DEFENCE WORKS SERVICES MINISTRY OF DEFENCE Defence Works Functional Standard Design and installation guide for specialist works on petroleum installations - electrical JANUARY 1995 COMPILED BY AIRFIELDS & BULK FUELS GROUP DEFENCE WORKS SERVICES LONDON : HMSO © Crown copyright 1995 Applications for reproductions should be made to HMSO First published 1994 ISBN 0 1 1 772690 7 Amendments Issue A, Rev 000 iii Foreword This document is for the use of Top Level Budget Holders (TLBHs) for application by the Project Sponsors, Property Managers (PROM), Establishment Works Consultants (EWC), Works Services Managers (WSM) and other parties involved in the design, selection and installation of electrical equipment within petroleum hazardous areas on the MOD estate. The principal users of the document are expected to be EWC specifiers and WSM designers, installers and maintainers for works which fall within the Property Services remit; and Project Managers, designers and installers for projects. The organisation of works on the MOD estate is determined by the value of the project or task. Over a certain value work is conducted as a Project under the control of a Project Sponsor, who directs the appointment of a Project Manager for all aspects of implementation. For work below the project value, the EWC, acting on behalf of the PROM, briefs the WSM who acts as Project Manager for the works. When completed, the work is accepted by the Property Manager on the basis of technical acceptance by the EWC. Maintenance tasks are conducted by the WSM, and are subject to audit by the EWC. The guidance given within this document is based upon British Standards, Health and Safety Guidance and Institute of Petroleum recommendations. Failure to implement the recommended practices given herein, could result in sub-standard equipment and workmanship in petroleum hazardous areas. The consequence of sub-standard equipment and workmanship is a very high probability of fire, explosion and possible loss of life. This Defence Works Functional Standard supersedes the following Department of Environment (DOE)/Property Services Agency (PSA) Electrical Design documentation, for petroleum hazardous installations : a. DOE/PSA Mechanical and Electrical Engineering Guide (MEG), Volume 3, Section 24, (1990). b. DOE/PSA Standard Specification (M&E) No.1 - Electrical Installations, (1985), Section 18. This Functional Standard was prepared under the patronage of the Defence Petroleum Distribution Committee (DPOLDC) for application to electrical installations within hazardous areas at bulk petroleum installations on the MOD estate. Guidance is given on apparatus standards for electrical installations in hazardous areas. In addition, general electrical standards which apply to both hazardous and non-hazardous areas, are cited in this Functional Standard. Examples are lightning protection, earthing and BS 7671: Requirements for Electrical Installations. This Functional Standard is not specifically directed to motor transport filling stations, however the electrical principles involved in this document afford guidance. iv Issue A, Rev 000 The design of motor transport filling stations should be in accordance with British Standards and Health and Safety Guidance documents. A DWS design guidance document to cater for MOD requirements at such installations is planned. Amendments to this Functional Standard will be advised by DWS Technical Bulletin, issued to PROM and TLBHs Works Staff. It is the responsibility of the user to check with the PROM or Project Sponsor if amendments have been issued. A sheet is provided for recording amendments. In addition, there is a feedback sheet at Annex B, for suggested changes or developments to the document. Technical advice and assistance on MOD petroleum matters can be obtained from DWS. Approaches may be through local DWS offices or directly to the petroleum Technical Authority, (DWS TA): Head of Bulk Petroleum Installations Room 121 Airfields and Bulk Fuels Group PO Box 1734, SUTTON COLDFIELD, West Midlands, B75 7QB. This DWS Functional Standard has been devised for use of the Crown and of its contractors in the execution of contracts for the Crown and, subject to the Unfair Contracts Tenns Act 1977, the Crown will not be liable in any way whatever (including but without limitation negligence on the part of the Crown its servants or agents) where the specification is used for other purposes. Notwithstanding that this document sets out guidance for specialist works on petroleum installations electrical, and is the MOD preferred solution, its use does not absolve a Project Manager from any responsibility for the design, neither does its existence constrain him from using alternatives, provided such alternatives can be demonstrated to provide a result of equal safety, quality and cost effectiveness. Issue A, Rev 000 Abbreviations AP (POL) APPET AVCAT AVGAS AVTUR BS BASEEFA CENELEC CSP DOE DPOLDC DWS EEx Ex EWC FSII GRP HSE IEE *IP IP JSP MOD PCP PET PM POL PROM PSA PVC SR&P LEL UEL TA TLBH's WSM XLPE vi Issue A, Rev 000 Authorised Person POL (current terminology) Authorised Person Petroleum (new terminology, to be introduced) Turbine Fuel, Aviation: High flash type Gasoline, Aviation: Grade 100/130 Turbine Fuel, Aviation: Kerosine type British Standard British Approval Service for Electrical Equipment in Flammable Atmospheres. European Committee for electrical standardisation Chlorosulphonated polyethylene Department of the Environment Defence Petroleum Distribution Committee Defence Works Services European Standard Certification Mark Health and Safety Executive Certification Mark Establishment Works Consultant Fuel System Icing Inhibitor Glass Reinforced Plastic Health and Safety Executive Institution of Electrical Engineers Institute of Petroleum Ingress Protection Joint Services Publication Ministry of Defence Polychloroprene Petroleum Project Manager Petroleum, Oil and Lubricant Property Manager Property Services Agency Polyvinylchloride Safety Rules and Procedures Lower Explosive Limit Upper Explosive Limit Technical Authority Top Level Budget Holders Works Services Manager Cross Linked Polyethylene Contents AMENDMENT SHEET ABBREVIATIONS FOREWORD CONTENTS 1 1 GENERAL REQUIREMENTS INTRODUCTION 1.1 AIM 1.2 1.3 DEFINITIONS 1.4 REGULATIONS 1.5 STANDARDS EQUIPMENT CERTIFICATION 1.6 1.7 TRAINING 1.8 DESIGN AND INSTALLATION CERTIFICATION 1.9 DRAWINGS, CALCULATIONS, MAINTENANCE AND OPERATING INSTRUCTIONS 1.10 MATERIALS 2 APPROACH TO THE SELECTION OF EQUIPMENT 2.1 HAZARDOUS PROPERTIES OF PETROLEUM 2.2 CLASSIFICATION OF HAZARDOUS AREAS 2.3 PROCEDURES FOR SELECTING ELECTRICAL EQUIPMENT 2.4 MARKING OF ELECTRICAL EQUIPMENT 3 21 ELECTRICAL WIRING SYSTEMS WITHIN HAZARDOUS AREA 3.1 ELECTRICAL SUPPLIES AND WIRING SYSTEMS WITHIN HAZARDOUS AREAS 3.2 WIRING SYSTEMS 4 EARTHING AND BONDING 4.1 GENERAL 4.2 ELECTRICAL INSTALLATIONS 4.3 LIGHTNING PROTECTION 4.4 EQUIPOTENTIAL BONDING 4.5 BONDING OF VEHICLES TO FIXED INSTALLATIONS 23 5 INSPECTION, TESTING AND MAINTENANCE OF ELECTRICAL EQUIPMENT WITHIN HAZARDOUS AREAS 27 5.1 5.2 GENERAL SAFE WORKING ANNEX A - COMPLETION & INSPECTION CERTIFICATE ANNEX B - CHANGE SUGGESTION FORM Issue A, Rev 000 13 29 34 vii Specialist works on petroleum installations - electrical Section 1 - General requirements Section 1 General requirements 1.1 INTRODUCTION DWS Functional Standard, Design and Installation Guide for Specialist Works on Petroleum Installations - Electrical, affords guidance and direction on the design, selection, and installation of electrical equipment within hazardous areas at fixed petroleum installations on the MOD estate. The Functional Standard guides the designer and installer of new facilities and the modifier and maintainer of existing facilities, in the precautions necessary to prevent ignition of an explosive atmosphere, caused by electrical equipment. 1.2 AIM The aim of this Functional Standard is to: a. Provide the details of design and installation standards for electrical equipment and associated works in fixed petroleum installations hazardous areas, within one document. b. Give guidance in the selection and installation of equipment, once the hazardous area has been defined. c. Provide a consistent approach in the selection of materials and workmanship, which will ensure similar solutions being constructed throughout the MOD estate. d. Provide the designer and installer with guidance to engineer safe and economic solutions, whilst ensuring compliance with the requirements of relevant British Standards and other applicable Codes of Practice. The document also assists the designer in the selection of materials, such as cables, which are used in non hazardous areas of petroleum installations. 1.2.1 Arrangement The document is arranged in the following manner, to achieve the aim : a. Section 1 includes the applicable standards, equipment certification, training of installation personnel, and the record information required for installations. Issue A, Rev 000 1 Specialist works on petroleum installations - electrical Section 1 - General requirements b. Section 2 comprises guidance on the approach to the selection of equipment for use in hazardous areas c. Sections 3,4 and 5 cover the detailed matters of electrical supplies and systems, earthing and bonding, and inspection and testing. 1.3 DEFINITIONS The terms used within this standard shall be read as having the definitions given below: Approval (and words derived therefrom): Shall mean qualified approval in writing by the Project Manager (PM) or Works Service Manager (WSM), unless stated otherwise, for the design or commodities concerned, at the time of consideration. Any such approval shall be given without prejudice to the requirement that formal acceptance of the Works shall be subject to such performance, testing and commissioning, as may be specified, and being to the satisfaction of the PM or WSM. Apparatus Group: Certain electrical apparatus for use in hazardous areas is allocated a group depending on its suitability for use with specific gases. Contractor: The company employed to carry out installation work on a site. Earth: The conductive mass of Earth, whose electrical potential at any point is conventionally taken as zero. Earth Electrode: A conductor or group of conductors in intimate contact with and providing an electrical connection to Earth. Establishment Works Consultant (EWC): The organisation responsible for the provision of specialist examinations, surveying, scheduling, financial assessments and overseeing services in support of the PROM of the Establishment. Equipotential Bonding: An electrical connection maintaining various exposedconductive-parts and extraneous conductive parts at the same potential. Explosive Atmosphere: A mixture with air, under atmospheric conditions, of flammable substances in the form of gas, vapour or mist in such proportions that it can be exploded by excessive temperatures, arcs or sparks. Equipment Certification: Equipment for use in Hazardous Areas is certified by one of a number of national testing authorities as meeting the requisite standard. This certification is arranged by the manufacturer of the equipment. Flash Point: The minimum temperature at which a material gives off sufficient vapour to form an explosive atmosphere within the apparatus used for flash point determination. Hazardous Area: An area where flammable or explosive gas or vapour-air mixture (often referred to as explosive gas-air mixtures) is, or may be expected to be, present 2 Issue A, Rev 000 Specialist works on petroleum installations - electrical Section 1 - General requirements in quantities which require special precautions to be taken against the risk of ignition. Ignition Temperature: The lowest temperature of a flammable gas or vapour at which ignition occurs. Non-hazardous Area: An area in which an explosive atmosphere is not expected to be present so that special precautions for the construction and use of the electrical equipment are not required. Project Manager (PM): An official of the MOD or commercial representative responsible for the purpose of management and administration of the works covered within this Functional Standard. For work within the remit of the WSM, the term PM shall be read as WSM. Property Manager (PROM): An MOD official responsible for conducting the day-to-day property management business at the establishment. Project Sponsor : The representative of the TLBH responsible for the delivery of the project through all stages. Preferred: This indicates the course of action to be pursued when there is a choice between acceptable alternatives. Technical Authority: Branch of DWS with responsibility for providing authorative technical works advice. Temperature Class: One of six values of temperature allocated to electrical apparatus derived from a system of classification according to the maximum surface temperature of the apparatus. Types of Protection: Measures applied in the construction of electrical apparatus to prevent the ignition of a surrounding explosive atmosphere by such apparatus. Works: This covers design, procurement, manufacture, installation, and relevant maintenance activities. Works Services Manager (WSM): The organisation responsible to the PROM for planning, organisation and managing operation, maintenance and repair of plant and facilities, and the design and construction of new works up to a specific value on the MOD establishment for which it is appointed. 1.4 REGULATIONS All work in and around petroleum hazardous areas must be carried out in accordance with the applicable MOD safety rules and procedures for work on petroleum installations. The current procedures are DOE/PSA Mechanical and Electrical Engineering Guide, Volume 8, Sections 51 and 53, which will be replaced by MOD Safety Rules and Procedures. When required by the MOD Safety Rules and Procedures, (SR&P), a covering Permit to Work (Petroleum) must be obtained from the responsible AP PET prior to the commencement of any work on or near a petroleum installation which either Issue A, Rev 000 3 Specialist works on petroleum installations - electrical Section 1 - General requirements contains, or has previously contained, petroleum products. Notwithstanding the receipt of a Permit to Work (Petroleum) in such cases, it shall be the responsibility of the contractor to ensure that the requirements for safety specified in the MOD SR&P are strictly complied with at all times. The completed work, and all aspects of the execution thereof, shall comply with all relevant latest enactments, statutory instruments, regulations and codes including the following where applicable: a. Factories Acts and Regulations made thereunder. b. Health and Safety at Work Act and Regulations made thereunder. c. Control of Pollution Act and Regulations made thereunder. d. Petroleum (Consolidation) Act and Regulations made thereunder. e. Home Office Model Code of Principles of Construction and Licensing Conditions for Premises Licensed under the Petroleum (Consolidation) Act 1928-Parts I and II. f. Standards listed in clause 1.5. g HMSO Publication 'Standard Fire Precautions for Contractors Engaged on Crown Works'. 1.5 STANDARDS The Works shall comply with the latest editions of appropriate standards including : a. 4 British Standards: BS308 Engineering drawing practice. BS 3429 Specification for sizes of drawing sheets. BS 3939 Graphical symbols for electric power, telecommunications and electronics diagrams. BS 4533 Section 102.51, Specification for luminaries with type of protection N. BS 4568 Parts 1 and 2: Steel conduit. BS 5000 Part 16: Rotating electrical machines with type of protection N. BS 5000 Part 17: Machines with flameproof enclosures. BS 5070 Engineering diagram drawing practice. Issue A, Rev 000 Specialist works on petroleum installations - electrical Section 1 - General requirements BS 5345 Code of practice for selection and maintenance of electrical apparatus for use in potentially explosive atmospheres (other than mining applications or explosive processing and manufacture). Part 1: General recommendations. Part 2: Classification of hazardous areas. Part 3: Installation and maintenance requirements for electrical apparatus with type of protection Flameproof enclosure. Part 4: Installation and maintenance requirements for electrical apparatus with type protection 'i'. Intrinsically safe electrical apparatus and systems. Part 5: Installation and maintenance requirements for electrical apparatus protected by pressurisation 'p' and by continuous dilution, for the pressurised room. Part 6: Installation and maintenance for electrical apparatus with type of protection Increased safety. Part 7: Installation and maintenance requirements for electrical apparatus with type of protection Part 8: Installation and maintenance requirements for electrical apparatus with type of protection 's'. Special protection. BS 5467 Specification for cables with thermosetting insulation for electricity supply for rated voltages up to and including 600/1000V and up to and including 1900/3300v. BS 5501 Electrical apparatus for potentially explosive atmospheres. Part 1: General requirements (EN 50014). Part 2: Oil immersion V (EN50015). Part 3: Pressurised apparatus "p" (EN50016). Part 4: Powder filling "q" (EN50017). Part 5: Flameproof enclosure "d" (EN50018). Part 6: Increased safety "e" (EN50019). Part 7: Intrinsic safety "i" (EN50020). Part 8: Encapsulation (EN50028). Part 9: Specification for intrinsically safe electrical systems "i" (EN50039). Note: EN numbers given in brackets are the European standard identical to the BS. BS 5958 Code of practice for control of undesirable static electricity. BS 6121 Part 1: Mechanical cable glands - specification for metallic glands. BS 6207 Specification for mineral insulated copper sheathed cables with copper conductors. Issue A, Rev 000 5 Specialist works on petroleum installations - electrical Section 1 - General requirements BS 6231 Specification for PVC insulated cables for switchgear and control gear. BS 6346 Specification for PVC insulated cables for power supply. BS 6480 Impregnated paper insulated lead/lead-alloy sheathed cables for rated voltages up to and including 3300V. BS 6651 Code of practice for protection of structures against lightning. BS 6656 Guide to the prevention of inadvertent ignition of flammable atmospheres by radio frequency ignition. BS 6941 Specification for electrical apparatus for explosive atmospheres with type of protection BS 7361 Cathodic protection. BS 7430 Code of practice for earthing. BS 7671 Requirements for electrical installations. Formerly the IEE wiring regulations sixteenth edition. BE EN 60529 Specification for degrees of protection afforded by enclosures (IP code). b. MOD Standards: JSP 317 Joint service safety regulations for the storage and handling of fuels and lubricants. Def Stan 01-5 Fuels, lubricants and associated products. DWS Functional Standard 05 Specification for specialist works on petroleum installations - Mechanical. DWS Functional Standard 07 The inspection, maintenance and testing of equipment installed at petroleum installations - Mechanical & Electrical. MOD Fire Standards. c. Institute of Petroleum (*IP) Model Code of Safe Practice for the Petroleum Industry: *IP Part 1 *IP Part 15 Electrical Safety Code. Area Classification Code for Petroleum Installations. Where there is a discrepancy between either the requirements of this document and those listed in clauses 1.4 and 1.5 herein, or between the documents listed in clauses 1.4 and 1.5 themselves, such discrepancy shall be referred to the PROM or WSM for resolution. 6 Issue A, Rev 000 Specialist works on petroleum installations - electrical Section 1 - General requirements It should be assumed that the resolution will be in favour of the most onerous requirement. 1.6 EQUIPMENT CERTIFICATION Equipment installed in petroleum hazardous areas must be certified in accordance with the relevant standard listed in clause 1.5. Equipment shall have a certification mark of a recognised testing authority; this verifies that the equipment is compliant with the relevant standard. Under no circumstance shall equipment which does not comply with clauses 1.4 and 1.5 be installed in petroleum hazardous areas. The Contractor shall provide current certificates of compliance for the equipment when so required by the PM or WSM. 1.7 TRAINING In order to satisfy the requirements of BS5345, Part 1, para 28: "The inspection, maintenance, testing and repair of apparatus, systems and installations should be carried out by persons whose training includes instruction on the various types of protection involved. Appropriate refresher training should be given from time to time." and the Memorandum of Guidance on the Electricity at Work Regulations 1989, Regulation 6, para 19: "the maintenance and repair of explosion protected equipment is a specialised field and should only be undertaken by those who have the necessary training." It is a requirement that only competent, suitably trained contractors and workers, undertake electrical works within petroleum hazardous areas. The PM or the WSM must judge the competency of the proposed contractor or worker prior to the work commencing. The PM or the WSM must also ensure that the applicable safety rules and procedures for electrical works on petroleum installations and general works on petroleum installations are brought to the attention of the contractor and worker. The electrical Contractor shall demonstrate that the worker proposed to conduct the work has a considerable appropriate knowledge, both theoretical and practical, of electrical equipment for hazardous areas and the associated risks. As part of the assessment of competency, and as a minimum, the worker shall have attended a course that covers the following main areas relating to electrical hazardous area works: Issue A, Rev 000 7 Specialist works on petroleum installations - electrical Section 1 - General requirements a. Ignition sources. b. Methods of protection. c. Earthing and bonding. d. Inspection and testing. e. Cable glanding. f. Safe working practices. Appropriate standards Certification of attendance and successful completion must be provided by the contractor to the Project manager or WSM. 1.8 DESIGN AND INSTALLATION CERTIFICATE Prior to handover and use of the installation the PM or WSM shall be in receipt of a suitably completed design, inspection and test certificate, as follows: a. The Completion and Inspection Certificate as detailed in BS 7671, Appendix 6. The Particulars of the Installation sheet, Appendix 6, is modified and included for use as Annex A of this Functional Standard. Note: Part 1 of Annex A is to be completed by the designer. Part 2 of Annex A is to be completed by the contractor /installer. Part 3 of Annex A is to be completed by the test/commissioning engineer. Part 4 is to be completed by the designer/contractor. b. Electrical design calculations, As-Installed drawings, test certification and operation and maintenance manuals. The number of copies of design calculations and certificates shall be determined by the PM or WSM. Alterations to existing installations must comply with BS 7671, Chapter 72. The procedure detailed in clauses 1.8.a and l.8.b above must be complied with, and a new certificate must be raised for the part of the installation affected by the modification. The new design must comply with this Functional Standard and the standards referenced within. 1.9 DRAWINGS, CALCULATIONS, MAINTENANCE AND OPERATING INSTRUCTIONS The Project Sponsor or the EWC, on behalf of the PROM for works within the Property services remit, determines the drawing, calculation, maintenance and operating instruction requirements. The timescale for submission of drawings, calculations, maintenance and operating documents will be determined by the PM or WSM. 8 Issue A, Rev 000 Specialist works on petroleum installations - electrical Section 1 - General requirements General layout drawings shall be drawn to a scale of 1:100 and more detailed drawings shall be to scales of 1:20; 1:10, 1:2 and 1:1, as appropriate. 1.9.1 Installation Drawings Detailed design drawings shall be produced by the designer. For a traditional contract where the installation contractor is responsible for procurement, the installation contractor shall carry out the necessary modifications to the design to accommodate the actual equipment purchased. a. b. The drawings as modified by the installation Contractor shall show the details of the contractor's proposals for the works and shall include everything necessary for the following purposes: (1) To illustrate in detail the arrangement of the various sections of the works and to identify components. (2) To integrate the works with the detail of the building and other installations works. (3) To show that the proposed installation and equipment is safely and adequately rated for duty. The installation drawings and documents shall include as appropriate: (1) General layout drawings showing the location of all equipment including cables, cable trays, conduits, trunking, ducting and earth electrodes. (2) Detailed layout drawings showing the location of all equipment including cables, cable trays, conduits, trunking and ducting in switchrooms and plant rooms. (3) Assembly drawings of factory built equipment and site built assemblies. (4) Detailed layout drawings showing the connection of cables, conduits and trunking to equipment. (5) System diagrams, circuit diagrams and wiring diagrams for all installations and equipment. (6) Hazardous area classification drawings. (See clause 2.1). (7) Calculations of short circuit levels and circuit protection settings. (8) Calculations of cable sizes and developed cable schedules. (9) Calculations of illumination levels and luminaire selection. Issue A, Rev 000 9 Specialist works on petroleum installations - electrical Section 1 - General requirements 1.9.2 As-Installed Drawings and Documents 10 a. These shall show the information necessary so that the installation can be safely operated, maintained, inspected and tested. The drawings shall incorporate the information necessary for the identification of the devices performing the functions of protection, isolation and switching, and their locations. The values of short circuit current and earth fault loop impedance shall be recorded on the appropriate system diagram/drawing. b. The drawings shall detail the items specified in clause 1.9.1 and 1.9.2. c. Circuit details including loading, origin, route, destination and where buried, the depth below finished ground level, shall be shown for each cable, conduit, trunking and ducting. Conductor size, material and the type of insulation of all cables shall be shown together with the number of cores in each cable or the number of cables in each conduit, trunking or ducting. Where identification is by colour of insulation or sheath, this shall be shown. Joints in draw boxes shall be shown. d. All earthing conductors, main equipotential bonding conductors, main earthing terminal, protective conductors and supplementary equipotential bonding conductors shall be identified with function, origin, route destination, conductor size and material, type of installation where buried and the depth below finished ground level. The test points and subsequent test readings shall be indicated. e. Earth electrodes shall be identified as to their type, dimension, material and depth below finished ground level. The nature of the soil and any treatment that has been given to it or special fill that has been used in the installation shall be identified. f. Details of each item of equipment including luminaires, shall include electrical characteristics, classification, degree of protection against ingress of solids and water, hazardous area classification, class of protection against corrosion, and manufacturer's name and reference. g. Drawings of the lightning protection system shall include identification of those elements of the building fabric used as air terminations and down conductors. Details of connections to structural steelwork or to the reinforcement of a concrete structure shall be included. Details of the earth electrodes are required. h. Each As-Installed drawing shall be suitable for micro-filming and shall be on durable translucent material, other than paper. The words "AS INSTALLED" shall be placed in 19mm block letters adjacent to the title block of each drawing together with the name of the site and the section of the works, the title of the installation, the date of completion of the works, the Authority's contract number and the name of the contractor. i. Drafts of each As-Installed drawing shall be submitted to the PM or WSM for Approval. Issue A, Rev 000 Specialist works on petroleum installations - electrical Section 1 - General requirements j. The number and format of final As-Installed drawings will be advised by the PM or WSM. 1.9.3 Maintenance and Operating Instructions For each electrical installation, system and equipment forming part of the works, the maintenance and operating instructions shall include: a. Certification and electrical design information as required by clause 1.8. b. A copy of inspection certificates and test records. c. Comprehensive instructions for switching on, operation, switching off and isolation. d. Instructions for maintenance, including frequency and spares required, to maintain the equipment/installation in a safe reliable condition. Maintenance, inspection and testing schedules shall be provided in the format indicated in DWS Functional Standard 07, unless otherwise specified. e. The names and addresses of equipment manufacturers and suppliers shall be provided together with the type, model reference, serial number, duty rating and the order number and date. Maintenance and operating instructions shall be indexed and contained in ring binders with stiff covers. The name of the site, Authority's contract number, and appropriate title shall be printed on the front cover and on the spine. A suitable index and reference to As-Installed drawings shall be provided within the binder. Copies of manufacturer's data may be incorporated in the binder to supplement the descriptions and instructions. Draft Operation and Instruction manuals will be submitted to the PM or WSM for approval. The number of final copies and timescale for handover will be advised by the PM or WSM. 1.10 MATERIALS Only new materials in accordance with the relevant BS shall be used unless otherwise specified. Where the PM or WSM directs the use of existing materials, these shall meet the specification for new materials. Issue A, Rev 000 11 Specialist works on petroleum installations - electrical Section 2 - Background for the selection of equipment Section 2 Background for the selection of equipment 2.1 GENERAL The classification of the hazardous area shall be completed by a suitably qualified and experienced engineer. The classification should be in accordance with JSP 317, which is based on the more detailed *IP Model Code of Safe Practice for the Petroleum Industry, Part 15, Area Classification. The Contractor will not be tasked to undertake the area classification, with the possible exception of design and construct contracts. In such circumstances the hazardous area classification shall be completed by a suitably qualified and experienced engineer. Once the area classification is complete and the area classification drawings have been produced, the design and selection of the electrical equipment can proceed. Clauses 2.2 and 2.3 offer elementary guidance on the hazardous properties of petroleum and the classification of hazardous areas. JSP 317 and *IP Part 15 are essential references for the area classification process. Clauses 2.4 and 2.5 deal with the selection and marking of electrical equipment. In some cases an installation is designed to accommodate Class I petroleum products even though only Class II petroleum products are to be stored. This is done to provide future flexibility. 2.2 HAZARDOUS PROPERTIES OF PETROLEUM Petroleum products produce flammable vapours which when mixed with air in certain proportions form a flammable atmosphere which will ignite if exposed to a source of ignition. A flammable/explosive atmosphere exists when the proportion of petroleum vapour in the air is between the Lower Explosive Limit (LEL) and the Upper Explosive Limit (UEL). Petroleum products are classified according to their minimum flash point. The classifications are in accordance with * IP Part 15, Appendix A. See Table 2.1. Class II and Class III petroleum products may be further sub-divided. The subdivision is dependent upon the temperatures at which the products are handled and stored. Class II(1) and Class III(1) refer to petroleum products stored and handled at temperatures below their flash point. Class II(2) and Class III(2) refers to petroleum product stored and handled at temperatures above their flash point. Issue A, Rev 000 13 Specialist works on petroleum installations - electrical Section 2 - Background for the selection of equipment TABLE 2.1 - Institute of Petroleum flash point classification of petroleum products For countries where ambient temperatures are high enough for the handling and storage temperatures of petroleum products to rise close to, or above, the product flash point, then petroleum products which fall into Class II(2) or Class III(2), should be treated as Class I. Based upon Clause 2.1 above, the fuels commonly handled on the MOD estate are detailed in Table 2.2. TABLE 2.2 - MOD Fuel data Note 1: It is possible that in certain circumstances, including hot climate installations, AVTUR could be stored at above its flash point, leading to a Class II (2) designation. 14 Issue A, Rev 000 Specialist works on petroleum installations - electrical Section 2 - Background for the selection of equipment Note 2: Although Class III products are not likely to reach their flashpoints in normal circumstances and thus do not give rise to a flammable vapour, they are treated as hazardous products in accordance with IP Part 15, Clause 2.12.3 in that the inside of the tank and an area around the vent are classified as hazardous zones. Specific guidance on petroleum characteristics are given in MOD, Defence Standard 01-5/Issue 10 (November 1993); Fuels, Lubricants and Associated Products. Further information is available from the DWS TA. 2.3 CLASSIFICATION OF HAZARDOUS AREAS Hazardous area classification zones are defined in BS5345 and presented in Table 2.3. TABLE 2.3 - Zone definitions (BS 5345) Zone 0 Zone in which an explosive atmosphere is continuously present, or present for long periods Zone 1 Zone in which an explosive atmosphere is likely to occur under normal operation. Zone 2 Zone in which an explosive atmosphere is not likely to occur in normal operation, and if it occurs will only exist for a short time. 2.4 PROCEDURES FOR SELECTING ELECTRICAL EQUIPMENT The selection of electrical equipment for use in petroleum hazardous zones is dependent upon the four following criteria: 2.4.1 The Selection of Equipment Suitable for the Particular Hazardous Zone BS 5345 determines that there are nine accepted types of protection for electrical apparatus. The relationships between the type of protection and zone are given in Table 2.4. Issue A, Rev 000 15 Specialist works on petroleum installations - electrical Section 2 - Background for the selection of equipment TABLE 2.4 - Types of hazardous area protection (BS5345) 0 Intrinsically safe, category in Zone 0) Special Protection (specifically certified for use 1 Intrinsically safe, category 'ia' or Flameproof enclosure 'd' Pressurised apparatus Special protection 's' Increased safety 2 Intrinsically safe, category 'ia' or 'ib' Flameproof enclosure 'd' Pressurised apparatus 'p' Special protection Increased safety 'e' Type 'N' Oil immersion 'o' Powder filling 'q' The preferred types of protection, for use on MOD estate hazardous areas are: a. Zone 0: In general, electrical equipment is not allowed in Zone 0 areas. In some cases intrinsically safe instrumentation is used in the vapour space of tanks, a Zone 0 area. b. Zone 1 Increased safety 'e' Flameproof enclosure 'd' {preferred first choice} {preferred second choice} c. Zone 2 Type 'N' Increased safety 'e' Flameproof enclosure 'd' {preferred first choice} {preferred second choice} {preferred third choice} The most economical solution that satisfies the requirements for safety should be chosen. 2.4.2 The Maximum Surface Temperature of the Equipment in Relation to the Ignition Temperature of the Petroleum Vapours/Product The maximum surface temperature of equipment (the temperature classification) selected must be below that of the ignition temperature of the petroleum product that the installation is designed to handle. Details of temperature classification for equipment are given in BS 5345 Part 1. Details are summarised in Table 2.5. 16 Issue A, Rev 000 Specialist works on petroleum installations - electrical Section 2 - Background for the selection of equipment TABLE 2.5 - Temperature classification (BS5345) T1 T2 T3 T4 T5 T6 450 300 200 135 100 85 Reference to BS 5345 Part 1 Table 7 gives the following temperature classifications: a. Kerosene - T3 (AVTUR, AVTUR/FSII, AVCAT/FSII). b. Gasoline (Petroleum) - T3 (AVGAS 100LL) BS 5345 does not give guidance for diesel fuel; this is treated as classification T3 as for the other fuels, based on *IP Part 15. Thus the "T" class for all equipment associated with all the fuels listed shall be "T3" or better, ie T4, T5 or T6. 2.4.3 The Apparatus Grouping The designations Group I and Group II are employed to differentiate between electrical equipment installed in mines and that installed in all other locations. Consequently, electrical apparatus for use on petroleum hazardous areas on MOD estate will be Group II. Within Group II, preferred protection type flameproof 'd' is sub-divided into groups IIA, IIB and IIC. Reference to BS 5345 Part 1 Table 7 gives the following equipment groups: a. Kerosene - IIA. b. Petroleum - IIA. BS5345 gives no guidance for diesel fuel; this will be treated as petroleum. All flameproof 'd1 equipment associated with all the fuels listed shall be Class IIA. Issue A, Rev 000 17 Specialist works on petroleum installations - electrical Section 2 - Background for the selection of equipment 2.4.4 The Environmental Conditions at the Installation Electrical equipment installed within hazardous areas shall be suitable for the environmental conditions to which it is exposed. This will include protection against: a. Ingress of solid bodies, water or liquids, BS EN 60529 (IP Number). The degree of ingress protection afforded by the enclosure is denoted by the letters IP followed by two numbers. Details of IP classification are given in Table 2.6. TABLE 2.6 - IP protection (BS EN 60529) 0 1 2 3 4 5 6 X No protection Entry up to 50mm Entry up to 12.5mm Entry up to 2.5mm Entry up to 1mm Dust proof Dust tight Characteristic numeral not required 0 1 2 3 4 5 6 7 8 X No protection Drip proof Rain proof up to 15° from vertical Rain proof up to 60° from vertical Splash proof Jet proof Cascade proof Proof against temporary immersion Proof against permanent immersion Characteristic numeral not required For outdoor locations, the degree of protection shall not be less than IP 55. For indoor locations, the degree of protection shall not be less than IP 52. b. 18 Corrosion. Issue A, Rev 000 Specialist works on petroleum installations - electrical Section 2 - Background for the selection of equipment c. Effects of exposure to the petroleum product. d. Effects of heat from adjacent plant. 2.5 MARKING OF ELECTRICAL EQUIPMENT The explosion-protection markings of electrical apparatus permits visual confirmation of the correct selection of suitable equipment for the hazardous zone. The markings are defined in the relevant BS and include the following details: a. The name of the manufacturer or his registered trade mark. b. The manufacturer's type identification. c. The symbol Ex or EEx, which indicates that the electrical apparatus corresponds to one or more of the types of protection as required by the appropriate standards. (See clause 2.5.g. below). d. The symbol for the type of protection used, either e. The symbol of the group of electrical apparatus, for protection type 'd', either IIA, IIB or IIC. f. The symbol indicating the temperature class. g. The number of the certificate and name or mark of the certifying authority. 'e' or 'N'. Note: If the type of protection complies with a British Standard, which mirrors a European Standard, for example BS5501 part I, and equivalent BS EN 50014, then the prefix to the type of protection code becomes 'EEx'. The Registered mark for the British Approval Service for Electrical Equipment in Flammable Atmospheres (BASEEFA) are the letters 'Ex' are located within a crown. Similarly equipment certified by Sira Certification Service would be marked with 'SCS'. h. Any other particular information, for example, IP protection or electrical rating. Issue A, Rev 000 19 Specialist works on petroleum installations - electrical Section 3 - Electrical supplies and wiring systems within hazardous areas Section 3 Electrical supplies and wiring systems within hazardous areas 3.1 ELECTRICAL SUPPLIES The electrical supply to a petroleum hazardous area shall be via underground cables except where cables necessarily have to exit the ground to reach above-ground equipment. When the installation is supplied via overhead circuit this shall terminate outside of the hazardous area and be routed via underground cable to the installation. Overhead conductors are not permitted within the hazardous area. Underground cables shall be protected against mechanical and environmental damage. LV cables shall be installed to a minimum depth of 500mm in open ground and under footpaths and 800mm under roadways unless otherwise specified by the PM. Warning tape shall be placed above each cable route mat is laid directly in the ground, at a depth of 300mm below finished ground level. Where ducting enters hazardous areas the cable ducts shall be sealed with a suitable petroleum resistant material to prevent the ingress of hazardous vapour or product. The petroleum installation electrical supply shall generally be 240V 50Hz, singlephase and neutral or 415/140V, 50Hz, 3 phase and neutral with the neutral solidly earthed at source. The electrical supply shall be TN-S or TT as defined in BS 7671. TN-C, TN-C-S and IT systems are not acceptable in classified hazardous areas. When the petroleum installation is fed from a dedicated substation or a feeder pillar feeding other installations, the new installation shall be constructed sufficiently far away from the electrical supply so that the electrical supply equipment is outside of the hazardous area. As a matter of good practice and economics, whenever possible, the electrical equipment should be located outside of the classified hazardous area. Standby power supplies, when provided, shall be located outside the hazardous area. The standby power supply shall be provided with suitable changeover and isolation facilities. Issue A, Rev 000 21 Specialist works on petroleum installations - electrical Section 3 - Electrical supplies and wiring systems within hazardous areas 3.2 WIRING SYSTEMS Cabling wiring systems for classified hazardous area installations shall be, in order of preference: a. Thermoplastic or XLPE insulated, lead alloy or thermoplastic sheathed, single steel wire armoured with polyvinylchloride (PVC), chlorosulphonated polyethylene (CSP) or polychloroprene (PCP) overall sheath - first. b. Mineral insulated copper sheathed cables - second. c. Paper insulated, lead/lead alloy sheathed, steel wire armouring and PVC/CSP/PCP overall sheath - third. d. Cables drawn into conduit - fourth. Where there is a possibility that cables may come into contact with product, they shall be lead alloy sheathed with either CSP or PCP overall sheath. All cables shall have copper conductors. Compression cable glands shall be brass or brass plated, weatherproof type, with inner and outer cable sheath seal and overall protective PVC boot. They shall be provided with a separate earthing tag that is secured with the gland fixing. Glands shall have metric fixing threads. Where compression glands are used with lead sheathed cables, the glands shall incorporate an internal lead sealing ring. For apparatus protection types "d" and cable glands shall be certified EEx "d" or For apparatus protection type "N", cable glands shall be either weatherproof or certified EEx "d" or "e". Conduit fittings for use in Zone 1 hazardous areas shall be certified enclosure protection type "d". Steel conduit and fittings shall be heavy duty, galvanised with metric threads. Conduits shall be threaded to the full length of the tapped entry on apparatus protection type "d". Conduits shall be sealed in accordance with BS 5345 Part 1, clause 16 where they enter apparatus protection type "e". Where paper insulated cables are used, terminated cable cores shall be sealed with heat-shrink sleeving that also seals the cores into the cable. 22 Issue A, Rev 000 Specialist works on petroleum installations - electrical Section 4 - Earthing and bonding Section 4 Earthing and bonding 4.1 GENERAL Flammable atmospheres found in the vicinity of petroleum installations necessitate special earthing and bonding procedures which by correct design and installation must provide adequate protection against fire and explosion. The employment of earthing and bonding can generally be sub-divided into three categories, those associated with the: a. Electrical installation. b. Protection against lightning. c. Equipotential bonding of structures, storage tanks, plant, pipelines and other non-electrical metallic parts. Details of potential causes of incendive conditions and the relevant precautionary guidance documentation are given in the Table 4.1. 4.2 ELECTRICAL INSTALLATION The design of the electrical system and installation shall be in accordance with BS 7671, BS 7430 and IP Part 1. As noted in clause 3.1 above, the electrical distribution system shall be TN-S. This requires a protective conductor(s) to connect the main source earth to the various items of electrical equipment. For all wiring systems, a separate dedicated protective conductor shall be provided as part of the wiring system and shall comprise: a. Copper conductor incorporated in an armoured flexible cable. b. Separately insulated copper conductor. The protective conductors shall be sized in accordance with BS 7671 Chapter 54. Issue A, Rev 000 23 Specialist works on petroleum installations - electrical Section 4 - Earthing and bonding TABLE 4.1 - Causes of incendive conditions Electrical equipment that is incorrectly selected for the hazardous environment, incorrectly installed, defective, incorrectly operated or poorly maintained BS7671 BS 7430 Static discharges between objects at different potentials BS 5958 Lightning discharges, direct or indirect BS6651 Stray electric currents eg cathodic protection systems Cathodically protected pipelines have an insulating flange at each end to prevent current loss to other installations. In a petroleum hazardous area exposed insulating flanges should be fitted with protective covers to avoid the risk of sparking. It is preferable to have insulating flanges sited in nonhazardous areas BS 7361 Radio frequency induction Structures that are constructed from conductive materials, for example, tanks, pipelines, metal gantries etc, can have a potential as a result of radio frequency induction. A potential difference between equipment can occur, which may result in incendive sparking and fire/explosion BS 6656 4.3 LIGHTNING PROTECTION The design of lightning protection systems is covered by BS 6651 and IP Part 1. a. 24 Although it is recognised that steel storage tanks and vessels are by their method of installation normally effectively earthed through their general contact with the mass of earth, extraneous piping, and cable connections, they shall be provided with lightning protection earth electrodes. Issue A, Rev 000 Specialist works on petroleum installations - electrical Section 4 - Earthing and bonding b. To facilitate the earthing of a metal storage tank, earthing bosses shall be welded onto the tank. The number and approximate positions are determined by the type, shape and size of the tank. Typical details are given in Table 4.2. TABLE 4.2 - Storage tank earthing bosses The earthing bosses shall be fabricated from flat carbon steel bar, 75mm x 30mm x 8mm drilled with an 8mm hole for connection of earth cable lug. Each boss shall be connected to either a dedicated earth electrode or an earthing grid as determined by die Contractor's design. If the storage tank is fitted with a cathodic protection system, for example, for tank bottom protection, then the tank earthing system shall comply with BS 7361, Section 4.5. 4.4 EQUIPOTENTIAL BONDING All non-current carrying conducting parts of an installation shall be effectively bonded together and to the main earth system to ensure that: a. The electric potential of one mass of metal cannot rise to dangerous levels with respect to another mass of metal, due to either wiring system faults or lightning strikes. b. Potentially hazardous static electric charges are safely dissipated. Issue A, Rev 000 25 Specialist works on petroleum installations - electrical Section 4 - Earthing and bonding 4.4.1 Examples Examples of metallic, conducting non-current carrying equipment that requires bonding together and to the earthing system are: a. Pipework. b. Tanks. c. Stairways, ladders, pipetrack bridges. d. Lighting columns and towers. e. Firefighting foam solution tanks, fire monitors. f. Cranes and hoists. The resistance to Earth at any point of any metallic, conducting non-current carrying equipment must be less than 10 ohms (Q). Pipelines that are connected by screwed joints or bolted flanges do not generally require bonding across the flange or joint. Bonding would only be required if the pipeline resistance to earth is greater than 10 Q, and this is due to high resistance across the bolted flange or screwed joint. Exceptionally however where long runs of pipe are needed they may require earthing at intervals to ensure that the resistance to earth of any part of the system of pipework does not exceed 10Q. Generally metallic conducting non-current carrying equipment which is cathodically protected must not be earthed. Special precautions may have to be taken to protect against earthing through cable armours to actuators and instruments, and conducting paths through pipe supports etc. Special earthing requirements for cathodically protected equipment are given in BS 7361. Concerning equipment fabricated from non-metallic materials, such as GRP, each case has to be considered on its merits, and guidance on earthing is given in BS 5958. For such equipment, the resistance to earth shall not exceed 106Q, but conducting metallic parts of such equipment shall have a resistance to earth of less than 10Q. 4.5 BONDING OF VEHICLES TO FIXED INSTALLATIONS Fuel dispense and receipt points shall be provided with a bonding cable. The bonding cable shall be connected to the fixed earthing network, which in turn will be connected to the dispense/receipt pipeline. The resistance from the end of the bonding cable to earth shall be less than 10Q. 26 Issue A, Rev 000 Specialist works on petroleum installations - electrical Section 5 - inspection, testing of electrical equipment within hazardous areas Section 5.0 Inspection, testing and maintenance of electrical equipment within hazardous areas 5.1 GENERAL Inspection, testing and maintenance of electrical equipment shall be undertaken in accordance with DWS Functional Standard 07. 5.2 SAFE WORKING All work on petroleum installations is controlled under the delegation of the Operating Authority, by the Authorised Person, AP (POL)/AP PET. Permits to work are issued by the AP (POL)/AP PET. Electrical permits are issued by the Authorised Person (Electrical) in coordination with the AP (POL)/AP PET. 5.2.1 Competent personnel Inspection, maintenance and testing in petroleum hazardous areas should only be undertaken by competent personnel who are : a. Familiar with the MOD Safety Rules and Procedures for Works on Petroleum Installations, and are familiar with the MOD Safety Rules and Procedures - Electrical. b. Experienced in inspection, maintenance and testing within petroleum hazardous areas. In addition, electrical personnel should be trained and experienced in: c. The principles and details of the various types of explosion protection. d. Related installation practice. e. The general principles of the selection of equipment for installations in hazardous areas. Earth fault loop impedance tests, high current continuity tests and prospective short circuit current tests are not to be carried out in hazardous areas. Such tests can introduce current and/or voltages in parts of the installation they might not be expected, due to bonding of extraneous conductive parts and Issue A, Rev 000 27 Specialist works on petroleum installations - electrical Section 5 - inspection, testing of electrical equipment within hazardous areas lightning protection systems. This could result in incendive sparking in areas or parts of the installation not covered by the permit to work. 28 Issue A, Rev 000 Specialist works on petroleum installations - electrical Annex A - Design, contractor installation and inspectiont test certificate Annex A Design, contractor installation and inspection\test certificate Electrical design certification - completed by electrical designer. Installation certification - completed by the contractor /installer. Test/commissioning certification - completed by test/commissioning engineer eg contractor/designer. Installation particulars - completed by the designer/contractor. Issue A, Rev 000 29 Specialist works on petroleum installations - electrical Annex A - Design, contractor installation and inspection\test certificate PART 1 - DESIGN CERTIFICATION Client: Address: DESIGN I/We being the person(s) responsible (as indicated by my/our signatures below) for the Design of the electrical installation, particulars of which are described in part 4 of this form CERTIFY that the said work for which I/we have been responsible is to the best of my/our knowledge and belief in accordance with the BS 7671, Regulations for Electrical Installations published by the Institution of Electrical Engineers, 16th Edition, amended to (date.......), and any other relevant standards particular to the installation, except for the departures, if any, stated in mis Certificate. The extent of liability of the signatory is limited to the work described in part 4 as the subject of this Certificate. For the Design of the Installation: Name (In Block Letters): Position: For and on behalf of: Address: Signature: 30 Date: Issue A, Rev 000 Specialist works on petroleum installations - electrical Annex A - Design, contractor installation and inspection\test certificate PART 2 - INSTALLATION CERTIFICATION Client: Address: CONSTRUCTION I/We being the person(s) responsible (as indicated by my/our signatures below) for the Construction of the electrical installation, particulars of which are described in part 4 of this form CERTIFY that the said work for which I/we have been responsible is to the best of my/our knowledge and belief in accordance with the BS 7671, Regulations for Electrical Installations published by the Institution of Electrical Engineers, 16th Edition, amended to (date.......), and any other relevant standards particular to the installation, except for the departures, if any, stated in this Certificate. The extent of liability of the signatory is limited to the work described in part 4 as the subject of this Certificate. For the Construction of the Installation: Name (In Block Letters): Position: For and on behalf of: Address: Signature: Date: Issue A, Rev 000 31 Specialist works on Annex A - Design, contractor installation and inspection\test certificate petroleum installations - electrical PART 3 - TEST/COMMISSIONING CERTIFICATION Client: Address: INSPECTION AND TEST I/We being the person(s) responsible (as indicated by my/our signatures below) for the Inspection and Test of the electrical installation, particulars of which are described in part 4 of this form CERTIFY that the said work for which I/we have been responsible is to the best of my/our knowledge and belief in accordance with the BS 7671, Regulations for Electrical Installations published by the Institution of Electrical Engineers, 16th Edition, amended to (date.......), and any other relevant standards particular to the installation, except for the departures, if any, stated in this Certificate. The extent of liability of the signatory is limited to the work described in part 4 as the subject of this Certificate. For the Inspection and Test of the Installation: Name (In Block Letters): Position: For and on behalf of: Address: I RECOMMEND that this installation be further inspected and tested after an interval of not more than years. Signature: 32 Date: Issue A, Rev 000 Specialist works on petroleum installations - electrical Annex A - Design, contractor installation and inspection\test certificate PART 4 - PARTICULARS OF THE INSTALLATION A full record of the details of the installation should be made including : A description of the installation. The earthing system adopted for electrical equipment and the results of the earth resistance measurement taken. Characteristics of the supply, short circuit currents, protective measures, overcurrent devices and circuit breakers. Details of the equipotential bonding system and the size of conductors installed. Details of any departures from the Wiring Regulations or other relevant standards. Hazardous area details. note: Part 4 is initially completed by the designer and amended by the contractor to reflect any changes that may have occurred during the construction/installation process. Number of additional pages Issue A, Rev 000 33 Specialist works on petroleum installations - electrical Annex B - Change suggestion form Annex B Change suggestion form 34 Issue A, Rev 000 Specialist works on petroleum installations - electrical Annex B - Change suggestion form Date: Originator: Ref: Section: Page: Change Detail: Continuation Sheet included ? Y N Continuation Sheet included ? Y N Reason: Ref: Action: Action Date: Approved: Actioned: 35 Issue A, Rev 000 Printed in the United Kingdom for HMSO Dd. 298037 C35 3/95 59226