PL300 FI Protection and Control High voltage circuit breaker INGEPACTM PL300FI is a suitable solution for backup protection of single-pole and three-pole high voltage breakers, guaranteeing the clearance of faults when main protection trip does not succeed. Its main unit is a breaker failure detector that performs trip on CB’s alternative trip circuits or on CBs upstream of the fault, thus isolating the faulted area from receiving any energy. Additionally, this equipment provides a continuous real time CB monitoring and ancillary protection and supervision features such as logic signals generation, events recording and different communication options regarding physical means and protocols, which are usually not performed by the main unit. BUSBAR 3 74TC 74CC 52 3 51 Flashover 51N End fault prot. 50BF 3 2x50 Software ∙∙ All of the equipment in the INGEPACTM family can be accessed using powerful software tools developed by Ingeteam and which run on Windows®. ∙∙ Application software specifically designed for simple and user-friendly access to the equipment. 2x50N 46 46BC 3 1 51 46 51N 2x50N 50BF 2x50 46BF Flashover End fault prot. 3 87N 74TC 74CC 52 1 1 25 27 Current functions 50BF Trip and open failure, single-pole and three-pole operation 50BF Open failure with low load or neutral current (two-pole/threepole trip) 50BF Close failure End fault protection Flashover detection, by current level or by voltage level 50/51, 50/51N Instantaneous and timed phases and neutral overcurrent 46 Current unbalance 46BC Broken conductor detection 2nd harmonic overcurrent restraint Voltage functions 27 Undervoltage on both sides of the breaker 87N Low impedance restricted earth protection 6 setting groups Other functions Pole discrepancy 25 Synchrocheck Breaker closure under coupling conditions 6 setting groups Breaker monitoring 74TC/CC trip and close circuit supervision Openings, closures, kI2 counter Excessive number of trips alarm Command failure Pulse opening/closure command or change of status detection (latch) Data Acquisition Functions Measurements historical report (maximum/minimum) Event, fault and oscillographic recorder Current measurement (fundamental and sequences), voltage (fundamental and sequences), power (active, reactive and apparent), power factor, frequency, demand maximeter, harmonics distortion Incoming active energy counter, outgoing active energy, incoming reactive energy and outgoing reactive energy Digital inputs and outputs Communications DB9 RS232 PROCOME protocol front port Up to 2 rear ports: RS232, RS485, Glass Fibre Optic, Plastic Fibre Optic, Ethernet RJ45 or Fibre Optic PROCOME, Modbus RTU, DNP 3.0, IEC60870-5-101, IEC60870-5-103 protocols Ports, protocols, digital inputs and outputs and logic capacity increased on TCP embedded versions Synchronisation Via communications protocol or via demodulated IRIG-B input. Local interface Keypad (16 keys + 4 operating buttons) + local display (2 rows x 16 characters) SIPCON software running on Windows for PC, front or rear port access. General Description ∙∙ Measurement of conducted radioelectric emissions in DC power port IEC60255-25/ EN55022 ∙∙ Measurement of radiated radioelectric emissions IEC60255-25/ EN55022 ∙∙ Insulation resistance test IEC60255-5 ∙∙ Dielectric test IEC60255-5 ∙∙ Impulse voltage test IEC60255-5 ∙∙ Electrostatic discharges immunity test IEC61000-4-2 ∙∙ Radiated radiofrequency fields immunity test ENV 50204/IEC 61000-4-3 ∙∙ Electrical fast transients immunity test IEC61000-4-4 ∙∙ Surge immunity test IEC61000-4-5 ∙∙ Conducted disturbances induced by radio-frequency fields immunity test IEC61000-4-6 ∙∙ 50 Hz magnetic fields immunity test IEC61000-4-8 ∙∙ Pulse magnetic fields immunity test IEC61000-4-9 ∙∙ Damped oscillatory magnetic fields immunity test IEC61000-4-10 ∙∙ 50 Hz magnetic fields immunity test IEC61000-4-17 ∙∙ Damped oscillatory waves immunity test IIEC61000-4-18/ IEC60255-22-1 ∙∙ DC supply voltage polarity inversion, variations, dips and interruptions immunity test IEC61000-4-29/ IEC60255-11 ∙∙ Power frequency immunity test IEC60255-22-7 Climatic ∙∙ Saline-oiled fog test UNE112-017-92 ∙∙ Cold test IEC 60068-2-2 ∙∙ Dry heat test IEC 60068-2-1 ∙∙ Damp heat test, steady state IEC 60068-2-78 ∙∙ Change of temperature (thermal shock) IEC 60068-2-14 Mechanical ∙∙ Vibration test IEC60255-21-1 ∙∙ Shock and bump test IEC 60255-21-2 ∙∙ Seismic IEC 60255-21-3 ∙∙ Different hardware configuration options allowing to choose the most suitable one for each application. ∙∙ Restricted zone earth faults protection for GIS modular installations (model C) ∙∙ Grids coupling and monitoring (breaker closure) under synchronisation conditions, in order to provide a stable connection of generators or separated grids (model C) ∙∙ Intuitive configuration and monitoring software supplied with the equipment. It does not require a previous configuration to communicate with the device. ∙∙ Different standard communication protocols for electric substations selectable via setting ∙∙ Wide dynamic range allowing connection to 5A or 1A secondary of CT ∙∙ User-defined logic signals ∙∙ Digital inputs and outputs and programmable LED indicators ∙∙ Real time monitoring and recording of the parameters of the breaker ∙∙ Events and faults recording ∙∙ 6 setting groups for the automatic adaptation of the relay’s programming to the grid conditions. ∙∙ Synchronisation via demodulated IRIG-B or through communication protocols Options ∙∙ Available formats Vertical 266x132.5x259 mm; Horizontal 132.5x266x259 mm; Embedded into TCP: 177x480x256 mm (19” rack) ∙∙ Connections for pin or ring type terminals ∙∙ Field interfaces Configuration Digital inputs 0 8 Digital outputs 7 1 17 14 ∙∙ Power supply: 24/48 Vcc; 125/220 Vcc ∙∙ Power supply voltage measurement ∙∙ Communications ports All of the devices have a front RS232 port for local access and additionally: 1 serial; 2 serials; 1 serial + 1 Ethernet (other variants in TCP embedded models) ∙∙ Communication ports connection types: Serial: RS232, RS485, Glass Fibre Optic, Plastic Fibre Optic Ethernet: RJ45, Fibre Optic ∙∙ IP54 front lid ∙∙ Models by protection functions: PL300FI-A: 50BF, 50, 51, 50N, 51N, 46, 46BC, Flashover (with busbar voltages), End fault detection, Pole discrepancy, 2nd harmonic restraint, 74TC/CC PL300FI-B: 50BF, 50, 51, 50N, 51N, 46, 46BC, Flashover (with busbar voltages), End fault detection, Pole discrepancy, 2nd harmonic restraint, 74TC/CC PL300FI-C: 50BF, 50, 51, 50N, 51N, 46, 46BC, Flashover (with busbar voltages), End fault detection, Pole discrepancy, 27, 87N, 25, Grids coupling, 2nd harmonic restraint, 74TC/CC Applications ∙∙ High Voltage breaker backup protection unit for conventional or compact substations (GIS). The technical data in this catalogue is subject to change without prior notice. FY20IPTT01_A/112014 Main Features Electromagnetic and Insulation