Power Quality Impact of Distributed Generation: Effect on Steady State Voltage Regulation Reginald Comfort Manuel Gonzalez Arshad Mansoor Phil Barker & Tom Short Ashok Sundaram Reliant Energy EPRI PEAC EPRI 942 Corridor Park Blvd. Knoxville, TN 37932 3412 Hillview Avenue Palo Alto, California 94304 th 1111 Louisiana, 24 Floor Room 2452, Houston, TX 77002-5231 ABSTRACT With the advent of deregulation, distributed generation will play an increasing role in electric distribution systems. Various new types of Distributed Generation (DG), such as micro-turbines and fuel cells, are now being developed in addition to the more traditional solar and wind power. A common belief among developers is that DR will improve power quality, and this potential for better quality is cited as one of the value attributes of installing distributed generators. In some cases distributed generation and storage are being promoted as an answer to the premium-quality power requirements of high technology or sensitive end-use customers. Whether or not this value-attribute of DG is valid will depend on the specific technologies, site conditions and potential interaction with the existing electric power system. The objective of this paper is to provide a technical assessment of the impact of distributed generation technologies on the power quality of the power distribution system. Power quality is a broad term covering a wide range of operating parameters including both steady state and dynamic conditions. The full range of power quality conditions are described in IEEE Std. 1159-1995 Recommended Practice for Monitoring Electric Power Quality. This paper focuses on steady-state voltage regulation impacts of DG and is the first of several papers covering the various power quality impacts of DG. The guidelines provided in this paper will help utility engineers evaluate the impact of distributed generation on voltage regulation and identify methods to mitigate problems that arise. The paper also makes recommendations for voltage trip thresholds to be used for DG interconnection that will help reduce the susceptibility of DG to nuisance trips but still provide utility system protection against sustained overvoltage. Introduction Distributed generation will affect steady-state voltage for end users. Voltage regulation can be improved or degraded by the addition of DG. When DG improves voltage regulation, this is generally referred to as “voltage support,” commonly cited as one of the benefits of DG. However, voltage support is by no means guaranteed, and in some cases DG will actually degrade voltage regulation. This paper discusses the impacts of DG on distribution system voltage regulation and the conditions under which voltage is degraded. Voltage regulation variations are defined as: • Long-Duration Variations: Rms deviations at power frequencies for longer than one minute. [IEEE Std. 1159-1995] [1]. Long-duration variations can be caused by: - Improper voltage regulation - Broken neutral Utility-initiated voltage reduction Sudden change of load or unusual load on a distribution circuit Figure 1 shows an example of a long-duration undervoltage scenario. 24-Hour Minimum/Average/Maximum Voltage 100 Voltage (%) 97 94 Undervoltage 91 88 85 7:12 PM 12:12 AM 5:12 AM 10:12 AM 3:12 PM Figure 1. Example of a Long-Duration Undervoltage [2] ANSI/IEEE standard C84.1 specifies the preferred voltage levels for electric power systems. Most utilities have adopted the C84.1 standard as a minimum requirement, and some have more stringent requirements imposed by their respective public utilities commission. The C84.1 standard has two ranges: range A and range B service voltages [3]. These are defined as follows: • Range A – Proper range considered to be within limits. • Range B – Infrequent excursion – “The occurrence of service voltages outside of these limits should be infrequent” and “When they occur, corrective measures shall be undertaken within a reasonable time to improve voltages to meet Range A requirements.” The standard gives ranges at two locations, the service voltage (“voltage at the point where the electrical system of the supplier and the electrical system of the user are connected”) and utilization voltage (voltage at utilization equipment). The C84 ranges are shown in Figure 2. Voltage (120-V Base) 104 108 112 116 120 124 128 Utilization Voltage Service Voltage: 120- to 600-V Systems Range A Service Voltage: Systems 600 V or Greater Utilization Voltage Service Voltage: 120- to 600-V Systems Range B Service Voltage: Systems 600 V or Greater Nominal System Voltage Figure 2 ANSI C84.1 Voltage Ranges. [3] The Shaded Portions on the Lower End of the Utilization Voltages do not Apply for Circuits Supplying Lighting Load. The Shaded Portion at the Top of Range A Utilization Voltage Does Not Apply to 120 to 600-V Systems Long-duration under and overvoltages measured during a national power quality study [4] are shown in Table 1. Long-duration variations are less common than many other power quality disturbances including voltage sags and momentary interruptions. Long-duration undervoltages are more common than overvoltages. Table 1 Average Annual Number of Long-Duration Overvoltages and Undervoltages Per Site Recorded in the NPL Power Quality Study [4] Sustained overvoltage V>110% for t>10 sec 0.3 Sustained undervoltage V<87% for t>10 sec 1.0 Regulation in Distribution Systems Maintaining proper voltage regulation of the distribution system is a key operating objective and responsibility of the electric utility company. Voltage conditions that are out of the normal operating range can lead to poor operation of the power system and customer loads, damage to utility equipment and customer loads, and in extreme cases can even be a safety hazard. Generally speaking, utilities strive to meet ANSI C84.1 Range A service voltage standards, while realizing that some customers some of the time won’t quite be in this range. On a 120-volt base, the standard requires that the service entrance voltage be between 114 volts and 126 volts. To those unfamiliar with power systems this may seem like a broad range that should easily be achievable. However, given the lengths in distribution circuits, and the significant variations in load that occur, this is not easy to achieve for all customers. It requires careful coordination and placement of voltage regulating equipment, diligence in monitoring load growth on the system and in performing periodic load flow studies to assess voltage conditions. Figure 3 shows the distribution of percentage range of daily voltage changes measured in the EPRI DPQ study. Most undergo less than a 3% change, but a sizeable portion has swings of more then 7%. Distribution of Daily Range of RMS Voltage 18% 100% 16% Frequency 12% 60% 10% 8% 40% 6% 4% Cumulative Frequency 80% 14% 20% 2% 19% 18% 17% 16% 15% 14% 13% 12% 11% 10% 9% 8% 7% 6% 5% 4% 3% 2% 1% 0% 0% 0% Daily RMS Volatge Range (% of Site Average Voltage) Figure 3 DPQ Results for Regulation Voltage Ranges. The Plot Shows the Percent Daily Change in Voltage Occurring Due to Demand Cycles on the Power System [2] For radial power systems, voltage regulation practices are based on a single source of power (the substation) and the power taking only one path from the substation to all loads on the system. This condition leads to the assumption that the voltage will always drop on the primary feeder as the distance from the substation increases. The only exception to this assumption is when there is too much reactive compensation (this will cause a rise in voltage as one moves towards a capacitor bank). Utilities are careful to avoid this condition, so it is reasonable to assume that the voltage drops on the primary feeder for most applications. The condition of radial flow also implies that the voltage (on a per-unit basis) will drop across each distribution transformer and secondary service (see Figure 4). DG introduction onto the radial distribution system will impact both of these basic assumptions used for voltage regulation. 130 128 Voltage, V with base=120 V 126 ANSI Range A Upper Limit 124 Primary feeder drop 122 120 118 Transformer drop 116 Secondary drop 114 ANSI Range A Lower Limit 112 110 0 1 2 3 4 5 6 7 8 Distance from the substation, miles Figure 4 Example Voltage Profile on a Distribution Circuit For network systems, voltage regulation is usually done entirely with load-tap changing (LTC) transformers at substations, and there is no supplementary voltage regulation equipment on the primary feeders or on the LV network side. Such equipment is not usually necessary because networks, being in an urban environment, have relatively short primary feeder lengths, and the secondary grid is very stiff electrically and tightly interconnected in a manner that allows little voltage drop. The amount of voltage drop from the substation to the service entrance of a typical network customer is far less on a per-unit basis than on a typical suburban or rural radial distribution circuit. The LTC device in the substation alone is usually enough to compensate for any voltage drops. In general, urban networks are good examples of systems that are thermally limited – this means that as the load is increased, the transformers and cables reach their thermal limits long before voltage drop becomes a major issue. In contrast, longer radial distribution systems are usually voltage drop limited – meaning that the voltage drop becomes too excessive well before any thermal limits are reached. In general, urban low-voltage networks, since they are thermally limited, will be less sensitive than radial distribution circuits with respect to the impact of DG on voltage regulation. This means it takes a lot of injected power to significantly alter the voltage on a network. It is important to recognize that while low voltage urban networks are less sensitive with respect to DG’s impact on voltage regulation, that they are actually more complex to deal with and more sensitive than radial distribution systems in regards to other issues such as protection and fault coordination. This has to do with the directional relaying employed to protect network systems. The relaying and protection issue is not discussed in this paper, but it should be recognized as a serious complication and will be discussed in follow-up papers. Distribution utilities have several ways to control steady-state voltage. The most popular regulation methods include: • Substation load tap-changing transformers (LTCs) • Substation feeder regulators • Line regulators • Switched capacitors As stated before, most networks use only LTCs. However radial circuits in suburban and rural areas may use any of the above devices. For radial systems, most utilities use LTCs to regulate the substation bus and supplementary feeder regulators and/or switched capacitor banks where needed. On relatively short feeders, utilities may employ only an LTC transformer and switched capacitors. A few utilities use only switched capacitors for regulation. Voltage regulators are autotransformers with automatically adjusting taps. A common regulator range is ±10% with 32 steps (5/8% each). The tap changer controls are often adjusted to control the voltage with line-drop compensation. This compensates for downstream voltage drop due to the impedance of the line. Using line-drop compensation, it is possible to hold the voltage nearly constant at a point on the feeder several miles downstream from the regulator. During heavy load, the voltage at the regulator output terminals is boosted the most, and during light load it is boosted the least. The amount of boost is directly proportional to the current on the line and offsets the voltage drop between the terminals of the regulator and the point where the voltage is to be regulated (this point is called the constant voltage point or load center). The line drop compensator uses an internal model of the impedance of the distribution line to determine how much voltage boost is required for a given current level (see Figure 5). The current and voltage on the line are measured with a CT and PT at the regulator. The user can set the R and X values in the line drop compensator to adjust the compensation based on the type and size of wire (its impedance characteristics) and the presumed load distribution on the feeder. The set voltage on the regulator is the value it will hold at the constant voltage point (load center). I CT R PT V/pt I/ct X (R+jX)(I/ct) R Regulation poin X Voltage Regulating Relay Figure 5 Line Drop Compensator Circuit In selecting the line-drop compensator settings, one practice is to attempt to hold the voltage constant at the physical center of the line (or center of the regulated region). For example, on a 5-mile line regulated entirely from the substation, the voltage could be held constant at about the 2.5-mile point. In determining the settings it is often assumed that the load is uniformly distributed along the line and uniform wire size is used throughout the feeder section being regulated. To satisfy the objective of holding the voltage constant at the center of the section being regulated under these conditions, analysis shows that the R and X settings need to be set to 3/8th of the total line resistance and reactance of the section being regulated. Some utilities add a bit of additional compensation to account for distribution transformer and secondary voltage drops. The set voltage and compensation levels are also evaluated from the perspective of the “first” and “last” customer. The first customer (closest to the source from a voltage-drop perspective) is evaluated such that they will not see high voltage at any time, and the last customer (farthest from the source from a voltage-drop perspective) is checked for low voltage. If the settings can meet these criteria and provide nearly constant voltage at the center of the regulated region, then they should work effectively and be considered good practice. Load tap changing transformers (LTC) use the same type of controller with line-drop compensation as do auto-transformer step regulators, but they often regulate an entire substation bus that serves many distribution feeders. The LTC must therefore regulate several lines at once, so the characteristics of each line need to be considered in the settings. It is not usually possible to pick the ideal settings for all feeders served from a common bus. For this reason, many utilities apply compromise settings for the line drop compensation that amount to using far less compensation than would be the case for any single feeder application. In fact, some utilities use none at all (R=0 and X=0). When no line drop compensation is applied it means that the constant voltage point is at the regulator location – which in this case would be the substation bus. The use of no line-drop compensation leads to greater fluctuations in voltage for customers at the end of the regulation zone. Another complication in adjusting regulators is that the load may not be uniformly distributed on the feeder. This means that regulator settings when based on uniformly distributed loads may cause a mismatch between desired and actual voltage profile results. Load may be biased towards the front or rear of the feeder depending on the situation. When load is at the rear, more line-drop compensation is needed. When it is towards the front, less is needed. Capacitor banks and distributed generation are current sources that confuse voltage regulators by making the load less uniformly distributed and perhaps even causing reverse flows. Regulator operation should be coordinated with these devices when they are significant in size relative to the system loads. Regulator controls also have two other settings that help prevent an excessive number of tap changes: Bandwidth: Voltage regulator controls monitor the difference between the measured voltage and the voltage setpoint. When the difference exceeds the bandwidth, a tap change is initiated. As a rule of thumb, the minimum bandwidth should be 2 times the step size (1.25% for 5/8% steps). Time delay: After a tap-change operation, further changes are permitted until the time delay has elapsed. Typical time delays are 30 to 60 seconds. Summary of DG Impacts DG can improve regulation or cause problems with regulation. The main ways that DG can cause regulation problems are: • Low voltage due to DG just downstream of a regulator with line-drop compensation: Linedrop compensation is the technique commonly applied by LTC transformer controllers and linevoltage regulators to control the voltage on the distribution system based on the line current. Under heavy load, a generator just downstream of the generator will reduce the observed load on the feeder (so the regulator will not boost the voltage as much). This leads to lower voltage downstream of the regulator. • High voltage due to DG: High voltages may be caused by reverse power flow. Under light load for a location where the primary voltage is already high, the voltage rise can be enough to push the voltage above ANSI limits. This can even happen for a small DG located on the secondary because of the voltage drop along the service drop, the secondary wiring, and the distribution transformer. • Interaction with regulating equipment: Another area of concern is with interaction of regulation equipment and DG. If the DG has varying output, it may change the system voltage or current flows enough to cause a regulator tap change or an operation of a switched capacitor. Likewise, a distributed generator that has feedback to control voltage may interact negatively to the utility regulation equipment. There may be undesirable cycling of regulation devices and noticeable power quality impacts under such conditions. DG Operating Ranges per Standards Table 2 shows the normal operating range of photovoltaics per the IEEE 929-2000 interface standard [5]. Note that the high-end limit of 132 V is well above the ANSI range B upper limit of 127 V for the service and utilization voltage. Since DG can cause a voltage rise because it injects real power, this is inconsistent with the ANSI range B upper limits and could lead to long-duration overvoltages caused by DG. The IEEE P1547 interconnection standard that is currently in draft form that applies to all distributed generation was initially based on IEEE 929 but has evolved slightly to have different trip levels and tripping times as shown in Table 3. Qualitatively, the proposed settings of IEEE P1547 are still quite similar to IEEE 929 and both standards allow sustained DG operation outside of the ANSI C84.1 limits. Within the industry, this topic has been an area of active discussion as to the pro’s and con’s of this approach. In subsequent sections of this paper, the voltage regulation issues related to DG are discussed, and recommended alternative settings for IEEE 929 and 1547 are proposed. Table 2 Standard Trip Thresholds (120-V nominal) for DG Operations per the IEEE 929 Photovoltaic Interface Guideline RMS Voltage Trip Time* V<60 6 cycles 60≤V<106 120 cycles 106≤V≤132 Normal Operation 132<V<165 120 cycles 165≤V 2 cycles Table 3 Proposed voltage trip settings per IEEE P1547-D7. Note the IEEE P1547 document is a proposed standard under development and these settings could change pending committee review Voltage Range (% of base Note 1 voltage) Clearing Time (seconds) Note 2 V<50 0.16 50≤V<88 2 88≤V<110 Operation Allowed (no trip) 110≤V<120 1 V 120 0.16 Note 1: Base voltages are the nominal voltages stated in ANSI C84.1 Note 2: DR≤30 kW Maximum Clearing Time. DR>30 kW, Default Clearing Time or area EPS operator may specify different voltage settings or trip times to accommodate area EPS system requirements Voltage “Following” versus Voltage Regulating DG Units DG is usually operated in a voltage-following mode. This means that the DG makes no intentional attempt to regulate the voltage on the power system. With this mode DG simply supplies real power at nearly constant power factor and the voltage on the feeder changes according to the effects of the DG power injection – in other words, the DG does not attempt to force a given voltage by using reactive power control. The concept of voltage following is a source of confusion within the industry since many people have incorrectly interpreted its meaning to be that DG will “follow” the existing utility system voltage and will not change the voltage on the feeder in any way. However, the basic physics of injecting power into any power system guarentee that the voltage will change as a result of current flow through the system impedance. These changes will be superimposed (add to or subtract from depending on phase angle of the injected currents) on the existing utility system voltage that is controlled by utility equipment such as LTC’s and feeder regulators. In a voltage following mode, as the real power output of the DG increases, the voltage will increase! Too much power injected into the power system can cause higher than normal voltage. If relays are set to allow the unit to continue to operate into the grid with voltage outside of normal voltage limits (as is the case in the proposed P1547), then sustained overvoltage can occur. When DG is operated in a voltage-regulating mode it attempts to hold the voltage at a constant set point. Voltage regulation can be accomplished by adjusting the reactive component of the generator output either to raise or lower the voltage to offset any rise due to the real power component. This is done with rotating synchronous generators by adjusting the field excitation level. Leading reactive current (high excitation) will increase the voltage and lagging current (low excitation) will decrease the voltage. As long as the generator has sufficient capability to support the reactive and real power requirements imposed by this type of duty, it can help regulate the voltage on the power system. This type of operation, while done in some cases, is mostly avoided in grid parallel applications because it is usually not desirable to give this responsibility to independently owned generation as it requires considerable coordination with upstream equipment and the utility company. Also, many DG are too small (do not have sufficient reactive capability) to regulate the distribution system effectively. Finally, it can be difficult to coordinate operation of the independently owned DG with utility feeder regulation devices in a suitable manner that may not severely penalize the generator real power capacity. Note that the voltageregulation mode of operation is preferred in stand-alone grid independent DG applications where the generator supplies power to all of the load and is needed to perform the voltage regulation function. Voltage Regulator Interaction There can be considerable interaction between DG units and utility system voltage regulation equipment. Figure 6 shows a scenario where a DG just downstream of a regulator can cause low voltage on the end of the circuit due to the use of line-drop compensation on the regulator. The power injected by the generator will cause the regulator to not raise voltage as much as it should. To determine if the DG will cause a significant impact on the feeder voltage, the size and location of the DG, the voltage regulator settings, and impedance characteristics of the line must be considered. The low voltage is exacerbated if there is reverse power flow. Under this condition, the regulator can ratchet all the way to the lowest tap, which would cause very low voltage downstream. Regulator FEEDER (QGRI)HHGHU Injected Power G Peak Load (no DG) Peak Load (with DG) 9ROWDJH CVP ANSI Range A Lower Limit Regulator End of Feeder Figure 6 DG Just Downstream of a Regulator that Leads to Low Voltage at the End of the Feeder A simple screening criteria to avoid low voltage on circuits with line-drop compensation is that there may be problems if the size of the generator exceeds 10% of the load at the regulator and the DG is located closer to the regulator than the load center. When these conditions are met, then further study may be warranted to investigate the decrease in voltage on the feeder and determine if mitigation is required. If problems are found, there are several options. One option for minor undervoltages is to reduce the linedrop compensator settings and raise the voltage setpoint slightly. This moves the regulator constant voltage point closer to the regulator and reduces the impact of the DG. The key is the location of the constant voltage point (also called the load center – the fictitious point on the feeder where voltage is held constant). DGs upstream of this point will lower the voltage downstream of this point, while DGs downstream of the constant voltage point will support rather than lower the voltage. A more extreme option for larger DGs is to remove (turn-off) the line-drop compensation on the regulator. Generally, the voltage setpoint will have to be significantly raised to provide adequate voltage on the circuit at the end of the regulation zone. If this is done, a check would have to be made to make sure high voltages don’t occur on the feeder at light load due to the higher set voltage. If the problems are due to reverse power flow, advanced regulator controllers are available to change operating mode during reverse power flow to prevent the regulator from dropping to the lowest tap. For example, the tap change can be blocked or programmed to revert back to the neutral position if power reverses. Other options include moving either the generator or the regulator so that the regulator is downstream of the generator. Sometimes there is no way to avoid installation of new regulation equipment if the DG is especially large relative to feeder capacity. Another consideration with regulators (and switched capacitor banks) is unwanted interaction with DG (especially fluctuating sources). The main way to avoid this is by widening the regulator bandwidth setting and, in some situations, reducing line drop compensation settings. Increasing the time delay can also help prevent excessive regulator tap changes depending on the rate of change of the DG energy source. Wind and photovoltaic energy sources that impact the feeder load by 10% or more at voltage regulators or switched capacitors are the most likely causes of these types of interactions. Wind and PV energy sources experience wide fluctuations in output on a repeating basis due to partial cloud cover or wind variations. These fluctuations may occur over many seconds or minutes depending on conditions. DG-Caused High Voltages There are also concerns with DG causing high voltages on distribution circuits because of reverse power flow. It is possible to estimate the effect of a generator by using the standard voltage drop equations with reverse power flow. The voltage drop along a feeder due to a load is approximately equal to: Vdrop ≈ IR·R+IX·X where, Vdrop, voltage drop along the feeder R, line resistance, ohms X, line reactance, ohms IR, line current due to real power flow, amps (negative for a generator injecting power) IX, line current due to reactive power flow, amps (negative for a capacitor) The voltage at the generator can be estimated by taking the highest prefault voltage and adding the voltage rise due to the generator from the equation above. Note that this approximation is no substitute for a proper load flow. It does not fully model the response of the load to the change in voltage, and it does not consider regulator response. It is useful for a first attempt at estimating whether the voltage rise due to the generator might be a problem. The DG which is exporting mainly real power will cause voltage to go up most where X/R ratios are low. The real power portion will cause the largest voltage rise when the line resistance is high. If the DG is injecting vars like a capacitor or there are fixed capacitors nearby, the voltage rise is even larger. Under the right circumstances, this voltage rise is beneficial (voltage support), but if too much rise occurs or it occurs on a section of feeder where the voltage was already near the upper ANSI limit before the DG started, then a high voltage problem may be created (see Figure 7). SUBSTATION (QGRI)HHGHU FEEDER Injected Power G 9ROWDJH ANSI Range A Upper Limit ANSI Range A Lower Limit Substation After DG Before DG End of Feeder 'LVWDQFH Figure 7 Voltage profile on feeder before and after addition of large DG. High voltage may occur at the end due to the voltage rise caused by the DG injected power If voltage rise can be a problem, there are several options. One would be to limit the size of the generator to below the level necessary to cause problems. Another would be to relocate the DG to a more suitable location on the distribution circuit or build an express feeder to the generator. On the DG side, the generator could be operated to absorb more reactive power (by removing local capacitors or operating a synchronous generator or line-commutated inverter at reduced power factor). This is the opposite of what is normally done and reduces the T&D support value of DG. Reducing the power factor of the generator causes voltage drop due to the reactive component of the generator. This approach may increase losses on the feeder, however, and result in an effective reduction in available capacity on the feeder. A utility company option would be to reduce the resistance of the lines and transformers from the substation bus to the DG site – a costly scenario. This would be done by using larger conductors on lines and cables and specifying lower copper losses on transformers. Another utility-side option is to add regulation equipment (capacitors or regulators) to counteract the voltage rise from the distributed generator. Of course, the least costly utility option could be reducing the voltage level setting on the existing regulation equipment – that is, if this can be done without risking low voltage on the feeder during periods when the DG is off and/or there is heavy load. While these are all technically feasible option the question remains who is going to pay for the technical study and implementation for changing distribution system practices to accommodate customer owned DG. Selecting DG Trip Thresholds That Work in the Real World Sometimes DG units will unneccessarily trip offline due to short-term excursions of voltage that are slightly outside of the steady state operating limits defined by ANSI C84.1. Temporary high voltages on the distribution system can occur for a variety of reasons including the loss of a single large load or block of loads when a fuse, switch or breaker interrupts power flow. Also, the switching of a large power factor correction capacitor can result in a sudden increase in voltage. These events frequently lead to mild overvoltages up to about 10% above nominal that persist until utility voltage regulation equipment can respond to correct the situation. Utility voltage regulators usually employ time delays of anywhere from 10-90 seconds. Short term mild overvoltages of this nature are not a threat to loads, but they will cause nuisance trips of DG that strictly use the ANSI C84.1 limits as the acceptable operating window and trip offline very fast for anything outside the range. To prevent nuisance DG trips, the IEEE 929 PV standard and various utility DG interface requirements have employed voltage trip settings that allow DG to continue operating indefinitely even when the voltage is slightly outside of the ANSI limits. For example, IEEE 929 allows PV inverters to operate at up to 132 volts (+10% above nominal) before they are required to trip. Draft-standard IEEE P1547-D7 that is still in development also allows for a +10% limit. The upper ANSI range B limit is 127 volts (+6% nominal) so both IEEE 929 and IEEE P1547-D7 allow the DG to function considerably higher than the ANSI range B limit. This approach certainly will reduce the incidence of nuisance trips, however, it also creates the potential of sustained high voltage above ANSI range B limits being allowed to occur as a result of DG power injection. In some cases this could be a threat to loads and power system equipment - potentially causing damage and perhaps even posing safety issues. It is recommended that the industry consider an alternative approach that provides suitable protection against sustained overvoltage but will still allow DG to ride-through mild overvoltages without nuisance trips. This approach essentially means that DG should have an acceptable continuous operating window that is consistent with ANSI C84.1 and should use a long time delay for mild overvoltages. Table 4 shows recommended voltage trip settings for DG that should offer good protection against nuisance trips and sustained overvoltages. This table essentially follows the settings in the IEEE P1547-D7 draft standard, but includes an extra row of settings for voltages ranging from 106% to 110% of nominal with a time delay of 180 seconds. It also allows a continuous (no trip) operating range of only 88% to 106% that is a bit narrower than the current draft standard. Table 4 Alternative Voltage Trip Settings Recommended for IEEE P1547 Voltage Range (% of base Note 1 voltage) Clearing Time (seconds) Note 2 V<50 0.16 50≤V<88 2 88≤V<106 Operation Allowed (no trip) 106≤V<110 180 110≤V<120 1 V 120 0.16 Note 1: Base voltages are the nominal voltages stated in ANSI C84.1 Note 2: DR≤30 kW Maximum Clearing Time. DR>30 kW, Default Clearing Time or area EPS operator may specify different voltage settings or trip times to accommodate area EPS system requirements An instructive example of an overvoltage event and the DG nuisance trip response to it recently occurred at a utility distribution system. In this case a 5 MW combustion turbine was operating in parallel with the utility system at an industrial load that is supplied by a 12 kV distribution circuit. The DG unit is located 3 miles from the substation. The DG trip settings were in accordance with Texas PUC Rule 25.212 where the first trip threshold is 126 volts with a 30 second time delay and the second trip threshold is 132 volts with a 10 cycle time delay. In this case the generator unit was operating normally until the voltage at the DG site suddenly increased to approximately 126 volts (on a 120 volt base) in the first stage. The first stage of the voltage rise shown in Figure 8 was a result of the switching-on of a large bank of substation capacitors used for transmission support and was not directly related to the DG since it was not exporting net power to the feeder at that time (although by offsetting load on the feeder due to this customer it did help raise the voltage). Figure 8 Voltage rise; 7.281 kV, then 7.559 kV for 28 sec., then 7.809 kV for 14 sec. The DG interconnection breaker tripped after the 30 second time delay had elapsed and since this also caused the loss of customer load the voltage rose to 130V (on a 120V base) before the voltage on the feeder was corrected by the substation LTC. This event is very instructive as it shows that the time delay setting of the DG overvoltage relay had not been coordinated with the feeder voltage regulation equipment. If the time delay had been set to 15 seconds longer than the LTC’s time delay then that would have provided sufficient time for the LTC to lower feeder voltage and the generator would not have tripped. Note that the present draft 7 IEEE P1547-D7 settings would have worked well for this case, however, as stated before, they would also allow continuous operation at an elevated voltage should that condition arise. The preferred and technically better approach is the settings recommended in Table 4. These provide good mitigation of false trips due to temporary overvoltages up to a few minutes duration but will protect against a sustained overvoltage outside the ANSI C84.1 standard. References [1] IEEE Std. 1159-1995, IEEE Recommended Practice for Monitoring Electric Power Quality. [2] An Assessment of Distribution System Power Quality: Volume 2: Statistical Summary Report, EPRI TR-106294-V2, Palo Alto, California, May 1996. [3] ANSI C84.1-1989, American National Standard for Electric Power Systems and Equipment - Voltage Ratings (60Hz). [4] D. S. Dorr, T. M. Gruzs, M. B. Hughes, R. E. Jurewicz, G. Dang, and J. McClaine, “Interpreting Recent Power Quality Surveys to Define the Electrical Environment,” IEEE Transactions on Industry Applications, vol. IA-33, No. 6, Nov/Dec 1997. [5] IEEE Std. 929-2000, Recommended Practice for Utility Interface of Photovoltaic (PV) Systems.