PACKAGED
GASL"
/ ELECTRIC
PACKAGED
SERIES
LG
L SERIES® ROOFTOP UNITS − 60HZ
ENGINEERING DATA
Variable or Constant Air Volume
13 to 30 Tons
Bulletin No. 210318
October 2004
Supersedes July 2004
Insulated Panels in all
Conditioned Areas
Copper Tube Coil
with Enhanced Fins
Humiditrol® Hot Gas
Reheat Option
Available (Not Shown)
(Not available for all models)
MERV 7 Filters Furnished
(Optional MERV 11
Available)
Thermally Protected
Outdoor Coil Fan Motors
with PVC Coated Fan Guard
Independent Fan
Motor Mount
(Separate from fan guard)
Hinged Access Panels
with Quarter Turn latches
Heavy Gauge
Galvanized Steel
Panels with Two−layer
Enamel Paint Finish
Intelligent Unit Controller
Solid−State Microprocessor
Provides Flexible Control of
all Unit Functions and
Diagnostics
High and Low
Pressure Switches
Thermal Expansion
Valves with Filter
Drier
R−410A Refrigerant Available
(15, 20, 21 and 30 Ton High
Efficiency CAV Models Only)
Belt Drive Blowers
Circuit Breaker,
Disconnect
and GFI Service Outlets
Available
Full Perimeter
Base Rail with
Rigging Holes and
Fork Lift Slots
Aluminized Steel
Heat Exchanger
(Optional Stainless
Steel Available)
Fully
Insulated Base
Refrigerant
Service Valves
Available
Power/Gas Entry
Through Base
or Side of Unit
Combustion Air
Inducer
Aluminized
Steel Inshot
Burners
Copeland Scroll
Compressors
with Crankcase Heater
Dual Stage
Gas Valve with
Manual Shut−Off
ASHRAE 90.1
COMPLIANT
NOTE − Due to Lennox’ ongoing committment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.
Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.
Installation and service must be performed by a qualified installer and servicing agency.
2004 Lennox Industries Inc.
TABLE OF CONTENTS
Application Guide − Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 85−87
Accessory Air Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 41−43
Blower Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 38−40
Control Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 53−61
Cooling Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 24−29
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 64−75
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 47−51
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 3−7
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 76−84
High Altitude Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 37
Humiditrol® Condenser Reheat Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 9−10
Humiditrol® Condenser Reheat Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 35−37
Installation Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page −51−52
Model Number Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2
Optional Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 8−13
Optional Disconnect Switch Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 46
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 14−23
Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 51
Weight Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 62−63
MODEL NUMBER IDENTIFICATION
L G C 240 S 2 B S 1 Y
Voltage
Y = 208/230V-3 phase-60hz
G = 460V-3 phase-60hz
J = 575V-3 phase-60hz
Brand/Family
L = L Series Product Line
Unit Type
G = Packaged Gas Heat w/ Electric Cooling
Major Design Sequence
A = 1st Generation
B = 2nd Generation
C = 3rd Generation
E = 4th Generation
Nominal Cooling Capacity − Tons
156 = 13 Tons
180= 15 Tons
210 = 17.5 Tons
240 = 20 Tons
248 = 21 Tons
300 = 25 Tons
360 = 30 Tons
Cooling Efficiency
S = Standard Efficiency
H = High Efficiency
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 2
Minor Design Sequence
1 = 1st Revision
2 = 2nd Revision
3 = 3rd Revision
Heating Type
L = Low Gas Heat, 1 Stage
S = Standard Gas Heat, 2 Stage
M = Medium Gas Heat, 2 Stage
H = High Gas Heat, 2 Stage
Blower Type
B = Constant Air Volume (CAV) − Belt Drive
V = Variable Air Volume (VAV) − Belt Drive
Refrigerant Type
2 = R−22
4 = R−410A
FEATURES AND BENEFITS
CERTIFICATIONS
ETL and CSA listed.
Heating efficiency ratings verified by
CSA.
Components bonded for grounding to
meet safety standards for servicing
required by UL, CSA and National and
Canadian Electrical Codes.
156 thru 248 models are certified in
accordance with the ULE certification
program, which is based on ARI
Standard 340/360-2000.
300 and 360 models are tested at
conditions included in ARI Standard
340/360−2000.
ISO 9001 Registered Manufacturing
Quality System.
ENERGY STAR® certified units are
designed to use less energy, help save
money on utility bills, and help protect
the environment.
WARRANTY
Limited ten years aluminized heat
exchanger, limited fifteen years optional
stainless steel heat exchanger.
Limited five years on compressors.
Limited three years on Integrated
Modular Control.
Limited one year all other covered
components.
COOLING SYSTEM
Designed to maximize sensible and
latent cooling performance at design
conditions.
Two efficiency levels provide flexibility.
System can operate from 0°F to 125°F
without any additional controls.
Compressors
Resiliently
mounted
on
rubber
grommets for quiet operation.
Copeland Scroll compressors on all
models for high performance, reliability
and quiet operation.
Compressor Crankcase Heaters
Protects against refrigerant migration
that can occur during low ambient
operation.
Thermal Expansion Valves
Assures
optimal
performance
throughout the application range.
Removable element head.
Filter/Driers
High capacity filter/driers protect the
system from dirt and moisture.
High Pressure Switches
Protects the compressor from overload
conditions such as dirty condenser
coils, blocked refrigerant flow, or loss of
outdoor fan operation. Automatic reset
Low Pressure Switches
Protects the compressor from low
pressure conditions such as low
refrigerant charge, or low/no air flow.
Automatic reset
Freezestats
Protects the evaporator coil from
damaging ice build−up due to conditions
such as low/no air flow, or low/no
refrigerant charge.
Coil Construction
Copper tube construction, enhanced
rippled−edge aluminum fins, flared
shoulder tubing connections, silver
soldered construction for improved heat
transfer. Factory leak tested.
Evaporator Coil
Cross row circuiting with rifled copper
tubing optimizes both sensible and
latent cooling capacity. Low fin per inch
count minimizes air pressure drop.
Constant air volume (CAV) models have
face−split evaporator coils. Variable air
volume (VAV) models have row−split
evaporator coils designed to keep
condensate water off of an inactive part
of the coil so the condensate will not
re−enter the air stream.
Condenser Coil
Angled, slab design helps protect coil
from possible contact or hail damage.
Condensate Drain Pan
Drain connection extends outside unit.
Painted, galvanized pan with positive
slope.
Stainless steel drain pan available as a
factory installed option.
Outdoor Coil Fan Motors
Thermal overload protected, totally
enclosed, permanently lubricated ball
bearings, shaft up, wire basket mount.
Outdoor Coil Fan
PVC coated fan guard furnished.
Refrigerant Choice
LGC180H, LGA240H, LGA248H, and
LGA360H models can be ordered with
R−22 (CAV and VAV models) or R−410A
(CAV models only) refrigerant systems.
REQUIRED SELECTIONS
Cooling Capacity
Specify the nominal cooling capacity of
the unit
Cooling Efficiency
Specify either standard or high
efficiency.
Refrigerant Choice
(LGC180H, LGA240H, LGA248H, and
LGA360H Models Only)
Specify R−22 (CAV and VAV models) or
R−410A (CAV models only) refrigerant.
OPTIONS / ACCESSORIES
Factory Installed
Discharge Air Temperature Sensor
Sensor sends information to the IMC to
cycle up to 4 stages of heating or cooling
to maintain the discharge air setpoints
for heating or cooling. Optional for CAV
units (single zone or bypass zoning
control). Automatically furnished with all
Variable Air Volume (VAV) units. Sensor
is shipped with the unit for remote field
installation in the supply duct.
Service Valves
Fully serviceable brass valves installed
in discharge & liquid lines. Not for use
with Humiditrol equipped units.
Four Stage Control
Add−on board that enables the unit to
operate four stages of cooling and four
stages of gas heat when controlled by a
4−stage thermostat or aftermarket DDC
control system.
For 248H, 300H, 360H models only.
Fresh Air Tempering
Provides heating and cooling as needed
to maintain the supply air temperature
within a comfort range, regardless of the
thermostat demand. Sensor ships with
unit but must be field installed in the
supply air duct. Requires change to IMC
(ECTO) parameter in the field to activate
this mode of operation.
Stainless Steel Condensate Drain Pan
Factory installed
Factory or Field Installed
Condensate Drain Trap
Field installed only, may be factory
enclosed to ship with unit. Available in
copper or PVC.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 3
FEATURES AND BENEFITS
HEATING SYSTEM
Aluminized steel inshot burners, direct
spark ignition, electronic flame sensor,
combustion air inducer, redundant
automatic single or dual stage gas valve
with manual shut-off.
Heat Exchanger
Tubular construction, aluminized steel,
life cycle tested.
Stainless Steel Heat Exchanger is
required if mixed air temperature is less
than 45°F.
Fan & Limit Controls
Factory installed with fixed temperature
setting.
Heat limit controls protect against
overheating.
Safety Switches
Flame roll−out switches, flame sensors
and combustion air inducer proving
switches protect system operation.
All safety switches are monitored by the
IMC unit controller and diagnostic errors
are reported and recorded.
REQUIRED SELECTIONS
Gas Input − Order one:
169,000 Btuh Low Heat Gas Input
(LGC156, LGC180 and LGC210
models only).
169,000 / 260,000 Btuh low/high fire −
Standard Heat Gas Input.
234,000 / 360,000 Btuh low/high fire −
Medium Gas Heat Input.
312,000 / 480,000 Btuh low/high fire −
High Gas Heat Input (Not available for
LGC156).
OPTIONS / ACCESSORIES
Factory Installed
Discharge Air Temperature Sensor
Sensor sends information to the IMC to
cycle up to 4 stages of heating or cooling
to maintain the discharge air setpoints
for heating or cooling. Optional for CAV
units (single zone or bypass zoning
control). Automatically furnished with all
Variable Air Volume (VAV) units. Sensor
is shipped with the unit for remote field
installation in the supply duct.
Stainless Steel Heat Exchanger
Required if mixed air temperature is
below 45°F.
Four Stage Control − Add−on board that
enables the unit to operate four stages of
cooling and four stages of gas heat when
controlled by a 4−stage thermostat or
aftermarket DDC control system.
For 248H, 300H, 360H models only.
Factory or Field Installed
Fresh Air Tempering
Provides heating and cooling as needed
to maintain the supply air temperature
within a comfort range, regardless of the
thermostat demand. Sensor ships with
unit but must be field installed in the
supply air duct. Requires change to IMC
(ECTO) parameter in the field to activate
this mode of operation.
Field Installed
Combustion Air Intake Extensions
Recommended for use with existing flue
extension kits in areas where high snow
drifts can block intake air.
LPG/Propane Kits
Conversion kit to field change over units
from Natural Gas to LPG/Propane.
Vertical Vent Extension Kit
Exhausts flue gases vertically above
unit.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 4
BLOWER
A wide selection of supply air blower
options are available to meet a variety of
air flow requirements.
Motor
Overload protected, equipped with ball
bearings.
Belt drive motors are offered in several
different sizes to maximize air
performance.
Motor Efficiency
Specify standard or high.
Supply Air Blower
Forward curved blades, blower wheel is
statically and dynamically balanced.
Belt drive motors with adjustable pulley
for speed change on CAV units.
Blower assembly slides out of unit for
servicing.
Grease fittings furnished.
REQUIRED SELECTIONS
Supply Air Blower
Specify Constant Air Volume (CAV) or
Variable Air Volume (VAV). Order
Standard or High Efficiency Blower
motor (See Blower Data Table for
specifications).
NOTE − 575V VAV models are only
available with high efficiency blower
motors.
Order one drive kit, see Drive Kit
Specifications Table.
OPTIONS / ACCESSORIES
Factory Installed
Supply Static Transducer
Transducer sends information to the IMC
to control VFD blower speed. Optional for
CAV units (single zone or bypass zoning
control). Automatically furnished with all
VAV units. Transducer is shipped with the
unit for remote field installation in the
supply duct.
Supply VFD Blower Bypass Control
Allows variable air volume (VAV) unit to
operate as a constant air volume (CAV)
unit in case of variable frequency drive
(VFD) failure.
Field Installed
Supply Static Limit Switch
Field installed manual reset switch for
supply static high pressure limit.
Prevents exceeding pressure limit in
supply air duct. Optional Mounting Kit
includes tubing and adaptors.
FEATURES AND BENEFITS
CABINET
Construction
Heavy−gauge steel panels and full
perimeter heavy−gauge galvanized
steel base rail provides structural
integrity for transportation, handling,
and installation.
Base rails have rigging holes. Three
sides of the base rail have fork slots.
Raised edges around duct and power
entry openings in the bottom of the unit
provide additional protection against
water entering the building.
Air−Flow Choice
Units are available in down−flow
(vertical) or horizontal return air flow
configuration.
Horizontal air flow requires Horizontal
Roof Curb.
Horizontal Return Air Panel Kit is also
required if converting a down−flow
configured unit to horizontal air flow.
Power and Gas Entry
Electrical and gas lines can be brought
through the unit base or through
horizontal access knock−outs.
Exterior Panels
Constructed
of
heavy−gauge,
galvanized steel with a two−layer
enamel paint finish.
Insulation
All panels adjacent to conditioned air are
fully insulated with non−hygroscopic
fiberglass insulation.
Unit base is fully insulated. The
insulation also serves as an air seal to
the roof curb, eliminating the need to
add a seal during installation.
Access Panels
Hinged access panels are provided for 2
compressor/controls/heating
areas,
blower access and air filter/economizer
access.
All panels have seals and quarter−turn
latching handles to provide a tight air
and water seal.
REQUIRED SELECTIONS
Air Flow Configuration
Specify horizontal or down−flow.
OPTIONS / ACCESSORIES
Factory Installed
Corrosion Protection
Phenolic epoxy coating, applied to
condenser coils (with painted base
section) and evaporator coils (with
painted base and painted blower
housings), factory applied to either
section or both sections.
Field Installed
Coil Guards
Painted, galvanized steel wire guards to
protect outdoor coil. Not used with Hail
Guards.
Grille Guards
Protects the space between outdoor
coils and main cabinet.
Hail Guards
Constructed of heavy gauge steel,
painted to match cabinet, helps protect
outdoor coils from hail damage. Not
used with Coil Guards.
Horizontal Return Air Panel Kit
Required for horizontal applications with
Horizontal Roof Curb, contains panel
with return air opening for field
replacement of existing unit panel and
panel to cover bottom return air opening
in unit, see dimension drawings.
AIR FILTERS
Disposable 2 inch (51 mm) pleated
MERV 7 filters (Minimum Efficiency
Reporting Value based on ASHRAE
52.2).
OPTIONS / ACCESSORIES
Factory or Field Installed
MERV 11 Filters
Disposable 2 inch pleated MERV 11
filters (Minimum Efficiency Reporting
Value based on ASHRAE 52.2).
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 5
FEATURES AND BENEFITS
CONTROLS
Intelligent Unit Controller
The Integrated Modular Control (IMC) is
a solid−state microprocessor−based
control board that provides flexible
control of all unit functions.
All control voltage is provided via a 24V
(secondary) transformer with built−in
circuit breaker protection.
Built-in functions include:
Blower On/Off Delay − Adjustable time
delay between blower on and off.
Blower Air Delivery Options − Three air
delivery options; single zone CAV, bypass
zoning with bypass dampers, and
modulating VAV with VFD.
Built-in Control Parameter Defaults −
No programming required for standard
CAV models.
Compressor Time−Off Delay −
Adjustable
time
delay
between
compressor shutoff and start up.
DDC Compatible − Various third party
DDC controllers can be factory or field
installed. Refer to the Unit Controllers
section for details.
Dirty Filter Switch Input − When a Dirty
Filter Switch is installed, the IMC will
signal when the indoor blower static
pressure increases, indicating a dirty
filter condition. Switch is optional and
can be factory or field installed.
Discharge Air Temperature Control −
The IMC will cycle up to 4 stages of
heating or cooling to maintain the
discharge air setpoints for heating or
cooling. Optional for CAV units (single
zone or bypass zoning control). Sensor
is automatically furnished with all
Variable Air Volume (VAV) units. Sensor
is shipped with the unit for remote field
installation in the supply duct.
Display/Sensor Readout − Displays
control parameters, diagnostic codes,
and sensor readings. The IMC unit
controller
displays
temperature
readings from return air, supply air, and
outdoor air sensors that are furnished as
standard on all L Series units. IMC will
also display readings from optional
sensors such as zone sensors, CO2
sensors or relative humidity sensors.
Economizer Control Choice − The
economizer is controlled by an add−on
board to the IMC. The economizer
control board has several choices for
controlling the economizer. See
Economizer / Outdoor Air / Exhaust
Options.
Fresh Air Tempering − Provides heating
and cooling as needed to maintain the
supply air temperature within a comfort
range, regardless of the thermostat
demand. Sensor ships with unit but must
be field installed in the supply air duct.
Requires change to
IMC (ECTO)
parameter in the field to activate this
mode of operation.
Extensive Unit Diagnostics − The IMC
monitors all sensors and functions
related to unit operation to provide
critical information. The IMC will display
detailed diagnostic information with
over 80 diagnostic codes to pinpoint any
problems and reduce troubleshooting
time. All diagnostic codes are listed
inside control access panel for easy
reference.
Exhaust Fan Control Modes − Fans
controlled by fresh air damper position
(non−VFD power exhaust) or building
static differential pressure transducer.
Permanent Diagnostic Code Storage
− Maintains diagnostic codes through a
power failure.
Field
Changeable
Control
Parameters − Over 200 different control
parameters allow customization of the
unit operation by changing delays,
cooling stages, deadbands, and
setpoints.
Indoor Air Quality Input − The IMC is
Demand Control Ventilation ready from
the factory (optional field installed CO2
sensor required). Two modes of
operation are available: setpoint and
proportional.
1 − Setpoint − Opens the economizer
dampers to full position when CO2
setpoint level is reached.
2 − Proportional − Opens the dampers
at the first set point and gradually
increases it as the CO2 level increases
until the second setpoint is reached.
Low Ambient Controls − Allows unit
cooling operation down to 0°F.
Gas Valve Time Delay Between First
and Second Stage − Allows gradual
increase of input rate.
Minimum Compressor Run Time −
Ensures proper oil return to the
compressor.
Network Capable − The IMC can be
daisy chained to other L Series units or L
Connection® Network controllers using
twisted pair wire.
Night Setback Mode − Adjusts
setpoints, closes outdoor air dampers
and operates the blower on demand,
may be customized for special
requirements.
Return Air Temperature Limit
Control − Allows the user to override
the demands based upon the return air
temperature during either heating or
cooling operation. Helps protect
against abnormal operating conditions
in the event of a room sensor or
thermostat failure.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 6
Safety Switch Input − Normally−closed
digital input allows the IMC to respond to
a external safety switch trip (phase
protector, low voltage, etc.) shutting
down unit operation.
Service Relay Output − Digital output
can indicate a critical error has occurred
to an external control device. Can also
be configured to energize based on
relative humidity, indoor air quality,
outdoor air temperature or unit
operation.
Smoke Alarm Mode − Control board
has four choices for responding to a
smoke alarm.
1 − Unit Off − unit will turn off.
2 − Positive Pressure − blower is
energized, exhaust fan is de−energized,
and the outdoor air dampers are
opened.
3 − Negative Pressure − blower is
energized, exhaust fan is energized,
and the outdoor air dampers are closed.
4 − Purge − blower is energized, exhaust
fan is energized, and the outdoor air
dampers are opened.
Staging − 2 heat/2 cool. Capable of up to
4 heat/4 cool with zone sensor or with
optional Four Stage Control (FS1) board
and 4 heat/4 cool thermostat or third
party DDC control system.
Strike Three" Protection − Ends
cooling or heating operation when any
of the following occurs three times
(adjustable) within a thermostat cycle:
low pressure trip, high pressure trip,
heat limit trip, or freeze−stat trip.
Gas Reheat − Control parameter option
that allows simultaneous heating and
cooling operation on CAV gas units for
controlling humidity for process air
applications such as supermarkets. Field
installed relative humidity sensor or
dehumidistat can be used.
On−Demand
Dehumidification
−
Monitors and controls condenser hot gas
bypass operation with Humiditrol option.
Prioritizes heat and cool demand with
dehumidification
demand.
Reheat
demand can be enabled by digital input
or a field installed relative humidity
sensor can be used. CAV models only.
Thermostat Bounce Delay − Protects
compressor from short cycling when
mechanical thermostat is used.
Warm-up Mode Delay − Adjustable time
that the economizer dampers are kept in
the closed position during morning
warm−up.
On−Board
User
Interface
−
Push−button, DIP switches used with
three−digit display readout for field
adjustment of control parameters. LED
indicators for L Connection Network
(transmit and receive) and for each
thermostat input.
FEATURES AND BENEFITS
CONTROLS − CONTINUED
ELECTRICAL
PC Interface − PC with optional Unit
Controller software may be used to field
or remotely adjust parameters, read
alarms, or display unit status.
VAV Control − Supports variable air
volume (VAV) units with variable
frequency drive or constant air volume
units with bypass zoning control system.
Constant air volume bypass zoning
control units require add−on control
board.
Zone Sensor Operation − Controls
zone temperature with up to 4 stages of
heating or cooling with optional zone
sensor. Four Stage Control (FS1) Board
is not required.
OPTIONS / ACCESSORIES
Factory Installed
Four Stage Control
Provides additional 24VAC thermostat
inputs for 4 heat/4 cool thermostats and
aftermarket DDC controls. Factory
installed.
Factory or Field Installed
Blower Proving Switch
Monitors blower operation, shuts down
unit if blower fails. Factory installed.
Dirty Filter Switch
Senses static pressure increase
indicating dirty filter condition.
Indoor Air Quality (CO2) Sensor
Monitors CO2 levels, reports to IMC board
which adjusts economizer dampers as
needed.
Smoke Detector
Photoelectric type, installed in supply air
section or return air section or both
sections
Commercial Control Systems
L Connection® Network
Control system to complement the IMC
in single zone applications. Options
include local interface, software for local
or
remote
communication,
and
hardware for networking other control
functions.
See pages 53 − 55.
Sectrat Commercial Zoning System
Control system to complement the IMC
in VFD, bypass zoning applications and
single zone control. Options include
local interface, software for local or
remote communication, and hardware
for networking other control functions.
See Pages 56 − 58.
Aftermarket DDC
See Pages 59−60.
Thermostats
Control system and thermostat options.
Aftermarket unit controller options.
See Page 61.
Field Installed
Humidity Sensor Kit, Remote
Mounted
Humidity sensor required with factory
installed Humiditrol Option.
REQUIRED SELECTIONS
Voltage Choice
Specify 208/23V, 460V or 575V
3−phase−60hz when ordering base unit.
OPTIONS / ACCESSORIES
Factory Installed
Circuit Breakers up to 250 Amp
HACR circuit breaker without power
distribution lugs. Accessible from
outside
of
unit,
spring−loaded
weatherproof cover furnished. Main
power to the unit is field connected to the
circuit breaker which allows all power to
be shutoff for service. Circuit breaker is
sized to the unit maximum overcurrent
protection (MOCP) size.
Field Installed
Disconnect Switch up to 250 Amp
Accessible from outside of unit, spring
loaded weatherproof cover furnished.
Main power to the unit is field connected
to the disconnect which allows all power
to be shut off for service. See Optional
Disconnect Switch Requirements table,
Page 46 for field installed disconnect
switches.
GFI Service Outlets (2)
115v ground fault circuit interrupter
(GFCI) type, field wired or unit powered.
SERVICEABILITY
Designed to streamline general
maintenance
and
decrease
troubleshooting time.
Diagnostics
IMC
diagnostic
codes
pinpoint
problems, minimizing troubleshooting
time.
Marked & Color−Coded Wiring
All electrical wiring is color−coded and
marked to identify which components it
is connecting.
Electrical Plugs
Positive connection electrical plugs are
used to connect common accessories
or maintenance parts for easy removal
or installation.
Tool−less, Hinged Access Panels
Large access panels are hinged and
have quarter−turn, latching handles for
quick and easy access to maintenance
areas.
Filter access panels are hinged for easy
access to the filters.
Blower Access
Blower assembly slides out of the unit
for easy access.
Coil Cleaning
Slab condenser coils allow easier
cleaning.
Standard Components
A
large
number
of
common
maintenance parts are standard
throughout the entire range of sizes
(3−30 tons), reducing the need to carry a
lot of different parts to the job or in
inventory.
Compressor Compartment
Compressors are located near the
perimeter of the unit for easier access.
Compressors are isolated from the
condenser air flow allowing system
operation checks to be done without
changing the air flow across the outdoor
coils.
Thermal Expansion Valves
Thermal expansion valves are located
near the perimeter of the unit for easier
access.
Removable element head allows
change out of element and bulb without
removing the TXV.
Service Valves (optional)
Optional factory installed liquid and
discharge
service
valves
allow
refrigerant to be isolated to the high side
for service work on the low side of the
refrigeration system.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 7
OPTIONS / ACCESSORIES
ECONOMIZER/OUTDOOR AIR/EXHAUST
Factory or Field Installed
Economizer − Parallel gear driven action
recirculated air and outdoor air dampers,
plug-in connections to unit, nylon
bearings, neoprene seals, 24 volt fully
modulating
spring
return
motor,
adjustable minimum damper position,
damper assembly slides in unit, outdoor
air hood must be ordered separately,
optional down-flow barometric relief
dampers available, choice of economizer
controls. The IMC add−on board for
economizer control is included with the
economizer. Control board has five
choices for controlling the economizer
(DIP switch selections).
1 − Differential Sensible Control −
Factory setting. Uses the outdoor air
and return air sensors that are
furnished with the unit. The IMC
compares the outdoor air and return air
and using setpoints, enables the
economizer when the outdoor air
temperature is below the configured
setpoint and cooler than return air.
NOTE − Differential Sensible Control
can be configured in the field to provide
Offset Differential Sensible Control or
Single Sensible Control.
In Offset Differential Sensible Control
mode, the economizer is enabled if the
temperature
differential
(offset)
between outdoor air and return air
reaches the configured setpoint.
In Single Sensible Control mode, the
economizer is enabled when outdoor
air temperature falls b
2 − Single Sensible Control −
Differential Sensible Control above
can be configured to Single Sensible
Control. The IMC compares the
outdoor air sensor temperature to the
setpoint and enables the economizer
when the outdoor air is cooler than the
setpoint.
3 − Global Control − The IMC
communicates with a DDC system with
one global sensor (enthalpy or sensible)
to determine whether outside air is
suitable for free cooling on all units
connected to the control system. Sensor
must be field provided.
4 − Single Enthalpy Control − Outdoor
air
enthalpy
sensor
enables
economizer if the outdoor enthalpy is
less than the setpoint of the board.
Factory installed.
5 − Differential Enthalpy Control −
Two solid-state enthalpy sensors allow
the economizer control board to select
between outdoor air or return air,
whichever has lower enthalpy. Factory
installed.
Outdoor Air Dampers (Manual or
Motorized) − Linked mechanical
dampers, 0 to 25% (fixed) outdoor air
adjustable, installs in unit, outdoor air
hood must be ordered separately.
Motorized model features fully modulating
spring return damper motor with plug−in
connection. Manual model features a slide
damper.
Minimum mixed air temperature in
heating mode 30°F. Maximum mixed air
temperature in cooling mode: 90°F.
Outdoor Air Hood − Required with
LAREMD Economizer, LAOAD and
LAOADM
Outdoor
Air
Damper
Sections, cleanable aluminum mesh
fresh air filters furnished.
Down−Flow
Barometric
Relief
Dampers − Allows relief of excess air,
aluminum blade dampers prevent blow
back and outdoor air infiltration during
off cycle, bird screen furnished.
Dampers are required with Standard
Static Power Exhaust Fans. Down−Flow
Barometric Relief Damper Hood is
available and must be ordered extra.
Field Installed
Down−Flow
Barometric
Relief
Damper Hood − Field installed only. Use
with Barometric Relief Dampers.
Horizontal
Barometric
Relief
Dampers − Aluminum blade dampers
prevent blow back and outdoor air
infiltration during off cycle, field installed
in return air duct, bird screen furnished.
Factory or Field Installed
Standard Static Power Exhaust Fans
− LAPEF18/24 models have two, 1/3 hp
motors with 20 in., five blade
propeller−type fans with a total power
input of 750 Watts and a total air volume
of 8630 cfm at 0 in. w.g.
LAPEF30/36 models have three, 1/3 hp
motors with 20 in., five blade
propeller−type fans with a total power
input of 1125 Watts and a total air
volume of 12,800 cfm at 0 in. w.g.
Motor is inherently protected and
enclosed for maximum protection from
weather, dust and corrosion. Installs
internal to unit for down-flow
applications only with economizer
option, provides exhaust air pressure
relief, interlocked to run when return air
dampers are closed and supply air
blower is operating, fan runs when
outdoor air dampers are 50% open
(adjustable),
motor
is
overload
protected, steel cabinet and hood
painted to match unit, requires optional
Down-flow Economizer Barometric
Relief Dampers.
See Standard Static Power Exhaust
Blower Tables.
High Static Power Exhaust Fans
(248H/300H/360H Models Only −
Choice of 50% (two, 2 hp motors) or
100%
(three,
2
hp
motors)
centrifugal−type
power
exhaust.
Overload and sub−fuse protected,
equipped with ball bearings. Forward
curved blades, blower wheel is statically
and dynamically balanced.
Constant volume high static power
exhaust fans have adjustable pulleys for
speed adjustments and are controlled
by damper position.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 8
Variable air volume units (with variable
frequency drive) have 100% capacity
and can be ordered with an optional
VFD bypass. Fans feature solid−state
analog pressure transducer control
which senses differential pressure
between conditioned space and outdoor
air to regulate fan speed. See Power
Exhaust Blower Tables
See High Static Power Exhaust Blower
Tables.
NOTE − High Static Power Exhaust is
field installed but must be ordered at the
same time as the rooftop unit so the unit
can be factory configured for this option.
Power Exhaust Control Options:
Damper Position Control
IMC controls exhaust fan based on
economizer damper position. For
Standard or High Static Power
Exhaust (without VFD) Fans only.
Differential Pressure Transducer
Differential
pressure
transducer
compares atmospheric pressure to
conditioned space static pressure for
controlling exhaust fan. Transducer is
shipped with the unit for remote field
installation. For High Static Power
Exhaust (with VFD) fans only.
CEILING DIFFUSERS
Field Installed
Ceiling Diffusers − Aluminum grilles,
large center grille, insulated diffuser box
with flanges, hanging rings furnished,
interior transition (even air flow),
internally
sealed
(prevents
recirculation), adapts to T-bar ceiling
grids or plaster ceilings.
Transitions (Supply and Return) −
Used with diffusers, installs in roof curb,
galvanized steel construction, flanges
furnished for duct connection to
diffusers, fully insulated.
ROOF CURBS
Field Installed
Nailer strip furnished, mates to unit,
shipped knocked down.
Standard Down−Flow − US National
Roofing
Contractors
Approved,
available in 14 inch and 24 inch heights
Horizontal − Converts unit from
down-flow to horizontal (side) air flow,
return air is on unit, supply air is on curb,
see dimension drawings. Curbs for
rooftop applications meet National
Roofing Code requirements. Requires
Horizontal Return Air Panel. Available in
26 inch, 30 inch, 37 inch and 41 inch
heights. Optional Insulation Kit is
available to help prevent sweating.
Cliplock
1000
Full
Perimeter
Down−Flow − Available in 14 inch, 18
inch and 24 inch heights.
OPTIONS
HUMIDITROL® HOT GAS BYPASS REHEAT OPTION
156H & 180H (3 Compressors)
210H, 240H & 300S (4 Compressors)
R−22 CAV MODELS ONLY
Factory installed option designed to
control humidity.
Provides dehumidification on demand
using ASHRAE 90.1 recommended
method for reheat with comfort
conditioning humidity control.
In addition to a thermostat/room sensor
used for conventional operation, a
humidity sensor is required and must be
located in the occupied space.
Humidity sensor provides input to the
Integrated Modular Control (IMC) which
is used to control activation of the
dehumidification operation.
Reheat controls are located in the
compressor control section of the unit
for easy access.
Benefits
Improves indoor air quality.
Helps prevents damage due to high
humidity levels.
Improves comfort levels by reducing
space humidity levels.
Operation
No Dehumidification Demand
The unit will operate conventionally
whenever there is a demand for cooling
or heating and no dehumidification
demand.
Free cooling is only permitted when
there is no demand for dehumidification.
Dehumidification Demand Only
The IMC is factory set at 60% relative
humidity setpoint and can be adjusted at
the IMC or with optional Unit Controller
Software.
For Network Control Panel (NCP)
applications, the humidity setpoint can
be adjusted at the NCP. The unit will
operate in the dehumidification mode
until the relative humidity of the
conditioned space is 3% below the
setpoint.
Reheat operation will initiate on a
dehumidification demand and does not
require a cooling demand.
The reheat coil is sized to offset most of
the first stage sensible cooling effect
during reheat only operation. This
reduction in sensible cooling capacity
extends compressor run time to control
humidity when cooling loads are light.
Solenoid valves divert hot gas from
compressor 1 and compressor 2 to the
reheat coil.
The cooled and dehumidified air from
the evaporator is then reheated as it
passes through the reheat coil.
The de−superheated and partially
condensed refrigerant continues to the
outdoor
condenser
coil
where
condensing is completed.
The unit will continue to operate in this
mode until the dehumidification demand
is satisfied.
A heating demand will terminate reheat
operation.
Dehumidification and Cooling Demand
for 156H/180H three compressor
models (Thermostat Application)
If both a dehumidification and a first
stage cooling demand occur, the system
will operate compressor 1 and
compressor 2 in reheat and compressor
3 will operate in cooling.
A demand for second stage cooling will
terminate reheat operation until second
stage cooling demand is satisfied.
Dehumidification and Cooling Demand
for 210H/240H/300S four compressor
models (Thermostat Application)
If both a dehumidification and a first
stage cooling demand occur, the system
will operate compressor 1 and
compressor 2 in reheat and compressor
3 and compressor 4 will operate in
cooling.
A demand for second stage cooling will
terminate reheat operation until second
stage cooling demand is satisfied.
Dehumidification and Cooling
Demand for 156H/180H three
compressor models (Room Sensor
Application)
If both a dehumidification and a first
stage cooling demand occur, the system
will operate compressor 1 and
compressor 2 in reheat and compressor
3 will operate in cooling.
A demand for second stage cooling will
terminate reheat and compressor 3
operation and operate compressor 1
and compressor 2 in cooling until
second stage cooling demand is
satisfied.
A demand for third stage cooling will
operate compressor 1, compressor 2
and compressor 3 in cooling.
Dehumidification and Cooling
Demand for 210H/240H/300S four
compressor models (Room Sensor
Application)
If both a dehumidification demand and a
first stage cooling demand occur, the
system will operate compressor 1 and
compressor 2 in reheat and compressor
3 will operate in cooling.
If a demand for second stage cooling is
initiated, compressor 1 and compressor
2 will operate in reheat and compressor
3 and compressor 4 will operate in
cooling.
A demand for third stage cooling will
terminate reheat and compressor 4
operation and operate compressor 1,
compressor 2 and compressor 3 in
cooling until third stage cooling demand
is satisfied. A demand for fourth stage
cooling will operate compressor 1,
compressor 2, compressor 3 and
compressor 4 in cooling.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 9
OPTIONS
HUMIDITROL® HOT GAS BYPASS REHEAT OPTION (CONTINUED)
REFRIGERANT SCHEMATIC (156H, 180H MODELS ONLY)
NOTE: Refrigerant circuits one and two operates
when there is a first-stage thermostat demand.
MIXED
INDOOR/OUTDOOR
AIR
3
CONDENSER
COIL
2
1
2
2
1
1
2
1
2
3
3
3
OUTDOOR
AIR
1
REFRIGERANT
CIRCUIT 1
2
REFRIGERANT
CIRCUIT 2
3
REFRIGERANT
CIRCUIT 3
REHEAT
VALVE
S
CHECK
VALVE
THERMAL
EXPANSION
VALVE
REFRIGERANT SCHEMATIC (210H, 240H and 300S MODELS ONLY)
NOTE: Refrigerant circuits one and two operates
when there is a first-stage thermostat demand.
MIXED
INDOOR/OUTDOOR
AIR
4
3
CONDENSER
COIL
2
1
2
2
1
1
2
4
3
2
4
3
1
OUTDOOR
AIR
1
REFRIGERANT
CIRCUIT 1
2
REFRIGERANT
CIRCUIT 2
3
REFRIGERANT
CIRCUIT 3
4
REFRIGERANT
CIRCUIT 4
S
REHEAT
VALVE
CHECK
VALVE
THERMAL
EXPANSION
VALVE
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 10
OPTIONs / ACCESSORIES
210
240
248
300H
360
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
1x
1x
1x
1x
f
1x
f
f
f
f
1x
1x
1x
1x
f
1x
f
f
f
1x
1x
1x
1x
f
1x
f
f
f
1x
1x
1x
1x
f
1x
f
f
f
1x
1x
1x
1x
f
1x
f
f
f
1x
1x
1x
1x
f
1x
f
f
f
1x
1x
1x
1x
f
1x
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
x
x
x
x
x
x
x
x
f
x
f
f
f
f
f
f
f
f
⊗
f
f
x
f
f
f
f
f
f
f
f
⊗
f
f
x
x
x
f
x
x
x
300S
180
Item
156
L Series
COOLING SYSTEM
Standard Efficiency
High Efficiency
Condensate Drain Trap − Copper
Condensate Drain Trap − PVC
Corrosion Protection
Service Valves
Stainless Steel Condensate Drain Pan
Factory installed only
Factory installed only
LTACDKC09/36
LTACDKP09/36
Factory installed only
Factory installed only
Factory installed only
f
HEATING SYSTEM
Low Heat (1 stage)
Standard Heat (2 stage)
Medium Heat (2 stage)
High Heat (2 stage)
Combustion Air Intake Extensions
LPG/Propane
Conversion Kits
Stainless Steel Heat Exchanger
Vertical Vent Extension
Factory installed only
Factory installed only
Factory installed only
Factory installed only
89L97
130/260 (2 kits) kBtuh input − 72M94
180/360 (2 kits) kBtuh input − 72M95
240/480 (2 kits) kBtuh input − 72M96
Factory installed only
73M72
f
f
f
1x
1x
1x
1x
f
1x
Blower − SUPPLY MOTOR
f
f
2, 3, 5 hp Std. Efficiency CAV
2, 3, 5 hp High Efficiency CAV
3, 5, 7.5 hp Std. Efficiency CAV
3, 5, 7.5 hp High. Efficiency CAV
5, 7.5, 10 hp Std. Efficiency CAV
5, 7.5, 10 hp High Efficiency CAV
5, 7.5, 10 hp Std. Efficiency VAV with VFD (not 575V units)
5, 7.5, 10 hp High Efficiency VAV with VFD (not 575V units)
Supply VFD Blower Bypass (VAV units with VFD only)
AIR FILTERS
MERV 11 High Efficiency
97L87 (24 x 24 x 2 order 6 per unit)
97L88 (20 x 20 x 2 order 12 per unit)
f
88K52
88K53
78K78
86K30
88K25
88K26
38K47
38K48
x
f
f
f
f
f
CABINET
Coil Guards
Grille Guards
Hail Guards
Horizontal Return Air Panel Kit
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
CONTROLS
Blower Proving Switch
30K49
f
f
f
Dehumidistat − Supermarket reheat only
65F86
x
x
x
Commercial Controls
L Connection® Building Automation System
f
f
f
Novar® ETM−2051 Unit Controller
f
f
f
Sectrat Zoning System w/ VFD Control − C0CTRL05BD1L
Sectrat Zoning System with Bypass Control − C0CTRL04BD1L
f
f
f
Sectrat Zoning System Single Zone Control − C0CTRL03BD1L
f
f
f
Dirty Filter Switch
30K48
f
f
f
2 Discharge Air Temperature Sensor
Factory installed only
Four Stage Control
Factory installed only
Fresh Air Tempering
45L78
⊗
⊗
⊗
Smoke Detector − Supply
LTSASDK10/36
f
f
f
Smoke Detector − Return
LTARSDK10/30
f
f
f
Smoke Detector − Return
LTARSDK30/36
C0SNSR11AE1 (Switch)
x
x
x
Supply Static Limit Switch
C0SNSR12AE1− (Mounting Kit)
x
x
x
2 Supply Static Transducer
NOTE − The catalog and part numbers that appear here are for ordering field installed accessories only.
f
x
f
f
f
f
f
⊗
f
f
x
x
f
x
f
f
f
f
f
f
f
f
⊗
f
f
x
x
x
f
x
f
f
f
f
f
⊗
f
f
x
x
⊗ − Field Installed Accessory or Configure to Order (factory installed)
f − Configure to Order (Factory Installed)
X − Field Installed.
1 Two required.
2 Optional for Constant Air Volume (CAV) units (single zone or bypass zoning control). Automatically furnished with all Variable Air Volume (VAV) units. Sensor is shipped with
the unit for remote field installation in the supply duct.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 11
OPTIONs / ACCESSORIES
156
180
210
240
248
300S
300H
360
L Series
77N39
87N53
87N52
87N54
85L43
90N43
70N93
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Voltage (60HZ) − 208/230V−3 phase, 460V−3 phase or 575V−3 phase
HACR Circuit Breakers
Factory installed only
80 Amp − 30M39
Disconnect Switch
150 Amp − 30M40
250 Amp − 30M41
GFI Service Outlets
74M70
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
Item
INDOOR AIR QUALITY (Co2) SENSORS
Sensor − white case, CO2 display
Sensor − white case, no display
Sensor − black case, CO2 display
Sensor − black case, no display
CO2 Sensor Duct Mounting Kit
Aspiration Box for duct mounting
Handheld CO2 Monitor
ELECTRICAL
HUMIDITROL® CONDENSER REHEAT OPTION
Humiditrol®
Humidity Sensor Kit, Remote Mounted (required)
Remote Sensor Wall Seal Plate
17M50
58L33
H
x
x
H
x
x
H
x
x
f
f
f
S
x
x
ECONOMIZER/OUTDOOR AIR / EXHAUST
Economizer
LAREMD18/24
LAREMD30/36
Economizer
(Order Outdoor Air Hood Below Separately)
f
f
f
Economizer Controls
Differential Sensible Control
Global Control
Single Enthalpy Control
Differential Enthalpy Control
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
LAGEH18/30S
LAGEH30H/36
f
f
f
f
LAGEDH18/24
f
f
f
f
Factory Setting
Sensor field provided
LTASEK03/36
LTADEK03/36
f
f
f
f
f
f
f
f
Barometric Relief
Down−Flow Barometric
Relief Dampers
(Order Outdoor Air Hood Below Separately)
Hood for Down
Down−Flow
Flow LAGED
Horizontal Barometric
Relief Dampers
(Hood Furnished)
LAGED18/24
f
f
LAGED30/36
f
f
f
f
LAGEDH30/36
Outdoor Air Dampers
Damper Section (down−flow)
Motorized
(Order Hood Separately)
Damper Section (down−flow)
Manual
(Order Hood Separately)
f
LAOADM18/24
f
f
f
f
f
LAOADM30/36
f
LAOAD18/24
f
f
f
f
f
LAOAD30/36
Outdoor Air Hoods
Outdoor Air Hood (down−flow)
(Number of Filters)
16 x 25 x 1 in.
f
LAOAH18/24 (3)
f
f
f
f
f
LAOAH30/36 (5)
Power Exhaust
Standard Static
High
g Static
50%
100%
100% with VFD
100% with VFD and Bypass
LAPEF18/24
LAPEF30/36
LAPEB30/36D
LAPEB30/36E
LAPEV30/36E
LAPEV30/36F
f
f
f
f
f
f
1f
1f
1f
1f
NOTE − The catalog and part numbers that appear here are for ordering field installed accessories only.
⊗ − Field Installed Accessory or Configure to Order (factory installed)
f − Configure to Order (Factory Installed)
S − Configure to Order (Factory Installed) R−22 Standard Efficiency Models Only
H − Configure to Order (Factory Installed) R−22 High Efficiency Models Only
X − Field Installed.
1 High Static Power Exhaust is field installed, but must be ordered at the same time as the rooftop unit so the unit can be factory configured for this option.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 12
f
f
1f
1f
1f
1f
1f
1f
1f
1f
OPTIONs / ACCESSORIES
300H
360
x
300S
x
248
x
240
x
210
180
Item
156
L Series
x
x
x
x
x
x
CEILING DIFFUSERS
Step−Down
p
(O d one))
(Order
RTD11−185
RTD11−275
LARTD30/36
Flush
(O d one))
(Order
Transitions
S
l and
d Return
R t
Supply
(Order one)
RTD11−185S
RTD11−275S
LARTD30/36S
FD11−185
FD11−150/180S
FD11−275
FD11−275S
LAFD30/36
LAFD30/36S
LASRT18
LASRT18S
LASRT21/24
LASRT21/24S
LASRT30/36
LASRT30/36S
x
x
x
x
x
x
x
x
x
x
x
x
x
x
ROOF CURBS − STANDARD
Down−Flow
14 in. height
LARMF18/36−14
x
x
x
x
x
x
x
x
24 in. height
LARMF18/36−24
x
x
x
x
x
x
x
x
26 in. height
LARMFH18/24−26
x
x
x
x
30 in. height
LARMFH30/36−30
x
x
x
x
Horizontal
Slab Applications
x
x
Rooftop Applications
37 in. height
LARMFH18/24−37
41 in. height
LARMFH30/36−41
x
x
x
x
x
x
Insulation Kits
for LARMFH18/24−26
73K32
x
x
x
x
x
for LARMFH18/24−37
73K34
x
x
x
x
x
for LARMFH30/36−30
73K33
x
x
x
for LARMFH30/36−41
73K35
x
x
x
x
x
x
x
x
x
ROOF CURBS − CLIPLOCK 1000
Down−Flow
14 in. height
g
LARMF18/30S−14
x
x
x
x
x
x
x
x
LARMF30/36S−14
18 in. height
g
LARMF18/30S−18
x
LARMF30/36S−18
24 in. height
g
LARMF18/30S−24
x
x
x
x
x
x
x
LARMF30/36S−24
x
x
Horizontal
26 in. height
LARMFH18/24S−26
x
x
x
x
x
37 in. height
LARMFH18/24S−37
x
x
x
x
x
30 in. height
LARMFH30/36S−30
x
x
x
41 in. height
LARMFH30/36S−41
x
x
x
NOTE − The catalog and part numbers that appear here are for ordering field installed accessories only.
X − Field Installed
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 13
SPECIFICATIONS − STANDARD EFFICIENCY COOLING (CAV)
General
Data
Nominal Tonnage
Model No.
Efficiency Type
Blower Type
Cooling
g
Gross Cooling Capacity − Btuh (kW)
Performance
P
f
1 Net Cooling Capacity − Btuh (kW)
ARI Rated Air Flow − cfm (L/s)
Total Unit Power (kW)
1 EER (Btuh/Watt)
2 Integrated Part Load Value (Btuh/Watt)
Refrigerant
g
Charge
g
Circuit 1
Furnished (R
(R-22)
22)
Circuit 2
Circuit 3
Circuit 4
Gas Heating
Heat Input Type
Performance
Input − Btuh (KW)
First Stage
Second Stage
Output − Btuh (kW)
First Stage
Second Stage
CSA Thermal Efficiency
Gas Supply Connections
Recommended Gas Supply Pressure − Natural
LPG/Propane
Compressor Type (no.)
Condenser
Net face area − sq. ft. (m2) total
C il
Coils
Tube diameter − in. (mm)
Number of rows
Fins per inch (m)
Condenser
Motor horsepower (W)
Fans
F
Motor rpm
Total Motor watts
Diameter − in. (mm)
No. of blades
Total Air volume − cfm (L/s)
p
Evaporator
Net face area − sq. ft. (m2) total
Coils
C il
Tube diameter − in. (mm)
No. of rows
Fins per inch (m)
Drain connection − number and size
Expansion device type
3 Indoor
Nominal motor output
Blower and
Drive
Selection
Maximum usable motor output
(US Only)
Motor − Drive kit
15 Ton
15 Ton
LGC180S2B (R−22)
Standard
Constant Air Volume (CAV)
186,000 (54.5)
180,000 (52.7)
6000 (2830)
18.0
10.0
10.6
9 lbs. 0 oz. (4.08 kg)
9 lbs. 0 oz. (4.08 kg)
9 lbs. 0 oz. (4.08 kg)
−−−
Low
Standard
Medium
High
1 Stage
2 Stage
2 Stage
2 Stage
169,000 (49.5)
169,000 (49.5)
234,000 (68.6)
312,000 (91.4)
−−−
260,000 (76.2)
360,000 (105.5)
480,000 (140.6)
135,000 (39.6)
−−−
−−−
−−−
−−−
208,000 (60.9)
288,000 (84.4)
384,000 (112.5)
80.0%
1 in.
7 in. w.g. (1.7 kPa)
11 in. w.g. (2.7 kPa)
Scroll (3)
56.5 (5.25)
3/8 (9.5)
1
20 (787)
(4) 1/3 (249)
1075
1370
(4) 24 (610)
3
15,850 (7480)
22.3 (2.07)
3/8 (9.5)
3
14 (551)
(1) 1 in. NPT coupling
Balanced Port Thermostatic Expansion Valve, removeable power head
3 hp (2.2 kW)
5 hp (3.7 kW)
7.5 hp (5.6 kW)
3.45 hp (2.6 kW)
5.75 hp (4.3 kW)
8.63 hp (6.4 kW)
3 hp
kit #A − 535 − 725 rpm
kit #1 − 685 − 865 rpm
kit #2 − 685 − 865 rpm
5 hp
kit #2 − 685 − 865 rpm
kit #3 − 850 − 1045 rpm
kit #4 − 945 − 1185 rpm
Blowerwheelnominaldiameterxwidth
Type of filter
No. and size − in. (mm)
Electrical characteristics
Filters
7.5 hp
kit# 5 − 945 − 1185 rpm
kit# 6 − 1045 − 1285 rpm
kit# 7 − 850 − 1045 rpm
(2) 15 x 15 in. (381 x 381 mm)
Disposable, pleated MERV 7 (standard) or MERV 11 (optional)
(6) 24 x 24 x 2 (610 x 610 x 51)
208/230V, 460V or 575V − 60 hertz − 3 phase
NOTE − Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1 Certified in accordance with the ULE certification program, which is based on ARI Standard 340/360; 95_F (35_C) outdoor air temperature and 80_F (27_C) db/67_F
(19_C) wb entering evaporator air; minimum external duct static pressure.
2 Integrated Part Load Value tested at 80_F (27_C) outdoor air temperature.
3 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of
motors furnished by Lennox are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep
within the service factor limitations outlined on the motor nameplate.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 14
SPECIFICATIONS − STANDARD EFFICIENCY COOLING (CAV)
General
Data
Nominal Tonnage
Model No.
Efficiency Type
Blower Type
Gross Cooling Capacity − Btuh (kW)
Cooling
g
P
f
Performance
1 Net Cooling Capacity − Btuh (kW)
ARI Rated Air Flow − cfm (L/s)
Total Unit Power (kW)
1 EER (Btuh/Watt)
2 Integrated Part Load Value (Btuh/Watt)
Circuit 1
Refrigerant
g
Charge
g
Furnished (R
(R-22)
22)
Circuit 2
Circuit 3
Circuit 4
Gas Heating
Heat Input Type
Performance
Input − Btuh (KW)
First Stage
Second Stage
Output − Btuh (kW)
First Stage
Second Stage
CSA Thermal Efficiency
Gas Supply Connections
Recommended Gas Supply Pressure − Natural
LPG/Propane
Compressor Type (no.)
Net face area − sq. ft. (m2) total
Condenser
C il
Coils
Tube diameter − in. (mm)
Number of rows
Fins per inch (m)
Motor horsepower (W)
Condenser
F
Fans
Motor rpm
Total Motor watts
Diameter − in. (mm)
No. of blades
Total Air volume − cfm (L/s)
Net face area − sq. ft. (m2) total
Evaporator
p
C il
Coils
Tube diameter − in. (mm)
No. of rows
Fins per inch (m)
Drain connection − number and size
Expansion device type
3 Indoor
Nominal motor output
Blower and
Drive
Maximum usable motor output
Selection
(US Only)
Motor − Drive kit
Blowerwheelnominaldiameterxwidth
Type of filter
No. and size − in. (mm)
Electrical characteristics
Filters
17.5 Ton
17.5 Ton
LGC210S2B (R−22)
Standard
Constant Air Volume (CAV)
212,000 (62.1)
204,000 (59.8)
6800 (3210)
20.4
10.0
10.5
7 lbs. 0 oz. (3.18 kg)
7 lbs. 0 oz. (3.18 kg)
7 lbs. 0 oz. (3.18 kg)
7 lbs. 0 oz. (3.18 kg)
Low
Standard
Medium
High
1 Stage
2 Stage
2 Stage
2 Stage
169,000 (49.5)
169,000 (49.5)
234,000 (68.6)
312,000 (91.4)
−−−
260,000 (76.2)
360,000 (105.5)
480,000 (140.6)
135,000 (39.6)
−−−
−−−
−−−
−−−
208,000 (60.9)
288,000 (84.4)
384,000 (112.5)
80.0%
1 in.
7 in. w.g. (1.7 kPa)
11 in. w.g. (2.7 kPa)
Scroll (4)
56.5 (5.25)
3/8 (9.5)
1
20 (787)
(4) 1/3 (249)
1075
1370
(4) 24 (610)
3
15,850 (7480)
22.3 (2.07)
3/8 (9.5)
3
14 (551)
(1) 1 in. NPT coupling
Balanced Port Thermostatic Expansion Valve, removeable power head
3 hp (2.2 kW)
5 hp (3.7 kW)
7.5 hp (5.6 kW)
3.45 hp (2.6 kW)
5.75 hp (4.3 kW)
8.63 hp (6.4 kW)
3 hp
kit #A − 535 − 725 rpm
kit #1 − 685 − 1045 rpm
kit #2 − 685 − 1045 rpm
5 hp
kit #2 − 685 − 865 rpm
kit #3 − 850 − 865 rpm
kit #4 − 945 − 1185 rpm
7.5 hp
kit# 5 − 945 − 1185 rpm
kit# 6 − 1045 − 1285 rpm
kit# 7 − 850 − 1045 rpm
(2) 15 x 15 in. (381 x 381 mm)
Disposable, pleated MERV 7 (standard) or MERV 11 (optional)
(6) 24 x 24 x 2 (610 x 610 x 51)
208/230V, 460V or 575V − 60 hertz − 3 phase
NOTE − Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1 Certified in accordance with the ULE certification program, which is based on ARI Standard 340/360; 95_F (35_C) outdoor air temperature and 80_F (27_C) db/67_F
(19_C) wb entering evaporator air; minimum external duct static pressure.
2 Integrated Part Load Value tested at 80_F (27_C) outdoor air temperature.
3 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of
motors furnished by Lennox are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep
within the service factor limitations outlined on the motor nameplate.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 15
SPECIFICATIONS − STANDARD EFFICIENCY COOLING (CAV)
20 and 25 Ton
General
Data
G
General
l
Data
Nominal Tonnage
20 Ton
25 Ton
Model No.
LGC240S2B (R−22)
LGC300S2B (R−22)
Efficiency Type
Standard
Standard
Constant Air Volume (CAV)
Blower Type Type
Constant Air Volume (CAV)
Cooling
g
Gross Cooling Capacity − Btuh (kW)
243,000 (71.2)
302,000 (88.4)
Performance
P
f
1 232,000 (67.9)
2 286,000 (83.7)
Net Cooling Capacity − Btuh (kW)
Total Unit Power (kW)
24.4
30.1
ARI Rated Air Flow − cfm (L/s)
8000 (3775)
9000 (4250)
1 9.5
2 9.5
EER (Btuh/Watt)
3 Integrated Part Load Value (Btuh/Watt)
9.8
9.7
Refrigerant
g
Charge
g
Circuit 1
11 lbs. 0 oz. (4.99 kg)
11 lbs. 4 oz. (5.10 kg)
Furnished (R
(R-22)
22)
11 lbs. 4 oz. (5.10 kg)
Circuit 2
11 lbs. 0 oz. (4.99 kg)
Circuit 3
11 lbs. 0 oz. (4.99 kg)
11 lbs. 4 oz. (5.10 kg)
Circuit 4
11 lbs. 0 oz. (4.99 kg)
11 lbs. 4 oz. (5.10 kg)
g
g
Refrigerant
Charge
Circuit 1
Not Available
12 lbs. 4 oz. (5.56 kg)
Furnished (R-22)
(R 22)
Circuit 2
Not Available
12 lbs. 4 oz. (5.56 kg)
with Humiditrol Option
Circuit 3
Not Available
11 lbs. 4 oz. (5.10 kg)
Circuit 4
Not Available
11 lbs. 4 oz. (5.10 kg)
Gas Heating
Heat Input Type
Standard
Medium
High
Standard
Medium
High
Performance
2 Stage
2 Stage
2 Stage
2 Stage
2 Stage
2 Stage
Input − Btuh (kW)
First Stage 169,000 (49.5) 234,000 (68.6) 312,000 (91.4) 169,000 (49.5) 234,000 (68.6) 312,000 (91.4)
Second Stage 260,000 (76.2) 360,000 (105.5) 480,000 (140.6) 260,000 (76.2) 360,000 (105.5) 480,000 (140.6)
Output − Btuh (kW) Second Stage 208,000 (60.9) 288,000 (84.4) 384,000 (112.5) 208,000 (60.9) 288,000 (84.4) 384,000 (112.5)
CSA Thermal Efficiency
80.0%
80.0%
Gas Supply Connections
1 in.
1 in.
Recommended Gas Supply Pressure
Natural
7 in. w.g. (1.7 kPa)
7 in. w.g. (1.7 kPa)
LPG/Propane
11 in. w.g. (2.7 kPa)
11 in. w.g. (2.7 kPa)
Compressor Type (no.)
Scroll (4)
Scroll (4)
Condenser
Net face area − sq. ft. (m2) total
56.5 (5.25)
56.5 (5.25)
C il
Coils
3/8 (9.5)
Tube diameter − in. (mm)
3/8 (9.5)
Number of rows
2
2
Fins per inch (m)
20 (787)
20 (787)
Condenser
Motor horsepower (W)
(4) 1/3 (249)
(4) 1/2 (373)
Fans
F
1075
Motor rpm
1075
Total Motor watts
1395
1800
Diameter − in. (mm)
(4) 24 (610)
(4) 24 (610)
No. of blades
3
3
Total Air volume − cfm (L/s)
15,450 (7290)
16,000 (7550)
p
Evaporator
Net face area − sq. ft. (m2) total
22.3 (2.07)
22.3 (2.07)
Coils
C il
3/8 (9.5)
Tube diameter − in. (mm)
3/8 (9.5)
No. of rows
3
4
Fins per inch (m)
14 (551)
14 (551)
Drain connection − number and size
(1) 1 in. NPT coupling
(1) 1 in. NPT coupling
Expansion device type
Balanced Port Thermostatic Expansion Valve, removeable power head
4 Indoor
Nominal motor output
5 hp (3.7 kW)
5 hp (3.7 kW)
7.5 hp (5.6 kW)
7.5 hp (5.6 kW)
Blower and
10 hp (7.5 kW)
10 hp (7.5 kW)
Drive
Maximum usable motor output
5.75 hp (4.3 kW)
5.75 hp (4.3 kW)
Selection
(US Only)
8.63 hp (6.4 kW)
8.63 hp (6.4 kW)
11.5 hp (8.6 kW)
11.5 hp (8.6 kW)
Motor − Drive kit
5 hp
5 hp
kit #2 − 685 − 865 rpm
kit #2 − 685 − 865 rpm
kit #3 − 850 − 1045 rpm
kit #3 − 850 − 1045 rpm
kit #4 945 − 1185 rpm
kit #4 − 945−1185 rpm
7.5 hp
7.5 hp
kit #5 − 945 − 1185 rpm
kit #5 − 945 − 1185 rpm
kit #6 − 1045 − 1285 rpm
kit#6 − 1045−1285 rpm
kit #7 − 850 − 1045 rpm
kit #7 − 850 − 1045 rpm
10 hp
10 hp
kit #6 − 1045−1285 rpm
kit #6 − 1045 − 1285 rpm
kit #8 − 1135−1365 rpm
kit #8 − 1135−1365 rpm
Blowerwheelnominaldiameterxwidth
(2) 15 x 15 in. (381 x 381 mm)
(2) 15 x 15 in. (381 x 381 mm)
Filters
Type of filter
Disposable, pleated MERV 7 (standard) or MERV 11 (optional)
No. and size − in. (mm)
(6) 24 x 24 x 2 (610 x 610 x 51)
Electrical characteristics
208/230V, 460V or 575V − 60 hertz − 3 phase
NOTE − Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1 Certified in accordance with the ULE certification program, which is based on ARI Standard 340/360; 95_F (35_C) outdoor air temperature and 80_F (27_C) db/67_F
(19_C) wb entering evaporator air; minimum external duct static pressure.
2 Tested at conditions included in with ARI Standard 340/360; 95_F (35_C) outdoor air temperature and 80_F (27_C) db/67_F (19_C) wb entering evaporator air; minimum
external duct static pressure.
3 Integrated Part Load Value tested at 80_F (27_C) outdoor air temperature.
4 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of
motors furnished by Lennox are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep
within the service factor limitations outlined on the motor nameplate.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 16
13 Ton
SPECIFICATIONS − HIGH EFFICIENCY COOLING (CAV)
General
Data
D t
Nominal Tonnage
Model No.
Efficiency Type
Blower Type Type
Gross Cooling Capacity − Btuh (kW)
1 Net Cooling Capacity − Btuh (kW)
ARI Rated Air Flow − cfm (L/s)
Total Unit Power (kW)
1 EER (Btuh/Watt)
2 Integrated Part Load Value (Btuh/Watt)
Circuit 1
Refrigerant Charge
Furnished
(R-22)
F i h d (R
22)
Circuit 2
Circuit 3
Circuit 1
Refrigerant Charge
Furnished
(R-22)
F i h d (R
22)
Circuit 2
with Humiditrol Option
Circuit 3
Gas Heating
Heat Input Type
Performance
13 Ton
LGC156H2B (R−22)
High
Constant Air Volume (CAV)
Cooling
P f
Performance
Input − Btuh (kW)
First Stage
Second Stage
Output − Btuh (kW)
First Stage
Second Stage
CSA Thermal Efficiency
Gas Supply Connections
Recommended Gas Supply Pressure
Natural
LPG/Propane
Compressor Type (no.)
Condenser
C il
Coils
Condenser
F
Fans
Evaporator
C il
Coils
3
Indoor
Blower and
Drive
Selection
Net face area − sq. ft. (m2) total
Tube diameter − in. (mm) − No. of rows
Fins per inch (m)
Motor horsepower (W)
Motor rpm
Total Motor watts
Diameter − in. (mm) − No. of blades
Total Air volume − cfm (L/s)
Net face area − sq. ft. (m2) total
Tube diameter − in. (mm) − No. of rows
Fins per inch (m)
Condensate Drain − number and size
Expansion device type
Nominal motor output
Maximum usable motor output
(US Only)
Motor − Drive kit number
Blowerwheelnom. dia.xwidth−in.(mm)
Type of filter
No. and size − in. (mm)
Electrical characteristics
Filters
Low
1 Stage
160,000 (46.8)
156,000 (45.7)
5100 (2405)
12.8
12.2
13.6
11 lbs. 0 oz. (4.99 kg)
11 lbs. 0 oz. (4.99 kg)
11 lbs. 0 oz. (4.99 kg)
13 lbs. 8 oz. (6.12 kg)
13 lbs. 8 oz. (6.12 kg)
11 lbs. 0 oz. (4.99 kg)
Standard
2 Stage
Medium
2 Stage
169,000 (49.5)
169,000 (49.5)
234,000 (68.6)
−−−
260,000 (76.2)
360,000 (105.5)
135,000 (39.6)
−−−
−−−
−−−
208,000 (60.9)
288,000 (84.4)
80.0%
1 in.
7 in. w.g. (1.7 kPa)
11 in. w.g. (2.7 kPa)
Scroll (3)
56.5 (5.25)
3/8 (9.5) − 2
20 (787)
(4) 1/3 (249)
1075
1395
(4) 24 (610) − 3
15,450 (7290)
22.3 (2.07)
3/8 (9.5) − 3
14 (551)
(1) 1 in. NPT coupling
Balanced Port Thermostatic Expansion Valve, removeable power head
2 hp (1.5 kW)
3 hp (2.2 kW)
5 hp (3.7 kW)
2.3 hp (1.7 kW)
3.45 hp (2.6 kW)
5.75 hp (4.3 kW)
2 hp
kit #A − 535 − 725 rpm
3 hp
kit #A − 535 − 725 rpm
kit #1 − 685 − 865 rpm
kit #2 − 685 − 865 rpm
5 hp
kit #2 − 685 − 865 rpm
kit #3 − 850 − 1045 rpm
kit #4 − 945 − 1185 rpm
(2) 15 x 15 (381 x 381)
Disposable, pleated MERV 7 (standard) or MERV 11 (optional)
(6) 24 x 24 x 2 (610 x 610 x 51)
208/230V, 460V or 575V − 60 hertz − 3 phase
NOTE − Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1 Certified in accordance with the ULE certification program, which is based on ARI Standard 340/360; 95_F (35_C) outdoor air temperature and 80_F (27_C) db/67_F
(19_C) wb entering evaporator air; minimum external duct static pressure.
2 Integrated Part Load Value tested at 80_F (27_C) outdoor air temperature.
3 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of
motors furnished by Lennox are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep
within the service factor limitations outlined on the motor nameplate.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 17
SPECIFICATIONS − HIGH EFFICIENCY COOLING (CAV)
General
Data
D t
Cooling
Performance
Nominal Tonnage
Model No.
Efficiency Type
Blower Type
Gross Cooling Capacity − Btuh (kW)
1
Net Cooling Capacity − Btuh (kW)
ARI Rated Air Flow − cfm (L/s)
Total Unit Power (kW)
1 EER (Btuh/Watt)
2 Integrated Part Load Value (Btuh/Watt)
Refrigerant Charge
Circuit 1
Furnished
(R-22)
F i h d (R
( 22))
Circuit 2
Circuit 3
Circuit 4
Refrigerant Charge
Circuit 1
Furnished
(R-410A)
F i h d (R
( 410A))
Circuit 2
Circuit 3
Refrigerant Charge
Circuit 1
Furnished
(R-22)
F i h d (R
( 22))
Circuit 2
with Humiditrol Option
Circuit 3
Circuit 4
Gas Heating
Heat Input Type
Performance
Input − Btuh (kW)
First Stage
Second Stage
Output − Btuh (kW)
First Stage
Second Stage
CSA Thermal Efficiency
Gas Supply Connections
Recommended Gas Supply Pressure
Natural
LPG/Propane
Compressor Type (no.)
Condenser
Net face area − sq. ft. (m2) total
Coils
C il
Tube diameter − in. (mm) − No. of rows
Fins per inch (m)
Condenser
Motor horsepower (W)
Fans
F
Motor rpm
Total Motor watts
Diameter − in. (mm) − No. of blades
Total Air volume − cfm (L/s)
Evaporator
Net face area − sq. ft. (m2) total
C il
Coils
Tube diameter − in. (mm) − No. of rows
Fins per inch (m)
Condensate Drain − number and size
Expansion device type
3 Indoor
Nominal motor output
Blower and
Drive
Selection
Maximum usable motor output
(US Only)
Motor − Drive kit number
Blowerwheelnom. dia.xwidth−in.(mm)
Type of filter
No. and size − in. (mm)
Electrical characteristics
Filters
15 Ton
15 Ton
LGC180H2B (R−22)
LGC180H4B (R−410A)
High
Constant Air Volume (CAV)
188,000 (55.1) (R−22)
190,000 (55.7) (R−410A)
182,000 (53.3) (R−22
184,000 (53.9) (R−410A)
5700 (2690)
15.4 (R−22) 16.1 (R−410A)
11.8 (R−22) 11.4 (R−410A)
13.3 (R−22) 12.8 (R−410A)
11 lbs. 8 oz. (5.22 kg)
11 lbs. 8 oz. (5.22 kg)
11 lbs. 8 oz. (5.22 kg)
−−−
12 lbs. 8 oz. (5.67 kg)
12 lbs. 8 oz. (5.67 kg)
12 lbs. 8 oz. (5.67 kg)
14 lbs. 0 oz. (6.35 kg)
14 lbs. 0 oz. (6.35 kg)
11 lbs. 8 oz. (5.22 kg)
−−−
Low
Standard
Medium
High
1 Stage
2 Stage
2 Stage
2 Stage
169,000 (49.5)
169,000 (49.5)
234,000 (68.6)
312,000 (91.4)
−−−
260,000 (76.2)
360,000 (105.5)
480,000 (140.6)
135,000 (39.6)
−−−
−−−
−−−
−−−
208,000 (60.9)
288,000 (84.4)
384,000 (112.5)
80.0%
1 in.
7 in. w.g. (1.7 kPa)
11 in. w.g. (2.7 kPa)
Scroll (3)
56.5 (5.25)
3/8 (9.5) − 2
20 (787)
(4) 1/3 (249)
1075
1395
(4) 24 (610) − 3
15,450 (7290)
22.3 (2.07)
3/8 (9.5) − 3
14 (551)
(1) 1 in. NPT coupling
Balanced Port Thermostatic Expansion Valve, removeable power head
3 hp (2.2 kW)
5 hp (3.7 kW)
7.5 hp (5.6 kW)
3.45 hp (2.6 kW)
5.75 hp (4.3 kW)
8.63 hp (6.4 kW)
3 hp
kit #A − 535 − 725 rpm
kit #1 − 685 − 865 rpm
kit #2 − 685 − 865 rpm
5 hp
kit #2 − 685 − 865 rpm
kit #3 − 850 − 1045 rpm
kit #4 − 945 − 1185 rpm
7.5 hp
kit# 5 − 945 − 1185 rpm
kit# 6 − 1045 − 1285 rpm
kit# 7 − 850 − 1045 rpm
(2) 15 x 15 (381 x 381)
Disposable, pleated MERV 7 (standard) or MERV 11 (optional)
(6) 24 x 24 x 2 (610 x 610 x 51)
208/230V, 460V or 575V − 60 hertz − 3 phase
NOTE − Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1 Certified in accordance with the ULE certification program, which is based on ARI Standard 340/360; 95_F (35_C) outdoor air temperature and 80_F (27_C) db/67_F
(19_C) wb entering evaporator air; minimum external duct static pressure.
2 Integrated Part Load Value tested at 80_F (27_C) outdoor air temperature.
3 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of
motors furnished by Lennox are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep
within the service factor limitations outlined on the motor nameplate.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 18
SPECIFICATIONS − HIGH EFFICIENCY COOLING (CAV)
General
Data
Nominal Tonnage
Model No.
Efficiency Type
Blower Type
Cooling
Gross Cooling Capacity − Btuh (kW)
1 Net Cooling Capacity − Btuh (kW)
Performance
P
f
ARI Rated Air Flow − cfm (L/s)
Total Unit Power (kW)
1 EER (Btuh/Watt)
2 Integrated Part Load Value (Btuh/Watt)
Refrigerant Charge
Circuit 1
Furnished
(R-22)
F i h d (R
( 22))
Circuit 2
Circuit 3
Circuit 4
Refrigerant Charge
Circuit 1
Furnished
(R-410A)
( 410A))
F i h d (R
Circuit 2
Circuit 3
Refrigerant Charge
Circuit 1
Furnished
(R-22)
F i h d (R
( 22))
Circuit 2
with Humiditrol Option
Circuit 3
Circuit 4
Gas Heating
Heat Input Type
Performance
Input − Btuh (kW)
First Stage
Second Stage
Output − Btuh (kW)
First Stage
Second Stage
CSA Thermal Efficiency
Gas Supply Connections
Recommended Gas Supply Pressure
Natural
LPG/Propane
Compressor Type (no.)
Condenser
Net face area − sq. ft. (m2) total
Coils
C il
Tube diameter − in. (mm) − No. of rows
Fins per inch (m)
Condenser
Motor horsepower (W)
F
Fans
Motor rpm
Total Motor watts
Diameter − in. (mm) − No. of blades
Total Air volume − cfm (L/s)
Evaporator
Net face area − sq. ft. (m2) total
C il
Coils
Tube diameter − in. (mm) − No. of rows
Fins per inch (m)
Condensate Drain − number and size
Expansion device type
3 Indoor
Nominal motor output
Blower and
Drive
Selection
Maximum usable motor output
(US Only)
Motor − Drive kit number
Blowerwheelnom. dia.xwidth−in.(mm)
Type of filter
No. and size − in. (mm)
Electrical characteristics
Filters
17.5 Ton
17.5 Ton
LGC210H2B (R−22)
High
Constant Air Volume (CAV)
218,000 (63.9)
210,000 (61.5)
6600 (3115)
18.3
11.5
12.3
11 lbs. 0 oz. (4.99 kg)
11 lbs. 0 oz. (4.99 kg)
11 lbs. 0 oz. (4.99 kg)
11 lbs. 0 oz. (4.99 kg)
−−−
−−−
−−−
13 lbs. 0 oz. (5.90 kg)
13 lbs. 0 oz. (5.90 kg)
11 lbs. 0 oz. (4.99 kg)
11 lbs. 0 oz. (4.99 kg)
Low
Standard
Medium
High
1 Stage
2 Stage
2 Stage
2 Stage
169,000 (49.5)
169,000 (49.5)
234,000 (68.6)
312,000 (91.4)
−−−
260,000 (76.2)
360,000 (105.5)
480,000 (140.6)
135,000 (39.6)
−−−
−−−
−−−
−−−
208,000 (60.9)
288,000 (84.4)
384,000 (112.5)
80.0%
1 in.
7 in. w.g. (1.7 kPa)
11 in. w.g. (2.7 kPa)
Scroll (4)
56.5 (5.25)
3/8 (9.5) − 2
20 (787)
(4) 1/3 (249)
1075
1395
(4) 24 (610) − 3
15,450 (7290)
22.3 (2.07)
3/8 (9.5) − 4
14 (551)
(1) 1 in. NPT coupling
Balanced Port Thermostatic Expansion Valve, removeable power head
3 hp (2.2 kW)
5 hp (3.7 kW)
7.5 hp (5.6 kW)
3.45 hp (2.6 kW)
5.75 hp (4.3 kW)
8.63 hp (6.4 kW)
3 hp
kit #A − 535 − 725 rpm
kit #1 − 685 − 1045 rpm
kit #2 − 685 − 1045 rpm
5 hp
kit #2 − 685 − 865 rpm
kit #3 − 850 − 865 rpm
kit #4 − 945 − 1185 rpm
7.5 hp
kit# 5 − 945 − 1185 rpm
kit# 6 − 1045 − 1285 rpm
kit# 7 − 850 − 1045 rpm
(2) 15 x 15 (381 x 381)
Disposable, pleated MERV 7 (standard) or MERV 11 (optional)
(6) 24 x 24 x 2 (610 x 610 x 51)
208/230V, 460V or 575V − 60 hertz − 3 phase
NOTE − Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1 Certified in accordance with the ULE certification program, which is based on ARI Standard 340/360; 95_F (35_C) outdoor air temperature and 80_F (27_C) db/67_F
(19_C) wb entering evaporator air; minimum external duct static pressure.
2 Integrated Part Load Value tested at 80_F (27_C) outdoor air temperature.
3 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of
motors furnished by Lennox are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep
within the service factor limitations outlined on the motor nameplate.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 19
SPECIFICATIONS − HIGH EFFICIENCY COOLING (CAV)
General
Data
D t
Cooling
Performance
Nominal Tonnage (kW)
Model No.
Efficiency Type
Blower Type
Gross Cooling Capacity − Btuh (kW)
1 Net
Gas Heating
Performance
Cooling Capacity − Btuh (kW)
ARI Rated Air Flow − cfm (L/s)
Total Unit Power (kW)
1 EER (Btuh/Watt)
2 Integrated Part Load Value (Btuh/Watt)
Refrigerant Charge
Circuit 1
F i h d (R
Furnished
(R-22)
( 22))
Circuit 2
Circuit 3
Circuit 4
Refrigerant Charge
Circuit 1
F i h d (R
Furnished
(R-410A)
( 410A))
Circuit 2
Circuit 3
Circuit 4
Refrigerant Charge
Circuit 1
Furnished
(R-22)
F i h d (R
( 22))
Circuit 2
with Humiditrol Option
Circuit 3
Circuit 4
Heat Input Type
Input − Btuh (kW)
First Stage
Second Stage
Output − Btuh (kW) Second Stage
CSA Thermal Efficiency
Gas Supply Connections
Recommended Gas Supply Pressure
Natural
LPG/Propane
Compressor Type (no.)
Condenser
Net face area − sq. ft. (m2) total
Coils
Tube diameter − in. (mm)
Number of rows
Fins per inch (m)
Condenser
Motor horsepower (W)
Fans
Motor rpm
Total Motor watts
Diameter − in. (mm)
Number of blades
Total Air volume − cfm (L/s)
Evaporator
Net face area − sq. ft. (m2) total
Coils
Tube diameter − in. (mm)
Number of rows
Fins per inch (m)
Condensate Drain − number and size
Expansion device type
3 Indoor
Nominal motor output
Blower and
Max. usable motor output (US Only)
Di
Drive
Motor − Drive kit
Selection
Filters
Blowerwheelnominaldia.xwidth
Type of filter
Number and size − in. (mm)
Electrical characteristics
20 and 21 Ton
20 Ton
21 Ton
LGA248H2B (R−22)
LGA240H2B (R−22)
LGA248H4B (R−410A)
LGA240H4B (R−410A)
High
High
Constant Air Volume (CAV)
Constant Air Volume (CAV)
252,000 (73.8) (R−22)
257,000 (75.3) (R−22)
254,000 (74.4) (R−410A)
257,000 (75.3) (R−410A)
242,000 (70.9) (R−22)
248,000 (72.6) (R−22)
244,000 (71.5) (R−410A)
248,000 (72.6) (R−410A)
7500 (3540)
8,000 (3775)
22.0 (R−22) 23.2 (R−410A)
21.2
11.0 (R−22) 10.5 (R−410A)
11.7
11.8 (R−22) 11.5 (R−410A)
12.3 (R−22) 12.7 (R−410A)
11 lbs. 4 oz. (5.10 kg)
12 lbs. 8 oz. (5.67 kg)
11 lbs. 4 oz. (5.10 kg)
12 lbs. 8 oz. (5.67 kg)
11 lbs. 4 oz. (5.10 kg)
12 lbs. 8 oz. (5.67 kg)
11 lbs. 4 oz. (5.10 kg)
12 lbs. 8 oz. (5.67 kg)
11 lbs. 4 oz. (5.10 kg)
13 lbs. 0 oz. (5.90 kg)
11 lbs. 4 oz. (5.10 kg)
13 lbs. 0 oz. (5.90 kg)
11 lbs. 4 oz. (5.10 kg)
13 lbs. 0 oz. (5.90 kg)
11 lbs. 4 oz. (5.10 kg)
13 lbs. 0 oz. (5.90 kg)
12 lbs. 4 oz. (5.56 kg)
--12 lbs. 4 oz. (5.56 kg)
----11 lbs. 4 oz. (5.10 kg)
11 lbs. 4 oz. (5.10 kg)
--Standard
Medium
High
Standard
Medium
High
2 Stage
2 Stage
2 Stage
2 Stage
2 Stage
2 Stage
169,000 (49.5) 234,000 (68.6) 312,000 (91.4) 169,000 (49.5) 234,000 (68.6) 312,000 (91.4)
260,000 (76.2) 360,000 (105.5) 480,000 (140.6) 260,000 (76.2) 360,000 (105.5) 480,000 (140.6)
208,000 (60.9) 288,000 (84.4) 384,000 (112.5) 208,000 (60.9) 288,000 (84.4) 384,000 (112.5)
80.0%
80.0%
1 in.
1
7 in. w.g. (1.7 kPa)
7 in. w.g. (1.7 kPa)
11 in. w.g. (2.7 kPa)
11 in. w.g. (2.7 kPa)
Scroll (4)
Scroll (4)
56.5 (5.25)
70.6 (6.6)
3/8 (9.5)
3/8 (9.5)
2
2
20 (787)
20 (787)
(4) 1/3 (249)
(6) 1/3 (249)
1075
1075
1395
2500
(4) 24 (610)
(6) 24 (610)
3
3
15,450 (7290)
21,500 (10,145)
22.3 (2.07)
33.3 (3.1)
3/8 (9.5)
3/8 (9.5)
4
3
14 (551)
14 (551)
(1) 1 in. NPT coupling
(1) 1 in. NPT coupling
Balanced Port Thermostatic Expansion Valve, removeable power head
5 hp (3.7 kW) − 7.5 hp (5.6 kW) − 10 hp (7.5 kW)
5.75 hp (4.3 kW) − 8.63 hp (6.4 kW) − 11.5 hp (8.6 kW)
5 hp
5 hp
kit #2 − 685 − 865 rpm
kit #1 − 660 − 810 rpm
kit #3 − 850 − 1045 rpm
kit #2 − 770 − 965 rpm
kit #4 945 − 1185 rpm
kit #6 − 560 − 710 rpm
7.5 hp
kit #5 − 945 − 1185 rpm
7.5 hp
kit #6 − 1045 − 1285 rpm
kit #3 − 715 − 880 rpm
kit #7 − 850 − 1045 rpm
kit#4 − 770 − 965 rpm
10 hp
kit #6 − 1045−1285 rpm
10 hp
kit #8 − 1135−1365 rpm
kit #3 − 715 − 880 rpm
kit #5 − 850 − 1045 rpm
(2) 15 x 15 in. (381 x 381 mm)
(2) 18 x 15 in. (457 x 381 mm)
Disposable, pleated MERV 7 (standard) or MERV 11 (optional)
(6) 24 x 24 x 2 (610x610x51)
(12) 20 x 20 x 2 (508 x 508 x 51)
208/230V, 460V or 575V − 60 hertz − 3 phase
NOTE − Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1 Certified in accordance with the ULE certification program, which is based on ARI Standard 340/360; 95_F (35_C) outdoor air temperature and 80_F (27_C) db/67_F
(19_C) wb entering evaporator air; minimum external duct static pressure.
2 Integrated Part Load Value tested at 80_F (27_C) outdoor air temperature.
3 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of
motors furnished by Lennox are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep
within the service factor limitations outlined on the motor nameplate.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 20
21 Ton
SPECIFICATIONS − HIGH EFFICIENCY COOLING (VAV)
General
Data
D t
Cooling
P f
Performance
Gas Heating
Performance
Nominal Tonnage (kW)
Model No.
Efficiency Type
Blower Type
Gross Cooling Capacity − Btuh (kW)
1 Net Cooling Capacity − Btuh (kW)
ARI Rated Air Flow − cfm (L/s)
Total Unit Power (kW)
1 EER (Btuh/Watt)
2 Integrated Part Load Value (Btuh/Watt)
Refrigerant Charge
Circuit 1
F i h d (R
Furnished
(R-22)
22)
Circuit 2
Circuit 3
Circuit 4
Heat Input Type
169,000 (49.5)
234,000 (68.6)
312,000 (91.4)
Btuh (kW)
260,000 (76.2)
360,000 (105.5)
480,000 (140.6)
Output − Second Stage
Btuh (kW)
208,000 (60.9)
288,000 (84.4)
384,000 (112.5)
Indoor
Blower and
Drive
Selection
80.0%
1
Natural
7 in. w.g. (1.7 kPa)
LPG/Propane
11 in. w.g. (2.7 kPa)
Compressor Type (no.)
3
High
2 Stage
Btuh (kW)
Gas Supply Connections
Evaporator
Coils
Standard
2 Stage
Input − First Stage
Recommended Gas Supply Pressure
Condenser
Fans
257,000 (75.3)
248,000 (72.6)
8,000 (3775)
21.0
11.8
14.7
12 lbs. 8 oz. (5.67 kg)
12 lbs. 8 oz. (5.67 kg)
12 lbs. 8 oz. (5.67 kg)
12 lbs. 8 oz. (5.67 kg)
Medium
2 Stage
Input − Second Stage
CSA Thermal Efficiency
Condenser
Coils
21 Ton
LGA248H2V (R−22)
High
Variable Air Volume (VAV)
Scroll (4)
Net face area − sq. ft. (m2) total
Tube diameter − in. (mm)
Number of rows
Fins per inch (m)
Motor horsepower (W)
Motor rpm
Total Motor watts
Diameter − in. (mm)
Number of blades
Total Air volume − cfm (L/s)
Net face area − sq. ft. (m2) total
Tube diameter − in. (mm)
Number of rows
Fins per inch (m)
Condensate Drain − number and size
Expansion device type
Nominal motor output
Motor − Drive kit
(maximum rpm,
60hz inverter frequency setting)
70.6 (6.6)
3/8 (9.5)
2
20 (787)
(6) 1/3 (249)
1075
2500
(6) 24 (610)
3
21,500 (10,145)
33.3 (3.1)
3/8 (9.5)
3
14 (551)
(1) 1 in. NPT coupling
Balanced Port Thermostatic Expansion Valve, removeable power head
5 hp (3.7 kW) − 7.5 hp (5.6 kW) − 10 hp (7.5 kW)
5 hp
kit #7 − 965 rpm
7.5 hp
kit#8 − 965 rpm
10 hp
kit #9 − 1045 rpm
Filters
Blowerwheelnominaldia.xwidth
Type of filter
Number and size − in. (mm)
Electrical characteristics
(2) 18 x 15 in. (457 x 381 mm)
Disposable, pleated MERV 7 (standard) or MERV 11 (optional)
(12) 20 x 20 x 2 (508 x 508 x 51)
208/230V, 460V or 575V − 60 hertz − 3 phase
NOTE − Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1 Certified in accordance with the ULE certification program, which is based on ARI Standard 340/360; 95_F (35_C) outdoor air temperature and 80_F (27_C) db/67_F
(19_C) wb entering evaporator air; minimum external duct static pressure.
2 Integrated Part Load Value tested at 80_F (27_C) outdoor air temperature.
3 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. If motors of comparable output
are used, be sure to keep within the service factor limitations outlined on the motor nameplate.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 21
SPECIFICATIONS − HIGH EFFICIENCY COOLING (CAV)
Nominal Tonnage (kW)
General
D t
Data
Model No.
Efficiency Type
Cooling
Performance
Blower Type
Gross Cooling Capacity − Btuh (kW)
1 Net
Gas Heating
Performance
Cooling Capacity − Btuh (kW)
ARI Rated Air Flow − cfm (L/s)
Total Unit Power (kW)
1 EER (Btuh/Watt)
2 Integrated Part Load Value (Btuh/Watt)
g
g
Refrigerant
Charge
Circuit 1
Furnished
(R-22)
F i h d (R
22)
Circuit 2
Circuit 3
Circuit 4
g
g
Refrigerant
Charge
Circuit 1
Furnished
(R-410A)
F i h d (R
410A)
Circuit 2
Circuit 3
Heat Input Type
Input − Btuh (kW)
First Stage
Second Stage
Output − Btuh (kW) Second Stage
CSA Thermal Efficiency
Gas Supply Connections
Recommended Gas Supply Pressure
Natural
LPG/Propane
Compressor Type (no.)
Condenser
Net face area − sq. ft. (m2) total
Coils
C il
Tube diameter − in. (mm)
Number of rows
Fins per inch (m)
Condenser
Motor horsepower (W)
F
Fans
Motor rpm
Total Motor watts
Diameter − in. (mm)
Number of blades
Total Air volume − cfm (L/s)
p
Evaporator
Net face area − sq. ft. (m2) total
Coils
C il
Tube diameter − in. (mm)
Number of rows
Fins per inch (m)
Condensate Drain − number and size
Expansion device type
3 Indoor
Nominal motor output
Blower
and
Bl
d
Max. usable motor output (US Only)
Drive
Motor − Drive kit
Selection
Blowerwheelnominaldiameterxwidth
Type of filter
Number and size − in. (mm)
Electrical characteristics
Filters
25 and 30 Ton
25 Ton
30 Ton
LGC300H2B (R−22)
LGA360H2B (R−22)
LGA360H4B (R−410A)
High
High
Constant Air Volume (CAV)
311,000 (91.1)
Constant Air Volume (CAV)
355,000 (104.0) (R−22)
377,000 (110.5) (R−410A)
300,000 (87.9)
336,000 (98.4) (R−22)
360,000 (105.5) (R−410A)
9500 (4484)
10,500 (4955)
28.4
32.9 (R−22) 37.1 (R−410A)
11.0
10.2 (R−22) 9.7 (R−410A)
11.5
10.6 (R−22) 10.4 (R−410A)
11 lbs. 0 oz. (4.99 kg)
17 lbs. 0 oz (7.71 kg)
17 lbs. 0 oz (7.71 kg)
11 lbs. 0 oz. (4.99 kg)
11 lbs. 0 oz. (4.99 kg)
17 lbs. 0 oz (7.71 kg)
11 lbs. 0 oz. (4.99 kg)
----18 lbs. 8 oz. (8.39 kg)
18 lbs. 8 oz. (8.39 kg)
----18 lbs. 8 oz. (8.39 kg)
Standard
Medium
High
Standard
Medium
High
2 Stage
2 Stage
2 Stage
2 Stage
2 Stage
2 Stage
169,000 (49.5) 234,000 (68.6) 312,000 (91.4) 169,000 (49.5) 234,000 (68.6) 312,000 (91.4)
260,000 (76.2) 360,000 (105.5) 480,000 (140.6) 260,000 (76.2) 360,000 (105.5) 480,000 (140.6)
208,000 (60.9) 288,000 (84.4) 384,000 (112.5) 208,000 (60.9) 288,000 (84.4) 384,000 (112.5)
80.0%
80.0%
1
1
7 in. w.g. (1.7 kPa)
7 in. w.g. (1.7 kPa)
11 in. w.g. (2.7 kPa)
11 in. w.g. (2.7 kPa)
Scroll (4)
Scroll (3)
70.6 (6.6)
70.6 (6.6)
3/8 (9.5)
3/8 (9.5)
2
2
20 (787)
20 (787)
(6) 1/3 (249)
(6) 1/3 (249)
1075
1075
2500
2500
(6) 24 (610)
(6) 24 (610)
3
3
21,500 (10,145)
21,500 (10,145)
33.3 (3.1)
33.3 (3.1)
3/8 (9.5)
3/8 (9.5)
3
3
14 (551)
14 (551)
(1) 1 in. NPT coupling
(1) 1 in. NPT coupling
Balanced Port Thermostatic Expansion Valve, removeable power head
5 hp (3.7 kW) − 7.5 hp (5.6 kW) − 10 hp (7.5 kW)
5.75 hp (4.3 kW) − 8.63 hp (6.4 kW) − 11.5 hp (8.6 kW)
5 hp
5 hp
kit #1 − 660 − 810 rpm
kit #1 − 660 − 810 rpm
kit #2 − 770 − 965 rpm
kit #2 − 770 − 965 rpm
kit #6 − 560 − 710 rpm
kit #6 − 560 − 710 rpm
7.5 hp
7.5 hp
kit #3 − 715 − 880 rpm
kit #3 − 715 − 880 rpm
kit#4 − 770 − 965 rpm
kit#4 − 770 − 965 rpm
10 hp
10 hp
kit #3 − 715 − 880 rpm
kit #3 − 715 − 880 rpm
kit #5 − 850 − 1045 rpm
kit #5 − 850 − 1045 rpm
(2) 18 x 15 in. (457 x 381 mm)
Disposable, pleated MERV 7 (standard) or MERV 11 (optional)
(12) 20 x 20 x 2 (508 x 508 x 51)
208/230V, 460V or 575V − 60 hertz − 3 phase
NOTE − Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1 Tested at conditions included in with ARI Standard 340/360; 95_F (35_C) outdoor air temperature and 80_F (27_C) db/67_F (19_C) wb entering evaporator air; minimum
external duct static pressure.
2 Integrated Part Load Value tested at 80_F (27_C) outdoor air temperature.
3 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of
motors furnished by Lennox are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep
within the service factor limitations outlined on the motor nameplate.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 22
25 and 30 Ton
SPECIFICATIONS − HIGH EFFICIENCY COOLING (VAV)
General
D t
Data
Nominal Tonnage (kW)
Model No.
Efficiency Type
Blower Type
Cooling
g
Gross Cooling Capacity − Btuh (kW)
P
f
Performance
1 Net Cooling Capacity − Btuh (kW)
ARI Rated Air Flow − cfm (L/s)
Total Unit Power (kW)
1 EER (Btuh/Watt)
2 Integrated Part Load Value (Btuh/Watt)
Refrigerant
Charge
g
g
Circuit 1
F i h d (R
22)
Furnished
(R-22)
Circuit 2
Circuit 3
Circuit 4
Gas Heating
Performance
Heat Input Type
25 Ton
30 Ton
LGC300H2V (R−22)
LGC360H2V (R−22)
High
High
Variable Air Volume (VAV)
309,000 (90.5)
300,000 (87.9)
9000 (4245)
27.8
10.8
13.4
12 lbs. 0 oz. (5.44 kg)
12 lbs. 0 oz. (5.44 kg)
12 lbs. 0 oz. (5.44 kg)
12 lbs. 0 oz. (5.44 kg)
Variable Air Volume (VAV)
348,000 (101.9)
336,000 (98.4)
10,500 (4955)
32.9
10.3
13.0
12 lbs. 0 oz (5.44 kg)
11 lbs. 0 oz (4.99 kg)
11 lbs. 0 oz (4.99 kg)
11 lbs. 0 oz (4.99 kg)
Standard
2 Stage
Medium
2 Stage
High
2 Stage
Standard
2 Stage
Medium
2 Stage
High
2 Stage
Input − First Stage
Btuh (kW) 169,000 (49.5) 234,000 (68.6) 312,000 (91.4) 169,000 (49.5) 234,000 (68.6) 312,000 (91.4)
Input − Second Stage
Btuh (kW) 260,000 (76.2) 360,000 (105.5) 480,000 (140.6) 260,000 (76.2) 360,000 (105.5) 480,000 (140.6)
Output − Second Stage
Btuh (kW) 208,000 (60.9) 288,000 (84.4) 384,000 (112.5) 208,000 (60.9) 288,000 (84.4) 384,000 (112.5)
CSA Thermal Efficiency
80.0%
80.0%
Gas Supply Connections
1
1
Recommended Gas Supply Pressure
Natural
7 in. w.g. (1.7 kPa)
7 in. w.g. (1.7 kPa)
LPG/Propane
11 in. w.g. (2.7 kPa)
11 in. w.g. (2.7 kPa)
Compressor Type (no.)
Scroll (4)
Scroll (4)
Condenser
Net face area − sq. ft. (m2) total
70.6 (6.6)
70.6 (6.6)
C il
Coils
Tube diameter − in. (mm)
3/8 (9.5)
3/8 (9.5)
Number of rows
2
2
Fins per inch (m)
20 (787)
20 (787)
Condenser
Motor horsepower (W)
(6) 1/3 (249)
(6) 1/3 (249)
F
Fans
Motor rpm
1075
1075
Total Motor watts
2500
2500
Diameter − in. (mm)
(6) 24 (610)
(6) 24 (610)
Number of blades
3
3
Total Air volume − cfm (L/s)
21,500 (10,145)
21,500 (10,145)
Evaporator
p
Net face area − sq. ft. (m2) total
33.3 (3.1)
33.3 (3.1)
C il
Coils
3/8 (9.5)
Tube diameter − in. (mm)
3/8 (9.5)
Number of rows
3
3
Fins per inch (m)
14 (551)
14 (551)
Condensate Drain − number and size
(1) 1 in. NPT coupling
(1) 1 in. NPT coupling
Expansion device type
Balanced Port Thermostatic Expansion Valve, removeable power head
3 Indoor
Nominal motor output
5 hp (3.7 kW) − 7.5 hp (5.6 kW) − 10 hp (7.5 kW)
Bl
d
Blower
and
Motor − Drive kit
5 hp
5 hp
Drive
kit #7 − 965 rpm
kit #7 − 965 rpm
(maximum rpm,
Selection
60hz inverter frequency setting)
7.5 hp
7.5 hp
kit#8 − 965 rpm
kit#8 − 965 rpm
10 hp
kit #9 − 1045 rpm
Blowerwheelnominaldiameterxwidth
Type of filter
Number and size − in. (mm)
Electrical characteristics
Filters
10 hp
kit #9 − 1045 rpm
(2) 18 x 15 in. (457 x 381 mm)
Disposable, pleated MERV 7 (standard) or MERV 11 (optional)
(12) 20 x 20 x 2 (508 x 508 x 51)
208/230V, 460V or 575V − 60 hertz − 3 phase
NOTE − Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1 Tested at conditions included in with ARI Standard 340/360; 95_F (35_C) outdoor air temperature and 80_F (27_C) db/67_F (19_C) wb entering evaporator air; minimum
external duct static pressure.
2 Integrated Part Load Value tested at 80_F (27_C) outdoor air temperature.
3 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. If motors of comparable output
are used, be sure to keep within the service factor limitations outlined on the motor nameplate.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 23
COOLING RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
13 TON HIGH EFFICIENCY − LGC156H (R−22/CAV) − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
4160
5200
6240
4160
5200
6240
4160
5200
6240
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
1965
2455
2945
1965
2455
2945
1965
2455
2945
105.6
110.2
113.9
113.2
117.3
120.4
121.4
125.7
128.7
30.9
32.3
33.4
33.2
34.4
35.3
35.6
36.8
37.7
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
4.67
.64
4.69
.69
4.71
.74
4.70
.50
4.73
.53
4.75
.55
4.75
.38
4.77
.39
4.79
.40
80_F
27_C
.79
.87
.94
.61
.66
.71
.48
.51
.54
85_F
29_C
.94
1.00
1.00
.74
.82
.91
.59
.63
.68
Total
Cooling
Capacity
kBtuh
102.8
107.2
110.7
110.0
114.0
116.8
117.9
121.9
124.7
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
30.1 5.27
.64
31.4 5.29
.70
32.4 5.31
.76
32.2 5.30
.51
33.4 5.32
.53
34.2 5.34
.56
34.6 5.34
.38
35.7 5.36
.39
36.5 5.38
.40
80_F
27_C
.80
.89
.96
.62
.67
.73
.49
.52
.55
85_F
29_C
.96
1.00
1.00
.76
.84
.92
.59
.64
.70
Total
Cooling
Capacity
kBtuh kW
99.6
103.8
107.2
106.4
110.1
112.8
114.1
117.8
120.4
29.2
30.4
31.4
31.2
32.3
33.1
33.4
34.5
35.3
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
5.95
.65
5.97
.71
5.99
.77
5.99
.51
6.00
.54
6.02
.57
6.02
.38
6.03
.39
6.05
.40
80_F
27_C
.82
.90
.98
.63
.68
.75
.49
.52
.55
85_F
29_C
.97
1.00
1.00
.77
.86
.94
.60
.65
.72
Total
Cooling
Capacity
kBtuh kW
96.1
99.9
103.5
102.5
106.0
108.5
109.8
113.3
115.7
28.2
29.3
30.3
30.0
31.1
31.8
32.2
33.2
33.9
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
75_F
80_F 85_F
Input
24_C 27_C 29_C
6.71
.66
.83
.99
6.74
.73
.93
1.00
6.75
.79
.99
1.00
6.74
.52
.64
.79
6.76
.55
.70
.89
6.78
.58
.77
.97
6.78
.38
.50
.61
6.80
.40
.53
.67
6.81
.41
.56
.74
13 TON HIGH EFFICIENCY − LGC156H (R−22/CAV) − ALL COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
4160
5200
6240
4160
5200
6240
4160
5200
6240
85_F (29_C)
Total
Cooling
Capacity
L/s kBtuh kW
1965
2455
2945
1965
2455
2945
1965
2455
2945
150.4
156.7
161.9
160.7
166.2
170.2
172.2
177.8
181.6
44.1
45.9
47.4
47.1
48.7
49.9
50.5
52.1
53.2
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
9.03
.68
9.06
.74
9.09
.80
9.09
.53
9.12
.56
9.14
.59
9.15
.40
9.17
.41
9.19
.42
80_F
27_C
.84
.92
.99
.66
.71
.77
.52
.55
.58
85_F
29_C
.98
1.00
1.00
.79
.88
.96
.63
.69
.74
Total
Cooling
Capacity
kBtuh
145.1
150.9
156.3
154.8
160.0
163.7
165.8
171.0
174.6
105_F (41_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
42.5 10.18 .69
44.2 10.22 .75
45.8 10.25 .82
45.4 10.24 .54
46.9 10.26 .57
48.0 10.29 .60
48.6 10.29 .40
50.1 10.32 .41
51.2 10.34 .43
80_F
27_C
.85
.94
1.00
.67
.72
.79
.52
.56
.59
85_F
29_C
1.00
1.00
1.00
.81
.90
.98
.64
.70
.76
Total
Cooling
Capacity
kBtuh kW
139.2
144.8
150.7
148.5
153.3
156.6
159.0
163.6
166.9
40.8
42.4
44.2
43.5
44.9
45.9
46.6
47.9
48.9
115_F (46_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
11.51 .70
11.54 .77
11.54 .84
11.54 .55
11.58 .58
11.60 .62
11.59 .41
11.64 .42
11.64 .43
80_F
27_C
.87
.96
1.00
.68
.74
.81
.53
.57
.60
85_F
29_C
1.00
1.00
1.00
.83
.93
1.00
.66
.72
.79
Total
Cooling
Capacity
kBtuh kW
132.9
138.5
144.5
141.6
145.9
149.2
151.7
155.8
158.7
38.9
40.6
42.3
41.5
42.8
43.7
44.5
45.7
46.5
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
12.98 .72
.90
1.00
13.01 .79
.99
1.00
13.02 .87
1.00
1.00
13.01 .56
.70
.86
13.05 .59
.77
.95
13.07 .63
.84
1.00
13.07 .41
.54
.67
13.10 .42
.58
.74
13.12 .44
.62
.81
15 TON STANDARD EFFICIENCY − LGC180S (R−22/CAV) − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
4800
6000
7200
4800
6000
7200
4800
6000
7200
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
2265
2830
3400
2265
2830
3400
2265
2830
3400
123.4
128.2
132.0
131.2
135.4
138.3
139.5
143.7
146.5
36.2
37.6
38.7
38.5
39.7
40.5
40.9
42.1
42.9
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
7.02
.66
7.13
.71
7.20
.77
7.18
.53
7.28
.55
7.34
.58
7.36
.40
7.46
.41
7.53
.42
80_F
27_C
.80
.88
.94
.64
.69
.74
.51
.54
.57
85_F
29_C
.94
1.00
1.00
.77
.84
.91
.62
.66
.72
Total
Cooling
Capacity
kBtuh
120.2
124.8
128.5
127.7
131.8
134.7
136.0
140.0
142.8
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
35.2 7.72
.67
36.6 7.82
.72
37.7 7.90
.78
37.4 7.88
.53
38.6 7.98
.55
39.5 8.04
.58
39.9 8.06
.40
41.0 8.16
.41
41.9 8.22
.42
80_F
27_C
.81
.89
.96
.65
.69
.75
.51
.54
.57
85_F
29_C
.95
1.00
1.00
.78
.86
.93
.62
.67
.73
Total
Cooling
Capacity
kBtuh kW
116.3
120.8
124.5
123.7
127.6
130.4
131.8
135.6
138.2
34.1
35.4
36.5
36.3
37.4
38.2
38.6
39.7
40.5
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
8.52
.68
8.62
.73
8.71
.79
8.69
.53
8.78
.56
8.85
.59
8.87
.40
8.97
.41
9.03
.42
80_F
27_C
.83
.91
.97
.65
.71
.77
.52
.55
.58
85_F
29_C
.97
1.00
1.00
.79
.87
.95
.63
.68
.74
Total
Cooling
Capacity
kBtuh kW
112.1
116.5
120.2
119.2
123.0
125.6
127.1
130.8
133.1
32.9
34.1
35.2
34.9
36.0
36.8
37.2
38.3
39.0
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
9.45
.69
.85
.98
9.55
.75
.93
1.00
9.63
.81
.99
1.00
9.61
.54
.66
.81
9.71
.57
.72
.89
9.79
.60
.79
.96
9.82
.40
.52
.64
9.90
.41
.55
.70
9.98
.43
.59
.76
15 TON STANDARD EFFICIENCY − LGC180S (R−22/CAV) − ALL COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
4800
6000
7200
4800
6000
7200
4800
6000
7200
85_F (29_C)
Total
Cooling
Capacity
L/s kBtuh kW
2265
2830
3400
2265
2830
3400
2265
2830
3400
176.3
183.2
188.8
187.6
193.5
197.7
199.8
205.6
209.5
51.7
53.7
55.3
55.0
56.7
57.9
58.6
60.3
61.4
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
12.81 .69
12.96 .74
13.09 .80
13.06 .54
13.20 .57
13.31 .60
13.34 .41
13.49 .42
13.58 .43
80_F
27_C
.84
.91
.97
.67
.72
.78
.53
.56
.59
85_F
29_C
.97
1.00
1.00
.80
.88
.95
.64
.70
.75
Total
Cooling
Capacity
kBtuh
169.9
176.6
182.2
180.7
186.4
190.4
192.6
198.2
201.8
Comp
Motor
kW
75_F
kW Input
24_C
49.8 14.20 .70
51.8 14.35 .76
53.4 14.48 .82
53.0 14.45 .55
54.6 14.60 .58
55.8 14.72 .61
56.4 14.76 .41
58.1 14.89 .42
59.1 15.01 .43
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 24
105_F (41_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
80_F
27_C
.85
.93
.99
.68
.73
.80
.53
.57
.60
85_F
29_C
.98
1.00
1.00
.82
.90
.97
.66
.71
.77
Total
Cooling
Capacity
kBtuh kW
163.3
169.6
175.5
173.6
178.8
182.6
185.1
190.3
193.8
47.9
49.7
51.4
50.9
52.4
53.5
54.2
55.8
56.8
115_F (46_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
15.75 .71
15.93 .78
16.08 .84
16.05 .56
16.19 .59
16.31 .62
16.37 .41
16.51 .43
16.61 .44
80_F
27_C
.87
.95
1.00
.69
.75
.82
.54
.58
.61
85_F
29_C
1.00
1.00
1.00
.83
.92
.98
.67
.73
.79
Total
Cooling
Capacity
kBtuh kW
156.8
162.9
169.1
166.5
171.4
174.8
177.5
182.1
185.3
46.0
47.7
49.6
48.8
50.2
51.2
52.0
53.4
54.3
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
17.52 .73
.89
1.00
17.73 .79
.97
1.00
17.91 .86
1.00
1.00
17.83 .56
.70
.85
18.01 .60
.77
.94
18.11 .64
.84
1.00
18.18 .42
.55
.68
18.36 .43
.59
.74
18.45 .44
.63
.81
COOLING RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
15 TON HIGH EFFICIENCY − LGC180H (R−22/CAV) − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
4800
6000
7200
4800
6000
7200
4800
6000
7200
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
2265
2830
3400
2265
2830
3400
2265
2830
3400
128.6
133.8
137.6
137.0
141.7
145.1
146.2
150.9
154.1
37.7
39.2
40.3
40.2
41.5
42.5
42.8
44.2
45.2
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
5.78
.66
5.82
.71
5.85
.76
5.84
.52
5.87
.55
5.91
.57
5.91
.40
5.95
.41
5.98
.42
80_F
27_C
.80
.87
.93
.64
.68
.73
.51
.53
.56
85_F
29_C
.93
.99
1.00
.76
.83
.90
.61
.66
.71
Total
Cooling
Capacity
kBtuh
125.2
130.0
133.9
133.3
137.7
140.9
142.0
146.5
149.6
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
36.7 6.47
.67
38.1 6.52
.72
39.2 6.54
.77
39.1 6.53
.53
40.4 6.58
.55
41.3 6.61
.58
41.6 6.61
.40
42.9 6.65
.41
43.8 6.68
.42
80_F
27_C
.81
.88
.95
.64
.69
.74
.51
.54
.57
85_F
29_C
.94
1.00
1.00
.77
.84
.91
.62
.67
.72
Total
Cooling
Capacity
kBtuh kW
121.4
126.1
129.9
129.1
133.3
136.3
137.7
141.8
144.8
35.6
37.0
38.1
37.8
39.1
39.9
40.4
41.6
42.4
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
7.29
.67
7.32
.73
7.36
.78
7.35
.53
7.39
.56
7.41
.59
7.42
.40
7.46
.41
7.48
.42
80_F
27_C
.82
.90
.96
.65
.70
.76
.51
.54
.57
85_F
29_C
.96
1.00
1.00
.78
.86
.93
.63
.68
.73
Total
Cooling
Capacity
kBtuh kW
117.2
121.8
125.4
124.7
128.6
131.4
132.9
136.8
139.6
34.3
35.7
36.8
36.5
37.7
38.5
38.9
40.1
40.9
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
8.22
.68
.84
.97
8.26
.74
.91
1.00
8.29
.80
.98
1.00
8.30
.54
.66
.80
8.32
.57
.72
.88
8.35
.60
.78
.95
8.37
.40
.52
.64
8.40
.41
.55
.69
8.43
.42
.58
.75
15 TON HIGH EFFICIENCY − LGC180H (R−22/CAV) − ALL COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
4800
6000
7200
4800
6000
7200
4800
6000
7200
85_F (29_C)
Total
Cooling
Capacity
L/s kBtuh kW
2265
2830
3400
2265
2830
3400
2265
2830
3400
177.6
184.4
189.9
188.9
195.0
199.5
201.4
207.6
211.8
52.0
54.0
55.7
55.4
57.1
58.5
59.0
60.8
62.1
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
10.86 .69
10.92 .73
10.96 .79
10.96 .54
11.02
.57
11.05
.60
11.06
.41
11.13
.42
11.17
.43
80_F
27_C
.82
.90
.96
.66
.71
.76
.52
.55
.58
85_F
29_C
.96
1.00
1.00
.79
.86
.93
.64
.69
.74
Total
Cooling
Capacity
kBtuh
171.5
178.1
183.6
182.3
188.1
192.3
194.5
200.2
204.1
105_F (41_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
50.3 12.26 .69
52.2 12.31 .75
53.8 12.36 .80
53.4 12.36 .54
55.1 12.40 .57
56.4 12.46 .60
57.0 12.47 .41
58.7 12.52 .42
59.8 12.56 .43
80_F
27_C
.84
.92
.98
.67
.72
.78
.53
.56
.59
85_F
29_C
.97
1.00
1.00
.80
.88
.95
.64
.70
.76
Total
Cooling
Capacity
kBtuh kW
165.1
171.4
176.9
175.4
180.9
184.8
187.0
192.5
196.0
48.4
50.2
51.8
51.4
53.0
54.2
54.8
56.4
57.4
115_F (46_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
13.86 .70
13.91 .76
13.97 .82
13.97 .55
14.00 .58
14.06 .61
14.09 .41
14.13 .42
14.19 .44
80_F
27_C
.85
.93
.99
.68
.74
.80
.53
.57
.60
85_F
29_C
.99
1.00
1.00
.82
.90
.97
.66
.71
.78
Total
Cooling
Capacity
kBtuh kW
158.3
164.3
170.3
168.2
173.2
176.8
179.4
184.4
187.6
46.4
48.2
49.9
49.3
50.8
51.8
52.6
54.0
55.0
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
15.67 .72
.88
1.00
15.75 .78
.96
1.00
15.78 .84
1.00
1.00
15.78 .56
.69
.84
15.84 .59
.76
.92
15.90 .63
.82
.99
15.91 .41
.54
.67
15.96 .43
.58
.73
16.01 .44
.62
.80
15 TON HIGH EFFICIENCY − LGC180H (R−410A/CAV) − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
4800
6000
7200
4800
6000
7200
4800
6000
7200
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
2265
2830
3400
2265
2830
3400
2265
2830
3400
131.6
137.0
141.2
140.4
145.5
149.0
149.8
155.0
158.6
38.6
40.2
41.4
41.1
42.6
43.7
43.9
45.4
46.5
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
5.75
.68
5.77
.72
5.79
.77
5.79
.54
5.81
.56
5.83
.59
5.83
.42
5.85
.42
5.87
.43
80_F
27_C
.80
.86
.92
.65
.70
.74
.52
.55
.57
85_F
29_C
.92
.98
1.00
.77
.83
.89
.63
.67
.72
Total
Cooling
Capacity
kBtuh
126.8
131.9
135.9
135.2
139.9
143.2
144.3
149.1
152.3
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
37.2 6.57
.69
38.7 6.61
.73
39.8 6.63
.78
39.6 6.62
.55
41.0 6.65
.57
42.0 6.68
.60
42.3 6.68
.42
43.7 6.71
.42
44.6 6.74
.43
80_F
27_C
.82
.88
.94
.66
.71
.76
.53
.55
.58
85_F
29_C
.94
.99
1.00
.78
.85
.91
.64
.68
.73
Total
Cooling
Capacity
kBtuh kW
121.7
126.6
130.5
129.7
134.1
137.2
138.5
142.8
145.8
35.7
37.1
38.2
38.0
39.3
40.2
40.6
41.9
42.7
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
7.51
.70
7.54
.75
7.56
.80
7.56
.55
7.60
.58
7.62
.61
7.62
.42
7.66
.43
7.69
.44
80_F
27_C
.83
.90
.96
.67
.72
.78
.53
.56
.59
85_F
29_C
.95
1.00
1.00
.80
.87
.93
.65
.70
.75
Total
Cooling
Capacity
kBtuh kW
116.3
120.9
124.7
123.9
127.9
130.8
132.2
136.2
139.0
34.1
35.4
36.5
36.3
37.5
38.3
38.7
39.9
40.7
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
8.57
.71
.85
.97
8.60
.76
.92
1.00
8.63
.82
.98
1.00
8.63
.56
.69
.82
8.66
.59
.74
.89
8.68
.62
.79
.95
8.69
.42
.54
.66
8.73
.43
.57
.72
8.75
.44
.61
.77
15 TON HIGH EFFICIENCY − LGC180H (R−410A/CAV) − ALL COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
4800
6000
7200
4800
6000
7200
4800
6000
7200
85_F (29_C)
Total
Cooling
Capacity
L/s kBtuh kW
2265
2830
3400
2265
2830
3400
2265
2830
3400
182.2
189.5
195.4
194.2
200.8
205.4
207.3
213.8
218.3
53.4
55.5
57.3
56.9
58.8
60.2
60.8
62.7
64.0
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
11.30
.70
11.35
.75
11.38
.80
11.38
.55
11.44
.58
11.47
.61
11.47
.42
11.53
.43
11.58
.44
80_F
27_C
.83
.90
.96
.67
.72
.77
.53
.56
.59
85_F
29_C
.95
1.00
1.00
.80
.86
.93
.65
.70
.75
Total
Cooling
Capacity
kBtuh
174.1
181.0
186.7
185.5
191.5
195.9
197.9
203.9
208.1
105_F (41_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
51.0 12.89 .71
53.0 12.94 .76
54.7 12.98 .81
54.4 12.99 .56
56.1 13.03 .59
57.4 13.06 .62
58.0 13.08 .42
59.8 13.14 .43
61.0 13.17 .44
80_F
27_C
.85
.92
.98
.68
.74
.79
.54
.57
.61
85_F
29_C
.97
1.00
1.00
.81
.89
.95
.66
.71
.77
Total
Cooling
Capacity
kBtuh kW
165.4
171.8
177.5
176.1
181.6
185.5
188.0
193.4
196.9
48.5
50.3
52.0
51.6
53.2
54.4
55.1
56.7
57.7
115_F (46_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
14.68 .73
14.72 .78
14.76 .84
14.76 .57
14.81 .60
14.86 .63
14.88 .42
14.91 .43
14.97 .45
80_F
27_C
.87
.94
.99
.70
.76
.82
.55
.58
.62
85_F
29_C
.99
1.00
1.00
.83
.91
.97
.67
.73
.79
Total
Cooling
Capacity
kBtuh kW
155.8
161.9
168.3
165.8
170.6
174.4
177.1
181.8
185.1
45.7
47.4
49.3
48.6
50.0
51.1
51.9
53.3
54.2
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
16.68 .74
.90
1.00
16.74 .81
.97
1.00
16.75 .87
1.00
1.00
16.76 .58
.72
.86
16.82 .61
.78
.94
16.84 .65
.84
.99
16.85 .43
.56
.69
16.91 .44
.60
.76
16.93 .45
.64
.82
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 25
COOLING RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
17.5 TON STANDARD EFFICIENCY − LGC210S (R−22/CAV) − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
5600
7000
8400
5600
7000
8400
5600
7000
8400
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
2645
3305
3965
2645
3305
3965
2645
3305
3965
104.0
108.0
111.0
110.4
113.8
116.4
117.4
120.8
123.2
30.5
31.7
32.5
32.4
33.4
34.1
34.4
35.4
36.1
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
5.70
.64
5.80
.69
5.86
.75
5.86
.50
5.92
.53
6.00
.56
6.02
.38
6.10
.39
6.16
.40
80_F
27_C
.79
.87
.95
.62
.66
.72
.49
.52
.55
85_F
29_C
.94
1.00
1.00
.75
.84
.91
.60
.64
.70
Total
Cooling
Capacity
kBtuh
100.8
104.4
107.6
107.0
110.2
112.4
113.8
116.8
119.0
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
29.5 6.34
.65
30.6 6.44
.70
31.5 6.50
.76
31.4 6.48
.51
32.3 6.58
.54
32.9 6.62
.56
33.4 6.66
.38
34.2 6.74
.39
34.9 6.80
.40
80_F
27_C
.81
.89
.96
.63
.67
.74
.49
.52
.56
85_F
29_C
.96
1.00
1.00
.77
.86
.93
.60
.65
.71
Total
Cooling
Capacity
kBtuh kW
97.2
100.8
104.0
103.2
106.2
108.4
109.8
112.6
114.8
28.5
29.5
30.5
30.2
31.1
31.8
32.2
33.0
33.6
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
7.06
.66
7.14
.72
7.22
.78
7.20
.51
7.30
.54
7.34
.57
7.38
.39
7.48
.39
7.54
.41
80_F
27_C
.82
.91
.98
.63
.69
.76
.50
.53
.56
85_F
29_C
.98
1.00
1.00
.78
.88
.95
.61
.67
.73
Total
Cooling
Capacity
kBtuh kW
93.6
97.0
100.2
99.2
102.0
104.0
105.4
108.2
110.2
27.4
28.4
29.4
29.1
29.9
30.5
30.9
31.7
32.3
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
7.88
.67
.84
.99
7.96
.74
.93
1.00
8.06
.80
.99
1.00
8.04
.52
.65
.80
8.12
.55
.71
.90
8.18
.58
.78
.97
8.22
.39
.51
.63
8.30
.40
.54
.68
8.38
.41
.57
.76
17.5 TON STANDARD EFFICIENCY − LGC210S (R−22/CAV) − ALL COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
5600
7000
8400
5600
7000
8400
5600
7000
8400
85_F (29_C)
Total
Cooling
Capacity
L/s kBtuh kW
2645
3305
3965
2645
3305
3965
2645
3305
3965
202.0
209.4
215.8
214.4
220.6
225.2
228.0
234.0
238.4
59.2
61.4
63.2
62.8
64.7
66.0
66.8
68.6
69.9
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
14.24 .69
14.40 .74
14.56 .80
14.52 .54
14.72 .57
14.82 .60
14.88 .40
15.08 .42
15.20 .43
80_F
27_C
.84
.92
.98
.67
.72
.78
.52
.56
.59
85_F
29_C
.98
1.00
1.00
.80
.89
.96
.64
.70
.76
Total
Cooling
Capacity
kBtuh
194.4
201.4
208.0
206.0
212.0
216.2
219.2
224.8
229.0
105_F (41_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
57.0 15.88 .70
59.0 16.06 .76
61.0 16.26 .82
60.4 16.22 .55
62.1 16.38 .58
63.4 16.50 .61
64.2 16.58 .41
65.9 16.74 .42
67.1 16.90 .43
80_F
27_C
.86
.94
1.00
.68
.73
.80
.53
.57
.60
85_F
29_C
.99
1.00
1.00
.82
.91
.98
.66
.71
.78
Total
Cooling
Capacity
kBtuh kW
186.2
193.2
199.8
197.0
202.8
206.6
209.8
215.2
218.6
54.6
56.6
58.6
57.7
59.4
60.5
61.5
63.1
64.1
115_F (46_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
17.76 .72
17.96 .78
18.16 .85
18.10 .55
18.28 .59
18.40 .62
18.48 .41
18.64 .42
18.80 .44
80_F
27_C
.88
.96
1.00
.69
.75
.82
.54
.58
.62
85_F
29_C
1.00
1.00
1.00
.84
.93
.99
.67
.73
.80
Total
Cooling
Capacity
kBtuh kW
177.4
184.4
191.2
187.6
192.6
196.6
199.6
204.6
207.6
52.0
54.0
56.0
55.0
56.4
57.6
58.5
60.0
60.8
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
19.92 .73
.91
1.00
20.12 .80
.99
1.00
20.34 .87
1.00
1.00
20.24 .56
.71
.87
20.46 .60
.78
.96
20.54 .64
.85
1.00
20.66 .41
.55
.69
20.82 .43
.59
.76
20.94 .44
.63
.83
17.5 TON HIGH EFFICIENCY − LGC210H (R−22/CAV) − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
5600
7000
8400
5600
7000
8400
5600
7000
8400
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
2645
3305
3965
2645
3305
3965
2645
3305
3965
109.2
114.0
117.6
116.6
120.8
123.8
124.8
129.0
131.8
32.0
33.4
34.5
34.2
35.4
36.3
36.6
37.8
38.6
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
4.94
.65
4.98
.70
5.00
.76
5.00
.51
5.02
.54
5.06
.57
5.06
.39
5.10
.40
5.12
.41
80_F
27_C
.80
.89
.97
.63
.67
.74
.49
.52
.56
85_F
29_C
.95
1.00
1.00
.76
.85
.93
.60
.65
.71
Total
Cooling
Capacity
kBtuh
106.2
110.6
114.2
113.2
117.0
119.8
121.0
124.8
127.4
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
31.1 5.58
.66
32.4 5.60
.72
33.5 5.64
.78
33.2 5.62
.51
34.3 5.66
.55
35.1 5.68
.58
35.5 5.70
.39
36.6 5.72
.40
37.3 5.76
.41
80_F
27_C
.81
.91
.98
.63
.69
.75
.50
.53
.56
85_F
29_C
.97
1.00
1.00
.77
.86
.95
.61
.66
.72
Total
Cooling
Capacity
kBtuh kW
102.6
106.8
110.6
109.4
113.0
115.6
116.8
120.4
122.8
30.1
31.3
32.4
32.1
33.1
33.9
34.2
35.3
36.0
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
6.28
.67
6.32
.73
6.34
.80
6.34
.52
6.38
.55
6.40
.58
6.40
.39
6.44
.40
6.46
.41
80_F
27_C
.83
.93
1.00
.64
.70
.77
.50
.54
.57
85_F
29_C
.98
1.00
1.00
.79
.89
.97
.62
.67
.74
Total
Cooling
Capacity
kBtuh kW
98.8
102.8
107.0
105.2
108.6
111.0
112.4
115.6
117.8
29.0
30.1
31.4
30.8
31.8
32.5
32.9
33.9
34.5
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
75_F
80_F 85_F
Input
24_C 27_C 29_C
7.08
.68
.85
1.00
7.12
.75
.95
1.00
7.14
.82
1.00
1.00
7.14
.53
.65
.81
7.18
.56
.72
.91
7.20
.60
.79
.99
7.20
.39
.51
.63
7.24
.40
.55
.69
7.26
.42
.59
.77
17.5 TON HIGH EFFICIENCY − LGC210H (R−22/CAV) − ALL COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
5600
7000
8400
5600
7000
8400
5600
7000
8400
85_F (29_C)
Total
Cooling
Capacity
L/s kBtuh kW
2645
3305
3965
2645
3305
3965
2645
3305
3965
207.7
216.4
223.8
221.4
228.9
234.2
236.6
244.1
249.0
60.9
63.4
65.6
64.9
67.1
68.6
69.3
71.5
73.0
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
12.74 .70
12.82 .76
12.86 .82
12.84 .55
12.92 .58
12.96 .62
12.98 .41
13.04 .42
13.08 .44
80_F
27_C
.85
.93
.99
.68
.74
.80
.53
.57
.60
85_F
29_C
.98
1.00
1.00
.81
.90
.97
.65
.71
.77
Total
Cooling
Capacity
kBtuh
200.3
208.4
216.4
213.2
220.1
225.2
228.0
234.5
239.0
Comp
Motor
kW
75_F
kW Input
24_C
58.7 14.36 .71
61.1 14.44 .78
63.4 14.50 .84
62.5 14.48 .56
64.5 14.56 .59
66.0 14.60 .63
66.8 14.60 .41
68.7 14.68 .43
70.0 14.72 .44
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 26
105_F (41_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
80_F
27_C
.87
.95
1.00
.69
.75
.81
.54
.58
.62
85_F
29_C
1.00
1.00
1.00
.83
.92
.99
.66
.73
.79
Total
Cooling
Capacity
kBtuh kW
192.0
199.9
208.4
204.3
210.8
215.3
218.4
224.4
228.6
56.3
58.6
61.1
59.9
61.8
63.1
64.0
65.8
67.0
115_F (46_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
16.20 .73
16.30 .79
16.34 .86
16.32 .56
16.38 .60
16.42 .64
16.46 .42
16.50 .43
16.54 .45
80_F
27_C
.89
.97
1.00
.70
.77
.84
.55
.59
.63
85_F
29_C
1.00
1.00
1.00
.85
.94
1.00
.68
.74
.81
Total
Cooling
Capacity
kBtuh kW
183.1
191.2
199.6
194.7
200.8
205.2
208.0
213.7
217.6
53.7
56.0
58.5
57.1
58.8
60.1
61.0
62.6
63.8
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
18.30 .74
.91
1.00
18.36 .82
.99
1.00
18.44 .89
1.00
1.00
18.42 .57
.72
.87
18.48 .61
.79
.97
18.52 .65
.86
1.00
18.56 .42
.56
.69
18.60 .44
.60
.76
18.64 .45
.65
.84
COOLING RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
20 TON STANDARD EFFICIENCY − LGC240S (R−22/CAV) − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
6400
8000
9600
6400
8000
9600
6400
8000
9600
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
3020
3775
4530
3020
3775
4530
3020
3775
4530
118.8
123.0
126.4
126.0
129.8
132.4
133.8
137.4
140.0
34.8
36.0
37.0
36.9
38.0
38.8
39.2
40.3
41.0
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
6.72
.60
6.80
.65
6.86
.71
6.86
.48
6.92
.50
6.98
.52
7.02
.36
7.08
.37
7.14
.38
80_F
27_C
.76
.85
.93
.58
.62
.68
.46
.49
.51
85_F
29_C
.92
1.00
1.00
.72
.81
.89
.56
.61
.66
Total
Cooling
Capacity
kBtuh
115.8
120.0
123.4
122.8
126.4
129.0
130.6
134.2
136.6
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
33.9 7.38
.61
35.2 7.46
.66
36.2 7.54
.72
36.0 7.52
.48
37.0 7.58
.50
37.8 7.64
.53
38.3 7.66
.36
39.3 7.74
.37
40.0 7.80
.38
80_F
27_C
.77
.86
.94
.59
.63
.70
.46
.49
.52
85_F
29_C
.94
1.00
1.00
.73
.82
.91
.56
.61
.67
Total
Cooling
Capacity
kBtuh kW
112.0
116.2
119.6
119.0
122.6
125.0
126.6
130.0
132.4
32.8
34.1
35.1
34.9
35.9
36.6
37.1
38.1
38.8
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
8.14
.62
8.24
.67
8.30
.74
8.28
.48
8.36
.51
8.42
.54
8.44
.36
8.52
.37
8.56
.38
80_F
27_C
.79
.89
.96
.59
.64
.72
.47
.50
.53
85_F
29_C
.96
1.00
1.00
.74
.84
.93
.57
.62
.69
Total
Cooling
Capacity
kBtuh kW
108.0
112.2
115.6
114.6
118.0
120.4
122.2
125.4
127.6
31.7
32.9
33.9
33.6
34.6
35.3
35.8
36.8
37.4
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
9.02
.62
.81
.98
9.12
.69
.91
1.00
9.18
.76
.98
1.00
9.16
.49
.60
.76
9.26
.51
.66
.87
9.30
.54
.74
.95
9.32
.36
.47
.58
9.40
.37
.50
.63
9.46
.39
.53
.71
20 TON STANDARD EFFICIENCY − LGC240S (R−22/CAV) − ALL COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
6400
8000
9600
6400
8000
9600
6400
8000
9600
85_F (29_C)
Total
Cooling
Capacity
L/s kBtuh kW
3020
3775
4530
3020
3775
4530
3020
3775
4530
230.6
239.2
246.2
245.0
252.2
257.4
260.6
267.6
272.6
67.6
70.1
72.2
71.8
73.9
75.4
76.4
78.4
79.9
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
16.66 .69
16.86 .74
16.98 .80
16.94 .54
17.10 .57
17.24 .60
17.28 .41
17.44 .42
17.52 .43
80_F
27_C
.85
.93
1.00
.67
.72
.78
.52
.56
.59
85_F
29_C
.99
1.00
1.00
.81
.89
.97
.64
.70
.75
Total
Cooling
Capacity
kBtuh
222.4
231.0
238.0
236.0
243.0
248.0
251.6
258.2
262.8
105_F (41_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
65.2 18.46 .70
67.7 18.66 .76
69.8 18.80 .82
69.2 18.76 .55
71.2 18.94 .58
72.7 19.04 .61
73.7 19.08 .41
75.7 19.24 .42
77.0 19.36 .43
80_F
27_C
.86
.95
1.00
.68
.73
.80
.53
.57
.60
85_F
29_C
1.00
1.00
1.00
.82
.91
.99
.65
.71
.77
Total
Cooling
Capacity
kBtuh kW
213.8
222.0
229.4
227.0
233.4
238.4
241.8
248.0
252.4
62.7
65.1
67.2
66.5
68.4
69.9
70.9
72.7
74.0
115_F (46_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
20.54 .71
20.70 .78
20.88 .84
20.82 .55
21.00 .59
21.12 .62
21.18 .41
21.36 .42
21.46 .44
80_F
27_C
.88
.97
1.00
.69
.75
.82
.54
.58
.61
85_F
29_C
1.00
1.00
1.00
.84
.94
1.00
.67
.73
.79
Total
Cooling
Capacity
kBtuh kW
205.4
213.4
220.8
217.6
223.8
228.4
232.0
237.8
241.8
60.2
62.5
64.7
63.8
65.6
66.9
68.0
69.7
70.9
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
22.84 .73
.91
1.00
23.02 .80
.99
1.00
23.24 .87
1.00
1.00
23.18 .56
.70
.87
23.34 .60
.77
.96
23.46 .63
.84
1.00
23.58 .41
.55
.68
23.72 .43
.58
.74
23.84 .44
.62
.82
20 TON HIGH EFFICIENCY − LGA240H (R−22/CAV) − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
6400
8000
9600
6400
8000
9600
6400
8000
9600
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
3020
3775
4530
3020
3775
4530
3020
3775
4530
126.6
131.6
135.8
134.6
139.2
142.4
143.6
148.0
151.2
37.1
38.6
39.8
39.4
40.8
41.7
42.1
43.4
44.3
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
6.26
.63
.78
.94
6.32
.68
.87
1.00
6.36
.74
.95
1.00
6.34
.50
.61
.74
6.40
.52
.65
.83
6.42
.55
.72
.91
6.44
.38
.48
.59
6.48
.39
.51
.63
6.52
.40
.54
.69
75_F (24_C)
Total
Cooling
Capacity
kBtuh kW
122.8
127.8
131.8
130.6
134.8
138.0
139.4
143.4
146.4
36.0
37.5
38.6
38.3
39.5
40.4
40.9
42.0
42.9
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
7.04
.64
.80
.95
7.08
.69
.89
1.00
7.14
.76
.97
1.00
7.12
.50
.62
.75
7.18
.53
.67
.85
7.20
.56
.73
.93
7.22
.38
.49
.59
7.28
.39
.52
.64
7.30
.40
.55
.70
85_F (29_C)
Total
Cooling
Capacity
kBtuh kW
118.8
123.6
127.6
126.4
130.4
133.4
134.8
138.6
141.4
34.8
36.2
37.4
37.0
38.2
39.1
39.5
40.6
41.4
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
7.94
.65
.81
.97
8.00
.71
.91
1.00
8.04
.78
.98
1.00
8.02
.51
.62
.77
8.08
.54
.68
.87
8.12
.57
.75
.95
8.14
.38
.49
.60
8.18
.39
.52
.66
8.24
.40
.56
.72
95_F (35_C)
Total
Cooling
Capacity
kBtuh kW
114.8
119.2
123.4
121.8
125.6
128.4
129.8
133.6
136.0
33.6
34.9
36.2
35.7
36.8
37.6
38.0
39.2
39.9
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
8.98
.66
.83
.99
9.04
.73
.93
1.00
9.10
.80
1.00
1.00
9.08
.51
.63
.79
9.13
.54
.70
.89
9.18
.58
.77
.97
9.20
.38
.50
.61
9.24
.39
.53
.67
9.28
.41
.57
.74
20 TON HIGH EFFICIENCY − LGA240H (R−22/CAV) − ALL COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
6400
8000
9600
6400
8000
9600
6400
8000
9600
85_F (29_C)
Total
Cooling
Capacity
L/s kBtuh kW
3020
3775
4530
3020
3775
4530
3020
3775
4530
238.4
248.0
256.0
253.4
261.6
267.5
270.3
278.1
283.6
69.9
72.7
75.0
74.3
76.7
78.4
79.2
81.5
83.1
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
15.72 .70
.85
.99
15.84 .75
.93
1.00
15.92 .81
1.00
1.00
15.89 .55
.67
.81
16.00 .58
.73
.89
16.08 .61
.79
.97
16.12 .41
.53
.65
16.20 .42
.56
.70
16.32 .43
.60
.76
95_F (35_C)
Total
Cooling
Capacity
kBtuh kW
230.2
239.2
247.6
244.3
252.0
257.6
260.5
268.0
272.9
67.5
70.1
72.6
71.6
73.9
75.5
76.3
78.5
80.0
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
17.80 .71
.86
1.00
17.90 .77
.95
1.00
18.02 .83
1.00
1.00
17.98 .55
.68
.82
18.09 .58
.74
.91
18.18 .62
.81
.99
18.22 .41
.53
.66
18.30 .42
.57
.72
18.39 .44
.61
.78
105_F (41_C)
Total
Cooling
Capacity
kBtuh kW
221.2
230.0
238.6
234.8
241.9
247.1
250.4
257.2
261.7
64.8
67.4
69.9
68.8
70.9
72.4
73.4
75.4
76.7
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
20.16 .72
.88
1.00
20.28 .78
.97
1.00
20.40 .85
1.00
1.00
20.32 .56
.69
.84
20.48 .59
.76
.94
20.56 .63
.83
1.00
20.60 .41
.54
.67
20.72 .43
.58
.73
20.79 .44
.62
.81
115_F (46_C)
Total
Cooling
Capacity
kBtuh kW
211.5
220.2
229.4
224.4
231.0
236.0
239.5
245.7
249.9
62.0
64.5
67.2
65.8
67.7
69.2
70.2
72.0
73.2
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
22.82 .73
.91
1.00
22.96 .81
.99
1.00
23.09 .88
1.00
1.00
23.02 .57
.71
.87
23.18 .60
.78
.96
23.24 .64
.85
1.00
23.28 .42
.55
.69
23.40 .43
.59
.75
23.48 .45
.64
.83
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 27
COOLING RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
20 TON HIGH EFFICIENCY − LGA240H (R−410A/CAV) − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
6400
8000
9600
6400
8000
9600
6400
8000
9600
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
3020
3775
4530
3020
3775
4530
3020
3775
4530
133.0
138.4
142.6
141.4
146.4
149.8
150.8
155.6
159.0
39.0
40.6
41.8
41.4
42.9
43.9
44.2
45.6
46.6
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
6.30
.67
6.36
.72
6.38
.77
6.36
.53
6.42
.56
6.46
.58
6.46
.41
6.50
.41
6.54
.42
80_F
27_C
.80
.87
.94
.65
.69
.74
.51
.54
.57
85_F
29_C
.93
1.00
1.00
.76
.84
.91
.62
.67
.72
Total
Cooling
Capacity
kBtuh
128.0
133.2
137.2
136.0
140.6
144.0
145.0
149.4
152.6
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
37.5 7.18
.68
39.0 7.24
.73
40.2 7.28
.78
39.9 7.26
.54
41.2 7.32
.56
42.2 7.36
.59
42.5 7.36
.41
43.8 7.42
.42
44.7 7.46
.43
80_F
27_C
.82
.89
.95
.66
.70
.76
.52
.55
.58
85_F
29_C
.95
1.00
1.00
.78
.86
.93
.63
.68
.74
Total
Cooling
Capacity
kBtuh kW
122.6
127.6
131.6
130.4
134.6
137.6
139.0
143.0
145.8
35.9
37.4
38.6
38.2
39.4
40.3
40.7
41.9
42.7
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
8.20
.69
8.24
.75
8.30
.80
8.28
.54
8.34
.57
8.38
.60
8.38
.41
8.46
.42
8.48
.43
80_F
27_C
.83
.91
.97
.67
.72
.78
.52
.56
.59
85_F
29_C
.97
1.00
1.00
.80
.88
.95
.64
.70
.76
Total
Cooling
Capacity
kBtuh kW
117.0
121.6
125.6
124.2
128.2
131.0
132.4
136.2
138.8
34.3
35.6
36.8
36.4
37.6
38.4
38.8
39.9
40.7
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
9.34
.70
.85
.98
9.40
.77
.93
1.00
9.44
.83
.99
1.00
9.42
.55
.68
.82
9.48
.58
.74
.90
9.52
.62
.80
.97
9.54
.41
.53
.66
9.58
.42
.57
.71
9.62
.44
.61
.78
20 TON HIGH EFFICIENCY − LGA240H (R−410A/CAV) − ALL COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
6400
8000
9600
6400
8000
9600
6400
8000
9600
85_F (29_C)
Total
Cooling
Capacity
L/s kBtuh kW
3020
3775
4530
3020
3775
4530
3020
3775
4530
245.5
255.5
263.5
261.1
269.5
275.6
278.3
286.4
292.0
71.9
74.9
77.2
76.5
79.0
80.8
81.6
83.9
85.6
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
16.40 .69
16.48 .74
16.60 .80
16.56 .54
16.68 .57
16.76 .60
16.76 .41
16.92 .42
16.96 .43
80_F
27_C
.83
.91
.97
.67
.72
.78
.52
.56
.59
85_F
29_C
.96
1.00
1.00
.79
.87
.95
.64
.70
.75
Total
Cooling
Capacity
kBtuh
234.3
243.5
251.6
248.7
256.7
262.4
265.1
272.8
277.9
105_F (41_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
68.7 18.68 .70
71.4 18.79 .76
73.7 18.88 .82
72.9 18.84 .55
75.2 18.96 .58
76.9 19.04 .62
77.7 19.08 .41
79.9 19.16 .42
81.4 19.25 .44
80_F
27_C
.85
.93
.99
.68
.74
.80
.53
.57
.61
85_F
29_C
.98
1.00
1.00
.81
.90
.97
.66
.71
.78
Total
Cooling
Capacity
kBtuh kW
221.9
230.7
239.5
235.5
242.4
248.0
251.2
257.6
262.4
65.0
67.6
70.2
69.0
71.0
72.7
73.6
75.5
76.9
115_F (46_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
21.20 .72
21.32 .78
21.44 .85
21.40 .56
21.52 .59
21.56 .63
21.59 .41
21.72 .43
21.76 .44
80_F
27_C
.88
.96
1.00
.70
.76
.83
.54
.58
.62
85_F
29_C
1.00
1.00
1.00
.84
.93
.99
.67
.73
.80
Total
Cooling
Capacity
kBtuh kW
208.4
217.1
226.3
221.1
227.6
232.4
236.0
241.7
246.0
61.1
63.6
66.3
64.8
66.7
68.1
69.2
70.8
72.1
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
24.08 .74
.91
1.00
24.16 .81
.99
1.00
24.28 .88
1.00
1.00
24.24 .57
.72
.87
24.32 .61
.79
.96
24.40 .65
.86
1.00
24.43 .42
.56
.69
24.52 .43
.60
.76
24.59 .45
.64
.84
21 TON HIGH EFFICIENCY − LGA248H (R−22/CAV) − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
6720
8400
10080
6720
8400
10080
6720
8400
10080
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
3170
3965
4760
3170
3965
4760
3170
3965
4760
123.2
128.1
132.0
131.1
135.6
138.9
139.9
144.4
147.5
36.1
37.5
38.7
38.4
39.7
40.7
41.0
42.3
43.2
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
5.56
.58
5.59
.63
5.63
.70
5.61
.46
5.65
.48
5.68
.50
5.69
.35
5.72
.35
5.75
.36
80_F
27_C
.74
.84
.93
.56
.60
.66
.44
.47
.49
85_F
29_C
.92
1.00
1.00
.69
.79
.89
.54
.58
.63
Total
Cooling
Capacity
kBtuh
119.8
124.6
128.3
127.5
131.7
134.8
136.0
140.3
143.1
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
35.1 6.23
.59
36.5 6.25
.64
37.6 6.29
.71
37.4 6.29
.46
38.6 6.32
.48
39.5 6.34
.51
39.9 6.35
.35
41.1 6.39
.36
41.9 6.41
.37
80_F
27_C
.76
.86
.95
.56
.61
.68
.45
.47
.50
85_F
29_C
.94
1.00
1.00
.71
.81
.91
.54
.59
.65
Total
Cooling
Capacity
kBtuh kW
116.1
120.7
124.6
123.6
127.5
130.4
131.7
135.8
138.5
34.0
35.4
36.5
36.2
37.4
38.2
38.6
39.8
40.6
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
7.00
.59
7.03
.66
7.06
.73
7.06
.46
7.09
.49
7.12
.52
7.13
.35
7.15
.36
7.19
.37
80_F
27_C
.77
.88
.97
.57
.62
.70
.45
.48
.51
85_F
29_C
.96
1.00
1.00
.72
.83
.93
.55
.60
.67
Total
Cooling
Capacity
kBtuh kW
112.2
116.5
120.5
119.3
123.0
125.7
127.3
130.9
133.4
32.9
34.1
35.3
35.0
36.0
36.8
37.3
38.4
39.1
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
7.89
.60
.79
.98
7.93
.67
.91
1.00
7.95
.75
.99
1.00
7.95
.47
.58
.74
7.99
.50
.64
.86
8.01
.52
.72
.96
8.02
.35
.45
.56
8.06
.36
.49
.61
8.09
.37
.52
.69
21 TON HIGH EFFICIENCY − LGA248H (R−22/CAV) − ALL COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
6720
8400
10080
6720
8400
10080
6720
8400
10080
85_F (29_C)
Total
Cooling
Capacity
L/s kBtuh kW
3170
3965
4760
3170
3965
4760
3170
3965
4760
244.2
253.6
261.8
259.8
268.2
274.0
277.0
285.4
291.0
71.6
74.3
76.7
76.1
78.6
80.3
81.2
83.6
85.3
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
14.08 .69
14.14 .75
14.22 .80
14.20 .54
14.26 .57
14.34 .61
14.34 .41
14.42 .42
14.46 .43
80_F
27_C
.84
.92
.98
.67
.72
.78
.53
.56
.60
85_F
29_C
.97
1.00
1.00
.80
.88
.95
.64
.70
.76
Total
Cooling
Capacity
kBtuh
235.8
245.0
253.2
250.8
258.8
264.4
267.4
275.2
280.4
Comp
Motor
kW
75_F
kW Input
24_C
69.1 15.88 .70
71.8 15.94 .76
74.2 16.02 .82
73.5 16.00 .55
75.8 16.06 .58
77.5 16.12 .62
78.4 16.14 .41
80.7 16.22 .42
82.2 16.26 .44
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 28
105_F (41_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
80_F
27_C
.85
.93
.99
.68
.74
.80
.53
.57
.60
85_F
29_C
.99
1.00
1.00
.81
.90
.97
.65
.71
.77
Total
Cooling
Capacity
kBtuh kW
227.2
236.0
244.4
241.4
248.8
254.0
257.4
264.6
269.4
66.6
69.2
71.6
70.7
72.9
74.4
75.4
77.5
79.0
115_F (46_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
17.94 .71
18.02 .78
18.06 .84
18.06 .56
18.14 .59
18.20 .63
18.22 .41
18.28 .43
18.34 .44
80_F
27_C
.87
.95
1.00
.69
.75
.82
.54
.58
.62
85_F
29_C
1.00
1.00
1.00
.83
.92
.99
.67
.73
.79
Total
Cooling
Capacity
kBtuh kW
217.8
226.4
235.4
231.2
238.2
243.2
246.8
253.2
257.8
63.8
66.4
69.0
67.8
69.8
71.3
72.3
74.2
75.6
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
20.30 .73
.89
1.00
20.38 .80
.97
1.00
20.46 .86
1.00
1.00
20.42 .56
.70
.85
20.50 .60
.77
.94
20.56 .64
.84
1.00
20.58 .42
.55
.68
20.66 .43
.59
.75
20.70 .44
.63
.82
COOLING RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
21 TON HIGH EFFICIENCY − LGA248H (R−410A/CAV) − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
6720
8400
10080
6720
8400
10080
6720
8400
10080
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
3170
3965
4760
3170
3965
4760
3170
3965
4760
128.2
133.5
137.6
136.6
141.5
144.8
145.9
150.7
153.9
37.6
39.1
40.3
40.0
41.5
42.4
42.8
44.2
45.1
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
5.25
.54
5.29
.59
5.33
.66
5.31
.43
5.35
.45
5.38
.47
5.39
.33
5.43
.33
5.46
.34
80_F
27_C
.71
.82
.92
.52
.56
.63
.41
.44
.46
85_F
29_C
.91
1.00
1.00
.66
.77
.87
.50
.54
.59
Total
Cooling
Capacity
kBtuh
123.4
128.4
132.5
131.5
136.0
139.1
140.4
144.8
147.8
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
36.2 6.08
.55
37.6 6.11
.61
38.8 6.15
.69
38.5 6.14
.43
39.9 6.17
.46
40.8 6.21
.48
41.1 6.22
.33
42.4 6.26
.33
43.3 6.29
.34
80_F
27_C
.74
.85
.95
.53
.57
.65
.42
.44
.47
85_F
29_C
.94
1.00
1.00
.68
.80
.91
.51
.55
.62
Total
Cooling
Capacity
kBtuh kW
118.3
123.0
127.2
126.0
130.1
133.0
134.6
138.6
141.3
34.7
36.0
37.3
36.9
38.1
39.0
39.4
40.6
41.4
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
6.95
.56
6.99
.63
7.03
.71
7.02
.44
7.06
.46
7.09
.49
7.11
.33
7.15
.34
7.18
.35
80_F
27_C
.76
.88
.98
.54
.59
.68
.42
.45
.48
85_F
29_C
.97
1.00
1.00
.71
.83
.94
.52
.57
.65
Total
Cooling
Capacity
kBtuh kW
112.9
117.4
121.7
120.2
123.9
126.6
128.3
132.0
134.4
33.1
34.4
35.7
35.2
36.3
37.1
37.6
38.7
39.4
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
7.91
.57
.80
1.00
7.97
.66
.92
1.00
7.99
.75
1.00
1.00
7.99
.44
.55
.74
8.03
.47
.62
.87
8.05
.50
.72
.98
8.07
.33
.43
.53
8.11
.34
.46
.59
8.15
.35
.49
.68
21 TON HIGH EFFICIENCY − LGA248H (R−410A/CAV) − ALL COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
6720
8400
10080
6720
8400
10080
6720
8400
10080
85_F (29_C)
Total
Cooling
Capacity
L/s kBtuh kW
3170
3965
4760
3170
3965
4760
3170
3965
4760
247.6
257.2
266.0
263.4
272.0
278.2
281.4
289.8
295.4
72.6
75.4
78.0
77.2
79.7
81.5
82.5
84.9
86.6
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
13.94 .66
14.02 .72
14.10 .78
14.08 .52
14.16 .55
14.22 .58
14.24 .39
14.34 .40
14.40 .41
80_F
27_C
.82
.92
.99
.64
.69
.76
.50
.54
.57
85_F
29_C
.98
1.00
1.00
.78
.87
.96
.62
.67
.73
Total
Cooling
Capacity
kBtuh
236.2
245.4
254.4
251.2
259.0
264.6
268.2
275.6
280.8
105_F (41_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
69.2 15.86 .68
71.9 15.98 .74
74.6 16.02 .81
73.6 16.02 .53
75.9 16.10 .56
77.5 16.16 .59
78.6 16.18 .39
80.8 16.26 .40
82.3 16.34 .42
80_F
27_C
.84
.94
1.00
.65
.71
.78
.51
.55
.58
85_F
29_C
1.00
1.00
1.00
.80
.90
.98
.63
.69
.76
Total
Cooling
Capacity
kBtuh kW
223.6
232.8
242.4
237.8
244.8
250.0
253.8
260.8
265.2
65.5
68.2
71.0
69.7
71.7
73.3
74.4
76.4
77.7
115_F (46_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
18.06 .69
18.14 .77
18.22 .84
18.18 .53
18.26 .57
18.30 .61
18.36 .39
18.42 .41
18.48 .42
80_F
27_C
.88
.97
1.00
.67
.74
.82
.52
.56
.60
85_F
29_C
1.00
1.00
1.00
.83
.94
1.00
.65
.71
.79
Total
Cooling
Capacity
kBtuh kW
210.2
219.8
229.4
223.2
229.8
234.6
238.4
244.4
248.4
61.6
64.4
67.2
65.4
67.3
68.8
69.9
71.6
72.8
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
20.50 .71
.92
1.00
20.58 .80
1.00
1.00
20.66 .88
1.00
1.00
20.62 .55
.69
.87
20.70 .59
.77
.98
20.74 .63
.86
1.00
20.80 .40
.53
.67
20.86 .41
.58
.74
20.90 .43
.62
.83
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 29
COOLING RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
21 TON HIGH EFFICIENCY − LGA248H2V (R−22/VAV) − COOLING CAPACITY − ONE COMPRESSOR OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperat
ure
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
1680 795
2100 990
2520 1190
1680 795
2100 990
2520 1190
1680 795
2100 990
2520 1190
49.3
52.9
55.4
53.0
56.7
59.3
56.9
60.8
63.5
14.4
15.5
16.2
15.5
16.6
17.4
16.7
17.8
18.6
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
4.32
.64
4.36
.65
4.38
.67
4.36
.53
4.40
.53
4.43
.54
4.40
.43
4.45
.43
4.48
.42
80_F
27_C
.72
.74
.77
.61
.62
.64
.50
.51
.52
Total
Cooling
Capacity
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
85_F
75_F
kBtuh kW Input
29_C
24_C
.80
48.1 14.1 4.84
.64
.84
51.4 15.1 4.88
.65
.88
53.8 15.8 4.91
.67
.68
51.7 15.2 4.88
.53
.71
55.1 16.1 4.92
.53
.74
57.6 16.9 4.95
.54
.57
55.5 16.3 4.93
.43
.59
59.1 17.3 4.97
.43
.61
61.7 18.1 5.00
.42
80_F
27_C
.72
.75
.78
.61
.62
.65
.50
.51
.52
Total
Cooling
Capacity
85_F
kBtuh kW
29_C
.80
46.7 13.7
.84
49.9 14.6
.89
52.1 15.3
.68
50.2 14.7
.71
53.4 15.6
.75
55.7 16.3
.58
53.9 15.8
.59
57.3 16.8
.62
59.6 17.5
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
5.45
.64
5.49
.66
5.52
.68
5.50
.53
5.53
.54
5.56
.55
5.54
.43
5.58
.42
5.61
.42
80_F
27_C
.73
.76
.79
.61
.63
.65
.50
.51
.52
Total
Cooling
Capacity
85_F
kBtuh kW
29_C
.81
45.2 13.2
.85
48.1 14.1
.90
50.2 14.7
.69
48.6 14.2
.72
51.6 15.1
.76
53.7 15.7
.58
52.1 15.3
.60
55.3 16.2
.62
57.5 16.9
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
6.16
.64
.73
.82
6.19
.66
.77
.87
6.22
.69
.80
.92
6.20
.53
.61
.69
6.24
.54
.63
.73
6.26
.55
.66
.77
6.25
.43
.51
.58
6.28
.42
.52
.60
6.32
.43
.53
.63
21 TON HIGH EFFICIENCY − LGA248H2V (R−22/VAV) − COOLING CAPACITY − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
3570
4200
4830
3570
4200
4830
3570
4200
4830
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
1685
1980
2280
1685
1980
2280
1685
1980
2280
135.1
139.0
142.2
144.3
147.9
150.7
154.0
157.8
160.6
39.6
40.7
41.7
42.3
43.3
44.2
45.1
46.2
47.1
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
7.45
.73
7.49
.76
7.52
.80
7.54
.57
7.57
.59
7.60
.62
7.62
.43
7.67
.44
7.69
.45
80_F
27_C
.87
.91
.96
.70
.74
.78
.56
.58
.60
85_F
29_C
.99
1.00
1.00
.83
.88
.93
.68
.71
.75
Total
Cooling
Capacity
kBtuh
131.2
134.9
138.1
140.0
143.4
146.0
149.4
152.9
155.5
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
38.5 8.33
.74
39.5 8.36
.77
40.5 8.40
.81
41.0 8.41
.58
42.0 8.45
.60
42.8 8.47
.62
43.8 8.50
.43
44.8 8.55
.44
45.6 8.57
.45
80_F
27_C
.88
.93
.97
.71
.75
.79
.56
.58
.61
85_F
29_C
1.00
1.00
1.00
.84
.89
.94
.68
.73
.77
Total
Cooling
Capacity
kBtuh kW
127.0
130.5
133.5
135.4
138.6
141.0
144.4
147.7
150.1
37.2
38.2
39.1
39.7
40.6
41.3
42.3
43.3
44.0
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
9.36
.75
9.39
.79
9.43
.83
9.44
.58
9.48
.61
9.50
.63
9.53
.44
9.57
.45
9.60
.46
80_F
27_C
.89
.94
.99
.72
.76
.80
.57
.59
.62
85_F
29_C
1.00
1.00
1.00
.86
.91
.96
.70
.74
.78
Total
Cooling
Capacity
kBtuh kW
122.4
125.8
128.8
130.3
133.4
135.6
139.2
142.1
144.4
35.9
36.9
37.7
38.2
39.1
39.7
40.8
41.6
42.3
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
10.54 .76
.91
1.00
10.58 .80
.96
1.00
10.61 .84
1.00
1.00
10.62 .59
.73
.87
10.66 .61
.78
.93
10.68 .64
.82
.98
10.72 .44
.57
.71
10.75 .45
.60
.75
10.78 .46
.63
.80
21 TON HIGH EFFICIENCY − LGA248H2V (R−22/VAV) − COOLING CAPACITY − THREE COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
5040
6300
7560
5040
6300
7560
5040
6300
7560
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
2380
2975
3570
2380
2975
3570
2380
2975
3570
197.1
205.0
212.2
208.9
214.3
218.3
222.5
227.5
231.1
57.8
60.1
62.2
61.2
62.8
64.0
65.2
66.7
67.7
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
11.48
.69
11.55
.75
11.62
.83
11.59
.53
11.64
.57
11.68
.60
11.73
.39
11.78
.40
11.82
.42
80_F
27_C
.89
.97
1.00
.67
.73
.80
.52
.56
.60
85_F
29_C
1.00
1.00
1.00
.85
.95
.99
.65
.71
.78
Total
Cooling
Capacity
kBtuh
191.5
199.5
206.5
202.7
207.7
211.6
215.7
220.5
223.8
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
56.1 12.83 .70
58.5 12.90 .77
60.5 12.98 .85
59.4 12.93 .54
60.9 12.99 .57
62.0 13.03 .61
63.2 13.07 .39
64.6 13.13 .40
65.6 13.17 .42
80_F
27_C
.91
.98
1.00
.68
.74
.82
.52
.57
.60
85_F
29_C
1.00
1.00
1.00
.86
.96
1.00
.66
.72
.80
Total
Cooling
Capacity
kBtuh kW
185.6
193.5
200.3
195.9
200.7
204.5
208.4
212.9
216.1
54.4
56.7
58.7
57.4
58.8
59.9
61.1
62.4
63.3
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
14.41 .71
14.47 .79
14.56 .87
14.52 .54
14.57 .58
14.62 .62
14.65 .39
14.70 .41
14.75 .42
80_F
27_C
.93
.99
1.00
.69
.76
.84
.53
.57
.62
85_F
29_C
1.00
1.00
1.00
.89
.97
1.00
.67
.74
.82
Total
Cooling
Capacity
kBtuh kW
179.2
187.2
193.9
188.7
193.3
196.9
200.8
204.9
207.8
52.5
54.9
56.8
55.3
56.7
57.7
58.8
60.1
60.9
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
16.23 .73
.95
1.00
16.32 .81
1.00
1.00
16.38 .89
1.00
1.00
16.34 .55
.71
.91
16.39 .59
.78
.99
16.45 .63
.87
1.00
16.48 .39
.54
.69
16.53 .41
.59
.76
16.57 .43
.63
.84
21 TON HIGH EFFICIENCY − LGA248H2V (R−22/VAV) − COOLING CAPACITY − FOUR COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
6720
8400
10080
6720
8400
10080
6720
8400
10080
85_F (29_C)
Total
Cooling
Capacity
L/s kBtuh kW
3170
3965
4760
3170
3965
4760
3170
3965
4760
244.4
254.7
262.3
253.0
258.7
264.1
268.2
272.7
276.0
71.6
74.6
76.9
74.1
75.8
77.4
78.6
79.9
80.9
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
17.92 .71
18.02 .76
18.09 .89
18.00 .53
18.09 .58
18.14 .62
18.17 .37
18.23 .39
18.27 .41
80_F
27_C
.98
1.00
1.00
.69
.75
.85
.53
.57
.62
85_F
29_C
1.00
1.00
1.00
.93
1.00
1.00
.68
.74
.82
Total
Cooling
Capacity
kBtuh
236.4
246.4
253.6
243.8
249.3
254.8
258.2
262.3
265.6
Comp
Motor
kW
75_F
kW Input
24_C
69.3 20.18 .72
72.2 20.28 .80
74.3 20.37 .92
71.5 20.28 .54
73.1 20.35 .59
74.7 20.39 .63
75.7 20.44 .37
76.9 20.49 .39
77.8 20.54 .41
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 30
105_F (41_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
80_F
27_C
1.00
1.00
1.00
.71
.76
.89
.54
.59
.63
85_F
29_C
1.00
1.00
1.00
.96
1.00
1.00
.69
.75
.86
Total
Cooling
Capacity
kBtuh kW
228.2
237.6
244.5
234.0
239.7
245.3
247.8
251.6
254.7
66.9
69.6
71.7
68.6
70.2
71.9
72.6
73.7
74.6
115_F (46_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
22.77 .73
22.89 .85
22.98 .95
22.87 .55
22.94 .60
23.00 .65
23.04 .38
23.11 .40
23.11 .42
80_F
27_C
1.00
1.00
1.00
.72
.81
.93
.55
.60
.65
85_F
29_C
1.00
1.00
1.00
.99
1.00
1.00
.71
.77
.90
Total
Cooling
Capacity
kBtuh kW
219.5
228.2
234.8
224.0
229.7
235.2
236.9
240.6
243.4
64.3
66.9
68.8
65.6
67.3
68.9
69.4
70.5
71.3
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
25.76 .75
1.00
1.00
25.86 .89
1.00
1.00
25.93 .99
1.00
1.00
25.84 .56
.74
1.00
25.91 .62
.85
1.00
25.93 .66
.97
1.00
26.01 .38
.56
.72
26.07 .41
.61
.82
26.09 .43
.66
.94
COOLING RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
25 TON STANDARD EFFICIENCY − LGC300S (R−22/CAV) − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
8000
10000
12000
8000
10000
12000
8000
10000
12000
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
3775
4720
5665
3775
4720
5665
3775
4720
5665
149.0
154.6
159.2
158.0
162.8
166.2
167.8
172.4
175.6
43.7
45.3
46.7
46.3
47.7
48.7
49.2
50.5
51.5
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
8.34
.61
8.46
.66
8.56
.73
8.52
.48
8.64
.50
8.74
.53
8.76
.36
8.88
.37
8.96
.38
80_F
27_C
.77
.86
.95
.59
.63
.70
.46
.49
.52
85_F
29_C
.94
1.00
1.00
.72
.82
.91
.56
.61
.67
Total
Cooling
Capacity
kBtuh
144.6
150.0
154.4
153.2
157.8
161.0
162.6
167.2
170.0
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
42.4 9.28
.61
44.0 9.42
.67
45.3 9.52
.74
44.9 9.48
.48
46.2 9.60
.51
47.2 9.70
.54
47.7 9.74
.36
49.0 9.84
.37
49.8 9.94
.38
80_F
27_C
.78
.88
.96
.59
.64
.71
.47
.50
.53
85_F
29_C
.95
1.00
1.00
.74
.84
.93
.57
.62
.69
Total
Cooling
Capacity
kBtuh kW
140.0
145.2
149.6
148.0
152.4
155.6
157.4
161.4
164.2
41.0
42.6
43.8
43.4
44.7
45.6
46.1
47.3
48.1
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
10.38 .62
10.50 .69
10.62 .76
10.58 .49
10.70 .51
10.78 .55
10.82 .36
10.94 .37
11.02 .39
80_F
27_C
.80
.90
.98
.60
.66
.73
.47
.50
.54
85_F
29_C
.97
1.00
1.00
.75
.86
.95
.58
.63
.71
Total
Cooling
Capacity
kBtuh kW
135.0
140.0
144.6
142.8
146.8
149.8
151.6
155.4
158.2
39.6
41.0
42.4
41.9
43.0
43.9
44.4
45.5
46.4
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
11.62 .63
.82
.99
11.74 .71
.93
1.00
11.88 .78
1.00
1.00
11.82 .49
.61
.78
11.94 .52
.68
.89
12.04 .55
.76
.97
12.08 .37
.48
.59
12.20 .38
.51
.65
12.28 .39
.55
.73
25 TON STANDARD EFFICIENCY − LGC300S (R−22/CAV) − ALL COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
8000
10000
12000
8000
10000
12000
8000
10000
12000
85_F (29_C)
Total
Cooling
Capacity
L/s kBtuh kW
3775
4720
5665
3775
4720
5665
3775
4720
5665
291.5
302.4
311.6
308.4
317.4
324.1
327.8
336.3
342.1
85.4
88.6
91.3
90.4
93.0
95.0
96.1
98.6
100.3
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
20.90 .70
21.15 .76
21.38 .82
21.30 .55
21.55 .58
21.71 .61
21.79 .41
22.03 .42
22.20 .43
80_F
27_C
.86
.95
1.00
.68
.73
.80
.53
.57
.60
85_F
29_C
1.00
1.00
1.00
.82
.91
.99
.65
.71
.77
Total
Cooling
Capacity
kBtuh
281.1
291.7
301.3
297.4
305.9
312.2
315.9
323.9
329.6
105_F (41_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
82.4 23.41 .71
85.5 23.65 .77
88.3 23.92 .84
87.2 23.81 .55
89.7 24.05 .59
91.5 24.24 .62
92.6 24.33 .41
94.9 24.57 .42
96.6 24.73 .44
80_F
27_C
.88
.97
1.00
.69
.75
.82
.54
.58
.61
85_F
29_C
1.00
1.00
1.00
.84
.93
1.00
.66
.73
.79
Total
Cooling
Capacity
kBtuh kW
270.1
280.5
290.1
285.5
293.5
299.4
303.4
311.0
316.0
79.2
82.2
85.0
83.7
86.0
87.7
88.9
91.1
92.6
115_F (46_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
26.23 .72
26.51 .79
26.79 .86
26.67 .56
26.91 .60
27.11 .63
27.23 .41
27.43 .43
27.63 .44
80_F
27_C
.90
.99
1.00
.70
.77
.84
.55
.59
.63
85_F
29_C
1.00
1.00
1.00
.86
.96
1.00
.68
.74
.82
Total
Cooling
Capacity
kBtuh kW
258.4
268.5
278.7
272.7
280.2
286.0
290.1
297.0
301.6
75.7
78.7
81.7
79.9
82.1
83.8
85.0
87.0
88.4
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
29.44 .74
.92
1.00
29.74 .81
1.00
1.00
30.05 .89
1.00
1.00
29.89 .57
.71
.88
30.17 .61
.79
.98
30.37 .65
.87
1.00
30.46 .42
.55
.69
30.67 .43
.60
.76
30.87 .45
.64
.84
25 TON HIGH EFFICIENCY − LGC300H (R−22/CAV) − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
8000
10000
12000
8000
10000
12000
8000
10000
12000
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
3775
4720
5665
3775
4720
5665
3775
4720
5665
157.5
163.6
168.5
167.5
173.2
177.2
178.5
184.2
187.9
46.2
47.9
49.4
49.1
50.8
51.9
52.3
54.0
55.1
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
8.00
.58
8.08
.63
8.14
.69
8.12
.46
8.19
.48
8.25
.51
8.27
.35
8.34
.36
8.39
.37
80_F
27_C
.73
.83
.91
.56
.60
.66
.44
.47
.49
85_F
29_C
.90
.99
1.00
.69
.78
.87
.54
.58
.63
Total
Cooling
Capacity
kBtuh
152.7
158.6
163.4
162.4
167.7
171.5
173.0
178.3
181.8
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
44.8 9.01
.59
46.5 9.11
.64
47.9 9.17
.71
47.6 9.16
.46
49.1 9.25
.49
50.3 9.31
.51
50.7 9.33
.35
52.3 9.41
.36
53.3 9.48
.37
80_F
27_C
.75
.85
.93
.57
.61
.67
.45
.47
.50
85_F
29_C
.92
1.00
1.00
.70
.80
.89
.55
.59
.65
Total
Cooling
Capacity
kBtuh kW
147.9
153.6
158.4
157.1
162.2
165.8
167.5
172.4
175.7
43.3
45.0
46.4
46.0
47.5
48.6
49.1
50.5
51.5
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
10.09 .60
10.20 .65
10.28 .72
10.26 .47
10.36 .49
10.43 .52
10.45 .35
10.55 .36
10.61 .37
80_F
27_C
.77
.87
.95
.57
.62
.69
.45
.48
.51
85_F
29_C
.94
1.00
1.00
.72
.82
.91
.55
.60
.66
Total
Cooling
Capacity
kBtuh kW
143.0
148.4
153.1
151.8
156.5
160.0
161.7
166.3
169.5
41.9
43.5
44.9
44.5
45.9
46.9
47.4
48.7
49.7
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
11.28 .60
.79
.96
11.39 .67
.89
1.00
11.49 .74
.97
1.00
11.46 .47
.58
.74
11.57 .50
.64
.85
11.64 .53
.71
.94
11.67 .35
.46
.56
11.77 .36
.49
.61
11.85 .37
.52
.69
25 TON HIGH EFFICIENCY − LGC300H (R−22/CAV) − ALL COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
8000
10000
12000
8000
10000
12000
8000
10000
12000
85_F (29_C)
Total
Cooling
Capacity
L/s kBtuh kW
3775
4720
5665
3775
4720
5665
3775
4720
5665
294.0
305.2
314.8
312.4
322.4
329.6
332.8
342.6
349.4
86.2
89.4
92.3
91.6
94.5
96.6
97.5
100.4
102.4
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
18.94 .67
19.16 .72
19.30 .78
19.26 .53
19.46 .56
19.58 .59
19.62 .40
19.80 .41
19.94 .42
80_F
27_C
.82
.90
.96
.65
.70
.76
.51
.54
.57
85_F
29_C
.96
1.00
1.00
.78
.86
.93
.62
.68
.73
Total
Cooling
Capacity
kBtuh
284.2
295.2
304.2
301.8
311.2
318.0
321.4
330.6
337.0
105_F (41_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
83.3 21.18 .68
86.5 21.38 .74
89.2 21.56 .80
88.4 21.52 .53
91.2 21.70 .56
93.2 21.84 .59
94.2 21.90 .40
96.9 22.10 .41
98.8 22.24 .42
80_F
27_C
.83
.91
.98
.66
.71
.77
.52
.55
.58
85_F
29_C
.97
1.00
1.00
.79
.88
.95
.63
.69
.75
Total
Cooling
Capacity
kBtuh kW
274.0
284.4
293.6
290.6
299.4
305.6
309.4
318.0
323.6
80.3
83.3
86.0
85.2
87.7
89.6
90.7
93.2
94.8
115_F (46_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
23.66 .69
23.88 .75
24.06 .82
24.06 .54
24.22 .57
24.40 .60
24.48 .40
24.66 .41
24.82 .43
80_F
27_C
.85
.93
.99
.67
.73
.79
.52
.56
.59
85_F
29_C
.99
1.00
1.00
.81
.90
.97
.65
.70
.77
Total
Cooling
Capacity
kBtuh kW
262.6
272.8
282.2
278.4
286.6
292.4
296.4
304.4
309.8
77.0
79.9
82.7
81.6
84.0
85.7
86.9
89.2
90.8
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
26.46 .70
.87
1.00
26.74 .77
.96
1.00
26.98 .84
1.00
1.00
26.88 .55
.68
.83
27.08 .58
.75
.92
27.28 .62
.81
.99
27.34 .40
.53
.66
27.54 .42
.57
.72
27.70 .43
.61
.79
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 31
COOLING RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
25 TON HIGH EFFICIENCY − LGC300H2V (R−22/VAV) − COOLING CAPACITY − ONE COMPRESSOR OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
2000
2500
3000
2000
2500
3000
2000
2500
3000
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
945
1180
1415
945
1180
1415
945
1180
1415
59.8
64.2
67.4
64.3
68.9
72.2
69.0
73.8
77.2
17.5
18.8
19.8
18.8
20.2
21.2
20.2
21.6
22.6
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
5.10
.60
5.19
.61
5.25
.63
5.20
.50
5.28
.50
5.34
.51
5.29
.41
5.38
.41
5.44
.40
80_F
27_C
.68
.71
.73
.57
.58
.60
.48
.48
.49
Total
Cooling
Capacity
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
85_F
75_F
kBtuh kW Input
29_C
24_C
.76
58.2 17.1 5.75
.61
.80
62.4 18.3 5.85
.62
.84
65.4 19.2 5.92
.64
.64
62.6 18.3 5.86
.50
.67
67.0 19.6 5.96
.51
.70
70.1 20.5 6.03
.51
.54
67.2 19.7 5.97
.41
.56
71.8 21.0 6.08
.41
.57
75.0 22.0 6.15
.40
80_F
27_C
.69
.71
.74
.57
.59
.61
.48
.48
.49
Total
Cooling
Capacity
85_F
kBtuh kW
29_C
.77
56.7 16.6
.81
60.6 17.8
.85
63.4 18.6
.65
60.9 17.8
.67
65.0 19.0
.71
67.9 19.9
.54
65.5 19.2
.56
69.7 20.4
.58
72.7 21.3
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
6.45
.61
6.55
.62
6.63
.64
6.57
.50
6.68
.51
6.76
.51
6.70
.41
6.81
.40
6.89
.40
80_F
27_C
.69
.72
.75
.58
.59
.61
.48
.48
.49
Total
Cooling
Capacity
85_F
kBtuh kW
29_C
.77
55.0 16.1
.82
58.7 17.2
.86
61.4 18.0
.65
59.1 17.3
.68
63.0 18.5
.71
65.7 19.3
.55
63.5 18.6
.56
67.5 19.8
.58
70.3 20.6
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
7.22
.61
.70
.78
7.33
.63
.73
.83
7.42
.65
.76
.88
7.35
.50
.58
.66
7.47
.51
.59
.69
7.55
.52
.62
.72
7.49
.41
.48
.55
7.62
.40
.48
.57
7.70
.40
.50
.59
25 TON HIGH EFFICIENCY − LGC300H2V (R−22/VAV) − COOLING CAPACITY − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
4000
5000
6000
4000
5000
6000
4000
5000
6000
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
1890
2360
2830
1890
2360
2830
1890
2360
2830
156.1
162.4
167.4
166.8
172.7
177.0
177.9
184.0
188.4
45.7
47.6
49.1
48.9
50.6
51.9
52.1
53.9
55.2
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
9.43
.71
9.54
.75
9.61
.80
9.59
.57
9.70
.59
9.76
.62
9.77
.43
9.87
.44
9.94
.45
80_F
27_C
.84
.91
.97
.68
.73
.78
.55
.57
.60
85_F
29_C
.97
1.00
1.00
.81
.87
.94
.66
.70
.75
Total
Cooling
Capacity
kBtuh
151.3
157.4
162.0
161.5
167.2
171.2
172.4
178.1
182.2
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
44.3 10.63 .72
46.1 10.74 .77
47.5 10.84 .82
47.3 10.83 .57
49.0 10.95 .60
50.2 11.02
.62
50.5 11.04
.43
52.2 11.15
.44
53.4 11.22
.45
80_F
27_C
.85
.92
.98
.69
.74
.79
.55
.58
.61
85_F
29_C
.98
1.00
1.00
.82
.89
.95
.66
.71
.76
Total
Cooling
Capacity
kBtuh kW
146.5
152.2
156.8
156.3
161.6
165.3
166.8
172.2
175.9
42.9
44.6
46.0
45.8
47.4
48.4
48.9
50.5
51.6
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
11.92 .73
12.03 .78
12.15 .83
12.13 .57
12.25 .60
12.35 .63
12.36 .44
12.49 .44
12.59 .46
80_F
27_C
.87
.94
1.00
.70
.75
.80
.56
.59
.62
85_F
29_C
1.00
1.00
1.00
.83
.90
.97
.67
.72
.78
Total
Cooling
Capacity
kBtuh kW
141.5
147.0
151.4
150.9
155.9
159.4
161.0
166.1
169.4
41.5
43.1
44.4
44.2
45.7
46.7
47.2
48.7
49.6
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
13.32 .74
.88
1.00
13.44 .79
.95
1.00
13.56 .84
1.00
1.00
13.55 .58
.71
.85
13.69 .61
.76
.92
13.78 .64
.82
.99
13.81 .44
.56
.68
13.94 .45
.59
.74
14.04 .46
.63
.80
25 TON HIGH EFFICIENCY − LGC300H2V (R−22/VAV) − COOLING CAPACITY − THREE COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
6000
7500
9000
6000
7500
9000
6000
7500
9000
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
2830
3540
4250
2830
3540
4250
2830
3540
4250
238.8
247.2
255.4
252.9
259.5
264.2
269.0
275.3
279.8
70.0
72.4
74.9
74.1
76.1
77.4
78.8
80.7
82.0
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
14.71 .69
14.83 .74
14.97 .82
14.93 .53
15.04 .56
15.12 .59
15.19 .39
15.31 .40
15.38 .42
80_F
27_C
.88
.97
1.00
.67
.72
.79
.52
.55
.59
85_F
29_C
1.00
1.00
1.00
.83
.93
1.00
.64
.70
.76
Total
Cooling
Capacity
kBtuh
231.3
239.8
247.9
244.9
251.0
255.6
260.5
266.3
270.5
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
67.8 16.58 .70
70.3 16.74 .76
72.7 16.91 .84
71.8 16.85 .54
73.6 16.98 .57
74.9 17.07 .60
76.3 17.15 .39
78.0 17.28 .40
79.3 17.37 .42
80_F
27_C
.90
.99
1.00
.68
.73
.81
.52
.56
.60
85_F
29_C
1.00
1.00
1.00
.85
.95
1.00
.65
.71
.78
Total
Cooling
Capacity
kBtuh kW
224.0
232.5
240.4
236.8
242.5
246.9
251.8
257.3
261.0
65.6
68.1
70.5
69.4
71.1
72.4
73.8
75.4
76.5
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
18.58 .71
18.77 .78
18.95 .86
18.88 .54
19.02 .58
19.12 .61
19.23 .39
19.36 .41
19.45 .42
80_F
27_C
.92
1.00
1.00
.69
.75
.83
.53
.57
.61
85_F
29_C
1.00
1.00
1.00
.88
.97
1.00
.67
.73
.80
Total
Cooling
Capacity
kBtuh kW
216.5
225.2
232.9
228.5
233.8
238.2
242.8
247.9
251.5
63.4
66.0
68.3
67.0
68.5
69.8
71.2
72.7
73.7
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
20.76 .72
.94
1.00
20.97 .80
1.00
1.00
21.19 .88
1.00
1.00
21.08 .55
.70
.90
21.23 .59
.77
.99
21.34 .62
.85
1.00
21.47 .40
.54
.68
21.60 .41
.58
.75
21.71 .43
.62
.83
25 TON HIGH EFFICIENCY − LGC300H2V (R−22/VAV) − COOLING CAPACITY − FOUR COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
8000
10000
12000
8000
10000
12000
8000
10000
12000
85_F (29_C)
Total
Cooling
Capacity
L/s kBtuh kW
3775
4720
5665
3775
4720
5665
3775
4720
5665
304.1
316.2
325.9
316.5
323.5
329.3
335.4
341.3
345.2
89.1
92.7
95.5
92.8
94.8
96.5
98.3
100.0
101.2
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
23.84 .70
24.12 .76
24.36 .88
24.13 .53
24.29 .57
24.42 .61
24.57 .37
24.71 .39
24.79 .41
80_F
27_C
.97
1.00
1.00
.69
.74
.85
.52
.57
.61
85_F
29_C
1.00
1.00
1.00
.93
1.00
1.00
.67
.73
.81
Total
Cooling
Capacity
kBtuh
294.7
306.4
315.7
305.4
312.1
317.9
323.5
328.8
332.8
Comp
Motor
kW
75_F
kW Input
24_C
86.4 26.66 .71
89.8 26.98 .80
92.5 27.19 .91
89.5 26.94 .54
91.5 27.12 .58
93.2 27.27 .62
94.8 27.41 .38
96.4 27.56 .39
97.5 27.66 .41
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 32
105_F (41_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
80_F
27_C
.99
1.00
1.00
.70
.76
.88
.53
.58
.62
85_F
29_C
1.00
1.00
1.00
.95
1.00
1.00
.68
.74
.85
Total
Cooling
Capacity
kBtuh kW
284.6
296.0
304.7
293.8
300.1
306.4
310.9
316.1
319.6
83.4
86.7
89.3
86.1
88.0
89.8
91.1
92.6
93.7
115_F (46_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
29.78 .73
30.11 .84
30.37 .94
30.07 .55
30.25 .59
30.44 .63
30.58 .38
30.72 .40
30.84 .42
80_F
27_C
1.00
1.00
1.00
.71
.80
.92
.54
.59
.63
85_F
29_C
1.00
1.00
1.00
.98
1.00
1.00
.70
.76
.89
Total
Cooling
Capacity
kBtuh kW
273.8
284.8
292.9
281.3
287.6
294.0
297.5
302.0
305.5
80.2
83.5
85.8
82.4
84.3
86.2
87.2
88.5
89.5
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
33.35 .74
1.00
1.00
33.70 .88
1.00
1.00
33.98 .97
1.00
1.00
33.61 .56
.73
1.00
33.83 .61
.85
1.00
34.00 .65
.95
1.00
34.12 .38
.55
.71
34.31 .41
.60
.81
34.43 .43
.65
.93
COOLING RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
30 TON HIGH EFFICIENCY − LGA360H (R−22/CAV) − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
9000
11200
13400
9000
11200
13400
9000
11200
13400
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
4250
5285
6325
4250
5285
6325
4250
5285
6325
228.1
236.4
242.9
241.8
249.1
254.2
256.8
263.7
268.6
66.8
69.3
71.2
70.9
73.0
74.5
75.3
77.3
78.7
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
11.16
.65
11.32
.70
11.44
.75
11.42
.51
11.56
.54
11.67
.56
11.72
.39
11.87
.40
11.98
.41
80_F
27_C
.79
.87
.94
.63
.67
.73
.50
.53
.55
85_F
29_C
.93
1.00
1.00
.76
.83
.91
.61
.65
.70
Total
Cooling
Capacity
kBtuh
222.4
230.4
236.8
235.6
242.6
247.6
250.2
257.0
261.6
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
65.2 12.26 .66
67.5 12.42 .71
69.4 12.53 .76
69.0 12.51 .52
71.1 12.65 .54
72.6 12.77 .57
73.3 12.81 .39
75.3 12.95 .40
76.7 13.07 .41
80_F
27_C
.80
.88
.95
.63
.68
.74
.50
.53
.56
85_F
29_C
.95
1.00
1.00
.77
.85
.92
.61
.66
.72
Total
Cooling
Capacity
kBtuh kW
216.0
223.6
230.0
228.7
235.3
240.1
242.9
249.3
253.7
63.3
65.5
67.4
67.0
69.0
70.4
71.2
73.1
74.4
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
13.51 .66
13.67 .72
13.79 .78
13.76 .52
13.91 .55
14.00 .58
14.06 .39
14.21 .40
14.30 .41
80_F
27_C
.82
.90
.97
.64
.69
.75
.51
.54
.57
85_F
29_C
.96
1.00
1.00
.78
.86
.94
.62
.67
.73
Total
Cooling
Capacity
kBtuh kW
208.7
216.2
222.6
221.0
227.2
231.9
234.8
240.7
245.0
61.2
63.4
65.2
64.8
66.6
68.0
68.8
70.5
71.8
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
14.96 .67
.83
.98
15.08 .73
.92
1.00
15.21 .79
.98
1.00
15.19 .53
.65
.80
15.34 .56
.71
.88
15.42 .59
.77
.95
15.49 .39
.51
.63
15.63 .40
.54
.68
15.72 .42
.58
.75
30 TON HIGH EFFICIENCY − LGA360H (R−22/CAV) − ALL COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
9000
11200
13400
9000
11200
13400
9000
11200
13400
85_F (29_C)
Total
Cooling
Capacity
L/s kBtuh kW
4250
5285
6325
4250
5285
6325
4250
5285
6325
340.0
352.4
362.6
360.3
370.6
378.2
382.9
392.8
399.7
99.6
103.3
106.3
105.6
108.6
110.8
112.2
115.1
117.1
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
22.02 .71
22.26 .76
22.46 .82
22.41 .55
22.64 .58
22.77 .62
22.87 .42
23.09 .43
23.26 .44
80_F
27_C
.85
.92
.98
.68
.74
.79
.54
.57
.61
85_F
29_C
.98
1.00
1.00
.82
.89
.96
.66
.72
.77
Total
Cooling
Capacity
kBtuh
328.5
340.4
350.9
347.8
357.7
365.0
369.9
379.2
385.7
105_F (41_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
96.3 24.34 .72
99.8 24.55 .77
102.8 24.76 .83
101.9 24.70 .56
104.8 24.93 .59
107.0 25.07 .63
108.4 25.17 .42
111.1 25.39 .43
113.0 25.53 .44
80_F
27_C
.87
.94
.99
.69
.75
.81
.54
.58
.62
85_F
29_C
.99
1.00
1.00
.83
.91
.97
.67
.73
.79
Total
Cooling
Capacity
kBtuh kW
315.8
327.5
338.2
334.1
343.6
350.4
355.4
364.2
370.2
92.6
96.0
99.1
97.9
100.7
102.7
104.2
106.7
108.5
115_F (46_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
26.98 .73
27.17 .79
27.40 .85
27.34 .57
27.53 .60
27.69 .64
27.81 .42
27.98 .43
28.13 .45
80_F
27_C
.88
.96
1.00
.71
.77
.83
.55
.59
.63
85_F
29_C
1.00
1.00
1.00
.85
.93
.99
.68
.75
.81
Total
Cooling
Capacity
kBtuh kW
302.2
313.6
324.6
319.5
328.2
334.4
339.6
347.9
353.0
88.6
91.9
95.1
93.6
96.2
98.0
99.5
102.0
103.5
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
29.91 .74
.90
1.00
30.17 .81
.98
1.00
30.41 .87
1.00
1.00
30.31 .58
.72
.87
30.49 .61
.79
.95
30.68 .65
.85
1.00
30.78 .42
.56
.70
30.96 .44
.60
.76
31.13 .45
.64
.83
30 TON HIGH EFFICIENCY − LGA360H (R−410A/CAV) − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
9600
12000
14400
9600
12000
14400
9600
12000
14400
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
4530
5665
6795
4530
5665
6795
4530
5665
6795
263.3
272.8
280.2
278.8
287.4
293.5
295.4
304.0
310.0
77.2
79.9
82.1
81.7
84.2
86.0
86.6
89.1
90.9
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
14.58 .60
14.72 .64
14.85 .70
14.81 .48
14.95 .50
15.05 .52
15.07 .36
15.21 .37
15.30 .38
80_F
27_C
.74
.82
.90
.58
.62
.67
.46
.48
.51
85_F
29_C
.89
.98
1.00
.70
.78
.86
.55
.60
.64
Total
Cooling
Capacity
kBtuh
254.3
263.7
270.8
269.5
277.7
283.5
285.8
294.0
299.6
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
74.5 16.10 .61
77.3 16.28 .65
79.4 16.41 .71
79.0 16.36 .48
81.4 16.52 .50
83.1 16.63 .53
83.8 16.67 .37
86.2 16.83 .37
87.8 16.93 .38
80_F
27_C
.76
.84
.92
.58
.62
.69
.46
.49
.52
85_F
29_C
.91
.99
1.00
.71
.80
.88
.56
.61
.66
Total
Cooling
Capacity
kBtuh kW
244.3
253.1
260.3
258.8
266.5
272.0
274.7
282.3
287.4
71.6
74.2
76.3
75.8
78.1
79.7
80.5
82.7
84.2
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
18.00 .61
18.18 .67
18.33 .73
18.28 .48
18.46 .51
18.59 .53
18.63 .37
18.80 .37
18.92 .38
80_F
27_C
.78
.86
.94
.59
.64
.71
.47
.50
.52
85_F
29_C
.93
1.00
1.00
.73
.82
.91
.57
.62
.68
Total
Cooling
Capacity
kBtuh kW
233.0
241.5
248.6
246.7
253.9
259.1
262.1
269.0
273.7
68.3
70.8
72.9
72.3
74.4
75.9
76.8
78.8
80.2
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
20.28 .62
.80
.96
20.49 .69
.89
1.00
20.63 .76
.97
1.00
20.58 .49
.60
.76
20.77 .52
.66
.85
20.91 .54
.73
.93
20.95 .37
.48
.58
21.13 .38
.51
.64
21.27 .39
.54
.71
30 TON HIGH EFFICIENCY − LGA360H (R−410A/CAV) − ALL COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
9600
12000
14400
9600
12000
14400
9600
12000
14400
85_F (29_C)
Total
Cooling
Capacity
L/s kBtuh kW
4530
5665
6795
4530
5665
6795
4530
5665
6795
371.1
384.2
395.4
392.9
404.3
412.4
417.0
428.0
435.7
108.8
112.6
115.9
115.1
118.5
120.9
122.2
125.4
127.7
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
25.91 .68
26.20 .73
26.36 .78
26.30 .53
26.54 .56
26.74 .59
26.80 .40
27.04 .41
27.19 .42
80_F
27_C
.82
.90
.96
.65
.71
.76
.52
.55
.58
85_F
29_C
.96
1.00
1.00
.78
.86
.94
.63
.69
.74
Total
Cooling
Capacity
kBtuh
352.8
365.4
376.6
373.2
383.7
391.7
396.3
406.2
413.3
105_F (41_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
103.4 29.18 .69
107.1 29.46 .75
110.4 29.68 .81
109.4 29.59 .54
112.5 29.86 .57
114.8 30.03 .60
116.1 30.12 .40
119.0 30.39 .42
121.1 30.54 .43
80_F
27_C
.84
.92
.98
.67
.72
.79
.53
.56
.60
85_F
29_C
.98
1.00
1.00
.81
.89
.96
.65
.70
.76
Total
Cooling
Capacity
kBtuh kW
332.4
345.0
355.9
351.3
361.3
368.3
373.2
382.2
388.7
97.4
101.1
104.3
103.0
105.9
107.9
109.4
112.0
113.9
115_F (46_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
33.00 .71
33.22 .77
33.52 .84
33.45 .55
33.64 .59
33.81 .62
33.98 .41
34.22 .42
34.35 .44
80_F
27_C
.87
.95
1.00
.69
.75
.82
.54
.57
.61
85_F
29_C
1.00
1.00
1.00
.84
.92
.99
.67
.73
.80
Total
Cooling
Capacity
kBtuh kW
310.2
322.0
333.8
327.2
336.0
342.3
347.4
355.7
360.7
90.9
94.4
97.8
95.9
98.5
100.3
101.8
104.2
105.7
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
37.29 .73
.91
1.00
37.56 .81
.99
1.00
37.86 .88
1.00
1.00
37.71 .56
.71
.87
37.94 .60
.78
.96
38.15 .64
.86
1.00
38.27 .41
.55
.69
38.48 .43
.59
.76
38.63 .44
.64
.83
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 33
COOLING RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
30 TON HIGH EFFICIENCY − LGA360H2V (R−22/VAV) − COOLING CAPACITY − ONE COMPRESSOR OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
2250
2800
3350
2250
2800
3350
2250
2800
3350
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
1060
1320
1580
1060
1320
1580
1060
1320
1580
67.5
72.2
75.5
72.5
77.4
80.8
77.9
82.8
86.4
19.8
21.2
22.1
21.2
22.7
23.7
22.8
24.3
25.3
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
5.73
.67
5.86
.68
5.96
.70
5.87
.56
6.01
.56
6.12
.57
6.03
.46
6.18
.45
6.29
.45
80_F
27_C
.76
.78
.81
.64
.65
.67
.53
.54
.54
Total
Cooling
Capacity
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
85_F
75_F
kBtuh kW Input
29_C
24_C
.84
65.8 19.3 6.40
.67
.88
70.2 20.6 6.52
.69
.92
73.3 21.5 6.62
.71
.72
70.6 20.7 6.54
.56
.74
75.2 22.0 6.68
.56
.77
78.4 23.0 6.78
.57
.61
75.8 22.2 6.70
.46
.62
80.5 23.6 6.85
.45
.64
83.8 24.6 6.95
.45
80_F
27_C
.76
.79
.82
.64
.66
.68
.53
.54
.55
Total
Cooling
Capacity
85_F
kBtuh kW
29_C
.85
63.8 18.7
.89
68.0 19.9
.93
70.9 20.8
.72
68.6 20.1
.75
72.9 21.4
.78
75.9 22.2
.61
73.6 21.6
.63
78.0 22.9
.65
81.1 23.8
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
7.16
.68
7.28
.69
7.37
.71
7.31
.56
7.43
.57
7.53
.57
7.47
.45
7.61
.45
7.71
.45
80_F
27_C
.77
.80
.83
.64
.66
.68
.53
.54
.55
Total
Cooling
Capacity
85_F
kBtuh kW
29_C
.85
61.9 18.1
.90
65.7 19.3
.94
68.4 20.0
.73
66.4 19.5
.76
70.4 20.6
.79
73.2 21.5
.61
71.3 20.9
.63
75.4 22.1
.65
78.3 22.9
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
8.02
.68
.77
.86
8.14
.70
.80
.91
8.24
.72
.84
.96
8.17
.56
.65
.73
8.31
.57
.67
.77
8.40
.58
.69
.81
8.34
.45
.53
.61
8.49
.45
.54
.64
8.59
.45
.55
.66
30 TON HIGH EFFICIENCY − LGA360H2V (R−22/VAV) − COOLING CAPACITY − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
4500
5400
6300
4500
5400
6300
4500
5400
6300
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
2125
2550
2975
2125
2550
2975
2125
2550
2975
174.1
179.7
184.2
185.7
191.0
194.9
197.9
203.3
207.2
51.0
52.7
54.0
54.4
56.0
57.1
58.0
59.6
60.7
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
10.78 .71
10.93 .74
11.03
.78
11.08
.56
11.21
.58
11.32
.60
11.40
.43
11.54
.43
11.65
.44
80_F
27_C
.84
.89
.94
.68
.72
.75
.54
.56
.58
85_F
29_C
.96
1.00
1.00
.80
.86
.91
.65
.69
.73
Total
Cooling
Capacity
kBtuh
168.8
174.0
178.5
179.9
184.8
188.5
191.8
196.7
200.3
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
49.5 11.95
.71
51.0 12.09 .75
52.3 12.20 .79
52.7 12.23 .56
54.2 12.38 .58
55.2 12.47 .61
56.2 12.55 .43
57.6 12.70 .43
58.7 12.80 .44
80_F
27_C
.85
.91
.96
.69
.73
.77
.54
.57
.59
85_F
29_C
.98
1.00
1.00
.82
.87
.93
.66
.70
.74
Total
Cooling
Capacity
kBtuh kW
163.1
168.2
172.3
173.8
178.3
181.8
185.1
189.8
193.3
47.8
49.3
50.5
50.9
52.3
53.3
54.2
55.6
56.7
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
13.28 .72
13.42 .76
13.54 .81
13.57 .57
13.70 .59
13.81 .61
13.90 .43
14.06 .44
14.14 .45
80_F
27_C
.87
.92
.98
.70
.74
.78
.55
.58
.60
85_F
29_C
.99
1.00
1.00
.83
.89
.95
.67
.71
.76
Total
Cooling
Capacity
kBtuh kW
157.1
162.0
166.0
167.3
171.6
174.8
178.2
182.6
185.7
46.0
47.5
48.6
49.0
50.3
51.2
52.2
53.5
54.4
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
14.81 .73
.88
1.00
14.94 .78
.94
1.00
15.08 .82
.99
1.00
15.12 .57
.71
.85
15.24 .60
.75
.91
15.36 .62
.80
.96
15.47 .43
.56
.68
15.59 .44
.58
.73
15.71 .45
.61
.77
30 TON HIGH EFFICIENCY − LGA360H2V (R−22/VAV) − COOLING CAPACITY − THREE COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
6750
8400
10050
6750
8400
10050
6750
8400
10050
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
3185
3965
4745
3185
3965
4745
3185
3965
4745
258.7
267.6
276.2
273.3
279.9
284.8
290.3
296.7
301.0
75.8
78.4
80.9
80.1
82.0
83.5
85.1
87.0
88.2
75_F (24_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
16.85 .69
17.10 .74
17.34 .82
17.27 .53
17.46 .56
17.60 .59
17.74 .39
17.94 .40
18.06 .41
80_F
27_C
.88
.97
1.00
.67
.72
.79
.52
.55
.59
85_F
29_C
1.00
1.00
1.00
.84
.94
.99
.65
.70
.76
Total
Cooling
Capacity
kBtuh
250.6
259.7
268.2
264.7
270.8
275.4
281.0
287.0
291.1
85_F (29_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
75_F
kW Input
24_C
73.4 18.68 .70
76.1 18.92 .76
78.6 19.16 .84
77.6 19.06 .54
79.4 19.24 .57
80.7 19.39 .60
82.4 19.54 .39
84.1 19.73 .40
85.3 19.85 .42
80_F
27_C
.90
.98
1.00
.68
.73
.81
.52
.56
.60
85_F
29_C
1.00
1.00
1.00
.86
.96
1.00
.66
.72
.78
Total
Cooling
Capacity
kBtuh kW
242.4
251.6
259.7
255.5
261.4
265.7
271.3
276.6
280.6
71.0
73.7
76.1
74.9
76.6
77.9
79.5
81.1
82.2
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
20.76 .71
21.02 .78
21.27 .86
21.15 .54
21.33 .58
21.48 .61
21.64 .39
21.81 .41
21.94 .42
80_F
27_C
.93
.99
1.00
.69
.75
.83
.53
.57
.61
85_F
29_C
1.00
1.00
1.00
.88
.97
1.00
.67
.73
.81
Total
Cooling
Capacity
kBtuh kW
233.7
243.1
251.0
245.8
251.3
255.8
261.0
266.0
269.5
68.5
71.2
73.6
72.0
73.6
75.0
76.5
78.0
79.0
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
23.15 .72
.95
1.00
23.44 .81
1.00
1.00
23.69 .88
1.00
1.00
23.54 .55
.70
.91
23.72 .59
.78
.99
23.86 .63
.86
1.00
24.05 .39
.54
.68
24.22 .41
.58
.75
24.34 .43
.62
.84
30 TON HIGH EFFICIENCY − LGA360H2V (R−22/VAV) − COOLING CAPACITY − FOUR COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Ai
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
9000
11200
13400
9000
11200
13400
9000
11200
13400
85_F (29_C)
Total
Cooling
Capacity
L/s kBtuh kW
4250
5285
6325
4250
5285
6325
4250
5285
6325
343.5
356.5
366.8
356.2
363.7
370.1
377.2
383.1
387.1
100.7
104.5
107.5
104.4
106.6
108.5
110.5
112.3
113.4
95_F (35_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
27.98 .70
28.36 .75
28.67 .88
28.35 .53
28.56 .57
28.76 .60
28.96 .37
29.15 .39
29.29 .40
80_F
27_C
.97
1.00
1.00
.68
.74
.84
.52
.56
.60
85_F
29_C
1.00
1.00
1.00
.93
1.00
1.00
.67
.73
.81
Total
Cooling
Capacity
kBtuh
331.9
344.5
354.5
342.7
350.1
356.6
362.7
368.2
372.3
Comp
Motor
kW
75_F
kW Input
24_C
97.3 31.20 .71
101.0 31.61 .79
103.9 31.90 .91
100.4 31.55 .53
102.6 31.77 .58
104.5 31.99 .62
106.3 32.18 .37
107.9 32.37 .39
109.1 32.51 .41
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 34
105_F (41_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
80_F
27_C
.99
1.00
1.00
.70
.75
.88
.53
.57
.62
85_F
29_C
1.00
1.00
1.00
.96
1.00
1.00
.68
.74
.85
Total
Cooling
Capacity
kBtuh kW
319.7
331.9
341.1
328.8
335.7
342.7
347.6
352.6
356.4
93.7
97.3
100.0
96.4
98.4
100.4
101.9
103.3
104.5
115_F (46_C)
Sensible To Total
Ratio (S/T)
Dry Bulb
Comp
Motor
kW
Input 75_F
24_C
34.92 .72
35.32 .84
35.63 .94
35.21 .55
35.49 .59
35.71 .63
35.89 .38
36.07 .40
36.23 .41
80_F
27_C
1.00
1.00
1.00
.71
.80
.92
.54
.59
.63
85_F
29_C
1.00
1.00
1.00
.98
1.00
1.00
.70
.76
.89
Total
Cooling
Capacity
kBtuh kW
307.0
318.6
327.0
314.0
320.8
327.8
331.5
336.3
339.8
90.0
93.4
95.8
92.0
94.0
96.1
97.2
98.6
99.6
Sensible To Total
Comp
Ratio (S/T)
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
39.18 .74
1.00
1.00
39.59 .88
1.00
1.00
39.93 .98
1.00
1.00
39.42 .56
.73
1.00
39.74 .60
.85
1.00
39.99 .65
.95
1.00
40.10 .38
.55
.71
40.31 .40
.60
.82
40.47 .42
.65
.93
HUMIDITROL® REHEAT OPTION RATINGS
13 TON HIGH EFFICIENCY − LGC156H − COOLING CAPACITY WITH HUMIDITROL ON − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
Total
Air
Volume
65_F (18_C)
Total
Cooling
Capacity
cfm
L/s kBtuh kW
4200
5200
6200
4200
5200
6200
4200
5200
6200
1980 57.6 16.9
2455 62.2 18.2
2925 65.9 19.3
1980 79.2 23.2
2455 83.3 24.4
2925 86.4 25.3
1980 104.4 30.6
2455 108.7 31.8
2925 111.7 32.7
75_F (24_C)
Sensible To Total
Ratio (S/T)
85_F (29_C)
Sensible To Total
Ratio (S/T)
95_F (35_C)
Sensible To Total
Ratio (S/T)
Sensible To Total
Total
Total
Total
Ratio (S/T)
Comp
Comp
Comp
Comp
Cooling
Cooling
Cooling
Motor
Capacity Motor
Capacity Motor
Capacity Motor
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
kW
kW
kW
kW
Input 75_F 80_F 85_F
Input 75_F 80_F 85_F
Input 75_F 80_F 85_F
Input 75_F 80_F 85_F
kBtuh kW
kBtuh kW
kBtuh kW
24_C 27_C 29_C
24_C 27_C 29_C
24_C 27_C 29_C
24_C 27_C 29_C
4.73 0.34
0.62
0.89 50.8 14.9 5.35 0.27
0.60
0.92 44.6 13.1 6.04 0.22
0.60
0.93 36.1 10.6 6.67 0.09
0.55
0.97
4.76 0.45
0.77
1.00 55.2 16.2 5.37 0.42
0.79
1.00 48.8 14.3 6.05 0.38
0.79
1.00 39.9 11.7 6.70 0.32
0.82
1.00
4.78 0.55
0.90
1.00 58.7 17.2 5.39 0.55
0.92
1.00 52.2 15.3 6.07 0.53
0.96
1.00 43.5 12.7 6.72 0.50
0.98
1.00
4.77 0.29
0.44
0.63 72.0 21.1 5.38 0.25
0.42
0.63 65.4 19.1 6.07 0.20
0.40
0.63 57.5 16.8 6.71 0.14
0.36
0.63
4.80 0.34
0.52
0.75 76.0 22.3 5.40 0.30
0.51
0.76 69.1 20.2 6.09 0.27
0.49
0.78 61.0 17.9 6.73 0.22
0.48
0.81
4.81 0.37
0.60
0.87 78.8 23.1 5.42 0.35
0.60
0.88 71.8 21.0 6.11 0.32
0.61
0.91 63.5 18.6 6.75 0.28
0.61
0.95
4.81 0.28
0.40
0.52 95.9 28.1 5.42 0.24
0.37
0.50 88.1 25.8 6.11 0.20
0.34
0.48 78.8 23.1 6.75 0.14
0.30
0.46
4.84 0.29
0.43
0.57 99.9 29.3 5.44 0.26
0.41
0.56 91.8 26.9 6.12 0.22
0.38
0.55 82.3 24.1 6.76 0.17
0.35
0.55
4.86 0.31
0.47
0.63 102.7 30.1 5.46 0.27
0.45
0.64 94.4 27.6 6.14 0.23
0.43
0.64 84.7 24.8 6.78 0.19
0.40
0.64
13 TON HIGH EFFICIENCY − LGC156H − COOLING CAPACITY WITH HUMIDITROL ON − ALL COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
4200
5200
6200
4200
6200
6200
4200
5200
6200
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
1980
2455
2925
1980
2455
2925
1980
2455
2925
111.5
118.4
123.9
136.9
143.1
147.7
166.3
172.7
177.2
32.6
34.7
36.3
40.1
41.9
43.2
48.7
50.6
51.9
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
7.08 0.53
0.73
0.93
7.12 0.61
0.85
1.00
7.16 0.68
0.94
1.00
7.14 0.41
0.55
0.71
7.19 0.44
0.62
0.81
7.20 0.48
0.68
0.90
7.20 0.34
0.46
0.58
7.25 0.35
0.49
0.63
7.28 0.36
0.53
0.69
75_F (24_C)
Total
Cooling
Capacity
kBtuh kW
103.3
109.8
115.2
128.1
134.0
138.3
156.0
162.0
166.2
30.2
32.2
33.7
37.5
39.2
40.5
45.7
47.4
48.7
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
8.01 0.50
0.73
0.95
8.04 0.60
0.87
1.00
8.07 0.70
0.96
1.00
8.06 0.39
0.55
0.71
8.09 0.44
0.61
0.82
8.12 0.48
0.69
0.92
8.12 0.32
0.44
0.57
8.15 0.33
0.48
0.64
8.18 0.34
0.51
0.69
85_F (29_C)
Total
Cooling
Capacity
kBtuh kW
95.4
101.7
106.9
119.7
125.2
129.2
146.2
151.8
155.6
27.9
29.8
31.3
35.0
36.7
37.8
42.8
44.4
45.6
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
9.04 0.50
0.75
0.97
9.06 0.60
0.88
1.00
9.09 0.70
0.98
1.00
9.09 0.37
0.54
0.72
9.12 0.42
0.62
0.84
9.14 0.46
0.70
0.95
9.15 0.29
0.43
0.56
9.17 0.31
0.47
0.64
9.19 0.32
0.51
0.70
95_F (35_C)
Total
Cooling
Capacity
kBtuh kW
85.1
90.9
96.3
109.8
115.0
118.7
134.8
140.0
143.6
24.9
26.6
28.2
32.2
33.7
34.8
39.5
41.0
42.0
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
10.05 0.47
0.74
1.00
10.09 0.58
0.90
1.00
10.12 0.71
1.00
1.00
10.11 0.35
0.53
0.73
10.14 0.40
0.61
0.86
10.17 0.45
0.71
0.97
10.17 0.26
0.41
0.56
10.19 0.28
0.46
0.63
10.21 0.31
0.50
0.71
15 TON HIGH EFFICIENCY − LGC180H − COOLING CAPACITY WITH HUMIDITROL ON − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
4800
6000
7200
4800
6000
7200
4800
6000
7200
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
2265
2830
3400
2265
2830
3400
2265
2830
3400
66.6
71.8
75.8
92.2
96.9
100.2
119.4
124.1
127.4
19.5
21.0
22.2
27.0
28.4
29.4
35.0
36.4
37.3
Sensible To Total
Ratio (S/T)
75_F (24_C)
Total
Cooling
Capacity
Sensible To Total
Ratio (S/T)
Comp
Comp
Motor
Motor
Dry Bulb
Dry Bulb
kW
kW
Input 75_F 80_F 85_F
Input 75_F 80_F 85_F
kBtuh kW
24_C 27_C 29_C
24_C 27_C 29_C
5.91 0.34
0.61
0.86 58.0 17.0 6.63 0.27
0.59
0.89
5.95 0.44
0.76
1.00 62.9 18.4 6.67 0.40
0.75
1.00
5.99 0.55
0.89
1.00 66.9 19.6 6.70 0.54
0.90
1.00
5.97 0.29
0.45
0.64 82.2 24.1 6.69 0.22
0.42
0.63
6.01 0.33
0.53
0.75 86.6 25.4 6.73 0.28
0.51
0.76
6.05 0.38
0.61
0.86 89.9 26.3 6.76 0.34
0.59
0.87
6.05 0.26
0.39
0.52 110.1 32.3 6.77 0.23
0.37
0.51
6.09 0.27
0.43
0.57 114.6 33.6 6.82 0.23
0.40
0.57
6.12 0.28
0.47
0.64 117.7 34.5 6.84 0.25
0.44
0.64
85_F (29_C)
Total
Cooling
Capacity
kBtuh kW
45.1
49.9
53.7
74.9
79.1
82.2
102.7
106.9
109.8
13.2
14.6
15.7
22.0
23.2
24.1
30.1
31.3
32.2
Sensible To Total
Ratio (S/T)
95_F (35_C)
Sensible To Total
Ratio (S/T)
Comp
Comp
Motor
Motor
Dry Bulb
Dry Bulb
kW
kW
Input 75_F 80_F 85_F
Input 75_F 80_F 85_F
kBtuh kW
24_C 27_C 29_C
24_C 27_C 29_C
7.42 0.11
0.52
0.89 39.0 11.4 8.14 0.04
0.52
0.94
7.44 0.32
0.75
1.00 43.6 12.8 8.18 0.27
0.78
1.00
7.48 0.47
0.93
1.00 47.4 13.9 8.21 0.47
0.95
1.00
7.48 0.19
0.40
0.62 66.5 19.5 8.21 0.12
0.36
0.63
7.52 0.24
0.50
0.76 70.5 20.7 8.24 0.20
0.47
0.78
7.54 0.30
0.60
0.88 73.4 21.5 8.28 0.27
0.59
0.91
7.56 0.20
0.34
0.49 91.9 26.9 8.29 0.13
0.31
0.46
7.60 0.22
0.39
0.56 95.9 28.1 8.32 0.16
0.36
0.56
7.62 0.24
0.43
0.64 98.6 28.9 8.35 0.18
0.41
0.65
Total
Cooling
Capacity
15 TON HIGH EFFICIENCY − LGC180H − COOLING CAPACITY WITH HUMIDITROL ON − ALL COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
4800
6000
7200
4800
6000
7200
4800
6000
7200
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
2265
2830
3400
2265
2830
3400
2265
2830
3400
126.3
133.9
139.8
155.9
162.7
167.6
187.3
194.3
199.2
37.01
39.2
41.0
45.7
47.7
49.1
54.9
56.9
58.4
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
8.87 0.51
0.70
0.90
8.93 0.58
0.81
1.00
8.98 0.65
0.91
1.00
8.96 0.39
0.54
0.70
9.02 0.43
0.60
0.80
9.08 0.47
0.67
0.89
9.08 0.31
0.44
0.57
9.14 0.33
0.48
0.61
9.19 0.34
0.51
0.67
75_F (24_C)
Total
Cooling
Capacity
kBtuh kW
116.0
123.3
129.2
144.2
150.6
155.3
176.2
182.8
187.3
34.0
36.1
37.9
42.3
44.1
45.5
51.6
53.6
54.9
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
9.95 0.50
0.70
0.92
10.01 0.57
0.83
1.00
10.05 0.67
0.92
1.00
10.04 0.36
0.53
0.70
10.10 0.41
0.60
0.80
10.15 0.46
0.67
0.89
10.16 0.29
0.43
0.56
10.23 0.31
0.46
0.61
10.27 0.32
0.50
0.68
85_F (29_C)
Total
Cooling
Capacity
kBtuh kW
101.3
108.3
113.9
134.8
141.0
145.4
166.6
172.7
177.0
29.7
31.7
33.4
39.5
41.3
42.6
48.8
50.6
51.9
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
11.16 0.44
0.70
0.93
11.20 0.54
0.83
1.00
11.26 0.65
0.95
1.00
11.25 0.36
0.52
0.71
11.31 0.39
0.60
0.82
11.35 0.44
0.67
0.92
11.37 0.27
0.42
0.55
11.44 0.29
0.46
0.63
11.47 0.32
0.50
0.69
95_F (35_C)
Total
Cooling
Capacity
kBtuh kW
93.3
100.0
105.6
124.3
130.1
134.4
153.6
159.4
163.4
27.3
29.3
30.9
36.4
38.1
39.4
45.0
46.7
47.9
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
12.36 0.43
0.71
0.96
12.42 0.56
0.86
1.00
12.47 0.67
0.97
1.00
12.47 0.33
0.52
0.71
12.52 0.38
0.60
0.83
12.58 0.43
0.69
0.93
12.59 0.25
0.39
0.54
12.64 0.27
0.45
0.62
12.69 0.29
0.49
0.70
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 35
HUMIDITROL® REHEAT OPTION RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
17.5 TON HIGH EFFICIENCY − LGC210H − COOLING CAPACITY WITH HUMIDITROL ON − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
Total
Air
Volume
65_F (18_C)
Total
Cooling
Capacity
cfm
L/s kBtuh kW
5600
7000
8400
5600
7000
8400
5600
7000
8400
2645 45.2 13.2
3305 50.0 14.6
3965 53.6 15.7
2645 68.6 20.1
3305 72.8 21.3
3965 75.8 22.2
2645 97.8 28.6
3305 102.0 29.9
3965 104.8 30.7
Sensible To Total
Ratio (S/T)
75_F (24_C)
Sensible To Total
Ratio (S/T)
85_F (29_C)
Total
Cooling
Capacity
Sensible To Total
Ratio (S/T)
95_F (35_C)
Sensible To Total
Ratio (S/T)
Comp
Comp
Comp
Comp
Motor
Motor
Motor
Motor
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
kW
kW
kW
kW
Input 75_F 80_F 85_F
Input 75_F 80_F 85_F
Input 75_F 80_F 85_F
Input 75_F 80_F 85_F
kBtuh kW
kBtuh kW
kBtuh kW
24_C 27_C 29_C
24_C 27_C 29_C
24_C 27_C 29_C
24_C 27_C 29_C
4.94 0.15
0.52
0.90 40.2 11.8 5.37 0.10
0.52
0.95 32.6 9.5
5.84 −0.04 0.50
1.00 23.8 6.7
6.51 −0.33 0.42
1.00
4.98 0.32
0.77
1.00 44.6 13.1 5.39 0.28
0.78
1.00 36.8 10.8 5.88 0.22
0.83
1.00 27.8 8.1
6.54 0.08
0.85
1.00
5.00 0.50
0.93
1.00 48.2 14.1 5.43 0.50
0.98
1.00 40.6 11.9 5.90 0.46
1.00
1.00 32.0 9.4
6.56 0.43
1.00
1.00
5.00 0.17
0.35
0.59 63.2 18.5 5.41 0.12
0.34
0.61 55.4 16.2 5.90 0.05
0.29
0.59 46.2 13.5 6.56 −0.09 0.20
0.57
5.02 0.24
0.47
0.75 67.0 19.6 5.45 0.20
0.46
0.77 59.0 17.3 5.94 0.14
0.43
0.81 49.6 14.5 6.60 0.04
0.39
0.82
5.06 0.30
0.58
0.90 69.8 20.4 5.47 0.28
0.59
0.93 61.6 18.0 5.96 0.21
0.59
0.96 52.0 15.2 6.62 0.12
0.57
1.00
5.06 0.21
0.35
0.49 92.0 26.9 5.49 0.18
0.34
0.49 83.8 24.5 5.96 0.15
0.30
0.47 74.4 21.8 6.62 0.08
0.26
0.44
5.10 0.23
0.39
0.56 95.8 28.1 5.51 0.21
0.39
0.56 87.4 25.6 6.00 0.17
0.37
0.56 77.6 22.7 6.66 0.11
0.33
0.54
5.12 0.25
0.45
0.64 98.4 28.8 5.55 0.24
0.44
0.65 89.8 26.3 6.01 0.19
0.41
0.66 79.8 23.4 6.67 0.13
0.39
0.66
Total
Cooling
Capacity
Total
Cooling
Capacity
17.5 TON HIGH EFFICIENCY − LGC210H − COOLING CAPACITY WITH HUMIDITROL ON − ALL COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
5600
7000
8400
5600
7000
8400
5600
7000
8400
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
2645
3305
3965
2645
3305
3965
2645
3305
3965
155.4
164.8
172.2
186.2
194.6
200.6
223.6
232.0
237.6
45.5
48.3
50.4
54.5
57.0
58.7
65.5
67.9
69.6
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
10.02 0.52
0.73
0.94
10.08 0.61
0.86
1.00
10.14 0.70
0.97
1.00
10.12 0.40
0.55
0.71
10.18 0.44
0.61
0.83
10.26 0.48
0.69
0.93
10.26 0.32
0.45
0.57
10.34 0.33
0.49
0.63
10.38 0.34
0.52
0.70
75_F (24_C)
Total
Cooling
Capacity
kBtuh kW
147.2
156.0
163.4
177.2
185.0
190.6
214.0
221.6
226.8
43.1
45.7
47.8
51.9
54.2
55.8
62.7
64.9
66.4
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
11.09 0.52
0.75
0.97
11.15 0.62
0.89
1.00
11.21 0.72
0.99
1.00
11.91 0.40
0.55
0.73
11.27 0.44
0.62
0.85
11.31 0.48
0.71
0.95
11.35 0.31
0.44
0.58
11.39 0.32
0.48
0.64
11.45 0.35
0.53
0.71
85_F (29_C)
Total
Cooling
Capacity
kBtuh kW
136.1
144.5
152.1
165.7
172.8
178.1
201.6
208.8
213.6
39.9
42.3
44.5
48.5
50.6
52.1
59.0
61.1
62.5
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
12.29 0.52
0.76
1.00
12.36 0.61
0.91
1.00
12.42 0.72
1.00
1.00
12.40 0.38
0.55
0.73
12.50 0.42
0.63
0.87
12.54 0.48
0.71
0.97
12.54 0.30
0.44
0.58
12.62 0.32
0.48
0.64
12.65 0.33
0.53
0.72
95_F (35_C)
Total
Cooling
Capacity
kBtuh kW
123.4
131.5
139.8
152.2
159.0
163.9
187.7
194.2
198.5
36.1
38.5
40.9
44.6
46.6
48.0
55.0
56.9
58.1
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
13.79 0.50
0.77
1.00
13.87 0.62
0.94
1.00
13.90 0.74
1.00
1.00
13.90 0.36
0.54
0.75
13.98 0.41
0.63
0.89
14.02 0.47
0.74
1.00
14.02 0.28
0.42
0.58
14.10 0.29
0.47
0.65
14.13 0.32
0.52
0.74
20 TON HIGH EFFICIENCY − LGA240H − COOLING CAPACITY WITH HUMIDITROL ON − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
Total
Air
Volume
65_F (18_C)
Total
Cooling
Capacity
cfm
L/s kBtuh kW
6400
8000
9600
6400
8000
9600
6400
8000
9600
3020 51.6 15.1
3775 56.6 16.6
4530 60.8 17.8
3020 78.6 23.0
3775 83.2 24.4
4530 86.4 25.3
3020 106.6 31.2
3775 111.0 32.5
4530 114.2 33.5
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
6.08 0.09
0.46
0.85
6.14 0.26
0.70
1.00
6.18 0.42
0.89
1.00
6.16 0.14
0.33
0.55
6.22 0.20
0.41
0.72
6.24 0.26
0.54
0.85
6.26 0.16
0.30
0.45
6.30 0.19
0.35
0.51
6.34 0.21
0.39
0.59
75_F (24_C)
Total
Cooling
Capacity
kBtuh kW
41.8
46.8
50.8
69.6
73.8
77.0
101.4
105.4
108.4
12.3
13.7
14.9
20.4
21.6
22.6
29.7
30.9
31.8
85_F (29_C)
Sensible To Total
Ratio (S/T)
95_F (35_C)
Sensible To Total
Ratio (S/T)
Sensible To Total
Total
Total
Ratio (S/T)
Comp
Comp
Comp
Cooling
Cooling
Motor
Capacity Motor
Capacity Motor
Dry Bulb
Dry Bulb
Dry Bulb
kW
kW
kW
Input 75_F 80_F 85_F
Input 75_F 80_F 85_F
Input 75_F 80_F 85_F
kBtuh kW
kBtuh kW
24_C 27_C 29_C
24_C 27_C 29_C
24_C 27_C 29_C
6.72 −0.06 0.41
0.85 30.8 9.0
7.37 −0.35 0.27
0.88 19.8 5.8
8.13 −0.97 0.01
0.94
6.75 0.15
0.70
1.00 35.6 10.4 7.43 −0.01 0.69
1.00 24.2 7.1
8.19 −0.33 0.66
1.00
6.81 0.38
0.92
1.00 39.6 11.6 7.46 0.29
0.94
1.00 28.4 8.3
8.24 0.13
1.00
1.00
6.79 0.06
0.29
0.53 58.4 17.1 7.44 −0.06 0.18
0.50 46.8 13.7 8.22 −0.28 0.04
0.45
6.85 0.14
0.40
0.73 62.4 18.3 7.50 0.04
0.33
0.73 50.6 14.9 8.27 −0.14 0.26
0.73
6.87 0.21
0.52
0.87 65.4 19.2 7.54 0.12
0.49
0.90 53.4 15.7 8.32 −0.01 0.45
0.93
6.89 0.15
0.30
0.44 91.8 26.9 7.56 0.09
0.25
0.41 84.8 24.8 8.33 0.05
0.23
0.40
6.95 0.17
0.35
0.51 95.6 28.0 7.59 0.12
0.30
0.51 88.6 26.0 8.37 0.08
0.29
0.50
6.96 0.19
0.39
0.59 98.4 28.8 7.65 0.14
0.37
0.60 91.0 26.7 8.41 0.12
0.36
0.61
20 TON HIGH EFFICIENCY − LGA240H − COOLING CAPACITY WITH HUMIDITROL ON − ALL COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
6400
8000
9600
6400
8000
9600
6400
8000
9600
65_F (18_C)
Total
Cooling
Capacity
L/s kBtuh kW
3020
3775
4530
3020
3775
4530
3020
3775
4530
178.9
189.0
197.4
214.0
223.2
230.0
251.3
260.2
266.3
52.4
55.4
57.9
62.7
65.4
67.4
73.6
76.3
78.0
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
12.22 0.55
0.74
0.94
12.34 0.62
0.86
1.00
12.42 0.71
0.96
1.00
12.40 0.42
0.57
0.72
12.50 0.45
0.64
0.82
12.57 0.49
0.70
0.93
12.58 0.32
0.45
0.58
12.68 0.33
0.49
0.63
12.78 0.35
0.52
0.70
75_F (24_C)
Total
Cooling
Capacity
kBtuh kW
165.6
175.4
183.6
201.0
209.8
216.1
241.6
250.0
255.7
48.5
51.4
53.8
58.9
61.5
63.3
70.8
73.3
74.9
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 36
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
13.62 0.54
0.75
0.96
13.73 0.62
0.87
1.00
13.81 0.71
0.97
1.00
13.78 0.40
0.56
0.73
13.89 0.44
0.63
0.85
13.97 0.49
0.72
0.94
13.97 0.32
0.44
0.58
14.09 0.33
0.49
0.64
14.16 0.35
0.53
0.71
85_F (29_C)
Total
Cooling
Capacity
kBtuh kW
150.4
160.0
168.0
185.4
193.6
199.5
227.3
235.1
240.6
44.0
46.9
49.2
54.3
56.7
58.5
66.6
68.9
70.5
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
15.19 0.52
0.76
0.98
15.27 0.61
0.89
1.00
15.37 0.71
1.00
1.00
15.34 0.38
0.55
0.74
15.43 0.43
0.64
0.85
15.54 0.48
0.72
0.96
15.54 0.30
0.44
0.58
15.65 0.31
0.48
0.65
15.72 0.33
0.53
0.72
95_F (35_C)
Total
Cooling
Capacity
kBtuh kW
135.2
144.2
152.6
169.3
177.0
182.6
215.5
223.0
227.9
39.6
42.3
44.7
49.6
51.9
53.5
63.2
65.4
66.8
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
16.95 0.51
0.76
1.00
17.05 0.62
0.92
1.00
17.15 0.72
1.00
1.00
17.13 0.35
0.54
0.74
17.21 0.40
0.63
0.87
17.32 0.46
0.73
0.99
17.35 0.29
0.43
0.59
17.43 0.30
0.48
0.66
17.52 0.33
0.53
0.74
HUMIDITROL® REHEAT OPTION RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
25 TON HIGH EFFICIENCY − LGC300S − COOLING CAPACITY WITH HUMIDITROL ON − TWO COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
8000
10000
12000
8000
10000
12000
8000
10000
12000
65_F (18_C)
Sensible To Total
Ratio (S/T)
Total
Cooling
Capacity
L/s kBtuh kW
3775
4720
5665
3775
4720
5665
3775
4720
5665
77.0
82.6
87.2
99.0
103.8
107.2
138.8
143.4
146.6
22.5
24.2
25.5
29.0
30.4
31.4
40.6
42.0
42.9
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
8.34
.25
.55
.88
8.46
.36
.74
1.00
8.56
.51
.91
1.00
8.52
.17
.35
.55
8.64
.22
.42
.72
8.74
.27
.53
.86
8.76
.23
.35
.47
8.88
.24
.39
.53
8.96
.26
.43
.60
75_F (24_C)
Total
Cooling
Capacity
kBtuh kW
62.6
68.0
72.4
90.2
94.8
98.0
122.6
127.2
130.0
18.3
19.9
21.2
26.4
27.8
28.7
35.9
37.2
38.1
85_F (29_C)
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
9.01
.10
.49
.88
9.14
.27
.74
1.00
9.24
.45
.91
1.00
9.20
.12
.30
.56
9.32
.18
.40
.73
9.42
.24
.52
.89
9.46
.15
.30
.43
9.55
.17
.34
.50
9.65
.19
.39
.59
Total
Cooling
Capacity
kBtuh kW
45.0
50.2
54.6
70.0
74.4
77.6
102.4
106.4
109.2
13.2
14.7
16.0
20.5
21.8
22.7
30.0
31.2
32.0
95_F (35_C)
Sensible To Total
Ratio (S/T)
Sensible To Total
Ratio (S/T)
Comp
Comp
Motor
Motor
Dry Bulb
Dry Bulb
kW
kW
Input 75_F 80_F 85_F
Input 75_F 80_F 85_F
kBtuh kW
24_C 27_C 29_C
24_C 27_C 29_C
9.59
−.18
.38
.91
27.0 7.9 10.37 −.85
.10
.95
9.71
.10
.71
1.00 32.0 9.4 10.47 −.27
.69
1.00
9.82
.34
.95
1.00 36.6 10.7 10.60 .13
1.00
1.00
9.78
−.08
.15
.47
50.8 14.9 10.54 −.43
−.10
.38
9.89
0
.30
.71
54.8 16.0 10.65 −.29
.14
.71
9.96
.10
.46
.90
57.8 16.9 10.74 −.17
.38
.92
10.00 .02
.19
.35
82.6 24.2 10.78 −.16
.05
.25
10.11
.04
.24
.44
86.4 25.3 10.88 −.12
.12
.37
10.19 .08
.31
.56
89.2 26.1 10.95 −.08
.20
.52
Total
Cooling
Capacity
25 TON HIGH EFFICIENCY − LGC300S − COOLING CAPACITY WITH HUMIDITROL ON − ALL COMPRESSORS OPERATING
Outdoor Air Temperature Entering Outdoor Coil
Entering
Wet Bulb
Temperature
Total
Air
Volume
cfm
63_F
(17_C)
67_F
(19_C)
71_F
(22_C)
8000
10000
12000
8000
10000
12000
8000
10000
12000
65_F (18_C)
Sensible To Total
Ratio (S/T)
Total
Cooling
Capacity
L/s kBtuh kW
3775
4720
5665
3775
4720
5665
3775
4720
5665
238.3
249.9
259.5
269.8
279.9
287.0
320.3
330.0
336.7
69.8
73.2
76.0
79.0
82.0
84.0
93.8
96.6
98.6
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
16.78 .58
.78
.97
17.03 .65
.88
1.00
17.23 .73
.97
1.00
17.16 .44
.59
.74
17.40 .48
.65
.85
17.59 .52
.72
.94
17.65 .36
.48
.60
17.89 .37
.51
.66
18.05 .38
.55
.73
75_F (24_C)
Total
Cooling
Capacity
kBtuh kW
219.1
230.4
239.6
256.0
265.5
272.3
298.7
308.2
314.2
64.2
67.5
70.2
75.0
77.7
79.7
87.5
90.2
92.0
85_F (29_C)
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
18.42 .57
.79
.99
18.69 .66
.91
1.00
18.89 .74
1.00
1.00
18.81 .43
.59
.75
19.05 .47
.65
.86
19.24 .51
.74
.96
19.32 .33
.47
.59
19.52 .34
.50
.66
19.72 .36
.54
.73
Total
Cooling
Capacity
kBtuh kW
196.5
207.4
216.6
230.4
239.4
246.1
272.8
281.3
287.1
57.3
60.7
63.4
67.5
70.1
72.1
79.9
82.4
84.1
95_F (35_C)
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
20.11
.55
.79
1.00
20.35 .65
.93
1.00
20.58 .74
1.00
1.00
20.50 .40
.57
.76
20.74 .44
.64
.88
20.89 .49
.74
.99
20.97 .29
.44
.58
21.20 .31
.49
.65
21.37 .32
.52
.73
Total
Cooling
Capacity
kBtuh kW
173.1
183.7
193.3
205.4
213.9
220.2
246.9
254.9
260.6
50.7
53.8
56.6
60.1
62.6
64.5
72.3
74.6
76.3
Sensible To Total
Ratio (S/T)
Comp
Motor
Dry Bulb
kW
Input 75_F 80_F 85_F
24_C 27_C 29_C
22.16 .53
.81
1.00
22.38 .63
.95
1.00
22.64 .75
1.00
1.00
22.53 .35
.55
.77
22.76 .41
.64
.90
22.94 .46
.74
1.00
23.03 .25
.41
.56
23.25 .26
.47
.66
23.40 .29
.51
.73
HIGH ALTITUDE DERATE
Units may be installed at altitudes up to 2000 feet (610 m) above sea level without any modification.
At altitudes above 2000 feet (610 m), units must be derated to match gas manifold pressures shown
in table below. NOTE − This is the only permissible derate for these units.
Natural Gas
LPG/Propane
Altitude − ft.
ft (m)
in. w.g.
kPa
in. w.g.
kPa
2001 − 3000 (610 − 915)
3.6
0.90
10.2
2.54
3001 − 4000 (915 − 1220)
3.5
0.87
9.9
2.46
4001 − 5000 (1220 − 1525)
3.4
0.85
9.6
2.39
5001 − 6000 (1525 − 1830)
3.3
0.82
9.4
2.34
6001 − 7000 (1830 − 2135)
3.2
0.80
9.1
2.26
7001 − 8000 (2135 − 2440)
3.1
0.77
8.8
2.19
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 37
BLOWER DATA
13, 15, 17.5, 20, and 25 TON (156H, 180, 210, 240, and 300S)
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL & AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 − Wet indoor coil air resistance of selected unit.
2 − Any factory installed options air resistance (heat section, economizer, etc.)
3 − Any field installed accessories air resistance (duct resistance, diffuser, etc.)
Then determine from blower table blower motor output and drive required.
See pages 41 and 43 for wet coil and option/accessory air resistance data.
See page 40 for factory installed drive kit specifications.
Air
Volume
cfm
f
(L/s)
4000
(1890)
4250
(2005)
4500
(2125)
4750
(2240)
5000
(2360)
5250
(2475)
5500
(2595)
5750
(2715)
6000
(2830)
6250
(2950)
6500
(3065)
6750
(3185)
7000
(3305)
7250
(3420)
7500
(3540)
7750
(3655)
8000
(3775)
8250
(3895)
8500
(4010)
8750
(4130)
9000
(4245)
9250
(4365)
9500
(4485)
9750
(4600)
10000
(4720)
10250
(4835)
10500
(4955)
10750
(5075)
11000
(5190)
.40 (100)
RPM BHP
(kW)
545
0.85
(0.63)
555
0.90
(0.67)
565
1.00
(0.75)
575
1.10
(0.82)
585
1.25
(0.93)
595
1.35
(1.01)
605
1.45
(1.08)
615
1.60
(1.19)
630
1.75
(1.31)
640
1.90
(1.42)
650
2.05
(1.53)
665
2.20
(1.64)
675
2.35
(1.75)
690
2.60
(1.94)
700
2.75
(2.05)
715
3.00
(2.24)
725
3.20
(2.39)
740
3.40
(2.54)
750
3.65
(2.72)
765
3.90
(2.91)
780
4.20
(3.13)
790
4.45
(3.32)
805
4.75
(3.54)
820
5.05
(3.77)
835
5.40
(4.03)
845
5.65
(4.21)
860
6.00
(4.48)
875
6.40
(4.77)
890
6.80
(5.07)
.60 (150)
RPM BHP
(kW)
635 1.10
(0.82)
645 1.25
(0.93)
655 1.35
(1.01)
660 1.45
(1.08)
670 1.60
(1.19)
680 1.70
(1.27)
690 1.85
(1.38)
700 2.00
(1.49)
710 2.15
(1.60)
720 2.35
(1.75)
730 2.50
(1.87)
745 2.70
(2.01)
755 2.90
(2.16)
765 3.10
(2.31)
775 3.30
(2.46)
790 3.55
(2.65)
800 3.80
(2.83)
810 4.00
(2.98)
825 4.30
(3.21)
835 4.55
(3.39)
850 4.85
(3.62)
860 5.15
(3.84)
875 5.45
(4.07)
885 5.75
(4.29)
900 6.15
(4.59)
910 6.45
(4.81)
925 6.85
(5.11)
940 7.25
(5.41)
950 7.60
(5.67)
.80 (200)
RPM BHP
(kW)
715 1.40
(1.04)
725 1.55
(1.16)
730 1.65
(1.23)
740 1.80
(1.34)
750 1.95
(1.45)
755 2.10
(1.57)
765 2.25
(1.68)
775 2.45
(1.83)
785 2.60
(1.94)
795 2.80
(2.09)
805 3.00
(2.24)
815 3.20
(2.39)
825 3.40
(2.54)
835 3.65
(2.72)
845 3.85
(2.87)
855 4.10
(3.06)
865 4.35
(3.25)
880 4.65
(3.47)
890 4.90
(3.66)
900 5.20
(3.88)
910 5.50
(4.10)
925 5.85
(4.36)
935 6.15
(4.59)
950 6.55
(4.89)
960 6.85
(5.11)
970 7.20
(5.37)
985 7.65
(5.71)
1000 8.05
(6.01)
1010 8.45
(6.30)
TOTAL STATIC PRESSURE Inches Water Gauge (Pa)
1.00 (250) 1.20 (300) 1.40 (350) 1.60 (400) 1.80 (450) 2.00 (495)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
(kW)
(kW)
(kW)
(kW)
(kW)
(kW)
785 1.70 850 2.00 910 2.30 965 2.60 1020 2.90 1070 3.25
(1.27)
(1.49)
(1.72)
(1.94)
(2.16)
(2.42)
795 1.85 855 2.15 915 2.45 970 2.80 1025 3.10 1075 3.45
(1.38)
(1.60)
(1.83)
(2.09)
(2.31)
(2.57)
800 2.00 865 2.35 925 2.65 980 3.00 1030 3.30 1080 3.65
(1.49)
(1.75)
(1.98)
(2.24)
(2.46)
(2.72)
810 2.15 870 2.50 930 2.85 985 3.20 1040 3.55 1085 3.90
(1.60)
(1.87)
(2.13)
(2.39)
(2.65)
(2.91)
815 2.30 880 2.70 940 3.05 995 3.40 1045 3.80 1095 4.15
(1.72)
(2.01)
(2.28)
(2.54)
(2.83)
(3.10)
825 2.50 890 2.90 945 3.25 1000 3.65 1050 4.00 1100 4.40
(1.87)
(2.16)
(2.42)
(2.72)
(2.98)
(3.28)
835 2.65 895 3.05 955 3.45 1010 3.85 1060 4.25 1110 4.70
(1.98)
(2.28)
(2.57)
(2.87)
(3.17)
(3.51)
840 2.85 905 3.25 960 3.65 1015 4.10 1065 4.50 1115 4.95
(2.13)
(2.42)
(2.72)
(3.06)
(3.36)
(3.69)
850 3.05 910 3.45 970 3.90 1025 4.35 1075 4.80 1120 5.20
(2.28)
(2.57)
(2.91)
(3.25)
(3.58)
(3.88)
860 3.25 920 3.70 975 4.15 1030 4.60 1080 5.05 1130 5.50
(2.42)
(2.76)
(3.10)
(3.43)
(3.77)
(4.10)
870 3.45 930 3.95 985 4.40 1040 4.85 1090 5.35 1140 5.85
(2.57)
(2.95)
(3.28)
(3.62)
(3.99)
(4.36)
880 3.70 940 4.20 995 4.65 1045 5.10 1095 5.60 1145 6.10
(2.76)
(3.13)
(3.47)
(3.80)
(4.18)
(4.55)
890 3.95 950 4.45 1005 4.95 1055 5.40 1105 5.95 1155 6.45
(2.95)
(3.32)
(3.69)
(4.03)
(4.44)
(4.81)
900 4.15 955 4.65 1015 5.25 1065 5.75 1115 6.25 1160 6.75
(3.10)
(3.47)
(3.92)
(4.29)
(4.66)
(5.04)
910 4.45 965 4.95 1020 5.50 1075 6.05 1125 6.60 1170 7.15
(3.32)
(3.69)
(4.10)
(4.51)
(4.92)
(5.33)
920 4.70 975 5.25 1030 5.80 1080 6.35 1130 6.90 1180 7.50
(3.51)
(3.92)
(4.33)
(4.74)
(5.15)
(5.60)
930 4.95 985 5.50 1040 6.10 1090 6.70 1140 7.25 1185 7.85
(3.69)
(4.10)
(4.55)
(5.00)
(5.41)
(5.86)
940 5.25 995 5.85 1050 6.45 1100 7.05 1150 7.65 1195 8.25
(3.92)
(4.36)
(4.81)
(5.26)
(5.71)
(6.15)
950 5.55 1005 6.15 1060 6.80 1110 7.40 1160 8.05 1205 8.65
(4.14)
(4.59)
(5.07)
(5.52)
(6.01)
(6.45)
960 5.85 1015 6.45 1070 7.15 1120 7.75 1165 8.35 1215 9.05
(4.36)
(4.81)
(5.33)
(5.78)
(6.23)
(6.75)
970 6.15 1025 6.80 1080 7.50 1130 8.15 1175 8.75 1220 9.40
(4.59)
(5.07)
(5.60)
(6.08)
(6.53)
(7.01)
985 6.55 1040 7.20 1090 7.85 1140 8.55 1185 9.20 1230 9.85
(4.89)
(5.37)
(5.86)
(6.38)
(6.86)
(7.35)
995 6.90 1050 7.60 1100 8.25 1150 8.95 1195 9.60 1240 10.30
(5.15)
(5.67)
(6.15)
(6.68)
(7.16)
(7.68)
1005 7.20 1060 7.95 1110 8.65 1160 9.40 1205 10.05 1250 10.80
(5.37)
(5.93)
(6.45)
(7.01)
(7.50)
(8.06)
1015 7.60 1070 8.35 1120 9.05 1170 9.80 1215 10.50 1260 11.25
(5.67)
(6.23)
(6.75)
(7.31)
(7.83)
(8.39)
1030 8.00 1080 8.75 1135 9.55 1180 10.25 1225 11.00
−−−
(5.97)
(6.53)
(7.12)
(7.65)
(8.21)
1040 8.40 1095 9.20 1145 10.00 1190 10.70 1235 11.45
−−−
(6.27)
(6.86)
(7.46)
(7.98)
(8.54)
1055 8.85 1105 9.65 1155 10.45 1200 11.20
−−−
−−−
(6.60)
(7.20)
(7.80)
(8.36)
1065 9.30 1115 10.05 1165 10.90
−−−
−−−
−−−
(6.94)
(7.50)
(8.13)
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 38
2.20 (545)
RPM BHP
(kW)
1115 3.55
(2.65)
1120 3.75
(2.80)
1130 4.05
(3.02)
1135 4.25
(3.17)
1140 4.50
(3.36)
1150 4.80
(3.58)
1155 5.10
(3.80)
1160 5.35
(3.99)
1170 5.65
(4.21)
1175 5.95
(4.44)
1185 6.30
(4.70)
1190 6.60
(4.92)
1200 6.95
(5.18)
1205 7.30
(5.45)
1215 7.65
(5.71)
1225 8.05
(6.01)
1230 8.40
(6.27)
1240 8.85
(6.60)
1250 9.25
(6.90)
1255 9.65
(7.20)
1265 10.10
(7.53)
1275 10.55
(7.87)
1285 11.05
(8.24)
1295 11.50
(8.58)
2.40 (595)
RPM BHP
(kW)
1160 3.85
(2.87)
1165 4.10
(3.06)
1175 4.35
(3.25)
1180 4.65
(3.47)
1185 4.90
(3.66)
1195 5.20
(3.88)
1200 5.50
(4.10)
1205 5.80
(4.33)
1215 6.10
(4.55)
1220 6.45
(4.81)
1225 6.75
(5.04)
1235 7.10
(5.30)
1240 7.45
(5.56)
1250 7.85
(5.86)
1260 8.25
(6.15)
1265 8.60
(6.42)
1275 9.00
(6.71)
1280 9.40
(7.01)
1290 9.85
(7.35)
1300 10.30
(7.68)
1310 10.80
(8.06)
1315 11.20
(8.36)
2.60 (645)
RPM BHP
(kW)
1205 4.15
(3.10)
1210 4.45
(3.32)
1215 4.70
(3.51)
1225 5.00
(3.73)
1230 5.30
(3.95)
1235 5.60
(4.18)
1240 5.90
(4.40)
1250 6.25
(4.66)
1255 6.55
(4.89)
1265 6.90
(5.15)
1270 7.25
(5.41)
1275 7.60
(5.67)
1285 8.00
(5.97)
1290 8.35
(6.23)
1300 8.75
(6.53)
1305 9.15
(6.83)
1315 9.60
(7.16)
1325 10.05
(7.50)
1330 10.45
(7.80)
1340 10.90
(8.13)
1350 11.40
(8.50)
−−−
−−−
−−−
−−−
−−−
−−−
−−−
−−−
−−−
−−−
−−−
−−−
−−−
−−−
−−−
−−−
−−−
−−−
−−−
−−−
BLOWER DATA
21, 25, and 30 TON (248H, 300H, and 360H)
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL & AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 − Wet indoor coil air resistance of selected unit.
2 − Any factory installed options air resistance (heat section, economizer, etc.)
3 − Any field installed accessories air resistance ( duct resistance, diffuser, etc.)
Then determine from blower table blower motor output and drive required.
See pages 42−43 for wet coil and option/accessory air resistance data.
See page 40 for factory installed drive kit specifications.
BOLD INDICATES FIELD FURNISHED DRIVE
Air
Volume
cfm
f
(L/s)
TOTAL STATIC PRESSURE Inches Water Gauge (Pa)
.20 (50)
.40 (100)
.60 (150)
.80 (200)
1.00 (250) 1.20 (300) 1.40 (350) 1.60 (400) 1.80 (450) 2.00 (495) 2.20 (545) 2.40 (595) 2.60 (645)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
(kW)
(kW)
(kW)
(kW)
(kW)
(kW)
(kW)
(kW)
(kW)
(kW)
(kW)
(kW)
(kW)
6000
(2830)
---
435 1.20 525 1.45 570 1.60 630 2.00 700 2.35 750 2.80 795 3.15 840 3.40 880 3.80 920 4.20 960 4.65 995 5.10
(0.90)
(1.08)
(1.19)
(1.49)
(1.75)
(2.09)
(2.35)
(2.54)
(2.83)
(3.13)
(3.47)
(3.80)
6500
(3065)
---
445 1.30 530 1.60 580 1.80 640 2.20 705 2.60 755 3.05 800 3.40 845 3.70 885 4.15 925 4.60 965 5.00 1000 5.45
(0.97)
(1.19)
(1.34)
(1.64)
(1.94)
(2.28)
(2.54)
(2.76)
(3.10)
(4.43)
(3.73)
(4.07)
7000
(3305)
---
455 1.40 535 1.75 590 2.05 650 2.45 710 2.85 760 3.30 805 3.70 850 4.05 890 4.50 930 4.95 970 5.40 1005 5.85
(1.04)
(1.31)
(1.53)
(1.83)
(2.13)
(2.46)
(2.76)
(3.02)
(3.36)
(3.69)
(4.03)
(4.36)
7500
(3540)
380
1.05 465 1.50 540 1.90 600 2.30 660 2.70 715 3.15 765 3.60 810 4.00 855 4.45 895 4.90 935 5.35 975 5.85 1010 6.30
(0.78)
(1.12)
(1.42)
(1.72)
(2.01)
(2.35)
(2.69)
(2.98)
(3.32)
(3.66)
(3.99)
(4.36)
(4.70)
8000
(3775)
390
1.25 475 1.65 545 2.10 610 2.55 665 2.95 720 3.45 770 3.90 815 4.35 860 4.85 900 5.30 940 5.75 980 6.30 1015 6.75
(0.93)
(1.23)
(1.57)
(1.90)
(2.20)
(2.57)
(2.91)
(3.25)
(3.62)
(3.95)
(4.29)
(4.70)
(5.04)
8500
(4010)
405
1.40 485 1.90 555 2.35 620 2.80 675 3.30 725 3.75 775 4.20 820 4.70 865 5.20 905 5.70 945 6.20 985 6.75 1020 7.25
(1.04)
(1.42)
(1.75)
(2.09)
(2.46)
(2.80)
(3.13)
(3.51)
(3.88)
(4.25)
(4.63)
(5.04)
(5.41)
9000
(4245)
415
1.60 495 2.10 565 2.60 625 3.10 685 3.60 735 4.10 785 4.60 830 5.10 870 5.60 915 6.15 955 6.70 990 7.20 1025 7.70
(1.19)
(1.57)
(1.94)
(2.31)
(2.69)
(3.06)
(3.43)
(3.80)
(4.18)
(4.59)
(5.00)
(5.37)
(5.74)
9500
(4485)
430
1.85 505 2.35 575 2.90 635 3.40 690 3.90 745 4.50 790 4.95 835 5.50 880 6.05 920 6.60 960 7.15 995 7.70 1035 8.30
(1.38)
(1.75)
(2.16)
(2.54)
(2.91)
(3.36)
(3.69)
(4.10)
(4.51)
(4.92)
(5.33)
(5.74)
(6.19)
10,000
(4720)
445
2.10 520 2.65 585 3.20 645 3.75 700 4.30 750 4.85 800 5.40 845 5.95 885 6.50 925 7.05 965 7.65 1000 8.20 1040 8.85
(1.57)
(1.98)
(2.39)
(2.80)
(3.21)
(6.49)
(4.03)
(4.44)
(4.85)
(5.26)
(5.71)
(6.12)
(6.60)
10,500
4955)
455
2.35 530 2.95 595 3.50 655 4.10 710 4.70 760 5.25 805 5.80 850 6.40 895 7.00 935 7.60 970 8.15 1010 8.80 1045 9.40
(1.75)
(2.20)
(2.61)
(3.06)
(3.03)
(3.92)
(4.33)
(4.77)
(5.22)
(5.67)
(608)
(6.56)
(7.01)
11,000
(5190)
470
2.60 545 3.25 605 3.85 665 4.45 720 5.10 765 5.66 815 6.30 860 6.90 900 7.50 940 8.10 980 8.75 1015 9.35
(1.94)
(2.42)
(2.87)
(3.32)
(3.80)
(4.22)
(4.70)
(5.15)
(5.60)
(6.04)
(6.53)
(6.98)
---
11,500
(5425)
485
2.95 555 3.60 620 4.25 675 4.85 730 5.55 775 6.10 820 6.70 865 7.40 910 8.05 945 8.65 985 9.30 1020 9.95
(2.20)
(2.69)
(3.17)
(3.62)
(4.14)
(4.55)
(5.00)
(5.52)
(6.01)
(6.45)
(6.94)
(7.42)
---
12,000
(5665)
500
3.30 570 4.00 630 4.65 685 5.30 740 6.00 785 6.60 830 7.25 875 7.95 915 8.60 955 9.25 995 9.95 1030 10.60
(2.46)
(2.98)
(3.47)
(3.95)
(4.480
(4.92)
(5.41)
(5.93)
(6.42)
(6.90)
(7.42)
(7.91)
---
12,500
(5900)
515
3.65 580 4.35 640 5.05 695 5.75 750 6.50 795 7.10 840 7.80 885 8.55 925 9.20 965 9.90 1000 10.55 1035 11.25
(2.72)
(3.25)
(3.77)
(4.29)
(4.85)
(5.30)
(5.82)
(6.38)
(6.86)
(7.39)
(7.87)
(8.39)
---
13,000
(6135)
530
4.05 595 4.80 655 5.55 710 6.25 760 7.00 805 7.65 850 8.40 890 9.05 930 9.75 970 10.50 1010 11.30
(3.02)
(3.58)
(4.14)
(4.66)
(5.22)
(5.71)
(6.27)
(6.75)
(7.27)
(7.83)
(8.43)
---
---
13,500
(6370)
545
4.45 610 5.25 665 6.00 720 6.75 770 7.50 815 8.25 860 9.00 900 9.70 940 10.45 980 11.20
(3.32)
(3.92)
(4.48)
(5.04)
(5.60)
(6.15)
(6.71)
(7.24)
(7.80)
(8.36)
---
---
---
14,000
(6605)
560
4.90 620 5.70 680 6.55 730 7.30 780 8.10 825 8.85 870 9.65 910 10.40 950 11.15
(3.66)
(4.25)
(4.89)
(5.45)
(6.04)
(6.60)
(7.20)
7.76)
(8.31)
---
---
---
---
14,500
(6845)
575
5.40 635 6.25 690 7.05 745 7.90 790 8.65 835 9.45 880 10.30 920 11.10
(4.03)
(4.66)
(5.26)
(5.89)
(6.45)
(7.05)
(7.68)
(8.28)
---
---
---
---
---
15,000
(7080)
590
5.90 650 6.80 705 7.65 755 8.50 800 9.30 845 10.10 890 11.00
(4.40)
(5.07)
(5.71)
(6.340
(6.94)
(7.53)
(8.21)
---
---
---
---
---
---
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 39
BLOWER DATA
CONSTANT AIR VOLUME (CAV) BELT DRIVE KIT SPECIFICATIONS
Model No.
Motor Efficiency
Nominal
hp
Maximum
hp
Nominal
kW
Maximum
kW
Drive Kit
Number
RPM Range
156H
Standard or High
2 hp
2.3
1.5
1.7
A
535 − 725
156H thru 210
Standard
3 hp
3.45
2.2
2.6
A
1
535 − 725
685 − 865
High
3 hp
3.45
2.2
2.6
2
685 − 865
156H thru 300S
Standard or High
5 hp
5.75
3.7
4.3
2
3
4
685 − 865
850 − 1045
945 − 1185
180 thru 300S
Standard or High
7.5 hp
8.63
5.6
6.4
5
6
7
945 − 1185
1045 − 1285
850 − 1045
240 thru 300S
Standard or High
10 hp
11.5
7.5
8.6
6
8
1045 − 1285
1135 − 1365
248H, 300H, and 360H
Standard or High
5 hp
5.75
3.7
4.3
1
2
6
660 − 810
770 − 965
560 − 710
Standard or High
7.5 hp
8.63
5.6
6.4
3
4
715 − 880
770 − 965
Standard or High
10 hp
11.5
7.5
8.6
3
5
715 − 880
850 − 1045
NOTE − Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output
of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the
service factor limitations outlined on the motor nameplate.
VARIABLE AIR VOLUME (VAV) DRIVE KIT SPECIFICATIONS
Model No.
248H, 300H, and 360H
Motor Efficiency
Nominal
hp
Nominal
kW
Drive Kit Number
Maximum RPM @ 60Hz
VFD Output (Fixed Pulley)
Standard or High
5 hp
3.7
7
965
Standard or High
7.5 hp
5.6
8
965
Standard or High
10 hp
7.5
9
1045
NOTE − Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. For VFD applications,
nominal motor output is also maximum usable motor output.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 40
BLOWER DATA
13, 15, 17.5, 20, and 25 TON (156H, 180, 210, 240, and 300S)
FACTORY INSTALLED OPTIONS/FIELD INSTALLED ACCESSORY AIR RESISTANCE
Air
Volume
cfm
Wet Indoor Coil
Humiditrol
Gas Heat Exchanger
Hot Gas
Low/Std.
Heat
Med. Heat
High Heat
Reheat Coil
156H,180H,
156H,
210H,
180S/H 240H, 300S 210H, 240H 156 thru 300S 156 thru 300S 180 thru 300S
300S
L/s 210S, 240S
in.
in.
in.
in.
in.
in.
Pa
Pa
Pa
w.g.
w.g.
w.g.
w.g. Pa w.g. Pa w.g. Pa
Horizontal
Roof Curb
Economizer
156H thru
300S
156H thru
240H
in.
w.g.
in.
w.g.
Pa
Pa
MERV 11
Filter
300S
in.
w.g.
Pa
in.
w.g.
Pa
4000 1890 .02
5
.04
10
.02
5
.04
10
.06
15
−−−
−−−
.06
15
−−−
.01
2
4250 2005 .02
5
.04
10
.02
5
.04
10
.06
15
−−−
−−−
.07
17
−−−
.01
2
4500 2125 .02
5
.05
12
.02
5
.05
12
.07
17
.09
22
−−−
.07
17
.02
5
.01
2
4750 2240 .02
5
.05
12
.02
5
.05
12
.08
20
.10
25
−−−
.08
20
.03
7
.01
2
5000 2360 .02
5
.05
12
.02
5
.05
12
.09
22
.11
27
−−−
.08
20
.03
7
.01
2
5250 2475 .02
5
.06
15
.03
7
.06
15
.10
25
.12
30
−−−
.09
22
.04
10
.02
5
5500 2595 .02
5
.07
17
.03
7
.06
15
.10
25
.13
32
−−−
.10
25
.04
10
.02
5
5750 2715 .03
7
.07
17
.03
7
.06
15
.11
27
.14
35
−−−
.11
27
.05
12
.02
5
6000 2830 .03
7
.08
20
.03
7
.07
17
.12
30
.15
37
−−−
.11
27
.06
15
.02
5
6250 2950 .03
7
.08
20
.03
7
.07
17
.12
30
.16
40
.01
2
.12
30
.07
17
.02
5
6500 3065 .03
7
.09
22
.04
10
.08
20
.13
32
.17
42
.02
5
.13
32
.08
20
.02
5
6750 3185 .04
10
.10
25
.04
10
.08
20
.14
35
.18
45
.03
7
.14
35
.08
20
.02
5
7000 3305 .04
10
.10
25
.04
10
.09
22
.15
37
.19
47
.04
10
.15
37
.09
22
.03
7
7250 3420 .04
10
.11
27
.04
10
.09
22
.16
40
.20
50
.05
12
.16
40
.10
25
.03
7
7500 3540 .05
12
.12
30
.05
12
.10
25
.17
42
.21
52
.06
15
.17
42
.11
27
.03
7
8000 3775 .05
12
.13
32
.05
12
.11
27
.19
47
.24
60
.09
22
.19
47
.13
32
.04
10
8500 4010 .06
15
.15
37
.05
12
.12
30
.20
50
.26
65
.11
27
.21
52
.15
37
.04
10
9000 4245 .07
17
.16
40
.06
15
.13
32
.23
57
.29
72
.14
35
.24
60
.17
42
.04
10
9500 4485 .08
20
.18
45
.07
17
.14
35
.25
62
.32
80
.16
40
.26
65
.19
47
.05
12
10,000 4720 .08
20
.20
50
.07
17
.16
40
.27
67
.35
87
.19
47
.29
72
.21
52
.06
15
10,500 4955 .09
22
.22
55
.08
20
.17
42
.30
75
.38
94
.22
55
.31
77
.24
60
.06
15
11,000 5190 .11
27
.24
60
.08
20
.18
45
.31
77
.40
99
.25
62
.34
85
.27
67
.07
17
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 41
BLOWER DATA
21, 25, and 30 TON (248H, 300H, and 360H)
FACTORY INSTALLED OPTIONS/FIELD INSTALLED ACCESSORY AIR RESISTANCE
Air
V l
Volume
Wet Indoor
C il
Coil
Gas Heat Exchanger
Standard Heat
in.
w.g.
Pa
Medium Heat
in.
w.g.
Pa
Economizer
Horizontal
R f Curb
Roof
C b
MERV 11
Filt
Filter
High Heat
in.
w.g.
Pa
in.
w.g.
Pa
in.
w.g.
Pa
in.
w.g.
Pa
cfm
L/s
in.
w.g.
Pa
6000
2830
.04
10
.12
30
.16
40
.19
47
.01
3
.08
20
.01
2
6500
3070
.05
13
.13
32
.18
45
.21
52
.01
3
.09
22
.01
2
7000
3305
.06
15
.14
35
.20
50
.24
59
.02
5
.10
25
.01
2
7500
3540
.07
17
.15
37
.21
52
.25
62
.02
5
.11
27
.02
5
8000
3775
.08
20
.17
42
.24
59
.28
70
.02
5
.13
32
.02
5
8500
4010
.08
20
.20
50
.27
67
.31
77
.03
7
.15
37
.02
5
9000
4245
.09
22
.22
55
.29
72
.34
85
.04
10
.17
42
.02
5
9500
4485
.10
25
.24
60
.32
80
.38
94
.04
10
.19
47
.03
7
10,000
4720
.11
27
.27
67
.36
90
.42
104
.05
12
.21
52
.03
7
10,500
4955
.12
30
.30
75
.40
99
.46
114
.06
15
.24
60
.03
7
11,000
5190
.12
30
.33
92
.43
107
.50
137
.07
17
.27
67
.04
10
11,500
5425
.13
32
.37
92
.48
119
.55
137
.08
20
.30
75
.04
10
12,000
5665
.14
35
.40
99
.52
129
.60
149
.10
25
.33
82
.04
10
12,500
5900
.15
37
.44
109
.57
142
.65
162
.11
27
.37
92
.05
12
13,000
6135
.16
40
.48
119
.61
152
.70
174
.13
32
.40
99
.05
12
13,500
6370
.17
42
.53
132
.67
167
.76
189
.14
35
.44
109
.06
15
14,000
6605
.18
45
.57
142
.72
179
.82
204
.16
40
.49
122
.06
15
14,500
6845
.19
47
.62
154
.78
194
.89
221
.18
45
.53
132
.06
15
15,000
7080
.20
50
.68
169
.84
209
.95
236
.21
52
.58
144
.07
17
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 42
BLOWER DATA
CEILING DIFFUSER AIR RESISTANCE
Step-Down Diffuser
RTD11−185
Air Volume
2 Ends
Open
1 Side/2
Ends
Open
Flush Diffuser
RTD11−275
All Ends
& Sides
Open
2 Ends
Open
1 Side/2
Ends
Open
LARTD30/36
All Ends
& Sides
Open
2 Ends
Open
1 Side/2
Ends
Open
All Ends FD11−185 FD11−275 LAFD30/36
& Sides
Open
in.
in.
in.
in.
in.
in.
in.
in.
in.
in.
Pa
Pa
Pa
Pa
Pa
Pa
Pa
Pa
Pa
Pa
w.g.
w.g.
w.g.
w.g.
w.g.
w.g.
w.g.
w.g.
w.g.
w.g.
in.
Pa
w.g.
in.
w.g.
Pa
67
−−− −−−
−−−
−−−
.30
75
−−− −−−
−−−
−−−
112 − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − −
.33
82
−−− −−−
−−−
−−−
.48
119 − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − −
.36
90
−−− −−−
−−−
−−−
147
.51
127 − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − −
.39
97
−−− −−−
−−−
−−−
.63
157
.55
137
.42 104
.29
72
−−−
−−−
199
.68
169
.59
147 − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − −
.46 114 − − − − − −
−−−
−−−
214
.72
179
.63
157 − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − −
.50 124 − − − − − −
−−−
−−−
85
−−−
−−−
167 − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − −
.54 134 − − − − − −
−−−
−−−
.72
174 − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − −
.58 144 − − − − − −
−−−
−−−
216
.76
189
.62 154
99
−−−
−−−
.92
229
.80
199 − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − −
.66 164 − − − − − −
−−−
−−−
.97
241
.84
209 − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − −
.70 174 − − − − − −
−−−
−−−
−−− −−−
.45 112
.29
72
.74 184 − − − − − −
−−−
−−−
72
−−− −−−
.50 124
.34
85
.34
85
−−− −−−
.57 142
.39
97
117
.39
97
−−− −−−
.66 164
.44
109
.53
132
.45
112 − − − − − −
.74 184
.51
127
174
.60
149
.51
127 − − − − − −
.81 201
.57
142
.78
194
.68
169
.58
144 − − − − − −
.89 221
.65
162
219
.87
216
.76
190
.65
162 − − − − − −
.96 239
.72
179
11,500 5425
−−− −−− −−− −−− −−− −−− −−− −−− −−− −−− −−− −−−
.97
241
.85
211
.73
182 − − − − − − − − − − − −
.81
201
12,000 5665
− − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − 1.08 269
.94
234
.82
204 − − − − − − − − − − − −
.90
223
12,500 5900
− − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − 1.19 296 1.04 259
.91
226 − − − − − − − − − − − −
.99
246
13,000 6135
− − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − 1.30 323 1.15 286 1.00 249 − − − − − − − − − − − − 1.10 274
13,500 6370
− − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − 1.43 356 1.26 313 1.10 374 − − − − − − − − − − − − 1.20 298
14,000 6605
− − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − 1.56 388 1.38 343 1.20 298 − − − − − − − − − − − − 1.31 326
14,500 6845
− − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − 1.69 420 1.50 373 1.31 326 − − − − − − − − − − − − 1.43 356
15,000 7080
− − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − 1.84 457 1.63 405 1.43 356 − − − − − − − − − − − − 1.56 388
cfm
L/s
5000
2360
.51
127
.44
109
.39
97
−−− −−− −−− −−− −−− −−− −−− −−− −−− −−− −−− −−−
.27
5200
2455
.56
139
.48
119
.42
104 − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − −
5400
2550
.61
152
.52
129
.45
5600
2645
.66
164
.56
139
5800
2735
.71
177
.59
6000
2830
.76
189
6200
2925
.80
6400
3020
.86
6500
3065
−−− −−− −−− −−− −−− −−−
6600
3115
.92
229
.77
191
.67
6800
3210
.99
246
.83
206
7000
3305 1.03 256
.87
7200
3400 1.09 271
7400
3490 1.15 286
7500
3540
7600
3585 1.20 301 1.02 254
8000
3775
−−− −−− −−− −−− −−− −−−
.59
147
.49
122
.43
107
.42
104
.36
90
.29
8500
4010
−−− −−− −−− −−− −−− −−−
.69
172
.58
144
.50
124
.48
119
.41
102
9000
4245
−−− −−− −−− −−− −−− −−−
.79
196
.67
167
.58
144
.55
137
.47
9500
4485
−−− −−− −−− −−− −−− −−−
.89
221
.75
186
.65
162
.62
154
10,000 4720
− − − − − − − − − − − − − − − − − − 1.00 249
.84
209
.73
182
.70
10,500 4955
− − − − − − − − − − − − − − − − − − 1.10 273
.92
229
.80
199
11,000 5190
− − − − − − − − − − − − − − − − − − 1.21 301 1.01 251
.88
−−− −−− −−− −−− −−− −−−
.88
.36
.42
.49
.51
90
104
122
127
.31
.36
.41
.46
77
90
102
114
.27
.31
.36
.41
67
77
90
102
−−− −−− −−− −−− −−− −−−
−−− −−− −−− −−− −−− −−− −−− −−−
−−− −−− −−− −−− −−− −−−
.37
92
.31
77
.25
62
219 − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − − −
.34
.40
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 43
BLOWER DATA
POWER EXHAUST FANS
50% HIGH STATIC OPERATION
BOLD INDICATES FIELD FURNISHED DRIVE
Air
Volume
f
cfm
(L/s)
Return Duct Negative Static Pressure − Inches Water Gauge (Pa)
0 (0)
RPM
.10 (25)
BHP RPM
(kW)
.20 (50)
BHP RPM
(kW)
.30 (75)
BHP RPM
(kW)
.40 (100)
BHP RPM
(kW)
.50 (125)
BHP RPM
(kW)
.60 (150)
BHP RPM
(kW)
.70 (175)
BHP RPM
(kW)
.80 (200)
BHP RPM
(kW)
.90 (225)
BHP RPM
(kW)
1.0 (250)
BHP RPM
(kW)
BHP
(kW)
4000
(1890)
335
0.30 380
(0.22)
0.35 430
(0.26)
0.40 475
(0.30)
0.45 520
(0.34)
0.50 570
(0.37)
0.55 615
(0.41)
0.65 665
(0.48)
0.70 710
(0.52)
0.75 755
(0.56)
0.85
(0.63)
4500
(2125)
375
0.40 415
(0.30)
0.45 460
(0.34)
0.55 500
(0.41)
0.60 545
(0.45)
0.65 585
(0.48)
0.70 625
(0.52)
0.80 670
(0.60)
0.85 710
(0.63)
0.95 750
(0.71)
1.00 795
(0.75)
1.10
(0.82)
5000
(2360)
415
0.55 455
(0.41)
0.65 490
(0.48)
0.70 530
(0.52)
0.75 570
(0.56)
0.85 605
(0.63)
0.90 645
(0.67)
1.00 680
(0.75)
1.05 720
(0.78)
1.15 755
(0.86)
1.20 795
(0.90)
1.30
(0.97)
5500
(2595)
460
0.75 495
(0.56)
0.85 525
(0.63)
0.90 560
(0.67)
0.95 595
(0.71)
1.05 630
(0.78)
1.10 665
(0.82)
1.20 700
(0.90)
1.30 735
(0.97)
1.35 765
(1.01)
1.45 800
(1.08)
1.55
(1.16)
6000
(2830)
500
1.00 530
(0.75)
1.05 565
(0.78)
1.15 595
(0.86)
1.20 625
(0.90)
1.30 660
(0.97)
1.40 690
(1.04)
1.45 720
(1.08)
1.55 750
(1.16)
1.65 785
(1.23)
1.70 815
(1.27)
1.80
(1.34)
6500
(3065)
540
1.25 570
(0.93)
1.30 600
(0.97)
1.40 630
(1.04)
1.50 660
(1.12)
1.60 685
(1.19)
1.65 715
(1.23)
1.75 745
(1.31)
1.85 775
(1.38)
1.95 805
(1.45)
2.05 830
(1.53)
2.10
(1.57)
7000
(3305)
585
1.55 610
(1.16)
1.65 635
(1.23)
1.70 665
(1.27)
1.85 690
(1.38)
1.90 720
(1.42)
2.00 745
(1.49)
2.10 770
(1.57)
2.20 800
(1.64)
2.30 825
(1.72)
2.40 855
(1.79)
2.50
(1.87)
7500
(3540)
625
1.90 650
(1.42)
2.00 675
(1.49)
2.10 700
(1.57)
2.20 725
(1.64)
2.30 750
(1.72)
2.40 775
(1.79)
2.50 800
(1.87)
2.60 825
(1.94)
2.70 850
(2.01)
2.80 875
(2.09)
2.90
(2.16)
8000
(3775)
665
2.30 690
(1.72)
2.40 715
(1.79)
2.55 735
(1.90)
2.60 760
(1.94)
2.70 785
(2.01)
2.85 810
(2.13)
2.95 830
(2.20)
3.05 855
(2.28)
3.15 880
(2.35)
3.25 905
(2.42)
3.40
(2.54)
8500
(4010)
710
2.80 730
(2.09)
2.90 755
(2.16)
3.00 775
(2.24)
3.10 795
(2.31)
3.20 820
(2.39)
3.35 840
(2.50)
3.45 865
(2.57)
3.55 885
(2.65)
3.65 910
(2.72)
3.80 930
(2.83)
3.90
(2.91)
−−−
POWER EXHAUST FANS
100% HIGH STATIC OPERATION
BOLD INDICATES FIELD FURNISHED DRIVE
Air
Volume
cfm
f
(L/s)
8500
(4010)
9000
(4245)
9500
(4485)
10,000
(4720)
10,500
(4955)
11,000
(5190)
11,500
(5425)
12,000
(5665)
12,500
(5900)
13,000
(6135)
13,500
(6370)
14,000
(6605)
Return Duct Negative Static Pressure − Inches Water Gauge (Pa)
0 (0)
RPM
.10 (25)
BHP RPM
(kW)
.20 (50)
BHP RPM
(kW)
.30 (75)
BHP RPM
(kW)
.40 (100)
BHP RPM
(kW)
.50 (125)
BHP RPM
(kW)
.60 (150)
BHP RPM
(kW)
.70 (175)
BHP RPM
(kW)
.80 (200)
BHP RPM
(kW)
.90 (225)
BHP RPM
(kW)
1.0 (250)
BHP RPM
(kW)
BHP
(kW)
475
1.30 500
(0.97)
1.30 525
(0.97)
1.40 550
(1.04)
1.50 585
(1.12)
1.60 625
(1.19)
1.75 670
(1.31)
1.90 710
(1.42)
2.10 745
(1.57)
2.30 780
(1.72)
2.50 815
(1.87)
2.70
(2.01)
520
1.55 535
(1.16)
1.60 550
(1.19)
1.65 570
(1.23)
1.70 605
(1.27)
1.85 640
(1.38)
1.95 685
(1.45)
2.15 720
(1.60)
2.35 760
(1.75)
2.55 790
(1.90)
2.75 825
(2.05)
3.00
(2.24)
550
1.80 560
(1.34)
1.85 575
(1.38)
1.90 600
(1.42)
2.00 620
(1.49)
2.10 655
(1.57)
2.20 695
(1.64)
2.40 735
(1.79)
2.60 770
(1.94)
2.80 800
(2.09)
3.00 835
(2.24)
3.25
(2.42)
575
2.10 590
(1.57)
2.15 605
(1.60)
2.20 620
(1.64)
2.30 645
(1.72)
2.40 675
(1.79)
2.50 710
(1.87)
2.65 745
(1.98)
2.85 780
(2.13)
3.05 815
(2.28)
3.30 845
(2.46)
3.50
(2.61)
605
2.45 615
(1.83)
2.45 625
(1.83)
2.50 645
(1.87)
2.60 670
(1.94)
2.75 690
(2.05)
2.80 725
(2.09)
3.00 755
(2.24)
3.15 790
(2.35)
3.35 825
(2.50)
3.60 855
(2.69)
3.80
(2.83)
630
2.80 645
(2.09)
2.85 660
(2.13)
2.95 675
(2.20)
3.00 685
(2.24)
3.05 715
(2.28)
3.20 740
(2.39)
3.30 770
(2.46)
3.50 805
(2.61)
3.70 835
(2.76)
3.90 870
(2.91)
4.20
(3.13)
665
3.25 675
(2.42)
3.30 680
(2.46)
3.30 695
(2.46)
3.40 715
(2.54)
3.50 735
(2.61)
3.60 755
(2.69)
3.70 785
(2.76)
3.85 815
(2.87)
4.05 850
(3.02)
4.30 880
(3.21)
4.50
(3.36)
685
3.60 700
(2.69)
3.70 710
(2.76)
3.75 725
(2.80)
3.85 740
(2.87)
3.95 755
(2.95)
4.00 780
(2.98)
4.15 805
(3.10)
4.30 830
(3.21)
4.45 860
(3.32)
4.65 890
(3.47)
4.90
(3.66)
720
4.10 730
(3.06)
4.20 740
(3.13)
4.25 750
(3.17)
4.30 765
(3.21)
4.40 780
(3.28)
4.50 800
(3.36)
4.60 820
(3.43)
4.75 845
(3.54)
4.90 875
(3.66)
5.10 905
(3.80)
5.35
(3.99)
745
4.60 750
(3.43)
4.65 765
(3.47)
4.75 780
(3.54)
4.85 790
(3.62)
4.90 805
(3.66)
5.00 820
(3.73)
5.10 840
(3.80)
5.25 865
(3.92)
5.40 890
(4.03)
5.60 915
(4.18)
5.80
(4.33)
775
5.15 785
(3.84)
5.25 795
(3.92)
5.35 805
(3.99)
5.40 815
(4.03)
5.50 830
(4.10)
5.60 845
(4.18)
5.70 865
(4.25)
5.80 880
(4.33)
5.95 905
(4.44)
6.10 930
(4.55)
6.30
(4.70)
805
5.80 810
(4.33)
5.80 820
(4.33)
5.90 830
(4.40)
6.00 845
(4.48)
6.10 855
(4.55)
6.20 870
(4.63)
6.30 885
(4.70)
6.40 905
(4.77)
6.55 925
(4.89)
6.70 945
(5.00)
6.85
(5.11)
HIGH STATIC POWER EXHAUST FANS WITH CONSTANT AIR VOLUME − DRIVE KIT SPECIFICATIONS
Unit Model No.
248H,, 300H,, and 360H
Power Exhaust Fan
Model No.
LAPEB30/36A (50%)
LAPEB30/36B (50%)
LAPEB30/36C (50%)
LAPEB30/36D (100%)
LAPEB30/36E (100%)
LAPEB30/36F (100%)
Motor HP
Drive Kit Number
(2) 2 hp
(2) 2 hp
(2) 2 hp
(3) 2 hp
(3) 2 hp
(3) 2 hp
1
2
3
1
2
3
NOTE − Using total air volume and system static pressure requirements, determine from blower performance tables rpm and required.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 44
RPM Range
406 − 533
531 − 731
731 − 932
406 − 533
531 − 731
731 − 932
BLOWER DATA
POWER EXHAUST FANS
STANDARD STATIC OPERATION
156H, 180, 210, 240, and 300S
Return Duct
Air Volume
Negative Static Pressure
in. w.g.
Pa
cfm
L/s
248H, 300H, and 360H
Return Duct
Air Volume
Negative Static Pressure
in. w.g.
Pa
cfm
L/s
0
0
8630
4070
0
0
12,800
6040
0.05
12
8210
3875
0.05
12
12,200
5760
0.10
25
7725
3645
0.10
25
11,500
5430
0.15
37
7110
3355
0.15
37
10,800
5100
0.20
50
6470
3055
0.20
50
9900
4670
0.25
62
5790
2730
0.25
62
9000
4250
0.30
75
5060
2390
0.30
75
7900
3730
0.35
87
4300
2030
0.35
87
6750
3190
0.40
100
3510
1655
0.40
100
5450
2570
0.45
112
2690
1270
0.45
112
4150
1960
0.50
125
1840
870
0.50
125
2900
1370
Model
No.
Air Volume
CEILING DIFFUSER AIR THROW DATA
1
Model
No.
Air Volume
cfm
156H
180
210
240
300S
1
L/s
Step-Down
ft.
1
Effective Throw Range
m
Flush
ft.
cfm
m
Diffuser Model
5600
2645
5800
2740
6000
2830
6200
2925
6400
3020
6600
3115
RTD11−185
39 − 49 12 − 15
42 − 51 13 − 16
44 − 54 13 − 17
45 − 55 14 − 17
46 − 55 14 − 17
57 − 56 14 − 17
FD11−185
28 − 37
9 − 11
29 − 38
9 − 12
40 − 50 12 − 15
42 − 51 13 − 16
53 − 52 13 − 16
45 − 56 14 − 17
Diffuser Model
7200
3400
7400
3490
7600
3585
7800
3680
3775
8000
8200
3870
8400
3965
8600
4060
8800
4155
RTD11−275
33 − 38 10 − 12
35 − 40 11 − 12
36 − 41 11 − 13
38 − 43 11 − 13
39 − 44 12 − 13
41 − 46 12 − 14
43 − 49 13 − 15
44 − 50 13 − 15
47 − 55 14 − 17
FD11−275
26 − 35
8 − 11
28 − 37
9 − 11
29 − 38
9 − 12
40 − 50 12 − 15
42 − 51 13 − 16
43 − 52 13 − 16
44 − 54 13 − 17
46 − 57 14 − 17
48 − 59 15 − 18
Throw is the horizontal or vertical distance an airstream travels on leaving the
outletor diffuser before the maximum velocity is reduced to 50 ft. (15 m) per
minute. Four sides open.
L/s
Diffuser Model
248H
300H
360H
Effective Throw Range
Step-Down
ft.
m
LARTD30/36
Flush
ft.
m
LAFD30/36
9000
4245
40 − 47
12 − 14
29 − 35
8 − 11
9500
4485
43 − 50
13 − 15
33 − 41
10 − 12
10,000
4720
46 − 54
14 − 16
37 − 46
11 − 14
10,500
4955
50 − 58
15 − 18
42 − 51
13 − 15
11,000
4190
53 − 61
16 − 19
46 − 56
14 − 17
11,500
5425
55 − 64
17 − 20
50 − 61
15 − 19
12,000
5665
58 − 67
18 − 20
54 − 66
16 − 20
12,500
5900
61 − 71
19 − 22
58 − 71
18 − 22
13,000
6135
64 − 74
20 − 23
62 − 75
19 − 23
13,500
6370
67 − 77
20 − 23
66 − 79
20 − 24
1
Throw is the horizontal or vertical distance an airstream travels on leaving the
outletor diffuser before the maximum velocity is reduced to 50 ft. (15 m) per
minute. Four sides open.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 45
OPTIONAL DISCONNECT SWITCH REQUIREMENTS
Model No
No.
156H
180
210
240
248
300
360
Voltage
Blower Motor hp
208/230v−3ph
208/230v−3ph
460v−3ph
575v−3ph
208/230v−3ph
460v−3ph
575v−3ph
208/230v−3ph
460v−3ph
575v−3ph
208/230v−3ph
460v−3ph
575v−3ph
2, 3
5
2, 3, 5
2, 3, 5
3, 5, 7.5
3, 5, 7.5
3, 5, 7.5
5, 7.5, 10
5, 7.5, 10
5, 7.5, 10
5, 7.5, 10
5, 7.5, 10
5, 7.5, 10
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 46
Disconnect Switch
80A
30M39
−−−
30M39
30M39
−−−
30M39
30M39
−−−
30M39
30M39
−−−
30M39
30M39
150A
−−−
30M40
−−−
−−−
30M40
−−−
−−−
30M40
−−−
−−−
−−−
−−−
−−−
250A
−−−
−−−
−−−
−−−
−−−
−−−
−−−
−−−
−−−
−−−
30M41
−−−
−−−
ELECTRICAL DATA
13 TON HIGH EFFICIENCY
ModelNo.
Linevoltagedata−60Hz−3phase
Rated load amps each (total)
Compressors
p
((3))
Locked rotor amps each (total)
Fullloadamps each(total)
Condenser
F M t
(4)
FanMotors
Lockedrotoramps each(total)
Motor Output − hp
Evaporator
p
Bl
Blower
M
Motor
t
kW
Fullloadamps
Lockedrotoramps
1 Maximum Overcurrent
With Standard PEF
P t ti ((amps))
Protection
No PEF
2 Minimum Circuit
With Standard PEF
A
Ampacity
it
No PEF
(Number)Horsepower (W)
Optional
p
Standard
St ti Power
Static
P
Fullloadamps(total)
Exhaust Fans
Lockedrotoramps(total)
Service Outlet (2) 115 volt GFCI (amp rating)
208/230V
14.7 (44.1)
91 (273)
2.4 (9.6)
4.7 (18.8)
2
3
5
2.2
3.7
1.5
7.5
10.6
16.7
46.9
66
105
80
80
90
80
90
70
70
73
79
65
68
75
(2) 1/3 (249)
4.8
9.4
15
LGC156H2B (R−22)
460V
7.1 (21.3)
50 (150)
1.3 (5.2)
2.4 (9.6)
2
3
5
1.5
2.2
3.7
3.4
4.8
7.6
20.4
26.8
45.6
40
40
45
35
40
40
35
36
39
32
34
36
(2) 1/3 (249)
2.6
4.8
15
575V
5.1 (15.3)
37 (111)
1 (4)
1.9 (7.6)
2
3
5
1.5
2.2
3.7
2.7
3.9
6.1
16.2
23.4
36.6
30
30
35
25
25
30
26
27
29
24
25
27
(2) 1/3 (249)
2
3.8
15
208/230V
15.4 (46.2)
124 (372)
2.4 (9.6)
4.7 (18.8)
3
5
7.5
3.7
5.6
2.2
10.6
16.7
24.2
66
105
152
90
90
110
90
110
80
76
82
89
77
84
71
(2) 1/3 (249)
4.8
9.4
15
LGC180S2B (R−22)
460V
7.4 (22.2)
59.6 (178.8)
1.3 (5.2)
2.4 (9.6)
3
5
7.5
2.2
3.7
5.6
4.8
7.6
11
26.8
45.6
66
40
45
50
40
40
50
37
40
43
35
37
41
(2) 1/3 (249)
2.6
4.8
15
575V
5.9 (17.7)
49.4 (148.2)
1 (4)
1.9 (7.6)
3
5
2.2
3.7
3.9
6.1
23.4
36.6
35
35
30
35
30
32
28
30
(2) 1/3 (249)
2
3.8
15
15 TON STANDARD EFFICIENCY
ModelNo.
Linevoltagedata−60Hz−3phase
Rated load amps each (total)
Compressors
p
((3))
Locked rotor amps each (total)
Fullloadamps each(total)
Condenser
F M t
(4)
FanMotors
Lockedrotoramps each(total)
Motor Output − hp
Evaporator
p
Bl
Blower
M
Motor
t
kW
Fullloadamps
Lockedrotoramps
1 Maximum Overcurrent
With Standard PEF
P t ti ((amps))
Protection
No PEF
2 Minimum Circuit
With Standard PEF
A
Ampacity
it
No PEF
(Number)Horsepower (W)
Optional
p
Standard
St ti Power
Static
P
Fullloadamps(total)
Exhaust Fans
Lockedrotoramps(total)
Service Outlet (2) 115 volt GFCI (amp rating)
7.5
5.6
9
54
40
40
35
33
15 TON HIGH EFFICIENCY
ModelNo.
LGC180H2B (R−22)
Linevoltagedata−60Hz−3phase
208/230V
460V
575V
Rated load amps each (total) 17.3 (51.9)
9 (27)
7.1 (21.3)
Compressors
p
((3))
Locked rotor amps each (total) 123 (369)
62 (186)
50 (150)
Fullloadamps each(total)
2.4 (9.6)
1.3 (5.2)
1 (4)
Condenser
F M t
FanMotors
(4)
2.4 (9.6)
1.9 (7.6)
Lockedrotoramps each(total) 4.7 (18.8)
Motor Output − hp 3
5 7.5 3
5 7.5 3
5 7.5
Evaporator
p
Bl
M
t
Blower
Motor
kW 2.2 3.7 5.6 2.2 3.7 5.6 2.2 3.7 5.6
Fullloadamps 10.6 16.7 24.2 4.8 7.6 11 3.9 6.1 9
Lockedrotoramps 66 105 152 26.8 45.6 66 23.4 36.6 54
1 Maximum Overcurrent
With Standard PEF 90 100 110 50 50 50 40 40 45
P t ti ((amps))
Protection
No PEF 90 90 110 45 50 50 35 40 45
2 Minimum Circuit
With Standard PEF 82 88 95 42 45 49 33 36 39
A
it
Ampacity
No PEF 77 83 91 40 43 46 31 34 37
(Number)Horsepower (W) (2) 1/3 (249)
(2) 1/3 (249)
(2) 1/3 (249)
Optional
p
Standard
St ti Power
Static
P
Fullloadamps(total)
4.8
2.6
2
Exhaust Fans
Lockedrotoramps(total)
9.4
4.8
3.8
Service Outlet (2) 115 volt GFCI (amp rating)
15
15
15
LGC180H4B (R−410A)
208/230V
460V
575V
20.5 (61.5)
9.6 (28.8)
7.6 (22.8)
155 (465)
75 (225)
54 (162)
2.4 (9.6)
1.3 (5.2)
1 (4)
4.7 (18.8)
2.4 (9.6)
1.9 (7.6)
3
5 7.5 3
5 7.5 3
5 7.5
2.2 3.7 5.6 2.2 3.7 5.6 2.2 3.7 5.6
10.6 16.7 24.2 4.8 7.6 11 3.9 6.1 9
66 105 152 26.8 45.6 66 23.4 36.6 54
110 110 125 50 50 60 40 40 45
110 110 125 50 50 50 40 40 45
92 98 106 44 47 50 35 37 40
87 93 101 42 44 48 33 35 38
(2) 1/3 (249)
(2) 1/3 (249)
(2) 1/3 (249)
4.8
2.6
2
9.4
4.8
3.8
15
15
15
NOTE− Extremesofoperatingrangeareplusandminus10%oflinevoltage.
1 HACR type breaker or fuse.
2 RefertoNational or CanadianElectricalCodemanualtodeterminewire,fuseanddisconnectsizerequirements.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 47
ELECTRICAL DATA
17.5 TON STANDARD / HIGH EFFICIENCY
ModelNo.
LGC210S2B (R−22)
LGC210H2B (R−22)
Linevoltagedata−60Hz−3phase
208/230V
460V
575V
208/230V
460V
575V
Rated load amps each (total) 14.7 (58.8)
7.1 (28.4)
5.8 (23.2)
14.7 (58.8)
7.1 (28.4)
5.1 (20.4)
Compressors
p
((4))
Locked rotor amps each (total)
91 (364)
50 (200)
37 (148)
91 (364)
50 (200)
37 (148)
Fullloadamps each (total)
2.4 (9.6)
1.3 (5.2)
1 (4)
2.4 (9.6)
1.3 (5.2)
1 (4)
Condenser
F M t
(4)
FanMotors
2.4 (9.6)
1.9 (7.6)
4.7 (18.8)
2.4 (9.6)
1.9 (7.6)
Lockedrotoramps each (total) 4.7 (18.8)
Motor Output − hp 3
5 7.5 3
5 7.5 3
5 7.5 3
5 7.5 3
5 7.5 3
5 7.5
Evaporator
p
Bl
Blower
M
Motor
t
kW 2.2 3.7 5.6 2.2 3.7 5.6 2.2 3.7 5.6 2.2 3.7 5.6 2.2 3.7 5.6 2.2 3.7 5.6
Fullloadamps 10.6 16.7 24.2 4.8 7.6 11 3.9 6.1 9 10.6 16.7 24.2 4.8 7.6 11 3.9 6.1 9
Lockedrotoramps 66 105 152 26.8 45.6 66 23.4 36.6 54 66 105 152 26.8 45.6 66 23.4 36.6 54
1 Maximum Overcurrent
With Standard PEF 100 110 125 45 50 60 40 40 45 100 110 125 45 50 60 35 40 45
P t ti (amps)
(
)
Protection
No PEF 90 100 110 45 50 50 35 40 45 90 100 110 45 50 50 30 35 40
2 Minimum Circuit
With Standard PEF 88 94 102 43 46 49 35 37 40 88 94 102 43 46 49 32 34 37
A
Ampacity
it
No PEF 83 89 97 41 43 47 33 35 38 83 89 97 41 43 47 30 32 35
(No.)Horsepower (W) (2) 1/3 (249)
(2) 1/3 (249)
(2) 1/3 (249)
(2) 1/3 (249)
(2) 1/3 (249)
(2) 1/3 (249)
Optional
p
Standard
St ti Power
Static
P
Fullloadamps(total)
4.8
2.6
2
4.8
2.6
2
Exhaust Fans
Lockedrotoramps(total)
9.4
4.8
3.8
9.4
4.8
3.8
Service Outlet (2) 115 volt GFCI (amp rating)
15
15
15
15
15
15
20 TON STANDARD EFFICIENCY
ModelNo.
Linevoltagedata−60Hz−3phase
Rated load amps each (total)
Compressors
p
((4))
Locked rotor amps each (total)
Fullloadamps(total)
Condenser
F M t
(4)
FanMotors
Lockedrotoramps(total)
Motor Output − hp
Evaporator
p
Bl
Blower
M
Motor
t
kW
Fullloadamps
Lockedrotoramps
1 Maximum Overcurrent
With Standard PEF
P t ti (amps)
(
)
Protection
No PEF
2 Minimum Circuit
With Standard PEF
A
Ampacity
it
No PEF
(No.)Horsepower (W)
Optional
p
Standard
St ti Power
Static
P
Fullloadamps(total)
Exhaust Fans
Lockedrotoramps(total)
Service Outlet (2) 115 volt GFCI (amp rating)
208/230V
15.4 (61.6)
124 (469)
2.4 (9.6)
4.7 (18.8)
5
7.5
10
5.6
7.5
3.7
16.7
24.2
30.8
105
152
193
110
125
125
125
125
100
97
105
111
100
106
92
(2) 1/3 (249)
4.8
9.4
15
LGC240S2B (R−22)
460V
7.4 (29.6)
59.6 (238.4)
1.3 (5.2)
2.4 (9.6)
5
7.5
10
3.7
5.6
7.5
7.6
11
14
45.6
66
84
50
60
60
50
50
60
47
51
54
45
48
51
(2) 1/3 (249)
2.6
4.8
15
575V
5.9 (23.6)
49.4 (197.6)
1 (4)
1.9 (7.6)
5
7.5
3.7
5.6
6.1
9
36.6
54
40
45
40
45
38
41
36
39
(2) 1/3 (249)
2
3.8
15
10
7.5
11
66
50
50
43
41
20 TON HIGH EFFICIENCY
ModelNo.
Linevoltagedata−60Hz−3phase
Rated load amps each (total)
Compressors
p
((4))
Locked rotor amps each (total)
Fullloadamps(total)
Condenser
F M t
(4)
FanMotors
Lockedrotoramps(total)
Motor Output − hp
Evaporator
p
Bl
Blower
M
Motor
t
kW
Fullloadamps
Lockedrotoramps
1 Maximum Overcurrent
With Standard PEF
P t ti (amps)
(
)
Protection
No PEF
2 Minimum Circuit
With Standard PEF
A
Ampacity
it
No PEF
(No.)Horsepower (W)
Optional
p
Standard
St ti Power
Static
P
Fullloadamps(total)
Exhaust Fans
Lockedrotoramps(total)
Service Outlet (2) 115 volt GFCI (amp rating)
LGA240H2B (R−22)
208/230V
460V
575V
17.3 (69.2)
9 (36)
7.1 (28.4)
123 (492)
62 (248)
50 (200)
2.4 (9.6)
1.3 (5.2)
1 (4)
2.4 (9.6)
1.9 (7.6)
4.7 (18.8)
5 7.5 10 5 7.5 10 5 7.5 10
3.7 5.6 7.5 3.7 5.6 7.5 3.7 5.6 7.5
16.7 24.2 30.8 7.6 11 14 6.1 9 11
105 152 193 45.6 66 84 36.6 54 66
110 125 150 60 60 70 45 50 50
110 125 125 60 60 70 45 50 50
105 113 119 54 58 61 43 46 48
100 108 114 52 55 58 41 44 46
(2) 1/3 (249)
(2) 1/3 (249)
(2) 1/3 (249)
4.8
2.6
2
9.4
4.8
3.8
15
15
15
NOTE− Extremesofoperatingrangeareplusandminus10%oflinevoltage.
1 HACR type breaker or fuse.
2 RefertoNational or CanadianElectricalCodemanualtodeterminewire,fuseanddisconnectsizerequirements.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 48
LGA240H4B (R−410A)
208/230V
460V
575V
20.5 (82)
9.6 (38.4)
7.6 (30.4)
155 (620)
75 (300)
54 (216)
2.4 (9.6)
1.3 (5.2)
1 (4)
4.7 (18.8)
2.4 (9.6)
1.9 (7.6)
5 7.5 10 5 7.5 10 5 7.5 10
3.7 5.6 7.5 3.7 5.6 7.5 3.7 5.6 7.5
16.7 24.2 30.8 7.6 11 14 6.1 9 11
105 152 193 45.6 66 84 36.6 54 66
125 150 150 60 70 70 50 50 60
125 125 150 60 60 70 50 50 50
119 126 133 57 60 63 45 48 50
114 121 128 54 57 60 43 46 48
(2) 1/3 (249)
(2) 1/3 (249)
(2) 1/3 (249)
4.8
2.6
2
9.4
4.8
3.8
15
15
15
ELECTRICAL DATA
21 TON HIGH EFFICIENCY
ModelNo.
Linevoltagedata−60Hz−3phase
Rated load amps each (total)
Compressors
p
((4))
Locked rotor amps each (total)
Fullloadamps(total)
Condenser
F M t
FanMotors
(6)
Lockedrotoramps(total)
Motor Output − hp
Evaporator
p
Bl
M
t
Blower
Motor
kW
Fullloadamps
Lockedrotoramps
1 Maximum Overcurrent
With Standard PEF
P t ti (amps)
(
)
Protection
With 50% High Static PEF
With 100% High Static PEF
No PEF
2 Minimum Circuit
With Standard PEF
A
Ampacity
it
With 50% High Static PEF
With 100% High Static PEF
No PEF
(No.)Horsepower (W)
Optional
p
St d d St
Standard
Static
ti
Fullloadamps(total)
Power Exhaust Fans
Lockedrotoramps(total)
(No.)Horsepower (W)
Optional
p
50% Hi
High
h St
Static
ti
Fullloadamps(total)
Power Exhaust Fans
Lockedrotoramps(total)
(No.)Horsepower (W)
Optional
p
100% Hi
High
h St
Static
ti
Fullloadamps(total)
Power Exhaust Fans
Lockedrotoramps(total)
Service Outlet (2) 115 volt GFCI (amp rating)
LGA248H2B (R−22)
208/230V
460V
575V
17.3 (69.2)
9 (36)
7.1 (28.4)
123 (492)
62 (248)
50 (200)
2.4 (14.4)
1.3 (7.8)
1 (6)
2.4 (14.4)
1.9 (11.4)
4.7 (28.2)
5 7.5 10 5 7.5 10 5 7.5 10
3.7 5.6 7.5 3.7 5.6 7.5 3.7 5.6 7.5
16.7 24.2 30.8 7.6 11 14 6.1 9 11
105 152 193 45.6 66 84 36.6 54 66
125 125 150 60 70 70 50 50 60
125 150 150 70 70 80 50 60 60
150 150 175 70 70 80 60 60 60
110 125 150 60 60 70 45 50 50
112 120 126 58 61 64 46 49 51
120 128 134 61 64 67 48 51 53
128 135 142 64 68 71 51 54 56
105 113 119 54 58 61 43 46 48
(3) 1/3 (249)
(3) 1/3 (249)
(3) 1/3 (249)
7.2
3.9
3
14.1
7.2
5.7
(2) 2 (1491)
(2) 2 (1491)
(2) 2 (1491)
7.5 (15)
3.4 (6.8)
2.7 (5.4)
69.4 (138.8)
31.4 (62.8)
20.1 (40.2)
(3) 2 (1491)
(3) 2 (1491)
(3) 2 (1491)
7.5 (22.5)
3.4 (10.2)
2.7 (8.1)
69.4 (208.2)
31.4 (94.2)
20.1 (60.3)
15
15
15
LGA248H4B (R−410A)
208/230V
460V
575V
18.1 (72.4)
9 (36)
6.8 (27.2)
137 (548)
62 (248)
50 (200)
2.4 (14.4)
1.3 (7.8)
1 (6)
4.7 (28.2)
2.4 (14.4)
1.9 (11.4)
5 7.5 10 5 7.5 10 5 7.5 10
3.7 5.6 7.5 3.7 5.6 7.5 3.7 5.6 7.5
16.7 24.2 30.8 7.6 11 14 6.1 9 11
105 152 193 45.6 66 84 36.6 54 66
125 125 150 60 70 70 50 50 60
125 150 150 70 70 80 50 50 60
150 150 175 70 70 80 50 60 60
125 125 150 60 60 70 45 50 50
116 123 130 58 61 64 44 47 49
124 131 138 61 64 67 47 50 52
131 139 145 64 68 71 50 52 54
109 116 123 54 58 61 41 44 46
(3) 1/3 (249)
(3) 1/3 (249)
(3) 1/3 (249)
7.2
3.9
3
14.1
7.2
5.7
(2) 2 (1491)
(2) 2 (1491)
(2) 2 (1491)
7.5 (15)
3.4 (6.8)
2.7 (5.4)
69.4 (138.8)
31.4 (62.8)
20.1 (40.2)
(3) 2 (1491)
(3) 2 (1491)
(3) 2 (1491)
7.5 (22.5)
3.4 (10.2)
2.7 (8.1)
69.4 (208.2)
31.4 (94.2)
20.1 (60.3)
15
15
15
25 TON STANDARD EFFICIENCY
ModelNo.
Linevoltagedata−60Hz−3phase
Rated load amps each (total)
Compressors
p
((4))
Locked rotor amps each (total)
Fullloadamps each(total)
Condenser
F M t
FanMotors
(4)
Lockedrotoramps each(total)
Motor Output − hp
Evaporator
p
Bl
Blower
M
Motor
t
kW
Fullloadamps
Lockedrotoramps
1 Maximum Overcurrent
With Standard PEF
P t ti (amps)
Protection
(
)
No PEF
2 Minimum Circuit
With Standard PEF
A
Ampacity
it
No PEF
(No.)Horsepower (W)
Optional
Standard
p
St ti Power
P
Static
Fullloadamps(total)
Exhaust Fans
Lockedrotoramps(total)
Service Outlet (2) 115 volt GFCI (amp rating)
208/230V
18.6 (74.4)
156 (624)
3 (12)
6 (24)
5
7.5
10
5.6
7.5
3.7
16.7
24.2
30.8
105
152
193
125
125
150
125
150
125
113
121
127
116
122
108
(2) 1/3 (249)
4.8
9.4
15
LGC300S2B (R−22)
460V
9 (36)
75 (300)
1.5 (6)
3 (12)
5
7.5
10
3.7
5.6
7.5
7.6
11
14
45.6
66
84
60
60
70
60
60
70
55
58
61
52
56
59
(2) 1/3 (249)
2.6
4.8
15
575V
7.4 (29.6)
54 (216)
1.2 (4.8)
2.9 (11.6)
5
7.5
3.7
5.6
6.1
9
36.6
54
50
50
45
50
45
48
43
46
(2) 1/3 (249)
2
3.8
15
10
7.5
11
66
60
50
50
48
NOTE− Extremesofoperatingrangeareplusandminus10%oflinevoltage.
1 HACR type breaker or fuse.
2 RefertoNational or CanadianElectricalCodemanualtodeterminewire,fuseanddisconnectsizerequirements.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 49
ELECTRICAL DATA
25 TON HIGH EFFICIENCY
ModelNo.
Linevoltagedata−60Hz−3phase
Rated load amps each (total)
Compressors
p
((4))
Locked rotor amps each (total)
Fullloadamps each(total)
Condenser
F M t
(6)
FanMotors
Lockedrotoramps each(total)
Motor Output − hp
Evaporator
p
Bl
Blower
M
Motor
t
kW
Fullloadamps
Lockedrotoramps
1 Maximum Overcurrent
With Standard PEF
P t ti (amps)
(
)
Protection
With 50% High Static PEF
With 100% High Static PEF
No PEF
2 Minimum Circuit
With Standard PEF
A
Ampacity
it
With 50% High Static PEF
With 100% High Static PEF
No PEF
(No.)Horsepower (W)
Optional
p
Standard
St ti Power
Static
P
Fullloadamps(total)
Exhaust Fans
Lockedrotoramps(total)
(No.)Horsepower (W)
Optional
p
50% Hi
High
h St
Static
ti
Fullloadamps(total)
Power Exhaust Fans
Lockedrotoramps(total)
(No.)Horsepower (W)
Optional
p
100% Hi
High
h St
Static
ti
Fullloadamps(total)
Power Exhaust Fans
Lockedrotoramps(total)
Service Outlet (2) 115 volt GFCI (amp rating)
208/230V
18.6 (74.4)
156 (624)
2.4 (14.4)
4.7 (28.2)
5
7.5
10
5.6
7.5
3.7
16.7
24.2
30.8
105
152
193
125
150
150
150
150
150
150
150
175
125
125
150
118
125
132
133
140
126
133
141
147
111
118
125
(3) 1/3 (249)
7.2
14.1
(2) 2 (1491)
7.5 (15)
69.4 (138.8)
(3) 2 (1491)
7.5 (22.5)
69.4 (208.2)
15
LGC300H2B / LGC300H2V (R−22)
460V
9 (36)
75 (300)
1.3 (7.8)
2.4 (14.4)
5
7.5
10
3.7
5.6
7.5
7.6
11
14
45.6
66
84
60
70
70
70
70
80
70
70
80
60
60
70
58
61
64
61
64
67
64
68
71
54
58
61
(3) 1/3 (249)
3.9
7.2
(2) 2 (1491)
3.4 (6.8)
31.4 (62.8)
(3) 2 (1491)
3.4 (10.2)
31.4 (94.2)
15
575V
7.4 (29.6)
54 (216)
1 (6)
1.9 (11.4)
5
7.5
3.7
5.6
6.1
9
36.6
54
50
50
50
60
60
60
50
50
47
50
49
52
52
55
44
47
(3) 1/3 (249)
3
5.7
(2) 2 (1491)
2.7 (5.4)
20.1 (40.2)
(3) 2 (1491)
2.7 (8.1)
20.1 (60.3)
15
10
7.5
11
66
60
60
60
60
52
54
57
49
30 TON HIGH EFFICIENCY
ModelNo.
LGA360H2B (R−22)
Linevoltagedata−60Hz−3phase
208/230V
460V
575V
Rated load amps each (total) 30.1 (90.3)
15.5 (46.5)
12.1 (36.3)
Compressors
p
((3))
Locked rotor amps each (total) 225 (675)
114 (342)
80 (240)
Fullloadamps each(total) 2.4 (14.4)
1.3 (7.8)
1 (6)
Condenser
F M t
FanMotors
(6)
2.4 (14.4)
1.9 (11.4)
Lockedrotoramps each (total) 4.7 (28.2)
Motor Output − hp 5 7.5 10 5 7.5 10 5 7.5 10
Evaporator
p
Bl
M
t
Blower
Motor
kW 3.7 5.6 7.5 3.7 5.6 7.5 3.7 5.6 7.5
Fullloadamps 16.7 24.2 30.8 7.6 11 14 6.1 9 11
Lockedrotoramps 105 152 193 45.6 66 84 36.6 54 66
1 Maximum Overcurrent
With Standard PEF 150 150 175 80 80 90 60 60 70
P t ti (amps)
(
)
Protection
With 50% High Static PEF 150 175 175 80 90 90 60 70 70
With 100% High Static PEF 175 175 175 90 90 90 70 70 70
No PEF 150 150 150 80 80 80 60 60 60
2 Minimum
With Standard PEF 137 144 151 70 74 77 55 58 60
Ci
Circuit
it A
Ampacity
it
With 50% High Static PEF 144 152 159 73 76 79 57 60 62
With 100% High Static PEF 152 159 166 76 80 83 60 63 65
No PEF 129 137 144 66 70 73 52 55 57
(No.)Horsepower (W) (3) 1/3 (249)
(3) 1/3 (249)
(3) 1/3 (249)
Optional
p
Standard
St ti Power
Static
P
Fullloadamps(total)
7.2
3.9
3
Exhaust Fans
Lockedrotoramps(total)
14.1
7.2
5.7
(No.)Horsepower (W) (2) 2 (1491)
(2) 2 (1491)
(2) 2 (1491)
Optional
p
50% Hi
High
h St
Static
ti
Fullloadamps(total)
7.5 (15)
3.4 (6.8)
2.7 (5.4)
Power Exhaust Fans
Lockedrotoramps(total) 69.4 (138.8)
31.4 (62.8)
20.1 (40.2)
(No.)Horsepower (W) (3) 2 (1491)
(3) 2 (1491)
(3) 2 (1491)
Optional
p
100% Hi
High
h St
Static
ti
Fullloadamps(total)
7.5 (22.5)
3.4 (10.2)
2.7 (8.1)
Power Exhaust Fans
Lockedrotoramps(total) 69.4 (208.2)
31.4 (94.2)
20.1 (60.3)
Service Outlet (2) 115 volt GFCI (amp rating)
15
15
15
NOTE− Extremesofoperatingrangeareplusandminus10%oflinevoltage.
1 HACR type breaker or fuse.
2 RefertoNational or CanadianElectricalCodemanualtodeterminewire,fuseanddisconnectsizerequirements.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 50
LGA360H4B (R−410A)
208/230V
460V
575V
33.3 (99.9)
17.9 (53.7)
11.5 (34.5)
239 (717)
125 (375)
80 (240)
2.4 (14.4)
1.3 (7.8)
1 (6)
4.7 (28.2)
2.4 (14.4)
1.9 (11.4)
5 7.5 10 5 7.5 10 5 7.5 10
3.7 5.6 7.5 3.7 5.6 7.5 3.7 5.6 7.5
16.7 24.2 30.8 7.6 11 14 6.1 9 11
105 152 193 45.6 66 84 36.6 54 66
175 175 175 90 90 100 60 60 60
175 175 200 90 100 100 60 60 70
175 200 200 100 100 100 60 70 70
150 175 175 90 90 90 60 60 60
147 155 161 78 81 84 53 56 58
155 162 169 81 84 87 55 58 60
162 170 176 84 88 91 58 61 63
140 147 154 74 77 80 50 53 55
(3) 1/3 (249)
(3) 1/3 (249)
(3) 1/3 (249)
7.2
3.9
3
14.1
7.2
5.7
(2) 2 (1491)
(2) 2 (1491)
(2) 2 (1491)
7.5 (15)
3.4 (6.8)
2.7 (5.4)
69.4 (138.8)
31.4 (62.8)
20.1 (40.2)
(3) 2 (1491)
(3) 2 (1491)
(3) 2 (1491)
7.5 (22.5)
3.4 (10.2)
2.7 (8.1)
69.4 (208.2)
31.4 (94.2)
20.1 (60.3)
15
15
15
ELECTRICAL DATA
30 TON HIGH EFFICIENCY
ModelNo.
Linevoltagedata−60Hz−3phase
Rated load amps each (total)
Compressors
p
((4))
Locked rotor amps each (total)
Fullloadamps each(total)
Condenser
F M t
(6)
FanMotors
Lockedrotoramps each (total)
Motor Output − hp
Evaporator
p
Bl
Blower
M
Motor
t
kW
Fullloadamps
Lockedrotoramps
1 Maximum Overcurrent
With Standard PEF
P t ti (amps)
(
)
Protection
With 50% High Static PEF
With 100% High Static PEF
No PEF
2 Minimum
With Standard PEF
Ci
Circuit
it A
Ampacity
it
With 50% High Static PEF
With 100% High Static PEF
No PEF
(No.)Horsepower (W)
Optional
p
Standard
St ti Power
Static
P
Fullloadamps(total)
Exhaust Fans
Lockedrotoramps(total)
(No.)Horsepower (W)
Optional
p
50% Hi
High
h St
Static
ti
Fullloadamps(total)
Power Exhaust Fans
Lockedrotoramps(total)
(No.)Horsepower (W)
Optional
p
100% Hi
High
h St
Static
ti
Fullloadamps(total)
Power Exhaust Fans
Lockedrotoramps(total)
Service Outlet (2) 115 volt GFCI (amp rating)
208/230V
22.4 (89.6)
164 (656)
2.4 (14.4)
4.7 (28.2)
5
7.5
10
5.6
7.5
3.7
16.7
24.2
30.8
105
152
193
150
150
175
150
175
150
150
175
175
150
150
150
134
141
148
149
156
142
149
157
163
127
134
141
(3) 1/3 (249)
7.2
14.1
(2) 2 (1491)
7.5 (15)
69.4 (138.8)
(3) 2 (1491)
7.5 (22.5)
69.4 (208.2)
15
LGC360H2V (R−22)
460V
10.9 (43.6)
100 (400)
1.3 (7.8)
2.4 (14.4)
5
7.5
10
3.7
5.6
7.5
7.6
11
14
45.6
66
84
70
80
80
70
80
80
80
80
90
70
70
80
66
70
73
69
72
75
72
76
79
62
66
69
(3) 1/3 (249)
3.9
7.2
(2) 2 (1491)
3.4 (6.8)
31.4 (62.8)
(3) 2 (1491)
3.4 (10.2)
31.4 (94.2)
15
575V
8.3 (33.2)
78 (312)
1 (6)
1.9 (11.4)
5
7.5
3.7
5.6
6.1
9
36.6
54
60
60
60
60
60
60
50
60
51
54
53
56
56
59
48
51
(3) 1/3 (249)
3
5.7
(2) 2 (1491)
2.7 (5.4)
20.1 (40.2)
(3) 2 (1491)
2.7 (8.1)
20.1 (60.3)
15
10
7.5
11
66
60
60
70
60
56
58
61
53
NOTE− Extremesofoperatingrangeareplusandminus10%oflinevoltage.
1 HACR type breaker or fuse.
2 RefertoNational or CanadianElectricalCodemanualtodeterminewire,fuseanddisconnectsizerequirements.
OUTDOOR SOUND DATA
Octave Band Sound Power Levels dBa, re 10−12 Watts
*Unit
Model No.
1
Center Frequency − HZ
1 Sound
Rating Number
(dB)
125
250
500
1000
2000
4000
8000
156H, 180S, 180H
97
92
91
88
83
79
72
93
210S, 210H, 240S, 240H
94
91
90
87
83
79
72
92
300S
96
93
90
87
82
76
65
93
248H, 300H
95
93
92
88
84
81
75
94
360H
94
93
93
90
86
81
75
95
Tested according to ARI Standard 270-95 test conditions and ANSI Standard S1.32-1981.
INSTALLATION CLEARANCES − INCHES (MM)
13, 15, 17.5, 20, and 25 TON (156H, 180, 210, 240, and 300S)
OUTDOOR
AIR HOOD
*NOTE − 66 in. (1676 mm)
Recommended service clearance
for blower deck removal
36 (914)
*41
(1041)
NOTE − Top Clearance 60 in. (1524 mm).
NOTE − Entire perimeter of unit base requires
support when elevated above mounting surface.
NOTE − 60 in. (1524 mm) Recommended service clearance
for heat exchanger removal
36
(914)
36 (914)
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 51
INSTALLATION CLEARANCES − INCHES (MM)
21, 25, and 30 TON (248H, 300H, and 360H) − Unit With Economizer
OUTDOOR
AIR HOOD
*NOTE − 66 in. (1676 mm)
Recommended service clearance
for blower deck removal
36
(914)
*41
(1041)
36
(914)
NOTE − Top Clearance 60 in. (1524 mm).
NOTE − Entire perimeter of unit base requires
support when elevated above mounting surface.
36 (914)
NOTE − 60 in. (1524 mm) Recommended service clearance for heat exchanger removal
21, 25, and 30 TON (248H, 300H, and 360H) − Unit With High Static Power Exhaust Fans
80 (2032)
OUTDOOR
AIR HOOD
*NOTE − 66 in. (1676 mm)
Recommended service clearance
for blower deck removal
*41
(1041)
36
(914)
NOTE − Top Clearance 60 in. (1524 mm).
NOTE − Entire perimeter of unit base requires
support when elevated above mounting surface.
36 (914)
NOTE − 60 in. (1524 mm) Recommended service clearance for heat exchanger removal
21, 25, and 30 TON (248H, 300H, and 360H) − Unit With Horizontal Barometric Relief Dampers
OPTIONAL BAROMETRIC
RELIEF EXHAUST
DAMPERS
(Field Installed
on Return Air Duct)
NOTE Allow adequate clearance for duct and
barometric relief damper installation.
NOTE Dampers may be installed on each side
of return air duct or end to end on one side of
return air duct.
OUTDOOR
AIR HOOD
*NOTE − 66 in. (1676 mm)
Recommended service clearance
for blower deck removal
NOTE − Top Clearance 60 in. (1524 mm).
NOTE − Entire perimeter of unit base requires
support when elevated above mounting surface.
NOTE − 60 in. (1524 mm) Recommended service clearance for heat exchanger removal
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 52
*41
(1041)
36
(914)
36 (914)
L CONNECTION® BUILDING AUTOMATION SYSTEM
Network Control Up To 31 Units − Integrates with Integrated Modular Control (IMC) Control on S−Classt and L Series® Packaged Units and
other non−IMC Lennox or Aftermarket Equipment with optional DDC Network Thermostat Controller (NTC) − 7 Day Programming plus Holidays − Six Different Time/Temperature Schedules per Day − Storage of Last 75 Alarms With Time/Date − Remote Access (with PC Software)
− Large LCD Display Screen
NCP1 Network Control Panel
59L21
ZONE TEMPERATURE SENSORS (One sensor required per unit)
Order
No.
Description
Wall−Mount After Hours Override Button − Terminal Block Connection − Network Jack for L Connection PC
Software
Wall Mounted Zone Sensor − With warmer/cooler adjustment
56L80
Wall Mounted Zone Sensor − Without warmer/cooler adjustment
94L60
Miniature Wall−Mount − Terminal Block Connection
Miniature Wall Mounted Zone Sensor
94L61
Wall−Mount − Terminal Block Connection
Wall Mounted Zone Sensor − use with Building Controller (BC1) for monitoring critical areas
59M04
Wall−Mount − Wire Lead Connection
Flush Mount Zone Sensor
76M32
Temperature Averaging Kit
Two zone sensors for temperature averaging in one room
23M20
Duct−Mount (For return air duct)
Duct Mounted Zone Sensor
56L81
Wall Mounted Zone Humidity Sensor
17M50
Duct Mounted Relative Humidity Sensor
76M31
ZONE HUMIDITY SENSOR
OUTDOOR TEMPERATURE SENSOR
Mounted in watertight enclosure with a sun shield. Use with Building Controller (BC1) to monitor outdoor temperature
59M05
CO2 SENSORS
CO2 − Wall mount, white case, digital display
CO2 − Wall mount, white case, no display
CO2 − Wall mount, black case, digital display
CO2 − Wall mount, black case, no display (UL rated for interior duct and plenum mounting)
AFTER HOURS REMOTE OVERRIDE BUTTON
After Hours Remote Override Button − Wall Plate furnished (Use with Duct Mounted Zone Sensor if
required)
77N39
87N53
87N52
87N54
56L16
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 53
L CONNECTION® BUILDING AUTOMATION SYSTEM
Description
Order
No.
NETWORK THERMOSTAT CONTROL − DDC that allows network control of all other non−IMC Lennox or aftermarket equipment over L Connectiont Network
1
Description
Order
No.
NTC1 − 2 Htg.−3 Clg.
17M10
PC SOFTWARE
FOR SETUP, CONFIGURATION AND SCHEDULE ADJUSTMENT OF THE NETWORK CONTROL PANEL (NCP)
Network Control Panel (NCP) Software
For Remote/Local NCP access
96L82
NOTE − Version 2.06 or higher is required for use with M1−7 IMC Controller
Requires PC Converter Kit (96L78) for local access and Network Modem Kit (94L62) for remote access
FOR SETUP, CONFIGURATION AND SERVICING OF INTEGRATED MODULAR CONTROL (IMC), BUILDING
CONTROLLER AND NETWORK THERMOSTAT CONTROL (NTC)
Unit Controller Software
For Remote/Local network control
96L80
NOTE − Version 2.06 or higher is required for use with M1−7 IMC Controller
Requires PC Converter Kit (96L78) for local access and Network Modem Kit (94L62) for remote access
LENNOX COMMERCIAL CONTROLS SELECTION SOFTWARE
Includes L Connection® (and Sectra®) Estimator Software for product selection and submittal information
34M78
NETWORK MODEM KIT − Provides direct digital communication between a single rooftop unit (or network of rooftop units) and the Network Control Panel
Connects phone line directly to L Connection network − Includes modem, PC Converter, cables
94L62
NOTE − Requires either NCP software and/or Unit Controller Software
BUILDING CONTROLLER
BC1−1 − Use to control lights, vent hoods, exhaust fans, sprinklers and other devices based upon unit
occupied operation or time schedule.
17M12
NETWORK ETHERNET CONVERTER − Required to interface between the L Connection network and an Ethernet LAN (local area network).
Includes Ethernet converter, L Connection modem converter, cable, and transformer
76M77
NOTE − Requires L Connection Unit Controller and/or NCP software (version 2.05 or higher)
Does NOT require Network Bus to PC Converter Kit (96L78)
1 Computer system requirements: IBM compatible PC with Pentium or higher processor, Microsoft® Windows® 95, 98, Me, 2000, XP, or NT®. (Windows® 95, Windows® 98,
Windows® Me, Windows® 2000, Windows® XP, and Windows® NT® are registered trademarks of Microsoft Corp.), 256 MB RAM (more memory may be required to run additional
applications simultaneously), requires at least 20 MB of free hard drive space, VGA or higher resolution monitor (screen resolution must be 800 X 600 or higher and 256 colors),
CD−ROM drive, mouse or compatible pointing device, serial COM port, PC modem (US Robotics® model no. USR5699B, USR5610B, USR5686E, 005686−03, 3CP5610A,
3CP5699A, 005687−03, or USR3686D is recommended) for remote connections.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 54
L CONNECTION® BUILDING AUTOMATION SYSTEM
Description
Order
No.
Used with the Building Controller, the monitor sends a 24VAC output to a building control device to load
shed when electrical demand is high.
76M33
kWH DEMAND CONTROLLER
NOTE − Requires kWH meter with KYZ output.
AMBIENT LIGHT SENSOR
Use with the Building Controller and Network Control Panel for automatic lighting control
34M67
NEMA 1 ENCLOSURES
NEMA Enclosure
17M11
For Network Modem Kit or Building Controller
34M23
For Network Control Panel
34M24
NETWORK PHONE LINE AUTO−ROUTER
(Allows modem, fax and phone to share one line − routes signal to connect to device automatically)
Network Phone Line Auto−Router
34M22
NETWORK BUS TO PC CONVERTER KIT
Allows PC connection directly to L Connection® network − Required for any L Connection® PC software when used on a local network
96L78
NOTE − Not required for use with Ethernet Converter Kit (76M77)
COMMUNICATION CABLE
500 ft. Roll − RS−485 twisted pair communication wire − plenum rated
27M19
1
76M76
500 ft. Roll − RS−485 double twisted pair communication wire − plenum rated
1000 ft. Roll − RS−485 twisted pair communication wire − plenum rated
94L63
2500 ft. Roll − RS−485 twisted pair communication wire − plenum rated
68M25
1
Three wires are required for CO2 Sensors or Humidity Sensors.
NETWORK CONTROL PANEL WALL TRANSFORMER − Separate power supply for NCP (if desired)
Screw terminals
Transformer − 20VA, Class 2, Primary 120V, 60Hz, Secondary 24V
18M13
FACTORY INSTALLED COMPONENTS
Air Flow Switch
Dirty Filter Switch
Factory
Installed
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 55
SECTRAt COMMERCIAL ZONING SYSTEM − FACTORY INSTALLED
SECTRA SINGLE ZONE CONTROL
Module monitors and controls heating, cooling and economizer functions of Lennox’ S−Classt and L Series® rooftop equipment
configured for single−zone applications. Up to 50 zoned (bypass or VFD) and single zone (DDC or communicating thermostat) units
can be combined on a single Sectra Commercial Zoning System network (maximum of 120 LonWorks® nodes). Allows 2 stage
heat/3 stage cool demands to operate 1 four stages of cooling and heating by grouping compressors/heat stages in the factory IMC
configuration. Uses LonTalk protocol, conforming with LonMark® Rooftop Unit Functional Profile. Occupied, unoccupied, standby,
override, start−up and wait, cooling, heating, emergency heat, off, disabled, freeze protect, manual position, and fan−only modes.
Factory installed complete with return air temperature sensor and blower proving switch. Controls economizer damper via minimum
position, proportional free cooling (sensible, single enthalpy, or differential enthalpy), or demand control ventilation using an optional
carbon dioxide sensor. Supports modulating hydronic valves for heating and/or cooling. A total of one resistive analog input, two
binary inputs, and six relay outputs are available.
1
Sectra Single Zone Control is not compatible with the Four Stage Control Board (FS1).
SECTRA BYPASS CONTROL
Module monitors and controls heating, cooling and economizer functions of Lennox’ S−Classt and L Series® rooftop equipment
configured for pressure dependent constant volume bypass applications. Controls up to 18 zones per rooftop unit, with up to 50
combined zoned (bypass or VFD) and single zone (DDC or communicating thermostat) units on a single Sectra Commercial Zoning
System network (maximum of 120 LonWorks nodes). Allows 2 stage heat/3 stage cool demands to operate 1 four stages of cooling
and heating by grouping compressors/heat stages in the factory IMC configuration. Modulates bypass damper to maintain constant
static pressure input as zone dampers modulate. Occupied, unoccupied, vent and shutdown modes. Factory installed complete with
return air temperature sensor, discharge air temperature sensor, and blower proving switch. Controls economizer damper via minimum position, proportional free cooling ( sensible, single enthalpy, or differential enthalpy), or demand control ventilation using an
optional carbon dioxide sensor. Supports modulating hydronic valves for heating and/or cooling. A total of eight analog inputs, eight
binary inputs, eight binary outputs, and six analog outputs are available.
1
Sectra Bypass Control is not compatible with the Four Stage Control Board (FS1).
SECTRA VFD CONTROL
Module works with the Integrated Modular Controller (IMC) control module to monitor and control heating and cooling functions of
Lennox’ S−Classt and L Series® rooftop equipment configured for pressure dependent, variable air volume applications with a factory mounted variable frequency drive (VFD). Controls up to 18 zones per rooftop unit, with up to 50 combined zoned (bypass or
VFD) and single zone (DDC or communicating thermostat) units on a single Sectra Commercial Zoning System network (maximum
of 120 LonWorks nodes). Module communicates with IMC using blower enable (G), occupied (OCP), discharge cooling enable
(Y1), and discharge heating enable (W1) digital outputs. IMC modulates VFD to maintain constant static pressure input as zone
dampers modulate. IMC controls 4 stage heat/4 stage cool 1 individually based on discharge air temperature input. Economizer,
demand control ventilation, power exhaust, and other unit functionality are controlled directly by the IMC.
1
Sectra Bypass Control is not compatible with the Four Stage Control Board (FS1).
AFTERMARKET ZONING SYSTEMS
See "Aftermarket Zoning System Interface" in the Controls Application Guide section of this document.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 56
SECTRAt COMMERCIAL ZONING SYSTEM − FIELD INSTALLED
SECTRA ROOFTOP UNIT CONTROL KITS
Single Zone Control − Includes controller, blower proving switch, return air temperature sensors, mounting bracket, and wiring harness
Sectra Single Zone Control − L Series® 7.5 to 30 ton (CAV Models)
Sectra Single Zone Control − L
Series®
71M59
3 to 6 ton, S−Classt 40 ton (CAV Models)
21M51
Bypass Control − Includes controller, blower proving switch, return and discharge air temperature sensors, mounting bracket, and wiring
harness
Sectra Bypass Control − L Series® 7.5 to 30 ton
Sectra Bypass Control − L
Series®
34M42
3 to 6 ton, S−Classt 40 ton
34M41
Sectra VFD Control −− Includes controller and wiring harness to communicate with IMC controller
Sectra VFD Control − L Series® 25−30 ton (300H − 360H) (VFD Models)
83M59
Sectra VFD Control − S−Classt 40 ton (VFD Models)
83M58
NOTE − All Rooftop Unit Control Kits require 75VA transformer (32M78)
SECTRA ROOFTOP UNIT CONTROL SENSORS
Temperature −− Wall mount, three hour override button, override status LED, and setpoint adjust
29M56
Temperature −− Wall mount, without override or setpoint adjust
29M55
Temperature −− Wallplate, without override or setpoint adjust
85X52
Temperature − Duct mount, discharge air
19L22
CO2 − Wall mount white case, no display
87N53
CO2 − Wall mount, black case, no display (UL rated for interior duct and plenum mounting)
87N54
CO2 − Wall mount, white case, digital display
77N39
CO2 − Duct Kit − Aspiration box to mount any CO2 sensor in duct
90N43
Switch − Dirty Filter
30K48
Relay − Baseboard auxiliary heat
56L68
SECTRA PROGRAMMABLE THERMOSTAT
Three stage heating/cooling, seven day programmable, four periods/day, intelligent recovery, automatic
or manual changeover
60L59
Communicating subbase, conforms to LonMark® Thermostat Functional Profile
(required for use with Sectra network)
82N52
SECTRA THERMOSTAT SENSORS
Remote wall mount temperature sensor with setpoint adjust
58C92
1
86G67
Remote wall mount temperature sensor with three hour override button, override status LED, and setpoint adjust
Remote duct mount return air temperature sensor
27C40
2
66P91
Remote wall mount averaging temperature sensor
1, 2
Remote wall mount averaging temperature sensor
16P03
1 In averaging sensor applications, one 86G67 sensor can replace one 16P03 sensor (only one 86G67 can be used per thermostat).
2 Remote averaging sensors can be used in the following combinations only: (1) 16P03, (2) 66P91’s, (2) 16P03’s and (1) 66P91, (4) 16P03’s,
(5) 66P91’s or (9) 16P03’s.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 57
SECTRAt COMMERCIAL ZONING SYSTEM − FIELD INSTALLED
SECTRA ROOFTOP UNIT CONTROL SCHEDULER
Scheduler − Maintains schedules for up to four rooftop unit controllers
29M49
NOTE − 75VA transformer (32M78) required
SECTRA ROOFTOP UNIT CONTROL NETWORK DISPLAY
Network Display − Local interface to monitor and control Sectra network setpoints, schedules and
alarms
29M50
NOTE − 75VA transformer (32M78) required
SECTRA NETWORK MODEM
Modem − allows remote telephone communications to network, includes transformer
32M03
Modem cable −− DB9 to DB25 serial cable to connect modem to SLTA
54X01
NOTE: SLTA (92N65) required to connect modem to Sectra network
SECTRA SERIAL LONTALK® ADAPTOR
STLA − Provides communication between Sectra network and PC or modem
92N65
Operations Kit − Cable to connect SLTA to PC, 120/24VAC transformer for SLTA with power cord, instructions
83X18
NOTE: Modem (32M03) and modem cable (54X01) required for remote communication
SECTRA SOFTWARE
Lennox Commercial Controls Selection Software − Includes Sectra® (and L Connection®) Estimator Software for product selection and
submittal information
34M78
Sectrat Configurator − Windows® based PC software to configure, monitor and control Sectra system
29M57
SECTRA ZONE CONTROLLER
Zone Controller − Combined controller/actuator modulates zone damper based on signal from zone
sensor, reports demand to rooftop unit controller
29M52
NOTE − 75VA transformer (32M78) required
− Compatible with Sectra Bypass and Sectra VFD applications
SECTRA BYPASS DAMPER ACTUATOR
Bypass Damper Actuator − Modulates bypass damper based on signal from rooftop unit controller
29M16
NOTE − 75VA transformer (32M78) required
Static Pressure Transducer − Sends pressure signal to Sectra rooftop unit controller for bypass control
78M19
SECTRA TRANSFORMER
Transformer − 75VA, 120/208/220V primary, 24V secondary at rated power output
32M78
NOTE − Transformer can be used with unit controllers, Sectra Network Display, etc.
SECTRA LONWORKS® NETWORK WIRING
LonWorks Wire − 1000 feet, 22AWG, unshielded twisted pair, plenum rated, daisy chain on free topology transceiver (FTT) network
84X49
Four Way Repeater − Required for Sectra networks exceeding 4600 ft. (1400 m) in length or a combined 60 LonWorks nodes
99X43
Termination Module − Required at each non−repeater termination point (typically two per Sectra network)
37X75
NOTE − If repeater is present, one termination module is required per subnet − maximum four subnets.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 58
OPTIONAL UNIT CONTROLLERS − FACTORY OR Field Installed
Field Installed
Catalog No.
System and Component Description
CPC 810−3062
Control Module/Blower Proving Switch/Return Air Sensor/Discharge Air Sensor/Wiring Harness − Network communications (RS−485, shielded pair twisted wire), 8 analog/digital inputs, 8
form−C relay outputs, 2 analog outputs, 24 VAC, output connections (2 stage heat/2 stage cool, 2
auxiliary outputs (user defined), economizer, fan), input connections (space temperature, discharge
and return air temperature, 2 compressor monitoring, 2 aux. inputs (user defined), local override (1
to 240 minutes), Blower Proving Switch monitors blower operation and locks out unit in case of
blower failure, Return Air Sensor provides input to module to determine heating or cooling operation
and number of stages required, Discharge Air Sensor monitors leaving air temperature during unit
operation
71M57
Sensor − Room temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
48J43
Dirty Filter Switch − Senses static pressure increase indicating a dirty filter condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30K48
NO
START
CPC 810-3062 2 Heat/2 Cool
Includes: Control Module, Blower Proving
Switch, Return Air Sensor, Discharge Air
Sensor, Room Sensor (in kits 61J80 and
61J81 Only) and Wiring Harness
NO
DIRTY
FILTER
SWITCH
ROOM
SENSOR
(48J43)
(30K48)
STOP
CSI MR88R
Control Module/Blower Proving Switch/Return Air Sensor/Discharge Air Sensor/Wiring Harness − Small point count controller, supports free-form modular DDC programming, intelligent I/STAT for independent local analog or digital control, local
override and setpoint adjustment, 4 local or global points, integral start/stop schedule, standalone operation, universal inputs
(thermistor, voltage, current, contact), 8 relay or low voltage triac outputs, analog outputs, 7 signal inputs plus power, ISTAT
port, MR LAN port (RS−485, shielded pair twisted wire), self test diagnostics with LED readout, input point parameters (normal
and narrow range, indoor and outdoor temperature range, individual calibration) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
71M56
Sensor − Room temperature sensor with microprocessor data communications and power, alphanumeric LCD display for modes
selected, mode selection push buttons for (Function, Call, Service, Change and Select), password protection for Service mode,
up to 4 global point assignment with red LED’s to indicate (Set Temp., Fan Speed, Room and Outside) . . . . . . . . . . . . . . . . . . . . .
I/STAT
(Field Furnished)
Dirty Filter Switch − Senses static pressure increase indicating a dirty filter condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30K48
NO
START
CSI MR88R 2 Heat/2 Cool
Includes: Control Module, Blower Proving
DIRTY
FILTER
SWITCH
Switch, Return Air Sensor, Discharge Air
Sensor and Wiring Harness
(30K48)
STOP
HONEYWELL EXCEL 10 (W7750B)
Control Module (W7750B)/Blower Proving Switch/Discharge Air Sensor/Return Air Sensor/Wiring Harness − Standalone control (staged or modulating) of all heating, cooling, mixed air, system
fan and economizer functions, up to four stages of heating/cooling combinations, for single zone
applications, 6 relay outputs, 2 digital inputs, 1 resistive analog input, network communications,
LonMark compliant, configuration options include: supply fan type of air handler, occupancy sensor,
window sensor, wall module option, dirty filter monitor, indoor air quality override and smoke control.
modes of operation include: occupied, standby, unoccupied, bypass occupied, override modes,
start−up and wait, cooling, heating, emergency heat, off mode, disabled mode, smoke emergency,
freeze protect, manual position, fan only and disabled. Blower Proving Switch monitors blower operation and locks out unit in case of blower failure, Return Air Sensor provides input to module to
determine heating or cooling operation and number of stages required. . . . . . . . . . . . . . . . . . . . . . . . . .
..
71M59
Sensor − Room temperature, with setpoint knob . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
19L21
Dirty Filter Switch − Senses static pressure increase indicating a dirty filter condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30K48
NO
NO
START
HONEYWELL EXCEL 10 (W7750B)
4 Heat/4 Cool
Includes: Control Module, Blower Proving
Switch, Discharge Air Sensor, Return Air Sensor
and Wiring Harness
T7770
ROOM
SENSOR
DIRTY
FILTER
SWITCH
(19L21)
(30K48)
STOP
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 59
OPTIONAL UNIT CONTROLLERS − Factory or Field Installed
JOHNSON METASYS UNT
Control Module/Blower Proving Switch/Wiring Harness −Standalone control of all heating, cooling and economizer functions, various operation modes (including: occupied, unoccupied, warmup, standby), network communications, 6 analog inputs, 4 binary inputs, momentary override,
zone lighting control, advanced unit diagnostics, indoor air quality control, outdoor air temperature
and humidity monitoring, alarm monitoring of: sensors, airflow, economizer, dirty filter, heating
/cooling operation, cooling limit, Blower Proving Switch monitors blower operation and locks out
unit in case of blower failure, Control module may be used in multi−zone applications (i.e. L−Zone).
71M62
(208/230V−3ph)
71M63
(460V−3ph)
71M64
(575V−3ph)
Commissioning Tool − Hand−held interface tool, monitor & adjust 36 analog/binary points, carrying
case. . . . . . . . . . . . .
60K37
Sensor − Room temperature, phone jack style wiring, quick−mount design, latching door mechanism, setpoint adjustment (warmer/cooler), optional override button, nickel sensors, options for
choosing setpoint, indication, mounting and wiring type, plug for handheld commissioning tool
(60K36). . . . . . . . . .
42N44
Dirty Filter Switch − Senses static pressure increase indicating a dirty filter condition . . . . . . . . . . . .
30K48
NO
NO
START
JOHNSON METASYS UNT 2 Heat/2 Cool
Includes: Control Module, Discharge Air Sensor,
Return Air Sensor, Blower Proving Switch and
Wiring Harness
TE-6411
ROOM
SENSOR
DIRTY
FILTER
SWITCH
(42N44)
(30K48)
STOP
NOVAR ETM−2051
Electronic Thermostat Module (ETM)/Blower Proving Switch/Return Air Sensor/Discharge Air
Sensor/Wiring Harness − Module monitors unit operation from different sensors installed in unit and
monitors unit diagnostic codes of the IMC. The ETM has outputs for 2 stage heat/2 stage cool, 7 relay
outputs: fan Cool 1, Cool 2. Heat 1, Heat 2, Economizer, Night Mode, automatic or continuous blower
operation, economizer damper operation and night setback, features: day/occupied mode with low
enthalpy (outdoor air damper open), high enthalpy (outdoor air damper closed) or night/unoccupied
mode (outdoor air damper closed), network communication (RS−485, shielded pair twisted wire), local override (1 to 255 minutes), watchdog function, fail−safe operation, ETM allows units to be daisy
chained" together (up to 31 units) to be operated from one central location with an executive" type
control processor (on−site or off−site), built-in time delays, built-in unit operating defaults, diagnostic
LED’s indicate various operating functions, surge suppression protects ETM against lightning or voltage spikes, Blower Proving Switch monitors blower operation and locks out unit in case of blower failure, Return Air Sensor provides input to ETM module to determine heating or cooling operation and
number of stages required, Discharge Air Sensor monitors leaving air temperature during unit operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
71M58
Dirty Filter Switch − Senses static pressure increase indicating a dirty filter condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30K48
Room Temperature Sensor with Built−in Night Setback Override Button − Provides input to ETM module to determine heating
or cooling operation and number of stages required (ordered separately). Override button allows momentary override of night
setback during unoccupied mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
67K61
Sensor − Remote switch over . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
18L36
NO
NO
NO
START
NOVAR ETM-2051 2 Heat/2 Cool
Includes: Control Module, Blower Proving
Switch, Return Air Sensor, Discharge Air
Sensor and Wiring Harness
ROOM SENSOR W/
NIGHT SETBACK
OVERRIDE BUTTON
REMOTE
SWITCH OVER
SENSOR
DIRTY
FILTER
SWITCH
(67K61)
(18L36)
(30K48)
STOP
NOVAR CUSTOM CONTROLLER
Control Module/Blower Proving Switch/Discharge Air Sensor/Room Air Sensor/Wiring Harness
− User definable comfort setpoint, on/off and time of day control, cycle II ventilation control . . . . . .
71M65
Dirty Filter Switch − Senses static pressure increase indicating a dirty filter condition . . . . . . . . . . . .
30K48
NO
START
NOVAR CUSTOM CONTROLLER
2 Heat/2 Cool (48K89)
Includes: Control Module, Blower Proving
DIRTY
FILTER
SWITCH
Switch, Discharge Air Sensor, Room Air
Sensor and Wiring Harness
(30K48)
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 60
STOP
OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS − Field Installed
Field Installed
Catalog No.
System and Component Description
ELECTRO-MECHANICAL THERMOSTAT
Thermostat − Two stage heat & two stage cool with dual temperature levers, subbase choice . . . . . . .
Subbase − Manual system switch (Off-Heat-Auto-Cool), fan switch (Auto-On) . . . . . . . . . . . . . . . . . . .
Subbase − Non-switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Night Setback Operation − Order components below
Heating Thermostat − Single stage heat / Single stage cool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Subbase − Non-switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Time Clock − 7 day operation, indicates day and night periods, 2 hour increments, battery back-up .
Time Clock − 24 hour night setback operation, 15 minute increments, battery back-up . . . . . . . . . . . .
Blower Proving Switch − Monitors blower operation, locks out unit in case of blower failure . . . . . .
Dirty Filter Switch − Senses static pressure increase indicating a dirty filter condition . . . . . . . . . . . .
13F06
13F17
13F16
12F99
13F16
See Price Book
See Price Book
30K49
30K48
NO
NON
SWITCHING
SUBBASE
7 DAY
TIME
CLOCK
(13F16)
START
ELECTRO
MECHANICAL
THERMOSTAT
(13F06)
2 Heat−2 Cool
NIGHT
THERMOSTAT
1 Heat/1 Cool
NON
SWITCHING
SUBBASE
(12F99)
(13F16)
NO
24 HOUR
TIME
CLOCK
SWITCHING
SUBBASE
(13F17)
NO
BLOWER
PROVE
SWITCH
DIRTY
FILTER
SWITCH
(30K49)
(30K48)
ELECTRONIC THERMOSTAT
Electronic Thermostat − Any two stage heat/ two stage cool electronic thermostat may be used. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Time Clock − 7 day operation, indicates day and night periods, 2 hour increments, battery back-up . . . . . . . . . . . . . . . . . . . . . . . . .
Time Clock − 24 hour night setback operation, 15 minute increments, battery back-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blower Proving Switch − Monitors blower operation, locks out unit in case of blower failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dirty Filter Switch − Senses static pressure increase indicating a dirty filter condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
STOP
See Price Book
See Price Book
See Price Book
30K49
30K48
LESS ECONOMIZER
NO
NO
START
7 DAY
TIME
CLOCK
*ELECTRONIC
ROOM
THERMOSTAT
2 Heat−2 Cool
WITH ECONOMIZER
24 HOUR
TIME
CLOCK
* Any 2 stage heat/ 2 stage cool electronic
thermostat may be used.
See Lennox Price Book, Thermostats and Controls, Tab
for selection.
BLOWER
PROVE
SWITCH
DIRTY
FILTER
SWITCH
(30K49)
(30K48)
STOP
NO
PROGRAMMABLE COMMERCIAL THERMOSTAT
Thermostat − Programmable, internal or optional remote temperature sensing (sensor required), touch
sensitive keyboard, automatic switching, _F or _C readout, no anticipator, droop/no droop selection, indicator LED’s, hour/day programming, override capabilities, time and operational mode readout, stage
status indicators, battery back-up, subbase choice, manual system switch (Heat-Off-Auto-Cool), fan
switch (Auto-On) . .
Subbase − Selectable staging, indicator LED’s, auxiliary relay output for economizer operation
2 Heat / 2 Cool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Heat / 3 Cool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sensor − Room temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sensor − Room temperature with 3 hour override and setpoint adjustment . . . . . . . . . . . . . . . . . . . . . .
Sensor − Return air temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blower Proving Switch − Monitors blower operation, locks out unit in case of blower failure . . . . . .
Dirty Filter Switch − Senses static pressure increase indicating a dirty filter condition . . . . . . . . . . . .
59N27
37L55
37L53
58C92
86G67
27C40
30K49
30K48
NO
SWITCHING
SUBBASE
(37L55)
2 Heat−2 Cool
START
ROOM
TEMPERATURE
SENSOR
(59N27)
(86G67)
SWITCHING
SUBBASE
NO
(58C92)
ROOM
TEMPERATURE
SENSOR
W/OVERRIDE
T7300
THERMOSTAT
NO
(37L53)
RETURN AIR
TEMPERATURE
SENSOR
3 Heat−3 Cool
(27C40)
BLOWER
PROVE
SWITCH
DIRTY
FILTER
SWITCH
(30K49)
(30K48)
STOP
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 61
WEIGHT DATA − 13, 15, 17.5, 20, and 25 TON (156H, 180, 210, 240, and 300S)
Shipping
lbs.
kg
2555
1159
2760
1252
2685
1218
2880
1306
2735
1241
2940
1334
Net
Model Number
lbs.
2355
2560
2485
2680
2535
2740
156H/180 Base Unit
156H/180 Max. Unit
210 Base Unit
210 Max. Unit
240/300S Base Unit
240/300S Max. Unit
kg
1070
1161
1127
1216
1150
1243
OPTIONS / ACCESSORIES
Weight
CEILING DIFFUSERS
Step−Down
p
Flush
Transitions
ECONOMIZER / OUTDOOR AIR / EXHAUST
Economizer
Barometric Relief
Down−Flow Barometric Relief Dampers
Horizontal Barometric Relief Dampers
Outdoor Air Dampers
Damper Section (down−flow) − Motorized
Damper Section (down−flow) − Manual
Outdoor Air Hood (down−flow)
Power Exhaust
HEAT EXCHANGER
High Fire Heat Exchanger
PACKAGING
LTL Packaging (less than truck load)
ROOF CURBS − STANDARD
Down−Flow
14 in. (356 mm) height
24 in. (610 m) height
Horizontal
26 in. (660 mm) height
37 in. (940 mm) height
30 in. (762 mm) height
41 in. (1041 mm) height
ROOF CURBS − CLIPLOCK 1000
Down−Flow
14 in. (356 mm) height
18 in. (457 mm) height
24 in. (610 mm) height
Horizontal
26 in. (660 mm) height
37 in. (940 mm) height
30 in. (762 mm) height
41 in. (1041 mm) height
lbs.
kg.
RTD11−185
RTD11−275
FD11−185
FD11−275
LASRT18
LASRT21/24
392
403
289
363
80
75
178
183
135
165
36
34
LAREMD18/24
86
39
LAGED18/24
LAGEDH18/24
30
20
14
9
LAOADM18/24
52
24
LAOAD18/24
LAOAH18/24
LAPEF18/24
49
65
62
22
29
28
80
36
280
127
LARMF18/36−14
LARMF18/36−24
160
220
73
100
LARMFH18/24−26
LARMFH18/24−37
LARMFH30/36−30
LARMFH30/36−41
420
580
445
725
191
263
202
329
LARMF18/30S−14
LARMF18/30S−18
LARMF18/30S−24
165
193
234
75
88
106
LARMFH18/24S−26
LARMFH18/24S−37
LARMFH30/36S−30
LARMFH30/36S−41
457
491
456
480
207
223
207
218
Base Unit − The unit with low fire heat exchanger NO OPTIONS.
Max. Unit − The unit with ALL OPTIONS Installed. (High Input Heat Exchanger, Economizer, Power Exhaust Fans, Controls)
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 62
WEIGHT DATA − 21, 25, and 30 TON (248H, 300H, and 360H)
Shipping
lbs.
kg
3230
1465
3450
1565
3540
1606
3750
1701
Net
Model Number
lbs.
3020
3340
3330
3640
248H/300H Base Unit
248H/300H Max. Unit
360 Base Unit
360 Max. Unit
kg
1370
1515
1510
1651
OPTIONS / ACCESSORIES
Weight
lbs.
kg.
LARTD30/36
LAFD30/36
LASRT30/36
437
414
85
198
188
39
LAREMD30/36
119
54
LAGED30/36
LAGEDH30/36
45
20
20
9
LAOADM30/36
72
33
LAOAD30/36
LAOAH30/36
68
76
31
34
LAPEF30/36
50% High Static − LAPEB30/36DY
100% High Static with or without VFD − LAPEB30/36
99
400
465
45
181
211
80
36
300
136
LARMF18/36−14
LARMF18/36−24
160
220
73
100
LARMFH30/36−30
LARMFH30/36−41
445
725
202
329
LARMF30/36S−14
LARMF30/36S−18
LARMF30/36S−24
149
204
248
68
93
112
LARMFH30/36S−30
LARMFH30/36S−41
456
480
207
218
CEILING DIFFUSERS
Step−Down
Flush
Transitions
ECONOMIZER/OUTDOOR AIR
Economizer
Barometric Relief
Down−Flow Barometric Relief Dampers
Horizontal Barometric Relief Dampers
Outdoor Air Dampers
Damper Section (down−flow) − Motorized
Damper Section (down−flow) − Manual
Outdoor Air Hood (down−flow)
Power Exhaust
Power Exhaust
HEAT EXCHANGER
High Fire Heat Exchanger
PACKAGING
LTL Packaging (less than truck load)
ROOF CURBS − STANDARD
Down−Flow
14 in. (356 mm) height
24 in. (610 m) height
Horizontal
30 in. (762 mm) height
41 in. (1041 mm) height
ROOF CURBS − CLIPLOCK 1000
Down−Flow
14 in. (356 mm) height
18 in. (457 mm) height
24 in. (610 mm) height
Horizontal
30 in. (762 mm) height
41 in. (1041 mm) height
Base Unit − The unit with low fire heat exchanger NO OPTIONS.
Max. Unit − The unit with ALL OPTIONS Installed. (High Input Heat Exchanger, Economizer, Power Exhaust Fans, Controls)
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 63
DIMENSIONS − INCHES (MM)
13, 15, 17.5, 20, and 25 TON (156H, 180, 210, 240, and 300S)
CORNER WEIGHTS
Model
Number
AA
BB
CENTER OF GRAVITY
CC
DD
EE
FF
lbs.
kg
lbs.
kg
lbs.
kg
lbs.
kg
inch
mm
inch
156H/180 Base Unit
470
213
470
213
650
295
650
295
50
1270
38−1/2
978
156H/180 Max. Unit
580
263
590
268
700
318
690
313
54
1372
41-1/2
1054
210 Base Unit
480
218
460
209
680
308
710
322
52-1/2
1334
37
940
210 Max. Unit
610
277
590
268
730
331
750
304
52-1/2
1334
41
1041
240/300S Base Unit
490
222
520
236
740
336
710
322
54-1/2
1384
37-1/2
953
349
53
1346
40-1/2
1029
240/300S Max. Unit
610
277
610
277
750
304
770
mm
BB
AA
4-1/4 (108)
12-3/8
(314)
15 (381)
18 (457)
BOTTOM RETURN
AIR OPENING
BOTTOM SUPPLY
AIR OPENINGS
28
(711)
20 (508)
12-3/8
(314)
60-1/2 (1537)
4-1/2
(114)
28
(711)
20 (508)
EE
CENTER OF
GRAVITY
FF
4 (102)
DD
CC
BOTTOM POWER ENTRY
5 X 8 inches (127 X 203 mm)
4
(102)
TOP VIEW
OPTIONAL DISCONNECT
(Factory Installed)
132-5/8 (3369)
GAS SUPPLY
INLET
(For Bottom
Gas Supply Only)
90-1/8 (2289)
OPTIONAL
115 VOLT OUTLET
(Factory Installed Inside Unit)
54-1/4
(1378)
FLUE
OUTLET
51
(1295)
19-3/8
(492)
1-1/2
(38)
5-3/8
(137)
31-1/2
(800)
SIDE ELECTRICAL INLETS
3-1/4
(83)
CONDENSATE DRAIN
91-1/8 (2315)
END VIEW
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 64
GAS SUPPLY
INLET
OPTIONAL
OUTDOOR
GRILLE KIT
(Field Installed)
(Both Sides)
5-7/8
(149)
LIFTING HOLES
(For Rigging
Front and Back)
FORKLIFT SLOTS
(Front and Left Side Only)
107-3/4 (2737)
SIDE VIEW
25-3/8
(645)
ACCESSORY DIMENSIONS − INCHES (MM)
OPTIONAL OUTDOOR AIR HOOD DETAIL
WITH STANDARD STATIC POWER EXHAUST FANS
16
(406)
OPTIONAL
OUTDOOR AIR HOOD
(Factory or Field Installed)
Required with
Economizer or
Outdoor Air Damper
1 OPTIONAL
STANDARD STATIC
POWER EXHAUST
FANS HOOD
(Field Installed)
1
Field Installed in Return Air Duct for Horizontal Applications.
HORIZONTAL BAROMETRIC RELIEF DAMPERS
(Field installed in horizontal return air duct adjacent to unit)
31−5/8 (803)
29−1/2 (749)
6-1/2
(165)
FRONT VIEW
SIDE VIEW
1
14-1/2
(368)
1 13
(330)
NOTE − Two furnished per order no.
1 NOTE − Opening size required in return air duct.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 65
ACCESSORY DIMENSIONS − INCHES (MM)
13, 15, 17.5, 20, and 25 TON (156H, 180, 210, 240, and 300S)
STANDARD ROOF CURBS − DOUBLE DUCT OPENING
1-13/16
(46)
1-13/16
(46)
102-1/8 (2594)
98-1/2 (2502)
Frame
Opening
8−1/4
(210)
61−1/2 (1562)
16 (406)
NAILER STRIP
(Furnished)
CURB RETURN
AIR OPENING
17 (432)
14 (356) LARMF18/36-14
24 (610) LARMF18/36-24
3/4 (19) Typ.
82-5/8
(2099)
86-1/8
(2188)
1-13/16
(46)
Frame
Opening
102-1/2 (2604)
61-1/2 (1562)
8−1/4
(210)
NOTE Roof deck may be omitted within confines of curb.
CURB
SUPPLY AIR
OPENING
21
(533
)
SIDE VIEW
1-13/16 (46)
A
1 (25)
14 (356) LARMF18/36-14
24 (610) LARMF18/36-24
A
NAILER STRIP
(Furnished)
2 (51)
SECTION A-A
1-13/16
(46)
TOP VIEW
CLIPLOCK 1000 ROOF CURBS − DOUBLE DUCT OPENING
16"
(406.4)
86−1/4"
(2190.75)
21"
(533.4)
102−1/8"
(2593.975)
8−1/4"
(209.55)
81−1/2"
(2070.1)
61−1/2"
(1562.1)
17"
(431.8)
98−1/2"
(2501.9)
RETURN AIR
OPENING
8−1/4"
(209.55)
SUPPLY AIR
OPENING
14 (356)
18 (457)
24 (610)
61−1/2"
(1562.1)
DISCARD DUCT SUPPORT WHEN
USING FOR OTHER THAN
LARMF − 18/36
2" MIN.
FACTORY INSTALLED
PERIMETER WOOD
NAILER STRIP
CORNER DETAIL
TOP EDGE
WOOD NAILER STRIP
BOTTOM FLANGE
TYPICAL SLOT
TYPICAL LOCKING TAB
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 66
ACCESSORY DIMENSIONS − INCHES (MM)
13, 15, 17.5, 20, and 25 TON (156H, 180, 210, 240, and 300S)
STANDARD ROOF CURBS WITH SUPPLY & RETURN AIR TRANSITIONS FOR CEILING DIFFUSERS
1-13/16 (46)
102-1/8 (2594)
98-1/2 (2502)
1-13/16 (46)
Frame
Opening
69-1/4 (1759)
1-13/16 (46)
TRANSITION DETAIL
26-1/2
(673)
LASRT RETURN TRANSITION
Frame
Opening
RETURN
AIR OPENING
SUPPORT
ANGLE
(Furnished
with
Transitions)
A
B
8 (203)
54
(1372)
4-1/2
(114)
82-5/8
(2099)
69-1/4
(1759)
A
SUPPLY AIR
OPENINGS
86-1/8
(2188)
A
2
(51)
B
1-1/2 Typ.
(38)
B
LASRT SUPPLY TRANSITION
1-13/16 (46)
1 (25)
14 (356) LARMF18/36-14
24 (610) LARMF18/36-24
NAILER STRIP
(Furnished)
3/4 Typ.
(19)
A
TRANSITION OPENING SIZES
A
2 (51)
SECTION A-A
1-13/16 (46)
TOP VIEW
INSULATION
(Furnished)
10 8 (203)
(254)
NAILER STRIP
(Furnished)
2
(51)
A
B
Model
Number
inch
mm
inch
mm
LASRT18
18
457
36
914
LASRT21/24
24
610
48
1219
14 (356) LARMF18/36-14
24 (610) LARMF18/36-24
102-1/2 (2604)
NOTE Roof deck may be omitted within confines of curb.
SIDE VIEW
ROOF CURB SPECIFICATIONS
TYPICAL FLASHING DETAIL FOR ROOF CURBS
Roof Curb is rigid enough to be spanned over its entire length or cantilevered if supported on both sides of center of gravity.
Roof Curb
1
Moment of inertia (I) (in.4) (cm4)
1
Section modulus
I
(in.3) (cm3)
C
Curb weight. (lb/ft) (kg/m) of length
Design strength (psi) (kPa)
1
UNIT BASE
BOTTOM
LARMF18/36-14 LARMF18/36-24
39 (1634)
160 (6639)
5.5 (90)
13.1 (512)
5.5 (8.2)
8.5 (12.7)
20,000 (137,900)
UNIT BASE RAIL
FIBERGLASS
INSULATION
(Furnished)
COUNTER FLASHING
(Field Supplied)
NAILER STRIP
(Furnished)
ROOF CURB
(Extends around entire
perimeter of unit)
Includes both sides of curb.
CANT STRIP
(Field Supplied)
ROOFING
MATERIAL
RIGID INSULATION
(Field Supplied)
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 67
ACCESSORY DIMENSIONS − INCHES (MM)
13, 15, 17.5, 20, and 25 TON (156H, 180, 210, 240, and 300S)
HORIZONTAL ROOF CURBS − Requires Optional Horizontal Return Air Panel Kit
102-1/8 (2594)
1-13/16 (46)
1-13/16
(46)
98-1/2 (2502)
1-13/16 (46)
Frame
Opening
NOTE LARMFH18/24-26 and LARMFH30/36-30
are designed for horizontal discharge
when unit is mounted on a slab.
LARMFH18/24-37 and LARMFH30/36-41
are designed for horizontal discharge
when unit is mounted on a rooftop.
Opening
Frame
1-13/16 (46)
1
2
3
4
1 (25)
26 (660)
37 (940)
30 (762)
41 (1041)
A
A
NAILER STRIP
(Furnished)
2 (51)
PANEL TO COVER RETURN AIR OPENING IN BOTTOM OF UNIT
(Furnished With Optional Horizontal Return Air Panel Kit)
SECTION A-A
82-5/8
(2099)
98-1/2 (2502)
86-1/8
(2188)
54
(1372)
SUPPLY AIR
TURNING VANE
(Furnished)
SIDE VIEW
NOTE − Roof deck may be omitted within confines of curb.
1,2
3,4
TOP VIEW
1-13/16 (46)
(PACKAGED UNIT)
8-1/4 (210)
13-1/4 (337)
NAILER STRIP
(Furnished)
86-1/4 (2191)
102-1/8 (2594)
5-1/2 (140)
1
2
3
4
75
26 (660)
37 (940)
30 (762)
41 (1041)
CURB SUPPLY (1905)
AIR OPENING
With 1-1/2 in. (38 mm) FLANGE
1,2
3,4
1,3
2,4
SUPPLY AIR
TURNING VANE
(Furnished)
14 (356)
18 (457)
6-1/2 (165)
17-1/2 (445)
86-5/8 (2200)
102-1/2 (2604)
FRONT VIEW
2
1 LARMFH18/24-26
LARMFH18/24-37
3
SUPPLY
DUCT
PANELS
(Furnished)
SIDE VIEW
4 LARMFH30/36-40
LARMFH30/36-30 (used with 300S/300H/360 Models)
(used with 300S/300H/360 Models)
HORIZONTAL SUPPLY AND RETURN AIR OPENINGS
WITH HORIZONTAL ROOF CURB
OPTIONAL RETURN AIR PANEL KIT
(Required For
Horizontal Applications)
54-1/4
(1378)
1
2
3
4
76-1/4 (1937)
87-1/4 (2216)
80-1/4 (2038)
91-1/4 (2318)
12-3/8
(314)
60-1/2 (1537)
15 (381) HORIZONTAL RETURN
AIR OPENING
2 (51)
1
2
3
4
22 (559)
33 (838)
26 (660)
37 (940)
NOTE − Top of Roof Curb extends 4 inch
(102 mm) inside bottom of unit base. See
Typical flashing detail.
30-3/8
(772)
75 (1905)
HORIZONTAL
1,2 14 (356)
SUPPLY AIR OPENING 3,4 18 (457)
HORIZONTAL ROOF CURB
(Required For Horizontal Applications)
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 68
1
2
3
4
1,3
2,4
6-1/2 (165)
17-1/2 (445)
LARMFH18/24-26
LARMFH18/24-37
LARMFH30/36-30 (used with 300S Models Only)
LARMFH30/36-40 (used with 300S Models Only)
1,2
3,4
8-1/4 (210)
13-1/4 (337)
ACCESSORY DIMENSIONS − INCHES (MM)
13, 15, 17.5, 20, and 25 TON (156H, 180, 210, 240, and 300S)
COMBINATION CEILING SUPPLY AND RETURN DIFFUSERS
STEP-DOWN CEILING DIFFUSER
H
FLUSH CEILING DIFFUSER
E
4−5/8 (117)
G
G
F
4−13/16
(122)
F
2 (51)
C
4−5/8 (117)
E
B
E
D
4−13/16
(122)
2 (51)
A
A
C
K
G
B
D
Model Number
A
B
C
D
E
F
G
H
K
RTD11−185
RTD11−275
in.
34
40
mm
864
1016
in.
23−7/8
28−7/8
mm
606
225
in.
10−1/8
11−1/8
mm
257
283
in.
47−5/8
59−5/8
mm
1210
1514
in.
45−5/8
57−7/8
mm
1159
1470
in.
36
48
mm
914
1219
in.
18
24
Model Number
A
B
C
D
E
F
in.
FD11−185
FD11−275
30−1/8
36−1/8
mm
613
918
in.
47−5/8
59−5/8
mm
1210
1514
in.
45−5/8
57−5/8
mm
1159
1464
in.
36
48
mm
914
1219
in.
18
24
mm
457
610
in.
45−5/8
57−5/8
mm
457
610
mm
1159
1464
in.
45−5/8
57−5/8
in.
47−5/8
59−5/8
mm
1159
1464
mm
1210
1521
in.
47−5/8
59−5/8
mm
1210
1521
G
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 69
DIMENSIONS − INCHES (MM)
21, 25, and 30 TON (248H, 300H, and 360H)
Shown With Optional Economizer Dampers, Power Exhaust Fans, Convenience Outlet, Unit Disconnect
CORNER WEIGHTS
Model
Number
AA
BB
CENTER OF GRAVITY
CC
DD
EE
FF
lbs.
kg
lbs.
kg
lbs.
kg
lbs.
kg
inch
mm
inch
248H/300H Base Unit
588
267
630
286
932
423
870
395
62-5/8
1591
36-3/4
mm
933
248H/300H Max. Unit
716
325
743
337
958
335
923
419
61-1/4
1556
39-3/4
1010
360 Base Unit
656
298
639
290
1004
455
1031
468
59-3/4
1518
35-3/8
899
360 Max. Unit
785
356
740
336
1025
465
1090
494
58-7/8
1495
38-1/4
972
ACCESSORY SHIPPING WEIGHTS (add to base unit weight)
High Fire Heat Exchange
80 lbs.
36 kg
Power Exhaust
90 lbs.
41 kg
Economizer + Hood
195 lbs.
88 kg
LTL Packaging (less than truck load)
300 lbs.
136 kg
Outdoor Air Damper + Hood
148 lbs.
67 kg
Base Unit − The unit with low fire heat exchanger NO OPTIONS.
Max. Unit − The unit with ALL OPTIONS Installed. (High Input Heat Exchanger, Economizer, Power Exhaust Fans, Controls)
EE
4-1/4
(108)
AA
5-3/4
(146)
BB
15 (381)
78-1/2 (1994)
18 (457)
17-1/2
(445)
BOTTOM RETURN
AIR OPENING
CENTER OF
GRAVITY
28
28
(711)
(711)
4-1/2 20 (508)
20 (508)
(114)
FF
BOTTOM SUPPLY
AIR OPENINGS
4 (102)
DD
CC
BOTTOM POWER/GAS ENTRY 5 X 8 inches (127 X 203 mm)
4 (102)
TOP VIEW
OPTIONAL
115 VOLT OUTLET
(Factory Installed Inside Unit)
145 (3683)
90-1/8 (2289)
OPTIONAL
DISCONNECT
(Factory Installed)
65
(1651)
SIDE
ELECTRICAL
INLETS
61-3/4
(1568)
CONDENSATE DRAIN
91-1/8 (2315)
END VIEW
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 70
FLUE
OUTLET
OPTIONAL
OUTDOOR
GRILLE KIT
(Field Installed)
(Both Sides)
5-3/4
(146)
5-3/8
(137)
31-1/2
(800)
GAS SUPPLY
INLET
(For Bottom
Gas Supply Only)
3-1/4
(83) 4
(102)
FORKLIFT SLOTS
(Front and Left Side Only)
119−3/4 (3042)
SIDE VIEW
LIFTING HOLES
(For Rigging
Front and Back)
25-3/4
(654)
ACCESSORY DIMENSIONS − INCHES (MM)
OPTIONAL OUTDOOR AIR HOOD DETAIL
WITH STANDARD STATIC POWER EXHAUST FANS
16
(406)
OPTIONAL
OUTDOOR AIR HOOD
(Factory or Field Installed)
Required with
Economizer or
Outdoor Air Damper
1 OPTIONAL
STANDARD STATIC
POWER EXHAUST
FANS HOOD
(Field Installed)
1
Field Installed in Return Air Duct for Horizontal Applications.
OPTIONAL HIGH STATIC POWER EXHAUST FANS DETAIL
13−3/4
(349)
28
(711)
OPTIONAL
HIGH STATIC
POWER EXHAUST FANS
(Field Installed)
HORIZONTAL BAROMETRIC RELIEF DAMPERS
(Field installed in horizontal return air duct adjacent to unit)
54−1/2 (1384)
52−1/2 (1334)
6-1/2
(165)
1
14-1/2
(368)
1 13
(330)
FRONT VIEW
SIDE VIEW
NOTE − Two furnished per order no.
1 NOTE − Opening size required in return air duct.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 71
ACCESSORY DIMENSIONS − INCHES (MM)
21, 25, and 30 TON (248H, 300H, and 360H)
STANDARD ROOF CURBS − DOUBLE DUCT OPENING
1-13/16
(46)
1-13/16
(46)
1-13/16
(46)
102-1/8 (2594)
98-1/2 (2502)
Frame
Opening
79-1/2 (2019)
Frame
Opening
1-3/4
(44)
CURB RETURN
AIR OPENING
16 (406)
17 (432)
NAILER STRIP
(Furnished)
3/4 (19) Typ.
82-5/8
(2099)
86-1/8
(2188)
13-1/4
(337)
14 (356) LARMF18/36-14
24 (610) LARMF18/36-24
61-1/2 (1562)
21
(533)
CURB SUPPLY
AIR OPENINGS
102-1/2 (2604)
NOTE Roof deck may be omitted within confines of curb.
1-13/16 (46)
1 (25)
14 (356) LARMF18/36-14
24 (610) LARMF18/36-24
A
SIDE VIEW
A
NAILER STRIP
(Furnished)
2 (51)
SECTION A-A
1-13/16
(46)
TOP VIEW
CLIPLOCK 1000 ROOF CURBS − DOUBLE DUCT OPENING
1−3/4"
(44.45)
16"
(406.4)
86−1/4"
(2190.75)
21"
(533.4)
114"
(2895.6)
81−1/2"
(2070.1)
79−1/2"
(2019.3)
17"
(431.5)
110−3/8"
(2803.525)
RETURN AIR
OPENING
13−1/4"
(336.55)
SUPPLY AIR
OPENING
14 (356)
18 (457)
24 (610)
61−1/2"
(1562.1)
FACTORY INSTALLED
PERIMETER WOOD
NAILER STRIP
CORNER DETAIL
TOP EDGE
WOOD NAILER STRIP
2" MIN.
(50.8)
BOTTOM FLANGE
TYPICAL SLOT
TYPICAL LOCKING TAB
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 72
ACCESSORY DIMENSIONS − INCHES (MM)
21, 25, and 30 TON (248H, 300H, and 360H)
STANDARD ROOF CURBS WITH SUPPLY & RETURN AIR TRANSITIONS FOR CEILING DIFFUSERS
102-1/8 (2594)
1-13/16
(46)
1-13/16
(46)
98-1/2 (2502)
ROOF CURB DETAIL
1-13/16
(46)
Frame
Opening
80-3/4 (2051)
1-13/16 (46)
B
28
(711)
60 (1524)
82-5/8
(2099
)
LASRT RETURN
TRANSITION
Frame
Opening
RETURN
AIR OPENING
1 (25)
14 (356) LARMF18/36-14
24 (610) LARMF18/36-24
SUPPORT
ANGLE
(Furnished
with
Transitions)
2 (51)
54
(1372)
SECTION A-A
4-1/2 (114)
SUPPLY AIR
OPENINGS
28
(711)
TRANSITION DETAIL
LASRT SUPPLY
TRANSITION
60 (1524)
86-1/8
(2188)
1-1/2 Typ.
(38)
3/4 Typ.
(19)
A
B
14 12 (305)
(356
)
A
26-1/2
(673)
26-1/2
(673)
LASRT SUPPLY
TRANSITION
LASRT RETURN
TRANSITION
2
(51)
28
(711)
TOP VIEW
1-13/16
(46)
NAILER STRIP
(Furnished)
4-1/2
(114)
28
(711)
SECTION B-B
INSULATION
(Furnished)
14 12 (305)
(356
)
2
(51)
NAILER STRIP
(Furnished)
14 (356) LARMF18/36-14
24 (610) LARMF18/36-24
102-1/2 (2604)
NOTE Roof deck may be omitted within confines of curb.
SIDE VIEW
ROOF CURB SPECIFICATIONS
TYPICAL FLASHING DETAIL FOR ROOF CURBS
Roof Curb is rigid enough to be spanned over its entire length or cantilevered if supported on both sides of center of gravity.
Roof Curb
1
Moment of inertia (I) (in.4) (cm4)
1
Section modulus
I
(in.3) (cm3)
C
Curb weight. (lb/ft) (kg/m) of length
Design strength (psi) (kPa)
1
UNIT BASE
BOTTOM
LARMF18/36-14 LARMF18/36-24
39 (1634)
160 (6639)
5.5 (90)
13.1 (512)
5.5 (8.2)
8.5 (12.7)
20,000 (137,900)
UNIT BASE RAIL
FIBERGLASS
INSULATION
(Furnished)
COUNTER FLASHING
(Field Supplied)
NAILER STRIP
(Furnished)
ROOF CURB
(Extends around entire
perimeter of unit)
Includes both sides of curb.
CANT STRIP
(Field Supplied)
ROOFING
MATERIAL
RIGID INSULATION
(Field Supplied)
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 73
ACCESSORY DIMENSIONS − INCHES (MM)
21, 25, and 30 TON (248H, 300H, and 360H)
HORIZONTAL ROOF CURBS − Requires Optional Horizontal Return Air Panel Kit
102-1/8 (2594)
1-13/16 (46)
1-13/16
(46)
98-1/2 (2502)
1-13/16 (46)
Frame
Opening
NOTE LARMFH30/36-30 is designed for horizontal
discharge when unit is mounted on a slab.
LARMFH30/36-41 is designed for horizontal
discharge when unit is mounted on a rooftop.
1
2
3
4
Opening
Frame
1-13/16 (46)
1 (25)
26 (660)
37 (940)
30 (762)
41 (1041)
A
A
NAILER STRIP
(Furnished)
2 (51)
PANEL TO COVER RETURN AIR OPENING IN BOTTOM OF UNIT
(Furnished With Optional Horizontal Return Air Panel Kit)
SECTION A-A
82-5/8
(2099)
98-1/2 (2502)
86-1/8
(2188)
54
(1372)
SUPPLY AIR
TURNING VANE
(Furnished)
SIDE VIEW
NOTE − Roof deck may be omitted within confines of curb.
1-13/16 (46)
(PACKAGED UNIT)
1,2
3,4
TOP VIEW
8-1/4 (210)
13-1/4 (337)
NAILER STRIP
(Furnished)
86-1/4 (2191)
102-1/8 (2594)
5-1/2 (140)
1
2
3
4
26 (660)
37 (940)
30 (762)
41 (1041)
75 (1905)
CURB SUPPLY
AIR OPENING
With 1-1/2 in. (38 mm) FLANGE
1,3
2,4
1,2
3,4
SUPPLY AIR
TURNING VANE
(Furnished)
14 (356)
18 (457)
6-1/2 (165)
17-1/2 (445)
86-5/8 (2200)
102-1/2 (2604)
FRONT VIEW
1 LARMFH18/24-26
2
LARMFH18/24-37
3
SUPPLY
DUCT
PANELS
(Furnished)
SIDE VIEW
LARMFH30/36-30 (used with 248H/300S/300H/360 Models) 4 LARMFH30/36-40 (used with 248H/300S/300H/360 Models)
HORIZONTAL SUPPLY AND RETURN AIR OPENINGS
ROOFTOP UNIT WITH HORIZONTAL ROOF CURB
OPTIONAL RETURN AIR PANEL KIT
(Required For
Horizontal Applications
65
(1651)
91 (2311)
LARMFH30/36-30
102 (2591)
LARMFH30/36-41
78-1/2 (1994)
15 (381)
HORIZONTAL RETURN
AIR OPENING
5-1/4
(133)
2 (51)
1
26 (660)
LARMFH30/36-30
37 (9401)
LARMFH30/36-41
75 (1905)
1
1
NOTE − Top of Curb extends 4 inch (102
mm) inside bottom of unit base. See Typical
Flashing Detail.
HORIZONTAL
SUPPLY AIR OPENING
42-7/8
(1089)
HORIZONTAL ROOF CURB
(Required For Horizontal Applications)
SIDE VIEW
(Horizontal Openings)
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 74
18 (457)
13-1/4
(337)
6-1/2 (165)
LARMFH30/36-30
17-1/2 (445)
LARMFH30/36-41
ACCESSORY DIMENSIONS − INCHES (MM)
21, 25, and 30 TON (248H, 300H, and 360H)
COMBINATION CEILING SUPPLY AND RETURN DIFFUSERS
LARTD30/36 STEP-DOWN CEILING DIFFUSER
63−5/8
(1616) 4−5/8 (117)
28
28
(711)
(711)
63−5/8
(1616)
1−13/16
60
(46)
(1524)
LAFD30/36 FLUSH CEILING DIFFUSER
2 (51)
63−5/8
(1616) 4−5/8 (117)
28
28
(711)
(711)
63−5/8
(1616) 1−13/16
60
(46)
(1524)
38−7/8 51
(987)(1295)
2 (51)
46
(1168)
12−1/8
(308)
65−5/8 (1667)
65−5/8
(1667)
65−5/8 (1667)
65−5/8 (1667)
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 75
GUIDE SPECIFICATIONS
This MANU−SPEC® utilizes the Construction Specifications Institute (CSI) Manual of Practice, including
MasterFormatt, SectionFormatt and PageFormatt. A MANU−SPEC is a manufacturer−specific proprietary
product specification using the proprietary method of specifying applicable to project specifications and master
guide specifications. Optional text is indicated by brackets [ ]; delete optional text in final copy of specification.
Specifier Notes typically precede specification text; delete notes in final copy of specification. Trade/brand names
with appropriate symbols typically are used in Specifier Notes; symbols are not used in specification
text. Metric conversion, where used, is soft metric conversion.
This MANU−SPEC specifies Lennox L Series® Rooftop Units. These products are manufactured by Lennox
Industries Inc. Revise MANU−SPEC section number and title below to suit project requirements, specification
practices and section content. Refer to CSI MasterFormat for other section numbers and titles.
SECTION 15730
UNITARY AIR CONDITIONING EQUIPMENT
PART 1 GENERAL
PART 1.01
A.
SUMMARY
Section Includes: Packaged rooftop units and commercial packaged, gas/electric and electric/electric heat pumps.
Specifier Note: Revise paragraph below to suit project requirements. Add section numbers and titles per CSI MasterFormat and
specifier’s practice.
B.
Related Sections:
Specifier Note: Article below may be omitted when specifying manufacturer’s proprietary products and recommended installation.
Retain Reference Article when specifying products and installation by an industry reference standard. If retained, list standard(s)
referenced in this section. Indicate issuing authority name, acronym, standard designation and title. Establish policy for indicating
edition date of standard referenced. Conditions of the Contract or Division 1 References Section may establish the edition date of
standards. This article does not require compliance with standard, but is merely a listing of references used. Article below should list
only those industry standards referenced in this section. Retain only those reference standards to be used within the text of this
Section. Add and delete as required for specific project.
PART 1.02
A.
B.
C.
REFERENCES
American National Standards Institute (ANSI):
1.
ANSI/ASHRAE 15 Safety Standard for Refrigeration Systems.
2.
ANSI/ASHRAE/IESNA 90.1 Energy Efficient Design of New Buildings Except Low−Rise Residential Buildings.
3.
ANSI Z21.47 Gas−Fired Central Furnaces.
Air−Conditioning and Refrigeration Institute (ARI):
1.
ARI 210/240 Unitary Air−Conditioning and Air−Source Heat Pump Equipment.
2.
ARI 270 Sound Rating of Outdoor Unitary Equipment.
3.
ARI 340/360 Commercial and Industrial Unitary Air−Conditioning and Heat Pump Equipment.
4.
ARI 370 Sound Rating of Large Outdoor Refrigerating and Air Conditioning Equipment.
American Society of Heating, Refrigerating, and Air−Conditioning Engineers, Inc. (ASHRAE):
1.
ASHRAE 52.2 Method of Testing General Ventilation Air−Cleaning Devices for Removal Efficiency by Particle Size
(ANSI approved).
2.
ASHRAE 62.1 Ventilation for Acceptable Indoor Air Quality.
D.
U.S. Energy Policy Act of 1992 (EPACT).
E.
U.S. National Appliance Energy Conservation Act (NAECA):
1.
F.
National Fire Protection Association (NFPA):
1.
G.
NAECA 1988.
NFPA 90A Installation of Air Conditioning and Ventilation Systems.
Underwriters Laboratories, Inc. (UL):
1.
UL 1995 Standard for Safety for Heating and Cooling Equipment.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 76
GUIDE SPECIFICATIONS
Specifier Note: Article below should be restricted to statements describing design or performance requirements and functional (not
dimensional) tolerances of a complete system. Limit descriptions to composite and operational properties required to link components
of a system together and to interface with other systems.
PART 1.03
SYSTEM DESCRIPTION
A. Design Requirements: Provide products and systems that have been manufactured, fabricated and installed to following
criteria:
1.
ANSI/ASHRAE/IESNA 90.1.
2.
ANSI Z21.47.
3.
UL 1995.
B. Performance Requirements:
1.
Packaged Gas Electric:
a.
Natural Gas Supply Pressure: 7 in. w.c. (1.7 kPa).
b.
LPG/Propane Supply Pressure: 11 in. w.c. (2.7 kPa).
Specifier Note: Specify 208/230 V or 460 V or 575 V, 3−phase for L Series® units from 6 − 30 ton (21.1 − 105.6 kW). Specify 208/230
V, 1−phase, 208/230 V, 460 V, or 575 V, 3−phase for L Series® units from 3 − 5 ton (10.6 − 17.6 kW).
2.
Packaged Cooling:
a.
Electrical Requirements for Direct Drive Blowers: 60 hz, [208/230 V, 1−phase] [208/230 V, 3−phase] [460 V,
3−phase] [575 V, 3−phase].
Specifier Note: For belt drive blowers from models LCC072S, LCA072H, LCC090S, LCA090H, LCC102S, LCA102H, LCC156H,
LCC180S, LCC180H, LCC210S, LCC210H, LCC240S, LCA240H, LCC300S, LCC300H, LCA360H, and LCC360H single phase is
not an option.
b.
Electrical Requirements for Belt Drive Blowers: 60 hz, [208/230 V, 1−phase] [208/230 V, 3−phase] [460 V,
3−phase] [575 V, 3−phase].
Specifier Note: Available Heat Pump units include LHA090, LHC090, LHA240 and LHC240 only.
3.
Packaged Heat Pumps:
a.
Electrical Requirements: 60 hz, [208/230 V, 3−phase] [460 V, 3−phase] [575 V, 3−phase].
4.
ARI Rated Net Cooling Efficiency: To meet or exceed ASHRAE Standard 90.1 at rated airflow not less than 350
cfm/ton.
Specifier Note: Article below includes submittal of relevant data to be furnished by Contractor before, during or after construction.
Coordinate this article with Architect’s and Contractor’s duties and responsibilities in Conditions of the Contract and Division 1
Submittal Procedures Section.
PART 1.04
SUBMITTALS
A. General: Submit listed submittals in accordance with Conditions of the Contract and Division 1 Submittal Procedures.
B. Product Data: Submit product data, including manufacturer’s SPEC−DATA® product sheet, for specified products.
C. Shop Drawings:
1.
Submit shop drawings in accordance with Section 01330 − Submittal Procedures.
2.
Indicate:
a.
Equipment, piping and connections, together with valves, strainers, control assemblies, thermostatic controls,
auxiliaries and hardware, and recommended ancillaries which are mounted, wired and piped ready for final
connection to building system, its size and recommended bypass connections.
b.
Piping, valves and fittings shipped loose showing final location in assembly.
c.
Control equipment shipped loose, showing final location in assembly.
d.
Dimensions, internal and external construction details, recommended method of installation with proposed
structural steel support, mounting curb details, sizes and location of mounting bolt holes; include mass
distribution drawings showing point loads.
e.
Detailed composite wiring diagrams for control systems showing factory installed wiring and equipment on
packaged equipment or required for controlling devices or ancillaries, accessories and controllers.
f.
Details of vibration isolation.
g.
Estimate of sound levels to be expected across individual octave bands in dB.
h.
Type of refrigerant used.
D. Quality Assurance:
1.
Test Reports: Certified test reports showing compliance with specified performance characteristics and physical
properties.
2.
Certificates: Product certificates signed by manufacturer certifying materials comply with specified performance
characteristics and criteria and physical requirements.
3.
Manufacturer’s Instructions: Manufacturer’s installation instructions.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 77
GUIDE SPECIFICATIONS
Specifier Note: Coordinate paragraph below with Part 3 Field Quality Requirements Article herein. Retain or delete as applicable.
E.
Manufacturer’s Field Reports: Manufacturer’s field reports specified.
F.
Closeout Submittals: Submit the following:
1.
Warranty: Warranty documents specified.
2.
Operation and Maintenance Data: Operation and maintenance data for installed products in accordance with
Division 1 Closeout Submittals (Maintenance Data and Operation Data) Section. Include methods for maintaining
installed products and precautions against cleaning materials and methods detrimental to finishes and performance.
Include names and addresses of spare part suppliers.
3.
Provide brief description of unit, with details of function, operation, control and component service.
4.
Commissioning Report: Submit commissioning reports, report forms and schematics in accordance with
Section 01810 − Commissioning.
PART 1.05
A.
QUALITY ASSURANCE
Qualifications:
1.
Installer experienced in performing work of this section who has specialized in installation of work similar to that
required for this project.
2.
Manufacturer Qualifications: Manufacturer capable of providing field service representation during construction and
approving application method.
Specifier Note: Paragraph below should list obligations for compliance with specific code requirements particular to this section.
General statements to comply with a particular code are typically addressed in Conditions of the Contract and Division 1 Regulatory
Requirements Section. Repetitive statements should be avoided. Current data on building code requirements and product compliance
may be obtained from filter manufacturer technical support specialists.
B.
C.
Regulatory Requirements: Provide [Packaged gas electric] [Packaged cooling] [Packaged heat pump] that complies with
the following requirements:
1.
ARI 210/240.
2.
ARI 270.
3.
ARI 340/360.
4.
ASHRAE 52.2.
5.
NFPA 90A.
Preinstallation Meetings: Conduct preinstallation meeting to verify project requirements, manufacturer’s installation
instructions and manufacturer’s warranty requirements. Comply with Division 1 Project Management and Coordination
(Project Meetings).
PART 1.06
DELIVERY, STORAGE & HANDLING
A.
General: Comply with Division 1 Product Requirements.
B.
Ordering: Comply with manufacturer’s ordering instructions and lead time requirements to avoid construction delays.
C.
Packing, Shipping, Handling and Delivery:
D.
PART 1.07
A.
1.
Deliver materials in manufacturer’s original, unopened, undamaged containers with identification labels intact.
2.
Ship, handle and unload units according to manufacturer’s instructions.
Storage and Protection:
1.
Store materials protected from exposure to harmful weather conditions.
2.
Factory shipping covers to remain in place until installation.
PROJECT CONDITIONS
Installation Location: [Confirm design conditions and temperature.].
Specifier Note: Coordinate article below with Conditions of the Contract and with Division 1 Closeout Submittals (Warranty).
PART 1.08
WARRANTY
A.
Project Warranty: Refer to Conditions of the Contract for project warranty provisions.
B.
Manufacturer’s Warranty: Submit, for Owner’s acceptance, manufacturer’s standard warranty document executed by
authorized company official. Manufacturer’s warranty is in addition to, and not a limitation of, other rights Owner may have
under Contract Documents.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 78
GUIDE SPECIFICATIONS
Specifier Note: Coordinate paragraph below with manufacturer’s warranty requirements.
C.
Warranty: Commencing on Date of Installation.
1.
Compressors: 5 years (limited).
2.
Integrated Modular Control: 3 years (limited).
3.
Other System Components: 1 year (limited).
4.
Aluminized Heat Exchangers: 10 years (limited).
5.
Stainless Steel Heat Exchangers: 15 years (limited).
PART 2 PRODUCTS
Specifier Note: Retain article below for proprietary method specification. Add product attributes, performance characteristics, material
standards and descriptions as applicable. Use of such phrases as or equal" or or approved equal" or similar phrases may cause
ambiguity in specifications. Such phrases require verification (procedural, legal and regulatory) and assignment of responsibility for
determining or equal" products.
PART 2.01
A.
ROOFTOP UNITS
Manufacturer: Lennox Industries Inc.
1.
B.
Contact: 2100 Lake Park Blvd., Richardson, TX 75080; Telephone: (800) 453−6669; website: www.lennox.com.
Proprietary Products/Systems: Lennox L Series® Unitary Air Conditioning Equipment, including the following equipment:
1.
Cabinet: Weatherproofing tested and certified to AGA [Rain test standards] and soundproofing tested to ARI 270,
dbA at [______] y (______) y (______) m free field.
a.
Heavy gauge steel panels and full perimeter heavy gauge galvanized steel base rails.
b.
Raised edges around duct and power entry openings in bottom of unit.
c.
Airflow Configuration: [Down−flow (vertical) return air] [Horizontal return airflow with Horizontal Roof Mounting
Frame] [And Horizontal Return Air Panel Kit (required when converting down−flow configured unit to horizontal
airflow)].
d.
Power Entry: Electrical [And gas] lines brought through unit base or through horizontal access knockouts.
e.
Exterior Panels: Constructed of heavy gauge, galvanized steel with 2−layer enamel paint finish.
f.
Insulation: All panels adjacent to conditioned air fully insulated with non−hygroscopic fiberglass insulation. Unit
base fully insulated.
g.
Base Rail: Full perimeter base rail with rigging holes; 3 sides with fork slots.
h.
Access Panels: Hinged for compressor/controls/heating areas, blower access and air filter/economizer access;
and, sealed with quarter−turn latching handles and tight air and water seal.
2.
Compressor:
3.
Fans, General: Centrifugal, forward curved impellers, statically and dynamically balanced. [Multi] V−belt drive with
adjustable variable pitch motor pulley.
a.
Copeland scrollt type, hermetically sealed.
a.
Condenser Fan: Low sound operating, PVC coated fan guard, direct drive propeller type fans to discharge
vertically.
b.
Condenser Fan Motor: Permanently lubricated, permanent split capacitor; totally enclosed from weather, dust
and corrosion; permanently lubricated ball bearings; resiliently mounted; overload protected.
4.
Evaporator Coils: Pressure and leak tested to 500 psi (3445 kPa), nonferrous coils with enhanced aluminum fins
mechanically bonded to durable copper tubes.
5.
Condenser Coils:
a.
Pressure and leak tested to 500 psi (3445 kPa), nonferrous coils with enhanced aluminum fins mechanically
bonded to durable copper tubes.
Specifier Note: Specify slab construction for L Series® over 6 tons (21.1 kW), excluding heat pumps.
b.
6.
[Formed construction] [Slab construction].
Air Distribution:
a.
Equipment capable of down−flow (vertical) or side (horizontal) handling of conditioned air.
b.
Optional Equipment:
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 79
GUIDE SPECIFICATIONS
Specifier Note: The following kit is required for horizontal air handling for L Series® 3 − 12 ton (10.6 − 42.2 kW) models.
1)
Horizontal conversion kit for horizontal air handling.
Specifier Note: The following kit is required for horizontal air handling for L Series®, 13 − 30 ton (45.8 − 105.6 kW) models.
2)
7.
Horizontal return air panel kit and horizontal roof mounting frame for horizontal air handling.
Filters: To meet NFPA 90A, air filter requirements [Type Class 1] [Type Class 2]; [______]% efficiency, metal framed,
[Replaceable media] [Throwaway] [Standard to unit manufacturer].
a.
Disposable 2 inch (51 mm) pleated MERV 7 rated.
b.
Disposable 2 inch (51 mm) pleated MERV 11 rated.
8.
Heat Exchanger: Removable for servicing; stainless steel optional for applications where mixed air temperature
below 45 degrees F (7 degrees C); E.T.L./C.S.A. design certified for outdoor installation.
9.
Gas Heating System:
a.
Tubular heat exchanger and inshot type gas burners constructed of aluminized steel.
b.
Direct spark ignition; electronic flame sensor controls; flame rollout switch; limit controls and automatic
redundant dual gas valve with staging control and combustion air proving switch on combustion air inducer.
Specifier Note: When LPG/propane is required, specify optional kit.
10.
11.
c.
Able to use LPG/propane [With optional kit].
d.
Complete service access provided for controls and wiring.
Electric Heating System:
a.
Available for factory or field installation.
b.
Heating elements of Nichrome bare wire exposed directly to airstream.
Refrigeration System:
a.
Self−sealing, discharge, suction and liquid line service gauge ports, freeze−stats, expansion valves and full
refrigerant charge.
b.
Copper tubing not to touch sharp metal surfaces.
c.
Compressor Circuits: Automatic reset, high pressure switch; automatic reset, low pressure switch; liquid line
filter−drier.
Cooling system capable of operating down to 0 deg. F outdoor
temperature as shipped from the factory.
d.
12.
13.
Capable of operating down to 0 degrees F (−17 degrees C) without installation of additional controls.
Supply Air Blower:
a.
[Constant air volume with adjustable pulleys] [Variable air volume with fixed pulleys and variable frequency
drive] [Variable air volume with fixed pulleys and variable frequency drive with bypass].
b.
Centrifugal supply air blower with [Permanently lubricated ball bearings and adjustable belt drive] [Sleeve
bearings and multi−speed direct drive motor].
c.
Blower assembly [Slides out of unit] [Is accessible] for servicing.
d.
Blower wheel statically and dynamically balanced.
Integrated Modular Control (IMC):
a.
Solid−state control board to operate unit.
b.
Built−in functions include: blower on/off delay; built−in control parameter defaults; service relay output; dirty filter
switch input; dehumidistat input, economizer control; [Gas valve delay between stages]; [ETM compatible];
[DDC compatible]; unit diagnosis; diagnostics code storage; indoor air quality input; low ambient controls;
minimum run time; night setback mode; smoke alarm mode; low pressure control; thermostat bounce delay;
3−digit display; degrees F or degrees C display, 2−stage heat/3−stage cool thermostat compatible and warm−up
mode; [Electric heat staging].
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 80
GUIDE SPECIFICATIONS
14.
15.
16.
Gas Heating Controls:
a.
Remote thermostat[s] as indicated.
b.
Built−in [Un] fused disconnect switch.
c.
Two stages of heating control from [Thermostat] [DDC].
d.
Supply fan to turn on [40] seconds after heating demand is received with 8 − 60 second adjustable time delay.
e.
Supply fan to turn off [120] seconds after heating demand has ended with 80 − 300 second adjustable time
delay.
f.
Adjustable delay time of [30] [Value between 30 − 160] seconds between low and high fire of 2−stage gas valve
system.
g.
Heat off delay of [100] [Value between 30 − 300] seconds after thermostat heating demand has ended.
h.
To turn off heat and keep supply air fan running if overheat limit occurs.
i.
Adjustable maximum overheat limit trip count during heating cycle of [3] [Value between 1 − 15], with digital
output, limit indicator.
j.
To report error with each occurrence of overheat limit trip and to identify limit that tripped. Error code stored in
nonvolatile memory.
k.
To shut off gas heat if flame rollout occurs and to report error identifying rollout switch.
l.
Maximum flame rollout switch trip count of [3] during heating cycle, with digital output, limit indicator. Maximum
count limit adjustable from 1 − 6 counts.
m.
To turn off heat if induced airflow is too low and to report error identifying pressure switch.
n.
Maximum induced airflow pressure switch trip count of [3] during heating cycle, with digital output, limit
indicator. Maximum count limit adjustable from 1 − 6 counts.
o.
Error reported if gas valve not energized 2 minutes after heating demand; gas valve identified.
p.
Maximum ignition failure count of [3] with digital output, limit indicator. Maximum count limit adjustable from 1 −
6 counts.
q.
To shut off gas valve if flame not sensed. Error reported and stored in nonvolatile memory.
r.
Delay between stages on gas valve.
s.
To shut off unit if gas valve is energized with no demand for heat. Error reported and stored in nonvolatile
memory.
Electric Heating Controls:
a.
Panel board with [______] stage controller.
b.
Remote thermostat[s] as indicated.
c.
Built−in [Un] fused disconnect switch.
d.
Supply Fan: Start before electric elements are energized and continue operating until bonnet temperature
reaches minimum setting. Include switch for continuous fan operation.
e.
Two stages of heating control from [Thermostat] [DDC].
f.
Supply fan to turn off [20] seconds after heating demand has ended. Time delay adjustable from 0 − 300
seconds.
g.
With delay time of [12] seconds between low and high heat stages. Time delay adjustable from 12 − 60
seconds.
h.
To turn off heat and keep supply air fan running if overheat limit occurs.
i.
Adjustable maximum overheat limit trip count of [3] during heating cycle with digital output, limit indicator.
Maximum count limit adjustable from 1 − 15 counts.
j.
Error reported and identified if overheat limit tripped. Error code stored in nonvolatile memory.
Cooling Controls:
a.
Provide [Smoke detectors in return] [Smoke detectors in supply].
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 81
GUIDE SPECIFICATIONS
Specifier Note: Specify b, c or d below.
b.
c.
[Manual] [Automatic] outside [And return] air dampers for fixed outside air quantity.
Remote controlled outside [And return] air dampers with damper operator and means for adjusting outside air
quantity.
d.
Motorized outside, return and [Automatic] [Power exhaust] [Gravity] relief dampers with spring return damper
operator and control package to automatically vary outside air quantity. Outside air and exhaust air dampers,
normally closed.
e.
Tight−fitting parallel blade dampers with neoprene or suitable gaskets, synthetic bushings and 1% maximum
leakage.
f.
Damper Operation: 24 V, spring return motor with gear train sealed in oil.
g.
Mixed Air Controls: [Maintain 55 degrees F (13 degrees C)] [Indicated] mixed air temperature (adjustable).
h.
Up to 2 stages of cooling from [Thermostat] [External DDC controller] without need for additional controls.
i.
Up to 3 stages of cooling when used with relay and [3−stage thermostat] [DDC controller].
Specifier Note: Specify article j" when used with Lennox L Connection Network Building Automation System.
j.
k.
l.
m.
n.
o.
p.
q.
r.
s.
t.
u.
v.
w.
x.
y.
z.
Up to 4 stages of cooling.
To allow blower on delay of up to 60 seconds after cooling demand is received. Default value of zero.
To allow blower off delay of up to 240 seconds after cooling demand has ended. Default value of zero.
Minimum compressor on time of [240] seconds on 3−phase units, adjustable between 60 − 510 seconds.
Minimum compressor off time of [300] seconds on single−phase units, adjustable from 60 − 510 seconds.
Default maximum high pressure switch trip occurrence during cooling or dehumidification cycle of [3]. Trip
occurrence limit adjustable from 1 − 8 occurrences. If maximum limit reached, compressor locked out and
digital output for service activated.
Default maximum low pressure switch trip occurrence during cooling or dehumidification cycle of [3]. Trip
occurrence limit adjustable from 1 − 8 occurrences. If maximum limit reached, compressor locked out and
digital output for service activated.
Low pressure trip read delay of [5] minutes if compressor off time has been less than 4 hours and outdoor
temperature is less than 70 degrees F (21 degrees C). Delay adjustable from 0 − 34 minutes. Temperature set
point adjustable from 10 degrees F (−12 degrees C) to 100 degrees F (38 degrees C). Compressor off time
adjustable from 1 − 6 hours.
Low pressure trip read delay of [15] minutes if compressor off time has been 4 hours or greater and outdoor
temperature is less than 70 degrees F (21 degrees C). Delay adjustable from 0 − 34 minutes. Temperature set
point adjustable from 10 degrees F (−12 degrees C) to 100 degrees F (38 degrees C). Compressor off time
adjustable from 1 − 6 hours.
Low pressure trip read delay of [2] minutes if compressor off time has been less than 4 hours and outdoor
temperature is 70 degrees F (21 degrees C) or greater. Delay adjustable from 0 − 34 minutes.
Temperature set point adjustable from 10 degrees F (−12 degrees C) to 100 degrees F (38 degrees C).
Compressor off time adjustable from 1 − 6 hours.
Low pressure trip read delay of [8] minutes if compressor off time has been 4 hours or greater and outdoor
temperature is 70 degrees F (21 degrees C) or greater. Delay adjustable from 0 − 34 minutes.
Temperature set point adjustable from 10 degrees F (−12 degrees C) to 100 degrees F (38 degrees C).
Compressor off time adjustable from 1 − 6 hours.
Each pressure switch trip occurrence (either high or low) to record error in nonvolatile memory and identify
compressor circuit.
Low outdoor air temperature compressor lockout set point of 0 degrees F (−18 degrees C) for each compressor
circuit. Low outdoor temperature limit set point individually adjustable for each compressor circuit from 80
degrees F (27 degrees C) to −30 degrees F (−34 degrees C).
Maximum allowable evaporator freeze−stat trip occurrence of [3] during cooling demand with limit adjustable
from 1 − 4 occurrences. Control to shut off compressor each time freeze−stat trip occurs and record error code
in nonvolatile memory. If maximum limit reached, compressor locked out and digital output for service
activated.
Condenser Fan Control:
1)
On units with multiple condenser fans, [6] second time delay between condenser fan shutoff and restart
to prevent reverse rotation of fan. Time delay adjustable between 0 − 16 seconds.
2)
On units with 4 condenser fans, first stage low outdoor temperature set point of 55 degrees F (13 degrees
C) that reduces airflow through condenser by turning off some fans. Set point adjustable between 60
degrees F (16 degrees C) and 10 degrees F (−12 degrees C).
3)
On units with 6 condenser fans, second stage low outdoor temperature set point of 40 degrees F (4
degrees C) to reduce airflow through condenser by turning off all fans. Set point adjustable between 60
degrees F (16 degrees C) and 10 degrees F (−12 degrees C).
4)
On units with 6 condenser fans, condenser fan on delay of [2] seconds. Adjustable between 0 − 240
seconds.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 82
GUIDE SPECIFICATIONS
Specifier Note: Edit article below to suit project requirements. If substitutions are permitted, edit text below. Add text to refer to
Division 1 Project Requirements (Product Substitutions Procedures) Section.
PART 2.02
A.
PRODUCT SUBSTITUTIONS
Substitutions: No substitutions permitted.
PART 3 EXECUTION
PART 3.01
MANUFACTURER’S INSTRUCTIONS
Specifier Note: Article below is an addition to the CSI SectionFormat and a supplement to MANU−SPEC. Revise article below to suit
project requirements and specifier’s practice.
A.
Compliance: Comply with manufacturer’s written data, including product technical bulletins, product catalog installation
instructions, product carton installation instructions and manufacturer SPEC−DATA® sheets.
PART 3.02
A.
EXAMINATION
Site Verification of Conditions: Verify substrate conditions, which have been previously installed under other sections, are
acceptable for product installation in accordance with manufacturer’s instructions.
PART 3.03
INSTALLATION
A.
Install [Packaged rooftop units] [And] [Commercial packaged, gas/electric and electric/electric heat pumps] in accordance
with manufacturer’s instructions, on roof curbs [Provided by manufacturer] [As indicated].
B.
Run drain line from cooling coil condensation drain pan to discharge [Over roof drain].
PART 3.04
FIELD QUALITY CONTROL
Specifier Note: Use the following Articles only when manufacturer’s field services are desired to verify the quality of the installed
components. Establish the number and duration of periodic site visits required by Manufacturer and specify below. Consult
Manufacturer for services required. Delete if field services are not required.
A.
Have manufacturer of products supplied under this Section review Work involved in handling, installation/application,
protection and cleaning of its product[s], and submit written reports in acceptable format to verify compliance of Work with
Contract.
B.
Manufacturer’s Field Services: Provide manufacturer’s field services consisting of product use recommendations and
periodic site visits for inspection of product installation in accordance with manufacturer’s instructions.
C.
Schedule site visits to review Work at stages listed:
D.
1.
After delivery and storage of products, and when preparatory Work on which Work of this Section depends is
complete, but before installation begins.
2.
[Twice] during progress of Work at [25%] and [60%] complete.
3.
Upon completion of Work, after cleaning is carried out.
Obtain reports within [3] days of review and submit.
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 83
GUIDE SPECIFICATIONS
PART 3.05
PERFORMANCE VERIFICATION
Specifier Note: Commissioning must ensure performance verification of every part of the unit including, but not necessarily limited to,
the following components, as a factory−built and packaged unit: (a) mixing chamber or plenum with outside air and return air dampers;
filters; either (i) heating coil or (ii) gas−fired heating unit; DX refrigeration system (generally with air−cooled condenser DX cooling coil
with drain pan); humidifier; supply fan with motor and drive; exhaust air dampers; weatherproof curbs [Incorporating vibration
isolators].
A.
General:
1.
Perform rooftop air handling unit verification in accordance with Section 01750 Starting and Adjusting supplemented
as follows:
2.
Settings:
a.
Set outside air and return air dampers for minimum outside air.
b.
Set outside air and return air dampers for percentage of outside air required by design and repeat
measurements of fan capacity.
3.
Measurements:
a.
Measure supply fan capacity.
b.
Measure pressure drop of each component of air handling unit.
c.
Measure DBT, WBT of SA, RA, EA.
d.
Measure air cooled condenser discharge DBT.
e.
Measure flow rates (minimum and maximum) of SA, RA, EA.
f.
Measure radiated and discharge sound power levels under maximum heating demand and under maximum
cooling demand with compressors running.
g.
Measure DX refrigeration system performance as specified.
4.
Simulations:
a.
Simulate maximum cooling load and measure refrigerant hot gas and suction temperatures and pressures.
b.
Simulate maximum heating load and:
1)
Verify temperature rise across heat exchanger.
2)
Perform flue gas analysis.
3)
Verify combustion airflow to heat exchanger.
4)
Simulate minimum heating load and repeat measurements.
5.
Control Strategies:
a.
Verify operating control strategies, including:
1)
Heat exchanger operating and high limit.
2)
Early morning warm−up cycle.
3)
Freeze protection.
4)
cycle operation, temperature of changeover.
5)
Alarms.
6)
Voltage drop across thermostat wiring.
7)
Operation of remote panel, including pilot lights, failure modes.
6.
Operation and Adjustment:
a.
Check for smooth, vibrationless correct rotation of supply fan impeller.
b.
Adjust impeller speed as necessary and repeat measurement of fan capacity.
c.
Reduce differences between fan capacity at minimum and maximum outside air less than [5]%.
d.
Reduce difference between fan capacity at full cooling and fan capacity at full heating to less than [5]%.
e.
OAD: Verify for proper travel.
f.
Use smoke test to verify no short−circuiting of EA, relief air to outside air intake.
g.
Check for smooth, vibrationless, correct rotation of power exhaust impeller.
h.
Check capacity of heating unit.
i.
Refer to other sections of these specifications for PV procedures for other components.
PART 3.06
COMPLETION AND CLEANUP
A. Upon completion and verification of performance of installation, remove surplus materials, excess materials, rubbish, tools
and equipment.
END OF SECTION
L Series Packaged Gas/Electric − 13 to 30 Tons / Page 84
APPLICATION GUIDE
CONTROLS
IMC M1−7
AFTERMARKET ZONING SYSTEM INTERFACE
Introduction
Lennox’ seventh generation premium rooftop unit (RTU) controller, the Integrated Modular Controller (IMC) version M1−7,
along with a variable frequency drive (VFD) option on certain L Series® and S−Classt RTUs, increases the ability of premium
Lennox RTUs to be applied to a variety of zoning systems. The type of zoning system to be used dictates the type of RTU and
the requirements for the zoning control system. The following explains each basic system and how the IMC must interface
with an aftermarket zoning control system to meet the requirements of each application.
Lennox units in single zone and constant volume bypass applications may utilize an aftermarket unit controller as
supervisory controller for the RTU. The IMC runs in thermostat mode and is primarily useful for diagnostic purposes, allowing
the aftermarket controller to directly monitor and control heat/cool staging, the bypass damper, zone dampers, economizer
damper, etc. When the IMC is used in thermostat mode, a maximum of two stage heating and three stage cooling are
available. An optional Four Stage Control (FS1) board may be added to allow four stages of heating and cooling control.
Supervisory control must be provided by the Lennox IMC to minimize complication and standardize control on Lennox
VFD−controlled variable air volume (VAV) RTUs. In this configuration, the IMC controls the VFD based on static pressure in
the supply duct. It controls the economizer, and stages compressors based on discharge air temperature. The aftermarket
controller simply sends calls for cooling or heating based on setpoint and schedule conditions. The IMC also has many
options for controlling single−stage, 50% power exhaust fans; two−stage, 100% Power exhaust fans; or modulating power
exhaust fans.
NOTE − Please refer to the IMC Manual (M1−7 Version 5.0x) for additional details.
Interface Definition
With a aftermarket control system interface, the IMC requires four digital inputs to control the rooftop unit: G (blower enable),
OCP (occupied), Y1 (enables discharge cooling), and W1 (enables discharge heating).
This application minimizes the controls expertise required to create a viable interface. Further, it creates a consistent,
standardized approach conducive to support and trouble−shooting on a broad basis without the need for substantial
knowledge of the IMC, VFD, bypass, or aftermarket controllers or systems.
SG − Packaged Gas / Electric − 40 Ton / Page 85
APPLICATION GUIDE
CONTROLS
IMC M1−7
AFTERMARKET ZONING SYSTEM INTERFACE
Constant Volume Bypass RTU Wiring Summary
(Aftermarket Supervisory Control)
24VAC Digital Signals
Ventilation Demand
G
Occupied Demand
Aftermarket
RTU Controller
L Series / S-Class RTU
w/M1-6 or M1-7 IMC
TB1
OCP
Cooling Demand
Y1
Heating Demand
TB18
W1
Common
C
Bypass Damper
2-10V , 2V Full
Open
Supply Static
Pres. Sensor
Optional Building
Static Pres. Switch or
Sensor
Variable Air Volume RTU Wiring Summary
(IMC Supervisory Control)
24VAC Digital Signals
Ventilation Demand
Aftermarket
RTU Controller
L Series / S-Class RTU
w/ M1-7 IMC
TB1
G
Occupied Demand
OCP
Cooling Demand
Heating Demand
Common
Y1
W1
TB18
C
Variable
Frequency Drive
2-10V , 10V Full
Open (or Bypass
Damper as
Shown Above )
SG − Package Gas / Electric − 40 Ton / Page 86
Supply Static
Pres. Sensor
Optional Building
Static Pres. Switch or
Sensor
APPLICATION GUIDE
CONTROLS
IMC M1−7
AFTERMARKET ZONING SYSTEM INTERFACE
Sequence of Operation
IMC Supervisory Control
Operation when IMC blower (G) input is energized
When a G signal is present, the IMC controls the VFD or bypass damper to hold a constant supply duct static
pressure based on the input from the IMC pressure sensor using a PID control loop. For increased flexibility,
the IMC has separate adjustable static pressure setpoints for ventilation, cooling, heating and smoke
alarms. These set points reside in the memory of the IMC, have factory default settings, and may be
adjusted in the field prior to start up.
Operation when IMC occupied (OCP) input is energized
When an OCP signal is present the IMC adjusts the fresh air damper to either a fixed minimum position or
allows it to modulate based on a CO2 sensor. The CO2 sensor can be wired directly to the IMC, to another
controller that can monitor the sensor and pass a signal to the IMC for damper control, or to both the IMC and
another device for monitoring through the desired man−machine interface while the IMC maintains damper
control. During morning warm−up/cool−down the IMC keeps the fresh air damper closed based on the IMC
configuration settings selected. The set points for minimum and maximum damper position setting and CO2
control reside in the memory of the IMC, have factory default settings, and may be adjusted at start up. They
cannot be adjusted using the aftermarket controls system.
Operation when IMC first stage cooling (Y1) input is energized
When a Y1 signal is present the IMC controls up to 4 stages of cooling (depending on RTU size) to maintain a
cooling discharge air temperature setpoint. These stages include mechanical cooling, or outdoor air for
cooling with an economizer. The discharge air temperature setpoint resides in the IMC, has a factory default
setting, and may be adjusted at start up. It cannot be adjusted using the aftermarket controls system. The
IMC has advanced discharge−air cooling reset options selected at start up based on return air temperature
and/or outside air temperature. Outside air reset saves energy by gradually increasing the discharge air set
point as outside air temperature decreases. Return air reset reduces potential for overcooling if the zoning
system is misapplied or has an abnormal condition or dominant zone. The reset gradually increases
discharge air temperature as return air temperature decreases.
Operation when IMC first stage heating (W1) input is energized
When a W1 signal is present, the IMC controls up to 4 stages of heating (depending on RTU size) to maintain
a heating discharge air temperature. The heating discharge air temperature set point resides in the IMC, has
a factory default setting, and may be adjusted at start up. It cannot be adjusted using the aftermarket controls
system. The IMC has advanced discharge air heating reset options based on return air temperature and/or
outside air temperature. Outside air reset saves energy by gradually decreasing the discharge air set point
as outside air temperature increases. Return air reset reduces possibility of overheating if the zoning system
is misapplied, has an abnormal condition or dominant zone. The reset gradually decreases discharge air
temperature as return air temperature decreases.
Power Exhaust Fan Operation
The IMC has many power exhaust fan control options that include single−stage, two−stage and modulating
control depending on how the unit is equipped. Stage control options can be triggered based on fresh air
damper positions, pressure switches, or a pressure analog sensor. Modulating control for units with VFD
powered exhaust fans are typically modulated to maintain return or building static pressure, but can be
staged. Set points and operation settings for controlling power exhaust fans reside in the IMC, have factory
default settings, and may be adjusted at start up. They cannot be adjusted using the aftermarket controls
system.