3 97/157/NP Electrical installations for lighting and beaconing of aerodromes – Electronic lamp systems in series circuits – General safety requirements Contents Page Introduction...................................................................................................................................... 4 1 Scope ................................................................................................................................... 5 2 Normative references ............................................................................................................ 5 3 Terms and definitions ............................................................................................................ 6 4 Requirements ....................................................................................................................... 8 4.1 General ................................................................................................................................. 8 4.2 Environmental conditions ...................................................................................................... 8 4.3 Degree of protection provided by enclosures ........................................................................ 9 4.4 Electromagnetic compatibility (EMC) ..................................................................................... 9 4.5 Marking ................................................................................................................................. 9 4.6 Protection against electric shock ........................................................................................... 9 4.7 Interfaces ............................................................................................................................ 11 5 Testing ............................................................................................................................... 12 5.1 Testing documentation ........................................................................................................ 12 5.2 Assemblies with direct connection to the series circuit ........................................................ 12 5.3 Type tests ........................................................................................................................... 12 5.4 Routine tests....................................................................................................................... 12 4 97/157/NP Introduction With a few exceptions, aeronautical ground lighting is designed for series circuit technology. Such series circuits are operated with constant current. The series circuit input voltage of the unearthed primary circuit is tracked by a constant current regulator dependent of variations in the load. The properties and characteristics of such constant current regulators are laid down in IEC 61822. The maximum series circuit input voltage is limited to AC 5 000 V, tolerances included. Due to the structure of the series circuit, i.e. a series connection of all consumers, the usual protective organs for personal protection of an IT, TT or TN network cannot be applied. Aeronautical ground lighting rates among optical navigation systems and as such is subject to special requirements with respect to availability. Insulation faults in the series circuit are thus tolerated and do not lead to automatic shutdown of supply. In view of the above no work of any kind shall be performed on live series circuits without appropriate protective equipment according to IEC 61821. In practice, it is not always easy to assign rated voltages correctly to individual consumers and to recognize possible touch voltages in the series circuit. Here, the connections of the familiar network are often wrongly taken for granted, i.e. constant input voltage, consumers connected in parallel and a load-dependent current. In the usual network, the rate voltage for consumers and the maximum touch voltage are usually smaller than or equal to the mains input voltage. In a series circuit installation the series circuit input voltage is divided in proportion to the internal resistances of consumers via the series circuit. The rated voltage, i.e. the voltage between the input lines of consumers, is defined by the series circuit current that flows through the consumer and the input impedance of the consumer. Since input impedance depends on the design and the series circuit current is constant, the input voltage is always the same for the consumer. Due to current control in the series circuit the series circuit input voltage is controlled load-dependent and corresponds to the sum of all partial voltages in the series circuit. The internal consumer electronics is designed on the basis of the input voltage at the consumer. This is different for the maximum possible touch voltage against earth. Since one or more earth faults are tolerated during operation, the touch voltage against earth can assume any value up to the maximum series circuit input voltage depending on the location of the earth fault and the consumer in the series circuit. The dimensioning of the dielectric strength against earth potential shall therefore be oriented on the maximum series circuit input voltage. Such peculiarities of the series circuit have been taken into account in the requirements for new electronic lamp systems in this standard. Since only few of the established equipment for personal protection are effective in series circuit technology the protective measure “safety extra low voltage” is applied in this standard for the supply of electronic lamp systems. This measure is common practice and can resort to well-known and accepted methods. The introduction is especially favoured and made possible for the first time by lower power requirements and hence lower voltage of the illuminants. At present, electronic lamp systems normally consist of LEDs and their snubber circuit. New technologies are intended not to be excluded by this standard. 5 1 97/157/NP Scope This standard specifies protective provisions for the operation of electronic lamp systems powered by series circuits in aeronautical ground lighting. The protective provisions described here refer only to secondary supply systems for illuminants that are decoupled from the series circuit. This standard also takes account of special operational features of aeronautical ground lighting. It also takes account of the level of training and the requirements for maintenance procedures according to IEC 61821. The requirements and tests are intended to set a specification framework for system designers, users and maintenance personnel to ensure a safe and economic use of the systems in installations for beaconing of aerodromes. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. DIN EN 55022 (VDE 0878-22), Einrichtungen der Funkstöreigenschaften – Grenzwerte und Messverfahren Informationstechnik – DIN EN 60529 (VDE 0470-1), Schutzarten durch Gehäuse (IP-Code) DIN EN 61000-6-2 (VDE 0839-6-2), Elektromagnetische Verträglichkeit (EMV) – Teil 6-2: Fachgrundnormen – Störfestigkeit für Industriebereiche DIN EN 61140 (VDE 0140-1), Schutz gegen Anforderungen für Anlagen und Betriebsmittel elektrischen Schlag – Gemeinsame DIN EN 61558-2-4 (VDE 0570-2-4), Sicherheit von Transformatoren, Drosseln, Netzgeräten und dergleichen für Versorgungsspannungen bis 1 100 V – Teil 2-4: Besondere Anforderungen und Prüfungen an Trenntransformatoren und Netzgeräte, die Trenntransformatoren enthalten DIN EN 61558-2-6 (VDE 0570-2-6), Sicherheit von Transformatoren, Drosseln, Netzgeräten und dergleichen für Versorgungsspannungen bis 1 100 V – Teil 2-6: Besondere Anforderungen und Prüfungen an Sicherheitstransformatoren und Netzgeräte, die Sicherheitstransformatoren enthalten DIN EN 61821 (VDE 0161-103), Elektrische Anlagen für Beleuchtung und Befeuerung von Flugplätzen – Instandhaltung von Konstantstrom-Serienkreisen für Flugplatzbefeuerungsanlagen DIN EN 61822 (VDE 0161-100), Elektrische Anlagen für Beleuchtung und Befeuerung von Flugplätzen – Konstantstromregler DIN EN 61823 (VDE 0161-104), Elektrische Anlagen für Beleuchtung und Befeuerung von Flugplätzen – AGL-Serienkreistransformatoren IEC 60050-195, International Electrotechnical Vocabulary – Part 195: Earthing and protection against electric shock 6 97/157/NP IEC 60050-826, International Electrotechnical Vocabulary – Part 826: Electrical installations IEC 60050-851, International Electrotechnical Vocabulary – Part 851: Electric welding IEC 60417-2, Graphical symbols for use on equipment – Part 2: Symbol originals IEC 61000-6-4, Electromagnetic compatibility (EMC) – Part 6-4: Generic standards – Emission standard for industrial environments IEC/TS 61201, Use of conventional touch voltage limits - Application guide IEC 61558-1, Safety of power transformers, power supplies, reactors and similar products – Part 1: General requirements and tests IEC/CISPR 11, Industrial, scientific and medical equipment – Radio-frequency disturbance characteristics – Limits and methods of measurement 3 Terms and definitions 3.1 assembly self-contained, closed functional unit forming an electronic lamp system together with other assemblies 3.2 equipment assembly operated as a consumer connected to the energy supply 3.3 basic protection protection against electric shock under fault-free conditions 3.4 basic insulation insulation of hazardous live parts providing basic protection NOTE The term “basic insulation” does not include insulation used exclusively for functional purposes. 3.5 electrically skilled person person with relevant education and experience to enable him or her to perceive risks and to avoid hazards which electricity can create Elektrofachkraft ist, wer aufgrund seiner fachlichen Ausbildung, Kenntnisse und Erfahrungen sowie Kenntnis der einschlägigen Normen die ihm übertragenen Arbeiten beurteilen und mögliche Gefahren erkennen kann. NOTE 1 Several years of experience/work in the relevant field of activity can be taken into account to evaluate the technical education. NOTE 2 For the use in aeronautical ground lighting with series circuit technology relevant electrotechnical knowledge must be available about direct and indirect risks of this technology. Since this technology is not part of the basic contents of a general electrotechnical education, the education and examination of knowledge must be provided by the airport operator or his representative and be part of the recurring safety briefing. 7 97/157/NP 3.6 electrically instructed person person adequately advised or supervised by electrically skilled persons to enable him or her to perceive risks and to avoid hazards which electricity can create 3.7 fault protection protection against electric shock under single-fault conditions 3.8 extra-low voltage ELV (abbreviation) voltage not exceeding the relevant voltage limit specified in IEC 61201 3.9 communication unit subsystem and its components for data exchange with an external remote station 3.10 ordinary person a person who is neither a skilled person nor an instructed person [IEV 195-04-03] 3.11 lighting system all components of the power supply unit and the lighting unit 3.12 lighting unit all components used to generate light, adjust the luminous intensity, control functions and reproduce colours 3.13 illuminant light emitting component of the lighting unit 3.14 optical unit all components used to guide the light produced by the illuminants 3.15 interface electrical, optical or mechanical separation between subsystems with defined properties to maintain given functions 3.16 SELV system electrical system in which the voltage cannot exceed ELV: – under normal conditions – and under single-fault conditions, including earth faults in other circuits NOTE SELV is the abbreviation for safety extra low voltage. [IEV 826-12-31] 8 97/157/NP 3.17 SELV equipment SELV assembly connected to a SELV energy supply as a user in a SELV system 3.18 (electrically) protective separation separation of one electric circuit from another by means of: – double insulation or – basic insulation and electrically protective screening or – reinforced insulation 3.19 safety extra-low voltage SELV (abbreviation) [IEV 851-15-08] AC voltage the r.m.s. value of which does not exceed 50 V or ripple-free DC voltage the value of which does not exceed 120 V, between conductors, or between any conductor and reference earth, in an electric circuit which has galvanic separation from the supplying electric power system by such means as a separate-winding transformer [IEC 61558-1, definition 3.7.16 MOD] NOTE 1 Maximum voltage lower than 50 V AC or 120 V ripple-free DC may be specified in particular requirements, especially when direct contact with live parts is allowed. NOTE 2 The voltage limit should not be exceeded at any load between full load and no-load when the source is a safety isolating transformer. NOTE 3 Ripple-free qualifies conventionally an r.m.s. ripple voltage not more than 10 % of the DC component; the maximum peak value does not exceed 140 V for a nominal 120 V ripple-free DC system and 70 V for a nominal 60 V ripple-free DC system. 3.20 power supply unit all components for the supply and transfer of energy used to operate a lighting unit in a series circuit 4 Requirements 4.1 General Electronic lamp systems for use in aeronautical ground lighting shall be designed for the power supply in a 6,6 A series circuit. The maximum ratings of the series circuit supply are given by the constant current regulators according to IEC 61822. If the lamp systems are designed for other current or voltage ranges, such information shall be given by the manufacturer on the type plate. 4.2 Environmental conditions Electronic lamp systems shall be designed for continuous indoor operation without derating, under the following environmental conditions: – temperature range from −25 °C to +55 °C; – relative humidity from 10 % to 100 %; – altitude from sea-level to 1 000 m; 9 4.3 97/157/NP Degree of protection provided by enclosures The degree of protection against contact with conducting parts or the ingress of solid objects and liquids shall be indicated by the IP coding according to IEC 60529. When installed, enclosures of individual assemblies shall comply with the requirements in normal operation at aerodromes. 4.4 Electromagnetic compatibility (EMC) 4.4.1 Limits of electromagnetic emission Lighting systems shall comply with the requirements given in the EMC generic standard IEC 61000-6-4, Emission standard for industrial environments. The limits of electromagnetic emission shall comply with IEC/CISPR 11, class B. 4.4.2 Limits of immunity Lighting systems shall comply with the requirements given in the generic standard for industrial environments IEC 61000-6-2. The immunity limits and methods of measurement of IEC/CISPR 22 shall be complied with. 4.5 Marking Each assembly shall be marked with a name plate. The name plate shall be captively attached to a visible part of the enclosure. If the enclosure is too small for a name plate to be attached the assembly shall be marked with an unambiguous type designation. The name plate shall contain the following information: – Unambiguous type designation of the manufacturer – Name of the manufacturer of the assembly – Nominal input voltage and nominal input current – Nominal output voltage and nominal output current – Maximum output of a current supply unit – Marking of the assembly as class III (SELV) with symbol original 5180 of IEC 60417-2 (Roman III within rhombus) The SELV marking shall be attached in a way that it is clearly visible for maintenance personnel where it is in the normal installation position. If variants of the installation position are allowed the SELV marking shall be attached in more than one place to ensure visibility, if applicable. 4.6 Protection against electric shock 4.6.1 Basic requirements Hazardous live parts shall not be accessible and accessible conductive parts shall not be hazardous live – neither in normal use without fault, nor – under single fault conditions. 4.6.2 Protective measure to be applied A SELV system shall be provided as a protective measure on the secondary side of the series circuit. The protective mechanisms of the SELV system shall not be lost if a single fault occurs. 10 97/157/NP For this purpose – limitation of voltage in a circuit (the SELV system) and – protective-separation of the SELV system from all circuits other than SELV and PELV and – simple-separation of the SELV system from other SELV systems, from PELV systems and from earth shall be provided. Intentional connection of parts to a protective conductor or to an earth conductor according to IEC 61140 is not permitted. In locations where protective screening is used for the purpose of protective separation the protective screen shall be separated from each adjacent circuit by basic insulation intended for the highest voltage present. If internal circuits produce a voltage value higher than the value that is allowed for SELV this part of the circuit shall be separated safely. If such parts with a higher voltage value are accessible when repair work is done on the open enclosure, the working instructions shall contain respective warnings. All external interfaces of the SELV system shall not exceed the SELV level. This applies for loaded and unloaded interfaces. Operational earthing of active parts of the SELV system is not allowed. The maximum SELV shall not exceed the following values: – 50 V AC for sinusoidal AC voltages in the 15 to 100 Hz range, – 71 V peak value for non-sinusoidal AC voltages and – 120 V DC for direct voltages with a maximum harmonic content of 10 % of the direct voltage effective value. 4.6.3 Protective separation from the primary series circuit The power supply unit of the electronic lamp systems with the SELV system shall provide a galvanic, safe separation from the primary part of the series circuit. The power supply unit can be used in series circuits of maximum 30 kVA and 6,6 A series circuit rated current. The partial voltage in the series circuit occurring at the input of a single power supply unit through its power input at series circuit nominal current results in the rated voltage of the power supply unit and shall not exceed 1 000 V. The dielectric strength shall comply with the maximum series circuit voltage. Protective separation between the primary and the secondary winding of a transformer shall be achieved according to IEC 61140 by means of: – basic insulation and supplementary insulation, each rated for the highest voltage present, i.e. double insulation, or – reinforced insulation rated for the highest voltage present, or – protective screening with the protective screen being separated from each adjacent circuit by basic insulation rated for the adjacent circuit voltage, or – a combination of these provisions. If conductors of the separated circuit are contained together with conductors of other circuits in a multi-conductor cable or in another grouping of conductors, they shall be insulated, 11 97/157/NP individually or collectively, for the highest voltage present, so that double insulation is achieved. SELV and non-SELV circuits shall not be carried in one common cable. If any component is connected between the separated circuits, that component shall comply with the requirements for protective impedance devices according to IEC 61140. 4.6.4 Assemblies in the SELV system If assemblies in the SELV system are connected to the power supply unit by means of an external interface they shall be designed as class III equipment according to IEC 61140. Electric interfaces shall be designed for at least 50 V AC and 120 V DC. Assemblies of class III equipment shall have no equipment for the connection to a protective conductor. In no case provisions for the connection of active parts to earth potential shall exist. An earthing connection of the enclosure of an assembly may be provided if earthing is necessary for other functional reasons than personal protection. NOTE An earth connection may be necessary e.g. to integrate a fire enclosure into a lightning protection system. 4.6.5 Use of class III equipment Class III equipment for use in beaconing systems shall be used only in SELV or PELV systems. 4.7 Interfaces 4.7.1 Supply unit The supply of the lighting system is made by the series circuit. All subsystems having a direct galvanic connection to the primary series circuit shall comply with IEC 61823 (AGL series transformers). If the supply of a series circuit or another voltage supply is intended with a nominal voltage of up to 1 000 V AC, the dielectric strength can be determined according to IEC 61558-2-4. 4.7.2 Connections Connections between SELV assemblies shall be unambiguously identifiable in the mated and unmated condition as SELV connection by the maintenance personnel. It shall not be possible to connect SELV equipment to non-SELV equipment via connections. Connectors shall be marked as a SELV component with a permanently visible graphic symbol 5180 according to IEC 60417-2 (Roman III inside rhombus) The marking shall be long lasting and visible all around. The live side shall be equipped with the socket. Consumers shall be equipped with the plug. 12 5 Testing 5.1 Testing documentation 97/157/NP The manufacturer shall give a detailed test instruction for each assembly. The test instruction shall contain each component test and the sequence of component tests. For each component test the exact tolerances shall be specified for successful testing. If the component test is required by a standard the relevant standard and the section of the standard shall be indicated. For each component test the test arrangement including the environmental conditions shall be specified for the test. The manufacturer shall provide the following test information to the operator of the units upon request: – type and sequence of all component tests of the type and routine test as far as these are relevant for electrical safety and mechanical strength; – tolerances for such type tests; – results of the type test for the component tests. 5.2 Assemblies with direct connection to the series circuit All applicable tests of dielectric and mechanical strength shall be carried out on power supply units having a galvanic connection to the series circuit on one side according to IEC 61823. The applicable tests for safety isolating transformers according to IEC 61558-2-6 shall be carried out. 5.3 Type tests All tests according to 5.2 shall be carried out as type tests. The test has been passed if all electrical and mechanical requirements have been fulfilled. The test shall be documented with all single results and a clear description of the structural condition of units. If an assembly is modified in a way that this has an effect on the safety or basic function the type test shall be repeated. 5.4 Routine tests After production the manufacturer shall submit each assembly to a visual inspection, a nondestructive dielectric test according to the applicable parts of IEC 61558-2-6 and a functional test. The functional test shall contain the basic functions and compliance with the maximum permitted output voltage for supply units. The manufacturer shall document the type and scope of tests in the test instructions.