Dornier 328Jet - Fire Protection Fire Protection Panel (Cockpit Panel) (Sheet 1 of 2) Page 1 Dornier 328Jet - Fire Protection Fire Protection Panel (Cockpit Panel) (Sheet 2 of 2) Page 2 Dornier 328Jet - Fire Protection CARG FIRE (red) – Illuminates during fire test loop and when actual cargo compartment fire occurs. Red Warning Panel Page 3 Dornier 328Jet - Fire Protection Engine Fire Extinguishing Sequence Page 4 Dornier 328Jet - Fire Protection APU Fire Extinguishing Sequence Page 5 Dornier 328Jet - Fire Protection APU Fire Protection Panel (Ground Control Panel) Page 6 Dornier 328Jet - Fire Protection MESSAGE (SYNOPTIC) Location (COLOR) SMOKE CARGO FAIL CAS Field INHIBIT 1 2 3 Cargo smoke detector failed. Smoke in lavatory. (AMBER) SMOKE LAV FAIL CAS Field CONDITION (AMBER) SMOKE LAV CAS Field WARN TONE Lavatory smoke detector failed. (AMBER) Message inhibit logic: 1. WOW, Engines off and Electrical Bus Failure refer to Section 12–27–03 2. Takeoff phase 3. Landing phase CAS Field and System Messages Page 7 Dornier 328Jet - Fire Protection FIRE PROTECTION AND OVERHEAT DETECTION GENERAL Fire protection, consisting of fire detection, warning and extinguishing, is provided by three independent systems: one for the LH/RH engines each and one for the auxiliary power unit (APU). Each system includes electrical fire detection and extinguishing circuits, cooperating with warning, arming and discharge button lights. Two fire extinguishing agent (Firex) bottles are installed for each engine in the rear compartment of the pylon, aft of the fire wall and outside the engine firezone. One bottle is installed for the APU in front of the forward fire wall of the APU compartment outside the fire zone. An illuminated discharge (DIS) light indicates low pressure in the Firex bottles. Test switches test the electrical continuity of the detection and discharge cartridge circuits. Each system is capable of detecting electrical short circuits in the sensing cable circuits. A loop (LOOP) fail light on the engine FIRE PROTECTION control panel (overhead panel) illuminates to indicate a fire detection failure. Titanium fire walls on the engine pylon and in the APU compartment serve to isolate the engine and APU fire zones from the adjacent airfoil structure. The fuel and engine bleed air lines can all be isolated from the engine fire zones by shutoff valves located behind the fire wall and from the APU fire zones on the inboard side of the fire wall. Fire and overheat detection for the engines are provided by detection elements in each engine compartment. The position of the detection elements are: – the inner side of the left and right engine cowl doors – the engine turbine section Fire and overheat detection for the APU is provided by detection elements in the APU compartment. The position of the detection elements are: – the area around the compartment structure – on the underside of the upper fire wall and on the forward fire wall. FIREWIRE SENSOR CABLE Heat sensitive cables are routed through the fire and overheat detection zones and are connected to fire/overheat detection units. Each firewire sensor cable is a co–axial electrical cable consisting of two conductors, a stainless steel outer conductor grounded to the airframe and an inner conductor connected in a closed loop to a control unit. The two conductors are separated by a semi–conductor material which decreases in electrical resistance as temperature increases. When the resistance of the semi–conductor decreases to a preset limit, a warning is generated to the flight compartment. A single break in a cable does not impair its warning capabilities but if a cable is broken in more than one place, any section between the breaks will not function and the failure would be indicated by a loop fail light when the test switch is selected to loop test. Page 8 Dornier 328Jet - Fire Protection Engine and APU Firewire Sensor Cable – Installation Page 9 Dornier 328Jet - Fire Protection FIRE/OVERHEAT CONTROL UNITS Two engine fire/overheat control units and one APU fire/overheat control unit are installed below the cabin floor in the front part of the fuselage in a pressurized environment. The control units monitor the LH/RH engine and APU fire protection and overheat detection system. Each control unit contains two separate alarm circuits to discriminate between valid fire or overheat warnings and fault indication generated by sensing cable short circuits. The units compare the speed and extent of sensing cable resistance change and initiate fire warnings caused by fire or overheating. Page 10 Dornier 328Jet - Fire Protection FIRE PROTECTION SYSTEM COMPONENTS AND CONTROLS Three red fire warning buttons marked ENG LH FIRE PUSH, APU FIRE PUSH, and ENG RH FIRE PUSH, each guarded by a security cover, are located on the FIRE PROTECTION control panel on the overhead panel in the flight compartment. If a valid fire warning is received, the control unit causes the appropriate fire warning button(s) to illuminate and activates the fire warning alert. The illuminated fire warning button(s) and the aural fire warning alert continue to operate as long as a fire/overheat condition exists. The fire warning alert is silenced when one of the MASTER WARNING lights on the glareshield panel is pushed. If a fire control unit detects a short circuit signal, the appropriate amber LOOP FAIL light on the FIRE PROTECTION control panel comes on to indicate the failure. FIRE WARNING CIRCUIT TESTING Three TEST switches on the FIRE PROTECTION control panel are used to check the serviceability of the engine and APU fire detection warning and fault circuits. Engine Fire Warning Test Setting the appropriate engine TEST switch to the upper position (FIRE SQUIB) causes the following lights to illuminate: – the MASTER WARNING lights, – the appropriate red FIRE lights on the red warning panel (RWP), – the appropriate red ENG FIRE button warning light(s) (loop test): – fire detection loop is ok, no breaks detected (if the system has a short circuit, the appropriate LOOP FAIL light is already on, and the particular fire warning light remains off) – the appropriate green SQUIB lights (BTL1/BTL2) (cartridge test): – the cartridge of the particular extinguisher is ok and – the FIRE BELL in the flight compartment to sound. Setting the appropriate engine TEST switch to the lower position (FAIL AGN) causes the following lights to illuminate: – the appropriate green AGN lights (extinguisher test): – the required agent capacity of the particular extinguisher is available – the appropriate amber LOOP FAIL light: – the circuit of the control units in the fire loop is functional. Page 11 Dornier 328Jet - Fire Protection APU Fire Warning Test Setting the APU TEST switch to the upper position (FIRE SQUIB) causes the following lights to illuminate: – the MASTER WARNING lights, – the red APU FIRE light on the red warning panel (RWP), – the red APU FIRE button warning light on the FIRE PROTECTION control panel and APU ground panel (loop test): – fire detection loop is ok, no breaks detected (if the system has a short circuit, the LOOP FAIL light on the FIRE PROTECTION control panel is already on, and the APU fire warning light remains off) – the green SQUIB light (BTL) in the flight compartment and on the APU ground panel (cartridge test): – the cartridge of the extinguisher is ok and – the FIRE BELL in the flight compartment and – the APU FIRE HORN on APU ground panel to sound. NOTE: The APU fire shutoff relay is isolated from the fire warning circuits when the test is performed. This permits operation of the APU during the fire warning system test. Setting the APU TEST switch to the lower position (FAIL AGN) causes the following lights to illuminate: – the green AGN lights (extinguisher test): – the required agent capacity of the extinguisher is available – the amber LOOP FAIL light: – the circuit of the control unit in the fire loop is functional. FAULT CASE If a short circuit occurs in any one fire detection loop, the amber LOOP FAIL light illuminates automatically. A break in the loop will not be indicated, because the function of the system is not affected. An interruption or break can only be detected by selecting the TEST switch to the lower position. If there is low pressure in the extinguisher due to a leakage or no pressure due to a bottle discharge, the white DIS light will be illuminated automatically. Page 12 Dornier 328Jet - Fire Protection FIRE/OVERHEAT CASE If there is a fire or an overheat condition in anyone engine nacelle, there will be four separate indications in the flight compartment as follows: – – – – MASTER WARNING light illuminated ENGINE LH/RH FIRE warning light on RWP red LH/RH ENG buttons lights illuminated fire warning alert (FIRE BELL) sounds. If there is a fire or an overheat condition in the APU compartment, there will be four separate indications in the flight compartment as follows: – – – – MASTER WARNING light illuminated red APU FIRE warning light on RWP red APU FIRE button light illuminated fire warning alert (FIRE BELL) sounds. Additionally a dual indication will be on the APU ground panel as follows: – red APU FIRE button light illuminated – fire warning alert (FIRE HORN) sounds. Page 13 Dornier 328Jet - Fire Protection FIRE EXTINGUISHING The fire extinguishing systems for the two engines and the APU are controlled by buttons located on the FIRE PROTECTION control panel on the overhead panel in the flight compartment. Five Firex bottles are provided, two for each engine, and one Firex bottle for the APU. Firex bottle low pressure warning lights and test switches for the bottle discharge cartridges (squibs) are integrated into the FIRE PROTECTION control panel and the APU ground panel. ENGINE FIRE EXTINGUISHING SYSTEM OPERATION NOTE: The operation of the LH/RH engine fire extinguishing system are identical. When a fire or overheat condition occurs in the detection zones of an engine, the appropriate fire/overheat control unit causes the red ENG FIRE button light to illuminate and the fire warning alert (FIRE BELL) to sound. Pushing the ENG FIRE button light arms both squibs of the engine Firex bottles and causes the green BTL 1/BTL2 SQUIB button to illuminate. In addition, the following will occur: – – – – – the fuel shutoff valve will be closed the fuel motive flow valve will be closed the bleed air shutoff valve will be closed the AC generator will be switched off the auto–ignition will be switched off and – the DC generator will be switched off. Pushing the green BTL 1 SQUIB button allows pressurized Firex agent to flow through the outlet port and associated discharge lines into the fire zone of the left engine. As the Firex agent discharges, the green BTL 1 SQUIB light extinguishes and the white BTL 1 DIS light illuminates. If the fire condition persist after bottle 1 has been fully discharged, the green BTL 2 SQUIB button can be pushed to fire the squib on bottle 2. The Firex agent from bottle 2 is also released through the outlet port and associated discharge lines into the fire zone of the engine. As the pressure in bottle 2 decreases, the green BTL 2 SQUIB light extinguishes and the white BTL 2 DIS light illuminates. SYSTEM RESET After a fire warning occurs and the appropriate ENG FIRE button is pressed, the fire warning and extinguishing system can be reset, if circumstances warrant, by pushing the ENG FIRE button a second time which returns the system to the pre–warning condition except for the fuel shutoff valve, the DC generator and the ECS bleed valve. These functions can only be reactivated by moving the thrust lever to the CUT OFF position and respectively recycling the GEN ALT and BLEED buttons. WARNING: NEVER TRY TO RESTART AN ENGINE AFTER ACTUAL FIRE. Page 14 Dornier 328Jet - Fire Protection APU FIRE EXTINGUISHING SYSTEM OPERATION The operation of the APU fire extinguishing system is similar to the operation of the LH/RH engine fire extinguishing system described above with the following exceptions: NOTE: The APU Firex bottle discharges into the APU compartment. Pushing the APU FIRE button light arms the squib of the APU Firex bottle and causes the green BTL SQUIB button light to illuminate. In addition, the following will occur: – the shutdown of the APU through the APU fire shutoff relay will be initiated – the bleed air shutoff valve will be closed – the fuel shutoff valves on the APU normal feed and negative–g protection lines will be closed and – the APU DC generator will be switched off. SYSTEM RESET After a fire warning occurs and the APU FIRE button is pressed, the APU fire warning and extinguishing system can be reset, if circumstances warrant, by pushing the APU FIRE button a second time which returns the system to the pre–warning condition except for the fuel shutoff valve, the APU DC generator and the APU bleed air valve. These functions can only be reactivated by recycling the APU MASTER button on the APU control panel OFF and ON and by pressing the START button to restart the APU. WARNING: NEVER TRY TO RESTART AN APU AFTER ACTUAL FIRE. Page 15 Dornier 328Jet - Fire Protection Engine and APU Fire Extinguisher System Discharge Lines – Installation Page 16 Dornier 328Jet - Fire Protection SMOKE DETECTION AND FIRE EXTINGUISHING – LAVATORY GENERAL A smoke detection and an automatic fire extinguisher system is installed in the lavatory. In the event of smoke being detected in the lavatory an amber message will appear on the EICAS. If the ambient temperature in the lavatory exceeds a pre–determined limit the fire extinguisher system will operate independent of crew action and a warning illuminates on the red warning panel. SMOKE DETECTION SYSTEM An ionisation smoke detector with built–in test equipment (BITE) is fitted to roof of the lavatory. If smoke develops in the lavatory the detector senses the change in air density caused by the smoke and will send an amber SMOKE LAV message to the CAS field of the EICAS. If the detector or its associated circuitry fails a SMOKE LAV FAIL amber message on the CAS field on the EICAS comes on. EXTINGUISHING SYSTEM A fire extinguisher is fitted above the lavatory waste bin. The extinguisher comprises a pressure switch and a discharge arm and nozzle. Incoporated in the discharge nozzle is a heat sensitive capsule that in its passive mode prevents discharge. If the ambient temperature reaches 780C the heat sensitive capsule melts and extinguishing agent discharge automatically. The pressure switch senses the loss of pressure in the extinguisher that results in a LAV FIRE message on the red warning panel and a triple chime warning tone. Page 17 Dornier 328Jet - Fire Protection Lavatory Smoke Detector and Fire Extinguishing System Page 18 Dornier 328Jet - Fire Protection CARGO COMPARTMENT SMOKE DETECTION AND FIRE SUPPRESSION SYSTEM GENERAL An automatic smoke detection and manual activated fire extinguisher system for the cargo compartment is installed inside the pressurized fuselage shell. The Cargo Fire Protection System (CFPS) indicates fire (latest one minute after ignition) and remains on for the duration of fire/smoke, indicates when the fire is extinguished (warnings OFF) and indicates reignition of fire. The CFPS comprises following components: – – – – – – – – smoke detector (with heat detection device) fire suppression bottle for high rate discharge fire suppression bottle for metered discharge (metering device in the discharge head) two nozzles in the cargo compartment tubing / fittings check valve / T–check valve distribution box cargo fire control panel in the cockpit. Smoke Detector Distribution Box RWP Alarm Pulse Cargo Fire Control Panel Nozzles DAU EICAS Check Valve Speaker High Rate Discharge Bottle Meterde Discharge Bottle TCPS 1 Cartrige TCPS 2 T–Check Valve Cartrige Metering/ Drying Device Cargo Compartment Smoke Detection and Fire Extinguishing System Schematic Page 19 Dornier 328Jet - Fire Protection SMOKE DETECTION SYSTEM A photoelectric smoke detector with a built–in test equipment (BITE) is fitted to roof the of the cargo compartment measuring the presence of smoke particles in the air. The detector compensates for environmental influences and performs automatic re–adjustments of its smoke alarm threshold settings caused by pollution. An integrated temperature sensor compensates temperature influences and generates a fire alarm above the temperature threshold of 85OC (inside temperature). In case of smoke/fire or a fault detected by the BITE a signal is sent to the DAU and to the Cargo Fire Extinguisher Panel. The smoke detector is equipped with a test feature to be initiated through the Cargo Fire Control Panel. EXTINGUISHING SYSTEM Two Halon fire extinguisher bottles are fitted beneath the floor panels of the cargo compartment, one with a high pressure discharge and the other one metered. Each extinguisher comprises a combination fill valve/safety relief valve, a temperature compensated pressure switch and a discharge outlet assembly with a cartridge. The extinguishing agent is led through pipes to two nozzles installed in the ceiling panel. If the system is activated via crew initiated commands, the explosive cartridges (squibs) of both bottles are ignited forcing a rupture disc incorporated in each discharge outlet assembly to burst and thus allowing the agent to discharge through the distribution pipes into the cargo compartment. The high–rate bottle discharges in less than 2 seconds and rises the Halon concentration to 5% (volume) while the metered bottle discharges continuously to keep a Halon concentration above 3% for at least 1 hour. If an overpressurization condition in excess of the primary safety relief valve occurs, the rupture disc assembly serves the dual function of being a mechanism for discharging the agent and the system‘s secondary safety device. To monitor whether the fire suppression bottles are fully charged or not a temperature compensated pressure switch (TCPS) is mounted on the container. The TCPS closes a switch contact when a small amount of pressure loss occurred at any ambient temperature. Pressure differences due to a temperature increase/decrease are compensated. A loss of pressure is indicated on the cargo fire control panel. A check valve integrated in the tubing prevents water collection in the discharge line of the fire protection system. The valve opens in flow direction and closes water tight in unpressurized condition. Page 20 Dornier 328Jet - Fire Protection Component Installation / Location Page 21 Dornier 328Jet - Fire Protection OPERATION General For indication and operation of the fire protection system a cargo fire control panel is installed in the center pedestal of the cockpit. The control panel comprises a safety covered CARGO FIRE button, a DIS BOTTLE button, a secured TEST Switch and a DET FAIL indicator. A warning light CARG FIRE is activated on the RED WARNING panel and an audio warning signal is created by the audio warning system, to alert the crew of a possible fire in the cargo compartment. Fire/Smoke Condition If a fire/smoke condition in the cargo compartment is detected the flight crew will be alerted by following indications in the cockpit: – TRIPLE CHIME on and MASTER WARNING (red) flashing – CARG FIRE warning light (red) on RWP illuminated – CARGO FIRE button (red) on the cargo fire control panel flashing Pushing the CARGO FIRE button on the cargo fire control panel arms the system and the squib lights SQ1 and QS2 illuminate, indicating that the system is ready to discharge. To fire the bottle discharge cartridges (squibs) and allow the pressurized agent to dispense, the DIS BOTTLE button has to be pushed. As the detonators have fired and the pressure in the extinguisher bottles decrease, the green SQ1 and SQ2 lights extinguish and the white DIS (discharge) light comes on respectively. The red warnings remain on for duration of fire/smoke. NOTE: The CARGO FIRE button is secured with protective device to prevent inadvertent activation. Fault Indications If the smoke detector is inoperative or a wiring failure between the smoke detector and the distribution box exists following indications are given to the flight crew: – DET FAIL light (amber) on the cargo fire control panel illuminated – SMOKE CARGO FAIL caution message (amber) on the EICAS displayed – SINGLE CHIME on and MASTER CAUTION light (amber) flashing. If there is a wiring failure between the power supply busses and the distribution box or cargo fire control panel following indications are given: – SMOKE CARGO FAIL caution message (amber) on the EICAS displayed – SINGLE CHIME on and MASTER CAUTION light (amber) flashing. If there is a loss of pressure (no fire) following indication is given: – DIS BOTTLE button (white) on the cargo fire control panel illuminated. Page 22 Dornier 328Jet - Fire Protection Test Mode The condition of the smoke detector and the extinguisher bottles are tested (pre–flight–test) by using the TEST switch on the cargo fire control panel. In TEST FIRE SQUIB position a test sequence for the smoke detector is initiated. In TEST FAIL AGN position a bottle check is performed. NOTE: The test switch cargo fire is secured with protective device to prevent inadvertent switching. NOTE: The test switch cargo fire has to be kept in TEST position for at least 10 seconds to release the test sequence. Setting the TEST switch to TEST FIRE SQUIB position causes the following indications: – – – – – – – TRIPLE CHIME on and MASTER WARNING (red) flashing CARG FIRE warning light (red) on RWP illuminated CARGO FIRE button (red) on the cargo fire control panel flashing DET FAIL light (amber) on the cargo fire control panel illuminated SINGLE CHIME on and MASTER CAUTION (amber) SMOKE CARGO FAIL caution message (amber) on the EICAS displayed SQ1/SQ2 lights (green) on the cargo fire control panel illuminated. Setting the test switch to TEST FAIL AGN position causes the following indications: – AGN light (green) on fire control panel illuminated. If the agent capacity is too low, the white DIS light is already on, and the AGN light on the fire control panel remains off. Page 23