SECTION 16425 - DISTRIBUTION PANELBOARD PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. 1.02 DESCRIPTION A. Description: Provide factory-assembled, dead-front distribution panelboard with main breaker for service entrance (Panel MDP) from line terminals to outgoing feeder terminals, complete, installed, and tested in place. B. General: Panelboard shall include all main and branch protective devices, related equipment as required or as listed on drawings, with all necessary interconnections, instrumentation, control wiring, etc. C. 1.03 General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification sections, apply to work specified of this section. Manufacturer: Square-D I-‘Line, Westinghouse Pow-R-Line 4 or G.E. Spectra Series. DISTRIBUTION SWITCHBOARDS QUALITY ASSURANCE A. ANSI: The latest edition of the Reference Standards for the American National Standards Institute shall apply as follows; 1. ANSI Y32.2 - Graphic Symbols for Electrical and Electronic Diagrams. 2. ANSI Z55.1 - (R1973) Gray finishes for Industrial Apparatus and Equipment. 3. ANSI C57.13 - Instrument transformers B. NEMA: National Electrical Manufacturers Association shall apply as follows; 1. NEMA PB1-1984, Panelboards. 2. NEMA AB1, for molded case circuit breakers and switches. 3. NEMA PB1-57 gutter space. C. NFPA: The latest edition of the National Fire Protection Association shall apply as follows; 1. NFPA 70, National Electrical Code (NEC). 2. Refer to Section 16010 for additional references. DISTRIBUTION SWITCHBOARDS 16425-1 D. UL: The latest edition of the Underwriters' Laboratories, Incorporated shall apply as follows; 1. UL Electrical Construction Materials List Panelboards-dead front type 2. UL 67 Panelboard wiring gutter space, bus heat rise test. 3. UL 50 Cabinets – Rigidity and gauge of steel. 4. UL 489 Molded case circuit breakers. E. 1.04 Listing: Panelboards shall be listed by Underwriters Laboratories and bear the UL or other nationally recognized testing laboratory label. Where required, panelboards shall be listed for use as service entrance equipment. SUBMITTALS - DISTRIBUTION SWITCHBOARDS A. General: Submit layouts showing concrete pad dimensions (where applicable), conduit entrance and available space, bus duct connections, electrical rating, nameplate nomenclature, single-line diagram (in accordance with ANSI Y32.2) indicating all connections and control. B. Shop Drawings: Shop Drawings shall be submitted for main distribution panelboard (UDP) and shall clearly indicate all of the following information; Enclosure elevations, studs and details. Complete Construction Information U.L. Label Each overcurrent device amperage rating, circuit number and position/location in the panelboard. 5. Electrical characteristics 6. Dimensions, (width, depth, height, weight) 1. 2. 3. 4. 7. Frame size, rating and interrupting capacity of each breaker, and of total assembly. 8. Horsepower rating at rated voltage of fused switches and/or breakers. 9. Size and type of fuses being provided. 10. Ranges of all meters (all meters shall be analog unless otherwise noted). 11. Type of labeling for each overcurrent device and load (Provide at least one sample with shop drawing). 12. Equipment nameplate indicating project name; Architect, Engineer and Contractor. 13. Product data for panelboard mounted transformers; or other specialties clearly and/or separately called out in the contract documents. 14. Bus bar size, type arrangement and spacing (Phase, neutral and ground bar). DISTRIBUTION SWITCHBOARDS 16425-2 15. Transparency log paper time current curves for protective relays, current and potential transformer excitation and saturation curves, and fuses. 16. Protective relay instruction books. 17. Shipping sections. 18. Lug sizes for cables on all switches or breakers. 19. Incoming lug sizes. 1.05 C. Product Data: Manufacturer's written recommendations for storage, protection, handling, installation instructions and field test requirements. Record all field tests, itemize data and submit at end of project with project manual. D. Test Reports: Reports of production and field tests. E. Operations and Maintenance Data: Provide and comply with manufacturer's instructions for tightening bus connections, performing cleaning, operating and maintaining switchboard. PRODUCT DELIVERY, STORAGE AND HANDLING A. Handling: Only lift panelboard using eyes, yokes, and skids provided by manufacturer. B. Storage: Do not store indoor switchboard exposed to weather. C. Protection: Physically protect switchboard against all damage. Cover switchboard with suitable material to avoid damage to finish. PART 2 - PRODUCTS 2.01 MAIN SECTION A. General: The main disconnect device shall be as specified herein and shall be totally front accessible and front connectable. Main device shall be provided with ground fault protection, shunt trip. Main circuit breaker shall be solid-state with adjustable settings for long-time, short time, instantaneous, long-time delay and short time delay. B. Digital Line Metering and Protection System: Provide a digital line metering and protection system in each switchboard. The device shall display the functions listed below: METERED VALUES (Accuracy) AC Phase Amperes (1%) AC Phase Voltage (1%) Watts, (2%) DISTRIBUTION SWITCHBOARDS 16425-3 PROTECTIVE FUNCTIONS Voltage Phase Loss (less than 50% rms) Current Phase Loss (1/16 largest phase) Phase voltage Unbalance (5 to 40% - 5% steps) Vars, (2%) Phase Voltage Reversal Power Factor (4%) Overvoltage (105 to 140% - 5% steps) Frequency (0.5%) Overvoltage (105 to 140% - 5% steps) Watthours (2%) Undervoltage (95 to 60% - 5% steps) Watt Demand (2%) with (5, 10, 15, Time Delay for Overvoltage, Undervoltage, 30 min. interval) and phase unbalance (0 to 8 sec. - 1 sec. steps) The device shall auto range between units, kilo-units, and mega-units. The device shall have the capability to communicate data via twisted pair network. C. Inputs: Input ranges of the device shall accommodate external current transformers as required. Provide three external current transformers with rating sized for incoming service. Potential transformers shall be provided and fused. Control power shall be derived from the metered line. D. Outputs: Outputs shall have separate Form C (NO/NC) trip and alarm contacts with ratings of 10 amperes at 480 volt A.C. Also provide a separate Form C (NO/NC) contact to provide programmable kilowatt hour pulse output. E. Design Selection: Westinghouse IQ Data Plus II, G.E. or Square-D equals. F. Ground Fault Protection: Ground fault protection system shall be provided consisting of the following; 1. A ground sensor on line side of main switch encircling all phase and 2. 3. 4. 5. G. neutral conductors connected to an adjustable solid state ground relay switch which initiates automatic shunt tripping of the main and/or branch circuit interrupting devices. System shall be adjustable from 200 to 1200 primary amperes, and time current characteristics shall provide 6 cycle operation at about ten times setting. Relay output shall operate at 120 volts A.C. fused source from main bus. Provide all terminal blocks, transformer, auto-reset fuses, interconnecting wiring, etc. Submit relay curves and all main/branch breakers for coordination study. Provide two levels of ground fault protection in accordance with NEC 517. Phase Protection: A phase protection system shall be provided as follows; 1. System shall provide loss of phase, phase reversal, low voltage and phase unbalance protection. DISTRIBUTION SWITCHBOARDS 16425-4 2. System shall consist of solid state controller, DPDT relay, terminal 3. 4. 5. 6. 7. 2.02 blocks, audio and visual failure indicator with local silence switch, adjustable trip delay (1 to 10 seconds) adjustable sensitivity, autoreset fuses and all interconnecting wiring. Unit shall be mounted in NEMA 1 enclosure adjacent to or mounted on side of, or in the main section of the distribution panelboard. System shall control shunt trip mechanisms on circuit breakers were equipped with such features. Unit voltage shall match voltage system of main board. Provide additional relay operated, by phase protection system, as required if tripping more than one breaker. Phase protection system unit shall be Time Mark #259 for system voltage, or equal. Submit phase protection system layout with shop drawing. DISTRIBUTION SECTIONS A. General: Circuit breakers below 400 amps shall be bolt-on thermal magnetic molded case circuit breakers, and shall be totally front accessible. The branch protective devices are to be mounted to permit easy installation, maintenance and testing without reaching over any line side bussing. The circuit breakers shall be removable by the disconnection of only the load side cable terminations and all line and load side connections shall be individual to each circuit breaker. No common mounting brackets or electrical bus connectors shall be acceptable. Each circuit breaker is to be provided with an externally operable mechanical means to trip the circuit breaker, enabling maintenance personnel to verify the ability of the circuit breaker trip mechanism to operate, as well as exercise the circuit breaker operating mechanisms. Handles shall have “ON”, “OFF”, and “TRIPPED” positions. B. Solid State Circuit Breakers: All breakers 400 amperes and above shall be solid-state with adjustable settings for long-time, short-time, instantaneous, long-time delay and short-time delay. C. All circuit breakers shall be fully rated. No series rating is allowed. PART 3 - EXECUTION 3.01 INSPECTION A. Preparation: Examine area to receive panelboard to assure that there is adequate clearance to meet NEC requirements and normal maintenance issues for panelboard installation. Check that housekeeping pads (concrete base) are level and free of irregularities. Start work only after any unsatisfactory conditions have been corrected. DISTRIBUTION SWITCHBOARDS 16425-5 3.02 INSTALLATION A. Compliance: Provide panelboard complete in accordance with manufacturer's written instructions, NEC, and all applicable codes. B. Mounting: Where full height, mount panelboard on 4 inch housekeeping pad (concrete base). Pad shall extend 6 inches beyond edge on all sides with all equipment installed. C. Mats: Provide continuous rubber insulating mat on floor in front of panelboard. Mat shall extend for the entire length of panelboard plus two feet beyond each side. Mat to be minimum 3 feet wide and 1/4 inch thick. Mat shall lie flat on floor without the use of any adhesive or fastener. Entire edge of mat shall be chamfered. Submit manufacturers data sheet of mat with shop drawings. D. Storage and Delivery: Panelboards shall be delivered to the site during that phase of panelboard installation in order to avoid storing panels on site where damage may occur. Replace any damaged parts prior to energizing panel. Cover panelboard to avoid damage to finish. E. Mounting: Do not mount equipment directly to masonry or concrete walls. Provide two uni-strut spacers between wall and panelboard. F. 3.03 Operations and Maintenance Data: Manufacturer’s instructions for tightening bus connections, cleaning, operation and maintenance. FIELD QUALITY CONTROL A. General: Provide field tests prior to energization as follows; 1. Megger check and record all data, of phase to phase and phase to ground insulation levels. 2. Continuity. 3. Short Circuit. 4. Proper phase relationship. B. 3.04 Provisions: Perform tests according to panelboard manufacturer's instructions. ADJUSTMENT AND CLEANING A. Adjustments: Adjust operating mechanisms for free mechanical movement. B. Connections: Tighten bus connections and mechanical fasteners. DISTRIBUTION SWITCHBOARDS 16425-6 C. 3.05 Finish: Touch-up scratched or marred surfaces to match original finish. CHECK-OUT MEMO A. General: Submit check-out memo from panelboard representative. END OF SECTION 16425 DISTRIBUTION SWITCHBOARDS 16425-7 CHECK-OUT MEMO NOTE TO CONTRACTOR: Do not submit this form at the time Technical Information Brochure is submitted. This form shall be completed and submitted before Instruction in Operation to Owner or a request for final inspection. N a m e o f e q u i p m checked:________________________________________________ N a m e o f m a n u f a c t u equipment:__________________________________________ r e e r n t o f R e : ____________________________________________________________________ (Name of Project) 1. The equipment furnished by us has been checked on the Job by us. We have reviewed (where applicable) the performance verification information submitted to us by the Contractor. 2. The equipment is properly installed, except for items noted below.* 3. 4. The equipment is operating satisfactorily, except for items noted below.* The written operating and maintenance information (where applicable) has been presented to the Contractor, and gone over with him in detail. Five (5) copies of all applicable operating and maintenance information and parts lists have been furnished to him for insertion in each of the Equipment Brochures. Checked by: _______________________________________________________________ (Printed Name of Manufacturer's Representative) _____________________________________________________________ (Address and Phone No. of Representative) ____________________________________________________________ (Signature and Title of Person Making Check) ____________________________________________________________ (Date Checked) cc: Owner, Architect, Engineer, Contractor and Subcontractor *Exceptions noted at time of check were as follows: