BECSys7 Installation and Technical Manual

advertisement
Installation and Technical Manual
Rev: B09
Installation and Technical
Manual
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Rev: B09
TABLE OF CONTENTS
Unpacking........................................................................... 1
B – 12.5: Vacuum Transducer.................................. 13
General Guidelines ............................................................. 1
B – 12.6: Murphy Swichgages ................................. 13
Firmware Version ............................................................... 1
B – 12.6.1: A20P Pressure Gauge: ....................... 13
Environmental Conditions .................................................. 2
B – 12.6.2: A20DP Differential Pressure Gauge:. 13
Electrical Specifications...................................................... 2
B – 12.6.3: A20V Vacuum Gauge:.......................13
Warnings............................................................................. 3
B – 12.7: Proximity Switches...................................14
Section A: Mounting the BECSys5 Controller .................. 4
B – 13: 4-20mA Outputs .............................................. 14
A – 1: Mounting the Controller...................................... 4
B – 14: BECSysRPM (Remote Probe Module)............14
A – 2: Wrapping the Fittings.......................................... 4
B – 14.1: Wiring the BECSysRPM ...........................14
A – 3: Assembling the Flow cell.................................... 4
B – 14.2: Wiring to the BECSys5 .............................15
A – 4: Plumbing the Sample Stream .............................. 4
B – 15: BECSys Ethernet Card Cable ...........................15
A – 5: Free Chlorine Sensor Flow Cell.......................... 4
B – 16: Re-installing the safety shield.......................... 15
A – 6: Sensor preparations ............................................. 5
B – 17: Fuses ................................................................ 15
A – 6.1: ORP and pH Sensor ..................................... 5 Section C: Programming the Controller ...........................16
A – 6.2: Free Chlorine Sensor.................................... 5
C – 1: Adjusting the Display Contrast.......................... 16
A – 7: Opening the Sample Stream Valve ..................... 5
C – 2: Security Settings ................................................16
A – 8: Plugging in the Sensors....................................... 5
C – 2.1: Access Codes and levels ............................. 16
Section B: Wiring the BECSys5 Controller....................... 6
C – 2.2: Setting Access Codes..................................16
B – 1: Opening The Cover ............................................. 6
C – 2.3: Recovering Lost Access Codes...................17
B – 2: Removing the safety shield ................................. 6
C – 2.4: Setting Permissions.....................................17
B – 3: Supplied Cords .................................................... 6
C – 3: Navigating the menus ........................................17
B – 4: Conduit Connect.................................................. 7
C – 3.1: Common status messages ...........................17
B – 5: Wiring the Relays................................................ 7
C – 3.2: The Menu Screens ......................................17
B – 5.1: Externally Powered Wiring .......................... 7
C – 3.2.1: Entry Screens ....................................... 18
B – 5.2: Relay 1 ......................................................... 7
C – 3.2.2: List Screens..........................................18
B – 5.2.1: Line Powered Wiring ............................ 7
C – 3.3: The Lock Screen Key .................................18
B – 5.2.2: Externally Powered ............................... 8
C – 4: Fixed Inputs .......................................................19
B – 5.3: Relay 2 ......................................................... 8
C – 4.1: pH Setup .....................................................19
B – 5.3.1: Line Powered Wiring ............................ 8
C – 4.2: ORP Setup ..................................................19
B – 5.3.2: Externally Powered ............................... 8
C – 4.3: ppm Setup ...................................................20
B – 5.4: Relay 3 ......................................................... 8
C – 4.3.1: Input Source: Calculated.......................20
B – 5.4.1: Line Powered Wiring ............................ 8
C – 4.3.2: Input Source: Probe ..............................20
B – 5.4.2: Externally Powered ............................... 8
C – 4.4: Temperature Setup......................................21
B – 5.5: Relay 4 ......................................................... 9
C – 4.5: Conductivity/TDS Setup.............................21
B – 5.5.1: Line Powered Wiring ............................ 9
C – 4.6: Flow Rate Setup..........................................22
B – 5.5.2: Externally Powered ............................... 9
C – 5: Re-assignable Inputs..........................................22
B – 6: Wiring a Relay Expansion Module ..................... 9
C – 5.1: pH Inventory Setup.....................................22
B – 6.1: Setting Dip Switches .................................... 9
C – 5.1.1: Sensor Type 4-20mA Input...................22
B – 7: Wiring a Flow Switch ....................................... 10
C – 5.1.2: Sensor Type dry contact (NO or NC) ...........23
B – 7.1: Paddlewheel Flow Switch .......................... 10
C – 5.2: Chlorine (Bromine) Inventory Setup ..........23
B – 7.2: Reed Flow Switch ...................................... 10
C – 5.2.1: Sensor Type 4-20mA Input: .................24
B – 8: Wiring the Amperometric Probe ....................... 10
C – 5.2.2: Sensor Type dry contact (NO or NC)...........24
B – 9: Wiring the Temperature Sensor ........................ 10
C – 5.3: Turbidity .....................................................25
B – 10: Wiring the Flow Meter.................................... 11
C – 5.4: Surge Pit Level ........................................... 25
B – 10.1: +GF+Signet 2536 (Blue Cap)................... 11
C – 5.4.1: Sensor Type 4-20mA Input...................25
B – 10.2: +GF+Signet 515 (Red Cap)...................... 11
C – 5.4.2: Sensor Type dry contact (NO or NC) ...........26
B – 11: Conductivity.................................................... 11
C – 5.5: Pressure & Vacuum Setup ..........................26
B – 12: Wiring 4-20mA and digital inputs................... 11
C – 5.5.1: Influent Pressure ..................................26
B – 12.1: BECSysLS................................................ 12
C – 5.5.1.1: Sensor Type: PSI Transducer........26
B – 12.2: Floats ........................................................ 12
C – 5.5.1.2: Sensor Type: dry contact (NO or NC) ....26
B – 12.3: Turbidity sensor........................................ 12
C – 5.5.1.3: Sensor Type: Vac Transducer:......27
B – 12.4: Pressure Transducer .................................. 13
C – 5.5.2: Effluent Pressure..................................27
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
C – 5.5.2.1: Sensor Type: PSI Transducer ....... 27
C – 5.5.2.2: Sensor Type: dry contact (NO or NC) ... 28
C – 5.5.3: Differential Pressure............................ 28
C – 5.5.4: Strainer Vacuum.................................. 28
C – 5.5.4.1: Sensor Type: Vac Transducer ...... 28
C – 5.5.4.2: Sensor Type: dry contact (NO or NC) ... 29
C – 5.5.5: Total Dynamic Head ........................... 29
C – 5.6: Autofill ....................................................... 29
C – 6: Control Outputs................................................. 29
C – 6.1: Assign Relays............................................. 29
C – 6.1.1: Sanitization feeds ................................ 29
C – 6.1.1.1: Cl (Br) Feed.................................. 29
C – 6.1.1.2: Cl (Br) Booster ............................. 30
C – 6.1.1.3: SuperChlor ................................... 30
C – 6.1.1.4: DeChlor ........................................ 30
C – 6.1.1.5: Ozone ........................................... 30
C – 6.1.2: Other feeds .......................................... 30
C – 6.1.2.1: pH feeds........................................ 30
C – 6.1.2.2: Heater ........................................... 30
C – 6.1.2.3: Polymer feed ................................ 30
C – 6.1.2.4: Autofill ......................................... 30
C – 6.1.2.5: TDS Control ................................. 31
C – 6.1.2.6: Sensor Wash................................. 31
C – 6.1.2.7: Enzyme Feed ................................ 31
C – 6.1.2.8: Alarm Relay ................................. 31
C – 6.1.2.9: Recirculation Pump ...................... 31
C – 6.2: pH Control.................................................. 31
C – 6.3: Chlorine (Bromine) Control ....................... 32
C – 6.4: Chlorine (Bromine) Booster Control.......... 34
C – 6.5: Super Chlorination ..................................... 35
C – 6.6: Dechlorination............................................ 36
C – 6.7: Ozone Control ............................................ 36
C – 6.8: Heater ......................................................... 37
C – 6.9: Polymer ...................................................... 37
C – 6.10: Autofill ..................................................... 38
C – 6.11: TDS Control ............................................. 38
C – 6.12: Sensor Wash............................................. 38
C – 6.13: Enzyme..................................................... 39
C – 6.14: Alarm Relay ............................................. 39
C – 6.15: Recirculation Pump .................................. 39
C – 7: Control Options................................................. 40
C – 7.1: Flow Restored ............................................ 40
C – 7.2: Power Saver ............................................... 40
C – 7.3: pH Lockout................................................. 41
C – 8: Calculations....................................................... 41
C – 8.1: Enter Parameters ........................................ 41
C – 8.2: LSI Setup.................................................... 41
C – 9: System Configuration........................................ 41
C – 9.1: SN............................................................... 41
C – 9.2: Communication .......................................... 41
Rev: B09
C – 9.2.1: Direct Baud Rate (Operator)................41
C – 9.2.2 Modem type (Read Only) ......................41
C – 9.2.3 Modem Options (Rep) ...........................41
C – 9.2.4: Ethernet Setup (Operator)....................41
C – 9.2.5: Call Out Setup (Operator).....................42
C – 9.2.6: RS485 Network Setup (Rep) ................43
C – 9.2.7: Installed Options...................................43
C – 9.3: Datalog Frequency...................................... 43
C – 9.4: Date, Time & Units.....................................43
C – 9.5: Name and Location.....................................43
C – 9.6: User Setup...................................................43
C – 9.7: Factory Defaults.......................................... 43
C – 9.8: Display Options ........................................... 44
C – 10: 4-20mA Outs ................................................... 44
C – 10.1: Usage ........................................................44
C – 10.2: Source (Recorder Out) ..............................44
C – 10.3: Factory Defaults........................................ 44
C – 11: VFD Turndowns .............................................. 44
C – 12: Access Menu....................................................44
Section D: The Normal Display .......................................45
D – 1: Inputs and Feeds................................................45
D – 2: Alarms & Status messages ................................45
Section E: Using the Face Panel Quick Keys................... 46
E – 1: The Set Points Key ............................................ 46
E – 2: The Relay Mode Key.........................................46
E – 3: The Cal Key (calibration) .................................. 47
E – 4: The Reset Fail / Safe Key ..................................47
E – 5: The Emergency Off Key.................................... 47
Section F: Maintenance ....................................................48
F – 1: Potentiometric Sensors (pH and ORP)...............48
F – 1.1: Electrode Cleaning ......................................48
F – 1.2: Long-Term Storage .....................................48
F – 2: Free Chlorine Sensor..........................................48
F – 2.1: Cleaning ......................................................48
F – 2.2: Long-Term Storage .....................................48
F – 2.3: Filling electrolyte ........................................ 48
F – 3: Conductivity Sensor........................................... 49
F – 3.1: Cleaning ......................................................49
Section G: Tables .............................................................50
G – 1: Flow Meter K-Factors .......................................50
G – 1.1 Schedule 40 PVC Pipe..................................50
G – 1.2 Schedule 80 PVC Pipe..................................50
Section H: Feed Charts.....................................................51
H – 1: Spa Feed Charts.................................................51
H – 2: Pool Feed Charts ...............................................52
Section I: Installation Diagrams .......................................53
I – 1: Pressure Filter Installation ..................................53
I – 2: Vacuum Filter Installation ..................................53
Section J: Warranty ..........................................................54
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Rev: B09
Unpacking
Your Shipping package should contain these items:
A.
B.
C.
D.
E.
F.
G.
H.
I.
The BECSys5 Controller
ORP Sensor
pH Sensor
Temperature Sensor
Flow cell Kit
Rotary or Reed flow switch
This manual (not shown)
BECSys for Windows Installation CD (not shown)
Optional sensors (not shown)
A
B
C
D
E
F
Rotary
or
Reed
Warning: The ORP and pH Sensors are very fragile and must be handled with care. The tips of the probes
must be kept wet at all times, requiring the wetting caps to remain in place until they are ready to be
installed. The probes must be stored in temperatures above freezing.
General Guidelines
Proper installation and use of the BECSys controller depends on the specific needs of the application. Read the manual
completely before starting the installation and ensure all guidelines and recommendations are followed. All components
should be mounted and the flow cell plumbing installed and pressure tested before wiring the controller. Ensure
compliance with all applicable plumbing and electrical codes during the installation as well.
Firmware Version
This manual was written for firmware v1.26. If you received newer firmware but did not receive a copy of the manual
covering that version of firmware, please contact your distributor.
Page 1
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Rev: B09
Environmental Conditions
The BECSys5 is housed in a NEMA 4X (IP65) enclosure. It should not be used in explosive environments. The
BECSys5 should be mounted so that adequate ventilation is provided around the enclosure, preventing general
environmental specifications from being exceeded (see table below).
Environmental Specifications
Specification
Rating
Storage Temperature
-40 to 85 Deg C
Ambient Operating Temperature
-18 to 50 Deg C
Ambient Humidity
95% non condensing maximum humidity
Electrical Specifications
The BECSys5 may be ordered in either a 115VAC model or a 230VAC model. Following are the electrical specifications
for each model:
115VAC Model:
Voltage:
Phase:
Current:
230VAC Model:
Voltage:
Phase:
Current:
115VAC 60Hz
Single
12.25 Amps Full Load
(¼ Amp – Controller)
(12 Amps – Relay Outputs: 3A X 4)
230VAC 50Hz
Single
12.125 Amps Full Load
(⅛ Amp – Controller)
(12 Amps – Relay Outputs: 3A X 4)
Page 2
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Rev: B09
Warnings
Pay particular attention to the following warnings encountered in the pages of the
BECSys5 Installation and Technical Manual:
Warning: Various other warnings may be found
throughout the manual text.
Page 3
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Rev: B09
Section A: Mounting the BECSys5 Controller
A – 1: Mounting the Controller
The BECSys5 Controller and flow cell are mounted
separately. The BECSys5 enclosure should be
mounted to the wall with four anchor bolts. To
mount the BECSys5 properly, please use the
included mounting template and hardware. Drill the
holes for the anchors using a 3/16” drill bit. Install
the anchors in the wall. Remove the lid from the
unit and place the included screws in the four
corners of the box. Attach the screws into the
anchors. The BECSys5 and flow cell should be
mounted in a location that is free from chemical
fumes and excessive heat, isolated from electrical
interference, and near a power source protected by a
ground fault interrupter. The BECSys5 has a
NEMA4 weather resistant enclosure but should still
be protected if mounted outdoors.
A – 4: Plumbing the Sample Stream
Install the sample stream; ½-inch tubing is
recommended for sample stream pickup and return.
Make sure that you tap the supply off the discharge
side of the recirculation pump, upstream of the
chemical injection points. The sample should be
filtered water. Connect the sample stream pickup
line to the flow cell and run the sample stream return
line from the flow cell to the suction side of the main
recirculation pump. Install ½-inch ball valves to
allow isolation of the sample lines.
A – 5: Free Chlorine Sensor Flow Cell
There are two ways to order the Free Chlorine
Sensor – with the flow cell only, or with the flow cell
and a flow and psi restrictor assembly.
A – 2: Wrapping the Fittings
If you are assembling a flow cell, first open the bag
of flow cell fittings and wrap each fitting two times
around clockwise with Teflon tape.
A – 3: Assembling the Flow cell
Assemble the flow cell as shown below:
When installing the pH or ORP sensor, remove the
wetting cap, then remove any existing Teflon tape
from the sensor threads. Re-wrap the threads with
new Teflon tape. Rinse the sensor tip in de-ionized
water and install as shown.
Warning: These sensors should be handtightened only. Tools are not necessary for
installing the pH or ORP sensor and will
damage the sensor housing.
Page 4
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
The Free Chlorine Sensor requires a constant flow
rate and a constant pressure. This helps ensure that
the ppm level will remain stable.
Warning: Negative pressure will damage the
sensor membrane.
Here is the recommended method for plumbing the
free chlorine sensor flow cell:
Rev: B09
A – 6.2: Free Chlorine Sensor
The Free Chlorine Sensor is supplied with a yellow
protective cap. This cap has an inner sponge that is
used to keep the sensor membrane hydrated. This
cap should be saved for long-term storage.
The sensor can remain in the flow cell for shortterm interruptions in measurement. To prevent
membrane dehydration, the flow cell must not
drain off. If this is not ensured, then remove the
sensor from the flow cell and slide the yellow
protective cap, moistened at the inner sponge,
onto the measuring end of the sensor.
The voltage applied by the controller to the Free
Chlorine Sensor polarizes the surface of the gold
cathode. The polarization period must elapse
before calibration is performed based on the
results acquired through the use of a DPD test kit.
See Section F - 2.3 for filling the electrolyte.
Admission pressure must be above the regulated
pressure (15 psi is the limit on the sensor). Run the
sample stream through a flow restrictor valve (to
maintain flow rate, minimum flow rate requirement
is 8 gph). Take the stream through the flow cell.
Discharge the sample stream to a free outlet (for
example into a surge tank).
A – 6: Sensor preparations
NOTE: As soon as you install the sensors,
immediately move on to the next step to insure that
they always stay wet.
A – 6.1: ORP and pH Sensor
The pH and ORP sensors are shipped with a
wetting cap covering the measuring end. This cap
contains a solution of pH 4 buffer saturated with
potassium chloride (KCl). Gently remove the
wetting cap by unscrewing the sensor and sliding
the cap off of the sensor body.
A – 7: Opening the Sample Stream Valve
Open the sample stream valve and check for leaks.
Note the reading on the compound pressure gauge
and make sure that it shows a positive and steady
pressure. The sample stream should be about 2-20
psi at the flow cell. If this is not the case, then adjust
the valves or relocate the point at which the sample
stream is connected to the recirculation system.
Negative pressure will destroy the sensors. Once
you have a positive and steady pressure, open the wet
test valve and make sure that it generates a vigorous
stream.
A – 8: Plugging in the Sensors
Remove the protective covers from the BNCs. Plug
the pH sensor into the coded BNC jack and the
ORP sensor into the coded BNC jack on the bottom
of the BECSys5 controller by twisting them a quarter
of a turn. Allow the sensors to rinse in the sample
water while you do the wiring (Section B).
It is a good idea to save the wetting cap and
the box that the sensor came in for future
long-term storage.
During shipping, the air space inside the pH glass
may have moved into the bulb. Grasp the sensor
near the cable end and gently swing it through an
arc to force the internal electrolyte into the pH
bulb. Rinse the measuring ends of potentiometric
sensors with de-ionized or distilled water before
installation into a flow cell.
Page 5
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Rev: B09
Section B: Wiring the BECSys5 Controller
B – 2: Removing the safety shield
To remove the shield, remove the four
screws using a Philips screwdriver.
Gently lift the cover straight up and
set it to the side.
B – 1: Opening The Cover
Remove the cover by loosening the four screws at the
corners with a screwdriver as shown. NOTE: The
screws are captive and do not need to be totally
removed, but only loosened. Once the screws are
loosened, carefully lift the top cover off of the unit.
The cover will still be connected to the base by the
ribbon cable. Set the moisture absorbent packet
found inside aside for now.
B – 3: Supplied Cords
Warning: Make sure power is disconnected
while you wire the unit
You may order your controller with a male power
cord and two female power cords (Only for 115V
applications). Plug the male AC Cord into a GFCI
outlet and connect the chemical feeders to the female
power cords. The two female power cords will have
the following warning tags. Be sure to connect the
correct female power cord to the correct chemical
feeder.
We recommend that you disconnect the ribbon cable
by spreading the two holders at the end of the cable
attached to the cover as shown, unplug the cable and
remove the cover.
NOTE: Be sure to store the cover in a safe, dry place
while you wire the unit.
Page 6
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
B – 4: Conduit Connect
Warning: Make sure power is disconnected
while you wire the unit
You may instead order the controller for conduit
connection (For 115V or 230V applications).
TB4 is for the Line power coming into the unit.
Rev: B09
B – 5.1: Externally Powered Wiring
If you wish to use the C (Common) to
power a relay (commonly used to
interlock feeds with the recirculation
pump), you will need to move the black
hat jumpers located to the left of each of
the solid state relays to their upper
position using a pair of long nosed
needle nose pliers (shown left). Be
careful not to put pressure on the relays
as you are slipping between them as you
may damage their connections to the
board.
We recommend using a minimum of 14 gauge
stranded wire for the line power. Use of solid wire is
strongly discouraged.
The black wire goes to L (Line) on the upper level, the
white wire to N (Neutral), and the ground wire to the
terminal marked Earth Ground.
Hats shown in L (Line) positions
NOTE: The black and white wires are colored
brown and blue outside North America.
B – 5: Wiring the Relays
Warning: Make sure power is disconnected
while you wire the unit
The BECSys5 has four solid-state relays. From the
Factory, the controller is configured to use Relay 1 for
the pH Feed and Relay 2 for the ORP/Cl/Br Feed.
The rest of the relays are unassigned.
Hats shown in C (Common) positions
B – 5.2: Relay 1
B – 5.2.1: Line Powered Wiring
The black wire goes to the R1 position, the
white wire goes into any of the unused N
(Neutral) positions, and the Earth Ground wire
goes to any of the unused Earth Ground
positions.
Each relay can be powered from either the L (Line)
terminal that the controller itself is powered from, or
from the common terminals. Relay 1 and 2 share a
common (labeled C1 C2), Relays 3 and 4 have their
own common labeled C3 and C4 respectfully. As
shipped from the factory, all four relays are configured
for Line power.
Note: The black and white wires are colored
brown and blue outside North America.
Page 7
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
B – 5.2.2: Externally Powered
Move the hat jumper to the upper position.
Connect the power supply to the C1 C2 terminal.
The load should be connected to the R1 position.
If Earth and Neutral are involved in this circuit,
these can be wired into any of the unused N
(Neutral) positions, and Earth Ground positions.
B – 5.3: Relay 2
B – 5.3.1: Line Powered Wiring
The black wire goes to the R2 position, the white
wire goes into any of the unused N (Neutral)
positions, and the Earth Ground wire goes to any
of the unused Earth Ground positions.
Rev: B09
B – 5.4: Relay 3
B – 5.4.1: Line Powered Wiring
The black wire goes to the R3 position, the
white wire goes into any of the unused N
(Neutral) positions, and the Earth Ground wire
goes to any of the unused Earth Ground
positions.
Note: The black and white wires are colored
brown and blue outside North America.
B – 5.4.2: Externally Powered
Move the hat jumper to the upper position.
Connect the power supply to the C3 terminal.
The load should be connected to the R3
position. If Earth and Neutral are involved in
this circuit, these can be wired into any of the
unused N (Neutral) positions, and Earth
Ground positions.
Note: The black and white wires are colored
brown and blue outside North America.
B – 5.3.2: Externally Powered
Move the hat jumper to the upper position.
Connect the power supply to the C1 C2 terminal.
The load should be connected to the R2 position.
If Earth and Neutral are involved in this circuit,
these can be wired into any of the unused N
(Neutral) positions, and Earth Ground positions.
Page 8
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
B – 5.5: Relay 4
B – 5.5.1: Line Powered Wiring
The black wire goes to the R4 position, the white
wire goes into any of the unused N (Neutral)
positions, and the Earth Ground wire goes to any
of the unused Earth Ground positions.
Rev: B09
B – 6: Wiring a Relay Expansion Module
Your controller may have been ordered with one or
more Relay Expansion Modules (BECSysMRX or
BECSysSRX).
Up to three Relay Expansion
Modules may be connected to one controller. These
are connected to the RS485 terminal inside the
BECSys5.
Recommended wire: 22 gauge shielded twisted pair
(1 pair: 2 conductors + shield).
For outdoor use, use NEC type PLTC.
For indoor use, use NEC type CMG general, CMR
riser (through floors), or CMP plenum as required by
the local wiring code.
Note: The black and white wires are colored
brown and blue outside North America.
B – 5.5.2: Externally Powered
Move the hat jumper to the upper position.
Connect the power supply to the C4 terminal.
The load should be connected to the R4 position.
If Earth and Neutral are involved in this circuit,
these can be wired into any of the unused N
(Neutral) positions, and Earth Ground positions.
The Relay Expansion Modules have a second RS485
connector to allow daisy chaining of units. It doesn’t
matter which connector you use – whichever is
easiest. For each unit, connect “A” to “A”, “B” to
“B”, and “Shield” to “Shield.”
B – 6.1: Setting Dip Switches
Located on the left hand side of the Relay
Expansion Module are two dipswitch banks. One
sets the Controller ID, the other sets the Relay
Box ID.
The Controller ID should always be set to 1 – turn
on switch 1 of the “CntrID” bank. Each Relay
Expansion Module should have a different Relay
Box ID – set by the “RlyBoxID” bank. The IDs
can be from 1 to 3 – turn on the corresponding
dipswitch to set the ID.
Page 9
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
B – 7: Wiring a Flow Switch
Rev: B09
B – 7.2: Reed Flow Switch
A flow switch must be used in the operation of the
BECSys5 Controller
A paddlewheel flow switch or reed flow switch is
incorporated into the flow cell to disable chemical
feed in the event of loss of flow to the flow cell.
Warning: NEVER BYPASS FLOW
SWITCH CONNECTIONS
The Flow Switch is a critical safety device which
prevents uncontrolled chemical feed.
Uncontrolled feeding of chemicals can result in
injury or death.
Warning: Failure to incorporate a Flow
Switch and Flow cell into the sample
Stream of your BECSys chemical controller
can result in injury or death to swimmers in or
around the pool if the recirculation pump
should fail or shut down.
The reed flow switch is a (2) two-wire switch.
Connect the black wire to the terminal labeled IN,
and the red wire to the terminal labeled + 12.
NOTE: Unlike the paddlewheel flow switch,
the reed flow switch is a directional switch.
Make sure it is installed with the flow arrow in
the proper direction. No check valve is
required with the reed flow switch.
B – 8: Wiring the Amperometric Probe
B – 7.1: Paddlewheel Flow Switch
Connect the black wire of the paddlewheel/rotary
flow switch to the terminal marked ground, the
white wire to the terminal labeled IN, and the red
wire to the terminal labeled + 12. The green “flow”
light on the flow switch will light whenever flow is
present.
Warning: A check valve is must be installed
with the paddlewheel flow switch to prevent
backflow when the system is shut down. If a
check valve is not installed, backflow could give
the controller a false reading of flow and
continue to pump chemicals into the pool.
Connect the red "A" wire to the A terminal, the "K"
white tip with transparent wire to the K terminal, and
the thick unlabeled wire to the ground terminal.
NOTE: This probe requires a minimum flow
velocity of 15 cm/s against its membrane. If the
default calibration is off more than 0.3 ppm, the flow
rate may be too low. Contact the factory for
assistance.
B – 9: Wiring the Temperature Sensor
Connect the temperature probe to the Temp
terminals. The temperature probe is non-polarized,
wire orientation does not matter.
Page 10
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
B – 10: Wiring the Flow Meter
B – 10.1: +GF+Signet 2536 (Blue Cap)
Connect the black wire to the +12 terminal, the red
wire to the IN terminal, and the silver wire to the
ground terminal. Set SW1 switches 6 = off, 7 = on.
B – 10.2: +GF+Signet 515 (Red Cap)
Rev: B09
B – 12: Wiring 4-20mA and digital inputs
Depending on what inputs you need, you may need
to re-assign the input to one of the physical 420mA/digital inputs in the firmware. See “Reassignable Inputs” in section C for more
information.
The standard BECSys5 input board comes with four
4-20mA/digital inputs (outlined in red) labeled pH
Inv, Cl Inv, CH3, and CH4. Each input has a + and
– terminal and be configured as either a 4-20mA
input or a digital input by setting the corresponding
dipswitch for that channel (outline in blue). Dip 1
(the left most switch) sets the pH Inv labeled input,
dip 2 sets the Cl Inv labeled input, and so on. The
input is a 4-20mA input when the switch is up, and a
digital input when the switch is down.
Dip 1:
Dip 2:
Dip 3:
Dip 4:
Connect the red wire to the IN terminal and both
the black wire and the silver wire to the ground
terminal. Set SW1 switches 6 = on, 7 = off.
B – 11: Conductivity
You may order the BECSys5 with an optional
Conductivity Input Board.
Connect the conductivity probe to the Cond
terminals. The Conductivity probe is non-polarized
(wire orientation does not matter).
pH Inv
Cl Inv
CH3
CH4
Up = 4-20mA
Down = Digital
The following sections describe how to wire each
device to a 4-20mA/digital input without specifying
which input to wire too. It is up to the installer to
choose one of the four inputs to wire to, then
program the controller to use that physical input for
that input function (MenuÆInputsÆReassign
Inputs).
Example: Wiring a BECSysLS to CH3 to measure
the Surge Pit Level:
1. Power down the controller.
2. Set dipswitch 3 up if down.
3. Wire the BECSysLS to CH3 as shown in the
next section.
4. Power up the unit.
5. Press Menu and log on as Rep if necessary.
6. Select “Inputs”, then “Reassign Inputs”.
7. Select “CH3”.
8. Select “Surge Pit”
9. Press “Menu” again then select “Inputs”, then
“Surge Pit”, and finally “Sensor Type”.
10. Choose “4-20mA Input”
Page 11
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
B – 12.1: BECSysLS
Rev: B09
B – 12.2: Floats
Floats may be used to trigger low
liquid level Alarms:
♦ Low pH Inventory Alarm
♦ Low Cl/Br Inventory Alarm
♦ Low Surge pit Alarm
Connect the float to one of the
available 4-20mA/digital inputs on
the controller. The float is non
polarized (wire orientation does not
matter).
A BECSysLS may be used to monitor liquid levels:
pH Inventory
Cl/Br Inventory
Water level (Surge/Balance pit/tank)
The BECSysLS is a 4-20mA input and requires the
Loop Power Supply Board. Connect this to one of
the available 4-20mA/digital inputs on the
BECSys5 as follows:
Simply connect one wire to the input’s “+”
terminal and the other wire to the input’s “–”
terminal.
Make sure you configure the input as a digital
input by switching the input’s dip switch to the
down position.
B – 12.3: Turbidity sensor
The Turbidity sensor is
a 4-20mA self powered
device and does not
require the use of the
loop power supply
board. Connect this to
an available 4-20mA
input as follows:
Connect the turbidity
sensor’s positive wire to
the
input’s
“+”
terminal,
and
the
turbidity
sensor’s
negative wire to the
input’s “–” terminal.
Make sure you configure the input for 4-20mA by
switching the input’s dip switch to the upper
position.
Page 12
Make sure you configure the input for 4-20mA by
switching the input’s dip switch to the upper
position.
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
B – 12.4: Pressure Transducer
The pressure transducer is a 4-20mA
device that requires the loop power
supply board.
Pressure transducers can be used to
monitor:
♦ Filter Influent Pressure
♦ Filter Effluent Pressure
Wire the transducer to an available
4-20mA/digital input on the controller as follows:
♦ The transducer’s black wire does not get
connected and should be cut off
♦ Use the wire you cut off or another wire to
jumper the loop power supply board’s negative
terminal to the negative terminal on the
controller’s 4-20mA input.
♦ Connect the red wire to the positive position
on the loop power supply board.
♦ Connect the white wire to the positive terminal
on the controller’s 4-20mA input.
♦ Make sure you configure input to 4-20mA by
switching the input’s dip switch to the upper
position.
B – 12.5: Vacuum Transducer
The vacuum transducer is a 4-20mA
device that requires the loop power
supply board.
Vacuum transducers can be used to
monitor:
♦ Filter Influent Pressure
♦ Strainer/Drain Vacuum
Wire the transducer to an available 420mA/digital input on the controller as follows:
♦
♦
♦
♦
♦
The transducer’s white wire does not get
connected and should be cut off.
Use the wire you cut off or another wire to
jumper the loop power supply board’s negative
terminal to the input’s negative terminal.
The red wire should go to the positive
connection on the loop power supply board.
The Black wire should go to the “+” terminal
on the input.
Make sure you configure input to 4-20mA by
switching the input’s dip switch to the upper
position.
Rev: B09
B – 12.6: Murphy Swichgages
B – 12.6.1: A20P Pressure Gauge:
A pressure gauge can be
used to trigger the following:
♦ High filter influent
pressure alarm.
Simply connect the gauge’s “C” terminal and the
“N.C.” terminal to the “+” and “–” terminals on
an available 4-20mA/Digital input.
All
Swichgages are non-polarized (wire orientation
does not matter).
Make sure you configure the input as a digital
input by switching the input’s dip switch to the
down position.
B – 12.6.2:
A20DP Differential Pressure
Gauge:
A differential pressure
gauge can be used to trigger
the following:
♦ High
differential
pressure alarm
Simply connect the gauge’s “C” terminal and the
“N.O.” terminal to the “+” and “–” terminals
on an available 4-20mA/Digital input. All
Swichgages are non-polarized (wire orientation
does not matter).
Make sure you configure the input as a digital
input by switching the input’s dip switch to the
down position.
B – 12.6.3: A20V Vacuum Gauge:
A vacuum gauge can be
used to trigger the
following:
♦ High strainer vacuum
alarm
Simply connect the gauge’s “C” terminal and the
“N.O.” terminal to the “+” and “–” terminals
on an available 4-20mA/Digital input. All
Swichgages are non-polarized (wire orientation
does not matter).
Make sure you configure the input as a digital
input by switching the input’s dip switch to the
down position.
Page 13
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
B – 12.7: Proximity Switches
Proximity switches require the loop power supply
board and the proximity level interface box (BECS
PN: 1210254).
Proximity switches are mounted on a sight glass and
may be used to trigger the following:
♦
♦
♦
♦
Autofill Feed Start/End (single point control)
Autofill Feed Start (dual point control)
Autofill Feed End (dual point control)
Low Surge pit Alarm
Do not wire the proximity switch directly
to the controller. The proximity switch
must be connected to the proximity level
interface box which is what gets wired to
the controller.
Rev: B09
B – 14: BECSysRPM (Remote Probe Module)
Your controller may have been ordered with a
BECSys Remote Probe Module Interface Board.
Using this, you may connect to a BECSys Remote
Probe Module (BECSysRPM).
The BECSysRPM provides a method of extending
the probe signal.
B – 14.1: Wiring the BECSysRPM
Remove the cover of the BECSysRPM by
loosening the four screws at the corners with a
screwdriver. Note: The screws are captive and
do not need to be totally removed, but only
loosened. Once the cover has been removed, you
will see two sets of connectors. The left bank of
connectors provides connection between the
BECSysRPM and the BECSys5. The right bank of
connectors provides connection for the Flow
Switch and Temperature Sensor.
The proximity switch comes with a connector on
the end of its cable and connects to the mating
connector on the proximity level interface box.
Connect the proximity switch interface box to one
of the available 4-20mA/digital inputs on the
controller as follows:
♦ Connect the white wire to the positive terminal
on the loop power supply board.
♦ Connect the black wire to the positive terminal
on the controller’s 4-20mA input.
♦ Connect the green wire to the negative terminal
on the controller’s 4-20mA input.
♦ Jumper the negative terminal on the
controller’s 4-20mA input to the negative
terminal on the loop power supply board.
♦ Make sure you configure input to digital input
by switching the input’s dip switch to the lower
position.
B – 13: 4-20mA Outputs
Your controller may have
been ordered with a 4-20mA
output board. Using this
you can connect the
controller to a building
management system or
other device.
You would connect the “+”
on the 4-20mA output
board to the “+” on the
device and the “-“ on the 420mA output board to the “-“ on the device.
Page 14
Wiring the Temperature Sensor: Connect the
Temperature Sensor to the RTD-IN + and RTDIN – connectors on the right bank.
The
Temperature Sensor is non-polarized, wire
orientation does not matter.
Wiring a Paddlewheel Flow Switch: Connect
the black wire of the paddlewheel/rotary flow
switch to the terminal labeled GND, the white
wire to the terminal labeled Flow, and the red wire
to the terminal labeled +12V. The green “flow”
light on the flow switch will light whenever flow is
present.
Warning: A check valve is must be installed
with the paddlewheel flow switch to prevent
backflow when the system is shut down. If a
check valve is not installed, backflow could
give the controller a false reading of flow and
continue to pump chemicals into the pool.
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Wiring a Reed Flow Switch: The reed flow
switch is a two wire switch. Connect the black wire
to the terminal labeled “FLOW” and the red wire to
the terminal labeled “+12V”.
NOTE:
Unlike the paddlewheel flow
switch, the reed flow switch is a directional
switch. Make sure it is installed with the
flow arrow in the proper direction. No
check valve is required with the reed flow
switch.
Connecting the Probes: Remove the protective
covers from the BNCs. Plug the pH sensor into the
coded BNC jack and the ORP sensor into the
coded BNC jack on the bottom of the BECSysRPM
by twisting them a quarter of a turn.
B – 14.2: Wiring to the BECSys5
There are a total of seven connections that must be
made between the BECSys5 and the BECSysRPM
(24 gauge wire is acceptable to use).
Power: Power is provided to the BECSysRPM
from the BECSys Remote Probe Module Interface
Board. Connect the terminal labeled +12V on the
BECSysRPM Interface Board to the terminal
marked +12V on the BECSysRPM (left bank of
connectors). Connect the terminal labeled GND
on the BECSysRPM Interface Board to the terminal
marked GND on the BECSysRPM (left bank of
connectors).
Probe Signal: From the BECSysRPM Interface
Board connect the terminal labeled Out(1) to
Out(1) on the BECSysRPM. Connect Out(2) to
Out(2) on the BECSysRPM.
Flow: On the BECSys5 CPU board, connect a
wire to “IN” on the Flow Switch Input. Connect
the other end to the terminal labeled “FLOW” on
the BECSysRPM. The +12V and GND on the
BECSys5 Flow Switch Input are not used.
Rev: B09
B – 15: BECSys Ethernet Card Cable
Use these wiring instructions for controllers that
come with a BECSys Ethernet card installed at the
factory. If you are installing a BECSys Ethernet card
into a controller yourself, use the instructions
supplied with the BECSys Ethernet card instead of
these.
Connected to the end of the network cable is an inline coupler. You may either connect a cable directly
to this or remove the coupler and connect to a wall
jack.
B – 16: Re-installing the safety shield
Gently place the safety shield over the
fuse holders – you may have to adjust
the fuse holders a little in order for it to
fit properly. Once the shield is sitting
flat, replace the four screws.
B – 17: Fuses
115VAC Model (F4):
¼ Amp 250V Time Lag Fuse (¼” x 1¼”)
230VAC Model (F4):
⅛ Amp 250V Time Lag Fuse (¼” x 1¼”)
Relay Fuses (F1 – F4):
3 Amp 250V Time Lag Fuse (¼” x 1¼”)
RS485 Fuse (F11 CPU Board):
¼ Amp 250V Time Lag Microfuse (5.08mm)
Temperature: From the BECSys5 Input Board,
connect two wires to the “Temp” input. Connect
the other end of these two wires to the terminal
labeled “RTD-OUT +” and “RTD-OUT –“. The
temperature input is not polarized, wire orientation
does not matter.
Page 15
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Rev: B09
Section C: Programming the Controller
C – 1: Adjusting the Display Contrast
You can adjust the display contrast by holding down
either the up or down arrow keys for two seconds,
then after the controller beeps three times, use the
up and down keys to adjust the contrast.
C – 2: Security Settings
C – 2.1: Access Codes and levels
The BECSys5 controller ships from the factory
with all access codes disabled. The controller will
not ask you for an access code when you press the
menu or other quick buttons until you enable and
set the Rep access code and at least one Operator
access code. Setting Manager access codes is
optional.
If the Rep access code is disabled, you are
automatically given rep access without the
controller prompting you for an access code. This
is true even if you set an Operator and/or
Manager access codes.
Warning: It is strongly recommended to set a
Rep Access Code. By not setting a Rep Access
Code, anyone can access Rep Menus.
To view who is currently logged on, press the lock
screen button while in any menu.
Until you set the rep access code, you will always
have rep access, and until you set at least one
operator code, the controller will never prompt
you to enter an access code to gain access to a
particular screen (see table).
Rep
Managers
Operators
Access level
given
Not set
Set
Set
Set
Don't care
Not set
1 or both set
Don't care
Don't care
Not set
Not set
1 or more set
Rep
Manager
Operator
Prompt
Setting just the rep access code will result in the
default access level being Manager, and the
controller will still not prompt you to enter in an
access code when you press the Menu or other
face panel buttons. However, any items exclusive
to rep access will not be shown unless you log on
manually via the Logon selection in the main
menu.
C – 2.2: Setting Access Codes
To set an access code, press the menu button,
then:
Select System Config
Choose User Setup
Then select the access level you want to set an
access code for.
To set Operator 1's access code, you would select
Oper. Access Codes, then select Operator 1.
The Main Menu will also display who is logged on
along with the version of firmware.
You do not need to set all the access codes for
each level if you do not wish to. Also, a disabled
access code is not equivalent to 000, so entering
000 when it prompts for an access code will only
work if you have specifically assigned an access
code to be 000.
NOTE: Once access codes have been set, certain
programmable options will not be accessible to
Operators and Managers.
Page 16
Pressing and holding the +/- button disables the
access code, while pressing enter will enable and
set the access code to the value on the screen.
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Operators may only change their own access code.
Managers may change their access code and any of
the Operators. Reps can change anyone's access
code.
C – 2.3: Recovering Lost Access Codes
If an access code is forgotten, the code can be
recovered by the following procedure:
1. Flip switch 2 on SW1 to the on position.
2.
Press Menu, and if necessary select logon to
bring up the Access Menu.
Rev: B09
If you set the permissions for Calibrations, when
you press the Cal button while in the normal
display, the unit will display the current enabled
inputs. Once you select input to calibrate, you will
then be prompted to log into the controller. If
you do not have permission to change the value,
“Access level denied” will be displayed in the
status area.
A third permission level is set up for Emergency
Off and Reset Fail/Safe. This level is “Anyone”
and is the default setting. If the permission setting
is “Anyone”, you may access these functions
without logging onto the controller.
C – 3: Navigating the menus
3.
4.
Select the level of the access code you wish
to recover.
Record the encrypted value(s) displayed
beneath the prompt and turn Dip 2 off
when done. The example below shows the
encrypted codes for Op1 (D), Op3 (F), and
Op4 (G), while Op2, Op5, & Op6 are
disabled on that system.
5.
BECS Technology can be contacted for
decryption of this code, providing the
original access code.
C – 2.4: Setting Permissions
You may set what operators, managers, or anyone
have access to in the Permissions menu. By
default, all permissions are set to their lowest level
(Oper, Mgr, & Rep or Anyone). When you select
the Permissions menu under the User Setup menu,
you are given several options to choose from.
By selecting one of these options you are able to
select who has access to what.
If “Oper, Mgr & Rep” is selected, everyone with
an access code is able to modify that setting. If
“Mgr & Rep” is selected, only Managers and Reps
are able to modify the settings. If “Rep only” is
selected, only Reps are able to modify the setting.
The controller's menus incorporate built in help text
to aid in understanding the function of each
parameter, item, and option.
C – 3.1: Common status messages
The very bottom line of the display contains the
time and date on the left while the right is reserved
for a number of status messages; the most
common are as follows:
"Busy..." - Indicates the controller is busy doing
something critical and it cannot stop until it
finishes.
Until this message disappears, the
controller will not respond to your key presses
(although it does record them any will process
them when done). Normally this message is only
seen briefly after changing a setting, but it is also
used for lengthier operations such as factory
defaults and in the extremely rare case where the
internal diagnostics detect a memory problem and
attempts to correct it.
Warning: Interrupting the controller by
turning the power off while it displays the busy
message could result in the complete loss of all
of its settings.
"(1 of 2) (More Æ)" - and the like indicate there
are more options for you to choose from than the
controller could show at one time. Press the right
arrow key (Next) to view them. The left number
indicates the current page, while the right number
indicates the total number of pages.
"Bad Value, Retry..." - Accompanied by an error
beep, this indicates the value you just entered was
not within the allowable range of values and was
not stored.
C – 3.2: The Menu Screens
Most of the features of the controller are
configured via the Menu button's menus. The
menu screens can be broken up into two types:
entry screens and lists.
Page 17
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
C – 3.2.1: Entry Screens
An entry screen is used to enter a value using
the keypad.
The current value is usually displayed at the top
while the cursor will be positioned under the
current digit or character of the value you are
entering in. The up and down arrows allow you
to move the cursor right or left so you do not
have to retype the existing digits if you only wish
to change one.
Most numerical values will display the minimum
and maximum values you can enter in at the
bottom of the display in the format "< ### to
###>". These ranges many times will be
dependant on other values you have set, such as
alarm points or set points, while others are
simply fixed to stay within a reasonable range.
Entering a value that is not within the acceptable
range will result in an error beep and the
message "Bad Value, Retry..." being displayed in
the status area.
For some values, certain keys may take on
special functions that are explained in the lower
lines of the screen. The Down/up message in
the example above is one of them.
C – 3.2.2: List Screens
The list screens are mainly composed of lists of
menu items that you can choose from by either
pressing an item's number or by using the up
and down arrow keys to select it (indicated by
the arrow) and then pressing enter to choose it.
Using the up and down arrow keys also allows
you to view each item's help text. And if the
item leads to an entry screen or a list screen that
sets a setting (see below), the current value is
displayed in the lower right side.
Page 18
Rev: B09
Lists can also be used to change a setting:
When a list is used this way, it will display the
current setting followed by the words "Change
to:". Because it is a list, you can select an item
with the up/down buttons to see help
information about that particular selection.
There are a few list screens that use the entire
width of the display for displaying values
associated with each item and therefore do
not have help. See Section E: Using the
Quick Set Face Panel Keys for examples of
these types of screens.
C – 3.3: The Lock Screen Key
When not in a menu (i.e. viewing the normal
display), pressing the lock screen key will prevent
the controller from paging the screen to show
more inputs, alarms, and other status information.
See Section D: The Normal Display for more info
about using the lock screen key in the normal
display.
While within any menu, if the user does not press
a key within sixty seconds of the last key press, the
current user is logged out and the screen is
returned to the normal display. To prevent the
controller from timing out, you may lock the
screen.
While within a menu, pressing the Lock Screen key
will bring up a popup menu:
The first option on the popup will be either to
lock or unlock the screen depending on the
current lock state. While the screen is locked, key
presses normally are ignored. However, in some
instances certain keys are given special functions
while the screen is locked, such as using the up
and down arrows to scroll the help text if all of the
help text cannot be displayed at once.
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
You can also lock/unlock the screen without
bringing up the popup menu by holding down
the lock button for one second.
The
controller will acknowledge this action with a
triple beep and the yellow Lock Screen light
will turn on.
The Lock button popup menu also identifies who
is currently logged on, and provides an option for
the user to log off. You can also select cancel if
you pressed the lock button in error.
C – 4: Fixed Inputs
To enter the program menu, press the Menu button
on the front face panel of your controller. This will
allow the viewing of the Main Menu where the
programming options are displayed.
The ppm Input, Cl (Br) Inventory Input, Cl
(Br) feed, and Cl (Br) booster feed are all
displayed as either Chlorine and Cl or
Bromine and Br depending on the chemical
selected in the Cl (Br) feed menu. This
manual is written using the Chlorine setting.
If you select Bromine as the sanitizing
chemical, the controller will display Bromine
and Br instead of Chlorine and Cl, but the
menus and functions are otherwise exactly the
same as shown.
Select Inputs from the menu.
C – 4.1: pH Setup
After entering the Inputs option, select the pH
Setup from the menu. This will allow you to
program the following for the pH Input:
Decimal Places (Rep): This option allows you
to configure the controller to display pH with 1 or
2 decimal places.
The controller sees far more resolution than
what it displays on the screen. Setting the
number of decimal places only affects what
the user sees and the set points they can enter.
It does not affect how accurately the
controller controls.
High Alarm (Operator): The high alarm will
activate when the pH rises above this setting.
Input the desired level and press enter. Disable
this alarm by holding down the +/- key for 1
second. The range is dependant on the pH feed's
set point and/or the low alarm point.
Low Alarm (Operator): The low alarm will
activate when the pH falls below this setting.
Input the desired level and press enter. Disable
this alarm by holding down the +/- key for 1
second. The range is dependant on the pH feed's
set point and/or the high alarm point.
Rev: B09
Alarm Hysteresis (Manager): This value sets
the amount that the pH reading has to rise above
the high alarm or fall below the low alarm before
the alarm will shut off. Input the desired level and
press enter. (the range is from 0.0 to 1.4)
Input Averaging (Rep): This value sets the
number of samples used to get an average for the
pH display reading. (The input is read once every
two seconds.) Input the desired number and press
enter (the range is from 1 to 20).
Calibrate (Rep): This selection allows you to
perform a two point calibration of the pH Input.
Note: You will need a signal generator to
perform this function. Hook up the signal
generator to the controller and set it to the pH
mode. Set the signal generator to a pH setting of
7.0, type that value into the controller, and press
enter. Then set the signal generator to a pH setting
of 12.24, type that value into the controller, and
press enter. This will give you an accurate reading
of the pH level.
Factory Defaults (Rep): This option allows you
to reset the controller back to the factory defaults
for all of the pH Input settings.
Disable Input (Rep): Allows you to disable the
pH Input on the controller. pH will not be shown
on the main screen and all control features
associated with pH will be disabled also.
C – 4.2: ORP Setup
After entering the Inputs option, select the ORP
Setup from the menu. This will allow you to
program the following for the ORP Input:
High Alarm (Operator): The high alarm will
activate when the ORP rises above this setting.
Input the desired level and press enter. Disable
this alarm by holding down the +/- key for 1
second. The range is dependant on the Cl feed's
ORP set point and/or the low alarm point.
Low Alarm (Operator): The low alarm will
activate when the ORP falls below this setting.
Input the desired level and press enter. Disable
this alarm by holding down the +/- key for 1
second. The range is dependant on the Cl feed's
ORP set point and/or the high alarm point.
Alarm Hysteresis (Manager): This value sets the
amount that the ORP reading has to rise above the
high alarm or fall below the low alarm before the
alarm will shut off. Input the desired level and
press enter. (the range is from 0 to 200 mV)
Input Averaging (Rep): This value sets the
number of samples used to get an average for the
ORP display reading. (The input is read once every
two seconds.) Input the desired number and press
enter. (the range is from 1 to 20)
Page 19
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Calibrate (Rep): This selection allows you to
perform a two point calibration of the ORP Input.
Note: You will need a signal generator to
perform this function. Hook up the signal
generator to the controller and set it to the ORP
mode. Set the signal generator to 0 ORP, type that
value into the controller, and press enter. Then set
the signal generator to 750 ORP, type that value
into the controller, and press enter. This will give
you an accurate reading of the ORP level.
Factory Defaults (Rep): This option allows you
to reset the controller back to the factory defaults
for all of the ORP Input settings.
Disable Input (Rep): Allows you to disable the
ORP Input on the controller. ORP will not be
shown on the main screen and all control features
associated with ORP will be disabled also.
C – 4.3: ppm Setup
After entering the Input option, select the ppm
Setup from the menu. This will allow you to
program the following for the ppm Input:
Input Source (Rep): Once you have entered the
ppm setup menu, select Input Source. Here you
can select whether your ppm reading will be by
calculation, amperometric probe, or disabled.
C – 4.3.1: Input Source: Calculated
High Alarm (Operator): The high alarm will
activate when the ppm rises above this setting.
Input the desired level and press enter. Disable
this alarm by holding down the +/- key for 1
second. The range is dependant on the Cl (Br)
feed's ppm set point and/or the low alarm
point.
Low Alarm (Operator): The low alarm will
activate when the ppm falls below this setting.
Input the desired level and press enter. Disable
this alarm by holding down the +/- key for 1
second. The range is dependant on the Cl (Br)
feed's ppm set point and/or the high alarm
point.
Alarm Hysteresis (Manager): This value sets
the amount that the ppm reading has to rise
above the high alarm or fall below the low
alarm before the alarm will shut off. Input the
desired level and press enter. (the range is from
0.0 to 2.0 ppm)
Factory Defaults (Rep): This option allows
you to reset the controller back to the factory
defaults for all the ppm Input settings.
C – 4.3.2: Input Source: Probe
Decimal Places (Rep): This option allows
you to configure the controller to display ppm
with 1 or 2 decimal places.
Page 20
Rev: B09
High Alarm (Operator): The high alarm will
activate when the ppm rises above this setting.
Input the desired level and press enter. Disable
this alarm by holding down the +/- key for 1
second. The range is dependant on the Cl (Br)
feed's ppm set point and/or the low alarm
point.)
Low Alarm (Operator): The low alarm will
activate when the ppm falls below this setting.
Input the desired level and press enter. Disable
this alarm by holding down the +/- key for 1
second. The range is dependant on the Cl (Br)
feed's ppm set point and/or the high alarm
point.
Alarm Hysteresis (Manager): This value sets
the amount that the ppm reading has to rise
above the high alarm or fall below the low
alarm before the alarm will shut off. Input the
desired level and press enter. (the range is from
0.0 to 2.0 ppm)
Input Averaging (Rep): This value sets the
number of samples used to get an average for
the ppm display reading. (The input is read
once every two seconds.) Input the desired
number and press enter (the range is from 1 to
20)
Calibrate (Operator): This selection allows
you to do a single point calibration of ppm,
enter the reading from you test kit, and press
enter. The value entered must be 1.0 or greater.
Reset Calibration (Operator): Resets the
calibration to the original factory setting.
Interlock Duration (Rep): Enter the amount
of time to wait after providing power to the
probe before allowing ppm-based control and
press enter. (the range is 0:30 to 18:00 hours)
When power is first applied to the
amperometric probe, it takes time for the
probe to polarize and give accurate readings.
Depending on the probe and the situation,
this time can be as little as ten minutes and as
long as several hours.
While the interlock timer is active, all ppmbased controls are disabled, defaulting to
ORP control if available.
Factory Defaults (Rep): This option allows
you to reset the controller back to the factory
defaults for all the ppm Input settings.
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
C – 4.4: Temperature Setup
After entering the Input option, choose the
Temperature Setup from the menu. This will allow
you to program the following for the Temperature
Input:
Temp Input Enable (Rep): If a Temperature
Sensor is installed, enable this input.
The included temperature probe must be
installed in the flow cell and connected to the
controller for the temperature display to work.
If enabled, you will have the following options:
High Alarm (Operator): The high alarm will
activate when the temperature rises above this
setting. Input the desired temperature and press
enter. Disable this alarm by holding down the +/key for 1 second. The range is dependant on the
Heater's set point (if installed) and/or the low
alarm point.
Low Alarm (Operator): The low alarm will
activate when the temperature falls below this
setting. Input the desired temperature and press
enter. Disable this alarm by holding down the +/key for 1 second. The range is dependant on the
Heater's set point (if installed) and/or the high
alarm point.
Input Averaging (Rep): This value sets the
number of samples used to get an average for the
temperature display reading. (The input is read
once every two seconds.) Input the desired
number and press enter (the range is from 1 to 20)
Alarm Hysteresis (Manager): This value sets
the amount that the temperature reading has to
rise above the high alarm or fall below the low
alarm before the alarm will shut off. Input the
desired level and press enter. (the range is from 0
to 18)
Calibrate (Rep): This selection allows you to
perform a two point calibration of the
Temperature Input. Note: You will need a
signal generator to perform this function.
Hook up the signal generator to the controller and
set it to the temperature mode (RTD). Set the
signal generator to 59 degrees, type that value into
the controller, and press enter. Then set the signal
generator to 123 degrees, type that value into the
controller, and press enter. This will give you an
accurate reading of the temperature.
Factory Defaults (Rep): This option allows you
to reset the controller back to the factory defaults
for all the Temperature Input settings.
Rev: B09
C – 4.5: Conductivity/TDS Setup
Note: Available only with Conductivity Input
Board.
After entering the Input option, choose the
Conductivity Setup from the menu. This will allow
you to program the following for the Conductivity
Input:
Input Enable (Rep): If a Conductivity/TDS
Sensor is installed, enable this input.
If enabled, you will have the following options:
Units (Rep): This allows you to choose the units
conductivity will be displayed in. You may choose
either conductivity (μmhos) or TDS (ppm).
High Alarm (Operator): The high alarm will
activate when the input rises above this setting.
Enter the desired value and press enter. Disable
this alarm by holding down the +/- key for 1
second. The range is dependant on the TDS
control's set point (if installed) and/or the low
alarm point.
Low Alarm (Operator): The low alarm will
activate when the input falls below this setting.
Enter the desired value and press enter. Disable
this alarm by holding down the +/- key for 1
second. The range is dependant on the TDS
control's set point (if installed) and/or the high
alarm point.
Input Averaging (Rep): This value sets the
number of samples used to get an average for the
Conductivity/TDS display reading. (The input is
read once every two seconds.) Input the desired
number and press enter (the range is from 1 to 20)
Alarm Hysteresis (Manager): This value sets
the amount that the Conductivity/TDS reading
has to rise above the high alarm or fall below the
low alarm before the alarm will shut off. Input the
desired level and press enter. (the range is from 0
to 1000 for TDS and 0 to 2000 for conductivity)
Calibrate (Rep): This selection allows you to
perform a two point calibration of the
Conductivity/TDS Input.
Factory Defaults (Rep): This option allows you
to reset the controller back to the factory defaults
for all the Conductivity/TDS Input settings.
Page 21
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
C – 4.6: Flow Rate Setup
After entering the Inputs menu, choose the Flow
Rate Setup from the menu. This will allow you to
program the following for the Flow Rate Input:
Enable Input (Rep): If a Flow Rate Sensor is
installed, enable this input.
If enabled, you will have the following options:
Input Range (Rep): Allows you to change
ranges between gpm and kgpm
Display Volume (Rep): Selects whether or not
to display the filter volume on the normal display.
K Factor (Rep): (See Section F-1 for values)
The K Factor is the number of pulses the sensor
will generate for each engineering unit of water
that passes by it. The K Factor is determined by
the size and material of the pipe as well as the
fittings that are used. Enter the proper value and
press enter. (the range is from 0.500 to 65.535 for
U.S. or 0.132 to 17.314 for metric)
No Chemical Feeds on Low Flow Alarm
(Rep): Chooses whether or not to lockout
chemical feeding on a low flow alarm.
Low Alarm (Operator): This value sets the
reading that the flow rate low alarm will be
activated. Input the desired value and press enter.
Disable this alarm by holding down the +/- key
for 1 second. (The range is 0 to 3000.0 gpm or
lpm)
Alarm Hysteresis (Manager): This value sets
the reading that the flow rate must rise above the
low alarm before the alarm will shut off. Enter the
desired number and press enter. (The range is 1 to
50.0 gpm or lpm)
Input Averaging (Rep): This value sets the
number of samples used to get an average for the
flow rate display reading. Enter the desired
number and press enter. (the range is from 1 to 20)
The controller updates the flow rate every two
seconds by taking the total number of pulses
recorded over the last ten seconds,
multiplying that by six (to get sixty seconds or
1 minute), then divides by the K factor to get
gpm or lpm. The ten second timeframe is an
average by itself, so you should only set the
Input Averaging to greater than one if the
flow rate reading bounces up and down.
Factory Defaults (Rep): This option allows you
to reset the controller back to the factory defaults
for all of the Flow Rate Input settings.
Page 22
Rev: B09
C – 5: Re-assignable Inputs
All of the 4-20mA inputs are re-assignable. You may
reassign inputs based on what you need.
After entering the Inputs menu, select Reassign
Inputs (you may need to go to the second page).
After entering this menu, you will see a list of the
inputs that are assigned.
C – 5.1: pH Inventory Setup
After entering the Inputs menu, choose pH Inv
from the menu. This will allow you to program the
following for the pH Inventory Setup.
Sensor Type (Rep):
4-20mA Input: Select this if you are using a
BECSysLS or similar 4-20mA
device. The controller will
prompt you to choose between
level or weight, and then ask
you for the input range of the
sensor. The input range is
whatever the maximum value
the sensor is rated to measure
and
ideally
the
value
represented by 20mA.
N.O. dry contact: Select this if you are using a
float with normally open
contact switches closing when
the chemical level falls below
the point you wish an alarm to
be triggered.
N.C. dry contact: Select this if you are using a
float with normally closed
contact switches opening when
the chemical level falls below
the point you wish an alarm to
be triggered.
Not Installed:
No sensor installed.
C – 5.1.1: Sensor Type 4-20mA Input
Be sure to set the dipswitch to the 4-20mA
position.
Once 4-20mA Input has been selected, you will
be prompted to select either level or weight, and
then to enter the input range. Once the input
range has been entered, you will have the
following options:
Sensor Type (Rep): Allows you to change the
sensor type to a different type.
Level or Weight (Rep): Choose if your pH
inventory is to be measured by the level of
chemical or the weight of the chemical. Level is
measured in feet or meters and weight is
measured in lbs or kg.
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Input Range (Rep): This value sets the input
range which is whatever the maximum value the
sensor is rated to measure and ideally the value
represented by 20mA (for level, the range is
from 1.0 to 50.0 ft. U.S. or 0.3 to 20.0 meters
metric; for weight, the range is from 100 to
5000 lbs U.S. or 45 to 500 kg metric).
Low Alarm (Operator): This value sets at
what level or weight the pH inventory low
alarm will be activated. Enter the desired level
or weight and press enter. You may also disable
this alarm by holding down the +/- key for 1
second (the range is dependant on the input
range).
Alarm Hysteresis (Manager): This value sets
at what level the pH inventory level or weight
has to rise above the low level or weight alarm
setting before the alarm will shut off. Enter the
desired number and press enter (the range is
10% of the input range).
Input Averaging (Rep): This value sets the
number of samples used to get an average for
the pH inventory level. Enter the desired
number and press enter (the range is from 1 to
20).
Calibrate (Rep): Once you have entered pH
Inventory Setup, select Calibrate from the
menu.
This calibration is only needed if the readings
are accurate at one level/weight, but are off
by an increasing amount the farther away you
go from that level/weight.
If the reading is off by a consistent amount
throughout the input range, perform a single
point calibration by pressing the Cal button
and selecting this input from the list.
It is important that the Input Range is set to
the correct value; otherwise you may find that
the controller refuses to accept the second
value due to it being "out of range" or "points
too close" (see below).
Calibration is a two step process:
1) While the inventory is low, measure or
estimate the current level/weight, enter
this value in as the first point and press
enter. The controller will not time out
and exit the menu while waiting for the
second point of a calibration, so you do
not need to lock the screen here.
2) Fill the inventory by a known amount.
Add this amount to the value you entered
for the first point, enter the sum as the
second point.
Rev: B09
If you discover later that your first point was
off, simply do a single point calibration to
correct it.
If you get a "points too close" error message,
either the values you entered or the input
readings taken for those values were too close
together to perform an accurate calibration
calculation. You either did not add enough
inventory, the Input Range is wrong for the
sensor attached, or there could be a problem
with the wiring if the reading did not change
when you added the inventory.
If you get a "out of range" error message, you
entered a value outside of the configured
Input Range. If the sensor is supposed to be
able to measure the value you entered, then
the Input Range was not set to the correct
value and should be corrected.
Factory Defaults (Rep): This option allows
you to reset the controller back to the factory
defaults of the pH inventory settings.
C – 5.1.2: Sensor Type dry contact (NO or NC)
Be sure to set the dipswitch to the digital
position.
This setting will give you the following option:
Sensor Type (Rep): Allows you to change the
sensor type to a different type.
C – 5.2: Chlorine (Bromine) Inventory Setup
After entering the Inputs menu, choose Cl Inv
from the menu. This will allow you to program the
following for the Chlorine Inventory Setup.
Sensor Type (Rep):
4-20mA Input: Select this if you are using a
BECSysLS or similar 4-20mA
device. The controller will
prompt you to choose between
level or weight, and then ask
you for the input range of the
sensor. The input range is
whatever the maximum value
the sensor is rated to measure
and
ideally
the
value
represented by 20mA.
N.O. dry contact: Select this if you are using a
float with normally open
contact switches closing when
the chemical level falls below
the point you wish an alarm to
be triggered.
Page 23
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
N.C. dry contact: Select this if you are using a
float with normally closed
contact switches opening when
the chemical level falls below
the point you wish an alarm to
be triggered.
Not Installed:
No sensor installed.
C – 5.2.1: Sensor Type 4-20mA Input:
Be sure to set the dipswitch to the 4-20mA
position.
Once 4-20mA Input has been selected, you will
be prompted to select between level or weight,
and then to enter the input range. Once the
input range has been entered, you will have the
following options:
Level or Weight (Rep): Choose if your
Chlorine Inventory is to be measured by the
level of chemical or the weight of the chemical.
Level is measured in feet or meters and weight
is measured in lbs or kg.
Input Range (Rep): This value sets the input
range which is whatever the maximum value the
sensor is rated to measure and ideally the value
represented by 20mA (for level, the range is
from 1.0 to 50.0 ft. U.S. or 0.3 to 20.0 meters
metric; for weight, the range is from 100 to
5000 lbs U.S. or 45 to 500 kg metric).
Low Alarm (Operator): This value sets at
what level or weight the pH inventory low
alarm will be activated. Enter the desired level
or weight and press enter. You may also disable
this alarm by holding down the +/- key for 1
second (the range is dependant on the input
range).
Alarm Hysteresis (Manager): This value sets
at what level the Chlorine Inventory level or
weight has to rise above the low level or weight
alarm setting before the alarm will shut off.
Enter the desired number and press enter (the
range is 10% of the input range).
Input Averaging (Rep): This value sets the
number of samples used to get an average for
the Chlorine Inventory level. Enter the desired
number and press enter (the range is from 1 to
20).
Calibrate (Rep): Once you have entered
Chlorine Inventory Setup, select Calibrate from
the menu.
This calibration is only needed if the readings
are accurate at one level/weight, but are off
by an increasing amount the farther away you
go from that level/weight.
Page 24
Rev: B09
If the reading is off by a consistent amount
throughout the input range, perform a single
point calibration by pressing the Cal button
and selecting this input from the list.
It is important that the Input Range is set to
the correct value; otherwise you may find that
the controller refuses to accept the second
value due to it being "out of range" or "points
too close" (see below).
Calibration is a two step process:
1) While the inventory is low, measure or
estimate the current level/weight, enter
this value in as the first point and press
enter. The controller will not time out
and exit the menus while waiting for the
second point of a calibration, so you do
not need to lock the screen here.
2) Fill the inventory by a known amount.
Add this amount to the value you entered
for the first point, enter the sum as the
second point.
If you discover later that your first point was
off, simply do a single point calibration to
correct it.
If you get a "points too close" error message,
either the values you entered or the input
readings taken for those values were too close
together to perform an accurate calibration
calculation. You either did not add enough
inventory, the Input Range is wrong for the
sensor attached, or there could be a problem
with the wiring if the reading did not change
when you added the inventory.
If you get a "out of range" error message, you
entered a value outside of the configured
Input Range. If the sensor is supposed to be
able to measure the value you entered, then
the Input Range was not set to the correct
value and should be corrected.
Factory Defaults (Rep): This option allows
you to reset the controller back to the factory
defaults of the Chlorine Inventory settings.
C – 5.2.2: Sensor Type dry contact (NO or NC)
Be sure to set the dipswitch to the digital
position.
This setting will give you the following option:
Sensor Type (Rep): Allows you to change the
sensor type to a different type.
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
C – 5.3: Turbidity
After entering the Inputs menu, choose Turbidity
from the menu. This will allow you to program the
following for the Turbidity Input.
Enable Input (Rep): If a Turbidity Meter is
installed, enable this input.
Be sure to set the dipswitch to the 4-20mA
position.
If enabled, you will have the following options:
High Alarm (Operator): The high alarm will
activate when the input reaches or rises above this
setting. Enter the desired value and press enter.
Disable this alarm by holding down the +/- key
for 1 second. (The range is dependant on the input
range.)
Alarm Hysteresis (Manager): This value sets
the level that the turbidity reading has to rise
above the high alarm setting before the alarm will
shut off. Input the desired level and press enter.
(the range is 10% of the input range)
Input Averaging (Rep): This value sets the
number of samples used to get an average for the
turbidity display reading. (The input is read once
every two seconds.) Input the desired number and
press enter (the range is from 1 to 20)
Calibrate (Rep): Perform a two point calibration
of the turbidity input.
Input Range (Rep): Enter the sensor's input
range which is whatever the maximum value the
sensor is rated to measure and ideally the value
represented by 20mA. (the range is from 2 to 20
NTU)
Factory Defaults (Rep): This option allows you
to reset the controller back to the factory defaults
for all of the turbidity input settings.
C – 5.4: Surge Pit Level
After entering the Inputs menu, select Surge Pit
Level from the menu (you may have to go to the
second page). This will allow you to program the
following for the Surge Pit Level Input.
Sensor Type (Rep): Once you have entered the
Surge Level, select Sensor Type from the menu.
Here you will be able to choose between:
4-20 mA Input: The controller will prompt you
for the input range of the
sensor. The input range is
whatever the maximum value
the sensor is rated to measure
and
ideally
the
value
represented by 20mA.
N.O. dry contact: Select this if you are using a
float with normally open
contact switches closing when
the surge pit level reaches the
Rev: B09
point you wish an alarm to be
triggered.
N.C. dry contact: Select this if you are using a
float with normally closed
contact switches opening when
the surge pit level reaches the
point you wish an alarm to be
triggered.
Not Installed:
No sensor installed.
C – 5.4.1: Sensor Type 4-20mA Input
Be sure to set the dipswitch to the 4-20mA
position.
Once 4-20mA Input has been selected, you will
be prompted to enter the input range. Once the
input range has been entered, you will have the
following options:
High Alarm (Operator): The high alarm will
activate when the input rises above this setting.
Enter the desired value and press enter. Disable
this alarm by holding down the +/- key for 1
second. (the range is dependant on the input
range)
Low Alarm (Operator): The low alarm will
activate when the input falls below this setting.
Enter the desired value and press enter. Disable
this alarm by holding down the +/- key for 1
second. (the range is dependant on the input
range)
Alarm Hysteresis (Manager): This value sets
the amount that the surge pit level has to rise
above the high alarm or fall below the low
alarm before the alarm will shut off. Input the
desired level and press enter.
Input Averaging (Rep): This value sets the
number of samples used to get an average for
the surge pit level. Enter the desired number
and press enter (the range is from 1 to 20).
Calibrate (Rep):
Performs a two point
calibration of the Surge Pit Level Input.
Input Range (Rep): This value sets the input
range which should be whatever the maximum
value the sensor is rated to measure and ideally
the value represented when the sensor outputs
20mA (the range is from 1.0 to 50.0 ft. U.S. or
0.3 to 20.0 m metric).
Label (Rep): You may rename this input if you
choose. There is a 12 character maximum.
Factory Defaults (Rep): This option allows
you to reset the controller back to the factory
defaults for all of the surge pit level input
settings.
Page 25
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
C – 5.4.2: Sensor Type dry contact (NO or NC)
Be sure to set the dipswitch to the digital
position.
This setting will give you the following options:
Sensor Type (Rep): Allows you to change the
sensor type to a different type.
Label (Rep): You may rename this input if
you choose. There is a 12 character maximum.
C – 5.5: Pressure & Vacuum Setup
After entering the Input menu, choose Pressure &
Vac. from the menu. This will allow you to
program the following for the Filter Pressure
Inputs:
C – 5.5.1: Influent Pressure
Once Influent Pressure has been selected, you
will need to set the following:
Sensor Type (Rep):
PSI Transducer: Select this if you are using a
pressure transducer that will
output a 4-20mA signal. The
controller will prompt you for
the input range of the sensor.
The input range is whatever
the maximum value the sensor
is rated to measure and ideally
the value represented by
20mA.
N.O. dry contact: Select this if you are using a
gauge with normally open
contact switches closing on a
high or low pressure.
N.C. dry contact: Select this if you are using a
gauge with normally closed
contact switches opening on a
high or low pressure.
Vac Transducer: Select this if you are using a
vacuum transducer that will
output a 4-20mA signal. The
controller will prompt you for
the input range of the sensors.
The input range is whatever
the maximum value the sensor
is rated to measure and ideally
the value represented by
20mA.
Not Installed: No sensor installed
C – 5.5.1.1: Sensor Type: PSI Transducer
Be sure to set the dipswitch to the 4-20mA
position.
If the sensor type is set to PSI transducer, you
will be prompted to enter the input range.
Once the input range has been entered, you
will have the following options:
Page 26
Rev: B09
Sensor Type (Rep): Allows you to change
the sensor type to a different type.
Input Range: (Rep):
Enter the
transducer’s input range which is whatever
the maximum value the sensors are rated to
measure and ideally the value represented by
20mA. (the range is from 10 to 100 psi or 69
to 690 kPa).
High Alarm: (Operator) The high alarm
will activate when the pressure reaches or
rises above this setting. Input the desired
pressure and press enter. Disable this alarm
by holding down the +/- key for 1 second.
(The range is dependant on the low alarm
point.)
Low Alarm: (Operator) The low alarm will
activate when the pressure falls below this
setting. Input the desired pressure and press
enter. Disable this alarm by holding down
the +/- key for 1 second. (The range is
dependant on the high alarm point.)
Alarm Hysteresis: (Manager) This value
sets the amount that the pressure reading has
to rise above the high alarm or fall below the
low alarm before the alarm will shut off.
Input the desired level and press enter. (The
range is from 0 to 5)
Input Averaging (Rep): This value sets the
number of samples used to get an average
for the pressure display reading. (The input
is read once every two seconds.) Input the
desired number and press enter (The range is
from 1 to 20)
Display Input (Operator): This option
enables/disables displaying the influent
pressure on the normal display.
Calibrate (Rep): This selection allows you
to perform a two point calibration of the
Influent Pressure Input.
Factory Defaults (Rep):
This option
allows you to reset the controller back to the
factory defaults for all the Influent Pressure
Input settings.
C – 5.5.1.2: Sensor Type: dry contact (NO or NC)
Be sure to set the dipswitch to the digital
position.
This setting will give you the following
options:
Sensor Type (Rep): Allows you to change
the sensor type to a different type. See
above section for a description of the
selections under this menu.
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Factory Defaults (Rep):
This option
allows you to reset the controller back to the
factory defaults for all the Influent Pressure
Input settings.
C – 5.5.1.3: Sensor Type: Vac Transducer:
Be sure to set the dipswitch to the 4-20mA
position.
If the sensor type is set to Vac transducer, you
will be prompted to select the units to display.
Once the units have been selected, you will
have the following options:
Sensor Type (Rep): Allows you to change
the sensor type.
Units (Rep): Selects the units to display
this input in. The choices for US units are
PSI (+/-) or in-Hg (+/-), and for metric
kPa (+/-) or cm-Hg (+/-).
High Alarm (Operator): The high alarm
will activate when the vacuum falls below
this setting. Input the desired pressure and
press enter. Disable this alarm by holding
down the +/- key for 1 second. (The range
is dependant on the low alarm point.)
Low Alarm (Operator): The low alarm will
activate when the vacuum reaches or rises
above this setting. Input the desired pressure
and press enter. Disable this alarm by
holding down the +/- key for 1 second.
(The range is dependant on the high alarm
point.)
Alarm Hysteresis (Manager): This value
sets the amount that the vacuum reading has
to rise above the low alarm or fall below the
high alarm before the alarm will shut off.
Input the desired level and press enter. (The
range is from 0 to 5)
Input Averaging (Rep): This value sets the
number of samples used to get an average
for the vacuum display reading. (The input is
read once every two seconds.) Input the
desired number and press enter (The range is
from 1 to 20)
Display Input (Operator): This option
enables/disables displaying the influent
pressure on the normal display.
Calibrate (Rep): This selection allows you
to perform a two point calibration of the
influent pressure input.
Factory Defaults (Rep):
This option
allows you to reset the controller back to the
factory defaults for all the Influent Pressure
Input settings.
Rev: B09
C – 5.5.2: Effluent Pressure
Once Effluent Pressure has been selected, you
will need to set the following:
Sensor Type (Rep):
PSI Transducer: Select this if you are using a
pressure transducer that will
output a 4-20mA signal.
The controller will prompt
you for the input range of
the sensor. The input range
is whatever the maximum
value the sensor is rated to
measure and ideally the
value represented by 20mA.
N.O. dry contact: Select this if you are using a
gauge with normally open
contact switches closing on a
high or low pressure.
N.C. dry contact: Select this if you are using a
gauge with normally closed
contact switches opening on
a high or low pressure.
Not Installed: No sensor installed.
C – 5.5.2.1: Sensor Type: PSI Transducer
Be sure to set the dipswitch to the 4-20mA
position.
If sensor type is set to PSI transducer, you will
be prompted to enter the input range. Once
the input range has been entered, you will
have the following options:
Sensor Type (Rep): Allows you to change
the sensor type to a different type.
Input Range (Rep): Enter the transducer’s
input range which is whatever the maximum
value the sensors are rated to measure and
ideally the value represented by 20mA. (the
range is from 10 to 100 psi or 69 to 690 kPa)
High Alarm (Operator): The high alarm
will activate when the pressure reaches or
rises above this setting. Input the desired
pressure and press enter. Disable this alarm
by holding down the +/- key for 1 second.
(The range is dependant on the low alarm
point.)
Low Alarm (Operator): The low alarm will
activate when the pressure falls below this
setting. Input the desired pressure and press
enter. Disable this alarm by holding down
the +/- key for 1 second. (The range is
dependant on the high alarm point.)
Page 27
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Alarm Hysteresis (Manager): This value
sets the amount that the pressure reading has
to rise above the high alarm or fall below the
low alarm before the alarm will shut off.
Input the desired level and press enter. (The
range is from 0 to 5)
Input Averaging (Rep): This value sets the
number of samples used to get an average
for the pressure display reading. (The input
is read once every two seconds.) Input the
desired number and press enter (The range is
from 1 to 20)
Display Input (Operator): This option
enables/disables displaying the Effluent
pressure on the normal display.
Calibrate (Rep): This selection allows you
to perform a two point calibration of the
Effluent Pressure Input.
Factory Defaults (Rep):
This option
allows you to reset the controller back to the
factory defaults for all the Effluent Pressure
Input settings.
C – 5.5.2.2: Sensor Type: dry contact (NO or NC)
Be sure to set the dipswitch to the digital
position.
This setting will give you the following
options:
Sensor Type (Rep): Allows you to change
the sensor type to a different type. See
above section for a description of the
selections under this menu.
Factory Defaults (Rep):
This option
allows you to reset the controller back to the
factory defaults for all the Influent Pressure
Input settings.
C – 5.5.3: Differential Pressure
High Alarm (Operator): The high alarm will
activate when the pressure rises above this
setting. Input the desired pressure and press
enter. Disable this alarm by holding down the
+/- key for 1 second. (the range is 0 to 40)
Alarm Hysteresis (Manager): This value sets
the amount that the pressure reading has to rise
above the high alarm or fall below the low
alarm before the alarm will shut off. Input the
desired level and press enter. (the range is from
0 to 10)
Factory Defaults (Rep): This option allows
you to reset the controller back to the factory
defaults for all the Differential Pressure Input
settings.
Page 28
Rev: B09
C – 5.5.4: Strainer Vacuum
After entering the Input option, choose the
Strainer Vacuum from the menu. This will allow
you to program the following for the Strainer
Vacuum Input:
Sensor Type (Rep): Once you have entered
the Strainer Vacuum menu, select Sensor Type.
Here you will be able to choose between:
Vac Transducer: Select this if you are using
a vacuum transducer that
will output a 4-20mA
signal. The controller will
prompt you for the input
range of the sensor. The
input range is whatever
the maximum value the
sensor is rated to measure
and ideally the value
represented by 20mA
N.O. dry contact: Select this if you are using
a gauge with normally
open contact switches
closing on a high or low
vacuum.
N.C. dry contact: Select this if you are using
a gauge with normally
closed contact switches
opening on a high or low
vacuum.
Not Installed: No sensor installed
C – 5.5.4.1: Sensor Type: Vac Transducer
Be sure to set the dipswitch to the 4-20mA
position.
If sensor type is set to Vac transducer, you
will be prompted to select which units to
display. Once the units have been selected,
you will have the following options:
Sensor Type (Rep): Allows you to change
the sensor type to a different type.
Units (Rep): Selects the units to display this
input in. The choices for US units are PSI
(+/-) or in-Hg (+/-), and for metric kPa
(+/-) or cm-Hg (+/-).
High Vac Alarm (Operator): The high
vacuum alarm will activate when the
pressure falls below this setting. This is
actually a low pressure alarm that operates in
the negative pressure range, which is a
vacuum. Input the desired pressure and
press enter. Disable this alarm by holding
down the +/- key for 1 second.
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Alarm Hysteresis (Manager): This value
sets the level that the vacuum reading must
fall below the high alarm setting before the
alarm will shut off. Input the desired level
and press enter. (The range is from 0 to 5)
Input Averaging (Rep): This value sets the
number of samples used to get an average
for the vacuum display reading. (The input is
read once every two seconds.) Input the
desired number and press enter (The range is
from 1 to 20)
Calibrate (Rep): Perform a two point
calibration of the Strainer Vacuum Input.
Factory Defaults (Rep):
This option
allows you to reset the controller back to the
factory defaults for all the Strainer Vacuum
Input settings.
C – 5.5.4.2: Sensor Type: dry contact (NO or NC)
Be sure to set the dipswitch to the digital
position.
Sensor Type (Rep): Allows you to change
the sensor type to a different type.
Factory Defaults (Rep):
This option
allows you to reset the controller back to the
factory defaults for all the Strainer Vacuum
Input settings.
C – 5.5.5: Total Dynamic Head
In order to show the menu for Total Dynamic
Head, the Strainer and the Influent Pressure
Input must be set to Transducer. Here you can
choose to display the total dynamic head. If
Total Dynamic Head is displayed, you will have
the following options:
Display TDH (Operator): Will display the
Total Dynamic Head on the normal display.
High Alarm (Operator): The high alarm will
activate when the Total Dynamic Head across
the pump rises above this setting. Input the
desired value and press enter. Disable this
alarm by holding down the +/- key for 1
second.
Low Alarm (Operator): The low alarm will
activate when the Total Dynamic Head across
the pump falls below this setting. Input the
desired value and press enter. Disable this
alarm by holding down the +/- key for 1
second.
Alarm Hysteresis (Manager): This value sets
the amount that the Total Dynamic Head has to
rise above the high alarm or fall below the low
alarm before the alarm will shut off. Input the
desired level and press enter (The range is from
0 to 5).
Rev: B09
Factory Defaults (Rep): This option allows
you to reset the controller back to the factory
defaults for all the Total Dynamic Head
settings.
C – 5.6: Autofill
This menu item is only available if the Surge Pit is
set to 4-20mA Input, or if the Autofill 1 or Autofill
2 inputs have been installed (see the next section
for information on how to do this). After entering
the Inputs menu, select Autofill (you may have to
go to the second page).
Sensor Type (Rep): Once you have entered the
Autofill menu, select Sensor Type. Here you will
be able to choose between:
Surge Pit Level: Allows the Autofill to be
triggered from the Surge Pit
Level.
N.O. prox switch: Select this if you are using a
proximity switch with normally
open contacts
N.C. prox switch: Select this if you are using a
proximity switch with normally
open contacts
Not Installed:
No sensor installed.
C – 6: Control Outputs
Press the Menu button on the front face panel of the
Controller and select Control Outputs. You will
then be able to select the following items:
C – 6.1: Assign Relays
To enable control functions, you must assign that
function a relay. You may also reassign the pH
feed and/or Cl (Br) feed if you desire to.
The following details how to assign relays to the
different control functions.
After entering the Control Outputs option, select
Assign Relays you will be able to select the
following:
C – 6.1.1: Sanitization feeds
This
will
list
the
available
Sanitization/Oxidization control functions:
You can use the up and down arrow keys to
view the current relay assignment of a
particular control function.
C – 6.1.1.1: Cl (Br) Feed
This is your primary Cl (Br) feed. To set or
change the relay used, or to disable this
control, select the Cl Feed from the menu.
This will display all of the relays available to
be assigned to this control, including the
current relay if one was already assigned.
Page 29
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
C – 6.1.1.2: Cl (Br) Booster
The Cl (Br) Booster is a highly programmable
secondary Cl (Br) feed for helping maintain
the ORP and/or ppm levels of the pool
during high bather loads. This feed also runs
during Super Chlorination cycles, and is
locked out by the Cl (Br) failsafe alarm.
To set or change the relay used, or to disable
this control, select the Cl Booster from the
menu. This will display all of the relays
available to be assigned to this control,
including the current relay if one was already
assigned.
C – 6.1.1.3: SuperChlor
The Super Chlorination (shock) function is
unique to the other control functions in the
sense that you can either assign its own relay
[for controlling an additional chlorine
(bromine) feed or a non-chlorine shock
chemical feed], or assign it to the primary Cl
(Br) feed's relay if an additional feeder is not
used. SuperChlor will always override and run
the primary Cl (Br) feed and the Cl (Br)
booster feed, if enabled, in order to help bring
the ORP or ppm level up to the set point.
To set or change the relay used, or to disable
this control, select SuperChlor from the
menu. This will display all of the relays
available to be assigned to this control,
including the current relay if one was already
assigned.
C – 6.1.1.4: DeChlor
The DeChlor feature is only shown if
SuperChlor has been assigned a relay.
DeChlor is intended to be used following a
super chlorination to bring the ORP and/or
ppm level back down to a safe level.
To set or change the relay used, or to disable
this control, select the DeChlor from the
menu. This will display all of the relays
available to be assigned to this control,
including the current relay if one was already
assigned.
C – 6.1.1.5: Ozone
The Ozone feed is a highly programmable
feed similar to the Cl (Br) booster, but is not
limited by the Cl (Br) failsafe or forced to
operate during a Super Chlorination cycle.
To set or change the relay used, or to disable
this control, select the Ozone from the menu.
This will display all of the relays available to
be assigned to this control, including the
current relay if one was already assigned.
Page 30
Rev: B09
C – 6.1.2: Other feeds
Depending on your controller’s configuration,
some of these feeds may not be available.
After entering the Assign Relay menu, select
Other Feeds from the menu. This will list the
available control functions that do not deal with
sanitization/oxidization or pumps and valves.
You can use the up and down arrow keys to
view the current relay assignment of a
particular control function.
C – 6.1.2.1: pH feeds
Two pH feeds are available for use. If both
feed directions are used, they will work
together to maintain a single set point. This is
useful if you have other feeds that affect the
pH in different directions (for example: the Cl
(Br) feed drives the pH up but the Cl (Br)
booster feed drives the pH down more).
To set or change the relay used, or to disable
this control, select the pH direction from the
menu. This will display all of the relays
available to be assigned to this control,
including the current relay if one was already
assigned.
C – 6.1.2.2: Heater
The heater control allows you to control the
heater to a different set point at different
times of the day and will be automatically shut
down during no flow or low flow alarms.
To set or change the relay used, or to disable
this control, select the Heater from the menu.
This will display all of the relays available to
be assigned to this control, including the
current relay if one was already assigned.
C – 6.1.2.3: Polymer feed
The Polymer feed uses the Turbidity Input to
determine when to add polymer to the water
to increase the filtration power of your filters.
To set or change the relay used, or to disable
this control, select the Polymer feed from the
menu. This will display all of the relays
available to be assigned to this control,
including the current relay if one was already
assigned.
C – 6.1.2.4: Autofill
The Autofill control operates a makeup water
valve to add water to your pool. It uses the
Surge Pit 4-20mA Input, and has a
programmable alternate set point to control to
a different level while, for example, feature
pumps are running.
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
To set or change the relay used, or to disable
this control, select the Autofill from the
menu. This will display all of the relays
available to be assigned to this control,
including the current relay if one was already
assigned.
C – 6.1.2.5: TDS Control
The TDS control works with the Autofill
control or an independent Autofill device to
lower the TDS of the pool by operating a
drain valve to drain water while the Autofill
adds
fresh
water
requires
the
conductivity/TDS sensor.
To set or change the relay used, or to disable
this control, select the TDS Ctrl from the
menu. This will display all of the relays
available to be assigned to this control,
including the current relay if one was already
assigned.
C – 6.1.2.6: Sensor Wash
Sensor Wash is a programmable timer
triggering an acid feed wash to clean the pH
and ORP probes.
To set or change the relay used, or to disable
this control, select the Sensor Wash from the
menu. This will display all of the relays
available to be assigned to this control,
including the current relay if one was already
assigned.
C – 6.1.2.7: Enzyme Feed
To set or change the relay used, or to disable
this control, select the Enzyme Feed from the
menu. This will display all of the relays
available to be assigned to this control,
including the current relay if one was already
assigned.
C – 6.1.2.8: Alarm Relay
The Alarm Relay triggers whenever there is an
active alarm or while the emergency off
feature is active.
To set or change the relay used, or to disable
this control, select the Alarm Relay from the
menu. This will display all of the relays
available to be assigned to this control,
including the current relay if one was already
assigned.
There are no programmable options for the
Alarm relay.
C – 6.1.2.9: Recirculation Pump
The Recirculation Pump control is used to
shutdown the Recirculation Pump under
certain alarm conditions and by the
powersaver control option.
Rev: B09
To set or change the relay used, or to disable
this control, select the Recirculation Pump
from the menu. This will display all of the
relays available to be assigned to this control,
including the current relay if one was already
assigned.
C – 6.2: pH Control
After entering the Control Outputs option, select
pH Control from the menu. This will allow for
the programming of the following for the pH
control:
Control Type (Operator): Choose from On/Off
or Time Base Proportional control.
In general, if you are using a motor driven
chemical feeder then you should choose the
On/Off option. If you are using a solenoid
driven or pulsed diaphragm chemical feeder
(such as Pulsatron, most LMI models or most
Prominent Models), you should choose the
TBP option. This feature helps to hold a set
point and to minimize over-shoot by making a
standard feeder mimic the action of more
sophisticated modulating feeders.
If you choose the On/Off option and are
feeding up, then the controller will activate
the chemical feeder whenever the pH falls
below the set point and continue to feed until
the pH rises above the set point plus
hysteresis at which point it will stop.
If you choose the TBP option and are feeding
up then the controller will activate the
chemical feeder whenever the pH falls below
the set point and will feed for a percentage of
the Time Base (default one minute)
proportional to the offset from set point. For
the remainder of the Time Base the feeder will
be paused. The feeder will continue this feed
and pause cycle until the controller achieves
the set point plus hysteresis. The closer to set
point, the less time the feeder is ON.
Set Point (Operator): This value sets the desired
level to maintain the pH at. Input the desired pH
set point. (the range is 6.0 to 9.0 ppm)
Span/Prop. Bnd (Operator): This option is only
shown if the Control Type is Time Base Proportional. This
value sets the distance (or span) from the set point
that the output will be proportionally controlled.
(the range is from 0.0 to 2.0)
Warning: Increasing or decreasing the
proportional band may cause the feed to
severely overshoot or never achieve set point.
Adjust this option only when recommended to
do so by a factory representative.
Page 31
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Time Base (Operator): This option is only shown if
the Control Type is Time Base Proportional. This sets
the total time that control is based on. During this
time, the feeder will turn on for a percentage of
the Time Base and turn off for the remainder (the
range is from 15 to 300 seconds).
Warning: Increasing or decreasing the time
base may cause the feed to severely overshoot
or never achieve set point. Adjust this option
only when recommended to do so by a factory
representative.
Minimum On Time (Rep): This value is the
minimum time the pump will be on during Time
Base Proportional control. This helps protect the
feeder from cycling on or off for too short a
period of time.
Failsafe Timer (Operator): This value sets the
time that the relay is allowed to stay continuously
on. (the range is 0:00 to 18:00 hours)
The most common failures of automated
chemical feed systems are depletion of the
chemical supply and/or chemical feeder
failure. Both problems result in the controller
being unable to reach set point in a reasonable
period of time. The failsafe timer sets the
maximum length of time the feeder can run.
If the feeder has been trying to achieve set
point without success for the selected time,
the controller will cut power to the feeder,
flash the Reset Fail/Safe LED on the face
panel and display a message to alert the
operator.
If in TBP Pause mode, the
controller will reset the timer.
An operator must reset the failsafe through
the Reset Fail/Safe button to re-enable
normal control.
Warning: Disabling the failsafe timers is
highly discouraged. They are an important
safety feature to protect against dangerous
chemical overfeeds and will protect the
equipment from running continuously if it runs
out of chemical.
Hysteresis (Rep): This value sets the amount the
input must rise above (feed up) or fall below (feed
down) the set point before the feed is shut off.
(the range is from 0.0 to 1.4)
Dead Band (Manager): This option is only shown
only if you have both feed up and feed down feeds enabled.
This value sets the amount the input must exceed
the set point by before the feed of the opposite
direction will trigger. (The range is from twice the
feeds' hysteresis to 2.8 pH)
Page 32
Rev: B09
Factory Defaults (Rep): This option allows you
to reset the controller back to the factory defaults
for all of the pH Control settings.
C – 6.3: Chlorine (Bromine) Control
After entering the Control Outputs option, select
the Cl Control from the menu. This will allow the
programming of the following:
Sanitizer Chemical (Operator):
Sets the
sanitizer chemical name (Chlorine or Bromine).
This option controls what chemical name the
controller displays for the ppm Input and the
primary sanitization/oxidizing chemical.
Control Input Src (Operator): This option is only
available if the ppm Input source is set to Calculated or
Probe. Choose between ORP and ppm to use as
the primary control input for the sanitizer feed.
If the ppm Input is selected and the ppm
Input source is set to probe, ORP is still used
for control while the ppm interlock timer is
running.
If the ppm Input is selected and the ppm
Input source is set to calculated, the controller
still controls off of ORP, but the ORP set
point is calculated by the controller based on
the ppm set point, the pH set point, and the
ppm calibration. Modification of any one of
those three values will result in a new ORP set
point.
Control Type (Operator): Choose from On/Off
or Time Base Proportional control.
In general, if you are using a motor driven
chemical feeder then you should choose the
On/Off option. If you are using a solenoid
driven or pulsed diaphragm chemical feeder
(such as Pulsatron, most LMI models or most
Prominent Models), you should choose the
TBP option. This feature helps to hold a set
point and to minimize over-shoot by making a
standard feeder mimic the action of more
sophisticated modulating feeders.
If you choose the On/Off option, then the
controller will activate the chemical feeder
whenever the ORP falls below the set point
and continue to feed until the ORP rises
above the set point plus hysteresis at which
point it will stop.
If you choose the TBP option, then the
controller will activate the chemical feeder
whenever the ORP falls below the set point
and will feed for a percentage of the Time
Base (default one minute) proportional to the
offset from set point. For the remainder of
the Time Base the feeder will be paused. The
feeder will continue this feed and pause cycle
until the controller achieves the set point plus
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
hysteresis. The closer to set point, the less
time the feeder is ON.
ORP Set Point (Operator): This option is NOT
shown if the Control Source is set to ppm and the ppm
Input source is set to Calculated. This value sets the
desired level to maintain the ORP at (the range is
700 to 800 mV).
ORP Ctrl Hyst (Rep): This value sets the
amount the input must rise above the set point
before the feed will shut off (the range is 0 to 200
mV).
ORP Span/Prop. Bnd (Operator): This option is
only shown if the Control Type is Time Base Proportional
and the ORP Set Point is shown above. This value sets
the distance (or span) from the set point that the
output will be proportionally controlled. (the range
is from 0 to 500 mV)
Warning: Increasing or decreasing the
proportional band may cause the feed to
severely overshoot or never achieve set point.
Adjust this option only when recommended to
do so by a factory representative.
ppm Set Point (Operator): This option is only
shown if the Control Source is set to ppm. This value
sets the desired level to maintain the ppm at (the
range is dependant on the ppm high and low
alarms).
ppm Ctrl Hyst (Rep): This option is only shown if
the Control Source is set to ppm and the ppm Input source
is set to probe. This value sets the amount the input
must rise above set point before the feed will shut
off (the range is 0.0 to 2.0 ppm).
ppm Span/Prop Bnd: (Operator) This option is
only shown if the Control Type is Time Base
Proportional, the Control Source is set to ppm,
and the ppm Input source is set to probe. This
value sets the distance (or span) from the set point
that the output will be proportionally controlled
(the range is from 0.0 to 2.0 ppm).
Warning: Increasing or decreasing the
proportional band may cause the feed to
severely overshoot or never achieve set point.
Adjust this option only when recommended to
do so by a factory representative.
Rev: B09
Time Base (Operator): This option is only shown if
the Control Type is Time Base Proportional. This sets
the total time that control is based on. During this
time, the feeder will turn on for a percentage of
the Time Base and turn off for the remainder (the
range is from 15 to 300 seconds).
Warning: Increasing or decreasing the time
base may cause the feed to severely overshoot
or never achieve set point. Adjust this option
only when recommended to do so by a factory
representative.
Minimum On Time (Rep): This value is the
minimum time the pump will be on during Time
Proportional control. This helps protect the
feeder from cycling on or off for too short a
period of time.
Failsafe Timer (Operator): This value sets the
time that the relay is allowed to stay continuously
on. (the range is 0:00 to 18:00 hours)
The most common failures of automated
chemical feed systems are depletion of the
chemical supply and/or chemical feeder
failure. Both problems result in the controller
being unable to reach set point in a reasonable
period of time. The failsafe timer sets the
maximum length of time the feeder can run.
If the feeder has been trying to achieve set
point without success for the selected time,
the controller will cut power to the feeder,
flash the Reset Fail/Safe LED on the face
panel and display a message to alert the
operator.
If in TBP Pause mode, the
controller will reset the timer.
An operator must reset the failsafe through
the Reset Fail/safe button to re-enable normal
control.
Warning: Disabling the failsafe timers is
highly discouraged. They are an important
safety feature to protect against dangerous
chemical overfeeds and will protect the
equipment from running continuously if it runs
out of chemical.
Alt Set Point: The 4 Event 28 Day Timer allows
you to program a schedule to define when to use
alternate set point.
Alt Set Point 4 Event 28 Day Timer
(Operator): To program the 4 Event 28 Day
Timer, perform the following:
• Select the Alt. Set point from the Cl (Br)
Control menu.
Page 33
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
• Now select the 4Event 28Day Timer from the
Alt. Set Point menu.
• Selecting Event1 will allow you to select the
weekly interval to use the alternate set point.
If the 1st, 2nd, 3rd, or 4th week is selected,
the timer will only trigger on that week in the
four-week cycle. The Odd Weeks selection
will trigger on the 1st and 3rd weeks, the
Even Weeks selection will trigger on the 2nd
and 4th weeks, and the Every Week selection
triggers every week.
The week number and day of week for the
current date is displayed on the bottom
right side of these screens.
The first week is fixed to be the week of
Sunday, January 2nd, 2000 and every four
weeks afterwards.
The next set of screens will allow you to
choose the actual day(s).
• Select what day of the week, or every day, the
alternate set point should be used.
• Once you make your selection you will be
returned to the 4Event 28Day Timer menu
where you will have a new menu item: Event
1 Times.
• Select the Event1 Times from the 4Event
28Day Timer menu.
This screen allows you to set both the start
time and the end time for the event's
programmed weeks/days.
To toggle
AM/PM, press the +/- key while the cursor is
on the time you wish to change.
If your start time is before midnight (12:00
AM) and the end time is after midnight, the
alternate set point will continue to be used
the following day up to the end time even if
that day did not fall within the week/day
selection for that event.
Example:
Event1 Week/Day: Odd weeks/ Tuesday
Event1 Times:
11:00 PM to 3:00 AM
Event2 Week/Day: Even weeks/ Monday
Event2 Times:
11:00 PM to 6:00 AM
Current Week/Day: 2nd/Tuesday
Current Time:
4:00 PM
The alternate set point last ran from 11:00 PM
last night to 6:00AM this morning.
The next time the alternate set point will run will
be from 11:00 PM next Tuesday to
3:00AM next Wednesday.
ORP Set Point (Operator): This value sets
the desired level to maintain the ORP at during
Page 34
Rev: B09
any of the programmed alternate set point
events. (the range is dependant on the alarm
points)
ppm Set Point (Operator): This option is only
available if the ppm probe is installed and the Control
Source is set to ppm. This value sets the desired
level to maintain the ppm at during any of the
programmed alternate set point events. (the
range is dependant on the alarm points)
Bracketed ppm (Operator): This option is only
available if the ppm probe is installed and the Control
Source is set to ORP. If enabled, the controller will
override the ORP control so that the ppm will not
drop out of a programmed range.
Bracketed ORP (Operator): This option is only
available if the ppm probe is installed and the Control
Source is set to ppm. If enabled, the controller will
override the ppm control so that the ORP will not
drop out of a programmed range.
Factory Defaults (Rep): This option allows you
to reset the controller back to the factory defaults
for all of the Cl Control settings.
C – 6.4: Chlorine (Bromine) Booster Control
After entering the Control Outputs option, select
the Cl Booster Ctrl from the menu. This will allow
the programming of the following:
Control Input (Operator): This option is only
available if the ppm Input is enabled. Choose between
ORP, ppm or, if the ppm probe is used, both to
control the chlorine booster.
ORP Trigger Point (Operator): This option is only
shown if the Control Input is ORP or Both. This value
sets the ORP level that the input must drop below
to activate the chlorine booster control. (the range
is -1000 mV to the Cl Booster's ORP Set Point)
ppm Trigger Point (Operator): This option is only
shown if the Control Input is ppm or Both. This value
sets the ppm level that the input must drop below
to activate the chlorine booster control. (the range
is from 0.0 ppm to the Cl Booster's ppm Set
Point)
ORP Set Point (Operator): This option is only
shown if the Control Input is ORP or Both. This value
sets the ORP level that once it is reached the
chlorine booster control will shut off. (the range is
from Cl Booster's ORP Trigger Point to the ORP
high alarm point)
ppm Set Point (Operator): This option is only
shown if the Control Input is ppm or Both. This value
sets the ppm level that once it is reached the
chlorine booster control will shut off. (the range is
from the Cl Booster's ppm Trigger Point to the
ppm high alarm point)
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
ORP Hysteresis (Operator): This option is only
shown if the Control Input is ORP, Both, or, if ppm Input
source is set to calculated, ppm. This value sets the
level that the input must rise above the set point
before the chlorine booster control will turn off.
(the range is from 0 to 200 mV)
ppm Hysteresis (Operator): This option is only
shown if the ppm probe is used and the Control Input is
ppm or Both. This value sets the level that the input
must rise above the set point before the chlorine
booster control will turn off. (the range is from 0.0
to 2.0 ppm)
Label (Rep): Allows you to change the name of
this control. There is a 12 character maximum.
Failsafe Timer (Operator): This value sets the
time that the relay is allowed to stay continuously
on. (the range is 0:00 to 18:00 hours)
Warning: Disabling the failsafe timers is
highly discouraged. They are an important
safety feature to protect against dangerous
chemical overfeeds and will protect the
equipment from running continuously if it runs
out of chemical.
The most common failures of automated
chemical feed systems are depletion of the
chemical supply and/or chemical feeder
failure. Both problems result in the controller
being unable to reach set point in a reasonable
period of time. The failsafe timer sets the
maximum length of time the feeder can run.
If the feeder has been trying to achieve set
point without success for the selected time,
the controller will cut power to the feeder,
flash the Reset Fail/Safe LED on the face
panel and display a message to alert the
operator.
If in TBP Pause mode, the
controller will reset the timer.
An operator must reset the failsafe through
the Reset Fail/Safe button to re-enable
normal control.
Factory Defaults (Rep): This option allows you
to reset the controller back to the factory defaults
for all of the Cl Booster Control settings.
C – 6.5: Super Chlorination
After entering the Control Outputs option, select
Super Chlorination from the menu. This will allow
the programming of the following:
Control Input (Operator): This option is only
available if the ppm probe is installed. Choose between
ppm and ORP to use to control the Super
Chlorination feed.
Rev: B09
4 Event 28 Day Timer (Operator): To program
when the super chlorination should trigger, select
4Event 28Day Timer from the Super Chlorination
menu:
Selecting Event1 will allow you to select the
weekly interval to trigger the Super
Chlorination. If the 1st, 2nd, 3rd, or 4th week
is selected, the timer will only trigger on that
week in the four-week cycle. The Odd Weeks
selection will trigger on the 1st and 3rd weeks,
the Even Weeks selection will trigger on the
2nd and 4th weeks, and the Every Week
selection triggers every week.
The week number and day of week for the
current date is displayed on the bottom
right side of these screens.
The first week is fixed to be the week of
Sunday, January 2nd, 2000 and every four
weeks afterwards.
Next you can select the day of the week (or
every day) the event should be triggered on.
Once you make your selection, you will be
returned to the 4Event 28Day Timer menu where
you will have a new menu item: Event 1 Start
Time.
Select the Event1 Start Time from the 4Event
28Day Timer menu.
This screen allows you to set the time to trigger
the event on the programmed weeks/days. The
event will trigger at the start time if the
controller is running at that time. To toggle
AM/PM, press the +/- key. Enter the desired
time and press enter.
After setting the time, press the left arrow to
return to Super Chlorination's main menu. Here
you will notice the next scheduled super
chlorination is displayed for you. The controller
will also list the last super chlorination here once
one has been completed.
Maximum Time On (Operator): This value sets
the maximum time you want the Super
Chlorination on to reach the set point. If the time
expires before set point is reached, the controller
will trigger the SuperChlor failsafe alarm and end
the SuperChlor feeds. (the range is from 0:00 to
18:00 hours)
An operator can reset the failsafe through the
Reset Fail/Safe button; however the failsafe
alarm will automatically clear itself when the
regular Cl feed begins feeding.
Page 35
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
ORP Set Point (Operator): This option is only
shown if the Control Input is set to ORP. This value sets
the desired ORP level to shock the pool. (the
range is from -1000 to 1000 mV)
ppm Set Point (Operator): This option is only
shown if the Control Input is set to ppm. This value sets
the desired ppm level to shock the pool. (the range
is from 0.0 to 20.0 ppm)
Factory Defaults (Rep): This option allows you
to reset the controller back to the factory defaults
for all of the Super Chlorination settings.
C – 6.6: Dechlorination
After entering the Control Outputs option, select
Dechlorination from the menu. This will allow the
programming of the following:
Control Input (Operator): This option is only
available if the ppm probe is installed. Choose between
ppm and ORP to use to control the dechlor feed.
Follow Super Chlorination (Operator): Choose
whether or not you want your dechlorination to
automatically follow your super chlorination.
4 Event 28 Day Timer (Operator): The 4 Event
28 Day Timer allows you to program the
dechlorination on a schedule. See the section on
Super Chlorination's 4 Event 28 Day Timer for
details on how to set this.
Maximum Time On (Operator): This value sets
the maximum time you want the dechlorination on
to reach the set point. (the range is from 0:00 to
18:00 hours)
ORP Set Point (Operator): This option is only
shown if the Control Input is set to ORP. This value sets
the desired final ORP level. (the range is from
ORP low alarm point to the ORP high alarm
point)
ppm Set Point (Operator): This option is only
shown if the Control Input is set to ppm. This value sets
the desired final ppm level. (the range is from ppm
low alarm point to the ppm high alarm point)
Factory Defaults (Rep): This option allows you
to reset the controller back to the factory defaults
for all of the dechlorination settings.
Page 36
Rev: B09
C – 6.7: Ozone Control
After entering the Control Outputs option, select
Ozone Control from the menu. This will allow the
programming of the following:
Control Input (Operator): This option is only
available if the ppm probe is installed. Choose between
ppm, ORP, or both to use to control the Ozone
feed.
ORP Set Point (Operator): This option is only
shown if the Control Input is ORP or Both. This value
sets the ORP level that the input must drop below
to activate the Ozone. (the range is from ORP low
alarm point to the ORP high alarm point)
ppm Set Point (Operator): This option is only
shown if the Control Input is ppm or Both. This value
sets the ppm level that the input must drop below
to activate the Ozone. (the range is from ppm low
alarm point to the ppm high alarm point)
ORP Hysteresis (Operator): This option is only
shown if the Control Input is ORP or Both. This value
sets the level that the input must rise above the set
point before the Ozone control will turn off the
relay. (the range is from 0 to 200 mV)
ppm Hysteresis (Operator): This option is only
shown if the Control Input is ppm or Both. This value
sets the level that the input must rise above the set
point before the Ozone control will turn off the
relay. (the range is from 0.0 to 2.0 ppm)
Fireman Switch (Operator): This option is only
shown if a relay is assigned to the recirculation pump. This
value sets the minimum amount of time to leave
the recirculation pump on after the Ozone relay
shuts off.
Label (Rep): Allows you to change the name of
this control. There is a 12 character maximum.
Failsafe Timer (Operator): This value sets the
time that the relay is allowed to stay continuously
on. (the range is 0:00 to 18:00 hours)
Factory Defaults (Rep): This option allows you
to reset the controller back to the factory defaults
for all of the Ozone Control settings.
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
C – 6.8: Heater
After entering the Control Outputs option, select
Heater Control from the menu. This will allow the
programming of the following:
Temp. Ctrl Enable (Operator): Enables or
disables controlling the Heater using the
Temperature Input.
Set Point (Operator): Only shown if Temp. Ctrl is
enabled. This value sets the desired temperature.
(the range is from the temperature low alarm to
the temperature high alarm)
Failsafe Timer (Operator): Only shown if Temp.
Ctrl is enabled. This value sets the time that the
relay is allowed to stay on without reaching set
point before the relay is locked out. If the heater
has been trying to achieve set point without
success for the selected time, the controller will cut
power to the heater, flash the Reset Fail/Safe LED
on the face panel and display a message to alert the
operator. (the range is 0:00 to 18:00 hours)
An operator must reset the failsafe through
the Reset Fail/safe button to re-enable normal
control.
Fireman Switch (Operator): This option is only
shown if a relay is assigned to the recirculation pump. This
value sets the minimum amount of time to leave
the recirculation pump on after the heater shuts
off.
Hysteresis (Operator): Only shown if Temp. Ctrl is
enabled. This value sets the level that the input
must rise above the set point before the heater
control will turn off. (the range is from 0 to 18 °F
or 0 to 10 °C)
Alternate Temperature (Operator): Only shown if
Temp. Ctrl is enabled. The 4 Event 28 Day Timer
allows you to program an alternate set point on a
schedule. See the Chlorine (Bromine) Control's
Alt Set Point for details on how to set this.
After the schedule is set, you may choose the
alternate temperature set point option and enter
the desired setting.
Factory Defaults (Rep): This option allows you
to reset the controller back to the factory defaults
for all of the Heater settings.
Rev: B09
C – 6.9: Polymer
After entering the Control Outputs option, select
Polymer Control from the menu. This will allow
the programming of the following:
The polymer control is controlled by the
Turbidity 4-20 mA input and will not trigger
until the turbidity reading remains above the
High Set Point for the Trigger Delay Time.
The control cycle time is fixed at 10 minutes,
but the user sets the actual feed On Time.
The control cycle will repeat every 10 minutes
until Low set point is achieved.
The polymer feed will not trigger until 10
minutes after the last backwash cycle.
High Set Point (Operator): When the turbidity
reading rises above this value for the Trigger Delay
Time, the controller will trigger the polymer
control cycle.
Low Set Point (Operator): At the end of each
10 minute control cycle, the controller checks to
see if the turbidity reading is below this value. If it
is, the control cycle ends, otherwise the controller
starts a new control cycle.
On Time (Operator): This value sets how long
the controller will feed polymer during each 10
minute control cycle.
Trigger Delay Time (Operator): This value sets
how long the turbidity reading must remain above
the high set point before triggering the polymer
control cycle.
Failsafe Timer (Operator): This value sets the
time that the control is allowed to stay active
without reaching set point before the relay is
locked out. If the polymer feed has been trying to
achieve set point without success for the selected
time, the controller will end the control cycle, flash
the Reset Fail/Safe LED on the face panel and
display a message to alert the operator. (the range
is 0:00 to 18:00 hours)
An operator must reset the failsafe through
the Reset Fail/safe button to re-enable normal
control.
Factory Defaults (Rep): This option allows you
to reset the controller back to the factory defaults
for all of the Polymer Control settings.
Page 37
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
C – 6.10: Autofill
After entering the Control Outputs option, select
Autofill from the menu. This will allow the
programming of the following:
Set Point (Operator): Only shown if Autofill sensor
type is set to Surge Pit Level. This value sets the surge
pit level that the controller will fill to. (the range is
from the surge pit low alarm point to the surge pit
high alarm point)
Alternate Set Point (Operator): Only shown if
Autofill sensor type is set to Surge Pit Level. To
program when to use the alternate set point, see
the section on Chlorine (Bromine) Control’s
Alternate Set point Timer Settings. After the
schedule is set, you may choose the alternate set
point option and enter the desired setting.
Hysteresis (Rep): Only shown if Autofill sensor type
is set to Surge Pit Level. This value sets the level that
the input must rise above the set point before the
Autofill will close the valve. (the range is from 0 to
10% of the surge pit level's input range)
Overfill Delay (Operator): This is a timer that
sets how long the Autofill should continue filling
after the set point has been reached (the input
range is from 0 seconds to 1 hour). In order to
disable this, set the timer to 0 seconds.
Failsafe Timer (Operator): This value sets the
time that the relay is allowed to stay on without
reaching set point before the relay is locked out. If
Autofill has been trying to achieve set point
without success for the selected time, the
controller will cut power to the relay, flash the
Reset Fail/Safe LED on the face panel and display
a message to alert the operator. (the range is 0:00
to 18:00 hours)
An operator must reset the failsafe through
the Reset Fail/safe button to re-enable normal
control.
Factory Defaults (Rep): This option allows you
to reset the controller back to the factory defaults
for all of the Autofill settings.
C – 6.11: TDS Control
After entering the Control Outputs option, select
TDS Control from the menu. This will allow the
programming of the following:
Makeup water TDS (Operator): Enter the test
kit TDS reading for the water controlled by your
Autofill. This is used to determine the appropriate
TDS set point. (the range is 0 to 5000 ppm)
Page 38
Rev: B09
Pool TDS cycle (Operator): Enter the pools'
cycle multiplier of the incoming makeup water.
The resulting TDS set point is the incoming
makeup water's TDS times this value. (range is 2.0
to 9.9)
Hysteresis (Rep): This value sets the level that
the TDS Input must fall below the set point before
the TDS control will close the drain valve. (the
range is from 0 to 1000 ppm)
Failsafe Timer (Operator): This value sets the
time that the relay is allowed to stay on without
reaching set point before the relay is locked out. If
the TDS control has been trying to achieve set
point without success for the selected time, the
controller will cut power to the relay, flash the
Reset Fail/Safe LED on the face panel and display
a message to alert the operator. (the range is 0:00
to 18:00 hours)
An operator must reset the failsafe through
the Reset Fail/safe button to re-enable normal
control.
Factory Defaults (Rep): This option allows you
to reset the controller back to the factory defaults
for all of the TDS Control settings.
C – 6.12: Sensor Wash
After entering the Control Outputs option, select
Sensor Wash from the menu. This will allow the
programming of the following:
4 Event 28 Day Timer (Operator): Once you
have entered Sensor Wash, select 4Event 28Day
Timer from the menu. The 4 Event 28 Day Timer
allows you to program the sensor wash on a
schedule. See the section on Super Chlorination's 4
Event 28 Day Timer for details on how to set this.
Start/End Time (Operator): Allows you to
set what times the feed may be triggered during
a day.
# Of Cycles (Operator): Sets how many
times the relay will trigger between the Start
and End times.
Duration (Operator): Sets how long the feed will
run for each cycle.
Label (Rep): Allows you to change the name of
this control. There is a 12 character maximum.
Factory Defaults (Rep): This option allows you
to reset the controller back to the factory defaults
for all of the Sensor Wash settings.
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
C – 6.13: Enzyme
After entering the Control Outputs option, select
Enzyme from the menu. This will allow the
programming of the following:
Start/End Time (Operator): Allows you to set
what times the feed may be triggered during a day.
# Of Cycles (Operator): Sets how many times
the relay will trigger between the Start and End
times.
Duration (Operator): Sets how long the feed will
run for each cycle.
Label (Operator): Allows you to change the
name of this control. There is a 12 character
maximum.
Factory Defaults (Rep): This option allows you
to reset the controller back to the factory defaults
for the Enzyme feed settings.
C – 6.14: Alarm Relay
There are no programmable options for the Alarm
Relay. Whenever there is an alarm or Emergency
Off is active, this relay will turn on.
C – 6.15: Recirculation Pump
After entering the Control Outputs option, select
Recirculation Pump from the menu. This will
allow the programming of the following:
Pres. Alarm Delay (Operator): Delay pressure
and vacuum alarms from triggering for this
amount of time whenever the recirc pump starts
up.
Heater Fireman Switch (Operator): This option
is only shown if a relay is assigned to the Heater control.
This value sets the minimum amount of time to
leave the recirculation pump on after the heater
shuts off.
Ozone Fireman Switch (Operator): This option
is only shown if a relay is assigned to the Ozone control.
This value sets the minimum amount of time to
leave the recirculation pump on after the Ozone
relay shuts off.
VFD Control (Operator):
Allows you to
configure the VFD control settings for the
Recirculation Pump. Once you have selected
VFD Control you will have the following items to
choose from:
Control Input (Operator): Allows you to
select the input to use for VFD control.
Turndowns (Operator):
Allows you to
configure scheduled and manual turndowns.
Ramp up rate (Rep): Allows you to set the
rate which the output will ramp up in % per
second. Setting the value to 100% disables
ramping up.
Rev: B09
Ramp down rate (Rep): Allows you to set
the rate which the output will ramp up in %
per second. Setting the value to 100% disables
ramping down.
OOR alarm delay (Operator): This option is
only shown if the Control Input is set to Flow Meter.
If the output required to meet the set point
exceeds 100%, the triggering of the Out Of
Range (OOR) alarm will be delayed by this
amount of time. Set to 0 to disable the alarm.
Set Point (Operator): Allows you to set the
value to control to. (in %, flow rate, or
pressure units depending on what the control
input is set to).
Dead Band (Operator): This option is only
shown if the Control Input is set to Flow Meter. The
VFD output will not change until the input is
this far away from the set point.
Minimum Output (Rep): Allows you to set
the minimum percent output allowed.
Auto Tune (Rep): This option is only shown if the
Control Input is set to Flow Meter. Selecting this
option allows the controller to begin the tuning
sequence around the current output.
Warning: Adjust these options only when
recommended to do so by BECS Technology.
Dead Time (Rep: Change/Operator: View
Only): This option is only shown if the Control Input
is set to Flow Meter. This option should not be
changed unless requested by BECS
Technology.
Prop. Band (Rep: Change/Operator: View
Only): This option is only shown if the Control Input
is set to Flow Meter. This option should not be
changed unless requested by BECS
Technology.
Kp (Rep): This option is only shown if the Control
Input is set to Flow Meter. This option should not
be changed unless requested by BECS
Technology.
Ki (Rep): This option is only shown if the Control
Input is set to Flow Meter. This option should not
be changed unless requested by BECS
Technology.
Kd (Rep): This option is only shown if the Control
Input is set to Flow Meter. This option should not
be changed unless requested by BECS
Technology.
Factory Defaults (Rep): This option allows
you to reset the controller back to the factory
defaults for all of the Recirculation Pump
settings.
Page 39
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
C – 7: Control Options
Press Menu on the controller’s face panel and select
Control Options from the menu.
This will allow the programming of the following:
C – 7.1: Flow Restored
After you have entered the Control Options
section, select Flow Restored from the menu. This
will allow for the programming of the following:
Enable / Disable (Operator): Once you have
entered the Flow Restored option, select Enable /
Disable from the menu. Here you will be able to
select whether you want to delay the chemical
feeders after flow is restored to the system.
Delay Duration (Operator): This option is only
available if flow restored feed delay is enabled. Once you
have entered the Flow Restored option, and
selected to enable this option, you can select Delay
Duration and enter the desired time that the
chemical feeders must wait to operate after flow is
restored. (the range is from 0:00 to 60:00 minutes)
C – 7.2: Power Saver
Power Saver is a timer triggered function that
saves energy by shutting down the recirculation
pump for programmable periods of time while the
pool is not in use.
When active, power saver has the following states:
• CONTROLLING:
At least one control
function is currently feeding. Once all feeds
have finished, the system will enter the
GOING TO SLEEP state.
• GOING TO SLEEP: All control functions
must be satisfied (they don't turn their feeds
on) for the Enter Sleep Delay duration before
allowing system to enter the SLEEPING
state.
• SLEEPING: Timed period (Sleep Duration)
where the shutdown of recirculation pump is
triggered and all feeds are disabled. After
entering SLEEPING state, the recirculation
pump will continue to run until the heater and
ozone fireman switch timers run out. The
sleep timer starts when all conditions have
been met, not when controller shuts down the
recirculation pump. Only a timer triggered
backwash, the sleep timer expiring, or the
Power Saver timer expiring will put the
system into the WAKING UP state. No
feeds or input alarms will operate while the
system is asleep or waking up.
Page 40
Rev: B09
• WAKING UP: Timed period (Exit Sleep
Delay) where the recirculation pump is ran
before allowing feeds to operate. Once the
wake up time expires, if the Power Saver
timer expired, the system will remain awake
even if all feeds are satisfied. Otherwise the
system enters the CONTROLLING state,
performing a backwash if triggered, and will
reenter GOING TO SLEEP again once all
feeds have been satisfied again.
While Power Saver is active, the system
automatically uses the Alternate Temperature
set point for the Heater and the Alternate
ORP and/or Alternate ppm set points for the
Cl feed.
Enable (Operator): Enable or disable the Power
Saver feature.
4 Event 28 Day Timer (Operator): The 4 Event
28 Day Timer allows you to program power
saver's schedule. See the section on the Chlorine
(Bromine) Control's Alt Set Point for details on
how to set this.
Sleep Duration (Operator): Sets how long the
controller will sleep.
Enter Sleep Delay (Operator): Sets how long to
wait after all of the feeds have been satisfied
before entering SLEEP (i.e. the GOING TO
SLEEP duration). If any feed starts feeding during
this time, the controller goes back to the
CONTROLLING state.
Exit Sleep Delay (Operator): Sets how long to
wait after coming out of sleep before allowing any
feeds to run. (i.e. the WAKING UP duration).
Alternate ORP (Operator): Sets the alternate
ORP value used during power saver and the Cl
feed's alternate set point event timer.
Alternate ppm (Operator): Sets the alternate
ppm value used during power saver and the Cl
feed's alternate set point event timer.
Alternate temp (Operator): Sets the alternate
temperature value used during power saver and the
heater's alternate set point event timer.
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
C – 7.3: pH Lockout
pH lockout (Manager) disables the sanitizer feed
when a pH high and/or low alarm is activated:
Full lockout:
The Cl (Br) feed is disabled
when either a pH high or low
alarm occurs.
Feed direction: For pH feed up, the Cl (Br)
feed is disabled on a pH low
alarm.
For pH feed down, the Cl (Br)
feed is disabled on a pH high
alarm.
Disable:
pH alarms do not disable the
Cl
(Br)
feed.
(Not
Recommended)
Warning: Disabling the pH lockout will allow
for chemical overfeeds which may damage
equipment or harm patrons.
C – 8: Calculations
Press Menu on the controller’s face panel and select
Calculations from the menu.
This will allow the programming of the following:
C – 8.1: Enter Parameters
By selecting this, the controller will step you
through entering the values for Pool Volume,
whether it should use TDS for calculations,
Calcium Hardness, and Alkalinity. Once the values
have been entered, the calculated LSI & Ryzner
reading will appear in the menu and on the display.
C – 8.2: LSI Setup
Use TDS?: Selects if the controller should use
TDS for the LSI/RSI calculations.
Pool Volume: Allows you to enter the volume of
the pool.
Display RSI/LSI: Allows you to select if the
RSI/LSI information is displayed on the routine
display.
C – 9: System Configuration
Press Menu on the controller’s face panel and select
System Configuration from the menu.
This will allow you to configure the following for the
system:
C – 9.1: SN
This shows the controller serial number. By
selecting this menu, you are shown the System
Info. This includes the System type and the Serial
Number.
Rev: B09
C – 9.2: Communication
Once you have entered System Configuration,
select Communication from the menu. Under
communication, you can select from the following.
C – 9.2.1: Direct Baud Rate (Operator)
This option is only shown if a BECSys Ethernet card is
NOT installed. Here you can choose the desired
direct connect baud rate for the system.
C – 9.2.2 Modem type (Read Only)
This option is only shown if a BECSys Ethernet card is
NOT installed. Shows the type of modem
installed in the controller.
C – 9.2.3 Modem Options (Rep)
This option is only shown if a 56K BECSys modem is
installed. Selecting this option allows you to
disable the V.92 mode of the modem. This may
be useful if you are having trouble connecting to
the controller from another analog modem.
C – 9.2.4: Ethernet Setup (Operator)
This option is only shown if a BECSys Ethernet card is
installed. These parameters should be set to
values provided by the network’s administrators.
Enable DHCP – Enables/disables using
DHCP. If DHCP is enabled, the controller will
retrieve its IP address information from a
DHCP server on the network. If DHCP is
disabled, the IP address information must be set
manually via the remaining items listed here.
IP Address - This option is only shown if DHCP is
disabled. Sets the controllers IP address.
IP Netmask - This option is only shown if DHCP
is disabled. Sets the controllers IP netmask.
IP Default Route - This option is only shown if
DHCP is disabled. Sets the controllers IP default
route/gateway.
SMTP Server Addr - Sets the email SMTP
server address used by alarm call-out to send
email and text messages.
SMTP Server Port - Sets the email SMTP TCP
port. This value should be set to 25 unless
otherwise
instructed
by
a
network
administrator.
DNS Server 1 - Sets the IP address for the
primary DNS server. Required for email callouts.
DNS Server 2 - Sets the IP address for the
secondary DNS server which is only used if
DNS server 1 cannot be contacted.
Page 41
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
C – 9.2.5: Call Out Setup (Operator)
This option is only shown if a BECSys Ethernet card or
modem is installed.
Here you can set the
parameters for the alarm call-out functions.
Call Out Enable – Here you can choose to
enable call outs.
Call Start Time – Here you can set the time
the controller will start allowing call outs.
Call End Time – Here you can set the time the
controller will stop allowing call outs.
Ack. Page outs – Allows the controller to
determine if somebody is responding to the
page. If somebody receives the page and calls
the controller this stops the controller from
calling the remaining page phone numbers.
Pre-Delay – Here you can set the amount of
time the controller will delay to allow for alarm
to reset before calling out. (the range is from
1:00 to 60:00 minutes)
Recipients Setup – Allows configuration of
eight recipients which can individually be
configured for fax, pager, email, or text message
call-out.
Call-Out Type:
• Pager: Requires a BECSys Ethernet Modem
card or a standard modem. Calls a numeric
pager and leaves a callback number.
After dialing the pager's number, the
controller will wait for five seconds of
silence before sending the callback
number.
• Fax: Requires a BECSys Ethernet Modem
card or a standard modem. Calls a fax
machine and sends a fax containing all
active alarms and the times they were
triggered.
• Email: Requires a BECSys Ethernet card
with functioning DNS and SMTP server
settings. Sends an email to the recipient's
email address containing all active alarms
and the times they were triggered.
• Text Message: Requires BECSys Ethernet
card with functioning DNS and SMTP server
settings. Sends a text message with a list of
active alarms to a text pager or cell phone
using email.
• Disabled: Disables the call-out recipient.
Pager Service # (pager) - This option is only
shown if the call-out type is set to pager. Enter the
recipient's pager phone number to dial. You
may use commas to add two second delays
in the dialing of the number. Example
9,1234567 will dial 9, wait two seconds, then
dial 1234567.
Page 42
Rev: B09
Callback # (pager) - This option is only shown
if the call-out type is set to pager. Enter a number
to leave as the callback number displayed on
the pager.
Fax Number (fax) – This option is only shown
if the call-out type is set to fax. Enter the phone
number of the recipient's fax machine. You
may use commas to add two second delays
in the dialing of the number. Example
9,1234567 will dial 9, wait two seconds, then
dial 1234567.
Email address (Email) – This option is only
shown if the call-out type is set to email. Enter the
recipients email address. Enter the local part
of the email address (the part before the @)
into the first screen, then enter the domain
part of the email address (the part after the
@) into the second screen.
Email address (text message) - This option
is only shown if the call-out type is set to text
message. The recipients email address for text
messaging is usually in the form of the
pager's
or
cell's
ten-digitnumber@domain.com
or
the
like.
(2223334444@txt.att.net). Enter the phone
number into the first screen, then enter the
domain part of the email address (the part
after the @) into the second screen. Check
with the recipient's wireless carrier for the
correct email address to use.
Post-Delay – The time to delay starting the
next recipient call-out after this recipient callout is triggered.
Test – Triggers a test call-out of the current
recipient only. Note you may only test one
recipient at a time.
Current State – Shows the current state of
the recipient's call-out when a call-out is in
progress.
Last Status – Shows the status of the
previous call-out for the selected recipient.
This is only updated when a call-out has
been completed. Some of the possible
results are: success, no dial tone, busy, no
answer, and no carrier.
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
C – 9.2.6: RS485 Network Setup (Rep)
Relay Exp. Boxes – Allows you to setup
communication to up to 3 Relay Expansion
Modules (either Mechanical or Solid State).
Each expansion module offers 5 additional
relays allowing up to 24 total relays.
Relay Exp. Box 1 – Enables or disables
communications to this relay expansion box.
Do not enable this option unless you have a
relay expansion module configured as box 1
connected to the RS485 network.
Relay Exp. Box 2 – Enables or disables
communications to this relay expansion box.
Do not enable this option unless you have a
relay expansion module configured as box 2
connected to the RS485 network.
Relay Exp. Box 3 – Enables or disables
communications to this relay expansion box.
Do not enable this option unless you have a
relay expansion module configured as box 3
connected to the RS485 network.
C – 9.2.7: Installed Options
This screen lists the currently supported
notification hardware (modem and email) and
their current status.
C – 9.3: Datalog Frequency
Once you have entered System Configuration,
select Datalog Frequency (Operator) from the
menu. Here you can choose how often the
controller collects data. By setting the Datalog
Frequency longer, the more information the
controller can store, but the less detailed the
information is.
C – 9.4: Date, Time & Units
Once you have entered System Configuration,
select Date, Time & Units from the menu. Here
you can enter the values for the following:
Units (Operator): Here you can choose from
U.S. or Metric measurements.
Date Format (Operator): Here you can choose
the format for the date.
Current Date (Operator): Here you can set the
current date.
Current Time (Operator): Here you can set the
current time. Use the + / - key to toggle between
AM and PM.
Rev: B09
C – 9.5: Name and Location
Once you have entered System Configuration,
select Name and Location from the menu. Here
you can enter the information for the following:
Customer Name (Rep): Here you can enter the
customer’s name. This entry screen uses cell
phone-like alphanumeric key entry.
Location (Rep):
Here you can enter the
customer’s location. This entry screen uses cell
phone-like alphanumeric key entry.
Rep Name (Rep): Here you can enter the
representative’s name. This entry screen uses cell
phone-like alphanumeric key entry.
Rep Phone Number (Rep): Here you can enter
the representative’s phone number.
System ID (Rep): Here you can enter the
controller’s Unique ID number or serial number.
Display Info (Rep): Here you can configure
whether to show the Customer Name, Location,
Rep, and Rep Phone Number on the display.
C – 9.6: User Setup
Once you have entered System Configuration,
select User Setup from the menu. Here you can
enter the access codes for Operators, Managers
and the Representatives. You can enter 6 codes for
Operators, 2 codes for Managers and 1 code for
Representative.
See the section on Access Codes for more
information.
C – 9.7: Factory Defaults
Once you have entered System Configuration,
select Factory Defaults from the menu. Here you
can enter the information for the following:
Input Defaults - Here you can choose from the
list of Inputs that you want to reset to the factory
defaults.
Feed / Relay - Here you can choose from the list
of Feed / Relays that you want to reset to the
factory defaults.
Control Options - Here you can choose from the
list of Control Options that you want to reset to
the factory defaults.
Calculations - Here you can reset the LSI & RSI
Calculations to the factory defaults.
System Configuration - Here you can choose
from the list of System Configurations that you
want to reset to the factory defaults.
All Settings - Here you can choose to reset all
System Settings to the factory defaults.
Page 43
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
C – 9.8: Display Options
Once you have entered System Configuration,
select Display Options from the menu.
Page Delay (Operator): Here you can set the
delay for scrolling to the next page in the normal
display. These screens will only scroll when not in
a menu screen.
Info Screens (Operator): If this option is
enabled, pressing the number keys while in the
normal display will bring up detailed info about
different features.
Toggle LCD Mode (Operator): Toggles the
LCD display between negative and positive modes.
C – 10: 4-20mA Outs
If you have a 4-20 mA board installed in your system
you may choose 4-20mA outputs from the main
menu.
The 4-20mA output board allows you to connect to
either a building management system or to control a
VFD.
Rev: B09
Feed Set Points: By selecting Feed Set Points,
you can choose to output the current active pH
feed set point, ORP or ppm Cl/Br feed set point,
or the heater’s set point to output.
High Alarm Set Points: By selecting the High
Alarm Set Point, you can choose any available
input’s high alarm set point to output.
Low Alarm Setpoints: By selecting the Low
Alarm Set Point, you can choose any available
input’s low alarm set point to output.
C – 10.3: Factory Defaults
Selecting Factory Defaults allows you to reset the
controller back to the factory defaults for the
selected 4-20mA output channel.
C – 11: VFD Turndowns
VFD Turndowns allow you to trigger or cancel
manual turndowns (must have a manual turndown
enabled for this menu to appear). This will also
display the next scheduled turndown.
C – 12: Access Menu
Once the Rep and Operator access codes have been
set, the controller will require users to enter their
access code before allowing them to enter the menus
or set any values under the quick set keys. The
controller automatically displays the access screen
whenever a user does not have a high enough access
level to enter a specific screen.
By selecting one of the 4-20mA output channels you
will be able to select the following:
C – 10.1: Usage
Selecting Usage allows you to select what to use
the selected 4-20mA output channel for.
Recorder Out: Output a 4-20mA signal based on
one of the controller’s inputs, feed set points, or
alarm set points. Once you have selected Recorder
Out you will be returned to the main menu for the
4-20mA channel and you will be able to select the
source.
VFD Control Out: Use this channel to control a
VFD unit connected to the recirculation pump.
Disable: Disables the 4-20mA output.
C – 10.2: Source (Recorder Out)
To enter an Operator access code, press 1.
To enter a Manager access code, press 2.
To enter the Rep access code, press 9.
Inputs: By selecting inputs you can choose any
assigned input to output the value on the selected
4-20mA output channel.
If at anytime you wish to logon as another access
level, you may do so by pressing the Menu key and
selecting Logon from the main menu.
Page 44
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Rev: B09
Section D: The Normal Display
The normal display refers to the screens that display all
of your inputs, current alarms, and status messages.
These are read only and do not offer any selections to
chose from.
D – 1: Inputs and Feeds
information in this area as well. If there are any
active alarms while one or more of these control
functions' are active, the alarms will be shown every
other page while the control functions will alternate
with each other.
When no alarms or status messages are present, the
entire screen will be used to display all of the enabled
inputs. If a particular input is used by a control
output and the control output is feeding based off of
that input, the controller will display a message next
to that input indicating so.
Other information such as LSI/RSI calculated values
and Customer/Location/Rep information may also
be displayed.
If there are more items to show than there is room
for, the controller the controller will page through
them until they all have been displayed, then start
over.
Pressing the right arrow key (Next) will
display the next page.
Pressing the Lock Screen button will prevent
the controller from paging the screen to show
more inputs, alarms, and other status
information.
You can adjust the rate at which the controller
pages by pressing the up and/or down arrow
keys.
D – 2: Alarms & Status messages
When one or more alarms are active, the bottom
three lines are used to list them. If more than three
alarms are active, the controller will page through
them three at a time until they all have been
displayed, then start over.
Super chlorination, dechlorination, sensor wash,
backwash, and power saver all display status
Page 45
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Rev: B09
Section E: Using the Face Panel Quick Keys
E – 1: The Set Points Key
The Set Points Key on the front face panel, when
pressed, allows you to quickly change desired feed set
points for the various control outputs that are
enabled.
By selecting one of the assigned relays, you are
allowed to choose between automatic, manual on or
manual off. Unused relays and the alarm relay
cannot be manually overridden, but their current
state is always displayed.
To change the existing feed set point, first select the
desired option, input the new value, and then press
enter.
Pressing the Set Points key a second time will display
the alarm set points for all of the enabled inputs.
To change the existing alarm set point, first select the
desired option, input the new value, and then press
enter.
E – 2: The Relay Mode Key
Pressing the Relay Mode key on the front face panel
shows you which options have been assigned relays,
and each of the relays' current mode
(AUTO/MANUAL OFF/MANUAL ON) and its
state (Off or On).
Pressing the Relay Mode key again will cycle through
the Relay Modules connected to the controller,
showing what is assigned to those relays and their
current state.
Page 46
If Manual On is selected, you will be prompted to
enter how long the relay can stay in Manual On
before returning to Auto (the maximum on time is
30 minutes).
To test a relay or to prime a pump (on the
local relay screen), lock the screen while in the
main Relay Mode menu, then press the relay's
numeric key (i.e., for relay 3, press the 3 key).
This will turn the relay on for as long as you
are pressing that key. If the relay is already
on, this will have no affect.
The Relay Expansion modules have a button
to test the relays.
If you have the controller set up to control a VFD,
pressing the Relay Mode Key again will display the 420mA Control Outputs.
From here you can switch between auto and manual
on. There are two different manual on options:
Manual % Out and Manual Flow Rate.
Manual % Out sets the VFD output at a specified
value.
Manual Flow Rate changes the VFD output to
maintain a specified flow rate.
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Rev: B09
E – 3: The Cal Key (calibration)
The Cal (calibration) key on the front face panel,
when pressed shows you the inputs you can perform
a single point calibration. The standard inputs that
can be calibrated are pH and ORP. Any other inputs
you have enabled can also be calibrated from this
Menu screen. Select the input you wish to calibrate
and enter the proper value.
ORP can only be calibrated by Rep.
Perform a single point calibration if the
reading is off by a consistent amount
throughout the input range.
If the readings are accurate at one reading,
but are off by an increasing amount the
farther away you go from that reading, check
the wiring and the condition of the probe (if
applicable). If the problem is not found, you
may need to do a two-point calibration
located in the input's menu under the Menu
button.
E – 4: The Reset Fail / Safe Key
The Reset Fail / Safe key on the front face panel,
when pressed, lists any active failsafe alarms and
allows you to reset them. A failsafe alarm is generally
triggered when one of the relays has remained on
past the set time the function has been given to reach
its set point. By choosing to reset the failsafe, the
control that triggered the failsafe will be able to
resume operating normally once again.
Warning: Before resetting the Failsafe
Alarm, ensure that all functions of the
controller are working properly.
E – 5: The Emergency Off Key
When the Emergency Off button is pressed, all
relays are automatically shut off except for the alarm
relay which will turn on. All the other relays will
remain off until the emergency off button is press
again.
Page 47
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Rev: B09
Section F: Maintenance
The BECSys5 requires no maintenance other than a
periodic calibration check and sensor cleaning.
F – 1: Potentiometric Sensors (pH and ORP)
F – 1.1: Electrode Cleaning
Slow response time and large offsets may indicate the
electrode has become coated. The nature of the
coating will dictate the type of cleaning technique
that should be used.
Warning: You may lightly blot the water
On a pH sensor tip on a paper towel, but never
vigorously rub or wipe the pH bulb because this
may scratch the delicate outer layer on the pH
glass impairing its response.
Soft coatings, like bacterial films, are best removed
using a squirt bottle or the water jet from a faucet.
If this is not successful, then gently wipe with a
soft wet cloth.
For a more severe coating, first try a strong
detergent (something similar to Dawn liquid
detergent) and warm water, using a soft brush (like
a toothbrush). Isopropyl alcohol on a Q-tip is
another good choice. Rinse the measuring end in
distilled water before reinstallation.
Greasy and oily coatings are best removed with a
detergent solution or a solvent that will not attack
the sensor body. Methanol and isopropyl alcohol
are good choices for solvents. Acetone, MEK,
THF, or trichloroethane will irreparably harm the
electrode.
Hard coatings, like calcium or lime scale, are best
removed with a solvent appropriate for the
particular coating. A 5% solution of hydrochloric
acid (HCl) would be a good choice for calcium
scale. If unsure of the proper solvent to remove a
hard mineral coating, then alternate between a 5%
hydrochloric acid and a 4% sodium hydroxide
(NaOH) for 10 minutes each. After treating the
electrode with these strong acids or bases, rinse the
electrode with water and soak it in a pH 4 buffer
for at least 1/2 hour.
The platinum tip of an ORP sensor can be cleaned
with an abrasive as a last resort. Gently scour the
platinum with a 600 grit wet emery cloth, or
preferably, a 1-3 micron alumina polishing powder.
F – 1.2: Long-Term Storage
Save the wetting cap that came with the sensor for
long-term storage. After removing the sensor
from the flow cell, clean it as in routine
maintenance, then store it in the wetting cap using
Page 48
a pH 4 buffer saturated with potassium chloride
(KCl). The potassium chloride will prevent
electrolyte from leaching out of the sensors
reference cell. The wetting cap only needs to be
half full. If a number of sites are going to be
serviced, for example, at the end of a season, then
it might be a good idea to carry a pint of 4.0/KCl
storage solution.
F – 2: Free Chlorine Sensor
Check the sensor measurement at regular intervals (at
least once a month), and perform a recalibration if
necessary.
As a rule of thumb, refill the measuring cell with
electrolyte once per season (or every 12 months).
F – 2.1: Cleaning
If the sensor membrane is visibly soiled, then
remove the sensor from the flow cell and clean the
membrane with a gentle water jet, or soak the
membrane for a few minutes in a 1% to 10%
hydrochloric acid (HCl) solution. Avoid chemical
additives as they may damage the membrane.
Replace a heavily soiled or damaged membrane.
F – 2.2: Long-Term Storage
Save the yellow protective cap that came with the
sensor for long-term storage. After removing the
sensor from the flow cell, empty the measuring cell
of electrolyte (particularly if dehydration of the
membrane is possible). Rinse the measuring
chamber and electrode shaft with cold water and
let them dry. Then screw the measuring cell down
loosely and not to the stop, so that the membrane
remains unstressed. When the sensor is put back
into service, it will have to be refilled with
electrolyte and run through an initial polarization
before calibration.
F – 2.3: Filling electrolyte
Unscrew the measuring chamber from the shaft.
Hold the measuring chamber at an angle and fill in
approximately 7 to 8 ml electrolyte, up to
approximately 1 cm under the top edge.
Tap the filled chamber several times on a flat
surface to release any air bubbles.
Screw the electrode shaft into the measuring
chamber vertically from above, displacing all air
from inside. Tighten slowly to the stop.
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Rev: B09
F – 3: Conductivity Sensor
F – 3.1: Cleaning
The sensor should be kept as clean as possible for
optimum measurement accuracy. The frequency
of cleaning will depend upon the application.
Warning: Residue from cleaning solutions, or
even skin contact, can leave trace elements on
the sensor that may affect the reading,
When necessary, wash with strong detergent
(something similar to Dawn liquid detergent) and
warm water, using a pipe cleaner or small soft
brush for most fouling. Rinse with tap water to
completely remove the detergent, and then
perform a final rinse with distilled or de-ionized
water.
For hard scale, try a mild acid solution. Vinegar
will often do it, 5% hydrochloric acid if the vinegar
doesn’t work. You can use acetone or something
similar on this sensor.
Warning: Do not soak the sensor in a strong
solvent as the O-rings may be attacked after
time.
Page 49
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Rev: B09
Section G: Tables
G – 1: Flow Meter K-Factors
G – 1.1 Schedule 40 PVC Pipe
G – 1.2 Schedule 80 PVC Pipe
+GF+Signet 515
+GF+Signet 2536
Pipe Size
(red)
(blue)
(in)
U.S. GAL LITERS U.S. GAL LITERS
SCH 80 PVC SADDLE ON SCH 40 PVC PIPE
2
27.350
7.226
54.700
14.452
2-1/2
18.874
4.987
37.159
9.818
3
12.638
3.339
23.697
6.261
4
6.728
1.778
13.456
3.555
6
3.730
0.985
7.459
1.971
8
2.153
0.569
4.529
1.197
10
1.350
0.357
2.800
0.740
12
0.960
0.254
1.980
0.523
PP CLAMP-ON SADDLE ON SCH 40 PP PIPE
10
1.350
0.357
2.800
0.740
0.960
0.254
1.980
0.523
12
SCH 80 IRON SADDLE ON SCH 40 PIPE
2
26.820
2-1/2
18.800
3
11.990
4
6.850
5
5.330
6
3.760
8
2.130
10
1.350
12
0.960
WELDOLETS ON SCH 40 PIPE
2-1/2
18.800
3
12.170
4
6.960
5
5.260
6
3.690
8
2.130
10
1.350
12
0.960
Page 50
7.086
4.967
3.168
1.810
1.408
0.993
0.563
0.357
0.254
53.640
37.600
23.220
13.260
11.040
7.240
4.400
2.800
1.980
14.172
9.934
6.135
3.503
2.917
1.913
1.162
0.740
0.523
4.967
3.215
1.839
1.390
0.975
0.563
0.357
0.254
37.600
24.340
13.920
10.860
7.520
4.340
2.760
1.940
9.934
6.431
3.678
2.869
1.987
1.147
0.729
0.513
+GF+Signet 515
+GF+Signet 2536
(red)
(blue)
U.S. GAL LITERS U.S. GAL LITERS
SCH 80 PVC TEES FOR SCH 80 PVC PIPE
1
174.670
46.148 352.440
93.114
1-1/4
83.390
22.032 177.180
46.812
1-1/2
58.580
15.477 117.850
31.137
2
32.480
8.581
66.739
17.633
2-1/2
21.833
5.768
42.994
11.359
3
13.541
3.578
26.652
7.041
4
7.626
2.015
15.006
3.965
SCH 80 PVC SADDLES FOR SCH 80 PVC PIPE
2
32.480
8.581
66.739
17.633
2-1/2
21.833
5.768
42.994
11.359
3
13.541
3.578
26.652
7.041
4
7.626
2.015
15.006
3.965
6
4.162
1.100
8.325
2.199
8
2.371
0.626
5.016
1.325
10
1.530
0.404
3.060
0.808
12
1.060
0.280
2.160
0.571
PP CLAMP-ON SADDLE ON SCH 80 PP PIPE
10
1.530
0.404
3.060
0.808
12
1.060
0.280
2.160
0.571
Pipe Size
(in)
SCH 80 IRON SADDLES ON SCH 80 PIPE
2
32.360
2-1/2
22.220
3
13.420
4
7.660
5
5.860
6
4.090
8
2.330
10
1.530
12
1.060
8.550
5.871
3.546
2.024
1.548
1.081
0.616
0.404
0.280
64.720
42.480
26.420
14.700
12.180
8.440
4.900
3.060
2.160
17.099
11.223
6.980
3.884
3.218
2.230
1.295
0.808
0.571
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Rev: B09
Section H: Feed Charts
Use the charts on the following pages to determine the correct amount of chemical to add to spa or pool water to
achieve desired conditions. Choose which chart to use by the chemical indicated and the number of gallons to be
treated.
H – 1: Spa Feed Charts
Quantity of Muriatic Acid Needed to Lower Total Alkalinity
Desired
Decrease
In ppm
10
20
30
40
50
60
70
80
90
100
100
1.25 ts
2.50 ts
1.25 tb
5.00 ts
2.00 tb
2.50 tb
3.00 tb
3.50 tb
0.25 cp
0.25 cp
ts = teaspoon
Gallons in Spa
150
250
500
750
1000
2.00 ts 1.00 tb 2.00 tb 3.00 tp 0.25 cp
4.00 ts 2.00 tb 0.25 cp 0.33 cp 0.50 cp
2.00 tb 3.00 tb 0.33 cp 0.67 cp 0.75 cp
2.50 tb 0.25 cp 0.50 cp 0.75 cp 1.00 cp
3.00 tb 5.00 tb 0.67 cp 1.00 cp 1.33 cp
0.25 cp 0.33 cp 0.75 cp 1.00 cp 1.50 cp
0.25 cp 0.50 cp 1.00 cp 1.33 cp 1.75 cp
0.33 cp 0.50 cp 1.00 cp 1.50 cp 2.00 cp
0.33 cp 0.67 cp 1.00 cp 1.67 cp 2.33 cp
0.50 cp 0.67 cp 1.33 cp 2.00 cp 2.50 cp
tb = tablespoon cp = one cup (8 fl oz)
Quantity of Sodium Bisulfate Needed to Lower Total Alkalinity
Desired
Decrease
In ppm
10
20
30
40
50
60
70
80
90
100
100
1.50 ts
1.00 tb
1.50 tb
2.00 tb
2.50 tb
3.00 tb
0.25 cp
0.25 cp
0.33 cp
0.33 cp
ts = teaspoon
Gallons in Spa
150
250
2.50 ts
1.00 tb
1.50 tb 2.50 tb
2.50 tb 0.25 cp
3.00 tb 0.33 cp
0.25 cp 0.50 cp
4.50 tb 0.50 cp
0.33 cp 0.50 cp
0.33 cp 0.67 cp
0.50 cp 0.75 cp
0.50 cp 0.75 cp
tb = tablespoon
500
750
1000
2.50 tb 0.25 cp 0.33 cp
0.33 cp 0.50 cp 0.67 cp
0.50 cp 0.75 cp 1.00 cp
0.67 cp 1.00 cp 1.25 cp
0.75 cp 1.25 cp 1.50 cp
1.00 cp 1.50 cp 2.00 cp
1.00 cp 1.67 cp 2.25 cp
1.25 cp 2.00 cp 2.50 cp
1.50 cp 2.25 cp 3.00 cp
1.67 cp 2.50 cp 3.25 cp
cp = one cup (8 fl oz)
Quantity of Bicarbonate of Soda Needed to Raise Total Alkalinity
Quantity of Calcium Chloride Needed to Increase Calcium Hardness
Desired
Increase
In ppm
Desired
Increase
In ppm
10
20
30
40
50
60
70
80
90
100
100
1.25 ts
1.00 tb
1.50 tb
2.00 tb
2.50 tb
3.00 tb
3.50 tp
0.25 cp
0.33 cp
0.33 cp
ts = teaspoon
Gallons in Spa
150
250
2.00 ts
4.00 ts
1.50 tb 2.50 tb
2.00 tb 3.50 tb
3.00 tb 0.33 cp
3.50 tb 6.00 tb
0.25 tb 0.50 cp
0.35 cp 0.50 cp
0.33 cp 0.50 cp
0.50 cp 0.67 cp
0.50 cp 0.75 cp
tb = tablespoon
500
750
1000
2.50 tb 0.25 cp 0.33 cp
5.00 tb 0.50 cp 0.50 cp
0.50 cp 0.67 cp 1.00 cp
0.50 cp 1.00 cp 1.00 cp
0.75 cp 1.00 cp 1.50 cp
1.00 cp 1.33 cp 1.75 cp
1.00 cp 1.50 cp 2.00 cp
1.25 cp 1.75 cp 2.50 cp
1.33 cp 2.05 cp 2.75 cp
1.50 cp 2.25 cp 3.00 cp
cp = one cup (8 fl oz)
10
20
30
40
50
60
70
80
90
100
100
1.25 ts
2.50 ts
1.25 tb
4.00 ts
2.00 tb
2.50 tb
3.00 tp
3.50 tp
0.25 cp
0.25 cp
ts = teaspoon
Gallons in Spa
150
250
2.00 ts
1.00 tb
4.00 ts
2.00 tb
2.00 tb 3.00 tb
2.50 tb 0.25 cp
3.00 tb 5.00 tb
0.25 cp 0.33 cp
0.25 cp 0.50 cp
0.25 cp 0.50 cp
0.33 cp 0.33 cp
0.50 cp 0.67 cp
tb = tablespoon
500
750
1000
2.00 tb 3.00 tb 0.25 cp
0.25 cp 0.33 cp 0.50 cp
0.33 cp 0.67 cp 0.75 cp
0.50 cp 0.75 cp 1.00 cp
0.67 cp 1.00 cp 1.33 cp
0.75 cp 1.00 cp 1.50 cp
1.00 cp 1.33 cp 1.75 cp
1.00 cp 1.50 cp 2.00 cp
1.00 cp 1.67 cp 2.33 cp
1.33 cp 2.00 cp 2.50 cp
cp = one cup (8 fl oz)
Quantity of Chlorine Compound Needed to Increase 1 ppm
Percent
Chlorine In
Product
5
10
12
30
40
50
60
65
100
0.50 tb
0.25 tb
0.25 tb
0.25 tb
0.167 ts
0.167 ts
0.167 tb
0.100 ts
ts = teaspoon
Gallons in Spa
150
250
500
750
2.00 ts
1.25 tb
2.50 tb
0.25 cp
1.00 ts
2.00 ts
1.25 tb
2.00 tb
1.00 ts
0.50 tb
1.00 tb
1.50 tb
0.33 ts
0.75 ts
1.25 ts
2.00 ts
0.25 ts
0.500 ts
1.00 ts
1.50 ts
0.25 ts
0.375 ts
0.75 ts
1.25 ts
0.200 ts
0.375 ts
0.50 ts
1.00 ts
0.167 ts
0.250 ts
0.50 ts
0.75 ts
tb = tablespoon cp = one cup (8 fl oz)
1000
0.33 cp
2.50 tb
2.00 tb
2.50 ts
2.00 ts
1.50 ts
1.25 ts
1.00 ts
Page 51
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Rev: B09
H – 2: Pool Feed Charts
Desired Decrease
In ppm
10
20
30
40
50
60
70
80
90
100
120
150
200
Desired Increase
In ppm
10
20
30
40
50
60
70
80
90
100
Desired Increase
In ppm
10
20
30
40
50
60
70
80
90
100
150
200
Percent Chlorine
In Product
5
10
12
30
40
50
60
65
70
75
80
85
90
100
Page 52
10,000
1.30 pt
1.30 pt
1.95 qt
2.80 qt
3.25 qt
3.90 qt
1.14 gl
1.30 gl
1.48 gl
1.63 gl
1.96 gl
2.44 gl
3.25 gl
10,000
1.50 lb
3.00 lb
4.50 lb
6.00 lb
7.50 lb
9.00 lb
10.50 lb
12.00 lb
13.50 lb
15.00 lb
10,000
lb oz
1 4
2 8
3 12
5 0
6 4
7 8
8 12
10 0
11 4
12 8
18 12
25 0
10,000
3.2 cp
1.6 cp
1.33 cp
0.278 lb
0.209 lb
0.167 lb
0.139 lb
0.128 lb
0.119 lb
0.111 lb
0.104 lb
0.096 lb
0.093 lb
0.083 lb
Quantity of Muriatic Acid Needed to Lower Total Alkalinity
Gallons in Pool
25,000
50,000
75,000
100,000
200,000
1.62 qt
3.25 qt
1.22 gl
1.62 gl
3.25 gl
3.25 qt
1.62 gl
2.43 gl
3.25 gl
7.50 gl
1.22 gl
2.44 gl
3.86 gl
4.98 gl
9.76 gl
1.63 gl
3.25 gl
4.87 gl
6.50 gl
13.00 gl
2.03 gl
4.07 gl
6.10 gl
8.14 gl
16.28 gl
2.44 gl
4.88 gl
7.32 gl
9.76 gl
19.52 gl
2.84 gl
5.69 gl
8.54 gl
11.38 gl
22.76 gl
3.25 gl
6.50 gl
9.75 gl
13.00 gl
26.00 gl
3.66 gl
7.31 gl
10.96 gl
14.82 gl
29.24 gl
4.06 gl
8.12 gl
12.18 gl
16.24 gl
32.48 gl
4.88 gl
9.76 gl
14.64 gl
19.52 gl
39.00 gl
6.09 gl
12.18 gl
18.27 gl
24.40 gl
48.80 gl
8.12 gl
18.24 gl
24.36 gl
32.50 gl
65.00 gl
pt = one pt (16 fl oz) qt = one quart (32 fl oz) gl = one gallon (128 fl oz)
Quantity of Bicarbonate of Soda Needed to Raise Total Alkalinity
Gallons in Pool
25,000
50,000
75,000
100,000
200,000
3.75 lb
7.50 lb
11.25 lb
15.00 lb
30.00 lb
7.50 lb
15.00 lb
22.50 lb
30.00 lb
60.00 lb
11.25 lb
22.50 lb
33.75 lb
45.00 lb
90.00 lb
15.00 lb
30.00 lb
45.00 lb
60.00 lb
120.00 lb
18.75 lb
37.50 lb
56.25 lb
75.00 lb
150.00 lb
22.50 lb
45.00 lb
67.50 lb
90.00 lb
180.00 lb
26.25 lb
52.50 lb
78.75 lb
105.00 lb
210.00 lb
30.00 lb
60.00 lb
90.00 lb
120.00 lb
240.00 lb
33.75 lb
67.50 lb
101.25 lb
135.00 lb
270.00 lb
37.50 lb
75.00 lb
112.50 lb
150.00 lb
300.00 lb
lb =pounds of dry chemical
500,000
8.13 gl
16.20 gl
24.40 gl
32.50 gl
40.70 gl
48.80 gl
56.90 gl
65.00 gl
73.10 gl
81.20 gl
97.80 gl
121.80 gl
162.40 gl
750,000
12.20 gl
24.30 gl
36.60 gl
48.80 gl
61.00 gl
73.20 gl
85.45 gl
97.50 gl
109.60 gl
121.80 gl
148.40 gl
182.70 gl
243.80 gl
1,000,000
16.25 gl
32.50 gl
48.80 gl
65.00 gl
81.40 gl
97.80 gl
113.80 gl
138.00 gl
146.20 gl
162.40 gl
196.20 gl
244.00 gl
325.00 gl
500,000
75.00 lb
150.00 lb
225.00 lb
300.00 lb
375.00 lb
450.00 lb
525.00 lb
600.00 lb
675.00 lb
750.00 lb
750,000
112.50 lb
225.00 lb
337.50 lb
450.00 lb
562.50 lb
675.00 lb
787.50 lb
900.00 lb
1012.50 lb
1125.00 lb
1,000,000
150.00 lb
300.00 lb
450.00 lb
600.00 lb
750.00 lb
900.00 lb
1050.00 lb
1200.00 lb
1350.00 lb
1500.00 lb
750,000
lb oz
93 12
197 8
281 4
375 0
468 12
562 8
658 4
750 0
843 12
937 8
1,406 4
1,875 0
1,000,000
lb
125
250
375
500
625
750
875
1,000
1,125
1,250
1,875
2,500
750,000
15 gl
7.5 gl
6.245 gl
20.850 lb
15.645 lb
12.511 lb
10.425 lb
9.630lb
8.940 lb
8.340 lb
7.815 lb
7.365 lb
6.945 lb
6.225lb
1,000,000
20 gl
10 gl
8.326 gl
27.800 lb
20.860 lb
16.680 lb
13.900 lb
12.840 lb
11.920 lb
11.120 lb
10.420 lb
9.829 lb
9.260 lb
8.340 lb
Quantity of Calcium Chloride Needed to Increase Calcium Hardness
Gallons in Pool
25,000
50,000
75,000
100,000
200,000
500,000
lb oz
lb oz
lb oz
lb oz
lb
lb oz
3 2
6 4
9 6
12 8
25
62 8
6 4
12 8
18 12
25 0
50
125 0
9 6
18 12
28 2
37 8
75
187 8
12 8
25 0
37 8
50 0
100
250 0
15 10
31 4
46 14
62 8
125
312 8
18 12
37 8
56 4
75 0
150
375 0
21 14
43 12
65 10
87 8
175
437 8
25 0
50 0
75 0
100 0
200
500 0
28 2
56 4
84 6
112 8
225
562 8
31 4
62 8
93 12
125 0
250
625 0
46 14
93 12
104 10
187 8
375
937 8
62 8
125 0
187 8
250 0
500
1,250 0
Quantity of Chlorine Compound Needed to Increase 1 ppm
Gallons in Pool
25,000
50,000
75,000
100,000
200,000
2 qt
1 gl
1.5 gl
2 gl
4 gl
1 qt
2 qt
3 qt
1 gl
2 gl
1.67 pt
1.517 qt
2.276 pt
3.33 qt
1.665 gl
0.665 lb
1.390 lb
2.085 lb
2.780 lb
5.580 lb
0.521 lb
1.043 lb
1.565 lb
2.086 lb
4.172lb
0.417 lb
0.834 lb
1.251 lb
1.668 lb
3.336lb
0.348 lb
0.695 lb
1.043 lb
1.390 lb
2.780lb
0.321 lb
0.642 lb
0.963 lb
1.284 lb
2.568lb
0.298 lb
0.596 lb
0.894 lb
1.192 lb
2.384lb
0.278 lb
0.556 lb
0.834 lb
1.112 lb
2.224 lb
0.261 lb
0.521 lb
0.782 lb
1.042 lb
2.064 lb
0.417 lb
0.491 lb
0.737 lb
0.982 lb
1.964 lb
0.232 lb
0.463 lb
0.695 lb
0.926 lb
1.852 lb
0.209 lb
0.417 lb
0.626 lb
0.634 lb
1..668 lb
cp = one cup (8 fl oz) pt = one pt (16 fl oz) qt = one quart (32 fl oz)
gl = one gallon (128 fl oz)
lb =pounds of dry chemical
500,000
10 gl
5 gl
4.163 gl
13.900 lb
10.430 lb
8.340lb
6.950 lb
6.420 lb
5.960lb
5.560 lb
5.210 lb
4.910 lb
4.630 lb
4.170 lb
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Rev: B09
Section I: Installation Diagrams
I – 1: Pressure Filter Installation
I – 2: Vacuum Filter Installation
Page 53
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Rev: B09
Section J: Warranty
LIMITED WARRANTY
BECS warrants the controller electronics and flow cell against any defect in workmanship or
materials for a period of five years from the date of shipment. BECS warrants the pH and ORP
sensors against any defect in workmanship or materials for a period of two years from the date of
shipment. In the event of a component failure due to any defect in workmanship or materials,
BECS will repair, or if repair is not possible, replace the defective part or parts of the BECSys
controller.
BECS will have the sole right to determine whether to repair or replace a product. BECS will not be
responsible for any expense associated with installation of repaired or replacement parts.
LIMITATIONS AND EXCLUSIONS
This is a LIMITED WARRANTY. BECS makes NO WARRANTIES other than those contained
herein. The LIMITED WARRANTY replaces and is in lieu of any WARRANTIES of
MERCHANTABILITY or of FITNESS FOR A PARTICULAR PURPOSE which are expressly
DISCLAIMED. All GENERAL, SPECIAL, INDIRECT, INCIDENTAL AND/OR
CONSEQUENTIAL DAMAGES ARE EXCLUDED AND DISCLAIMED.
This Limited Warranty is governed by Missouri Law and all disputes related to or arising from this
transaction or Limited Warranty shall be resolved in Circuit Court of St. Louis County, Missouri.
Any claims under this Limited Warranty must be brought within ONE YEAR after the cause of
action accrued.
Page 54
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Installation and Technical Manual
Rev: B09
BECS
TECHNOLOGY Inc. has been designing and manufacturing the industry’s
most reliable water chemistry controller for over 15 years. Our 24,000 ft2 facility in
Saint Louis, Missouri is home to an exceptional design team, and all manufacturing is
performed onsite at this facility where we can personally assure the quality of our
products. The BECS commitment to excellence drives the most innovative new
products and unparalleled customer service.
Document Part Number: 8620013-B09
February 2009
9487 Dielman Rock Island Industrial Dr. St. Louis, MO 63132 Tel:(314) 567-0088
Download