842 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS. VOL. IA-21, NO. 4. JULY/AUGUST 1985 Understanding Asymmetry CRAIG N. HARTMAN, MEMBER, IEEE Abstract-When calculated fault levels lie very close to circuit breaker interrupting ratings, a thorough evaluation of the asymmetrical currents involved may become the deciding factor between breakers of varied capabilities and costs. The increasing emphasis on efficiency tends to exacerbate concerns in this area. An attempt is made to help the reader visualize the events of the first few cycles after fault inception as well as providing a rigorous quantitative analysis of the magnitude of currents involved. Equations for sizing both molded-case and power circuit breakers are developed. INTRODUCTION WHENEVER a short-circuit occurs on a conductor there Time (Cycles) exists a transient response time during which the circuit (a) circuits In ac attempts to reach a steady-state fault condition. Magnitude (P.U.) of those excess in currents produce may response transient this 2.0 encountered either before the fault occurred or after the DC Componn Asymmetria steady-state condition is achieved. These high currents must be taken into consideration when specifying power system equipment. It is instructive to note the effect which high efficiency equipment is having on this type of analysis. Generally transformers constitute the bulk of the systems impedance, and thus have a predominate effect on the system X/R ratio. A 00 0 Q1 0.2 0.3 0 4 0.5 0.6 0.7 0 8 0.9 1 0 cursory look at this situation would indicate that increasing the Time (Cycles) efficiency of a transformer from 98-percent to 99-percent (b) would have the effect of doubling the X/R ratio. This effect is Fig. 1. Fully offset wave. seen in virtually all high efficiency equipment. The X/R ratio 3) the fault impedance is purely inductive; of modem distribution systems commonly exceeds the estab4) no current was flowing prior to fault inception. lished X/R ratio of the protective equipment, thus requiring derating. Referring to Fig. 1(a) we note that at time zero both current The author feels that it is important not only to take these and voltage are zero. Recall that the rate of change of current factors into account when sizing the equipment, but also to in an inductor is proportional to the voltage across that device. have some visual conception of what actually takes place At time 0.05 cycles the voltage is beginning to rise but is still during those first few cycles following inception of a fault. It is rather low. The current in the inductor is also beginning to felt that a good visualization of the situation would clarify a rise, but the slope of current change is small in response to the number of misconceptions which exist relative to this subject. low voltage value. As the voltage increases, the rate of change Accordingly this article shall begin by "walking through" a (slope) of the current wave increases in response. At time 0.25 hypothetical fault. cycles the voltage reaches a maximnum, and the slope of current is at its steepest value. NoW the voltage begins to drop, FAULT VISUALIZATION but since it is still positive the current continues to increase. At A worst-case condition is assumed in which time 0.45 cycles the current is still increasing, but due to the 1) the fault occurs at an instant of time when the source low voltage level the current increases at a very slow rate. At time 0.5 cycles the current finally reaches its maximum value. voltage is equal to zero; 2) the source voltage can supply an infinite amount of Not until the voltage goes negative can the current begin to decrease. Using the same arguments one can follow the course current with no voltage dip; cycles. Paper IPSD 84-38, approved by the Power Semiconductor Committee of of the current wave back to zero magnitude at time 1.0 Using the same reasoning above, but with the fault the IEEE Industry Applications Society for presentation at the 1984 Industrial and Commercial Power Systems Conference, Milwaukee, WI, May 9-12, occurring at a voltage maximum, one could trace a current 1984. Manuscript released for publication November 2, 1984. (no The author is with the Westinghouse Electric Corporation, 3900 S. wave which is symmetrical with regard to current zero offset). By looking at the two waves it bbecomes obvious that Wadsworth Blvd., Lakewood, CO 80235. - 0093-9994/85/0700-0842$01.00 (© 1985 IEEE Authorized licensed use limited to: CHILECTRA. Downloaded on May 03,2010 at 22:48:37 UTC from IEEE Xplore. Restrictions apply. 843 HARTMAN: UNDERSTANDING ASYMMETRY the fully offset current wave is simply obtained by adding a dc current equal to the peak magnitude of the symmetrical wave to the wave itself (Fig. 1(b)). The actual value of the dc component would depend on the time at which the short-circuit in the voltage wave and is quantitatively equal and opposite to the value of the steady-state symmetrical current wave at time zero. When the dc current assumes a value equal to the peak value of the symmetrical current, we say that the wave is fully offset (maximum asymmetry). It is possible under certain circumstances to get more than 100-percent offset, but these special circumstances are beyond the scope of this paper. occurs QUANTIFYING THE CURRENT VALUES In real life, of course, perfect inductors do not exist any more than do perfect voltage sources. In order to obtain more realistic actual values the hypothetical fault circuit discussed above will be modified to include a resistance. This circuit is now as shown in Fig. 2. If the switch is closed at time zero to simulate initiation of the fault and if current values are per-unitized according to the peak symmetrical current (IO) then the current plot is a function of three independent variables (0, X/R, and time). Equation (1) results from using Kirchhoffs voltage law to sum the voltages around the circuit of Fig. 2 and then solving the resulting nonhomogeneous first order differential equation for current. I= IO{sin [arctan (X/R) exp [- 27rt/(X/R)1 (dc component) + sin [2rxt arctan (X/R)I} (ac component) (1) where Io symmetrical peak current X reactance value R resistance value t time (cycles). A few comments concerning (1) might be expedient at this point. The voltage and current waves will be displaced from each other by an angle corresponding to the amount of reactance in the circuit compared to the amount of resistance in the circuit. This angle is equal to arctan (X/R). When the circuit is purely inductive (which it is to a large degree during faults on high power circuits) the current wave will be displaced from the voltage wave by 90 degrees. As resistance is added to the circuit this angle will go from 90 degrees to zero degrees so that in the purely resistive circuit the voltage and current will be completely in-phase. Also note that at time zero the dc component is exactly equal in magnitude to the value of the ac component but opposite in sign. This condition must exist due to the fact that current cannot change instantaneously in an inductive circuit. The argument of the exponential indicates that the dc component will decay at a rate dependent on the X/R ratio. MAXIMUM ASYMMETRY VERSUS MAXIMUM PEAK CURRENT to It is Interesting note that the maximum asymmetrical peak currents do not generally occur during conditions of maximum asymmetry. It has been shown [I] that the maximum peak asymmetrical current will be produced for any X/R ratio when the fault occurs at voltage zero (O = 0). As shown in (I), however, maximum asymmetry exists when the fault occurs at a symmetrical current component maximum (0 = arctan (X/R) - 90°). (Maximum asymmetry is defined as being that state which produces the maximum dc component value.) Thus the fault angle for maximum peak current is always zero whereas, the fault angle for maximum asymmetry ranges from 0-90 degrees. Table I shows the maximum actual peak current for several X/R ratios, along with the dc component, ac component, and the time in cycles at which the current peaks. Table II TABLE I MAXIMUM FAULT CURRENTS - X/R I Ii I. I Time 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 10 15 20 25 30 35 40 45 50 100 1000 1.00 1.00 5E-9 3E-5 6E-4 3E-3 0.01 0.02 0.03 0.04 0.06 0.07 0.25 0.39 0.49 0.56 0.74 0.82 0.86 0.88 0.90 0.92 0.93 0.93 0.94 0.97 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0.26 0.28 0.29 0.31 0.32 0.33 0.34 0.35 0.36 0.36 0.41 0.43 0.44 0.45 0.47 0.48 0.48 0.49 0.49 0.49 0.49 0.49 0.49 - V Ldi VL=L-Ll dit (J' v(t) =Vo sin v st VR=Ri(t) (wt +o) I.,, id I. In T Fig. 2. Asymmetrical circuit model. 1.00 1.00 1.01 1.02 1.03 1.04 1.05 1.07 1.24 1.38 1.48 1.55 1.74 1.81 1.86 1.88 1.90 1.92 1.93 1.93 1.94 1.96 2.00 0.99 0.99 0.99 0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.01 1.06 1.14 1.21 1.27 1.45 1.53 1.57 1.60 1.62 1.64 1.65 1.66 1.66 1.70 1.73 0.50 0.50 maximum current in per-unit of peak symmetrical dc component in per-unit of peak symmetrical ac component in per-unit of peak symmetrical rms current in per-unit of symmetrical rms time to I, in cycles. Note: Maximum peak always occurs when fault is initiated at zero voltage (not maximum asymmetry). Authorized licensed use limited to: CHILECTRA. Downloaded on May 03,2010 at 22:48:37 UTC from IEEE Xplore. Restrictions apply. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 844 IA-21. NO. 4. JULY/AUGUST 1985 TABLE II DIFFERENCES IN CALCULATED FAULT LEVELS ACCORDING TO METHOD OF CALCULAFION .I Ipeak maximum X/R asymmetry 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 1.000 1.000 1.000 1.000 3 4 5 10 15 20 25 30 35 40 45 50 100 1000 Inf. 1.002 1.005 1.011 1.020 1.030 1.043 1.208 1.351 1.456 1.533 1.730 1.811 1.855 1.882 1.901 1.914 1.924 1.933 1.939 1.969 1.997 2.000 1p,ek (maximum asymmetry) I'k (maximum peak) 'ems (maximum asymmetry) ,e,s (maximum peak) rm* 'peak maximum peak 1.000 1.000 1.001 1.003 1.008 1.016 1.026 1.039 1.053 1.069 1.242 1.379 1.477 1.550 1.737 1.814 1.857 1.883 1.902 1.915 1.925 1.933 1.939 1.696 1.997 2.000 Difference (percent) 0 0 0.10 0.26 0.61 1.05 1.44 1.86 2.14 2.41 2.75 2.04 1.43 1.07 0.38 0.16 0.13 0.06 0.05 0.04 0.03 0.02 0.01 0 0 0 frms I,ms maximum asymmetry maximum peak 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 Difference 1.002 1.042 1.116 1.190 1.253 1.438 1.522 1.569 1.599 1.619 1.634 1.646 1.655 1.662 1.273 1.477 1.526 1.572 1.601 1.621 1.636 1.647 1.656 1.663 1.697 1.728 1.732 1.732 1.001 1.004 1.009 1.016 1.025 1.036 0.09 0.16 0.21 0.31 1.76 2.07 1.99 1.60 0.64 0.28 0.21 0.15 0.11 0.10 0.06 0.05 0.03 0.02 1.214 1.627 1.728 1.000 0 0 0 0 0 0 1.000 1.000 1.000 1.000 1.001 1.002 1.003 1.005 1.061 1.140 1.001 I.* (percent) 1.048 1.062 1.076 1.2 19 1.324 1.395 1.446 1.571 1.620 1.646 1.662 1.673 1.681 1.687 1.692 1.695 1.713 1.729 1.732 0.02 0 peak current under conditions of maximum asymmetry maximum peak current possible rms current under conditions of maximum asymmetry rms current under conditions of maximum peak current actual calculated rms current over the first half-cycle assuming conditions of maximum asymmetry. compares the actual maximum peak current to the peak current under conditions of maximum asymmetry. Since finding maximum current magnitudes using (1) is rather unwieldy, the traditional method for calculating currents has been to assume a fault of maximum asymmetry and then calculate the peak current at 0.5 cycles. Substituting these assumptions into (1) yields the following: (2) Ipeak = 'o exp [ -7r/(X/R)] + 1. As shown in Table II the maximum error one can expect from using this simplification will be less than 3-percent. For high X/R ratios, where asymmetrical current is most important, the errors are negligible. In addition to the maximum peak value of current, one may also be interested in the value of peak or root mean square (rms) current at other times (e.g., at the time the circuit breaker interrupts the circuit). Fig. 3 shows a typical plot of current for an X/R ratio of 15. Either peak or rms current values may be obtained at any instant of time by simply knowing the values of the dc and ac components. A common misconception is that high asymmetrical currents are the result of stored energy which is released from the system during the first few cycles. Actually, exactly the opposite is true. Any energy stored in the system inductances tends to reduce the amount of asymmetry which occurs. Also, asymmetry is maximum when the power factor of the fault is close to zero indicating that the energy loss is only a small Magnitude (P.U.) 20 DC Components 1.8 g 1.6 - 14 _Actual Current - 1.21.0 0.8p A tu l XI -02 0.2 04 - 0 6 - 0.8 =06. -,i 11olI I I I 7 I AI I I I X I I 00 05 1.0 1.5 20 25 3.0 3.5 40 45 5.0 5.5 60 6.5 70 Time (Cycles) Fig. 3. Current wave for an X/R of 15. fraction of the kilovolt ampere figure. Thus far we have discussed only a simple series inductanceresistance (LR) circuit. It is obvious that, were two such circuits to feed a fault, the asymmetrical current would be the sum of the current contributions from each leg of the circuit. While combining the two impedances into a Thevenin's equivalent impedance would yield accurate values of symmetrical current, the asymmetric current would contain an error dependent on the mismatch of X/R ratios of the two legs. Modern distribution systems contain many series/parallel elements making rigorous analysis unfeasible. In addition, the power system data is rarely characterized with better than 10percent accuracy when all is told. One should therefore not be caught up in assuming an accuracy of calculation greatly Authorized licensed use limited to: CHILECTRA. Downloaded on May 03,2010 at 22:48:37 UTC from IEEE Xplore. Restrictions apply. 845 HARTMAN: UNDERSTANDING ASYMMETRY beyond the accuracy of the assumptions. All calculation methods presently employed are the result of judicious compromise, generally containing both conservative and nonconservative elements. A final note to consider is that when generation is close to the fault or there is a substantial motor load the ac component of the wave will decay along with the dc component. Neither ac decrement nor methods of computing fault levels in power systems will be covered in this discussion. Although brief mention is made of ac decriment curves in the high voltage circuit breaker section of this paper one should refer to a more extensive treatise on circuit breaker application [2] for this information. APPLICATIONS TO AC CIRCUIT BREAKERS Since asymmetrical currents play an important role in the rating of ac circuit breakers it may be appropriate to address the subject of circuit breaker ratings in connection with this discussion. rms and Peak Currents Since circuit breakers are generally rated with reference to rms amperes it is important to discuss exactly what this term means and how it relates to peak currents and circuit breaker ratings. Mathematically an rms value is computed by taking the square root of the mean (arithmetic average) of the square of the current wave oVf r a certain period of time. Thus the term rms is inseparably ,onnected with the value of time over which it is compared. The rms value bears no relationship to the peak value unless the shape of the current wave is known. When an ac periodic nondecaying sinusoidal wave is superimposed on a dc wave the rms value will be the square root of the sum of the squares of the ac symmetrical rms value and the dc value. In circuit breaker ratings rms values are computed in this manner by taking a "snapshot" of the dc current component at a certain instant of time and calculating the rms value as if this dc component were constant over the entire cycle. This value might be referred to an an "instantaneous rms" (which almost seems to be a contradiction of terms) and is much simpler to compute than a real rms value over a period of time. According to ANSI C37.04-1979 [7]. ...the required asymmetrical interrupting capability of a circuit breaker is the highest value of the total short-circuit current rms amperes at the instant of primary arcing contact separation... All rms currents mentioned henceforth is this article will be computed using the instantaneous rms concept. (Table II shows the actual rms values over the first half-cycle of the fault current wave, assuming maximum asymmetry, for comparison.) A Circuit Breaker Primer When fault current flows through a breaker, magnetic forces proportional to the square of the instantaneous current are created which tend to blow the contacts apart or otherwise cause mechanical damage. These considerations are most important in establishing the momentary rating of a circuit Magnitude (P.U.) 2.8 1 = Peak value (in P.U. of sym. RMS) 2.6 2 = Peak value (in P.U. of sym. Peak) = RMS value (in P.U. of sym. RMS) 2.2 = = 2.0 1.8 1.6 1.4 N 2 - 1.2Z 1.0 0.0 23 L..ILI I.L 1.0 2.0 3.0 4.0 Tiime (Cycles) 5.0 6.0 7.0 Fig. 4. Peak versus rms currents. breaker. Since these forces respond to instantaneous values of current, the momentary rating is dependent on the maximum peak current value. In addition to the mechanical stress, thermal stresses proportional to the current times the arc voltage (i.e., power input) exist which cause temperatures within the arc to approach 50 000 K. This energy tends to ionize particles, which then perpetuate the arc. The interrupting device must be able to deal with the heat being generated within the arc to achieve successful interruption. It is the rms value or heating effect which is most important here. Although the above is oversimplified, neglecting other important criteria, it will serve to allow us to look at these two important values (peak current and rms current). Fig. 4 shows the curve for peak current and rms current as a function of time for an X/R ratio of 15. Note that while the maximum asymmetrical rms value is 1.732 times the symmetrical rms value, the peak instantaneous value may reach double the symmetrical peak value. At approximately 0.5 cycles where the first real peak would occur in Fig. 4 the peak value is 1.81 times that of the symmetrical wave while the rms value is only 1.52 times that of the rms symmetrical value. A circuit breaker seeing an asymmetrical rms fault value of 1.52 would therefore have to withstand a peak value of 1.81. (High voltage circuit breakers have a momentary rating of 1.6 times symmetrical, or 1.88 times peak. This is 5 percent higher than shown in Fig. 4.) APPLICATION TO AC HIGH-VOLTAGE CIRCUIT BREAKERS Most ac high-voltage circuit breakers today are rated on the "symmetrical current basis of rating" which, simply stated, means that when the breaker is rated to interrupt the symmetrical value of fault current, and the X/R ratio is below a predetermined value, then the circuit breaker will be able to withstand and interrupt any asymmetrical current values which occur. This makes sizing a circuit breaker easy given that the X/R ratio is less than the predetermined value. The actual capability of circuit breakers is stated in ANSI C37.04 and C37.06 [7] and [8], and the test procedures are given in ANSI C37.09 [9]. The application procedures are given in ANSI C37.010 [10]. According to ANSI/IEEE C37.010-1979 [10], A circuit breaker having adequate symmetrical interruption capability will have adequate capability to meet all of the related short-circuit requirements unless there is a significant contribution from motor load or unless the X/R ratio is greater than approximately 15. Authorized licensed use limited to: CHILECTRA. Downloaded on May 03,2010 at 22:48:37 UTC from IEEE Xplore. Restrictions apply. IEEE TRANSACTIONS ON INDUJSTRY 846 TABLE I1I CIRCUIT BREAKER OPERATION TIMES Contact Rated Interrupting Time (cycles) Opening (cycles) (cycles) Time Capability Factor 2 3 5 8 1.0 1.5 2.5 3.5 1.5 2.0 3.0 4.0 1.3 1.2 1.1 1.0 Time Parting APPLICATIONS, VOL. IA-21 NO. 4, JULY/AUGUST 1985 While (6) gives the estimated capability factor, it should be understood that for each circuit breaker a certain capability factor is mandated by standards and that circuit breakers are tested to those stated values. These values were noted for each breaker in Table III. It would appear from the above that a circuit breaker with a large capability factor could be applied on systems with low X/R ratios at a symmetrical current higher than its rating. Current interruption, however, is a function of the transient recovery voltage (TRV) as well as the thermal energy in the arc. TRV is a function of di/dt which relates to the symmetrical component of the current, so the symmetrical value of the fault current is just as important as the asymmetrical value. Circuit breakers should therefore never be applied where the symmetrical fault current exceeds their symmetrical rating, no matter what the X/R ratio. For systems with larger X/R ratios, however, the capability factor can be put to good use. Equation (7) may be used to determine a multiplying factor for X/R ratios higher than 15 by which the symmetrical fault current must be multiplied. (The reciprocal of (7) could also be used as a derating factor for the breaker.) V I + 2 exp [ - 4xt/(X/R)] multiplying factor (7) S In ac high-voltage circuit breakers, the predetermined X/R ratio value has been established at 15. Thus, all ac highvoltage breakers must be able to withstand the 1.52 per-unit rms current and 1.81 per-unit peak current (2.55 times the symmetrical rms value) as shown in Fig. 4 at 0.5 cycles. As stated previously they are actually rated at 1.6 per-unit rms or 2.7 per-unit peak.) The interrupting rating is somewhat more difficult to assess since different circuit breakers will interrupt the fault at different times. As a result these circuit breakers are classified according to their rated interrupting times. Table III shows circuit breaker operating times according to ANSI/IEEE C37.04-1979 [7]. The rated interrupting time is the maximum permissible where interval between the energizing of the trip circuit at rated t contact parting time in cycles control voltage and the interruption of the main circuit on all X/R actual circuit X/R poles. A breaker should be rated to interrupt the amount of S factor. capability current present at the contact parting time. Contact parting time is determined by adding 1/2 cycle relay time to the A plot of (7) will correspond to the graphs shown in ANSI/ breaker opening time. The curves of Fig. 4 may be drawn for IEEE C37.010-1979 [10, fig. 10, p. 36]. The equation is not any X/R ratio using (3), (4), and (5). meant to imply greater accuracy than the curve it represents, but only greater convenience should the user wish to use some dc t in cycles 27rt/(X/R)] exp [ sort of computerized selection procedure for large distribution systems. (4) peak current dc + 1 So far we have discussed derating only with regard to the rms current- l2dc2+l . (5) rms values. Should we not have equal concern for the peak A five-cycle breaker with a standard three-cycle contact current values? Table IV shows the peak values of current parting time will be used as an example. As seen in Fig. 4 the along with the multiplying factors for rms current from (7). Note that under certain conditions the peak ratio multiplying rms current which the breaker must interrupt is 1.08 times the symmetrical value. This value occurs at the contact parting factor exceeds that of the rms by about 2 percent. Since the time of 3.0 cycles. The ability of a circuit breaker to interrupt actual momentary tested value of 1.6 discussed earlier exceeds the calculated value of 1.52 by 5 percent it would appear that a higher rms value of asymmetrical current than its symmetrithe multiplying factors provided by (7) would provide the cal value is called "capability factor." The breaker just necessary protection for peak currents as well as rms. discussed would need a capability factor of about 1.08. The to ANSI/IEEE C37.010-1979 [10], if the fault is According actual capability factor of this breaker is 1.1. Therefore a fivefrom generators through a) not more than fed predominantly cycle circuit breaker with a contact parting time of three cycles or b) a per-unit reactance external to the transformation one can interrupt 10 percent more asymmetrical rms current that is which less than 1.5 times the generator per-unit its rated symmetrical value. The approximate capability factor generator on a common system megavolt-ampere subtransient reactance for any circuit breaker may be obtained from (6) base, then one should use Figs. 8 and 9 from [10] for derating. These figures include the effect of ac decrement and have been (6) S = 1+2 exp[-4irt/(X/R)] determined by empirical methods. where The IEEE working group has determined that the standards S are slightly "pessimistic" as far as handling the dc component capability factor t is concerned, but "optimistic" as far as handling the ac contact parting time in cycles X/R 15. component is concerned. Combined, the results are quite = = Authorized licensed use limited to: CHILECTRA. Downloaded on May 03,2010 at 22:48:37 UTC from IEEE Xplore. Restrictions apply. 847 HARTMAN: UNDERSTANDING ASYMMETRY TABLE IV COMPARISON OF DERATING HIGH-VOLTAGE BREAKERS BY PEAK VERSUS DERATING BY RMS X/R 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 Peak ratio 1 1.006 1.011 1.016 1.020 1.024 1.028 1.031 1.034 1.037 1.039 1.041 1.044 1.046 1.048 1.049 -rms (by maximum asymmetry)Two cycle Three cycle Five cycle Eight cycle 0.964 0.978 0.991 1.004 1.015 1.026 1.036 1.046 1.055 1.064 1.072 1.079 1.087 1.093 1.100 1.106 0.977 0.992 1.006 1.019 1.032 1.044 1.056 1.067 1.077 1.087 1.097 1.106 1.114 1.123 1.131 1.138 0.980 0.992 1.003 1.015 1.027 1.038 1.049 1.060 1.071 1.082 1.092 1.102 1.112 1.121 1.130 1.139 1.034 1.042 1.051 1.060 1.069 1.078 1.087 1.097 1.107 1.116 1.126 1.135 1.145 1.154 1.163 1.172 Peak ratio: peak current in per-unit of peak current with X/R = 15. rms (by maximum asymmetry): derating factor by (7) [6-10] for each breaker interrupting time. TABLE V POWER FACTOR OF TEST CIRCUIT FOR MOLDED CASE BREAKERS Rated Interrupting Current Amperes Power Factor 10000 and less 10001 to 2000 Above 20000 0.45-0.50 0.25-0.30 0.15-0.20 TABLE VI CAPABILITIES OF MOLDED CASE CIRCUIT BREAKERS Rated Interrupting Current (amperes) X/R (rms) iaym lsym (peak) 10000 and less 10001 and 20000 Above 20000 1.7-2.0 3.2-3.9 4.9-6.6 1.03-1.04 1.13-1.18 1.25-1.33 1.16-1.21 1.37-1.44 1.53-1.62 Iaym (rms) is in per-unit of symmetrical rms. I8,y. (peak) is in per-unit of symmetrical peak. Using (3), (4), and (5) as before we can calculate the close. It should be stated, also, that long experience with asymmetrical currents shown in Table VI. For values of Iasym applying circuit breakers by these methods has seemed to in per-unit of symmetrical rms current, simply multiply by the square root of 2. These values are usually taken to be 1.7, 2.0, verify their adequacy. and 2.2, respectively, for the three breaker ratings. For system X/R ratios higher than those in Table VI, the multiplying LOW-VOLTAGE POWER CIRCUIT BREAKERS Low-voltage power circuit breakers are assumed to have a factor to use for modifying the calculated fault values is arrived at using (9) contact parting time of 1/2 cycle unless otherwise stated. This means that their momentary and interrupting ratings should be 1 + exp [ - 7r/(X/R)] multiplying factor = identical. An X/R ratio of 6.6 is also used rather than the 15 Iasym (peak) used for high-voltage breakers. Finally considering the characteristics of low-voltage breakers (both power and molded case) (see Table VI). (9) it has been decided that peak currents rather than rms currents will determine the interrupting capability. From (3) and (4), OTHER METHODS OF BREAKER RATINGS using a time of 0.5 cycles and an X/R ratio of 6.6, it can be Occasionally circuit breakers (especially older models) may seen that these breakers must interrupt a peak current of 1.62 be rated according to asymmetrical single-phase amperes or times that of the symmetrical peak (2.3 times that of the asymmetrical three-phase amperes. In the asymmetrical sinsymmetrical rms). For X/R ratios higher than 6.6 one may gle-phase case one may use (3) and (5) to find the nns current use (8) to modify the fault current prior to selecting a breaker and match this to the interrupting rating. In the asymmetrical three-phase case, (10) should be used and matched to the 1 + exp [-rl(XIR)] multiplying factor (8) interrupting rating. A convenient table to use for this purpose 1.62 is included in NEMA standard publication No. AB1-1975 [4, Equation 8 would correspond to table 3, ANSI/IEEE C37. 13- pt. 2, p. 121. 1981. Again, (8) should be not used for X/R ratios lower than 6.6. Iave (asym)- {{Il + 2 exp [- 4it/(X/R) MOLDED CASE CIRCUIT BREAKERS + 2 V11+ 1/2 exp [-47rt/(X/R)] } (10) Due to the lack of standards, the following procedures are suggested for applying molded case circuit breakers. t in cyles. Unless otherwise stated, molded case circuit breakers are APPLICATIONS TO OTHER DEVICES assumed to have contact parting times of 1/2 cycle. The rated X/R ratio, however, depends on the size of the breaker. Table Fuses will not be covered in this paper, but the point should V, taken from NEMA publication No. ABI-1975 141, shows be made that (3), (4), and (5) of this paper are much preferred the power factor of the test circuit under which each of these to the "up-over-down" method used on most fuse curves, the breakers must be tested. "up-over-down" method assumes an X/R for you. Authorized licensed use limited to: CHILECTRA. Downloaded on May 03,2010 at 22:48:37 UTC from IEEE Xplore. Restrictions apply. 848 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. IA-21, NO. 4, JULY/AUGUST 1985 Solid-state overcurrent protective devices usually operate on peak current and are thus prone to operate sooner than [1] expected for asymmetrical faults. Coordination by peak current value is sometimes helpful. A similar condition occurs when using adjustable magnetic-trip-only breakers for motor [2] protection. The National Electric Code Article 430, Sections [3] 52 and 152, prohibits magnetic-only trips to be set above 1300 [4] percent. It is not uncommon today for high-efficiency motors to have asymmetrical peak currents more than 20 times their [51 rated value. The result is sporadic "nuisance" tripping. [6] Many other applications can be found where asymmetrical currents play an important part in the engineering solution to a [7] problem. A sound understanding of the principle of asymme- [8] try will greatly enhance the ability of the engineer to find an acceptable solution. While not covered in this paper, an understanding of iron saturation is also essential in many of [9] these applications. [10] CONCLUSION A familiarization with the mechanics of asymmetry can be a valuable tool in the analyzation of disturbances on a power system. At times the asymmetry involved may become the deciding factor between breakers of different interrupting ratings with considerably varied price tags. In addition, a good visual understanding of the "phenomenon" of asymmetry makes one much more comfortable in responding to the problem. The traditional methods of calculating fault currents were shown to produce values very close to the actual maximum currents attained. Finally, in an age where computers are readily available to most practicing engineers the equations for circuit breaker derating may be programmed for convenience. This is particularly useful on modem large distribution systems where X/R ratios are high and copious numbers of interrupting devices are to be sized. REFERENCES H. W. Reichenstein and J. C. Gomez, "Relationship of X/R, I, and IRMs' to asymmetry in resistance/reactance circuits," presented at the IEEE/IAS conference, Mexico City, Mexico, 1983. T. E. Brown, Jr., Theory and Techniques of Circuit Interruption. Marcel Dekkar, Inc., 1984. R. E. Friedrich, Application of Power Circuit Breakers, an IEEE Tutorial Course. New York: IEEE, 1975. Molded Case Circuit Breakers, National Electrical Manufacturers Association Standard AB1-1975. Low- Voltage Power Circuit Breakers, National Electrical Manufacturers Association Standard SG3-1975. Low-VoltageACPower Circuit Breakers Used in Enclosures, ANSI Standard C37.13-1981. Rating StructureforAC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis, ANSI Standard C37.04-1979. Preferred Ratings and Related Required Capabilitiesfor AC HighVoltage Circuit Breakers Rated on a Symmetrical Current Basis, ANSI Standard C37.06-1979. Test Procedure for AC High- Voltage Circuit Breakers Rated on a Symmetrical Current Basis, ANSI Standard C37.09-1979. Application Guidefor AC High- Voltage Circuit Breakers Rated on a Symmetrical Current Basis, ANSI Standard C7.010-1979. Craig N. Hartman (S'78-M'80) received the B.S.E.E. degree from the University of Utah, Salt Lake City, in 1980. He joined the Westinghouse Electric Corporation, San Francisco, CA, as an Industrial Application Engineer in 1980. Since 1983 he has worked as a District Engineer for Westinghouse in Denver, CO, responsible for technical support of the corporation with reference to industrial business in that area. Mr. Hartman currently serves as the Editor of the IEEE Newsletter for Colorado, and he is a Registered Professional Engineer in the State of California. Authorized licensed use limited to: CHILECTRA. Downloaded on May 03,2010 at 22:48:37 UTC from IEEE Xplore. Restrictions apply.