meteocontrol Power Control Operating Manual Version 20131213 Copyright Copyright for this manual remains with the manufacturer. No part of this manual may be reproduced or edited, duplicated or distributed using electronic systems without written permission from meteocontrol GmbH. Compensation shall be payable in the event of any copyright infringements. All brand names mentioned in this manual are the property of their respective manufacturers and are hereby acknowledged. Contact data The manufacturer of the device described in this documentation is: meteocontrol GmbH Spicherer Str. 48 D-86157 Augsburg Tel.: +49 (0) 821 / 3 46 66-0 Web: www.meteocontrol.de Technical support: Tel.: +49 (0) 821 / 3 46 66-88 Fax: +49 (0) 821 / 3 46 66-11 E-mail: technik@meteocontrol.de Details regarding the manual The original operating manual is written in German. All other language versions are translations of the original operating manual and are hereby identified as such. © 2013 meteocontrol GmbH All rights reserved. All information in this operating manual has been compiled and checked with the greatest care and diligence. Nevertheless, the possibility of errors cannot be entirely excluded. meteocontrol GmbH therefore cannot accept any liability for errors or any circumstances resulting from errors. Subject to technical alterations. meteocontrol Power Control Contents 1. General notes ..............................................................................................................2 1.1 Safety instructions ............................................................................................... 2 1.2 Warning symbols ................................................................................................. 2 1.3 Additional information .......................................................................................... 2 1.4 Text display .......................................................................................................... 3 2. Notes on using the operating manual ...........................................................................4 2.1 Warranty and liability ............................................................................................ 5 3. Technical description ...................................................................................................6 3.1 Grid feed-in management requirements ............................................................... 6 3.2 meteocontrol Power Control requirements .......................................................... 6 3.3 meteocontrol Power Control functionality ............................................................ 7 3.4 Power Control Unit functionality ........................................................................... 7 3.5 Power Control with PCU+ functionality ................................................................ 8 3.6 Power Control without PCU+ functionality ........................................................... 9 3.7 Functions ........................................................................................................... 10 4. Power Control device configuration ............................................................................ 11 5. meteocontrol Power Control configuration.................................................................. 11 5.1 WEB’log definition as master ............................................................................. 11 5.2 WEB`log definition as slave ................................................................................ 12 5.3 Power Control system data ................................................................................ 13 5.4 Power control procedures for the meteocontrol Power Control ......................... 14 5.5 Active power procedure ..................................................................................... 18 5.5.1 P(DI) ................................................................................................................... 18 5.5.2 P(AI) ................................................................................................................... 19 5.5.3 P Fix ................................................................................................................... 20 5.5.4 P(DI) internal ...................................................................................................... 20 5.6 Reactive power procedure ................................................................................. 21 5.6.1 Cosφ (DI) ............................................................................................................ 21 5.6.2 Cosφ (AI) ............................................................................................................ 22 5.6.3 Cosφ Fix ............................................................................................................. 23 5.6.4 Cosφ (P) ............................................................................................................. 23 5.6.5 Cosφ (U) ............................................................................................................. 24 5.6.6 Q(DI) .................................................................................................................. 25 5.6.7 Q(AI)................................................................................................................... 26 5.6.8 Q fix ................................................................................................................... 27 5.6.9 Q(U) ................................................................................................................... 27 5.6.10 Inverter cosφ (P) ................................................................................................. 28 5.6.11 Inverter Q(U) ...................................................................................................... 28 5.7 Enabling Power Control ...................................................................................... 29 5.8 Power Control status.......................................................................................... 29 5.9 Power Control settings via the data logger display ............................................. 30 6. Power quality analyser ............................................................................................... 31 7. Grid feed-in management overview ............................................................................ 32 8. List of figures ............................................................................................................ 33 meteocontrol Power Control 1| 34 1. General notes 1.1 Safety instructions Safety instructions warn of dangers when using the devices and explain how they can be avoided. The safety instructions are classified according to the severity of the risk and are subdivided into three groups: DANGER Imminent danger – Failure to comply with the warning notice will lead to an imminent risk of death or serious physical injury! WARNING Possible danger – Failure to comply with the warning notice may lead to a risk of death or serious physical injury! CAUTION Hazard with a risk of material damage – Failure to comply with the warning notice may lead to minor injuries! ATTENTION Hazard with a risk of material damage – Failure to comply with the warning notice will lead to material damage! 1.2 Warning symbols Particular dangers are highlighted using warning symbols. RISK OF ELECTRIC SHOCK Electric shock hazard! Danger to life and limb! – Failure to comply with the warning notice will lead to an imminent risk of serious injury or death. 1.3 Additional information This symbol can be found next to notes, additional information and tips. 2| 34 meteocontrol Power Control 1.4 Text display Emphasised points are shown in bold and indicate important information. Lists are shown with bullet points (level 1) and dashes (level 2): List 1 Point A Point B List 2 Instructions describe steps which are to be carried out in the given order. 1. Instruction 1 2. Instruction 2 Result of the operation Button names are shown in capitals and in "QUOTATION MARKS". In figures, item numbers are used to indicate components. The legend with item numbers and descriptions of the components are shown below the figure. Alternatively, direct references to components are made in the text. meteocontrol Power Control 3| 34 2. Notes on using the operating manual This description is designed to ensure that the WEB’log, PCU and PCU+ devices function properly. It contains important information and safety notes to help you use the devices correctly, economically and in the intended manner. The description helps to avoid dangers, to reduce repair costs and downtimes, and to increase the reliability and operating life of the devices. This operating manual describes the additional Power Control functions and, specifically, the power control procedures. DANGER Danger owing to improper handling of the devices - The staff responsible for the installation, operation and maintenance of the system must have read and understood this operating manual before the devices can be configured and used safely! - If necessary, the description and documents must be available at all times. meteocontrol GmbH accepts no liability for personal injury, damage to property, or system malfunctions and their consequences, insofar as these result from nonobservance of this operating manual. The manual is continually updated. The most up-to-date version of this description can be found on our internet page www.meteocontrol.de 4| 34 meteocontrol Power Control 2.1 Warranty and liability Details of the scope and form of the warranty as well as the warranty period are given in the meteocontrol GmbH General Terms and Conditions. meteocontrol rejects any liability for damage arising from the non-observance of the operating manual. This applies, in particular, for damage from: Unintended use Faulty operation Wrongly chosen materials and tools Faulty or non-executed maintenance and repairs With Power Control, meteocontrol GmbH accepts no liability for events and occurrences outside of its control, such as: the correctness of control commands given by an energy supply company or failure to implement control commands that have been passed on hardware and/or software faults on the part of the system operator switching processes on consumer end. Any liability for damage caused by such events and occurrences, such as lost profits, grid instability, damage to parts of the customer's system, for instance of an inverter, shall remain expressly excluded. meteocontrol Power Control 5| 34 3. Technical description Power Control is a system for controlling and managing different operating parameters of PV systems (such as reactive and active power). 3.1 Grid feed-in management requirements As the proportion of solar power in relation to overall power production increases, it becomes increasingly necessary for PV system operators to become actively involved in grid feed-in management. This means it must be possible to reduce feed-in power and play a role in compensating for the reactive power in the grid as stipulated in the EEG (German Renewable Energy Law), the Medium Voltage Directive, the Transmission Code and VDE AR-N 4105. In view of this, the system operators must fulfil the following requirements: 3.2 They must be able to reduce the feed-in power of systems by remote control or disconnect systems from the grid entirely. They must be able to reduce the reactive power in the grid by reactive power compensation. meteocontrol Power Control requirements It is recommended that you clarify the following requirements of the grid operator, inverter manufacturer and system operator for Power Control in the system planning phase: Procedures according to which the requirements of the grid operator are implemented, resulting in control values for the inverters. Procedures that are supported by the WEB`log for the inverter types used (inverter drivers). Interfaces used for the grid operator's remote control and monitoring systems. Characteristic requirements for the power control mechanism made by the system operator: If difficulties regarding these requirements arise or the necessary configuration options are not available, consult your meteocontrol contact in sales or system planning/system start-up. 6| 34 meteocontrol Power Control 3.3 meteocontrol Power Control functionality Basic function: The requirements for power reduction and control are given by the grid operator and carried out via a selected interface (digital, analogue) by the PCU, PCU+ or WEB`log inputs. The control values are determined from the requirements in accordance with configurable rules. The rules can be defined in accordance with the requirements. Feedback to the grid operator is optionally provided. The control values are set on the inverter within a response time as required by the grid operator. The grid operator receives a message about the control value set on the inverters. 3.4 Power Control Unit functionality The Power Control Unit (PCU) and the Power Control Unit + (PCU+) are intelligent, high-performance modules which expand the functions of the WEB‘log by adding reactive power control. This ensures efficient control of the active and reactive power in photovoltaic systems. General function: The PCU receives the requirements from the grid operator's remote control and monitoring system via its inputs. The PCU prepares the requirements and forwards them to the WEB`log. The WEB`log establishes the control values and sends them to the inverters. No PCU is required to achieve a reduction in active power via four potential-free contacts and without feedback to the grid operator. The corresponding procedures (referred to as P(DI) internal and P (fix)) can be implemented with the WEB’logs BASIC, LIGHT+ 20 and PRO unlimited via the digital inputs. Likewise, no PCU is required for reactive power procedures defined via a characteristic curve. On the following pages, meteocontrol Power Control functions are presented with and without a PCU. The way in which the requirements for active and reactive power issued by the grid operator reach the inverters is depicted clearly. meteocontrol Power Control 7| 34 3.5 Power Control with PCU+ functionality Fig. 1: PCU<->Power Control functionality (1) (2) (3) (4) (5) (6) 8| 34 Grid operator Public grid Ripple control receiver Power Control Unit (PCU) WEB`log PRO as master Ethernet switch (7) (8) (9) (10) (11) WEB`log PRO as slave Inverter Internet Web portal Power requirements report meteocontrol Power Control 3.6 Power Control without PCU+ functionality Fig. 2: Power Control functionality (1) (2) (3) (4) (5) Grid operator Public grid Ripple control receiver WEB`log master Ethernet switch meteocontrol Power Control (6) (7) (8) (9) (10) WEB`log slave Inverter Internet Web portal Power requirements report 9| 34 3.7 Functions Power control Active power procedure (P procedure) With the internal inputs of the WEB`log PRO unlimited, only the active power procedure can be carried out via digital requirements. Active and reactive power procedures (P/Q/cosφ procedures) With the PCU, various active and reactive power procedures can be selected and configured. Master functions In larger systems with several WEB`log PRO Unlimited devices, a WEB`log assumes the master function. The master receives the requirement values from the grid operator. The information is forwarded to all WEB`log slaves or to the configured IP addresses in the form of a broadcast via the Ethernet. Power requirements change message When changing the power requirements, the WEB`log PRO Unlimited informs one or more recipients via the reporting route configured. The message contains information on the time of changing and the required power level. 10| 34 meteocontrol Power Control 4. Power Control device configuration Configuration of the Power Control Unit is carried out on the WEB’log websites. The PCU configuration website is used to configure the Power Control Unit required for the majority of power control procedures of the meteocontrol Power Control. The site can be accessed via the menu item Admin Measurement > Power Control > PCU Configuration. For the corresponding configuration settings, please see the respective PCU or PCU+ operating manual. Up-to-date versions of the operating manuals are available for downloading on our website. 5. meteocontrol Power Control configuration Configuration of the power control procedures of the meteocontrol Power Control is carried out on the WEB’log websites. First, a computer must be connected to the WEB'log via Ethernet. Afterwards the WEB'log home page can be addressed in the web browser. Use the selection "Professional mode" and you log in to the admin area via the General > Login menu. The standard password is: “ist02“. The configuration is now carried out in the Admin Measurement > Power Control > General Configuration menu. The individual steps are listed in order so that they can be carried out consecutively. 5.1 WEB’log definition as master With this selection, the WEB’log master defines the power control procedures and, if desired, sends the parameters to the WEB’log slaves. The following figures show the possible settings for the master: Fig. 3: WEB`log master with broadcast to all slaves Fig. 4: WEB`log master without slaves Fig. 5: WEB`log master with slave groups meteocontrol Power Control 11| 34 5.2 WEB`log definition as slave With this selection, the data logger receives the control values for Power Control from the master. The power control procedures are defined by the master and the parameters are sent to the slaves. If the WEB`log is operated as a slave, control values which are used in the event of a failure in communication with the master must be defined. The following figures show the possible settings: Fig. 6: WEB`log definition as slave – general broadcast Fig. 7: WEB`log definition as slave – group broadcast Input box Meaning Master (none) Master (to all slaves) Transfers no control value information to slaves (Fig. 3) Transfers control value information as a broadcast to all available slaves (Fig. 4) Transfers control value information as a broadcast to all slave groups (Fig. 5) Receives control value information from the master via general broadcast (Fig. 6) Receives control value information from the master via group broadcast (Fig. 7) Slave group ID for addressing Master (slave group) Slave (general broadcast messages) Slave (group broadcast messages) Slave group The activated master data logger sends information on active and reactive power values to slaves. Active and reactive power procedures can be set and configured on the master only. In most cases, the operating modes Master (to all slaves) and Slave (general broadcast message) are sufficient. A number of slave groups are needed if data loggers which belong to the systems of various grid connection points are used within the same Ethernet network. 12| 34 meteocontrol Power Control Fallback operation In slave mode, the “Options” heading contains input boxes in which fixed default values for the inverters in the event of a failure in communication between the master and slave can be stipulated. Specifying default values in this way is referred to as fallback. Fig. 8: Fallback defaults, example cosφ Fix Input box Active power default Default value in fallback mode Reactive power default Fallback value None 5.3 Meaning Active power level in the event of communication failure in % of the agreed connection power PAV It is possible to select a reactive power control procedure in the event of a communication failure: cos φ Fix, Q Fix or an inverter internal procedure No reactive power default will be sent to the inverters in fallback mode cos φ Fix Use of the power factor as a control value in fallback mode Q Fix Inverter internal Use of the reactive power as a control value in fallback mode In fallback mode, the reactive power procedure implemented in the inverter will be used Power Control system data The system data need to be entered at this point. These are basic values for the majority of the power control procedures. It is imperative that parameters in this section are entered correctly in order to ensure the proper function of power control procedures and system control loop. Fig. 9: Power control system data Input box Meaning Agreed connection power PAV Agreed maximum apparent power SAmax Nominal voltage AC UNom Maximum feed-in active power at the grid connection point as agreed upon with the grid operator Maximum apparent power at the grid connection point as agreed upon with the grid operator Nominal voltage at the grid connection point meteocontrol Power Control 13| 34 5.4 Power control procedures for the meteocontrol Power Control The WEB’log PRO Unlimited is able to use a whole range of different procedures for controlling the power of your PV system. However, an additional PCU, PCU+ and/or a power quality analyser must be used for the more extensive procedures. The active and reactive power procedures selected determine the processing type of the requirements received. Various procedures with different control values are brought together under these active and reactive power procedures. Select the relevant procedure according to the requirements. The various procedures cannot use any control value sources or be combined at will. A procedure for active power reduction can be selected without adding a procedure for reactive power control. (Selecting the procedure for reactive power control is optional). A procedure for reactive power control can only be selected if a procedure for active power reduction was chosen (selecting the procedure for active power reduction is required). An individual input screen for selecting parameters for the particular procedures selected is displayed. Normal operation In normal operation, control values are determined and sent to the inverters, changes to the requirements are logged and a notification is sent when changing the active power reduction (if notification is configured) from the requirements in accordance with the defined rules. Fallback operation In the event of a communication failure between PCU and WEB`log or master and slave WEB‘log, i.e. if no default values are received at that time, fallback operation becomes active after a delay period of 10 minutes. In this case, the pre-configured default values will be used during fallback. During the delay period, the parameter set of the last valid control values is used. If Power Control is enabled with the set of required information being incomplete, fallback operation will likewise be enabled immediately. Possible causes: Error when receiving the requirements (digital-in or analogue-in). Error in the definition of the configuration for the power procedures chosen. Communication error between PCU and WEB`log master 14| 34 meteocontrol Power Control Setting up the power control procedures Fig. 10: Active power and reactive power procedures Input box Active power default Active power procedure Capping at PAV Default value in fallback mode Reactive power default Procedure switching Reactive power procedure Q procedure gradient limitation cos φ (Fix) default value in fallback mode Q (Fix) default value in fallback mode Configuration Meaning Active power procedure selection When this option is selected, the data logger ensures the agreed connection power PAV is not exceeded. Default value for active power in fallback mode Enables switching between various reactive power procedures via the digital inputs Reactive power procedure selection Enables gradient limitation The maximum permitted reactive power change per second can be specified Default value for power factor in fallback mode Default value for reactive power in fallback mode Brings up the configuration settings for the selected active and reactive power procedure A description of all power control procedures and the relevant settings can be found in Chapters 5.5 and 5.6. meteocontrol Power Control 15| 34 System control loop The system control procedure ensures that inconsistencies in the power fed-in, caused by the transmission route between the inverter and grid connection point (GCP), are compensated (low voltage or medium voltage). As a result, the requirements imposed by the grid operator are met at the GCP itself. The GCP controlling procedure is only active if the reactive power procedure is selected. For correct functionality of the system control loop, the following parameters must be entered correctly. Agreed connection power PAV [kW] Agreed maximum apparent power SAmax [kVA] Nominal voltage AC UNom [kV] Parameter model [transformer / no transformer] * Transformer nominal power [kVA] * Lower Plimit [%] Lower cosφlimit * Upper Qlimit [%] * The "Upper Qlimit" field automatically generates its contents from the "Lower cosφlimit" field and vice versa. Therefore it is sufficient to enter the data provided by the inverter manufacturer in one of the two fields. Once the cursor leaves the field or if the enter key is pressed, the relevant other field is updated as well. The following data also has to be entered under Configuration > System Data: Installed power [kW] * ATTENTION 16| 34 - All data must be entered correctly. The parameters marked with * are particularly important when it comes to ensuring correct control. - Incorrectly entered data or values outside the technically feasible range of the inverter(s) will result in control malfunctions. meteocontrol Power Control Fig. 11: GCP control loop configuration Input box Meaning System control loop Parameter model Activates the system control loop Selection of the parameter model to calculate the start configuration control loop Nominal power of the transformer Transformer nominal power Lower Plimit Lower cos φlimit Upper Qlimit Generate start configuration Work threshold of the NAP control loop Work threshold of the NAP control loop Work threshold of the NAP control loop Generate the start configuration for the GCP control loop A power quality analyser at the grid connection point is essential for the operation of the system control loop. Information regarding power quality analysers can be found in Chapter 6. meteocontrol Power Control 17| 34 5.5 Active power procedure 5.5.1 P(DI) With this procedure, the active power P is used as the control value. The default value is provided by the grid operator as a digital input signal. This is possible for example via a ripple control receiver connected to the digital inputs of the PCU. The reduction levels are assigned to the digital inputs via a parameter table. In this case, every digital PCU input corresponds to a default value. Feedback regarding reduction is provided via the digital outputs of the PCU. Only individual outputs of the ripple control receiver may be assigned. Bit samples (e.g. DI 1,2,4 = Adr. 007 for assigning the default value) are not permitted. In contrast, the P(DI) internal procedure allows bit samples. Fig. 12: Active power procedure – P(DI) control 18| 34 Input box Meaning Number Active Input Output P% Control number Setting whether the rule should be applied Number of the IO port Number of the IO port Relative active power in percent (in relation to PAV) meteocontrol Power Control 5.5.2 P(AI) With this procedure, the active power P is used as the control value. The default value is provided by the grid operator as an analogue input signal. This is possible for example via a remote control system with analogue outputs connected to the analogue input (4–20 mA current signal in accordance with DIN IEC 60381-1) of the PCU. Feedback is provided via the analogue output (4-20 mA current signal in accordance with DIN IEC 60381-1). The power reduction from the analogue value is calculated via a linear equation. For the configuration, the value pairs P1 and P2 are required, which are at the end of the line (min and max). Fig. 13: Active power procedure – P(AI) control Input box Meaning AI The lowest measured value The highest measured value Sensitivity Number of the analogue input Value pair for defining the lowest operating point (example: 4 mA corresponds to zero percent) Value pair for defining the highest operating point (example: 20 mA corresponds to one hundred percent) Point from when a change in the analogue input results in a change in the control value (given in %) meteocontrol Power Control 19| 34 5.5.3 P Fix With this procedure, a fixed active power limit is used as the control value. To this end, a configurable, consistent value is saved. With this procedure, a downward inverter regulation to 70% or 60% for example is possible. A PCU is not required for this procedure. Feedback on the set power level is not possible with this procedure. 5.5.4 P(DI) internal With this procedure, the active power P is used as the control value. The default value is provided by the grid operator as a digital input signal. This is possible for example via a ripple control receiver connected to the internal digital inputs of the WEB`log. Unlike with the P(DI) procedure with PCU, the use of bitmasks is permitted for the P(DI) internal procedure. The digital inputs are assigned to the reduction levels via a parameter table. In this case, every digital PCU input corresponds to a requirement value. The PCU is not required for this procedure. Feedback on the set power level to the grid operator is not possible with this procedure. Fig. 14: Active power procedure – P(DI) internal 20| 34 Input box Meaning Digital inputs column (DI 4 - DI 1) Specification Configurable for up to 16 different power levels. Green indicates what input must be activated Power requirement in percent when occupying the relevant digital inputs meteocontrol Power Control 5.6 Reactive power procedure 5.6.1 Cosφ (DI) With this procedure, the power factor cosϕ is used as the control value. The default value is provided by the grid operator as a digital input signal. This is possible for example via a remote control system with digital outputs connected to the digital inputs of the PCU. Feedback is then provided via the digital outputs of the PCU. The assignment is carried out via a parameter table. The breakdown and assignment of the levels are freely selectable. In doing so, every digital PCU input corresponds to a requirement value. Fig. 15: Reactive power procedure – cosφ (DI) Input box Meaning Number Active Input Output cos φ / excitation Control number Setting whether the rule should be applied Number of the IO port Number of the IO port Power factor control values for reactive power reduction meteocontrol Power Control 21| 34 5.6.2 Cosφ (AI) With this procedure, the power factor cos ϕ is used as the control value. The default value is provided by the grid operator as an analogue input signal. This is possible for example via a remote control system with analogue outputs connected to the analogue input of the PCU. Feedback can be provided via the analogue output of the PCU. The value is provided by the grid operator as an analogue input signal (4 – 20mA). The power factor is calculated from the analogue value via a linear equation. For the configuration, the value pairs P1 and P2 are required, which are at the end of the line. Furthermore, the excitation type per point is required. Fig. 16: Example cosφ (AI) characteristic curve Fig. 17: Reactive power procedure – cosφ (AI) control Input box Meaning AI The lowest measured value Number of the analogue input Indicated in mA and %. Value pair for defining the lowest operating point (example: 4mA corresponds to factor 0.95 – overexcited) Indicated in mA and %. Value pair for defining the highest operating point (example: 20mA corresponds to factor 0.95 – under- excitated) Sensitivity setting: indicates from when a change to the analogue input results in a change to the control value Highest measurement value Sensitivity 22| 34 meteocontrol Power Control 5.6.3 Cosφ Fix With this procedure, a fixed power factor cosϕ is used as the control value. To this end, a configurable, consistent value is saved. No feedback is provided. The PCU is not required for this procedure. Feedback on the set power level is not possible with this procedure. 5.6.4 Cosφ (P) With this procedure, the power factor cosφ is used as the control value. By changing the power factor, it is possible to influence the power fed-in at the grid connection point. Here the selected measuring device records the active power (P) fed-in at the grid connection point and transfers it to the data logger, which then assigns the cosφ control value to the relevant power on the basis of a 4 point characteristic curve. The following details are required for the configuration: The 4 characteristic points P1 to P4 of the characteristic curve Details of the areas in which the points lie (overexcited or under- excitated) Fig. 18: Reactive power procedure – cosφ (P) control Input box Meaning Curve Point 1…4 PHyst Type of curve Support points 1…4 Hysteresis as the ratio of P/PAV This procedure requires a power quality analyser that has been configured and connected to the data logger. The PCU is not required for this procedure. Feedback on the set power level is not possible with this procedure. meteocontrol Power Control 23| 34 5.6.5 Cosφ (U) With this procedure, the power factor cosϕ is used as the control value. By changing the power factor, it is possible to influence the voltage at the grid connection point. To do this, the voltage U at the grid connection point is recorded by the selected measuring device and transferred to the data logger, which then assigns the cosφ control value to the relevant voltage on the basis of a linear equation. The following details are required for the configuration: The 4 points P1 to P4 of the characteristic curve Details in what areas the points are (overexcited or under- excitated) Fig. 19: Reactive power procedure – cosφ (U) control Input box Meaning Curve Point 1…4 UHyst Type of curve Support points 1…4 Hysteresis as the ratio of U/UNom This procedure requires a power quality analyser that has been configured and connected to the data logger. The PCU is not required for this procedure. Feedback on the set power level is not possible with this procedure. 24| 34 meteocontrol Power Control 5.6.6 Q(DI) With this procedure, the reactive power Q is used as the control value. The default value is provided by the grid operator as a digital input signal, which is possible for example via a remote control system with digital outputs connected to the digital inputs of the PCU. Feedback is provided via the digital outputs of the PCU. The assignment is carried out via a parameter table. The breakdown and assignment of the levels are freely selectable. In doing so, every digital PCU input corresponds to a requirement value. Fig. 20: Reactive power procedure – Q(DI) control Input box Meaning Number Active Input Output Q(%) / excitation Control number Setting whether the rule should be applied Number of the IO port Number of the IO port Reactive power control value for reactive power reduction in percent meteocontrol Power Control 25| 34 5.6.7 Q(AI) With this procedure, the reactive power Q is used as the control value. The default value is provided by the grid operator as an analogue input signal, which is possible for example via a remote control system with analogue outputs connected to the analogue input of the PCU. Feedback is provided via an analogue output of the PCU. The value is provided by the grid operator as an analogue input signal (typically: 4– 20mA). The reactive power is calculated from the analogue value via a linear equation. The following details are required for the configuration: The value pairs P1 and P2, which are at the end of the line (min and max). Details in what areas the points are (overexcited or under-excitated) Fig. 21: Q(AI) characteristic curve Fig. 22: Reactive power procedure – Q(AI) control Input box Meaning AI The lowest measured value Number of the analogue input Indicated in mA and %. Value pair for defining the lowest operating point (example: 4 mA corresponds to 15 % overexcited) Indicated in mA and %. Value pair for defining the highest operating point (example: 20 mA corresponds to 15% - underexcitated) Sensitivity setting: indicates from when a change to the analogue input results in a change to the control value The highest measured value Sensitivity 26| 34 meteocontrol Power Control 5.6.8 Q fix With this procedure, a fixed reactive power Q is used as the control value. To this end, a configurable, consistent value is saved in the WEB`log. No feedback is provided. The PCU is not required for this procedure. Feedback on the set power level is not possible with this procedure. 5.6.9 Q(U) With this procedure, the reactive power Q is used as the control value. By changing the reactive power, it is possible to influence the voltage at the grid connection point. To do this, the voltage U at the grid connection point is recorded by the selected measuring device and transferred to the data logger, which then assigns the Q control value to the relevant voltage on the basis of a linear equation. Power quality analysers are supported as measuring devices. The following details are required for the configuration: The 4 points P1 to P4 of the characteristic curve Details in what areas the points are (overexcited or under- excitated) Fig. 23: Reactive power procedure – Q(U) control Input box Meaning Curve Point 1…4 UHyst Lower limit cos φLimit Type of curve Support points 1…4 Hysteresis as the ratio of U/UNom Lower cos φ limit up to which the characteristic curve is moved, then the selected cos φ is used as the fixed value This procedure requires a power quality analyser that has been configured and connected to the data logger. The PCU is not required for this procedure. Feedback on the set power level is not possible with this procedure. meteocontrol Power Control 27| 34 5.6.10 Inverter cosφ (P) This procedure is an inverter-internal procedure. The data logger has no influence over control and allows the inverters to take over internal control. The power factor cosϕ is used as the control value. For the majority of inverters supporting this procedure, no settings need to be made in the data logger. The parameters should be saved in the inverter itself. For details of how to do this, please read the operating manual for the particular inverter. 5.6.11 Inverter Q(U) This procedure is an inverter internal procedure. The data logger has no influence over control and allows the inverters to take over internal control. The reactive power Q is used as the control value. For the majority of inverters that support this procedure, no settings need to be made in the data logger. The parameters should be saved in the inverter itself. For details on the respective steps, please read the operating manual for the inverter in use. 28| 34 meteocontrol Power Control 5.7 Enabling Power Control Once all settings for meteocontrol Power Control have been made, Power Control must be enabled. It is recommended to start Power Control only after the configuration has been completed. Fig. 24: Enabling Power Control 5.8 Input box Meaning Power Control Save Enables or disables the PC Saves the settings Power Control status Under Online Values > Power Control, you can bring up the current Power Control status. Fig. 25: Power Control online values Description Meaning Operating status Active power procedure Reactive power procedure Current control value Current Power Control status Displays the current active power procedure Displays the current reactive power procedure Control value requirement for active and reactive power procedures in percent The highlighted values are updated every 10 seconds. It is not possible to configure these online values. meteocontrol Power Control 29| 34 5.9 Power Control settings via the data logger display The Power Control status can be queried and modified via the WEB’log PRO unlimited display. Configuration of the meteocontrol Power Control on the other hand can only be done via the web browser, as detailed in the previous chapters. The WEB'log's user groups are password protected. The standard passwords are: User group "End customer" password "0030“ User group "Installer“ password "0020“ User group "Administrator“ password "0010“ Menu structure on the PRO unlimited display Settings** PC settings *** PC status enabled disabled * ** *** 30| 34 Power Control is active Power Control is inactive User group “End customer” User group “Installer” User group “Administrator” meteocontrol Power Control 6. Power quality analyser Because a power quality analyser (PQA) is a technical device with numerous functions, a user-specific configuration is necessary. It is recommended to install the transmitters at the grid connection point (support type current transformer, voltage converter) in accordance with the generator meter arrow system. When selecting the components, the precision classes of at least 0.5 (fine measurement device classes) should be ensured. Furthermore, power and current converter must be selected in order to utilize the measurement range of the power quality analyser to its fullest possible extent. To control the active power, a single-phase measurement is considered sufficient. However, a three-phase measurement is better recommended, as at the medium voltage end the transformer usually has a triangular switching group, while the voltage is measured against a star point. To allow the use of Power Control, meteocontrol offers a suitable power quality analyser (UMG604), which enables the measurements needed for a number of procedures to be taken at the grid connection point. Electrical installation of the PQA The electrical planning and installation of PV systems, in particular the connection of the power quality analyser at the grid connection point, are not covered by this manual. However, the following steps for the use of the PQA must be observed: PQA to GCP The power quality analyser is connected to the grid connection point in accordance with the relevant low voltage and/or medium voltage directives. Depending on the system design, transmitters are required (support type current transformer, voltage converter). PQA to WEB`log A power quality analyser (PQA) is always connected to the WEB’log configured as the master via Modbus-RTU or Modbus-TCP. The device should be connected and configured in accordance with the “Connecting Modbus devices" section of the WEB’log operating manual. meteocontrol Power Control 31| 34 7. Grid feed-in management overview Supported WEB’logs WEB‘log Light+ 20 WEB‘log Basic 100 Necessary accessories Web’log Pro Unlimited WEB‘log Pro Unlimited Power quality analyser (PQA) PCU+ Active power procedure P DI) WEB`log internal** + + + P (DI) + + P (AI) + + P (fix) + + Inverter internal + Driverdependent Reactive power procedure cosφ (DI) + +* + cosφ (AI) + + + + +* cosφ (P) + + cosφ (U) + + + +* + + cosφ (fix) Q (fix) + + + + Q (U) Inverter internal * : **: 32| 34 Driverdependent Driverdependent + Driverdependent PQA not necessary for systems connected to the low-voltage grid; PQA not compatible with the Web’log Basic 100 and the Light+ 20 Connection of ripple control receiver to the internal digital inputs of the WEB'log. For other procedures, connection is via the PCU. meteocontrol Power Control 8. List of figures Fig. 1: PCU<->Power Control functionality ................................................................... 8 Fig. 2: Power Control functionality ................................................................................ 9 Fig. 3: WEB`log master with broadcast to all slaves .................................................... 11 Fig. 4: WEB`log master without slaves ....................................................................... 11 Fig. 5: WEB`log master with slave groups .................................................................. 11 Fig. 6: WEB`log definition as slave – general broadcast .............................................. 12 Fig. 7: WEB`log definition as slave – group broadcast ................................................. 12 Fig. 8: Fallback defaults, example cosφ Fix ................................................................. 13 Fig. 9: Power control system data .............................................................................. 13 Fig. 10: Active power and reactive power procedures ................................................ 15 Fig. 11: GCP control loop configuration ....................................................................... 17 Fig. 12: Active power procedure – P(DI) control .......................................................... 18 Fig. 13: Active power procedure – P(AI) control .......................................................... 19 Fig. 14: Active power procedure – P(DI) internal ......................................................... 20 Fig. 15: Reactive power procedure – cosφ (DI)............................................................ 21 Fig. 16: Example cosφ (AI) characteristic curve ........................................................... 22 Fig. 17: Reactive power procedure – cosφ (AI) control ................................................ 22 Fig. 18: Reactive power procedure – cosφ (P) control ................................................. 23 Fig. 19: Reactive power procedure – cosφ (U) control ................................................. 24 Fig. 20: Reactive power procedure – Q(DI) control...................................................... 25 Fig. 21: Q(AI) characteristic curve ............................................................................... 26 Fig. 22: Reactive power procedure – Q(AI) control ...................................................... 26 Fig. 23: Reactive power procedure – Q(U) control....................................................... 27 Fig. 24: Enabling Power Control .................................................................................. 29 Fig. 25: Power Control online values ........................................................................... 29 meteocontrol Power Control 33| 34 Spicherer Str. 48 D-86157 Augsburg Phone +49 (0) 821 / 3 46 66-88 Fax +49 (0) 821 / 3 46 66-11 technik@meteocontrol.de www.meteocontrol.de Text and illustrations represent state-of-the-art technology at the time of printing May be subject to technical updates We assume no liability for printing errors. Version 20131213