DC Power Systems PROTECT MIP Series Rectifier Module Operation Manual Product involved: PM24-50 (CR1249) 3AW17849AAAA01 Rev 01 3AW17849AAAA01 Operation Manual Rectifier Module 1. GENERAL DESCRIPTION The PM24 module is a 1500 watts fan cooled rectifier. It converts the single phase AC line voltage into an isolated DC voltage. It can be used as a power supply or battery charger. Key features: • Optimal electronic and thermal design for industrial applications with wide output voltage range for charging of many battery types, including open and closed lead acid batteries and NiCd batteries. • High power density 0.55 W/cm3. • Wide operating input voltage range. • Special commissioning mode • Automatic disconnect on low and high mains voltage with automatic restart. • Hot plug capability. • High efficiency. • Sine wave input current. • Electronic fan speed (low noise – extended fan life) • Full thermal management with fan speed control and automatic power de-rating. • Adjustable output voltage via analogical control loop. • Unlimited paralleling within ±5%. • Led’s signalling. • Alarm loops. • CE marked. 2. STANDARDS 2.1. SAFETY EN 60950-1. EN 50178 2.2. EMC 2.2.1.EMISSION: EN 55022 complies with EN 61000.6-3 (generic standard) complies with EN 61000.6-4 (generic industrial) 2.2.2.IMMUNITY : complies with EN 61000.6-1 complies with EN 61000.6-2 Standard IEC TS 61000 -6-5 2.3. ENVIRONMENTAL: EN 60721-3-1 Storage. EN60721-3-2 Transportation. EN60721-3-3 Stationary use. 2.4. TECHNICAL: DEP33.65.50.31 Gen. Static (DC UPS) Page 2 of 7 3AW17849AAAA01 Operation Manual Rectifier Module 3. CHARACTERISTICS 3.1. ENVIRONMENTAL CHARACTERISTICS 3.1.1.TEMPERATURE Shipping and storage : -25°C to + 70°C. Operating : -0°C to +45°C.Above 45°C to 55°C output current de-rating (1.25% per °C) 3.1.2.HUMIDITY Shipping and storage : 15 to 90%. In the original package Operating humidity : 10 to 95% relative humidity non-condensing 3.1.3.ALTITUDE Operating without de-rating : 0 -1000m up to 4000m , power de-rating of 7% per 1000m 3.1.4.COOLING Forced air cooling with electronic speed control of fans 3.2. MECHANILCAL CHARACTERISTIC Height : 43.6 mm (complies with 1U standard). Width : 210 mm Depth : 298 mm (without handles). Weight : 3 kg Connector (input / control and signal / output connector J1): 51939-302LF Degree of protection : IP 20 Connector J1: Pin out location (Front view). P1 P2 P3 1 2 3 4 5 6 P4 P5 P6 P7 P8 P9 P10 Row D Row C Row B Row A Signal pins Signal pins Row D Row C 1 2 3 4 5 6 Output current signal - Iout Alarm Loop signal + Auxs 0-10V Control Shutdown + Shutdown - Mains fail Alarm Loop SignalFan fail Commission enable Output Temp. sensor Bus Share Backdrive RIP 0VS RIP Row B Row A + Iout Power Pins P1 Input LINE P2 Input NEUTRAL P3 EARTH P4 Output - Vout P5 Output - Vout P6 Output - Vout Precharge P7 Output + Vout Pre- charge P8 Outpu t + Vout P9 Outpu t + Vout P10 Outpu t + Vout Page 3 of 7 3AW17849AAAA01 Operation Manual Rectifier Module 3.3. ELECTRICAL CHARACTERISTICS DIELECTRIC STRENGTH AC line to output AC line to chassis Output to chassis 4300 VDC 2800 VDC 1200 VDC INPUT Nominal voltage Normal operating range Extended operating voltage Frequency Nominal current Inrush current Available power versus input voltage Harmonic (typical) Power factor 208 Vrms / 220 Vrms / 230 Vrms / 240 Vrms. 184 V to 276 Vrms single-phase. 80 V to 280 Vrms with: . power de-rating below 185 Vrms . low (< 65 V) and high (> 300 V) voltage out of range with automatic re-start. 47.5 to 63 Hz 6.4 A at 230 Vrms – (26V@50A) < 1.5 In peak 40% Pn at 100 Vrms 75% Pn at 150 Vrms 100% Pn at 187 Vrms < 5% 0.97 OUTPUT Output voltage Fall back voltage Hold up time Static regulation accuracy Dynamic regulation accuracy Acoustic noise Load sharing Maximum output current Maximum output power at nominal input voltage Commissioning Charge Voltage Remotely by 2 - 8 V voltage loop Adjustment range : 16.5V to 33V UDC = 26 V when loop voltage < 1.5 V or > 8.5 V 4 ms < 3% (added mains and load variations). < 5% UDC with load step 10% - 90% and 90% - 10%. Recovery to normal regulation limit in 5 ms. < 60 dBA < ±5% at P > Pn/2 No more than 54A 1400 W at 208Vac and 28Vdc A commissioning charge of 33Vdc facility will be provided. This will be at a reduced current EFFICIENCY > 86% for 24V output voltage, 75% load and nominal input voltage. > 85% for 75% load on the global input, output and temperature range. Page 4 of 7 3AW17849AAAA01 Operation Manual Rectifier Module 4. PROTECTIONS 4.1. INPUT Caution: double pole/neutral fusing. Hot pluggable Soft-start Input over and under-voltage. Module shutdown below 65 Vrms and above 300 Vrms with automatic re-start. Surge suppression by varistors (L/N), (L/Gnd), (N/Gnd). Mains power system TT, TN and IT (Limited at 230Vac line to line). 4.2. OUTPUT Hot pluggable DC overvoltage selective and memorized shutdown. Output power limit. Output current limit Output over and under-voltage Over-current and short-circuit electronic protection. Reverse polarity protection. 4.3. THERMAL Automatic power de-rating on high temperature. Fan: Rectifier stop on fan fail. Fan speed control versus temperature. 5. SIGNALLING Led ON Event Alarms Green Red Main Fan No Loop Vout Open Vout > 15V and in Fall Back voltage Yes Open Open Vout > 15V and in under loop control Yes No Close Open Open Vout < 15V and under loop control or Fall Back voltage No No Open Open Open Main between 184Vac and 276Vac Vout Fall Back Yes No Open Open Open Main > 287Vac or < 176Vac Vout Fall Back Yes No Open Close Open Main > 300Vac or < 65Vac Rectifier no working No No Open Close Open Fan Stop No No Open Open Close No Yes Open Open Open Vout: Fall Back Rectifier no working Rectifier fault Loop alarm = Open collector and potential free. Fan and Main alarms = Open collector and potential referenced in 0V. Page 5 of 7 3AW17849AAAA01 Operation Manual Rectifier Module 6. DETAILED DESCRIPTION 6.1. SYNOPTIC ~ = = Precharge and start Power factor correction = DC /DC converter System management Unit Auxiliary J1 signal 6.2. TECHNOLOGY The rectifier module converts the AC mains supply into direct current. The function is achieved using the latest high-frequency-switching and results in reduced volume. The forced convection design offers high power density of 0.55 W/cm3 at 45°C, as well as high efficiency and low weight. Each rectifier module is factory pre-set and can operate independently or in parallel with other rectifiers. The modules share their nominal power between the load or the battery. 6.3. OPERATING DESCRIPTION The rectifier module consists of four sub-assemblies: - An input circuit with protection devices, a rectifying circuit, an EMI filter and a filtering and storage capacitor. The input circuit includes an active power factor correction (boost chopper at 50 kHz) which ensures a sinusoidal input current as well as a power factor better than 0.97. - A full bridge phase shift converter connected to an RF transformer converting DC voltage from the storage capacitor into high-frequency AC voltage (100 kHz). - An output circuit with EMI filter and rectifying devices converts the transformed secondary voltage into DC voltage. - A control and regulation circuit drives the full bridge on the basis of output voltage and current information using pulse-width modulation devices. Page 6 of 7 3AW17849AAAA01 Operation Manual Rectifier Module 7. PACKAGING AND PRODUCT REFERENCE 7.1. PACKAGING In cardboard. 7.2. PACKING TABLE WxDxH Gross Weight Volume PM24-50 packed dimensions and weight mm 275 x 380 x 70 kg 3 m3 0.007 7.3. PRODUCT REFERENCE Designation PM24-50 H&S code 3AW01249AALA 8. MANUFACTURING AND ORDERING HARMER &SIMMONS (M) SDN. BHD. PLOT 19 TKT. PERUSAHAAN 6 PHASE IV KAW PERUSAHAAN PRAI SEBERANG PRAI PENANG 13600 MALAYSIA 9. INSTALLATION SAFETY INSTRUCTION. 1) This apparatus must be professionally installed. The installation should be such that its power and alarm terminals and wiring connected thereto is not operator accessible. 2) The apparatus should be used only on TT, IT and TT power systems as defined in Annex V of EN60950-1, IEC 60950-1 or UL60950-1.The apparatus should be installed in a rack or frame onto which the incoming safety earth is hard wired. 3) The apparatus should be installed in a restricted access location. 4) The apparatus should be installed in a non operator accessible metal enclosure host system which constitutes a fire enclosure within the meaning laid down in EN60950-1, IEC60950-1 or UL60950-1. 5) The apparatus takes the form of stationary pluggable equipment which is hotpluggable and therefore in itself performs the function of a disconnect device. WARNING Failure to observe the above precautions may result in hazardous conditions on the network. END OF DOCUMENT Page 7 of 7