Ceiling diffusers - visible

advertisement
lindab
|
ceiling diffusers - vi sible
Ceiling diffusers - visible
1
2
3
4
5
6
7
8
9
10
HLD, DSB, Aarhus.
Usage
Function
For ventilation of larger rooms in industry, shopping malls,
hangars, arenas and similar buildings, there will typically be a need for both heating and cooling. This makes
demands on being able to vary the jet pattern from horizontal (cooling needs) to vertical (heating needs). This is in
order to avoid too great a velocity in the occupied zone in
the cooling situation, and that the air penetrates the occupied zone in the heating situation, so the greatest amount
of efficiency is obtained.
The diffusers have an adjustable jet pattern, which makes
the diffusers suitable for both heating and cooling. The jet
pattern can be adjusted manually or with several types of
electric motors.
RCW/RCWB is available with a thermal actuator, where
the jet pattern is adjustable in relation to the supply air
temperature. This way costly electrical work for the individual diffusers is saved.
11
12
13
14
15
16
17
RCW, rotation diffuser
Right to alterations reserved
18
307
lin d a b
|
c e i l i n g d i ff u s e r s - v i s i b l e
Ceiling diffusers - visible
1
2
3
4
Industrial diffusers
Product
Introduction
Functions
Page
307
RCW
309
RCWB
315
HLD
321
FKD
327
5
6
7
8
9
10
11
12
13
14
15
16
17
18
308
Right to alterations reserved
li ndab | ceiling diffu se rs - v isible
Swirl diffuser
RCW
Dimensions
d
1
60
Ø
L
H
2
U
Ø
3
D
9
Ø
4
5
6
Description
RCW is a rotation diffuser particularly suitable for rooms
with a high ceiling.
7
The diffuser is equipped with adjustable blades, so the supply air pattern can be changed from vertical to horizontal.
8
The blade settings can be adjusted manually, or the function
can be automated using various types of motor. RCW with
manual blade adjustment is supplied as standard with a
blade setting of 30°.
The motorized models are supplied as standard with a blade
setting from 30° to 75°. In the motorized versions, RCW can
be supplied with an electric on/off motor, a modulating
motor or a thermal actuator, where the supply air pattern is
changed in step with the supply air temperature
•
•
•
•
•
Suitable for both cooling and heating
Horizontal and vertical dispersal pattern
High induction
Can be supplied with an electric motor
Can be supplied with a thermal actuator
Ød
Size
ØD
mm
H
mm
L
mm
ØU
mm
Weight *
kg
250
360
240
143
285
2.40
315
460
267
168
365
3.10
400
560
292
178
450
4.40
500
670
341
226
570
6.80
630
870
391
273
740
9.90
9
10
* Motorized models weigh approx. 1 kg more than the
weight stated in the table above.
11
Motor type
12
RCW-1 Ød
Motor
315-400
NM24A-MF-F
500-630
LH24A-MF60
13
Maintenance
The visible parts of the diffuser can be wiped with a damp
cloth. For other maintenance, see installation instructions.
RCW-2 Ød
Motor
250-400
NM24A-F
500-630
LH24A60
14
15
Order code
Product
Type
Manual
Motorized - modulating
Motorized- on/off
Thermal actuator
Size
Version
RCW
a
bbb
A
Materials and finish
0
1
2
3
Material:
Aluminium & steel
Standard finish: Powder-coated
Standard colour: RAL 9010 Gloss 30
Available in other colours. Please contact Lindab's sales
department for further information.
Other blade settings can be supplied on request.
We reserve the right to make changes without prior notice
16
17
18
309
lindab | ceil ing di ffusers - visi ble
Swirl diffuser
RCW
Technical data
1
RCW with electric modulating motor
2
75
4
Blade angle
3
Capacity
Volume flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw
l0.2 [m] and sound power level LWA [dB(A)] can be seen in
the diagrams.
α°
70
Throw l0.2 / turning point l0.0
65
Throw l0.2[m] can be seen in the diagrams for isothermal air
at a speed of 0.2 m/s. Turning point l0.0 [m] can be seen in
the diagrams for heated air, +5 K, +10 K and +15 K respectively.
60
55
50
45
5
Frequency-related sound effect level
40
The sound effect level in the frequency band is defined as
LWA+Kok. Kok values are specified in charts beneath the diagrams on the following pages.
35
30
6
2
4
6
8
10
Control voltage (V)
Quick selection
7
RCW with thermal actuator
8
75
α°
70
9
Blade angle
10
65
60
qv
[m³/h]
Angle
250
30°
138
498
63
250
75°
138
498
22
315
30°
237
854
65
315
75°
237
854
24
400
30°
361
1299
60
50
400
75°
361
1299
22
500
30°
453
1630
52
500
75°
453
1630
13
630
30°
818
2943
57
630
75°
818
2943
40
35
13
14
15
16
17
l0.0
+10K
[m]
10
5
6
6
5
6
5
5
6
17
7
LWA = 50
16
18
20
22
24
Temperature (C°) C°
26
28
250
30°
192
692
121
250
75°
192
692
42
315
30°
329
1183
124
315
75°
329
1183
46
400
30°
513
1846
122
400
75°
513
1846
44
500
30°
636
2290
103
500
75°
636
2290
25
630
30°
1136
4088
110
630
75°
1136
4088
13
7
8
8
7
8
6
6
8
32
9
LWA = 60
250
30°
267
962
234
250
75°
267
962
81
315
30°
455
1638
238
315
75°
455
1638
88
400
30°
729
2623
247
400
75°
729
2623
89
500
30°
893
3216
203
500
75°
893
3216
49
630
30°
1577
5679
213
630
75°
1577
5679
62
18
310
l0.2
isoterm
[m]
LWA = 40
Size
30
12
Pt
[Pa]
55
45
11
qv
[l/s]
We reserve the right to make changes without prior notice
18
10
10
11
11
12
8
9
11
12
li ndab | ceiling diffu se rs - v isible
Swirl diffuser
RCW
Technical data
1
ǻpt [Pa] RCW-250a
150
60°
45° 75°
30°
ǻpt [Pa] RCW-500a
150
30°
45°
60°
75°
50
100
70
50
70
40
50
45
50
35
30
30
2
100
45
3
40
35
30
25
30
20
20
4
25
20
15
15
20
LWA dB(A)
10
50
60
70
80 90 100
200
300
150
400
500
200
qV [l/s]
400
qV [m3/h]
300
700
LWA dB(A)
10
200
300
1000
400
1000
500
1500
600 700
1000
2000
2500 3000
4000
qV [l/s]
1500
qV [m3/h]
5000
5
6
Hz
63
125
250
500
1K
2K
4K
8K
Hz
63
125
250
500
1K
2K
4K
8K
Kok
7
1
-2
-2
-4
-9
-18
-21
Kok
12
1
-2
-1
-4
-12
-20
-22
ǻpt [Pa] RCW-315a
150
30°
60°
45°
ǻpt [Pa] RCW-630a
150
75°
30°
60°
75°
100
100
45
70
70
8
50
40
50
7
45°
50
50
45
35
30
40
30
20
30
25
20
15
20
30
25
10
15
LWA dB(A)
10
100
150
400
200
500
300
700
400
1000
1500
qV [l/s]
500
600 700
qV [m3/h]
2000
2500
9
35
20
7
400
500
1500
600
2000
700
1000
2500
3000
qV [l/s]
2000
qV [m3/h]
7000
1500
4000
5000
Hz
63
125
250
500
1K
2K
4K
8K
Hz
63
125
250
500
1K
2K
4K
8K
Kok
10
2
-1
-3
-4
-10
-17
-21
Kok
15
5
0
-2
-5
-12
-18
-22
ǻpt [Pa] RCW-400a
150
30°
45° 60°75°
45
70
Throw l0.2 horizontal
40
l0.2 [m]
20
30
30
LWA dB(A)
10
150
200
300
700
1000
250
315
400
500
630
10
20
15
RCW 30° isoterm
15
25
20
400
500
1500
600
2000
qV [l/s]
1000
qV [m3/h]
700
2500
13
14
50
35
11
12
Horizontal throw l0.2 is specified for free suspension. If the
diffuser is installed < 300 mm from the ceiling, the value
must be multiplied by 1.4.
50
100
10
LWA dB(A)
5
7
6
5
15
16
4
3
3000
2
Hz
63
125
250
500
1K
2K
4K
8K
Kok
12
1
-2
-2
-3
-13
-20
-23
17
l0.2 [m]
1
10
15 20
40 50
70
30 40 50
100
150
We reserve the right to make changes without prior notice
70
100
300
qV [l/s]
500 700 1000 1500
qV [m3/h]
500 700 1000 1500
3000 5000
150 200
300
18
311
lindab | ceil ing di ffusers - visi ble
Swirl diffuser
1
L;M=
RCW
2#7ISOTERM
L;M=
ª ª
ª
2
3
4
l0.0 [m]
20
8
ª
ª
L;M=
5
7
ª
6
2#7ISOTERM
L;M=
Q6;LS=
Q6;MH=
RCW-250 +5K
15
75°
60°
10
45°
l0.0 [m]
20
RCW-315 ǻT=+5K
75°
60°
15
45°
10
7
6
5
7
6
5
4
4
3
3
2
2
l0.0 [m]
1
9
30
40
150
10
l0.0 [m]
20
50
60 70 80
200
100
300
150
500
200
700
1000
l0.0 [m]
qV [l/s]
500
qV [m3/h]
300
1
30
1500
40
150
RCW-250 +10K
75°
60°
15
Q6;LS=
Q6;MH=
l0.0 [m]
20
50
60 70 80
200
100
300
150
500
200
700
300
1000
500
1500
qV [l/s]
700
qV [m3/h]
2000
RCW-315 ǻT=+10K
75°
15
60°
11
12
13
10
10
45°
7
6
5
7
6
5
4
4
3
3
2
2
l0.0 [m]
1
30
40
150
14
l0.0 [m]
20
15
50
60 70 80
200
100
300
150
500
200
700
300
1000
17
l0.0 [m]
qV [l/s]
500
qV [m3/h]
1
30
1500
40
150
RCW-250 +15K
l0.0 [m]
20
15
50
60 70 80
200
100
300
150
500
200
700
300
1000
500
1500
7
6
5
45°
RCW-315 ǻT=+15K
75°
60°
7
6
5
45°
4
3
3
2
2
l0.0 [m]
30
40
150
312
2000
10
4
1
18
qV [l/s]
700
qV [m3/h]
15
75°
60°
10
16
45°
50
60 70 80
200
300
100
150
500
200
700
qV [l/s]
500
qV [m3/h]
300
1000
1500
l0.0 [m]
1
30
40
150
50
60 70 80
200
300
We reserve the right to make changes without prior notice
100
150
500
200
700
300
1000
500
1500
2000
qV [l/s]
700
qV [m3/h]
li ndab | ceiling diffu se rs - v isible
Swirl diffuser
L;M=
RCW
2#7ISOTERM
ª
L;M=
ª
2#7ISOTERM
ª
1
ª
ª
ª
2
3
L;M=
l0.0 [m]
20
RCW-400 ǻT=+5K
4
L;M=
Q6;LS=
Q6;MH=
75°
l0.0 [m]
20
Q6;LS=
Q6;MH=
RCW-500 ǻT=+5K
5
75°
60°
15
60°
15
10
45°
10
6
45°
7
6
5
7
6
5
4
4
3
3
2
2
7
8
l0.0 [m]
1
100
150
500
l0.0 [m]
20
200
700
300
1000
500
1500
700
2000
l0.0 [m]
qV [l/s]
1000
qV [m3/h]
1
100
2500 3000
150
500
RCW-400 ǻT=+10K
l0.0 [m]
20
75°
15
200
700
300
1000
500
1500
700
2000
qV [l/s]
1500
qV [m3/h]
5000
1000
3000
10
RCW-500 ǻT=+10K
15
75°
60°
10
60°
10
45°
7
6
5
45°
7
6
5
4
4
3
3
2
2
100
150
500
l0.0 [m]
20
200
700
300
1000
500
1500
700
2000
13
l0.0 [m]
qV [l/s]
1000
qV [m3/h]
1
100
2500 3000
150
500
RCW-400 ǻT=+15K
l0.0 [m]
20
15
200
700
300
1000
500
1500
700
2000
1000
3000
qV [l/s]
1500
qV [m3/h]
5000
15
60°
10
7
6
5
45°
7
6
5
14
RCW-500 ǻT=+15K
75°
10
11
12
l0.0 [m]
1
9
75°
15
60°
4
4
3
3
2
2
45°
17
l0.0 [m]
1
100
150
500
200
700
300
1000
500
1500
qV [l/s]
1000
qV [m3/h]
700
2000
3000
16
l0.0 [m]
1
100
150
500
200
700
We reserve the right to make changes without prior notice
300
1000
500
1500
2000
700
1000
3000
qV [l/s]
1500
qV [m3/h]
5000
18
313
lindab | ceil ing di ffusers - visi ble
Swirl diffuser
1
L;M=
2#7ISOTERM
ª
RCW
ª
ª
2
3
4
L;M=
5
l0.0 [m]
20
6
RCW-630 ǻT=+5K
75°
Q6;LS=
Q6;MH=
60°
15
45°
10
7
7
6
5
4
3
8
2
l0.0 [m]
1
9
200
300
1000
10
l0.0 [m]
20
500
1500
700
2000
1000
3000
1500
5000
qV [l/s]
2000 2500
qV [m3/h]
7000
RCW-630 ǻT=+10K
75°
15
60°
11
10
45°
7
6
5
4
12
3
2
13
l0.0 [m]
1
200
1000
14
l0.0 [m]
20
15
16
300
500
1500
700
2000
1000
3000
1500
5000
qV [l/s]
2000 2500
qV [m3/h]
7000
RCW-630 ǻT=+15K
15
75°
10
60°
7
6
5
45°
4
3
17
2
l0.0 [m]
1
18
200
300
1000
314
500
1500
2000
700
1000
3000
1500
5000
qV [l/s]
2000 2500
qV [m3/h]
7000
We reserve the right to make changes without prior notice
lindab | ceil ing dif fusers - visi ble
Swirl diffuser
RCWB
Dimensions
B
1
H/2
2
H
Ød
3
4
5
ØA
6
Description
RCWB is a rotation diffuser (RCW) with integral box, particularly suitable for rooms with a high ceiling.
The diffuser is equipped with adjustable blades, so the supply air pattern can be changed from vertical to horizontal.
The blade settings can be adjusted manually, or the function
can be automated using various types of motor.
Ød
Size
ØA
mm
H
mm
B
mm
Weight *
kg
250
360
415
250
5.70
315
460
480
300
8.20
400
560
570
350
11.8
500
670
670
412
17.2
630
870
800
500
25.7
RCWB with manual blade adjustment is supplied as standard with a blade setting of 30°.
* Motorized models weigh approx. 1 kg more than the
weight stated in the table above.
The motorized models are supplied as standard with a blade
setting from 30° to 75°. In the motorized versions, RCWB
can be supplied with an electric on/off motor, a modulating
motor or a thermal actuator, where the supply air pattern is
changed in step with the supply air temperature.
Motor type
•
•
•
•
•
Suitable for both cooling and heating
Horizontal and vertical dispersal patterns
High induction
Can be supplied with an electric motor
Can be supplied with a thermal actuator
Product
Type
RCWB
Manual
Motorized - modulating
Motorized- on/off
Thermal actuator
0
1
2
3
Galvanised box
Box RAL 9010
Size
Version
0
1
a
bbb
c
A
8
9
10
RCWB-1 Ød
Motor
315-400
NM24A-MF-F
500-630
LH24A-MF60
RCWB-2 Ød
Motor
250-400
NM24A-F
500-630
LH24A60
11
12
13
14
Maintenance
Order code
7
The visible parts of the diffuser can be wiped with a damp
cloth. For other maintenance, see installation instructions.
15
Materials and finish
Material:
Standard finish:
Standard colour:
Box:
Aluminium & steel
Powder-coated
RAL 9010 Gloss 30
Hot-galvanised steel
Available in other colours. Please contact Lindab's sales
department for further information.
We reserve the right to make changes without prior notice
16
17
18
315
lindab | ceil ing di ffusers - v isible
Swirl diffuser
RCWB
Technical data
1
RCWB with electric modulating motor
2
75
4
Blade angle
3
α°
70
Throw l0.2 / turning point l0.0
65
Throw l0.2[m] can be seen in the diagrams for isothermal air
at a speed of 0.2 m/s. Turning point l0.0 [m] can be seen in
the diagrams for heated air, +5 K, +10 K and +15 K respectively.
60
55
50
45
5
Frequency-related sound effect level
40
The sound effect level in the frequency band is defined as
LWA+Kok. Kok values are specified in charts beneath the diagrams on the following pages.
35
30
6
Capacity
Volume flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw
l0.2 [m] and sound power level LWA [dB(A)] can be seen in the
diagrams.
2
4
6
8
10
Control voltage (V)
Quick selection
7
RCWB with thermal actuator
8
75
α°
Angle
30°
115
415
57
250
75°
115
415
28
315
30°
187
672
53
60
315
75°
187
672
29
55
400
30°
290
1043
49
400
75°
290
1043
27
500
30°
403
1451
47
50
45
11
13
14
15
16
17
500
75°
403
1451
22
630
30°
605
2178
39
35
630
75°
605
2178
l0.0
+10K
[m]
8
5
5
5
4
5
4
4
5
19
5
LWA = 50
16
18
20
22
24
Temperature (C°) C°
26
28
250
30°
160
575
108
250
75°
160
575
54
315
30°
257
924
101
315
75°
257
924
54
400
30°
397
1428
91
400
75°
397
1428
50
500
30°
565
2034
91
500
75°
565
2034
43
630
30°
861
3098
80
630
75°
861
3098
11
6
6
7
6
7
6
6
7
39
7
LWA = 60
250
30°
221
796
208
250
75°
221
796
103
315
30°
353
1271
190
315
75°
353
1271
103
400
30°
543
1954
170
400
75°
543
1954
93
500
30°
792
2851
180
500
75°
792
2851
85
630
30°
1224
4407
161
630
75°
1224
4407
78
18
316
l0.2
isoterm
[m]
LWA = 40
40
30
12
Pt
[Pa]
250
65
Blade angle
10
qv
[m³/h]
Size
70
9
qv
[l/s]
We reserve the right to make changes without prior notice
15
8
8
9
8
9
8
8
9
10
lindab | ceil ing dif fusers - visi ble
Swirl diffuser
RCWB
Technical data
1
ǻpt [Pa] RCWB-250a
150
30°
45°
60° 75°
100
2
50
50
40
45
40
35
30
35
20
25
15
30
15
25
20
10
10
7
7
LWA dB(A)
5
qV [l/s]
50
60
70
80
3
30
30
20
45°
60° 75°
70
45
50
30°
100
50
70
ǻpt [Pa] RCWB-500a
150
90 100
150
4
20
LWA dB(A)
5
200
200
300
400
500
600
qV [l/s]
1000
qV [m3/h]
700
qV [m3/h]
200
300
400
500
700
1000
1500
2000
2500
Hz
63
125
250
500
1K
2K
4K
8K
Hz
63
125
250
500
1K
2K
4K
8K
Kok
5
0
-5
-4
-3
-9
-17
-26
Kok
8
2
-3
-2
-4
-11
-21
-30
ǻpt [Pa] RCWB-315a
150
30°
45°
60° 75°
100
5
3000
ǻpt [Pa] RCWB-630a
150
30°
6
7
45°
60° 75°
100
50
70
70
45
50
30
45
30
35
30
20
15
20
90 100
300
150
400
25
200
500
qV [l/s]
400
qV [m3/h]
300
700
20
7
LWA dB(A)
80
30
10
5
9
35
15
7
70
40
20
25
10
8
50
50
40
300
1000
400
1000
500
1500
600
700
2000
1000
2500
3000
4000
qV [l/s]
1500
qV [m3/h]
5000
Hz
63
125
250
500
1K
2K
4K
8K
Hz
63
125
250
500
1K
2K
4K
8K
Kok
7
-1
-4
-3
-3
-10
-19
-27
Kok
7
-1
-3
-1
-4
-13
-24
-33
ǻpt [Pa] RCWB-400a
150
11
12
Throw l0.2 horizontal
30°
45°
60° 75°
100
50
70
10
LWA dB(A)
5
Horizontal throw l0.2 is specified for free suspension. If the
diffuser is installed < 300 mm from the ceiling, the value
must be multiplied by 1.4.
13
45
50
14
40
30
l0.2 [m]
20
35
20
30
15
RCWB 30° isoterm
250
315
400
15
500
25
630
10
10
15
20
7
LWA dB(A)
5
150
200
300
700
400
1000
qV [l/s]
600
qV [m3/h]
500
1500
7
6
5
16
4
3
2000
2
Hz
63
125
250
500
1K
2K
4K
8K
Kok
8
0
-5
-2
-3
-11
-20
-28
17
l0.2 [m]
1
10
15 20
40 50
70
30 40 50
100
150
We reserve the right to make changes without prior notice
70
100
300
qV [l/s]
500 700 1000 1500
qV [m3/h]
500 700 1000 1500
3000 5000
150 200
300
18
317
lindab | ceil ing di ffusers - v isible
Swirl diffuser
1
l0.2 [m]
20
RCWB
RCWB-250 - isoterm
l0.2 [m]
20
75° 60°
45°
15
2
3
4
10
7
6
5
4
4
3
3
2
2
l0.2 [m]
1
40
150
l0.0 [m]
20
8
60°
45°
7
6
5
5
7
75°
15
10
30
6
RCWB-315 - isoterm
50
60 70 80
200
100
300
150
500
200
700
300
1000
l0.2 [m]
qV [l/s]
500
qV [m3/h]
1
30
1500
40
150
RCWB-250 +5K
15
75°
60°
10
45°
l0.0 [m]
20
50
60 70 80
200
100
300
150
500
200
700
300
1000
1500
RCWB-315 ǻT=+5K
75°
60°
45°
10
7
6
5
4
4
3
3
2
2
l0.0 [m]
9
30
40
150
10
l0.0 [m]
20
50
60 70 80
200
100
300
150
500
200
700
1000
l0.0 [m]
qV [l/s]
500
qV [m3/h]
300
1
30
1500
40
150
RCWB-250 +10K
75°
60°
15
2000
15
7
6
5
1
qV [l/s]
700
qV [m3/h]
500
l0.0 [m]
20
50
60 70 80
200
100
300
150
500
200
700
300
1000
500
1500
qV [l/s]
700
qV [m3/h]
2000
RCWB-315 ǻT=+10K
75°
15
60°
11
12
13
10
10
45°
7
6
5
7
6
5
4
4
3
3
2
2
l0.0 [m]
1
30
40
150
14
l0.0 [m]
20
15
50
60 70 80
200
100
300
150
500
200
700
300
1000
17
l0.0 [m]
qV [l/s]
500
qV [m3/h]
1
30
1500
40
150
RCWB-250 +15K
l0.0 [m]
20
15
50
60 70 80
200
100
300
150
500
200
700
300
1000
500
1500
7
6
5
45°
RCWB-315 ǻT=+15K
75°
60°
7
6
5
45°
4
3
3
2
2
l0.0 [m]
30
40
150
318
2000
10
4
1
18
qV [l/s]
700
qV [m3/h]
15
75°
60°
10
16
45°
50
60 70 80
200
300
100
150
500
200
700
qV [l/s]
500
qV [m3/h]
300
1000
1500
l0.0 [m]
1
30
40
150
50
60 70 80
200
300
We reserve the right to make changes without prior notice
100
150
500
200
700
300
1000
500
1500
2000
qV [l/s]
700
qV [m3/h]
lindab | ceil ing dif fusers - visi ble
Swirl diffuser
l0.2 [m]
20
RCWB
RCWB-400 - isoterm
75°
l0.2 [m]
20
60°
15
RCWB-500 - isoterm
75°
1
60°
45°
15
45°
10
10
7
6
5
7
6
5
4
4
3
3
2
2
2
3
l0.2 [m]
1
100
150
500
l0.0 [m]
20
200
700
300
1000
500
1500
700
2000
0.2
qV [l/s]
1000
qV [m3/h]
1
100
3000
150
500
RCWB-400 ǻT=+5K
75°
l0.0 [m]
20
200
700
300
1000
500
1500
700
2000
4
[m]
qV [l/s]
1500
qV [m3/h]
5000
1000
3000
RCWB-500 ǻT=+5K
5
75°
60°
15
60°
15
10
45°
10
6
45°
7
6
5
7
6
5
4
4
3
3
2
2
7
8
l0.0 [m]
1
100
150
500
l0.0 [m]
20
200
700
300
1000
500
1500
700
2000
l0.0 [m]
qV [l/s]
1000
qV [m3/h]
1
100
2500 3000
150
500
RCWB-400 ǻT=+10K
l0.0 [m]
20
75°
15
200
700
300
1000
500
1500
700
2000
qV [l/s]
1500
qV [m3/h]
5000
1000
3000
10
RCWB-500 ǻT=+10K
15
75°
60°
10
60°
10
45°
7
6
5
45°
7
6
5
4
4
3
3
2
2
100
150
500
l0.0 [m]
20
200
700
300
1000
500
1500
700
2000
13
l0.0 [m]
qV [l/s]
1000
qV [m3/h]
1
100
2500 3000
150
500
RCWB-400 ǻT=+15K
l0.0 [m]
20
15
200
700
300
1000
500
1500
700
2000
1000
3000
qV [l/s]
1500
qV [m3/h]
5000
15
60°
10
7
6
5
45°
7
6
5
14
RCWB-500 ǻT=+15K
75°
10
11
12
l0.0 [m]
1
9
75°
15
60°
4
4
3
3
2
2
45°
17
l0.0 [m]
1
100
150
500
200
700
300
1000
500
1500
qV [l/s]
1000
qV [m3/h]
700
2000
3000
16
l0.0 [m]
1
100
150
500
200
700
We reserve the right to make changes without prior notice
300
1000
500
1500
2000
700
1000
3000
qV [l/s]
1500
qV [m3/h]
5000
18
319
lindab | ceil ing di ffusers - v isible
Swirl diffuser
1
l0.2 [m]
20
RCWB-630 - isoterm
75°
RCWB
60°
45°
15
2
10
7
6
5
4
3
3
2
4
l0.2 [m]
1
200
1000
5
l0.0 [m]
20
6
300
500
1500
700
2000
1000
3000
1500
5000
RCWB-630 ǻT=+5K
75°
qV [l/s]
2000 2500
qV [m3/h]
7000
60°
15
45°
10
7
7
6
5
4
3
8
2
l0.0 [m]
1
9
200
300
1000
10
l0.0 [m]
20
500
1500
700
2000
1000
3000
1500
5000
qV [l/s]
2000 2500
qV [m3/h]
7000
RCWB-630 ǻT=+10K
75°
15
60°
11
10
45°
7
6
5
4
12
3
2
13
l0.0 [m]
1
200
1000
14
l0.0 [m]
20
15
16
300
500
1500
700
2000
1000
3000
1500
5000
qV [l/s]
2000 2500
qV [m3/h]
7000
RCWB-630 ǻT=+15K
15
75°
10
60°
7
6
5
45°
4
3
17
2
l0.0 [m]
1
18
200
300
1000
320
500
1500
2000
700
1000
3000
1500
5000
qV [l/s]
2000 2500
qV [m3/h]
7000
We reserve the right to make changes without prior notice
l indab | ceiling diff users - visible
Perforated diffuser
HLD
Dimensions
1
Ød
2
3
82
650
1000
4
5
6
7
173
HLD is a circular high level displacement diffuser adapted
for industrial requirements. HLD is equipped with a damper
function, which makes it possible to vary the supply air pattern between horizontal or vertical, depending on whether
heating or cooling is required. The switch can be made manually, or it can be automated using several types of motor.
The external dimensions of the diffuser are adapted to the
connection, making it easy to integrate into an ordinary duct
system. HLD can be suspended from or installed on a wall
or column using the installation bracket, which ensures
great flexibility no matter how premises are used.
10
Description
8
1 7 .5
9
A
•
•
•
•
•
•
Suitable for both cooling and heating
Horizontal and vertical dispersal patterns
High capacity
Flexible positioning
Can be supplied with an electric motor
Can be supplied with a thermal actuator
Maintenance
The visible parts of the diffuser can be wiped with a damp
cloth. For other maintenance, see installation instructions.
Ød
Size
A
mm
Weight *
kg
250
192
11.5
315
225
13.7
400
270
17,0
500
322
21,0
630
390
27,0
*Motorized models weigh approx. 1 kg more than the weight
stated in the table above.
Motor type
Order code
Product
Type
Manual
Motorized - modulating
Motorized- on/off
Automatic thermal actuator
Size
10
HLD
a
0
1
2
3
Motor
NM24A-MF-F
NM24A-F
13
15
16
Materials and finish
Accessories
Product
Installation brackets (1set)
Size
12
14
bbb
Type
HLD - 1
HLD - 2
11
HLZ
a
Material:
Galvanised steel
Standard finish: Galvanised
17
HLD is also available in stainless steel. Please contact
Lindab’s sales department for further information.
18
We reserve the right to make changes without prior notice
321
lindab | ceil ing di ffusers - visi ble
Perforated diffuser
HLD
Technical data
1
2
3
4
Capacity
Supply air
Volume flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw
l0.2 [m] and sound power level LWA [dB(A)] can be seen in the
diagrams.
With its special design, HLD is suitable for the supply of
large volumes of air with short throws in a limited area. This
concentrates the supplied air in a small area within a larger
space, after which the air distributes itself around the
premises. Normally, a horizontal dispersal pattern is recommended in cooling situations and a vertical dispersal pattern
in heating situations.
Throw l0.2 / turning point l0.0
Throw l0.2[m] can be seen in the diagrams for isothermal air
at a speed of 0.2 m/s. Turning point l0.0 [m] can be seen in
the diagrams for heated air, +5 K +10 K respectively.
Frequency-related sound effect level
5
The sound effect level in the frequency band is defined as
LWA+Kok. Kok values are specified in charts beneath the diagrams on the following pages.
6
Quick selection
7
qv
[l/s]
qv
[m³/h]
Size
8
9
10
11
12
13
14
15
16
17
Pt
[Pa]
l0.2
isoterm
[m]
l0.0
+5K
[m]
Planning
HLD with cooled air works in much the same way as displacement ventilation. Displacement ventilation has a higher
temperature efficiency than mixing ventilation, and thus
more power is discharged with the same volume of air and
the same cooling temperature. For the calculation of discharged power in a cooling situation, use the calculation
method for displacement ventilation. For HLD with heated
air, power is calculated as for mixing ventilation.
Horizontal supply air - cooling
LWA = 50
250
Horizontal
259
934
44
250
Vertical
259
934
44
315
Horizontal
394
1420
37
315
Vertical
394
1420
37
400
Horizontal
586
2111
32
400
Vertical
586
2111
32
500
Horizontal
938
3377
32
500
Vertical
938
3377
32
630
Horizontal
1500
5401
32
630
Vertical
1500
5401
2
3
2
3
2
2
3
2
4
32
2
LWA = 55
250
Horizontal
305
1099
62
250
Vertical
305
1099
62
315
Horizontal
457
1647
50
315
Vertical
457
1647
50
400
Horizontal
680
2447
44
400
Vertical
680
2447
44
500
Horizontal
1087
3915
42
500
Vertical
1087
3915
42
630
Horizontal
1739
6262
42
630
Vertical
1739
6262
2
3
2
3
3
3
Vertical supply air - heating
3
3
4
42
2
LWA = 60
250
Horizontal
359
1294
85
250
Vertical
359
1294
85
315
Horizontal
531
1910
68
315
Vertical
531
1910
68
400
Horizontal
788
2838
58
400
Vertical
788
2838
58
500
Horizontal
1261
4539
57
500
Vertical
1261
4539
57
630
Horizontal
2017
7260
57
630
Vertical
2017
7260
57
2
4
3
3
3
3
4
3
5
3
18
322
We reserve the right to make changes without prior notice
l indab | ceiling diff users - visible
Perforated diffuser
HLD
Technical data
Sound power level
The diagram for sound effect level and pressure applies to
both horizontal and vertical dispersal.
L;M=
1
(,$ISOTERM
2
ǻpt [Pa] HLD
200
250
315
400
500
630
3
150
70
100
65
70
4
60
50
55
L;M=
50
30
45
20
Q6 ;LS=
40
15
35
10
30
L;M=
LWA dB(A)
7
qV [l/s]
100
150
200
300
400 500
700
1000
1500 2000
3000
qV [m3/h]
400 500
700
1000
1500 2000
3000
5000
7000 10000
(,$ISOTERM
Q6 ;MH=
5
6
7
Size
Hz
63
125
250
500
1K
2K
4K
8K
250
Kok
4
-3
-3
1
-6
-16
-29
-37
315
Kok
12
1
0
1
-7
-16
-27
-36
400
Kok
5
-3
2
1
-8
-17
-29
-41
500
Kok
5
-3
2
1
-8
-17
-29
-41
630
Kok
5
-3
2
1
-8
-17
-29
-41
8
L;M=
Throw l0.2 / Turning point l0.0
l0.0 [m]
10
These diagrams apply for installation heights > 1 m
9
Q6;LS=
HLD +5K
250
315
400
Q6;MH=
500
8
7
6
630
5
10
11
4
3
12
2
13
l0.0 [m]
1
100
150 200
500
l0.0 [m]
10
700
qV [l/s]
500 700 1000 1500 2000 3000
5000
qV [m3/h]
2000
3000
5000 7000 10000 15000
300
1000
HLD +10K
250
315
14
400
500
8
7
6
15
630
5
4
16
3
2
17
l0.0 [m]
1
150 200
700
300
1000
500
2000
We reserve the right to make changes without prior notice
700
1000
3000
1500 2000
3000
5000 7000 10000
qV [l/s]
5000 7000
qV [m3/h]
20000
18
323
lindab | ceil ing di ffusers - visi ble
Perforated diffuser
Technical data
1
Nearzone, Horizontal
All diagrams apply for suspended installation.
a0.2 [m]
8
Near zones
2
3
HLD
HLD-315
-9K (0.1m)
For cooling and horizontal supply air, HLD will function as a
displacement diffuser positioned high up.
The near zone is shown for two different heights, one “inner”
near zone a0.2 (1.8 m) defined as the distance from the diffuser where the speed at a height of 1.8 m is 0.2 m/s, and an
“outer” near zone a0.2 (0.1 m), which is the distance from the
diffuser where the speed at a height of 0.1 m is 0.2 m/s.
4
7
-6K (0.1m)
6
-3K (0.1m)
5
-3K (1.8m)
4
-6K (1.8m)
3
-9K (1.8m)
2
1
a0.2 [m]
0
300
5
400
500
600
1500
a0.2 [m]
10
6
qV [l/s]
800
qV [m3/h]
700
2000
2500
HLD-400
9
3m
-9K (0.1m)
-6K (0.1m)
8
1,8 m
7
7
-3K (0.1m)
6
0,1 m
a0,2(1,8 m)
5
-3K (1.8m)
4
-6K (1.8m)
8
3
a0,2(0,1 m)
-9K (1.8m)
2
1
9
10
a0.2 [m]
0
For wall installation the following corrections apply:
a0.2 at right angles to wall = diagram value.
a0.2 along wall = diagram value × 3.
400
500
1500
a0.2 [m]
10
600
700
2000
800
2500
qV [l/s]
1000
qV [m3/h]
3500
900
3000
HLD-500
-9K (0.1m)
-6K (0.1m)
9
3 x a0,2
11
8
7
-3K (0.1m)
6
5
12
4
-3K (1.8m)
3
-6K (1.8m)
-9K (1.8m)
2
13
1
a0,2
a0.2 [m]
0
500
14
600
2000
HLD-250
a0.2 [m]
8
-9K (0.1m)
a0.2 [m]
10
700
800
2500
900
3000
qV [l/s]
1100
qV [m3/h]
1000
3500
HLD-630
-9K (0.1m)
-6K (0.1m)
-6K (0.1m)
15
7
9
-3K (0.1m)
-3K (1.8m)
6
16
17
7
5
-6K (1.8m)
4
-9K (1.8m)
6
4
-3K (1.8m)
2
3
-6K (1.8m)
-9K (1.8m)
2
1
0
324
5
3
a0.2 [m]
18
-3K (0.1m)
8
150
500
200
700
300
1000
400
1500
500
600
2000
qV [l/s]
700
qV [m3/h]
2500
1
a0.2 [m]
0
700
800
900
3000
We reserve the right to make changes without prior notice
1000
3500
1100
4000
1200
1300
4500
qV [l/s]
1400
qV [m3/h]
5000
l indab | ceiling diff users - visible
Perforated diffuser
Technical data
HLD
Spread, Vertical
Spread
For vertical supply air with warm air, the air from the diffuser
will turn at a vertical distance of l0.0 from the diffuser. The
width of the air jet, b0.0, which can also be designated horizontal spread, can be seen in the diagrams for spread.
b0.0 [m]
8
1
HLD-315
7
6
2
+3K
5
4
3
+6K
+9K
3
2
4
1
b0.0 [m]
0
300
400
500
600
1500
b0.0 [m]
5
qV [l/s]
800
qV [m3/h]
700
2000
5
2500
HLD-400
6
+3K
l0,0
4
7
3
+6K
+9K
2
8
1
b0,0
b0.0 [m]
l0.0 values in 2 diagrams bottom right hand corner page 323.
For wall installation the following correction applies:
b0.0 wall = diagram value × 1.4.
0
400
500
1500
b0.0 [m]
5
600
700
2000
800
2500
9
qV [l/s]
1000
qV [m3/h]
3500
900
3000
10
HLD-500
4
11
+3K
3
+6K
2
+9K
12
1
1,4 x b0,0
500
b0.0 [m]
8
13
b0.0 [m]
0
600
2000
HLD-250
+3K
7
b0.0 [m]
5
700
800
2500
900
3000
qV [l/s]
1100
qV [m3/h]
1000
3500
HLD-630
15
6
4
5
14
+6K
4
+9K
+3K
3
16
3
+6K
2
2
+9K
17
1
b0.0 [m]
0
150
500
200
700
300
1000
400
1500
500
600
2000
qV [l/s]
700
qV [m3/h]
2500
1
b0.0 [m]
0
700
800
900
3000
We reserve the right to make changes without prior notice
1000
3500
1100
4000
1200
1300
4500
qV [l/s]
1400
qV [m3/h]
5000
18
325
l indab | ceiling diff users - visible
Multi-cone diffuser
FKD
Dimensions
1
Vertical
ØN
F
G
2
D
3
4
C
ØA
ØB
5
Horizontal
6
Description
The diffuser can be switched between horizontal and vertical supply air and is therefore ideal for the supply of both
heated and cooled air.
Installing an FKD diffuser up to size 400 in a plenum box
type MBB can help to achieve a stable airflow to the diffuser
as well as realise the potential for individual adjustment.
• Suitable for both supply and exhaust air
• Vertical or horizontal supply air pattern
Maintenance
The multi-cone insert can be removed to enable cleaning of
internal parts or to gain access to the duct or box. The visible parts of the diffuser can be wiped with a damp cloth.
7
E
FKD is an adjustable circular multi-cone diffuser, which is
typically used for supply air.
FKD
ØA
ØB
C
D
E
F
G
ØN
Weight
Size
mm
mm
mm
mm
mm
mm
mm
mm
kg
160
279
323
12
35
22
85
46
160
1.75
200
375
428
10
51
26
101
55
200
2.70
250
467
538
14
67
33
117
68
250
4.70
315
557
635
10
85
42
135
80
315
6.20
355
648
743
18
96
46
146
86
355
8,00
400
740
856
14
116
49
166
92
400
11.8
450
832
970
14
135
66
185
110
450
14,0
500
924
1081
17
149
66
199
116
500
18,0
630
1103
1286
18
182
66
232
116
630
21,0
Number of cones:
size 160–400: 2
size 450-630: 3
Ø A: ceiling grid opening
8
9
10
11
12
13
14
15
16
Order code
Product
Type
FKD
Connection dim.
FKD
aaa
Materials and finish
Material:
Steel
Standard finish: Powder-coated
Standard colour: RAL 9010 white
17
Ø160-630
Example: FKD-200
The diffuser is available in other colours. Please contact
Lindab’s sales department for further information.
We reserve the right to make changes without prior notice
18
327
lindab | ceil ing di ffusers - visi ble
Multi-cone diffuser
FKD
Accessories
1
2
Dispersal patterns
Plenum box
MBB
FKD is supplied for vertical supply air as standard.
The dispersal pattern can be altered to horizontal supply air
by setting the inner part of the diffuser to its lowest position.
3
E
4
FKD + MBB
LxB
10
6
7
C
Ød1
10
Ød2
8
F
9
E
FKD + MBB
Duct
FKD
B
Ød1 mm Ød2 mm mm
10
11
12
13
14
15
C
mm
E
328
L
mm
160
260
159
216
50
195 - 235
310
160
310
184
262
50
220 - 260
376
125
200
310
184
262
50
236 - 276
376
160
160
380
220
323
50
255 - 295
459
160
200
380
220
323
50
270 - 310
459
160
250
380
220
323
50
286 - 326
459
200
200
460
259
396
70
361 - 401
565
200
250
460
259
396
70
327 - 367
565
200
315
460
259
396
70
345 - 385
565
250
250
540
309
486
70
377 - 417
698
250
315
540
309
486
70
395 - 435
698
250
400
540
309
486
70
426 - 466
698
315
315
540
373
646
70
460 - 500
858
315
400
540
373
646
70
491 - 531
858
Order code
MBB
MBB
Duct connection
Diffuser dimension
18
H
mm
125
Ø100-315
17
F
mm mm
100
Product
Type
16
H
5
Ø160-400
Functional use
S = Supply air
E = Exhaust
Example: FKD 200+MBB-160-200-S
We reserve the right to make changes without prior notice
aaa
bbb
c
l indab | ceiling diff users - visible
Multi-cone diffuser
Technical data
FKD
Horizontal
1
Capacity
Air flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l0.2
[m] and sound power level LWA [dB(A)] can be seen in the
diagrams.
l0.2 [m]
20
FKD
355 450
250 315 400 500
160 200
630
2
15
10
Throw l0.2
Throw l0.2 [m] can be seen in the diagram for isothermal air
at a speed of 0.2 m/s.
8
7
6
3
5
4
Frequency-related sound effect level
The sound effect level in the frequency band is defined as
Lwok = LWA + Kok. Kok values are specified in charts beneath
the diagrams on the following pages. Kok values for FKD
without a box can be found in a separate supplement.
4
3
l0.2 [m]
2
qV [l/s]
40
50 60 70 80
100
150
200
300
400 500
700
5
1000
qV [m3/h]
150
200
300
500
ǻpt [Pa] FKD
100
700
160
200
900
1500 2000
250
3000
6
315 355 400 450 500
70
630
50
7
50
45
30
40
20
8
35
15
30
10
25
7
20
5
50 60 70
200
100
150 200
300 400 500
700
300 400 500
1000
700
1500 2000
1000
3000
9
LWA dB(A)
qV [l/s]
2500
qV [m3/h]
1500
5000 7000
10
11
Sound attenuation
Sound attenuation of the diffuser ΔL from duct to room,
including end reflection, see table below.
12
FKD + MBB
Duct
FKD
Ød1
Ød2
63
Centre frequency Hz
100
160
20
125 250 500
16
5
15
1K
2K
4K
8K
17
17
16
19
125
160
13
13
8
19
13
16
16
19
125
200
15
11
6
15
12
14
16
17
160
160
16
17
10
18
17
18
20
21
160
200
15
14
7
19
15
16
18
19
160
250
17
16
4
16
15
16
16
18
200
200
13
10
6
15
18
15
19
17
200
250
13
9
4
12
17
13
17
16
200
315
13
8
3
8
16
14
16
15
250
250
14
8
8
15
17
17
17
18
250
315
13
6
5
13
15
15
16
17
250
400
12
4
3
12
13
14
14
15
315
315
7
9
8
12
17
16
17
21
315
400
7
8
7
11
16
14
16
19
13
14
15
16
17
Balancing
Balancing data is contained in a separate brochure.
We reserve the right to make changes without prior notice
18
329
lindab | ceil ing di ffusers - visi ble
Multi-cone diffuser
FKD
Technical data
1
2
3
4
Throw l0.2 / turning point l0.0
Throws l0.2[m] can be seen in the diagrams for isothermal air
at a speed of 0.2 m/s. Turning point l0.0 [m] can be seen in
the diagrams for heated air, +5 K, +10 K respectively.
Vertical
Vertical supply air correction
sound power level (LWA) and pressure loss
(Δpt)
On the following pages you can find diagrams for all sizes
FKD+MBB horizontal supply air. When Vertical supply air
values are wanted, use the correction factors in the table
below.
FKD + MBB
ǻpt [Pa] FKD
150
160
200
250
315
355 400 450 500
100
630
5
70
50
50
45
30
6
40
20
35
15
30
25
10
7
20
7
LWA dB(A)
5
30
70
150 200
8
9
40 50
L;M=
100
150 200
300
500
& +$ISOTERM
700
qV [l/s]
500 700 1000
2000
qV [m3/h]
2000 3000
5000 7000
300
1000
Vertical supply air
Duct
FKD
Ød1
Ød2
LWA
Correction factor
Δpt
100
160
3
x 1,2
125
160
1
x 1,2
125
200
1
x 1,1
160
160
5
x 1,5
160
200
3
x 1,3
160
250
0
x 1,1
200
200
1
x 1,3
200
250
5
x 1,2
200
315
0
x 1,1
250
250
1
x 1,3
250
315
2
x 1,3
250
400
1
x 1,1
315
315
4
x 1,4
315
400
3
x 1,2
10
11
12
L;M=
Q6 ;LS=
13
14
l0.0 [m]
20
FKD +5K
160 200
Q6 ;MH=
250 315
355
400
450
15
l0.0 [m]
20
FKD +10K
160 200 250
315
15
355
400
450
10
500
500
15
16
17
10
630
7
6
5
7
6
5
4
4
3
3
2
2
330
l0.0 [m]
l0.0 [m]
1
30
18
630
40
150
50 60 70
200
100
300
150
500
200
700
300
1000
qV [l/s]
500
700
1000
qV [m3/h]
1500 2000
3000
1
30
40
150
50 60 70
200
100
300
We reserve the right to make changes without prior notice
150
500
200
700
300
1000
500
1500 2000
qV [l/s]
1000
qV [m3/h]
3000
700
l indab | ceiling diff users - visible
Multi-cone diffuser
FKD
Technical data
FKD 160 + MBB Horizontal
FKD 200 + MBB Horizontal
ǻpt [Pa] FKD-160+MBB-160-160-S
250
ǻpt [Pa] FKD-200+MBB-200-200-S
250
200
200
150
150
100
40
LWA dB(A)
10
30
40
25
15
20
50
150
60
70
200
80
100
300
120
400
140
500
qV [l/s]
160
qV [m3/h]
4
30
20
25
15
40
35
30
30
20
3
45
50
35
30
50
70
45
50
2
100
50
70
1
LWA dB(A)
20
10
50
60
70
80
200
100
300
120
140
400
160
500
5
qV [l/s]
240
qV [m3/h]
180 200
700
6
Hz
63
125
250
500
1K
2K
4K
8K
Hz
63
125
250
500
1K
2K
4K
8K
Kok
11
7
0
-6
-4
-9
-22
-31
Kok
13
5
-2
-5
-3
-12
-22
-28
7
ǻpt [Pa] FKD-160+MBB-125-160-S
ǻpt [Pa] FKD-200+MBB-160-200-S
250
250
200
200
150
8
150
50
100
45
70
35
30
30
25
20
15
LWA dB(A)
10
20
25
30
80
30
40
100
50
150
60
70
80
200
100
300
qV [l/s]
120
qV [m3/h]
400
10
25
20
20
15
9
40
50
35
30
45
70
40
50
50
100
20
LWA dB(A)
10
30
40
50
150
60
70
80
200
100
300
120
qV [l/s]
160
qV [m3/h]
140
400
500
Hz
63
125
250
500
1K
2K
4K
8K
Hz
63
125
250
500
1K
2K
4K
8K
Kok
10
5
2
-5
-5
-9
-18
-25
Kok
11
5
1
-5
-4
-11
-20
-25
200
50
150
150
45
100
30
35
25
20
20
15
15
LWA dB(A)
10
10
15
40
50
20
60
70
25
80
30
100
40
150
50
60
70
200
80
300
qV [l/s]
100
qV [m3/h]
15
30
30
20
20
40
50
25
30
14
45
70
35
50
50
100
40
70
12
13
ǻpt [Pa] FKD-200+MBB-125-200-S
250
200
ǻpt [Pa] FKD-160+MBB-100-160-S
250
11
LWA dB(A)
10
20
25
80
30
40
100
50
150
60
70
200
80
300
100
120
400
qV [l/s]
140
qV [m3/h]
500
Hz
63
125
250
500
1K
2K
4K
8K
Hz
63
125
250
500
1K
2K
4K
8K
Kok
9
4
2
-3
-5
-9
-16
-22
Kok
11
4
1
-4
-4
-10
-16
-23
We reserve the right to make changes without prior notice
16
17
18
331
lindab | ceil ing di ffusers - visi ble
Multi-cone diffuser
FKD
Technical data
1
2
3
FKD 250 + MBB Horizontal
FKD 315 + MBB Horizontal
ǻpt [Pa] FKD-250+MBB-250-250-S
250
ǻpt [Pa] FKD-315+MBB-315-315-S
250
200
200
150
150
100
100
50
70
50
50
70
45
45
50
40
40
4
30
50
60
70
200
80
100
120
300
25
15
LWA dB(A)
20
10
30
20
25
15
5
30
35
30
20
35
140
400
160 180 200
500
240
700
280
1000
qV [l/s]
20
LWA dB(A)
10
50
qV [m3/h]
60
70
200
80 90 100
300
150
400
500
200
250
qV [l/s]
350 400
qV [m3/h]
1250
300
700
6
Hz
63
125
250
500
1K
2K
4K
8K
Hz
63
125
250
500
1K
2K
4K
8K
Kok
12
5
-2
-4
-3
-13
-20
-26
Kok
14
3
0
-2
-4
-14
-20
-26
7
8
ǻpt [Pa] FKD-250+MBB-200-250-S
250
ǻpt [Pa] FKD-315+MBB-250-315-S
250
200
200
150
150
100
9
100
50
70
70
45
40
50
50
45
50
40
35
30
10
30
30
25
20
50
70
80
200
12
13
60
100
300
120
140
400
160
500
700
60
70
200
80 90 100
300
150
400
500
200
250
qV [l/s]
350 400
qV [m3/h]
1250
300
700
63
125
250
500
1K
2K
4K
8K
Hz
63
125
250
500
1K
2K
4K
8K
5
-2
-3
-3
-12
-19
-24
Kok
12
5
-1
-2
-4
-12
-19
-21
ǻpt [Pa] FKD-250+MBB-160-250-S
250
ǻpt [Pa] FKD-315+MBB-200-315-S
250
200
200
50
100
35
30
30
25
15
LWA dB(A)
10
50
150
17
60
30
25
20
20
40
40
50
35
15
50
45
70
40
30
150
100
45
30
332
50
11
20
18
LWA dB(A)
Kok
50
16
20
10
Hz
70
15
qV [l/s]
240
qV [m3/h]
180 200
150
14
25
15
LWA dB(A)
10
11
30
20
20
15
35
70
80
200
100
300
120
400
qV [l/s]
140 160 180
qV [m3/h]
500
20
LWA dB(A)
10
50
60
70
200
80
100
300
120
400
140
160 180 200
500
240
700
280
1000
Hz
63
125
250
500
1K
2K
4K
8K
Hz
63
125
250
500
1K
2K
4K
8K
Kok
12
4
0
-3
-4
-12
-18
-24
Kok
9
5
-1
-2
-5
-11
-18
-24
We reserve the right to make changes without prior notice
qV [l/s]
qV [m3/h]
l indab | ceiling diff users - visible
Multi-cone diffuser
FKD
Technical data
1
FKD 400 + MBB Horizontal
ǻpt [Pa] FKD-400+MBB-315-400-S
250
2
200
150
100
50
70
3
45
50
40
35
30
4
30
20
25
15
20
LWA dB(A)
10
70
80 90
150
300
400
200
500
250
300 350 400
700
5
qV [l/s]
500
1250 1500
2000
qV [m3/h]
6
Hz
63
125
250
500
1K
2K
4K
8K
Kok
11
4
1
-1
-6
-12
-17
-24
7
ǻpt [Pa] FKD-400-MBB-250-400-S
250
200
8
150
50
100
45
70
9
40
50
35
30
30
20
10
25
15
20
LWA dB(A)
10
50
60
70
200
80 90 100
300
150
400
500
200
250
300
700
qV [l/s]
350 400
qV [m3/h]
1250
Hz
63
125
250
500
1K
2K
4K
8K
Kok
9
4
1
-1
-6
-12
-17
-25
11
12
13
14
15
16
17
18
We reserve the right to make changes without prior notice
333
Download