P6SD Series
3%%24HREE0HASE0ACKAGED
!IR#ONDITIONING
4ON5NITS
FEATURES and BENEFITS
s 3TATEOFTHEART#OPELAND3CROLL compressor is standard
equipment.
s 0ROVEN)NDUSTRY3TANDARD#OMPONENTS Easier service
and availability.
s 486 Externally equalized. Provides precise refrigerant
control under varying load conditions.
s (IGH0RESSURE3WITCH Protects against abnormally high
system pressures.
The P6SD Series packaged units are high efficiency self
contained cooling units that can be installed on a roof or
on a slab. The convertible unit design makes installations
simple in all applications. Units are ETL and ETLc listed.
The unit is truly designed with the contractor and the end
user in mind.
s ,IQUID,INE&ILTER$RIER Insures clean and dry refrigeration
system.
s %XTERNALLY!CCESSIBLE3ERVICE0ORTS Quick access to
refrigerant system without disrupting operation.
s #OMPACT&OOTPRINT Easy to handle and transport.
s #ONVERTIBLE !IR $ELIVERY Horizontal or downflow to
accommodate rooftop or horizontal application.
s (EAVY'AUGE &ULL 0ERIMETER "ASE 2AILS Facilitates
forklift handling and curb mounting.
s 'ALVANIZED 3TEEL #ABINET with polyurethane finish
provides 950 hour salt spray protection.
s 7IRE 'UARD #OATED WITH %ARTH &RIENDLY %POXY AND
0LASTIC-ESH(AIL'UARD will never rust and protect the
coil from being damaged by balls, lawnmowers, hail etc.
s #ORROSION2ESISTANT $RAIN 0AN Quickly drains away
evaporator condensate.
s 1UIET/PERATION,OW6IBRATION. 20" fan blade combined
with custom venture condenser fan opening.
s !CCESSTO#ONTROLSAND-AJOR#OMPONENTS Easy in
and out service.
s 3ERVICE!CCESS0ANELS To all major components and
the compressor. Designed to make servicing easier for
the Contractor.
s &ACTORY)NSTALLED&ILTER2ACK 1" or 2" Capable.
s %ASYTO)NSTALL Electric heat strip provides 9 or 15 KW
of heat output.
s !CCESSORIES Roof curbs, economizers, fresh air dampers
and more.
MODEL IDENTIFICATION CODE
P
6
S
D
-
X
36
C
Electrical Code
C = 208/230-60-3
D = 460-60-3
Application
P = Air Conditioning
Packaged Unit
Nominal Capacity
x 1000 Btu
Series
D = 13 SEER
R410A TXV
Square Duct
DIMENSIONS
24.9
.75" NPT Female
Drain Connector
Top View
DOWNFLOW
SUPPLY DUCT
OPENING
47.5
CG
13.5
16
16
13.5
B
13.3
12
12
23.5
DOWNFLOW
RETURN DUCT
OPENING
A
P6SD Models
2
Center of Gravity
Model Number
P6SD-
Unit Weight
X36
X48
X60
405
415
480
A
B
29.5
29.5
30.0
26.0
26.5
27.5
Height (in inches)
C
with base rails
35.3
35.3
39.3
DIMENSIONS (Continued)
1 4/5
1 3/4 Ø Power Entry (Capped)
1 1/4 Ø Power Entry
22/25 Ø Control Wiring Entry
30
27 1/5
23 3/5
4
Side View
FILTER
ACCESS
PANEL
5
HORIZONTAL
SUPPLY DUCT
OPENING
C
HORIZONTAL
RETURN DUCT
OPENING
4
CONDENSING
COIL
13 1/2
16
8
13 1/2
16
13 7/10
12 9/20
11 3/4
4
22 3/4
55 4/5
Back (Duct) View
3
SPECIFICATIONS
P6SD Models - 208/230V Three Phase
Model
Number
Performance
Capacity -Cooling BTUH
Efficiency - SEER
EER (Btuh/watt)
Electrical Rating - 60 Hz
Phase
Operating Voltage Range
Compressor Data
Volts
Rated Load Amps
Lock Rotor Amps
Indoor Blower
Type
Motor - HP / RPM
Motor - Amps
Outdoor Fan
Motor - HP / RPM
Motor - Amps
Fan Diameter / CFM
Refrigerant Charge - Oz. R-410A
Net Weight lbs.
Shipping Weight lbs.
Filters (Field Installed)
Style
Size (Qty)
X36C
P6SD
X48C
X60C
34,200
13.30
11.2
46,000
13.00
11.5
58,000
13.30
11.00
3
187 - 253
3
187 - 253
3
187 - 253
208 / 230
11.6
73
208 / 230
15.3
83
208 / 230
17.4
110
DD / 3
1/4 - 1075
1.3
DD / 3
1/2 - 1080
3.1
Fixed Torque
3/4
6.0
1/4 - 1100
1.2
20/3600
110
405
415
1/4 - 1100
1.2
20/3800
168
415
425
1/4 - 1100
1.2
20/3800
192
480
490
Disposable
Disposable
Disposable
16 x 25 x 1 (2)
18 x 25 x 1 (2)
Field convertible to two inches
BLOWER PERFORMANCE
P6SD Models
Model Number
P6SDHigh
X36
Medium
* Low
High
X48
Medium
* Low
Tap T1
* * Tap T2
X60 * Tap T3
Tap T4
Tap T5
External Static Pressure Drop - inches water column
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
1610 1562 1504 1442 1365 1295 1214 1109
1367 1320 1271 1205 1138 1065
968
845
1153 1102 1043
990
912
831
731
618
2361 2278 2218 2141 2066 1976 1870 1758
2026 1982 1935 1889 1822 1744 1660 1554
1584 1568 1532 1489 1445 1387 1322 1236
1515 1450 1380 1350 1300 1250 1200 1160
1580 1520 1460 1400 1360 1300 1260 1230
1740 1690 1650 1600 1540 1500 1460 1390
1960 1910 1840 1820 1780 1740 1700 1600
2090 2050 2010 1975 1940 1900 1850 1790
* Denotes factory set cooling speed
** Denotes factory set electric heating speed
NOTE: Airflow performance is with a dry coil
4
SPECIFICATIONS
P6SD Models - 460V Three Phase
Model
Number
Performance
Capacity -Cooling BTUH
Efficiency - SEER
EER (Btuh/watt)
Electrical Rating - 60 Hz
Phase
Operating Voltage Range
Compressor Data
Volts
Rated Load Amps
Lock Rotor Amps
Indoor Blower
Type
Motor - HP / RPM
Motor - Amps
Outdoor Fan
Motor - HP / RPM
Motor - Amps
Fan Diameter / CFM
Refrigerant Charge - Oz. R-410A
Net Weight lbs.
Shipping Weight lbs.
Filters (Field Installed)
Style
Size (Qty)
X36D
P6SD
X48D
X60D
34,200
13.30
11.2
46,000
13.00
11.5
58,000
13.30
11.00
3
414 - 506
3
414 - 506
3
414 - 506
460
6.4
38
460
6.9
41
460
8.6
52
DD / 3
1/4 - 1075
0.8
DD / 3
1/2 - 1080
1.7
Fixed Torque
3/4
3.2
1/4 - 1100
0.6
20/3600
110
405
415
1/4 - 1100
0.6
20/3800
168
415
425
1/4 - 1100
0.6
20/3800
192
480
490
Disposable
Disposable
Disposable
16 x 25 x 1 (2)
18 x 25 x 1 (2)
Field convertible to two inches
5
AIR CONDITIONER ELECTRICAL DATA
P6SD SERIES - 460V - 3 PHASE MODELS
P6SD SERIES - 208/230V - 3 PHASE MODELS
MODEL
NUMBER
P6SD-
X36C
X48C
X60C
SINGLE CIRCUIT
HEATER
INSTALLED
NOMINAL KW
MCA
MOP
0
17.0
25
9
28.7
30
15
46.8
50
0
21.6
35
9
28.7
35
15
46.8
50
0
29
45
9
15
29
46.7
45
50
SINGLE CIRCUIT
MODEL
NUMBER
P6SD-
HEATER
INSTALLED
NOMINAL KW
MCA
MOP
X36D
0
9
15
9.4
15.1
24.5
15
15
25
X48D
0
9
15
10.9
16.2
25.7
15
15
30
X60D
0
9
15
14.6
14.9
24.3
15
15
25
NOTE: P6SD 3 & 4 ton models have PSC motors. Since the power wires run through the heater plug, keep the blower and heater on different
circuits when adding a heater kit.
HEATER APPLICATION MATRIX
TONNAGE
& PHASE
UNIT
3,4, & 5 TON
3 Phase 208/230V
P6SD
3,4, & 5 TON
3 Phase 460V
NOMINAL
KW
HEATER KIT
MODEL
HEATER KIT
PART NUMBER
BREAKERS
REQUIRED
9
H3HK-009Q-01B
903854B
None
15
H3HK-015Q-01B
903855B
None
9
H3HK-009S-01B
903850B
None
15
H3HK-015S-01B
903851B
None
P6SD
MODEL IDENTIFICATION CODE
H
3
HK
015
-
H
0
1
A
Rev
Heater
Stages
3-Pkgd. Units
4-Air Handlers
5-7-1/2 & 10 Ton
Pkg. Units
6
Heater Kit
Electric
Heater KW
No. of Breakers
Electric Code
Q=208/240-3-60
S=460-3-60
P6SD ACCESSORIES
Description
Part Number
Roof Curb (8”)
547830
Roof Curb (14”)
547831
Roof Curb (18”)
547850
Roof Curb (24”)
547851
Supply/return transition, 16”
547834
Supply/return transition, 18”
547835
Concentric diffuser, flush, 16”
547836
Concentric diffuser, flush, 18”
547837
Concentric diffuser, step down 16”
547838
Concentric diffuser, step down 18”
547839
Manual Fresh Air Damper
547832
Motorized Fresh Air Damper
547840
Economizer, downflow w/filter modulating, enthalpy controlled
558870
Economizer, horizontal modulating, enthalpy controlled
547841
Power Exhaust for use with downflow economizer (208/230 3 Phase) Special Order
555578
Power Exhaust for use with horizontal economizer (208/230 3 Phase) Special Order
555580
Power Exhaust for use with downflow economizer (460V 3 Phase) Special Order
555579
Power Exhaust for use with horizontal economizer (460V 3 Phase) Special Order
555581
HOOD TYPE HAIL GUARD 34” X 76” (3 or 4 Ton)
547846
HOOD TYPE HAIL GUARD 38” X 76” (5 Ton)
547847
Differential enthalpy sensor kit
920233
Control, CO2 sensor, wall mount
547848
Duct Smoke Detector Photo Elec
558863
Multi Signal Control
558866
Sampling Tube DST 3, 2-4'
558864
Sampling Tube DST 5, 4-8'
558865
Low Pressure Switch Kit
913551
Low Ambient Kit
918837
Freezestat
917108
Duct Adaptor, 14" Round (2 each)
913812A
Outdoor Thermostat Kit
913852
Circuit Breaker, Three Phase (3-Pole)
913740
7
P6SD EXPANDED RATINGS
P6SD-X36
O.D.T
CFM E.D.B. E.W.B.
80
62
80
67
900
80
72
75
63
80
62
80
67
1000 80
72
75
63
80
62
80
67
1100
80
72
75
63
T.C.
35.5
38.7
42.3
36.0
36.4
39.4
43.1
36.7
37.7
40.7
44.4
37.9
65°F
S.C.
27.4
22.3
17.3
21.7
29.1
23.6
18.1
22.9
31.9
26.0
19.7
25.2
K.W.
2.20
2.23
2.27
2.21
2.22
2.24
2.27
2.21
2.22
2.25
2.29
2.22
T.C.
34.2
37.1
40.6
34.6
35.0
37.8
41.4
35.2
36.2
39.0
42.6
36.4
75°F
S.C.
27.2
22.2
17.2
21.6
29.7
24.3
18.9
23.5
32.1
26.3
20.1
25.4
K.W.
2.42
2.45
2.49
2.43
2.43
2.46
2.50
2.43
2.44
2.48
2.52
2.45
T.C.
32.8
35.5
38.9
33.1
33.5
36.2
39.6
33.7
34.7
37.3
40.7
34.8
85°F
S.C.
27.3
22.4
17.6
21.7
29.1
23.7
18.4
22.9
31.4
25.7
19.6
24.8
K.W.
2.67
2.70
2.75
2.68
2.68
2.71
2.76
2.68
2.69
2.73
2.77
2.70
T.C.
31.2
33.9
37.1
31.5
31.9
34.4
37.8
32.0
33.1
35.5
38.8
33.1
95°F
S.C.
26.8
22.0
17.2
21.3
28.8
23.5
18.2
22.7
31.2
25.6
19.6
24.7
K.W.
2.95
2.98
3.03
2.95
2.96
2.99
3.04
2.96
2.97
3.00
3.05
2.97
T.C.
29.6
32.1
35.2
29.8
30.3
32.6
35.8
30.4
31.6
33.6
36.7
31.3
105°F
S.C.
28.3
21.7
17.0
19.7
28.7
23.5
18.4
22.8
30.5
25.5
19.6
24.4
K.W.
3.27
3.30
3.34
3.28
3.28
3.31
3.35
3.28
3.30
3.32
3.37
3.29
T.C.
27.9
30.1
33.1
28.0
28.7
30.7
33.7
28.6
29.9
31.6
34.5
29.4
115°F
S.C.
26.6
20.4
17.4
21.2
28.4
23.7
18.5
22.7
29.8
25.6
19.9
24.5
K.W.
3.64
3.67
3.71
3.64
3.65
3.67
3.72
3.65
3.66
3.69
3.73
3.66
P6SD-X48
O.D.T
CFM E.D.B. E.W.B.
80
62
80
67
1250
80
72
75
63
80
62
80
67
1400
80
72
75
63
80
62
80
67
1550
80
72
75
63
T.C.
47.9
52.0
56.7
48.5
49.1
53.1
57.8
49.5
50.2
54.1
58.9
50.5
65°F
S.C.
37.2
30.2
23.3
29.4
39.8
32.0
24.5
31.2
42.8
34.4
26.2
33.4
K.W.
2.82
2.84
2.86
2.82
2.82
2.84
2.87
2.83
2.83
2.85
2.87
2.83
T.C.
46.1
49.9
54.4
46.5
47.3
51.0
55.4
47.5
48.4
51.9
56.4
48.4
75°F
S.C.
37.0
30.0
23.2
29.2
40.6
33.0
25.6
32.0
43.1
34.8
26.7
33.7
K.W.
3.12
3.15
3.18
3.12
3.13
3.16
3.19
3.13
3.14
3.16
3.20
3.14
T.C.
44.2
47.7
51.9
44.5
45.2
48.7
52.9
45.5
46.2
49.6
53.8
46.3
85°F
S.C.
37.2
30.3
23.6
29.4
39.7
32.2
24.8
31.2
42.1
34.4
25.9
33.2
K.W.
3.45
3.49
3.54
3.46
3.46
3.50
3.54
3.46
3.47
3.51
3.55
3.47
T.C.
42.1
45.5
49.5
42.4
43.1
46.3
50.4
43.3
44.2
47.1
51.1
44.0
95°F
S.C.
36.6
29.8
23.1
28.8
39.3
31.9
24.6
30.8
41.8
34.3
26.0
33.1
K.W.
3.84
3.87
3.92
3.84
3.85
3.88
3.93
3.85
3.86
3.89
3.95
3.86
T.C.
40.0
43.1
46.9
40.2
41.0
43.9
47.7
41.0
42.2
44.6
48.4
41.7
105°F
S.C.
38.5
29.4
22.8
26.8
39.2
32.3
24.8
31.1
40.8
34.1
26.0
32.8
K.W.
4.27
4.31
4.35
4.28
4.29
4.32
4.36
4.29
4.30
4.33
4.37
4.29
T.C.
37.7
40.6
44.2
37.9
39.0
41.4
44.9
38.6
40.1
42.0
45.5
39.2
115°F
S.C.
36.3
28.0
23.4
29.0
38.6
32.3
25.0
31.1
39.9
34.4
26.4
33.0
K.W.
4.77
4.80
4.85
4.77
4.78
4.81
4.86
4.78
4.80
4.82
4.86
4.79
P6SD-X60
O.D.T
CFM E.D.B. E.W.B.
80
62
80
67
1600
80
72
75
63
80
62
80
67
1750
80
72
75
63
80
62
80
67
1900
80
72
75
63
T.C.
61.8
66.8
72.9
62.1
63.0
67.8
73.7
63.2
64.0
68.7
74.3
64.1
65°F
S.C.
47.9
39.3
30.5
38.2
50.5
41.2
31.6
40.0
53.6
43.6
33.5
42.3
K.W.
3.74
3.83
3.92
3.74
3.79
3.87
3.97
3.81
3.85
3.92
4.02
3.85
T.C.
59.4
63.9
69.7
59.6
60.5
64.9
70.4
60.6
61.4
65.8
70.8
61.4
75°F
S.C.
47.5
39.1
30.3
38.0
51.4
42.3
33.0
41.0
53.8
44.1
34.1
42.6
K.W.
4.11
4.19
4.29
4.11
4.16
4.24
4.35
4.16
4.21
4.29
4.39
4.21
T.C.
56.8
61.1
66.4
56.9
57.8
62.0
67.0
57.8
58.7
62.7
67.5
58.5
85°F
S.C.
47.7
39.4
30.8
38.2
50.2
41.2
32.0
39.8
52.6
42.9
33.1
41.4
K.W.
4.53
4.61
4.72
4.54
4.59
4.67
4.77
4.59
4.64
4.72
4.81
4.64
T.C.
54.1
58.1
63.1
54.2
55.1
58.9
63.5
54.9
56.0
59.6
64.0
55.6
95°F
S.C.
46.9
38.6
30.1
37.3
49.6
40.7
31.7
39.3
52.2
42.8
33.0
41.2
K.W.
5.02
5.09
5.20
5.02
5.07
5.14
5.24
5.07
5.13
5.20
5.29
5.12
T.C.
51.3
55.0
59.5
51.2
52.2
55.7
59.9
51.9
53.1
56.3
60.5
52.5
105°F
S.C.
49.2
38.0
29.7
34.5
49.4
40.7
31.8
39.2
51.3
42.4
32.8
40.7
K.W.
5.57
5.65
5.75
5.57
5.62
5.70
5.79
5.62
5.68
5.75
5.84
5.66
T.C.
48.4
51.7
55.7
48.2
49.3
52.3
56.2
48.8
50.4
52.8
56.7
49.3
115°F
S.C.
46.4
36.0
30.4
37.0
48.8
40.6
31.9
39.0
50.1
42.6
33.1
40.8
K.W.
6.19
6.26
6.36
6.18
6.24
6.31
6.41
6.23
6.30
6.36
6.46
6.28
For complete catalog information including submittals,
energy calculations, dimension drawings, and more go to
www.ReznorHVAC.com or call 800-695-1901.
© 2014 Reznor LLC.
Reznor is registered in at least the United States. All other trademarks are the property of their respective owners.
All rights Reserved. Printed in U.S.A.
266E-1014
Form S-P6SD-3
Note: In keeping with our policy of continuous
product improvement, we reserve the right to alter,
at any time, the design, construction, dimensions,
weights, etc., of equipment information shown here.