SHEET INDEX GENERAL G001 COVER, SHEET INDEX ARCHITECTURAL D100 DEMOLITION FLOOR PLAN A101 RENOVATION FLOOR PLAN, WALL SECTION, NOTES A181 TAS INFORMATION, ENLARGED TOILET PLANS, TOILET ELEVATIONS A501 REFLECTED CEILING PLAN, MATERIAL LEGEND, CLG DETAILS, NOTES A601 DOOR AND WINDOW ELEVATIONS, SCHEDULE, AND DETAILS A701 FINISH FLOOR PLAN, FINISH LEGEND, GENERAL FINISH NOTES A771 INTERIOR ELEVATIONS AND MILLWORK MECHANICAL MD101 MECHANICAL DEMOLITION FLOOR PLAN ARCHITECT MECHANICAL HVAC FLOOR PLAN IS E REG PLUMBING ST PLUMBING LEGEND A PLUMBING DEMOLITION FLOOR PLAN TE T C Y L OR C H ARL S AR B ARR E T 18563 OF EC T MECHANICAL SCHEDULES ED TA M701 T ER IT MECHANICAL DETAILS H M501 S MECHANICAL SYMBOL LEGEND A M001 TE X WASTE & VENT FLOOR PLAN PP101 PLUMBING PIPING FLOOR PLAN P501 PLUMBING DETAILS ENGINEER ELECTRICAL ES101 ELECTRICAL SITE PLAN ED101 BAND HALL DEMOLITION FLOOR PLAN EL101 BAND HALL LIGHTING FLOOR PLAN EP101 BAND HALL POWER FLOOR PLAN ET101 BAND HALL SPECIAL SYSTEMS FLOOR PLAN ET501 TECHNOLOGY DETAILS E601 ONE-LINE DIAGRAM E602 GROUNDING & FIRE RISER DIAGRAMS E603 LIGHTING DETAIL & DIAGRAMS E701 LUMINARE SCHEDULES E702 PANEL SCHEDULES PROJECT 200 LONGHORN STREET VEGA, TEXAS 79092 ELECTRICAL LEGEND BAND HALL RENOVATION E001 REVISIONS VEGA BAND HALL RENOVATION PROJECT TEAM OWNER ARCHITECT / INTERIORS VEGA ISD DEKKER/PERICH/SABATINI, LLC. 200 LONGHORN ST. VEGA, TX 79092 TEL: 806-267-2126 FAX: 806-267-2146 500 S. TAYLOR, SUITE 750 AMARILLO, TX 79101 TEL: 806-376-8199 FAX: 806-376-8189 CONTACT: MIKE WARTES CONTACT: BARRY TAYLOR, AIA ELECTRICAL, PLUMBING, MECHANICAL & FIRE PROTECTION BRIDGERS & PAXTON CONSULTING ENGINEERS, INC. 4600-C MONTGOMERY BLVD. NE ALBUQUERQUE, NM 87109 TEL: 505-883-4111 FAX: 505-888-1436 CONTACT: ABBAS SHIRIAN, P.E. DRAWN BY REVIEWED BY DATE 7/29/2016 PROJECT NO. 14-0424.002 DRAWING NAME COVER SHEET INDEX of DRAWINGS G 001 BUILDING DEMOLITION NOTES ARCHITECT 1'-71 4" S Y L OR A TE X 2'-0"+/VERIFY 2'-1018"+/- VERIFY VERIFY 6"+/VERIFY 12'-27 8" 3'-218"+/- EXISTING SHELVING TO REMAIN (TYP) 512"+/6"+/VERIFY 11'-93 8"+/VERIFY 6"+/VERIFY 200 LONGHORN STREET VEGA, TEXAS 79092 VERIFY 13'-712"+/- PROJECT BAND HALL RENOVATION VERIFY 7'-83 4"+/- 13'-75 8"+/- 1. REMOVE EXISTING CEILING MATERIAL AND DUCTWORK, REFERENCE MEP DOC's AND COORDINATE BETWEEN TRADES. 2. ALL FLOORING, IN ITS ENTIRETY, TO BE REMOVED. 3. ALL CEILING, IN ITS ENTIRETY, TO BE REMOVED. 4. ALL LIGHTING, IN ITS ENTIRETY, TO BE REMOVED 12'-91 4"+/VERIFY 18563 OF EC T 6"+/VERIFY EXISTING MECHANICAL EQUIPMENT TO BE REMOVED SEE MD 101 CLOSE REMAINING WALL PENETRATIONS, WITH SIMILAR BUILDING MATERIAL IN FINISH & COLOR. MAKE WEATHER TIGHT (TYP) VERIFY C TA TE T IT A REMOVE EXISTING DOORS, FRAMES AND HARDWARE - SHOWN DASHED (TYP) SALVAGE F/A PULL STATION FOR RE-INSTALLATION, (IF POSSIBLE) TO NEW LOCATIONS AR B ARR E T ENGINEER EXISTING SHELVING TO BE DEMOLISHED - SHOWN DASHED (TYP) VERIFY NOTE: MAINTAIN EXISTING VENT STACK & EXHAUST FAN ROOF OPENINGS - FOR RE-USE w/ NEW VENT STACKS AND EXHAUST FAN EQUIPMENT (MODIFY CURBS AS NEEDED TO PREVENT NEW ROOF PENETRATIONS) MAKE WATER TIGHT (TYP) ED H S ST THE CONTRACTOR SHALL DELIVER THE ABOVE ITEMS TO THE OWNER AT HIS DIRECTION. CONSULT CONSTRUCTION MANAGER, CONCERNING DISPOSITIONS OF SALVAGE. ANY OF THE ABOVE ITEMS NOT WANTED BY THE OWNER SHALL BE DISPOSED OF, BY THE CONTRACTOR. NOTE: DEMO WALLS TO REQUIRED WIDTH, AS REQUIRED TO ACCOMMODATED NEW FRAMING OF NEW OPENINGS (TYP) T ER E EXISTING SHELVING TO BE DEMOLISHED - SHOWN DASHED (TYP) IS SALVAGE F/A PULL STATIONS FOR POSSIBLE RE-INSTALLATION, (IF POSSIBLE) TO NEW LOCATIONS R EG 5'-43 8"+/- SALVAGE FIRE EXTINGUISHER, FOR POSSIBLE RE-INSTALLATION IN NEW FIRE EXTINGUISHED CABINET VERIFY B. FIRE EXTINGUISHERS, TACK BOARDS, MAPS, ELECTRONICS, AND PROJECTION SCREENS SHALL BE REMOVED AND REMOVED & STORED FOR REINSTALLATION OR SALVAGED TO VISD. MAP AND TV BRACKETS ATTACHED TO THE WALL SHALL BE REMOVED, PROTECTED, AND SALVAGED TO THE OWNER, AT OWNERS DISCRETION. VISD SHALL RETAIN CERTAIN ITEMS REMOVED FROM THE BUILDING. (1) THE CLOCK AND BELL COMPONENTS. (2) THE AUDIO-VISUAL SYSTEM, INCLUDING SPEAKERS. (3) LIGHT FIXTURES. (4) ALL LOCKS, PANIC DEVICES, DOOR CLOSERS AND DOOR HARDWARE NOT RE-USED. (5) ALL BREAKERS, STARTERS, STAGE LIGHTING AND LIGHT FIXTURES NOT RE-USED. (6) ALL PUMPS AND MOTORS NOT RE-USED, INCLUDING STARTERS. (7) ALL COPPER PIPES REMOVED. (8) ALL DRINKING FOUNTAINS, BUBBLERS, AND VALVES. (9) ANY SHELVING NOT RE-USED. (10) ALL FLUSH VALVES NOT RE-USED. (11) ANY WATER CLOSETS AND FIXTURES NOT RE-USED. (12) THE OWNER'S CHOICE OF PIPE ABOVE 1-1/4" IN DIAMETER. (13) FIRE ALARM SYSTEMS, INCLUDING HORNS AND PULL STATIONS (IF UNABLE TO REUSE). (14) HVAC UNITS AND EXHAUST FANS. C H AR L A. REMOVE EXISTING CONSTRUCTION SHOWN DASHED (TYP) REVISIONS EXISTING CANOPY TO REMAIN (TYP) LEGEND WALLS AT PERIMETER TO REMAIN A1 BAND HALL DEMOLITION PLAN 1/4" = 1'-0" 0 2' 4' 8' EXISTING CONSTRUCTION TO REMAIN DRAWN BY EXISTING CONSTRUCTION TO BE REMOVED IN IT'S ENTIRETY REVIEWED BY DATE ALL EXISTING DIMS +/- TO BE VERIFIED. (TYP.) PROJECT NO. 7/29/2016 14-0424.002 DRAWING NAME BAND HALL DEMOLITION PLAN D100 GENERAL SHEET NOTES 1. 2. 3. 4. 5. 5'-43 8" 5'-612" 4'-103 4" 6" MTL STUDS NOTE: CHASE WALL CONSTR., TO BE 212" MTL STUDS at 16" o.c., (MAX.) w/ 5 8" GYP. BD. ROOM SIDE ONLY, UTILIZE 'V' BAR HORIZ. BRACING at 24" VERTICALLY, ON CHASE SIDE, (TYP) 4" 1'-0" 3'-4" 2'-612" 46'-95 8" NEW CARPET TILE TO MATCH NEW HIGH SCHOOL NEW WALLS TO BE FILLED WITH 2 12" (THERMA-FIBER) SOUND ATTENUATION BLANKETS. WALLS & DOORS ARE TO BE BUILT AS SOUND PROOF AS POSSIBLE RESTROOM FINISHES ARE TO MATCH NEW HIGH SCHOOL. FURR OUT EXISTING WALLS AT PERIMETER OF BUILDING, IF REQ'D., TO ACCOMMODATE NEW POWER OUTLETS, SWITCHES, ETC. 19'-45 8" A1 2" 6'-4" A601 ARCHITECT S 18563 OF A T E IS C H ARL R EG 4'-212" Y L OR TE EC T A C TA 7'-83 4" AR B A RRE T T TE X ENGINEER 6" MTL STUDS NOTE: CHASE WALL CONSTR., TO BE 212" MTL STUDS at 16" o.c., (MAX.) w/ 5 8" GYP. BD. ROOM SIDE ONLY, UTILIZE 'V' BAR HORIZ. BRACING at 24" VERTICALLY, ON CHASE SIDE, (TYP) PROJECT NOTE: ALL NEW WALL CONSTRUCTION AT EXISTING WALLS TO REMAIN, ARE TO BE 2 x MATERIAL, w/ LAYERS OF GYP. BD. AS REQUIRED, TO MEMBER OUT w/ EXISTING WALLS (TYP) A1 1'-41 2" 6'-45 8"+/- 5'-97 8"+/- 6'-4" 6'-4" 6" MTL STUDS 5'-01 4" 1'-93 4" MATERIAL LEGEND EXISTING CONSTRUCTION TO REMAIN NEW CONSTRUCTION at MTL STUDS 2" TH'K ACOUSTICAL SOUND PANELS OVER GYP. BD FINISH, WHERE SHOWN. NEW DISPLAY SHELF 200 LONGHORN STREET VEGA, TEXAS 79092 A601 BAND HALL RENOVATION 5'-41 2" 6'-4" 2'-612" SIM TO STRUCTURE ABOVE ED IT NOTE: CHASE WALL CONSTR., TO BE 212" MTL STUDS at 16" o.c., (MAX.) w/ 5 8" GYP. BD. ROOM SIDE ONLY, UTILIZE 'V' BAR HORIZ. BRACING at 24" VERTICALLY, ON CHASE SIDE, (TYP) S ST 2'-612" ER H NOTE: ALL NEW WALL CONSTRUCTION IN SOUTH PORTION OF BUILDING AREA, ARE TO BE METAL STUD CONSTRUCTION, w/ 16" o.c., SPACING & 5 8" GYP. BD. EA. SIDE (TYP) NEW ACOUSTICAL CEILING AS HIGH AS POSSIBLE. R-19 THERMAL BATT INSULATION ABOVE APC. (TYP) NEW CONSTR. at EXISTING WALLS SOUND ATTENUATION BLANKETS (212" THERMA-FIBER OR EQUAL) TYP. ALL WALLS NEW ACOUSTICAL CEILING REVISIONS 4" 1'-4" SHELF TO HAVE HIDDEN BRACKETS AND APPEAR TO BE CONTINUOUS 47 8" KEYPLAN 4" 2" THICK ACOUSTICAL SOUND PANELS REF ELEV's A771 11'-0" 10'-10" DRAWN BY REVIEWED BY 7'-2" DATE DOOR AND FRAME AS SCHEDULED 7/29/2016 14-0424.002 PROJECT NO. DRAWING NAME FINISHED FLOOR AS SCHEDULED SEE A701 A1 RENOVATION FLOOR PLAN WALL SECTION 3/8" = 1'-0" A101 3'-6 7/8" 1'-9 1/4" LAVATORY PAPER TOWEL DISPENSER SHOWER CURTAIN, ROD & HOOKS MOP RACK SANITARY NAPKIN DISPOSAL CLEAR FLOOR SPACE MOP BASIN HI / LO ELECTRIC WATER COOLER ROBE HOOK 1'-6" 5'-2 1/2" 3'-6 7/8" SEE NOTE 'F' SHT. A701 1'-9 1/4" SEE NOTE 'F' SHT. A701 CONTROL AREA CENTERED ON TACTILE CHARACTERS 2' 4' 8' ACCESSIBLE SHOWER STALL NOTES LOCATIONS OF TACTILE E2 SIGNS AT DOORS FINISHED CEILING PAINTED GYP. BOARD SOFFITT (P-4) 0 1/2" = 1'-0" 1' 2' 1. 'ELL' SHAPED GRAB BAR 1/2" MAX SHOWER CURB 60" HOSE ACCESSIBLE TRANSFER SHOWER STALL CONTROL WALL ELEVATION (ADULT) 2. 3. 4. 4' 5. TILE (T-1 & T-2) SEE DETAIL A2/A701 'ELL'SHAPED GRAB BAR 6. 7. FINISHED FLOOR 8. TOILET GIRLS 207 1/4" = 1'-0" 0 2' 9. SHOWER SEAT 4' 8' ACCESSIBLE TRANSFER SHOWER STALL BACK WALL ELEVATION (ADULT) IN THE TRANSFER STALL, PROVIDE A SEAT ON THE WALL OPPOSITE THE CONTROLS AS INDICATED. MOUNT THE SEAT 18" ABOVE BATHROOM FLOOR (FOR ADULTS) AND EXTEND THE FULL DEPTH OF THE STALL. PROVIDE GRAB BARS AS INDICATED. LOCATE FAUCETS AND OTHER CONTROLS ON THE WALL OPPOSITE THE SEAT. PROVIDE A SHOWER SPRAY UNIT AS INDICATED WITH A HOSE AT LEAST 60" THAT CAN BE FIXED OR HAND-HELD. MOUNT THE UNIT AT 42" MAX (GRADE PRE-K THRU 5 OR 6) ABOVE SHOWER FLOOR FOR FORWARD REACH AND 48" MAX (ADULT) FORWARD REACH, OR 54" MAX (ADULT) SIDE REACH, ABOVE SHOWER FLOOR. PROVIDE FOLDING TYPE SEAT WHERE A FIXED SEAT IS INDICATED IN A 36" x 36" MIN. SHOWER STALL, MOUNTED ON THE WALL ADJACENT TO THE CONTROLS. PROVIDE MARBLE THRESHOLD (MAX HEIGHT OF 1/2") WHERE INDICATED, IN SHOWER STALLS 36" X 36", UNLESS PRE-FAB SHOWER UNIT IS PROVIDED. DO NOT OBSTRUCT CONTROLS OR OBSTRUCT TRANSFER FROM WHEELCHAIRS ONTO SHOWER SEATS WITHIN ENCLOSURES FOR SHOWER STALLS. THE STRUCTURAL STRENGTH OF SEATS AND THEIR ATTACHMENTS SHALL COMPLY WITH TAS 610.4. FINISHED CEILING 60" MAX. TILE (T-1 & T-2) SEE DETAIL A2/A701 BASELINE OF HIGHEST TACTILE CHARACTER 48" MIN BASELINE OF LOWEST TACTILE CHARACTER MEN TOILET PAPER DISPENSER OUTLET LOCATION 0 1/4" = 1'-0" 2' 4' FINISH FLOOR WHEELCHAIR ACCESSIBLE AMBULATORY ACCESSIBLE ACCESSIBLE STALL FRONT ELEVATION (ADULT) ACCESSIBLE STALL SIDE ELEVATION (ADULT) ACCESSIBLE WATER CLOSET & TOILET COMPARTMENTS TOILET GIRLS 207 2' 4' 8' 2. 3. FINISHED CEILING 30" x 48" CLEAR FLOOR SPACE COLORS SELECTED BY ARCHITECT B1 ACCESSIBLE DRESSING BENCH PLAN (IF INDICATED on PLANS) TTD 0 2' 4' 8' MEN ACCESSIBLE DRESSING BENCH BACK SUPPORT (IF INDICATED on PLANS) FINISHED CEILING PAINTED GYP. BOARD SOFFITT (P-4) (a) WALL HUNG TYPE TILE (T-1 & T-2) SEE DETAIL A2/A701 AMBULATORY ACCESSIBLE TOILET COMPARTMENT * OTHER APPROACHES 48" MIN. ADULT WALL HUNG WATER CLOSET (a) ELEVATION ADULT FINISHED FLOOR A1 TOILET BOYS 206 1/4" = 1'-0" 0 2' 4' 8' A2 HC SIGNAGE ELEV. AT R.R. 6" = 1'-0" 0 1" 2" 3" OF TE X ENGINEER TOILET SEAT HEIGHT (MEASURED FROM FLOOR TO RIM) A. AGES 3 & 4 = 11" TO 12" B. AGES 5 THROUGH 8 = 12" TO 15" C. AGES 9 THROUGH 12 = 15" TO 17" D. ADULT = 15" E. ACCESSIBLE = 17" TO 19" PROJECT ACCESSIBLE GRAB BAR HEIGHTS (MEASURED FROM FLOOR TO TOP OF BAR) A. AGES 3 & 4 = 18" TO 20" B. AGES 5 THROUGH 8 = 20 TO 25" C. AGES 9 THROUGH 12 = 25" TO 27" D. ADULT = 33" MIN. TO 36" MAX. TOILET PAPER DISPENSER HEIGHT (MEASURE FROM FLOOR TO CENTERLINE OF DISPENSER) A. AGES 3 & 4 = 14" B. AGES 5 THROUGH 8 = 14" TO 17" C. AGES 9 THROUGH 12 = 17 TO 19" D. ADULT (ACCESSIBLE) = 15" TO 48" * SANITARY NAPKIN DISPENSER (MEASURE FROM FLOOR TO COIN SLOT) A. FORWARD REACH = 15" TO 48" (UNOBSTRUCTED) B. FORWARD REACH = 48" MAX (OBSTRUCTED REACH DEPTH 20" MAX) C. FORWARD REACH = 44" MAX (OBSTRUCTED REACH DEPTH 25" MAX) D. SIDE REACH = 15" - 48" (UNOBSTRUCTED) E. SIDE REACH = 48" MAX (OBSTRUCTED HEIGHT 34" REACH DEPTH 10" MAX) F. SIDE REACH = 46" MAX (OBSTRUCTED HEIGHT 34" REACH DEPTH 24" MAX) SOAP DISPENSER & PAPER TOWEL DISPENSER (LOCATED WITHIN THE FORWARD & SIDE REACH RANGES) A. AGES 3 & 4 = 20" TO 36" B. AGES 5 THROUGH 8 = 18" TO 40" C. AGES 9 THROUGH 12 = 16" TO 44" D. FORWARD REACH = 15" TO 48" (UNOBSTRUCTED) E. FORWARD REACH = 48" MAX (OBSTRUCTED REACH DEPTH 20" MAX) F. FORWARD REACH = 44" MAX (OBSTRUCTED REACH DEPTH 25" MAX) G. SIDE REACH = 15" - 48" (UNOBSTRUCTED) H. SIDE REACH = 48" MAX (OBSTRUCTED HEIGHT 34" REACH DEPTH 10" MAX) J. SIDE REACH = 46" MAX (OBSTRUCTED HEIGHT 34" REACH DEPTH 24" MAX) MIRROR A. ABOVE COUNTERTOP B. NO COUNTERTOP C. FULL LENGTH = 40" MAX BOTTOM EDGE OF REFLECTING SURFACE FROM F.F. = 35" MAX BOTTOM EDGE OF REFLECTING SURFACE FROM F.F. = TOP OF MIRROR EDGE 74" MIN FROM FLOOR SHOWER HEADS (MEASURED FROM FLOOR TO HEAD) A. ADULTS = 78" B. ACCESSIBLE = 48" TO SHOWER HEAD (FORWARD REACH) = 48" TO TOP OF CONTROLS REVISIONS DRINKING FOUNTAINS (MEASURED FROM FLOOR TO SPOUT OUTLETS) A. ADULTS = 38" - 43" (STANDING PERSON) B. ACCESSIBLE = 36" (SPOUT SHALL BE LOCATED 15" MIN. FROM THE VERTICAL SUPPORT AND 5" MAX FROM THE FRONT EDGE OF THE UNIT, INCLUDING BUMPERS) SEATS A. BATHTUB B. SHOWER - STANDARD ROLL IN SHOWER (b) ELEVATION CHILDREN TTD WHEELCHAIR ACCESSIBLE TOILET COMPARTMENT TOE CLEARANCE LATCH APPROACH 3'-0" DOOR HEIGHT & DEPTH OF URINALS NOTE: 1. FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH TAS 309. 2. A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH TAS 305 POSITIONED FOR FORWARD APPROACH SHALL BE PROVIDED. 18563 WATER CLOSET CENTERLINE (MEASURED FROM SIDE WALL TO CENTERLINE) A. AGES 3 & 4 = 12" B. AGES 5 THROUGH 8 = 12" TO 15" C. AGES 9 THROUGH 12 = 15" TO 18" D. WHEELCHAIR = 16" TO 18" (NO MORE, NO LESS) E. AMBULATORY = 17" TO 19" (NO MORE, NO LESS) TOE CLEARANCE C. SHOWER - ALTERNATE ROLL-IN SHOWER BRAILLE, CONTRACTED (GRADE 2) TAS 703.3.1 NOTE: 1. INTERNATIONAL SYMBOL REQUIRED AT ALL TOILET SIGNAGE. 2. CHARACTERS AND THEIR BACKGROUND SHALL HAVE A NON-GLARE FINISH. CHARACTERS SHALL CONTRAST WITH THEIR BACKGROUND WITH EITHER LIGHT CHARACTERS ON A DARK BACKGROUND OR DARK CHARACTERS ON A LIGHT BACKGROUND. 3. PICTOGRAMS AND THEIR FIELD SHALL HAVE A NON-GLARE FINISH. PICTOGRAMS SHALL CONTRAST WITH THEIR FIELD WITH EITHER A LIGHT PICTOGRAM ON A DARK FIELD OR A DARK PICTOGRAM ON A LIGHT FIELD. C TTD (b) STALL TYPE SANS SERIF, UPPERCASE 1/32" MIN. RAISED CHARACTERS ABOVE BACKGROUND AR B ARR E T T SHOWER CURTAINS AND RODS (MEASURED FROM FLOOR TO BOTTOM OF CURTAIN) A. GENERAL = 1" NOTE: WHERE INSTALLED IN WET LOCATIONS, THE SURFACE OF THE SEAT SHALL BE SLIP RESISTANT AND SHALL NOT ACCUMULATE WATER. TOILET BOYS 206 1/4" = 1'-0" TOE CLEARANCE LATCH APPROACH FINISHED FLOOR 4. 3'-0" DOOR PICTOGRAM FIELD ONLY TILE (T-1 & T-2) SEE DETAIL A2/A701 BENCH SHALL PROVIDE FOR BACK SUPPORT OR SHALL BE AFFIXED TO A WALL. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE WATER CLOSET EXCEPT IN AMBULATORY ACCESSIBLE COMPARTMENTS (604.6) REQUIRED CLEAR FLOOR SPACES, CLEARANCES AT FIXTURES, AND TURNING SPACE SHALL BE PERMITTED TO OVERLAP. (TAS 603.2.2) DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE. (TAS 603.2.3) TOILET COMPARTMENT DOORS, SHALL HAVE PULLS ON BOTH SIDES OF DOOR, NEAR THE LATCH. LATCH APPROACH 0 1. 3'-0" DOOR 1/4" = 1'-0" TE SANITARY NAPKIN DISPOSAL UNIT (MEASURE FROM FLOOR TO TOP OF UNIT) A. SIDE REACH = 15" - 48" (UNOBSTRUCTED) FINISH FLOOR 8' FINISHED FLOOR C1 A * SHALL NOT BE LOCATED BEHIND GRAB BARS FLUSH CONTROL ON WIDE SIDE ED S TRANSFER SIDE HEIGHT OF TACTILE CHARACTERS ABOVE FINISH FLOOR OR GROUND C2 URINALS (MEASURED FROM FLOOR TO RIM) A. ADULT = 24" B. ACCESSIBLE = 17" MAX. ER Y L OR 0 TYPICAL WALL LAVATORY LAVATORIES (MEASURED FROM FLOOR TO SINK RIM) A. NON ACCESSIBLE 5 YEARS & YOUNGER = PARALLEL APPROACH COMPLYING WITH TAS 305 ELEM.SCH. B. NON ACCESSIBLE 6 TO 12 YEARS = 31" MAX (24" MIN. KNEESPACE) BUBBLER C. NON ACCESSIBLE ADULT = 32" D. ACCESSIBLE (ALL AGE GROUPS) = 34" MAX (29" MIN. KNEESPACE) *WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST CONTACT. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES UNDER LAVATORIES AND SINKS. (TAS 606.5) EC T ACCESSIBLE MIRROR ELEVATION FIXTURE MOUNTING HEIGHT SCHEDULE TA A181 ARCHITECT IT WALL MOUNTED SOAP DISPENSER WALL MOUNTED LAVATORY 18" X 36" CHANNEL FRAMED TEMPERED GLASS MIRROR (REFER TO ACCESSIBLE MIRROR ELEVATION FOR MIRROR HEIGHT AT ACCESSIBLE LAVATORIES) ENLARGED TOILET PLAN 1/4" = 1'-0" CURTAIN ROD AND CURTAIN w/ HOOKS SHOWER HEAD A1 B1 WASHFOUNTAIN NOTE: THE MOUNTING DEVICE FOR THE HAND-HELD SHOWER HEAD SHALL FALL WITHIN THE FORWARD REACH RANGES H 4'-8 5/8" URINAL CHANNEL FRAMED MIRROR (18" x 34" UNLESS NOTED OTHERWISE) TYPICAL ACCESSIBLE TRANSFER SHOWER STALL PLAN NOTE : UNLESS NOTED OTHERWISE, 3 5 8" MTL STUDS at 16"o.c. (MAX), ARE TO BE USED at TOILET WALLS, USE 'V' BAR BRACING at 24" o.c., VERT. AT CHASE SIDE OF PLUMBING CHASE WALL. (TYP) D1 SOAP DISPENSER ALL DIMENSIONS ARE FROM FINISH MATERIAL. ALL TOILET ROOM WALLS EXTEND TO DECK, UNLESS OTHERWISE NOTED. PROVIDE SOUND ATTENUATION BATT INSULATION IN STUD WALL CONSTRUCTION AROUND TOILET ROOMS. 4. PROVIDE WALL MOUNTED DOOR STOPS IN RESTROOMS. 5. REFER TO SHEET A701 FOR INTERIOR FINISHES 6. EXTEND CERAMIC TILE UP TO AND AROUND MIRRORS ON WALLS WITH CERAMIC TILE WAINSCOT. 7. REFER TO 'TOILET ROOM LEGEND' ON THIS SHEET FOR FIXTURES AND ACCESSORY INFO. 8. PROVIDE THE SAME FIXTURES AND ACCESSORIES AT ALL SINGLE ACCESSIBLE TOILET ROOMS WHICH ARE TO BE PROVIDED AT TYPICAL FIXTURES, AS INDICATED IN 'TOILET ROOM LEGEND'. PROVIDE ACCESSORIES FOR ACCESSIBLE WATER CLOSETS AS INDICATED FOR A 'TYPICAL ACCESSIBLE STALL', PROVIDE ACCESSORIES FOR ACCESSIBLE LAVATORIES AS INDICATED FOR A 'TYPICAL ACCESSIBLE WALL LAVATORY', AND PROVIDE ACCESSORIES FOR ACCESSIBLE SHOWER STALLS AS INDICATED FOR A 'TYPICAL ACCESSIBLE SHOWER'. 9. REFER TO 'FIXTURE MOUNTING HEIGHT SCHEDULE' FOR MOUNTING HEIGHT INFORMATION. ALL ACCESSIBLE FIXTURES AND EQUIPMENT, ARE TO BE ADULT ACCESSIBLE FIXTURES & HEIGHTS , UNLESS NOTED OTHERWISE, FOR ELEMENTARY SCHOOL HEIGHTS, OR FIXTURES FOR USE BY AGES 5 THRU 12. 10. COORDINATE INSTALLATION OF REQ'D BLOCKING AND STABILIZING FOR FIXTURES. 11. THE STRUCTURAL STRENGTH OF GRAB BARS AT ACCESSIBLE WATER CLOSETS SHALL COMPLY WITH TAS 2012 - 609.8. 12. REFER TO TOILET ACCESSORIES SCHEDULE AND / OR SPECIFICATIONS FOR ACCESSORIES AND INSTALLATION INFORMATION. ST E1 WALL MOUNTED WATER CLOSET 1. 2. 3. S 3 5/8" 3 5/8" 4'-2 3/8" 5'-2 1/2" CONTROL WALL 5 1/2" 1'-6" 'ELL' SHAPED GRAB BAR TOILET TISSUE DISPENSER (TTD) A SEAT WALL A181 SEE NOTE 'F' SHT. A701 1" 3'-11 3/4" C1 D1 3 5/8" 3 5/8" 4'-2 3/8" 19'-10 1/4" 8 1/2" SHOWER SEAT FLOOR MOUNTED WATER CLOSET 200 LONGHORN STREET VEGA, TEXAS 79092 BACK WALL BAND HALL RENOVATION 6'-6 7/8" T 3'-9 1/8" TOILET PLAN GENERAL NOTES IS 3'-2" TOILET ROOM LEGEND 3 5/8" E 5'-1 1/2" 3 5/8" 1" R EG 3 5/8" 1" C H AR L 19'-4 5/8" D. SHOWER - TRANSFER TYPE * OTHER APPROACHES 48" MIN. D/P/S DRAWN BY = 17" - 19" ABOVE BATHROOM FINISH FLOOR = 15" - 16" DEPTH (REMOVABLE) = 15" DEPTH (PERMANENT, EXTEND FROM BACK TO OR BEYOND THE OUTER EDGE OF THE BATHTUB) = FOLDING TYPE, INSTALLED ON SIDE WALL ADJACENT TO CONTROLS, EXTEND FROM BACK WALL TO A POINT WITHIN 3" OF THE COMPARTMENT ENTRY = FOLDING TYPE, INSTALLED ON FRONT WALL OPPOSITE THE BACK WALL, EXTEND FROM THE ADJACENT SIDE WALL TO A POINT WITHIN 3" OF THE COMPARTMENT ENTRY = 17" - 19" ABOVE BATHROOM FINISH FLOOR. SEAT SHALL EXTEND FROM BACK WALL TO A POINT WITHIN 3" OF THE COMPARTMENT ENTRY. CANE APRON REVIEWED BY JW 7/29/2016 DATE PROJECT NO. 14-0424.002 DRAWING NAME TAS INFORMATION ENLARGED TOILET PLANS, & TOILET ELEVATIONS ADULT FLOOR MOUNTED WATER CLOSET & CHILDREN'S WATER CLOSET COMPARTMENT ENTRY RECTANGULAR SHOWER SEAT COMPARTMENT ENTRY L-SHAPED SHOWER SEAT HI - LO E.W.C. ELEVATION A181 1'-4" FINISHED CEILING LIGHT FIXTURE REFER TO ELECTRICAL 'J' MOULD at PERIMETER (TYP) GYP. BOARD 0 3" 6" B2 9" 0 1/2" = 1'-0" 1' 2' B3 4' ARCHITECT MECH. SUSP. GYP BD CEILING 0 1" = 1'-0" 1/2' 2' 1' TA TE Y L OR ST A C 18563 OF 4' x 4' PYRAMID DIFFUSER (TYPICAL OF 3) EC T E AR B A RRE T T C H AR L S ED IT R EG ER H T IS 3" = 1'-0" SUSPENDED APC CLG DET. S B1 (REFER RCP) CAULK ALL AROUND AT WALL / CLG ANGLE (TYP) 8'-0" AFF EGG CRATE LENS SECTION, TYP. CLG. HT. ABOVE FIN.FLR. STRUCTURE ABOVE SUSPENSION WIRE 3 5 8" MTL STUD FRAMING (TYP) TYP SUSPENDED GDW CEILING SYSTEM, UON: 5 8" GYP BD (PAINTED) ON 7 8" FURRING CHANNELS AT 16" o.c., ON 1-1/2" C RUNNER CHANNELS AT 36" o.c. w/ 8 GA HANGER WIRE AT 48" o.c., UON A 8" 1'-0" 5 TE X ENGINEER MATERIAL LEGEND GYP. BOARD LIGHT COVE B2 A501 4' x 4' & 2' x 2' 'WENGER' TYPE, ACOUSTICAL PYRAMID DIFFUSERS PROJECT A TROPHY DISPLAY SHELF - ABOVE 2" ACOUSTICAL WALL PANEL - BUT, BELOW 2' x 2' CEILING GRID 2' x 2' PYRAMID DIFFUSER (TYPICAL OF 8) 11'-0" A.F.F. MECHANICALLY SUSPENDED 5 8" GYP. BRD. CEILING (TO PAINT) 11'-0" A.F.F. 11'-0" A.F.F. BAND HALL RENOVATION ACP - ARMSTRONG # 1894 - 24" x 24" x 3 4" w/ NRC = .60 (TEGULAR EDGE) IN 'SUPRAFINE' ML 9 16" EXPOSED TEE SYSTEM, ALSO by ARMSTRONG 5 8" GYP. BRD. DROPPED HEADWALL (TO PAINT) ON MTL STUD FRAMING B2 2 x 4 FLUORESCENT TROFFERS - SEE ELECTRICAL DOC's (TYP) A501 LED RECESSED CAN LIGHT FIXTURES - SEE ELECTRICAL DOC's EXIT LIGHTS - SEE ELECTRICAL DOC's B2 A501 LIGHT COVE STRIP FIXTURES SEE ELECTRICAL DOC's SUPPLY AIR DIFFUSERS SEE MECHANICAL DOC's 200 LONGHORN STREET VEGA, TEXAS 79092 11'-0" AFF OR AS HIGH AS POSSIBLE EX GR RETURN AIR DIFFUSERS SEE MECHANICAL DOC's LINEAR RECESSED FLUORESCENT LIGHT FIXTURE 9'-0" A.F.F. B1 A501 9'-0" A.F.F. 8'-0" A.F.F. EXHAUST GRILLES SEE MECHANICAL DOC's GYP. BRD. HEADWALL EX GR REVISIONS 9'-0" A.F.F. 8'-0" A.F.F. 9'-0" A.F.F. 9'-2" A.F.F. 9'-0" A.F.F. 9'-0" A.F.F. 9'-0" A.F.F. B1 A501 B2 D/P/S DRAWN BY A501 REVIEWED BY EX GR RO/JW 7/29/2016 DATE PROJECT NO. 14-0424.002 DRAWING NAME A1 REFLECTED CEILING PLAN 1/4" = 1'-0" 0 2' 4' 8' NORTH REFLECTED CEILING PLAN MATERIAL LEGEND CLG DETAILS NOTES A501 47 8" DOOR AND FRAME SCHEDULE DOOR 5 8" 35 8" SIZE MARK W H 201 3'-0" 7'-0" 202 PR 3'-0" 7'-0" 203 3'-0" 7'-0" 204 3'-0" 7'-0" 205 3'-0" 7'-0" 206 3'-0" 7'-0" 207 3'-0" 7'-0" 208 3'-0" 7'-0" 8" O.A. FRAME HEIGHT 2" 5 FRAME LOUVER DETAIL THK MATL EL GLZ W H MATL EL GLZ HEAD JAMB SILL FIRE RATING LABEL 1 3/4" SC WD D1 ---HM F1 -- B2/A601 A1/A601 --1 3/4" SC WD D2 ---HM F2 -- B2/A601 A1/A601 --1 3/4" SC WD D1 ---HM F1 -- B2/A601 A1/A601 --1 3/4" SC WD D1 ---HM F1 -- B2/A601 A1/A601 --1 3/4" SC WD D1 ---HM F1 -- B2/A601 A1/A601 --1 3/4" SC WD D1 ---HM F1 -- D1/A601 C1/A601 --1 3/4" SC WD D1 ---HM F1 -- D1/A601 C1/A601 --1 3/4" SC WD D1 ---HM F1 -- D1/A601 C1/A601 --- NOTES FRAME IN WD STUDS " " " " " " " " " " " " FRAME IN WD STUDS FRAME IN MTL STUDS " " " " FRAME IN MTL STUDS 57 8" ARCHITECT WALL / FIXTURE WHERE OCCURS OF S A IS E R EG C H ARL 18563 TE X ENGINEER 5 8" 47 8" 7'-0" 7'-0" 8" 5 35 8" Y L OR TE C EC T 57 8" AR B ARR E T T TA A DOOR MARK KEY ED IT 6'-0" S ST 3'-0" ER H T PROJECT B5 AT EXIST'G WALLS DOOR ELEVATIONS 1/4" = 1'-0" 3'-4" B2 0 AT EXIST'G WALLS 2' 8' 4' 6'-4" B2 A601 2" A601 2" 2" 6'-4" B1 A601 2" 2" A1 A601 A601 SIM 3'-0" A601 SIM A1 7'-2" A1 7'-2" 7'-2" 4'-2" 2" 2" 2" AT EXIST'G WALLS 2" 4" O.A. FRAME HEIGHT O.A. FRAME HEIGHT 2" 4" 1 C5 DOOR FRAME / BORROWED LIGHT ELEVATIONS 1/4" = 1'-0" 0 2' 4' 8' 200 LONGHORN STREET VEGA, TEXAS 79092 O.A. FRAME WIDTH BAND HALL RENOVATION 2" GENERAL DOOR AND WINDOW NOTES: 1. ALL DOORS TO BE 1 3/4" THICK (UON) 2. ALL STL FRAMES TO HAVE A 2" FACE DIMENSION UON, W/ 5/8" STOP. 3/4" STOP REQUIRED FOR FIRE RATED FRAMES, UON. 3. STEEL FRAME DEPTHS INDICATED IN THE DETAILS ARE NOMINAL. PROVIDE STANDARD WIDTH FRAME WITH THROAT OPENING APPROPRIATE TO WALL TYPE. REVISIONS 4. COORDINATE WITH MECH DOCUMENTS FOR DOOR UNDERCUTS AND DOOR LOUVERS, IF ANY. 5. ALL LIGHTS IN DOORS TO HAVE SAFETY GLAZING (UON). 1'-0" 41 6. NOT USED. 2" 7. FIELD VERIFY DIMENSIONS PRIOR TO FABRICATING FRAMES. 2" 2" 8. PROVIDE WD BLKG IN GYP BD WALLS BEHIND DOORS SCHEDULED TO HAVE WALL MOUNTED DOOR STOPS. (REFER HARDWARE SCHEDULE). 9. FLOOR MATERIAL CHANGES BETWEEN ROOMS TO OCCUR UNDER DOOR. 10. IF A DOOR HAS A CLOSER, THEN THE SWEEP PERIOD OF THE CLOSER SHALL BE ADJUSTED SO THAT FROM AN OPEN POSITION OF 70 DEGREES, THE DOOR WILL TAKE AT LEAST 3 SECONDS TO MOVE TO A POINT 3" (75 mm) FROM THE LATCH, MEASURED TO THE LEADING EDGE OF THE DOOR. 11. THE MAXIMUM FORCE FOR PUSHING OR PULLING OPEN A DOOR SHALL BE AS FOLLOWS: (1) FIRE DOORS SHALL HAVE THE MINIUMUM OPENING FORCE ALLOWABLE BY THE APPROPRIATE ADMINISTRATIVE AUTHORITY. (2) OTHER DOORS. (a) EXTERIOR HINGED DOORS: (RESERVED) (b) INTERIOR HINGED DOORS: 5 lbf (22.2N) (c) SLIDING OR FOLDING DOORS: 5 lbf (22.2N) DRAWN BY RKO REVIEWED BY RKO DATE 7/29/2016 14-0424.002 PROJECT NO. DRAWING NAME DOOR SCHEDULE DOOR & BORROWED LITE FRAMES DETAILS A601 S 18563 OF A TE Y L OR ST A C TA C H AR L S AR B ARR E T T EC T E IS ED IT R EG ER H T ARCHITECT TE X ENGINEER RB-1 C1 ACP-1 P-1 D1 P-3 RB-1 A771 B1 ACP-1 A1 P-1 A771 PORCELAIN TILE (PT-1) B3 RB-1 ACP-1 P-1 BELOW ACOUSTICAL PANEL B2 PORCELAIN TILE (PT-2) 200 LONGHORN STREET VEGA, TEXAS 79092 BAND HALL RENOVATION 6'-0" PROJECT WALLS: PT-1 & PT-2 SEE DETAIL A2/A701 CEILING: P-4 REVISIONS RB-1 ACP-1 P-1 E1 A181 D/P/S DRAWN BY REVIEWED BY JW A3 7/29/2016 DATE P-1 RB-1 5'-0 7/8" WALLS: PT-1 & PT-2 SEE DETAIL A2/A701 CEILING: P-4 P-1 RB-1 PROJECT NO. A771 P-1 RB-1 14-0424.002 DRAWING NAME FINISH FLOOR PLAN A2 P-3 A1 A2 FINISH FLOOR PLAN 1/4" = 1'-0" 0 2' 4' 8' TILE PATTERN 1" = 1'-0" 0 1/2' 1' 2' A701 ACOUSTICAL PANEL (ACP-2) 1'-7 1/2" FINISHED CEILING PLASTIC LAMINATE SHELF (PL-1) 1'-10" 1'-10" DIMENSIONAL ACOUSTICAL PANELCOLOR TO MATCH LONGHORN PANELS AUDITORIUM REMODEL ACOUSTICAL PANEL (ACP-1) 1'-0" 2 3/4" 5 1/2" 3'-6" TACKBOARD 4' 8' E ST DIMENSIONAL ACOUSTICAL PANELCOLOR TO MATCH LONGHORN PANELS AUDITORIUM REMODEL A DIMENSIONAL ACOUSTICAL PANELCOLOR TO MATCH LONGHORN PANELS AUDITORIUM REMODEL ACOUSTICAL PANEL (ACP-2) TE C Y L OR C H AR L S AR B A RR E T T TA R EG ED 18563 OF EC T 1'-0" ER IT IS 2' T 0 1/4" = 1'-0" 9'-0" BAND HALL 200 ELEVATION ARCHITECT S SCHLUTER DILEX TRIM H D1 FINISHED FLOOR 3'-3 1/4" PORCELAIN TILE PT-1 & PT-2 RUBBER BASE (RB-1) A 3 - 78 COMPARTMENT FOLIO STORAGE CABINETRY BY STEVENS 4'-6" 9'-0" 10'-10" 1'-0" PAINT (P-1) 6" TE X FINISHED CEILING ENGINEER 3'-5" 1'-0" 1'-6" 4" PLASTIC LAMINATE SHELF (PL-1) 10'-10" PAINT (P-1) 8'-0" ACOUSTI-GRILLE INSTRUMENT STORAGE RUBBER BASE (RB-1) PROJECT FINISHED FLOOR 2' 4' C2 8' A1 DIMENSIONAL ACOUSTICAL PANELCOLOR TO MATCH LONGHORN PANELS AUDITORIUM REMODEL A101 0 1" = 1'-0" 1/2' 2' 1' ACOUSTICAL PANEL (ACP-2) FINISHED CEILING FINISHED CEILING FINISHED CEILING ACOUSTICAL PANEL ACP-1 PAINT (P-1) B1 BAND HALL 200 ELEVATION 1/4" = 1'-0" 0 2' 4' MARKER BOARD SMART BOARD PAINT (P-1) MARKER BOARD FINISHED FLOOR ELEMENTARY MUSIC 208 ELE. 0 1/4" = 1'-0" 2' 4' RUBBER BASE (RB-1) 2'-10" 2'-10" RUBBER BASE (RB-1) B2 8' ACOUSTICAL PANEL ACP-1 4" TACKBOARD RUBBER BASE (RB-1) FINISHED FLOOR 11'-0" PAINT (P-1) 4'-0" 8'-0" 11'-0" 10'-10" 4" 1'-0" 3'-10" 3'-10" ACOUSTICAL PANEL (ACP-1) 4'-0" 4" 1'-6" PLASTIC LAMINATE SHELF (PL-1) FINISHED FLOOR ELEMENTARY MUSIC 208 ELE. B3 8' 200 LONGHORN STREET VEGA, TEXAS 79092 0 1/4" = 1'-0" MILLWORK SECTION BAND HALL RENOVATION C1 BAND HALL 200 ELEVATION 0 1/4" = 1'-0" 2' 4' 8' REVISIONS ACOUSTICAL PANEL (ACP-1) FINISHED CEILING C2 C3 PLASTIC LAMINATE SHELF (PL-1) A771 A771 A1 1/4" = 1'-0" 0 2' 4' 8' A2 PAINT (P-1) REVIEWED BY 3'-0" PLASTIC LAMINATE SHELF (PL-1) FINISHED FLOOR FINISHED FLOOR BAND HALL 200 ELEVATION DRAWN BY UNIFORM STOR. 203 ELE. 1/4" = 1'-0" 0 2' 4' 8' D/P/S JW 7/29/2016 DATE PLASTIC LAMINATE CABINETRY (PL-1) 6'-0" 5'-8" 9'-0" NEED TO VERIFY HOW MANY BAND STUDENTS FOR THE HAT/SHOE STORAGE. OR DIMENSIONS ON HAT SIZE. RUBBER BASE (RB-1) FINISHED FLOOR 4" RUBBER BASE (RB-1) FINISHED CEILING RUBBER BASE (RB-1) 3'-6" 8'-0" 9'-0" SMART BOARD FINISHED CEILING PAINT (P-1) 7'-3 1/4" 10'-10" 1 3/4" 1'-0" PAINT (P-1) 3'-6" DIMENSIONAL ACOUSTICAL PANELCOLOR TO MATCH LONGHORN PANELS AUDITORIUM REMODEL 1 1/2" ACOUSTICAL PANEL (ACP-2) 1'-8 3/4" 1'-10" DIMENSIONAL ACOUSTICAL PANELCOLOR TO MATCH LONGHORN PANELS AUDITORIUM REMODEL A3 PROJECT NO. 14-0424.002 DRAWING NAME INTERIOR ELEVATIONS UNIFORM STOR. 203 ELE. 1/4" = 1'-0" 0 2' 4' 8' A771 Digitally signed by Abbas Date: 2016.07.29 09:13:56-06'00' Digitally signed by Abbas Date: 2016.07.29 09:14:13-06'00' Digitally signed by Abbas Date: 2016.07.29 09:14:32-06'00' Digitally signed by Abbas Date: 2016.07.29 09:14:43-06'00' Digitally signed by Abbas Date: 2016.07.29 09:14:53-06'00' Digitally signed by Abbas Date: 2016.07.29 09:15:34-06'00' Digitally signed by Abbas Date: 2016.07.29 09:15:45-06'00' Digitally signed by Abbas Date: 2016.07.29 09:15:57-06'00' Digitally signed by Abbas Date: 2016.07.29 09:16:08-06'00' Digitally signed by Abbas Date: 2016.07.29 09:16:21-06'00' 1 2 3 4 5 (NOT ALL SYMBOLS APPLY TO THIS PROJECT) ELECTRICAL SYMBOL LEGEND UPDATED: 03/03/2014 AMPS, AMPERE, AMPERAGE ABOVE COUNTER ALTERNATING CURRENT AMERICANS WITH DISABILITIES ACT ABOVE FINISHED FLOOR ABOVE FINISHED GRADE AVAILABLE INTERRUPTING CURRENT ALUMINUM AMERICAN NATIONAL STANDARDS INSTITUTE AUTOMATIC TRANSFER SWITCH CONTROL AUTOMATIC TRANSFER SWITCH AUDIO/VISUAL AMERICAN WIRE GAUGE CONDUIT CIRCUIT BREAKER CLOSED CIRCUIT TELEVISION CIRCUIT CLOCK CURRENT LIMITING FUSE CONDUIT ONLY COPPER DIMMING DIRECT CURRENT DAY-LIGHTING DIAMETER EMERGENCY EMERGENCY, CRITICAL ENGINE GENERATOR EMERGENCY, LIFE SAFETY EMERGENCY, EQUIPMENT EXISTING FUTURE FIRE ALARM FIRE ALARM ANNUNCIATOR FIRE ALARM CONTROL PANEL FIRE ALARM TERMINAL CABINET FEEDER FACILITY MANAGEMENT SYSTEM GENERATOR GROUND FAULT INTERRUPTER GROUND FAULT CIRCUIT INTERRUPTER GROUND FAULT EQUIPMENT PROTECTION GROUND FAULT PROTECTION GROUND. HAND-OFF-AUTOMATIC. HORSEPOWER INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS ISOLATED GROUND THOUSAND CIRCULAR MILS KILOVOLT KILOVOLT AMPS KILOVOLT AMPS REACTIVE KILOWATT KILOWATT HOUR. LONG TIME, SHORT TIME, INSTANTANEOUS, AND GROUND FAULT PROTECTION MAXIMUM MOTOR CONTROL CENTER MINIMUM MANHOLE MIXED MEDIA MANUAL TRANSFER SWITCH MEGAVOLT AMPS NEW NOT APPLICABLE NORMALLY CLOSED NATIONAL ELECTRICAL CODE NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION NEUTRAL NATIONAL FIRE PROTECTION ASSOCIATION NOT IN CONTRACT NORMAL NEW MEXICO NORMALLY OPEN OVERHEAD POLE PUBLIC ADDRESS PHOTOCELL PHASE POWER MONITORING AND CONTROL SYSTEM REMOVED/REMOVAL ROOM CONTROLLER RIGID STEEL CONDUIT SECURITY SURGE PROTECTIVE DEVICE SWITCH TEMPORARY TELEPHONE TERMINAL BOARD TELEVISION TRANSIENT VOLTAGE SURGE SUPPRESSER TYPICAL UNDER COUNTER UNDERGROUND UNDERGROUND ELECTRIC UNDERWRITERS' LABORATORIES UNLESS OTHERWISE NOTED UNINTERRUPTABLE POWER SUPPLY VOLTS, VOLTAGE VARIABLE FREQUENCY DRIVE WALL MOUNTED WEATHERPROOF AND GFCI WEATHERPROOF TRANSFER TRANSFORMER C IG KCMIL KV KVA KVAR KW KWH LSIG MAX MCC MIN MH MM MTS MVA N N/A NC NEC NEMA B NEUT NFPA NIC NL NM NO O/H P PA PC PH PMCS R RC RSC SEC SPD SW TEMP TTB TV TVSS TYP. UC U/G UGE UL UON UPS V VFD W WG WP XFER XFMR (TRANSF) REFERENCE TAGS SYMBOL 1, 2, 3, . . = SUBFED PANEL VAV-9 1, 2, 3, . . = FLOOR LEVEL (SB=SUB-BASEMENT, B=BASEMENT, M=MEZZANINE, P=PENTHOUSE) T = TRANSFORMER DB = DISTRIBUTION BOARD MSB = MAIN SWITCH BOARD MCC= MOTOR CONTROL CENTER I = ISOLATED PANELBOARD ATS = AUTOMATIC TRANSFER SWITCH PDU = POWER DISTRIBUTION UNIT UPS = UNINTERRUPTABLE POWER SUPPLY B = BUSWAY H L SYMBOL X X = HIGH VOLTAGE PANELBOARD (480Y/277V) = LOW VOLTAGE PANELBOARD (208Y/120V) X BLANK FOR NORMAL POWER E = EMERGENCY EL = EMERGENCY-LIFE SAFETY-BRANCH EC = EMERGENCY-CRITICAL-BRANCH EQ = EMERGENCY-EQUIPMENT-BRANCH SES = SERVICE ENTRANCE SECTION NUMBER OR MAIN EMERG SWBD NUMBER EXAMPLES: A. SES1 (SERVICE ENTRANCE SECTION #1) B. 1H1A (SERVED FROM SES#1, 480/277 NORMAL, LEVEL 1, FIRST BOARD) C. 1EQH1A (SERVED FROM MAIN EMER SWBD #1, 480/277 EQUIP POWER, LEVEL 1, FIRST BOARD) RACEWAY & CONDUCTORS BRANCH CIRCUIT GENERAL INFORMATION: SYMBOL = NEUTRAL HOMERUN FROM EQUIPMENT LOCATION. THE CIRCUIT NUMBER ADJACENT TO HOMERUN INDICATES PANEL SOURCE AND INDIVIDUAL TWO OR THREE POLE CIRCUIT BREAKERS. CONDUCTOR IDENTIFICATION SYMBOL INDICATES NUMBER OF CONDUCTORS IN HOMERUN. MINIMUM #12 CONDUCTORS AND 3/4" RACEWAY PATH WILL BE PROVIDED IN HOMERUN UON. NEUTRAL MAY BE USED WHERE INDICATED ON PLAN. ALL HOMERUNS WILL INCLUDE GROUND CONDUCTOR. LA-7 LA-13 DENOTES MOUNTING HEIGHT AFF KITCHEN EQUIPMENT REFERENCE GENERAL DRAWING SYMBOLS A 6 E4 E4 DEVICE INDICATOR LETTER. "X" EQUALS DESIGNATION BELOW (TYPICAL FOR MOST SWITCH TYPES): 6 A E3 E4 E3 E4 SECTION/ELEVATION LETTER OR DETAIL NUMBER 30/3R LIGHTNING PROTECTION AIR TERMINAL ROOF VARIES OS L1A THERMOSTAT WALL +44" UON OS ENCLOSED CIRCUIT BREAKER. AMPERAGE/NEMA ENCLOSURE RATING, 3 POLE UON 30/1 NON-FUSED DISCONNECT SWITCH. AMPERAGE/NEMA ENCLOSURE RATING, 3 POLE UON 30/3R FUSED DISCONNECT SWITCH. AMPERAGE/NEMA ENCLOSURE RATING, 3 POLE UON 0/1 MOTOR STARTER. STARTER SIZE INDICATED BY NUMBER/NEMA ENCLOSURE RATING, SINGLE SPEED UON 1/30/3R COMBINATION FUSIBLE DISCONNECT SWITCH AND MOTOR STARTER. NEMA STARTER SIZE/AMPERAGE/NEMA ENCLOSURE RATING, 3 POLE UON 5 MOTOR. NUMBER INDICATES HORSEPOWER RATING FOR 1HP AND LARGER F MOTOR. "F" INDICATES FRACTIONAL HORSEPOWER CEILING MOUNTED OCCUPANCY SENSOR; TYPE AS INDICATED ON PLANS DAY-LIGHTING SENSOR; TYPE AS INDICATED ON PLANS ROOM CONTROLLER; TYPE AS INDICATED ON PLANS DL RC VARIES VFD 300 400 X X X 300 400 300 400 UPS-A X X UT AUTOMATIC TRANSFER SWITCH. DASHED LINES INDICATE CLEARANCES. ATS-1 G DEMOLITION DESCRIPTION NOTES DASHED SYMBOL INDICATES EXISTING DEVICE OR EQUIPMENT TO BE REMOVED NORTH R REMOVE EXISTING RACEWAY IN ALL ACCESSIBLE AREAS. CAPPED AND ABANDONED IF IN UNACCESSIBLE AREA SOLID SYMBOL, LIGHTER IN COLOR INDICATES EXISTING DEVICE OR EQUIPMENT TO REMAIN 80' SCALE BAR OR MATCH ARCHITECT'S EX S CC GROUND BAR EXISTING CONDUIT TO BE REUSED REFER TO DEMOLITION PLANS FOR ADDITIONAL INFORMATION PHOTOELECTRIC SMOKE DETECTOR IONIZATION SMOKE DETECTOR I R/F COMBINATION RATE OF RISE / FIXED TEMPERATURE F FIXED TEMERATURE; TEMPERATURE AS NOTED ON PLANS OR SPECIFICATIONS VARIES X BEAM TRANSMITTER BT BEAM RECEIVER UNDER FLOOR SMOKE DETECTOR U FIRE/SMOKE DAMPER AS DETAILED PS PRESSURE SWITCH TS TAMPER SWITCH FS FLOW SWITCH PIV POST INDICATOR VALVE +44" UON WALL M MAGNETIC DOOR HOLDER R CONTROL RELAY DRAWOUT CIRCUIT BREAKER TRIP SETTING FRAME SIZE MEDIUM VOLTAGE DRAWOUT CIRCUIT BREAKER TRIP SETTING FRAME SIZE 208Y/120V UTILITY OR FACILITY TRANSFORMER CONNECTION CABINET (UTILITY METER MOUNT) PM PRIMARY SITE METER ENCLOSURE ME METER ENCLOSURE. EITHER ON BUILDING OR ON UTILITY EQUIPMENT T1A 75kVA K-4 480V CT CT ENCLOSURE. EITHER ON BUILDING OR ON UTILITY EQUIPMENT ENGINE GENERATOR TP TELECOMMUNICATION PEDESTAL TVP TELEVISION PEDESTAL SEE PLANS AT DUCT SEE PLANS PIPE VARIES ENGINEER 300A DISCONNECT SWITCH. "300A" DENOTES AMPERAGE RATING 300A FUSE. "300A" DENOTES AMPERAGE RATING SYMBOL CEILING SURFACE Jxx DESCRIPTION 4 PORT FLOOR BOX WITH A/V. REFER TO J-BOX SCHEDULE ON 600 SERIES SHEETS. B 2 PORT VOICE\DATA OUTLET ROUGH-IN ONLY WALL W TELEPHONE OUTLET WALL MOUNTED KW KILOWATT METER +18" UON +18" UON WALL +44" UON WALL +84" UON WALL +108 UON WALL SEE PLANS A/V JUNCTION BOX. REFER TO J-BOX SCHEDULE ON 600 SERIES SHEETS. A/V J- BOXES STACKED VERTICALLY. REFER TO J-BOX SCHEDULE ON 600 SERIES SHEETS. WALL SEE PLANS C S COMBINATION CLOCK/SPEAKER. MOUNTED ABOVE AND CENTER TO WRITING/TACK BOARD WALL SEE PLANS VC VOLUME CONTROL FOR PAGING LOUDSPEAKER WALL SEE PLANS VP VIDEO PROJECTOR REFER TO PLANS S CEILING SPEAKER: LOCAL SOUND SYSTEM IC INTERCOM CALL SWITCH INTERCOM MASTER STATION S COMMUNICATION HORN COMMUNICATION BELL S WALL SPEAKER LD J Jx Jx J Jx J PA DURESS ALARM PUSHBUTTON LOCK DOWN PUSHBUTTON CEILING FLUSH REVISIONS J-HOOK ROUTING PATH 2 PORT CEILING MOUNTED VOICE/DATA OUTLET Jx J SEE PLANS CEILING MOUNTED A/V JUNCTION BOX. REFER TO J-BOX SCHEDULE ON 600 SERIES SHEETS. SECURITY MOUNTING LOC. HT. DESCRIPTION ELECTRONIC METER K1 KIRK KEY INTERLOCK No.1 R1 RELAY No.1 AS AMMETER SWITCH INTERIOR SECURITY CAMERA AMMETER INTERIOR SECURITY CAMERA 180° VOLTMETER SWITCH INTERIOR SECURITY CAMERA 360° KEY PAD EXTERIOR SECURITY CAMERA WALL, UON +44" UON VARIES SEE PLANS VARIES SEE PLANS GLASS BREAK DETECTOR WINDOW SEE PLANS MD MOTION DETECTOR CEILING SEE PLANS DS DOOR SWITCH MOTOR CONNECTION ES ELECTRIC STRIKE DOOR SEE PLANS UPS M MAGNETIC LOCK VOLTMETER G DELTA CONNECTED WYE CONNECTED - DRAWN BY REVIEWED BY CARD READER. M KP ABOVE CEILING WIRELESS ACCESS POINT SYMBOL CR 100 % CONSTRUCTION DOCUMENTS CEILING SPEAKER: INTERCOM SYSTEM SURGE ARRESTOR SURGE PROTECTIVE DEVICE VARIES SEE PLANS CABLE TRAY FOR COMMUNICATIONS TRANSFER SWITCH. SEE PLANS FOR TYPE OF SWITCH V FLOOR WALL S IC GROUND CONNECTION SPD SEE PLANS MOUNTING LOC. HT. 2 PORT VOICE\DATA OUTLET SHUNT TRIP OPERATOR VS VARIES 4 PORT FLOOR BOX WITH POWER AND DATA GROUND FAULT PROTECTION ST PROJECT SPECIAL SYSTEMS Jx J CURRENT TRANFORMER, NUMBER "3000/5" DENOTES RATIO. G A EG UNDER FLOOR 4600 C Montgomery Blvd. NE Albuquerque, NM 87109 505.883.4111 www.bpce.com ADDRESSABLE/SUPERVISED RELAY R PAD MOUNTED SWITCH HH VARIES REMOTE ALARM INDICATING LIGHT TRANSFORMER. TRANSFORMER NAME, TRANSFORMER kVA RATING, PRIMARY VOLTAGE AND WIRING CONFIGURATION, SECONDARY VOLTAGE, K RATING (IF APPLICABLE) UNDERGROUND UTILITY AND OR SYSTEM DISTRIBUTION. HAND HOLE - POWER OR COMMUNICATION AS INDICATED ON PLANS CEILING OR WALL Digitally signed by William D. Herbst Date: 2016.07.29 11:03:39-06'00' MONITOR MODULE MM WAP MANHOLE - POWER OR COMMUNICATION AS INDICATED ON PLANS SURFACE BR J OVERHEAD UTILITY AND OR SYSTEM DISTRIBUTION. MH CEILING RATE OF RISE ONLY DA N/A DESCRIPTION N = NEW EX = EXISTING VARIABLE FREQUENCY DRIVE +80" UON P B P = ELECTRICAL PRIMARY S = ELECTRICAL SECONDARY T = TELECOMMUNICATION TV = TELEVISION E = EMERGENCY POWER ATSC = AUTOMATIC TRANSFER SWITCH CONTROL DRY TYPE TRANSFORMER (LESS THAN 15kVA), WITH NO EQUIPMENT TAG. SIZE, TYPE AND LOCATION NOTED ON PLANS. WALL BELL (GONG) B CIRCUIT BREAKER; TRIP SETTING/FRAME SIZE OR NO. OF POLES. SETTINGS AND PROTECTION AS NOTED ON PLANS 3PH = THREE PHASE 1PH = SINGLE PHASE DRY TYPE TRANSFORMER (15kVA OR ABOVE), WITH EQUIPMENT TAG (TAG INSIDE OR OUTSIDE, DEPENDING ON SIZE). IN MOST CASES, ACTUAL SIZE SHOWN ON PLANS (ELECTRICAL ROOMS). +44" STROBE LIGHT ONLY ICM DISTRIBUTION POLE FOR OVERHEAD ELECTRICAL OR COMMUNICATIONS AS INDICATED ON PLAN. UNINTERRUPTABLE POWER SUPPLY. DASHED LINES INDICATE CLEARANCES. CHIME NOTIFICATION VARIES MAIN SWITCHBOARD. DASHED LINES INDICATE CLEARANCES. SYMBOL WALL DESCRIPTION 3000/5 MOTOR CONTROL CENTER. DASHED LINES INDICATE CLEARANCES. T C ONE-LINE DIAGRAM SYMBOL DESCRIPTION MCC T1A SPEAKER NOTIFICATION WALL MOUNTED OCCUPANCY SENSOR; TYPE AS INDICATED ON PLANS UTILITIES SYMBOL 1" = 40'-0" VARIES SEE PLANS VARIES SEE PLANS N/A FIRE ALARM RACEWAY DRAWING NUMBER WHERE TAKEN 40' X DISTRIBUTION BOARD. DASHED LINES INDICATE CLEARANCES. DRAWING NUMBER WHERE DETAILED NORTH ARROW OR MATCH ARCHITECT'S LOW VOLTAGE SWITCH CONTROL. REFER TO PLANS FOR TYPE. CODE SIZE PULLBOX (OR AS SIZED ON PLAN) CB DATA RACEWAY VOICE/DATA COMBINATION RACEWAY SURFACE MOUNTED PANELBOARD. DASHED LINES INDICATE CLEARANCES. S COMBINATION SPEAKER AND CHIME NOTIFICATION SPEAKER/HORN WITH STROBE LIGHT a= PHOTOCELL P T VARIES SEE PLANS PUSHBUTTON (EMERGENCY POWER OFF - EPO) CODE SIZE JUNCTION BOX - NO TAG INDICATES SINGLE POLE TOGGLE SWITCH VARIES SEE PLANS SMALL CASE LETTER DENOTES SWITCHING CONTROL 2= DOUBLE POLE TOGGLE SWITCH 3= THREE-WAY TOGGLE SWITCH 4= FOUR-WAY TOGGLE SWITCH P= PILOT LIGHT TOGGLE SWITCH M = MOMENTARY CONTACT SWITCH K= KEY OPERATED SWITCH WP = WEATHERPROOF TOGGLE SWITCH T= MANUAL MOTOR STARTER SWITCH WITH THERMAL OVERLOAD PROTECTION D = DIMMER SWITCH J PC GROUNDING CONDUCTOR CABLE TRAY - POWER AND TELECOMMUNICATIONS TELECOMMUNICATIONS RACEWAY FLUSH MOUNTED PANELBOARD. DASHED LINES INDICATE CLEARANCES. HORN NOTIFICATION R EXTERIOR DB H1A F DUCT DETECTOR POTENTIAL TRANSFORMER. SECTION/ELEVATION LETTER OR DETAIL NUMBER DRAWING NUMBER WHERE DETAILED +18", UON SPECIAL PURPOSE RECEPTACLE. NEMA CONFIGURATION AND AMPERAGE AS NOTED ON PLANS WALL MOUNTED CODE SIZE J-BOX WALL FIRE ALARM ANNUNCIATOR PANEL PULL STATION EMERGENCY BATTERY PACK LUMINAIRE (BUG-EYE/FROG-EYE) X EQUIPMENT MSB DOUBLE FACE EXIT LUMINAIRE. SHADED SIDE INDICATES FACE SIDE. PROVIDE DIRECTIONAL ARROW(S) AS INDICATED ON PLANS WALL EMERGENCY DOUBLE DUPLEX (QUADPLEX) RECEPTACLE BUSWAY SYMBOL CEILING WALL, UON FIRE ALARM TERMINAL CABINET (EQUIPMENT NAMING CONVENTION PER PLANS) EXIT LUMINAIRE. SHADED SIDE INDICATES FACE SIDE. PROVIDE DIRECTIONAL ARROW(S) AS INDICATED ON PLANS X J CONDUIT STUBBED AND CAPPED T D V/D FA WALL DOUBLE HEAD, POLE MOUNTED LUMINAIRE CONDUIT TURNS B G SURFACE EMERGENCY DUPLEX RECEPTACLE COMBINATION POWER/COMMUNICATION POLE. CONFIGURATION AS NOTED ON PLANS EXPOSED RACEWAY BETWEEN DEVICES AND OR EQUIPMENT ON WALLS OR CEILINGS UP WALL STRIP LUMINAIRE CEILING DOUBLE DUPLEX (QUADPLEX) RECEPTACLE CEILING TRACK MOUNTED LUMINAIRES SIMPLEX RECEPTACLE FATC F LINEAR DIRECT/INDIRECT LUMINAIRE. CABLE OR STEM MOUNTED WALL MOUNTED LUMINAIRES FLUSH FIRE ALARM CONTROL PANEL FAA DOWN LIGHT LUMINAIRE; CEILING MOUNTED CEILING FACP FIREMAN'S TELEPHONE OUTLET VARIES COMBINATION POWER/COMMUNICATION IN CEILING OUTLET. CONFIGURATION AS INDICATED ON PLANS DUPLEX RECEPTACLE VARIES MOUNTING LOC. HT. DESCRIPTION RECESSED MOUNTED LUMINAIRE SURFACE MOUNTED LUMINAIRE. LUMINAIRE TYPE AS INDICATED ON PLANS CEILING MOUNTED EMERGENCY DOUBLE DUPLEX (QUADPLEX) RECEPTACLE MULTI-OULET ASSEMBLY (SURFACE MOUNTED RACEWAY) UNDERGROUND RACEWAY BETWEEN DEVICES AND OR EQUIPMENT MEDICAL EQUIPMENT REFERENCE 0 10' 20' X CONCEALED RACEWAY BETWEEN DEVICES AND OR EQUIPMENT IN WALLS OR IN CEILING SPACE DOWN CEILING MOUNTED EMERGENCY DUPLEX RECEPTACLE MOUNTING LOC. HT. DESCRIPTION HATCHING INDICATES EMERGENCY LIGHTING. HATCH WILL BE MODIFIED FOR EACH LUMINAIRE TYPE. EMERGENCY LUMINAIRE DESIGNATED WITH "E" IN TYPE DESIGNATION. FLOOR SYMBOL SINGLE HEAD, POLE MOUNTED LUMINAIRE HOMERUN FROM EQUIPMENT LOCATION. THE CIRCUIT NUMBER ADJACENT TO HOMERUN INDICATES PANEL SOURCE AND INDIVIDUAL SINGLE POLE CIRCUIT BREAKER (S). SYMBOL REPRESENTS A MULTI-BRANCH CIRCUIT. NUMBER OF CONDUCTORS IN HOMERUN WILL INCLUDE A SEPERATE NEUTRAL FOR EACH CIRCUIT PHASE CONDUCTOR. MINIMUM #12 CONDUCTORS AND 3/4" RACEWAY PATH WILL BE PROVIDED IN HOMERUN UON. ALL HOMERUNS WILL INCLUDE GROUND CONDUCTOR. LA-5,7,9 X CEILING MOUNTED DOUBLE DUPLEX (QUADPLEX) RECEPTACLE X HOMERUN FROM EQUIPMENT LOCATION. THE CIRCUIT NUMBER ADJACENT TO HOMERUN INDICATES PANEL SOURCE AND INDIVIDUAL SINGLE POLE CIRCUIT BREAKER (S). CONDUCTOR IDENTIFICATION SYMBOL INDICATES NUMBER OF CONDUCTORS IN HOMERUN. MINIMUM #12 CONDUCTORS AND 3/4" RACEWAY PATH WILL BE PROVIDED IN HOMERUN UON. ALL HOMERUNS WILL INCLUDE GROUND CONDUCTOR. LA-1,3 CEILING MOUNTED DUPLEX RECEPTACLE X = SWITCH LEG LA-1 X X CONDUCTOR IDENTIFICATION SYMBOLS. REFER TO PLANS FOR COMBINATION USE. CONDUCTOR IDENTIFICATION MOSTLY USED IN HOMERUN LOCATION, BUT CAN ALSO BE USED IN BRANCH CIRCUITING WHERE APPLIED. GROUND CONDUCTORS WILL BE INSTALLED IN ALL RACEWAYS WHETHER SHOWN OR NOT. = HOT/PHASE COMBINATION DUPLEX RECEPTACLE AND COMMUNICATIONS FLOORBOX. DEVICE CONFIGURATION AS INDICATED ON PLANS. X DESCRIPTION = GROUND X X BRANCH CIRCUITS FROM OVERCURRENT PROTECTION (20A) TO FURTHEST DEVICE SHALL NOT EXCEED 75 FEET FOR #12AWG COPPER AND 150 FEET FOR #10AWG COPPER; MEASURED ALONG CONDUCTORS ROUTING PATH. BRANCH CIRCUITS EXCEEDING 150 FEET WILL BE SIZED SO THAT VOLTAGE DROP DOES NOT EXCEED 5%. IN FLOOR DUPLEX RECEPTACLE. CONFIGURATION AS INDICATED ON PLANS IN FLOOR DOUBLE DUPLEX (QUADPLEX) RECEPTACLE. CONFIGURATION AS INDICATED ON PLANS IN FLOOR EMERGENCY DUPLEX RECEPTACLE. CONFIGURATION AS INDICATED ON PLANS IN FLOOR EMERGENCY DOUBLE DUPLEX (QUADPLEX) RECEPTACLE. CONFIGURATION AS INDICATED ON PLANS X SYMBOL MOUNTING LOC. HT. DESCRIPTION X MECHANICAL EQUIPMENT REFERENCE +44" A BLANK FOR NORMAL POWER G = GFCI RATED IG = ISOLATED GROUND T = TAMPERPROOF WG = WEATHERPROOF AND GFCI WP = WEATHERPROOF (IN-USE COVER) CL = CLOCK TV = TELEVISION A, B, C, = SEQUENCE OF PANELS OF THIS TYPE DEFINITION KEYED NOTE REFERENCE DEVICE INDICATOR LETTER. "X" EQUALS DESIGNATION BELOW (TYPICAL FOR MOST RECEPTACLE TYPES): 200 LONGHORN STREET VEGA, TEXAS 79092 A AC A/C ADA AFF AFG AIC AL ANSI ATSC ATS A/V AWG C CB CCTV CKT CL CLF CO CU D DC DL DIA E EC EG EL EQ EX FUT FA FAA FACP FATC FDR FMS GEN GFI G OR GFCI GFEP GFP GND HOA HP IEEE FIRE ALARM BAND HALL RENOVATION D DEFINITION LIGHTING REFER TO LUMINAIRE SCHEDULE FOR ALL LUMINAIRE TYPES WHETHER WALL MOUNTED OR CEILING MOUNTED. REFER TO LIGHTING SCHEDULE ABBREV. DEVICES EQUIPMENT NAMING CONVENTION ABBREVIATIONS 7/29/2016 DATE PROJECT NO. 14-0424.002 DRAWING NAME ELECTRICAL LEGEND GENERATOR VFD 5 UPS VFD CONNECTION SHEET NO. E-001 OF 1 2 3 4 5 1 2 3 4 5 GENERAL NOTES A. BEFORE COMMENCEMENT OF ANY WORK, COORDINATE AND LOCATE ALL UTILITIES, OVERHEAD AND UNDERGROUND. REFER TO SHEET SERIES "A", "C", "L", "M", AND "P" UTILITY PLANS. WHERE OTHER UTILITIES MAYBE SHOWN ON THIS PLAN THEY ARE FOR REFERENCE ONLY. COORDINATE ACTUAL UTILITY LOCATIONS PRIOR TO COMMENCEMENT OF ANY WORK. B. CONTRACTOR WILL REFER TO ARCHITECT PLANS AND SPECIFICATIONS FOR CONSTRUCTION SEQUENCE OF THIS PHASE OF THE PROJECT. ANY AND ALL MODIFICATIONS TO ANY BUILDING OR UTILITY WILL BE COORDINATED PRIOR TO COMMENCEMENT OF ANY WORK. BUILDINGS OR PORTIONS THERE OF THAT WILL NEED TO STAY OPERATIONAL DURING CONSTRUCTION WILL BE MODIFIED TO DO SO. D S01 W M 4600 C Montgomery Blvd. NE Albuquerque, NM 87109 505.883.4111 www.bpce.com S07 ENGINEER S09 SHEET KEYED NOTES S08 S03 S01. FIRE ALARM CONTROL PANEL (FACP), INSTALLED IN PHASE 1. S05 PROJECT S02. EXISTING 2000A (208V /120V) SWITCHBOARD; 11MDP. REFER TO SHEET E-601 FOR ADDITIONAL INFORMATION. S04 S03. DISTRIBUTION FROM FIRE ALARM CONTROL PANEL INSTALLED IN PHASE 1 TO BAND HALL RENOVATION. REFER TO FIRE ALARM DIAGRAM ON SHEET E-602 FOR ADDITIONAL INFORMATION. ROUTE UNDERGROUND. S02 S10 BAND HALL RENOVATION S07 S07 Digitally signed by William D. Herbst Date: 2016.07.29 11:04:01-06'00' S04. PROVIDE A CONDUIT FOR SECONDARY POWER FROM EXISTING SWITCHBOARD TO BAND HALL RENOVATION. REFER TO ONE-LINE DIAGRAM ON SHEET E-601 FOR ADDITIONAL INFORMATION. ROUTE UNDERGROUND. S09 S06 S05. PANEL LOCATION FOR BAND ROOM. REFER TO SHEET EP-101 AND E-601 FOR ADDITIONAL INFORMATION. S06. FIRE ALARM TERMINAL CABINET (FATCBR) IN BAND ROOM. REFER TO SHEET ET-101 AND E-602 FOR ADDITIONAL INFORMATION. S11 S07. ROUTE CONDUIT FROM FACP OVERHEAD IN CEILING SPACE AND OUT BUILDING AT POINT INDICATED. S08. ROUTE CONDUIT SURFACE TO EXTERIOR WALL TO A POINT WHERE CONDUIT WILL GO UNDERGROUND. SEE NOTE S03 AND S04. THIS IS FOR BOTH FIRE ALARM AND SECONDARY POWER TO BAND HALL. B S09. IN DASH AREA CONTRACTOR WILL INFORM HIMSELF AND COORDINATE WITH ALL OTHER UTILITIES BEING INSTALLED IN OTHER PHASES OF CONSTRUCTION. S10. REMOVE EXISTING PANEL AND FEEDER BACK TO PANEL SERVICE IN MAINTENANCE SHOP. RACEWAY TO BE REMOVED WHERE POSSIBLE. ABANDON IN PLACE WHERE NECESSARY. S11. CONNECTION TO EXISTING SERVER ROOM. ROUTE (1)4" CONDUIT FROM NEW CABINET IN BAND ROOM UNDERGROUND TO EXISTING MAIN BUILDING. TRANSITION CONDUIT UP THE SIDE OF EXISTING BUILDING TO POINT ABOVE DROP CEILING IN EXISTING BUILDING. HORIZONTALLY PENETRATE WALL WITH CONDUIT AND CONTINUE 4" CONDUIT TO EXISTING SERVER ROOM IN EAST WING. PROVIDE 4" 3-CELL MAXCELL INNERDUCT TO SPAN BOTH ENDS. 200 LONGHORN STREET VEGA, TEXAS 79092 C 100 % CONSTRUCTION DOCUMENTS REVISIONS DRAWN BY BEL REVIEWED BY JMM 7/29/2016 DATE PROJECT NO. 14-0424.002 DRAWING NAME A ELECTRICAL SITE PLAN A2 ELECTRICAL SITE PLAN 0 1" = 20'-0" 2' 4' 8' NORTH SHEET NO. ES101 OF 1 2 3 4 5 1 2 3 4 5 GENERAL NOTES A. REFER TO ARCHITECTURAL DEMOLITION SHEETS "AD" SERIES AND SPECIFICATIONS FOR ADDITIONAL DEMOLITION REQUIREMENTS. D02 D D02 D02 D01 11S D02 4600 C Montgomery Blvd. NE Albuquerque, NM 87109 505.883.4111 www.bpce.com D02 ENGINEER C SHEET KEYED NOTES D02 PROJECT D02 BAND HALL RENOVATION D02. REMOVE ALL ELECTRICAL POWER CONNECTION, ELECTRICAL EQUIPMENT FOR MECHANICAL EQUIPMENT, LIGHTING AND LIGHTING CONTROL AND ALL GENERAL POWER DEVICES. PLUS ASSOCIATED RACEWAY AND CONDUCTORS BACK TO PANEL SOURCE (11S). D02 B B2 BAND HALL - DEMOLITION FLOOR PLAN 0 1/4" = 1'-0" 2' 4' 8' NORTH 200 LONGHORN STREET VEGA, TEXAS 79092 D01. REMOVE EXISTING PANEL AND FEEDER BACK TO PANEL SERVICE IN MAINTENANCE SHOP. RACEWAY TO BE REMOVED WHERE POSSIBLE. ABANDON IN PLACE WHERE NECESSARY. Digitally signed by William D. Herbst Date: 2016.07.29 11:04:12-06'00' 100 % CONSTRUCTION DOCUMENTS REVISIONS DRAWN BY BEL REVIEWED BY JMM 7/29/2016 DATE PROJECT NO. 14-0424.002 DRAWING NAME A BAND HALL DEMOLITION FLOOR PLAN SHEET NO. ED101 OF 1 2 3 4 5 1 2 3 4 5 GENERAL NOTES L09 A. ALL EXIT SIGNS WILL BE CONNECTED TO CIRCUIT SERVING THE ROOM THEY ARE LOCATED IN AND FROM NO OTHER CIRCUIT. B. REFER TO SHEET E-701 FOR ELECTRICAL LUMINAIRE SCHEDULE. FL 11S-1 3b 3a E PANEL 11S L01 D ARaD C. REFER TO SHEET EP101 FOR ELECTRICAL EQUIPMENT LAYOUT. L01 a,b ARaDE ARaD a,b ARaD a,b ARaD a,b ARaD a,b ARaD b a a,b ARaDE ENSEMBLE 201 D. REFER TO DETAIL B1 ON THIS SHEET FOR LUMINAIRE MOUNTING. E. REFER TO ARCHITECTURAL SHEETS FOR ADDITIONAL CEILING GRID MOUNTING SUPPORT INFORMATION. ALL LUMINAIRES WILL BE SECURELY SUPPORTED SEPARATELY FROM LUMINAIRES TO CEILING STRUCTURE. F. ALL LUMINAIRES AND DEVICES IN THE DASHED AREA WILL BE CONNECTED TO CIRCUIT INDICATED UNLESS OTHERWISE NOTED. ARaDE L05 L05 A4 E-603 a,b L05 L05 a,b ARaD ARaD ELEMENTARY MUSIC 208 a,b ARaD a,b ARaDE a,b ARaD a,b ARaD a,b ARaD 11S-5 BAND HALL 200 11S-3 4600 C Montgomery Blvd. NE Albuquerque, NM 87109 505.883.4111 www.bpce.com L01 ARaDE a b a,b ARaD a,b ARaDE a,b ARaD ENGINEER b a a,b ARaD L01 C ARaDE L05 GIRLS 207 C6LE C6L L05 L02 a,b L05 L01. TWO SWITCHES, SWITCH TYPE AS INDICATED. ONE SWITCH (A) WILL CONTROL INNER LAMP(S) AND ONE SWITCH WILL CONTROL OTHER LAMPS OF LUMINAIRE IN ROOM. C6L K E L05 11S-7 L08 BVb a,b ARaDE C6L BVbE L01 BVb a,b ARaD L01 a,b ARaD L05 BOYS 206 K C6LE L02 C6L a,b ARaD L02 L05 C6LE E a,b ARaD OFFICE 205 MUSIC STOR. 204 a,b ARaDE UNIFORM STOR. 203 L03 ARb ARb 11S-5 PROJECT L03. WALL-MOUNTED OCCUPANCY SENSOR, WATT STOPPER PW-100 OR APPROVED EQUAL. LOCATE PER MANUFACTURER'S RECOMMENDATIONS. SHOWN HERE FOR BID PURPOSES. SWITCH ASSOCIATED WILL PROVIDE ON/OFF CONTROL. PERCUSSION 202 L03 Digitally signed by William D. Herbst Date: 2016.07.29 11:04:21-06'00' L02. REUSE OUTLET REPLACE DEVICE. ONE SWITCH, SWITCH TYPE AS INDICATED, WILL CONTROL THE LUMINAIRES IN ROOM. a,b ARaD b a C6L C6L L08 a,b ARaD 3b 3a 11S-3 BVbE C6L SHEET KEYED NOTES L05. CEILING-MOUNTED OCCUPANCY SENSOR, WATT STOPPER DT-355 OR APPROVED EQUAL. LOCATE PER MANUFACTURER'S RECOMMENDATIONS. SHOWN HERE FOR BID PURPOSES. L08. REFER TO DETAIL B1 ON SHEET A-501 FOR MOUNTING DETAIL FOR THESE LUMINAIRES. a,b ARaD L09. REMOVE EXISTING LUMINAIRE AND REPLACE WITH NEW LUMINAIRE. B B2 BAND HALL - LIGHTING FLOOR PLAN 0 1/4" = 1'-0" 2' 4' 8' NORTH 100 % CONSTRUCTION DOCUMENTS REVISIONS NO. 12 GAUGE WIRE HANGER TO BUILDING FRAMING OR STRUCTURAL MEMBERS. SUSPEND FROM ALL FOUR CORNERS OF THE LUMINAIRE CEILING SYSTEM HANGER WIRES (TYP.) 200 LONGHORN STREET VEGA, TEXAS 79092 ARaD a,b ARaD a,b ARaD BAND HALL RENOVATION ARaD DRAWN BY CEILING SYSTEM HANGER WIRES (TYP.) BEL REVIEWED BY JMM 7/29/2016 DATE PROJECT NO. 14-0424.002 DRAWING NAME A LAY-IN LUMINAIRE A1 SEISMIC FIXTURE CLAMPS: REQUIRED AT ALL (4) LUMINAIRE CORNERS WITH 2#10 SELF-TAPPING SCREWS. AGI SEISMIC PRODUCTS OR EQUAL. AC 184 COMPLIANT. BAND HALL LIGHTING FLOOR PLAN LUMINAIRE SUPPORT DETAIL SHEET NO. NO SCALE EL101 OF 1 2 3 4 5 1 2 3 4 5 GENERAL NOTES P03 F01 A. GFCI RECEPTACLES WILL BE INSTALLED AT ALL LOCATIONS AS REQUIRED BY THE LATEST VERSION OF NEC, STATE AND LOCAL CODES WHETHER INDICATED ON PLANS OR NOT. SOME LOCATIONS WILL BE WITHIN 6'-0" OF SINKS, EXTERIOR DOORS AND WET LOCATIONS. ALL EXTERIOR RECEPTACLE LOCATIONS WILL BE GFCI RATED AND WEATHERPROOF. B. ALL DEVICES IN THE DASHED AREA WILL BE CONNECTED TO THE PANEL INDICATED UNLESS OTHERWISE NOTED. 11S-15,17,19 8 11S 10 F02 18 P06 3,6 D WG 11S-24 8 P05 4 AC-03 G 10 ENSEMBLE 201 P02 32 ELEMENTARY MUSIC 208 P05 10 AC-02 P06 8 WG 11S-24 BAND HALL 200 4600 C Montgomery Blvd. NE Albuquerque, NM 87109 505.883.4111 www.bpce.com 4 P05 AC-01 ENGINEER 8 F04 2 P06 20 F04 11S-21,23,25 WG 11S-24 8 P04 10 C SHEET KEYED NOTES Digitally signed by William D. Herbst Date: 2016.07.29 11:04:32-06'00' 11S-9,11,13 P01 PERCUSSION 202 11S-29,31 G 12 P07 G 30 2,4 6 P04. ROUTE CONDUIT UNDERGROUND TO EXTERIOR WALL THEN UP WALL TO LEVEL IN CEILING SPACE IN BUILDING, THEN OVER TO PANEL 11S-27 F P01 6 EF-1 18 T 16 P05. REFER TO SHEET E-702 FOR ELECTRICAL CONNECTION SCHEDULE FOR MECHANICAL EQUIPMENT. REFER TO SHEET M-701 FOR MECHANICAL / ELECTRICAL INFORMATION. 18 11S-22 16,18 FATCBR OFFICE 205 16,20 F03 MUSIC STOR. 204 P06. UNIT MOUNTED GFCI WEATHERPROOF RECEPTACLE. CONTRACTOR WILL PROVIDE CIRCUIT INDICATED TO THIS DEVICE. UNIFORM STOR. 203 P07. MOUNT DEVICE IN CONJUNCTION WITH EQUIPMENT. COORDINATE FINAL LOCATION PRIOR TO COMMENCEMENT OF ANY WORK. 26,28 20 P02. DEVICE IS FOR SHORT THROW PROJECTOR SCREEN. REFER TO SHEET SERIES “T” FOR SWITCH LOCATION AND ADDITIONAL INSTALLATION INFORMATION. P03. REFER TO SHEET ES101 AND E-601 FOR ADDITIONAL INFORMATION. P02 11S-14 12 G PROJECT P07 F01. REFER TO SHEET ES101 AND E-602 FOR ADDITIONAL INFORMATION. B CIRCUITS FOR GENERAL POWER WITHIN DASHED AREA ARE FED FROM PANEL 11S. F02. TO FIRE ALARM TERMINAL CABINET (FATCBR); OVERHEAD DISTRIBUTION. B2 F03. REFER TO FIRE ALARM RISER DIAGRAM ON SHEET E-602 FOR ADDITIONAL INFORMATION. BAND HALL - POWER FLOOR PLAN 0 1/4" = 1'-0" 2' 4' 8' 200 LONGHORN STREET VEGA, TEXAS 79092 P05 EWH-1 GIRLS 207 BOYS 206 6 BAND HALL RENOVATION P04 P01. MOUNT DEVICE 6" ABOVE COUNTER TOP BACK SPLASH, TABLE TOP OR SINK. RECEPTACLE WILL BE GFCI RATED. F04. PROVIDE DUCT DETECTOR FOR UNITS 2000 CFM OR GREATER FOR INSTALLATION BY MECHANICAL INSTALLER. NORTH 100 % CONSTRUCTION DOCUMENTS REVISIONS DRAWN BY BEL REVIEWED BY JMM 7/29/2016 DATE PROJECT NO. 14-0424.002 DRAWING NAME A BAND HALL POWER FLOOR PLAN SHEET NO. EP101 OF 1 2 3 4 5 1 2 3 4 5 GENERAL NOTES PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ. B. CONTRACTOR TO VERIFY ALL CABLE COUNTS AND NUMBER OF PATCH PANELS REQUIRED. C. ALL CABLING TO BE PLENUM RATED THROUGHOUT BUILDING. D. ALL COMMUNICATIONS CABLING TO MEET OR EXCEED CAT6 STANDARDS. E. TELECOMMUNICATIONS OUTLETS TO BE MOUNTED AT +18" A.F.F. (BOTTOM OF BOX) UNLESS OTHERWISE NOTED. FOR EXAMPLE, DEVICES SPECIFIED AT +18" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR POWER RECEPTACLES AND TELECOMMUNICATIONS OUTLETS. DEVICES SPECIFIED AT +48" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR LIGHT SWITCHES ETC. F. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL, THIN-WALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED. UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR PATHWAYS INDICATED. ALL CONDUITS ARE TO BE, AT A MINIMUM 1" TRADE SIZE, UNLESS OTHERWISE NOTED. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL. T09 T05 T09 A. T10 D ENSEMBLE 201 T09 T14 T07 ELEMENTARY MUSIC 208 T09 T13 4600 C Montgomery Blvd. NE Albuquerque, NM 87109 505.883.4111 www.bpce.com BAND HALL 200 ENGINEER T09 C SHEET KEYED NOTES T06 F03. REFER TO FIRE ALARM RISER DIAGRAM ON SHEET E-602 FOR ADDITIONAL INFORMATION. T13 Digitally signed by William D. Herbst Date: 2016.07.29 11:04:43-06'00' PROJECT PERCUSSION 202 T04 T08 T14 T02. WALL MOUNTED COMBINATION CLOCK/SPEAKER FOR DISTRIBUTED INTERCOM/PAGING AND CLOCK SYSTEM. COORDINATE SIGNAL PULL BOX TYPE AND ROUGH-IN LOCATION WITH EQUIPMENT INSTALLER PRIOR TO COMMENCING ANY WORK. REFER TO SPECIFICATIONS SECTION 27 5123 FOR ADDITIONAL REQUIREMENTS. TYP T03. INTERCOM CALL SWITCH WIRED TO CLOCK/SPEAKER COMPLETE FOR OPERATION. T02 BOYS 206 T03 TYP F03 T05 FATCBR BAND HALL RENOVATION T10 OFFICE 205 TYP MUSIC STOR. 204 T04. WALL MOUNTED CLOCK. REFER TO SPECIFICATIONS SECTION 27 5313 FOR ADDITIONAL REQUIREMENTS. UNIFORM STOR. 203 T05. QUANTITY (2) PORT VOICE/DATA OUTLET U.N.O. T06. PAGING LOUDSPEAKER FOR DISTRIBUTED INTERCOM/PAGING SYSTEM. COORDINATE SIGNAL PULL BOX TYPE AND ROUGH-IN LOCATION WITH EQUIPMENT INSTALLER PRIOR TO COMMENCING ANY WORK. T01 T07. INTERIOR CAMERA LOCATION. PROVIDE DATA OUTLET AT HEIGHT INDICATED. B T08. BACK BOX FOR WALL MOUNTED VOLUME CONTROL SWITCH FOR PAGING LOUDSPEAKER. PROVIDE SINGLE-GANG BOX 2-1/2"D BOX WITH 1/2" SIDE KNOCKOUTS. RAISED AS NEEDED FOR FINISHED WALLBOARD THICKNESS. 200 LONGHORN STREET VEGA, TEXAS 79092 T01. NEW IT/AV CABINET, CPI MODEL - E SERIES ISP CO-LOCATION CABINET E1051742 WITH REAR FAN KIT. GIRLS 207 T09. ROUGH-IN ONLY, PROVIDE BOX, CONDUIT, AND A STAINLESS STEEL BLANK FACEPLATE. T10. BACK BOX FOR A/V PLUG-IN CONNECTION PANEL. PROVIDE A 3-GANG 2-1/2"D BOX WITH 1" SIDE KNOCKOUTS, CATALOG #942 AS MFD BY RACO. PROVIDE A 3-GANG COVER, RAISED AS NEEDED FOR FINISHED WALLBOARD THICKNESS. INSTALL AT 18" AFF. PROVIDE WITH (1) 1" CONDUIT TO A/V CONTROL PANEL BACK BOX ON WALL DIRECTLY ABOVE THIS BOX. (1) 4" CONDUIT TO EXISTING SERVER ROOM IN EXISTING MAIN BUILDING. SEE SITE PLAN ES101. CONNECTION TO EXISTING SERVER ROOM. ROUTE (1)4" CONDUIT FROM NEW CABINET IN BAND ROOM UNDERGROUND TO EXISTING MAIN BUILDING. TRANSITION CONDUIT UP THE SIDE OF EXISTING BUILDING TO POINT ABOVE DROP CEILING IN EXISTING BUILDING. HORIZONTALLY PENETRATE WALL WITH CONDUIT AND CONTINUE 4" CONDUIT TO EXISTING SERVER ROOM IN EAST WING. PROVIDE 4" 3-CELL MAXCELL INNERDUCT TO SPAN BOTH ENDS. B2 A 6 PAIR MM OSP FIBER CABINET IN BAND #205 ONE LINE DIAGRAM A1 0 1/4" = 1'-0" 2' 4' 8' NORTH IT IS THE INTENT OF THESE DOCUMENTS TO SHOW A BASIC REPRESENTATION OF THE FIRE ALARM SYSTEM. DEVICES INDICATED ON THESE DOCUMENTS ARE IN NO WAY IMPLIED TO BE COMPREHENSIVE OF THE FINAL DESIGN. IT IS THE RESPONSIBILITY OF THE FIRE ALARM CONTRACTOR TO PROVIDE A DESIGN/BUILD FIRE ALARM SYSTEM BASED UPON A THOROUGH REVIEW OF ALL CONTRACT DOCUMENTS. IT IS THE RESPONSIBILITY OF THE FIRE ALARM CONTRACTOR TO ENSURE THAT THE FIRE ALARM SYSTEM IS CODE COMPLIANT, MEETS THE REQUIREMENTS OF THE AHJ AND COMPREHENSIVELY COVERS AND INCLUDES ALL NECESSARY PARTS AND LABOR ASSOCIATED WITH OTHER TRADES AND SYSTEMS IMPACTING THE FIRE ALARM SYSTEM. NO CHANGE ORDERS SHALL BE APPROVED FOR THE BASE SCOPE OF WORK. 25 PAIR OSP COPPER EXISTING SERVER ROOM BAND HALL - SPECIAL SYSTEMS FLOOR PLAN T11. BACK BOX FOR BASIC A/V CONTROL PANEL. PROVIDE 4-11/16" SQUARE AND 2-1/8"D BOX WITH 3/4" AND 1" SIDE KNOCKOUTS, CATALOG #265 AS MFD. BY RACO. PROVIDE A 1-GANG COVER, RAISED AS NEEDED FOR FINISHED WALLBOARD THICKNESS. INSTALL AT LIGHT SWITCH HEIGHT. PROVIDE WITH (2) 1" EMT CONDUITS TO A/V JUNCTION BOX AT SMARTBOARD LOCATION. N.T.S. T12. WALL MOUNTED SMART BOARD WITH SHORT THROW VIDEO PROJECTOR LOCATION. PROVIDE STRUCTURAL BACKING AND MULTI-SERVICE JUNCTION BOX FOR POWER OUTLET, VOICE/DATA OUTLET, AND FUTURE AUDIO-VISUAL CONNECTIONS. SMART BOARD AND VIDEO PROJECTOR TO BE OWNER PROVIDED. REFER TO DETAIL B1 ON SHEET ET-501 FOR BOX AND ROUGH-IN REQUIREMENTS. T13. FUTURE OWNER PROVIDED SMART BOARD WITH WALL MOUNTED SHORT-THROW PROJECTOR. T14. ROUGH-IN AND STRUCTURAL BACKING FOR OWNER PROVIDED SMART BOARD WITH WALL MOUNTED SHORT-THROW PROJECTOR. 100 % CONSTRUCTION DOCUMENTS REVISIONS DRAWN BY SDR / BEL REVIEWED BY GR 7/29/2016 DATE PROJECT NO. 14-0424.002 DRAWING NAME BAND HALL SPECIAL SYSTEMS FLOOR PLAN SHEET NO. ET101 OF 1 2 3 4 5 1 2 3 4 5 96" POWER DUPLEX A/V COMPONENT D 24" 1 J 8" DATA PORT VOLTAGE BARRIER 24" 18" NOTE: POWER OUTLET MUST BE DECORA STYLE NOT, NEMA 106 STYLE IN ORDER TO INTEGRATE WITH THE OTHER DEVICES IN THE BOX. 12" PROVIDE BACKING MATERIAL. (SHEET METAL OR 3/4" PLYWOOD) 68" 4600 C Montgomery Blvd. NE Albuquerque, NM 87109 505.883.4111 www.bpce.com CABLE TYPE: C = COPPER F = FIBER CX = COAX CABLE U = UTP SMARTBOARD / ELECTRONIC WHITEBOARD (O.F.O.I.) B1 J-BOX #7 TEL CONDUIT #1 TR1-ER TEL CONDUIT #2 TR1-ER TEL CONDUIT #2 TR1-ER TEL CONDUIT #3 TR1-TR2 TEL CONDUIT #3 TR1-TR2 Digitally signed by William D. Herbst Date: 2016.07.29 11:04:55-06'00' U-089-1-202A LABEL WITHIN 6" OF CABLE BREAKOUT FINISHED FLOOR ROUGH-IN AND STRUCTURAL BACK FOR WALL MOUNTED SMARTBOARD B3 NO SCALE TELECOMMUNICATIONS CONDUIT IDENTIFICATION SCHEME B5 NO SCALE A/V USER CONTROLS TELECOM ROOM # TELECOM ROOM ID# B PATCH PANEL PORT PATCH PANEL # EQPT. RACK ID TELECOM ROOM ID# 221-TR1 1.3.B.28 PROJECT TYPICAL CABLE IDENTIFICATION SCHEME NO SCALE 1" CONDUIT & CONNECTOR. 4-11/16" SQUARE, 2-1/8" DEEP JUNCTION BOX WITH KNOCKOUTS. SERVICING CLOSET 4-11/16" SQUARE 1-DEVICE RAISED MUD RING. PORT LABEL A/V COMPONENTS 200 LONGHORN STREET VEGA, TEXAS 79092 TEL CONDUIT #1 TR1-ER CABLE # ORIGIN (TR NAME) DESTINATION (OUTLET NAME) BAND HALL RENOVATION C ENGINEER 100 % CONSTRUCTION DOCUMENTS REVISIONS IT CABINET 1.3.B.29 113-B CABLE LENGTH 12" COIL IN BACK BOX OUTLET ID OUTLET ID OUTLET ROOM # CATEGORY CABLES (QTY AS INDICATED ON PLANS) DRAWN BY SDR REVIEWED BY MODULAR JACK OR BLANK AS NEEDED 7/29/2016 DATE FACEPLATE GR PROJECT NO. 14-0424.002 DRAWING NAME A TECHNOLOGY DETAILS A2 RACK ELEVATION - CPI E SERIES E1051-742 A3 NO SCALE CEILING TELECOM OUTLET IDENTIFICATION SCHEME (TYPICAL) NO SCALE A4 TELECOMMUNICATIONS OUTLET BOX DETAILS (TYPICAL) NO SCALE SHEET NO. ET-501 OF 1 2 3 4 5 1 2 3 4 5 GENERAL SHEET NOTES FEEDER SCHEDULE ALL CONDUCTORS ARE COPPER, TYPE THWN/THHN UNLESS OTHERWISE NOTED. CONDUCTORS GROUND CONDUIT PANELBOARD AIC RATINGS ARE INDICATED ON THE NEW PANEL SCHEDULE. B. INFORMATION SHOWN IS DIAGRAMMATIC AND IS NOT INTENDED TO REPRESENT PHYSICAL ARRANGEMENTS, LOCATIONS, ROUTING OR CONNECTIONS. PHYSICAL LAYOUTS ARE TO BE PER FIELD CONDITIONS AND AS INDICATED ELSEWHERE IN THE ELECTRICAL PLANS. C. REFERENCE THE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS REGARDING EQUIPMENT AND INSTALLATION. NOT ALL INFORMATION SHOWN ON THIS DIAGRAM. D. ALL PANELS WILL HAVE DOOR-IN-DOOR ACCESSIBILITY FOR EACH PANEL. E. CONTRACTOR WILL MEASURE AND TORQUE ALL PANEL FEEDERS, MEASURE RESISTANCE TO GROUND AT SERVICE GROUND AND PROVIDE WRITTEN DOCUMENTATION OF TEST RESULTS. CONTRACTOR WILL COORDINATE TIME SO THAT SFPS REPRESENTATIVE IS PRESENT DURING TEST. F. CONTRACTOR WILL LABEL ALL DISTRIBUTION EQUIPMENT PRIOR TO FINAL OBSERVATION WALK THROUGH. G. WHEN ALL EQUIPMENT IS INSTALLED REQUIRING PROGRAMMING AND TRAINING HAS BEEN COMPLETED, THE SCHOOL'S IP ADDRESS WILL NEED TO BE GIVEN TO OWNER'S REPRESENTATIVE FOR ELECTRICAL M&O USE. H. REFER TO GROUNDING DIAGRAM ON SHEET E-602. NOTES THREE PHASE THREE WIRE & GROUND FEEDER D C 20 3#12 12 3/4" 25 3#10 10 3/4" 30 3#10 10 3/4" 35 3#8 10 3/4" 40 3#8 10 3/4" 45 3#8 10 3/4" 50 3#8 10 3/4" 60 3#6 10 1" 70 3#4 8 1 1/4" 80 3#4 8 1 1/4" 90 3#2 8 1 1/4" 100 3#2 8 1 1/4" 125 3#1 6 1 1/2" 150 3#1/0 6 1 1/2" 175 3#2/0 6 2" 200 3#3/0 6 2" 225 3#4/0 4 2 1/2" 250 3-250 KCMIL 4 3" 300 3-350 KCMIL 4 3" 350 3-500 KCMIL 2 4" 400 2 450 3-600 KCMIL (2) 3#4/0 (2) 2 4" (2) 2 1/2" 500 (2) 3-250 KCMIL (2) 2 (2) 3" 600 (2) 3-350 KCMIL (2) 1 (2) 3" 700 (2) 3-500 KCMIL (2) 1 (2) 4" 800 (2) 3-600 KCMIL (2) 1/0 (2) 4" 1000 (3) 3-400 KCMIL (3) 2/0 (3) 3" 1200 (3) 3-600 KCMIL (3) 3/0 (3) 4" 1600 (4) 3-600 KCMIL (4) 4/0 (4) 4" 2000 (5) 3-600 KCMIL (5)250 KCMIL 2500 (6) 3-600 KCMIL 3000 4000 D2 FAULT CURRENT CALCULATION NO SCALE C2 VOLTAGE DROP CALCULATION NO SCALE 4600 C Montgomery Blvd. NE Albuquerque, NM 87109 505.883.4111 www.bpce.com SHEET KEYED NOTES 1. REFER TO SHEET E-602 FOR GROUNDING INFORMATION FOR THIS EQUIPMENT. 2. MOLDED CASE, THERMAL-MAGNETIC CIRCUIT BREAKERS, 100% RATED AND LOCKABLE. (5) 4" 3. REFER TO ES-101 FOR ROUTING OF ALL RACEWAYS. (6)350 KCMIL (6) 4" 4. TO EXISTING MSB VIA TRANSFORMER. (8) 3-500 KCMIL (8)400 KCMIL (8) 4" (10) 3-600 KCMIL (10)500 KCMIL (10) 4" Digitally signed by William D. Herbst Date: 2016.07.29 11:05:06-06'00' THREE PHASE FOUR WIRE & GROUND FEEDER 20Y 4#12 12 3/4" 25Y 4#10 10 3/4" 30Y 4#10 10 3/4" 35Y 4#8 10 3/4" 40Y 4#8 10 3/4" 45Y 4#8 10 3/4" 50Y 4#8 10 3/4" 60Y 4#6 10 1" 70Y 4#4 8 1 1/4" 80Y 4#4 8 1 1/4" 90Y 4#2 8 1 1/4" 100Y 4#2 8 1 1/4" 125Y 4#1 6 1 1/2" 150Y 4#1/0 6 2" 175Y 4#2/0 6 2" 200Y 4#3/0 6 2" 225Y 4#4/0 4 2 1/2" 250Y 4-250 KCMIL 4 3" 300Y 4-350 KCMIL 4 3" 350Y 4-500 KCMIL 2 4" 400Y 450Y 4-600 KCMIL (2) 4#4/0 2 (2) 2 4" (2) 2 1/2" 500Y (2) 4-250 KCMIL (2) 2 (2) 3" 600Y (2) 4-350 KCMIL (2) 1 (2) 3" 700Y (2) 4-500 KCMIL (2) 1 (2) 4" 800Y (2) 4-600 KCMIL (2) 1/0 (2) 4" 1000Y (3) 4-400 KCMIL (3) 2/0 (3) 3" 1200Y (3) 4-600 KCMIL (3) 3/0 (3) 4" 1600Y (4) 4-600 KCMIL (4) 4/0 (4) 4" 2000Y (5) 4-600 KCMIL (5) 250 KCMIL (5) 4" 2500Y (6) 4-600 KCMIL (6) 350 KCMIL (6) 4" 3000Y (8) 4-500 KCMIL (8) 400 KCMIL (8) 4" 4000Y (10) 4-600 KCMIL (10) 500 KCMIL (10) 4" 5000Y (12) 4-600 KCMIL (12) 700 KCMIL (12) 4" B2 ELECTRICAL SERVICE CALCULATION NO SCALE BAND HALL BUILDING 6 175YS THRU 200YS 4 225YS THRU 300YS 2 350YS THRU 500YS 1/0 600YS THRU 700YS 2/0 800YS THRU 5000YS 3/0 REVISIONS 3 2 225A 3P PANEL "11S" 250Y GROUND 8 125YS THRU 150YS 100 % CONSTRUCTION DOCUMENTS 1 EQUIPMENT BONDING JUMPER FOR SEPARATELY DERIVED SYSTEMS PER NEC 250.66 (PROVIDE CONDUCTOR GROUND BELOW INSTEAD OF FEEDER GROUND FOR THREE PHASE, 4-WIRE SYSTEMS INDICATED ABOVE) DESIGNATION 20YS THRU 100YS BAND HALL RENOVATION PROJECT 225A B ENGINEER 200 LONGHORN STREET VEGA, TEXAS 79092 DESIGNATION A. EXISTING "11MDP" DRAWN BY 2000 AMPERE, NEMA 3R, 208Y/120V BUS GRADE EXISTING BAND HALL BUILDING 4 A 3#2, 1#4/0 NEUTRAL 8 2" 150Y-E 3#2/0, 2#2/0 NEUT. 6 2" 4 2 1/2" 225Y-E 3-250 KCMIL, 2-250 KCMIL NEUT. 350Y-E (2) 3#3/0, (2) 2#3/0 NEUT. (2) 2 (2) 2 1/2" 400Y-E (2) 3#4/0, (2) 2#4/0 NEUT. (2) 2 (2) 2 1/2" 500Y-E (2) 3-350 KCMIL, (2) 2-350KCMIL NEUT. (2) 2 (2) 3" UNDERGROUND JMM 7/29/2016 DATE PROJECT NO. 14-0424.002 ONE-LINE DIAGRAM 3 A2 REVIEWED BY DRAWING NAME THREE PHASE FOUR WIRE 200% NEUTRAL & GROUND FEEDER 100Y-E BEL ELECTRICAL ONE-LINE DIAGRAM NO SCALE SHEET NO. E-601 OF 1 2 3 4 5 1 2 3 4 5 GENERAL NOTES FIRE ALARM DIAGRAM INDICATED GENERAL DIAGRAMMATIC CONNECTIONS ONLY. ALL CONNECTIONS AND INSTALLATION WILL BE PER FIRE ALARM SYSTEM MANUFACTURER'S SHOP DRAWINGS. B. DEVICE QUANTITIES ARE NOT INDICATED ON THIS DRAWING. REFER TO FLOOR PLANS FOR QUANTITIES AND LOCATIONS. TYPICAL ALL LOCATIONS ENTIRE FIRE ALARM SYSTEM WILL BE IN RACEWAYS; NO EXCEPTIONS IT IS THE INTENT OF THESE DOCUMENTS TO SHOW A BASIC REPRESENTATION OF THE FIRE ALARM SYSTEM. DEVICES INDICATED ON THESE DOCUMENTS ARE IN NO WAY IMPLIED TO BE COMPREHENSIVE OF THE FINAL DESIGN. IT IS THE RESPONSIBILITY OF THE FIRE ALARM CONTRACTOR TO PROVIDE A DESIGN/BUILD FIRE ALARM SYSTEM BASED UPON A THOROUGH REVIEW OF ALL CONTRACT DOCUMENTS. IT IS THE RESPONSIBILITY OF THE FIRE ALARM CONTRACTOR TO ENSURE THAT THE FIRE ALARM SYSTEM IS CODE COMPLIANT, MEETS THE REQUIREMENTS OF THE AHJ AND COMPREHENSIVELY COVERS AND INCLUDES ALL NECESSARY PARTS AND LABOR ASSOCIATED WITH OTHER TRADES AND SYSTEMS IMPACTING THE FIRE ALARM SYSTEM. NO CHANGE ORDERS SHALL BE APPROVED FOR THE BASE SCOPE OF WORK. 4 2"C 3 D A. C. REFER TO SPECIFICATION SECTION 283100 FOR FIRE ALARM SYSTEM REQUIREMENTS. (TYP) RET. 7 120VAC D. FIRE ALARM WIRING AND CABLING SHALL BE IN CONFORMANCE WITH NEC AND TYPE SHALL BE AS RECOMMENDED BY FIRE ALARM SYSTEM MANUFACTURER. E. SEAL ALL PENETRATIONS THROUGH WALL, FLOOR, CEILING AND ROOF PER ARCHITECTURAL SPECIFIED REQUIREMENTS. SEAL WILL MATCH THE FIRE RATING OF EACH PENETRATION LOCATION. F. INSTALL GROUNDING CONNECTIONS TO BUILDING STRUCTURE AND WATER PIPES AT LOCATIONS THAT ARE VISIBLE AND ACCESSIBLE FOR INSPECTION, MAINTENANCE, AND TESTING. G. INSTALL AN INSULATED THROAT GROUNDING BUSHING ON EACH METALLIC SERVICE ENTRANCE CONDUIT. BOND TO SERVICE ENTRANCE EQUIPMENT GROUND BUS USING GROUNDING ELECTRODE CONDUCTOR. H. INSTALL AN INSULATED THROAT GROUNDING BUSHING ON EACH METALLIC FEEDER CONDUIT. BOND TO GROUND BUS USING CONDUCTOR THAT IS SIZED EQUAL TO EQUIPMENT GROUNDING CONDUCTOR. SUP. 2 FATCBR FACP 1 5 PANEL 11S 120VAC C2 C FIRE ALARM RISER DIAGRAM I. BOND ELECTRICAL EQUIPMENT ENCLOSURES TO GROUND BAR USING SAME SIZE CONDUCTOR AS FEEDER EQUIPMENT GROUND CONDUCTOR OR FACTORY PROVIDED GREEN SCREW. J. CLEAN COATED RE-BAR PRIOR TO PERFORMING ELECTRICAL CONNECTION. 4600 C Montgomery Blvd. NE Albuquerque, NM 87109 505.883.4111 www.bpce.com ENGINEER NO SCALE Digitally signed by William D. Herbst Date: 2016.07.29 11:05:17-06'00' FIRE ALARM TERMINAL CABINET (FATC) WILL BE A FACTORY MANUFACTURED, UL LABELED PANEL TO MATCH EXISTING SYSTEM ON CAMPUS. THE FATC WILL ENCLOSE ALL TERMINATIONS FOR DEVICES ON THE FLOOR IT SERVES, INTELLIGENT CARDS AS REQUIRED FOR INDEPENDENT OPERATION, AND POWER SUPPLIES. 2. WIRING AND CONDUCTORS AS REQUIRED BY THE FIRE ALARM MANUFACTURER AND INSTALLER. 3. FIRE/SMOKE DAMPER, ROUTE 120VAC VIA FIRE ALARM ADDRESSABLE RELAY. DUCT DETECTOR FOR FIRE/SMOKE DAMPERS WILL BE INSTALLED WITHIN 5'-0" OF EACH FIRE/SMOKE DAMPER. DETECTOR SUPPLIED BY DIVISION 26 AND INSTALLED BY DIVISION 23. 4. DUCT SMOKE DETECTOR, FURNISHED BY DIVISION 26, INSTALLED IN DUCT BY DIVISION 23, CONNECTED, WIRED, TESTED BY DIVISION 16. REFERENCE MECHANICAL CONTROL DIAGRAMS FOR MECHANICAL INTERCONNECTIONS. DUCT DETECTOR FOR UNITS OVER 2000 C.F.M. WILL BE INSTALLED ON SUPPLY SIDE OF UNIT. DUCT DETECTORS FOR UNITS OVER 15,000 C.F.M. WILL BE INSTALLED ON SUPPLY RETURN SIDE OF UNIT. DO NOT INSTALL DUCT DETECTOR ON EXHAUST FANS. 5. MAIN FIRE ALARM CONTROL PANEL REFER TO ES-101 FOR APPROXIMATE LOCATION. EXTEND RACEWAY AND CONDUCTORS BETWEEN FACP AND FATCBR AS NECESSARY. ROUTE RACEWAY AND CONDUCTORS AS INDICATED ON ES-101. 6. REFER TO ONE-LINE DIAGRAM AND FEEDER SCHEDULE FOR GROUNDED CONDUCTOR SIZE. 7. BONDING JUMPER SIZED PER GROUNDING ELECTRODE CONDUCTOR SCHEDULE THIS SHEET. EXISTING 11MDP NEUTRAL GROUNDING ELECTRODE CONDUCTOR SCHEDULE NOTE: ALL CONDUCTORS ARE COPPER. SERVICE CONDUCTOR SIZE (AWG OR kCMIL) GROUNDING ELECTRODE CONDUCTOR (AWG) <= #2 8 NON K-RATED TRANSFORMER 1/0 OR 1/0 6 2/0 OR 3/0 4 OVER 3/0 THROUGH 350 2 OVER 350 THROUGH 600 1/0 8 B 6 2/0 OVER 600 THROUGH 1100 OVER 1100 3/0 8. FOR EQUIPMENT GROUNDING CONDUCTOR SIZE REFER TO ONE-LINE DIAGRAM AND FEEDER SCHEDULE. 9. PROVIDE GROUNDING ELECTRODE CONDUCTOR SIZE BASED ON THE CONDUCTOR SIZE OF THE SECONDARY OF THE TRANSFORMER. SIZE PER NEC 250.66 AND PER SCHEDULE ON THIS SHEET. COLD WATER PIPE 7 10 9 GROUND NEUTRAL PANEL 11S 10. USE THE "MAIN GROUNDING ELECTRODE GROUND BAR" INSTEAD OF BUILDING STRUCTURAL STEEL IF THE FIRST OVER CURRENT DEVICE FOR THE SEPARATELY DERIVED SYSTEM IS WITHIN SAME ROOM OF THE "MAIN GROUNDING ELECTRODE GROUND BAR". 100 % CONSTRUCTION DOCUMENTS REVISIONS DRAWN BY JMM 7/29/2016 DATE 14-0424.002 DRAWING NAME A GROUNDING & FIRE RISER DIAGRAMS 10 A3 BEL REVIEWED BY PROJECT NO. BUILDING STRUCTURAL STEEL 200 LONGHORN STREET VEGA, TEXAS 79092 GROUND 1. PROJECT BAND HALL RENOVATION SHEET KEYED NOTES GROUNDING DIAGRAM SHEET NO. NO SCALE E-602 OF 1 2 3 4 5 1 2 3 4 5 LIGHTING SEQUENCE OF OPERATION NEUTRAL A. DIAGRAMS ARE SHOWN FOR BIDDING PURPOSES. CONTRACTOR WILL PROVIDE ACCURATE AND COORDINATED DIAGRAMS FOR SHOP DRAWING SUBMITTALS. B. CONTRACTOR WILL PROVIDE ENGRAVED SWITCHES. ROOM LUMINAIRES LIGHTING CONTROL DESCRIPTION Scene (A) 50% Lumen Output or Manual-ON/Auto-OFF Scene (B) 100% Lumen Output or Manual-ON/Auto-OFF DIMMING ROOM CONTROLLER LMRC-211 D 0-10V CONTROL LOOP (CLASS 2) LIGHTING SEQUENCE OF OPERATION A. CLASSROOMS & PRACTICE ROOMS: 1. UNOCCUPIED MODE: WHEN ROOM IS UNOCCUPIED ALL LIGHTING SHALL BE DISABLED AND DE-ENERGIZED BY OCCUPANCY SENSOR(S) IN ROOM. 2. OCCUPIED MODE: a. LIGHTING CONTROL IN ROOM WILL BE ENABLED BY SWITCHES IN ROOM. NO LUMINAIRES WILL AUTOMATICALLY ENERGIZE. b. DURING OCCUPANCY AT TWO BUTTON SWITCH: - TOP BUTTON (A) WILL BE PROGRAMMED TO CONTROL ALL LUMINAIRES IN CLASSROOM AT 50% LUMEN OUTPUT. WHEN BUTTON IS PUSHED AGAIN THE LUMINAIRES WILL TURN OFF. - BOTTOM BUTTON (B) WILL BE PROGRAMMED TO CONTROL ALL LUMINAIRES IN CLASSROOM AT 100% LUMEN OUTPUT. WHEN BUTTON IS PUSHED AGAIN THE LUMINAIRES WILL TURN OFF. c. WHEN PERSONNEL LEAVE THE ROOM THEY CAN TURN THE LUMINAIRES OFF BY PUSHING SWITCH OR ALLOWING THE OCCUPANCY SENSOR TO TIME OUT AND THE SYSTEM SHALL RESET TO THE UNOCCUPIED MODE. B. ENTRY VESTIBULE: a. TOGGLE SWITCH WILL TURN LUMINAIRES ON/OFF. C. RESTROOMS: a. DUAL TECHNOLOGY (ULTRA-SONIC/INFRARED) CEILING MOUNTED SENSORS WILL CONTROL LUMINIARES ON AND OFF AUTOMATICALLY. KEYED SWITCH WILL BE SECONDARY MEANS OF CONTROL. D. STORAGE ROOMS: a. WALL MOUNTED OCCUPANCY SENSOR WILL CONTROL THE LUMINAIRE IN THE ROOM. E. OFFICE: a. LIGHTING CONTROL IN ROOM WILL BE ENABLED BY SWITCHES IN ROOM. NO LUMINAIRES WILL AUTOMATICALLY ENERGIZE. b. DURING OCCUPANCY AT TWO BUTTON SWITCH: - LEFT BUTTON (A) WILL BE PROGRAMMED TO CONTROL ALL LUMINAIRES IN THE OFFICE AT 50% LUMEN OUTPUT. WHEN BUTTON IS PUSHED AGAIN THE LUMINAIRES WILL TURN OFF. - RIGHT BUTTON (B) WILL BE PROGRAMMED TO CONTROL ALL LUMINAIRES IN THE OFFICE AT 100% LUMEN OUTPUT. WHEN BUTTON IS PUSHED AGAIN THE LUMINAIRES WILL TURN OFF. c. WHEN PERSONNEL LEAVE THE ROOM THEY CAN TURN THE LUMINAIRES OFF BY PUSHING SWITCH OR ALLOWING THE OCCUPANCY SENSOR TO TIME OUT AND THE SYSTEM SHALL RESET TO THE UNOCCUPIED MODE. HOT 120/277 1 NO. 12 GAUGE WIRE HANGER TO BUILDING FRAMING OR STRUCTURAL MEMBERS. SUSPEND FROM ALL FOUR CORNERS OF THE LUMINAIRE CAT5e LMRJ-Watt Stopper Cable WALL SWITCH OCCUPANCY SENSOR LMDW-102 CEILING SYSTEM HANGER WIRES (TYP.) A B Watt Stopper REFER TO SHEET SERIES "EL" FOR LOCATIONS AND ADDITIONAL INFORMATION LUMINAIRE SUPPORT DETAIL C3 NO SCALE PROJECT NO SCALE NEUTRAL ROOM LUMINAIRES ROOM LUMINAIRES LIGHTING CONTROL DESCRIPTION Scene (A) 50% Lumen Output or Manual-ON/Auto-OFF Scene (B) 100% Lumen Output or Manual-ON/Auto-OFF ROOM LUMINAIRES DIMMING ROOM CONTROLLER LMRC-211 Digitally signed by William D. Herbst Date: 2016.07.29 11:05:28-06'00' WATT STOPPER "DLM" WIRING DIAGRAM NEUTRAL B ENGINEER DIMMING ROOM CONTROLLER LMRC-211 0-10V CONTROL LOOP (CLASS 2) HOT 120/277 0-10V CONTROL LOOP (CLASS 2) HOT 120/277 A = 50% LUMEN OUTPUT 1 2 ROOM LUMINAIRES A = 50% LUMEN OUTPUT 1 2 B = 100% LUMEN OUTPUT 200 LONGHORN STREET VEGA, TEXAS 79092 C C1 RJ45 (TYPICAL) SEISMIC FIXTURE CLAMPS: REQUIRED AT ALL (4) LUMINAIRE CORNERS WITH 2#10 SELF-TAPPING SCREWS. AGI SEISMIC PRODUCTS OR EQUAL. AC 184 COMPLIANT. LAY-IN LUMINAIRE 4600 C Montgomery Blvd. NE Albuquerque, NM 87109 505.883.4111 www.bpce.com BAND HALL RENOVATION CEILING SYSTEM HANGER WIRES (TYP.) B = 100% LUMEN OUTPUT 100 % CONSTRUCTION DOCUMENTS REVISIONS CAT5e LMRJ-Watt Stopper Cable LIGHTING CONTROL DESCRIPTION PLACARD MOUNT ADJACENT TO SWITCH 2 BUTTON SWITCH LMSW-102 LMDC-100 SEE INSTALLATION INSTRUCTIONS FOR TERMINATION TYPE 2 BUTTON SWITCH LMSW-102 A A A DRAWN BY B B B REVIEWED BY Watt Stopper Watt Stopper LMDC-100 LMDC-100 LMDC-100 SEE INSTALLATION INSTRUCTIONS FOR TERMINATION TYPE (TYPICAL) RJ45 (TYPICAL) A4 NO SCALE JMM 14-0424.002 DRAWING NAME LIGHTING DETAIL & DIAGRAMS REFER TO SHEET SERIES "EL" FOR LOCATIONS AND ADDITIONAL INFORMATION WATT STOPPER "DLM" WIRING DIAGRAM BEL 7/29/2016 DATE PROJECT NO. RJ45 (TYPICAL) REFER TO SHEET SERIES "EL" FOR LOCATIONS AND ADDITIONAL INFORMATION A3 MOUNT ADJACENT TO SWITCHES 2 BUTTON SWITCH LMSW-102 LMDC-100 Watt Stopper A LIGHTING CONTROL DESCRIPTION PLACARD CAT5e LMRJ-Watt Stopper Cable WATT STOPPER "DLM" WIRING DIAGRAM NO SCALE SHEET NO. E-603 OF 1 2 3 4 5 1 2 3 4 5 D 4600 C Montgomery Blvd. NE Albuquerque, NM 87109 505.883.4111 www.bpce.com ENGINEER C Digitally signed by William D. Herbst Date: 2016.07.29 11:05:39-06'00' B 200 LONGHORN STREET VEGA, TEXAS 79092 BAND HALL RENOVATION PROJECT 100 % CONSTRUCTION DOCUMENTS REVISIONS DRAWN BY BEL REVIEWED BY JMM 7/29/2016 DATE PROJECT NO. 14-0424.002 DRAWING NAME A LUMINIARE SCHEDULES SHEET NO. E-701 OF 1 2 3 4 5 1 2 3 4 5 D 4600 C Montgomery Blvd. NE Albuquerque, NM 87109 505.883.4111 www.bpce.com ENGINEER C Digitally signed by William D. Herbst Date: 2016.07.29 11:05:50-06'00' B 200 LONGHORN STREET VEGA, TEXAS 79092 BAND HALL RENOVATION PROJECT 100 % CONSTRUCTION DOCUMENTS REVISIONS DRAWN BY BEL REVIEWED BY JMM 7/29/2016 DATE PROJECT NO. 14-0424.002 DRAWING NAME A PANEL SCHEDULES SHEET NO. E-702 OF 1 2 3 4 5