R805 SERIES
SOLID STATE RELAYS ( SSR'S )
•
•
240 Vac up to 600 Vac models
10 Amps up to 75 Amps models
DESCRIPTION
The Viconics R805 series solid state relays are designed for silent switching of electric resistive loads typically found in electric
heating applications or any other application with where zero-cross firing is acceptable.
•
•
•
•
•
UL/cUL recognized
2 years warranty
Direct bond copper substrate
Improved lead frame design
LED input status indicator
SPECIFICATIONS
Model
number
Nominal
AC line
voltage
Nominal
current
rating
( Amps )
1 cycle
surge
peak
( Amps )
Peak
maximum
repetitive
voltage
Maximum
output
voltage
drop
Maximum
off-state
leakage
Operating
voltage
range
( Vac )
I square t
Rating
(60Hz, ½ cycle)
R805-211
R805-321
R805-641
R805-691
240
660
660
660
10
25
50
75
150
450
750
1000
600
1200
1200
1200
1.35 Volts
1.35 Volts
1.35 Volts
1.30 Volts
5 mA
5 mA
5 mA
5 mA
24 - 280
48 - 660
48 - 660
48 - 660
416
937
2458
5000
Operating conditions:
Input to output Voltage Isolation:
Control voltage input:
Drop out voltage:
Capacitance input to output:
Turn on time:
Turn off time:
-20°C to 80°C ( - 4°F to 176°F ) 0 % to 95 % R.H. non-condensing
4000 Vrms
4 - 32 Vdc
1.0 Vdc
8 pF
0.5 cycle 8.33ms
0.5 cycle 8.33ms
HIGH VOLTAGE WIRING
General cautions:
•
Adequate heatsinking, including consideration of air temperature and flow, is essential to the proper operation of a solid state
relay. Refer to proper thermal dissipation graphic for each model.
•
High voltages are present on the terminals of these devices. Please read all the instruction in this manual carefully.
•
Have the wiring done by a qualified a skilled professional.
•
High voltage can be fatal.
•
All wiring must conform to national electrical code regulations.
•
The instrument must be wired before applying power.
•
For maximum protection, fuse circuits with semi conductor fuses.
Note:
These instruments have undergone rigorous tests and verifications prior to shipment to ensure proper and reliable operation in the
field. However, like other such products, they are subject to failure. It is therefore the responsibility of the installer / user / electrical
panel designer to incorporate safety features and devices ( such as relays, flow switch, thermal protections, etc….. ) to protect the
entire system from catastrophic failure.
Viconics Electronics Inc. 9245, Langelier Blvd, St-Leonard, Quebec, Canada H1P 3K9
www.viconics.com
sales@viconics.com
LIT-R805X-E02