LENNOX INSTALLATION INSTRUCTIONS STANDARD MIXING BOX INDUSTRIES INC. ECONOMIZERS LXIMB05 JUNE 7, 2004 EMD17 - 95 THRU 275 INSTALLATION INSTRUCTIONS FOR EMD17 MIXING BOX USED WITH CB17, CBH17 95 THROUGH 275 TON SERIES UNITS I—SHIPPING AND PACKING LIST RETURN AIR DAMPER Package 1 of 1 contains: 1 - Mixing Box Assembly 1 - Wiring Diagram Sticker 3 - Wire Ties 12 - #10 - 18 x ½ SDST Screws II—APPLICATION EMD7 Mixing Boxes are used for automatic sensorcontrolled introduction of outdoor air into the system through an electro-mechanically controlled damper. III—INSTALLATION 1—Disconnect all power to unit. FRESH AIR DAMPER 2—Determine the application upflow or horizontal. Note: Wiring and controls are the same regardless of size or application. CONTROL ACCESS PANEL Figure 1 A—For Upflow Application. 3—Attach mixing box over return opening with screws provided. See Figure 2. SUPPLY AIR OUTLET 4—Remove control access panel on mixing box and unit. 5—Remove and discard existing jumper (P3) on unit wiring harness. Route mixing box harness and mixed air sensor wiring over indoor air blower and make necessary connections. Mixing box wiring harness connector (P4) plugs into mating jack (J3) of unit wiring harness or appropriate control module jack. Use wire ties to secure excess coiled wire to blower motor capacitor leads. See Figure 8 for jack/plug pin designations. WARNING DO NOT CONNECT ECONOMIZER PLUG P4 TO UNIT JACK J3 WHEN USING A TEMPERATURE CONTROL SYSTEM (I.E. W973 CONTROL, W7400 CONTROL, WARM-UP KIT, OR NIGHT KIT). CONTROL DAMAGE COULD RESULT. SEE CONTROL WIRING DIAGRAM SECTION FOR PROPER JACK/PLUG CONNECTIONS. RETURN AIR INLET CONTROL ACCESS Figure 2 6—Replace control access panel on mixing box and unit. SUPPLY AIR DUCT 7—Place return air duct and fresh air duct to mixing box and seal weather tight. See Figure 3. Note: Mixing box section maybe rotated 180o for bottom return air connection. See Figure 4. RETURN AIR DUCT 8—Locate mixing box wiring diagram sticker next to unit wiring diagram. 9—Restore power to unit. FRESH AIR DUCT Figure 3 SUPPLY AIR DUCT FRESH AIR DUCT RETURN AIR DUCT Figure 4 Note: Wiring and controls are the same regardless of size or application. B—For Horizontal Application. 3—Attach mixing box over return opening with screws provided. See Figure 5. 4—Remove control access panel on mixing box and unit. 5—Remove and discard existing jumper (P3) on unit wiring harness. Route mixing box harness and mixed air sensor wiring over indoor air blower and make necessary connections. Mixing box wiring harness connector (P4) plugs into mating jack (J3) of unit wiring harness or appropriate control module jack. Use wire ties to secure excess coiled wire to blower motor capacitor leads. See Figure 8 for jack/plug pin designations. RETURN AIR INLET CONTROL ACCESS Figure 5 WARNING DO NOT CONNECT ECONOMIZER PLUG P4 TO UNIT JACK J3 WHEN USING A TEMPERATURE CONTROL SYSTEM (I.E. W973 CONTROL, W7400 CONTROL, WARM-UP KIT, OR NIGHT KIT). CONTROL DAMAGE COULD RESULT. SEE CONTROL WIRING DIAGRAM SECTION FOR PROPER JACK/PLUG CONNECTIONS. RETURN AIR DUCT SUPPLY AIR DUCT 6—Replace control access panel on mixing box and unit. 7—Place return air duct and fresh air duct to mixing box and seal weather tight. See Figure 6. Note: Mixing box section maybe rotated 180o for bottom return air connection. See Figure 7. 8—Locate mixing box wiring diagram sticker next to unit wiring diagram. FRESH AIR DUCT Figure 6 9—Restore power to unit. SUPPLY AIR DUCT FRESH AIR DUCT RETURN AIR DUCT Figure 7 15-PIN PLUG TERMINAL DESIGNATIONS NOTE-Flattops indicate pins 1, 3 and 14. Male (Plug) Reference Tab Indicates Pin 1 and top of plug Female (Jack) Flattop opposite pin 1 is pin 3 Reference Tab Indicates Pin 1 and top of plug Single flattop on opposite side of plug is pin 14 NOTE-To find a certain pin number, locate pins 1, 2 or 3 and add 3 for each row as you proceed downward Figure 8 2—On a call for heat during night operation (requires optional night thermostat with clock), damper will remain closed. IV—OPERATION A—Cooling Mode 1—On a call for cooling, with ambient temperature and humidity above enthalpy control set point damper will open to minimum vent position and cooling demand is satisfied by compressor. 2—On a call for cooling, with ambient temperature and humidity below enthalpy control set point the damper will modulate to control supply air temperature at 55° F (13° C). If additional cooling is required, compressor will be energized through second stage of thermostat. B—Heating Mode C—Enthalpy Control The enthalpy control senses both temperature and humidity or the heat content of the outside air. It controls whether outdoor air is brought into the system. When the heat content of the outside air is below control setpoint, the control permits outdoor dampers to operate. When the heat content rises above control setpoint, the control closes outdoor dampers to minimum position. The recommended setpoint is “A”. If Economizer is allowing air which is too warm or too humid to enter the system, control may be changed to a lower setpoint (B, C, or D). Refer to Chart 1. 1—On a call for heat during day operation, damper will open to the minimum vent position. Chart 1 V—SYSTEM CHECK 1—Disconnect main power to unit. HONEYWELL DAMPER MOTOR 2—Install jumper to auxiliary contacts of blower contactor in main unit control box. 3—Turn thermostat control to “OFF” position. 4—Remove control access cover. See Figure 1. 5—Install jumper on damper motor terminal T and T1. See Figure 8. 6—Restore power to unit. Damper should drive to fully opened position (requires 1 ½ minutes for full travel). Observe travel for proper damper operation. 7—Disconnect power to unit. Damper should spring return to closed position. 8—Remove jumper installed on Step 5 then restore power to unit. Adjust minimum vent position on potentiometer on control module. See Figure 9. Replace control access cover. 9—Disconnect power to unit and remove jumper on auxiliary contacts of blower contactor in main unit control box. Restore power to unit. Figure 9 VI—MAINTENANCE 1— Damper motor is prelubricated and does not require further lubrication. 2—Make visual inspection of dampers and linkage assemblies during routine maintenance. ENTHALPY CONTROL SETPOINT ADJUSTMENT MINIMUM POSITION CONTROL MODULE Figure 10