SECTION 40 27 95 ELECTRIC VALVE AND GATE ACTUATORS PART 1 GENERAL 1.1 SUMMARY A. Section includes general information, products, and execution for electric valve and gate actuators. B. Related Sections: 1. SECTION 01 44 33 – MANUFACTURERS’ SERVICES 1.2 REFERENCES A. American Water Works Association (AWWA): 1. C504 – Rubber Seated Butterfly Valves 2. C542 – Electric Motor Actuators for Valves and Slide Gates 1.3 SUBMITTALS A. Shop Drawings: 1. Product data sheets for make and model. 2. Complete actuator information, descriptive literature, Specifications, and identification of materials of construction. 3. Factory mechanical drawings of the complete actuator assembly including the electric motor, pedestal and rod extensions. 4. Open/close and throttling sizing calculations. 5. Maximum torque capabilities of operator mechanism and operating torque requirement for each valve under the specified operation condition. 6. Motor and actuator characteristic data and nameplate data. 7. Actuator mechanical contactor or solid state starter Manufacturer, model number, cut-sheet, etc. 8. Factory electrical drawings showing schematic representation of the complete power and control circuitry and wiring diagrams showing all interconnections, wire designations and terminal numbers for remote operation and position indication by the OWNER. Each actuator drawing shall be identified with the respective valve number or tag number indicated in the Bill of Materials, Electric Actuator Schedule or on the P&IDs in the I&C Drawings. 9. Factory installation and services information giving full installation and adjustment instructions, and part listings for all field replaceable parts. 10. Listings of normal starting and running currents, and full nameplate data from the motor. 11. Provide all drawings in .dwg or dxf electronic format. AutoCAD Drawings shall be in accordance with DW Design Drafting Standards and shall include, but not be limited to, the Standards located online in DW’s CPPM: http://www.denverwater.org/DoingBusinesswithUs/EngineeringOverview/Capital ProjectsProceduresManual/. B. Quality Control Submittals 1. For electric actuators, certified copies of reports covering proof-of-design testing of the actuators in accordance with AWWA C542, Section 5, together with an affidavit of compliance in accordance with AWWA C542, Section 6.3, shall be submitted to ENGINEER before the actuators are shipped. C. O&M Manuals: 1. Shop Drawing Submittals as previously outlined. 2. Quality Control Submittals as previously outlined. 3. The Manufacturer shall submit installation and O&M instructions in a manual presenting full details for installation, care, and maintenance of all equipment furnished under the Contract. 4. Manual: a. O&M manuals shall be provided by the Equipment Manufacturer at least 2 weeks prior to shipment of all major equipment components. b. Each manual shall be a bound, indexed binder prepared specifically for this Project rather than general equipment instructions. c. Installation and maintenance instructions for the specific equipment, including the installation and startup sequences, maintenance items, and trouble-shooting checkpoints d. Provide printed, tabbed, and bound instructions covering all details pertaining to installation, care, and maintenance of all equipment and data. Identify all parts with a number and a description. e. Provide 3 hard copies and 3 electronic copies (pdf with sections tabbed/linked) on jump drives to the OWNER. D. Extra Materials: Furnish, box, tag, and clearly mark on exterior, identify each item with the Manufacturer’s name, description, and part number for shipment and long-term storage, and deliver the following extra materials prior to 75% of the Substantial Completion date: 1. Provide five hand-held programmers, three IR communication setups (including sensors, sensor mounting bracket, cables, etc) for laptop computer, and three licensed copies of actuator software, for the actuators. 2. Provide 2 fuses, for every actuator, of every size and type of fuse internal to the actuator. Provide one spare battery for every applicable actuator. 3. Provide one extra lockable clasp for lock out, tag out use. 1 SECTION 40 27 95 ELECTRIC VALVE AND GATE ACTUATORS E. Warranty Documentation 1. Sample warranty. 2. Warranty. F. Supplements listed in this Section. 1.4 QUALITY ASSURANCE A. Equipment Manufacturer Qualifications: A minimum of 10 years of documented experience in the Work of this Section. B. UL Compliance: Materials manufactured within the scope of UL shall conform to UL Standards and have an applied UL listing mark. C. Performance and Design Requirements: 1. General: a. Actuators and appurtenances shall be designed for the conditions and requirements as specified IN the respective valve sections. b. Liberal factors of safety shall be used throughout the design, especially in the design of parts subject to intermittent or alternating stresses. In general, working stresses shall not exceed one-third of the yield point or one-fifth of the ultimate strength of each material. 2. Valve actuators: a. Each actuator shall be designed to open or close the valve under all operating conditions. b. The actuators and gear train shall be designed for the full design head rating of the valve or gate and a maximum fluid velocity of 16 feet per second c. Valve actuators shall be provided and adjusted by the valve manufacturer. Actuator mounting arrangements and positions shall facilitate operation and maintenance and shall be determined by the Valve Manufacturer unless shown otherwise on the Drawings or directed by ENGINEER. 3. Limit switches: a. A minimum of 8 programmable limit switches shall be provided for each actuator. Limit switches shall be programmed for all status functions. D. Manufacturer's Training: 1. The actuator manufacturer shall supply a factory-trained field service representative to provide operator and maintenance training for the actuators. The representative must be a full time employee of the Manufacturer qualified to do field training presentations. 2. Training will consist of a minimum of 4 hours and should include both a classroom presentation and a field presentation. The training must be specific to the products installed and the application. 1.5 DELIVERY, STORAGE, AND HANDLING A. Delivery and handling of the valves shall be in accordance to Manufacturer’s recommendations in their O&M manual. Upon delivery, equipment shall be stored in a safe, secure area protected from damage, vandalism, and weather (e.g. sun, precipitation, and flooding). 1.6 SITE CONDITIONS A. Environmental Requirements: Materials and equipment shall be designed and constructed for continuous operation, at rated current and voltage, at 5,400 feet above mean sea level, 104°F ambient temperature and 95% relative humidity. The Equipment Manufacturer shall submit a certified letter stating that the equipment provided meets the requirement. 1.7 WARRANTY A. Manufacturer: Warranty for one year from the Substantial Completion date for the satisfactory performance and installation of the electric valve actuator system and associated appurtenances. PART 2 PRODUCTS 2.1 APPROVED MANUFACTURERS A. Rotork, IQ B. Auma: Aumatic AC.2. 2.2 MATERIALS A. Except as modified or supplemented herein, materials used in the manufacture of actuators shall be in accordance with AWWA and C542. 2.3 COMPONENTS A. Electric Actuators: 1. General: a. Electric motor-operated actuator shall be designed to develop sufficient operating torque to unseat, open and close the valve under all operating conditions specified herein. Except as modified or supplemented herein, the actuator shall be in accordance with AWWA C542. b. Electric motor-operated actuator shall be designed to move the valve or gate from fully open to fully closed position within the time specified in the Electric Actuator Schedule, under the maximum differential pressure across the valve and maximum flow conditions. c. Electric actuator shall be a completely integrated, electrically powered unit with isolated manual handwheel operation in case of power failure. Provide motor actuator with rated output torque at least 1.5 times the maximum torque required to open or close the valve at any position including seating and unseating conditions. 2 SECTION 40 27 95 ELECTRIC VALVE AND GATE ACTUATORS d. 2. Electric actuator shall include the motor, actuator unit gearing, motorized adaptor, limit switches, torque switches, declutch mechanism, manual operating handwheel, local valve position indicator, position transducer, and push button control station to allow local electric control of valve position. e. Electric actuator shall be suitable for open/close or throttling service, unless modulating service is specified in the Electric Actuator Schedule or on the P&IDs on the I&C Drawings. Electric actuator shall be suitable for Class I duty cycle, shall be suitable for operation over a temperature range of -20°F to 150°F and shall be of totally enclosed, non-ventilated construction, O-ring sealed, meeting NEMA Type 6 enclosure requirements, at a minimum of 7m submersion for 72 hours according to IP68 standards. f. The complete actuator shall be furnished fully factory wired, tested, and ready for interconnection with the electric power source and external remote control "dry-contact" interposing relays furnished by others. g. Gearing shall be grease or oil-bath lubricated. Lubricating oil shall be food grade. Ball or tapered roller bearings shall be used throughout. h. A handwheel shall be provided for manual operation with an arrow to indicate the open or close rotation. The handwheel shall not rotate during electric motor operation and operation of the handwheel shall not cause the motor to rotate. When in manual operation, the operator shall remain in this mode until the electric motor is energized, at which time the actuator shall automatically return to electric motor operation and shall remain in motor operation until manual operation is again re-engaged. The change from electric motor to manual operation shall be accomplished by a positive action declutching mechanism, which mechanically disengages the motor and motor gearing. The declutching mechanism shall be lockable with a standard padlock. A blocked or fused motor shall not prevent manual operation. It shall be impossible to place the operator directly into manual operation while the motor is running. The handwheel shall rotate in a counter-clockwise direction to close the valve. The handwheel diameter shall be selected to result in a maximum required force of 80 pounds to close or open the valve under any operating conditions. i. The valve actuator shall have an electro-mechanical reversing contactor mounted in the control enclosure, with a control power transformer furnishing control power voltage. The control power transformer shall utilize a fuse in each primary lead and one fuse in the secondary lead. The other secondary lead shall be grounded. The contactor shall be either a standard full size NEMA type horse-power rated device, or shall be a definite purpose contactor sized to provide a minimum of 50,000 full load current interruption cycles using IEC utilization Category AC-4 curves. Contactors designated as IEC type devices, which do not meet these requirements, will not be acceptable. Features: a. Open/close. b. Programmable, non-intrusive set up and calibration. 1) Externally programmable. 2) Programming performed with: a) Handheld infrared linked device. b) Local control switches and LCD. c. Self-contained unit with cast iron or aluminum alloy housing. d. Shall be integrally assembled on the applicable valve or gate by the Valve or Gate Manufacturer e. Protected from the ingress of moisture and dust when terminal cover is removed. Provide the same rating as the actuator when the terminal cover is removed. f. Enclosure to allow for temporary site storage without the need for electrical supply connection. g. Mount the actuator above the reduction gearing. h. Electronic torque sensing circuitry with independently programmed motor shutoff torque set points in either direction of travel. i. Valve travel limit switch function provided by electronic Hall Effect magnetic pulse counting circuitry. j. Rotary selector or integral pushbutton control station to provide full valve operation, using the electric motor, while operating isolated from the remote control equipment. 1) Three Position rotary selector switch local–off–remote and padlockable in any position. 2) Switch leads brought to the terminal strip: a) To allow for remote indication of switch position. b) To provide remote open and close contact power. c) To provide a means of disabling local control power. 3) Valve function rotary selector switch for open–close–stop operation: a) Operate when selector switch is in the local position. b) Field configurable for push and hold control. 4) Provide LED indicating lights: a) Red: Full open. b) Green: Full closed. 3 SECTION 40 27 95 ELECTRIC VALVE AND GATE ACTUATORS c) Red and green: Modulating. Position transducer: 1) Internally mounted, programmable. 2) 4 mA to 20 mA, scaled to 0% to 100% valve position. Uses Hall Effect measurement or absolute encoder. 3) Suitable for use with an external load impedance of up to 500 ohms. 4) Output signal at a terminal strip for connection. 5) External 24 VDC power supply input to keep current transmitter, status contacts, and LCD operational and indicating valve position when the main operator motor power source has been de-energized. 6) Actuator position shall be internally updated while the main power source is removed, including manual operation, and reflect actual position when the power is restored. l. Electric actuator control power wired out to terminals for the customer’s use. Each actuator shall be furnished with a sealed compartment containing a reversing controller, multi-tap transformer, electronic controls, and monitoring and protection modules. Reversing controllers shall be both mechanically and electrically interlocked and provided with the necessary direct-operated auxiliary contacts for required interlocking and control. The multi-tap transformer shall provide power for all internal circuits, and shall provide 120 VAC or 24 VDC power supply power wired out to terminals for remote controls. m. Electromechanical reversing contactor: 1) Mounted in the control enclosure. 2) Control power transformer furnishing control power voltage. 3) Standard full size NEMA type horsepower rated device, or a definite purpose contactor. 4) Sized to provide a minimum of 50,000 full load current interruption cycles using IEC utilization Category AC-4 curves. 5) Contactors designed as IEC type devices, which do not meet these requirements, will not be accepted. n. Remote controls: 1) Valve position and actuator status indication shall be provided by 8 contacts which can be selected to indicate any position of the valve. Contacts shall be NO or NC selectable. Contacts shall maintain and update position indication during handwheel operation. Contacts shall be rated 5 amperes, 250 VAC or 30 VDC. o. Vandal resistant, lockable cover protecting standard rotary selectors and window display. 3. Electric Motor shall: a. Be rated for an operating voltage in accordance with the Contract Documents or Electric Actuator Schedule, 60 Hz, 1.0 Service Factor, reversing, totally enclosed non-ventilated. b. Produce actuator output of 1.5 times the required valve operating torque. c. Normal operating temperature rise that does not exceed NEMA Class B standards at 5,400 feet above mean sea level. d. Ratings are for 5,400 feet above mean sea level without reducing the service factor. e. NEMA Class H Insulation. f. Anti-friction bearings, lubricated and sealed against contamination. g. Motor overload protection via thermal switches. 4. Terminal facilities: a. Terminal facilities for connection to motor leads, switches, and control and indication signals shall be provided in a readily accessible terminal compartment. The terminal compartment shall have at least 3 openings for external electrical conduits, all sized for at least 3/4 inch RGS conduit. Each terminal compartment shall be large enough to allow easy routing and termination of fifteen #14 AWG conductors. b. The terminals shall be embedded in a terminal block of high tracking resistance compound. c. The terminal compartment shall be separated from the inner electrical components of the actuator by means of a watertight seal and shall be provided with a minimum of 2 threaded cable entries with provision for a maximum of 4. Wiring supplied as part of the actuator to be contained within the main enclosure for physical and environmental protection. External conduit connections between components are not acceptable. A durable terminal identification card showing plan of terminals shall be provided attached to the inside of the terminal box cover indicating: 1) Serial number. 2) External voltage values. 3) Wiring diagram number. 4) Terminal layout. FINISHES A. Shop Painting: 1. Ferrous metal surfaces, except bearing and finished surfaces and stainless steel components of valve actuators and accessories, shall be shop painted for corrosion protection. The Valve Manufacturer's k. 2.4 4 SECTION 40 27 95 ELECTRIC VALVE AND GATE ACTUATORS 2. standard coating will be acceptable, provided it is functionally equivalent to the specified coating and is compatible with the specified field painting. The following surfaces shall be painted: Polished or Machined Surfaces Rust-preventive compound Other Surfaces Epoxy enamel Actuators and Accessories Universal primer PART 3 EXECUTION 3.1 GENERAL A. Equipment provided under this Section shall be fabricated and assembled in accordance with the Drawings, Specifications, engineering data, instructions, and recommendations of the equipment Manufacturer, unless exceptions are noted by ENGINEER. B. Actuators shall be furnished with all necessary parts and accessories in accordance with the Contract Documents or otherwise required for a complete, properly operating installation and shall be the latest standard products of a Manufacturer regularly engaged in the production of actuators. C. Governing Standards: 1. Except as modified or supplemented herein, all powered actuators shall be in accordance with AWWA C542. 2. Except as modified or supplemented herein, all manual and cylinder actuators for butterfly valves shall be in accordance with AWWA C504. D. Power Supply: Power supply to electric actuators will be in accordance with the Drawings or the Electric Actuator Schedule. E. Marking: 1. Each actuator shall be marked with the Manufacturer's name, model number, and the country of origin. An identifying serial number shall be stamped on a corrosion-resistant plate attached to the actuator. 2. Each actuator shall be factory tagged or marked to identify the actuator and the applicable valve or gate by number or service as indicated in the Electric Actuator Schedule or on the P&IDs in the Instrumentation and Control Drawings. F. Temporary Number Plates: 1. Each actuator shall be factory tagged or marked to identify the actuator and the applicable valve or gate by number or service in accordance with the Electric Actuator Schedule and on the P&IDs in the I&C Drawings. 3.2 INSTALLATION A. In accordance with the Manufacturer’s instructions and recommendations 3.3 QUALITY CONTROL A. Manufacturer's Field Services: 1. The Actuator Manufacturer shall supply a factory-trained field service representative to inspect the installation of the actuators. The representative must be a full-time employee of the Manufacturer qualified to do field service work. As specified in SECTION 01 44 33. 2. The Manufacturer's field service representative must be on-site as often as required to properly oversee the installation of the actuators and to assist with troubleshooting, and as a minimum shall be there for 24 hours during three separate trips. The representative shall also be available for providing the Manufacturer's Certificate of Proper Installation. 3.4 SUPPLEMENTS A. Supplement A – Electric Actuator Schedule END OF SECTION 5 SECTION 40 27 95 ELECTRIC VALVE AND GATE ACTUATORS ELECTRIC ACTUATOR SCHEDULE VALVE LOCATION TAG NO. SIZE (IN) SERVICE, CLASS QUINCY AVE. & IRVING ST. VAULT FV-01 42-INCH O/C, CLASS 3 ACTUATOR LOCAL CONTROLS MAINTAINED POWER SOURCE CYCLE TIME RANGE (SEC) 240V/1PH 180-300 DIRECTION OF HANDWHEEL TO OPEN RIGHT Abbreviations: OR Open Right OL Open Left SEC SecondsService: O/C = Open-Close, T = Throttling*, M = Modulating* Actuator Local Controls: Maintained = Seal-in latching contacts Momentary = No seal-in latching contacts *Specify Class 1, 2, 3 or 4 per AWWA C542 (60, 100, 600, 1200 Starts/Hour) 1 SECTION 40 27 95 SUPPLEMENT A ELECTRIC VALVE AND GATE ACTUATORS