INSTALLATION INSTRUCTIONS FIELD INSTALLED ECONOMIZER ACCESSORY INSTALLATION INSTRUCTIONS MODEL 2EE04703224 FOR 6.5 THRU 12.5 TON SINGLE PACKAGE EQUIPMENT MODEL AIR CONDITIONERS General The instruction provides all the necessary information to properly field install this economizer on the above indicated equipment. Economizer Model 2EE04703224 has a single input solid state enthalpy sensor that provides automatic 100% outdoor air capability with 2% leakage. Refer to the respective unit wiring diagram for information regarding electrical circuitry on the economizer. A relief air damper for barometric air balance is provided with each basic unit and is mounted on the face of the return air damper section. Refer to the basic unit installation instruction for additional information. PANELS TO BE REMOVED RETURN AIR DAMPER FRESH AIR DAMPER Step 1: Verify all unit parts in box. a. b. c. d. 1 ea. - Return Air Damper 1 ea. - Fresh Air Damper 4 ea. - 24 58“ x 23 18“ x 1” Mist Eliminator Filter (shipped inside Return Air Damper) 1 ea. - Hood Package 1 ea. - Barometric Relief Hood 1 ea. - Barometric Relief Damper 1 ea. - Fresh Air Hood 1 ea. - Hardware Bag: 48 ea. - Type A #10 - 16 x ½ Screws 14 ea. - Self tapping #10 - 16 x ½ Screws 2 ea. - Seal Tight #10 - 32 x ½ Screws w / washers 4 ea. - Filter Clips 10 ft. - 18 x 12 Gasket HOOD PACKAGE FIELD INSTALLED ECONOMIZER ACCESSORY INSTALLATION INSTRUCTIONS MODEL 2EE04703224 INSTALLATION INSTRUCTIONS Step 2: Remove the Enthalpy Control and Discharge Air Sensor from the return air damper and save for later installation (Steps 3 and 16). ENTHALPY CONTROL DISCHARGE AIR SENSOR Step 3: To assemble the fresh air hood the following will be needed. 34 ea. - Type A #10 - 16 x ½ Screws 2 ea. - Seal Tight #10 - 32 x ½ Screws w/ washers GASKET 4 ea. - Filter Clips 10 ft. - 18 x 12 Gasket (10) (7) (6) GASKET Follow these steps: A. Take (1 and 2) and use the 2 Seal Tight (11) screws with washers and screw though (2) into (1) and tighten. B. Take (3 and 4) and screw through (2) into (5) (3 and 4) using the Type A screws. C. Take (5 and 6) and screw through (7) into (5 and 6) using the Type A screws. D. Take (8) and put to the inside of (2 and 7) and secure with Type A screws. E. Take (9) and place tabs into slots of (2 and 7) and bend tabs down on the outside of (2 and 7). F. Take (10) and place flanges with the three holes over (2 and 7) and secure with Type A screws. G. Take (11) and secure to (2, 7, 10) with Type A screws. H. Take filter clips and screw to (9 and 10) with Type A screws. I. Place gasket on the back flanges of (2, 7, 8, 10) J. Install filters in the hood and fasten clips to FILTER CLIPS hold in place. Set Fresh Air Hood to the side for use in Step 14. (4) (9) GASKET (2) (1) (3) (8) ENTHALPY SENSOR (FROM STEP 2) 23 5 16 35 1516 25 1116 (2) FIELD INSTALLED ECONOMIZER ACCESSORY INSTALLATION INSTRUCTIONS MODEL 2EE04703224 INSTALLATION INSTRUCTIONS Step 4: To assemble the Barometric Relief Hood use the Type A #10 - 16 x ½ screws (Qty 14) provided. Follow these steps: (5) A. Take (1 and 2) put the flange of (1) to the inside of (2) and screw in place. B. Take (3) and screw in place like step A. C. Take (4) and place flanges over (2 and 3) and secure. D. Take (5) and do the same as step C. (4) Set Barometric Relief Hood to the side for use in Step 13. 31 1116 18 (3) 1 2 (2) 12 (1) 1 4 21 916 Step 5: Remove the return air duct cover and the two (2) rear panels from the end of the unit as shown. Keep screws to use later in Steps 7 and 15. HORIZONTAL DUCT OPENING WITH COVER AND END PANELS REMOVED HOLES TO ATTACH FRESH AIR DAMPER Step 6: Install the fresh air damper into the horizontal return air duct opening as shown. Using the self tapping #10 - 16 x ½ screws provided secure to duct connection (two on each side). The two holes with bushings will be on the right hand side and the damper bracket will be on the damper bottom inside the unit. TWO HOLES WITH BUSHINGS DAMPER BRACKET FIELD INSTALLED ECONOMIZER ACCESSORY INSTALLATION INSTRUCTIONS MODEL 2EE04703224 INSTALLATION INSTRUCTIONS Step 7: Slide the return air damper into the unit as shown using some of the screws removed in Step 5. Step 8: Secure the return air damper to the unit with the screws removed in Step 6 though the slotted holes in the damper section. Do Not tighten screws at this time. Step 9: Connect the linkage from the return air damper to the fresh air damper. The linkage rod is shipped connected to the return air damper. To connect the linkage to the fresh air damper, open the fresh air damper and insert the rod through the opening in the damper bracket. With the rod through the fresh air damper bracket, close the fresh air damper tightly, and tighten the set screw on the fresh air damper bracket as shown. Note: Linkage rod should be flush with the back of the return air damper bracket. Step 10: Route the blue and violet wire from the Logic Module “+” and “S” terminals through the lower bushing provided in the fresh air damper as shown. These wires will be connected to the Enthalpy Control mounted on the fresh air hood as shown in Step 14. INSTALLATION INSTRUCTIONS FIELD INSTALLED ECONOMIZER ACCESSORY INSTALLATION INSTRUCTIONS MODEL 2EE04703224 Step 11: Install the barometric relief damper over the screws on return air damper. Using the “keyhole” slots on the barometric relief damper, place the barometric relief damper over the screws and slide down into the slots. Do Not tighten screws at this time. Step 12: Plug the economizer cable into the unit as shown. The “jumper” plug that ships with the unit should be removed and saved in the control compartment for future needs. ECONOMIZER CABLE 3” Step 13: Install the assembled Barometric Relief Hood as shown. Using the “keyhole” slots on the barometric relief hood, place the barometric relief hood over the screws and slide down into the slots and tighten screws in place. This is the time to tighten all screws that were previously not tightened. FLANGE ON HOOD SIDE Step 14: Install the assembled Fresh Air Hood as shown using #10 - 16 x ½ self tapping screws. Place fresh air hood approximately 3” down from top of the unit and flush with flange on hood side. Route wire to Enthalpy Control in the lower right hand corner of the Fresh Air Hood as shown. Connect the violet wire to the “+” terminal and the blue wire to the “S” terminal. FIELD INSTALLED ECONOMIZER ACCESSORY INSTALLATION INSTRUCTIONS MODEL 2EE04703224 INSTALLATION INSTRUCTIONS Step 15: Reinstall the top rear panel which was removed in Step 5 of the unit using the remaining screws also removed in Step 5. TOP REAR PANEL Step 16: The Discharge Air Sensor installs in the blower compartment of the unit. Open the access door to the blower and you will see a cable on the left side. The cable has two wires with insulated connectors that the Discharge Air Sensor plugs into. These wires are shown in the photo. Plug the Discharge Air Sensor wires into those provided inside the unit, and using a wire tie, strap the Discharge Air Sensor to the cable as shown below. DISCHARGE AIR SENSOR WIRES CONTROL CONTROLoPOINT APPROX. F (o C) CURVE AT 50% RH A 73 (23) B 70 (21) C 67 (19) D 63 (17) WIRE TIE DISCHARGE AIR SENSOR APPROXIMATE DRY BULB TEMPERATURE - oF ( oC) 1 HIGH LIMIT CURVE FOR W6210D, W7210D, W7459D. SUPERCEDES 06-19-00 JULY 24, 2000 FORM# YKIEC29B S7/P7 ECONOMIZER SECTION SOCKET /PLUG CONNECTION DAS DISCHARGE AIR SENSOR S12/P12 POWER EXHAUST SOCKET/PLUG CONNECTION M5 POWER EXHAUST CONTACTOR RC CAPACITOR ES1 POWER EXHAUST END SWITCH NOTES: 1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL AND/OR NATIONAL CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT. 2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSED IMPROPER AND DANGEROUS OPERATION. IF ANY OF THE WIRE, AS SUPPLIED WITH THE UNIT MUST BE REMOVED. IT MAY BE REPLACED WITH TYPE 105 DEGREE C, GOO VOLT WIRE OR EQUIVALENT CLEARLY RENUMBERED FOR IDENTIFICATION. VERIFY PROPER OPERATION AFTER SERVICING. 3. WHEN ECONOMIZER IS INSTALLED REMOVE PLUG WITH JUMPER WIRE 816/Y