AIR DEVICE TAG, TYPE "A", BALANCE FOR 100 CFM, 6"
ROUND NECK
BDD
BACK DRAFT DAMPER
ABBREVIATION
DESCRIPTION
ABBREVIATION
---
1000 BTUH/HR
MBH
BDD
ABOVE
CEILING
A/C
ABOVE FINISHED FLOOR
AFF
HVAC GENERAL NOTES
DUCT SMOKE DETECTORS:
1.
ALL MECHANICAL EQUIPMENT AND INSTALLATIONS SHALL CONFORM WITH THE REQUIREMENTS OF THE 2009 INTERNATIONAL
MECHANICAL CODE, THE 2009 INTERNATIONAL BUILDING CODE, THE 2009 INTERNATIONAL ENERGY CONSERVATION CODE,
STATE AND LOCAL AMENDMENTS, NFPA 90A, 101, UNDERWRITERS LABORATORIES (OR ETL) AND ALL APPLICABLE LOCAL
CODES AND ORDINANCES.
1.
ALL FANS SUPPLYING MORE THAN 2000 CFM OF AIR TO ANY SPACE SHALL BE INSTALLED WITH A SMOKE DETECTOR IN THE
RETURN DUCTWORK. DUCT SMOKE DETECTORS SHALL BE INSTALLED IN THE RETURN AIR PATH OF AIR DISTRIBUTION
SYSTEMS UTILIZING A COMMON SUPPLY AND/OR RETURN AIR PLENUM WITH A COMBINED DESIGN CAPACITY GREATER THAN
2000 CFM.
2.
THE LOCATIONS, ARRANGEMENT AND EXTENT OF EQUIPMENT, PIPING, SUPPORTS, DEVICES, CONDUIT, AND OTHER
APPURTENANCES RELATED TO THE INSTALLATION OF THE MECHANICAL AND ELECTRICAL WORK SHOWN ARE APPROXIMATE.
THE DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE THE DRAWINGS, BUT REFER TO THE ARCHITECTURAL DRAWINGS FOR
EXACT DIMENSIONS OF BUILDING COMPONENTS. SHOULD A CONFLICT EXIST BETWEEN THE ARCHITECTURAL AND
ENGINEERING DRAWINGS REGARDING DIMENSIONS, SCALE, ETC., NOTIFY THE ARCHITECT IMMEDIATELY.
2.
THE SMOKE DETECTOR SHALL BE WIRED TO STOP THE FAN UPON DETECTION OF SMOKE, AND SIGNAL THE BUILDING FIRE
ALARM CONTROL PANEL. THE SMOKE DETECTOR SHALL BE FURNISHED BY THE ELECTRICAL CONTRACTOR, MOUNTED IN THE
DUCT BY THE MECHANICAL CONTRACTOR, AND WIRED BY THE ELECTRICAL CONTRACTOR.
3.
MATERIALS, EQUIPMENT OR LABOR NOT INDICATED, BUT WHICH CAN BE REASONABLY INFERRED TO BE NECESSARY FOR A
COMPLETE INSTALLATION SHALL BE PROVIDED. THE DRAWINGS AND SPECIFICATIONS DO NOT UNDERTAKE TO INDICATE EVERY
ITEM OF MATERIAL, EQUIPMENT OR LABOR REQUIRED TO PRODUCE A SAFE, COMPLETE AND PROPERLY OPERATING SYSTEM.
1.
SUPPLY, RETURN AND O.A. DUCTWORK SHALL BE CONSTRUCTED OF GALVANIZED SHEETMETAL IN ACCORDANCE WITH
SMACNA DUCT CONSTRUCTION STANDARDS, LATEST EDITION. ALL JOINTS AND SEAMS IN ALL SHEETMETAL DUCTWORK
SHALL BE SEALED WITH DUCT SEALER.
4.
PRIOR TO PURCHASING ANY MATERIALS OR STARTING ANY WORK, CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS, DUCTWORK SIZES AND LOCATIONS, EQUIPMENT, ETC. SHOWN ON THE DRAWINGS OR AFFECTING THIS WORK
AND SHALL REPORT ANY DEVIATIONS TO THE ARCHITECT.
2.
ALL OPEN ENDED DUCTS AND FAN OUTLETS SHALL HAVE ½” X ½” HARDWARE CLOTH AFFIXED TO THE OPENING.
3.
EXHAUST DUCTWORK SHALL BE GALVANIZED SHEET METAL (G 90 MINIMUM) CONSTRUCTED TO SMACNA STANDARDS AND
SHALL NOT BE INSULATED UNLESS NOTED OTHERWISE.
4.
ALL DUCTWORK SHALL BE SUPPORTED BY THE BUILDING STRUCTURE AND SHALL NOT REST ON CEILING TILES OR CEILING
STRUCTURE. DUCT SUPPORTS AND ATTACHMENT TO STRUCTURE SHALL BE PER SMACNA STANDARDS.
5.
FLEXIBLE DUCTWORK SHALL BE THERMAFLEX M-KE (U.L. 181 LISTED, CLASS 1 FLEXIBLE AIR DUCT) OR EQUAL. PROVIDE
MINIMUM INSULATION VALUE OF R-6; R-8 WHEN LOCATED OUTSIDE THE THERMAL ENVELOPE OF THE BUILDING, OR GREATER
WHERE REQUIRED BY APPLICABLE ENERGY CODE. AIR CONNECTORS ARE NOT ACCEPTABLE. FLEX DUCT DIAMETER SHALL
MATCH DEVICE NECK DIAMETER. PROVIDE ROUND GALVANIZED STEEL DUCT RUNOUTS TO MAINTAIN A MAXIMUM FLEXIBLE
DUCT LENGTH OF 8'-0". FLEXIBLE DUCTWORK SHALL BE INSTALLED AS STRAIGHT AS POSSIBLE AND SHALL BE ROUTED AND
SUPPORTED WITHOUT FORMING CRIMPS OR OTHER AIR FLOW RESTRICTIONS. PROVIDE SQUARE TO ROUND ADAPTERS OR
BOOTS TO CONNECT TO AIR DEVICE NECK WHEN REQUIRED.
6.
ROUND AND FLEXIBLE SUPPLY AIR DUCTWORK SHALL BE CONNECTED TO MAIN DUCTS WITH A CONICAL TYPE SPIN-IN
FITTING WITH MANUAL VOLUME DAMPER (EXCEPT WHERE INSTALLED ABOVE INACCESSIBLE CEILINGS, THE DAMPER SHALL
BE OMITTED AND PROVIDED IN THE AIR DEVICE NECK).
7.
TAPE, BED AND SEAL AIR TIGHT ALL PENETRATIONS FROM RETURN AIR PLENUMS TO NON RETURN AIR PLENUMS THAT ARE
REQUIRED DUE TO DUCTWORK, PIPING OR OTHER ITEMS.
8.
DUCTWORK DIMENSIONS SHOWN ON THE DRAWINGS ARE INSIDE CLEAR DIMENSIONS.
9.
EXTERNAL STATIC PRESSURE (ESP) DOES NOT INCLUDE COIL, CASING OR FILTER PRESSURE DROP.
10.
PROVIDE ALL OUTDOOR AIR INTAKES AND EXHAUST OPENINGS WITH MOTORIZED OR GRAVITY DAMPERS IN ACCORDANCE
WITH THE LOCAL ENERGY CODE. DAMPERS SHALL CLOSE WHEN THE VENTILATION SYSTEM IS NOT OPERATING.
11.
LOCATIONS OF GRILLES, REGISTERS, AND DIFFUSERS SHOWN ON THE DRAWINGS ARE APPROXIMATE. COORDINATE EXACT
LOCATIONS WITH LIGHTS, CEILING GRID, ETC. AND ARCHITECTURAL REFLECTED CEILING PLAN.
12.
WHERE BALANCING DAMPERS CANNOT BE ACCESSED FROM BELOW THE CEILING, PROVIDE A REMOTE OPERATED DAMPER;
YOUNG REGULATOR OR EQUAL.
13.
FLEXIBLE DUCT CONNECTORS SHALL BE USED TO CONNECT DUCTWORK AND PLENUMS TO FAN-ROTATING EQUIPMENT;
DURODYNE EXCELON OR APPROVED EQUAL. FLEXIBLE CONNECTORS EXPOSED TO THE WEATHER SHALL BE UV AND OZONE
RESISTANT. FABRICS, COATING AND ADHESIVES SHALL BE TESTED IN ACCORDANCE WITH UL 701 AND HAVE A FLAME
SPREAD/ SMOKE DEVELOPED RATING OF 25/50.
mO
u
N
b
o
-b n
C
c
P
M
E
J
3
0
6
P
H
:a
IL
U
A
le
k
S
&
n
rd
o
E
R
Y
N
iT
.g
,Ic
rs
e
D
O IG
jN
E
@H
e
,s
V
R
T
4
)
0
7
(
m
l.c
k
s
n
a
rd
o
O
N
j 5
R
7
4
C2
1
0
X
A
R
F
O J
O
8
4
)
0
7
(
S
, R
D
6
2
A
G
0 N
A
1 &S
7
0
3
K A
G N
N
E
L
I E
R S IN C
.
DN
DUCT DROP
---
R
DUCT RISE
---
DUCT SIZE - FLAT OVAL
---
BOTTOM OF DUCT
BOD
DUCT SIZE - RECTANGULAR (OR 12/10)
---
CEILING RADIATION DAMPER
CRD
DUCT SIZE - ROUND
---
CLEAN OUT
CO
DUCT SMOKE DETECTOR
---
CONDENSATE DRAIN
CD
DOWN
DN
DRY BULB
DB
8
12x10
8"∅
DUCT TRANSITION
FCU
--
EQUIPMENT DESIGNATION
H
M
T
S
---
FIRE DAMPER (HORIZONTAL)
FD
FIRE DAMPER (VERTICAL)
FD
ACCESS PANEL (REFER TO ARCHITECTURAL DWGS.)
AP
ELECTRIC UNIT HEATER
EUH
ELECTRIC WALL HEATER
EWH
5.
FLEXIBLE DUCT
---
ENTERNING AIR TEMPERATURE
EAT
FLEXIBLE DUCT CONNECTOR
---
EXHAUST AIR (ENVIRONMENTAL AIR)
EA
EA
EXHAUST FAN
EF
ESP
HUMIDISTAT
H
LINED DUCT
---
EXTERNAL STATIC PRESSURE
MANUAL VOLUME DAMPER (RECTANGULAR DUCT)
MVD
GAS FIRED UNIT HEATER
MANUAL VOLUME DAMPER (ROUND DUCT)
MVD
HEAT PUMP
MOTORIZED DAMPER
MD
GUH
LEAVING AIR TEMPERATURE
NOT TO SCALE
NTS
RETURN / EXHAUST AIR DUCT TURNED UP
---
OUTSIDE AIR
OA
RETURN / EXHAUST AIR GRILLE (CEILING)
---
PRESSURE DROP
PD
SIDEWALL SUPPLY REGISTER OR GRILLE
---
RETURN AIR
RA
SIDEWALL RETURN AIR REGISTER OR GRILLE
-----
ROOF TOP UNIT
SLOT DIFFUSER
---
SQUARE FEET
SF
SQUARE CEILING DIFFUSER
---
STATIC PRESSURE (IN. W.C.)
SP
SUPPLY AIR DUCT TURNED DOWN
---
SUPPLY AIR
SA
SUPPLY AIR DUCT TURNED UP
---
SUPPLY GRILLE
SG
THERMOSTAT/TEMPERATURE SENSOR
TSTAT
SUPPLY REGISTER
SR
TURNING VANES
---
UNLESS NOTED OTHERWISE
UNO
WALL CAP (EA OR OA)
---
WALL LOUVER
WL
WATER COLUMN OR WATER GAUGE
WALL LOUVER (EXHAUST)
WL
WET BULB
---
---
---
---
7.
ALL MECHANICAL EQUIPMENT AND SYSTEMS SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR AFTER ACCEPTANCE BY
OWNER.
8.
ALL HVAC COMPRESSORS SHALL HAVE EXTENDED 4-YEAR MANUFACTURER'S WARRANTY FOR A 5-YEAR TOTAL WARRANTY.
9.
FOR EXACT LOCATION OF OUTDOOR AIR CONDITIONING UNITS, SEE ARCHITECTURAL DRAWINGS.
10.
INSTALL ROOF MOUNTED OUTDOOR AIR CONDITIONING EQUIPMENT LEVEL ON 2" (MIN.) THICK POLYPROPYLENE EQUIPMENT
PAD 4" LARGER THAN OUTDOOR UNIT FOOTPRINT; DIVERSITECH "E LITE PAD" OR APPROVED EQUAL. MOUNT ALL EQUIPMENT
ON ½” THICK NEOPRENE PADS (MINIMUM OF 4 PADS PER UNIT). ALL ROOFTOP MOUNTED EQUIPMENT SHALL BE INSTALLED
PER DETAILS AND AS RECOMMENDED BY THE MANUFACTURER.
11.
12.
13.
WL
---
ALL MECHANICAL EQUIPMENT SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S RECOMMENDATIONS.
RTU
WALL LOUVER (INTAKE)
---
6.
LAT
---
---
WC or WG
M-101
M-102
M-103
M-104
M-201
M-202
M-301
M-302
14.
15.
16.
WB
---
---
---
---
---
---
---
---
---
---
DRAWINGLIST‐HVAC
SHEETNUMBER
SHOP DRAWINGS SHALL BE SUBMITTED TO AND APPROVED BY THE ARCHITECT PRIOR TO ORDERING, PURCHASING, OR
FABRICATING ANY MECHANICAL EQUIPMENT. SHOP DRAWINGS SHALL INCLUDE: ALL EQUIPMENT SCHEDULED OR SPECIFIED
ON THE DRAWINGS; DUCTWORK DRAWN TO 1/4" SCALE OR THE SCALE SHOWN ON THE DRAWINGS; PARKING GARAGE
CO/NO2 MONITORING AND CONTROL SYSTEM LAYOUT INCLUDING SENSOR LOCATIONS, SEQUENCE OF OPERATION AND
PRODUCT DATA; MECHANICAL VENTILATION REFRIGERANT PIPING AND CONTROL WIRING SCHEMATICS CERTIFIED BY THE
AIR CONDITIONING EQUIPMENT MANUFACTURER. FAILURE TO SUBMIT REFRIGERANT PIPING DRAWINGS SHALL BE CAUSE
FOR REJECTION OF THE ENTIRE SUBMITTAL. LONG LINE REFRIGERANT PIPING APPLICATIONS SHALL BE IN ACCORDANCE
WITH THE MANUFACTURER'S CURRENT SPLIT SYSTEM LONG-LINE APPLICATION GUIDELINE. SHOP DRAWINGS SHALL BE
SUBMITTED SIMULTANEOUSLY IN ONE PACKAGE WITH EACH ITEM CLEARLY NOTED BY THE TAG USED ON THE DRAWINGS.
HP
RETURN / EXHAUST AIR DUCT TURNED DOWN
MECHANICAL EQUIPMENT WITH SERVICE AND
AIRFLOW
CLEARANCES (AS REQUIRED BY THE MANUFACTURER)
AIR DISTRIBUTION:
PORTIONS OF DUCTWORK AND PIPE INSULATION VISIBLE THROUGH AIR DISTRIBUTION DEVICES IN FINISHED AREAS SHALL
BE PAINTED FLAT BLACK.
MOUNT TOP OF THERMOSTATS AND SENSORS 46" AFF UNLESS NOTED OTHERWISE. PROVIDE CLEAR LOCKING GUARD
ASSEMBLIES FOR ALL PUBLIC AREA AND CLASSROOM THERMOSTATS. COORDINATE THERMOSTAT LOCATIONS WITH OTHER
TRADES. ALL THERMOSTATS SHALL BE ADA COMPLIANT.
ANY EXISTING WALL, FLOOR, OR CEILING SURFACE THAT IS DISTURBED DURING THE COURSE OF THE HVAC WORK SHALL BE
REPAIRED TO MATCH NEW AND/OR EXISTING CONDITIONS.
CONTRACTOR SHALL COORDINATE THE INSTALLATION OF ALL MECHANICAL EQUIPMENT, DUCTWORK, PIPING, ETC. TO FIT
WITHIN THE SPACE ALLOWED BY THE ARCHITECTURAL AND STRUCTURAL CONDITIONS. CUTTING OR OTHERWISE ALTERING
ANY STRUCTURAL MEMBERS SHALL NOT BE PERMITTED WITHOUT WRITTEN PERMISSION FROM THE ARCHITECT.
PROVIDE ACCESS PANELS IN NON-ACCESSIBLE CEILINGS AND IN WALL STRUCTURE TO ALLOW ADEQUATE ROOM FOR
MAINTENANCE OF EQUIPMENT AND BALANCING OF SYSTEMS. ACCESS PANELS IN CEILING AND WALLS SHALL BE PROVIDED
WHERE SHOWN ON THE DRAWINGS OR NECESSARY TO ACCESS DAMPERS, VALVES, ETC. COORDINATE EXACT LOCATION OF
ALL ACCESS PANELS WITH THE ARCHITECT DURING THE SHOP DRAWING PROCESS.
ALL MECHANICAL EQUIPMENT SHALL BE LABELED WITH A 2” HIGH SEMI-RIGID PLASTIC LAMINATE NAMEPLATE WITH 1” HIGH WHITE
LETTERS ON A BLACK BACKGROUND SECURELY AFFIXED TO THE EQUIPMENT. THE NAMEPLATE SHALL SHOW THE EQUIPMENT TAG
USED ON THESE DRAWINGS.
17.
REFER TO ARCHITECTURAL PLANS FOR FLOOR AND CEILING ASSEMBLY UL RATINGS AND DETAILS.
18.
ALL MATERIALS EXPOSED WITHIN HVAC PLENUMS SHALL HAVE A FLAME-SPREAD INDEX OF NOT MORE THAN 25 AND A
SMOKE-DEVELOPED RATING INDEX OF NOT MORE THAN 50 UNLESS OTHERWISE ALLOWED BY CODE.
16.
14.
EXPOSED INTERIOR DUCTWORK TO BE PAINTED SHALL HAVE ALL EXPOSED SURFACES (INCLUDING HANGER STRAPS) COATED
WITH A "PAINT GRIP" FINISH FOR FIELD PAINTING. AS AN OPTION, MILL PHOSPHATIZED STEEL DUCTWORK MAY BE USED. LINE OR
INSULATE PER HVAC GENERAL NOTES OR SPEC SECTION 23 07 00.
15.
EXPOSED DOUBLE-WALL, INSULATED ROUND OR FLAT OVAL DUCT AND FITTINGS SHALL BE BY McGILL AIRFLOW LLC (OR
EQUAL BY LINDAB, INC OR SEMCO, INC.). DUCT SYSTEM SHALL HAVE SPIRAL LOCKSEAM (OR WELDED) GALVANIZED SHEET
METAL OUTER SHELL, 1” THICK COATED ACOUSTICAL LINER, AND A PERFORATED SHEET METAL INNER LINER.
SHEETNAME
KEY PLAN
A
B
ISSUE FOR PERMIT
BID & CONSTRUCTION
PROTECT DUCTS EXPOSED IN FINISHED SPACES FROM BEING DENTED, SCRATCHED, OR DAMAGED. TRIM DUCT SEALANTS FLUSH
WITH METAL TO CREATE A SMOOTH AND UNIFORM EXPOSED BEAD. TWO-PART TAPE SEALING SYSTEMS ARE NOT ALLOWED.
REPAIR OR REPLACE DAMAGED DUCTWORK AND FINISH WORK THAT DOES NOT COMPLY WITH THESE REQUIREMENTS.
INSULATION:
19.
THE FIRE SPRINKLER CONTRACTOR SHALL INSTALL AND LOCATE ALL FIRE SPRNKLER PIPING TO PREVENT PIPING FROM THE
POTENTIAL OF FREEZING. THE FIRE SPRINKLER CONTRACTOR IS REQUIRED TO NOTIFY THE ARCHITECT AND COORDINATE WITH
THE MECHANICAL AND ELECTRICAL CONTRACTORS IF HEATING IS REQUIRED.
20.
UNLESS NOTED OTHERWISE, THE ROOF CURB SHALL BE FURNISHED WITH THE EQUIPMENT IT SUPPORTS (SUBMIT WITH
SHOP DRAWINGS). VIBRATION/SOUND ATTENUATING ROOF CURBS (WHERE SCHEDULED OR NOTED) SHALL BE MASON
RSC-A (2½“) OR EQUAL WITH ACOUSTICAL PACKAGE.
21.
DUCTWORK AND PIPING SHALL NOT BE INSTALLED IN ELECTRICAL ROOMS, TELECOMM ROOMS, OR ELEVATOR EQUIPMENT
ROOMS EXCEPT FOR DUCTWORK AND PIPING SERVING THAT SPECIFIC ROOM. DUCTWORK AND PIPING SHALL NOT BE
ROUTED ABOVE ELECTRICAL EQUIPMENT PER THE NATIONAL ELECTRICAL CODE ARTICLE 110.
1.
1.
AFTER CONSTRUCTION, THE ENTIRE HVAC SYSTEM SHALL BE TESTED, ADJUSTED, AND BALANCED TO DELIVER THE AIR
QUANTITIES SHOWN ON THE DRAWINGS. SUBMIT CERTIFIED (AABC OR NEBB) TEST AND BALANCE REPORT TO THE
ARCHITECT FOR APPROVAL.
2.
VENTILATION AIR DISTRIBUTION SYSTEMS (OUTDOOR AIR AND EXHAUST AIR) SHALL BE BALANCED TO ACHIEVE THE AIRFLOW
RATES INDICATED ON THE DRAWINGS. THESE AIRFLOW RATES SHALL BE CONSIDERED MINIMUM RATES. THE MEASURED AIR
BALANCE TOLERANCE FOR BOTH OUTDOOR AIR AND EXHAUST AIR RATES SHALL BE 0% TO +10%.
b. INDOOR EXPOSED ROUND, SPIRAL AND OVAL SUPPLY AND RETURN AIR DUCT SHALL BE LINED WITH 1” THICK ROUND DUCT
LINER (MINIMUM R-4), JOHNS MANVILLE SPIRACOUSTIC PLUS OR EQUAL.
c. DUCT LINER FOR ACOUSTICS: LINE ALL SHEETMETAL DUCTWORK A MINIMUM OF 15'_0" (OR AS INDICATED) UPSTREAM AND
DOWNSTREAM OF ALL ROOFTOP UNITS, AND AIR HANDLING UNITS. DUCT LINER SHALL BE 1½” THICK, (MINIMUM R-6 OR
GREATER WHERE REQUIRED BY APPLICABLE ENERGY CODE), JOHNS MANVILLE LINACOUSTIC RC OR EQUAL. THE
LEADING EDGE OF THE DUCT LINER SHALL HAVE A SHEETMETAL NOSING. LINED DUCTWORK DOES NOT REQUIRE
ADDITIONAL EXTERIOR INSULATION WHERE LINER MEETS REQUIRED R-VALUES.
d. REFER TO ARCHITECTURAL DRAWINGS AND/OR SPECIFICATIONS FOR PAINTING OF DUCTWORK, INSULATION, ETC. IN
EXPOSED INTERIOR AREAS.
2.
CONTRACTOR SHALL COORDINATE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS OF ALL MECHANICAL EQUIPMENT
WITH ELECTRICAL DRAWINGS PRIOR TO ORDERING EQUIPMENT OR SUBMITTING SHOP DRAWINGS, AND SHALL FURNISH
EQUIPMENT WIRED FOR THE VOLTAGES SHOWN THEREIN. SHOP DRAWING SUBMITTALS SHALL CLEARLY STATE THAT THE
ELECTRICAL CHARACTERISTICS OF ALL EQUIPMENT HAS BEEN COORDINATED WITH THE ELECTRICAL CONTRACT
DOCUMENTS AND THE ELECTRICAL CONTRACTOR.
2.
ALL MECHANICAL EQUIPMENT REQUIRING ELECTRICAL POWER SHALL BE INSTALLED WITH DISCONNECT SWITCHES AT EACH
PIECE OF EQUIPMENT. COORDINATE SWITCH TYPE (FUSED OR NON-FUSED) WITH EQUIPMENT CHARACTERISTICS,
MANUFACTURER'S RECOMMENDATIONS AND THE ELECTRICAL DRAWINGS.
3.
PROVIDE ALL SYSTEM CONTROLS AND ASSOCIATED CONTROL AND INTERLOCK WIRING FOR COMPLETE AND OPERABLE
SYSTEMS. 120 VOLT AND HIGHER WIRING SHALL BE MC CABLE OR IN CONDUIT IN ACCORDANCE WITH LOCAL CODES AND THE
MATERIALS AND INSTALLATION REQUIREMENTS OF DIVISION 26 - ELECTRICAL.
4.
COORDINATE POWER AND FIRE ALARM REQUIREMENTS OF ALL COMBINATION FIRE/SMOKE DAMPERS AND SMOKE DAMPERS
WITH THE ELECTRICAL CONTRACTOR.
5.
6.
7.
ALL REQUIRED CONTROL WIRING (INCLUDING POWER WIRING REQUIRED FOR CONTROL PANELS, DEVICES, ETC.) NOT
INDICATED ON THE ELECTRICAL DRAWINGS SHALL BE INCLUDED AS PART OF THE MECHANICAL WORK.
WIRING IN HVAC PLENUM SPACES SHALL BE INSTALLED ACCORDING
TO CODE REQUIREMENTS.
UNLESS NOTED OTHERWISE, TRANSFORMERS, CONTROLS AND CONTROL WIRING REQUIRED FOR ALL MECHANICAL
SYSTEMS SHALL BE FURNISHED WITH THE EQUIPMENT IT SERVES AND INSTALLED BY THE MECHANICAL CONTRACTOR.
MOTOR STARTERS FOR HVAC EQUIPMENT SHALL BE FURNISHED WITH THE MOTOR OR APPARATUS WHICH IT OPERATES.
MOTOR STARTER INSTALLATION SHALL BE BY THE DIVISION 26 CONTRACTOR.
ROUTING OF PIPING AND DUCTWORK SHALL BE COORDINATED WITH THE ELECTRICAL CONTRACTOR AND ALL OTHER
TRADES DURING THE SUBMITTAL AND LAYOUT PHASE. PIPING AND DUCTWORK SHALL NOT BE ROUTED THROUGH THE
DEDICATED ELECTRICAL SPACE ABOVE EACH LOAD CENTER.
PIPE INSULATION:
a. REFRIGERANT SUCTION PIPING INSULATION SHALL BE FLEXIBLE ELASTOMERIC TUBING, AP/ARMAFLEX PIPE INSULATION
WITH REINFORCED LAP SEAL AS MANUFACTURED BY ARMACELL OR EQUAL. INSULATION THICKNESS SHALL BE PER
SPECIFICATION 23 23 00. INSULATION SHALL BE SLID OVER PIPING FROM ONE END BEFORE PIPE ENDS ARE JOINED
AND SHALL NOT BE SLIT OR CUT. ALL JOINTS AND SEAMS SHALL BE SEALED WEATHER-TIGHT. FINISH COAT FOR
FLEXIBLE ELASTOMERIC INSULATION INSTALLED OUTDOORS SHALL BE WATER-BASED LATEX ENAMEL DESIGNED
FOR USE OVER ALL FORMS OF FLEXIBLE ELASTOMERIC INSULATION. FINISH COAT SHALL PROVIDE A PROTECTIVE
FINISH SUITABLE TO BOTH INDOOR AND OUTDOOR APPLICATIONS, FORMULATED FOR COLD WEATHER FLEXIBILITY
TO RESIST CRACKING AND WEATHER-RESISTANT TO ULTRAVIOLET (UV) AND OZONE. COATING SHALL BE
ARMAFLEX WB FINISH OR EQUIVALENT.
MECHANICAL/ELECTRICAL COORDINATION:
1.
DUCT INSULATION:
a. DUCT WRAP SHALL BE UL LISTED FIBERGLASS BLANKET INSULATION WITH FOIL VAPOR BARRIER, JOHNS MANVILLE
MICROLITE XG OR EQUAL. PUNCTURES AND TEARS IN THE FOIL JACKET SHALL BE PATCHED WITH FOIL TAPE TO MAINTAIN
THE INTEGRITY OF THE VAPOR BARRIER. INSULATE SHEET METAL DUCTWORK IN THE THICKNESSES AND DENSITIES AS
LISTED BELOW:
i. SHEET METAL SUPPLY AND OUTSIDE AIR DUCTWORK: 2” THICK, 1 LB/FT3 DENSITY, R-6 MINIMUM INSTALLED.
ii. SHEET METAL RETURN DUCTWORK IN NON-AIR CONDITIONED AREAS (SUCH AS INTERSTITIAL SPACES AND FLOOR/CEILING
ASSEMBLIES): 2" THICK, 1 LB/FT3 DENSITY, R-6 MINIMUM INSTALLED.
TESTING, ADJUSTING AND BALANCING
GENERAL NOTES AND LEGEND - MECHANICAL
SCHEDULES - MECHANICAL
DETAILS - MECHANICAL
DETAILS - MECHANICAL
FLOOR PLAN AREA A - MECHANICAL
FLOOR PLAN AREA B - MECHANICAL
ROOF PLAN AREA A - MECHANICAL
ROOF PLAN AREA B - MECHANICAL
2808 Fairmount Street, Suite 300
Dallas, Texas 75201 | 214.303.1500
DESCRIPTION
P
3
0
6
CU
M
E
c
m
u
N
b
o
J
H
O
:P
IL
A
a
l N
k
S
&
n
d
o
r-E
e
b
D
Y
IT
R
O
n
i R
.g
,c
rs
e
,jN
E
IV
G O
@
e
s
N
4
)
0
7
(
T
H
m
l.c
k
s
n
a
rd
o
j R
C
7 R
4
5
O
X
A
F
1
0
2 S
,(
8
4
)
0
7
O A
J
G
6
2
R
D 3
0
1
7
0
N &K
A
S A
G IN E
N
E
L
R S IN C
.
CENTRAL BAPTIST CHURCH
CHILDRENS BUILDING
SYMBOL
3300 West 7th Street, Suite 110
Fort Worth, Texas 76107 | 817.303.1500
HVAC NOTES
C
c
P
mO
u
N
b
o
M
JE
3
0
6
P
H
:A
IL
U
a
- Y
e
klb
S
&
n
rd
o
E
R
N
D
IT
O
n
i IG
rs,c.g
e
jR
E
@
e
,s
V
N H
T
(
4
)
0
7
m
l.c
k
s
n
a
rd
o
O
N
j 5
R
7
4
C2
1
0
R
X
A
F
O J
O
S
8
4
)
0
7
(
, R
D
6
2
A
G
0 N
A
1 &S
7
0
3
K A
G N
N
E
L
I E
R S IN C
.
b. INSULATE ALL CONDENSATE DRAIN PIPING WITH FIBERGLASS PIPE INSULATION WITH VAPOR BARRIER JACKET; JOHNS
MANVILLE MICRO-LOK OR APPROVED EQUAL. FITTINGS, VALVES AND PIPING SPECIALITIES SHALL BE PROVIDED WITH
FORMED FITTING COVERS BY PROTO PVC CORPORATION. SEE SPECIFICATIONS FOR INSULATION THICKNESSES AND
ADDITIONAL INFORMATION. ALL EXPOSED INSULATED PIPING BELOW 10'_0" AFF SHALL BE PROTECTED BY A CORRUGATED
ALUMINUM JACKET WITH ALUMINUM BANDS 3'-0" O.C.
1991 FM 158, BRYAN, TX 77845
HVAC LEGEND
PIPING:
1.
REFRIGERANT PIPING SHALL BE TYPE L OR ACR (AIR CONDITIONING AND REFRIGERATION FIELD SERVICE) COPPER TUBING
WITH BRAZED JOINTS.
2.
REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT
CAPS.
3.
CONDENSATE FROM ALL AIR CONDITIONING EQUIPMENT SHALL BE TRAPPED AND ROUTED TO THE NEAREST PLUMBING
DRAIN. CONDENSATE PIPING SHALL BE SCHEDULE 40 PVC (EXCEPT INSULATED TYPE M COPPER IN HVAC PLENUMS).
CONDENSATE SHALL BE PUMPED AS REQUIRED. PVC EXPOSED TO THE WEATHER SHALL BE PAINTED WITH A LIGHT
COLORED ACRYLIC OR LATEX ULTRAVIOLET (UV) AND OZONE INHIBITOR PAINT THAT IS CHEMICALLY COMPATIBLE WITH PVC.
4.
ALL PIPING ABOVE GRADE SHALL BE SUPPORTED BY THE BUILDING STRUCTURE AND SHALL NOT REST ON CEILING TILES OR
CEILING STRUCTURE. PIPING HUNG FROM JOISTS SHALL BE HUNG FROM THE TOP CHORDS OF THE JOISTS.
No. Date
Revision
RAC
Drawn
JRM
Checked
WAS
Approved
GENERAL NOTES
AND LEGEND MECHANICAL
Project No.
Date
Last Revision
15187.00
05/11/2016
M-101
printed5/11/2016 12:25:59 PM
MANF.
EQUIP
SERIES
MORGANIZER
MODELNO.
OCD181E_TXV
A112,A113,A114,A115,A116
OCD181E_TXV
A107,A108,A109,A110,A111
OE360B4DH_100
A119,A117,A118,A122,A120,A121
OE420B4DH_100
A124,A125,A126,A123,A127,A128,A129
OHC120E
A101,A102,A103,A104,A105,A106,104,105
A100
OCD181E_TXV B166,B168,B167,112,A135,A134,A133,B103,B
102,B101,108,A132
107
100,101
OHC120E
101
101,115
B100
OE360B4DH_100 B156,B165,B159,B164,B160,B161,B163,B162,
B132,B133,B131,B130,B134,B135
OCD151E_TXV
B114,B113,B115,B112,B116,B117
OHC120E
B104,B105,B106,B107
OCD211E_TXV
B155,B154,B153,B149,B147,B145,B146
B139,B138,B137,B141,B140,B144,B143,B142,
B100M
OCD151E_TXV
B136,B126,B125,B124,B123,B127,B128,B129
OCD151E_TXV
B121,B120,B119,B118,B110,B109,B108
RTU 1
RTU 2
RTU 3
RTU 4
RTU 5
RTU 6
RTU 7
TRANE
TRANE
TRANE
TRANE
TRANE
TRANE
TRANE
THD181
THD181
TED360
TED420
THC120
THC120
THD181
RTU 8
RTU 9
RTU 10
RTU 11
RTU 12
RTU 13
TRANE
TRANE
TRANE
TRANE
TRANE
TRANE
THC102
THD150
THC120
THC092
THD240
TED360
RTU 14
RTU 15
RTU 16
RTU 17
TRANE
TRANE
TRANE
TRANE
THD151
THC120
THD211
THC060
RTU 18
RTU 19
TRANE
TRANE
THD151
THD151
SYSTEM
TYPE
AREASERVED
HEATING
EFFICIENCY
EER/IEER SEER
KW
FILTERS
WEIGHT
NO.OF
MERV
EAT
(LB)
CONTROL RATING
(˚F)
STAGES
ACCESSORIES
CV
CV
CV
CV
CV
CV
CV
3600
3550
7800
8200
2200
3400
3200
1320
1310
2250
2390
850
520
1280
3600
3550
7800
8200
2200
3400
3200
3
3
7 1/2
7 1/2
3 3/4
3 3/4
3
1.0
1.0
1.0
1.0
1.0
1.0
1.0
15
15
30
35
10
10
15
170.9
169.8
320.5
363.9
108.2
105.7
165.2
107.1
106.4
214.5
242.1
69.1
87.7
103.4
84.2
84.4
82.2
82.3
84.7
78.8
85
70
70
69
69
70
65
70
12
12
12
12
12.4
12.4
12
-
54
36
90
90
27
27
36
52.2
51.9
55.6
55.5
51.4
62.2
50.8
SCR
2
SCR
SCR
2
2
2
7
7
7
7
7
7
7
3000
3000
4100
4100
1800
3000
3000
1,2,3,4,5,6,7,8,9,10,11,12,13,14,15
1,2,3,4,5,6,7,8,9,10,11,12,13,14,15
1,2,3,4,5,6,7,8,10,11,12,13,14,15
1,2,3,4,5,6,7,8,10,11,12,13,14,15
1,2,3,4,5,6,7,8,9,10,11,12,13,14,15
1,2,3,4,5,6,7,8,10,11,13,14,15
1,2,3,4,5,6,7,8,9,10,11,12,13,14,15
CV
CV
CV
CV
CV
CV
3000
5000
2300
2700
7200
6500
560
830
770
700
690
3130
3000
5000
2300
2700
7200
6500
3 3/4
3
3 3/4
3 3/4
7 1/2
7 1/2
1.0
1.0
1.0
1.0
1.0
1.0
8.5
12.5
10
7.5
20
30
93.8
147
109.2
87
236.6
314.4
69.8
113.2
67.2
62
156.9
221
79.7
79.2
83.4
81.5
77.5
87.2
67
67
70
69
65
72
12.5
12.1
12.4
12.6
11.0
12
-
27
54
27
27
72
90
60.0
60.9
53.6
56.9
59.6
47.0
2
SCR
2
2
SCR
SCR
7
7
7
7
7
7
1500
3000
1800
1500
3000
4100
1,2,3,4,5,6,7,8,9,10,11,12,13,14,15
1,2,3,4,5,6,7,8,9,10,11,12,13,14,15
1,2,3,4,5,6,7,8,10,11,12,13,14,15
1,2,3,4,5,6,7,8,9,10,11,12,13,14,15
1,2,3,4,5,6,7,8,10,11,13,14,15
1,2,3,4,5,6,7,8,9,10,11,12,13,14,15
CV
CV
CV
CV
2100
2300
3650
1600
1220
1030
1620
170
2100
2300
3650
1600
3
3 3/4
5
3/4
1.0
1.0
1.0
1.0
12.5
10
17.5
5
127.5
132.9
188
58
82.7
71.2
125
40
87.2
86.2
86.3
77.9
72
72
72
65
12.1
12.4
11.8
-
14.2
36
27
54
12
46.7
48.7
48.7
62.6
2
2
SCR
2
7
7
7
7
3000
1800
3000
1000
1,2,3,4,5,6,7,8,9,10,11,12,13,14,15
1,2,3,4,5,6,7,8,9,10,11,12,13,14,15
1,2,3,4,5,6,7,8,9,10,11,12,13,14,15
1,2,3,4,5,6,7,8,9,10,11,13,14,15
CV
CV
2730
2950
1140
1080
2730
2950
3
3
1.0
1.0
15
12.5
135.5
131.4
91
79.8
85.4
85.8
70
70
12
12.1
-
36
36
49.5
49.2
2
2
7
7
3000
3000
1,2,3,4,5,6,7,8,9,10,11,12,13,14,15
1,2,3,4,5,6,7,8,9,10,11,12,13,14,15
2808 Fairmount Street, Suite 300
Dallas, Texas 75201 | 214.303.1500
TAG
SUPPLYFAN
NETCOOLING
AIRFLOW(CFM)
CAPACITY(MBH)
EAT(˚F)
MAX
ESP
MOTOR
OUTSIDEAIR
(INWC) NOM TOT
TOTAL
SENS DB
WB
HP
TONS
MIN
MAX
3300 West 7th Street, Suite 110
Fort Worth, Texas 76107 | 817.303.1500
ROOFTOPUNIT(ELECTRICHEAT)
NOTES: (APPLIES TO ALL UNITS).
A. SCHEDULED COOLING CAPACIITY BASED ON THE FOLLOWING OUTDOOR AMBIENT
TEMPERATURE: 100 ˚F DB
B. REFRIGERANT SHALL BE R-410A.
C. ALL RTU'S WITH CAPACITIES 7.5 TONS AND HIGHER SHALL BE PROVIDED WITH MULTIPLE
COMPRESSORS AND MINIMUM OF 2 INDEPENDENT REFRIGERANT CIRCUITS.
D. RETURN AND OUTSIDE AIR DAMPERS SHALL BE CLASS 1 LOW-LEAKAGE TYPE.
E. PROVIDE CRANKCASE HEATERS ON ALL UNITS 6 TONS AND LARGER.
F. RTU'S SHALL BE PROVIDED WITH 2" PLEATED DISPOSABLE FILTERS, CONDENSATE
OVERFLOW SWITCH IN PRIMARY DRAIN PAN, MOTORIZED MODULATING OUTSIDE AIR DAMPER,
COMPRESSOR ANTI-RECYCLE CONTROLS, SINGLE POINT POWER
CONNECTION, COOLING OPERATION DOWN TO 40˚F, 14" HIGH INSULATED ROOF
CURB WITH BASE SLOPED TO MATCH ROOF PITCH.
ACCESSORIES:
KEY PLAN
1. CONTROLS CONTRACTOR TO PROVIDE PROGRAMMABLE THERMOSTATS.
2. LOCKING THERMOSTAT COVER.
3. BACnet COMPATIBLE BAS CONTROLLER.
4. POWERED EXHAUST FOR ECONOMIZER RELIEF.
5. UNIT MOUNTED DISCONNECT.
6. SMOKE DETECTORS. MOUNT IN RETURN AIRSTREAM.
7. MODULATING HOT GAS RE-HEAT ADAPTIVE DEHUMIDIFICATION SYSTEM, CONTROLS.
8. HOT GAS BYPASS. INSTALL ON LEADING COMPRESSOR ON 2-STAGE UNITS.
9. KINETICS KNM-100C SOUND BARRIER MATERIAL INSIDE OF ROOF CURB AND ON TOP OF ROOF DECK.
10. GFCI 15 AMP CONVENIENCE OUTLET POWERED ON LINE SIDE OF DISCONNECT.
11. PHASE MONITORING PROTECTION.
12. RTU DEMAND CONTROL VENTILATION WIRING AND CONTROLS. PROVIDE WITH RETURN DUCT MOUNTED CO2 SENSORS AND ADDITIONAL SENSORS WHERE INDICATED.
13. INTEGRATED DIFFERENTIAL ENTHALPY TYPE ECONOMIZER, SIZED FOR 100% SUPPLY AIR CAPACITY, CAPABLE OF SIMULTANEOUS ECONOMIZER AND COMPRESSOR OPERATION,
AND INTAKE HOOD.
14. CONDENSER COIL HAIL GUARDS.
15. PROVIDE MANUFACTURER STARTUP.
A
B
EQUIPMENT SELECTIONS BASED ON PRODUCTS INDICATED. SUBJECT TO COMPLIANCE WITH ALL PRODUCTS, EQUAL PRODUCTS BY: CARRIER, LENNOX, DAIKIN.
CU 1
CU 2
CU 3
CU 4
WAH 1
WAH 2
WAH 3
WAH 4
MODELNO. TOTALCFM
RK18NMVJU
RK24NMVJU
RK18NMVJU
RK18NMVJU
FTK18NMVJU
FTK24NMVJU
FTK18NMVJU
FTK18NMVJU
MINO.A.
CFM
MAXFAN
HP
MBHTOT
COOL
MBHSENS
COOL
MINSEER
ACCESSORIES
TAG
MODELNO.
AREA
SERVED
TOTALCFM
OUTDOOR
AIRCFM
ESP
(IN.WG.)
MBHTOTAL
COOL
MBHSENS
COOL
MBHINTL
HEAT
MAXFAN
HP
AUXHEAT
KW
MINSEER
MINHSPF
NOTES/
ACCESSORIES
-
-
18
24
18
18
18
24
18
18
14.4
21.2
14.4
14.4
14.4
21.2
14.4
14.4
18
18
18
18
1,3
1,3
1,3
1,3
2,4
2,4
2,4
2,4
AH 1
HP 1
GAM5024
4TWR4024
102 - LIBRARY
-
750
-
120
-
0.8
-
23
23
17.7
17.7
21.5
21.5
1/2
-
5
-
14
14
8.5
8.5
1,2,3,4,5,6,7,8,9
1,2,3,4,5,6,7,8,9
710
710
710
710
ISSUE FOR PERMIT
BID & CONSTRUCTION
NOTES:
A. COOLING CAPACITY BASED ON EAT 80DEG FDB/67 DEG. FWB INDOOR ENTERING AIR TEMPERATURE AND 95 DEG. FWB.
B. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL CHARACTERISTICS. HEATER SHALL BE CAPABLE OF SCHEDULED HEATING CAPACITY AT VOLTAGE SHOWN ON ELECTRICAL
DRAWINGS.
NOTES:
ACCESSORIES:
A. COOLING CAPACITY BASED ON EAT 80DEG FDB/67 DEG. FWB INDOOR ENTERING AIR TEMPERATURE
AND 95 DEG. FWB.
B. COOLING ONLY
1. INDOOR UNIT - SINGLE POINT POWER WIRING KIT WITH DISCONNECTING MEANS AND OVERLOAD PROTECTION
2. OUTDOOR UNIT - DISCONNECT PROVIDED BY ELECTRICAL
3. FACTORY MOUNTED THERMAL EXPANSION VALVE TO ACHIEVE 14 SEER RATING (IF REQUIRED)
4. REFRIGERANT FILTER DRIER (LOCATE PER MANUFACTURERS RECOMMENDATION)
5. SAF-T-SWITCH INSTALLED IN SECONDARY CONDENSATE DRAIN FOR OVERFLOW PROTECTION.
6. MINIMUM MERV 7 REMOVABLE FILTER.
7. 7-DAY PROGRAMMABLE THERMOSTAT WITH FAN-ON-AUTO CONTROL AND AUTO HEATING/COOLING CHANGEOVER.
8. LOCKING THERMOSTAT COVER.
9. COMPRESSOR ANTI-RECYCLE CONTROLS.
ACCESSORIES:
1. LOW AMBIENT OPERATION KIT.
2. WASHABLE FILTER.
3. SINGLE POWER POINT OF CONNECTION.
4. EQUIPMENT MANUFACTURER PROVIDED CONDENSATE PUMP.
SELECTIONS BASED ON PRODUCTS BY TRANE
EQUAL PRODUCTS BY CARRIER, YORK, LENNOX.
SELECTIONS BASED ON PRODUCTS BY DAIKIN
EQUAL PRODUCTS BY LG, MITSUBISHI, TOSHIBA.
FANS
GRILLES,REGISTERSANDDIFFUSERS
TAG
MODEL
DUTY
CFM
ESP
(IN.WG.)
MOTORHP
RPM
DRIVE
WEIGHT
(LBS)
ACCESSORIES
EF 1
EF 2
EF 3
EF 4
EF 5
EF 6
EF 7
G-103-VG
G-095-VG
G-095-VG
G-090-VG
G-090-VG
G-090-VG
SP-110-VG
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
1200
750
800
450
525
675
100
0.375
0.375
0.375
0.375
0.375
0.375
0.25
1/4
1/6
1/6
1/10
1/10
1/6
8.4 W
1725
1725
1725
1725
1725
1725
940
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
40
30
30
30
30
30
15
1,2,3,4,5
1,2,3,4,5
1,2,3,4,5
1,2,3,4,5
1,2,3,4,5
1,2,3,4,5
1,2,3,5
SERIES
TAG
A
B
C
D
E
F
G
H
TMS
TMS
50F
50F
300FL
350FL
TBDI
50FF
CFM
SEE DWGS
SEE DWGS
SEE DWGS
SEE DWGS
SEE DWGS
SEE DWGS
SEE DWGS
SEE DWGS
DUTY
SUPPLY
SUPPLY
RETURN
EXHAUST
SUPPLY
RETURN / TXR
SUPPLY
RETURN
NECKSIZE
FACESIZE
(IN)
DAMPER
MATERIAL
NOTES/
ACCESSORIES
SEE DWGS
SEE DWGS
SEE DWGS
SEE DWGS
SEE DWGS
SEE DWGS
SEE DWGS
SEE DWGS
24x24
12x12
24x24
12x12
SEE DWGS
SEE DWGS
SEE DWGS
24x24
YES
YES
NO
NO
NO
NO
NO
NO
STEEL
ALUMINUM
ALUMNIUM
ALUMINUM
ALUMINUM
ALUMINUM
STEEL
ALUMINUM
ACCESSORIES 1,2
ACCESSORIES 1,2
NOTE E
-
1991 FM 158, BRYAN, TX 77845
TAG
SPLITSYSTEMHEATPUMP
CENTRAL BAPTIST CHURCH
CHILDRENS BUILDING
DUCTLESSSPLITSYSTEM(COOLINGONLY)
ACCESSORIES:
NOTES (APPLY TO ALL DEVICES UNO):
1. MOTORIZED BACKDRAFT DAMPER
2. SPEED CONTROLLER
3. DISCONNECT SWITCH
4. 12" HIGH INSULATED ROOF CURB
5. BIRD SCREEN
A. REFER TO ARCHITECTURAL DRAWINGS FOR TYPE OF CEILING AND/ OR SUSPENSION SYSTEM.
B. FINISH SHALL BE OF THE TYPE AND COLOR SELECTED BY THE ARCHITECT. SUBMIT CHART FOR SHOP DRAWINGS.
C. FOR DRYWALL OR PLASTER CEILING INSTALLATION, PROVIDE PLASTER FRAME.
D. WHEN A DAMPER IS CALLED FOR ABOVE AND THE DEVICE IS TO BE MOUNTED IN AN INACCESSIBLE CEILING, EITHER A FACE
ADJUSTABLE OR REMOTE OPERATED BALANCING DAMPER SHALL BE INCLUDED.
E. TWO 1" SLOTS, 4' LONG, FACTORY INSULATED PLENUM.
SELECTIONS ARE BASED ON PRODUCTS BY: GREENHECK
EQUAL PRODUCTS: PENN, CARNES, COOK
ACCESSORIES:
1. MOLDED INSULATION (R-6) BLANKET ON BACK PAN.
2. BALANCING DAMPER IN INLET.
SELECTIONS ARE BASED ON PRODUCTS BY: TITUS.
EQUAL PRODUCTS: KRUEGER, CARNES, ANEMOSTAT, TUTTLE& BAILEY, PRICE, J & J, METAL AIRE.
WALLLOUVERS
SIZE(IN)
TAG
MODELNO.
WL 1
WL 2
ELECTRICHEATERS
MINFREE
AREA
(SQ.FT.)
CFM
MAXPRESS.
DROP
(IN.WG.)
WIDTH
HEIGHT
ESD-603
12
16
0.44
100
0.15
ESD-603
12
16
0.44
120
0.1
NOTES:
A. FINAL COLOR SELECTION SHALL BE MADE BY ARCHITECT AT TIME OF SHOP DRAWINGS APPROVAL.
ACCESSORIES:
1. MOTOR OPERATED DAMPER
2. BAKED ON ENAMEL FINISH.
3. BIRD SCREEN
SELECTIONS ARE BASED ON GREENHECK
EQUAL PRODUCTS: CARNES, RUSKIN, ARROW
OPERATOR
INTERLOCK
FRAME
ACCESSORIES
MOTORIZED
DAMPER
MOTORIZED
DAMPER
EF-7
ALUMINUM
1,2,3
AH-3
ALUMINUM
1,2,3
TAG
MODELNO
EH 1
AFA840D
APPLICATION MOUNTING
FREEZE
PROTECTION
24" AFF
K.W.
WEIGHT
(LBS)
ACCESSORIES
4
30
1,2,3
NOTES:
A. ALL HEATERS SHALL BE UL LISTED.
B. CAPACITY SCHEDULED IS AT INSTALLED VOLTAGE. COORDINATE WITH
ELECTRICAL DRAWINGS.
C. ALL HEATERS SHALL HAVE THERMAL OVERLOAD PROTECTION.
D. SPRINKLER RISER ROOM HEATER - THERMOSTAT SETPOINT SHALL BE 45
DEGREES FARENHEIGHT
ACCESSORIES:
1. INTEGRAL TAMPERPROOF THERMOSTAT.
2. INTEGRAL DISCONNECT SWITCH.
3. SURFACE MOUNTING KIT.
No. Date
Revision
RAC
Drawn
SELECTIONS ARE BASED ON PRODUCTS BY: RAYWALL
EQUAL PRODUCTS: MARKEL, BERKO, INDEECO
JRM
Checked
WAS
Approved
SCHEDULES MECHANICAL
Project No.
Date
Last Revision
15187.00
05/11/2016
M-102
printed5/11/2016 12:26:06 PM
WING
NUT
NYLON ZIP TIES
H
UNION
ROOFTOP UNIT
INTERIOR LINER
H = FAN INLET
PRESSURE
(IN. WC) + 1"
CL
H/2 MINIMUM
ROUND SHEET
METAL
DUCT DIAMETER AS
INDICATED ON PLANS
PRE-INSULATED FLEXIBLE
DUCTWORK. SEE GENERAL
NOTES/SPECIFICATIONS.
LENGTH SHALL NOT EXCEED
8'-0". PROVIDE SUPPORT PER
SMACNA STANDARDS AND
INSTALL FREE OF KINKS &
SAGS.
ROOF CURB
FINISHED ROOF
THERMAFLEX FLEXFLOW
ELBOW SUPPORT
SUPPORT PIPING 6' OC WITH MIFAB MODEL C PIPE
SUPPORT ON ROOFING WALKPAD MATERIAL - SECURE
PIPE WITH PIPE CLAMP
CONICAL SPIN-IN FITTING
WITH MVD
VOLUME DAMPER
NOT TO SCALE
CONDENSING UNIT
OR HEAT PUMP
1/4" x 1-1/2" CADMIUMPLATED LAG SCREWS
INSULATED
REFRIGERANT LINE
SET, TYPICAL
2"X2", 3/8 " THICK
NEOPRENE PAD,
TYPICAL OF 4
ROOF INSULATION
DIRECTION
OF GRAIN
ROOF DECK
2"R
45°
MIN. 26 GAUGE
VANES
B
1/8" MALLEABLE GALVANIZED STEEL
WIRE ROPE CLIP
1 INCH WIDE, MINIMUM 22 GAUGE
SHEET METAL HANGER STRAP AT 10'-0"
OC (MIN.)
45°
THIMBLE
FILTER SECTION WITH SIDE
ACCESS - MAINTAIN CLEAR
SPACE FOR FILTER REMOVAL
OUTDOOR AIR
INTAKE HOOD
FLEX CONNECTION,
TYP.
14" HIGH (MIN.)
ROOF CURB
LINED SUPPLY AIR DUCT (OR
DUCTBOARD IF SPECIFIED)
OA INTAKE PER PLANS
ROOF DECK
2x4 WOOD NAILER. CAULK
BETWEEN NAILER AND ROOF
CURB
CONTINUOUS 1_2 " x 1"
RUBBER GASKET
GALVANIZED FLASHING
CONTINUOUS OVER WOOD
NAILER
ROOF MOUNTED EXHAUST
FAN (RE: SCHEDULE)
INTERNAL DISCONNECT
SWITCH
DRYER EXHAUST DUCT ROUTED
TO WALL CAP. SEE PLANS FOR
DUCT SIZE AND ROUTING.
BIRD SCREEN
ELECTRIC CONDUIT GUIDE
NOTES:
1. PROVIDE WITH INTEGRAL BACKDRAFT DAMPER
2. WALL CAP BY VENTCRAFT, OR APPROVED EQUAL.
3. PROVIDE CAP WITH PAINT GRIP COATING FOR
FIELD PAINTING.
4. PROVIDE INSECT SCREEN FOR BATHROOM
EXHAUST WALL CAP ONLY.
WELDED PREFABRICATED INSULATED
AIR TIGHT ROOF CURB
C
c
P
ma
u
N
b
o
M
E
J
3
0
6
O
-P
e
lb
k
S
&
n
rd
o
E
H
:A n
IL
U
R
Y
N
iT
.g
,Ic
rs
e
D
O IG
E
@
e
,s
V
R
j H
N
T
4
)
0
7
(
m
l.c
k
s
n
a
rd
o
O
N
j 5
R
7
4
C2
1
0
X
A
R
F
O J
O
8
4
)
0
7
(
S
, R
D
6
2
A
G
0 A
N
1 &S
7
0
3
K A
G N
N
E
L
I E
R S IN C
.
P
3
0
6
CU
M
E
c
m
u
N
b
Jo
H
O
:P
IL
a
A
kl N
S
&
n
d
o
r-E
e
b
D
Y
IT
O
R
n
i R
rs,c.g
e
,N
E
IV
js
G N
@
e
O
4
)
0
7
(
T
H
m
l.c
k
s
n
a
rd
o
j R
C
7 R
4
5
O
X
A
F
1 S
0
2
,(
8
4
)
0
7
O G
J
A
6
2
R
0
D 0
1
7
3
N &S
A
K A
G IN E
N
E
L
R S N
I C
.
4"
M
CO2
CONDENSATE DRAIN- TRAP
PER DETAIL; SIZE AND
ROUTE PER PLANS
NOTES:
1. WHEN FACTORY MOUNTED DISCONNECT SWITCH IS SCHEDULED OR SPECIFIED, CONDUIT FROM BELOW THE ROOF SHALL BE
LOCATED INSIDE THE ROOF CURB. FIELD MOUNTED DISCONNECT SWITCH, BRACKETS, AND CONDUIT SHALL BE LOCATED
SUCH THAT THEY ARE CLEAR OF ALL UNIT ACCESS PANELS AND DO NOT OBSTRUCT AIRFLOW. ATTACH DISCONNECT
SWITCH SUPPORT BRACKETS TO STRUCTURAL MEMBERS OF UNIT AND NOT DIRECTLY TO SHEETMETAL CASING (COORDINATE
WITH ELECTRICIAN).
2. DO NOT MOUNT DISCONNECT SWITCH OVER NAMEPLATE OF UNIT (COORDINATE WITH ELECTRICIAN).
3. CUT OPENINGS IN THE ROOF DECK ONLY FOR SUPPLY AND RETURN DUCT PENETRATIONS PER MANUFACTURER'S
DIMENSIONAL LAYOUT DRAWINGS. BATT INSULATION SHALL COVER THE ENTIRE AREA OUTLINED BY THE CURB AND IN
BETWEEN SUPPLY AND RETURN DUCTS.
4. MAINTAIN 10 LINEAL FEET BETWEEN OA INTAKE HOOD AND EXHAUST FANS, PLUMBING VENTS, ETC.
ROOF TOP UNIT DETAIL
NOT TO SCALE
RA
SA
CO2 SENSOR. PROVIDE
AS NOTED.
EXPOSED SPIRAL DUCT HANGER DETAIL
NOT TO SCALE
SECURE TO CURB WITH
STAINLESS STEEL SCREWS
8" O.C. ALL SIDES
PRIMARY CONDENSATE DRAIN- FULL SIZE OF UNIT
CONNECTION (3/4" MIN.) UNLESS NOTED
OTHERWISE. SLOPE 1/8"/FT. (OR SLOPE PER LOCAL
CODE) MIN. REFER TO FLOOR PLANS FOR ROUTING
DRAIN PAN
GALVANIZED FLASHING.
EXTEND 6" (MIN.) AND
SEAL WEATHERTIGHT
14" MIN ABOVE ROOF FINISHED SURFACE.
COORDINATE CURB HEIGHT WITH INSULATION
THICKNESS TO ACHIEVE THIS DIMENSION
ROOF CURB INSULATION
ROOF MEMBRANE.
RE: ARCH
DRYER EXHAUST WALL CAP
NOT TO SCALE
CONDENSATE TRAP PER DETAIL OR INSTALL
PER MANUFACTURER'S RECOMMENDATIONS
CONDENSATE OVERFLOW SWITCH IN
SECONDARY DRAIN; "SAFE-T-SWITCH"
OR EQUAL. INTERLOCK WITH AH TO
SHUT UNIT OFF IF LIQUID IS DETECTED
LINED RETURN AIR
PLENUM/DUCTWORK
(OR DUCTBOARD IF SPECIFIED)
NOTES:
1. STRUCTURE VARIES. COORDINATE WITH STRUCTURAL DOCUMENTS FOR PROPER ANCHORING METHOD (BEAM CLAMPS, EXPANSION BOLTS,
INSERTS, ETC.).
2. ON SERVICE SIDE OF UNIT, MAINTAIN A 42"W X LENGTH OF UNIT CLEARANCE TO PIPING, DUCTWORK, EQUIPMENT, CONDUIT, ETC. ELECTRIC HEAT
SECTIONS OR DUCT HEATERS: MAINTAIN A MIN. OF 42" CLEARANCE (OR PER N.E.C.) IN FRONT OF ALL ELECTRIC HEATER CONTROL PANELS. THE WIDTH
OF THE SERVICE CLEARANCE SHALL BE 30" OR THE WIDTH OF THE PANEL WHICHEVER IS GREATER. FOR LOW VOLTAGE CONTROL PANELS (WITHOUT
ELECTRIC HEATER), MAINTAIN A MIN. OF 24" CLEARANCE (OR PER N.E.C.) IN FRONT OF PANEL. THE WIDTH OF THE SERVICE CLEARANCE SHALL BE 24"
OR THE WIDTH OF THE PANEL WHICHEVER IS GREATER. NO PIPES, SPRINKLERS, CONDUITS, ETC. SHALL BE INSTALLED WITHIN THIS ZONE.
COORDINATE AND PLAN WORK CAREFULLY WITH ALL OTHER TRADES.
3. WHERE AHs OR THEIR WORKING CLEARANCE ARE LOCATED ABOVE LIGHT FIXTURES, THE FIXTURE SHALL HAVE A FLEXIBLE WHIP TO ALLOW
TEMPORARY RELOCATION OF THE FIXTURE FOR ACCESS TO THE AH. COORDINATE WITH ELECTRICAL CONTRACTOR.
4. PROVIDE MINIMUM SERVICE CLEARANCES AS RECOMMENDED BY UNIT MANUFACTURER.
SUSPENDED HORIZONTAL AIR HANDLING UNIT DETAIL
NOT TO SCALE
ISSUE FOR PERMIT
BID & CONSTRUCTION
SPIRAL DUCTWORK - ALL EXPOSED
SHEETMETAL SURFACES (SA & RA) AND
HANGAR STRAPS SHALL HAVE A "PAINT
GRIP" FINISH FOR FIELD PAINTING. AS AN
OPTION, MILL PHOSPHATIZED STEEL
DUCTWORK MAY BE USED. INTERNALLY
INSULATE PER HVAC GENERAL NOTES OR
SPEC SECTION 23 07 00 UNO.
NOTES:
1. PAINT COLOR SHALL BE
SELECTED BY
ARCHITECT.
2. PAINTING BY OTHERS.
COORDINATE WITH
ARCHITECTURAL DWGS.
TURNING VANE DETAILS
NOT TO SCALE
THREADED ROD WITH SPRING TYPE
VIBRATION ISOLATORS (SIZE RODS AND
SUPPORT UNIT AS RECOMMENDED BY
MANUFACTURER) (TYPICAL OF FOUR ONE PER CORNER). SEE NOTE 1
SMALL
NOTE:
TURNING VANES SHALL BE CONSTRUCTED PER SMACNA HVAC DUCT
CONSTRUCTION STANDARDS (2005 EDITION FIGURE 4-3).
ROOF CURB FRAMING MECHANICAL EQUIPMENT
FLEXIBLE DUCT CONNECTOR, TYP.
THERMOSTAT WIRING
DUCT SMOKE
DETECTOR PER CODE
LARGE
STEEL JOIST
NOT TO SCALE
BOLT AND NUT
TYPE 2 RUNNER
WELD EVERY SIXTH
VANE TO RUNNER
(OVER 1500 FPM)
2-1/4"
BURGLAR BARS, IF SPECIFIED
A
MINIMUM 1/8" 7x19 STRANDED
GALVANIZED AIRCRAFT CABLE
45°
STEEL ANGLES, ALL SIDES OF
ROOF OPENING - SEE
STRUCTURAL DWGS.
c
NOT TO SCALE
KEY PLAN
MIN. 24 GAUGE
VANES
STEEL DECK
PIPING SUPPORT (CONDENSATE)
KINETICS NOISE CONTROL "KIP-R1"
FIBERGLASS PAD CONTINUOUS BETWEEN
RTU AND CURB PER MANUFACTURER'S
RECOMMENDATIONS
POWER WIRING (SEE ELECTRICAL DWGS.)
3-1/4"
45°
NOT TO SCALE
LINE INSIDE OF CURB AND ROOF
DECK WITH KINETICS KNM-100C
ACOUSTICAL BARRIER
SUSPEND FROM STRUCTURE ABOVE
TURNBUCKLE
4-1/2"R
OUTDOOR UNIT ROOF MOUNTING DETAIL
FELTED SEMI-RIGID MINERAL
WOOL BATT INSULATION, 4 LB.
DENSITY, 8" THICK TOTAL
NOTE:
DETAIL SHOWN APPLIES TO 18"
MAXIMUM DUCT SIZE. FOR LARGER
SIZES REFER TO SMACNA HVAC DUCT
CONSTRUCTION STANDARDS.
2-1/8"
CANT
ROOF INSULATION
1'-2" MINIMUM
1. PLACE BASE SHEETS ON ROOFING BEFORE GRAVEL, IF ANY. SET BLOCKS FREE ON BASE
SHEETS.
STACK BLOCKS AND NAIL THEM TOGETHER WHERE REQUIRED TO ELEVATE PIPING.
2. SUPPORTS SHALL BE PLACED EVERY 6' ON CENTER (BASED ON SCHEDULE 40 PVC).
NOTES:
1. MIFAB PIPE SUPPORT TO HAVE 14 GA. X 3/16 " WIDE GALVANIZED CHANNEL. LENGTH TO SUIT QUANTITY OF
PIPING SUPPORTED. PROVIDE INSULATION SHIELD WHERE STRUT CLAMP COMES IN CONTACT WITH INSULATION.
2. EQUIPMENT SUPPORTS WITH THE FEWEST ROOF PENETRATIONS ARE PREFERRED HOWEVER, ALTERNATE
SYSTEMS BY MIRO OR CADDY PYRAMID ARE ACCEPTABLE PROVIDED THEY ARE INSTALLED IN A PERMANENT
MANNER AND SECURED TO THE ROOF STRUCTURE.
DISCONNECT SWITCH
(SEE ELECTRICAL
DWGS. UNLESS
FACTORY MOUNTED)
1-1/8"
2-1/4"
NOTES:
SOLID PLATFORM TYPE EQUIPMENT CURB BY ROOF
PRODUCTS AND SUPPORTS, INC.- SECURE TO ROOF
STRUCTURE PER MANUFACTURER'S
RECOMMENDATIONS
CONDENSER FAN
DISCHARGE
NOT TO SCALE
1-1/8"
SEAL OPENING AIR AND WATER
TIGHT WITH EXPANDING FOAM
INSULATION
ROOF STRUCTURE
ROOFING
PROVIDE MULTIPLE
BASE SHEETS OR
TRIM THE TIMBER
AS REQUIRED TO
ACCOMMODATE
VARIATIONS IN
ROOF ELEVATION.
NOT TO SCALE
c
PROVIDE FLASHING AND
COUNTERFLASHING AT
ROOFTOP UNIT BASE RAIL
INTEGRAL 2X WOOD NAILER
ROOF CURB BY ROOFTOP UNIT MANUFACTURER
SUPPORT PIPING 6' OC WITH MIFAB MODEL C PIPE
SUPPORT ON ROOFING WALKPAD MATERIAL SECURE
PIPE WITH PIPE CLAMP
18" x 18" x 1/2" THICK
ROOF WALKWAY MATERIAL
FOR BASE SHEET.
("CAREY-TRED" OR
PER ARCHITECTURAL
SPECIFICATIONS.)
SPIRAL DUCT THRU WALL DETAIL
3/4" x1/4" WIDE GASKET
AROUND
ENTIRE CURB FRAME
3/4"
NOTES:
1. WHEN SPECIFIED TO BE PAINTED, ALL EXPOSED SHEETMETAL SURFACES INCLUDING HANGER
STRAPS
SHALL HAVE A "PAINT GRIP" FINISH FOR FIELD PAINTING. AS AN OPTION, MILL PHOSPHATIZED STEEL
DUCTWORK MAY BE USED.
2. PAINT COLOR SHALL BE SELECTED BY ARCHITECT.
3. PAINTING BY OTHERS. COORDINATE WITH ARCHITECTURAL DWGS.
4. SECURE ESCUTCHEON TO DUCT WITH SHEETMETAL SCREWS AT 6" OC.
SPIRAL DUCT SUPPLY REGISTER DETAIL
ROOFTOP UNIT SHALL BE LEVEL AND
SHALL NOT SIT ON METAL DECK, BUT
ON STEEL ANGLES.
ROOF TOP UNIT
GALVANIZED STEEL PIPE CLAMP.
DO NOT CLAMP PIPE TIGHT.
c
NOTES:
1. PAINT COLOR SHALL BE SELECTED BY ARCHITECT.
2. PAINTING BY OTHERS. COORDINATE WITH ARCHITECTURAL DWGS.
NOT TO SCALE
WATERTIGHT
REFRIGERANT LINE
SET CHASE
SUPPORT RS & RL 6' OC WITH MIFAB
MODEL C PIPE SUPPORT ON ROOFING
WALKPAD MATERIAL - SECURE PIPE
WITH PIPE CLAMP
SA DUCTWORK - INTERNALLY LINED;
RA DUCTWORK - NO INSULATION;
OA DUCTWORK - EXTERNALLY
INSULATED; REFER TO HVAC GENERAL
NOTES OR SPEC SECTION 23 07 00 UNO.
TURN DOWN 30 DEGREES
NOT TO SCALE
SECURE OUTDOOR UNIT TO CURB PER
MANUFACTURER'S RECOMMENDATIONS,
TYP. 4 LOCATIONS. SEAL SCREW HOLES
WITH 20-YR SILICONE SEALANT
CONCEALED AREA (DUCT ROUTED
ABOVE CEILING)
FOLD SHEET METAL
ENDS DOWN 1"
COMMERCIAL
FLEXIBLE DUCT TAKE-OFF DETAIL
CONDENSATE DRAIN TRAP DETAIL
ARM
20 GAUGE SHEETMETAL
ESCUTCHEON PLATE (TO COVER
ENTIRE OPENING) FOR A CLEAN
AND NEAT APPEARANCE
FILL ANNULAR SPACE
WITH MINERAL WOOL
SUPPLY
DIFFUSER
OR REGISTER
CEILING - SEE ARCH.
DWGS. FOR TYPE
WALL
SUPPLY DUCTWORK
(CONCEALED)
EXPOSED AREA (DUCT ROUTED IN
SPACE)
SUPPLY REGISTER
BRANCH DUCT
NOTES:
1. SLOPE PIPING DOWN TOWARDS PLUMBING DRAIN AT 1/8 " PER FOOT.
2. RUNNING TRAPS ARE NOT ALLOWED.
3. TEST THE FLOAT SWITCH IN THE DRAIN PAN FOR PROPER OPERATION AT LEAST ONCE A YEAR.
VOLUME DAMPER SHAFT
RAISED PANEL
1/ " PLATE FOR DUCTS UP TO 18"
16
1/ " PLATE FOR DUCTS 19" AND UP
8
SPIRAL SUPPLY DUCTWORK ALL EXPOSED SHEETMETAL SURFACES (SA &
RA) AND HANGAR STRAPS SHALL HAVE A "PAINT
GRIP" FINISH FOR FIELD PAINTING. AS AN
OPTION, MILL PHOSPHATIZED STEEL
DUCTWORK MAY BE USED. INTERNALLY
INSULATE PER HVAC GENERAL NOTES OR SPEC
SECTION 23 07 00 UNO.
MECHANICAL FASTENER
INSULATION
PROVIDE SPACE FOR ELECTRICAL
CONDUIT BETWEEN DAMPER AND
ROOF OPENING
1991 FM 158, BRYAN, TX 77845
QUADRANT
3/ " FOR DUCTS UP TO 18"
8
1/ " FOR DUCTS 19" THRU 48"
2
CONNECT FLEX DUCT ENDS TO SHEET METAL
DUCT AND DIFFUSER NECK WITH NYLON ZIP TIES.
APPLY A BEAD OF MASTIC BETWEEN THE INTERIOR
LINER AND THE SHEETMETAL PRIOR TO ZIP-TYING.
THE INTERIOR LINER AND EXTERIOR INSULATION
OF THE FLEX DUCT SHALL BE ZIP-TIED
INDIVIDUALLY. INSTALL ZIP TIES USING A
TENSIONING TOOL PER MANUFACTURER'S
RECOMMENDATIONS
2808 Fairmount Street, Suite 300
Dallas, Texas 75201 | 214.303.1500
FACTORY DRAIN PAN
SUSPEND FROM STRUCTURE - REFER TO
EXPOSED SPIRAL DUCT HANGER DETAIL
CENTRAL BAPTIST CHURCH
CHILDRENS BUILDING
TRAP AND PIPE SAME SIZE AS UNIT
CONNECTION - ROUTE TO
NEAREST PLUMBING DRAIN SEE PLANS FOR CONTINUATION
HAND TIGHT PLUGS FOR
CLEANOUT PURPOSES
3300 West 7th Street, Suite 110
Fort Worth, Texas 76107 | 817.303.1500
FLOAT SWITCH WIRED TO SHUT DOWN
RTU; SAF-T-SWITCH MODEL SS3
SCREWS
DUCT INSULATION
ROOF TOP
UNIT
ROOF DECK, RE: STRUCT.
BACKDRAFT
DAMPER
(SEE NOTE 3)
FLEX. CONNECTOR
LINE INSIDE OF CURB AND ROOF
DECK WITH KINETICS KNM-100C
ACOUSTICAL BARRIER
ROOF CURB
CAULK TO FILL GAP
CONTINUOUS BENT
DUCT FLANGE
ROOF
CURB
ROOF
EXHAUST DUCT SIZE AS SHOWN
ON PLANS. DUCT SHALL
EXTEND UP TO ROOF
EXHAUSTER OPENING. DUCT
SHALL NOT TERMINATE BELOW
ROOF.
RADIUS ELBOW (WHERE
REQUIRED FOR DUCT
OFFSET)
COVER OPENING
WITH 1/2''x1/2"
HARDWARE CLOTH,
0.135'' WIRE
NOTES:
1. SEAL PENETRATION AIR TIGHT AROUND CONDUIT THRU WELDED ROOF CURB.
2. SEAL AIR TIGHT ANY PENETRATIONS THROUGH WELDED ROOF CURB.
3. WITH THE EXCEPTION OF KITCHEN GREASE EXHAUST FANS, PROVIDE MOTORIZED DAMPER FOR ALL EXHAUST FANS
WITH CAPACITY 300 CFM AND GREATER.
ROOF MOUNTED EXHAUST FAN
NOT TO SCALE
ROOF DECK
RADIUS ELBOWS SHALL BE
USED ON ALL SUPPLY DUCT
TURNS WHEN POSSIBLE. IF
RADIUS ELBOWS CANNOT BE
USED, MITERED ELBOWS WITH
TURNING VANES MAY BE
SUBSTITUTED.
No. Date
Revision
RAC
Drawn
SMOKE DETECTOR.
PROVIDE AS NOTED.
(TYP.)
ROOF TOP UNIT MOUNTING DETAIL
JRM
Checked
WAS
Approved
NOT TO SCALE
DETAILS MECHANICAL
Project No.
Date
Last Revision
15187.00
05/11/2016
M-103
printed5/11/2016 12:26:10 PM
RTU SEQUENCE OF OPERATION
3300 West 7th Street, Suite 110
Fort Worth, Texas 76107 | 817.303.1500
RECTANGULAR
SUPPLY, RETURN OR
EXHAUST DUCT
RECTANGULAR
SUPPLY, RETURN OR
EXHAUST DUCT
RECTANGULAR
BRANCH
DUCT TAKE-OFF
LOW PRESSURE
BRANCH DUCT TAKE-OFF
(RECTANGULAR 45° ENTRY)
LOW PRESSURE
BRANCH DUCT TAKE-OFF
(ROUND BRANCH ENTRY)
NOT TO SCALE
NOT TO SCALE
SA AIRFLOW
SA AIRFLOW
e.
Morning Warm-Up Mode:
During optimal start, if the space temperature is below the occupied heating setpoint a morning warm-up mode shall be activated. When
morning warm-up is initiated the unit shall enable the heating and supply fan. The outside air damper shall remain closed. When the space
temperature reaches the occupied heating setpoint (adj.), the unit shall transition to the occupied mode.
f.
Pre-Cool Mode:
During optimal start, if the space temperature is above the occupied cooling setpoint, pre-cool mode shall be activated. When pre-cool is
initiated the unit shall enable the fan and cooling or economizer. The outside air damper shall remain closed, unless economizing. When the
space temperature reaches occupied cooling setpoint (adj.), the unit shall transition to the occupied mode.
RA & EA AIRFLOW
g.
Optimal Stop:
The BAS shall monitor the scheduled unoccupied time, occupied setpoints and space temperature to calculate when the optimal stop
occurs. When the optimal stop mode is active the unit controller shall maintain the space temperature to the space temperature offset
setpoint.
RA & EA AIRFLOW
SHOP
FABRICATED
90° CONICAL
FITTING
h.
Occupied Bypass:
The BAS shall monitor the status of the “on” and “cancel” buttons of the space temperature sensor. When an occupied bypass request is
received from a space sensor, the unit shall transition from its current occupancy mode to occupied bypass mode and the unit shall maintain
the space temperature to the occupied setpoints (adj.).
i.
Cooling Mode:
The unit controller shall use space temperature and space temperature setpoint to determine when to initiate requests for cooling. When the
space temperature rises above the setpoint, the unit controller shall modulate the economizer or stage the DX cooling as required to
maintain the space temperature setpoint. The first compressor shall energize after its minimum 3-minute off time has expired. If additional
cooling capacity is required the second stage of cooling shall be enabled. Once the space temperature falls below the setpoint the
compressors shall be deactivated and the economizer shall return to minimum position.
SHOP
FABRICATED
45° CONICAL
FITTING
NOTE:
1. ACCEPTABLE ALTERNATES ARE CONICAL TAPS AND CONICAL
SADDLE TAPS PER SMACNA HVAC DUCT CONSTRUCTION
STANDARDS.
j.
Heating Mode:
The unit controller shall use the space temperature and space temperature setpoint to determine when to initiate requests for heat. When
the space temperature drops below the setpoint, the unit controller shall enable electric heating stages to maintain the space temperature
setpoint. Once the space temperature rises above the setpoint the electric heating stages shall be disabled.
k.
Dehumidification:
Factory installed hot gas reheat shall allow application of dehumidification. Dehumidification shall be allowed only when the outside air
temperature is above 40.0 deg. F and below 100.0 deg. F. The economizer outside air damper shall drive to minimum position during
dehumidification.
2808 Fairmount Street, Suite 300
Dallas, Texas 75201 | 214.303.1500
CONICAL TAP
(SPIN-IN OR
FLANGED)
L = 1/4W, 4" MIN.
d.
Optimal Start:
The BAS shall monitor the scheduled occupied time, occupied space setpoints and space temperature to calculate when the optimal start
occurs.
SA AIRFLOW
ROUND
BRANCH DUCT
TAKE-OFF
L
c.
Unoccupied Mode:
When the space temperature is below the unoccupied heating setpoint of 60.0 deg. F (adj.) the supply fan shall start, the outside air damper
shall remain closed and the electric heat shall be enabled. When the space temperature rises above the unoccupied heating setpoint of 60.0
deg. F (adj.) plus the unoccupied differential of 4.0 deg. F (adj.) the supply fan shall stop and the electric heat shall be disabled.
When the space temperature is above the unoccupied cooling setpoint of 85.0 deg. F (adj.) the supply fan shall start, the outside air damper
shall open if economizing is enabled and remain closed if economizing is disabled and the DX cooling shall be enabled. When the space
temperature falls below the unoccupied cooling setpoint of 85.0 deg. F (adj.) minus the unoccupied differential of 4.0 deg. F (adj.) the supply
fan shall stop, the DX cooling shall be disabled and the outside air damper shall close.
RA & EA AIRFLOW
b.
Occupied Mode:
During occupied periods, the supply fan shall run continuously and the outside air damper shall open to maintain minimum ventilation
requirements. The DX cooling and electric heat shall stage to maintain the occupied space temperature setpoint. If economizing is enabled
the outside air damper shall modulate to maintain the occupied space temperature setpoint.
MVD
RA & EA AIRFLOW
W
a.
Building Automation System Interface:
The Building Automation System (BAS) shall send the controller Occupied Bypass, Morning Warm-up / Pre-Cool, Occupied / Unoccupied
and Heat / Cool modes. If a BAS is not present, or communication is lost with the BAS the controller shall operate using default modes and
setpoints.
SA AIRFLOW
MVD
NOTE:
1. ACCEPTABLE ALTERNATES ARE CONICAL TAPS AND CONICAL
SADDLE TAPS PER SMACNA HVAC DUCT CONSTRUCTION
STANDARDS.
LOW PRESSURE
BRANCH DUCT TAKE-OFF (ALTERNATIVE
ROUND 90° BRANCH)
LOW PRESSURE
BRANCH DUCT TAKE-OFF (ALTERNATIVE
ROUND 45° BRANCH)
NOT TO SCALE
NOT TO SCALE
KEY PLAN
A
B
l.
Single compressor units:
On a call for dehumidification, the reheat valve shall energize and the compressor shall enable. When the humidity control setpoint is
satisfied, the valve shall be de-energized and the compressor shall be disabled. If there is a call for cooling from the space temperature
controller, while in reheat, the reheat valve shall be de-energized and the compressor continues to run.
ISSUE FOR PERMIT
BID & CONSTRUCTION
2W
WALL - SEE ARCH.
DWGS. FOR TYPE
DOUBLE
THICKNESS
TURNING VANES
n.
Economizer:
The mixed air sensor shall measures the dry bulb temperature of the air leaving the evaporator coil while economizing. When economizing is
enabled and the unit is operating in the cooling mode, the economizer damper shall be modulated between its minimum position and 100% to
maintain the space temperature setpoint. The economizer damper shall modulate toward minimum position in the event the mixed air
temperature falls below the low limit temperature setting. Compressors shall be delayed from operating until the economizer has opened to
100%.
MVD
STEEL LINTEL, IF
REQUIRED - SEE
STRUCT./ARCH. DWGS.
MVD
W
HEAD FLASHING
W
o.
Reference Dry Bulb:
Outside air (OA) temperature shall compared with a reference dry bulb setpoint. The economizer shall enable when the OA temperature is
less than reference dry bulb setpoint. The economizer shall be disabled when OA temperature is greater than reference dry bulb setpoint +
5.0 deg. F.
ALUMINUM ANGLE
AROUND PERIMETER SECURE TO WALL &
LOUVER
LOUVER
p.
Supply Fan:
The supply fan shall be enabled while in the occupied mode and cycled on during the unoccupied mode. A differential pressure switch shall
monitor the differential pressure across the fan. If the switch does not open within 40 seconds after a request for fan operation a fan failure
alarm shall be annunciated at the BAS, the unit shall stop, requiring a manual reset.
SUPPLY, RETURN
OR EXHAUST DUCT
2W
BIRD SCREEN
q.
Building Pressure Control:
The power exhaust shall enable when the economizer damper position is equal to or greater than the exhaust fan setpoint.
90°
r.
Filter Status:
A differential pressure switch shall monitor the differential pressure across the filter when the fan is running. If the switch closes for 2
minutes after a request for fan operation a dirty filter alarm shall be annunciated at the BAS.
SEAL AROUND
ENTIRE PERIMETER
TO MAKE WATERTIGHT
CENTERLINE RADIUS = 1.5 x 2W
MVD
MVD
MOUNTING AND
LINKAGE
HARDWARE FOR
ELECTRIC ACTUATOR
(PROVIDE CONCEALED
ACTUATOR/ LINKAGE IN
SILL AS REQUIRED FOR
FLUSH INTERIOR
INSTALLATION)
W
W
DRIP SILL AND
FLASHING
NOTE:
ARCH. DWGS. AND
MANUFACTURER'S
INSTALLATION
MANUAL SUPERCEDE THIS DWG.
DIVIDED FLOW FITTING DETAILS
WALL LOUVER DETAIL
NOT TO SCALE
NOT TO SCALE
ROUTE DRYER EXHAUST DUCT TO
EXTERIOR WALL IN THE MOST
DIRECT MANNER POSSIBLE
2
RTU POINTS LIST
4" ROUND DRYER EXHAUST DUCT
SHALL BE A MINIMUM OF 26 GAUGE
20 GAUGE GALVANIZED SHEET METAL
HOOD - PAINT IN A COLOR SELECTED
BY ARCHITECT.
Scale: 1" = 1'-0"
LINE INTERIOR OF
SHEET METAL HOOD
WITH DUCT LINER
PROVIDE WATERPROOF
SEALANT BETWEEN SLEEVES
AND PIPES
16 GAUGE (MIN.)
EQUIPMENT
CURB
SLOPE PIPING
AWAY FROM HOOD
1991 FM 158, BRYAN, TX 77845
SUPPLY, RETURN OR
EXHAUST DUCT
CENTRAL BAPTIST CHURCH
CHILDRENS BUILDING
m.
Dual compressor units:
On a call for dehumidification, the reheat valve shall energize and both compressors shall enable. When the humidity control setpoint is
satisfied, the valve shall be de-energized and both compressors shall be disabled. If there is a call for 1st stage cooling while in the
dehumidification mode, no action shall take place. If there is a call for 2nd stage cooling, the reheat valve shall be de-energized, and the unit
shall revert to the cooling mode. If 2nd stage cooling is satisfied and there is still a call for dehumidification, the reheat valve shall once again
be energized.
EXTEND 4" DRYER EXHAUST
DUCT THRU DRYER EXHAUST BOX
TO ALLOW CONNECTION FOR
FLEXIBLE DRYER HOSE
METAL FLANGE
SECURE EXHAUST BOX TO WALL
PER MANUFACTURER'S
RECOMMENDATIONS
FLEXIBLE DRYER
HOSE BY INSTALLER
DRYER EXHAUST WALL BOX REFER TO PLANS FOR EXACT
LOCATION AND SEE NOTES BELOW
FOR ADDITIONAL INFORMATION
ROOF DECK
1-1/4"x1-1/4"x1/4"
ANGLE FRAMING
ROOFING CONTRACTOR
TO INSTALL ROOF
CURB.
MECH. CONTRACTOR
SHALL SUPERVISE THE
INSTALLATION
AND PAY ALL COSTS.
SECURE PIPE TO WALL
AND SUPPORT AT BASE
1-1/4"x 1-1/4"x 1/4" ANGLE FRAMING
No. Date
PIPE CURB DETAIL
NOT TO SCALE
NOTES:
1. DRYER EXHAUST BOX MODEL 425 AS MANUFACTURED BY IN-O-VATE TECHNOLOGIES; LISTED FOR 1-HR (F AND
T RATINGS) WALL INSTALLATION; UL THROUGH-PENETRATION FIRESTOP SYSTEM NO. W-L-7129. USE FOR UPWARD
EXHAUST DIRECTION AND DOWNWARD EXHAUST DIRECTION ONLY FOR PEDESTAL AND STACKING DRYERS.
2. FOR DOWNWARD EXHAUST DIRECTION USE THE MODEL 4D (EXCEPT FOR PEDESTAL AND STACKABLE DRYERS).
3. INSTALLATION REQUIRES THE SPACES BETWEEN THE SIDES OF THE BOX AND THE STUDS AND THE SPACE
IMMEDIATELY ABOVE THE BOX TO BE TIGHTLY PACKED WITH GLASS FIBER BATT OR MINERAL WOOL BATT
INSULATION. REFER TO UL INSTALLATION DETAILS FOR ADDITIONAL INFORMATION.
4. INSTALL 16 GA STEEL SHIELD PLATES AT THE FINISHED FACE OF FRAMING MEMBERS WHERE THERE IS LESS THAN
1 1/4 " BETWEEN THE DUCT AND THE FINISHED FACE OF THE FRAMING. SHIELD PLATES SHALL EXTEND 2" ABOVE
SOLE PLATES AND 2" BELOW TOP PLATES.
Revision
RAC
Drawn
JRM
Checked
WAS
Approved
DRYER EXHAUST WALL BOX DETAIL
NOT TO SCALE
DETAILS MECHANICAL
Project No.
Date
Last Revision
15187.00
05/11/2016
M-104
printed5/11/2016 12:26:14 PM
KEYVALUE
1
2
3
4
5
6
7
1.
CONTRACTOR SHALL MAINTAIN A MINIMUM OF 36" IN FRONT OF ALL ELECTRICAL DISCONNECTS.
2.
CONTRACTOR SHALL OBSERVE ALL MANUFACTURER CLEARANCE AND INSTALLATION GUIDELINES FOR MECHANICAL
EQUIPMENT.
3.
CONDENSATE FROM COOLING COILS SHALL BE COLLECTED PER LOCAL CITY REQUIREMENTS.
4.
MATERIALS, EQUIPMENT OR LABOR NOT INDICATED BUT WHICH CAN BE REASONABLY INFERRED TO BE NECESSARY FOR A
COMPLETE INSTALLATION SHALL BE PROVIDED. DRAWINGS AND SPECIFICATIONS DO NOT UNDERTAKE TO INDICATE
EVERY ITEM OF MATERIAL, EQUIPMENT, OR LABOR REQUIRED TO PRODUCE A COMPLETE AND PROPERLY OPERATING
INSTALLATION.
5.
THE DRAWINGS ARE DIAGRAMMATIC AND DO NOT NECESSARILY DEPICT EXACT CONDITIONS. THE LOCATION OF
EQUIPMENT, DUCTWORK, ETC. IS APPROXIMATE ONLY. THE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT TO BE
SCALED. SCALES ARE SHOWN FOR REFERENCE AND APPROXIMATION ONLY. REFER TO THE ARCHITECTURAL DRAWINGS
FOR DIMENSIONAL DATA OF BUILDING COMPONENTS.
6.
INSTALL ALL DUCTWORK AS TIGHT TO STRUCTURE AS POSSIBLE, IN ORDER TO MAXIMIZE CEILING HEIGHTS.
7.
PROVIDE ALL OFFSETS AND TRANSITIONS IN DUCTWORK AS NEEDED TO MAINTAIN CEILING HEIGHTS AND TRANSITION
OVER OR UNDER DUCTWORK AND OTHER BUILDING SYSTEMS, WHETHER SHOWN ON DRAWINGS OR NOT.
8.
COORDINATE DUCTWORK WITH STRUCTURE, LIGHTING, SPRINKLERS, ETC. PRIOR TO CONSTRUCTION.
9.
CONTRACTOR SHALL MAKE EVERY EFFORT TO INSTALL DUCTWORK IN ORDER TO MINIMIZE DUCT TRANSITIONS, FITTINGS,
AND ELBOWS AS MUCH AS POSSIBLE TO REDUCE SYSTEM STATIC PRESSURE.
10.
ROUND AND RECTANGULAR ELBOWS SHALL BE IN STRICT CONFORMANCE OF THE SPECIFICATIONS. SEGMENTED
ELBOWS ARE NOT ALLOWED.
11.
CONVERGING AND DIVERGING AIRFLOWS SHALL BE PROVIDED WITH FITTINGS CONFORMING TO SMACNA'S "HVAC DUCT
CONSTRUCTION STANDARDS - METAL AND FLEXIBLE", LATEST EDITION, TO MINIMIZE SYSTEM PRESSURE DROP.
12.
NOT ALL VOLUME CONTROL DAMPERS ARE INDICATED ON THE DRAWINGS. PROVIDE DAMPERS PER THE SPECIFICATIONS
AND AS REQUIRED FOR BALANCING MAIN AND BRANCH TAKE-OFF AIRFLOWS TO THE DOWNSTREAM CFM SHOWN.
13.
CONTRACTOR SHALL BE RESPONSIBLE FOR PREPARING COORDINATION DRAWINGS TO SCALE, AS REQUIRED, USING
INPUT FROM ALL OTHER TRADES PRIOR TO FABRICATION AND INSTALLATION OF DUCTWORK. CONTRACTOR DRAWINGS
SHALL INDICATE DUCT INSTALLATION IN CONGESTED SPACES, INDICATING COORDINATION WITH GENERAL
CONSTRUCTION, BUILDING COMPONENTS, CEILING ELEVATIONS, AND OTHER BUILDING SERVICES. INDICATE PROPOSED
CHANGES TO DUCT LAYOUT.
14.
MOUNT THERMOSTATS AT 46" AFF AND 8" FROM THE EDGE OF THE WALL. COORDINATE LOCATIONS WITH OWNER AND
ARCHITECT PRIOR TO INSTALLATION.
15.
PROVIDE 1" DOOR UNDERCUT UNDER RESTROOM DOORS FOR MAKEUP AIR.
3300 West 7th Street, Suite 110
Fort Worth, Texas 76107 | 817.303.1500
KEYNOTES(THISSHEET)
GENERAL NOTES
NOTE
OFFSET, TRANSITION AND CONNECT SUPPLY AND RETURN DUCTWORK UP TO ROOFTOP UNIT.
OFFSET, TRANSITION AND CONNECT EXHAUST DUCT UP TO FAN ON ROOF.
REFER TO ARCHITECTURAL ELEVATIONS FOR AIR DEVICE LOCATIONS.
REFER TO ARCHITECTURAL FOR LOUVER LOCATIONS. MAINTAIN 10' BETWEEN INTAKE AND EXHAUST.
CONDENSATE DRAIN DOWN TO TAILPIECE. COORDINATE WITH PLUMBING FOR LOCATION.
ROUTE RETURN DUCT BELOW SUPPLY AND TURN UP TO CONNECT GRILLES TO BOTTOM OF DUCT.
ROUTE CONDENSATE TO HUB DRAIN ABOVE CEILING. TERMINATE 1" ABOVE DRAIN. REFER TO PLUMBING FOR EXACT
LOCATION.
ROUTE DUCT BELOW STRUCTURE. TURN UP AFTER STRUCTURE TO AVOID CONFLICTS WITH CEILING, LIGHTS, ETC.
SLOPE DOWN AND ROUTE DUCT BELOW JOIST. TRANSITION TO ROUND DUCT AND TURN UP AFTER WALL
PENETRATION.
RETURN DUCT OPEN TO PLENUM. PROVIDE WIRE MESH SCREEN ON OPENING.
ROUTE RETURN DUCTWORK BELOW SUPPLY DUCTWORK. OFFSET, TRANSITION AND CONNECT TO RETURN GRILLE.
RETURN DUCT TURNED UP AFTER JOIST.
8
9
2808 Fairmount Street, Suite 300
Dallas, Texas 75201 | 214.303.1500
10
11
12
KEY PLAN
B
C
C.1
D
C.9
D.8
E
E.6
F
F.1
G G.1 G.2
G.7
H
H.1 H.5
J
J.8
K
A
B
235
A
10"ø
235
A
10"ø
235
A
10"ø
24x20 SA
12x14 SA
A
260
10"ø
CLASSROOM
A116
235
A
10"ø
235
A
10"ø
235
A
10"ø
A
12x12 SA
CLASSROOM
A112
16x16
A
16x16
C
A
230
10"ø
230
10"ø
A
16x16
C
1" CD
CORRIDOR
A100d
DN
DN
12"ø SA
230
10"ø
230
10"ø
A
CLASSROOM
A111
T
RTU-2
230
A
10"ø
1" CD
1
335
10"ø
C
B
16x16
7
A
34x26 SA
CLASSROOM
A117
F
8x8
18x20 SA 24x20 SA
335
10"ø
D
STORAGE
A118
38x24 RA
200
E
8x8
DN
18x12 SA
24x14 SA
9
DN
18x12 SA
T
9
DN
F
RTU-3
20"ø SA
3
16"ø SA
BOD 12'-0" AFF
46x34
DN
E
290
10x10
450 BOYS RR
10x10 A122
180
8"ø
12x10 EA
CLASSROOM
A110
14x14 SA
1" CD
DN
DN
18x12 SA
9
9
DN
35
B
6"ø
DN
DN
UNSX RR
A120
195
E
10x10
195
E
10x10
E
BOD 12'-0"
AFF
195
10x10
415
E
10x10
290
E
18"ø SA 10x10
E
290
10x10
195
E
10x10
75
D
6x6
35
6"ø
18x12 SA
9
UNSX RR
A121
B
E
12"ø SA
12"ø SA
E
295
E
10x10
295
E
10x10
9
170
10x10
9
UNSX RR
WAH
A126
4
170
E
10x10
260
E
10x10
18"ø SA
20"ø SA
BOD 12'-0" AFF
540
12"ø
E
195
10x10
E
195
10x10
E
295
10x10
195
10x10
180
10x10
E
180
10x10
195
10x10
4TH-5TH LARGE
GROUP
A119
12"ø SA
295
E
10x10
E
E
180
E
10x10
250
10x10
E
250
10x10
38x26 RA
1
34x26 SA
A
250
10"ø
E
9
ISSUE FOR PERMIT
BID & CONSTRUCTION
C
16x16
C
16x16
WL
2
1" CD
24x24
35
6"ø
F
UNSX
RR
42x30
A128
260
E
10x10
170
E
10x10
B
F
42x30
RTU-4
9
3
260
E
10x10
260
10x10
E
3
C
20"ø SA
265
10x10
E
265
10x10
E
E
12x12 SA
200
A
8"ø
265
10x10
E
20x18 RA
265
E
10x10
180
10x10
300
10x10
E
300
10x10
E
E
C
180
10x10
16x16
100
A
6"ø
300
10x10
250
E
10x10
2
RE: M-202
12"ø SA
8x12 EA
12x12 EA
A
540
12"ø
14x12 EA
E
180
10x10
10x8 EA
T
RTU-11
EF
7
AH-3
H
20x20
CLASSROOM
A104
E
250
10x10
D
C
24x24
2300
48x18
E
310
310
A
10"ø
10"ø
8x10 SACLASSROOM
A103
225
D
8x8
105
B
6"ø
GIRLS RR
A102
26x16 RA
6x10 SA
1" CD
BOYS RR
A101
105
B
6"ø
10x8 EA
20x22 RA
A
75
6"ø
7
5
AQUARIUM
SERVICE
103
COMMONS
101
3
75
6x6
UNISEX RR
104
40
B
6"ø
D
1
5
5
1
225
8x8
DN
40
B
6"ø
3
UNISEX RR
105
2300
E
48x18
75
D
6x6
DN
44x16 RA
RTU-10
44x16 SA
6
26x26 RA
6
8
T
12x14 EA
1" CD
T
20x20 SA
RTU-5
STOR
A130
10
310
10"ø
520
A
12"ø
12"ø SA
E
3
12x14 SA
T
8
12x12 SA
12
A
11
265
E
10x10
300
10x10
3/4" CD
C
16x16
A
12"ø SA
LIBRARY
102
AH
1
6"ø SA
1
CORR
A100b
8x6 EA
14"ø SA
180
10x10
12x12 SA
F
48x18
310
10"ø
M
6"ø EA
400
18x8
30x14 RA
A
265
10x10
E
265
E
10x10
265
E
10x10
100
A
6"ø
10
210
8"ø
10"Ø OA
3
18x18 SA
DN
8
24x22 RA
VEST
115
A
14x18 RA
12"ø SA
1
M
10x10 SA
16x16 SA
170
10x10
135
8"ø
(TYP 5)
2
BOD 12'-0" AFF
K-3RD LARGE
GROUP
A124
T
CORR
A100a
210
8"ø
A
E
UNSX RR
A129
18"ø SA
BOD 12'-0" AFF
18"ø SA
E
16x16
6x10 SA
16x20 SA
35
B
20x14 SA 6"ø
9
4
G
200
STORAGE
E
8x8
A127
75
75
D
D
6x6 6x6 EA
6x6
34x18 RA
24x14 SA
8
4
16x16 RA
24x22 SA
WL
1
CLASSROOM
A105
1
295
10x10
RTU-6
RE: M-201
250
10"ø
18"ø SA
180
10x10
E
22x20 SA
540
12"ø
230
10"ø
C
12"ø SA
E
A
12x12 SA CLASSROOM
A107
18x16 RA
12"ø SA
520
12"ø
12"ø SA
E
A
CLASSROOM
A109
230
10"ø
34x18 RA
F
12x10
BOD 12'-0" AFF
14"ø SA
CORR
A100e
290
E
10x10
250
10"ø
1" CD
T
12"ø SA
12"ø SA
295
10x10
35
B
6"ø
16"ø SA
195
10x10
CLASSROOM
A108
E
415
E
10x10
E
75
D
6x6
35
B
6"ø
UNSX RR
A125
BOD 12'-0"
AFF
E
A
200
E
8x8
16x20 SA
75
24x14 SA
D
6x6
20x14 SA
ELEC
3/4" CD
A127a
16x16 SA
195
10x10
26x20 RA
A
A
24x22 SA
E
290
E
10x10
235
A
10"ø
5
16"ø SA
195
E
10x10
A
235
10"ø
16x16 SA
20x18 RA
GIRLS RR
450
D
A123
12x12
8x10 EA
A
BOD 12'-0" AFF
180
B
8"ø
A
16x16
C
12x10 EA
16x14 EA
75
D
6x6
18x20 SA 14x18 SA
195
E
10x10
BOD 12'-0" AFF
235
A
10"ø
18x18 SA 1
16x16
C
6x10 SA
16"ø SA
290
E
10x10
235
10"ø
16x16 SA
2
24x22 SA
DN
A
C
16x16
7
A
235
10"ø
24x20 SA
C
540
A
12"ø
235
A
10"ø
12x12 SA
24x16 RA
CLASSROOM
A115
T
235
A
10"ø
16x14 SA
26x20 RA
CLASSROOM
CLASSROOM
A113
A114
1
RTU-1
C
24x24
235
A
10"ø
18x18 SA
16x16 SA
C
16x16 A 230
10"ø
C
16x16
235
A
10"ø
235
A
10"ø
1991 FM 158, BRYAN, TX 77845
270
A
10"ø
CENTRAL BAPTIST CHURCH
CHILDRENS BUILDING
270
A
10"ø
26x16 RA
34x20 SA
RE: M-201
RE: M-202
5.8
No. Date
Revision
RAC
Drawn
JRM
1
FLOOR PLAN - AREA A MECHANICAL
Checked
WAS
Approved
Scale: 3/32" = 1'-0"
FLOOR PLAN
AREA A MECHANICAL
Project No.
Date
Last Revision
15187.00
05/11/2016
M-201
TRUE NORTH
PLAN NORTH
printed5/11/2016 12:26:24 PM
3300 West 7th Street, Suite 110
Fort Worth, Texas 76107 | 817.303.1500
KEYNOTES(THISSHEET)
GENERAL NOTES
1.
CONTRACTOR SHALL MAINTAIN A MINIMUM OF 36" IN FRONT OF ALL ELECTRICAL DISCONNECTS.
2.
CONTRACTOR SHALL OBSERVE ALL MANUFACTURER CLEARANCE AND INSTALLATION GUIDELINES FOR MECHANICAL
EQUIPMENT.
KEYVALUE
1
2
3
4
CONDENSATE FROM COOLING COILS SHALL BE COLLECTED PER LOCAL CITY REQUIREMENTS.
4.
MATERIALS, EQUIPMENT OR LABOR NOT INDICATED BUT WHICH CAN BE REASONABLY INFERRED TO BE NECESSARY FOR A
COMPLETE INSTALLATION SHALL BE PROVIDED. DRAWINGS AND SPECIFICATIONS DO NOT UNDERTAKE TO INDICATE
EVERY ITEM OF MATERIAL, EQUIPMENT, OR LABOR REQUIRED TO PRODUCE A COMPLETE AND PROPERLY OPERATING
INSTALLATION.
5.
THE DRAWINGS ARE DIAGRAMMATIC AND DO NOT NECESSARILY DEPICT EXACT CONDITIONS. THE LOCATION OF
EQUIPMENT, DUCTWORK, ETC. IS APPROXIMATE ONLY. THE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT TO BE
SCALED. SCALES ARE SHOWN FOR REFERENCE AND APPROXIMATION ONLY. REFER TO THE ARCHITECTURAL DRAWINGS
FOR DIMENSIONAL DATA OF BUILDING COMPONENTS.
6.
INSTALL ALL DUCTWORK AS TIGHT TO STRUCTURE AS POSSIBLE, IN ORDER TO MAXIMIZE CEILING HEIGHTS.
7.
PROVIDE ALL OFFSETS AND TRANSITIONS IN DUCTWORK AS NEEDED TO MAINTAIN CEILING HEIGHTS AND TRANSITION
OVER OR UNDER DUCTWORK AND OTHER BUILDING SYSTEMS, WHETHER SHOWN ON DRAWINGS OR NOT.
8.
COORDINATE DUCTWORK WITH STRUCTURE, LIGHTING, SPRINKLERS, ETC. PRIOR TO CONSTRUCTION.
9.
CONTRACTOR SHALL MAKE EVERY EFFORT TO INSTALL DUCTWORK IN ORDER TO MINIMIZE DUCT TRANSITIONS, FITTINGS,
AND ELBOWS AS MUCH AS POSSIBLE TO REDUCE SYSTEM STATIC PRESSURE.
10.
ROUND AND RECTANGULAR ELBOWS SHALL BE IN STRICT CONFORMANCE OF THE SPECIFICATIONS. SEGMENTED
ELBOWS ARE NOT ALLOWED.
11.
CONVERGING AND DIVERGING AIRFLOWS SHALL BE PROVIDED WITH FITTINGS CONFORMING TO SMACNA'S "HVAC DUCT
CONSTRUCTION STANDARDS - METAL AND FLEXIBLE", LATEST EDITION, TO MINIMIZE SYSTEM PRESSURE DROP.
12.
NOT ALL VOLUME CONTROL DAMPERS ARE INDICATED ON THE DRAWINGS. PROVIDE DAMPERS PER THE SPECIFICATIONS
AND AS REQUIRED FOR BALANCING MAIN AND BRANCH TAKE-OFF AIRFLOWS TO THE DOWNSTREAM CFM SHOWN.
13.
CONTRACTOR SHALL BE RESPONSIBLE FOR PREPARING COORDINATION DRAWINGS TO SCALE, AS REQUIRED, USING
INPUT FROM ALL OTHER TRADES PRIOR TO FABRICATION AND INSTALLATION OF DUCTWORK. CONTRACTOR DRAWINGS
SHALL INDICATE DUCT INSTALLATION IN CONGESTED SPACES, INDICATING COORDINATION WITH GENERAL
CONSTRUCTION, BUILDING COMPONENTS, CEILING ELEVATIONS, AND OTHER BUILDING SERVICES. INDICATE PROPOSED
CHANGES TO DUCT LAYOUT.
14.
MOUNT THERMOSTATS AT 46" AFF AND 8" FROM THE EDGE OF THE WALL. COORDINATE LOCATIONS WITH OWNER AND
ARCHITECT PRIOR TO INSTALLATION.
15.
PROVIDE 1" DOOR UNDERCUT UNDER RESTROOM DOORS FOR MAKEUP AIR.
5
6
7
8
2808 Fairmount Street, Suite 300
Dallas, Texas 75201 | 214.303.1500
3.
NOTE
OFFSET, TRANSITION AND CONNECT SUPPLY AND RETURN DUCTWORK UP TO ROOFTOP UNIT.
REFER TO ARCHITECTURAL ELEVATIONS FOR AIR DEVICE LOCATIONS.
OFFSET, TRANSITION AND CONNECT EXHAUST DUCT UP TO FAN ON ROOF.
COORDINATE LOCATION OF HEATER WITH SPRINKLER CONTRACTOR PRIOR TO INSTALLATION. MOUNT HEATER 24"
AFF.
4" ROUND DRYER EXHAUST DUCT FROM VENT BOX ROUTED TO EXTERIOR WALL CAP.
CONDENSATE DRAIN DOWN TO TAILPIECE. COORDINATE WITH PLUMBING FOR LOCATION.
CONDENSATE DRAIN DOWN TO JANITOR SINK. COORDINATE WITH PLUMBING FOR EXACT LOCATION.
ROUTE DUCT THROUGH OPENING IN JOIST.
KEY PLAN
A
RE: M-202
12x12 EA
12x14 EA
PRE-SCHOOL
B166
275
A
10"ø
B
RR
B167
40
6"ø
A
255
10"ø
A
365
10"ø
PANTRY
112B
50
D
6x6
BREAK RM
112A
1
A
C
12x12
275
10"ø
365
10"ø
14x12 SA
DN
10x12 SA
C
12x12
T
230
10"ø
A
7
ELEC
110
WAH
2
14x14
C
10x10 EA
WOMEN
80
A134
B
150
6"ø
D
8x8
150
D
8x8
8x8
EA
1" CD
8x8 EA
3/4" CD
16x14 SA
A
10x10 EA
80
MENS B
6"ø
A133
RESOURCE
A135
7
3/4" CD
PRE-SCHOOL
B168
255
A
10"ø
24x20 RA
IT/AVL
111
1" CD
22x20 SA
12x12 RA
JAN
109
6x10 EA
8x8 EA
1" CD
1" CD
150
D
8x8
MENS
B103
80
6"ø
B
C
8x8
24x24
230
10"ø
10x12 SA
75
D
6x6
RR
B158
1
34x24 RA
325
10"ø
A
A
40
B
6"ø
STOR
B165b
A
A
14x16 SA
24x24
C
B
ADULT RR
B169
75
D
8x8
50
6"ø
A
26x20 RA
PRE-SCHOOL
B152
50
230
B
A
6"ø
10"ø
RTU-16
16x16
325
A
10"ø
325
A
10"ø
PRE-SCHOOL
B155
C
150
D
8x8
10x12 SA
10x12 SA
235
10"ø
235
A
10"ø
A
18x14 RA
16x16
8x6 EA
12x12 SA
PRE-SCHOOL
300
B153
A
50
10"ø
B
6"ø
RR
B154
A
DN
300
A
10"ø
12x12
E
500
18x10
E
500
18x10
500
18x10
E
RR
B151
150
8x8
C
8x8
6
230
A
10"ø
18x16 SA
8x12 EA
DN
DN
C
90
6"ø
STOR
B149
A
175
8"ø
A
10x10 RA
PRE-SCHOOL
LARGE GROUP
40
B130
B
6"ø
PRE-SCHOOL
185
A
PLAY
8"ø
B133
STOR
B131
310
10"ø
DN
18x18 SA
A
16x16 SA
10x12 SA
A
185
8"ø
RR
B135
185
A
8"ø
18x18 RA
DN
C
C
16x16
12x12 RA
24x22 SA
C
3
OPEN AREA
B100n
DN
DN
500
12"ø
8x12 EA
12x12 SA
C
A
OFFICES
B142
16x16 SA
270
A
10"ø
8"ø SA
C
10x10
C
16x16
1
ELEC.
B148
A
3/4" CD
300
10"ø
295
A
10"ø
18x14 RA
10x10
35
6"ø
B
A
C
10x10
DN
B
40
6"ø
STOR
B134
A
40
6"ø
B
50
6"ø
A
RR
B146
C
C
10x12 SA
RR
B128
150
D
8x8
16x16 RA
10x10
8x12 SA
A
295
10"ø
230
10"ø
C
A
C
16x16
10x10
230
10"ø
D
OFFICE
B139
150
8x8
OFFICE
B138
16x16
240
A
10"ø
CORRIDOR
B100a
PRE-SCHOOL
B127
1
80
A
6"ø
1" CD
A
240
A
10"ø
50
6"ø
8x8
STORAGE
B126
OFFICE
B137
RES.
B117
300
10"ø
PRE-SCHOOL
B125
A
12x12
310
A
10"ø
310
10"ø
24x24
C
24x24
VEST
100
1350
30x12
4
2
16x16
150
8"ø
(TYP 4)
A
12x12 RA
12x12
235
10"ø
235
10"ø
24x18 RA
A
8x8 EA
NURSERY
B106
DN
22x18 RA 20x18 SA
75
D
8x8
12x12 SA
1
3
STOR
B121
150
8"ø
(TYP 4)
A
6
8x10 SA
16x16 RA RTU-15
STOR
B171
A
235
10"ø
PRE-SCHOOL
B118
A
150
8x8
10x12 SA
T
20x18 SA
500
12"ø
OPEN AREA
B100d
14x14 SA
C
16x16
NURSERY
B107
C
12x12 SA
24x24
2
16x16 RA
T
8x8 EA
290
10"ø
NURSERY
B105
C
16x16
12x12 RA
14x12 SA
ADULT RR
C
12x12 B170
50
B
6"ø
RR
B119
C
8x8
12x12 SA
12x12 12x12 SA
290
A
10"ø
C
C
RTU-19
12x12
C
12x12
290
A
10"ø
12x12 SA
A
350
10"ø
A
350
10"ø
6x12 SA
A
50
6"ø
290
10"ø
PRE-SCHOOL
B123
RR
B124
50
6"ø
6x12 SA
FIRE RISER
B122
A
A
D
16x14 SA
E
C
1350
30x12
2
150
A
8"ø
(TYP 4)
18x16 RA C
A
50
B
6"ø
300
10"ø 14x12 SA
B
DRYER VENT CAP.
REFER TO DETAIL.
16x16
E
20x20 SA
NURSERY PLAY
B111
C
12x12
D
C
2300
48x18
1
10x12 EA
7
LAUNDRY
410
B136
A
12"ø
5
230
10"ø
50
6"ø
310
10"ø
PRE-SCHOOL
B120
16x16
NURSERY
B104
C
12x12
235
235
A
A
10"ø
10"ø
NURSERY
B112
STROLLER
STORAGE
B116
110
A
8"ø
A
A
1" CD
A
235
A
10"ø
T
C
E
16x16 SA
RTU-18
20x16 SA
2
125
8"ø
(TYP 4)
1" CD
OPEN AREA
8x8 EA
B100g
A
10x10
310
10"ø
235
A
10"ø
18x18 SA
16x16
12x12 RA
14x12 SA
8x6 EA
1" CD
12x12 SA
C
T
A
C
A
5
T
195
8"ø
500
12"ø
24x24
RTU-9
250
10"ø
12x12 RA
C
12x12
8x12 SA
A
12x12
CORRIDOR
B100h
C
RTU-14
16x14 SA
C
B
18x18 SA
C
28x16 SA
CORR
B100m
14x12 SA
14x12 RA
RTU-17
14x14
24x24
12x12 SA
NURSERY
B113
1
A
190
8"ø
24x22 SA
PRE-SCHOOL
B129
240
A
10"ø
PRE-SCHOOL
B145
PRE-SCHOOL
B147
6
C
3
240
10"ø
35
B
6"ø
75
6x6
C
75
8x8
D
22x20 RA
ADULT RR
B140
D
14x14
95
6"ø
A
75
D
6x6
ADULT RR
B141
95
6"ø
14x14 SA
250
10"ø
A
24x16 RA
235
A
10"ø
NURSERY
B115
310
10"ø
A
8x12 SA
300
10"ø
16x16
110
18x16 RA A
8"ø
6x10 EA
8x8 EA
16x16
RESOURCE
B143
OFFICES
B144
270
A
10"ø
310
10"ø
10x12 SA
A
B
250
250
A
10"ø NURSERY
10"ø
B114
1" CD
C
12x12
190
8"ø
A
14x12 SA
235
10"ø
PRE-SCHOOL
B161 A 235
10"ø
DN
T
A
A
195
A
8"ø
185
8"ø
A
6x12 SA
A
RTU-12
12x12 SA
C
T
1
C
10x10
CORR.
B100k
PRE-SCHOOL
B159
C
16x16
16x14 SA
300
10"ø
180
8"ø
ISSUE FOR PERMIT
BID & CONSTRUCTION
RTU-8
C
24x24
34x26 RA
6
A
10x14 EA
10x12 SA
16x14 SA DN
WAH
1
150
D
8x8
235
10"ø
6x12 SA
235
A
10"ø
6x12 SA
C
10x10
A
16x14 SA
150
8x8
RR
B160
40
B
6"ø
A
C
16x16
230
10"ø
D
8x8 EA
D
DN
24x24
COMMONS
101
8
8x10 SA
8x8 EA
PRE-SCHOOL
B163
24x20 SA
PRE-SCHOOL
B150
16x14 RA
T
CHECK-IN
106
C
A
6x12 SA
1
325
10"ø
C
36x36
F
20x20 RA
B
5.8
34x20 SA
INDOOR PLAY
107
2
DN
28x20 SA
20x18 SA
A
RESOURCE
B132
180
8"ø
8x8 EA
DN
175
A
8"ø
12x12 RA
230
10"ø
C
8x8
14x14 RA
A
PRE-SCHOOL
PLAY
B162
20x12 SA
235
10"ø
480
12"ø
1" CD
C
235
10"ø
6x12 SA
PRE-SCHOOL
B165
OPEN AREA
B100p
325
A
10"ø
1" CD
40
B
6"ø
RR
B164
A
175
8"ø
A
10x6 EA
A
C
10x10
12x12 SA
175
A
8"ø
175
A
8"ø
30x24 SA
C
16x16
325
10"ø
500
18x10
E
26x26 RA
C
34x26 SA
14x12 SA
6
A
12x14 SA
500
18x10
T
3
40
B
6"ø
175
A
8"ø
STOR
B157
DN
480
12"ø
E
(TYP.)
DN
10x12 EA
10x10 EA
18x12 RA
230
10"ø
230
10"ø
40
B
6"ø
A
T
20x14 SA
24x22 RA
CORR.
B100r
A
230
10"ø
A
A
DN
RTU-13
C
20x20
C
20x20
310
A
10"ø
12"ø SA
14x16 RA
230
10"ø
A
14x14 SA
12"ø SA
2
500
18x10
E
16x16 SA
PRE-SCHOOL
LARGE GROUP
B156
8x12 SA
A
150
8x8
80
B
6"ø
WOMEN
B102
14x12 SA
480
A
12"ø
230
10"ø
480
12"ø
A
90
6"ø
28x24 SA
A
ACTIVITY
A132
300
A
10"ø
C
8x8
MOTHERS
B101
1
50
A
6"ø
CORR.
B100b
RE: M-202
26x16 RA
C
24x24
DN
26x14 RA
C
A
RE: M-201
12x12 SA
DN
D
WAH
3
RTU-7
16x16 SA
80
A
6"ø
10x12 SA
150
D
8x8
14x14 SA
FIRST AID16x16 SA
108
8x12 EA
1
1991 FM 158, BRYAN, TX 77845
3
CENTRAL BAPTIST CHURCH
CHILDRENS BUILDING
RE: M-201
4
EH
1
NURSERY
B110
290
10"ø
A
NURSERY
B109
6x12 SA
290
10"ø
No. Date
Revision
NURSERY
B108
1
150
8x8
RAC
Drawn
JRM
Checked
A
A.1
B
C
C.1
C.9
1
D
D.8
E
E.6
F
F.1
G
G.1 G.2
G.7
H
H.1 H.5
J
J.8
WAS
K
Approved
FLOOR PLAN
AREA B MECHANICAL
FLOOR PLAN - AREA B MECHANICAL
Scale: 3/32" = 1'-0"
Project No.
Date
Last Revision
15187.00
05/11/2016
M-202
TRUE NORTH
PLAN NORTH
printed5/11/2016 12:26:34 PM
3300 West 7th Street, Suite 110
Fort Worth, Texas 76107 | 817.303.1500
KEYNOTES(THISSHEET)
GENERAL NOTES
KEYVALUE
1
2
3
CONTRACTOR SHALL MAINTAIN A MINIMUM OF 36" IN FRONT OF ALL ELECTRICAL DISCONNECTS.
2.
REFER TO ARCHITECTURAL PLANS FOR EXACT PLACEMENT OF MECHANICAL EQUIPMENT ON ROOF. COORDINATE WITH
STRUCTURAL.
3.
CONTRACTOR SHALL OBSERVE ALL MANUFACTURER CLEARANCE AND INSTALLATION GUIDELINES FOR MECHANICAL
EQUIPMENT.
4.
CONDENSATE FROM COOLING COILS SHALL BE COLLECTED PER LOCAL CITY REQUIREMENTS.
5.
MATERIALS, EQUIPMENT OR LABOR NOT INDICATED BUT WHICH CAN BE REASONABLY INFERRED TO BE NECESSARY FOR A
COMPLETE INSTALLATION SHALL BE PROVIDED. DRAWINGS AND SPECIFICATIONS DO NOT UNDERTAKE TO INDICATE EVERY
ITEM OF MATERIAL, EQUIPMENT, OR LABOR REQUIRED TO PRODUCE A COMPLETE AND PROPERLY OPERATING
INSTALLATION.
6.
THE DRAWINGS ARE DIAGRAMMATIC AND DO NOT NECESSARILY DEPICT EXACT CONDITIONS. THE LOCATION OF
EQUIPMENT IS APPROXIMATE ONLY. THE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT TO BE SCALED. SCALES
ARE SHOWN FOR REFERENCE AND APPROXIMATION ONLY. REFER TO THE ARCHITECTURAL DRAWINGS FOR DIMENSIONAL
DATA OF BUILDING COMPONENTS.
7.
CONTRACTOR SHALL BE RESPONSIBLE FOR PREPARING COORDINATION DRAWINGS TO SCALE, AS REQUIRED, USING
INPUT FROM ALL OTHER TRADES PRIOR TO FABRICATION AND INSTALLATION OF DUCTWORK. CONTRACTOR DRAWINGS
SHALL INDICATE DUCT INSTALLATION IN CONGESTED SPACES, INDICATING COORDINATION WITH GENERAL
CONSTRUCTION, BUILDING COMPONENTS, CEILING ELEVATIONS, AND OTHER BUILDING SERVICES. INDICATE PROPOSED
CHANGES TO DUCT LAYOUT.
8.
FALL PROTECTION BY OTHERS MAINTAIN 42" HIGH RAILING OR KEEP EQUIPMENT 10'-0" AWAY FROM EDGE OF BUILDING.
2808 Fairmount Street, Suite 300
Dallas, Texas 75201 | 214.303.1500
1.
NOTE
MANUFACTURERS RECOMMENDED SERVICE CLEARANCE.
10' OUTSIDE AIR CLEARANCE. EXHAUST AND PLUMBING VENTS SHALL NOT BE LOCATED IN THIS AREA.
ROUTE CONDENSATE DOWN THROUGH ROOF CURB.
KEY PLAN
A
B
9
3
3
RTU
2
RTU
1
HP
1
8
EF
1
1
CU
4
(TYP.)
RTU
4
3
3
RTU
3
3
EQUIPMENT CURB.
REFER TO DETAIL
RTU
5
7
2
(TYP.)
EF
2
1991 FM 158, BRYAN, TX 77845
CENTRAL BAPTIST CHURCH
CHILDRENS BUILDING
ISSUE FOR PERMIT
BID & CONSTRUCTION
RTU
11
3
1" CD
RTU
10
3
EF
3
6
RTU
9
RTU
6
No. Date
3
RE: M-301
RE: M-301
RE: M-302
RE: M-302
5.8
Revision
RAC
Drawn
JRM
Checked
WAS
C C.1
C.9
D
D.8
E
E.6
F
F.1
G
G.1 G.2
G.7
H H.1 H.5
J
J.8
Approved
K
ROOF PLAN AREA
A - MECHANICAL
1
ROOF PLAN - AREA A - MECHANICAL
Scale: 3/32" = 1'-0"
Project No.
Date
Last Revision
15187.00
05/11/2016
M-301
TRUE NORTH
PLAN NORTH
printed5/11/2016 12:26:40 PM
KEYVALUE
1
2
3
CONTRACTOR SHALL MAINTAIN A MINIMUM OF 36" IN FRONT OF ALL ELECTRICAL DISCONNECTS.
2.
REFER TO ARCHITECTURAL PLANS FOR EXACT PLACEMENT OF MECHANICAL EQUIPMENT ON ROOF. COORDINATE WITH
STRUCTURAL.
3.
CONTRACTOR SHALL OBSERVE ALL MANUFACTURER CLEARANCE AND INSTALLATION GUIDELINES FOR MECHANICAL
EQUIPMENT.
4.
CONDENSATE FROM COOLING COILS SHALL BE COLLECTED PER LOCAL CITY REQUIREMENTS.
5.
MATERIALS, EQUIPMENT OR LABOR NOT INDICATED BUT WHICH CAN BE REASONABLY INFERRED TO BE NECESSARY FOR A
COMPLETE INSTALLATION SHALL BE PROVIDED. DRAWINGS AND SPECIFICATIONS DO NOT UNDERTAKE TO INDICATE EVERY
ITEM OF MATERIAL, EQUIPMENT, OR LABOR REQUIRED TO PRODUCE A COMPLETE AND PROPERLY OPERATING
INSTALLATION.
6.
THE DRAWINGS ARE DIAGRAMMATIC AND DO NOT NECESSARILY DEPICT EXACT CONDITIONS. THE LOCATION OF
EQUIPMENT IS APPROXIMATE ONLY. THE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT TO BE SCALED. SCALES
ARE SHOWN FOR REFERENCE AND APPROXIMATION ONLY. REFER TO THE ARCHITECTURAL DRAWINGS FOR DIMENSIONAL
DATA OF BUILDING COMPONENTS.
7.
CONTRACTOR SHALL BE RESPONSIBLE FOR PREPARING COORDINATION DRAWINGS TO SCALE, AS REQUIRED, USING
INPUT FROM ALL OTHER TRADES PRIOR TO FABRICATION AND INSTALLATION OF DUCTWORK. CONTRACTOR DRAWINGS
SHALL INDICATE DUCT INSTALLATION IN CONGESTED SPACES, INDICATING COORDINATION WITH GENERAL
CONSTRUCTION, BUILDING COMPONENTS, CEILING ELEVATIONS, AND OTHER BUILDING SERVICES. INDICATE PROPOSED
CHANGES TO DUCT LAYOUT.
8.
FALL PROTECTION BY OTHERS MAINTAIN 42" HIGH RAILING OR KEEP EQUIPMENT 10'-0" AWAY FROM EDGE OF BUILDING.
NOTE
MANUFACTURERS RECOMMENDED SERVICE CLEARANCE.
10' OUTSIDE AIR CLEARANCE. EXHAUST AND PLUMBING VENTS SHALL NOT BE LOCATED IN THIS AREA.
ROUTE CONDENSATE DOWN THROUGH ROOF CURB.
2808 Fairmount Street, Suite 300
Dallas, Texas 75201 | 214.303.1500
1.
3300 West 7th Street, Suite 110
Fort Worth, Texas 76107 | 817.303.1500
KEYNOTES(THISSHEET)
GENERAL NOTES
KEY PLAN
A
B
RE: M-301
RE: M-302
RE: M-301
RE: M-302
3
5.8
RTU
6
3
ISSUE FOR PERMIT
BID & CONSTRUCTION
CU
2
CENTRAL BAPTIST CHURCH
CHILDRENS BUILDING
RTU
8
CU
3
RTU
7
3
EQUIPMENT CURB.
REFER TO DETAIL
RTU
12
5
3
EF
4
1
(TYP.)
RTU
13
3
RTU
14
3
4
1991 FM 158, BRYAN, TX 77845
EF
3
3
2
EF
6
EF
5
(TYP.)
RTU
15
3
3
RTU
17
3
RTU
18
RTU
16
3
3
RTU
19
CU
1
2
EQUIPMENT CURB.
REFER TO DETAIL
No. Date
Revision
RAC
Drawn
JRM
1
Checked
WAS
Approved
ROOF PLAN AREA
B - MECHANICAL
A
A.1
B
C
C.1
C.9 D
D.8
E
E.6
F F.1
G G.1 G.2
G.7
H H.1 H.5
J
J.8
K
Project No.
1
ROOF PLAN - AREA B - MECHANICAL
Date
Last Revision
Scale: 3/32" = 1'-0"
15187.00
05/11/2016
M-302
TRUE NORTH
PLAN NORTH
printed5/11/2016 12:26:47 PM