lindab | ceiling diffusers - vi sible Ceiling diffusers - visible 1 2 3 4 5 6 7 8 9 10 HLD, DSB, Aarhus. Usage Function For ventilation of larger rooms in industry, shopping malls, hangars, arenas and similar buildings, there will typically be a need for both heating and cooling. This makes demands on being able to vary the jet pattern from horizontal (cooling needs) to vertical (heating needs). This is in order to avoid too great a velocity in the occupied zone in the cooling situation, and that the air penetrates the occupied zone in the heating situation, so the greatest amount of efficiency is obtained. The diffusers have an adjustable jet pattern, which makes the diffusers suitable for both heating and cooling. The jet pattern can be adjusted manually or with several types of electric motors. RCW/RCWB is available with a thermal actuator, where the jet pattern is adjustable in relation to the supply air temperature. This way costly electrical work for the individual diffusers is saved. 11 12 13 14 15 16 17 RCW, rotation diffuser Right to alterations reserved 18 307 lin d a b | c e i l i n g d i ff u s e r s - v i s i b l e Ceiling diffusers - visible 1 2 3 4 Industrial diffusers Product Introduction Functions Page 307 RCW 309 RCWB 315 HLD 321 FKD 327 5 6 7 8 9 10 11 12 13 14 15 16 17 18 308 Right to alterations reserved li ndab | ceiling diffu se rs - v isible Swirl diffuser RCW Dimensions d 1 60 Ø L H 2 U Ø 3 D 9 Ø 4 5 6 Description RCW is a rotation diffuser particularly suitable for rooms with a high ceiling. 7 The diffuser is equipped with adjustable blades, so the supply air pattern can be changed from vertical to horizontal. 8 The blade settings can be adjusted manually, or the function can be automated using various types of motor. RCW with manual blade adjustment is supplied as standard with a blade setting of 30°. The motorized models are supplied as standard with a blade setting from 30° to 75°. In the motorized versions, RCW can be supplied with an electric on/off motor, a modulating motor or a thermal actuator, where the supply air pattern is changed in step with the supply air temperature • • • • • Suitable for both cooling and heating Horizontal and vertical dispersal pattern High induction Can be supplied with an electric motor Can be supplied with a thermal actuator Ød Size ØD mm H mm L mm ØU mm Weight * kg 250 360 240 143 285 2.40 315 460 267 168 365 3.10 400 560 292 178 450 4.40 500 670 341 226 570 6.80 630 870 391 273 740 9.90 9 10 * Motorized models weigh approx. 1 kg more than the weight stated in the table above. 11 Motor type 12 RCW-1 Ød Motor 315-400 NM24A-MF-F 500-630 LH24A-MF60 13 Maintenance The visible parts of the diffuser can be wiped with a damp cloth. For other maintenance, see installation instructions. RCW-2 Ød Motor 250-400 NM24A-F 500-630 LH24A60 14 15 Order code Product Type Manual Motorized - modulating Motorized- on/off Thermal actuator Size Version RCW a bbb A Materials and finish 0 1 2 3 Material: Aluminium & steel Standard finish: Powder-coated Standard colour: RAL 9010 Gloss 30 Available in other colours. Please contact Lindab's sales department for further information. Other blade settings can be supplied on request. We reserve the right to make changes without prior notice 16 17 18 309 lindab | ceil ing di ffusers - visi ble Swirl diffuser RCW Technical data 1 RCW with electric modulating motor 2 75 4 Blade angle 3 Capacity Volume flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l0.2 [m] and sound power level LWA [dB(A)] can be seen in the diagrams. α° 70 Throw l0.2 / turning point l0.0 65 Throw l0.2[m] can be seen in the diagrams for isothermal air at a speed of 0.2 m/s. Turning point l0.0 [m] can be seen in the diagrams for heated air, +5 K, +10 K and +15 K respectively. 60 55 50 45 5 Frequency-related sound effect level 40 The sound effect level in the frequency band is defined as LWA+Kok. Kok values are specified in charts beneath the diagrams on the following pages. 35 30 6 2 4 6 8 10 Control voltage (V) Quick selection 7 RCW with thermal actuator 8 75 α° 70 9 Blade angle 10 65 60 qv [m³/h] Angle 250 30° 138 498 63 250 75° 138 498 22 315 30° 237 854 65 315 75° 237 854 24 400 30° 361 1299 60 50 400 75° 361 1299 22 500 30° 453 1630 52 500 75° 453 1630 13 630 30° 818 2943 57 630 75° 818 2943 40 35 13 14 15 16 17 l0.0 +10K [m] 10 5 6 6 5 6 5 5 6 17 7 LWA = 50 16 18 20 22 24 Temperature (C°) C° 26 28 250 30° 192 692 121 250 75° 192 692 42 315 30° 329 1183 124 315 75° 329 1183 46 400 30° 513 1846 122 400 75° 513 1846 44 500 30° 636 2290 103 500 75° 636 2290 25 630 30° 1136 4088 110 630 75° 1136 4088 13 7 8 8 7 8 6 6 8 32 9 LWA = 60 250 30° 267 962 234 250 75° 267 962 81 315 30° 455 1638 238 315 75° 455 1638 88 400 30° 729 2623 247 400 75° 729 2623 89 500 30° 893 3216 203 500 75° 893 3216 49 630 30° 1577 5679 213 630 75° 1577 5679 62 18 310 l0.2 isoterm [m] LWA = 40 Size 30 12 Pt [Pa] 55 45 11 qv [l/s] We reserve the right to make changes without prior notice 18 10 10 11 11 12 8 9 11 12 li ndab | ceiling diffu se rs - v isible Swirl diffuser RCW Technical data 1 ǻpt [Pa] RCW-250a 150 60° 45° 75° 30° ǻpt [Pa] RCW-500a 150 30° 45° 60° 75° 50 100 70 50 70 40 50 45 50 35 30 30 2 100 45 3 40 35 30 25 30 20 20 4 25 20 15 15 20 LWA dB(A) 10 50 60 70 80 90 100 200 300 150 400 500 200 qV [l/s] 400 qV [m3/h] 300 700 LWA dB(A) 10 200 300 1000 400 1000 500 1500 600 700 1000 2000 2500 3000 4000 qV [l/s] 1500 qV [m3/h] 5000 5 6 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K Kok 7 1 -2 -2 -4 -9 -18 -21 Kok 12 1 -2 -1 -4 -12 -20 -22 ǻpt [Pa] RCW-315a 150 30° 60° 45° ǻpt [Pa] RCW-630a 150 75° 30° 60° 75° 100 100 45 70 70 8 50 40 50 7 45° 50 50 45 35 30 40 30 20 30 25 20 15 20 30 25 10 15 LWA dB(A) 10 100 150 400 200 500 300 700 400 1000 1500 qV [l/s] 500 600 700 qV [m3/h] 2000 2500 9 35 20 7 400 500 1500 600 2000 700 1000 2500 3000 qV [l/s] 2000 qV [m3/h] 7000 1500 4000 5000 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K Kok 10 2 -1 -3 -4 -10 -17 -21 Kok 15 5 0 -2 -5 -12 -18 -22 ǻpt [Pa] RCW-400a 150 30° 45° 60°75° 45 70 Throw l0.2 horizontal 40 l0.2 [m] 20 30 30 LWA dB(A) 10 150 200 300 700 1000 250 315 400 500 630 10 20 15 RCW 30° isoterm 15 25 20 400 500 1500 600 2000 qV [l/s] 1000 qV [m3/h] 700 2500 13 14 50 35 11 12 Horizontal throw l0.2 is specified for free suspension. If the diffuser is installed < 300 mm from the ceiling, the value must be multiplied by 1.4. 50 100 10 LWA dB(A) 5 7 6 5 15 16 4 3 3000 2 Hz 63 125 250 500 1K 2K 4K 8K Kok 12 1 -2 -2 -3 -13 -20 -23 17 l0.2 [m] 1 10 15 20 40 50 70 30 40 50 100 150 We reserve the right to make changes without prior notice 70 100 300 qV [l/s] 500 700 1000 1500 qV [m3/h] 500 700 1000 1500 3000 5000 150 200 300 18 311 lindab | ceil ing di ffusers - visi ble Swirl diffuser 1 L;M= RCW 2#7ISOTERM L;M= ª ª ª 2 3 4 l0.0 [m] 20 8 ª ª L;M= 5 7 ª 6 2#7ISOTERM L;M= Q6;LS= Q6;MH= RCW-250 +5K 15 75° 60° 10 45° l0.0 [m] 20 RCW-315 ǻT=+5K 75° 60° 15 45° 10 7 6 5 7 6 5 4 4 3 3 2 2 l0.0 [m] 1 9 30 40 150 10 l0.0 [m] 20 50 60 70 80 200 100 300 150 500 200 700 1000 l0.0 [m] qV [l/s] 500 qV [m3/h] 300 1 30 1500 40 150 RCW-250 +10K 75° 60° 15 Q6;LS= Q6;MH= l0.0 [m] 20 50 60 70 80 200 100 300 150 500 200 700 300 1000 500 1500 qV [l/s] 700 qV [m3/h] 2000 RCW-315 ǻT=+10K 75° 15 60° 11 12 13 10 10 45° 7 6 5 7 6 5 4 4 3 3 2 2 l0.0 [m] 1 30 40 150 14 l0.0 [m] 20 15 50 60 70 80 200 100 300 150 500 200 700 300 1000 17 l0.0 [m] qV [l/s] 500 qV [m3/h] 1 30 1500 40 150 RCW-250 +15K l0.0 [m] 20 15 50 60 70 80 200 100 300 150 500 200 700 300 1000 500 1500 7 6 5 45° RCW-315 ǻT=+15K 75° 60° 7 6 5 45° 4 3 3 2 2 l0.0 [m] 30 40 150 312 2000 10 4 1 18 qV [l/s] 700 qV [m3/h] 15 75° 60° 10 16 45° 50 60 70 80 200 300 100 150 500 200 700 qV [l/s] 500 qV [m3/h] 300 1000 1500 l0.0 [m] 1 30 40 150 50 60 70 80 200 300 We reserve the right to make changes without prior notice 100 150 500 200 700 300 1000 500 1500 2000 qV [l/s] 700 qV [m3/h] li ndab | ceiling diffu se rs - v isible Swirl diffuser L;M= RCW 2#7ISOTERM ª L;M= ª 2#7ISOTERM ª 1 ª ª ª 2 3 L;M= l0.0 [m] 20 RCW-400 ǻT=+5K 4 L;M= Q6;LS= Q6;MH= 75° l0.0 [m] 20 Q6;LS= Q6;MH= RCW-500 ǻT=+5K 5 75° 60° 15 60° 15 10 45° 10 6 45° 7 6 5 7 6 5 4 4 3 3 2 2 7 8 l0.0 [m] 1 100 150 500 l0.0 [m] 20 200 700 300 1000 500 1500 700 2000 l0.0 [m] qV [l/s] 1000 qV [m3/h] 1 100 2500 3000 150 500 RCW-400 ǻT=+10K l0.0 [m] 20 75° 15 200 700 300 1000 500 1500 700 2000 qV [l/s] 1500 qV [m3/h] 5000 1000 3000 10 RCW-500 ǻT=+10K 15 75° 60° 10 60° 10 45° 7 6 5 45° 7 6 5 4 4 3 3 2 2 100 150 500 l0.0 [m] 20 200 700 300 1000 500 1500 700 2000 13 l0.0 [m] qV [l/s] 1000 qV [m3/h] 1 100 2500 3000 150 500 RCW-400 ǻT=+15K l0.0 [m] 20 15 200 700 300 1000 500 1500 700 2000 1000 3000 qV [l/s] 1500 qV [m3/h] 5000 15 60° 10 7 6 5 45° 7 6 5 14 RCW-500 ǻT=+15K 75° 10 11 12 l0.0 [m] 1 9 75° 15 60° 4 4 3 3 2 2 45° 17 l0.0 [m] 1 100 150 500 200 700 300 1000 500 1500 qV [l/s] 1000 qV [m3/h] 700 2000 3000 16 l0.0 [m] 1 100 150 500 200 700 We reserve the right to make changes without prior notice 300 1000 500 1500 2000 700 1000 3000 qV [l/s] 1500 qV [m3/h] 5000 18 313 lindab | ceil ing di ffusers - visi ble Swirl diffuser 1 L;M= 2#7ISOTERM ª RCW ª ª 2 3 4 L;M= 5 l0.0 [m] 20 6 RCW-630 ǻT=+5K 75° Q6;LS= Q6;MH= 60° 15 45° 10 7 7 6 5 4 3 8 2 l0.0 [m] 1 9 200 300 1000 10 l0.0 [m] 20 500 1500 700 2000 1000 3000 1500 5000 qV [l/s] 2000 2500 qV [m3/h] 7000 RCW-630 ǻT=+10K 75° 15 60° 11 10 45° 7 6 5 4 12 3 2 13 l0.0 [m] 1 200 1000 14 l0.0 [m] 20 15 16 300 500 1500 700 2000 1000 3000 1500 5000 qV [l/s] 2000 2500 qV [m3/h] 7000 RCW-630 ǻT=+15K 15 75° 10 60° 7 6 5 45° 4 3 17 2 l0.0 [m] 1 18 200 300 1000 314 500 1500 2000 700 1000 3000 1500 5000 qV [l/s] 2000 2500 qV [m3/h] 7000 We reserve the right to make changes without prior notice lindab | ceil ing dif fusers - visi ble Swirl diffuser RCWB Dimensions B 1 H/2 2 H Ød 3 4 5 ØA 6 Description RCWB is a rotation diffuser (RCW) with integral box, particularly suitable for rooms with a high ceiling. The diffuser is equipped with adjustable blades, so the supply air pattern can be changed from vertical to horizontal. The blade settings can be adjusted manually, or the function can be automated using various types of motor. Ød Size ØA mm H mm B mm Weight * kg 250 360 415 250 5.70 315 460 480 300 8.20 400 560 570 350 11.8 500 670 670 412 17.2 630 870 800 500 25.7 RCWB with manual blade adjustment is supplied as standard with a blade setting of 30°. * Motorized models weigh approx. 1 kg more than the weight stated in the table above. The motorized models are supplied as standard with a blade setting from 30° to 75°. In the motorized versions, RCWB can be supplied with an electric on/off motor, a modulating motor or a thermal actuator, where the supply air pattern is changed in step with the supply air temperature. Motor type • • • • • Suitable for both cooling and heating Horizontal and vertical dispersal patterns High induction Can be supplied with an electric motor Can be supplied with a thermal actuator Product Type RCWB Manual Motorized - modulating Motorized- on/off Thermal actuator 0 1 2 3 Galvanised box Box RAL 9010 Size Version 0 1 a bbb c A 8 9 10 RCWB-1 Ød Motor 315-400 NM24A-MF-F 500-630 LH24A-MF60 RCWB-2 Ød Motor 250-400 NM24A-F 500-630 LH24A60 11 12 13 14 Maintenance Order code 7 The visible parts of the diffuser can be wiped with a damp cloth. For other maintenance, see installation instructions. 15 Materials and finish Material: Standard finish: Standard colour: Box: Aluminium & steel Powder-coated RAL 9010 Gloss 30 Hot-galvanised steel Available in other colours. Please contact Lindab's sales department for further information. We reserve the right to make changes without prior notice 16 17 18 315 lindab | ceil ing di ffusers - v isible Swirl diffuser RCWB Technical data 1 RCWB with electric modulating motor 2 75 4 Blade angle 3 α° 70 Throw l0.2 / turning point l0.0 65 Throw l0.2[m] can be seen in the diagrams for isothermal air at a speed of 0.2 m/s. Turning point l0.0 [m] can be seen in the diagrams for heated air, +5 K, +10 K and +15 K respectively. 60 55 50 45 5 Frequency-related sound effect level 40 The sound effect level in the frequency band is defined as LWA+Kok. Kok values are specified in charts beneath the diagrams on the following pages. 35 30 6 Capacity Volume flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l0.2 [m] and sound power level LWA [dB(A)] can be seen in the diagrams. 2 4 6 8 10 Control voltage (V) Quick selection 7 RCWB with thermal actuator 8 75 α° Angle 30° 115 415 57 250 75° 115 415 28 315 30° 187 672 53 60 315 75° 187 672 29 55 400 30° 290 1043 49 400 75° 290 1043 27 500 30° 403 1451 47 50 45 11 13 14 15 16 17 500 75° 403 1451 22 630 30° 605 2178 39 35 630 75° 605 2178 l0.0 +10K [m] 8 5 5 5 4 5 4 4 5 19 5 LWA = 50 16 18 20 22 24 Temperature (C°) C° 26 28 250 30° 160 575 108 250 75° 160 575 54 315 30° 257 924 101 315 75° 257 924 54 400 30° 397 1428 91 400 75° 397 1428 50 500 30° 565 2034 91 500 75° 565 2034 43 630 30° 861 3098 80 630 75° 861 3098 11 6 6 7 6 7 6 6 7 39 7 LWA = 60 250 30° 221 796 208 250 75° 221 796 103 315 30° 353 1271 190 315 75° 353 1271 103 400 30° 543 1954 170 400 75° 543 1954 93 500 30° 792 2851 180 500 75° 792 2851 85 630 30° 1224 4407 161 630 75° 1224 4407 78 18 316 l0.2 isoterm [m] LWA = 40 40 30 12 Pt [Pa] 250 65 Blade angle 10 qv [m³/h] Size 70 9 qv [l/s] We reserve the right to make changes without prior notice 15 8 8 9 8 9 8 8 9 10 lindab | ceil ing dif fusers - visi ble Swirl diffuser RCWB Technical data 1 ǻpt [Pa] RCWB-250a 150 30° 45° 60° 75° 100 2 50 50 40 45 40 35 30 35 20 25 15 30 15 25 20 10 10 7 7 LWA dB(A) 5 qV [l/s] 50 60 70 80 3 30 30 20 45° 60° 75° 70 45 50 30° 100 50 70 ǻpt [Pa] RCWB-500a 150 90 100 150 4 20 LWA dB(A) 5 200 200 300 400 500 600 qV [l/s] 1000 qV [m3/h] 700 qV [m3/h] 200 300 400 500 700 1000 1500 2000 2500 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K Kok 5 0 -5 -4 -3 -9 -17 -26 Kok 8 2 -3 -2 -4 -11 -21 -30 ǻpt [Pa] RCWB-315a 150 30° 45° 60° 75° 100 5 3000 ǻpt [Pa] RCWB-630a 150 30° 6 7 45° 60° 75° 100 50 70 70 45 50 30 45 30 35 30 20 15 20 90 100 300 150 400 25 200 500 qV [l/s] 400 qV [m3/h] 300 700 20 7 LWA dB(A) 80 30 10 5 9 35 15 7 70 40 20 25 10 8 50 50 40 300 1000 400 1000 500 1500 600 700 2000 1000 2500 3000 4000 qV [l/s] 1500 qV [m3/h] 5000 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K Kok 7 -1 -4 -3 -3 -10 -19 -27 Kok 7 -1 -3 -1 -4 -13 -24 -33 ǻpt [Pa] RCWB-400a 150 11 12 Throw l0.2 horizontal 30° 45° 60° 75° 100 50 70 10 LWA dB(A) 5 Horizontal throw l0.2 is specified for free suspension. If the diffuser is installed < 300 mm from the ceiling, the value must be multiplied by 1.4. 13 45 50 14 40 30 l0.2 [m] 20 35 20 30 15 RCWB 30° isoterm 250 315 400 15 500 25 630 10 10 15 20 7 LWA dB(A) 5 150 200 300 700 400 1000 qV [l/s] 600 qV [m3/h] 500 1500 7 6 5 16 4 3 2000 2 Hz 63 125 250 500 1K 2K 4K 8K Kok 8 0 -5 -2 -3 -11 -20 -28 17 l0.2 [m] 1 10 15 20 40 50 70 30 40 50 100 150 We reserve the right to make changes without prior notice 70 100 300 qV [l/s] 500 700 1000 1500 qV [m3/h] 500 700 1000 1500 3000 5000 150 200 300 18 317 lindab | ceil ing di ffusers - v isible Swirl diffuser 1 l0.2 [m] 20 RCWB RCWB-250 - isoterm l0.2 [m] 20 75° 60° 45° 15 2 3 4 10 7 6 5 4 4 3 3 2 2 l0.2 [m] 1 40 150 l0.0 [m] 20 8 60° 45° 7 6 5 5 7 75° 15 10 30 6 RCWB-315 - isoterm 50 60 70 80 200 100 300 150 500 200 700 300 1000 l0.2 [m] qV [l/s] 500 qV [m3/h] 1 30 1500 40 150 RCWB-250 +5K 15 75° 60° 10 45° l0.0 [m] 20 50 60 70 80 200 100 300 150 500 200 700 300 1000 1500 RCWB-315 ǻT=+5K 75° 60° 45° 10 7 6 5 4 4 3 3 2 2 l0.0 [m] 9 30 40 150 10 l0.0 [m] 20 50 60 70 80 200 100 300 150 500 200 700 1000 l0.0 [m] qV [l/s] 500 qV [m3/h] 300 1 30 1500 40 150 RCWB-250 +10K 75° 60° 15 2000 15 7 6 5 1 qV [l/s] 700 qV [m3/h] 500 l0.0 [m] 20 50 60 70 80 200 100 300 150 500 200 700 300 1000 500 1500 qV [l/s] 700 qV [m3/h] 2000 RCWB-315 ǻT=+10K 75° 15 60° 11 12 13 10 10 45° 7 6 5 7 6 5 4 4 3 3 2 2 l0.0 [m] 1 30 40 150 14 l0.0 [m] 20 15 50 60 70 80 200 100 300 150 500 200 700 300 1000 17 l0.0 [m] qV [l/s] 500 qV [m3/h] 1 30 1500 40 150 RCWB-250 +15K l0.0 [m] 20 15 50 60 70 80 200 100 300 150 500 200 700 300 1000 500 1500 7 6 5 45° RCWB-315 ǻT=+15K 75° 60° 7 6 5 45° 4 3 3 2 2 l0.0 [m] 30 40 150 318 2000 10 4 1 18 qV [l/s] 700 qV [m3/h] 15 75° 60° 10 16 45° 50 60 70 80 200 300 100 150 500 200 700 qV [l/s] 500 qV [m3/h] 300 1000 1500 l0.0 [m] 1 30 40 150 50 60 70 80 200 300 We reserve the right to make changes without prior notice 100 150 500 200 700 300 1000 500 1500 2000 qV [l/s] 700 qV [m3/h] lindab | ceil ing dif fusers - visi ble Swirl diffuser l0.2 [m] 20 RCWB RCWB-400 - isoterm 75° l0.2 [m] 20 60° 15 RCWB-500 - isoterm 75° 1 60° 45° 15 45° 10 10 7 6 5 7 6 5 4 4 3 3 2 2 2 3 l0.2 [m] 1 100 150 500 l0.0 [m] 20 200 700 300 1000 500 1500 700 2000 0.2 qV [l/s] 1000 qV [m3/h] 1 100 3000 150 500 RCWB-400 ǻT=+5K 75° l0.0 [m] 20 200 700 300 1000 500 1500 700 2000 4 [m] qV [l/s] 1500 qV [m3/h] 5000 1000 3000 RCWB-500 ǻT=+5K 5 75° 60° 15 60° 15 10 45° 10 6 45° 7 6 5 7 6 5 4 4 3 3 2 2 7 8 l0.0 [m] 1 100 150 500 l0.0 [m] 20 200 700 300 1000 500 1500 700 2000 l0.0 [m] qV [l/s] 1000 qV [m3/h] 1 100 2500 3000 150 500 RCWB-400 ǻT=+10K l0.0 [m] 20 75° 15 200 700 300 1000 500 1500 700 2000 qV [l/s] 1500 qV [m3/h] 5000 1000 3000 10 RCWB-500 ǻT=+10K 15 75° 60° 10 60° 10 45° 7 6 5 45° 7 6 5 4 4 3 3 2 2 100 150 500 l0.0 [m] 20 200 700 300 1000 500 1500 700 2000 13 l0.0 [m] qV [l/s] 1000 qV [m3/h] 1 100 2500 3000 150 500 RCWB-400 ǻT=+15K l0.0 [m] 20 15 200 700 300 1000 500 1500 700 2000 1000 3000 qV [l/s] 1500 qV [m3/h] 5000 15 60° 10 7 6 5 45° 7 6 5 14 RCWB-500 ǻT=+15K 75° 10 11 12 l0.0 [m] 1 9 75° 15 60° 4 4 3 3 2 2 45° 17 l0.0 [m] 1 100 150 500 200 700 300 1000 500 1500 qV [l/s] 1000 qV [m3/h] 700 2000 3000 16 l0.0 [m] 1 100 150 500 200 700 We reserve the right to make changes without prior notice 300 1000 500 1500 2000 700 1000 3000 qV [l/s] 1500 qV [m3/h] 5000 18 319 lindab | ceil ing di ffusers - v isible Swirl diffuser 1 l0.2 [m] 20 RCWB-630 - isoterm 75° RCWB 60° 45° 15 2 10 7 6 5 4 3 3 2 4 l0.2 [m] 1 200 1000 5 l0.0 [m] 20 6 300 500 1500 700 2000 1000 3000 1500 5000 RCWB-630 ǻT=+5K 75° qV [l/s] 2000 2500 qV [m3/h] 7000 60° 15 45° 10 7 7 6 5 4 3 8 2 l0.0 [m] 1 9 200 300 1000 10 l0.0 [m] 20 500 1500 700 2000 1000 3000 1500 5000 qV [l/s] 2000 2500 qV [m3/h] 7000 RCWB-630 ǻT=+10K 75° 15 60° 11 10 45° 7 6 5 4 12 3 2 13 l0.0 [m] 1 200 1000 14 l0.0 [m] 20 15 16 300 500 1500 700 2000 1000 3000 1500 5000 qV [l/s] 2000 2500 qV [m3/h] 7000 RCWB-630 ǻT=+15K 15 75° 10 60° 7 6 5 45° 4 3 17 2 l0.0 [m] 1 18 200 300 1000 320 500 1500 2000 700 1000 3000 1500 5000 qV [l/s] 2000 2500 qV [m3/h] 7000 We reserve the right to make changes without prior notice l indab | ceiling diff users - visible Perforated diffuser HLD Dimensions 1 Ød 2 3 82 650 1000 4 5 6 7 173 HLD is a circular high level displacement diffuser adapted for industrial requirements. HLD is equipped with a damper function, which makes it possible to vary the supply air pattern between horizontal or vertical, depending on whether heating or cooling is required. The switch can be made manually, or it can be automated using several types of motor. The external dimensions of the diffuser are adapted to the connection, making it easy to integrate into an ordinary duct system. HLD can be suspended from or installed on a wall or column using the installation bracket, which ensures great flexibility no matter how premises are used. 10 Description 8 1 7 .5 9 A • • • • • • Suitable for both cooling and heating Horizontal and vertical dispersal patterns High capacity Flexible positioning Can be supplied with an electric motor Can be supplied with a thermal actuator Maintenance The visible parts of the diffuser can be wiped with a damp cloth. For other maintenance, see installation instructions. Ød Size A mm Weight * kg 250 192 11.5 315 225 13.7 400 270 17,0 500 322 21,0 630 390 27,0 *Motorized models weigh approx. 1 kg more than the weight stated in the table above. Motor type Order code Product Type Manual Motorized - modulating Motorized- on/off Automatic thermal actuator Size 10 HLD a 0 1 2 3 Motor NM24A-MF-F NM24A-F 13 15 16 Materials and finish Accessories Product Installation brackets (1set) Size 12 14 bbb Type HLD - 1 HLD - 2 11 HLZ a Material: Galvanised steel Standard finish: Galvanised 17 HLD is also available in stainless steel. Please contact Lindab’s sales department for further information. 18 We reserve the right to make changes without prior notice 321 lindab | ceil ing di ffusers - visi ble Perforated diffuser HLD Technical data 1 2 3 4 Capacity Supply air Volume flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l0.2 [m] and sound power level LWA [dB(A)] can be seen in the diagrams. With its special design, HLD is suitable for the supply of large volumes of air with short throws in a limited area. This concentrates the supplied air in a small area within a larger space, after which the air distributes itself around the premises. Normally, a horizontal dispersal pattern is recommended in cooling situations and a vertical dispersal pattern in heating situations. Throw l0.2 / turning point l0.0 Throw l0.2[m] can be seen in the diagrams for isothermal air at a speed of 0.2 m/s. Turning point l0.0 [m] can be seen in the diagrams for heated air, +5 K +10 K respectively. Frequency-related sound effect level 5 The sound effect level in the frequency band is defined as LWA+Kok. Kok values are specified in charts beneath the diagrams on the following pages. 6 Quick selection 7 qv [l/s] qv [m³/h] Size 8 9 10 11 12 13 14 15 16 17 Pt [Pa] l0.2 isoterm [m] l0.0 +5K [m] Planning HLD with cooled air works in much the same way as displacement ventilation. Displacement ventilation has a higher temperature efficiency than mixing ventilation, and thus more power is discharged with the same volume of air and the same cooling temperature. For the calculation of discharged power in a cooling situation, use the calculation method for displacement ventilation. For HLD with heated air, power is calculated as for mixing ventilation. Horizontal supply air - cooling LWA = 50 250 Horizontal 259 934 44 250 Vertical 259 934 44 315 Horizontal 394 1420 37 315 Vertical 394 1420 37 400 Horizontal 586 2111 32 400 Vertical 586 2111 32 500 Horizontal 938 3377 32 500 Vertical 938 3377 32 630 Horizontal 1500 5401 32 630 Vertical 1500 5401 2 3 2 3 2 2 3 2 4 32 2 LWA = 55 250 Horizontal 305 1099 62 250 Vertical 305 1099 62 315 Horizontal 457 1647 50 315 Vertical 457 1647 50 400 Horizontal 680 2447 44 400 Vertical 680 2447 44 500 Horizontal 1087 3915 42 500 Vertical 1087 3915 42 630 Horizontal 1739 6262 42 630 Vertical 1739 6262 2 3 2 3 3 3 Vertical supply air - heating 3 3 4 42 2 LWA = 60 250 Horizontal 359 1294 85 250 Vertical 359 1294 85 315 Horizontal 531 1910 68 315 Vertical 531 1910 68 400 Horizontal 788 2838 58 400 Vertical 788 2838 58 500 Horizontal 1261 4539 57 500 Vertical 1261 4539 57 630 Horizontal 2017 7260 57 630 Vertical 2017 7260 57 2 4 3 3 3 3 4 3 5 3 18 322 We reserve the right to make changes without prior notice l indab | ceiling diff users - visible Perforated diffuser HLD Technical data Sound power level The diagram for sound effect level and pressure applies to both horizontal and vertical dispersal. L;M= 1 (,$ISOTERM 2 ǻpt [Pa] HLD 200 250 315 400 500 630 3 150 70 100 65 70 4 60 50 55 L;M= 50 30 45 20 Q6 ;LS= 40 15 35 10 30 L;M= LWA dB(A) 7 qV [l/s] 100 150 200 300 400 500 700 1000 1500 2000 3000 qV [m3/h] 400 500 700 1000 1500 2000 3000 5000 7000 10000 (,$ISOTERM Q6 ;MH= 5 6 7 Size Hz 63 125 250 500 1K 2K 4K 8K 250 Kok 4 -3 -3 1 -6 -16 -29 -37 315 Kok 12 1 0 1 -7 -16 -27 -36 400 Kok 5 -3 2 1 -8 -17 -29 -41 500 Kok 5 -3 2 1 -8 -17 -29 -41 630 Kok 5 -3 2 1 -8 -17 -29 -41 8 L;M= Throw l0.2 / Turning point l0.0 l0.0 [m] 10 These diagrams apply for installation heights > 1 m 9 Q6;LS= HLD +5K 250 315 400 Q6;MH= 500 8 7 6 630 5 10 11 4 3 12 2 13 l0.0 [m] 1 100 150 200 500 l0.0 [m] 10 700 qV [l/s] 500 700 1000 1500 2000 3000 5000 qV [m3/h] 2000 3000 5000 7000 10000 15000 300 1000 HLD +10K 250 315 14 400 500 8 7 6 15 630 5 4 16 3 2 17 l0.0 [m] 1 150 200 700 300 1000 500 2000 We reserve the right to make changes without prior notice 700 1000 3000 1500 2000 3000 5000 7000 10000 qV [l/s] 5000 7000 qV [m3/h] 20000 18 323 lindab | ceil ing di ffusers - visi ble Perforated diffuser Technical data 1 Nearzone, Horizontal All diagrams apply for suspended installation. a0.2 [m] 8 Near zones 2 3 HLD HLD-315 -9K (0.1m) For cooling and horizontal supply air, HLD will function as a displacement diffuser positioned high up. The near zone is shown for two different heights, one “inner” near zone a0.2 (1.8 m) defined as the distance from the diffuser where the speed at a height of 1.8 m is 0.2 m/s, and an “outer” near zone a0.2 (0.1 m), which is the distance from the diffuser where the speed at a height of 0.1 m is 0.2 m/s. 4 7 -6K (0.1m) 6 -3K (0.1m) 5 -3K (1.8m) 4 -6K (1.8m) 3 -9K (1.8m) 2 1 a0.2 [m] 0 300 5 400 500 600 1500 a0.2 [m] 10 6 qV [l/s] 800 qV [m3/h] 700 2000 2500 HLD-400 9 3m -9K (0.1m) -6K (0.1m) 8 1,8 m 7 7 -3K (0.1m) 6 0,1 m a0,2(1,8 m) 5 -3K (1.8m) 4 -6K (1.8m) 8 3 a0,2(0,1 m) -9K (1.8m) 2 1 9 10 a0.2 [m] 0 For wall installation the following corrections apply: a0.2 at right angles to wall = diagram value. a0.2 along wall = diagram value × 3. 400 500 1500 a0.2 [m] 10 600 700 2000 800 2500 qV [l/s] 1000 qV [m3/h] 3500 900 3000 HLD-500 -9K (0.1m) -6K (0.1m) 9 3 x a0,2 11 8 7 -3K (0.1m) 6 5 12 4 -3K (1.8m) 3 -6K (1.8m) -9K (1.8m) 2 13 1 a0,2 a0.2 [m] 0 500 14 600 2000 HLD-250 a0.2 [m] 8 -9K (0.1m) a0.2 [m] 10 700 800 2500 900 3000 qV [l/s] 1100 qV [m3/h] 1000 3500 HLD-630 -9K (0.1m) -6K (0.1m) -6K (0.1m) 15 7 9 -3K (0.1m) -3K (1.8m) 6 16 17 7 5 -6K (1.8m) 4 -9K (1.8m) 6 4 -3K (1.8m) 2 3 -6K (1.8m) -9K (1.8m) 2 1 0 324 5 3 a0.2 [m] 18 -3K (0.1m) 8 150 500 200 700 300 1000 400 1500 500 600 2000 qV [l/s] 700 qV [m3/h] 2500 1 a0.2 [m] 0 700 800 900 3000 We reserve the right to make changes without prior notice 1000 3500 1100 4000 1200 1300 4500 qV [l/s] 1400 qV [m3/h] 5000 l indab | ceiling diff users - visible Perforated diffuser Technical data HLD Spread, Vertical Spread For vertical supply air with warm air, the air from the diffuser will turn at a vertical distance of l0.0 from the diffuser. The width of the air jet, b0.0, which can also be designated horizontal spread, can be seen in the diagrams for spread. b0.0 [m] 8 1 HLD-315 7 6 2 +3K 5 4 3 +6K +9K 3 2 4 1 b0.0 [m] 0 300 400 500 600 1500 b0.0 [m] 5 qV [l/s] 800 qV [m3/h] 700 2000 5 2500 HLD-400 6 +3K l0,0 4 7 3 +6K +9K 2 8 1 b0,0 b0.0 [m] l0.0 values in 2 diagrams bottom right hand corner page 323. For wall installation the following correction applies: b0.0 wall = diagram value × 1.4. 0 400 500 1500 b0.0 [m] 5 600 700 2000 800 2500 9 qV [l/s] 1000 qV [m3/h] 3500 900 3000 10 HLD-500 4 11 +3K 3 +6K 2 +9K 12 1 1,4 x b0,0 500 b0.0 [m] 8 13 b0.0 [m] 0 600 2000 HLD-250 +3K 7 b0.0 [m] 5 700 800 2500 900 3000 qV [l/s] 1100 qV [m3/h] 1000 3500 HLD-630 15 6 4 5 14 +6K 4 +9K +3K 3 16 3 +6K 2 2 +9K 17 1 b0.0 [m] 0 150 500 200 700 300 1000 400 1500 500 600 2000 qV [l/s] 700 qV [m3/h] 2500 1 b0.0 [m] 0 700 800 900 3000 We reserve the right to make changes without prior notice 1000 3500 1100 4000 1200 1300 4500 qV [l/s] 1400 qV [m3/h] 5000 18 325 l indab | ceiling diff users - visible Multi-cone diffuser FKD Dimensions 1 Vertical ØN F G 2 D 3 4 C ØA ØB 5 Horizontal 6 Description The diffuser can be switched between horizontal and vertical supply air and is therefore ideal for the supply of both heated and cooled air. Installing an FKD diffuser up to size 400 in a plenum box type MBB can help to achieve a stable airflow to the diffuser as well as realise the potential for individual adjustment. • Suitable for both supply and exhaust air • Vertical or horizontal supply air pattern Maintenance The multi-cone insert can be removed to enable cleaning of internal parts or to gain access to the duct or box. The visible parts of the diffuser can be wiped with a damp cloth. 7 E FKD is an adjustable circular multi-cone diffuser, which is typically used for supply air. FKD ØA ØB C D E F G ØN Weight Size mm mm mm mm mm mm mm mm kg 160 279 323 12 35 22 85 46 160 1.75 200 375 428 10 51 26 101 55 200 2.70 250 467 538 14 67 33 117 68 250 4.70 315 557 635 10 85 42 135 80 315 6.20 355 648 743 18 96 46 146 86 355 8,00 400 740 856 14 116 49 166 92 400 11.8 450 832 970 14 135 66 185 110 450 14,0 500 924 1081 17 149 66 199 116 500 18,0 630 1103 1286 18 182 66 232 116 630 21,0 Number of cones: size 160–400: 2 size 450-630: 3 Ø A: ceiling grid opening 8 9 10 11 12 13 14 15 16 Order code Product Type FKD Connection dim. FKD aaa Materials and finish Material: Steel Standard finish: Powder-coated Standard colour: RAL 9010 white 17 Ø160-630 Example: FKD-200 The diffuser is available in other colours. Please contact Lindab’s sales department for further information. We reserve the right to make changes without prior notice 18 327 lindab | ceil ing di ffusers - visi ble Multi-cone diffuser FKD Accessories 1 2 Dispersal patterns Plenum box MBB FKD is supplied for vertical supply air as standard. The dispersal pattern can be altered to horizontal supply air by setting the inner part of the diffuser to its lowest position. 3 E 4 FKD + MBB LxB 10 6 7 C Ød1 10 Ød2 8 F 9 E FKD + MBB Duct FKD B Ød1 mm Ød2 mm mm 10 11 12 13 14 15 C mm E 328 L mm 160 260 159 216 50 195 - 235 310 160 310 184 262 50 220 - 260 376 125 200 310 184 262 50 236 - 276 376 160 160 380 220 323 50 255 - 295 459 160 200 380 220 323 50 270 - 310 459 160 250 380 220 323 50 286 - 326 459 200 200 460 259 396 70 361 - 401 565 200 250 460 259 396 70 327 - 367 565 200 315 460 259 396 70 345 - 385 565 250 250 540 309 486 70 377 - 417 698 250 315 540 309 486 70 395 - 435 698 250 400 540 309 486 70 426 - 466 698 315 315 540 373 646 70 460 - 500 858 315 400 540 373 646 70 491 - 531 858 Order code MBB MBB Duct connection Diffuser dimension 18 H mm 125 Ø100-315 17 F mm mm 100 Product Type 16 H 5 Ø160-400 Functional use S = Supply air E = Exhaust Example: FKD 200+MBB-160-200-S We reserve the right to make changes without prior notice aaa bbb c l indab | ceiling diff users - visible Multi-cone diffuser Technical data FKD Horizontal 1 Capacity Air flow qv [l/s] and [m3/h], total pressure Δpt [Pa], throw l0.2 [m] and sound power level LWA [dB(A)] can be seen in the diagrams. l0.2 [m] 20 FKD 355 450 250 315 400 500 160 200 630 2 15 10 Throw l0.2 Throw l0.2 [m] can be seen in the diagram for isothermal air at a speed of 0.2 m/s. 8 7 6 3 5 4 Frequency-related sound effect level The sound effect level in the frequency band is defined as Lwok = LWA + Kok. Kok values are specified in charts beneath the diagrams on the following pages. Kok values for FKD without a box can be found in a separate supplement. 4 3 l0.2 [m] 2 qV [l/s] 40 50 60 70 80 100 150 200 300 400 500 700 5 1000 qV [m3/h] 150 200 300 500 ǻpt [Pa] FKD 100 700 160 200 900 1500 2000 250 3000 6 315 355 400 450 500 70 630 50 7 50 45 30 40 20 8 35 15 30 10 25 7 20 5 50 60 70 200 100 150 200 300 400 500 700 300 400 500 1000 700 1500 2000 1000 3000 9 LWA dB(A) qV [l/s] 2500 qV [m3/h] 1500 5000 7000 10 11 Sound attenuation Sound attenuation of the diffuser ΔL from duct to room, including end reflection, see table below. 12 FKD + MBB Duct FKD Ød1 Ød2 63 Centre frequency Hz 100 160 20 125 250 500 16 5 15 1K 2K 4K 8K 17 17 16 19 125 160 13 13 8 19 13 16 16 19 125 200 15 11 6 15 12 14 16 17 160 160 16 17 10 18 17 18 20 21 160 200 15 14 7 19 15 16 18 19 160 250 17 16 4 16 15 16 16 18 200 200 13 10 6 15 18 15 19 17 200 250 13 9 4 12 17 13 17 16 200 315 13 8 3 8 16 14 16 15 250 250 14 8 8 15 17 17 17 18 250 315 13 6 5 13 15 15 16 17 250 400 12 4 3 12 13 14 14 15 315 315 7 9 8 12 17 16 17 21 315 400 7 8 7 11 16 14 16 19 13 14 15 16 17 Balancing Balancing data is contained in a separate brochure. We reserve the right to make changes without prior notice 18 329 lindab | ceil ing di ffusers - visi ble Multi-cone diffuser FKD Technical data 1 2 3 4 Throw l0.2 / turning point l0.0 Throws l0.2[m] can be seen in the diagrams for isothermal air at a speed of 0.2 m/s. Turning point l0.0 [m] can be seen in the diagrams for heated air, +5 K, +10 K respectively. Vertical Vertical supply air correction sound power level (LWA) and pressure loss (Δpt) On the following pages you can find diagrams for all sizes FKD+MBB horizontal supply air. When Vertical supply air values are wanted, use the correction factors in the table below. FKD + MBB ǻpt [Pa] FKD 150 160 200 250 315 355 400 450 500 100 630 5 70 50 50 45 30 6 40 20 35 15 30 25 10 7 20 7 LWA dB(A) 5 30 70 150 200 8 9 40 50 L;M= 100 150 200 300 500 & +$ISOTERM 700 qV [l/s] 500 700 1000 2000 qV [m3/h] 2000 3000 5000 7000 300 1000 Vertical supply air Duct FKD Ød1 Ød2 LWA Correction factor Δpt 100 160 3 x 1,2 125 160 1 x 1,2 125 200 1 x 1,1 160 160 5 x 1,5 160 200 3 x 1,3 160 250 0 x 1,1 200 200 1 x 1,3 200 250 5 x 1,2 200 315 0 x 1,1 250 250 1 x 1,3 250 315 2 x 1,3 250 400 1 x 1,1 315 315 4 x 1,4 315 400 3 x 1,2 10 11 12 L;M= Q6 ;LS= 13 14 l0.0 [m] 20 FKD +5K 160 200 Q6 ;MH= 250 315 355 400 450 15 l0.0 [m] 20 FKD +10K 160 200 250 315 15 355 400 450 10 500 500 15 16 17 10 630 7 6 5 7 6 5 4 4 3 3 2 2 330 l0.0 [m] l0.0 [m] 1 30 18 630 40 150 50 60 70 200 100 300 150 500 200 700 300 1000 qV [l/s] 500 700 1000 qV [m3/h] 1500 2000 3000 1 30 40 150 50 60 70 200 100 300 We reserve the right to make changes without prior notice 150 500 200 700 300 1000 500 1500 2000 qV [l/s] 1000 qV [m3/h] 3000 700 l indab | ceiling diff users - visible Multi-cone diffuser FKD Technical data FKD 160 + MBB Horizontal FKD 200 + MBB Horizontal ǻpt [Pa] FKD-160+MBB-160-160-S 250 ǻpt [Pa] FKD-200+MBB-200-200-S 250 200 200 150 150 100 40 LWA dB(A) 10 30 40 25 15 20 50 150 60 70 200 80 100 300 120 400 140 500 qV [l/s] 160 qV [m3/h] 4 30 20 25 15 40 35 30 30 20 3 45 50 35 30 50 70 45 50 2 100 50 70 1 LWA dB(A) 20 10 50 60 70 80 200 100 300 120 140 400 160 500 5 qV [l/s] 240 qV [m3/h] 180 200 700 6 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K Kok 11 7 0 -6 -4 -9 -22 -31 Kok 13 5 -2 -5 -3 -12 -22 -28 7 ǻpt [Pa] FKD-160+MBB-125-160-S ǻpt [Pa] FKD-200+MBB-160-200-S 250 250 200 200 150 8 150 50 100 45 70 35 30 30 25 20 15 LWA dB(A) 10 20 25 30 80 30 40 100 50 150 60 70 80 200 100 300 qV [l/s] 120 qV [m3/h] 400 10 25 20 20 15 9 40 50 35 30 45 70 40 50 50 100 20 LWA dB(A) 10 30 40 50 150 60 70 80 200 100 300 120 qV [l/s] 160 qV [m3/h] 140 400 500 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K Kok 10 5 2 -5 -5 -9 -18 -25 Kok 11 5 1 -5 -4 -11 -20 -25 200 50 150 150 45 100 30 35 25 20 20 15 15 LWA dB(A) 10 10 15 40 50 20 60 70 25 80 30 100 40 150 50 60 70 200 80 300 qV [l/s] 100 qV [m3/h] 15 30 30 20 20 40 50 25 30 14 45 70 35 50 50 100 40 70 12 13 ǻpt [Pa] FKD-200+MBB-125-200-S 250 200 ǻpt [Pa] FKD-160+MBB-100-160-S 250 11 LWA dB(A) 10 20 25 80 30 40 100 50 150 60 70 200 80 300 100 120 400 qV [l/s] 140 qV [m3/h] 500 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K Kok 9 4 2 -3 -5 -9 -16 -22 Kok 11 4 1 -4 -4 -10 -16 -23 We reserve the right to make changes without prior notice 16 17 18 331 lindab | ceil ing di ffusers - visi ble Multi-cone diffuser FKD Technical data 1 2 3 FKD 250 + MBB Horizontal FKD 315 + MBB Horizontal ǻpt [Pa] FKD-250+MBB-250-250-S 250 ǻpt [Pa] FKD-315+MBB-315-315-S 250 200 200 150 150 100 100 50 70 50 50 70 45 45 50 40 40 4 30 50 60 70 200 80 100 120 300 25 15 LWA dB(A) 20 10 30 20 25 15 5 30 35 30 20 35 140 400 160 180 200 500 240 700 280 1000 qV [l/s] 20 LWA dB(A) 10 50 qV [m3/h] 60 70 200 80 90 100 300 150 400 500 200 250 qV [l/s] 350 400 qV [m3/h] 1250 300 700 6 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K Kok 12 5 -2 -4 -3 -13 -20 -26 Kok 14 3 0 -2 -4 -14 -20 -26 7 8 ǻpt [Pa] FKD-250+MBB-200-250-S 250 ǻpt [Pa] FKD-315+MBB-250-315-S 250 200 200 150 150 100 9 100 50 70 70 45 40 50 50 45 50 40 35 30 10 30 30 25 20 50 70 80 200 12 13 60 100 300 120 140 400 160 500 700 60 70 200 80 90 100 300 150 400 500 200 250 qV [l/s] 350 400 qV [m3/h] 1250 300 700 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K 5 -2 -3 -3 -12 -19 -24 Kok 12 5 -1 -2 -4 -12 -19 -21 ǻpt [Pa] FKD-250+MBB-160-250-S 250 ǻpt [Pa] FKD-315+MBB-200-315-S 250 200 200 50 100 35 30 30 25 15 LWA dB(A) 10 50 150 17 60 30 25 20 20 40 40 50 35 15 50 45 70 40 30 150 100 45 30 332 50 11 20 18 LWA dB(A) Kok 50 16 20 10 Hz 70 15 qV [l/s] 240 qV [m3/h] 180 200 150 14 25 15 LWA dB(A) 10 11 30 20 20 15 35 70 80 200 100 300 120 400 qV [l/s] 140 160 180 qV [m3/h] 500 20 LWA dB(A) 10 50 60 70 200 80 100 300 120 400 140 160 180 200 500 240 700 280 1000 Hz 63 125 250 500 1K 2K 4K 8K Hz 63 125 250 500 1K 2K 4K 8K Kok 12 4 0 -3 -4 -12 -18 -24 Kok 9 5 -1 -2 -5 -11 -18 -24 We reserve the right to make changes without prior notice qV [l/s] qV [m3/h] l indab | ceiling diff users - visible Multi-cone diffuser FKD Technical data 1 FKD 400 + MBB Horizontal ǻpt [Pa] FKD-400+MBB-315-400-S 250 2 200 150 100 50 70 3 45 50 40 35 30 4 30 20 25 15 20 LWA dB(A) 10 70 80 90 150 300 400 200 500 250 300 350 400 700 5 qV [l/s] 500 1250 1500 2000 qV [m3/h] 6 Hz 63 125 250 500 1K 2K 4K 8K Kok 11 4 1 -1 -6 -12 -17 -24 7 ǻpt [Pa] FKD-400-MBB-250-400-S 250 200 8 150 50 100 45 70 9 40 50 35 30 30 20 10 25 15 20 LWA dB(A) 10 50 60 70 200 80 90 100 300 150 400 500 200 250 300 700 qV [l/s] 350 400 qV [m3/h] 1250 Hz 63 125 250 500 1K 2K 4K 8K Kok 9 4 1 -1 -6 -12 -17 -25 11 12 13 14 15 16 17 18 We reserve the right to make changes without prior notice 333