PLC Interface for High Inrush Currents (Lamp Loads, Capacitive

advertisement
PLC Interface for High Inrush Currents (Lamp Loads,
Capacitive Loads, Etc.) With Screw or Spring-Cage
Connection – PLC-R...1IC/ACT
1. Short Description
PLC interface, the narrow, plug-in, and flexible
modular interface system with a user-friendly plug-in
bridge system, now offers an extended range of relay
interfaces for special load applications, such as lamp
loads, capacitive loads and/or loads with increased
continuous current.
Lamp Loads and Capacitive Loads
The most difficult loads to manage include all loads
with high inrush currents. If the wrong relay is selected,
this can considerably shorten service life due to welded
contacts.
These heavy loads include all types of lamps that
cause high inrush currents due to their low cold
resistance. This category also includes loads that cause
high inrush peaks due to capacitors in the circuit. These
include energy-saving lamps, shunt-compensated
fluorescent tubes or types with electronic ballasts,
AC motors with starting capacitor, etc.
Inrush Currents up to 130 A
The 14 mm wide PLC-R...-24DC/1IC/ACT inrush
current relay offers the ideal solution with an N/O
contact designed specifically for these applications.
This relay safely manages short-term inrush peaks of
up to 130 A. The maximum permissible continuous
current is 6 A, when the double contact connections of
the relay are connected (e.g., with the FBST 14-PLC…
plug-in bridge) continuous currents of up to 10 A are
supported. The block is controlled with 24 V DC signals
directly from PLCs, IPCs or DDCs.
The actuator block version enables the connection
and bridging of lamp and motor return conductors,
which eliminates the need for additional return
conductor terminal blocks.
All Other PLC Advantages
The PLC-R…1IC/ACT series also features the other
advantages of the PLC range:
– User-friendly plug-in bridge system
– Integrated input wiring
– Relay can be quickly replaced using an engagement
lever
– Safe isolation between I/O
– Markers from the standard modular terminal block
range
– Cost-effective
Phoenix Contact GmbH & Co. KG • 32823 Blomberg, Germany
Phone +49 - 52 35 - 30 0 • Fax +49 - 52 35 - 34 12 00 • www.phoenixcontact.com
Local Contact: www.phoenixcontact.com/salesnetwork
PLC Interface for High Inrush Currents – PLC-R...1IC/ACT
A2
13
A1
BB
1)
94 mm
2. Technical Data
2
14
1
80 mm
1 PLC-RSC...1IC/ACT
2 PLC-RSP...1IC/ACT
8 mm
M3
Terminal block width 14 mm
Solid
uF
Stranded
[mm2]
AWG
Connection data 1 0.14 - 2.5
Connection data 2 0.2 - 2.5
0.14 - 2.5 26 - 14
0.2 - 1.5 25 - 14
Description
PLC interface
24 V DC input voltage, comprising PLC-BSP...
basic terminal block and plug-in miniature
relay, for mounting on 3
1 Screw connection
2
Spring-cage
connection
Type
Order No.
Pcs.
Pkt.
PLC-RSC-24DC/1IC/ACT
PLC-RSP-24DC/1IC/ACT
29 67 60 4
29 12 41 3
10
10
Technical Data
Input Data (Input)
Nominal input voltage UN
Permissible range (with reference to UN)
Typical input current at UN
Typical response time at UN
Typical release time at UN
Input wiring:
24 V DC
Output Data (Output)
Contact type
Contact material
Maximum switching voltage
Minimum switching voltage
Limiting continuous current
Maximum inrush current
Minimum switching current
Maximum shutdown power, ohmic load:
Minimum switching power
24 V DC
48 V DC
60 V DC
110 V DC
220 V DC
250 V AC
24 V DC
Diagram (see INTERFACE catalog)
18 mA
8 ms
10 ms
Operating indicator, diode for protection against polarity reversal,
free-wheeling diode
Single contact, 1 PDT
AgSnO
250 V AC/DC 3)
12 V AC/DC
6 (10) A4)
80 A for 20 ms
130 Apeak at capacitive load, 230 V AC, 24 µF
100 mA
144 (240) W4)
58 W
48 W
50 W
80 W
1500 (2500) VA4)
1.2 W
Phoenix Contact page 2 of 3
PLC Interface for High Inrush Currents – PLC-R...1IC/ACT
General Data
Rated voltage withstand level of I/O
Ambient operating temperature range
Nominal operating mode
Inflammability class of housing
Mechanical service life
Air and creepage distances between circuits according to:
Mounting position/mounting
1)
Input wiring depends on the type, see Technical Data for input side.
Available for screw versions, provided for spring-cage versions.
3)
For voltages greater than 250 V (L1, L2, L3) between the same
terminal points on adjacent modules, the PLC-ATP insulating plate
(see INTERFACE catalog) should be fitted. FBST 8-PLC... or
FBST 500... can be used for potential bridging.
4)
The values in brackets are permitted if connections 13/13, 14/14, and
BB/BB are bridged.
5)
The PLC-ATP insulating plate (see INTERFACE catalog) should be
fitted between adjacent modules for safe isolation. FBST 8-PLC... or
FBST 500... can be used for potential bridging.
Notes:
Insulating housing version
Spring-cage version: Polyester PBT not reinforced
Screw version: PA not reinforced
(see INTERFACE catalog)
Color: green
For torque of terminal block screws, see INTERFACE catalog.
For marking systems and assembly material, see CLIPLINE
catalog.
The dimensioning cross section (see INTERFACE catalog) refers to
simple wires without ferrules.
Inductive loads must be attenuated with an effective protective circuit
to protect inputs and outputs.
The PLC-ATP insulating plate should always be fitted at the start
and end of a PLC terminal strip.
TNR:5104192-01-gb/03/15/05 © Phoenix Contact 2005
2)
6 kV
-20°C to +60°C
100% operating factor
V0 according to UL 94
3 x 107 cycles
DIN EN 50178/VDE 0160
Safe isolation, reinforced insulation I/O5)
Pollution degree 2
Surge Voltage Category III
Any/can be mounted without spacing
Phoenix Contact page 3 of 3