SuperLok® Mechanically Seamed Roof System Technical/Installation Information IMPORTANT NOTICE READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE SUPERLOK® ROOFING SYSTEM. THE MANUFACTURER DETAILS MUST BE FOLLOWED AS A MINIMUM TO INSURE APPROPRIATE WARRANTIES WILL BE ISSUED. ALWAYS INSPECT EACH AND EVERY PANEL AND ALL ACCESSORIES BEFORE INSTALLATION. NEVER INSTALL ANY PRODUCT IF ITS QUALITY IS IN QUESTION. NOTIFY MBCI IMMEDIATELY IF ANY PRODUCT IS BELIEVED TO BE OUT OF TOLERANCE, SPECIFICATION OR HAS BEEN DAMAGED DURING SHIPMENT. IF THERE IS A CONFLICT BETWEEN PROJECT INSTALLATION DRAWINGS PROVIDED OR APPROVED BY THE MANUFACTURER AND DETAILS IN THIS MANUAL, PROJECT INSTALLATION DRAWINGS WILL TAKE PRECEDENCE. Ice Dam Disclaimer MBCI designs it’s standing seam roofs to meet the load requirements dictated by governing codes and project specifications, including applicable snow loads. However, MBCI expressly disclaims responsibilty for weathertightness or roof point loading issues or other hazards resulting from ice dam situations. Any time ice and snow can melt on the main body of the roof and refreeze at the eave or in the shadow of an adjacent wall, an ice dam situation may develop. In addition to local climate, ice dam formation is affected by many other factors, including but not limited to, roof insulation R value, roof panel color, interior temperature of building, heater location in building, eave overhangs, parapet walls, shading of building roof areas from adjacent trees, parapets, buildings, etc. These factors are design and maintenance issues and are outside the control of MBCI. MBCI specifically disclaims any liability for damage due to ice dam formation, although the following issues should be taken into consideration concerning standing seam roofs installed in freezing climates: • Always use field seamed panels. These machine-folded seams are more durable when subjected to occasional icing. • Eliminate “cold” eave overhangs and parapet walls from the building design. Roof overhangs outside the heated envelope of the building will tend to be colder than the roof areas over the heated envelope. Simple roof designs are preferred. Parapet walls at the eave allow ice and snow to collect due to shading effects and the lower roof temperatures caused thereby. • Make sure the interior of the building is adequately insulated and the heating is properly distributed. Inadequate insulation in the roof and/or improper heat distribution causes heat flow though the main body of the roof. On days when the temperature is below freezing, this heat gain can cause ice and snow to melt and refreeze at the eave where the roof is colder. • Lay out the building to prevent the eaves and other roof areas from being shaded during the winter. This may mean eliminating adjacent trees or reconsidering roof geometries. • Consider using self-regulating heating cables at the eaves to mitigate the effects of ice dams. • On building designs using attics, over-insulate the attic floor and provide adequate ventilation in the attic. This will reduce heat transfer through the roof resulting in more consistent roof temperatures between eave and field of roof. • Increase the degree of diligence with respect to underlayment materials at roof areas prone to icing. This may include valleys, eaves, dormers and roof areas near dormers, parapets and the like where shading may occur. For more information on this subject, please refer to the MCA’s Metal Roof Design For Cold Climates manual. The engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommended that the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed Steel Structural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria for cold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable to the project jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired, please contact the manufacturer ©Copyright NCI Group, Inc. 2016 All Rights Reserved Descriptions and specifications contained herein were in effect at the time this publication was approved for printing. In a continuing effort to refine and improve products, MBCI reserves the right to discontinue products at any time or change specifications and/or designs without incurring obligation. To ensure you have the latest information available, please inquire or visit our website at www.mbci.com. Application details are for illustration purposes only and may not be appropriate for all environmental conditions, building designs or panel profiles. Projects should be designed to conform to applicable building codes, regulations and accepted industry practices. If there is a conflict between this manual and project erection drawings, the erection drawings will take precedence. SuperLok® TABLE OF CONTENTS ROOFING SYSTEM General Description ............................................................................................................................................................. SL-3 Architect/Engineering Information........................................................................................................................................ SL-4 ENGINEERING Read This First .................................................................................................................................................................... SL-5 UL 90 Requirements ............................................................................................................................................................ SL-6 12" Properties/Load Tables ......................................................................................................................................SL-7 – SL-8 16" Properties/Load Tables ....................................................................................................................................SL-9 – SL-10 GENERAL INFORMATION Product Checklist ..................................................................................................................................................SL-11 – SL-20 Panel Orientation ............................................................................................................................................................... SL-21 Installation Guidelines........................................................................................................................................................ SL-21 Preparatory Requirements................................................................................................................................................. SL-22 Unloading ..............................................................................................................................................................SL-23 – SL-24 Handling/Panel Storage ..................................................................................................................................................... SL-25 Proper Handling, Storage and Maintenance of Painted and Galvalume Plus® Panels ........................................SL-26 – SL-27 INSTALLATION SEQUENCE Step Step Step Step Step Step Step Step Step Step Step Step Step Step 1 2 2A 3 4 5 6 7 8 9 10 11 12 13 — — — — — — — — — — — — — — Rake Attachments ....................................................................................................................................... SL-28 Low System Eave ........................................................................................................................................ SL-29 High System Eave ....................................................................................................................................... SL-30 Thermal Spacer (For High Systems Only) .................................................................................................. SL-31 First Panel ................................................................................................................................................... SL-32 Clip Installation ............................................................................................................................................ SL-33 Endlap.......................................................................................................................................................... SL-34 Ridge ........................................................................................................................................................... SL-35 Subsequent Runs Eave ............................................................................................................................... SL-36 Subsequent Runs Endlap ............................................................................................................................ SL-37 Subsequent Runs Ridge.............................................................................................................................. SL-38 Last Panel Run ............................................................................................................................................ SL-39 Seaming Operation.........................................................................................................................SL-40 – SL-42 Outside Closure Installation......................................................................................................................... SL-43 SPECIAL ERECTION TECHNIQUES UL 90 Light Transmitting Panel Installation ....................................................................................................................... SL-44 Curb Installation ....................................................................................................................................................SL-45 – SL-62 Pipe Penetration Installation .................................................................................................................................SL-63 – SL-64 DETAILS Open Framing Fixed Eave With Sculptured Gutter ................................................................................................................................... SL-65 Fixed Eave With Sculptured Eave Trim............................................................................................................................. SL-66 Fixed Eave With Box Eave Trim........................................................................................................................................ SL-67 Floating Ridge.................................................................................................................................................................... SL-68 Floating Vented Ridge ....................................................................................................................................................... SL-69 Fixed Vented Eave ............................................................................................................................................................ SL-70 Sculptured Rake ................................................................................................................................ SL-71 Sculptured Rake With Cleat .............................................................................................................................................. SL-72 Parapet Rake ..................................................................................................................................................................... SL-73 Floating Sculptured High Side Eave .................................................................................................................................. SL-74 Parapet Floating High Side Eave ...................................................................................................................................... SL-75 Fixed Valley...................................................................................................................................... SL-76 Floating Hip...................................................................................................................................... SL-77 SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-1 SuperLok® TABLE OF CONTENTS Wood Deck Field Hemming Panel End ................................................................................................................................................. SL-78 Floating Endlap................................................................................................................................. SL-79 Floating Eave with Box Gutter ........................................................................................................................................... SL-80 Floating Eave with Eave Trim with Extended Drip Edge ................................................................................................... SL-81 Fixed Ridge...................................................................................................................................... SL-82 Fixed Vented Ridge ........................................................................................................................................................... SL-83 Box Rake......................................................................................................................................... SL-84 Parapet Rake ..................................................................................................................................................................... SL-85 Fixed Box High Side Eave ................................................................................................................................................. SL-86 Parapet Fixed High Side Eave .......................................................................................................................................... SL-87 Floating Valley ................................................................................................................................................................... SL-88 Fixed Hip......................................................................................................................................... SL-89 Rigid Insulation Over Metal Deck Floating Endlap.................................................................................................................................. SL-90 Floating Eave With Box Gutter .......................................................................................................................................... SL-91 Floating Eave With Eave Trim with Extended Drip Edge .................................................................................................. SL-92 Fixed Ridge...................................................................................................................................... SL-93 Fixed Vented Ridge ........................................................................................................................................................... SL-94 Box Rake......................................................................................................................................... SL-95 Parapet Rake ..................................................................................................................................................................... SL-96 Fixed Box High Side Eave ................................................................................................................................................. SL-97 Parapet Fixed High Side Eave .......................................................................................................................................... SL-98 Floating Valley ................................................................................................................................................................... SL-99 Fixed Hip.........................................................................................................................................SL-100 SL-2 REV 00.01 SEE SEEwww.mbci.com www.mbci.comFOR FORCURRENT CURRENTINFORMATION INFORMATION SUBJECT SUBJECTTO TOCHANGE CHANGEWITHOUT WITHOUTNOTICE NOTICE SuperLok® ROOFING SYSTEM GENERAL DESCRIPTION 16" or 12" ¹⁄₁₆" 2" Coverage Width - 16" or 12" Minimum Slope - 1/2:12 Panel Attachment - Low, High (Fixed or Floating) or Utility (No insulation clearance) Panel Substrate - Galvalume® (standard) Gauge - Standard: 24 ; Optional: 22 Finishes - Smooth Striated (standard)* or Embossed Striated Coatings - Signature® 200, Signature® 300, Signature® 300 Metallic PRODUCT SELECTION CHART Signature® 300 Metallic PRODUCT Signature® 300 Signature® 200 Galvalume Plus® 24 Ga. 22 Ga. 24 Ga. 22 Ga. 24 Ga. 22 Ga. 24 Ga. 22 Ga. z z SuperLok® HS 16" Wide 12" Wide Signature is a registered trademark of NCI Group, Inc. Galvalume Plus is a registered trademark of BIEC International. z — Available in any quantity. — Minimum quantity may be required. Other colors, finishes, gauges, and materials available; please inquire. * Striated panels are standard to reduce “oil canning”. CAUTION Diaphragm capabilities and purlin stability are not provided by manufactures SuperLok® roof system. Therefore, other bracing may be required to conform to A.I.S.C. or A.I.S.I. specifications. SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-3 SuperLok® ROOFING SYSTEM ARCHITECT/ENGINEER INFORMATION 1. SuperLok® is a mechanically seamed roof system. SuperLok® panels are available in 12" and 16" widths. Factory applied mastic inside of female leg of panel is standard. 2. SuperLok® is a structural roofing panel. This panel can be installed directly over purlins or bar joists. It does not require a solid substructure for support. The SuperLok® roof system has several different UL 90 construction numbers. 3. SuperLok® is recommended for roof slopes of ¹⁄₂:12 or greater. 4. Weathertight and aesthetically pleasing endlaps may be accomplished through the use of swaged and prepunched panels. 12" wide panels are not prepunched for endlaps. The manufacturer provides a prepunched back-up plate at the endlap for weathertightness. Swaged endlaps require the roof erection to proceed from right to left as viewed from the eave looking toward the ridge. Roofs with no endlaps and less than 6:12 may be erected from either direction. 5. Heavier gauges, striations and embossing minimize oil canning. Industry standard is a minimum 24 gauge material. Striations are standard to reduce oil canning. Oil canning is not a cause for rejection. 6. Substructure must be on an even plane from eave to ridge to avoid panel distortion (¹⁄₄" in 20', ³⁄₈" in 40' tolerance). 7. All panels require end sealant at eave and valley conditions; however, for illustration purposes, this sealant is not shown on all drawings. 8. For proper fastener application, see Product Checklist. 9. All perimeter trim dimensions in this manual are based on a wall panel thickness of 1¹⁄₄" ("PBR" Panel). Any variation from this wall panel thickness may affect the perimeter trim dimensions. 10. The information in this manual is believed to be correct and accurate. 11. Drawings in this manual utilize the low floating clip. Clips are available in low or high fixed, low or high floating and utility. 12. Avoid restricting the thermal expansion and contraction of the SuperLok® panels. (ie: Do not attach panel to the substructure at both the eave and ridge.) However, panels must be attached to the substructure at one end to prevent their sliding downslope. 13. SuperLok® panels are not designed to be work platforms. Avoid any unnecessary foot traffic on SuperLok® panels. If foot traffic is required, protect the roof panels by using soft soled shoes and some type of roof pad, temporary deck, or walkway. 14. WARNING: Light transmitting panels are not designed or intended to bear the weight of any person walking, stepping, standing or resting on them. THE MANUFACTURER DISCLAIMS ANY WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, that any person can safely walk, step, stand or rest on or near these light transmitting panels or that they comply with any OSHA regulation. 15. A vapor retarder may be necessary to protect roofing components when high interior humidity is a factor. The need for a vapor retarder, as well as the type, placement and location should be determined by an architect or engineer. The following are examples of conditions that may require a vapor retarder: (A) Projects where outside winter temperatures below 40°F are anticipated and where average winter interior relative humidity of 45% or greater is expected. (B) Building usages with high humidity interiors, such as indoor swimming pools, textile manufacturing operations, food, paper or other wet-process industrial plants. (C) Construction elements that may release moisture after the roof is installed, such as interior concrete and masonry, plaster finishes and fuel burning heaters. 16. Field cutting of the panels should be avoided where possible. If field cutting is required, the panels must be cut with nibblers, snips, or shears to prevent edge rusting. Do not cut the panels with abrasive saw blades, grinders, or torches. CAUTION Application and design details are for illustration purposes only, and may not be appropriate for all environmental conditions or building designs. Projects should be engineered to conform to applicable building codes, regulations, and accepted industry practices. SL-4 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® ENGINEERING IMPORTANT READ THIS FIRST CAUTION The use of any field seaming machine other than that provided by the manufacturer will damage the panels and void all warranties and will void all engineering data. Low Floating System - With or without ³⁄₈" thermal spacer. See Insulation/Thermal Spacer Selection Chart below. High Floating System - With ³⁄₈", ⁵⁄₈" or 1" thermal spacer. See Insulation/Thermal Spacer Selection Chart below. Thermal calculations should be performed for each project to ensure that the thermal movement of the roof is not greater than the floating clip’s capacity. Various densities of blanket insulation may affect the installation and or the appearance of a metal roof system. The installer is responsible for selecting the proper clip and thermal spacer for their conditions. Insulation/Thermal Spacer Selection Chart Insulation Thickness Low System High System No Insulation ³⁄₈" Thermal Spacer High System Not Recommended 3" Insulation Thermal Spacer Not Recommended ⁵⁄₈" Thermal Spacer 4" Insulation Thermal Spacer Not Recommended ³⁄₈" Thermal Spacer 6" Insulation Low System Not Recommended Thermal Spacer Not Recommended Warning As with all standing seam roof systems, sound attenuation (example: blanket insulation) should be installed between the panels and open framing, such as purlins or joists, to prevent “roof rumble” during windy conditions. Applications over solid deck such as rigid insulation over a metal deck or a wood deck may require additional acoustical consideration to ensure that thermal vibration noises are isolated from the building interior. This is especially important if the bottom of the deck is left open to the interior or in cathedral ceiling applications. A vapor retarder may be necessary to protect roofing components when high humidity is a factor. The need for a vapor retarder, as well as the type, placement and location should be determined by an architect or engineer. The following are examples of conditions that may require a vapor retarder: (A) a project where outside winter temperatures below 40 degrees F. are anticipated and where average winter interior relative humidity of 45% or greater is expected. (B) building usages with high humidity interiors such as indoor swimming pools, textile manufacturing operations, food, paper or other wet-process industrial plants. (C) Construction elements that may release moisture after the roof is installed, such as interior concrete, masonry or plaster work and fuel burning heaters. Thermal Spacer Disclaimer The above thermal spacer chart is intended to be used as a general guideline only. Because of the various densities of insulation currently available, the manufacturer cannot guarantee that this chart will be accurate in all situations. Further, the manufacturer does not specifically require that the roofing contractor use thermal spacers with it’s SuperLok® roof system. However, please review the following information: • Although the manufacturer does not require a thermal spacer, the architect or building owner may. • In certain environments, the compression of the fiberglass insulation, without a thermal spacer, may create a thermal break which can cause condensation to form on the purlins/joists. • On uninsulated buildings, eliminating the thermal spacer: (1) may cause “roof rumble” and (2) you may encounter problems holding panel module. • When a high clip is used without a thermal spacer: (1) you may encounter problems holding panel module and (2) foot traffic on the panel ribs may result in bent clips. • Using a low clip with too much insulation or too thick of a thermal spacer: (1) may cause “purlin read” (2) may cause difficulty in properly installing the panel side laps, and (3) you may encounter problems holding panel module. SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-5 SuperLok® ENGINEERING UNDERWRITERS LABORATORIES APPROVAL SuperLok® Substrate UL-2218 Impact Resistance UL-263 Fire Rating UL-580 Rating 5'-0 ¹⁄₁₆" Open Framing Class 4 Class A Class 90 N/A 5'-0 ¹⁄₄" Open Framing Class 4 Class A Class 90 24 min. ** 5'-0 ¹⁄₄" Open Framing Class 4 Class A Class 90 16" 24 min. ** 2'-6" Composite System Class 4 Class A Class 90 437 16" 24 min. ** 5'-0" Plywood Class 4 Class A Class 90 449 16" 24 min. * 5'-0" Open Framing Class 4 Class A Class 90 451 16" 24 min. * 2'-0" Composite System Class 4 Class A Class 90 452 16" 24 min. * 2'-0" Composite System Class 4 Class A Class 90 487 16" 24 min. ** 4'-0" Composite System Class 4 Class A Class 90 Construction Number Panel Width (In.) Clip Clip Type Spacing Gauge 90 16" 24 min. * 176 16" 24 min. 180 16" 238B * Fixed or Floating (high or low) ** Fixed or Floating (high, low, or utility) NOTES: 1. Tests procedures are in accordance with Underwriters Laboratories Standard UL-580 under “Tests For Uplift Resistance of Roof Assemblies”. 2. A detailed installation method is available for each Construction Number above and can be found in the UL Roofing Materials and Systems Directory. The panels must be installed in a certain manner to achieve the published results. 3. The panel qualifies for a Class A fire rating in compliance with Underwriters Laboratories Standard UL-263 when installed over a non-combustible substrate. A Class C fire rating can be obtained over a combustible deck. 4. The panel system qualifies under the following Fire Resistance Design Numbers: P225, P227, P230, P237, P265, P268, P508, P510, P512, P701, P711, P720, P722, P726, P731, P734, P801, P815, and P819. Refer to the UL Fire Resistance Directory for specific construction methods and hourly ratings. 5. SuperLok® panels carry a Class 4 rating under UL-2218 “Test Standard For Impact Resistance”. FACTORY MUTUAL APPROVAL SuperLok® Panel Width Gauge Clip Type Clip Spacing Hail Damage Rating ASTM E108 Fire Rating FM Windstorm Rating 16 24 Floating 4’-0” Class 1-SH Class A Class 1-90 16 22 Floating 5’-0” Class 1-SH Class A Class 1-105 16 22 Floating 4’-0” Class 1-SH Class A Class 1-135 NOTES: 1. Tests procedures are in accordance with Factory Mutual Research Corportion (FMRC) Standard 4471. 2. A detailed test report is available for each product above. The panels must be installed in a specific manner to achieve the published results. Contact MBCI for more information. SuperLok® is a registered trademark of NCI Building Systems, L.P. Galvalume® is a registered trademark of BIEC International, Inc. Vise-Grip® is a registered trademark of American Tool Companies, Inc. FLORIDA BUILDING CODE PRODUCT APPROVAL Double-Lok® Roofing System details and engineering load tables have been examined by the State of Florida and comply with the 2010 Florida Building Code Product Approval Number (FL#11819.4). SL-6 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® ENGINEERING SuperLok® Panel 12" ¹⁄₁₆" 2" SECTION PROPERTIES NEGATIVE BENDING POSITIVE BENDING PANEL Fy WEIGHT Ixe Sxe Maxo Ixe Sxe Maxo GAUGE (KSI) (PSF) (IN.4/FT.) (IN.3/FT.) (KIP-IN.) (IN.4/FT.) (IN.3/FT.) (KIP-IN.) 24 50 1.47 0.0756 0.0711 2.1307 0.1667 0.1025 3.0693 22 50 1.83 0.1053 0.1027 3.0751 0.2231 0.1387 4.1551 NOTES: 1. All calculations for the properties of SuperLok panels are calculated in accordance with the 2012 edition of the North American Specification For Design Of Cold-Formed Steel Structural Members. 2. Ixe is for deflection determination. 3. Sxe is for bending. 4. Maxo is allowable bending moment. 5. All values are for one foot of panel width. The Engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommended that the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed Steel Structural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria for coldformed steel components. Along with the Specification, the designer should reference the most current building code applicable to the project jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired, please contact the manufacturer. SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-7 SuperLok® ENGINEERING SuperLok® Panel 12" ¹⁄₁₆" 2" ALLOWABLE UNIFORM LOADS IN POUNDS PER SQUARE FOOT 24 Gauge (Fy = 50 KSI) SPAN TYPE LOAD TYPE SPAN IN FEET 2.5 3.0 3.5 4.0 4.5 5.0 5.5 SINGLE LIVE 216.0 180.0 154.3 127.9 101.0 81.8 67.6 2-SPAN LIVE 216.0 157.8 116.0 88.8 70.1 56.8 47.0 3-SPAN LIVE 216.0 180.0 144.9 111.0 87.7 71.0 58.7 4-SPAN LIVE 216.0 180.0 135.3 103.6 81.9 66.3 54.8 2.5 3.0 3.5 4.0 4.5 5.0 5.5 22 Gauge (Fy = 50 KSI) SPAN TYPE LOAD TYPE SPAN IN FEET SINGLE LIVE 313.0 260.8 223.6 173.1 136.8 110.8 91.6 2-SPAN LIVE 313.0 227.8 167.4 128.1 101.2 82.0 67.8 3-SPAN LIVE 313.0 260.8 209.2 160.2 126.5 102.5 84.7 4-SPAN LIVE 313.0 260.8 195.3 149.5 118.2 95.7 79.1 NOTES: 1. THE ABOVE LOADS ARE NOT FOR USE WHEN DESIGNING PANELS TO RESIST WIND UPLIFT. 2. Strength calculations based on the 2012 AISI Standard “North American Specification for the Design of Cold-formed Steel Structural Members.” 3. Allowable loads are applicable for uniform loading and spans without overhangs. 4. LIVE load capacities are for those loads that push the panel against its supports. The applicable limit states are flexure, shear, combined shear and flexure, web crippling at end and interior supports, and a deflection limit of L/180 under strength-level loads. 5. Panel pullover and Screw pullout capacity must be checked separately using the screws employed for each particular application when utilizing this load chart. 6. The use of any field seaming equipment or accessories including but not limited to clips, fasteners, and support plates other than tha provided by the manufacturer may (eave, backup, rake, etc.) damage panels, void all warranties and will void all engineering data. 7. This material is subject to change without notice. Please contact MBCI for the most current data. The Engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommended that the design professional have a copy of the most current version of the North American Specification for the Design of ColdFormed Steel Structural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria for cold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable to the project jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired, please contact the manufacturer. SL-8 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® ENGINEERING SuperLok® Panel 16" ¹⁄₁₆" 2" SECTION PROPERTIES NEGATIVE BENDING POSITIVE BENDING PANEL Fy WEIGHT Ixe Sxe Maxo Ixe Sxe Maxo GAUGE (KSI) (PSF) (IN.4/FT.) (IN.3/FT.) (KIP-IN.) (IN.4/FT.) (IN.3/FT.) (KIP-IN.) 24 50 1.38 0.0574 0.0538 1.6096 0.1324 0.0779 2.3324 22 50 1.72 0.0794 0.0776 2.325 0.1779 0.1057 3.1654 NOTES: 1. All calculations for the properties of SuperLok panels are calculated in accordance with the 2012 edition of the North American Specification For Design Of Cold-Formed Steel Structural Members. 2. Ixe is for deflection determination. 3. Sxe is for bending. 4. Maxo is allowable bending moment. 5. All values are for one foot of panel width. The Engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommended that the design professional have a copy of the most current version of the North American Specification for the Design of ColdFormed Steel Structural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria for cold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable to the project jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired, please contact the manufacturer. SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-9 SuperLok® ENGINEERING SuperLok® Panel 16" ¹⁄₁₆" 2" ALLOWABLE UNIFORM LOADS IN POUNDS PER SQUARE FOOT 24 Gauge (Fy = 50 KSI) SPAN TYPE LOAD TYPE SPAN IN FEET 2.5 3.0 3.5 4.0 4.5 5.0 5.5 SINGLE LIVE 162.0 135.0 115.7 97.2 76.8 62.2 51.4 2-SPAN LIVE 162.0 119.2 87.6 67.1 53.0 42.9 35.5 3-SPAN LIVE 162.0 135.0 109.5 83.8 66.2 53.7 44.3 4-SPAN LIVE 162.0 135.0 102.2 78.3 61.8 50.1 41.4 22 Gauge (Fy = 50 KSI) SPAN TYPE LOAD TYPE SINGLE LIVE SPAN IN FEET 2.5 3.0 3.5 4.0 4.5 5.0 5.5 233.4 194.5 166.7 131.9 104.2 84.4 69.8 2-SPAN LIVE 233.4 172.2 126.5 96.9 76.5 62.0 51.2 3-SPAN LIVE 233.4 194.5 158.2 121.1 95.7 77.5 64.0 4-SPAN LIVE 233.4 194.5 147.7 113.1 89.3 72.4 59.8 NOTES: 1. THE ABOVE LOADS ARE NOT FOR USE WHEN DESIGNING PANELS TO RESIST WIND UPLIFT. 2. Strength calculations based on the 2012 AISI Standard “North American Specification for the Design of Cold-formed Steel Structural Members.” 3. Allowable loads are applicable for uniform loading and spans without overhangs. 4. LIVE load capacities are for those loads that push the panel against its supports. The applicable limit states are flexure, shear, combined shear and flexure, web crippling at end and interior supports, and a deflection limit of L/180 under strength-level loads. 5. Panel pullover and Screw pullout capacity must be checked separately using the screws employed for each particular application when utilizing this load chart. 6. The use of any field seaming equipment or accessories including but not limited to clips, fasteners, and support plates other than tha provided by the manufacturer may (eave, backup, rake, etc.) damage panels, void all warranties and will void all engineering data. 7. This material is subject to change without notice. Please contact MBCI for the most current data. The Engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommended that the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed Steel Structural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria for coldformed steel components. Along with the Specification, the designer should reference the most current building code applicable to the project jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired, please contact the manufacturer. SL-10 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® GENERAL INFORMATION PRODUCT CHECKLIST SuperLok® Panel Back-Up Plate 16" or 12" 2" • For use at ridge and endlaps • Prepunched • 16 gauge red oxide ¹⁄₁₆" 12" R 16" R Clip, Floating • Low – For use with or without ³⁄₈" thermal spacer. HW-230 R R HW-7766 R 12" Wide HW-7764 16" Wide Rake Support • • • • 20'-0" length 14 gauge red oxide Factory slots For use with low or high clip • High – For use with ³⁄₈", ⁵⁄₈" or 1" thermal spacer. HW-232 R Clip, Fixed • Low – For use with or without ³⁄₈" thermal spacer HW-7712 - Low HW-7722 - High HW-236 R Bearing Plate Standard R R • 16 gauge red oxide • For use with low or utility systems • For use with rigid board insulation • High – For use with ³⁄₈", ⁵⁄₈" or 1" thermal spacer HW-234 R SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION HW-7500 R REV 00.01 SL-11 SuperLok® GENERAL INFORMATION PRODUCT CHECKLIST Eave Plate, Low • 8'-0" length • 14 gauge • Red Oxide Eave Plate, High HW-7600 R Floating Eave Plate, Low • 8'-0" length • 14 gauge • Red Oxide HW-7616 R Floating Eave Plate, High • 14 gauge • Red Oxide Mid-Slope Fixed Plate, High HW-7630 (10'-0" Long) R HW-7631 (20'-0" Long) R HW-7632 (6'-0" Long) R SL-12 REV 00.01 • 8'-0" length • 14 gauge • Red Oxide HW-7618 R HW-7617 R Mid-Slope Fixed Plate, Low • 8'-0" length • 14 gauge • Red Oxide SEE www.mbci.com FOR CURRENT INFORMATION • 14 gauge • Red Oxide HW-7637 (6'-0" Long) R HW-7638 (10'-0" Long) R HW-7639 (20'-0" Long) R SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® GENERAL INFORMATION PRODUCT CHECKLIST Valley Support Plate – Low Systems Extended Valley Support Plate – Low Systems SPECIFY ANGLE 17" 14" 1" 1" 90° 90° • Extended Width • Standard Width 10'-0" Long P-106 R • Use Over Purlins/Joists Valley Support Plate - High Systems Valley Support Plate – High Systems SPECIFY ANGLE 12" 1⁷⁄₁₆" SPECIFY ANGLE 135° 1" 10'-0" Long P-101 R • Use Over Purlins/Joists 21" 1⁷⁄₁₆" 1" 135° 135° 135° 1⁹⁄₁₆" 1⁹⁄₁₆" • Standard Width 10'-0" Long P-164 R • Use Over Purlins/Joists • Extended Width • Use Over Purlins/Joists Valley Support Plate – Low Systems Valley Support Plate – Low Systems • Standard Width • Extended Width 10'-0" Long P-105 R • Use Over Rigid Insulation Hip Support Plate - High or Low Floating Systems • Use Over Rigid Insulation 10'-0" Long P-162 R 10'-0" Long P-100 R Hip Support Plate – Low Floating Systems " 10¹¹⁄₁₆ 1" SPECIFY ANGLE • Use Over Purlins/Joists 10'-0" Long P-141 R Ridge/Hip Support Plate – Low Fixed Systems • Use with all Substrates SUBJECT TO CHANGE WITHOUT NOTICE 10'-0" Long P-145 R • Use Over Solid Substrate 10'-0" Long P-140 R Ridge/Hip Support Plate – High Fixed Systems • Use with all Substrates SEE www.mbci.com FOR CURRENT INFORMATION 10'-0" Long P-155 R REV 00.01 SL-13 SuperLok® GENERAL INFORMATION PRODUCT CHECKLIST • ³⁄₁₆" x 2 ¹⁄₂" x 20' • For use at valley when using exposed fasteners • For use with roof curbs Tape Sealer • Polystyrene block used to increase the insulation capacity along the purlins Thermal Spacer Triple Bead HW-502 R • ³⁄₁₆" x ⁷⁄₈" x 25' • For use at eave, ridge, endlaps and trim connections HW-583 ³⁄₈" R Tri-Bead HW-582 ⁵⁄₈" R HW-504 R Tape Sealer-Swaged HW-581 Panel Hemming Tool 1" R Tube Sealant Urethane (White) - HW-540 R Urethane (Gray) - HW-541 R Outside Closure Urethane (Bronze) - HW-542 R HW-602 R HW-515 R • 24 gauge • Painted Non-Skinning Butyl - HW-549 R Light Transmitting Panel (Reinforced) ‡ • Std. Insulated - HW- 1621S R 12" wide HW-446 R 16" wide HW-440 R • Std. Uninsulated - HW-1620S R • UL 90 Insulated - HW-1617S R • UL 90 Uninsulated - HW-1616S R ‡ It is the user’s responsibility to ensure that the installation and use of all light transmitting panels comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding all light transmitting panels with screens, fixed standard railings, or other acceptable safety controls that prevent fall-through. SL-14 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® GENERAL INFORMATION PRODUCT CHECKLIST Ridge Flashing • Includes Cinch Angles and Flexible Membrane • Specify Roof Slope Floating Peak Box "A" 2¹⁄₂" COLOR 120° FL-125 R Length - 2'-1" Girth - 33¹⁄₄" • For use with FL-200, FL-202, FL-213, FL-214, FL-300, FL-302, FL-540 or FL-541 Ridge Flashing 120° " 1¹⁄₄ PART NO. ROOF PITCH DIM. “A” FL-200 ¹⁄₂-3³⁄₄:12 3¹⁄₂" FL-202 3¹³⁄₁₆-6:12 4¹⁄₂" FL-213 ¹⁄₂-3³⁄₄:12 6¹⁄₂" FL-214 3¹³⁄₁₆-6:12 7¹⁄₂" Ridge Flashing for Perforated Vent Drip "A" For use without ventilator 18" Peak purlin spacing For use without ventilator 24" Peak purlin spacing FL-126 R Length - 2'-6" Girth - 37¹⁄₄" • For use with FL-205, FL-207, FL-303, FL-304, FL-543 or FL-544 Ridge Flashing R R R R Perforated Vent Drip COLOR 1 ¹⁄₄" PERFORATED • Use w ith FL-300, FL-302, FL-303 or FL-304 Ridge Flashing " ¹⁄₂ " 2 ¹⁄₂ NOTE 1" 1" 1" ROOF PITCH DIM. “A” NOTE FL-300 ¹⁄₂-3³⁄₄:12 4¹⁄₂" FL-302 3¹³⁄₁₆-6:12 5¹⁄₂" For use with perforated vent drip (FL-254) 18" Peak purlin spacing R R FL-303 ¹⁄₂-3³⁄₄:12 7¹⁄₂" FL-304 3¹³⁄₁₆-6:12 8¹⁄₂" For use with perforated vent drip (FL-254) 24" Peak purlin spacing R R 1" PART NO. Ridge/Hip Flashing - Fixed "A " 3¹⁄₄" FL-254 R 24 Gauge Material “Z” Closure • Use at Hips 1" "A" COLOR COLOR 1" FL-361 R 24 Gauge Material PART NO. ROOF PITCH DIM. “A” FL-209 ¹⁄₂-3³⁄₄:12 6" FL-211 3¹³⁄₁₆-6:12 7" FL-212 All Pitches 11¹⁄₂" • Specify open hem when using with continuous cleat Sculptured High Side Eave Trim NOTE 5 ¹⁄₂" For use without vent material 18" Peak purlin spacing For use without vent material 24" Peak purlin spacing R R R 4 ³⁄₄" 2" 4 ³⁄₄" 102° 102° 90° + ° of ROOF SLOPE 1 ³⁄₄" COLOR Ridge End Cap • Specify Ridge to be used and Roof Slope FL-201 SUBJECT TO CHANGE WITHOUT NOTICE R 135° " ⁵⁄₈ PART NO. ROOF PITCH DIM. A FL-265 ¹⁄₄-1³⁄₄:12 2" FL-265B 1¹³⁄₁₆-4:12 3¹¹⁄₁₆" SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 R R SL-15 SuperLok® GENERAL INFORMATION PRODUCT CHECKLIST Sculptured Gutter - Standard ¹⁄₂" 1" 90° 4 ³⁄₄" • For use with Sculptured Gutter Gutter Strap 90°-° of 1" ROOF SLOPE 10" 102° 156° DIM "A" COLOR 4 ³⁄₄" 102° 4 ¹⁄₂" FL-246 R 18 Gauge Material Gutter Ends Left or Right 90°+° of • Use with all Sculptured or Style Gutters • End Caps will be made to fit gutter ordered • Specify left or right • Specify gutter part number ROOF SLOPE PART NO. ROOF PITCH DIM.“A” GIRTH FL-248A ¹⁄₂-4:12 7⁵⁄₁₆" 23³⁄₁₆" FL-248B 4⁹⁄₁₆-6:12 7¹⁵⁄₁₆" 24⁷⁄₁₆" R R FL-245 R Variable Termination Sculptured Rake Trim COLOR 3 ⁵⁄₈ " ³⁄₄ " 4 ³⁄₄" 90° 156° 9" ³⁄₄" 102° 90° 4 ³⁄₄" COLOR 90° FL-117 R Rake Slide - High Wind ¹⁄₂” 1³⁄₄ " 2" 135° ⁵⁄₈" ⁄₈” ⁷ FL-111 R ⁵⁄₈” 90° Sculptured Eave Trim ³⁄₄” COLOR 2" 156° 2 ¹⁄₂" 4 ³⁄₄" Eave with Extended Drip Edge 102° 2¹ ⁄₂" 102° 90°-° of ROOF SLOPE 1 ³⁄₄" " ⁵⁄₈ COLOR 135° Specify Roof Pitch FL-215 R 24 Gauge Material 90° ¹⁄₂" 2 ⁵⁄₈" FL-253 R Box High Side Eave Trim • Use with Roof Slopes ¹⁄₂ - 6:12 • Specify open hem when using with continuous cleat 1¹ ⁄₂" SPECIFY ANGLE ⁵⁄₈ " 3" COLOR COLOR 10 ¹⁄₄ Box Eave Trim " 3¹ ⁄₂" COLOR 5" SPECIFY ANGLE SPECIFY ANGLE ⁵⁄₈" Specify Roof Pitch SL-16 45° REV 00.01 FL-331 R SEE www.mbci.com FOR CURRENT INFORMATION T-5151 R • Specify open hem when using with continuous cleat 4" ⁵⁄₈ " FL-326 R SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® GENERAL INFORMATION PRODUCT CHECKLIST Parapet Rake Cleat High Wind Box Rake Trim 3" COLOR 1" ³⁄₄" 5" 1" " ⁵⁄₈ COLOR ³⁄₄" FL-306 R Box Gutter with Drip Edge Gutter Strap 1 ¹⁄₂" 6" F-292 R • For use with Box Gutter ⁵⁄₈" 1" 2" 5 ¹⁄₂" SPECIFY ANGLE 4 ¹⁄₂" 10" 5 ¹⁄₄" COLOR T-5271 R Specify Roof Pitch Parapet High Side Eave Flashing - Fixed • Specify Roof Slope 6" Gutter Ends Left or Right • Use with T-5271Box Gutter with Drip Edge • Specify left or right COLOR 5 ¹⁄₂" FL-276 R T-5291 R Parapet High Side Eave Flash Floating Parapet Rake Flash COLOR 4" FL310 R 24 Gauge Material "A" COLOR 4 ³⁄₄" OPEN HEM "A" 2 ¹⁄₂" 1" PART NO. 1¹⁄₄" DIM. A FL-285 3" FL-286 5" FL-287 7" R R R PART NO. DIM. A FL-275 3¹⁄₂" FL-274 4¹⁄₂" R R NOTE: All trim to be 26 gauge material unless noted. Refer to current price book for part numbers and descriptions. SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-17 SuperLok® GENERAL INFORMATION PRODUCT CHECKLIST Continous Cleat Offset Cleat 1¹⁄₂" ¹⁄₂" 2¹⁄₂" ¹⁄₈" 1¹⁄₂" 135° " ¹⁄₂ FL-337 R 24 Gauge Material FL-338 R 24 Gauge Material Alternate Counter Flash Counter Flash ¹⁄₂" " ⁵⁄₈ 30° 90° COLOR 1" ¹⁄₂" 1" 2¹⁄₂" 150° ⁵⁄₈" ³⁄₄" COLOR FL-341 R 24 Gauge Material Box Panel Cap Trim FL-343 R 24 Gauge Material Offset Panel Cap Trim 3¹⁄₂" 2 ¹⁄₂" 95° SPECIFY ANGLE 2" 4" ¹⁄₂" Standard Valley - Utility, Low and High Systems Extended Valley - Utility, Low and High Systems SPECIFY ANGLE 2" 16 " 2" 11 ¹⁄₂" REV 00.01 SPECIFY ANGLE ¹⁄₂" FL-271 R SPECIFY ANGLE SL-18 1¹⁄₈" FL-272 R Specify Roof Pitch 24 Gauge Material 1³⁄₈" 45° 45° FL-705 R 24 Gauge Material SEE www.mbci.com FOR CURRENT INFORMATION FL-711 R SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® GENERAL INFORMATION PRODUCT CHECKLIST Fastener #1B • Clip to purlin (Up to 4" insulation between panel and purlin) Fastener #1E • Panel to eave plate or eave strut • Rake trim to roof panel • Standard endlaps • Panel to valley plate • Outside closure to panel with back-up plate or support plate ¹⁄₄"-14 x 1 ¹⁄₄" Long Life Self Driller ⁵⁄₁₆" Hex Washer Head, with sealing washer Fastener #2A ¹⁄₄"-14 x 1 ¹⁄₄" Self Driller ⁵⁄₁₆" Hex Washer Head with no washer Fastener #142 R R • Use in place of Fasteners #1E, #2B and #4 at all strip outs • Clip to purlin (Over 4" insulation between panel and purlin) 17 x 1" Long Life AB ⁵⁄₁₆" Hex Washer Head, with sealing washer Fastener #6A ¹⁄₄"-14 x 1 ¹⁄₂" Self Driller ⁵⁄₁₆” Hex Washer Head with no washer Fastener #2B R • Clip to joist R • Endlap over plywood 12-24 x 1 ¹⁄₄" Tek® 5 Self Driller ⁵⁄₁₆" Hex Washer Head, with no washer Fastener #4 ¹⁄₄"-14 x 1" Long Life AB ³⁄₈" Hex Washer Head, with sealing washer Fastener #5 • Rake support to purlin (Floating System Only) • Floating eave plate to eave strut ¹⁄₄"-14 x 1 ¹⁄₄" Shoulder Tek® 2 Self Driller ⁵⁄₁₆" Hex Washer Head, with no washer SUBJECT TO CHANGE WITHOUT NOTICE R R R • Ridge and other flashing to outside closure • Gutter to panel • Gutter to strap • Trim to trim connections • Sculptured eave trim to panel ¹⁄₄"-14 x ⁷⁄₈" Long Life Lap Tek® Self Driller ⁵⁄₁₆" Hex Washer Head, with sealing washer Fastener #11 R • Special application fastener • For attaching trim to masonary walls R ¹⁄₄" x 1 ¹⁄₄" Nail Drive Masonry Anchor SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-19 SuperLok® GENERAL INFORMATION PRODUCT CHECKLIST Fastener #12A • Rake angle to purlin • Hip and valley support plates to purlins • Valley flashing to valley support plate R 12 x 1" #2 Phillips/Square Drive Pancake Head Driller Fastener #14A • Outside closure to angle on floating hip detail R Stainless Steel Pop Rivet ¹⁄₈" diameter x ³⁄₈" grip range Fastener #226 • Dekstrip to Expansion Ridge/Expansion Lap ³⁄₁₆" x ⁹⁄₁₆" Rivet Cendalum Closed End Rivet Fastener #18 R • Panel clips to wood deck • Outside closure to panel over wood deck Fastener #13A • Offset cleat to plywood • Rake angle to plywood 12 x 1" #2 Phillips/Square Drive Pancake Type “A” Fastener #14 • Trim to trim connections Stainless Steel Pop Rivet ¹⁄₈" diameter x ³⁄₁₆" grip range Fastener #1 Fastener #228 R Deck Screw Fastener #210 14 x 3" 10 x ¹⁄₂" Aluminum Grommet Washer REV 00.01 R • 18 Gauge maximum drilling thickness • Dekstrip to Expansion Ridge/Expansion Lap Fastener #209 14 x 2" SL-20 R • Panel endlaps over solid substrate ¹⁄₄"-14 x ⁵⁄₈" Long Life Type B with washer 14 x 1” Type A ⁵⁄₁₆" Hex Washer Head, with ⁵⁄₈" O.D. washer R • Eave plate to eave strut • Mid-slope fixed plate to purlin • Rake support to angle (Fixed system only) ¹⁄₄"-14 x 1" Self Driller ⁵⁄₁₆" Hex Head, with ⁵⁄₈" O.D. washer Fastener #46 R R Fastener #211 14 x 4" Fastener #15D 14 x 6" SEE www.mbci.com FOR CURRENT INFORMATION R R R R SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® GENERAL INFORMATION SuperLok® Panel Orientation INSTALLATION GUIDELINES I. Jobsite Storage and Handling A. Check the shipment against the shipping list. B. Damaged material must be noted on Bill of Lading. C. Panel crates should be handled carefully. A spreader bar of appropriate length is recommended for hoisting. D. Check to see that moisture has not formed inside the bundles during shipment. If moisture is present, panels should be uncrated and wiped dry, then restacked and loosely covered so that air can circulate between the panels. II. Application Checklist A. Check substructure for proper alignment and uniformity to avoid panel distortion. B. Periodic check of panel alignment is crucial to proper panel alignment. C. If there is a conflict between this manual and the project erection drawings, the erection drawings will take precedence. III. LTP Warning A. WARNING: Light transmitting panels are not designed or intended to bear the weight of any person walking, stepping, standing or resting on them. THE MANUFACTURER DISCLAIMS ANY WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, that any person can safely walk, step, stand or rest on or near these light transmitting panels or that they comply with any OSHA regulation. LEFT TO RIGHT RIGHT TO LEFT SHEETING DIRECTION FOR ROOFS WITHOUT PANEL ENDLAPS SUBJECT TO CHANGE WITHOUT NOTICE RIGHT TO LEFT ONLY SHEETING DIRECTION FOR ROOFS WITH PANEL ENDLAPS SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-21 SuperLok® GENERAL INFORMATION PREPARATORY REQUIREMENTS 1. For the purpose of this manual, we have assumed that the SuperLok® roof will be installed over purlins and an eave gutter will be installed. Please refer to the Design Section of the manuals for details of SuperLok® over other substrates. 2. A rake angle or an alternate structural flat surface must be installed on top of the purlins to accept the rake support. 3. All primary and secondary framing must be erected, plumbed and squared with bolts tightened according to accepted building practices. 4. The substructure (eave to ridge) must be on plane (¹⁄₄" in 20' or ³⁄₈" in 40' tolerance). 5. It is critical that the purlins or bar joists at the ridge and endlaps be located exactly as detailed and that they are straight from rafter to rafter. Any mislocation or bowing of these members can cause the fasteners at the ridge or endlaps to foul as the panels expand and contract. 6. The manufacturer recommends the use of a screw gun with a speed range of 0-2000 RPM to properly install all fasteners referenced in this manual. Tools rated to 4000 RPM should never be used for self drilling fasteners typically supplied with metal roof and wall systems. 7. Field cutting of the panels should be avoided where possible. If field cutting is required, the panels must be cut with nibblers, snips, or shears to prevent edge rusting. Do not cut the panels with abrasive saw blades, grinders, or torches. CAUTION Avoid restricting the thermal expansion and contraction of the SuperLok® panels. (i.e., Do not attach panel to the substructure at either the eave and ridge.) WARNING: Light transmitting panels are not designed or intended to bear the weight of any person walking, stepping, standing or resting on them. THE MANUFACTURER DISCLAIMS ANY WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, that any person can safely walk, step, stand or rest on or near these light transmitting panels or that they comply with any OSHA regulation. NOTE It is the responsibility of the erector to install this roof using safe construction practices that are in compliance with OSHA regulations. The manufacturer is not responsible for the performance of this roof system if it is not installed in accordance with the instructions shown in this manual. Deviations from these instructions and details must be approved in writing by the manufacturer. CAUTION Diaphragm capabilities and purlin stability are not provided by the SuperLok® roof system. Therefore, other bracing may be required. SL-22 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® GENERAL INFORMATION UNLOADING Upon receiving material, check shipment against shipping list for shortages and damages. The manufacturer will not be responsible for shortages or damages unless they are noted on the shipping list. Each bundle should be lifted at its center of gravity. Where possible, bundles should remain banded until final placement on roof. If bundles must be opened, they should be retied before lifting. RIGHT WAY When lifting bundles with a crane, a spreader bar and nylon straps should be used. NEVER USE WIRE ROPE SLINGS, THEY WILL DAMAGE THE PANELS. WRONG WAY When lifting bundles with a forklift, forks must be a minimum of five feet apart. Do not transport open bundles. Drive slowly when crossing rough terrain to prevent panel buckling. RIGHT WAY CAUTION WRONG WAY SUBJECT TO CHANGE WITHOUT NOTICE Improper unloading and handling of bundles and crates may cause bodily injury or material damage. The manufacturer is not responsible for bodily injuries or material damages during unloading and storage. SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-23 SuperLok® GENERAL INFORMATION UNLOADING (Continued) BLOCK AND BAND This method of bundling is used for orders that are to be picked up by the customer or shipped by common carrier. 2 x 4’s are strapped under the bundles to allow access for straps or a forklift. Bundles less than 25' long may be handled by a forklift. The forklift should have at least 5' between forks. Bundles longer than 25' should be lifted utilizing a spreader bar with nylon straps. FULL CRATE This method is used on all overseas shipments or by customer’s order. Handling requirements are the same as block and band. SL-24 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® GENERAL INFORMATION HANDLING/PANEL STORAGE Standing on one side of the panel, lift it by the seam. If the panel is over 10' long, lift it with two or more people on one side of the panel to prevent buckling. Do not pick panels up by the ends. RIGHT WAY NOTE: Protective gloves and safety glasses should always be used while handling panels. OSHA safety regulations must be followed at all times. WRONG WAY Store bundled sheets off the ground sufficiently high to allow air circulation beneath bundle and to prevent rising water from entering bundle. Slightly elevate one end of bundle. Prevent rain from entering bundle by covering with tarpaulin, making provision for air circulation between draped edges of tarpaulin and the ground. PROLONGED STORAGE OF SHEETS IN A BUNDLE IS NOT RECOMMENDED. If conditions do not permit immediate erection, extra care should be taken to protect sheets from white rust or water marks. Check to see that moisture has not formed inside the bundles during shipment. If moisture is present, panels should be uncrated and wiped dry, then restacked and loosely covered so that air can circulate between the panels. SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-25 SuperLok® GENERAL INFORMATION PROPER HANDLING, STORAGE AND MAINTENANCE OF PAINTED AND GALVALUME PLUS® PANELS PANEL HANDLING • All panel bundles must be inspected during unloading and carrier advised immediately if damage is noted. • Never unload or move panel bundles that have been opened without adequately clamping them. Without the banding to hold the bundle stable, panels may shift during unloading or movement, causing the bundle to fall. • Never use wire slings to unload or move panel bundles. • When unloading or moving panel bundles over 20' long, a spreader bar may be required. It is the erector’s responsibility to determine the location and number of lift points required to safely unload or move panel bundles. • When handling individual panels, always wear protective gloves. OSHA safety regulations must be followed at all times. • When cutting panels, always wear all required safety equipment such as safety glasses and gloves. Cut panels with nibblers, shears or snips. Do not use abrasive blade saws as these will melt the Galvalume® coating causing the panel to edge rust which will void the Galvalume® and Paint warranties. Drilling fasteners into panels will create metal filings that will rust and create an unsightly stain. Metal filings must removed by sweeping or wiping down panels immediately after installation to avoid this occurrence. PANEL STORAGE • If water is permitted to enter panel bundles, it is necessary to open bundles, separate the panels and dry all surfaces. • Store bundled panels off the ground sufficiently high to allow air circulation beneath bundle and to prevent rising water from entering bundle. Slightly elevate one end of bundle. • Prevent rain from entering bundle by covering with tarpaulin, making provision for air circulation between draped edges of tarpaulin and the ground. • Prolonged storage of panels in a bundle is not recommended. If conditions do not permit immediate erection, extra care should be taken to protect panels from white rust or water marks. If panels have not been erected within three weeks of receipt, the panels should be removed from the bundle for inspection. Condensation may cause damage to panels. The manufacturer’s Paint and Galvalume® warranties do not cover damage caused by improper panel storage. PANEL MAINTENANCE • Never allow Galvalume® panels to come into contact with or water runoff from dissimilar materials such as copper, lead, or graphite. These materials will cause galvanic corrosion of the panels and will void the Galvalume® warranty. This includes treated wood and AC condensate, both of which contain copper compounds. This also applies to painted panels. • Always use long life fasteners in all exposed fastener applications. Non long life fasteners can rust through the panel at each exposed fastener location. Use of non long life fasteners in exposed applications will void the Galvalume® and Paint warranties. • Panels should be protected against exposure to masonry products, strong acids or bases and solvents. Exposure to these agents may etch or stain Galvalume Plus® panels and cause painted panels to blister or peel. • Never allow anyone to apply any coating or patching material to the panel surface. These products may contain chemicals that will adversely affect the Galvalume Plus® or paint coating. Also, water may become trapped between the coating material and the panel, causing premature corrosion. If you have any question as to proper methods to use in the handling, storage or maintenance of these panels, call your nearest manufacturer representative. SL-26 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® GENERAL INFORMATION • Never allow anyone to apply any coating or patching material to the panel surface. These products may contain chemicals that will adversely affect the Galvalume Plus® or paint coating. Also, water may become trapped between the coating material and the panel, causing premature corrosion. If you have any question as to proper methods to use in the handling, storage or maintenance of these panels, call your nearest manufacturer representative. NOTICE Uniform visual appearance of Galvalume Plus® coated panels cannot be guaranteed. The Galvalume Plus® coating is subject to variances in spangle from coil to coil which may result in a noticeable shade variation in installed panels. The Galvalume Plus® coating is also subject to differential weathering after panel installation. Panels may appear to be different shades due to this weathering characteristic. If uniform visual appearance is required, the manufacturer recommends that our prepainted Signature® 200 or Signature® 300 panels be used in lieu of Galvalume Plus®. Shade variations in panels manufactured from Galvalume Plus® coated material do not diminish the structural integrity of the product. These shade variations should be anticipated and are not a cause for rejection. SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-27 SuperLok® INSTALLATION SEQUENCE STEEL LINE RAKE ATTACHMENT RAKE ANGLE FASTENER #12A WALL PANEL Attach the rake angle to the purlin with the Fastener #12A. Attach the rake support on top of the rake angle with the proper self-drilling fasteners (See “Rake Support Fastener Requirements” Below) on 2'-0" centers with a fastener in the first and last prepunched slot. The vertical leg is to be installed flush with the steel line. IT IS IMPORTANT THAT THE RAKE SUPPORT IS INSTALLED STRAIGHT AND SQUARE WITH THE EAVE AS IT CONTROLS THE ALIGNMENT OF THE ROOF SYSTEM. PURLIN Install 6" long pieces of double faced tape (not by Manufacturer) on 3'-0" centers to the top of the horizontal leg of the rake support. This will help hold the insulation in place at the rake. RAKE ANGLE ATTACHMENT RAKE SUPPORT FASTENER REQUIREMENTS FLOATING SYSTEM • Fixed System - Fastener #1 • Floating System - Fastener #5 FASTENER #5 RAKE SUPPORT *DOUBLE FACED TAPE FIXED SYSTEM FASTENER #1 CAUTION (For Floating Systems Only) It is important that shoulder fasteners are installed through the CENTER of the slotted holes of the rake support to allow for expansion and contraction. RAKE SUPPORT ATTACHMENT *Not by Manufacturer SL-28 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® INSTALLATION SEQUENCE WALL PANEL DEPTH FASTENER #14 *DOUBLE FACED TAPE LOW SYSTEM EAVE BOX PANEL CAP TRIM FASTENER #14 EAVE STRUT WALL PANEL 2" MAX. WALL PANEL INSTALLED BEFORE ROOF FASTENER #14 TRI-BEAD TAPE SEALER *DOUBLE FACED TAPE For applications in which the wall panels have already been erected, install box panel cap trim or offset panel cap trim to the eave strut with Fastener #14. Eave trim must be pulled tight to wall panels with Fastener #14 before fastening to eave strut. For applications in which the wall panels have not been erected, use offset panel cap trim. If using panel cap trim, it will space itself for the wall offset panels. Use three Fastener #14 per trim piece. Install Tri-Bead tape sealer along top of the trim. For vinyl insulation, install double faced tape (not by Manufacturer) along the length of the top leg of the trim. Double faced tape must be upslope from Tri-Bead tape sealer. OFFSET PANEL CAP TRIM FASTENER #14 EAVE STRUT 1¹⁄₄" MAX. WALL PANEL INSTALLED BEFORE OR AFTER ROOF FLAT EAVE TRIM FASTENER #14 OFFSET PANEL CAP TRIM FASTENER #4 1" 2" LAP URETHANE SEALANT Lap trim 2". Apply two beads of urethane sealant between the trim pieces, approximately 1" from the end of the bottom piece. Attach trim laps in flat eave trim with Fastener #14. Attach trim laps on panel cap trim with Fastener #4. BOX PANEL CAP TRIM ENDLAP DETAIL URETHANE SEALANT 2" LAP 1" OFFSET PANEL CAP TRIM ENDLAP DETAIL *Not by Manufacturer SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-29 SuperLok® INSTALLATION SEQUENCE HIGH EAVE PLATE EAVE STRUT FASTENER #1 HIGH SYSTEM EAVE Wall Panels Installed Before Roof FACE OF WALL FASTENER #14 FASTENER #1 TRI-BEAD TAPE SEALER *DOUBLE FACED TAPE BOX PANEL CAP TRIM HIGH EAVE PLATE FASTENER #14 WALL PANEL 2" MAX. FLAT EAVE TRIM DETAIL (WITHOUT GUTTER) FASTENER #1 HIGH EAVE PLATE *DOUBLE FACED TAPE TRI-BEAD TAPE SEALER OFFSET PANEL CAP TRIM FASTENER #14 TRI-BEAD TAPE SEALER EAVE STRUT 1¹⁄₄" MAX. OFFSET PANEL CAP TRIM DETAIL (WITH GUTTER) FLAT EAVE TRIM OFFSET PANEL CAP TRIM FASTENER #14 Wall Panels Installed After Roof Install offset panel cap trim to the eave strut and wall panel with Fastener #14 at 10'-0" centers. Use three fasteners per trim piece. Install high eave plates flush with the outside of the offset panel cap trim. Install Fastener # 1 in each prepunched slot (1'-0" on center) of the eave plate. The first eave plate will butt against the rake support. All of the eave plates may be installed at this time Lay Tri-Bead tape sealer under the eave plate on top of the offset panel cap trim. FASTENER #4 Be sure to butt each eave plate end to end without leaving a gap between the plates. Place an 8" length of Triple Bead tape sealer at each butt joint. 1" URETHANE SEALANT 2" LAP 1" 2" LAP URETHANE SEALANT BOX PANEL CAP TRIM ENDLAP DETAIL OFFSET PANEL CAP TRIM ENDLAP DETAIL *Not by Manufacturer SL-30 Install high eave plates flush with the outside face of the high crowns of the wall panels. Install Fastener #1 in prepunched slots (1'-0" on center) of the eave plate. The first eave plate will butt against the rake support. All of the eave plates may be installed at this time. Be sure to butt each eave plate end to end without leaving a gap between the plates. Place an 8" length of Triple Bead tape sealer at each butt joint. Install box panel cap trim to the top of the eave plates. Check to make sure the trim is flat against the wall. Attach the trim to the eave plate and the wall panel with a Fastener #14 at 10'-0" centers. Lay Tri-Bead tape sealer across the top of the eave trim, flush with the outside edge. For vinyl back insulation, install double faced tape (not by manufacturer) along the length of the bottom of the eave plate. Double faced tape must be upslope from the Tri-Bead tape sealer. REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION Lay Tri-Bead tape sealer across the top of the eave plates, flush with the outside edge. For vinyl back insulation, install double faced tape (not by manufacturer) along the length of the bottom leg of the eave plate. Lap trim 2". Apply two beads of urethane sealant between the trim pieces, approximately 1" from the end of the bottom piece. Attach trim laps in flat eave trim with Fastener #14. Attach trim laps on panel cap trim with Fastener #4. SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® INSTALLATION SEQUENCE THERMAL SPACER THERMAL SPACER (FOR HIGH SYSTEM ONLY) Position the thermal spacer on top of the insulation over each purlin and against the rake support prior to installing the roof panel. *DOUBLE FACED TAPE OFFSET PANEL CAP TRIM INSULATION THERMAL SPACER *DOUBLE FACED TAPE 6" LONG PIECES @ 3'-0" RAKE SUPPORT THERMAL SPACER Using spray adhesive, (not by manufacturer), adhere the thermal spacer to the insulation (First Panel Run Only). The thermal spacer increases the insulation capacity along the purlins. *SPRAY ADHESIVE *Not by manufacturer SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-31 SuperLok® INSTALLATION SEQUENCE WALL PANEL THICKNESS *DOUBLE FACED TAPE FIRST PANEL 2³⁄₄" INSULATION FASTENER #14 FASTENER #1E OFFSET PANEL CAP TRIM TRI-BEAD TAPE SEALER WALL PANEL Position the panel so that it overhangs the eave strut by the dimension shown on the building drawings. The upper end of the panel must extend 7" beyond the web of the purlin if the panel covers eave to ridge. If more than one panel is required to cover eave to ridge, one or more endlaps will be required. The upper end of the panel will extend 10" beyond the web of the purlin at endlaps. WALL PANEL FASTENER NOTE: If an endlap is required then roof panel must be sheeted right to left as viewed from the eave looking toward the ridge. Vise Grip® LOCKING C-CLAMP RAKE SUPPORT SuperLok® PANEL EAVE STRUT RAKE ANGLE WALL PANEL FASTENER FASTENER #12A FASTENER #5 24" O.C. 2 1” 3 3 ¹⁄₂” 4 3 ¹⁄₂” 5 3 ¹⁄₂” WALL PANEL SuperLok® PANEL 1 3 ¹⁄₂” Lay the female leg of the panel over the rake support. To prevent wind damage, secure the female leg of the panel to the rake support with Vise Grip® Locking C-Clamps or temporary fasteners. Fasteners must go through the rake support. The panel will not be fastened permanently to the rake support until the rake trim is installed. 1” RAKE SUPPORT RAKE ANGLE WALL PANEL FASTENER Attach the panel to the eave strut or eave plate with Fastener #1E. Five fasteners are required at this location. WALL PANEL EAVE STRUT FASTENING PATTERN AT EAVE *Not by Manufacturer SL-32 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® INSTALLATION SEQUENCE FACTORY APPLIED MASTIC SuperLok® PANEL FACTORY APPLIED MASTIC LOW FIXED CLIP Hook the panel clip onto male leg of panel. Hold end of clip up to keep it engaged onto male leg and rotate the clip base down to completely engage clip onto male leg. Install panel clips at each purlin. SuperLok® PANEL PANEL CLIP INSTALLATION LOW FIXED CLIP SuperLok® PANEL FASTENER #1B (TWO PER CLIP) LOW FIXED CLIP CLIP FASTENER REQUIREMENTS SuperLok® PANEL FASTENER #1B (TWO PER CLIP) WRONG WAY Before fastening clip to purlins, check to ensure that vertical leg of clip is tight to the vertical leg of the panel. Failure to keep this leg tight to the panel leg will affect panel module. PURLIN RIGHT WAY SUBJECT TO CHANGE WITHOUT NOTICE CLIP INSTALLATION Two fasteners per clip Purlins - Fastener #1B - Up to 4" Insulation Fastener #1F - Over 4" Insulation Bar Joists - Fastener #6A CAUTION PURLIN The panel clip has factory applied mastic in the upper lip. This mastic is compressed when the clip is rotated in place. If, for some reason, a clip must be removed, a new clip must be used. SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-33 SuperLok® INSTALLATION SEQUENCE PREPUNCHED HOLES UPPER SWAGED SuperLok® PANEL ENDLAP-PANEL SWAGED ENDLAP TAPE SEALER NOTE: Step 6 applies only where more than one panel is used in a single slope. BACK-UP PLATE TEETH LOWER SuperLok® PANEL TRI-BEAD TAPE SEALER PANEL INSTALLATION SEQUENCE UPPER SWAGED SuperLok® PANEL FASTENER #1E Slide a prepunched back-up plate onto the upslope end of the bottom panel. Make sure the teeth on top of the back-up plate are on top of the panel. Visually check to ensure that the prepunched holes in the back-up plate are aligned with the prepunched holes in the panel. At upslope end of bottom panel, install Tri-Bead tape sealer across entire width of panel. Tape sealer must be centered over prepunched holes in panel. Apply swaged endlap tape sealer to swaged vertical male leg of upper panel. Pigtail portion of tape sealer must lap over vertical leg of panel. TRI-BEAD TAPE SEALER BACK-UP PLATE LOW CLIP LOWER SuperLok® PANEL FASTENER #1B Using an awl to align the prepunched holes, install upper panel by nesting it over the lower panel for 6". Rotate the male leg of the upper panel under the male leg of the bottom panel, then force the female leg of the upper panel down onto the female leg of the bottom panel. Install Fastener #1E in the prepunched holes in the proper sequence. Install clips as outlined in Step 5. Repeat this endlap procedure as required until ridge is reached. FASTENER SEQUENCE NOTE: If you are using 12" SuperLok® panels, they are not prepunched for endlaps. Use Triple Bead Tape Sealant at endlaps with 12" wide panels. SL-34 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® INSTALLATION SEQUENCE RIDGE BACK-UP PLATE At the ridge, the panel should extend 7" past the web of the peak purlin. SuperLok® PANEL FASTENER #1B At the ridge install a back-up plate as outlined in Step 6. SuperLok® CLIP PEAK PURLIN Install clips as outlined in Step 5. SuperLok® PANEL RIDGE END OF PANEL BACK-UP PLATE SUPERLOK CLIP PEAK PURLIN PANEL END SEALANT DETAIL AT RIDGE SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-35 SuperLok® INSTALLATION SEQUENCE SUBSEQUENT RUNS EAVE SuperLok® PANEL Apply urethane sealant to the male leg of the first panel directly over the Tri-Bead tape sealer at the eave. This will prevent water infiltration through the end of the panel seam. SuperLok® PANEL RAKE SUPPORT FASTENER #5 RAKE ANGLE Position the next panel with the female leg over the male leg of the previous panel with panel ends flush. FASTENER #1E URETHANE SEALANT TRI-BEAD TAPE SEALER FASTENER #12A PANEL END SEALANT DETAIL AT EAVE EAVE STRUT SuperLok® PANEL Vise Grip® LOCKING C-CLAMP Clamp the panel seam together at both ends. Long panels may require one or more clamps in the middle. This will help hold panel module. Install fasteners at eave as outlined in Step 4. Install clips as outlined in Step 5. Crimp panel seam at all clip locations with hand crimping tool. Panels should be fully seamed with electric seamer as quickly as possible after a section of the roof is completed. CAUTION Panel must be crimped at all clip locations as they are installed to provide temporary wind resistance. SL-36 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® INSTALLATION SEQUENCE SUBSEQUENT RUNS ENDLAP UPPER SWAGED SuperLok® PANEL Install endlap panels as outlined in Step 6. SWAGED ENDLAP TAPE SEALER FASTENER #1E (5) PER PANEL BACK-UP PLATE Install clips as described in Step 5. TRI-BEAD TAPE SEALER LOWER SuperLok® PANEL PURLIN Repeat endlap procedures as required until ridge is reached. FASTENER #1E 2 4 3 5 1 FASTENER SEQUENCE SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-37 SuperLok® INSTALLATION SEQUENCE SUBSEQUENT RUNS RIDGE Install back-up plate and clip as outlined in Step 7. SL-38 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® INSTALLATION SEQUENCE 8" TO 14" SuperLok® LOW FIXED CLIP LOW RAKE SUPPORT LAST PANEL RUN Install rake support at the finishing end of the roof as outlined in Step 1. SuperLok® PANEL RAKE ANGLE FASTENER #5 24" O.C. FASTENER #12A FINISHING DIMENSION RUN OF 8" TO 14" PANEL FASTENER Field cut and bend a 2" tall vertical leg on the panels in the last run of roof. The vertical leg must be tight to the rake support angle. Secure the vertical leg to the rake support angle with clamps or temporary fasteners. At the endlap and ridge, a partial back-up plate must be cut. WALL PANEL 8" MAX VARIABLE TERMINATION TRIM TRI-BEAD TAPE SEALER FASTENER #1E 24" O.C. FASTENER #4 6" O.C. FASTENER #5 24" O.C. TRI-BEAD TAPE SEALER SuperLok® PANEL RAKE ANGLE PANEL FASTENER RAKE SLIDE HIGH WIND If the width of the last panel run is 8" or less, a second run of rake support angle must be installed for attachment of the vertical leg of the panel. A variable termination trim will be required to seal the gap between the vertical leg of the panel and the rake trim. RAKE ANGLE FASTENER #12A RAKE TRIM FINISHING DIMENSION RUN OF LESS THAN 8" The male leg of the panel and the termination trim must be field cut to fit the condition. FASTENER #5 24" O.C. TRIM FASTENER CLOSURE PURLIN WALL PANEL SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-39 SuperLok® INSTALLATION SEQUENCE CRIMPING ARM (Up Position) LOCKING ARM (Up Position) SEAMING OPERATION As panels are installed, hand crimp at each clip location with the hand crimper. Panels should be completely seamed with the electric seamer as soon as possible. CRIMPING ARM (Up Position) STEP 1 Hand Tool Positioned Over Seam LOCKING ARM (Down Position) Push locking arm down to lock crimper onto seam. If difficulty is encountered, check to make sure that the hand crimper is properly alighned on seam. Do not force locking arm. LOCKING ARM (Down Position) CRIMPING ARM (Down Position) STEP 2 Hand Tool Locked Onto Seam Push crimping arm down to crimp panel. Return both the crimping arm and locking arm to the up postion and remove tool from seam. STEP 3 Hand Tool Crimps Seam SL-40 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® INSTALLATION SEQUENCE SEAMING OPERATION (Continued) HANDLE FORMING ARM HANDLE FORMING ARM GREASE ZERK FITTINGS BEGINNING PHASE 1 ACTION HANDLE CAUTION To begin seaming with hand tool, set the hand tool on the seam making sure seam is in the PHASE 1 Action slot. Align the edge of the hand tool with the end of the panel. Rotate the forming arm under the handle to produce 6" of PHASE 1 seam. This should be done three times along the seam for a total of 18". FINISHED PHASE 1 ACTION HANDLE FORMING ARM FORMING ARM BEGINNING PHASE 2 ACTION It is critical that the panel seams are crimped and folded as shown before using the electric seamer. Failure to follow these guidlines will result in damaged seams. FINISHED PHASE 2 ACTION Return to the end of the panel to begin PHASE 2 Action. Set hand tool onto seam making sure seam is in the PHASE 2 Action slot. Align the edge of the hand tool with the edge of the panel. Rotate the forming arm under the handle to produce 6" of finished PHASE 2 seam. This should be done once per rib. The relationship of this 6" of finished seam to the 18" of crimped seam is critical to the proper alignment of the rolls in the electric seamer. HAND TOOL STAGE 2 6” HAND TOOL STAGE 1 12” NOTE All grease zerk fittings on the hand tool should be greased with lithium based grease daily. The seam is now ready to accept the electric seamer. SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-41 SuperLok® INSTALLATION SEQUENCE DIRECTION OF ROOF INSTALLATION DIRECTION OF ROOF INSTALLATION SEAMING OPERATION (Continued) The electric seamer will run in one direction only. To determine the direction of the seamer, stand at the eave and look upslope. If the roof is being installed left to right, the seamer will run upslope. If the roof is being installed right to left, the seamer will run downslope, An orientation plate is on the seamer to assist you in placing the seamer onto the seam properly. When the roof has endlaps, the panels will always be installed right to left. When the roof slope is 6 on 12 or greater, panels must run right to left. To begin seaming, set seamer on seam with the locking bar up and to the open side of the seam. The rear wheels should be even with the edge of the roof panel. Push the locking bar down to engage the rolls and turn the seamer on. Stop seamer about one foot from end of panels. Disengage locking bar and remove the electric seamer. Finish seam with hand tool. CAUTION • Seamer operation should be closely supervised at all times. • A safety line should be attached to the seamer. • Do not entangle the electrical cords in the seamer tooling while it is in operation. This could cause serious injury or death to the operator and severely damage the seamer. • Electrical cords should be 10-gauge to provide power to the seamer and never be over 200 feet from the electrical source. SL-42 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® INSTALLATION SEQUENCE OUTSIDE CLOSURE INSTALLATION Panels must be seamed before closures can be installed. Install Tri-Bead tape sealer across full width of panels, including under panel seams at ridge. Center of tape sealer should be 1 ¹⁄₂" from end of panels. WN DO PE SLO Field cut the end of the outside closure that fits to the open side of the panel seam. Notch and bend the vertical leg of the closure above the end tab back to the dimple formed into the closure. It is important that the closures fit tight to the panel seams to prevent the need for excess urethane sealant at this location. WN DO PE SLO URETHANE SEALANT (AS REQUIRED) SUBSEQUENT OUTSIDE CLOSURE Install outside closures by rotating the end cut for the panel seam into place first. Then rotate the other end of the outside closure into place. The vertical leg of the outside closure should be 2" from the upslope end of the panel. Attach the outside closure to the panel with Fastener #1 at each prepunched hole in the closure. Before installing the next outside closure, install a piece of Tri-Bead tape sealer onto the top flange of the outside closure previously installed. This is to prevent water being blown between the outside closures where the top flanges overlap. After all closures are in place, install Tri-Bead tape sealer across the top flange. FIRST OUTSIDE CLOSURE FASTENER #1 TRI-BEAD TAPE SEALER Use urethane sealant to fill any voids around the panel seams on the upslope side of the outside closures. BACK-UP PLATE FASTENER #1 SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-43 SuperLok® SPECIAL ERECTION TECHNIQUES UL 90 LIGHT TRANSMITTING PANEL INSTALLATION SuperLok® LIGHT TRANSMITTING PANEL SEALANT (Factory Applied) FASTENER #1E (TWO EACH SIDE) SuperLok® LIGHT TRANSMITTING PANEL (Panels at this side of light transmitting panel reoved for clarity) 1. SuperLok® PANEL 2. SuperLok® LIGHT TRANSMITTING PANEL 3. LIGHT TRANSMITTING PANEL STIFFENER PLATE 4. BACK-UP PLATE 5. PURLIN STIFFENER PLATE [HW-7747] NOTES: 1. Maximum width of purlin flange to be 3 ¹⁄₂". 2. Stiffener plate is to be field installed on bottom side of light transmitting panel over mid-purlin. 3. Light transmitting panel rivets that obstruct stiffener plate must be drilled out and replaced with Fastener #1E. Minimum two fasteners per side. 4. Stiffener plate must be centered exactly over mid-purlin so that thermal movement of the system is not restrained by the purlin. 5. Endlaps created by the use of light transmitting panels require roof erection to proceed from right to left as viewed from the eave looking toward the ridge. 6. WARNING: It is the user’s responsibility to ensure that the installation and use of all light transmitting panels comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding all light transmitting panels with screens, fixed standard railings, or other acceptable safety controls that prevent fall-through. SL-44 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® SPECIAL ERECTION TECHNIQUES ROOF CURB INSTALLATION INSTRUCTIONS 6 5 7 8 2 3 5 1 IN. 6" 12" M IN. 18" M When ordering curbs, specify one-piece curbs as shown on this page. 6 4 1. SuperLok® Panel 2. Urethane Sealant 3. Outside Cap Cell 4. Back-up Plate 5. Fastener #1E 6. Tri-bead Tape Sealer 7. Roof Curb Made From Structural Aluminum (Min. .080 Thickness) 8. Water Diverter 9. Panel Fins (to be cut from an extra panel the length equal to length of the curb). 9 1 7 3 8 5 MBCI recommends that only one-piece .080 Aluminum (Min.) roof curbs be used with the SuperLok® roof system. The roof curb will be installed under the roof panels on the upslope end and over the panels at the downslope end. To accomplish this, the roof panels must be endlapped at the upslope and downslope end of the curb. This allows both ends of the curb to shed water and places the heavier gauge metal of the curb under the roof panels for better resistance to foot traffic. The exception is at the downslope end where the curb is on top of the roof panels. Since there are endlaps at this area, back-up plates provide support. Outside cap cells (for bottom) are used to seal the panel to the roof curb. If the curb must be located in a precise location, order the cap cells loose for field installation. ROOF SLOPE NOTCH FEMALE LEG OF LOWER PANEL DIRECTION OF PANEL INSTALLATION SUBJECT TO CHANGE WITHOUT NOTICE For the purpose of these instructions, a curb with a factory attached cap cell is illustrated. Panels are assumed to be blank and installed right to left. CAUTION It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through. SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-45 SuperLok® SPECIAL ERECTION TECHNIQUES CURB INSTALLATION FLOATING ROOF CURB SUPPORT GUIDE SuperLok® SuperLok® SuperLok® SuperLok® CAUTION It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through. SL-46 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® SPECIAL ERECTION TECHNIQUES CURB INSTALLATION CURB BASE INSTALLATION #1 NOTES: 1. Install all lower roof panels to support the curb base. 2. Install back up plates. CAUTION It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through. SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-47 SuperLok® SPECIAL ERECTION TECHNIQUES CURB INSTALLATION CURB BASE INSTALLATION #2 NOTES: 1. Apply Triple Bead tape sealer (HW-502) on roof panels as shown CAUTION It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through. SL-48 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® SPECIAL ERECTION TECHNIQUES CURB INSTALLATION CURB BASE INSTALLATION #3 NOTES: 1. For field located Panel Fin Caps, notch Curb Base at all panel Fins. 2. Install Curb Base on lower roof panels with a 3" End Lap. CAUTION It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through. SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-49 SuperLok® SPECIAL ERECTION TECHNIQUES CURB INSTALLATION CURB BASE INSTALLATION #4 NOTES: 1. Attach the Curb Base to the roof panels. CAUTION It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through. SL-50 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® SPECIAL ERECTION TECHNIQUES CURB INSTALLATION CAP CELL INSTALLATION NOTES: 1. Fill Fin cavity of Cap Cell with Urethane Tube Sealant. Apply Triple Bead tape sealer (HW-502) on the bottom of (2) loose the Cap Cell, install over the panel Fins and attach with (6) Fastener #1E. CAUTION It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through. SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-51 SuperLok® SPECIAL ERECTION TECHNIQUES CURB INSTALLATION CURB PANEL FIN PREPARATION NOTES: 1. Field cut male and female panel ribs from an extra roof panel supplied by the building manufacturer. CAUTION It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through. SL-52 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® SPECIAL ERECTION TECHNIQUES CURB INSTALLATION FEMALE PANEL FIN INSTALLATION NOTES: 1. Install Triple Bead tape sealer (HW-502) to panel #2 Male Fin, and along the edge of the Curb Base. 2. Install the Female Panel Rib over the tape sealer and attach with Fastener # 1E at 12" O.C. CAUTION It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through. SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-53 SuperLok® SPECIAL ERECTION TECHNIQUES CURB INSTALLATION MALE PANEL FIN INSTALLATION NOTES: 1. Notch the male Panel Fin. Apply Triple Bead tape sealer (HW-502) to the top and side of the Male Panel Fin. 2. Apply Triple Bead tape sealer on the Curb Base under the male Panel Fin. 3. Insert the field cut male Panel Fin on top of the Triple Bead tape sealer. CAUTION It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through. SL-54 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® SPECIAL ERECTION TECHNIQUES CURB INSTALLATION CURB BASE INSTALLATION #5 CAUTION It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through. SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-55 SuperLok® SPECIAL ERECTION TECHNIQUES CURB INSTALLATION CURB BASE INSTALLATION #6 NOTES: 1. Apply Triple Bead tape sealer (HW-502) on Curb Base at the up hill end. CAUTION It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through. SL-56 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® SPECIAL ERECTION TECHNIQUES CURB INSTALLATION CURB BASE INSTALLATION #7 NOTES: 1. Apply Triple Bead tape sealer (HW-502) between the Panel Fins on Panels #5 and #6 for water seal. CAUTION It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through. SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-57 SuperLok® SPECIAL ERECTION TECHNIQUES CURB INSTALLATION CURB BASE INSTALLATION #8 NOTES: 1. Install Roof Panels #5, #6, & #7 to the Curb Base on top of the tape sealer with Fastener #1E (5 per panel). 2. Install Roof Panel #8. CAUTION It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through. SL-58 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® SPECIAL ERECTION TECHNIQUES CURB INSTALLATION UPLIFT PLATE DETAIL SuperLok® PANEL ® CAUTION It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through. SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-59 SuperLok® SPECIAL ERECTION TECHNIQUES CURB INSTALLATION UPLIFT PLATE FIELD NOTCH CAUTION It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through. SL-60 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® SPECIAL ERECTION TECHNIQUES CURB INSTALLATION DOWN SLOPE CURB BASE END LAP SuperLok® PANEL CAUTION It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through. SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-61 SuperLok® SPECIAL ERECTION TECHNIQUES CURB INSTALLATION UP SLOPE CURB BASE END LAP SuperLok® PANEL HW-7617 HW-7618 ® CAUTION It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other acceptable safety controls that prevent fall-through. SL-62 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® SPECIAL ERECTION TECHNIQUES PIPE PENETRATION INSTALLATION RECOMMENDED SMALL AND LARGE PIPE PENETRATION INSTALLATION RIGHT WAY WRONG WAY RECOMMENDED SMALL PIPE PENETRATION INSTALLATION INSTALL PIPE IN CENTER OF PANEL TO ALLOW BASE OF RUBBER ROOF JACK TO LAY FLAT ON PANEL. STAINLESS STEEL CLAMP (NOT BY BUILDING MANUFACTURER) SuperLok® PANEL PIPE CURB RO OF SL OP E PURLIN SuperLok® PANEL RECOMMENDED LARGE PIPE PENETRATION INSTALLATION THIS METHOD TO BE USED IN ALL CASES WHERE A PIPE PENETRATION INTERSECTS A PANEL RIB OR WHEN THE PIPE IS TOO LARGE AND WILL NOT ALLOW ADEQUATE WATER FLOW DOWN THE PANEL. SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-63 SuperLok® SPECIAL ERECTION TECHNIQUES PIPE PENETRATION INSTALLATION DECK-TIGHT INSTALLATION DECK-TIGHT (NOT BY BUILDING MANUFACTURER) ROLL TOP OF DECK-TIGHT DOWN STAINLESS STEEL CLAMP (NOT BY BUILDING MANUFACTURER) ¹⁄₄"-14 x ⁷⁄₈" LONG LIFE LAP TEK® S.D. W/WASHER (FASTENER #4) @ 1" O.C. TRI-BEAD TAPE SEALER (HW-504) APPLY TRI-BEAD TAPE SEALER STAINLESS STEEL CLAMP (NOT BY BUILDING MANUFACTURER) DECK-TIGHT (NOT BY BUILDING MANUFACTURER) ¹⁄₄"-14 x ⁷⁄₈" LONG LIFE LAP TEK S.D. W/WASHER (FASTENER #4) @ 1" O.C. ® STEP 2 TRI-BEAD TAPE SEALER (HW-504) TRI-BEADTAPE SEALER (HW-504) STAINLESS STEEL CLAMP (NOT BY BUILDING MANUFACTURER) DECK-TIGHT (NOT BY BUILDING MANUFACTURER) ¹⁄₄"-14 x ⁷⁄₈" LONG LIFE LAP TEK® S.D. W/WASHER (FASTENER #4) @ 1" O.C. STEP 3 NOTE: ROLL DECK-TIGHT UP OVER TRI-BEAD TAPE SEALER AND SECURE CALMP AROUND TOP OF DECK-TIGHT SL-64 REV 00.01 TRI-BEAD TAPE SEALER (HW-504) SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® DETAILS OPEN FRAMING FIXED EAVE WITH SCULPTURED GUTTER GUTTER STRAP (FL-246) @ EVERY OTHER RIB ¹⁄₄" -14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) (2) PER STRAP 12” 1” 3⁵⁄₁₆” 3⁵⁄₁₆” 3⁵⁄₁₆” 1” SuperLok® PANEL 2" GUTTER STRAP ATTACHMENT 16” SuperLok® PANEL 1” URETHANE TUBE SEALANT BETWEEN PANEL RIBS 3¹⁄₂” 3¹⁄₂” 3¹⁄₂” 3¹⁄₂” 1” 2" FASTENER SPACING @ EAVE EAVE END OF PANEL ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) EAVE SEALANT URETHANE SEALANT MUST COME IN CONTACT WITH TAPE SEALER TO FORM A WEATHERTIGHT SEAL 2 ³⁄₄" ANEL WALL P SS E N K IC H T ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (5) PER 16" PANEL (4) PER 12" PANEL URETHANE TUBE SEALANT BETWEEN PANEL RIBS GUTTER STRAP (FL-246) @ EVERY OTHER RIB ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) (2) PER STRAP SuperLok® PANEL LOW FIXED EAVE PLATE (HW-7600) ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 12" O.C. ¹⁄₄" -14 x 1" SELF-DRILLER W/WASHER (FASTENER #1) @ 12" O.C. BOX PANEL CAP TRIM (FL-272) ¹⁄₈" x ³⁄₈" POP RIVET (FASTENER #14A) @ 5'-0" O.C. 12 - 14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #3) TRI-BEAD TAPE SEALER (HW-504) ¹⁄₈" x ³⁄₁₆" POP RIVET (FASTENER #14) @ 3'-0" O.C. SCULPTURED GUTTER (FL-248A) WALL PANEL EAVE STRUT BUILDING DIM. SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-65 SuperLok® DETAILS OPEN FRAMING FIXED EAVE WITH SCULPTURED EAVE TRIM 12” 1” 3⁵⁄₁₆” 3⁵⁄₁₆” 3⁵⁄₁₆” 1” 2" SuperLok® PANEL URETHANE TUBE SEALANT BETWEEN PANEL RIBS 16” 1” 3¹⁄₂” 3¹⁄₂” 3¹⁄₂” 3¹⁄₂” 1” 2" EAVE END OF PANEL EAVE SEALANT DETAIL FASTENER SPACING @ EAVE URETHANE SEALANT MUST COME IN CONTACT WITH TAPE SEALER TO FORM A WEATHERTIGHT SEAL W/ VARIES PE O L S F ROO ANEL WALL P ESS N K THIC ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (5) PER 16" PANEL (4) PER 12" PANEL URETHANE TUBE SEALANT BETWEEN PANEL RIBS SuperLok® PANEL ³⁄₄" LOW FIXED EAVE PLATE (HW-7600) ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 16" O.C. BOX PANEL CAP TRIM (FL-272) 12 - 14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #3) ¹⁄₄"-14 x 1" SELF-DRILLER W/WASHER (FASTENER #1) @ 12" O.C. ¹⁄₈" x ³⁄₈" POP RIVET (FASTENER #14A) @ 5'-0" O.C. ¹⁄₈" x ³⁄₁₆" POP RIVET (FASTENER #14) @ 3'-0" O.C. TRI-BEAD TAPE SEALER (HW-504) SCULPTURED EAVE TRIM (FL-253) ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 12" O.C. EAVE STRUT OUTSIDE CLOSURE WALL PANEL SL-66 REV 00.01 BUILDING DIM. SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® DETAILS OPEN FRAMING FIXED EAVE WITH BOX EAVE TRIM 12” 1” 3⁵⁄₁₆” 3⁵⁄₁₆” 3⁵⁄₁₆” 1” 2" SuperLok® PANEL URETHANE TUBE SEALANT BETWEEN PANEL RIBS 16” 1” 3¹⁄₂” 3¹⁄₂” 3¹⁄₂” 3¹⁄₂” 1” 2" EAVE END OF PANEL ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE EAVE SEALANT DETAIL FASTENER SPACING @ EAVE SELF-DRILLER W/WASHER (FASTENER #1E) URETHANE SEALANT MUST COME IN CONTACT WITH TAPE SEALER TO FORM A WEATHERTIGHT SEAL PANEL WALL ESS N K THIC . ³⁄₄" O.H ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (5) PER 16" PANEL (4) PER 12" PANEL URETHANE TUBE SEALANT BETWEEN PANEL RIBS LOW FIXED EAVE PLATE (HW-7600) SuperLok® PANEL BOX EAVE TRIM (FL-326) 12-14 x 1¹⁄₄" LONG-LIFE SELF DRILLER W/WASHER (FASTENER #3) ¹⁄₄"-14 x 1" SELF-DRILLER W/WASHER (FASTENER #1 @ 12" O.C.) ¹⁄₈" - ³⁄₁₆" POP RIVET (FASTENER #14A) @ 5'-0" O.C. ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 12" O.C. TRI-BEAD TAPE SEALER (HW-504) OUTSIDE CLOSURE WALL PANEL EAVE STRUT BUILDING DIM. SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-67 SuperLok® DETAILS OPEN FRAMING FLOATING RIDGE URETHANE TUBE SEALANT @ CLOSURE ENDS/PANEL RIB & LAPPING CLOSURE TABS TO SEAL ALL VOIDS TRI-BEAD TAPE SEALER (HW-504) OUTSIDE CLOSURE (HW-440) @16" PANEL (HW-446) @12" PANEL ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (1) PER RIB RIDGE TRIM (FL-213) LOW FLOATING CLIP (HW-230) ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 6" O.C. (DO NOT INSTALL THRU PANEL RIB) SuperLok® PANEL BACK-UP PLATE (HW-7766) @ 16" PANEL (HW-7764) @ 12" PANEL ¹⁄₄"-14 x 1¹⁄₄" SELF-DRILLER W/O WASHER (FASTENER #1B) (2) PER CLIP SL-68 REV 00.01 TRI-BEAD TAPE SEALER (HW-504) CONT. ACROSS PANEL ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (4) PER 16" PANEL (3) PER 12" PANEL SEE www.mbci.com FOR CURRENT INFORMATION ZEE PURLIN SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® DETAILS OPEN FRAMING FLOATING VENTED RIDGE FLOATING VENTED RIDGE FLASHING 12-14 x 1" SELF-DRILLER W/WASHER (FASTENER #17) (1) PER BIB PERFORATED VENT DRIP (FL-254) ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAP TEK® SELF-DRILLER W/WASHER (FASTENER #4) @ 6" O.C. ¹⁄₈" x ³⁄₁₆" POP RIVET (FASTENER #14) @ 6" O.C. TRI-BEAD TAPE SEALER (HW-504) OUTSIDE CLOSURE (HW-440) @ 16" PANEL (HW-446) @ 12" PANEL SuperLok® PANEL LOW FLOATING CLIP (HW-230) SuperLok® PANEL BACK-UP PLATE (HW-7766) @ 16" PANEL (HW-7764) @ 12" PANEL ¹⁄₄"-14 x 1¹⁄₄" SELF DRILLER W/O WASHER (FASTENER #1B) (2) PER CLIP SUBJECT TO CHANGE WITHOUT NOTICE TRI-BEAD TAPE SEALER (HW-504) ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (4) PER 16" PANEL (3) PER 12" PANEL SEE www.mbci.com FOR CURRENT INFORMATION PURLIN REV 00.01 SL-69 SuperLok® DETAILS OPEN FRAMING FIXED VENTED EAVE SuperLok® PANEL ¹⁄₂" URETHANE SEALANT PANEL WALL NESS K IC TH ¹⁄₄"-14 x 1¹⁄₄" LONG LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (5) PER 16" PANEL (4) PER 12" PANEL LOW FLOATING CLIP (HW-230) SuperLok® PANEL ¹⁄₄" -14 x 1¹⁄₄" S.D. W/O WASHER (FASTENER #1B) (2) PER CLIP EAVE TRIM CLOSURE 10-16 x 1" PANCAKE HD. S.D. (FASTENER #12A) @ 12" O.C. TRI-BEAD TAPE SEALER (HW-504) ¹⁄₈" x ³⁄₁₆" POP RIVET (FASTENER #14) @ 10" O.C. FASCIA PANEL SILL TRIM ¹⁄₈" x ³⁄₁₆" POP RIVET (FASTENER #14) @ 12" O.C. EAVE STRUT CANOPY STRUT 4" MIN. ¹⁄₈" x ³⁄₁₆" POP RIVET (FASTENER #14) @ 12" O.C. ANGLE TRIM CAP TRIM PERFORATED ALUMINUM SOFFIT PANEL REV 00.01 ¹⁄₄"-14 x 1⁷⁄₈" LAP TEK® S.D. W/WASHER (FASTENER #4A) @ 12" O.C. GIRT ¹⁄₄"-14 x 1¹⁄₄" LONG LIFE SELF-DRILLER W/WASHER (FASTENER #1E) @ 12" O.C. CROSS SECTION OF VENTED EAVE (OVERHANG MAXIMUM 2'-0") SL-70 ¹⁄₈" x ³⁄₁₆" POP RIVET (FASTENER #14) @ 12" O.C. CLOSURE WALL PANEL SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® DETAILS OPEN FRAMING SCULPTURED RAKE TRI-BEAD TAPE SEALER (HW-504) ¹⁄₄"-14 x 1¹⁄₄" LONG LIFE S.D. W/WASHER (FASTENER #1E) @ 24" O.C. FIELD CUT & BEND UP 2” PANEL LEG AS REQ’D WHEN ENDING OFF MODULE 12-14 X 1¹⁄₄" LONG-LIFE SELF DRILLER W/WASHER (FASTENER #3) LOW RAKE SUPPORT ANGLE (HW-7712) LOW FLOATING CLIP (HW-230) SuperLok® PANEL ¹⁄₄"-14 x 1¹⁄₄" SHOULDER TEK® 2 SELF DRILLER (FASTENER #5) @ 24" O.C. (CENTER IN SLOT) SCULPTURED RAKE TRIM (FL-111) 12-14 X 1" PANCAKE HEAD SELF DRILLER (FASTENER #12A) (1 PER CONN. @ EACH PURLIN) ¹⁄₄"-14 x 1¹⁄₄" SELF DRILLER W/O WASHER (FASTENER #1B) (2) PER CLIP 2 X 4 X 16 GA. ANGLE HIGH WIND RAKE SLIDE (F-215) ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 12" O.C. ZEE PURLIN OUTSIDE CLOSURE WALL PANEL SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-71 SuperLok® DETAILS OPEN FRAMING SCULPTURED RAKE WITH CLEAT ¹⁄₄"-14 x 1⁷⁄₈" LONG LIFE LAPTEK W/WASHER (FASTENER #4) @ 6" O.C. TRI-BEAD TAPE SEALER (HW-504) ¹⁄₄"-14 x 1¹⁄₄" LONG LIFE S.D. W/WASHER (FASTENER #1E) @ 24" O.C. 12-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #3) HIGH WIND PARAPET RAKE CLEAT (F-292) FIELD CUT & BEND UP 2” PANEL LEG AS REQ’D WHEN ENDING OFF LOW FLOATING MODULE CLIP (HW-230) LOW RAKE SUPPORT SuperLok® PANEL ANGLE (HW-7712) ¹⁄₄"-14 x 1¹⁄₄" SHOULDER TEK® 2 SELF DRILLER (FASTENER #5) @ 24" O.C. (CENTER IN SLOT) SCULPTURED RAKE TRIM (FL-111) 12-14 X 1" PANCAKE HEAD SELF-DRILLER (FASTENER #12A) (1) PER CONN. @ EACH PURLIN ¹⁄₄"-14 x 1¹⁄₄" SELF DRILLER W/O WASHER (FASTENER #1B) (2) PER CLIP 2 X 4 X 16 GA. ANGLE HIGH WIND RAKE SLIDE (F-215) ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @12" O.C. ZEE PURLIN OUTSIDE CLOSURE WALL PANEL SL-72 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® DETAILS DETAILS SuperLok® OPEN FRAMING PARAPET RAKE BUILDING DIM. URETHANE TUBE SEALANT CONTINUOUS FEILD SAWCUT 1¹⁄₂" (MIN.) 14-10 x 2" DECK SCREW (FASTENER #209) @ 24" O.C. (PRE-DRILL HOLE) COUNTERFLASH (FL-341) PARAPET RAKE TRIM (FL-285) TRI-BEAD TAPE SEALER (HW-504) EA. SIDE OF FLEXIBLE MEMBRANE HIGH WIND PARAPET RAKE CLEAT (F-292) TRI-BEAD TAPE SEALER (HW-504) EA. SIDE OF FLEXIBLE MEMBRANE ¹⁄₄"-14 x 1¹⁄₄" LONG LIFE S.D. W/WASHER (FASTENER #1E) @ 24" O.C. LOW FLOATING CLIP (HW-230) SuperLok® PANEL FLEXIBLE MEMBRANE LOW RAKE SUPPORT ANGLE (HW-7712) FIELD CUT & BEND UP 2" PANEL LEG AS REQ’D WHEN ENDING OFF MODULE MASONRY WALL (NOT BY MBCI) ¹⁄₄"-14 x 1¹⁄₄" SHOULDER TEK® 2 SELF DRILLER (FASTENER #5) @ 24" O.C. (CENTER IN SLOT) 12-14 X 1" PANCAKE HEAD SELF DRILLER (FASTENER #12A) (1) PER CONN. @ EACH PURLIN ¹⁄₄"-14 x 1¹⁄₄" SELF DRILLER W/O WASHER (FASTENER #1B) (2) PER CLIP 2 X 4 X 16 GA. ANGLE ZEE PURLIN SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-73 SuperLok® DETAILS OPEN FRAMING FLOATING SCULPTURED HIGH SIDE EAVE ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 6" O.C. (DO NOT INSTALL THRU PANEL RIB) URETHANE TUBE SEALANT @ CLOSURE ENDS/PANEL RIB & LAPPING CLOSURE TABS TO SEAL ALL VOIDS ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (1) PER RIB 1" 2 x 2 x 16 GA. BACK UP ANGLE SuperLok® PANEL SCULPTURED HIGH SIDE EAVE TRIM (FL-265) TRI-BEAD TAPE SEALER (HW-504) TOP & BOTTOM OF CLOSURE ³⁄₈" 2¹⁄₂" OUTSIDE CLOSURE (HW-440) @ 16" PANEL (HW-446) @ 12" PANEL ALTERNATE DETAIL ¹⁄₄"-14 x ⁷⁄₈" LONG LIFE-LAPTEK W/WASHER (FASTENER #4) @ 6" O.C. (DO NOT INTALL THRU PANEL RIB) URETHANE TUBE SEALANT @ CLOSURE ENDS/PANEL RIB & LAPPING CLOSURE TABS TO SEAL ALL VOIDS 2" TRI-BEAD TAPE SEALER (HW-504) ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (4) PER 16" PANEL (3) PER 12" PANEL ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (1) PER RIB OUTSIDE CLOSURE (HW-440) @ 16" PANEL (HW-446) @ 12" PANEL TRI-BEAD TAPE SEALER (HW-504) LOW FLOATING CLIP (HW-230) BACKUP PLATE (HW-7766) @ 16" PANEL (HW-7764) @ 12" PANEL SuperLok® PANEL 2¹⁄₂" ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (4) PER 16" PANEL (3) PER 12" PANEL ¹⁄₄"-14 x 1¹⁄₄" SELF DRILLER W/O WASHER (FASTENER #1B) (2) PER CLIP 12-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #3) SCULPTURED HIGH SIDE EAVE TRIM (FL-265) ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 12" O.C. EAVE STRUT OUTSIDE CLOSURE WALL PANEL BUILDING DIM. SL-74 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® DETAILS OPEN FRAMING PARAPET FLOATING HIGH SIDE EAVE MASONRY WALL (NOT BY MBCI) BUILDING DIM. URETHANE TUBE SEALANT CONTINUOUS FIELD SAWCUT COUNTER FLASH (FL341) PARAPET HIGH EAVE TRIM (FL-275) TRI-BEAD TAPE SEALER (HW-504) EA. SIDE OF FLEXIBLE MEMBRANE ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 6" O.C. (DO NOT INSTALL THRU PANEL RIB) 14-10 x 2" DECK SCREW (FASTENER #209) @ 24" O.C. (PRE-DRILL HOLE) TRI-BEAD TAPE SEALER (HW-504) @ TOP OF CLOSURE & TOP OF FLEXIBLE MEMBRANE FLEXIBLE MEMBRANE OUTSIDE CLOSURE (HW-440) @ 16" PANEL (HW-446) @ 12" PANEL URETHANE TUBE SEALANT @ CLOSURE ENDS/PANEL RIB & LAPPING CLOSURE TABS TO SEAL ALL VOIDS 2" ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (1) PER RIB LOW FLOATING CLIP (HW-230) SuperLok® PANEL ³⁄₈" BACKUP PLATE (HW-7766) @ 16" PANEL (HW-7764) @ 12" PANEL ¹⁄₄"-14 x 1¹⁄₄" SELF DRILLER W/O WASHER (FASTENER #1B) (2 PER CLIP) TRI-BEAD TAPE SEALER (HW-504) 2" 7" ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (4) PER 16" PANEL (3) PER 12" PANEL ZEE PURLIN SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-75 SuperLok® DETAILS OPEN FRAMING FIXED VALLEY SuperLok® PANEL TRIPLE-BEAD TAPE SEALER (HW-502) URETHANE SEALANT ¹⁄₄"-14 x 1¹⁄₄" LONG LIFE SELF-DRILLER W/WASHER (FASTENER #1E) @ 3" O.C. (FASTENER MUST GO THROUGH TAPE SEALER) R VA VALLEY END OF PANEL IES BEVELED EDGE OF ROOF PANEL PANEL RIB URETHANE SEALANT MUST COME IN CONTACT WITH TAPE SEALER TO FORM A WEATHERTIGHT SEAL DETAIL "A" VALLEY TRIM (FL-705) TRIPLE-BEAD TAPE SEALER (HW-502) SuperLok® PANEL 4¹⁄₂" DETAIL "A" 2" URETHANE TUBE SEALANT BETWEEN PANEL RIBS ¹⁄₄"-14 x 1¹⁄₄" LONG LIFE SELF-DRILLER W/WASHER (FASTENER #1E) @ 3" O.C. (FASTENER MUST GO THROUGH TAPE SEALER) FIELD NOTCH PLATE @ PURLIN AS REQUIRED ZEE PURLIN 12-14 X 1" PANCAKE HEAD SELF DRILLER (FASTENER #12A) @ 5'-0" O.C. SL-76 REV 00.01 VALLEY SUPPORT PLATE (P-106) SEE www.mbci.com FOR CURRENT INFORMATION 12-14 X 1" PANCAKE HEAD SELF-DRILLER (FASTENER #12A) (2) PER CONN. @ EACH PURLIN SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® DETAILS OPEN FRAMING FLOATING HIP URETHANE TUBE SEALANT @ CLOSURE ENDS TRI-BEAD TAPE SEALER (HW-504) ¹⁄₄"-14 x 1¹⁄₄" SELF DRILLER W/O WASHER (FASTENER #1B) (2) PER CLIP ¹⁄₄"-14 x ⁷⁄₈" LONG LIFE LAPTEK W/WASHER (FASTENER #4) @ 6" O.C. (DO NOT INSTALL THRU PANEL RIB) RIDGE/HIP TRIM (FL-213) ZEE CLOSURE (FL-361) (FIELD CUT TO LENGTH & BEVEL CUT TO FIT PANEL) LOW FLOATING CLIP (HW-230) SuperLok® PANEL 2 x 2 x 16 GA. BACK-UP ANGLE TRI-BEAD TAPE SEALER (HW-504) CONT. ACROSS PANEL 12-14 X 1" PANCAKE HEAD SELF DRILLER (FASTENER #12A) (2) PER CONN. @ EACH PURLIN 8 x ⁵⁄₈" NIBBED DRILLER (FASTENER #24) @ 4" O.C. HIP SUPPORT PLATE (P-141) (FIELD NOTCH @ PURLINS) ZEE PURLIN SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-77 SuperLok® DETAILS FIELD HEMMING PANEL END SuperLok® PANEL SuperLok® PANEL SuperLok® PANEL SL-78 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® DETAILS WOOD DECK FLOATING ENDLAP SuperLok® PANEL SuperLok® PANEL (LOWER) ¹⁄₄" -14 x ⁵⁄₈" LONG-LIFE TYPE "B" W/WASHER (FASTENER #46) (5) PER 16" PANEL (2) PER 12" PANEL SuperLok® PANEL BACK-UP PLATE (HW-7766) 16" PANEL (HW-7766) 12" PANEL SuperLok® PANEL (LOWER) ⁵⁄₈" PLYWOOD (MIN.) (NOT BY MBCI) 2 3 4 1 MOISTURE BARRIER (NOT BY MBCI) ¹⁄₄" -14 x ⁵⁄₈" LONG-LIFE TYPE "B" W/WASHER (FASTENER #46) (5) PER 16" PANEL (2) PER 12" PANEL SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-79 SuperLok® DETAILS WOOD DECK FLOATING EAVE WITH BOX GUTTER SuperLok® PANEL FIELD NOTCH PANEL LEGS AND BEND PAN TO FORM OPEN HEM 1¹⁄₂" NON-SKINNING BUTYL SEALANT (HW-549) BETWEEN PANEL RIBS 1¹⁄₂" EAVE END OF PANEL ¹⁄₂" 1¹⁄₂" EAVE SELANT DETAIL BUTYL SEALANT MUST COME IN CONTACT WITH THE DRIP EDGE TO FORM A WEATHERTIGHT SEAL ¹⁄₂" 1" EAVE TRIM W/DRIP EDGE (T-5271) . AX 1'-0" M 2" PANEL WALL NESS K THIC LOW FLOATING CLIP (HW-230) NON-SKINNING BUTYL SEALANT (HW-549) BETWEEN PANEL RIBS SuperLok® PANEL MOISTURE BARRIER (NOT BY MBCI) ³⁄₈" GUTTER STRAP (FL-310) @ EVERY OTHER RIB ¹⁄₈" x ³⁄₁₆" POP RIVET (FASTENER #14) (2) PER STRAP 14-10 x 1" TYPE 'A' SELF-TAPPER W/WASHER (FASTENER #18) (2) PER CLIP ⁵⁄₈" PLYWOOD (MIN.) (NOT BY MBCI) BOX GUTTER W/DRIP EDGE (T-5271) 12-11 x 1" PANCAKE HEAD SELF-TAPPER (FASTENER #13A) @ 12" O.C. ¹⁄₄"-14 x 1" LONG-LIFE 'TYPE AB' SELF-TAPPER W/WASHER (FASTENER #2B) ³⁄₈" PLYWOOD SPACER (NOT BY MBCI) WOOD BLOCKING (NOT BY MBCI) WALL PANEL BUILDING DIM. NOTE: DO NOT USE THIS DETAIL ON ROOF SLOPES LESS THAN 3:12 SL-80 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® DETAILS WOOD DECK FLOATING EAVE WITH EAVE TRIM WITH EXTENDED DRIP EDGE SuperLok® PANEL FIELD NOTCH PANEL LEGS AND BEND PAN TO FORM OPEN HEM 1¹⁄₂" NON-SKINNING BUTYL SEALANT (HW-549) BETWEEN PANEL RIBS 1¹⁄₂" EAVE END OF PANEL ¹⁄₂" EAVE SELANT DETAIL ¹⁄₂" 1" 1¹⁄₂" BUTYL SEALANT MUST COME IN CONTACT WITH THE DRIP EDGE TO FORM A WEATHERTIGHT SEAL EAVE TRIM W/DRIP EDGE (T-5271) . AX 1'-0" M 2" NON-SKINNING BUTYL SEALANT (HW-549) BETWEEN PANEL RIBS PANEL WALL NESS K THIC 12 - 11 X 1 PANCAKE HEAD SELF-TAPPER (FASTENER #13A) @ 12" O.C. LOW FLOATING CLIP (HW-230) SuperLok® PANEL MOISTURE BARRIER (NOT BY MBCI) ³⁄₈" EAVE TRIM W/DRIP EDGE (T-5151) ⁵⁄₈" PLYWOOD (MIN.) (NOT BY MBCI) ¹⁄₄ -14 x 1 LONG-LIFE 'TYPE AB' SELF-TAPPER W/WASHER (FASTENER #2B) 14-10 x 1 TYPE 'A' SELF-TAPPER W/WASHER (FASTENER #18) (2) PER CLIP CONT. ³⁄₈" PLYWOOD SPACER (NOT BY MBCI) ¹⁄₄ -14 x ⁷⁄₈ LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 12" O.C. 12-11 x 1 PANCAKE HEAD SELF-TAPPER (FASTENER #13A) @ 12" O.C. OUTSIDE CLOSURE WALL PANEL WOOD BLOCKING (NOT BY MBCI) BUILDING DIM. NOTE: DO NOT USE THIS DETAIL ON ROOF SLOPES LESS THAN 3:12 SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-81 SuperLok® DETAILS WOOD DECK FIXED RIDGE 3" TRI-BEAD TAPE SEALER (HW-504) RIDGE END OF PANEL RIDGE TRIM (FL-209) 2" URETHANE TUBE SEALANT @ CLOSURE ENDS/PANEL RIB & LAPPING CLOSURE TABS TO SEAL ALL VOIDS 2" ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (1) PER RIB ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 6" O.C. (DO NOT INSTALL THRU PANEL RIB) TRI-BEAD TAPE SEALER (HW-504) OUTSIDE CLOSURE (HW-440) @ 16" PANEL (HW-446) @ 12" PANEL ® SuperLok PANEL ³⁄₈" ³⁄₈" PLYWOOD SPACER (NOT BY MBCI) TRI-BEAD TAPE SEALER (HW-504) CONT. ACROSS PANEL 14-10 x 1" TYPE 'A' SELF-TAPPER W/WASHER (FASTENER #18) (4) PER 16" PANEL (3) PER 12" PANEL SL-82 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION MOISTURE BARRIER (NOT BY MBCI) ⁵⁄₈" PLYWOOD (MIN. (NOT BY MBCI) SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® DETAILS WOOD DECK FIXED VENTED RIDGE 3" 3” LA (M P IN .) TRI-BEAD TAPE SEALER (HW-504) RIDGE END OF PANEL PERFORATED VENT DRIP (FL-254) URETHANE TUBE SEALANT @ CLOSURE ENDS/PANEL RIB & LAPPING CLOSURE TABS TO SEAL ALL VOIDS PERFORATED VENT DRIP (FL-254) ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (1) PER RIB URETHANE SEALANT (HW-504) 2" 2" RIDGE TRIM (FL-300) ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 6" O.C. (DO NOT INSTALL THRU PANEL RIB) ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 6" O.C. TRI-BEAD TAPE SEALER (HW-504) OUTSIDE CLOSURE (HW-440) @ 16" PANEL (HW-446) @ 12" PANEL ® SuperLok PANEL TRI-BEAD TAPE SEALER (HW-504) CONT. ACROSS PANEL 14 - 10 x 1" TYPE 'A' SELF-TAPPER W/WASHER (FASTENER #18) (4) PER 16" PANEL (3) PER 12" PANEL MOISTURE BARRIER (NOT BY MBCI) ⁵⁄₈" PLYWOOD (MIN. (NOT BY MBCI) ³⁄₈" PLYWOOD SPACER (NOT BY MBCI) SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-83 SuperLok® DETAILS WOOD DECK BOX RAKE BUILDING DIM. 1¹⁄₄" ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 6" O.C. HIGH WIND PARAPET RAKE CLEAT (F-292) TRI-BEAD TAPE SEALER (HW-504) LOW RAKE SUPPORT ANGLE (HW-7712) BOX RAKE TRIM ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF DRILLER W/WASHER (FASTENER #1E) @ 24" O.C. FIELD CUT & BEND UP 2" PANEL LEG AS REQUIRED WHEN ENDING OFF MODULE LOW FLOATING CLIP (HW-230) SuperLok® PANEL 2 x 4 x 16 GA. ANGLE ¹⁄₄"-14 x 1" LONG-LIFE 'TYPE AB' SELF-TAPPER W/WASHER (FASTENER #2B) ¹⁄₈" x ³⁄₁₆" POP RIVET (FASTENER #14) @ 12" O.C. CONTINUOUS CLEAT (FL-338) OUTSIDE CLOSURE ⁵⁄₈" PLYWOOD (MIN.) (NOT BY MBCI) 12-11 x 1" PANCAKE HEAD SELF-TAPPER (FASTENER #13A) @ 24" O.C. (PRE-DRILL ANGLE) ¹⁄₄"-14 x 1¹⁄₄" SHOULDER TEK® 2 SELF-DRILLER (FASTENER #5) @ 24" O.C. (CENTER IN SLOT) 14-10 x 1" TYPE 'A' SELF-TAPPER W/WASHER (FASTENER #18) (2) PER CLIP MOISTURE BARRIER (NOT BY MBCI) WOOD BLOCKING (NOT BY MBCI) WALL PANEL SL-84 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® DETAILS WOOD DECK PARAPET RAKE BUILDING DIM. URETHANE TUBE SEALANT CONTINUOUS FEILD SAWCUT 1¹⁄₂" (MIN.) PARAPET RAKE TRIM (FL-285) TRI-BEAD TAPE SEALER (HW-504) EA. SIDE OF FLEXIBLE MEMBRANE HIGH WIND PARAPET RAKE CLEAT (F-292) TRI-BEAD TAPE SEALER (HW-504) EA. SIDE OF FLEXIBLE MEMBRANE FLEXIBLE MEMBRANE ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) @ 24" O.C. LOW FLOATING CLIP (HW-230) SuperLok® PANEL ³⁄₈" 14-10 x 2 DECK SCREW (FASTENER #209) @ 24" O.C. (PRE-DRILL HOLE) COUNTERFLASH (FL-341) 2 x 4 x 16 GAUGE ANGLE LOW RAKE SUPPORT ANGLE (HW-7712) FIELD CUT & BEND UP 2" PANEL LEG AS REQ’D WHEN ENDING OFF MODULE MASONRY WALL (NOT BY MBCI) ⁵⁄₈" PLYWOOD (MIN.) (NOT BY MBCI) ¹⁄₄"-14 x 1¹⁄₄" SHOULDER TEK® 2 SELF-DRILLER (FASTENER #5) @ 24" O.C. (CENTER IN SLOT) 12-11 x 1" PANCAKE HEAD SELF-TAPPER (FASTENER #13A) @ 24" O.C. (PRE-DRILL ANGLE) MOISTURE BARRIER (NOT BY MBCI) 14-10 x 1" TYPE 'A' SELF-TAPPER W/WASHER (FASTENER #18) (2) PER CLIP WOOD BLOCKING (NOT BY MBCI) SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-85 SuperLok® DETAILS WOOD DECK FIXED BOX HIGH SIDE EAVE 7" TRI-BEAD TAPE SEALER (HW-504) RIDGE END OF PANEL HIGH EAVE SEALANT DETAIL ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 6" O.C. (DO NOT INSTALL THRU PANEL RIB) TRI-BEAD TAPE SEALER (HW-504) 2" 2" URETHANE TUBE SEALANT @ CLOSURE ENDS/PANEL RIB & LAPPING CLOSURE TABS TO SEAL ALL VOIDS ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF DRILLER W/WASHER (FASTENER #1E) (1) PER RIB 14-10 x 1" TYPE 'A' SELF-TAPPER W/WASHER (FASTENER #18) (4) PER 16" PANEL (3) PER 12" PANEL OUTSIDE CLOSURE (HW-440) @ 16" PANEL (HW-446) @ 12" PANEL ³⁄₈" PLYWOOD SPACER (NOT BY MBCI) TRI-BEAD TAPE SEALER (HW-504) SuperLok® PANEL BOX HIGH SIDE EAVE TRIM (FL-331) ³⁄₈" ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAP TEK® W/WASHER (FASTENER #4) @ 12" O.C. MOISTURE BARRIER (NOT BY MBCI) OUTSIDE CLOSURE ¹⁄₄"-14 x 1" LONG-LIFE 'TYPE AB' SELF-TAPPER W/WASHER (FASTENER #2B) ⁵⁄₈" PLYWOOD (MIN.) (NOT BY MBCI) WOOD BLOCKING (NOT BY MBCI) WALL PANEL BUILDING DIM. SL-86 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® DETAILS WOOD DECK PARAPET FIXED HIGH SIDE EAVE 7" TRI-BEAD TAPE SEALER (HW-504) HIGH EAVE END OF PANEL BUILDING DIM. HIGH EAVE SEALANT DETAIL MASONRY WALL (NOT BY MBCI) FIELD SAWCUT TRI-BEAD TAPE SEALER (HW-504) EA. SIDE OF FLEXIBLE MEMBRANE URETHANE TUBE SEALANT CONTINUOUS COUNTER FLASH (FL341) 14-10 x 2" DECK SCREW (FASTENER #209) @ 24" O.C. (PRE-DRILL HOLE) PARAPET HIGH EAVE TRIM (FL-276) ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 6" O.C. (DO NOT INSTALL THRU PANEL RIB) FLEXIBLE MEMBRANE URETHANE TUBE SEALANT @ CLOSURE ENDS/PANEL RIB & LAPPING CLOSURE TABS TO SEAL ALL VOIDS TRI-BEAD TAPE SEALER (HW-504) @ TOP OF CLOSURE & TOP OF FLEXIBLE MEMBRANE OUTSIDE CLOSURE (HW-440) @ 16" PANEL (HW-446) @ 12" PANEL ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (1) PER RIB 2" TRI-BEAD TAPE SEALER (HW-504) SuperLok® PANEL MOISTURE BARRIER (NOT BY MBCI) 14-10 x 1" TYPE 'A' SELF-TAPPER W/WASHER (FASTENER #18) (4) PER 16" PANEL (3) PER 12" PANEL ⁵⁄₈" PLYWOOD (MIN.) (NOT BY MBCI) ³⁄₈" PLYWOOD SPACER (NOT BY MBCI) SUBJECT TO CHANGE WITHOUT NOTICE 2" SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-87 SuperLok® DETAILS WOOD DECK FLOATING VALLEY SuperLok® PANEL 1 ¹⁄₂" FIELD NOTCH PANEL LEGS AND BEND PAN TO FORM OPEN HEM NON-SKINNING BUTYL SEALANT (HW-549) BETWEEN PANEL RIBS 1 ¹⁄₂" VALLEY END OF PANEL ¹⁄₂" 1" ¹⁄₂" 1 ¹⁄₂" OFFSET CLEAT (FL-337) BUTYL SEALANT MUST COME IN CONTACT WITH THE OFFSET CLEAT TO FORM A WEATHERTIGHT SEAL LOW FLOATING CLIP (HW-230) 1'-0" MAX VALLEY TRIM (FL-707) . 12-11 x 1" PANCAKE HEAD SELF-TAPPER (FASTENER #13A) @ 12" O.C. (FASTENER MUST GO THROUGH TAPE SEALER) NON-SKINNING BUTYL SEALANT (HW-549) BETWEEN PANEL RIBS TRI-BEAD TAPE SEALER (HW-504) SuperLok® PANEL 4 ¹⁄₂" ¹⁄₂" 2" ³⁄₈" OFFSET CLEAT (FL-337) 12-11 x 1" PANCAKE HEAD SELF-TAPPER (FASTENER #13A) @ 5'-0" O.C. MOISTURE BARRIER (NOT BY MBCI) 14-10 x 1" TYPE “A” SELF-TAPPER W/WASHER (FASTENER #18) (2) PER CLIP ⁵⁄₈" PLYWOOD (MIN.) (NOT BY MBCI) NOTE: DO NOT USE THIS DETAIL ON ROOF SLOPES LESS THAN 3:12 SL-88 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® DETAILS WOOD DECK FIXED HIP 3" TRI-BEAD TAPE SEALER (HW-504) HIP END OF PANEL RIDGE/HIP TRIM (FL-209) 2" URETHANE TUBE SEALANT @ CLOSURE ENDS 2" ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 12" O.C. TRI-BEAD TAPE SEALER (HW-504) ZEE CLOSURE (FL-361) (FIELD CUT TO LENGTH & BEVEL CUT TO FIT PANEL) SuperLok® PANEL ³⁄₈" 14-10 x 1" TYPE “A” SELF-TAPPER W/WASHER (FASTENER #18) @ 6" O.C. SUBJECT TO CHANGE WITHOUT NOTICE ³⁄₈" PLYWOOD SPACER (NOT BY MBCI) TRI-BEAD TAPE SEALER (HW-504) CONTINUED ACCROSS PANEL SEE www.mbci.com FOR CURRENT INFORMATION MOISTURE BARRIER (NOT BY MBCI) ⁵⁄₈" PLYWOOD (MIN.) (NOT BY MBCI) REV 00.01 SL-89 SuperLok® DETAILS RIGID INSULATION OVER METAL DECK FLOATING ENDLAP UPPER SWAGED SuperLok® PANEL SWAGED ENDLAP TAPE SEALER (HW-515) EW VI ” “A SWAGED ENDLAP TAPE SEALER (HW-515) PREPUNCHED HOLES (16" PANEL ONLY) VIEW “A” ¹⁄₄"-14 x ⁵⁄₈" LONG-LIFE TYPE “B” W/WASHER (FASTENER #46) (5) PER 16" PANEL (4) PER 12" PANEL BACK-UP PLATE (HW-7766) 16” PANEL (HW-7764) 12” PANEL TRI-BEAD TAPE SEALER (HW-504) @ 16" PANEL TRIPLE-BEAD TAPE SEALER (HW-502) @ 12" PANEL 6" LOWER SuperLok® PANEL 1 ¹⁄₂" TRI-BEAD TAPE SEALER (HW-504) @ 16" PANEL TRIPLE-BEAD TAPE SEALER (HW-502) @12" PANEL UPPER SWAGED SuperLok® PANEL LOW FLOATING CLIP (HW-230) BACK-UP PLATE (HW-7766) 16” PANEL (HW-7764) 12” PANEL SuperLok® PANEL (LOWER) ³⁄₈" RIGID INSULATION (NOT BY MBCI) 4 ¹⁄₂" METAL DECK (MIN. 22 GA.) (NOT BY MBCI) 10" VAPOR BARRIER (NOT BY MBCI) 12” 3 2 4 1 BEARING PLATE (HW-7500) DECK SCREW (2) PER CLIP (MIN. ³⁄₄" PENETRATION INTO METAL DECK) ¹⁄₄"-14 x ⁵⁄₈" LONG-LIFE TYPE “B” SELF-TAPPER W/WASHER (FASTENER #46) (5) PER 16" PANEL (4) PER 12" PANEL 16” 2 3 4 5 1 FASTENER INSTALLATION SEQUENCE SL-90 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® DETAILS RIGID INSULATION OVER METAL DECK FLOATING EAVE WITH BOX GUTTER FIELD NOTCH PANEL LEGS AND BEND PAN TO FORM OPEN HEM 1¹⁄₂" SuperLok® PANEL 1¹⁄₂" NON-SKINNING BUTYL SEALANT (HW-549) BETWEEN PANEL RIBS 1" ¹⁄₂" EAVE END OF PANEL BOX GUTTER W/DRIP EDGE (T-5271) ¹⁄₂" 1¹⁄₂" PANEL ENGAGMENT DETAIL BUTYL SEALANT MUST COME IN CONTACT WITH THE DRIP EDGE TO FORM A WEATHERTIGHT SEAL AX. 1'-0" M PANEL WALL NESS THICK 2" LOW FLOATING CLIP (HW-230) DECK SCREW (2) PER CLIP (MIN. ³⁄₄" PENETRATION INTO METAL DECK) ¹⁄₂" NON-SKINNING BUTYL SEALANT (HW-549) BETWEEN PANEL RIBS 12-14 x 1" PANCAKE HEAD SELF-DRILLER (FASTENER #12A) @ 12" O.C. GUTTER STRAP (FL-310) @ EVER OTHER RIB BEARING PLATE (HW-7500) SuperLok® PANEL ³⁄₈" ¹⁄₈" x ³⁄₁₆" POP RIVET (FASTENER #14) (2) PER STRAP RIGID INSULATION (NOT BY MBCI) BOX GUTTER W/DRIP EDGE (T-5271) VAPOR BARRIER (NOT BY MBCI) 12 x 24 x 1¹⁄₄" LONG-LIFE TEK 4.5 W/WASHER (FASTENER #78) 3" x 5" x 14 GA. BENT PLATE (HOLD TOP LEG ³⁄₈" ABOVE TOP OF INSULATION) METAL DECK (NOT BY MBCI) 12 - 24 x 1¹⁄₂" PAN HEAD TEK 4.5 SELF-DRILLER (FASTENER #16) @ 12" O.C. WALL PANEL STRUCTURAL ANGLE (NOT BY MBCI) BUILDING DIM. NOTE: DO NOT USE THIS DETAIL ON ROOF SLOPES LESS THAN 3:12 SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-91 SuperLok® DETAILS RIGID INSULATION OVER METAL DECK FLOATING EAVE WITH EAVE TRIM WITH EXTENDED DRIP EDGE SuperLok® PANEL FIELD NOTCH PANEL LEGS AND BEND PAN TO FORM OPEN HEM 1¹⁄₂" NON-SKINNING BUTYL SEALANT (HW-549) BETWEEN PANEL RIBS 1¹⁄₂" EAVE END OF PANEL ¹⁄₂" 1" ¹⁄₂" EAVE TRIM W/EXTENDED DRIP EDGE (T-5151) 1¹⁄₂" PANEL ENGAGMENT DETAIL BUTYL SEALANT MUST COME IN CONTACT WITH THE DRIP EDGE TO FORM A WEATHERTIGHT SEAL AX. 1'-0" M LOW FLOATING CLIP (HW-230) DECK SCREW (2) PER CLIP (MIN. ³⁄₄" PENETRATION INTO METAL DECK) 2" ¹⁄₂" NON-SKINNING BUTYL SEALANT (HW-549) BETWEEN PANEL RIBS 12-14 x 1" PANCAKE HEAD SELF-DRILLER (FASTENER #12A) @ 12" O.C. EAVE TRIM W/DRIP EDGE (T-5151) BEARING PLATE (HW-7500) SuperLok® PANEL ³⁄₈" 12 - 24 x 1¹⁄₄" LONG-LIFE TEK 4.5 W/WASHER (FASTENER #78) RIGID INSULATION (NOT BY MBCI) VAPOR BARRIER (NOT BY MBCI) ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 12" O.C. 3" x 5" x 14 GA. BENT PLATE (HOLD TOP OF PLATE ³⁄₈" ABOVE TOP OF RIGID INSULATION) OUTSIDE CLOSURE METAL DECK (NOT BY MBCI) 12-24 x 1¹⁄₂" PAN HEAD TEK 4.5 SELF-DRILLER (FASTENER #16) @ 12" O.C. WALL PANEL STRUCTURAL ANGLE (NOT BY MBCI) BUILDING DIM. NOTE: DO NOT USE THIS DETAIL ON ROOF SLOPES LESS THAN 3:12 SL-92 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® DETAILS RIGID INSULATION OVER METAL DECK FIXED RIDGE 3" TRI-BEAD TAPE SEALER (HW-504) RIDGE END OF PANEL RIDGE TRIM (FL-209) ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (1) PER RIB 2" URETHANE TUBE SEALANT @ CLOSURE ENDS/PANEL RIB & LAPPING CLOSURE TABS TO SEAL ALL VOIDS 2" ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 6” O.C. (DO NOT INSTALL THRU PANEL RIB) TRI-BEAD TAPE SEALER (HW-504) RIDGE/HIP SUPPORT PLATE (P-145) SuperLok® PANEL OUTSIDE CLOSURE (HW-440) @ 16" PANEL (HW-446) @ 12" PANEL ³⁄₈" DECK SCREW @ 12" O.C.(MIN. ³⁄₄" PENETRATION INTO METAL DECK) ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (4) PER 16" PANEL (3) PER 12" PANEL RIGID INSULATION (NOT BY MBCI) TRI-BEAD TAPE SEALER (HW-504) VAPOR BARRIER (NOT BY MBCI) METAL DECK (NOT BY MBCI) SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-93 SuperLok® DETAILS RIGID INSULATION OVER METAL DECK FIXED VENTED RIDGE 3" URETHANE SEALANT (HW-504) 1" LA (M P IN .) TRI-BEAD TAPE SEALER (HW-504) RIDGE END OF PANEL PERFORATED VENT DRIP (FL-254) URETHANE TUBE SEALANT @ CLOSURE ENDS/PANEL RIB & LAPPING CLOSURE TABS TO SEAL ALL VOIDS PERFORATED VENT DRIP (FL-254) 2" ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (1) PER RIB 2" RIDGE TRIM (FL-303) TRI-BEAD TAPE SEALER (HW-504) ¹⁄₄"-14 x ⁷⁄₈" LONG LIFE LAPTEK W/WASHER (FASTENER #4) @ 6” O.C. (DO NOT INSTALL THRU PANEL RIB) ¹⁄₄"-14 x ⁷⁄₈" LONG LIFE LAPTEK W/WASHER (FASTENER #4) @ 6” O.C. OUTSIDE CLOSURE (HW-440) @ 16" PANEL (HW-446) @ 12" PANEL ® SuperLok PANEL ³⁄₈" 1" MIN. TRI-BEAD TAPE SEALER (HW-7631) DECK SCREW @ 12" O.C. (MIN. ³⁄₄" PENETRATION INTO METAL DECK) ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (4) PER 16" PANEL (3) PER 12" PANEL LOW MID-SLOPE FIXED PLATE (HW-7631) SL-94 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION RIGID INSULATION (NOT BY MBCI) VAPOR BARRIER (NOT BY MBCI) METAL DECK (NOT BY MBCI) SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® DETAILS RIGID INSULATION OVER METAL DECK BOX RAKE BUILDING DIM. 1¹⁄₄" ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 6" O.C. TRI-BEAD TAPE SEALER (HW-504) BOX RAKE TRIM LOW RAKE SUPPORT ANGLE (HW-7712) 12 - 24 x 1¹⁄₄" PAN HEAD TEK 4.5 SELF-DRILLER (FASTENER #16) @ 12" O.C. HIGH WIND PARAPET RAKE CLEAT (F-292) ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) @ 24" O.C. FIELD CUT & BEND UP 2" PANEL LEG AS REQUIRED WHEN ENDING OFF MODULE LOW FLOATING CLIP (HW-230) BEARING PLATE (HW-7500) SuperLok® PANEL ³⁄₈" 12 - 24 x 1¹⁄₄" LONG-LIFE TEK 4.5 W/WASHER (FASTENER #78) CONTINUOUS CLEAT (FL-338) ¹⁄₈" x ³⁄₁₆" POP RIVET (FASTENER #14) @ 12" O.C. OUTSIDE CLOSURE 2 x 4 x 16 GA. ANGLE WALL PANEL ¹⁄₄ -14 x 1¹⁄₄ SHOULDER TEK® 2 SELF-DRILLER (FASTENER #5) @ 24" O.C (CENTER IN SLOT) STRUCTURAL ANGLE (NOT BY MBCI) SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION RIGID INSULATION (NOT BY MBCI) VAPOR BARRIER (NOT BY MBCI) DECK SCREW (2) PER CLIP (MIN. ³⁄₄" PENETRATION INTO METAL DECK) METAL DECK (NOT BY MBCI) REV 00.01 SL-95 SuperLok® DETAILS RIGID INSULATION OVER METAL DECK PARAPET RAKE URETHANE TUBE SEALANT CONTINUOUS 14-10 x 2" DECK SCREW (FASTENER #209) @ 24" O.C. (PRE-DRILL HOLE) 1¹⁄₂" (MIN.) COUNTERFLASH (FL-341) PARAPET RAKE TRIM (FL-285) TRI-BEAD TAPE SEALER (HW-504) EA. SIDE OF FLEXIBLE MEMBRANE HIGH WIND PARAPET RAKE CLEAT (F-292) TRI-BEAD TAPE SEALER (HW-504) EA. SIDE OF FLEXIBLE MEMBRANE FLEXIBLE MEMBRANE ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) @ 24" O.C. LOW FLOATING CLIP (HW-230) DECK SCREW @ (2) PER CLIP (MIN. ³⁄₄" PENETRATION INTO METAL DECK) BEARING PLATE (HW-7500) SuperLok® PANEL ³⁄₈" FEILD SAWCUT LOW RAKE SUPPORT ANGLE (HW-7712) FIELD CUT & BEND UP 2" PANEL LEG AS REQ’D WHEN ENDING OFF MODULE BEARING PLATE (HW-7500) @ 24" O.C. ¹⁄₄"-14 x 1¹⁄₄" SHOULDER TEK® 2 SELF-DRILLER (FASTENER #5) @ 24" O.C VAPOR BARRIER (NOT BY MBCI) DECK SCREW @ 24" O.C. (MIN. ³⁄₄" PENETRATION INTO METAL DECK) STRUCTURAL ANGLE (NOT BY MBCI) SL-96 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION RIGID INSULATION (NOT BY MBCI) METAL DECK (NOT BY MBCI) SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® DETAILS RIGID INSULATION OVER METAL DECK FIXED BOX HIGH SIDE EAVE 7" TRI-BEAD TAPE SEALER (HW-504) HIGH EAVE END OF PANEL HIGH EAVE SEALANT DETAIL ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 6" O.C. (DO NOT INSTALL THRU PANEL RIB) TRI-BEAD TAPE SEALER (HW-504) LOW FIXED EAVE PLATE (HW-7600) DECK SCREW @ 12" O.C. (MIN. ³⁄₄" PENETRATION INTO METAL DECK) 2" 2" URETHANE TUBE SEALANT @ CLOSURE ENDS/PANEL RIB & LAPPING CLOSURE TABS TO SEAL ALL VOIDS ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF DRILLER W/WASHER (FASTENER #1E) (1) PER RIB OUTSIDE CLOSURE (HW-440) @ 16" PANEL (HW-446) @ 12" PANEL TRI-BEAD TAPE SEALER (HW-504) BOX HIGH SIDE EAVE TRIM (FL-331) SuperLok® PANEL ³⁄₈" ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 12" O.C. OUTSIDE CLOSURE RIGID INSULATION (NOT BY MBCI) VAPOR BARRIER (NOT BY MBCI) METAL DECK (NOT BY MBCI) ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (4) PER 16" PANEL (3) PER 12" PANEL 12-24 x 1¹⁄₄" LONG-LIFE TEK 4.5 W/WASHER (FASTENER #78) WALL PANEL STURCTURAL ANGLE (NOT BY MBCI) BUILDING DIM. SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-97 SuperLok® DETAILS RIGID INSULATION OVER METAL DECK PARAPET FIXED HIGH SIDE EAVE 7" TRI-BEAD TAPE SEALER (HW-504) RIDGE END OF PANEL HIGH EAVE SEALANT DETAIL MASONRY WALL (NOT BY MBCI) URETHANE TUBE SEALANT CONTINUOUS COUNTER FLASH (FL-341) PARAPET HIGH EAVE TRIM (FL-276) ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 6" O.C. (DO NOT INSTALL THRU PANEL RIB) TRI-BEAD TAPE SEALER (HW-504) EA. SIDE OF FLEXIBLE MEMBRANE 14 -10 x 2" DECK SCREW (FASTENER #209) @ 24" O.C. (PRE-DRILL HOLE) TRI-BEAD TAPE SEALER (HW-504) @ TOP OF CLOSURE & TOP OF FLEXIBLE MEMBRANE LOW MID-SLOPE FIXED PLATE (HW-7631) FIELD SAWCUT FLEXIBLE MEMBRANE 2" URETHANE TUBE SEALANT @ CLOSURE ENDS/PANEL RIB & LAPPING CLOSURE TABS TO SEAL ALL VOIDS ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (1) PER RIB SuperLok® PANEL OUTSIDE CLOSURE (HW-440) @ 16" PANEL (HW-446) @ 12" PANEL ³⁄₈" TRI-BEAD TAPE SEALER (HW-504) RIGID INSULATION (NOT BY MBCI) VAPOR BARRIER (NOT BY MBCI) ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) (4) PER 16" PANEL (3) PER 12" PANEL DECK SCREW @ 12" O.C. (MIN. ³⁄₄" PENETRATION INTO METAL DECK) METAL DECK (NOT BY MBCI) SL-98 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® DETAILS RIGID INSULATION OVER METAL DECK FLOATING VALLEY SuperLok® PANEL 1 ¹⁄₂" FIELD NOTCH PANEL LEGS AND BEND PAN TO FORM OPEN HEM NON-SINNING BUTYL SEALANT (HW-549) BETWEEN PANEL RIBS 1 ¹⁄₂" VALLEY END OF PANEL ¹⁄₂" 1" ¹⁄₂" 1 ¹⁄₂" OFFSET CLEAT (FL-337) BUTYL SEALANT MUST COME IN CONTACT WITH THE OFFSET CLEAT TO FORM A WEATHERTIGHT SEAL VALLEY TRIM (FL-707) LOW FLOATING CLIP (HW-230) NON-SINNING BUTYL SEALANT (HW-549) BETWEEN PANEL RIBS 4 ¹⁄₂" 1'-0" M AX. OFFSET CLEAT (FL-337) TRI-BEAD TAPE SEALER (HW-504) ¹⁄₂" SuperLok® PANEL 2" ³⁄₈" BEARING PLATE (HW-7500) 12-14 X 1" PANCAKE HEAD SELF-DRILLER (FASTENER #12A) @ 12" O.C. (FASTENER MUST GO THROUGH TAPE SEALER) DECK SCREW @ 12" O.C. (MIN. ³⁄₄" PENETRATION INTO METAL DECK) VALLEY SUPPORT PLATE (P-105) DECK SCREW (2) PER CLIP (MIN. ³⁄₄" PENETRATION INTO METAL DECK) RIGID INSULATION (NOT BY MBCI) VAPOR BARRIER (NOT BY MBCI) METAL DECK (NOT BY MBCI) NOTE: DO NOT USE THIS DETAIL ON ROOF SLOPES LESS THAN 3:12 SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-99 SuperLok® DETAILS RIGID INSULATION OVER METAL DECK FIXED HIP 3" TRI-BEAD TAPE SEALER (HW-504) HIP END OF PANEL RIDGE/HIP TRIM (FL-209) 2" URETHANE TUBE SEALANT @ CLOSURE ENDS (¹⁄₄" BEAD MIN.) 2" ¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK W/WASHER (FASTENER #4) @ 6" O.C. (DO NOT INSTALL THRU PANEL RIB) TRI-BEAD TAPE SEALER (HW-504) ZEE CLOSURE (FL-361) (FIELD CUT TO LENGTH & BEVEL CUT TO FIT PANEL) SuperLok® PANEL ³⁄₈" ¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE SELF-DRILLER W/WASHER (FASTENER #1E) @ 6" O.C. DECK SCREW @ 12" O.C. (MIN. ³⁄₄" PENETRATION INTO METAL DECK) TRI-BEAD TAPE SEALER (HW-504) CONTINUED ACROSS PANEL RIGID/HIP SUPPORT PLATE (P-145) SL-100 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION RIGID INSULATION (NOT BY MBCI) VAPOR BARRIER (NOT BY MBCI) METAL DECK (NOT BY MBCI) SUBJECT TO CHANGE WITHOUT NOTICE SuperLok® NOTES SUBJECT TO CHANGE WITHOUT NOTICE SEE www.mbci.com FOR CURRENT INFORMATION REV 00.01 SL-101 SuperLok® NOTES SL-102 REV 00.01 SEE www.mbci.com FOR CURRENT INFORMATION SUBJECT TO CHANGE WITHOUT NOTICE For the most current information available, visit our Web site at www.mbci.com Houston, TX 14031 West Hardy P.O. Box 38217 Houston, TX 77238 281-407-6915 Adel, GA 1601 Rogers Road P.O. Box 1107 Adel, GA 31620 888-514-6062 Atlanta, GA 2280 Monier Avenue P.O. Box 44729 Atlanta, GA 30336 678-337-1619 Atwater, CA 550 Industry Way P.O. Box 793 Atwater, CA 95301 209-445-3891 Ennis TX 1804 Jack McKay Blvd. P.O. Box 1210 Ennis, TX 75120 469-256-8255 Indianapolis, IN 1780 McCall Drive P.O. Box 657 Shelbyville, IN 46176 317-364-4329 Lubbock, TX 5711 East FM-40 P.O. Box 10133 Lubbock, TX 79408 806-224-2724 Memphis, TN 300 Highway 51 North P.O. Box 366 Hernando, MS 38632 662-298-2337 Oklahoma City, OK 7000 S. Eastern Avenue P.O. Box 95998 Oklahoma City, OK 73149 405-492-6968 Omaha, NE 1011 Ellison Avenue Omaha, NE 68110 402-983-8006 Phoenix, AZ 660 South 91st Avenue P.O. Box 739 Tolleson, AZ 85353 480-630-3022 Rome, NY 6168 State Route 233 P.O. Box 4141 Rome, NY 13442 315-371-4330 Salt Lake City, UT 1155 West 2300 North P.O. Box 16027 Salt Lake City, UT 84116 385-715-2952 San Antonio, TX 8677 I-10 East P.O. Box 69 Converse, TX 78109 210-888-9768 September 15, 2016 / Rev 00.01