Specifications SPECIFICATIONS TABLE OF CONTENTS 1. ITEM............................................................................................................................ 2 1.1. SCOPE .......................................................................................................... 2 1.2. STANDARDS ................................................................................................ 2 1.3. TESTS ........................................................................................................... 2 2. MATERIAL .................................................................................................................. 2 2.1. BREAKER TYPE AND CONSTRUCTION ..................................................... 2 2.2. RATINGS....................................................................................................... 3 2.3. LOW-VOLTAGE COMPARTMENT ................................................................ 3 2.4. CURRENT TRANSFORMERS....................................................................... 5 2.5. CONTROL PANEL ........................................................................................ 6 2.6. COMPARTMENT CONSTRUCTION ............................................................. 6 2.7. MOUNTING REQUIREMENTS ...................................................................... 6 2.8. BUSHINGS AND TERMINALS ...................................................................... 7 3. DRAWINGS AND DATA .............................................................................................. 7 3.1. INFORMATION TO BE FURNISHED WITH BID ........................................... 7 3.2. APPROVAL SUBMITTAL............................................................................... 7 3.3. FINAL SUBMITTAL ........................................................................................ 7 4. WORKMANSHIP, MATERIAL, AND FINISH ............................................................... 8 APPENDIX I Bid No. 16-46 Page 1 of 10 Specifications 1200 Amp 15 kV Outdoor Substation Circuit Breakers with Microprocessor Relays 1. ITEM 1.1. SCOPE This Specification is intended to cover the electrical and mechanical requirements necessary to furnish seven (7) 15kV vacuum circuit breakers with factory installed relays and meters for use in the District’s Plain and Wapato substations. Circuit breakers furnished under this specification shall be three-phase, single throw, outdoor, free-standing type, with seismic bracing and rated for service on a three-phase, 60 Hz, effectively grounded system at a nominal 12.5kV line-to-line operating voltage. Circuit breakers furnished under this specification shall be operated under normal altitude conditions in accordance with ANSI C37.04, however, circuit breakers shall be subject to operation under temperatures ranging from -40°C to 45°C (-40°F to 113°F). 1.2. STANDARDS All circuit breakers furnished under this specification shall meet or exceed the electrical and mechanical requirements of the latest applicable IEEE, ANSI, and NEMA standards for equipment of this class and type. The circuit breakers must be capable of meeting all design and production tests outlined in ANSI C37.09- latest, and be the latest generally accepted design of the manufacturer. Exposed parts at line potential shall meet or exceed the requirements of the latest NESC for unguarded line parts. 1.3. TESTS Design and production tests shall be in accordance with the requirements of ANSI C37.09, C37.09a, and NEMA SG4 for circuit breakers and ANSI C57.13 for current transformers. Each current transformer shall withstand a low-frequency dielectric test. All certified test reports shall be included with final drawing submittals. 2. MATERIAL 2.1. BREAKER TYPE AND CONSTRUCTION 2.1.1. The vacuum circuit breaker shall be capable of automatic reclosing following a trip. The breaker shall be electrically operated from remote 120/240VAC and 48VDC power sources, with 48VDC control circuit tripping and closing. 2.1.2. There shall be only one (1) high-voltage compartment containing the three (3) vacuum interrupters and three (3) sets of current transformers. The high voltage compartment shall be weatherproof and dust resistant. Heaters with Bid No. 16-46 Page 2 of 10 Specifications thermostatic control shall be provided, and shall be sufficiently rated to maintain satisfactory operation of the vacuum interrupters. 2.1.3. There shall be only one (1) low-voltage compartment containing the operating mechanism, and panel mounted relay and meter as described in this specification. The low voltage compartment shall be weatherproof and dust resistant. The compartment doors shall have wind props and provisions for padlocking the door handles. Heaters with thermostatic control shall be provided, and shall be sufficiently rated to maintain satisfactory operation of internal equipment. 2.1.4. Breaker shall be free-standing, unit mounted, and suitable for mounting on a flat concrete pad. 2.1.5. Breaker shall have seismic bracing. 2.2. RATINGS 2.2.1. Vacuum circuit breakers furnished under this specification are intended for use under usual service conditions, except for temperatures listed in section 1.1, and will be used for the protection and switching of three-phase, 60Hz, effectively grounded 12.47kV overhead or underground distribution feeder circuits. 2.2.2. Breakers shall have minimum ratings and electrical characteristics as defined in ANSI C37.04 and listed in ANSI C37.06 including, but not limited to, the following: Rated Maximum Voltage Rated Continuous Current at 60Hz Min. Interrupting Capability at Maximum kV Basic Impulse Level 60 Hz one-minute withstand dry 60 Hz 10 second withstand wet Closing and Latching Nominal Operating Frequency Interrupting time Duty Cycle Closing Coil Voltage Tripping Coil Voltage Motor Voltage Heater Voltage 15 kV or higher 1200A RMS 20 kA Symmetrical 110 kV 50 kV 45 kV 52 kA 60 Hz 3 cycles O-0.3s-CO-3m-CO 48 VDC 48 VDC 240 VAC 120 VAC 2.3. LOW-VOLTAGE COMPARTMENT The low-voltage compartment shall include the following: Bid No. 16-46 Page 3 of 10 Specifications 2.3.1. One loss of AC relay, 27AC, shall be mounted and wired in the breaker. One (1) “a” and one (1) “b” contact shall be wired for the District’s use. 2.3.2. SEL-351-S, part number 0351S6X3D3G5221. Relays must be ordered Factory Configured with OUT104 configured as a ‘b’ contact, OUT107 configured as an additional alarm contact. 2.3.3. Test switch, ABB TYPE FT-19R, part number FR3G014001485 2.3.4. Bitronics M650, KVAM, part number M650B3U510 2.3.5. Test switch, ABB TYPE FT-1, #C129A514G01 2.3.6. GE ET-16 red, white, and green indicating lamps with LED cluster bulbs 2.3.7. Auxiliary relay, TYPE SG, 48VDC, DPDT with solid cover, ABB part number 293B254A18 2.3.8. An emergency manual trip (ANSI device 69) shall be provided and shall be readily accessible on the exterior mechanism side of the breaker. The actuating handle shall be clearly labeled and be operable without opening any doors or covers. The emergency manual trip device shall trip the breaker and prevent breaker closing until manually reset. 2.3.9. The operating mechanism shall have an indicator for open and closed status, and an indicator showing whether the mechanism is charged or discharged. Both indicators shall be visible from the outside of the breaker 2.3.10. The operating mechanism shall have an operations counter. The operations counter shall be visible from the outside of the breaker. 2.3.11. A minimum of six (6) spare electrically separate reversible auxiliary contacts are required. All spare auxiliary contacts shall be wired to terminal blocks. 2.3.12. Terminal blocks for auxiliary contacts, control wiring, and current transformers shall be readily accessible for the District’s wiring connections. Terminal blocks shall be Marathon 1512STD or approved equivalent for auxiliary and control wiring, and shall be Marathon 1506SC or a p p ro ve d equivalent for current transformer circuits. Position 6 on each shorting terminal block shall be connected to ground. Bid No. 16-46 Page 4 of 10 Specifications 2.3.13. All devices, terminal blocks, and wiring shall be adequately identified. Nameplates shall be attached on or near each device to designate proper device names. 2.3.14. All wiring shall be a minimum #12 AWG SIS stranded tinned copper, except for CT wiring, which shall be #10 AWG SIS stranded tinned copper. All component wiring shall be terminated at terminal blocks utilizing ring terminal connectors. 2.3.15. A manually operated knife switch and thumb safe fuse holder shall be provided to disconnect the 48VDC control circuit. The fuse slots shall be slugged at both polarities. 2.3.16. A similar manually operated disconnect device shall be provided for AC motor and heater circuit protection. 2.3.17. Control circuits shall be such that closing and tripping operations will be completed when the contacts have been only momentarily closed. The breaker shall be electrically and mechanically trip free and non-pumping for both manual and automatic operations. 2.3.18. Each operating mechanism shall operate to open and close all three phases simultaneously. 2.3.19. The bottom of the compartment shall have a removable plate with minimum dimensions of 8” X 14” for entry of control conduits. 2.3.20. A utility light with hand or door actuated switch and a 120VAC GFI duplex receptacle shall be provided in the compartment. 2.3.21. A thermostatically controlled heater shall be sufficiently rated to maintain satisfactory operation of internal equipment. provided, 2.3.22. The compartment doors shall have wind props and provisions for padlocking the door handles. 2.4. CURRENT TRANSFORMERS The circuit breaker shall be equipped with bushing current transformers as follows: 2.4.1. Two (2) sets of current transformers shall be located on the load side of the breaker (bushings 2, 4, 6). The first set shall be 2000:5 MR, relay accuracy class 10C400 (per NEMA and ANSI Standards), with a minimum continuous thermal current rating Bid No. 16-46 Page 5 of 10 Specifications factor (RF) of 1.5. This set shall be installed in the “X” CT location. The second set shall be 600:5 MR, metering accuracy class 0.3B1.8, with a minimum RF of 2. This set shall be installed in the “Y” CT location. 2.4.2. One (1) set of current transformers shall be located on the source side of the breaker (bushings 1, 3, 5). This set shall be 600:5 MR, relay accuracy class 10C400, with a minimum RF of 2. 2.5. CONTROL PANEL 2.5.1. Panel Arrangement See Appendix I. for typical panel arrangement. 2.6. COMPARTMENT CONSTRUCTION 2.6.1. The compartment roof top cap and high and low voltage compartments shall be weatherproof and dust resistant. 2.7. MOUNTING REQUIREMENTS 2.7.1. The circuit breaker shall be equipped with mounting frames to provide a 9 foot clearance from the base to live parts, capable of adjustment for an approximate 9 to 11 foot clearance. The frame and supports shall be designed to meet seismic requirements at maximum adjustable height. 2.7.2. All non-energized metal parts shall be bonded so that one ground connection will ground all normally dead parts. Grounding shall not rely on any structural frame bolted joint. 2.7.3. The breaker shall have two (2) grounding pads, with provisions for NEMA 2 hole connectors, located at diagonally opposite corners. Each grounding pad shall be capable of conducting the maximum short circuit current rating of the breaker. 2.7.4. The circuit breaker mounting legs shall be drilled for concrete pad attachment. 2.7.5. The breaker shall be equipped with lifting eyes loading/unloading the entire unit, and shall be shipped completely assembled. Bid No. 16-46 for Page 6 of 10 Specifications 2.8. BUSHINGS AND TERMINALS 2.8.1. Six (6) roof bushings shall be provided. Bushings shall be ANSI 70 light gray in color. 2.8.2. Bushings shall have a minimum rating of 15kV, 110kV BIL per applicable ANSI and NEMA standards. 2.8.3. Bushing terminals shall be threaded stud type, and each bushing shall be equipped with a 4-hole NEMA, bronze or copper-to-aluminum rated, stud-toflat connector. 3. DRAWINGS AND DATA 3.1. INFORMATION TO BE FURNISHED WITH BID The following drawings and data shall be furnished with bid or quote: 3.1.1. Dimensioned outline drawing including base details, total weight, calculated moments at foundation, and other information required for installation and foundation design. 3.1.2. Breaker ratings, typical control schematic and diagrams, and spare parts list. 3.1.3. Bushing current transformer characteristics, ratings, type, quantity and location. 3.1.4. Bushing outline, ratings, manufacturer and type. 3.1.5. Three (3) references representing U.S. electric utilities which have purchased and installed the proposed circuit breaker, and have operated the proposed circuit breaker for at least five (5) years on their system. 3.2. APPROVAL SUBMITTAL The following drawings and data shall be submitted for approval within 45 calendar days after award: 3.2.1. Outline drawings, Arrangement drawings 3.2.2. Schematic diagrams 3.2.3. Wiring diagrams 3.3. FINAL SUBMITTAL The following drawings and data shall be furnished at time of breaker shipment: 3.3.1. One (1) copy of all approved drawings and instruction books for installation, operation, and maintenance shall be bound, indexed, and shipped with the breaker. 3.3.2. Two (2) copies of the above documentation shall be mailed to the engineer at the following address: Chelan County PUD Bid No. 16-46 Page 7 of 10 Specifications 327 N. Wenatchee Ave., Bldg. B Wenatchee, WA 98801 Attn: Jack Nieborsky 3.3.3. Final drawings shall also be provided electronically in AutoCAD R2010 or previous version. 4. WORKMANSHIP, MATERIAL, AND FINISH The finish of the equipment shall be clean, and all metal surfaces usually finished shall be smooth turned. All nuts and bolts shall have Unified National series threads. Where applicable, metal parts shall be hot double-dipped galvanized. Surfaces that require painting shall be thoroughly cleaned and painted with rust inhibitive epoxy paint. The finish coat shall be ANSI 70 sky gray. Total paint thickness shall be 3.0 mils. Remainder of this page intentionally left blank. Bid No. 16-46 Page 8 of 10 Appendix I Specifications Panel Arrangement Bid No. 16-46 Page 9 of 10