Technical Data Low voltage regulation system LVRSys™ 0 0 0 0 0 0 0 Power range 55 kVA – 400 kVA Regulation range: ±6 % / ±10 % Phase spacing: 1.5 % / 2.5 % Overall efficiency 99.7 % Phase-independent regulation Voltage tolerance band parametrisable No grid interference 1. Application The low voltage regulation system LVRSys™ represents a cost-effective alternative for grid expansion. The economic use is recommended in all low voltage grids where short-circuit power is sufficient, but have voltage maintenance problems. Voltage maintenance problems can occur locally (in single lines) or at the level of the entire low voltage grid. LVRSys™ can be used with flexibility as line regulator or as direct regulator on the local grid station. Voltage profile, with and without LVRSys™ Regulation of bus bar voltage Regulation of the line voltage The direct regulation of the bus bar via LVRSys™ is comparable with the function of an adjustable local grid transformer. A pre-condition for this application is the uniform occurrence of voltage maintenance over the entire low voltage grid. This occurs if the distribution of decentralised "feeders" is homogeneous. If single lines are affected by voltage maintenance problems, it is economically to use LVRSys™ as line regulator (linear regulator). The powers to be regulated are low and hence the use of the system is costefficient. A classical application example would be a grid branch with multiple photovoltaic extensions (PV). g We take care of it. 2. Functioning The principle of the LVRSys™ control is based on a linear regulator. By coupling and uncoupling two transformers with selected transfer ratios, it is possible to regulate the output voltage in 9 steps. The regulation range can be selected from ±6 % (phase spacing 1.5 %) to ±10 % (phase spacing 2.5 %). The transformers are controlled using thyristors. These solid state electronic components are characterised by robustness, easy maintenance and short-circuit resistance. The stages of the transformers are determined by setting the switching of the thyristors in the following fashion. Step Transformer 1.5%/2.5% Transformer 4.5%/7.5% -6 % / -10 % -1.5 % / -2.5 % -4.5 % / -7.5 % -4.5 % / -7.5 % 0%/0% -4.5 % / -7.5 % -3 % / -5 % +1.5 % / +2.5 % -4.5 % / -7.5 % -1.5 % / -2.5 % -1.5 % / -2.5 % 0%/0% 0%/0% 0%/0% 0%/0% +1.5 % / +2.5 % +1.5 % / +2.5 % 0%/0% +3 % / +5 % -1.5 % / -2.5 % +4.5 % / +7.5 % +4.5 % / +7.5 % 0%/0% +4.5 % / +7.5 % +6 % / +10 % +1.5 % / +2.5 % +4.5 % / +7.5 % The control signals for the thyristors are generated by driver circuits which switch the thyristors intelligently. Taking into consideration the magnetic flow in the transformers, these can be switched to generate smooth current without voltage dips or over-voltages. 4,5% transformer 1,5% transformer +4,5% -1,5% = +3% controller Example of 3 % voltage reduction Generating voltage steps by use of thyristors 3. LVRSys™ application locations LVRSys™ can be used in various ways. Applications range from "regulation street distribution boxes" up to regulation entire local grids. LVRSys™ as line regulator LVRSys™ as local grid regulator LVRSys™ as regulator of an outgoing circuit Page 2 The "balancing" of the three phase voltage additionally improves grid quality, as shown by the following power consumption of a line regulator. Unregulated input voltage LVRSys™ Regulated output voltage LVRSys™ 4. Technical Data Operating temperature -40 °C to 45 °C Maximum permitted air temperature in the switch cabinet 70 °C Altitude of the installation (NN) < 2000 m Safety class IP 54 Rated voltage 400 V/230 V ±20 % (L-L/LE) Rated current 80 A (55 kVA system) 160 A (110 kVA system) 250 A (175 kVA system) 315 A (250 kVA system) 580 A (400 kVA system) Rated frequency 50 Hz Efficiency 99.7 % Standard regulation range ±6 % of Extended regulation range ±10 % of Step number/Distance 6 % 9 / 1.5 % Step number/Distance 10 % 9 / 2.5 % Switch cabinet dimensions W/D/H 120 cm/40 cm/135 cm (55 kVA system ±6 %) 120 cm/40 cm/135 cm (55 kVA system ±10 %) 120 cm/40 cm/135 cm (110 kVA system ±6 %) 140 cm/50 cm/145 cm (110 kVA system ±10 %) 140 cm/50 cm/145 cm (175 kVA system ±6 %) 140 cm/50 cm/145 cm (175 kVA system ±10 %) 160 cm/50 cm/155 cm (250 kVA system ±6 %) 160 cm/50 cm/155 cm (250 kVA system ±10 %) 160 cm/50 cm/155 cm (400 kVA system ±6 %) Page 3 We take care of it. Weight switch cabinet 200 kg (55 kVA system ±6 %) 240 kg (55 kVA system ±10 %) 230 kg (110 kVA system ±6 %) 280 kg (110 kVA system ±10 %) 320 kg (175 kVA system ±6 %) 400 kg (175 kVA system ±10 %) 430 kg (250 kVA system ±6 %) 550 kg (250 kVA system ±10 %) 540 kg (400 kVA system ±6 %) Dimensions of ground base W/D/H 120 cm / 40 cm / 100 cm (55 kVA system ± 6 %) 120 cm / 40 cm / 100 cm (55 kVA system ±10 %) 120 cm / 40 cm / 100 cm (110 kVA system ±6 %) 140 cm / 50 cm / 100 cm (110 kVA system ±10 %) 140 cm / 50 cm / 100 cm (175 kVA system ±6 %) 140 cm / 50 cm / 100 cm (175 kVA system ±10 %) 160 cm / 50 cm / 100 cm (250 kVA system ±6 %) 160 cm / 50 cm / 100 cm (250 kVA system ±10 %) 160 cm / 50 cm / 100 cm (400 kVA system ±6 %) Weight of ground base 260 kg (55 kVA system ±6 %) 260 kg (55 kVA system ±10 %) 260 kg (110 kVA system ±6 %) 280 kg (110 kVA system ±10 %) 280 kg (175 kVA system ±6 %) 280 kg (175 kVA system ±10 %) 300 kg (250 kVA system ±6 %) 300 kg (250 kVA system ±10 %) 300 kg (400 kVA system ±6 %) Max. power consumption of secondary electronics 300 mA (230 V) Cooling - passive (convection via switch cabinet housing) - active (redundant ventilation system) (depending on the application conditions) Short-circuit impedance approx. 0.3% Maximum phasing duration 30 ms Noise emissions < 30 dB(A) EMC stability DIN EN 61000-6-1 EMC interference emission DIN EN 61000-6-3 Assembly instructions DIN EN 61439-1/5 Low voltage directive 2014/35/EU Page 4 5. Installation LVRSys™ is suitable for inside as well as outside mounting. Cable routing takes place from beneath the switch cabinets. If mounted outside, a base is needed. The base consists of light concrete and is delivered with the system. The low voltage cables are connected through box terminals (35 mm² to 300 mm²). The PEN conductor is connected via cable lug and rivet nut to the PEN bus. Installation & connection schematic LVRSys™ to 175kVA Installation & connection schematic LVRSys™ to 110 kV Installation & connection schematic LVRSys™ to 400kVA Page 5 We take care of it. 6. Operation Regulation parameters Temperature display 0 Reference value (voltage value, 3- phase) 0 Tolerance band + (upper limit value of the tolerance area) 0 Tolerance band - (lower limit value of the tolerance area) 0 Time ratio (selection of time characteristics) 0 Delay (delay of characteristics) 0 Synchronous phasing (phases are stepped synchronously) 0 Grid impedance (current values are included in regulation) Temperature display Update & CSV file output The measurement data (CSV) and the log book can be retrieved with the help of an USB stick. One can also update the firmware with the help of an USB stick. Tolerance area Drag indicator function The "drag pointer" displays the 15-minutes average values for the following measurement parameters: 0 0 0 0 Maximum voltage values Ph1-Ph3 CSV- file output Maximum current values Ph1-Ph3 Grid impedance Maximum output values Ph1-Ph3 Minimum/maximum temperatures T1 output level aluminium plate T2 control housing T3 switch cabinet air The regulator measures the output voltage and phases it in case of over-/under-voltage in the tolerance bands. When an additional parametrising of the "grid impedance" takes place, a new voltage regulation value is created. By measuring the grid current and the parametrised grid impedance one can calculate the voltage value in "grid branch" exactly. The regulation can be therefore optimised without communication devices. Drag indicator function Parametrising grid impedance Page 6 7. LVRSys™ product family 7.1 Standard 7.2 Individually Scope of delivery: 0 By-pass switch according to customer specifications 0 Concrete base (Outdoor- application) 0 Steel base (Indoor- application) 0 By-pass switch with output-specific characteristics System Dimensions/Model 55 kVA NH 000 separator 110 kVA NH 00 separator 175 kVA NH 1 separator 250 kVA NH 2 switch-disconnector fuse 400 kVA NH 3 switch-disconnector fuse (NH- size) 0 0 0 0 0 Current measurement output side Current measurement input side Voltage measurement input side Additional outflows/inflows (bus system) Integrated Power Quality Analysis (PQI-DA smart) input side 0 Integrated Power Quality Analysis (PQI-DA smart) output side 0 2 x 3- phase voltage taps for external measurement devices 0 Regulator with voltage measurement on the output side LVRSys™ 55 kVA 6 % / 10 % – 110 kVA 6 % LVRSys™ 250 kVA 6 % / 10 % - 400 kVA 6% PQI-DA smart LVRSys™ 110 kVA 10 % - 175 kVA 6 % / 10 % Page 7 We take care of it. A. Eberle GmbH & Co. KG Frankenstraße 160 D-90461 Nuremberg Tel.: +49 (0) 911 / 62 81 08 0 Fax: +49 (0) 911 / 62 81 08 99 Email: info@a-eberle.de http://www.a-eberle.de Edition of: 19/11/2014 Copyright 2014 A. Eberle GmbH & Co. KG Subject to change without prior notice.