CONTROLLER SECTION
TM
• Wall Controllers
CONTROLLERS
LINE UP
• Sensors
• Zone Cards, Zone Modules & Optional Zone Kit
• Optional Control Boards
• CCI CPI & CVI
CONTROLLER
MATRIX
WALL CONTROLLER
COMPARISON
• Wall Controllers for Split Ducted Units
• Wall Controllers for Package Units
• An overview of all available ActronAir Wall Controllers with
quick reference to functions / features of each of the controllers
• LM - Series Wall Controller Features
WALL CONTROLLER
FEATURES
• C - Series Wall Controller Features
• Zone Controller Features
• Zone Sensor Features
• LM - Series Controllers for SRA Models
CONTROLLER
CONFIGURATIONS
• LM - Series Controllers for ESP Plus Models
• LM - Series Controllers for Ultima Models
• C - Series Controllers for Tri-Capacity Models
• C - Series Controllers for SCA & PCA Models
• LM - Series Wall Controller to Standard Indoor PCB
• LM - Series Models with Optional 4 - or - 8 Zone Controller
MAXIMUM
CABLE LENGTHS
• LM - Series Wall Controller to Indoor PCB Ultima Models
• LM - Series Ultima Models with 8-Zone Controller
• C - Series Tri-Capacity Models
• C - Series SCA & PCA Models with Third Party 240V Zone Barrels
• LM - Series Control with Optional 4Z-24V Kit
• LM - Series 8-Zone Wall Controller with 8-Zone Module
• LM - Series Controller with Optional AMZ Card
INSTALLATION
WIRING DIAGRAMS
• C - Series Single Stage Controller with Optional CZ Zone Control
• C - Series 2-Stage Controller with Optional CZ Zone Control
• C - Series Tri-Capacity System with C7-4 Wall Controller
• LM - Series Wall Controller Temperature Sensor Wiring
• C7-4 Wall Controller Temperature Sensor Wiring
CONTROLLER
FAULT / FUNCTION
DISPLAY CODES
• Residential Models - SRA / SRE / SRD
• Commercial Models - SCA / PCA / PCG / PKY
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
CONTROLLER SECTION 120312
THIS PAGE WAS INTENTIONALLY LEFT BLANK
®
ACTRONAIR CONTROLLERS LINE UP
WALL CONTROLLERS
Features:
Model: LM7
Part No. LM7
(7-Day 8-Zone)
ON
OFF
LOW
COOL
• 7-Day Programmable Controller with
2 Events/Day
• 24-Hr ON/OFF Timer
• Auto, Heat & Cool Modes
• Auto/Continuous Indoor Fan Operation
• 3 Speed Indoor Fan Setting
•
•
•
•
•
•
•
AUTO
HEAT / COOL
FAN
PROGRAM
8-Zone Capability
Self Diagnosis
Filter Change Light Indicator
Last Zone Enable/Disable Feature
Hot Start Feature
Manual Control Inputs
Remote ON/OFF Capability
(e.g. Home/Building Automation)
TIMER
SET TEMP
SELECT
REPEAT /
EXIT
Options:
• Remote Temperature Sensor
• Secondary Wall Controller with Mimic Logic
Features:
Model: LM7-D
Part No. LM7-D
(ESP 7-Day 8-Zone)
OFF
LOW
COOL
AUTO
HEAT / COOL
FAN
PROGRAM
TIMER
SET TEMP
SELECT
REPEAT /
EXIT
SRD Models:
• 3 Speed Indoor Fan Setting
• Auto/Continuous Indoor Fan Operation
SRV Models:
• 3 Speed + ESP Indoor Fan Setting
• Auto/Continuous/ESP Indoor Fan Operation
CONTROL INFORMATION
ON
• 7-Day Programmable Controller with
2 Events/Day
• 24-Hr ON/OFF Timer
• Auto, Heat & Cool Modes
• 8-Zone Capability
• Self Diagnosis
• Filter Change Light Indicator
• Last Zone Enable/Disable Feature
• Hot Start Feature
• Manual Control Inputs
• Remote ON/OFF Capability
(e.g. Home/Building Automation)
SRM Models:
• 3 Speed + ESP Indoor Fan Setting
• Auto/Continuous/ESP ID Fan Operation
• ON/OFF Switch Capability up to 8 Zones
• Check Room Temperature up to 8 Zones
Options:
• Remote Temperature Sensor
• Secondary Wall Controller with Mimic Logic
Features:
Model: LM24
Part No. LM24
(24-Hr 8-Zone)
•
•
•
•
24-Hr ON/OFF Timer
Auto, Heat & Cool Modes
Auto/Continuous Indoor Fan Operation
3 Speed Indoor Fan Setting
ON
OFF
MED
COOL
CONT
• 8-Zone Capability
• Self Diagnosis
•
•
•
•
•
Filter Change Light Indicator
Last Zone Enable/Disable Feature
Hot Start Feature
Manual Control Inputs
Remote ON/OFF Capability
(e.g. Home/Building Automation)
AUTO
HEAT / COOL
FAN
TIMER
SET
SELECT
TEMP
DISPLAY
Options:
• Remote Temperature Sensor
• Secondary Wall Controller with Mimic Logic
Model: AM-ZC
Part No. AM-ZC
(Ultima Zone Controller)
C
ZONE
COOL
ESP AUTO
HEAT
Features:
•
•
•
•
•
Individual Zone Temperature Setting
Set Point Display
Actual Room Temperature Display
On Board Temperature Sensor
Zone / Room Temperature Averaging
• ESP Auto Mode
• Zone Open Mode
• BackLight LCD display
OFF
ZONE CONTROL
SET
TEMP
ROOM
TEMP
MODE
ON/OFF
R
®
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2010 Actron Engineering Pty. Ltd.
®
Controller Line Up P1 111014
®
ACTRONAIR CONTROLLERS LINE UP
WALL CONTROLLERS
Features:
Model: AM24-H
Part No. AM24-H
(24-Hr Cool Only)
ON
OFF
ON OFF ROOM
CONT HIGH MID LOW COOL HOME AWAY RUN TIMER FILTER
FAN
HOME / AWAY
CONTROL
•
•
•
•
•
•
24-Hr ON/OFF Timer
Cool Mode Operation
Auto/Continuous Indoor Fan Operation
Control Calibrated Indoor Fan speeds
Auto-Restart After Power Failure
Home & Away Setback Modes Capability
•
•
•
•
Self Diagnosis
Filter Change Light Indicator
In-Built Random Start Timer
Set Temperature Limit Adjustments
•
•
•
•
Self Diagnosis
Filter Change Light Indicator
In-Built Random Start Timer
Set Temperature Limit Adjustments
•
•
•
•
•
2 Speed Indoor Fan Setting
4-Zone Capability
Temperature Setback & After Hours Timer
Hot Start Feature
Filter Change Light Indicator
TIMER
SET
TEMP
Options:
• Remote Temperature Sensor
• Secondary Wall Controller with Mimic Logic
Model: AM24-HH
CONTROL INFORMATION
Part No. AM24-HH
(24-Hr Home & Away)
ON
OFF
ON OFF ROOM
CONT HIGH MID LOW COOL AUTO HEAT AWAY RUN TIMER FILTER
FAN
AUTO
HEAT/COOL
CONTROL
Features:
•
•
•
•
•
•
24-Hr ON/OFF Timer
Auto, Heat & Cool Modes
Auto/Continuous Indoor Fan Operation
Control Calibrated Indoor Fan speeds
Auto-Restart After Power Failure
Home & Away Setback Modes Capability
TIMER
SET
TEMP
HOME
Options:
AWAY
• Remote Temperature Sensor
• Secondary Wall Controller with Mimic Logic
Features:
Model: C7-4
Part No. C7-4
(7-Day Commercial)
AM
SET BACK EVENT 1
PM
o C TIME CLOCK ON OFF
2
ON
MON TUE WED THU FRI SAT SUN TIMER FILTER AH
CONT HIGH LOW
AUTO HEAT COOL RUN STAGE ROOM
FAN
CONTROL
AUTO
HEAT/COOL
SET
TEMP
DISPLAY
TIME CLOCK
PROGRAM
TIMER
OFF
• 7-Day Programmable Controller with
2 Events/Day
• 24-Hr ON/OFF Timer
• 3 Stage Cooling / 3 Stage Heating Control
• Auto, Heat & Cool Modes
• Auto/Continuous Indoor Fan Operation
REPEAT
CANCEL
RESTORE
EXIT
1
2
3
4
Options:
• Two Remote Temperature Sensors
R
®
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2010 Actron Engineering Pty. Ltd.
®
Controller Line Up P2 100727
®
ACTRONAIR CONTROLLERS LINE UP
SENSORS
Model: AM-ZS
Part No. AM-ZS
Ultima Zone Sensor
(Optional)
Features:
• Maintains Room / Zone Temperature by using Wall Controller Set Point
Temperature as it’s Target Temperature
• Constantly Relays Information to the Ultima Module and Zone Barrels Air Damper
• Regulate Cooling / Heating Airflow to Achieve Desired Room / Zone Temperature
Dimensions:
• Dimensions (H x W x D): 75 x 32 x 28 (Including RJ45 Socket)
Connections:
• RJ45 Socket
Part No. AERSN
Remote Sensor
(Optional)
Features:
CONTROL INFORMATION
Model: AERSN
• Senses Room / Zone Temperature
• Temperature Readings Averaging when coupled with Wall Controller
Dimensions:
• Dimensions (H x W x D): 75 x 32 x 24 (Including Terminal Block)
sor
Sen
Connections:
• 2-Way Terminal Block
Model: AERSS
Part No. AERSS
Duct Bead Sensor
(Optional)
Features:
• Senses Air Temperature flowing through Ductwork
• Easy to Install
• Double Insulated Lead Wires
R
®
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2010 Actron Engineering Pty. Ltd.
®
Controller Line Up P3 100727
®
ACTRONAIR CONTROLLERS LINE UP
ZONE CARDS ZONE MODULES & OPTIONAL ZONE KIT
Model: 4Z-24V
Features:
Part No. 4Z-24V
24VAC 4-Zone Module (Optional)
ZONE 1
ZONE 2
EARTH
NEUT ACT
RLY
ZONE 3
Z1
Z2
Z3
ZONE 4
Features:
Part No. AMZ
230VAC 4-Zone Module (Optional)
CONTROL INFORMATION
EARTH
NEUT
NC
NO
ZONE 2
ACT
RLY
NC
NO
ZONE 3
Z1
Z2
Z3
NEUT
NO
NEUT
NEUT
NEUT
NC
Control up to 4-Zones Switching
Supports 24VAC ActronAir Integrated Zone Barrel Motor (RJ45 Plug Connection)
Easy to Install
Optional Last Zone Enable / Disable Feature
Option to Assign Sensor
Includes 20VA, 230VAC to 24VAC “Plug-In” Transformer
Z4
Model: AMZ
ZONE 1
•
•
•
•
•
•
NC
NO
ZONE 4
•
•
•
•
•
Control up to 4-Zones Switching
Supports 230VAC Third Party Zone Barrel Motor (Hardwired Connection)
Easy to Install
Optional Last Zone Enable / Disable Feature
Option to Assign Sensor
Z4
Model: 8Z-24V
Part No. 8Z-24V
24VAC 8-Zone Module (Optional)
Features:
•
•
•
•
•
•
Control up to 8-Zones Switching
Supports 24VAC ActronAir Integrated Zone Barrel Motor (RJ45 Plug Connection)
Easy to Install Zone Module
Optional Last Zone Enable / Disable Feature
Option to Assign Sensor
Supplied with 20m Data and Main Cable Looms
Model: 8Z-VAV
Part No. 8Z-VAV
ULTIMA 8-ZONE MODULE
(Factory Supplied & Fitted)
Features:
Model: CZ
Features:
Part No. CZ
230V 4-Zone Kit
(Optional)
WARNING
240 VOLTS
• Control up to 8-Zones VAV Modulation
• Supports 24VAC ActronAir Integrated Zone Barrel Motor (RJ45 Plug Connection)
• Option to Use Zone Sensor and Zone Controller or Combination
of Both to Control each Zone
• Factory Supplied & Fitted to SRM Ultima Models
•
•
•
•
Control up to 4-Zones Switching
Supports 230VAC Third Party Zone Barrel Motor
Easy to Install Zone Kit
Option to Assign Sensor
ISOLATE POWER BEFORE
REMOVING COVER
R
®
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2010 Actron Engineering Pty. Ltd.
®
Controller Line Up P4 100727
®
ACTRONAIR CONTROLLERS LINE UP
OPTIONAL CONTROL BOARDS
Features:
Model: D4FD
Part No. 2040-006-K
Fault Detection Board
(Optional)
• Up to Two Compressors Run Current Monitoring
• Up to Two 230VAC Compressor Call Signal Monitoring
• Up to Two 230VAC HP/LP Signal Monitoring
• Voltage Free Relay for Compressor Run Signal Output
• Voltage Free Relay for HP/LP Trip Signal Output
• Voltage Free Relay for Compressor Trip Signal Output
• 6 LED to Indicate Status of “Run” or “HP/LP” Trip or “Compressor” Trip
• Remote Reset Signal Input or Local Push Button for Resetting
• Dip Switch for Setting “Auto” or “Manual” Reset, 1 or 2 Stage Unit
• Interlaced 2-Stage or Separate 2-Stage
Model: D4STG2
Part No. 2020-009
2 / 3 Stage Boost Heat Board (Optional)
Features:
• 230VAC Interlaced 2-Stage Compressor Output
• 230VAC Boost Heat Output (Used as Stage-3 Heating)
• Enable and Disable Control Input
• One LED to Indicate Operation
CCH
E
CCH
NEU
RUN
Part No. 3PS5-001-K
3-Phase Soft Starter
(Optional)
N2132
Model: SS9
DANGER - HIGH VOLTAGE
Part No. 2035-004-K
1-Phase Soft Starter
(Optional)
Model: RPW-FSA
Part No. 2055-015
3-Phase Sequence Protection Relay
(Optional)
15
L2
CONTROL INFORMATION
Model: 3PS5
Features:
•
•
•
•
•
•
•
•
•
•
3-Phase Soft Start of Compressor (< 45A Start Current)
3Phase Rotation and Phase Lost Protection
LED Indication for Operation Status
By Pass Contactor not Required
Built-In Anti-Cycle Protection Timer
Low Mains Voltage Starting Protection
Lock-Rotor Starting Protection
Over-Current / Under-Current Protection
Crankcase Heater Output
Continuously Monitor Compressor Current Start & Run Operation
to Protect Compressor
Features:
•
•
•
•
•
•
•
•
•
1-Phase Soft Start of Compressor (< 45A Start Current)
LED Indication for Operation Status & Fault Codes
By Pass Contactor not Required
Built-In Anti-Cycle Protection Timer
Random Start Delay
Low Mains Voltage Starting Protection
Lock-Rotor Starting Protection
Over-Current / Under-Current Protection
Continuously Monitor Compressor Current Start & Run Operation
to Protect Compressor
• Plastic Enclosed - DIN Mount
Features:
• Monitor 3-Phase Supply Voltages for Incorrect Phase Sequence
• Detects Phase Loss when One Phase Drops to 70%
or Less in relation to other Phases
• Fast Response Time
• LED for Status Indication
RPW - SF
R
®
16
18
L3
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2010 Actron Engineering Pty. Ltd.
®
Controller Line Up P5 100727
®
ACTRONAIR CONTROLLERS LINE UP
CCI CPI & CVI
Model: CCI
Features:
•
•
•
•
•
•
•
•
•
•
3 Stage Cooling / 3 Stage Heating Control
24VAC Inputs
Optional 0 - 10V Compressor Control Inputs
Directly Interface to most Third Party Controllers including BMS System
Demand Response Capable (AS4755 Compliant)
Night Mode / Economy Mode / Boost Heat Inputs
System Run & Fault Status Relay Outputs
Directly Communicate with D4 Outdoor Boards
RS485 Communication Capability for Future Expansion
Separate Indoor Fan Input (AUTO/CONT./FAN MODE)
Model: CVI-1
Features:
Part No. 2020-081
Indoor Fan Variable Speed Board
(Factory Supplied & Fitted)
•
•
•
•
•
•
•
+VIN
0-10V DC Indoor Fan Speed Control Output
Fully Adjustable Fan Speed by a Trimmer Pot with 1% Step
2-Digit Display Speed Settings (10% - 99%)
6 Models Selection by a Jumper Pin
240VAC Indoor Fan Control Input
Compact Design
0-10VDC Fan Speed Input (Third Party Control)
Model: CVI-2
Features:
Part No. 2020-085
Indoor Fan Variable Speed Board
(Factory Supplied & Fitted)
•
•
•
•
•
•
•
Model: CPI
Features:
Part No. 2020-101 / 102 / 103
Indoor Fan Variable Speed Board
(Factory Supplied & Fitted)
•
•
•
•
•
•
•
PWM2 OUT
P4
P3
C7
R4
R3
R2
D3
A
B
C
D
E
R15
F
C8
U3
U4
MODEL
R10
R11
R12
R13
R14
R1
C5
ADJUST
INPUT
GND 0 - 10V
PWM1 OUT
DISP2 DISP1
V1.0
V2
RV1
+
C3
P6
C2
CPI3-1
D1
+
D2
P2
DAMAGE DUE TO
INCORRECT WIRING
VOIDS WARRANTY
0-10V DC Indoor Fan Speed Control Output
Fully Adjustable Fan Speed by a Trimmer Pot with 1% Step
2-Digit Display Speed Settings (10% - 99%)
6 Models Selection by a Jumper Pin
240VAC Indoor Fan Control Input
Compact Design
0-10VDC Fan Speed Input (Third Party Control)
0-10V DC Indoor Fan Speed Control Output
Fully Adjustable Fan Speed by a Trimmer Pot with 1% Step
2-Digit Display Speed Settings (10% - 99%)
6 Models Selection by a Jumper Pin
240VAC Indoor Fan Control Input
Compact Design
0-10VDC Fan Speed Input (Third Party Control)
TRA-0100-R
C1
S/No: 11G12276
CONTROL INFORMATION
Part No. 2020-080
Commercial Control Interface
(Factory Supplied & Fitted)
TX1
240VAC OUT
P5
CPI 3
23787-3
P1
ActronAir
IF
PWR
IF
ON/OFF 240VAC IN
R
®
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2011 Actron Engineering Pty. Ltd.
®
Controller Line Up P6 111031
®
ACTRONAIR CONTROLLER MATRIX
SPLIT DUCTED UNITS
WALL CONTROLLERS
(See Note Below)
LM7
LM7-D
LM24
C7-4
AM-ZC
AM-ZS
AERSN
AERSS
MANUAL
INPUT *
CCI
REMOTE **
ON/OFF
(HOME
AUTOMATION)
SRE091C / SRG091E
STD
N/A
OPT
OPT
N/A
N/A
OPT
OPT
N/A
OPT
SRA131C / SRG131E
STD
N/A
OPT
OPT
N/A
N/A
OPT
OPT
N/A
OPT
SRA133C / SRG131E
STD
N/A
OPT
OPT
N/A
N/A
OPT
OPT
N/A
OPT
SRD131C / SRV131E
N/A
STD
OPT
N/A
N/A
N/A
OPT
N/A
N/A
OPT
SRA151C / SRG151E
STD
N/A
OPT
OPT
N/A
N/A
OPT
OPT
N/A
OPT
SRA153C / SRG151E
STD
N/A
OPT
OPT
N/A
N/A
OPT
OPT
N/A
OPT
SRD151C / SRV151E
N/A
STD
OPT
N/A
N/A
N/A
OPT
N/A
N/A
OPT
SRD151C / SRM151E
N/A
STD
OPT
N/A
N/A
N/A
OPT
N/A
N/A
OPT
SRA171C / SRG171E
STD
N/A
OPT
OPT
N/A
N/A
OPT
OPT
N/A
OPT
SRA173C / SRG171E
STD
N/A
OPT
OPT
N/A
N/A
OPT
OPT
N/A
OPT
SRD173C / SRV171E
N/A
STD
OPT
N/A
N/A
N/A
OPT
N/A
N/A
OPT
SRD173C / SRM171E
N/A
STD
OPT
N/A
N/A
N/A
OPT
N/A
N/A
OPT
SRD191C / SRV191E
N/A
STD
OPT
N/A
N/A
N/A
OPT
N/A
N/A
OPT
SRD191C / SRM191E
N/A
STD
OPT
N/A
N/A
N/A
OPT
N/A
N/A
OPT
SRA203C / SRG201E
STD
N/A
OPT
OPT
N/A
N/A
OPT
OPT
N/A
OPT
SRA230C / SRA230E
STD
N/A
OPT
OPT
N/A
N/A
OPT
OPT
N/A
OPT
SRD230C / SRV230E
N/A
STD
OPT
N/A
N/A
N/A
OPT
N/A
N/A
OPT
SRD230C / SRM230E
N/A
STD
OPT
N/A
OPT
OPT
N/A
N/A
N/A
OPT
SRA260C / SRA260E
STD
N/A
OPT
OPT
N/A
N/A
OPT
OPT
N/A
OPT
SCA290C / SCG290E
N/A
N/A
N/A
OPT
N/A
N/A
OPT
OPT
N/A
OPT
SCA300C / SCA300E
N/A
N/A
N/A
OPT
N/A
N/A
OPT
OPT
N/A
OPT
SCA330C / SCA330E
N/A
N/A
N/A
OPT
N/A
N/A
OPT
OPT
N/A
OPT
SCA340C / SCA340E
N/A
N/A
N/A
OPT
N/A
N/A
OPT
OPT
N/A
OPT
SCA400C / SCG400E
N/A
N/A
N/A
OPT
N/A
N/A
OPT
OPT
N/A
OPT
CAY470T-6Q1 / EVY470T-6Q1
N/A
N/A
N/A
OPT
N/A
N/A
OPT
OPT
STD
OPT
CAY470T-6Q1 / ELY470T-6Q1
N/A
N/A
N/A
OPT
N/A
N/A
OPT
OPT
STD
OPT
CAY540T-6Q1 / EVY540T-6Q1
N/A
N/A
N/A
OPT
N/A
N/A
OPT
OPT
STD
OPT
CAY540T-6Q1 / ELY540T-6Q1
N/A
N/A
N/A
OPT
N/A
N/A
OPT
OPT
STD
OPT
CAY620T-6Q1 / EVY620T-6Q1
N/A
N/A
N/A
OPT
N/A
N/A
OPT
OPT
STD
OPT
CAY620T-6Q1 / ELY620T-6Q1
N/A
N/A
N/A
OPT
N/A
N/A
OPT
OPT
STD
OPT
CAY700T-6Q1 / EVY700T-6Q1
N/A
N/A
N/A
OPT
N/A
N/A
OPT
OPT
STD
OPT
CAY700T-6Q1 / ELY700T-6Q1
N/A
N/A
N/A
OPT
N/A
N/A
OPT
OPT
STD
OPT
CONTROL INFORMATION
MODELS
NOTE: These Wall Controllers are Low Voltage Inputs only. Usage of 240V manual input will damage equipment and void warranty.
* When using manual inputs, a 4 core 14/0.20 screened cable must be used between controller and PCB.
** ON / OFF switching operation of air conditioning system from a remote location. This is designed to work with Home / Building Automation System.
STD - Standard Supplied.
OPT - Optional, contact ActronAir Customer Care for your specific application requirement.
R
®
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
CONTROLLER MATRIX 120312
®
ACTRONAIR CONTROLLER MATRIX
PACKAGE UNITS
CONTROL INFORMATION
WALL CONTROLLERS
(See Note Below)
MODELS
C7-4
LM7-D
LM24
AERSN
AERSS
MANUAL
INPUT **
CCI
REMOTE ***
ON/OFF
(HOME
AUTOMATION)
PCG153U
OPT
OPT *
OPT *
OPT
OPT
N/A
OPT
PCG173U
OPT
OPT *
OPT *
OPT
OPT
N/A
OPT
PCG203U
OPT
OPT *
OPT *
OPT
OPT
N/A
OPT
PCA230U
OPT
OPT *
OPT *
OPT
OPT
N/A
OPT
PCA260U
OPT
OPT *
OPT *
OPT
OPT
N/A
OPT
PCG290U
OPT
OPT *
OPT *
OPT
OPT
N/A
OPT
PCA300U
OPT
OPT *
OPT *
OPT
OPT
N/A
OPT
PCA330U
OPT
OPT *
OPT *
OPT
OPT
N/A
OPT
PCA340U
OPT
OPT *
OPT *
OPT
OPT
N/A
OPT
PCG400U
OPT
OPT *
OPT *
OPT
OPT
N/A
OPT
PCG290L/R
OPT
OPT *
OPT *
OPT
OPT
N/A
OPT
PCG300L/R
OPT
OPT *
OPT *
OPT
OPT
N/A
OPT
PCG330L/R
OPT
OPT *
OPT *
OPT
OPT
N/A
OPT
PCG340L/R
OPT
OPT *
OPT *
OPT
OPT
N/A
OPT
PCG400L/R
OPT
OPT *
OPT *
OPT
OPT
N/A
OPT
PKY470T-6Q1
OPT
N/A
N/A
OPT
OPT
STD
OPT
PKY540T-6Q1
OPT
N/A
N/A
OPT
OPT
STD
OPT
PKY620T-6Q1
OPT
N/A
N/A
OPT
OPT
STD
OPT
PKY700T-6Q1
OPT
N/A
N/A
OPT
OPT
STD
OPT
PKY820T-3Q1
OPT
N/A
N/A
OPT
OPT
STD
OPT
PKY960T-3Q1
OPT
N/A
N/A
OPT
OPT
STD
OPT
NOTE: These Wall Controllers are Low Voltage Inputs only. Usage of 240V manual input will damage equipment and void warranty.
* It is possible to use this controller, however modifications are necessary. Contact ActronAir ® for details.
** When using manual inputs, a 4 core 14/0.20 screened cable must be used between controller and PCB.
*** ON / OFF switching operation of air conditioning system from a remote location. This is designed to work with Home / Building Automation System.
STD - Standard Supplied.
OPT - Optional, contact ActronAir Customer Care for your specific application requirement.
R
®
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2011 Actron Engineering Pty. Ltd.
®
CONTROLLER MATRIX 120210
®
ACTRONAIR CONTROL COMPARISON
WALL CONTROLLERS
M Series
24 Hr Control
8 Zone
(LM24)
M Series
7 Day Control
8 Zone
(LM7-D)
M Series
24 Hr Control
(AM24-H)
M Series
24 Hr Control
(AM24-HH)
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Adjustable Operating Range and Lockable
Set Temperature
•
•
Adjustable Lower / Upper Set Point Limits
•
•
Zone Control with Auto Sensor Tracking
Simple Operation
Attractive Slimline Design
Onboard Temperature Sensor
Optional Remote Sensor
Set Point Displayed
Dual Sensor Operation (Optional)
One Touch Temporary Room Temperature Display
Optional Temperature Set Point and Time Display
Auto Heat / Cool Change Over
•
2 Speed Indoor Fan
C Series
7 Day Control
(C7-4)
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Dual Control Capability - Optional (Using Mimic Logic)
Operate the System from 2 Separate Locations
•
•
•
•
•
Home / Building Automation Interface for Remote
ON / OFF Operation
•
•
•
•
•
Return Air Filter Indicator (100 to 600 Hrs Adjustable)
•
•
•
•
•
3 Speed Indoor fan
Fan Only Operation
Fan - Continuous - Function
2 Speed Outdoor Fan
Hot start Feature to Reduce Cold Drafts
Time Delay Manual Over-Rides
Self Diagnostic Fault Code Display
24 Hour Timer
7 Day Time Clock
Fully Programmable
Set Back Temperature
Home and Away Modes
Adjustable Differential for All Stages
Adjustable Dead Band
Multiple Staging 2 Cool / 3 Heat
Multiple Staging 3 Cool / 3 Heat
Adjustable Set Point in 0.50C Increments
4 Zone Control Option
8 Zone Control
Return Air Filter Indicator (30 to 370 Days Adjustable)
•
•
Minimum 1- Zone ON Safety with
Enable and Disable Feature
Sensor Logic
Memory for Auto Restart after Power Failure
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Auto Mode Lock
Repeat Function
Auto Defrost
•
•
•
•
•
•
•
After Hours Timer Function
Back Up Battery
•
•
•
•
•
•
•
•
•
•
CONTROL INFORMATION
M Series
7 Day Control
8 Zone
( LM7)
FUNCTIONS
•
•
•
•
•
•
•
R
®
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
CONTROLLER COMPARISON 120210
®
ACTRONAIR WALL CONTROLLER
FEATURES & FUNCTIONS
LM-SERIES - WALL CONTROLLER
ON
ON
OFF
LOW
COOL
LOW
AUTO
HEAT / COOL
FAN
PROGRAM
AUTO
HEAT / COOL
FAN
PROGRAM
TIMER
SET TEMP
SELECT
REPEAT /
EXIT
COOL
TIMER
SET TEMP
SELECT
EXIT
LM7
ON
OFF
REPEAT /
LM7-D
OFF
MED
COOL
CONT
AUTO
HEAT / COOL
FAN
SET
TEMP
TIMER
SELECT
DISPLAY
LM24
LM-SERIES
CONTROL INFORMATION
Available in standard 7-Day programmable and optional 24-Hr Timer models.
The “LM Series” controls are perfect controllers for large and double storey Home/Building installations requiring
two digital wall controls connected per system. The two controllers “Mimic” each other, such as whatever function
is selected on one control, the other control does likewise.
C7 - WALL CONTROLLER
AM
SET BACK EVENT 1
PM
o C TIME CLOCK ON OFF
2
ON
OFF
MON TUE WED THU FRI SAT SUN TIMER FILTER AH
CONT HIGH LOW
AUTO HEAT COOL RUN STAGE ROOM
FAN
CONTROL
AUTO
HEAT/COOL
SET
TEMP
DISPLAY
TIME CLOCK
PROGRAM
REPEAT
EXIT
CANCEL
RESTORE
1
2
3
4
TIMER
C7-4
C SERIES
Available in fully programmable 7-Day version.
The “C Series” control is a perfect wall controller for large and double storey Home/Building application. The controller is
capable of supporting up to 3-stage multiple staging systems.
FEATURES & FUNCTIONS
SIMPLE OPERATION
Simple to follow operating instructions with clear LCD/LED displays and indication lights to ensure ease of operation.
ATTRACTIVE SLIMLINE DESIGN
At only 15mm in depth, the same size as a standard switch plate, this Wall Controller is unobtrusive and will suit any decor.
ON BOARD TEMPERATURE SENSOR
The ActronAir AM-Series, LM-Series and C-Series wall controllers have an “In-built” temperature sensor. This sensor can be
enabled or disabled depending on the application requirements.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice, Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
FEATURES LM-C SERIES 120210
OPTIONAL REMOTE SENSOR
There may be air conditioning installations wherein the wall controller cannot be located in the most ideal position to sense
the air temperature. In such situations, it is recommended to use an optional remote sensor instead, which will also perform
the specific functions of the wall controller’s “In-built” sensor.
DUAL SENSOR OPERATION
The AM & LM-Series wall controllers have the provision for the use of two sensors wherein an even and uniform temperature
readings will be required, such as in a large room application. Two optional remote sensors can be utilized for this
requirement or a combination of one optional remote sensor coupled with the “In-built” sensor of the wall controller. The
sensors will ideally be placed on both ends of the room to average the temperature readings.
SET POINT DISPLAYED
Displaying the Set Point Temperature only and not the room temperature, will clearly indicate the setting temperature and not
the actual temperature. Therefore, the display dispels the confusion between room temperature readings and the room set
temperature. Such a simple control logic makes the operation much easier to understand. However, the installer can still be
able to access the room temperature readings via access code.
AUTO HEAT/COOL CHANGE OVER
An option to use Automatic Mode wherein the system will automatically select Heating or Cooling mode accordingly,
depending on the ambient temperature, in order to maintain a comfortable indoor temperature is a distinct feature included in
the AM & LM-Series Wall Controllers.
3- SPEED INDOOR FAN
There are three convenient Indoor Fan settings that are standard features of the M-Series controllers, which are: High,
Medium and Low. The High-Fan setting is for super responsive and fast delivery of comfort in demand, Medium-Fan setting
is designed for normal operation at maximum performance and efficiency, and Low-Fan setting is for quiet operation during
sleeping hours and also applied on a zoned system when reduced number of air outlets are operating.
FAN ONLY
A useful function when the requirement is only for the circulation and filtration of indoor air, without cooling or heating
condition.
FAN - CONT. FUNCTION
With the CONT. (Continuous Fan) selected, the indoor fan will run continuously while the air conditioner is turned on. This is
preferred during cooling mode to ensure maximum air circulation. However, during the heating mode it can create an effect
of cool drafts. It is then recommended not to have CONT. fan setting selected, so that the indoor fan will cycle On and Off
automatically with the outdoor unit.
ESP FAN SETTING (ESP ESP PLUS & ULTIMA Models)
Depending on the number of open vents or activated zones, the ESP fan mode will automatically adjust fan speed from
20% to 100% in order to deliver just the right amount of airflow required when zoning arrangement is changed. If more airflow
is needed to each zone, the manual LOW / MED / HIGH speed is recommended.
2 - SPEED OUTDOOR FAN
The microcomputer control will monitor outdoor conditions and will increase or decrease the fan speed in order to give the
maximum outdoor unit performance with minimal noise generation.
HOT START FUNCTION
When the air conditioner starts in heating mode, the indoor fan is delayed for a short period of time. This allows the heat
exchanger to warm up before the airflow starts, thereby preventing cold drafts. The hot start feature also activates itself when
the system finishes defrosting.
TIME DELAY MANUAL OVER-RIDE
In some instances, where over-riding the delay timer is necessary, it is possible to cancel the delay timer by pressing the
cancel timer’s button. Note that this feature should only be used by a qualified technician/installer. These time delays are
programmed for safety and the protection of the air conditioning system. Cancelling the timers may affect system operation
and possibly damage the system.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice, Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
FEATURES LM-C SERIES 120210
CONTROL INFORMATION
2- SPEED INDOOR FAN (WITH 2 SPEED CAPABLE INDOOR FAN ONLY)
The C-Series Wall Controllers has two convenient Indoor Fan settings that are standard features, which are: Hi and Low. The
Hi-Fan setting function is for super responsive and fast delivery of comfort in demand, while the Low-Fan setting is for quiet
operation during sleeping hours and also is applied on a zoned system when a reduced number of air outlets are operating.
SELF-DIAGNOSTIC FAULT CODE DISPLAY
In the unlikely event that a fault develops with the air conditioner, the microprocessor will diagnose the fault (where possible)
and display a fault code on the wall controller.
24- HOUR TIMER
This timer function is provided to automatically turn your air conditioner ON or OFF in a pre-set time of up to 24 Hours.
ADJUSTABLE DIFFERENTIAL DEAD BAND
This feature allows greater flexibility for system control. The difference between the Cut-In and Cut-Out temperature (the
differential) is adjustable from 0.50C to 5.00C. A small differential will maintain a more precise room temperature and a large
differential will reduce the number of compressor starts for a more economical operation. The difference between the cooling
and heating modes (the dead band) is also adjustable to suit varying conditions.
MULTIPLE STAGING AM & LM-SERIES WALL CONTROLLERS
With the addition of the 2 stage C.P.U. Board to the Outdoor Unit, the Wall Controller has the capability to control a second
stage HEAT / COOL mode and a third stage HEAT for Electric Boost Heater if required. These stages are also fully adjustable
and a typical set up is shown below:
SETPOINT
20.00C
20.50C
21.00C
CONTROL INFORMATION
STAGE 1 REV. CYCLE
22.00C
HEAT 1
22.50C
23.00C
23.50C
24.00C
COOL 1
HEAT 2
STAGE 2 REV. CYCLE
STAGE 3 BOOST HEAT
21.50C
COOL 2
BOOST
HEAT
MULTIPLE STAGING C-SERIES WALL CONTROLLERS
With the addition of the 2 stage C.P.U. Board to the Outdoor Unit, the Wall Controller has the capability to control a second
and third stage HEAT / COOL mode if required. These stages are also fully adjustable and a typical set up is shown below:
SETPOINT
20.00C
20.50C
STAGE 1 REV. CYCLE
HEAT 1
21.50C
22.00C
22.50C
23.00C
23.50C
24.00C
COOL 1
HEAT 2
STAGE 2 REV. CYCLE
STAGE 3 REV. CYCLE
21.00C
HEAT 3
COOL 2
COOL 3
7- DAY PROGRAMMABLE (AM7, LM7 & LM7-D MODELS ONLY)
A fully programmable 7- Day TIMECLOCK feature allows for setting the air conditioner to Turn On and Off at different times at
each day of the week. Each day can have two programmed events, wherein each event has ON and OFF Time.
ADJUSTABLE OPERATING RANGE AND LOCKABLE SET TEMPERATURE
The default operating range is factory set at 160C to 300C. However this can be adjusted to have a lower limit of 100C and an
upper limit of 380C. In some cases this could be detrimental to the air conditioning equipment. Therefore the lower and upper
limits should never exceed 160C and 300C. The chosen SET POINT can also be locked if required.
ZONE CONTROL OPTION
Depending on the applicable Wall Controller model, a zone control option is available to control up to 4 zones and 8 zones.
The integrated zoning system has a unique feature, where it can select which remote temperature to use depending on which
zone is selected. One example is on a two-storey house with only the downstairs zone turned-on. In this case, the zone
control will select the downstairs sensor to control the temperature, thereby ensuring perfect comfort in the occupied areas.
NOTE: C-Series Wall Controller is only available with 4-Zone option when used with optional CZ-1 230VAC zone
controller and third party zone barrels. The C-Series wall controller is an extra low voltage inputs only.
Usage of 230VAC input will damage equipment and void warranty.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice, Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
FEATURES LM-C SERIES 120210
DUAL WALL CONTROLLER OPERATION (Mimic LOGIC)
AM & LM-Series controllers are designed to support an additional secondary controller for total flexibility and optimum
comfort control. Dual control offers convenience in controller’s accessibility, particularly with units installed in a large or multistorey home or building. When a second controller is connected, the air conditioning unit can be controlled from either of the
wall controllers.
NOTE: 1. Combination of two 7-Day wall controllers is not possible. Use two of 24-Hr controllers or
a combination of one 24-Hr and one 7-Day programmable.
2. Information displayed on the two wall controllers are identical.
3. Last wall controller used has the priority.
HOME AUTOMATION INTERFACE FOR REMOTE ON/OFF SWITCHING
The AM, LM-Series and C-Series remote ON / OFF switching option works with most of the Home/Building Management
System. The automation function is used to switch the air conditioning system ON or OFF from a remote location, thereby
integrating the control of the A/C units with most of the central management system for flexibility of control and to attain
maximum comfort at optimum efficiency. Remote ON/OFF switching will also work with normal remote switch or time clock.
RETURN AIR FILTER INDICATOR
The microprocessor monitors the accumulated run time of the air conditioner and after a preset number of hours has passed,
the “FILTER” light will flash, indicating it is time to check if the filter needs cleaning. Time setting is adjustable from 100 to 600
hours or 30 to 370 days, depending on the wall controller model.
AUTO RESTART AFTER POWER FAILURE
Should a power failure occur while the air conditioner is running, the wall controller will restart the air conditioner in the same
mode (set prior to the loss of power) when the power is restored.
MINIMUM ONE ZONE ON WITH ENABLE AND DISABLE FEATURE
All AM & LM-Series wall controllers has a safety feature of always having at least one zone On to prevent the air conditioning
system from unnecessary tripping off. This feature can also be disabled / enabled through the wall controller set-up menu.
This added feature is most beneficial when you have a common area and still wants to use the maximum number of zones
on the wall controller.
NOTE: This feature is only available when wall controller is used with indoor board AMIB-8.
SENSOR LOGIC
This controller is pre-programmed with sensor logic. It has the ability, where two sensors are used, to detect faults with any
one of the sensors and automatically revert to using the readings from the operational sensor.
TIME DELAY
There are a number of time delays incorporated into the controllers for a high degree of compressor protection.
AUTO-DEFROST FUNCTION (HEATING MODE APPLICATION)
At certain outdoor conditions wherein the ambient temperature could drop very low, frost may gradually build up on the
outdoor heat exchanger which reduces the performance of the air conditioning unit. In some cases, this may cause damage
to the heat exchanger if the frost build up becomes excessive. The controllers’ microprocessor can detect this frost build up
and will automatically activate the defrost mode, ensuring optimum performance of the system.
R
®
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice, Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
FEATURES LM-C SERIES 120210
CONTROL INFORMATION
BACK UP BATTERY (APPLICABLE TO 7-DAY MODELS ONLY)
The the C-Series and the 7-Day models of the AM & LM-Series controllers incorporate a back-up battery. This feature is
useful during power interruption, wherein the controller will retain the programmed time clock and day settings.
®
ACTRONAIR ESP ULTIMA ZONE CONTROLLER
FEATURES & FUNCTIONS
AM-ZC Model (Optional Controller)
• Control Room / Zone Temperature
• Check Room Temperature at a Touch of a Button
• Constantly Relays Information to the Ultima Module and to the
Integrated Zone Barrels Air Damper
• Regulate Cooling / Heating Airflow in order to achieve the
desired Room Temperature
C
ZONE
COOL
ESP AUTO
HEAT
OFF
ZONE CONTROL
SET
TEMP
ROOM
TEMP
MODE
ON/OFF
CONTROL INFORMATION
SIMPLE OPERATION
Simple to operate Zone Controller, which allows individual zone comfort setting to be made.
ATTRACTIVE SLIMLINE DESIGN
This feature packed Zone Controller has design and pattern of a standard switch plate’s smooth contour and neutral colour
finish. Together with a slimline depth of only 15mm and the aesthetically presented LED display, this controller will perfectly
blend with any interior decor.
SET POINT DISPLAYED
Displaying the set point temperature only and not the room temperature dispels the confusion and makes the operation much
simpler. A room temperature button has been provided to check room temperature.
INDIVIDUAL ZONE TEMPERATURE SETTING
Lower or raise individual zone or room temperature.
NOTE: It is not possible to adjust the temperature set point of zone controller by 2 degrees lower / higher than the
set point temperature setting of wall controller.
ACTUAL ROOM TEMPERATURE DISPLAY
Single press of Room Temperature button will display actual room temperature for 5 seconds. The actual room temperature
can be displayed longer (for 45 seconds) when Room Temperature button is pressed and held for 5 seconds.
ON BOARD TEMPERATURE SENSOR
The AM-ZC Zone Controller has an onboard temperature sensor, when combined with a Zone Sensor, reads the average
room or zone temperature. Combination of Zone Controller and Zone Sensor, especially in large open plan room, has a
distinct advantage in maintaining uniform room or zone temperature throughout. See Installation & Commissioning Guide for
complete details.
ESP AUTO MODE
In the ESP mode, the Zone Controller will automatically regulate the position of the zone barrel damper in order to ensure
that zone temperature requirements are satisfied. The zone temperature requirement will be included in the system’s demand
for operation.
ZONE OPEN MODE
In this mode, the zone barrel damper will fully open to provide maximum circulation of air and will disregard onboard room
sensor. This mode will not control temperature.
BACKLIGHT
Easy to read blue backlight LCD display, which turns on when any key is pressed and turns off after 30 seconds.
R
®
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice, Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
FEATURES C - SERIES 120210
®
ACTRONAIR ESP ULTIMA ZONE SENSOR
FEATURES & FUNCTIONS
AM-ZS Model (Optional Sensor)
• Maintains the Zone / Room Temperature by using the Wall Controller
(AM7-D8) Set Point as its Target Temperature
• Constantly relays information to the Ultima Module and to the
Integrated Zone Barrels air Damper
• Regulate Cooling / Heating Airflow in order to Achieve Desired
Room Temperature
• Used as Averaging Sensor in Combination with AM-ZC Zone Controller
ATTRACTIVE SLIMLINE DESIGN
This Zone Sensor has a compact slimline design smooth contour and neutral colour finish that aesthetically blend with any
interior decoration.
CONTROL INFORMATION
TEMPERATURE SENSOR
The AM-ZS Zone Sensor is basically a compact temperature sensor, when combined with a Zone Controller, reads the
average room or zone temperature. Combination of Zone Controller and Zone Sensor, especially in large open plan room,
has a distinct advantage in maintaining uniform room or zone temperature throughout. See Installation & Commissioning
Guide for complete details.
R
®
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice, Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
FEATURES C - SERIES 120210
CONTROLLER CONFIGURATION
LM - SERIES CONTROLLER R410A STANDARD RESIDENTIAL MODELS
WALL
CONTROLLERS
DUAL CONTROL OPTION - A
DUAL CONTROL OPTION - B
Combination of 1 x 7-Day and 1 x 24-Hr Wall Controllers
Combination of 2 x 24-Hr Wall Controllers
ON
ON
OFF
LOW
COOL
AUTO
HEAT / COOL
FAN
PROGRAM
MED
AUTO
HEAT / COOL
TEMP
OPTIONS
SELECT
MED
AUTO
HEAT / COOL
FAN
TIMER
OFF
COOL
CONT
DUAL CONTROL
SET
SELECT
REPEAT /
EXIT
ON
OFF
COOL
CONT
FAN
TIMER
SET TEMP
ON
OFF
MED
SET
TEMP
DISPLAY
COOL
CONT
AUTO
HEAT / COOL
FAN
TIMER
SET
SELECT
TEMP
DISPLAY
TIMER
SELECT
DISPLAY
"A" or "B"
LM7
(Supplied)
4 CORE 14/0.20 (0.44mm)
Shielded Data Cable
(Wall Controllers - Indoor PCB)
LM24
(Optional)
LM24
(Purchased Separately)
LM24
(Optional)
OPTIONAL ZONE MODULES
INDOOR UNIT
(SRA - SRG FAN COIL)
ZONE 1
AMIB-PEC
Indoor Board
(Factory Supplied & Fitted)
MID
LOW
HIGH
RLY
Z1
Z2
Z3
ZONE 4
Z4
NC NO
NC NO
NEUT
NEUT
NC NO
NEUT
E
DATA /
AMZ
230VAC 4-Zone
INCORRECT
WIRING
INDOOR FAN 240V
VOIDS WARRANTY
2020-042
AMIB-P
PCB S/N
ZONE 1
EARTH
S-2
S - 1/G
KEY/Y
NEUT ACT
ZONE 3
NC NO
WARNING
DAMAGE DUE TO
COM / B
ZONE 2
ActronAir
AMIB-3
NEUT
ANE
NEUT
MODEL
EARTH
4Z-24V
24VAC 4-Zone
NEUT
ZONE 2
ACT
RLY
ZONE 3
Z1
Z2
Z3
ZONE 4
Z4
P.2.0.1.0.0
COM / B
SCRN
R-410A
“CAUTION”
3670-043
8Z-24V
24VAC 8-Zone
230VAC Cable*
2 CORE 14/0.20 (0.44mm)
Shielded Data Cable
FAN
HEAT
COMP
NEUT
ACT
HIGH
N
E
LOW
A
D2
SCRN
15 V
DATA
HEAT
FAN
COMP
NEUT
LOW
HIGH
ACT
NEUT
SCRN
15 V
DATA
HEAT
FAN
COMP
NEUT
LOW
HIGH
ACT
NEUT
ETH
RL2
HIGH
LP/HP COMP
RL1
MANUAL INPUT
(Optional)
LOW
SUPPLY RUN
MODULES
COMP
FAN
HEAT
15V
ACT
D4FD
Fault Diagnostic Board
(Optional)
15 V
TO
OPTIONAL
ZONE
D4STG2
2/3 Stage Boost Heat Board
(Optional)
NEUT
OUTDOOR UNIT
(SRA CONDENSER)
ETH
D4
D1
R1
ZD1
NEUT
REV
R22
R23
R21
R24
R19
R20
R16
R17
R18
R15
R11
RUN-2
RUN-1
LP/HP-2
LP/HP-1
COMP-2
COMP-1
EXT
AUTO
ST2
D4+ST2
MANUAL
ST1
2XD4
RST
COMP
R2
VERIFY2
CALL2CALL1N(IN)
VERIFY1
LP
R3
J2
COMP
R4
R5
SW1
NEUT
R10
C4
R25
R14
LP
R7
LP
R12
HP
HP
RESET
R8
LP
R13
HP
C2
C3
PB1
U4
HP
X1
U2
U5
R9
REV
C1
U1
C5
C6
U6
NEUT
D5
+
TX1
RL3
U3
COMPRESSOR
1
NEUT
COMPRESSOR
2
D3
J1
NEUT
NEUT
CONTROL INFORMATION
PLEASE ENSURE THERE IS
NO GAS / PRESSURE IN THE
FAN COIL UNIT BEFORE
REMOVING COPPER END CAPS.
D4CPU-P
Outdoor Board
(Factory Supplied & Fitted)
* 230V / 1Ph+N / 50Hz Supply. Suggested Minimum Control Cable Size = 1mm2 Must comply with AS/NZS 3000 Wiring Rules.
INTEGRATED ZONE BARRELS
1-ZONE UP TO 8-ZONE
(Optional)
PIGGY BACK CONFIGURATION
ZB-10-250
1-Zone
ZB-12-300
Up To
ZB-14-350
8-Zone
Options
ZB-16-400
REMOTE SENSOR AND
DUCT BEAD SENSOR
2 CORE 14/0.20 (0.44mm)
Shielded Data Cable
sor
Sen
AERSN
Remote Sensor
(Optional)
CAT5E Cable with Basic
Non-Moulded RJ45 Plug
AERSS
Duct Bead Sensor
(Optional)
NOTE:
R
®
1. DIAGRAM SHOWN ABOVE IS A GENERAL PRESENTATION ONLY. REFER TO INDIVIDUAL UNIT WIRING
DIAGRAM FOR COMPLETE WIRING CONNECTION DETAILS.
2. REFER TO M-SERIES MAXIMUM CABLE LENGTH PAGE FOR CABLE LENGTH DETAILS & SPECIFICATIONS.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
CONTROLLER CONFIGURATION 120210
LM-SERIES SRA MODELS
CONTROLLER CONFIGURATION
LM - SERIES CONTROLLER R410A ESP PLUS MODELS
WALL
CONTROLLERS
®
DUAL CONTROL OPTION - A
DUAL CONTROL OPTION - B
Combination of 1 x 7-Day and 1 x 24-Hr Wall Controllers
Combination of 2 x 24-Hr Wall Controllers
ON
ON
OFF
LOW
COOL
AUTO
HEAT / COOL
FAN
PROGRAM
MED
DUAL CONTROL
AUTO
HEAT / COOL
SET
SELECT
TEMP
REPEAT /
EXIT
ON
OFF
COOL
CONT
FAN
TIMER
SET TEMP
ON
OFF
MED
OPTION
TIMER
SELECT
MED
AUTO
HEAT / COOL
FAN
COOL
CONT
AUTO
HEAT / COOL
FAN
TIMER
SET
TIMER
SET
SELECT
TEMP
DISPLAY
OFF
COOL
CONT
SELECT
TEMP
DISPLAY
DISPLAY
"A" or "B"
LM7-D
(Supplied)
4 CORE 14/0.20 (0.44mm)
Shielded Data Cable
(Wall Controllers - Indoor PCB)
LM24
(Purchased Separately)
LM24
(Optional)
AMIB-1PDV (1Ph Digital)
AMIB-3PDV (3Ph Digital)
INDOOR UNIT
(SRV FAN COIL)
LM24
(Optional)
OPTIONAL ZONE MODULES
Indoor Board
(Factory Supplied & Fitted)
ZONE 1
ActronAir
AMIB-3
EARTH
MID
HIGH
LOW
ANE
NEUT
MODEL
4Z-24V
24VAC 4-Zone
NEUT ACT
ZONE 2
RLY
Z1
ZONE 3
Z2
Z3
ZONE 4
Z4
WARNING
DAMAGE DUE TO
E
DATA /
COM / B
S-2
S - 1/G
KEY/Y
INCORRECT
WIRING
INDOOR FAN 240V
VOIDS WARRANTY
2020-040
AMIB-P3D
PCB S/N
P.3.X.1.0.0
COM / B
SCRN
COIL OUT A B C D E
COIL IN
EXV
GAB
R-410A
“CAUTION”
PLEASE ENSURE THERE IS
NO GAS / PRESSURE IN THE
FAN COIL UNIT BEFORE
REMOVING COPPER END CAPS.
3670-043
OUTDOOR UNIT
(SRD CONDENSER)
230VAC Cable*
CONTROL INFORMATION
2 CORE 14/0.20 (0.44mm)
Shielded Data Cable
8Z-24V
24VAC 8-Zone
D4CPU-PD
Outdoor Board
(Factory Supplied & Fitted)
TO
OPTIONAL
ZONE
MODULES
CAT5E Cable with Basic
Non-Moulded RJ45 Plug
NEUT
ACT
FAN
HIGH
LOW
ON/OFF
NEUT
COMP
FAN
HEAT
15V
MANUAL INPUT
(Optional)
* 230V / 1Ph+N / 50Hz Supply. Suggested Minimum Control Cable Size = 1mm2 Must comply with AS/NZS 3000 Wiring Rules.
INTEGRATED ZONE BARRELS
1-ZONE UP TO 8-ZONE
(Optional)
PIGGY BACK CONFIGURATION
ZB-10-250
1-Zone
ZB-12-300
Up To
ZB-14-350
8-Zone
Options
ZB-16-400
REMOTE SENSOR AND
DUCT BEAD SENSOR
sor
Sen
AERSN
Remote Sensor
(Optional)
AERSS
Duct Bead Sensor
(Optional)
2 CORE 14/0.20 (0.44mm)
Shielded Data Cable
NOTE:
1. DIAGRAM SHOWN ABOVE IS A GENERAL PRESENTATION ONLY. REFER TO INDIVIDUAL UNIT WIRING
DIAGRAM FOR COMPLETE WIRING CONNECTION DETAILS.
2. REFER TO M-SERIES MAXIMUM CABLE LENGTH PAGE FOR CABLE LENGTH DETAILS & SPECIFICATIONS.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2011 Actron Engineering Pty. Ltd.
®
R
®
CONTROLLER CONFIGURATION 100727
M-SERIES ESP PLUS MODELS
CONTROLLER CONFIGURATION
LM - SERIES CONTROLLER R410A ESP ULTIMA MODELS
WALL
CONTROLLERS
TM
DUAL CONTROL OPTION - A
DUAL CONTROL OPTION - B
Combination of 1 x 7-Day and 1 x 24-Hr Wall Controllers
Combination of 2 x 24-Hr Wall Controllers
ON
ON
OFF
LOW
MED
AUTO
HEAT / COOL
FAN
PROGRAM
AUTO
HEAT / COOL
SET
SELECT
TEMP
REPEAT /
EXIT
ON
OFF
DUAL CONTROL
COOL
CONT
FAN
TIMER
SET TEMP
ON
OFF
COOL
MED
SELECT
MED
AUTO
HEAT / COOL
FAN
OPTION
TIMER
COOL
CONT
AUTO
HEAT / COOL
FAN
TIMER
SET
SET
SELECT
TEMP
DISPLAY
OFF
COOL
CONT
TEMP
DISPLAY
TIMER
SELECT
DISPLAY
"A" or "B"
LM24
(Purchased Separately)
LM7-D
(Supplied)
4 CORE 14/0.20 (0.44mm)
Shielded Data Cable
(Wall Controllers - Indoor PCB)
INDOOR UNIT
(SRM FAN COIL)
LM24
(Optional)
LM24
(Optional)
AMIB-PDVM
ULTIMA MODULE
8Z-VAV
Indoor Board
(Factory Supplied & Fitted)
24VAC 8-Zone
(Factory Supplied & Fitted)
MODEL
MID
HIGH
LOW
ANE
NEUT
ActronAir
AMIB-3
WARNING
DAMAGE DUE TO
E
DATA /
COM / B
S-2
S - 1/G
KEY/Y
INCORRECT
WIRING
INDOOR FAN 240V
VOIDS WARRANTY
2020-040
AMIB-P3D
PCB S/N
P.3.X.1.0.0
COM / B
R-410A
COIL OUT A B C D E
3670-043
CONTROL INFORMATION
3 Way Joiner
RJ45
SCRN
“CAUTION”
PLEASE ENSURE THERE IS
NO GAS / PRESSURE IN THE
FAN COIL UNIT BEFORE
REMOVING COPPER END CAPS.
COIL IN
EXV
GAB
2 CORE 14/0.20 (0.44mm)
Shielded Data Cable
OUTDOOR UNIT
(SRD CONDENSER)
D4CPU-PD
Outdoor Board
(Factory Supplied & Fitted)
230VAC Cable*
CAT5E Cable with
Fully-Moulded RJ45 Plug
ON/OFF
NEUT
NEUT
COMP
FAN
HEAT
15V
MANUAL INPUT
(Optional)
* 230V / 1Ph+N / 50Hz Supply. Suggested Minimum Control Cable Size = 1mm2 Must comply with AS/NZS 3000 Wiring Rules.
INTEGRATED ZONE BARRELS
1-ZONE UP TO 8-ZONE
(Optional)
PIGGY BACK CONFIGURATION
ZB-10-250
1-Zone
ZB-12-300
Up To
ZB-14-350
8-Zone
Options
ZB-16-400
ZONE CONTROL OPTIONS
C
ZONE
COOL
ESP AUTO
ZONE
COOL
ESP AUTO
HEAT
TEMP
SET
TEMP
MODE
ON/OFF
AM-ZC
OPTION A ZONE CONTROLLER
ZONE CONTROL
ROOM
TEMP
AM-ZS
OPTION B ZONE SENSOR
AM-ZS
ZONE
COOL
ESP AUTO
HEAT
OFF
OFF
ZONE CONTROL
SET
C
C
HEAT
OFF
ZONE CONTROL
ROOM
TEMP
SET
TEMP
MODE
ON/OFF
AM-ZC
OPTION C - AVERAGING
ZONE SENSOR/ZONE CONTROLLER
ROOM
TEMP
MODE
ON/OFF
AM-ZC
OPTION D PIGGY BACK CONFIGURATION
OPTION D - SHOWS ZONE CONTROL IN DIAGRAM BUT CAN HAVE ANY OF THE ABOVE CONFIGURATION
NOTE:
1. DIAGRAM SHOWN ABOVE IS A GENERAL PRESENTATION ONLY. REFER TO INDIVIDUAL UNIT WIRING
DIAGRAM FOR COMPLETE WIRING CONNECTION DETAILS.
2. REFER TO M-SERIES MAXIMUM CABLE LENGTH PAGE FOR CABLE LENGTH DETAILS & SPECIFICATIONS.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
R
®
CONTROLLER CONFIGURATION 120210
LM-SERIES ULTIMA MODELS
CONTROLLER CONFIGURATION
C-SERIES CONTROLLER R410A TRI-CAPACITY MODELS
WALL
CONTROLLERS
SET BACK EVENT 1
AM
2
ON
o C TIME CLOCK ON OFF
PM
OFF
MON TUE WED THU FRI SAT SUN TIMER FILTER AH
CONT HIGH LOW
AUTO HEAT COOL RUN STAGE ROOM
FAN
AUTO
HEAT/COOL
CONTROL
SET
DISPLAY
TIME CLOCK
PROGRAM
REPEAT
EXIT
CANCEL
RESTORE
TEMP
sor
TIMER
Sen
1
FAMILY
2
RUMPUS
3
MASTER BED
4
BEDROOM 1
AERSS
Duct Bead Sensor
(Optional)
2 CORE 14/0.20 (0.44mm)
Shielded Data Cable
C7-4
(Optional)*
2 CORE 14/0.20 (0.44mm)
Shielded Data Cable
AERSN
Remote Sensor
(Optional)
* Cannot use C7-4 and CCI together, disconnect CCI before fitting C7-4 wall controller.
D4CPU-P2
Outdoor CPU Board
Large Compressor
(Factory Supplied & Fitted)
D - OPTION
D4CPU-P2
Outdoor CPU Board
Small Compressor
(Factory Supplied & Fitted)
D4FD
Fault Diagnostic Board
(Optional)
2 CORE 14/0.20 (0.44mm)
Shielded Data Cable
AUTO
ST2
D4+ST2
R21
R24
SW1
R23
EXT
MANUAL
ST1
2XD4
CONTROL INFORMATION
R22
RST
Z - OPTION
3PS
3-Phase Soft Starter
Small Compressor
(Optional)
3PS
3-Phase Soft Starter
Large Compressor
(Optional)
N2132
N2132
E
E
NEU
NEU
RUN
RUN
CCH
CCH
CCH
CCH
CVI
Indoor Fan Variable Speed Board
(Factory Supplied & Fitted)
0 - 10V GND
+VIN
AUX AUX
MODEL
ADJUST
CVI 1
23782 - 1
ACT
NEU
GND
2 CORE 14/0.20 (0.44mm)
Shielded Data Cable
230VAC Cable*
Z-OPTION
OR
W-OPTION
2 CORE 14/0.20 (0.44mm)
Shielded Data Cable
W - OPTION
+15V
AUX3
AUX2
NEUT
AUX1
NIGHT
ON/OFF
ECONY
INFAN
BOOST
HEAT
REV
NEUT
COMP3
COMP2
COMP1
GND
0-10V
CCI
Commercial Control Interface
(Factory Supplied & Fitted)
15
L2
U12
N2132
U1
U2
U3
U10
U5
U4
U8
U11
U9
RPW-FSA
3-Phase Sequence
Protection Relay
(Optional)
U15
P6
R
P7
C1U1
23781 - 1
P8
C1
P4
LED1
RPW - SF
P3
P4
BOOST
ECO
IN
RUN
FAULT
16
18
L3
* 230V / 1Ph+N / 50Hz Supply.
Suggested Minimum Control Cable Size = 1mm2 .
Must comply with AS/NZS 3000 Wiring Rules.
NOTES:
1. DIAGRAM SHOWN ABOVE IS A GENERAL PRESENTATION ONLY. REFER TO INDIVIDUAL UNIT
WIRING DIAGRAM FOR COMPLETE WIRING CONNECTION DETAILS.
2. DISCONNECT CCI WHEN USING ACTRONAIR C7-4 WALL CONTROLLER. REFER TO WIRING
DIAGRAM FOR COMPLETE INSTRUCTIONS WHEN USING C7-4 CONTROLLER.
3. REFER MAXIMUM CABLE LENGTH DETAILS & SPECIFICATIONS TO
C-SERIES MAXIMUM CABLE LENGTH PAGE IN CONTROL SECTION.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
2 CORE 14/0.20 (0.44mm)
Shielded Data Cable
R
®
CONTROLLER CONFIGURATION 120210
C-SERIES TRI-CAPACITY MODELS
CONTROLLER CONFIGURATION
C - SERIES CONTROLLER R410A COMMERCIAL MODELS
WALL CONTROLLER
SET BACK EVENT 1
AM
2
ON
o C TIME CLOCK ON OFF
PM
OFF
MON TUE WED THU FRI SAT SUN TIMER FILTER AH
CONT HIGH LOW
AUTO HEAT COOL RUN STAGE ROOM
C7-4
FAN
CONTROL
AUTO
HEAT/COOL
SET
DISPLAY
TIME CLOCK
PROGRAM
TEMP
TIMER
REPEAT
CANCEL
RESTORE
EXIT
1
FAMILY
2
RUMPUS
3
MASTER BED
4
BEDROOM 1
2 CORE 14/0.20 (0.44mm)
Shielded Data Cable
2 CORE 14/0.20 (0.44mm)
Shielded Data Cable
OUTDOOR UNIT
(SCA CONDENSER)
D4FD
Fault Diagnostic Board
(Optional)
COMPRESSOR
1
D4STG2
2/3 Stage Boost Heat Board
(Optional)
COMPRESSOR
2
R10
R12
R13
J1
SUPPLY RUN
R4
U3
U5
A
RL3
U4
N
R7
RUN-1
LP/HP COMP
RL2
R2
R8
R3
VERIFY2
CALL2
N(IN)
VERIFY1
CALL1
R9
J2
RL1
U6
R5
R11
R15
LP/HP-1
E
U2
R16
COMP-1
R17
RUN-2
R18
R19
C6
LP/HP-2
R20
COMP-2
R24
TX1
C5
X1
AUTO
ST2
D4+ST2
R21
C4
+
R14
C1
SW1
ZD1
R25
R23
R22
ETH
NEUT
ACT
HIGH
LOW
HP
NEUT
HP
NEUT
LP
REV
LP
COMP
NEUT
D5
R1
CONTROL INFORMATION
D3
D4
D2
D1
RST
RESET
EXT
C2
C3
U1
MANUAL
ST1
2XD4
PB1
NEUT
ACT
HIGH
LOW
NEUT
COMP
FAN
HEAT
COMP
15 V
FAN
HEAT
15 V
DATA
SCRN
D4CPU11
Outdoor Board
(Factory Supplied & Fitted))
CAUTION
MEPS
CERTIFIED
MODEL
R-410A
AU S T RA L I N M A D E
AUSTR ALI N OW NED
LIVE ELECTRICAL WIRING
AUTHORISED TECHNICIANS ONLY
INTERNAL CONTROL ISOLATOR FITTED
COMP
FAN
HEAT
15V
MANUAL INPUT
(Optional)
CZ
2 CORE 14/0.20 (0.44mm)
Shielded Data Cable
240Volt Zone Kit
(Optional)
230VAC CABLES *
WARNING
240 VOLTS
ISOLATE POWER BEFORE
REMOVING COVER
* 230V / 1Ph+N / 50Hz Supply. Suggested Minimum Control Cable Size = 1mm2 .
Must comply with AS/NZS 3000 Wiring Rules.
THIRD PARTY 230VAC ZONE BARRELS
1-Zone
Up To
4-Zone
(Max. of 4 Third Party Zone Motors per System)
REMOTE SENSOR AND
DUCT BEAD SENSOR
sor
Sen
AERSN
Remote Sensor
(Optional)
AERSS
Duct Bead Sensor
(Optional)
NOTE:
1. DIAGRAM SHOWN ABOVE IS A GENERAL PRESENTATION ONLY. REFER TO INDIVIDUAL UNIT WIRING
DIAGRAM FOR COMPLETE WIRING CONNECTION DETAILS.
2. REFER TO C-SERIES MAXIMUM CABLE LENGTH PAGE FOR CABLE LENGTH DETAILS & SPECIFICATIONS.
3. SPECIFIED CABLES AND CONTROLLERS ARE ALSO APPLICABLE TO CORRESPONDING PACKAGE MODELS.
SPLIT OUTDOOR UNIT SHOWN FOR ILLUSTRATION PURPOSES ONLY.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2010 Actron Engineering Pty. Ltd.
®
R
®
CONTROLLER CONFIGURATION 120210
C-SERIES COMMERCIAL MODELS
MAXIMUM CABLE LENGTHS
LM-SERIES WALL CONTROLLER TO STANDARD INDOOR PCB
OPTIONAL
DUAL MASTER CONTROLLER
(Mimic Logic)
Secondary Wall Controller
Master Wall Controller
ON
ON
OFF
MED
COOL
CONT
AUTO
HEAT / COOL
FAN
SET
TEMP
OFF
LOW
COOL
SELECT
AUTO
HEAT / COOL
FAN
TIMER
DISPLAY
PROGRAM
TIMER
SET TEMP
SELECT
EXIT
REPEAT /
3A
3
4 CORE 14/0.20 (0.44mm)
Shielded Data Cable
MODEL
R-410A
“CAUTION”
CONTROL INFORMATION
PLEASE ENSURE THERE IS
NO GAS / PRESSURE IN THE
FAN COIL UNIT BEFORE
REMOVING COPPER END CAPS.
3670-043
TO OUTDOOR PCB
1
2
INDOOR UNIT
TO INDOOR PCB
CAUTION
MEPS
CERTIFIED
TR
AU
ED
E
ST
2 CORE 14/0.20 (0.44mm)
Shielded Data Cable
AL I AN M
AU
S
R-410A
AD
LIVE ELECTRICAL WIRING
AUTHORISED TECHNICIANS ONLY
INTERNAL CONTROL ISOLATOR FITTED
RA
N
MODEL
L I AN
OW
OUTDOOR UNIT
ITEM
DESCRIPTION
1 to 2
Outdoor PCB to Indoor PCB
60 m
2 to 3
Indoor PCB to Master Wall Controller
40 m
2 to 3A
MAXIMUM CABLE LENGTH *
Indoor PCB to Secondary Wall Controller
40m (Including 2 to 3) **
* Suggested Maximum Cable Length
Long runs beside Mains cables or TV antenna cables should be avoided where possible.
2 CORE 14/0.20 (0.44mm) Shielded Data Cable must be used between Indoor and Outdoor units.
4 CORE 14/0.20 (0.44mm) Shielded Data Cable must be used for wall controller wires.
** Total Cumulative Cable Length with Secondary Controller must not exceed 40 meters.
For example, if 2 to 3 is 30m then 2 to 3A must not exceed 10m.
NOTE: Trace wire connects to SCN/COM terminal at Outdoor PCB and to SCN on Indoor PCB. Do not connect at Wall Controllers.
NOTES:
1. DIAGRAM SHOWN ABOVE IS A GENERAL PRESENTATION ONLY. REFER TO INDIVIDUAL UNIT
WIRING DIAGRAM FOR COMPLETE WIRING CONNECTION DETAILS.
2. LM SERIES WALL CONTROLLERS SHOWN ARE FOR ILLUSTRATION PURPOSES ONLY. DATA ABOVE ARE
APPLICABLE TO AM SERIES CONTROLS.
R
®
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
MAXIMUM CABLE LENGTH 120210
Copyright © 2011 Actron Engineering Pty. Ltd.
LM-SERIES WALL CONTROL TO INDOOR PCB
®
MAXIMUM CABLE LENGTHS
LM - SERIES MODELS WITH OPTIONAL 4 - OR - 8 ZONE CONTROLLER
OPTION - A
INTEGRATED ZONE BARRELS WITH OPTIONAL ZONE MODULE
(1-Zone Up To 8-Zone Options)
NOTE:
DIAGRAM SHOWN IS A GENERAL PRESENTATION ONLY.
REFER TO INDIVIDUAL UNIT WIRING DIAGRAM FOR COMPLETE
WIRING CONNECTION DETAILS.
6
OPTIONAL
DUAL MASTER CONTROLLER
(Mimic Logic)
OPTIONAL
REMOTE SENSOR
AND
DUCT HEAD SENSOR
Secondary Wall Controller
COOL
CONT
AUTO
HEAT / COOL
FAN
SET
TEMP
sor
Sen
5
LOW
COOL
AUTO
HEAT / COOL
FAN
PROGRAM
SET TEMP
DISPLAY
OPTIONAL
ZONE MODULE
(8Z - 24V) ^^
TIMER
SELECT
EXIT
REPEAT /
4
3
8
7
INDOOR UNIT
4 CORE 14/0.20 (0.44mm)
Shielded Data Cable
OPTIONAL
PIGGY-BACK
CONFIGURATION
MODEL
8-ZONES
OR
4-ZONES
R-410A
CAT5E Cable with Basic
Non-Moulded RJ45 Plug
CONTROL INFORMATION
6
OFF
TIMER
SELECT
6
CAT5E Cable with Basic
Non-Moulded RJ45 Plug
ON
OFF
MED
5
Master Wall Controller
ON
OPTIONAL
1 ZONE - UP - TO - 8 ZONES
(Max. of 10 Zone Motors/System)
“CAUTION”
PLEASE ENSURE THERE IS
NO GAS / PRESSURE IN THE
FAN COIL UNIT BEFORE
REMOVING COPPER END CAPS.
3670-043
OPTIONAL
PIGGY-BACK
CONFIGURATION
2
TO INDOOR PCB
10
1
CAT5E Cable with Basic
Non-Moulded RJ45 Plug
TO OUTDOOR PCB
TO INDOOR PCB
WITH OPTIONAL ZONE KIT
4Z-24V ^^^
9
CAUTION
MEPS
CERTIFIED
TR
AL I AN M
ED
AU
ST
RA
W
L I AN O
OUTDOOR UNIT
ITEM
9
E
AU
S
R-410A
9
AD
LIVE ELECTRICAL WIRING
AUTHORISED TECHNICIANS ONLY
INTERNAL CONTROL ISOLATOR FITTED
OPTIONAL
1 ZONE - UP - TO - 4 ZONES
(Max. of 8 Zone Motors/System)
N
MODEL
OPTION - B
INTEGRATED ZONE BARRELS WITH OPTIONAL ZONE KIT
(1-Zone Up To 4-Zone Options)
DESCRIPTION
MAXIMUM CABLE LENGTH * ^
1 to 2
Outdoor PCB to Indoor PCB
60 m
2 to 3
Indoor PCB to Master Controller
40m
2 to 4
Indoor PCB to Secondary Wall Controller
40m (Including 2 to 3) See Note Below
2 to 5
Indoor PCB to Remote Sensor (Max. of 2 Optional Sensors)
2 to 7
Indoor PCB to Zone Module
50 m each
50 m
2 to 8
Maximum Cumulative Cable Length ** (per zone - 8 zone), i.e. 2 to 8
100 m
2 to 10
Maximum Cumulative Cable Length ** (per zone - 4 zone), i.e. 2 to 10
100 m
3 to 4
Master Wall Controller to Secondary Wall Controller
20 m
6 to 7
Integrated Zone Barrel 6 to Zone Module ***
100 m
6 to 8
Zone Barrel 6 to Zone Barrel 8 (Piggy-Back) ****
95 m
9 to 10
Zone Barrel 9 to Zone Barrel 10 (Piggy-Back) ****
95 m
* Recommended Maximum Cable Length
Long runs beside Mains cables or TV antenna cables should be avoided where possible.
2 CORE 14/0.20 (0.44mm) and 4 CORE 14/0.20 (0.44mm) Shielded Data Cable must be used.
** Maximum Cumulative Cable Length must not exceed 100 m per zone.
For Example, 2 to 8 (Optional 8 Zones Piggy-Back Configuration), if 2 to 7 is 25m, 6 to 7 is 25m, then 6 to 8 must be 50m to make a total of 100m.
2 to 10 (Optional 4 Zones Piggy-Back Configuration), if 2 to 9 is 75m, then 9 to 10 must be 25m to make a total of 100m.
*** Recommended maximum cable length, provided total of preceding and subsequent cable connections are only 5m.
**** Recommended maximum cable length, provided total of preceding cable connections are less than 5m.
^ Total Cumulative length of all the aggregate cable must not exceed 500 meters. Consult ActronAir for longer cable length requirement.
^^ Total of 8 Zone Barrels are allowed with 4Z-24V zone controllers. 10 Zone Barrels are allowed for 8Z-24V.
NOTE: Total Cumulative Cable Length with Dual Controller must not exceed 40 meters. For example, if 2 to 3 is 30m then 2 to 4 must not exceed 10m.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
MAXIMUM CABLE LENGTH 120210
M-SERIES MODELS WITH 4 OR 8-ZONE
MAXIMUM CABLE LENGTHS
LM-SERIES WALL CONTROLLER TO INDOOR PCB ULTIMA MODELS
TM
OPTIONAL
DUAL MASTER CONTROLLER
(Mimic Logic)
Master Wall Controller
ON
ON
OFF
MED
COOL
CONT
AUTO
HEAT / COOL
FAN
SET
TEMP
OFF
LOW
COOL
TIMER
SELECT
DISPLAY
AUTO
HEAT / COOL
FAN
PROGRAM
TIMER
SET TEMP
SELECT
EXIT
4A
REPEAT /
4
INDOOR UNIT
4 CORE 14/0.20 (0.44mm)
Shielded Data Cable
MODEL
ULTIMA
MA
A
MODULE
LE
E
Secondary Wall Controller
3
R-410A
R-410
“CAUTION”
PLEASE ENSURE THE
THERE IS
NO GAS / PRESSURE IN THE
BEFO
FAN COIL UNIT BEFORE
REMOVING COPPER END CAPS.
3670-043
CONTROL INFORMATION
TO O
TO
OUTDOOR PCB
1
2
TO INDOOR PCB
CAUTION
MEPS
CERTIFIED
TR
AU
ED
E
ST
2 CORE 14/0.20 (0.44mm)
Shielded Data Cable
AL I AN M
AU
S
R-410A
AD
LIVE ELECTRICAL WIRING
AUTHORISED TECHNICIANS ONLY
INTERNAL CONTROL ISOLATOR FITTED
RA
N
MODEL
W
L I AN O
OUTDOOR UNIT
ITEM
DESCRIPTION
1 to 2
Outdoor PCB to Indoor PCB
2 to 3
Indoor PCB to Ultima Module (factory fitted)
2 to 4
Indoor PCB to Master Wall Controller
2 to 4A
MAXIMUM CABLE LENGTH *
Indoor PCB to Secondary Wall Controller
60 m
0.60 m
40 m
40m (Including 2 to 4) **
Suggested Maximum Cable Length
* Long runs beside Mains cables or TV antenna cables should be avoided where possible.
2 CORE 14/0.20 (0.44mm) Shielded Data Cable must be used between Indoor and Outdoor units.
4 CORE 14/0.20 (0.44mm) Shielded Data Cable must be used for wall controller wires.
** Total Cumulative Cable Length with Secondary Controller must not exceed 40 meters.
For example, if 2 to 3 is 30m then 2 to 3A must not exceed 10m.
NOTE: Trace wire connects to SCN/COM terminal at Outdoor PCB and to SCN on Indoor PCB. Do not connect at Wall Controllers.
NOTE:
DIAGRAM SHOWN ABOVE IS A GENERAL PRESENTATION ONLY. REFER TO INDIVIDUAL UNIT WIRING DIAGRAM
FOR COMPLETE WIRING CONNECTION DETAILS.
R
®
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
MAXIMUM CABLE LENGTH 120210
Copyright © 2012 Actron Engineering Pty. Ltd.
M-SERIES WALL CONTROL TO ULTIMA ID PCB
®
MAXIMUM CABLE LENGTHS
LM-SERIES ULTIMA MODELS WITH 8-ZONE CONTROLLER
TM
INTEGRATED ZONE BARRELS
(1-Zone Up To 8-Zone Options / Max. of 10 Zone Motors per System)
OPTIONAL
1 ZONE - UP - TO - 8 ZONES
C
ZONE
COOL HEAT
ESP AUTO
3
5
4
MAX
OFF
TEMP
COOL HEAT
MAX
OFF
ZONE CONTROL
ROOM
TEMP
SET
MODE
ON/OFF
SET
TEMP
3A
4A
OPTIONAL
ZONE
CONTROLLER
ROOM
TEMP
MODE
ON/OFF
6B
OPTIONAL
REMOTE SENSOR
6
8Z-VAV
ULTIMA 8 - ZONE MODULE
(Factory Supplied & Fitted)
ULTIMA
MODULE
MODEL
CONTROL INFORMATION
6A
C
ZONE
ESP AUTO
ZONE CONTROL
2
OPTIONAL
INTEGRATED ZONE BARRELS
(With Piggy-Back configuration)
R-410A
“CAUTION”
PLEASE ENSURE THERE IS
NO GAS / PRESSURE IN THE
FAN COIL UNIT BEFORE
REMOVING COPPER END CAPS.
3670-043
1
INDOOR UNIT
7
TO 3A / 4A / 5 / 6B
CABLE JOINER
ACTRONAIR
3-WAY RJ45 ***
(4070-012)
8
OPTIONAL
ZONE SENSOR CONNNECTION
(With 3 - Way Joiner)
TOTAL LENGTH OF ALL ZONING CABLE MUST NOT EXCEED 250 MTRS *
TOTAL CABLE LENGTH PER INDIVIDUAL ZONE MUST NOT EXCEED 100MTRS**
ITEM
DESCRIPTION
1 to 2
Indoor to Ultima Module factory fitted cable
0.60 m
2 to 3A
Ultima Module to Zone Barrel to Zone Controller
100 m
2 to 4A
Ultima Module to Zone Barrel to Zone Sensor
100 m
Ultima Module to Zone Barrel
100 m
Ultima Module to Zone Barrel to Zone Barrel to Zone Controller
100 m
2 to 5
2 to 6B
*
**
***
MAXIMUM CABLE LENGTH
2 to 7
Ultima Module to 3-Way Cable Joiner (ActronAir 4070-012)
0.175 m
7 to 3A
3-Way Cable Joiner to Zone Barrel to Zone Control
50 m
7 to 5
3-Way Cable Joiner to Zone Barrel
50 m
7 to 6B
3-Way Cable Joiner to Zone Barrel to Zone Barrel to Zone Controller
50 m
7 to 8
3-Way Cable Joiner to Zone Sensor
50 m
Long runs beside MAIN cable and TV antenna cables should be avoided where possible.
ActronAir CAT5E zone cables must be used:- 4070-013 (7m), 4070-018 (12m), 4070-014 (20m).
4070-020 (7m) CAT 5E zone cable supplied with Ultima Zone Barrel can also be used.
Always run the minimum possible length of zone cable.
2-Way Cable Joiner (2045-121) also available. Same max. cable length apply.
NOTE:
R
®
DIAGRAM SHOWN ABOVE IS A GENERAL PRESENTATION ONLY. REFER TO INDIVIDUAL UNIT WIRING DIAGRAM
FOR COMPLETE WIRING CONNECTION DETAILS.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
MAXIMUM CABLE LENGTH 120210
M-SERIES ULTIMA MODELS
MAXIMUM CABLE LENGTHS
C-SERIES TRI-CAPACITY MODELS
INDOOR UNIT
2
(OPTIONAL)
WALL CONTROLLER
ActronAir ® C7-4
SET BACK EVENT 1
AM
* 230V / 1Ph+N / 50Hz Supply.
Suggested Minimum Control Cable Size = 1mm2 .
Must comply with AS/NZS 3000 Wiring Rules.
2
(OPTIONAL)
DUCT BEAD SENSOR
AERSS
ON
o C TIME CLOCK ON OFF
PM
(OPTIONAL)
REMOTE SENSOR
AERSN
OFF
MON TUE WED THU FRI SAT SUN TIMER FILTER AH
CONT HIGH LOW
AUTO HEAT COOL RUN STAGE ROOM
FAN
AUTO
HEAT/COOL
CONTROL
SET
DISPLAY
TIMER
TIME CLOCK
PROGRAM
REPEAT
EXIT
CANCEL
RESTORE
TEMP
1
FAMILY
2
RUMPUS
3
MASTER BED
4
BEDROOM 1
sor
Sen
4
5
CONTROL INFORMATION
2 CORE 14/0.20 (0.44mm)
Shielded Data Cable
OUTDOOR UNIT
2 CORE 14/0.20 (0.44mm)
Shielded Data Cable
3
1
ACTRONAIR C7-4 WALL CONTROLLER
OR
THIRD PARTY CONTROL
THIRD PARTY CONTROL
INPUT TERMINALS
TO
OUTDOOR
PCB
ITEM
DESCRIPTION
1 to 2
Outdoor PCB to Indoor CVI (Not Applicable to Package Units - Factory Wired Already)
1 to 3
Outdoor PCB to Third Party Control
1 to 4
Outdoor PCB to Optional ActronAir C7-4 Wall Controller
4 to 5
Master Controller to Remote Sensor (Max. of 2 Optional Sensors)
MAXIMUM CABLE LENGTH (SEE NOTES 3 & 4)
50 m
Refer to Third Party Control Supplier
60 m
50 m each
NOTES:
1. TRI-CAPACITY SPLIT DUCTED UNIT SHOWN. SPECIFIED MAXIMUM CABLE LENGTHS ARE ALSO APPLICABLE TO PACKAGE UNITS (PKY MODEL SERIES).
2. DIAGRAM SHOWN ABOVE IS A GENERAL PRESENTATION ONLY. REFER TO INDIVIDUAL UNIT WIRING DIAGRAM FOR COMPLETE WIRING CONNECTION DETAILS.
2. DISCONNECT CCI INSIDE OUTDOOR UNIT WHEN USING ACTRONAIR C7-4 WALL CONTROLLER. REFER TO WIRING DIAGRAM FOR COMPLETE INSTRUCTIONS.
3. RECOMMENDED MAXIMUM CABLE LENGTH. LONG RUNS BESIDE MAINS CABLES OR TV ANTENNA CABLES SHOULD BE AVOIDED WHERE POSSIBLE.
2 CORE 14/0.20 (0.44MM) AND/OR 4 CORE 14/0.20 (0.44MM) SHIELDED DATA CABLE MUST BE USED.
4. TOTAL CUMULATIVE LENGTH OF ALL THE AGGREGATE CABLE LENGTHS MUST NOT EXCEED 160 M FOR C7-4 AND TWO REMOTE SENSOR INSTALLATION.
CONSULT ACTRONAIR ® FOR LONGER CABLE LENGTH REQUIREMENT.
NOTE:
DIAGRAM SHOWN ABOVE IS A GENERAL PRESENTATION ONLY. REFER TO INDIVIDUAL UNIT WIRING DIAGRAM
FOR COMPLETE WIRING CONNECTION DETAILS.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
R
®
MAXIMUM CABLE LENGTH 120210
C-SERIES TRI-CAPACITY MODELS
MAXIMUM CABLE LENGTHS
C - SERIES COMMERCIAL MODEL WITH THIRD PARTY 230VAC ZONE BARRELS
THIRD PARTY 230VAC ZONE BARRELS WITH CZ-1 ZONE KIT
(1-Zone Up To 4-Zone Options / Max. of 4 Third Party Zone Motors per System)
5
OPTIONAL
REMOTE SENSOR
AND
DUCT BEAD SENSOR
5
5
5
WALL CONTROLLER
C7-4
sor
Sen
AM
SET BACK EVENT 1
PM
o C TIME CLOCK ON OFF
2
OPTIONAL
ZONE KIT ^^
(CZ-1 230 VAC)
ON
OFF
MON TUE WED THU FRI SAT SUN TIMER FILTER AH
CONT HIGH LOW
AUTO HEAT COOL RUN STAGE ROOM
FAN
AUTO
HEAT/COOL
CONTROL
SET
3
DISPLAY
TIMER
TIME CLOCK
PROGRAM
REPEAT
EXIT
CANCEL
RESTORE
TEMP
230VAC CABLES
1
FAMILY
2
RUMPUS
3
MASTER BED
4
BEDROOM 1
2
•
WARNING
240 VOLTS
• 230VAC / 1Ph+N / 50Hz Supply.
Suggested Minimum Cable Size = 1mm2
Must comply with AS/NZS 3000 Wiring Rules.
ISOLATE POWER BEFORE
REMOVING COVER
4
2 CORE 14/0.20 (0.44mm)
Shielded Data Cable
CONTROL INFORMATION
2 CORE 14/0.20 (0.44mm)
Shielded Data Cable
CAUTION
1
TO
OUTDOOR
PCB
MODEL
CAUTION
ISOLATE ELECTRICAL SUPPLY
BEFORE REMOVING PANELS
AUTHORISED TECHNICIANS ONLY
R-410A
“CAUTION”
PLEASE ENSURE THERE IS
NO GAS / PRESSURE IN THE
FAN COIL UNIT BEFORE
REMOVING COPPER END CAPS.
3670-043
.
CAUTION
MEPS
CERTIFIED
MODEL
R-410A
A US T R A LI N MA D E
AUSTR ALI N OW NED
LIVE ELECTRICAL WIRING
AUTHORISED TECHNICIANS ONLY
INTERNAL CONTROL ISOLATOR FITTED
OUTDOOR UNIT
INDOOR UNIT
SPECIFIED MAXIMUM CABLE LENGTHS ARE ALSO APPLICABLE TO PACKAGE UNITS (PCA MODELS)
SPLIT INDOOR/OUTDOOR UNITS SHOWN ARE FOR ILLUSTRATION PURPOSES ONLY
ITEM
DESCRIPTION
1 to 2
Outdoor PCB to Master Controller
1 to 4
Outdoor PCB to Optional Zone Kit
1 to 5
Maximum Cumulative Cable Length, i.e. 1 to 5 (230VAC)
2 to 3
Master Controller to Remote Sensor (Max. of 2 Optional Sensors)
4 to 5
Optional Zone Kit to Zone Barrels (230VAC).
MAXIMUM CABLE LENGTH * ^
50 m (60 m without CZ-1)
40 m
Refer to Third Party Zone Barrel Supplier
50 m each
Refer to Third Party Zone Barrel Supplier
* Recommended maximum cable length.
Long runs beside Mains cables or TV antenna cables should be avoided where possible, 2 CORE 14/0.20 (0.44mm) Shielded Data Cable must be used.
^ Total Cumulative length of all the aggregate cable lengths must not exceed 500 meters. Consult ActronAir ® for longer cable length requirement.
^^ Total of 4 Third Party 240V Zone Barrels are allowed with CZ-1 230VAC.
NOTE:
R
®
DIAGRAM SHOWN ABOVE IS A GENERAL PRESENTATION ONLY. REFER TO INDIVIDUAL UNIT WIRING DIAGRAM
FOR COMPLETE WIRING CONNECTION DETAILS.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
MAXIMUM CABLE LENGTH 120210
C-SERIES SCA & PCA MODELS
J1
CLOSE OPEN CLOSE OPEN CLOSE OPEN
24V ZONE CARD
23002-2
RLY 2
MAINS
240V
AMZL2
RLY 3
RLY 1
ACT
OPTIONAL
4-ZONE 24 VOLT ZONE CARD
OPTIONAL ZONE CARD
AND TRANSFORMER
AND TRANSFORMER
(4Z-24V) (4Z-24V KIT)
RLY 4
COM
J2
24V AC
J3
NEUT
J4
TRANSFORMER
AMZ-24V
INSTALLATION WIRING DIAGRAM
M-SERIES CONTROLLER WITH OPTIONAL 4 ZONE 24 VOLT ZONE KIT (4Z-24V)
RLY
INDOOR BOARD
(AMIB)
HIGH
MID
SCRN
COM
PWR
KEY
COM
DATA
NEUT
ACT
NEUT
CONTROL INFORMATION
4 CORE DATA CABLE WITH SCREEN
4 CORE DATA CABLE WITH SCREEN
OPTIONAL REMOTE
WALL SENSOR 2
OPTIONAL REMOTE
WALL SENSOR 1
2 CORE DATA CABLE WITH SCREEN
CONDENSER CPU BOARD
EARTH
KEY
POWER
COMM.
NEUT
SENSOR
KEY
POWER
COMM.
ACT
SENSOR
HIGH
NEUT
NEUT
REV
HP
HP
COMP
NEUT
CORE&&EARTH
EARTH230VAC
240V CABLE
2 2CORE
CABLE
240V
AUX.
NEUT
ACT
HIGH
STANDARD
DIP SWITCH
SETTINGS
COOL ONLY ON
STAGE-2 ON
BOOST HEAT ON
WALL CONTROL
CONT. FAN
SINGLE SPEED
INDOOR FAN
240V
INDOOR
FAN
NEUT
ALL M SERIES CONTROLS
SET TO STANDARD
COMP
EXTRA LOW VOLTAGE
MANUAL INPUTS
AND OUTPUT
DUAL SPEED
INDOOR FAN
AUTO FAN
MANUAL INPUTS
OUTDOOR
COIL
SENSOR
FAN
HEAT
EXTRA LOW VOLTAGE DATA
MANUAL INPUTS
COMM/
AND OUTPUT
SCREEN
NOTE:
R
®
DIAGRAM SHOWN ABOVE IS A GENERAL PRESENTATION ONLY. REFER TO INDIVIDUAL UNIT WIRING DIAGRAM
FOR COMPLETE WIRING CONNECTION DETAILS.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
9005-008 120210
REVISION B
INSTALLATION WIRING DIAGRAM
M-SERIES CONTROLLER WITH OPTIONAL 8 ZONE 24VAC ZONE MODULE (8Z-24V)
NOTE: When mounting Zone Module to ceiling timber frame or other fixtures, use the supplied mounting screws.
IMPORTANT: When mounting Zone Module on the Fan Coil unit, use the supplied double adhesive tape.
(Do not screw to Fan Coil unit as it may cause internal damage to the unit.)
ACTRONAIR 24V
ZONE MOTOR
Zone 8
Zone 7
Zone 6
Zone 5
Zone 4
Zone 3
Zone 2
Zone 1
DATA
OPTIONAL INTEGRATED
8-ZONE MODULE
OPTIONAL
(8Z-24V)
CONTROL INFORMATION
8-ZONE 24VAC ZONE MODULE
(8Z-24V)
2 CORE & EARTH CABLE
(230VAC) - 2M LONG
NOTE:
2 CORE DATA CABLE
WITH SCREEN
- 2M LONG
INDOOR BOARD 8-ZONE MODULE COMPATIBLE
INDOOR BOARD
AMIB
NO
AMIB-D
NO
AMIB-8
YES
AMIB-D8
YES
AMIB-DV
YES
HIGH
MID
NEUT
(1)
YES
SCRN
COM
PWR
KEY
COM
DATA
GRND
NEUT
ACT
AMIB-P***
Note: (1) Available to all R-410A models, except ESP Ultima.
4 CORE DATA CABLE WITH SCREEN
4 CORE DATA CABLE WITH SCREEN
OPTIONAL REMOTE
WALL SENSOR 2
OPTIONAL REMOTE
WALL SENSOR 1
2 CORE DATA CABLE WITH SCREEN
OPTIONAL
EARTH
NEUT
SENSOR
KEY
POWER
COMM.
ACT
SENSOR
KEY
POWER
COMM.
HIGH
NEUT
NEUT
REV
HP
HP
COMP
NEUT
2 CORE & EARTH
240VCABLE
CABLE
2 CORE & EARTH
230VAC
240V
AUX.
NEUT
ACT
CONDENSER CPU BOARD
DATA
COMM/
SCREEN
NOTE:
R
®
DIAGRAM SHOWN ABOVE IS A GENERAL PRESENTATION ONLY. REFER TO INDIVIDUAL UNIT WIRING DIAGRAM
FOR COMPLETE WIRING CONNECTION DETAILS.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
9005-010 120210
REVISION B
INSTALLATION WIRING DIAGRAM
M-SERIES CONTROLLER WITH OPTIONAL 4 ZONE 230VAC ZONE CARD (AMZ)
NEUT
NC NO
NEUT
NEUT
NEUT
NC NO
NC NO
NC NO
EARTH
OPTIONAL
OPTIONAL ZONE
CARD (AMZ)
NEUT
ACT
4-ZONE 230VAC ZONE CARD
(AMZ)
RLY
INDOOR BOARD
(AMIB)
HIGH
MID
SCRN
COM
PWR
KEY
COM
DATA
ACT
NEUT
NEUT
CONTROL INFORMATION
4 CORE DATA CABLE WITH SCREEN
4 CORE DATA CABLE WITH SCREEN
OPTIONAL REMOTE
WALL SENSOR 2
OPTIONAL REMOTE
WALL SENSOR 1
2 CORE DATA CABLE WITH SCREEN
EARTH
KEY
POWER
COMM.
NEUT
SENSOR
KEY
POWER
COMM.
ACT
SENSOR
HIGH
NEUT
NEUT
REV
HP
HP
COMP
NEUT
CORE && EARTH
EARTH 240V
230VAC
CABLE
22CORE
CABLE
CONDENSER CPU BOARD
240V
AUX.
NEUT
ACT
HIGH
STANDARD
DIP SWITCH
SETTINGS
COOL ONLY ON
STAGE-2 ON
BOOST HEAT ON
WALL CONTROL
CONT. FAN
SINGLE SPEED
INDOOR FAN
240V
INDOOR
FAN
NEUT
ALL M SERIES CONTROLS
SET TO STANDARD
COMP
EXTRA LOW VOLTAGE
MANUAL INPUTS
AND OUTPUT
DUAL SPEED
INDOOR FAN
AUTO FAN
MANUAL INPUTS
OUTDOOR
COIL
SENSOR
FAN
HEAT
EXTRA LOW VOLTAGE DATA
MANUAL INPUTS
COMM/
AND OUTPUT
SCREEN
NOTE:
R
®
DIAGRAM SHOWN ABOVE IS A GENERAL PRESENTATION ONLY. REFER TO INDIVIDUAL UNIT WIRING DIAGRAM
FOR COMPLETE WIRING CONNECTION DETAILS.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
9005-004 120210
REVISION H
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
6
5
4
3
2
1
OFF
Not Used
Not Used
When not using Actron Air Optional
zone control panel ( CZ )
Not Used
Not Used
Remote sensor is to be
wired into SNS1
HIGH
NEUT
NEUT
REV
HP
HP
COMP
NEUT
EARTH
NEUT
ACT
This drawing remains the intellectual property of Actron Engineering Pty Ltd.
Reproduction, modification and/or distribution are prohibited without written consent.
COM/
SCREEN
DATA
WIRE CONNECTED TO THE SCREEN / COMMON TERMINAL
CABLE MUST BE 2 CORE 14/0.20 SCREENED CABLE WITH TRACE
NEUT
NEUT
EXTRA LOW VOLTAGE
ELECTRONIC
WALL CONTROL
N/C
HEAT
ZONE 4
NEUT
INTERNAL AUTO RESET
OVERLOAD PROTECTION
N/O
LOW
N/C
INDOOR FAN
NEUT
FAN
ZONE 3
IF USED
CAPACITOR
N/C
EXTRA LOW VOLTAGE
MANUAL INPUTS
AND OUTPUT
N/O
EARTH
Integral
Sensor
Power
SEN 1
SEN 2
N/C
HIGH
ZONE 2
N/O
COMP
SET TO
7-DAY
EARTH
STD 24HR TIMER
7-DAY TIMECLOCK
ZONE
MOTORS
EARTH
NEUT
EARTH
FAN
NEUT
HIGH
ACT
OPTIONAL
OPTIONAL
4-ZONE 230VAC
ZONE
CONTROL
ZONE CONTROL
INTERFACE
(CZ) PANEL
OFF
NO ZONES
REMOTE SNS 1
DATA
ZONE 1
ON
INTEGRAL SNS 6
5
4
ZONES 3
2
1
COMM.
240V
230VAC
VOLT
FAN
IF USED
OFF
Not Used
Not Used
When not using Actron Air Optional
zone control panel ( CZ )
Not Used
Not Used
Remote sensor is to be
wired into SNS1
DATA
230VAC NEUT
AUX.
AUX. ACT
ON
Not Used
Not Used
6
5
4
3
2
1
WALL CONTROL
FIELD WIRING
COMM.
CONDENSER CPU BOARD
D4CPU-P
CONDENSER
CPU BOARD
Not Used
Not Used
Internal or "Onboard"
Sensor is SNS1
When using Actron Air Optional
zone control panel ( CZ )
SINGLE
SINGLESTAGE
STAGECONDENSER
CONDENSERWIRING
WIRING
ON
Not Used
Not Used
When using Actron Air Optional
zone control panel ( CZ )
Not Used
Not Used
Internal or "Onboard"
Sensor is SNS1
C7 Controller will work on single
and 2 stage but not 3 stage units.
C7-3 Controller will work single,
2 and 3 stage units.
NOTE
CONTROL INFORMATION
OPTIONAL
SENSOR 2
OPTIONAL
SENSOR 1
INSTALLATION WIRING DIAGRAM
C-SERIES 1-STAGE CONTROLLER WITH OPTIONAL 230VAC ZONE CONTROL (CZ)
N/O
NEUT
R
®
WD0166 120210
This drawing remains the intellectual property of Actron Engineering Pty Ltd.
Reproduction, modification and/or distribution are prohibited without written consent.
HIGH
LOW
NEUT
NEUT
REV
HP
HP
LP
LP
COMP
NEUT
OUTDOOR
COIL
SENSOR
DUAL SPEED
INDOOR FAN
AUTO. FAN
MANUAL INPUTS
STAGE-2
BOOST HEAT ON
WALL CONTROL
CONT. FAN
SINGLE SPEED
INDOOR FAN
COOL ONLY ON
EARTH
ACT
INDOOR
FAN
MAINS
OUT
NEUT
LOW
HIGH
ACT
NEUT
EXTRA LOW VOLTAGE
ELECTRONIC
WALL CONTROL
EXTRA LOW VOLTAGE
MANUAL INPUTS
AND OUTPUT
COM.
DATA
15V
HEAT
FAN
COMP
7-DAY TIMECLOCK
24HR TIMER
230VAC
240V
NEUT
DIP SWITCH
SETTINGS
CONDENSER CPU BOARD
D4CPU-P
STAGE 2 PCB
SET TO
7-DAY
IF USED
NEUT
STAGE 1 PCB
BOOST
TERMINAL
STRIP
ON
Not Used
Not Used
OFF
Not Used
Not Used
ZONE 1
EARTH
NEUT
LOW
HIGH
OFF
ZONE 2
ZONE 3
OPTIONAL
OPTIONAL
4-ZONE
230VAC
ZONE
CONTROL
ZONE CONTROL
INTERFACE
PANEL
(CZ)
ON
INDOOR FAN
INTERNAL AUTO RESET
OVERLOAD PROTECTION
ZONE 4
CAPACITOR
IF USED
Integral
Sensor
NO ZONES
REMOTE SNS 1
CABLE MUST BE 2 CORE 14/0.20 SCREENED CABLE WITH TRACE
WIRE CONNECTED TO THE SCREEN / COMMON TERMINAL
ZONE
MOTORS
When not using Actron Air Optional
zone control panel ( CZ )
Not Used
Not Used
Remote sensor is to be
wired into SNS1
EARTH
Not Used
6
5
4
3
2
1
EARTH
N/C
When using Actron Air Optional
zone control panel ( CZ )
ACT
NEUT
NEUT
2-STAGE
CONDENSER WIRING
2-STAGE
CONDENSER
WIRING
STAGE2
ACT
N/O
Not Used
N/C
EARTH
NEUT
DATA
NEUT
Internal or "Onboard"
Sensor is SNS1
NEUT
COMM.
N/O
DATA
N/C
COMM.
N/C
INTEGRAL SNS 6
5
4
ZONES 3
2
1
N/O
CONTROL INFORMATION
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
N/O
FIELD WIRING
INSTALLATION WIRING DIAGRAM
C-SERIES 2-STAGE CONTROLLER WITH OPTIONAL 230VAC ZONE CONTROL (CZ)
R
®
WD0162 091102
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
Rev.
A
ORIGINAL
TO OCB
BOARDS
Description
10
9
8
7
6
5
4
3
2
1
TERM
BLUE
RED
PCR
OFF
Power
SEN 1
SEN 2
BLUE
RED
COMP1
GND
R
Date
By
REV
Pty Ltd. Reproduction, modification and/or distribution are prohibited
without written consent.
INFAN
20-05-2010 This drawing remains the intellectual property of Actron Engineering
GREY
ORANGE
NIGHT
KJP
BLUE
RED
COMP2
CCI
0-10V
COMP 0-10V
PWM INPUT
P5
COMP3
MANUAL INPUT
TERMINALS
24VAC
NEUT
AEDC1 - 2 CORE (14/0.2) ORANGE DATA CABLE WITH FOIL SCREEN
WC-1
ON
NO ZONES
REMOTE SNS 1
BOOST
HEAT
P4
ECONY
MANUAL INPUT
TERMINALS
24VAC
BOOST
INTEGRAL SNS 6
5
4
ZONES 3
2
1
+15V
CIU1
AUX3
AUX1
OPTIONAL
SENSOR 2
OPTIONAL
SENSOR 1
KJP
Drawn:
Description:
Base
Model No:
Variation Code:
CCI
OCB
TERM
WC-1
Variation:
LEGEND
20-05-2010
Date:
Drawing No:
9525-4900
D4 TRI-CAPACITY CONTROL SYSTEM WIRING DIAGRAM
FOR C7-4 WALL CONTROLLER
CAY470-700T
PKY470-700T
SEE NOTE "A"
DISCONNECT CABLES FROM OCB
BOARD AND TERMINAL BLOCK
ROLL UP AND STORE IN UNIT FOR
FUTURE SERVICE APPLICATIONS
IN
WALL CONTROL C-SERIES
NEUT
ECO
ON/OFF
EXTRA LOW VOLTAGE
MANUAL INPUTS
AND OUTPUT
RUN
®
FAULT
FIELD WIRING
AUX2
CONTROL INFORMATION
A
Revision
Size:
A4
INSTALLATION WIRING DIAGRAM
C-SERIES TRI-CAPACITY SYSTEM WITH C7-4 WALL CONTROLLER
9525-4900 120210
REVISION A
INSTALLATION WIRING DIAGRAM
LM-SERIES WALL CONTROLLER TEMPERATURE SENSOR WIRING
SPECIAL NOTES:
1. FOR BETTER RESPONDING TEMPERATURE CONTROL IT IS RECOMMENDED FITTING REMOTE WALL MOUNTED OR RETURN SENSORS.
2. PLEASE ENSURE THE DIP SWITCH IN THE OUTDOOR UNIT IS SELECTED TO 7-DAY.
3. DATA CABLE MUST BE 4 CORE 14/0.20 SCREENED CABLE.
4. REMOTE SENSOR CABLES MUST BE SCREENED WHEN RUN CLOSE TO ANY OTHER TYPE OF CABLES.
A: ONE ONBOARD SENSOR ONLY
B: ONE ONBOARD AND ONE REMOTE SENSOR
TO
OUTDOOR
UNIT
TO
OUTDOOR
UNIT
ACT
NEUT
ACT
EARTH
NEUT
DATA/R
COM/BL
S-2
S-1/G
EARTH
DATA/R
INDOOR BOARD
(AMIB)
COM/BL
S-1/G
PWR/R
COM/BK
SCRN
INDOOR BOARD
(AMIB)
S-2
KEY/Y
KEY/Y
WALL
CONTROLLER
PWR/R
COM/BK
WALL
CONTROLLER
SCRN
WC-1
WC-1
CONTROL INFORMATION
SENSOR
KEY
OPTIONAL
SENSOR
POWER
DO NOT
CONNECT
TRACE WIRE
AT WALL
CONTROL
COM
SENSOR
KEY
POWER
COM
DO NOT
CONNECT
TRACE WIRE
AT WALL
CONTROL
C: TWO REMOTE SENSORS WITH TWO WALL CONTROLLERS - MIMIC LOGIC
TO
OUTDOOR
UNIT
NOTES:
1. When using 2 wall controls, the second wall control’s
onboard sensor must be wired from the indoor board and
cannot be looped from the other wall control’s sensor terminal.
2. Use only one 7-day controller with dual (MIMIC LOGIC)
controller set up.
ACT
NEUT
EARTH
DATA/R
COM/BL
S-2
S-1/G
INDOOR BOARD
(AMIB)
KEY/Y
PWR/R
COM/BK
SCRN
WALL
CONTROLLER 1
OPTIONAL WALL
CONTROLLER 2
WC-1
WC-2
SENSOR
KEY
POWER
DO NOT
CONNECT
TRACE WIRE
AT WALL
CONTROL
COM
SENSOR
KEY
POWER
COM
OPTIONAL
SENSOR 1
OPTIONAL
SENSOR 2
NOTES:
1. WHEN REMOTE SENSOR IS USED AS SENSOR 1, DIS-ABLE ONBOARD SENSOR VIA DIP SWITCH 6 ON WALL CONTROL PAD.
(AS SEEN IN B CONFIGURATION)
2. WITH ZONED SYSTEM USING TWO SENSORS, SUCH AS IN DOMESTIC APPLICATIONS:
ZONE 1 IS ALWAYS ASSIGNED TO SENSOR 1 (EITHER WALL CONTROLLER ONBOARD SENSOR OR REMOTE SENSOR 1).
ZONE 2, 3 OR 4 CAN BE ASSIGNED TO SENSOR 1 OR SENSOR 2. SELECTION ENTRY VIA OPERATING INSTRUCTIONS 9005-006.
WHEN TWO SENSORS ARE IN CIRCUIT, THE COMBINED TEMPERATURE READINGS WILL BE AVERAGED.
3. NON ZONED SYSTEMS USING TWO SENSORS, SUCH AS COMMERCIAL APPLICATION:
THE COMBINED TEMPERATURE READINGS OF THE TWO SENSORS WILL BE AVERAGED.
4. TEMPERATURE SENSOR WIRINGS SHOWN ABOVE ARE FOR STANDARD SPLIT DUCTED AND ESP PLUS MODELS.
R
®
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
LM7 SENSOR WIRING 120210
REVISION 5
INSTALLATION WIRING DIAGRAM
C7 WALL CONTROLLER TEMPERATURE SENSOR WIRING
SPECIAL NOTES:
1. FOR BETTER RESPONDING TEMPERATURE CONTROL IT IS RECOMMENDED FITTING REMOTE WALL MOUNTED OR RETURN SENSORS.
2. PLEASE ENSURE THE DIP SWITCH IN THE OUTDOOR UNIT IS SELECTED TO 7-DAY.
3. DATA CABLE MUST BE 2 CORE 14/0.20 SCREENED CABLE.
4. REMOTE SENSOR CABLES MUST BE SCREENED WHEN RUN CLOSE TO ANY OTHER TYPE OF CABLES.
A: ONE ONBOARD SENSOR ONLY
B: ONE REMOTE SENSOR ONLY
C7 WALL
CONTROLLER
INTEGRAL SNS 6
5
4
ZONES 3
2
1
ON
C7 WALL
CONTROLLER
REMOTE SNS
INTEGRAL SNS 6
5
4
ZONES 3
2
1
ON
NO ZONE
OFF
REMOTE SNS
NO ZONE
OFF
SENS 1
SENS 2
SENS 1
SENS 2
COMMON
POWER
COMMON
POWER
CONTROL INFORMATION
ORANGE
SHEATH
DO NOT CONNECT
TRACE WIRE TO
WALL CONTROLLER
ORANGE
SHEATH
DO NOT CONNECT
TRACE WIRE TO
WALL CONTROLLER
FOIL
SCREEN
FOIL
SCREEN
DATA CABLE FROM
OUTDOOR UNIT CPU
DATA CABLE FROM
OUTDOOR UNIT CPU
DIPSWITCH SETTING
CHANGE DIPSWITCH 6 FROM INTEGRAL
SENSOR TO REMOTE SENSOR 1.
C: ONE ONBOARD AND ONE REMOTE SENSOR
C7 WALL
CONTROLLER
INTEGRAL SNS 6
5
4
ZONES 3
2
1
ON
D: TWO REMOTE SENSORS
C7 WALL
CONTROLLER
INTEGRAL SNS 6
REMOTE SNS
5
4
ZONES 3
2
1
ON
NO ZONE
OFF
REMOTE SNS
NO ZONE
OFF
SENS 1
SENS 2
SENS 1
SENS 2
COMMON
POWER
COMMON
POWER
ORANGE
SHEATH
DO NOT CONNECT
TRACE WIRE TO
WALL CONTROLLER
FOIL
SCREEN
ORANGE
SHEATH
DO NOT CONNECT
TRACE WIRE TO
WALL CONTROLLER
FOIL
SCREEN
DATA CABLE FROM
OUTDOOR UNIT CPU
DATA CABLE FROM
OUTDOOR UNIT CPU
DIPSWITCH SETTING
CHANGE DIPSWITCH 6 FROM INTEGRAL
SENSOR TO REMOTE SENSOR 1.
NOTES:
1. WHEN REMOTE SENSOR IS USED AS SENSOR 1, DIS-ABLE ONBOARD SENSOR VIA DIP SWITCH 6 ON WALL CONTROL PAD.
(AS SEEN IN B CONFIGURATION)
2. WITH ZONED SYSTEM USING TWO SENSORS, SUCH AS IN DOMESTIC APPLICATIONS:
ZONE 1 IS ALWAYS ASSIGNED TO SENSOR 1 (EITHER WALL CONTROLLER ONBOARD SENSOR OR REMOTE SENSOR 1).
ZONE 2, 3 OR 4 CAN BE ASSIGNED TO SENSOR 1 OR SENSOR 2. SELECTION ENTRY VIA OPERATING INSTRUCTIONS 9005-006.
WHEN TWO SENSORS ARE IN CIRCUIT, THE COMBINED TEMPERATURE READINGS WILL BE AVERAGED.
3. NON ZONED SYSTEMS USING TWO SENSORS, SUCH AS COMMERCIAL APPLICATION:
THE COMBINED TEMPERATURE READINGS OF THE TWO SENSORS WILL BE AVERAGED.
R
®
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
WD0032 120210
REVISION C
INSTALLATION WIRING DIAGRAM
C7 WALL CONTROLLER TEMPERATURE SENSOR WIRING
SPECIAL NOTES:
1. FOR BETTER RESPONDING TEMPERATURE CONTROL IT IS RECOMMENDED FITTING REMOTE WALL MOUNTED OR RETURN SENSORS.
2. PLEASE ENSURE THE DIP SWITCH IN THE OUTDOOR UNIT IS SELECTED TO 7-DAY.
3. DATA CABLE MUST BE 2 CORE 14/0.20 SCREENED CABLE.
4. REMOTE SENSOR CABLES MUST BE SCREENED WHEN RUN CLOSE TO ANY OTHER TYPE OF CABLES.
A: ONE ONBOARD SENSOR ONLY
B: ONE REMOTE SENSOR ONLY
C7 WALL
CONTROLLER
INTEGRAL SNS 6
5
4
ZONES 3
2
1
ON
C7 WALL
CONTROLLER
REMOTE SNS
INTEGRAL SNS 6
5
4
ZONES 3
2
1
ON
NO ZONE
OFF
REMOTE SNS
NO ZONE
OFF
SENS 1
SENS 2
SENS 1
SENS 2
COMMON
POWER
COMMON
POWER
CONTROL INFORMATION
ORANGE
SHEATH
DO NOT CONNECT
TRACE WIRE TO
WALL CONTROLLER
ORANGE
SHEATH
DO NOT CONNECT
TRACE WIRE TO
WALL CONTROLLER
FOIL
SCREEN
FOIL
SCREEN
DATA CABLE FROM
OUTDOOR UNIT CPU
DATA CABLE FROM
OUTDOOR UNIT CPU
DIPSWITCH SETTING
CHANGE DIPSWITCH 6 FROM INTEGRAL
SENSOR TO REMOTE SENSOR 1.
C: ONE ONBOARD AND ONE REMOTE SENSOR
C7 WALL
CONTROLLER
INTEGRAL SNS 6
5
4
ZONES 3
2
1
ON
D: TWO REMOTE SENSORS
C7 WALL
CONTROLLER
INTEGRAL SNS 6
REMOTE SNS
5
4
ZONES 3
2
1
ON
NO ZONE
OFF
REMOTE SNS
NO ZONE
OFF
SENS 1
SENS 2
SENS 1
SENS 2
COMMON
POWER
COMMON
POWER
ORANGE
SHEATH
DO NOT CONNECT
TRACE WIRE TO
WALL CONTROLLER
FOIL
SCREEN
ORANGE
SHEATH
DO NOT CONNECT
TRACE WIRE TO
WALL CONTROLLER
FOIL
SCREEN
DATA CABLE FROM
OUTDOOR UNIT CPU
DATA CABLE FROM
OUTDOOR UNIT CPU
DIPSWITCH SETTING
CHANGE DIPSWITCH 6 FROM INTEGRAL
SENSOR TO REMOTE SENSOR 1.
NOTES:
1. WHEN REMOTE SENSOR IS USED AS SENSOR 1, DIS-ABLE ONBOARD SENSOR VIA DIP SWITCH 6 ON WALL CONTROL PAD.
(AS SEEN IN B CONFIGURATION)
2. WITH ZONED SYSTEM USING TWO SENSORS, SUCH AS IN DOMESTIC APPLICATIONS:
ZONE 1 IS ALWAYS ASSIGNED TO SENSOR 1 (EITHER WALL CONTROLLER ONBOARD SENSOR OR REMOTE SENSOR 1).
ZONE 2, 3 OR 4 CAN BE ASSIGNED TO SENSOR 1 OR SENSOR 2. SELECTION ENTRY VIA OPERATING INSTRUCTIONS 9005-006.
WHEN TWO SENSORS ARE IN CIRCUIT, THE COMBINED TEMPERATURE READINGS WILL BE AVERAGED.
3. NON ZONED SYSTEMS USING TWO SENSORS, SUCH AS COMMERCIAL APPLICATION:
THE COMBINED TEMPERATURE READINGS OF THE TWO SENSORS WILL BE AVERAGED.
R
®
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®
WD0032 120210
REVISION C
CONTROLLER FAULT / FUNCTION DISPLAY CODES
CPU AND WALL CONTROLLER
RESIDENTIAL MODELS - SRA SRE SRD
FAULT / FUNCTION CODES
OUTDOOR
CPU
WALL CONTROLLERS
(LM7 / LM7-D / LM24)
0
-
Cooling Mode
1
-
Heating Mode
2
-
Heating Mode - Compressor run time > 20 min
3
HEAT blink every 8 seconds
Heating Mode - Defrost
4
LOW speed blink 30 seconds
Over Heat or Anti-Freeze Protection Mode (Low Capacity Mode)
5
HEAT blink every 8 seconds
Heating Mode - indoor coil pre-heat after defrost
6
E6
Fault discharge high temperature (low on refrigerant)
7
E7
Fault outdoor coil sensor (open or short circuit)
8
E8
Fault outdoor discharge sensor (open or short circuit)
9
E9
High or Low Pressure / Phase Error (3 Phase models only)
-
E5
Communication error between outdoor and indoor
-
E3
Fault room sensor(s) (open or short circuit)
-
E4
Fault indoor coil-in sensor (open or short circuit)
-
E2
Fault indoor coil-out sensor (open or short circuit)
FAULT / FUNCTION
CONTROL INFORMATION
COMMERCIAL MODELS - SCA PCA PCG PKY
FAULT / FUNCTION CODES
OUTDOOR
CPU
WALL CONTROLLERS
(C7-4)
0
-
Cooling Mode
1
-
Heating Mode - Normal
2
-
Heating Mode - Compressor run time > 20 min
3
HEAT blink every 8 seconds
Heating Mode - Defrost
5
HEAT blink every 8 seconds
Heating Mode - Indoor Coil Pre-Heat
7
E7
Fault, Open Circuit Outdoor Coil Sensor
8
E7
Fault, Short Circuit Outdoor Coil Sensor
9
E9
Fault, High - Low Pressure
-
E5
Communication error between outdoor and indoor
FAULT / FUNCTION
NOTES:
1. When unit is powered up, the first No. shown on LED display will be the CPU version No., then 8 followed by normal controller status codes.
2. Faults may not be displayed on the wall control until the fault occurs several times.
3. ** E9 can also indicate a phase error (incorrect phase rotation or phase loss).
4. Phase error will be indicated by a red light on the 3 phase sequence relay.
5. Phase correction must be applied to the incoming supply side.
R
®
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
Copyright © 2012 Actron Engineering Pty. Ltd.
®