ELEC0047 - Power system dynamics, control and stability Long-term voltage stability: fundamentals Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct December 2015 1 / 34 Long-term voltage stability: fundamentals Introduction Classification of power system instabilities 2 / 34 Long-term voltage stability: fundamentals Introduction Table of contents Voltage instability results from the inability of the combined transmission and generation system to provide the power requested by loads I Transmission aspects Generation aspects Load aspects 3 / 34 Long-term voltage stability: fundamentals Transmission aspects One-generator one-load system in steady-state operation Complex power absorbed by the load: S = P + jQ = V̄ I¯? = V̄ j Ē ? − V̄ ? = (EV cos θ + jEV sin θ − V 2 ) −jX X Power flow equations: P=− EV sin θ X Q=− V2 EV + cos θ X X After eliminating θ: V2 2 + (2QX − E 2 )V 2 + X 2 (P 2 + Q 2 ) = 0 (1) 4 / 34 Long-term voltage stability: fundamentals Transmission aspects Feasible region in load power space To have (at least) one solution: 2 PX QX − − 2 + 0.25 ≥ 0 E2 E (2) any P can be reached provided Q is adjusted (but V may be unacceptable !) dissymmetry between P and Q due to reactive transmission impedance locus symmetric w.r.t. Q axis; this does no longer hold when transmission resistance is included 5 / 34 Long-term voltage stability: fundamentals Transmission aspects Maximum load power under constant power factor Under the given load power factor cos φ : Substituting in (2) gives: P2 + Q = P tan φ E2 E4 tan φ P − =0 X 4X 2 from which one obtains: Pmax = cos φ E 2 1 + sin φ 2X Qmax = sin φ E 2 1 + sin φ 2X E VmaxP = √ √ 2 1 + sin φ Particular cases: cos φ = 1 : cos φ = 0 : Pmax = E2 2X Pmax = 0 Qmax = 0 Qmax = E2 4X E VmaxP = √ 2 VmaxP = E 2 6 / 34 Long-term voltage stability: fundamentals Transmission aspects Load voltage as a function of load power Solving (1) for V 2 and taking the square root: s r E2 E4 − QX ± − X 2 P 2 − XQE 2 V = 2 4 7 / 34 Long-term voltage stability: fundamentals Transmission aspects PV curves for a given power : 1 solution with “high” voltage and “low” current (normal operating point) 1 solution with “low” voltage and “high” current compensating the load increases the maximum power but the “critical” voltage approaches normal values ! similar curves: QV or SV under constant tan φ, QV under constant P, etc. 8 / 34 Long-term voltage stability: fundamentals Transmission aspects Generator reactive power requirement Reactive power provided by generator: Qg = Q + XI 2 = Q + X P 2 + Qg2 E2 Reordering and with respect to Qg : ssolving 2 QE 2 E2 E2 ± − − P2 Qg = 2X 2X X normal operation is on the lower part of this curve Qg increases with P more than linearly (due to losses) 9 / 34 Long-term voltage stability: fundamentals Transmission aspects Effect of line capacitance and/or shunt compensation Thevenin equivalent as seen by the load: E Eth = 1 − (Bc + Bl )X Xth = X 1 − (Bc + Bl )X Maximum deliverable power under power factor cos φ: Pmax = 2 cos φ Eth 1 cos φ E 2 = 1 + sin φ 2Xth 1 − (Bc + Bl )X 1 + sin φ 2X corresponding load voltage: 1 E Eth √ √ VmaxP = √ √ = 1 − (Bc + Bl )X 2 1 + sin φ 2 1 + sin φ 10 / 34 Long-term voltage stability: fundamentals Transmission aspects Effect of variable shunt compensation Bl = 0, Bc varied shunt compensation adjusted to keep voltage in an interval smooth change in compensation by SVC at load bus V almost constant as long as SVC is within limits 11 / 34 Long-term voltage stability: fundamentals Transmission aspects Sensitivities Sensitivities can help determine if operating point is on the upper part of the PV curve Example : sensitivity SQg Q of reactive power generation to reactive load power How many additional Mvar’s must be produced if the load consumes 1 Mvar more ? positive at normal operating points tend to infinity as the maximum load power is approached 12 / 34 Long-term voltage stability: fundamentals Transmission aspects First glance at instability mechanisms Assume that the load behaves as constant power in steady-state P = zPo Q = zQo When z increases, the load characteristic changes until it eventually does not intersect the network characteristic. Equilibrium is lost at the loadability limit. The large disturbance causes the network characteristic to shrink so drastically that the post-disturbance network characteristic does no longer intersect the (unchanged) load characteristic 13 / 34 Long-term voltage stability: fundamentals Generation aspects Table of contents Transmission aspects I Generation aspects Load aspects 14 / 34 Long-term voltage stability: fundamentals Generation aspects Field and armature current limiters field current limit imposed by OverExcitation Limiter (OEL) armature (or stator) current limit: seldom enforced by a limiter; most often, action by operator. 15 / 34 Long-term voltage stability: fundamentals Generation aspects Generator QV curves Region of admissible operating points in the (Q, V ) plane, under constant P Example of QV curves 50-Hz turbo-generator rated apparent power: 1200 MVA rated turbine power: 1020 MW Xd = 2.051 pu Xq = 1.966 pu saturation taken into account If = 2671 A at no load and nominal voltage If = 8300 A after OEL activation 16 / 34 Long-term voltage stability: fundamentals Generation aspects Under Automatic Voltage Regulator (AVR) control: small voltage drop when the reactive power output increases (due to proportional control often used) significant for machines with low AVR steady-state open-loop gain (e.g. 30-50 pu/pu) assuming constant reactive power for a machine under rotor limit is an approximation (there is some change with voltage) the reactive power must be updated with the active power output at low voltages the armature limit is very constraining usually the limited generator will be tripped by a protection when its voltage reaches ' 0.85 pu. 17 / 34 Long-term voltage stability: fundamentals Generation aspects Effect of generator reactive limits on maximum load power L closer to G than to G∞ simple PV/PQ model used for G increase of P of load covered by G∞ maximum load power reached at point M’, not M ! maximum load power significantly reduced by generator reactive limits most often voltage stability would not be a problem if generators were unlimited sources of reactive power (i.e. constant voltage sources) maintain reactive power reserves on generators located near load centers maximum load power generally reached at higher voltages (more dangerous) electrical decoupling does no longer hold ! 18 / 34 Long-term voltage stability: fundamentals Generation aspects Illustration with a power flow calculation XAB = 0.2, XBL = 0.005, XGB = 0.02 pu, rGB = 1.04, BL = 200 Mvar PL = 900, PG = 400 MW, QL = 200, QGmax = 250 Mvar, VG = 1.04, VA = 1.05 pu Operating point beyond maximum load power Trace of Newton iterations: iter max mismatches 1 2 3 4 5 6 Gener G : Q = 457.8 > 6 7 8 9 10 : MW 900.0 199.3 23.7 2.4 0.8 0.3 Qmax = 0.3 50.0 258.6 140.2 304.6 Mvar 445.3 339.1 28.2 1.4 0.4 0.2 250.0. Switched to PQ type 207.8 22.3 19.2 11.3 37.6 divergence of Newton iterations after the generator reactive limit is enforced. 19 / 34 Long-term voltage stability: fundamentals Generation aspects Effect of generator reactive limits - another situation Same system respective position of the PV curves is different maximum load power: not reached at point M, where reactive capability of G is exceeded (would cause the OEL to act) not reached at point M’, where generator voltage VG is higher than setpoint VG0 (would cause the AVR to regain control) reached at the breaking point A, where VG = Vg0 and QG = QGmax 20 / 34 Long-term voltage stability: fundamentals Generation aspects Illustration with a power flow calculation same data except QGmax = 350 Mvar iter max mismatches 1 2 3 4 5 6 Gener G : Q = 457.8 > 6 7 8 9 Volt of gener G = 1.1418 9 10 11 12 13 Gener G : Q = 458.4 > 13 14 15 16 Volt of gener G = 1.1418 16 17 18 : MW Mvar 900.0 445.3 199.3 339.1 23.7 28.2 2.4 1.4 0.8 0.4 0.3 0.2 dQg/dQl Qmax = 350.0. Switched to PQ type 0.3 107.8 13.1 5.0 5.0 0.4 0.2 0.1 dQg/dQl > setpoint = 1.0500. Back under volt ctl 32.2 496.0 20.6 43.3 1.7 1.5 0.5 0.4 0.2 0.1 dQg/dQl Qmax = 350.0. Switched to PQ type 0.2 108.4 13.1 5.0 5.1 0.5 0.2 0.1 dQg/dQl > setpoint = 1.0500. Back under volt ctl 32.2 496.0 20.6 43.3 1.7 1.5 ... = 2.45 at bus L = -2.22 at bus L = 2.46 at bus L = -2.22 at bus L 21 / 34 Long-term voltage stability: fundamentals Generation aspects Sensitivity behaviour in the presence of generator limits Discontinuities at the points where a generator limit is enforced case of slide 17 case of slide 19 sensitivity goes to infinity when approaching max load power sensitivity does not go to infinity when passing through max load power 22 / 34 Long-term voltage stability: fundamentals Load aspects Table of contents Transmission aspects Generation aspects I Load aspects 23 / 34 Long-term voltage stability: fundamentals Load aspects Load power restoration if loads behaved as constant admittances, no voltage instability would occur (low but steady voltages would be experienced in severe cases) voltage instability is largely caused by the trend of loads to restore their pre-disturbance power after a disturbance this may take place in several time scales : component time scale internal variable induction motor ' 1 second motor speed load tap changer ' few minutes thermostatically controlled load ' few minutes - tens of min. transformer ratio amount of connected load equilibrium condition mechan. torque = electrom. torque controlled voltage within deadband temperature within deadband others: distribution voltage regulators, consumer reaction to voltage drop 24 / 34 Long-term voltage stability: fundamentals Load aspects Load power restoration in induction motor Steady-state characteristics of motor large industrial motor Xs = 0.067, Xm = 3.800, Xr = 0.17, Rs = 0.013, Rr = 0.009 pu 25 / 34 Long-term voltage stability: fundamentals Load aspects Load tap changers also referred to as on-load tap changers or under-load tap changers Automatic adjustment of r to maintain V2 in a deadband r ' [0.85 − 0.90 1.10 − 1.15] ∆r ' 0.5 - 1.5 % [V2o − V2o + ] ∆r < 2 “Slow” device → long-term dynamics Delay between two tap changes: minimum delay Tm of mechanical origin ' 5 seconds intentional additional delay: from a few seconds up to 1 − 2 minutes to let network transients die out before reacting (avoid unnecessary wear) fixed or variable delay before first tap change (' 30 − 60 seconds) usually larger than delay between subsequent tap changes (' 10 seconds) 26 / 34 Long-term voltage stability: fundamentals Load aspects Load power restoration through LTC Assume the load is represented by an exponential model: P2 (V2 ) = P o ( V2 α ) V2o Q2 (V2 ) = Q o ( V2 β ) V2o The power balance equations at bus 2 are: Po( Qo( V2 α ) V2o V2 β ) − BV22 V2o V1 V2 sin θ rX V2 V1 V2 = − 2 + cos θ X rX = − (3) (4) 27 / 34 Long-term voltage stability: fundamentals Load aspects For given values of V1 and r , Eqs. (3,4) can be solved numerically with respect to θ and V2 (using Newton method for instance) from which the power leaving the transmission network is obtained as: P1 = − V1 V2 sin θ (= P2 ) rX Q1 = V12 V1 V2 − cos θ r2 X rX repeating this operation for various values of V1 and r yields the curves shown on the next slide. Numerical example transformer: 30 MVA, X = 0.14 pu, LTC voltage setpoint = 1 pu load: α = 1.5, β = 2.4, P2 = 20 MW under V2 = 1 pu, cos φu = 0.90 (lagging) under V2 = 1 pu with the compensation capacitor: cos φc = 0.96 (lagging) under V2 = 1 pu On the SB = 100 MVA base: V2o = 1 pu o P = 0.20 pu X = 0.14(100/30) = 0.467 pu o Q = P o tan φu = 0.20 × 0.4843 = 0.097 pu B.12 = Q o − P o tan φc ⇒ B = 0.097 − 0.20 × 0.2917 = 0.039 pu 28 / 34 Long-term voltage stability: fundamentals Load aspects 29 / 34 Long-term voltage stability: fundamentals Load aspects Response to a 5 % drop of voltage V1 : in the short term, the operating point changes from A to B next, three tap changes take place, under the effect of the LTC and the operating point changes from B to C. Neglecting the deadband 2, and assuming that LTC does not hit a limit: the V2 voltage is restored to the setpoint value V2o hence, the P2 and Q2 powers are restored to their pre-disturbance values the same holds true for the P1 and Q1 powers, since: P1 = P2 (V2 ) Q1 = Q2 (V2 ) − BV22 + XI22 = Q2 (V2 ) − BV22 + X P22 (V2 ) + Q22 (V2 ) V22 hence, the load seen by the transmission system behaves in the long-term (i.e. after the tap changer has acted) as a constant power. 30 / 34 Long-term voltage stability: fundamentals Load aspects Thermostatic load power recovery Heating resistors are switched on/off by thermostats so that the mean power consumed over a cycle = power required to keep the temperature = Preq ton GV 2 = Preq ton + toff (5) If V drops, P = GV 2 drops ⇒ ton increases until (5) is satisfied For a large number n of identical thermostatically-controlled resistors: ! n n X ton 1X 2 fi (t) GV 2 ' n GV 2 P(t) = fi (t)GV = n n ton + toff i=1 i=1 where fi (t) = 1 if the i-th resistor is on at time t fi (t) = 0 if it is off. 31 / 34 Long-term voltage stability: fundamentals P(t) ' n Load aspects ton GV 2 ton + toff following a voltage drop, nGV 2 decreases ton increases until P(t) recovers to nPreq but after some time, ton + toff thus, the load behaves as constant admittance in the short term and as constant power in steady state thermostatically controlled loads are also referred to as “constant-energy” loads. However, if the voltage drop is too pronounced, all resistors stay connected (toff = 0) but Preq cannot be obtained. Then, the load behaves as constant admittance. 32 / 34 Long-term voltage stability: fundamentals Load aspects Generic model of load power restoration Power consumed by the load at any time t: βt αt V V Q(t) = zQ Qo P(t) = zP Po Vo Vo (6) zP , zQ : dimensionless state variables associated with load dynamics αt , βt : short-term (or transient) load exponents In steady-state, the load obeys: αs V Ps = Po Vo Qs = Qo V Vo βs (7) αs , βs : steady-state (or long-term) load exponents; usually αs < αt , βs < βt . The load dynamics are given by: αs αt V V T żP = − zP Vo Vo T żQ = with zPmin ≤ zP ≤ zPmax and zQmin ≤ zQ ≤ zQmax . V Vo βs − zQ V Vo βt (8) T ' several minutes 33 / 34 Long-term voltage stability: fundamentals Load aspects Response of active power P to a step decrease of voltage V αt ' ∆Pt /Po ∆V /Vo αs ' ∆Ps /Po ∆V /Vo Similar expressions hold true for reactive power 34 / 34