City and County of San Francisco Contract Proposal 75711 ATTACHMENT A San Francisco Water Department Specifications For Water Meter Boxes And Covers (August 2011) i City and County of San Francisco Contract Proposal 75711 ATTACHMENT A San Francisco Water Department Specifications for Water Meter Boxes and Covers All water meter boxes and covers shall be manufactured and conform to all provisions and standard ANSI/SCTE 77 for Tier 15, Western Underground Committee’s Guide 3.6 and as specified herein. The more stringent requirements shall be used when there is a contradiction between standards. All meter boxes and covers shall conform and comply with the specifications stated herein and with all drawings, Appendices 1-13. I. WATER METER BOXES The meter boxes shall be a two-piece box consisting of body and frame. The boxes shall be manufactured with minimum inside dimensions as shown on the attached drawings Appendixes 1-13 for the various boxes and covers. Outside dimensions shown are minimum values. Bidder offering thinner boxes must justify, with calculations and tests that the box can perform satisfactorily for the intended usage. A. BODY: 1. Materials: Meter box body shall be made of Fiberglass-Reinforced Plastic or Polyethylene. Polyethylene shall be treated with UV inhibitor to prevent UV degradation. 2. Fabrication: Meter box body shall be manufactured using rotation or injection molding techniques for Polyethylene. Other techniques may be acceptable if they can produce products with comparable quality as rotation or injection molding techniques. 3. Characteristics: Meter body shall have straight walls with vertical reinforcements. Flared wall body will not be acceptable. The box shall be designed to have a bottom integral flange a minimum of 1” wide to prevent settling. The body shall have pre-cut pipe entry areas (mouse holes) 3” wide x 4” high, located on the bottom center of each short side end wall. Attachment A (August 2011) 1 City and County of San Francisco B. Contract Proposal 75711 FRAME: 1. Material: Meter box frame shall be made of fiberglass reinforced polymer concrete. 2. Characteristics: The frame shall be rigidly attached to the body to form a structurally sound box. Meter box frame top surface shall have a 0.5 minimum coefficient of friction when tested in accordance with ASTM C-1028. Meter box frame shall be extended beyond the box wall allowing the box to lock into the sidewalk pavement or surrounding backfill materials. Fiberglass reinforced polymer concrete shall meet impact resistant tested per ASTM D-2444 and have water absorption less than 1% per ASTM D-570. II. WATER METER BOX COVERS A. Material: 1. Water meter box covers shall be made of fiberglass reinforced polymer concrete. Cover shall contain sufficient fiberglass reinforcement to meet or exceed the product performance characteristics specified herein, including but not limited to vertical loading. 2. Manufacturer shall provide third party, independent test lab certification of compliance with the material testing specified herein and in WUC, Guide 3.6. 3. Fiberglass reinforced polymer concrete covers shall withstand an impact force of 70 foot-pounds with a type “C tup” when tested per ASTM D-2444 without puncturing or splitting. 4. Water absorption of the fiberglass reinforced polymer concrete covers shall be less than 1% per ASTM D-570. 5. All covers shall have a minimum coefficient of friction of 0.65 when tested in accordance with ASTM C-1028. 6. Fiberglass reinforced polymer concrete meter box covers shall be resistant to chemicals commonly found in the operating environment. Polymer concrete material shall be tested in accordance with ASTM D-543 to the chemical reagents listed in WUG, Guide 3.6, Section 6.2.4. There shall be no more than 2 percent change in specimen weight. 7. The polymer concrete material shall be ultraviolet light resistant and shall be tested in accordance with ASTM G-154-current revision. Attachment A (August 2011) 2 City and County of San Francisco 8. B. III. Characteristics: 1. Covers shall be manufactured per the dimensions shown on the attached drawings. Fiberglass reinforced polymer concrete shall meet impact resistant tested per ASTM D-2444. 2. Locking provisions shall not be required to secure covers to box. Covers shall be interchangeable with San Francisco Water Department’s existing concrete boxes (BES C-9WX, BES C-30W, Christy box B30, and BES C-36W, Christy box B36, Armorcast box –A6001534X12 and A6001921X12) except Christy box B9X. The letters “SFWD” shall be recessed, in the approximately center of the cover. The letters shall be at least 1/16 inch deep and 1 ¼ inch high and ¾ wide. D. Advanced Meter Infrastructure Compatibility: 1. Manufacturer may be requested to demonstrate their product compatibility with ACLARA standards for RF signal transmission. 2. All lids shall allow ACLARA meter transmission unit to be securely mounted to the bottom of the lid. Predrilled holes shall be included to accommodate mounting of Aclara meter transmission unit. CHEMICAL RESISTANCE Fiberglass reinforced polymer concrete and polyethylene material shall be resistant to chemicals commonly found in the soil or in the operating environment. Polymer concrete material shall be tested in accordance with ASTM D-543. The polymer concrete material shall be resistant to sunlight and any climatic condition and shall be tested in accordance with ASTM D-756, procedure “E”. COLOR A. V. Water meter box cover must be a proven product, in use by three (3) other Utilities for a minimum of three (3) years. C. A. IV. Contract Proposal 75711 Meter boxes and covers shall be “concrete gray” in color. LOAD CAPACITY A. Boxes: Box assembly shall be designed to withstand 20,800 lbs. Box will be vertical load tested on a 10”x20”x1” steel plate without damage. B. Covers: General: Attachment A (August 2011) 3 City and County of San Francisco 1. Contract Proposal 75711 The Covers shall be tested to demonstrate a Design Load of 10,400 lb. force, the maximum possible wheel load of a Class 6 vehicle (26,000 GVWR). A Safety Factor of 2.17 shall be applied for Proof of Design Load (per ASTM C 497). The covers shall be tested as described below and certified to withstand the (minimum) Proof Load of 22,568 lbs when loaded with a 10” x 10” x 1” steel plate. 2. C. VI. VII. While the preferred method for cover testing would be in the “box” in which the cover is intended to function, that is not practical for this project. Specially fabricated test frames shall be prepared to support the cover in a fashion simulating the support the cover will receive in the box after installation. The test frame shall provide the same area of support to the cover as existing meter boxes (see those required above). The frames shall provide no more contact area that the boxes provide. Vertical Load Test Protocol: 1. Apply the 10,400 lb load over the prescribed area centered on the cover. The load shall be transferred into the cover and test frame through a ½” thick piece of rubber backed by ten inch by ten inch by one-inch thick steel plate. A spherical bearing swivel head shall be used in the testing machine. The load shall be applied at a rate of 550 lb/ second, +/- 450 lb/ second. 2. The Design Load (10,400 lb) shall be cycled on the cover in the test frame ten times as per WUC, Guide 3.6 test protocol. On the eleventh cycle, the load shall be increased to confirm the cover can sustain the Proof of Design Load (22,568 lb.). 3. The failure criteria shall be determined by the one of the two following criteria. Yield – the point on a stress / strain curve where resistance to the applied load no longer increases as deflection continues. Break – the point where increasing load results in exceeding the tensile or elastic limit of a material. SUBMITTALS A. Prior to award, samples may be required. Refer to Special Condition #73 – Samples. B. Prior to production, shop drawings will be submitted to SFWD department for approval. C. Boxes and covers shall conform to all provisions of standard ANSI/SCTE 77 for Tier 15 and Western Underground Committee’s Guide 3.6. Test reports to be submitted shall be provided by a nationally recognized Standards Testing Laboratory at no cost to the City. DESIGN/PRODUCT MODIFICATIONS A. Meter boxes and covers specified in this attachment are intended for installation in sidewalks and driveways (traffic load areas) and occasionally in bare ground, lawn areas, or sand areas. Heavy loads from traffic are expected in some of these areas. The specifications stated are minimum industry requirements for meter boxes and covers to perform satisfactorily under normal usage in these areas. Attachment A (August 2011) 4 City and County of San Francisco Contract Proposal 75711 B. Bids offered for the boxes and cover designs must be conducive to the various ground areas and conditions and perform satisfactorily under normal usage as stated in this attachment. C. After award, in situations where the boxes and covers do not perform satisfactorily under normal use, the City representative shall notify Contractor of the problem. The Contractor shall modify the design to correct the deficiencies at no cost to the City. D. Prior to any modifications, the Contractor shall provide revised specifications and drawings at no additional costs to the City representative and Purchaser for review and approval. E. Failure of Contractor to comply with this section of this contract shall constitute a default of this Contract as stated in General Condition No. 48, Contractor’s Default. END OF SPECIFICATIONS – ATTACHMENT A Attachment A (August 2011) 5