Outsmart SensorMate Installation Guide For connection to LoadRunner Ethernet (PN: 110-0098) Doc#: 410-0004 Rev 0, 12/18/2013 OutSmart Power Systems, 11 Mercer Road, Natick MA 01760 Phone: 508 650 0055 Fax: 508 650 0054 SensorMate Overview The OutSmart SensorMate is an accessory of the OutSmart Monitoring System. It allows off-theshelf sensors such as current transformers to be used in the system. SensorMates connect to the system through the OutSmart LoadRunner. Multiple SensorMates can be daisy-chained together. For each SensorMate added to a LoadRunner the max number of EnergyMates that can be connected to that LoadRunner is reduced by one. SensorMate Installation Guide, 410-0002 R8 Page 2 ©2012 OutSmart Power Systems Symbols and General Safety Symbol Description Caution, risk of electrical shock Alternating Current 3 I O 3 Phase Alternating Current Supply on Supply Off Caution, installation guide must be consulted Safety DANGER — HIGH VOLTAGE HAZARD WARNING - These installation/servicing instructions are for use by qualified personnel only. To avoid electrical shock, do not perform any servicing unless you are qualified to do so. Only qualified personnel or electricians should install the OutSmart SensorMate. The OutSmart SensorMate is intended to be used in accordance with this manual and all safety instructions must be followed. All wiring in the United States must be installed in accordance with the latest adopted edition of the National Electrical Code (ANSI/NFPA 70, NEC) and state or local requirements. It is recommended that a licensed electrician install the OutSmart SensorMate. It is recommended that the OutSmart SensorMate be installed either in an electrical enclosure (panel or junction box) or in a limited access electrical room. Ensure that the line voltage inputs to the OutSmart SensorMate have either fuses or circuit breakers on each phase (not the neutral or ground wires). To disconnect the OutSmart monitoring system remove fuses or shut off breakers that the line voltage inputs are connected to. Equipment must be disconnected from the HAZARDOUS LIVE voltage before access. In case “I” to “O”) the breakers or remove the fuses the line of hazard turn off (switch from voltage inputs are connected to. SensorMate Installation Guide, 410-0002 R8 Page 3 ©2012 OutSmart Power Systems Environmental Conditions: 1) 2) 3) 4) 5) 6) 7) 8) 9) 10) 11) 12) 13) 14) Indoor use only Maximum altitude: 2000m Temperature Range: 5 °C to 40 °C Maximum relative humidity: 80% for temperatures up to 31C decreasing linearly to 50% relative humidity at 40 °C Transient over-voltages which may be present on the MAINS supply up to 2.5kV. The OutSmart SensorMate requires an environment no worse than pollution degree 2 (normally only non-conductive pollution; occasionally temporary conductivity caused by condensation). Equipment mobility: Built-in Connections to mains supply: Up to 3 monitored voltages. Operating conditions: continuous Mass of SensorMate: 1.5lbs Equipment classification: Professional Equipment Class: Class 1 Equipment Type: Permanently connected, Fixed – Built-in Measurement category: III Input Ratings: 12V DC, 1W External voltage sense connections to be made with appropriate gage wire with a voltage rating commensurate with the voltages to which the wires will be subjected, subject to a 300V minimum rating. SensorMate Installation Guide, 410-0002 R8 Page 4 ©2012 OutSmart Power Systems General description The SensorMate is a device that allows off-the-shelf current transformers to be added to the OutSmart energy monitoring system. It can accept up to three current transformer inputs and 3 voltages with a neutral reference. Multiple SensorMates can be connected in series. A maximum of 32 SensorMates can be connected to one OutSmart LoadRunner, or any combination of SensorMates and EnergyMates up to a total of 32 devices. Dimensions and Callouts Figure A Items A. B. C. D. E. F. G. H. Screws- access to PCB LEDs – measurement channels Ground wire Terminal Block – Up to 3 current sensors RJ11 connection (J6) - incoming from LoadRunner (or SensorMate) RJ11 connection (J7) - outgoing to additional SensorMate(s) (optional) PCB Voltage sense terminal block SensorMate Installation Guide, 410-0002 R8 Page 5 ©2012 OutSmart Power Systems Dimensions and Callouts Figure B Items P. Current Sensors Q. Phone Wire - Station100 4C R. Wire to Load(s) Approved Current Sensors Manufactured by: Sentran Corp 2547 Arial Way SE Salem, Oregon 97302 www.sentrancorp.com P: 503-370-7377 Series: 4LSF (20A to 6000A), LCF (1A to 100A), BCF (25A to 300A), LN2F (1A to 100A), LN3F (5A to 200A), LN4F (5A to 600A). All are listed in UL file number E344051 SensorMate Installation Guide, 410-0002 R8 Page 6 ©2012 OutSmart Power Systems Schematic, 3 phase 277/480v Y 4 wire Figure C Schematic, 3 phase 480v 3 wire Figure D SensorMate Installation Guide, 410-0002 R8 Page 7 ©2012 OutSmart Power Systems SensorMate installation The base housing of the SensorMate is a standard 4” X 4” X 2” work box. Remove the two screws holding the top of the SensorMate to the base housing. Mount the base housing as you would a typical 4X4 work box. It can be screwed directly to a rigid surface such as a concrete or ¾” plywood. The SensorMate housing should be mounted in accordance with local and national electrical codes. The SensorMate is connected to the OutSmart LoadRunner by a 4 conductor phone cable. The cable is to be run in conduit. Current transformers are to be mounted in accordance with the instructions supplied by the current transformer manufacturer. Leads from the current transformers to the SensorMate should not be accessible to users or operators, and if necessary should be run in conduit. Line voltage is brought to the SensorMate for each of the lines being monitored. A neutral or ground reference voltage is brought to the SensorMate. The Wires are to be installed and run in accordance with local and national electrical codes. Ground is to be attached to the work box. Ground is then brought to the ground terminal on the PCB ONLY when attached to a delta wired circuit (no neutral present). DO NOT bring ground to the PCB when neutral is present. Ground is used as a voltage reference for delta wired circuits. The SensorMate cover is to be installed with a #8 washer and #8 lock-washer. The washer goes under the head of the screw, the lock-washer goes between the washer and the SensorMate cover. This is needed to maintain the ground connection between the SensorMate cover and the work box. Tightening torque for field connections: 4.5 to 6 inch-lbs System functionality check To determine system functionality you must first reenergize the circuits that are being monitored. Turn the breakers back on that were shut off during installation. If the breakers remain on and don’t trip the first level of functionality has been achieved. The final functional check is done by the system software. The system setup procedure is run. During this setup procedure all devices that have been added to the system will be identified. If a SensorMate, is not located by the system software then it is either a non-functioning unit or it was not properly installed. SensorMate Installation Guide, 410-0002 R8 Page 8 ©2012 OutSmart Power Systems Current Transformer installation: Current transformers (CT) to be mounted in accordance with local and national electric codes. CT to be installed in accordance with the installation instructions supplied with the CT. The current rating of the CT to equal or exceed the rating of the breaker /fuse on the line to be monitored by that CT. CT to be secured to line with appropriate wire tie device. CT should always to be mounted on a wire, inside of a metal box with appropriate UL ratings. Lead wires from CT to be run to SensorMate inside appropriate enclosure or UL recognized conduit. Label side of CT should face towards the expected source of power. (Not a safety issue) White lead from CT connects to positive CT terminal in SensorMate. (Not a safety issue) Black lead from CT connects to negative CT terminal in SensorMate. (Not a safety issue) CT leads to be secured with wire ties away from high voltage wires where possible and to prevent the possibility of pinching wires when the box cover is installed. SensorMate Installation Guide, 410-0002 R8 Page 9 ©2012 OutSmart Power Systems