State of Florida Department of Transportation DISTRICT SIX Exhibit

advertisement
Request for Proposal - Exhibit A Scope of Services
Appendix IV
SunGuide TMC Control Room Retrofit Project
State of Florida
Department of Transportation
DISTRICT SIX
Exhibit A
Scope of Services, Appendix IV
90% Submittal Specifications
SunGuide Transportation Management Center (TMC)
Control Room Retrofit Project
Financial Project Number(s): 434834-1-92-01
Proposal/Contract Number: RFP-DOT-14/15-6145HO
STATE OF FLORIDA
DEPARTMENT OF TRANSPORTATION
DISTRICT 6
SunGuide Transportation Management Center (TMC)
Control Room Retrofit Project
Financial Project Number(s): 434834-1-92-01
Proposal/Contract Number: RFP-DOT-13/14-6138
90% SUBMITTAL SPECIFICATIONS
90% SPECIFICATIONS
TABLE OF CONTENTS
FOR
FLORIDA DEPARTMENT OF TRANSPORTATION
SUNGUIDE TRANSPORTATION MANAGEMENT CENTER
CONTROL ROOM RETROFIT PROJECT
District 6
Section
Number
TITLE
DIVISION 2 – EXISTING CONDITIONS
024119
SELECTIVE STRUCTURE DEMOLITION
DIVISION 9 - FINISHES
092216
NON-STRUCTURAL METAL FRAMING
092900
GYPSUM BOARD
096513
RESILIENT BASE AND ACCESSORIES
096813
TILE CARPETING
098413
FIXED SOUND ABSORPTIVE PANELS
099123
INTERIOR PAINTING
DIVISION 12 - FURNISHINGS
123200
MANUFACTURED FURNISHINGS- CONSOLES AND WORKSTATIONS
DIVISION 23 - HEATING VENTILATING AND AIR CONDITIONING
230593
TESTING, ADJUSTING, AND BALANCING FOR HVAC
DIVISION 26 - ELECTRICAL
260519
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
260526
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
260529
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
260533
RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
260543
UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS
260544
SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND CABLING
260553
IDENTIFICATION FOR ELECTRICAL SYSTEMS
260943.16
ADDRESSABLE-FIXTURE LIGHTING CONTROLS
262200
LOW-VOLTAGE TRANSFORMERS
262416
PANELBOARDS
262726
WIRING DEVICES
262813
FUSES
262816
ENCLOSED SWITCHES AND CIRCUIT BREAKERS
265100
INTERIOR LIGHTING
END OF TABLE OF CONTENTS
TABLE OF CONTENTS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
000001-1
SECTION 024119 - SELECTIVE STRUCTURE DEMOLITION
PART 1 - GENERAL
1.1
SUMMARY
A.
This Section includes the following:
1.
2.
1.2
Demolition and removal of selected portions of building or structure.
Salvage of existing items to be reused or recycled.
QUALITY ASSURANCE
A.
Demolition Firm Qualifications: An experienced firm that has specialized in demolition work similar in
material and extent to that indicated for this Project.
B.
Regulatory Requirements: Comply with governing EPA notification regulations before beginning
selective demolition. Comply with hauling and disposal regulations of authorities having jurisdiction.
C.
Standards: Comply with ANSI A10.6 and NFPA 241.
D.
Predemolition Conference: Conduct conference at Project site to comply with requirements from Florida
Department of Transportation. Review methods and procedures related to selective demolition including,
but not limited to, the following:
1.
2.
3.
4.
1.3
Inspect and discuss condition of construction to be selectively demolished.
Review and finalize selective demolition schedule and verify availability of materials, demolition
personnel, equipment, and facilities needed to make progress and avoid delays.
Review requirements of work performed by other trades that rely on substrates exposed by
selective demolition operations.
Review areas where existing construction is to remain and requires protection.
PROJECT CONDITIONS
A.
Owner will occupy portions of building immediately adjacent to selective demolition area. Conduct
selective demolition so Owner's operations will not be disrupted.
B.
Conditions existing at time of inspection for bidding purpose will be maintained by Owner as far as
practical.
C.
Hazardous Materials: It is not expected that hazardous materials will be encountered in the Work.
1.
If materials suspected of containing hazardous materials are encountered, do not disturb;
immediately notify Owner.
D.
Storage or sale of removed items or materials on-site is not permitted.
E.
Utility Service: Maintain existing utilities indicated to remain in service and protect them against damage
during selective demolition operations.
SELECTIVE STRUCTURE DEMOLITION
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
024119 - 1
1.
1.4
Maintain fire-protection facilities in service during selective demolition operations.
WARRANTY
A.
Existing Warranties: Remove, replace, patch, and repair materials and surfaces cut or damaged during
selective demolition, by methods and with materials so as not to void existing warranties.
PART 2 - PRODUCTS (Not Used)
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Survey existing conditions and correlate with requirements indicated to determine extent of selective
demolition required.
B.
Inventory and record the condition of items to be removed and reinstalled and items to be removed and
salvaged.
C.
When unanticipated mechanical, electrical, or structural elements that conflict with intended function or
design are encountered, investigate and measure the nature and extent of conflict. Promptly submit a
written report to Owner.
D.
Survey of Existing Conditions: Record existing conditions by use of preconstruction photographs.
3.2
UTILITY SERVICES AND MECHANICAL/ELECTRICAL SYSTEMS
A.
Existing Services/Systems: Maintain services/systems indicated to remain and protect them against
damage during selective demolition operations.
B.
Service/System Requirements: Locate, identify, disconnect, and seal or cap off indicated utility services
and mechanical/electrical systems serving areas to be selectively demolished.
1.
2.
3.
3.3
Owner will arrange to shut off indicated services/systems when requested by Contractor.
If services/systems are required to be removed, relocated, or abandoned, before proceeding with
selective demolition provide temporary services/systems that bypass area of selective demolition
and that maintain continuity of services/systems to other parts of building.
Cut off pipe or conduit in walls or partitions to be removed. Cap, valve, or plug and seal
remaining portion of pipe or conduit after bypassing.
PREPARATION
A.
Temporary Facilities: Provide temporary barricades and other protection required to prevent injury to
people and facilities to remain.
1.
2.
Provide protection to ensure safe passage of people around selective demolition area and to and
from occupied portions of building.
Protect walls, ceilings, floors, and other existing finish work that are to remain or that are exposed
during selective demolition operations.
SELECTIVE STRUCTURE DEMOLITION
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
024119 - 2
3.
4.
3.4
Cover and protect furniture, furnishings, and equipment that have not been removed.
Comply with requirements for temporary enclosures, dust control, and cooling specified by
Owner.
SELECTIVE DEMOLITION, GENERAL
A.
General: Demolish and remove existing construction only to the extent required by new construction and
as indicated. Use methods required to complete the Work within limitations of governing regulations and
as follows:
1.
2.
3.
4.
5.
B.
Removed and Salvaged Items:
1.
2.
3.
4.
5.
C.
2.
3.
4.
3.5
Clean salvaged items.
Pack or crate items after cleaning. Identify contents of containers.
Store items in a secure area until delivery to Owner.
Transport items to Owner's storage area designated by Owner.
Protect items from damage during transport and storage.
Removed and Reinstalled Items:
1.
D.
Neatly cut openings and holes plumb, square, and true to dimensions required. Use cutting
methods least likely to damage construction to remain or adjoining construction. Use hand tools
or small power tools designed for sawing or grinding, not hammering and chopping, to minimize
disturbance of adjacent surfaces.
Cut or drill from the exposed or finished side into concealed surfaces to avoid marring existing
finished surfaces.
At concealed spaces, such as duct and pipe interiors, verify condition and contents of hidden space
before starting flame-cutting operations. Maintain fire watch and portable fire-suppression
devices during flame-cutting operations.
Maintain adequate ventilation when using cutting torches.
Dispose of demolished items and materials promptly.
Clean and repair items to functional condition adequate for intended reuse. Paint equipment to
match new equipment.
Pack or crate items after cleaning and repairing. Identify contents of containers.
Protect items from damage during transport and storage.
Reinstall items in locations indicated. Comply with installation requirements for new materials
and equipment. Provide connections, supports, and miscellaneous materials necessary to make
item functional for use indicated.
Existing Items to Remain: Protect construction indicated to remain against damage and soiling during
selective demolition. When permitted by Owner, items may be removed to a suitable, protected storage
location during selective demolition and cleaned and reinstalled in their original locations after selective
demolition operations are complete.
DISPOSAL OF DEMOLISHED MATERIALS
A.
General: Except for items or materials indicated to be recycled, reused, salvaged, reinstalled, or
otherwise indicated to remain Owner's property, remove demolished materials from Project site and
legally dispose of them in an EPA-approved landfill.
1.
2.
Do not allow demolished materials to accumulate on-site.
Remove and transport debris in a manner that will prevent spillage on adjacent surfaces and areas.
SELECTIVE STRUCTURE DEMOLITION
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
024119 - 3
3.
B.
3.6
Comply with requirements specified in Division 01 Section "Construction Waste Management and
Disposal."
Burning: Do not burn demolished materials.
CLEANING
A.
Clean adjacent structures and improvements of dust, dirt, and debris caused by selective demolition
operations. Return adjacent areas to condition existing before selective demolition operations began.
END OF SECTION 024119
SELECTIVE STRUCTURE DEMOLITION
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
024119 - 4
SECTION 092216 - NON-STRUCTURAL METAL FRAMING
PART 1 - GENERAL
1.1
SUMMARY
A.
This Section includes non-load-bearing steel framing members for the following applications:
1.
2.
Interior framing systems (e.g., supports for partition walls, framed soffits, furring, etc.).
Interior suspension systems (e.g., supports for ceilings, suspended soffits, etc.).
PART 2 - PRODUCTS
2.1
NON-LOAD-BEARING STEEL FRAMING, GENERAL
A.
Recycled Content of Steel Products: Provide products with average recycled content of steel products
such that postconsumer recycled content plus one-half of preconsumer recycled content is not less than 25
percent.
B.
Framing Members, General: Comply with ASTM C 754 for conditions indicated.
1.
2.2
Steel Sheet Components: Comply with ASTM C 645 requirements for metal, unless otherwise
indicated.
SUSPENSION SYSTEM COMPONENTS
A.
Tie Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper, 0.0625-inch- diameter wire, or
double strand of 0.0475-inch- diameter wire.
B.
Hanger Attachments to Concrete:
1.
Anchors: Fabricated from corrosion-resistant materials with holes or loops for attaching wire
hangers and capable of sustaining, without failure, a load equal to 5 times that imposed by
construction as determined by testing according to ASTM E 488 by an independent testing
agency.
a.
Type: Postinstalled, chemical anchor or Postinstalled, expansion anchor.
C.
Wire Hangers: ASTM A 641/A 641M, Class 1 zinc coating, soft temper, 0.162-inch diameter.
D.
Furring Channels (Furring Members):
1.
2.
Cold-Rolled Channels: 0.0538-inch bare-steel thickness, with minimum 1/2-inch- wide flanges,
3/4 inch deep.
Steel Studs: ASTM C 645.
a.
b.
Minimum Base-Metal Thickness: 0.0312 inch.
Depth: As indicated on Drawings; if not indicated as required on ASTM C754.
NON-STRUCTURAL METAL FRAMING
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
092216 - 1
3.
Hat-Shaped, Rigid Furring Channels: ASTM C 645, 7/8 inch deep.
a.
E.
Grid Suspension System for Ceilings: ASTM C 645, direct-hung system composed of main beams and
cross-furring members that interlock.
1.
Products: Subject to compliance with requirements, provide one of the following:
a.
b.
c.
2.3
Minimum Base Metal Thickness: 0.0312 inch.
Armstrong World Industries, Inc.; Drywall Grid Systems.
Chicago Metallic Corporation; [640-C] [Fire Front 650-C] [660-C] [Fire Front 670-C]
Drywall Furring System.
USG Corporation; Drywall Suspension System.
STEEL FRAMING FOR FRAMED ASSEMBLIES
A.
Steel Studs and Runners: ASTM C 645.
1.
2.
B.
Minimum Base-Metal Thickness: 0.0312 inch.
Depth: As indicated on Drawings.
Firestop Tracks: Top runner manufactured to allow partition heads to expand and contract with
movement of the structure while maintaining continuity of fire-resistance-rated assembly indicated; in
thickness not less than indicated for studs and in width to accommodate depth of studs.
1.
Products: Subject to compliance with requirements, provide one of the following:
a.
b.
C.
Flat Strap and Backing Plate: Steel sheet for blocking and bracing in length and width indicated.
1.
D.
Depth: 1-1/2 inches.
Clip Angle: Not less than 1-1/2 by 1-1/2 inches, 0.068-inch- thick, galvanized steel.
Hat-Shaped, Rigid Furring Channels: ASTM C 645.
1.
2.
F.
Minimum Base-Metal Thickness: 0.0312 inch.
Cold-Rolled Channel Bridging: 0.0538-inch bare-steel thickness, with minimum 1/2-inch- wide flanges.
1.
2.
E.
Fire Trak Corp.; Fire Trak.
Metal-Lite, Inc.; The System.
Minimum Base Metal Thickness: 0.0312 inch.
Depth: 7/8 inch.
Cold-Rolled Furring Channels: 0.0538-inch bare-steel thickness, with minimum 1/2-inch- wide flanges.
1.
2.
3.
Depth: As indicated on Drawings.
Furring Brackets: Adjustable, corrugated-edge type of steel sheet with minimum bare-steel
thickness of 0.0312 inch.
Tie Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper, 0.0625-inch- diameter wire,
or double strand of 0.0475-inch- diameter wire.
NON-STRUCTURAL METAL FRAMING
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
092216 - 2
G.
2.4
Z-Shaped Furring: With slotted or nonslotted web, face flange of 1-1/4 inches, wall attachment flange of
7/8 inch, minimum bare-metal thickness of 0.0179 inch, and depth required to fit insulation thickness
indicated.
AUXILIARY MATERIALS
A.
General: Provide auxiliary materials that comply with referenced installation standards.
1.
Fasteners for Metal Framing: Of type, material, size, corrosion resistance, holding power, and
other properties required to fasten steel members to substrates.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine areas and substrates, with Installer present, and including welded hollow-metal frames, cast-in
anchors, and structural framing, for compliance with requirements and other conditions affecting
performance.
1.
3.2
PREPARATION
A.
Suspended Assemblies: Coordinate installation of suspension systems with installation of overhead
structure to ensure that inserts and other provisions for anchorages to building structure have been
installed to receive hangers at spacing required to support the Work and that hangers will develop their
full strength.
1.
3.3
Furnish concrete inserts and other devices indicated to other trades for installation in advance of
time needed for coordination and construction.
INSTALLATION, GENERAL
A.
Installation Standard: ASTM C 754, except comply with framing sizes and spacing indicated.
1.
3.4
Proceed with installation only after unsatisfactory conditions have been corrected.
Gypsum Board Assemblies:
framing installation.
Also comply with requirements in ASTM C 840 that apply to
B.
Install supplementary framing, and blocking to support fixtures, equipment services, heavy trim,
furnishings, or similar construction.
C.
Install bracing at terminations in assemblies.
D.
Do not bridge building control and expansion joints with non-load-bearing steel framing members.
Frame both sides of joints independently.
INSTALLING SUSPENSION SYSTEMS
NON-STRUCTURAL METAL FRAMING
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
092216 - 3
A.
Install suspension system components in sizes and spacings indicated on Drawings, but not less than
those required by referenced installation standards for assembly types and other assembly components
indicated.
B.
Isolate suspension systems from building structure where they abut or are penetrated by building structure
to prevent transfer of loading imposed by structural movement.
C.
Suspend hangers from building structure as follows:
1.
Install hangers plumb and free from contact with insulation or other objects within ceiling plenum
that are not part of supporting structural or suspension system.
a.
Splay hangers only where required to miss obstructions and offset resulting horizontal
forces by bracing, countersplaying, or other equally effective means.
2.
Where width of ducts and other construction within ceiling plenum produces hanger spacings that
interfere with locations of hangers required to support standard suspension system members,
install supplemental suspension members and hangers in the form of trapezes or equivalent
devices.
3.
Wire Hangers: Secure by looping and wire tying, either directly to structures or to inserts, eye
screws, or other devices and fasteners that are secure and appropriate for substrate, and in a
manner that will not cause hangers to deteriorate or otherwise fail.
Flat Hangers: Secure to structure, including intermediate framing members, by attaching to
inserts, eye screws, or other devices and fasteners that are secure and appropriate for structure and
hanger, and in a manner that will not cause hangers to deteriorate or otherwise fail.
Do not attach hangers to permanent metal forms. Furnish cast-in-place hanger inserts that extend
through forms.
Do not connect or suspend steel framing from ducts, pipes, or conduit.
4.
5.
6.
D.
Fire-Resistance-Rated Assemblies: Wire tie furring channels to supports.
E.
Grid Suspension Systems: Attach perimeter wall track or angle where grid suspension systems meet
vertical surfaces. Mechanically join main beam and cross-furring members to each other and butt-cut to
fit into wall track.
F.
Installation Tolerances: Install suspension systems that are level to within 1/8 inch in 12 feet measured
lengthwise on each member that will receive finishes and transversely between parallel members that will
receive finishes.
3.5
INSTALLING FRAMED ASSEMBLIES
A.
Install studs so flanges within framing system point in same direction.
1.
Space studs as follows:
a.
b.
B.
Single-Layer Application: 16 inches o.c., unless otherwise indicated.
Multilayer Application: 16 inches o.c., unless otherwise indicated.
Install tracks (runners) at floors and overhead supports. Extend framing full height to structural supports
or substrates above suspended ceilings, except where partitions are indicated to terminate at suspended
ceilings. Continue framing around ducts penetrating partitions above ceiling.
NON-STRUCTURAL METAL FRAMING
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
092216 - 4
1.
Slip-Type Head Joints: Where framing extends to overhead structural supports, install to produce
joints at tops of framing systems that prevent axial loading of finished assemblies.
2.
Other Framed Openings: Frame openings other than door openings the same as required for door
openings, unless otherwise indicated. Install framing below sills of openings to match framing
required above door heads.
C.
Direct Furring:
1.
Attach to concrete or masonry with stub nails, screws designed for masonry attachment, or
powder-driven fasteners spaced 24 inches o.c.
D.
Installation Tolerance: Install each framing member so fastening surfaces vary not more than 1/8 inch
from the plane formed by faces of adjacent framing.
END OF SECTION 092216
NON-STRUCTURAL METAL FRAMING
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
092216 - 5
SECTION 092900 - GYPSUM BOARD
PART 1 - GENERAL
1.1
SUMMARY
A.
1.2
This Section includes the following:
1.
Interior gypsum board.
SUBMITTALS
A.
Product Data: For each type of product indicated.
B.
Samples: For the following products:
1.
Trim Accessories: Full-size Sample in 12-inch- long length for each trim accessory
indicated.
1.3
STORAGE AND HANDLING
A.
1.4
Store materials inside under cover and keep them dry and protected against damage from weather,
condensation, direct sunlight, construction traffic, and other causes. Stack panels flat to prevent
sagging.
PROJECT CONDITIONS
A.
Environmental Limitations:
Comply with ASTM C 840 requirements or gypsum board
manufacturer's written recommendations, whichever are more stringent.
B.
Do not install interior products until installation areas are enclosed and conditioned.
C.
Do not install panels that are wet, those that are moisture damaged, and those that are mold
damaged.
1.
Indications that panels are wet or moisture damaged include, but are not limited to,
discoloration, sagging, or irregular shape.
2.
Indications that panels are mold damaged include, but are not limited to, fuzzy or splotchy
surface contamination and discoloration.
PART 2 - PRODUCTS
2.1
PANELS, GENERAL
A.
2.2
Size: Provide in maximum lengths and widths available that will minimize joints in each area and
that correspond with support system indicated.
INTERIOR GYPSUM BOARD
A.
General: Complying with ASTM C 36/C 36M or ASTM C 1396/C 1396M, as applicable to type of
gypsum board indicated and whichever is more stringent.
1.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
a.
G-P Gypsum.
b.
National Gypsum Company.
c.
USG Corporation.
d.
Or approved equivalent determined by Department Project Manager
GYPSUM BOARD
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
092900-1
B.
2.3
Ceiling Type: Manufactured to have more sag resistance than regular-type gypsum board.
1.
Thickness: 1/2 inch.
2.
Long Edges: Tapered.
TRIM ACCESSORIES
A.
Interior Trim: ASTM C 1047.
1.
Material: Plastic.
2.
Shapes:
a.
Cornerbead.
b.
Bullnose bead.
c.
L-Bead: L-shaped; exposed long flange receives joint compound.
d.
U-Bead: J-shaped; exposed short flange does not receive joint compound.
e.
Expansion (control) joint.
1)
Product: Amico Drywall Vinyl Control Joint, or Vinyl Corp. CJV16, Surface
Application.
B.
Aluminum Trim: Extruded accessories of profiles and dimensions indicated.
1.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
a.
Fry Reglets Corp.
b.
Gordon, Inc.
c.
Pittcon Industries.
2.
Aluminum: Alloy and temper with not less than the strength and durability properties of
ASTM B 221, Alloy 6063-T5.
3.
Finish: Corrosion-resistant primer compatible with joint compound and finish materials
specified.
2.4
JOINT TREATMENT MATERIALS
A.
General: Comply with ASTM C 475/C 475M.
B.
Joint Tape:
1.
Interior Gypsum Wallboard: Paper.
C.
Joint Compound for Interior Gypsum Wallboard: For each coat use formulation that is compatible
with other compounds applied on previous or for successive coats.
1.
Pre filling: At open joints and damaged surface areas, use setting-type taping compound.
2.
Embedding and First Coat: For embedding tape and first coat on joints, fasteners, and trim
flanges, use setting-type taping compound.
3.
Fill Coat: For second coat, use setting-type, sandable topping compound.
4.
Finish Coat: For third coat, use setting-type, sandable topping compound.
5.
Skim Coat: For final coat of Level 5 finish, use high-build interior coating product designed
for application by airless sprayer and to be used instead of skim coat to produce Level 5
finish.
D.
Joint Compound for Tile Backing Panels:
1.
Water-Resistant Gypsum Backing Board: Use setting-type taping compound and settingtype, sandable topping compound.
2.
Cementitious Backer Units: As recommended by backer unit manufacturer.
2.5
AUXILIARY MATERIALS
A.
General: Provide auxiliary materials that comply with referenced installation standards and
manufacturer's written recommendations.
GYPSUM BOARD
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
092900-2
B.
Laminating Adhesive: Adhesive or joint compound recommended for directly adhering gypsum
panels to continuous substrate. Use adhesives that have a VOC content of 50 g/L or less when
calculated according to 40 CFR 59, Subpart D (EPA Method 24).
C.
Steel Drill Screws: ASTM C 1002, unless otherwise indicated.
1.
Use screws complying with ASTM C 954 for fastening panels to steel members from 0.033
to 0.112 inch thick.
2.
For fastening cementitious backer units, use screws of type and size recommended by panel
manufacturer.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine areas and substrates, with Installer present, and including welded hollow-metal frames and
framing, for compliance with requirements and other conditions affecting performance.
B.
Examine panels before installation.
damaged.
C.
Proceed with installation only after unsatisfactory conditions have been corrected.
3.2
Reject panels that are wet, moisture damaged, and mold
APPLYING AND FINISHING PANELS, GENERAL
A.
Comply with ASTM C 840.
B.
Install ceiling panels across framing to minimize the number of abutting end joints and to avoid
abutting end joints in central area of each ceiling. Stagger abutting end joints of adjacent panel’s
not less than one framing member.
C.
Install panels with face side out. Butt panels together for a light contact at edges and ends with not
more than 1/16 inch of open space between panels. Do not force into place.
D.
Locate edge and end joints over supports, except in ceiling applications where intermediate supports
or gypsum board back-blocking is provided behind end joints. Do not place tapered edges against
cut edges or ends. Stagger vertical joints on opposite sides of partitions. Do not make joints other
than control joints at corners of framed openings.
E.
Form control and expansion joints with space between edges of adjoining gypsum panels.
F.
Cover both faces of support framing with gypsum panels in concealed spaces (above ceilings, etc.),
except in chases braced internally.
1.
Unless concealed application is indicated or required for sound, fire, air, or smoke ratings,
coverage may be accomplished with scraps of not less than 8 sq. ft. in area.
2.
Fit gypsum panels around ducts, pipes, and conduits.
3.
Where partitions intersect structural members projecting below underside of floor/roof slabs
and decks, cut gypsum panels to fit profile formed by structural members; allow 1/4- to 3/8inch-wide joints to install sealant.
G.
Isolate perimeter of gypsum board applied to non-load-bearing partitions at structural abutments,
except floors. Provide 1/4- to 1/2-inch- wide spaces at these locations, and trim edges with edge
trim where edges of panels are exposed. Seal joints between edges and abutting structural surfaces
with acoustical sealant.
GYPSUM BOARD
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
092900-3
H.
3.3
Attachment to Steel Framing: Attach panels so leading edge or end of each panel is attached to
open (unsupported) edges of stud flanges first.
APPLYING INTERIOR GYPSUM BOARD
A.
Install interior gypsum board in the following locations:
1.
Ceiling Type: Ceiling surfaces.
2.
B.
Single-Layer Application:
1.
On partitions/walls, apply gypsum panels vertically (parallel to framing), unless otherwise
indicated or required by fire-resistance-rated assembly, and minimize end joints.
a.
Stagger abutting end joints not less than one framing member in alternate courses of
panels.
b.
At stairwells and other high walls, install panels horizontally, unless otherwise
indicated or required by fire-resistance-rated assembly.
2.
Fastening Methods: Apply gypsum panels to supports with steel drill screws.
C.
Multilayer Application:
1.
On partitions/walls, apply gypsum board indicated for base layers and face layers vertically
(parallel to framing) with joints of base layers located over stud or furring member and facelayer joints offset at least one stud or furring member with base-layer joints, unless otherwise
indicated or required by fire-resistance-rated assembly. Stagger joints on opposite sides of
partitions.
2.
Fastening Methods: Fasten base layers and face layers separately to supports with screws.
3.4
INSTALLING TRIM ACCESSORIES
A.
General: For trim with back flanges intended for fasteners, attach to framing with same fasteners
used for panels. Otherwise, attach trim according to manufacturer's written instructions.
B.
Control Joints: Install control joints according to ASTM C 840 and in specific locations approved
by Architect for visual effect.
C.
Interior Trim: Install in the following locations:
1.
Cornerbead: Use at outside corners, unless otherwise indicated.
2.
L-Bead: Use where indicated.
3.
U-Bead: Use at exposed panel edges.
4.
Curved-Edge Cornerbead: Use at curved openings.
D.
Aluminum Trim: Install in locations indicated on Drawings.
3.5
FINISHING GYPSUM BOARD
A.
General: Treat gypsum board joints, interior angles, edge trim, control joints, penetrations, fastener
heads, surface defects, and elsewhere as required to prepare gypsum board surfaces for decoration.
Promptly remove residual joint compound from adjacent surfaces.
B.
Prefill open joints, rounded or beveled edges, and damaged surface areas.
C.
Apply joint tape over gypsum board joints, except those with trim having flanges not intended for
tape.
D.
Gypsum Board Finish Levels: Finish panels to levels indicated below and according to ASTM C
840:
1.
Level 4: At ceiling panel surfaces that will be exposed to view, unless otherwise indicated.
GYPSUM BOARD
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
092900-4
2.
E.
3.6
a.
Primer and its application to surfaces are specified in other Division 9 Sections.
Level 5: At all locations unless indicated otherwise Drawings.
a.
Primer and its application to surfaces are specified in other Division 9 Sections.
Cementitious Backer Units: Finish according to manufacturer's written instructions.
PROTECTION
A.
Protect installed products from damage from weather, condensation, direct sunlight, construction,
and other causes during remainder of the construction period.
B.
Remove and replace panels that are wet, moisture damaged, and mold damaged.
1.
Indications that panels are wet or moisture damaged include, but are not limited to,
discoloration, sagging, or irregular shape.
2.
Indications that panels are mold damaged include, but are not limited to, fuzzy or splotchy
surface contamination and discoloration.
END OF SECTION 092900
GYPSUM BOARD
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
092900-5
SECTION 096513 - RESILIENT BASE AND ACCESSORIES
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary Conditions and
Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
Section Includes:
1.
2.
1.3
Resilient base.
Resilient molding accessories.
SUBMITTALS
A.
Product Data: For each type of product indicated.
B.
Shop drawings showing exterior and interior corner installation and joints. Shop drawing showing each
resilient molding accessory condition and each metal edge strip condition.
C.
Samples for Verification: For each type of product indicated, in manufacturer's standard-size Samples
but not less than 12 inches long, of each resilient product color, texture, and pattern required.
1.4
DELIVERY, STORAGE, AND HANDLING
A.
1.5
Store resilient products and installation materials in dry spaces protected from the weather, with ambient
temperatures maintained within range recommended by manufacturer, but not less than 50 deg F or more
than 90 deg F.
EXTRA MATERIALS
A.
Furnish extra materials that match products installed and that are packaged with protective covering for
storage and identified with labels describing contents.
1.
Furnish not less than 10 linear feet for every or fraction thereof, of each type, color, pattern, and
size of resilient product installed.
PART 2 - PRODUCTS
2.1
RESILIENT BASE
A.
Basis of Design; “Roppe-6” x .080 vinyl base” Styles: Colors: 619 Java. (Or approved equivalent
determined by Department Project Manager)
B.
Resilient Base Standard: ASTM F 1861.
RESILIENT BASE AND ACCESSORIES
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
096513-1
1.
2.
Material Requirement: Type TV (Thermoplastic Vinyl).
Manufacturing Method: Group 1 (solid, homogeneous).
C.
Minimum Thickness: 0.125 inch, unless otherwise indicated.
D.
Lengths: Coils in manufacturer's standard length.
E.
Outside Corners: Job formed.
F.
Inside Corners: Job formed.
2.2
RESILIENT MOLDING ACCESSORY
A.
Resilient Molding Accessory:
1.
Manufacturers: provide products by one of the following:
a.
Roppe Corporation, USA.
b.
Johnsonite.
c.
R.C.A. Rubber Company (The).
d.
Flexco, Inc.
e.
Or approved equivalent determined by Department Project Manager
B.
Description: Carpet edge for glue-down applications; reducer strip for resilient floor covering; joiner for
resilient tile and carpet; transition strips.
C.
Material: Rubber.
2.3
INSTALLATION MATERIALS
A.
Trowelable Leveling and Patching Compounds: Latex-modified, portland cement based or blended
hydraulic-cement-based formulation provided or approved by manufacturer for applications indicated.
B.
Adhesives: Water-resistant type recommended by manufacturer to suit resilient products and substrate
conditions indicated.
1.
Use adhesives that comply with the following limits for VOC content when calculated according
to 40 CFR 59, Subpart D (EPA Method 24):
a.
C.
Cove Base Adhesives: Not more than 50 g/L.
Metal Edge Strips: Extruded aluminum with mill finish of width shown, of height required to protect
exposed edges of tiles, and in maximum available lengths to minimize running joints. Manufacturer:
Schluter Systems, unless otherwise indicated
RESILIENT BASE AND ACCESSORIES
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
096513-2
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine substrates, with Installer present, for compliance with requirements for maximum moisture
content and other conditions affecting performance of the Work.
B.
Verify that finishes of substrates comply with tolerances and other requirements specified in other
Sections and that substrates are free of cracks, ridges, depressions, scale, and foreign deposits that might
interfere with adhesion of resilient products.
C.
Proceed with installation only after unsatisfactory conditions have been corrected.
3.2
PREPARATION
A.
Prepare substrates according to manufacturer's written instructions to ensure adhesion of resilient
products.
B.
Fill cracks, holes, and depressions in substrates with trowelable leveling and patching compound and
remove bumps and ridges to produce a uniform and smooth substrate.
C.
Do not install resilient products until they are same temperature as the space where they are to be
installed.
3.3
RESILIENT BASE INSTALLATION
A.
Comply with manufacturer's written instructions for installing resilient base.
B.
Install resilient base in lengths as long as practicable without gaps at seams and with tops of adjacent
pieces aligned.
C.
Tightly adhere resilient base to substrate throughout length of each piece, with base in continuous contact
with horizontal and vertical substrates.
D.
Do not stretch resilient base during installation.
E.
On masonry surfaces or other similar irregular substrates, fill voids along top edge of resilient base with
manufacturer's recommended adhesive filler material.
F.
Job-Formed Corners:
1.
2.
3.
3.4
Outside Corners: Use straight pieces of maximum lengths possible. Form without producing
discoloration (whitening) at bends.
Inside Corners: Use straight pieces of maximum lengths possible.
Strictly follow manufacturer’s published recommendations.
RESILIENT ACCESSORY INSTALLATION
A.
Comply with manufacturer's written instructions for installing resilient accessories.
RESILIENT BASE AND ACCESSORIES
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
096513-3
B.
Resilient Molding Accessories: Butt to adjacent materials and tightly adhere to substrates throughout
length of each piece. Install reducer strips at edges of carpet and resilient floor covering that would
otherwise be exposed.
C.
Install metal edge strips in strict accordance with manufacturer’s published recommendations and shop
drawings.
3.5
CLEANING AND PROTECTION
A.
Comply with manufacturer's written instructions for cleaning and protection of resilient products.
B.
Perform the following operations immediately after completing resilient product installation:
1.
C.
Remove adhesive and other blemishes from exposed surfaces.
Protect resilient products from mars, marks, indentations, and other damage from construction operations
and placement of equipment and fixtures during remainder of construction period.
END OF SECTION 096513
RESILIENT BASE AND ACCESSORIES
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
096513-4
SECTION 096813 - TILE CARPETING
PART 1 - GENERAL
1.1
SUMMARY
A.
This Section includes modular, non-virgin PVC free carpet tile.
B.
Related Sections include the following:
1.
Section 096513 - "Resilient Base and Accessories" for resilient wall base and accessories
installed with carpet tile.
1.2
SUBMITTALS
A.
Product Data: For each type of product indicated. Include manufacturer's written data on
physical characteristics, durability, and fade resistance. Include installation recommendations
for each type of substrate.
1.
Include product data for installation adhesive, including printed statement of VOC
content.
B.
Shop Drawings: Show the following:
1.
2.
3.
4.
5.
6.
7.
8.
9.
C.
Doorways, enclose walls or partitions, and locations where cutouts are required in carpet
tiles.
Carpet tile type, color, and dye lot.
Type of installation.
Pattern of installation.
Pattern type, location, and direction.
Pile direction.
Type, color, and location of insets and borders.
Type, color, and location of edge, transition, and other accessory strips.
Transition details to other flooring materials.
Samples: For each of the following products and for each color and texture required. Label
each Sample with manufacturer's name, material description, color, pattern, and designation
indicated on Drawings and in schedules.
1.
2.
Carpet Tile: Full-size Sample.
Exposed Edge, Transition, and other Accessory Stripping: 12-inch- long Samples.
D.
Qualification Data: For Installer.
E.
Product Test Reports: Based on evaluation of comprehensive tests performed by a qualified
testing agency.
F.
Maintenance Data: For carpet tiles to include in maintenance manuals. Include the following:
TILE CARPETING
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
096813-1
1.
2.
G.
1.3
Methods for maintaining carpet tile, including cleaning and stain-removal products and
procedures and manufacturer's recommended maintenance schedule.
Precautions for cleaning materials and methods that could be detrimental to carpet tile.
Warranty: Special warranty specified in this Section.
QUALITY ASSURANCE
A.
Installer Qualifications: An experienced installer who is certified by the Floor Covering
Installation Board or who can demonstrate compliance with its certification program
requirements.
B.
Fire-Test-Response Characteristics: Provide products with the critical radiant flux classification
indicated in Part 2, as determined by testing identical products per ASTM E 648 by an
independent testing and inspecting agency acceptable to authorities having jurisdiction.
1.4
DELIVERY, STORAGE, AND HANDLING
A.
1.5
Comply with CRI 104, Section 5, "Storage and Handling."
WARRANTY
A.
Special Warranty for Carpet Tiles: Manufacturer's standard form in which manufacturer agrees
to repair or replace components of carpet tile installation that fail in materials or workmanship
within specified warranty period.
1.
2.
3.
1.6
Warranty does not include deterioration or failure of carpet tile due to unusual traffic,
failure of substrate, vandalism, or abuse.
Failures include, but are not limited to, more than 10 percent loss of face fiber, edge
raveling, snags, runs, and delaminating.
Warranty Period: 10 years from date of Substantial Completion.
EXTRA MATERIALS
A.
Furnish extra materials described below, before installation begins, that match products
installed and that are packaged with protective covering for storage and identified with labels
describing contents.
1.
Carpet Tile: Full-size units equal to 5 percent of amount installed for each type indicated,
but not less than 10 sq. yd.
TILE CARPETING
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
096813-2
PART 2 - PRODUCTS
2.1
ACCEPTABLE MANUFACTURERS:
A.
2.2
Basis of Design: Bentley Prince Street, Inc.; Style: So Vintage; Style Number: 4SQ260620R
(Or approved equivalent determined by Department Project Manager)
CARPET TILE
A.
Color: Photoplay Topics; Number: 407230.
B.
Fiber: Ultron Color cf nylon; 6,6 by Ascend.
C.
Applied Soil-Resistance Treatment: Manufacturer's standard material.
D.
Carpet tile shall be PVC free with cushioned backing.
E.
Antimicrobial Treatment: Manufacturer's standard material.
F.
Performance Characteristics: As follows:
1.
Radiant Panel Classification: Class 1 per ASTM E648.
2.
Flaming Mode: <450.
2.3
INSTALLATION ACCESSORIES
A.
Trowelable Leveling and Patching Compounds: Latex-modified, hydraulic-cement-based
formulation provided or recommended by carpet tile manufacturer.
B.
Adhesives: Water-resistant, mildew-resistant, nonstaining, pressure-sensitive type to suit
products and subfloor conditions indicated, that complies with flammability requirements for
installed carpet tile and is recommended by carpet tile manufacturer for releasable installation.
1.
VOC Limits: Provide adhesives with VOC content not more than 50 g/L when calculated
according to 40 CFR 59, Subpart D (EPA method 24).
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine substrates, areas, and conditions, with Installer present, for compliance with
requirements for maximum moisture content, alkalinity range, installation tolerances, and other
conditions affecting carpet tile performance. Examine carpet tile for type, color, pattern, and
potential defects.
B.
Concrete Subfloors: Verify that concrete slabs comply with ASTM F 710 and the following:
TILE CARPETING
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
096813-3
1.
2.
C.
3.2
Slab substrates are dry and free of curing compounds, sealers, hardeners, and other
materials that may interfere with adhesive bond. Determine adhesion and dryness
characteristics by performing bond and moisture tests recommended by carpet tile
manufacturer.
Subfloors are free of cracks, ridges, depressions, scale, and foreign deposits.
Proceed with installation only after unsatisfactory conditions have been corrected.
PREPARATION
A.
General: Comply with CRI 104, Section 6.2, "Site Conditions; Floor Preparation," and with
carpet tile manufacturer's written installation instructions for preparing substrates indicated to
receive carpet tile installation.
B.
Use trowelable leveling and patching compounds, according to manufacturer's written
instructions, to fill cracks, holes, depressions, and protrusions in substrates. Fill or level cracks,
holes and depressions 1/8 inch wide or wider and protrusions more than 1/32 inch, unless more
stringent requirements are required by manufacturer's written instructions.
C.
Remove coatings, including curing compounds, and other substances that are incompatible with
adhesives and that contain soap, wax, oil, or silicone, without using solvents. Use mechanical
methods recommended in writing by carpet tile manufacturer.
3.3
INSTALLATION
A.
General: Comply with CRI 104, Section 14, "Carpet Modules," and with carpet tile
manufacturer's written installation instructions.
B.
Installation Method: Quarter Turn.
C.
Maintain dye lot integrity. Does not mix dye lots in same area.
D.
Cut and fit carpet tile to butt tightly to vertical surfaces, permanent fixtures, and built-in
furniture including cabinets, pipes, outlets, edgings, thresholds. Bind or seal cut edges as
recommended by carpet tile manufacturer.
E.
Extend carpet tile into toe spaces, door reveals, closets, open-bottomed obstructions, removable
flanges, alcoves, and similar openings.
F.
Maintain reference markers, holes, and openings that are in place or marked for future cutting
by repeating on finish flooring as marked on subfloor. Use nonpermanent, nonstaining marking
device.
G.
Install pattern parallel to video wall and borders.
H.
Stagger joints of carpet tiles so carpet tile grid is offset from access flooring panel grid. Do not
fill seams of access flooring panels with carpet adhesive; keep seams free of adhesive.
TILE CARPETING
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
096813-4
3.4
CLEANING AND PROTECTION
A.
Perform the following operations immediately after installing carpet tile:
1.
2.
3.
Remove excess adhesive, seam sealer, and other surface blemishes using cleaner
recommended by carpet tile manufacturer.
Remove yarns that protrude from carpet tile surface.
Vacuum carpet tile using commercial machine with face-beater element.
B.
Protect installed carpet tile to comply with CRI 104, Section 16, "Protection of Indoor
Installations."
C.
Protect carpet tile against damage from construction operations and placement of equipment and
fixtures during the remainder of construction period. Use protection methods indicated or
recommended in writing by carpet tile manufacturer.
END OF SECTION 096813
TILE CARPETING
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
096813-5
SECTION 098413 - FIXED SOUND-ABSORPTIVE PANELS
PART 1 - GENERAL
1.1
SUMMARY
A.
1.2
This Section includes back-mounted acoustical wall panels.
DEFINITIONS
A.
1.3
NRC: Noise reduction coefficient.
SUBMITTALS
A.
Product Data: For each type of panel edge, core material, and mounting indicated.
B.
Shop Drawings: For acoustical wall panels. Include mounting devices and details; details at panel head,
base, joints, and corners; and details at ceiling, floor base, and wall intersections. Include elevations
showing panel sizes and direction of fabric weave and pattern matching. Indicate panel edge and core
materials.
C.
Samples for Initial Selection:
manufacturer's full range.
D.
Samples for Verification: For the following products. Prepare Samples from same material to be used
for the Work.
1.
Fabric: Full-width by 36-inch- long Sample from dye lot to be used for the Work, and as follows:
a.
b.
c.
2.
3.
4.
5.
For each type of fabric facing material from acoustical wall panel
With specified treatments applied.
Show complete pattern repeat.
Mark top and face of fabric.
Panel Edge: 12-inch- long Sample showing edge profile, corner, and finish.
Core Material: 12-inch- square Sample showing corner.
Mounting Device: Full-size Sample.
Sample Panels: No larger than 36 by 36 inches. Show joints and mounting methods.
E.
Product Certificates: For each type of acoustical wall panel, signed by product manufacturer.
F.
Qualification Data: For fabricator and testing agency.
G.
Product Test Reports: Based on evaluation of comprehensive tests performed by a qualified testing
agency, for each type of acoustical wall panel.
H.
Maintenance Data: For acoustical wall panels to include in maintenance manuals. Include fabric
manufacturers' written cleaning and stain-removal recommendations.
I.
Warranty: Special warranty specified in this Section.
FIXED SOUND-ABSORPTIVE PANELS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
098413 - 1
1.4
QUALITY ASSURANCE
A.
Fabricator Qualifications: Shop that employs skilled workers who custom-fabricate products similar to
those required for this Project and whose products have a record of successful in-service performance.
B.
Source Limitations: Obtain acoustical wall panels through one source from a single manufacturer.
C.
Fire-Test-Response Characteristics: Provide acoustical wall panels with the following surface-burning
characteristics as determined by testing identical products per ASTM E 84 by UL or another testing and
inspecting agency acceptable to authorities having jurisdiction:
1.
2.
D.
Mockups: Build mockups to verify selections made under sample submittals and to demonstrate aesthetic
effects and set quality standards for materials, fabrication, and installation.
1.
E.
1.5
Install mockups in the location and of the size indicated or, if not indicated, as directed by
Architect.
Preinstallation Conference: Conduct conference at Project site.
DELIVERY, STORAGE, AND HANDLING
A.
Comply with fabric and acoustical wall panel manufacturers' written instructions for minimum and
maximum temperature and humidity requirements for shipment, storage, and handling.
B.
Deliver materials and panels in unopened bundles and store in a temperature-controlled dry place with
adequate air circulation.
C.
Protect panel edges from crushing and impact.
1.6
PROJECT CONDITIONS
A.
1.7
Field Measurements: Verify locations of acoustical wall panels by field measurements before fabrication
and indicate measurements on Shop Drawings.
WARRANTY
A.
Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace
components of acoustical wall panels that fail in performance, materials, or workmanship within specified
warranty period.
1.
2.
3.
1.8
Flame-Spread Index: 25 or less.
Smoke-Developed Index: 450 or less.
Failure in performance includes, but is not limited to, acoustical performance.
Failures in materials include, but are not limited to, fabric sagging, distorting, or releasing from
panel edge; or warping of core.
Warranty Period: Two years from date of Substantial Completion.
EXTRA MATERIALS
FIXED SOUND-ABSORPTIVE PANELS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
098413 - 2
A.
Furnish extra materials described below, before installation begins, that match products installed and that
are packaged with protective covering for storage and identified with labels describing contents.
1.
2.
Fabric: For each fabric, color, and pattern installed, provide length equal to 10 percent of amount
installed.
Acoustical Wall Panel Mounting Devices: Full-size units equal to 5 percent of amount installed.
PART 2 - PRODUCTS
2.1
CORE MATERIALS
A.
Glass-Fiber Board: ASTM C 612, Type IA or Types IA and IB; density as specified, unfaced,
dimensionally stable, molded rigid board, with maximum flame-spread and smoke-developed indexes of
25 and 50, respectively.
B.
Products: Basis-of-Design product: Subject to compliance with requirements, provide AlphaSorb Wall
Panel by Acoustical Solutions, Inc. or comparable product (or approved equivalent determined by
Department Project Manager).
2.2
1.
Facing Material: Guilford of Maine FR 701- Style 2100- 100% polyester.
2.
Panel Thickness: nominal 2” thick.
3.
Noise Reduction Coefficient: NRC 1.15.
4.
Panel Width and Height: Match existing panels.
5.
Fabric Color: Chocolate; Number: 793.
FABRICATION
A.
Sound-Absorption Performance: Provide acoustical wall panels with minimum NRCs indicated, as
determined by testing per ASTM C 423 for mounting type specified.
B.
Acoustical Wall Panels: Panel construction consisting of facing material adhered to face, edges and back
border of dimensionally stable core; with rigid edges to reinforce panel perimeter against warpage and
damage.
1.
C.
Fabric Facing: Stretched straight, on the grain, tight, square, and free from puckers, ripples, wrinkles,
sags, blisters, seams, adhesive, or other foreign matter. Applied with visible surfaces fully covered.
1.
2.
3.
D.
Glass-Fiber Board: Resin harden areas of core for attachment of mounting devices.
Where square corners are indicated, tailor corners.
Where radius or other nonsquare corners are indicated, attach facing material so there are no
seams or gathering of material.
Where fabrics with directional or repeating patterns or directional weave are indicated, mark fabric
top and attach fabric in same direction so pattern or weave matches in adjacent panels.
Core-Face Layer: Evenly stretched over core face and edges and securely attached to core; free from
puckers, ripples, wrinkles, sags.
FIXED SOUND-ABSORPTIVE PANELS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
098413 - 3
E.
Dimensional Tolerances of Finished Units: Plus or minus 1/16 inch for the following:
1.
2.
3.
4.
5.
F.
Thickness.
Edge straightness.
Overall length and width.
Squareness from corner to corner.
Chords, radii, and diameters.
Back-Mounting Devices: Concealed on backside of panel, recommended to support weight of
panel, with base-support bracket system where recommended by manufacturer for additional support of
panels, and as follows:
1.
2.
Metal "Z" Clips: Two-part panel clips, with one part of each clip mechanically attached to back of
panel and the other part to wall substrate, designed to allow for panel removal.
As recommended by manufacturer.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine fabric, substrates, blocking, and conditions, with Installer present, for compliance with
requirements, installation tolerances, and other conditions affecting performance of acoustical wall
panels.
1.
3.2
Proceed with installation only after unsatisfactory conditions have been corrected.
INSTALLATION
A.
Install acoustical wall panels in locations indicated with vertical surfaces and edges plumb, top edges
level and in alignment with other panels, faces flush, and scribed to fit adjoining work accurately at
borders and at penetrations.
1.
Cut units to be at least 50 percent of unit width, with facing material extended over cut edge to
match uncut edge. Scribe acoustical wall panels to fit adjacent work. Butt joints tightly.
B.
Comply with acoustical wall panel manufacturer's written instructions for installation of panels using type
of concealed mounting accessories indicated or, if not indicated, as recommended by manufacturer.
Anchor panels securely to supporting substrate.
C.
Match and level fabric pattern and grain among adjacent panels.
D.
Installation Tolerances: As follows:
1.
2.
3.3
Variation from Level and Plumb: Plus or minus 1/16 inch.
Variation of Panel Joints from Hairline: Not more than 1/32 inch wide.
CLEANING
A.
Clip loose threads; remove pills and extraneous materials.
FIXED SOUND-ABSORPTIVE PANELS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
098413 - 4
B.
3.4
Clean panels with fabric facing, on completion of installation, to remove dust and other foreign materials
according to manufacturer's written instructions.
PROTECTION
A.
Provide final protection and maintain conditions, in a manner acceptable to manufacturer and Installer, to
ensure that acoustical wall panels are without damage or deterioration at time of Substantial Completion.
B.
Replace acoustical wall panels that cannot be cleaned and repaired, in a manner approved by Owner,
before time of Substantial Completion.
END OF SECTION 098413
FIXED SOUND-ABSORPTIVE PANELS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
098413 - 5
SECTION 099123 - INTERIOR PAINTING
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary Conditions and
Division 1 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
This Section includes surface preparation and the application of paint systems on the following interior
substrates:
1.
Gypsum board.
SUBMITTALS
A.
Product Data: For each type of product indicated.
B.
Samples: For each finish and for each color and texture required.
1.4
QUALITY ASSURANCE
A.
1.5
MPI Standards:
1.
Products: Complying with MPI standards indicated.
2.
Preparation and Workmanship:
Comply with requirements in "MPI Architectural Painting
Specification Manual" for products and paint systems indicated.
EXTRA MATERIALS
A.
Furnish extra materials described below that are from same production run (batch mix) as materials applied and
that are packaged for storage and identified with labels describing contents.
1.
Quantity: Furnish an additional 5 percent, but not less than 1 gal. of each material and color applied.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
2.2
Manufacturers: Subject to compliance with requirements, provide paint products by one of the following:
1.
Benjamin Moore & Co.
2.
ICI Paints.
3.
Scuff master Architectural Finishes.
4.
Sherwin-Williams Company (The).
5.
Or approved equivalent determined by Department Project Manager.
PAINT, GENERAL
A.
Material Compatibility:
1.
Provide materials for use within each paint system that are compatible with one another and substrates
indicated, under conditions of service and application as demonstrated by manufacturer, based on
testing and field experience.
2.
For each coat in a paint system, provide products recommended in writing by manufacturers of topcoat
for use in paint system and on substrate indicated.
B.
Chemical Components of Field-Applied Interior Paints and Coatings: Provide products that comply with the
following limits for VOC content, exclusive of colorants added to a tint base, when calculated according to
40 CFR 59, Subpart D (EPA Method 24) and the following chemical restrictions; these requirements do not
apply to primers or finishes that are applied in a fabrication or finishing shop:
1.
Flat Paints and Coatings: VOC content of not more than 50 g/L.
2.
Non-flat Paints and Coatings: VOC content of not more than 150 g/L.
INTERIOR PAINTING
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
099123-1
3.
4.
C.
2.3
Aromatic Compounds: Paints and coatings shall not contain more than 1.0 percent by weight of total
aromatic compounds (hydrocarbon compounds containing one or more benzene rings).
Restricted Components: Paints and coatings shall not contain any of the following:
a.
Acrolein.
b.
Acrylonitrile.
c.
Antimony.
d.
Benzene.
e.
Butyl benzyl phthalate.
f.
Cadmium.
g.
Di (2-ethylhexyl) phthalate.
h.
Di-n-butyl phthalate.
i.
Di-n-octyl phthalate.
j.
1,2-dichlorobenzene.
k.
Diethyl phthalate.
l.
Dimethyl phthalate.
m.
Ethylbenzene.
n.
Formaldehyde.
o.
Hexavalent chromium.
p.
Isophorone.
q.
Lead.
r.
Mercury.
s.
Methyl ethyl ketone.
t.
Methyl isobutyl ketone.
u.
Methylene chloride.
v.
Naphthalene.
w.
Toluene (methylbenzene).
x.
1,1,1-trichloroethane.
y.
Vinyl chloride.
Colors: As indicated in Finish Schedule on Drawings.
BLOCK FILLERS
A.
2.4
Interior/Exterior Latex Block Filler: MPI #4.
1.
VOC Content: E Range of E3.
PRIMERS/SEALERS
A.
2.5
Interior Latex Primer/Sealer: MPI #50.
1.
VOC Content: E Range of E2.
METAL PRIMERS
A.
Alkyd Anticorrosive Metal Primer: MPI #79.
1.
VOC Content: E Range of E1.
B.
Waterborne Galvanized-Metal Primer: MPI #134.
1.
VOC Content: E Range of E2.
2.6
LATEX PAINTS
A.
Interior Latex (Flat): MPI #53 (Gloss Level 1).
1.
VOC Content: E Range of E3.
B.
Interior Latex (Eggshell): MPI #52 (Gloss Level 3).
1.
VOC Content: E Range of E2.
C.
Interior Latex (Semigloss): MPI #54 (Gloss Level 5).
1.
VOC Content: E Range of E2.
D.
High-Performance Architectural Latex (Semigloss): MPI #141 (Gloss Level 5).
INTERIOR PAINTING
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
099123-2
1.
2.7
VOC Content: E Range of E2.
ALKYD PAINTS
A.
Interior Alkyd (Semigloss): MPI #47 (Gloss Level 5).
1.
VOC Content: E Range of E1.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine substrates and conditions, with Applicator present, for compliance with requirements for maximum
moisture content and other conditions affecting performance of work.
B.
Maximum Moisture Content of Substrates: When measured with an electronic moisture meter as follows:
1.
Gypsum Board: 12 percent.
C.
Verify suitability of substrates, including surface conditions and compatibility with existing finishes and
primers.
D.
Begin coating application only after unsatisfactory conditions have been corrected and surfaces are dry.
1.
Beginning coating application constitutes Contractor's acceptance of substrates and conditions.
3.2
PREPARATION AND APPLICATION
A.
Comply with manufacturer's written instructions and recommendations in "MPI Architectural Painting
Specification Manual" applicable to substrates indicated.
B.
Clean substrates of substances that could impair bond of paints, including dirt, oil, grease, and incompatible
paints and encapsulates.
1.
Remove incompatible primers and reprime substrate with compatible primers as required to produce
paint systems indicated.
C.
Apply paints to produce surface films without cloudiness, spotting, holidays, laps, brush marks, roller tracking,
runs, sags, ropiness, or other surface imperfections. Cut in sharp lines and color breaks.
D.
Painting Mechanical and Electrical Work: Paint items exposed in equipment rooms and occupied spaces
including, but not limited to, the following:
1.
Mechanical Work:
a.
Uninsulated metal piping.
b.
Uninsulated plastic piping.
c.
Pipe hangers and supports.
d.
Tanks that do not have factory-applied final finishes.
e.
Visible portions of internal surfaces of metal ducts, without liner, behind air inlets and outlets.
f.
Duct, equipment, and pipe insulation having cotton or canvas insulation covering or other
paintable jacket material.
g.
Mechanical equipment that is indicated to have a factory-primed finish for field painting.
2.
Electrical Work:
a.
Switchgear.
b.
Panel-boards.
c.
Electrical equipment that is indicated to have a factory-primed finish for field painting.
E.
Protect work of other trades against damage from paint application. Correct damage to work of other trades by
cleaning, repairing, replacing, and refinishing, as approved by Architect, and leave in an undamaged condition.
F.
At completion of construction activities of other trades, touch up and restore damaged or defaced painted
surfaces.
INTERIOR PAINTING
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
099123-3
3.3
INTERIOR PAINTING SCHEDULE
A.
Gypsum Board Substrates:
1.
Latex System: MPI INT 9.2A.
a.
Prime Coat: Interior latex primer/sealer matching topcoat.
b.
Intermediate Coat: Interior latex matching topcoat.
c.
Topcoat: Interior latex.
END OF SECTION 099123
INTERIOR PAINTING
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
099123-4
SECTION 123200 - MANUFACTURED FURNISHINGS- CONSOLES AND WORKSTATIONS
PART 1 - GENERAL
1.1
SUMMARY
A.
Section Includes:
1.
1.2
Plastic-laminate-faced wood furnishing of stock design for consoles, workstations and bookcases.
SUBMITTALS
A.
Product Data: For each type of product indicated.
B.
Shop Drawings: Include plans, elevations, sections, and details drawings (in PDF format) of console and
equipment layouts for coordination of site measurements, architectural and electrical project elements for
each console type. Provide CAD (PDF format) drawings of each console type with its specific equipment
per application.
C.
Pre-production review, to include a drawing submittal and component listing complete with samples of
selected finish materials upon request.
D.
Samples for Initial Selection: For cabinet finishes and for each type of top material indicated.
E.
Samples for Verification which demonstrate workmanship: 8-by-10-inch Samples for each type of
finish, including top material and the following:
1.
2.
3.
F.
1.3
Section of work surface showing top and ergonomic nosing.
Sample panel construction and finish materials.
Maintain full-size Samples at Project site during construction in an undisturbed condition as a
standard for judging the completed Work. Unless otherwise indicated, approved sample units may
become part of the completed Work if in undisturbed condition at time of Substantial Completion.
Notify Architect of their exact locations.
Warranty: Sample of special warranty.
QUALITY ASSURANCE
A.
Source Limitations:
manufacturer.
B.
Product Designations: Drawings indicate sizes, configurations, and finish material of manufactured wood
furnishings.
1.4
Obtain all manufactured wood furnishings from single source from single
DELIVERY, STORAGE, AND HANDLING
A.
Deliver manufactured wood casework only after carpeting, utility roughing-in, and similar operations that
could damage, soil, or deteriorate casework have been completed in installation areas. If furnishings
MANUFACTURED FURNISHING- CONSOLES AND WORKSTATIONS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
123200 - 1
must be stored in other than installation areas, store only in areas where environmental conditions meet
requirements specified by Owner.
B.
1.5
Keep finished surfaces covered with polyethylene film or other protective covering during handling and
installation.
PROJECT CONDITIONS
A.
1.6
Field Measurements: Verify actual dimensions of existing room sizes and presented layout contiguous
with manufactured wood furnishings by field measurements before fabrication.
COORDINATION
A.
1.7
Coordinate layout with existing access to trench for electrical and data. Ensure that furnishings can
accommodate all electrical and data feeds to not only to the individual unit but all units in unison.
WARRANTY
A.
Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace
components of manufactured wood furnishings (consoles and workstations) that fail in materials or
workmanship within specified warranty period from date of transfer.
1.
Failures include, but are not limited to, the following:
a.
b.
c.
d.
Delamination of components or other failures of glue bond.
Warping of components.
Failure of operating hardware.
Deterioration of finishes.
B.
LIFETIME WARRANTY on all fixed structural frame components;
C.
LIFETIME WARRANTY (parts) on all static exterior panels and work surface components parts; (5
years on labor);
D.
LIFETIME WARRANTY (parts) on all adjustable, sliding or hinged mechanisms or parts (5 years on
labor);
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
Basis-of-Design Product: Subject to compliance with requirements, provide Response Consoles for main
workstations as indicated in drawings and Strategy Consoles for operator console (directly underneath
video wall) as indicated in drawings by Evans Consoles Corporation or comparable product. The console
shall have the following features and capabilities:
1. The console must accommodate a variety of computer, communication, display, environmental
controls and operator interface devices.
MANUFACTURED FURNISHING- CONSOLES AND WORKSTATIONS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
123200 - 2
2.
The console shall include efficient ventilation and wire management systems.
3.
The laminate front and rear panels shall give the console a contemporary appeal with cuttingedge cladding design and color options.
4.
No metal to be used for exterior panels. All exterior panels should have a wood core for superior
acoustics and minimal sound reverberation.
5.
The design of the console shall address the functional, ergonomic and aesthetic requirements of
the particular working environment while complying with accepted human factor design and ergonomic standards for viewing distance, angle, keyboard height, and knee-well space.
6.
The consoles shall be modular, reconfigurable and with an independent steel frame structure.
Design shall facilitate future equipment retrofits and full reconfigurations without requiring any
major modification to the structure or independent exterior cladding.
7.
Consoles must be available in 90 degree configurations, in order to accommodate 4 position clusters.
8.
Consoles must be available in straight configurations, and modular components must be common
with angled configuration in order to reconfigure these consoles if future technology or mission
requirements dictate, with limited cost to the owner.
9.
Consoles must be designed in accordance with the ergonomic standards of ISO, ANSI/HFES,
BIFMA and CSA.
10. The work surface platform shall have smooth edges and transitions, thus avoiding sharp corners
or potential “rib catchers” for operator safety.
11. Sharp edges at the console base and in CPU cavities are not acceptable and represent potential
“knee-banger” operator safety issues. All transitions and curves must have a minimum 5-inch radius.
12. All human-machine interface-related equipment (display, keyboard, mouse, etc.) must travel with
the upper console section. Any variety or combination of input/output devices must be accommodated by the system. Reach and viewing distances/relationships must not be compromised when
console is in standing position.
13. Pinch points must be managed. All pinch points shall be managed according to the appropriate
ergonomic standard.
B.
Structural Frame System
1. The console frame shall be constructed using a combination of precision-tooled minimum 14gauge sheet metal (with min. yield of 27 ksi and modulus of elasticity of 29 x 106 psi) and formed
in such a way as to provide maximum buckling and torsional resistance.
Extrusions shall be constructed of thick wall, custom extruded aluminum as outlined in the table
below.
Component
Upper Beam
Lower Beam, Frame and
Door Columns
2.
Alloy & Temper
6005A-T5
6063-T54
Yield Strength
31 KSI / 100
PSi
30 KSI
Ultimate
Strength
38 KSI
30 KSI
Console frame to be a standalone structure that does not depend on any exterior panels for
structural integrity.
MANUFACTURED FURNISHING- CONSOLES AND WORKSTATIONS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
123200 - 3
B.
C.
3.
The console shall have a modular design allowing multiple re-configuration options. The base
frame shall be independent of the console worksurface thus allowing for various worksurface
options without having the need to change the base frame structure.
4.
The frame must accommodate the installation of an acoustical partition system.
5.
The horizontal frame members shall be constructed with pre-designed ports allowing for flexible
equipment mounting along the length of each module as well as the addition of accessories after
the installation without having the need to do additional drilling.
6.
The console frame shall have provisions for leveler legs to be incorporated into the frame.
7.
The frame structure shall have fully integrated cable management. The base structure will have a
minimum of 3 lateral raceways; the transition from the base to the worksurface will have a
minimum of 2 vertical raceways; and the worksurface will have a lateral raceway location
depending on the size of equipment being mounted in the console. The cable raceways shall be
continuous throughout the entire console layout thus allowing uninterrupted cable management.
Console Cladding
1.
Console panel base cladding shall be fabricated from 3/4” composite solid core with plastic
laminate faces (both sides). Panel cladding edges to receive post applied 1.4 mm PVC edging in
matching or complementary colors.
2.
All panels must attach to the frame with concealed fasteners. Console access panels must be
removable without the use of tools. Front and back panels must be hinged and must be removable
and replaceable without the use of tools.
3.
The end gables must be constructed of a 1" Particle Board with min. density of 45 lb. / ft3 and a
minimum screw holding face of 247 lb, covered by plastic laminate and use a mechanical
fastening system that readily accepts future reconfigurations and additions with no site cutting,
drilling, or machining required. Wood screws shall not be acceptable.
Worksurface
1.
The core of the worksurface shall be constructed using a minimum 1” particleboard (wheat chaff
not acceptable) and shall have High Pressure Laminate (HPL) on both topside and under side of
the worksurface.
2.
The worksurface must be able to sustain a minimum loading in accordance to BIFMA x5.5-2008.
3.
The external worksurface edge (nosing) shall have an ergonomic sloped edge to ensure operator
comfort and eliminate contact stress. The worksurface nosing must be constructed of a high
impact molded urethane edging over an extruded aluminum core. Nosing shall be able to
accommodate minimum radius bends of 12 inch (30 cm) either in a convex or concave
configuration to conform to the console design. The polyurethane nosing must be readily
replaceable if damaged in use without having to remove or replace the entire work surface.
4.
The worksurface should be smooth and level and take into consideration all accepted human factor
criteria, including view, reach distances, keyboard height and knee well space. The worksurface
height must be adjustable.
MANUFACTURED FURNISHING- CONSOLES AND WORKSTATIONS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
123200 - 4
5.
D.
E.
The worksurface shall be supported by an independent steel frame structure and the actuator
columns shall attach directly to the steel frame for added strength and rigidity.
Equipment Mounting
1.
The console equipment mounting system shall accommodate a variety of computer, communication, display and operator interface devices within the enclosure without requiring the need for
outboard storage. The console shall allow front or rear equipment loading with easy interchange
between the two.
2.
The internal frame structure shall be able to accommodate various equipment mounting options
including:
a.
Processor shelves – The shelves shall be available in a fixed, hinged-elbow slide-out or
swing-out option depending on the specific equipment application.
b.
Rack mount Shelves – The rack mount shelves shall be available as fixed or optional slideout. The rack mount shelves shall be available in a 2-point or 4-point mounting
onfiguretion depending on the equipment weight or access requirements. The 4-point
rack mount shelf shall have an optional adjustable depth-mounting bracket to accommodate
varying equipment depths.
3.
The CPU will sit on the processor shelves that are housed within the base of the console. All cables running between equipment shall have a 6-inch separation between power and data. Cables
from equipment shall be managed effectively within the console base frame. The size and spacing of equipment support kits shall be variable to optimize the available equipment mounting area
and maximize the number of devices the console enclosure is capable of accommodating.
4.
When using flat panel monitors, the monitors should be supported on adjustable monitor arms
suspended in a slat wall system, which allows for flexibility in mounting positions. The console
supplier must provide an articulating monitor arm, capable of triple articulation; letting the operator tilt, rotate, raise and/or lower the flat panel monitor. The arm must have 8” in height adjustment and can extend a min of 18” from where it is mounted. An optional adjustable monitor platform will be available providing a minimum 8” of travel front to back. This can be increased with
a longer pole. Assumes lcd monitor on base but can upgrade to an “ARC View” with a maximum
of 4 lcds.
5.
The console supplier shall provide for the following equipment and operator convenience kits:
a.
19” E.I.A. (483 mm) rack mount panels
b.
Pencil drawers
c.
Keyboard drawers
d.
Internal cable management trays and power bars.
Cable Management
1. The frame structure shall have fully integrated cable management.
2.
The base structure will have a minimum of 3 lateral raceways; the transition from the base to the
worksurface will have a minimum of 2 vertical “energy chain” raceways; and the worksurface
will have 1 lateral raceway locations depending on the size of equipment being mounted in the
console.
3.
The cable raceways shall be continuous throughout the entire console layout thus allowing uninterrupted cable management.
MANUFACTURED FURNISHING- CONSOLES AND WORKSTATIONS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
123200 - 5
4.
F.
Additional Operator Features
1. The console supplier must provide storage modules such as mobile storage pedestals, fixed position credenzas and printer cabinets. All accessory storage cabinets, mobile drawer pedestals,
printer enclosures, etc. must be constructed of materials and finishes to match the console exterior. File pedestals must have 5th wheel for extra stability.
2.
G.
H.
Cable management on the monitor deck shall be through grommets to the underside of the
worksurface where cables will be protected by an easily accessible, enclosed, management system, which runs cables horizontally to the energy chain.
The console system must have an optional ventilation fan and grill assembly that enhances natural convection air currents to maintain optimum operating temperatures within the console enclosure while minimizing fan noise.
Partition System
1. The console shall have two optional partition systems, which can be used stand alone or together.
2.
The partition system must be constructed of a 3/4" (19 mm), 45 lb./ft3 Particle Board covered by a
fabric wrap supported by a durable steel cold rolled steel (modulus of elasticity 29 x 106 psi)
frame. Panels material options include acoustic Homesote, cork, HPL or Plexiglas. Hollow core
and freestanding panel systems are optional.
3.
Floating Partition Desktop Slatwall System. The floating partition system must allow for the
height of the partition system to adjust as the worksurface is raised or lowered. The desktop
mounted slatwall partition system should allow for a max height of 12 inches. An integrated
slatwall system is required. Slatwall system should allow for monitor and equipment mounting
and offer the option of built in cable management raceways. Slatwall extrusions and all sheet
metal parts are finished with a durable, black, electrostatic powder coating.
4.
The partition system must be fully integrated into the console system. The Full Height Partition
System must be integrated into the base frame structure. Floating Partition Desktop Slat wall
Systems must be integrated into the monitor deck. A method of reconfiguration between these
two partition systems must be designed into the console in order to accommodate future technology requirements.
Chairs
1. Basis-of-Design Product: Subject to compliance with requirements, provide Aeron Chair by
Herman Miller, Inc (or approved equivalent determined by Department Project Manager).
a. Fully Adjustable function.
b. Colors: Armpads-Black; Base and frame: Graphite; Seat and Back; Carbon
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine areas, with Installer present, for compliance with requirements for installation tolerances,
location of framing and reinforcements, and other conditions affecting performance of manufactured
wood casework.
B.
Proceed with installation only after unsatisfactory conditions have been corrected.
MANUFACTURED FURNISHING- CONSOLES AND WORKSTATIONS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
123200 - 6
3.2
CLEANING AND PROTECTING
A.
Repair or remove and replace defective work as directed on completion of installation.
B.
Clean finished surfaces, touch up as required, and remove or refinish damaged or soiled areas to match
original factory finish, as approved by Owner.
C.
Protection: Provide 6-mil plastic or other suitable water-resistant covering over top surfaces. Tape to
underside of countertop at a minimum of 48 inches. Remove protection at Substantial Completion.
END OF SECTION 123200
MANUFACTURED FURNISHING- CONSOLES AND WORKSTATIONS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
123200 - 7
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract Documents apply to this Section.
SUMMARY
A.
Section Includes:
1.
Balancing Air Systems:
a.
2.
1.3
Variable-air-volume systems.
Pre-occupancy and Post- occupancy Balancing Air Systems ONLY in temporary
occupied spaces in the second floor Rooms 232 and 213. The aim is to comply with
ASHRAE Standards for outside air and maintain spaces temperatures 75 deg F Summer
and 68 deg F Winter.
DEFINITIONS
A.
AABC: Associated Air Balance Council.
B.
NEBB: National Environmental Balancing Bureau.
C.
TAB: Testing, adjusting, and balancing.
D.
TABB: Testing, Adjusting, and Balancing Bureau.
E.
TAB Specialist: An entity engaged to perform TAB Work.
1.4
ACTION SUBMITTALS
1.5
INFORMATIONAL SUBMITTALS
A.
Qualification Data: Within 30 days of Contractor's Notice to Proceed, submit documentation
that the TAB contractor and this Project's TAB team members meet the qualifications specified
in "Quality Assurance" Article.
TESTING, ADJUSTING, AND BALANCING FOR HVAC
Sunguide Transportation Management Center Control Room Retrofit
90% Submittal
230593 - 1
B.
Contract Documents Examination Report: Within 30 days of Contractor's Notice to Proceed,
submit the Contract Documents review report as specified in Part 3.
C.
Strategies and Procedures Plan: Within 30 days of Contractor's Notice to Proceed, submit TAB
strategies and step-by-step procedures as specified in "Preparation" Article.
D.
Certified TAB reports.
E.
Sample report forms.
F.
Instrument calibration reports, to include the following:
1.
2.
3.
4.
5.
1.6
Instrument type and make.
Serial number.
Application.
Dates of use.
Dates of calibration.
QUALITY ASSURANCE
A.
TAB Contractor Qualifications: Engage a TAB entity certified by NEBB
1.
2.
B.
TAB Field Supervisor: Employee of the TAB contractor and certified NEBB.
TAB Technician: Employee of the TAB contractor and who is certified by NEBB as a
TAB technician.
TAB Conference: Meet with Owner on approval of the TAB strategies and procedures plan to
develop a mutual understanding of the details. Require the participation of the TAB field
supervisor and technicians. Provide seven days' advance notice of scheduled meeting time and
location.
1.
Agenda Items:
a.
b.
c.
d.
C.
Certify TAB field data reports and perform the following:
1.
2.
D.
The Contract Documents examination report.
The TAB plan.
Coordination and cooperation of trades and subcontractors.
Coordination of documentation and communication flow.
Review field data reports to validate accuracy of data and to prepare certified TAB
reports.
Certify that the TAB team complied with the approved TAB plan and the procedures
specified and referenced in this Specification.
TAB Report Forms: Use standard TAB contractor's forms approved by Owner.
TESTING, ADJUSTING, AND BALANCING FOR HVAC
Sunguide Transportation Management Center Control Room Retrofit
90% Submittal
230593 - 2
E.
Instrumentation Type, Quantity, Accuracy, and Calibration: As described in ASHRAE 111,
Section 5, "Instrumentation."
F.
ASHRAE Compliance:
Balancing."
G.
ASHRAE/IESNA Compliance:
Applicable
Section 6.7.2.3 - "System Balancing."
1.7
Applicable requirements in ASHRAE 62.1, Section 7.2.2 - "Air
requirements
in
ASHRAE/IESNA 90.1,
PROJECT CONDITIONS
A.
Full Owner Occupancy: Owner will occupy the site and existing building during entire TAB
period. Cooperate with Owner during TAB operations to minimize conflicts with Owner's
operations.
B.
Partial Owner Occupancy: Owner may occupy completed areas of building before Substantial
Completion. Cooperate with Owner during TAB operations to minimize conflicts with Owner's
operations.
1.8
COORDINATION
A.
Notice: Provide seven days' advance notice for each test. Include scheduled test dates and
times.
B.
Perform TAB after leakage and pressure tests on air distribution systems have been
satisfactorily completed.
PART 2 - PRODUCTS (Not Applicable)
PART 3 - EXECUTION
3.1
TAB SPECIALISTS
A.
Subject to compliance with requirements.
1.
Earl Hagood Inc.
2.
Dade Test and Balance or Approved Equal.
Or approved equal.
TESTING, ADJUSTING, AND BALANCING FOR HVAC
Sunguide Transportation Management Center Control Room Retrofit
90% Submittal
230593 - 3
3.2
EXAMINATION
A.
Examine the Contract Documents to become familiar with Project requirements and to discover
conditions in systems' designs that may preclude proper TAB of systems and equipment.
B.
Examine systems for installed balancing devices, such as test ports, gage cocks, thermometer
wells, flow-control devices, balancing valves and fittings, and manual volume dampers. Verify
that locations of these balancing devices are accessible.
C.
Examine the approved submittals for HVAC systems and equipment.
D.
Examine design data including HVAC system descriptions, statements of design assumptions
for environmental conditions and systems' output, and statements of philosophies and
assumptions about HVAC system and equipment controls.
E.
Examine ceiling plenums and underfloor air plenums used for supply, return, or relief air to
verify that they meet the leakage class of connected ducts as installed and are properly separated
from adjacent areas. Verify that penetrations in plenum walls are sealed and fire-stopped if
required.
F.
Examine equipment performance data including fan and pump curves.
1.
2.
Relate performance data to Project conditions and requirements, including system effects
that can create undesired or unpredicted conditions that cause reduced capacities in all or
part of a system.
Calculate system-effect factors to reduce performance ratings of HVAC equipment when
installed under conditions different from the conditions used to rate equipment
performance. To calculate system effects for air systems, use tables and charts found in
AMCA 201, "Fans and Systems," or in SMACNA's "HVAC Systems - Duct Design."
Compare results with the design data and installed conditions.
G.
Examine system and equipment installations and verify that field quality-control testing,
cleaning, and adjusting specified in individual Sections have been performed.
H.
Examine test reports specified in individual system and equipment Sections.
I.
Examine HVAC equipment and filters and verify that bearings are greased, belts are aligned
and tight, and equipment with functioning controls is ready for operation.
J.
Examine terminal units, such as variable-air-volume boxes, and verify that they are accessible
and their controls are connected and functioning.
K.
Examine strainers. Verify that startup screens are replaced by permanent screens with indicated
perforations.
L.
Examine three-way valves for proper installation for their intended function of diverting or
mixing fluid flows.
M.
Examine heat-transfer coils for correct piping connections and for clean and straight fins.
TESTING, ADJUSTING, AND BALANCING FOR HVAC
Sunguide Transportation Management Center Control Room Retrofit
90% Submittal
230593 - 4
N.
Examine system pumps to ensure absence of entrained air in the suction piping.
O.
Examine operating safety interlocks and controls on HVAC equipment.
P.
Report deficiencies discovered before and during performance of TAB procedures. Observe
and record system reactions to changes in conditions. Record default set points if different from
indicated values.
3.3
PREPARATION
A.
Prepare a TAB plan that includes strategies and step-by-step procedures.
B.
Complete system-readiness checks and prepare reports. Verify the following:
1.
2.
3.
4.
5.
6.
7.
8.
3.4
Permanent electrical-power wiring is complete.
Hydronic systems are filled, clean, and free of air.
Automatic temperature-control systems are operational.
Equipment and duct access doors are securely closed.
Balance, smoke, and fire dampers are open.
Isolating and balancing valves are open and control valves are operational.
Ceilings are installed in critical areas where air-pattern adjustments are required and
access to balancing devices is provided.
Windows and doors can be closed so indicated conditions for system operations can be
met.
GENERAL PROCEDURES FOR TESTING AND BALANCING
A.
Perform testing and balancing procedures on each system according to the procedures contained
in NEBB's "Procedural Standards for Testing, Adjusting, and Balancing of Environmental
Systems" and SMACNA's "HVAC Systems - Testing, Adjusting, and Balancing" and in this
Section.
1.
B.
Comply with requirements in ASHRAE 62.1, Section 7.2.2 - "Air Balancing."
Cut insulation, ducts, pipes, and equipment cabinets for installation of test probes to the
minimum extent necessary for TAB procedures.
1.
2.
3.
After testing and balancing, patch probe holes in ducts with same material and thickness
as used to construct ducts.
After testing and balancing, install test ports and duct access doors that comply with
requirements in Section 233300 "Air Duct Accessories."
Install and join new insulation that matches removed materials. Restore insulation,
coverings, vapor barrier, and finish according to Section 230713 "Duct Insulation,"
Section 230716 "HVAC Equipment Insulation," and Section 230719 "HVAC Piping
Insulation."
TESTING, ADJUSTING, AND BALANCING FOR HVAC
Sunguide Transportation Management Center Control Room Retrofit
90% Submittal
230593 - 5
C.
Mark equipment and balancing devices, including damper-control positions, valve position
indicators, fan-speed-control levers, and similar controls and devices, with paint or other
suitable, permanent identification material to show final settings.
D.
Take and report testing and balancing measurements in inch-pound (IP) units.
3.5
GENERAL PROCEDURES FOR BALANCING AIR SYSTEMS
A.
Prepare test reports for both fans and outlets. Obtain manufacturer's outlet factors and
recommended testing procedures. Crosscheck the summation of required outlet volumes with
required fan volumes.
B.
Prepare schematic diagrams of systems' "as-built" duct layouts.
C.
For variable-air-volume systems, develop a plan to simulate diversity.
D.
Determine the best locations in main and branch ducts for accurate duct-airflow measurements.
E.
Check airflow patterns from the outdoor-air louvers and dampers and the return- and exhaust-air
dampers through the supply-fan discharge and mixing dampers.
F.
Locate start-stop and disconnect switches, electrical interlocks, and motor starters.
G.
Verify that motor starters are equipped with properly sized thermal protection.
H.
Check dampers for proper position to achieve desired airflow path.
I.
Check for airflow blockages.
J.
Check condensate drains for proper connections and functioning.
K.
Check for proper sealing of air-handling-unit components.
L.
Verify that air duct system is sealed as specified in Section 233113 "Metal Ducts."
3.6
PROCEDURES FOR CONSTANT-VOLUME AIR SYSTEMS
A.
Adjust fans to deliver total indicated airflows within the maximum allowable fan speed listed by
fan manufacturer.
1.
Measure total airflow.
a.
2.
Where sufficient space in ducts is unavailable for Pitot-tube traverse
measurements, measure airflow at terminal outlets and inlets and calculate the total
airflow.
Measure fan static pressures as follows to determine actual static pressure:
TESTING, ADJUSTING, AND BALANCING FOR HVAC
Sunguide Transportation Management Center Control Room Retrofit
90% Submittal
230593 - 6
a.
b.
c.
d.
3.
Measure static pressure across each component that makes up an air-handling unit,
rooftop unit, and other air-handling and -treating equipment.
a.
4.
5.
6.
7.
B.
Report the cleanliness status of filters and the time static pressures are measured.
Measure static pressures entering and leaving other devices, such as sound traps, heatrecovery equipment, and air washers, under final balanced conditions.
Review Record Documents to determine variations in design static pressures versus
actual static pressures. Calculate actual system-effect factors. Recommend adjustments
to accommodate actual conditions.
Obtain approval from Architect for adjustment of fan speed higher or lower than
indicated speed. Comply with requirements in HVAC Sections for air-handling units for
adjustment of fans, belts, and pulley sizes to achieve indicated air-handling-unit
performance.
Do not make fan-speed adjustments that result in motor overload. Consult equipment
manufacturers about fan-speed safety factors. Modulate dampers and measure fan-motor
amperage to ensure that no overload will occur. Measure amperage in full-cooling, fullheating, economizer, and any other operating mode to determine the maximum required
brake horsepower.
Adjust volume dampers for main duct, submain ducts, and major branch ducts to indicated
airflows within specified tolerances.
1.
Measure airflow of submain and branch ducts.
a.
2.
3.
C.
Measure outlet static pressure as far downstream from the fan as practical and
upstream from restrictions in ducts such as elbows and transitions.
Measure static pressure directly at the fan outlet or through the flexible connection.
Measure inlet static pressure of single-inlet fans in the inlet duct as near the fan as
possible, upstream from the flexible connection, and downstream from duct
restrictions.
Measure inlet static pressure of double-inlet fans through the wall of the plenum
that houses the fan.
Where sufficient space in submain and branch ducts is unavailable for Pitot-tube
traverse measurements, measure airflow at terminal outlets and inlets and calculate
the total airflow for that zone.
Measure static pressure at a point downstream from the balancing damper, and adjust
volume dampers until the proper static pressure is achieved.
Remeasure each submain and branch duct after all have been adjusted. Continue to
adjust submain and branch ducts to indicated airflows within specified tolerances.
Measure air outlets and inlets without making adjustments.
1.
Measure terminal outlets using a direct-reading hood or outlet manufacturer's written
instructions and calculating factors.
TESTING, ADJUSTING, AND BALANCING FOR HVAC
Sunguide Transportation Management Center Control Room Retrofit
90% Submittal
230593 - 7
D.
Adjust air outlets and inlets for each space to indicated airflows within specified tolerances of
indicated values. Make adjustments using branch volume dampers rather than extractors and
the dampers at air terminals.
1.
2.
3.7
Adjust each outlet in same room or space to within specified tolerances of indicated
quantities without generating noise levels above the limitations prescribed by the
Contract Documents.
Adjust patterns of adjustable outlets for proper distribution without drafts.
PROCEDURES FOR VARIABLE-AIR-VOLUME SYSTEMS
A.
Compensating for Diversity: When the total airflow of all terminal units is more than the
indicated airflow of the fan, place a selected number of terminal units at a minimum set-point
airflow with the remainder at maximum-airflow condition until the total airflow of the terminal
units equals the indicated airflow of the fan. Select the reduced-airflow terminal units so they
are distributed evenly among the branch ducts.
B.
Pressure-Independent, Variable-Air-Volume Systems: After the fan systems have been
adjusted, adjust the variable-air-volume systems as follows:
1.
2.
3.
4.
5.
Set outdoor-air dampers at minimum, and set return- and exhaust-air dampers at a
position that simulates full-cooling load.
Select the terminal unit that is most critical to the supply-fan airflow and static pressure.
Measure static pressure. Adjust system static pressure so the entering static pressure for
the critical terminal unit is not less than the sum of the terminal-unit manufacturer's
recommended minimum inlet static pressure plus the static pressure needed to overcome
terminal-unit discharge system losses.
Measure total system airflow. Adjust to within indicated airflow.
Set terminal units at maximum airflow and adjust controller or regulator to deliver the
designed maximum airflow. Use terminal-unit manufacturer's written instructions to
make this adjustment. When total airflow is correct, balance the air outlets downstream
from terminal units the same as described for constant-volume air systems.
Set terminal units at minimum airflow and adjust controller or regulator to deliver the
designed minimum airflow. Check air outlets for a proportional reduction in airflow the
same as described for constant-volume air systems.
a.
6.
Remeasure the return airflow to the fan while operating at maximum return airflow and
minimum outdoor airflow.
a.
7.
If air outlets are out of balance at minimum airflow, report the condition but leave
outlets balanced for maximum airflow.
Adjust the fan and balance the return-air ducts and inlets the same as described for
constant-volume air systems.
Measure static pressure at the most critical terminal unit and adjust the static-pressure
controller at the main supply-air sensing station to ensure that adequate static pressure is
maintained at the most critical unit.
TESTING, ADJUSTING, AND BALANCING FOR HVAC
Sunguide Transportation Management Center Control Room Retrofit
90% Submittal
230593 - 8
8.
C.
Record final fan-performance data.
Pressure-Dependent, Variable-Air-Volume Systems without Diversity: After the fan systems
have been adjusted, adjust the variable-air-volume systems as follows:
1.
2.
3.
4.
5.
6.
7.
Balance variable-air-volume systems the same as described for constant-volume air
systems.
Set terminal units and supply fan at full-airflow condition.
Adjust inlet dampers of each terminal unit to indicated airflow and verify operation of the
static-pressure controller. When total airflow is correct, balance the air outlets
downstream from terminal units the same as described for constant-volume air systems.
Readjust fan airflow for final maximum readings.
Measure operating static pressure at the sensor that controls the supply fan if one is
installed, and verify operation of the static-pressure controller.
Set supply fan at minimum airflow if minimum airflow is indicated. Measure static
pressure to verify that it is being maintained by the controller.
Set terminal units at minimum airflow and adjust controller or regulator to deliver the
designed minimum airflow. Check air outlets for a proportional reduction in airflow the
same as described for constant-volume air systems.
a.
8.
Measure the return airflow to the fan while operating at maximum return airflow and
minimum outdoor airflow.
a.
D.
If air outlets are out of balance at minimum airflow, report the condition but leave
the outlets balanced for maximum airflow.
Adjust the fan and balance the return-air ducts and inlets the same as described for
constant-volume air systems.
Pressure-Dependent, Variable-Air-Volume Systems with Diversity: After the fan systems have
been adjusted, adjust the variable-air-volume systems as follows:
1.
2.
3.
4.
5.
6.
7.
Set system at maximum indicated airflow by setting the required number of terminal
units at minimum airflow. Select the reduced-airflow terminal units so they are
distributed evenly among the branch ducts.
Adjust supply fan to maximum indicated airflow with the variable-airflow controller set
at maximum airflow.
Set terminal units at full-airflow condition.
Adjust terminal units starting at the supply-fan end of the system and continuing
progressively to the end of the system. Adjust inlet dampers of each terminal unit to
indicated airflow. When total airflow is correct, balance the air outlets downstream from
terminal units the same as described for constant-volume air systems.
Adjust terminal units for minimum airflow.
Measure static pressure at the sensor.
Measure the return airflow to the fan while operating at maximum return airflow and
minimum outdoor airflow. Adjust the fan and balance the return-air ducts and inlets the
same as described for constant-volume air systems.
TESTING, ADJUSTING, AND BALANCING FOR HVAC
Sunguide Transportation Management Center Control Room Retrofit
90% Submittal
230593 - 9
3.8
PROCEDURES FOR TESTING, ADJUSTING, AND BALANCING EXISTING SYSTEMS
A.
Perform a preconstruction inspection of existing equipment that is to remain and be reused.
1.
2.
3.
4.
5.
6.
7.
8.
B.
Before performing testing and balancing of existing systems, inspect existing equipment that is
to remain and be reused to verify that existing equipment has been cleaned and refurbished.
Verify the following:
1.
2.
3.
4.
5.
6.
C.
New filters are installed.
Coils are clean and fins combed.
Drain pans are clean.
Fans are clean.
Bearings and other parts are properly lubricated.
Deficiencies noted in the preconstruction report are corrected.
Perform testing and balancing of existing systems to the extent that existing systems are
affected by the renovation work.
1.
2.
3.
4.
3.9
Measure and record the operating speed, airflow, and static pressure of each fan.
Measure motor voltage and amperage. Compare the values to motor nameplate
information.
Check the refrigerant charge.
Check the condition of filters.
Check the condition of coils.
Check the operation of the drain pan and condensate-drain trap.
Check bearings and other lubricated parts for proper lubrication.
Report on the operating condition of the equipment and the results of the measurements
taken. Report deficiencies.
Compare the indicated airflow of the renovated work to the measured fan airflows, and
determine the new fan speed and the face velocity of filters and coils.
Verify that the indicated airflows of the renovated work result in filter and coil face
velocities and fan speeds that are within the acceptable limits defined by equipment
manufacturer.
If calculations increase or decrease the air flow rates and water flow rates by more than 5
percent, make equipment adjustments to achieve the calculated rates. If increase or
decrease is 5 percent or less, equipment adjustments are not required.
Balance each air outlet.
TOLERANCES
A.
Set HVAC system's air flow rates and water flow rates within the following tolerances:
1.
2.
Supply, Return, and Exhaust Fans and Equipment with Fans: Plus or minus 10 percent.
Air Outlets and Inlets: Plus or minus 10 percent.
TESTING, ADJUSTING, AND BALANCING FOR HVAC
Sunguide Transportation Management Center Control Room Retrofit
90% Submittal
230593 - 10
3.10
REPORTING
A.
Initial Construction-Phase Report: Based on examination of the Contract Documents as
specified in "Examination" Article, prepare a report on the adequacy of design for systems'
balancing devices. Recommend changes and additions to systems' balancing devices to
facilitate proper performance measuring and balancing. Recommend changes and additions to
HVAC systems and general construction to allow access for performance measuring and
balancing devices.
B.
Status Reports: Prepare weekly progress reports to describe completed procedures, procedures
in progress, and scheduled procedures. Include a list of deficiencies and problems found in
systems being tested and balanced. Prepare a separate report for each system and each building
floor for systems serving multiple floors.
3.11
A.
FINAL REPORT
General: Prepare a certified written report; tabulate and divide the report into separate sections
for tested systems and balanced systems.
1.
2.
B.
Final Report Contents: In addition to certified field-report data, include the following:
1.
2.
3.
4.
5.
C.
Include a certification sheet at the front of the report's binder, signed and sealed by the
certified testing and balancing engineer.
Include a list of instruments used for procedures, along with proof of calibration.
Pump curves.
Fan curves.
Manufacturers' test data.
Field test reports prepared by system and equipment installers.
Other information relative to equipment performance; do not include Shop Drawings and
product data.
General Report Data: In addition to form titles and entries, include the following data:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
Title page.
Name and address of the TAB contractor.
Project name.
Project location.
Architect's name and address.
Engineer's name and address.
Contractor's name and address.
Report date.
Signature of TAB supervisor who certifies the report.
Table of Contents with the total number of pages defined for each section of the report.
Number each page in the report.
Summary of contents including the following:
a.
Indicated versus final performance.
TESTING, ADJUSTING, AND BALANCING FOR HVAC
Sunguide Transportation Management Center Control Room Retrofit
90% Submittal
230593 - 11
b.
c.
12.
13.
14.
15.
Nomenclature sheets for each item of equipment.
Data for terminal units, including manufacturer's name, type, size, and fittings.
Notes to explain why certain final data in the body of reports vary from indicated values.
Test conditions for fans and pump performance forms including the following:
a.
b.
c.
d.
e.
f.
g.
h.
D.
Settings for outdoor-, return-, and exhaust-air dampers.
Conditions of filters.
Cooling coil, wet- and dry-bulb conditions.
Face and bypass damper settings at coils.
Fan drive settings including settings and percentage of maximum pitch diameter.
Inlet vane settings for variable-air-volume systems.
Settings for supply-air, static-pressure controller.
Other system operating conditions that affect performance.
System Diagrams: Include schematic layouts of air and hydronic distribution systems. Present
each system with single-line diagram and include the following:
1.
2.
3.
4.
5.
6.
7.
E.
Notable characteristics of systems.
Description of system operation sequence if it varies from the Contract
Documents.
Quantities of outdoor, supply, return, and exhaust airflows.
Water and steam flow rates.
Duct, outlet, and inlet sizes.
Pipe and valve sizes and locations.
Terminal units.
Balancing stations.
Position of balancing devices.
Air-Handling-Unit Test Reports: For air-handling units with coils, include the following:
1.
Unit Data:
a.
b.
c.
d.
e.
f.
g.
h.
i.
j.
k.
2.
Unit identification.
Location.
Make and type.
Model number and unit size.
Manufacturer's serial number.
Unit arrangement and class.
Discharge arrangement.
Sheave make, size in inches (mm), and bore.
Center-to-center dimensions of sheave, and amount of adjustments in inches (mm).
Number, make, and size of belts.
Number, type, and size of filters.
Motor Data:
a.
b.
Motor make, and frame type and size.
Horsepower and rpm.
TESTING, ADJUSTING, AND BALANCING FOR HVAC
Sunguide Transportation Management Center Control Room Retrofit
90% Submittal
230593 - 12
c.
d.
e.
f.
3.
Test Data (Indicated and Actual Values):
a.
b.
c.
d.
e.
f.
g.
h.
i.
j.
k.
l.
m.
F.
Volts, phase, and hertz.
Full-load amperage and service factor.
Sheave make, size in inches (mm), and bore.
Center-to-center dimensions of sheave, and amount of adjustments in inches (mm).
Total air flow rate in cfm (L/s).
Total system static pressure in inches wg.
Fan rpm.
Discharge static pressure in inches wg.
Filter static-pressure differential in inches wg.
Preheat-coil static-pressure differential in inches wg.
Cooling-coil static-pressure differential in inches wg.
Heating-coil static-pressure differential in inches wg.
Outdoor airflow in cfm.
Return airflow in cfm.
Outdoor-air damper position.
Return-air damper position.
Vortex damper position.
Apparatus-Coil Test Reports:
1.
Coil Data:
a.
b.
c.
d.
e.
f.
g.
h.
i.
j.
2.
System identification.
Location.
Coil type.
Number of rows.
Fin spacing in fins per inch o.c.
Make and model number.
Face area in sq. ft.
Tube size in NPS (DN).
Tube and fin materials.
Circuiting arrangement.
Test Data (Indicated and Actual Values):
a.
b.
c.
d.
e.
f.
g.
h.
i.
j.
Air flow rate in cfm (L/s).
Average face velocity in fpm.
Air pressure drop in inches wg.
Outdoor-air, wet- and dry-bulb temperatures in deg F.
Return-air, wet- and dry-bulb temperatures in deg F.
Entering-air, wet- and dry-bulb temperatures in deg F.
Leaving-air, wet- and dry-bulb temperatures in deg F.
Water flow rate in gpm.
Water pressure differential in feet of head or psig.
Entering-water temperature in deg F.
TESTING, ADJUSTING, AND BALANCING FOR HVAC
Sunguide Transportation Management Center Control Room Retrofit
90% Submittal
230593 - 13
k.
l.
m.
n.
o.
G.
Electric-Coil Test Reports: For electric furnaces, duct coils, and electric coils installed in
central-station air-handling units, include the following:
1.
Unit Data:
a.
b.
c.
d.
e.
f.
g.
h.
i.
j.
2.
System identification.
Location.
Coil identification.
Capacity in Btu/h (kW).
Number of stages.
Connected volts, phase, and hertz.
Rated amperage.
Air flow rate in cfm
Face area in sq. ft.
Minimum face velocity in fpm
Test Data (Indicated and Actual Values):
a.
b.
c.
d.
e.
f.
g.
H.
Leaving-water temperature in deg F.
Refrigerant expansion valve and refrigerant types.
Refrigerant suction pressure in psig.
Refrigerant suction temperature in deg F.
Inlet steam pressure in psig.
Heat output in Btu/h (kW).
Air flow rate in cfm.
Air velocity in fpm (m/s).
Entering-air temperature in deg F.
Leaving-air temperature in deg F.
Voltage at each connection.
Amperage for each phase.
Fan Test Reports: For supply, return, and exhaust fans, include the following:
1.
Fan Data:
a.
b.
c.
d.
e.
f.
g.
h.
2.
System identification.
Location.
Make and type.
Model number and size.
Manufacturer's serial number.
Arrangement and class.
Sheave make, size in inches and bore.
Center-to-center dimensions of sheave, and amount of adjustments in inches
Motor Data:
a.
b.
Motor make, and frame type and size.
Horsepower and rpm.
TESTING, ADJUSTING, AND BALANCING FOR HVAC
Sunguide Transportation Management Center Control Room Retrofit
90% Submittal
230593 - 14
c.
d.
e.
f.
g.
3.
Test Data (Indicated and Actual Values):
a.
b.
c.
d.
e.
I.
Total airflow rate in cfm.
Total system static pressure in inches wg.
Fan rpm.
Discharge static pressure in inches wg.
Suction static pressure in inches wg.
Round, Flat-Oval, and Rectangular Duct Traverse Reports: Include a diagram with a grid
representing the duct cross-section and record the following:
1.
Report Data:
a.
b.
c.
d.
e.
f.
g.
h.
i.
j.
k.
J.
Volts, phase, and hertz.
Full-load amperage and service factor.
Sheave make, size in inches, and bore.
Center-to-center dimensions of sheave, and amount of adjustments in inches (mm).
Number, make, and size of belts.
System and air-handling-unit number.
Location and zone.
Traverse air temperature in deg F.
Duct static pressure in inches wg.
Duct size in inches.
Duct area in sq. ft.
Indicated air flow rate in cfm.
Indicated velocity in fpm.
Actual air flow rate in cfm.
Actual average velocity in fpm.
Barometric pressure in psig.
Air-Terminal-Device Reports:
1.
Unit Data:
a.
b.
c.
d.
e.
f.
g.
h.
i.
2.
System and air-handling unit identification.
Location and zone.
Apparatus used for test.
Area served.
Make.
Number from system diagram.
Type and model number.
Size.
Effective area in sq. ft.
Test Data (Indicated and Actual Values):
a.
b.
Air flow rate in cfm.
Air velocity in fpm.
TESTING, ADJUSTING, AND BALANCING FOR HVAC
Sunguide Transportation Management Center Control Room Retrofit
90% Submittal
230593 - 15
c.
d.
e.
f.
g.
K.
System-Coil Reports: For reheat coils and water coils of terminal units, include the following:
1.
Unit Data:
a.
b.
c.
d.
e.
2.
Report Data:
a.
b.
c.
d.
e.
A.
Air flow rate in cfm.
Entering-water temperature in deg F.
Leaving-water temperature in deg F.
Water pressure drop in feet of head.
Entering-air temperature in deg F.
Leaving-air temperature in deg F.
Instrument Calibration Reports:
1.
3.12
System and air-handling-unit identification.
Location and zone.
Room or riser served.
Coil make and size.
Flowmeter type.
Test Data (Indicated and Actual Values):
a.
b.
c.
d.
e.
f.
L.
Preliminary air flow rate as needed in cfm.
Preliminary velocity as needed in fpm.
Final air flow rate in cfm.
Final velocity in fpm.
Space temperature in deg F.
Instrument type and make.
Serial number.
Application.
Dates of use.
Dates of calibration.
INSPECTIONS
Initial Inspection:
1.
2.
After testing and balancing are complete, operate each system and randomly check
measurements to verify that the system is operating according to the final test and balance
readings documented in the final report.
Check the following for each system:
a.
b.
c.
Measure airflow of at least 10 percent of air outlets.
Measure water flow of at least 5 percent of terminals.
Measure room temperature at each thermostat/temperature sensor. Compare the
reading to the set point.
TESTING, ADJUSTING, AND BALANCING FOR HVAC
Sunguide Transportation Management Center Control Room Retrofit
90% Submittal
230593 - 16
d.
e.
B.
Final Inspection:
1.
2.
3.
4.
5.
C.
2.
3.13
After initial inspection is complete and documentation by random checks verifies that
testing and balancing are complete and accurately documented in the final report, request
that a final inspection be made by Architect.
The TAB contractor's test and balance engineer shall conduct the inspection in the
presence of Architect.
Architect shall randomly select measurements, documented in the final report, to be
rechecked. Rechecking shall be limited to either 10 percent of the total measurements
recorded or the extent of measurements that can be accomplished in a normal 8-hour
business day.
If rechecks yield measurements that differ from the measurements documented in the
final report by more than the tolerances allowed, the measurements shall be noted as
"FAILED."
If the number of "FAILED" measurements is greater than 10 percent of the total
measurements checked during the final inspection, the testing and balancing shall be
considered incomplete and shall be rejected.
TAB Work will be considered defective if it does not pass final inspections. If TAB Work fails,
proceed as follows:
1.
D.
Verify that balancing devices are marked with final balance position.
Note deviations from the Contract Documents in the final report.
Recheck all measurements and make adjustments. Revise the final report and balancing
device settings to include all changes; resubmit the final report and request a second final
inspection.
If the second final inspection also fails, Owner may contract the services of another TAB
contractor to complete TAB Work according to the Contract Documents and deduct the
cost of the services from the original TAB contractor's final payment.
Prepare test and inspection reports.
ADDITIONAL TESTS
A.
Within 90 days of completing TAB, perform additional TAB to verify that balanced conditions
are being maintained throughout and to correct unusual conditions.
B.
Seasonal Periods: If initial TAB procedures were not performed during near-peak summer and
winter conditions, perform additional TAB during near-peak summer and winter conditions.
END OF SECTION 230593
TESTING, ADJUSTING, AND BALANCING FOR HVAC
Sunguide Transportation Management Center Control Room Retrofit
90% Submittal
230593 - 17
SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract Documents apply to this Section.
SUMMARY
A.
Section Includes:
1.
2.
1.3
Building wires and cables rated 600 V and less.
Connectors, splices, and terminations rated 600 V and less.
ACTION SUBMITTALS
A.
1.4
Product Data: For each type of product.
INFORMATIONAL SUBMITTALS
A.
Qualification Data: For testing agency.
B.
Field quality-control reports.
1.5
QUALITY ASSURANCE
A.
Testing Agency Qualifications: Member company of NETA or an NRTL.
1.
Testing Agency's Field Supervisor: Certified by NETA to supervise on-site testing.
PART 2 - PRODUCTS
2.1
CONDUCTORS AND CABLES
A.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following (or approved equivalent determined by Department Project Manager):
1.
Alpha Wire.
2.
Belden Inc.
3.
Encore Wire Corporation.
4.
General Cable Technologies Corporation.
5.
Southwire Incorporated.
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260519 - 1
B.
C.
2.2
Copper Conductors: Comply with NEMA WC 70/ICEA S-95-658.
Conductor Insulation:
THWN-2 .
Comply with NEMA WC 70/ICEA S-95-658 for
Type THHN-2-
CONNECTORS AND SPLICES
A.
Manufacturers: Subject to compliance with requirements, provide products by the following :
1.
2.
3.
4.
5.
6.
7.
8.
9.
B.
2.3
AFC Cable Systems, Inc.
Gardner Bender.
Hubbell Power Systems, Inc.
Ideal Industries, Inc.
Ilsco; a branch of Bardes Corporation.
NSi Industries LLC.
O-Z/Gedney; a brand of the EGS Electrical Group.
3M; Electrical Markets Division.
Tyco Electronics.
Description: Factory-fabricated connectors and splices of size, ampacity rating, material, type,
and class for application and service indicated.
SYSTEM DESCRIPTION
A.
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
by a qualified testing agency, and marked for intended location and application.
B.
Comply with NFPA 70.
PART 3 - EXECUTION
3.1
CONDUCTOR MATERIAL APPLICATIONS
A.
Feeders: Copper . Solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger.
B.
Branch Circuits: Copper. Solid for No. 10 AWG and smaller; stranded for No. 8 AWG and
larger, except VFC cable, which shall be extra flexible stranded.
3.2
CONDUCTOR INSULATION AND MULTICONDUCTOR CABLE APPLICATIONS AND
WIRING METHODS
A.
Service Entrance: Type THHN-2-THWN-2, single conductors in raceway .
B.
Exposed Feeders: Type THHN-2-THWN-2, single conductors in raceway
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
.
260519 - 2
C.
Feeders Concealed in Ceilings, Walls, Partitions, and Crawlspaces: Type THHN-2-THWN-2,
single conductors in raceway .
D.
Feeders Concealed in Concrete, below Slabs-on-Grade, and Underground: Type THHN-2THWN-2, single conductors in raceway .
E.
Feeders Installed below Raised Flooring:
raceway .
F.
Feeders in Cable Tray: Type THHN-2-THWN-2, single conductors in raceway
G.
Exposed Branch Circuits, Including in Crawlspaces:
conductors in raceway .
H.
Branch Circuits Concealed in Ceilings, Walls, and Partitions: Type THHN-2-THWN-2, single
conductors in raceway .
I.
Branch Circuits Concealed in Concrete, below Slabs-on-Grade, and Underground:
Type THHN-2-THWN-2, single conductors in raceway .
J.
Branch Circuits Installed below Raised Flooring: Type THHN-2-THWN-2, single conductors
in raceway .
K.
Branch Circuits in Cable Tray: Type THHN-2-THWN-2, single conductors in raceway
L.
Cord Drops and Portable Appliance Connections: Type SO, hard service cord with stainlesssteel, wire-mesh, strain relief device at terminations to suit application.
3.3
Type THHN-2-THWN-2, single conductors in
.
Type THHN-2-THWN-2, single
.
INSTALLATION OF CONDUCTORS AND CABLES
A.
Conceal cables in finished walls, ceilings, and floors unless otherwise indicated.
B.
Complete raceway installation between conductor and cable termination points according to
Section 260533 "Raceways and Boxes for Electrical Systems" prior to pulling conductors and
cables.
C.
Use manufacturer-approved pulling compound or lubricant where necessary; compound used
must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended
maximum pulling tensions and sidewall pressure values.
D.
Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips, that will
not damage cables or raceway.
E.
Install exposed cables parallel and perpendicular to surfaces of exposed structural members, and
follow surface contours where possible.
F.
Support cables according to Section 260529 "Hangers and Supports for Electrical Systems."
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260519 - 3
3.4
CONNECTIONS
A.
Tighten electrical connectors and terminals according to manufacturer's published torquetightening values. If manufacturer's torque values are not indicated, use those specified in
UL 486A-486B.
B.
Make splices, terminations, and taps that are compatible with conductor material and that
possess equivalent or better mechanical strength and insulation ratings than unspliced
conductors.
C.
Wiring at Outlets: Install conductor at each outlet, with at least 12 inches (300 mm) of slack.
3.5
IDENTIFICATION
A.
Identify and color-code conductors and cables according to Section 260553 "Identification for
Electrical Systems."
B.
Identify each spare conductor at each end with identity number and location of other end of
conductor, and identify as spare conductor.
3.6
SLEEVE AND SLEEVE-SEAL INSTALLATION FOR ELECTRICAL PENETRATIONS
A.
3.7
Install sleeves and sleeve seals at penetrations of exterior floor and wall assemblies. Comply
with requirements in Section 260544 "Sleeves and Sleeve Seals for Electrical Raceways and
Cabling."
FIRESTOPPING
A.
3.8
Apply firestopping to electrical penetrations of fire-rated floor and wall assemblies to restore
original fire-resistance rating of assembly according to Section 078413 "Penetration
Firestopping."
FIELD QUALITY CONTROL
A.
B.
Perform the following tests and inspections:
1.
After installing conductors and cables and before electrical circuitry has been energized,
test service entrance and feeder conductors for compliance with requirements.
2.
Perform each visual and mechanical inspection and electrical test stated in NETA
Acceptance Testing Specification. Certify compliance with test parameters.
Test and Inspection Reports: Prepare a written report to record the following:
1.
2.
Procedures used.
Results that comply with requirements.
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260519 - 4
3.
C.
Results that do not comply with requirements and corrective action taken to achieve
compliance with requirements.
Cables will be considered defective if they do not pass tests and inspections.
END OF SECTION 260519
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260519 - 5
SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract Documents apply to this Section.
SUMMARY
A.
Section Includes: Grounding systems and equipment.
B.
Section includes grounding systems and equipment, plus the following special applications:
1.
Ground bonding common with lightning protection system.
1.3
ACTION SUBMITTALS
A.
1.4
Product Data: For each type of product indicated.
INFORMATIONAL SUBMITTALS
A.
Informational Submittals: Plans showing dimensioned as-built locations of grounding features
specified in "Field Quality Control" Article, including the following:
1.
2.
3.
4.
Test wells.
Ground rods.
Ground rings.
Grounding arrangements and connections for separately derived systems.
B.
Qualification Data: For qualified testing agency and testing agency's field supervisor.
C.
Field quality-control reports.
1.5
CLOSEOUT SUBMITTALS
A.
Operation and Maintenance Data: For grounding to include in emergency, operation, and
maintenance manuals. In addition to items specified in Section 017823 "Operation and
Maintenance Data," include the following:
1.
Instructions for periodic testing and inspection of grounding features at test wells
on NETA MTS .
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
based
260526 - 1
a.
b.
1.6
Tests shall determine if ground-resistance or impedance values remain within
specified maximums, and instructions shall recommend corrective action if values
do not.
Include recommended testing intervals.
QUALITY ASSURANCE
A.
Testing Agency Qualifications: Member company of NETA or an NRTL.
1.
Testing Agency's Field Supervisor: Currently certified by NETA to supervise on-site
testing.
B.
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
by a qualified testing agency, and marked for intended location and application.
C.
Comply with UL 467 for grounding and bonding materials and equipment.
PART 2 - PRODUCTS
2.1
CONDUCTORS
A.
Insulated Conductors: Copper wire or cable insulated for 600 V unless otherwise required by
applicable Code or authorities having jurisdiction.
B.
Bare Copper Conductors:
1.
2.
3.
4.
5.
6.
7.
C.
2.2
Solid Conductors: ASTM B 3.
Stranded Conductors: ASTM B 8.
Tinned Conductors: ASTM B 33.
Bonding Cable: 28 kcmil, 14 strands of No. 17 AWG conductor, 1/4 inch (6 mm) in
diameter.
Bonding Conductor: No. 4 or No. 6 AWG, stranded conductor.
Bonding Jumper: Copper tape, braided conductors terminated with copper ferrules; 1-5/8
inches (41 mm) wide and 1/16 inch (1.6 mm) thick.
Tinned Bonding Jumper: Tinned-copper tape, braided conductors terminated with copper
ferrules; 1-5/8 inches (41 mm) wide and 1/16 inch (1.6 mm) thick.
Grounding Bus: Predrilled rectangular bars of annealed copper, 1/4 by 4 inches (6.3 by 100
mm) in cross section, with 9/32-inch (7.14-mm) holes spaced 1-1/8 inches (28 mm) apart.
Stand-off insulators for mounting shall comply with UL 891 for use in switchboards, 600 V.
Lexan or PVC, impulse tested at 5000 V.
CONNECTORS
A.
Listed and labeled by an NRTL acceptable to authorities having jurisdiction for applications in
which used and for specific types, sizes, and combinations of conductors and other items
connected.
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260526 - 2
B.
Bolted Connectors for Conductors and Pipes: Copper or copper alloy, pressure type with at
least two bolts.
1.
Pipe Connectors: Clamp type, sized for pipe.
C.
Welded Connectors: Exothermic-welding kits of types recommended by kit manufacturer for
materials being joined and installation conditions.
D.
Bus-bar Connectors: Mechanical type, cast silicon bronze, solderless exothermic-type wire
terminals, and long-barrel, two-bolt connection to ground bus bar.
2.3
GROUNDING ELECTRODES
A.
Ground Rods: Copper-clad steel; 3/4 inch by 10 feet (19 mm by 3 m) in diameter.
PART 3 - EXECUTION
3.1
APPLICATIONS
A.
Conductors: Install solid conductor for No. 8 AWG and smaller, and stranded conductors for
No. 6 AWG and larger unless otherwise indicated.
B.
Underground Grounding Conductors: Install bare copper conductor, No. 2/0 AWG minimum.
1.
C.
Grounding Bus: Install in electrical and telephone equipment rooms, in rooms housing service
equipment, and elsewhere as indicated.
1.
2.
D.
Install bus on insulated spacers 2 inches (50 mm) minimum from wall, 6 inches (150
mm) above finished floor unless otherwise indicated.
Where indicated on both sides of doorways, route bus up to top of door frame, across top
of doorway, and down to specified height above floor; connect to horizontal bus.
Conductor Terminations and Connections:
1.
2.
3.
4.
3.2
Bury at least 24 inches (600 mm) below grade.
Pipe and Equipment Grounding Conductor Terminations: Bolted connectors.
Underground Connections: Welded connectors except at test wells and as otherwise
indicated.
Connections to Ground Rods at Test Wells: Bolted connectors.
Connections to Structural Steel: Welded connectors.
GROUNDING UNDERGROUND DISTRIBUTION SYSTEM COMPONENTS
A.
Comply with IEEE C2 grounding requirements.
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260526 - 3
B.
Grounding Manholes and Handholes: Install a driven ground rod through manhole or handhole
floor, close to wall, and set rod depth so 4 inches (100 mm) will extend above finished floor. If
necessary, install ground rod before manhole is placed and provide No. 1/0 AWG bare, tinnedcopper conductor from ground rod into manhole through a waterproof sleeve in manhole wall.
Protect ground rods passing through concrete floor with a double wrapping of pressure-sensitive
insulating tape or heat-shrunk insulating sleeve from 2 inches (50 mm) above to 6 inches (150
mm) below concrete. Seal floor opening with waterproof, nonshrink grout.
C.
Grounding Connections to Manhole Components: Bond exposed-metal parts such as inserts,
cable racks, pulling irons, ladders, and cable shields within each manhole or handhole, to
ground rod or grounding conductor. Make connections with No. 4 AWG minimum, stranded,
hard-drawn copper bonding conductor. Train conductors level or plumb around corners and
fasten to manhole walls. Connect to cable armor and cable shields according to written
instructions by manufacturer of splicing and termination kits.
D.
Pad-Mounted Transformers and Switches: Install two ground rods and ground ring around the
pad. Ground pad-mounted equipment and noncurrent-carrying metal items associated with
substations by connecting them to underground cable and grounding electrodes. Install tinnedcopper conductor not less than No. 2 AWG for ground ring and for taps to equipment grounding
terminals. Bury ground ring not less than 6 inches (150 mm) from the foundation.
3.3
EQUIPMENT GROUNDING
A.
Install insulated equipment grounding conductors with all feeders and branch circuits.
B.
Air-Duct Equipment Circuits: Install insulated equipment grounding conductor to ductmounted electrical devices operating at 120 V and more, including air cleaners, heaters,
dampers, humidifiers, and other duct electrical equipment. Bond conductor to each unit and to
air duct and connected metallic piping.
C.
Water Heater, Heat-Tracing, and Antifrost Heating Cables: Install a separate insulated
equipment grounding conductor to each electric water heater and heat-tracing cable. Bond
conductor to heater units, piping, connected equipment, and components.
D.
Signal and Communication Equipment: In addition to grounding and bonding required by
NFPA 70, provide a separate grounding system complying with requirements in TIA/ATIS JSTD-607-A.
1.
2.
3.
E.
For telephone, alarm, voice and data, and other communication equipment, provide
No. 4 AWG minimum insulated grounding conductor in raceway from grounding
electrode system to each service location, terminal cabinet, wiring closet, and central
equipment location.
Service and Central Equipment Locations and Wiring Closets: Terminate grounding
conductor on a 1/4-by-4-by-12-inch (6.3-by-100-by-300-mm) grounding bus.
Terminal Cabinets: Terminate grounding conductor on cabinet grounding terminal.
Metal Poles Supporting Outdoor Lighting Fixtures: Install grounding electrode and a separate
insulated equipment grounding conductor in addition to grounding conductor installed with
branch-circuit conductors.
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260526 - 4
3.4
INSTALLATION
A.
Grounding Conductors: Route along shortest and straightest paths possible unless otherwise
indicated or required by Code. Avoid obstructing access or placing conductors where they may
be subjected to strain, impact, or damage.
B.
Ground Bonding Common with Lightning Protection System: Comply with NFPA 780 and
UL 96 when interconnecting with lightning protection system. Bond electrical power system
ground directly to lightning protection system grounding conductor at closest point to electrical
service grounding electrode. Use bonding conductor sized same as system grounding electrode
conductor, and install in conduit.
C.
Ground Rods: Drive rods until tops are 2 inches (50 mm) below finished floor or final grade
unless otherwise indicated.
1.
2.
D.
Test Wells: Ground rod driven through drilled hole in bottom of handhole. Handholes are
specified in Section 260543 "Underground Ducts and Raceways for Electrical Systems," and
shall be at least 12 inches (300 mm) deep, with cover.
1.
E.
Test Wells: Install at least one test well for each service unless otherwise indicated.
Install at the ground rod electrically closest to service entrance. Set top of test well flush
with finished grade or floor.
Bonding Straps and Jumpers: Install in locations accessible for inspection and maintenance
except where routed through short lengths of conduit.
1.
2.
3.
F.
Interconnect ground rods with grounding electrode conductor below grade and as
otherwise indicated. Make connections without exposing steel or damaging coating if
any.
For grounding electrode system, install at least three rods spaced at least one-rod length
from each other and located at least the same distance from other grounding electrodes,
and connect to the service grounding electrode conductor.
Bonding to Structure: Bond straps directly to basic structure, taking care not to penetrate
any adjacent parts.
Bonding to Equipment Mounted on Vibration Isolation Hangers and Supports: Install
bonding so vibration is not transmitted to rigidly mounted equipment.
Use exothermic-welded connectors for outdoor locations; if a disconnect-type connection
is required, use a bolted clamp.
Grounding and Bonding for Piping:
1.
Metal Water Service Pipe: Install insulated copper grounding conductors, in conduit,
from building's main service equipment, or grounding bus, to main metal water service
entrances to building. Connect grounding conductors to main metal water service pipes;
use a bolted clamp connector or bolt a lug-type connector to a pipe flange by using one of
the lug bolts of the flange. Where a dielectric main water fitting is installed, connect
grounding conductor on street side of fitting. Bond metal grounding conductor conduit or
sleeve to conductor at each end.
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260526 - 5
2.
3.
Water Meter Piping: Use braided-type bonding jumpers to electrically bypass water
meters. Connect to pipe with a bolted connector.
Bond each aboveground portion of gas piping system downstream from equipment
shutoff valve.
G.
Bonding Interior Metal Ducts: Bond metal air ducts to equipment grounding conductors of
associated fans, blowers, electric heaters, and air cleaners. Install tinned bonding jumper to
bond across flexible duct connections to achieve continuity.
H.
Grounding for Steel Building Structure: Install a driven ground rod at base of each corner
column and at intermediate exterior columns at distances not more than 60 feet (18 m) apart.
I.
Ground Ring: Install a grounding conductor, electrically connected to each building structure
ground rod and to each steel column , extending around the perimeter of building .
1.
2.
J.
Ufer Ground (Concrete-Encased Grounding Electrode): Fabricate according to NFPA 70; use a
minimum of 20 feet (6 m) of bare copper conductor not smaller than No. 4 AWG.
1.
2.
3.5
Install tinned-copper conductor not less than No. 2/0 AWG for ground ring and for taps
to building steel.
Bury ground ring not less than 24 inches (600 mm) from building's foundation.
If concrete foundation is less than 20 feet (6 m) long, coil excess conductor within base
of foundation.
Bond grounding conductor to reinforcing steel in at least four locations and to anchor
bolts. Extend grounding conductor below grade and connect to building's grounding grid
or to grounding electrode external to concrete.
LABELING
A.
Comply with requirements in Section 260553 "Identification for Electrical Systems" for
instruction signs. The label or its text shall be green.
B.
Install labels at the telecommunications bonding conductor and grounding equalizer and at the
grounding electrode conductor where exposed.
1.
3.6
Label Text: "If this connector or cable is loose or if it must be removed for any reason,
notify the facility manager."
FIELD QUALITY CONTROL
A.
Testing Agency: Engage a qualified testing agency to perform tests and inspections.
B.
Tests and Inspections:
1.
After installing grounding system but before permanent electrical circuits have been
energized, test for compliance with requirements.
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260526 - 6
2.
3.
Inspect physical and mechanical condition. Verify tightness of accessible, bolted,
electrical connections with a calibrated torque wrench according to manufacturer's
written instructions.
Test completed grounding system at each location where a maximum ground-resistance
level is specified, at service disconnect enclosure grounding terminal, at ground test wells
, and at individual ground rods. Make tests at ground rods before any conductors are
connected.
a.
b.
4.
Measure ground resistance no fewer than two full days after last trace of
precipitation and without soil being moistened by any means other than natural
drainage or seepage and without chemical treatment or other artificial means of
reducing natural ground resistance.
Perform tests by fall-of-potential method according to IEEE 81.
Prepare dimensioned Drawings locating each test well, ground rod and ground-rod
assembly, and other grounding electrodes. Identify each by letter in alphabetical order,
and key to the record of tests and observations. Include the number of rods driven and
their depth at each location, and include observations of weather and other phenomena
that may affect test results. Describe measures taken to improve test results.
C.
Grounding system will be considered defective if it does not pass tests and inspections.
D.
Prepare test and inspection reports.
E.
Report measured ground resistances that exceed the following values:
1.
2.
3.
4.
5.
6.
F.
Power and Lighting Equipment or System with Capacity of 500 kVA and Less: 10
ohms.
Power and Lighting Equipment or System with Capacity of 500 to 1000 kVA: 5 ohms.
Power and Lighting Equipment or System with Capacity More Than 1000 kVA: 3
ohms.
Power Distribution Units or Panelboards Serving Electronic Equipment: 3 ohm(s).
Substations and Pad-Mounted Equipment: 5 ohms.
Manhole Grounds: 10 ohms.
Excessive Ground Resistance: If resistance to ground exceeds specified values, notify Architect
promptly and include recommendations to reduce ground resistance.
END OF SECTION 260526
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260526 - 7
SECTION 260529 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract Documents apply to this Section.
SUMMARY
A.
This Section includes the following:
1.
2.
B.
1.3
Hangers and supports for electrical equipment and systems.
Construction requirements for concrete bases.
Related Sections include the following:
DEFINITIONS
A.
EMT: Electrical metallic tubing.
B.
IMC: Intermediate metal conduit.
C.
RMC: Rigid metal conduit.
1.4
PERFORMANCE REQUIREMENTS
A.
Design supports for multiple raceways capable of supporting combined weight of supported
systems and its contents.
B.
Design equipment supports capable of supporting combined operating weight of supported
equipment and connected systems and components.
C.
Rated Strength: Adequate in tension, shear, and pullout force to resist maximum loads
calculated or imposed for this Project, with a minimum structural safety factor of five times the
applied force.
1.5
ACTION SUBMITTALS
A.
Product Data: For the following:
1.
2.
Steel slotted support systems.
Nonmetallic slotted support systems.
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260529 - 1
B.
Shop Drawings: Signed and sealed by a qualified professional engineer. Show fabrication and
installation details and include calculations for the following:
1.
2.
3.
4.
1.6
Trapeze hangers. Include Product Data for components.
Steel slotted channel systems. Include Product Data for components.
Nonmetallic slotted channel systems. Include Product Data for components.
Equipment supports.
INFORMATIONAL SUBMITTALS
A.
1.7
Welding certificates.
QUALITY ASSURANCE
A.
Welding: Qualify procedures and personnel according to AWS D1.1/D1.1M, "Structural
Welding Code - Steel."
B.
Comply with NFPA 70.
1.8
COORDINATION
A.
Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases. Concrete,
reinforcement, and formwork requirements are specified together with concrete Specifications.
B.
Coordinate installation of roof curbs, equipment supports, and roof penetrations. These items
are specified in Section 077200 "Roof Accessories."
PART 2 - PRODUCTS
2.1
SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS
A.
Steel Slotted Support Systems: Comply with MFMA-4, factory-fabricated components for field
assembly.
1.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following (or approved equivalent determined by Department Project Manager):
a.
b.
c.
d.
e.
f.
g.
2.
Allied Tube & Conduit.
Cooper B-Line, Inc.; a division of Cooper Industries.
ERICO International Corporation.
GS Metals Corp.
Thomas & Betts Corporation.
Unistrut; Tyco International, Ltd.
Wesanco, Inc.
Metallic Coatings:
MFMA-4.
Hot-dip galvanized after fabrication and applied according to
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260529 - 2
3.
4.
B.
Painted Coatings: Manufacturer's standard painted coating applied according to MFMA4.
Channel Dimensions: Selected for applicable load criteria.
Nonmetallic Slotted Support Systems: Structural-grade, factory-formed, glass-fiber-resin
channels and angles with 9/16-inch- (14-mm-) diameter holes at a maximum of 8 inches (200
mm) o.c., in at least 1 surface.
1.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following (or approved equivalent determined by Department Project Manager):
a.
b.
c.
d.
2.
3.
4.
Allied Tube & Conduit.
Cooper B-Line, Inc.; a division of Cooper Industries.
Fabco Plastics Wholesale Limited.
Seasafe, Inc.
Fittings and Accessories: Products of channel and angle manufacturer and designed for
use with those items.
Fitting and Accessory Materials: Same as channels and angles.
Rated Strength: Selected to suit applicable load criteria.
C.
Raceway and Cable Supports: As described in NECA 1 and NECA 101.
D.
Conduit and Cable Support Devices: Steel hangers, clamps, and associated fittings, designed
for types and sizes of raceway or cable to be supported.
E.
Support for Conductors in Vertical Conduit: Factory-fabricated assembly consisting of
threaded body and insulating wedging plug or plugs for non-armored electrical conductors or
cables in riser conduits. Plugs shall have number, size, and shape of conductor gripping pieces
as required to suit individual conductors or cables supported. Body shall be malleable iron.
F.
Structural Steel for Fabricated Supports and Restraints:
shapes, and bars; black and galvanized.
G.
Mounting, Anchoring, and Attachment Components: Items for fastening electrical items or
their supports to building surfaces include the following:
1.
ASTM A 36/A 36M, steel plates,
Powder-Actuated Fasteners: Threaded-steel stud, for use in hardened portland cement
concrete, steel, or wood, with tension, shear, and pullout capacities appropriate for
supported loads and building materials where used.
a.
Manufacturers: Subject to compliance with requirements, provide products by one
of the following (or approved equivalent determined by Department Project
Manager):
1)
2)
3)
4)
Hilti Inc.
ITW Ramset/Red Head; a division of Illinois Tool Works, Inc.
MKT Fastening, LLC.
Simpson Strong-Tie Co., Inc.; Masterset Fastening Systems Unit.
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260529 - 3
2.
Mechanical-Expansion Anchors: Insert-wedge-type, zinc-coated steel, for use in
hardened portland cement concrete with tension, shear, and pullout capacities appropriate
for supported loads and building materials in which used.
a.
Manufacturers: Subject to compliance with requirements, provide products by one
of the following (or approved equivalent determined by Department Project
Manager):
1)
2)
3)
4)
5)
3.
4.
5.
6.
7.
2.2
Cooper B-Line, Inc.; a division of Cooper Industries.
Empire Tool and Manufacturing Co., Inc.
Hilti Inc.
ITW Ramset/Red Head; a division of Illinois Tool Works, Inc.
MKT Fastening, LLC.
Concrete Inserts: Steel or malleable-iron, slotted support system units similar to MSS
Type 18; complying with MFMA-4 or MSS SP-58.
Clamps for Attachment to Steel Structural Elements: MSS SP-58, type suitable for
attached structural element.
Through Bolts: Structural type, hex head, and high strength. Comply with
ASTM A 325.
Toggle Bolts: All-steel springhead type.
Hanger Rods: Threaded steel.
FABRICATED METAL EQUIPMENT SUPPORT ASSEMBLIES
A.
Description: Welded or bolted, structural-steel shapes, shop or field fabricated to fit dimensions
of supported equipment.
B.
Materials: Comply with requirements in Section 055000 "Metal Fabrications" for steel shapes
and plates.
PART 3 - EXECUTION
3.1
APPLICATION
A.
Comply with NECA 1 and NECA 101 for application of hangers and supports for electrical
equipment and systems except if requirements in this Section are stricter.
B.
Multiple Raceways or Cables: Install trapeze-type supports fabricated with steel slotted support
system, sized so capacity can be increased by at least 25 percent in future without exceeding
specified design load limits.
1.
3.2
Secure raceways and cables to these supports with two-bolt conduit clamps .
SUPPORT INSTALLATION
A.
Comply with NECA 1 and NECA 101 for installation requirements except as specified in this
Article.
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260529 - 4
B.
Raceway Support Methods: In addition to methods described in NECA 1, EMT IMC RMC
EMT, IMC, and RMC may be supported by openings through structure members, as permitted
in NFPA 70.
C.
Strength of Support Assemblies: Where not indicated, select sizes of components so strength
will be adequate to carry present and future static loads within specified loading limits.
Minimum static design load used for strength determination shall be weight of supported
components plus 200 lb (90 kg).
D.
Mounting and Anchorage of Surface-Mounted Equipment and Components: Anchor and fasten
electrical items and their supports to building structural elements by the following methods
unless otherwise indicated by code:
1.
2.
3.
4.
5.
6.
7.
8.
E.
3.3
To Wood: Fasten with lag screws or through bolts.
To New Concrete: Bolt to concrete inserts.
To Masonry: Approved toggle-type bolts on hollow masonry units and expansion anchor
fasteners on solid masonry units.
To Existing Concrete: Expansion anchor fasteners.
Instead of expansion anchors, powder-actuated driven threaded studs provided with lock
washers and nuts may be used in existing standard-weight concrete 4 inches (100 mm)
thick or greater. Do not use for anchorage to lightweight-aggregate concrete or for slabs
less than 4 inches (100 mm) thick.
To Steel: Beam clamps (MSS Type 19, 21, 23, 25, or 27) complying with MSS SP-69 .
To Light Steel: Sheet metal screws.
Items Mounted on Hollow Walls and Nonstructural Building Surfaces: Mount cabinets,
panelboards, disconnect switches, control enclosures, pull and junction boxes,
transformers, and other devices on slotted-channel racks attached to substrate.
Drill holes for expansion anchors in concrete at locations and to depths that avoid reinforcing
bars.
INSTALLATION OF FABRICATED METAL SUPPORTS
A.
Comply with installation requirements in Section 055000 "Metal Fabrications" for sitefabricated metal supports.
B.
Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and elevation
to support and anchor electrical materials and equipment.
C.
Field Welding: Comply with AWS D1.1/D1.1M.
3.4
CONCRETE BASES
A.
Construct concrete bases of dimensions indicated but not less than 4 inches (100 mm) larger in
both directions than supported unit, and so anchors will be a minimum of 10 bolt diameters
from edge of the base.
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260529 - 5
B.
Use 3000-psi (20.7-MPa) , 28-day compressive-strength concrete. Concrete materials,
reinforcement, and placement requirements are specified in Section 033000 "Cast-in-Place
Concrete."
C.
Anchor equipment to concrete base.
1.
2.
3.
3.5
Place and secure anchorage devices. Use supported equipment manufacturer's setting
drawings, templates, diagrams, instructions, and directions furnished with items to be
embedded.
Install anchor bolts to elevations required for proper attachment to supported equipment.
Install anchor bolts according to anchor-bolt manufacturer's written instructions.
PAINTING
A.
Touchup: Clean field welds and abraded areas of shop paint. Paint exposed areas immediately
after erecting hangers and supports. Use same materials as used for shop painting. Comply
with SSPC-PA 1 requirements for touching up field-painted surfaces.
1.
B.
Apply paint by brush or spray to provide minimum dry film thickness of 2.0 mils (0.05
mm).
Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply
galvanizing-repair paint to comply with ASTM A 780.
END OF SECTION 260529
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260529 - 6
SECTION 260533 - RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract Documents apply to this Section.
SUMMARY
A.
Section Includes:
1.
2.
3.
4.
5.
6.
7.
B.
Related Requirements:
1.
2.
3.
1.3
Metal conduits, tubing, and fittings.
Nonmetal conduits, tubing, and fittings.
Metal wireways and auxiliary gutters.
Nonmetal wireways and auxiliary gutters.
Surface raceways.
Boxes, enclosures, and cabinets.
Handholes and boxes for exterior underground cabling.
Section 260543 "Underground Ducts and Raceways for Electrical Systems" for exterior
ductbanks, manholes, and underground utility construction.
Section 270528 "Pathways for Communications Systems" for conduits, wireways,
surface pathways, innerduct, boxes, faceplate adapters, enclosures, cabinets, and
handholes serving communications systems.
Section 280528 "Pathways for Electronic Safety and Security" for conduits, surface
pathways, innerduct, boxes, and faceplate adapters serving electronic safety and security.
DEFINITIONS
A.
GRC: Galvanized rigid steel conduit.
B.
IMC: Intermediate metal conduit.
1.4
ACTION SUBMITTALS
A.
Product Data: For surface raceways, wireways and fittings, floor boxes, hinged-cover
enclosures, and cabinets.
B.
Shop Drawings: For custom enclosures and cabinets. Include plans, elevations, sections, and
attachment details.
RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260533 - 1
1.5
INFORMATIONAL SUBMITTALS
A.
Coordination Drawings: Conduit routing plans, drawn to scale, on which the following items
are shown and coordinated with each other, using input from installers of items involved:
1.
2.
B.
Structural members in paths of conduit groups with common supports.
HVAC and plumbing items and architectural features in paths of conduit groups with
common supports.
Source quality-control reports.
PART 2 - PRODUCTS
2.1
METAL CONDUITS, TUBING, AND FITTINGS
A.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following (or approved equivalent determined by Department Project Manager):
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
AFC Cable Systems, Inc.
Allied Tube & Conduit; a Tyco International Ltd. Co.
Anamet Electrical, Inc.
Electri-Flex Company.
O-Z/Gedney; a brand of EGS Electrical Group.
Picoma Industries, a subsidiary of Mueller Water Products, Inc.
Republic Conduit.
Robroy Industries.
Southwire Company.
Thomas & Betts Corporation.
Western Tube and Conduit Corporation.
Wheatland Tube Company; a division of John Maneely Company.
B.
Listing and Labeling: Metal conduits, tubing, and fittings shall be listed and labeled as defined
in NFPA 70, by a qualified testing agency, and marked for intended location and application.
C.
GRC: Comply with ANSI C80.1 and UL 6.
D.
IMC: Comply with ANSI C80.6 and UL 1242.
E.
EMT: Comply with ANSI C80.3 and UL 797.
F.
FMC: Comply with UL 1; zinc-coated steel or aluminum.
G.
LFMC: Flexible steel conduit with PVC jacket and complying with UL 360.
H.
Fittings for Metal Conduit: Comply with NEMA FB 1 and UL 514B.
1.
2.
Conduit Fittings for Hazardous (Classified) Locations:
NFPA 70.
Fittings for EMT:
RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
Comply with UL 886 and
260533 - 2
a.
b.
3.
4.
I.
2.2
Material: Steel or die cast.
Type: compression.
Expansion Fittings: PVC or steel to match conduit type, complying with UL 651, rated
for environmental conditions where installed, and including flexible external bonding
jumper.
Coating for Fittings for PVC-Coated Conduit: Minimum thickness of 0.040 inch (1 mm),
with overlapping sleeves protecting threaded joints.
Joint Compound for IMC, or GRC : Approved, as defined in NFPA 70, by authorities having
jurisdiction for use in conduit assemblies, and compounded for use to lubricate and protect
threaded conduit joints from corrosion and to enhance their conductivity.
NONMETALLIC CONDUITS, TUBING, AND FITTINGS
A.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following (or approved equivalent determined by Department Project Manager):
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
AFC Cable Systems, Inc.
Anamet Electrical, Inc.
Arnco Corporation.
CANTEX Inc.
CertainTeed Corp.
Condux International, Inc.
Electri-Flex Company.
Kraloy.
Lamson & Sessions; Carlon Electrical Products.
Niedax-Kleinhuis USA, Inc.
RACO; a Hubbell company.
Thomas & Betts Corporation.
B.
Listing and Labeling: Nonmetallic conduits, tubing, and fittings shall be listed and labeled as
defined in NFPA 70, by a qualified testing agency, and marked for intended location and
application.
C.
RNC: Type EPC-40-PVC , complying with NEMA TC 2 and UL 651 unless otherwise
indicated.
D.
LFNC: Comply with UL 1660.
E.
Fittings for LFNC: Comply with UL 514B.
F.
Solvent cements and adhesive primers shall have a VOC content of 510 and 550 g/L or less,
respectively, when calculated according to 40 CFR 59, Subpart D (EPA Method 24).
RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260533 - 3
2.3
METAL WIREWAYS AND AUXILIARY GUTTERS
A.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following (or approved equivalent determined by Department Project Manager):
1.
2.
3.
4.
B.
Cooper B-Line, Inc.
Hoffman; a Pentair company.
Mono-Systems, Inc.
Square D; a brand of Schneider Electric.
Description: Sheet metal, complying with UL 870 and NEMA 250, Type 1 Type 3R Type 4 or
Type 12 unless otherwise indicated, and sized according to NFPA 70.
1.
Metal wireways installed outdoors shall be listed and labeled as defined in NFPA 70, by a
qualified testing agency, and marked for intended location and application.
C.
Fittings and Accessories: Include covers, couplings, offsets, elbows, expansion joints, adapters,
hold-down straps, end caps, and other fittings to match and mate with wireways as required for
complete system.
D.
Wireway Covers:
E.
Finish: Manufacturer's standard enamel finish.
2.4
Flanged-and-gasketed type unless otherwise indicated.
NONMETALLIC WIREWAYS AND AUXILIARY GUTTERS
A.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following (or approved equivalent determined by Department Project Manager):
1.
2.
3.
4.
Allied Moulded Products, Inc.
Hoffman; a Pentair company.
Lamson & Sessions; Carlon Electrical Products.
Niedax-Kleinhuis USA, Inc.
B.
Listing and Labeling: Nonmetallic wireways and auxiliary gutters shall be listed and labeled as
defined in NFPA 70, by a qualified testing agency, and marked for intended location and
application.
C.
Description: Fiberglass polyester, extruded and fabricated to required size and shape, without
holes or knockouts. Cover shall be gasketed with oil-resistant gasket material and fastened with
captive screws treated for corrosion resistance. Connections shall be flanged and have stainlesssteel screws and oil-resistant gaskets.
D.
Fittings and Accessories: Couplings, offsets, elbows, expansion joints, adapters, hold-down
straps, end caps, and other fittings shall match and mate with wireways as required for complete
system.
E.
Solvent cements and adhesive primers shall have a VOC content of 510 and 550 g/L or less,
respectively, when calculated according to 40 CFR 59, Subpart D (EPA Method 24).
RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260533 - 4
2.5
SURFACE RACEWAYS
A.
Listing and Labeling: Surface raceways and tele-power poles shall be listed and labeled as
defined in NFPA 70, by a qualified testing agency, and marked for intended location and
application.
B.
Surface Metal Raceways: Galvanized steel with snap-on covers complying with UL 5.
Manufacturer's standard enamel finish in color selected by Architect .
1.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following (or approved equivalent determined by Department Project Manager):
a.
b.
c.
C.
Surface Nonmetallic Raceways: Two- or three-piece construction, complying with UL 5A, and
manufactured of rigid PVC with texture and color selected by Architect from manufacturer's
standard colors. Product shall comply with UL 94 V-0 requirements for self-extinguishing
characteristics.
1.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following (or approved equivalent determined by Department Project Manager):
a.
b.
c.
d.
2.6
Mono-Systems, Inc.
Panduit Corp.
Wiremold / Legrand.
Hubbell Incorporated; Wiring Device-Kellems Division.
Mono-Systems, Inc.
Panduit Corp.
Wiremold / Legrand.
BOXES, ENCLOSURES, AND CABINETS
A.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following (or approved equivalent determined by Department Project Manager):
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
Adalet.
Cooper Technologies Company; Cooper Crouse-Hinds.
EGS/Appleton Electric.
Erickson Electrical Equipment Company.
FSR Inc.
Hoffman; a Pentair company.
Hubbell Incorporated; Killark Division.
Kraloy.
Milbank Manufacturing Co.
Mono-Systems, Inc.
O-Z/Gedney; a brand of EGS Electrical Group.
RACO; a Hubbell Company.
Robroy Industries.
Spring City Electrical Manufacturing Company.
Stahlin Non-Metallic Enclosures; a division of Robroy Industries.
RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260533 - 5
16.
17.
Thomas & Betts Corporation.
Wiremold / Legrand.
B.
General Requirements for Boxes, Enclosures, and Cabinets: Boxes, enclosures, and cabinets
installed in wet locations shall be listed for use in wet locations.
C.
Sheet Metal Outlet and Device Boxes: Comply with NEMA OS 1 and UL 514A.
D.
Cast-Metal Outlet and Device Boxes: Comply with NEMA FB 1, ferrous alloyoraluminum,
Type FD, with gasketed cover.
E.
Metal Floor Boxes:
1.
2.
3.
4.
Material: Cast metal .
Type: Fully adjustable .
Shape: Rectangular.
Listing and Labeling: Metal floor boxes shall be listed and labeled as defined in
NFPA 70, by a qualified testing agency, and marked for intended location and
application.
F.
Luminaire Outlet Boxes: Nonadjustable, designed for attachment of luminaire weighing 50 lb
(23 kg). Outlet boxes designed for attachment of luminaires weighing more than 50 lb (23 kg)
shall be listed and marked for the maximum allowable weight.
G.
Small Sheet Metal Pull and Junction Boxes: NEMA OS 1.
H.
Cast-Metal Access, Pull, and Junction Boxes: Comply with NEMA FB 1 and UL 1773, cast
aluminumor galvanized, cast iron with gasketed cover.
I.
Box extensions used to accommodate new building finishes shall be of same material as
recessed box.
J.
Device Box Dimensions: 4 inches square by 2-1/8 inches deep (100 mm square by 60 mm
deep) .
K.
Gangable boxes are allowed .
L.
Hinged-Cover Enclosures: Comply with UL 50 and NEMA 250, Type 1, Type 3R, Type 4
orType 12 with continuous-hinge cover with flush latch unless otherwise indicated.
1.
2.
3.
M.
Metal Enclosures: Steel, finished inside and out with manufacturer's standard enamel.
Nonmetallic Enclosures: Fiberglass.
Interior Panels: Steel; all sides finished with manufacturer's standard enamel.
Cabinets:
1.
2.
3.
4.
NEMA 250, Type 1, Type 3Ror Type 12 galvanized-steel box with removable interior
panel and removable front, finished inside and out with manufacturer's standard enamel.
Hinged door in front cover with flush latch and concealed hinge.
Key latch to match panelboards.
Metal barriers to separate wiring of different systems and voltage.
RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260533 - 6
5.
6.
Accessory feet where required for freestanding equipment.
Nonmetallic cabinets shall be listed and labeled as defined in NFPA 70, by a qualified
testing agency, and marked for intended location and application.
PART 3 - EXECUTION
3.1
RACEWAY APPLICATION
A.
Outdoors: Apply raceway products as specified below unless otherwise indicated:
1.
2.
3.
4.
5.
B.
Exposed Conduit: GRC .
Concealed Conduit, Aboveground: GRC .
Underground Conduit: RNC, Type EPC-40-PVC , concrete encased.
Connection to Vibrating Equipment (Including Transformers and Hydraulic, Pneumatic,
Electric Solenoid, or Motor-Driven Equipment): LFNC.
Boxes and Enclosures, Aboveground: NEMA 250, Type 4.
Indoors: Apply raceway products as specified below unless otherwise indicated:
1.
2.
3.
Exposed, Not Subject to Physical Damage: EMT .
Exposed, Not Subject to Severe Physical Damage: EMT .
Exposed and Subject to Severe Physical Damage: GRC . Raceway locations include the
following:
a.
b.
c.
d.
e.
4.
5.
6.
7.
Loading dock.
Corridors used for traffic of mechanized carts, forklifts, and pallet-handling units.
Mechanical rooms.
Gymnasiums.
Maintenance Building.
Concealed in Ceilings and Interior Walls and Partitions: EMT .
Connection to Vibrating Equipment (Including Transformers and Hydraulic, Pneumatic,
Electric Solenoid, or Motor-Driven Equipment): FMC, except use LFMC in damp or wet
locations.
Damp or Wet Locations: GRC .
Boxes and Enclosures: NEMA 250, Type 1, except use NEMA 250, Type 4 stainless
steel in damp or wet locations.
C.
Minimum Raceway Size: 3/4-inch (21-mm) trade size.
D.
Raceway Fittings: Compatible with raceways and suitable for use and location.
1.
2.
Rigid and Intermediate Steel Conduit: Use threaded rigid steel conduit fittings unless
otherwise indicated. Comply with NEMA FB 2.10.
PVC Externally Coated, Rigid Steel Conduits: Use only fittings listed for use with this
type of conduit. Patch and seal all joints, nicks, and scrapes in PVC coating after
installing conduits and fittings. Use sealant recommended by fitting manufacturer and
apply in thickness and number of coats recommended by manufacturer.
RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260533 - 7
3.
4.
E.
3.2
EMT: Use setscrew or compression, steel fittings. Comply with NEMA FB 2.10.
Flexible Conduit: Use only fittings listed for use with flexible conduit. Comply with
NEMA FB 2.20.
Do not install aluminum conduits, boxes, or fittings in contact with concrete or earth.
INSTALLATION
A.
Comply with NECA 1 and NECA 101 for installation requirements except where requirements
on Drawings or in this article are stricter. Comply with NFPA 70 limitations for types of
raceways allowed in specific occupancies and number of floors.
B.
Keep raceways at least 6 inches (150 mm) away from parallel runs of flues and steam or hotwater pipes. Install horizontal raceway runs above water and steam piping.
C.
Complete raceway installation before starting conductor installation.
D.
Comply with requirements in Section 260529 "Hangers and Supports for Electrical Systems"
for hangers and supports.
E.
Arrange stub-ups so curved portions of bends are not visible above finished slab.
F.
Install no more than the equivalent of three 90-degree bends in any conduit run except for
control wiring conduits, for which fewer bends are allowed. Support within 12 inches (300
mm) of changes in direction.
G.
Conceal conduit and EMT within finished walls, ceilings, and floors unless otherwise indicated.
Install conduits parallel or perpendicular to building lines.
H.
Support conduit within 12 inches (300 mm) of enclosures to which attached.
I.
Raceways Embedded in Slabs:
1.
2.
3.
4.
J.
Run conduit larger than 1-inch (27-mm) trade size, parallel or at right angles to main
reinforcement. Where at right angles to reinforcement, place conduit close to slab
support. Secure raceways to reinforcement at maximum 10-foot (3-m) intervals.
Arrange raceways to cross building expansion joints at right angles with expansion
fittings.
Arrange raceways to keep a minimum of 1 inch (25 mm) of concrete cover in all
directions.
Do not embed threadless fittings in concrete unless specifically approved by Architect for
each specific location.
Stub-ups to Above Recessed Ceilings:
1.
2.
Use EMT, for raceways.
Use a conduit bushing or insulated fitting to terminate stub-ups not terminated in hubs or
in an enclosure.
RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260533 - 8
K.
Threaded Conduit Joints, Exposed to Wet, Damp, Corrosive, or Outdoor Conditions: Apply
listed compound to threads of raceway and fittings before making up joints. Follow compound
manufacturer's written instructions.
L.
Raceway Terminations at Locations Subject to Moisture or Vibration: Use insulating bushings
to protect conductors including conductors smaller than No. 4 AWG.
M.
Install raceways square to the enclosure and terminate at enclosures with locknuts. Install
locknuts hand tight plus 1/4 turn more.
N.
Do not rely on locknuts to penetrate nonconductive coatings on enclosures. Remove coatings in
the locknut area prior to assembling conduit to enclosure to assure a continuous ground path.
O.
Cut conduit perpendicular to the length. For conduits 2-inch (53-mm) trade size and larger, use
roll cutter or a guide to make cut straight and perpendicular to the length.
P.
Install pull wires in empty raceways. Use polypropylene or monofilament plastic line with not
less than 200-lb (90-kg) tensile strength. Leave at least 12 inches (300 mm) of slack at each end
of pull wire. Cap underground raceways designated as spare above grade alongside raceways in
use.
Q.
Surface Raceways:
1.
2.
Install surface raceway with a minimum 2-inch (50-mm)radius control at bend points.
Secure surface raceway with screws or other anchor-type devices at intervals not
exceeding 48 inches (1200 mm) and with no less than two supports per straight raceway
section. Support surface raceway according to manufacturer's written instructions. Tape
and glue are not acceptable support methods.
R.
Install raceway sealing fittings at accessible locations according to NFPA 70 and fill them with
listed sealing compound. For concealed raceways, install each fitting in a flush steel box with a
blank cover plate having a finish similar to that of adjacent plates or surfaces. Install raceway
sealing fittings according to NFPA 70.
S.
Install devices to seal raceway interiors at accessible locations. Locate seals so no fittings or
boxes are between the seal and the following changes of environments. Seal the interior of all
raceways at the following points:
1.
2.
3.
T.
Where conduits pass from warm to cold locations, such as boundaries of refrigerated
spaces.
Where an underground service raceway enters a building or structure.
Where otherwise required by NFPA 70.
Expansion-Joint Fittings:
1.
2.
Install in each run of aboveground RMC and EMT conduit that is located where
environmental temperature change may exceed 100 deg F (55 deg C) and that has
straight-run length that exceeds 100 feet (30 m).
Install expansion fittings at all locations where conduits cross building or structure
expansion joints.
RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260533 - 9
3.
U.
Install each expansion-joint fitting with position, mounting, and piston setting selected
according to manufacturer's written instructions for conditions at specific location at time
of installation. Install conduit supports to allow for expansion movement.
Flexible Conduit Connections: Comply with NEMA RV 3. Use a maximum of 72 inches
(1830 mm) of flexible conduit for recessed and semirecessed luminaires, equipment subject to
vibration, noise transmission, or movement; and for transformers and motors.
1.
2.
Use LFMC in damp or wet locations subject to severe physical damage.
Use LFMC or LFNC in damp or wet locations not subject to severe physical damage.
V.
Mount boxes at heights indicated on Drawings. If mounting heights of boxes are not
individually indicated, give priority to ADA requirements. Install boxes with height measured
to center of box unless otherwise indicated.
W.
Recessed Boxes in Masonry Walls: Saw-cut opening for box in center of cell of masonry block,
and install box flush with surface of wall. Prepare block surfaces to provide a flat surface for a
raintight connection between box and cover plate or supported equipment and box.
X.
Horizontally separate boxes mounted on opposite sides of walls so they are not in the same
vertical channel.
Y.
Locate boxes so that cover or plate will not span different building finishes.
Z.
Support boxes of three gangs or more from more than one side by spanning two framing
members or mounting on brackets specifically designed for the purpose.
AA. Fasten junction and pull boxes to or support from building structure. Do not support boxes by
conduits.
BB.
Set metal floor boxes level and flush with finished floor surface.
CC.
Set nonmetallic floor boxes level. Trim after installation to fit flush with finished floor surface.
3.3
SLEEVE AND SLEEVE-SEAL INSTALLATION FOR ELECTRICAL PENETRATIONS
A.
3.4
Install sleeves and sleeve seals at penetrations of exterior floor and wall assemblies. Comply
with requirements in Section 260544 "Sleeves and Sleeve Seals for Electrical Raceways and
Cabling."
FIRESTOPPING
A.
3.5
Install firestopping at penetrations of fire-rated floor and wall assemblies.
requirements in Section 078413 "Penetration Firestopping."
Comply with
PROTECTION
A.
Protect coatings, finishes, and cabinets from damage and deterioration.
RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260533 - 10
1.
2.
Repair damage to galvanized finishes with zinc-rich paint recommended by
manufacturer.
Repair damage to PVC coatings or paint finishes with matching touchup coating
recommended by manufacturer.
END OF SECTION 260533
RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260533 - 11
SECTION 260543 - UNDERGROUND DUCTS & RACEWAYS FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract Documents apply to this Section.
SUMMARY
A.
This Section includes the following:
1.
2.
3.
1.3
Conduit, ducts, and duct accessories for concrete-encased duct banks, and in single duct
runs.
Handholes and boxes.
Manholes.
DEFINITION
A.
1.4
RNC: Rigid nonmetallic conduit.
ACTION SUBMITTALS
A.
Product Data: For the following:
1.
2.
3.
4.
5.
1.5
Duct-bank materials, including separators and miscellaneous components.
Ducts and conduits and their accessories, including elbows, end bells, bends, fittings, and
solvent cement.
Accessories for manholes, handholes, boxes.
Warning tape.
Warning planks.
INFORMATIONAL SUBMITTALS
A.
Duct-Bank Coordination Drawings: Show duct profiles and coordination with other utilities
and underground structures.
1.
2.
B.
Include plans and sections, drawn to scale, and show bends and locations of expansion
fittings.
Drawings shall be signed and sealed by a qualified professional engineer.
Product Certificates: For concrete and steel used in precast concrete manholes and handholes,
as required by ASTM C 858.
UNDERGROUND DUCTS & RACEWAYS FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260543 - 1
1.6
QUALITY ASSURANCE
A.
Comply with ANSI C2.
B.
Comply with NFPA 70.
1.7
DELIVERY, STORAGE, AND HANDLING
A.
Deliver ducts to Project site with ends capped. Store nonmetallic ducts with supports to prevent
bending, warping, and deforming.
B.
Store precast concrete and other factory-fabricated underground utility structures at Project site
as recommended by manufacturer to prevent physical damage. Arrange so identification
markings are visible.
C.
Lift and support precast concrete units only at designated lifting or supporting points.
1.8
COORDINATION
A.
Coordinate layout and installation of ducts, manholes, handholes, and boxes with final
arrangement of other utilities, site grading, and surface features as determined in the field.
B.
Coordinate elevations of ducts and duct-bank entrances into manholes, handholes, and boxes
with final locations and profiles of ducts and duct banks as determined by coordination with
other utilities, underground obstructions, and surface features. Revise locations and elevations
from those indicated as required to suit field conditions and to ensure that duct runs drain to
manholes and handholes, and as approved by Architect.
PART 2 - PRODUCTS
2.1
CONDUIT
A.
2.2
RNC: NEMA TC 2, Type EPC-40-PVC , UL 651, with matching fittings by same
manufacturer as the conduit, complying with NEMA TC 3 and UL 514B.
NONMETALLIC DUCTS AND DUCT ACCESSORIES
A.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following (or approved equivalent determined by Department Project Manager):
1.
2.
3.
4.
5.
6.
ARNCO Corp.
Beck Manufacturing.
Cantex, Inc.
CertainTeed Corp.; Pipe & Plastics Group.
Condux International, Inc.
ElecSys, Inc.
UNDERGROUND DUCTS & RACEWAYS FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260543 - 2
7.
8.
9.
10.
11.
B.
Electri-Flex Company.
IPEX Inc.
Lamson & Sessions; Carlon Electrical Products.
Manhattan/CDT; a division of Cable Design Technologies.
Spiraduct/AFC Cable Systems, Inc.
Duct Accessories:
1.
2.
3.
Duct Separators: Factory-fabricated rigid PVC interlocking spacers, sized for type and
sizes of ducts with which used, and selected to provide minimum duct spacings indicated
while supporting ducts during concreting or backfilling.
Warning Tape:
Underground-line warning tape specified in Section 260553
"Identification for Electrical Systems."
Concrete Warning Planks: Nominal 12 by 24 by 3 inches (300 by 600 by 76 mm) in size,
manufactured from 6000-psi (41-MPa) concrete.
a.
b.
2.3
Color: Red dye added to concrete during batching.
Mark each plank with "ELECTRIC" in 2-inch- (50-mm-) high, 3/8-inch- (10-mm-)
deep letters.
PRECAST CONCRETE HANDHOLES AND BOXES
A.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following (or approved equivalent determined by Department Project Manager):
1.
2.
3.
4.
5.
6.
7.
Carder Concrete Products.
Christy Concrete Products.
Elmhurst-Chicago Stone Co.
Oldcastle Precast Group.
Riverton Concrete Products; a division of Cretex Companies, Inc.
Utility Concrete Products, LLC.
Utility Vault Co.
B.
Comply with ASTM C 858 for design and manufacturing processes.
C.
Description: Factory-fabricated, reinforced-concrete, monolithically poured walls and bottom
unless open-bottom enclosures are indicated. Frame and cover shall form top of enclosure and
shall have load rating consistent with that of handhole or box.
1.
Frame and Cover: Weatherproof cast-iron frame, with cast-iron cover with recessed
cover hook eyes and tamper-resistant, captive, cover-securing bolts.
2.
3.
4.
Cover Finish: Nonskid finish shall have a minimum coefficient of friction of 0.50.
Cover Legend: Molded lettering, As indicated for each service.
Configuration: Units shall be designed for flush burial and have open bottom, unless
otherwise indicated.
UNDERGROUND DUCTS & RACEWAYS FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260543 - 3
5.
Windows: Precast openings in walls, arranged to match dimensions and elevations of
approaching ducts and duct banks plus an additional 12 inches (300 mm) vertically and
horizontally to accommodate alignment variations.
a.
b.
c.
6.
2.4
Windows shall be located no less than 6 inches (150 mm) from interior surfaces of
walls, floors, or frames and covers of handholes, but close enough to corners to
facilitate racking of cables on walls.
Window opening shall have cast-in-place, welded wire fabric reinforcement for
field cutting and bending to tie in to concrete envelopes of duct banks.
Window openings shall be framed with at least two additional No. 4 steel
reinforcing bars in concrete around each opening.
Handholes 12 inches wide by 24 inches long (300 mm wide by 600 mm long) and larger
shall have inserts for cable racks and pulling-in irons installed before concrete is poured.
PRECAST MANHOLES
A.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following (or approved equivalent determined by Department Project Manager):
1.
2.
3.
4.
5.
6.
7.
B.
Carder Concrete Products.
Christy Concrete Products.
Elmhurst-Chicago Stone Co.
Oldcastle Precast Group.
Riverton Concrete Products; a division of Cretex Companies, Inc.
Utility Concrete Products, LLC.
Utility Vault Co.
Comply with ASTM C 858 and with interlocking mating sections, complete with accessories,
hardware, and features.
1.
Windows: Precast openings in walls, arranged to match dimensions and elevations of
approaching ducts and duct banks plus an additional 12 inches (300 mm) vertically and
horizontally to accommodate alignment variations.
a.
b.
c.
Windows shall be located no less than 6 inches (150 mm) from interior surfaces of
walls, floors, or roofs of manholes, but close enough to corners to facilitate racking
of cables on walls.
Window opening shall have cast-in-place, welded wire fabric reinforcement for
field cutting and bending to tie in to concrete envelopes of duct banks.
Window openings shall be framed with at least two additional No. 4 steel
reinforcing bars in concrete around each opening.
C.
Concrete Knockout Panels: 1-1/2 to 2 inches (38 to 50 mm) thick, for future conduit entrance
and sleeve for ground rod.
D.
Joint Sealant: Asphaltic-butyl material with adhesion, cohesion, flexibility, and durability
properties necessary to withstand maximum hydrostatic pressures at the installation location
with the ground-water level at grade.
UNDERGROUND DUCTS & RACEWAYS FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260543 - 4
2.5
SOURCE QUALITY CONTROL
A.
Test and inspect precast concrete utility structures according to ASTM C 1037.
PART 3 - EXECUTION
3.1
UNDERGROUND DUCT APPLICATION
A.
Ducts for Electrical Feeders 600 V and Less: RNC, NEMA Type EPC-40 -PVC, in concreteencased duct bank, unless otherwise indicated.
B.
Underground Ducts for Telephone, Communications, or Data Utility Service Cables: RNC,
NEMA Type EPC-40 -PVC, in concrete-encased duct bank, unless otherwise indicated.
3.2
UNDERGROUND ENCLOSURE APPLICATION
A.
Handholes and Boxes for 600 V and Less, Including Telephone, Communications, and Data
Wiring:
1.
2.
B.
Manholes: Precast or cast-in-place concrete.
1.
3.3
Units in Roadways and Other Deliberate Traffic Paths:
Precast concrete.
AASHTO HB 17, H-20 structural load rating.
Units in Sidewalk and Similar Applications with a Safety Factor for Nondeliberate
Loading by Vehicles: Precast concrete, AASHTO HB 17, H-10 structural load rating.
Units Located in Roadways and Other Deliberate Traffic Paths by Heavy or Medium
Vehicles: H-20 structural load rating according to AASHTO HB 17.
EARTHWORK
A.
Excavation and Backfill: Comply with Section 312000 "Earth Moving," but do not use heavyduty, hydraulic-operated, compaction equipment.
B.
Restore surface features at areas disturbed by excavation and reestablish original grades, unless
otherwise indicated. Replace removed sod immediately after backfilling is completed.
C.
Restore areas disturbed by trenching, storing of dirt, cable laying, and other work. Restore
vegetation and include necessary topsoiling, fertilizing, liming, seeding, sodding, sprigging, and
mulching. Comply with Section 329200 "Turf and Grasses" and Section 329300 "Plants."
D.
Cut and patch existing pavement in the path of underground ducts and utility structures
according to Section 017329 "Cutting and Patching."
UNDERGROUND DUCTS & RACEWAYS FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260543 - 5
3.4
DUCT INSTALLATION
A.
Slope: Pitch ducts a minimum slope of 1:300 down toward manholes and handholes and away
from buildings and equipment. Slope ducts from a high point in runs between two manholes to
drain in both directions.
B.
Curves and Bends: Use 5-degree angle couplings for small changes in direction. Use
manufactured long sweep bends with a minimum radius of 48 inches (1220 mm) , both
horizontally and vertically, at other locations, unless otherwise indicated.
C.
Joints: Use solvent-cemented joints in ducts and fittings and make watertight according to
manufacturer's written instructions. Stagger couplings so those of adjacent ducts do not lie in
same plane.
D.
Duct Entrances to Manholes and Concrete and Polymer Concrete Handholes: Use end bells,
spaced approximately 10 inches (250 mm) o.c. for 5-inch (125-mm) ducts, and vary
proportionately for other duct sizes.
1.
2.
Begin change from regular spacing to end-bell spacing 10 feet (3 m) from the end bell
without reducing duct line slope and without forming a trap in the line.
Grout end bells into structure walls from both sides to provide watertight entrances.
E.
Building Wall Penetrations: Make a transition from underground duct to rigid steel conduit at
least 10 feet (3 m) outside the building wall without reducing duct line slope away from the
building, and without forming a trap in the line. Use fittings manufactured for duct-to-conduit
transition. Install conduit penetrations of building walls as specified in Section 260544
"Sleeves and Sleeve Seals for Electrical Raceways and Cabling."
F.
Sealing: Provide temporary closure at terminations of ducts that have cables pulled. Seal spare
ducts at terminations. Use sealing compound and plugs to withstand at least 15-psig (1.03MPa) hydrostatic pressure.
G.
Pulling Cord: Install 100-lbf- (445-N-) test nylon cord in ducts, including spares.
H.
Concrete-Encased Ducts: Support ducts on duct separators.
1.
2.
Separator Installation: Space separators close enough to prevent sagging and deforming
of ducts, with not less than 5 spacers per 20 feet (6 m) of duct. Secure separators to earth
and to ducts to prevent floating during concreting. Stagger separators approximately 6
inches (150 mm) between tiers. Tie entire assembly together using fabric straps; do not
use tie wires or reinforcing steel that may form conductive or magnetic loops around
ducts or duct groups.
Concreting Sequence: Pour each run of envelope between manholes or other
terminations in one continuous operation.
a.
Start at one end and finish at the other, allowing for expansion and contraction of
ducts as their temperature changes during and after the pour. Use expansion
fittings installed according to manufacturer's written recommendations, or use
other specific measures to prevent expansion-contraction damage.
UNDERGROUND DUCTS & RACEWAYS FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260543 - 6
b.
3.
4.
5.
6.
7.
Pouring Concrete: Spade concrete carefully during pours to prevent voids under and
between conduits and at exterior surface of envelope. Do not allow a heavy mass of
concrete to fall directly onto ducts. Use a plank to direct concrete down sides of bank
assembly to trench bottom. Allow concrete to flow to center of bank and rise up in
middle, uniformly filling all open spaces. Do not use power-driven agitating equipment
unless specifically designed for duct-bank application.
Forms: Use walls of trench to form side walls of duct bank where soil is self-supporting
and concrete envelope can be poured without soil inclusions; otherwise, use forms.
Minimum Space between Ducts: 3 inches (75 mm) between ducts and exterior envelope
wall, 2 inches (50 mm) between ducts for like services, and 4 inches (100 mm) between
power and signal ducts.
Depth: Install top of duct bank at least 24 inches (600 mm) below finished grade in areas
not subject to deliberate traffic, and at least 30 inches (750 mm) below finished grade in
deliberate traffic paths for vehicles, unless otherwise indicated.
Stub-Ups: Use manufactured rigid steel conduit elbows for stub-ups at poles and
equipment and at building entrances through the floor.
a.
b.
8.
3.5
If more than one pour is necessary, terminate each pour in a vertical plane and
install 3/4-inch (19-mm) reinforcing rod dowels extending 18 inches (450 mm)
into concrete on both sides of joint near corners of envelope.
Couple steel conduits to ducts with adapters designed for this purpose, and encase
coupling with 3 inches (75 mm) of concrete.
Stub-Ups to Equipment: For equipment mounted on outdoor concrete bases,
extend steel conduit horizontally a minimum of 60 inches (1500 mm) from edge of
base. Install insulated grounding bushings on terminations at equipment.
Warning Tape: Bury warning tape approximately 12 inches (300 mm) above all
concrete-encased ducts and duct banks. Align tape parallel to and within 3 inches (75
mm) of the centerline of duct bank. Provide an additional warning tape for each 12-inch
(300-mm) increment of duct-bank width over a nominal 18 inches (450 mm). Space
additional tapes 12 inches (300 mm) apart, horizontally.
INSTALLATION OF CONCRETE MANHOLES, HANDHOLES, AND BOXES
A.
Cast-in-Place Manhole Installation:
1.
2.
3.
B.
Finish interior surfaces with a smooth-troweled finish.
Windows for Future Duct Connections: Form and pour concrete knockout panels 1-1/2
to 2 inches (38 to 50 mm) thick, arranged as indicated.
Cast-in-place concrete, formwork, and reinforcement are specified in Section 033000
"Cast-in-Place Concrete."
Precast Concrete Handhole and Manhole Installation:
1.
2.
Comply with ASTM C 891, unless otherwise indicated.
Install units level and plumb and with orientation and depth coordinated with connecting
ducts to minimize bends and deflections required for proper entrances.
UNDERGROUND DUCTS & RACEWAYS FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260543 - 7
3.
C.
Unless otherwise indicated, support units on a level bed of crushed stone or gravel,
graded from 1-inch (25-mm) sieve to No. 4 (4.75-mm) sieve and compacted to same
density as adjacent undisturbed earth.
Elevations:
1.
2.
3.
4.
Manhole Roof: Install with rooftop at least 15 inches (380 mm) below finished grade.
Manhole Frame: In paved areas and trafficways, set frames flush with finished grade.
Set other manhole frames 1 inch (25 mm) above finished grade.
Handhole Covers: In paved areas and trafficways, set surface flush with finished grade.
Set covers of other handholes 1 inch (25 mm) above finished grade.
Where indicated, cast handhole cover frame integrally with handhole structure.
D.
Manhole Access: Circular opening in manhole roof; sized to match cover size.
1.
Install chimney, constructed of precast concrete collars and rings to support frame and
cover and to connect cover with manhole roof opening. Provide moisture-tight masonry
joints and waterproof grouting for cast-iron frame to chimney.
E.
Hardware: Install removable hardware, including pulling eyes, cable stanchions, and cable
arms, and insulators, as required for installation and support of cables and conductors and as
indicated.
F.
Warning Sign: Install "Confined Space Hazard" warning sign on the inside surface of each
manhole cover.
3.6
INSTALLATION OF HANDHOLES AND BOXES OTHER THAN PRECAST CONCRETE
A.
Install handholes and boxes level and plumb and with orientation and depth coordinated with
connecting ducts to minimize bends and deflections required for proper entrances. Use box
extension if required to match depths of ducts, and seal joint between box and extension as
recommended by the manufacturer.
B.
Unless otherwise indicated, support units on a level bed of crushed stone or gravel, graded from
1/2-inch (12.7-mm) sieve to No. 4 (4.75-mm) sieve and compacted to same density as adjacent
undisturbed earth.
C.
Elevation: In paved areas and trafficways, set so cover surface will be flush with finished
grade. Set covers of other handholes 1 inch (25 mm) above finished grade.
3.7
GROUNDING
A.
3.8
Ground underground ducts and utility structures according to Section 260526 "Grounding and
Bonding for Electrical Systems."
FIELD QUALITY CONTROL
A.
Perform the following tests and inspections and prepare test reports:
UNDERGROUND DUCTS & RACEWAYS FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260543 - 8
1.
2.
3.
B.
3.9
Demonstrate capability and compliance with requirements on completion of installation
of underground ducts and utility structures.
Pull aluminum or wood test mandrel through duct to prove joint integrity and test for outof-round duct. Provide mandrel equal to 80 percent fill of duct. If obstructions are
indicated, remove obstructions and retest.
Test manhole and handhole grounding to ensure electrical continuity of grounding and
bonding connections.
Measure and report ground resistance as specified in
Section 260526 "Grounding and Bonding for Electrical Systems."
Correct deficiencies and retest as specified above to demonstrate compliance.
CLEANING
A.
Pull leather-washer-type duct cleaner, with graduated washer sizes, through full length of ducts.
Follow with rubber duct swab for final cleaning and to assist in spreading lubricant throughout
ducts.
B.
Clean internal surfaces of manholes, including sump. Remove foreign material.
END OF SECTION 260543
UNDERGROUND DUCTS & RACEWAYS FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260543 - 9
SECTION 260544 - SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND
CABLING
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract Documents apply to this Section.
SUMMARY
A.
Section Includes:
1.
2.
3.
4.
5.
1.3
Sleeves for raceway and cable penetration of non-fire-rated construction walls and floors.
Sleeve-seal systems.
Sleeve-seal fittings.
Grout.
Silicone sealants.
ACTION SUBMITTALS
A.
Product Data: For each type of product.
PART 2 - PRODUCTS
2.1
SLEEVES
A.
Wall Sleeves:
1.
Cast-Iron Pipe Sleeves: Cast or fabricated "wall pipe," equivalent to ductile-iron pressure
pipe, with plain ends and integral waterstop unless otherwise indicated.
B.
Sleeves for Conduits Penetrating Non-Fire-Rated Gypsum Board Assemblies: Galvanized-steel
sheet; 0.0239-inch (0.6-mm) minimum thickness; round tube closed with welded longitudinal
joint, with tabs for screw-fastening the sleeve to the board.
C.
Sleeves for Rectangular Openings:
1.
2.
Material: Galvanized sheet steel.
Minimum Metal Thickness:
a.
For sleeve cross-section rectangle perimeter less than 50 inches (1270 mm) and
with no side larger than 16 inches (400 mm), thickness shall be 0.052 inch (1.3
mm).
SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND
CABLING
SunGuide Transportation Management Center Control Retrofit
90% Submittal
260544 - 1
b.
2.2
For sleeve cross-section rectangle perimeter 50 inches (1270 mm) or more and one
or more sides larger than 16 inches (400 mm), thickness shall be 0.138 inch (3.5
mm).
SLEEVE-SEAL SYSTEMS
A.
Description: Modular sealing device, designed for field assembly, to fill annular space between
sleeve and raceway or cable.
1.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following (or approved equivalent determined by Department Project Manager):
a.
b.
c.
d.
e.
2.
3.
4.
2.3
Advance Products & Systems, Inc.
CALPICO, Inc.
Metraflex Company (The).
Pipeline Seal and Insulator, Inc.
Proco Products, Inc.
Sealing Elements: Nitrile (Buna N) rubber interlocking links shaped to fit surface of
pipe. Include type and number required for pipe material and size of pipe.
Pressure Plates: Carbon steel .
Connecting Bolts and Nuts: Carbon steel, with corrosion-resistant coating, of length
required to secure pressure plates to sealing elements.
SLEEVE-SEAL FITTINGS
A.
Description: Manufactured plastic, sleeve-type, waterstop assembly made for embedding in
concrete slab or wall. Unit shall have plastic or rubber waterstop collar with center opening to
match piping OD.
1.
Manufacturers: Subject to compliance with requirements, provide products by the
following (or approved equivalent determined by Department Project Manager):
a.
2.4
Presealed Systems.
GROUT
A.
Description: Nonshrink; recommended for interior and exterior sealing openings in non-firerated walls or floors.
B.
Standard: ASTM C 1107/C 1107M, Grade B, post-hardening and volume-adjusting, dry,
hydraulic-cement grout.
C.
Design Mix: 5000-psi (34.5-MPa), 28-day compressive strength.
D.
Packaging: Premixed and factory packaged.
SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND
CABLING
SunGuide Transportation Management Center Control Retrofit
90% Submittal
260544 - 2
PART 3 - EXECUTION
3.1
SLEEVE INSTALLATION FOR NON-FIRE-RATED ELECTRICAL PENETRATIONS
A.
Comply with NECA 1.
B.
Comply with NEMA VE 2 for cable tray and cable penetrations.
C.
Sleeves for Conduits Penetrating Above-Grade Non-Fire-Rated Concrete and Masonry-Unit
Floors and Walls:
1.
Interior Penetrations of Non-Fire-Rated Walls and Floors:
a.
b.
2.
3.
4.
D.
Seal annular space between sleeve and raceway or cable, using joint sealant
appropriate for size, depth, and location of joint. Comply with requirements in
Section 079200 "Joint Sealants."
Seal space outside of sleeves with mortar or grout. Pack sealing material solidly
between sleeve and wall so no voids remain. Tool exposed surfaces smooth;
protect material while curing.
Use pipe sleeves unless penetration arrangement requires rectangular sleeved opening.
Size pipe sleeves to provide 1/4-inch (6.4-mm) annular clear space between sleeve and
raceway or cable unless sleeve seal is to be installed.
Install sleeves for wall penetrations unless core-drilled holes or formed openings are
used. Install sleeves during erection of walls. Cut sleeves to length for mounting flush
with both surfaces of walls. Deburr after cutting.
Sleeves for Conduits Penetrating Non-Fire-Rated Gypsum Board Assemblies:
1.
2.
Use circular metal sleeves unless penetration arrangement requires rectangular sleeved
opening.
Seal space outside of sleeves with approved joint compound for gypsum board
assemblies.
E.
Roof-Penetration Sleeves: Seal penetration of individual raceways and cables with flexible
boot-type flashing units applied in coordination with roofing work.
F.
Aboveground, Exterior-Wall Penetrations: Seal penetrations using cast-iron pipe sleeves and
mechanical sleeve seals. Select sleeve size to allow for 1-inch (25-mm) annular clear space
between pipe and sleeve for installing mechanical sleeve seals.
G.
Underground, Exterior-Wall and Floor Penetrations: Install cast-iron pipe sleeves. Size sleeves
to allow for 1-inch (25-mm) annular clear space between raceway or cable and sleeve for
installing sleeve-seal system.
SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND
CABLING
SunGuide Transportation Management Center Control Retrofit
90% Submittal
260544 - 3
3.2
SLEEVE-SEAL-SYSTEM INSTALLATION
A.
Install sleeve-seal systems in sleeves in exterior concrete walls and slabs-on-grade at raceway
entries into building.
B.
Install type and number of sealing elements recommended by manufacturer for raceway or
cable material and size. Position raceway or cable in center of sleeve. Assemble mechanical
sleeve seals and install in annular space between raceway or cable and sleeve. Tighten bolts
against pressure plates that cause sealing elements to expand and make watertight seal.
3.3
SLEEVE-SEAL-FITTING INSTALLATION
A.
Install sleeve-seal fittings in new walls and slabs as they are constructed.
B.
Assemble fitting components of length to be flush with both surfaces of concrete slabs and
walls. Position waterstop flange to be centered in concrete slab or wall.
C.
Secure nailing flanges to concrete forms.
D.
Using grout, seal the space around outside of sleeve-seal fittings.
END OF SECTION 260544
SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND
CABLING
SunGuide Transportation Management Center Control Retrofit
90% Submittal
260544 - 4
SECTION 260553 - IDENTIFICATION FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract Documents apply to this Section.
SUMMARY
A.
Section Includes:
1.
2.
3.
4.
5.
6.
7.
8.
1.3
Identification for raceways.
Identification of power and control cables.
Identification for conductors.
Underground-line warning tape.
Warning labels and signs.
Instruction signs.
Equipment identification labels.
Miscellaneous identification products.
ACTION SUBMITTALS
A.
1.4
Product Data: For each electrical identification product indicated.
QUALITY ASSURANCE
A.
Comply with ANSI A13.1.
B.
Comply with NFPA 70.
C.
Comply with 29 CFR 1910.144 and 29 CFR 1910.145.
D.
Comply with ANSI Z535.4 for safety signs and labels.
E.
Adhesive-attached labeling materials, including label stocks, laminating adhesives, and inks
used by label printers, shall comply with UL 969.
1.5
COORDINATION
A.
Coordinate identification names, abbreviations, colors, and other features with requirements in
other Sections requiring identification applications, Drawings, Shop Drawings, manufacturer's
wiring diagrams, and the Operation and Maintenance Manual; and with those required by codes,
standards, and 29 CFR 1910.145. Use consistent designations throughout Project.
IDENTIFICATION FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260553 - 1
B.
Coordinate installation of identifying devices with completion of covering and painting of
surfaces where devices are to be applied.
C.
Coordinate installation of identifying devices with location of access panels and doors.
D.
Install identifying devices before installing acoustical ceilings and similar concealment.
PART 2 - PRODUCTS
2.1
POWER AND CONTROL RACEWAY IDENTIFICATION MATERIALS
A.
Comply with ANSI A13.1 for minimum size of letters for legend and for minimum length of
color field for each raceway size.
B.
Colors for Raceways Carrying Circuits at 600 V or Less:
1.
2.
Black letters on an orange field .
Legend: Indicate voltage and system or service type.
C.
Vinyl Labels for Raceways Carrying Circuits at 600 V or Less: Preprinted, flexible label
laminated with a clear, weather- and chemical-resistant coating and matching wraparound clear
adhesive tape for securing ends of legend label.
D.
Metal Tags: Brass or aluminum, 2 by 2 by 0.05 inch (50 by 50 by 1.3 mm), with stamped
legend, punched for use with self-locking cable tie fastener.
2.2
ARMORED AND METAL-CLAD CABLE IDENTIFICATION MATERIALS
A.
Comply with ANSI A13.1 for minimum size of letters for legend and for minimum length of
color field for each cable size.
B.
Colors for Cables Carrying Circuits at 600 V and Less:
1.
2.
C.
2.3
Black letters on an orange field .
Legend: Indicate voltage and system or service type.
Vinyl Labels: Preprinted, flexible label laminated with a clear, weather- and chemical-resistant
coating and matching wraparound clear adhesive tape for securing ends of legend label.
POWER AND CONTROL CABLE IDENTIFICATION MATERIALS
A.
Comply with ANSI A13.1 for minimum size of letters for legend and for minimum length of
color field for each cable size.
B.
Vinyl Labels: Preprinted, flexible label laminated with a clear, weather- and chemical-resistant
coating and matching wraparound clear adhesive tape for securing ends of legend label.
IDENTIFICATION FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260553 - 2
C.
2.4
Metal Tags: Brass or aluminum, 2 by 2 by 0.05 inch (50 by 50 by 1.3 mm), with stamped
legend, punched for use with self-locking cable tie fastener.
CONDUCTOR IDENTIFICATION MATERIALS
A.
Color-Coding Conductor Tape: Colored, self-adhesive vinyl tape not less than 3 mils (0.08
mm) thick by 1 to 2 inches (25 to 50 mm) wide.
B.
Self-Adhesive, Self-Laminating Polyester Labels: Preprinted , 3-mil- (0.08-mm-) thick flexible
label with acrylic pressure-sensitive adhesive that provides a clear, weather- and chemicalresistant, self-laminating, protective shield over the legend. Labels sized to fit the conductor
diameter such that the clear shield overlaps the entire printed legend.
2.5
FLOOR MARKING TAPE
A.
2.6
2-inch- (50-mm-) wide, 5-mil (0.125-mm) pressure-sensitive vinyl tape, with yellow and black
stripes and clear vinyl overlay.
UNDERGROUND-LINE WARNING TAPE
A.
Tape:
1.
2.
3.
B.
Color and Printing:
1.
2.
3.
2.7
Recommended by manufacturer for the method of installation and suitable to identify and
locate underground electrical and communications utility lines.
Printing on tape shall be permanent and shall not be damaged by burial operations.
Tape material and ink shall be chemically inert, and not subject to degrading when
exposed to acids, alkalis, and other destructive substances commonly found in soils.
Comply with ANSI Z535.1 through ANSI Z535.5.
Inscriptions for Red-Colored Tapes: ELECTRIC LINE, HIGH VOLTAGE, .
Inscriptions for Orange-Colored Tapes: TELEPHONE CABLE, CATV CABLE,
COMMUNICATIONS CABLE, OPTICAL FIBER CABLE, .
WARNING LABELS AND SIGNS
A.
Comply with NFPA 70 and 29 CFR 1910.145.
B.
Baked-Enamel Warning Signs:
1.
2.
3.
C.
Preprinted aluminum signs, punched or drilled for fasteners, with colors, legend, and size
required for application.
1/4-inch (6.4-mm) grommets in corners for mounting.
Nominal size, 7 by 10 inches (180 by 250 mm).
Warning label and sign shall include, but are not limited to, the following legends:
IDENTIFICATION FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260553 - 3
1.
1.
2.
2.8
Multiple Power Source Warning: "DANGER - ELECTRICAL SHOCK HAZARD EQUIPMENT HAS MULTIPLE POWER SOURCES." To be installed in all Automatic
Transfer Switches.
Workspace Clearance Warning: "WARNING - OSHA REGULATION - AREA IN
FRONT OF ELECTRICAL EQUIPMENT MUST BE KEPT CLEAR FOR 48 INCHES
(1220 MM)." To be installed in all electrical equipment, such as switchboards,
panelboards, industrial control panels, meter socket enclosures, and motor control
centers.
Arc Flash Hazard Warning: "WARNING - ARC FLASH HAZARD – APPROPRIATE
PPE REQUIRED – FAILURE TO COMPLY CAN RESULT IN DEATH OR INJURY –
REFER TO NFPA 70E. To be installed in all electrical equipment, such as switchboards,
panelboards, industrial control panels, meter socket enclosures, and motor control
centers.
INSTRUCTION SIGNS
A.
Engraved, laminated acrylic or melamine plastic, minimum 1/16 inch (1.6 mm) thick for signs
up to 20 sq. inches (129 sq. cm) and 1/8 inch (3.2 mm) thick for larger sizes.
1.
2.
3.
2.9
Engraved legend with black letters on white face .
Punched or drilled for mechanical fasteners.
Framed with mitered acrylic molding and arranged for attachment at applicable
equipment.
EQUIPMENT IDENTIFICATION LABELS
A.
2.10
A.
Engraved, Laminated Acrylic or Melamine Label: Punched or drilled for screw mounting.
White letters on a dark-gray background. Minimum letter height shall be 3/8 inch (10 mm).
CABLE TIES
General-Purpose Cable Ties: Fungus inert, self extinguishing, one piece, self locking, Type 6/6
nylon.
1.
2.
3.
4.
B.
Minimum Width: 3/16 inch (5 mm).
Tensile Strength at 73 deg F (23 deg C), According to ASTM D 638: 12,000 psi (82.7
MPa).
Temperature Range: Minus 40 to plus 185 deg F (Minus 40 to plus 85 deg C).
Color: Black except where used for color-coding.
UV-Stabilized Cable Ties: Fungus inert, designed for continuous exposure to exterior sunlight,
self extinguishing, one piece, self locking, Type 6/6 nylon.
1.
2.
3.
Minimum Width: 3/16 inch (5 mm).
Tensile Strength at 73 deg F (23 deg C), According to ASTM D 638: 12,000 psi (82.7
MPa).
Temperature Range: Minus 40 to plus 185 deg F (Minus 40 to plus 85 deg C).
IDENTIFICATION FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260553 - 4
4.
C.
Plenum-Rated Cable Ties: Self extinguishing, UV stabilized, one piece, self locking.
1.
2.
3.
4.
5.
2.11
Color: Black.
Minimum Width: 3/16 inch (5 mm).
Tensile Strength at 73 deg F (23 deg C), According to ASTM D 638: 7000 psi (48.2
MPa).
UL 94 Flame Rating: 94V-0.
Temperature Range: Minus 50 to plus 284 deg F (Minus 46 to plus 140 deg C).
Color: Black.
MISCELLANEOUS IDENTIFICATION PRODUCTS
A.
Paint: Comply with requirements in painting Sections for paint materials and application
requirements. Select paint system applicable for surface material and location (exterior or
interior).
B.
Fasteners for Labels and Signs: Self-tapping, stainless-steel screws or stainless-steel machine
screws with nuts and flat and lock washers.
PART 3 - EXECUTION
3.1
INSTALLATION
A.
Verify identity of each item before installing identification products.
B.
Location: Install identification materials and devices at locations for most convenient viewing
without interference with operation and maintenance of equipment.
C.
Apply identification devices to surfaces that require finish after completing finish work.
D.
Attach signs and plastic labels that are not self-adhesive type with mechanical fasteners
appropriate to the location and substrate.
E.
Aluminum Wraparound Marker Labels and Metal Tags: Secure tight to surface of conductor or
cable at a location with high visibility and accessibility.
F.
Cable Ties: For attaching tags. Use general-purpose type, except as listed below:
1.
2.
G.
Outdoors: UV-stabilized nylon.
In Spaces Handling Environmental Air: Plenum rated.
Underground-Line Warning Tape:
During backfilling of trenches install continuous
underground-line warning tape directly above line at 6 to 8 inches (150 to 200 mm) below
finished grade. Use multiple tapes where width of multiple lines installed in a common trench
or concrete envelope exceeds 16 inches (400 mm) overall.
IDENTIFICATION FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260553 - 5
H.
3.2
Painted Identification: Comply with requirements in painting Sections for surface preparation
and paint application.
IDENTIFICATION SCHEDULE
A.
Accessible Raceways and Metal-Clad Cables, 600 V or Less, for Service, Feeder, and Branch
Circuits More Than 30 A, and 120 V to ground: Identify with self-adhesive vinyl label .
Install labels at 30-foot (10-m) maximum intervals.
B.
Accessible Raceways and Cables within Buildings: Identify the covers of each junction and
pull box of the following systems with self-adhesive vinyl labels with the wiring system legend
and system voltage. System legends shall be as follows:
1.
2.
3.
C.
Emergency Power.
Power.
UPS.
Power-Circuit Conductor Identification, 600 V or Less: For conductors in vaults, pull and
junction boxes, manholes, and handholes, use color-coding conductor tape to identify the phase.
1.
Color-Coding for Phase and Voltage Level Identification, 600 V or Less: Use colors
listed in drawings for service feeder and branch-circuit conductors.
D.
Control-Circuit Conductor Identification: For conductors and cables in pull and junction boxes,
manholes, and handholes, use
self-adhesive vinyl labels with the conductor or cable
designation, origin, and destination.
E.
Control-Circuit Conductor Termination Identification: For identification at terminations
provide heat-shrink preprinted tubes with the conductor designation.
F.
Conductors to Be Extended in the Future: Attach write-on tags to conductors and list source.
G.
Auxiliary Electrical Systems Conductor Identification: Identify field-installed alarm, control,
and signal connections.
1.
2.
3.
H.
Identify conductors, cables, and terminals in enclosures and at junctions, terminals, and
pull points. Identify by system and circuit designation.
Use system of marker tape designations that is uniform and consistent with system used
by manufacturer for factory-installed connections.
Coordinate identification with Project Drawings, manufacturer's wiring diagrams, and the
Operation and Maintenance Manual.
Locations of Underground Lines: Identify with underground-line warning tape for power,
lighting, communication, and control wiring and optical fiber cable.
1.
2.
Limit use of underground-line warning tape to direct-buried cables.
Install underground-line warning tape for both direct-buried cables and cables in
raceway.
IDENTIFICATION FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260553 - 6
I.
Workspace Indication: Install floor marking tape to show working clearances in the direction of
access to live parts. Workspace shall be as required by NFPA 70 and 29 CFR 1926.403 unless
otherwise indicated. Do not install in electrical rooms.
J.
Warning Labels for Indoor Cabinets, Boxes, and Enclosures for Power and Lighting: Bakedenamel warning signs .
1.
2.
3.
4.
Comply with 29 CFR 1910.145.
Identify system voltage with black letters on an orange background.
Apply to exterior of door, cover, or other access.
For equipment with multiple power or control sources, apply to door or cover of
equipment including, but not limited to, the following:
a.
b.
Power transfer switches.
Controls with external control power connections.
K.
Operating Instruction Signs: Install instruction signs to facilitate proper operation and
maintenance of electrical systems and items to which they connect. Install instruction signs
with approved legend where instructions are needed for system or equipment operation.
L.
Emergency Operating Instruction Signs: Install instruction signs with white legend on a red
background with minimum 3/8-inch- (10-mm-) high letters for emergency instructions at
equipment used for power transfer .
M.
Equipment Identification Labels: On each unit of equipment, install unique designation label
that is consistent with wiring diagrams, schedules, and the Operation and Maintenance Manual.
Apply labels to disconnect switches and protection equipment, central or master units, control
panels, control stations, terminal cabinets, and racks of each system. Systems include power,
lighting, control, communication, signal, monitoring, and alarm systems unless equipment is
provided with its own identification.
1.
Labeling Instructions:
a.
b.
c.
d.
2.
Indoor Equipment:
Engraved, laminated acrylic or melamine label. Unless
otherwise indicated, provide a single line of text with 1/2-inch- (13-mm-) high
letters on 1-1/2-inch- (38-mm-) high label; where two lines of text are required, use
labels 2 inches (50 mm) high.
Outdoor Equipment: Engraved, laminated acrylic or melamine label .
Elevated Components: Increase sizes of labels and letters to those appropriate for
viewing from the floor.
Unless provided with self-adhesive means of attachment, fasten labels with
appropriate mechanical fasteners that do not change the NEMA or NRTL rating of
the enclosure.
Equipment to Be Labeled:
a.
b.
Panelboards: Typewritten directory of circuits in the location provided by
panelboard manufacturer. Panelboard identification shall be engraved, laminated
acrylic or melamine label.
Enclosures and electrical cabinets.
IDENTIFICATION FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260553 - 7
c.
d.
e.
f.
g.
h.
i.
j.
k.
l.
m.
n.
o.
p.
q.
r.
s.
t.
u.
v.
Access doors and panels for concealed electrical items.
Switchgear.
Switchboards.
Transformers: Label that includes tag designation shown on Drawings for the
transformer, feeder, and panelboards or equipment supplied by the secondary.
Substations.
Emergency system boxes and enclosures.
Motor-control centers.
Enclosed switches.
Enclosed circuit breakers.
Enclosed controllers.
Variable-speed controllers.
Push-button stations.
Power transfer equipment.
Contactors.
Remote-controlled switches, dimmer modules, and control devices.
Battery-inverter units.
Battery racks.
Power-generating units.
Monitoring and control equipment.
UPS equipment.
END OF SECTION 260553
IDENTIFICATION FOR ELECTRICAL SYSTEMS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260553 - 8
SECTION 260943.16 - ADDRESSABLE-FIXTURE LIGHTING CONTROLS
PART 1 - GENERAL
1.1
SUMMARY
A.
1.2
Section includes addressable-fixture lighting controls based on NLIGHT digital controls.
ACTION SUBMITTALS
A.
Product Data: For each type of product.
B.
Shop Drawings:
1.
2.
1.3
Address Drawing: Reflected ceiling plan and floor plans, showing data-bus-connected
devices, address for each device, and device groups. The plans shall be based on
construction plans, using the same legend, symbols, and schedules.
Wire Termination Diagrams and Schedules: Coordinate nomenclature and presentation
with Drawings and block diagram. Differentiate between manufacturer-installed and
field-installed wiring.
INFORMATIONAL SUBMITTALS
A.
Coordination Drawings: Submit evidence that lighting controls are compatible with connected
monitoring and control devices and systems specified.
1.
Show interconnecting signal and control wiring, and interface devices that prove
compatibility of inputs and outputs.
B.
Field quality-control reports.
C.
Sample Warranty: For manufacturer's special warranty.
1.4
CLOSEOUT SUBMITTALS
A.
1.5
Operation and maintenance data.
WARRANTY
A.
Manufacturer's Warranty: Manufacturer agrees to repair or replace components of lighting
controls that fail in materials or workmanship within specified warranty period.
1.
Failures include, but are not limited to, the following:
ADDRESSABLE-FIXTURE LIGHTING CONTROLS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260943.16 - 1
a.
b.
c.
d.
2.
Software: Failure of input and output to execute switching or dimming commands.
Failure of modular relays to operate under manual or software commands.
Power drive failure.
Damage of electronic components due to transient voltage surges.
Warranty Periods:
a.
b.
For LED Power Drives: Three years from date of Substantial Completion.
For Control Components That Are Not Part of LED Power Drives: Three years
from date of Substantial Completion.
PART 2 - PRODUCTS
2.1
SYSTEM DESCRIPTION
A.
Operation: Input signal from digital signal sources dims LED power driver devices associated
with lighting fixtures, or switches field-deployed, control relays.
1.
2.
3.
4.
Each device and relay is connected to a digital data bus.
Each LED power driver device and relay has a digital address and can be operated by a
digital signal.
Each device or relay can be assigned to any or all of 16 available groups connected to a
single data bus.
Each dimming power driver may have as many as 16 preset lighting levels or scenes.
Scenes can be programmed to lighting fixtures and may be applied to groups.
B.
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
by a qualified testing agency, and marked for intended location and application.
C.
Comply with 47 CFR, Subparts A and B, for Class A digital devices.
D.
Comply with protocol described in IEC 60929, Annexes E and G, for power drive lighting
control devices, wiring, and computer hardware and software.
E.
Comply with UL 916.
2.2
PERFORMANCE REQUIREMENTS
A.
Surge Suppression: Factory installed as an integral part of control components or field-mounted
surge suppressors complying with UL 1449, SPD Type 2.
B.
LED Power Drive Requirements:
1.
Components: Individually addressable devices (such as power drives, relays, dimmers,
and switches) that are operated from digital signals received through a NLIGHTcompliant bus, from data-entry and -retrieval devices (such as PCs, personal digital
assistants, hand-held infrared programming devices, wired Ethernet hubs, wireless
ADDRESSABLE-FIXTURE LIGHTING CONTROLS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260943.16 - 2
IEEE 802.11 hubs. Devices also report status to data-entry and -retrieval devices though
the bus.
2.3
BUS POWER SUPPLY
A.
Basis-of-Design Product: Subject to compliance with requirements, provide product indicated
on Drawings.
B.
Description: Supply power to data bus for 64 addressable devices, suitable for use with
NFPA 70, Class 2 control circuit.
1.
2.
3.
2.4
Primary Power: Field selectable, 120 and 277 V.
Power Supply: Regulated to maintain the operating voltage above 15-V dc under full
load, and rated for full charging load of 250 mA and a minimum maintained connected
load of 190 mA.
Pilot Lights: Indicate data bus ground fault and data bus traffic.
LED LIGHTING FIXTURE SWITCHING AND DIMMING
A.
Basis-of-Design Product: Subject to compliance with requirements, provide product indicated
on Drawings or comparable product by one of the following (or approved equivalent
determined by Department Project Manager):
1.
2.
3.
Lutron Electronics Co., Inc.
Osram Sylvania.
Philips Lighting Electronics.
B.
Each driver or group shall be addressable and shall include on-off, fade, dimming, scene
settings, and other standard DALI control functions and as required to meet the sequence of
operation.
C.
Driver: Comply with requirements in Section 265100 "Interior Lighting" for ballasts for linear
LED lamps, electronic programmed-start, and the following:
1.
2.
3.
4.
2.5
Starting Method: Programmed rapid start with antiflash (turns on at previously set light
level).
Dimming Range: 100 to 10 percent of rated lumens unless otherwise indicated.
Driver Factor: 1.0 at full output; 0.01 at full dim.
Input Voltage Range: 108 to 305 V.
RELAYS
A.
Relays: Electrically operated, mechanically held single-pole switch, rated at 20 A at 277 V.
Short-circuit current rating shall be not less than 5 kA. With pilot light indicating when relay is
closed and latched. Control shall be by digital data bus. Relay status shall be displayed when
queried by lighting management software.
ADDRESSABLE-FIXTURE LIGHTING CONTROLS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260943.16 - 3
B.
Individually Mounted Relays:
1.
2.
2.6
Enclosure: Standard outlet box or NEMA 250, Type 1, unless otherwise indicated.
Directory: Cover mounted, identifying each relay with its device address.
MANUAL SWITCHES AND PLATES
A.
Connection Type: RS-485 protocol, Category 5e UTP cable, using RJ-45 connectors. Power
shall be from the control unit.
B.
Push-Button Switches: Modular, operating over the digital data bus.
1.
Each switch shall control the following functions, in coordination with programmed
sequence of operation and related sensors:
a.
b.
c.
d.
e.
2.
3.
4.
On.
Off.
Dimming, increase light level.
Dimming, decrease light level.
Return to preset light level.
LED Pilot Lights: On to indicate that the control is active, or when the manual control is
operated.
Match color and style specified in Section 262726 "Wiring Devices."
Integral IR receiver for programming.
C.
Wall Plates: Single and multigang plates as specified in Section 262726 "Wiring Devices."
D.
Legend: Engraved or permanently silk-screened on wall plate where indicated.
designations indicated on Drawings.
2.7
Use
CONDUCTORS AND CABLES
A.
Power Wiring to Supply Side of Class 2 Power Source: Not smaller than No. 12 AWG,
complying with Section 260519 "Low-Voltage Electrical Power Conductors and Cables."
B.
Class 2 Control Cables: Multiconductor cable with copper conductors not smaller than No. 18
AWG, complying with Section 260519 "Low-Voltage Electrical Power Conductors and
Cables."
C.
Class 1 Control Cables: Multiconductor cable with copper conductors not smaller than No. 14
AWG, complying with Section 260519 "Low-Voltage Electrical Power Conductors and
Cables."
D.
Digital and Multiplexed Signal Cables: Unshielded, twisted-pair cable with copper conductors,
complying with TIA/EIA-568-B.2 Category 6 for horizontal copper cable.
ADDRESSABLE-FIXTURE LIGHTING CONTROLS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260943.16 - 4
PART 3 - EXECUTION
3.1
WIRING INSTALLATION
A.
Comply with NECA 1.
B.
Wiring Method: Install cables in raceways except within wall boxes, and except in accessible
ceiling spaces and in gypsum board partitions where unenclosed wiring method may be used.
1.
2.
3.2
Install plenum cable in environmental air spaces, including plenum ceilings.
Comply with requirements for raceways and boxes specified in Section 260533
"Raceways and Boxes for Electrical Systems."
IDENTIFICATION
A.
Identify system components, wiring, cabling, boxes, cabinets, and terminals. Comply with
identification requirements specified in Section 260553 "Identification for Electrical Systems."
B.
Identify field-installed conductors, interconnecting wiring, and components; install warning
signs complying with Section 260553 "Identification for Electrical Systems."
C.
Identify all ceiling-mounted controls with data bus number and device address.
D.
Label each device cable within 6 inches of connection to bus power supply or termination
block.
3.3
FIELD QUALITY CONTROL
A.
Acceptance Testing Preparation:
1.
B.
Field Test Reports:
1.
2.
C.
3.4
Test continuity of each circuit.
Printed list of all points created from actual queries of all addressed control points to
include power drives and manual controls.
Event log verifying the performance of all devices generating event messages to include
control buttons and any other change of value messages.
Lighting controls will be considered defective if they do not pass tests and inspections.
DEMONSTRATION
A.
Engage a factory-authorized service representative to train Owner's maintenance personnel to
adjust, operate, and maintain the control unit and operator interface.
ADDRESSABLE-FIXTURE LIGHTING CONTROLS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260943.16 - 5
END OF SECTION 260943.16
ADDRESSABLE-FIXTURE LIGHTING CONTROLS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
260943.16 - 6
SECTION 262200 - LOW-VOLTAGE TRANSFORMERS
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract Documents apply to this Section.
SUMMARY
A.
This Section includes the following types of dry-type transformers rated 600 V and less, with
capacities up to 1000 kVA:
1.
1.3
Distribution transformers.
ACTION SUBMITTALS
A.
Product Data: Include rated nameplate data, capacities, weights, dimensions, minimum
clearances, installed devices and features, and performance for each type and size of
transformer indicated.
B.
Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads, required
clearances, method of field assembly, components, and location and size of each field
connection.
1.
1.4
Wiring Diagrams: Power, signal, and control wiring.
INFORMATIONAL SUBMITTALS
A.
Source quality-control test reports.
B.
Field quality-control test reports.
1.5
CLOSEOUT SUBMITTALS
A.
1.6
Operation and Maintenance Data: For transformers to include in emergency, operation, and
maintenance manuals.
QUALITY ASSURANCE
A.
Source Limitations: Obtain transformers from single source from single manufacturer of
switchboards and panelboards for this project.
LOW-VOLTAGE TRANSFORMERS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262200 - 1
B.
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
C.
Comply with IEEE C57.12.91, "Test Code for Dry-Type Distribution and Power Transformers."
1.7
DELIVERY, STORAGE, AND HANDLING
A.
1.8
Temporary Heating: Apply temporary heat according to manufacturer's written instructions
within the enclosure of each ventilated-type unit, throughout periods during which equipment is
not energized and when transformer is not in a space that is continuously under normal control
of temperature and humidity.
COORDINATION
A.
Coordinate size and location of concrete bases with actual transformer provided. Cast anchorbolt inserts into bases. Concrete, reinforcement, and formwork requirements are specified with
concrete.
B.
Coordinate installation of wall-mounting and structure-hanging supports with actual transformer
provided.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
Basis-of-Design Product: Subject to compliance with requirements, provide product indicated
on drawings or comparable product by one of the following (Drawings indicate maximum
dimensions for transformers including clearances. Comply with indicated maximum
dimensions.) (or approved equivalent determined by Department Project Manager):
1.
2.
3.
4.
2.2
Eaton Electrical Inc.; Cutler-Hammer Business Unit.
General Electric Company; GE Consumer & Industrial - Electrical Distribution.
Siemens Energy & Automation, Inc.
Square D; a brand of Schneider Electric.
GENERAL TRANSFORMER REQUIREMENTS
A.
Description: Factory-assembled and -tested, air-cooled units for 60-Hz service.
B.
Cores: Grain-oriented, non-aging silicon steel.
C.
Coils: Continuous windings without splices except for taps.
1.
2.
Internal Coil Connections: Brazed or pressure type.
Coil Material: Aluminum .
LOW-VOLTAGE TRANSFORMERS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262200 - 2
2.3
DISTRIBUTION TRANSFORMERS
A.
Comply with NEMA ST 20, and list and label as complying with UL 1561.
B.
Cores: One leg per phase.
C.
Enclosure: Ventilated , NEMA 250, Type 2.
1.
D.
Enclosure: Ventilated , NEMA 250, Type 3R .
1.
E.
Core and coil shall be encapsulated within resin compound, sealing out moisture and air.
Core and coil shall be encapsulated within resin compound, sealing out moisture and air.
Transformer Enclosure Finish: Comply with NEMA 250.
1.
Finish Color: Gray .
F.
Taps for Transformers Smaller Than 3 kVA: None .
G.
Taps for Transformers 7.5 to 24 kVA: One 5 percent tap above and one 5 percent tap below
normal full capacity .
H.
Taps for Transformers 25 kVA and Larger: Two 2.5 percent taps above and two 2.5 percent
taps below normal full capacity .
I.
Insulation Class: 220 deg C, UL-component-recognized insulation system with a maximum of
150 deg C rise above 40 deg C ambient temperature.
J.
Energy Efficiency for Transformers Rated 15 kVA and Larger:
1.
2.
K.
K-Factor Rating: Transformers indicated to be K-factor rated shall comply with UL 1561
requirements for nonsinusoidal load current-handling capability to the degree defined by
designated K-factor.
1.
2.
L.
2.4
Complying with NEMA TP 1, Class 1 efficiency levels.
Tested according to NEMA TP 2.
Unit shall not overheat when carrying full-load current with harmonic distortion
corresponding to designated K-factor.
Indicate value of K-factor on transformer nameplate.
Wall Brackets: Manufacturer's standard brackets.
IDENTIFICATION DEVICES
A.
Nameplates: Engraved, laminated-plastic or metal nameplate for each transformer, mounted
with corrosion-resistant screws. Nameplates and label products are specified in Section 260553
"Identification for Electrical Systems."
LOW-VOLTAGE TRANSFORMERS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262200 - 3
2.5
SOURCE QUALITY CONTROL
A.
Test and inspect transformers according to IEEE C57.12.91.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine conditions for compliance with enclosure- and ambient-temperature requirements for
each transformer.
B.
Verify that field measurements are as needed to maintain working clearances required by
NFPA 70 and manufacturer's written instructions.
C.
Examine walls, floors, roofs, and concrete bases for suitable mounting conditions where
transformers will be installed.
D.
Verify that ground connections are in place and requirements in Section 260526 "Grounding
and Bonding for Electrical Systems" have been met. Maximum ground resistance shall be 5
ohms at location of transformer.
E.
Proceed with installation only after unsatisfactory conditions have been corrected.
3.2
INSTALLATION
A.
3.3
Construct concrete bases and anchor floor-mounting transformers according to manufacturer's
written instructions and requirements in Section 260529 "Hangers and Supports for Electrical
Systems."
CONNECTIONS
A.
Ground equipment according to Section 260526 "Grounding and Bonding for Electrical
Systems."
B.
Connect wiring according to Section 260519 "Low-Voltage Electrical Power Conductors and
Cables."
3.4
FIELD QUALITY CONTROL
A.
Perform tests and inspections and prepare test reports.
1.
B.
Manufacturer's Field Service: Engage a factory-authorized service representative to
inspect components, assemblies, and equipment installations, including connections, and
to assist in testing.
Tests and Inspections:
LOW-VOLTAGE TRANSFORMERS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262200 - 4
1.
Perform each visual and mechanical inspection and electrical test stated in NETA
Acceptance Testing Specification. Certify compliance with test parameters.
C.
Remove and replace units that do not pass tests or inspections and retest as specified above.
D.
Test Labeling: On completion of satisfactory testing of each unit, attach a dated and signed
"Satisfactory Test" label to tested component.
3.5
ADJUSTING
A.
Record transformer secondary voltage at each unit for at least 48 hours of typical occupancy
period. Adjust transformer taps to provide optimum voltage conditions at secondary terminals.
Optimum is defined as not exceeding nameplate voltage plus 10 percent and not being lower
than nameplate voltage minus 3 percent at maximum load conditions. Submit recording and tap
settings as test results.
B.
Output Settings Report: Prepare a written report recording output voltages and tap settings.
3.6
CLEANING
A.
Vacuum dirt and debris; do not use compressed air to assist in cleaning.
END OF SECTION 262200
LOW-VOLTAGE TRANSFORMERS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262200 - 5
SECTION 262416 - PANELBOARDS
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract Documents apply to this Section.
SUMMARY
A.
Section Includes:
1.
2.
1.3
Distribution panelboards.
Lighting and appliance branch-circuit panelboards.
DEFINITIONS
A.
SVR: Suppressed voltage rating.
B.
TVSS: Transient voltage surge suppressor.
1.4
ACTION SUBMITTALS
A.
Product Data: For each type of panelboard, switching and overcurrent protective device,
transient voltage suppression device, accessory, and component indicated. Include dimensions
and manufacturers' technical data on features, performance, electrical characteristics, ratings,
and finishes.
B.
Shop Drawings: For each panelboard and related equipment.
1.
2.
3.
4.
5.
6.
7.
8.
Include dimensioned plans, elevations, sections, and details. Show tabulations of
installed devices, equipment features, and ratings.
Detail enclosure types and details for types other than NEMA 250, Type 1.
Detail bus configuration, current, and voltage ratings.
Short-circuit current rating of panelboards and overcurrent protective devices.
Include evidence of NRTL listing for series rating of installed devices.
Detail features, characteristics, ratings, and factory settings of individual overcurrent
protective devices and auxiliary components.
Include wiring diagrams for power, signal, and control wiring.
Include time-current coordination curves for each type and rating of overcurrent
protective device included in panelboards. Submit on translucent log-log graft paper;
include selectable ranges for each type of overcurrent protective device.
PANELBOARDS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262416 - 1
1.5
INFORMATIONAL SUBMITTALS
A.
Field Quality-Control Reports:
1.
2.
3.
B.
1.6
Test procedures used.
Test results that comply with requirements.
Results of failed tests and corrective action taken to achieve test results that comply with
requirements.
Panelboard Schedules:
balancing.
For installation in panelboards.Submit final versions after load
CLOSEOUT SUBMITTALS
A.
Operation and Maintenance Data: For panelboards and components to include in emergency,
operation, and maintenance manuals. In addition to items specified in Section 017823
"Operation and Maintenance Data," include the following:
1.
2.
1.7
Manufacturer's written instructions for testing and adjusting overcurrent protective
devices.
Time-current curves, including selectable ranges for each type of overcurrent protective
device that allows adjustments.
QUALITY ASSURANCE
A.
Source Limitations: Obtain panelboards, overcurrent protective devices, components, and
accessories from single source from single manufacturer.
B.
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
by a qualified testing agency, and marked for intended location and application.
C.
Comply with NEMA PB 1.
D.
Comply with NFPA 70.
1.8
DELIVERY, STORAGE, AND HANDLING
A.
Remove loose packing and flammable materials from inside panelboards; install temporary
electric heating (250 W per panelboard) to prevent condensation.
B.
Handle and prepare panelboards for installation according to NEMA PB 1.
1.9
PROJECT CONDITIONS
A.
Environmental Limitations:
PANELBOARDS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262416 - 2
1.
2.
Do not deliver or install panelboards until spaces are enclosed and weathertight, wet work
in spaces is complete and dry, work above panelboards is complete, and temporary
HVAC system is operating and maintaining ambient temperature and humidity conditions
at occupancy levels during the remainder of the construction period.
Rate equipment for continuous operation under the following conditions unless otherwise
indicated:
a.
b.
1.10
A.
1.11
A.
Ambient Temperature: Not exceeding 23 deg F (minus 5 deg C) to plus 104 deg F
(plus 40 deg C).
Altitude: Not exceeding 6600 feet (2000 m).
COORDINATION
Coordinate layout and installation of panelboards and components with other construction that
penetrates walls or is supported by them, including electrical and other types of equipment,
raceways, piping, encumbrances to workspace clearance requirements, and adjacent surfaces.
Maintain required workspace clearances and required clearances for equipment access doors
and panels.
WARRANTY
Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or
replace transient voltage suppression devices that fail in materials or workmanship within
specified warranty period.
1.
Warranty Period: Five years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1
GENERAL REQUIREMENTS FOR PANELBOARDS
A.
Enclosures: Surface -mounted cabinets.
1.
Rated for environmental conditions at installed location.
2.
a.
Indoor Dry and Clean Locations: NEMA 250, Type 1 .
b.
Outdoor Locations: NEMA 250, Type 3R .
Hinged Front Cover: Entire front trim hinged to box and with standard door within
hinged trim cover.
Finishes:
3.
a.
b.
c.
Panels and Trim: Steel and galvanized steel, factory finished immediately after
cleaning and pretreating with manufacturer's standard two-coat, baked-on finish
consisting of prime coat and thermosetting topcoat.
Back Boxes: Galvanized steel .
Fungus Proofing: Permanent fungicidal treatment for overcurrent protective
devices and other components.
PANELBOARDS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262416 - 3
4.
Directory Card: Inside panelboard door, mounted in transparent card holder .
B.
Incoming Mains Location:
C.
Phase, Neutral, and Ground Buses:
1.
2.
3.
D.
Top and bottom.
Material: Hard-drawn copper, 98 percent conductivity.
Equipment Ground Bus: Adequate for feeder and branch-circuit equipment grounding
conductors; bonded to box.
Extra-Capacity Neutral Bus: Neutral bus rated 200 percent of phase bus and UL listed as
suitable for nonlinear loads where required in drawings.
Conductor Connectors: Suitable for use with conductor material and sizes.
1.
2.
3.
4.
5.
6.
Material: Hard-drawn copper, 98 percent conductivity.
Main and Neutral Lugs: Mechanical type.
Ground Lugs and Bus-Configured Terminators: Mechanical type.
Feed-Through Lugs: Compression type, suitable for use with conductor material.
Locate at opposite end of bus from incoming lugs or main device.
Subfeed (Double) Lugs: Compression type suitable for use with conductor material.
Locate at same end of bus as incoming lugs or main device.
Extra-Capacity Neutral Lugs: Rated 200 percent of phase lugs mounted on extracapacity neutral bus.
E.
Service Equipment Label: NRTL labeled for use as service equipment for panelboards or load
centers with one or more main service disconnecting and overcurrent protective devices.
F.
Future Devices: Mounting brackets, bus connections, filler plates, and necessary appurtenances
required for future installation of devices.
G.
Panelboard Short-Circuit Current Rating: Rated for series-connected system with integral or
remote upstream overcurrent protective devices and labeled by an NRTL. Include size and type
of allowable upstream and branch devices, listed and labeled for series-connected short-circuit
rating by an NRTL.
2.2
DISTRIBUTION PANELBOARDS
A.
Basis-of-Design Product: Subject to compliance with requirements, provide product indicated
on Drawings or comparable product by one of the following (Drawings indicate maximum
dimensions for panelboards including clearances between panelboards and adjacent surfaces
and other items. Comply with indicated maximum dimensions.) (or approved equivalent
determined by Department Project Manager):
1.
2.
3.
B.
Eaton Electrical Inc.; Cutler-Hammer Business Unit.
Siemens Energy & Automation, Inc.
Square D; a brand of Schneider Electric.
Panelboards: NEMA PB 1, with factory-installed, integral TVSS; labeled by an NRTL for
compliance with UL 67 after installing TVSS.Mains: Circuit breaker or Lugs only.
PANELBOARDS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262416 - 4
C.
Branch Overcurrent Protective Devices for Circuit-Breaker Frame Sizes 125 A and Smaller:
Bolt-on circuit breakers.
D.
Branch Overcurrent Protective Devices for Circuit-Breaker Frame Sizes Larger Than 125 A:
Bolt-on circuit breakers.
E.
Surge Protection Device: IEEE C62.41-compliant, integrally mounted, bolt-on, solid-state,
parallel-connected, modular (with field-replaceable modules) type, with sine-wave tracking
suppression and filtering modules, short-circuit current rating complying with UL 1449, second
edition, and matching or exceeding the panelboard short-circuit rating, redundant suppression
circuits, with individually fused metal-oxide varistors.
1.
Accessories:
a.
Redundant suppression circuits.
b.
Redundant replaceable modules.
c.
Arrangement with wire connections to phase buses, neutral bus, and ground bus.
d.
LED indicator lights for power and protection status.
e.
Audible alarm, with silencing switch, to indicate when protection has failed.
f.
Form-C contacts rated at 5 A and 250-V ac, one normally open and one normally
closed, for remote monitoring of system operation. Contacts shall reverse position
on failure of any surge diversion module or on opening of any current-limiting
device. Coordinate with building power monitoring and control system.
g.
Four -digit, transient-event counter set to totalize transient surges.
2.
3.
Peak Single-Impulse Surge Current Rating: 160 kA per mode/320 kA per phase .
Minimum single-impulse current ratings, using 8-by-20-mic.sec. waveform described in
IEEE C62.41.2.
a.
b.
c.
4.
5.
Withstand Capabilities: 12,000 IEEE C62.41, Category C3 (10 kA), 8-by-20-mic.sec.
surges with less than 5 percent change in clamping voltage.
Protection modes and UL 1449 SVR for grounded wye circuits with 480Y/277 or
208Y/120 -V, three-phase, four-wire circuits shall be as follows:
a.
b.
c.
6.
Line to Neutral: 800 V for 480Y/277 and 400 V for 208Y/120 .
Line to Ground: 800 V for 480Y/277 and 400 V for 208Y/120 .
Neutral to Ground: 800 V for 480Y/277 and 400 V for 208Y/120 .
Protection modes and UL 1449 SVR for 240/120-V, single-phase, three-wire circuits
shall be as follows:
a.
b.
c.
7.
Line to Neutral: 70,000 A.
Line to Ground: 70,000 A.
Neutral to Ground: 50,000 A.
Line to Neutral: 400 V.
Line to Ground: 400 V.
Neutral to Ground: 400 V.
Protection modes and UL 1449 SVR for 240/120-V, three-phase, four-wire circuits with
high leg shall be as follows:
PANELBOARDS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262416 - 5
a.
b.
c.
2.3
Line to Neutral: 400 V, 800 V from high leg.
Line to Ground: 400 V.
Neutral to Ground: 400 V.
LIGHTING AND APPLIANCE BRANCH-CIRCUIT PANELBOARDS
A.
Basis-of-Design Product: Subject to compliance with requirements, provide product indicated
on Drawings or comparable product by one of the following (Drawings indicate maximum
dimensions for panelboards including clearances between panelboards and adjacent surfaces
and other items. Comply with indicated maximum dimensions.) (or approved equivalent
determined by Department Project Manager):
1.
2.
3.
4.
Eaton Electrical Inc.; Cutler-Hammer Business Unit.
General Electric Company; GE Consumer & Industrial - Electrical Distribution.
Siemens Energy & Automation, Inc.
Square D; a brand of Schneider Electric.
B.
Panelboards: NEMA PB 1, with factory-installed, integral TVSS; labeled by an NRTL for
compliance with UL 67 after installing TVSS.
C.
Mains: As indicated on drawings.
D.
Branch Overcurrent Protective Devices:
disturbing adjacent units.
E.
Buses:
1.
F.
Bolt-on circuit breakers, replaceable without
Copper phase and neutral buses; 200 percent capacity neutral bus and lugs where
indicated on drawings.
Surge Protection Device: IEEE C62.41-compliant, integrally mounted, bolt-on, solid-state,
parallel-connected, modular (with field-replaceable modules) type, with sine-wave tracking
suppression and filtering modules, short-circuit current rating complying with UL 1449, second
edition, and matching or exceeding the panelboard short-circuit rating, redundant suppression
circuits, with individually fused metal-oxide varistors.
1.
Accessories:
a.
LED indicator lights for power and protection status.
b.
Audible alarm, with silencing switch, to indicate when protection has failed.
c.
Form-C contacts rated at 5 A and 250-V ac, one normally open and one normally
closed, for remote monitoring of system operation. Contacts shall reverse position
on failure of any surge diversion module or on opening of any current-limiting
device. Coordinate with building power monitoring and control system.
d.
Four -digit, transient-event counter set to totalize transient surges.
2.
Peak Single-Impulse Surge Current Rating: 160 kA per mode/320 kA per phase .
PANELBOARDS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262416 - 6
3.
Minimum single-impulse current ratings, using 8-by-20-mic.sec. waveform described in
IEEE C62.41.2.
a.
b.
c.
4.
5.
Withstand Capabilities: 12,000 IEEE C62.41, Category C3 (10 kA), 8-by-20-mic.sec.
surges with less than 5 percent change in clamping voltage.
Protection modes and UL 1449 SVR for grounded wye circuits with 480Y/277 or
208Y/120 -V, three-phase, four-wire circuits shall be as follows:
a.
b.
c.
6.
2.4
Line to Neutral: 400 V.
Line to Ground: 400 V.
Neutral to Ground: 400 V.
Protection modes and UL 1449 SVR for 240/120-V, three-phase, four-wire circuits with
high leg shall be as follows:
a.
b.
c.
G.
Line to Neutral: 800 V for 480Y/277 and 400 V for 208Y/120 .
Line to Ground: 800 V for 480Y/277 and 400 V for 208Y/120 .
Neutral to Ground: 800 V for 480Y/277 and 400 V for 208Y/120 .
Protection modes and UL 1449 SVR for 240/120-V, single-phase, three-wire circuits
shall be as follows:
a.
b.
c.
7.
Line to Neutral: 70,000 A.
Line to Ground: 70,000 A.
Neutral to Ground: 50,000 A.
Line to Neutral: 400 V, 800 V from high leg.
Line to Ground: 400 V.
Neutral to Ground: 400 V.
Doors: Concealed hinges; secured with flush latch with tumbler lock; keyed alike.
DISCONNECTING AND OVERCURRENT PROTECTIVE DEVICES
A.
Molded-Case Circuit Breaker (MCCB): Comply with UL 489, with series-connected rating to
meet available fault currents.
1.
2.
3.
Thermal-Magnetic Circuit Breakers: Inverse time-current element for low-level
overloads, and instantaneous magnetic trip element for short circuits. Adjustable
magnetic trip setting for circuit-breaker frame sizes 250 A and larger.
Adjustable Instantaneous-Trip Circuit Breakers: Magnetic trip element with frontmounted, field-adjustable trip setting.
Electronic trip circuit breakers with rms sensing; field-replaceable rating plug or fieldreplicable electronic trip; and the following field-adjustable settings:
a.
b.
Instantaneous trip.
Long- and short-time pickup levels.
PANELBOARDS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262416 - 7
c.
d.
4.
5.
6.
7.
Long- and short-time time adjustments.
Ground-fault pickup level, time delay, and I2t response.
Current-Limiting Circuit Breakers: Frame sizes 400 A and smaller; let-through ratings
less than NEMA FU 1, RK-5.
GFCI Circuit Breakers: Single- and two-pole configurations with Class A ground-fault
protection (6-mA trip).
Arc-Fault Circuit Interrupter (AFCI) Circuit Breakers: Comply with UL 1699; 120/240V, single-pole configuration.
Molded-Case Circuit-Breaker (MCCB) Features and Accessories:
a.
b.
c.
d.
e.
f.
g.
Standard frame sizes, trip ratings, and number of poles.
Lugs: Mechanical style, suitable for number, size, trip ratings, and conductor
materials.
Application Listing: Appropriate for application; Type SWD for switching
fluorescent lighting loads; Type HID for feeding fluorescent and high-intensity
discharge (HID) lighting circuits.
Ground-Fault Protection: Integrally mounted relay and trip unit with adjustable
pickup and time-delay settings, push-to-test feature, and ground-fault indicator.
Undervoltage Trip: Set to operate at 35 to 75 percent of rated voltage without
intentional time delay.
Auxiliary Contacts: One SPDT switch with "a" and "b" contacts; "a" contacts
mimic circuit-breaker contacts and "b" contacts operate in reverse of circuitbreaker contacts.
Handle Clamp: Loose attachment, for holding circuit-breaker handle in on
position.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Receive, inspect, handle, and store panelboards according to NEMA PB 1.1.
B.
Examine panelboards before installation. Reject panelboards that are damaged or rusted or have
been subjected to water saturation.
C.
Examine elements and surfaces to receive panelboards for compliance with installation
tolerances and other conditions affecting performance of the Work.
D.
Proceed with installation only after unsatisfactory conditions have been corrected.
3.2
INSTALLATION
A.
Install panelboards and accessories according to NEMA PB 1.1.
B.
Temporary Lifting Provisions: Remove temporary lifting eyes, channels, and brackets and
temporary blocking of moving parts from panelboards.
PANELBOARDS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262416 - 8
C.
Comply with mounting and anchoring requirements specified in Section 260548 "Vibration and
Seismic Controls for Electrical Systems."
D.
Mount top of trim 90 inches (2286 mm) above finished floor unless otherwise indicated. Mount
panelboard cabinet plumb and rigid without distortion of box. Mount recessed panelboards with
fronts uniformly flush with wall finish and mating with back box.
F.
Install overcurrent protective devices and controllers not already factory installed.
1.
Set field-adjustable, circuit-breaker trip ranges.
G.
Install filler plates in unused spaces.
H.
Comply with NECA 1.
3.3
IDENTIFICATION
A.
Identify field-installed conductors, interconnecting wiring, and components; provide warning
signs complying with Section 260553 "Identification for Electrical Systems."
B.
Create a directory to indicate installed circuit loads after balancing panelboard loads;
incorporate Owner's final room designations. Obtain approval before installing. Use a
computer or typewriter to create directory; handwritten directories are not acceptable.
C.
Panelboard Nameplates: Label each panelboard with a nameplate complying with requirements
for identification specified in Section 260553 "Identification for Electrical Systems."
3.4
FIELD QUALITY CONTROL
A.
Manufacturer's Field Service: Engage a factory-authorized service representative to inspect,
test, and adjust components, assemblies, and equipment installations, including connections.
B.
Perform tests and inspections.
1.
C.
Acceptance Testing Preparation:
1.
2.
D.
Manufacturer's Field Service: Engage a factory-authorized service representative to
inspect components, assemblies, and equipment installations, including connections, and
to assist in testing.
Test insulation resistance for each panelboard bus, component, connecting supply, feeder,
and control circuit.
Test continuity of each circuit.
Tests and Inspections:
1.
Perform each visual and mechanical inspection and electrical test stated in NETA
Acceptance Testing Specification. Certify compliance with test parameters.
PANELBOARDS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262416 - 9
2.
3.
Correct malfunctioning units on-site, where possible, and retest to demonstrate
compliance; otherwise, replace with new units and retest.
Perform the following infrared scan tests and inspections and prepare reports:
a.
b.
Initial Infrared Scanning: After Substantial Completion, but not more than 60 days
after Final Acceptance, perform an infrared scan of each panelboard. Remove
front panels so joints and connections are accessible to portable scanner.
Instruments and Equipment:
1)
Use an infrared scanning device designed to measure temperature or to
detect significant deviations from normal values. Provide calibration record
for device.
E.
Panelboards will be considered defective if they do not pass tests and inspections.
F.
Prepare test and inspection reports, including a certified report that identifies panelboards
included and that describes scanning results. Include notation of deficiencies detected, remedial
action taken, and observations after remedial action.
3.5
ADJUSTING
A.
Adjust moving parts and operable component to function smoothly, and lubricate as
recommended by manufacturer.
B.
Set field-adjustable circuit-breaker trip ranges as specified in Section 260573 "Overcurrent
Protective Device Coordination Study."
3.6
PROTECTION
A.
Temporary Heating: Apply temporary heat to maintain temperature according to manufacturer's
written instructions.
END OF SECTION 262416
PANELBOARDS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262416 - 10
SECTION 262726 - WIRING DEVICES
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract Documents apply to this Section.
SUMMARY
A.
Section Includes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
1.3
Receptacles, receptacles with integral GFCI, and associated device plates.
Twist-locking receptacles.
Receptacles with integral surge-suppression units.
Weather-resistant receptacles.
Snap switches and wall-box dimmers.
Digital wall switch timer.
Wall-switch.
Communications outlets.
Floor service outlets, and multioutlet assemblies.
DEFINITIONS
A.
EMI: Electromagnetic interference.
B.
GFCI: Ground-fault circuit interrupter.
C.
Pigtail: Short lead used to connect a device to a branch-circuit conductor.
D.
RFI: Radio-frequency interference.
E.
TVSS: Transient voltage surge suppressor.
F.
UTP: Unshielded twisted pair.
1.4
ADMINISTRATIVE REQUIREMENTS
A.
Coordination:
1.
2.
Receptacles for Owner-Furnished Equipment: Match plug configurations.
Cord and Plug Sets: Match equipment requirements.
WIRING DEVICES
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262726 - 1
1.5
ACTION SUBMITTALS
A.
Product Data: For each type of product.
B.
Shop Drawings: List of legends and description of materials and process used for premarking
wall plates.
1.6
INFORMATIONAL SUBMITTALS
A.
1.7
Field quality-control reports.
CLOSEOUT SUBMITTALS
A.
Operation and Maintenance Data: For wiring devices to include in all manufacturers' packinglabel warnings and instruction manuals that include labeling conditions.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
Manufacturers' Names:
Shortened versions (shown in parentheses) of the following
manufacturers' names are used in other Part 2 articles (or approved equivalent determined by
Department Project Manager):
1.
2.
3.
4.
B.
2.2
Cooper Wiring Devices; Division of Cooper Industries, Inc. (Cooper).
Hubbell Incorporated; Wiring Device-Kellems (Hubbell).
Leviton Mfg. Company Inc. (Leviton).
Pass & Seymour/Legrand (Pass & Seymour).
Source Limitations: Obtain each type of wiring device and associated wall plate from single
source from single manufacturer.
GENERAL WIRING-DEVICE REQUIREMENTS
A.
Wiring Devices, Components, and Accessories: Listed and labeled as defined in NFPA 70, by a
qualified testing agency, and marked for intended location and application.
B.
Comply with NFPA 70.
2.3
STRAIGHT-BLADE RECEPTACLES
A.
Convenience Receptacles, 125 V, 20 A:
Comply with NEMA WD 1, NEMA WD 6
Configuration 5-20R, UL 498, and FS W-C-596.
WIRING DEVICES
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262726 - 2
1.
Products: Subject to compliance with requirements, (or approved equivalent determined
by Department Project Manager):
a.
b.
c.
d.
2.4
Cooper.
Hubbell.
Leviton.
Pass & Seymour.
GFCI RECEPTACLES
A.
General Description:
1.
2.
3.
B.
Straight blade, non-feed-through type.
Comply with NEMA WD 1, NEMA WD 6, UL 498, UL 943 Class A, and FS W-C-596.
Include indicator light that shows when the GFCI has malfunctioned and no longer
provides proper GFCI protection.
Duplex GFCI Convenience Receptacles, 125 V, 20 A:
1.
Products: Subject to compliance with requirements, provide one of the following (or
approved equivalent determined by Department Project Manager):
a.
b.
c.
d.
2.5
Cooper.
Hubbell.
Pass & Seymour.
Leviton.
HAZARDOUS (CLASSIFIED) LOCATION RECEPTACLES
A.
Wiring Devices for Hazardous (Classified) Locations:
UL 1010.
1.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following (or approved equivalent determined by Department Project Manager):
a.
b.
c.
d.
e.
2.6
Comply with NEMA FB 11 and
Cooper.
Hubbell.
Pass & Seymour.
Leviton
EGS/Appleton Electric.
TWIST-LOCKING RECEPTACLES
A.
Single Convenience Receptacles, 125 V, 20 A: Comply with NEMA WD 1, NEMA WD 6
Configuration L5-20R, and UL 498.
1.
Products: Subject to compliance with requirements, provide one of the following (or
approved equivalent determined by Department Project Manager):
WIRING DEVICES
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262726 - 3
a.
b.
c.
d.
2.7
Cooper.
Hubbell.
Leviton.
Pass & Seymour.
TOGGLE SWITCHES
A.
Comply with NEMA WD 1, UL 20, and FS W-S-896.
B.
Switches, 120/277 V, 20 A:
1.
Products: Subject to compliance with requirements, provide one of the following (or
approved equivalent determined by Department Project Manager):
1)
2)
3)
4)
2.8
Cooper.
Hubbell.
Leviton.
Pass & Seymour.
DIGITAL WALL SWITCH TIMER
A.
Comply with NEMA WD 1, and UL,
B.
Switches, 120/277 V, 20 A:
1.
Products: Subject to compliance with requirements, provide one of the following (or
approved equivalent determined by Department Project Manager):
1)
2)
3)
4)
C.
Cooper.
Hubbell.
Leviton.
Pass & Seymour.
General
1.
The Timer shall control lighting and motor loads, and be solid state with
electroluminescent backlit LCD.
2.
The Timer shall be an interval timer with intervals that can be preset using a series of dip
switches, with a tamper resistant manual scroll-up mode that can be used to temporarily
override the preset count-down time.
3.
The Timer shall be programmable to beep or to flicker the load (lights) as a warning time
minutes prior to the load being shut OFF.
4.
The Timer shall be compatible with electronic ballasts, incandescent lighting or motor
loads.
5.
The Timer shall have dual voltage input of 120/277VAC with no minimum load
requirement.
WIRING DEVICES
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262726 - 4
2.9
WALL PLATES
A.
Single and combination types shall match corresponding wiring devices.
1.
2.
3.
4.
B.
2.10
Plate-Securing Screws: Metal with head color to match plate finish.
Material for Finished Spaces: Smooth, high-impact thermoplastic .
Material for Unfinished Spaces: Smooth, high-impact thermoplastic.
Material for Damp Locations: Cast aluminum with spring-loaded lift cover, and listed
and labeled for use in wet and damp locations.
Wet-Location, Weatherproof Cover Plates: NEMA 250, complying with Type 3R, weatherresistant, die-cast aluminum with lockable cover.
FLOOR SERVICE FITTINGS
A.
Type: Modular, flush-type , dual-service units suitable for wiring method used.
B.
Compartments: Barrier separates power from voice and data communication cabling.
C.
Service Plate: Round, die-cast aluminum with satin finish.
D.
Power Receptacle: NEMA WD 6 Configuration 5-20R, gray finish, unless otherwise indicated.
E.
Voice and Data Communication Outlet: Two modular, keyed, color-coded, RJ-45 jacks for
UTP cable complying with Owner’s requirements .
2.11
A.
FINISHES
Device Color:
1.
2.
B.
Wiring Devices Connected to Normal Power System:
White
indicated or required by NFPA 70 or device listing.
Wiring Devices Connected to Emergency Power System: Red .
unless otherwise
Wall Plate Color: For plastic covers, match device color.
PART 3 - EXECUTION
3.1
INSTALLATION
A.
Comply with NECA 1, including mounting heights listed in that standard, unless otherwise
indicated.
B.
Coordination with Other Trades:
WIRING DEVICES
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262726 - 5
1.
2.
3.
4.
C.
Protect installed devices and their boxes. Do not place wall finish materials over device
boxes and do not cut holes for boxes with routers that are guided by riding against outside
of boxes.
Keep outlet boxes free of plaster, drywall joint compound, mortar, cement, concrete, dust,
paint, and other material that may contaminate the raceway system, conductors, and
cables.
Install device boxes in brick or block walls so that the cover plate does not cross a joint
unless the joint is troweled flush with the face of the wall.
Install wiring devices after all wall preparation, including painting, is complete.
Conductors:
1.
2.
3.
4.
Do not strip insulation from conductors until right before they are spliced or terminated
on devices.
Strip insulation evenly around the conductor using tools designed for the purpose. Avoid
scoring or nicking of solid wire or cutting strands from stranded wire.
The length of free conductors at outlets for devices shall meet provisions of NFPA 70,
Article 300, without pigtails.
Existing Conductors:
a.
b.
c.
D.
Device Installation:
1.
2.
3.
4.
5.
6.
7.
8.
9.
E.
Cut back and pigtail, or replace all damaged conductors.
Straighten conductors that remain and remove corrosion and foreign matter.
Pigtailing existing conductors is permitted, provided the outlet box is large enough.
Replace devices that have been in temporary use during construction and that were
installed before building finishing operations were complete.
Keep each wiring device in its package or otherwise protected until it is time to connect
conductors.
Do not remove surface protection, such as plastic film and smudge covers, until the last
possible moment.
Connect devices to branch circuits using pigtails that are not less than 6 inches (152 mm)
in length.
When there is a choice, use side wiring with binding-head screw terminals. Wrap solid
conductor tightly clockwise, two-thirds to three-fourths of the way around terminal
screw.
Use a torque screwdriver when a torque is recommended or required by manufacturer.
When conductors larger than No. 12 AWG are installed on 15- or 20-A circuits, splice
No. 12 AWG pigtails for device connections.
Tighten unused terminal screws on the device.
When mounting into metal boxes, remove the fiber or plastic washers used to hold
device-mounting screws in yokes, allowing metal-to-metal contact.
Receptacle Orientation:
1.
Install ground pin of vertically mounted receptacles up , and on horizontally mounted
receptacles to the right .
WIRING DEVICES
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262726 - 6
F.
Device Plates: Do not use oversized or extra-deep plates. Repair wall finishes and remount
outlet boxes when standard device plates do not fit flush or do not cover rough wall opening.
G.
Dimmers:
1.
2.
Install dimmers within terms of their listing.
Install unshared neutral conductors on line and load side of dimmers according to
manufacturers' device listing conditions in the written instructions.
H.
Arrangement of Devices: Unless otherwise indicated, mount flush, with long dimension
vertical and with grounding terminal of receptacles on top. Group adjacent switches under
single, multigang wall plates.
I.
Adjust locations of floor service outlets and service poles to suit arrangement of partitions and
furnishings.
3.2
GFCI RECEPTACLES
A.
Install non-feed-through-type GFCI receptacles.IDENTIFICATION
B.
Comply with Section 260553 "Identification for Electrical Systems."
C.
Identify each receptacle with panelboard identification and circuit number. Use hot, stamped,
or engraved machine printing with black -filled lettering on face of plate, and durable wire
markers or tags inside outlet boxes.
3.3
FIELD QUALITY CONTROL
A.
Perform the following tests and inspections:
1.
Test Instruments: Use instruments that comply with UL 1436.
B.
Tests for Convenience Receptacles:
1.
2.
3.
4.
5.
6.
Line Voltage: Acceptable range is 105 to 132 V.
Percent Voltage Drop under 15-A Load: A value of 6 percent or higher is unacceptable.
Ground Impedance: Values of up to 2 ohms are acceptable.
GFCI Trip: Test for tripping values specified in UL 1436 and UL 943.
Using the test plug, verify that the device and its outlet box are securely mounted.
Tests shall be diagnostic, indicating damaged conductors, high resistance at the circuit
breaker, poor connections, inadequate fault current path, defective devices, or similar
problems. Correct circuit conditions, remove malfunctioning units and replace with new
ones, and retest as specified above.
C.
Wiring device will be considered defective if it does not pass tests and inspections.
D.
Prepare test and inspection reports.
END OF SECTION 262726
WIRING DEVICES
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262726 - 7
SECTION 262813 - FUSES
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract Documents apply to this Section.
SUMMARY
A.
Section Includes:
1.
2.
1.3
Cartridge fuses rated 600-V ac and less for use in enclosed switches
Spare-fuse cabinets.
.
ACTION SUBMITTALS
A.
Product Data: For each type of product indicated. Include construction details, material,
dimensions, descriptions of individual components, and finishes for spare-fuse cabinets. Include
the following for each fuse type indicated:
1.
Ambient Temperature Adjustment Information: If ratings of fuses have been adjusted to
accommodate ambient temperatures, provide list of fuses with adjusted ratings.
a.
b.
2.
3.
4.
5.
1.4
For each fuse having adjusted ratings, include location of fuse, original fuse rating,
local ambient temperature, and adjusted fuse rating.
Provide manufacturer's technical data on which ambient temperature adjustment
calculations are based.
Dimensions and manufacturer's technical data on features, performance, electrical
characteristics, and ratings.
Current-limitation curves for fuses with current-limiting characteristics.
Time-current coordination curves (average melt) and current-limitation curves
(instantaneous peak let-through current) for each type and rating of fuse.
Coordination charts and tables and related data.
CLOSEOUT SUBMITTALS
A.
Operation and Maintenance Data: For fuses to include in emergency, operation, and
maintenance manuals. Include the following:
1.
2.
3.
Ambient temperature adjustment information.
Current-limitation curves for fuses with current-limiting characteristics.
Time-current coordination curves (average melt) and current-limitation curves
(instantaneous peak let-through current) for each type and rating of fuse.
FUSES
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262813 - 1
4.
1.5
Coordination charts and tables and related data.
MAINTENANCE MATERIAL SUBMITTALS
A.
Furnish extra materials that match products installed and that are packaged with protective
covering for storage and identified with labels describing contents.
1.
1.6
Fuses: Equal to 10 percent of quantity installed for each size and type, but no fewer than
two of each size and type.
QUALITY ASSURANCE
A.
Source Limitations: Obtain fuses, for use within a specific product or circuit, from single
source from single manufacturer.
B.
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
by a qualified testing agency, and marked for intended location and application.
C.
Comply with NEMA FU 1 for cartridge fuses.
D.
Comply with NFPA 70.
E.
Comply with UL 248-11 for plug fuses.
1.7
PROJECT CONDITIONS
A.
1.8
Where ambient temperature to which fuses are directly exposed is less than 40 deg F (5 deg C)
or more than 100 deg F (38 deg C), apply manufacturer's ambient temperature adjustment
factors to fuse ratings.
COORDINATION
A.
Coordinate fuse ratings with utilization equipment nameplate limitations of maximum fuse size
and with system short-circuit current levels.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following (or approved equivalent determined by Department Project Manager):
1.
2.
3.
Cooper Bussmann, Inc.
Edison Fuse, Inc.
Ferraz Shawmut, Inc.
FUSES
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262813 - 2
4.
2.2
Littelfuse, Inc.
CARTRIDGE FUSES
A.
2.3
Characteristics: NEMA FU 1, nonrenewable cartridge fuses with voltage ratings consistent
with circuit voltages.
SPARE-FUSE CABINET
A.
Characteristics: Wall-mounted steel unit with full-length, recessed piano-hinged door and keycoded cam lock and pull.
1.
2.
3.
4.
Size: Adequate for storage of spare fuses specified with 15 percent spare capacity
minimum.
Finish: Gray, baked enamel.
Identification: "SPARE FUSES" in 1-1/2-inch- (38-mm-) high letters on exterior of
door.
Fuse Pullers: For each size of fuse, where applicable and available, from fuse
manufacturer.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine fuses before installation.
damaged.
B.
Examine holders to receive fuses for compliance with installation tolerances and other
conditions affecting performance, such as rejection features.
C.
Examine utilization equipment nameplates and installation instructions. Install fuses of sizes
and with characteristics appropriate for each piece of equipment.
D.
Evaluate ambient temperatures to determine if fuse rating adjustment factors must be applied to
fuse ratings.
E.
Proceed with installation only after unsatisfactory conditions have been corrected.
3.2
Reject fuses that are moisture damaged or physically
INSTALLATION
A.
Install fuses in fusible devices.
removing fuse.
B.
Install spare-fuse cabinet(s).
Arrange fuses so rating information is readable without
FUSES
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262813 - 3
3.3
IDENTIFICATION
A.
Install labels complying with requirements for identification specified in Section 260553
"Identification for Electrical Systems" and indicating fuse replacement information on inside
door of each fused switch and adjacent to each fuse block, socket, and holder.
END OF SECTION 262813
FUSES
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262813 - 4
SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract Documents apply to this Section.
SUMMARY
A.
Section Includes:
1.
2.
3.
4.
5.
6.
1.3
Fusible switches.
Nonfusible switches.
Receptacle switches.
Molded-case circuit breakers (MCCBs).
Molded-case switches.
Enclosures.
DEFINITIONS
A.
NC: Normally closed.
B.
NO: Normally open.
C.
SPDT: Single pole, double throw.
1.4
PERFORMANCE REQUIREMENTS
1.5
ACTION SUBMITTALS
A.
Product Data: For each type of enclosed switch, circuit breaker, accessory, and component
indicated. Include dimensioned elevations, sections, weights, and manufacturers' technical data
on features, performance, electrical characteristics, ratings, accessories, and finishes.
1.
2.
3.
4.
5.
6.
Enclosure types and details for types other than NEMA 250, Type 1.
Current and voltage ratings.
Short-circuit current ratings (interrupting and withstand, as appropriate).
Include evidence of NRTL listing for series rating of installed devices.
Detail features, characteristics, ratings, and factory settings of individual overcurrent
protective devices, accessories, and auxiliary components.
Include time-current coordination curves (average melt) for each type and rating of
overcurrent protective device; include selectable ranges for each type of overcurrent
protective device.
ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262816 - 1
B.
Shop Drawings: For enclosed switches and circuit breakers. Include plans, elevations, sections,
details, and attachments to other work.
1.
1.6
Wiring Diagrams: For power, signal, and control wiring.
INFORMATIONAL SUBMITTALS
A.
Qualification Data: For qualified testing agency.
B.
Field quality-control reports.
1.
2.
3.
1.7
Test procedures used.
Test results that comply with requirements.
Results of failed tests and corrective action taken to achieve test results that comply with
requirements.
CLOSEOUT SUBMITTALS
A.
Operation and Maintenance Data: For enclosed switches and circuit breakers to include in
emergency, operation, and maintenance manuals.
In addition to items specified in
Section 017823 "Operation and Maintenance Data," include the following:
1.
1.8
Manufacturer's written instructions for testing and adjusting enclosed switches and circuit
breakers.
MAINTENANCE MATERIAL SUBMITTALS
A.
Furnish extra materials that match products installed and that are packaged with protective
covering for storage and identified with labels describing contents.
1.
2.
1.9
Fuses: Equal to 10 percent of quantity installed for each size and type, but no fewer than
three of each size and type.
Fuse Pullers: Two for each size and type.
QUALITY ASSURANCE
A.
Source Limitations: Obtain enclosed switches and circuit breakers, overcurrent protective
devices, components, and accessories, within same product category, from single source from
single manufacturer of switchboards and panelboards for this project .
B.
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
by a qualified testing agency, and marked for intended location and application.
C.
Comply with NFPA 70.
ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262816 - 2
1.10
A.
PROJECT CONDITIONS
Environmental Limitations: Rate equipment for continuous operation under the following
conditions unless otherwise indicated:
1.
2.
1.11
A.
Ambient Temperature: Not less than minus 22 deg F (minus 30 deg C) and not
exceeding 104 deg F (40 deg C).
Altitude: Not exceeding 6600 feet (2010 m).
COORDINATION
Coordinate layout and installation of switches, circuit breakers, and components with equipment
served and adjacent surfaces. Maintain required workspace clearances and required clearances
for equipment access doors and panels.
PART 2 - PRODUCTS
2.1
FUSIBLE SWITCHES
A.
Basis-of-Design Product: Subject to compliance with requirements, provide product indicated
on Drawings or comparable product by one of the following (Drawings indicate maximum
dimensions for transformers including clearances. Comply with indicated maximum
dimensions.) (or approved equivalent determined by Department Project Manager):
1.
2.
3.
Eaton Electrical Inc.; Cutler-Hammer Business Unit.
Siemens Energy & Automation, Inc.
Square D; a brand of Schneider Electric.
B.
Type HD, Heavy Duty, Single Throw, 240 and 600-V ac, 1200 A and Smaller: UL 98 and
NEMA KS 1, horsepower rated, with clips or bolt pads to accommodate indicated fuses,
lockable handle with capability to accept three padlocks, and interlocked with cover in closed
position.
C.
Accessories:
1.
2.
3.
4.
2.2
Equipment Ground Kit: Internally mounted and labeled for copper and aluminum ground
conductors.
Neutral Kit: Internally mounted; insulated, capable of being grounded and bonded;
labeled for copper and aluminum neutral conductors.
Lugs: Mechanical type, suitable for number, size, and conductor material.
Service-Rated Switches: Labeled for use as service equipment.
NONFUSIBLE SWITCHES
A.
Basis-of-Design Product: Subject to compliance with requirements, provide product indicated
on Drawings or comparable product by one of the following (Drawings indicate maximum
ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262816 - 3
dimensions for transformers including clearances. Comply with indicated maximum
dimensions.) (or approved equivalent determined by Department Project Manager):
1.
2.
3.
Eaton Electrical Inc.; Cutler-Hammer Business Unit.
Siemens Energy & Automation, Inc.
Square D; a brand of Schneider Electric.
B.
Type HD, Heavy Duty, Single Throw, 240 and 600-V ac, 1200 A and Smaller: UL 98 and
NEMA KS 1, horsepower rated, lockable handle with capability to accept three padlocks, and
interlocked with cover in closed position.
C.
Accessories:
1.
2.
3.
2.3
Equipment Ground Kit: Internally mounted and labeled for copper and aluminum ground
conductors.
Neutral Kit: Internally mounted; insulated, capable of being grounded and bonded;
labeled for copper and aluminum neutral conductors.
Lugs: Mechanical type, suitable for number, size, and conductor material.
MOLDED-CASE CIRCUIT BREAKERS
A.
Basis-of-Design Product: Subject to compliance with requirements, provide product indicated
on Drawings or comparable product by one of the following (Drawings indicate maximum
dimensions for transformers including clearances. Comply with indicated maximum
dimensions.) (or approved equivalent determined by Department Project Manager):
1.
2.
3.
4.
Eaton Electrical Inc.; Cutler-Hammer Business Unit.
General Electric Company; GE Consumer & Industrial - Electrical Distribution.
Siemens Energy & Automation, Inc.
Square D; a brand of Schneider Electric.
B.
General Requirements:
Comply with UL 489, NEMA AB 1, and NEMA AB 3, with
interrupting capacity to comply with available fault currents.
C.
Thermal-Magnetic Circuit Breakers: Inverse time-current element for low-level overloads and
instantaneous magnetic trip element for short circuits. Adjustable magnetic trip setting for
circuit-breaker frame sizes 250 A and larger.
D.
Adjustable, Instantaneous-Trip Circuit Breakers: Magnetic trip element with front-mounted,
field-adjustable trip setting.
E.
Electronic Trip Circuit Breakers: Field-replaceable rating plug, rms sensing, with the following
field-adjustable settings:
1.
2.
3.
4.
Instantaneous trip.
Long- and short-time pickup levels.
Long- and short-time time adjustments.
Ground-fault pickup level, time delay, and I2t response.
ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262816 - 4
F.
Current-Limiting Circuit Breakers: Frame sizes 400 A and smaller, and let-through ratings less
than NEMA FU 1, RK-5.
G.
Integrally Fused Circuit Breakers: Thermal-magnetic trip element with integral limiter-style
fuse listed for use with circuit breaker and trip activation on fuse opening or on opening of fuse
compartment door.
H.
Ground-Fault, Circuit-Interrupter (GFCI) Circuit Breakers: Single- and two-pole configurations
with Class A ground-fault protection (6-mA trip).
I.
Features and Accessories:
1.
2.
3.
4.
5.
6.
7.
2.4
Standard frame sizes, trip ratings, and number of poles.
Lugs: Mechanical type, suitable for number, size, trip ratings, and conductor material.
Application Listing: Appropriate for application; Type SWD for switching fluorescent
lighting loads; Type HID for feeding fluorescent and high-intensity discharge lighting
circuits.
Ground-Fault Protection: Comply with UL 1053; integrally mounted, self-powered type
with mechanical ground-fault indicator; relay with adjustable pickup and time-delay
settings, push-to-test feature, internal memory, and shunt trip unit; and three-phase, zerosequence current transformer/sensor.
Communication Capability:
Circuit-breaker-mounted
[Din-rail-mounted]
communication module with functions and features compatible with power monitoring
and control system, specified in Section 260913 "Electrical Power Monitoring and
Control."
Undervoltage Trip: Set to operate at 35 to 75 percent of rated voltage without intentional
time delay.
Auxiliary Contacts: One SPDT switch with "a" and "b" contacts; "a" contacts mimic
circuit-breaker contacts, "b" contacts operate in reverse of circuit-breaker contacts.
ENCLOSURES
A.
Enclosed Switches and Circuit Breakers: NEMA AB 1, NEMA KS 1, NEMA 250, and UL 50,
to comply with environmental conditions at installed location.
1.
2.
3.
Indoor, Dry and Clean Locations: NEMA 250, Type 1 .
Outdoor Locations: NEMA 250, Type 3R .
Hazardous Areas Indicated on Drawings: NEMA 250, Type 7 and Type 9 .
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine elements and surfaces to receive enclosed switches and circuit breakers for compliance
with installation tolerances and other conditions affecting performance of the Work.
B.
Proceed with installation only after unsatisfactory conditions have been corrected.
ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262816 - 5
3.2
INSTALLATION
A.
Install individual wall-mounted switches and circuit breakers with tops at uniform height unless
otherwise indicated.
B.
Temporary Lifting Provisions: Remove temporary lifting eyes, channels, and brackets and
temporary blocking of moving parts from enclosures and components.
C.
Install fuses in fusible devices.
D.
Comply with NECA 1.
3.3
IDENTIFICATION
A.
Comply with requirements in Section 260553 "Identification for Electrical Systems."
1.
2.
3.4
Identify field-installed conductors, interconnecting wiring, and components; provide
warning signs.
Label each enclosure with engraved metal or laminated-plastic nameplate.
FIELD QUALITY CONTROL
A.
Perform tests and inspections.
1.
B.
Acceptance Testing Preparation:
1.
2.
C.
Manufacturer's Field Service: Engage a factory-authorized service representative to
inspect components, assemblies, and equipment installations, including connections, and
to assist in testing.
Test insulation resistance for each enclosed switch and circuit breaker, component,
connecting supply, feeder, and control circuit.
Test continuity of each circuit.
Tests and Inspections:
1.
2.
3.
Perform each visual and mechanical inspection and electrical test stated in NETA
Acceptance Testing Specification. Certify compliance with test parameters.
Correct malfunctioning units on-site, where possible, and retest to demonstrate
compliance; otherwise, replace with new units and retest.
Perform the following infrared scan tests and inspections and prepare reports:
a.
b.
Initial Infrared Scanning: After Substantial Completion, but not more than 60 days
after Final Acceptance, perform an infrared scan of each enclosed switch and
circuit breaker. Remove front panels so joints and connections are accessible to
portable scanner.
Instruments and Equipment: Use an infrared scanning device designed to measure
temperature or to detect significant deviations from normal values. Provide
calibration record for device.
ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262816 - 6
4.
Test and adjust controls, remote monitoring, and safeties.
malfunctioning controls and equipment.
Replace damaged and
D.
Enclosed switches and circuit breakers will be considered defective if they do not pass tests and
inspections.
E.
Prepare test and inspection reports, including a certified report that identifies enclosed switches
and circuit breakers and that describes scanning results. Include notation of deficiencies
detected, remedial action taken, and observations after remedial action.
3.5
ADJUSTING
A.
Adjust moving parts and operable components to function smoothly, and lubricate as
recommended by manufacturer.
B.
Set field-adjustable circuit-breaker trip ranges as specified in Section 260573 "Overcurrent
Protective Device Coordination Study."
END OF SECTION 262816
ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
262816 - 7
SECTION 265100 - INTERIOR LIGHTING
PART 1 - GENERAL
1.1
A.
RELATED DOCUMENTS
Drawings and general provisions of the Contract Documents apply to this Section.
1.2
A.
SUMMARY
Section Includes:
1.
2.
B.
Interior lighting fixtures, led lamps, and power drives.
Lighting fixture supports.
Related Sections:
1.
2.
1.3
Section 260943.16 "Addressable-Fixture Lighting Controls" for manual or programmable
control systems with low-voltage control wiring or data communication circuits.
Section 262726 "Wiring Devices" for manual wall-box dimmers for linear led lamps.
DEFINITIONS
A.
CRI: Color-rendering index.
B.
LED: Light-emitting diode.
C.
LER: Luminaire efficacy rating.
D.
Lumen: Measured output of lamp and luminaire, or both.
E.
Luminaire: Complete lighting fixture, including power drive housing if provided.
1.4
A.
ACTION SUBMITTALS
Product Data: For each type of lighting fixture, arranged in order of fixture designation.
Include data on features, accessories, finishes, and the following:
1.
2.
3.
4.
5.
6.
Physical description of lighting fixture including dimensions.
Emergency lighting units including battery and charger.
Power drive.
Energy-efficiency data.
Life, output (lumens, CCT, and CRI), and energy-efficiency data for lamps.
Photometric data and adjustment factors based on laboratory tests, complying with
IESNA Lighting Measurements Testing & Calculation Guides, of each lighting fixture
INTERIOR LIGHTING
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
265100 - 1
type. The adjustment factors shall be for lamps, power drive, and accessories identical to
those indicated for the lighting fixture as applied in this Project.
a.
Manufacturer Certified Data:
Photometric data shall be certified by a
manufacturer's laboratory with a current accreditation under the National
Voluntary Laboratory Accreditation Program for Energy Efficient Lighting
Products.
B.
Installation instructions.
1.5
A.
INFORMATIONAL SUBMITTALS
Coordination Drawings: Reflected ceiling plan(s) and other details, drawn to scale, on which
the following items are shown and coordinated with each other, using input from installers of
the items involved:
1.
2.
3.
4.
5.
Lighting fixtures.
Suspended ceiling components.
Partitions and millwork that penetrate the ceiling or extends to within 12 inches (305
mm) of the plane of the luminaires.
Structural members (existing) to which suspension systems for lighting fixtures will be
attached.
Other items in finished ceiling including the following:
a.
b.
c.
d.
e.
6.
Air outlets and inlets.
Speakers.
Sprinklers.
Smoke and fire detectors.
Access panels.
Perimeter moldings.
B.
Product Certificates: For each type of power drive for bi-level and dimmer-controlled fixtures,
from manufacturer.
C.
Field quality-control reports.
D.
Warranty: Sample of special warranty.
1.6
A.
CLOSEOUT SUBMITTALS
Operation and Maintenance Data: For lighting equipment and fixtures to include in emergency,
operation, and maintenance manuals.
1.
Provide a list of all LED lamp types used on Project; use ANSI and manufacturers' codes.
INTERIOR LIGHTING
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
265100 - 2
1.7
A.
MAINTENANCE MATERIAL SUBMITTALS
Furnish extra materials that match products installed and that are packaged with protective
covering for storage and identified with labels describing contents.
1.
2.
3.
1.8
Lamps: 10 for every 100 of each type and rating installed. Furnish at least one of each
type.
Plastic Diffusers and Lenses: One for every 100 of each type and rating installed.
Furnish at least one of each type.
Power drives: One for every 100 of each type and rating installed. Furnish at least one
of each type.
QUALITY ASSURANCE
A.
Luminaire Photometric Data Testing Laboratory Qualifications: Provided by manufacturers'
laboratories that are accredited under the National Volunteer Laboratory Accreditation Program
for Energy Efficient Lighting Products.
B.
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
by a qualified testing agency, and marked for intended location and application.
C.
Comply with NFPA 70.
1.9
A.
1.10
A.
COORDINATION
Coordinate layout and installation of lighting fixtures and suspension system with other
construction that penetrates ceilings or is supported by them, including HVAC equipment, firesuppression system, and partition assemblies.
WARRANTY
Special Warranty for Emergency Lighting Batteries: Manufacturer's standard form in which
manufacturer of battery-powered emergency lighting unit agrees to repair or replace
components of rechargeable batteries that fail in materials or workmanship within specified
warranty period.
PART 2 - PRODUCTS
2.1
A.
MANUFACTURERS
Products: Subject to compliance with requirements, available products that may be
incorporated into the Work include, but are not limited to, product(s) indicated on Drawings (or
approved equivalent determined by Department Project Manager).
INTERIOR LIGHTING
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
265100 - 3
2.2
GENERAL REQUIREMENTS FOR LIGHTING FIXTURES AND COMPONENTS
A.
Recessed Fixtures: Comply with NEMA LE 4 for ceiling compatibility for recessed fixtures.
B.
LED Fixtures: Comply with UL 1598. Where LER is specified, test according to NEMA LE 5
and NEMA LE 5A as applicable.
C.
Metal Parts: Free of burrs and sharp corners and edges.
D.
Sheet Metal Components: Steel unless otherwise indicated. Form and support to prevent
warping and sagging.
E.
Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage under
operating conditions, and designed to permit relamping without use of tools. Designed to
prevent doors, frames, lenses, diffusers, and other components from falling accidentally during
relamping and when secured in operating position.
F.
Diffusers:
1.
Acrylic Lighting Diffusers: 100 percent virgin acrylic plastic. High resistance to
yellowing and other changes due to aging, exposure to heat, and UV radiation.
a.
b.
G.
Factory-Applied Labels: Comply with UL 1598. Include recommended LED lamps and power
drives. Labels shall be located where they will be readily visible to service personnel, but not
seen from normal viewing angles when lamps are in place.
1.
Label shall include the following LED lamp and power drive characteristics:
a.
b.
c.
2.3
A.
2.4
A.
Lens Thickness: At least 0.125 inch (3.175 mm) minimum unless otherwise
indicated.
UV stabilized.
"USE ONLY" and include specific lamp type.
Lamp code (long-life LED), linear configuration base type, and nominal wattage
for LED luminaires.
CCT and CRI for all luminaires.
LED LAMPS
LED lamps, rated 38 W maximum, nominal length of 24 inches (669 mm), 3300 initial lumens
(minimum), CRI 80 (minimum), color temperature indicated in drawings, and average rated life
50,000 hours unless otherwise indicated.
LIGHTING FIXTURE SUPPORT COMPONENTS
Comply with Section 260529 "Hangers and Supports for Electrical Systems" for channel- and
angle-iron supports and nonmetallic channel and angle supports.
INTERIOR LIGHTING
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
265100 - 4
B.
Single-Stem Hangers: 1/2-inch (13-mm) steel tubing with swivel ball fittings and ceiling
canopy. Finish same as fixture.
C.
Twin-Stem Hangers: Two, 1/2-inch (13-mm) steel tubes with single canopy designed to mount
a single fixture. Finish same as fixture.
D.
Wires: ASTM A 641/A 641M, Class 3, soft temper, zinc-coated steel, 12 gage (2.68 mm) .
E.
Wires for Humid Spaces: ASTM A 580/A 580M, Composition 302 or 304, annealed stainless
steel, 12 gage (2.68 mm) .
F.
Rod Hangers: 3/16-inch (5-mm) minimum diameter, cadmium-plated, threaded steel rod.
G.
Hook Hangers: Integrated assembly matched to fixture and line voltage and equipped with
threaded attachment, cord, and locking-type plug.
PART 3 - EXECUTION
3.1
A.
INSTALLATION
Lighting fixtures:
1.
2.
Set level, plumb, and square with ceilings and walls unless otherwise indicated.
Install lamps in each luminaire.
B.
Temporary Lighting: If it is necessary, and approved by Architect, to use permanent luminaires
for temporary lighting, install and energize the minimum number of luminaires necessary.
When construction is sufficiently complete, remove the temporary luminaires, disassemble,
clean thoroughly, install new lamps, and reinstall.
C.
Remote Mounting of Power Drives: Distance between the power drives and fixture shall not
exceed that recommended by power drive manufacturer.
Verify, with power drive
manufacturers, maximum distance between power drive and luminaire.
D.
Lay-in Ceiling Lighting Fixtures Supports: Use grid as a support element.
1.
2.
3.
E.
Install ceiling support system rods or wires, independent of the ceiling suspension
devices, for each fixture. Locate not more than 6 inches (150 mm) from lighting fixture
corners.
Support Clips: Fasten to lighting fixtures and to ceiling grid members at or near each
fixture corner with clips that are UL listed for the application.
Fixtures of Sizes Less Than Ceiling Grid: Install as indicated on reflected ceiling plans
or center in acoustical panel, and support fixtures independently with at least two 3/4inch (20-mm) metal channels spanning and secured to ceiling tees.
Connect wiring according to Section 260519 "Low-Voltage Electrical Power Conductors and
Cables."
INTERIOR LIGHTING
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
265100 - 5
3.2
A.
3.3
IDENTIFICATION
Install labels with panel and circuit numbers on concealed junction and outlet boxes. Comply
with requirements for identification specified in Section 260553 "Identification for Electrical
Systems."
FIELD QUALITY CONTROL
A.
Test for Emergency Lighting: Interrupt power supply to demonstrate proper operation.
B.
Prepare a written report of tests, inspections, observations, and verifications indicating and
interpreting results. If adjustments are made to lighting system, retest to demonstrate
compliance with standards.
3.4
STARTUP SERVICE
Burn-in all lamps that require specific aging period to operate properly, prior to occupancy by
Owner.
END OF SECTION 265100
INTERIOR LIGHTING
SunGuide Transportation Management Center Control Room Retrofit
90% Submittal
265100 - 6