Bulletin 140U Molded Case Circuit Breakers Multitap End Cap Optional Optional Optional 140U-J-MTL3A 140U-J-MTL6A 140U-J-ECM Aluminum Aluminum Molded Housing 1/4…20 screw 1/4…20 screw — 50 lb-in 50 lb-in — 5.6 N•m 5.6 N•m — Cu/Al Cu/Al — 60/75°C 60/75°C — (3) (6) — (A) 3/8…1/2 in. (B) 3/4…7/8 in. (C) 1-1/4…1-3/8 in. (A) 3/8…1/2 in. (B) 3/4…7/8 in. (C) 1-1/4…1-3/8 in. — (A) 9…13 mm (B) 19…22 mm (C) 32…35 mm (A) 9…13 mm (B) 19…22 mm (C) 32…35 mm — #14…#2 #14…#6 — 2.5…25 2.5…10 — Allen - 5/32 in. (4 mm) Allen - 3/32 in. Allen - 4 mm 275' Lb-in 70 lb-in 25 lb-in 7.9 N•m 2.8 N•m 31 N•m Optional Optional Optional 140U-K-MTL3A 140U-K-MTL6A 140U-K-ECM Aluminum Aluminum Molded Housing .375 x 25 screw .375 x 25 screw — 72 -96 lb-in 72 -96 lb-in — 8.6…10.8 N•m 8.6…10.8 N•m — Cu/Al Cu/Al — 60/75°C 60/75°C — (3) (6) — (A) 9/16.…3/4 in. (B) 1-3/16.…1-1/2 in. (C) 1-7/8…2-1/4 in. (A) 9/16.…3/4 in. (B) 1-3/16.…1-1/2 in. (C) 1-7/8…2-1/4 in. (A) 14…19 mm (B) 30…38 mm (C) 48…57 mm (A) 14…19 mm (B) 30…38 mm (C) 48…57 mm #12…2/0 #14…2/0 — — — 4…70 2.5…70 — Allen - 3/16 in. (X mm) Allen - 1/8 in. (3 mm) Allen - 8 mm 120 lb-in 25 lb-in 275 Lb-in 13.5 N•m 2.8 N•m 31 -m Visit our website: www.ab.com/catalogs 11 Bulletin 140U Molded Case Circuit Breakers Terminal and Lug Specifications Terminals Frame Size Lugs Specification Specification Material Dim. — — — — — — Cat. No. — — — — — — 15/16(23.81) Material — — — — — — — — — — — — Lb-in — — — — — — N•m 1(25.4) C 1/2(12.7) Fastener Torque Slotted Terminal Fastener Hardware Lb-in 42 Terminal Fastener Torque — — — — — — N•m 3 Cable Type — — — — — — Cable Temperature Rating — — — — — — L Cable Quantity A Wire Strip Length C Wire Range — — — — — — in. — — — — — — mm — — — — — — AWG — — — — — — mm2 — — — — — — — — — — — — Lb-in — — — — — — N•m — — — — — — — Optional Optional Optional — — 140U-MTLC2 140U-MTLA4 — — Terminal Type B Wire Torque Material Std/Optional Dim. A 1-1/16(26.99) Cat. No. — 140U-MTLA2 B 15/16(23.81) Material — Aluminum Copper Aluminum — — d 1/2(12.7) Fastener Torque Socket Lb-in 275/400 N•m 31.1/45.2 M A Terminal Fastener Hardware Terminal Fastener Torque C — — — Lb-in — — 275 275 275 — — N•m — 31.1 31.1 31.1 — — Cable Type — Cu/Al Cu only Cu/Al — — Cable Temperature Rating — 60/75°C 60/75°C 60/75°C — — Cable Quantity — (2) (2) (4) — — — 1-1/16 1-1/16 1 1/16 — — — Wire Strip Length Wire Range in. mm — 26.99 26.99 26.99 — AWG — 310…350 250…350 400…500 — — mm2 — 95…150 120…300 185…240 — — — Socket Socket Socket — — Lb-in — 275 275 275 — — N•m — 31.1 31.1 31.1 — — Terminal Type B Wire Torque 12 Mechanical Lugs Std/Optional A B Box Lugs Visit our website: www.ab.com/catalogs Bulletin 140U Molded Case Circuit Breakers Multitap End Cap Optional Optional Optional 140U-L-MTL3 140U-L-MTL6 140U-L-ECM Aluminum Aluminum Molded Housing 0.375 x 25 screw 0.375 x 25 screw — 72 -96 lb-in 72 -96 lb-in — 8.6…10.8 N•m 8.6…10.8 N•m — Cu/Al Cu/Al — 60/75°C 60/75°C — (3) (A) 9/16.…3/4 (B) 1-3/16.…1in. 1/2 in. (A) 14…19 mm (B) 30…38 mm (6) (C) 1-7/8…21/4 in. (C) 48…57 mm (A) 9/16.…3/4 (B) 1-3/16.…1in. 1/2 in. (A) 14…19 mm — (C) 1-7/8…21/4 in. — (C) 48…57 mm — (B) 30…38 mm #12…2/0 #14…2/0 — 4…70 2.5…70 — Allen - 3/16 in. (X mm) Allen - 1/8 in. (3 mm) Allen - 8 mm 120 lb-in 25 lb-in 275'Lb-in 13.5 N•m 2.8 N•m 31 N•m — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — Visit our website: www.ab.com/catalogs 13 Bulletin 140U Molded Case Circuit Breakers Terminal and Lug Specifications Terminals Frame Size Lugs Specification Specification Box Lugs CU/Plate Std/Optional — Optional Optional — A 1/2”(12.7) Cat. No. — 140U-N-TLA4 140U-N-TLA3 — B 3/8”(9.53) Material — Aluminum Copper — C Terminal Fastener 1/8”(3.175) Hardware Material Dim. Slip on box Terminal lug Fastener Torque — Fastener Torque Lb-in N•m — N A — Lb-in — N•m 35…45 35…45 — — 4…5 4…5 — — CU/Al Cu/Al — Cable Temperature Rating — 60/75°C 60/75°C — Cable Quantity — (4) (3) — — 4-3/8 4-3/8 — 111.125 111.125 Wire Range in. mm — AWG — mm2 — 11.7…240 85…185 — Allen Allen — Lb-in — 375 375 — N•m — 42.2 42.4 — Terminal Type B Wire Torque 14 — Cable Type Wire Strip Length C Mechanical Lugs 4/0…500MCM 3/0…400 MCM Visit our website: www.ab.com/catalogs — — — Bulletin 140U Molded Case Circuit Breakers Dimensions, Cont. H Frame .47 [ 11,9 ] .88 [ 22,2 ] .54 [ 13,6 ] 3.00 [ 76,2 ] 1.00 [ 25,4 ] 2.47 [ 62,7 ] .97 [ 24,6 ] 5.50 [ 139,7 ] 3.81 [ 96,9 ] 3.44 [ 87,4 ] 1.00 [ 25,4 ] 1.00 [ 25,4 ] 2.93 [ 74,3 ] .88 [ 22,4 ] 18 BUL 140U E125 FRAME Visit our website: www.ab.com/catalogs Bulletin 140U Molded Case Circuit Breakers 4.00 3.00 2.00 1.00 1.00 1.00 .97 5.50 .97 3.81 3.81 5.50 BUL 140U H FRAME 3 AND 4 POLE Visit our website: www.ab.com/catalogs 19 Bulletin 140U Molded Case Circuit Breakers Time-Current Curves, Cont. Bul.140U/UE Time-Current Curves for Bulletin 140U-J Thermal-Magnetic Molded Case Circuit Breakers Allen-Bradley 63…250 A 40752-620 (1) SC-XXX Effective March 2004 28 Visit our website: www.ab.com/catalogs Bulletin 140U Molded Case Circuit Breakers Time-Current Curves, Cont. Bul.140U/UE Time-Current Curves for Bulletin 140U-J Electronic LS Molded Case Circuit Breakers 2 Long Delay Response & Short Delay with I T Response Curve 2 HOURS Current in Multiples of (Ir) 10000 9000 8000 7000 .5 .7 1 3 4 7 5 10 20 30 6000 5000 1 HOUR 2 1.15 4000 Circuit Breaker Time/Current Curve 3000 2 Long Delay (LD) & Short Delay (SD) with I T Response (LS) 2000 In Ir Available Sensors (In): A B C D E F G H 50A 100A 160A 250A 1000 900 800 700 Maximum Total Clearing Time 600 500 50 A 100 A 160 20A 20A 25A 30A 32A 40A 45A 50A 40A 45A 50A 63A 70A 80A 90A 100A 63A 80A 90A 100A 110A 125A 150A 160A 250 A 100A 125A 150A 160A 175A 200A 225A 250A 400 Notes: 300 1. Curve accuracy applies from -20°C to +55°C ambient. Temperatures above +88° C cause an over temperature protection trip. For possible continuous ampere derating for ambient above 40°C, consult Rockwell Automation. 200 1 MINUTE 2. Application frequency is 50/60 Hertz. Available Long Delay Time: 2,4,7,10,12,15,20,24 sec. Shown @ 6x Ir 2,4,7,15,24 seconds +0/-30% 100 90 80 70 60 50 4. The right portion of the curve is determined by the interrupting rating of the circuit breaker. 40 5. The left portion of the curve is shown as a multiple of the Long Delay Setting (Long Delay Pick Up = 115% of Ir). Range is 110% - 120%. 30 . . 6. Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current. 24 20 TIME IN SECONDS 3. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into play if a current above the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset memory. Minimum Total Clearing Time 10 9 8 7 6 7. The Short Delay Pick Up has 9 settings/positions: 2 - 8 & 10, 14. 2 8. Short Delay I T band has a tolerance of ± 15%. 15 2 9. Breakpoint back to FLAT response occurs @ 8x Ir for upper line of the I T curve. . 10. For high fault current levels an additional fixed instantaneous hardware override is provided at 14x (In). 7 5 4 . 11. For LD Response & SD with Flat Response curve, see: 4 12. For LD Response & SD with I T Response (this curve): 40752-621 3 2 13. For Ground Fault Delay Response curve, see: . 3 40752-622 2 40752-623 2 2 4 1 .9 .8 .7 .6 1 .9 .8 .7 5 .6 .5 .5 7 .4 .4 14 8 Available Short Delay Pick Up Settings 2 - 8,10, 14 x Ir 5% (See Note 7) .2 6 2 I T Short Delay (See Note 8) .1 .09 .08 .07 .2 Instantaneous Override (See Note 10) 10 Application Determines End of Curve . .06 67ms .05 .05 .04 .04 .03 .03 See Note 9 14x .02 .01 .1 .09 .08 .07 .06 TIME IN SECONDS .3 .3 .02 .5 .7 1 2 3 4 5 7 10 20 30 40 50 70 100 2 3 4 Current in Multiples of (Ir) 5 7 10 20 30 40 50 70 .01 100 Current in Multiples of ( I n ) 2 I T Trip Style 40752-621 (1) TC-01201002E Effective September 2003 Visit our website: www.ab.com/catalogs 29 Bulletin 140U Molded Case Circuit Breakers Time-Current Curves, Cont. Bul.140U 40,000 50,000 20,000 30,000 5000 4000 6000 7000 8000 9000 10,000 2000 3000 500 600 700 800 900 1000 300 400 200 60 70 80 90 100 50 CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In) 60,000 70,000 80,000 9 0 , 0 00 100,000 Time-Current Curves for Bulletin 140U-K3/K6 Thermal-Magnetic Molded Case Circuit Breakers 10,000 10,000 2 HOURS 2 HOURS 1 HOUR Circuit Breaker Time/Current Curves For application and coordination purposes only. Based on 40 °C ambient, cold start. Connected with four (4) feet of rated wire (60°C up to 125 A. 75° C above 125 A) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. 2,000 1 HOUR 5,000 5,000 3,000 3,000 2,000 Maximum Voltage 600V., AC (60 Hz) 250 V., DC 1,000 1,000 500 Breaker Rating Rated Amperes (In) Instantaneous Trip Amperes 100, 125, 150, 500 to 1000% of trip unit rating 175, 200, 225, (See Figure Below) 250, 300, 350, (Dc values are approximately 40% higher) 400 Interrupting Rating (UL/CSA) RMS Sym Amperes Amperes Breaker Type @ 240 V., AC @ 480 V., AC @ 600 V., AC @ 250 V., DC (250-400A) 300 (125-225A) 200 Maximum Single Pole Trip Times at 25°C ➀ 140U-K3 140U-K6 65,000 100,000 35,000 65,000 25,000 35,000 10,000 22,000 100 Maximum 50 50 30 30 20 20 7.5 7.5 10 10 10 5 5 Amps (In) Magnetic Multiples Of In 7.5 Push to Trip C Thermal Magnetic Trip Unit Typical Trip Unit Nameplate 10 40°C 1 MINUTE 1 MINUTE 100 Minimum 300 200 ➀ Single pole data at 25°C based on NEMA Procedures (AB 4-1991) for verifying performance of molded case circuit breakers. (100A) 500 5 10 Cat. No. 5 5 Individual Pole Adjustments 3 3 1 1 .5 5X ±20% 10X 2 .5 ±10% .3 .3 .2 .2 .1 .1 .05 .05 .03 .03 .02 .02 Maximum Interrupting Time .01 .01 .005 .005 Interrupting Rating Determines End of Curve .003 .002 .002 .001 40,000 50,000 60,000 70,000 80,000 90,000 100,000 20,000 30,000 4000 5000 6000 7000 8000 9000 10,000 3000 2000 500 600 700 800 900 1000 400 300 200 60 70 80 90 1 00 50 .001 CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In) 40752-630 (1) SC-4118-87B Effective October 1997 32 .003 Visit our website: www.ab.com/catalogs TIME IN SECONDS TIME IN SECONDS Adjustable Magnetic Trip 2 Bulletin 140U Molded Case Circuit Breakers Time-Current Curves, Cont. Bul.140U 50,000 30,000 40,000 20,000 5000 60 00 7 000 8000 9000 10,000 3000 4000 2000 600 700 800 900 1000 500 30 0 400 200 60 50 70 80 90 100 CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In) 60,000 70,000 80,000 90,000 100,000 Time-Current Curves for Bulletin 140U-K0 Thermal-Magnetic Molded Case Circuit Breakers 10,000 10,000 2 HOURS 2 HOURS 1 HOUR 5,000 Circuit Breaker Time/Current Curves For application and coordination purposes only. Based on 40 °C ambient, cold start. Connected with four (4) feet of rated wire (60°C up to 125 A. 75° C above 125 amps) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. 3,000 2,000 1 HOUR 5,000 3,000 2,000 Maximum Voltage 600V., AC (60 Hz) 250 V., DC 1,000 Breaker Rating Rated Amperes (In) 500 100, 125, 150, 175, 200, 225, 250, 300, 350, 400 (250-400A) 300 500 Interrupting Rating (UL/CSA) RMS Sym Amperes Breaker Type @ 240 V., AC @ 480 V., AC (125-225A) Maximum Single Pole Trip Times at 25°C ➀ 200 1,000 Instantaneous Trip Amperes 500 to 1000% of trip unit rating (See Figure Below) (DC values are approximately 40% higher) 200,000 140U-K0 100,000 Amperes @ 600 V., AC @ 250 V., DC 50,000 22,000 ➀ Single pole test data at 25°C based on NEMA Procedures (AB 4-1991) for verifying performance of molded case circuit breakers. 300 200 (100A) 100 Minimum Maximum 50 50 30 30 20 20 7.5 7.5 10 10 10 5 5 Amps (In) Magnetic Multiples Of In 7.5 Push to Trip C Thermal Magnetic Trip Unit Typical Trip Unit Nameplate 10 40°C 1 MINUTE 1 MINUTE 100 5 10 Cat. No. 5 5 Individual Pole Adjustments 3 3 1 1 .5 5X ±20% 10X 2 TIME IN SECONDS TIME IN SECONDS Adjustable Magnetic Trip 2 .5 ±10% .3 .3 .2 .2 .1 .1 .05 .05 .03 .03 .02 .02 Maximum Interrupting Time 600 V., Ac .01 .01 480 V., Ac .005 .005 240 V., Ac .003 .003 Interrupting Rating Determines End of Curve .002 .002 .001 60,000 70,000 80,000 90,000 100,000 50,000 40,000 30,000 20,000 5000 6000 7000 8000 9000 10,000 4000 2000 3000 600 700 800 900 1000 500 400 200 300 60 70 80 90 100 50 .001 CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In) 40752-631 (1) SC-4119-87B Effective October 1997 Visit our website: www.ab.com/catalogs 33 Bulletin 140U Molded Case Circuit Breakers Time-Current Curves, Cont. Bul.140U Time-Current Curves for Bulletin 140U-K Electronic LSI, LSIG Trip Units and 140U-K0 Molded Case Circuit Breakers .5 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) .7 .9 1 5 6 7 8 9 10 20 2 HOURS 10,000 Circuit Breaker Time/Current Curves (Phase Current) 1 HOUR 5,000 ➃ Technical Data Covers, Cat. Nos. 140U-KTL3, -KTI3 Electronic Trip Units for use with Circuit Breaker Cat. No 140U-K0, 400A. max. 3,000 Adjustable Short Delay Time Typical Trip Unit Nameplate Rating Plug 2,000 Short Delay Cat. Standard Fixed Rating Plug Pickup • xIr Push to Trip In 4 Engaged 5 2 1,000 6 3 7 8 Time • ms 200 100 INST 300 TEST Trip Unit 40oC Remove Available Rating Plugs 500 300 200 Long Delay➀ Maximum Total Clearing Time 1 MINUTE Catalog Number Short Delay Pickup Range Amperes Fixed Fixed Fixed Fixed Fixed Fixed 140U-KRP3-D40 140U-KRP3-D35 140U-KRP3-D30 140U-KRP3-D25 140U-KRP3-D22 140U-KRP3-D20 800-3200 700-2800 600-2400 500-2000 450-1800 400-1600 50 30 Hz UL/CSA 240V 480V 200 600V 100 50 IEC 947-2 Breaker Type 240V 140U-K0 200 380V 415V 100 100 Notes electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA publication AB-4-1991. 2X 20 There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pick up value exists for a time and then is cleared by the tripping of a down stream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. 4X 10 Short Delay Pick Up Settings (Tolerance ±10%) 6X 5 3 ➀ Curve accuracy applies from –20°C to +55° C ambient. For possible continuous ampere derating for ambient above 40°C, consult Rockwell Automation. ➁ For high fault current levels a fixed instantaneous override is provided at 4000A. (Tolerance ±15%). 2 8X ➂ The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. ➃ For ground fault time/current curve see 40752-636. 7X TIME IN SECONDS Type 400 350 300 250 225 200 Interrupting Ratings – 50/60 RMS Sym. Amperes (kA) Breaker Type 140U-K0 Long Delay➀ Minimum Total Clearing Time 100 Ampere Rating (In) 1 1 5X 3X .5 300 ms .3 200 ms .2 100 ms .1 .1 I .05 .05 Fixed Instantaneous Override ➁ .04 .03 .02 .02 SECONDS .03 .01 Interrupting Rating Determines End of Curve ➂ Maximum Interrupting Time 600 VAC .01 480 VAC 240 VAC .005 .003 .002 200,000 100,000 30,000 40,000 50,000 .001 20 20,000 6 7 8 9 10 10,000 5 5000 2 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) 4000 .6 .7 .8 .9 1 3000 .5 2000 .001 CURRENT IN AMPS 40752-635 (1) SC-5645-93 Effective October 1997 Visit our website: www.ab.com/catalogs 37 Bulletin 140U Molded Case Circuit Breakers Time-Current Curves, Cont. Bul.140U Time-Current Curves for Bulletin 140U-M Electronic LS, LSG Trip Units and 140U-M5, -M6 Molded Case Circuit Breakers .5 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) .7 .9 1 ..86 2 6 7 8 9 10 3 4 5 20 1 HO U R 2 HO U R S 10,000 Circuit Breaker Time/Current Curves (Phase Current) ➃ 5,000 Technical Data Covers, Cat. Nos. 140U-MTL3, -MTG3 Electronic Trip Unit for use with Circuit Breaker Types 140U-M5, -M6, 800 A max. 3,000 Fixed Short Delay Time 2,000 Standard Fixed Rating Plug Rating Plug Typical Trip Unit Nameplate Push to Trip In 4 1,000 Test Short Delay Pickup x I n Cat. Engaged 2 5 6 3 7 Trip Unit 40o C Ambient 8 Remove 500 300 200 Long Delay➀ Maximum Total Clearing Time Available Rating Plugs Ampere Rating (I n ) Type 800 700 600 500 450 400 Fixed Fixed Fixed Fixed Fixed Fixed Rating Plug Catalog Number 140U-MRP3-D80 140U-MRP3-D70 140U-MRP3-D60 140U-MRP3-D50 140U-MRP3-D45 140U-MRP3-D40 Short Delay Pickup Range Amperes 1600-6400 1400-5600 1200-4800 1000-4000 900-3600 800-3200 Interrupting Rating 1 MIN U T E 100 Long Delay➀ Minimum Total Clearing Time UL/CSA RMS Sym. kA, 50/60 Hz Breaker Type 240V 65 100 140U-M5 140U-M6 50 Breaker Type 3X 2X 65 100 50 70 e) 50 50 Icu 690V (U e) Ics 20 25 10 13 Notes Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA AB4-1991 publications. Calibration response in short delay pick-up range is same for 1, 2 or 3 poles in series. 4X Short Delay Pick Up Settings (Tolerance ±10%) ➀ Curve accuracy applies from –20 °C to +55°C ambient. For possible continuous ampere derating for ambient above 40 °C, consult Rockwell Automation. 8X 5X There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pick-up value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. ➁ For high fault current levels a fixed instantaneous override is provided at 5500A. (Tolerance ±15%). 1 6X TIME IN SECONDS 25 35 Utilization Category A U imp = 8kV 3 2 65 100 140U-M5 140U-M6 10 5 600V 50 65 IEC 947-2 RMS Sym. kA, 50/60 Hz 380/415V (U 240V (U e) Ics Icu Ics Icu 30 20 480V ➂ The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. ➃ For ground fault time/current curves see 40752-678. .3 7X .5 .2 .1 .1 .05 .05 Fixed Instantaneous Override ➁ .04 .03 .02 .02 SECONDS .03 .01 Interrupting Rating Determines End of Curve ➂ .01 .005 .003 .002 CURRENT IN AMPS 40752-676 (1) SC-7204-99 Effective February 1999 44 Visit our website: www.ab.com/catalogs 100,000 50,000 30,000 40,000 20,000 10,000 5000 4000 3000 .001 2000 20 1000 .001 2 3 6 7 8 9 10 4 5 .5 .6 .7 .8 .9 1 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) Bulletin 140U Molded Case Circuit Breakers Time-Current Curves, Cont. Bul.140U Time-Current Curves for Bulletin 140U-M Electronic LSI, LSIG Trip Units and 140U-M5, -M6 Molded Case Circuit Breakers .5 .7 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) .9 .1.86 2 6 7 8 9 10 3 4 5 20 2 HO U R S 10,000 ➃ Circuit Breaker Time/Current Curves (Phase Current) 1 HO U R 5,000 Technical Data Covers, Cat. nos. 140U-MTH3, -MTI3 Electronic Trip Units for use with Circuit Breaker Types 140U-M5, -M6, 800 A max. 3,000 Adjustable Short Delay Time 2,000 Rating Plug Standard Fixed Rating Plug Push to Trip In Typical Trip Unit Nameplate Short Delay Pickup x In 5 4 6 3 7 Cat. Engaged 2 Test Time MIsec 200 100 I 8 300 Trip Unit 40oC Ambient Remove 1,000 Available Rating Plugs Ampere Rating (In) Type 800 700 600 500 450 400 Fixed Fixed Fixed Fixed Fixed Fixed Rating Plug Catalog Number 140U-MRP3-D80 140U-MRP3-D70 140U-MRP3-D60 140U-MRP3-D50 140U-MRP3-D45 140U-MRP3-D40 500 300 200 Long Delay➀ Maximum Total Clearing Time 1 MIN U T E Interrupting Rating UL/CSA RMS Sym. kA, 50/60 Hz Breaker Type Long Delay➀ Minimum Total Clearing Time 100 Short Delay Pickup Range Amperes 1600-6400 1400-5600 1200-4800 1000-4000 900-3600 800-3200 140U-M5 140U-M6 Breaker Type 50 240V 480V 600V 65 100 50 65 25 35 IEC 947-2 RMS Sym. kA, 50/60 Hz 240V (Ue) Icu Ics 30 65 100 140U-M5 140U-M6 380/415V (U e ) Icu Ics 65 100 50 70 50 50 690V (U e) Icu Ics 20 25 10 13 Utilization Category A U imp = 8kV 2X 20 Notes Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA AB4-1991 publications. 10 4X Calibration response in short delay pickup range is same for 1, 2 or 3 poles in series. 6X 5 3 There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. Short Delay Pickup Settings (Tolerance ? 10%) ➀ Curve accuracy applies from –20 °C to +55 °C ambient. For possible continuous ampere derating for ambient above 40 °C, consult Rockwell Automation. ➁ For high fault current levels a fixed instantaneous override is provided at 5500A. (Tolerance ±15%). ➂ The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. 7X TIME IN SECONDS 8X 2 1 ➃ For ground fault time/current curves see 40752-678. 5X 3X .5 300 ms .3 200 ms .2 100 ms .1 .1 I .05 .05 Fixed Instantaneous Override ➁ .04 .03 .02 .02 SECONDS .03 .01 Interrupting Rating Determines End of Curve ➂ .01 .005 .003 .002 100,000 50,000 30,000 40,000 20,000 10,000 5000 4000 20 3000 2 3 6 7 8 9 10 4 5 .6 .7 .8 .9 1 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) 2000 .001 .5 1000 .001 CURRENT IN AMPS 40752-677 (1) SC-6913-98 Effective February 1999 Visit our website: www.ab.com/catalogs 45 Bulletin 140U Molded Case Circuit Breakers Time-Current Curves, Cont. Bul.140U Time-Current Curves for Bulletin 140U-M Electronic Trip Units with Ground Fault Protection 16000 640 960 8 00 480 1 60 320 GROUND CURRENT-AMPERES 1120 12 80 1440 1600 Ground Fault Protection 2 HOURS 10,000 1 HOUR 5,000 Circuit Breaker Time/Current Curves (Ground Current) ➀ Technical Data Covers, Electronic Trip Units for use with Circuit Breaker Types 140U-M5, -M6, 800 A max. 3,000 Typical Trip Unit Nameplate Fixed Short Delay Time Rating Plug 2,000 Cat. Push to Trip In Engaged Short Delay Pickup x In 5 4 6 3 7 2 Ground Fault Pickup x Ig Time MIsec 4 500 3 2 1 8 300 150 I Ig = 160A 5 Test Trip Unit 40 o C Ambient Remove 1,000 Typical Trip Unit Nameplate Adjustable Short Delay Time Rating Plug Cat. 500 Short Delay Pickup x In Push to Trip In 4 Engaged 2 5 6 3 7 8 Time MIsec 200 100 I 300 Ground Fault Pickup x Ig Time MIsec 4 500 3 2 1 300 150 I Ig = 160A 5 Test Trip Unit 40 oC Ambient Remove Notes Curve accuracy applies from –20 °C to +55 °C ambient. For possible continuous ampere derating for ambient above 40 °C, consult Rockwell Automation. 300 200 Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA publication (AB4-1991). ➀ For phase time/current curves see: 40752-674 40752-675 40752-676 40752-677 1 MINUTE 100 50 30 1xIG 20 3xIG 4xIG 10 5 3 Ground Fault Pickup Settings (Tolerance ± 10% Except ± 20% on 1xIG Setting) 2xIG TIME IN SECONDS 5xIG 2 1 500 ms .5 300 ms .3 .2 150 ms .1 I .05 .03 .02 .01 .005 .003 .002 .001 40752-678 (1) SC-6914-98 Effective February 1999 46 1 2 3 4 5 6 7 8 910 GROUND CURRENT-IN MULTIPLES OF Ig = 160A 100 Visit our website: www.ab.com/catalogs Bulletin 140U Molded Case Circuit Breakers Time-Current Curves, Cont. Bul.140U Time-Current Curves for Bulletin 140U-N Electronic LS Trip Units CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 1 HO U R 2 HO U R S 10,000 Circuit Breaker Time/Current Curves (Phase Current) Electronic Trip Units are AC only devices that employ microprocessor based technology that provides true RMS current sensing means for proper correlation with thermal characteristics of conductors and equipment. They are used with Circuit Breaker Types 140U-N5, -N6, and -N0. 5,000 3,000 I2t Ramp Short Time Delay 2,000 Typical Trip Unit Nameplate Rating Plug Standard Fixed Rating Plug Push to Trip Short Delay Pickup x In 5 4 6 Cat.– /n– “Y” 3 Engaged 500 300 200 1 MIN U T E 100 A vailable Rating Plugs Ampere Rating (I n) Type Catalog Number Short Delay Pickup Range Amperes 1200 1200 1000 800 700 600 600, 800, 1000, 1200 Fixed Fixed Fixed Fixed Fixed Adj. 140U-NRP3-E12 140U-NRP3-E10 140U-NRP3-D80 140U-NRP3-D70 140U-NRP3-D60 140U-NRPA-E12 2400-9600 2000-8000 1600-6400 1400-5600 1200-4800 1200-9600 Interrupting Ratings – 50/60 Hz RMS Sym. Amperes (kA) UL/CSA Breaker Type 240V 480V 65 50 ND, CND 100 65 HND, CHND 200 100 NDC, CNDC 50 Trip Unit 40° C Ambient 8 Remov e Frame Rating Amperes (Max.) Long Delay➀ Maximum Total Clearing Time Long Delay➀ Minimum Total Clearing Time TEST 7 2 1,000 IEC 947-2 220-240V 65 100 200 600V 25 35 50 30 380-415V 50 65 100 ICS = .25 ICU ICW = 15 kA @ .5S U imp = 8kV 3X 2X 20 Notes Curve accuracy applies from -20 °C to +55° ambient above 40 °C, consult Rockwell Automation 10 Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA publication AB-4-1991. For ground fault time-current curves see 40752-692. Short Delay Pick Up Settings (Tolerance ± 10%) 4X 5 3 8X 5X ➁ For high fault current levels a fixed instantaneous override is provided at14000A (Tolerance ±15%). ➂ The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. ➃ Not UL/CSA Listed. 1 6X TIME IN SECONDS 2 ➀ There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overloads will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory .3 7X .5 .2 .05 .05 .03 .03 .02 .02 .001 CURRENT IN AMPS 50,000 20 60,000 70,000 80,000 90,000 100,000 .002 40,000 .003 .002 30,000 .005 .003 20,000 .005 .001 2 3 4 5 6 7 8 9 10 .5 .6 .7 .8 .9 1 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) Interrupting Rating Determines End of Curve➂ .01 10,000 .01 Fixed Instantaneous Overide➁ 200,000 .1 SECONDS .1 40752-690 (1) SC-5375-92A Effective October 1997 Visit our website: www.ab.com/catalogs 47 Bulletin 140U Molded Case Circuit Breakers Time-Current Curves, Cont. Bul.140U Time-Current Curves for Bulletin 140U-N LSI Electronic Trip Unit CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 1 HO U R 2 HO U R S 10,000 Circuit Breaker Time/Current Curves (Phase Current) Electronic Trip Units are AC only devices that employ microprocessor-based technology that provides true RMS current sensing means for proper correlation with thermal characteristics of conductors and equipment. For use with Circuit Breaker Types 140U-N5, -N6, and -N0. 5,000 3,000 Adjustable Short Time Delay Typical Trip Unit Nameplate Rating Plug 2,000 Push to Trip Standard Fixed Rating Plug Short Delay Pickup x In 5 4 6 Cat.– /n– “Y” 3 TEST 7 2 Engaged Trip Unit 40°C Ambient 8 Remov e 1,000 500 Frame Rating Amperes (Max.) A vailable Rating Plugs Ampere Type Rating (I n) Catalog Number Short Delay Pickup Range Amperes 1200 1200 1000 800 700 600 600, 800, 1000, 1200 140U-NRP3-E12 140U-NRP3-E10 140U-NRP3-D80 140U-NRP3-D70 140U-NRP3-D60 140U-NRPA-E12 2400-9600 2000-8000 1600-6400 1400-5600 1200-4800 1200-9600 300 200 1 MIN U T E 100 Long Delay➀ Maximum Total Clearing Time Interrupting Ratings – 50/60 Hz RMS Sym. Amperes (kA) UL/CSA Breaker Type 240V 480V 65 50 140U-N5 100 65 140U-N6 200 100 140U-N0 Long Delay➀ Minimum Total Clearing Time Fixed Fixed Fixed Fixed Fixed Adj. IEC 947-2 220-240V 65 100 200 600V 25 35 50 380-415V 50 65 100 ICS = .25 ICU ICW = 15 kA @ .5S U imp = 8kV 50 Notes 30 Curve accuracy applies from -20 °C to +55° C ambient. For possible ampere derating for ambient above 40 °C, consult Rockwell Automation 20 Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA publication AB-4-1991. 2X For ground fault time-current curves see 40752-692. ➀ There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overloads will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory 4X 10 Short Delay Pick Up Settings (Tolerance ±10%) 6X 5 3 ➁ For high fault current levels a fixed instantaneous override is provided at14000A (Tolerance ±15%). ➂ The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. ➃ Not UL/CSA Listed. 7X TIME IN SECONDS 8X 2 1 5X 3X .5 300 MS .3 200 MS .2 100MS .1 .1 I .03 .03 .02 .02 20 .001 CURRENT IN AMPS 40752-691 (1) SC-5376-92A Effective October 1997 48 Visit our website: www.ab.com/catalogs 60,000 70,000 80,000 90,000 100,000 .002 40,000 .003 .002 50,000 .003 20,000 .005 30,000 .01 .005 .001 2 3 4 5 6 7 8 9 10 .5 .6 .7 .8 .9 1 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) Interrupting Rating Determines End of Curve➂ 10,000 .01 Fixed Instantaneous Overide➁ 200,000 .05 SECONDS .05 Bulletin 140U Molded Case Circuit Breakers Time-Current Curves, Cont. Bul.140U Time-Current Curves for Bulletin 140U-N Electronic LSG, LSIG Trip Units with Ground Fault Protection 1 HO U R 4000 5000 3000 2000 400 600 700 800 900 1000 500 300 200 2 HO U R S .50 .60 .70 .80 .90 100 CURRENT IN AMPERES 10,000 C i rcui t B reak er Ti m e/C urrent C urv es (G round C urrent) Electronic Trip Units are AC only devices that employ microprocessor-based technology that provides true RMS current sensing means for proper correlation with thermal characteristics of conductors and equipment. They are used with Circuit Breaker Types 140U-N5, -N6, and N0. 5,000 3,000 Typical Trip Unit Nameplate 2,000 Rating Plug Push to Trip Cat.– /n– “ Y” 1,000 S hort D elay Pick up x In 5 4 6 G round Fault Pickup x IG 4 3 5 3 2 2 Engaged 7 8 Remov e 6 1 IG =200A Time 500 TEST 300 150 Trip U nit 40°C A mbient 1 Millisec 500 N otes Curve accuracy applies from –20 °C to + 55°C ambient. Electronic trip units are suitable for functional field testing with test kit. For field testing using primary injection methods, follow NEMA publication AB-4-1991. For phase time-current curves see 40752-690, and -691. 300 200 1 MIN U T E 100 50 30 200 A . 600 A . 10 1000 A . 20 5 G round Fault Pick U p S ettings (Tolerance±1 0% E xcept ±20% on 200 A . S etting) 800 A . 400 A . 2 1200 A . 3 TIME IN SECONDS 1 .5 S E C .5 .3 S E C .3 .2 .15 S E C .1 I .05 .03 .02 .01 .005 .003 .002 5000 4000 3000 2000 500 600 700 800 900 1000 400 200 300 .50 .60 .70 .80 .90 100 .001 CURRENT IN AMPERES 40752-692 (1) SC-5377-92A Effective October 1997 Visit our website: www.ab.com/catalogs 49