MSP1000 Motor Protection System • • • • • • • • • • • • • • • Real time true RMS measurement. Current range 1.60 - 10,000 Amp Can use low price instrument class CT's because of the very low burden. PC interface. Memory of reserve capacity, trip causes, status and pre-trip values, number of starts and running hours. Can be used to protect variable frequency driven motors. Current unbalance protection Level settable: 3%-40% in 1% steps, Delay settable: 1s-30s in 1s steps, or -30 min., in 1 min. steps. Switchable alarm/trip. Earth fault protection Short circuit protection, wide range settable. Contactor trip inhibit. (class C coordination) Stall protection. Undercurrent protection. Local and remote trip reset. Phase reversal with switchable ABC or BAC Configuration. INTRODUCTION The MSP1000 Motor protection relays are designed to protect electrical motors and connected loads from possible damage whilst minimizing the possibility of erroneous tripping and providing full information to the operator. The MSP1000 Motor protection relay is designed to protect the motor from the following occurrences. Thermal overload and cooling problems by RMS current measurement, thermistor monitoring, true thermal models and programmable starting conditions. Mechanical overload by stall protection as well as the thermal overload model. Electrical fault conditions of short circuit, phase imbalance, earth fault and phase reversal. The MSP1000 Motor protection relay may be configured to control Direct on Line (DOL), Direct on Line Reversing (DOLR), 2 Speed, Star-Delta, Auto-Transformer, Soft Start and Variable speed drives. Total protection means system protection not just the motor Up to 99A Full Load current can be monitored directly with the 16mm internal diameter Current transformers which are an integral part of the Protection Unit whilst above this various configurations of CTs can be provided. Earth Leakage current can be monitored either directly with the integral phase Current transformers or for more accurate requirements a Core Balance Current Transformer (CBCT) can be connected. The Monitor Unit provides a local Interface to the operator and can display percentage load current, phase current, unbalance, earth fault current, reserve thermal capacity & remaining time to trip. User configurable settings can be monitored. Alarms and trips can be reset locally or remotely. The MSP1000 Motor protection relay can be configured by a PC over a RS232 Serial Link or alternatively via a MSP Gateway Device. The MSP1000 Motor protection relay consists of a Protection unit and an optional Monitor unit. The units are intended for mounting in Motor Control Centers . MSP 1000 layout Remote reset Contact input See local reset button for more reset options. External core balance CT input 2 methods for ground fault measurement • CBCT: with core balance CT, for accurate ground-fault measurement in [Amp] • SPILL: without core balance CT, sufficient in most cases were no external CT’s are used for motor current measurement. in [%load] Motor Current input 3 phase direct feed trough hole up to 100 A Trip circuit 2 isolated circuits (NO/NC) 5A 380 Vac, 1250VA, 150W Selectable failsafe/non-failsafe. In non-failsafe selectable pulse tripping (shunt) Alarm circuit 2 isolated circuits (NO/NC) 5A 380 Vac, 1250VA, 150W Selectable failsafe/non-failsafe. Options Optional features Control voltage 115 or 230 Vac PC connection (RS232) Connects to programming / readout PC with use of Gateway multiple units on one PC. Local reset button Reset can also be done: • Via remote reset contact • Via programming PC • Via local display Alarm / Trip indicator Led indication of an alarm / trip Thermistor input Integrated with thermal model, S/C and O/C detection, switchable on/off . (Connection of separate TRD unit possible.) Remote reset contact input see local reset button for more reset options Monitor Shows 12 readings of actual values and 13 settings. Indication of alarm and trip causes, reset button, Relay test capability. Some examples of readings: • continuous reading of thermal capacity at all times • stall set limit and trip value • earth fault limit and trip value • unbalance limit and trip value • undercurrent set limit • phase reversal • reserve capacity for allowable start • reserve capacity alarm level • time to trip • short circuit limit as % of Imon Technical specifications In current ranges [Amp] One model covering the range of 1.6 to 10,000 Amps. Using ../5A CT’s Inom range 1.6 – 9.99 A 10.0 – 99 A 100 – 999 A 1.00 – 9.99 kA 10.0 – 99.9 kA Step 0.01 A 0.1 A 1 A 0.01 kA 0.12 kA CT’s Int. Int/Ext External External External NOTE: Interposing CT's may be low cost Instrument Class (IEC158/BS7626) because of the low burden. Thermal model T-6x In [sec] Locked rotor time 1-60 sec in 0.1 sec steps at 6xIn. Reserve cap at 100% load (hot curve) [%] Level settable 10-100%. Res.cap for start [%] Settable reserve capacity level needed for motor start. Start is inhibited below this level. Switchable trip if reserve capacity falls below this level to always guarantee one start capability. Res.cap alarm level [%] Warning level settable in % reserve capacity; switchable on/off. Time to trip alarm level [sec] Warn if remaining time before trip drops below level settable in sec; switchable on/off. Contactor trip inhibit (class C coordination) Level programmable from 200-1050% of the set In in 10% steps. If switched on it allows S/C to be cleared without opening contactor. Then trips contactor safely with indication of short circuit. Delay until current falls back below level. E/F Limit (Spill) % PH Level programmable from 3-30% of actual running load, in 1% steps. Delay settable 1-10 sec, steps 1 sec. Switchable alarm/trip. E/F Limit (CBCT) [Amp] Level settable 100 mA-10 A, in 100 mA steps. Delay settable 50 msec-10 sec in 25 msec-1 sec. steps. Switchable alarm/trip. U/B Limit [%] Level settable 3-40%, in 1% steps. Delay settable, 1-30 sec in 1 sec steps, or 1-30 min., in 1 min. steps. Switchable alarm/trip. Phase loss (U/B > 50%): Delay settable: 1-30 sec, 1 sec steps; always trips. Phase reversal Switchable trip/off. Phase rotation switchable ABC/ BAC. Detection time: 2 cycles. Thermistor input Integrated with thermal model, S/C and O/C detection, switchable on/off. (RTD via separate add-on option). U/C Level [% In] Level settable 10-100% of In, 1% steps. Delay programmable 1-30 sec, in 1 sec steps or 1-30 min., in 1 min. steps. Switchable on/off. Switchable trip or alarm. Stall limit [% In] Level programmable from 100-300%, steps 10%. Delay programmable from 50 msec-10 sec, steps 25 msec-1 sec. Switchable on/off, always trips if on. Memory Reserve capacity is memorized during power down. Running status, trip causes, pre-trip values, number of starts and running hours are all memorized. S/C Limit [% In] Level programmable from 200-1050% of the set In in 10% steps. Delay 50 msec-10 sec., steps 25 msec-1 sec. Excludes contactor trip inhibit Trip relay 2 isolated circuits (NO/NC). 5A/380Vac, 1250VA, 150W. Selectable failsafe/non-failsafe. In non-failsafe selectable pulse tripping (shunt). Alarm relay 2 isolated circuits (NO/NC). 5A/380Vac, 1250VA, 150W. Selectable failsafe/non-failsafe. Control voltage 115 of 230 Vac (specify at order) Plug-in LCD display Shows 12 readings of actual values and 13 settings Indication of trip and alarm causes. Reset button. Relay test capability. Cooling reduction motor off Specifies reduction in cooling due to stopped fan as compared to running fan. Normally set at 3. External core balance CT input Use special low power zener protected core balance CT's. * round cores / internal diameter CB500-12/Z 46 mm CB500-33/Z 65 mm CB500-30/Z 85 mm CB500-31/Z 145 mm CB500-32/Z 245 mm * square cores / inside dimension CB5-1015SP/Z 100 x 150 mm CB5-1020SP/Z 100 x 200 mm CB5-1025SP/Z 100 x 250 mm CB5-1030SP/Z 100 x 300 mm CB5-1035SP/Z 100 x 350 mm CB5-1040SP/Z 100 x 400 mm All these cores are also available as split cores. Consult factory for other dimensions. Dimensions MSP1000 base unit (WxHxD) 154x74x96mm 3 cables holes round 16mm MSP1000 monitor 130x90x42mm door cut-out 81x121mm (WxHxD) Ambient temperature range -10°C - +60°C (operating) -50°C - +80°C (storage)