8- 66 KV CIRCUIT BREAKERS, 66 KV CTS AND ISOLATORS 1.1 Circuit Breakers 1.1.1 Applicable Standards 1.1.2. Parameters 1.1.3.1 1.1.3.2 : IEC 62271-100/BS 5311 / IS 13118 : a) Type of circuit breaker SF6, Outdoor b) c) d) e) f) g) h) Rated current Rated short circuit breaking current Short time withstand for 1 sec. Auto reclosing No. of poles Operating duty Rated breaking time 3 pole O –0.3 sec. – CO – 3 min -CO 3 cycles i) Power system particulars As per requirements j) No. of auxiliary contacts 6 NO+6 NC k) Out-of-phase breaking current l) Line charging breaking current 25 % of rated short circuit breaking current 10A m) Auxiliary supplies 48 V DC 630 A 26.2 kA 26.2 kA General Requirements a) Circuit breakers shall be three-phase type, supplied with a common base; factory installed inter-phase wiring and common control cubicle. b) Circuit breakers shall be capable of clearing short line faults with the impedance behind the bus corresponding to the rated fault current. c) Circuit breakers shall be suitable for 3-phase auto reclosing. Operating Devices a) Anti-pumping features shall be provided with breaker. b) Two trip coils shall be provided for 66 kV breakers. The trip coils shall have sufficient continuous rating to cater to the trip coil supervision relay current. c) As specified for line breakers, operating mechanism shall be suitable for high speed reclosing. It shall be non-pumping electrically and mechanically, under every method of closing (except during manual tripping of a breaker for maintenance). d) A mechanical indicator shall be provided inside the operating mechanism box to show open and closed positions, visible through a glass window from ground level. An operation counter shall also be provided. (a) A closing release shall operate correctly at all values of voltage between 80% and 110 % of the rated voltage. A shunt trip shall operate correctly under all operating conditions of the circuit breaker upto the rated breaking capacity of the circuit breaker and at all values of supply voltage between 50 % and 110 % of rated voltage. (b) Two stage pressure switches shall be provided to monitor SF6 gas pressure inside the interrupting chambers. The first stage shall initiate alarm of the breaker and blocking of closing. The second stage shall initiate blocking of tripping. (c) Provision shall be made for attaching an operation analyser to perform speed tests after installation of the breakers at site. 1.1.4 Operating Mechanism 1.1.4.1 Operating Mechanism shall be spring-operated type complete with motor, opening spring, closing spring with limit switch for automatic charging and all necessary accessories. 1.1.4.2 As long as power is available to the motor, a continuous sequence of at least 10 closing and opening operations shall be possible. After failure of power supply to the motor, at least one open-close-open operation of the circuit breaker shall be possible. 1.1.4.3 Breaker operation shall be independent of the motor operation, which shall be used solely for compressing the closing spring. 1.1.4.4 Motor rating shall be such that it requires a maximum of 15 seconds for fully charging the closing spring. 1.1.4.5 Closing action of the circuit breaker shall compress the opening spring to keep it ready for tripping. 1.1.4.6 When closing springs are discharged, after closing a breaker, they shall automatically be charged for the next operation. Facility for manual charging of closing springs shall be provided. 1.1.4.7 Mechanical interlocks shall be provided in the operating mechanism to prevent discharging of closing springs when the breaker is already in the closed position. Provision shall be made to prevent a closing operation to be carried out with the springs partially charged. 1.1.5 Operating mechanism control 1.1.5.1 Operating mechanism shall normally be operated by remote electrical control. Electrical tripping shall be performed by shunt trip coils. Provision shall be made for local electrical control. 'Local/Remote' selector switch shall be provided in the operating mechanism cubicle. 1.1.5.2 A conveniently located emergency tripping lever shall also be provided for local tripping of the breaker. A local manual-closing device, which can easily be operated from the ground, shall also be provided for maintenance purposes. Direction of motion of handle shall be clearly marked. 1.1.6 Operating mechanism housing 1.1.6.1 Operating mechanism and all accessories shall be enclosed in a weatherproof mechanism cabinet of hot dip galvanised sheet steel construction, the thickness of which shall not be less than 2 mm. Hinged doors giving access to the mechanism at the front and sides shall be provided. Suitable gaskets shall be provided to make the mechanism housing waterproof and dust-proof. Padlock and duplicate keys shall be provided. 1.1.6.2 Common marshalling box with necessary tubing and cables shall be provided. A light point suitable for 11 W CFL lamp with pin type holder and door switch and one 15A, 240 V, AC socket outlet shall be provided in the housing. 1.1.7 Bushing/Insulators 1.1.7.1 Puncture strength of bushings/insulators shall be greater than the dry flashover value. When operating at normal rated voltage, there shall be no electric discharge between the conductors and bushing/insulator, which would cause corrosion or damage to conductors, insulators or supports. No radio interference shall be caused by the bushings/insulators when operating at the normal rated voltage. 1.1.7.2 All iron parts shall be hot dip galvanised and all joints shall be airtight. Surface of the joints shall be trued-up; porcelain parts by grinding and metal parts by machining. 1.1.7.3 All current carrying contact surfaces shall be silver faced. Silver facing shall not be less than one mil in thickness. 1.1.8 Fittings/Accessories All the fittings and accessories necessary for ensuring satisfactory operation as per design and O&M requirements shall be considered to be part of Scope/Responsibility. 1.1.9 Tests 1.1.9.1 All routine tests shall be carried out as per the latest applicable standards on the breaker and its accessories. Certificates of tests on bought out items such as bushings shall be furnished for approval. 1.1.9.2 Type tests, if specified and routine tests shall also be carried out on all associated equipment as per relevant standards. 1.1.9.3 In addition to the routine tests, the following tests shall be performed on each breaker: a) b) Lightning impulse withstand test Radio Interference Voltage Test (for 66kV Breakers) 1.1.9.4 Speed curves for each breaker shall be obtained with the help of a suitable Operation Analyzer to determine breaker contact movement during opening, closing, auto-recessing and trip free operation under normal as well as limiting operating conditions (of control voltage, pneumatic pressure, etc). The tests shall show the speed of contacts at various stages of operation, travel of contacts, opening time, closing time, shortest time between separation and meeting of contacts at break-make operation, etc. 1.1.9.5 A copy of the test results shall be supplied for approval before shipment of the circuit breakers. Bound copies of complete test results shall be furnished with the circuit breakers. These shall include complete reports and results of the routine test as also certified copies of type tests carried out on circuit breakers of identical design. 2.1 Isolators 2.1.1 Applicable standards : IEC 62271-102/ IS 9921 Parameters a) b) Voltage Class Rated current 66kV 630 A c) e) Rated SC breaking Rated making current of earth switch Power frequency withstand Voltage 20 kA 50 kA f) g) h) i) j) Installation No. of poles Mode of Operation No. of auxiliary contacts k) Line charging 70 kVp + altitude correction Outdoor 3 pole Motorised 12NO+12NC as spare for Client’s use 10 A 2.1.2 Base channels and other structural steel members such as operating pipes, phase coupling rods, operating mechanism boxes, bolts, pins, etc. shall be hot dip galvanised. All castings except current-carrying parts shall be made of malleable cast iron or cast steel. Grey iron shall not be used in the manufacture of any part. Manual operating handles shall be of galvanised steel. 2.1.3 Live metal parts shall be of non-rusting and non-corroding metal. Current carrying parts shall be of non-ferrous material such as aluminium or copper. Bolts, screws and pins shall be provided with lock washers, keys or equivalent locking facilities and, if on current carrying parts, shall be made of non-rusting and non-corroding metal such as copper silicon alloy. 2.14 The isolator or earthing switch shall be provided with current carrying contacts on the hinge and jaw ends and all contact surfaces shall be of silver faced copper. 2.2.1 Earthing pads 2.2.2 Each pole of the isolator shall be provided with two earthing pads of noncorroding material at opposite ends, brazed to the channel base. Flexible tinned copper earth connectors shall be provided for connecting operating handles of isolators and earthing switches to the earthing system. 2.2.3 Earthing switch 2.2.3.1 Earthing switch shall form an integral part of each pole of the isolator. Two independent earthing pads each with flexible tinned copper braids and suitable connectors for the specified size of earth conductor lead shall be provided at the hinge end of the switch. 2.2.3 Interlocks 2.2.3.1 Isolators and earthing switches shall be provided with padlocking facility to lock them in fully open or fully closed positions. Padlock with keys shall be supplied with the isolator. 2.2.3.2 Isolator and earthing switch shall be mechanically interlocked such that it will not be possible to close the earthing switch when the isolator is closed and vice versa. 2.2.3.3 Isolator shall be provided with electrical interlocking feature. This shall be in the form of bolt interlock comprising an interlock coil of latch-in type to lock the isolator-driving shaft and thus prevent isolator operation in the latch-in condition. It shall be possible to release the latch by energising the interlock coil when certain preset conditions of external interlocking scheme are fulfilled. For this purpose the Contractor shall provide facilities for wiring external interlocking contacts both in isolator opening and closing circuits. Further, a separate bypass switch or a similar facility shall be provided on the local control cabinet to facilitate emergency manual operation of isolator. Electrical interlocking arrangement shall be fail-safe type. 2.2.3.4 Typical isolator interlocks such as breaker open for opening and closing of isolator and earth switch, earth switch closing when the respective isolator is open and ensuring the bus is dead before closing the earth switch for bus earthing shall be provided. 2.2.4 Insulators 2.2.4.1 Insulators used in the assembly of isolators shall be of porcelain and of brown colour. Insulator cap and base shall be of high-grade cast steel or malleable steel casting and they shall be machine faced and galvanised. 2.2.5 Operating Mechanism and Controls 2.2.5.1 The ganging mechanism shall be provided with sufficient adjustment to allow for final alignment of the isolator blades for simultaneous operation. Adjustable stops shall be provided to prevent over-travel in both directions. The mechanism shall provide quick, simple and effective operation. 2.2.5.2 The manual operating handles shall be mounted on the base of supporting structure. Guide bearings shall be provided, if necessary, at a height of 1250 mm above grade level. Where isolator is required to be connected to high level buses, the operating rod shall be provided with guide bearings at an interval of 3 metres. All members necessary for attaching the operating mechanism and operating handles to the supporting structure and foundations shall be supplied as an integral part of the isolator. Rustproof pins and bearings of the brass bushing, ball and roller type, shall be furnished. All bearings shall be weather protected by means of covers and grease retainers. 2.2.5.3 A weather-proof galvanised sheet steel cabinet with gasketed hinged door and padlocking facility shall be provided to house driving mechanism, motor starters, control valve solenoids, auxiliary switches, etc., as applicable. All cabling from operating mechanism and auxiliary contacts to operating mechanism box shall be in the scope of supply of the Contractor and shall be carried out using 1100 V grade, 1.5 sq. mm. stranded copper conductor, PVC insulated, armoured, multicore cables or single core cables laid in heavy gauge galvanised steel conduits, unless otherwise specified. 2.2.5.4 In addition to the limit switch contacts required for control of power operated isolators, the number of spare auxiliary contacts as mentioned above (6 NO + 6 NC) shall be provided for Employer's use. The auxiliary contacts shall be of silver faced copper. The contacts shall be designed to carry 10 A continuously. All contacts shall be suitable for breaking an inductive current of 0.2 A at 220 V DC. 2.2.5.5 A local isolating switch-fuse unit/MCB for disconnection of power supply, a local/remote selector switch and a set of open/close push buttons shall be provided in the operating mechanism box for power operated isolators. 2.2.5.6 The control of power operated isolators shall be so arranged that the desired operation shall be completed when corresponding push button is pressed even momentarily. The control circuit shall be so arranged that necessary interlocks with associated breaker and earthing switch can be incorporated. 2.2.5.7 Arrangement shall be provided to permit manual operation of power operated isolators. The arrangement shall be such that when manual operating handle is in the engaged position, the power operation is made inoperative. Padlocking facility shall be provided for the manual operating handle. One detachable manual operating handle for every group of four (4) power operated isolators shall be provided. 2.2.5.8 The operating mechanism design shall be such that during the operation of the isolator, especially manual operation, when the moving blades reach the sparking distance, springs take over to give a quick, snap action closing so that the isolator closing is independent of manual efforts. Similarly, the springs must assist during the opening operation to give quick breaking feature. 2.2.5.9 Motors shall be totally enclosed, weatherproof, outdoor universal type and tropicalised. Magnetic contactor type of starters suitable for direct-on-line duty shall be provided for control of motors. 2.2.5.10 Limit switches for motor control shall be fitted on the isolator shaft, within the cabinet, to sense open and close positions of the isolator. 2.2.5.11 Adequate no. of spare terminals shall be provided in the operating cabinet for the purpose of external interlocks. 2.2.6 Supporting structures 2.2.6.1 Supporting structures for isolators shall be of hot dip galvanised steel. The Contractor shall furnish detailed dimensioned drawings indicating weights and all fixing details and relative locations of chassis, operating mechanism box and operating handles, etc. after the award of the work. 2.2.6.2 Insulators used in the isolators shall be of the sleek solid core post type made of porcelain to withstand a mechanical force of 1600 N. 2.2.6.3 Terminations shall be suitable for connection of compression terminal lugs. 2.2. Tests 2.2.7.1 All routine tests shall be conducted on completely assembled isolators, earthing switches, their operating devices and auxiliary equipment in accordance with the applicable standards. 2.2.8 Current Transformers 2.2.8.1 Applicable Standards : IEC 60044-1, 60186 /BS 7625 & 7626/IS 2705, 3156 2.2.8.2 Parameters for CTs a) Type i. 66 kV CTs : Outdoor Oil filled b) Power System details : As per protection and metering requirements c) Class of insulation : A or better d) Rated extended primary current for CTs : 120% of rated primary current e) Parameters such as no. of : cores, output, accuracy class, current and voltage ratios, etc. Will be finalized after award of contract 2.2.8.3 Specific requirements 2.2.8.3.1 Secondary terminals of voltage and current transformers shall be brought out in a weatherproof terminal box. Facility shall be provided for shortcircuiting and grounding the CT secondary at the terminal box. Glands and lugs for terminating external cable connections shall be provided. 2.2.8.3.2 Terminal and polarity marks shall be indelibly marked on each VT and CT on the associated terminals and these marks shall be in accordance with relevant standards. 2.8.3.3 Current transformers shall be provided with the following accessories including but not limited to: a) H.V. connectors for the HV conductor. b) Two earthing terminals on tanks on opposite sides for connecting to the station earthing conductors. c) Oil level gauge. d) Filling and draining plugs. e) Power factor testing terminal. f) Facility for lifting bushings and tanks. g) Insulating oil required for first filling plus 10% excess. Power factor of the transformer oil shall not exceed 0.005. Insulation oil shall comply with applicable standards. h) Rating and diagram plate as per relevant standards. 2.2.8.4 The temperature rise shall not exceed the figures given in applicable standards for operation under ambient temperature conditions specified. 2.2.8.5 The tanks/base and all exposed ferrous parts shall be hot dip galvanised conforming to applicable standards. 2.2.8.6 In the case of multi-core CTs, it shall be possible to adjust the tap settings on any core independent of the setting on the other cores, for which purpose these tappings will have to be provided on the secondary windings. 2.2.8.7 All CT cores under this Specification shall be of low reactance type. 2.2.8.8 No turn’s compensation shall be used in case of class 'PS' CTs. 2.2.8.9 In case of multiratio CTs, the minimum specified requirements in respect of VA, accuracy, Knee Point Voltage (KPV) and maximum secondary resistance specified shall be met at all taps. 2.2.8.10 Magnetising characteristics (extending well beyond KPV) and secondary impedance values shall be furnished in Schedule of particulars for all protection cores. 2.2.9 Insulators/ Bushings 2.2.9.1 Insulators/Bushings shall conform to applicable standards and shall be made of homogeneous vitreous porcelain, the glazing of which shall be of uniform brown or dark brown colour. 2.2.9.2 Oil filled insulator/ bushings shall be hermetically sealed to prevent ingress of moisture. A cushion of nitrogen gas shall be provided to allow for expansion. 2.2.10 Tests 2.2.10.1 Certificates of type tests carried out on similar CTs and VTs shall be furnished with the Bid. 2.2.10.2 All routine tests as per applicable standards shall be carried out on CTs in the presence of the Employer's representative. 2.2.10.3 Optional tests, where applicable shall be carried out by mutual agreement between the Employer and the manufacturer. 2.2.10.4 In addition, the following tests shall be carried out on CT and VT of each type a) b) c) Temperature rise test Lightning impulse test Determination of errors