Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 KRUEGER Single-Duct and Retro Fit Terminal Units PRE-INSTALLATION General — The LMHS, RVE, and SVE single duct terminals are available with factory installed Pneumatic, Analog electronic, and DDC control options. Figure 1 shows a basic LMHS unit. Figure 1 – LMHS Unit (with pneumatic controls shown) STORAGE AND HANDLING — Inspect for damage upon receipt. Shipping damage claims should be filed with shipper at time of delivery. Store in a clean, dry, and covered location. Do not stack cartons. When unpacking units, care should be taken that the inlet collars and externally mounted components do not become damaged. Do not lift units using collars, inlet flow sensors, or externally mounted components as handles. Do not lay uncrated units on end or sides. Do not stack uncrated units over 6 ft high. Do not handle control boxes by tubing connections or other external attachments. Table 1 shows component weights. Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 INITIAL INSPECTION — Once items have been removed from the carton, check carefully for damage to duct connections, inlet probes or controls. File damage claim immediately with transportation agency and notify Factory. UNIT IDENTIFICATION — Each unit is supplied with a shipping label and an identification label: INSTALLATION PRECAUTION — Check that construction debris does not enter unit or ductwork. Do not operate the central-station air-handling fan without final or construction filters in place. Accumulated dust and construction debris distributed through the ductwork can adversely affect unit operation. SERVICE ACCESS — Provide service clearance for unit access. CODES — Install units in compliance with all applicable code requirements. UNIT SUSPENSION — See Fig. 3 for optional unit suspension details: Warranty – All Krueger furnished items carry the standard 1-year limited warranty from the date of shipment. Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 MAINTENANCE No periodic preventative maintenance required, unless called for by specific control sequence. CONTROL ARRANGEMENTS The LMHS single duct and RVE/SVE retrofit units are offered with a wide variety of factorymounted controls that regulate the volume of air delivery from the unit and respond to cooling and heating load requirements of the conditioned space. Stand-alone controls will fulfill the thermal requirements of a given control space. These devices are available in both pneumatic and electronic arrangements. A number of DDC (Direct Digital Controls) control packages by others are available for consignment mounting, as indicated. Each control approach offers a variety of operating functions; a control package number identifies combinations of control functions. The following listings contain the basic function arrangements for each control offering. Because of the variety of functions available, circuit diagrams, operating sequences, and function descriptions are contained in separate Application Data publications. Refer to the specific control publication for details. Direct Digital Electronic Control Arrangement (Field Supplied) — Control packages are field supplied for factory mounting, unless otherwise noted. All DDC control arrangements include a flow sensor, control enclosure and optional 24-volt transformer. Contact factory for details about mounting field-supplied controls. Analog Electronic Control Arrangement — Pressure independent control packages are available without supplemental heat, with on/off hot water or electric heat, proportional hot water heat, or with cooling/heating automatic changeover control. All analog control arrangements include an inlet flow sensor, 24V transformer (optional), control enclosure and wall thermostat with LCD display. 2100: Heating control 2101: Cooling control 2102: Cooling with on/off electric heat control 2103: Cooling with on/off hot water heat control 2104: Cooling/heating automatic changeover control 2105: Cooling with proportional hot water heat control 2110: Cooling with Solid State LineaHeat Proportional heat control 2111: Cooling/Heating with automatic change over with up to 3 stages of electric heat control 2113: Cooling/Heating with automatic change over with Solid State LineaHeat Proportional heat 2115: Upstream static pressure monitoring 2116: Downstream static pressure monitoring Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 Pneumatic Control Arrangement — All control packages are pressure independent (unless otherwise noted) and available with or without hot water heat, dual maximum airflow, heating and cooling maximum airflow and dual minimum airflow. All control arrangements include a standard linear inlet flow sensor. 1100 (Actuator only): DA-NC Pressure dependent control 1101 (Actuator only): RA-NO Pressure dependent control 1102 (Single function controller): DA-NO with or without hot water or electric heat 1103 (Single function controller): RA-NC with or without hot water or electric heat 1104 (Multi-function controller): DA-NO with or without hot water or electric heat 1105 (Multi-function controller): DA-NC with or without hot water or electric heat 1106 (Multi-function controller): RA-NO with or without hot water or electric heat 1107 (Multi-function controller): RA-NC with or without hot water or electric heat 1108 (Dual Maximum Control): DA-NO with or without hot water or electric heat 1109 (Heating/Cooling Maximum Control): DA-NO with or without hot water or electric heat 1110 (Dual Minimum Control): DA-NO with or without hot water or electric heat PNEUMATIC CONTROL LEGEND DA: Direct acting thermostat RA: Reverse acting thermostat NO: Normally open damper position NC: Normally closed damper position Single function controller: Provides single function, i.e., DA-NO Multi-function controller: Capable of providing DA-NO, DA-NC, RA-NC or RA-NO functions No Control 0000: Unit with no control box. D000: Unit with control enclosure and transformer. D001: Unit with control enclosure and no transformer. Also used for control enclosure and electric heat. INSTALLATION Step 1 — Install Unit 1. Move unit to installation area. Remove unit from shipping package. Do not handle by controls, flow sensors or damper extension rod. 2. Optionally, the unit may have factory-installed hanger brackets. 3. Suspend units from building structure with straps, rods, or hanger wires. Secure the unit and level it in each direction Step 2 — Make Duct Connections 1. Install supply ductwork on each of the unit inlet collars. It is recommended that 3 duct diameters of straight duct are supplied to the inlet of the unit. An elbow put at the inlet of the unit will create turbulence at the inlet making it difficult for the flow sensor to accurately measure the airflow. Check that air-supply duct connections are airtight and follow all accepted medium-pressure duct installation procedures. (Refer to Table 2a – LMHS, 2b – RVE, 2c – SVE for pressure and flow data). 2. Install the discharge ducts. Fully open all balancing dampers. For optimal performance it is recommended that 3 inlet diameters of straight duct be provided to the unit. Ninety degree elbows or tight radius flexible duct immediately upstream of inlet collar should be avoided as these can affect the balancing of the unit. Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 Model: LMHS Basic Pressure and Flow Data Minimum Airflow (CFM) Inlet Size (area ft2) Maximum Airflow (CFM) Cooling Only or with Hot Water Electric Heat 4 (0.09) 230 40 55 5 (0.14) 360 62 85 6 (0.20) 515 90 110 7 (0.27) 700 121 140 8 (0.35) 920 160 190 9 (0.44) 1160 201 240 10 (0.55) 1430 248 300 12 (0.78) 2060 357 425 14 (1.07) 2800 486 580 16 (1.40) 3660 634 750 22 (2.63) 7000 1212 1800 Electric Heat* Max Kw vs. CFM @55F EAT 55 110 150 230 85 140 250 360 100 250 400 520 140 330 550 700 190 440 700 920 240 550 900 1160 250 700 1100 1450 425 1000 1600 2060 580 1375 2100 2800 750 1775 2800 3660 1800 3300 5300 7000 1.1 2.2 3! 3! 1.7 2.8 5! 5! 2 5.1 7.5! 7.5! 2.9 6.7 9.5! 9.5! 3.9 9.1 13 ! 13 ! 4.9 11.3 16 ! 16 ! 5.1 14.3 21 ! 21 ! 8.7 20.6 30! 30! 11.9 28.2 36 ! 36 ! 15.4 36 ! 36 ! 36 ! 36 ! 36 ! 36 ! 36 ! Minimum Inlet Static Pressure (Unit & Heat Pressure Drop) Velocity Press. Basic Unit Basic w/ 1R Coil Basic w/ 2R Coil Basic w/ 3R Coil Basic w/ 4R Coil Basic + Heater** VPS PS PS PS PS PS PS 0.02 0.10 0.18 0.43 0.02 0.06 0.21 0.43 0.02 0.10 0.25 0.42 0.02 0.09 0.25 0.40 0.02 0.09 0.23 0.39 0.02 0.08 0.23 0.38 0.01 0.08 0.21 0.36 0.01 0.08 0.20 0.33 0.01 0.07 0.16 0.29 0.01 0.06 0.14 0.24 0.02 0.07 0.17 0.30 0.01 0.05 0.10 0.24 0.01 0.03 0.10 0.21 0.01 0.04 0.10 0.17 0.01 0.04 0.10 0.16 0.01 0.04 0.10 0.17 0.01 0.04 0.10 0.17 0.01 0.04 0.10 0.17 0.01 0.04 0.10 0.17 0.01 0.04 0.10 0.18 0.01 0.04 0.10 0.17 0.01 0.04 0.10 0.17 0.02 0.06 0.12 0.28 0.02 0.05 0.15 0.31 0.01 0.09 0.22 0.38 0.01 0.08 0.22 0.36 0.02 0.12 0.29 0.51 0.02 0.09 0.25 0.42 0.02 0.13 0.32 0.56 0.02 0.14 0.35 0.58 0.02 0.13 0.30 0.53 0.02 0.14 0.34 0.58 0.05 0.18 0.45 0.79 0.02 0.07 0.13 0.31 0.02 0.06 0.19 0.40 0.02 0.13 0.34 0.57 0.02 0.12 0.33 0.53 0.03 0.19 0.47 0.81 0.03 0.14 0.38 0.64 0.03 0.21 0.53 0.91 0.04 0.22 0.57 0.95 0.04 0.21 0.48 0.85 0.04 0.22 0.56 0.95 0.09 0.30 0.77 1.35 0.02 0.08 0.15 0.35 0.03 0.07 0.24 0.49 0.03 0.17 0.45 0.75 0.03 0.16 0.44 0.71 0.05 0.25 0.64 1.11 0.04 0.19 0.52 0.86 0.04 0.29 0.73 1.26 0.06 0.31 0.80 1.32 0.05 0.28 0.66 1.17 0.06 0.31 0.77 1.32 0.13 0.42 1.09 1.91 0.02 0.09 0.16 0.39 0.03 0.09 0.28 0.58 0.03 0.22 0.56 0.94 0.04 0.20 0.54 0.88 0.06 0.32 0.82 1.42 0.05 0.24 0.66 1.09 0.05 0.38 0.93 1.62 0.07 0.40 1.02 1.69 0.06 0.36 0.84 1.49 0.07 0.40 0.99 1.69 0.16 0.55 1.41 2.46 0.01 0.05 0.10 0.24 0.01 0.03 0.10 0.21 0.01 0.04 0.10 0.17 0.01 0.04 0.10 0.16 0.01 0.04 0.10 0.17 0.01 0.04 0.10 0.17 0.01 0.04 0.10 0.17 0.01 0.04 0.10 0.17 0.01 0.04 0.10 0.18 0.01 0.04 0.10 0.17 0.01 0.04 0.10 0.17 Notes: 1.) ∆ PS is the difference in static pressure across the assembly, with the damper fully open. 2.) To obtain Total Pressure, add the Velocity Pressure for a given CFM to the Static Pressure drop (D PS) of the Example: Pt for a Size 8 Basic Unit @925 CFM = 0.39 + 0.17 = 0.56 3.) Max Kw shown assumes 55F entering air and is limited by unit's selected voltage, phase and max capacity. Minimum cfm for electric heat is based on UL/ETL listings. Note: Diffuser performance will likely be poor at this low flow rate. 4.) Maximum discharge temperatures with Electric Heat are set at 120F by the National Electric Code. * The ASHRAE Handbook of Fundamentals does not recommend a discharge temperature exceeding 90F ** A minimum 0.10” discharge static pressure is required to ensure steady operation for the airflow switch in the electric heater *** Minimums for DDC by others are the responsibility of the controls' provider. ! Max Kw is limited by design Table 2a - LMHS Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 Model: RVE Inlet Size (area ft2) 4 (0.09) 5 (0.14) 6 (0.20) 7 (0.27) 8 (0.35) 9 (0.44) 10 (0.55) 12 (0.78) 14 (1.07) 16 (1.40) Notes: 1.) 2.) Maximum Airflow (CFM) 230 360 515 700 920 1160 1430 2060 2800 3660 Minimum Airflow (CFM) Flow Rate Min Ps CFM "WG 40 62 90 121 160 201 248 357 486 634 40 0.007 103 0.048 167 0.126 230 0.239 62 0.008 161 0.052 261 0.137 360 0.261 90 0.007 233 0.050 377 0.131 520 0.249 120 0.007 330 0.056 525 0.142 700 0.252 160 0.008 440 0.059 675 0.138 920 0.256 200 0.008 550 0.058 875 0.146 1160 0.257 250 0.008 675 0.056 1075 0.142 1430 0.252 360 0.008 1000 0.060 1550 0.143 2060 0.253 480 0.008 1375 0.063 2125 0.149 2800 0.259 630 0.008 1775 0.060 2725 0.141 3660 0.255 ∆ Ps is the difference in static pressure across the assembly, with the damper fully open. Minimum CFM value is based on a signal of 0.03 in w.g. differential pressure of the inlet Table 2b - RVE Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 Model: SVE Inlet Size Maximum Airflow (CFM) Minimum Airflow (CFM) A 456 79 B 656 114 C 875 152 D 1458 253 E 2042 354 F 1969 351 G 2188 379 H 3281 568 J 3938 682 K 5104 884 L 6563 1137 M 6417 1111 N 7875 1364 P 10938 1894 R 14583 2526 Flow Rate Min DPs CFM "WG 75 155 235 315 114 225 350 473 152 350 575 786 253 475 675 902 354 675 1000 1328 341 650 950 1270 379 725 1075 1435 568 1175 1775 2414 682 1475 2300 3121 884 2225 3550 4923 1137 2925 4725 6563 1111 2850 4625 6417 1364 3525 5650 7875 1894 4875 7875 10938 2526 6500 10475 14583 0.057 0.242 0.556 1.000 0.058 0.226 0.548 1.000 0.037 0.198 0.535 1.000 0.079 0.278 0.561 1.001 0.071 0.258 0.567 1.000 0.072 0.262 0.560 1.001 0.070 0.255 0.561 1.000 0.055 0.237 0.541 1.000 0.048 0.223 0.543 1.000 0.032 0.204 0.520 1.000 0.013 0.085 0.222 0.429 0.017 0.110 0.290 0.559 0.013 0.086 0.221 0.430 0.013 0.086 0.223 0.430 0.013 0.085 0.221 0.429 Notes: 1.) Minimum CFM value is based on a signal of 0.03 in w.g. differential pressure of the inlet Table 2c - SVE Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 Step 3 — Install Sensors and Make Field Wiring Connections — Electric Analog or DDC (Direct Digital Controls) — Refer to specific unit dimensional submittals and control application diagrams for control specifications. All field wiring must comply with National Electrical Code (NEC) and local requirements. Refer to the wiring diagram on the unit for specific wiring connections. A field-supplied transformer is required if the unit was not equipped with a factory installed transformer. See Fig. 4. L1 120VAC 208VAC 240VAC 277VAC LEGEND Factory Wiring Field Wiring CLASS II TRANSFORMER GROUND 24 VAC ANALOG OR DDC CONTROLLER 24 VAC POWER YELLOW BLUE Figure 4 - Wiring of Optional Factory Mounted Transformer NOTE: Refer to wiring diagram attached to each unit for specific information on that particular unit. Unit airflow should not be set outside of the range noted in Table. 2a. Single duct terminal units with electric heat are supplied with a single point wiring connection in the heater control box. All unit power is supplied through this connection. Models with electric heat are factory equipped with a control transformer. See Fig. 5. Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 Terminal Block Or or Optional Disconnect Switch Line Fuse (Optional) Transformer Brown #12 Black #18 Yellow #18 L1 L3 Yellow #12 N 24VAC Brown #12 Red #12 Red #12 L2 480V Yellow #18 Blue #18 Blue #18 Red #18 Black #18 COM White #18 White #18 To Controller Brown #18 White #12 Black #18 Yellow #12 Power Supply Manual Reset N.O. AFS Yellow #12 Red #12 Step 3 Heat Contactor Yellow #12 Step 2 Heat Contactor Red #12 Black #18 Red #18 Step 1 Heat Contactor Brown #12 Note: Drawing is typical of 480V 3-phase, 4 wire heater and controller. Refer to actual unit wiring diagram located on inside cover of control enclosure. White #12 LEGEND AFS: Airflow Switch DDC: Direct Digital Controls Black #18 Black #18 Brown #12 Thermal Hi-Limit Auto-Reset (Typ) White #12 Figure 5 - Typical Power Connections for LMHS units with 3-Stage Electric Heat Wiring and unit ampacities are referenced in Table 3. NOTE: Refer to wiring diagram attached to each unit for specific information on that particular unit. Units with 480-3-60 electric heater REQUIRE 4-wire, wye connected power. Units with 208/230 v, 3-phase heater can be connected with 3-wire power. Unit airflow should not be set outside of the range noted in Figure 6. The minimum recommended airflow for units with electric heat must be at least 75 cfm per kW and not drop below the minimum values listed in Table 2a. The maximum unit discharge temperature should not exceed 120 F. To prevent air stratification, the ASHREA Handbook of Fundamentals recommends a discharge temperature not to exceed 90F. Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 CONTROL SET UP General — The LMHS single duct VAV terminal is designed to supply a varying quantity of cold primary air to a space in response to a thermostat demand. Some units have reheat options to provide heating demand requirements as well. Most VAV terminals are equipped with pressure compensating controls to regulate the response to the thermostat independent of the pressure in the supply ductwork. To balance the unit it is necessary to set both the maximum and minimum set points of the controller. The many types of control options available each have specific procedures required for balancing the unit Set Points — Maximum and minimum airflow set points are normally specified for the job and specific for each unit on the job. Where maximum and minimum airflow levels are not specified on the order, default values are noted on unit ID label. Field Adjustment of Minimum and Maximum Airflow Set Points Each unit is equipped with an amplifying flow probe that measures a differential pressure proportional to the airflow. The relationship between flow probe pressures and cfm is shown in the Flow Probe Graphs (Fig.6). This chart is attached to each unit. There are several conventions (and no universally accepted method) in use for representing this flow factor: 1. Magnification Factor: The magnification factor may be expressed as the ratio of either velocity or pressure, of the output of the sensor to that of a pitot tube. a. For example, a velocity magnification may be used. All Krueger probes develop an average signal of 1” w.g. @ 2625 fpm. This gives a velocity magnification of 4005 / 2625 or 1.52. b. It may be a pressure magnification factor. In this case, the ratio of pressures at a given air velocity is presented. For a velocity constant of 2626, at 1000 fpm, this is 0.1451 / 0.0623 = 2.33 2. K-Factor: The K-factor may be represented in two ways: a. It may be a velocity K-factor, which is the velocity factor times the inlet area, (which for all Krueger probes, both the Linear and the k4 LineaCross, is 2625 fpm/in w.g.). b. Alternatively, it may be the airflow K-Factor, which is the velocity factor times the inlet area. For an 8 inch Krueger unit, therefore, this would be 2625 * 0.349, or 916. A separate airflow factor is required for each size. All Krueger VAV terminals have round inlets. Below is a K-Factor table for all Krueger VAV terminal inlets. Inlet Probe Area and K Factor LMHS, RVE Inlet Diameter, in. Velocity Magnification Velocity Constant CFM K Factor. 04 4 1.52 2625 229 05 5 1.52 2625 358 06 6 1.52 2625 515 Inlet Area, Sq. ft. 0.087 0.136 0.196 Recommended Min cfm 40 62 89 07 7 1.52 2625 702 0.26 7 122 08 8 1.52 2625 916 09 9 1.52 2625 1160 10 10 1.52 2625 1432 0.349 0.442 0.545 159 201 248 12 12 1.52 2625 2062 0.78 5 357 14 14 1.52 2625 2806 16 16 1.52 2625 3665 1.069 1.396 486 635 Table 4 System Calibration of the Flow Probe — To achieve accurate pressure independent operation, the velocity sensor and flow probe must be calibrated to the controller. This will ensure that airflow measurements will be accurate for all terminals at system start-up. System calibration is accomplished by calculating a flow coefficient that adjusts the pressure fpm characteristics. The flow coefficient is determined by dividing the flow for a given unit (design air volume in cfm), at a pressure of 1.0 in. w.g differential pressure, by the standard Pitot tube coefficient of 4005. 22 22 1.52 2625 7000 2.66 7 1212 Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 This ratio is the same for all sizes, no matter which probe type is installed. Determine the design air velocity by dividing the design air volume (the flow at 1.0 in. w.g) by the nominal inlet area (sq. ft). This factor is the K factor. Figure 6 – Inlet Sensor Pressure Chart Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 PNEUMATIC CONTROLS Volume controllers for LMHS units are shown in Fig. 7, 8 and 9. Identification for each controller is shown in Table 5. Control Sequence Function Arrangement Identification Figure DA‐NO 7 1102 1103 RA‐NC 8 1104 DA‐NO 9 1105 DA‐NC 9 1106 RA‐NO 9 RA‐NC 9 1107 1108 DUAL MAXIMUM 9 1109 HEATING/COOLING MAXIMUM 9 1110 DUAL MINIMUM 9 Preparation for Balancing (Control Sequences 1102 and 1103) KMC Part Number CSC‐2003 CSC‐2004 CSC‐3011 CSC‐3011 CSC‐3011 CSC‐3011 CSC‐3011 CSC‐3011(2X) CSC‐3011 1. Inspect all pneumatic connections to assure tight fit and proper location. 2. Verify that the thermostat being used is compatible with the control sequence provided (direct acting or reverse acting). 3. Check main air pressure at the controller(s). The main air pressure must be between 15 psi and 25 psi. (If dual or switched-main air pressure is used, check the pressure at both high and low settings.) The difference between “high” pressure main and “low” pressure main should be at least 4 psi, unless otherwise noted, and the “low” set-ting difference should exceed 15 psi. 4. Check that the unit damper will fail to the proper position when main air pressure is lost. Disconnect the pneumatic actuator line from the velocity controller and observe the VAV damper position. The damper should fail to either a normally open position (indicator mark on shaft end is horizontal) or a normally closed position (indicator mark on shaft end is vertical). Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 5. Check that there is primary airflow in the inlet duct. 6. Connect a Magnehelic gage, inclined manometer or other differential pressure measuring device to the balancing taps provided in the velocity probe sensor lines. The manometer should have a full scale reading of 0.0 to 1.0 in. wg. The high-pressure signal is delivered from the front sensor tap (away from the valve), and the low pressure signal is delivered from the back line (near the valve). The pressure differential between high and low represents the amplified velocity pressure in the inlet duct. 7. Read the differential pressure and enter the Linear Aver-aging Probe Chart to determine the airflow in the terminal unit. This chart is shown in Fig. 6 and is also attached to the side of each unit. For example, a differential pressure of 0.10 in. wg for a size 8 unit yields an airflow of 275 cfm. Balancing Procedure (Control Sequences 1102 and 1103) DIRECT ACTING THERMOSTAT; NORMALLY OPEN DAMPER (CONTROL SEQUENCE 1102) — Refer to Fig. 7. (Beige Controller) 1. Minimum Volume Setting: a. Disconnect the thermostat line from the volume controller. b. Adjust the minimum volume control knob (marked “LO” and located in the center of the controller) to achieve the required minimum flow. To determine the required pressure differential, refer to Tables 2 and 5 and the Probe Chart provided on the side of the VAV unit and in Fig. 6. c. Reconnect the thermostat line. 2. Maximum Volume Setting: a. Disconnect the thermostat line from the volume controller. b. Apply 15 + psi to the thermostat port on the volume controller (marked “T”) by tapping into the main air pressure line. c. Adjust the maximum volume control knob (marked “HI” and located at the side of the controller) until the desired pressure differential is registered on the manometer. To determine the required pressure differential, refer to Table 5 and the Probe Chart provided on the side of the VAV unit and in Fig. 6. d. Reconnect the thermostat line. REVERSE ACTING THERMOSTAT; NORMALLY CLOSED DAMPER (CONTROL SEQUENCE 1103) —Refer to Fig. 8 (Gray Controller) 1. Maximum Volume Setting: a. Disconnect the thermostat line from the velocity controller. b. Adjust the maximum volume control knob (marked “HI” and located in the center of the controller) c. To achieve the required minimum flow. To determine the required pressure differential, refer to Tables 2 and 5 and the Probe Chart provided on the side of the VAV unit and in Fig. 6. d. Reconnect the thermostat line. 2. Minimum Volume Setting: a. Disconnect the thermostat line from the velocity controller. b. Apply 15 + psi to the thermostat port on the volume controller (marked “T”) by tapping into the main air pressure line. c. Adjust the minimum volume control knob (marked “LO” and located at the side of the controller) until the desired pressure differential is registered on the manometer. To determine the required pressure differential, refer to Table 5 and the Probe Chart provided on the side of the VAV unit and in Fig. 6. d. Reconnect the thermostat line. Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 Balancing Procedure (Control Sequences 1104-1110) 1. Damper action is factory set at N.O. (normally open), or N.C. (normally closed). To change perform the following steps: 1. Loosen the damper selection screw. 2. Turn the selection dial clockwise until the “NC” or “NO” arrow aligns with the “DAMPER” arrow. NOTE: Accuracy in the alignment of the arrows is very important. Make this adjustment as exact as possible. (See Fig. 10.) 2. Pipe the controller: Connect port “B” to the damper actuator. Connect port “M” to the clean, dry main air. Connect port “T” to the thermostat output. Connect port “H” to the total pressure tap o n the airflow sensor. Connect port “L” to the static pressure tap on the airflow sensor. The controller can be set up for cooling or heating applications using either a Direct Acting (DA) or Reverse Acting (RA) thermostat signal. The two flow adjustments are labeled “LO STAT ∆P” and “HI STAT ∆P”. Adjusting Minimums and Maximums When adjusting the minimum and maximum airflow settings, the output responds slowly to changes in the set point. Wait for the flow rate to stabilize after making an adjustment (usually 20 to 30 seconds) before making further adjustments. Also, if the damper position is all the way closed or open when starting this step, turn the adjustment one full turn, and then wait 20 to 30 seconds for a change in the flow reading of the Magnehelic gauge. If no change occurs after this time, repeat until the flow rate changes. LO STAT ∆P setting is the desired airflow limit when the thermostat pressure is less than, or equal to, the reset start point. For DA Cooling or RA Heating: Adjust LO STAT ∆P to the desired minimum airflow with 0 psig (or a pressure less than the reset start point) at port “T”. The LO STAT ∆P must be set first. The LO STAT ∆P will affect the HI STAT ∆P setting. (Turn Clockwise) For RA Cooling or DA Heating: Adjust LO STAT ∆P to the desired maximum airflow with 0 psig (or a pressure less than the reset start point) at port “T”. The LO STAT ∆P Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 must be set first. The LO STAT ∆P will affect the HI STAT ∆P setting. (Turn Counter Clockwise) HI STAT ∆P setting is the desired airflow limit when the thermostat pressure is greater than, or equal to, the reset stop-point. The reset stop-point is the reset span pressure added to the reset start point pressure. For DA Cooling or RA Heating (see Fig. 6): Adjust HI STAT ∆P to the desired maximum airflow with 20 psig (or a pressure greater than the reset stop point) at port “T”. The HI STAT ∆P must be set last. The HI STAT ∆P setting will be affected by the LO STAT ∆P setting. (Turn Counter Clockwise) For RA Cooling or DA Heating (see Fig. 6): Adjust HI STAT ∆P to the desired minimum airflow with 20 psig (or a pressure greater than the reset stop point) at port “T”. The HI STAT ∆P must be set last. The HI STAT ∆P setting will be affected by the LO STAT ∆P setting. (Turn Clockwise) NOTE: IF the LO STAT ∆P Limit must be set at “0” (zero minimum), do not turn the LO STAT ∆P knob fully clockwise. The knob will adjust one and one-half turns after a zero minimum is reached. Turning the LO STAT ∆P knob fully clockwise will result in a negative reset condition. This means that when the controller begins to reset at the reset start point, it must first overcome the negative adjustment and will not begin to reset from “0” until a higher thermostat reset pressure is reached. This negative reset will also reduce the effective range of the controller by reducing the low end reset, narrowing the reset span. If a zero minimum is required, adjust the LO STAT ∆P knob until the controller just begins to crack the damper open, and then back-off one-quarter turn and verify zero airflow. (This is typically 2-1/2 knob rotations counter clockwise from the fully clockwise position.) NOTE: After the “LO STAT ∆P” and “HI STAT ∆P” initial adjustments are made, cycle the thermostat pressure a few times to settle the internal reset mechanisms and verify settings. Finetune the settings if necessary. The thermostat pressure may be left at a high pressure and the “G” port cap may be removed and replaced to cycle the reset mechanism. RESET START setting is factory set at 8.0 psig. This is the lowest thermostat pressure that the LO STAT ∆P airflow will begin to reset towards the HI STAT ∆P airflow. To change the RESET START setting; regulate thermostat pressure to the “T” port to the desired reset start point pressure, adjust RESET START adjustment until pressure at the “G” port is slightly higher than 0 psig, i.e., 0.1 psig. Note: (For Dual Duct Units the Reset Start Must To Be Adjusted To 3.0 Psig. ON THE HEATING SIDE ONLY) NOTE: The “G” port taps into the controller’s internal reset chamber, which always starts at 0 psig. The RESET START adjustment is a positive bias adjustment that sets the desired thermostat start point to the controller’s internal reset start point of 0 psig. RESET SPAN setting is factory set at 5.0 psig. This is the required change in thermostat pressure that the controller will reset between the LO STAT ∆P setting and the HI STAT ∆P setting. To change the RESET SPAN setting; adjust RESET SPAN adjustment until pressure at the “G” port equals the desired reset span pressure. (Do Not Adjust) NOTE: The “G” port taps into the controller’s internal reset chamber, which will always be at a pressure between 0 psig and the RESET SPAN pressure. Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 Preventative Maintenance 1. Inspect pneumatic tubing for loose connections or leaks. 2. Clean out pneumatic line filters regularly according to manufacturer’s recommendations. Pneumatic Control Troubleshooting Table 6 – Pneumatic Controls Trouble Shooting Analog Controls Installation and Balancing Procedures The Analog Electronic Control System is a pressure independent volume reset control that uses a KMC CSP-4702 controller-actuator (see Fig. 12). Figure 12: CSP-4702 Controller/Actuator Adjustments for the minimum and maximum airflow settings are made at the thermostat. The thermostat (CTE-5202) operates on a 16 VDC power supply from the CSP 4702 controller and outputs a 0 to 10 VDC signal on the AO1 and AO2 terminals. AO1 is used as the cooling output and AO2 is used as the heating output. Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 Thermostat Installation For proper operation, mount the thermostat on an interior wall. Do not mount the thermostat in a location that will cause it to be affected by direct sunlight or other heat or cold sources. The thermostat should be clear of all obstructions so it can properly sense the room temperature. Complete rough-in wiring at each location prior to thermostat installation. Cable insulation must meet local building codes. 1. Remove thermostat cover. If the thermostat is locked on the back plate, turn the two hex screws in on the bottom of the cover (in the two outermost holes) in the back plate CLOCKWISE until they clear the cover. Do not remove these screws completely. Swing the thermostat up and away from the back plate to remove it. 2. Route the wires through the opening in the back plate. 3. Install the back plate directly to the junction box using the screws supplied with the thermostat. Verify the hex screws used for securing the cover are located at the bottom before installing. 4. Connect the wires to the terminal block. Refer to the wiring diagram located on the inside cover of the control enclosure of each unit showing the wiring terminations. The wiring schematic can also be found on the control sequence submittal found on the Krueger website. 5. Replace the thermostat cover. Turn the two hex screws COUNTER CLOCKWISE until they are flush with the bottom cover and secure it to the back plate. Programming Thermostat 1. The thermostat has three sequences that are selectable from the display screen. To access the configuration menu on the thermostat, press and hold the Up and Down arrows for 10 seconds until the display starts flashing “LIMITS”. Use the Up and Down arrows to scroll between the different menu options or set a specific value. Use the Setpoint button to select a menu or set a value. 2. To set the minimum and maximum airflow limits, Use AO1 Min and AO1 Max or AO2 Min and AO2 Max. Use the Table 7 below to determine thermostat setting for the CFM per inlet size. 3. For details on how to program the thermostat for each control sequence see the specific control sequence submittal. The control sequence submittals can be at the Krueger Website: www.krueger-hvac.com. Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 AO1 & Sensor AO2 Signal 4 5 6 7 Setting "W.G. 0‐2 0.00 0 0 0 0 2.1 0.03 36 57 81 111 2.2 0.05 51 80 115 157 2.3 0.08 63 98 141 192 2.4 0.10 72 113 163 222 2.5 0.13 81 127 182 248 2.6 0.15 89 139 200 272 2.7 0.18 96 150 216 293 2.8 0.20 102 160 231 314 2.9 0.23 109 170 244 333 3 0.25 115 179 258 351 3.1 0.28 120 188 270 368 3.2 0.30 125 196 282 384 3.3 0.33 131 204 294 400 3.4 0.35 136 212 305 415 3.5 0.38 140 219 316 430 3.6 0.40 145 226 326 444 3.7 0.43 149 233 336 457 3.8 0.45 154 240 346 471 3.9 0.48 158 247 355 484 4 0.50 162 253 364 496 4.1 0.53 166 259 373 508 4.2 0.55 170 265 382 520 4.3 0.58 174 271 391 532 4.4 0.60 177 277 399 543 4.5 0.63 181 283 407 555 4.6 0.65 185 289 416 566 4.7 0.68 188 294 423 576 4.8 0.70 192 299 431 587 4.9 0.73 195 305 439 597 5 0.75 198 310 446 608 5.1 0.78 202 315 454 618 5.2 0.80 205 320 461 627 5.3 0.83 208 325 468 637 5.4 0.85 211 330 475 647 5.5 0.88 214 335 482 656 5.6 0.90 217 340 489 666 5.7 0.93 220 344 496 675 5.8 0.95 223 349 502 684 5.9 0.98 226 353 509 693 6 1.00 229 358 515 702 CFMs Per Inlet Size 8 9 10 12 14 16 20 22 0 145 205 251 290 324 355 383 410 435 458 481 502 522 542 561 580 597 615 632 648 664 680 695 710 724 739 753 767 780 794 807 820 832 845 857 869 881 893 905 916 0 183 259 318 367 410 449 485 519 550 580 608 635 661 686 710 733 756 778 799 820 840 860 879 898 917 935 953 970 987 1004 1021 1037 1053 1069 1085 1100 1115 1130 1145 1160 0 226 320 392 453 506 555 599 640 679 716 751 784 816 847 877 905 933 960 987 1012 1037 1062 1086 1109 1132 1154 1176 1198 1219 1240 1260 1281 1300 1320 1339 1358 1377 1395 1414 1432 0 326 461 565 652 729 798 862 922 978 1031 1081 1129 1175 1220 1263 1304 1344 1383 1421 1458 1494 1529 1563 1597 1630 1662 1694 1725 1755 1785 1815 1844 1873 1901 1929 1956 1983 2009 2036 2062 0 444 627 768 887 992 1087 1174 1255 1331 1403 1472 1537 1600 1660 1718 1775 1829 1882 1934 1984 2033 2081 2128 2174 2218 2262 2305 2348 2389 2430 2470 2510 2549 2587 2625 2662 2699 2735 2771 2806 0 580 820 1004 1159 1296 1420 1533 1639 1739 1833 1922 2008 2089 2168 2244 2318 2389 2459 2526 2592 2656 2718 2779 2839 2898 2955 3011 3067 3121 3174 3227 3278 3329 3379 3428 3477 3525 3572 3619 3665 0 315 445 545 630 704 771 833 891 945 996 1045 1091 1136 1178 1220 1260 1299 1336 1373 1408 1443 1477 1510 1543 1575 1606 1636 1666 1696 1725 1753 1782 1809 1836 1863 1890 1916 1941 1967 1992 0 1107 1565 1917 2214 2475 2711 2928 3130 3320 3500 3671 3834 3991 4141 4287 4427 4563 4696 4824 4950 5072 5191 5308 5422 5534 5644 5751 5857 5960 6062 6162 6261 6358 6454 6548 6641 6732 6823 6912 7000 Table 7: CFM Chart for setting min and max values on thermostat Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 Analog Control Troubleshooting — The following troubleshooting guide is directed towards single duct cooling applications, the same concepts can be applied to other configurations. NOTE: For about 15 seconds after power is applied, no rotation occurs and one or both of the LEDs will flash. Controller 1. Check that the shaft moves freely. (Press and hold the actuator release clutch and manually rotate the shaft.) 2. Check wiring. (See Wiring Issues section below.) 3. Check for a tripped circuit breaker to the transformer, for proper supply voltage from the transformer (or power supply), and for enough capacity (VA) for all connected devices. 4. Check that the direction jumper is in the proper position. 5. Check the polarity and level of the input signal from the thermostat. Wrong Rotation Direction or Stroke Range 1. Check the position of the direction jumper. 2. Check the Min and Max flow limits on the thermostat 3. Check the adjustable stop position. No Pressure Output Signal from Inlet Sensor 1. Check the wiring. 2. Check air flow and sensor. Tubing should be free of kinks and restrictions. Sensor must be oriented in the correct airflow direction. Wiring Issues 1. Check for correct wiring at unit and thermostat. 2. At the Controller, verify 24 VAC at terminals “~” (phase) and “-” (ground). Tolerance can be –15% to +20% (20.4 to 28.8 VAC). 3. Verify 16 VDC at terminals “16 VDC” and “COM” a. Tolerance is 15.0 to 17.0 VDC power supply to thermostat. b. If not correct, disconnect thermostat and recheck. c. If still incorrect, replace CSP controller. 4. Check “Requested Flow” voltage on terminal “2-10 IN” and “COM“. a. Use Table 7 to correlate into cubic feet per minute (CFM) b. If reading is not what is desired, see “calibration to adjust thermostat. NOTE: Never jumper terminal 16 VDC to “-” as this would cause a short, and possibly damage the power supply NOTE: When using the same transformer for more than one control, the phase and ground must be consistent with each device. WATER VALVE INSTALLATION WARNING: Disconnect power before wiring or electrical shock and personal injury could result. Water valves are field supplied. Most control manufacturers offer three different hot water valve applications; on/off and floating point, and proportional control. The controls contractor should provide water valve specs used on controls supplied by others. To connect the field-supplied water valves to the controller, refer to the wiring labels for the control package. Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 Replacement Parts Primary Damper Assembly 4, 5, 6" round (Includes damper blade and shaft) 7" round (Includes damper blade and shaft) 8" round (Includes damper blade and shaft) 9" round (Includes damper blade and shaft) 10" round (Includes damper blade and shaft) 12" round (Includes damper blade and shaft) 14" round (Includes damper blade and shaft) 16" round (Includes damper blade and shaft) Size 20 - 13 1/2" x 7 7/8" rectangle (Includes damper blade and shaft) Size 22 - 23 7/8" x 15 7/8" (Includes opposed blade damper and shaft) Pneumatic Tubing, Tees and Caps tee, 1/4", connects pneumatic tubing each cap, 1/4", for pneumatic tubing each tubing, 1/4", red, for pneumatic controls (1 foot length) tubing, 1/4", green, for pneumatic controls (1 foot length) tubing, 1/4", yellow, for pneumatic controls (1 foot length) tubing, 1/4", Gray, for pneumatic controls (1 foot length) inline filter for 1/4" pneumatic tubing Four Quadrant, K4LineaCross Inlet Airflow Sensor 4” Inlet 5” Inlet 6” Inlet 7” Inlet 8” Inlet 9” Inlet 10” Inlet 12” Inlet 14” Inlet 16” Inlet 22" Inlet (Requires (2) Sensors per unit) Part Number 30182001 30182002 30182003 30182004 30182005 30182006 30182007 30182008 3512701200 10336604 42150011 42160081 61510035 61510234 61510260 10221501 10154701 15010904 15010904 15010906 15010907 15010908 15010909 15010910 15010912 15010914 15010916 15010914 Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 Transformers 120 volts to 24 volts, 50 VA 120 volts to 24 volts, 75 VA 277 volts to 24 volts, 50 VA 277 volts to 24 volts, 75 VA 208/240 volts to 24 volts, 50 VA 208/240 volts to 24 volts, 75 VA 480 volts to 24 volts, 50 VA 24 volts to 24 volts, 50 VA 10029301 10336801 10006601 10313401 10057501 10336901 10100301 10166601 Electric Heat and LineaHeat Thermal cutout, automatic reset (115-130° Limit) Thermal cutout, manual reset (160° Limit) Disconnect Switch 30A Assembly (Does not include Snap-In Neutral Block) Disconnect Switch 60A Assembly (Does not include Snap-In Neutral Block) Disconnect Neutral Block - 30A (Snap-In) Disconnect Neutral Block - 60A (Snap-In) Magnetic Contactor, 30A, 24V coil, 1 pole (DIGITAL/ ANALOG) Magnetic Contactor, 30A, 24V coil, 2 pole (DIGITAL/ ANALOG) Magnetic Contactor, 60A, 24V coil, 2 pole (DIGITAL/ ANALOG) Solid State Relay - 1 Pole, 50A (AC Volt) EHM Board (including mounting bracket) Solid State Relay - 1 Pole, 50A (DC Volt) [Crydom CWD 4850] Heat Sink Discharge Temperature Sensor 10052101 10118801 31453101 31453102 10341201 10341202 10323601 10054401 10162501 15018001 35134901 15012101 15012001 HH79NZ074 Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 Water Coils 1 Row: Unit Size: 4-6 7-8 9-10 12 14 16 20 22 2 Row: Unit Size: 4-6 7-8 9-10 12 14 16 20 22 NOTE: 1 & 2 Row Coils can be used for both Left and Right Hand Orientation 41410148 41410149 41410150 41410151 41410152 41410153 10344201 41410214 41410154 41410155 41410156 41410157 41410158 41410159 10344202 41410215 3 Row: Unit Size: 4-6 7-8 9-10 12 14 16 22 41410195 (RH) 15020301 (LH) 41410196 (RH) 15020302 (LH) 41410197 (RH) 15020303 (LH) 41410198 (RH) 15020304 (LH) 41410199 (RH) 15020305 (LH) 41410200 (RH) 15020306 (LH) 41410216 (RH) 15020307 (LH) Models: LMHS, RVE, SVE Form No. SIDOM.3 4/14 4 Row: Unit Size: 4-6 7-8 9-10 12 14 16 22 41410201 (RH) 15020401 (LH) 41410202 (RH) 15020402 (LH) 41410203 (RH) 15020403 (LH) 41410204 (RH) 15020404 (LH) 41410205 (RH) 15020405 (LH) 41410206 (RH) 15020406 (LH) 41410217 (RH) 15020407 (LH)