BAND HALL RENOVATION - Southwest General Contractors

advertisement
SHEET INDEX
GENERAL
G001
COVER, SHEET INDEX
ARCHITECTURAL
D100
DEMOLITION FLOOR PLAN
A101
RENOVATION FLOOR PLAN, WALL SECTION, NOTES
A181
TAS INFORMATION, ENLARGED TOILET PLANS, TOILET ELEVATIONS
A501
REFLECTED CEILING PLAN, MATERIAL LEGEND, CLG DETAILS, NOTES
A601
DOOR AND WINDOW ELEVATIONS, SCHEDULE, AND DETAILS
A701
FINISH FLOOR PLAN, FINISH LEGEND, GENERAL FINISH NOTES
A771
INTERIOR ELEVATIONS AND MILLWORK
MECHANICAL
MD101
MECHANICAL DEMOLITION FLOOR PLAN
ARCHITECT
MECHANICAL HVAC FLOOR PLAN
IS
E
REG
PLUMBING
ST
PLUMBING LEGEND
A
PLUMBING DEMOLITION FLOOR PLAN
TE
T
C
Y L OR
C H ARL
S
AR
B ARR E T
18563
OF
EC T
MECHANICAL SCHEDULES
ED
TA
M701
T
ER
IT
MECHANICAL DETAILS
H
M501
S
MECHANICAL SYMBOL LEGEND
A
M001
TE
X
WASTE & VENT FLOOR PLAN
PP101
PLUMBING PIPING FLOOR PLAN
P501
PLUMBING DETAILS
ENGINEER
ELECTRICAL
ES101
ELECTRICAL SITE PLAN
ED101
BAND HALL DEMOLITION FLOOR PLAN
EL101
BAND HALL LIGHTING FLOOR PLAN
EP101
BAND HALL POWER FLOOR PLAN
ET101
BAND HALL SPECIAL SYSTEMS FLOOR PLAN
ET501
TECHNOLOGY DETAILS
E601
ONE-LINE DIAGRAM
E602
GROUNDING & FIRE RISER DIAGRAMS
E603
LIGHTING DETAIL & DIAGRAMS
E701
LUMINARE SCHEDULES
E702
PANEL SCHEDULES
PROJECT
200 LONGHORN STREET
VEGA, TEXAS 79092
ELECTRICAL LEGEND
BAND HALL RENOVATION
E001
REVISIONS
VEGA BAND HALL RENOVATION
PROJECT TEAM
OWNER
ARCHITECT / INTERIORS
VEGA ISD
DEKKER/PERICH/SABATINI, LLC.
200 LONGHORN ST.
VEGA, TX 79092
TEL: 806-267-2126
FAX: 806-267-2146
500 S. TAYLOR, SUITE 750
AMARILLO, TX 79101
TEL: 806-376-8199
FAX: 806-376-8189
CONTACT: MIKE WARTES
CONTACT: BARRY TAYLOR, AIA
ELECTRICAL, PLUMBING,
MECHANICAL & FIRE PROTECTION
BRIDGERS & PAXTON
CONSULTING ENGINEERS, INC.
4600-C MONTGOMERY BLVD. NE
ALBUQUERQUE, NM 87109
TEL: 505-883-4111
FAX: 505-888-1436
CONTACT: ABBAS SHIRIAN, P.E.
DRAWN BY
REVIEWED BY
DATE
7/29/2016
PROJECT NO.
14-0424.002
DRAWING NAME
COVER SHEET
INDEX of DRAWINGS
G 001
BUILDING DEMOLITION NOTES
ARCHITECT
1'-71 4"
S
Y L OR
A
TE
X
2'-0"+/VERIFY
2'-1018"+/-
VERIFY
VERIFY
6"+/VERIFY
12'-27 8"
3'-218"+/-
EXISTING SHELVING TO
REMAIN (TYP)
512"+/6"+/VERIFY
11'-93 8"+/VERIFY
6"+/VERIFY
200 LONGHORN STREET
VEGA, TEXAS 79092
VERIFY
13'-712"+/-
PROJECT
BAND HALL RENOVATION
VERIFY
7'-83 4"+/-
13'-75 8"+/-
1. REMOVE EXISTING CEILING MATERIAL AND DUCTWORK, REFERENCE MEP DOC's
AND COORDINATE BETWEEN TRADES.
2. ALL FLOORING, IN ITS ENTIRETY, TO BE REMOVED.
3. ALL CEILING, IN ITS ENTIRETY, TO BE REMOVED.
4. ALL LIGHTING, IN ITS ENTIRETY, TO BE REMOVED
12'-91 4"+/VERIFY
18563
OF
EC T
6"+/VERIFY
EXISTING MECHANICAL
EQUIPMENT TO BE
REMOVED SEE MD 101
CLOSE REMAINING WALL
PENETRATIONS, WITH SIMILAR
BUILDING MATERIAL IN FINISH
& COLOR. MAKE WEATHER TIGHT
(TYP)
VERIFY
C
TA
TE
T
IT
A
REMOVE EXISTING DOORS, FRAMES AND
HARDWARE - SHOWN DASHED (TYP)
SALVAGE F/A PULL STATION FOR
RE-INSTALLATION, (IF POSSIBLE) TO NEW
LOCATIONS
AR
B ARR E T
ENGINEER
EXISTING SHELVING TO BE DEMOLISHED
- SHOWN DASHED (TYP)
VERIFY
NOTE:
MAINTAIN EXISTING VENT STACK &
EXHAUST FAN ROOF OPENINGS - FOR
RE-USE w/ NEW VENT STACKS AND
EXHAUST FAN EQUIPMENT
(MODIFY CURBS AS NEEDED TO
PREVENT NEW ROOF PENETRATIONS)
MAKE WATER TIGHT (TYP)
ED
H
S
ST
THE CONTRACTOR SHALL DELIVER THE ABOVE ITEMS TO THE OWNER
AT HIS DIRECTION. CONSULT CONSTRUCTION MANAGER, CONCERNING
DISPOSITIONS OF SALVAGE. ANY OF THE ABOVE ITEMS NOT WANTED
BY THE OWNER SHALL BE DISPOSED OF, BY THE CONTRACTOR.
NOTE:
DEMO WALLS TO REQUIRED WIDTH, AS
REQUIRED TO ACCOMMODATED NEW
FRAMING OF NEW OPENINGS (TYP)
T
ER
E
EXISTING SHELVING TO BE DEMOLISHED
- SHOWN DASHED (TYP)
IS
SALVAGE F/A PULL STATIONS FOR
POSSIBLE RE-INSTALLATION, (IF
POSSIBLE) TO NEW LOCATIONS
R EG
5'-43 8"+/-
SALVAGE FIRE EXTINGUISHER,
FOR POSSIBLE RE-INSTALLATION
IN NEW FIRE EXTINGUISHED CABINET
VERIFY
B.
FIRE EXTINGUISHERS, TACK BOARDS, MAPS, ELECTRONICS, AND
PROJECTION SCREENS SHALL BE REMOVED AND REMOVED & STORED
FOR REINSTALLATION OR SALVAGED TO VISD. MAP AND TV BRACKETS
ATTACHED TO THE WALL SHALL BE REMOVED, PROTECTED, AND
SALVAGED TO THE OWNER, AT OWNERS DISCRETION.
VISD SHALL RETAIN CERTAIN ITEMS REMOVED FROM THE BUILDING.
(1)
THE CLOCK AND BELL COMPONENTS.
(2)
THE AUDIO-VISUAL SYSTEM, INCLUDING SPEAKERS.
(3)
LIGHT FIXTURES.
(4)
ALL LOCKS, PANIC DEVICES, DOOR CLOSERS AND DOOR
HARDWARE NOT RE-USED.
(5)
ALL BREAKERS, STARTERS, STAGE LIGHTING AND LIGHT
FIXTURES NOT RE-USED.
(6)
ALL PUMPS AND MOTORS NOT RE-USED, INCLUDING STARTERS.
(7)
ALL COPPER PIPES REMOVED.
(8)
ALL DRINKING FOUNTAINS, BUBBLERS, AND VALVES.
(9)
ANY SHELVING NOT RE-USED.
(10)
ALL FLUSH VALVES NOT RE-USED.
(11)
ANY WATER CLOSETS AND FIXTURES NOT RE-USED.
(12)
THE OWNER'S CHOICE OF PIPE ABOVE 1-1/4" IN DIAMETER.
(13)
FIRE ALARM SYSTEMS, INCLUDING HORNS AND PULL STATIONS
(IF UNABLE TO REUSE).
(14)
HVAC UNITS AND EXHAUST FANS.
C H AR L
A.
REMOVE EXISTING CONSTRUCTION SHOWN DASHED (TYP)
REVISIONS
EXISTING CANOPY TO REMAIN (TYP)
LEGEND
WALLS AT PERIMETER TO REMAIN
A1
BAND HALL DEMOLITION PLAN
1/4" = 1'-0"
0
2'
4'
8'
EXISTING CONSTRUCTION TO REMAIN
DRAWN BY
EXISTING CONSTRUCTION TO BE REMOVED
IN IT'S ENTIRETY
REVIEWED BY
DATE
ALL EXISTING DIMS +/- TO BE VERIFIED. (TYP.)
PROJECT NO.
7/29/2016
14-0424.002
DRAWING NAME
BAND HALL
DEMOLITION PLAN
D100
GENERAL SHEET NOTES
1.
2.
3.
4.
5.
5'-43 8"
5'-612"
4'-103 4"
6" MTL STUDS
NOTE: CHASE WALL CONSTR., TO BE
212" MTL STUDS at 16" o.c., (MAX.) w/ 5 8" GYP.
BD. ROOM SIDE ONLY, UTILIZE 'V' BAR HORIZ.
BRACING at 24" VERTICALLY, ON CHASE SIDE,
(TYP)
4"
1'-0"
3'-4"
2'-612"
46'-95 8"
NEW CARPET TILE TO MATCH NEW HIGH SCHOOL
NEW WALLS TO BE FILLED WITH 2 12" (THERMA-FIBER) SOUND
ATTENUATION BLANKETS.
WALLS & DOORS ARE TO BE BUILT AS SOUND PROOF AS
POSSIBLE
RESTROOM FINISHES ARE TO MATCH NEW HIGH SCHOOL.
FURR OUT EXISTING WALLS AT PERIMETER OF BUILDING, IF
REQ'D., TO ACCOMMODATE NEW POWER OUTLETS,
SWITCHES, ETC.
19'-45 8"
A1
2"
6'-4"
A601
ARCHITECT
S
18563
OF
A
T
E
IS
C H ARL
R EG
4'-212"
Y L OR
TE
EC T
A
C
TA
7'-83 4"
AR
B A RRE T T
TE
X
ENGINEER
6" MTL STUDS
NOTE: CHASE WALL CONSTR.,
TO BE 212" MTL STUDS at 16" o.c.,
(MAX.) w/ 5 8" GYP. BD. ROOM SIDE
ONLY, UTILIZE 'V' BAR HORIZ.
BRACING at 24" VERTICALLY,
ON CHASE SIDE, (TYP)
PROJECT
NOTE: ALL NEW WALL CONSTRUCTION AT
EXISTING WALLS TO REMAIN, ARE TO BE 2 x
MATERIAL, w/ LAYERS OF GYP. BD. AS REQUIRED,
TO MEMBER OUT w/ EXISTING WALLS (TYP)
A1
1'-41 2"
6'-45 8"+/-
5'-97 8"+/-
6'-4"
6'-4"
6" MTL STUDS
5'-01
4"
1'-93 4"
MATERIAL LEGEND
EXISTING CONSTRUCTION TO
REMAIN
NEW CONSTRUCTION at MTL STUDS
2" TH'K ACOUSTICAL SOUND PANELS
OVER GYP. BD FINISH, WHERE SHOWN.
NEW DISPLAY SHELF
200 LONGHORN STREET
VEGA, TEXAS 79092
A601
BAND HALL RENOVATION
5'-41 2"
6'-4"
2'-612"
SIM
TO STRUCTURE ABOVE
ED
IT
NOTE: CHASE WALL CONSTR., TO BE
212" MTL STUDS at 16" o.c., (MAX.) w/ 5 8" GYP.
BD. ROOM SIDE ONLY, UTILIZE 'V' BAR HORIZ.
BRACING at 24" VERTICALLY, ON CHASE SIDE,
(TYP)
S
ST
2'-612"
ER
H
NOTE: ALL NEW WALL CONSTRUCTION IN
SOUTH PORTION OF BUILDING AREA, ARE
TO BE METAL STUD CONSTRUCTION,
w/ 16" o.c., SPACING & 5 8" GYP. BD. EA. SIDE
(TYP)
NEW ACOUSTICAL CEILING
AS HIGH AS POSSIBLE.
R-19 THERMAL BATT
INSULATION ABOVE
APC. (TYP)
NEW CONSTR. at EXISTING WALLS
SOUND ATTENUATION
BLANKETS (212"
THERMA-FIBER OR
EQUAL) TYP. ALL WALLS
NEW ACOUSTICAL
CEILING
REVISIONS
4"
1'-4"
SHELF TO HAVE HIDDEN
BRACKETS AND APPEAR
TO BE CONTINUOUS
47 8"
KEYPLAN
4"
2" THICK ACOUSTICAL
SOUND PANELS REF ELEV's A771
11'-0"
10'-10"
DRAWN BY
REVIEWED BY
7'-2"
DATE
DOOR AND FRAME
AS SCHEDULED
7/29/2016
14-0424.002
PROJECT NO.
DRAWING NAME
FINISHED FLOOR
AS SCHEDULED SEE A701
A1
RENOVATION
FLOOR PLAN
WALL SECTION
3/8" = 1'-0"
A101
3'-6 7/8"
1'-9 1/4"
LAVATORY
PAPER TOWEL
DISPENSER
SHOWER
CURTAIN,
ROD & HOOKS
MOP RACK
SANITARY NAPKIN
DISPOSAL
CLEAR FLOOR
SPACE
MOP BASIN
HI / LO ELECTRIC
WATER COOLER
ROBE HOOK
1'-6"
5'-2 1/2"
3'-6 7/8"
SEE NOTE 'F'
SHT. A701
1'-9 1/4"
SEE NOTE 'F'
SHT. A701
CONTROL
AREA
CENTERED ON
TACTILE CHARACTERS
2'
4'
8'
ACCESSIBLE SHOWER STALL NOTES
LOCATIONS OF TACTILE
E2 SIGNS AT DOORS
FINISHED CEILING
PAINTED GYP. BOARD
SOFFITT (P-4)
0
1/2" = 1'-0"
1'
2'
1.
'ELL' SHAPED
GRAB BAR
1/2" MAX SHOWER
CURB
60" HOSE
ACCESSIBLE TRANSFER SHOWER STALL
CONTROL WALL ELEVATION (ADULT)
2.
3.
4.
4'
5.
TILE (T-1 & T-2)
SEE DETAIL A2/A701
'ELL'SHAPED
GRAB BAR
6.
7.
FINISHED FLOOR
8.
TOILET GIRLS 207
1/4" = 1'-0"
0
2'
9.
SHOWER SEAT
4'
8'
ACCESSIBLE TRANSFER SHOWER STALL
BACK WALL ELEVATION (ADULT)
IN THE TRANSFER STALL, PROVIDE A SEAT ON THE WALL
OPPOSITE THE CONTROLS AS INDICATED.
MOUNT THE SEAT 18" ABOVE BATHROOM FLOOR (FOR
ADULTS) AND EXTEND THE FULL DEPTH OF THE STALL.
PROVIDE GRAB BARS AS INDICATED.
LOCATE FAUCETS AND OTHER CONTROLS ON THE WALL
OPPOSITE THE SEAT.
PROVIDE A SHOWER SPRAY UNIT AS INDICATED WITH A HOSE
AT LEAST 60" THAT CAN BE FIXED OR HAND-HELD. MOUNT
THE UNIT AT 42" MAX (GRADE PRE-K THRU 5 OR 6) ABOVE
SHOWER FLOOR FOR FORWARD REACH AND 48" MAX (ADULT)
FORWARD REACH, OR 54" MAX (ADULT) SIDE REACH, ABOVE
SHOWER FLOOR.
PROVIDE FOLDING TYPE SEAT WHERE A FIXED SEAT IS
INDICATED IN A 36" x 36" MIN. SHOWER STALL, MOUNTED ON
THE WALL ADJACENT TO THE CONTROLS.
PROVIDE MARBLE THRESHOLD (MAX HEIGHT OF 1/2") WHERE
INDICATED, IN SHOWER STALLS 36" X 36", UNLESS PRE-FAB
SHOWER UNIT IS PROVIDED.
DO NOT OBSTRUCT CONTROLS OR OBSTRUCT TRANSFER
FROM WHEELCHAIRS ONTO SHOWER SEATS WITHIN
ENCLOSURES FOR SHOWER STALLS.
THE STRUCTURAL STRENGTH OF SEATS AND THEIR
ATTACHMENTS SHALL COMPLY WITH TAS 610.4.
FINISHED CEILING
60" MAX.
TILE (T-1 & T-2)
SEE DETAIL A2/A701
BASELINE OF
HIGHEST
TACTILE
CHARACTER
48" MIN
BASELINE OF
LOWEST
TACTILE
CHARACTER
MEN
TOILET PAPER DISPENSER
OUTLET LOCATION
0
1/4" = 1'-0"
2'
4'
FINISH
FLOOR
WHEELCHAIR ACCESSIBLE
AMBULATORY ACCESSIBLE
ACCESSIBLE STALL FRONT ELEVATION (ADULT)
ACCESSIBLE STALL SIDE ELEVATION (ADULT)
ACCESSIBLE WATER CLOSET & TOILET COMPARTMENTS
TOILET GIRLS 207
2'
4'
8'
2.
3.
FINISHED CEILING
30" x 48"
CLEAR
FLOOR
SPACE
COLORS SELECTED
BY ARCHITECT
B1
ACCESSIBLE DRESSING BENCH PLAN
(IF INDICATED on PLANS)
TTD
0
2'
4'
8'
MEN
ACCESSIBLE DRESSING BENCH BACK SUPPORT
(IF INDICATED on PLANS)
FINISHED CEILING
PAINTED GYP. BOARD
SOFFITT (P-4)
(a)
WALL HUNG
TYPE
TILE (T-1 & T-2)
SEE DETAIL A2/A701
AMBULATORY ACCESSIBLE
TOILET COMPARTMENT
* OTHER
APPROACHES
48" MIN.
ADULT WALL HUNG WATER CLOSET
(a)
ELEVATION
ADULT
FINISHED FLOOR
A1
TOILET BOYS 206
1/4" = 1'-0"
0
2'
4'
8'
A2
HC SIGNAGE ELEV. AT R.R.
6" = 1'-0"
0
1"
2"
3"
OF
TE
X
ENGINEER
TOILET SEAT HEIGHT (MEASURED FROM FLOOR TO RIM)
A. AGES 3 & 4
= 11" TO 12"
B. AGES 5 THROUGH 8
= 12" TO 15"
C. AGES 9 THROUGH 12
= 15" TO 17"
D. ADULT
= 15"
E. ACCESSIBLE
= 17" TO 19"
PROJECT
ACCESSIBLE GRAB BAR HEIGHTS (MEASURED FROM FLOOR TO TOP OF BAR)
A. AGES 3 & 4
= 18" TO 20"
B. AGES 5 THROUGH 8
= 20 TO 25"
C. AGES 9 THROUGH 12
= 25" TO 27"
D. ADULT
= 33" MIN. TO 36" MAX.
TOILET PAPER DISPENSER HEIGHT (MEASURE FROM FLOOR TO CENTERLINE OF DISPENSER)
A. AGES 3 & 4
= 14"
B. AGES 5 THROUGH 8
= 14" TO 17"
C. AGES 9 THROUGH 12
= 17 TO 19"
D. ADULT (ACCESSIBLE)
= 15" TO 48" *
SANITARY NAPKIN DISPENSER (MEASURE FROM FLOOR TO COIN SLOT)
A. FORWARD REACH
= 15" TO 48" (UNOBSTRUCTED)
B. FORWARD REACH
= 48" MAX (OBSTRUCTED REACH DEPTH 20" MAX)
C. FORWARD REACH
= 44" MAX (OBSTRUCTED REACH DEPTH 25" MAX)
D. SIDE REACH
= 15" - 48" (UNOBSTRUCTED)
E. SIDE REACH
= 48" MAX (OBSTRUCTED HEIGHT 34" REACH DEPTH 10" MAX)
F. SIDE REACH
= 46" MAX (OBSTRUCTED HEIGHT 34" REACH DEPTH 24" MAX)
SOAP DISPENSER & PAPER TOWEL DISPENSER (LOCATED WITHIN THE FORWARD & SIDE REACH
RANGES)
A. AGES 3 & 4
= 20" TO 36"
B. AGES 5 THROUGH 8
= 18" TO 40"
C. AGES 9 THROUGH 12
= 16" TO 44"
D. FORWARD REACH
= 15" TO 48" (UNOBSTRUCTED)
E. FORWARD REACH
= 48" MAX (OBSTRUCTED REACH DEPTH 20" MAX)
F. FORWARD REACH
= 44" MAX (OBSTRUCTED REACH DEPTH 25" MAX)
G. SIDE REACH
= 15" - 48" (UNOBSTRUCTED)
H. SIDE REACH
= 48" MAX (OBSTRUCTED HEIGHT 34" REACH DEPTH 10" MAX)
J. SIDE REACH
= 46" MAX (OBSTRUCTED HEIGHT 34" REACH DEPTH 24" MAX)
MIRROR
A. ABOVE COUNTERTOP
B. NO COUNTERTOP
C. FULL LENGTH
= 40" MAX BOTTOM EDGE OF REFLECTING SURFACE FROM F.F.
= 35" MAX BOTTOM EDGE OF REFLECTING SURFACE FROM F.F.
= TOP OF MIRROR EDGE 74" MIN FROM FLOOR
SHOWER HEADS (MEASURED FROM FLOOR TO HEAD)
A. ADULTS
= 78"
B. ACCESSIBLE
= 48" TO SHOWER HEAD (FORWARD REACH)
= 48" TO TOP OF CONTROLS
REVISIONS
DRINKING FOUNTAINS (MEASURED FROM FLOOR TO SPOUT OUTLETS)
A. ADULTS
= 38" - 43" (STANDING PERSON)
B. ACCESSIBLE
= 36" (SPOUT SHALL BE LOCATED 15" MIN. FROM THE VERTICAL
SUPPORT AND 5" MAX FROM THE FRONT EDGE OF THE UNIT,
INCLUDING BUMPERS)
SEATS
A. BATHTUB
B. SHOWER - STANDARD
ROLL IN SHOWER
(b)
ELEVATION
CHILDREN
TTD
WHEELCHAIR ACCESSIBLE
TOILET COMPARTMENT
TOE CLEARANCE
LATCH
APPROACH
3'-0"
DOOR
HEIGHT & DEPTH OF URINALS
NOTE:
1. FLUSH CONTROLS SHALL BE HAND
OPERATED OR AUTOMATIC. HAND
OPERATED FLUSH CONTROLS SHALL
COMPLY WITH TAS 309.
2. A CLEAR FLOOR OR GROUND SPACE
COMPLYING WITH TAS 305 POSITIONED FOR
FORWARD APPROACH SHALL BE PROVIDED.
18563
WATER CLOSET CENTERLINE (MEASURED FROM SIDE WALL TO
CENTERLINE)
A. AGES 3 & 4
= 12"
B. AGES 5 THROUGH 8
= 12" TO 15"
C. AGES 9 THROUGH 12
= 15" TO 18"
D. WHEELCHAIR
= 16" TO 18" (NO MORE, NO LESS)
E. AMBULATORY
= 17" TO 19" (NO MORE, NO LESS)
TOE CLEARANCE
C. SHOWER - ALTERNATE
ROLL-IN SHOWER
BRAILLE, CONTRACTED (GRADE 2)
TAS 703.3.1
NOTE:
1. INTERNATIONAL SYMBOL REQUIRED AT ALL TOILET SIGNAGE.
2. CHARACTERS AND THEIR BACKGROUND SHALL HAVE A NON-GLARE FINISH. CHARACTERS
SHALL CONTRAST WITH THEIR BACKGROUND WITH EITHER LIGHT CHARACTERS ON A
DARK BACKGROUND OR DARK CHARACTERS ON A LIGHT BACKGROUND.
3. PICTOGRAMS AND THEIR FIELD SHALL HAVE A NON-GLARE FINISH. PICTOGRAMS SHALL
CONTRAST WITH THEIR FIELD WITH EITHER A LIGHT PICTOGRAM ON A DARK FIELD OR A
DARK PICTOGRAM ON A LIGHT FIELD.
C
TTD
(b)
STALL
TYPE
SANS SERIF, UPPERCASE
1/32" MIN. RAISED CHARACTERS
ABOVE BACKGROUND
AR
B ARR E T T
SHOWER CURTAINS AND RODS (MEASURED FROM FLOOR TO BOTTOM OF CURTAIN)
A. GENERAL
= 1"
NOTE:
WHERE INSTALLED IN WET
LOCATIONS, THE SURFACE
OF THE SEAT SHALL BE SLIP
RESISTANT AND SHALL NOT
ACCUMULATE WATER.
TOILET BOYS 206
1/4" = 1'-0"
TOE CLEARANCE
LATCH
APPROACH
FINISHED FLOOR
4.
3'-0"
DOOR
PICTOGRAM FIELD ONLY
TILE (T-1 & T-2)
SEE DETAIL A2/A701
BENCH SHALL PROVIDE
FOR BACK SUPPORT OR
SHALL BE AFFIXED TO
A WALL.
FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF
THE WATER CLOSET EXCEPT IN AMBULATORY ACCESSIBLE
COMPARTMENTS (604.6)
REQUIRED CLEAR FLOOR SPACES, CLEARANCES AT FIXTURES,
AND TURNING SPACE SHALL BE PERMITTED TO OVERLAP.
(TAS 603.2.2)
DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE
PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE.
(TAS 603.2.3)
TOILET COMPARTMENT DOORS, SHALL HAVE PULLS ON BOTH
SIDES OF DOOR, NEAR THE LATCH.
LATCH
APPROACH
0
1.
3'-0"
DOOR
1/4" = 1'-0"
TE
SANITARY NAPKIN DISPOSAL UNIT (MEASURE FROM FLOOR TO TOP OF UNIT)
A. SIDE REACH
= 15" - 48" (UNOBSTRUCTED)
FINISH
FLOOR
8'
FINISHED FLOOR
C1
A
* SHALL NOT BE LOCATED BEHIND GRAB BARS
FLUSH CONTROL ON
WIDE SIDE
ED
S
TRANSFER SIDE
HEIGHT OF TACTILE CHARACTERS
ABOVE FINISH FLOOR OR GROUND
C2
URINALS (MEASURED FROM FLOOR TO RIM)
A. ADULT
= 24"
B. ACCESSIBLE
= 17" MAX.
ER
Y L OR
0
TYPICAL WALL
LAVATORY
LAVATORIES (MEASURED FROM FLOOR TO SINK RIM)
A. NON ACCESSIBLE 5 YEARS & YOUNGER
= PARALLEL APPROACH
COMPLYING WITH TAS 305
ELEM.SCH.
B. NON ACCESSIBLE 6 TO 12 YEARS
= 31" MAX (24" MIN. KNEESPACE)
BUBBLER
C. NON ACCESSIBLE ADULT
= 32"
D. ACCESSIBLE (ALL AGE GROUPS)
= 34" MAX (29" MIN. KNEESPACE)
*WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES AND SINKS SHALL BE INSULATED OR
OTHERWISE CONFIGURED TO PROTECT AGAINST CONTACT. THERE SHALL BE NO SHARP OR
ABRASIVE SURFACES UNDER LAVATORIES AND SINKS. (TAS 606.5)
EC T
ACCESSIBLE
MIRROR
ELEVATION
FIXTURE MOUNTING HEIGHT SCHEDULE
TA
A181
ARCHITECT
IT
WALL MOUNTED SOAP
DISPENSER
WALL MOUNTED
LAVATORY
18" X 36" CHANNEL FRAMED
TEMPERED GLASS MIRROR
(REFER TO ACCESSIBLE
MIRROR ELEVATION FOR
MIRROR HEIGHT AT
ACCESSIBLE LAVATORIES)
ENLARGED TOILET PLAN
1/4" = 1'-0"
CURTAIN ROD
AND CURTAIN w/ HOOKS
SHOWER
HEAD
A1
B1
WASHFOUNTAIN
NOTE: THE MOUNTING DEVICE FOR THE
HAND-HELD SHOWER HEAD SHALL FALL
WITHIN THE FORWARD REACH RANGES
H
4'-8 5/8"
URINAL
CHANNEL FRAMED MIRROR
(18" x 34" UNLESS NOTED
OTHERWISE)
TYPICAL ACCESSIBLE TRANSFER SHOWER STALL PLAN
NOTE : UNLESS NOTED OTHERWISE, 3 5 8" MTL STUDS at 16"o.c.
(MAX), ARE TO BE USED at TOILET WALLS, USE 'V' BAR BRACING
at 24" o.c., VERT. AT CHASE SIDE OF PLUMBING CHASE WALL.
(TYP)
D1
SOAP DISPENSER
ALL DIMENSIONS ARE FROM FINISH MATERIAL.
ALL TOILET ROOM WALLS EXTEND TO DECK, UNLESS OTHERWISE NOTED.
PROVIDE SOUND ATTENUATION BATT INSULATION IN STUD WALL CONSTRUCTION
AROUND TOILET ROOMS.
4. PROVIDE WALL MOUNTED DOOR STOPS IN RESTROOMS.
5. REFER TO SHEET A701 FOR INTERIOR FINISHES
6. EXTEND CERAMIC TILE UP TO AND AROUND MIRRORS ON WALLS WITH CERAMIC TILE
WAINSCOT.
7. REFER TO 'TOILET ROOM LEGEND' ON THIS SHEET FOR FIXTURES AND ACCESSORY INFO.
8. PROVIDE THE SAME FIXTURES AND ACCESSORIES AT ALL SINGLE ACCESSIBLE TOILET
ROOMS WHICH ARE TO BE PROVIDED AT TYPICAL FIXTURES, AS INDICATED IN 'TOILET
ROOM LEGEND'. PROVIDE ACCESSORIES FOR ACCESSIBLE WATER CLOSETS AS
INDICATED FOR A 'TYPICAL ACCESSIBLE STALL', PROVIDE ACCESSORIES FOR
ACCESSIBLE LAVATORIES AS INDICATED FOR A 'TYPICAL ACCESSIBLE WALL LAVATORY',
AND PROVIDE ACCESSORIES FOR ACCESSIBLE SHOWER STALLS AS INDICATED FOR A
'TYPICAL ACCESSIBLE SHOWER'.
9. REFER TO 'FIXTURE MOUNTING HEIGHT SCHEDULE' FOR MOUNTING HEIGHT
INFORMATION. ALL ACCESSIBLE FIXTURES AND EQUIPMENT, ARE TO BE ADULT
ACCESSIBLE FIXTURES & HEIGHTS , UNLESS NOTED OTHERWISE, FOR ELEMENTARY
SCHOOL HEIGHTS, OR FIXTURES FOR USE BY AGES 5 THRU 12.
10. COORDINATE INSTALLATION OF REQ'D BLOCKING AND STABILIZING FOR FIXTURES.
11. THE STRUCTURAL STRENGTH OF GRAB BARS AT ACCESSIBLE WATER CLOSETS SHALL
COMPLY WITH TAS 2012 - 609.8.
12. REFER TO TOILET ACCESSORIES SCHEDULE AND / OR SPECIFICATIONS FOR
ACCESSORIES AND INSTALLATION INFORMATION.
ST
E1
WALL MOUNTED
WATER CLOSET
1.
2.
3.
S
3 5/8"
3 5/8"
4'-2 3/8"
5'-2 1/2"
CONTROL WALL
5 1/2"
1'-6"
'ELL' SHAPED
GRAB BAR
TOILET TISSUE
DISPENSER
(TTD)
A
SEAT WALL
A181
SEE NOTE 'F'
SHT. A701
1"
3'-11 3/4"
C1
D1
3 5/8"
3 5/8"
4'-2 3/8"
19'-10 1/4"
8 1/2"
SHOWER SEAT
FLOOR MOUNTED
WATER CLOSET
200 LONGHORN STREET
VEGA, TEXAS 79092
BACK WALL
BAND HALL RENOVATION
6'-6 7/8"
T
3'-9 1/8"
TOILET PLAN GENERAL NOTES
IS
3'-2"
TOILET ROOM LEGEND
3 5/8"
E
5'-1 1/2"
3 5/8"
1"
R EG
3 5/8"
1"
C H AR L
19'-4 5/8"
D. SHOWER - TRANSFER
TYPE
* OTHER
APPROACHES
48" MIN.
D/P/S
DRAWN BY
= 17" - 19" ABOVE BATHROOM FINISH FLOOR
= 15" - 16" DEPTH (REMOVABLE)
= 15" DEPTH (PERMANENT, EXTEND FROM BACK TO OR BEYOND
THE OUTER EDGE OF THE BATHTUB)
= FOLDING TYPE, INSTALLED ON SIDE WALL ADJACENT TO
CONTROLS, EXTEND FROM BACK WALL TO A POINT WITHIN 3"
OF THE COMPARTMENT ENTRY
= FOLDING TYPE, INSTALLED ON FRONT WALL OPPOSITE THE
BACK WALL, EXTEND FROM THE ADJACENT SIDE WALL TO A
POINT WITHIN 3" OF THE COMPARTMENT ENTRY
= 17" - 19" ABOVE BATHROOM FINISH FLOOR. SEAT SHALL
EXTEND FROM BACK WALL TO A POINT WITHIN 3" OF THE
COMPARTMENT ENTRY.
CANE
APRON
REVIEWED BY
JW
7/29/2016
DATE
PROJECT NO.
14-0424.002
DRAWING NAME
TAS INFORMATION
ENLARGED TOILET
PLANS, & TOILET
ELEVATIONS
ADULT FLOOR MOUNTED WATER CLOSET
& CHILDREN'S WATER CLOSET
COMPARTMENT
ENTRY
RECTANGULAR SHOWER SEAT
COMPARTMENT
ENTRY
L-SHAPED SHOWER SEAT
HI - LO
E.W.C. ELEVATION
A181
1'-4"
FINISHED
CEILING
LIGHT FIXTURE
REFER TO
ELECTRICAL
'J' MOULD at
PERIMETER
(TYP)
GYP. BOARD
0
3"
6"
B2
9"
0
1/2" = 1'-0"
1'
2'
B3
4'
ARCHITECT
MECH. SUSP. GYP BD CEILING
0
1" = 1'-0"
1/2'
2'
1'
TA
TE
Y L OR
ST
A
C
18563
OF
4' x 4' PYRAMID DIFFUSER
(TYPICAL OF 3)
EC T
E
AR
B A RRE T T
C H AR L
S
ED
IT
R EG
ER
H
T
IS
3" = 1'-0"
SUSPENDED APC CLG DET.
S
B1
(REFER RCP)
CAULK ALL AROUND
AT WALL / CLG ANGLE
(TYP)
8'-0"
AFF
EGG CRATE LENS
SECTION, TYP.
CLG. HT.
ABOVE FIN.FLR.
STRUCTURE ABOVE
SUSPENSION WIRE
3 5 8" MTL STUD
FRAMING (TYP)
TYP SUSPENDED GDW
CEILING SYSTEM, UON:
5
8" GYP BD (PAINTED) ON
7
8" FURRING CHANNELS
AT 16" o.c., ON 1-1/2" C
RUNNER CHANNELS AT 36"
o.c. w/ 8 GA HANGER WIRE
AT 48" o.c., UON
A
8"
1'-0"
5
TE
X
ENGINEER
MATERIAL LEGEND
GYP. BOARD LIGHT COVE
B2
A501
4' x 4' & 2' x 2' 'WENGER'
TYPE, ACOUSTICAL
PYRAMID DIFFUSERS
PROJECT
A TROPHY DISPLAY
SHELF - ABOVE 2"
ACOUSTICAL WALL
PANEL - BUT, BELOW
2' x 2' CEILING GRID
2' x 2' PYRAMID DIFFUSER
(TYPICAL OF 8)
11'-0"
A.F.F.
MECHANICALLY
SUSPENDED 5 8" GYP. BRD.
CEILING (TO PAINT)
11'-0"
A.F.F.
11'-0"
A.F.F.
BAND HALL RENOVATION
ACP - ARMSTRONG
# 1894 - 24" x 24" x 3 4" w/
NRC = .60
(TEGULAR EDGE) IN
'SUPRAFINE' ML 9 16"
EXPOSED TEE SYSTEM,
ALSO by ARMSTRONG
5
8" GYP. BRD. DROPPED
HEADWALL (TO PAINT)
ON MTL STUD FRAMING
B2
2 x 4 FLUORESCENT
TROFFERS - SEE
ELECTRICAL DOC's (TYP)
A501
LED RECESSED CAN LIGHT
FIXTURES - SEE ELECTRICAL DOC's
EXIT LIGHTS - SEE ELECTRICAL DOC's
B2
A501
LIGHT COVE STRIP FIXTURES SEE ELECTRICAL DOC's
SUPPLY AIR DIFFUSERS SEE MECHANICAL DOC's
200 LONGHORN STREET
VEGA, TEXAS 79092
11'-0" AFF
OR AS HIGH AS POSSIBLE
EX GR
RETURN AIR DIFFUSERS SEE MECHANICAL DOC's
LINEAR RECESSED
FLUORESCENT LIGHT
FIXTURE
9'-0"
A.F.F.
B1
A501
9'-0"
A.F.F.
8'-0"
A.F.F.
EXHAUST GRILLES SEE MECHANICAL DOC's
GYP. BRD.
HEADWALL
EX GR
REVISIONS
9'-0"
A.F.F.
8'-0"
A.F.F.
9'-0"
A.F.F.
9'-2"
A.F.F.
9'-0"
A.F.F.
9'-0"
A.F.F.
9'-0"
A.F.F.
B1
A501
B2
D/P/S
DRAWN BY
A501
REVIEWED BY
EX GR
RO/JW
7/29/2016
DATE
PROJECT NO.
14-0424.002
DRAWING NAME
A1
REFLECTED CEILING PLAN
1/4" = 1'-0"
0
2'
4'
8'
NORTH
REFLECTED CEILING
PLAN
MATERIAL LEGEND
CLG DETAILS NOTES
A501
47 8"
DOOR AND FRAME SCHEDULE
DOOR
5
8"
35 8"
SIZE
MARK
W
H
201
3'-0" 7'-0"
202 PR 3'-0" 7'-0"
203
3'-0" 7'-0"
204
3'-0" 7'-0"
205
3'-0" 7'-0"
206
3'-0" 7'-0"
207
3'-0" 7'-0"
208
3'-0" 7'-0"
8"
O.A. FRAME
HEIGHT
2"
5
FRAME
LOUVER
DETAIL
THK MATL EL GLZ W
H MATL EL GLZ HEAD
JAMB SILL FIRE RATING LABEL
1 3/4" SC WD D1 ---HM F1 -- B2/A601 A1/A601 --1 3/4" SC WD D2 ---HM F2 -- B2/A601 A1/A601 --1 3/4" SC WD D1 ---HM F1 -- B2/A601 A1/A601 --1 3/4" SC WD D1 ---HM F1 -- B2/A601 A1/A601 --1 3/4" SC WD D1 ---HM F1 -- B2/A601 A1/A601 --1 3/4" SC WD D1 ---HM F1 -- D1/A601 C1/A601 --1 3/4" SC WD D1 ---HM F1 -- D1/A601 C1/A601 --1 3/4" SC WD D1 ---HM F1 -- D1/A601 C1/A601 ---
NOTES
FRAME IN WD STUDS
" " " "
" " " "
" " " "
FRAME IN WD STUDS
FRAME IN MTL STUDS
" " " "
FRAME IN MTL STUDS
57 8"
ARCHITECT
WALL / FIXTURE WHERE OCCURS
OF
S
A
IS
E
R EG
C H ARL
18563
TE
X
ENGINEER
5
8"
47 8"
7'-0"
7'-0"
8"
5
35 8"
Y L OR
TE
C
EC T
57 8"
AR
B ARR E T T
TA
A
DOOR MARK KEY
ED
IT
6'-0"
S
ST
3'-0"
ER
H
T
PROJECT
B5
AT
EXIST'G
WALLS
DOOR ELEVATIONS
1/4" = 1'-0"
3'-4"
B2
0
AT
EXIST'G
WALLS
2'
8'
4'
6'-4"
B2
A601
2"
A601
2"
2"
6'-4"
B1
A601
2"
2"
A1
A601
A601
SIM
3'-0"
A601
SIM
A1
7'-2"
A1
7'-2"
7'-2"
4'-2"
2"
2"
2"
AT
EXIST'G
WALLS
2"
4"
O.A. FRAME
HEIGHT
O.A. FRAME
HEIGHT
2"
4"
1
C5
DOOR FRAME / BORROWED LIGHT ELEVATIONS
1/4" = 1'-0"
0
2'
4'
8'
200 LONGHORN STREET
VEGA, TEXAS 79092
O.A. FRAME
WIDTH
BAND HALL RENOVATION
2"
GENERAL DOOR AND WINDOW NOTES:
1. ALL DOORS TO BE 1 3/4" THICK (UON)
2. ALL STL FRAMES TO HAVE A 2" FACE DIMENSION UON, W/ 5/8"
STOP. 3/4" STOP REQUIRED FOR FIRE RATED FRAMES, UON.
3. STEEL FRAME DEPTHS INDICATED IN THE DETAILS ARE
NOMINAL. PROVIDE STANDARD WIDTH FRAME WITH THROAT
OPENING APPROPRIATE TO WALL TYPE.
REVISIONS
4. COORDINATE WITH MECH DOCUMENTS FOR DOOR
UNDERCUTS AND DOOR LOUVERS, IF ANY.
5. ALL LIGHTS IN DOORS TO HAVE SAFETY GLAZING (UON).
1'-0"
41
6. NOT USED.
2"
7. FIELD VERIFY DIMENSIONS PRIOR TO FABRICATING FRAMES.
2"
2"
8. PROVIDE WD BLKG IN GYP BD WALLS BEHIND DOORS
SCHEDULED TO HAVE WALL MOUNTED DOOR STOPS. (REFER
HARDWARE SCHEDULE).
9. FLOOR MATERIAL CHANGES BETWEEN ROOMS TO OCCUR
UNDER DOOR.
10. IF A DOOR HAS A CLOSER, THEN THE SWEEP PERIOD OF THE
CLOSER SHALL BE ADJUSTED SO THAT FROM AN OPEN POSITION
OF 70 DEGREES, THE DOOR WILL TAKE AT LEAST 3 SECONDS TO
MOVE TO A POINT 3" (75 mm) FROM THE LATCH, MEASURED TO
THE LEADING EDGE OF THE DOOR.
11. THE MAXIMUM FORCE FOR PUSHING OR PULLING OPEN A
DOOR SHALL BE AS FOLLOWS:
(1) FIRE DOORS SHALL HAVE THE MINIUMUM OPENING FORCE
ALLOWABLE BY THE APPROPRIATE ADMINISTRATIVE AUTHORITY.
(2) OTHER DOORS.
(a) EXTERIOR HINGED DOORS: (RESERVED)
(b) INTERIOR HINGED DOORS: 5 lbf (22.2N)
(c) SLIDING OR FOLDING DOORS: 5 lbf (22.2N)
DRAWN BY
RKO
REVIEWED BY
RKO
DATE
7/29/2016
14-0424.002
PROJECT NO.
DRAWING NAME
DOOR SCHEDULE
DOOR & BORROWED
LITE FRAMES DETAILS
A601
S
18563
OF
A
TE
Y L OR
ST
A
C
TA
C H AR L
S
AR
B ARR E T T
EC T
E
IS
ED
IT
R EG
ER
H
T
ARCHITECT
TE
X
ENGINEER
RB-1
C1
ACP-1
P-1
D1
P-3
RB-1
A771
B1
ACP-1
A1
P-1
A771
PORCELAIN TILE
(PT-1)
B3
RB-1
ACP-1
P-1 BELOW
ACOUSTICAL PANEL
B2
PORCELAIN TILE
(PT-2)
200 LONGHORN STREET
VEGA, TEXAS 79092
BAND HALL RENOVATION
6'-0"
PROJECT
WALLS: PT-1 & PT-2
SEE DETAIL A2/A701
CEILING: P-4
REVISIONS
RB-1
ACP-1
P-1
E1
A181
D/P/S
DRAWN BY
REVIEWED BY
JW
A3
7/29/2016
DATE
P-1
RB-1
5'-0 7/8"
WALLS: PT-1 & PT-2
SEE DETAIL A2/A701
CEILING: P-4
P-1
RB-1
PROJECT NO.
A771
P-1
RB-1
14-0424.002
DRAWING NAME
FINISH FLOOR
PLAN
A2
P-3
A1
A2
FINISH FLOOR PLAN
1/4" = 1'-0"
0
2'
4'
8'
TILE PATTERN
1" = 1'-0"
0
1/2'
1'
2'
A701
ACOUSTICAL PANEL
(ACP-2)
1'-7 1/2"
FINISHED CEILING
PLASTIC LAMINATE
SHELF (PL-1)
1'-10"
1'-10"
DIMENSIONAL ACOUSTICAL PANELCOLOR TO MATCH LONGHORN PANELS
AUDITORIUM REMODEL
ACOUSTICAL PANEL
(ACP-1)
1'-0"
2 3/4"
5 1/2"
3'-6"
TACKBOARD
4'
8'
E
ST
DIMENSIONAL ACOUSTICAL PANELCOLOR TO MATCH LONGHORN PANELS
AUDITORIUM REMODEL
A
DIMENSIONAL ACOUSTICAL PANELCOLOR TO MATCH LONGHORN PANELS
AUDITORIUM REMODEL
ACOUSTICAL PANEL
(ACP-2)
TE
C
Y L OR
C H AR L
S
AR
B A RR E T T
TA
R EG
ED
18563
OF
EC T
1'-0"
ER
IT
IS
2'
T
0
1/4" = 1'-0"
9'-0"
BAND HALL 200 ELEVATION
ARCHITECT
S
SCHLUTER
DILEX TRIM
H
D1
FINISHED FLOOR
3'-3 1/4"
PORCELAIN TILE
PT-1 & PT-2
RUBBER BASE (RB-1)
A
3 - 78 COMPARTMENT
FOLIO STORAGE
CABINETRY
BY STEVENS
4'-6"
9'-0"
10'-10"
1'-0"
PAINT (P-1)
6"
TE
X
FINISHED CEILING
ENGINEER
3'-5"
1'-0"
1'-6"
4"
PLASTIC LAMINATE
SHELF (PL-1)
10'-10"
PAINT (P-1)
8'-0"
ACOUSTI-GRILLE INSTRUMENT
STORAGE
RUBBER BASE (RB-1)
PROJECT
FINISHED FLOOR
2'
4'
C2
8'
A1
DIMENSIONAL ACOUSTICAL PANELCOLOR TO MATCH LONGHORN PANELS
AUDITORIUM REMODEL
A101
0
1" = 1'-0"
1/2'
2'
1'
ACOUSTICAL PANEL
(ACP-2)
FINISHED CEILING
FINISHED CEILING
FINISHED CEILING
ACOUSTICAL
PANEL
ACP-1
PAINT (P-1)
B1
BAND HALL 200 ELEVATION
1/4" = 1'-0"
0
2'
4'
MARKER BOARD
SMART BOARD
PAINT (P-1)
MARKER BOARD
FINISHED FLOOR
ELEMENTARY MUSIC 208 ELE.
0
1/4" = 1'-0"
2'
4'
RUBBER BASE (RB-1)
2'-10"
2'-10"
RUBBER BASE (RB-1)
B2
8'
ACOUSTICAL PANEL
ACP-1
4"
TACKBOARD
RUBBER BASE (RB-1)
FINISHED FLOOR
11'-0"
PAINT (P-1)
4'-0"
8'-0"
11'-0"
10'-10"
4"
1'-0"
3'-10"
3'-10"
ACOUSTICAL PANEL
(ACP-1)
4'-0"
4"
1'-6"
PLASTIC LAMINATE
SHELF (PL-1)
FINISHED FLOOR
ELEMENTARY MUSIC 208 ELE.
B3
8'
200 LONGHORN STREET
VEGA, TEXAS 79092
0
1/4" = 1'-0"
MILLWORK SECTION
BAND HALL RENOVATION
C1
BAND HALL 200 ELEVATION
0
1/4" = 1'-0"
2'
4'
8'
REVISIONS
ACOUSTICAL PANEL
(ACP-1)
FINISHED CEILING
C2
C3
PLASTIC LAMINATE
SHELF (PL-1)
A771
A771
A1
1/4" = 1'-0"
0
2'
4'
8'
A2
PAINT (P-1)
REVIEWED BY
3'-0"
PLASTIC
LAMINATE
SHELF (PL-1)
FINISHED
FLOOR
FINISHED FLOOR
BAND HALL 200 ELEVATION
DRAWN BY
UNIFORM STOR. 203 ELE.
1/4" = 1'-0"
0
2'
4'
8'
D/P/S
JW
7/29/2016
DATE
PLASTIC
LAMINATE
CABINETRY (PL-1)
6'-0"
5'-8"
9'-0"
NEED TO VERIFY
HOW MANY BAND
STUDENTS FOR
THE HAT/SHOE
STORAGE. OR
DIMENSIONS ON
HAT SIZE.
RUBBER
BASE (RB-1)
FINISHED
FLOOR
4"
RUBBER BASE
(RB-1)
FINISHED
CEILING
RUBBER
BASE (RB-1)
3'-6"
8'-0"
9'-0"
SMART BOARD
FINISHED
CEILING
PAINT (P-1)
7'-3 1/4"
10'-10"
1 3/4"
1'-0"
PAINT (P-1)
3'-6"
DIMENSIONAL ACOUSTICAL PANELCOLOR TO MATCH LONGHORN PANELS
AUDITORIUM REMODEL
1 1/2"
ACOUSTICAL PANEL
(ACP-2)
1'-8 3/4"
1'-10"
DIMENSIONAL ACOUSTICAL PANELCOLOR TO MATCH LONGHORN PANELS
AUDITORIUM REMODEL
A3
PROJECT NO.
14-0424.002
DRAWING NAME
INTERIOR
ELEVATIONS
UNIFORM STOR. 203 ELE.
1/4" = 1'-0"
0
2'
4'
8'
A771
Digitally signed by Abbas
Date: 2016.07.29
09:13:56-06'00'
Digitally signed by
Abbas
Date: 2016.07.29
09:14:13-06'00'
Digitally signed by
Abbas
Date: 2016.07.29
09:14:32-06'00'
Digitally signed by
Abbas
Date: 2016.07.29
09:14:43-06'00'
Digitally signed by
Abbas
Date: 2016.07.29
09:14:53-06'00'
Digitally signed by
Abbas
Date: 2016.07.29
09:15:34-06'00'
Digitally signed by
Abbas
Date: 2016.07.29
09:15:45-06'00'
Digitally signed by Abbas
Date: 2016.07.29
09:15:57-06'00'
Digitally signed by Abbas
Date: 2016.07.29
09:16:08-06'00'
Digitally signed by Abbas
Date: 2016.07.29
09:16:21-06'00'
1
2
3
4
5
(NOT ALL SYMBOLS APPLY TO THIS PROJECT)
ELECTRICAL SYMBOL LEGEND
UPDATED: 03/03/2014
AMPS, AMPERE, AMPERAGE
ABOVE COUNTER
ALTERNATING CURRENT
AMERICANS WITH DISABILITIES ACT
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AVAILABLE INTERRUPTING CURRENT
ALUMINUM
AMERICAN NATIONAL STANDARDS INSTITUTE
AUTOMATIC TRANSFER SWITCH CONTROL
AUTOMATIC TRANSFER SWITCH
AUDIO/VISUAL
AMERICAN WIRE GAUGE
CONDUIT
CIRCUIT BREAKER
CLOSED CIRCUIT TELEVISION
CIRCUIT
CLOCK
CURRENT LIMITING FUSE
CONDUIT ONLY
COPPER
DIMMING
DIRECT CURRENT
DAY-LIGHTING
DIAMETER
EMERGENCY
EMERGENCY, CRITICAL
ENGINE GENERATOR
EMERGENCY, LIFE SAFETY
EMERGENCY, EQUIPMENT
EXISTING
FUTURE
FIRE ALARM
FIRE ALARM ANNUNCIATOR
FIRE ALARM CONTROL PANEL
FIRE ALARM TERMINAL CABINET
FEEDER
FACILITY MANAGEMENT SYSTEM
GENERATOR
GROUND FAULT INTERRUPTER
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT EQUIPMENT PROTECTION
GROUND FAULT PROTECTION
GROUND.
HAND-OFF-AUTOMATIC.
HORSEPOWER
INSTITUTE OF ELECTRICAL AND ELECTRONICS
ENGINEERS
ISOLATED GROUND
THOUSAND CIRCULAR MILS
KILOVOLT
KILOVOLT AMPS
KILOVOLT AMPS REACTIVE
KILOWATT
KILOWATT HOUR.
LONG TIME, SHORT TIME, INSTANTANEOUS,
AND GROUND FAULT PROTECTION
MAXIMUM
MOTOR CONTROL CENTER
MINIMUM
MANHOLE
MIXED MEDIA
MANUAL TRANSFER SWITCH
MEGAVOLT AMPS
NEW
NOT APPLICABLE
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NEUTRAL
NATIONAL FIRE PROTECTION ASSOCIATION
NOT IN CONTRACT
NORMAL
NEW MEXICO
NORMALLY OPEN
OVERHEAD
POLE
PUBLIC ADDRESS
PHOTOCELL
PHASE
POWER MONITORING AND CONTROL SYSTEM
REMOVED/REMOVAL
ROOM CONTROLLER
RIGID STEEL CONDUIT
SECURITY
SURGE PROTECTIVE DEVICE
SWITCH
TEMPORARY
TELEPHONE TERMINAL BOARD
TELEVISION
TRANSIENT VOLTAGE SURGE SUPPRESSER
TYPICAL
UNDER COUNTER
UNDERGROUND
UNDERGROUND ELECTRIC
UNDERWRITERS' LABORATORIES
UNLESS OTHERWISE NOTED
UNINTERRUPTABLE POWER SUPPLY
VOLTS, VOLTAGE
VARIABLE FREQUENCY DRIVE
WALL MOUNTED
WEATHERPROOF AND GFCI
WEATHERPROOF
TRANSFER
TRANSFORMER
C
IG
KCMIL
KV
KVA
KVAR
KW
KWH
LSIG
MAX
MCC
MIN
MH
MM
MTS
MVA
N
N/A
NC
NEC
NEMA
B
NEUT
NFPA
NIC
NL
NM
NO
O/H
P
PA
PC
PH
PMCS
R
RC
RSC
SEC
SPD
SW
TEMP
TTB
TV
TVSS
TYP.
UC
U/G
UGE
UL
UON
UPS
V
VFD
W
WG
WP
XFER
XFMR (TRANSF)
REFERENCE TAGS
SYMBOL
1, 2, 3, . . = SUBFED PANEL
VAV-9
1, 2, 3, . . = FLOOR LEVEL
(SB=SUB-BASEMENT, B=BASEMENT, M=MEZZANINE,
P=PENTHOUSE)
T
= TRANSFORMER
DB = DISTRIBUTION BOARD
MSB = MAIN SWITCH BOARD
MCC= MOTOR CONTROL CENTER
I
= ISOLATED PANELBOARD
ATS = AUTOMATIC TRANSFER SWITCH
PDU = POWER DISTRIBUTION UNIT
UPS = UNINTERRUPTABLE POWER SUPPLY
B
= BUSWAY
H
L
SYMBOL
X
X
= HIGH VOLTAGE PANELBOARD (480Y/277V)
= LOW VOLTAGE PANELBOARD (208Y/120V)
X
BLANK FOR NORMAL POWER
E
= EMERGENCY
EL = EMERGENCY-LIFE SAFETY-BRANCH
EC = EMERGENCY-CRITICAL-BRANCH
EQ = EMERGENCY-EQUIPMENT-BRANCH
SES = SERVICE ENTRANCE SECTION
NUMBER OR MAIN EMERG SWBD NUMBER
EXAMPLES:
A.
SES1 (SERVICE ENTRANCE SECTION #1)
B.
1H1A (SERVED FROM SES#1, 480/277 NORMAL, LEVEL 1, FIRST BOARD)
C.
1EQH1A (SERVED FROM MAIN EMER SWBD #1, 480/277 EQUIP POWER,
LEVEL 1, FIRST BOARD)
RACEWAY & CONDUCTORS
BRANCH CIRCUIT GENERAL INFORMATION:
SYMBOL
= NEUTRAL
HOMERUN FROM EQUIPMENT LOCATION. THE CIRCUIT
NUMBER ADJACENT TO HOMERUN INDICATES PANEL
SOURCE AND INDIVIDUAL TWO OR THREE POLE CIRCUIT
BREAKERS. CONDUCTOR IDENTIFICATION SYMBOL
INDICATES NUMBER OF CONDUCTORS IN HOMERUN.
MINIMUM #12 CONDUCTORS AND 3/4" RACEWAY PATH
WILL BE PROVIDED IN HOMERUN UON. NEUTRAL MAY BE
USED WHERE INDICATED ON PLAN. ALL HOMERUNS WILL
INCLUDE GROUND CONDUCTOR.
LA-7
LA-13
DENOTES MOUNTING HEIGHT AFF
KITCHEN EQUIPMENT REFERENCE
GENERAL DRAWING SYMBOLS
A
6
E4
E4
DEVICE INDICATOR LETTER. "X" EQUALS
DESIGNATION BELOW
(TYPICAL FOR MOST SWITCH TYPES):
6
A
E3 E4
E3 E4
SECTION/ELEVATION LETTER OR DETAIL
NUMBER
30/3R
LIGHTNING PROTECTION AIR TERMINAL
ROOF
VARIES
OS
L1A
THERMOSTAT
WALL
+44"
UON
OS
ENCLOSED CIRCUIT BREAKER.
AMPERAGE/NEMA ENCLOSURE RATING, 3 POLE
UON
30/1
NON-FUSED DISCONNECT SWITCH.
AMPERAGE/NEMA ENCLOSURE RATING, 3 POLE
UON
30/3R
FUSED DISCONNECT SWITCH.
AMPERAGE/NEMA ENCLOSURE RATING, 3 POLE
UON
0/1
MOTOR STARTER. STARTER SIZE INDICATED
BY NUMBER/NEMA ENCLOSURE RATING,
SINGLE SPEED UON
1/30/3R
COMBINATION FUSIBLE DISCONNECT SWITCH
AND MOTOR STARTER. NEMA STARTER
SIZE/AMPERAGE/NEMA ENCLOSURE RATING, 3
POLE UON
5
MOTOR. NUMBER INDICATES HORSEPOWER
RATING FOR 1HP AND LARGER
F
MOTOR. "F" INDICATES FRACTIONAL
HORSEPOWER
CEILING MOUNTED OCCUPANCY SENSOR; TYPE
AS INDICATED ON PLANS
DAY-LIGHTING SENSOR; TYPE AS INDICATED
ON PLANS
ROOM CONTROLLER; TYPE AS INDICATED
ON PLANS
DL
RC
VARIES
VFD
300
400
X
X
X
300
400
300
400
UPS-A
X
X
UT
AUTOMATIC TRANSFER SWITCH. DASHED LINES INDICATE CLEARANCES.
ATS-1
G
DEMOLITION
DESCRIPTION
NOTES
DASHED SYMBOL INDICATES EXISTING
DEVICE OR EQUIPMENT TO BE REMOVED
NORTH
R
REMOVE EXISTING RACEWAY IN ALL ACCESSIBLE
AREAS. CAPPED AND ABANDONED IF IN
UNACCESSIBLE AREA
SOLID SYMBOL, LIGHTER IN COLOR
INDICATES EXISTING DEVICE OR EQUIPMENT
TO REMAIN
80'
SCALE BAR OR MATCH ARCHITECT'S
EX
S
CC
GROUND BAR
EXISTING CONDUIT TO BE REUSED
REFER TO
DEMOLITION
PLANS FOR
ADDITIONAL
INFORMATION
PHOTOELECTRIC SMOKE DETECTOR
IONIZATION SMOKE DETECTOR
I
R/F
COMBINATION RATE OF RISE / FIXED
TEMPERATURE
F
FIXED TEMERATURE; TEMPERATURE AS
NOTED ON PLANS OR SPECIFICATIONS
VARIES
X
BEAM TRANSMITTER
BT
BEAM RECEIVER
UNDER FLOOR SMOKE DETECTOR
U
FIRE/SMOKE DAMPER
AS
DETAILED
PS
PRESSURE SWITCH
TS
TAMPER SWITCH
FS
FLOW SWITCH
PIV
POST INDICATOR VALVE
+44"
UON
WALL
M
MAGNETIC DOOR HOLDER
R
CONTROL RELAY
DRAWOUT CIRCUIT BREAKER
TRIP SETTING
FRAME SIZE
MEDIUM VOLTAGE DRAWOUT
CIRCUIT BREAKER
TRIP SETTING
FRAME SIZE
208Y/120V
UTILITY OR FACILITY TRANSFORMER
CONNECTION CABINET (UTILITY
METER MOUNT)
PM
PRIMARY SITE METER ENCLOSURE
ME
METER ENCLOSURE. EITHER ON BUILDING OR ON UTILITY
EQUIPMENT
T1A
75kVA
K-4
480V
CT
CT ENCLOSURE. EITHER ON BUILDING OR ON UTILITY EQUIPMENT
ENGINE GENERATOR
TP
TELECOMMUNICATION PEDESTAL
TVP
TELEVISION PEDESTAL
SEE
PLANS
AT
DUCT
SEE
PLANS
PIPE
VARIES
ENGINEER
300A
DISCONNECT SWITCH. "300A"
DENOTES AMPERAGE RATING
300A
FUSE. "300A" DENOTES AMPERAGE
RATING
SYMBOL
CEILING
SURFACE
Jxx
DESCRIPTION
4 PORT FLOOR BOX WITH A/V. REFER TO J-BOX
SCHEDULE ON 600 SERIES SHEETS.
B
2 PORT VOICE\DATA OUTLET ROUGH-IN ONLY
WALL
W
TELEPHONE OUTLET WALL MOUNTED
KW
KILOWATT METER
+18"
UON
+18"
UON
WALL
+44"
UON
WALL
+84"
UON
WALL
+108
UON
WALL
SEE
PLANS
A/V JUNCTION BOX. REFER TO J-BOX SCHEDULE
ON 600 SERIES SHEETS.
A/V J- BOXES STACKED VERTICALLY. REFER TO
J-BOX SCHEDULE ON 600 SERIES SHEETS.
WALL
SEE
PLANS
C S
COMBINATION CLOCK/SPEAKER. MOUNTED
ABOVE AND CENTER TO WRITING/TACK BOARD
WALL
SEE
PLANS
VC
VOLUME CONTROL FOR PAGING LOUDSPEAKER
WALL
SEE
PLANS
VP
VIDEO PROJECTOR
REFER TO PLANS
S
CEILING SPEAKER: LOCAL SOUND SYSTEM
IC
INTERCOM CALL SWITCH
INTERCOM MASTER STATION
S
COMMUNICATION HORN
COMMUNICATION BELL
S
WALL SPEAKER
LD
J Jx
Jx
J
Jx
J
PA
DURESS ALARM PUSHBUTTON
LOCK DOWN PUSHBUTTON
CEILING
FLUSH
REVISIONS
J-HOOK ROUTING PATH
2 PORT CEILING MOUNTED VOICE/DATA OUTLET
Jx
J
SEE
PLANS
CEILING MOUNTED A/V JUNCTION BOX. REFER TO
J-BOX SCHEDULE ON 600 SERIES SHEETS.
SECURITY
MOUNTING
LOC.
HT.
DESCRIPTION
ELECTRONIC METER
K1
KIRK KEY INTERLOCK No.1
R1
RELAY No.1
AS
AMMETER SWITCH
INTERIOR SECURITY CAMERA
AMMETER
INTERIOR SECURITY CAMERA 180°
VOLTMETER SWITCH
INTERIOR SECURITY CAMERA 360°
KEY PAD
EXTERIOR SECURITY CAMERA
WALL,
UON
+44"
UON
VARIES
SEE
PLANS
VARIES
SEE
PLANS
GLASS BREAK DETECTOR
WINDOW
SEE
PLANS
MD
MOTION DETECTOR
CEILING
SEE
PLANS
DS
DOOR SWITCH
MOTOR CONNECTION
ES
ELECTRIC STRIKE
DOOR
SEE
PLANS
UPS
M
MAGNETIC LOCK
VOLTMETER
G
DELTA CONNECTED
WYE CONNECTED
-
DRAWN BY
REVIEWED BY
CARD READER.
M
KP
ABOVE
CEILING
WIRELESS ACCESS POINT
SYMBOL
CR
100 % CONSTRUCTION
DOCUMENTS
CEILING SPEAKER: INTERCOM SYSTEM
SURGE ARRESTOR
SURGE PROTECTIVE DEVICE
VARIES
SEE
PLANS
CABLE TRAY FOR COMMUNICATIONS
TRANSFER SWITCH. SEE PLANS
FOR TYPE OF SWITCH
V
FLOOR
WALL
S IC
GROUND CONNECTION
SPD
SEE
PLANS
MOUNTING
LOC.
HT.
2 PORT VOICE\DATA OUTLET
SHUNT TRIP OPERATOR
VS
VARIES
4 PORT FLOOR BOX WITH POWER AND DATA
GROUND FAULT PROTECTION
ST
PROJECT
SPECIAL SYSTEMS
Jx
J
CURRENT TRANFORMER, NUMBER
"3000/5" DENOTES RATIO.
G
A
EG
UNDER
FLOOR
4600 C Montgomery Blvd. NE
Albuquerque, NM 87109
505.883.4111 www.bpce.com
ADDRESSABLE/SUPERVISED RELAY
R
PAD MOUNTED SWITCH
HH
VARIES
REMOTE ALARM INDICATING LIGHT
TRANSFORMER. TRANSFORMER NAME, TRANSFORMER kVA RATING,
PRIMARY VOLTAGE AND WIRING CONFIGURATION, SECONDARY
VOLTAGE, K RATING (IF APPLICABLE)
UNDERGROUND UTILITY AND OR SYSTEM DISTRIBUTION.
HAND HOLE - POWER OR COMMUNICATION
AS INDICATED ON PLANS
CEILING
OR WALL
Digitally signed by
William D. Herbst
Date: 2016.07.29
11:03:39-06'00'
MONITOR MODULE
MM
WAP
MANHOLE - POWER OR COMMUNICATION
AS INDICATED ON PLANS
SURFACE
BR
J
OVERHEAD UTILITY AND OR SYSTEM DISTRIBUTION.
MH
CEILING
RATE OF RISE ONLY
DA
N/A
DESCRIPTION
N = NEW
EX = EXISTING
VARIABLE FREQUENCY DRIVE
+80"
UON
P
B
P = ELECTRICAL PRIMARY
S = ELECTRICAL SECONDARY
T = TELECOMMUNICATION
TV = TELEVISION
E = EMERGENCY POWER
ATSC = AUTOMATIC TRANSFER SWITCH CONTROL
DRY TYPE TRANSFORMER (LESS THAN 15kVA), WITH NO EQUIPMENT TAG.
SIZE, TYPE AND LOCATION NOTED ON PLANS.
WALL
BELL (GONG)
B
CIRCUIT BREAKER; TRIP SETTING/FRAME SIZE OR NO. OF POLES.
SETTINGS AND PROTECTION AS NOTED ON PLANS
3PH = THREE PHASE
1PH = SINGLE PHASE
DRY TYPE TRANSFORMER (15kVA OR ABOVE), WITH EQUIPMENT TAG
(TAG INSIDE OR OUTSIDE, DEPENDING ON SIZE). IN MOST CASES,
ACTUAL SIZE SHOWN ON PLANS (ELECTRICAL ROOMS).
+44"
STROBE LIGHT ONLY
ICM
DISTRIBUTION POLE FOR OVERHEAD ELECTRICAL OR
COMMUNICATIONS AS INDICATED ON PLAN.
UNINTERRUPTABLE POWER SUPPLY. DASHED LINES INDICATE
CLEARANCES.
CHIME NOTIFICATION
VARIES
MAIN SWITCHBOARD. DASHED LINES INDICATE CLEARANCES.
SYMBOL
WALL
DESCRIPTION
3000/5
MOTOR CONTROL CENTER. DASHED LINES INDICATE CLEARANCES.
T
C
ONE-LINE DIAGRAM
SYMBOL
DESCRIPTION
MCC
T1A
SPEAKER NOTIFICATION
WALL MOUNTED OCCUPANCY SENSOR; TYPE
AS INDICATED ON PLANS
UTILITIES
SYMBOL
1" = 40'-0"
VARIES
SEE
PLANS
VARIES
SEE
PLANS
N/A
FIRE ALARM RACEWAY
DRAWING NUMBER WHERE TAKEN
40'
X
DISTRIBUTION BOARD. DASHED LINES INDICATE CLEARANCES.
DRAWING NUMBER WHERE DETAILED
NORTH ARROW OR MATCH ARCHITECT'S
LOW VOLTAGE SWITCH CONTROL. REFER TO
PLANS FOR TYPE.
CODE SIZE PULLBOX (OR AS SIZED ON PLAN)
CB
DATA RACEWAY
VOICE/DATA COMBINATION RACEWAY
SURFACE MOUNTED PANELBOARD. DASHED LINES INDICATE
CLEARANCES.
S
COMBINATION SPEAKER AND CHIME
NOTIFICATION
SPEAKER/HORN WITH STROBE LIGHT
a=
PHOTOCELL
P
T
VARIES
SEE
PLANS
PUSHBUTTON (EMERGENCY POWER OFF - EPO)
CODE SIZE JUNCTION BOX
-
NO TAG INDICATES SINGLE POLE TOGGLE SWITCH
VARIES
SEE
PLANS
SMALL CASE LETTER DENOTES SWITCHING
CONTROL
2=
DOUBLE POLE TOGGLE SWITCH
3=
THREE-WAY TOGGLE SWITCH
4=
FOUR-WAY TOGGLE SWITCH
P=
PILOT LIGHT TOGGLE SWITCH
M = MOMENTARY CONTACT SWITCH
K=
KEY OPERATED SWITCH
WP = WEATHERPROOF TOGGLE SWITCH
T=
MANUAL MOTOR STARTER SWITCH WITH
THERMAL OVERLOAD PROTECTION
D = DIMMER SWITCH
J
PC
GROUNDING CONDUCTOR
CABLE TRAY - POWER AND TELECOMMUNICATIONS
TELECOMMUNICATIONS RACEWAY
FLUSH MOUNTED PANELBOARD. DASHED LINES INDICATE CLEARANCES.
HORN NOTIFICATION
R
EXTERIOR
DB
H1A
F
DUCT DETECTOR
POTENTIAL TRANSFORMER.
SECTION/ELEVATION LETTER OR DETAIL
NUMBER
DRAWING NUMBER WHERE DETAILED
+18",
UON
SPECIAL PURPOSE RECEPTACLE. NEMA
CONFIGURATION AND AMPERAGE AS NOTED ON
PLANS
WALL MOUNTED CODE SIZE J-BOX
WALL
FIRE ALARM ANNUNCIATOR PANEL
PULL STATION
EMERGENCY BATTERY PACK LUMINAIRE
(BUG-EYE/FROG-EYE)
X
EQUIPMENT
MSB
DOUBLE FACE EXIT LUMINAIRE. SHADED SIDE
INDICATES FACE SIDE. PROVIDE DIRECTIONAL
ARROW(S) AS INDICATED ON PLANS
WALL
EMERGENCY DOUBLE DUPLEX (QUADPLEX)
RECEPTACLE
BUSWAY
SYMBOL
CEILING
WALL,
UON
FIRE ALARM TERMINAL CABINET (EQUIPMENT
NAMING CONVENTION PER PLANS)
EXIT LUMINAIRE. SHADED SIDE INDICATES
FACE SIDE. PROVIDE DIRECTIONAL ARROW(S)
AS INDICATED ON PLANS
X
J
CONDUIT STUBBED AND CAPPED
T
D
V/D
FA
WALL
DOUBLE HEAD, POLE MOUNTED LUMINAIRE
CONDUIT TURNS
B
G
SURFACE
EMERGENCY DUPLEX RECEPTACLE
COMBINATION POWER/COMMUNICATION POLE.
CONFIGURATION AS NOTED ON PLANS
EXPOSED RACEWAY BETWEEN DEVICES AND OR
EQUIPMENT ON WALLS OR CEILINGS
UP
WALL
STRIP LUMINAIRE
CEILING
DOUBLE DUPLEX (QUADPLEX) RECEPTACLE
CEILING
TRACK MOUNTED LUMINAIRES
SIMPLEX RECEPTACLE
FATC
F
LINEAR DIRECT/INDIRECT LUMINAIRE. CABLE
OR STEM MOUNTED
WALL MOUNTED LUMINAIRES
FLUSH
FIRE ALARM CONTROL PANEL
FAA
DOWN LIGHT LUMINAIRE; CEILING MOUNTED
CEILING
FACP
FIREMAN'S TELEPHONE OUTLET
VARIES
COMBINATION POWER/COMMUNICATION IN
CEILING OUTLET. CONFIGURATION AS
INDICATED ON PLANS
DUPLEX RECEPTACLE
VARIES
MOUNTING
LOC.
HT.
DESCRIPTION
RECESSED MOUNTED LUMINAIRE
SURFACE MOUNTED LUMINAIRE.
LUMINAIRE TYPE AS INDICATED ON PLANS
CEILING MOUNTED EMERGENCY DOUBLE
DUPLEX (QUADPLEX) RECEPTACLE
MULTI-OULET ASSEMBLY (SURFACE MOUNTED
RACEWAY)
UNDERGROUND RACEWAY BETWEEN DEVICES AND
OR EQUIPMENT
MEDICAL EQUIPMENT REFERENCE
0 10' 20'
X
CONCEALED RACEWAY BETWEEN DEVICES AND OR
EQUIPMENT IN WALLS OR IN CEILING SPACE
DOWN
CEILING MOUNTED EMERGENCY DUPLEX
RECEPTACLE
MOUNTING
LOC.
HT.
DESCRIPTION
HATCHING INDICATES EMERGENCY LIGHTING.
HATCH WILL BE MODIFIED FOR EACH
LUMINAIRE TYPE. EMERGENCY LUMINAIRE
DESIGNATED WITH "E" IN TYPE DESIGNATION.
FLOOR
SYMBOL
SINGLE HEAD, POLE MOUNTED LUMINAIRE
HOMERUN FROM EQUIPMENT LOCATION. THE CIRCUIT
NUMBER ADJACENT TO HOMERUN INDICATES PANEL
SOURCE AND INDIVIDUAL SINGLE POLE CIRCUIT BREAKER
(S). SYMBOL REPRESENTS A MULTI-BRANCH CIRCUIT.
NUMBER OF CONDUCTORS IN HOMERUN WILL INCLUDE A
SEPERATE NEUTRAL FOR EACH CIRCUIT PHASE
CONDUCTOR. MINIMUM #12 CONDUCTORS AND 3/4"
RACEWAY PATH WILL BE PROVIDED IN HOMERUN UON.
ALL HOMERUNS WILL INCLUDE GROUND CONDUCTOR.
LA-5,7,9
X
CEILING MOUNTED DOUBLE DUPLEX
(QUADPLEX) RECEPTACLE
X
HOMERUN FROM EQUIPMENT LOCATION. THE CIRCUIT
NUMBER ADJACENT TO HOMERUN INDICATES PANEL
SOURCE AND INDIVIDUAL SINGLE POLE CIRCUIT BREAKER
(S). CONDUCTOR IDENTIFICATION SYMBOL INDICATES
NUMBER OF CONDUCTORS IN HOMERUN. MINIMUM #12
CONDUCTORS AND 3/4" RACEWAY PATH WILL BE
PROVIDED IN HOMERUN UON. ALL HOMERUNS WILL
INCLUDE GROUND CONDUCTOR.
LA-1,3
CEILING MOUNTED DUPLEX RECEPTACLE
X
= SWITCH LEG
LA-1
X
X
CONDUCTOR IDENTIFICATION SYMBOLS. REFER TO
PLANS FOR COMBINATION USE. CONDUCTOR
IDENTIFICATION MOSTLY USED IN HOMERUN
LOCATION, BUT CAN ALSO BE USED IN BRANCH
CIRCUITING WHERE APPLIED. GROUND
CONDUCTORS WILL BE INSTALLED IN ALL RACEWAYS
WHETHER SHOWN OR NOT.
= HOT/PHASE
COMBINATION DUPLEX RECEPTACLE AND
COMMUNICATIONS FLOORBOX. DEVICE
CONFIGURATION AS INDICATED ON PLANS.
X
DESCRIPTION
= GROUND
X
X
BRANCH CIRCUITS FROM OVERCURRENT PROTECTION (20A) TO FURTHEST DEVICE
SHALL NOT EXCEED 75 FEET FOR #12AWG COPPER AND 150 FEET FOR #10AWG
COPPER; MEASURED ALONG CONDUCTORS ROUTING PATH. BRANCH CIRCUITS
EXCEEDING 150 FEET WILL BE SIZED SO THAT VOLTAGE DROP DOES NOT EXCEED 5%.
IN FLOOR DUPLEX RECEPTACLE.
CONFIGURATION AS INDICATED ON PLANS
IN FLOOR DOUBLE DUPLEX (QUADPLEX)
RECEPTACLE. CONFIGURATION AS INDICATED ON
PLANS
IN FLOOR EMERGENCY DUPLEX RECEPTACLE.
CONFIGURATION AS INDICATED ON PLANS
IN FLOOR EMERGENCY DOUBLE DUPLEX
(QUADPLEX) RECEPTACLE. CONFIGURATION AS
INDICATED ON PLANS
X
SYMBOL
MOUNTING
LOC.
HT.
DESCRIPTION
X
MECHANICAL EQUIPMENT REFERENCE
+44"
A
BLANK FOR NORMAL POWER
G
= GFCI RATED
IG
= ISOLATED GROUND
T
= TAMPERPROOF
WG
= WEATHERPROOF AND GFCI
WP
= WEATHERPROOF (IN-USE COVER)
CL
= CLOCK
TV
= TELEVISION
A, B, C, = SEQUENCE OF PANELS OF THIS TYPE
DEFINITION
KEYED NOTE REFERENCE
DEVICE INDICATOR LETTER. "X" EQUALS DESIGNATION BELOW
(TYPICAL FOR MOST RECEPTACLE TYPES):
200 LONGHORN STREET
VEGA, TEXAS 79092
A
AC
A/C
ADA
AFF
AFG
AIC
AL
ANSI
ATSC
ATS
A/V
AWG
C
CB
CCTV
CKT
CL
CLF
CO
CU
D
DC
DL
DIA
E
EC
EG
EL
EQ
EX
FUT
FA
FAA
FACP
FATC
FDR
FMS
GEN
GFI
G OR GFCI
GFEP
GFP
GND
HOA
HP
IEEE
FIRE ALARM
BAND HALL RENOVATION
D
DEFINITION
LIGHTING
REFER TO LUMINAIRE SCHEDULE FOR ALL LUMINAIRE TYPES WHETHER WALL MOUNTED
OR CEILING MOUNTED.
REFER TO LIGHTING SCHEDULE
ABBREV.
DEVICES
EQUIPMENT NAMING CONVENTION
ABBREVIATIONS
7/29/2016
DATE
PROJECT NO.
14-0424.002
DRAWING NAME
ELECTRICAL
LEGEND
GENERATOR
VFD
5
UPS
VFD CONNECTION
SHEET NO.
E-001
OF
1
2
3
4
5
1
2
3
4
5
GENERAL NOTES
A. BEFORE COMMENCEMENT OF ANY WORK, COORDINATE AND
LOCATE ALL UTILITIES, OVERHEAD AND UNDERGROUND.
REFER TO SHEET SERIES "A", "C", "L", "M", AND "P" UTILITY
PLANS. WHERE OTHER UTILITIES MAYBE SHOWN ON THIS
PLAN THEY ARE FOR REFERENCE ONLY. COORDINATE
ACTUAL UTILITY LOCATIONS PRIOR TO COMMENCEMENT OF
ANY WORK.
B. CONTRACTOR WILL REFER TO ARCHITECT PLANS AND
SPECIFICATIONS FOR CONSTRUCTION SEQUENCE OF THIS
PHASE OF THE PROJECT. ANY AND ALL MODIFICATIONS TO
ANY BUILDING OR UTILITY WILL BE COORDINATED PRIOR TO
COMMENCEMENT OF ANY WORK. BUILDINGS OR PORTIONS
THERE OF THAT WILL NEED TO STAY OPERATIONAL DURING
CONSTRUCTION WILL BE MODIFIED TO DO SO.
D
S01
W
M
4600 C Montgomery Blvd. NE
Albuquerque, NM 87109
505.883.4111 www.bpce.com
S07
ENGINEER
S09
SHEET KEYED NOTES
S08
S03
S01. FIRE ALARM CONTROL PANEL (FACP), INSTALLED IN
PHASE 1.
S05
PROJECT
S02. EXISTING 2000A (208V /120V) SWITCHBOARD; 11MDP.
REFER TO SHEET E-601 FOR ADDITIONAL INFORMATION.
S04
S03. DISTRIBUTION FROM FIRE ALARM CONTROL PANEL
INSTALLED IN PHASE 1 TO BAND HALL RENOVATION. REFER
TO FIRE ALARM DIAGRAM ON SHEET E-602 FOR ADDITIONAL
INFORMATION. ROUTE UNDERGROUND.
S02
S10
BAND HALL RENOVATION
S07
S07
Digitally signed by
William D. Herbst
Date: 2016.07.29
11:04:01-06'00'
S04. PROVIDE A CONDUIT FOR SECONDARY POWER FROM
EXISTING SWITCHBOARD TO BAND HALL RENOVATION.
REFER TO ONE-LINE DIAGRAM ON SHEET E-601 FOR
ADDITIONAL INFORMATION. ROUTE UNDERGROUND.
S09
S06
S05. PANEL LOCATION FOR BAND ROOM. REFER TO SHEET
EP-101 AND E-601 FOR ADDITIONAL INFORMATION.
S06. FIRE ALARM TERMINAL CABINET (FATCBR) IN BAND
ROOM. REFER TO SHEET ET-101 AND E-602 FOR
ADDITIONAL INFORMATION.
S11
S07. ROUTE CONDUIT FROM FACP OVERHEAD IN CEILING SPACE
AND OUT BUILDING AT POINT INDICATED.
S08. ROUTE CONDUIT SURFACE TO EXTERIOR WALL TO A POINT
WHERE CONDUIT WILL GO UNDERGROUND. SEE NOTE S03
AND S04. THIS IS FOR BOTH FIRE ALARM AND SECONDARY
POWER TO BAND HALL.
B
S09. IN DASH AREA CONTRACTOR WILL INFORM HIMSELF AND
COORDINATE WITH ALL OTHER UTILITIES BEING INSTALLED
IN OTHER PHASES OF CONSTRUCTION.
S10. REMOVE EXISTING PANEL AND FEEDER BACK TO
PANEL SERVICE IN MAINTENANCE SHOP. RACEWAY TO BE
REMOVED WHERE POSSIBLE. ABANDON IN PLACE WHERE
NECESSARY.
S11. CONNECTION TO EXISTING SERVER ROOM. ROUTE
(1)4" CONDUIT FROM NEW CABINET IN BAND ROOM
UNDERGROUND TO EXISTING MAIN BUILDING. TRANSITION
CONDUIT UP THE SIDE OF EXISTING BUILDING TO POINT
ABOVE DROP CEILING IN EXISTING BUILDING. HORIZONTALLY
PENETRATE WALL WITH CONDUIT AND CONTINUE 4"
CONDUIT TO EXISTING SERVER ROOM IN EAST WING.
PROVIDE 4" 3-CELL MAXCELL INNERDUCT TO SPAN BOTH
ENDS.
200 LONGHORN STREET
VEGA, TEXAS 79092
C
100 % CONSTRUCTION
DOCUMENTS
REVISIONS
DRAWN BY
BEL
REVIEWED BY
JMM
7/29/2016
DATE
PROJECT NO.
14-0424.002
DRAWING NAME
A
ELECTRICAL
SITE PLAN
A2
ELECTRICAL SITE PLAN
0
1" = 20'-0"
2'
4'
8'
NORTH
SHEET NO.
ES101
OF
1
2
3
4
5
1
2
3
4
5
GENERAL NOTES
A.
REFER TO ARCHITECTURAL DEMOLITION SHEETS "AD" SERIES
AND SPECIFICATIONS FOR ADDITIONAL DEMOLITION
REQUIREMENTS.
D02
D
D02
D02
D01
11S
D02
4600 C Montgomery Blvd. NE
Albuquerque, NM 87109
505.883.4111 www.bpce.com
D02
ENGINEER
C
SHEET KEYED NOTES
D02
PROJECT
D02
BAND HALL RENOVATION
D02. REMOVE ALL ELECTRICAL POWER CONNECTION,
ELECTRICAL EQUIPMENT FOR MECHANICAL EQUIPMENT,
LIGHTING AND LIGHTING CONTROL AND ALL GENERAL
POWER DEVICES. PLUS ASSOCIATED RACEWAY AND
CONDUCTORS BACK TO PANEL SOURCE (11S).
D02
B
B2
BAND HALL - DEMOLITION FLOOR PLAN
0
1/4" = 1'-0"
2'
4'
8'
NORTH
200 LONGHORN STREET
VEGA, TEXAS 79092
D01. REMOVE EXISTING PANEL AND FEEDER BACK TO PANEL
SERVICE IN MAINTENANCE SHOP. RACEWAY TO BE
REMOVED WHERE POSSIBLE. ABANDON IN PLACE WHERE
NECESSARY.
Digitally signed by
William D. Herbst
Date: 2016.07.29
11:04:12-06'00'
100 % CONSTRUCTION
DOCUMENTS
REVISIONS
DRAWN BY
BEL
REVIEWED BY
JMM
7/29/2016
DATE
PROJECT NO.
14-0424.002
DRAWING NAME
A
BAND HALL DEMOLITION
FLOOR PLAN
SHEET NO.
ED101
OF
1
2
3
4
5
1
2
3
4
5
GENERAL NOTES
L09
A.
ALL EXIT SIGNS WILL BE CONNECTED TO CIRCUIT SERVING
THE ROOM THEY ARE LOCATED IN AND FROM NO OTHER
CIRCUIT.
B.
REFER TO SHEET E-701 FOR ELECTRICAL LUMINAIRE
SCHEDULE.
FL
11S-1
3b
3a
E
PANEL 11S
L01
D
ARaD
C. REFER TO SHEET EP101 FOR ELECTRICAL EQUIPMENT
LAYOUT.
L01
a,b
ARaDE
ARaD
a,b
ARaD
a,b
ARaD
a,b
ARaD
a,b
ARaD
b
a
a,b
ARaDE
ENSEMBLE
201
D.
REFER TO DETAIL B1 ON THIS SHEET FOR LUMINAIRE
MOUNTING.
E.
REFER TO ARCHITECTURAL SHEETS FOR ADDITIONAL
CEILING GRID MOUNTING SUPPORT INFORMATION. ALL
LUMINAIRES WILL BE SECURELY SUPPORTED SEPARATELY
FROM LUMINAIRES TO CEILING STRUCTURE.
F.
ALL LUMINAIRES AND DEVICES IN THE DASHED AREA WILL BE
CONNECTED TO CIRCUIT INDICATED UNLESS OTHERWISE
NOTED.
ARaDE
L05
L05
A4
E-603
a,b
L05
L05
a,b
ARaD
ARaD
ELEMENTARY
MUSIC
208
a,b
ARaD
a,b
ARaDE
a,b
ARaD
a,b
ARaD
a,b
ARaD
11S-5
BAND HALL
200
11S-3
4600 C Montgomery Blvd. NE
Albuquerque, NM 87109
505.883.4111 www.bpce.com
L01
ARaDE
a b
a,b
ARaD
a,b
ARaDE
a,b
ARaD
ENGINEER
b
a
a,b
ARaD
L01
C
ARaDE
L05
GIRLS
207
C6LE
C6L
L05
L02
a,b
L05
L01. TWO SWITCHES, SWITCH TYPE AS INDICATED. ONE SWITCH
(A) WILL CONTROL INNER LAMP(S) AND ONE SWITCH WILL
CONTROL OTHER LAMPS OF LUMINAIRE IN ROOM.
C6L
K
E
L05
11S-7
L08
BVb
a,b
ARaDE
C6L
BVbE
L01
BVb
a,b
ARaD
L01
a,b
ARaD
L05
BOYS
206
K
C6LE
L02
C6L
a,b
ARaD
L02
L05
C6LE
E
a,b
ARaD
OFFICE
205
MUSIC
STOR.
204
a,b
ARaDE
UNIFORM
STOR.
203
L03
ARb
ARb
11S-5
PROJECT
L03. WALL-MOUNTED OCCUPANCY SENSOR, WATT STOPPER
PW-100 OR APPROVED EQUAL. LOCATE PER
MANUFACTURER'S RECOMMENDATIONS. SHOWN HERE FOR
BID PURPOSES. SWITCH ASSOCIATED WILL PROVIDE
ON/OFF CONTROL.
PERCUSSION
202
L03
Digitally signed by
William D. Herbst
Date: 2016.07.29
11:04:21-06'00'
L02. REUSE OUTLET REPLACE DEVICE. ONE SWITCH, SWITCH
TYPE AS INDICATED, WILL CONTROL THE LUMINAIRES IN
ROOM.
a,b
ARaD
b a
C6L
C6L
L08
a,b
ARaD
3b 3a
11S-3
BVbE
C6L
SHEET KEYED NOTES
L05. CEILING-MOUNTED OCCUPANCY SENSOR, WATT STOPPER
DT-355 OR APPROVED EQUAL. LOCATE PER
MANUFACTURER'S RECOMMENDATIONS. SHOWN HERE FOR
BID PURPOSES.
L08. REFER TO DETAIL B1 ON SHEET A-501 FOR MOUNTING
DETAIL FOR THESE LUMINAIRES.
a,b
ARaD
L09. REMOVE EXISTING LUMINAIRE AND REPLACE WITH NEW
LUMINAIRE.
B
B2
BAND HALL - LIGHTING FLOOR PLAN
0
1/4" = 1'-0"
2'
4'
8'
NORTH
100 % CONSTRUCTION
DOCUMENTS
REVISIONS
NO. 12 GAUGE WIRE HANGER TO
BUILDING FRAMING OR STRUCTURAL
MEMBERS. SUSPEND FROM ALL FOUR
CORNERS OF THE LUMINAIRE
CEILING SYSTEM
HANGER WIRES
(TYP.)
200 LONGHORN STREET
VEGA, TEXAS 79092
ARaD
a,b
ARaD
a,b
ARaD
BAND HALL RENOVATION
ARaD
DRAWN BY
CEILING SYSTEM
HANGER WIRES
(TYP.)
BEL
REVIEWED BY
JMM
7/29/2016
DATE
PROJECT NO.
14-0424.002
DRAWING NAME
A
LAY-IN LUMINAIRE
A1
SEISMIC FIXTURE CLAMPS:
REQUIRED AT ALL (4) LUMINAIRE
CORNERS WITH 2#10
SELF-TAPPING SCREWS. AGI
SEISMIC PRODUCTS OR EQUAL. AC
184 COMPLIANT.
BAND HALL LIGHTING
FLOOR PLAN
LUMINAIRE SUPPORT DETAIL
SHEET NO.
NO SCALE
EL101
OF
1
2
3
4
5
1
2
3
4
5
GENERAL NOTES
P03
F01
A.
GFCI RECEPTACLES WILL BE INSTALLED AT ALL LOCATIONS
AS REQUIRED BY THE LATEST VERSION OF NEC, STATE AND
LOCAL CODES WHETHER INDICATED ON PLANS OR NOT.
SOME LOCATIONS WILL BE WITHIN 6'-0" OF SINKS, EXTERIOR
DOORS AND WET LOCATIONS. ALL EXTERIOR RECEPTACLE
LOCATIONS WILL BE GFCI RATED AND WEATHERPROOF.
B.
ALL DEVICES IN THE DASHED AREA WILL BE CONNECTED TO
THE PANEL INDICATED UNLESS OTHERWISE NOTED.
11S-15,17,19
8
11S
10
F02
18
P06
3,6
D
WG
11S-24
8
P05
4
AC-03
G
10
ENSEMBLE
201
P02
32
ELEMENTARY
MUSIC
208
P05
10
AC-02
P06
8
WG
11S-24
BAND HALL
200
4600 C Montgomery Blvd. NE
Albuquerque, NM 87109
505.883.4111 www.bpce.com
4
P05
AC-01
ENGINEER
8
F04
2
P06
20
F04
11S-21,23,25
WG
11S-24
8
P04
10
C
SHEET KEYED NOTES
Digitally signed by
William D. Herbst
Date: 2016.07.29
11:04:32-06'00'
11S-9,11,13
P01
PERCUSSION
202
11S-29,31
G
12
P07
G
30
2,4
6
P04. ROUTE CONDUIT UNDERGROUND TO EXTERIOR WALL
THEN UP WALL TO LEVEL IN CEILING SPACE IN BUILDING,
THEN OVER TO PANEL
11S-27
F
P01
6
EF-1
18
T
16
P05. REFER TO SHEET E-702 FOR ELECTRICAL CONNECTION
SCHEDULE FOR MECHANICAL EQUIPMENT. REFER TO SHEET
M-701 FOR MECHANICAL / ELECTRICAL INFORMATION.
18
11S-22
16,18
FATCBR
OFFICE
205
16,20
F03
MUSIC
STOR.
204
P06. UNIT MOUNTED GFCI WEATHERPROOF RECEPTACLE.
CONTRACTOR WILL PROVIDE CIRCUIT INDICATED TO THIS
DEVICE.
UNIFORM
STOR.
203
P07. MOUNT DEVICE IN CONJUNCTION WITH EQUIPMENT.
COORDINATE FINAL LOCATION PRIOR TO COMMENCEMENT
OF ANY WORK.
26,28
20
P02. DEVICE IS FOR SHORT THROW PROJECTOR SCREEN.
REFER TO SHEET SERIES “T” FOR SWITCH LOCATION AND
ADDITIONAL INSTALLATION INFORMATION.
P03. REFER TO SHEET ES101 AND E-601 FOR ADDITIONAL
INFORMATION.
P02
11S-14
12
G
PROJECT
P07
F01. REFER TO SHEET ES101 AND E-602 FOR ADDITIONAL
INFORMATION.
B
CIRCUITS FOR GENERAL POWER WITHIN
DASHED AREA ARE FED FROM PANEL 11S.
F02. TO FIRE ALARM TERMINAL CABINET (FATCBR); OVERHEAD
DISTRIBUTION.
B2
F03. REFER TO FIRE ALARM RISER DIAGRAM ON SHEET E-602 FOR
ADDITIONAL INFORMATION.
BAND HALL - POWER FLOOR PLAN
0
1/4" = 1'-0"
2'
4'
8'
200 LONGHORN STREET
VEGA, TEXAS 79092
P05 EWH-1
GIRLS
207
BOYS
206
6
BAND HALL RENOVATION
P04
P01. MOUNT DEVICE 6" ABOVE COUNTER TOP BACK SPLASH,
TABLE TOP OR SINK. RECEPTACLE WILL BE GFCI RATED.
F04. PROVIDE DUCT DETECTOR FOR UNITS 2000 CFM OR
GREATER FOR INSTALLATION BY MECHANICAL INSTALLER.
NORTH
100 % CONSTRUCTION
DOCUMENTS
REVISIONS
DRAWN BY
BEL
REVIEWED BY
JMM
7/29/2016
DATE
PROJECT NO.
14-0424.002
DRAWING NAME
A
BAND HALL POWER FLOOR
PLAN
SHEET NO.
EP101
OF
1
2
3
4
5
1
2
3
4
5
GENERAL NOTES
PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS
THROUGH WALLS, FLOORS, CEILINGS, AND ROOF AS PER
OWNER, CODE, AND AHJ.
B.
CONTRACTOR TO VERIFY ALL CABLE COUNTS AND NUMBER
OF PATCH PANELS REQUIRED.
C.
ALL CABLING TO BE PLENUM RATED THROUGHOUT
BUILDING.
D.
ALL COMMUNICATIONS CABLING TO MEET OR EXCEED CAT6
STANDARDS.
E.
TELECOMMUNICATIONS OUTLETS TO BE MOUNTED AT +18"
A.F.F. (BOTTOM OF BOX) UNLESS OTHERWISE NOTED. FOR
EXAMPLE, DEVICES SPECIFIED AT +18" A.F.F. SHALL MATCH
THE STANDARD MOUNTING HEIGHT FOR POWER
RECEPTACLES AND TELECOMMUNICATIONS OUTLETS.
DEVICES SPECIFIED AT +48" A.F.F. SHALL MATCH THE
STANDARD MOUNTING HEIGHT FOR LIGHT SWITCHES ETC.
F.
ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS
SHALL BE STEEL, THIN-WALL ELECTRICAL METALLIC TUBING
(TYPE EMT) UNLESS OTHERWISE NOTED. UNDER NO
CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR
PATHWAYS INDICATED. ALL CONDUITS ARE TO BE, AT A
MINIMUM 1" TRADE SIZE, UNLESS OTHERWISE NOTED.
CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS
40% FILL.
T09
T05
T09
A.
T10
D
ENSEMBLE
201
T09
T14
T07
ELEMENTARY
MUSIC
208
T09
T13
4600 C Montgomery Blvd. NE
Albuquerque, NM 87109
505.883.4111 www.bpce.com
BAND HALL
200
ENGINEER
T09
C
SHEET KEYED NOTES
T06
F03. REFER TO FIRE ALARM RISER DIAGRAM ON SHEET E-602
FOR ADDITIONAL INFORMATION.
T13
Digitally signed by
William D. Herbst
Date: 2016.07.29
11:04:43-06'00'
PROJECT
PERCUSSION
202
T04
T08
T14
T02. WALL MOUNTED COMBINATION CLOCK/SPEAKER FOR
DISTRIBUTED INTERCOM/PAGING AND CLOCK SYSTEM.
COORDINATE SIGNAL PULL BOX TYPE AND ROUGH-IN
LOCATION WITH EQUIPMENT INSTALLER PRIOR TO
COMMENCING ANY WORK. REFER TO SPECIFICATIONS
SECTION 27 5123 FOR ADDITIONAL REQUIREMENTS.
TYP
T03. INTERCOM CALL SWITCH WIRED TO CLOCK/SPEAKER
COMPLETE FOR OPERATION.
T02
BOYS
206
T03
TYP
F03
T05
FATCBR
BAND HALL RENOVATION
T10
OFFICE
205
TYP
MUSIC
STOR.
204
T04. WALL MOUNTED CLOCK. REFER TO SPECIFICATIONS
SECTION 27 5313 FOR ADDITIONAL REQUIREMENTS.
UNIFORM
STOR.
203
T05. QUANTITY (2) PORT VOICE/DATA OUTLET U.N.O.
T06. PAGING LOUDSPEAKER FOR DISTRIBUTED
INTERCOM/PAGING SYSTEM. COORDINATE SIGNAL PULL
BOX TYPE AND ROUGH-IN LOCATION WITH EQUIPMENT
INSTALLER PRIOR TO COMMENCING ANY WORK.
T01
T07. INTERIOR CAMERA LOCATION. PROVIDE DATA OUTLET AT
HEIGHT INDICATED.
B
T08. BACK BOX FOR WALL MOUNTED VOLUME CONTROL SWITCH
FOR PAGING LOUDSPEAKER. PROVIDE SINGLE-GANG BOX
2-1/2"D BOX WITH 1/2" SIDE KNOCKOUTS. RAISED AS
NEEDED FOR FINISHED WALLBOARD THICKNESS.
200 LONGHORN STREET
VEGA, TEXAS 79092
T01. NEW IT/AV CABINET, CPI MODEL - E SERIES ISP
CO-LOCATION CABINET E1051742 WITH REAR FAN KIT.
GIRLS
207
T09. ROUGH-IN ONLY, PROVIDE BOX, CONDUIT, AND A
STAINLESS STEEL BLANK FACEPLATE.
T10. BACK BOX FOR A/V PLUG-IN CONNECTION PANEL. PROVIDE
A 3-GANG 2-1/2"D BOX WITH 1" SIDE KNOCKOUTS, CATALOG
#942 AS MFD BY RACO. PROVIDE A 3-GANG COVER, RAISED
AS NEEDED FOR FINISHED WALLBOARD THICKNESS.
INSTALL AT 18" AFF. PROVIDE WITH (1) 1" CONDUIT TO A/V
CONTROL PANEL BACK BOX ON WALL DIRECTLY ABOVE
THIS BOX.
(1) 4" CONDUIT TO EXISTING SERVER ROOM
IN EXISTING MAIN BUILDING. SEE SITE PLAN
ES101.
CONNECTION TO EXISTING SERVER ROOM. ROUTE (1)4" CONDUIT FROM
NEW CABINET IN BAND ROOM UNDERGROUND TO EXISTING MAIN
BUILDING. TRANSITION CONDUIT UP THE SIDE OF EXISTING BUILDING TO
POINT ABOVE DROP CEILING IN EXISTING BUILDING. HORIZONTALLY
PENETRATE WALL WITH CONDUIT AND CONTINUE 4" CONDUIT TO
EXISTING SERVER ROOM IN EAST WING. PROVIDE 4" 3-CELL MAXCELL
INNERDUCT TO SPAN BOTH ENDS.
B2
A
6 PAIR MM OSP FIBER
CABINET IN
BAND #205
ONE LINE DIAGRAM
A1
0
1/4" = 1'-0"
2'
4'
8'
NORTH
IT IS THE INTENT OF THESE DOCUMENTS TO SHOW A BASIC
REPRESENTATION OF THE FIRE ALARM SYSTEM. DEVICES INDICATED ON
THESE DOCUMENTS ARE IN NO WAY IMPLIED TO BE COMPREHENSIVE OF
THE FINAL DESIGN. IT IS THE RESPONSIBILITY OF THE FIRE ALARM
CONTRACTOR TO PROVIDE A DESIGN/BUILD FIRE ALARM SYSTEM BASED
UPON A THOROUGH REVIEW OF ALL CONTRACT DOCUMENTS. IT IS THE
RESPONSIBILITY OF THE FIRE ALARM CONTRACTOR TO ENSURE THAT THE
FIRE ALARM SYSTEM IS CODE COMPLIANT, MEETS THE REQUIREMENTS OF
THE AHJ AND COMPREHENSIVELY COVERS AND INCLUDES ALL NECESSARY
PARTS AND LABOR ASSOCIATED WITH OTHER TRADES AND SYSTEMS
IMPACTING THE FIRE ALARM SYSTEM. NO CHANGE ORDERS SHALL BE
APPROVED FOR THE BASE SCOPE OF WORK.
25 PAIR OSP COPPER
EXISTING
SERVER ROOM
BAND HALL - SPECIAL SYSTEMS FLOOR PLAN
T11. BACK BOX FOR BASIC A/V CONTROL PANEL. PROVIDE
4-11/16" SQUARE AND 2-1/8"D BOX WITH 3/4" AND 1" SIDE
KNOCKOUTS, CATALOG #265 AS MFD. BY RACO. PROVIDE A
1-GANG COVER, RAISED AS NEEDED FOR FINISHED
WALLBOARD THICKNESS. INSTALL AT LIGHT SWITCH
HEIGHT. PROVIDE WITH (2) 1" EMT CONDUITS TO A/V
JUNCTION BOX AT SMARTBOARD LOCATION.
N.T.S.
T12. WALL MOUNTED SMART BOARD WITH SHORT THROW VIDEO
PROJECTOR LOCATION. PROVIDE STRUCTURAL BACKING
AND MULTI-SERVICE JUNCTION BOX FOR POWER OUTLET,
VOICE/DATA OUTLET, AND FUTURE AUDIO-VISUAL
CONNECTIONS. SMART BOARD AND VIDEO PROJECTOR TO
BE OWNER PROVIDED. REFER TO DETAIL B1 ON SHEET
ET-501 FOR BOX AND ROUGH-IN REQUIREMENTS.
T13. FUTURE OWNER PROVIDED SMART BOARD WITH WALL
MOUNTED SHORT-THROW PROJECTOR.
T14. ROUGH-IN AND STRUCTURAL BACKING FOR OWNER
PROVIDED SMART BOARD WITH WALL MOUNTED
SHORT-THROW PROJECTOR.
100 % CONSTRUCTION
DOCUMENTS
REVISIONS
DRAWN BY
SDR / BEL
REVIEWED BY
GR
7/29/2016
DATE
PROJECT NO.
14-0424.002
DRAWING NAME
BAND HALL SPECIAL
SYSTEMS
FLOOR PLAN
SHEET NO.
ET101
OF
1
2
3
4
5
1
2
3
4
5
96"
POWER DUPLEX
A/V COMPONENT
D
24"
1
J
8"
DATA PORT
VOLTAGE BARRIER
24"
18"
NOTE: POWER
OUTLET MUST BE
DECORA STYLE
NOT, NEMA 106
STYLE IN ORDER
TO INTEGRATE
WITH THE OTHER
DEVICES IN THE
BOX.
12"
PROVIDE BACKING MATERIAL.
(SHEET METAL OR 3/4" PLYWOOD)
68"
4600 C Montgomery Blvd. NE
Albuquerque, NM 87109
505.883.4111 www.bpce.com
CABLE TYPE:
C = COPPER
F = FIBER
CX = COAX CABLE
U = UTP
SMARTBOARD /
ELECTRONIC
WHITEBOARD
(O.F.O.I.)
B1
J-BOX #7
TEL CONDUIT #1 TR1-ER
TEL CONDUIT #2 TR1-ER
TEL CONDUIT #2 TR1-ER
TEL CONDUIT #3 TR1-TR2
TEL CONDUIT #3 TR1-TR2
Digitally signed by
William D. Herbst
Date: 2016.07.29
11:04:55-06'00'
U-089-1-202A
LABEL WITHIN 6"
OF CABLE BREAKOUT
FINISHED FLOOR
ROUGH-IN AND STRUCTURAL BACK FOR WALL MOUNTED
SMARTBOARD
B3
NO SCALE
TELECOMMUNICATIONS CONDUIT
IDENTIFICATION SCHEME
B5
NO SCALE
A/V USER CONTROLS
TELECOM ROOM #
TELECOM ROOM ID#
B
PATCH PANEL PORT
PATCH PANEL #
EQPT. RACK ID
TELECOM ROOM ID#
221-TR1
1.3.B.28
PROJECT
TYPICAL CABLE
IDENTIFICATION SCHEME
NO SCALE
1" CONDUIT & CONNECTOR.
4-11/16" SQUARE, 2-1/8" DEEP
JUNCTION BOX WITH KNOCKOUTS.
SERVICING CLOSET
4-11/16" SQUARE
1-DEVICE RAISED
MUD RING.
PORT LABEL
A/V COMPONENTS
200 LONGHORN STREET
VEGA, TEXAS 79092
TEL CONDUIT #1 TR1-ER
CABLE #
ORIGIN (TR NAME)
DESTINATION (OUTLET NAME)
BAND HALL RENOVATION
C
ENGINEER
100 % CONSTRUCTION
DOCUMENTS
REVISIONS
IT CABINET
1.3.B.29
113-B
CABLE LENGTH 12"
COIL IN BACK BOX
OUTLET ID
OUTLET ID
OUTLET ROOM #
CATEGORY CABLES
(QTY AS INDICATED
ON PLANS)
DRAWN BY
SDR
REVIEWED BY
MODULAR JACK OR
BLANK AS NEEDED
7/29/2016
DATE
FACEPLATE
GR
PROJECT NO.
14-0424.002
DRAWING NAME
A
TECHNOLOGY
DETAILS
A2
RACK ELEVATION - CPI E SERIES
E1051-742
A3
NO SCALE
CEILING TELECOM OUTLET
IDENTIFICATION SCHEME (TYPICAL)
NO SCALE
A4
TELECOMMUNICATIONS
OUTLET BOX DETAILS (TYPICAL)
NO SCALE
SHEET NO.
ET-501
OF
1
2
3
4
5
1
2
3
4
5
GENERAL SHEET NOTES
FEEDER SCHEDULE
ALL CONDUCTORS ARE COPPER, TYPE THWN/THHN UNLESS OTHERWISE NOTED.
CONDUCTORS
GROUND
CONDUIT
PANELBOARD AIC RATINGS ARE INDICATED ON THE NEW
PANEL SCHEDULE.
B.
INFORMATION SHOWN IS DIAGRAMMATIC AND IS NOT
INTENDED TO REPRESENT PHYSICAL ARRANGEMENTS,
LOCATIONS, ROUTING OR CONNECTIONS. PHYSICAL
LAYOUTS ARE TO BE PER FIELD CONDITIONS AND AS
INDICATED ELSEWHERE IN THE ELECTRICAL PLANS.
C.
REFERENCE THE SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS REGARDING EQUIPMENT AND INSTALLATION.
NOT ALL INFORMATION SHOWN ON THIS DIAGRAM.
D.
ALL PANELS WILL HAVE DOOR-IN-DOOR ACCESSIBILITY FOR
EACH PANEL.
E.
CONTRACTOR WILL MEASURE AND TORQUE ALL PANEL
FEEDERS, MEASURE RESISTANCE TO GROUND AT SERVICE
GROUND AND PROVIDE WRITTEN DOCUMENTATION OF TEST
RESULTS. CONTRACTOR WILL COORDINATE TIME SO THAT
SFPS REPRESENTATIVE IS PRESENT DURING TEST.
F.
CONTRACTOR WILL LABEL ALL DISTRIBUTION EQUIPMENT
PRIOR TO FINAL OBSERVATION WALK THROUGH.
G.
WHEN ALL EQUIPMENT IS INSTALLED REQUIRING
PROGRAMMING AND TRAINING HAS BEEN COMPLETED, THE
SCHOOL'S IP ADDRESS WILL NEED TO BE GIVEN TO OWNER'S
REPRESENTATIVE FOR ELECTRICAL M&O USE.
H.
REFER TO GROUNDING DIAGRAM ON SHEET E-602.
NOTES
THREE PHASE THREE WIRE & GROUND FEEDER
D
C
20
3#12
12
3/4"
25
3#10
10
3/4"
30
3#10
10
3/4"
35
3#8
10
3/4"
40
3#8
10
3/4"
45
3#8
10
3/4"
50
3#8
10
3/4"
60
3#6
10
1"
70
3#4
8
1 1/4"
80
3#4
8
1 1/4"
90
3#2
8
1 1/4"
100
3#2
8
1 1/4"
125
3#1
6
1 1/2"
150
3#1/0
6
1 1/2"
175
3#2/0
6
2"
200
3#3/0
6
2"
225
3#4/0
4
2 1/2"
250
3-250 KCMIL
4
3"
300
3-350 KCMIL
4
3"
350
3-500 KCMIL
2
4"
400
2
450
3-600 KCMIL
(2) 3#4/0
(2) 2
4"
(2) 2 1/2"
500
(2) 3-250 KCMIL
(2) 2
(2) 3"
600
(2) 3-350 KCMIL
(2) 1
(2) 3"
700
(2) 3-500 KCMIL
(2) 1
(2) 4"
800
(2) 3-600 KCMIL
(2) 1/0
(2) 4"
1000
(3) 3-400 KCMIL
(3) 2/0
(3) 3"
1200
(3) 3-600 KCMIL
(3) 3/0
(3) 4"
1600
(4) 3-600 KCMIL
(4) 4/0
(4) 4"
2000
(5) 3-600 KCMIL
(5)250 KCMIL
2500
(6) 3-600 KCMIL
3000
4000
D2 FAULT CURRENT CALCULATION
NO SCALE
C2 VOLTAGE DROP CALCULATION
NO SCALE
4600 C Montgomery Blvd. NE
Albuquerque, NM 87109
505.883.4111 www.bpce.com
SHEET KEYED NOTES
1.
REFER TO SHEET E-602 FOR GROUNDING INFORMATION FOR
THIS EQUIPMENT.
2.
MOLDED CASE, THERMAL-MAGNETIC CIRCUIT BREAKERS, 100%
RATED AND LOCKABLE.
(5) 4"
3.
REFER TO ES-101 FOR ROUTING OF ALL RACEWAYS.
(6)350 KCMIL
(6) 4"
4.
TO EXISTING MSB VIA TRANSFORMER.
(8) 3-500 KCMIL
(8)400 KCMIL
(8) 4"
(10) 3-600 KCMIL
(10)500 KCMIL
(10) 4"
Digitally signed by
William D. Herbst
Date: 2016.07.29
11:05:06-06'00'
THREE PHASE FOUR WIRE & GROUND FEEDER
20Y
4#12
12
3/4"
25Y
4#10
10
3/4"
30Y
4#10
10
3/4"
35Y
4#8
10
3/4"
40Y
4#8
10
3/4"
45Y
4#8
10
3/4"
50Y
4#8
10
3/4"
60Y
4#6
10
1"
70Y
4#4
8
1 1/4"
80Y
4#4
8
1 1/4"
90Y
4#2
8
1 1/4"
100Y
4#2
8
1 1/4"
125Y
4#1
6
1 1/2"
150Y
4#1/0
6
2"
175Y
4#2/0
6
2"
200Y
4#3/0
6
2"
225Y
4#4/0
4
2 1/2"
250Y
4-250 KCMIL
4
3"
300Y
4-350 KCMIL
4
3"
350Y
4-500 KCMIL
2
4"
400Y
450Y
4-600 KCMIL
(2) 4#4/0
2
(2) 2
4"
(2) 2 1/2"
500Y
(2) 4-250 KCMIL
(2) 2
(2) 3"
600Y
(2) 4-350 KCMIL
(2) 1
(2) 3"
700Y
(2) 4-500 KCMIL
(2) 1
(2) 4"
800Y
(2) 4-600 KCMIL
(2) 1/0
(2) 4"
1000Y
(3) 4-400 KCMIL
(3) 2/0
(3) 3"
1200Y
(3) 4-600 KCMIL
(3) 3/0
(3) 4"
1600Y
(4) 4-600 KCMIL
(4) 4/0
(4) 4"
2000Y
(5) 4-600 KCMIL
(5) 250 KCMIL
(5) 4"
2500Y
(6) 4-600 KCMIL
(6) 350 KCMIL
(6) 4"
3000Y
(8) 4-500 KCMIL
(8) 400 KCMIL
(8) 4"
4000Y
(10) 4-600 KCMIL
(10) 500 KCMIL
(10) 4"
5000Y
(12) 4-600 KCMIL
(12) 700 KCMIL
(12) 4"
B2 ELECTRICAL SERVICE CALCULATION
NO SCALE
BAND HALL
BUILDING
6
175YS THRU 200YS
4
225YS THRU 300YS
2
350YS THRU 500YS
1/0
600YS THRU 700YS
2/0
800YS THRU 5000YS
3/0
REVISIONS
3
2
225A
3P
PANEL
"11S"
250Y
GROUND
8
125YS THRU 150YS
100 % CONSTRUCTION
DOCUMENTS
1
EQUIPMENT BONDING JUMPER FOR SEPARATELY DERIVED SYSTEMS PER
NEC 250.66 (PROVIDE CONDUCTOR GROUND BELOW INSTEAD OF FEEDER GROUND FOR
THREE PHASE, 4-WIRE SYSTEMS INDICATED ABOVE)
DESIGNATION
20YS THRU 100YS
BAND HALL RENOVATION
PROJECT
225A
B
ENGINEER
200 LONGHORN STREET
VEGA, TEXAS 79092
DESIGNATION
A.
EXISTING "11MDP"
DRAWN BY
2000 AMPERE, NEMA 3R, 208Y/120V BUS
GRADE
EXISTING BAND
HALL BUILDING
4
A
3#2, 1#4/0 NEUTRAL
8
2"
150Y-E
3#2/0, 2#2/0 NEUT.
6
2"
4
2 1/2"
225Y-E
3-250 KCMIL,
2-250 KCMIL NEUT.
350Y-E
(2) 3#3/0,
(2) 2#3/0 NEUT.
(2) 2
(2) 2 1/2"
400Y-E
(2) 3#4/0,
(2) 2#4/0 NEUT.
(2) 2
(2) 2 1/2"
500Y-E
(2) 3-350 KCMIL,
(2) 2-350KCMIL NEUT.
(2) 2
(2) 3"
UNDERGROUND
JMM
7/29/2016
DATE
PROJECT NO.
14-0424.002
ONE-LINE
DIAGRAM
3
A2
REVIEWED BY
DRAWING NAME
THREE PHASE FOUR WIRE 200% NEUTRAL & GROUND FEEDER
100Y-E
BEL
ELECTRICAL ONE-LINE DIAGRAM
NO SCALE
SHEET NO.
E-601
OF
1
2
3
4
5
1
2
3
4
5
GENERAL NOTES
FIRE ALARM DIAGRAM INDICATED GENERAL DIAGRAMMATIC
CONNECTIONS ONLY. ALL CONNECTIONS AND INSTALLATION
WILL BE PER FIRE ALARM SYSTEM MANUFACTURER'S SHOP
DRAWINGS.
B.
DEVICE QUANTITIES ARE NOT INDICATED ON THIS DRAWING.
REFER TO FLOOR PLANS FOR QUANTITIES AND LOCATIONS.
TYPICAL ALL LOCATIONS
ENTIRE FIRE ALARM SYSTEM WILL BE IN RACEWAYS; NO EXCEPTIONS
IT IS THE INTENT OF THESE DOCUMENTS TO SHOW A BASIC
REPRESENTATION OF THE FIRE ALARM SYSTEM. DEVICES INDICATED ON
THESE DOCUMENTS ARE IN NO WAY IMPLIED TO BE COMPREHENSIVE OF
THE FINAL DESIGN. IT IS THE RESPONSIBILITY OF THE FIRE ALARM
CONTRACTOR TO PROVIDE A DESIGN/BUILD FIRE ALARM SYSTEM BASED
UPON A THOROUGH REVIEW OF ALL CONTRACT DOCUMENTS. IT IS THE
RESPONSIBILITY OF THE FIRE ALARM CONTRACTOR TO ENSURE THAT THE
FIRE ALARM SYSTEM IS CODE COMPLIANT, MEETS THE REQUIREMENTS OF
THE AHJ AND COMPREHENSIVELY COVERS AND INCLUDES ALL NECESSARY
PARTS AND LABOR ASSOCIATED WITH OTHER TRADES AND SYSTEMS
IMPACTING THE FIRE ALARM SYSTEM. NO CHANGE ORDERS SHALL BE
APPROVED FOR THE BASE SCOPE OF WORK.
4
2"C
3
D
A.
C. REFER TO SPECIFICATION SECTION 283100 FOR FIRE ALARM
SYSTEM REQUIREMENTS.
(TYP)
RET.
7
120VAC
D.
FIRE ALARM WIRING AND CABLING SHALL BE IN
CONFORMANCE WITH NEC AND TYPE SHALL BE AS
RECOMMENDED BY FIRE ALARM SYSTEM MANUFACTURER.
E.
SEAL ALL PENETRATIONS THROUGH WALL, FLOOR, CEILING
AND ROOF PER ARCHITECTURAL SPECIFIED REQUIREMENTS.
SEAL WILL MATCH THE FIRE RATING OF EACH PENETRATION
LOCATION.
F.
INSTALL GROUNDING CONNECTIONS TO BUILDING
STRUCTURE AND WATER PIPES AT LOCATIONS THAT ARE
VISIBLE AND ACCESSIBLE FOR INSPECTION, MAINTENANCE,
AND TESTING.
G.
INSTALL AN INSULATED THROAT GROUNDING BUSHING ON
EACH METALLIC SERVICE ENTRANCE CONDUIT. BOND TO
SERVICE ENTRANCE EQUIPMENT GROUND BUS USING
GROUNDING ELECTRODE CONDUCTOR.
H.
INSTALL AN INSULATED THROAT GROUNDING BUSHING ON
EACH METALLIC FEEDER CONDUIT. BOND TO GROUND BUS
USING CONDUCTOR THAT IS SIZED EQUAL TO EQUIPMENT
GROUNDING CONDUCTOR.
SUP.
2
FATCBR
FACP
1
5
PANEL 11S
120VAC
C2
C
FIRE ALARM RISER DIAGRAM
I.
BOND ELECTRICAL EQUIPMENT ENCLOSURES TO GROUND
BAR USING SAME SIZE CONDUCTOR AS FEEDER EQUIPMENT
GROUND CONDUCTOR OR FACTORY PROVIDED GREEN
SCREW.
J.
CLEAN COATED RE-BAR PRIOR TO PERFORMING ELECTRICAL
CONNECTION.
4600 C Montgomery Blvd. NE
Albuquerque, NM 87109
505.883.4111 www.bpce.com
ENGINEER
NO SCALE
Digitally signed by William
D. Herbst
Date: 2016.07.29
11:05:17-06'00'
FIRE ALARM TERMINAL CABINET (FATC) WILL BE A FACTORY
MANUFACTURED, UL LABELED PANEL TO MATCH EXISTING
SYSTEM ON CAMPUS. THE FATC WILL ENCLOSE ALL
TERMINATIONS FOR DEVICES ON THE FLOOR IT SERVES,
INTELLIGENT CARDS AS REQUIRED FOR INDEPENDENT
OPERATION, AND POWER SUPPLIES.
2.
WIRING AND CONDUCTORS AS REQUIRED BY THE FIRE
ALARM MANUFACTURER AND INSTALLER.
3.
FIRE/SMOKE DAMPER, ROUTE 120VAC VIA FIRE ALARM
ADDRESSABLE RELAY. DUCT DETECTOR FOR FIRE/SMOKE
DAMPERS WILL BE INSTALLED WITHIN 5'-0" OF EACH
FIRE/SMOKE DAMPER. DETECTOR SUPPLIED BY DIVISION 26
AND INSTALLED BY DIVISION 23.
4.
DUCT SMOKE DETECTOR, FURNISHED BY DIVISION 26,
INSTALLED IN DUCT BY DIVISION 23, CONNECTED, WIRED,
TESTED BY DIVISION 16. REFERENCE MECHANICAL CONTROL
DIAGRAMS FOR MECHANICAL INTERCONNECTIONS. DUCT
DETECTOR FOR UNITS OVER 2000 C.F.M. WILL BE INSTALLED
ON SUPPLY SIDE OF UNIT. DUCT DETECTORS FOR UNITS
OVER 15,000 C.F.M. WILL BE INSTALLED ON SUPPLY RETURN
SIDE OF UNIT. DO NOT INSTALL DUCT DETECTOR ON
EXHAUST FANS.
5.
MAIN FIRE ALARM CONTROL PANEL REFER TO ES-101 FOR
APPROXIMATE LOCATION. EXTEND RACEWAY AND
CONDUCTORS BETWEEN FACP AND FATCBR AS NECESSARY.
ROUTE RACEWAY AND CONDUCTORS AS INDICATED ON
ES-101.
6.
REFER TO ONE-LINE DIAGRAM AND FEEDER SCHEDULE FOR
GROUNDED CONDUCTOR SIZE.
7.
BONDING JUMPER SIZED PER GROUNDING ELECTRODE
CONDUCTOR SCHEDULE THIS SHEET.
EXISTING 11MDP
NEUTRAL
GROUNDING ELECTRODE
CONDUCTOR SCHEDULE
NOTE: ALL CONDUCTORS ARE COPPER.
SERVICE
CONDUCTOR
SIZE
(AWG OR kCMIL)
GROUNDING ELECTRODE
CONDUCTOR (AWG)
<= #2
8
NON K-RATED
TRANSFORMER
1/0 OR 1/0
6
2/0 OR 3/0
4
OVER 3/0
THROUGH 350
2
OVER 350
THROUGH 600
1/0
8
B
6
2/0
OVER 600
THROUGH 1100
OVER 1100
3/0
8.
FOR EQUIPMENT GROUNDING CONDUCTOR SIZE REFER TO
ONE-LINE DIAGRAM AND FEEDER SCHEDULE.
9.
PROVIDE GROUNDING ELECTRODE CONDUCTOR SIZE BASED
ON THE CONDUCTOR SIZE OF THE SECONDARY OF THE
TRANSFORMER. SIZE PER NEC 250.66 AND PER SCHEDULE
ON THIS SHEET.
COLD WATER
PIPE
7
10
9
GROUND
NEUTRAL
PANEL 11S
10. USE THE "MAIN GROUNDING ELECTRODE GROUND BAR"
INSTEAD OF BUILDING STRUCTURAL STEEL IF THE FIRST
OVER CURRENT DEVICE FOR THE SEPARATELY DERIVED
SYSTEM IS WITHIN SAME ROOM OF THE "MAIN GROUNDING
ELECTRODE GROUND BAR".
100 % CONSTRUCTION
DOCUMENTS
REVISIONS
DRAWN BY
JMM
7/29/2016
DATE
14-0424.002
DRAWING NAME
A
GROUNDING &
FIRE RISER
DIAGRAMS
10
A3
BEL
REVIEWED BY
PROJECT NO.
BUILDING STRUCTURAL STEEL
200 LONGHORN STREET
VEGA, TEXAS 79092
GROUND
1.
PROJECT
BAND HALL RENOVATION
SHEET KEYED NOTES
GROUNDING DIAGRAM
SHEET NO.
NO SCALE
E-602
OF
1
2
3
4
5
1
2
3
4
5
LIGHTING SEQUENCE OF OPERATION
NEUTRAL
A. DIAGRAMS ARE SHOWN FOR BIDDING PURPOSES. CONTRACTOR WILL PROVIDE
ACCURATE AND COORDINATED DIAGRAMS FOR SHOP DRAWING SUBMITTALS.
B. CONTRACTOR WILL PROVIDE ENGRAVED SWITCHES.
ROOM
LUMINAIRES
LIGHTING CONTROL DESCRIPTION
Scene (A) 50% Lumen Output or Manual-ON/Auto-OFF
Scene (B) 100% Lumen Output or Manual-ON/Auto-OFF
DIMMING ROOM
CONTROLLER
LMRC-211
D
0-10V CONTROL LOOP
(CLASS 2)
LIGHTING SEQUENCE OF OPERATION
A. CLASSROOMS & PRACTICE ROOMS:
1. UNOCCUPIED MODE:
WHEN ROOM IS UNOCCUPIED ALL LIGHTING SHALL BE DISABLED AND
DE-ENERGIZED BY OCCUPANCY SENSOR(S) IN ROOM.
2. OCCUPIED MODE:
a. LIGHTING CONTROL IN ROOM WILL BE ENABLED BY SWITCHES IN ROOM.
NO LUMINAIRES WILL AUTOMATICALLY ENERGIZE.
b. DURING OCCUPANCY AT TWO BUTTON SWITCH:
- TOP BUTTON (A) WILL BE PROGRAMMED TO CONTROL ALL
LUMINAIRES IN CLASSROOM AT 50% LUMEN OUTPUT. WHEN
BUTTON IS PUSHED AGAIN THE LUMINAIRES WILL TURN OFF.
- BOTTOM BUTTON (B) WILL BE PROGRAMMED TO CONTROL ALL
LUMINAIRES IN CLASSROOM AT 100% LUMEN OUTPUT. WHEN
BUTTON IS PUSHED AGAIN THE LUMINAIRES WILL TURN OFF.
c. WHEN PERSONNEL LEAVE THE ROOM THEY CAN TURN THE LUMINAIRES
OFF BY PUSHING SWITCH OR ALLOWING THE OCCUPANCY SENSOR TO
TIME OUT AND THE SYSTEM SHALL RESET TO THE UNOCCUPIED MODE.
B. ENTRY VESTIBULE:
a. TOGGLE SWITCH WILL TURN LUMINAIRES ON/OFF.
C. RESTROOMS:
a. DUAL TECHNOLOGY (ULTRA-SONIC/INFRARED) CEILING MOUNTED
SENSORS WILL CONTROL LUMINIARES ON AND OFF AUTOMATICALLY.
KEYED SWITCH WILL BE SECONDARY MEANS OF CONTROL.
D. STORAGE ROOMS:
a. WALL MOUNTED OCCUPANCY SENSOR WILL CONTROL THE LUMINAIRE IN
THE ROOM.
E. OFFICE:
a. LIGHTING CONTROL IN ROOM WILL BE ENABLED BY SWITCHES IN ROOM.
NO LUMINAIRES WILL AUTOMATICALLY ENERGIZE.
b. DURING OCCUPANCY AT TWO BUTTON SWITCH:
- LEFT BUTTON (A) WILL BE PROGRAMMED TO CONTROL ALL
LUMINAIRES IN THE OFFICE AT 50% LUMEN OUTPUT. WHEN
BUTTON IS PUSHED AGAIN THE LUMINAIRES WILL TURN OFF.
- RIGHT BUTTON (B) WILL BE PROGRAMMED TO CONTROL ALL
LUMINAIRES IN THE OFFICE AT 100% LUMEN OUTPUT. WHEN
BUTTON IS PUSHED AGAIN THE LUMINAIRES WILL TURN OFF.
c. WHEN PERSONNEL LEAVE THE ROOM THEY CAN TURN THE LUMINAIRES
OFF BY PUSHING SWITCH OR ALLOWING THE OCCUPANCY SENSOR TO
TIME OUT AND THE SYSTEM SHALL RESET TO THE UNOCCUPIED MODE.
HOT
120/277
1
NO. 12 GAUGE WIRE HANGER TO
BUILDING FRAMING OR STRUCTURAL
MEMBERS. SUSPEND FROM ALL FOUR
CORNERS OF THE LUMINAIRE
CAT5e
LMRJ-Watt Stopper Cable
WALL SWITCH
OCCUPANCY SENSOR
LMDW-102
CEILING SYSTEM
HANGER WIRES
(TYP.)
A B
Watt Stopper
REFER TO SHEET SERIES "EL" FOR LOCATIONS AND ADDITIONAL INFORMATION
LUMINAIRE SUPPORT DETAIL
C3
NO SCALE
PROJECT
NO SCALE
NEUTRAL
ROOM
LUMINAIRES
ROOM
LUMINAIRES
LIGHTING CONTROL DESCRIPTION
Scene (A) 50% Lumen Output or Manual-ON/Auto-OFF
Scene (B) 100% Lumen Output or Manual-ON/Auto-OFF
ROOM
LUMINAIRES
DIMMING ROOM
CONTROLLER
LMRC-211
Digitally signed by William
D. Herbst
Date: 2016.07.29
11:05:28-06'00'
WATT STOPPER "DLM" WIRING DIAGRAM
NEUTRAL
B
ENGINEER
DIMMING ROOM
CONTROLLER
LMRC-211
0-10V CONTROL LOOP
(CLASS 2)
HOT
120/277
0-10V CONTROL LOOP
(CLASS 2)
HOT
120/277
A = 50% LUMEN
OUTPUT
1
2
ROOM
LUMINAIRES
A = 50% LUMEN
OUTPUT
1
2
B = 100% LUMEN
OUTPUT
200 LONGHORN STREET
VEGA, TEXAS 79092
C
C1
RJ45
(TYPICAL)
SEISMIC FIXTURE CLAMPS:
REQUIRED AT ALL (4) LUMINAIRE
CORNERS WITH 2#10
SELF-TAPPING SCREWS. AGI
SEISMIC PRODUCTS OR EQUAL. AC
184 COMPLIANT.
LAY-IN LUMINAIRE
4600 C Montgomery Blvd. NE
Albuquerque, NM 87109
505.883.4111 www.bpce.com
BAND HALL RENOVATION
CEILING SYSTEM
HANGER WIRES
(TYP.)
B = 100% LUMEN
OUTPUT
100 % CONSTRUCTION
DOCUMENTS
REVISIONS
CAT5e
LMRJ-Watt Stopper Cable
LIGHTING CONTROL
DESCRIPTION PLACARD
MOUNT ADJACENT TO SWITCH
2 BUTTON SWITCH
LMSW-102
LMDC-100
SEE INSTALLATION INSTRUCTIONS
FOR TERMINATION TYPE
2 BUTTON SWITCH
LMSW-102
A
A
A
DRAWN BY
B
B
B
REVIEWED BY
Watt Stopper
Watt Stopper
LMDC-100
LMDC-100
LMDC-100
SEE INSTALLATION INSTRUCTIONS
FOR TERMINATION TYPE (TYPICAL)
RJ45
(TYPICAL)
A4
NO SCALE
JMM
14-0424.002
DRAWING NAME
LIGHTING
DETAIL &
DIAGRAMS
REFER TO SHEET SERIES "EL" FOR LOCATIONS AND ADDITIONAL INFORMATION
WATT STOPPER "DLM" WIRING DIAGRAM
BEL
7/29/2016
DATE
PROJECT NO.
RJ45
(TYPICAL)
REFER TO SHEET SERIES "EL" FOR LOCATIONS AND ADDITIONAL INFORMATION
A3
MOUNT ADJACENT TO SWITCHES
2 BUTTON SWITCH
LMSW-102
LMDC-100
Watt Stopper
A
LIGHTING CONTROL
DESCRIPTION PLACARD
CAT5e
LMRJ-Watt Stopper Cable
WATT STOPPER "DLM" WIRING DIAGRAM
NO SCALE
SHEET NO.
E-603
OF
1
2
3
4
5
1
2
3
4
5
D
4600 C Montgomery Blvd. NE
Albuquerque, NM 87109
505.883.4111 www.bpce.com
ENGINEER
C
Digitally signed by
William D. Herbst
Date: 2016.07.29
11:05:39-06'00'
B
200 LONGHORN STREET
VEGA, TEXAS 79092
BAND HALL RENOVATION
PROJECT
100 % CONSTRUCTION
DOCUMENTS
REVISIONS
DRAWN BY
BEL
REVIEWED BY
JMM
7/29/2016
DATE
PROJECT NO.
14-0424.002
DRAWING NAME
A
LUMINIARE
SCHEDULES
SHEET NO.
E-701
OF
1
2
3
4
5
1
2
3
4
5
D
4600 C Montgomery Blvd. NE
Albuquerque, NM 87109
505.883.4111 www.bpce.com
ENGINEER
C
Digitally signed by
William D. Herbst
Date: 2016.07.29
11:05:50-06'00'
B
200 LONGHORN STREET
VEGA, TEXAS 79092
BAND HALL RENOVATION
PROJECT
100 % CONSTRUCTION
DOCUMENTS
REVISIONS
DRAWN BY
BEL
REVIEWED BY
JMM
7/29/2016
DATE
PROJECT NO.
14-0424.002
DRAWING NAME
A
PANEL
SCHEDULES
SHEET NO.
E-702
OF
1
2
3
4
5