SECTION 9: PROTECTION AND CONTROL SECTION 9 PROTECTION AND CONTROL 9.1 SCOPE (1) This Section covers the protection and control of electrical circuits and apparatus installed in accordance with the requirements of this Code. 9.2 NORMATIVE REFERENCES (1) The following references contain provisions which, through reference in this text, constitute provisions of the Ethiopian Building Code Standard on Electrical Installation of Buildings. (a) CSA C22.1:2002 (b) BS 7671:2001 Canadian Electrical Code Part I, Safety Standard for Electrical Installation, Nineteenth Edition. Requirements for Electrical Installation, IEE Wiring Regulations, Sixteenth Edition. (c ) NFPA 70 / NEC: 2008 American National Fire Protection Association/ National Electrical Code, 2008 Edition 9.3 GENERAL REQUIREMENTS 9.3.1 Protective and Control Devices (1) Every electrical apparatus and unearthed conductors shall be protected by one or more devices as may be necessary for automatic and/or manual interruption of the supply in the event of any fault and shall be provided with: (a) protection against fault current to break any fault current in a circuit before such current causes danger due to thermal or mechanical effects produced in those conductors or the associated connection; (b) protection against overload current to break any such current flowing in the circuit conductors before such a current causes a temperature rise detrimental to insulation, joints, termination or the surroundings of the conductors; (c) protection against under-voltage which when necessary will open the circuit, where a reduction in voltage, or loss and subsequent restoration of voltage could cause danger; (d) manually-operable control device which will safely disconnect all unearthed conductors of the circuit at the point of supply simultaneously; and ETHIOPIAN BUILDING CODE STANDARDS EBCS 10: 2013 SECTION 9: PROTECTION AND CONTROL (e) protection against earth fault in accordance with Clause 9.4.2. 9.3.2 Types and Ratings of Protective and Control Devices (1) Circuit breakers, fuses, and switches shall be of type and ratings acceptable to the department in charge of inspection. (2) Overcurrent protective devices shall ensure safe operation and shall have interrupting capacity sufficient for the voltage employed and for the anticipated fault current which must be interrupted. 9.4 Protective Devices 9.4.1 Overcurrent Devices (1) Each unearthed conductor shall be protected by an overcurrent device at the point where it receives its supply of current and at each point where the size of conductor is decreased, except that such protection may be omitted where: (a) the overcurrent device in a larger conductor properly protects the smaller conductor; (b) the smaller conductor is not over 3.0m long and does not extend beyond the switchboard, panel board, control device which it supplies; or (c) the smaller conductor has an ampacity not less than one-third that of the larger conductor from which it is supplied. (2) The rating or setting of overcurrent devices shall not exceed the allowable ampacity of the conductors which they protect except: (a) where a fuse or circuit breaker having a rating or setting of the same value as the ampacity of the conductor is not available, the ratings or settings given in Table 9.1 may be used; (b) in case of equipment wire, flexible cord, and tinsel cord, which will be considered as being protected by 16.0A overcurrent devices; or (c) as provided for by other Clauses of this Code. (3) Overcurrent devices shall be enclosed in cutout boxes or cabinets unless they form a part of an approved assembly which affords equivalent protection, or unless mounted on switchboards, panel boards, or controllers located in room or enclosures free from easily ignitable material and dampness, and accessible only to authorized persons. (4) Overcurrent devices shall not be connected in parallel in circuits of 1000.0V or less unless otherwise they are factory-assembled in parallel as a single unit. ETHIOPIAN BUILDING CODE STANDARDS EBCS 10: 2013 SECTION 9: PROTECTION AND CONTROL 9.4.2 Earth-Fault Protection (1) Earth-fault protection shall be provided to de-energize all normally earthed conductors of a faulted circuit in the event of an earth fault in those conductors as follows: (a) in solidly earthed circuits rated more than 230.0V-to-earth, less than 1000.0V phase-to phase and 1000.0A or more; and (b) in solidly earthed circuits rated 230.0V-to-earth or less and 2000.0A or more. (2) The maximum setting of the earth-fault protection shall be l200.0A and the maximum time delay shall be 1.0s for earth fault currents equal to or greater than 3000.0A. (3) The ampere rating of the circuits referred to in (1) above shall be considered to be: (a) the rating of the largest fuse that Can be installed in a fusible disconnecting device; (b) the highest trip setting for which the actual overcurrent device installed in a circuit breaker is rated or can be adjusted; or (c) the ampacity of the main conductor feeding the devices in cases where no main disconnecting device is provided. (4) Earth-fault protection shall be provided by: (a) an overcurrent device which incorporates earth-fault protection; (b) earth-fault trippi.ng system comprising a sensor sensors, relay and auxiliary tripping mechanism; or (c) other appropriate means. 9.5 Fuses (1) Only fuses and fuse holders of proper rating shall be used, and no bridging or short circuiting of either component shall be permitted. (2) Where plug fuses are used in branch circuits, they shall be of such a type and so installed that they are non-interchangeable with a fuse of larger rating. (3) A fuse having a fuse link which is likely to be removed or replaced while the supply is connected shall be of a type such that it can be removed or replaced without danger. 9.6 Circuit Breakers (1) Circuit breakers shall be of the trip-free type. ETHIOPIAN BUILDING CODE STANDARDS EBCS 10: 2013 SECTION 9: PROTECTION AND CONTROL (2) Indication shall be provided at the circuit breaker and at the point of operation to show whether the circuit breaker is open or closed. (3) Circuit breakers shall open the circuit in all unearthed conductors by the manual operation of a single handle and by the action of overcurrent. (4) Circuit breakers shall be of such design that any alteration by the user of either the tripping current or the time will be difficult. (5) Circuit breakers shall be equipped with tripping elements as specified in Table 9.2. 9.7 control devices (1) Control devices shall have ratings suitable for the connected load of the circuits which they control and, with the exception of isolating switches, shall be capable of safely establishing and interrupting such loads. (2) Control devices used in combination with overcurrent devices or overload devices for the control of circuits or apparatus shall be connected so that the overcurrent or overload devices will be dead when the control device is in the open position, except where this is impracticable. (4) Control devices, unless located or guarded so as to render them inaccessible to unauthorized persons and to prevent fire hazards, shall have all current-carrying parts in enclosures of metal or other fireresisting material. (5) Where electrical equipment is supplied by two or more different transformers or other sources of voltage, then: (a) a single disconnecting mean~, which will effectively isolate all unearthed conductor supplying the equipment, shall be provided integral with or adjacent to the equipment; or (b) each supply circuit shall be provided with a disconnecting means integral with or adjacent to the equipment, and the disconnecting means shall be grouped together. 9.8 switches (1) Single-throw knife switches shall be mounted with their bases in a vertical plane so that gravitational force will not tend to close them. (2) (a) Double-throw knife switches may be mounted so that the throw will be either vertical or horizontal. (b) If the throw in (1) above is vertical, a positive locking device or stop shall be provided to ensure that the blades remain in the open position when so set unless it is not intended that the switch be left in the open position. (3) Manual single-throw switches, circuit breakers, or magnetic switches, shall be connected so that the bases or moving contacts will be dead when the device is in the open position except when other conditions make this requirement unnecessary. ETHIOPIAN BUILDING CODE STANDARDS EBCS 10: 2013 SECTION 9: PROTECTION AND CONTROL 9.9 Protection and Control of Miscellaneous Apparatus (1) Socket outlets shall not be connected to a branch circuit having overcurrent protection rated or set at more than the ampere rating of the socket outlets except as permitted by other Sections of this Code. (2) Portable appliances need not be equipped with additional control devices where the appliances are (3) Control devices, with the exception of isolating switches, shall be readily accessible. (a) rated at not more than 1500.0W; and (b) provided with cord connectors, attachment plugs or other means by which they can be disconnected readily from the circuits. (3) Where switches are used to control an outlet or outlets from more than one point, the switches shall be wired and connected so that the earthed conductor runs directly to the outlet or outlets controlled by the switches. (4) Except for panel boards where more than 90% of the overcurrent devices supply feeders or motor branch circuits, every panel board shall be protected on the supply side by overcurrent devices having a rating not greater than that of the panel board. (5) Transfer equipment for standby power systems shall prevent the inadvertent interconnection of normal and standby sources of supply in any operation of the transfer equipment. ETHIOPIAN BUILDING CODE STANDARDS EBCS 10: 2013 SECTION 9: PROTECTION AND CONTROL Table 9.1 Rating or setting of overcurrent devices protecting conductors (For general use where not otherwise specifically provided for) Rating or setting permitted [A] Ampacity of Conductors Fuse Circuit breaker 0-16 16 16 17-22 20 20 21-25 25 32 26-32 32 32 33-40 40 40 41-50 50 50 51-63 63 63 64-80 80 100 91-100 100 100 101-110 110 125 111-125 125 125 126-150 150 150 151-175 175 175 176-200 200 200 201-225 225 225 226-250 250 250 251-275 300 300 276-300 300 300 301-325 350 350 326-350 350 350 351-400 400 400 401-450 450 450 451-500 500 500 501-525 600 600 526-550 600 600 551-600 600 600 ETHIOPIAN BUILDING CODE STANDARDS EBCS 10: 2013 SECTION 9: PROTECTION AND CONTROL Table 9.2 Overcurrent trip coils for circuit breakers and overload devices for protecting motors For circuit protection† Number and location of overcurrent devices (Trip Coils) For motor overload protection System 3-trip coils, one in each conductor 3-wite, 3-phase a.c., unearthed or with earthed neutral 3-trip coils, one in each phase 4-wire, 3- phase a.c 2-trip coils, one each phase 4-wire, 2-phase a.c., unearthed Number and location of overload devices such as trip coils relays, or thermal cutouts Kind of motor 3 one in each phase not to be connected in any neural conductor 3-phase a.c. 2 one in each phase, not be connected in any neutral or earthed conductor 2-phase a.c. 1 in any conductor except a neutral or earthed conductor 1-phase a.c. or d.c 2-trip coils, o ne in each outside 3-wore, 2-phase a.c. conductor 4-trip coils, one in each unearthed conductor 4-2ire, 2-phase a.c., with earthed neutral 4-trip coils, one in each unearthed conductor 5-wire, 2-phase a.c. 2-trip coils, one in each outside 3-wire, 1-phase a.c. or d.c. 1-trip coil in each unearthed conductor 2-wire a.c. or d.c., unearthed or with one conductor earthed†† 2-trip coils, one in each unearthed conductor 3-wirie, 1-phase a.c. or d.c., with earthed neutral † This will not preclude the use of other arrangements which will provide equivalent protection. This will not prevent the use of one single-pole circuit breaker in each conductor for the protection of an unearthed 2-wire circuit. †† ETHIOPIAN BUILDING CODE STANDARDS EBCS 10: 2013