ADDENDUM #2 April 19, 2016 UNIVERSITY OF CENTRAL OKLAHOMA MURDAUGH HALL RENOVATION FRANKFURT+SHORT+BRUZA, ASSOC., P.C. ARCHITECTS-ENGINEERS-PLANNERS OKLAHOMA CITY, OKLAHOMA Items in this Addendum take precedence over the original documents. Items not specifically revised remain in effect. GENERAL RESPONSE TO BIDDER QUESTIONS Item 2-1 Question: The main switchboard MSB one-line does not indicate a requirement for digital metering or the requirement for an SPD. However, Section 262413 has paragraphs detailing the specifications of these items, but does not necessarily specify that these items are required. Since, both are typically seen on projects of this nature, can you confirm if a Digital Meter and/or if an SPD is required in MSB? Answer: Yes the digital metering and surge protection equipment (SPD) are required. That is why they are in the specifications. Item 2-2 Question: Does the Chair Rail in the Dorm Rooms only happen on the wall with the mirror and vanity? Answer: No, on both walls. Item 2-3 Question: On one detail the wood species says Oak and another it says Birch. Is there a preference to wood species? Answer: Wood species is Oak. Item 2-4 Question: There is only base at the portal spots of the corridors correct? I do not see it anywhere else. What kind of detail is this do you know? Answer: Yes, only at portals, terrazzo base is typical. GC to submit on base profiles for approval. Item 2-5 Question: Is the base going to be stained like the crown molding and chair rail to match existing? Answer: Yes REFERENCE THE SPECIFICATIONS Item 2-6 Reference Section 283111 -The fire alarm system and its products specified in specification section shall be provided by Simplex-Grinnell. REFERENCE THE GENERAL DRAWINGS Item 2-7 G-002 Sheet Index changes Item 2-8 G-003, G-004, G-005, & G-006 Fire extinguisher legend changes Item 2-9 General Drawing –CU101 changed location of fireline tie-in and added storm well drain details and other items. Item 2-10 C501 Added sheet Item 2-11 A102- added rustification joints and chamfer joints at ramp wall. Item 2-12 AD102 change note 2, 6 &14. Added note 17 A2-1 ADDENDUM #2 April 19, 2016 UNIVERSITY OF CENTRAL OKLAHOMA MURDAUGH HALL RENOVATION FRANKFURT+SHORT+BRUZA, ASSOC., P.C. ARCHITECTS-ENGINEERS-PLANNERS OKLAHOMA CITY, OKLAHOMA Item 2-13 AD103 & AD104- corrected note 3 to say plaster veneer. Added to note 13 to include demo of jamb wall. Added note 14. Item 2-14 AD105 – Corrected existing partition condition Item 2-15 AD106- added note 11 Item 2-16 AD107 & AD108 revise note 7 & add note 8. Item 2-17 AE103 note 2 changed. Also adding new handrail to ramp area. Item 2-18 AE104 & AE105 & AE 106 change note 7, 11, 12 Item 2-19 AE108 change note 7 and reduced size of furr-down Item 2-20 AE109 change note 2 Item 2-21 AE110 change note 2 & 3 Item 2-22 AE112 change note 9 Item 2-23 AE113 Parasquare note finish and access door to be lockable Item 2-24 AE114 Lounge ceiling removed some exit signs Item 2-25 P-001 add P-5 to Plumbing Schedule Item 2-26 P-101 add note to Restroom 008 & 009 Item 2-27 P-103 & P-104 Add janitor sink to center janitor closet Item 2-28 P-401 Add janitor sink to 100E Item 2-29 EL100, EL101, EL102, EL103, Add note 10 to exterior lights Item 2-30 EL501 Add LC1 Diagram, Light Schedule, Lighting control notes Item 2-31 EP100 change General note A, and power to FCU-020 Item 2-32 EP101 change note 12, and add outlet by existing plaza stairs Item 2-33 EP102 & EP103 change note 6 Item 2-34 EP702 & EP703 change panel schedule ATTACHMENTS A2-2 ADDENDUM #2 April 19, 2016 UNIVERSITY OF CENTRAL OKLAHOMA MURDAUGH HALL RENOVATION FRANKFURT+SHORT+BRUZA, ASSOC., P.C. ARCHITECTS-ENGINEERS-PLANNERS OKLAHOMA CITY, OKLAHOMA 1) Addendum #2 set of drawing modifications End of Addendum #2 A2-3 University of Centeral Oklahoma Murdaugh Hall Renovation Edmond, Oklahoma SITE LOCATION VICINITY MAP - UCO CAMPUS Telephone 405. 840. 2931 Facsimile 405. 842. 7750 www.fsb-ae.com D A RCH IT OKLAHOMA CERTIFICATE OF AUTHORIZATION ARCHITECTURE: # 00199 EXP. 06/30/17 OK P L A HO MA OKLAHOMA CERTIFICATE OF AUTHORIZATION P.E: # 1072 EXP. 06/30/16 L IC E N S E D P L IC E N S E D T EC SE F E S S I O NA RUSSELL FRANK KETNER 15891 OK L A HO MA G IN E E R 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 GARY W. JAMES 16166 RO EN Architects Engineers Planners F E S S IO NA G IN E E R Frankfurt Short Bruza RO EN L IC EN A PHILIP G. McNAYR 2134 H OM STA O F O K LA L E L T ADDENDUM #002 - OWNER COMMENTS APRIL 18, 2016 HM HORIZ HT HVAC HOLLOW METAL HORIZONTAL HEIGHT HEATING, VENTILATING, & AIR CONDITIONING ID INSUL INT INSIDE DIAMETER INSULATE (OR) INSULATION INTERIOR JAN JANITOR K NOT USED NA NIC NOM NRC NTS NOT APPLICABLE NOT IN CONTRACT NOMINAL NOISE REDUCTION COEFFICIENT NOT TO SCALE OA OC OD OFCI OPH ORD OVHD OVERALL ON CENTER OUTSIDE DIAMETER OWNER FURNISHED CONTRACTOR INSTALLED OWNER FURNISHED OWNER INSTALLED OPPOSITE HAND OVERFLOW ROOF DRAIN OVERHEAD PLAM PLBG PLYWD PR PRCST PREFAB PT PVC PLASTIC LAMINATE PLUMBING PLYWOOD PAIR PRECAST PREFABRICATED PAINT (INTERIOR) POLYVINYL CHLORIDE QTF QTB QTY QUARRY TILE FLOOR QUARRY TILE BASE QUANTITY OFOI SECT SF SHTHG SIM SPEC SST STC STD STL STRUCT SECTION SQUARE FOOT SHEATHING SIMILAR SPECIFICATION(S) STAINLESS STEEL SOUND TRANSMISSION CLASSIFICATION STANDARD STEEL STRUCTURAL (OR) STRUCTURE T T&B TBD TD TO TOC TOJ TOM TOS TYP TREAD TOP AND BOTTOM TO BE DETERMINED TOWEL DISPENSER TOP OF TOP OF CONCRETE TOP OF JOIST TOP OF MASONRY TOP OF STEEL TYPICAL UNO UNLESS NOTED OTHERWISE VB VCT VERT VTR VWC VINYL BASE VINYL COMPOSITION TILE VERTICAL VENT THROUGH ROOF VINYL WALL COVERING W/ W/O WC WD WH WITH WITHOUT WATER CLOSET WOOD WALL HYDRANT (OR) WATER HEATER XFMR TRANSFORMER Y NOT USED Z NOT USED SHEET NUMBER GENERAL G-001 G-002 1 1 1 1 1 C ARCHITECTURAL ANNOTATION SYMBOLS LEGEND 1 DISCIPLINE TYPE (ARCHITECTURE SHOWN) DISCIPLINE MODIFIER (ELEMENTS SHOWN) DRAWING TYPE (PLAN, ELEVATION, ETC., SERIES NUMBER GROUND FLOOR PLAN D3 SCALE:1/8"=1'-0" 0 4' 8' 16' 0 4' 8' 16' PLAN DRAWING TITLE A - 101 DRAWING TYPES LEGEND 1 - PLANS (HORIZONTAL VIEWS) 2 - ELEVATIONS (VERTICAL VIEWS) 3 - SECTIONS (SECTIONAL VIEWS) 4 - ENLARGED VIEWS (PLANS, ELEVATIONS OR SECTIONS THAT ARE NOT DETAIL VIEWS) 5 - DETAILS 6 - SCHEDULES & DIAGRAMS Top Text Bottom Text ELEVATION DATUM SYMBOL INDICATES DATUM ELEVATION AS INDICATED D3 WALL SECTION CALLOUT ARROW INDICATE WALL SECTION ON SHEET INDICATED SCALE:1/8"=1'-0" ALL OTHER DRAWING TITLES 1 A301 1 A301 1 A302 BUILDING SECTION BUILDING SECTION CALLOUT ARROWS INDICATE BUILDING SECTION ON SHEET INDICATED TITLE COVER SHEET SHEET INDEX, ANNOTATION SYMBOLS, AND TYPICAL PLAN DIMENSIONS CODE COMPLIANCE PLAN - BASEMENT CODE COMPLIANCE PLAN - FIRST FLOOR CODE COMPLIANCE PLAN - SECOND FLOOR CODE COMPLIANCE PLAN - THIRD FLOOR PARTITION TYPES & DETAILS DOOR & HARDWARE SCHEDULES G-003 G-004 G-005 G-006 G-007 G-008 CIVIL C-001 GENERAL NOTES, LEGEND AND ABBREVIATIONS V-101 ORIGINAL SURVEY CD101 DEMOLITION PLAN CS101 SITE PLAN CG101 GRADING PLAN CG201 EROSION CONTROL PLAN CU101 UTILITY PLAN C-501 CIVIL DETAILS ARCHITECTURAL A-100 SITE PLAN A-101 ENLARGED SITE PLANS AND SECTIONS A-102 RAMP SECTIONS AND DETAILS AD101 DEMOLITION BASEMENT FLOOR PLAN AD102 DEMOLITION FIRST FLOOR PLAN AD103 DEMOLITION SECOND FLOOR PLAN AD104 DEMOLITION THIRD FLOOR PLAN AD105 DEMOLITION BASEMENT CEILING PLAN AD106 DEMOLITION FIRST FLOOR CEILING PLAN AD107 DEMOLITION SECOND FLOOR CEILING PLAN AD108 DEMOLITION THIRD FLOOR CEILING PLAN AE103 BASEMENT FLOOR PLAN AE104 FIRST FLOOR PLAN AE105 SECOND FLOOR PLAN AE106 THIRD FLOOR PLAN AE107 ATTIC FLOOR PLAN AE108 FIRST FLOOR - NEW CEILING PLAN AE109 SECOND FLOOR - NEW CEILING PLAN AE110 THIRD FLOOR - NEW CEILING PLAN AE111 ENLARGED CEILING PLANS AE112 INTERIOR ELEVATIONS, SECTIONS & DETAILS AE113 INTERIOR SECTIONS & DETAILS AE114 ADD ALTERNATE - LOBBY FLOOR FINISHES, LOBBY PENDANTS AND TOILET & SHOWER PARTITIONS AE115 TYPICAL INTERIOR FINISH PLAN FIRE PROTECTION F-001 FIRE PROTECTION LEGEND, ABBREVIATIONS, AND PIPING SCHEMATIC F-100 BASEMENT FIRE PROTECTION PLAN F-101 FIRST FLOOR FIRE PROTECTION PLAN F-102 SECOND FLOOR FIRE PROTECTION PLAN F-103 THIRD FLOOR FIRE PROTECTION PLAN F-104 ATTIC FIRE PROTECTION PLAN F-401 FIRE SUPPRESSION FIRE PUMP AND BUILDING SUPPRESSION SYSTEM RISER SECTIONS F-402 DORM ROOM ENLARGED PLAN - EAST WING, DORM ROOM AND HALLWAY SECTION, AND SPRINKLER SYSTEM RISER SECTION. F-601 FIRE ALARM & EMERGENCY COMMUNICATIONS INPUT/OUTPUT MATRIX F-602 FIRE ALARM RISER DIAGRAM SHEET INDEX SHEET NUMBER PLUMBING P-001 P-100 P-101 P-102 P-103 P-104 P-105 P-401 P-601 MECHANICAL M-001 M-100 M-101 M-102 M-103 M-104 M-301 M-401 M-402 M-403 M-501 M-601 M-602 M-603 M-604 M-605 M-701 M-702 M-703 M-801 ELECTRICAL E-001 EP100 EP101 EP102 EP103 EP104 EP401 EP501 EP701 EP702 EP703 EP704 EP705 EP706 EP707 EL100 EL101 EL102 EL103 EL501 ET101 ET102 ET103 Frankfurt Short Bruza TITLE Architects Engineers Planners LEGEND & ABBREVIATIONS 1 UNDERFLOOR PLUMBING PLAN BASEMENT PLUMBING PLAN FIRST FLOOR PLUMBING PLAN SECOND FLOOR PLUMBING PLAN THIRD FLOOR PLUMBING PLAN ATTIC PLUMBING PLAN 1 ENLARGED PLUMBING PLAN FLOW DIAGRAMS 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com 1 D LEGEND & ABBREVIATIONS BASEMENT MECHANICAL PLAN FIRST FLOOR MECHANICAL PLAN SECOND FLOOR MECHANICAL PLAN THIRD FLOOR MECHANICAL PLAN ATTIC MECHANICAL PLAN SECTIONS ENLARGED PLANS FIRST FLOOR ENLARGED PLAN ENLARGED MECHANICAL ROOM PLAN DETAILS FLOW DIAGRAMS FLOW DIAGRAMS FLOW DIAGRAMS FLOW DIAGRAMS FLOW DIAGRAMS SCHEDULES SCHEDULES SCHEDULES CONTROL DIAGRAMS 1 A401 DETAIL CALLOUT ENLARGED PLAN OR DETAIL ON SHEET INDICATED REVISION SYMBOL REFER TO SHEET BORDER FOR REVISION HISTORY LEGEND, ABBREVIATIONS & MOUNTING HEIGHT DETAIL BASEMENT ELECTRICAL MASTER PLAN 1 FIRST FLOOR ELECTRICAL PLAN SECOND FLOOR ELECTRICAL PLAN THIRD FLOOR ELECTRICAL PLAN ATTIC ELECTRICAL PLAN ENLARGED ELECTRICAL PLANS ELECTRICAL RISER DIAGRAM PANEL SCHEDULES PANEL SCHEDULES 1 PANEL SCHEDULES PANEL SCHEDULES PANEL SCHEDULES PANEL SCHEDULES PANEL SCHEDULES BASEMENT LIGHTING PLAN FIRST FLOOR LIGHTING PLAN 1 SECOND FLOOR LIGHTING PLAN THIRD FLOOR LIGHTING PLAN LIGHT FIXTURE SCHEDULE & LIGHTING CONTROL DIAGRAM FIRST FLOOR TELECOMMUNICATION PLAN SECOND FLOOR TELECOMMUNICATION PLAN THIRD FLOOR TELECOMMUNICATION PLAN C A STRUCTURAL GRIDS AS INDICATED ON DRAWINGS B B BUILDING DATA BUILDING CODES AND STANDARDS INTERNATIONAL EXISTING BUILDING CODE 2009 (IEBC) LEVEL 2 ALTERATION (CHAPTER 7) - NO CHANGE IN OCCUPANCY - AREA OF ALTERATION UNDER IBC INTERNATIONAL BUILDING CODE 2009 (IBC) INTERNATIONAL MECHANICAL CODE 2009 INTERNATIONAL PLUMBING CODE 2009 NATIONAL ELECTRIC CODE 2011 LIFE SAFETY CODE, NFPA 101 ICC/ANSI A117.1 2009 / ADAAG 2010 4/18/2016 7:21:48 PM O F O K LA H PHILIP G. McNAYR 2134 EN 1 1 E T GAGE GALVANIZED GRAB BAR GENERAL CONTRACTOR GUARD RAIL GENERAL GLASS GRADE GYPSUM BOARD MATERIAL MAXIMUM MECHANICAL MANUFACTURER MINIMUM MIRROR MISCELLANEOUS MASONRY OPENING MOUNTED METAL SHEET INDEX RADIUS (OR) RISER RESILIENT BASE ROOF DRAIN RECESSED REFERENCE (OR) REFRIGERATOR REQUIRED REVISION RESILIENT FLOORING ROOM ROUGH OPENING SE D A RCH IT Edmond, Oklahoma DBL DOUBLE DEG DEGREE DEMO DEMOLITION DEPT DEPARTMENT DF DRINKING FOUNTAIN DIA DIAMETER DIAG DIAGONAL DIM DIMENSION DISP DISPENSER DN DOWN DR DOOR DS DOWNSPOUT DET DETAIL DNG DRAWING GA GALV GB GC GDR GEN GL GRD GYP BD MATL MAX MECH MFR MIN MIRR MISC MO MTD MTL R RB RD REC REF REQD REV RF RM RO EC CABINET COLD-FORMED METAL FRAMING CORNER GUARD CONTROL JOINT CENTER LINE CEILING CLEAR CONCRETE MASONRY UNIT COLUMN CONCRETE CONTINUOUS CORRIDOR CARPET CERAMIC TILE BASE CERAMIC WALL TILE CENTER FLOOR DRAIN FIRE EXTINGUISHER FINISH FLOOR ELEVATION FINISHED GRADE FLOOR FLUORESCENT FOOT (OR) FEET FURRING LAMINATE LAVATORY LINEAR LOCATION LIGHTING LOUVER A CAB CFMF CG CJ CL CLG CLR CMU COL CONC CONT CORR CPT CTB CWT CTR FD FE FF EL FG FLR FLUOR FT FURG LAM LAV LIN LOC LTG LVR C BOTTOM OF BOTTOM BEARING BOTH SIDES BETWEEN EJ EL ELEC ELEV EQ EQUIP EW EXIST EXT EACH EXTERIOR INSULATION & FINISH SYSTEM EXPANSION JOINT ELEVATION ELECTRIC (OR) ELECTRICAL ELEVATOR EQUAL EQUIPMENT EACH WAY EXISTING EXTERIOR LI BO BOT BRG BS BTWN EA EIFS OM D ACOUSTICAL CEILING TILE AMERICANS WITH DISABILITIES ACT ADA ACCESSIBILITY GUIDELINES ABOVE FINISH FLOOR AIR HANDLING UNIT ALIGN ALTERNATE ALUMINUM AMERICAN NATIONAL STANDARDS INSTITUTE University of Central Oklahoma Murdaugh Hall Renovation ARCHITECTURAL ABBREVIATIONS ACT ADA ADAAG AFF AHU AL ALT ALUM ANSI 5 4 T 3 2 STA 1 REVISION HISTORY: BUILDING AREA MURDAUGH HALL EXISTING AFTER REMODEL BASEMENT 25,902 SF - FIRST FLOOR 18,716 SF - SECOND FLOOR 17,407 SF - THIRD FLOOR 17,407 SF - ATTIC 17,407 SF - 1 C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt FIRE RESISTANCE RATED CONSTRUCTION A ADDENDUM 002 04/18/16 DESCRIPTION DATE PROJECT INFORMATION: DESIGNED BY: BUILDING ELEMENT HOURS FIRE WALLS (IBC Section 706) 2-hr / 1-hr LGN DRAWN BY: LGN FIRE BARRIER ASSEMBLIES (IBC SECTION 707, TABLE 707.3.10) N/A REVIEWED BY: FIRE PARTITIONS (IBC SECTION 708) N/A PROJECT MANAGER: SMOKE PARTITIONS (IBC SECTION 710) N/A VERTICAL OPENINGS (IBC SECTION 707) N/A 20141700 STAIRWAYS (IBC SECTION 1022.3, TABLE 715.4) N/A SHEET TITLE: FIRE PUMP ROOM & ACCESS CORRIDOR EXISTING CHASE REFERENCE CODE ANALYSIS BELOW 2-hr FIRE RESISTANCE 1-hr JBC A TJC PROJECT NUMBER: SHEET INDEX, ANNOTATION SYMBOLS, AND TYPICAL PLAN DIMENSIONS ISSUE DATE: 03/30/16 SHEET NUMBER: G-002 1 2 3 4 5 4 LIFE SAFETY LEGEND BUILDING AREA BASEMENT TRAVEL DISTANCE 190 240 STORAGE & MECHANICAL (1:300) 1 OCCUPANCY LOAD NUMBER AT EXIT COMPONENT OCCUPANCY COUNT EXIT COMPONENT MAXIMUM OCCUPANY CAPACITY NUMBER ACCESSORY STORAGE MECHANICAL (BASEMENT) 46 ASSEMBLY UNCONCENTRATED (BASEMENT) 16 BUSINESS (BASEMENT) 7 MULTI-PURPOSE TYPE FIRE EXTINGUISHER WALL BRACKET MOUNTED AT 48" AFF BUSINESS (1:100) Frankfurt Short Bruza Architects Engineers Planners MULTI-PURPOSE TYPE FIRE EXTINGUISHER SEMI - RECESSED CABINET MOUNT TOP OF CABINET AT 54" AFF MAX. ASSEMBLY UNCONCENTRATED (1:15) 25,902 GSF A. REFER TO SHEET G - 002 FOR CODE SUMMARY AND REQUIREMENTS. 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com H PHILIP G. McNAYR 2134 A EXIT LIGHT O F O K LA OM D E C EN EC LI T DORMITORY (1:50) D BUILDING DATA 1-HOUR PARTITION/BARRIER 2-HOUR PARTITION/BARRIER 1HR 2HR 5 GENERAL NOTES T 3 OCCUPANCY LEGEND 2 ST A 1 1 3 2 4 7 5 9 8 10 11 12 14 15 16 SE D A RCH IT 17 18 A IT 014 ELECTRICAL ROOM 007 C RESTROOM 008 IT ROOM 014A STORAGE 010A MECHANICAL ROOM 006 C CORR. 014B RESTROOM 009 7 160 MECHANICAL ROOM 006A UP STORAGE 013 TRAVEL DISTANCE 196' STORAGE 010 MAINT. OFFICE 014C CORR. 014B B B 2HR 2HR 2HR STORAGE 011 RAMP UP 2HR 23 160 STAIR 011A CORR. H015 2HR LANDING 2HR STORAGE 001B 2HR RAMP UP INVENTORY OFFICE 014D 2HR 2HR CORR. 001 23 160 MAINTENANCE SHOP 012 TRAVEL DISTANCE 152' 2HR B RESTROOM 023 STAIR 01B HALL 011B STAIR 002 OFFICE TORNADO SHELTER 016 B SHOWERS 022 2HR 2HR 2HR UP FIRE PUMP ROOM 005 STAIR S04 4/15/2016 5:02:17 PM 2HR 2HR 2HR STAIR S02 C ELECTRICAL CLOSET 004A C REVISION HISTORY: RESTROOM 011C ELECTRICAL 004C W W W W W W TORNADO SHELTER 017 W W LAUNDRY 020 D D D D W W HYDRONIC PUMP RM 004B CORR. 024 Edmond, Oklahoma CRAWL SPACE 167 University of Central Oklahoma Murdaugh Hall Renovation A CRAWL SPACE 178 1 16 160 6 5 7 9 8 10 11 12 13 ADDENDUM 002 04/18/16 DESCRIPTION DATE PROJECT INFORMATION: DESIGNED BY: 14 BDF DRAWN BY: CODE COMPLIANCE PLAN - BASEMENT KITCHENETTE 019 SCALE: 1/8" = 1'-0" A REVIEWED BY: JBC BIKE SHOP 018 A REF. C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt 1 LGN PROJECT MANAGER: TJC PROJECT NUMBER: 20141700 D D SHEET TITLE: CODE COMPLIANCE PLAN BASEMENT ISSUE DATE: 1 2 3 4 15 16 17 18 03/30/16 SHEET NUMBER: N 0 1 2 3 4 5 4' 8' 16' G-003 LIFE SAFETY LEGEND 1HR 2HR DORMITORY (1:50) 190 240 STORAGE & MECHANICAL (1:300) 1-HOUR PARTITION/BARRIER 2-HOUR PARTITION/BARRIER BUILDING AREA TRAVEL DISTANCE FIRST FLOOR OCCUPANCY LOAD NUMBER AT EXIT COMPONENT OCCUPANCY COUNT EXIT COMPONENT MAXIMUM OCCUPANY CAPACITY NUMBER DORMITORY OCCUPANTS (FIRST FLOOR) MULTI-PURPOSE TYPE FIRE EXTINGUISHER WALL BRACKET MOUNTED AT 48" AFF BUSINESS (1:100) Frankfurt Short Bruza 18,716 GSF Architects Engineers Planners 1 MULTI-PURPOSE TYPE FIRE EXTINGUISHER SEMI - RECESSED CABINET MOUNT TOP OF CABINET AT 54" AFF MAX. ASSEMBLY UNCONCENTRATED (1:15) 157 ASSEMBLY - UNCONCENTRATED (FIRST FLOOR) 237 ACCESSORY STORAGE (FIRST FLOOR) 22 BUSINESS (FIRST FLOOR) D 4 E O F O K LA H PHILIP G. McNAYR 2134 A EXIT LIGHT 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com OM D 5 BUILDING DATA C EN EC LI T 4 OCCUPANCY LEGEND T 3 1 3 2 4 7 5 9 8 10 11 12 14 15 16 UP DN 156 160 17 18 38 DORM 165 DORM 122 DORM 121 TRAVEL DISTANCE 131' DORM 120 TRAVEL DISTANCE 50' University of Central Oklahoma Murdaugh Hall Renovation CORR. H101 DORM 163 DORM 119 PLAZA C C MECH. 168 2HR 2HR 2HR 2HR 2HR 2HR 2HR 5 DORM 160 89' 89' 10 MEN'S RR 161 MEN'S RR 118 HALL DIRECTOR APARTMENT 144 CORR. H169 HALL DIRECTOR APARTMENT 140 FRONT DESK 128 RA OFFICE 126 2HR MECHANICAL CLOSET 100B DORM 156 LOUNGE 130 BONUS DORM ROOM 141A HOUSEKEEPING CLOSET 100A BONUS DORM ROOM 143 20 4/15/2016 5:02:30 PM DORM 151 UP BONUS DORM ROOM 123 DN DN C HK CLOSET 100E HOUSEKEEPING CLOSET 100F 19 11 RR 141B DORM 111 80'-0" 82' UP DORM 152 5 2HR 2HR DORM 154 2HR 2HR 2HR 2HR DORM 113 CORR. H101 RR 124A RR 144A 2HR B BONUS DORM ROOM 124 2HR DORM 158 DORM 115 149 160 149 160 B B DORM 117 2HR DORM 162 20 IT A 35 DORM 164 D A RCH DN 153 160 A DORM 166 SE BONUS DORM ROOM 123A RR 123B DORM 109 B C 20 STAIR S12 STAIR S13 DORM 108 DORM 107 Edmond, Oklahoma 2 ST A 1 REVISION HISTORY: GAME ROOM 130A DORM 150 22 340 DORM 105 78' DORM 106 78' DORM 149 19 340 DORM 147 DORM 148 DORM 104 5 6 7 9 8 10 11 12 13 DORM 103 14 1 ADDENDUM 002 04/18/16 DESCRIPTION DATE PROJECT INFORMATION: DORM 146 DORM 145 1 CODE COMPLIANCE PLAN - FIRST FLOOR DESIGNED BY: DORM 102 SCALE: 1/8" = 1'-0" BDF DORM 101 DRAWN BY: LGN REVIEWED BY: 38 C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt D A 35 JBC D A 153 160 156 160 DN PROJECT MANAGER: TJC PROJECT NUMBER: DN 20141700 SHEET TITLE: CODE COMPLIANCE PLAN FIRST FLOOR 1 2 3 4 15 16 17 18 ISSUE DATE: 03/30/16 N SHEET NUMBER: 0 1 2 3 4 5 4' 8' 16' G-004 4 OCCUPANCY LEGEND LIFE SAFETY LEGEND 1HR 2HR DORMITORY (1:50) 190 240 STORAGE & MECHANICAL (1:300) BUILDING AREA TRAVEL DISTANCE SECOND FLOOR OCCUPANCY LOAD NUMBER AT EXIT COMPONENT OCCUPANCY COUNT EXIT COMPONENT MAXIMUM OCCUPANY CAPACITY NUMBER DORMITORY OCCUPANTS (SECOND FLOOR) 211 ACCESSORY STORAGE (SECOND FLOOR) 2 Frankfurt Short Bruza 17,407 GSF Architects Engineers Planners 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com MULTI-PURPOSE TYPE FIRE EXTINGUISHER WALL BRACKET MOUNTED AT 48" AFF H PHILIP G. McNAYR 2134 A EXIT LIGHT O F O K LA OM D E C EN EC LI T BUSINESS (1:100) D 1-HOUR PARTITION/BARRIER 2-HOUR PARTITION/BARRIER 1 MULTI-PURPOSE TYPE FIRE EXTINGUISHER SEMI - RECESSED CABINET MOUNT TOP OF CABINET AT 54" AFF MAX. ASSEMBLY UNCONCENTRATED (1:15) 5 BUILDING DATA T 3 2 ST A 1 1 3 2 4 7 5 9 8 10 11 12 14 15 16 17 SE D A RCH IT DN 18 DN DN 118 160 118 160 A C 2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR 5 89' 89' 5 B B 2HR 2HR 2HR 2HR 2HR 5 2HR 2HR 2HR 5 2HR 2HR 42 47 181' 42 181' 47 B B C 4/15/2016 5:02:39 PM C Edmond, Oklahoma C University of Central Oklahoma Murdaugh Hall Renovation A 78' 78' REVISION HISTORY: 5 6 7 8 9 10 11 12 13 1 14 ADDENDUM 002 04/18/16 DESCRIPTION DATE PROJECT INFORMATION: DESIGNED BY: 1 BDF CODE COMPLIANCE PLAN - SECOND FLOOR DRAWN BY: LGN SCALE: 1/8" = 1'-0" REVIEWED BY: C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt JBC A D A D DN TJC PROJECT NUMBER: 118 160 DN 118 160 PROJECT MANAGER: 20141700 SHEET TITLE: CODE COMPLIANCE PLAN SECOND FLOOR 1 2 3 4 15 16 17 18 ISSUE DATE: 03/30/16 N SHEET NUMBER: 0 1 2 3 4 5 4' 8' 16' G-005 4 OCCUPANCY LEGEND LIFE SAFETY LEGEND 1HR 2HR DORMITORY (1:50) 190 240 STORAGE & MECHANICAL (1:300) BUILDING AREA TRAVEL DISTANCE THIRD FLOOR OCCUPANCY LOAD NUMBER AT EXIT COMPONENT OCCUPANCY COUNT EXIT COMPONENT MAXIMUM OCCUPANY CAPACITY NUMBER DORMITORY OCCUPANTS (THIRD FLOOR) Frankfurt Short Bruza 17,407 GSF Architects Engineers Planners 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com 211 ACCESSORY STORAGE (THIRD FLOOR) 2 MULTI-PURPOSE TYPE FIRE EXTINGUISHER WALL BRACKET MOUNTED AT 48" AFF H PHILIP G. McNAYR 2134 A EXIT LIGHT O F O K LA OM D E C EN EC LI T BUSINESS (1:100) D 1-HOUR PARTITION/BARRIER 2-HOUR PARTITION/BARRIER MULTI-PURPOSE TYPE FIRE 1 EXTINGUISHER SEMI - RECESSED CABINET MOUNT TOP OF CABINET AT 54" AFF MAX. ASSEMBLY UNCONCENTRATED (1:15) 5 BUILDING DATA T 3 2 ST A 1 1 3 2 4 7 5 9 8 10 11 12 14 15 16 SE D A RCH IT 17 DN 18 59 160 59 160 DN A C 2HR 2HR 2HR 2HR 2HR 2HR 2HR 2HR 5 89' 89' 5 B 2HR 2HR 1HR 2HR 2HR 2HR 5 2HR 2HR 2HR B 5 2HR 181' 42 181' 47 47 42 B B C 4/15/2016 5:02:48 PM C Edmond, Oklahoma C University of Central Oklahoma Murdaugh Hall Renovation A 78' 78' REVISION HISTORY: 1 5 6 7 9 8 10 11 12 13 14 ADDENDUM 002 04/18/16 DESCRIPTION DATE PROJECT INFORMATION: DESIGNED BY: 1 BDF CODE COMPLIANCE PLAN - THIRD FLOOR DRAWN BY: LGN SCALE: 1/8" = 1'-0" REVIEWED BY: C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt JBC A A D PROJECT MANAGER: TJC PROJECT NUMBER: D 20141700 59 160 DN 59 160 DN 1 3 2 4 15 DN SHEET TITLE: CODE COMPLIANCE PLAN THIRD FLOOR 16 17 18 ISSUE DATE: DN 03/30/16 SHEET NUMBER: N 0 1 2 3 4 5 4' 8' 16' G-006 1 2 3 4 5 GENERAL NOTES 3 4' MANHOLE 12" FL= 1208.81 N: 239797.61 E: 2125292.63 4' MANHOLE 12" FL= 1209.05 N: 239796.96 E: 2125247.96 STEEL PIPE RISER THREADED TOP, FLANGE BOTTOM INSIDE CHROMEPLATED SLEEVE 1 5" STORZ CONNECTION, COMPLETE WITH ALL UNDERGROUND PIPING, RISER PIPE & ACCESSORIES. COORDINATE WITH CITY OF EDMOND FIRE DEPARTMENT FOR HARDWARE REQUIREMENTS. 3 D D 12" HDPE CLEANOUT 10" FL= 1209.68 N: 239792.48 E: 2125156.80 D D ESCUTCHEON PLATE TOP OF SLAB SET FLUSH WITH FINISH GRADE 4' MANHOLE 15" FL= 1208.37 12" FL= 1208.62 N: 239772.74 E: 2125316.57 PE D "H 12 10" HDPE CO 12" HDPE PE 12" HD D 15" HDPE 1 12" HDPE CO MJ DUCTILE IRON ELBOW WITH RETAINING GLAND 1 4 1 3 1 DUCTILE IRON PIPE 4'-0" DIP RISER CLEANOUT 12" FL= 1209.49 N: 239746.80 E: 2125057.05 36" SQUARE x 6" CONC SLAB REINF WITH #4 BARS @ 12" OCEW MID-DEPTH 2'-6" REMOTE FIRE DEPARTMENT CONNECTION 1 2 EXISTING OR FINISHED GRADE 1 1 MARKING TAPE 2 5 4 CO CLEANOUT 12" FL= 1207.93 N: 239614.35 E: 2125245.55 E DP "H 12 12 "H D PE 4' MANHOLE 15" FL= 1207.33 N: 239565.55 E: 2125318.14 15" HDPE 1 W B 2" EXP. MAT'L. ALL-AROUND 4" 1 1 EXISTING AREA INLET 15" FL= 1207.25 N: 239554.55 E: 2125307.42 1'-0" 6" 6" #3 PERIMETER BAR, LAP 1'-0" 6" CAST IRON SOIL PIPE (PE x PE) RISER CONC ANCHOR APPROX 2' x 2' x 2' STORM DRAIN PIPE, SEE PLAN 6" FLOW 4" PLUG FOR FIRST DRAIN ON RUN 4" 8" 12" 18" MIN. 1" BYPASS 3" 1" GATE VALVE 6 3" CLEANOUT 12" 4x dia. 3" METER (METER TO BE PURCHASED THROUGH CITY OF EDMOND) 18" CITY OF EDMOND METER VAULT MANHOLE RING & COVER CONCRETE WALL REINFORCEMENT NOT SHOWN FOR CLARITY DETAIL A 6" WALLS DETAIL 'A' #7 - ENTRY WELL DRAIN DETAIL KEYED NOTES 6" WALLS 2'-0" 4" 3" CL 3" 3" 6" 2'-0" 2'-0" 4 6" 5'-4" 3" CL #4 @ 12" OC EW IN CENTER OF WALLS TYPICAL FOR WALLS WITHOUT PIPES PEDESTRIAN SAFE CAST IRON GRATE 6" 3. SIDEWALK REMOVE AND REPLACE. RE: 4/C-501. #5 - WATER LINE TRENCH SECTION 1. COMPACT BEDDING MATERIAL TO 95% ASTM D698 DENSITY (STANDARD PROCTOR). COMPACT CAREFULLY WITH SMALL MANUALLY OPERATED VIBRATORY COMPACTION EQUIPMENT. 2. INITIAL BACKFILL: FOR ALL AREAS INITIAL BACKFILL SHALL BE CRUSHED STONE SCREENINGS, PLACED TO A DEPTH OF 12" ABOVE TOP OF BEDDING MATERIAL AS SHOWN. PLACE IN 6" LIFTS & COMPACT TO 95% STANDARD PROCTOR DENSITY. FOR DUCTILE IRON PIPE, INITIAL BACKFILL MATERIAL IS NOT REQUIRED; FINAL BACKFILL MATERIAL MAY BE USED FOR ALL BACKFILL. 3. FINAL BACKFILL: UNDER PAVEMENTS USE GRANULAR SOILS SUCH AS COARSE SANDS AND GRAVELS, WITH NOT MORE THAN 15% PASSING THE #200 SIEVE (FINES). ALL FINES SHALL HAVE A MAXIMUM PLASTICITY INDEX (PI) OF 12 AND A LIQUID LIMIT NOT GREATER THAN 35. PLACE BACKFILL IN LIFTS NOT GREATER THAN 8" LOOSE THICKNESS FOR COMPACTION WITH HEAVY EQUIPMENT, AND NOT MORE THAN 6" LOOSE THICKNESS FOR COMPACTION WITH MANUALLY OPERATED VIBRATORY COMPACTORS. COMPACT EACH LIFT TO 98% STANDARD PROCTOR DENSITY (ASTM D698). IN OPEN AREAS NOT TO BE OCCUPIED BY BUILDINGS OR PAVEMENTS, FINAL BACKFILL MAY BE MADE WITH EXCAVATED SOILS, PLACED IN LIFTS AS NOTED ABOVE, AND COMPACTED TO 95% ASTM D698 DENSITY. 4. HEIGHT OF VERTICAL TRENCH SIDES FOR UNSHORED TRENCH SHALL BE GOVERNED BY CURRENT OSHA REGULATIONS AND SLOPE STABILITY RECOMMENDATIONS OF THE GEOTECHNICAL ENGINEER. HEIGHT SHALL NOT EXCEED 4 FEET, IN ANY CASE, UNLESS TRENCH IS SHORED AND BRACED FROM TOP TO BOTTOM. REVISION HISTORY: 8. FINISHED GRADE UNDER PAVEMENTS OR SLABS ON GRADE. FINISHED GRADE FOR TOP OF BACKFILL IS BOTTOM OF BASE COURSE SHOWN ON PAVEMENT OR SLAB SECTIONS. FINISHED GRADE IN GRASSED AREAS IS BOTTOM OF TOPSOIL COURSE. DESCRIPTION C 7 STD HOOK BARS DESIGNED BY: RFK DRAWN BY: JMS REVIEWED BY: PROJECT MANAGER: A C 7 TJC PROJECT NUMBER: BEFORE YOU DIG.. 20141700 OKLAHOMA ONE-CALL SYSTEM, INC. SHEET TITLE: UTILITY PLAN CALL OKIE 2" 9" #4 @ 12" OC EW 1'-0" 6" AGGREGATE BASE AS SPECIFIED COMPACTED TO 95% ASTM D1557 DENSITY 7 THE UTILITIES AS SHOWN ON THIS DRAWING WERE DEVELOPED FROM THE INFORMATION AVAILABLE. THIS IS NOT IMPLIED NOR INTENDED TO BE THE COMPLETE INVENTORY OF UTILITIES IN THIS AREA. IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE LOCATION OF ALL UTILITIES (WHETHER SHOWN OR NOT) AND PROTECT SAID UTILITIES FROM ANY DAMAGE. ISSUE DATE: 03/30/16 SHEET NUMBER: ENTRY WELL DRAIN CU101 DETAIL 'C' 3 DATE PROJECT INFORMATION: CALL 811 ANYWHERE INCREASE SLAB THICKNESS AS REQUIRED 2 B GWJ DETAIL 'B' DOMESTIC WATER METER PIT 1 3 1 #5 BARS 12"c/c EACH WAY #5 BARS 12"c/c EACH WAY 3 4" 2" CL 8" HDPE 8" 3" STRAINER 3" VARIES - SEE PLAN 3" GATE VALVE 3" CL 4. TYPICAL WALL REINFORCEMENT AT PIPE. 4" 8" MIN 3" METER (METER TO BE PURCHASED THROUGH CITY OF EDMOND) PROVIDE CORNER BARS FOR ALL HORIZ REINF IN WALLS 1" BITUMINOUS EXPANSION MATERIAL (TYP.) 3" CHECK VALVE 12" 3" GATE VALVE 8" 36" A 1'-6" 3500 PSI CONCRETE 3500 PSI CONCRETE #6 BARS 12"c/c EACH WAY CITY OF EDMOND WATER PIT COVER 1. NEW WINDOW WELL DRAIN, RE: 2/CU101. 7. REMOVE ANY UNSTABLE MATERIAL FROM THE TRENCH BOTTOM AND REPLACE WITH SELECT GRANULAR MATERIAL AS SPECIFIED. 3. SPACE REINFORCEMENT AROUND PIPE AT NOT MORE THAN 6" OC HORIZONTAL AND VERTICAL OR CLOSER AS SHOWN. 2 1'-6" CITY OF EDMOND METER VAULT MANHOLE RING & COVER C 6. WATER LINE PIPE: AS SPECIFIED. 2. BACKFILL AROUND INLET WITH SATISFACTORY SOILS COMPACTED TO 95% ASTM D1557 DENSITY IN 6" LIFTS WITH MANUALLY OPERATED PLATE COMPACTORS. 2 9'-10" H. ALL WATER LINES SHALL BE CONSTRUCTED WITH RESTRAINED JOINTS OR THRUST BLOCKS IN ACCORDANCE WITH CITY OF EDMOND STANDARD DRAWING WL-08. 1. SEE PLANS FOR FLOW ELEVATION. PLACE 2-#4 @ 4" C-C @ TOP OF WALLS #5 BARS 12"c/c EACH WAY F. CONSTRUCTION FENCE SHALL BE PLACED ALONG THE PROJECT LIMIT LINE EXCEPT WHERE SHOWN OTHERWISE ON THIS PLAN. AREAS OUTSIDE THE CONSTRUCTION FENCE BUT INSIDE THE PROJECT LIMIT LINE SHALL BE COORDINATED IN CONSTRUCTION PHASING SO AS TO MINIMIZE DISRUPTION OF TRAFFIC AND PEDESTRIAN ACCESS. WORK AREAS SHOWN OUTSIDE THE LIMITS OF CONSTRUCTION FENCE SHOWN ON THIS PLAN SHALL BE PROTECTED BY CONSTRUCTION FENCE DURING THOSE TIMES WHEN WORK IS TAKING PLACE IN THE AFFECTED AREAS. 6" 3500 PSI CONCRETE ADD 1-#4 DIAGONAL BAR EACH SIDE PIPE IN WALLS 12" 18" MIN. 3" GATE VALVE 8" 6" 6'-0" 3" GATE VALVE 15891 5. SIDES OF TRENCH ABOVE 4 FEET IN HEIGHT MUST BE LAID BACK ON STABLE SLOPES FOR EXISTING SOILS, AS DETERMINED BY A PROFESSIONAL GEOTECHNICAL ENGINEER AND MUST BE IN ACCORDANCE WITH CURRENT OSHA REGULATIONS. 3" STRAINER 3" CHECK VALVE RUSSELL FRANK KETNER 2. NEW ENTRY WELL DRAIN, RE:7/CU101. FERRULE AND SCREW PLUG COUNTERSUNK AS SHOWN WHERE MAIN SIZE IS LARGER THAN RISER SIZE, FURNISH REDUCING BRANCH WYE AND/OR BENDS 1 SUMP D E. CONTRACTOR SHALL PROTECT ALL EXISTING UTILITIES THAT PASS THROUGH THE PROJECT SITE. THESE UTILITIES ARE ACTIVE AND THEY SHALL NOT BE DISRUPTED. ANY DAMAGE TO EXISTING UTILITIES SHALL BE REPAIRED TO THE SATISFACTION OF THE UTILITY OWNER AT THE CONTRACTOR'S EXPENSE. #1 - UTILITY PLAN D TOP OF GRATE 1 1 5 UTILITY PLAN FRAME TO FIT GRATE D. THE CONTRACTOR SHALL FIELD-VERIFY THE LOCATION AND DEPTHS OF ALL UTILITIES. CARE SHALL BE EXERCISED TO AVOID DAMAGE TO EXISTING UTILITY LINES AND PREVENT LOSS OF SERVICE TO ADJACENT FACILITIES. ANY DAMAGE TO EXISTING UTILITIES SHALL BE REPAIRED TO THE OWNER'S SATISFACTION AT THE CONTRACTOR'S EXPENSE. SHEET KEYED NOTES WATER LINE TRENCH SECTION 18" x 18" x 6" CONCRETE PAD FINISH GRADE 15 "H D PE 3" TAP, 3" METER VAULT, RE: 3/CU101 1 C. ALL EMBANKMENTS AND BACKFILL SHALL MEET CITY OF EDMOND STANDARD SPECIFICATION 615.03 (g). D 4' MANHOLE 15" FL= 1207.46 12' FL = 1207.71 N: 239583.62 E: 2125276.75 3 18" INITIAL BACKFILL 2 W =PIPE OD + 2' 7 3 D #5 BARS 12"c/c EACH WAY 15" HDPE 12 "H DP E 3 4' MANHOLE 15" FL= 1208.32 12" FL= 1208.57 N: 239582.25 E: 2125100.55 3 8"x 6" TAPPING SLEEVE AND VALVE FINAL BACKFILL 3 PIPE BEDDING 1 MATERIAL 6 CLEANOUT 12" FL= 1208.82 N: 239624.35 E: 2125129.37 CO CLEANOUT 12" FL= 1208.88 N: 239628.43 E: 2125057.94 LAY BACK SIDES TO STABLE SLOPE TRENCH SIDE IF SHORED & BRACED 4'-0" MAX 12" HDPE 12" HDPE 3 CO Telephone 405.840.2931 Facsimile 405.842.7750 www.fsb-ae.com 1 12" HDPE 8" HDPE 8" HDPE 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 B. IN INSTANCES WHERE FLOW LINES ARE NOT INDICATED ON THE DRAWINGS, MAIN SHALL BE CONSTRUCTED WITH A MINIMUM OF 4'-0" COVER, OR AS DIRECTED BY THE CITY ENGINEER AND IN ACCORDANCE WITH OKLAHOMA STATE DEPARTMENT OF ENVIRONMENTAL QUALITY STANDARDS. G. ALL BURIED METAL (INCLUDING, BUT NOT LIMITED TO, STEEL AND CAST OR DUCTILE IRON) FIXTURES, PIPES AND FITTINGS SHALL USE STAINLESS STEEL NUTS AND BOLTS (WHERE APPLICABLE) AND SHALL BE PROTECTED FROM CORROSION BY POLYETHYLENE WRAPPING AS SPECIFIED. TRACING WIRE 1 C 8 12" REMOTE FDC, RE: 4/CU101 Frankfurt Short Bruza Architects Engineers Planners University of Central Oklahoma Murdaugh Hall Utility Repairs 4' MANHOLE 12" FL= 1209.18 10" FL = 1209.35 N: 239792.75 E: 2125223.09 A. ALL EXISTING WATER MAINS BEING ABANDONED BY ANY PROJECT ARE TO REMAIN THE PROPERTY OF THE CITY OF EDMOND, AND SHALL BE SALVAGED FOR THE CITY WATER DEPARTMENT. 4 5 2 3 4 SMOOTH FINISH TOOLED 18"R 3/8" 1 1 1/2" 1 2" 4" TYP. SILICONE SEALANT 2" CLR PAVEMENT REINFORCING CONTINUOUS @ JOINT. 4" 1 1/2" 12" 5" TRACING WIRE TRENCH SIDE IF SHORED & BRACED FINAL 3 BACKFILL INITIAL 2 BACKFILL FIN GRADE 8"R TOOL JOINT ANTICIPATED SHRINKAGE CRACK TOOLED JOINT DIMENSIONS MAY VARY SLIGHTLY FROM NOTE: THOSE SHOWN TO SUIT STANDARD DEEP BIT GROOVING TOOLS. NOTE: T = PAVEMENT THICKNESS 1 CONTINUOUSLY REINF CONTRACTION JOINT (SJ) 2 SIDEWALK TOOLED JOINT (STJ) NEENAH FOUNDRY R-1682-S MANHOLE FRAME & COVER OR APPROVED EQUAL. STAMP COVER WITH "STORM SEWER". 12" CAST IRON DOME GRATE 3 1'-0" 4" COMPACTED 1-1/2" CRUSHED ROCK 6 JOINTS: CONSTRUCT TOOLED JOINT (STJ) EVERY 5 FEET, CONSTRUCT EXPANSION JOINT (SWEJ) NOT TO EXCEED EVERY 50 FEET. CAP STRIPS MAY BE USED. DEPTHS SHOWN SHALL BE STRICTLY ADHERED TO. 7 CONCRETE MINIMUM 3500 psi COMPRESSIVE STRENGTH 512 SACK MIX, MAX 4" SLUMP, 4-6% AIR ENTRAINED SIDEWALK EXPANSION JOINT (SWEJ) 4 TYPICAL SIDEWALK DETAIL 5 WINDOW WELL DRAIN D RUSSELL FRANK KETNER 15891 W =PIPE OD + 2' STORM SEWER TRENCH SECTION SHEET KEYNOTES #5 - STORM SEWER TRENCH SECTION TOP OF NEW PAVEMENT OR FINISHED GRADE STD PRECAST CONE SECTION VARIES 1. COMPACT BEDDING MATERIAL TO 95% ASTM D698 DENSITY (STANDARD PROCTOR). COMPACT CAREFULLY WITH SMALL MANUALLY OPERATED VIBRATORY COMPACTION EQUIPMENT. 2. INITIAL BACKFILL: FOR ALL AREAS INITIAL BACKFILL SHALL BE CRUSHED STONE SCREENINGS, PLACED TO A DEPTH OF 12" ABOVE TOP OF BEDDING MATERIAL AS SHOWN. PLACE IN 6" LIFTS & COMPACT TO 95% STANDARD PROCTOR DENSITY. FOR DUCTILE IRON PIPE SEWERS INITIAL BACKFILL MATERIAL IS NOT REQUIRED; FINAL BACKFILL MATERIAL MAY BE USED FOR ALL BACKFILL. BRICK MASONRY, PRECAST OR CAST-IN-PLACE RING 5" MH DIA (SEE SCHED) RUBBER RING JOINTS 1'-0" 8" HDPE D. STEEL GRATING SHALL BE GALVANIZED AFTER FABRICATION. PIPE BEDDING 1 MATERIAL SD OUTFALL SD LINE t INNER FACE OF MANHOLE MASTIC SEALER TO BE PLACED BEFORE SECTIONS ARE SET FORMED SEAT 2" DEEP x 6" WIDE AROUND PERIM 2" 3" MIN 2" 3" MIN 8" MIN. #5 BARS @ 12" OC (HOOP BARS) #5 BARS @ 24" OC AROUND PERIMETER MASTIC SEALER TO BE PLACED BEFORE SECTIONS ARE SET 2-#5 CONTINUOUS AROUND PERIMETER T (T=t+4") CRUSHED STONE UNDER MANHOLE SD OUTFALL SD LINE 1'-0" 4. HEIGHT OF VERTICAL TRENCH SIDES FOR UNSHORED TRENCH SHALL BE GOVERNED BY CURRENT OSHA REGULATIONS AND SLOPE STABILITY RECOMMENDATIONS OF THE GEOTECHNICAL ENGINEER. HEIGHT SHALL NOT EXCEED 4 FEET, IN ANY CASE, UNLESS TRENCH IS SHORED AND BRACED FROM TOP TO BOTTOM. COMPACTED PIPE BEDDING MATERIAL 1'-0" #5 BARS @ 8" OCEW 6" MIN 3" CLR CRUSHED STONE UNDER MANHOLE B NOTE: ALTERNATE DETAILS FOR PRECAST OR CAST-IN-PLACE MANHOLES MAY BE SUBMITTED FOR REVIEW & APPROVAL. 7 C 3. FINAL BACKFILL: UNDER PAVEMENTS USE GRANULAR SOILS SUCH AS COARSE SANDS AND GRAVELS, WITH NOT MORE THAN 15% PASSING THE #200 SIEVE (FINES). ALL FINES SHALL HAVE A MAXIMUM PLASTICITY INDEX (PI) OF 12 AND A LIQUID LIMIT NOT GREATER THAN 35. PLACE BACKFILL IN LIFTS NOT GREATER THAN 8" LOOSE THICKNESS FOR COMPACTION WITH HEAVY EQUIPMENT, AND NOT MORE THAN 6" LOOSE THICKNESS FOR COMPACTION WITH MANUALLY OPERATED VIBRATORY COMPACTORS. COMPACT EACH LIFT TO 98% STANDARD PROCTOR DENSITY (ASTM D698). IN OPEN AREAS NOT TO BE OCCUPIED BY BUILDINGS OR PAVEMENTS, FINAL BACKFILL MAY BE MADE WITH EXCAVATED SOILS, PLACED IN LIFTS AS NOTED ABOVE, AND COMPACTED TO 95% ASTM D698 DENSITY. 5" MIN WALL VARIES 6 COMPACTED SUBGRADE 4 Telephone 405.840.2931 Facsimile 405.842.7750 www.fsb-ae.com 1' MIN STANDARD PRECAST SECTIONS (TYPE AND QUANTITIES TO MEET LINE DEPTH REQUIREMENTS) C DRAIN BASIN 8" IN GRASSED AREAS, TOP OF MANHOLE TO BE A MINIMUM OF 4" ABOVE FINISHED GRADE EXPANSION JOINT NOTES: 1) SAWCUT AND REMOVE EXISTING CONCRETE FOR INSTALLATION OF NEW DRAIN. 2) REPLACE CONCRETE AROUND NEW DRAIN TO MATCH EXISITNG CONCRETE. 3) DOWEL INTO EXISTING CONCRETE A MINIMUM OF 6". #3 DOWELS x 12". 4 DOWELS PER DRAIN. 9" PREMOLDED EXPANSION JOINT MATERIAL MAX SPACING 50 FEET 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 C.MAIN BARS TO BE 4" DEEP BY 3 8" THICK, SPACED AT 13 8" OC AND CROSS BARS SHALL BE WELDED USING 12" ROUNDED BARS SPACED 4" OC ADDITIONAL CROSS BARS SHALL BE WELDED TO MAIN BARS AS SHOWN. 6" 1 Frankfurt Short Bruza Architects Engineers Planners 6" T 4'-0" MAX. 1" MIN D 2" #5 - AREA INLET DETAIL B. GRATING MATERIAL SHALL CONFORM TO ASTM A36 STEEL SPECIFICATIONS FOR MAIN BEARING BARS. CONCRETE PAVEMENT 1 GENERAL NOTES A.STEEL GRATING TO BE IKG INDUSTRIES STYLE HW, TYPE C18C OR APPROVED EQUAL. MARKING TAPE #3 BARS @ 16" OCEW, MID-DEPTH OF PVMT. 2% MAX LAY BACK 5 SIDES TO STABLE SLOPE EXISTING OR 8 FINISHED GRADE FORMS SHALL BE FULL-DEPTH OF SIDEWALK 1 4" TIGHT FLOAT 2" DEEP TOOLED DUMMY 3 FINISH BAND JOINT WITH 8" TROWELLED RADIUS BOTH SIDES. STIFF-BRISTLE BROOM FINISH PRODUCE APPROX. 132" TOOTH WIDTH VARIES (SEE PLANS) SAWED JOINT RE: X/C-5XX 5 STORM DRAIN MANHOLE DIAMETER SCHEDULE PIPE SIZE MIN MH Ø (IN) (FT) 24 & LESS 30 36 42 48 54 60 5. SIDES OF TRENCH ABOVE 4 FEET IN HEIGHT MUST BE LAID BACK ON STABLE SLOPES FOR EXISTING SOILS, AS DETERMINED BY A PROFESSIONAL GEOTECHNICAL ENGINEER AND MUST BE IN ACCORDANCE WITH CURRENT OSHA REGULATIONS. 4.0 5.0 5.0 5.0 5.5 6.0 6.5 B 6. STORM PIPE: AS SPECIFIED. 7. REMOVE ANY UNSTABLE MATERIAL FROM THE TRENCH BOTTOM AND REPLACE WITH SELECT GRANULAR MATERIAL AS SPECIFIED. STORM SEWER MANHOLE DETAIL University of Central Oklahoma Murdaugh Hall Utility Repairs 1 REVISION HISTORY: 8. FINISHED GRADE UNDER PAVEMENTS OR SLABS ON GRADE. FINISHED GRADE FOR TOP OF BACKFILL IS BOTTOM OF BASE COURSE SHOWN ON PAVEMENT OR SLAB SECTIONS. FINISHED GRADE IN GRASSED AREAS IS BOTTOM OF TOPSOIL COURSE. #5 - AREA INLET DETAIL 1. SEE PLANS FOR FLOW ELEVATION. 2. BACKFILL AROUND INLET WITH SATISFACTORY SOILS COMPACTED TO 95% ASTM D1557 DENSITY IN 6" LIFTS WITH MANUALLY OPERATED PLATE COMPACTORS. 3. SPACE REINFORCEMENT AROUND PIPE AT NOT MORE THAN 6" OC HORIZONTAL AND VERTICAL OR CLOSER AS SHOWN. DESCRIPTION DATE PROJECT INFORMATION: 4. TYPICAL WALL REINFORCEMENT AT PIPE. DESIGNED BY: RFK DRAWN BY: JMS REVIEWED BY: GWJ PROJECT MANAGER: A A TJC PROJECT NUMBER: 20141700 SHEET TITLE: CIVIL DETAILS 1 ISSUE DATE: 03/30/16 SHEET NUMBER: C-501 1 2 3 4 5 5 4 3 1/4" 4" 5'-0" 1/2" DIA STEEL PICKETS SPACED 4" CLEAR MAX 8" 8" 4'-11" 4" FINISH GRADE #4 VERT @ 12" OC CONCRETE BRIDGE CAST IN PLACE CONCRETE FOOTING PHILIP G. McNAYR 2134 1 1" CHAMFER CAST IN PLACE CONCRETE RETAINING WALL BEYOND H EN C #4 DOWEL INTO WALL @ 12" O.C. W/ HILTI HY-200 (4 1/2" EMBED) TYP @ RETAINING WALLS D LI CAST IN PLACE CONCRETE RETAINING WALL #4 @ 12" O.C.E.W. #4 HORIZ @ 9" OC O F O K LA A 6 A-102 E OM CONCRETE SLAB EMBED PLATE 1/2" X 4 1/2" X 4 1/2" W/ (4) 1/2" X 12" DEFORMED BAR ANCHORS ON 3 1/2" X 3 1/2" PATTERN SE D A RCH IT 1 1/2" CLEAR COVER 1'-0" 1" CHAMFER 1 3/4" 1" CHAMFER 5'-3" #4 @ 12" O.C.E.W. AT MID - THICKNESS (TYP. @ RAMPS) T 1" CHAMFER 1/2" CHAMFER TYP ALL RETAINING WALLS 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com EC 1 1 3/4" 1 1/2" D 1 1/2" DIA STEEL PIPE GUARDRAIL VARIES 1 3/16 3'-6" 1 3/4" Frankfurt Short Bruza Architects Engineers Planners EPOXY BARS INTO WALL (4 1/2" EMBEDED) 4" 3'-0" 3'-6" 1 1 1/2" DIA STEEL PIPE GUARDRAIL POSTS AT 4' OC MIN 3'-2" 4 3/4" 4 A-102 8" 1 3/4" CLEAR 1 1/2" DIA STEEL PIPE HANDRAIL 1 3/4" 3 1/4" TYP STEEL TUBE POST AT GUARD 5'-0" 5'-0" CLEAR 1 1/2" T 3 2 ST A 1 #4 @ 12" OC 1 1/2" 7 A-102 10" 5'-0" 3" CONC COVER IN FOOTING 3" FINISH GRADE RAMP SECTION 1'-0" SCALE: 3/4" = 1'-0" 8" 1'-0" University of Central Oklahoma Murdaugh Hall Renovation 2'-8" 16'-3 1/4" 3 1/4" 5'-2 3/4" EQ 4" EQ 2 3/4" 10'-8 1/2" EQ EQ 2 EQ RAMP SECTION 6 SCALE: 3/4" = 1'-0" SECTION DETAIL (TYPICAL RAMP WALL) SCALE: 1 1/2" = 1'-0" 2 A-102 C C 1 1/2" DIA STEEL PIPE GUARDRAIL. POSTS AT 4' OC MIN 1 1/2" DIA STEEL HANDRAIL 1/2" DIA STEEL PICKETS SPACED 4" CLEAR MIN 1/4" EXPANSION MATERIAL 4" 4" 1 8" CONCRETE SLAB TYP POST AT GUARD REINFORCED CONCRETE BRIDGE 6" CONSTRUCTION JOINT 10'-6" 3/4" RUSTICATION JOINT CAST IN PLACE CONCRETE RETAINING WALL EXISTING WINDOW WELL 1 1/2" CLEAR COVER B 3 RAMP SECTION 5 SCALE: 3/4" = 1'-0" 3/16 #4 @ 12" OC 1 1/2" CAST IN PLACE CONCRETE FOOTINGS 3/16 4" 1" 1/4" NEOPRENE BEARING PAD 8" #4 DOWELS @ 16" O.C. CAST IN PLACE CONCRETE RETAINING WALL EMBED PLATE 1/2" X 4 1/2" X 4 1/2" W/ (4) 1/2" X 10" DBA ON 3 1/2" X 3 1/2" PATTERN 1'-0" 5 A-102 1/2" 1 1 1/2" 3 1/4" 3 1/4" ENLARGED DETAIL 7 SCALE: 6" = 1'-0" #4 @ 8" OC B SECTION DETAIL SCALE: 1 1/2" = 1'-0" 35'-8 3/4" 4/15/2016 5:03:51 PM 2'-10 1/4" 2'-10 1/4" 3'-11 3/4" 3'-11 3/4" 3'-11 3/4" 3'-11 3/4" 3'-11 3/4" 3'-11 3/4" 2'-0 1/2" REVISION HISTORY: 3" DIA X 1/4" STEEL MOUNTING PLATE W/ 3/8" FLAT HEAD COUNTERSUNK MACHINE BOLT EACH SIDE IN HILTI HIS-N INSERTS IN HY-200 ADHESIVE 1 A-102 2'-10" 3 A-102 1 1/2" DIA STEEL PIPE GUARDRAIL POSTS AT 4' OC MIN 4" 4" 3'-6" 3'-11 3/4" 1 1'-9 1/2" 1 1/2" DIA STEEL PIPE HANDRAIL 04/18/16 DESCRIPTION DATE PROJECT INFORMATION: LLS CONCRETE SLAB DRAWN BY: LLS 1" CHAMFER REVIEWED BY: 1 MJW 3'-0" 2'-6 1/2" C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt ADDENDUM 002 DESIGNED BY: RAMP BEYOND 1'-0" A Edmond, Oklahoma 1 A PROJECT MANAGER: TJC PROJECT NUMBER: CAST IN PLACE CONCRETE FOOTING 20141700 SHEET TITLE: RAMP SECTIONS AND DETAILS CONTRACTION JOINT IN CONCRETE WALLS 5'-0" 5'-0" 5'-0" 3'-3 1/2" 1'-8 1/2" 4 1 2 5'-0" 5'-0" 5'-0" SECTION THROUGH ADA RAMP EW ISSUE DATE: 1 SCALE: 3/4" = 1'-0" 3 4 5 0 1" 2" 4" 0 4" 8" 1'-4" 0 8" 1'-4" 2'-8" 03/30/16 SHEET NUMBER: A-102 5 GENERAL NOTES 4 5 7 8 9 10 11 12 14 15 16 17 13 DN DN 18 DN DN A DORM 166 5 11 2 4 11 5 11 2 4 DORM 164 C 4 2 11 1 11 2 4 DORM 165 DORM 122 DORM 163 DORM 120 5 11 2 4 11 5 11 2 4 CORR. H101 DORM 121 DORM 119 4 2 11 1 2 4 11 PLAZA DORM 162 4 2 5 8 11 MECH. 168 17 1 11 10 MECH. 101A 17 11 10 4 2 5 8 11 1 MEN'S RR 118 MEN'S RR 161 DORM 160 DORM 115 11 2 4 15 B 2 4 11 15 B 3 DORM 158 11 4 2 5 8 11 11 1 3 HALL DIRECTOR APARTMENT 144 6 11 2 4 1 16 7 11 11 11 11 FRONT DESK 128 RA OFFICE 126 LOUNGE 130 MECHANICAL CLOSET 100C DORM 154 DORM 152 C DORM 150 DORM 148 UP 4 2 5 8 11 UP 11 2 4 4 2 5 8 11 4 2 5 11 8 UP 9 BONUS DORM ROOM 141A BONUS DORM ROOM 143 11 11 HOUSEKEEPING CLOSET 100A DN HOUSEKEEPING CLOSET 100F BONUS DORM ROOM 123 6 DN 11 11 11 B 4 2 5 8 11 UP 1 11 STAIR S12 11 DORM 108 GAME ROOM 130A DORM 151 DORM 106 DORM 149 CORR. H101 2 4 11 5 6 7 9 8 10 11 12 13 4 2 5 8 11 4 2 5 11 8 T EC D A RCH IT REVISION HISTORY: DORM 105 DORM 103 2 4 11 14 SE 2 4 11 DORM 104 11 2 4 DORM 109 DORM 107 DN STAIR S13 11 C 2 4 11 7 DN DORM 113 DORM 111 1 16 UP BONUS DORM ROOM 123A DORM 147 2 4 11 4 2 5 8 11 HK CLOSET 100E 1 1 11 2 4 1 TPHONE CLOSET 100D 9 B 12 11 1 BONUS DORM ROOM 124 14 MECHANICAL CLOSET 100B UP 11 HALL DIRECTOR APARTMENT 140 DORM 156 4/15/2016 5:02:55 PM DORM 117 PHILIP G. McNAYR 2134 EN DEMOLITION KEYNOTES 1. DEMO PLASTER VENEER WALL TO ACCESS BACKSIDE OF CHASE FOR PLUMBING WORK. PROTECT EXISTING TERRAZZO BASE. REMOVE EXISTING WOOD TRIM PRIOR TO DEMO OF WALL SURFACE. SAVE AND PROTECT WOOD TRIM FOR REINSTALLATION. 2. DEMO PLASTER /METAL CHANNEL WALLS TO ACCESS ON SIDE OF CHASE FOR PLUMBING WORK. DEMO EXISTING WALL HUNG SINK, TOOTHBRUSH/SOAP HOLDERS AND TOWEL RINGS. PROTECT EXISTING TERRAZZO FLOOR AND BASE. 1 3. DEMO CLAY TERRA COTTA BLOCK WALL, PROTECT TERRAZZO BASE. 4. DEMO EXISTING LIGHT FIXTURE. TV CABLE OUTLET RELOCATION, REFERENCE SHEET E-401. 5. DEMO PLASTER/METAL CHASE WALLS. 6. REMOVE EXISTING WATER COOLER AND RETURN TO OWNER. GENERAL CONTRACTOR TO REINSTALL WATER COOLER AT SAME LOCATION. VERIFY BACKING WITH OWNER PRIOR TO REINSTALLATION. 1 7. DEMO GYPSUM DRYWALL. 8. DEMO EXISTING LATH AND PLASTER. 9. DEMO 8" BRICK WALL TO ACCESS CHASE FOR NEW MECHANICAL DUCT WORK. 10.DEMO EXISTING EXHAUST FAN. 11.DEMO EXISTING FAN COIL UNIT. 12.DEMO EXISTING URINAL 13.DEMO EXISTING RAMP, RAILING AND EXISTING SIGNAGE. PROTECT BUILDING AND ITS EXISTING SURROUNDINGS DURING THE DEMO PROCESS AND THROUGHOUT CONSTRUCTION. 14.REMOVE EXISTING CARPET TILE AND RETURN TO OWNER IF ALTERNATE IS ACCEPTED. GENERAL CONTRACTOR TO STORE AND REINSTALL CARPET TILE AT SAME LOCATION. 1 15.DEMO EXISTING FURR-OUT. 16.DEMO EXISTING DOUBLE DOORS AND WALL ABOVE 17.DEMO CONTENTS OF ROOM. 1 H Edmond, Oklahoma 3 O F O K LA A 2 D E C 1 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com OM D Frankfurt Short Bruza Architects Engineers Planners LI A. DRAWINGS ARE ONLY AN APPROXIMATION OF EXISTING CONDITIONS. GENERAL CONTRACTOR SHALL VISIT SITE AND EXAMINE EXISTING STRUCTURE, NOTE ALL CONDITIONS AS TO CHARACTER AND EXTENT OF WORK INVOLVED, VERIFY ALL DIMENSIONS PRIOR TO LAYOUT AND NOTIFY ARCHITECT OF ANY DISCREPANCIES, BEFORE STARTING ANY WORK. B. GENERAL CONTRACTOR SHALL COORDINATE ALL TRADE REQUIREMENTS AND REPORT CONFLICTS IMMEDIATELY IF FOUND. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONAL DATA AND LOCATIONS OF ALL OPENINGS AND EQUIPMENT TO REMAIN. DISCONNECT ANY ELECTRIC, GAS, WATER, OR OTHER LINES SERVICING THE EQUIPMENT PER RULES AND REGULATIONS OF AUTHORITIES HAVING JURISDICTION BEFORE ANY WORK IS TO PROCEED. C. REPAIR EXISTING CONSTRUCTION, AS REQUIRED, TO MATCH ADJACENT CONSTRUCTION IN QUALITY, SIZE, TEXTURE, AND FINISH, WHERE DAMAGED BY DEMOLITION WORK. D. GENERAL CONTRACTOR TO PROTECT EXISTING BUILDING DURING CONSTRUCTION. GENERAL CONTRACTOR SHALL TAKE PROPER AND NECESSARY PRECAUTIONS TO PROTECT EXISTING BUILDING FROM TEMPERATURE AND HUMIDITY EXTREMES. BUILD TEMPORARY ENCLOSURES AS REQUIRED TO ENSURE BUILDING IS PROTECTED. REPAIR ALL WATER DAMAGED ITEMS DUE TO CONSTRUCTION AT NO ADDITIONAL EXPENSE TO THE OWNER. E. DEMOLITION OF ANY EXISTING CONSTRUCTION REQUIRED BY ANY TRADE TO PROPERLY COMPLETE THEIR WORK SHALL BE ACCOMPLISHED AS A PART OF THEIR WORK AND SHALL BE PART OF THE PRIME CONTRACT. F. REFER TO PLUMBING SHEETS TO VERIFY PLUMBING PIPING TO BE REMOVED. G. REFER TO MECHANICAL SHEETS TO VERIFY MECHANICAL PIPING AND EQUIPMENT TO BE REMOVED. University of Central Oklahoma Murdaugh Hall Renovation 4 T 3 2 ST A 1 1 ADDENDUM 002 04/18/16 DESCRIPTION DATE PROJECT INFORMATION: 2 4 11 DESIGNED BY: BDF DRAWN BY: C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt LGN A DORM 146 D 5 4 2 11 4 2 5 11 11 1 FIRST FLOOR DEMOLITION PLAN DORM 102 SCALE: 1/8" = 1'-0" DORM 145 4 2 5 11 REVIEWED BY: 4 2 5 11 11 MJW A PROJECT MANAGER: TJC PROJECT NUMBER: DORM 101 20141700 SHEET TITLE: DEMOLITION FIRST FLOOR PLAN DN DN DN 1 3 2 ISSUE DATE: DN 4 15 16 17 03/30/16 18 SHEET NUMBER: N 0 1 2 3 4 5 4' 8' 16' AD102 5 GENERAL NOTES 9 8 10 11 12 14 15 16 17 DN DN 18 UP A 5 UP DORM 265 11 DORM 266 2 4 11 C DORM 264 5 11 2 4 11 2 4 DORM 222 4 2 5 8 11 11 9 1 4 2 5 11 8 MECH. 201A MEN'S RR 218 1 MEN'S RR 261 11 DORM 260 DORM 11 215 2 4 1 DORM 4 258 2 5 8 11 6 DORM 244 1 4/15/2016 5:03:02 PM CORR. H202 11 5 DORM 236 4 8 2 4 8 2 DORM 234 2 4 4 2 11 11 11 5 5 DORM 232 11 4 4 2 DORM 230 DORM 228 4 4 8 2 2 DORM 226 2 11 5 DORM 224 MECH 261A CORR. H201 DORM 243 2 4 11 5 11 1 DORM 252 DORM 239 DORM 241 DORM 237 2 4 8 5 11 DORM 233 DORM 235 2 4 8 5 11 2 4 11 2 4 11 DORM 231 DORM 229 2 4 8 5 11 DORM 225 2 4 11 DORM 227 2 4 8 5 11 2 4 11 4 2 5 8 11 DORM 247 2 4 11 4 2 5 11 8 5 11 DORM 209 1 11 2 4 2 4 11 4 2 5 8 11 B 8 DORM 251 2 4 11 DORM 213 2 4 7 13 3 STAIRUP S21 DORM 223 C DORM 11 211 1 13 7 3 UP 4 2 5 11 8 6 3 MECH. 218A DORM 254 DORM 248 C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt DORM 238 DORM 240 5 11 2 4 1 H.C. 234A B 4 2 5 11 8 DORM 249 5 6 7 8 9 10 11 12 13 DORM 208 T EC IT 11 2 4 4 2 5 11 8 DORM 206 DORM 205 1 DORM 203 11 2 4 14 D A RCH REVISION HISTORY: DORM 207 DORM 204 11 2 4 SE ADDENDUM 002 04/18/16 DESCRIPTION DATE 11 PROJECT INFORMATION: 2 4 DESIGNED BY: BDF DRAWN BY: LGN 4 2 5 DORM 246 11 A 11 DORM 242 4 2 3 11 2 4 DORM 250 11 11 11 3 5 DORM 256 C 10 12 3 10 B 4 2 5 11 DORM 217 1. DEMO PLASTER/CLAY TILE BLOCK WALL TO ACCESS BACKSIDE OF CHASE FOR PLUMBING WORK. PROTECT EXISTING TERRAZZO BASE. REMOVE EXISTING WOOD TRIM PRIOR TO DEMO OF WALL SURFACE. SAVE AND PROTECT WOOD TRIM FOR REINSTALLATION. 2. DEMO PLASTER/METAL CHANNEL WALLS TO ACCESS ON SIDE OF CHASE FOR PLUMBING WORK. DEMO EXISTING WALL HUNG SINK & TOOTHBRUSH/SOAP HOLDERS. PROTECT EXISTING TERRAZZO FLOORS AND BASE. 1 3. DEMO PLASTER VENEER PARTITION ONLY AT ONE SIDE TO ACCESS EXISTING PLUMBING. 4. DEMO EXISTING LIGHT FIXTURE. TV CABLE OUTLET RELOCATION, REFERENCE SHEET E-401. 5. DEMO PLASTER/METAL CHASE WALLS. 6. REMOVE EXISTING WATER COOLER AND RETURN TO OWNER. GENERAL CONTRACTOR TO REINSTALL WATER COOLER AT SAME LOCATION. 7. DEMO 8" BRICK TO ACCESS CHASE FOR NEW MECHANICAL DUCT WORK. 8. DEMO EXISTING LATH AND PLASTER. 9. DEMO EXISTING EXHAUST FAN 10.DEMO EXISTING FURR-OUT 11.DEMO EXISTING FAN COIL UNIT 12.DEMO EXISTING URINAL 13.DEMO EXISTING DOUBLE DOORS, JAMB AND WALL ABOVE 14.DEMO CONENTS OF ROOM 1 PHILIP G. McNAYR 2134 EN DEMOLITION KEYNOTES 11 2 4 DORM 11 219 2 4 14 11 9 DORM 221 4 2 11 1 DORM 263 11 1 MECH. 202A 14 5 11 DORM 220 4 2 11 2 4 DORM 262 5 H Edmond, Oklahoma 7 5 O F O K LA A 4 D E C 3 2 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com LI 1 Frankfurt Short Bruza Architects Engineers Planners OM D A. DRAWINGS ARE ONLY AN APPROXIMATION OF EXISTING CONDITIONS. GENERAL CONTRACTOR SHALL VISIT SITE AND EXAMINE EXISTING STRUCTURE, NOTE ALL CONDITIONS AS TO CHARACTER AND EXTENT OF WORK INVOLVED, VERIFY ALL DIMENSIONS PRIOR TO LAYOUT AND NOTIFY ARCHITECT OF ANY DISCREPANCIES, BEFORE STARTING ANY WORK. B. GENERAL CONTRACTOR SHALL COORDINATE ALL TRADE REQUIREMENTS AND REPORT CONFLICTS IMMEDIATELY IF FOUND. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONAL DATA AND LOCATIONS OF ALL OPENINGS AND EQUIPMENT TO REMAIN. DISCONNECT ANY ELECTRIC, GAS, WATER, OR OTHER LINES SERVICING THE EQUIPMENT PER RULES AND REGULATIONS OF AUTHORITIES HAVING JURISDICTION BEFORE ANY WORK IS TO PROCEED. C. REPAIR EXISTING CONSTRUCTION, AS REQUIRED, TO MATCH ADJACENT CONSTRUCTION IN QUALITY, SIZE, TEXTURE, AND FINISH, WHERE DAMAGED BY DEMOLITION WORK. D. GENERAL CONTRACTOR TO PROTECT EXISTING BUILDING DURING CONSTRUCTION. GENERAL CONTRACTOR SHALL TAKE PROPER AND NECESSARY PRECAUTIONS TO PROTECT EXISTING BUILDING FROM TEMPERATURE AND HUMIDITY EXTREMES. BUILD TEMPORARY ENCLOSURES AS REQUIRED TO ENSURE BUILDING IS PROTECTED. REPAIR ALL WATER DAMAGED ITEMS DUE TO CONSTRUCTION AT NO ADDITIONAL EXPENSE TO THE OWNER. E. DEMOLITION OF ANY EXISTING CONSTRUCTION REQUIRED BY ANY TRADE TO PROPERLY COMPLETE THEIR WORK SHALL BE ACCOMPLISHED AS A PART OF THEIR WORK AND SHALL BE PART OF THE PRIME CONTRACT. F. REFER TO PLUMBING SHEETS TO VERIFY PLUMBING PIPING TO BE REMOVED. G. REFER TO MECHANICAL SHEETS TO VERIFY MECHANICAL PIPING AND EQUIPMENT TO BE REMOVED. University of Central Oklahoma Murdaugh Hall Renovation 4 T 3 2 ST A 1 11 DORM 245 4 2 5 11 1 SECOND FLOOR DEMOLITION PLAN 4 2 5 11 SCALE: 1/8" = 1'-0" REVIEWED BY: DORM 202 4 2 5 11 11 MJW A PROJECT MANAGER: TJC PROJECT NUMBER: DORM 201 20141700 SHEET TITLE: D DEMOLITION SECOND FLOOR PLAN UP UP ISSUE DATE: 1 3 2 4 15 16 17 03/30/16 18 SHEET NUMBER: N DN 1 0 DN 2 3 4 5 4' 8' 16' AD103 5 GENERAL NOTES 9 8 10 11 12 14 15 16 DN 17 DN 18 DN DN A 5 11 5 DORM 366 11 2 2 4 DORM 364 4 DORM 363 4 2 2 4 11 C 5 11 2 4 DORM 365 4 2 11 1 1 11 DORM 322 5 11 DORM 321 1. DEMO PLASTER/CLAY TILE BLOCK WALL TO ACCESS BACKSIDE OF CHASE FOR PLUMBING WORK. PROTECT EXISTING TERRAZZO BASE. REMOVE EXISTING WOOD TRIM PRIOR TO DEMO OF WALL SURFACE. SAVE AND PROTECT WOOD TRIM FOR REINSTALLATION. 2. DEMO PLASTER/METAL CHANNEL WALLS TO ACCESS ON SIDE OF CHASE FOR PLUMBING WORK. DEMO EXISTING WALL HUNG SINK & TOOTHBRUSH/SOAP HOLDERS. PROTECT EXISTING TERRAZZO FLOOR AND BASE. 1 3. DEMO EXISTING PLASTER VENEER PARTITION ONLY AT ONE SIDE TO ACCESS EXISTING PLUMBING. 4. DEMO EXISTING LIGHT FIXTURE. TV CABLE OUTLET RELOCATION, REFERENCE SHEET E-401. 5. DEMO PLASTER/METAL CHASE WALLS. 6. REMOVE EXISTING WATER COOLER AND RETURN TO OWNER. GENERAL CONTRACTOR TO REINSTALL WATER COOLER AT SAME LOCATION. 7. DEMO 8" BRICK TO ACCESS CHASE FOR NEW MECHANICAL DUCT WORK. 8. DEMO EXISTING LATH AND PLASTER. 9. DEMO EXISTING FURR-OUT 10.DEMO EXISTING EXHAUST FANS 11.DEMO EXISTING FAN COIL UNIT 12.DEMO EXISTING URINAL 13.DEMO EXISTING DOUBLE DOORS, JAMB AND WALL ABOVE 14.DEMO CONTENTS OF ROOM DORM 319 11 2 4 DORM 320 1 4 2 5 11 8 14 MECH. 302A DORM 362 11 10 11 10 MEN'S RR 361 DORM 11 360 2 4 1 DORM 317 4 2 5 11 8 MEN'S RR 318 DORM 315 11 2 1 B 9 3 4 2 5 11 8 14 MECH. 301A 11 4 2 5 6 DORM 358 11 5 11 3 DORM 344 4 2 4 DORM 2 340 DORM 342 11 5 11 DORM 338 11 2 4 DORM 334 4 DORM 2 336 11 11 11 5 5 11 4 2 DORM 330 4 DORM 2 332 4 2 4 4 2 5 11 4 DORM 2 328 1 9 12 3 DORM 313 6 DORM DORM 326 324 3 H.C. 334B 11 2 4 B 4 2 5 11 8 4/18/2016 7:25:09 PM C 11 2 4 4 2 5 11 8 DORM 356 1 DORM 311 1 CORR. H300 DN DORM 343 DORM 341 DORM 354 DORM 352 DORM 349 DORM 348 DORM 337 2 4 11 2 4 DORM 8 335 5 11 DORM 333 2 4 11 DORM 331 DORM 329 2 4 8 5 11 DORM 325 2 4 DORM 8 327 5 11 2 4 11 5 4 2 8 2 4 11 5 11 DORM 309 3 CORR. H301 DORM 308 11 2 4 4 2 5 11 8 DORM 305 DORM 306 DORM 304 11 2 4 5 6 7 9 8 10 11 12 13 DORM 303 11 2 4 14 11 8 DORM 307 11 2 4 11 2 4 4 2 5 11 8 B 1 DORM 347 11 2 4 STAIR S31 DORM 323 1 DORM 351 DORM 350 2 4 8 DORM 339 5 11 2 4 11 5 11 3 CORR. H302 11 2 4 13 7 13 7 STAIR DN S34 C 1 5 11 8 PHILIP G. McNAYR 2134 T EC EN DEMOLITION KEYNOTES 2 4 H SE D A RCH IT Edmond, Oklahoma 7 5 O F O K LA A 4 D E C 3 2 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com LI 1 Frankfurt Short Bruza Architects Engineers Planners OM D A. DRAWINGS ARE ONLY AN APPROXIMATION OF EXISTING CONDITIONS. GENERAL CONTRACTOR SHALL VISIT SITE AND EXAMINE EXISTING STRUCTURE, NOTE ALL CONDITIONS AS TO CHARACTER AND EXTENT OF WORK INVOLVED, VERIFY ALL DIMENSIONS PRIOR TO LAYOUT AND NOTIFY ARCHITECT OF ANY DISCREPANCIES, BEFORE STARTING ANY WORK. B. GENERAL CONTRACTOR SHALL COORDINATE ALL TRADE REQUIREMENTS AND REPORT CONFLICTS IMMEDIATELY IF FOUND. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONAL DATA AND LOCATIONS OF ALL OPENINGS AND EQUIPMENT TO REMAIN. DISCONNECT ANY ELECTRIC, GAS, WATER, OR OTHER LINES SERVICING THE EQUIPMENT PER RULES AND REGULATIONS OF AUTHORITIES HAVING JURISDICTION BEFORE ANY WORK IS TO PROCEED. C. REPAIR EXISTING CONSTRUCTION, AS REQUIRED, TO MATCH ADJACENT CONSTRUCTION IN QUALITY, SIZE, TEXTURE, AND FINISH, WHERE DAMAGED BY DEMOLITION WORK. D. GENERAL CONTRACTOR TO PROTECT EXISTING BUILDING DURING CONSTRUCTION. GENERAL CONTRACTOR SHALL TAKE PROPER AND NECESSARY PRECAUTIONS TO PROTECT EXISTING BUILDING FROM TEMPERATURE AND HUMIDITY EXTREMES. BUILD TEMPORARY ENCLOSURES AS REQUIRED TO ENSURE BUILDING IS PROTECTED. REPAIR ALL WATER DAMAGED ITEMS DUE TO CONSTRUCTION AT NO ADDITIONAL EXPENSE TO THE OWNER. E. DEMOLITION OF ANY EXISTING CONSTRUCTION REQUIRED BY ANY TRADE TO PROPERLY COMPLETE THEIR WORK SHALL BE ACCOMPLISHED AS A PART OF THEIR WORK AND SHALL BE PART OF THE PRIME CONTRACT. F. REFER TO PLUMBING SHEETS TO VERIFY PLUMBING PIPING TO BE REMOVED. G. REFER TO MECHANICAL SHEETS TO VERIFY MECHANICAL PIPING AND EQUIPMENT TO BE REMOVED. University of Central Oklahoma Murdaugh Hall Renovation 4 T 3 2 ST A 1 REVISION HISTORY: 4 5 2 11 8 1 11 2 4 ADDENDUM 002 04/18/16 DESCRIPTION DATE PROJECT INFORMATION: DESIGNED BY: BDF C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt DRAWN BY: 4 2 5 11 A DORM 346 4 2 5 11 11 D 1 4 2 5 11 THIRD FLOOR DEMOLITION PLAN SCALE: 1/8" = 1'-0" DORM 345 LGN DORM 302 DORM 301 11 4 2 5 11 REVIEWED BY: MJW A PROJECT MANAGER: TJC PROJECT NUMBER: 20141700 SHEET TITLE: DN 1 DN 3 2 DEMOLITION THIRD FLOOR PLAN 4 15 16 DN 17 ISSUE DATE: 18 03/30/16 DN SHEET NUMBER: N 0 1 2 3 4 5 4' 8' 16' AD104 5 GENERAL NOTES 4 7 5 9 8 10 11 12 14 15 16 17 18 O F O K LA H PHILIP G. McNAYR 2134 T A 3 2 D E EN C 1 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com OM D Frankfurt Short Bruza Architects Engineers Planners LI A. DRAWINGS ARE ONLY AN APPROXIMATION OF EXISTING CONDITIONS. CONTRACTOR SHALL VISIT SITE AND EXAMINE EXISTING STRUCTURE, NOTE ALL CONDITIONS AS TO CHARACTER AND EXTENT OF WORK INVOLVED, VERIFY ALL DIMENSIONS PRIOR TO LAYOUT AND NOTIFY ARCHITECT OF ANY DISCREPANCIES, BEFORE STARTING ANY WORK. B. CONTRACTOR SHALL COORDINATE ALL TRADE REQUIREMENTS AND REPORT CONFLICTS IMMEDIATELY IF FOUND. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONAL DATA AND LOCATIONS OF ALL OPENINGS AND EQUIPMENT TO REMAIN. DISCONNECT ANY ELECTRIC, GAS, WATER, OR OTHER LINES SERVICING THE EQUIPMENT PER RULES AND REGULATIONS OF AUTHORITIES HAVING JURISDICTION BEFORE ANY WORK IS TO PROCEED. C. REPAIR EXISTING CONSTRUCTION, AS REQUIRED, TO MATCH ADJACENT CONSTRUCTION IN QUALITY, SIZE, TEXTURE, AND FINISH, WHERE DAMAGED BY DEMOLITION WORK. D. PROTECT EXISTING BUILDING DURING CONSTRUCTION. CONTRACTOR SHALL TAKE PROPER AND NECESSARY PRECAUTIONS TO PROTECT EXISTING BUILDING FROM TEMPERATURE AND HUMIDITY EXTREMES. BUILD TEMPORARY ENCLOSURES AS REQUIRED TO ENSURE BUILDING IS PROTECTED. REPAIR ALL WATER DAMAGED ITEMS AT NO ADDITIONAL EXPENSE TO THE OWNER. E. DEMOLITION OF ANY EXISTING CONSTRUCTION REQUIRED BY ANY TRADE TO PROPERLY COMPLETE THEIR WORK SHALL BE ACCOMPLISHED AS A PART OF THEIR WORK AND SHALL BE PART OF THE PRIME CONTRACT. F. ANY DISCREPANCIES OR ITEMS NOT SPECIFICALLY OR GENERALLY LISTED SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR RESOLUTION PRIOR TO DEMOLITION OR REMOVAL. EC 4 T 3 2 ST A 1 SE D A RCH IT A IT 014 CRAWL SPACE 167 C ELECTRICAL ROOM 007 1. DEMO EXISTING ACOUSTICAL CEILING AND FUR DOWN INCLUDING GRIDS, SUSPENSION SYSTEMS, HANGER SUPPORT WIRES INCLUDING ANY CLIPS ATTACHED TO THE STRUCTURE ABOVE. 2. CONTRACTOR SHALL RETURN ALL DEMO'D ITEMS WHICH SHALL INCLUDE BUT NOT LIMITED TO THE FOLLOWING, LIGHT FIXTURES, MECHANICAL DIFFUSERS, ELECTRICAL FACE PLATES, ETC. C IT ROOM 014A RESTROOM 008 STORAGE 010A DEMOLITION LEGEND DEMO EXISTING 1'X4' SURFACE MOUNT FIXTURE MECHANICAL ROOM 006 CORR. 014B RESTROOM 009 DEMO EXISTING SURFACE MOUNT FIXTURE STORAGE 013 MAINT. OFFICE 014C STORAGE 010 MECHANICAL ROOM 006A 1 B B MAINTENANCE SHOP 012 STORAGE 001B INVENTORY OFFICE 014D STORAGE 011 CORR. H015 STAIR 011A B ELECTRICAL CLOSET 005B FIRE PUMP ROOM 005 ELECTRICAL CLOSET 005A 4/15/2016 5:01:20 PM DEMO EXISTING ACT FUR DOWN STAIR STAIR 01B 002 B HALL 011B STAIR S02 CORR. 024 RESTROOM 023 STAIR S04 SHOWERS 022 OFFICE TORNADO SHELTER 016 CORR. H024 Edmond, Oklahoma A University of Central Oklahoma Murdaugh Hall Renovation SHEET KEYNOTES REVISION HISTORY: C C HYDRONIC PUMP RM 004B ELECTRICAL CLOSET 004A RESTROOM 011C ELECTRICAL 004C TORNADO SHELTER 017 2 1 LAUNDRY 020 1 ADDENDUM 002 04/18/16 DESCRIPTION DATE PROJECT INFORMATION: CRAWL SPACE 178 DESIGNED BY: BDF DRAWN BY: 5 6 7 9 8 10 11 12 13 LGN 14 REVIEWED BY: C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt MJW A A KITCHENETTE 019 1 TJC PROJECT NUMBER: BIKE SHOP 018 BASEMENT DEMOLITION CEILING PLAN PROJECT MANAGER: 20141700 SHEET TITLE: SCALE: 1/8" = 1'-0" D DEMOLITION BASEMENT CEILING PLAN D ISSUE DATE: 03/30/16 SHEET NUMBER: N 1 2 3 1 4 15 2 3 16 4 17 18 0 5 4' 8' 16' AD105 5 GENERAL NOTES 9 10 4 TYP 2 2 2 3 9 TYPICAL DORM ROOM TYPICAL BATHROOM 10 B 2 1 2 2 1 9 6 3 6 2 6 9 3 2 TYPICAL DORM ROOM 6 9 9 2 C 1. DEMO EXISTING ACOUSTICAL CEILING AND FUR DOWN INCLUDING GRIDS, SUSPENSION SYSTEMS, HANGER SUPPORT WIRES INCLUDING ANY CLIPS ATTACHED TO THE STRUCTURE ABOVE. 2. DEMO EXISTING, SURFACE MOUNT 1X4 FLUORESCENT LIGHT FIXTURES. 3. DEMO PLASTER CEILING TO ACCOMMODATE ACCESS TO SEWER ABOVE. NEW CEILING TO BE INSTALLED WITH MOISTURE RESISTANT GYPSUM BOARD ON SUSPENDED CEILING SYSTEM AND PAINTED WITH EPOXY PAINT. 4. CEILING BETWEEN COFFERS HAS ALREADY BEEN DEMO'D 5. DEMO EXISTING CEILING THROUGHOUT 6. REMOVE EXISTING, SURFACE MOUNT ELECTRICAL CONDUIT. 7. DEMO EXISTING, SURFACE MOUNT ELECTRICAL CONDUIT. EXISTING CEILING FANS TO REMAIN. 8. DEMO PORTION OF EXISTING TIN CEILING TILE AS NOTED ON PLAN. EXISTING TIN CEILING TILE TO BE REUSED AT NEW FURR-DOWN - REF. SHEET AE108, NOTE 3 9. DEMO SMOKE AND FIRE ALARM DEVISES AND WIRE. 10.DEMO EXISTING SURFACE MOUNT VANITY LIGH 11.DEMO ALL COPPER TELEPHONE WIRE THROUGHOUT CORRIDORS AND DORM ROOMS. (TYP.) C 9 2 2 TYPICAL DORM ROOM 10 2 7 9 TYPICAL DORM ROOM 1 6 9 3 2 2 STAIR TYPICAL DORM ROOM 9 1 2 6 2 C C 1 9 8 ENLARGED RESTROOM DEMOLITION CEILING PLAN 2 2 3 4 5 7 8 9 10 11 12 14 15 16 10 11 DEMOLITION LEGEND ENLARGED LOBBY DEMOLITION CEILING PLAN 3 SCALE: 3/16" = 1'-0" 1 DEMO EXISTING 1'X4' SURFACE MOUNT FIXTURE SCALE: 3/16" = 1'-0" 17 DEMO EXISTING SURFACE MOUNT FIXTURE DN DN DEMO EXISTING ACT FUR DOWN 18 1 DN B 1 DN A 4/15/2016 5:03:21 PM 122 165 164 121 120 163 H101 119 101A 168 8 D A RCH IT REVISION HISTORY: 3 AD106 162 B B A 166 SE SHEET KEYNOTES TYPICAL DORM ROOM 2 1 EN Edmond, Oklahoma 2 PHILIP G. McNAYR 2134 C 1 9 6 H A TYPICAL DORM ROOM D O F O K LA OM D E University of Central Oklahoma Murdaugh Hall Renovation 1 9 6 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com T B Frankfurt Short Bruza Architects Engineers Planners LI A. DRAWINGS ARE ONLY AN APPROXIMATION OF EXISTING CONDITIONS. CONTRACTOR SHALL VISIT SITE AND EXAMINE EXISTING STRUCTURE, NOTE ALL CONDITIONS AS TO CHARACTER AND EXTENT OF WORK INVOLVED, VERIFY ALL DIMENSIONS PRIOR TO LAYOUT AND NOTIFY ARCHITECT OF ANY DISCREPANCIES, BEFORE STARTING ANY WORK. B. CONTRACTOR SHALL COORDINATE ALL TRADE REQUIREMENTS AND REPORT CONFLICTS IMMEDIATELY IF FOUND. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONAL DATA AND LOCATIONS OF ALL OPENINGS AND EQUIPMENT TO REMAIN. DISCONNECT ANY ELECTRIC, GAS, WATER, OR OTHER LINES SERVICING THE EQUIPMENT PER RULES AND REGULATIONS OF AUTHORITIES HAVING JURISDICTION BEFORE ANY WORK IS TO PROCEED. C. REPAIR EXISTING CONSTRUCTION, AS REQUIRED, TO MATCH ADJACENT CONSTRUCTION IN QUALITY, SIZE, TEXTURE, AND FINISH, WHERE DAMAGED BY DEMOLITION WORK. D. PROTECT EXISTING BUILDING DURING CONSTRUCTION. CONTRACTOR SHALL TAKE PROPER AND NECESSARY PRECAUTIONS TO PROTECT EXISTING BUILDING FROM TEMPERATURE AND HUMIDITY EXTREMES. BUILD TEMPORARY ENCLOSURES AS REQUIRED TO ENSURE BUILDING IS PROTECTED. REPAIR ALL WATER DAMAGED ITEMS DUE TO CONSTRUCTION AT NO ADDITIONAL EXPENSE TO THE OWNER. E. DEMOLITION OF ANY EXISTING CONSTRUCTION REQUIRED BY ANY TRADE TO PROPERLY COMPLETE THEIR WORK SHALL BE ACCOMPLISHED AS A PART OF THEIR WORK AND SHALL BE PART OF THE PRIME CONTRACT. F. REFER TO PLUMBING SHEETS TO VERIFY PLUMBING PIPING TO BE REMOVED. EC 4 T 3 2 ST A 1 117 115 160 B 161 158 128 144 126 113 FIRST LEVEL ROOMS 111 156 Room Number Room Name FIRST LEVEL ROOMS Room Number FIRST LEVEL ROOMS Room Name Room Number Room Name FIRST LEVEL ROOMS Room Number FIRST LEVEL ROOMS Room Name Room Number Room Name 100B 100A 100F S12 STAIR 154 143 STAIR 109 123 C C 1 152 1 S13 151 C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt 141A 150 A 107 108 106 149 105 H101 148 147 D 260 166 164 162 160 H169 156 154 152 150 148 146 H167 145 147 149 5 6 7 8 9 10 11 12 13 14 145 146 102 DN 1 DN 103 104 1 DEMOLITION FIRST FLOOR CEILING PLAN 101 DN D DORM DORM DORM DORM DORM CORR. DORM DORM DORM DORM DORM DORM CORR. DORM DORM DORM 151 161 168 163 165 144 141A 143 S13 128 S12 123 122 120 118 108 DORM MEN'S RR MECH. DORM DORM HALL DIRECTOR APARTMENT BONUS DORM ROOM BONUS DORM ROOM STAIR FRONT DESK STAIR BONUS DORM ROOM DORM DORM MEN'S RR DORM 106 104 102 101 103 105 107 109 111 113 115 117 119 121 H101 100E 100B 1 DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM CORR. HK CLOSET MECHANICAL CLOSET H100 100C 100A 126 124 123A 100F 100D 101A H200 S04 158 167 178 024 123A CORR. MECHANICAL CLOSET HOUSEKEEPING CLOSET RA OFFICE RA DIRECTOR STAFF OFFICE HOUSEKEEPING CLOSET TPHONE CLOSET MECH. CORR. STAIR DORM CRAWL SPACE CRAWL SPACE CORR. BONUS DORM ROOM 124 124A 123B 123C 123D 144A 140 BONUS DORM ROOM RR RR Room Room RR HALL DIRECTOR APARTMENT RR LOUNGE GAME ROOM MECH. MECH. CORR. CORR. CORR. CORR. STAIR 141B 130 130A 161A 130B H171 H172 H173 H174 S12B 1 ADDENDUM 002 04/18/16 DESCRIPTION DATE PROJECT INFORMATION: DESIGNED BY: BDF DRAWN BY: LGN REVIEWED BY: MJW A PROJECT MANAGER: TJC PROJECT NUMBER: 20141700 SHEET TITLE: DEMOLITION FIRST FLOOR CEILING PLAN ISSUE DATE: DN N SCALE: 1/16" = 1'-0" 0 2'-8" 5'-4" 10'-8" 03/30/16 SHEET NUMBER: 0 8' 16' 32' AD106 1 2 3 4 5 5 GENERAL NOTES 10 11 12 14 15 16 17 DN DN 18 UP UP 6 6 1 5 7 1 C 5 7 4 6 DORM 264 5 DORM 265 6 5 7 6 1 6 1 5 7 5 DORM 266 4 1 7 6 1 5 6 5 7 6 DORM 220 5 6 CORR. H201 2 6 5 7 DORM 260 5 7 5 MEN'S RR 261 1 7 6 5 3 3 1 7 6 5 4 DORM 242 1 7 6 5 DORM 240 4 1 7 6 5 5 4 1 7 6 5 DORM 234 DORM 236 DORM 238 1 7 6 5 1 7 6 5 4 DORM 230 DORM 232 1 7 6 1 7 6 5 4 DORM 228 1 7 6 5 DORM 226 MEN'S RR 218 5 5 6 5 5 5 1 1 DORM 215 DEMO EXISTING 1'X4' SURFACE MOUNT FIXTURE 4 3 5 7 5 5 3 1 DEMO EXISTING SURFACE MOUNT FIXTURE DORM 213 DEMO EXISTING ACT FUR DOWN 6 DORM 256 C DEMOLITION LEGEND 6 DORM 224 1 DORM 217 6 DORM 244 1 4 5 DORM 258 1. DEMO EXISTING ACOUSTICAL CEILING AND FUR DOWN INCLUDING GRIDS, SUSPENSION SYSTEMS, HANGER SUPPORT WIRES INCLUDING ANY CLIPS ATTACHED TO THE STRUCTURE ABOVE. 2. DEMO CEILING THROUGHOUT 3. DEMO PLASTER CEILING TO ACCOMMODATE ACCESS TO SEWER ABOVE. NEW CEILING TO BE INSTALLED WITH MOISTURE RESISTANT GYPSUM BOARD ON SUSPENDED CEILING SYSTEM AND PAINTED WITH EPOXY PAINT. 4. DEMO EXISTING SURFACE MOUNT VANITY LIGHT. 5. REMOVE EXISTING, SURFACE MOUNT 1X4 FLUORESCENT LIGHT FIXTURES. 6. REMOVE EXISTING, SURFACE MOUNT ELECTRICAL CONDUIT, TYP. 7. DEMO ALL EXISTING SMOKE AND FIRE ALARM DEVISES AND WIRE. 8. REMOVE COPPER TELEPHONE WIRE THROUGHOUT CORRIDORS AND DORM ROOMS. (TYP.) DORM 219 MECH. 201A DORM 262 B 1 DORM 221 7 6 2 AD106 MECH. 202A 5 DORM 222 4 1 DORM 263 5 7 4 5 7 5 1 5 1 DORM 211 5 B STAIR 3 4/15/2016 5:03:29 PM DORM 254 C 1 5 7 6 DORM 252 4 1 5 7 DORM 243 6 5 7 6 DORM 250 5 7 5 5 7 6 1 DORM 241 5 7 6 1 DORM 239 4 4 DORM 237 7 6 1 5 7 6 1 DORM 235 5 DORM 233 7 6 1 5 5 DORM 231 7 6 1 DORM 229 7 6 1 5 DORM 227 5 7 6 1 DORM 225 5 7 6 1 DORM 223 6 7 6 1 5 7 5 1 1 5 1 5 7 6 5 7 6 6 DORM 248 4 5 7 5 1 6 5 7 6 7 6 DORM 247 5 6 7 8 9 10 11 12 13 5 14 SE D A RCH IT 1 REVISION HISTORY: DORM 207 4 6 DORM 206 1 DORM 209 5 DORM 208 4 1 DORM 249 1 STAIR 3 5 7 5 CORR. H201 1 B 4 4 DORM 251 4 6 6 4 4 5 T EN SHEET KEYNOTES A 1 PHILIP G. McNAYR 2134 Edmond, Oklahoma 9 8 H University of Central Oklahoma Murdaugh Hall Renovation 7 5 O F O K LA A 4 D E C 3 2 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com LI 1 Frankfurt Short Bruza Architects Engineers Planners OM D A. DRAWINGS ARE ONLY AN APPROXIMATION OF EXISTING CONDITIONS. CONTRACTOR SHALL VISIT SITE AND EXAMINE EXISTING STRUCTURE, NOTE ALL CONDITIONS AS TO CHARACTER AND EXTENT OF WORK INVOLVED, VERIFY ALL DIMENSIONS PRIOR TO LAYOUT AND NOTIFY ARCHITECT OF ANY DISCREPANCIES, BEFORE STARTING ANY WORK. B. CONTRACTOR SHALL COORDINATE ALL TRADE REQUIREMENTS AND REPORT CONFLICTS IMMEDIATELY IF FOUND. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONAL DATA AND LOCATIONS OF ALL OPENINGS AND EQUIPMENT TO REMAIN. DISCONNECT ANY ELECTRIC, GAS, WATER, OR OTHER LINES SERVICING THE EQUIPMENT PER RULES AND REGULATIONS OF AUTHORITIES HAVING JURISDICTION BEFORE ANY WORK IS TO PROCEED. C. REPAIR EXISTING CONSTRUCTION, AS REQUIRED, TO MATCH ADJACENT CONSTRUCTION IN QUALITY, SIZE, TEXTURE, AND FINISH, WHERE DAMAGED BY DEMOLITION WORK. D. PROTECT EXISTING BUILDING DURING CONSTRUCTION. CONTRACTOR SHALL TAKE PROPER AND NECESSARY PRECAUTIONS TO PROTECT EXISTING BUILDING FROM TEMPERATURE AND HUMIDITY EXTREMES. BUILD TEMPORARY ENCLOSURES AS REQUIRED TO ENSURE BUILDING IS PROTECTED. REPAIR ALL WATER DAMAGED ITEMS DUE TO CONSTRUCTION AT NO ADDITIONAL EXPENSE TO THE OWNER. E. DEMOLITION OF ANY EXISTING CONSTRUCTION REQUIRED BY ANY TRADE TO PROPERLY COMPLETE THEIR WORK SHALL BE ACCOMPLISHED AS A PART OF THEIR WORK AND SHALL BE PART OF THE PRIME CONTRACT. F. REFER TO PLUMBING SHEETS TO VERIFY PLUMBING PIPING TO BE REMOVED. EC 4 T 3 2 ST A 1 DORM 205 7 6 6 5 7 DORM 204 4 5 1 1 1 ADDENDUM 002 04/18/16 DESCRIPTION DATE PROJECT INFORMATION: DESIGNED BY: DORM 203 BDF DRAWN BY: C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt 1 5 7 A 4 6 6 1 DORM 246 5 7 1 1 DORM 245 1 DEMOLITION SECOND FLOOR CEILING PLAN 5 SCALE: 1/8" = 1'-0" LGN 4 7 6 6 1 5 7 DORM 202 REVIEWED BY: 1 MJW A DORM 201 PROJECT MANAGER: TJC PROJECT NUMBER: 20141700 D SHEET TITLE: UP DEMOLITION SECOND FLOOR CEILING PLAN UP ISSUE DATE: 1 2 3 4 15 16 DN 17 18 03/30/16 SHEET NUMBER: N DN 0 1 2 3 4 5 4' 8' 16' AD107 7 8 9 10 11 12 14 15 16 17 DN DN A 5 7 5 7 5 DORM 366 2 2 6 5 7 DORM 364 2 MECH. 302A 6 5 7 C DORM 363 DORM 362 5 6 DORM 320 B 2 6 5 5CORR. H301 5 MEN'S RR 361 1 6 1 6 DORM 360 2 5 5 7 5 5 5 DORM 358 DORM 356 CORR. H302 5 2 4/15/2016 5:03:36 PM 7 6 2 5 7 6 DORM 334 DORM 336 2 7 6 DORM 332 5 5 7 6 2 DORM 330 5 7 6 DORM 328 5 7 6 2 DORM 326 7 6 CORR. H300 5 5 6 5 5 5 DORM 354 7 6 3 STAIR 5 7 6 2 5 7 6 DORM 343 DORM 341 7 6 2 5 5 DORM 352 2 1 5 DORM 339 DORM 337 5 7 6 DORM 335 7 6 2 5 DORM 333 5 7 6 DORM 331 5 7 6 2 5 DORM 329 7 6 5 7 6 2 5 DORM 325 DORM 327 7 6 3 DORM 323 7 6 2 2 6 DORM 306 2 5 DORM 347 6 7 8 9 10 11 12 13 CORR. H301 DORM 304 1 DEMOLITION THIRD FLOOR CEILING PLAN 5 7 DORM 302 DORM 345 IT REVISION HISTORY: DORM 303 2 6 5 SCALE: 1/8" = 1'-0" D A RCH 5 7 6 6 5 7 2 SE 6 5 7 5 14 DORM 305 5 7 5 7 6 6 DORM 346 6 B DORM 307 5 7 5 DORM 349 6 6 7 6 5 7 5 5 DORM 2 308 5 7 DORM 309 5 7 5 6 DORM 2 348 2 6 STAIR DORM 351 6 DEMO EXISTING ACT FUR DOWN DORM 311 5 7 5 DORM 350 DEMO EXISTING SURFACE MOUNT FIXTURE 6 5 6 5 7 DORM 313 5 5 5 DEMO EXISTING 1'X4' SURFACE MOUNT FIXTURE 3 MECH. 318A C DEMOLITION LEGEND 5 7 5 H.C. 334B 5 3 DORM 324 1. DEMO CEILING THROUGHOUT 2. DEMO EXISTING SURFACE MOUNT VANITY LIGHT. 3. DEMO PLASTER CEILING TO ACCOMMODATE ACCESS TO SEWER ABOVE. NEW CEILING TO BE INSTALLED WITH MOISTURE RESISTANT GYPSUM BOARD ON SUSPENDED CEILING SYSTEM AND PAINTED WITH EPOXY PAINT. 4. NOT USED 5. REMOVE EXISTING, SURFACE MOUNT 1X4 FLUORESCENT LIGHT FIXTURES. 1 6. REMOVE EXISTING, SURFACE MOUNT ELECTRICAL CONDUIT. 7. DEMO SMOKE AND FIRE ALARM DEVISES AND WIRE. 8. REMOVE COPPER TELEPHONE WIRE THROUGHOUT CORRIDORS AND DORM ROOMS (TYP.) 2 6 STAIR S31 CORR. H302 5 7 7 6 2 DORM 338 DORM 340 5 6 5 7 7 6 5 5 MEN'S RR 318 STAIR S34 5 5 7 7 6 5 MECH. 361A 5 6 5 7 5 DORM 342 DORM 344 3 C B 5 2 7 6 3 6 5 7 DORM 315 5 7 5 6 5 7 DORM 317 6 6 5 7 DORM 319 5 7 EN SHEET KEYNOTES 6 6 5 7 DORM 321 5 7 2 7 6 5 5 6 5 DORM 322 2 DORM 365 6 5 7 7 6 6 6 A 18 PHILIP G. McNAYR 2134 C DN H LI DN D O F O K LA OM D E Edmond, Oklahoma 5 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com T 4 Frankfurt Short Bruza Architects Engineers Planners EC 3 A. DRAWINGS ARE ONLY AN APPROXIMATION OF EXISTING CONDITIONS. CONTRACTOR SHALL VISIT SITE AND EXAMINE EXISTING STRUCTURE, NOTE ALL CONDITIONS AS TO CHARACTER AND EXTENT OF WORK INVOLVED, VERIFY ALL DIMENSIONS PRIOR TO LAYOUT AND NOTIFY ARCHITECT OF ANY DISCREPANCIES, BEFORE STARTING ANY WORK. B. CONTRACTOR SHALL COORDINATE ALL TRADE REQUIREMENTS AND REPORT CONFLICTS IMMEDIATELY IF FOUND. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONAL DATA AND LOCATIONS OF ALL OPENINGS AND EQUIPMENT TO REMAIN. DISCONNECT ANY ELECTRIC, GAS, WATER, OR OTHER LINES SERVICING THE EQUIPMENT PER RULES AND REGULATIONS OF AUTHORITIES HAVING JURISDICTION BEFORE ANY WORK IS TO PROCEED. C. REPAIR EXISTING CONSTRUCTION, AS REQUIRED, TO MATCH ADJACENT CONSTRUCTION IN QUALITY, SIZE, TEXTURE, AND FINISH, WHERE DAMAGED BY DEMOLITION WORK. D. PROTECT EXISTING BUILDING DURING CONSTRUCTION. CONTRACTOR SHALL TAKE PROPER AND NECESSARY PRECAUTIONS TO PROTECT EXISTING BUILDING FROM TEMPERATURE AND HUMIDITY EXTREMES. BUILD TEMPORARY ENCLOSURES AS REQUIRED TO ENSURE BUILDING IS PROTECTED. REPAIR ALL WATER DAMAGED ITEMS DUE TO CONSTRUCTION AT NO ADDITIONAL EXPENSE TO THE OWNER. E. DEMOLITION OF ANY EXISTING CONSTRUCTION REQUIRED BY ANY TRADE TO PROPERLY COMPLETE THEIR WORK SHALL BE ACCOMPLISHED AS A PART OF THEIR WORK AND SHALL BE PART OF THE PRIME CONTRACT. F. REFER TO PLUMBING SHEETS TO VERIFY PLUMBING PIPING TO BE REMOVED. University of Central Oklahoma Murdaugh Hall Renovation 2 5 GENERAL NOTES 4 T 1 3 2 ST A 1 DORM 301 1 ADDENDUM 002 04/18/16 DESCRIPTION DATE PROJECT INFORMATION: DESIGNED BY: D BDF DRAWN BY: LGN DN DN REVIEWED BY: C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt MJW A 1 3 2 4 15 16 DN 17 A 18 PROJECT MANAGER: TJC PROJECT NUMBER: DN 20141700 SHEET TITLE: DEMOLITION THIRD FLOOR CEILING PLAN ISSUE DATE: 03/30/16 N SHEET NUMBER: 0 1 2 3 4 5 4' 8' 16' AD108 BOND BEAM W/ (2) #4 4000 PSI CONCRETE 4X4 W4.0X X W4.0 WWF AT SLAB MID - DEPTH 8" CMU FULLY GROUTED 12" CMU FULLY GROUTED #4 REBAR DOWEL, EPOXY ANCHOR TO EXISTING SLAB @ 24" O.C. #4 REBAR DOWEL, EPOXY ANCHOR TO EXISTING SLAB @ 24" O.C. BASEMENT 91'-0" 11 5/8" 4'-6" a. ON EACH SIDE OF CONTROL JOINTS b. AT ALL WALL INTERSECTIONS OF EXTERIOR WALLS c. AT ALL DISCONTINUOUS EDGES d. AS SHOWN ON STRUCTURAL DRAWINGS 1 EN SECTION DETAIL 2-HR NEW PARTITION - 2 HR RATED 1-HR NEW PARTITION - 1 HR RATED C 014 1 014A 007B RESTROOM 008 STORAGE 010A 014B 013B 008 MECHANICAL ROOM 006 EXISTING LANDING & STAIR 006B 6 RESTROOM 009 MECHANICAL ROOM 006A STORAGE 013 1 UP CORR. 014B STORAGE 010 MAINT. OFFICE 014C 6 014C G1 B PROTECT COPPER TELEPHONE WIRE, IT WIRING AND COX CABLING WITHIN SHADED AREA IT ROOM 014A B 006A 2-HR 2-HR 001 6 001A B 2-HR LANDING G1 EXISTING RAMP UP INVENTORY OFFICE 014D B STORAGE 001B 1 LANDING 4/18/2016 7:49:03 PM 1 004A G1 2-HR 1 2 1 F1 E1 2-HR G1 2-HR E1 5 4 2-HR 015A 1 G1 022 023 015B STAIR S04 RESTROOM 023 5 4 HALL 011B STAIR 01B CORR. H015 2 E1 E1 G1 2-HR 014E 013A 2-HR EXISTING RAMP UP 005 014D MAINTENANCE SHOP 012 STORAGE 011 016 E1 SHOWERS 022 3 OFFICE TORNADO SHELTER 016 Edmond, Oklahoma IT 014 007A IT 1 SCALE: 1 1/2" = 1'-0" CRAWL SPACE 167 ELECTRICAL ROOM 007 D A RCH EXISTING WALL A C SE NEW PARTITION MAX. 2 PHILIP G. McNAYR 2134 ARCHITECTURAL LEGEND J. CMU LINTELS SHALL USE THE TYPICAL BOND BEAM K. CELLS WHICH CONTAIN REINFORCING STEEL SHALL BE FILLED SOLIDLY WITH 3,000 psi GROUT MEETING THE REQUIREMENTS OF ASTM C476. 7 5/8" H A 2 EA. #4 CONTINUOUS @ BOND BEAM EXISTING RAMP LANDING O F O K LA C 2 EA. #4 CONTINUOUS @ BOND BEAM D E LI 1 1/2" METAL DECK, 22 GA. PROVIDE 14GA L6X6 POUR STOP AT DOORWAY 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com OM 1/4" TAPCON SCREWS @ 12" O.C. TO ANCHOR DECT FROM DECK TO BE CONTINUOUS D 1/4" TAPCON SCREWS @ 12" O.C. TO ANCHOR FROM DECK TO BE CONTINUOUS Frankfurt Short Bruza Architects Engineers Planners T 8" CMU 2-HR RATED WALL A. DRAWINGS ARE ONLY AN APPROXIMATION OF EXISTING CONDITIONS. GENERAL CONTRACTOR SHALL VISIT SITE AND EXAMINE EXISTING STRUCTURE, NOTE ALL CONDITIONS AS TO CHARACTER AND EXTENT OF WORK INVOLVED, VERIFY ALL DIMENSIONS PRIOR TO LAYOUT AND NOTIFY ARCHITECT OF ANY DISCREPANCIES, BEFORE STARTING ANY WORK. B. GENERAL CONTRACTOR SHALL COORDINATE ALL TRADE REQUIREMENTS AND REPORT CONFLICTS IMMEDIATELY IF FOUND. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONAL DATA AND LOCATIONS OF ALL OPENINGS AND EQUIPMENT TO REMAIN. DISCONNECT ANY ELECTRIC, GAS, WATER, OR OTHER LINES SERVICING THE EQUIPMENT PER RULES AND REGULATIONS OF AUTHORITIES HAVING JURISDICTION BEFORE ANY WORK IS TO PROCEED. C. GENERAL CONTRACTOR SHALL REPAIR EXISTING CONSTRUCTION, AS REQUIRED, TO MATCH ADJACENT CONSTRUCTION IN QUALITY, SIZE, TEXTURE, AND FINISH, WHERE DAMAGED BY DEMOLITION WORK. D. ALL DRYWALL AND PLASTER WALLS AND CEILING TO RECEIVE NEW PAINT; LEVEL ONE, TWO AND THREE E. ALL INTERIOR DIMENSIONS ARE TO FACE OF STUDS AND CONCRETE MASONRY UNLESS NOTED OTHERWISE. EC EXISTING WALL TO REMAIN #4 VERTICAL BAR @ 48" O.C. FULL HEIGHT (TYP.) 1. EXISTING INCINERATOR TO CONTAIN FIRESTOP SILICONE SEALANT, SELF LEVELING. REF. SHEET 10/G-007. 2. ACCESS PANEL - LOCKABLE 1 3. REPAIR PLASTER VENEER 4. GYPSUM BOARD FURROUT TO CONCEAL NEW HYDRONIC PIPING. 5. FIRE SEAL NEW PIPE PENETRATIONS, CONCRETE INFILL, SEAL WITH INTUMESCENT SEALER, TYP. REF. SHEET 10/G-007. 6. NEW RAILING TO BE INSTALLED NEW 8" CMU 2-HR RATED WALL 4000 PSI CONCRETE 14 GAUGE L6X6 POUR STOP AT NEW DOOR #005 7 5/8" A. ALL CMU SHALL BE 1 OR 2-CELL BLOCK. B. MASONRY DESIGN STRENGTH, F'm = 1,5000 psi C. MINIMUM MORTAR COMPRESSIVE STRENGTH SHALL BE 1,800 psi AT 28 DAYS. D. VERTICAL CELLS TO BE FILLED SHALL HAVE VERTICAL ALIGNMENT SUFFICIENT TO MAINTAIN A CLEAR UNOBSTRUCTED CONTINUOUS VERTICAL CELL NOT LESS THAN 2 INCHES BY 3 INCHES IN PLAN DIMENSION. E. SLAB DOWELS SHALL MATCH VERTICAL REINFORCEMENT. F. VERTICAL WALL REINFORCEMENT SHALL BE #4 BARS @ 48" O.C. IN 8" WALLS. VERTICAL REINFORCING SHALL EXTEND CONTINUOUSLY FROM THE TOP OF THE SLAB TO EMBED AT LEAST 6 INCHES INTO TOP OF BOND BEAM. G. BOND BEAM REINFORCING SHALL USE (2) #4 BARS AND SHALL RUN CONTINUOUS THROUGHOUT. CORNER BARS SHALL BE PROVIDED AND LAP SLICES OF 40 BAR DIAMETERS PERMITTED. BOND BEAMS SHALL EXIST AT THE BOTTOM, TOP, AND INTERMEDIATE (EVERY 6TH COURSE OR CLOSER PER DETAILS) COORDINATE WITH ARCHITECTURAL REQUIREMENTS. H. ADD ADDITIONAL VERTICAL BAR OF THE SAME SIZE AND LENGTH AS THE NORMAL REINFORCING BAR SHALL BE PLACED University of Central Oklahoma Murdaugh Hall Renovation 2'-7" STRUCTURAL NOTES ARCHITECTURAL KEYNOTES NEW DOORWAY BEYOND DOOR #005 C 5 GENERAL NOTES 4 T 3 2 ST A 1 REVISION HISTORY: S04 2-HR G1 C FIRE PUMP ROOM 005 C 011C RESTROOM 011C ELECTRICAL 004C W W W 020A 2 1 TORNADO SHELTER 017 ADDENDUM 002 04/18/16 DESCRIPTION DATE PROJECT INFORMATION: DESIGNED BY: BDF W D W D W D HYDRONIC PUMP RM 004B W D E1 W W 2 AE103 ELECTRICAL CLOSET 004A W DRAWN BY: LGN CRAWL SPACE 178 A REVIEWED BY: MJW A 3 5 6 7 8 9 1 10 11 12 13 14 019 017 20141700 BASEMENT FLOOR PLAN BASEMENT FLOOR PLAN 018 KITCHENETTE 019 SCALE: 1/8" = 1'-0" BIKE SHOP 018 ISSUE DATE: D N 0 1 3 4 15 2 3 4 16 17 18 5 4" 8" 1'-4" 03/30/16 SHEET NUMBER: 0 2 TJC SHEET TITLE: D 1 PROJECT MANAGER: PROJECT NUMBER: REF. C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt LAUNDRY 020 4' 8' 16' AE103 E1 ALN MECH. 101A 2-HR D1 DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM CORR. HK CLOSET MECHANICAL CLOSET 2-HR ALN Room Number CORR. MECHANICAL CLOSET HOUSEKEEPING CLOSET RA OFFICE RA DIRECTOR STAFF OFFICE HOUSEKEEPING CLOSET TPHONE CLOSET MECH. CORR. STAIR DORM CRAWL SPACE CRAWL SPACE CORR. BONUS DORM ROOM 126 124 123A 100F 100D 101A H200 S04 158 167 178 024 123A 124 124A 123B 123C 123D 144A 140 141B 130 130A 161A 130B H171 H172 H173 H174 S12B Room Name BONUS DORM ROOM RR RR Room Room RR HALL DIRECTOR APARTMENT RR LOUNGE GAME ROOM MECH. MECH. CORR. CORR. CORR. CORR. STAIR D1 2 AE113 MEN'S RR 118 TYP. ENLARGED MECHANICAL CLOSET - TYPICAL 3 SCALE: 3/8" = 1'-0" 1 3 2 ALN DN 2-HR NEW PARTITION - 2 HR RATED 1-HR NEW PARTITION - 1 HR RATED 9 8 10 11 12 14 15 16 17 DN 15 9 166 1 164 E1 E1 15 A C1 122 165 3 AE114 4'-6" 11 12 121 9 H101 WEST CORRIDOR D1 163 7 C1 120 2 AE113 2 AE113 3 AE104 2 AE104 119 H101 7 PLAZA 101A 168 162 2 ALN E1 ALN 9 MECH. 161A C1 TYPICAL DORM ROOM D1 161A E1 AE112 A2 UP 143A UP 141B 7 9 141A S13 141A E1 13 10 2 11 152 D A RCH IT 2'-1 3/4" 113 B 9 F1 111 C1 109 123B REVISION HISTORY: 123 7 151 6'-0" 6" ALN SE DN 123A 7 E1 S13 4'-9" 130B S12 5'-9" 10 5 B C1 100E 143 4'-7" TYPICAL DORM ROOM 3 7 100D UP 11 2 11 1 124A 100F 13 10 E1 DN 154 130 100A 100A 9 11 8 124 126 10 100C 100B F1 C1 1'-4" 2 AE113 100D F1 C1 6 128 115 16 161A E1 C1 140 3 144A 161A 156 UP 3 144 C1 6 ALN 4/15/2016 5:00:49 PM A2 A2 11 4 10 4'-6" E1 2 2 AE113 10 A2 E1 9 158 ALN 9 7 E1 RR 144A 117 C1 11 12 3'-5" C1 5 B 8 9 7 160 SHOWER 1 AE114 ALN 10 5 1 11 161 1'-0" D1 TYPICAL DORM ROOM 1 118 EAST CORRIDOR ALN C1 E1 PHILIP G. McNAYR 2134 EN C C1 4 10 11 H EXISTING WALL C1 1'-0" 2 AE113 O F O K LA NEW PARTITION DN C1 E1 B 7 5 1 11 TYPICAL SHOWER / RESTROOM E1 D E ARCHITECTURAL LEGEND DN 2-HR 9 C1 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com 18 TYPICAL DORM ROOM TYP. 4 DN ALN E1 Frankfurt Short Bruza Architects Engineers Planners 10 1 11 3 2 2-HR 5'-5" 5 1. PLASTER PATCH BACKSIDE OF WALL AFTER THE INSTALLATION OF NEW PLUMBING PIPING. REPAIR AND PATCH CERAMIC TILE 2. PLASTER PATCH BACKSIDE OF WALL AFTER THE INSTALLATION OF NEW PLUMBING PIPING 3. EXISTING INCINERATOR TO CONTAIN FIRESTOP SILICONE SEALANT, SELF LEVELING. REF. SHEET 10/G-007. 4. INSTALL NEW VANITY AND COMBINATION MIRROR/MEDICINE CABINET 5. NEW TERRAZZO PRECAST COVE BASE - TO MATCH 1 BASE BUILDING 6. MOCKUP DORM ROOM #154 & #156 7. NEW ACCESS PANEL WITH TAMPER PROOF SCREWS. ACCESS PANEL TO BE INSTALLED WITH "BEST LOCKING SYSTEM" PER OWNER REQUEST. 8. EXISTING WATERCOOLER TO BE REINSTALLED. 9. CORRIDOR PORTAL, REF. SHEET 4/AE113 & 8/AE113 FOR SECTIONS AND DETAILS. 10.SEAL ALL NEW PIPE PENETRATIONS, CONCRETE 1 INFILL, SEAL WITH INTUMESCENT SEALER, TYP. REF. SHEET 10/G-007. 11.SURROUNDING WALLS, FLOORING AND TERRAZZO COVE BASE TO BE REPAIRED AND CLEANED. NEW TILE TO MATCH EXISTING 12.GYPSUM BOARD FURROUT TO CONCEAL NEW PLUMBING PIPING. FURROUT TO BEGIN 30" AFF. TILE TO MATCH EXISTING 13.GYPSUM BOARD FURROUT TO CONCEAL NEW HYDRONIC PIPING. 14.NOT USED 15.TERRAZZO TO BE PATCHED. MATCH EXISTING. 16.REINSTALL EXISTING CARPET TILE 2-HR 6'-0" 11 10 5 1 6" 2 AE113 2-HR TYPICAL DORM ROOM 2 TYP. AE113 D1 10 5 MECH. 168 2'-2" TYP. A. DRAWINGS ARE ONLY AN APPROXIMATION OF EXISTING CONDITIONS. GENERAL CONTRACTOR SHALL VISIT SITE AND EXAMINE EXISTING STRUCTURE, NOTE ALL CONDITIONS AS TO CHARACTER AND EXTENT OF WORK INVOLVED, VERIFY ALL DIMENSIONS PRIOR TO LAYOUT AND NOTIFY ARCHITECT OF ANY DISCREPANCIES, BEFORE STARTING ANY WORK. B. GENERAL CONTRACTOR SHALL COORDINATE ALL TRADE REQUIREMENTS AND REPORT CONFLICTS IMMEDIATELY IF FOUND. THE GENERAL CONTRACTOR SHALL VERIFY ALL DIMENSIONAL DATA AND LOCATIONS OF ALL OPENINGS AND EQUIPMENT TO REMAIN. DISCONNECT ANY ELECTRIC, GAS, WATER, OR OTHER LINES SERVICING THE EQUIPMENT PER RULES AND REGULATIONS OF AUTHORITIES HAVING JURISDICTION BEFORE ANY WORK IS TO PROCEED. C. GENERAL CONTRACTOR TO REPAIR EXISTING CONSTRUCTION, AS REQUIRED, TO MATCH ADJACENT CONSTRUCTION IN QUALITY, SIZE, TEXTURE, AND FINISH, WHERE DAMAGED BY DEMOLITION WORK.ALL DRYWALL AND PLASTER WALLS AND CEILING TO RECEIVE NEW PAINT; LEVEL ONE, TWO AND THREE D. ALL INTERIOR DIMENSIONS ARE TO FACE OF STUDS AND CONCRETE MASONRY UNLESS NOTED OTHERWISE. 4 E1 2'-2" 4 10 C H100 100C 100A Room Name C D1 141A 143 S13 128 S12 123 122 120 118 108 106 104 102 101 103 105 107 109 111 113 115 117 119 121 H101 100E 100B Room Number LI MECH. SHAFT 2-HR 2'-10" 2-HR DORM MEN'S RR MECH. DORM DORM HALL DIRECTOR APARTMENT BONUS DORM ROOM BONUS DORM ROOM STAIR FRONT DESK STAIR BONUS DORM ROOM DORM DORM MEN'S RR DORM Room Name Edmond, Oklahoma 2'-5" Room Number A 1'-2 1/2" D1 151 161 168 163 165 144 Room Name ARCHITECTURAL KEYNOTES FIRST LEVEL ROOMS OM D DORM DORM DORM DORM DORM CORR. DORM DORM DORM DORM DORM DORM CORR. DORM DORM DORM Room Number FIRST LEVEL ROOMS University of Central Oklahoma Murdaugh Hall Renovation E1 260 166 164 162 160 H169 156 154 152 150 148 146 H167 145 147 149 Room Name FIRST LEVEL ROOMS T Room Number FIRST LEVEL ROOMS EC FIRST LEVEL ROOMS 5 GENERAL NOTES 4 T 3 2 ST A 1 2 11 C H101 108 107 9 130A C1 C1 9 ALN TYPICAL DORM ROOM 11 E1 5 10 TYPICAL DORM ROOM E1 148 4 10 E1 E1 9 4 10 106 147 5 C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt 8 9 10 11 12 13 104 14 2 1 04/18/16 DESCRIPTION DATE PROJECT INFORMATION: 103 DESIGNED BY: BDF DRAWN BY: 9 145 1 FIRST FLOOR PLAN LGN 9 102 REVIEWED BY: 101 MJW C1 SCALE: 3/32" = 1'-0" C1 D DN ADDENDUM 002 C1 C1 A 7 C1 146 C1 6 105 EAST CORRIDOR C 149 WEST CORRIDOR 150 5 15 DN A PROJECT MANAGER: TJC PROJECT NUMBER: 15 20141700 SHEET TITLE: 2 ENLARGED FLOOR PLAN TYPICAL - FIRST FLOOR DN 1 SCALE: 3/16" = 1'-0" 2 FIRST FLOOR PLAN DN 3 4 15 16 17 18 0 1'-4" 2'-8" 5'-4" ISSUE DATE: N 0 2 3 4 5 10'-8" 03/30/16 SHEET NUMBER: 0 1 2'-8" 5'-4" 5'-4" 10'-8" 21'-4" AE104 2-HR MEN'S RR 261 5 SCALE: 3/8" = 1'-0" 12 13 14 Frankfurt Short Bruza Architects Engineers Planners 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com D 3 2-HR NEW PARTITION - 2 HR RATED 1-HR NEW PARTITION - 1 HR RATED 4 7 5 9 8 10 11 12 14 15 16 17 C 5'-9" 6'-0" 9 DN UP CLOSET F1 E1 A 7 2 9 C1 9 266 C1 265 222 221 C1 4 10 5 10 5 BATHROOM 12 C1 TYPICAL DORM ROOM TYPICAL DORM ROOM W/ PRIVATE BATHROOM 11 11 264 263 4 AE105 7 220 E1 7 ALN E1 ALN 262 201A 217 E1 1 7 17 260 261 D1 C1 6" 254 A2 C1 CLOSET 9 E1 CLOSET CLOSET 224 C1 9 H200 C1 239 237 B C1 A2 A2 9 9 C1 C1 CENTER CORRIDOR 9 9 C1 C1 218A A2 3 235 233 231 229 227 225 9 211 7 2'-9" 243 213 218A 9 CENTER CORRIDOR 8 1 11 F1 F1 UP REVISION HISTORY: 209 H201 2 11 3 AE105 208 207 C1 9 2 AE105 249 206 204 6 5 247 7 8 9 10 11 12 13 14 205 1 1 C1 9 246 5 DESCRIPTION DATE DESIGNED BY: BDF 203 DRAWN BY: C1 LGN SECOND FLOOR PLAN MJW A 9 SCALE: 1" = 10'-0" 245 C1 202 201 C1 PROJECT MANAGER: TJC PROJECT NUMBER: 20141700 SHEET TITLE: SECOND FLOOR PLAN 5 13 UP DN ENLARGED FLOOR PLAN TYPICAL ONE - SECOND FLOOR 1 2 14 3 DN 4 15 16 14 UP 17 N 2 3 4 5 ISSUE DATE: 18 0 SCALE: 1/4" = 1'-0" 1 04/18/16 PROJECT INFORMATION: D 2 ADDENDUM 002 REVIEWED BY: ALN ALN IT C1 S21 223 7 9 TYPICAL DORM ROOM E1 226 234A 6 C1 248 A D A RCH 4 11 CORRIDOR 228 9 250 5'-9" 6'-0" 230 232 251 252 13 TYP. 3'-0" C1 234 241 H202 11 A2 A2 F1 261A S22 C TYPICAL DORM ROOM 236 D1 2'-7" 5 13 3 7 2 UP 11 WEST CORRIDOR CLOSET C1 238 215 9 7 EAST CORRIDOR 4/15/2016 5:01:01 PM 256 240 D1 261A 9 242 244 11 1 8 4 ALN C1 D1 ALN 258 E1 218 11 1 12 2 2 SCALE: 1/4" = 1'-0" C E1 D1 ALN ENLARGED FLOOR PLAN TYPICAL TWO - SECOND FLOOR 2'-6" 1 4'-6" 4'-6" 11 12 D1 B 1'-0" 9 1'-0" C1 3 11 11 261 C B 219 5 AE105 202A 3 14 EAST CORRIDOR CLOSET ALN ALN E1 CLOSET ALN CLOSET UP DN 14 3 C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt C 18 C1 SE EXISTING WALL C1 CORRIDOR PHILIP G. McNAYR 2134 EN 15 2 H NEW PARTITION SCALE: 3/8" = 1'-0" 1 O F O K LA ARCHITECTURAL LEGEND ENLARGED MECHANICAL CLOSET 201A 3'-0" TYP. E T 1. PLASTER PATCH BACKSIDE OF WALL AFTER THE INSTALLATION OF NEW PLUMBING PIPING. REPAIR AND PATCH CERAMIC TILE 2. PLASTER PATCH BACKSIDE OF WALL AFTER THE INSTALLATION OF NEW PLUMBING PIPING 3. EXISTING INCINERATOR TO CONTAIN FIRESTOP SILICONE SEALANT, SELF LEVELING. REF. SHEET 10/G-007. 4. INSTALL NEW VANITY AND COMBINATION MIRROR/MEDICINE CABINET 5. NEW TERRAZZO PRECAST COVE BASE - TO MATCH 1 BASE BUILDING 6. ENLARGED PLUMBING CHASE 7. NEW ACCESS PANEL WITH TAMPER PROOF SCREWS. ACCESS PANEL TO BE INSTALLED WITH "BEST LOCKING SYSTEM" PER OWNER REQUEST. 8. EXISTING WATERCOOLER TO BE REINSTALLED 9. CORRIDOR PORTAL, REF. SHEET 4/AE113 & 8/AE113 FOR SECTIONS AND DETAILS 10.SEAL ALL NEW PIPE PENETRATIONS, CONCRETE INFILL, SEAL WITH INTUMESCENT SEALER, TYP. REF. SHEET 10/G-007. 11.SURROUNDING WALLS, FLOORING AND TERRAZZO COVE BASE TO BE REPAIRED AND CLEANED. NEW TILE TO MATCH EXISTING. 12.GYPSUM BOARD FURROUT TO CONCEAL NEW PLUMBING PIPING. FURROUT TO BEGIN 30" AFF. NEW TILE TO MATCH EXISTING. 13.NOT USED 1 14.TERRAZZO TO BE PATCHED. MATCH EXISTING. DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM CORR. MECH. STAIR STAIR CORR. H.C. MECH. D1 ENLARGED MECHANICAL CLOSET 202A 4 D1 204 202 201 203 205 207 209 211 215 217 219 221 222 220 H201 201A S21 S04 024 234A 218A A. DRAWINGS ARE ONLY AN APPROXIMATION OF EXISTING CONDITIONS. GENERAL CONTRACTOR SHALL VISIT SITE AND EXAMINE EXISTING STRUCTURE, NOTE ALL CONDITIONS AS TO CHARACTER AND EXTENT OF WORK INVOLVED, VERIFY ALL DIMENSIONS PRIOR TO LAYOUT AND NOTIFY ARCHITECT OF ANY DISCREPANCIES, BEFORE STARTING ANY WORK. B. GENERAL CONTRACTOR SHALL COORDINATE ALL TRADE REQUIREMENTS AND REPORT CONFLICTS IMMEDIATELY IF FOUND. THE GENERAL CONTRACTOR SHALL VERIFY ALL DIMENSIONAL DATA AND LOCATIONS OF ALL OPENINGS AND EQUIPMENT TO REMAIN. DISCONNECT ANY ELECTRIC, GAS, WATER, OR OTHER LINES SERVICING THE EQUIPMENT PER RULES AND REGULATIONS OF AUTHORITIES HAVING JURISDICTION BEFORE ANY WORK IS TO PROCEED. C. GENERAL CONTRACTOR TO REPAIR EXISTING CONSTRUCTION, AS REQUIRED, TO MATCH ADJACENT CONSTRUCTION IN QUALITY, SIZE, TEXTURE, AND FINISH, WHERE DAMAGED BY DEMOLITION WORK.ALL DRYWALL AND PLASTER WALLS AND CEILING TO RECEIVE NEW PAINT; LEVEL ONE, TWO AND THREE D. ALL INTERIOR DIMENSIONS ARE TO FACE OF STUDS AND CONCRETE MASONRY UNLESS NOTED OTHERWISE. Edmond, Oklahoma MECH. SHAFT 2-HR 2'-10" 2-HR MECH. SHAFT 2-HR D1 2-HR DORM DORM DORM DORM DORM DORM MEN'S RR MECH. MECH DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM MEN'S RR DORM DORM Room Name University of Central Oklahoma Murdaugh Hall Renovation 2'-5" D1 2-HR 2-HR 2'-10" 1'-1 1/2" 229 227 225 223 265 263 261 202A 261A 244 242 240 238 236 234 232 230 228 226 224 218 208 206 Room Number A D1 D1 2'-5" 1'-1 1/2" 2-HR D1 D1 DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM CORR. DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM Room Name C MECH. 201A MECH. 202A Room Number OM D Room Name ARCHITECTURAL KEYNOTES SECOND LEVEL ROOMS LI 213 266 264 262 258 256 254 252 250 248 246 H202 245 247 249 251 243 241 239 237 235 233 231 SECOND LEVEL ROOMS EC SECOND LEVEL ROOMS Room Number 5 GENERAL NOTES 4 T 3 2 ST A 1 1'-4" 2'-8" 5'-4" 03/30/16 SHEET NUMBER: 0 2' 4' 8' 0 . 10' 20' AE105 EXISTING WALL MECH. 301A D1 2-HR 2-HR 2-HR 2'-8 3/4" 2-HR 2-HR D1 D1 MEN'S RR 318 ENLARGED MECHANICAL CLOSET 301A 4 D1 SCALE: 3/8" = 1'-0" MEN'S RR 361 ENLARGED MECHINCAL CLOSET 302A 5 SCALE: 3/8" = 1'-0" 1 12 13 14 2 3 4 5 7 8 9 10 O F O K LA H PHILIP G. McNAYR 2134 A D1 MECH. SHAFT D E EN C MECH. SHAFT D1 2-HR 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com OM CORR. H302 2-HR D1 NEW PARTITION - 1 HR RATED 1'-1 1/2" 2'-2" CORR. H301 2-HR 2'-2" D 1-HR MECH. 302A D1 1'-1 1/2" NEW PARTITION - 2 HR RATED Frankfurt Short Bruza Architects Engineers Planners LI 1. PLASTER PATCH BACKSIDE OF WALL AFTER THE INSTALLATION OF NEW PLUMBING PIPING. REPAIR AND PATCH CERAMIC TILE 2. PLASTER PATCH BACKSIDE OF WALL AFTER THE INSTALLATION OF NEW PLUMBING PIPING 3. EXISTING INCINERATOR TO CONTAIN FIRESTOP SILICONE SEALANT, SELF LEVELING. REF. SHEET 10/G-007 4. INSTALL NEW VANITY AND COMBINATION MIRROR/MEDICINE CABINET 5. NEW TERRAZZO PRECAST COVE BASE - TO MATCH BASE BUILDING 1 6. NEW ACCESS PANEL WITH TAMPER PROOF SCREWS. ACCESS PANELS TO BE INSTALLED WITH "BEST LOCKING SYSTEM" PER OWNER REQUEST. 7. EXISTING WATERCOOLER TO BE REINSTALLED 8. CORRIDOR PORTAL, REF. SHEET 4/AE113 & 8/AE113 FOR SECTIONS AND DETAILS. 9. SEAL ALL NEW PIPE PENETRATIONS, CONCRETE 1 INFILL, SEAL WITH INTUMESCENT SEALER, TYP. REF. SHEET 10/G-007 10.SURROUNDING WALLS, FLOORING AND TERRAZZO COVE BASE TO BE REPAIRED AND CLEANED. NEW TILE TO MATCH EXISTING. 11.GYPSUM BOARD FURROUT TO CONCEAL NEW PLUMBING PIPPING. FURROUT TO BEGIN 30" AFF. NEW TILE TO MATCH EXISTING. 12.NOT USED 13.TERRAZZO TO BE PATCHED. MATCH EXISTING. 16 A. DRAWINGS ARE ONLY AN APPROXIMATION OF EXISTING CONDITIONS. GENERAL CONTRACTOR SHALL VISIT SITE AND EXAMINE EXISTING STRUCTURE, NOTE ALL CONDITIONS AS TO CHARACTER AND EXTENT OF WORK INVOLVED, VERIFY ALL DIMENSIONS PRIOR TO LAYOUT AND NOTIFY ARCHITECT OF ANY DISCREPANCIES, BEFORE STARTING ANY WORK. B. GENERAL CONTRACTOR SHALL COORDINATE ALL TRADE REQUIREMENTS AND REPORT CONFLICTS IMMEDIATELY IF FOUND. THE GENERAL CONTRACTOR SHALL VERIFY ALL DIMENSIONAL DATA AND LOCATIONS OF ALL OPENINGS AND EQUIPMENT TO REMAIN. DISCONNECT ANY ELECTRIC, GAS, WATER, OR OTHER LINES SERVICING THE EQUIPMENT PER RULES AND REGULATIONS OF AUTHORITIES HAVING JURISDICTION BEFORE ANY WORK IS TO PROCEED. C. GENERAL CONTRACTOR TO REPAIR EXISTING CONSTRUCTION, AS REQUIRED, TO MATCH ADJACENT CONSTRUCTION IN QUALITY, SIZE, TEXTURE, AND FINISH, WHERE DAMAGED BY DEMOLITION WORK.ALL DRYWALL AND PLASTER WALLS AND CEILING TO RECIEVE NEW PAINT; LEVEL ONE, TWO AND THREE D. ALL INTERIOR DIMENSIONS ARE TO FACE OF STUDS AND CONCRETE MASONRY UNLESS NOTED OTHERWISE. T ARCHITECTURAL KEYNOTES NEW PARTITION 2-HR 5 GENERAL NOTES EC 4 ARCHITECTURAL LEGEND T 3 2 ST A 1 SE D A RCH IT 17 15 DN 18 C1 3 6 CLOSET C1 8 363 5 AE106 364 E1 362 1 C1 E1 1 10 TYPICAL DORM ROOM W/ PRIVATE BATHROOM 360 4'-6" E1 10 E1 11 361 D1 B 7 D1 H302 C1 C1 358 6 C 8 356 C1 ENLARGED FLOOR PLAN TYPICAL TWO - THIRD FLOOR C1 CLOSET 4/15/2016 5:01:13 PM C A2 361A 361A A2 3 6 F1 354 2 342 340 338 336 334 332 330 328 326 C1 8 8 8 C1 C1 C1 C1 334B C1 H300 8 C1 8 C1 C1 8 C1 C1 6" 315 D1 B D1 7 324 1 10 318 318A 3 6 318A C1 313 C1 8 C1 C1 311 1 2 C1 8 1 DN D1 S31 343 341 339 337 335 333 331 329 327 325 DN 10 323 6 352 E1 11 10 1 D1 A2 C E1 6 1 10 2'-1 3/4" 2 344 S34 4 C1 C1 E1 4'-6" 2 SCALE: 1/4" = 1'-0" 3 10 317 E1 8 1 318 1 8 C1 6 10 B 6 C 319 4 AE106 301A 361 1 10 3 E1 6 320 302A BATHROOM TYPICAL DORM ROOM 321 C1 CLOSET 9 5 5 322 C1 ALN ALN ALN E1 365 C1 8 CLOSET 4 9 8 366 F1 E1 C1 C1 309 H301 C 6 351 8 C1 308 B 307 C1 5 9 350 349 306 305 Edmond, Oklahoma 5'-9" TYP. A2 1'-0" CLOSET A 1'-0" C 6'-0" CORRIDOR 13 A 318A 3'-0" TYP. DN 13 University of Central Oklahoma Murdaugh Hall Renovation DN REVISION HISTORY: TYPICAL DORM ROOM 348 10 CLOSET 6'-0" 5'-9" TYP. ALN 6 7 8 9 8 C1 E1 3'-0" TYP. 5 10 11 12 13 304 14 303 8 C1 4 346 9 1 345 C1 C1 C1 8 THIRD FLOOR PLAN 302 301 C1 C1 SCALE: 3/32" = 1'-0" D CLOSET 8 347 C1 D DN 13 13 DN 2 1 1 TYPICAL DORM ROOM 2 DN 3 4 15 16 DN 17 CLOSET 04/18/16 DESCRIPTION DATE 18 PROJECT INFORMATION: DESIGNED BY: 10 BDF THIRD LEVEL ROOMS E1 ALN ADDENDUM 002 Room Number 5 THIRD LEVEL ROOMS Room Name Room Number Room Name THIRD LEVEL ROOMS Room Number THIRD LEVEL ROOMS Room Name Room Number Room Name THIRD LEVEL ROOMS Room Number DRAWN BY: LGN Room Name REVIEWED BY: C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt MJW A 318 H300 S31 H301 317 361 362 356 311 H302 S34 366 364 360 358 354 E1 ALN 2 5 9 ENLARGED FLOOR PLAN TYPICAL ONE - THIRD FLOOR SCALE: 1/4" = 1'-0" 1 2 MEN'S RR CORR. STAIR CORR. DORM MEN'S RR DORM DORM DORM CORR. STAIR DORM DORM DORM DORM DORM 352 350 348 346 345 347 349 351 343 341 339 337 335 333 331 329 3 DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM 327 325 323 308 306 304 302 301 303 305 307 309 313 315 319 321 DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM 322 320 301A 324 318A 326 328 330 332 334 336 338 340 342 344 361A 4 DORM DORM MECH. DORM MECH. DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM MECH. 363 365 302A S04 024 334B DORM DORM MECH. STAIR CORR. H.C. A PROJECT MANAGER: TJC PROJECT NUMBER: 20141700 SHEET TITLE: THIRD FLOOR PLAN 0 N 5 1'-4" 2'-8" 5'-4" 0 2' 4' 8' 0 . 10' 20' ISSUE DATE: 03/30/16 SHEET NUMBER: AE106 3 4 DORM MEN'S RR MECH. DORM DORM HALL DIRECTOR APARTMENT BONUS DORM ROOM BONUS DORM ROOM STAIR FRONT DESK STAIR BONUS DORM ROOM DORM DORM MEN'S RR DORM 141A 143 S13 128 S12 123 122 120 118 108 7 5 106 104 102 101 103 105 107 109 111 113 115 117 119 121 H101 100E 100B Room Name DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM CORR. HK CLOSET MECHANICAL CLOSET 9 8 Room Number H100 100C 100A 126 124 123A 100F 100D 101A H200 S04 158 167 178 024 123A 10 Room Name Room Number CORR. MECHANICAL CLOSET HOUSEKEEPING CLOSET RA OFFICE RA DIRECTOR STAFF OFFICE HOUSEKEEPING CLOSET TPHONE CLOSET MECH. CORR. STAIR DORM CRAWL SPACE CRAWL SPACE CORR. BONUS DORM ROOM 11 124 124A 123B 123C 123D 144A 140 BONUS DORM ROOM RR RR Room Room RR HALL DIRECTOR APARTMENT RR LOUNGE GAME ROOM MECH. MECH. CORR. CORR. CORR. CORR. STAIR 141B 130 130A 161A 130B H171 H172 H173 H174 S12B 12 Room Name 14 1. SUSPENDED LIGHT FIXTURES, ADD SUPPORT AS REQUIRED, TYP. REFERENCE SHEET 1/EL101 FOR LIGHT FIXTURE PLACEMENT. 2. EXISTING BEAMS LOCATED WITHIN MAIN LOBBY, TO BE REPAIRED, CLEANED AND PAINTED. 3. DEMO'D TIN CEILING TILES TO BE REUSED AT NEW FURR DOWN. 4. 5/8" MOISTURE RESISTANT GYP BD CEILING, FINISH & PAINT PER FINISH SCHEDULE. 5. GYP BD CEILING ON SUSPENDED SYSTEM 1 BETWEEN EXISTING COFFER BEAM. 6. FURR DOWN TO ENCLOSE DUCTWORK. 7. ACCESS PANEL WITH TAMPER PROOF SCREWS. TO BE INSTALLED WITH "BEST LOCKING SYSTEM" PER OWNER REQUEST. 8. DRYWALL FURR DOWN STAIR LANDING CEILING 15 5 AE113 16 17 A. DRAWINGS ARE ONLY AN APPROXIMATION OF EXISTING CONDITIONS. GENERAL CONTRACTOR SHALL VISIT SITE AND EXAMINE EXISTING STRUCTURE, NOTE ALL CONDITIONS AS TO CHARACTER AND EXTENT OF WORK INVOLVED, VERIFY ALL DIMENSIONS PRIOR TO LAYOUT AND NOTIFY ARCHITECT OF ANY DISCREPANCIES, BEFORE STARTING ANY WORK. B. GENERAL CONTRACTOR SHALL COORDINATE ALL TRADE REQUIREMENTS AND REPORT CONFLICTS IMMEDIATELY IF FOUND. THE GENERAL CONTRACTOR SHALL VERIFY ALL DIMENSIONAL DATA AND LOCATIONS OF ALL OPENINGS AND EQUIPMENT TO REMAIN. DISCONNECT ANY ELECTRIC, GAS, WATER, OR OTHER LINES SERVICING THE EQUIPMENT PER RULES AND REGULATIONS OF AUTHORITIES HAVING JURISDICTION BEFORE ANY WORK IS TO PROCEED. C. GENERAL CONTRACTOR TO REPAIR EXISTING CONSTRUCTION, AS REQUIRED, TO MATCH ADJACENT CONSTRUCTION IN QUALITY, SIZE, TEXTURE, AND FINISH, WHERE DAMAGED BY DEMOLITION WORK.ALL DRYWALL AND PLASTER WALLS AND CEILING TO RECIEVE NEW PAINT; LEVEL ONE, TWO AND THREE D. ALL INTERIOR DIMENSIONS ARE TO FACE OF STUDS AND CONCRETE MASONRY UNLESS NOTED OTHERWISE. Frankfurt Short Bruza Architects Engineers Planners 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com D E O F O K LA H PHILIP G. McNAYR 2134 A 5 AE113 2 151 161 168 163 165 144 Room Number EN C 1 DORM DORM DORM DORM DORM CORR. DORM DORM DORM DORM DORM DORM CORR. DORM DORM DORM Room Name ARCHITECTURAL KEYNOTES FIRST LEVEL ROOMS OM D Room Number FIRST LEVEL ROOMS LI 260 166 164 162 160 H169 156 154 152 150 148 146 H167 145 147 149 Room Name FIRST LEVEL ROOMS T Room Number FIRST LEVEL ROOMS EC FIRST LEVEL ROOMS 5 GENERAL NOTES 4 T 3 2 ST A 1 SE D A RCH IT TYPICAL CEILING LEGEND DN 2' x 2' COFFERED CEILING TILE 7 A DN 7 8'-0" AFF MOISTURE RESISTANT GYPSUM BOARD CEILING 4' FLUORESCENT FIXTURE - STRIP 8'-0" AFF WALL MTD INTERIOR LIGHT EXIT SIGNS 122 166 GYP BD CEILING University of Central Oklahoma Murdaugh Hall Renovation DN 3'-4 1/4" 3'-4 1/2" 18 H101 121 165 LIGHT COVE DIFFUSER CROWN MOLDING C 163 WEST CORRIDOR 162 1 AE111 120 EAST CORRIDOR 164 2 AE111 C 2X2 SUPPLY DIFFUSER 119 RETURN REGISTER ACCESS DOORS 117 5 160 115 B 161 2 AE112 118 128 158 144 140 126 124 3 113 124A 144A 1 2 1'-0" 8'-6" AFF 156 3'-1" B 1'-0" 1 8'-6" AFF 130 1 8'-6" AFF 8'-6" AFF 100F 3'-1" 100E 154 S12 4 8'-4" AFF UP 143 141A DN DN 4'-9 1/4" 100B STAIR 4/15/2016 5:01:27 PM 111 100D 4 UP 109 123B 123 8'-4" AFF 123A 8 C B STAIR Edmond, Oklahoma DN H101 8 REVISION HISTORY: 8'-6" AFF 152 S13 151 6 108 107 106 105 3 AE113 EAST CORRIDOR 150 148 147 5 6 7 8 9 10 11 12 13 WEST CORRIDOR 130A 149 1 04/18/16 DESCRIPTION DATE PROJECT INFORMATION: DESIGNED BY: 103 104 14 ADDENDUM 002 LGN DRAWN BY: 1 REVIEWED BY: FIRST FLOOR - NEW CEILING PLAN MJW 145 146 D A SCALE: 1/8" = 1'-0" 102 8'-0" AFF 101 7 PROJECT MANAGER: TJC PROJECT NUMBER: 20141700 8'-0" AFF 3'-5" A 3'-5" C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt LGN SHEET TITLE: FIRST FLOOR - NEW CEILING PLAN 7 DN DN ISSUE DATE: DN 1 2 DN 3 4 15 16 03/30/16 17 18 N SHEET NUMBER: 0 4' 8' 16' AE108 1 2 3 4 5 DORM DORM DORM DORM DORM DORM MEN'S RR MECH. MECH DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM MEN'S RR DORM DORM 204 202 201 203 205 207 209 211 215 217 219 221 222 220 H201 201A S21 S04 024 234A 218A Room Name DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM CORR. MECH. STAIR STAIR CORR. H.C. MECH. 1 1. 5/8" MOISTURE RESISTANT GYP BD CEILING, FINISH & PAINT PER FINISH SCHEDULE. 2. 2' x 4' ACCESS PANEL WITH TAMPER PROOF SCREWS. ACCESS PANEL TO BE INSTALLED WITH "BEST LOCKING SYSTEM" PER OWNER REQUEST. 3. DRYWALL FURR DOWN STAIR LANDING CEILING. A. DRAWINGS ARE ONLY AN APPROXIMATION OF EXISTING CONDITIONS. GENERAL CONTRACTOR SHALL VISIT SITE AND EXAMINE EXISTING STRUCTURE, NOTE ALL CONDITIONS AS TO CHARACTER AND EXTENT OF WORK INVOLVED, VERIFY ALL DIMENSIONS PRIOR TO LAYOUT AND NOTIFY ARCHITECT OF ANY DISCREPANCIES, BEFORE STARTING ANY WORK. B. GENERAL CONTRACTOR SHALL COORDINATE ALL TRADE REQUIREMENTS AND REPORT CONFLICTS IMMEDIATELY IF FOUND. THE GENERAL CONTRACTOR SHALL VERIFY ALL DIMENSIONAL DATA AND LOCATIONS OF ALL OPENINGS AND EQUIPMENT TO REMAIN. DISCONNECT ANY ELECTRIC, GAS, WATER, OR OTHER LINES SERVICING THE EQUIPMENT PER RULES AND REGULATIONS OF AUTHORITIES HAVING JURISDICTION BEFORE ANY WORK IS TO PROCEED. C. GENERAL CONTRACTOR TO REPAIR EXISTING CONSTRUCTION, AS REQUIRED, TO MATCH ADJACENT CONSTRUCTION IN QUALITY, SIZE, TEXTURE, AND FINISH, WHERE DAMAGED BY DEMOLITION WORK.ALL DRYWALL AND PLASTER WALLS AND CEILING TO RECIEVE NEW PAINT; LEVEL ONE, TWO AND THREE D. ALL INTERIOR DIMENSIONS ARE TO FACE OF STUDS AND CONCRETE MASONRY UNLESS NOTED OTHERWISE. Frankfurt Short Bruza Architects Engineers Planners 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com D E O F O K LA H PHILIP G. McNAYR 2134 A 229 227 225 223 265 263 261 202A 261A 244 242 240 238 236 234 232 230 228 226 224 218 208 206 Room Number EN C DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM CORR. DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM Room Name T Room Number OM D Room Name ARCHITECTURAL KEYNOTES SECOND LEVEL ROOMS LI 213 266 264 262 258 256 254 252 250 248 246 H202 245 247 249 251 243 241 239 237 235 233 231 SECOND LEVEL ROOMS EC SECOND LEVEL ROOMS Room Number 5 GENERAL NOTES 4 T 3 2 ST A 1 SE D A RCH IT TYPICAL CEILING LEGEND 2' x 2' COFFERED CEILING TILE GYP BD CEILING MOISTURE RESISTANT GYPSUM BOARD CEILING UP 8'-0" AFF 4' FLUORESCENT FIXTURE - STRIP DN WALL MTD INTERIOR LIGHT 2 EXIT SIGNS 8'-0" AFF LIGHT COVE DIFFUSER 266 265 222 221 H201 CROWN MOLDING C C 2X2 SUPPLY DIFFUSER 264 263 WEST CORRIDOR RETURN REGISTER 220 202A 201A 219 262 ACCESS DOORS 217 EAST CORRIDOR 261 260 B 1 218 8'-0" AFF 215 8'-0" AFF 244 242 240 238 236 234 232 230 228 226 224 218 1 1 258 213 234A B CENTRAL CORRIDOR 261A 256 8'-0" AFF 8'-4" AFF 8'-0" AFF CENTRAL CORRIDOR 218A B 211 STAIR UP DN S21 1 254 1 8'-4" AFF 243 241 239 237 235 233 231 229 227 225 223 251 EAST CORRIDOR 252 250 208 207 206 249 248 REVISION HISTORY: 3 3 C 209 8'-4" AFF WEST CORRIDOR 4/15/2016 5:01:39 PM UP Edmond, Oklahoma A UP 5 AE113 University of Central Oklahoma Murdaugh Hall Renovation 2 5 AE113 3'-7" 3'-0 1/2" DN 247 5 6 7 8 9 10 11 12 13 205 1 04/18/16 DESCRIPTION DATE PROJECT INFORMATION: DESIGNED BY: LGN DRAWN BY: 204 14 ADDENDUM 002 LGN 203 REVIEWED BY: A 1 246 A SECOND FLOOR - NEW CEILING PLAN SCALE: 1/8" = 1'-0" 202 H201 SHEET TITLE: 201 SECOND FLOOR - NEW CEILING PLAN UP AE113 5 DN 3'-6" 8'-0" AFF 2 AE113 5 DN 2 ISSUE DATE: UP 03/30/16 SHEET NUMBER: N 1 2 3 1 4 15 2 TJC 20141700 8'-0" AFF D PROJECT MANAGER: PROJECT NUMBER: 245 3'-6" C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt MJW 3 16 4 17 0 18 5 4' 8' 16' AE109 4 7 5 DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM Room Name 327 325 323 308 306 304 302 301 303 305 307 309 313 315 319 321 DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM 9 8 Room Number 322 320 301A 324 318A 326 328 330 332 334 336 338 340 342 344 361A Room Name Room Number DORM DORM MECH. DORM MECH. DORM DORM DORM DORM DORM DORM DORM DORM DORM DORM MECH. 10 363 365 302A S04 024 334B Room Name DORM DORM MECH. STAIR CORR. H.C. 1. 5/8" MOISTURE RESISTANT GYP BD CEILING, FINISH & PAINT PER FINISH SCHEDULE. 2. 2' x 4' ACCESS PANEL WITH TAMPER PROOF SCREWS. ACCESS PANEL TO BE INSTALLED WITH "BEST LOCKING SYSTEM" PER OWNER REQUEST. 3. DRYWALL FURR DOWN STAIR LANDING CEILING 4". 4. 2' x 3' EXISTING ATTIC DOOR. DOOR LOCATIONS ARE APPROXIMATE, VERIFY IN FIELD. 1 11 12 14 15 16 17 A. DRAWINGS ARE ONLY AN APPROXIMATION OF EXISTING CONDITIONS. GENERAL CONTRACTOR SHALL VISIT SITE AND EXAMINE EXISTING STRUCTURE, NOTE ALL CONDITIONS AS TO CHARACTER AND EXTENT OF WORK INVOLVED, VERIFY ALL DIMENSIONS PRIOR TO LAYOUT AND NOTIFY ARCHITECT OF ANY DISCREPANCIES, BEFORE STARTING ANY WORK. B. GENERAL CONTRACTOR SHALL COORDINATE ALL TRADE REQUIREMENTS AND REPORT CONFLICTS IMMEDIATELY IF FOUND. THE GENERAL CONTRACTOR SHALL VERIFY ALL DIMENSIONAL DATA AND LOCATIONS OF ALL OPENINGS AND EQUIPMENT TO REMAIN. DISCONNECT ANY ELECTRIC, GAS, WATER, OR OTHER LINES SERVICING THE EQUIPMENT PER RULES AND REGULATIONS OF AUTHORITIES HAVING JURISDICTION BEFORE ANY WORK IS TO PROCEED. C. GENERAL CONTRACTOR TO REPAIR EXISTING CONSTRUCTION, AS REQUIRED, TO MATCH ADJACENT CONSTRUCTION IN QUALITY, SIZE, TEXTURE, AND FINISH, WHERE DAMAGED BY DEMOLITION WORK.ALL DRYWALL AND PLASTER WALLS AND CEILING TO RECIEVE NEW PAINT; LEVEL ONE, TWO AND THREE D. ALL INTERIOR DIMENSIONS ARE TO FACE OF STUDS AND CONCRETE MASONRY UNLESS NOTED OTHERWISE. Frankfurt Short Bruza Architects Engineers Planners 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com D E O F O K LA H PHILIP G. McNAYR 2134 A 3 2 352 350 348 346 345 347 349 351 343 341 339 337 335 333 331 329 Room Number EN C 1 MEN'S RR CORR. STAIR CORR. DORM MEN'S RR DORM DORM DORM CORR. STAIR DORM DORM DORM DORM DORM Room Name ARCHITECTURAL KEYNOTES THIRD LEVEL ROOMS OM D Room Number THIRD LEVEL ROOMS LI 318 H300 S31 H301 317 361 362 356 311 H302 S34 366 364 360 358 354 Room Name THIRD LEVEL ROOMS T Room Number THIRD LEVEL ROOMS EC THIRD LEVEL ROOMS 5 GENERAL NOTES 4 T 3 2 ST A 1 SE D A RCH IT TYPICAL CEILING LEGEND 2' x 2' COFFERED CEILING TILE 18 366 4' FLUORESCENT FIXTURE - STRIP 8'-0" AFF 3'-1 1/4" 8'-0" AFF 2 WALL MTD INTERIOR LIGHT EXIT SIGNS 365 322 H301 321 LIGHT COVE DIFFUSER CROWN MOLDING 364 320 363 302A 1 362 EAST CORRIDOR B 319 RETURN REGISTER ACCESS DOORS 317 301A 1 361 360 C 2X2 SUPPLY DIFFUSER WEST CORRIDOR C 315 361 318 1 358 344 342 340 338 336 334 332 330 328 326 324 313 1 H302 334B 7'-4 1/2" 4 356 H300 B 8'-0" AFF CENTRAL CORRIDOR 4 8'-4" AFF 8'-0" AFF CENTRAL CORRIDOR H300 311 B S34 1 354 329 4 343 341 339 337 335 333 331 327 325 323 S31 1 8'-4" AFF 3 3 C 351 349 EAST CORRIDOR 350 348 347 5 6 7 8 9 10 11 12 13 REVISION HISTORY: 308 307 306 305 WEST CORRIDOR 4/18/2016 7:27:27 PM 8'-4" AFF 352 309 1 ADDENDUM 002 04/18/16 DESCRIPTION DATE PROJECT INFORMATION: 304 14 Edmond, Oklahoma 2 A MOISTURE RESISTANT GYPSUM BOARD CEILING DN University of Central Oklahoma Murdaugh Hall Renovation 5 AE113 3'-6 1/4" 5 AE113 GYP BD CEILING DESIGNED BY: 303 LGN DRAWN BY: LGN 1 A 346 THIRD FLOOR - NEW CEILING PLAN MJW SCALE: 1/8" = 1'-0" H301 302 345 2 DN PROJECT MANAGER: TJC 20141700 8'-0" AFF AE113 5 SHEET TITLE: 3'-7 1/2" D A 301 PROJECT NUMBER: 8'-0" AFF 3'-1 1/2" C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt REVIEWED BY: THIRD FLOOR - NEW CEILING PLAN 2 DN AE113 5 ISSUE DATE: 03/30/16 1 2 3 4 15 16 17 18 N SHEET NUMBER: 0 4' 8' 16' AE110 1 2 3 4 5 5 GENERAL NOTES ARCHITECTURAL KEYNOTES Frankfurt Short Bruza Architects Engineers Planners 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com O F O K LA H PHILIP G. McNAYR 2134 A D E OM D 16. DEMO TRIM WHERE ABUTS PORTAL FURR DOWN 17. DEMO CHAIR RAIL WHERE ABUTS PORTAL FURR OUT 18. NEW GYP PORTAL AT FOREGROUND - PAINTED AND TEXTURED TO MATCH EXISTING. 19. EXISTING PLASTER WALL TO REMAIN 20. PORTAL BASE TO BE 1X6 OAK STOCK, FLAT AT RETURN, SCRIBE WOOD BASE TO MATCH COVE BASE. 21. EXISTING TERRAZZO COVE BASE TO REMAIN 22. NEW 3/4" X 5 1/4" CROWN MOLDING, STAIN TO MATCH BASE BUILDING FINISH 23. LIGHT COVE BEYOND 24. METAL STUD TO BE ATTTACHED WITH CONCRETE ANCHORS 25. HIGH PRESSURE LAMINATE DOORS AND TOEKICK 26. PULLS LI EN C 1. 5/8" GYP. BD ON 3 5/8" METAL STUDS @ 16" O.C. 2. FURR DOWN TO BE FINISHED AND PAINTED CEILING WHITE. ALL CORNERS TO HAVE CORNER BEAD, TAPE / BED, SAND AND PAINT. 3. SURFACE MOUNT LED DIRECT / INDIRECT LIGHT FIXTURE. REFERENCE ELECTRICAL SHEET EL501 LIGHTING FIXTURE SCHEDULE 4. FAN COIL UNIT ABOVE WITH INTEGRATED TELESCOPING BOTTOM PANEL 5. FURR OUT BEYOND 6. EXISTING MIRROR TO REMAIN 7. EXISTING SOLID SURFACE INTEGRAL SINK VANITY TO REMAIN 8. NEW SOLID SURFACE TOILET PARTITIONS 1 9. NEW VANITY WITH ROUND, UNDERMOUNT VITREOUS CHINA SINK & SOLID SURFACE COUNTERTOP, BACK SPLASH AND SIDE SPLASH 10.NEW RECESSED MOUNT, STAINLESS STEEL MEDICINE CABINET WITH MIRROR 11.NEW SURFACE MOUNT VANITY LIGHT - REFERENCE ELECTRICAL SHEET EL501 LIGHTING FIXTURE SCHEDULE 12.ELECTRICAL WITHIN NEW WOOD CHAIR RAIL 13.6" TERRAZZO COVE BASE TO REMAIN 14.PORTAL FURR OUT BEYOND 15.EXISITING CONCRETE BEAM A. DRAWINGS ARE ONLY AN APPROXIMATION OF EXISTING CONDITIONS. GENERAL CONTRACTOR SHALL VISIT SITE AND EXAMINE EXISTING STRUCTURE, NOTE ALL CONDITIONS AS TO CHARACTER AND EXTENT OF WORK INVOLVED, VERIFY ALL DIMENSIONS PRIOR TO LAYOUT AND NOTIFY ARCHITECT OF ANY DISCREPANCIES, BEFORE STARTING ANY WORK. B. GENERAL CONTRACTOR SHALL COORDINATE ALL TRADE REQUIREMENTS AND REPORT CONFLICTS IMMEDIATELY IF FOUND. THE GENERAL CONTRACTOR SHALL VERIFY ALL DIMENSIONAL DATA AND LOCATIONS OF ALL OPENINGS AND EQUIPMENT TO REMAIN. DISCONNECT ANY ELECTRIC, GAS, WATER, OR OTHER LINES SERVICING THE EQUIPMENT PER RULES AND REGULATIONS OF AUTHORITIES HAVING JURISDICTION BEFORE ANY WORK IS TO PROCEED. C. GENERAL CONTRACTOR TO REPAIR EXISTING CONSTRUCTION, AS REQUIRED, TO MATCH ADJACENT CONSTRUCTION IN QUALITY, SIZE, TEXTURE, AND FINISH, WHERE DAMAGED BY DEMOLITION WORK.ALL DRYWALL AND PLASTER WALLS AND CEILING TO RECIEVE NEW PAINT; LEVEL ONE, TWO AND THREE D. ALL INTERIOR DIMENSIONS ARE TO FACE OF STUDS AND CONCRETE MASONRY UNLESS NOTED OTHERWISE. T ARCHITECTURAL KEYNOTES EC 4 T 3 2 ST A 1 SE D A RCH IT 8'-4" AFF C 2 3'-1" 22 23 22 24 23 5'-10" C 2 3'-1" SECTION - PORTAL CEILING TRANSITION SCALE: 1" = 1'-0" 24 22 23 1'-3" 24 8'-0" AFF 22 1 6 24 2 2 16 16 1 1/2" CONTINUOUS SEALANT 3/4" 16 1 17 17 17 18 18 5 1/4" 17 ELEC COVER PLATE BEYOND 19 MC CABLE REF. SHEET EP401 FOR NUMBER OF RECEPTACLES PER RACEWAY BLOCKING 19 21 B 4/15/2016 5:01:58 PM 20 3 21 19 3'-1" 1X6 STAIN TO MATCH EXISTING WOOD FINISH THRU-OUT DORMATORY GROUND FLOOR 21 100'-0" 21 19 20 1/2" ELEVATION - TYPICAL CORRIDOR PORTAL AT 1ST, 2ND AND 3RD 4 SCALE: 1/2" = 1'-0" 1 3/4" B CONTINUOUS SEALANT CHAIR RAIL/ ELECT RACEWAY FOR DORM RM Edmond, Oklahoma 24 24 University of Central Oklahoma Murdaugh Hall Renovation 1'-7" 24 1'-2 1/2" EXISTING STRUCTURE REVISION HISTORY: SCALE: 6" = 1'-0" 2 1 AE113 FURR DOWN BEYOND 15 2'-0" 1'-2 1/2" 1'-6" 26 25 6'-0" DATE PROJECT INFORMATION: DESIGNED BY: LGN DRAWN BY: LGN 6 7 4'-7" A PROJECT MANAGER: TJC 20141700 SHEET TITLE: 8 INTERIOR ELEVATIONS, SECTIONS & DETAILS GROUND FLOOR 100'-0" ISSUE DATE: 0 3 DESCRIPTION PROJECT NUMBER: 2'-6" 2 04/18/16 JBC CORRIDOR 2 ADDENDUM 002 REVIEWED BY: 13 1 1 2'-6" 4" EXTERIOR FOR REF. ONLY TYPICAL DORM ROOM 4 3'-8" A 3 2 1 14 3'-0" C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt 12 REF. RCP 8' - 0" 5 11 10 9 6'-7 1/2" 4 AE112 3 2 1 8'-0" AFF ELEVATION - TYPICAL DORM ROOM AT 1ST, 2ND & 3RD 2' 4' 03/30/16 SHEET NUMBER: SCALE: 1/2" = 1'-0" 4 1' 5 0 6" 1'-0" 2'-0" 0 1" 2" 4" AE112 1 3 2 5 4 Frankfurt Short Bruza Architects Engineers Planners EXISTING STRUCTURE 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com 5" BIRCH CROWN MOLDING STAIN TO MATCH BASE BUILDING EC C SURFACE MOUNT STRIP LIGHT WITH REFLECTOR. REF. ELECTRICAL SHEET EL501 LIGHT FIXTURE SCHEDULE. SE D A RCH IT BLOCKING METAL TRANSITION STRIP EXISTING TERRAZZO FLOOR 5/8" GYP BOARD PAINT AS SCHED. CLEAR PHILIP G. McNAYR 2134 EN 1X6 OAK STOCK, FLAT @ RETURN, SCRIBE WOOD BASE TO MATCH TERRAZZO BASE COVE 2 1/2" METAL STUD AT 16" O.C. 8" H T 5/8" GYP BOARD T 5/8" GYP BOARD PAINT AS SCHED. ST A 1'-4" 7/8"HAT CHANNEL @ 16" O.C. O F O K LA A CONTINUOUS SEALANT D E LI EXISTING STRUCTURE OM D BLOCKING 1 5/8" PARASQUARE DIFFUSER, CONTINUOUS; CHROME FINISH 7 SCALE: 3" = 1'-0" SCALE: 3" = 1'-0" EXISTING CONCRETE SLAB & BEAM 6" 8 AE113 EXISTING STRUCTURE 2'-0" C 5" BIRCH CROWN MOLDING STAIN TO MATCH BASE BUILDING EXISTING MOLDING BEYOND TO BE TRIMMED TO FIT NEW GYP. FUR OUT. 4'-1 3/4" EXISTING STRUCTURE C FAN COIL UNIT REF. MECH. PLANS REINSTALL DEMO'D 24" X 24" DECORATIVE CEILING TILE 5'-9" EXISTING 24" X 24" DECORATIVE CEILING TILE TO REMAIN FAN COIL UNIT 6'-0" 5/8" GYP. BOARD ON 3-5/8" METAL STUDS PAINTED 1 5/8" GYP BOARD ON 3 5/8" MTL. STUDS PAINT AS SCHED. DRYWALL COFFER BEAM BEYOND NEW 4'X4' ACCESS PANEL WITH TAMPER PROOF SCREWS. ACCESS PANEL TO BE INSTALLED WITH "BEST LOCKING SYSTEM" PER OWNER REQUEST. 3-5/8" GYP. BOARD ON 7/8" HAT CHANNEL @ 16" O.C. PAINTED 2'-1" 5/8" GYP BOARD ON 3 5/8" MTL. STUDS PAINT AS SCHED. 1'-1" SECTION - FUR DOWN AT MANAGERS APT. SCALE: 1" = 1'-0" 8'-0" AFF 9'-5" 6 8" 8'-0" AFF 5/8" GYP BOARD PAINT AS SCHED. 1'-10" AIR DIFFUSER 4/15/2016 5:02:12 PM B 3 5/8" STUD @ 16" O.C. 2'-5" 7 AE113 5 SCALE: 1" = 1'-0" 4 B 5/8" GYP BOARD PAINT AS SCHED. 3 SECTION - CORRIDOR FAN COIL UNIT @ EXIT DOOR AT 1ST, 2ND & 3RD 8'-6" AFF SECTION - FUR DOWN @ GAME ROOM Edmond, Oklahoma 8 DETAIL - TERRAZZO BASE TRANSITION University of Central Oklahoma Murdaugh Hall Renovation DETAIL - CEILING PORTAL FURR-OUT REVISION HISTORY: SCALE: 1 1/2" = 1'-0" SECTION - CORRIDOR PORTAL FURR-OUT AT 1ST, 2ND AND 3RD SCALE: 1" = 1'-0" 2 NEW RATED PARTITION EXISTING TERRAZZO BASE TO REMAIN 2 #3'S, CONT. 4" MIN. F.V. DRILL AND EPOXY #3'S @ 24" O.C., ALTERNATING EACH SIDE FAN COIL UNIT REF. MECH. PLANS C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt A EXISTING CONCRETE SLAB 3000 PSI CONCRETE INFILL, TYP. 1 24" X 24" ACOUSTICAL COFFERED CEILINGS AS SPEC'D 5/8" GYP BOARD ON 1 1/2" MTL. STUDS PAINT AS SCHED. STRIP LIGHT REF. ELECTRICAL PLANS & SCHED. 5/8" GYP BOARD ON 3 5/8" MTL. STUDS PAINT AS SCHED. 5" BIRCH CROWN MOLDING STAIN TO MATCH BASE BUILDING EXISTING CONCRETE BEAM 5/8" GYPSUM BOARD ON 2 1/2" METAL STUDS, PAINT AS SCHED. 4'-1 3/4" 3" 9" PIPE BEYOND (IF APPLICABLE), FIRE SEAL PIPE PENETRATIONS OF CONCRETE INFILL, SEAL WITH INTUMESCENT SEALER, TYP. REF. DETAIL 10/G-007 5 1/2" EXISTING WALL 1'-1 3/4" 1'-4" 1'-3" 5/8" GYP BOARD ON 7/8" HAT CHANNELS PAINT AS SCHED. RETURN AIR GRILL WALL MOUNT STRIP LIGHT WITH REFLECTOR REF. ELECTRICAL SHEET EL501 LIGHTING FIXTURE SCHEDULE EXISTING BEAM (IF APPLICABLE) 2 CHASE INFILL DETAIL AT 1ST, 2ND, 3RD AND ATTIC 1 SCALE: 1 1/2" = 1'-0" 1 2 3 ADDENDUM 002 04/18/16 DESCRIPTION DATE PROJECT INFORMATION: DESIGNED BY: LGN WALL MOUNT STRIP LIGHT WITH REFLECTOR REF. ELECTRICAL SHEET EL501 LIGHTING FIXTURE SCHEDULE DRAWN BY: 5/8" PARASQUARE DIFFUSER, CONTINUOUS PROJECT MANAGER: LGN REVIEWED BY: JBC A 5/8" GYPSUM BOARD ON 2 1/2" METAL STUDS PAINT AS SCHED. SECTION - DORM ROOM / CORRIDOR FUR DOWN 0 SCALE: 1" = 1'-0" TJC PROJECT NUMBER: 20141700 SHEET TITLE: INTERIOR SECTIONS & DETAILS 2" 4" 8" ISSUE DATE: 03/30/16 4 5 0 6" 1'-0" 2'-0" 0 4" 8" 1'-4" SHEET NUMBER: AE113 5 GENERAL NOTES 4 ADD ALTERNATE FINISH SCHEDULE CODE MATERIAL MANUFACTURER PATTERN NAME CPT1 WALK - OFF CARPET TILE BENTLEY MILLS CARPET CPT2 CARPET TILE - FIELD BENTLEY MILLS CARPET CPT3 CARPET TILE - ACCENT BENTLEY MILLS CARPET WD1 WOOD PLANK SHAW CONTRACT GROUP WDB1 WOOD BASE BY CONTRACTOR 1. TO BE INSTALLED QUARTER TURN PATTERN 2. TO BE INSTALLED BRICK PATTERN 3. TO BE INSTALLED HERRINGBONE PATTERN 4. TO BE INSTALLED STRIP STAGGARD ROUGH IDEA ARCADE LEGEND COHORT CLASSIC OAK CLASSIC OAK COLOR NAME FRAME WORK #800657 SPACE WOLF #800601 THUNDER + LIGHTING RUSTIC NATURAL RUSTIC NATURAL SIZE / FINISH 24"X24" 18"X36" 18"X36" 3 1/2" W X 3/4" T&G 6" NOTES 1 2 3 4 ADD - ALTERNATE Frankfurt Short Bruza 1. NEW FLOORING AT LOUNGE #130, REFERENCE FINISH SCHEDULE SHEET AE114 2. NEW SUSPENDED PENDANT TYPE "B", TYP. ADD SUPPORT AS REQUIRED, TYP. REFERENCE SHEET 1/EL101 FOR LIGHT FIXTURE PLACEMENT 3. NEW SOLID SURFACE TOILET AND SHOWER PARTITIONS 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com T ST A O F O K LA H PHILIP G. McNAYR 2134 A D E OM D Architects Engineers Planners C EC LI EN 1 1 1 1 C C 1 1 2 1 ADD ALTERNATE #02 - LOUNGE NEW FIXTURES SCALE: 3/16" = 1'-0" CPT1 CPT1 3 B B CPT3 4/15/2016 5:02:03 PM 3 IT 1 1 1 D A RCH University of Central Oklahoma Murdaugh Hall Renovation 1 SE CPT2 Edmond, Oklahoma 3 2 T 1 CPT2 REVISION HISTORY: WD1 2 1 ADDENDUM 002 04/18/16 DESCRIPTION DATE PROJECT INFORMATION: 3 DESIGNED BY: LGN DRAWN BY: CPT3 LGN C:\Users\lgn\Documents\My Revit\41700_Arch_lgn.rvt REVIEWED BY: CPT2 A JBC CPT3 A PROJECT MANAGER: TJC PROJECT NUMBER: 20141700 SHEET TITLE: ADD ALTERNATE - LOBBY FLOOR FINISHES, LOBBY PENDANTS AND TOILET & SHOWER PARTITIONS ISSUE DATE: 3 1 ENLARGED BATHROOM TYPICAL DETAIL - ADD ALTERNATE #03 SCALE: 1/4" = 1'-0" 2 3 1 03/30/16 ADD ALTERNATE #01 - LOUNGE FLOORING N SCALE: 3/16" = 1'-0" 4 0 0 5 2' 4' 2'-8" 5'-4" 8' 10'-8" SHEET NUMBER: AE114 GLOBE VALVE ABBREVIATIONS M Q W *ABV.................................................ABOVE EA..................................................EACH HB.........................................HOSE BIBB *MA......................................MEDICAL AIR QA.........................QUALITY ASSURANCE W....................................................WATT AFF..................ABOVE FINISHED FLOOR EL...........................................ELEVATION HORIZ..................................HORIZONTAL MAINT................................MAINTENANCE QTY..........................................QUANTITY W....................................................WEST AGA..........AMERICAN GAS ASSOCIATION *ELL...............................................ELBOW HOSP.......................................HOSPITAL MATL.......................................MATERIAL ALT.......................................ALTERNATE ELEC.........................................ELECTRIC HP.....................................HORSEPOWER MAX..........................................MAXIMUM R W/O..........................................WITHOUT APPROX............................APPROXIMATE EMER....................................EMERGENCY *HR..................................................HOUR MBH.............THOUSAND BTU PER HOUR RD.......................................ROOF DRAIN WC..................................WATER CLOSET LAVATORY ARCH...........ARCHITECT,ARCHITECTURAL EQUIP....................................EQUIPMENT HSKPG............................HOUSEKEEPING MC................MECHANICAL CONTRACTOR REF.......................................REFERENCE WC.................................WATER COLUMN WATER CLOSET AUTO.....................................AUTOMATIC EQUIV...................................EQUIVALENT HT...............................................HEIGHT MED.............................................MEDIUM REQD.......................................REQUIRED WG......................................WATER GAGE AUX........................................AUXILIARY EST..........................................ESTIMATE HW.......................................HOT WATER MECH...................................MECHANICAL REV.............................REVISE, REVISION WH...............................WATER HYDRANT AVG..........................................AVERAGE ETC............ET CETRA (AND SO FORTH) HWR.......................HOT WATER RETURN MEZZ.....................................MEZZANINE RFI.............REQUEST FOR INFORMATION WH..................................WATER HEATER EWC................ELECTRIC WATER COOLER HP.....................................HORSEPOWER MFG..............................MANUFACTURING RFP................REQUEST FOR PROPOSAL WHA............WATER HAMMER ARRESTOR EXIST.........................................EXISTING HYD.........................................HYDRANT MFR...............................MANUFACTURER RM.................................................ROOM WT...............................................WEIGHT EXT..........................................EXTERIOR HYD.......................................HYDRAULIC *MG....MEDIUM PRESSURE NATURAL GAS X F F..........................................FAHRENHEIT MIN............................................MINIMUM BFP....................BACKFLOW PREVENTER Hz.................................................HERTZ *RPBP...REDUCED PRESSURE BACKFLOW PREVENTER MISC..............................MISCELLANEOUS RPM..............REVOLUTIONS PER MINUTE BLDG.........................................BUILDING FCO............................FLOOR CLEANOUT I MOD............................................MODIFY RPS.............REVOLUTIONS PER SECOND FCU...................................FAN COIL UNIT ID.................................INSIDE DIAMETER MTD..........................................MOUNTED FD......................................FLOOR DRAIN IE................................INVERT ELEVATION FDC......FIRE DEPARTMENT CONNECTION *IN.................................................INCHES N *FF..................................FINISHED FLOOR IN WC...............INCHES WATER COLUMN N..................................................NORTH FFA........................FROM FLOOR ABOVE INFO...................................INFORMATION NA...............................NOT APPLICABLE FFB........................FROM FLOOR BELOW INSUL....................................INSULATION *NCS.............NATIONAL CAD STANDARDS FH....................................FIRE HYDRANT INV EL.......................INVERT ELEVATION NEG..........................................NEGATIVE FIG...............................................FIGURE *IPC......INTERNATIONAL PLUMBING CODE NIC............................NOT IN CONTRACT FIXT............................................FIXTURE IPS.................................IRON PIPE SIZE NO..............................................NUMBER FLA.............................FULL LOAD AMPS ISO.........................................ISOMETRIC J NOM...........................................NOMINAL SQ..............................................SQUARE SS................................SANITARY SEWER NPW.....................NONPOTABLE WATER NTS.................................NOT TO SCALE STOR........................................STORAGE PRESSURE REDUCING VALVE DOMESTIC HOT WATER PIPE ROUTED TO FLOOR DRAIN ASME RELIEF VALVE DOMESTIC HOT WATER RETURN V D PRESSURE AND TEMPERATURE RELIEF SOIL OR WASTE VENT SS SOIL OR WASTE - ABOVE FLOOR SS SOIL OR WASTE - BELOW FLOOR OR GRADE A REDUCER, ECCENTRIC URINAL REDUCER, CONCENTRIC COMPRESSED AIR - ABOVE FLOOR CO COMPRESSED AIR - BELOW FLOOR OR GRADE DRAIN A D G MG FP CO NATURAL GAS, LOW PRESSURE (0.5 PSI) NATURAL GAS, MEDIUM PRESSURE (50 PSIG) CLEANOUT, FLOOR B B/B...............................BACK TO BACK SINK BFF...................BELOW FINISHED FLOOR CLEANOUT, WALL SHOWER HEAD WATER HAMMER ARRESTOR DRINKING FOUNTAIN BLW................................................BELOW STRAINER, "Y" TYPE FIRE PROTECTION MAIN CD SERVICE SINK/BASIN FLOOR DRAIN DOUBLE CHECK VALVE BACKFLOW PREVENTION DEVICE CONDENSATE DRAIN BTU....................BRITISH THERMAL UNIT BTUH......................................BTU/HOUR COMPRESSED AIR OUTLET STATION A C REDUCED PRESSURE BACKFLOW PREVENTER W/STRAINER *CA...............................COMPRESSED AIR CAP...........................................CAPACITY CONNECT TO EXISTING RISER DOWN (ELBOW) CD..........................CONDENSATE DRAIN HB HOSE BIBB WH WALL HYDRANT *CBV..............CIRCUIT BALANCING VALVE *CFH....................CUBIC FEET PER HOUR RISER UP (ELBOW) CI...........................................CAST IRON PIPE ANCHOR RISE OR DROP CL......................................CENTER LINE PIPE SLEEVE THRU WALL, FOOTING ETC TEE DOWN CLG.............................................CEILING CO........................................CLEAN OUT FLOW IN DIRECTION OF ARROW TEE UP COL............................................COLUMN PIPE SLOPE IN DIRECTION OF ARROW TOP CONNECTION COMB.................................COMBINATION CONC......................................CONCRETE T1 BOTTOM CONNECTION CONN.....................................CONNNECT THERMOMETER C CONT..................CONTINUE, CONTINOUS TW SIDE CONNECTION BALL VALVE PI C GATE VALVE OR ISOLATION VALVE (1.2) TEXT SYMBOLS UNION ANGLE VALVE BLIND FLANGE ...................................ANGLE CHECK VALVE (STRAIGHT) CAP °...............................DEGREE Ø..........................DIAMETER CHECK VALVE (SWING GATE) Ø................................PHASE Ø................................ROUND %............................PERCENT FP...............................FIRE PROTECTION FPM............................FEET PER MINUTE FPS...........................FEET PER SECOND JAN CLO...................JANITOR'S CLOSET K O OC........................................ON CENTER K............................................THOUSAND KW...........................................KILOWATT KWH..............................KILOWATT HOUR FT.........................................FOOT, FEET OK S..................................................SOUTH Z SCHED....................................SCHEDULE SCHEM..................................SCHEMATIC SECT..........................................SECTION SF........................SQUARE FEET (FOOT) SPEC................................SPECIFICATION STRUCT...............................STRUCTURAL SYS.............................................SYSTEM OD............................OUTSIDE DIAMETER T OPP.........................................OPPOSITE T&P.......TEMPERATURE AND PRESSURE OPT.........................................OPTIONAL TECH.....................................TECHINICAL FURN.....................................FURNISHED L.....................................................LITER OUT............................................OUTLET TFA.............................TO FLOOR ABOVE FV.....................................FLUSH VALVE LAV.........................................LAVATORY OZ................................................OUNCE TFB.............................TO FLOOR BELOW G LBS............................................POUNDS P THRU........................................THROUGH CTR.............................................CENTER G......................................NATURAL GAS LF..........................LINEAR FEET (FOOT) PCT..........................................PERCENT TSTAT.................................THERMOSTAT CW......................................COLD WATER GA.....................................GAGE, GAUGE LKR.............................................LOCKER PH................................................PHASE TYP............................................TYPICAL D GAL.............................................GALLON PKG..........................................PACKAGE D...................................................DRAIN GALV....................................GALVANIZED PLBG.......................................PLUMBING DEG.............................................DEGREE GC......................GENERAL CONTRACTOR PPM........................PARTS PER MILLION DEMO....................................DEMOLITION GPH..........................GALLON PER HOUR PRELIM...............................PRELIMINARY DF...........................DRINKING FOUNTAIN GPM.......................GALLON PER MINUTE PRESS....................................PRESSURE C U UL..........UNDERWRITERS LABORATORIES UNO.............UNLESS NOTED OTHERWISE V DIA...........................................DIAMETER PRV...........PRESSURE REDUCING VALVE *V....................................................VENT DIAG..................DIAGRAM, DIAGRAMATIC PSI.............POUNDS PER SQUARE INCH V....................................................VOLT DN..................................................DOWN PSIA....POUNDS PER SQ. IN. ABSOLUTE VOL............................................VOLUME DWG..........................................DRAWING PSIG............POUNDS PER SQ. IN. GAGE VTR............................VENT THRU ROOF DWH..............DOMESTIC WATER HEATER PWR.............................................POWER DWV......................DRAIN, WASTE, VENT PVC.......................POLYVINYL CHLORIDE NOTE: ABBREVIATIONS SHOWN WITH AN * AT THE BEGINNING OF THE ABBREVIATION ARE NOT IN THE CURRENT NCS STANDARDS. 4/15/2016 3:17:59 PM MISCELLANEOUS PLUMBING SCHEDULE WATER HAMMER ARRESTOR PDI SYMBOL FIXTURE UNITS A B C D E F 1 - 11 12 - 32 33 - 60 61 - 113 114 - 154 155 - 330 BASIS OF DESIGN MARK FIXTURE P-1 C:\Users\meb\Documents\My Revit\41700_Plbg_meb.rvt A WASTE VENT (IN) (IN) MANUFACTURER MODEL NO. DORM ROOM VANITY LAVATORY KOHLER K-2210 P-2 WATER CLOSET TOTO CT705ENG 4 P-3 TUB/HAND SHOWER SYMMONS S-5504-XCHKS-1.5 P-4 SHOWERHEAD SYMMONS P-5 JANITOR'S SERVICE SINK CO-1 END OF PIPE CLEANOUT CO-2 FLOOR CLEANOUT 1-1/2 HW (IN) 1/2 1/2 DESCRIPTION 17"x 14", UNDERMOUNT SINK, VITREOUS CHINA, WITH OVERFLOW AND CLAMP ASSEMBLY. TRIM: ZURN Z7440-XL SINGLE LEVER MANUAL FAUCET, 5" SPOUT, POLISHED CHROME, DECK MOUNTED, 4" CENTERSET, 0.5 GPM VANDAL RESISTANT SPRAYER. ADA COMPLIANT. 1-1/4 --- FLOOR MOUNTED WATER CLOSET, WHITE VITREOUS CHINA, ELONGATED BOWL, 1.6 GPF, OPEN FRONT SEAT. TRIM: TOTO TET1GNC-32 TOILET FLUSHMETER VALVE, INFRARED SENSOR ACTIVATED, ECOPOWER SELF-GENERATING SYSTEM, MANUAL OVERRIDE BUTTON, 1.6 GPF, POLISHED CHROME. --- --- 3/4 3/4 TUB-HAND SHOWER SYSTEM WITH LEVER HANDLE, PRESSURE-BALANCING MIXING VALVE WITH ADJUSTABLE STOP SCREW TO LIMIT HANDLE TURN, WALL/HAND SHOWER WITH 5 FOOT FLEXIBLE METAL HOSE, IN-LINE VACUUM BREAKER, WALL CONNECTION AND CRADLE FOR HAND SHOWER MOUNTING, TUB SPOUT AND 1.5 GPM FLOW RATE RESTRICTOR. POLISHED CHROME FINISH. 1 4-221-1.5 --- --- --- --- WALL MOUNTED SHOWERHEAD AT 6'-6" AFF WITH ADJUSTABLE SPRAY AND VOLUME CONTROL, 1.5 GPM FLOW RATE RESTRICTOR, POLISHED CHROME FINISH. KOHLER K-6714 3 2 3/4 3/4 WALL MOUNTED SERVICE SINK, 22"x18"x12" DEEP, 10" BACKSPLASH, 8" CENTER FAUCET HOLES, CAST IRON, ACID-RESISTANT ENAMEL FINISH W/ STAINLESS STEEL RIM GUARD. TRIM: KOHLER SERVICE SINK FAUCET K-8907 CHROME PLATED FINISH, VACUUM BREAKER, 8" CENTERS, PAIL HOOK, HOSE CONNECTION AND WALL BRACE. KOHLER 6673 TRAP FOR 3" IRON PIPE. WADE 8590-B --- --- --- THREADED BRASS RAISED HEAD CLEANOUT PLUG DRILLED AND TAPPED FOR 1/4-20 SCREW. WADE FLOOR DRAIN WADE FD-2 FLOOR DRAIN WADE WH-1 WALL HYDRANT WADE RPZ BACKFLOW PREVENTER 1-1/2" CW (IN) 2 FD-1 BFP-1 (APPLIES TO ALL PLUMBING SHEETS) PIPING ROUGH-IN 6000 1100STD WATTS SEE PLAN SEE PLAN --- --- --- CAST IRON CLEANOUT WITH THREADED ADJUSTABLE HOUSING, FLANGED FERRULE AND ROUND SECURED NICKEL BRONZE TOP. SEE PLAN --- --- --- CAST IRON FLOOR DRAIN WITH FLANGE, INTEGRAL REVERSIBLE CLAMPING COLLAR, SEEPAGE OPENINGS, 1/2" TRAP PRIMER CONNECTION, NICKEL BRONZE STRAINER WITH VANDAL PROOF SCREWS. 1210 SEE PLAN --- --- --- CAST IRON MEDIUM DEPTH FLOOR DRAIN WITH FLANGE, INTEGRAL CLAMPING COLLAR AND DUCTILE IRON LOOSE SET TRACTOR GRATE AND (27) ALUMINUM SEDIMENT BUCKET, 1/2" TRAP PRIMER CONNECTION, VANDAL PROOF SCREWS. 8600 --- --- 3/4 --- 3/4" NON-FREEZE EXPOSED WALL HYDRANT WITH STRAIGHT INLET CONNECTIONS, BRONZE CASING NICKEL BRONZE FACE AND ANTI-SIPHON BACKFLOW PREVENTER. LF009 --- --- 3 --- TMV-1 THERMOSTATIC MIXING VALVE SYMMONS 7-1000A --- --- 1-1/2 1-1/2 TP-1 TRAP PRIMER SIOUX CHIEF 695 SEE PLAN --- 1/2 --- REDUCED PRESSURE ZONE BACKFLOW PREVENTER, 3" SIZE, TWO IN-LINE INDEPENDENT CHECK VALVES WITH AN INTERMEDIATE RELIEF VALVE. PROVIDE WITH 'QT' QUARTER TURN, FULL PORT, RESILIENT SEATED BALL VALVE SHUT-OFFS; AND STRAINER. 1-1/2" INLETS, 2" OUTLET, THERMOSTATIC CONTROLLER CAPABLE OF 67 GPM AT 10 PSI PRESSURE DIFFERENTIAL, WITH SEPARATE CHECK STOPS, REMOVABLE CARTRIDGE WITH STRAINER, STAINLESS STEEL PISTON AND LIQUID FILLED THERMAL MOTOR WITH BELLOWS MOUNTED OUT OF WATER. VOLUME CONTROL SHUT OFF VALVE, BIMETAL DIAL THERMOMETER, 3" FACE, BRASS PIPE FITTINGS AND UNIONS. A. SLOPE SOIL AND WASTE DRAIN 3" AND LARGER AT 1% SLOPE MINIMUM, UNLESS NOTED OTHERWISE, AND SIZE LESS THAN 3" SLOPE 2% MINIMUM UNLESS NOTED OTHERWISE. B. ALL PIPING SHALL BE COORDINATED WITH FIRE PROTECTION, MECHANICAL DUCTWORK AND PIPING, ELECTRICAL LIGHTING AND POWER, STRUCTURAL AND ARCHITECTURAL SYSTEMS. C. DEMOLITION OF ANY EXISTING CONSTRUCTION REQUIRED BY PLUMBING CONTRACTOR TO PROPERLY COMPLETE THEIR WORK SHALL BE ACCOMPLISHED AS A PART OF THEIR WORK AND SHALL BE PART OF THE PRIME CONTRACT. D. PIPE CLEANOUT SHALL BE LINE SIZE, 4" MAXIMUM. LOCATE 100' APART MAXIMUM. E. ALL RISER, STACKS, LEADERS, RUNOUTS OR BRANCHES THROUGH FLOOR LEVELS SHALL BE SLEEVED AND FIRE CAULKED. SLEEVES SHALL EXTEND MINIMUM OF 2" ABOVE FLOOR LEVEL. F. MANUFACTURER'S NAMES, MODEL NUMBERS OR SPECIFIC PRODUCT LINES LISTED IN THE CONTRACT DOCUMENTS ARE GIVEN ONLY TO INDICATE THE BASIS OF DESIGN. PRODUCTS MEETING THE REQUIREMENTS OF THE CONTRACT MAY BE SUBMITTED FOR APPROVAL. G. ALL EXISTING PLUMBING PIPING FROM ABOVE BASEMENT FLOOR TO BELOW ROOF SHALL BE DEMOLISHED. EXISTING PIPE ROUTING IS SIMILAR TO NEW PIPE ROUTING SHOWN. ALL PIPE SIZES SHOWN ARE FOR NEW PIPING. EXISTING PIPE SIZES AND ROUTING MAY DIFFER FROM THOSE SHOWN. H. ALL PIPING SHALL BE RAN AS HIGH AS POSSIBLE THROUGHOUT BASEMENT AND ATTIC. I. SHUTOFF VALVES AND DRAIN PIPE FOR ALL LAVATORY FIXTURES SHALL BE INSTALLED AS HIGH AND TIGHT TO FIXTURE AS POSSIBLE. J. ALL DEMOLISHED COPPER PIPE AND FITTINGS SHALL BE TURNED OVER TO UCO FOR RECYCLING. ALL OTHER MATERIALS SHALL BE HAULED AWAY. K. ALL DORM ROOM SINKS BACK TO BACK WASTE PIPING SHALL BE DOUBLE WYE AND 1/8" BEND. NO CROSS TEES SHALL BE USED. L. PROVIDE TRAP PRIMERS FOR ALL TRAPS REPLACED ON FLOOR DRAINS. PROVIDE ACCESS PANEL TO SERVICE TRAP PRIMER. M. MATERIALS WITHIN RETURN AIR PLENUM SHALL MEET ALL REQUIREMENTS OF APPLICABLE CODES. INCLUDING IBC. PRIME PREFECT TRAP PRIMER AND TRAP PRIMER DISTRIBUTOR AS REQUIRED FOR NUMBER OF FLOOR DRAINS SERVED. B REVISION HISTORY: 1 Addendum 02 DESIGNED BY: RDR DRAWN BY: RDR REVIEWED BY: BAS A PROJECT MANAGER: TJC PROJECT NUMBER: 20141700 SHEET TITLE: LEGEND & ABBREVIATIONS 03/30/16 SHEET NUMBER: CONTRACTOR SHALL PROVIDE C.P. SUPPLIES W/LOOSE-KEY STOPS, C.P. 'P' TRAP W/CLEANOUT, AND WALL ESCUTCHEONS AS REQUIRED. 2 3 4 5 DATE PROJECT INFORMATION: P-001 1 04/18/16 DESCRIPTION ISSUE DATE: NOTES: 1. L A H O MA XFMR...............................TRANSFORMER GENERAL NOTES B GARY W. JAMES 16166 YR..................................................YEAR *s.................................................SECOND TEMP................................TEMPERATURE NOTE: NOT ALL LEGEND AND ABBREVIATIONS SHOWN ARE USED ON THIS PROJECT. F E S S I O NA YH.................................YARD HYDRANT ORIG.........................................ORIGINAL *CP.................................CHROME PLATED LUBRICATED PLUG VALVE CIRCUIT BALANCING VALVE - SET FOR GPM SHOWN IN (). FM..............................FACTORY MUTUAL D RO Y S L CORR.......................................CORRIDOR PRESSURE GAUGE WITH GAUGE COCK (C=COMPOUND GAUGE) FLR...............................................FLOOR W/...................................................WITH FTG............................................FOOTING CORD.....................................CORDINATE THERMOMETER WELL FLEX..........................................FLEXIBLE MULT........................................MULTIPLE 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com G INEER H EN E L A COMPRESSED AIR RELIEF VALVE NON-POTABLE WATER (MAKE-UP) Frankfurt Short Bruza Architects Engineers Planners Edmond, Oklahoma SYMBOL DESCRIPTION University of Central Oklahoma Murdaugh Hall Renovation DOMESTIC COLD WATER 5 4 P SYMBOL DESCRIPTION SYMBOL DESCRIPTION NPW 3 2 L IC E NS E D 1 3 SHEET KEYNOTES A. REFER TO SHEET P-001 FOR GENERAL NOTES APPLICABLE TO THIS SHEET. B. ALL EXISTING PLUMBING PIPING FROM ABOVE BASEMENT FLOOR TO BELOW ROOF SHALL BE DEMOLISHED. EXISTING PIPE ROUTING IS SIMILAR TO NEW PIPE ROUTING SHOWN. ALL PIPE SIZES SHOWN ARE FOR NEW PIPING. EXISTING PIPE SIZES AND ROUTING MAY DIFFER FROM THOSE SHOWN. C. PROVIDE ACCESSIBLE SHUTOFF VALVES FOR ALL PLUMBING RISERS IN BASEMENT CEILING. 7. 3/4" CW/HW PIPING DOWN THRU HOSE BIBB SUPPLYING WASHING MACHINE. 8. ROUTE 1" HWR PIPING TO EXISTING HOT WATER CIRCULATING PUMP. 9. REFER TO 1/P-601 FOR ADDITIONAL INFORMATION. 10. ROUTE 2" CW PIPING TIGHT TO WALL THRU SHUTOFF VALVE AND CAP FOR FUTURE YARD SPRINKLER SYSTEM. 11. ROUTE 1" CW/HW PIPING UP AND 2" SS DOWN. 12. ROUTE 1" CW/HW PIPING UP AND 3" SS DOWN. 13. 3/4" CW/HW PIPING UP AND 2" SS DOWN. 14. 2" CW/HW PIPING UP AND 3/4" HWR PIPING UP. 15.2-1/2" CW , 1-1/4" HW AND 3/4" HWR PIPING UP. 16. 1-1/4" CW/HW UP AND 3/4" HWR PIPING UP. 17. 3/4" CW/HW DOWN AND 2" SS DOWN AND 1-1/2" V UP. 18. 2" SS PIPING UP TO SERVE FIXTURE ON FIRST FLOOR. 19. 4" SS PIPING UP TO SERVE FIXTURE ON FIRST FLOOR. Frankfurt Short Bruza Architects Engineers Planners 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com 3 2 4 7 9 8 10 11 12 14 15 16 17 G INEER GARY W. JAMES 16166 OK 1 F E S S I O NA EN D RO L 1. PROVIDE NEW RPZ BACKFLOW PREVENTER AT DOMESTIC WATER ENTRANCE. REFER TO SCHEDULE ON SHEET P-001 FOR BFP-1. 2. DOMESTIC HOT WATER SUPPLY AND RETURN PIPING SHALL BE REPLACED DOWNSTREAM OF CIRCULATION PUMP AND WATER STORAGE TANKS. PIPING BETWEEN WATER SOFTENER, EXTERIOR WATER HEATERS, STORAGE TANKS, AND CIRCULATION PUMP ARE NOT REQUIRED TO BE REPLACED. 3. PROVIDE ACCESSIBLE SHUTOFF VALVES AT EACH DOMESTIC COLD, HOT AND HOT WATER RETURN RISER IN THE BASEMENT. 4. REFER TO CU101 FOR CONTINUATION. 5. PROVIDE 1" METRALOOP MLSNSF80100 IN HWR AND 3" METRALOOP MLSNSF80300 IN HW OR EQUAL IN THIS APPROXIMATE LOCATION. PROVIDE GUIDES AND ANCHORS PER MANUFACTURER INSTALLATION INSTRUCTIONS. EXPANSION LOOPS SHALL BE LEAD FREE, NSF LISTED FOR USE IN POTABLE WATER SYSTEMS. 6. 1-1/4" CW/HW PIPING DOWN AND BRANCH 3/4" CW/HW PIPING TO HOSE BIBB SUPPLYING EACH WASHING MACHINE. D 5 GENERAL NOTES 4 SHEET KEYNOTES P 2 L IC E NS E D 1 L A H O MA 18 WH-1 3/4" 3/4" 1" 1" COORDINATE WITH OFFICE OF INFORMATION TECHNOLOGY IT ROOM 014A IT 014 3/4" 1" 3/4" CW HWR HWR 3" 4" 3" 2" 4" SS UP/DN 2" 1" HWR HWR 2" SS DN 3/4" 3" 2" SS 5 11 1" 11 11 STORAGE 011 3/4" CORR. H015 1-1/4" 4" 1" 1" 2" 11 12 2" SS DN 11 4" 3/4" 4" STAIR 011A 4" SS 2" HALL 011B 3/4" RESTROOM 023 FD-1 1-1/4" 1-1/4" RESTROOM 011C 2" SS UP 1" CO-1 18 STAIR S04 2" 19 SHOWERS 022 14 1-1/4" CW DN 4" 18 4" INVENTORY OFFICE 014D VENT UP (TYP) 9 3/4" DEMO FIXTURES & CAP SEWER THIS AREA CO-1 11 STAIR CORR. S02 024 14 2" HWR HWR CW 3/4" 4" SS UP/DN 3/4" OFFICE TORNADO SHELTER 016 FD-1 CORR. H024 11 B 4" SS UP/DN 1-1/4" 1" 2" 3/4" 1" CW DN 1" HW DN C 1" 1-1/2" W W REVISION HISTORY: W 7 EXISTING HOT WATER STORAGE TANKS TO REMAIN 3/4" 3/4" 1" HWR CW HWR 1-1/4" LAUNDRY 020 D HWR CW 1-1/4' 11 11 6 PROVIDE CW/HW SHUTOFF VALVE & CAP FOR FUTURE 3/4" 3/4" TORNADO SHELTER 017 1 3/4" 17 6 11 11 1" 7 9 8 10 11 12 13 11 DATE DESIGNED BY: RDR 3/4" 3/4" DRAWN BY: RDR REVIEWED BY: 3/4" 1" 1-1/4" WH-1 REF. WH-1 D 04/18/16 PROJECT INFORMATION: 11 BALANCING VALVE (TYP) Addendum 02 DESCRIPTION 14 3/4" 1" 3/4" 19 4" CRAWL SPACE 178 1 1/4" 1 1/4" 2" 3" FD-1 3/4" 8 HWR CW HWR 11 2 1/2" B 2" 2 1/2" 11 2" CW 11 1" 3/4" 4" 2" 18 2" SS 3" 3/4" 2" SS DN 2" TMV-1 EXISTING WATER SOFTENER TANK TO REMAIN A 2" CO-1 MAINTENANCE SHOP 012 MAINT. OFFICE 014C 2" 2 1/2" 2 1/2" 1 1/4" CORR. 014B W BFP-1 HYDRONIC PUMP RM 004B 2" 4" 3/4" ELECTRICAL 14 CLOSET 004A ELECTRICAL 004C 1 1/2" 2" 1-1/2" 3" 2 SS 2" 2" W STAIR 01B STAIR 002 4" 3/4" 4" SS UP/DN 3" SS UP TO FIXT ABV (TYP) 9 2" 2" 15 12 2" 18 3/4" CO-1 HWR 4/15/2016 3:18:09 PM FIRE PUMP 3/4" ROOM 005 3" 2" FD-2 1 1/4" C:\Users\meb\Documents\My Revit\41700_Plbg_meb.rvt 3/4" 2" 4 FAN COIL UNIT ABV CEILING (TYP) 3/4" 17 B 2" 3" 2" CW HWR HWR 2" SS UP 3/4" CO-1 11 2" 14 3" 4" 3" 2" C STORAGE 010 3/4" 4" SS UP/DN 18 4" 2" SS UP TO FD ON 1ST FLR 13 CO-1 STORAGE 013 2" SS CO-1 10 1-1/4" W SS UP TO FIXT ON 1ST 4" FLR (TYP) 2" 1 1/2" 4"STORAGE SS 2" 001B 2" 1 18 4" 2 1/2" FD-2 CO-1 15 11 FD-2 1 W 2" 2" W UP FD-1 3/4" MECHANICAL ROOM 006A 3/4" CO-1 PROVIDE CW/HW SHUTOFF 3" SS UP 18 UNDER SINK AND AT TOILETS 4" SS DN RESTROOM AND SHOWER VALVE. CAP FOR FUTURE USE BOTH 009 3/4" RESTROOMS. 4" SS UP/DN 3 TYP. 2" SS UP 4" CO-1 TO FD ON 1ST FLR CW HWR HWR MECHANICAL ROOM 2 1/2" 006 C 1-1/4" 11 16 W 3/4" 3/4" B 16 IT ROOM 3/4" 014A W ELECTRICAL 11 ROOM 007 3" SS UP 4" SS DN SS 1-1/2" SS C 13 11 STORAGE 010A D 1-1/4" RESTROOM 008 1-1/4" 1-1/4" CO-2 D 13 SHUTOFF VALVE (TYP) 3/4" 11 3/4" D 3/4" WH-1 Edmond, Oklahoma CRAWL SPACE 167 WH-1 A WH-1 University of Central Oklahoma Murdaugh Hall Renovation A BAS 3/4" KITCHENETTE 019 BIKE SHOP 018 A WH-1 TJC PROJECT NUMBER: D WH-1 PROJECT MANAGER: 20141700 SHEET TITLE: BASEMENT PLUMBING PLAN 1 1 2 3 BASEMENT PLUMBING PLAN SCALE: 1/8" = 1'-0" ISSUE DATE: 4 15 16 17 18 03/30/16 SHEET NUMBER: N 0 1 2 3 4 5 4' 8' 16' P-101 4 7 8 9 10 11 12 14 15 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com D 16 17 C P-1 P-1 TYP. 3 P-1 P-1 DORM 264 DORM 222 18 22 P-1 C DORM 219 18 11 TYP. 2 DORM 221 DORM 220 DORM 263 P-1 11 7 7 P-1 22 P-1 P-1 MECH. 201A DORM 262 FD-1 12 FD-1 12 23 4 23 2" SS UP TO FCO CO-1 11 DORM 260 P-1 FD-1 12 14 P-1 MEN'S RR 261 10 B DORM 240 DORM 238 P-1 P-1 5 DORM 256 DORM 242 DORM 236 DORM 234 DORM 232 DORM 230 8 P-1 P-1 P-1 CO-3 13 CORR. H200 20 CO-3 13 14 P-1 P-2 6 10 P-1 5 VENT UP (TYP) 9 MECH. 218A SS UP TO FIXT ABV (TYP) 9 21 8 20 13 CO-3 P-1 CORR. H201 P-1 P-1 4/15/2016 3:18:15 PM P-1 P-1 P-1 P-1 P-1 P-1 P-1 DORM 241 DORM 239 DORM 237 DORM 235 DORM 233 DORM 231 DORM 229 DORM 225 DORM 227 STAIR S21 DORM 223 20 20 DORM 252 DORM 209 5 DORM 243 21 P-1 P-1 5 DORM 254 C REVISION HISTORY: 21 11 C 11 DORM 207 DORM 208 DORM 251 P-1 P-1 P-1 P-1 P-1 P-1 P-1 P-1 DORM 249 DORM 250 B DORM 211 STAIR S22 P-1 DORM 213 1 13 CO-3 B P-1 MEN'S RR 218 P-5 21 MECH 261A 1 P-1 P-1 P-2 15 17 TP-1 2" DORM 2" 224 DORM 226 DORM 228 DORM 215 11 P-1 1 CORR. H202 19 CO-1 12 FD-1 2" DORM 2" 244 6 P-3 2" SS UP TO FCO TP-1 17 15 DORM 258 16 P-4 P-4 16 P-3 19 DORM 217 16 P-4 P-4 16 4 B University of Central Oklahoma Murdaugh Hall Renovation A DORM 265 L A H O MA 18 DORM 266 3/4" DRAIN LINE FROM FCU TO CHASE (TYP. OF ALL) P-1 F E S S I O NA GARY W. JAMES 16166 OK FAN COIL UNIT ABV CEILING (TYP.) A RO Edmond, Oklahoma 3 Frankfurt Short Bruza Architects Engineers Planners G INEER 2 A. REFER TO SHEET P-001 FOR GENERAL NOTES APPLICABLE TO THIS SHEET. B. ALL EXISTING PLUMBING PIPING FROM ABOVE BASEMENT FLOOR TO BELOW ROOF SHALL BE DEMOLISHED. EXISTING PIPE ROUTING IS SIMILAR TO NEW PIPE ROUTING SHOWN. ALL PIPE SIZES SHOWN ARE FOR NEW PIPING. EXISTING PIPE SIZES AND ROUTING MAY DIFFER FROM THOSE SHOWN. C. ALL EXISTING WALL HUNG LAVATORIES IN DORM ROOMS SHALL BE DEMOLISHED UNLESS NOTED OTHERWISE. D. EACH BATHROOM SHALL BE PROVIDED ISOLATION SHUTOFF VALVES FOR ALL DOMESTIC WATER PIPING. ACCESS PANEL SHALL BE PROVIDED NO HIGHER THAN 5 FEET AFF FOR EMERGENCY SHUTOFF. EN 1 11. COORDINATE ACCESS PANEL LOCATION WITH SHUTOFF VALVES FOR EACH SET OF RESTROOMS 12. EXISTING FLOOR DRAIN TO BE DEMOLISHED AND REPLACED WITH TRAP PRIMER FLOOR DRAIN. PROTECT DURING NEW CONSTRUCTION AND CONNECT NEW DRAIN PER 1/P-601. 13. INSTALL ACCESSIBLE WALL CLEANOUT TO SANITARY SEWER AND CONDENSATE DRAIN RISER UNDER LAVATORY AT 1'-0" AFF. 14. 2" VENT UP. 15. 3" VENT UP. 16. INSTALL NEW SHOWERHEAD AT 6'-6" AFF. 17. ACCESSIBLE TRAP PRIMER VALVE BELOW LAVATORY TO SERVE SHOWER AND RESTROOM FLOOR DRAINS. 18. 1-1/4" CW/HW UP FROM BELOW TO ABOVE AND 3/4" HWR DOWN FROM ABOVE TO BELOW. 19. 2" CW UP FROM BELOW TO ABOVE. 1-1/4" HW UP FROM BELOW AND 1" HW UP TO FLOOR ABOVE. 3/4" HWR DOWN FROM ABOVE TO BELOW. 20. 1-1/2" CW UP FROM BELOW AND 1-1/4" CW UP TO FLOOR ABOVE. 1" HW UP FROM BELOW AND 3/4" HW UP TO FLOOR ABOVE. 3/4" HWR DOWN FROM ABOVE TO FLOOR BELOW. 21. 4" SS AND 3" V PIPING UP FROM BELOW TO FLOOR ABOVE. 22. 3" SS PIPING UP AND DOWN. 23. 4" SS PIPING UP AND DOWN. L 1. DEMOLISH AND REPLACE ALL DOMESTIC COLD, HOT ,HOT WATER RETURN, DRAIN, WASTE AND VENT PIPING TO FIXTURES IN GANGED TOILET. RECONNECT EXISTING FIXTURES. REFER TO 1/P-601. 2. DEMOLISH AND REPLACE ALL DOMESTIC COLD, HOT DRAIN WASTE AND VENT PIPING TO BACK TO BACK LAVATORIES IN DORM ROOMS. PROVIDE 3/4" CONDENSATE DRAIN PIPING AT 8'-4" AFF AND SLOPE 1/8" PER FOOT FROM FAN COIL UNIT TO CHASE BEHIND LAVATORY. CONNECT CONDENSATE DRAIN TO SS THRU ACCESSIBLE AIR GAP IN CHASE BEHIND MEDICINE CABINET IN EACH ROOM. REFER TO 2/P-604. TYPICAL OF ALL. 3. DEMOLISH AND REPLACE ALL DOMESTIC COLD, HOT, DRAIN, WASTE AND VENT PIPING TO SINGLE LAVATORIES IN DORM ROOMS. PROVIDE 3/4" CONDENSATE DRAIN PIPING AT 8'-4" AFF AND 1/8" PER FOOT FROM FAN COIL UNIT TO CHASE BEHIND LAVATORY. CONNECT CONDENSATE DRAIN TO SS THRU ACCESSIBLE AIR GAP IN CHASE BEHIND MEDICINE CABINET IN EACH ROOM. REFER TO 4/P-601. TYPICAL OF ALL. 4. DEMOLISH AND REPLACE ALL DOMESTIC COLD, HOT, HOT WATER RETURN, DRAIN, WASTE AND VENT PIPING TO FIXTURES IN SHOWER ROOM. RECONNECT EXISTING FIXTURES. REFER TO 3/P-601. 5. DEMOLISH AND REPLACE ALL DOMESTIC COLD, HOT, DRAIN ,WASTE AND VENT PIPING TO FIXTURES IN RESTROOM. RECONNECT EXISTING FIXTURES. REFER TO 5/P-601. 6. DEMOLISH AND REPLACE ALL DOMESTIC COLD, HOT, HOT WATER RETURN, DRAIN WASTE, AND VENT PIPING TO LAVATORIES. RECONNECT EXISTING FIXTURES. REFER TO 6/P-601. 7. COORDINATE PLUMBING PIPING IN THIS AREA WITH EXHAUST DUCT SHOWN ON M-401. 8. COORDINATE PLUMBING PIPING IN THIS AREA WITH OA SUPPLY DUCT AND HEATING/CHILLED WATER RISER SHOWN ON M-401. 9. REFER TO 1/P-601 FOR ADDITIONAL INFORMATION. 10.REINSTALL EXISTING HYDRATION STATION IN THIS LOCATION AND CONNECT 1/2" CW COPPER DOMESTIC WATER PIPING. D 5 GENERAL NOTES 4 SHEET KEYNOTES P 3 SHEET KEYNOTES 2 L IC E NS E D 1 DORM 205 DORM 206 1 Addendum 02 04/18/16 DESCRIPTION DATE PROJECT INFORMATION: DESIGNED BY: RDR DORM 248 DORM 247 6 C:\Users\meb\Documents\My Revit\41700_Plbg_meb.rvt P-1 A 7 8 9 10 11 12 13 14 DRAWN BY: RDR REVIEWED BY: P-1 P-1 DORM 203 DORM 204 P-1 P-1 P-1 BAS P-1 A P-1 PROJECT MANAGER: TJC PROJECT NUMBER: DORM 246 DORM 202 DORM 245 DORM 201 20141700 SHEET TITLE: SECOND FLOOR PLUMBING PLAN D D 1 1 2 3 SECOND PLUMBING FLOOR PLAN ISSUE DATE: SCALE: 1/8" = 1'-0" 4 15 16 17 03/30/16 18 SHEET NUMBER: N 0 1 2 3 4 5 4' 8' 16' P-103 3 4 7 8 9 10 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com D RO GARY W. JAMES 16166 OK 11 12 14 15 16 17 F E S S I O NA G INEER 2 Frankfurt Short Bruza Architects Engineers Planners EN 1 A. REFER TO SHEET P-001 FOR GENERAL NOTES APPLICABLE TO THIS SHEET. B. ALL EXISTING PLUMBING PIPING FROM ABOVE BASEMENT FLOOR TO BELOW ROOF SHALL BE DEMOLISHED. EXISTING PIPE ROUTING IS SIMILAR TO NEW PIPE ROUTING SHOWN. ALL PIPE SIZES SHOWN ARE FOR NEW PIPING. EXISTING PIPE SIZES AND ROUTING MAY DIFFER FROM THOSE SHOWN. C. ALL EXISTING WALL HUNG LAVATORIES IN DORM ROOMS SHALL BE DEMOLISHED UNLESS NOTED OTHERWISE. D. EACH BATHROOM SHALL BE PROVIDED ISOLATION SHUTOFF VALVES FOR ALL DOMESTIC WATER PIPING. ACCESS PANEL SHALL BE PROVIDED NO HIGHER THAN 5 FEET AFF FOR EMERGENCY SHUTOFF. 11. COORDINATE ACCESS PANEL LOCATION WITH SHUTOFF VALVES FOR EACH SET OF RESTROOMS 12. EXISTING FLOOR DRAIN TO BE DEMOLISHED AND REPLACED WITH TRAP PRIMER FLOOR DRAIN. PROTECT DURING NEW CONSTRUCTION AND CONNECT NEW DRAIN PER 1/P-601. 13. 2" VENT UP. 14. 3" VENT UP. 15. INSTALL NEW SHOWERHEAD AT 6'-6" AFF. 16. ACCESSIBLE TRAP PRIMER VALVE BELOW LAVATORY TO SERVE SHOWER AND RESTROOM FLOOR DRAINS. 17. 1" CW/HW AND 3/4" HWR PIPING UP FROM BELOW. 18. 1-1/4" CW UP AND 3/4" HW/HWR PIPING UP FROM BELOW. 19. 2" CW, 1" HW AND 3/4" HWR PIPING UP FROM BELOW. 20. 3" SS DOWN AND 3" V PIPING UP. 21. 4" SS DOWN AND 4" V PIPING UP. L 1. DEMOLISH AND REPLACE ALL DOMESTIC COLD, HOT ,HOT WATER RETURN, DRAIN, WASTE AND VENT PIPING TO FIXTURES IN GANGED TOILET. RECONNECT EXISTING FIXTURES. REFER TO 1/P-601. 2. DEMOLISH AND REPLACE ALL DOMESTIC COLD, HOT DRAIN WASTE AND VENT PIPING TO BACK TO BACK LAVATORIES IN DORM ROOMS. PROVIDE 3/4" CONDENSATE DRAIN PIPING AT 8'-4" AFF AND SLOPE 1/8" PER FOOT FROM FAN COIL UNIT TO CHASE BEHIND LAVATORY. CONNECT CONDENSATE DRAIN TO SS THRU ACCESSIBLE AIR GAP IN CHASE BEHIND MEDICINE CABINET IN EACH ROOM. REFER TO 2/P-604. TYPICAL OF ALL. 3. DEMOLISH AND REPLACE ALL DOMESTIC COLD, HOT, DRAIN, WASTE AND VENT PIPING TO SINGLE LAVATORIES IN DORM ROOMS. PROVIDE 3/4" CONDENSATE DRAIN PIPING AT 8'-4" AFF AND 1/8" PER FOOT FROM FAN COIL UNIT TO CHASE BEHIND LAVATORY. CONNECT CONDENSATE DRAIN TO SS THRU ACCESSIBLE AIR GAP IN CHASE BEHIND MEDICINE CABINET IN EACH ROOM. REFER TO 4/P-601. TYPICAL OF ALL. 4. DEMOLISH AND REPLACE ALL DOMESTIC COLD, HOT, HOT WATER RETURN, DRAIN, WASTE AND VENT PIPING TO FIXTURES IN SHOWER ROOM. RECONNECT EXISTING FIXTURES. REFER TO 3/P-601. 5. DEMOLISH AND REPLACE ALL DOMESTIC COLD, HOT, DRAIN ,WASTE AND VENT PIPING TO FIXTURES IN RESTROOM. RECONNECT EXISTING FIXTURES. REFER TO 5/P-601. 6. DEMOLISH AND REPLACE ALL DOMESTIC COLD, HOT, HOT WATER RETURN, DRAIN WASTE, AND VENT PIPING TO LAVATORIES. RECONNECT EXISTING FIXTURES. REFER TO 6/P-601. 7. COORDINATE PLUMBING PIPING IN THIS AREA WITH EXHAUST DUCT SHOWN ON M-401. 8. COORDINATE PLUMBING PIPING IN THIS AREA WITH OA SUPPLY DUCT AND HEATING/CHILLED WATER RISER SHOWN ON M-401. 9. REFER TO 1/P-601 FOR ADDITIONAL INFORMATION. 10.REINSTALL EXISTING HYDRATION STATION IN THIS LOCATION AND CONNECT 1/2" CW COPPER DOMESTIC WATER PIPING. D 5 GENERAL NOTES 4 SHEET KEYNOTES P 3 SHEET KEYNOTES 2 L IC E NS E D 1 L A H O MA 18 A University of Central Oklahoma Murdaugh Hall Renovation A DORM 366 C DORM 322 DORM 321 3/4" DRAIN LINE FROM FCU TO CHASE (TYP. OF ALL) P-1 P-1 P-1 TYP. 3 P-1 P-1 DORM 365 DORM 363 DORM 364 17 7 20 7 P-1 MECH. 301A DORM 360 21 15 P-4 P-4 15 P-1 14 10 DORM 358 5 DORM 342 DORM 338 DORM 340 DORM 334 DORM 336 P-1 P-1 1 P-1 DORM 326 DORM 328 P-1 P-1 P-1 6 P-1 VENT UP 15 (TYP) DORM 313 5 MECH. 318A 21 SS UP TO FIXT ABV (TYP) 15 8 CORR. H300 18 18 DORM 311 CORR. H301 STAIR S31 STAIR S34 B P-1 P-1 P-1 DORM 354 CORR. H302 P-1 5 DORM 343 4/15/2016 3:18:20 PM B 14 1 MEN'S RR 318 P-1 P-5 8 P-1 DORM 330 P-1 P-2 10 MECH. 361A DORM 356 DORM 332 13 P-1 P-1 21 P-2 16 TP-1 2" DORM 2" 324 DORM 315 11 12 FD-1 TP-1 16 2" 2" DORM 344 1 6 MEN'S RR 361 P-1 CO-1 CO-1 FD-1 12 P-3 19 11 13 FD-1 12 4 P-3 19 DORM 317 FD-1 12 21 P-1 15 P-4 P-4 15 4 B DORM 319 P-1 DORM 362 B C DORM 320 11 11 20 P-1 TYP. 2 17 P-1 P-1 DORM 339 DORM 341 P-1 P-1 DORM 337 DORM 335 P-1 P-1 DORM 333 DORM 331 P-1 P-1 DORM 329 P-1 DORM 325 DORM 327 DORM 323 18 C REVISION HISTORY: 18 C 21 11 DORM 351 DORM 352 DORM 309 5 11 21 DORM 308 DORM 307 P-1 P-1 P-1 P-1 P-1 P-1 P-1 P-1 DORM 350 Edmond, Oklahoma FAN COIL UNIT ABV CEILING (TYP.) DORM 306 DORM 349 DORM 305 1 Addendum 02 DESCRIPTION 04/18/16 DATE PROJECT INFORMATION: C:\Users\meb\Documents\My Revit\41700_Plbg_meb.rvt DORM 348 A DORM 347 6 7 9 8 10 11 12 13 DORM 304 14 RDR DRAWN BY: RDR P-1 P-1 P-1 P-1 P-1 P-1 P-1 P-1 DORM 302 DORM 345 DORM 346 DESIGNED BY: DORM 303 REVIEWED BY: BAS A DORM 301 PROJECT MANAGER: TJC PROJECT NUMBER: 20141700 SHEET TITLE: D D 1 1 2 3 THIRD FLOOR PLUMBING PLAN SCALE: 1/8" = 1'-0" ISSUE DATE: 4 15 16 17 18 03/30/16 SHEET NUMBER: N 0 1 2 3 THIRD FLOOR PLUMBING PLAN 4 5 4' 8' 16' P-104 3 15 4 DORM 6 163 2 18 OK 2 P-1 14 P-4 SS PIPING UP TO FIXT ON FLR ABV. (TYP) 14 P-4 2" MEN'S RR 3 161 2" FD-1 11 MEN'S RR 118 3 FD-1 11 16 P-3 P-3 14 P-4 19 4" 2" SS UP TO FCO 19 10 10 2" B 2" 13 2 MEN'S RR 161 SS PIPING UP TO FIXT ABV. (TYP) 1 2" 1-1/2" V 2" V UP CO-1 21 MEN'S RR 118 2" SS UP VENT UP (TYP) 8 2" SS UP 3" 4 2" RR 124A 4" SS UP 4" 4" 9 4" MECH. 161A 17 DORM 113 2" V UP 4" CORR. H169 4" SS PIPING UP TO FIXT ABV (TYP) 1-1/2" V 2" 2" 4 4" SS UP P-1 1 2" 3" 2" SS UP RR 144A 9 11 FD-1 5 2" SS UP DORM 158 13 2" HALL DIRECTOR APARTMENT 144 2" B 2 5 21 CO-1 2" P-1 TP-1 15 2" FD-1 11 P-1 B 12 B B 15 TP-1 DORM 156 P-2 DORM 115 P-2 12 P-1 C 16 P-4 14 4" DORM 160 University of Central Oklahoma Murdaugh Hall Renovation DORM 117 DORM 162 C CORR. H101 4" 17 7 7 DORM 111 CORR. H172 B CORR. H174 1 P-1 4/15/2016 3:18:05 PM L A H O MA MECH. 2" 101A MECH. 168 16 GARY W. JAMES 16166 DORM 119 16 P-1 F E S S I O NA 18 6 2" 2" 2" DORM 120 18 10 10 17 D RO MECHANICAL CLOSET 100B 2 2" P-1 2 REVISION HISTORY: 21 CO-1 RR 141B CO-1 21 P-1 P-5 HK CLOSET 100E Edmond, Oklahoma DORM 164 16 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com G INEER 2 Frankfurt Short Bruza Architects Engineers Planners EN 1 A. REFER TO SHEET P-001 FOR GENERAL NOTES APPLICABLE TO THIS SHEET. B. ALL EXISTING PLUMBING PIPING FROM ABOVE BASEMENT FLOOR TO BELOW ROOF SHALL BE DEMOLISHED. EXISTING PIPE ROUTING IS SIMILAR TO NEW PIPE ROUTING SHOWN. ALL PIPE SIZES SHOWN ARE FOR NEW PIPING. EXISTING PIPE SIZES AND ROUTING MAY DIFFER FROM THOSE SHOWN. C. ALL EXISTING WALL HUNG LAVATORIES IN DORM ROOMS SHALL BE DEMOLISHED UNLESS NOTED OTHERWISE D. EACH BATHROOM SHALL BE PROVIDED ISOLATION SHUTOFF VALVES FOR ALL DOMESTIC WATER PIPING. ACCESS PANEL SHALL BE PROVIDED NO HIGHER THAN 5 FEET AFF FOR EMERGENCY SHUTOFF. L 9. REINSTALL EXISTING HYDRATION STATION IN THIS LOCATION. CONNECT 1/2" CW DOMESTIC WATER PIPING AND DRAIN LINE. 10. COORDINATE ACCESS PANEL LOCATION WITH SHUTOFF VALVES FOR EACH SET OF RESTROOMS. 11. EXISTING FLOOR DRAIN TO DEMOLISHED AND REPLACED WITH TRAP PRIMER FLOOR DRAIN. PROTECT DURING NEW CONSTRUCTION AND CONNECT NEW DRAIN PER 1/P-601. 12. 2" VENT RISER UP. 13. 3" VENT RISER UP. 14. INSTALL NEW SHOWERHEAD AT 6'-6" AFF. 15. ACCESSIBLE TRAP PRIMER VALVE BELOW LAVATORY TO SERVE SHOWER AND RESTROOM FLOOR DRAINS. 16. 4" SS PIPING UP AND DOWN. 17. 4" SS UP FROM BELOW TO ABOVE AND 3" V PIPING UP FROM BELOW TO FLOOR ABOVE. 18. 1-1/4" CW/HW UP FROM BELOW TO ABOVE AND 3/4' HWR PIPING DOWN FROM ABOVE. 19. 2" CW UP FROM BELOW TO ABOVE, 1-1/2" HW UP FROM BELOW AND 1-1/4" HW PIPING UP TO FLOOR ABOVE. 3/4" HWR PIPING DOWN FROM ABOVE. 20. 2" CW UP FROM BELOW AND 1-1/2" CW PIPING UP TO FLOOR ABOVE. 1-1/2" HW UP FROM BELOW AND 1-1/4" HW PIPING UP TO FLOOR ABOVE. 3/4" HWR PIPING DOWN FROM ABOVE TO BELOW. 21. INSTALL ACCESS PANEL IN CEILING FOR CLEANOUT ABOVE. 1. DEMOLISH AND REPLACE ALL DOMESTIC COLD, HOT, HOT WATER RETURN, DRAIN, WASTE AND VENT PIPING TO FIXTURES IN GANGED TOILET. RECONNECT EXISTING FIXTURES. REFER TO 1/P-601. 2. DEMOLISH AND REPLACE ALL DOMESTIC COLD, HOT, DRAIN, WASTE AND VENT PIPING TO BACK TO BACK LAVATORIES IN DORM ROOMS. PROVIDE 3/4" CONDENSATE DRAIN PIPING AT 8'-4" AFF AND SLOPE 1/8" PER FOOT FROM FCU TO CHASE BEHIND LAVATORY. CONNECT CONDENSATE DRAIN TO SS THRU ACCESSIBLE AIR-GAP IN CHASE BEHIND MEDICINE CABINET IN EACH ROOM. REFER TO 2/P-601. TYPICAL OF ALL. 3. DEMOLISH AND REPLACE ALL DOMESTIC COLD, HOT, HOT WATER RETURN, DRAIN, WASTE AND VENT PIPING TO FIXTURES IN SHOWER ROOM. RECONNECT EXISTING FIXTURE. REFER TO 3/P-601. 4. DEMOLISH AND REPLACE ALL DOMESTIC COLD, HOT, DRAIN, WASTE AND VENT PIPING TO FIXTURE IN BATHROOM. RECONNECT EXISTING FIXTURES. REFER TO 5P-601. 5. DEMOLISH AND REPLACE ALL DOMESTIC COLD, HOT, HOT WATER RETURN, DRAIN, WASTE AND VENT PIPING TO LAVATORIES. RECONNECT EXISTING FIXTURES. REFER TO 6/P-601. 6. COORDINATE PLUMBING PIPING IN THIS AREA WITH EXHAUST DUCT SHOWN ON SHEET M-401. 7. COORDINATE PLUMBING PIPING IN THIS AREA WITH OA SUPPLY DUCT AND HEATING/CHILLED WATER RISERS SHOWN ON SHEET M-401. 8. REFER TO 1/P-601 FOR ADDITIONAL INFORMATION. D 5 GENERAL NOTES 4 SHEET KEYNOTES P 3 SHEET KEYNOTES 2 L IC E NS E D 1 P-1 RR 123B 4 DORM 154 4 BONUS DORM ROOM 4" 141A 2" DORM 109 2" STAIR S11 STAIR S14 DORM 151 DORM 152 17 20 10 10 C 20 17 1 DORM 108 DORM 107 04/18/16 DESCRIPTION C C Addendum 02 DATE PROJECT INFORMATION: C DESIGNED BY: RDR DRAWN BY: RDR C:\Users\meb\Documents\My Revit\41700_Plbg_meb.rvt REVIEWED BY: 1 A 2 3 15 4 16 17 BAS 18 A PROJECT MANAGER: TJC PROJECT NUMBER: NOTE: FIRST FLOOR SHOWN, SECOND AND THIRD FLOOR SIMILAR. 1 20141700 NOTE: FIRST FLOOR SHOWN, SECOND AND THIRD FLOOR SIMILAR. ENLARGED PLUMBING PLAN -WEST 2 SCALE: 1/4" = 1'-0" SHEET TITLE: ENLARGED PLUMBING PLAN ENLARGED PLUMBING PLAN - EAST SCALE: 1/4" = 1'-0" ISSUE DATE: 03/30/16 SHEET NUMBER: N 0 1 2 3 4 5 2' 4' 8' P-401 5 SHEET KEYNOTES 6 5 7 9 8 10 11 12 13 14 15 16 17 18 A A ELECTRICAL ROOM-3 007-3 1 IT-2 014-2 G8 G8 8 1 RESTROOM 008 G8 C 9 STORAGE-2 010A-2 C 1 G8 G8 EMW1 - 25 PC VIA "LC1" G8 G8 9 10 RESTROOM 009 MECHANICAL ROOM-2 CORR. 006-2 01AD X MECHANICAL ROOM-2 006A-2 STORAGE-5 013-5 STORAGE 010 G8 M MAINT. OFFICE-2 014C-2 CORR.-9 014B-9 B B 1 M G8 X G8 X G8 G8 J G8 G8 G8 MAINTENANCE SHOP-5 012-5 3 G8 G8 3 PC VIA "LC1" 2 3 EMW1 - 24 3 X 9 G8 INVENTORY OFFICE-3 014D-3 10 3 1 STORAGE-2 011-2 J X X STAIR 01B G8 HALL 011B STAIR 002 EMW1 - 1 STAIR-2 011A-2 CORR.-3 H015-3 G8 ELECTRICAL 004C ELECTRICAL CLOSET-4 004A-4 HYDRONIC PUMP RM 004B SHOWERS-4 022-4 9 C RESTROOM 011C X G4 STAIR S02 0PW1 - 11 G4 0PE1 - 9 EMW1 - 17 FIRE PUMP ROOM-3 005-3 B 4/15/2016 2:56:06 PM G4 G4 3 G8 10 3 STORAGE-19 001B-19 STAIR S04 CORR. H024 9 M B OFFICE TORNADO SHELTER-2 016-2 RESTROOM 023 G8 GARY W. JAMES 16166 OK IT ROOM-8 014A-8 CLOSET 007A 1 F E S S I O NA L A H O MA C Edmond, Oklahoma 4 D RO G INEER 3 2 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com EN 1 Frankfurt Short Bruza Architects Engineers Planners L D 1. EXISTING LIGHTS TO REMAIN IN THIS AREA. DISCONNECT AND REMOVE EXISTING WIRING AND CONDUITS. PROVIDE NEW WIRING AND CONDUITS TO SERVE EXISTING LIGHTS. CONNECT LIGHTS IN THIS AREA TO PANEL "0PE1", CIRCUIT #11. 2. EXISTING LIGHTS TO REMAIN IN THIS AREA. DISCONNECT AND REMOVE EXISTING WIRING AND CONDUITS. PROVIDE NEW WIRING AND CONDUITS TO SERVE EXISTING LIGHTS. CONNECT LIGHTS IN THIS AREA TO PANEL "0PE1", CIRCUIT #12. 3. EXISTING LIGHTS TO REMAIN IN THIS AREA. DISCONNECT AND REMOVE EXISTING WIRING AND CONDUITS. PROVIDE NEW WIRING AND CONDUITS TO SERVE EXISTING LIGHTS. CONNECT LIGHTS IN THIS AREA TO PANEL "0PE1", CIRCUIT #13. 4. EXISTING LIGHTS TO REMAIN IN THIS AREA. DISCONNECT AND REMOVE EXISTING WIRING AND CONDUITS. PROVIDE NEW WIRING AND CONDUITS TO SERVE EXISTING LIGHTS. CONNECT LIGHTS IN THIS AREA TO PANEL "0PE1", CIRCUIT #14. 5. EXISTING LIGHTS TO REMAIN IN THIS AREA. DISCONNECT AND REMOVE EXISTING WIRING AND CONDUITS. PROVIDE NEW WIRING AND CONDUITS TO SERVE EXISTING LIGHTS. CONNECT LIGHTS IN THIS AREA TO PANEL "0PE2", CIRCUIT #5. 6. EXISTING LIGHTS TO REMAIN IN THIS AREA. DISCONNECT AND REMOVE EXISTING WIRING AND CONDUITS. PROVIDE NEW WIRING AND CONDUITS TO SERVE EXISTING LIGHTS. CONNECT LIGHTS IN THIS AREA TO PANEL "0PW1", CIRCUIT #7. 7. EXISTING LIGHTS TO REMAIN IN THIS AREA. DISCONNECT AND REMOVE EXISTING WIRING AND CONDUITS. PROVIDE NEW WIRING AND CONDUITS TO SERVE EXISTING LIGHTS. CONNECT LIGHTS IN THIS AREA TO PANEL "0PW1", CIRCUIT #13. 8. EXISTING LIGHTS TO REMAIN IN THIS AREA. DISCONNECT AND REMOVE EXISTING WIRING AND CONDUITS. PROVIDE NEW WIRING AND CONDUITS TO SERVE EXISTING LIGHTS. CONNECT LIGHTS IN THIS AREA TO PANEL "0PW1", CIRCUIT #15. 9. CONNECT ONE EXISTING LIGHT FIXTURE IN THIS AREA TO EMERGENCY CIRCUIT "EMW1-17". 10.EXISTING LIGHT FIXTURE TO REMAIN. CONTRACTOR MAY RE-USE EXISTING CONDUITS SERVING EXISTING EXTERIOR LIGHT FIXTURES. University of Central Oklahoma Murdaugh Hall Renovation 4 P 3 2 L IC E NS E D 1 REVISION HISTORY: 0PE1 - 15 7 3 9 5 G8 LAUNDRY-3 020-3 6 TORNADO SHELTER-16 017-16 G8 10 1 M 5 6 7 9 8 10 11 12 13 14 ADDENDUM 002 4/18/16 DESCRIPTION DATE PROJECT INFORMATION: DESIGNED BY: PC VIA "LC1" KITCHENETTE-3 019-3 FS/MBK EMW1 - 27 DRAWN BY: MBK 1 1 BIKE SHOP-6 018-6 C:\Users\mxk\Documents\My Revit\41700_Elec_mxk.rvt 9 9 REVIEWED BY: JTL 4 A A D PROJECT MANAGER: TJC PROJECT NUMBER: D 20141700 SHEET TITLE: BASEMENT LIGHTING PLAN 1 2 3 4 15 1 16 17 18 ISSUE DATE: BASEMENT LIGHTING PLAN 03/30/16 SCALE: 1/8" = 1'-0" SHEET NUMBER: N 0 1 2 3 4 5 4' 8' 16' EL100 7 9 8 10 11 12 13 14 15 16 17 M 18 SHEET KEYNOTES 1 10 10 M M 11 A A E X E 6 TYPICAL X J J 1PW1 - 38 DORM 165 D D DORM 166 DORM 122 J D D D 1PE1 - 38 DORM 121 J E DORM 164 D 10 M D M DORM 163 D DORM 120 DORM 119 J DORM 162 J MECH. 168 D D 8 EP401 7 EP401 D D DORM 117 MEN'S RR 118 10 E M 7 DORM 160 B VIA "LC1" D 10 D DORM 158 M M DORM 115 D D D 1PW1 - 63 HALL DIRECTOR APARTMENT 144 D DORM 9 156 FRONT DESK 128 2 STORAGE-18 001B-18 6 RR 141B D D 1 J X STORAGE-15 001B-15 M STAIR-1 011A-1 1 X EMW1 - 19 1PW1 - 36 DORM 151 J CORR. H174 1PE1 - 51 EMW1 - 2 1 X HOUSEKEEPING CLOSET 100F A 1 2 2 STAIR S12 3 J HOUSEKEEPING CLOSET 1PE1 - 49 100E RR 123B A BONUS DORM ROOM 123 D D DORM 109 BONUS DORM ROOM 123A C 4 EP401 5 4 EMW1 - 8 X PC D X J 10 B M E M M GAME ROOM 130A 10 DORM 106 10 M 1 DORM 107 J 1PE1 - 63 DORM 149 1PE1 - 36 D DORM 108 1 EMW1 - 8 4 4 1PE1 - 34 1 M D DORM 111 E C M 10 4/15/2016 2:56:39 PM 1PE1 - 48 3 1 2 1 M D RR 124A 10 DORM 113 D 1 PC E X X 1 D DORM 150 CORR.-2 H015-2 2 D J D A LOUNGE 130 2 X BONUS DORM ROOM 143 1PW1 - 58 C DORM 152 2 1 BONUS DORM ROOM 141A 10 M BONUS DORM ROOM 124 1PE1 - 61 1PW1 - 50 1PW1 - 34 2 J J EMW1 - 3 3 J RA OFFICE 126 EMW1 - 21 E 1PW1 - 37 X RR 144A 1 TYPICAL X HALL DIRECTOR APARTMENT 140 3 DORM 9 154 B J 1PW1 - 49 2 EP401 1 C 1PE1 - 37 8 J MEN'S RR 161 B 10 D DORM 105 D GARY W. JAMES 16166 OK E EMW1 - 28 C D L A H O MA 10 REVISION HISTORY: D D DORM 148 DORM 147 J 5 6 7 8 9 10 11 12 13 D DORM 104 14 J D DORM 146 DORM 103 J E D DORM 102 DORM 145 D X DORM 101 D X E E D D J E D 1 4/18/16 DESCRIPTION DATE PROJECT INFORMATION: 10 1 ADDENDUM 002 M M 3 2 1 4 15 16 DESIGNED BY: 10 17 FS/MBK 18 DRAWN BY: EMW1 - 26 MBK PC VIA "LC1" C:\Users\mxk\Documents\My Revit\41700_Elec_mxk.rvt G INEER EMW1 - 24 1. EXISTING LIGHT FIXTURE TO REMAIN. 2. EXISTING CHANDELIER FIXTURE TO REMAIN IN BASE BID. DISCONNECT FROM EXISTING WIRING AND RECONNECT TO NEW WIRING CIRCUITING. IN ALTERNATE 1, REPLACE EXISTING FIXTURE "J" WITH NEW FIXTURE "JA" WITH NEW WIRING AND NEW CONDUITS. 3. LIGHTING CONTROLLER ABOVE CEILING. 4. EXISTING FAN AND LIGHT FIXTURE TO REMAIN, DISCONNECT FROM EXISTING CIRCUIT AND PULL NEW WIRE INTO EXISTING CONDUIT EMBEDDED IN CONCRETE DECK, RECONNECT NEW WIRING TO PANEL "1PE1", CIRCUIT #50. 5. CEILING FANS CONTROLS BOX TO REMAIN. 6. JUNCTION BOX IN CLOSET FOR DORM ROOM LIGHTING. INSTALL JUNCTION BOX ABOVE CEILING. 7. RE-LOCATE EXISTING LIGHT FIXTURES IN MANAGER'S APARTMENT. REFER TO OWNER'S EXISTING PLANS FOR NEW LOCATION. CONNECT TO BREAKER IN NEW ELECTRICAL PANEL "1PW1". 8. RECONNECT EXISTING LIGHTS TO NEW BREAKER IN NEW ELECTRICAL PANEL "IPE1". 9. ROOMS 154 & 156 ARE TO BE COMPLETED FIRST AS MOCK-UP ROOMS. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH GENERAL CONTRACTOR AND ARCHITECT. 10.EXISTING LIGHT FIXTURE TO REMAIN. CONTRACTOR MAY RE-USE EXISTING CONDUITS SERVING EXISTING EXTERIOR LIGHT FIXTURES. 11.PHOTO CELL TO CONTROL EXTERIOR LIGHTS. MOUNT ON WALL AS HIGH AS POSSIBLE, SHEILD FROM STRAY LIGHT. F E S S I O NA EN PC VIA "LC1" RO Edmond, Oklahoma 6 5 University of Central Oklahoma Murdaugh Hall Renovation 4 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com L D 3 M Frankfurt Short Bruza Architects Engineers Planners 10 EMW1 - 25 2 A. REFER TO ARCHITECTURAL SHEETS FOR EXACT LOCATION & MOUNTING HEIGHT OF PHOTOLUMINESCENT EXIT SIGNS. B. REFER TO SHEET EP401, DETAIL 2 FOR DORM ROOM LIGHTING CIRCUITING. C. NOT ALL MATERIALS THAT EXIST IN THE WORK AREA HAVE BEEN SHOWN. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS IN THE AREA OF CONSTRUCTION PRIOR TO BID. 1 PC VIA "LC1" 10 1 5 GENERAL NOTES 4 P 3 2 L IC E NS E D 1 A 1 M REVIEWED BY: 10 FIRST FLOOR LIGHTING PLAN JTL A M SCALE: 1/8" = 1'-0" PROJECT MANAGER: TJC PROJECT NUMBER: 10 20141700 EMW1 - 27 SHEET TITLE: FIRST FLOOR LIGHTING PLAN ISSUE DATE: 03/30/16 SHEET NUMBER: N 0 1 2 3 4 5 4' 8' 16' EL101 5 GENERAL NOTES 4 A. REFER TO ARCHITECTURAL SHEETS FOR EXACT LOCATION & MOUNTING HEIGHT OF PHOTOLUMINESCENT EXIT SIGNS. B. REFER TO SHEET EP401, DETAIL 2 FOR DORM ROOM LIGHTING CIRCUITING. C. NOT ALL MATERIALS THAT EXIST IN THE WORK AREA HAVE BEEN SHOWN. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS IN THE AREA OF CONSTRUCTION PRIOR TO BID. SHEET KEYNOTES 1 PC EMW1 - 24 1 1 EMW1 - 25 2 3 M 4 7 5 9 8 10 11 12 14 15 16 17 M 18 1. LIGHTING CONTROLLER ABOVE CEILING. 2. JUNCTION BOX IN CLOSET FOR DORM ROOM LIGHTING. INSTALL JUNCTION BOX ABOVE CEILING. 3. EXISTING LIGHT FIXTURE TO REMAIN. 4. EXISTING LIGHT FIXTURE TO REMAIN. CONTRACTOR MAY RE-USE EXISTING CONDUITS SERVING EXISTING EXTERIOR LIGHT FIXTURES. D F E S S I O NA GARY W. JAMES 16166 OK G INEER 1 VIA "LC1" PC RO EN VIA "LC1" 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com L D Frankfurt Short Bruza Architects Engineers Planners P 3 2 L IC E NS E D 1 L A H O MA 4 4 2 A TYPICAL M M E E X A X J D DORM 266 DORM 222 DORM 265 D J DORM 221 J E E DORM 264 D DORM 220 DORM 263 D 2PE2 - 7 D D DORM 219 D J C J D DORM 262 MECH. 202A D MECH. 201A D D E E 2PE2 - 6 2PW2 - 3 D DORM 260 B C DORM 217 D MEN'S RR 218 MEN'S RR 261 J DORM 234 DORM 242 DORM 240 D 2PW2 - 5 D 2PW2 - 6 DORM 238 DORM 230 DORM 232 DORM 236 DORM 228 2PE2 - 1 DORM 226 2PE2 - 3 D EMW1 - 5 1 DORM 256 J D D X X E D 1 STAIR S22 2PW2 - 20 J J J D D J 3 D E D J D D J D E D J D J D D D D D 1 X E DORM 254 EMW1 - 4 DORM 213 J J J DORM 211 E X D 1 STAIR S21 2PE2 - 20 J EMW1 - 8 J EMW1 - 8 PC D D 1 2PE2 - 21 D D E E 1 J B 2PE2 - 19 J 2PW2 - 21 DORM 215 DORM 224 2PW2 - 18 1 D J DORM 244 DORM 258 D 2PW2 - 7 D DORM 243 H DORM 241 DORM 239 DORM 237 B DORM 235 DORM 233 DORM 231 DORM 229 2PE2 - 2 DORM 227 DORM 223 DORM 225 D D PC DORM 209 H B C C D 2PE2 - 4 D D 2PW2 - 1 2PW2 - 2 DORM 251 DORM 252 4/15/2016 2:56:13 PM DORM 208 J J E DORM 248 DORM 207 J J DORM 250 2PE2 - 5 E 6 EP401 D D D D REVISION HISTORY: DORM 249 DORM 206 DORM 247 DORM 204 5 6 7 8 9 10 11 12 13 14 J J D D D D D DORM 205 DORM 203 J J E E 1 D DORM 246 X D D Edmond, Oklahoma D University of Central Oklahoma Murdaugh Hall Renovation 2PW2 - 4 J DORM 202 DORM 245 D DESCRIPTION DATE DESIGNED BY: FS/MBK DRAWN BY: X E E 4/18/16 PROJECT INFORMATION: DORM 201 D ADDENDUM 002 MBK D REVIEWED BY: C:\Users\mxk\Documents\My Revit\41700_Elec_mxk.rvt A 1 JTL M M 3 2 4 15 16 4 17 A 18 PROJECT MANAGER: TJC PROJECT NUMBER: 20141700 4 SHEET TITLE: 1 M SECOND FLOOR LIGHTING PLAN SECOND FLOOR LIGHTING PLAN SCALE: 1/8" = 1'-0" M 1 EMW1 - 26 PC VIA "LC1" EMW1 - 27 ISSUE DATE: PC VIA "LC1" 1 03/30/16 SHEET NUMBER: N 0 1 2 3 4 5 4' 8' 16' EL102 5 GENERAL NOTES 4 A. REFER TO ARCHITECTURAL SHEETS FOR EXACT LOCATION & MOUNTING HEIGHT OF PHOTOLUMINESCENT EXIT SIGNS. B. REFER TO SHEET EP401, DETAIL 2 FOR DORM ROOM LIGHTING CIRCUITING. C. NOT ALL MATERIALS THAT EXIST IN THE WORK AREA HAVE BEEN SHOWN. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS IN THE AREA OF CONSTRUCTION PRIOR TO BID. SHEET KEYNOTES EMW1 - 25 EMW1 - 24 1 1 VIA "LC1" PC PC 2 3 M 4 7 5 9 8 10 11 12 14 15 16 M 17 18 D F E S S I O NA GARY W. JAMES 16166 OK G INEER VIA "LC1" 1 1. LIGHTING CONTROLLER ABOVE CEILING. 2. JUNCTION BOX IN CLOSET FOR DORM ROOM LIGHTING. INSTALL JUNCTION BOX ABOVE CEILING. 3. EXISTING LIGHT FIXTURE TO REMAIN. 4. EXISTING LIGHT FIXTURE TO REMAIN. CONTRACTOR MAY RE-USE EXISTING CONDUITS SERVING EXISTING EXTERIOR LIGHT FIXTURES. RO EN 1 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com L D Frankfurt Short Bruza Architects Engineers Planners P 3 2 L IC E NS E D 1 L A H O MA 4 4 2 M A A E X E X J J D D DORM 322 3PE2 - 7 D DORM 321 J J E E D DORM 364 D DORM 363 D DORM 320 DORM 319 D J J C MECH. 302A D DORM 362 C MECH. 301A D D D DORM 317 E E 3PE2 - 6 3PW2 - 3 D D DORM 360 B MEN'S RR 318 MEN'S RR 361 D J J DORM 344 DORM 358 D DORM 342 3PW2 - 5 D DORM 340 DORM 338 DORM 336 DORM 334 DORM 330 DORM 332 DORM 328 D 3PE2 - 1 3PW2 - 6 DORM 315 B DORM 324 DORM 326 3PE2 - 3 DORM 313 D 3PW2 - 20 3PE2 - 19 J E 1 X E D J D D D D D J 1 DORM 354 E D D D D D 3 E D D D D J E D D J DORM 343 H DORM 341 DORM 339 1 J DORM 337 DORM 333 DORM 331 DORM 329 DORM 327 DORM 311 E X D STAIR S31 J EMW1 - 8 3PE2 - 22 PC 3PE2 - 2 DORM 335 EMW1 - 6 1 X E J 3PW2 - 7 S34 D D E 1 J J EMW1 - 8 PC STAIR D 1 J J J 3PE2 - 21 D X 3PW2 - 21 J 3PW2 - 22 EMW1 - 7 DORM 356 J J 1 B D D DORM 309 D DORM 323 DORM 325 H B C C D 3PW2 - 1 D D DORM 352 4/15/2016 2:56:18 PM 3PE2 - 4 3PW2 - 2 DORM 307 J J J E DORM 350 DORM 348 3PE2 - 5 DORM 308 DORM 351 J D Edmond, Oklahoma D DORM 365 University of Central Oklahoma Murdaugh Hall Renovation 3PW2 - 4 DORM 366 TYPICAL M REVISION HISTORY: E D D D D J DORM 349 DORM 306 DORM 347 DORM 304 5 6 7 8 9 10 11 12 13 14 D D D D DORM 303 J J DORM 305 J 1 ADDENDUM 002 4/18/16 DESCRIPTION DATE E E PROJECT INFORMATION: DORM 346 D X C:\Users\mxk\Documents\My Revit\41700_Elec_mxk.rvt D A DORM 345 D DORM 302 DESIGNED BY: D D FS/MBK DORM 301 DRAWN BY: MBK REVIEWED BY: X E E JTL D A M M PROJECT MANAGER: TJC PROJECT NUMBER: 1 3 2 4 15 16 17 4 SHEET TITLE: THIRD FLOOR LIGHTING PLAN 4 M 1 EMW1 - 26 PC VIA "LC1" 20141700 18 THIRD FLOOR LIGHTING PLAN M ISSUE DATE: 1 SCALE: 1/8" = 1'-0" 03/30/16 EMW1 - 27 PC VIA "LC1" 1 SHEET NUMBER: N 0 1 2 3 4 5 4' 8' 16' EL103 1 3 2 5 4 Frankfurt Short Bruza Architects Engineers Planners 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com LIGHTING FIXTURE SCHEDULE GRY BLK EAST CORRIDOR COVE LIGHT FIXTURES GRY NOTES SURFACE IN COVE WALL BRACKET ABOVE MIRROR SURFACE IN COVE RECESSED CEILING MOUNTED SURFACE-MOUNT TO BOTTOM OF JOIST CORRIDOR COVE LIGHTING DIMMABLE 6" EVO DOWNLIGHT SURFACE IN COVE LOBBY LIGHTING PENDANT WALL MOUNTED WALL MOUNTED STAIRS LIGHTING FLICKER - FREE DIMMING TO DARK FLICKER - FREE DIMMING TO DARK BLK 1/2 CENTER CORRIDOR LIGHT FIXTURES VIO NEUTRAL WHT NEUTRAL WHT UNSWITCHED BLK 120/277 UNSWITCHED BLK 120/277 UNSWITCHED BLK 120/277 C GRN 0 TO 10 VOLT DIMMING OUTPUT. EARTH GROUND CLASS 2 LOW VOLTAGE WIRING 2 #18 AWG. TYPICAL CAT5E CABLE. (TYPICAL) 0 TO 10 VOLT DIMMING OUTPUT. 0 TO 10 VOLT DIMMING OUTPUT. CAT5E CABLE. (TYPICAL) CLASS 2 LOW VOLTAGE WIRING 2 #18 AWG. TYPICAL CAT5E CABLE. (TYPICAL) NOTES - TYPICAL CORRIDOR LIGHTING CONTROL DETAILS 1 1. THIS CONTROL DETAIL APPLIES TO ALL DORM ROOM CORRIDOR COVE LIGHTS. 2. CORRIDOR LIGHTS TO BE ON AT 100% DURING THE DAY AND SHALL BE DIMMED TO 30% AT NIGHT. PROGRAM SYSTEM SO THAT THE "ON" SIGNAL FROM THE TIME CLOCK TURNS LIGHTS ON AT FULL BRIGHTNESS AND THE "OFF" SIGNAL DIMS THE LIGHTS TO 30%. COORDINATE "ON/OFF" TIMES WITH OWNER. 3. ROOM CONTROLLERS IN THE CORRIDORS SHALL BE EQUAL TO WATTSTOPPER #LMRC-211. 4. DIGITAL INTERFACE MODULE EQUAL TO: WATTSTOPPER LM10-101. 5. TIME CLOCK EQUAL TO: TORK #DZM200DP-Q. 2 CHANNEL, CHANNEL 1 TO CONTROL EAST CORRIDOR LIGHTS ON FLOORS 1, 2 AND 3. CHANNEL 2 TO CONTROL WEST CORRIDOR LIGHTS ON FLOORS 1, 2 AND 3, PROVIDE (1) TIME CLOCK TO CONTROL ALL CORRIDOR LIGHTS. 1 CLASS 2 LOW VOLTAGE WIRING 2 #18 AWG. TYPICAL 4/15/2016 2:56:41 PM B 1 F E S S I O NA GARY W. JAMES 16166 L A H O MA 1 SINGLE RELAY ON/OFF/0-10V DIMMING ROOM CONTROLLER GRY EARTH GROUND RO OK NEUTRAL WHT GRN D P LED LED FLUORESCENT LED LED LED LED LED LED EXISTING FLUORESCENT LED LED EXISTING SINGLE RELAY ON/OFF/0-10V DIMMING ROOM CONTROLLER DIGITAL INTERFACE MODULE TIME CLOCK 2 2 1 2 1 1 2 2 2 1 8 1 1 1 N.W. VIO EARTH GROUND CLASS 2 LOW VOLTAGE WIRING 2 #18 AWG. TYPICAL 120 120 120 120 120 120 120 120 120 120 120 120 120 120 MOUNTING B TYPICAL CORRIDOR LIGHTING CONTROL DIAGRAM Edmond, Oklahoma SINGLE RELAY ON/OFF/0-10V DIMMING ROOM CONTROLLER 96" SURFACE LED STRIP LIGHT VANITY LIGHT ROUND FLUORESCENT FIXTURE WITH BUILT-IN OCCUPANCY SENSOR 96" SURFACE LED STRIP LIGHT VOLUMETRIC RECESSED DOWNLIGHT WITH BATTERY DOWN LIGHT 48" PENDANT LED STRIP LIGHT 96" PENDANT LED STRIP LIGHT 48" SURFACE LED STRIP LIGHT EXISTING TO REMAIN ROUND PENDANT FLUORESCENT LIGHT FIXTURE ROUND 4 WALL LED ROUND 4 WALL LED WITH BATTERY EXISTING TO REMAIN EXIT SIGN - WHITE THERMOPLASTIC, GREEN LETTERS NUM. University of Central Oklahoma Murdaugh Hall Renovation N.W. VIO C ZL1N-L48-7000M-FST-MVOLT-40K-80CRI-WH P2901-09 001-g863-OCC ZL1N-L48-3000LM-FST-MVOLT-40K-80CRI-WH RT5D-LED-1700L-40K-120-DIM-ELR EVO-41/4100K-14-6AR-CLEAR-WD-LD-MVOLT ZL1N-L48-3000LM-FST-MVOLT-40K-80CRI-WH-WGZ48 ZL1N-L96-6000LM-FST-MVOLT-40K-80CRI-WH-WGZ48 RTL4-40L-MVOLT-EZ1-LP840 NA CP4174-6TF32-2FCS40/22(MVOLT)-OBA-ABA) RD4WA-HI/HI-14-120-SCT-EZB-LP840-CO32-DL RD4WA-HI/HI-14-120-1SE-EC--SCT-EZB-LP840-CO32-DL NA BLP101F-U-A-S-G VOLTS L IC E NS E D LITHONIA LIGHTING PROGRESS LIGHTING LEVITON LITHONIA LIGHTING LITHONIA LIGHTING GOTHAM LITHONIA LIGHTING LITHONIA LIGHTING LITHONIA LIGHTING NA OLYMPIA PEERLESS LIGHTING PEERLESS LIGHTING NA BRIGHT PATH LIGHTING DESCRIPTION G INEER BLK WEST CORRIDOR COVE LIGHT FIXTURES A B C D E F G4 G8 H J JA K KA M X MODEL NUMBER EN N.W. MANUFACTURER L D ID LAMPS TYPE REVISION HISTORY: SCALE: NTS 1 LC1 EMW1-24 TO EXTERIOR LIGHTS EMW1-25 TO EXTERIOR LIGHTS EMW1-26 TO EXTERIOR LIGHTS EMW1-27 TO EXTERIOR LIGHTS 1 ADDENDUM 002 4/18/16 DESCRIPTION DATE PROJECT INFORMATION: EMW1-28 TO EXTERIOR LIGHTS DESIGNED BY: FS/MBK DRAWN BY: C MBK REVIEWED BY: C:\Users\mxk\Documents\My Revit\41700_Elec_mxk.rvt H JTL EMW1-24 A A 120V N PC PHOTO-CELL ON ROOF EQUAL TO TORK #2021 PROJECT MANAGER: TJC PROJECT NUMBER: 20141700 SHEET TITLE: LIGHT FIXTURE SCHEDULE & LIGHTING CONTROL DIAGRAM 2 LIGHT CONTACTOR "LC1" DIAGRAM ISSUE DATE: SCALE: NTS 03/30/16 SHEET NUMBER: EL501 1 2 3 4 5 1 6 1. 2. 3. 4. 5. EXISTING PANELS TO REMAIN. EXISTING TO BE REMOVED. EXISTING TO BE REPLACED. NEW PANEL. PROPOSED NEW PAD MOUNT XFMR BY EDMOND ELECTRIC. CONTRACTOR TO INSTALL CONCRETE PAD TO MEET POWER COMPANY SPECIFICATIONS. 6. EXISTING 4" UNDERGROUND CONDUITS FOR PRIMARY CABLES TO REMAIN. 7. REWORK AND EXTEND EXISTING 4" CONDUITS TO NEW PAD MOUNT TRANSFORMER LOCATION. INSTALL A MINIMUM OF 48" BELOW GRADE. INSTALL CONDUITS PER EDMOND ELECTRIC REQUIREMENTS. 8. UTILIZE LONG RADIUS BENDS (MIN. 48"). 9. MAIN ELECTRICAL SERVICE SECONDARY FEEDER. REFER TO ELECTRICAL RISER DIAGRAM , SHEET EP501. 10.POWER FOR HVAC CONTROL PANELS. 11.SEE ELECTRICAL RISER DIAGRAM, SHEET EP501 FOR FIRE PUMP CIRCUITING. 12.INSTALL CAT6 DATA OUTLET FOR HVAC CONTROL PANEL CONNECTION. EXTEND CAT6 CABLE TO EXISTING DATA RACK IN "IT ROOM 014AH". COORDINATE TERMINATION OF CABLE AT DATA RACK WITH OWNER'S IT PERSONAL. APPROX. 44'-5" UNDERGROUND UTILITIES LINES 13. COMBINATION MOTOR STARTER, IN NEMA 1 ENCLOSURE. SURFACE MOUNT +48" AFF ON MECHANICAL AHU. SQUARE D CLASS 8539, TYPE SCG5- V02-C-P1-P2-X22, OR EQUAL. 14. ENCASE CONDUIT IN 3" OF CONCRETE AND BURY 36" BELOW FINISHED GRADE, NOMINAL. 15. EXISTING VFD DRIVES FOR EXISTING HEATING AND CHILLED WATER PUMPS TO REMAIN. RECONNECT TO NEW CIRCUIT AS INDICATED ON ONE LINE DIAGRAM ON SHEET EP501. 16. EXISTING HEATING AND CHILLED WATER PUMPS TO REMAIN. EXISTING WIRING AND CONDUIT BETWEEN MOTORS AND VFD DRIVES TO REMAIN. 17. REMOVE THE EXISTING ELECTRICAL PANEL AND ASSOCIATED FEEDER CONDUIT AND WIRE THAT SERVED THE EXISTING VFD DRIVES. 18. EXISTING EQUIPMENT, RECEPTACLES, AND ASSOCIATED WIRING AND CONDUIT ARE TO REMAIN IN THIS AREA. POWER SHALL BE MAINTAINED TO THIS AREA AT ALL TIMES. COORDINATE INSTALLATION OF NEW ELECTRICAL PANELS AND FEEDERS WITH THE OWNER TO PREVENT POWER OUTAGES TO CRITICAL EQUIPMENT. PROVIDE TEMPORARY POWER AS NECESSARY TO PREVENT ANY DOWN TIME. 1 3 2 4 6 5 7 9 8 10 11 12 13 14 15 16 17 Frankfurt Short Bruza Architects Engineers Planners 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com D RO F E S S I O NA GARY W. JAMES 16166 OK G INEER 5 19. RECONNECT THE EXISTING EQUIPMENT AND RECEPTACLES REMAINING IN THIS AREA TO NEW ELECTRICAL PANEL OPE1. 20. RECONNECT THE EXISTING EQUIPMENT AND RECEPTACLES REMAINING IN THIS AREA TO NEW ELECTRICAL PANEL OPE2. 21. RECONNECT THE EXISTING EQUIPMENT AND RECEPTACLES REMAINING IN THIS AREA TO NEW ELECTRICAL PANEL OPW1. 22. RECONNECT THE EXISTING EXTERIOR BUILDING LIGHT FIXTURES BEING SERVED FROM THE EXISTING ELECTRICAL PANEL BEING REMOVED TO SPARE BREAKERS IN THE NEW ELECTRICAL PANEL OPW1. 23. FLUSH IN GRADE PULL BOX SIZE AS REQUIRED BY NATIONAL ELECTRICAL CODE. 24. EMERGENCY FEEDER FROM GENERATOR TO TRANSFORMER SWITCHBOARD. REFER TO ELECTRICAL RISER DIAGRAM , SHEET EP501. 25. CONNECTION FOR FIRE ALARM POWER EXTENDER PANEL. EN 8 SHEET KEYNOTES L UNDERGROUND UTILITIES LINES D SHEET KEYNOTES A. REMOVE ALL EXISTING ELECTRICAL PANELS INDICATED TO BE REMOVED. REMOVE ALL ASSOCIATED FEEDERS, BRANCH CIRCUITING AND CONDUITS. B. REPLACE ALL EXISTING ELECTRICAL PANELS WITH NEW PANELS THAT ARE INDICATED TO BE REPLACED. REMOVE ASSOCIATED FEEDER CONDUIT AND WIRING. CONNECT THE NEW ELECTRICAL PANEL TO THE NEW FEEDER WIRING AND CONDUIT AS INDICATED ON THE ONE LINE DIAGRAM ON SHEET EP501. RECONNECT THE EXISTING BRANCH CIRCUITS SERVING EXISTING EQUIPMENT TO REMAIN TO THE NEW BREAKERS IN THE NEW ELECTRICAL PANELS. C. ON ALL EXISTING ELECTRICAL PANELS INDICATED TO REMAIN, DISCONNECT AND REMOVE THE EXISTING FEEDER WIRING AND CONDUIT AND RECONNECT TO NEW FEEDER CIRCUITING AS INDICATED ON THE ONE LINE DIAGRAM ON SHEET EP501. 20' SIDEWALK 5 SHEET KEYNOTES 4 P 3 GENERAL NOTES 2 L IC E NS E D 1 L A H O MA 18 7 14 11 21 +/- 50' NTS IT ROOM PANEL "IT1" UH-006 M CRAWL SPACE-7 167-7 UH-007 3 M 1 NEW MSB 9 IT-2 014-2 18 IT ROOM PANEL "IT2" C CLOSET 007A 4 NEW ATS 23 RESTROOM 008 STORAGE-2 010A-2 FCU-004 M EF-2 RESTROOM 009 EMW1 - 23 6 DOAU-1 0PW1 - 6,8,10 M STORAGE 010 2 STORAGE-5 013-5 J 10 0PW1 - 4 MAINT. OFFICE-2 014C-2 UH-005 M 0PW1 - 5 FCU-002 0PE1 - 6,8,10 13 M UH-002 STORAGE-2 011-2 25 MECHANICAL ROOM-2 006A-2 UP 10 J UH-014 M 20 CORR. 01AD MECHANICAL ROOM-2 006-2 B C 0PW1 EMW1 12 IT ROOM-8 014A-8 WEST - OLD KITCHEN PANEL UH-003 EXIT 001 FCU-007 J MAINTENANCE UH-010 SHOP-5 M 0PE2 - 1 012-5 FCU-006 B 12 DOAU-2 CORR.-9 014B-9 CENTER HALLWAY PANEL. (SERVES SHOP CROSS THE HALLWAY) 0PW1 - 1 13 0PE1 0PE2 - 3 4 0PE2 - 4,6,8 0PE2 INVENTORY OFFICE-3 014D-3 0PE1 - 2 0PE1 - 1 M FCU-003 BASEMENT EAST CORRIDOR PANEL CORR.-3 H015-3 2 M 4 SOUTH - CENTER ENTRY WAY PANEL STORAGE-19 001B-19 UH-011 UH-013 UH-012 B FCU-021 24 0PW1 - 2 2 11 ELECTRICAL 004C STAIR 002 4/15/2016 2:56:09 PM 4'-0" 15 HALL 011B STAIR-2 011A-2 STAIR S02 M FCU-008 J 17 2 22 RESTROOM 011C M 2 UH-008 DOAU-3 REVISION HISTORY: C OFFICE TORNADO SHELTER-2 016-2 UH-009 0PW1 - 3 CL TORNADO SHELTER-16 017-16 2 0PW1 - 12 16 4' SIDEWALK LAUNDRY-3 020-3 C:\Users\mxk\Documents\My Revit\41700_Elec_mxk.rvt 19 12 0PE3 LAUNDRY ROOM PANEL M ELECTRICAL CLOSET-4 004A-4 J CORR. H024 RESTROOM 023 3 HYDRONIC PUMP 10 RM 12 004B LOUVERED GATE 4'-0" 0PE1 - 4 FCU-009 C LOUVERED FENCE SHOWERS-4 022-4 13 10 STAIR S04 UH-004 2 NEW GENERATOR Room 197 0PE1 - 3,5,7 2 0PE2 - 2 FCU-001 STAIR 01B FIRE PUMP ROOM-3 005-3 14 11 A B M Edmond, Oklahoma ELECTRICAL ROOM-3 007-3 A University of Central Oklahoma Murdaugh Hall Renovation A EXISTING BOILER ENCLOSURE. FIELD VERIFY EXACT LOCATION BEFORE BIDDING. 1 1 4/18/16 DESCRIPTION DATE PROJECT INFORMATION: DESIGNED BY: FCU-020 CRAWL SPACE-19 178-19 5 6 7 8 9 10 11 12 13 FS/MBK 14 DRAWN BY: MBK FCU-017 REVIEWED BY: JTL KITCHENETTE-3 019-3 A BIKE SHOP-6 018-6 SHEET TITLE: D 2 3 4 15 1 16 17 18 03/30/16 SHEET NUMBER: N SCALE: 1/8" = 1'-0" 3 BASEMENT ELECTRICAL MASTER PLAN ISSUE DATE: BASEMENT ELECTRICAL MASTER PLAN 0 2 TJC 20141700 D 1 PROJECT MANAGER: PROJECT NUMBER: FCU-005 1 ADDENDUM 002 4 5 4' 8' 16' EP100 6 5 7 9 8 10 11 12 13 14 15 16 17 18 1 11 11 A A DORM 165 FCU-H102B FCU-166 DORM 166 J DORM 122 J 1PW1 - 30,32 J FCU-164 J EF-1 1PE1 - 29,31 1PW1 51,53,55 J 6 10 J MEN'S RR 161 6 9 1PW1 - 22,24 FCU-158 EMW1 - 14 1PW1 - 42 DORM 158 J HALL DIRECTOR APARTMENT 144 1PW1 - 66 1PW1 - 65 13 1PW1 - 45 12 GFI FCU-118 FCU-161 1PW1 - 43 1PW1 - 60 1PW1 - 21,23 1PW1 1PW1 - 57 J FRONT DESK 128 HALL DIRECTOR S APARTMENT 140 13 2 FCU-144 RA OFFICE 126 FCU-128 1PE1 - 22,24 1PE1 - 67 FCU-126 FCU-124 1PE1 - 66 1PE1 - 62 1PW1 - 61 J J 2 6 1 1PW1 - 18,20 FCU-156 6 EMW1 - 9 1 EP401 J J 5 J 2 1PW1 - 62 STORAGE-15 STAIR-1 001B-15 011A-1 2 2 HOUSEKEEPING CLOSET 100F 13 1PE1 - 40 CORR.-2 H015-2 1PE1 - 64 2 1PW1 - 13,15 C BONUS DORM ROOM 143 BONUS DORM ROOM 141A J 12 2 5 J J J 13 2 BONUS DORM ROOM 123 1PE1 - 53 1PW1 - 47 STAIR S12 DORM 109 1 FCU-109 BONUS DORM ROOM SHOWERS-2 123A 022-2 J 1PE1 - 14,16 C 1PW1 - 39 1PW1 - 41 J FCU-152 J FCU-108 1PW1 - 14,16 FCU-151 3 DORM 151 4 DORM 150 B FCU-150 J FCU-149 FCU-148 J J DORM 146 J B FCU-147 5 DORM 147 6 7 8 9 10 11 12 13 DORM 103 J J 1PE1 - 5,7 FCU-103 DORM 104 14 7 1PW1 - 1,3 1PE1 - 65 PC 1PE1 - 6,8 1PW1 - 6,8 7 7 1PE1 - 2,4 1PE1 - 1,3 7 1PW1 - 2,4 L A H O MA REVISION HISTORY: FCU-101 FCU-146 DORM 102 FCU-145 1PW1 - 40 8 J FCU-H102A DORM 145 J FCU-102 J FCU-H101A 1PE1 - 42 DORM 8 101 J D D 1 C FCU-105 DORM 106 DORM 149 1. EXISTING ELECTRICAL PANEL TO BE REPLACED. 2. EXISTING RECEPTACLE TO REMAIN. DISCONNECT FROM EXISTING CIRCUIT AND REMOVE THE ASSOCIATED WIRING. RECONNECT TO NEW CIRCUIT AS INDICATED. 3. REMOVE EXISTING RECEPTACLE AND PROVIDE BLANK COVER FOR EXISTING BOX. 4. EXISTING FAN AND LIGHT FIXTURE TO REMAIN, SEE LIGHTING SHEET EL101, KEYNOTE 4 FOR CIRCUITING. 5. JUNCTION BOX IN CLOSET FOR DORM ROOM RECEPTACLES/POWER. INSTALL JUNCTION BOX ABOVE CEILING. 6. 120V POWER CONNECTION FOR FIRE DAMPERS. SEE MECHANICAL SHEETS FOR EXACT LOCATIONS. 7. ROUTE (4) - #10 & (1) - #10 EG IN 3/4 C. 8. ROUTE (2) - #10 & (1) - #10 EG IN 3/4 C. 9. RECONNECT EXISTING EQUIPMENT AND RECEPTACLES IN THIS AREA TO NEW ELECTRICAL PANEL 1PW1. 10.RECONNECT EXISTING EQUIPMENT AND RECEPTACLES IN THIS AREA TO NEW ELECTRICAL PANEL 1PE1. 11.FURNISH AND INSTALL J HOOKS FOR FUTURE DATA CABLES. THE J HOOKS SHALL BE INSTALLED IN THE TOP OF THE LIGHT COVE ON EACH SIDE OF THE CORRIDOR AND SHALL RUN THE ENTIRE LENGTH OF THE CORRIDOR. SPACE J HOOKS 4' 0' APART. 12.TWO (2) DUPLEX RECEPTACLES MOUNTED UNDER ELECTRICAL PANEL FOR COMPUTER INTERNET MODULE HOOKUP, RECEPTACLES SHALL BE IN A FLUSH LOCKABLE BOX, COORDINATE WITH OWNER FOR SPACING OF OUTLETS IN BOX, REFER TO DETAIL 2, SHEET EP101. 13.TV OUTLET COMBO WITH RECEPTACLE FOR DIGITAL SIGN. SEE NOTE 3 ON SHEET ET101 FOR MOUNTING INSTRUCTIONS. 14.ROOMS 154 & 156 ARE TO BE COMPLETED FIRST AS MOCK-UP ROOMS. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH GENERAL CONTRACTOR AND ARCHITECT. 15.CONNECTION FOR FIRE ALARM CONTROL PANEL "FACP". DORM 105 FCU-106 FCU-104 DORM 148 DORM 107 1PE1 - 10,12 1PW1 - 5,7 J 1PE1 - 43 1PE1 - 13,15 GAME ROOM 130A 1PW1 - 59 J FCU-107 1PE1 - 9,11 TYPICAL 1PW1 - 64 PC DORM 108 1PE1 - 57 4 2 3 EP401 1PW1 - 9,11 1PW1 - 10,12 2 4 J J 1PE1 - 41 1PE1 - 55 FCU-130A DORM 152 4/15/2016 2:56:22 PM FCU-111 1PE1 - 17,19 RR 123B FCU-123A DORM 111 J 1PE1 1PE1 - 59 1PE1 - 18,20 CORR. 6 H174 6 J FCU-123 FCU-143 1PE1 - 44 DORM 113 1PE1 - 52,54,56 FCU-141 FCU-113 J J EMW1 - 11 2 LOUNGE 130 J 1PW1 - 46 RR 141B DORM 154 14 FCU-154 J 13 J 1PE1 - 58,60 1PW1 52,54,56 1PW1 - 17,19 TYPICAL J B 13 1 MECHANICAL CLOSET 100C FCU-115 1PE1 - 21,23 1PE1 - 39 15 J 1PE1 - 45 BONUS DORM ROOM 124 FCU-140 DORM 14 156 DORM 115 48" AFF GFI OK SHEET KEYNOTES J 10 9 GARY W. JAMES 16166 FCU-117 1PE1 - 25,27 J C DORM 117 1PE1 - 26,28 MEN'S RR 118 1PW1 - 25,27 FCU-160 DORM 119 J PC 1PE1 - 65 MECH. 101A 48" AFF B FCU-119 DORM 120 J DORM 160 5 TYPICAL J FCU-120 MECH. 168 CORR. H169 FCU-162 1PE1 - 46 1PW1 - 44 PC 1PW1 - 64 DORM 162 FCU-121 1PE1 - 33,35 FCU-163 1PW1 - 26,28 J J 1PE1 - 30,32 DORM 163 1PW1 - 29,31 DORM 164 FCU-122 FCU-165 1PW1 - 33,35 DORM 121 FCU-H101B D F E S S I O NA G INEER WP GFI RO EN D 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com L 1PW1 - 67 Frankfurt Short Bruza Architects Engineers Planners Edmond, Oklahoma 4 A. REFER TO SHEET EP401, DETAIL 1 FOR DORM ROOM POWER CIRCUITING. B. NOT ALL MATERIALS THAT EXIST IN THE WORK AREA HAVE BEEN SHOWN. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS IN THE AREA OF CONSTRUCTION PRIOR TO BID. C. UNLESS NOTED OTHERWISE, CONTRACTOR SHALL REMOVE ALL MATERIALS DESIGNATED FOR DEMOLITION FROM THE SITE. D. CONTRACTOR SHALL DE-ENERGIZE THE MAIN POWER TO EQUIPMENT AND DEVICES SCHEDULED FOR DEMOLITION PRIOR TO THE START OF WORK. E. COORDINATE DEMOLITION TO ENSURE POWER AND LIGHTING DEVICES TO AREAS ADJACENT TO, BUT NOT INVOLVED IN THE RENOVATION ARE NOT ADVERSELY AFFECTED. F. COORDINATE ANY INTERRUPTION OF SERVICE WITH THE FACILITY MANAGER AND THE CONTRACTING OFFICER NOT LESS THAN SEVEN (7) - DAYS PRIOR TO THE PROPOSED INTERRUPTION. G. UNLESS NOTED OTHERWISE, DISCONNECT AND REMOVE ALL LIGHT FIXTURES, SWITCHES, PANEL BOARDS, RECEPTACLES, RACEWAYS AND CONDUCTORS ROUTED WITHIN ROOM / WALLS SCHEDULED FOR DEMOLITION. REMOVE CONDUIT AND CONDUCTORS BACK TO THEIR SOURCE OF ORIGINATION. H. REPLACE ALL EXISTING ELECTRICAL PANELS WITH NEW PANELS THAT ARE INDICATED TO BE REPLACED. REMOVE ASSOCIATED FEEDER CONDUIT AND WIRING. CONNECT THE NEW ELECTRICAL PANEL TO THE NEW FEEDER WIRING AND CONDUIT AS INDICATED ON THE ONE LINE DIAGRAM ON SHEET EP501. RECONNECT THE EXISTING BRANCH CIRCUITS SERVING EXISTING EQUIPMENT TO REMAIN TO THE NEW BREAKERS IN THE NEW ELECTRICAL PANELS. University of Central Oklahoma Murdaugh Hall Renovation 3 2 5 GENERAL NOTES 4 P 1 3 2 L IC E NS E D 1 3 2 4 15 1 16 17 CONDUIT TO CEILING ABOVE RECEPTACLES FLUSH IN WALL 18 FIRST FLOOR ELECTRICAL PLAN 1 SCALE: 1/8" = 1'-0" ADDENDUM 002 4/18/16 DESCRIPTION DATE PROJECT INFORMATION: DESIGNED BY: FS/MBK DRAWN BY: MBK REVIEWED BY: C:\Users\mxk\Documents\My Revit\41700_Elec_mxk.rvt JTL FLUSH LOCKABLE BOX (12"x12" MINIMUM) A A PROJECT MANAGER: TJC PROJECT NUMBER: 20141700 SHEET TITLE: FIRST FLOOR ELECTRICAL PLAN DOOR 2 LOCKABLE ELECTRICAL BOX ISSUE DATE: 03/30/16 SCALE: NTS SHEET NUMBER: N 0 1 2 3 4 5 4' 8' 16' EP101 5 GENERAL NOTES 4 6 5 7 9 8 10 11 12 13 14 15 16 17 6 18 6 A A FCU-H202B DORM 266 FCU-H201B DORM 265 FCU-265 FCU-266 J DORM 222 J FCU-221 FCU-222 TYPICAL DORM 264 DORM 220 J DORM 263 FCU-263 J 2PW2 - 13 J FCU-262 DORM 262 2PE1 - 45,47 J J 2PW1 - 22,24 FCU-218 FCU-261 DORM 244 2PW1 - 21,23 2PW1 - 62 2PW1 - 61 DORM 242 DORM 240 2PW2 J DORM 238 1 TYPICAL 2PW2 - 14 7 FCU-258 DORM 236 DORM 234 EMW1 - 16 PC 2PW2 - 16 FCU-236 FCU-240 DORM 230 DORM 232 9 DORM 228 4 DORM 226 2PE2 - 8 FCU-234 2PE2 - 10 FCU-232 2PW1 J FCU-256 FCU-242 8 J J EMW1 - 10 2 6 DORM 256 2PW1 - 34,36 2 J J J J J J 2PW1 - 50,52 3 2PW1 - 54,56 2PW1 - 46,48 2PW1 - 49,51 3 2PW1 - 53,55 2PW1 - 45,47 J J FCU-230 J 2PW1 - 42,44 2PW1 - 38,40 2PW1 - 41,43 J J J J FCU-226 FCU-243 B J FCU-241 J J J J FCU-237 FCU-239 DORM 241 DORM 243 2PW1 - 14,16 2PW2 - 8 J J J J J J FCU-235 FCU-233 2PE1 - 57 FCU-211 J J DORM 239 4 DORM 237 DORM 235 DORM 233 2 STAIR S21 DORM 227 DORM 225 2PE1 - 37,39 2PE1 - 33,35 DORM 223 C FCU-208 2PE2 - 12 DORM 251 4/15/2016 2:56:28 PM J FCU-249 DORM 206 DORM 249 REVISION HISTORY: FCU-205 FCU-206 J 2PW1 - 60 PC 2PW1 - 5,7 FCU-204 DORM 247 5 FCU-247 FCU-248 6 7 8 9 10 11 12 13 2PW1 - 2,4 3 2PW2 - 9 FCU-245 14 FCU-246 J FCU-H202A DORM 246 DORM 202 DORM 245 J DORM 204 J J FCU-203 DORM 203 2PE1 - 25,27 3 2PW1 - 1,3 4 2PE1 - 60 PC 2PE1 - 30,32 J 2PW1 - 6,8 DORM 248 DORM 205 2PE1 - 29,31 J J DORM 207 2PE1 - 38,40 2PE1 - 34,36 2PW1 - 10,12 B FCU-207 2PE2 - 14 DORM 208 5 EP401 J J 2PW1 - 9,11 FCU-250 FCU-209 J DORM 252 DORM 250 DORM 209 CORR. H201 2PE2 - 11 2PE2 - 9 DORM 229 DORM 231 2PE1 - 42,44 FCU-223 FCU-251 FCU-252 J 2PE1 - 22,24 FCU-227 FCU-229 FCU-231 DORM 211 J 2PE1 2 J J J J Room 2PE1 - 1,3 3 2PE1 - 17,19 3 2PE1 - 6,8 2PE1 - 10,12 2PE1 - 13,15 3 190 2PE1 - 5,7 2PE1 - 14,16 2PW1 - 59 EMW1 - 12 2PE1 - 2,4 2PE1 - 9,11 2PE1 - 18,20 3 2PW2 - 17 2PW2 - 15 2PW1 - 13,15 2PW2 - 10 J FCU-224 FCU-225 2PW1 - 17,19 FCU-254 C 2PE2 - 15 7 2PE2 2PW1 - 37,39 DORM 254 DORM 213 FCU-213 2PE1 - 58 FCU-228 J FCU-238 J 2PW1 - 18,20 STAIR S22 2PE1 - 41,43 8 2PE1 - 61 2PE1 - 59 1. JUNCTION BOX IN CLOSET FOR DORM ROOM RECEPTACLES/POWER. INSTALL JUNCTION BOX ABOVE CEILING. 2. 120V POWER CONNECTION FOR FIRE DAMPERS. SEE MECHANICAL SHEETS FOR EXACT LOCATIONS. 3. ROUTE (4) - #10 & (1) - #10 EG IN 3/4 C. 4. ROUTE (2) - #10 & (1) - #10 EG IN 3/4 C. 5. EXISTING ELECTRICAL PANEL TO BE REPLACED. 6. FURNISH AND INSTALL J HOOKS FOR FUTURE DATA CABLES. THE J HOOKS SHALL BE INSTALLED IN THE TOP OF THE LIGHT COVE ON EACH SIDE OF THE CORRIDOR AND SHALL RUN THE ENTIRE LENGTH OF THE CORRIDOR. SPACE J HOOKS 4' 0' APART. ALL CORRIDORS, TYPICAL. 7. TWO (2) DUPLEXES RECEPTACLES MOUNTED UNDER ELECTRIC PANEL FOR COMPUTER INTERNET MODULE HOOKUP, RECEPTACLES SHALL BE IN A FLUSH LOCKABLE BOX. REFER TO DETAIL 2, SHEET EP101. 8. TV OUTLET COMBO WITH RECEPTACLE FOR DIGITAL SIGN. SEE NOTE 3 ON SHEET ET101 FOR MOUNTING DETAILS. 9. CONNECTION FOR FIRE ALARM POWER EXTENDER PANEL. 5 FCU-244 2PW1 - 57 C DORM 224 5 J B 2PE2 - 16 8 DORM 258 2PE1 - 46,48 GFI 2PW1 - 58 2PW2 - 12 2PW2 - 11 GFI DORM 215 FCU-215 48" AFF 48" AFF FCU-260 1 FCU-217 J 2PW1 - 25,27 DORM 260 B TYPICAL 2 MEN'S RR 218 MEN'S RR 261 DORM 217 1 J 2 J PC 2PE1 - 60 MECH. 201A MECH. PC 2PW1 - 60 202A C DORM 219 2PE1 - 50,52 2PE2 - 17 L A H O MA FCU-219 2PE1 - 49,51 FCU-220 2PW1 - 29,31 J OK SHEET KEYNOTES 2PE1 - 54,56 2PW1 - 26,28 FCU-264 1 TYPICAL 2PE1 - 53,55 2PW1 - 33,35 J J J 2PW1 - 30,32 1 DORM 221 GARY W. JAMES 16166 Edmond, Oklahoma 4 F E S S I O NA University of Central Oklahoma Murdaugh Hall Renovation 3 2 D RO G INEER 1 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com EN D Frankfurt Short Bruza Architects Engineers Planners L A. REFER TO SHEET EP401, DETAIL 1 FOR DORM ROOM POWER CIRCUITING. B. NOT ALL MATERIALS THAT EXIST IN THE WORK AREA HAVE BEEN SHOWN. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS IN THE AREA OF CONSTRUCTION PRIOR TO BID. C. UNLESS NOTED OTHERWISE, CONTRACTOR SHALL REMOVE ALL MATERIALS DESIGNATED FOR DEMOLITION FROM THE SITE. D. CONTRACTOR SHALL DE-ENERGIZE THE MAIN POWER TO EQUIPMENT AND DEVICES SCHEDULED FOR DEMOLITION PRIOR TO THE START OF WORK. E. COORDINATE DEMOLITION TO ENSURE POWER AND LIGHTING DEVICES TO AREAS ADJACENT TO, BUT NOT INVOLVED IN THE RENOVATION ARE NOT ADVERSELY AFFECTED. F. COORDINATE ANY INTERRUPTION OF SERVICE WITH THE FACILITY MANAGER AND THE CONTRACTING OFFICER NOT LESS THAN SEVEN (7) - DAYS PRIOR TO THE PROPOSED INTERRUPTION. G. UNLESS NOTED OTHERWISE, DISCONNECT AND REMOVE ALL LIGHT FIXTURES, SWITCHES, PANEL BOARDS, RECEPTACLES, RACEWAYS AND CONDUCTORS ROUTED WITHIN ROOM / WALLS SCHEDULED FOR DEMOLITION. REMOVE CONDUIT AND CONDUCTORS BACK TO THEIR SOURCE OF ORIGINATION. H. REPLACE ALL EXISTING ELECTRICAL PANELS WITH NEW PANELS THAT ARE INDICATED TO BE REPLACED. REMOVE ASSOCIATED FEEDER CONDUIT AND WIRING. CONNECT THE NEW ELECTRICAL PANEL TO THE NEW FEEDER WIRING AND CONDUIT AS INDICATED ON THE ONE LINE DIAGRAM ON SHEET EP501. RECONNECT THE EXISTING BRANCH CIRCUITS SERVING EXISTING EQUIPMENT TO REMAIN TO THE NEW BREAKERS IN THE NEW ELECTRICAL PANELS. P 3 2 L IC E NS E D 1 2PE1 - 21,23 3 2PE1 - 26,28 3 FCU-201 1 FCU-202 J J FCU-H201A 2PE2 - 13 J 4 4/18/16 DESCRIPTION DATE PROJECT INFORMATION: DORM 201 D ADDENDUM 002 DESIGNED BY: FS/MBK D DRAWN BY: MBK REVIEWED BY: C:\Users\mxk\Documents\My Revit\41700_Elec_mxk.rvt JTL A 1 3 2 4 15 16 17 18 A PROJECT MANAGER: TJC PROJECT NUMBER: 1 20141700 SECOND FLOOR ELECTRICAL PLAN SHEET TITLE: SECOND FLOOR ELECTRICAL PLAN SCALE: 1/8" = 1'-0" ISSUE DATE: 03/30/16 SHEET NUMBER: N 0 1 2 3 4 5 4' 8' 16' EP102 5 GENERAL NOTES 4 9 8 10 11 12 14 15 16 17 6 18 6 A A DORM 366 FCU-H302A J J J FCU-366 3PW1 - 33,35 J FCU-322 DORM 365 FCU-365 FCU-H301A DORM 321 FCU-321 DORM 322 3PE1 - 54,56 3PE1 - 53,55 3PW1 - 30,32 1 TYPICAL DORM 364 J FCU-364 FCU-363 3PW1 - 29,31 FCU-362 DORM 363 J J 2 MEN'S RR 361 2 MEN'S RR 318 B 3PW1 - 22,24 3PW2 - 12 FCU-361 FCU-318 3PW1 - 62 3PW1 - 58 8 3PW2 7 FCU-342 FCU-340 FCU-338 J J J EMW1 - 13 FCU-334 FCU-332 FCU-330 3PW1 - 17,19 J J J J J J J J J J J J 3PE1 - 1,3 3 3PE1 - 2,4 3 J J J J FCU-324 STAIR S34 FCU-343 FCU-341 3PW2 - 15 DORM 343 3PW1 - 14,16 J J 3PE1 - 13,15 J J J J J J J J FCU-337 FCU-339 FCU-335 FCU-333 FCU-331 FCU-329 DORM 341 3PW2 - 17 DORM 4 337 DORM 339 DORM 335 DORM 333 FCU-325 FCU-327 2 J 3PE1 - 42,44 J 2 STAIR S31 3PE2 - 9 DORM 331 DORM 327 DORM 329 DORM 325 DORM 323 DORM 348 J J 3PE2 - 14 3PE1 - 29,31 3PE1 - 34,36 DORM 306 B DORM 307 3PE1 - 33,35 FCU-308 DORM 305 REVISION HISTORY: J FCU-306 3PE1 - 60 PC J J FCU-347 DORM 304 DORM 347 5 6 7 8 9 10 11 12 13 14 FCU-305 J J DORM 303 3PE1 - 25,27 FCU-304 FCU-303 3PE1 - 26,28 3 DORM 345 3 FCU-301 3PE1 - 21,23 FCU-345 3 FCU-302 FCU-346 J C FCU-307 3PE1 - 30,32 3 3PW1 - 1,3 3PW1 - 2,4 3PW2 - 9 4 J DORM 308 FCU-349 3PW1 - 6,8 DORM 346 FCU-309 3PE1 - 38,40 3PW1 - 5,7 FCU-348 3PE1 - 37,39 3PE2 - 12 DORM 349 3PW1 - 60 PC J DORM 309 J 3PW2 - 8 3PW1 - 9,11 CORR. H301 3PE2 - 11 3PW1 - 10,12 FCU-350 DORM 311 FCU-311 FCU-351 DORM 352 J 3PE1 3PE1 - 57 FCU-323 DORM 351 J 3PE2 - 15 J 3PE1 - 22,24 3PW1 - 13,15 DORM 350 7 3PE2 3PE1 - 6,8 EMW1 - 15 3PE1 - 5,7 3PE1 - 10,12 CORR. 3PE1 - 14,16 3 3PE1 - 9,11 H300 3PE1 - 17,19 ATTIC HATCH 3PE1 - 18,20 3 J 3PW1 - 59 3PW2 - 10 FCU-326 2 CORR. H302 FCU-352 FCU-313 3PE2 - 8 3PW1 - 38,40 3PW1 - 50,52 8 3PW1 - 53,55 3PW1 - 54,56 3 3PW1 - 41,43 3PW1 - 45,47 3PW1 - 42,44 3PW1 - 49,51 3 3 3PW1 - 46,48 3PW1 - 34,36 3PW1 - 37,39 6 J C 8 3PE2 - 10 FCU-328 DORM 313 3PE1 - 41,43 C 5 3PW1 3PW1 - 18,20 J 3PE1 - 61 3PE1 - 59 B 3PE2 - 16 3PE1 - 58 DORM 324 4 EMW1 - 16 PC FCU-336 DORM 326 3PE1 - 46,48 1. JUNCTION BOX IN CLOSET FOR DORM ROOM RECEPTACLES/POWER. INSTALL JUNCTION BOX ABOVE CEILING. 2. 120V POWER CONNECTION FOR FIRE DAMPERS. SEE MECHANICAL SHEETS FOR EXACT LOCATIONS. 3. ROUTE (4) - #10 & (1) - #10 EG IN 3/4 C. 4. ROUTE (2) - #10 & (1) - #10 EG IN 3/4 C. 5. EXISTING ELECTRICAL PANEL TO BE REPLACED. 6. FURNISH AND INSTALL J HOOKS FOR FUTURE DATA CABLES. THE J HOOKS SHALL BE INSTALLED IN THE TOP OF THE LIGHT COVE ON EACH SIDE OF THE CORRIDOR AND SHALL RUN THE ENTIRE LENGTH OF THE CORRIDOR. SPACE J HOOKS 4' 0' APART. ALL CORRIDORS, TYPICAL. 7. TWO (2) DUPLEXES RECEPTACLES MOUNTED UNDER ELECTRIC PANEL FOR COMPUTER INTERNET MODULE HOOKUP, RECEPTACLES SHALL BE IN A FLUSH LOCKABLE BOX. REFER TO DETAIL 2, SHEET EP101. 8. TV OUTLET COMBO WITH RECEPTACLE FOR DIGITAL SIGN. SEE NOTE 3 ON SHEET ET101 FOR MOUNTING DETAILS. 9. CONNECTION FOR FIRE ALARM POWER EXTENDER PANEL. J J 4/15/2016 2:56:32 PM 3PW2 - 16 DORM 328 DORM 330 GFI 5 J DORM 354 TYPICAL 1 DORM 332 DORM 334 DORM 336 9 FCU-344 FCU-356 FCU-354 DORM 342 DORM 338 2 J DORM 356 DORM 340 3PW2 - 14 3PW1 - 57 B DORM 344 3PW1 - 61 3PW2 - 11 DORM 315 48" AFF GFI 3PW1 - 21,23 DORM 358 FCU-315 J 48" AFF 1 FCU-317 3PE1 - 45,47 J FCU-358 DORM 317 J 3PW1 - 25,27 DORM 360 DORM 319 PC 3PE1 - 60 1 TYPICAL MECH. 301A C FCU-360 FCU-319 3PE2 - 17 MECH. 302A J L A H O MA SHEET KEYNOTES TYPICAL J 3PE1 - 50,52 FCU-320 3PW2 - 13 PC 3PW1 - 60 DORM 362 J 3PE1 - 49,51 3PW1 - 26,28 OK 1 DORM 320 J GARY W. JAMES 16166 Edmond, Oklahoma 7 5 F E S S I O NA University of Central Oklahoma Murdaugh Hall Renovation 4 D RO G INEER 3 2 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com EN 1 Frankfurt Short Bruza Architects Engineers Planners L D A. REFER TO SHEET EP401, DETAIL 1 FOR DORM ROOM POWER CIRCUITING. B. NOT ALL MATERIALS THAT EXIST IN THE WORK AREA HAVE BEEN SHOWN. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS IN THE AREA OF CONSTRUCTION PRIOR TO BID. C. UNLESS NOTED OTHERWISE, CONTRACTOR SHALL REMOVE ALL MATERIALS DESIGNATED FOR DEMOLITION FROM THE SITE. D. CONTRACTOR SHALL DE-ENERGIZE THE MAIN POWER TO EQUIPMENT AND DEVICES SCHEDULED FOR DEMOLITION PRIOR TO THE START OF WORK. E. COORDINATE DEMOLITION TO ENSURE POWER AND LIGHTING DEVICES TO AREAS ADJACENT TO, BUT NOT INVOLVED IN THE RENOVATION ARE NOT ADVERSELY AFFECTED. F. COORDINATE ANY INTERRUPTION OF SERVICE WITH THE FACILITY MANAGER AND THE CONTRACTING OFFICER NOT LESS THAN SEVEN (7) - DAYS PRIOR TO THE PROPOSED INTERRUPTION. G. UNLESS NOTED OTHERWISE, DISCONNECT AND REMOVE ALL LIGHT FIXTURES, SWITCHES, PANEL BOARDS, RECEPTACLES, RACEWAYS AND CONDUCTORS ROUTED WITHIN ROOM / WALLS SCHEDULED FOR DEMOLITION. REMOVE CONDUIT AND CONDUCTORS BACK TO THEIR SOURCE OF ORIGINATION. H. REPLACE ALL EXISTING ELECTRICAL PANELS WITH NEW PANELS THAT ARE INDICATED TO BE REPLACED. REMOVE ASSOCIATED FEEDER CONDUIT AND WIRING. CONNECT THE NEW ELECTRICAL PANEL TO THE NEW FEEDER WIRING AND CONDUIT AS INDICATED ON THE ONE LINE DIAGRAM ON SHEET EP501. RECONNECT THE EXISTING BRANCH CIRCUITS SERVING EXISTING EQUIPMENT TO REMAIN TO THE NEW BREAKERS IN THE NEW ELECTRICAL PANELS. P 3 2 L IC E NS E D 1 DORM 302 J FCU-H302B J FCU-H301B DORM 301 3PE2 - 13 1 ADDENDUM 002 4/18/16 DESCRIPTION DATE 4 J PROJECT INFORMATION: D D DESIGNED BY: FS/MBK DRAWN BY: MBK C:\Users\mxk\Documents\My Revit\41700_Elec_mxk.rvt 1 2 3 4 15 1 A 16 17 REVIEWED BY: 18 JTL THIRD FLOOR ELECTRICAL PLAN A SCALE: 1/8" = 1'-0" PROJECT MANAGER: TJC PROJECT NUMBER: 20141700 SHEET TITLE: THIRD FLOOR ELECTRICAL PLAN ISSUE DATE: 03/30/16 SHEET NUMBER: N 0 1 2 3 4 5 4' 8' 16' EP103 1 3 2 5 4 Frankfurt Short Bruza Architects Engineers Planners Branch Panel: EMW1 Location: Supply From: Mounting: Enclosure: Volts: 120/208 Wye Phases: 3 Wires: 4 ELECTRICAL ROOM-3 007-3 MSB TRANSFER SWITCH TSI SURFACE NEMA 1 A.I.C. Rating: Mains Type: Mains Rating: MCB Rating: Location: Supply From: Mounting: Enclosure: 42000 MLO 400 A 300 A A.I.C. Rating: Mains Type: Mains Rating: MCB Rating: 22000 MCB 225 A 225 A Notes: A 1200... 439 VA B C 439 VA 410 VA 410 VA 785 VA 600 VA 600 VA 600 VA 1000... 600 VA 2000... 1260... 11200... 600 VA 12400... 2000... 1400... 1600... 1600... 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 20294 VA 180 A 20849 VA 185 A Poles 1 1 410 VA 410 VA 1 1 1 600 VA 600 VA 1 1 1 200 VA 6400... 3 --1000... 1800... 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 11420 VA 95 A Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 200 A --20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A Circuit Description LIGHTING CORR. EAST WING LIGHTING CORR. 2ND FLOOR EAST WING LIGHTING CORR. 3RD FLOOR EAST WING STAIRS LIGHTING 2ND FLOOR FIRE DAMPERS 2ND FLOOR FIRE DAMPERS FACP * FA POWER EXTENDER PANELS * PANEL IT1 --EXTERIOR LIGHTING EXTERIOR LIGHTING EXTERIOR LIGHTING SPARE SPARE SPARE SPARE SPARE SPARE SPARE CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 1 Poles 1 3 --1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Trip 20 A 20 A --20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A Circuit Description FCU-001, FCU-006, FCU-009 DOAU-2 --SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE P D CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 GARY W. JAMES 16166 OK L A H O MA Legend: Connected Load 13338 VA 1680 VA 1000 VA 36600 VA Demand Factor 125.00% 100.00% 100.00% 63.66% Estimated Demand 16673 VA 1680 VA 1000 VA 23300 VA Panel Totals Total Conn. Load: Total Est. Demand: Total Conn.: Total Est. Demand: Load Classification Power Connected Load 7415 VA Demand Factor 100.00% Estimated Demand 7415 VA Panel Totals Total Conn. Load: Total Est. Demand: Total Conn.: Total Est. Demand: 52618 VA 42653 VA 146 A 118 A Notes: *. PROVIDE RED LABELED NON-PAD LOCKABLE LOCK-ON DEVICE FOR FACP CCT BREAKER. 7415 VA 7415 VA 21 A 21 A Notes: C C Branch Panel: 0PE1 Location: Supply From: Mounting: Enclosure: Volts: 120/208 Wye Phases: 3 Wires: 4 CORR.-9 014B-9 MSB SURFACE NEMA 1 A.I.C. Rating: Mains Type: Mains Rating: MCB Rating: 10000 MCB 225 A 225 A Notes: CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 B Circuit Description UH-013, UH-014, UH-015, UH-016 DOAU-3 --LIGHTING ROOM H015C, 012D BASEMENT LIGHTING BASEMENT LIGHTING LIGHTING LAUNDRY 020C SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE Trip Poles A 20 A 1 336 VA 700 VA 20 A 3 ----721 VA 901 VA 20 A 1 20 A 1 20 A 1 1000 VA 1000 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA SPARE 20 A 1 SPARE 20 A 1 4/15/2016 2:56:44 PM Total Load: Total... 4657 VA 39 A B C 721 VA 1000 VA 600 VA 901 VA 400 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 3621 VA 30 A Poles 1 1 721 VA 901 VA 3 --1000 VA 1000 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 3621 VA 30 A Trip 20 A 20 A 20 A --20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A Circuit Description FCU-002, FCU-003, FCU-010 HVAC CONTROL PANEL - DOAU-3 EF-2 --BASEMENT LIGHTING POWER BIKE SHOP 018F SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE 20 A SPARE 20 A SPARE CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 B REVISION HISTORY: Legend: Load Classification Power LIGHTING Edmond, Oklahoma Load Classification LIGHTING Other Power Receptacle Trip Poles A B C 20 A 1 252 VA 480 VA 20 A 1 1000... 1561... 20 A 1 1000... 1561... 20 A 1 0 VA 1561... 20 A 1 0 VA 0 VA 20 A 1 0 VA 0 VA 20 A 1 0 VA 0 VA 20 A 1 0 VA 0 VA 20 A 1 0 VA 0 VA 20 A 1 0 VA 0 VA 20 A 1 0 VA 0 VA 20 A 1 0 VA 0 VA 20 A 1 0 VA 0 VA 20 A 1 0 VA 0 VA 20 A 1 0 VA 0 VA 20 A 1 0 VA 0 VA 20 A 1 0 VA 0 VA 20 A 1 0 VA 0 VA 20 A 1 0 VA 0 VA 20 A 1 0 VA 0 VA 20 A 1 0 VA 0 VA 2293 VA 2561 VA 2561 VA Total Load: 19 A 22 A 22 A Total Amps: University of Central Oklahoma Murdaugh Hall Renovation Legend: Circuit Description UH-007, UH-009, UH-010 HVAC CONTROL PANEL - DOAU-2 BASEMENT LIGHTING SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE G INEER Trip Poles 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 Total Load: Total Amps: F E S S I O NA EN Circuit Description BASEMENT EMERGENCY LIGHTING LIGHTING CORR. WEST WING LIGHTING CORR. 2ND FLOOR WEST WING LIGHTING CORR. 3RD FLOOR WEST WING FIRST FLOOR FIRE DAMPERS FIRST FLOOR FIRE DAMPERS 3RD FLOOR FIRE DAMPERS 3RD FLOOR FIRE DAMPERS LIGHTING CORR.-BASEMENT CORRIDOR LIGHTING LIGHTING LOUNGE 130 FA POWER EXTENDER PANEL * EXTERIOR LIGHTING EXTERIOR LIGHTING SPARE SPARE SPARE SPARE SPARE SPARE SPARE RO L CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Volts: 120/208 Wye Phases: 3 Wires: 4 MAINTENANCE SHOP-5 012-5 MSB SURFACE NEMA 1 L IC E NS E D Notes: D 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com Branch Panel: 0PE2 Connected Load 10900 VA 1000 VA Demand Factor 100.00% 125.00% Estimated Demand 10900 VA 1250 VA Panel Totals Total Conn. Load: Total Est. Demand: Total Conn.: Total Est. Demand: 11900 VA 12150 VA 33 A 34 A Notes: 1 ADDENDUM 002 4/18/16 DESCRIPTION DATE PROJECT INFORMATION: DESIGNED BY: FS/MBK DRAWN BY: MBK REVIEWED BY: C:\Users\mxk\Documents\My Revit\41700_Elec_mxk.rvt JTL A A PROJECT MANAGER: TJC PROJECT NUMBER: 20141700 SHEET TITLE: PANEL SCHEDULES ISSUE DATE: 03/30/16 SHEET NUMBER: EP702 1 2 3 4 5 1 3 2 5 4 Frankfurt Short Bruza Architects Engineers Planners Branch Panel: 0PE3 Volts: 120/208 Wye Phases: 3 Wires: 4 A.I.C. Rating: Mains Type: Mains Rating: MCB Rating: 5801 Broadway Ext., Suite 500 Oklahoma City, Oklahoma 73118 Telephone 405 840 2931 Facsimile 405 842 7750 www.fsb-ae.com 22000 MCB 225 A 225 A Notes: A WASHER WASHER WASHER WASHER WASHER WASHER SPARE SPARE SPARE SPARE SPACE WITH PROVISIONS SPACE WITH PROVISIONS 1150 VA 1150 VA 1150 VA 1150 VA 0 VA 0 VA 0 VA 0 VA 4600 VA 38 A Poles 1 1 1150 VA 1150 VA 1 1 1 1150 VA 1150 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 4600 VA 38 A Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A Circuit Description DRYER DRYER DRYER DRYER DRYER WASHER WASHER SPARE SPARE SPARE SPARE SPARE CKT 2 4 6 8 10 12 14 16 18 20 22 24 D RO F E S S I O NA GARY W. JAMES 16166 OK G INEER Trip Poles 20 A 1 1150 VA 1150 VA 20 A 1 20 A 1 20 A 1 1150 VA 1150 VA 20 A 1 20 A 1 20 A 1 0 VA 1150 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA ----5750 VA Total Load: 48 A Total... EN D Circuit Description C L CKT 1 3 5 7 9 11 13 15 17 19 21 23 B P TORNADO SHELTER-16 017-16 MSB SURFACE NEMA 1 L IC E NS E D Location: Supply From: Mounting: Enclosure: L A H O MA Legend: Load Classification Power Connected Load 14950 VA Demand Factor 100.00% Estimated Demand 14950 VA Panel Totals Total Conn. Load: Total Est. Demand: Total Conn.: Total Est. Demand: 14950 VA 14950 VA 41 A 41 A C Branch Panel: 1PW1 Location: Supply From: Mounting: Enclosure: Branch Panel: 1PE1 Volts: 120/208 Wye Phases: 3 Wires: 4 STORAGE-16 001B-16 WEST CORRIDOR - FLR 1 MSB RECESSED SURFACE NEMA 1 A.I.C. Rating: Mains Type: Mains Rating: MCB Rating: Location: Supply From: Mounting: Enclosure: 22000 MCB 225 A 225 A Notes: 4/15/2016 2:56:42 PM B 1 A.I.C. Rating: Mains Type: Mains Rating: MCB Rating: 22000 MCB 225 A 225 A Notes: A CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 Volts: 120/208 Wye Phases: 3 Wires: 4 SpaceCORRIDOR 104 EAST - FLR 1 MSB RECESSED SURFACE NEMA 1 Circuit Description POWER DORM 146 POWER DORM 146 POWER DORM 148 POWER DORM 148 POWER DORM 150 POWER DORM 150 POWER DORM 152 POWER DORM 152 POWER DORM 154 POWER DORM 154 POWER DORM 158 POWER DORM 158 POWER DORM 162 POWER DORM 162 POWER DORM 163 POWER DORM 163 POWER DORM 165 POWER DORM 165 LIGHTING DORM 154, 156, 158, 160 Trip Poles 20 A 1 1500 VA 20 A 1 20 A 1 20 A 1 720 VA 20 A 1 20 A 1 20 A 1 1500 VA 20 A 1 20 A 1 20 A 1 720 VA 20 A 1 20 A 1 20 A 1 1500 VA 20 A 1 20 A 1 20 A 1 720 VA 20 A 1 20 A 1 20 A 1 1172 VA FCU-147, FCU-149, FCU-151 20 A 1 41 FCU-148, FCU-150, FCU-152 20 A 1 43 FCU-160, FCU-162, FCU-164 20 A 1 45 FCU-140, FCU-144 20 A 1 47 FCU-130A - GAME ROOM 20 A 1 49 LIGHTING CORR. 1ST FLOOR WEST WING 20 A 1 51 EF-1 20 A 3 53 -- -- -- 55 -- -- -- 57 RECEPTS. LOUNGE 130 20 A 1 59 RECEPTS. GAME ROOM 130A 20 A 1 61 RECEPTS. CORR. H169 20 A 1 63 LIGHTING LOUNGE 130 20 A 1 65 RECEPTS. MEN'S RR 161 20 A 1 67 EXTERIOR RECEPTACLE 20 A 1 69 SPARE 20 A 1 71 SPARE 20 A 1 73 SPARE 20 A 1 75 SPARE 20 A 1 77 SPARE 20 A 1 79 SPARE 20 A 1 81 SPARE 20 A 1 83 SPARE 20 A 1 Total Load: Total... B C 1500 VA 720 VA 720 VA 1500 VA 1500 VA 1500 VA 720 VA 720 VA 720 VA 1500 VA 1500 VA 1500 VA 720 VA 720 VA 720 VA 1500 VA 1500 VA 1172 VA 720 VA 624 VA 576 VA 816 VA 384 VA 934 VA 640 VA 1500 VA 1500 VA 540 VA 720 VA 586 VA 180 VA 180 VA 360 VA 900 VA 360 VA 180 VA 192 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 1172 VA 1758 VA 793 VA 0 VA 1500 VA 720 VA 793 VA 180 VA 720 VA 1500 VA 960 VA 720 VA 1500 VA 720 VA 564 VA 793 VA 720 VA 1500 VA 576 VA 640 VA 1500 VA 720 VA 576 VA 576 VA A 0 VA 0 VA 0 VA 21515 VA 179 A 0 VA 0 VA 0 VA 19842 VA 165 A 19999 VA 167 A Poles 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A Circuit Description POWER DORM 145 POWER DORM 145 POWER DORM 147 POWER DORM 147 POWER DORM 149 POWER DORM 149 POWER DORM 151 POWER DORM 151 POWER DORM 156 POWER DORM 156 POWER DORM 160 POWER DORM 160 POWER DORM 164 POWER DORM 164 POWER DORM 166 POWER DORM 166 LIGHTING DORM 146, 148, 150, 152 LIGHTING DORM 145, 147, 149, 151 LIGHTING DORM 162, 163, 164, 165, 166 20 A FCU-145, FCU-146, FCU-H102A CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 Circuit Description POWER DORM 101 POWER DORM 101 POWER DORM 103 POWER DORM 103 POWER DORM 105 POWER DORM 105 POWER DORM 107 POWER DORM 107 POWER DORM 109 POWER DORM 109 POWER DORM 113 POWER DORM 113 POWER DORM 117 POWER DORM 117 POWER DORM 120 POWER DORM 120 POWER DORM 122 POWER DORM 122 LIGHTING DORM 109, 111, 113, 115 Trip Poles 20 A 1 1500 VA 20 A 1 20 A 1 20 A 1 720 VA 20 A 1 20 A 1 20 A 1 1500 VA 20 A 1 20 A 1 20 A 1 720 VA 20 A 1 20 A 1 20 A 1 1500 VA 20 A 1 20 A 1 20 A 1 720 VA 20 A 1 20 A 1 20 A 1 1172 VA FCU-124, FCU-126, FCU-128 20 A 1 20 A 1 1 20 A FCU-154-FCU-156, FCU-158 42 41 FCU-104, FCU-106, FCU-108 1 20 A FCU-163, FCU-165, FCU-166, FCU-H102B 44 43 FCU-103, FCU-105, FCU-107 20 A 1 1 20 A FCU-141, FCU-143 46 45 FCU-115, FCU-117, FCU-119 20 A 1 1 20 A LIGHTING MENS RESTROOM161 48 47 LIGHTING RESTROOM 118 20 A 1 1 20 A LIGHTING CORR. 1ST FLOOR WEST WING 50 49 LIGHTING CORR. 1ST FLOOR EAST WING 20 A 1 1 20 A POWER DORM 141A, 143 52 51 ROOM 012A 20 A 1 1 20 A POWER DORM 141A, 143 54 53 RECEPTS. LOUNGE 130 20 A 1 1 20 A POWER DORM 141A, 143 56 55 RECEPTS. GAME ROOM 130A 20 A 1 1 20 A LIGHTING DORM 141A, 143 58 57 RECEPTS. GAME ROOM 130A 20 A 1 1 20 A DIGITAL SIGN 60 59 RECEPTS. CORR. H101 20 A 1 1 20 A DIGITAL SIGN 62 61 LIGHTING LOUNGE 130 20 A 1 1 20 A RECEPTS. CORR. H169 64 63 POWER GAME ROOM 130A 20 A 1 1 20 A POWER 66 65 RECEPTS. 20 A 1 1 20 A SPARE 68 67 POWER 20 A 1 1 20 A SPARE 70 69 SPARE 20 A 1 1 20 A SPARE 72 71 SPARE 20 A 1 1 20 A SPARE 74 73 SPARE 20 A 1 1 20 A SPARE 76 75 SPARE 20 A 1 1 20 A SPARE 78 77 SPARE 20 A 1 1 20 A SPARE 80 79 SPARE 20 A 1 1 20 A SPARE 82 81 SPARE 20 A 1 1 20 A SPARE 84 83 SPARE 20 A 1 Total Load: Total... Legend: B C 1500 VA 720 VA 720 VA 1500 VA 1500 VA 720 VA 720 VA 1500 VA 1500 VA 720 VA 720 VA 1500 VA 1500 VA 720 VA 1172 VA 720 VA 1500 VA 1500 VA 1500 VA 720 VA 720 VA 720 VA 1500 VA 1500 VA 1500 VA 720 VA 720 VA 720 VA 1500 VA 1172 VA 1758 VA 360 VA 384 VA 576 VA 576 VA 576 VA 576 VA 816 VA 934 VA 640 VA 1500 VA 720 VA 1500 VA 360 VA 360 VA 360 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 180 VA 0 VA 0 VA 0 VA 540 VA 180 VA 400 VA 192 VA 1500 VA 540 VA 360 VA 900 VA 640 VA 900 VA 586 VA 180 VA 624 VA 0 VA 0 VA 0 VA 20934 VA 175 A 0 VA 19834 VA 165 A 0 VA 0 VA 20206 VA 169 A Poles 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A Circuit Description POWER DORM 102 POWER DORM 102 POWER DORM 104 POWER DORM 104 POWER DORM 106 POWER DORM 106 POWER DORM 108 POWER DORM 108 POWER DORM 111 POWER DORM 111 POWER DORM 115 POWER DORM 115 POWER DORM 119 POWER DORM 119 POWER DORM 121 POWER DORM 121 LIGHTING DORM 102, 104, 106, 108 LIGHTING DORM 101, 103, 105, 107 LIGHTING DORM 119, 120, 121, 122 20 A FCU-123, FCU-123A CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 20 A FCU-101, FCU-102, FCU-H101A 42 1 20 A FCU-109, FCU-111, FCU-113 44 1 20 A FCU-120, FCU-121, FCU-122, FCU-H101B 46 1 20 A LIGHTING CORR. 1ST FLOOR EAST WING 48 1 20 A POWER GAME ROOM 130A 50 1 20 A POWER DORM 123, 123A 52 1 20 A POWER DORM 123, 123A 54 1 20 A POWER DORM 123, 123A 56 1 20 A POWER DORM 124 58 1 20 A POWER DORM 124 60 1 20 A DIGITAL SIGN 62 1 20 A DIGITAL SIGN 64 1 20 A RECEPTS. MEN'S RR 118 66 1 20 A SPARE 68 1 20 A SPARE 70 1 20 A SPARE 72 1 20 A SPARE 74 1 20 A SPARE 76 1 20 A SPARE 78 1 20 A SPARE 80 1 20 A SPARE 82 1 20 A SPARE 84 B Edmond, Oklahoma C University of Central Oklahoma Murdaugh Hall Renovation Notes: REVISION HISTORY: 1 ADDENDUM 002 4/18/16 DESCRIPTION DATE Legend: PROJECT INFORMATION: C:\Users\mxk\Documents\My Revit\41700_Elec_mxk.rvt Load Classification Power Receptacle RECEPTS. LIGHTING A Connected Load 42582 VA 12780 VA 2880 VA 3137 VA Demand Factor 100.00% 89.12% 100.00% 125.00% Estimated Demand 42582 VA 11390 VA 2880 VA 3921 VA Panel Totals Total Conn. Load: Total Est. Demand: Total Conn.: Total Est. Demand: Load Classification Power Receptacle RECEPTS. LIGHTING 61379 VA 60773 VA 170 A 169 A Notes: Connected Load 37040 VA 17820 VA 2700 VA 3437 VA Demand Factor 100.00% 78.06% 100.00% 125.00% Estimated Demand 37040 VA 13910 VA 2700 VA 4296 VA DESIGNED BY: Panel Totals Total Conn. Load: Total Est. Demand: Total Conn.: Total Est. Demand: FS/MBK 60997 VA 57946 VA 169 A 161 A DRAWN BY: MBK REVIEWED BY: JTL A Notes: PROJECT MANAGER: TJC PROJECT NUMBER: 20141700 SHEET TITLE: PANEL SCHEDULES ISSUE DATE: 03/30/16 SHEET NUMBER: EP703 1 2 3 4 5