SuperLok®
Mechanically Seamed Roof System
Technical/Installation Information
IMPORTANT NOTICE
READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE SUPERLOK®
ROOFING SYSTEM. THE MANUFACTURER DETAILS MUST BE FOLLOWED AS A MINIMUM TO INSURE
APPROPRIATE WARRANTIES WILL BE ISSUED.
ALWAYS INSPECT EACH AND EVERY PANEL AND ALL ACCESSORIES BEFORE INSTALLATION. NEVER
INSTALL ANY PRODUCT IF ITS QUALITY IS IN QUESTION. NOTIFY MBCI IMMEDIATELY IF ANY PRODUCT
IS BELIEVED TO BE OUT OF TOLERANCE, SPECIFICATION OR HAS BEEN DAMAGED DURING SHIPMENT.
IF THERE IS A CONFLICT BETWEEN PROJECT INSTALLATION DRAWINGS PROVIDED OR APPROVED
BY THE MANUFACTURER AND DETAILS IN THIS MANUAL, PROJECT INSTALLATION DRAWINGS WILL
TAKE PRECEDENCE.
Ice Dam Disclaimer
MBCI designs it’s standing seam roofs to meet the load requirements dictated by governing codes and project specifications,
including applicable snow loads. However, MBCI expressly disclaims responsibilty for weathertightness or roof point loading
issues or other hazards resulting from ice dam situations. Any time ice and snow can melt on the main body of the roof and
refreeze at the eave or in the shadow of an adjacent wall, an ice dam situation may develop. In addition to local climate,
ice dam formation is affected by many other factors, including but not limited to, roof insulation R value, roof panel color,
interior temperature of building, heater location in building, eave overhangs, parapet walls, shading of building roof areas
from adjacent trees, parapets, buildings, etc. These factors are design and maintenance issues and are outside the control of
MBCI. MBCI specifically disclaims any liability for damage due to ice dam formation, although the following issues should be
taken into consideration concerning standing seam roofs installed in freezing climates:
•
Always use field seamed panels. These machine-folded seams are more durable when subjected to occasional icing.
•
Eliminate “cold” eave overhangs and parapet walls from the building design. Roof overhangs outside the heated
envelope of the building will tend to be colder than the roof areas over the heated envelope. Simple roof designs
are preferred. Parapet walls at the eave allow ice and snow to collect due to shading effects and the lower roof
temperatures caused thereby.
•
Make sure the interior of the building is adequately insulated and the heating is properly distributed. Inadequate
insulation in the roof and/or improper heat distribution causes heat flow though the main body of the roof. On days
when the temperature is below freezing, this heat gain can cause ice and snow to melt and refreeze at the eave
where the roof is colder.
•
Lay out the building to prevent the eaves and other roof areas from being shaded during the winter. This may mean
eliminating adjacent trees or reconsidering roof geometries.
•
Consider using self-regulating heating cables at the eaves to mitigate the effects of ice dams.
•
On building designs using attics, over-insulate the attic floor and provide adequate ventilation in the attic. This will
reduce heat transfer through the roof resulting in more consistent roof temperatures between eave and field of roof.
•
Increase the degree of diligence with respect to underlayment materials at roof areas prone to icing. This may include
valleys, eaves, dormers and roof areas near dormers, parapets and the like where shading may occur.
For more information on this subject, please refer to the MCA’s Metal Roof Design For Cold Climates manual.
The engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommended that the design
professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed Steel Structural Members published
by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria for cold-formed steel components. Along with the
Specification, the designer should reference the most current building code applicable to the project jobsite in order to determine environmental loads. If further
information or guidance regarding cold-formed design practices is desired, please contact the manufacturer
©Copyright NCI Group, Inc. 2016 All Rights Reserved
Descriptions and specifications contained herein were in effect at the time this publication was approved for printing. In a
continuing effort to refine and improve products, MBCI reserves the right to discontinue products at any time or change
specifications and/or designs without incurring obligation. To ensure you have the latest information available, please inquire
or visit our website at www.mbci.com. Application details are for illustration purposes only and may not be appropriate for all
environmental conditions, building designs or panel profiles. Projects should be designed to conform to applicable building codes,
regulations and accepted industry practices. If there is a conflict between this manual and project erection drawings, the erection
drawings will take precedence.
SuperLok®
TABLE OF CONTENTS
ROOFING SYSTEM
General Description ............................................................................................................................................................. SL-3
Architect/Engineering Information........................................................................................................................................ SL-4
ENGINEERING
Read This First .................................................................................................................................................................... SL-5
UL 90 Requirements ............................................................................................................................................................ SL-6
12" Properties/Load Tables ......................................................................................................................................SL-7 – SL-8
16" Properties/Load Tables ....................................................................................................................................SL-9 – SL-10
GENERAL INFORMATION
Product Checklist ..................................................................................................................................................SL-11 – SL-20
Panel Orientation ............................................................................................................................................................... SL-21
Installation Guidelines........................................................................................................................................................ SL-21
Preparatory Requirements................................................................................................................................................. SL-22
Unloading ..............................................................................................................................................................SL-23 – SL-24
Handling/Panel Storage ..................................................................................................................................................... SL-25
Proper Handling, Storage and Maintenance of Painted and Galvalume Plus® Panels ........................................SL-26 – SL-27
INSTALLATION SEQUENCE
Step
Step
Step
Step
Step
Step
Step
Step
Step
Step
Step
Step
Step
Step
1
2
2A
3
4
5
6
7
8
9
10
11
12
13
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Rake Attachments ....................................................................................................................................... SL-28
Low System Eave ........................................................................................................................................ SL-29
High System Eave ....................................................................................................................................... SL-30
Thermal Spacer (For High Systems Only) .................................................................................................. SL-31
First Panel ................................................................................................................................................... SL-32
Clip Installation ............................................................................................................................................ SL-33
Endlap.......................................................................................................................................................... SL-34
Ridge ........................................................................................................................................................... SL-35
Subsequent Runs Eave ............................................................................................................................... SL-36
Subsequent Runs Endlap ............................................................................................................................ SL-37
Subsequent Runs Ridge.............................................................................................................................. SL-38
Last Panel Run ............................................................................................................................................ SL-39
Seaming Operation.........................................................................................................................SL-40 – SL-42
Outside Closure Installation......................................................................................................................... SL-43
SPECIAL ERECTION TECHNIQUES
UL 90 Light Transmitting Panel Installation ....................................................................................................................... SL-44
Curb Installation ....................................................................................................................................................SL-45 – SL-62
Pipe Penetration Installation .................................................................................................................................SL-63 – SL-64
DETAILS
Open Framing
Fixed Eave With Sculptured Gutter ................................................................................................................................... SL-65
Fixed Eave With Sculptured Eave Trim............................................................................................................................. SL-66
Fixed Eave With Box Eave Trim........................................................................................................................................ SL-67
Floating Ridge.................................................................................................................................................................... SL-68
Floating Vented Ridge ....................................................................................................................................................... SL-69
Fixed Vented Eave ............................................................................................................................................................ SL-70
Sculptured Rake ................................................................................................................................ SL-71
Sculptured Rake With Cleat .............................................................................................................................................. SL-72
Parapet Rake ..................................................................................................................................................................... SL-73
Floating Sculptured High Side Eave .................................................................................................................................. SL-74
Parapet Floating High Side Eave ...................................................................................................................................... SL-75
Fixed Valley...................................................................................................................................... SL-76
Floating Hip...................................................................................................................................... SL-77
SUBJECT TO CHANGE WITHOUT NOTICE
SEE
www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-1
SuperLok®
TABLE OF CONTENTS
Wood Deck
Field Hemming Panel End ................................................................................................................................................. SL-78
Floating Endlap................................................................................................................................. SL-79
Floating Eave with Box Gutter ........................................................................................................................................... SL-80
Floating Eave with Eave Trim with Extended Drip Edge ................................................................................................... SL-81
Fixed Ridge...................................................................................................................................... SL-82
Fixed Vented Ridge ........................................................................................................................................................... SL-83
Box Rake......................................................................................................................................... SL-84
Parapet Rake ..................................................................................................................................................................... SL-85
Fixed Box High Side Eave ................................................................................................................................................. SL-86
Parapet Fixed High Side Eave .......................................................................................................................................... SL-87
Floating Valley ................................................................................................................................................................... SL-88
Fixed Hip......................................................................................................................................... SL-89
Rigid Insulation Over Metal Deck
Floating Endlap.................................................................................................................................. SL-90
Floating Eave With Box Gutter .......................................................................................................................................... SL-91
Floating Eave With Eave Trim with Extended Drip Edge .................................................................................................. SL-92
Fixed Ridge...................................................................................................................................... SL-93
Fixed Vented Ridge ........................................................................................................................................................... SL-94
Box Rake......................................................................................................................................... SL-95
Parapet Rake ..................................................................................................................................................................... SL-96
Fixed Box High Side Eave ................................................................................................................................................. SL-97
Parapet Fixed High Side Eave .......................................................................................................................................... SL-98
Floating Valley ................................................................................................................................................................... SL-99
Fixed Hip.........................................................................................................................................SL-100
SL-2
REV 00.01
SEE
SEEwww.mbci.com
www.mbci.comFOR
FORCURRENT
CURRENTINFORMATION
INFORMATION
SUBJECT
SUBJECTTO
TOCHANGE
CHANGEWITHOUT
WITHOUTNOTICE
NOTICE
SuperLok®
ROOFING SYSTEM
GENERAL DESCRIPTION
16" or 12"
¹⁄₁₆"
2"
Coverage Width - 16" or 12"
Minimum Slope - 1/2:12
Panel Attachment - Low, High (Fixed or Floating) or Utility (No insulation clearance)
Panel Substrate - Galvalume® (standard)
Gauge - Standard: 24 ; Optional: 22
Finishes - Smooth Striated (standard)* or Embossed Striated
Coatings - Signature® 200, Signature® 300, Signature® 300 Metallic
PRODUCT SELECTION CHART
Signature® 300
Metallic
PRODUCT
Signature® 300
Signature® 200
Galvalume
Plus®
24
Ga.
22
Ga.
24
Ga.
22
Ga.
24
Ga.
22
Ga.
24
Ga.
22
Ga.
„
„
„
„
„
„
„
„
„
„
z
„
„
z
„
SuperLok® HS
16" Wide
12" Wide
„
Signature is a registered trademark of NCI Group, Inc. Galvalume Plus is a registered trademark of BIEC
International.
z
„
— Available in any quantity.
— Minimum quantity may be required.
Other colors, finishes, gauges, and materials available; please inquire.
* Striated panels are standard to reduce “oil canning”.
CAUTION
Diaphragm capabilities and purlin stability are not provided by manufactures SuperLok® roof system.
Therefore, other bracing may be required to conform to A.I.S.C. or A.I.S.I. specifications.
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-3
SuperLok®
ROOFING SYSTEM
ARCHITECT/ENGINEER INFORMATION
1. SuperLok® is a mechanically seamed roof system. SuperLok® panels are available in 12" and 16" widths.
Factory applied mastic inside of female leg of panel is standard.
2. SuperLok® is a structural roofing panel. This panel can be installed directly over purlins or bar joists. It does not
require a solid substructure for support. The SuperLok® roof system has several different UL 90 construction
numbers.
3. SuperLok® is recommended for roof slopes of ¹⁄₂:12 or greater.
4. Weathertight and aesthetically pleasing endlaps may be accomplished through the use of swaged and prepunched
panels. 12" wide panels are not prepunched for endlaps. The manufacturer provides a prepunched back-up
plate at the endlap for weathertightness. Swaged endlaps require the roof erection to proceed from right to left as
viewed from the eave looking toward the ridge. Roofs with no endlaps and less than 6:12 may be erected from
either direction.
5. Heavier gauges, striations and embossing minimize oil canning. Industry standard is a minimum 24 gauge
material. Striations are standard to reduce oil canning. Oil canning is not a cause for rejection.
6. Substructure must be on an even plane from eave to ridge to avoid panel distortion (¹⁄₄" in 20', ³⁄₈" in 40' tolerance).
7. All panels require end sealant at eave and valley conditions; however, for illustration purposes, this sealant is not
shown on all drawings.
8. For proper fastener application, see Product Checklist.
9. All perimeter trim dimensions in this manual are based on a wall panel thickness of 1¹⁄₄" ("PBR" Panel). Any
variation from this wall panel thickness may affect the perimeter trim dimensions.
10. The information in this manual is believed to be correct and accurate.
11. Drawings in this manual utilize the low floating clip. Clips are available in low or high fixed, low or high floating and
utility.
12. Avoid restricting the thermal expansion and contraction of the SuperLok® panels. (ie: Do not attach panel
to the substructure at both the eave and ridge.) However, panels must be attached to the substructure at
one end to prevent their sliding downslope.
13. SuperLok® panels are not designed to be work platforms. Avoid any unnecessary foot traffic on SuperLok®
panels. If foot traffic is required, protect the roof panels by using soft soled shoes and some type of roof pad,
temporary deck, or walkway.
14. WARNING: Light transmitting panels are not designed or intended to bear the weight of any person
walking, stepping, standing or resting on them. THE MANUFACTURER DISCLAIMS ANY WARRANTY OR
REPRESENTATION, EXPRESS OR IMPLIED, that any person can safely walk, step, stand or rest on or near
these light transmitting panels or that they comply with any OSHA regulation.
15. A vapor retarder may be necessary to protect roofing components when high interior humidity is a factor. The need
for a vapor retarder, as well as the type, placement and location should be determined by an architect or engineer.
The following are examples of conditions that may require a vapor retarder: (A) Projects where outside winter
temperatures below 40°F are anticipated and where average winter interior relative humidity of 45% or greater is
expected. (B) Building usages with high humidity interiors, such as indoor swimming pools, textile manufacturing
operations, food, paper or other wet-process industrial plants. (C) Construction elements that may release moisture
after the roof is installed, such as interior concrete and masonry, plaster finishes and fuel burning heaters.
16. Field cutting of the panels should be avoided where possible. If field cutting is required, the panels must be
cut with nibblers, snips, or shears to prevent edge rusting. Do not cut the panels with abrasive saw blades,
grinders, or torches.
CAUTION
Application and design details are for illustration purposes only, and may not be appropriate for all environmental conditions or
building designs. Projects should be engineered to conform to applicable building codes, regulations, and accepted industry
practices.
SL-4
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
ENGINEERING
IMPORTANT
READ THIS FIRST
CAUTION
The use of any field seaming machine other than that provided by the manufacturer will damage the panels and void all
warranties and will void all engineering data.
Low Floating System - With or without ³⁄₈" thermal spacer. See Insulation/Thermal Spacer Selection Chart below.
High Floating System - With ³⁄₈", ⁵⁄₈" or 1" thermal spacer. See Insulation/Thermal Spacer Selection Chart below.
Thermal calculations should be performed for each project to ensure that the thermal movement of the roof is not
greater than the floating clip’s capacity. Various densities of blanket insulation may affect the installation and or the
appearance of a metal roof system. The installer is responsible for selecting the proper clip and thermal spacer for their
conditions.
Insulation/Thermal Spacer Selection Chart
Insulation Thickness
Low System
High System
No Insulation
³⁄₈" Thermal Spacer
High System Not Recommended
3" Insulation
Thermal Spacer Not Recommended
⁵⁄₈" Thermal Spacer
4" Insulation
Thermal Spacer Not Recommended
³⁄₈" Thermal Spacer
6" Insulation
Low System Not Recommended
Thermal Spacer Not Recommended
Warning
As with all standing seam roof systems, sound attenuation (example: blanket insulation) should be installed between the
panels and open framing, such as purlins or joists, to prevent “roof rumble” during windy conditions.
Applications over solid deck such as rigid insulation over a metal deck or a wood deck may require additional acoustical
consideration to ensure that thermal vibration noises are isolated from the building interior. This is especially important if the
bottom of the deck is left open to the interior or in cathedral ceiling applications.
A vapor retarder may be necessary to protect roofing components when high humidity is a factor. The need for a vapor
retarder, as well as the type, placement and location should be determined by an architect or engineer. The following are
examples of conditions that may require a vapor retarder: (A) a project where outside winter temperatures below 40 degrees
F. are anticipated and where average winter interior relative humidity of 45% or greater is expected. (B) building usages with
high humidity interiors such as indoor swimming pools, textile manufacturing operations, food, paper or other wet-process
industrial plants. (C) Construction elements that may release moisture after the roof is installed, such as interior concrete,
masonry or plaster work and fuel burning heaters.
Thermal Spacer Disclaimer
The above thermal spacer chart is intended to be used as a general guideline only. Because of the various densities of insulation
currently available, the manufacturer cannot guarantee that this chart will be accurate in all situations. Further, the manufacturer
does not specifically require that the roofing contractor use thermal spacers with it’s SuperLok® roof system. However, please
review the following information:
• Although the manufacturer does not require a thermal spacer, the architect or building owner may.
• In certain environments, the compression of the fiberglass insulation, without a thermal spacer, may create a thermal break
which can cause condensation to form on the purlins/joists.
• On uninsulated buildings, eliminating the thermal spacer: (1) may cause “roof rumble” and (2) you may encounter problems
holding panel module.
• When a high clip is used without a thermal spacer: (1) you may encounter problems holding panel module and (2) foot traffic
on the panel ribs may result in bent clips.
• Using a low clip with too much insulation or too thick of a thermal spacer: (1) may cause “purlin read” (2) may cause difficulty
in properly installing the panel side laps, and (3) you may encounter problems holding panel module.
SUBJECT TO CHANGE WITHOUT NOTICE
SEE
www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-5
SuperLok®
ENGINEERING
UNDERWRITERS LABORATORIES APPROVAL
SuperLok®
Substrate
UL-2218
Impact
Resistance
UL-263
Fire Rating
UL-580
Rating
5'-0 ¹⁄₁₆"
Open Framing
Class 4
Class A
Class 90
N/A
5'-0 ¹⁄₄"
Open Framing
Class 4
Class A
Class 90
24 min.
**
5'-0 ¹⁄₄"
Open Framing
Class 4
Class A
Class 90
16"
24 min.
**
2'-6"
Composite System
Class 4
Class A
Class 90
437
16"
24 min.
**
5'-0"
Plywood
Class 4
Class A
Class 90
449
16"
24 min.
*
5'-0"
Open Framing
Class 4
Class A
Class 90
451
16"
24 min.
*
2'-0"
Composite System
Class 4
Class A
Class 90
452
16"
24 min.
*
2'-0"
Composite System
Class 4
Class A
Class 90
487
16"
24 min.
**
4'-0"
Composite System
Class 4
Class A
Class 90
Construction
Number
Panel
Width (In.)
Clip
Clip Type Spacing
Gauge
90
16"
24 min.
*
176
16"
24 min.
180
16"
238B
* Fixed or Floating (high or low)
** Fixed or Floating (high, low, or utility)
NOTES:
1. Tests procedures are in accordance with Underwriters Laboratories Standard UL-580 under “Tests For Uplift Resistance
of Roof Assemblies”.
2. A detailed installation method is available for each Construction Number above and can be found in the UL Roofing
Materials and Systems Directory. The panels must be installed in a certain manner to achieve the published results.
3. The panel qualifies for a Class A fire rating in compliance with Underwriters Laboratories Standard UL-263 when
installed over a non-combustible substrate. A Class C fire rating can be obtained over a combustible deck.
4. The panel system qualifies under the following Fire Resistance Design Numbers: P225, P227, P230, P237, P265, P268,
P508, P510, P512, P701, P711, P720, P722, P726, P731, P734, P801, P815, and P819.
Refer to the UL Fire Resistance Directory for specific construction methods and hourly ratings.
5. SuperLok® panels carry a Class 4 rating under UL-2218 “Test Standard For Impact Resistance”.
FACTORY MUTUAL APPROVAL
SuperLok®
Panel
Width
Gauge
Clip Type
Clip
Spacing
Hail Damage
Rating
ASTM E108
Fire Rating
FM Windstorm
Rating
16
24
Floating
4’-0”
Class 1-SH
Class A
Class 1-90
16
22
Floating
5’-0”
Class 1-SH
Class A
Class 1-105
16
22
Floating
4’-0”
Class 1-SH
Class A
Class 1-135
NOTES:
1. Tests procedures are in accordance with Factory Mutual Research Corportion (FMRC) Standard 4471.
2. A detailed test report is available for each product above. The panels must be installed in a specific manner to achieve
the published results. Contact MBCI for more information.
SuperLok® is a registered trademark of NCI Building Systems, L.P.
Galvalume® is a registered trademark of BIEC International, Inc.
Vise-Grip® is a registered trademark of American Tool Companies, Inc.
FLORIDA BUILDING CODE PRODUCT APPROVAL
Double-Lok® Roofing System details and engineering load tables have been examined by the State of Florida and comply with
the 2010 Florida Building Code Product Approval Number (FL#11819.4).
SL-6
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
ENGINEERING
SuperLok® Panel
12"
¹⁄₁₆"
2"
SECTION PROPERTIES
NEGATIVE BENDING
POSITIVE BENDING
PANEL
Fy
WEIGHT
Ixe
Sxe
Maxo
Ixe
Sxe
Maxo
GAUGE
(KSI)
(PSF)
(IN.4/FT.)
(IN.3/FT.)
(KIP-IN.)
(IN.4/FT.)
(IN.3/FT.)
(KIP-IN.)
24
50
1.47
0.0756
0.0711
2.1307
0.1667
0.1025
3.0693
22
50
1.83
0.1053
0.1027
3.0751
0.2231
0.1387
4.1551
NOTES:
1. All calculations for the properties of SuperLok panels are calculated in accordance with the 2012 edition of the North American
Specification For Design Of Cold-Formed Steel Structural Members.
2. Ixe is for deflection determination.
3. Sxe is for bending.
4. Maxo is allowable bending moment.
5. All values are for one foot of panel width.
The Engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommended
that the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed Steel
Structural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria for coldformed steel components. Along with the Specification, the designer should reference the most current building code applicable to the project
jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired, please
contact the manufacturer.
SUBJECT TO CHANGE WITHOUT NOTICE
SEE
www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-7
SuperLok®
ENGINEERING
SuperLok® Panel
12"
¹⁄₁₆"
2"
ALLOWABLE UNIFORM LOADS IN POUNDS PER SQUARE FOOT
24 Gauge (Fy = 50 KSI)
SPAN TYPE LOAD TYPE
SPAN IN FEET
2.5
3.0
3.5
4.0
4.5
5.0
5.5
SINGLE
LIVE
216.0
180.0
154.3
127.9
101.0
81.8
67.6
2-SPAN
LIVE
216.0
157.8
116.0
88.8
70.1
56.8
47.0
3-SPAN
LIVE
216.0
180.0
144.9
111.0
87.7
71.0
58.7
4-SPAN
LIVE
216.0
180.0
135.3
103.6
81.9
66.3
54.8
2.5
3.0
3.5
4.0
4.5
5.0
5.5
22 Gauge (Fy = 50 KSI)
SPAN TYPE LOAD TYPE
SPAN IN FEET
SINGLE
LIVE
313.0
260.8
223.6
173.1
136.8
110.8
91.6
2-SPAN
LIVE
313.0
227.8
167.4
128.1
101.2
82.0
67.8
3-SPAN
LIVE
313.0
260.8
209.2
160.2
126.5
102.5
84.7
4-SPAN
LIVE
313.0
260.8
195.3
149.5
118.2
95.7
79.1
NOTES:
1. THE ABOVE LOADS ARE NOT FOR USE WHEN DESIGNING PANELS TO RESIST WIND UPLIFT.
2. Strength calculations based on the 2012 AISI Standard “North American Specification for the Design of Cold-formed Steel
Structural Members.”
3. Allowable loads are applicable for uniform loading and spans without overhangs.
4. LIVE load capacities are for those loads that push the panel against its supports. The applicable limit states are flexure,
shear, combined shear and flexure, web crippling at end and interior supports, and a deflection limit of L/180 under strength-level loads.
5. Panel pullover and Screw pullout capacity must be checked separately using the screws employed for
each particular application when utilizing this load chart.
6. The use of any field seaming equipment or accessories including but not limited to clips, fasteners, and support plates
other than tha provided by the manufacturer may (eave, backup, rake, etc.) damage panels, void all warranties and will void all
engineering data.
7. This material is subject to change without notice. Please contact MBCI for the most current data.
The Engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is
recommended that the design professional have a copy of the most current version of the North American Specification for the Design of ColdFormed Steel Structural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design
criteria for cold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable
to the project jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is
desired, please contact the manufacturer.
SL-8
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
ENGINEERING
SuperLok® Panel
16"
¹⁄₁₆"
2"
SECTION PROPERTIES
NEGATIVE BENDING
POSITIVE BENDING
PANEL
Fy
WEIGHT
Ixe
Sxe
Maxo
Ixe
Sxe
Maxo
GAUGE
(KSI)
(PSF)
(IN.4/FT.)
(IN.3/FT.)
(KIP-IN.)
(IN.4/FT.)
(IN.3/FT.)
(KIP-IN.)
24
50
1.38
0.0574
0.0538
1.6096
0.1324
0.0779
2.3324
22
50
1.72
0.0794
0.0776
2.325
0.1779
0.1057
3.1654
NOTES:
1. All calculations for the properties of SuperLok panels are calculated in accordance with the 2012 edition of the North American
Specification For Design Of Cold-Formed Steel Structural Members.
2. Ixe is for deflection determination.
3. Sxe is for bending.
4. Maxo is allowable bending moment.
5. All values are for one foot of panel width.
The Engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is
recommended that the design professional have a copy of the most current version of the North American Specification for the Design of ColdFormed Steel Structural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design
criteria for cold-formed steel components. Along with the Specification, the designer should reference the most current building code applicable
to the project jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is
desired, please contact the manufacturer.
SUBJECT TO CHANGE WITHOUT NOTICE
SEE
www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-9
SuperLok®
ENGINEERING
SuperLok® Panel
16"
¹⁄₁₆"
2"
ALLOWABLE UNIFORM LOADS IN POUNDS PER SQUARE FOOT
24 Gauge (Fy = 50 KSI)
SPAN TYPE
LOAD TYPE
SPAN IN FEET
2.5
3.0
3.5
4.0
4.5
5.0
5.5
SINGLE
LIVE
162.0
135.0
115.7
97.2
76.8
62.2
51.4
2-SPAN
LIVE
162.0
119.2
87.6
67.1
53.0
42.9
35.5
3-SPAN
LIVE
162.0
135.0
109.5
83.8
66.2
53.7
44.3
4-SPAN
LIVE
162.0
135.0
102.2
78.3
61.8
50.1
41.4
22 Gauge (Fy = 50 KSI)
SPAN TYPE
LOAD TYPE
SINGLE
LIVE
SPAN IN FEET
2.5
3.0
3.5
4.0
4.5
5.0
5.5
233.4
194.5
166.7
131.9
104.2
84.4
69.8
2-SPAN
LIVE
233.4
172.2
126.5
96.9
76.5
62.0
51.2
3-SPAN
LIVE
233.4
194.5
158.2
121.1
95.7
77.5
64.0
4-SPAN
LIVE
233.4
194.5
147.7
113.1
89.3
72.4
59.8
NOTES:
1. THE ABOVE LOADS ARE NOT FOR USE WHEN DESIGNING PANELS TO RESIST WIND UPLIFT.
2. Strength calculations based on the 2012 AISI Standard “North American Specification for the Design of Cold-formed Steel
Structural Members.”
3. Allowable loads are applicable for uniform loading and spans without overhangs.
4. LIVE load capacities are for those loads that push the panel against its supports. The applicable limit states are flexure,
shear, combined shear and flexure, web crippling at end and interior supports, and a deflection limit of L/180 under strength-level loads.
5. Panel pullover and Screw pullout capacity must be checked separately using the screws employed for
each particular application when utilizing this load chart.
6. The use of any field seaming equipment or accessories including but not limited to clips, fasteners, and support plates
other than tha provided by the manufacturer may (eave, backup, rake, etc.) damage panels, void all warranties and will void all
engineering data.
7. This material is subject to change without notice. Please contact MBCI for the most current data.
The Engineering data contained herein is for the expressed use of customers and design professionals. Along with this data, it is recommended
that the design professional have a copy of the most current version of the North American Specification for the Design of Cold-Formed Steel
Structural Members published by the American Iron and Steel Institute to facilitate design. This Specification contains the design criteria for coldformed steel components. Along with the Specification, the designer should reference the most current building code applicable to the project
jobsite in order to determine environmental loads. If further information or guidance regarding cold-formed design practices is desired, please
contact the manufacturer.
SL-10
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
GENERAL INFORMATION
PRODUCT CHECKLIST
SuperLok® Panel
Back-Up Plate
16" or 12"
2"
• For use at ridge and
endlaps
• Prepunched
• 16 gauge red oxide
¹⁄₁₆"
12" R
16" R
Clip, Floating
• Low – For use
with or without ³⁄₈"
thermal spacer.
HW-230 R
R
HW-7766 R
12" Wide HW-7764
16" Wide
Rake Support
•
•
•
•
20'-0" length
14 gauge red oxide
Factory slots
For use with low or
high clip
• High – For use
with ³⁄₈", ⁵⁄₈" or 1"
thermal spacer.
HW-232 R
Clip, Fixed
• Low – For use
with or without ³⁄₈"
thermal spacer
HW-7712 - Low
HW-7722 - High
HW-236 R
Bearing Plate
Standard
R
R
• 16 gauge red
oxide
• For use with low
or utility systems
• For use with rigid
board insulation
• High – For use
with ³⁄₈", ⁵⁄₈" or 1"
thermal spacer
HW-234 R
SUBJECT TO CHANGE WITHOUT NOTICE
SEE
www.mbci.com FOR CURRENT INFORMATION
HW-7500 R
REV 00.01
SL-11
SuperLok®
GENERAL INFORMATION
PRODUCT CHECKLIST
Eave Plate, Low
• 8'-0" length
• 14 gauge
• Red Oxide
Eave Plate, High
HW-7600 R
Floating Eave Plate, Low
• 8'-0" length
• 14 gauge
• Red Oxide
HW-7616 R
Floating Eave Plate, High
• 14 gauge
• Red Oxide
Mid-Slope Fixed Plate, High
HW-7630 (10'-0" Long) R
HW-7631 (20'-0" Long) R
HW-7632 (6'-0" Long) R
SL-12
REV 00.01
• 8'-0" length
• 14 gauge
• Red Oxide
HW-7618 R
HW-7617 R
Mid-Slope Fixed Plate, Low
• 8'-0" length
• 14 gauge
• Red Oxide
SEE www.mbci.com FOR CURRENT INFORMATION
• 14 gauge
• Red Oxide
HW-7637 (6'-0" Long) R
HW-7638 (10'-0" Long) R
HW-7639 (20'-0" Long) R
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
GENERAL INFORMATION
PRODUCT CHECKLIST
Valley Support Plate – Low Systems
Extended Valley Support Plate – Low Systems
SPECIFY ANGLE
17"
14"
1"
1"
90°
90°
• Extended Width
• Standard Width
10'-0" Long P-106 R
• Use Over Purlins/Joists
Valley Support Plate - High Systems
Valley Support Plate – High Systems
SPECIFY ANGLE
12"
1⁷⁄₁₆"
SPECIFY ANGLE
135°
1"
10'-0" Long P-101 R
• Use Over Purlins/Joists
21"
1⁷⁄₁₆"
1"
135°
135°
135°
1⁹⁄₁₆"
1⁹⁄₁₆"
• Standard Width
10'-0" Long P-164 R
• Use Over Purlins/Joists
• Extended Width
• Use Over Purlins/Joists
Valley Support Plate – Low Systems
Valley Support Plate – Low Systems
• Standard Width
• Extended Width
10'-0" Long P-105 R
• Use Over Rigid Insulation
Hip Support Plate - High or Low Floating Systems
• Use Over Rigid Insulation
10'-0" Long P-162 R
10'-0" Long P-100 R
Hip Support Plate – Low Floating Systems
"
10¹¹⁄₁₆
1"
SPECIFY ANGLE
• Use Over Purlins/Joists
10'-0" Long P-141 R
Ridge/Hip Support Plate – Low Fixed Systems
• Use with all Substrates
SUBJECT TO CHANGE WITHOUT NOTICE
10'-0" Long P-145 R
• Use Over Solid Substrate
10'-0" Long P-140 R
Ridge/Hip Support Plate – High Fixed Systems
• Use with all Substrates
SEE www.mbci.com FOR CURRENT INFORMATION
10'-0" Long P-155 R
REV 00.01
SL-13
SuperLok®
GENERAL INFORMATION
PRODUCT CHECKLIST
• ³⁄₁₆" x 2 ¹⁄₂" x 20'
• For use at valley when
using exposed fasteners
• For use with roof curbs
Tape Sealer
• Polystyrene block
used to increase
the insulation
capacity along the
purlins
Thermal Spacer
Triple Bead
HW-502 R
• ³⁄₁₆" x ⁷⁄₈" x 25'
• For use at eave,
ridge, endlaps and
trim connections
HW-583 ³⁄₈" R
Tri-Bead
HW-582 ⁵⁄₈" R
HW-504 R
Tape Sealer-Swaged
HW-581
Panel Hemming Tool
1" R
Tube Sealant
Urethane (White) - HW-540 R
Urethane (Gray) - HW-541 R
Outside Closure
Urethane (Bronze) - HW-542 R
HW-602 R
HW-515 R
• 24 gauge
• Painted
Non-Skinning Butyl - HW-549 R
Light Transmitting Panel
(Reinforced) ‡
• Std. Insulated - HW- 1621S R
12" wide HW-446 R
16" wide HW-440 R
• Std. Uninsulated - HW-1620S R
• UL 90 Insulated - HW-1617S R
• UL 90 Uninsulated - HW-1616S R
‡ It is the user’s responsibility to ensure that the installation and use of all light transmitting panels comply with State, Federal and OSHA regulations and laws,
including, but not limited to, guarding all light transmitting panels with screens, fixed standard railings, or other acceptable safety controls that prevent fall-through.
SL-14
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
GENERAL INFORMATION
PRODUCT CHECKLIST
Ridge Flashing
• Includes Cinch Angles and
Flexible Membrane
• Specify Roof Slope
Floating Peak Box
"A"
2¹⁄₂"
COLOR
120°
FL-125 R
Length - 2'-1"
Girth - 33¹⁄₄"
• For use with FL-200, FL-202,
FL-213, FL-214, FL-300, FL-302,
FL-540 or FL-541 Ridge Flashing
120°
"
1¹⁄₄
PART
NO.
ROOF
PITCH
DIM.
“A”
FL-200
¹⁄₂-3³⁄₄:12
3¹⁄₂"
FL-202
3¹³⁄₁₆-6:12
4¹⁄₂"
FL-213
¹⁄₂-3³⁄₄:12
6¹⁄₂"
FL-214
3¹³⁄₁₆-6:12
7¹⁄₂"
Ridge Flashing for
Perforated Vent Drip
"A"
For use without ventilator
18" Peak purlin spacing
For use without ventilator
24" Peak purlin spacing
FL-126 R
Length - 2'-6"
Girth - 37¹⁄₄"
• For use with FL-205, FL-207,
FL-303, FL-304, FL-543 or FL-544
Ridge Flashing
R
R
R
R
Perforated
Vent Drip
COLOR
1 ¹⁄₄"
PERFORATED
• Use w ith FL-300,
FL-302, FL-303 or
FL-304 Ridge Flashing
"
¹⁄₂
"
2 ¹⁄₂
NOTE
1"
1"
1"
ROOF
PITCH
DIM.
“A”
NOTE
FL-300
¹⁄₂-3³⁄₄:12
4¹⁄₂"
FL-302
3¹³⁄₁₆-6:12
5¹⁄₂"
For use with perforated
vent drip (FL-254)
18" Peak purlin spacing
R
R
FL-303
¹⁄₂-3³⁄₄:12
7¹⁄₂"
FL-304
3¹³⁄₁₆-6:12
8¹⁄₂"
For use with perforated
vent drip (FL-254)
24" Peak purlin spacing
R
R
1"
PART
NO.
Ridge/Hip Flashing - Fixed
"A "
3¹⁄₄"
FL-254 R
24 Gauge Material
“Z” Closure
• Use at Hips
1"
"A"
COLOR
COLOR
1"
FL-361 R
24 Gauge Material
PART
NO.
ROOF
PITCH
DIM.
“A”
FL-209
¹⁄₂-3³⁄₄:12
6"
FL-211
3¹³⁄₁₆-6:12
7"
FL-212
All Pitches
11¹⁄₂"
• Specify open hem
when using with
continuous cleat
Sculptured High
Side Eave Trim
NOTE
5 ¹⁄₂"
For use without vent
material
18" Peak purlin spacing
For use without vent
material
24" Peak purlin spacing
R
R
R
4 ³⁄₄"
2"
4 ³⁄₄"
102°
102°
90° + ° of
ROOF SLOPE
1 ³⁄₄"
COLOR
Ridge End Cap
• Specify Ridge to be used
and Roof Slope
FL-201
SUBJECT TO CHANGE WITHOUT NOTICE
R
135°
"
⁵⁄₈
PART NO.
ROOF PITCH
DIM. A
FL-265
¹⁄₄-1³⁄₄:12
2"
FL-265B
1¹³⁄₁₆-4:12
3¹¹⁄₁₆"
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
R
R
SL-15
SuperLok®
GENERAL INFORMATION
PRODUCT CHECKLIST
Sculptured Gutter - Standard
¹⁄₂"
1"
90°
4 ³⁄₄"
• For use with
Sculptured Gutter
Gutter Strap
90°-° of
1" ROOF SLOPE
10"
102°
156°
DIM
"A"
COLOR
4 ³⁄₄"
102°
4 ¹⁄₂"
FL-246 R
18 Gauge Material
Gutter Ends
Left or Right
90°+° of
• Use with all Sculptured or Style
Gutters
• End Caps will be made to fit
gutter ordered
• Specify left or right
• Specify gutter part number
ROOF SLOPE
PART NO.
ROOF PITCH
DIM.“A”
GIRTH
FL-248A
¹⁄₂-4:12
7⁵⁄₁₆"
23³⁄₁₆"
FL-248B
4⁹⁄₁₆-6:12
7¹⁵⁄₁₆"
24⁷⁄₁₆"
R
R
FL-245 R
Variable Termination
Sculptured Rake Trim
COLOR
3 ⁵⁄₈ "
³⁄₄ "
4 ³⁄₄" 90°
156°
9"
³⁄₄"
102°
90°
4 ³⁄₄"
COLOR
90°
FL-117 R
Rake Slide - High Wind
¹⁄₂”
1³⁄₄ "
2"
135°
⁵⁄₈"
⁄₈”
⁷
FL-111 R
⁵⁄₈”
90°
Sculptured Eave Trim
³⁄₄”
COLOR
2"
156°
2 ¹⁄₂"
4 ³⁄₄"
Eave with Extended
Drip Edge
102°
2¹
⁄₂"
102°
90°-° of
ROOF SLOPE
1 ³⁄₄"
"
⁵⁄₈
COLOR
135°
Specify Roof Pitch
FL-215 R
24 Gauge Material
90°
¹⁄₂"
2 ⁵⁄₈"
FL-253 R
Box High Side
Eave Trim
• Use with Roof Slopes ¹⁄₂ - 6:12
• Specify open hem when using
with continuous cleat
1¹
⁄₂"
SPECIFY
ANGLE
⁵⁄₈
"
3"
COLOR
COLOR
10 ¹⁄₄
Box Eave Trim
"
3¹
⁄₂"
COLOR
5"
SPECIFY
ANGLE
SPECIFY
ANGLE
⁵⁄₈"
Specify Roof Pitch
SL-16
45°
REV 00.01
FL-331 R
SEE www.mbci.com FOR CURRENT INFORMATION
T-5151
R
• Specify open hem
when using with
continuous cleat
4"
⁵⁄₈
"
FL-326 R
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
GENERAL INFORMATION
PRODUCT CHECKLIST
Parapet Rake Cleat High Wind
Box Rake Trim
3"
COLOR
1"
³⁄₄"
5"
1"
"
⁵⁄₈
COLOR
³⁄₄"
FL-306 R
Box Gutter with Drip Edge
Gutter Strap
1 ¹⁄₂"
6"
F-292 R
• For use with Box Gutter
⁵⁄₈"
1"
2"
5 ¹⁄₂"
SPECIFY
ANGLE
4 ¹⁄₂"
10"
5 ¹⁄₄"
COLOR
T-5271 R
Specify Roof Pitch
Parapet High Side Eave
Flashing - Fixed
• Specify Roof Slope
6"
Gutter Ends
Left or Right
• Use with T-5271Box Gutter with
Drip Edge
• Specify left or right
COLOR
5 ¹⁄₂"
FL-276
R
T-5291 R
Parapet High Side Eave Flash Floating
Parapet Rake Flash
COLOR
4"
FL310 R
24 Gauge Material
"A"
COLOR
4 ³⁄₄"
OPEN
HEM
"A"
2 ¹⁄₂"
1"
PART NO.
1¹⁄₄"
DIM. A
FL-285
3"
FL-286
5"
FL-287
7"
R
R
R
PART NO.
DIM. A
FL-275
3¹⁄₂"
FL-274
4¹⁄₂"
R
R
NOTE: All trim to be 26 gauge material unless noted. Refer to current price book for part numbers and descriptions.
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-17
SuperLok®
GENERAL INFORMATION
PRODUCT CHECKLIST
Continous Cleat
Offset Cleat
1¹⁄₂"
¹⁄₂"
2¹⁄₂"
¹⁄₈"
1¹⁄₂"
135°
"
¹⁄₂
FL-337 R
24 Gauge Material
FL-338 R
24 Gauge Material
Alternate Counter Flash
Counter Flash
¹⁄₂"
"
⁵⁄₈
30°
90°
COLOR
1"
¹⁄₂"
1"
2¹⁄₂"
150°
⁵⁄₈"
³⁄₄"
COLOR
FL-341 R
24 Gauge Material
Box Panel Cap Trim
FL-343 R
24 Gauge Material
Offset Panel Cap
Trim
3¹⁄₂"
2 ¹⁄₂"
95°
SPECIFY
ANGLE
2"
4"
¹⁄₂"
Standard Valley - Utility, Low and High Systems
Extended Valley - Utility, Low and High Systems
SPECIFY ANGLE
2"
16 "
2"
11 ¹⁄₂"
REV 00.01
SPECIFY
ANGLE
¹⁄₂"
FL-271 R
SPECIFY ANGLE
SL-18
1¹⁄₈"
FL-272 R
Specify Roof Pitch
24 Gauge Material
1³⁄₈"
45°
45°
FL-705 R
24 Gauge Material
SEE www.mbci.com FOR CURRENT INFORMATION
FL-711 R
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
GENERAL INFORMATION
PRODUCT CHECKLIST
Fastener #1B
• Clip to purlin (Up to 4"
insulation between panel
and purlin)
Fastener #1E
• Panel to eave plate or
eave strut
• Rake trim to roof panel
• Standard endlaps
• Panel to valley plate
• Outside closure to panel
with back-up plate or
support plate
¹⁄₄"-14 x 1 ¹⁄₄" Long Life Self Driller
⁵⁄₁₆" Hex Washer Head, with sealing washer
Fastener #2A
¹⁄₄"-14 x 1 ¹⁄₄" Self Driller
⁵⁄₁₆" Hex Washer Head with no washer
Fastener #142
R
R
• Use in place of
Fasteners #1E, #2B and
#4 at all strip outs
• Clip to purlin (Over 4"
insulation between panel
and purlin)
17 x 1" Long Life AB
⁵⁄₁₆" Hex Washer Head, with sealing washer
Fastener #6A
¹⁄₄"-14 x 1 ¹⁄₂" Self Driller
⁵⁄₁₆” Hex Washer Head with no washer
Fastener #2B
R
• Clip to joist
R
• Endlap over plywood
12-24 x 1 ¹⁄₄" Tek® 5 Self Driller
⁵⁄₁₆" Hex Washer Head, with no washer
Fastener #4
¹⁄₄"-14 x 1" Long Life AB
³⁄₈" Hex Washer Head, with sealing washer
Fastener #5
• Rake support to purlin
(Floating System Only)
• Floating eave plate to
eave strut
¹⁄₄"-14 x 1 ¹⁄₄" Shoulder Tek® 2 Self Driller
⁵⁄₁₆" Hex Washer Head, with no washer
SUBJECT TO CHANGE WITHOUT NOTICE
R
R
R
• Ridge and other flashing
to outside closure
• Gutter to panel
• Gutter to strap
• Trim to trim connections
• Sculptured eave trim to
panel
¹⁄₄"-14 x ⁷⁄₈" Long Life Lap Tek® Self Driller
⁵⁄₁₆" Hex Washer Head, with sealing washer
Fastener #11
R
• Special application
fastener
• For attaching trim to
masonary walls
R
¹⁄₄" x 1 ¹⁄₄" Nail Drive Masonry Anchor
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-19
SuperLok®
GENERAL INFORMATION
PRODUCT CHECKLIST
Fastener #12A
• Rake angle to purlin
• Hip and valley support
plates to purlins
• Valley flashing to valley
support plate
R
12 x 1" #2 Phillips/Square Drive Pancake Head Driller
Fastener #14A
• Outside closure to angle
on floating hip detail
R
Stainless Steel Pop Rivet ¹⁄₈" diameter x ³⁄₈" grip range
Fastener #226
• Dekstrip to Expansion
Ridge/Expansion Lap
³⁄₁₆" x ⁹⁄₁₆" Rivet Cendalum
Closed End Rivet
Fastener #18
R
• Panel clips to wood deck
• Outside closure to panel
over wood deck
Fastener #13A
• Offset cleat to plywood
• Rake angle to plywood
12 x 1" #2 Phillips/Square Drive Pancake Type “A”
Fastener #14
• Trim to trim connections
Stainless Steel Pop Rivet ¹⁄₈" diameter x ³⁄₁₆" grip range
Fastener #1
Fastener #228
R
Deck Screw
Fastener #210 14 x 3"
10 x ¹⁄₂" Aluminum Grommet Washer
REV 00.01
R
• 18 Gauge maximum
drilling thickness
• Dekstrip to Expansion
Ridge/Expansion Lap
Fastener #209 14 x 2"
SL-20
R
• Panel endlaps over solid
substrate
¹⁄₄"-14 x ⁵⁄₈" Long Life
Type B with washer
14 x 1” Type A
⁵⁄₁₆" Hex Washer Head, with ⁵⁄₈" O.D. washer
R
• Eave plate to eave strut
• Mid-slope fixed plate to
purlin
• Rake support to angle
(Fixed system only)
¹⁄₄"-14 x 1" Self Driller
⁵⁄₁₆" Hex Head, with ⁵⁄₈" O.D. washer
Fastener #46
R
R
Fastener #211 14 x 4"
Fastener #15D 14 x 6"
SEE www.mbci.com FOR CURRENT INFORMATION
R
R
R
R
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
GENERAL INFORMATION
SuperLok®
Panel Orientation
INSTALLATION GUIDELINES
I.
Jobsite Storage and Handling
A. Check the shipment against the shipping list.
B. Damaged material must be noted on Bill of Lading.
C. Panel crates should be handled carefully. A spreader bar of appropriate length is recommended for
hoisting.
D. Check to see that moisture has not formed inside the bundles during shipment. If moisture is
present, panels should be uncrated and wiped dry, then restacked and loosely covered so that air
can circulate between the panels.
II. Application Checklist
A. Check substructure for proper alignment and uniformity to avoid panel distortion.
B. Periodic check of panel alignment is crucial to proper panel alignment.
C. If there is a conflict between this manual and the project erection drawings, the erection drawings
will take precedence.
III. LTP Warning
A. WARNING: Light transmitting panels are not designed or intended to bear the weight of any
person walking, stepping, standing or resting on them. THE MANUFACTURER DISCLAIMS
ANY WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, that any person can safely
walk, step, stand or rest on or near these light transmitting panels or that they comply with
any OSHA regulation.
LEFT TO RIGHT
RIGHT TO LEFT
SHEETING DIRECTION FOR
ROOFS WITHOUT PANEL
ENDLAPS
SUBJECT TO CHANGE WITHOUT NOTICE
RIGHT TO LEFT ONLY
SHEETING DIRECTION FOR
ROOFS WITH PANEL
ENDLAPS
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-21
SuperLok®
GENERAL INFORMATION
PREPARATORY REQUIREMENTS
1. For the purpose of this manual, we have assumed that the SuperLok® roof will be installed over purlins
and an eave gutter will be installed. Please refer to the Design Section of the manuals for details of
SuperLok® over other substrates.
2. A rake angle or an alternate structural flat surface must be installed on top of the purlins to accept the
rake support.
3. All primary and secondary framing must be erected, plumbed and squared with bolts tightened
according to accepted building practices.
4. The substructure (eave to ridge) must be on plane (¹⁄₄" in 20' or ³⁄₈" in 40' tolerance).
5. It is critical that the purlins or bar joists at the ridge and endlaps be located exactly as detailed and
that they are straight from rafter to rafter. Any mislocation or bowing of these members can cause the
fasteners at the ridge or endlaps to foul as the panels expand and contract.
6. The manufacturer recommends the use of a screw gun with a speed range of 0-2000 RPM to properly
install all fasteners referenced in this manual. Tools rated to 4000 RPM should never be used for self
drilling fasteners typically supplied with metal roof and wall systems.
7. Field cutting of the panels should be avoided where possible. If field cutting is required, the panels must
be cut with nibblers, snips, or shears to prevent edge rusting. Do not cut the panels with abrasive saw
blades, grinders, or torches.
CAUTION
Avoid restricting the thermal expansion and contraction of the SuperLok® panels.
(i.e., Do not attach panel to the substructure at either the eave and ridge.)
WARNING: Light transmitting panels are not designed or intended to bear the weight of any person walking, stepping,
standing or resting on them. THE MANUFACTURER DISCLAIMS ANY WARRANTY OR REPRESENTATION, EXPRESS
OR IMPLIED, that any person can safely walk, step, stand or rest on or near these light transmitting panels or that they
comply with any OSHA regulation.
NOTE
It is the responsibility of the erector to install this roof using safe construction practices that are in compliance with OSHA
regulations. The manufacturer is not responsible for the performance of this roof system if it is not installed in accordance
with the instructions shown in this manual. Deviations from these instructions and details must be approved in writing by the
manufacturer.
CAUTION
Diaphragm capabilities and purlin stability are not provided by the SuperLok® roof system.
Therefore, other bracing may be required.
SL-22
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
GENERAL INFORMATION
UNLOADING
Upon receiving material, check shipment
against shipping list for shortages and
damages. The manufacturer will not be
responsible for shortages or damages unless
they are noted on the shipping list.
Each bundle should be lifted at its center
of gravity. Where possible, bundles should
remain banded until final placement on roof.
If bundles must be opened, they should be
retied before lifting.
RIGHT WAY
When lifting bundles with a crane, a spreader
bar and nylon straps should be used. NEVER
USE WIRE ROPE SLINGS, THEY WILL
DAMAGE THE PANELS.
WRONG WAY
When lifting bundles with a forklift, forks
must be a minimum of five feet apart. Do
not transport open bundles. Drive slowly
when crossing rough terrain to prevent panel
buckling.
RIGHT WAY
CAUTION
WRONG WAY
SUBJECT TO CHANGE WITHOUT NOTICE
Improper unloading and handling of bundles
and crates may cause bodily injury or
material damage. The manufacturer is not
responsible for bodily injuries or material
damages during unloading and storage.
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-23
SuperLok®
GENERAL INFORMATION
UNLOADING
(Continued)
BLOCK AND BAND
This method of bundling is used for orders
that are to be picked up by the customer
or shipped by common carrier. 2 x 4’s are
strapped under the bundles to allow access
for straps or a forklift. Bundles less than
25' long may be handled by a forklift. The
forklift should have at least 5' between forks.
Bundles longer than 25' should be lifted
utilizing a spreader bar with nylon straps.
FULL CRATE
This method is used on all overseas shipments
or by customer’s order. Handling requirements
are the same as block and band.
SL-24
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
GENERAL INFORMATION
HANDLING/PANEL
STORAGE
Standing on one side of the panel, lift it by the
seam. If the panel is over 10' long, lift it with
two or more people on one side of the panel
to prevent buckling.
Do not pick panels up by the ends.
RIGHT WAY
NOTE:
Protective gloves and safety glasses should
always be used while handling panels.
OSHA safety regulations must be followed
at all times.
WRONG WAY
Store bundled sheets off the ground
sufficiently high to allow air circulation
beneath bundle and to prevent rising water
from entering bundle. Slightly elevate one end
of bundle. Prevent rain from entering bundle
by covering with tarpaulin, making provision
for air circulation between draped edges
of tarpaulin and the ground. PROLONGED
STORAGE OF SHEETS IN A BUNDLE IS
NOT RECOMMENDED. If conditions do not
permit immediate erection, extra care should
be taken to protect sheets from white rust or
water marks.
Check to see that moisture has not formed
inside the bundles during shipment. If moisture
is present, panels should be uncrated and
wiped dry, then restacked and loosely covered
so that air can circulate between the panels.
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-25
SuperLok®
GENERAL INFORMATION
PROPER HANDLING, STORAGE AND MAINTENANCE OF PAINTED
AND GALVALUME PLUS® PANELS
PANEL HANDLING
• All panel bundles must be inspected during unloading and carrier advised immediately if damage is noted.
• Never unload or move panel bundles that have been opened without adequately clamping them. Without the banding to
hold the bundle stable, panels may shift during unloading or movement, causing the bundle to fall.
• Never use wire slings to unload or move panel bundles.
• When unloading or moving panel bundles over 20' long, a spreader bar may be required. It is the erector’s responsibility to
determine the location and number of lift points required to safely unload or move panel bundles.
• When handling individual panels, always wear protective gloves. OSHA safety regulations must be followed at all times.
• When cutting panels, always wear all required safety equipment such as safety glasses and gloves. Cut panels with
nibblers, shears or snips. Do not use abrasive blade saws as these will melt the Galvalume® coating causing the panel to
edge rust which will void the Galvalume® and Paint warranties. Drilling fasteners into panels will create metal filings that
will rust and create an unsightly stain. Metal filings must removed by sweeping or wiping down panels immediately after
installation to avoid this occurrence.
PANEL STORAGE
• If water is permitted to enter panel bundles, it is necessary to open bundles, separate the panels and dry all surfaces.
• Store bundled panels off the ground sufficiently high to allow air circulation beneath bundle and to prevent rising water from
entering bundle. Slightly elevate one end of bundle.
• Prevent rain from entering bundle by covering with tarpaulin, making provision for air circulation between draped edges of
tarpaulin and the ground.
• Prolonged storage of panels in a bundle is not recommended. If conditions do not permit immediate erection, extra care
should be taken to protect panels from white rust or water marks. If panels have not been erected within three weeks of
receipt, the panels should be removed from the bundle for inspection. Condensation may cause damage to panels. The
manufacturer’s Paint and Galvalume® warranties do not cover damage caused by improper panel storage.
PANEL MAINTENANCE
• Never allow Galvalume® panels to come into contact with or water runoff from dissimilar materials such as copper, lead, or
graphite. These materials will cause galvanic corrosion of the panels and will void the Galvalume® warranty. This includes
treated wood and AC condensate, both of which contain copper compounds. This also applies to painted panels.
• Always use long life fasteners in all exposed fastener applications. Non long life fasteners can rust through the panel at
each exposed fastener location. Use of non long life fasteners in exposed applications will void the Galvalume® and Paint
warranties.
• Panels should be protected against exposure to masonry products, strong acids or bases and solvents. Exposure to these
agents may etch or stain Galvalume Plus® panels and cause painted panels to blister or peel.
• Never allow anyone to apply any coating or patching material to the panel surface. These products may contain chemicals
that will adversely affect the Galvalume Plus® or paint coating. Also, water may become trapped between the coating
material and the panel, causing premature corrosion.
If you have any question as to proper methods to use in the handling, storage or maintenance of these panels, call your
nearest manufacturer representative.
SL-26
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
GENERAL INFORMATION
• Never allow anyone to apply any coating or patching material to the panel surface. These products may
contain chemicals that will adversely affect the Galvalume Plus® or paint coating. Also, water may become
trapped between the coating material and the panel, causing premature corrosion.
If you have any question as to proper methods to use in the handling, storage or maintenance of these panels,
call your nearest manufacturer representative.
NOTICE
Uniform visual appearance of Galvalume Plus® coated panels cannot be guaranteed. The Galvalume Plus® coating is subject to
variances in spangle from coil to coil which may result in a noticeable shade variation in installed panels. The Galvalume Plus®
coating is also subject to differential weathering after panel installation. Panels may appear to be different shades due to this
weathering characteristic. If uniform visual appearance is required, the manufacturer recommends that our prepainted Signature®
200 or Signature® 300 panels be used in lieu of Galvalume Plus®. Shade variations in panels manufactured from Galvalume
Plus® coated material do not diminish the structural integrity of the product. These shade variations should be anticipated and
are not a cause for rejection.
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-27
SuperLok®
INSTALLATION SEQUENCE
STEEL LINE
RAKE ATTACHMENT
RAKE ANGLE
FASTENER #12A
WALL
PANEL
Attach the rake angle to the purlin with the
Fastener #12A.
Attach the rake support on top of the rake
angle with the proper self-drilling fasteners
(See “Rake Support Fastener Requirements”
Below) on 2'-0" centers with a fastener in the
first and last prepunched slot. The vertical leg
is to be installed flush with the steel line.
IT IS IMPORTANT THAT THE RAKE
SUPPORT IS INSTALLED STRAIGHT
AND SQUARE WITH THE EAVE AS IT
CONTROLS THE ALIGNMENT OF THE
ROOF SYSTEM.
PURLIN
Install 6" long pieces of double faced tape (not
by Manufacturer) on 3'-0" centers to the top of
the horizontal leg of the rake support. This will
help hold the insulation in place at the rake.
RAKE ANGLE ATTACHMENT
RAKE SUPPORT
FASTENER REQUIREMENTS
FLOATING SYSTEM
• Fixed System - Fastener #1
• Floating System - Fastener #5
FASTENER #5
RAKE SUPPORT
*DOUBLE FACED TAPE
FIXED SYSTEM
FASTENER #1
CAUTION
(For Floating Systems Only)
It is important that shoulder fasteners are
installed through the CENTER of the slotted
holes of the rake support to allow for
expansion and contraction.
RAKE SUPPORT ATTACHMENT
*Not by Manufacturer
SL-28
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
INSTALLATION SEQUENCE
WALL PANEL DEPTH
FASTENER #14
*DOUBLE FACED TAPE
LOW SYSTEM EAVE
BOX PANEL
CAP TRIM
FASTENER #14
EAVE STRUT
WALL PANEL
2" MAX.
WALL PANEL INSTALLED BEFORE ROOF
FASTENER #14
TRI-BEAD
TAPE SEALER
*DOUBLE FACED TAPE
For applications in which the wall panels have
already been erected, install box panel cap
trim or offset panel cap trim to the eave strut
with Fastener #14. Eave trim must be pulled
tight to wall panels with Fastener #14 before
fastening to eave strut. For applications
in which the wall panels have not been
erected, use offset panel cap trim. If using
panel cap trim, it will space itself for the wall
offset panels. Use three Fastener #14 per trim
piece.
Install Tri-Bead tape sealer along top of the
trim.
For vinyl insulation, install double faced tape
(not by Manufacturer) along the length of the
top leg of the trim. Double faced tape must be
upslope from Tri-Bead tape sealer.
OFFSET PANEL
CAP TRIM
FASTENER #14
EAVE STRUT
1¹⁄₄" MAX.
WALL PANEL INSTALLED
BEFORE OR AFTER ROOF
FLAT EAVE TRIM
FASTENER #14
OFFSET PANEL
CAP TRIM
FASTENER #4
1"
2" LAP
URETHANE
SEALANT
Lap trim 2". Apply two beads of urethane
sealant between the trim pieces, approximately
1" from the end of the bottom piece. Attach
trim laps in flat eave trim with Fastener
#14. Attach trim laps on panel cap trim with
Fastener #4.
BOX PANEL CAP
TRIM ENDLAP DETAIL
URETHANE
SEALANT
2" LAP
1"
OFFSET PANEL CAP
TRIM ENDLAP DETAIL
*Not by Manufacturer
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-29
SuperLok®
INSTALLATION SEQUENCE
HIGH EAVE PLATE
EAVE STRUT
FASTENER #1
HIGH SYSTEM EAVE
Wall Panels Installed Before Roof
FACE OF WALL
FASTENER #14
FASTENER #1
TRI-BEAD
TAPE SEALER
*DOUBLE
FACED TAPE
BOX PANEL
CAP TRIM
HIGH EAVE PLATE
FASTENER #14
WALL PANEL
2" MAX.
FLAT EAVE TRIM DETAIL
(WITHOUT GUTTER)
FASTENER #1
HIGH EAVE PLATE
*DOUBLE
FACED TAPE
TRI-BEAD
TAPE SEALER
OFFSET PANEL
CAP TRIM
FASTENER #14
TRI-BEAD
TAPE SEALER
EAVE STRUT
1¹⁄₄" MAX.
OFFSET PANEL CAP TRIM DETAIL
(WITH GUTTER)
FLAT EAVE TRIM
OFFSET
PANEL CAP
TRIM
FASTENER #14
Wall Panels Installed After Roof
Install offset panel cap trim to the eave strut and
wall panel with Fastener #14 at 10'-0" centers.
Use three fasteners per trim piece.
Install high eave plates flush with the outside
of the offset panel cap trim. Install Fastener # 1
in each prepunched slot (1'-0" on center) of the
eave plate. The first eave plate will butt against
the rake support. All of the eave plates may be
installed at this time
Lay Tri-Bead tape sealer under the eave plate on
top of the offset panel cap trim.
FASTENER #4
Be sure to butt each eave plate end to end
without leaving a gap between the plates. Place
an 8" length of Triple Bead tape sealer at each
butt joint.
1"
URETHANE
SEALANT
2" LAP
1"
2" LAP
URETHANE
SEALANT
BOX PANEL CAP
TRIM ENDLAP DETAIL
OFFSET PANEL CAP
TRIM ENDLAP DETAIL
*Not by Manufacturer
SL-30
Install high eave plates flush with the outside
face of the high crowns of the wall panels.
Install Fastener #1 in prepunched slots (1'-0" on
center) of the eave plate. The first eave plate
will butt against the rake support. All of the eave
plates may be installed at this time.
Be sure to butt each eave plate end to end
without leaving a gap between the plates. Place
an 8" length of Triple Bead tape sealer at each
butt joint.
Install box panel cap trim to the top of the
eave plates. Check to make sure the trim is
flat against the wall. Attach the trim to the eave
plate and the wall panel with a Fastener #14 at
10'-0" centers.
Lay Tri-Bead tape sealer across the top of the
eave trim, flush with the outside edge.
For vinyl back insulation, install double faced
tape (not by manufacturer) along the length of
the bottom of the eave plate. Double faced tape
must be upslope from the Tri-Bead tape sealer.
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
Lay Tri-Bead tape sealer across the top of the
eave plates, flush with the outside edge. For
vinyl back insulation, install double faced tape
(not by manufacturer) along the length of the
bottom leg of the eave plate.
Lap trim 2". Apply two beads of urethane sealant
between the trim pieces, approximately 1" from
the end of the bottom piece. Attach trim laps in
flat eave trim with Fastener #14. Attach trim laps
on panel cap trim with Fastener #4.
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
INSTALLATION SEQUENCE
THERMAL SPACER
THERMAL SPACER
(FOR HIGH SYSTEM
ONLY)
Position the thermal spacer on top of the
insulation over each purlin and against the
rake support prior to installing the roof panel.
*DOUBLE
FACED TAPE
OFFSET PANEL
CAP TRIM
INSULATION
THERMAL SPACER
*DOUBLE
FACED TAPE
6" LONG PIECES @ 3'-0"
RAKE SUPPORT
THERMAL SPACER
Using spray adhesive, (not by manufacturer), adhere the thermal spacer to the insulation (First Panel Run Only). The thermal
spacer increases the insulation capacity along
the purlins.
*SPRAY ADHESIVE
*Not by manufacturer
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-31
SuperLok®
INSTALLATION SEQUENCE
WALL PANEL
THICKNESS
*DOUBLE FACED TAPE
FIRST PANEL
2³⁄₄"
INSULATION
FASTENER #14
FASTENER #1E
OFFSET PANEL
CAP TRIM
TRI-BEAD TAPE SEALER
WALL PANEL
Position the panel so that it overhangs the
eave strut by the dimension shown on the
building drawings. The upper end of the panel
must extend 7" beyond the web of the purlin
if the panel covers eave to ridge. If more than
one panel is required to cover eave to ridge,
one or more endlaps will be required. The
upper end of the panel will extend 10" beyond
the web of the purlin at endlaps.
WALL PANEL
FASTENER
NOTE:
If an endlap is required then roof panel must
be sheeted right to left as viewed from the
eave looking toward the ridge.
Vise Grip® LOCKING
C-CLAMP
RAKE SUPPORT
SuperLok® PANEL
EAVE STRUT
RAKE ANGLE
WALL PANEL
FASTENER
FASTENER #12A
FASTENER #5
24" O.C.
2
1”
3
3 ¹⁄₂”
4
3 ¹⁄₂”
5
3 ¹⁄₂”
WALL PANEL
SuperLok® PANEL
1
3 ¹⁄₂”
Lay the female leg of the panel over the rake
support. To prevent wind damage, secure
the female leg of the panel to the rake
support with Vise Grip® Locking C-Clamps
or temporary fasteners. Fasteners must go
through the rake support. The panel will not
be fastened permanently to the rake support
until the rake trim is installed.
1”
RAKE SUPPORT
RAKE ANGLE
WALL PANEL
FASTENER
Attach the panel to the eave strut or eave
plate with Fastener #1E. Five fasteners are
required at this location.
WALL PANEL
EAVE STRUT
FASTENING PATTERN AT EAVE
*Not by Manufacturer
SL-32
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
INSTALLATION SEQUENCE
FACTORY APPLIED
MASTIC
SuperLok® PANEL
FACTORY APPLIED
MASTIC
LOW FIXED
CLIP
Hook the panel clip onto male leg of panel.
Hold end of clip up to keep it engaged onto
male leg and rotate the clip base down to
completely engage clip onto male leg. Install
panel clips at each purlin.
SuperLok® PANEL
PANEL CLIP
INSTALLATION
LOW FIXED
CLIP
SuperLok® PANEL
FASTENER #1B
(TWO PER CLIP)
LOW FIXED
CLIP
CLIP FASTENER REQUIREMENTS
SuperLok® PANEL
FASTENER #1B
(TWO PER CLIP)
WRONG WAY
Before fastening clip to purlins, check to
ensure that vertical leg of clip is tight to the
vertical leg of the panel. Failure to keep this
leg tight to the panel leg will affect panel
module.
PURLIN
RIGHT WAY
SUBJECT TO CHANGE WITHOUT NOTICE
CLIP INSTALLATION
Two fasteners per clip
Purlins - Fastener #1B - Up to 4" Insulation
Fastener #1F - Over 4" Insulation
Bar Joists - Fastener #6A
CAUTION
PURLIN
The panel clip has factory applied
mastic in the upper lip. This mastic is
compressed when the clip is rotated in
place. If, for some reason, a clip must be
removed, a new clip must be used.
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-33
SuperLok®
INSTALLATION SEQUENCE
PREPUNCHED
HOLES
UPPER SWAGED
SuperLok® PANEL
ENDLAP-PANEL
SWAGED ENDLAP
TAPE SEALER
NOTE:
Step 6 applies only where more than one
panel is used in a single slope.
BACK-UP PLATE
TEETH
LOWER SuperLok® PANEL
TRI-BEAD
TAPE SEALER
PANEL INSTALLATION SEQUENCE
UPPER SWAGED
SuperLok® PANEL
FASTENER #1E
Slide a prepunched back-up plate onto the
upslope end of the bottom panel. Make sure
the teeth on top of the back-up plate are on
top of the panel. Visually check to ensure that
the prepunched holes in the back-up plate
are aligned with the prepunched holes in the
panel. At upslope end of bottom panel, install
Tri-Bead tape sealer across entire width of
panel. Tape sealer must be centered over
prepunched holes in panel. Apply swaged
endlap tape sealer to swaged vertical male leg
of upper panel. Pigtail portion of tape sealer
must lap over vertical leg of panel.
TRI-BEAD
TAPE SEALER
BACK-UP
PLATE
LOW CLIP
LOWER SuperLok® PANEL
FASTENER #1B
Using an awl to align the prepunched holes,
install upper panel by nesting it over the
lower panel for 6". Rotate the male leg of the
upper panel under the male leg of the bottom
panel, then force the female leg of the upper
panel down onto the female leg of the bottom
panel. Install Fastener #1E in the prepunched
holes in the proper sequence. Install clips as
outlined in Step 5.
Repeat this endlap procedure as required until
ridge is reached.
FASTENER SEQUENCE
NOTE:
If you are using 12" SuperLok® panels,
they are not prepunched for endlaps. Use
Triple Bead Tape Sealant at endlaps with
12" wide panels.
SL-34
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
INSTALLATION SEQUENCE
RIDGE
BACK-UP PLATE
At the ridge, the panel should extend 7" past
the web of the peak purlin.
SuperLok® PANEL
FASTENER #1B
At the ridge install a back-up plate as outlined
in Step 6.
SuperLok® CLIP
PEAK PURLIN
Install clips as outlined in Step 5.
SuperLok® PANEL
RIDGE END OF PANEL
BACK-UP PLATE
SUPERLOK CLIP
PEAK PURLIN
PANEL END SEALANT DETAIL AT RIDGE
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-35
SuperLok®
INSTALLATION SEQUENCE
SUBSEQUENT RUNS
EAVE
SuperLok® PANEL
Apply urethane sealant to the male leg of
the first panel directly over the Tri-Bead tape
sealer at the eave. This will prevent water
infiltration through the end of the panel seam.
SuperLok® PANEL
RAKE SUPPORT
FASTENER #5
RAKE ANGLE
Position the next panel with the female leg
over the male leg of the previous panel with
panel ends flush.
FASTENER #1E
URETHANE
SEALANT
TRI-BEAD
TAPE SEALER
FASTENER #12A
PANEL END
SEALANT DETAIL
AT EAVE
EAVE STRUT
SuperLok® PANEL
Vise Grip®
LOCKING
C-CLAMP
Clamp the panel seam together at both
ends. Long panels may require one or
more clamps in the middle. This will help
hold panel module.
Install fasteners at eave as outlined in Step 4.
Install clips as outlined in Step 5.
Crimp panel seam at all clip locations with
hand crimping tool. Panels should be fully
seamed with electric seamer as quickly
as possible after a section of the roof is
completed.
CAUTION
Panel must be crimped at all clip locations
as they are installed to provide temporary
wind resistance.
SL-36
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
INSTALLATION SEQUENCE
SUBSEQUENT RUNS
ENDLAP
UPPER SWAGED
SuperLok® PANEL
Install endlap panels as outlined in Step 6.
SWAGED ENDLAP
TAPE SEALER
FASTENER #1E
(5) PER PANEL
BACK-UP PLATE
Install clips as described in Step 5.
TRI-BEAD
TAPE SEALER
LOWER
SuperLok® PANEL
PURLIN
Repeat endlap procedures as required until
ridge is reached.
FASTENER #1E
2
4
3
5
1
FASTENER SEQUENCE
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-37
SuperLok®
INSTALLATION SEQUENCE
SUBSEQUENT RUNS
RIDGE
Install back-up plate and clip as outlined in
Step 7.
SL-38
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
INSTALLATION SEQUENCE
8" TO 14"
SuperLok®
LOW FIXED CLIP
LOW RAKE SUPPORT
LAST PANEL RUN
Install rake support at the finishing end of the
roof as outlined in Step 1.
SuperLok® PANEL
RAKE ANGLE
FASTENER #5
24" O.C.
FASTENER #12A
FINISHING DIMENSION RUN OF
8" TO 14"
PANEL
FASTENER
Field cut and bend a 2" tall vertical leg on
the panels in the last run of roof. The vertical
leg must be tight to the rake support angle.
Secure the vertical leg to the rake support
angle with clamps or temporary fasteners. At
the endlap and ridge, a partial back-up plate
must be cut.
WALL PANEL
8" MAX
VARIABLE
TERMINATION TRIM
TRI-BEAD
TAPE SEALER
FASTENER #1E
24" O.C.
FASTENER #4
6" O.C.
FASTENER #5
24" O.C.
TRI-BEAD
TAPE SEALER
SuperLok® PANEL
RAKE ANGLE
PANEL
FASTENER
RAKE SLIDE
HIGH WIND
If the width of the last panel run is 8" or less,
a second run of rake support angle must be
installed for attachment of the vertical leg of
the panel. A variable termination trim will be
required to seal the gap between the vertical
leg of the panel and the rake trim.
RAKE ANGLE
FASTENER #12A
RAKE TRIM
FINISHING DIMENSION RUN OF
LESS THAN 8"
The male leg of the panel and the termination
trim must be field cut to fit the condition.
FASTENER #5
24" O.C.
TRIM FASTENER
CLOSURE
PURLIN
WALL PANEL
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-39
SuperLok®
INSTALLATION SEQUENCE
CRIMPING ARM
(Up Position)
LOCKING ARM
(Up Position)
SEAMING OPERATION
As panels are installed, hand crimp at each
clip location with the hand crimper. Panels
should be completely seamed with the electric
seamer as soon as possible.
CRIMPING ARM
(Up Position)
STEP 1
Hand Tool Positioned
Over Seam
LOCKING ARM
(Down Position)
Push locking arm down to lock crimper onto
seam. If difficulty is encountered, check to
make sure that the hand crimper is properly
alighned on seam. Do not force locking arm.
LOCKING ARM
(Down Position)
CRIMPING ARM
(Down Position)
STEP 2
Hand Tool Locked
Onto Seam
Push crimping arm down to crimp panel.
Return both the crimping arm and locking arm
to the up postion and remove tool from seam.
STEP 3
Hand Tool Crimps Seam
SL-40
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
INSTALLATION SEQUENCE
SEAMING OPERATION
(Continued)
HANDLE
FORMING
ARM
HANDLE
FORMING
ARM
GREASE
ZERK
FITTINGS
BEGINNING
PHASE 1 ACTION
HANDLE
CAUTION
To begin seaming with hand tool, set the hand tool
on the seam making sure seam is in the PHASE
1 Action slot. Align the edge of the hand tool with
the end of the panel. Rotate the forming arm under
the handle to produce 6" of PHASE 1 seam. This
should be done three times along the seam for a
total of 18".
FINISHED
PHASE 1 ACTION
HANDLE
FORMING
ARM
FORMING
ARM
BEGINNING
PHASE 2 ACTION
It is critical that the panel seams are crimped
and folded as shown before using the electric
seamer. Failure to follow these guidlines will
result in damaged seams.
FINISHED
PHASE 2 ACTION
Return to the end of the panel to begin PHASE
2 Action. Set hand tool onto seam making sure
seam is in the PHASE 2 Action slot. Align the
edge of the hand tool with the edge of the panel.
Rotate the forming arm under the handle to
produce 6" of finished PHASE 2 seam. This should
be done once per rib. The relationship of this 6"
of finished seam to the 18" of crimped seam is
critical to the proper alignment of the rolls in
the electric seamer.
HAND TOOL
STAGE 2
6”
HAND TOOL
STAGE 1
12”
NOTE
All grease zerk fittings on the hand tool should be
greased with lithium based grease daily.
The seam is now ready to accept the electric
seamer.
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-41
SuperLok®
INSTALLATION SEQUENCE
DIRECTION
OF ROOF
INSTALLATION
DIRECTION
OF ROOF
INSTALLATION
SEAMING OPERATION
(Continued)
The electric seamer will run in one direction only.
To determine the direction of the seamer, stand
at the eave and look upslope. If the roof is being
installed left to right, the seamer will run upslope.
If the roof is being installed right to left, the seamer
will run downslope, An orientation plate is on the
seamer to assist you in placing the seamer onto
the seam properly. When the roof has endlaps,
the panels will always be installed right to
left. When the roof slope is 6 on 12 or greater,
panels must run right to left.
To begin seaming, set seamer on seam with the
locking bar up and to the open side of the seam.
The rear wheels should be even with the edge
of the roof panel. Push the locking bar down to
engage the rolls and turn the seamer on.
Stop seamer about one foot from end of panels.
Disengage locking bar and remove the electric
seamer. Finish seam with hand tool.
CAUTION
• Seamer operation should be closely supervised
at all times.
• A safety line should be attached to the seamer.
• Do not entangle the electrical cords in the
seamer tooling while it is in operation. This
could cause serious injury or death to the
operator and severely damage the seamer.
• Electrical cords should be 10-gauge to provide
power to the seamer and never be over 200
feet from the electrical source.
SL-42
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
INSTALLATION SEQUENCE
OUTSIDE CLOSURE
INSTALLATION
Panels must be seamed before closures
can be installed. Install Tri-Bead tape sealer
across full width of panels, including under
panel seams at ridge. Center of tape sealer
should be 1 ¹⁄₂" from end of panels.
WN
DO PE
SLO
Field cut the end of the outside closure that
fits to the open side of the panel seam. Notch
and bend the vertical leg of the closure above
the end tab back to the dimple formed into
the closure. It is important that the closures fit
tight to the panel seams to prevent the need
for excess urethane sealant at this location.
WN
DO PE
SLO
URETHANE
SEALANT
(AS REQUIRED)
SUBSEQUENT
OUTSIDE CLOSURE
Install outside closures by rotating the end
cut for the panel seam into place first. Then
rotate the other end of the outside closure
into place. The vertical leg of the outside
closure should be 2" from the upslope end of
the panel. Attach the outside closure to the
panel with Fastener #1 at each prepunched
hole in the closure. Before installing the next
outside closure, install a piece of Tri-Bead
tape sealer onto the top flange of the outside
closure previously installed. This is to prevent
water being blown between the outside
closures where the top flanges overlap. After
all closures are in place, install Tri-Bead tape
sealer across the top flange.
FIRST OUTSIDE
CLOSURE
FASTENER #1
TRI-BEAD
TAPE SEALER
Use urethane sealant to fill any voids around
the panel seams on the upslope side of the
outside closures.
BACK-UP PLATE
FASTENER #1
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-43
SuperLok®
SPECIAL ERECTION TECHNIQUES
UL 90 LIGHT TRANSMITTING PANEL INSTALLATION
SuperLok®
LIGHT TRANSMITTING
PANEL
SEALANT (Factory Applied)
FASTENER #1E
(TWO EACH SIDE)
SuperLok®
LIGHT TRANSMITTING
PANEL
(Panels at this side of
light transmitting panel
reoved for clarity)
1. SuperLok® PANEL
2. SuperLok® LIGHT
TRANSMITTING PANEL
3. LIGHT TRANSMITTING PANEL
STIFFENER PLATE
4. BACK-UP PLATE
5. PURLIN
STIFFENER PLATE
[HW-7747]
NOTES:
1. Maximum width of purlin flange to be 3 ¹⁄₂".
2. Stiffener plate is to be field installed on bottom side of light transmitting panel over mid-purlin.
3. Light transmitting panel rivets that obstruct stiffener plate must be drilled out and replaced with Fastener #1E. Minimum
two fasteners per side.
4. Stiffener plate must be centered exactly over mid-purlin so that thermal movement of the system is not restrained by the
purlin.
5. Endlaps created by the use of light transmitting panels require roof erection to proceed from right to left as viewed from
the eave looking toward the ridge.
6. WARNING: It is the user’s responsibility to ensure that the installation and use of all light transmitting panels
comply with State, Federal and OSHA regulations and laws, including, but not limited to, guarding all light
transmitting panels with screens, fixed standard railings, or other acceptable safety controls that prevent
fall-through.
SL-44
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
SPECIAL ERECTION TECHNIQUES
ROOF CURB INSTALLATION INSTRUCTIONS
6
5
7
8
2
3
5
1
IN.
6"
12" M
IN.
18" M
When ordering curbs, specify one-piece curbs
as shown on this page.
6
4
1. SuperLok® Panel
2. Urethane Sealant
3. Outside Cap Cell
4. Back-up Plate
5. Fastener #1E
6. Tri-bead Tape Sealer
7. Roof Curb Made From Structural
Aluminum (Min. .080 Thickness)
8. Water Diverter
9. Panel Fins (to be cut from an extra
panel the length equal to length of the
curb).
9
1
7
3
8
5
MBCI recommends that only one-piece
.080 Aluminum (Min.) roof curbs be used
with the SuperLok® roof system. The roof
curb will be installed under the roof panels on
the upslope end and over the panels at the
downslope end. To accomplish this, the roof
panels must be endlapped at the upslope and
downslope end of the curb. This allows both
ends of the curb to shed water and places
the heavier gauge metal of the curb under the
roof panels for better resistance to foot traffic.
The exception is at the downslope end where
the curb is on top of the roof panels. Since
there are endlaps at this area, back-up plates
provide support.
Outside cap cells (for bottom) are used to seal
the panel to the roof curb. If the curb must be
located in a precise location, order the cap cells
loose for field installation.
ROOF SLOPE
NOTCH FEMALE LEG
OF LOWER PANEL
DIRECTION OF
PANEL INSTALLATION
SUBJECT TO CHANGE WITHOUT NOTICE
For the purpose of these instructions, a curb
with a factory attached cap cell is illustrated.
Panels are assumed to be blank and installed
right to left.
CAUTION
It is the user’s responsibility to ensure that openings
cut into the roof for installation of roof curbs comply
with State, Federal and OSHA regulations and laws,
including, but not limited to, guarding roof openings with
plywood, fixed standard railings, or other acceptable
safety controls that prevent fall-through.
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-45
SuperLok®
SPECIAL ERECTION TECHNIQUES
CURB INSTALLATION
FLOATING ROOF CURB SUPPORT GUIDE
SuperLok®
SuperLok®
SuperLok®
SuperLok®
CAUTION
It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and
OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other
acceptable safety controls that prevent fall-through.
SL-46
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
SPECIAL ERECTION TECHNIQUES
CURB INSTALLATION
CURB BASE INSTALLATION #1
NOTES:
1. Install all lower roof panels to support the curb base.
2. Install back up plates.
CAUTION
It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and
OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other
acceptable safety controls that prevent fall-through.
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-47
SuperLok®
SPECIAL ERECTION TECHNIQUES
CURB INSTALLATION
CURB BASE INSTALLATION #2
NOTES:
1. Apply Triple Bead tape sealer (HW-502) on roof panels as shown
CAUTION
It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and
OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other
acceptable safety controls that prevent fall-through.
SL-48
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
SPECIAL ERECTION TECHNIQUES
CURB INSTALLATION
CURB BASE INSTALLATION #3
NOTES:
1. For field located Panel Fin Caps, notch Curb Base at all panel Fins.
2. Install Curb Base on lower roof panels with a 3" End Lap.
CAUTION
It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and
OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other
acceptable safety controls that prevent fall-through.
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-49
SuperLok®
SPECIAL ERECTION TECHNIQUES
CURB INSTALLATION
CURB BASE INSTALLATION #4
NOTES:
1. Attach the Curb Base to the roof panels.
CAUTION
It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and
OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other
acceptable safety controls that prevent fall-through.
SL-50
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
SPECIAL ERECTION TECHNIQUES
CURB INSTALLATION
CAP CELL INSTALLATION
NOTES:
1. Fill Fin cavity of Cap Cell with Urethane Tube Sealant. Apply Triple Bead tape sealer (HW-502) on the bottom of (2)
loose the Cap Cell, install over the panel Fins and attach with (6) Fastener #1E.
CAUTION
It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and
OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other
acceptable safety controls that prevent fall-through.
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-51
SuperLok®
SPECIAL ERECTION TECHNIQUES
CURB INSTALLATION
CURB PANEL FIN PREPARATION
NOTES:
1. Field cut male and female panel ribs from an extra roof panel supplied by the building manufacturer.
CAUTION
It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and
OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other
acceptable safety controls that prevent fall-through.
SL-52
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
SPECIAL ERECTION TECHNIQUES
CURB INSTALLATION
FEMALE PANEL FIN INSTALLATION
NOTES:
1. Install Triple Bead tape sealer (HW-502) to panel #2 Male Fin, and along the edge of the Curb Base.
2. Install the Female Panel Rib over the tape sealer and attach with Fastener # 1E at 12" O.C.
CAUTION
It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and
OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other
acceptable safety controls that prevent fall-through.
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-53
SuperLok®
SPECIAL ERECTION TECHNIQUES
CURB INSTALLATION
MALE PANEL FIN INSTALLATION
NOTES:
1. Notch the male Panel Fin. Apply Triple Bead tape sealer (HW-502) to the top and side of the Male Panel Fin.
2. Apply Triple Bead tape sealer on the Curb Base under the male Panel Fin.
3. Insert the field cut male Panel Fin on top of the Triple Bead tape sealer.
CAUTION
It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and
OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other
acceptable safety controls that prevent fall-through.
SL-54
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
SPECIAL ERECTION TECHNIQUES
CURB INSTALLATION
CURB BASE INSTALLATION #5
CAUTION
It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and
OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other
acceptable safety controls that prevent fall-through.
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-55
SuperLok®
SPECIAL ERECTION TECHNIQUES
CURB INSTALLATION
CURB BASE INSTALLATION #6
NOTES:
1. Apply Triple Bead tape sealer (HW-502) on Curb Base at the up hill end.
CAUTION
It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and
OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other
acceptable safety controls that prevent fall-through.
SL-56
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
SPECIAL ERECTION TECHNIQUES
CURB INSTALLATION
CURB BASE INSTALLATION #7
NOTES:
1. Apply Triple Bead tape sealer (HW-502) between the Panel Fins on Panels #5 and #6 for water seal.
CAUTION
It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and
OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other
acceptable safety controls that prevent fall-through.
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-57
SuperLok®
SPECIAL ERECTION TECHNIQUES
CURB INSTALLATION
CURB BASE INSTALLATION #8
NOTES:
1. Install Roof Panels #5, #6, & #7 to the Curb Base on top of the tape sealer with Fastener #1E (5 per panel).
2. Install Roof Panel #8.
CAUTION
It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and
OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other
acceptable safety controls that prevent fall-through.
SL-58
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
SPECIAL ERECTION TECHNIQUES
CURB INSTALLATION
UPLIFT PLATE DETAIL
SuperLok® PANEL
®
CAUTION
It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and
OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other
acceptable safety controls that prevent fall-through.
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-59
SuperLok®
SPECIAL ERECTION TECHNIQUES
CURB INSTALLATION
UPLIFT PLATE FIELD NOTCH
CAUTION
It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and
OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other
acceptable safety controls that prevent fall-through.
SL-60
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
SPECIAL ERECTION TECHNIQUES
CURB INSTALLATION
DOWN SLOPE CURB BASE END LAP
SuperLok® PANEL
CAUTION
It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and
OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other
acceptable safety controls that prevent fall-through.
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-61
SuperLok®
SPECIAL ERECTION TECHNIQUES
CURB INSTALLATION
UP SLOPE CURB BASE END LAP
SuperLok® PANEL
HW-7617 HW-7618
®
CAUTION
It is the user’s responsibility to ensure that openings cut into the roof for installation of roof curbs comply with State, Federal and
OSHA regulations and laws, including, but not limited to, guarding roof openings with plywood, fixed standard railings, or other
acceptable safety controls that prevent fall-through.
SL-62
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
SPECIAL ERECTION TECHNIQUES
PIPE PENETRATION INSTALLATION
RECOMMENDED SMALL AND LARGE PIPE PENETRATION INSTALLATION
RIGHT WAY
WRONG WAY
RECOMMENDED SMALL PIPE PENETRATION INSTALLATION
INSTALL PIPE IN CENTER OF PANEL TO ALLOW BASE OF RUBBER ROOF JACK TO LAY FLAT
ON PANEL.
STAINLESS STEEL CLAMP
(NOT BY BUILDING
MANUFACTURER)
SuperLok® PANEL
PIPE CURB
RO
OF
SL
OP
E
PURLIN
SuperLok® PANEL
RECOMMENDED LARGE PIPE PENETRATION INSTALLATION
THIS METHOD TO BE USED IN ALL CASES WHERE A PIPE PENETRATION INTERSECTS A
PANEL RIB OR WHEN THE PIPE IS TOO LARGE AND WILL NOT ALLOW ADEQUATE WATER
FLOW DOWN THE PANEL.
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-63
SuperLok®
SPECIAL ERECTION TECHNIQUES
PIPE PENETRATION INSTALLATION
DECK-TIGHT INSTALLATION
DECK-TIGHT (NOT BY BUILDING
MANUFACTURER) ROLL TOP
OF DECK-TIGHT DOWN
STAINLESS STEEL CLAMP
(NOT BY BUILDING
MANUFACTURER)
¹⁄₄"-14 x ⁷⁄₈" LONG LIFE LAP TEK®
S.D. W/WASHER (FASTENER #4)
@ 1" O.C.
TRI-BEAD
TAPE SEALER
(HW-504)
APPLY TRI-BEAD TAPE SEALER
STAINLESS STEEL CLAMP
(NOT BY BUILDING
MANUFACTURER)
DECK-TIGHT
(NOT BY BUILDING
MANUFACTURER)
¹⁄₄"-14 x ⁷⁄₈" LONG LIFE LAP TEK
S.D. W/WASHER (FASTENER #4)
@ 1" O.C.
®
STEP 2
TRI-BEAD
TAPE SEALER
(HW-504)
TRI-BEADTAPE SEALER
(HW-504)
STAINLESS STEEL CLAMP
(NOT BY BUILDING
MANUFACTURER)
DECK-TIGHT (NOT BY BUILDING
MANUFACTURER)
¹⁄₄"-14 x ⁷⁄₈" LONG LIFE LAP TEK®
S.D. W/WASHER (FASTENER #4)
@ 1" O.C.
STEP 3
NOTE: ROLL DECK-TIGHT UP
OVER TRI-BEAD TAPE SEALER
AND SECURE CALMP AROUND
TOP OF DECK-TIGHT
SL-64
REV 00.01
TRI-BEAD
TAPE SEALER
(HW-504)
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
DETAILS
OPEN FRAMING
FIXED EAVE WITH SCULPTURED GUTTER
GUTTER STRAP (FL-246)
@ EVERY OTHER RIB
¹⁄₄" -14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4)
(2) PER STRAP
12”
1”
3⁵⁄₁₆”
3⁵⁄₁₆”
3⁵⁄₁₆”
1”
SuperLok® PANEL
2"
GUTTER STRAP ATTACHMENT
16”
SuperLok® PANEL
1”
URETHANE TUBE
SEALANT BETWEEN
PANEL RIBS
3¹⁄₂”
3¹⁄₂”
3¹⁄₂”
3¹⁄₂”
1”
2"
FASTENER SPACING @ EAVE
EAVE END
OF PANEL
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E)
EAVE SEALANT
URETHANE SEALANT MUST COME
IN CONTACT WITH TAPE SEALER
TO FORM A WEATHERTIGHT SEAL
2 ³⁄₄"
ANEL
WALL P SS
E
N
K
IC
H
T
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E)
(5) PER 16" PANEL (4) PER 12" PANEL
URETHANE TUBE SEALANT
BETWEEN PANEL RIBS
GUTTER STRAP (FL-246)
@ EVERY OTHER RIB
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4)
(2) PER STRAP
SuperLok® PANEL
LOW FIXED EAVE PLATE
(HW-7600)
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4)
@ 12" O.C.
¹⁄₄" -14 x 1" SELF-DRILLER
W/WASHER (FASTENER #1)
@ 12" O.C.
BOX PANEL CAP TRIM
(FL-272)
¹⁄₈" x ³⁄₈" POP RIVET
(FASTENER #14A)
@ 5'-0" O.C.
12 - 14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #3)
TRI-BEAD TAPE SEALER
(HW-504)
¹⁄₈" x ³⁄₁₆" POP RIVET
(FASTENER #14)
@ 3'-0" O.C.
SCULPTURED GUTTER
(FL-248A)
WALL PANEL
EAVE STRUT
BUILDING DIM.
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-65
SuperLok®
DETAILS
OPEN FRAMING
FIXED EAVE WITH SCULPTURED EAVE TRIM
12”
1”
3⁵⁄₁₆”
3⁵⁄₁₆”
3⁵⁄₁₆”
1”
2"
SuperLok® PANEL
URETHANE TUBE SEALANT
BETWEEN PANEL RIBS
16”
1”
3¹⁄₂”
3¹⁄₂”
3¹⁄₂”
3¹⁄₂”
1”
2"
EAVE END
OF PANEL
EAVE SEALANT DETAIL
FASTENER SPACING @ EAVE
URETHANE SEALANT MUST COME
IN CONTACT WITH TAPE SEALER
TO FORM A WEATHERTIGHT SEAL
W/
VARIES PE
O
L
S
F
ROO
ANEL
WALL P ESS
N
K
THIC
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E)
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E)
(5) PER 16" PANEL
(4) PER 12" PANEL
URETHANE TUBE SEALANT
BETWEEN PANEL RIBS
SuperLok® PANEL
³⁄₄"
LOW FIXED EAVE PLATE
(HW-7600)
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4)
@ 16" O.C.
BOX PANEL CAP TRIM
(FL-272)
12 - 14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #3)
¹⁄₄"-14 x 1" SELF-DRILLER
W/WASHER (FASTENER #1)
@ 12" O.C.
¹⁄₈" x ³⁄₈" POP RIVET
(FASTENER #14A)
@ 5'-0" O.C.
¹⁄₈" x ³⁄₁₆" POP RIVET
(FASTENER #14)
@ 3'-0" O.C.
TRI-BEAD TAPE SEALER
(HW-504)
SCULPTURED EAVE TRIM
(FL-253)
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4)
@ 12" O.C.
EAVE STRUT
OUTSIDE CLOSURE
WALL PANEL
SL-66
REV 00.01
BUILDING DIM.
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
DETAILS
OPEN FRAMING
FIXED EAVE WITH BOX EAVE TRIM
12”
1”
3⁵⁄₁₆”
3⁵⁄₁₆”
3⁵⁄₁₆”
1”
2"
SuperLok® PANEL
URETHANE TUBE SEALANT
BETWEEN PANEL RIBS
16”
1”
3¹⁄₂”
3¹⁄₂”
3¹⁄₂”
3¹⁄₂”
1”
2"
EAVE END
OF PANEL
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
EAVE SEALANT DETAIL
FASTENER SPACING @ EAVE SELF-DRILLER W/WASHER
(FASTENER #1E)
URETHANE SEALANT MUST COME
IN CONTACT WITH TAPE SEALER
TO FORM A WEATHERTIGHT SEAL
PANEL
WALL ESS
N
K
THIC
.
³⁄₄" O.H
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E)
(5) PER 16" PANEL
(4) PER 12" PANEL
URETHANE TUBE SEALANT
BETWEEN PANEL RIBS
LOW FIXED EAVE PLATE
(HW-7600)
SuperLok® PANEL
BOX EAVE TRIM (FL-326)
12-14 x 1¹⁄₄" LONG-LIFE
SELF DRILLER W/WASHER
(FASTENER #3)
¹⁄₄"-14 x 1" SELF-DRILLER
W/WASHER (FASTENER #1 @ 12" O.C.)
¹⁄₈" - ³⁄₁₆" POP RIVET
(FASTENER #14A) @ 5'-0" O.C.
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4)
@ 12" O.C.
TRI-BEAD TAPE SEALER
(HW-504)
OUTSIDE CLOSURE
WALL PANEL
EAVE STRUT
BUILDING DIM.
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-67
SuperLok®
DETAILS
OPEN FRAMING
FLOATING RIDGE
URETHANE TUBE SEALANT
@ CLOSURE ENDS/PANEL RIB
& LAPPING CLOSURE TABS
TO SEAL ALL VOIDS
TRI-BEAD TAPE
SEALER (HW-504)
OUTSIDE CLOSURE
(HW-440) @16" PANEL
(HW-446) @12" PANEL
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E) (1) PER RIB
RIDGE TRIM
(FL-213)
LOW FLOATING CLIP
(HW-230)
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4)
@ 6" O.C. (DO NOT INSTALL
THRU PANEL RIB)
SuperLok® PANEL
BACK-UP PLATE
(HW-7766) @ 16" PANEL
(HW-7764) @ 12" PANEL
¹⁄₄"-14 x 1¹⁄₄" SELF-DRILLER
W/O WASHER
(FASTENER #1B)
(2) PER CLIP
SL-68
REV 00.01
TRI-BEAD TAPE SEALER
(HW-504) CONT. ACROSS
PANEL
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E)
(4) PER 16" PANEL
(3) PER 12" PANEL
SEE www.mbci.com FOR CURRENT INFORMATION
ZEE PURLIN
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
DETAILS
OPEN FRAMING
FLOATING VENTED RIDGE
FLOATING VENTED
RIDGE FLASHING
12-14 x 1" SELF-DRILLER
W/WASHER (FASTENER #17)
(1) PER BIB
PERFORATED
VENT DRIP
(FL-254)
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAP TEK®
SELF-DRILLER W/WASHER
(FASTENER #4) @ 6" O.C.
¹⁄₈" x ³⁄₁₆" POP RIVET
(FASTENER #14) @ 6" O.C.
TRI-BEAD TAPE
SEALER (HW-504)
OUTSIDE CLOSURE
(HW-440) @ 16" PANEL
(HW-446) @ 12" PANEL
SuperLok® PANEL
LOW FLOATING
CLIP (HW-230)
SuperLok® PANEL
BACK-UP PLATE
(HW-7766) @ 16" PANEL
(HW-7764) @ 12" PANEL
¹⁄₄"-14 x 1¹⁄₄" SELF DRILLER
W/O WASHER (FASTENER #1B)
(2) PER CLIP
SUBJECT TO CHANGE WITHOUT NOTICE
TRI-BEAD TAPE SEALER
(HW-504)
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E)
(4) PER 16" PANEL
(3) PER 12" PANEL
SEE www.mbci.com FOR CURRENT INFORMATION
PURLIN
REV 00.01
SL-69
SuperLok®
DETAILS
OPEN FRAMING
FIXED VENTED EAVE
SuperLok® PANEL
¹⁄₂"
URETHANE
SEALANT
PANEL
WALL
NESS
K
IC
TH
¹⁄₄"-14 x 1¹⁄₄" LONG LIFE SELF-DRILLER
W/WASHER (FASTENER #1E)
(5) PER 16" PANEL
(4) PER 12" PANEL
LOW FLOATING
CLIP (HW-230)
SuperLok® PANEL
¹⁄₄" -14 x 1¹⁄₄" S.D.
W/O WASHER
(FASTENER #1B)
(2) PER CLIP
EAVE TRIM
CLOSURE
10-16 x 1" PANCAKE HD.
S.D. (FASTENER #12A)
@ 12" O.C.
TRI-BEAD TAPE SEALER
(HW-504)
¹⁄₈" x ³⁄₁₆" POP RIVET
(FASTENER #14)
@ 10" O.C.
FASCIA PANEL
SILL TRIM
¹⁄₈" x ³⁄₁₆" POP RIVET
(FASTENER #14)
@ 12" O.C.
EAVE STRUT
CANOPY STRUT
4"
MIN.
¹⁄₈" x ³⁄₁₆" POP RIVET
(FASTENER #14)
@ 12" O.C.
ANGLE TRIM
CAP TRIM
PERFORATED
ALUMINUM
SOFFIT PANEL
REV 00.01
¹⁄₄"-14 x 1⁷⁄₈" LAP TEK® S.D.
W/WASHER
(FASTENER #4A)
@ 12" O.C.
GIRT
¹⁄₄"-14 x 1¹⁄₄" LONG LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E) @ 12" O.C.
CROSS SECTION OF
VENTED EAVE
(OVERHANG MAXIMUM 2'-0")
SL-70
¹⁄₈" x ³⁄₁₆" POP RIVET
(FASTENER #14)
@ 12" O.C.
CLOSURE
WALL PANEL
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
DETAILS
OPEN FRAMING
SCULPTURED RAKE
TRI-BEAD TAPE SEALER
(HW-504)
¹⁄₄"-14 x 1¹⁄₄" LONG LIFE S.D.
W/WASHER (FASTENER #1E)
@ 24" O.C.
FIELD CUT & BEND UP 2” PANEL LEG
AS REQ’D WHEN ENDING OFF MODULE
12-14 X 1¹⁄₄" LONG-LIFE
SELF DRILLER W/WASHER
(FASTENER #3)
LOW RAKE SUPPORT
ANGLE (HW-7712)
LOW FLOATING
CLIP (HW-230)
SuperLok® PANEL
¹⁄₄"-14 x 1¹⁄₄" SHOULDER TEK® 2
SELF DRILLER (FASTENER #5)
@ 24" O.C. (CENTER IN SLOT)
SCULPTURED RAKE TRIM
(FL-111)
12-14 X 1" PANCAKE HEAD
SELF DRILLER (FASTENER #12A)
(1 PER CONN. @ EACH PURLIN)
¹⁄₄"-14 x 1¹⁄₄" SELF DRILLER
W/O WASHER (FASTENER #1B)
(2) PER CLIP
2 X 4 X 16 GA. ANGLE
HIGH WIND RAKE SLIDE
(F-215)
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4)
@ 12" O.C.
ZEE PURLIN
OUTSIDE CLOSURE
WALL PANEL
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-71
SuperLok®
DETAILS
OPEN FRAMING
SCULPTURED RAKE WITH CLEAT
¹⁄₄"-14 x 1⁷⁄₈" LONG LIFE LAPTEK
W/WASHER (FASTENER #4) @ 6" O.C.
TRI-BEAD TAPE SEALER
(HW-504)
¹⁄₄"-14 x 1¹⁄₄" LONG LIFE S.D.
W/WASHER (FASTENER #1E)
@ 24" O.C.
12-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #3)
HIGH WIND PARAPET RAKE
CLEAT (F-292)
FIELD CUT & BEND UP 2” PANEL LEG
AS REQ’D WHEN ENDING OFF
LOW FLOATING
MODULE
CLIP (HW-230)
LOW RAKE SUPPORT
SuperLok® PANEL
ANGLE (HW-7712)
¹⁄₄"-14 x 1¹⁄₄" SHOULDER TEK® 2
SELF DRILLER (FASTENER #5)
@ 24" O.C. (CENTER IN SLOT)
SCULPTURED RAKE TRIM
(FL-111)
12-14 X 1" PANCAKE HEAD
SELF-DRILLER (FASTENER #12A)
(1) PER CONN. @ EACH PURLIN
¹⁄₄"-14 x 1¹⁄₄" SELF DRILLER
W/O WASHER (FASTENER #1B)
(2) PER CLIP
2 X 4 X 16 GA. ANGLE
HIGH WIND RAKE SLIDE
(F-215)
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4)
@12" O.C.
ZEE PURLIN
OUTSIDE CLOSURE
WALL PANEL
SL-72
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
DETAILS
DETAILS
SuperLok®
OPEN FRAMING
PARAPET RAKE
BUILDING DIM.
URETHANE TUBE SEALANT
CONTINUOUS
FEILD SAWCUT
1¹⁄₂"
(MIN.)
14-10 x 2" DECK SCREW
(FASTENER #209) @ 24" O.C.
(PRE-DRILL HOLE)
COUNTERFLASH
(FL-341)
PARAPET RAKE TRIM
(FL-285)
TRI-BEAD TAPE SEALER
(HW-504) EA. SIDE OF
FLEXIBLE MEMBRANE
HIGH WIND PARAPET RAKE
CLEAT (F-292)
TRI-BEAD TAPE SEALER
(HW-504) EA. SIDE OF
FLEXIBLE MEMBRANE
¹⁄₄"-14 x 1¹⁄₄" LONG LIFE S.D.
W/WASHER (FASTENER #1E)
@ 24" O.C.
LOW FLOATING
CLIP (HW-230)
SuperLok® PANEL
FLEXIBLE MEMBRANE
LOW RAKE SUPPORT ANGLE
(HW-7712)
FIELD CUT & BEND UP 2"
PANEL LEG AS REQ’D WHEN
ENDING OFF MODULE
MASONRY WALL
(NOT BY MBCI)
¹⁄₄"-14 x 1¹⁄₄" SHOULDER TEK® 2
SELF DRILLER (FASTENER #5)
@ 24" O.C. (CENTER IN SLOT)
12-14 X 1" PANCAKE HEAD
SELF DRILLER (FASTENER #12A)
(1) PER CONN. @ EACH PURLIN
¹⁄₄"-14 x 1¹⁄₄" SELF DRILLER
W/O WASHER (FASTENER #1B)
(2) PER CLIP
2 X 4 X 16 GA. ANGLE
ZEE PURLIN
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-73
SuperLok®
DETAILS
OPEN FRAMING
FLOATING SCULPTURED HIGH SIDE EAVE
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4)
@ 6" O.C. (DO NOT INSTALL
THRU PANEL RIB)
URETHANE TUBE SEALANT
@ CLOSURE ENDS/PANEL RIB
& LAPPING CLOSURE TABS
TO SEAL ALL VOIDS
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E) (1) PER RIB
1"
2 x 2 x 16 GA. BACK UP ANGLE
SuperLok® PANEL
SCULPTURED HIGH SIDE EAVE
TRIM (FL-265)
TRI-BEAD TAPE SEALER (HW-504)
TOP & BOTTOM OF CLOSURE
³⁄₈"
2¹⁄₂"
OUTSIDE CLOSURE
(HW-440) @ 16" PANEL
(HW-446) @ 12" PANEL
ALTERNATE DETAIL
¹⁄₄"-14 x ⁷⁄₈" LONG LIFE-LAPTEK
W/WASHER (FASTENER #4) @ 6" O.C.
(DO NOT INTALL THRU PANEL RIB)
URETHANE TUBE SEALANT
@ CLOSURE ENDS/PANEL RIB
& LAPPING CLOSURE TABS TO
SEAL ALL VOIDS
2"
TRI-BEAD TAPE SEALER (HW-504)
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E)
(4) PER 16" PANEL
(3) PER 12" PANEL
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E) (1) PER RIB
OUTSIDE CLOSURE
(HW-440) @ 16" PANEL
(HW-446) @ 12" PANEL
TRI-BEAD TAPE SEALER (HW-504)
LOW FLOATING CLIP
(HW-230)
BACKUP PLATE
(HW-7766) @ 16" PANEL
(HW-7764) @ 12" PANEL
SuperLok® PANEL
2¹⁄₂"
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E)
(4) PER 16" PANEL
(3) PER 12" PANEL
¹⁄₄"-14 x 1¹⁄₄" SELF DRILLER
W/O WASHER (FASTENER #1B)
(2) PER CLIP
12-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #3)
SCULPTURED HIGH SIDE EAVE
TRIM (FL-265)
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4)
@ 12" O.C.
EAVE STRUT
OUTSIDE CLOSURE
WALL PANEL
BUILDING DIM.
SL-74
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
DETAILS
OPEN FRAMING
PARAPET FLOATING HIGH SIDE EAVE
MASONRY WALL
(NOT BY MBCI)
BUILDING DIM.
URETHANE TUBE SEALANT
CONTINUOUS
FIELD SAWCUT
COUNTER FLASH (FL341)
PARAPET HIGH EAVE TRIM
(FL-275)
TRI-BEAD TAPE SEALER
(HW-504) EA. SIDE OF
FLEXIBLE MEMBRANE
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4) @ 6" O.C.
(DO NOT INSTALL THRU PANEL RIB)
14-10 x 2" DECK SCREW
(FASTENER #209) @ 24" O.C.
(PRE-DRILL HOLE)
TRI-BEAD TAPE SEALER (HW-504)
@ TOP OF CLOSURE & TOP OF
FLEXIBLE MEMBRANE
FLEXIBLE MEMBRANE
OUTSIDE CLOSURE
(HW-440) @ 16" PANEL
(HW-446) @ 12" PANEL
URETHANE TUBE SEALANT
@ CLOSURE ENDS/PANEL RIB
& LAPPING CLOSURE TABS TO
SEAL ALL VOIDS
2"
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E) (1) PER RIB
LOW FLOATING CLIP (HW-230)
SuperLok®
PANEL
³⁄₈"
BACKUP PLATE
(HW-7766) @ 16" PANEL
(HW-7764) @ 12" PANEL
¹⁄₄"-14 x 1¹⁄₄" SELF DRILLER
W/O WASHER (FASTENER #1B)
(2 PER CLIP)
TRI-BEAD TAPE SEALER
(HW-504)
2"
7"
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E)
(4) PER 16" PANEL
(3) PER 12" PANEL
ZEE PURLIN
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-75
SuperLok®
DETAILS
OPEN FRAMING
FIXED VALLEY
SuperLok® PANEL
TRIPLE-BEAD TAPE SEALER
(HW-502)
URETHANE SEALANT
¹⁄₄"-14 x 1¹⁄₄" LONG LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E) @ 3" O.C.
(FASTENER MUST GO THROUGH
TAPE SEALER)
R
VA
VALLEY END
OF PANEL
IES
BEVELED EDGE
OF ROOF PANEL
PANEL RIB
URETHANE SEALANT MUST COME
IN CONTACT WITH TAPE SEALER
TO FORM A WEATHERTIGHT SEAL
DETAIL "A"
VALLEY TRIM
(FL-705)
TRIPLE-BEAD TAPE SEALER
(HW-502)
SuperLok®
PANEL
4¹⁄₂"
DETAIL "A"
2"
URETHANE TUBE SEALANT
BETWEEN PANEL RIBS
¹⁄₄"-14 x 1¹⁄₄" LONG LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E) @ 3" O.C.
(FASTENER MUST GO THROUGH
TAPE SEALER)
FIELD NOTCH PLATE @
PURLIN AS REQUIRED
ZEE PURLIN
12-14 X 1" PANCAKE HEAD
SELF DRILLER (FASTENER #12A)
@ 5'-0" O.C.
SL-76
REV 00.01
VALLEY SUPPORT PLATE
(P-106)
SEE www.mbci.com FOR CURRENT INFORMATION
12-14 X 1" PANCAKE HEAD
SELF-DRILLER (FASTENER #12A)
(2) PER CONN. @ EACH PURLIN
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
DETAILS
OPEN FRAMING
FLOATING HIP
URETHANE TUBE SEALANT
@ CLOSURE ENDS
TRI-BEAD TAPE SEALER
(HW-504)
¹⁄₄"-14 x 1¹⁄₄" SELF DRILLER
W/O WASHER (FASTENER #1B)
(2) PER CLIP
¹⁄₄"-14 x ⁷⁄₈" LONG LIFE LAPTEK
W/WASHER (FASTENER #4) @ 6" O.C.
(DO NOT INSTALL THRU PANEL RIB)
RIDGE/HIP TRIM
(FL-213)
ZEE CLOSURE (FL-361)
(FIELD CUT TO LENGTH &
BEVEL CUT TO FIT PANEL)
LOW FLOATING CLIP
(HW-230)
SuperLok® PANEL
2 x 2 x 16 GA. BACK-UP
ANGLE
TRI-BEAD TAPE SEALER (HW-504)
CONT. ACROSS PANEL
12-14 X 1" PANCAKE HEAD
SELF DRILLER
(FASTENER #12A)
(2) PER CONN.
@ EACH PURLIN
8 x ⁵⁄₈" NIBBED DRILLER
(FASTENER #24) @ 4" O.C.
HIP SUPPORT PLATE (P-141)
(FIELD NOTCH @ PURLINS)
ZEE PURLIN
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-77
SuperLok®
DETAILS
FIELD HEMMING PANEL END
SuperLok® PANEL
SuperLok® PANEL
SuperLok® PANEL
SL-78
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
DETAILS
WOOD DECK
FLOATING ENDLAP
SuperLok® PANEL
SuperLok®
PANEL (LOWER)
¹⁄₄" -14 x ⁵⁄₈" LONG-LIFE TYPE "B"
W/WASHER (FASTENER #46)
(5) PER 16" PANEL
(2) PER 12" PANEL
SuperLok® PANEL
BACK-UP PLATE
(HW-7766) 16" PANEL
(HW-7766) 12" PANEL
SuperLok® PANEL
(LOWER)
⁵⁄₈" PLYWOOD (MIN.)
(NOT BY MBCI)
2
3
4
1
MOISTURE BARRIER
(NOT BY MBCI)
¹⁄₄" -14 x ⁵⁄₈" LONG-LIFE TYPE "B"
W/WASHER (FASTENER #46)
(5) PER 16" PANEL
(2) PER 12" PANEL
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-79
SuperLok®
DETAILS
WOOD DECK
FLOATING EAVE WITH BOX GUTTER
SuperLok® PANEL
FIELD NOTCH PANEL
LEGS AND BEND PAN
TO FORM OPEN HEM
1¹⁄₂"
NON-SKINNING BUTYL
SEALANT (HW-549)
BETWEEN PANEL RIBS
1¹⁄₂"
EAVE END
OF PANEL
¹⁄₂"
1¹⁄₂"
EAVE SELANT DETAIL
BUTYL SEALANT MUST
COME IN CONTACT WITH
THE DRIP EDGE TO FORM A
WEATHERTIGHT SEAL
¹⁄₂"
1"
EAVE TRIM W/DRIP
EDGE (T-5271)
.
AX
1'-0" M
2"
PANEL
WALL
NESS
K
THIC
LOW FLOATING CLIP
(HW-230)
NON-SKINNING BUTYL
SEALANT (HW-549)
BETWEEN PANEL RIBS
SuperLok® PANEL
MOISTURE BARRIER
(NOT BY MBCI)
³⁄₈"
GUTTER STRAP (FL-310)
@ EVERY OTHER RIB
¹⁄₈" x ³⁄₁₆" POP RIVET
(FASTENER #14)
(2) PER STRAP
14-10 x 1" TYPE 'A'
SELF-TAPPER W/WASHER
(FASTENER #18)
(2) PER CLIP
⁵⁄₈" PLYWOOD (MIN.)
(NOT BY MBCI)
BOX GUTTER
W/DRIP EDGE
(T-5271)
12-11 x 1" PANCAKE HEAD
SELF-TAPPER (FASTENER #13A)
@ 12" O.C.
¹⁄₄"-14 x 1" LONG-LIFE
'TYPE AB' SELF-TAPPER
W/WASHER (FASTENER #2B)
³⁄₈" PLYWOOD SPACER
(NOT BY MBCI)
WOOD BLOCKING
(NOT BY MBCI)
WALL PANEL
BUILDING DIM.
NOTE: DO NOT USE THIS DETAIL ON ROOF SLOPES LESS THAN 3:12
SL-80
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
DETAILS
WOOD DECK
FLOATING EAVE WITH EAVE TRIM WITH EXTENDED DRIP EDGE
SuperLok® PANEL
FIELD NOTCH PANEL
LEGS AND BEND PAN
TO FORM OPEN HEM
1¹⁄₂"
NON-SKINNING BUTYL
SEALANT (HW-549)
BETWEEN PANEL RIBS
1¹⁄₂"
EAVE END
OF PANEL
¹⁄₂"
EAVE SELANT DETAIL
¹⁄₂"
1"
1¹⁄₂"
BUTYL SEALANT MUST
COME IN CONTACT WITH
THE DRIP EDGE TO FORM A
WEATHERTIGHT SEAL
EAVE TRIM W/DRIP
EDGE (T-5271)
.
AX
1'-0" M
2"
NON-SKINNING BUTYL
SEALANT (HW-549)
BETWEEN PANEL RIBS
PANEL
WALL
NESS
K
THIC
12 - 11 X 1
PANCAKE HEAD
SELF-TAPPER
(FASTENER #13A)
@ 12" O.C.
LOW FLOATING CLIP
(HW-230)
SuperLok® PANEL
MOISTURE BARRIER
(NOT BY MBCI)
³⁄₈"
EAVE TRIM W/DRIP EDGE
(T-5151)
⁵⁄₈" PLYWOOD (MIN.)
(NOT BY MBCI)
¹⁄₄ -14 x 1 LONG-LIFE
'TYPE AB' SELF-TAPPER
W/WASHER (FASTENER #2B)
14-10 x 1 TYPE 'A'
SELF-TAPPER W/WASHER
(FASTENER #18)
(2) PER CLIP
CONT. ³⁄₈" PLYWOOD SPACER
(NOT BY MBCI)
¹⁄₄ -14 x ⁷⁄₈ LONG-LIFE
LAPTEK W/WASHER
(FASTENER #4) @ 12" O.C.
12-11 x 1 PANCAKE HEAD
SELF-TAPPER (FASTENER #13A)
@ 12" O.C.
OUTSIDE CLOSURE
WALL PANEL
WOOD BLOCKING
(NOT BY MBCI)
BUILDING DIM.
NOTE: DO NOT USE THIS DETAIL ON ROOF SLOPES LESS THAN 3:12
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-81
SuperLok®
DETAILS
WOOD DECK
FIXED RIDGE
3"
TRI-BEAD TAPE SEALER
(HW-504)
RIDGE END
OF PANEL
RIDGE TRIM (FL-209)
2"
URETHANE TUBE SEALANT
@ CLOSURE ENDS/PANEL RIB
& LAPPING CLOSURE TABS TO
SEAL ALL VOIDS
2"
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E) (1) PER RIB
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4)
@ 6" O.C. (DO NOT INSTALL
THRU PANEL RIB)
TRI-BEAD TAPE SEALER
(HW-504)
OUTSIDE CLOSURE
(HW-440) @ 16" PANEL
(HW-446) @ 12" PANEL
®
SuperLok PANEL
³⁄₈"
³⁄₈" PLYWOOD SPACER
(NOT BY MBCI)
TRI-BEAD TAPE SEALER
(HW-504) CONT. ACROSS PANEL
14-10 x 1" TYPE 'A'
SELF-TAPPER W/WASHER
(FASTENER #18)
(4) PER 16" PANEL
(3) PER 12" PANEL
SL-82
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
MOISTURE BARRIER
(NOT BY MBCI)
⁵⁄₈" PLYWOOD (MIN.
(NOT BY MBCI)
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
DETAILS
WOOD DECK
FIXED VENTED RIDGE
3"
3”
LA
(M P
IN
.)
TRI-BEAD TAPE SEALER
(HW-504)
RIDGE END
OF PANEL
PERFORATED
VENT DRIP
(FL-254)
URETHANE TUBE SEALANT
@ CLOSURE ENDS/PANEL RIB
& LAPPING CLOSURE TABS TO
SEAL ALL VOIDS
PERFORATED VENT DRIP
(FL-254)
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E) (1) PER RIB
URETHANE SEALANT
(HW-504)
2"
2"
RIDGE TRIM
(FL-300)
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4)
@ 6" O.C. (DO NOT INSTALL
THRU PANEL RIB)
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4) @ 6" O.C.
TRI-BEAD TAPE SEALER
(HW-504)
OUTSIDE CLOSURE
(HW-440) @ 16" PANEL
(HW-446) @ 12" PANEL
®
SuperLok PANEL
TRI-BEAD TAPE SEALER
(HW-504) CONT. ACROSS PANEL
14 - 10 x 1" TYPE 'A'
SELF-TAPPER W/WASHER
(FASTENER #18)
(4) PER 16" PANEL
(3) PER 12" PANEL
MOISTURE BARRIER
(NOT BY MBCI)
⁵⁄₈" PLYWOOD (MIN.
(NOT BY MBCI)
³⁄₈" PLYWOOD SPACER
(NOT BY MBCI)
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-83
SuperLok®
DETAILS
WOOD DECK
BOX RAKE
BUILDING DIM.
1¹⁄₄"
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4)
@ 6" O.C.
HIGH WIND PARAPET RAKE
CLEAT (F-292)
TRI-BEAD TAPE SEALER
(HW-504)
LOW RAKE SUPPORT ANGLE
(HW-7712)
BOX RAKE TRIM
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF DRILLER W/WASHER
(FASTENER #1E) @ 24" O.C.
FIELD CUT & BEND UP 2" PANEL LEG
AS REQUIRED WHEN ENDING OFF MODULE
LOW FLOATING
CLIP (HW-230)
SuperLok® PANEL
2 x 4 x 16 GA. ANGLE
¹⁄₄"-14 x 1" LONG-LIFE
'TYPE AB' SELF-TAPPER
W/WASHER (FASTENER #2B)
¹⁄₈" x ³⁄₁₆" POP RIVET
(FASTENER #14)
@ 12" O.C.
CONTINUOUS CLEAT
(FL-338)
OUTSIDE CLOSURE
⁵⁄₈" PLYWOOD (MIN.)
(NOT BY MBCI)
12-11 x 1" PANCAKE HEAD
SELF-TAPPER (FASTENER #13A)
@ 24" O.C. (PRE-DRILL ANGLE)
¹⁄₄"-14 x 1¹⁄₄" SHOULDER TEK® 2
SELF-DRILLER (FASTENER #5)
@ 24" O.C. (CENTER IN SLOT)
14-10 x 1" TYPE 'A'
SELF-TAPPER W/WASHER
(FASTENER #18)
(2) PER CLIP
MOISTURE BARRIER
(NOT BY MBCI)
WOOD BLOCKING (NOT BY MBCI)
WALL PANEL
SL-84
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
DETAILS
WOOD DECK
PARAPET RAKE
BUILDING DIM.
URETHANE TUBE SEALANT
CONTINUOUS
FEILD SAWCUT
1¹⁄₂"
(MIN.)
PARAPET RAKE TRIM
(FL-285)
TRI-BEAD TAPE SEALER
(HW-504) EA. SIDE OF
FLEXIBLE MEMBRANE
HIGH WIND PARAPET RAKE
CLEAT (F-292)
TRI-BEAD TAPE SEALER
(HW-504) EA. SIDE OF
FLEXIBLE MEMBRANE
FLEXIBLE MEMBRANE
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E)
@ 24" O.C.
LOW FLOATING
CLIP (HW-230)
SuperLok® PANEL
³⁄₈"
14-10 x 2 DECK SCREW
(FASTENER #209) @ 24" O.C.
(PRE-DRILL HOLE)
COUNTERFLASH
(FL-341)
2 x 4 x 16 GAUGE ANGLE
LOW RAKE SUPPORT ANGLE
(HW-7712)
FIELD CUT & BEND UP 2"
PANEL LEG AS REQ’D WHEN
ENDING OFF MODULE
MASONRY WALL
(NOT BY MBCI)
⁵⁄₈" PLYWOOD (MIN.)
(NOT BY MBCI)
¹⁄₄"-14 x 1¹⁄₄" SHOULDER TEK® 2
SELF-DRILLER (FASTENER #5)
@ 24" O.C. (CENTER IN SLOT)
12-11 x 1" PANCAKE HEAD
SELF-TAPPER (FASTENER #13A)
@ 24" O.C. (PRE-DRILL ANGLE)
MOISTURE BARRIER
(NOT BY MBCI)
14-10 x 1" TYPE 'A'
SELF-TAPPER
W/WASHER
(FASTENER #18)
(2) PER CLIP
WOOD BLOCKING (NOT BY MBCI)
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-85
SuperLok®
DETAILS
WOOD DECK
FIXED BOX HIGH SIDE EAVE
7"
TRI-BEAD TAPE SEALER
(HW-504)
RIDGE END
OF PANEL
HIGH EAVE SEALANT DETAIL
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4) @ 6" O.C.
(DO NOT INSTALL THRU PANEL RIB)
TRI-BEAD TAPE SEALER
(HW-504)
2"
2"
URETHANE TUBE SEALANT
@ CLOSURE ENDS/PANEL RIB
& LAPPING CLOSURE TABS
TO SEAL ALL VOIDS
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF DRILLER W/WASHER
(FASTENER #1E) (1) PER RIB
14-10 x 1" TYPE 'A'
SELF-TAPPER W/WASHER
(FASTENER #18)
(4) PER 16" PANEL
(3) PER 12" PANEL
OUTSIDE CLOSURE
(HW-440) @ 16" PANEL
(HW-446) @ 12" PANEL
³⁄₈" PLYWOOD SPACER
(NOT BY MBCI)
TRI-BEAD TAPE SEALER
(HW-504)
SuperLok® PANEL
BOX HIGH SIDE EAVE TRIM
(FL-331)
³⁄₈"
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE
LAP TEK® W/WASHER
(FASTENER #4) @ 12" O.C.
MOISTURE BARRIER
(NOT BY MBCI)
OUTSIDE CLOSURE
¹⁄₄"-14 x 1" LONG-LIFE
'TYPE AB' SELF-TAPPER
W/WASHER
(FASTENER #2B)
⁵⁄₈" PLYWOOD (MIN.)
(NOT BY MBCI)
WOOD BLOCKING
(NOT BY MBCI)
WALL PANEL
BUILDING DIM.
SL-86
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
DETAILS
WOOD DECK
PARAPET FIXED HIGH SIDE EAVE
7"
TRI-BEAD TAPE SEALER
(HW-504)
HIGH EAVE END
OF PANEL
BUILDING DIM.
HIGH EAVE SEALANT DETAIL
MASONRY WALL
(NOT BY MBCI)
FIELD SAWCUT
TRI-BEAD TAPE SEALER
(HW-504) EA. SIDE OF
FLEXIBLE MEMBRANE
URETHANE TUBE SEALANT
CONTINUOUS
COUNTER FLASH (FL341)
14-10 x 2" DECK SCREW
(FASTENER #209) @ 24" O.C.
(PRE-DRILL HOLE)
PARAPET HIGH EAVE TRIM
(FL-276)
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4) @ 6" O.C.
(DO NOT INSTALL THRU PANEL RIB)
FLEXIBLE MEMBRANE
URETHANE TUBE SEALANT
@ CLOSURE ENDS/PANEL RIB
& LAPPING CLOSURE TABS TO
SEAL ALL VOIDS
TRI-BEAD TAPE SEALER (HW-504)
@ TOP OF CLOSURE & TOP OF
FLEXIBLE MEMBRANE
OUTSIDE CLOSURE
(HW-440) @ 16" PANEL
(HW-446) @ 12" PANEL
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E) (1) PER RIB
2"
TRI-BEAD TAPE SEALER
(HW-504)
SuperLok® PANEL
MOISTURE BARRIER
(NOT BY MBCI)
14-10 x 1" TYPE 'A'
SELF-TAPPER W/WASHER
(FASTENER #18)
(4) PER 16" PANEL
(3) PER 12" PANEL
⁵⁄₈" PLYWOOD (MIN.)
(NOT BY MBCI)
³⁄₈" PLYWOOD SPACER
(NOT BY MBCI)
SUBJECT TO CHANGE WITHOUT NOTICE
2"
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-87
SuperLok®
DETAILS
WOOD DECK
FLOATING VALLEY
SuperLok® PANEL
1 ¹⁄₂"
FIELD NOTCH PANEL
LEGS AND BEND PAN
TO FORM OPEN HEM
NON-SKINNING BUTYL
SEALANT (HW-549)
BETWEEN PANEL RIBS
1 ¹⁄₂"
VALLEY END
OF PANEL
¹⁄₂"
1"
¹⁄₂"
1 ¹⁄₂"
OFFSET CLEAT
(FL-337)
BUTYL SEALANT MUST COME IN
CONTACT WITH THE OFFSET CLEAT
TO FORM A WEATHERTIGHT SEAL
LOW FLOATING
CLIP (HW-230)
1'-0"
MAX
VALLEY TRIM
(FL-707)
.
12-11 x 1" PANCAKE HEAD
SELF-TAPPER (FASTENER #13A)
@ 12" O.C. (FASTENER MUST GO
THROUGH TAPE SEALER)
NON-SKINNING BUTYL
SEALANT (HW-549)
BETWEEN PANEL RIBS
TRI-BEAD TAPE
SEALER (HW-504)
SuperLok® PANEL
4 ¹⁄₂"
¹⁄₂"
2"
³⁄₈"
OFFSET CLEAT
(FL-337)
12-11 x 1" PANCAKE HEAD
SELF-TAPPER (FASTENER #13A)
@ 5'-0" O.C.
MOISTURE BARRIER
(NOT BY MBCI)
14-10 x 1" TYPE “A”
SELF-TAPPER W/WASHER
(FASTENER #18)
(2) PER CLIP
⁵⁄₈" PLYWOOD (MIN.)
(NOT BY MBCI)
NOTE: DO NOT USE THIS DETAIL ON ROOF SLOPES LESS THAN 3:12
SL-88
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
DETAILS
WOOD DECK
FIXED HIP
3"
TRI-BEAD TAPE SEALER
(HW-504)
HIP END
OF PANEL
RIDGE/HIP TRIM (FL-209)
2"
URETHANE TUBE SEALANT
@ CLOSURE ENDS
2"
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4)
@ 12" O.C.
TRI-BEAD TAPE SEALER
(HW-504)
ZEE CLOSURE (FL-361)
(FIELD CUT TO LENGTH &
BEVEL CUT TO FIT PANEL)
SuperLok® PANEL
³⁄₈"
14-10 x 1" TYPE “A”
SELF-TAPPER W/WASHER
(FASTENER #18) @ 6" O.C.
SUBJECT TO CHANGE WITHOUT NOTICE
³⁄₈" PLYWOOD SPACER
(NOT BY MBCI)
TRI-BEAD TAPE SEALER
(HW-504) CONTINUED
ACCROSS PANEL
SEE www.mbci.com FOR CURRENT INFORMATION
MOISTURE BARRIER
(NOT BY MBCI)
⁵⁄₈" PLYWOOD (MIN.)
(NOT BY MBCI)
REV 00.01
SL-89
SuperLok®
DETAILS
RIGID INSULATION OVER METAL DECK
FLOATING ENDLAP
UPPER SWAGED
SuperLok® PANEL
SWAGED ENDLAP
TAPE SEALER
(HW-515)
EW
VI
”
“A
SWAGED ENDLAP
TAPE SEALER
(HW-515)
PREPUNCHED HOLES
(16" PANEL ONLY)
VIEW “A”
¹⁄₄"-14 x ⁵⁄₈" LONG-LIFE
TYPE “B” W/WASHER
(FASTENER #46)
(5) PER 16" PANEL
(4) PER 12" PANEL
BACK-UP PLATE
(HW-7766) 16” PANEL
(HW-7764) 12” PANEL
TRI-BEAD TAPE SEALER
(HW-504) @ 16" PANEL
TRIPLE-BEAD TAPE SEALER
(HW-502) @ 12" PANEL
6"
LOWER
SuperLok® PANEL
1 ¹⁄₂"
TRI-BEAD TAPE SEALER
(HW-504) @ 16" PANEL
TRIPLE-BEAD TAPE SEALER
(HW-502) @12" PANEL
UPPER SWAGED
SuperLok® PANEL
LOW FLOATING CLIP
(HW-230)
BACK-UP PLATE
(HW-7766) 16” PANEL
(HW-7764) 12” PANEL
SuperLok® PANEL
(LOWER)
³⁄₈"
RIGID INSULATION
(NOT BY MBCI)
4 ¹⁄₂"
METAL DECK (MIN. 22 GA.)
(NOT BY MBCI)
10"
VAPOR BARRIER
(NOT BY MBCI)
12”
3
2
4
1
BEARING PLATE
(HW-7500)
DECK SCREW (2) PER CLIP
(MIN. ³⁄₄" PENETRATION
INTO METAL DECK)
¹⁄₄"-14 x ⁵⁄₈" LONG-LIFE
TYPE “B” SELF-TAPPER
W/WASHER (FASTENER #46)
(5) PER 16" PANEL
(4) PER 12" PANEL
16”
2
3
4
5
1
FASTENER INSTALLATION SEQUENCE
SL-90
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
DETAILS
RIGID INSULATION OVER METAL DECK
FLOATING EAVE WITH BOX GUTTER
FIELD NOTCH PANEL
LEGS AND BEND PAN
TO FORM OPEN HEM
1¹⁄₂"
SuperLok® PANEL
1¹⁄₂"
NON-SKINNING BUTYL
SEALANT (HW-549)
BETWEEN PANEL RIBS
1"
¹⁄₂"
EAVE END
OF PANEL
BOX GUTTER W/DRIP
EDGE (T-5271)
¹⁄₂"
1¹⁄₂"
PANEL ENGAGMENT DETAIL
BUTYL SEALANT MUST
COME IN CONTACT WITH
THE DRIP EDGE TO FORM A
WEATHERTIGHT SEAL
AX.
1'-0" M
PANEL
WALL
NESS
THICK
2"
LOW FLOATING CLIP
(HW-230)
DECK SCREW (2) PER CLIP
(MIN. ³⁄₄" PENETRATION
INTO METAL DECK)
¹⁄₂"
NON-SKINNING BUTYL
SEALANT (HW-549)
BETWEEN PANEL RIBS
12-14 x 1" PANCAKE HEAD
SELF-DRILLER
(FASTENER #12A)
@ 12" O.C.
GUTTER STRAP (FL-310)
@ EVER OTHER RIB
BEARING PLATE (HW-7500)
SuperLok® PANEL
³⁄₈"
¹⁄₈" x ³⁄₁₆" POP RIVET
(FASTENER #14)
(2) PER STRAP
RIGID INSULATION
(NOT BY MBCI)
BOX GUTTER
W/DRIP EDGE
(T-5271)
VAPOR BARRIER
(NOT BY MBCI)
12 x 24 x 1¹⁄₄" LONG-LIFE
TEK 4.5 W/WASHER
(FASTENER #78)
3" x 5" x 14 GA. BENT
PLATE (HOLD TOP
LEG ³⁄₈" ABOVE TOP
OF INSULATION)
METAL DECK
(NOT BY MBCI)
12 - 24 x 1¹⁄₂" PAN HEAD
TEK 4.5 SELF-DRILLER
(FASTENER #16) @ 12" O.C.
WALL PANEL
STRUCTURAL ANGLE
(NOT BY MBCI)
BUILDING DIM.
NOTE: DO NOT USE THIS DETAIL ON ROOF SLOPES LESS THAN 3:12
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-91
SuperLok®
DETAILS
RIGID INSULATION OVER METAL DECK
FLOATING EAVE WITH EAVE TRIM WITH EXTENDED DRIP EDGE
SuperLok® PANEL
FIELD NOTCH PANEL
LEGS AND BEND PAN
TO FORM OPEN HEM
1¹⁄₂"
NON-SKINNING BUTYL
SEALANT (HW-549)
BETWEEN PANEL RIBS
1¹⁄₂"
EAVE END
OF PANEL
¹⁄₂"
1"
¹⁄₂"
EAVE TRIM W/EXTENDED
DRIP EDGE (T-5151)
1¹⁄₂"
PANEL ENGAGMENT DETAIL
BUTYL SEALANT MUST
COME IN CONTACT WITH
THE DRIP EDGE TO FORM A
WEATHERTIGHT SEAL
AX.
1'-0" M
LOW FLOATING CLIP
(HW-230)
DECK SCREW (2) PER CLIP
(MIN. ³⁄₄" PENETRATION
INTO METAL DECK)
2"
¹⁄₂"
NON-SKINNING BUTYL
SEALANT (HW-549)
BETWEEN PANEL RIBS
12-14 x 1" PANCAKE HEAD
SELF-DRILLER
(FASTENER #12A)
@ 12" O.C.
EAVE TRIM W/DRIP EDGE
(T-5151)
BEARING PLATE (HW-7500)
SuperLok® PANEL
³⁄₈"
12 - 24 x 1¹⁄₄" LONG-LIFE
TEK 4.5 W/WASHER
(FASTENER #78)
RIGID INSULATION
(NOT BY MBCI)
VAPOR BARRIER
(NOT BY MBCI)
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE
LAPTEK W/WASHER
(FASTENER #4) @ 12" O.C.
3" x 5" x 14 GA. BENT
PLATE (HOLD TOP OF
PLATE ³⁄₈" ABOVE TOP
OF RIGID INSULATION)
OUTSIDE CLOSURE
METAL DECK
(NOT BY MBCI)
12-24 x 1¹⁄₂" PAN HEAD
TEK 4.5 SELF-DRILLER
(FASTENER #16) @ 12" O.C.
WALL PANEL
STRUCTURAL ANGLE
(NOT BY MBCI)
BUILDING DIM.
NOTE: DO NOT USE THIS DETAIL ON ROOF SLOPES LESS THAN 3:12
SL-92
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
DETAILS
RIGID INSULATION OVER METAL DECK
FIXED RIDGE
3"
TRI-BEAD TAPE SEALER
(HW-504)
RIDGE END
OF PANEL
RIDGE TRIM (FL-209)
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E) (1) PER RIB
2"
URETHANE TUBE SEALANT
@ CLOSURE ENDS/PANEL RIB
& LAPPING CLOSURE TABS TO
SEAL ALL VOIDS
2"
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4)
@ 6” O.C. (DO NOT INSTALL
THRU PANEL RIB)
TRI-BEAD TAPE SEALER
(HW-504)
RIDGE/HIP SUPPORT PLATE
(P-145)
SuperLok® PANEL
OUTSIDE CLOSURE
(HW-440) @ 16" PANEL
(HW-446) @ 12" PANEL
³⁄₈"
DECK SCREW
@ 12" O.C.(MIN. ³⁄₄" PENETRATION
INTO METAL DECK)
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E)
(4) PER 16" PANEL
(3) PER 12" PANEL
RIGID INSULATION
(NOT BY MBCI)
TRI-BEAD TAPE SEALER
(HW-504)
VAPOR BARRIER
(NOT BY MBCI)
METAL DECK
(NOT BY MBCI)
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-93
SuperLok®
DETAILS
RIGID INSULATION OVER METAL DECK
FIXED VENTED RIDGE
3"
URETHANE SEALANT
(HW-504)
1"
LA
(M P
IN
.)
TRI-BEAD TAPE SEALER
(HW-504)
RIDGE END
OF PANEL
PERFORATED
VENT DRIP
(FL-254)
URETHANE TUBE SEALANT
@ CLOSURE ENDS/PANEL RIB
& LAPPING CLOSURE TABS TO
SEAL ALL VOIDS
PERFORATED VENT DRIP
(FL-254)
2"
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E) (1) PER RIB
2"
RIDGE TRIM
(FL-303)
TRI-BEAD TAPE SEALER
(HW-504)
¹⁄₄"-14 x ⁷⁄₈" LONG LIFE LAPTEK
W/WASHER (FASTENER #4)
@ 6” O.C. (DO NOT INSTALL
THRU PANEL RIB)
¹⁄₄"-14 x ⁷⁄₈" LONG LIFE LAPTEK
W/WASHER (FASTENER #4)
@ 6” O.C.
OUTSIDE CLOSURE
(HW-440) @ 16" PANEL
(HW-446) @ 12" PANEL
®
SuperLok PANEL
³⁄₈"
1"
MIN.
TRI-BEAD TAPE
SEALER (HW-7631)
DECK SCREW @ 12" O.C.
(MIN. ³⁄₄" PENETRATION
INTO METAL DECK)
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E)
(4) PER 16" PANEL
(3) PER 12" PANEL
LOW MID-SLOPE FIXED PLATE
(HW-7631)
SL-94
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
RIGID INSULATION
(NOT BY MBCI)
VAPOR BARRIER
(NOT BY MBCI)
METAL DECK
(NOT BY MBCI)
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
DETAILS
RIGID INSULATION OVER METAL DECK
BOX RAKE
BUILDING DIM.
1¹⁄₄"
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4)
@ 6" O.C.
TRI-BEAD TAPE SEALER
(HW-504)
BOX RAKE TRIM
LOW RAKE SUPPORT
ANGLE (HW-7712)
12 - 24 x 1¹⁄₄" PAN HEAD
TEK 4.5 SELF-DRILLER
(FASTENER #16) @ 12" O.C.
HIGH WIND PARAPET RAKE
CLEAT (F-292)
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E) @ 24" O.C.
FIELD CUT & BEND UP 2"
PANEL LEG AS REQUIRED
WHEN ENDING OFF MODULE
LOW FLOATING
CLIP (HW-230)
BEARING PLATE
(HW-7500)
SuperLok® PANEL
³⁄₈"
12 - 24 x 1¹⁄₄" LONG-LIFE
TEK 4.5 W/WASHER
(FASTENER #78)
CONTINUOUS CLEAT
(FL-338)
¹⁄₈" x ³⁄₁₆" POP RIVET
(FASTENER #14)
@ 12" O.C.
OUTSIDE CLOSURE
2 x 4 x 16 GA. ANGLE
WALL PANEL
¹⁄₄ -14 x 1¹⁄₄ SHOULDER TEK® 2
SELF-DRILLER (FASTENER #5)
@ 24" O.C (CENTER IN SLOT)
STRUCTURAL ANGLE
(NOT BY MBCI)
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
RIGID INSULATION
(NOT BY MBCI)
VAPOR BARRIER
(NOT BY MBCI)
DECK SCREW (2) PER
CLIP (MIN. ³⁄₄" PENETRATION
INTO METAL DECK)
METAL DECK
(NOT BY MBCI)
REV 00.01
SL-95
SuperLok®
DETAILS
RIGID INSULATION OVER METAL DECK
PARAPET RAKE
URETHANE TUBE SEALANT
CONTINUOUS
14-10 x 2" DECK SCREW
(FASTENER #209) @ 24" O.C.
(PRE-DRILL HOLE)
1¹⁄₂"
(MIN.)
COUNTERFLASH
(FL-341)
PARAPET RAKE TRIM
(FL-285)
TRI-BEAD TAPE SEALER
(HW-504) EA. SIDE OF
FLEXIBLE MEMBRANE
HIGH WIND PARAPET RAKE
CLEAT (F-292)
TRI-BEAD TAPE SEALER
(HW-504) EA. SIDE OF
FLEXIBLE MEMBRANE
FLEXIBLE MEMBRANE
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E)
@ 24" O.C.
LOW FLOATING
CLIP (HW-230)
DECK SCREW @ (2) PER CLIP
(MIN. ³⁄₄" PENETRATION
INTO METAL DECK)
BEARING PLATE
(HW-7500)
SuperLok® PANEL
³⁄₈"
FEILD SAWCUT
LOW RAKE SUPPORT ANGLE
(HW-7712)
FIELD CUT & BEND UP 2"
PANEL LEG AS REQ’D WHEN
ENDING OFF MODULE
BEARING PLATE
(HW-7500) @ 24" O.C.
¹⁄₄"-14 x 1¹⁄₄" SHOULDER TEK® 2
SELF-DRILLER (FASTENER #5)
@ 24" O.C
VAPOR BARRIER
(NOT BY MBCI)
DECK SCREW @ 24" O.C.
(MIN. ³⁄₄" PENETRATION
INTO METAL DECK)
STRUCTURAL ANGLE
(NOT BY MBCI)
SL-96
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
RIGID INSULATION
(NOT BY MBCI)
METAL DECK
(NOT BY MBCI)
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
DETAILS
RIGID INSULATION OVER METAL DECK
FIXED BOX HIGH SIDE EAVE
7"
TRI-BEAD TAPE SEALER
(HW-504)
HIGH EAVE END
OF PANEL
HIGH EAVE SEALANT DETAIL
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4) @ 6" O.C.
(DO NOT INSTALL THRU PANEL RIB)
TRI-BEAD TAPE SEALER
(HW-504)
LOW FIXED EAVE PLATE
(HW-7600)
DECK SCREW @ 12" O.C.
(MIN. ³⁄₄" PENETRATION
INTO METAL DECK)
2"
2"
URETHANE TUBE SEALANT
@ CLOSURE ENDS/PANEL RIB
& LAPPING CLOSURE TABS
TO SEAL ALL VOIDS
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF DRILLER W/WASHER
(FASTENER #1E) (1) PER RIB
OUTSIDE CLOSURE
(HW-440) @ 16" PANEL
(HW-446) @ 12" PANEL
TRI-BEAD TAPE SEALER
(HW-504)
BOX HIGH SIDE EAVE TRIM
(FL-331)
SuperLok® PANEL
³⁄₈"
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4)
@ 12" O.C.
OUTSIDE CLOSURE
RIGID INSULATION
(NOT BY MBCI)
VAPOR BARRIER
(NOT BY MBCI)
METAL DECK
(NOT BY MBCI)
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E)
(4) PER 16" PANEL
(3) PER 12" PANEL
12-24 x 1¹⁄₄" LONG-LIFE
TEK 4.5 W/WASHER
(FASTENER #78)
WALL PANEL
STURCTURAL ANGLE
(NOT BY MBCI)
BUILDING DIM.
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-97
SuperLok®
DETAILS
RIGID INSULATION OVER METAL DECK
PARAPET FIXED HIGH SIDE EAVE
7"
TRI-BEAD TAPE SEALER
(HW-504)
RIDGE END
OF PANEL
HIGH EAVE SEALANT DETAIL
MASONRY WALL
(NOT BY MBCI)
URETHANE TUBE SEALANT
CONTINUOUS
COUNTER FLASH (FL-341)
PARAPET HIGH EAVE TRIM
(FL-276)
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4) @ 6" O.C.
(DO NOT INSTALL THRU PANEL RIB)
TRI-BEAD TAPE SEALER
(HW-504) EA. SIDE OF
FLEXIBLE MEMBRANE
14 -10 x 2" DECK SCREW
(FASTENER #209) @ 24" O.C.
(PRE-DRILL HOLE)
TRI-BEAD TAPE SEALER (HW-504)
@ TOP OF CLOSURE & TOP OF
FLEXIBLE MEMBRANE
LOW MID-SLOPE FIXED PLATE
(HW-7631)
FIELD SAWCUT
FLEXIBLE MEMBRANE
2"
URETHANE TUBE SEALANT
@ CLOSURE ENDS/PANEL RIB
& LAPPING CLOSURE TABS TO
SEAL ALL VOIDS
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E) (1) PER RIB
SuperLok® PANEL
OUTSIDE CLOSURE
(HW-440) @ 16" PANEL
(HW-446) @ 12" PANEL
³⁄₈"
TRI-BEAD TAPE SEALER
(HW-504)
RIGID INSULATION
(NOT BY MBCI)
VAPOR BARRIER
(NOT BY MBCI)
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E)
(4) PER 16" PANEL
(3) PER 12" PANEL
DECK SCREW @ 12" O.C.
(MIN. ³⁄₄" PENETRATION
INTO METAL DECK)
METAL DECK
(NOT BY MBCI)
SL-98
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
DETAILS
RIGID INSULATION OVER METAL DECK
FLOATING VALLEY
SuperLok® PANEL
1 ¹⁄₂"
FIELD NOTCH PANEL
LEGS AND BEND PAN
TO FORM OPEN HEM
NON-SINNING BUTYL
SEALANT (HW-549)
BETWEEN PANEL RIBS
1 ¹⁄₂"
VALLEY END
OF PANEL
¹⁄₂"
1"
¹⁄₂"
1 ¹⁄₂"
OFFSET CLEAT
(FL-337)
BUTYL SEALANT MUST
COME IN CONTACT WITH THE
OFFSET CLEAT TO FORM A
WEATHERTIGHT SEAL
VALLEY TRIM
(FL-707)
LOW FLOATING
CLIP (HW-230)
NON-SINNING BUTYL
SEALANT (HW-549)
BETWEEN PANEL RIBS
4 ¹⁄₂"
1'-0" M
AX.
OFFSET CLEAT
(FL-337)
TRI-BEAD TAPE SEALER
(HW-504)
¹⁄₂"
SuperLok® PANEL
2"
³⁄₈"
BEARING PLATE
(HW-7500)
12-14 X 1" PANCAKE HEAD
SELF-DRILLER (FASTENER #12A)
@ 12" O.C. (FASTENER MUST GO
THROUGH TAPE SEALER)
DECK SCREW @ 12" O.C.
(MIN. ³⁄₄" PENETRATION
INTO METAL DECK)
VALLEY SUPPORT
PLATE (P-105)
DECK SCREW (2) PER CLIP
(MIN. ³⁄₄" PENETRATION
INTO METAL DECK)
RIGID INSULATION
(NOT BY MBCI)
VAPOR BARRIER
(NOT BY MBCI)
METAL DECK
(NOT BY MBCI)
NOTE: DO NOT USE THIS DETAIL ON ROOF SLOPES LESS THAN 3:12
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-99
SuperLok®
DETAILS
RIGID INSULATION OVER METAL DECK
FIXED HIP
3"
TRI-BEAD TAPE SEALER
(HW-504)
HIP END
OF PANEL
RIDGE/HIP TRIM (FL-209)
2"
URETHANE TUBE SEALANT
@ CLOSURE ENDS (¹⁄₄" BEAD MIN.)
2"
¹⁄₄"-14 x ⁷⁄₈" LONG-LIFE LAPTEK
W/WASHER (FASTENER #4) @ 6" O.C.
(DO NOT INSTALL THRU PANEL RIB)
TRI-BEAD TAPE SEALER
(HW-504)
ZEE CLOSURE (FL-361)
(FIELD CUT TO LENGTH &
BEVEL CUT TO FIT PANEL)
SuperLok® PANEL
³⁄₈"
¹⁄₄"-14 x 1¹⁄₄" LONG-LIFE
SELF-DRILLER W/WASHER
(FASTENER #1E) @ 6" O.C.
DECK SCREW @ 12" O.C.
(MIN. ³⁄₄" PENETRATION
INTO METAL DECK)
TRI-BEAD TAPE SEALER
(HW-504) CONTINUED
ACROSS PANEL
RIGID/HIP SUPPORT PLATE
(P-145)
SL-100
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
RIGID INSULATION
(NOT BY MBCI)
VAPOR BARRIER
(NOT BY MBCI)
METAL DECK
(NOT BY MBCI)
SUBJECT TO CHANGE WITHOUT NOTICE
SuperLok®
NOTES
SUBJECT TO CHANGE WITHOUT NOTICE
SEE www.mbci.com FOR CURRENT INFORMATION
REV 00.01
SL-101
SuperLok®
NOTES
SL-102
REV 00.01
SEE www.mbci.com FOR CURRENT INFORMATION
SUBJECT TO CHANGE WITHOUT NOTICE
For the most current information available, visit our Web site at www.mbci.com
Houston, TX
14031 West Hardy
P.O. Box 38217
Houston, TX 77238
281-407-6915
Adel, GA
1601 Rogers Road
P.O. Box 1107
Adel, GA 31620
888-514-6062
Atlanta, GA
2280 Monier Avenue
P.O. Box 44729
Atlanta, GA 30336
678-337-1619
Atwater, CA
550 Industry Way
P.O. Box 793
Atwater, CA 95301
209-445-3891
Ennis TX
1804 Jack McKay Blvd.
P.O. Box 1210
Ennis, TX 75120
469-256-8255
Indianapolis, IN
1780 McCall Drive
P.O. Box 657
Shelbyville, IN 46176
317-364-4329
Lubbock, TX
5711 East FM-40
P.O. Box 10133
Lubbock, TX 79408
806-224-2724
Memphis, TN
300 Highway 51 North
P.O. Box 366
Hernando, MS 38632
662-298-2337
Oklahoma City, OK
7000 S. Eastern Avenue
P.O. Box 95998
Oklahoma City, OK 73149
405-492-6968
Omaha, NE
1011 Ellison Avenue
Omaha, NE 68110
402-983-8006
Phoenix, AZ
660 South 91st Avenue
P.O. Box 739
Tolleson, AZ 85353
480-630-3022
Rome, NY
6168 State Route 233
P.O. Box 4141
Rome, NY 13442
315-371-4330
Salt Lake City, UT
1155 West 2300 North
P.O. Box 16027
Salt Lake City, UT 84116
385-715-2952
San Antonio, TX
8677 I-10 East
P.O. Box 69
Converse, TX 78109
210-888-9768
September 15, 2016 / Rev 00.01