RIELLO RDB SERIES OIL BURNERS FAULT FINDING LOGIC FOR DIGITAL CONTROL BOX TYPE MO535‐MPF LED CODE ‐ LOCKOUT TYPES (control box in lock out) CONTROL BOX IS SUPPLIED WITH HEAT DEMAND A MOTOR STARTS AFTER INITIALIZATION CHECK TIME 3.5s? Y N N CHECK BOILER & SYSTEM CONTROLS Y GO TO BOX A RED 0.2s ON / RED 0.2s OFF Lock‐out for max n° of recycles FAN MOTOR OR OIL PUMP SEIZED? N RED 2.5s ON / ORANGE 0.5s ON RED 2.5s ON/ GREEN 0.5s ON Lock‐out for oil‐valve failure ORANGE 0.5s ON / GREEN 0.5s ON Control box internal error N C D ARE ELECTRODES N OK & SET CORRECTLY? N Y ORANGE steady ON When anomaly appears during pre‐purge, burner remains in pre‐purge. When anomaly appears after ignition, burner remains in operation. When anomaly disappears burner restarts. Push button is activated for more than 60s. When anomaly appears burner doesn't stop. AIR SET CORRECTLY? Y COMBUSTION HEAD SET CORRECTLY? N N N COIL LEAD OK? ADJUST COMBUSTION AIR SETTING RESET COMBUSTION HEAD Y CLEAN OR REPLACE FILTERS FLAME GOES OUT THEN RE‐LIGHTS? REPLACE NOZZLE E COIL RESISTANCE 90 to 110Ω? CHECK OIL PIPE FROM PUMP TO NOZZLE HOLDER Y CLEAR BLOCKAGE Y BOILER OR FLUE BLOCKED? N REPLACE OIL PUMP IGNITION LEADS OK? N CLEAN OR REPLACE PUMP & FUEL LINE FILTERS REPLACE COIL N IF BALANCED FLUE; REMOVE SNORKEL AND TEST ‐ NOW OK? Y Y COIL RESISTANCE 90 to 110 Ω? Y REPLACE IGNITION LEADS N AFTER 15s 25‐30Vdc TO COIL? (COIL CONNECTED) Y Y PHOTOCELL RESISTANCE >10 MΩ IN DARK AND <10 kΩ INLIGHT? REPLACE COIL REPLACE CONTROL BOX REPLACE OIL PUMP BALANCED FLUE CAN RECIRCULATE GASES CAUSING RECYCLING N F REPLACE COIL LEAD Y N REPLACE PUMP COUPLING REPLACE PHOTOCELL Y N Y N REPLACE PHOTOCELL CHECK FLUE POSITION & SEALS POST PURGE FEATURE POST PURGE FEATURE LIGHT DIAGNOSIS FEATURE (FLAME STRENGTH INDICATOR) LIGHT DIAGNOSTICS FEATURE (PHOTOCELL STRENGTH / LIGHT LUX LEVEL INDICATOR ) Sequence for post‐purge programming Sequence for enable / disable This can only be carried out during operation (burner running) This can only be carried out during operation (burner running) ) Press push‐button for 10 to 15 sec ) Press and hold the reset button for 15‐20 sec. LED ‐ GREEN flash 1 time ) Release push‐button LED ‐ GREEN OFF ) Press push‐button 1 to 6 times for selection (see TIMINGS) LED ‐ GREEN ON and OFF for each press and release LED ‐ RED blink 2 times after 5 sec. LED ‐ GREEN blink 1 time after 10 sec. LED ‐ GREEN blink 2 times ) Release the reset button LED ‐ GREEN OFF ) Press the reset button 1 time for enable or 2 times for disable LED ‐ GREEN ON and OFF for each press and release After 10 sec LED ‐ GREEN blinking for the programmed times (0.5s ON / 0.5s OFF) LIGHT LEVEL (see instruction manual) (see instruction manual) (see instruction manual) (see instruction manual) Only motor runs. Lock out after 25s. NOZZLE NEW? Y N REPLACE OR RESET ELECTRODES DRIVE COUPLING Y BROKEN? C Y N CONTAMINATED FUEL FILTERS? Y N REPLACE MOTOR CAPACITOR F GREEN 0.5s ON / RED 0.5s ON Anomaly for reset push‐buttonfailure CHECK OIL SUPPLY TO OIL PUMP NOZZLE ATOMIZING THE FUEL? Y N N Fit pre‐heater link GREEN 0.2s ON / RED 0.2s ON N REMOVE EXTRANEOUS LIGHT REPLACE FAN MOTOR AND CHECK CONTROL BOX E COIL RELEASES WORKING PRESSURE? N D APPROX 35Ω ACROSS BLUE & BLACK MOTOR WIRE? Pre‐heating time (gas oil units only) Control box internal error Y Y B GREEN 0.5s ON / GREEN 2.5s OFF ORANGE 0.2s ON / GREEN 0.2s ON BURNER FIRES WHEN PHOTOCELL IS COVERED? PHOTOCELL RESISTANCE >10 MΩ IN DARK AND <10 kΩ IN LIGHT? 230V TO MOTOR ACROSS BLUE & BLACK WIRE? IGNITION SPARK PRESENT? Y N N (control box in standby) Anomaly for presence of abnormal frequency supply B Y REPLACE FAN MOTOR LED CODES ‐ ANOMALY TYPE Anomaly for presence of extraneous light WASHING PRESSURE 1 ‐ 2 BAR? N Y MOTOR GIVES 5OVac ACROSS WHITE & BLACK WIRE? Y Lock‐out for fan motor failure BURNER LOCKS OUT AFTER 25s? Y REPLACE SEIZED COMPONENT RED 0.5s ON / RED 0.5s OFF Lock‐out for false flame signal N Y N RED steady ON Lock‐out for no flame after safety time FAN RUNS FOR LESS THAN 12s? Y After 10 sec LED ‐ GREEN blinking for the programmed times (0.5s ON / 0.5s OFF) NOTE: If heat demand switches off during the post purge programming sequence the control box will revert to the previous setting. If the heat demand switches off after the programming sequence but during the final light flashing confirmation stage of the programming, the new setting will be saved. TIMINGS 1 = 10 sec. (default) 2 = 20 sec. 3 = 30 sec. 4 = 60 sec. 5 = 120 sec. 6 = 0 sec. (disable) ‐ 1 flash ‐ 2 flash ‐ 3 flash ‐ 4 flash ‐ 5 flash ‐ 6 flash Minimum Good Very good ‐ 1 to 2 flash ‐ 3 to 4 flash ‐ 5 to steady on