PAGE 2| APEX MONTHLY - DECEMBER 2013 www.apexengineeringproducts.com RYDLYME improves flow A Canadian plastics and chemicals company, turned to RYDLYME to clean piping that has never been cleaned in its 30 years of service. The 5,000-foot carbon steel blow-down line from the plant’s main cooling tower system suffered from severe mineral scale that progressively increased over the years causing significant flow issues. As shown by the chart below, the system has not been close to its designed flow rate of 125 gpm for several years: 1 2 5 90 gpm 80 gpm 70 gpm 60 gpm G P M 50 gpm 40 gpm 30 gpm 2007200820092010201120122013 AFTER CLEANING Solution • Given the length of the pipeline, a typical circulation was not practical. Two 5,000-gallon vacuum pump trucks were positioned at each end of the pipeline. • 1,980 gallons of RYDLYME were pumped back and forth for 8 hours allowing for optimal contact time, as well as constant movement throughout the pipeline. Results • Personnel at the plant watched the flow rate improve to its design rate of 125 gpm! • The team also saw improved functionality and quieter operation of the system pumps. • The cleaning created a lot of excitement within the plant as many other departments are looking into how they can use RYDLYME on other equipment (e.g. heat exchangers, chillers, air compressors, cooling towers, lime slurry systems and condensers)! Plate and frame for methanol recovery cleaned A California biodiesel manufacturer wanted to test RYDLYME on one of its fouled plate and frame heat exchangers within the methanol recovery division of the plant. A byproduct of the biodiesel manufacturing process, methanol is extracted from spent cooking oil and grease, vaporized and recovered in plate and frame heat exchangers. Scaling inside the units were inhibiting proper heat exchange, making the entire recovery process inefficient. Solution • 37 gallons of RYDLYME circulated for 3 hours via RYDLYME 10PPC pneumatic pump cart. • Unit DID NOT have to be disassembled. • Unit drained and flushed with fresh water. Results • A fter the unit was brought back online, the plate and frame heat exchanger was returned to normal operating parameters. • T he customer stated, “Your product seems to have worked wonderfully on cleaning our exchanger. We have two more plate and frame exchangers that need attention, not to mention our entire cooling system!” w w w . a p e x e n g i n e e r i n g p r o d u c t s . c o m APEX MONTHLY - DECEMBER 2013 | PAGE 3 Write this downcleaning Bi-Carb System at Pennsylvania paper plant A major paper plant in Pennsylvania used RYDLYME to dissolve mineral deposits within its Bi-Carbonate System (Bi-Carb), which controls alkalinity in the plant’s process water system. The Bi-Carb produces scale buildup inside the mix and day tanks, plugging up the system’s pipes, strainers and other components. Solution • 125 gallons of RYDLYME. • Circulated via pump inside mix tank for 3 hours; solution then transferred to day tank and circulated throughout the rest of the system (closed-loop) for 6-8 hours. Results • After cleaning and water flush, scaling throughout the entire system was eliminated, returning it to peak operating efficiency. • Client plans to continue using RYDLYME in this cleaning application and is evaluating other applications in and around the plant where RYDLYME can be used. “Unbelievable” Descaling condensers A 6-foot heat exchanger at a facility for a major gas supplier on the east coast was experiencing a 35°F increase in temperature at the water outlet, which resulted in high Delta Ts. A 1,200-ton ammonia condenser at a turkey processing facility experienced scaling on the exterior of the tubes. This scaling caused significant issues with proper heat transfer and in turn, not cooling the ammonia inside the tubes for proper refrigeration temperatures. Solution • 10 gallons of RYDLYME circulated for 4 hours via RYDLYME 10MDC pumping system. Solution • 660 gallons of RYDLYME circulated for 8 hours via inline pumps. Results Results • 3 0°F drop in temperature and the Delta T was returned to normal! • S caling throughout the tubes was dissovled restoring proper heat • C lient plans to use RYDLYME on two more heat exchangers and six • Client purchased additional RYDLYME for other ammonia condensers. • R YDLYME has also been incorporated into the preventative • Client only had one comment, “Unbelievable.” aftercoolers, as well as the facility’s entire cooling loop system! transfer and refrigeration temperatures. maintenance guidelines of these units. PAGE 4| APEX MONTHLY - DECEMBER 2013 www.apexengineeringproducts.com Don’t lose money on shutdowns A petrochemical company turns to RYDLYME H ow much money would your company lose every hour if you had to shutdown operations for equipment maintenance or repair? A couple hundred dollars? A few thousand? Millions? Many companies with large and complex equipment, such as critical heat exchangers and other water-operated systems, ponder this question every year. They weigh the risk-benefit of scheduling a maintenance shutdown and the costs involved versus postponing to a later date and risking costly equipment repair or failure down the road. What if you didn’t have to shutdown? What if there was a way to clean out your equipment while it continues to operate? These questions were presented to a petrochemical company in Texas who wanted to avoid a costly shutdown despite having a heat exchanger and adjoining reactor column on the verge of failure. The four-pass heat exchanger, which boasts more than 500 3/4-inch tubes (8 feet in length), suffered from severe calcium buildup resulting in low flow rates (100 gpm) and high cooling water outlet temperatures (160°F). This disconcerting combination of low flow and high cooling water temperatures put additional strain on the reactor column, as well as increased energy and water consumption. for an online cleaning a third-party service company, the client eagerly agreed to move forward with the online cleaning. Since the system was not conducive to recirculation, a 330-gallon tote of RYDLYME was setup for direct injection at 4 gpm into a 6-inch water supply pipe prior to the heat exchanger. This would allow the system to continue operating while RYDLYME goes through the heat exchanger and reactor column, dissolving the calcium buildup inside all the tubes. After just 33 minutes and 132 gallons of RYDLYME, flow rates increased by more than 50% to 200 gpm with cooling water outlet temperatures dropping more than 40% to 90°F! The entire system, including the overhead pressure in the reactor column, returned to normal operating conditions. In fact, the staff had to recalibrate controls and instrumentation back to factory settings after years of compensating for the system’s inefficiencies! In less than one hour, a major petrochemical company went from a potentially catastrophic shutdown to returning to normal operating efficiency without interruption to its operations. So next time, rather than asking yourself how much money you When told that RYDLYME could not only safely clean the system, but also do it without shutdown or hiring would lose for a shutdown, you should be asking yourself how much money would you save with RYDLYME. w w w . a p e x e n g i n e e r i n g p r o d u c t s . c o m RYDLYME improves efficiency on cooling tower A 35-ton cooling tower at a major college had compressors operating at more than 260psi just to maintain a 70°F water temperature due to heavy water scale. RYDLYME was put into the system to dissolve the scaling. Solution • 55 gallons of RYDLYME circulated for 4 hours via inline pumps then flushed with water • Cleaning was done while system was in operation! Results • C ompressors are only operating at 165psi to maintain the 70°F water temperature! • RYDLYME is now part of the cooling tower’s annual maintenance schedule. • Maintenance personnel found additional uses for RYDLYME, including cleaning: steam lines, humidifier at the fieldhouse and plate and frame heat exchangers. Cool air and quiet, just what the doctor ordered A hospital was experiencing significant cooling problems with its 350-ton chiller and cooling tower due to severe scaling to the point where the lowest temperature they could achieve was only 76°F. The chiller was constantly running and making so much noise that the staff moved blankets onto the unit just to keep the sound from disturbing the patients. Solution • 220 gallons of RYDLYME circulated for 5 hours via inline pumps then flushed with water • Cleaning was done while system was in operation! Results • T he chiller returned to cycling properly and no longer making noise; tower flow returned to normal. • S ystem was also able to provide desired temperatures without straining, or constantly running helping to decrease energy usage. APEX MONTHLY - DECEMBER 2013 | PAGE 5 Into the boiler room A 1,000-gallon boiler at a plant that processes feed ingredients for animals was experiencing overheating and significantly reduced performance due to excessive water scale. Solution • 440 gallons of RYDLYME circulated for 6 hours (solution was pumped into the bottom of the boiler and out the top) Results • A fter circulation and thorough water flush, the entire boiler was free of scale and returned to peak operating efficiency. • T he customer stated, “Outstanding! The boiler looked awesome.” • W hen asked about the difficulty level of doing this cleaning, the customer stated, “RYDLYME is the easiest product I’ve ever used!” Cleaning ketone stripper An Oklahoma oil refinery experienced heavy fouling on the distribution plates/packing material in its ketone stripper unit. The fouling was a result of caustic solution and water being steam heated. Solution • 990 gallons of RYDLYME • Circulated via 2-inch diaphragm pump for 8 hours Results • Client was extremely happy with the cleaning as the unit was able to effectively remove the ketone, improving efficiency. Also, RYDLYME is now part of the unit’s normal maintenance procedure • RYDLYME was also used in a prior job at the plant cleaning out a heat exchanger. The cleaning reduced temperatures from 300o to 150o F on process side and 160o to 125o F on tube side. PAGE 6| APEX MONTHLY - DECEMBER 2013 www.apexengineeringproducts.com Getting RYD of grease & grime with An industrial cleaning contractor needed a degreaser/cleaner to cut through a significant buildup of oil, carbon black, grease and other contaminants on a Banbury mixer from a tire manufacturing facility. Solution • 5 gallons of RYDALL MP (50% solution) sprayed on entire unit, soaked for a few minutes and then powerwashed with water. Results • In only one hour, and simple soaking and rinse, the mixer was free of grease and other contaminants! • C lient was extremely impressed and contractor was eager to use RYDALL MP for additional jobs! MP’s part in recycling A waste management company was experiencing problems thoroughly removing contaminants from plastic containers to prepare them for recycling. Solution • RYDALL MP diluted (10% solution) into the parts washer, heated to approximately 120°F and sprayed continously onto the contaminated plastic followed by a water rinse. Results • S etup allowed good coverage on material passing through, cleaning each thoroughly for recycling. • RYDALL MP’s biodegradability was a big plus with safe and easy disposal. Grease is the word A manufacturing facility in Wisconsin used RYDALL MP Multi Purpose Degreaser to cut through eight months worth of grease, grime and dirt buildup on its Haas ST30 CNC Lathe unit. The unit had never been cleaned. Solution • Spray bottle of RYDALL MP (50% - 50% dillution with water) • Sprayed area, let sit for approximately 1 minute and wiped off Results • After just 3 applications, the heavy buildup was gone • The company is using RYDALL MP on other equipment and areas throughout its facility, and RYDALL DD Definitive Degreaser on heavier grease buildups. w w w . a p e x e n g i n e e r i n g p r o d u c t s . c o m APEX MONTHLY - DECEMBER 2013 | PAGE 7 tackles landfill odor issues A Florida landfill was experiencing significant odor issues from the open face of implemented. Approximately 65,000 gallons of leachate is collected daily and stored the landfill and its leachate holding tank. The odors were not only a nuisance in an 80,000-gallon tank until hauled off to the local wastewater treatment plant for residents and businesses in the surrounding community, but also resulted in (WWTP), adding significant costs for haul-off and WWTP fees. costly fines on a regular basis. Essential oils, fragrances and other masking agents were largely ineffective and proved not to be cost-effective. In this second phase, approximately 13 gallons of RYDALL OE was added to the 65,000 gallons of leachate and retained for 24 hours. After the treatment, rather than having After learning about the science behind RYDALL OE Odor Eliminator, as well as calcu- the leachate hauled off, this now odor-free leachate was able to be recycled back lating the cost-savings, the landfill decided to use RYDALL OE in two phases. The first onto the landfill for further odor eradication without additional RYDALL OE dosing. phase was to dilute 7 gallons of RYDALL OE into 3,500 gallons of water and apply it over the open face of the landfill on a daily basis. In addition to the elimination of fines and odor complaints, the landfill also saw substantial savings from reduced haul-off and WWTP fees for its leachate. The amount After approximately one week, the repugnant odors emanating from the landfill sig- of RYDALL OE needed on a daily basis to maintain the optimal level of odor control nificantly decreased, putting an end to the regularly issued fines. To achieve further was also decreased as this non-active biocatalyst continued to work on all layers and odor eradication and cost-savings, the second phase targeting the leachate was areas of the landfill. Say Cheese! A specialty cheese manufacturer in Wisconsin had an ongoing odor problem since installing a wastewater treatment system, which includes a 4,000-gallon wastewater sludge tank. The primary odor problem was coming from the sludge tank, which was pumped out and taken off-site about once a week. The odor emanating from the wastewater process was a source of complaint from neighboring facilities and businesses, as well as from the town’s police headquarters five miles away! The solution to the odor included 12 ounces of RYDALL OE per day, dispensed 1 ounce per hour over a 12 hour work day. The solution was injected at 100 ppm via a small metering pump into the waste stream prior to reaching the sludge tank. In just two days, the strong, pungent odor from the wastewater process was almost completely eliminated! The expedited result was due to the injection of RYDALL OE to the wastewater stream prior to it reaching the tank, which allowed ample mixing and retention time. The facility’s plant manager stated, “We’ve had no phone calls from the police or fire department, and none of our neighbors have complained since using RYDALL OE. We are very pleased with the result and will continue to use the product to control odor.” With such a positive result from the sludge portion of the wastewater process, the plant is now evaluating the use of RYDALL OE to help control extremely high BOD’s in the main waste stream. PAGE 8| APEX MONTHLY - DECEMBER 2013 www.apexengineeringproducts.com Down & dirty in the sewers reduces odors and contaminants in Oconto, Wisconsin T he city of Oconto, Wisconsin was looking to reduce corrosion from high levels of H2S at one of its sewer line lift stations, as well as odors that resulted in several complaints from residents. The system was also experiencing high and fluctuating levels of BOD, FOG, COD and TDS. Three sanitary districts feed into this sewer line through several miles of enclosed plastic sewer pipe with approximately 33,000 gallons of residential sewage flowing through this particular monitoring station. In addition to monitoring daily H2S levels using an Oda-Log monitoring system, the city was using Bioxide to control odors and corrosion. Anywhere from 2 gallons to as much as 15 gallons of Bioxide were added to the system per day, but was not effectively solving the issues. RYDALL WO Solution After understanding the science and benefits behind RYDALL WO, the city agreed to use the non-active biocatalyst per our recommendation to reduce the odors, corrosion and contaminants. We recommended injecting RYDALL WO at 100 ppm (3.3 gallons per day) with a metering pump at a lift station approximately 7 miles upstream from the problematic area. This allowed approximately 2.5 days of retention time for RYDALL WO to work. Along with the city’s continuous monitoring of H2S levels, samples of the wastewater were also taken weekly from each location and tested by an independant third-party for BOD, FOG, COD and TDS levels (samples of the wastewater prior to treatment were also taken for control purposes). Over the course of the next 90 days, our tests showed average levels of BOD, FOG, COD and TDS decreased significantly, as shown in the next column. On average... •BOD levels decreased by 28%! •FOG levels decreased by 67%! •COD levels decreased by 30%! •TDS levels decreased by 23%! •H2S levels decreased by 50%! Compared to the city’s data from a similar time frame in 2012 when Bioxide was used, the amount of H2S released during RYDALL WO treatment decreased by more than 50%! Within the first couple weeks, odors from the problematic lift station were drastically reduced and there were no odor complaints from the surrounding community. Also, the city saw a significant reduction in corrosion at the site. Components that were normally replaced due to corrosion from H2S, did not have to be replaced during the trial. w w w . a p e x e n g i n e e r i n g p r o d u c t s . c o m APEX MONTHLY - DECEMBER 2013 | PAGE 9 Starch processor puts to the test A specialty starch processor in Maine was intrigued by the capabilities of weeks of RYDALL WO being in the system, the bugs were still big and healthy. This RYDALL WO in reducing the amount of produced sludge and its effluent resulted in a cost-savings for the client as no solids needed to be dewatered, BOD levels. Apex provided a small sample of RYDALL WO to the client for pressed or hauled off! testing on a sample of its wastewater obtained from the sludge tank. Prior to the start of the test, the BOD level in the sample wast water measured 5,500 mg/l. We recommended applying 200 ppm of RYDALL WO to the sample and measuring the BOD level after a few days. After just six days, the BOD level dropped significantly, measuring only 75 mg/l! RYDALL WO not only reduced the BOD level by nearly 99%, the client observed very healthy “bugs” under a microscope. The dramatic results from the test prompted the client to state, “I’ve been in this field for 10 years now, tried lots of stuff, and this sure is different!” As a result of this successful lab test, our client decided to take the next step… adding RYDALL WO to its 350,000-gallon sludge tank. The client purchased a 55-gallon drum of RYDALL WO, which arrived at a time when his sludge tank was at maximum capacity and recovering from turning anaerobic due to bad starch the plant had processed. They had been running blowers constantly for two “ I’ve been in this field for 10 years now, tried lots of stuff, and this sure is different! ” weeks, but were unable to settle the tank during this period. The client immediately added (2) gallons of RYDALL WO to the sludge tank and Further enhancing the wastewater treatment process and cost-savings, the ex- after two days, they were amazed at immense growth in bugs and activity. An ceptional quality of the supernate has allowed it to be pumped back to the additional (2) gallons were added to the tank, and after the first week, they beginning of the whole waste system. were able to shut off the blowers and release 22,000 gallons of supernate (releasable water)! Additionally, RYDALL WO effectively controlled the filamentous bacteria within the system, eliminating foaming and other adverse effects that usually occur with At this point, the client let the system continue and during the second week, they an overabundance of the filamentous bacteria, as well as the need for extensive were able to pump off an additional 100,000 gallons of supernate! After four and costly nutrient replacement to counteract those effects. PAGE 10 | APEX MONTHLY - DECEMBER 2013 FOUL TERRITORY www.apexengineeringproducts.com A whimsical concotion of information in the world of scale, grease, odors and more. Great ball of fat LONDON (AFP) A 15-ton ball of congealed fat -- dubbed Britain’s biggest ever “fatberg” -- was removed from a London sewer after a 10-day operation following complaints from local residents that their toilets would not flush. FOULEST STORY OF 2013! The monstrous lump of festering food fat mixed with wet wipes -- the size of a bus -- formed in drains under a major road in Kingston, southwest London, utility firm Thames Water said Tuesday. Had it not been removed, the deposit could have led to sewage flooding homes, streets and businesses in the leafy London suburb, Thames Water said. “While we’ve removed greater volumes of fat from under central London in the past, we’ve never seen a single, congealed lump of lard this big clogging our sewers before,” Gordon Hailwood, waste contracts supervisor for the company, said in a statement. “Given we’ve got the biggest sewers and this is the biggest ‘fatberg’ we’ve encountered, we reckon it has to be the biggest such berg in British history.” “The sewer was almost completely clogged with over 15 tonnes of fat. If we hadn’t discovered it in time, raw sewage could have started spurting out of manholes across the whole of Kingston.” “It was so big it damaged the sewer and repairs will take up to six weeks.” CCTV images from the sewer showed that the mound of fat had reduced the 27 by 19-inch drain to five per cent of its normal capacity. CountyClean Environmental Services, the waste management company that removed the deposit, said it would go to good use. “We recycle everything that we remove -- the water is extracted and the remaining fats and oils are turned into products like soap, biodiesel and fuel,” a CountyClean spokesman told AFP. “We have a very specialized piece of equipment -- called a Kroll recycler -- that we can use from the road and allows us to remove the fat without any workmen having to descend into the sewers.” Thames Water warned homes and businesses needed to change their ways when it came to the disposal of fat and wet wipes, urging people to “Bin it -- don’t block it.” Regular dosing of RYDALL WO Water Optimizer into that sewer system could have prevented the Cloverfield of fat and wet wipes. DESCALER & PUMPING SYSTEMS RYDLYME biodegradable descaler is specifically designed to dissolve the toughest water scale, lime scale, mud and rust deposits from virtually any piece of water-based equipment. NSF-certified. 1241 Shoreline Drive Aurora, Illinois 60504 T: 630.820.8888 | 800.451.6291 F: 630.820.8886 For 70 years, Apex Engineering Products has been formulating and manufacturing safe and biodegradable specialty cleaning chemicals for a diverse range of applications around the world. From our RYDLYME biodegradable descaler to our versatile RYDALL line of cleaners and degreasers, our products will decrease downtime and increase efficiency. We are a fourth-generation, familyowned company renowned not only for our biodegradable line of products, but also our in-depth and exceptional customer support. With decades of knowledge and experience in a wide array of applications, our knowledgeable technicians will work closely with you to determine the best solution for your facility’s unique challenges. To further minimize your downtime, virtually all orders are shipped out within 24 hours. Apex Engineering Products also takes great pride in being an ISO 9001:2008 Certified Company providing the highest level of support and quality of products to our customers…another formula that hasn’t changed in 70 years! Made in the USA RYDLYME Pumping Systems are specifically designed to circulate RYDLYME through a vast array of equipment and systems keeping your facility in peak operating condition. CLEANERS & DEGREASERS RYDALL CC Coil Cleaner is a biodegradable coil cleaner specifically designed to clean dirt, grease and soil residue from air-exposed surfaces of critical cooling or heating equipment. NSF-certified. RYDALL MP Multi Purpose Degreaser is a biodegradable, medium-duty degreaser/ cleaner that quickly and safely removes oil, grease, grime and other pollutants from all surfaces and components. NSF-certified. RYDALL DD Definitive Degreaser is a biodegradable, heavy-duty degreaser used specifically on all carbon-based derivatives found on the oil and/or process side of your equipment or system. RYDALL VP Specialized Degreaser is a biodegradable, pH neutral degreaser specifically designed to safely and quickly clean and degas refinery process equipment. It can be applied in circulation or vapor phase applications. RYDALL CX Crude Deposit Cleaner is a biodegradable cleaner specifically designed to clean crude oil exchangers where pyrophoric corrosion deposits (e.g. iron sulfides) are present without having to pull bundles or dismantle exchangers. ODOR CONTROL & WATER TREATMENT RYDALL OE Odor Eliminator is a unique, environmentally beneficial biocatalyst containing a complex mixture of natural nutrients, vitamins, and trace elements designed to eliminate industrial odors and corrosion problems. RYDALL WO Water Optimizer is an environmentally beneficial additive that disallows the formation of H2S, COD, BOD, FOG, TDS and TSS. This unique biocatalyst is also effective in enhancing methane production and O2 content. [click on logos to learn more]