low voltage
QL - Series Miniature Circuit Breakers
DIN mount
(grey body)
Dual mount
(black body)
Dual mount + Auxiliary
(black body)
Features
Applications
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
AC Circuit Breaker
Hydraulic-Magnetic technology
100% rating capability, independent of ambient temperature
One, two and three pole (UL). One, two, three pole and
1+N, 3+N (VDE).
VDE and CCC approved, CE certified
UL listed (CSA / UL 489)
Ratings 0.1 to 25 A
Optional Auxiliary Switch / Trip Alarm - factory fitted
(6.5 mm wide)
Optional Shunt Trip (no approvals)
Wide range of time delays and operating currents
Precision tripping characteristics
Ultra compact – 13 mm wide module
Trip indication with mid-trip handle
Reset immediately after overload
DIN mount product in grey shells
Dual mount product in black shells
Current limiting capability
Ring terminal ready (terminal screw is removable)
Suitable to use for electrical isolation
Auxiliary Switch,Trip Alarm & Combo:
Features
•
•
•
•
•
•
AC branch circuit protection
Telecom / datacom equipment
Lighting control
UPS equipment
Alternative energy equipment
Mobile power generation equipment
Power conditioning equipment
Optional Accessories
•
•
AC and DC voltages
•
UL 489 listed (Auxiliary Switch: 6 A 250 V AC,
•
0.5 A 80 V DC)
•
IEC 60947-5-1 approved (Auxiliary Switch: 6 A 240 V AC,
0.5 A 110 V DC; Trip Alarm: 6 A 240 V AC, 0.5 A 110 V DC) •
•
Factory fitted
•
Attached to right hand side of Circuit Breaker
Auxiliary Switch
Auxiliary Switch + Trip Alarm
Trip Alarm
Handle lock
Surface mounting clips
Busbar
57 mm Escutcheon blank
57 mm Safety blank
Compact 6.5 mm width
QL-SERIES-DAT
DEC 2014
Data Sheet
Page 1 of 8
low voltage
QL - Series Miniature Circuit Breakers
Technical Data
Approvals
Number of Poles
Operating Voltages
Minimum Current Rating
Maximum Current Rating
Interrupting Capacity
Operating Temperature Range
Mounting Options
Time Delay Curves
Approvals
Number of Poles
Operating Voltages
Minimum Current Rating
Maximum Current Rating
Interrupting Capacity
Operating Temperature Range
Mounting Options
Time Delay Curves
1
1 Pole & 2 Pole
Data Sheet
Page 2 of 8
IEC / EN 60947-2, VDE
2
240 V AC
3
415 V AC
UL 489
1
120 V AC
1
240 V AC
2
120 / 240 V AC
3
240 V AC
25 A
10 kA
25 A
5 kA
0.1 A
25 A
10 kA
20 A
5 kA
-40oC to +85oC
DIN Rail, Dual mounting (DIN & Mini), surface mounting clip
1, 9, KM, OP
CCC
1
2 (1+N)
2
240 V AC
240 V AC
240 V AC
0.1 A
25 A
25 A
25 A
6 kA
-40oC to +85oC
DIN Rail, Dual mounting (DIN & Mini), surface mounting clip
1, 9, KM, OP
Wire Size mm² (IEC)
Wire Gauge (UL)
Torque (IEC)
Torque (UL)
0.75 - 35 mm²
18 – 2 – AWG
2.5 Nm
20 in-lb
QL-SERIES-DAT
DEC 2014
4 (3+N)
0.1 A
25 A
6 kA
-40oC to +85oC
DIN Rail, Dual mounting (DIN & Mini), surface mounting clip
1, 9, KM, OP
Approvals
Number of Poles
Operating Voltages
Minimum Current Rating
Maximum Current Rating
Interrupting Capacity
Operating Temperature Range
Mounting Options
Time Delay Curves
Breaker QL
2 (1+N)
Comments
Pozidriv #2
Combi head
low voltage
QL - Series Miniature Circuit Breakers
Long Code
Example Code: QL---AT-3(13)-D-KM-15A-------Z
Group
1
2
3
4
5
6
7
8
9
10
11
12
QL
Frame
Switch /
Neutral
Auxiliary
+ Trip
Alarm
Triple
pole
13 mm
module
width
DIN Rail
Medium
delay
curve KM
15 A
Future
use
No Shunt
Trip
Future
use
Parallel
bridged
(by
customer)
Long Code
QL
-
AT
3
(13)
D
KM
15A
-
-
-
Z
Group 1:
Frame Type
Code
Description
Comments
QL
13 mm wide Miniature Circuit Breaker
UL 489A, IEC / EN 60947-2,VDE, CE, CCC
Requirement
Group 2:
Code
Switch/Neutral
Group 3:
Auxiliary
Group 4:
No of Poles
Description
Comments
Not applicable
Overload poles do not have any further coding
N
Neutral
Code
Description
Comments
-
Not applicable
Use this code if no Auxiliary used
A
Auxiliary Switch (1 x Aux in 1 module)
6.5 mm module fitted on right-hand side
T
Trip Alarm (1 x Trip Alarm in 1 module)
6.5 mm module fitted on right-hand side
AT
Auxiliary Switch + Trip Alarm combo (combined in 1 module)
6.5 mm module fitted on right-hand side
Code
Description
Comments
1
Single pole
2
Double pole
3
Triple pole
2 pole or1+N
4
Four pole
3+N only
Group 5:
Module Width
Code
Description
Comments
(13)
13 mm module width
13 mm per pole
Group 6:
Mounting
Code
Description
Comments
D
DIN rail mount – 45 mm Escutcheon, grey body
DIN mount supplied in grey only
DM
Dual mount – 57 mm Escutcheon, black body
Group 7:
Time Delays
Code
Description
Instantaneous Trip Point (x In)
Comments
1
Long time delay, high instantaneous trip
10 – 20
Orange handle
Dual mount supplied in black only
9
Long time delay
7 – 12
White handle
KM
Medium time delay
6 – 12
White handle
OP
Instantaneous
None
White handle
Group 8:
Current
Ratings
Code / Description
Comments
Ratings available vary depending on certification
0.1, 0.2, 0.3, 0.5, 1, 2, 3, 4, 5, 6, 7, 8 ,9, 10, 12, 15, 16, 20, 25 A
* Other ratings are available as special orders. Check availability.
For future use (-)
Group 9:
Code
Group 10:
Shunt Trip
Code
Description
Comments
-
Not applicable
Use this code if no Shunt Trip is used
V0
100 – 480 V AC
Fly leads (approximately 60 mm long)
V5
100 – 480 V AC
Internally connected
(not certified,
only offered as
special order)
Other voltages are available as special orders. Check availability.
Group 11
Code
Group 12:
Special
Termination
Code
Description
Comments
-
Not applicable
Use this code if no special terminations are used
For future use (-)
P
Plug-in
Z
Bridged unit (bridge to be fitted by customer)
ZL
Bridged unit (factory fitted)
For options not listed, please contact CBI for assistance
QL-SERIES-DAT
DEC 2014
Data Sheet
Page 3 of 8
low voltage
QL - Series Miniature Circuit Breakers
Time Delay Curves
1500
100000
OPERATING
CHARACTERISTICS
10000
CURVE 1
Tripping Time (Seconds)
1000
100
10
1
0.1
Maximum
0.01
4000
5000
3000
2000
2500
1500
1000
500
400
300
200
130
100
105
0.001
150
Maximum
% Rated Current
1500
100000
OPERATING
CHARACTERISTICS
10000
CURVE 9
Tripping Time (Seconds)
1000
100
10
1
0.1
Maximum
0.01
% Rated Current
Data Sheet
Page 4 of 8
QL-SERIES-DAT
DEC 2014
4000
5000
3000
2000
2500
1500
1000
500
400
300
200
130
100
105
0.001
150
Maximum
low voltage
QL - Series Miniature Circuit Breakers
Time Delay Curves
1500
100000
OPERATING
CHARACTERISTICS
10000
CURVE KM
Tripping Time (Seconds)
1000
100
10
1
0.1
Maximum
0.01
5000
4000
3000
2000
1500
1000
500
400
300
200
150
100
0.001
125
Maximum
% Rated Current
1500
100000
OPERATING
CHARACTERISTICS
10000
CURVE OP
Tripping Time (Seconds)
1000
100
10
1
0.1
Maximum
0.01
5000
4000
3000
2000
2500
1500
1000
500
400
300
200
130
100
105
0.001
150
Maximum
% Rated Current
* The published time delay curves are generated at 30oC ambient temperature with the Circuit Breaker mounted in the up-right position. The “must hold”, “must trip” and “instantaneous
trip” current values are not affected by temperature, although delay time for the other operating current values may have to be adjusted using the temperature compensation curve which
is available on request.
QL-SERIES-DAT
DEC 2014
Data Sheet
Page 5 of 8
low voltage
QL - Series Miniature Circuit Breakers
Internal Impedance vs Current Rating
Q-Range impedance values
10,000
Impedance (m Ω )
1,000
100
10
Maximum
1
0.1
Maximum
0
5
10
15
20
25
30
35
Amp rating
40
45
Auxiliary Switch / Trip Alarm
Auxiliary available (6.5 mm module width) to match the unit to which it is attached.
Available types as listed in Group 3:
•
•
•
Type T - Trip Alarm as shown in outline drawings (fitted on a Dual mount product)
Type AT - Auxiliary Switch + Trip Alarm (as shown)
Type A - Auxiliary Switch
Data Sheet
Page 6 of 8
QL-SERIES-DAT
DEC 2014
50
55
60
65
low voltage
QL - Series Miniature Circuit Breakers
57.0
97.2
Typical outline of Auxiliary Switch / Trip Alarm
Typical outline for an Auxiliary module
attached to a Dual mount single pole
Circuit Breaker
All dimensions in mm
Tolerance ± 0.2 unless otherwise specified
All widths are maximum
69.8
35.5
19.3
AUXILIARY/ TRIP ALARM (AT)
18.0
6.0
Circuit Diagrams
Trip Alarm Switch
16
18
11
12
15
16
15
18
16
11
12
Auxiliary Switch
14
A005438
S
Q-AUX
V
D E
TEST BUTTON
(not on Auxiliary)
Uimp = 2.5kV
Icw = 0.1kA
UTIL. CAT. AC12/DC12
POLLUTION DEGREE 3
RoHS
15
TRIP ALARM SWITCH
AUXILIARY SWITCH
110 VDC : 0,5A
110 VDC : 0,5A
240 VAC : 6A
240 VAC : 6A EN/IEC 60947-5-1
18
11
12
14
14
11.7
6.5
18.0
37.8
1.4
0.8
0.5
2.3
6.8
45°
2.80
CONNECTING TERMINALS
DETAIL (COMMON TO ALL)
QL-SERIES-DAT
DEC 2014
Data Sheet
Page 7 of 8
low voltage
QL - Series Miniature Circuit Breakers
Outline Dimensions: Dual mount
69.1
2.720
61.0
13.0
2.400
19.6
1.024
39.0
1.536
2.801
71.2
3.827
97.2 (Ref)
2.244
57.0
3.244
0.772
82.4
26.0
0.512
19.6
13.0
0.772
5.0
0.512
45.0
0.197
1.772
All dimensions in mm [ inch ]
Tolerance ± 0.2 [ 0.008 ] unless otherwise specified
All widths are maximum
64.8
2.551
Outline Dimensions: DIN mount
68.1
2.681
60.0
2.362
18.6
1.024
39.0
1.536
2.803
3.827
97.2 (Ref)
1.772
45.0
71.2
0.512
3.244
82.4
26.0
13.0
0.732
18.6
13.0
0.732
5.0
0.512
44.0
0.197
1.732
63.8
2.512
All dimensions in mm [ inch ]
Tolerance ± 0.2 [ 0.008 ] unless otherwise specified
All widths are maximum
Please review our Customer Terms and Conditions on www.cbi-lowvoltage.co.za
All rights reserved. Unless otherwise indicated, all materials on these pages are copyrighted by CBI (Pty) Ltd. No part of these pages, either text or image may be used for any purpose other than personal use.
Therefore, reproduction, modification, storage in a retrieval system or retransmission, in any form or by any means, electronic, mechanical or otherwise, for reasons other than personal use, is strictly prohibited without
prior written permission. CBI (Pty) Ltd reserves the right to alter any details of this document without notice and while every effort is made to ensure the accuracy of the content, no warranty is given as to accuracy
of this document and no responsibility will be accepted for error or misinterpretation and any resulting loss.
AUSTRALIA
CBI-electric: Australia
90 Fairbank Road Clayton South
Melbourne Victoria 3169 Australia
Tel: + 61 39590 3500
Fax: +61 3 9551 1051
Email: sales@cbi-electric.com.au
Website: www.cbi-electric.com.au
Data Sheet
Page 8 of 8
QL-SERIES-DAT
DEC 2014
SOUTH AFRICA
CBI-electric: low voltage
Tripswitch Drive Elandsfontein
Gauteng South Africa
Tel: +27 11 928 2000
Fax: + 27 11 392 2354
Email: cbi@cbi-electric.com
Website: www.cbi-lowvoltage.co.za
USA
CBI-electric: North America
35 E. Uwchlan Ave Suite 328
Exton PA 19341 USA
Tel: +1 610 524 9949
Fax: +1 610 524 9945
E-mail: info@cbibreakers.com
Website: www.cbibreakers.com
A member of the Group
Related documents