normally part of the hazard) the discharge rate may be proportionately reduced to not less than 0.25 lbs./min./cu. ft. (NFPA 12 2005 paragraph 6.5.3.2) B. Refer to figure 3-3 to determine the allowable flow rate reduction for a hazard with a partial enclosure. % PERIMETER ENCLOSED 100 RATE BY VOLUME MATHEMATICAL METHOD FACTOR = [% PERIMETER OPEN (EXPRESSED AS A DECIMAL) x .75] + .25 75 50 25 0 .4 .425 .45 .475 .25 .375 .50 .625 .75 LBS/MIN/CU FT Figure 3-3 Partial Enclosure Flow Rate Reduction per NFPA 12 Discharge Angle (1) 45-60 60-75 75-90 90 (Perpendicular) Note: Aiming Factor (2) 1/4 1/4-3/8 3/8-1/2 1/2 (Center) (1) Degrees from plane of hazard surface. (2) Fractional amount of nozzle coverage side-of-square. 3-13 .875 1.0 Tomco2 Fire Systems System Design 8/16/10 Rev. 0 Example: Note: Distance “X” and the flow rate are the same in both examples, only the aiming point for the nozzle changes. 3-14 Tomco2 Fire Systems Installation 8/16/10 Rev. 0 SECTION 4 INSTALLATION Table of Contents Paragraph 4-1 4-2 4-3 4-4 4-5 4-6 4-7 4-8 4-9 4-10 4-11 4-12 4-13 4-14 4-15 4-16 4-17 4-18 4-19 4-20 Subject General Pipe and Fittings Welding Connections Tubing Connections Pipe Hangars and Bracing Expansion Joints Cylinder Assemblies Installation of Cylinders Installation of Pipe and Fittings Installation of Nozzles Local Manual Control Remote Cable Manual Control Solenoid Actuator Discharge Pressure Switch Pressure Release Trip System Verification and Testing Inspection for Mechanical Integrity Pressure and Leak Test Pipe Sleeves Pneumatic Time Delay Tomco2 Fire Systems Installation 8/16/10 Rev. 0 SECTION 4 INSTALLATION 4-1 GENERAL This specification is to be used as a minimum standard for installation of piping, supports, hangers and system components. If the requirements of local, national codes or the authority having jurisdiction are more stringent, these more stringent requirements shall take precedence. Installation shall be performed in a workman like manner according to the highest standards. A. All pipe and fittings shall be new and of recent manufacture. B. All pipe shall be reamed after cutting so that all burrs and sharp edges are removed. C. All pipe shall be blown clean and swabbed thoroughly with solvent inside before installation to remove foreign matter and oil. Some effective solvents are trichlorethylene, perchlorethylene or trichlorethane. D. All pipe and fittings installed outdoors or in corrosive areas should be galvanized or coated with a proper rust inhibitor. E. All screwed pipe shall be coated with Teflon tape or an approved pipe joint compound. Coating of the threads must start at least two threads back from the pipe end. 4-2 PIPE AND FITTINGS The following provides specifications for materials normally used. This includes the use of other materials such as brass, copper, stainless steel, flexible hose, etc. provided that they satisfy the system pressure/temperature requirements (working pressure of 3,00 psi [207 bar]). Pipe and fittings should have a minimum bursting pressure (not working pressure) of 5,000 psi (345 bar). The project drawings will indicate the specific piping materials to be utilized for each project. As the type of piping material to be utilized are incorporated into the system flow/pressure loss design, the system designer must be contacted if materials other than those specified are used, and the designers approval must be received. Ferrous Pipe Seamless or electric weld, black or galvanized steel pipe conforming to ASTM A-53, Grades A or B, ASTM A-106, Grades A,B or C Sizes: 1/4" through 3/4" Schedule 40 (standard) 1” through 4” Schedule 80 (extra heavy) Furnace butt weld ASTM-53 pipe, cast iron pipe, and pipe conforming to ASTM A-120 must not be used. Black pipe may be used when installed indoors and where moisture or corrosive atmospheres are not normally present. Where any portion of a piping system is outdoors or in an unheated area, that portion should be galvanized. Where galvanized pipe is used, galvanized fittings should be used. 4-1 Tomco2 Fire Systems Installation 8/16/10 Rev. 0 Ferrous Fittings Threaded 1/4" through 2”: Class 300 malleable iron, ASTM A-197, or ductile iron, ASTM A-394 2 1/2" and Larger: 3,000# forged steel Class 150 and cast iron fittings must not be used. Pipe Connections Pipe can be assembled using threaded, flanged, or welded joints as specified on the project drawings. Threaded Connections All threaded joints should have American Standard pipe threads (NPT) in accordance with ANSI B2.1. All threads should be full length and suitably reamed and chamfered. After cutting and threading, pipe should be reamed and cleaned before assembly to remove all cutting oil, lacquer, scale and cuttings, using a degreasing solution run through the pipe interior. For assembly, use pip sealant applied to male thread only. Joints should be tightened until engagement conforms to that specified for tight joints using American Standard pipe threads. Normal engagements for tight joints are: Pipe Size 1/4" 3/8" 1/2" 3/4"" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 3 1/2" 4" 5" 6" 4-3 Engagement 3/8" 3/8" 1/2" 9/16" 11/16" 11/16" 11/16" 3/4" 15/16" 1" 1 1/16" 1 1/8" 1 1/4" 1 5/16" WELDED PIPE CONNECTIONS When making welded connections, bevel type welding fittings should be installed and all welding should be performed in accordance with Section IX, Qualification Standard for Welding and Brazing Procedures, Welders, Brazer Operators, of the ASME Boiler and Pressure Vessel Code. During welding care must be taken to ensure that weld splatter and molten metal does not enter the pipe and that any roughness that could affect flow is removed. 4-2 Tomco2 Fire Systems 4-4 Installation 8/16/10 Rev. 0 TUBE CONNETIONS When using tube, compression type fittings are preferred. The pressure/temperature ratings of the manufacturer of the fitting should not be exceeded. When tube joints are soldered or brazed the melting point of the soldering metal should be at least 10,000°F. 4-5 HANGARS AND BRACING All system piping, both vertical and horizontal, most be suitably supported with hangars conforming to the least requirements or ANSI B31.1. Pipe hangars should be capable of supporting the pipe under all conditions of operation and service. They should allow for the expansion and contraction of the piping, and should prevent pipe loads and stresses from being transmitted into connected equipment. Hangars and supports should be of rugged design and installed so that they will not be loosened by movement of the supported pipe. U-bolts with double nuts should be used. Pipes must be braced or anchored to the building structure such as beams, columns, concrete walls, etc., in order to prevent longitudinal and lateral movement and sway. Carbon dioxide piping must not be hung or supported form other piping systems (i.e. water, compressed air, etc.). Large forces are exerted on the system cylinders and piping during discharge. Each section of pipe must be braced or secured to restrict both the vertical and lateral movement. Where practical, riser piping should be supported independently of the connected horizontal piping. A support must be installed adjacent to each discharge nozzle and wherever a change in pipe direction occurs. In addition, for some regions classified as earthquake zones, or for projects such as nuclear sites subject to unique code requirements, special sway bracing and/or hangars may be required. Refer to project and/or contract drawings for requirements of special bracing. Generally, no section of pipe should be without a hanger or brace. Maximum spacing between hangars and hangar rod sizes should be indicated as shown, which are in accordance with ANSI B31.1.0. Hangar Spacing Pipe Size 1/2" 3/4"" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 3 1/2" 4" 5" 6" Engagement 5' 6' 7' 9' 9' 10' 11' 12' 13' 14' 16' 17' 4-3 Rod Size 3/8" 1/2" 5/8" 3/4" Tomco2 Fire Systems Installation 8/16/10 Rev. 0 Intermediate Pipe Hanger (Trapeze) Pipe Size Rod Size 1" and smaller 3/8" 1-1/4" thru 3" 1/2" 4"& 5" 5/8" 6" 3/4" Rigid Pipe Hanger (Roof and Floor) Pipe Size 1" thru 2" 2-1/2" thru 4" 5" & 6" "A" 8" 12" 16" Angle Size 1-1/2" x 1-1/2" x 1/4" 3" x 3" x 1/4" 3-1/2" x 3-1/2" x 3/8" Figure 4-13 Typical Pipe Supports 4-4 U-Bolt Dia. 3/8" 1/2" 5/8" Tomco2 Fire Systems Installation 8/16/10 Rev. 0 Intermediate Pipe Hanger (Roof) Letter A B C D E F Angle Size U-Bolt Dia. Anchor Size 1" - 2" Pipe 6" 10" 1-1/2" 3" 1-3/4" 13-1/4" 1-1/2" x 1-1/2" x 1/4" 3/8" 3/8" 2-1/2" - 4" Pipe 8" 14" 1-1/2" 5" 1-3/4" 19-1/2" 3" x 3" x 1/4" 1/2" 1/2" Figure 4-14 Typical Pipe Supports 4-5 5" - 6" Pipe 10" 18" 1-1/2" 7" 1-3/4" 24-3/4" 3-1/2" x 3-1/2" x 3/8" 5/8" 5/8" Tomco2 Fire Systems Installation 8/16/10 Rev. 0 Rigid Pipe Hanger (Wall) Letter A B C D E F G Angle Size U-Bolt Dia. Anchor Size 1/2" - 3/4" Pipe 6" 1-1/2" 3" 10" 1-1/2" 7" 8-1/4" 1" x 1" x 3/16" 1/4" 1/4" 1" - 1-1/2" Pipe 9" 3" 4" 14" 2" 10" 12-3/4" 2" x 2" x 1/4" 3/8" 3/8" Figure 4-15 Typical Pipe Supports 4-6 1-1/2" - 2" Pipe 12" 4" 5" 18" 2-1/2" 13" 17" 3" x 3" x 3/8" 3/8" 1/2" Tomco2 Fire Systems Installation 8/16/10 Rev. 0 Rigid Pipe Hanger (Wall) Letter A B C D E F Angle Size U-Bolt Dia. Anchor Size 1" - 2" Pipe 8" 12" 2" 7" 5" 9-1/4" 1-1/2" x 1-1/2" x 1/4" 3/8" 3/8" 2-1/2" - 4" Pipe 12" 18" 2" 13" 8" 12-3/8" 3" x 3" x 1/4" 1/2" 1/2" Figure 4-16 Typical Pipe Supports 4-7 5" - 6" Pipe 16" 20" 2" 15" 11" 17-1/2" 3-1/2" x 3-1/2" x 3/8" 5/8" 5/8" Tomco2 Fire Systems Installation 8/16/10 Rev. 0 Tank Capacity (tons) Voltage Horsepower Phase Amps Fuse Wire 0.75 1.5 2 230 230 208/230 0.5 0.5 0.5 1 1 1 5.2 5.2 5.2 10 10 10 #12 #12 #12 3.75 208/230 1 1 9.8 15 #12 460 1 3 4.2 6 #12 208/230 1 1 9.8 15 #12 230 1 3 7.2 10 #12 460 1 3 4.2 5 #12 230 2 3 10.2 15 #12 460 2 3 6.2 10 #12 230 2 3 10.2 15 #12 460 2 3 6.2 10 #12 230 2 3 10.2 15 #12 460 2 3 6.2 10 #12 230 2 3 10.2 15 #12 460 2 3 6.2 10 #12 230 3 3 25.4 30 #10 460 3 3 12.5 15 #12 230 3 3 25.4 30 #10 460 3 3 12.5 15 #12 230 3 3 25.4 30 #10 460 3 3 12.5 15 #12 230 3 3 25.4 30 #10 460 3 3 12.5 15 #12 6 8 10 12 14 18 22 26 30 Consult factory for information regarding tank sizes larger than 30 tons. 4-6 EXPANSION JOINTS A certain amount of contraction can occur, which is caused by a maximum temperature change in long continuous pipe runs. Approximately 1 inch per 100 feet of steel pipe. Often, as part of the natural layout of the system, a swing joint can serve to give the desired flexibility. In straight runs an expansion joint should be installed on the basis of one after approximately 100 feet of continuous run and after each 100 feet run thereafter. 4-8 Tomco2 Fire Systems Installation 8/16/10 Rev. 0 SUPPORTS PERMITTING LONGITUDINAL MOVEMENT (TYP 2) ANCHOR 'H' 'W' PLAN VIEW Note: PIPE SIZE 1/2" 1/2" 1/2" 3/4" 3/4" 3/4" 3/4" 1" 1" 1" 1" 1 1/4" 1 1/4" 1 1/4" 1 1/4" 1 1/2" 1 1/2" 1 1/2" 1 1/2" 2" 2" 2" 2" Rigid hangers should be installed at all three (3) points noted above. However, the tension on the ‘U’ bolts supporting the pipe to the hanger must be adjusted to allow longitudinal movement on either side of the loop. DIM H 1'-0" 2'-0" 3'-0" 1'-0" 2'-0" 3'-0" 4'-0" 1'-0" 2'-0" 3-0" 4'-0" 1'-0" 2'-0" 3'-0" 4'-0" 1'-0" 2'-0" 3'-0" 4'-0" 1'-0" 2'-0" 3'-0" 4'-0" DIM W 5'-6" 1'-6" 0'-6" 8'-6" 3'-0" 1'-0" 0'-6" 10'-0" 3'-6" 1'-0" 0'-6" 12'-0" 5'-0" 1'-0" 0'-6" 13'-6" 6'-0" 2'-0" 0'-6" 15'-6" 7'-6" 2'-6" 0'-6" PIPE SIZE 3" 3" 3" 3" 3" 4" 4" 4" 4" 4" 5" 5" 5" 5" 6" 6" 6" 6" 8" 8" 8" 8" Figure 4-10 Estimating Guide for Expansion Loops 4-9 DIM H 1'-0" 2'-0" 3'-0" 4'-0" 5'-0" 1'-0" 2'-0" 3'-0" 4'-0" 5'-0" 2'-0" 3'-0" 4'-0" 5'-0" 2'-0" 3'-0" 4'-0" 5'-0" 2'-0" 3'-0" 4'-0" 5'-0" DIM W 20'-0" 10'-0" 5'-0" 1'-0" 0'-6" 21'-6" 11'-6" 5'-0" 2'-0" 0'-9" 13'-6" 6'-6" 2'-3" 0'-9" 14'-0" 7'-6" 2'-6" 1'-0" 14'-0" 9'-6" 3'-6" 1'-6" Tomco2 Fire Systems 4-7 Installation 8/16/10 Rev. 0 CYLINDER ASSEMBLIES Each cylinder assembly has safety features and components to ensure against accidental discharge during installation. Prior to starting work, the installer should become familiar with these features by reviewing the equipment, the appropriate data sheets, and the installation instructions. Carbon dioxide cylinders may be located inside or outside the protected space, although it is preferable to locate them outside the space. When they are installed within the space they protect, a remote manual control must be installed to ensure the system can be actuated from a safe location outside the fire area. All cylinder valves are supplied with transport plugs screwed into the discharge ports. These plugs have a small hole drilled at right angles to the axis of the discharge port, so that if accidental discharge dose occur, it will be diffused in a safe manner. In addition, the SW-50M valves have plugs to shield the vent valve and solenoid actuator ports. These plugs must be in position whenever the cylinder assemblies are not secured and/or disconnected from the discharge piping. (The SW-50M valve is initiated by depressing the pilot valve stem in either of these ports.) Actuators must only be assembled to the cylinder valve after the cylinders are secured in their brackets and connected to the discharge piping, which must be complete with nozzles, using the correct discharge bend assemblies. The cylinders should be located to provide convenient access so that they can be readily inspected and also easily removed after use for recharging. Do not install the cylinder where they will be exposed to the weather elements or the direct rays of the sun. Do not install the cylinders where temperatures of less than 0°F (-18°C) or higher than 130°F (54°C), unless otherwise specified on the project drawings. If cylinders are located in hazardous (explosion-proof) area, ensure that the cylinder solenoid control and all other components are approved for such use, and the installation of all materials is made in an approved manner. Cylinders are to be installed in normal upright position. All cylinders are provided with siphon tube. 4-8 INSTALLATION OF CYLINDERS 1. Fasten cylinder bracketing and manifold brackets securely onto a solid wall of floor or structural member using 1/2” bolts with suitable anchors. Bolts must not be anchored into plaster materials. Cylinder brackets must be absolutely secure to withstand the discharge thrust forces. Be sure that threaded rods are inserted in channel before channel is permanently mounted. 2. Fasten cylinder securely in bracketing. 3. All large carbon dioxide system cylinders are shipped with valve protection caps. Remove protection cap from the cylinder and coat it with a light film of grease. Protection caps should be stored close to cylinders, where they will be readily available for re-installation when cylinders are disconnected from the system and/or transported for recharging. 4. With cylinders properly mounted, attach flexible discharge bends to cylinder valves, hand tighten only. 5. Mount the header manifold using the discharge bends so that the least possible strain is put on the connections. 6. Disconnect the flexible bend from the cylinder valve and screw, wrench tight into manifold. 4-10 Tomco2 Fire Systems 4-9 Installation 8/16/10 Rev. 0 INSTALLATION OF PIPE AND FITTINGS Generally, drawings provided schematic piping layouts showing pipe diameter, pipe fittings, and pipe lengths utilized for the design calculations. The information shown is not to be used for fabrication of pipe. The installer must verify that the pipe can be installed as indicated, and establish fabrication data based upon his inspection of the site. Changes to piping that may be necessary to suit conditions can critically affect the system flow balance. Any deviations to the piping must be approved by the designer prior to their implementation. Where reducing fittings are called for on the installation drawings, hexagon bushings of 3,000 lb. forged steel may be used. Malleable iron hexagon reducing bushings may also be used, up to 2-inch size, provided ones with the correct pressure/temperature ratings are used. Under no conditions should flush bushings or cast iron bushings be used. If two reducing fittings are required to make the necessary reduction, they should be chosen to split the reduction equally. Pipe should be reamed and cleaned before assembly, and after assembly the entire piping system should be blown out before nozzles and other devices are installed. All valves (stop and selector) not flange, should be installed with a flange joint or union immediately downstream of the valve to facilitate inspection, repair, or replacement. All pressure relief devices should be located and orientated so that the discharge od carbon dioxide will not injure personnel, damage equipment, or be otherwise objectionable. A dirt trap and blow-out, consisting of a tee with capped nipple 3 to 6 inches (76 to 152 mm) long, should be installed at the end of each pipe run. Piping through walls, floors, etc. should be run through sleeves of Schedule 40 pipe at least two sizes larger than the pipe being run and not smaller than 1 inch. Sleeves through floor slabs should extended at least 2 inches above the floor. Sleeves should be packed with fire resistant material so as to be dust and weather tight, as specified on project drawings. 4-10 INSTALLATION OF NOZZLES 1. For total flooding applications, nozzles should be located at the highest practical elevation within the enclosure. Except where more than one tier of nozzles is used, or special application conditions apply, the bottom of the orifice should not be more than 12 inches (305 mm) from the top of the enclosure. For local applications, nozzles must be located as shown on the project drawings. 2. There must not be any obstructions adjacent to the nozzles (structural columns or beams, ducts, cable trays, racks, equipment, etc.) that will affect the discharge patterns or disbursement of the carbon dioxide. 3. Install nozzle piping at the hazard, as shown on the project drawings. Be sure to fasten piping securely at each nozzle and change in direction of flow. 4-11 LOCAL MANUAL CONTROL The local manual controls should not be installed on the cylinder assemblies until the cylinders have been secured into the cylinder bracket, all piping has been completed, and nozzles installed. 4-11 Tomco2 Fire Systems Installation 8/16/10 Rev. 0 1. Remove the shipping plug from the vent valve port on top of the SW-50M cylinder valve. 2. Ensure that the piston in the actuator is in the retracted position, and that the hand lever is secured with lock-pin and sealed. Then install the actuator into the vent valve port of the cylinder valve, wrench tight. (During servicing, if piston does not retract, the pressure on top of the piston must be relieved. Loosen then re-tighten the tube connector.) If any hissing or discharge of gas is noticed during connection of the actuator, stop at once and remove the actuator for cylinder valve. Check the actuator. If no cause for discharge is found contact Tomco Fire Systems. 3. To orientate the manual lever, unscrew the locking nut 1/4 turn, rotate main body of the actuator to the position required, then re-tighten locking nut. IMPORTANT: Do not unscrew the locking nut more than 1/4 turn. 4. If the system has two master cylinders, the actuators of the two units should be joined together with a connecting link to enable simultaneous actuation. a) Loosen cylinders with the bracket sufficient to allow the cylinders to be rotated. b) Attach the actuators to the cylinder valves. c) Unscrew the locking nut of each actuator 1/4" turn, sufficient for the hand levers to be rotated. d) Connect the hand levers of the two actuators together using a connecting link. Attach the link to the hole at the end of each lever. Rotate the cylinders and hand levers as necessary to assure a straight line movement. Do not remove the safety lock pin from its lever during this operation, otherwise accidental discharge of cylinders might occur. e) Tighten the locking nuts of the actuators and tighten the cylinder brackets. 5. If the manual/pressure actuator is to be used with a solenoid actuator, remove the blank plug from the pressure port and install the 1/8” Swagelock elbow, which is supplied with solenoid actuator. 4-12 REMOTE CABLE MANUAL CONTROL 1. Install the pull box in a readily accessible location, at a safe distance from the fire area, and preferably in the main path of egress from the area. The pull box should be 3 to 5 feet (920 to 1520 mm) above floor level. 2. Run 1/2" conduit or 3/8” standard weight galvanized steel pipe from the pull box to the location of the actuator hand lever, and terminate with a flared-end fitting. Corner pulleys must be installed at each change of direction of the conduit or pipe, bends or offsets will not be accepted. The conduit or pipe must be securely fastened with pipe straps, especially at each corner pulley. 4-12 Tomco2 Fire Systems 3. Installation 8/16/10 Rev. 0 Thread the cable through the handle in the pulley box until the end fitting (nipple) is engaged. 4. Thread the cable through the conduit and around the pulleys to the cylinder. Remove the cover from each corner pulley in order to thread the cable around the wheel. Ensure covers are replaced wrench tight. NOTE: Check to ensure the pulley wheels are correctly mounted in the housings and rotate freely. 5. Pull on end of cable (at cylinder end) to take up the slack. Be sure the pull handle is properly installed in the pull box and that end fitting fits into the hole in the pull handle. 6. Feed the cable through the hole in end of the hand lever or connecting link, and fasten with a cable clamp. The cable should be taught but not tight. When installed, be sure that there is at least 9 inches (230 mm) of free cable between the cable clamp and the flared-end fitting for proper operation of the lever(s). 7. On completion of the installation, install a seal wire on the pull box and remove the lock pin(s) from the actuator lever(s). The system is now ready for use. 4-13 SOLENOID ACTUATOR Check the solenoid nameplate to ensure that the coil voltage agrees with the supply voltage of the system and the site conditions. Caution: The solenoid actuator should not be connected to cylinder until after completion of all testing. 1. Provide a junction box located close to the cylinder valve for connection to the electric actuating circuit. 2. On completion of all testing, connect the solenoid actuator to the adaptor at the top of the SW-50M cylinder valve, after first confirming that there is no electric power being applied to the solenoid, and that all o-rings are in place. A slight discharge (puff) of carbon dioxide might occur as this connection is made. This connection should be made as follows: a) secure the mounting bracket square to the valve b) connect the solenoid valve to the bracket with the screws supplied c) attach the solenoid to the pressure connection of the cylinder valve wrench tight d) tighten the screws holding the solenoid to the bracket. 4-13 Tomco2 Fire Systems Installation 8/16/10 Rev. 0 3. Install the 3/16” hose to connect the solenoid valve exhaust port to the manual actuator. 4-14 DISCHARGE PRESSURE SWITCH The pressure operated switch is normally located adjacent to the cylinder(s) and is connected to the manifold or discharge piping from the cylinders. 1. Mount the switch box securely onto a wall or structural member using the mounting holes provided. Preferred mounting is upright with pipe and conduit connections to bottom. 2. Connect 1/2" conduit and appropriate wiring to the electrical connection on the switch box. To reverse the normal switch contact arrangement, remove the toggle switch assembly and reverse it in the switch box. 3. To switch loads heavier than the switch rating, or requiring more than two contacts, the switch should be used to operate a relay or contractor to control the load. 4. Connect the 1/4" NPT connection at the bottom of the front plate to the carbon dioxide piping using 1/4" steel pipe or 1/4" or 3/16” O.D. copper tube. Install a union fitting at base of cover to allow removal of front plate for testing. 4-15 PRESSURE RELEASE TRIP The pressure release trip is used to release loads of up to a maximum of 75 lbs (34 kg), which are hung on the piston stem. 1. Mount the pressure release trip onto a solid structural member using 5/16” bolts and appropriate anchors. Fixing must be suitable for the loading, including spring tension and/or dead weight of operated equipment. 2. Connect the release trip’s 1/4" NPT connection to the carbon dioxide discharge ” piping using 1/4" steel pipe or 1/4" or 3/16 O.D. copper tube. 1 3. Using /16-inch stainless steel cable and cable clamp (or equivalent), connect the equipment to be operated to the piston stem. The cable must be suspended at right angles to the piston stem in order to neither bind nor slide off the stem. 4-16 SYSTEM VERIFICATION AND TESTING Prior to placing the completed system in service, the installation should be inspected and tested to confirm: 1. Conformance to system design. 2. Suitability of piping, its correctness to project design, and its support and bracketing. 3. Conformance to the required system operating sequence. 4-14 Tomco2 Fire Systems Installation 8/16/10 Rev. 0 4. The suitability of the hazard environmental control, safety precautions, sealing, etc. 5. Compliance with the requirements of NFPA 12: Standard on Carbon Dioxide Extinguishing Systems and/or other applicable standard. If there is any doubt of the ability of the system to operate and provide the necessary protection, a full discharge test should be considered. A discharge test will verify the total system operation, check the agent concentration achieved, determine the duration (soaking time) that the concentration is retained, check acceptability of nozzle discharge, check audibility and/or visibility of alarms, ensure interlocks and all auxiliary equipment operate as required, and allow personnel to become completely familiar with the discharging system and to practice response. If a full discharge test is not performed, a puff test, using a minimum of one cylinder, must be conducted. A full discharge test must be conducted for all Extended Discharge type systems. 4-16.1 DESIGN Measure the room and calculate the actual room volume. Check actual volume against design volume (volume shown on project drawings) and ensure correct quantity of carbon dioxide is provided. 4-16.2 PIPING Check the pipe layout to ensure it agrees with the system layout drawings. Inspect the piping supports and ensure that the pipe is secure and restrained so that unacceptable movement will not occur. After the installation of the system piping is completed, and prior to the connection of the cylinders, nozzles and other equipment, the discharge piping should be blown out and then pressure tested for leakage. Plug or cap all piping outlets and apply 100 psi (7 bar) pressure with dry nitrogen or dry air for 10 minutes. At the end of 10 minutes, the pressure loss should not be greater than 5 psi (0.35 bar). When pressurizing piping, the pressure should be increased in 50 psi (3.5 bar) increments. Caution: Pneumatic pressure testing creates a potential risk of injury to personnel in the area as a result of airborne projectiles if piping should rupture. Prior to conducting the pneumatic pressure test, the protected area must be evacuated and appropriate safeguards must be provided for test personnel and for equipment in the area. 4-16.3 CYLINDERS 1. Inspect cylinders and ensure bracketing and cylinders are secure. 4-15 Tomco2 Fire Systems Installation 8/16/10 Rev. 0 2. Verify the weight of carbon dioxide in all cylinders, using either an accurate weigh scale or an approved liquid level gauge. The contents should be within +/-10% of the normal capacity. 3. Check cylinder discharge bends and check valves for proper connection and tightness. 4. Ensure that appropriate identification, operating and warning signs are mounted or posted. 4-16.4 NOZZLES Each nozzle has an orifice drilled to suit the specific location and discharge flow requirements. The orifice identification number is stamped on each nozzle. 1. Verify that orifice sizes are as indicated on the project drawings and that the nozzles are orientated to discharge correctly. Caution: Ensure discharge will not splash flammable liquids or create dust clouds that could extend the fire. Also, ensure the discharging agent will not injure personnel in the area. 2. Ensure that each nozzle pipe drop is bracketed or braced against the nozzle discharge thrust, and that the nozzle cannot swivel on its pipe fitting. 3. Check the cleanliness of the protected area to determine if protective caps or seals are required to prevent orifices from clogging. 4-16.5 MANUAL CONTROL: LOCAL AND REMOTE CABLE TYPE Ensure the manual actuators and the remote manual controls, for all parts of the system – master cylinders for main and reserve systems, all master cylinders in a joint system, and selector and stop valves – are accurately identified and will be accessible during a fire. All testing should be carried out with the manual actuator(s) disconnected from the cylinders, and other devices. 1. With the manual actuator disconnected from the cylinder or other device, pull the lock pin and operate the lever to verify the movement of the operating piston 1/8” (3.2 mm). 2. If a cable type remote control is used, pull the handle in the pull box and check the pull, force and length of pull required. Also ensure that there is at least 9 inches (229 mm) of clear movement at the actuator lever. 4-16 Tomco2 Fire Systems Installation 8/16/10 Rev. 0 Note: Manual controls should not require a pull of more than 40 lbs (178 Newtons), nor a movement of more than 14 inches (356 mm) for system operation. 3. Check to ensure that the cable runs free and that there is no binding of cable in the corner pulleys and conduit, and that the corner pulleys and conduit are securely fixed. 4. Reset the pull box and affix a lead and wire, or similar, seal. Ensure a lock pin is installed in the manual actuator and that the stem is retracted before reconnecting the actuator to the cylinder valve or other device. (This will prevent operation of the cylinder while actuator is being installed.) If a remote manual control is not used, secure the lock pin in the actuator with a lead and wire seal. If a remote manual control is used, the actuator lock-pin must be removed after installation before system is placed in service. 4-16.6 ELETRIC ACTUATOR Perform all inspections and tests on the control panel, detectors, signals and other devices as specifically indicated in the specific equipment manufacturer’s manuals. Note: The solenoid actuator and the manual actuator must be removed from the cylinder valve before any testing is performed. 1. Ensure the solenoid actuator is of the correct voltage for the service. 2. Connect the 3/16” hose (supplied) to the respective solenoid valve and manual actuator. Apply dry nitrogen pressure of 100 psi (7 bar) or dry, clean air pressure to the inlet port of the solenoid valve (cylinder connection port). 3. Apply the appropriate voltage to the solenoid by actuating a manual station or firing a detector to operate the discharge circuit. Note: Do not operate fixed thermal detectors unless they are of the restorable type. The solenoid should operate, which will be indicated by the movement of the piston stem in the manual actuator. Also there will be an escape of nitrogen from the small vent hole in the side of the manual actuator. 4. Remove electric power from the solenoid. The solenoid valve should close, indicated by the cessation of nitrogen discharge, and the return of the piston stem in the manual actuator to its normal standby position. Check for leakage at the vent hole. 5. Shut off the pressure supply, and exhaust the line pressure using the exhaust valve which should be part of the pressurizing equipment. 6. After all testing has been completed satisfactorily, remove the 3/16” hose, re-install all actuators to the cylinder valves, and ensure all electrical connections, including ground connections, are in order. Replace the 3/16” hose, taking care to ensure the pressure connections are gas tight. 4-17 Tomco2 Fire Systems Installation 8/16/10 Rev. 0 4-16.7 OPTIONAL DEVICES 1. Gas Operated Sirens. Disconnect the siren from the discharge piping and connect to a small carbon dioxide cylinder. Operate the carbon dioxide cylinder and ensure all sirens operate and that the sound is readily heard throughout the protected space. This should be done under normal background noise conditions. 2. Pressure Operated Switches. To test the circuits and to ensure auxiliary functions operate correctly, either: a) Disconnect the union at the pressure connection b) Insert a small rod into the pressure connection of the cover plate and push against the piston to trip the switch. c) Push plunger down to reset switch. OR... d) Remove the four cover screws and swing cover away from switch box. Manually operate interior toggle switch. After testing, ensure toggle is returned to normal stand-by position, then reinstall cover plate. 3. Pressure Release Trip. With a screw driver or other blunt instrument manually push the stem to the retracted position. Allow the cable to fall, and ensure the connected equipment operates as required. 4-16.8 CARBON DIOXIDE PUFF TEST The purpose of this test is to check the integrity of the piping system and to ensure the pipes are not blocked. It will not check the concentration of carbon dioxide that will be obtained under a full discharge conditions, or check the integrity (tightness) of the enclosure. 1. Disconnect all cylinders, except one master cylinder from the system. 2. Operate the remaining master cylinder and ensure carbon dioxide does discharge from all nozzles. 3. Ensure that there is no undue pipe movement. 4. Ensure all pressure-operated devices operate and that the connected equipment, alarms and other functions are controlled as required. 4-16.9 CARBON DIOXIDE DISCHARGE TEST A full discharge test should be performed when there are doubts about the operation of the system, when any inspection indicates their advisability, and for all extended 4-18 Tomco2 Fire Systems Installation 8/16/10 Rev. 0 discharge type systems. It is recommended that a full discharge test be performed whenever cylinders are removed for hydrostatic testing. During this test : 1. Make checks as indicated under the Puff Test. 2. With a concentration meter, check the carbon dioxide concentrations achieved at several locations within the enclosure, and specifically adjacent to the primary hazard within the enclosure. 3. Check the discharge time. 4. Check the holding time, the length of time the carbon dioxide concentration is maintained. 5. Ensure that the enclosure is reasonably well sealed, and that there is no major leakage. 6. Ensure all alarms function for the required period of time and that they can be heard and/or seen throughout the area. This should be done under normal area operating conditions, i.e. normal background noise and lighting, etc. 4-19 Tomco2 Fire Systems Operation And Service 8/16/10 Rev. 0 SECTION 5 OPERATION AND SERVICE Table of Contents Paragraph 5-1 5-2 5-3 5-4 5-5 5-6 Subject General System Activation Recharging System Maintenance Cylinder Recharge Manual CO2 Pressure/ Temperature Curve Tomco2 Fire Systems Operation and Service 8/16/10 Rev. 0 SECTION 5 OPERATION AND SERVICE 5-1 GENERAL A. Operation and service procedures in this section are provided as a guide for identifying and correcting systems faults. The use of these procedures by competent personnel will reduce system down time and minimize unnecessary costs. Troubleshooting tables are provided for identifying and isolating system/component faults. B. The CO2 system shall be maintained in full operating condition at all times. Use, impairment and restoration of this protection shall be promptly reported to the authority having jurisdiction. 5-1.1 Inspection and Testing All carbon dioxide systems shall be thoroughly inspected and tested for proper operation by competent personnel. 5-2 SYSTEM ACTIVATION 1. Notify your local fire department. 2. Do not open doors or windows, or remove the carbon dioxide from the protected area until the fire is completely out. 3. Do not enter the area until the carbon dioxide has been removed and the area ventilated. If it is necessary to enter the area while it still contains carbon dioxide, selfcontained breathing apparatus should be used. In general, providing the system discharges during the early stages of the fire, and providing all plant shut-down functions are operated and safety precautions are taken, the fire should be extinguished within one minute of the end of carbon dioxide discharge. However, the area should be kept closed for at least fifteen minutes following discharge to allow the area to cool, and to prevent re-ignition. For deep-seated hazards, the space should be kept tightly closed for at least sixty minutes following discharge. To check if fire is out: 1. Look for smoke and steam coming from cracks around doors, windows, vents, etc. 2. Feel the doors and walls. If they are hot do not open doors, the fire is still burning or is in the cooling stage. 3. Listen for crackling sounds. Have your fire department check the space for you. 5-1 Tomco2 Fire Systems Operation and Service 8/16/10 Rev. 0 Do not enter area with a lighted cigarette or open flame as flammable vapors may be present which could cause re-ignition or an explosion. After opening the door: 1. Completely ventilate the space. CO2 is heavier than air and will drift into low level spaces (e.g. rooms below grade). Use fans to remove CO2, smoke and fumes from low areas. 2. Clean-up residue from fire. 3. Determine cause of fire and take corrective action. 5-3 RECHARGING THE SYSTEM Have the system completely serviced by an Tomco Fire Systems approved service agency. After operation, the system should be recharged without delay in order to maintain protection. 1. Remove, inspect and recharge all cylinders. 2. Inspect the piping system and ensure pipe supports are still secure. 3. Inspect all components, including nozzles, switches, detectors, alarms, etc. Replace all equipment that has been damaged, or that has been exposed to direct flame or excessive heat from the fire. 4. Reinstall system in accordance with the Installation Instructions. 5. Verify and test system in accordance with this manual and Section 4.8 of NFPA 12. 6. Check the hydrostatic test date on cylinders and flex hose. If more than 5 years have elapsed from the date of last test, the cylinders will require hydrostatic testing. 5-4 SYSTEM MAINTENANCE In order to ensure that the system has not been tampered with and is in a fully operational condition, it must be inspected and tested on a regular basis by trained, competent, service personnel. In accordance with NFPA 12: Standard on Carbon Dioxide Extinguishing Systems, insurance and other code requirements, all carbon dioxide systems should be thoroughly inspected and tested annually. It is recommended that a service and maintenance contract be established with a Tomco Fire Systems approved service agency. All persons who may be expected to inspect, test, maintain, or operate carbon dioxide fire suppression systems should be thoroughly trained, and be kept thoroughly trained, in the functions they are expected to perform. 5-2 Tomco2 Fire Systems Operation and Service 8/16/10 Rev. 0 5-4.1 Monthly Inspections 1. Check system components for mechanical damage and tampering. All system lead and wire seals, or similar, should be intact. 2. Ensure that there are no obstructions that would prevent system operation, or prevent proper distribution of carbon dioxide from discharge nozzles. 3. Verify that egress is clear to allow safe evacuation of personnel from the hazard area, and safe access to the manual controls. 2. Check that all electrical circuits show normal. If a control panel is utilized, power lamp is on and all other lamps are off. 5-4.2 Semi Annual Inspections 1. Perform all the monthly inspections. 2. Check if there have been any changes in the shape, size, contents or use of the protected space. Any changes will necessitate a review of the system design. 3. Check the cylinder contents (weight), this may be done by using a platform or beam scale or an approved liquid level gauge. Record weight on the cylinder tag or in the log book. If the cylinder has a loss in net weight of more than 10 percent, it should be recharged or replaced. The cylinder full weight is indicated on the valve. Check the date of the last hydrostatic test. If more than 12 years have elapsed since the last test, the cylinders should be discharged and retested before being returned to service. (It is recommended that a full discharge test be performed when cylinders are emptied for hydrostatic testing.) 4. Examine cylinders, piping and nozzles for any evidence of corrosion or other physical damage. 5. Check cylinder bracketing, piping, pipe hangers and straps to ensure all are secure and suitably supported. This is particularly important where shock and vibration are encountered as a normal part of the environment (e.g. on board ships, etc.). 6. Ensure discharge nozzles are still located as originally installed, that the nozzle discharge orifices are clear and unobstructed, and that the nozzles are properly positioned and aligned. Ensure seals are used where necessary. 7. Remove the manual actuators from all cylinders that they operate and operate the hand lever. The actuator should operate freely and the operating stem should travel 1/8inch (3.2 mm). 5-3 Tomco2 Fire Systems Operation and Service 8/16/10 Rev. 0 Caution: When two actuators are connected together, both actuators must be removed from the equipment they control, before testing. 8. If a remote manual cable control is used, ensure the actuators are removed from the equipment they control, and operate all cable controls by the pulling cable at the pull box to ensure freedom of movement and travel. Both main and reserve actuator cables should be operated, if used. Check the condition of conduit and corner pulleys. 9. Inspect and clean all fire detectors. Check the sensitivity and adjust smoke detectors. 10. If the system is automatically electrically actuated, disconnect the solenoid actuators and manual actuators from the cylinder valves, then: a) Operate all electric Initiating devices (detectors, manual stations, etc.), one at a time, and ensure the respective actuators operate. There will be a click sound when the solenoid operates. This check should be made for both main and reserve banks of cylinders, if used. Reinstall the solenoid and manual actuators after all testing is completed. Alternatively, unplug the cable connectors from all solenoid valves and insert light bulbs In the cable connectors. The bulbs will light when each circuit is energized. Also, the operating stem of the manual actuator should travel down 1/8-inch (3.2 mm). b) Verify that all electric alarm signals function, and that all audible devices can be heard and all Illuminated devices can be seen throughout the protected space. This should be done in the normal working environment with normal background noises and lighting in place. c) If the system has an extinguishment control panel, refer to the panel manufacturer’s instruction manual for maintenance procedures. 11. Confirm operation of all auxiliary and supplementary components such as time delays, pressure operated switches, release trips, damper releases, shut-off valves, etc. by manual operation, where possible. Pressure operated time delays and gas operated sirens should be checked using a carbon dioxide portable extinguisher as a pressurizing source. Ensure all equipment is reset and all components are installed and left in the normal Standby condition on completion of testing. 5-4