VIRGINIA TECH VIRGINIA TECH ATHLETIC INTERIORS SYMBOLS

ABBREVIATIONS
GENERAL NOTES
A/C
A/E
ABV
AD
ALT
AP
AIR CONDITIONING
ARCHITECT/ENGINEER
ABOVE
ACCESS DOOR
ALTERNATE
ACCESS PANEL
PH
PHASE
QTY
QUANTITY
R
REG
RM
RETURN
REGISTER
ROOM
BB
BG
BLDG
BOD
BASEBOARD RADIATION
BOTTOM GRILLE (3"-12" ABOVE FLOOR)
BUILDING
BOTTOM OF DUCT
S/W
SUMMER-WINTER
CAP
CC
CD
CH
CLG
CONV
CU FT
CAPACITY
COOLING COIL
CONDENSATE DRAIN
CABINET HEATER
COOLING
CONVECTOR
CUBIC FEET
3SF
TC
TD
TSTAT
TYP
3 HOUR SMOKE FIRE DAMPER
TEMPERATURE CONTROL
TRANSFER DUCT
THERMOSTAT
TYPICAL
DEMO
DG
DIA
DEMOLISH
DOOR GRILLE
DIAMETER
EA
EF
EFF
EL/ELEV
EST
EXHAUST AIR
EXHAUST FAN
EFFICIENCY
ELEVATION
ESTIMATE
EXH
EXT
EXHAUST
EXTERNAL
F
FLEX
FLR
FP
FPB
FPM
FPS
FR
FAHRENHEIT
FLEXIBLE
FLOOR
FIRE PROTECTION
FAN POWERED TERMINAL UNIT
FEET PER MINUTE
FEET PER SECOND
FINNED RADIATION
GRL
GRILLE
H
HC
HVAC
HUMIDISTAT OR HUMIDIFIER
HEATING COIL
HEAT, VENTILATION, & AIR CONDITIONING
LF
LINEAR FEET
MAINT
MAX
MFR
MIN
MISC
MAINTENANCE
MAXIMUM
MANUFACTURER
MINIMUM
MISCELLANEOUS
N.C.
NIC
NTS
NORMALLY CLOSED
NOT IN CONTRACT
NOT TO SCALE
COORDINATE INSTALLATION OF NEW DUCTWORK AND PIPING WITH
1.
REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR ALL CEILING 12.
EXISTING BUILDING STRUCTURE, DUCTWORK, PIPING, ELECTRICAL CONDUIT,
AIR DEVICE LOCATIONS.
LIGHTING, ETC.
2.
REFER TO ARCHITECTURAL ELEVATION DRAWINGS FOR LOCATION OF
13.
RELOCATE EXISTING DUCTWORK AND/OR PIPEWORK IN EXISTING CEILING
WALL MOUNTED MECHANICAL ITEMS.
SPACES TO ACCOMMODATE ALL RENOVATIONS AND ADDITIONS.
3.
LOCATE ALL DUCT BALANCING DAMPERS ABOVE ACCESSIBLE CEILINGS,
14.
TAKE DOWN AND REINSTALL EXISTING CEILINGS IN ALL AREAS WHERE
OR PROVIDE ACCESS DOORS. MINIMUM ACCESS DOOR SIZE SHALL BE 18x18
MECHANICAL WORK IS INDICATED AND EXISTING CEILINGS REMAIN. REFER TO
UNLESS OTHERWISE APPROVED BY ENGINEER. ACCESS DOOR FINISH SHALL
ARCHITECTURAL REFLECTED CEILING PLAN DRAWINGS FOR LOCATIONS WHERE
MATCH COLOR OF FINISHED CEILING.
EXISTING CEILINGS REMAIN. REPLACE CEILING TILES DAMAGED DURING WORK.
5.
PROVIDE VOLUME DAMPERS AT ALL SUPPLY, RETURN AND EXHAUST
15.
INSTALL ALL FLOOR MOUNTED HVAC EQUIPMENT, INCLUDING AHUS,
DUCT BRANCH TAKE-OFFS. SEE DUCT CONSTRUCTION DETAILS.
PUMPS, CHILLERS, ETC. ON 4" MINIMUM HEIGHT CONCRETE HOUSEKEEPING PAD.
EXTEND PAD MINIMUM 4" BEYOND EQUIPMENT AT ALL SIDES.
6.
BLANK-OFF AREAS OF LOUVERS NOT USED WITH 20 GAGE SHEET
METAL DOUBLE WALL BLANK-OFF PANEL INSULATED WITH 2" RIGID FIBERBOARD.
16.
PATCH ALL WALLS, FLOORS, CEILINGS, AND ROOFS TO MATCH
SEAL AIR TIGHT.
EXISTING IN ALL CASES WHERE EXISTING WALLS, FLOORS, CEILINGS AND
ROOFS REMAIN AND HVAC DEMOLITION IS INDICATED.
7.
INSTALL RIGID 1"x1" GALVANIZED STEEL WIRE MESH AT ALL OPEN
ENDED DUCTS IN OCCUPIED AREAS OR EXPOSED TO VIEW.
17.
THIS PROJECT CONSISTS OF MULTIPLE PHASES OF CONSTRUCTION
OVER A SPECIFIED TIME PERIOD. PROVIDE ALL WORK NECESSARY TO KEEP
8.
COORDINATE SCHEDULE FOR HOOKUPS TO EXISTING SYSTEM AND
EXISTING SYSTEMS IN SAFE OPERATION. PROVIDE ISOLATION (SHUT-OFF)
REMOVAL OR RELOCATION OF EQUIPMENT WITH THE OWNER. PERFORM THIS
VALVES AT ALL CONNECTION POINTS TO EXISTING SYSTEMS.
WORK AT SUCH TIMES TO ENSURE THAT PERIODS OF SHUTDOWN WILL BE
ACCEPTABLE TO THE OWNER.
9.
VERIFY EXACT LOCATION OF CONNECTION POINTS (NEW TO EXISTING) IN
FIELD PRIOR TO CONSTRUCTION.
VIRGINIA TECH
VIRGINIA TECH ATHLETIC
INTERIORS
3030 Clarendon Boulevard, Suite 500
Arlington, Virginia 22201
T: 703.907.2300
F: 703.907.2050
SYMBOLS
T
SUPPLY DUCT RISE
OR
TEMPERATURE SENSOR (IN DUCT OR PIPE)
PUMP
E
ROOM PRESSURIZATION MONITOR
ELECTRICAL CONNECTION (BY DIVISION 23)
RETURN DUCT RISE
RECTANGULAR WYE DUCT FITTING
EXHAUST DUCT RISE
POINT OF CONNECTION (NEW TO EXISTING)
SUPPLY DUCT DROP
NEW HVAC PIPE
SENSING ELEMENT - AIR STREAM
RETURN DUCT DROP
EXISTING HVAC PIPE
SENSING ELEMENT - LIQUID SEPARABLE WELL
EXHAUST DUCT DROP
EXISTING HVAC PIPE TO BE REMOVED
NEW DUCT
PIPE ELBOW DOWN
EXISTING DUCT
PIPE ELBOW UP
DEMOED DUCT
PIPE RISE OR DROP
26
D
DUCT SMOKE DETECTOR
FM
ELECTRICAL CONNECTION (BY DIVISION 26)
T
CURRENT SENSOR
CS
AUTO
THERMOSTAT WITH LOCKING
COVER
H
ON
OFF
TEMPERATURE SENSOR
T
200-2
HUMIDITY SENSOR
S
200-5
SWITCH
PIPE BOTTOM DROP
CAPPED DUCTWORK
OS
"Ø
DN
UP
PB
CONTROL VALVE (2-WAY)
DUCT OFF-SET UP (IN DIRECTION OF FLOW)
24x12
RECTANGULAR DUCT DIMENSIONS
(SIZE IN INCHES, FIRST DIMENSION IS SHOWN)
24"Ø
ROUND DUCT DIMENSIONS (DIAMETER)
24x12 OV
OCCUPANCY SENSOR
ROUND (DIAMETER)
DUCT OFF-SET DN (IN DIRECTION OF FLOW)
CONTROL VALVE (3-WAY)
O²
TRIPLE DUTY VALVE
OVAL DUCT DIMENSIONS
(SIZE IN INCHES, FIRST DIMENSION IS SHOWN)
CHECK VALVE (SHOWN W/FLOW)
SOLENOID VALVE
SINGLE LINE SUPPLY DUCT
P
SAFETY/RELIEF VALVE
R
SINGLE LINE EXHAUST DUCT
FLOW SWITCH
P
TYPE
250-7
4LF-2-1
VSD
PILOT LIGHTLETTER INDICATES
COLOR:
G - GREEN
Y - YELLOW
R - RED
FIRESTAT
ELBOW WITH TURNING VANES
OPPOSED BLADE VOLUME
DAMPERS
EXPANSION JOINT
VOLUME DAMPER
EXPANSION LOOP
FIRE, SMOKE/FIRE, OR SMOKE DAMPER
IN RISER
STRAINER W/BLOWDOWN VALVE
SMOKE
AIT
FIRE, SMOKE/FIRE, OR SMOKE DAMPER
FD,SF, OR SM
BDD
AIF
TP
OR
TRAP
AO
DO
MOTORIZED DAMPER
PIPE GUIDE
BACKDRAFT DAMPER
DIRECTION OF FLOW
PIPE ANCHOR
AOP
A1
NEW EQUIPMENT
B
EXISTING
EX-XXX
EXISTING EQUIPMENT
N
EQUIPMENT TYPE
KEY PLAN
ANALOG INPUT, TEMPERATURE
ANALOG INPUT, FLOW
ANALOG OUTPUT
DIGITAL OUTPUT
DI
FLEXIBLE CONNECTION
A2
LINEAR DIFFUSER
1
M0101
CALLOUT INDICATOR TOP INDICATES
NUMBER ON THE SHEET BOTTOM
INDICATES SHEET NUMBER
1
M0101
SECTION INDICATOR TOP INDICATES
SECTION NUMBER BOTTOM
INDICATES SHEET NUMBER
Drawing Title:
ANALOG INPUT
AI
PIPING FLOW METER
SUPPLY/ RETURN/EXHAUST SIDEWALL GRILLEFIRST NO. CFM, SECOND NO. TYPE
BOTTOM NO. WIDTH BY HEIGHT OF GRILLE
(REFER TO SPECIFICATION FOR AIR DEVICE TYPE)
EQUIPMENT TYPE
SMOKE DETECTOR
ANALOG INPUT, PRESSURE
AIP
FM
Date
SLOT WIDTH (INCHES)
XXX-1
FLEXIBLE DUCT
FD,SF, OR SM
7/24/2015 4:57:29 PM
© Cannon Design 2015
All rights reserved. No part of this document may
be reproduced or utilized in any form, without prior
written authorization by The Cannon Corporation.
OR
24 JUL 2015
Description
VARIABLE SPEED DRIVE
FIRE
PRESSURE/TEMPERATURE TEST PORT
SCHEMATIC DESIGN
LENGTH
SINGLE LINE DUCT RISE OR DROP
OR
No.
TYPE NO.
UNION
CLEANOUT (CO)
EXHAUST AIR DEVICE (REFER TO SCHEDULE FOR SIZE)
FIRST NO. CFM, SECOND NO. TYPE
(REFER TO SPECIFICATION FOR AIR DEVICE TYPE)
PNEUMATIC-ELECTRIC SWITCH
EXISTING ITEM TO BE REMOVED
CO
RETURN AIR DEVICE (REFER TO SCHEDULE FOR SIZE)
FIRST NO. CFM, SECOND NO. TYPE
(REFER TO SPECIFICATION FOR AIR DEVICE TYPE)
ELECTRIC-PNEUMATIC SWITCH
P
MANUAL AIR VENT
SUPPLY AIR DEVICE (REFER TO SCHEDULE FOR SIZE)
FIRST NO. CFM, SECOND NO. TYPE
(REFER TO SPECIFICATION FOR AIR DEVICE TYPE)
NO. OF SLOTS
E
G
HOSE DRAIN VALVE WITH CAP
STARTER
CFM
FREEZESTAT
VALVE
EXISTING SINGLE LINE DUCT
200-14
10x8
RELAY
F
E
CARBON DIOXIDE SENSOR
PRESSURE GAGE
PRESSURE REDUCING VALVE
SINGLE LINE RETURN DUCT
200-5
OXYGEN SENSOR
FS
BALANCING VALVE
CAPPED PIPING OR SINGLE DUCTWORK
PUSH BUTTON
CO²
AIR FLOW MEASURING STATION
DIGITAL INPUT
ANALOG OUTPUT, PNEUMATIC
SYMBOLS,
ABBREVIATIONS, AND
GENERAL NOTES
Project No.: 004815.00
Checked by: Checker
M0001
© Cannon Design 2015
23
24
Kx
GENERAL NOTES:
1.
22
2.
3.
21
Jx
4.
MECHANICAL CONTRACTOR SHALL PERFORM
PRE-DEMOLITION BALANCING AND REBALANCE
ALL DIFFUSERS/GRILLES TO MATCH PRERENOVATION CONDITIONS.
FIRE PROTECTION CONTRACTOR SHALL FIELD
VERIFY EXISTING CONDITIONS AND REMOVE ALL
EXISTING SPRINKLER HEADS AND RELATED
BRANCH/ARMOVER PIPING. PROVIDE NEW
SPRINKLER HEADS AND RELATED
BRANCH/ARMOVER PIPING TO ALIGN WITH NEW
CEILING LAYOUT THROUGHOUT RENOVATED
AREAS AS REQUIRED.
SPRINKLER HEAD TYPE AND MANUFACTURER
SHALL MATCH EXISTING, COORDINATE WITH
ARCHITECT AS REQUIRED.
SPRINKLER HEAD COVERAGE SHALL BE IN
ACCORDANCE WITH NFPA 13 APPLICABLE
ADDITION AND LOCAL AUTHORITIES HAVING
JURISDICTION.
VIRGINIA TECH
VIRGINIA TECH ATHLETIC
INTERIORS
NOTES:
Fx
1.
PROVIDE NEW GRILLE/DIFFUSER TO MATCH
EXISTING.
2.
RELOCATE EXISTING THERMOSTAT TO LOCATION
SHOWN.
3.
EXISTING CABINET UNIT HEATER TO REMAIN.
3030 Clarendon Boulevard, Suite 500
Arlington, Virginia 22201
T: 703.907.2300
F: 703.907.2050
Kx
1
Ex
Jx
1
1
1
1
1
Cx
Fx
24
-
SCHEMATIC DESIGN
No.
23
24 JUL 2015
Description
Date
1
Ex
A2
1
22
A1
1
21gg
B
21ff
21ee
21
N
T
2
KEY PLAN
Cx
3
21dd
AB
LEVEL ONE MECHANICAL PLAN
1
BB
7/24/2015 4:57:30 PM
© Cannon Design 2015
All rights reserved. No part of this document may
be reproduced or utilized in any form, without prior
written authorization by The Cannon Corporation.
Drawing Title:
Project No.: 004815.00
Checked by:
SJJ
M0101
© Cannon Design 2015
23
24
Kx
GENERAL NOTES:
1.
22
2.
3.
21
Jx
4.
MECHANICAL CONTRACTOR SHALL PERFORM
PRE-DEMOLITION BALANCING AND REBALANCE
ALL DIFFUSERS/GRILLES TO MATCH PRERENOVATION CONDITIONS.
FIRE PROTECTION CONTRACTOR SHALL FIELD
VERIFY EXISTING CONDITIONS AND REMOVE ALL
EXISTING SPRINKLER HEADS AND RELATED
BRANCH/ARMOVER PIPING. PROVIDE NEW
SPRINKLER HEADS AND RELATED
BRANCH/ARMOVER PIPING TO ALIGN WITH NEW
CEILING LAYOUT THROUGHOUT RENOVATED
AREAS AS REQUIRED.
SPRINKLER HEAD TYPE AND MANUFACTURER
SHALL MATCH EXISTING, COORDINATE WITH
ARCHITECT AS REQUIRED.
SPRINKLER HEAD COVERAGE SHALL BE IN
ACCORDANCE WITH NFPA 13 APPLICABLE
ADDITION AND LOCAL AUTHORITIES HAVING
JURISDICTION.
VIRGINIA TECH
VIRGINIA TECH ATHLETIC
INTERIORS
NOTES:
1
1.
3030 Clarendon Boulevard, Suite 500
Arlington, Virginia 22201
T: 703.907.2300
F: 703.907.2050
PROVIDE NEW GRILLE/DIFFUSER TO MATCH
EXISTING.
Fx
1
Kx
Ex
1
Jx
1
1
Cx
1
Fx
24
-
SCHEMATIC DESIGN
No.
24 JUL 2015
Description
Date
23
A2
Ex
A1
22
B
1
21gg
N
21ff
KEY PLAN
21ee
21
21dd
Cx
LEVEL TWO MECHANICAL PLAN JAMERSON
AB
7/24/2015 4:57:30 PM
© Cannon Design 2015
All rights reserved. No part of this document may
be reproduced or utilized in any form, without prior
written authorization by The Cannon Corporation.
Drawing Title:
BB
Project No.: 004815.00
Checked by: Checker
M0102
© Cannon Design 2015
GENERAL NOTES:
1.
2.
21gg
3.
A
21dd
B
D
4.
21ff
MECHANICAL CONTRACTOR SHALL PERFORM
PRE-DEMOLITION BALANCING AND REBALANCE
ALL DIFFUSERS/GRILLES TO MATCH PRERENOVATION CONDITIONS.
FIRE PROTECTION CONTRACTOR SHALL FIELD
VERIFY EXISTING CONDITIONS AND REMOVE ALL
EXISTING SPRINKLER HEADS AND RELATED
BRANCH/ARMOVER PIPING. PROVIDE NEW
SPRINKLER HEADS AND RELATED
BRANCH/ARMOVER PIPING TO ALIGN WITH NEW
CEILING LAYOUT THROUGHOUT RENOVATED
AREAS AS REQUIRED.
SPRINKLER HEAD TYPE AND MANUFACTURER
SHALL MATCH EXISTING, COORDINATE WITH
ARCHITECT AS REQUIRED.
SPRINKLER HEAD COVERAGE SHALL BE IN
ACCORDANCE WITH NFPA 13 APPLICABLE
ADDITION AND LOCAL AUTHORITIES HAVING
JURISDICTION.
VIRGINIA TECH
VIRGINIA TECH ATHLETIC
INTERIORS
NOTES:
BB
21x
21x
21cc
6
1.
PROVIDE NEW GRILLE/DIFFUSER TO MATCH
EXISTING.
2.
PROVIDE NEW EXHAUST GRILLE IN LOCATION SHOWN.
RECONFIGURE DUCTWORK TO ACCOMODATE NEW
GRILLE LOCATION.
3.
RELOCATE EXISTING THERMOSTAT TO LOCATION
SHOWN.
4.
EXISTING FIN TUBE RADIATION TO REMAIN.
5.
PROVIDE NEW ADA COMPLIANT WATER FOUNTAIN
ADJACENT TO EXISTING WATER FOUNTAIN.
PROVIDE NEW DOMESTIC COLD WATER
CONNECTION FROM EXISTING MAIN ABOVE CEILING.
PROVIDE SHUT OFF VALVE AT BRANCH TAKE OFF
FROM MAIN.
6.
EXISTING DIFFUSER/GRILLE TO REMAIN.
6
T
3
18
CB
18
21bb
2
6
6
21aa
15
15
3030 Clarendon Boulevard, Suite 500
Arlington, Virginia 22201
T: 703.907.2300
F: 703.907.2050
DB
21z
6
6
12
EB
12
FB
11
1
5
7
7
6
6
-
SCHEMATIC DESIGN
No.
24 JUL 2015
Description
Date
4
1
A2
1
1
A1
3
3
B
1
1
N
KEY PLAN
LEVEL TWO MECHANICAL PLAN MERRYMAN
7/24/2015 4:57:31 PM
© Cannon Design 2015
All rights reserved. No part of this document may
be reproduced or utilized in any form, without prior
written authorization by The Cannon Corporation.
Drawing Title:
A
B
D
F
Project No.: 004815.00
Checked by: Checker
M0103
© Cannon Design 2015
ABBREVIATIONS
1. FOR EXACT LOCATION AND FINISH SURFACE CONDITIONS OF CEILING, WALL, FLOOR MOUNTED DEVICES,
REFER TO ARCHITECTURAL DRAWINGS.
2. FOR EXACT LOCATION OF FACILITY EXPANSION JOINTS, FIRE RATED WALLS AND SMOKE WALLS, REFER
TO ARCHITECTURAL DRAWINGS.
3. FOR EXACT LOCATIONS OF DUCT MOUNTED SMOKE DETECTORS, WATER FLOW SWITCHES AND
TAMPER SWITCHES REFER TO HVAC / FP DRAWINGS.
4. VERIFY EXACT LOCATION OF CONNECTION POINTS PRIOR TO CONNECTION.
5.
MOUNTING HEIGHTS ARE TO CENTER OF DEVICE OR EQUIPMENT, UNO.
6. PROVIDE RACEWAY, WIRE AND CABLE, ASSOCIATED FITTINGS AND CONNECTORS, AND COMPLETE
CONNECTIONS REQUIRED FOR DESIGNATED BRANCH CIRCUITS FROM DEVICE(S) TO FINAL OVERCURRENT
DEVICE AND TO LOCAL CONTROL DEVICE(S) PER SPECIFICATIONS.
7. MINIMUM BRANCH CIRCUIT WIRE SIZE SHALL BE #12 AWG EXCEPT LIFE SAFETY BRANCH CIRCUIT WIRING
WHICH SHALL BE MINIMUM #10 AWG. MAINTAIN MAXIMUM BRANCH CIRCUIT CONDUCTOR LENGTHS AS PER
SPECIFICATIONS AND SCHEDULED ON THIS DRAWING. INCLUDE GROUND CONDUCTOR DERATINGS.
8. PULL A SEPARATE NEUTRAL CONDUCTOR FROM PANELBOARD FOR EACH SET OF INCANDESCENT
LUMINARIES CONTROLLED FROM A DIMMER, EACH BRANCH CIRCUIT SERVING FLUORESCENT LUMINARIES,
EACH BRANCH CIRCUIT SERVING NEMA 5 RECEPTACLES WITHIN SIX (6) FEET OF COMPUTER DEVICE JACKS,
AND EACH BRANCH CIRCUIT PROTECTED BY A GROUND FAULT CIRCUIT INTERRUPTER. DERATE
CONDUCTORS PER NEC ACCORDINGLY.
9. PROVIDE GROUNDING PER NEC. ALSO PROVIDE GREEN GROUND WIRE IN ALL BRANCH AND FEEDER
CIRCUITS SIZED PER NEC.
10. THE SPACE ABOVE THE CEILING IS LIMITED AND THE INSTALLATION OF WORK WILL BE TIGHT. DUE TO
THIS, IT IS IMPORTANT THAT THE TRADE CONTRACTOR SHALL COORDINATE THE INSTALLATION OF THEIR
WORK (IE: DUCTWORK, TERMINAL UNITS, PIPING, ETC) WITH THE EXISTING CEILING SYSTEM HEIGHT AND
CONSTRUCTION, THE STRUCTURAL SYSTEM, THE LIGHTING FIXTURES, THE SPRINKLER HEADS/MAINS, AND
THE PLUMBING PIPES. ROUTE DUCTWORK AND PIPING AS HIGH AS POSSIBLE. LOCATE TERMINAL UNITS
BETWEEN STRUCTURAL BEAMS AND MAINTAIN PROPER SERVICE ACCESS CLEARANCES.
11.
DO NOT INSTALL ANY NEW WORK DIRECTLY ABOVE ANY ELECTRICAL PANELS AND TRANSFORMERS.
12. CIRCUIT NUMBERS SHOWN FOR EQUIPMENT WIRED TO EXISTING PANELBOARD(S) IS SHOWN FOR
DESIGN INTENT ONLY AND MAY NOT CORRESPOND TO ACTUAL CIRCUIT BREAKER MOUNTING POSITION IN
THE PANEL. UPDATE THE AS-BUILT DRAWINGS WITH THE ACTUAL CIRCUIT NUMBERS USED TO
CORRESPOND TO THE PANEL DIRECTORY.
13. CONFIRM ALL LABELS AND ROOM NUMBERS WITH OWNER PRIOR TO FINALIZING LABELING AND
PROGRAMMING.
14. COORDINATE FINAL OUTLET LOCATION WITH ALL TRADES AND FURNITURE/MILLWORK PLACEMENT
PRIOR TO ROUGH-IN.
15.
INSTALL DATA OUTLETS 6" AWAY FROM ASSOCIATED ELECTRICAL OUTLET.
DEVICE SUBSCRIPTS
II
a
7
A
B
BF
BS
C
C*
D
E
EN
EO
EQ
ER
ERL
EX
FL
GFCI
GFI
GFP
H
HA
HG
IG
K
L
LV
M
M*
NL
NLG
P
PP
Q
S
SG
SP
SW
TR
USB
W
WG
WP
WPS
Z*
ROMAN NUMERAL INDICATES QUANTITY OF GANGED DEVICES UNDER COMMON FACEPLATE
LOWER CASE LETTER(S) INDICATES MULTI SWITCH CONTROL ARRANGEMENT
NUMERAL INDICATES BRANCH CIRCUIT NUMBER
WITH AUXILIARY CONTACTS
REMOVE DEVICE AND INSTALL BLANK COVERPLATE
BLANK FACE GFCI
ITEM CONTROLLED BY BED STOP RELAY
ITEM INSTALLED FLUSH IN CEILING
CONTROL POINT IDENTIFIER (*INDICATES CONTROL NUMBER)
120 VOLT DISCONNECT SWITCH ARRANGEMENT
EXISTING BACKBOX TO REMAIN AND BE REUSED
EXISTING LOCATION NEW DEVICE
EQUIPMENT SUPPLIED BY OWNER
ITEM INSTALLED IN EQUIPMENT
EXISTING TO BE REMOVED
EXISTING TO BE RELOCATED
EXISTING DEVICE NEW LOCATION
ITEM INSTALLED FLUSH IN FLOOR
GROUND FAULT CIRCUIT INTERRUPTING RECEPTACLE
GROUND FAULT CIRCUIT INTERRUPTING BREAKER PROTECTED
FEED THROUGH GROUND FAULT CIRCUIT INTERRUPTING PROTECTED
HORIZONTALLY MOUNTED
HIGH ABUSE COVERPLATE
HOSPITAL GRADE
ISOLATED GROUND RECEPTACLE
KEY OPERATED
LOCATOR STYLE SWITCH OPERATING HANDLE
LOW VOLTAGE
MULLION MOUNTED
MONITORING POINT IDENTIFIER (*INDICATES MONITORING POINT)
NIGHT LIGHT RECEPTACLE
NIGHT LIGHT GFCI RECEPTACLE
PILOT TYPE SWITCH OPERATING HANDLE
FOR AUTO DOOR PUSH PLATE
QUAD (DOUBLE DUPLEX) DEVICE
SURFACE MOUNTED
SAFETY GROUNDING RECEPTACLE
SURGE PROTECTOR RECEPTACLE
SPLIT WIRED RECEPTACLE FOR REMOTE SWITCHING
TAMPER RESISTANT
USB PORT CHARGING RECEPTACLE
ITEM INSTALLED 3'-8" AFF OR AS DETAILED
WIRE GUARD
WEATHERPROOF
WEATHERPROOF SPRING COVER
DEVICE ZONE IDENTIFIER (* INDICATES ZONE NUMBER)
BRANCH VOLTAGE DROP
CONDUCTOR AWG
MAXIMUM CONDUCTOR LENGTH AT 120V
MAXIMUM CONDUCTOR LENGTH AT 277V
MAXIMUM CONDUCTOR LENGTH AT 208V 1 PH.
MAXIMUM CONDUCTOR LENGTH AT 480V 1 PH.
GROUND CONDUCTOR AWG
#12
#10
#8
95
225
170
390
#12
160
375
280
650
#10
245
565
425
985
#8
NOTES:
1. INCREASE BRANCH CIRCUIT CONDUCTOR AS INDICATED.
2. BASED ON 20A CIRCUIT LOADED TO 10A USING SINGLE PHASE, 2 WIRE CIRCUITS.
3. SCHEDULE REPRESENTS MINIMUM CONDUCTOR SIZE BASED ON LENGTH OF BRANCH
CIRCUIT CONDUCTOR FROM PANEL TO PHYSICAL CENTER OF LOAD TO OVERCOME
VOLTAGE DROP. 3% VOLTAGE DROP ASSUMED.
4. TRANSITION FROM LARGER CONDUCTOR SIZE TO #12 FOR FINAL TERMINATION TO
OUTLET DEVICE. PROVIDE JUNCTION BOX WITHIN 10' OF OUTLET. EXTEND #12
CONDUCTOR TO OUTLET.
GENERAL
NEW EQUIPMENT
DEVICE TO BE REMOVED (DEMO PLANS) UNDERFLOOR CONDUIT (NEW PLANS)
AMPERE
ARMOR CLAD CABLE
ARC-FAULT CIRCUIT INTERRUPTING
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AUTHORITY HAVING JURISDICTION
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
ALUMINUM
AMMETER
ANNUNCIATOR
AMERICAN NATIONAL STANDARDS INSTITUTE
AUTOMATIC TRANSFER SWITCH
AUDIO VISUAL
AMERICAN WIRE GAUGE
BAS
BDF
BFC
BFG
BKBD
BKR
BPS
BUILDING AUTOMATION SYSTEM
BUILDING DISTRIBUTION FRAME
BELOW FINISHED CEILING
BELOW FINISHED GRADE
BACKBOARD
BREAKER
BOLTED PRESSURE SWITCH
C
CAT
CATV
CB
CCTV
CEC
CKT
CLG
CM
CO
COAX
CT
CTTS
CU
CONDUIT
CATALOG
CABLE ANTENNA TELEVISION
CIRCUIT BREAKER
CLOSED CIRCUIT TELEVISION
CHICAGO ELECTRICAL CODE
CIRCUIT
CEILING
CONSTRUCTION MANAGER
COMPANY
COAXIAL
CURRENT TRANSFORMER
CLOSE TRANSITION TRANSFER SWITCH
COPPER
DC
DHCP
DIA
DIV
DN
DO
DPDT
DPST
DS
DSP
DVD
DVR
DVS
DWG
DIRECT CURRENT
DYNAMIC HOST CONFIGURATION PROTOCOL
DIAMETER
DIVISION
DOWN
DRAWOUT
DOUBLE POLE DOUBLE THROW
DOUBLE POLE SINGLE THROW
DISCONNECT SWITCH
DIGITAL SIGNAL PROCESSOR
DIGITAL VERSATILE DISC
DIGITAL VIDEO RECORDER
DIGITAL VIDEO SURVEILLANCE
DRAWING
EA
EF
EGS
ELEC
ELEV
EMT
EO
EOL
EQUIP
EWC
EXH
EXP
EACH
EXHAUST FAN
ENGINE-GENERATOR SET
ELECTRIC
ELEVATOR
ELECTRICAL METALLIC TUBING
EQUIPMENT BY OWNER
END OF LINE DEVICE
EQUIPMENT
ELECTRIC WATER COOLER
EXHAUST
EXPLOSION PROOF
FA
FACU
FBO
FI
FLR
FLUOR
FPS
FPU
FS
FTL
FIRE ALARM
FIRE ALARM CONTROL UNIT
FURNISHED BY OWNER
FILM ILLUMINATOR
FLOOR
FLUORESCENT
FRAMES PER SECOND
FIELD PROCESSING UNIT
FUSED SWITCH
FEED THRU LUGS
GA
Gb
GE
GEN
GFCI
GFI
GFR
GFRT
GND
GAUGE
GIGABIT
GROUNDING EQUALIZER CONDUCTOR
GENERATOR
GROUND FAULT CIRCUIT INTERRUPTING
GROUND FAULT INTERRUPTING
GROUND FAULT RELAY
GROUND FAULT RELAY TEST PANEL
GROUND
HCT
HF
HFT
HARMONIC CONDITIONING TRANSFORMER
HARMONIC FILTER
HARMONIC FILTER WITH INTEGRAL
TRANSFORMER
HID
HIGH INTENSITY DISCHARGE
HOA
HAND OFF AUTO
HP
HORSEPOWER
HST
HARMONIC SUPPRESSION TRANSFORMER
HSKPG HOUSEKEEPING
HTR
HEATER
HV
HIGH VOLTAGE
HZ
HERTZ (CYCLES/SECOND)
ICC
ID
IDF
IMC
IP
IPS
iSCSI
IR
INTERMEDIATE CROSS CONNECT
INSIDE DIAMETER
INTERMEDIATE DISTRIBUTION FRAME
INTERMEDIATE METAL CONDUIT
INTERNET PROTOCOL
IMAGES PER SECOND
INTERNET SMALL COMPUTER SYSTEM
INTERFACE
INFRARED
JB
JUNCTION BOX
KO
KV
KVA
KW
KWH
KNOCK OUT
KILOVOLT
KILOVOLT AMPERE
KILOWATT
KILOWATT HOUR
LA
LAN
LCD
LED
LS
LTD
LTG
LV
LIGHTNING ARRESTOR
LOCAL AREA NETWORK
LIQUID CRYSTAL DISPLAY
LIGHT EMITTING DIODE
LIFE SAFETY
LONG TIME DELAY
LIGHTING
LOW VOLTAGE
MAG
MAN
MAX
MATV
Mb
MC
MAGNETIC
MANUAL
MAXIMUM
MASTER ANTENNA TELEVISION
MEGABIT
METAL CLAD CABLE
MCA
MCB
MCC
MCS
MCP
MDF
MDP
MECH
MER
MFGR
MFS
MGP
MH
MI
MIC
MIN
MLO
MM
MOCP
MTD
MTS
MV
MINIMUM CIRCUIT AMPERES
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MOLDED CASE SWITCH
MOTOR CIRCUIT PROTECTOR
MAIN DISTRIBUTION FRAME
MAIN DISTRIBUTION PANELBOARD
MECHANICAL
MAIN EQUIPMENT ROOM
MANUFACTURER
MAIN FUSED SWITCH
MEDICAL GAS PANEL
MANHOLE
MINERAL INSULATED CABLE
MICROPHONE
MINIMUM
MAIN LUGS ONLY
MULTIMODE
MAXIMUM OVERCURRENT PROTECTION
MOUNTED
MANUAL TRANSFER SWITCH
MEDIUM VOLTAGE
N
NA
NC
NEC
NEMA
NFPA
NIC
NO
NOC
NTS
NEUTRAL
NOT APPLICABLE
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NATIONAL FIRE PROTECTION ASSOCIATION
NOT IN CONTRACT
NORMALLY OPEN
NETWORK OPERATIONS CENTER
NOT TO SCALE
OA
OC
OCPD
OD
OH
OUTSIDE AIR
ON CENTER
OVERCURRENT PROTECTIVE DEVICE
OUTSIDE DIAMETER
OVERHEAD
P
PA
PB
PC
PCU
P/E
PH
PNL
PLC
PoE
PRI
PSU
PT
PTZ
PVC
PWR
POLE
PUBLIC ANNOUNCEMENT
PULLBOX/PUSHBUTTON
PERSONAL COMPUTER
PACKAGED CONTROL UNIT
PNEUMATIC- ELECTRIC
PHASE
PANELBOARD
PROGRAMMABLE LOGIC CONTROLLER
POWER OVER ETHERNET
PRIMARY
PATIENT SERVING UNIT
POTENTIAL TRANSFORMER
PAN TILT ZOOM
POLYVINYL CHLORIDE
POWER
RAID
RCP
RCPT
RE
REF
RF
RF
RFID
RGS
RM
RTLS
RUPS
REDUNDANT ARRAY OF INDEPENDENT DISKS
REFLECTED CEILING PLANS
RECEPTACLE
REFER TO
REFRIGERATOR
RADIO FREQUENCY
RETURN FAN
RADIO FREQUENCY IDENTIFICATION DEVICE
RIGID GALVANIZED STEEL
ROOM
REAL TIME LOCATION SYSTEM
ROTARY HYBRID UNINTERRUPTIBLE POWER
SUPPLY
SCHED SCHEDULE
SEC
SECONDARY
SF
SUPPLY FAN
SFL
SUB FEED LUGS
SFP
SURGICAL FACILITY PANEL
SH
SHEET
SM
SINGLE MODE
SP
SINGLE POLE
SPDT SINGLE POLE DOUBLE THROW
SPST SINGLE POLE SINGLE THROW
SPC
SPACE
SPEC SPECIFICATION
SPKR SPEAKER
SPR
SPARE
SS
STAINLESS STEEL
ST
SHUNT TRIP
STD
SHORT TIME DELAY
STP
SHIELDED TWISTED PAIR
STR
STARTER
SWBD SWITCHBOARD
SWGR SWITCHGEAR
SYM
SYMMETRICAL
TB
TBB
TC
TERM
TEL
TGB
TERRA BYTES
TELECOMMUNICATIONS BONDING BACKBONE
TERMINAL CABINET
TERMINAL
TELEPHONE
TELECOMMUNICATIONS GROUNDING
BUS BAR
THD
TOTAL HARMONIC DISTORTION
TMGB TELECOMMUNICATIONS MAIN GROUNDING
BUS BAR
TR
TELECOM ROOM
TRANS TRANSITION
TSER TELECOMMUNICATIONS SERVICE ENTRANCE
ROOM
TTC
TELEPHONE TERMINAL CABINET
TV
TELEVISION
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION
TYP
TYPICAL
UC
UG
UNO
UPS
USS
UTP
UNDER COUNTER
UNDERGROUND
UNLESS NOTED OTHERWISE
UNINTERRUPTIBLE POWER SUPPLY
UNIT SUBSTATION
UNSHIELDED TWISTED PAIR
V
VAV
VM
VolP
VPI
VSD
VOLT
VARIABLE AIR VOLUME
VOLTMETER
VOICE OVER INTERNET PROTOCOL
VACUUM-PRESSURE IMPREGNATED
VARIABLE SPEED DRIVE
W
WAN
WAP
WLAN
WP
WATT
WIDE AREA NETWORK
WIRELESS ACCESS POINT
WIRELESS LOCAL AREA NETWORK
WEATHERPROOF
XFMR
TRANSFORMER
DRAWING KEYED NOTES
CCR*
CEILING CONCEALED, REGRESSED BACKBOX
X
CABLE ROUTING NOTES
FEW*
FLOOR BOX, EXPOSED, WITH PROVISIONS FOR WHIP
300/4
EXISTING EQUIPMENT DESIGNATION
FEF*
FLOOR BOX, EXPOSED, FLUSH
XXX
LAB EQUIPMENT TAG
FET*
FLOOR BOX, EXPOSED, WITH TOMBSTONE DEVICE
NEW EQUIPMENT DESIGNATION
FCR*
FLOOR BOX, CONCEALED, WITH REGRESSED DEVICES
EQUIPMENT DESIGNATION NUMBER
PEW*
POKE-THRU ASSEMBLY, EXPOSED, WITH PROVISIONS FOR WHIP
FEEDER IDENTIFICATION
PEF*
POKE-THRU ASSEMBLY, EXPOSED, FLUSH
SYMBOL WITH DASHED OUTLINE INDICATES INSTALLATION AT CEILING
PET*
POKE-THRU ASSEMBLY, EXPOSED, WITH TOMBSTONE DEVICE
SYMBOL WITH TAIL INDICATES WALL INSTALLATION, HEIGHT AS INDICATED
PCR*
POKE-THRU ASSEMBLY, CONCEALED, WITH REGRESSED DEVICES
RCR*
RAISED FLOOR BOX, CONCEALED, WITH REGRESSED DEVICES
REW*
RAISED FLOOR BOX, EXPOSED, WITH PROVISIONS FOR WHIP
SCR*
STAGE BOX, CONCEALED, WITH REGRESSED DEVICES
TEF*
TABLE BOX, EXPOSED, FLUSH
TET*
TABLE BOX, EXPOSED, WITH TOMBSTONE DEVICE
TCR*
TABLE BOX, CONCEALED, WITH REGRESSED DEVICES
UEF*
UNDER FLOOR DUCT, EXPOSED, FLUSH
UET*
UNDER FLOOR DUCT, EXPOSED, WITH TOMBSTONE DEVICE
NUMBERS INDICATES SOURCE PANELBOARD AND CIRCUIT(S)
WEW*
WALL BOX, EXPOSED, WITH PROVISIONS FOR WHIP
SPLICE
WCR*
WALL BOX, CONCEALED, WITH REGRESSED DEVICES
X
(E) XXX
WIRE AND CABLE
NEUTRAL WIRE SHOWN AS A LONG LINE, PHASE WIRE SHOWN AS SHORT LINES, AND
GROUND WIRE SHOWN AS LONG LINE WITH DOT
THREE CIRCUIT HOME RUN IN CONDUIT TO ASSOCIATED PANELBOARD. NUMBERS INDICATE
CIRCUIT NUMBERS. ARROWS INDICATE QUANTITY OF 20A-1P CIRCUITS. SLASH MARKS
INDICATE QUANTITY OF WIRE
5
3
1
1LNL1
MULTI-CIRCUIT HOME RUN IN CONDUIT TO ASSOCIATED PANELBOARD. SLASH MARKS
#10 INDICATE QUANTITY OF WIRES. PHASE WIRE SIZE SHOWN FOLLOWING THE # SYMBOL IF
APPLICABLE
30A-2P
1LNL1
1LNL1-12
DETAIL AND/OR SECTION REFERENCE
BRANCH CIRCUIT BOUNDARY
VIRGINIA TECH
NOTE: SPEC REFERENCES ARE GENERAL AND MAY NOT BE SPECIFIC
ACCESS
C - CONCEALED
E - EXPOSED
SERVICE COVER/DEVICE FITTING
B - BLANK
F - FLUSH
R - REGRESSED
S - SEMI FLUSH
T - TOMBSTONE
W - WHIP
LOCATION
F - FLOOR
P - POKE-THRU
R - RAISED FLOOR
S - STAGE
T - TABLE
U - UNDER FLOOR DUCT
W - WALL
SEQUENTIAL NUMBER
LIGHTING BRANCH CIRCUITS
XXX
#
a
XXX
#
a
LUMINAIRE TAG - CORRESPONDS TO LUMINAIRE SCHEDULE
CIRCUIT NUMBER (AND PANELBOARD IF SPECIFICALLY DESIGNATED)
LOWER CASE LETTER(S) INDICATE MULTI-SWITCH CONTROL ARRANGEMENT.
POWER BRANCH CIRCUITS
#
#
CIRCUIT NUMBER (AND PANELBOARD IF SPECIFICALLY DESIGNATED)
WIRING TERMINATIONS
X
#
VIRGINIA TECH ATHLETIC
INTERIORS
IDENTIFICATION CHART
DIVISION 26: LEGEND
1
X
#
1
DIRECT CONNECTION OR MATCHING RECEPTACLE FOR 120V EQUIPMENT
E
DIRECT CONNECTION OR RECEPTACLE FOR 120V CRITICAL EQUIPMENT (NEC 517)
E
DIRECT CONNECTION OR RECEPTACLE FOR 120V EMERGENCY EQUIPMENT (NEC 700)
DMS
DIMMING MASTER STATION, 3'-8" AFF
2
DIRECT CONNECTION OR MATCHING RECEPTACLE FOR 208V EQUIPMENT
RCS
REMOTE CONTROL STATION, 3'-8" AFF
5
DIRECT CONNECTION OR MATCHING RECEPTACLE FOR 277V EQUIPMENT
EQUIPMENT IDENTIFICATION TAG.
CIRCUIT NUMBER (AND PANELBOARD IF SPECIFICALLY DESIGNATED)
3030 Clarendon Boulevard, Suite 500
Arlington, Virginia 22201
T: 703.907.2300
F: 703.907.2050
____
REFER TO MULTI-SERVICE BOX SCHEDULE FOR ADDITIONAL INFORMATION REGARDING THE
FOLLOWING BOXES.
26 0936 WALLBOX DIMMING SYSTEMS
26 2416 PANELBOARDS
26 053* RACEWAY AND PATHWAY
NORMAL BRANCH PANELBOARD
CONDUIT TURNED UP
(LIFE SAFETY / NEC 517) - (EMERGENCY/ NEC 700) BRANCH PANELBOARD
CONDUIT TURNED DOWN
26 2726 WIRING DEVICES
CAPPED CONDUIT
INDICATES MULTIPLE DEVICES INSTALLED UNDER COMMON COVERPLATE AT ONE LOCATION
CONDUIT STUBBED AND BUSHED INTO ACCESSIBLE CEILING CAVITY
SINGLE POLE SWITCH, 3'-8" AFF
26 0535 BOXES AND CABINETS
2
2-POLE SWITCH, 3'-8" AFF
TELECOMMUNICATIONS OUTLET WITH BACKBOX AND CONDUIT, 1'-6" AFF
3
3-WAY SWITCH, 3'-8"
TELECOMMUNICATIONS OUTLET WITH BACKBOX AND CONDUIT, 3'-8" AFF OR 6" ABOVE COUNTER
4
4-WAY SWITCH, 3'-8"
TELECOMMUNICATIONS OUTLET WITH BACKBOX AND CONDUIT, 5'-0" AFF
M
MOMENTARY CONTACT SWITCH, 3'-8" AFF
TELECOMMUNICATIONS OUTLET WITH BACKBOX AND CONDUIT, 8'-0" AFF OR 1'-0" BELOW CEILING
(WHICHEVER IS LOWER)
TELECOMMUNICATIONS OUTLET, INSTALLED IN FLOORBOX / DEVICE, WITH CONDUIT ROUGH-IN IN
SLAB TO ACCESSIBLE CEILING.
F
TELECOMMUNICATIONS OUTLET, INSTALLED IN FURNITURE RACEWAY, WITH CABLE EXTENDED
THROUGH ACTIVATION DEVICE.
B
DEVICE BOX WITH BLANK COVER PLATE, HEIGHT AS INDICATED ON DWG
J
JUNCTION BOX
PB
D
WALLBOX DIMMER (NOT FLUORESCENT) D=600W, D1=1000W, D2=1500W, 3'-8" AFF
F
WALLBOX DIMMER - FLUORESCENT, (3 OR 4 = MULTI LOCATION), 3'-8" AFF
S
SWITCH TO MATCH DIMMER DESIGN FOR GANGED INSTALLATION UNDER COMMON COVERPLATE
L
WALL BOX DIMMER - LED, (3 OR 4 = MULTI LOCATION), 3'-8" AFF
NEMA 5-20R SIMPLEX RECEPTACLE, 1'-6" AFF
NEMA 5-20R RED SIMPLEX RECEPTACLE, 1'-6" AFF
NEMA 5-20R DUPLEX RECEPTACLE, 1'-6" AFF
PULL BOX
NEMA 5-20R RED DUPLEX RECEPTACLE, 1'-6" AFF
CABINET, TOP OF TRIM 6'-2" AFF
X#
TWO (2) NEMA 5-20R DUPLEX RECEPTACLES INSTALLED UNDER COMMON COVERPLATE, 1'-6" AFF
TELECOMMUNICATIONS OUTLET WITH BACKBOX, AND INDICATED DEVICES. PROVIDE CONDUIT STUB
THROUGH FLOOR INTO MILLWORK/ FURNITURE TO MOUNT BOX.
TWO (2) NEMA 5-20R RED DUPLEX RECEPTACLES INSTALLED UNDER COMMON COVERPLATE, 1'-6" AFF
26 0575 CONDUIT ROUGH-IN SYSTEMS
PP
POWER ASSIST PUSH PLATE BACKBOX- MOUNTED 3'-8" AFF
PP1
POWER ASSIST PUSH PLATE BACKBOX- MULLION MOUNTED 3'-8" AFF
26 5100 INTERIOR LIGHTING
INDICATES PENDANT HUNG STYLE LUMINAIRE
TS
WALL BOX STYLE ELECTRONIC TIME SWITCH, 3'-8" AFF
DOWNLIGHT, ROUND OR SQUARE, RECESSED OR SURFACE (INC, CFL, LED, HID)
#
AUTOMATIC SENSING CONTROL DEVICE- REFER TO TABLE BELOW FOR DESCRIPTION
WALL WASH STYLE LUMINAIRE, ARROW INDICATES AIMING DIRECTION
INDICATES WALL MOUNT STYLE, 7'-6" AFF, UNO
LIGHTING TRACK WITH TRACK MOUNTED LUMINARIES
WALL BOX STYLE, LINE VOLTAGE, 3'-8" AFF
2 POLE, WALL BOX STYLE, LINE VOLTAGE, 3'-8" AFF
WALL/CEILING MOUNT, LOW VOLTAGE, WIDE VIEW
CEILING MOUNT, LOW VOLTAGE, WIDE VIEW
WALL/CEILING MOUNT, LOW VOLTAGE, NARROW, LONG RANGE VIEW
WALL MOUNT, EXTERIOR MOTION SENSING
CEILING MOUNT, LOW VOLTAGE, ULTRASONIC, WIDE VIEW
CEILING MOUNT, LOW VOLTAGE, ULTRASONIC, NARROW, LONG RANGE VIEW
CEILING MOUNT, HIGH BAY, LOW VOLTAGE
WALL BOX STYLE, PIR COMBINATION OCCUPANCY SENSOR/DIMMER
WALL BOX STYLE, LOW VOLTAGE, 3'-8" AFF
DS
DAYLIGHT SENSING (ON/OFF), CONTROL DEVICE, CEILING MOUNTED
DH
DAYLIGHT SENSOR FOR DAYLIGHT HARVESTING INTERFACE, CEILING MOUNTED
PC
LINE VOLTAGE, PHOTOELECTRIC CONTROL, 1'-0" ABOVE ROOF, AIMED NORTH
TC
TIME SWITCH, 5'-0" AFF
NC
NURSE CALL LIGHTING INTERFACE DEVICE
24 JUL 2015
Description
Date
(T) INDICATES WALL MOUNT STYLE LUMINAIRE
WALL BOX STYLE ELECTRONIC INTERVAL TIMER, 3'-8" AFF
=
=
=
=
=
=
=
=
=
=
=
SCHEMATIC DESIGN
GEOMETRIC SHAPE LUMINAIRE, RECESSED OR SURFACE
T
# = P
2P
P1
P2
P3
P4
P5
P6
P7
P8
P9
No.
FLUORESCENT STRIP LUMINAIRE
26 0923 AUTOMATIC LIGHTING CONTROL EQUIPMENT
A2
SELF CONTAINED BATTERY LIGHTING UNIT
A1
REMOTE LIGHTING LAMP HEAD(S)
BATT
LOW VOLTAGE CONTROL UNIT, RACK MOUNTED
LUMINAIRE CONNECTED TO LIFE SAFETY / NEC 517 EMERGENCY / NEC 700 BRANCH
B
LUMINAIRE CONNECTED TO CRITICAL / NEC 517 STANDBY / NEC 701 BRANCH
LUMINAIRE CONNECTED TO CRITICAL / NORMAL BRANCH
LUMINAIRE CONNECTED TO OPTIONAL / NEC 702 BRANCH
ELBD#
EMERGENCY LIGHTING BYPASS DEVICE - # INDICATES TYPE (TYPE 2 OR TYPE 3)
N
KEY PLAN
ILLUMINATED "EXIT" SIGNAGE
SINGLE LINE - SINGLE FACE(DIRECTION OF ARROWS AS INDICATED)
DOUBLE LINE - DOUBLE FACE(DIRECTION OF ARROWS AS INDICATED)
Drawing Title:
26 5600 EXTERIOR LIGHTING
26 0933 LOCAL DIMMING SYSTEMS
WIRE AND/OR CONDUIT RUN CONTINUED ON REFERENCED DETAIL
MATCH LINE REFERENCING CONTINUATION ON OTHER DRAWINGS
26 0578 MULTI-SERVICE BOXES AND RACEWAYS
X
FUTURE WORK
7/24/2015 4:28:09 PM
© Cannon Design 2015
All rights reserved. No part of this document may
be reproduced or utilized in any form, without prior
written authorization by The Cannon Corporation.
EXISTING WORK
A
AC
AFCI
AFF
AFG
AHJ
AHU
AIC
AL
AM
ANN
ANSI
ATS
AV
AWG
DRAWING NOTES AND DESIGNATIONS
X
'E' SERIES GENERAL NOTES
LUMINAIRE(S) AND POLE ASSEMBLY
PDC
PROGRAMMABLE DIMMING CONTROL STATION, 3'-8" AFF
BUILDING MOUNTED LUMINAIRE
PSC
PARTITIONED SPACE CONTROL STATION, 3'-8" AFF
BOLLARD STYLE LUMINAIRE
SDC
SCENE DIMMING CONTROL STATION, 3'-8" AFF
SURFACE AT GRADE OR FLUSH TO GRADE LUMINAIRE
DEC*
DIMMING EQUIPMENT CABINET, TOP OF BACKBOX 6'-2" AFF
LPC
LIGHTING PERSONAL COMPUTER, DESK TOP UNIT WITH WALL BOX RECEPTACLES AND CONNECTORS
INSTALLED 1'-6" AFF
#
SPEAKER STROBE, MIN 6'-8"/ MAX 8'-0" AFF (# INDICATES CANDELA)
FBC
FULL BRIGHTNESS CONTROL (PANIC) STATION, 3'-8" AFF
F
MANUAL PULL STATION, 3'-8" AFF
FS
FLUSH CEILING MOUNTED SPEAKERS
S
SMOKE DETECTOR, SURFACE CEILING MOUNTED
28 3100 FIRE ALARM SYSTEMS
DR
NOTES, LEGENDS,
SYMBOLS AND
ABBREVIATIONS
Project No.: 004815.00
Checked by: Checker
E0001
ELECTRO-MAGNETIC DOOR HOLDER
© Cannon Design 2015
KEYED NOTES
:
1.
EXISTING TO REMAIN THIS AREA UNLESS OTHERWISE NOTED. MAINTAIN CIRCUIT CONTINUITY TO
THIS AREA NOT AFFECTED BY RENOVATION.
22
23
24
Kx
22
21
Jx
Jx
VIRGINIA TECH
21
VIRGINIA TECH ATHLETIC
INTERIORS
P3
BRANCH CIRCUIT NOTES
Fx
Fx
LT1
LT1
:
3030 Clarendon Boulevard, Suite 500
Arlington, Virginia 22201
T: 703.907.2300
F: 703.907.2050
1.
EXTEND BRANCH CIRCUITS IN THIS AREA TO THE EXISTING BRANCH CIRCUITS IN
THIS AREA, UNLESS OTHERWISE NOTED:
120 / 208V PANELBOARDS
PG2 - NORMAL POWER
E1 - LIFE SAFETY POWER (NEC 517)
LT1
LT1
Kx
LT1
LT1
LT1
Ex
Ex
LT1
LT1
LT1
LT1
Jx
LT1
LT1
LT1
LT1
1
P2
LT1
PG2
LT1
LT1
TC
TC
Cx
Cx
TC
LT1
LT1
24
CORRIDOR
A56
LT1
Fx
LT1
LR1
P3
P3
LR1
23
-
SCHEMATIC DESIGN
No.
LR1
24 JUL 2015
Description
Date
Ex
LR1
22
CORRIDOR
A50
LR1
21gg
A1
21ff
LR1
21ee
21
LR1
LD1
Cx
LD1
LD1
LD1
LD1
21dd
LD1
N
LR1
KEY PLAN
21ee
AB
LR1
Drawing Title:
P2
21dd
BB
LR1
7/24/2015 4:28:10 PM
© Cannon Design 2015
All rights reserved. No part of this document may
be reproduced or utilized in any form, without prior
written authorization by The Cannon Corporation.
VESTIBULE
A49
1
LEVEL 01 LIGHTING PLAN - AREA A1
1/8" = 1'-0"
LEVEL 01 LIGHTING PLAN
- JAMERSON
Project No.: 004815.00
Checked by: Checker
1
E0101
© Cannon Design 2015
KEYED NOTES
24
23
:
1.
EXISTING TO REMAIN THIS AREA UNLESS OTHERWISE NOTED. MAINTAIN CIRCUIT CONTINUITY
TO THIS AREA NOT AFFECTED BY RENOVATION.
Kx
Kx
LT1
23
22
2.
ADDITIONAL LUMINAIRES STACKED VERTICALLY THIS AREA. SEE ARCHITECTURAL ELEVATION
SHEET A0603 FOR MORE INFORMATION.
LT1
CORRIDOR
B51
LT1
LT1
LT1
22
21
VIRGINIA TECH
LT1
LT1
LT1
P2
LT1
Jx
LT1
LT1
VIRGINIA TECH ATHLETIC
INTERIORS
Jx
LR1
LT1
BRANCH CIRCUIT NOTES
LT1
21
LR1
:
P2
CORRIDOR
B51
CORRIDOR
B52
3030 Clarendon Boulevard, Suite 500
Arlington, Virginia 22201
T: 703.907.2300
F: 703.907.2050
1.
EXTEND BRANCH CIRCUITS IN THIS AREA TO THE EXISTING BRANCH CIRCUITS IN THIS
AREA, UNLESS OTHERWISE NOTED:
LT1
LT1
120 / 208V PANELBOARDS
L2 - NORMAL POWER
E1 - LIFE SAFETY POWER (NEC 517)
LR1
LT1
LT1
2
Fx
Fx
LR1
LL1
P3
P3
LT1
2
LL1
LT1
LR1
LT1
Kx
2
LT1
LL1
LR1
LL1
LT1
2
LT1
LL1
LR1
2
Ex
Ex
LT1
LL1
LT1
LR1
P3
2
LT1
P3
LL1
LT1
LR1
2
Jx
LL1
LT1
LT1
LR1
2
P3
LT1
LR1
LT1
LL1
Cx
P2
L2
LT1
LR1
Cx
LT1
TC
2
LL1
P2
TC
TC
2
Fx
LT1
LR1
LL1
LT1
LL1
LR1
2
24
P2
LR1
CORRIDOR
B52
LL1
LR1
-
SCHEMATIC DESIGN
No.
24 JUL 2015
Description
Date
LL1
2
P3
LL1
LR1
23
P2
LR1
A2
Ex
LR1
22
CORRIDOR
P2
B57
LR1
21gg
N
21ff
KEY PLAN
21ee
21
Cx
21ee
AB
7/24/2015 4:28:11 PM
© Cannon Design 2015
All rights reserved. No part of this document may
be reproduced or utilized in any form, without prior
written authorization by The Cannon Corporation.
Drawing Title:
LEVEL 02 LIGHTING PLAN
- JAMERSON
Project No.: 004815.00
1
LEVEL 02 LIGHTING PLAN - AREA A2
1/8" = 1'-0"
1
Checked by: Checker
E0102
© Cannon Design 2015
KEYED NOTES
:
1.
EXISTING TO REMAIN THIS AREA UNLESS OTHERWISE NOTED. MAINTAIN CIRCUIT
CONTINUITY TO THIS AREA NOT AFFECTED BY RENOVATION.
2.
ADDITIONAL OVERHEAD LIGHTING SHOWN ON SHEET E0104.
3.
COORDINATE LOCATION OF REMOTE RIVERS IN ACCESSIBLE LOCATION.
4.
PROVIDE PRESET WALL STATION (LUTRON GRAFIK EYE 4000 OR EQUAL) COORDINATE
THE LOCATION WITH ARCHITECT.
P2
21gg
VIRGINIA TECH
21ff
21ee
LR1
LS1
LR1
A
21dd
B
D
VIRGINIA TECH ATHLETIC
INTERIORS
F
P2
BRANCH CIRCUIT NOTES
LR1
21ee
AB
:
LS1
3030 Clarendon Boulevard, Suite 500
Arlington, Virginia 22201
T: 703.907.2300
F: 703.907.2050
1.
EXTEND BRANCH CIRCUITS IN THIS AREA TO THE EXISTING BRANCH CIRCUITS IN THIS
AREA, UNLESS OTHERWISE NOTED:
LR1
21dd
BB
21x
21x
21cc
21x
EX
CORRIDOR
B31
120 / 208V PANELBOARDS
LA - NORMAL POWER (LOCATED IN MECH MEZZANINE A40)
277 / 480V PANELBOARDS
HA - NORMAL POWER (LOCATED IN MECH MEZZANINE A40)
EM - LIFE SAFETY POWER (NEC 517) (LOCATED IN MECH MEZZANINE A40)
LR1
LS1
1
18
LR1
21cc
CB
CONF. ROOM
228
18
18
21bb
3
LR3
LR1
LS1
21aa 15
15
LR1
15
LW2
3
21bb
DB
LS1
21z
LR1
12
21aa
EB
LS1 CORRIDOR
LR1
B30
LR3
OFFICE
226
LS2
EX
12
LR1
12
3
LS2
LR1
LR3
EXHIBIT HALL
2
222
21z
FB
LR1
LS1
P3
11
LS1
LR2
4
LS1
PD
C
7
7
7
3
LR3
-
6
6
6
3
SCHEMATIC DESIGN
No.
24 JUL 2015
Description
Date
LR3
ENTRY HALL
B28
2
4
LR2
LR2
LR2
VESTIBULE
B26
B
3
3
3
N
KEY PLAN
A
7/24/2015 4:44:14 PM
© Cannon Design 2015
All rights reserved. No part of this document may
be reproduced or utilized in any form, without prior
written authorization by The Cannon Corporation.
Drawing Title:
B
D
F
LEVEL 02 LIGHTING PLAN
- MERRYMAN
Project No.: 004815.00
1
LEVEL 02 LIGHTING PLAN - AREA B
1/8" = 1'-0"
Checked by: Checker
E0103
© Cannon Design 2015
KEYED NOTES
:
1.
EXISTING TO REMAIN THIS AREA UNLESS OTHERWISE NOTED. MAINTAIN CIRCUIT CONTINUITY
TO THIS AREA NOT AFFECTED BY RENOVATION.
21gg
21ff
21ee
A
21dd
B
VIRGINIA TECH
D
VIRGINIA TECH ATHLETIC
INTERIORS
21ee
AB
21x
21cc
21dd
BB
21x
BRANCH CIRCUIT NOTES
:
3030 Clarendon Boulevard, Suite 500
Arlington, Virginia 22201
T: 703.907.2300
F: 703.907.2050
LW1
LW1
1.
EXTEND BRANCH CIRCUITS IN THIS AREA TO THE EXISTING BRANCH CIRCUITS IN THIS
AREA, UNLESS OTHERWISE NOTED:
LW1
120 / 208V PANELBOARDS
LA - NORMAL POWER (LOCATED IN MECH MEZZANINE A40)
LW1
18
21cc
CB
18
21bb
277 / 480V PANELBOARDS
HA - NORMAL POWER (LOCATED IN MECH MEZZANINE A40)
EM - LIFE SAFETY POWER (NEC 517) (LOCATED IN MECH MEZZANINE A40)
LS2
LW1
LW1
LW1
LW1
21aa 15
15
21bb
DB
LS2
LW1
LW1
21z
LW1
LW1
12
21aa
EB
12
LS2
LW1
LW1
21z
FB
LW1
LW1
LS2
LS2
LS2
LS2
LW1
LW1
7
7
LS2
LS2
LW1
LW1
6
6
LS2
LS2
LW1
-
SCHEMATIC DESIGN
No.
24 JUL 2015
Description
Date
LW1
LS2
LW1
LS2
LW1
3
3
B
1
1
N
KEY PLAN
A
7/24/2015 4:28:13 PM
© Cannon Design 2015
All rights reserved. No part of this document may
be reproduced or utilized in any form, without prior
written authorization by The Cannon Corporation.
Drawing Title:
1
LEVEL 03 LIGHTING PLAN - AREA B
1/8" = 1'-0"
B
LEVEL 03 LIGHTING PLAN
- MERRYMAN
D
1
Project No.: 004815.00
Checked by: Checker
E0104
© Cannon Design 2015
KEYED NOTES
:
1.
INSTALL DEVICES INDICATED AT CASEWORK/MILLWORK AS PER ARCHITECTURAL
DETAILS.
2.
EXISTING TO REMAIN THIS AREA UNLESS OTHERWISE NOTED. MAINTAIN CIRCUIT
CONTINUITY TO THIS AREA NOT AFFECTED BY RENOVATION.
22
23
Kx
24
3.
AUTO DOOR - FURNISH AND INSTALL ALL CONDUITS, WIRING, OUTLET OR JUNCTION
BOXES, AND ANY OTHER AUXILIARY ELECTRICAL COMPONENTS NECESSARY FOR PROPER
DOOR OPERATION.
4.
PROVIDE EQUIPOTENIAL GROUNDING THIS AREA AS PER DETAILS FOR
CORRESPONDING SPACE DESCRIPTION.
5.
PROVIDE THREATMENT/DIAGNOSTIC EQUIPMENT RACEWAY ROUGHIN THIS ROOM
PER MANUFACTURER'S RECOMMENDATIONS.
22
21
Jx
6.
REFER TO LIGHTING DRAWING THIS AREA FOR SPLIT WIRED RECEPTACLE(S) SWITCH
LOCATION.
Jx
7.
FURNISH AND INSTALL ALL POWER AND SYSTEMS EQUIPMENT IN INDICATED ROOM
(S) TYPICAL TO REFERENCED LAYOUT(S) WITH NOTED MODIFICATIONS, IF ANY. CONNECT TO
INDICATED BRANCH CIRCUITS.
BRANCH CIRCUIT NOTES
21
VIRGINIA TECH
VIRGINIA TECH ATHLETIC
INTERIORS
:
1.
EXTEND BRANCH CIRCUITS IN THIS AREA TO THE EXISTING BRANCH CIRCUITS IN THIS
AREA, UNLESS OTHERWISE NOTED:
3030 Clarendon Boulevard, Suite 500
Arlington, Virginia 22201
T: 703.907.2300
F: 703.907.2050
120 / 208V PANELBOARDS
PG2 - NORMAL POWER
Fx
Fx
Kx
Ex
Ex
Jx
PG2
Cx
24
Fx
CORRIDOR
A56
SCHEMATIC DESIGN
No.
24 JUL 2015
Description
Date
23
A2
Ex
22
CORRIDOR
A50
A1
21gg
B
21ff
21ee
21
N
KEY PLAN
VESTIBULE
A49
1
W W
21dd
1
Drawing Title:
21ee
AB
LEVEL 01 POWER AND
SYSTEMS PLAN
21dd
BB
7/24/2015 4:28:13 PM
© Cannon Design 2015
All rights reserved. No part of this document may
be reproduced or utilized in any form, without prior
written authorization by The Cannon Corporation.
Cx
Project No.: 004815.00
1
LEVEL 01 POWER AND SYSTEMS PLAN - AREA A1 1
1/8" = 1'-0"
Checked by: Checker
E0201
© Cannon Design 2015
KEYED NOTES
24
23
1.
INSTALL DEVICES INDICATED AT CASEWORK/MILLWORK AS PER ARCHITECTURAL
DETAILS.
2.
EXISTING TO REMAIN THIS AREA UNLESS OTHERWISE NOTED. MAINTAIN CIRCUIT
CONTINUITY TO THIS AREA NOT AFFECTED BY RENOVATION.
Kx
Kx
3.
AUTO DOOR - FURNISH AND INSTALL ALL CONDUITS, WIRING, OUTLET OR JUNCTION
BOXES, AND ANY OTHER AUXILIARY ELECTRICAL COMPONENTS NECESSARY FOR PROPER
DOOR OPERATION.
23
22
:
4.
PROVIDE EQUIPOTENIAL GROUNDING THIS AREA AS PER DETAILS FOR
CORRESPONDING SPACE DESCRIPTION.
5.
PROVIDE THREATMENT/DIAGNOSTIC EQUIPMENT RACEWAY ROUGHIN THIS ROOM
PER MANUFACTURER'S RECOMMENDATIONS.
6.
REFER TO LIGHTING DRAWING THIS AREA FOR SPLIT WIRED RECEPTACLE(S) SWITCH
LOCATION.
VIRGINIA TECH
7.
FURNISH AND INSTALL ALL POWER AND SYSTEMS EQUIPMENT IN INDICATED ROOM
(S) TYPICAL TO REFERENCED LAYOUT(S) WITH NOTED MODIFICATIONS, IF ANY. CONNECT TO
INDICATED BRANCH CIRCUITS.
22
Jx
21
Jx
BRANCH CIRCUIT NOTES
:
VIRGINIA TECH ATHLETIC
INTERIORS
1.
EXTEND BRANCH CIRCUITS IN THIS AREA TO THE EXISTING BRANCH CIRCUITS IN THIS
AREA, UNLESS OTHERWISE NOTED:
21
120 / 208V PANELBOARDS
L1 - NORMAL POWER
3030 Clarendon Boulevard, Suite 500
Arlington, Virginia 22201
T: 703.907.2300
F: 703.907.2050
Fx
Fx
Kx
Ex
Ex
Jx
24
DR
L2
W
W
Cx
Fx
1
SCHEMATIC DESIGN
No.
24 JUL 2015
Description
Date
23
A2
Ex
A1
22
B
21gg
N
21ff
21
KEY PLAN
21ee
Cx
21ee
AB
7/24/2015 4:28:14 PM
© Cannon Design 2015
All rights reserved. No part of this document may
be reproduced or utilized in any form, without prior
written authorization by The Cannon Corporation.
Drawing Title:
LEVEL 02 POWER AND
SYSTEMS PLAN
Project No.: 004815.00
1
LEVEL 02 POWER AND SYSTEMS PLAN - AREA A2
1/8" = 1'-0"
1
Checked by: Checker
E0202
© Cannon Design 2015
KEYED NOTES
1.
INSTALL DEVICES INDICATED AT CASEWORK/MILLWORK AS PER ARCHITECTURAL
DETAILS.
75
EX
CORRIDOR
B57
:
DR
2.
EXISTING TO REMAIN THIS AREA UNLESS OTHERWISE NOTED. MAINTAIN CIRCUIT
CONTINUITY TO THIS AREA NOT AFFECTED BY RENOVATION.
DR
3.
AUTO DOOR - FURNISH AND INSTALL ALL CONDUITS, WIRING, OUTLET OR JUNCTION
BOXES, AND ANY OTHER AUXILIARY ELECTRICAL COMPONENTS NECESSARY FOR PROPER
DOOR OPERATION.
F
21ee
4.
PROVIDE EQUIPOTENIAL GROUNDING THIS AREA AS PER DETAILS FOR
CORRESPONDING SPACE DESCRIPTION.
A
21dd
B
D
6.
REFER TO LIGHTING DRAWING THIS AREA FOR SPLIT WIRED RECEPTACLE(S) SWITCH
LOCATION.
7.
FURNISH AND INSTALL ALL POWER AND SYSTEMS EQUIPMENT IN INDICATED ROOM
(S) TYPICAL TO REFERENCED LAYOUT(S) WITH NOTED MODIFICATIONS, IF ANY. CONNECT TO
INDICATED BRANCH CIRCUITS.
1
AB
BB
21x
21cc
CORRIDOR
B31
VIRGINIA TECH
5.
PROVIDE THREATMENT/DIAGNOSTIC EQUIPMENT RACEWAY ROUGHIN THIS ROOM
PER MANUFACTURER'S RECOMMENDATIONS.
21x
BRANCH CIRCUIT NOTES
VIRGINIA TECH ATHLETIC
INTERIORS
:
3030 Clarendon Boulevard, Suite 500
Arlington, Virginia 22201
T: 703.907.2300
F: 703.907.2050
1.
EXTEND BRANCH CIRCUITS IN THIS AREA TO THE EXISTING BRANCH CIRCUITS IN THIS
AREA, UNLESS OTHERWISE NOTED:
120 / 208V PANELBOARDS
LA - NORMAL POWER (LOCATED IN MECH MEZZANINE A40)
75
EX
18
CB
EX
CONF. ROOM
228
21bb
18
277 / 480V PANELBOARDS
HA - NORMAL POWER (LOCATED IN MECH MEZZANINE A40)
EM - LIFE SAFETY POWER (NEC 517) (LOCATED IN MECH MEZZANINE A40)
1
1
1
1
DN
EX
1
DR
21aa 15
15
DB
DR
CLOSET
226A
21z
12
EB
12
F
1
F
CORRIDOR
B30
1
1
OFFICE
226
EXHIBIT HALL
222
FB
1
75
EX
1
75
EX
EX
7
7
1
1
6
6
SCHEMATIC DESIGN
No.
24 JUL 2015
Description
Date
ENTRY HALL
B28
1
75
EX
A2
VESTIBULE
B26
EX
EX
A1
F
3
3
B
1
1
1
N
KEY PLAN
EXTERIOR SIGNAGE
A
7/24/2015 4:28:14 PM
© Cannon Design 2015
All rights reserved. No part of this document may
be reproduced or utilized in any form, without prior
written authorization by The Cannon Corporation.
Drawing Title:
1
LEVEL 02 POWER AND SYSTEMS PLAN - AREA B
1/8" = 1'-0"
B
D
LEVEL 02 POWER AND
SYSTEMS PLAN
1
Project No.: 004815.00
Checked by: Checker
E0203
© Cannon Design 2015
LUMINAIRE SCHEDULE
TAG
LD1
DESCRIPTION
INSTALLATION
DEPTH
METHOD
3" ROUND ADUSTIBLE
DOWNLIGHT
RECESSED
DW
5-1/2
LIGHT SOURCE
BALLAST/DRIVER
SPEC
VOLT
INPUT
WATTS
MIN. EFF.
660LM
0-10V
120V
17
38LM/W
LED
DIMMING
SPEC
QTY
SHIELDING/OPTICS
FEATURES/OPTIONS
NARROW FLOOD OPTICS, SEMI DIFFUSE
REFLECTOR
LOCKABLE 40 DEGREE MAXIMUM TILT
REFERENCED PRODUCTS
AMERLUX - E2.9RA-G2-HP-17-LED-120-NF-GB-3500-0-10V/E2.9RA-G2-HP-SDC
NOTES
VIRGINIA TECH ATHLETIC
INTERIORS
3500K
85+ CRI
LL1
LINEAR LED
SURFACE
230LM/FT
REMOTE
LED
0-10V
3500K
DIMMING
120V
2.8W/FT
FROSTED LENS
EXTRUDED ALUMINUM 45 DEGREE
MOUNTING CHANNEL, ALUMINUM
FINISH. PROVIDE MOUNTING CLIPS,
JUMPER CABLES AND DRIVERS AS
REQUIRED
90+ CRI
LR1
4" LINEAR LED
RECESSED
DW
4-3/4"
400 LM/FT
0-10v
LED
DIMMING
RECESSED
DW
3'5/8"
400 LM/FT
0-10v
LED
DIMMING
122LM/W
SPOTLESS ACRYLIC REGRESSED LENS
EXTRUDED ALUMINUM HOUSING,
CONTINUOUS LENGTHS PER PLANS, LED
BOARD CONFIGURATION PROVIDE EVEN
LENS ILLUMINATION FOR HOUSINGS IN
1" INCRIMENTS.
AXIS - BBRLED-B3-MF-400-35-SO-RG-S#-W-UNIV-D-1-DF
1,2,4
UNIV
3.6W/FT
111LM/W
SPOTLESS ACRYLIC FLUSH LENS
EXTRUDED ALUMINUM HOUSING,
CONTINUOUS LENGTHS PER PLANS, LED
BOARD CONFIGURATION PROVIDE EVEN
LENS ILLUMINATION FOR HOUSINGS IN
1" INCRIMENTS.
AXIS - BRLED-B3-MF-400-35-SO-S#-W-UNIV-D-1-DF
1,2,4
12/277
3W/FT
94LM/FT
FROSTED POLYCARBONATE LENS
EXTRUDED ALUMINUM CHANNEL WITH
EXTRUDED ALUMINUM HOUSING,
JUMPER CABLES AND DRIVERS AS
REQUIRED
KLUS - K-35-1220 / B5553-HS22 FROSTED / B6638
1,2,4
UNIV
3.3W/FT
122LM/FT
SPOTLESS ACRYLIC FLUSH LENS
EXTRUDED ALUMINUM HOUSING,
CONTINUOUS LENGTHS PER PLANS, LED
BOARD CONFIGURATION PROVIDE EVEN
LENS ILLUMINATION FOR HOUSINGS IN
1" INCRIMENTS, WHITE FINISH
AXIS - BBSLED-B3-MF-400-35-SO-S#-W-UNV-D-1-S
2,4
277
8.5W/FT
30X60 DEGREE OPTICS
LENGTHS PER PLANS, SLIM ADJUSTIBLE
MOUNTING, SILVER SAND FINISH
LUMENPULSE - LOGi-277-LENGTH-35K-30X60-SAM-SI-DIM
2,4
UNIV
28W
78LM/W
FLUSH FORMED FROSTED ACRYLIC
DIFFUSER
STEEL HOUSING, WHITE FINISH
FOCAL POINT - FNVL-22-ACZ-LL1-35K-1C-UNV-LD1
1,2
UNIV
107W
93LM/W
ASYMETRIC FORWARD THROW
DISTRIBUTION, CLEAR LENS
EXTRUDED ALUMINUM HOUSING,
DIECAST ENDCAPS WITH STAINLESS
STEEL HARDWARE, BLACK
POWDERCOAT FINISH
WINONA - WLAWC803-YM1A-INT-24LONG-AL1A3-35-MVOLT-CA-SGB
2
277
5W/FT
110
FROSTED ACRYLIC LENS
EXTRUDED ALUMINUM HOUSING,
MACHINED ENDCAPS, SATIN ANODIZE
FINISH
BARTCO - BSS210-23-35-5-SM-SIN-SA
2
3500K
80+ CRI
LR3
1" LINEAR LED
RECESSED
DW
1.12"
284LM/FT
0-10V
LED
DIMMING
2,3,4
3.3W/FT
3500K
2" LINEAR LED
AION - 4924-35-LE / AT845
UNIV
80+ CRI
LR2
VIRGINIA TECH
1,2
3500K
3030 Clarendon Boulevard, Suite 500
Arlington, Virginia 22201
T: 703.907.2300
F: 703.907.2050
80+ CRI
LS1
4" LINEAR LED
SURFACE
5-1/2"
400 LM/FT
0-10v
LED
DIMMING
3500K
80+ CRI
LS2
LED LINEAR GRAZE
SURFACE
REMOTE
LED
0-10V
3500K
DIMMING
80+ CRI
LT1
2X2 LED TROFFER
RECESSED LG
2200LM
0-10V
LED
DIMMING
3500K
80+ CRI
LW1
LED UPLIGHT
SURFACE
WALL
10,023 LM
0-10V
LED
DIMMING
3500K
80+CRI
LW2
LED LINEAR STRIP
SURFACE
WALL
550LM/FT
LED
INTEGRAL
ELECTRONIC
3500K
80+CRI
SCHEMATIC DESIGN
No.
24 JUL 2015
Description
Date
GENERAL NOTES:
A
REFERENCED PRODUCTS ARE INCLUDED HEREIN, OF MANUFACTURERS & PRODUCTS, THAT GENERALLY CONFORM TO THE LUMINAIRE DESIGN INTENTS ESTABLISHED HEREIN, & IN THE PROJECT MANUAL. EQUIVALENT
PRODUCTS BY OTHER MANUFACTURERS MAY BE CONSIDERED, PRIOR TO BID.
B
C
DETERMINE SPECIFIC LUMINAIRE PART NUMBERS BASED ON THE REFERENCED PRODUCT SERIES, WRITTEN DESCRIPTIONS & PROJECT MANUAL SPECIFICATIONS.
INCLUSION HEREIN OF MANUFACTURER'S SERIES &/OR MODEL NUMBERS DOES NOT IMPLY UNCONDITIONAL PRODUCT APPROVAL - MANUFACTURER'S STANDARD PRODUCTS MAY REQUIRE CUSTOM MODIFICATIONS
TO MEET THE REQUIREMENTS SPECIFIED HEREIN & IN THE PROJECT MANUAL.
D
LISTED SIZES, LAMPING, & TYPES OF LUMINAIRES MAY NOT BE STANDARD PRODUCTS PRODUCED FROM ANY GIVEN MANUFACTURER OR SERIES LISTED. MANUFACTURER'S STANDARD PRODUCTS MAY REQUIRE CUSTOM
MODIFICATIONS TO MEET THE DESIGN CRITERIA, DESCRIPTIONS, & REQUIREMENTS SPECIFIED HEREIN & IN THE PROJECT MANUAL.
E
ALERT ARCHITECT TO DISCREPANCIES PRIOR TO BID.
ABBREVIATIONS:
CONC
CONCRETE
EXP
EXPOSED
LM/W
LUMENS PER WATT
DW
DRYWALL
LG
LAY-IN GRID
NT
D/I
DIRECT/INDIRECT
LO-IRI
LOW IRRIDESCENT
PAF
PPC
POLYESTER POWDER COAT FINISH
S'SPEC
NARROW TEE GRID
P-RS
PENDANT - RIGID STEM
SS
STAINLESS STEEL
PAINT AFTER FABRICATION
REFL'T
REFLECTOR/REFLECTANCE
TBS
TO BE SELECTED BY ARCH
SEMI-SPECULAR
EFF
EFFICIENCY/EFFICACY/LM/W
LM
LUMENS
P-AC
PENDANT - AIRCRAFT CABLE
SP
SPLINE CEILING SYSTEM
UNIV
UNIVERSAL 120-277VAC
ELBD
EMERG. LTG. BYPASS DEVICE
LM/FT
LUMENS PER LINEAR FOOT
PL
PLASTER
SPEC
SPECULAR
WH
WHITE
NOTES:
1 COORDINATE MOUNTING/FLANGE CONDITION WITH REFLECTED CEILING PLAN /ARCHITECT PRIOR TO ORDERING AND INSTALLATION
2
PROVIDE BALLASTS/ DRIVERS TO ACCOMMODATE SWITCHING/CONTROL SHOWN ON PLAN
3
REFER TO ARCHITECTURAL CEILING PLANS/DETAILS FOR MORE INFORMATION
4
LUMINAIRE TO RUN CONTINUOUSLY. COORDINATE AND PROVIDE NECESSARY CONNECTORS, ENDCAPS AND APPURTENANCES TO ENABLE CLEAN ONTINUOUS LINES OF LIGHT
N
KEY PLAN
1
LUMINAIRE SCHEDULE
LUMINAIRE SCHEDULE
7/24/2015 4:44:15 PM
© Cannon Design 2015
All rights reserved. No part of this document may
be reproduced or utilized in any form, without prior
written authorization by The Cannon Corporation.
Drawing Title:
Project No.: 004815.00
Checked by: Checker
E0601
© Cannon Design 2015