Submittal Package - S3 amazonaws com

advertisement
Submittal Package Riley Construction Company, Inc.
5301 99th Avenue
Kenosha, Wisconsin 53144
Project: 61672-900 - Gateway Mortgage Corporation
6441 Green Bay Road
Kenosha, Wisconsin 53144
34 - Electrical Control Devices SPEC SECTION:
26 00 00 - Electrical
LINK TO PROCORE: View CREATED DATE:
06/27/2016 CREATED BY:
Kelly Hoffman (Riley Construction Company, Inc.)
DESCRIPTION:
ATTACHMENTS:
ISSUE DATE:
7/1/2016
RCCI REVIEWER:
Chad Parker
RECEIVED FROM:
Jennifer Levin (Valiant Electric, Inc.) RETURN DATE:
BALL IN COURT:
Mark Molinaro (Partners In Design Architects, Inc. - Kenosha) COPIES TO:
Kelly Hoffman (Riley Construction Company, Inc.)
File Copy (Riley Construction Co, Inc. - Milwaukee)
Chad Parker (Riley Construction Company, Inc.)
Garrick Palay (Riley Construction Company, Inc.)
Vinnie Chambers (Riley Construction Company, Inc.)
SUBMITTALS
Title
26 00 00-1.0: PD: Electrical Control
Devices
Spec Section
26 00 00 - Electrical
Type
Status
Due Date
Product Data
Pending
Approval
07/08/2016 Riley Construction Company, Inc.
Page 1 of 2
Printed On: 07/01/2016 09:58 AM
EXHIBIT A
SUBMITTAL COVER SHEET – SHOP DRAWINGS, PRODUCT DATA, SAMPLES
Date of Submittal:
Project Name:
Contractor’s Name:
Subcontractor’s Name:
Supplier’s Name:
Specification Sections:
Submittal No/Rev No:
Description:
07/01/2016
Gateway Mortgage
Riley Construction Company Inc.
Valient Electric, Inc.
Submittal Packets/Drawings Procore
Architect’s Project No:
61672-900
Contractor’s Project No:
Subcontractor’s Project No:
Supplier’s Project No:
26 00 00
34/0
Electrical Control Devices
Subcontractor/Supplier Review Stamp (Optional)
Contractor’s Review Stamp (Mandatory)
Reviewed
Incorporate Any Correction Noted
Revise and Resubmit
Checking is only for conformance with the design concept of the
Project and compliance with the information given in the Contract
Document. Submitting contractor is responsible for confirming
dimensions and correlation at the job site, for information that
pertains solely to the fabrication processes or to techniques of
construction, and for coordination of the work of all trades.
RILEY CONSTRUCTION COMPANY, INC.
By_____________________________________
Consulting Engineer’s Review Stamp
□ Submittal Review Sheet Attached
Contractor & Consultant Submittal Procedures 122702
Architect’s Review Stamp
Lutron Proposal
Submitted To:
Project Name:
Location:
CED Interstate Kenosha
Gateway Mortgage
Kenosha, WI
Manufacturer:
PO#
Submitted By:
Date:
Lutron
3654-JES941190D
Engineered Representation Inc.
06-21-2016
A/E: Please confirm colors off attached color chart.
Submittal Specification
Sheets
Gateway Mortgage
Maestro®
Maestro® 0–10 V Dimmer Sensor
Sensor
369833b 1 04.16.15
Maestro® 0 – 10 V Dimmer Sensor
Lutron® Maestro® 0 – 10 V Dimmer Sensors are
lighting controls with passive infrared sensors that
automatically control the lights in an area. These
sensors detect heat from occupants moving within
an area to determine when the space is occupied.
The Maestro® 0 – 10 V Dimmer Sensor combines a
Maestro® 0 – 10 V Dimmer with an occupancy or
vacancy Sensor.
Features
• Controls 0 – 10 V- electronic fluorescent ballasts or
LED driver load types*
• Passive infrared motion detection with exclusive
Lutron® XCTTM Technology for fine motion detection
• 180° sensor field-of-view
• Up to 30 ft × 30 ft (9 m × 9 m) [900 ft2 (81 m2)]
major motion coverage and 20 ft × 20 ft (6 m × 6 m)
[400 ft2 (36 m2)] minor motion coverage
• Occupancy version can be set to auto-on/auto-off or
manual-on/auto-off
• Vacancy version available to meet CA Title 24
requirements
• Adjustable timeout (1, 5, 15, or 30 minutes)
• Adjustable settings for auto-on light level (occupied
level): 100%, 50%, last light level, or locked preset
light level
• Adjustable sensitivity level: High, Med, Low, Min
• Off warning fades lights to off over a period of
10 seconds
• Advanced Maestro® dimmer features available
(locked preset, fade-to-on, and fade-to-off, etc.)
• Adaptive switching algorithm for extended relay life
• Smart ambient light detection (ALD)
• All models have single pole and 3-way capability
• Works with a single standard mechanical 3-way
switch or up to 9 companion switches (MA-AS or
MSC-AS)*
• High-end trim and low-end trim to adjust maximum
and minimum light levels
• Selectable dimming curve—linear or square law
• Miswire and incompatible load alert
* When using with standard mechanical 3-way switch, some rewiring is
required. Not compatible with MA-R.
Models Available
Model Number1 Description
MS-Z101-XX
Occupancy/vacancy
Single-pole/multi-location
MS-Z101-V-XX
Vacancy Single-pole/
multi-location
1
2
Sensor Operation
Auto-on/auto-off or
manual-on/auto-off
Manual-on/auto-off
ONLY
Maximum Capacity
8 A electronic fluorescent
ballasts or LED driver2
8 A electronic fluorescent
ballasts or LED driver2
XX in model number represents color/finish code.
Works with all ballasts and drivers that provide a current source compliant to IEC 60629 Annex E.2.
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
1
Maestro®
Maestro® 0–10 V Dimmer Sensor
Sensor
369833b 2 04.16.15
Specifications
Regulatory Approvals
• UL Listed to U.S. and Canadian safety requirements
• Title 20/24 certified lighting control device
– Complies with Title 20 and Title 24 Section 110.9
Power
• Operating voltage: 120 – 277 V~ 50/60 Hz
Loads
• 8 A 0 –10 V- electronic fluorescent ballasts or
LED drivers
• Works with all ballasts and drivers that provide a
current source compliant to IEC 60629 Annex E.2,
and whose inrush current does not exceed
NEMA410 standards for electronic ballast/driver
loads of 8 A steady state current.
• 50 mA max sink current
• Controls up to 25 ballasts or drivers (IEC 60929
Annex E.2 requires the ballast /driver to limit the
current draw to 2.0 mA maximum)
Environment
• Ambient operating temperature: 32 °F to 104 °F
(0 °C to 40 °C), 0% – 90% humidity, non-condensing;
indoor use only
Warranty
• 5 Year Limited Warranty
For additional Warranty information, please visit:
www.lutron.com/TechnicalDocumentLibrary/Sensor_
Warranty.pdf
Additional Information on Sensors
• For single-circuit PIR Maestro® occupancy sensor
switch models, refer to Lutron® P/N 369666
• For Maestro® occupancy sensor C•L® dimmer
models, refer to Lutron® P/N 369748
• For dual-circuit PIR Maestro® occupancy sensor
switch, refer to Lutron® P/N 369758
• For dual technology occupancy sensor switch
models, refer to Lutron® P/N 369773
• For more information, please see
www.lutron.com/occvacsensors
• Lutron Technical Hotline: 1.800.523.9466.
Select Design Feature Details
• Selectable dimming curve—linear or square law.
Drivers exist with linear response and some exist
with square law response. By providing a selectable
dimming curve from the 0 –10 V Dimmer Sensor, the
user is able to choose his/her preferred response for
optimized dimming performance.
• Miswire and incompatible load alert. The user will
receive a visual alert when the product’s 0 –10 Vcontrol wires are incorrectly connected or an
incompatible load is detected. In these conditions,
the product will still function as a switch. Refer to
Application Note 048536 for more details.
• Fade-to-On and Fade-to-Off.
Key Design Features
•
•
•
•
•
Dimmer
On a single-tap, lights fade ON or OFF
On a double-tap, lights go to full ON
Light levels can be fine-tuned by pressing and
holding the dimming rocker until the desired light
level is reached
High-end trim (adjust maximum light level that can be
achieved, for energy savings)
Low-end trim (adjust minimum light level that can be
dimmed down, to prevent flickering lights)
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
2
Maestro®
Maestro® 0–10 V Dimmer Sensor
Sensor
369833b 3 04.16.15
Load Type and Capacity
with Multi-Location
Neutral
Vacancy 0 –10 V- Voltage/Load Type/Maximum Load Minimum 3-Way
Mechanical
with Accessory
1,2
3
Connection Only
Current
(Anywhere in gang)
Load
Switch
Switch
50
mA
120 – 277 V~ Electronic fluorescent
MS-Z101Optional
—
0A
P
P
max sink ballast or LED drivers, 8 A
50mA
MS-Z101-V
Optional
0A
P max sink 120 V~ Fan 4.4 A (1/6 HP)4
P
P
Control
1
The 0 –10 V- control wires are not to exceed 250 ft (76.2 m) in length, and must have a size of no less than 20 AWG (0.75 mm2).
The 0 –10 V- wires must be installed as Class One per NEC® or local jurisdiction.
3 Dimmer Sensor load type: Designed for use with permanently installed electronic fluorescent ballast or LED driver lighting loads. Do not install dimmers to
control receptacles or motor-operated appliances.
4 When controlling light and fan loads simultaneously on a single circuit, maximum load capacity per circuit is 4.4 A at 120 V~.
2
Notes:
• Ground or neutral is required for product to function.
If neither is present, consult a licensed electrician.
• When power is applied, the Dimmer Sensor can be
manually turned on or off after the first 10 seconds
and will automatically control the load after
2 minutes.
• Works with all ballasts and drivers that provide a
current source compliant to IEC 60929 Annex E.2.
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
3
Maestro®
Maestro® 0–10 V Dimmer Sensor
Sensor
369833b 4 04.16.15
Custom Settings (default settings shown in
•
•
•
•
: Timeout
30 min
15 min
5 min
1 min
•
•
•
•
Mode: Sensor Modes
Lights automatically turn off in all sensor modes
Occ: Occupancy mode (No ALD)
Lrn: Occupancy with learning ALD mode
Fixd: Occupancy with fixed ALD mode
Vac: Vacancy mode (No ALD)
bold )
PIR: Passive Infrared Sensitivity
• Hi
•Med
•Low
•Min
•
•
•
•
Fade On Rate
15 sec
5 sec
2.5 sec
0.75 sec
•
•
•
•
Fade Off Rate
15 sec
5 sec
2.5 sec
0.75 sec
•
•
•
•
•
Additional Settings
Fixed ALD Light Level
•Hi
•Med
• Low *
•Min
* Low is the default setting for any sensor that is set by the user to
“Occupancy with fixed ALD mode”
Manual Off-While-Occupied
• Enabled
•Disabled
Walk-Thru Mode
•Enabled
• Disabled
Occupied Level
A programmable setting that determines the light
level the Dimmer Sensor will turn on to, once
occupancy has been detected
• 100%
•50%
• Preset Level
– When the Occupied Level is set to Preset Level,
the Dimmer Sensor will automatically and manually
turn on to the selected Preset Level.
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Preset Level**
Locked (High range)
Locked (Med range)
Locked (Low range)
Locked (Min range)
Unlocked
– When the Preset Level is set to a locked level, the
Dimmer Sensor will turn ON to the predetermined
“locked” level with a single tap of the Tap button.
– When the Preset Level is set to unlocked, a single
tap of the Tap button will turn the Dimmer Sensor
ON to the light level to which it was adjusted the
last time the light was on.
•
•
•
•
Low-End Trim**
High range
Med range
Low range
Min range
•
•
•
•
High-End Trim**
High range
Med range
Low range
Min range
** Setting is fully variable within each range.
Page
4
Maestro®
Maestro® 0–10 V Dimmer Sensor
Sensor
369833b 5 04.16.15
Custom Settings: Details (default settings shown in
bold )
Ambient Light Detection (ALD) mode
Lights turn on only when natural light in the room is
below the set threshold.
• Enabled
– Learning: The ambient light threshold adjusts to
the user’s preference via manual interaction with
the Dimmer Sensor.
– Fixed: Choose a fixed ALD light level from
4 pre‑set options: High, Medium, Low, Minimum.
• Disabled
Fade-On Rate
The time required for the lights to reach the preset
light level when the tap button is pressed.
Manual Off-While-Occupied Options
• Enabled
– When the Dimmer Sensor is manually turned off,
the sensor switch will not turn the lights back on
automatically while the room is occupied.
– Once the room is vacated, the Auto-On feature
returns to normal operation after the timeout
period has expired.
– This may be the preference in conference rooms
or classrooms while viewing presentations. This
feature requires motions to keep the lights off.
• Disabled
– When the Dimmer Sensor is manually turned off,
the Auto-On feature will return to normal operation
after 25 seconds.
– This may be the preference in a restroom if the
user always wants the lights to turn on upon
entering and the lights to turn off when the room is
vacant.
High-End trim
Highest achievable light level to which the Dimmer
Sensor can be adjusted.
Fade-Off Rate
The time required for the lights to turn off (from the
ON state) when the tap button is pressed.
Low-End Trim
Lowest achievable light level to which the Dimmer
Sensor can be adjusted.
Walk-Thru Mode
• Enabled*
– If motion is not detected within 3 minutes after
initial occupancy, the lights will turn off after
3 minutes, instead of the current timeout.
– This setting may be the preference in commercial
applications where personnel may briefly trigger
sensors during non-working hours.
• Disabled
– When motion is detected, the lights will ALWAYS
remain on for the entire timeout duration
regardless of the duration of occupancy detection.
* 1 minute timeout would be overridden if walk-thru mode is also Enabled
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
5
Maestro®
Maestro® 0–10 V Dimmer Sensor
Sensor
369833b 6 04.16.15
Maestro® 0 – 10 V Dimmer Sensor Placement and Operation
• The ability of the Dimmer Sensor to detect motion requires line-of-sight of room occupants. The Dimmer Sensor
must have an unobstructed view of the room.
• Hot objects and moving air currents can affect the performance of the Dimmer Sensor. For best performance, the
Dimmer Sensor should be mounted at least 4 ft (1.2 m) away from HVAC vents and light bulbs.
• The performance of the Dimmer Sensor depends on a temperature differential between the ambient room
temperature and that of room occupants. Warmer rooms may reduce the ability of the Dimmer Sensor to detect
occupants.
NEMA WD7 Test Grid Coverage
(High Sensitivity Setting)
Horizontal Beam Diagram
(For Reference Only)
Major motion coverage: 900 ft2 (81 m2)
Minor motion coverage: 400 ft2 (36 m2)
15 ft
(4.5 m)
15 ft
(4.5 m)
10 ft
(3 m)
10 ft
(3 m)
5 ft
(1.5 m)
5 ft
(1.5 m)
0
0
5 ft
(1.5 m)
5 ft
(1.5 m)
10 ft
(3 m)
10 ft
(3 m)
15 ft
(4.5 m)
15 ft
(4.5 m)
0
5 ft
(1.5 m)
10 ft
(3 m)
15 ft
(4.5 m)
20 ft
(6 m)
25 ft
(7.5 m)
30 ft
(9m)
Vertical Beam Diagram
(For Reference Only)
4 ft
(1.2 m)
0
10 ft
(3 m)
20 ft
(6 m)
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
30 ft
(9m)
Page
6
Maestro®
Maestro® 0–10 V Dimmer Sensor
Sensor
369833b 7 04.16.15
Dimensions
Operation
Measurements shown as: in (mm)
Coopersburg, PA
800.523.9466
lutron.com
Side View
Front View
TURN OFF POWER
ARRETEZ LE COURANT
DESCONECT LA CORRIENTE
Up
Tap button
(tap on/off)
Programming
LEDs
Raise
Timeout
button
Sensor Mode
button
411⁄16
(119)
Sensor LED
(behind lens)
pulses during
Test mode
Alt
30 m
15
5
1
Alt button
Lower
PIR
Mode
Hi
Med
Low
Min
Occ
Lrn
Fixd
Vac
PIR sensitivity
button
PIR sensitivity
lens
120 – 277 V~
50 / 60 Hz
8A
215⁄16
(75)
5/16 (3)
11 ⁄8
(30)
1/8 (3)
Mounting
Wallbox
Recommended dimensions:
3.5 in (89 mm) D × 3 in (76 mm) H × 2 in (51 mm) W
Dimmer Sensor
Wallplate Adapter/ Wallplate
(sold separately)
30
15
5
1
Mounting
screws
e
Mod
Occ
Lr n
d
Fix
Vac
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Adapter
mounting
screws
Page
7
Maestro®
Maestro® 0–10 V Dimmer Sensor
Sensor
369833b 8 04.16.15
Wiring Installations with the Maestro® 0 – 10 V Dimmer Sensor
In order to function, the 0 –10 V Dimmer Sensor
must either have the green/yellow wire connected
to ground, or, with the white sleeve covering the
green/yellow wire, connect to neutral.
Before installing wallplate, program all desired
settings.
Coopersburg, PA
800.523.9466
lutron.com
TURN OFF POWER
ARRETEZ LE COURANT
DESCONECT LA CORRIENTE
Up
Alt
30 m
15
5
1
Mode
Occ
Lrn
Fixd
Vac
PIR
Hi
Med
Low
Min
Green/Yellow wire connects to
ground
Green/Yellow wire
covered by white
sleeve connects to
neutral
120 – 277 V~
50 / 60 Hz
8A
Wiring: Single-Pole Installation
Without Neutral
Coopersburg, PA
Line/Hot
Black
120 – 277 V~
50/60 Hz
TURN OFF POWER
ARRETEZ LE COURANT
DESCONECT LA CORRIENTE
800.523.9466
lutron.com
Black
Up
Alt
30 m
15
5
1
PIR
Mode
Hi
Med
Low
Min
Occ
Lrn
Fixd
Vac
Blue1
Gray (–)
Purple (+)
Gray (–)
Purple (+)
Gray (–)
Purple (+)
White
Black
White
Black
Gray (–)
Purple (+)
Gray (–)
Purple (+)
White
Black
White
Black
120 – 277 V~
50 / 60 Hz
8A
Green
Green/Yellow
Ground
Neutral
With Neutral
Coopersburg, PA
Line/Hot
Black
120 – 277 V~
50/60 Hz
TURN OFF POWER
ARRETEZ LE COURANT
DESCONECT LA CORRIENTE
800.523.9466
lutron.com
Black
Up
Alt
30 m
15
5
1
Mode
Occ
Lrn
Fixd
Vac
PIR
Hi
Med
Low
Min
Blue1
Gray (–)
Purple (+)
120 – 277 V~
50 / 60 Hz
8A
Green
Ground
Neutral
1
2
White2
When using controls in single location installations, cap the blue wire. Do not connect the blue wire to any other wiring or to ground.
Green/Yellow wire covered by white sleeve connects to neutral.
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
8
Maestro®
Maestro® 0–10 V Dimmer Sensor
Sensor
369833b 9 04.16.15
Wiring: 3-Way Installation* with Standard Mechanical Switch**
Without Neutral
Blue1
Coopersburg, PA
Line/Hot
Black
120 – 277 V~
50/60 Hz
TURN OFF POWER
ARRETEZ LE COURANT
DESCONECT LA CORRIENTE
800.523.9466
lutron.com
Up
Black
Alt
30 m
15
5
1
PIR
Mode
Hi
Med
Low
Min
Occ
Lrn
Fixd
Vac
Gray (–)
Blue
Gray (–)
Purple (+)
Purple (+)
Gray (–)
Purple (+)
White
Black
White
Black
Gray (–)
Purple (+)
Gray (–)
Purple (+)
White
Black
White
Black
120 – 277 V~
50 / 60 Hz
8A
Green
Green/Yellow
Ground
Ground
Neutral
With Neutral
Blue1
Coopersburg, PA
Black
Line/Hot
120 – 277 V~
50/60 Hz
TURN OFF POWER
ARRETEZ LE COURANT
DESCONECT LA CORRIENTE
800.523.9466
lutron.com
Up
Black
Alt
30 m
15
5
1
Mode
Occ
Lrn
Fixd
Vac
PIR
Hi
Med
Low
Min
Blue
Gray (–)
Purple (+)
120 – 277 V~
50 / 60 Hz
8A
Green
Ground
Ground
Neutral
*
**
1
2
White2
One Dimmer Sensor can be installed in any location.
Important: Some rewiring of 3-way mechanical switch is required. See page 10 for instructions.
The length of the Blue wire (3-way wire) must not exceed 150 ft (45.72 m).
Green/Yellow wire covered by white sleeve connects to neutral.
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
9
Maestro®
Maestro® 0–10 V Dimmer Sensor
Sensor
369833b 10 04.16.15
3-Way Retrofit Installation
For retrofit 3-way installations, the mechanical switch needs to be rewired as shown in the diagram below after
wiring the Dimmer Sensor. Otherwise, the 3-way installation will not work as expected. Single-pole mechanical
switches may also be used in a 3-way installation with MS-Z101 and MS-Z101-V models.
1.Connect Ground: Ensure that the bare copper or green ground wire from the wallbox is connected to the green
ground screw of the mechanical switch.
2.Tag circuit Common: Your 3-way mechanical switch should have three screw terminals, two of the same color,
and one of a different color. Tag the wire that is connected to the screw terminal of a different color.
3.Identify the wire that matches the color of the wire you connected to the blue wire of the Maestro® Dimmer Sensor.
Connect this wire to one of the two terminals of the same color.
4.Combine the tagged wire, the remaining wire, and the yellow jumper wire (included) using a wire connector.
Connect the other end of jumper wire to the different color screw.
Note: If the 0 –10 V Dimmer Sensor is first installed with a traditional 3-way mechanical switch and the mechanical
switch is later replaced with a Maestro® Accessory Switch, the 0 –10 V Dimmer Sensor will need to be
returned to factory default settings in order to function correctly.
Traditional 3-Way
Mechanical Switch Wiring
Traveler
Rewired to
3-Way Mechanical Switch Wiring
with Dimmer Sensor
Traveler
Traveler (to Blue wire)
Yellow Jumper wire
(included)
Common
Different
color screw
Tagged wire
(Common)
Different
color screw
Traveler
(to Black wire)
Ground
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Ground
Page
10
Maestro®
Maestro® 0–10 V Dimmer Sensor
Sensor
369833b 11 04.16.15
Wiring: 120 V~ Multi-Location Installation* with Maestro® Accessory Switches
Note: If the 0 –10 V Dimmer Sensor is first installed with a traditional 3-way mechanical switch and the mechanical
switch is later replaced with a Maestro® Accessory Switch, the 0 –10 V Dimmer Sensor will need to be
returned to factory default settings in order to function correctly.
Without Neutral
Blue1
Blue
Blue
Coopersburg, PA
Line/Hot
Black
Brass
Black
Brass
Black
120 V~
50/60 Hz
TURN OFF POWER
ARRETEZ LE COURANT
DESCONECT LA CORRIENTE
800.523.9466
lutron.com
Up
Black
Gray (–)
Alt
30 m
15
5
1
PIR
Mode
Hi
Med
Low
Min
Occ
Lrn
Fixd
Vac
MA-AS or
MSC-AS
MA-AS or
MSC-AS
Green
Purple (+)
Gray (–)
Purple (+)
120 – 277 V~
50 / 60 Hz
8A
Green
Ground
Gray (–)
Purple (+)
White
Black
White
Black
Green
Ground
Green/Yellow
Ground
Neutral
With Neutral
Blue1
Blue
Blue
Coopersburg, PA
Line/Hot
Black
Brass
Black
Brass
120 V~
50/60 Hz
Black
TURN OFF POWER
ARRETEZ LE COURANT
DESCONECT LA CORRIENTE
800.523.9466
lutron.com
Up
Black
Gray (–)
Alt
30 m
15
5
1
Mode
Occ
Lrn
Fixd
Vac
MA-AS or
MSC-AS
MA-AS or
MSC-AS
Green
Ground
PIR
Hi
Med
Low
Min
Gray (–)
Purple (+)
Purple (+)
Gray (–)
Purple (+)
White
Black
White
Black
120 – 277 V~
50 / 60 Hz
8A
Green
Ground
Green
White2
Ground
Neutral
* One Dimmer Sensor can be installed in any location.
1 The length of the Blue wire (3-way wire) must not exceed 150 ft (45.72 m).
2 Green/Yellow wire covered by white sleeve connects to neutral.
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
11
Maestro®
Maestro® 0–10 V Dimmer Sensor
Sensor
369833b 12 04.16.15
Wiring: 220–277 V~ Multi-Location Installation with Maestro® Accessory Switches
Note: If the 0 –10 V Dimmer Sensor is first installed with a traditional 3-way mechanical switch and the mechanical
switch is later replaced with a Maestro® Accessory Switch, the 0 –10 V Dimmer Sensor will need to be
returned to factory default settings in order to function correctly.
Without Neutral
Blue1
Blue
Blue
Coopersburg, PA
Line/Hot
Black
Red
Black
Red
Black
220 – 277 V~
50/60 Hz
TURN OFF POWER
ARRETEZ LE COURANT
DESCONECT LA CORRIENTE
800.523.9466
lutron.com
Up
Black
Gray (–)
Alt
30 m
15
5
1
PIR
Mode
Hi
Med
Low
Min
Occ
Lrn
Fixd
Vac
MA-AS-277 or
MSC-AS-277
MA-AS-277 or
MSC-AS-277
Green
Purple (+)
Gray (–)
Purple (+)
Purple (+)
120 – 277 V~
50 / 60 Hz
8A
Green
Ground
Gray (–)
White
Black
White
Black
Green
Ground
Green/Yellow
Ground
Neutral
With Neutral
Blue1
Blue
Blue
Coopersburg, PA
Line/Hot
Black
Red
Black
Red
220 – 277 V~
50/60 Hz
Black
TURN OFF POWER
ARRETEZ LE COURANT
DESCONECT LA CORRIENTE
800.523.9466
lutron.com
Up
Black
Gray (–)
Alt
30 m
15
5
1
Mode
Occ
Lrn
Fixd
Vac
MA-AS-277 or
MSC-AS-277
MA-AS-277 or
MSC-AS-277
Green
Ground
PIR
Hi
Med
Low
Min
Gray (–)
Purple (+)
Gray (–)
Purple (+)
Purple (+)
White
Black
White
Black
120 – 277 V~
50 / 60 Hz
8A
Green
Ground
Green
White2
Ground
Neutral
* One Dimmer Sensor can be installed in any location.
1 The length of the Blue wire (3-way wire) must not exceed 150 ft (45.72 m).
2 Green/Yellow wire covered by white sleeve connects to neutral.
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
12
Maestro®
Maestro® 0–10 V Dimmer Sensor
Sensor
369833b 13 04.16.15
Colors and Finishes
Gloss Finishes
A/E: Please confirm color.
Satin Finishes
White
WH
Ivory
IV
Hot
HT
Merlot
MR
Plum
PL
Turquoise
TQ
Almond
AL
Light Almond
LA
Taupe
TP
Eggshell
ES
Biscuit
BI
Snow
SW
Gray
GR
Brown
BR
Palladium
PD
Midnight
MN
Sienna SI
Terracotta
TC
Greenbriar
GB
Bluestone
BG
Mocha Stone
MS
Goldstone
GS
Desert Stone
DS
Stone
ST
Limestone
LS
Sea Glass
SG
Black
BL
• Due to printing limitations, colors and finishes shown cannot be guaranteed to perfectly match actual product
colors.
• Color chip keychains are available for more precise color matching:
– Gloss Finishes: DG-CK-1
– Satin Finishes: SC-CK-1
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
13
Sensors
LOS-CDT Series
Occupancy Sensors
369653c 1 02.07.13
Dual Technology Ceiling Mount Sensor
The LOS-CDT Series dual technology ceiling-mount
sensors can integrate into LutronR systems or function
as stand-alone controls using a LutronR power pack.
The technology eliminates manual sensitivity and timer
adjustments during installation and over the life of the
product.
Features
• Intelligent, continually adapting sensor
• Ultrasonic (US) combined with Passive Infrared (PIR)
sensing provide high sensitivity, high noise immunity,
and excellent false tripping immunity
• Suited for complex environments that are difficult to
control with single-technology sensors
• Snap-locks to ceiling-mounted cover plate
• Non-Volatile Memory: settings saved in protected
memory are not lost during power outages
• 500 ft( to 2000 ft( (46 m( to 186 m() coverage when
mounted on an 8 ft to 12 ft (2.4 m to 3.7 m) ceiling
• Affords choice of turning lights off or dimming to a
preset level in the unoccupied state when integrated
with a LutronR system.
A/E: Please confirm correct color.
Models Available
Model
Color Coverage
Field of
View
500 ft( (46 m()
180°
500 ft( (46 m()
180°
1000 ft( (93 m() 180°
1000 ft( (93 m() 180°
2000 ft( (186 m() 360°
2000 ft( (186 m() 360°
LOS-CDT-500-WH
LOS-CDT-500R-WH
LOS-CDT-1000-WH
LOS-CDT-1000R-WH
LOS-CDT-2000-WH
LOS-CDT-2000R-WH
White
White
White
White
White
White
Self-Adaptive Feature
The LOS-CDT Series sensors combine both Ultrasonic
(US) motion detection for maximum sensitivity and
Passive Infrared (PIR) motion detection for false
triggering immunity. The self-adapting internal
microprocessor analyzes the composite sum of both
signals to eliminate time-consuming adjustments and
callbacks found in non-intelligent sensors.
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
1
Sensors
LOS-CDT Series
Occupancy Sensors
369653c 2 02.07.13
Specifications
Housing
Regulatory Approvals
•Rugged, high-impact, injection-molded plastic
•Color-coded leads 6 in (15 cm)
•ULR and cULR listed
Power
•Operating voltage: 20 – 24 V-, IEC PELV/NECR
Class 2
•Operating current: 33 mA nominal
•Control output: 20 – 24 V- active high logic control
signal with short-circuit protection, open collector
when unoccupied
Environment
•Temperature: 32 °F to 104 °F (0 °C to 40 °C)
•Relative humidity: less than 95%, non-condensing
• For indoor use only
Timer Adjustment
•Automatic mode: Continually adapting sensor
automatically adjusts settings to the space
•Manual mode: 8 to 30 minutes
•Test mode: 8 seconds
Adaptive Functions
•Installation: 60 minutes
•Learning: 4 weeks for response to error conditions, air
current adaptation, and timer optimization
•Post-learning occupancy periods
—24 hour circadian occupancy periods learned
—Weekly occupancy periods learned
•Adjustments in post-learning period
—Generally occupied periods
(threshold = high-sensitivity mode)
—Generally unoccupied periods
(threshold = miser mode)
Contact Rating (R Models only)
•SPDT 500 mA rated at 24 V- isolated relay
Photo Cell (R Models only)
•Prevents light from turning on when there is sufficient
natural light
•Sensitivity: 0 lx to 1000 lx adjustable
LED Lamp
•Red: infrared motion detected
•Green: ultrasonic motion detected
Dimensions
1.4 in
(38 mm)
4.5 in
(114 mm)
Front View
Side View
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
2
Sensors
LOS-CDT Series
Occupancy Sensors
369653c 3 02.07.13
Wiring: System Control
Power packs may be required when interfaced to LutronR lighting control systems. If more than 1 occupancy
sensor is connected to the same input, a power pack is required. A maximum of 3 occupancy sensors can be
connected to the same input. If more than 3 sensors are required per input, use one of the following models:
LOS-CDT-500R-WH, LOS-CDT-1000R-WH, or LOS-CDT-2000R-WH.
Power Supply Options
LutronR Lighting Control System
Power Pack Required?
Digital microWATTT
EcoSystemR
Energi Savr NodeT
GRAFIK 5000T/6000R/7000T
No
No
No*
No, when used with seeTouchR wallstations with occupancy sensor
connections.
Yes
No*
Yes
No*
No, when used with seeTouchR wallstations with occupancy sensor
connections.
No
No*
Yes
Yes
No, when used with seeTouchR wallstations with occupancy sensor
connections.
GRAFIK EyeR 3000/4000
GRAFIK EyeR QS
HomeWorksR
HomeWorksR QS
LCP128T
microWATTR
QuantumR
RadioRAR
RadioRAR 2
Softswitch128R
*S
ome system components do not supply external power for occupancy sensors. Refer to individual product
specifications for more information.
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
3
Sensors
LOS-CDT Series
Occupancy Sensors
369653c 4 02.07.13
Wiring: Stand-Alone Control
1 to 3 Sensors with Power Pack
Line
120 / 277 / 347 V~ 60 Hz;
230 V~ 50 / 60 Hz
Neutral
Red (+20 – 24 V-)
Blue* (signal)
Power
Pack
Black
(common)
Black
White
Red
Red
Lighting
Load
NOTE: Maximum 3 occupancy sensors.
Switching Multiple Loads with Auxiliary Power Packs
Line
120 / 277 / 347 V~ 60 Hz
230 V~ 50 / 60 Hz
Neutral
Lighting
Load
Red
Red
Auxiliary
Power
Pack
Red (+20 – 24 V-)
Blue* (signal)
Black
(common)
Power
Pack
Black
White
Red
Red
Lighting
Load
NOTE: Maximum of 3 devices total (occupancy sensors and auxiliary power packs) can be connected to a power pack.
*Use gray wire for LOS-CDT-500R-WH, LOS-CDT-1000R-WH, and LOS-CDT-2000R-WH.
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
4
Sensors
LOS-CDT Series
Occupancy Sensors
369653c 5 02.07.13
Wiring
Relay Model Option
LOS-CDT-500R-WH, LOS-CDT-1000R-WH, and LOS-CDT-2000R-WH only
Red (+20 – 24 V-)
Lighting
Control
system*
Gray (control: occupancy and photo cell signal)
Blue: Cap off
Black (common)
Gray wire logic with photo cell active:
Room First Occupied
Light level
During Occupancy
Lights
Light level
Lights
Below set value
Turn on
Falls below set value
Turn on
Above set value
Remain off
Moves above set value
Remain on
*May require power pack
Yellow/White (NO)
Black/White (NC)
Blue/White (Relay, Common)
Choose wire based on functionality):
• Yellow/White: NO (normally open)
Open: Unoccupied
Closed: Occupied
• Black/White: NC (normally closed)
Open: Occupied
Closed: Unoccupied
Cap off unused wire.
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
5
Sensors
LOS-CDT Series
Occupancy Sensors
369653c 6 02.07.13
Installation
Sensor Setup
•Sensor setup is available as a service by Lutron. For more information see the Sensor Layout and Tuning
service document (LutronR P/N 3601235).
Sensor Placement
•Mount the sensor so the grilles face the open portion of the room and are not facing a nearby wall, window, or
other obstructing object.
•Do not place sensor within 6 ft (1.8 m) of air vents, air handlers, windows, fans, etc., as this may cause false
triggering.
•If installing a 180° occupancy sensor (500 and 1000 models), place the sensor on the same wall as the doorway
so that traffic in a hallway will not affect the sensor; otherwise, place in center of room.
•Closely follow the diagrams shown concerning major and minor motion coverage. The sensor can detect major
motion (e.g. person taking a half-step) at a greater distance than it can detect minor motion (e.g. writing at a
desk or reading a book).
•Decrease total coverage area by 15% for “soft” rooms (e.g. heavy draperies or thick carpeting).
Range Diagrams
32 ft (9.8 m)
23 ft (7 m)
23 ft (7 m)
16 ft (4.9 m)
23 ft 32 ft
(7 m) (9.8 m)
16 ft 23 ft
(4.9 m) (7 m)
12 ft (3.7 m)
22 ft (6.7 m)
12 ft (3.7 m)
22 ft (6.7 m)
LOS-CDT-500
LOS-CDT-1000
64 ft (19.5 m)
45 ft (13.7 m)
Major motion detection (Ultrasonic)
Minor motion detection (Ultrasonic)
23 ft 32 ft
(7 m) (9.8 m)
Major motion detection (Passive Infrared)
Minor motion detection (Passive Infrared)
LOS-CDT-2000
12 ft (3.7 m)
22 ft (6.7 m)
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
6
Sensors
LOS-CDT Series
Occupancy Sensors
369653c 7 02.07.13
Mounting
Normal Mounting
Mounting to Non-Standard Ceiling or Fixture
Twist and lock threaded mounting post onto cover
plate. Drill through ceiling tile with assembly, using
cutter end of the threaded mounting post. Secure
with washer and nut.
Mount twist-lock cover plate using mounting screws,
nuts, and washers (included). Drill/punch wire routing
hole through ceiling tile at center of cover plate.
13/16 in (21 mm)
Cutter
end
Wire Lengths
Mounting Plate Dimensions
0.52 in
(13.3 mm)
2.5 in
(63 mm)
4.2 in
(106.6 mm)
Number of Sensors
1
2
3
1
2
1
Number of Auxiliary
Power Packs
0
0
0
1
1
2
22 AWG
750 ft
375 ft
0.5 mm(
365 m
180 m
120 m
90 m
120 m
120 m
20 AWG
1200 ft 600 ft
400 ft
600 ft
400 ft
400 ft
0.75 mm(
730 m
240 m
365 m
240 m
365 m
18 AWG
2400 ft 1200 ft 800 ft
1200 ft 800 ft
800 ft
Using the Infrared Mask
Center Ceiling Mount
(Mask blocks sensor seeing
out doorway into hall)
Job Number:
375 ft
250 ft
250 ft
Typical Mask Patterns
Corner Ceiling Mount
(No mask needed)
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
365 m
250 ft
Conference
Room Mask
180° Mask
Rectangular
Areas
Over the Door
Full Mask
Specific Areas
You Wish to
Mask
Page
7
Sensors
LOS-CDT Series
Occupancy Sensors
369653c 8 02.07.13
Sensor Adjustments
Override Settings
Auto/Manual
Threshold
LED Motion Indicator
Reset Learned Settings
A Off (Default)
On
1
2
3
4
Manual on / off (Override)
Automatic (Normal)
Auto Threshold Adjustment
High Sensitivity (Low turn-on threshold)
Lights indicate motion
Disable LED Indicator
Retain Settings (Normal)
Erase all learned settings; Restart Learning (Toggle On)
OFF ON
Strong Airflow Compensation
Over Doorway Installation
Timer Adjust
Auto Sensitivity
OFF
(Default)
B OffON
1
2
3
4
On
Disable Compensation (Normal)
Enable Compensation
No (Normal)
Yes (Use increased turn-on threshold)
Adjust Timer Automatically
Use Manual Setting (No adjustment)
Adjust Sensitivity Automatically
Adjust Sensitivity Manually
OFF ON
OFF ON
Timer Test Mode
Factory Settings
1. Remove the retainer cover.
otate the black timer adjustment knob to about
2. R
midway (12 o’clock).
3. Return setting to minimum setting (full CCW).
Factory Settings
12 o’clock
Full CCW
NOTE: The timer will remain in the 8 second test mode
for 1 hour, then automatically reset to 8 minutes.
Red:
Infrared
sensitivity
75% default
Black: Timer
8 min
A
B
ON
ON
1
2
3
4
1
2
3
4
Green:
Ultrasonic
range
50% default
Blue:
Photo cell
(R models only)
100% default
4. T
o manually take the timer out of the 8 second test
mode, turn the timer adjustment approximately 1/16 in
(1.5 mm) clockwise to make the setting slightly above
minimum (just above the 8 minute setting).
Continued on next page...
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
8
Sensors
LOS-CDT Series
Occupancy Sensors
369653c 9 02.07.13
Sensor Adjustments (continued)
Adjusting the “Lights Not On” Level
Control Settings (Blue Knob)
LOS-CDT-500R-WH, LOS-CDT-1000R-WH, and LOS-CDT-2000R-WH only
LOS-CDT-500R-WH, LOS-CDT-1000R-WH, and LOS-CDT-2000R-WH only
1. Place timer in Test Mode (see page 8).
2. Set photo cell to maximum. Turn the blue knob full
clockwise (lights on no matter how bright the natural
light is), then about 30° counterclockwise.
3. Check for Lights-Out. Move from underneath the
sensor, and remain still until the lights turn off. Move
around normally to turn the light on.
4. Adjust to desired level. If lights remain off, adjust the
blue knob another 30° counterclockwise and repeat
step 3 until the lights turn on.
Minimum (low):
Lights will never come on, even though
room is occupied.
0
1000
Maximum (high):
Photo cell has no effect on operation
(factory setting).
0
1000
NOTE: Set blue knob to 100% to disable photo cell
functionality and leave secondary dry contact closure
output functionality intact.
Normal:
200 lx to 600 lx is normal range.
0
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
1000
Page
9
PP and UPP Series
-DV, -DV-M, -347H, -SH
Power Packs
369544f 1 03.13.15
PP and UPP Series Power Packs
PP and UPP* Series Power Packs provide both the
24 V- power supply to operate LutronR wired occupancy
sensors, as well as the 16 A line-voltage relay to control the
load, in one compact housing. The unit can be mounted
inside a ballast enclosure or inside / outside a junction box.
The manual-ON Power Pack (-DV-M) is used to provide
a vacancy solution when paired with LutronR wired
occupancy sensors. A low-voltage momentary switch
should be used to manually turn ON the load while the
sensor automatically shuts the load OFF when unoccupied.
Pressing the momentary switch can also turn the load OFF.
(-DV)
(-DV-M)
(-347H)
The auxiliary Power Pack (-SH) must be used in
conjunction with at least one line-voltage Power Pack and
one Lutron wired occupancy sensor to switch additional
loads.
Features
•High-impact UL94 flammability-rated plastic case
construction
•Relay: Class B 266 °F (130 °C) insulating material; silver
alloy contacts
•Complies with requirements for use in a compartment
handling environmental air (plenum) per NEC® 2011
300.22(C)(3)
•Power Pack units (PP-DV / UPP-DV, PP-347H,
PP-DV-M / UPP-DV-M) power up to 3 total devices.
PP-SH / UPP-SH counts as 1 device, each occupancy
sensor counts as 1 device.
•For indoor use only, 32 °F to 104 °F (0 °C to 40 °C), 0% to
90% humidity, non-condensing
(-SH)
Model
Power Input
Relay Contact Rating
PP-DV
UPP-DV
PP-DV-M
UPP-DV-M
PP-347H
120-277 V~
50/60 Hz
6.5 W
•1
20-277 V~ 16 A;
All lighting loads**
• 120-277 V~ 1 HP Motor Load
347 V~ 60 Hz
6.5 W
24 V(At least one
line-voltage Power
Pack must be used)
• 347 V~ 15 A Ballast
24 V- 5 mA
•1
20-277 V~ 16 A;
All lighting loads**
• 120-277 V~ 1 HP Motor Load
• 347 V~ 15 A Ballast
24 V- 5 mA
PP-SH
UPP-SH
Control Input IEC PELV/ NEC®
Class 2 Output
24 V- 5 mA 24 V- 150 mA
up to 3 Devices ***
24 V- 100 mA
up to 3 Devices ***
N/A
* “U” denotes BAA compliance
** Lighting loads include (but are not limited to): Incandescent, MLV, ELV, Resistive, Inductive
*** PP-SH / UPP-SH counts as 1 device and each occupancy sensor counts as 1 device
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page 1
PP and UPP Series
-DV, -DV-M, -347H, -SH
Power Packs
369544f 2 03.13.15
Specifications
Regulatory Approvals
Wiring
•UL® and cUL® Listed
•Complies with requirements for use in a
compartment handling conditioned air (plenum)
Power / Performance
•PP-DV, UPP-DV, PP-DV-M, UPP-DV-M:
120-277 V~ 50/60 Hz
•PP-347H: 347 V~ 60 Hz only
•7 in (178 mm) wire leads, 18 AWG (0.75 mm2) input;
7 in (178 mm) leads, 16 AWG (1.5 mm2) contacts.
Mounting
•Fits inside standard 4 in x 4 in (102 mm x 102 mm)
junction box or standard fluorescent fixture
ballast cavity
•Mount with 6/32 in (5 mm) x 11⁄4 in (32 mm) pan
head screws
•Mounts inside junction box through knockout,
with 1/2 in (13 mm) Electrical Metallic Tubing (EMT)
threaded nipple. Recommended volume is 30 in3
(762 mm3).
Dimensions
2.33 in
(59 mm)
1.36 in
(35 mm)
3.69 in
(94 mm)
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page 2
PP and UPP Series
-DV, -DV-M, -347H, -SH
Power Packs
369544f 3 03.13.15
Wiring
3 Sensors with Power Pack (PP-DV, UPP-DV or PP-347H) 1
Line / Hot
120-277 V~ 50/60 Hz (PP-DV / UPP-DV)
347 V~ 60 Hz (PP-347H)
Neutral
White
Black
Red (24 V-)
Blue (control)
Power Pack
(-DV or-347H)
Black (common)
Red
Manual switch OFF 2
(optional – sold
separately)
Occupancy Sensors 1
Lighting
Load
Red
Ground
Maximum 3 occupancy sensors can be used with PP-DV / UPP-DV or PP-347H.
When lights are manually turned off, switch must be returned back to the on position for occupancy sensors to function as set.
2
3 Sensors with Power Pack - Vacancy Solution (PP-DV-M, UPP-DV-M) 1
Line / Hot
120-277 V~
50/60 Hz
Neutral
Lighting
Load
White
Black
Red
Red
Ground
Power Pack
(-DV-M)
Red (24 V-)
Blue (control)
Black (common)
Orange
(manual override)
Low-Voltage
Momentary
Switch 2
Occupancy Sensors 1
Maximum 3 devices (excluding low-voltage momentary switches) can be used with PP-DV-M / UPP-DV-M. Each PP-SH / UPP-SH counts as one
device, each occupancy sensor counts as one device.
2
NTRCS-1 (Nova T*® momentary switch) or any low voltage momentary switch rated for at least 24 V-, 100 mA.
continued on next page...
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page 3
PP and UPP Series
-DV, -DV-M, -347H, -SH
Power Packs
369544f 4 03.13.15
Wiring (continued)
Switching Multiple Loads with 1 Power Pack and 1 Auxiliary Power Pack 1
Line / Hot
120-277 V~ 50/60 Hz
(PP-DV / UPP-DV);
347 V~ 60 Hz (PP-347H)
Neutral
Lighting
Load
Red
Red
Red (24 V-)
Blue (control)
Auxiliary
Power Pack
(-SH)
Black (common)
Power Pack
(-DV or-347H)
White
Black
Red
Red
Ground
Lighting
Load
Ground
Occupancy Sensors
1
Maximum of 3 devices can be used with PP-DV, UPP-DV, or PP-347H. Each PP-SH / UPP-SH counts as one device, each occupancy sensor counts as
one device.
Switching Multiple Loads with 2 Power Packs (PP-DV / UPP-DV)
120-277 V~ 50/60 Hz
(PP-DV / UPP-DV);
347 V~ 60 Hz (PP-347H)
Line / Hot
120-277 V~ 50/60 Hz
(PP-DV / UPP-DV);
347 V~ 60 Hz (PP-347H)
Neutral
Neutral
Red 1
White
Black
Red
Red
Lighting
Load
Power Pack
(-DV or -347H)
Red (24 V-)
Blue (control)
Black
(common)
White
Power Pack
(-DV or -347H)
Ground
Black
Red
Red
Lighting
Load
Ground
Occupancy Sensors
1
Only 1 Power Pack (PP-DV / UPP-DV) should power the occupancy senors. This 24 V- output is left disconnected.
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page 4
Diva®
0–10 V Control
Wallbox Controls
369147b 1 09.08.14
Diva® 0–10 V Controls
Controls for 0–10 V LED Drivers and
Fluorescent Ballasts.
Features
• Large paddle switch with a captive linear-slide
control for a standard designer-opening wallplate
• 0–10 V control link controls third party fixtures
• DVSTV- wires as single pole or 3-way,
120–277 V~ switch
• DVTV- wires as a 24 V- switch. A Power Pack is
required to switch 120–277 V~ and 347 V~
• Patented switching technology extends
product lifetime
• Coordinating Claro® and Satin Colors® wallplates
(available separately)
• High-end and low-end trim user adjustable for
optimal performance
Select light
level with slider
Switch on
(to selected
light level)/off
Diva® 0–10 V Control
A/E: Please confirm color, page 13.
Model Numbers
Model Number Operating Voltage
1
DVSTV-XX
120 –277 V~
2
DVSCSTV-YY
1
DVTV-XX
24 V2
DVSCTV-YY
1
2
3
4
Load Switching
Wiring
Capacity
3
Single pole / 3-way 8 A
Single pole only
0 A4
0–10 V Sink
Capacity
50 mA
30 mA
“XX” in the model number represents gloss finish color code. See Standard Colors and Finishes on Page 3.
“YY” in the model number represents satin finish color code. See Standard Colors and Finishes on Page 3.
For 3-way switching, use Claro ® switches or other mechanical switches.
A Lutron® Power Pack (PP-DV or PP-347H) is required for switching ballasts and drivers. For Lutron ® Power Pack Specification please see Lutron ® P/N 369544.
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
Job Number:
Page 1
Diva®
0–10 V Control
Wallbox Controls
369147b 2 09.08.14
Specifications
DVSTV- Models
Regulatory Approvals
• UL® Listed to US and Canadian safety requirements
UL244A
Power
Operating Voltage
120–277 V~ 50/60 Hz
Output Ratings
• Switch rating of 8 A
• 0–10 V control link for 50 mA maximum output,
sink ONLY
0–10 V Control Link
• 0–10 V control link is Class 1
• Controls up to 25 ballasts or drivers (IEC 60929 Annex
E.2 requires the ballast / driver to limit the current draw
to 2.0 mA maximum)
Environment
• For Indoor Use Only.
• Ambient operating temperature: 32 °F to 104 °F
(0 °C to 40 °C), 0% to 90% humidity.
Application Requirements
• No derating required if ganged.
• Night light not available.
• Always consult local wiring codes.
Warranty
• 1 Year Limited Warranty. For additional Warranty
information, please visit
www.lutron.com/TechnicalDocumentLibrary/
369-119_Wallbox_Warranty.pdf
Performance
• Power Pack cannot be used with DVSTV- models.
• Works with all ballasts and drivers that provide a
current source compliant to IEC 60629 Annex E.2,
and whose inrush current does not exceed NEMA410
standards for electronic ballast/driver loads of 8 A
steady state current.
• Adjustable high-end and low-end trim for optimal
dimming performance.
• Power failure memory: should power be interrupted,
the control will return to its previously set level prior to
the interruption when power is restored.
• Captive linear slider.
• Precise color matching.
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
Job Number:
Page 2
Diva®
0–10 V Control
Wallbox Controls
369147b 3 09.08.14
Specifications (continued)
DVTV- Models
Power
Operating Voltage
24 V- 100 mA
Output Ratings
• Power Pack required for load switching. Power Pack is
rated for 16 A
• 30 mA maximum output, sink ONLY.
0–10 V Control Link
• 0–10 V control is Class 2
• Controls up to 15 ballasts or drivers (IEC 60929 Annex
E.2 requires the ballast / driver to limit the current draw
to 2.0 mA maximum)
Performance
Environment
• For Indoor Use Only.
• Ambient operating temperature: 32 °F to 104 °F
(0 °C to 40 °C), 0% to 90% humidity.
Application Requirements
• No derating required if ganged.
• Night light not available.
• Always consult local wiring codes.
Warranty
• 1 Year Limited Warranty. For additional Warranty
information, please visit
www.lutron.com/TechnicalDocumentLibrary/
369-119_Wallbox_Warranty.pdf
• For 120-277 V~ installations switching more
than 8 A, use DVTV- with Lutron® Power Pack
(model PP-DV; see Lutron® P/N 369544).
• For 347 V~ installations, use DVTV- with Lutron®
Power Pack (model PP-347H; see Lutron®
P/N 369544).
• Works with all ballasts and drivers that provide a
current source compliant to IEC 60629 Annex E.2.
• Adjustable high-end and low-end trim for optimal
dimming performance.
• Power failure memory: should power be interrupted,
the 0–10 V- signal will return to its previously set level
prior to the interruption when power is restored.
• Captive linear slider.
• Precise color matching.
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
Job Number:
Page 3
Diva®
0–10 V Control
Wallbox Controls
369147b 4 09.08.14
Dimensions
2.75 in
(70 mm)
4.69 in
(119 mm)
2.94 in
(75 mm)
0.30 in
(7.6 mm)
1.31 in
(33 mm)
Standard Colors and Finishes
Gloss Finishes
Satin Colors®
Add color suffix to model #
Example: DVSTV-WH / DVTV-WH
Add color suffix to model #
Example: DVSCSTV-SW / DVSCTV-SW
WH
IV
AL
LA
GR
BR
BL
HT
MR
PL
TQ
SG
TP
ES
BI
SW
PD
White
Ivory
Almond
Light Almond
Gray
Brown
Black
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
Job Number:
Hot
Merlot
Plum
Turquoise
Sea Glass
Taupe
Eggshell
Biscuit
Snow
Palladium
MN
TC
SI
GB
BG
MS
GS
DS
ST
LS
Midnight
Terracotta
Sienna
Green Briar
Bluestone
Mocha Stone
Goldstone
Desert Stone
Stone
Limestone
Page 4
Diva®
0–10 V Control
Wallbox Controls
369147b 5 09.08.14
High-End and Low-End Adjustments
DVSTV- Models
All Models
Front View
Bottom View
Maximum Light Level
(High-End) Trim
Minimum Light Level
(Low-End) Trim
DVTV- Models
Side View
Maximum Light Level
(High-End) Trim
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
Job Number:
Page 5
Diva®
0–10 V Control
Wallbox Controls
369147b 6 09.08.14
Wiring Diagrams
DVSTV- and DVSCSTVSingle Pole Wiring
Line/Hot
Switched
Hot
Red
Black
Red / White
Violet (+)
Gray (-)
Violet (+)
Gray (-)
0-10 V- Ballast/Driver
Neutral
120–277 V~
50/60 Hz
Ground
Switched
Hot
Violet (+)
Gray (-)
Neutral
0-10 V- Ballast/Driver
Neutral
3-Way Wiring
Line/Hot
**
* Red
Black
Switched
Hot
* Red / White
Violet (+)
Gray (-)
Violet (+)
Gray (-)
3-Way
Switch †
0-10 V- Ballast/Driver
Neutral
120–277 V~
50/60 Hz
***
Ground
Ground
Switched
Hot
Violet (+)
Gray (-)
Neutral
0-10 V- Ballast/Driver
Neutral
* Copper / Black screw terminal
** Brass / Gold screw terminal
*** Green screw terminal
†
Please refer to installation instructions for 3-Way switch for proper wiring.
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
Job Number:
Page 6
Diva®
0–10 V Control
Wallbox Controls
369147b 7 09.08.14
Wiring Diagrams
DVSTV- and DVSCSTV- (continued)
4-Way Wiring
Line/Hot
*
**
4-Way
Switch †
3-Way
Switch †
*
120–277 V~
50/60 Hz
** Red
*
** Red / White
*
***
***
Ground
Ground
Black
Switched
Hot
Violet (+)
Gray (-)
Violet (+)
Gray (-)
0-10 V- Ballast/Driver
Neutral
Ground
Switched
Hot
Violet (+)
Gray (-)
Neutral
0-10 V- Ballast/Driver
Neutral
Note: For 4-way wiring, control must be installed line side or load side. It cannot be installed in the 4-way location.
* Copper / Black screw terminal
** Brass / Gold screw terminal
*** Green screw terminal
†
Please refer to installation instructions for 3-Way /4-Way switch for proper wiring.
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
Job Number:
Page 7
Diva®
0–10 V Control
Wallbox Controls
369147b 8 09.08.14
Wiring Diagrams
DVTV- and DVSCTVDimming With ON/OFF Control
Wiring Diagram Using a Power Pack
Class 2 Only
Neutral
Violet (+)
0-10 V- Ballast/Driver
Gray (-)
Red / White
Switched
Hot
Neutral
Violet (+)
Violet (+)
Gray (-)
Gray (-)
0-10 V- Ballast/Driver
Switched
Hot
Red
Blue
Red
Red
PP-DV / PP-347H
Black
White
Black
Neutral
120–277 / 347 V~ 50 / 60 Hz
Line / Hot
Dimming With ON / OFF Control For Drivers Which Support Dim To OFF Capability
Power Wiring Not Shown—See Lighting Device For Wiring
Red/White
Violet (+)
Violet (+)
Gray (-)
Gray (-)
0-10 V- Ballast/Driver
Red
Blue
Violet (+)
0-10 V- Ballast/Driver
Gray (-)
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
Job Number:
Page 8
Maestro®
Occupancy/Vacancy Sensor with C•L Dimmer
Sensor
369748b 1 03.13.13
MaestroR Occupancy Sensor C•LR Dimmer
LutronR MaestroR occupancy sensor C•LR dimmers
A/E: Does this meet design intent?
are lighting controls with passive infrared sensors that
automatically control the lights in an area. These sensors
detect heat from occupants moving within an area to
determine when the space is occupied. The MaestroR
occupancy sensor C•LR dimmer combines a MaestroR
C•LR dimmer with an occupancy or vacancy sensor.
Features
•C
ontrols CFL, LED, incandescent, and halogen
load types *
•P
assive infrared motion detection with exclusive
LutronR XCTT Technology for fine motion detection
• 180˚ sensor field-of-view
•U
p to 30 ft x 30 ft (9 m x 9 m) [900 ft2 (81 m²)] major
motion coverage and 20 ft x 20 ft (6 m x 6 m)
[400 ft2 (36 m²)] minor motion coverage
• Occupancy version can be set to auto-on/auto-off or
manual-on/auto-off
• Vacancy version available to meet CA Title 24
requirements
• Adjustable timeout (1, 3, 5, 15, or 30 minutes) and
high/low sensitivity adjustment
djustable settings for auto-on light level (occupied
•A
level): 100%, 50%, last light level, or locked preset
light level
• Off warning fades lights to off over a period of
10 seconds
• Advanced MaestroR dimmer features available (locked
preset, fade-to-on, and fade-to-off, etc.)
• All models have single pole and multi-location capability
• Works with a single standard mechanical 3-way switch
or up to 9 companion dimmers/switches (MA-R or
MSC-AD) **
Models Available
Model Number ***
Description
Sensor Operation
Maximum Capacity
MSCL-OP153M-XX
Occupancy/vacancy single-pole/
multi-location
Auto-on/auto-off or
manual-on/auto-off
600 W incandescent/halogen
150 W CFL/LED *
MSCL-VP153M-XX
Vacancy single-pole/multi-location
Manual-on/auto-off
600 W incandescent/halogen
150 W CFL/LED *
* For a complete list of compatible DIMMABLE CFLs and LEDs please visit www.lutron.com/dimcflled
** If using with standard mechanical 3-way switch, some rewiring and dimmer programming is required
*** XX in model number represents color/finish code
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
1
Maestro®
Occupancy/Vacancy Sensor with C•L Dimmer
Sensor
369748b 2 03.13.13
Specifications
Regulatory Approvals
• UL Listed to U.S. and Canadian safety requirements
• Title 20/24 certified lighting control device
– Complies with Title 20 and Title 24 Section 119
(Until Jan 1st, 2014)
• Title 20/24 certified lighting control device
– Complies with Title 20 and Title 24 Section 110.9
(After Jan 1st, 2014)
Power
• Operating voltage: 120 V~ 60 Hz
Environment
• Ambient operating temperature: 32 °F to 104 °F
(0 °C to 40 °C), 0%-90% humidity, non-condensing;
indoor use only
Warranty
• 5 Year Limited Warranty
For additional Warranty information, please visit:
www.lutron.com/TechnicalDocumentLibrary/Sensor_
Warranty.pdf
Key Design Features
Dimmer
•On a single-tap, lights fade ON or OFF
•On a double-tap, lights go to full ON
•When ON, press and hold to engage a long fade
to OFF
•Light levels can be fine-tuned by pressing and
holding the dimming rocker until the desired light
level is reached
Custom Sensor Settings
•
•
•
•
•
•
Timeout Options
1 Minute
3 Minute
5 Minutes (default)
15 Minutes
30 Minutes
Test Mode
– Short (less than 15-second) timeout for testing
sensor coverage. After entering, device will exit
test mode automatically after 5 minutes, or
when any button is pressed.
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Sensitivity Options
• High sensitivity (default)
• Low sensitivity
Auto-ON Options
• Occupancy (default): Auto-ON / Auto-OFF
– Occupancy Mode is also called “Auto-On: Enabled”
• Vacancy *: Manual-ON / Auto-OFF
– Vacancy Mode is also called “Auto-On: Disabled”
*T
here is a 15-second grace period that begins when the lights are
automatically turned off, during which the lights will automatically turn
back on in response to motion. This grace period is provided as a safety
and convenience feature in the event that the lights turn off while the
room is still occupied, so that the user does not need to manually turn the
lights back on. After 15 seconds, the grace period expires and the lights
must be manually turned on.
• Ambient Light Detection (ALD): Lights turn on only if
natural light in room is low
– Smart—Ambient light threshold adjusts to the
user’s preference **
** If sensor turns on when there is enough natural light, or if sensor does
not turn on when there is not enough natural light, press the large button
within 5 seconds of entering the room. Over time, this interaction will
“teach” the sensor your preferred setting.
• Off While Occupied (OWO)
– When the sensor dimmer is manually turned off,
the sensor dimmer will not turn the lights back on
automatically while the room is occupied.
– Once the room is vacated, the Auto-ON feature
returns to normal operation after the timeout period
has expired.
– This may be the preference in conference rooms
or classrooms while viewing presentations. This
feature requires motion to keep the lights off.
Occupied Level Options
Occupied Level is the light level that the sensor
dimmer will turn ON to when motion is detected.
• 100% (default)
•50%
•Preset
– While in preset mode, lights will automatically turn
to the last level or to the “Locked Preset” level if a
“Locked Preset” has been selected in Advanced
Programming.
Page
2
Maestro®
Occupancy/Vacancy Sensor with C•L Dimmer
Sensor
369748b 3 03.13.13
Load Type and Capacity
Control
Voltage
MSCL-OP153M
MSCL-VP153M
1
2
3
120 V~
Load Type 1
Incandescent,
halogen,
CFL, LED 2
Minimum
Load
1 bulb, or
as noted
on
approved
bulb list 3
Maximum Load
Neutral
Connection
Required
Not Ganged End of
Gang
Middle of
Gang
600 W incan/
halogen
or
150 W CFL/
LED
400 W incan/
halogen
or
NO
150 W CFL/
LED
500 W incan/
halogen
or
150 W CFL/
LED
Dimmer Load Type: designed for use with permanently installed lighting fixtures only. Do not install dimmers to control receptacles or motor-operated appliances.
For mixed load types, see Mixed Load Type and Capacity section.
For a complete list of approved Dimmable CFLs and LEDs, please visit www.lutron.com/dimcflled. For questions call: 1.800.523.9466.
Mixed Load Type and Capacity
Determine allowable wattage (W) of
dimmer by following the steps below.
If multiple dimmers are to be installed
adjacently in the same wallbox, derating
is required.
1.
2.
3.
4.
Derating Chart
Determine total wattage of CFL/LED
bulbs installed for dimmer control.
D
etermine total wattage of Incandescent/
Halogen bulbs to be controlled by the
dimmer.
U
se the Derating Chart to determine
if your total wattages are within the
allowable range of your configuration.
Derating Procedure (if necessary)
If multiple dimmers are installed
adjacently in the same wallbox, heat fins
MUST be removed between adjacent
dimmers. This will permanently derate
the dimmer, reducing its total allowable
Incandescent/Halogen wattage.
Derating Chart
Placing dimmers adjacent
to mechanical switches
does not require derating.
A
CFL
CFL
LFCA
LFCA
AFC
AFC
LED
LED
DEL
DEL
B
B
C
B
Incandescent / Halogen : Total Wattage
INC / HAL
Total W CFL/LED
0W
1 W – 25 W
26 W – 50 W
51 W – 75 W
76 W – 100 W
101 W – 125 W
126 W – 150 W
B
+
A
10 W – 600 W
0 W – 500 W
0 W – 400 W
0 W – 300 W
0 W – 200 W
0 W – 100 W
0W
B
B
10 W – 500 W
0 W – 400 W
0 W – 300 W
0 W – 200 W
0 W – 100 W
0 W – 50 W
0W
C
C
10 W – 400 W
0 W – 300 W
0 W – 200 W
0 W – 100 W
0 W – 50 W
0W
0W
Heat Fins
Example
If heat fins from one side of dimmer are removed (see B in chart) and you have two
24 W CFL bulbs installed (Total CFL Wattage = 48 W), you may add up to 300 W of
Incandescent/Halogen lighting.
Additional Information
• For MaestroR Occupancy sensing switch models, please see LutronR P/N 369666 at www.lutron.com.
•Lutron Technical Hotline: 1.800.523.9466.
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
3
Maestro®
Occupancy/Vacancy Sensor with C•L Dimmer
Sensor
369748b 4 03.13.13
MaestroR Occupancy Sensor C•LR Dimmer Placement and Operation
•
The ability of the sensor dimmer to detect motion requires line-of-sight of room occupants. The sensor dimmer
must have an unobstructed view of the room.
Hot objects and moving air currents can affect the performance of the sensor dimmer. For best performance, the
•
sensor dimmer should be mounted at least 4 ft (1.2 m) away from HVAC vents and light bulbs.
•
The performance of the sensor dimmer depends on a temperature differential between the ambient room temperature
and that of room occupants. Warmer rooms may reduce the ability of the sensor dimmer to detect occupants.
NEMA WD7 Test Grid Coverage (High Sensitivity Setting)
Horizontal Beam Diagram
30 ft
(9 m)
Major motion coverage: 900 ft( (81 m()
25 ft
(7.5 m)
Minor motion coverage: 400 ft( (36 m()
20 ft
(6 m)
15 ft
(4.5 m)
15 ft
(4.5 m)
10 ft
(3 m)
10 ft
(3 m)
5 ft
(1.5 m)
0
5 ft
(1.5 m)
5 ft
(1.5 m)
10 ft
(3 m)
15 ft
(4.5 m)
0
20 ft
(6 m)
25 ft
(7.5 m)
5 ft
(1.5 m)
30 ft
(9 m)
10 ft
(3 m)
Vertical Beam Diagram
4 ft
(1.2 m)
15 ft
(4.5 m)
0
5 ft
(1.5 m)
10 ft
(3 m)
15 ft
(4.5 m)
20 ft
(6 m)
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
25 ft
(7.5 m)
30 ft
(9 m)
0
5 ft
10 ft 15 ft 20 ft 25 ft 30 ft 35 ft
(1.5 m) (3 m) (4.5 m) (6 m) (7.5 m) (9 m) (10.7 m)
Page
4
Maestro®
Occupancy/Vacancy Sensor with C•L Dimmer
Sensor
369748b 5 03.13.13
Operation
NOTE:
Status LEDs
Indicate light level; glow softly as night
light when light is off
* LED only pulses to acknowledge motion when there is
motion AND the load is ON.
Dimming Rocker
Press to brighten
Press to dim
Tapswitch
Tap on / off;
Double-tap - lights go to full on
Sensor Lens
Sensor
LED *
FASST
Front
Accessible
Service
Switch
Important notice:
FASST – Front Accessible Service Switch – to service load, remove power by pulling the FASST switch out completely
on either the sensor dimmer or companion dimmer. After servicing load, push the FASST switch back in fully to restore
power to the control. Once power has been restored, the sensing dimmer can be manually turned on or off but will not
automatically control the load for the first 2 minutes.
Mounting
Mounting
Screws
Adapter
Mounting
Screws
Wallplate
Wallbox
MaestroR
Occupancy
Sensor C•LR
Dimmer
Wallplate / Adapter purchased
separately.
Wallplate
Adapter
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
5
Maestro®
Occupancy/Vacancy Sensor with C•L Dimmer
Sensor
369748b 6 03.13.13
Dimensions
Measurements shown as: in (mm)
Side View
Front View
411⁄16
(119)
215⁄16
(75)
11⁄8
(30)
1/8
(3)
5/16
(8)
Note: MSCL-OP153M and MSCL-VP153M have screw terminals.
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
6
Maestro®
Occupancy/Vacancy Sensor with C•L Dimmer
Sensor
369748b 7 03.13.13
Wiring Diagrams
Wiring Diagram 1
Single Location Installation 1
MSCL-OP153M and MSCL-VP153M
Sensor Dimmer
Blue 1
Brass
Line/Hot
Black
Green
Wire
120 V~
60 Hz
Load
Ground
Neutral
Wiring Diagram 2
Multi-Location Installation 2, 3, 4
MSCL-OP153M and MSCL-VP153M with MA-R or MSC-AD
Sensor Dimmer
Brass
Blue
Companion Dimmer
Brass
Blue
Companion Dimmer
Brass
Blue
Line/Hot
Black
Black
Green
Wire
120 V~
60 Hz
Black
Green
Wire
Ground
Green
Wire
Ground
Load
Ground
Neutral
When using controls in single location installations, tighten the blue terminal. Do not connect the blue terminal to any other wiring or to ground.
Up to 9 companion dimmers may be connected to a sensor dimmer. Total blue terminal wire length may be up to 150 ft (46 m).
3
Only one sensor dimmer can be used per multi-location circuit.
4
Sensor dimmer can be installed in any location in the circuit.
1
2
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
7
Maestro®
Occupancy/Vacancy Sensor with C•L Dimmer
Sensor
369748b 8 03.13.13
Wiring Diagrams
(continued)
Wiring Diagram 3
3-way Installation with Standard Mechanical Switch (120 V~) 1, 2
MSCL-OP153M and MSCL-VP153M
Standard
mechanical switch 3
Sensor Dimmer
Brass
Line/Hot
Jumper wire
Blue
Different
color screw
(Common)
Green screw
120 V~
60 Hz
Black
Green
Wire
Ground
Load
Ground
Neutral
OR
Sensor Dimmer
Brass
Line/Hot
Standard
mechanical switch 3
Black
Blue
Green screw
Green
Wire
120 V~
60 Hz
Ground
Different
color screw
(Common)
Ground
Jumper wire
Load
Neutral
1
2
3
Only one sensor dimmer can be used per multi-location circuit.
single standard mechanical 3-way switch or up to 9 companion dimmers may be connected to a sensor dimmer. Standard mechanical 3-way switch
A
cannot be combined with companion dimmer. Total blue terminal wire length may be up to 150 ft (46 m).
Diagram 3 shows a typical retrofit scenario, where one mechanical 3-way switch is being replaced with a sensor dimmer. The remaining mechanical 3-way
switch needs to be modified to effectively convert it to a single pole switch. For new construction, a standard mechanical single pole switch can be used here.
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
8
Maestro®
Occupancy/Vacancy Sensor with C•L Dimmer
Sensor
369748b 9 03.13.13
Colors and Finishes
A/E: Please confirm color.
Gloss Finishes
Satin Finishes
White
WH
Ivory
IV
Hot
HT
Merlot
MR
Plum
PL
Turquoise
TQ
Almond
AL
Light
Almond
LA
Taupe
TP
Eggshell
ES
Biscuit
BI
Snow
SW
Gray
GR
Brown
BR
Palladium
PD
Midnight
MN
Sienna
SI
Terracotta
TC
Greenbriar
GB
Bluestone
BG
Mocha
Stone
MS
Goldstone
GS
Desert Stone
DS
Stone
ST
Limestone
LS
Sea Glass
SG
Black
BL
Due to printing limitations, colors and finishes shown cannot be guaranteed to perfectly match actual
product colors.
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
9
Radio Powr SavrTM
LRFX-DCRB
Wireless Daylight Sensor
369262i 1 03.24.16
Radio Powr SavrT Wireless
Daylight Sensor
A/E: Please confirm color.
The LutronR wireless daylight sensor is a
battery-powered sensor that automatically controls
lights via RF communication to compatible dimming or
switching devices. This sensor mounts to the ceiling
and measures light in the space. The sensor then
transmits the light level to the associated dimming or
switching devices that automatically control the lights
to balance light level in the space. The sensor
combines both convenience and exceptional energy
savings potential along with ease of installation.
Features
•Wireless daylight sensor has simple calibration.
•Daylight compensation through LutronR reliable open
loop control.
•Designed to give a linear response to changes in
viewed light level.
•Light range 0 to 1600 lx (0 to 150 fc).
•Uses Clear ConnectR technology.
•Works with Radio Powr SavrTM occupancy / vacancy
sensors and Pico® wireless controls.
•Intuitive test mode provides instant system verification.
•Multiple ceiling-mount methods available for different
ceiling materials.
•Front accessible test buttons make setup easy.
•10-year battery life.
•RoHS compliant.
Model Number
LRFX-DCRB-WH
Color Code
Frequency / Channel Code
Frequency / Channel Codes
2 = 431.0 – 437.0 MHz (U.S.A., Canada, Mexico, Brazil)
3 = 868.125 – 869.850 MHz (Europe, U.A.E.)
4 = 868.125 – 868.475 MHz (China, Singapore)
5 = 865.5 – 866.5 MHz (India)
6 = 312.3 – 314.8 MHz (Japan)
7 = 433.05 – 434.79 MHz (Hong Kong, Macau)
Color Code
WH = White
Compatible RF Devices
•For use with Lutron® products only.
•Communicates to various wireless Lutron® systems*.
*Contact LutronR Customer Service at
www.lutron.com for frequency/channel code
compatibility with your particular geographic region,
and for integrating with other LutronR lighting and
shading products.
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
1
Radio Powr SavrTM
LRFX-DCRB
Wireless Daylight Sensor
369262i 2 03.24.16
Specifications
Regulatory
Lutron® Quality Systems Registered to ISO 9001:2008
Standards
LRF2•FCC certified
•IC certified
•COFETEL
•ANATEL
•ASEP
•CRC
•SUBTEL
•SUPERTEL
•SUTEL
•Meets CA (U.S.A.) Energy Commission Title 24
requirements
•cULus Listed
LRF3•CE Marked (European Union)
•TRA Type Approved (United Arab Emirates)
•CITC (Kingdom of Saudi Arabia)
LRF4•SRRC Type Approved (Mainland China)
•iDA Registered (Singapore)
LRF5•WPC Type Approved (India)
Power / Performance
•Operating voltage: 3 V•Operating current: 7 µA
•Requires one CR 2450 lithium battery
•10-year battery life
•Non-volatile memory (settings are stored during
power loss)
Enviroment
•Temperature: 32 ºF to 104 ºF (0 ºC to 40 ºC)
•For indoor use only
•Relative humidity: < 90% non-condensing
Range
•LRF2-, LRF3-, LRF4-, LRF5-, LRF7Local load controls must be located within 60 ft (18 m)
line of sight, or 30 ft (9 m) through walls, of a sensor.
•LRF6Local load controls must be located within 23 ft (7 m)
through walls of a sensor.
Dimensions
0.7 in
(17 mm)
LRF6•
007YUUL0688
LRF7•FCC certified
1.6 in
(41 mm)
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
2
Radio Powr SavrTM
LRFX-DCRB
Wireless Daylight Sensor
369262i 3 03.24.16
Mounting
Installation Overview
Location for average size areas
Determine the Daylight Sensor mounting
location using the diagrams at left:
Arrow points towards the area viewed by the sensor
(towards windows).
Bottom of sensor
1-2 H
H
3 ft (1 m)
H = Effective Window Height
Location for narrow areas
(corridors, private offices)
Arrow points towards the area viewed by the sensor
(away from window)
Bottom of sensor
S P E C I F I C AT I O N S U B M I T TA L
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
•The arrow on the daylight sensor points toward the
area viewed by the sensor.
•Place the daylight sensor so the arrow is pointed at
the nearest window at a distance from the window of
one to two times the effective window height (H).
•The effective window height (H) starts at the window
sill or 3 ft (1 m) up from the floor, whichever is higher,
and ends at the top of the window.
•Ensure that the view of the daylight sensor is not
obstructed (e.g. ceiling fans or pendant fixtures).
•Do not position the daylight sensor above an electric
light that shines up at the ceiling or at the sensor.
•Do not position the daylight sensor in the well of a
skylight or above indirect lighting fixtures.
•For narrow areas where the daylight sensor cannot
be placed 1-2 (H) from windows, place sensor near
windows facing into the space.
• Mount sensor(s) away from large metal surfaces
(e.g. light fixtures or metal-backed ceiling tiles). Metal
objects will affect the RF performance of the sensor.
• For detailed and application specific mounting
information, please see "Daylight Sensor Design and
Application Guide" (P/N 3683587) at
www.lutron.com/TechnicalDocumentLibrary/3683587_
Daylight_Sensor_Design_and_App_Guide_sg.pdf
Page
3
Radio Powr SavrTM
Ceiling
Wireless Occupancy/Vacancy Sensor
369480h 1 02.16.16
Radio Powr SavrTM Wireless
Occupancy / Vacancy Ceiling Sensor
A/E: Please confirm color.
Lutron® Radio Powr SavrTM occupancy/vacancy sensors
are wireless, battery-powered, passive infrared (PIR)
sensors that automatically control lights via RF
communication to compatible dimming and switching
devices. These sensors detect the heat (IR radiation of
9.5 μm) from people moving within an area to determine
when the space is occupied. The sensors then wirelessly
transmit the appropriate commands to the associated
dimming and switching devices to turn the lights on or off
automatically. They combine both convenience and
exceptional energy savings potential along with ease of
installation.
Features
• Wireless occupancy sensor has 3 settings available:
Auto‑On/Auto-Off, Auto-On Low-Light/Auto-Off, and
Manual-On/Auto-Off
• Auto-On Low-Light feature will turn lights on automatically
only if there is less than approximately 10 Lux (1 fc) of
ambient light
• Vacancy-only model available to meet California (U.S.A.)
Title 24 requirements
• Uses Clear Connect® technology
• Passive infrared motion detection with exclusive Lutron®
XCTTM Technology for fine motion detection
• 360˚ coverage ranges from 324 ft2 (30.2 m2) to 676 ft2
(62.4 m2), depending on mounting height
• Simple and intuitive adjustments available for Timeout,
Auto-On, and Activity settings
• Supports advanced occupancy features, such as
dependent occupancy groups and customizable
occupied/unoccupied presets in some systems
• Multiple sensors can be added for extended coverage.
Refer to product specification submittal of receiving device
to determine system limits
• Lens illuminates during test mode to verify ideal locations
• Multiple ceiling-mount methods available for different
ceiling materials
• Front accessible test buttons make programming easy
• 10-year battery life design
• RoHS compliant
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Models Available
• LRF -OCR2B-P-WH
• LRF2-VCR2B-P-WH
Color Code
Occupancy and Vacancy
Frequency/Channel Code
Vacancy Only
Available for Channel Code 2 Only
Frequency/Channel Codes
Available
2 = 431.0 – 437.0 MHz (U.S.A., Canada, Mexico, Brazil)
3 = 868.125 – 869.850 MHz (Europe, U.A.E.)
4 = 868.125 – 868.4755 MHz (China, Singapore)
5 = 865.5 – 866.5 MHz (India)
6 = 312.3 – 314.8 MHz (Japan)
7 = 433.05 – 434.79 MHz (Hong Kong, Macau)
Color Code
WH = White
Compatible RF Devices
• For use with Lutron® products only
• Communicates to various wireless Lutron® systems*
* Contact Lutron® Customer Service at www.lutron.com for frequency/
channel code compatibility with your particular geographic region, and for
integrating with other Lutron® lighting and shading products.
Page
1
Radio Powr SavrTM
Ceiling
Wireless Occupancy/Vacancy Sensor
369480h 2 02.16.16
Specifications
Range
Regulatory
• Lutron® Quality Systems Registered to ISO 9001:2008
LRF2-, LRF3-, LRF4-, LRF5-, LRF7Local load controls must be located within 60 ft (18 m)
line-of-sight, or 30 ft (9 m) through walls, of a sensor.
Standards Approved
LRF2- (USA and Canada)
cULus Listed
FCC certified
IC certified
Meets CA (U.S.A.) Energy Commission Title 24
requirements
• COFETEL
• ANATEL
• SUTEL
LRF6Local load controls must be located within 40 ft (12.2 m)
line-of-sight, or 23 ft (7 m) through walls, of a sensor.
•
•
•
•
LRF3• CE marked (European Union)
• TRA type approval (United Arab Emirates)
• CITC type approval (Saudi Arabia)
LRF4• SRRC type approval (Mainland China)
• iDA registered (Singapore)
LRF5• WPC Type (India)
LRF6007YUUL0689
•
LRF7• FCC
Power/Performance
•
•
•
•
•
Operating voltage: 3 VOperating current: 14 μA nominal
Requires one CR 123 lithium battery
10-year battery life
Non-volatile memory (saved changes are stored during
power loss)
Environment
• Temperature: 32 ˚F to 104 ˚F (0 ˚C to 40 ˚C)
• For indoor use only
Warranty
• 5
-Year Limited Warranty. For additional Warranty
information, please visit www.lutron.com/
TechnicalDocumentLibrary/Sensor_Warranty.pdf
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Sensor Coverage Test
• Front accessible test button
• Lens illuminates orange in response to motion during test
mode and is visible from 60 ft (18 m)
Wireless Communication Test
• Front accessible test button
• Turn associated loads on and off
Timeout Options
•
•
•
•
1 minute*
5 minutes
15 minutes (default setting)
30 minutes
Auto-On Options (Occupancy Versions Only)
• Enabled: Sensor turns lights ON and OFF automatically
(default setting).
• Low Light: Sensor turns lights ON automatically only
in low ambient light conditions; sensor turns lights OFF
automatically.
• Disabled**: Lights must be turned ON manually from
dimming or switching device; sensor turns lights OFF
automatically.
Activity Options
• Low Activity: (default setting)
• Medium Activity:
• High Activity:
* Intended for use in high-activity, briefly occupied areas only.
** During the 15-second grace period that begins when the lights are
automatically turned off, the lights will automatically turn back on in
response to motion. This grace period is provided as a safety and
convenience feature in the event the lights turn off while the room is still
occupied, so that the user does not need to manually turn the lights back
on. After 15 seconds, the grace period expires and the lights must be
manually turned on.
Page
2
Radio Powr SavrTM
Ceiling
Wireless Occupancy/Vacancy Sensor
369480h 3 02.16.16
Installation Overview
Mounting
Sensor Setup
Temporary mounting is optional to test sensor coverage
and wireless communication before permanently installing
the sensor.
• Sensor setup is available as a service by Lutron. For more
information see the Sensor Layout and Tuning service
document (Lutron® P/N 3601235).
Sensor Placement
• To detect motion, the sensor requires line-of-sight of
room occupants. The sensor must have an unobstructed
view of the room. DO NOT mount behind or near tall
cabinets, shelves, hanging fixtures, ceiling fans, etc. The
sensor cannot see through glass objects such as patio- or
shower doors.
• Hot objects and moving air currents can affect the
performance of the sensor. To ensure proper operation,
the sensor should be mounted at least 4 ft (1.2 m) away
from HVAC vents and light bulbs that are below the ceiling
line.
• The performance of the sensor depends on a temperature
differential between the ambient room temperature and
that of room occupants. Warmer rooms may reduce the
ability of the sensor to detect occupants.
• Devices emitting Radio Frequency (RF) energy can affect
the performance of sensors. To ensure proper operation,
sensors should be mounted at least 4 ft (1.2 m) away from
devices that emit radio waves (e.g., microwave ovens,
wireless routers or other wireless devices).
• For additional information on placing sensors, please see
the Occupancy/Vacancy Sensor Design and Application
Guide (P/N 368-3197) located at www.lutron.com.
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Drop Ceiling (Compressed Fiber Ceiling Tile)
The mounting wire is provided for both temporary and
permanent mounting of the sensor to ceiling tiles. It is
designed to allow temporary mounting, testing, and
repositioning (if necessary) of the sensor without
damaging a ceiling tile. Once the final position of the
sensor has been chosen, the mounting wire should be
twisted together to permanently secure the sensor in
place.
Solid Ceiling (Drywall, Plaster, Concrete, or
Wood)
• Temporary mounting: Ten (10) temporary mounting strips
can be purchased in the kit, L-CMDPIRKIT, for temporarily
mounting and testing the sensor.
• Permanent mounting: Screws and anchors (for drywall or
plaster) provided to mount the sensor.
Recess-Mount
• Do not recess-mount sensor in a metal surface.
• Recess-mounting ring requires an opening of 3 in (76 mm)
in diameter.
• Recess-mounting ring secures internally to ceiling. Sensor
twists into the recess mounting ring and sits flush with
ceiling (see image below).
• Recess-mounting ring purchased as a separate kit:
L-CRMK-WH.
Page
3
Radio Powr SavrTM
Ceiling
Wireless Occupancy/Vacancy Sensor
369480h 4 02.16.16
Dimensions
3.57 in
(90.7 mm)
2.85 in
(72.4 mm)
0.88 in
(22.5 mm)
1.13 in
(28.7 mm)
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
4
Radio Powr SavrTM
Ceiling
Wireless Occupancy/Vacancy Sensor
369480h 5 02.16.16
Range Diagrams
Ceiling
8 ft
(2.4 m)
Floor
15 ft
12 ft
9 ft
6 ft
3 ft
(4.6 m) (3.7 m) (2.7 m) (1.8 m) (0.9 m)
0
3 ft
6 ft
9 ft
12 ft
15 ft
(0.9 m) (1.8 m) (2.7 m) (3.7 m) (4.6 m)
18 ft × 18 ft (5.5 m × 5.5 m) maximum
square coverage area whenmounted
on an 8 ft (2.4 m) ceiling
Sensor
13 ft (4.0 m) radius of coverage
at floor when mounted on an
8 ft (2.4 m) ceiling
Occupant
Sensor Coverage Chart (for sensor mounted in center of room)
Ceiling Height
8 ft (2.4 m)
9 ft (2.7 m)
10 ft (3.0 m)
12 ft (3.7 m)
Maximum Square Coverage Area*
18 ft × 18 ft (5.5 m × 5.5 m) 324 ft2 (30.2 m2)
20 ft × 20 ft (6.1 m × 6.1 m) 400 ft2 (37.2 m2)
22 ft × 22 ft (6.7 m × 6.7 m) 484 ft2 (44.9 m2)
26 ft × 26 ft (7.9 m × 7.9 m) 676 ft2 (62.4 m2)
* 12 ft (3.7 m) is the recommended maximum mounting height
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
5
Radio Powr SavrTM
Ceiling
Wireless Occupancy/Vacancy Sensor
369480h 6 02.16.16
Lens Masking
Whenever possible, the sensor should be installed in a
location where it cannot view areas outside the intended
space, such as hallways or adjacent rooms. If this
situation cannot be avoided, portions of the lens may be
masked to block the view of the sensor into undesired
areas. Ten (10) PIR Lens Masks may be purchased in the
kit, L-CMDPIRKIT.
Lens sections
shown in gray
are not masked
Lens sections
shown in white are
masked with labels
PIR Lens Mask
sold separately
(L-CMDPIRKIT)
Hallway falls within
Sensor’s coverage area.
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
6
PowPak™ Relay Module with SoftSwitch®
Energi TriPak™ Series
Wireless Lighting Control
369-428d 1 10.11.11
PowPak™ Relay Module with SoftSwitch®
The PowPak™ Relay Module with SoftSwitch® is a radio frequency (RF)
device that uses Lutron patented SoftSwitch® technology to control up
to 16 A of general-purpose load based on input from Pico® controls
and Radio Powr Savr™ occupancy and daylight sensors. An optional,
low-voltage dry contact closure output is available to communicate
occupancy status to 3rd-party systems such as HVAC controllers.
Communication with RF input devices, such as Pico® controls and
Radio Powr Savr™ sensors, is accomplished using Lutron Clear
Connect™ RF Technology.
Features
•SoftSwitch®: Lutron patented technology prevents arcing of relay
contacts, extending product lifetime
•Various operating voltages available—refer to model number chart
below for details on voltage requirements
•Capable of switching 16 A of general-purpose loads
•Optional low-voltage dry contact closure output provides integration
to building management systems, HVAC, VAV, etc.
•Receives wireless inputs from up to nine Pico® controls, six Radio
Powr Savr™ occupancy/vacancy sensors, and one Radio Powr Savr™
daylight sensor
•Utilizes Lutron Clear Connect™ RF Technology – refer to model
number chart below for frequency band data
•Mounts to a junction box through a standard half-inch (NPT trade size)
knockout
•Complies with requirements for use in a compartment
handling environmental air (plenum) per NEC® 2011 300.22(C)(3)
Description
Model Number
PowPak™ Relay Module
with SoftSwitch®
PowPak™ Relay Module
with SoftSwitch® and
Occupancy-Status CCO
Frequency Band
Region
RMJ-16R-DV-B
Operating
Voltage
120 / 277 V~
431.0 – 437.0 MHz
RMQ-16R-DV-B
RMJ-16RCCO1-DV-B
220-240 V~
120 / 277 V~
433.05 – 434.79 MHz
431.0 – 437.0 MHz
RMQ-16RCCO1-DV-B 220-240 V~
433.05 – 434.79 MHz
U.S.A., Canada,
Mexico
Hong Kong
U.S.A., Canada,
Mexico
Hong Kong
Note: Contact Lutron for frequency band compatibility for your geographic region if it is not indicated above.
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
1
PowPak™ Relay Module with SoftSwitch®
Energi TriPak™ Series
Wireless Lighting Control
369-428d 2 10.11.11
Specifications
Regulatory Approvals
RMJ- models only
•UL Listed
•UL 2043 Plenum Rated
•FCC approved. Complies with the limits for a Class B
device, pursuant to Part 15 of the FCC rules.
•CSA and IC
•COFETEL
•NOM (expected Q1 2012)
Power
•Operating voltage:
RMJ- models 120/277 V~ 50 / 60 Hz
RMQ- models 220-240 V~ 50 / 60 Hz
System Communication
•Operates using Clear Connect™ RF Technology
for reliable wireless communication; refer to model
number chart on page 1 for band frequency details
•RF range is 30 ft (10 m)
Environment
•Ambient operating temperature: 32 °F to 131 °F
(0 °C to 55 °C)
•0% to 90% humidity, non-condensing
•For indoor use only
SoftSwitch®
•Patented SoftSwitch® circuit eliminates relay arcing at
mechanical contacts
•Extends relay life to an average of 1 million cycles
•Output is non-latching
Load
•Maximum load: 16 A general purpose. No minimum
load requirements.
•Load types include (but are not limited to):
Incandescent, MLV, ELV, Resistive, Inductive,
Magnetic fluorescent, Electronic fluorescent
•Motor rating:
RMJ- models 0.5 HP (120 V~), 1.5 HP (277 V~)
RMQ- models 1.5 HP (220-240 V~)
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Key Design Features
•LED status indicator shows current load status and
provides programming feedback
•Power failure memory: If power is interrupted,
connected loads will return to the previous level prior
to interruption
•Daylighting can be overridden by pressing the ON
button on any associated Pico®
– Daylighting will be re-enabled after 2 hours or after
the area becomes unoccupied
Contact Closure Output (CCO version only)
•Provides occupancy status to 3rd-party equipment
such as building management systems, HVAC, and
VAV controllers
•Provides both normally open (NO) and normally
closed (NC) dry contacts
•Maintained output type
•CCO terminals accept 20 to 16 AWG (0.5 to 1.5 mm2)
solid or stranded wire
•Output is latching
•Not for voltages greater than 24 V
Switching
Voltage
0-24 V0-24 V~
Resistive
Load
1.0 A
0.5 A
R
•The CCO is not rated to control unclamped,
inductive loads. Inductive loads include, but are not
Switching
Resistive
Flyback
limited
to, relays,
solenoids, and motors. To control
Voltage
Load
Diode
Inductivea flyback diode must be
these
types
of
equipment,
(required
for
0-24 V1.0 A Load
inductive
used
(DC voltages only). See diagram below. For
0-24 V~
0.5 A
moreloads)
information, please see+ Application Note # 434
NO
(p/n 048434).
NC
R
CCO
Output
Flyback
Diode
(required for
inductive
loads)
NO
CCO
Output
COM
24 Vmax.
Inductive
Load
NC
COM
+
24 Vmax.
Page
2
PowPak™ Relay Module with SoftSwitch®
Energi TriPak™ Series
Wireless Lighting Control
369-428d 3 10.11.11
System Diagram
To power source
and load
Pico® Control (up to 9)
Test
Radio Powr Savr™ Occupancy Sensor (up to 6)
To 3rd-Party
Equipment
Radio Powr Savr™ Daylight Sensor (up to 1)
Wiring Diagram
Junction Box
HOT
White
NEUTRAL
SWITCHED HOT
Black
LOAD
Red
Occupancy-Status CCO
(RM__-16RCCO1-DV-B only)
NC
NO
COM
To 3rd-Party
Equipment
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
3
PowPak™ Relay Module with SoftSwitch®
Energi TriPak™ Series
Wireless Lighting Control
369-428d 4 10.11.11
Wiring Diagram
Input Voltage
White
(Neutral)
To Load
Red
Black
(Switched Hot)
(Hot)
Conduit Nut
COM
To 3rd Party Equipment
(Common)
NO
NC
(Normally Open)
(Normally Closed)
Note: When wiring CCO to 3rd-party systems,
use 20 to 16 AWG (0.5 to 1.5 mm2) solid or
stranded wire.
CCO operation affected only by associated occupancy or vacancy sensors.
Room Occupied: NO = Close NC = Open
Room Unoccupied: NO = Open NC = Close
BOX A
In some applications, a PowPak™ module can be installed inside a 4 in x 4 in (102 mm x 102 mm) junction box. For
information about how to perform this installation, please see Application Note #423 (p/n 048423).
BOX B
Antenna
PowPak™ Installation Inside Junction Box
(Dimming Module RMJ-ECO32-DV-B shown)
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
4
PowPak™ Relay Module with SoftSwitch®
Energi TriPak™ Series
Wireless Lighting Control
369-428d 5 10.11.11
Dimensions
Dimensions are shown as: in (mm)
Half-inch
NPT Trade Size
3.94
(100.1)
3.42
(86.9)
2.82
(71.6)
1.25
(31.8)
Range Diagram
PowPak™
Relay Module
Radio
Powr Savr™
Occupancy
Sensor
30 ft (10 m)
Maximum
Pico®
Wireless
Transmitter
30 ft (10 m)
Install in center of room to
maximize RF coverage.
40 ft (12 m)
All Wireless Transmitters must be installed within
30 ft (10 m) of the PowPakTM Relay Module.
•Contact Lutron first for applications using foil-backed or metallic ceiling tiles.
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
5
PowPak™ Relay Module with SoftSwitch®
Energi TriPak™ Series
Wireless Lighting Control
369-428d 6 10.11.11
Default Operation
Transmitting Device
Pico®
Radio Powr Savr™
Occupancy Sensor
Radio Powr Savr™
Vacancy Sensor
Radio Powr Savr™
Daylight Sensor
Transmitted Command
On
Off
Raise
Lower
Preset
Occupied
Unoccupied
Occupied
Unoccupied
Ambient Light Below
Target Level
Ambient Light Above
Target Level
SoftSwitch® Relay Default Action
Close
Open
No Action
No Action
Close
Close
Open
No Action
Open
Close
CCO Default Action
No Action
No Action
No Action
No Action
No Action
NO = Close, NC = Open
NO = Open, NC = Close
NO = Close, NC = Open
NO = Open, NC = Close
No Action
Open
No Action
S p e c i f i c at i o n S u b m i t ta l
Job Name:
Model Numbers:
Gateway Mortgage
®
Job Number:
Page
6
Download