Features
• pure sine wave
• „long-life“ batteries
• Smart backup time estimation
• Adjustable voltage sensitivity, voltagetransfer points & charging voltage
• Generator compatible
• Automatic restart of load after UPS
shutdown
• Smart AVR function
(Two buck / boost modes)
• Cold-start capable
• Audible alarm
• Hot-swappable batteries for rack models
• Smart battery management
• Network manageable (SNMP optional)
• Full function of LCD display (LED display optional)
• Intelligent double stages of charging control
• Power Management Software inclusive
Micro-S 5000 RM/Tower convertible
Applications:
• Networkserver
• Small computersystems
• Data centers
• Telecommunicationssystems
• Industrial applications
• Safty and protection system
Micro-S Pro/
Micro-S RM Pro
Model (Tower version)
Micro-S 1000
Pro
1000 VA/
600 W
Micro-S 1100
RM-Pro
1100 VA/
660 W
Capacity, Power Levels (VA/W)
Output
Voltage
Voltage waveform
Crest factor
Frequency (synchronized to mains)
Regulation (nominal)
Regulation (battery mode)
Transfer time
Over current protection
Input
Nominal Voltage
Frequency
Efficiency (normal mode)
Noise filtering
Over current protection 230V
Over current protection 115V
Voltage range
AVR range (2 bucks, 2 boosts)
Surge protection 230V models
Surge protection 115V models
Battery
Type
Capacity Tower
Capacity 19"RM
Voltage in Vdc
Backup time half-load
Charging method
Charging time
Average charging current
Average charging voltage
for each battery
Protection
Monitoring
Micro-S 800
RM-Pro
800 VA/
480 W
Micro-S 5000
5000 VA/
3750 W
Micro-S 5000
RM
5000 VA/
3750 W
100/110/115/120 V or 200/220/230/240 V selectable
47Hz ~ 65Hz, 50/60Hz auto-sensing
97%
full time EMI/RFI filtering
by AC fuse
by re-settable over
current protector
by AC fuse
by re-settable over current protector
´-20% ~ +24% for selected nominal voltage;
-29% ~ +33% adjustable by using the remote set-up software
enhanced buck: +15% of selected nominal voltage;
buck mode: +5% of selected nominal voltage boost mode: -5% of selected nominal voltage;
enhanced boost: -12.5% of selected nominal voltage
220 Joules
440 Joules
660 Joules
216 Joules
324 Joules
maintenance-free sealed, valve-regulated, lead-acid
12V-7Ah
12V-7Ah
12V-9Ah
12V-9Ah
12V-7Ah
6V-9Ah
12V-9Ah
12V-7Ah
12V-9Ah
12V-9Ah
12V-7Ah
18
24
36
48
72
72 (2x6 Batt.)
18 Min.
14 Min.
12 Min.
smart pulse charging with two charging modes:
Quick charging when battery is not fully charged;
trickle charging when battery is 90% fully charged
less than 3 hours to 90% at normal line and normal temperature
2.5A
quick charging mode: 14V maximum trickle
charging mode: 13.2V ~ 13.9V adjustable with the remote set-up software
over current protection (SCR control); over charging voltage protection (SCR control);
thermal protection (CPU control); When temperature inside UPS is over 45°C, charger will
stop charging for 2.5 minutes followed by an 1.5 minutes charging. The cycle will be
repeated until the temperature is lower than 44° C.
smart monitoring&warning for failed battery or open-circuit battery.
Auto-detection each time when power on or every 6 days
RS232, DB9, USB, optional for RJ45
Standard interface port 19" RM
Software
Optional interface port Tower
EBT(estimation of backuptime)
Green mode function
(auto-shutdown during blackout)
Environmental and safety
Operation temperature
Transit/storage temperature
Relative humidity
Operating altitude
Audible noise, 1M from surface
Safety markings Tower
Safety markings 19" RM
EMC
Quality control system
Physical
Dimensions (DxHxW)
unit/shipping Tower in cm
Dimension (DxHxW)
unit/shipping 19" RM in cm
Weight (Net/Gross kg) Tower
Weight (Net/Gross kg) 19" RM
Packing
Micro-S 3300
Pro
3300 VA/
2000 W
Micro-S 3300
RM-Pro
3300 VA/
2000 W
100/110/115/120 V or 200/220/230/240 V selectable
sine wave
3:1
auto select for 50/60 Hz; 47Hz ~ 55Hz for 50Hz nominal; 56Hz ~ 65Hz for 60Hz nominal
±5% typical of nominal voltage (optional at ±8% AVR for wide I/P upt to ±35%)
±3% of selected output voltage (adjustable by using the remote set-up software)
blackout 3ms typical; brownout 1ms typical; battery mode to normal mode: 1ms typical
over load alarm level 100% ~ 120%; over load shutdown level 120% ~ 190%,
(adjustable by using the remote set-up software)
Communications & Management
Standard interface port Tower
Optional interface port 19" RM
Control panel
Audible alarm
Micro-S 2200
Pro
2200 VA/
1350 W
Micro-S 2200
RM-Pro
2200 VA/
1350 W
RS232, DB9, USB, RJ45 optional (Surge Protection)
UPSilon 2000 compatible
SNMP external type
3xRS232,DB9, USB,
RJ45 optional
as Tower
internal or
external
SNMP external
SNMP internal oder external type
LCD or LED selectable
alarm on battery: low battery & battery over voltage,
alarm on abnormal operation: Over load, Short-circuit & over heat
support for LCD display
1% to 14% full load (adjustable by using the remote set-up software)
The default setting is OFF.
up to 1500 meters: 0°C to 40°C (32°F to 104°F)
-15°C to 55°C (5°F to 131°F)
5 - 95% non condensing
0 ~ 3000 meters
≤ 40 dBA
EN 62040, 230V-models: CE, 115V-models: BSMI;
EN 62040, CE
Class B, EN50091-2, FCC part15, IEC1000-2-2
ISO 9001
18x20x38 / 30x33x48
1HE x 40
18x20x45 /
30x33x54
2HE x 47 / 59x61x22.5
18x20x51 / 30x33x61
17,8x48,3x52
3HEx47/
4HEx52
58x62x27
15/16 kg
21/22 kg
25/26 kg
36/37 kg
70/74 kg
14/16 kg
18/20 kg
23.5/25.5 kg
28/30 kg
41/43 kg
70/74 kg
export carton for each unit, Tower: 16-30 / 19“ RM 14~21 units per pallet
AdPoS Advanced Power Systems GmbH & Co. KG
Pfaffensee 2 · D-91301 Forchheim
Tel. +49 (0) 91 91 / 70 05 - 0 · Fax +49 (0) 91 91 / 70 05 - 20
info@adpos-ups.de · www.adpos-ups.de
November 2012
Model (19“ RM-version)
Capacity, Power Levels (VA/W)
Micro-S 1500
Pro
1500 VA/
900 W
Micro-S 1650
RM-Pro
1650 VA/
1000 W
Download